INSTALLATION

INSTRUCTIONS

The H-10™ gate operator has the capacity to operate slide gates up to 2200 lbs. and 75 ft. in length at 100% duty cycle under extreme conditions. This effi cient operator provides a solution for high traffi c residential and commercial slide gate applications. The Viking H-10™ gate operator offers effi ciency and technology combined in a single package.

THE VIKING H-10™ SLIDE GATE OPERATOR

H-10 Vehicular Gate Operator • Revision H10NXMN10.F • February 2014

PARTS DIAGRAM:

2

Item Description

1 Chassis

2 Chassis Battery Bracket

3 Gear Box

4 Motor

5 Electronic Positioning Sensor 2 (EPS2)

6 40B17 Sprocket

7 Idler Pulley

8 Idler Bushing (w/hardware)

9 Battery Switch

10 Alarm

11 Alarm Reset Switch

12 Manual Release Switch

13 Control Board

14 Battery

15 Access Door

16 Key and Lock

17 Operator Cover

18 Modular Power Box Assembly

19 Power Box Panel Assembly

20 Toroid Transformer - 15 amp

21 120V Receptacle

22 120VAC Power Switch

23 Fuse - 4 amp

24 Fuse - 20 amp

25 25’ #40 Chain Kit, Nickle Coated

26 Motor Harness

27 Power Harness

28 Brush Kit

29 Loop Rack

DUAL10

VNXDUARS

DUMRS20

VFLEXPCB

DUBA12

VNXAD

VNXSLCL

VNXCV

VNXMPB

VNXUPBPA

DUTT15

VA120PL

DUMRS10

VNXF4A

VNXF20A

VAL3CKN

VNXH10MH

VNXL3PH

VAH10MBK

VA-LR

Part No.

VNXL3CH

VNXCHBBRK

VNXL3GB

VNXH10MO

VNXSLEPS2

VAL3SP17

DSIP10

DSIB10

DUMRS20

VIKING TECHNICAL SUPPORT 1.800.908.0884

OPERATOR REFERENCES:

2. COVER LOCK

3. ACCESS DOOR external access to the Manual Release Switch and

Alarm Reset Button

4. BATTERY BACKUP SYSTEM

5. VFLEX CONTROL BOARD

SWITCH disconnects batteries from the charging circuit during troubleshooting

7. EPS (ELECTRONIC POSITIONING SENSOR) sensor for the digital limits

8. MOTOR

RACK for convenient loop detector installation

10. GEARBOX

11. MANUAL RELEASE/MOTOR SWITCH discontinues power to the motor and allows for manual operation of the gate

RESET resets the operators alarm

13. POST MOUNTING U-BOLT HOLES for optional post mount installation

14. J-BOX high voltage power supply connection

FUSE main power supply protection

16. MODULAR POWER BOX removable; provides a convenient solution for optional low voltage installations

VIKING TECHNICAL SUPPORT 1.800.908.0884

3

CONTROL BOARD REFERENCES:

4

1. POWER HARNESS CONNECTOR provides power to the control board. pg 18-19

2. “OPEN LEFT” & “OPEN RIGHT” provides power to the motor. pg 20

3. LIMIT SETUP BUTTONS sets limit positions. pg 20-21

4. FEATURE ACTIVATION TRIM POTS activate and set features. pg 24

5. “EPS1” CONNECTOR available for future developments

6. “EPS2” CONNECTOR monitors the limit positions.

7. EMI BOARD CONNECTOR monitors the high voltage power supply.

8. “CHECK MOTOR” Status LED indicates motor power status. pg 36

9. “BATTERY LOW” Status LED

indicates battery power status. pg 36

10. “POWER” Status LED control board power status. pg 18,36

11. “MAGNETIC LOCK RELAY” Status LED status of this on-board relay. pg 34, 36

12. “MAGNETIC LOCK RELAY” Terminal Block

connect electric locks here. pg 34, 36

13. INPUT STATUS LEDs indicates input status. pg 36-37

14. ACCESS CONTROL TERMINAL BLOCKS accessory connections. pg 29-32, 42-44

15. “MASTER/SLAVE” Terminal Block wired master/slave connection. pg 22

16. CONTROL BOARD MOUNTING HOLES secures and grounds the control board.

17. “Siren” Terminal Block

Vikings UL Siren is connected here.

18. ON-BOARD 3 BUTTON STATION controls the gate during set up.

19. “AUX. PWR” Terminal Block used for solar applications & in-motion warning devices. pg 19, 25

20. FEATURE ACTIVATION PIN HEADERS activate features by placing a jumper onto the pin headers. pg 25

21. “DIAGNOSE” Button allows you to navigate through the

Diagnostics LCD Display. pg 38-40

22. “DIAGNOSE” LED informs that errors have been detected and available on LCD Display. pg 38-40

23. LCD DIAGNOSTICS DISPLAY provides error messages, diagnostics and operator status information. pg 38-40

24. EXPANSION PRODUCT CONNECTIONS connections for additional products from Viking Access Systems. pg 46

25. “FAIL SAFE/SECURE” Jumper

power failure option. pg 25

26. FUSE HOLDER - 20 AMP for motor circuit.

27. FUSE HOLDER - 4 AMP for charging circuit.

28. HEAT SINK secures the control board and dissipates heat.

VIKING TECHNICAL SUPPORT 1.800.908.0884

PARTS DIAGRAM/PARTS LIST

OPERATOR REFERENCES

CONTROL BOARD REFERENCES

Maintenance

TABLE OF CONTENTS:

3 3

2 2

8

13

14-17

MASTER/SLAVE SET UP

CONTROL BOARD SETUP

Obstruction Detection Sensor (Primary Entrapment Protection) 26

Heater, Lock Mode................................................................................................................. 27

Radio Receiver (Typical) 30

Viking Loop Rack 32

LED References 36-37

LCD Display References 38-40

42-45

VIKING EXPANSION PRODUCTS

VIKING TECHNICAL SUPPORT 1.800.908.0884

5

6

IMPORTANT SAFETY INFORMATION

!

WARNING! Not Following these instructions may cause severe injury or death.

IMPORTANT SAFETY INSTRUCTIONS

!

WARNING! To reduce the risk of severe injury or death.

1. READ AND FOLLOW ALL INSTRUCTIONS.

2. Never let children operate or play with gate controls. Keep the remote away from children.

3. Always keep people and objects away from the gate. NO ONE SHOULD

CROSS THE PATH OF THE MOVING GATE.

4. Test the gate operator monthly. The gate MUST reverse on contact with a rigid object or when an object activates the non-contact sensors. After adjusting the force or the limit travel, retest the gate operator. Failure to adjust and retest the gate operator properly can increase the risk of injury or death.

5. Use the emergency release only when the gate is not moving.

6. KEEP GATES PROPERLY MAINTAINED. Read the user’s manual. Have a qualified service person make repairs to gate hardware.

7. The entrance is for vehicles only. Pedestrians must use a separate entrance.

8. Every gate operator installation MUST have secondary protection devices against entrapment, such as edge sensors and photo beams more in particularly in places where the risk of entrapment is more likely to occur.

9. SAVE THESE INSTRUCTIONS.

IMPORTANT INSTALLATION INSTRUCTIONS

1. Install the gate operator only when: a. The operator is appropriate for the construction of the gate and usage

Class of the gate (refer to page 9), b. All openings of a horizontal slide gate are guarded or screened from the bottom of the gate to a minimum of 6 feet (1.83 m) above the ground to prevent a 2-1/4 inch (57. 2 mm) diameter sphere from passing through the openings anywhere in the gate, and in that portion of the adjacent fence that the gate covers in the open position, c. ALL EXPOSED PINCH POINTS ARE ELIMINATED OR GUARDED, AND d. GUARDING IS SUPPLIED FOR EXPOSED ROLLERS.

2. The Operator is intended for installation only on gates used for vehicles.

Pedestrians must be supplied with a separate access opening. The pedestrian access opening shall be designed to promote pedestrian usage. Locate the gate such that persons will not come into contact with the vehicular gate during the entire path of travel of the vehicular gate.

3. The gate must be installed in a location so that enough clearance is supplied between the gate and adjacent structures when opening and closing to reduce the risk of entrapment. Swinging gates shall not open in to the public access areas.

4. The gate must be properly installed and work freely in both directions prior to the installation of the gate operator. Do not over-tighten the operator clutch or pressure relief valve to compensate for a damaged gate.

5. The gate operator controls must be placed so that the user has full view of the gate area when the gate is moving AND AWAY FROM THE GATE PATH

PERIMETER.

VIKING TECHNICAL SUPPORT 1.800.908.0884

IMPORTANT SAFETY INFORMATION

!

WARNING! Not Following these instructions may cause severe injury or death.

IMPORTANT INSTALLATION INSTRUCTIONS (Continued)

6. Controls intended for user activation must be located at least six feet (6’) away from any moving part of the gate and where the user is prevented from reaching over, under, around or through the gate to operate the controls.

Exception: Emergency access controls only accessible by authorized personnel

(i.e. fire, police, EMS) may be placed at any location in the line-of-sight of the gate.

7. The Stop and/or Reset button must be located in the line-of-sight of the gate.

Activation of the reset control shall not cause the operator to start.

8. A minimum of two (2) WARNING SIGNS shall be installed, one on each side of the gate where easily visible.

9. For gate operators using non-contact sensors (Photo Beams or like) in accordance with section 31.1.1 of the UL standard: a. See instructions on the placement of non-contact sensors for each type of application (refer to page 10).

b. Care shall be exercised to reduce the risk of nuisance tripping, such as when a vehicle, trips the sensor while the gate is still moving, and c. One or more non-contact sensors shall be located where the risk of entrapment or obstruction exists, such as the perimeter reachable by a moving gate or barrier (refer to page 10).

d. Use only Omron E3K-R10K4 photoelectric eye to comply with UL 325

10. For a gate operator utilizing a contact sensor (Edge sensor or like) in accordance with section 31.1.1 of the UL 325 standard: a. One or more contact sensors shall be located where the risk of entrapment or obstruction exists, such as a the leading edge, trailing edge, and post mounted both inside and outside of a vehicular horizontal slide gate (refer to page 11).

b. One or more contact sensors shall be located at the bottom of a vehicular vertical lift gate.

c. One or more contact sensors shall be located at the pinch point of a vehicular vertical pivot gate.

d. A hardwired contact sensor shall be located and its wiring arranged so that the communication between the sensor and the gate operator is not subject to mechanical damage.

e. A wireless contact sensor such as one that transmits radio frequency

(RF) signals to the gate operator for entrapment protection functions shall be located where the transmission of the signals are not obstructed or impeded by building structures, natural landscaping or similar obstructions. A wireless contact sensor shall function under the intended end-use conditions.

f. One or more contact sensors shall be located on the inside and outside leading edge of a swing gate. Additionally, if the bottom edge of a swing gate is greater than 6 inches (152 mm) above the ground at any point in its arc of travel, one or more contact sensors shall be located at the bottom.

g. One or more contact sensors shall be located at the bottom edge of a vertical barrier (arm).

h. Only Use Miller Edge Model MGR20 or MGS20 edge sensor to comply with

UL325.

7 VIKING TECHNICAL SUPPORT 1.800.908.0884

IMPORTANT SAFETY INFORMATION

!

WARNING! Not Following these instructions may cause severe injury or death.

MAINTENANCE

Remove the Power Harness from the Control Board. (refer to page 18)

• Clean and lubricate the gate track wheels using the recommended lubricant.

• Inspect the track for any signs of cracking or separation.

• Check that all mounting hardware of the gate operator is properly tighten.

• Ensure that the gate moves freely.

• Check for corroded parts and replace if necessary.

• Check the battery for the following:

- Battery connections must be free of corrosion.

- Battery voltage must be 26VDC (fully charged battery).

Reconnect the Power Harness for the Control Board. (refer to page 18)

• Check and confirm the proper operation of all safety devices (photoelectric eye, edge sensors or like).

• Check and confirm the operation of all installed accessories.

• Check and confirm the operation of all special features such as the Intelligent

Obstruction Sensor, Hold Open Timer. (refer to page 24 and 26)

• Check and confirm the operation of the manual release. (refer to page 7)

• Verify the functionally of the battery backup, or power failure option, by turning off the main power source (115VAC or 230VAC). DO NOT FORGET TO

TURN ON THE MAIN POWER SOURCE AFTER VERIFICATION.

8

GENERAL SAFETY PRECAUTIONS

The following precautions are an integral and essential part of the product and must be supplied to the user. Read them carefully as they contain important indications for the safe installation, use and maintenance.

• These instruction must be kept and forwarded to all possible future users of the system.

• This product must be used only for that which it has been expressly designed.

• Any other use is to be considered improper and therefore dangerous.

• The manufacturer cannot be held responsible for possible damage caused by improper, erroneous or unreasonable use.

• Avoid operating in the proximity of the hinges or moving mechanical parts.

• Do not enter the path of the moving gate while in motion.

• Do not obstruct the motion of the gate as this may cause a situation of danger.

• Do not allow children to play or stay within the path of the moving gate.

• Keep remote control or any other control devices out of the reach of children, in order to avoid possible involuntary activation of the gate operator.

• In case of break down or malfunctioning of the product, disconnect from the main power source. Do not attempt to repair or intervene directly, contact only qualified personnel for repair.

• Failure to comply with the above may create a situation of danger.

• All cleaning, maintenance or repair work must be carried out by qualified personnel.

• In order to guarantee that the system works efficiently and correctly it is important to have the manufacturer’s instructions on maintenance of the gate and operator carried out by qualified personnel.

• In particular, regular checks are recommended in order to verify that the safety devices are operating correctly.

All installation, maintenance and repair work must be documented and made available to the user.

VIKING TECHNICAL SUPPORT 1.800.908.0884

IMPORTANT SAFETY INFORMATION

!

CAUTION: To Reduce the Risk of Fire or Injury to Persons: a. Use only the following type and size battery(ies): Yuasa NP7-12 or VIKING DUBA12 b. Do not dispose of the battery(ies) in fire. The cells may explode. Check with local codes for possible disposal instructions.

c. Do not open or mutilate the battery(ies). Released electrolyte is corrosive and may cause damage to the eyes or skin. It may be toxic if swallowed.

d. Exercise care in handling batteries in order not to short the battery with conducting materials such as rings, bracelets and keys.

e. Change the battery(ies) provided with or identified for use with this product only in accordance with the instructions and limitations specified in this manual.

f. Observe proper polarity orientation between the battery(ies) and charging circuit.

g. Do not mix batteries of differ ant sizes or from different manufactures in this product (applies to products employing more than one user replaceable secondary battery).

h. A battery-operated product employing a secondary battery supply intended to be charged within the product shall contain specific instructions concerning the proper method of charging.

UL325 Gate Operator Classifications

GLOSSARY

RESIDENTIAL VEHICULAR GATE OPERATOR

CLASS I - A vehicular gate operator (or system) intended for use in garages or parking areas associated with a residence of one-to four single families.

COMMERCIAL/GENERAL ACCESS VEHICULAR GATE OPERATOR

CLASS II – A vehicular gate operator (or system) intended for use in a commercial location or building such as a multi-family housing unit (five or more single family units), hotel, garages, retail store, or other building servicing the general public.

INDUSTRIAL/LIMITED ACCESS VEHICULAR GATE OPERATOR

CLASS III – A vehicular gate operator (or system) intended for use in an industrial location or building such as a factory or loading dock area or other locations not accessible by or intended to service the general public.

RESTRICTED ACCESS VEHICULAR GATE OPERATOR

CLASS IV – A vehicular gate operator (or system) intended for use in a guarded industrial location or building such as an airport security area or other restricted access locations not servicing the general public, in which unauthorized access is prevented via supervision by security personnel.

Install the gate operator only when:

The operator is appropriate for the construction of the gate and the Usage Class of the gate.

VIKING TECHNICAL SUPPORT 1.800.908.0884

9

IMPORTANT SAFETY INFORMATION

!

WARNING! Not Following these instructions may cause severe injury or death.

NOTE: This type on installation dOEs NOT reverse the gate all the way back to its limits when the photo beam is obstructed. This installation is only to protect against entrapment and to comply with UL325.

Secondary Entrapment Protection

Photo Beam (non-contact sensor) Installation

• Photo beams or like must be installed to reduce the risk of entrapment.

• Use only Omron E3K-R10K4 photoelectric eye to comply with UL325

• Make the electrical connections of the photoelectric sensor as described here in this page.

• Care shall be exercised to reduce the risk of nuisance tripping, such as when a vehicle, trips the sensor while the gate is still moving, and;

• One or more non-contact sensors shall be located where the risk of entrapment or obstruction exists, such as the perimeter reachable by a moving gate or barrier.

Consult the installation manual for the UL325 device (photo beam or like) for detail information about the usage, installation and maintenance.

1 0 VIKING TECHNICAL SUPPORT 1.800.908.0884

IMPORTANT SAFETY INFORMATION

!

WARNING! Not Following these instructions may cause severe injury or death.

NOTE: This type on installation dOEs NOT reverse the gate all the way back to its limits when the edge sensor is obstructed. This installation is only to protect against entrapment and to comply with UL325.

Secondary Entrapment Protection

Edge Sensor (contact sensor) Installation

• Edge Sensors or like must be installed to reduce the risk of entrapment.

• Use only Miller Edge 3-sided activation type MGR20 or MGS20 to comply with

UL325

• One or more contact sensors shall be located on the inside and outside leading edge of a swing gate. Additionally, if the bottom edge of a swing gate is greater than 6 inches (152 mm) above the ground at any point in its arc of travel, one or more contact sensors shall be located on the bottom edge.

1. A hardwired contact sensor shall be located and its wiring arranged so that the communication between the sensor and the gate operator is not subjected to mechanical damage.

2. A wireless contact sensor such as one that transmits radio frequency (RF) signals to the gate operator for entrapment protection functions shall be located where the transmission of the signals are not obstructed or impeded by building structures, natural landscaping or similar obstruction. A wireless contact sensor shall function under the intended end-use conditions.

Manual Release

When manual operation is required:

1. Lift the Access Door, located on the front of the cover.

2. Press the Manual Release Switch to the “RELEASE” Position.

The gate can now be moved manually.

To resume normal operation, press the switch to the “ENGAGE” position.

VIKING TECHNICAL SUPPORT 1.800.908.0884

1 1

IMPORTANT SAFETY INFORMATION

!

WARNING! Not Following these instructions may cause severe injury or death.

Audible Alarm Reset Switch Installation

Manual Reset for the Audible Alarm

• UL325 standard requires an audible alarm to sound after two consecutive events detected by the primary entrapment protection of the gate operator (obstruction sensor).

• The audible alarm will continue to sound for 5 minutes or until a stop command gets actuated.

• The Stop command can be actuated in three different forms:

1. Using the Built in Stop switch on the Control Board or;

2. Using an External Stop button within the sight of the gate, away from moving parts of the gate and out of reach of children.

a. Controls intended for user activation must be located at least six feet (6’) away from any moving part of the gate and where the user is prevented from reaching over, under, around or through the gate to operate the controls.

Outdoor or easily accessible controls shall have a security feature to prevent unauthorized use.

b. The Stop and/or Reset button must be located in the line-of-sight of the gate.

Activation of the reset control shall not cause the operator to start.

3. Using the “Alarm Reset” Button on the operator that is externally accessible from the covers Access Door.

3

2

Warning Placard Installation

• All Warning Placards must be installed where visible in the area of the gate.

• A minimum of two placards shall be installed.

• A placard is to be installed in the area of each side of the gate and be visible.

1 2 VIKING TECHNICAL SUPPORT 1.800.908.0884

IMPORTANT INSTALLATION INFORMATION

!

CAUTION: To Reduce the Risk of Fire or Injury to Persons:

!

WARNING: For use with gates at a maximum 2200 lbs. in weight or 75 ft. in length.

DO NOT allow pedestrian use of this gate

Locate Control Buttons:

1. Within sight of the gate,

2. At a minimum height of 5 feet so small children are not able to reach it; and

3. At least 6 feet away from all moving parts of the gate.

DO NOT install the gate operator to lift gates

75 ft

2200 lb.

Specifications:

Maximum Gate Length:

Maximum Gate Weight:

Operating Temperature:

Power Requirements:

Alternative Power

75 ft.

2200 lb.

-20°F (-28°C) to 160°F (71°C)

115VAC / 230 VAC (6.0* Amp / 1.0 Amp)

*Includes 3 amp load on receptacle

Single Phase (50 Hz / 60 Hz)

24VAC / VDC (60VA) or Solar

VIKING TECHNICAL SUPPORT 1.800.908.0884

1 3

GATE OPERATOR INSTALLATION

Concrete Pad Option

1. Follow the local building code to determine the required depth of the concrete pad.

2. Pad measurements recommended by Viking Access Systems are at least

24” long, 18” wide and 24” deep to ensure the stable operation of the operator, and a minimum of 4” above level grade to avoid any flooding of the machinery.

3. Provide a sufficient number of conduit pathways for all low power accessories such as loop detector leads, maglock, non-contact sensors, contact sensors, safety and other commands. Also provide conduit for the power supply to the operator.

!

DO NOT run low voltage and high voltage wiring in the same conduit.

!

Provide at least 12” separation between low and high voltage conduits.

1 4 VIKING TECHNICAL SUPPORT 1.800.908.0884

GATE OPERATOR INSTALLATION

Post Mounting Option

TIP:

The operator is equipped for post mount applications and is ready for installation.

You will only need to supply the posts and u-bolts.

1. Consult the local building codes for the depth and concrete requirements.

2. Maximum 3.00” OD pipe.

3. Provide a sufficient number of conduit pathways for all low power accessories such as loop detector leads, maglock, non-contact sensors, contact sensors, safety and other commands. Also provide conduit for the power supply to the operator.

!

DO NOT run low voltage and high voltage wiring in the same conduit.

!

Provide at least 12” separation between low and high voltage conduits.

VIKING TECHNICAL SUPPORT 1.800.908.0884

1 5

GATE OPERATOR INSTALLATION

Operator Positioning

!

IMPORTANT: All openings of a horizontal slide gate are guarded or screened from the bottom of the gate to a minimum of 4 feet (1.22 m) above the ground to prevent a 2-1/2 inch

(57.2 mm) diameter sphere from passing through the openings anywhere in the gate, and in that portion of the adjacent fence that the gate covers in the open position.

1 6 VIKING TECHNICAL SUPPORT 1.800.908.0884

GATE OPERATOR INSTALLATION

!

TECHNICAL TIP:

Before completing the installation procedure;

• Open and close the gate manually, making sure there is sufficient space between the gate and adjacent walls.

• Check that the wheels are turning freely on the track and there are no restrictions while pushing the gate to the open and closed positions.

• Confirm that there is adequate spacing for the guide rollers and that there are no restrictions throughout the travel of the gate.

STEP 1

Before securing the chassis to the concrete pad or posts, make sure the gate and operator are LEVEL and

PARALLEL. Minimum distance between the operator and gate is 3”.

STEP 2

Chain Installation: Before welding the provided chain brackets, make sure the chain will be in a straight line with, and at the same height as, the chain leaving the gate operator rollers.

14.375"

1 7 VIKING TECHNICAL SUPPORT 1.800.908.0884

ELECTRICAL INSTALLATION

High Voltage Supply Option

!

Caution:

Always turn off power breakers when working with high voltage. DO NOT connect the “Power Harness” to the Control Board until the electrical installation is complete and ready for verification.

STEP 1

At the “Power Box”: a. Set the “Voltage Selector” according to the supply voltage (115V or 230V).

b. Turn the “AC Power” switch ON

STEP 2

!

WARNING:

SINGLE PHASE AC ONLY

At the “J-Box”: a. Connect the incoming power wires, matching the wire color codes.

b. If the supply voltage is 120VAC, connect the red wire, labeled “Outlet

Power”, to the neutral (white) wires.

1a

3b

1b

2a

STEP 3

a. Turn ON the main facility breaker b. Verify that all three (3) LEDs are illuminated at the “Power Box”.

c. Turn the “Battery Switch” ON.

At the Control Board: d. Connect the Power Harness and verify the “POWER” LED is illuminated solid.

3c

3d

!

TECHNICAL TIP:

If the “Power” LED is flashing or any of the 3 LEDs on the

“Power Box” are not illuminated, refer to the Troubleshooting pages.

Tips for proper ground installation:

To minimize the effects caused by lightning, follow these guidelines.

• Use a ground rod to provide a ground reference.

• Consult your city code and be aware of under-ground services in the site of the gate operator to prevent inconveniences.

• Always use a single bonding point for grounding.

• All ground wires must be as short and as thick as possible.

• Prevent unnecessary turns or loops in all ground wires.

1 8 VIKING TECHNICAL SUPPORT 1.800.908.0884

ELECTRICAL INSTALLATION

Low Voltage Supply Option

TIP:

The operator is equipped with a Modular Power Box that can be relocated to provide power for low voltage installations. Supplies 24VAC to the operator.

!

Caution:

Always turn off power breakers when working with high voltage. DO NOT connect the “Power Harness” to the Control Board until the electrical installation is complete and ready for verification.

Remove the “Power Box” from the operators chassis and relocate to the nearest high voltage source (115V or 230V single phase AC). Follow local codes or guidelines.

MAXIMUM DISTANCE:

400 ft. with 10 AWG wire

Solar Supply Option

Vikings Solar Package ( part # VA-SOCHP) is an efficient and effective solution to powering the operator with solar energy. (See page 46 for package details)

!

Tip:

Solar efficiency can be increased by activating the “Pre-Warning” A will provide 24VDC to all nonessential controls, beginning 3 seconds prior to gate movement, until the gate reaches either limit. (page 25)

A

B

Connect the two panels in series.

Connect the batteries in series.

Disconnect the operators power harness and use the

Solar Harness.

!

IMPORTANT:

The number of cycles achieved daily is dependent on many factors, including local solar radiation data and power consumption of the motor and accessories. It is very important that you consider this when using solar power.

VIKING TECHNICAL SUPPORT 1.800.908.0884

1 9

LIMITS SETUP

! IMPORTANT:

In the event of a complete power failure, including battery backup, the limits positions may have been cleared and will need to be reset by following the steps below.

STEP 1

Connect the “Motor Harness” to the

Control Board.

a. “OPEN RIGHT” Connector if the gate opens to the Right, when viewed from inside.

b. “OPEN LEFT” Connector if the gate opens to the Left, when viewed from inside.

1a 1b

STEP 2

Move the gate to the desired open position then press and hold the “Open

Limit” button until the LED stops flashing and illuminates solid.

STEP 3

Move the gate to the desired close position then press and hold the “Close

Limit” button until the LED stops flashing and illuminates solid.

“Open Limit” LED flashes if the open limit is not set.

“Close Limit” LED flashes if the close limit is not set

Tip:

The gate can be moved electronically with the “Open”, “Stop” and “Close” buttons on the Control Board or manually by following the instructions on page 11.

2 0 VIKING TECHNICAL SUPPORT 1.800.908.0884

LIMITS SETUP

! NOTE:

1. The 1st cycle after the limit setup is the “Learn Cycle”. Allow a complete cycle to confirm your settings.

2. During the limit setup process, the operator will run at half speed.

Open Limit Close Limit

To Readjust the Open Limit:

1. Clear the current limit setting by holding down the “Open Limit” button until the LED is flashing.

2. Repeat STEP 2 on page 20 to set the limit.

To Readjust the Close Limit:

1. Clear the current limit setting by holding down the “Close Limit” button until the LED is flashing.

2. Repeat STEP 3 on page 20 to set the limit.

VIKING TECHNICAL SUPPORT 1.800.908.0884

2 1

MASTER/SLAVE SETUP

Two Wire Communication

!

IMPORTANT:

DO NOT run the Master/Slave communication cable in the same conduit or within 12” of 115 - 230V power supply cables.

!

Technical Tip:

DO NOT set the “Timer” and/or “Overlap” features on both operators

Control Boards. Only turn these features on at the Master Control Board.

CABLE REQUIREMENTS:

• 2 Conductor (wire)

• 18 AWG or better

• Shielded (overall foil)

• Drain Wire (non-insulated or bare wire)

2 2

Shielded Cable

Master Board

“MS1”

“MS2”

Condui t

Drain Wire

Slave Board

“MS1”

“MS2”

Conduit between

Master and Slave

VIKING TECHNICAL SUPPORT 1.800.908.0884

MASTER/SLAVE SETUP

Wireless Communication Options

!

Technical Tip:

DO NOT set the “Timer” and/or “Overlap” features on both operators

Control Boards. Only turn these features on at the Master Control Board.

REQUIRED ADD-ON:

Choose option A or B

A. Viking Konnect - Wireless Master/Slave Kit

PART# VA-KONNECT-MS

B. Viking Blue - Wireless Master/Slave Kit

PART# VA-BLUE-MSKT

Connect the Modules provided to the “V.K” plug & play connection of each operators

Control Board. It is not important which board the master or slave module is placed on.

VIKING TECHNICAL SUPPORT 1.800.908.0884

Green LEDs will be illuminated solid when communication is ON.

2 3

CONTROL BOARD SETUP

Initial Settings

“Timer”

Hold Open Timer

Automatically closes the gate after the selected amount of time from 1-60 seconds.

Turning the dial between “0” and “OFF” will disable this feature, requiring a close command to close the gate.

“Overlap”

Overlap Delay

Delays the gate from opening for the selected amount of time from 1-6 seconds.

!

Typically not used on slide gates. For

Master/Slave application, the control board that has this feature turned on is the master and will close first.

2 4

“ODS”

Obstruction Detection Sensor

Sets the amount of force required to trip the inherent obstruction sensor.

See page 26 for more details about this feature.

“Speed”

Motor Speed

Increases or decreases the speed of gate travel.

VIKING TECHNICAL SUPPORT 1.800.908.0884

CONTROL BOARD SETUP

Initial Settings

NOTE:

Installing a shunt or jumper on the pins will activate the feature.

“Fail Safe/Secure”

During complete power failure, including battery power; determines the force required to manually move the gate.

• Fail Safe Mode:

By removing the wirejumper plug from the “Fail

Safe/Secure” connector:

The gate can move manually with a relatively low amount of force.

• Fail Secure Mode:

By inserting the wirejumper plug into the “Fail

Safe/Secure” connector:

The gate will not move manually.

“Auto Open” - Power Failure Option

Opens the gate automatically during power failure. Resumes normal operation when power is restored.

“Last Open” - Power Failure Option

Opens the gate automatically when the battery backup voltage is critically low.

“Pre-Warning”

Initiates two options for an audio or visual warning, 3 seconds prior to gate motion, and will continue:

1. Until gate reaches closed limit:

“Magnetic Lock” terminals provide a contact between “COM” and “N.O.”.

2. Until gate reaches either limit:

“AUX. PWR” terminals provide 24VDC.

“Sync”

Used only in conjunction with the Viking Barrier gate operator model

B-12. Activating this feature allows for synchronized operation with the B-12 operator. See page 35.

“EXT”

Available for future developments.

!

IMPORTANT:

Regardless of the power failure options chosen, the gate can be moved manually with a relatively low amount of force by following the steps for “Manual

Release” as outlined at on page 11.

VIKING TECHNICAL SUPPORT 1.800.908.0884

2 5

2 6

CONTROL BOARD SETUP

Obstruction Sensor (Primary Entrapment Protection)

!

IMPORTANT:

The appropriate “ODS” setting is dependant upon the gate installation and construction. Set this feature accordingly. Additional Safety equipment should be used to reduce possible risk of injury or vehicle damage.

“ODS” Obstruction Detection Sensor

The Obstruction Sensor detects obstructions in the path of the traveling gate. The dial sets the amount of force required to activate the operators inherent obstruction detection.

Setting the dial to “0” will require the least amount of force to activate;

Setting the dial to “100” will require the maximum amount of force to activate.

UL325 standard requires an audio alarm to go off after two consecutive entrapment events sensed by the

Inherent Entrapment Protection of the

Gate Operator.

The audio alarm will sound for a period of 5 minutes or until a Stop command or the “Alarm Reset” switch has been actuated. (refer to page 12)

When the Obstruction Sensor detects an obstruction it will:

1. Stop the gate’s movement and reverse it momentarily.

2. Bring the gate to a resting position.

3. Disable the Hold Open Timer feature until the Gate Operator receives a new command.

If second obstruction is detected before the gate reaches either limit it will:

1. Stop the gate’s movement.

2. Disable the Gate Operator.

3. Sound the UL Alarm

4. A STOP command must be provided to disable the alarm and continue operation.

!

TECHNICAL TIP:

The Status LED for the

“ODS” will indicate the following when it has been triggered.

A. Solid: Obstruction.

Detected a sudden or abrupt increase in gate resistance.

B. Flashing: Overload.

Detected a more subtle, but sustained increase in gate resistance.

VIKING TECHNICAL SUPPORT 1.800.908.0884

CONTROL BOARD SETUP

Viking Heater

The operator has an integrated heater that is thermostatically controlled. Activate this feature when the operator is used in application temperatures down to -20°F (-29°C).

To set the heater to turn on at the Close Limit:

1. Use the “Diagnose” button to scroll through the LCD

Display to “HEATER CLS”

2. Press and hold the “Stop” button on the control board.

3. Press and release the “Diagnose” button to turn this feature ON and OFF.

HEATER

CLS ON

To set the heater to turn on at the Open Limit:

1. Use the “Diagnose” button to scroll through the LCD

Display to “HEATER OPN”

2. Perform steps 2-3 as described above.

HEATER

OPN ON

NOTE:

If the application requires the gate to be held open for any reason, set the HEATER

ON for both limit positions.

!

IMPORTANT:

A POSITIVE STOP must be used on the gate at the limit position(s) the

HEATER has been set for.

Viking Lock Mode

Turning this feature ON will secure the gate at the closed position, preventing unauthorized manual entry.

Use the LCD Display to activate this feature.

1. Use the “Diagnose” button to scroll through the LCD menu to “LOCK MOD”

2. Press and hold the “Stop” button on the control board.

3. Press and release the “Diagnose” button to turn this feature ON and OFF.

LOCK MOD

ON

2 7 VIKING TECHNICAL SUPPORT 1.800.908.0884

(THIS PAGE LEFT BLANK INTENTIONALLY)

2 8 VIKING TECHNICAL SUPPORT 1.800.908.0884

ACCESSORY CONNECTIONS

Re-Open Photo Beam (vehicular Safety)

NOTE:

This type of photo-beam installation will stop then RE-OPEN the gate all the way to the open limit when the beam is obstructed. Intended for vehicular safety ONLY. For the purpose of pedestrian entrapment, see pages 10-11.

N.O.

COM

( - ) ( + )

Note regarding Photo Beam types:

Fail-Safe type - connect the “N.C.” terminal of the photo beam to the

“Re-Open” terminal on the control board.

Typically, these are the reflective type photo beams.

Fail -Secure type - connect the “N.O.” terminal of the photo beam to the

“Re-Open” terminal on the control board.

Typically, these are the transmitter/ receiver type photo beams.

Check for proper operation:

The “Re-Open” LED will illuminate solid while the beam is obstructed and remain off when the beam is unobstructed.

!

TECHNICAL TIP:

For more information regarding accessory connections to the control board and individual input terminal functions, refer to

“Appendix (A)”, pages 42-43.

VIKING TECHNICAL SUPPORT 1.800.908.0884

2 9

ACCESSORY CONNECTIONS

Radio Receiver (Typical)

!

IMPORTANT:

The Hold Open “Timer” setting (page 24) affects how the gate will respond to the radio receiver command.

COM

N.O.

( )

(+)

The control board provides two modes of operation that a radio receiver can control the gate:

Open-Stop-Close

1. By having the radio receiver connected as illustrated and with the Hold Open

Timer OFF (see page 24):

Every command of the radio transmitter will control the gate as follows: a. First command opens the gate, b. Second command stops the gate and c. Third command closes the gate d. Any subsequent commands will continue in the same order to control the gate.

This type of configuration is not recommended for commercial installations.

Open Only

2. By having the radio receiver connected as illustrated and with the Hold Open

Timer ON (see page 24):

Each command of the radio transmitter is

ALWAYS AN OPEN COMMAND

to the gate.

For maximum reception range:

Locate the radio antenna to the top of the gate column.

!

TECHNICAL TIP:

For more information regarding accessory connections and terminal functions, refer to

“Appendix (A)” on pages 42-43.

See “Appendix (B)” on page 44 for connecting common radio receiver models.

3 0 VIKING TECHNICAL SUPPORT 1.800.908.0884

ACCESSORY CONNECTIONS

Anti-Tailgate, Open Commands & Guard Station

!

TECHNICAL TIP:

For more information regarding accessory connections and terminal functions, refer to “Appendix (A)” on pages 42-43.

Open Commands

“Exit”, “Fire” and “Strike” input terminals all provide an open command to the control board. Any device connected as shown will open the gate.

+

+ -

+

-

N.O.

COM

N.O.

COM

N.O.

COM

Guard Station

!

All three buttons must be a

Normally Open “N.O.” type of switch, and can share the same common “C” connection to “GND”.

“ATG” Anti-Tailgate

This input will stop the gate when the vehicle triggers the sensor, then closes the gate when the vehicle leaves the sensor, preventing unauthorized vehicles from entry.

+ -

COM

N.O.

3 1 VIKING TECHNICAL SUPPORT 1.800.908.0884

ACCESSORY CONNECTIONS

Viking Loop Rack

TIP:

This operator may be equipped with a pre-wired Loop Rack that plug-in type loop detectors can be connected to. This provides a convenient alternative to the box type loop detectors that would need to be wired to the control board. Viking does not provide either type of loop detectors.

Loop Rack Wiring Harness: Part # VA-LRH

3 2 VIKING TECHNICAL SUPPORT 1.800.908.0884

ACCESSORY CONNECTIONS

Guidelines for Loop Installation

1. Prevent sharp corners in the geometry of the loop sensor.

2. Install the appropriate number of turns for your loop geometry based on the loop perimeter. Use Table C (below) as a guide.

3. Use XLP (cross-linked-polyethylene) type of wire. This wire reduces the effects of moisture and other environmental events in altering the functionality of the vehicular loop detector.

4. Twist the lead wire at least 6 turns per foot.

5. Use BACKER-ROD to minimize damage to the loop detector wire prior to using the sealant.

6. Place the loop detector wire and adjust the sensitivity of the vehicular loop detector unit in a way to minimize the effects of the gate over the loop detector wire.

!

IMPORTANT!

Some of the following parameters may affect the proper functionality of the vehicular loop detector.

Consult the manufacturer of the vehicular loop detector and/or loop wire.

• Gate size

• Number of turns in the loop sensor wire

• Distance of the loop sensor wire to the gate at either at the open or close position

Table C - Recommended Number of Turns

Perimeter (ft.) Number of Turns

50-100 2

VIKING TECHNICAL SUPPORT 1.800.908.0884

Dimension “A” - 5’ for Single Gate

6’ for Dual Gate

3 3

3 4

ACCESSORY CONNECTIONS

Magnetic Lock, Lock Solenoid

NOTE:

Viking Access Systems does not provide external gate lock devices. These items can be purchased from your dealer or distributor.

Magnetic Lock

( + )

( + )

Power for the Locks:

Do not use the 24VDC power supplied by the control board. An external power supply, or plug-in transformer, must be used for the magnetic lock or lock solenoid. Plug the transformer into the

“120VAC” receptacle provided at the operators Power Box. This will prevent rapid drainage of the battery in the event of power failure.

The control boards “Magnetic Lock” relay is rated for 10A-250VAC.

!

TECHNICAL TIP:

The Magnetic Lock Relay

LED will indicate status of the on-board relay even if a lock is not connected to the control board. Refer to page 36.

Lock Solenoid

( + )

( + )

VIKING TECHNICAL SUPPORT 1.800.908.0884

SYNCHRONIZATION WITH B-12

Barrier Arm (B-12) Synchronization Option

NOTE:

The Control Board provides a convenient solution for applications that require synchronized operation with the Viking Barrier Arm Operator model B-12.

This type of application opens and closes in the following pattern:

1. Open Command is provided only to the Viking B-12 Barrier Arm Operator.

2. The Barrier Arm will delay to open until this Gate Operator reaches its Open Limit.

3. The Gate Operator will delay to close until the Barrier Arm reaches its Close Limit.

STEP 1

(Figure A & B)

Connect the Gate Operator to the Viking

B-12 Barrier Arm Operator as illustrated.

STEP 3

(Figure B)

On the Gate Operator Control Board, activate Sync Mode by placing a jumper on to the pin headers labeled “SYNC”.

Figure A

1

STEP 2

(Figure A)

At the B-12 Barrier Arm Operator, connect the primary device that will be used as the OPEN input.

Figure B

2

STEP 4

(Figure C & D)

Connect Viking B-12 Barrier Arm

Operator to the Gate Operator as illustrated.

Figure C

Figure D

4

VIKING TECHNICAL SUPPORT 1.800.908.0884

3

3 5

TROUBLESHOOTING

LED References

In addition to the LCD Display, the control board LEDs monitor the various circuits of the control board. Use the table below to identify the corresponding “TS Ref#” and refer to page 38-41 for further troubleshooting.

3 6

# LED

1 “Magnetic

Lock Relay”

Status

OFF

SOLID

2 “Check Motor” OFF

SOLID

3 “Battery Low” OFF

SOLID

Meaning

At Closed Limit and Magnetic Lock Relay state is closed across “COM” &

“N.C.”. (pg 34). Gate should be at the Close Limit.

Not at Closed Limit and Magnetic Lock Relay state is closed across “COM” &

“N.O.”. (pg 34). Gate should not be at the Close Limit

Normal Condition.

Page 41

TS Ref#(s)

The control board is sending power to the motor but the circuit is open.

7, 8

Normal Condition.

Batteries are low. Check power supply to the operator. (pg 18-19).

FLASHING Batteries critically low. Check power supply to the operator. (pg 18-19).

1, 2

1, 2

4 “POWER” SOLID Normal Condition.

FLASHING Operator is running on batteries only (pg 18-19).

OFF No power to control board.

1, 2

1, 2, 4, 5

5 “Radio” OFF Normal Condition.

SOLID

6 “UL”

7 “Re-Open”

8 “ATG”

OFF

SOLID

OFF

SOLID

OFF

SOLID

Control Board is receiving an input from a device connected to the

Radio terminal (pg 30, 42).

Normal Condition.

Control Board is receiving an input from a device connected to the UL terminal (pg 12-13, 42).

Normal Condition.

Control Board is receiving an input from a device connected to the Re-

Open terminal (pg 29, 32, 42).

Normal Condition.

Control Board is receiving an input from a device connected to the ATG terminal (pg 31, 42).

9, 10

9, 10

9, 10

9, 10

VIKING TECHNICAL SUPPORT 1.800.908.0884

TROUBLESHOOTING

LED References

Use the table below to identify the corresponding “TS Ref#” and refer to page 38-41 for further troubleshooting.

Pg 41

# LED Status Meaning TS Ref#(s)

9 “C Loop” OFF Normal Condition.

10 “Open”

11 “STOP”

12 “Close”

13 “Siren”

14 “Aux. Pwr”

15 “Diagnose”

16 “Close Limit”

17 “Open Limit”

SOLID Control Board is receiving an input from a device connected to the

C Loop terminal (pg 32, 42).

Normal Condition.

OFF

SOLID

OFF

SOLID

Control board is receiving an input from a device connected to any of the following input terminals: Exit, Fire, Strike or Open (pg 31, 42).

Normal Condition.

Control Board is receiving an input from a device connected to the

Stop terminal (pg 31, 42).

Normal Condition.

OFF

SOLID Control Board is receiving an input from a device connected to the

Close terminal (pg 31, 42).

Normal Condition.

OFF

SOLID Second consecutive obstruction has been detected. (pg 26).

FLASHING Batteries are critically low.

9, 10

9, 10

9, 10

9, 10

11, 13, 1, 2

1, 2

OFF No voltage output on these terminals at the moment.

SOLID

OFF

There is 24VDC output on these terminals at the moment.

Normal Condition.

FLASHING Errors have been detected; Check LCD Display for ERR messages (pg 40).

OFF Gate is not at the close limit position.

SOLID Gate is at the close limit position.

FLASHING Close limit position has been erased or not set (pg 20-21).

OFF

SOLID

Gate is not at the open limit position.

Gate is at the open limit position.

6

18 “ODS”

19 “Timer”

FLASHING Open limit position has been erased or not set (pg 20-21).

OFF Normal Condition.

SOLID Obstruction has been detected. (pg 26).

FLASHING Overload has been detected. (pg 26).

OFF

SOLID

The close timer is turned OFF or gate is not at the open limit if the timer is turned ON. (pg 24).

Gate is at Open Limit, Timer is turned ON and counting down to close. (pg

24).

FLASHING Gate is at Open Limit, Timer is turned ON but is not timing out due to a conflicting command. (pg 24).

SOLID Normal Condition.

6

11, 13, 1, 2

11, 13, 1, 2

9, 10

20 “AC VOLTAGE INPUT”

OFF

21 “PROTECTION WORKING” SOLID

Incoming power to Power Supply Panel Assembly is not sufficient.(pg 18).

Normal Condition.

1

OFF

22 “AC VOLTAGE OUTPUT” SOLID

23 “AC POWER”

OFF

SOLID

OFF

EMI Board is damaged and circuit is not protected . Replace EMI Board.

Normal Condition.

There is no output voltage from the Power Supply Panel Assembly.

Normal Condition for High Voltage installations.

High Voltage is not supplied to the Modular Power Box (pg 18).

2

1

3 7 VIKING TECHNICAL SUPPORT 1.800.908.0884

TROUBLESHOOTING

LCD Display References

The control board is equipped with a LCD Display that provides operator information, current conditions, settings, diagnostics and error messages. Use the table below to identify the corresponding “TS Ref#” and refer to page 41 for further troubleshooting.

1. Error Messages will be displayed first.

2. The ”Diagnose” LED will flash consecutively indicating how many Error Messages are available.

3. Press the Diagnose button to manually scroll through all of the Messages.

LCD MSG

Meaning

VIKING

ACCESS

Welcome Message

MODEL

H10

Indicates the Model of the unit

System Status Messages

Page 41

TS Ref #s

GATE IS

IDLE

GATE IS

OPENING

GATE IS

CLOSING

GATE IS

OPENED

GATE IS

CLOSED

STOP BY

OBSTRUCT

STOP BY

OVERLOAD

OVERLAP

TIMING

HOLDING

__ SEC

EPS2

OK

3 8

Gate is stopped between limits

Gate is opening

Gate is closing

Gate is at the limit open position

Gate is at the limit close position

Gate stopped due to an obstruction sensor event

Gate stopped due to an overload of the gate system

Gate is waiting for the overlap time

Gate is at the limit open position and timing to close - The display shows the actual time left before closing

While the gate is running, indicates the percentage of accuracy of the EPS.

“OK” indicates 100% accurate communication

11, 12,

13

11, 12

VIKING TECHNICAL SUPPORT 1.800.908.0884

TROUBLESHOOTING

LCD Display References

EPS2

___% ERR

Speed

__%

OVERLAP

_._ SEC

ODS SENS

___%

TIMER

__ SEC

HEATER

__ OFF

HEATER

__ ON

LOCK MOD

OFF

LOCK MOD

ON

LCD MSG

Meaning

Multi Meter Displays

MOT AMP

__._ A

MOT VOLT

__._ VDC

AC VOLT

__._ VAC

CHARGE

__._ VDC

BAT VOLT

__._ VDC

This is the motor current amperage during operation

This is the actual motor voltage during operation

This is the actual low voltage AC to the Control Board from the transformer

Indicates the charging voltage to the batteries, if the Battery Switch is in the OFF position.

Indicates battery voltage, if the AC power is discontinued to the Control

Board.

Board Settings Messages

Indicates that the Electronic Positioning Sensor (EPS) needs to be tuned.

Error rate is displayed as a percentage

Shows the percentage of speed set by the Speed adjustment on the control board. (pg 24)

Shows the number of seconds set by the Overlap Adjustment on the control board. This feature is not available on slide gate operator models

Shows the force setting selected to trip the obstruction sensor. (pg 26)

Shows the amount time set or remaining to hold the gate at the Open Limit position, before the gate starts to close. (pg 24)

The Integrated Heater is disabled for the open

“OPN”

and/or close

“CLS”

limits (pg 27)

The Integrated Heater has been enabled to turn on at the open

“OPN”

and/ or close

“CLS”

limits (pg 27)

“*”

will be displayed while it is heating

The Lock Mode feature is turned OFF (pg 27)

The Lock Mode feature is turned ON (pg 27)

Page 41

TS Ref #s

3 9 VIKING TECHNICAL SUPPORT 1.800.908.0884

TROUBLESHOOTING

LCD Display References

LCD MSG

Meaning

Error Messages

Page 41

TS Ref #s

ERR AC

LOW

ERR AC

HIGH

ERR AC

NO AC

ERR CHRG

HIGH

ERR CHRG

CHECK 4A

ERR BAT

LOW

ERR EPS2

WRONG

ERR EPS2

MISSING

ERR ___

LIMIT

ERR FUSE

20 AMP

ERR EMI

NO EMI

ERR EMI

NO FUSE

ERR EMI

NO AC

ERR EMI

Unknown

ERR EMI

PROTECT

Indicates that the 24VAC supply to the VFlex Board is too low from the

115/230 power supply.

Indicates that the 24VAC supply to the VFlex Board is too high from the

115/230 power supply.

Indicates that there is no 24VAC supply detected to the VFlex Board from the 115/230 power supply.

Potential problem with the charging voltage from the control board.

The battery is low

The EPS (Electronic Positioning Sensor) has one of the following conditions: a) The EPS is not properly adjusted b) The EPS has a potential connection problem c) The EPS has the wrong cable harness

Missing or damaged EPS2 cable harness

Indicates that the open

“OPN”

, close

“CLS“

or both

“NO“

limits are cleared and need to be set.

20 Amp motor fuse is blown

No EMI board detected

4 Amp main fuse is blown on Power Supply Panel Assembly

There is no AC voltage detected from the EMI Board

Lightning strike protection for the EMI Board (behind the Power Supply

Panel Assembly) needs to be replaced

1, 3, 20

1, 3, 20

1, 2, 4,

20

1, ?

a) 4 Amp Fuse is blown, or; b) There is a problem with the batteries or the control board.

18, ?

1, 2, 3,

4

?

14, 17

6

7, 11, 12

15

2

20

There is a problem with the communication between the EMI Board and the

VFlex Board.

21

?

4 0 VIKING TECHNICAL SUPPORT 1.800.908.0884

TROUBLESHOOTING

Solutions

Begin the troubleshooting process by referring to the error messages on the LCD

Display and/or the Status LEDs on the control board. Use pages 36-40 to identify the Troubleshooting Reference # (TS Ref#) then reference the table below.

TS Ref# CHECK

1 Check that the high voltage power supplied to “J-Box” is within range.

100V-120V or 200V-240V

Page Ref#

2 Remove and check EMI Fuse for continuity.

3 Check that the “Voltage Selector”, on the Modular Power Box, is set according

4 to the high voltage power supply. 115VAC or 230VAC

Check that the “AC POWER” switch is turned ON

5 Check that the Power Harness is connected to the control board.

6 Set the limit position.

pg 18 pg 3, 18 pg 3, 18 pg 3, 18,

36-37 pg 4, 18 pg 20-21

7 Check Motor Fuse on the control board.

8 Check that the “Manual Release” switch is turned to the “Engage” position.

pg 4 pg 3, 11

9 Check the Status LEDs and LCD Display to determine if the control board is receiving an input from any external devices or if the “ODS” has been triggered. pg 24, 26,

36-38

10 Remove the external devices from the control board to determine if the control board is responding to an input or problem with the external device or wiring.

pg 29-32,

36-37

11 Check the gate, track and chain for any debris or cause for resistance. Check the “ODS” setting on the control board.

pg 8, 12,

26

12 Check that the gate can be moved manually with low resistance throughout its full length of travel.

13 Check the limit position.

pg 8, 17 pg 20-21

14 Check the cable for the Electronic Positioning Sensor for damage. Clean the connection pins.

15 Check that the EMI cable is properly connected to the “EMI” connection at the

VFlex control board and at the EMI Board.

pg 4

16 Check that the LCD Display for Error Messages

17 Check that the cable from the Electronic Positioning Sensor is connected to the

“EPS2” port on the Control Board.

pg 3-4 pg 4 18 Check 4 Amp fuse on the control board

19 Manually adjust any setting on the Control Board to clear all wireless override settings pg 4 pg 40

20 Check for 24VAC out from the Toroidal Transformer and Power Harness pg 3, 18

21 Check the EMI Cable and contacts between the EMI Board and the VFlex Board pg 2, 4

?

The Control Board or EMI board may be damaged. Call Viking Technical Support for further assistance

4 1 VIKING TECHNICAL SUPPORT 1.800.908.0884

Appendix (A)

Access Control Connections

Power Connections

The control board provides a 24VDC output to power external devices and controls.

Alternatively, for devices that require a power supply other than 24VDC, the operators Power Box contains a convenient 120VAC receptacle to connect a plug-in transformer.

Terminals Connections and Input Functions:

“C”

“N.O.”

=

=

Common

Normally Open

+

“GND” --------------------- Relay Common --------------- “C”

If “Timer” OFF:

If “Timer” ON:

Open - Stop - Close

Open / Reopen if closing

If input is brief:

If input is longer:

Stops gate then Reverses 12 inches

Stops gate, does not reverse

If stopped: No function

If closing: Stops then Opens gate

“N.O.”

Input is received:

Input is released:

Stops gate if closing

Closes gate to prevent tailgating

If not at open limit:

If at open limit:

No function

Prevents gate from Closing

If stopped:

If closing:

If traveling:

Opens gate

Stops then Opens gate

Stops gate

If stopped:

If traveling:

Closes gate

No function

!

TECHNICAL TIP:

Each input Terminal (i.e. Radio, Exit, Re-Open, UL) has a corresponding

Status LED that when illuminated indicates an input is currently being provided to the terminal and the gate is responding accordingly. (See pages 36-37 LED References)

4 2 VIKING TECHNICAL SUPPORT 1.800.908.0884

APPENDIX (A)

Relays In General

NOTE:

Viking Access Systems does not provide the external safety devices and access controls. These items can be purchases from your dealer or distributor.

In General

In regards to the Viking control board, all external safety devices and access controls contain, and are, simple relays that provide an input to the Viking control board when the device is activated.

When these devices are activated, their internal relays create a contact, or short, between the “C” and “N.O.” terminals This contact is what provides the command to the Viking control board.

!

TECHNICAL TIP:

Viking uses the

Normally Open “N.O.” contact from the device, excluding “fail-safe” type photo beams. In such instances, the Normally

Closed “N.C.” will be used instead.

+28V

GND

+

COM

N.O.

N.C.

GND

EXIT

Not

Used

Glossary of Terms

1. Terminal: Wire Connections.

2. Input Terminal: On the Viking control board, the terminal which is labeled for a specific command (Re-

Open, Exit, Radio, etc.). The N.O. contact from the access control device is to be connected to the Input

Terminal.

3. Terminal Block: On the Viking control board, a removable block containing multiple terminals.

4. Relay: The component of an access control or safety device that provides an input or command to the Viking control board.

5. “C” Relay Common Terminal: This is the relay terminal that makes contact

(a short) to the N.O. terminal when the device is activated. Always wire this relay terminal to any “GND” terminal at the control board.

6. “N.O.” Relay Normally Open

Terminal: The relay terminal that has an open contact to “C” while the relay is not activated, and a closed contact when the relay is activated. Almost always wire this relay terminal to an

“Input Terminal” at the control board,

7. “N.C.” Relay Normally Closed

Terminal: The relay terminal that has a closed contact to “C” while the relay is not activated, and an open contact when the relay is activated. This terminal is rarely used.

8. Relay Coil: Contains the terminals that provide power at the relay.

9. “

+

” Relay Positive Terminal: The positive power pole for the relay coil.

Always wire this relay terminal to any

“+28V ” terminal at the control board.

10. “

” Relay Negative Terminal: The negative power pole for the relay coil.

Always wire this relay terminal to any

“GND” terminal at the control board.

4 3 VIKING TECHNICAL SUPPORT 1.800.908.0884

4 4 VIKING TECHNICAL SUPPORT 1.800.908.0884

APPENDIX (C)

Solar Applications

NOTE:

Viking recommends Solar Package ( part # VA-SOCHP) for most general solar applications. Alternatively, individual and third party solar components can be used.

The following are minimum system requirements and installation information.

Panels

• Voltage 24V

• Wattage 80W (minimum)

Cut the wires coming from the toroidal transformer.

Connect the solar panel cables to the power harness as shown.

Batteries & Fuse

Voltage 24V

Amp Hour 35Ah (minimum)

Replace the operators batteries with

35Ah or greater.

!

IMPORTANT:

The chart provided can be used as a guide for the number of cycles the gate will operate per day. The chart is for a single gate operator with just: a. One Radio Receiver b. One low voltage, low current loop detector c. One low voltage, low current photo beam

If more specific information is needed please consult with Viking Access Systems.

For more information regarding solar energy refer to www.nrel.gov/solar

VIKING TECHNICAL SUPPORT 1.800.908.0884

4 5

4 6

VIKING EXPANSION PRODUCTS

VIKING KONNECT Master/Slave Kit

Secure and reliable

Master/Slave communication using Viking’s Konnect technology. Paired with the Viking App, each module also doubles as a diagnostic tool.

Part# VA-KONNECT-MS

***Q-7, B-12 & ECU Operators require (2) Antenna Extension Cables (part# VA-RPSMA)***

VIKING KONNECT Diagnostic Tool

On-site remote access to the operator from the convenience of a compatible hand held device. With the Viking App, this tool becomes a wireless extension of the control board allowing you to view and change settings, review diagnostic information, operate the gate for testing and update the control boards firmware. Part# VA-KONNECT-D

***Q-7, B-12 & ECU Operators require ( 1) Antenna Extension Cable (part# VA-RPSMA)***

VIKING MONITOR

Off-site access to operator diagnostics and perform firmware updates from just about anywhere with cellular service. With the Viking App, this tool allows you to monitor and label multiple operators by site and location for quick reference. Provides error notifications, operator status, settings and diagnostic information.

Part# VA-MONITOR

***Q-7, B-12 & ECU Operators require ( 1) Antenna Extension Cable (part# VA-RPSMA)***

VIKING APP

Mobile device user interface application for Viking

Konnect and Viking Monitor. Available for iOS, Android and Windows operating systems. Free for download from your mobile device application store or www.vikingaccess.com

VIKING AC SURGE PRO

Adds another layer of protection to the high voltage power supply of your gate operator. Connecting the AC

Surge Pro in parallel to the EMI Board, provides a dual layer of protection from surges up to 20,000 Volts / 10,000 Amps. Part# VA-SURGEPROAC

VIKING SOLAR KIT

The components included in this package are intended to provide sufficient power for general applications.

Part# VA-SOCHP

This Kit includes the following components:

(2) 12V 40W Solar Panels

(2) 12V 35Ah batteries

(1) Solar Charger

Part# VA-SO40W (wired in series = 24V 80W)

Part# DUBA35 (wired in series = 24V 35Ah)

Part# SOCHR10

Part# SOHAR (1) Solar Power Harness

!

NOTE:

The number of cycles achieved from this kit are dependent upon the following and may require increased panel and battery capacities:

• Power consumption of all accessories being used

• Average solar radiation of geographic location

VIKING TECHNICAL SUPPORT 1.800.908.0884

OUR CONTINUOUS COMMITMENT TO EXCELLENCE

Viking Access Systems is continuously working hard to identify and design products that will appeal to the industry and its needs. As technology continues to advance, we have developed a completely effi cient and intelligent line of gate operators to meet the changing demands. These machines offer: full UL325 and UL991 compliance, soft-start and soft-stop, intelligent obstruction sensors, continuous operation (100% duty cycle) and extreme power effi ciency. Innovative features include: adaptive and self-learning algorithms, redundancy design in both hardware and software to ensure operation and functionality, protection from lightning, short circuit and power surges, and our exclusive helical gearing offering the highest effi ciency rating in the industry. Our entire product line is continually modifi ed and improved based on the latest technology and our customer’s valuable feedback. The results are products that offer accuracy, effi ciency, reliability and performance, all in sleek, high-tech designs.

We pledge to continue establishing ourself as the leader in high quality, innovative gate operators by developing “Next Level” technology. We are committed to providing safety and convenience with innovative solutions for every security gate need.

STANDARD FEATURES

AND OPERATOR SPECIFICATIONS

• UL Listed; UL325 and UL991 • Intelligent speed control with smooth start and stop, self-adjust system

• ETL Listed; UL325 and UL991

• Anti-Tailgate and Operation Pre-Warming features

• Externally accessible Manual Release Switch

• Fail-Safe option sets the gate to automatically transfer to a fail-safe mode in the event of a power failure, allowing the gate to be pushed open without the use of special knowledge of the equipment

• On-Board LCD Display provides diagnostics, operator status, settings and real-time volt and amp readings

• Intelligent obstruction detection with adjustable sensitivity

• Fail- Secure option sets the gate to electronically lock in the event of a power failure, allowing no manual movement without the use of the manual release

• Built-in climate control for cold weather applications

• Built-in protection against lightning strikes or similar electrical surges • Elegant design, appealing to any architectural project

• Regulated power supply for your external accessories • Plated and powder coated steel chassis

• Adjustable travel speed

• Up to 75’ maximum gate opening

• 100% duty cycle

• Modular Power Supply Box for convenient low voltage installations

• 100 cycles of operation on backup battery

(1000 lb. gate and 20’ length)

• Inherent overload protection; redundancy design using multiple types of protection

• Modular connectors for easy access control and accessory installation

• Solar panel and low voltage wiring compatibility

• LED indicators display gate and operator status for easy troubleshooting

INSTALLATION DATE:

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

COMPANY / INSTALLER:

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

CONTACT:

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

SERIAL NUMBER(S):

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

A L L I N S TA L L AT I O N , M A I N T E N A N C E A N D R E PA I R W O R K M U S T B E

D O C U M E N T E D A N D M A D E AVA I L A B L E T O T H E U S E R .