advertisement
Installation Manual
20001700, Rev CH
October 2022
Micro Motion
™
1700 and 2700 Transmitters
Installation Manual
Safety messages
Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully before proceeding to the next step.
Safety and approval information
This Micro Motion product complies with all applicable European directives when properly installed in accordance with the instructions in this manual. Refer to the EU Declaration of Conformity for directives that apply to this product. The following are available: the EU Declaration of Conformity, with all applicable European directives, and the complete ATEX installation drawings and instructions. In addition, the IECEx installation instructions for installations outside of the European Union and the CSA installation instructions for installations in North America are available at Emerson.com
or through your local Micro Motion support center.
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found at Emerson.com
. For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Troubleshooting information can be found in the Configuration Manual . Product data sheets and manuals are available from the
Micro Motion website at Emerson.com
.
Return policy
Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Micro Motion employees. If you fail to follow Micro
Motion procedures, then Micro Motion will not accept your returned equipment.
Return procedures and forms are available on our web support site at Emerson.com
, or by calling the Micro Motion Customer
Service department.
2
Installation Manual
20001700
Contents
October 2022
Contents
Installation Manual 3
Contents
October 2022
Installation Manual
20001700
I/O wiring for 2700 with FOUNDATION fieldbus or PROFIBUS-PA...............................81
4 Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
1
1.1
1.2
1.3
Before you begin
October 2022
Before you begin
About this document
This manual provides information on planning, mounting, wiring, and initial setup of the
Micro Motion 1700-2700 transmitter. For information on full configuration, maintenance, troubleshooting, or service of the transmitter, see the .
The information in this document assumes that users understand basic transmitter and sensor installation, configuration, and maintenance concepts and procedures.
Hazard messages
This document uses the following criteria for hazard messages based on ANSI standards
Z535.6-2011 (R2017).
DANGER
Serious injury or death will occur if a hazardous situation is not avoided.
WARNING
Serious injury or death could occur if a hazardous situation is not avoided.
CAUTION
Minor or moderate injury will or could occur if a hazardous situation is not avoided.
NOTICE
Data loss, property damage, hardware damage, or software damage can occur if a situation is not avoided. There is no credible risk of physical injury.
Physical access
WARNING
Unauthorized personnel can potentially cause significant damage and/or misconfiguration of end users' equipment. Protect against all intentional or unintentional unauthorized use.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access to protect users' assets. This is true for all systems used within the facility.
Related documentation
You can find all product documentation on the product documentation DVD shipped with the product or at Emerson.com
.
See any of the following documents for more information:
Installation Manual 5
Before you begin
October 2022
Installation Manual
20001700
• Micro Motion Series 1000 and Series 2000 Transmitters with MVD Technology Product Data
Sheet
• 1700 documents
— Micro Motion Model 1700 Transmitters with Analog Outputs Configuration and Use
Manual
— Micro Motion Model 1700 Transmitters with Intrinsically Safe Outputs Configuration and Use Manual
• 2700 documents
— Micro Motion Model 2700 Transmitters with Analog Outputs Configuration and Use
Manual
— Micro Motion Model 2700 Transmitters with Configurable Input/Outputs Configuration and Use Manual
— Micro Motion Model 2700 Transmitters with Intrinsically Safe Outputs Configuration and Use Manual
— Micro Motion Model 2700 Transmitters with F OUNDATION
™
Use Manual
Fieldbus Configuration and
— Micro Motion Model 2700 Transmitters with PROFIBUS-PA Configuration and Use
Manual
• Micro Motion Fuel Consumption Application for Transmitters Installation and Operation
Guide
• Micro Motion 9-Wire Flow Meter Cable Preparation and Installation Guide
• Micro Motion Enhanced Density Application Manual
• Sensor installation manual
6 Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
2
2.1
2.2
Planning
October 2022
Planning
Meter components
A meter consists of the following components:
• A transmitter
• A sensor
The following sensors are compatible with the FMT:
— All CMFS sensors
— F025 - F100
— H025 - H100
— T025 - T150
• A core processor that provides additional memory and processing functions
Installation types
The transmitter was ordered and shipped for one of up to eight installation types. The fifth character of the transmitter model number indicates the installation type.
Figure 2-1: Installation type indication for 1700 and 2700 transmitters
The model number is located on the device tag on the side of the transmitter.
M
P
C
B
Table 2-1: Installation types for 1700 and 2700 transmitters
I
E
Model code
R
Description
Remote mount 4-wire
Integral
Remote enhanced core processor (painted aluminum housing) with remote transmitter
Remote mount 9-wire (painted aluminum housing with integral core)
Remote core processor with remote transmitter
Remote mount 4-wire (stainless steel housing)
Remote mount 9-wire (stainless steel housing)
Installation Manual 7
Planning
October 2022
Installation Manual
20001700
Table 2-1: Installation types for 1700 and 2700 transmitters (continued)
Model code
Description
Remote mount 4-wire (painted aluminum housing) for connecting to
Compact Density Meter (CDM), Fork Density Meter (FDM), Fork Viscosity
Meter (FVM)
(1) This option is available only with the 2700 F
OUNDATION
™ fieldbus transmitter
The transmitter is mounted directly to the sensor. Integral installations do not require separate transmitter installation. Power supply and I/O must be field wired to the transmitter.
Figure 2-2: Integral installation (model code I)
STATUS
SCROLL SELECT
Note
If replacing an integral 1700/2700 transmitter with a spare transmitter, retain the transition ring. The replacement does not include a new transition ring.
8 Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
Planning
October 2022
Figure 2-3: High-temperature meters with factory connection (model code I)
A
B
C
The transmitter is shipped with a flexible connection factory installed between the sensor and the transmitter. The transmitter must be dismounted from its shipping location (spotwelded to the sensor case) and then mounted separately. Power supply and I/O must be field wired to the transmitter.
A. Sensor
B. Transmitter or core processor
C. Factory-installed flexible connection
Figure 2-4: 4-wire remote installation for Coriolis meters (model code R or M)
A
B
C
D
A
The transmitter is installed remotely from the sensor. The 4-wire connection between the sensor and transmitter must be field wired. Power supply and I/O must be field wired to the transmitter.
A. Transmitter
B. Field-wired 4-wire connection
C. Core processor
D. Sensor
Installation Manual 9
Planning
October 2022
Installation Manual
20001700
Figure 2-5: 4-wire remote installation for density and viscosity meters (CDM, FDM, or
FVM with fieldbus only model code H)
The transmitter is installed remotely from the Compact Density Meter (CDM), Fork Density
Meter (FDM), or Fork Viscosity Meter (FVM). The 4-wire connection between the sensor and transmitter must be field wired. Power supply and I/O must be field wired to the transmitter.
A. Transmitter
B. Field-wired 4-wire connection
C. Meter electronics
10 Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
Figure 2-6: 9-wire remote installation (model code P)
A
B
C
D
A
Planning
October 2022
The transmitter and core processor are combined in a single unit that is installed remotely from the sensor. The 9-wire connection between the transmitter/core processor and the sensor must be field wired. Power supply and I/O must be field wired to the transmitter.
A. Transmitter
B. Field-wired 9-wire connection
C. Junction box
D. Sensor
Installation Manual 11
Planning
October 2022
Installation Manual
20001700
Figure 2-7: Remote core processor with remote sensor installation (model code B or
E)
C
A
B
D
E
2.3
F
The transmitter, core processor, and sensor are all mounted separately. The 4-wire connection between the transmitter and core processor must be field wired. The 9-wire connection between the core processor and the sensor must be field wired. Power supply and I/O must be field wired to the transmitter. This configuration is sometimes called double-hop .
A. Junction box
B. Sensor
C. Transmitter
D. Field-wired 4-wire connection
E. Core processor
F. Field-wired 9-wire connection
Maximum cable lengths between sensor and transmitter
The maximum cable length between the sensor and transmitter that are separately installed is determined by cable type.
Cable type
Micro Motion 4-wire remote mount
Micro Motion 9-wire remote mount
Wire gauge
Not applicable
Not applicable
Maximum length
• 1,000 ft (305 m) without
Ex-approval
• 500 ft (152 m) with IIC rated sensors
• 1,000 ft (305 m) with IIB rated sensors
60 ft (18 m)
12 Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
2.4
Planning
October 2022
Cable type
User-supplied 4-wire
Wire gauge
VDC 22 AWG (0.326 mm ² )
VDC 20 AWG (0.518 mm ² )
VDC 18 AWG (0.823 mm ² )
RS-485 22 AWG (0.326 mm ² ) or larger
Maximum length
300 ft (91 m)
500 ft (152 m)
1,000 ft (305 m)
1,000 ft (305 m)
Output options
The transmitter was ordered and shipped for one of up to 10 output options. You must know your transmitter output option to correctly install the transmitter. The eighth character of the transmitter model number indicates the output option.
Figure 2-8: Output option indication for 1700 and 2700 transmitters
Installation Manual
The model number is located on the device tag on the side of the transmitter.
Table 2-2: Output options for 1700 transmitters
Letter
A
D
Description
Analog outputs – one mA, one frequency, one RS-485
Intrinsically safe analog outputs – one mA, one frequency
Table 2-3: Output options for 2700 transmitters
G
N
D
E
2
3
B
C
Letter
A
4
Description
Analog outputs – one mA, one frequency, one RS-485
Configurable I/O channels (default configuration of two mA, one frequency)
Configurable I/O channels (custom configuration )
Intrinsically safe analog outputs – two mA, one frequency
Intrinsically safe F OUNDATION fieldbus H1 with standard function blocks
PROFIBUS-PA
Non-incendive F OUNDATION fieldbus H1 with standard function blocks
WirelessHART ® – one mA, one frequency, one RS-485
WirelessHART – one mA, two configurable I/O channels (custom configuration)
Intrinsically safe WirelessHART – two mA, one frequency
13
Planning
October 2022
2.5
2.6
Installation Manual
20001700
Electrical connections
Table 2-4: 1700 and 2700 transmitters
Connection type
Input/Output
1700
• Intrinsically safe version: Two pairs of wiring terminals for transmitter outputs
• Non-intrinsically safe analog outputs (output option A): Three pairs of wiring terminals for transmitter outputs
Power
2700
Three pairs of wiring terminals for transmitter
I/O and communications
Service port
• One pair of wiring terminals accepts AC or DC power
• One internal ground lug for power-supply ground wiring
Two clips for temporary connection to the service port
Notes
• Each screw terminal connection accepts one or two solid conductors, 14 AWG
(2.08 mm ² ) to 12 AWG (3.31 mm ² ) or one or two stranded conductors, 22 AWG
(0.326 mm ² ) to 14 AWG (2.08 mm ² ). Each plug type connector accepts one stranded or solid conductor, 24 AWG (0.205 mm ² ) to 12 AWG (3.31 mm ² ).
• For 1700/2700 transmitters with an integral core processor (mounting code C), the 4wire connection between the transmitter and core processor is not normally accessed.
Environmental limits
1700 and 2700
Type
Ambient temperature limits (1)
Humidity limits
Value
Operating:
-40 °F (-40.0 °C) to 140 °F (60.0 °C)
Storage:
-40 °F (-40.0 °C) to 140 °F (60.0 °C)
5 to 95% relative humidity, non-condensing at
140 °F (60.0 °C)
14 Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
2.7
2.8
Planning
October 2022
Type
Vibration limits
Value
Meets IEC 60068-2-6,endurance sweep, 5 to
2000 Hz up to 1.0 g
Housing rating
(1) Display responsiveness decreases, and display may become difficult to read below -4 °F
(-20.0 °C). Above 131 °F (55.0 °C), some darkening of display might occur.
(2) The protection is IP69K-based NEN-ISO 20653:2013 and IP69 when using standard IEC/EN
60529.
Hazardous area classifications
If you plan to mount the transmitter in a hazardous area:
• Verify that the transmitter has the appropriate hazardous area approval. Each transmitter has a hazardous area approval tag attached to the housing.
• Ensure that any cable used between the transmitter and the sensor meets the hazardous area requirements.
Power requirements
Self-switching AC/DC input, automatically recognizes supply voltage
• 85 to 265 VAC, 50/60 Hz, 6 watts typical, 11 watts maximum
• 18 to 100 VDC, 6 watts typical, 11 watts maximum
• Complies with low voltage directive 2006/95/EC per EN 61010-1 (IEC 61010-1) with amendment 2, and Installation (Overvoltage) Category II, Pollution Degree 2
Notes
For DC power:
• Power requirements assume a single transmitter per cable.
• At startup, the power source must provide a minimum of 1.5 amps of short-term current per transmitter.
• Length and conductor diameter of the power cable must be sized to provide 18 VDC minimum at the power terminals, at a load current of 0.5 amps.
M: Minimum supply voltage
R: Cable resistance
L: Cable length
M = 18V + R × L × 0.5A
Table 2-5: Typical power cable resistance at 68 °F (20.0 °C)
Wire gauge
14 AWG
16 AWG
Resistance
0.0050 Ω/ft
0.0080 Ω/ft
Installation Manual 15
Planning
October 2022
Table 2-5: Typical power cable resistance at 68 °F (20.0 °C) (continued)
Wire gauge
18 AWG
20 AWG
2.5 mm 2
1.5 mm 2
1.0 mm 2
0.75 mm 2
0.50 mm 2
Resistance
0.0128 Ω/ft
0.0204 Ω/ft
0.0136 Ω/m
0.0228 Ω/m
0.0340 Ω/m
0.0460 Ω/m
0.0680 Ω/m
Installation Manual
20001700
16 Micro Motion 1700 and 2700 Transmitters
3
3.1
3.2
Installation Manual
20001700
3.3
3.4
3.4.1
Mounting
October 2022
Mounting
Mounting for integral installations
There are no separate mounting requirements for integral transmitters.
Orientation
You can mount the transmitter in any orientation as long as the conduit openings do not point upward.
NOTICE
Upward-facing conduit openings risk condensation moisture entering the transmitter housing that could damage the transmitter.
Accessibility for maintenance
Mount the transmitter in a location and orientation that satisfies the following conditions:
• Allows sufficient clearance to open the transmitter housing cover. Micro Motion recommends 8 in (203 mm) – 10 in (254 mm) clearance at the rear of the transmitter.
• Provides clear access for installing cabling to the transmitter.
Mounting options
There are two options available for mounting the transmitter:
• Mount the transmitter to a wall or flat surface.
• Mount the transmitter to an instrument pole.
Mount the transmitter to a wall
Prerequisites
• Use two 0.31 in (7.9 mm) U-bolts for a 2 in (51 mm) pipe, and four matching nuts that can withstand the process environment. Appropriate bolts and nuts are shipped with remote mount transmitters in the ship kit. The pipe mount kit can be ordered as part of the 1700/2700 part number.
• Ensure that the surface is flat and rigid, does not vibrate, or move excessively.
• Confirm that you have the necessary tools, and the mounting kit shipped with the transmitter.
Procedure
1. If desired, re-orient the transmitter on the mounting bracket.
Installation Manual 17
Mounting
October 2022
Installation Manual
20001700 a) Remove the junction end-cap from the junction housing.
b) Loosen each of the four 0.16 in (4.1 mm) cap screws.
c) Rotate the bracket so that the transmitter is oriented as desired.
d) Tighten the cap screws, torquing to 30 in lbf (3.39 N m) to 38 in lbf (4.29 N m).
e) Replace the junction end-cap.
Figure 3-1: Components of 4-wire remote mount transmitter (aluminum housing)
A
B
C
D
A. Transmitter
B. Mounting bracket
C. Cap screws
D. End-cap
18 Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
Mounting
October 2022
Figure 3-2: Components of a 4-wire remote mount transmitter (stainless steel housing)
A. Transmitter
B. Mounting bracket
C. Cap screws
D. End-cap
Installation Manual 19
Mounting
October 2022
Figure 3-3: Components of 9-wire remote mount transmitter
A
Installation Manual
20001700
B
C
3.4.2
20
A. Transmitter
B. Cap screws
C. Mounting bracket
2. Attach the mounting bracket to the wall.
Mount the transmitter to an instrument pole
Prerequisites
• Use two 0.3125 in (8 mm) U-bolts for 2 in (51 mm) pipe, and four matching nuts, that can withstand the process environment. Micro Motion does not supply U-bolts or nuts
(appropriate bolts and nuts are available as an option).
• Ensure the instrument pole extends at least 12 in (305 mm) from a rigid base, and is no more than 2 in (51 mm) in diameter.
Procedure
1. If desired, re-orient the transmitter on the mounting bracket.
a) For 4-wire remote mount transmitters, remove the junction end-cap from the junction housing.
b) Loosen each of the four 0.16 in (4.1 mm) cap screws.
c) Rotate the bracket so that the transmitter is oriented as desired.
d) Tighten the cap screws, torquing to 30 in lbf (3.39 N m) to 38 in lbf (4.29 N m).
Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
Mounting
October 2022 e) If applicable, replace the junction end-cap.
Figure 3-4: Components of 4-wire remote mount transmitter (aluminum housing)
A
B
C
D
A. Transmitter
B. Mounting bracket
C. Cap screws
D. End-cap
Installation Manual 21
Mounting
October 2022
Figure 3-5: Components of 9-wire remote mount transmitter
A
Installation Manual
20001700
B
C
A. Transmitter and integral core
B. Cap screws
C. Mounting bracket
2. Attach the mounting bracket to an instrument pole.
22 Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
3.5
Mounting
October 2022
Rotate the transmitter on the sensor (optional)
In integral installations, you can rotate the transmitter on the sensor up to 360º in 90º increments.
Figure 3-6: Components of an integral transmitter
A
B
C
D
Installation Manual
A. Transmitter
B. Transition ring
C. Cap screws
D. Sensor
Procedure
1. Loosen each of the four cap screws 0.16 in (4.1 mm) that fasten the transmitter to the base.
2. Rotate the transmitter counter-clockwise so that the cap screws are in the unlocked position.
3. Gently lift the transmitter straight up, disengaging it from the cap screws.
NOTICE
Do not disconnect or damage the wires that connect the transmitter to the core processor.
4. Rotate the transmitter to the desired orientation.
NOTICE
Do not pinch or stress the wires.
The slots on the transition ring should be aligned with the cap screws.
5. Gently lower the transmitter onto the base, inserting the cap screws into the slots.
23
Mounting
October 2022
3.6
Installation Manual
20001700
6. Rotate the transmitter clockwise so that the cap screws are in the locked position.
7. Tighten the cap screws, torquing to 1.70 ft lbf (2 N m) to 2.51 ft lbf (3 N m).
Rotate the user interface on the transmitter
(optional)
The user interface on the transmitter electronics module can be rotated 90º or 180° from the original position. .
Figure 3-7: Display components
A
B
C
D
G
24
E
F
A. Transmitter housing
B. Sub-bezel
C. Display module
D. Display screws
E. End-cap clamp
F. Cap screw
G. Display cover
Notes
• When using the touch buttons, you must cover at least a 0.31 in (7.9 mm) diameter circle over the surface above the touch button: using your thumb may be more effective because it has a greater surface area.
• When the housing cover is removed, the touch buttons do not function.
Procedure
1. Shut off power to the unit.
2. Remove the end-cap clamp by removing the cap screw.
3. Turn the display cover counterclockwise to remove it from the main enclosure.
Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
Mounting
October 2022
4. Carefully loosen (and remove if necessary) the semicaptive display screws while holding the display module in place.
5. Carefully pull the display module out of the main enclosure until the sub-bezel pin terminals are disengaged from the display module.
Note
If the display pins come out of the board stack with the display module, remove the pins and reinstall them.
6. Rotate the display module to the desired position.
7. Insert the sub-bezel pin terminals into the display module pin holes to secure the display in its new position.
8. If you have removed the display screws, line them up with the matching holes on the sub-bezel, then reinsert and tighten them.
9. Place the display cover onto the main enclosure.
10. Turn the display cover clockwise until it is snug.
11. Replace the end-cap clamp by reinserting and tightening the cap screw.
12. Restore power to the transmitter.
Installation Manual 25
Mounting
October 2022
Installation Manual
20001700
26 Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
4
4.1
4.1.1
Preparing the wires
October 2022
Preparing the wires
Prepare the 4-wire cable
4-wire cable types and usage
Micro Motion offers two types of 4-wire cable: shielded and armored. Both types contain shield drain wires.
The cable supplied by Micro Motion consists of one pair of red and black 18 AWG
(0.823 mm ² ) wires for the VDC connection, and one pair of white and green 22 AWG
(0.326 mm ² ) wires for the RS-485 connection.
User-supplied cable must meet the following requirements:
• Twisted pair construction.
• Applicable hazardous area requirements, if the core processor is installed in a hazardous area.
• Wire gauge appropriate for the cable length between the core processor and the transmitter, or the host.
Wire gauge
VDC 22 AWG (0.326 mm ² )
VDC 20 AWG (0.518 mm ² )
VDC 18 AWG (0.823 mm ² )
RS-485 22 AWG (0.326 mm ² ) or larger
Maximum cable length
300 ft (91 m)
500 ft (152 m)
1,000 ft (305 m)
1,000 ft (305 m)
Prepare a cable with a metal conduit
Procedure
1. Remove the core processor cover using a flat-blade screw driver.
2. Run the conduit to the sensor.
3. Pull the cable through the conduit.
4. Cut the drain wires and let them float at both ends of the conduit.
Prepare a cable with user-supplied cable glands
Procedure
1. Remove the core processor cover using a flat-blade screw driver.
2. Pass the wires through the gland.
3. Terminate the shield and drain wires inside the gland.
4. Assemble the gland according to vendor instructions.
Installation Manual 27
Preparing the wires
October 2022
Installation Manual
20001700
Prepare a cable with Micro Motion-supplied cable glands
Procedure
1. Remove the core processor cover using a flat-blade screw driver.
2. Pass the wires through the gland nut and clamping insert.
28
A. Gland nut
B. Clamping insert
3. Strip the cable jacket.
Option
NPT gland type
M20 gland type
Description
Strip 4.5 in (114 mm)
Strip 4.25 in (107.9 mm)
4. Remove the clear wrap and filler material.
5. Strip most of the shielding.
Option
NPT gland type
M20 gland type
Description
Strip all but 0.75 in (19.0 mm)
Strip all but 0.5 in (13 mm)
6. Wrap the drain wires twice around the shield and cut off the excess drain wires.
A. Drain wires wrapped around shield
7. For foil (shielded cable) only:
Note
For braided (armored cable) skip this step and contine to the next step.
Option Description
NPT gland type a. Slide the shielded heat shrink over the drain wires. Ensure that the wires are completely covered.
b. Apply heat 250 °F (121.1 °C) to shrink the tubing. Do not burn the cable.
Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
Preparing the wires
October 2022
Option Description c. Position the clamping insert so the interior end is flush with the braid of the heat shrink.
M20 gland type
A. Shielded heat shrink
B. After heat is applied
Trim 0.3 in (8 mm).
A. Trim
8. Assemble the gland by folding the shield or braid back over the clamping insert and
0.125 in (3.18 mm) past the O-ring.
A. Shield folded back
9. Install the gland body into the conduit opening on the core processor housing.
10. Insert the wires through the gland body and tighten the gland nut onto the gland body.
A. Shield folded back
B. Gland body
Installation Manual 29
Preparing the wires
October 2022
4.2
4.2.1
Installation Manual
20001700
Prepare the 9-wire cable
Micro Motion supplies three types of 9-wire cable: jacketed, shielded, and armored. The type of cable you are using determines how you will prepare the cable.
9-wire cable types and usage
Cable types
Micro Motion supplies three types of 9-wire cable: jacketed, shielded, and armored. Note the following differences between the cable types:
• Armored cable provides mechanical protection for the cable wires.
• Jacketed cable has a smaller bend radius than shielded or armored cable.
• If ATEX compliance is required, the different cable types have different installation requirements.
Cable jacket types
All cable types can be ordered with a PVC jacket or Teflon ® required for the following installation types:
FEP jacket. Teflon FEP is
• All installations that include a T-series sensor.
• All installations with a cable length of 250 ft (76.20 m) or greater, a nominal flow less than 20 percent, and ambient temperature changes greater than 68 °F (20.0 °C).
Table 4-1: Cable jacket material and temperature ranges
Cable jacket material
PVC
Teflon FEP
Handling temperature
Low limit High limit
-4 °F (-20.0 °C)
-40 °F (-40.0 °C)
194 °F (90.0 °C)
194 °F (90.0 °C)
Operating temperature
Low limit High limit
-40 °F (-40.0 °C)
-76 °F (-60.0 °C)
221 °F (105.0 °C)
302 °F (150.0 °C)
Cable bend radii
Table 4-2: Bend radii of jacketed cable
Jacket material
PVC
Teflon FEP
Outside diameter
0.415 in (10.54 mm)
0.340 in (8.64 mm)
Minimum bend radii
Static (no load) condition
Under dynamic load
3.15 in (80.0 mm)
2.6 in (66 mm)
6.25 in (158.8 mm)
5.15 in (130.8 mm)
30 Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
Preparing the wires
October 2022
Table 4-3: Bend radii of shielded cable
Jacket material Outside diameter
PVC
Teflon FEP
0.525 in (13.33 mm)
0.425 in (10.80 mm)
Table 4-4: Bend radii of armored cable
Minimum bend radii
Static (no load) condition
Under dynamic load
4.25 in (107.9 mm)
3.25 in (82.6 mm)
8.5 in (216 mm)
6.38 in (162.1 mm)
Jacket material
PVC
Teflon FEP
Outside diameter
0.525 in (13.33 mm)
0.340 in (8.64 mm)
Minimum bend radii
Static (no load) condition
Under dynamic load
4.25 in (107.9 mm)
3.25 in (82.6 mm)
8.5 in (216 mm)
6.38 in (162.1 mm)
Cable illustrations
Figure 4-1: Cross-section view of jacketed cable
A
B (4)
C (4)
D (5)
A. Outer jacket
B. Drain wire (4 total)
C. Foil shield (4 total)
D. Filler (5 total)
Installation Manual 31
Preparing the wires
October 2022
Figure 4-2: Cross-section view of shielded cable
A
B
C (1)
D
G (5)
A. Outer jacket
B. Tin-plated copper braided shield
C. Foil shield (1 total)
D. Inner jacket
E. Drain wire (4 total)
F. Foil shield (4 total)
G. Filler (5 total)
Figure 4-3: Cross-section view of armored cable
A
B
F (4)
C (1)
E (4)
D
F (4)
E (4)
G (5)
A. Outer jacket
B. Stainless steel braided shield
C. Foil shield (1 total)
D. Inner jacket
E. Drain wire (4 total)
F. Foil shield (4 total)
G. Filler (5 total)
Installation Manual
20001700
32 Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
4.2.2
Preparing the wires
October 2022
Prepare jacketed cable
Prepare jacketed cable at sensor end
Procedure
1. Trim 4.5 in (114 mm) of cable jacket.
2. Remove the clear wrap and filler material.
3. Remove the foil that is around the insulated wires and separate them.
Installation Manual
A. Trim cable jacket
4. Identify the drain wires in the cable. Clip off each drain wire as close as possible to the cable jacket.
A. Drain wires clipped
5. Slide the 1.5 in (38 mm) heat-shrink tubing over the wires and cable jacket. The tubing should completely cover the clipped ends of the drain wires.
A. Heat-shrink tubing
6. Without burning the cable, apply heat to shrink all tubing. Recommended temperature is 250 °F (121.1 °C).
7. Allow the cable to cool, then strip 0.25 in (6.4 mm) of insulation from each wire.
Prepare jacketed cable at transmitter end
Procedure
1. Trim 4 in (102 mm) of cable jacket.
2. Remove the clear wrap and filler material.
3. Remove the foil that is around the insulated wires and separate them.
A. Trim cable jacket
33
Preparing the wires
October 2022
Installation Manual
20001700
4. Identify the drain wires in the cable and bring them together.
5. Fan the other wires to the outside of the cable.
6. Twist the drain wires together.
7. Slide the 3 in (76 mm) heat-shrink tubing over the drain wires. Push the tubing as close as possible to the cable jacket.
8. Slide the 1.5 in (38 mm) long heat-shrink tubing over the cable jacket. The tubing should completely cover all portions of the drain wires that remain exposed next to the cable jacket.
4.2.3
A. Heat-shrink tubing over cable jacket
B. Heat-shrink tubing over drain wires
9. Without burning the cable, apply heat to shrink all tubing. Recommended temperature is 250 °F (121.1 °C).
10. Allow the cable to cool, then strip 0.25 in (6.4 mm) of insulation from each wire.
Prepare shielded or armored cable
Prepare shielded or armored cable at sensor end
Procedure
1. Without cutting the shield, strip 7 in (178 mm) of outer jacket.
2. Strip 6.5 in (165 mm) of braided shield, so 0.5 in (13 mm) of shield remains exposed.
3. Remove the foil shield that is between the braided shield and inner jacket.
4. Strip 4.5 in (114 mm) of inner jacket.
34
A. Trim outer jacket
B. Trim braided shield
C. Trim inner jacket
5. Remove the clear wrap and filler material.
6. Remove the foil that is around the insulated wires and separate them.
Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
Preparing the wires
October 2022
7. Identify the drain wires in the cable. Clip each drain wire as close as possible to the cable jacket.
A. Drain wires clipped
8. Slide the 1.5 in (38 mm) heat-shrink tubing over the cable jacket. The tubing should completely cover the clipped ends of the drain wires.
A. Heat-shrink tubing
9. Without burning the cable, apply heat to shrink all tubing. Recommended temperature is 250 °F (121.1 °C).
10. Allow the cable to cool, then strip 0.25 in (6.4 mm) of insulation from each wire.
Prepare shielded or armored cable at transmitter end
Procedure
1. Without cutting the shield, strip 9 in (229 mm) of cable jacket.
2. Strip 8.5 in (216 mm) of braided shield, so 0.5 in (13 mm) of shield remains exposed.
3. Remove the foil shield that is between the braided shield and inner jacket.
4. Strip 4 in (102 mm) of inner jacket.
Installation Manual
A. Trim outer jacket
B. Trim braided shield
C. Trim inner jacket
5. Remove the clear wrap and filler material.
6. Remove the foil that is around the insulated wires and separate them.
7. Identify the drain wires in the cable and bring them together.
8. Fan the other wires to the outside of the cable.
35
Preparing the wires
October 2022
Installation Manual
20001700
9. Twist the drain wires together.
10. Slide the 3 in (76 mm) heat-shrink tubing over the drain wires. Push the tubing as close as possible to the cable jacket.
11. Slide the 1.5 in (38 mm) long heat-shrink tubing over the cable jacket. The tubing should completely cover all portions of the drain wires that remain exposed next to the cable jacket.
A. Heat-shrink tubing over cable jacket
B. Heat-shrink tubing over drain wires
12. Without burning the cable, apply heat to shrink all tubing. Recommended temperature is 250 °F (121.1 °C).
13. Allow the cable to cool, then strip 0.25 in (6.4 mm) of insulation from each wire.
36 Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
5
5.1
Wiring the transmitter to the sensor
October 2022
Wiring the transmitter to the sensor
Note
For integral installations, there is no need to connect wiring between the transmitter and the sensor.
Wire the transmitter to the sensor (4-wire)
Use this procedure to wire the transmitter to the sensor in a 4-wire remote installation.
Procedure
1. Connect the cable to the sensor-mounted core processor as described in the sensor documentation.
2. Feed the wires from the sensor through the conduit opening on the transmitter.
3. Connect wires to the appropriate terminals on the mating connector.
Tip
You may find it easier to unplug the mating connector to connect the wires. If you do so, remember to firmly reseat the mating connector and tighten the mating connector screws so that the mating connector cannot accidentally come loose.
Figure 5-1: Wiring path for transmitters with aluminum housing
Installation Manual
A. 4-wire cable
B. Transmitter conduit opening
C. Mating connector
37
Wiring the transmitter to the sensor
October 2022
5.2
Installation Manual
20001700
Wire the transmitter to the remote core processor (4-wire)
Use this procedure to wire the transmitter to the remote core processor in a 4-wire remote sensor installation. This procedure applies to both 700 and 800 core processors.
Procedure
1. If you are installing a Micro Motion-supplied cable gland at the core processor housing, identify the cable gland to use for the 4-wire cable conduit opening.
Figure 5-2: Cable gland identification
A
B
C
A. Cable gland used with 4-wire conduit opening
B.
¾ in–14 NPT cable gland used with 9-wire conduit opening
C.
½ in–14 NPT or M20x1.5 cable glands used with transmitter
2. Connect the cable to the core processor as described in the sensor documentation.
3. Feed the wires from the remote core processor through the conduit opening.
4. Connect wires to the appropriate terminals on the mating connector.
Tip
You may find it easier to unplug the mating connector to connect the wires. If you do so, remember to firmly reseat the mating connector and tighten the mating connector screws so that the mating connector cannot accidentally come loose.
38 Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
Wiring the transmitter to the sensor
October 2022
Figure 5-3: Wiring path for transmitters with aluminum housing
A. 4-wire cable
B. Transmitter conduit opening
C. Mating connector
Installation Manual 39
Wiring the transmitter to the sensor
October 2022
Installation Manual
Figure 5-4: Wiring path for transmitters with stainless steel housing
20001700
5.3
40
A. 4-wire cable
B. Transmitter conduit opening
C. Mating connector
Wire the remote core processor to the sensor using jacketed cable (9-wire)
Use this procedure to wire the remote core processor to the sensor using jacketed cable in a 9-wire remote sensor installation.
Prerequisites
For ATEX installations, the jacketed cable must be installed inside a user-supplied sealed metallic conduit that provides 360° termination shielding for the enclosed cable.
WARNING
Sensor wiring is intrinsically safe. To keep sensor wiring intrinsically safe, keep the sensor wiring separated from power supply wiring and output wiring.
NOTICE
• Any fittings, adapters, or blanking elements used on either conduit entries or threaded joints that are a part of flame proof joints must comply with the requirements of EN/IEC
Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
Wiring the transmitter to the sensor
October 2022
60079-1 & 60079-14 or CSA C22.2 No 30 & UL 1203 for Europe/International and North
America respectively.
Only qualified personnel can select and install these elements in accordance with
EN/IEC 60079-14 for ATEX/IECEx or to NEC/CEC for North America.
• To maintain the Ingress protection thread sealant, a sealing washer, or O-ring must be applied.
— For Zone 1 applications thread sealant must also comply with the requirements of
EN/IEC 60079-14 and thus must be non-setting, non-metallic, non-combustible, and maintain earthing between the equipment and conduit.
— For Class I, Groups A, B, C, and D applications thread sealant must also comply with the requirements of UL 1203/CSA C22.2 No. 30.
• Keep cable away from devices such as transformers, motors, and power lines, which produce large magnetic fields. Improper installation of cable, cable gland, or conduit could cause inaccurate measurements or flow meter failure.
• Improperly sealed housings can expose electronics to moisture, which can cause measurement error or flowmeter failure. Install drip legs in conduit and cable, if necessary. Inspect and grease all gaskets and O-rings. Fully close and tighten all housing covers and conduit openings.
Procedure
1. Run the cable through the conduit. Do not install 9-wire cable and power cable in the same conduit.
2. Remove the junction box cover and core processor end-cap.
3. At both the sensor and transmitter, do the following: a) Connect a male conduit connector and waterproof seal to the conduit opening for 9-wire.
b) Pass the cable through the conduit opening for the 9-wire cable.
c) Insert the stripped end of each wire into the corresponding terminal at the sensor and transmitter ends, matching by color. No bare wires should remain exposed.
Also see Sensor and remote core processor/transmitter terminals
.
Table 5-1: Sensor and remote core processor terminal designations
Wire color
Black
Brown
Red
Orange
Sensor terminal
No connection
1
2
3
1
2
3
Remote core processor terminal
Ground screw (see note)
Function
Drain wires
Drive +
Drive –
Lead length compensator/ composite RTD/ID resistor
Installation Manual 41
Wiring the transmitter to the sensor
October 2022
5.4
Installation Manual
20001700
Table 5-1: Sensor and remote core processor terminal designations
(continued)
Wire color
Yellow
Sensor terminal
4
Remote core processor terminal
4
Function
Green
Blue
Violet
Gray
White
7
8
5
6
9
7
8
5
6
9
Temperature return
Left pickoff +
Right pickoff +
Temperature +
Right pickoff –
Left pickoff – d) Tighten the screws to hold the wire in place.
e) Ensure integrity of gaskets, grease all O-rings, then replace the junction-box and transmitter housing covers and tighten all screws, as required.
Wire the remote core processor to the sensor using shielded or armored cable (9-wire)
Use this procedure to wire the remote core processor to the sensor using shielded or armored cable in a 9-wire remote sensor installation.
Prerequisites
For ATEX installations, shielded or armored cable must be installed with cable glands, at both the sensor and remote core processor ends. Cable glands that meet ATEX requirements can be purchased from Micro Motion. Cable glands from other vendors can be used.
NOTICE
• Keep cable away from devices such as transformers, motors, and power lines, which produce large magnetic fields. Improper installation of cable, cable gland, or conduit could cause inaccurate measurements or flow meter failure.
• Install cable glands in the 9-wire conduit opening in the transmitter housing and the sensor junction box. Ensure that the cable drain wires and shields do not make contact with the junction box or the transmitter housing. Improper installation of cable or cable glands could cause inaccurate measurements or flow meter failure.
• Improperly sealed housings can expose electronics to moisture, which can cause measurement error or flowmeter failure. Install drip legs in conduit and cable, if necessary. Inspect and grease all gaskets and O-rings. Fully close and tighten all housing covers and conduit openings.
42 Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
Wiring the transmitter to the sensor
October 2022
Procedure
1. Identify the components of the cable gland and cable.
Figure 5-5: Cable gland and cable (exploded view)
A B C D E F
G
A. Cable
B. Sealing nut
C. Compression nut
D. Brass compression ring
E. Braided shield
F. Cable
G. Tape or heat-shrink tubing
H. Clamp seat (shown as integral to nipple)
I. Nipple
H I
2. Unscrew the nipple from the compression nut.
3. Screw the nipple into the conduit opening for the 9-wire cable. Tighten it to one turn past hand-tight.
4. Slide the compression ring, compression nut, and sealing nut onto the cable. Make sure the compression ring is oriented so the taper will mate properly with the tapered end of the nipple.
5. Pass the cable end through the nipple so the braided shield slides over the tapered end of the nipple.
6. Slide the compression ring over the braided shield.
7. Screw the compression nut onto the nipple. Tighten the sealing nut and compression nut by hand to ensure that the compression ring traps the braided shield.
8. Use a 1 in (25 mm) wrench to tighten the sealing nut and compression nut 20 ft lbf
(27.1 N m) to 25 ft lbf (33.9 N m) of torque.
Installation Manual 43
Wiring the transmitter to the sensor
October 2022
Figure 5-6: Cross-section of assembled cable gland with cable
C
B
A
G A
Installation Manual
20001700
44
E
D
F
A. Cable
B. Sealing nut
C. Seal
D. Compression nut
E. Braided shield
F. Brass compression ring
G. Nipple
9. Remove the junction box cover and remote core processor end-cap.
10. At both the sensor and remote core processor, connect the cable according to the following procedure: a) Insert the stripped end of each wire into the corresponding terminal at the sensor and remote core processor ends, matching by color. No bare wires should remain exposed.
Also see Sensor and remote core processor/transmitter terminals
.
Table 5-2: Sensor and remote core processor terminal designations
Wire color
Black
Brown
Red
Orange
Yellow
Green
Blue
Sensor terminal
No connection
4
5
6
1
2
3
5
6
1
2
3
Remote core processor terminal
Ground screw (see notes)
4
Function
Drain wires
Drive +
Drive –
Lead length compensator/ composite RTD/ID resistor
Temperature return
Left pickoff +
Right pickoff +
Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
5.5
Table 5-2: Sensor and remote core processor terminal designations
(continued)
Wire color
Violet
Gray
White
Sensor terminal
7
8
9
7
8
Remote core processor terminal
9
Function
Temperature +
Right pickoff –
Left pickoff – b) Tighten the screws to hold the wires in place.
c) Ensure integrity of gaskets, grease all O-rings, then replace the junction box cover and remote core processor end-cap and tighten all screws, as required.
Sensor and remote core processor/transmitter terminals
This section describes the sensor to remote control processor terminals or the sensor to transmitter terminals.
Figure 5-7: All ELITE, H-Series, and T-Series sensor, and 2005 or newer F-Series sensor terminals
D
E
F
G
H
I
A B C
Wiring the transmitter to the sensor
October 2022
A. Violet
B. Yellow
C. Orange
D. Brown
E. White
F. Green
G. Red
H. Gray
I. Blue
Installation Manual 45
Wiring the transmitter to the sensor
October 2022
Figure 5-8: All D and DL, and pre-2005 F-Series sensor terminals
Installation Manual
20001700
46
Figure 5-9: DT sensor terminals (user-supplied metal junction box with terminal block)
7
8
9
5
6
3
4
1
2
A
A. Earth ground
Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
Wiring the transmitter to the sensor
October 2022
Figure 5-10: Remote core processor/transmitter terminals
J
A
B
C
I
H
G
F
E
D
A. Brown
B. Violet
C. Yellow
D. Orange
E. Gray
F. Blue
G. White
H. Green
I. Red
J. Ground screw (black)
Installation Manual 47
Wiring the transmitter to the sensor
October 2022
Installation Manual
20001700
48 Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
6
6.1
Grounding
October 2022
Grounding
Ground the meter components
• In integral installations, all components are grounded together.
• In 4-wire remote installations, the transmitter and sensor are grounded separately.
• In 9-wire remote installations, the transmitter/core processor assembly and sensor are grounded separately.
• In a remote core processor with remote sensor installation, the transmitter, remote core processor, and sensor are all grounded separately.
Prerequisites
If national standards are not in effect, adhere to the following guidelines for grounding:
• Use copper wire, 14 AWG (2.08 mm ² ) or larger wire size.
• Keep all ground leads as short as possible, less than 1 Ω impedance.
• Connect ground leads directly to earth, or follow plant standards.
Procedure
Depending on your installation type:
Option
For an integral installation
For all other installations
Description
Ground via the piping if possible (see the sensor documentation). If grounding via the piping is not possible, ground according to applicable local standards using the transmitter’s internal or external ground screw.
a. Ground the sensor according to the instructions in the sensor documentation.
b. Ground the transmitter according to applicable local standards, using the transmitter’s internal or external ground screw.
Installation Manual 49
Grounding
October 2022
Figure 6-1: Transmitter internal grounding screw
Installation Manual
20001700
Figure 6-2: Transmitter external grounding screw
50 Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
7
7.1
Wiring the power supply
October 2022
Wiring the power supply
Wire the power supply
A user-supplied switch may be installed in the power supply line. For compliance with lowvoltage directive 2006/95/EC (European installations), a switch in close proximity to the transmitter is required.
Procedure
1. Remove the transmitter housing cover.
2. Open the warning flap.
3. Connect the power supply wires to terminals 9 and 10.
Terminate the positive (line) wire on terminal 10 and the return (neutral) wire on terminal 9.
Figure 7-1: Power supply wiring terminals
Installation Manual
C
A B
A. Warning flap
B. Equipment ground
C. Power supply wiring terminals (9 and 10)
4. Ground the power supply using the equipment ground, also under the warning flap.
51
Wiring the power supply
October 2022
Installation Manual
20001700
52 Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
8
8.1
I/O wiring for transmitters with analog outputs
October 2022
I/O wiring for transmitters with analog outputs
Basic analog wiring
A
8.2
00042
B
A. mA Output loop (820 Ω maximum loop resistance)
B. Frequency receiving device (output voltage level is +24 VDC ± 3%, with a 2.2 kΩ pull-up resistor)
HART ® /analog single loop wiring
Note
For HART communications:
• 600 Ω maximum loop resistance
• 250 Ω minimum loop resistance
Installation Manual 53
I/O wiring for transmitters with analog outputs
October 2022
A
B
Installation Manual
20001700
8.3
54
A. 820 Ω maximum loop resistance
B. HART-compatible host or controller
RS-485 point-to-point wiring
B
C
RS-485A
RS-485B
A
A. Other devices
B. Primary controller
C. Multiplexer
Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
8.4
I/O wiring for transmitters with analog outputs
October 2022
HART multidrop wiring
Tip
For optimum HART communication, single-point ground the output loop to an instrument-grade ground.
B C
I give up
D E
F
A
A. 250–600 Ω resistance
B. HART-compatible host or controller
C. HART-compatible transmitters
D. 1700 or 2700 transmitter
E. SMART FAMILY ™ transmitters
F. 24 VDC loop power supply required for passive transmitters
Installation Manual 55
I/O wiring for transmitters with analog outputs
October 2022
Installation Manual
20001700
56 Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
9
9.1
I/O wiring for transmitters with intrinsically safe outputs
October 2022
I/O wiring for transmitters with intrinsically safe outputs
Safe area mA Output wiring (2700)
A mA1
B mA1
A mA2 mA2
A. External DC power supply (VDC)
B. R load
Installation Manual 57
I/O wiring for transmitters with intrinsically safe outputs
October 2022
Safe area mA Output load resistance values
Installation Manual
20001700
9.2
58
R max
= (V supply
− 12) / 0.023
Minimum 250Ω and 17.5V required for HART communications
A. External resistor R load
(ohms)
B. Supply voltage VDC (volts)
C. Operating region
Safe area HART/analog single-loop wiring
A mA1
B
C
A. External DC power supply (VDC)
B. R load
(250–600 Ω resistance)
C. HART-compatible host or controller
Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
I/O wiring for transmitters with intrinsically safe outputs
Safe area mA Output load resistance values
October 2022
9.3
R max
= (V supply
− 12) / 0.023
Minimum 250Ω and 17.5V required for HART communications
A. External resistor R load
(ohms)
B. Supply voltage VDC (volts)
C. Operating region
Safe area HART multidrop wiring
Tip
For optimum HART communication, single-point ground the output loop to an instrument-grade ground.
Installation Manual 59
I/O wiring for transmitters with intrinsically safe outputs
October 2022
B C
A
Installation Manual
20001700
D E
F
9.4
A. 250–600 Ω resistance
B. HART-compatible host or controller
C. HART-compatible transmitters
D. 1700 or 2700 transmitter with intrinsically safe outputs
E. SMART FAMILY transmitter
F. 24 VDC loop power supply required for HART 4–20 mA passive transmitters
Safe area Frequency Output/Discrete Output wiring
A
C
B
00042
A. External DC power supply (VDC)
B. Counter
C. R load
60 Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
I/O wiring for transmitters with intrinsically safe outputs
Safe area Frequency Output/Discrete Output load resistance values
October 2022
9.5
Installation Manual
R max
= (V supply
− 4) / 0.003
= (V supply
− 25) / 0.006
Minimum 100Ω for supply voltage less than 25.6 volts
A. External pull-up resistor R load range (ohms)
B. Supply voltage VDC (volts)
C. Operating region
Hazardous area wiring
Information provided about I.S. barriers is intended as an overview. Application-specific or product-specific questions should be addressed to the barrier manufacturer or
Micro Motion.
WARNING
• Hazardous voltage can cause severe injury or death. Shut off the power before wiring transmitter outputs.
• Improper wiring in a hazardous environment can cause an explosion. Install the transmitter only in an area that complies with the hazardous classification tag on the transmitter.
Table 9-1: Safety parameters
Parameter
Voltage (U i
)
Current (I i
)
Power (P i
)
4–20 mA
30 V
300 mA
1.0 W
Frequency/discrete
30 V
100 mA
0.75 W
61
I/O wiring for transmitters with intrinsically safe outputs
October 2022
Installation Manual
20001700
Table 9-1: Safety parameters (continued)
Parameter
Capacitance (C i
)
Inductance (L i
)
4–20 mA
0.0005 μF
0.0 mH
Frequency/discrete
0.0005 μF
0.0 mH
Voltage
Current
The transmitter’s safety parameters require the selected barrier’s opencircuit voltage to be limited to less than 30 VDC (V max
= 30 VDC). This voltage is the combination of the maximum safety barrier voltage
(typically 28 VDC) plus an additional 2 VDC for HART communications when communicating in the hazardous area.
The transmitter’s safety parameters require the selected barrier’s shortcircuit currents to sum to less than 300 mA (I milliamp outputs and 100 mA (I output.
max max
= 300 mA) for the
= 100 mA) for the frequency/discrete
Capacitance The capacitance (C capacitance (C o i
) of the transmitter is 0.0005 μF. This value added to the wire capacitance (C calculate the maximum length of the cable between the transmitter and the barrier: C i cable
) must be lower than the maximum allowable
) specified by the I.S. barrier. Use the following equation to
+ C cable
≤ C o
Inductance The inductance (L wiring inductance (L inductance (L o i
) of the transmitter is 0.0 mH. This value plus the field cable
), must be lower than the maximum allowable
) specified by the I.S. barrier. The following equation can then be used to calculate the maximum cable length between the transmitter and the barrier: L i
+ L cable
≤ L o
62 Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
9.5.1
I/O wiring for transmitters with intrinsically safe outputs
October 2022
Hazardous area mA Output wiring
A. Hazardous area
B. Safe area
C. V in
D. V out
E. Ground
F. R load
G. R barrier
Note
Add R load
and R barrier
to determine V in
.
Installation Manual 63
I/O wiring for transmitters with intrinsically safe outputs
October 2022
Safe area mA Output load resistance values
Installation Manual
20001700
R max
= (V supply
− 12) / 0.023
Minimum 250Ω and 17.5V required for HART communications
A. External resistor R load
(ohms)
B. Supply voltage VDC (volts)
C. Operating region
64 Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
9.5.2
I/O wiring for transmitters with intrinsically safe outputs
October 2022
Hazardous area Frequency Output/Discrete Output wiring using a galvanic isolator
A. Hazardous area
B. Safe area
C. External power supply
D. V out
E. R load
F. Galvanic isolator (see note)
G. Counter
Note
The galvanic isolator shown here has an internal 1000 Ω resistor used for sensing current:
• ON > 2.1 mA
• OFF < 1.2 mA
These current switching levels comply with DIN19234 (NAMUR)/DIN EN 60947-5-6/IEC
60947-5-6.
Installation Manual 65
I/O wiring for transmitters with intrinsically safe outputs
October 2022
9.5.3
Installation Manual
20001700
Hazardous area Frequency Output/Discrete Output wiring using barrier with external load resistance
A. Hazardous area
B. Safe area
C. R barrier
D. V in
E. V out
F. Counter
G. R load
H. Ground
Note
Add R barrier
and R load
to determine V in
.
66 Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
I/O wiring for transmitters with intrinsically safe outputs
Safe area Frequency Output/Discrete Output load resistance values
October 2022
R max
= (V supply
− 4) / 0.003
= (V supply
− 25) / 0.006
Minimum 100Ω for supply voltage less than 25.6 volts
A. External pull-up resistor R load range (ohms)
B. Supply voltage VDC (volts)
C. Operating region
Installation Manual 67
I/O wiring for transmitters with intrinsically safe outputs
October 2022
Installation Manual
20001700
68 Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
10
10.1
I/O wiring for 2700 with configurable input/outputs
October 2022
I/O wiring for 2700 with configurable input/outputs
Channel configuration
The six wiring terminals are divided into three pairs, and called Channels A, B, and C.
• Channel A = terminals 1 and 2
• Channel B = terminals 3 and 4
• Channel C = terminals 5 and 6
Variable assignments are governed by channel configuration.
Table 10-1: Channel configuration
Channel
A
B
C
Terminals
1, 2
3, 4
5, 6
Configuration options Power mA Output with HART/Bell202 Internal mA Output (default)
Frequency Output
Internal
Internal or external
Discrete Output
Frequency Output (default)
Discrete Output
Discrete Input
Internal or external
Internal or external
Internal or external
Internal or external
Notes
• For Channel A, the Bell 202 signal is superimposed on the mA Output.
• You must provide power to the outputs when a channel is set to external power.
• When both Channel B and Channel C are configured for Frequency Output (dual pulse),
Frequency Output 2 is generated from the same signal that is sent to the first
Frequency Output. Frequency Output 2 is electrically isolated but not independent.
• You cannot configure the combination of Channel B as Discrete Output and Channel C as Frequency Output.
Installation Manual 69
I/O wiring for 2700 with configurable input/outputs
October 2022
10.2
Basic mA Output wiring
A mA1
B mA2
10.3
A. 820 Ω maximum loop resistance
B. 420 Ω maximum loop resistance
HART/analog single loop wiring
Note
For HART communications:
• 600 Ω maximum loop resistance
• 250 Ω minimum loop resistance
Installation Manual
20001700
70 Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
A
I/O wiring for 2700 with configurable input/outputs
October 2022
B
10.4
A. 820 Ω maximum loop resistance
B. HART-compatible host or controller
HART multidrop wiring
Tip
For optimum HART communication, single-point ground the output loop to an instrument-grade ground.
B C
I give up
D E
F
A
Installation Manual
A. 250–600 Ω resistance
B. HART-compatible host or controller
C. HART-compatible transmitters
D. 2700 configurable I/O transmitter (internally powered outputs)
E. SMART FAMILY transmitters
F. 24 VDC loop power supply required for HART 4–20 mA passive transmitters
71
I/O wiring for 2700 with configurable input/outputs
October 2022
10.5
Installation Manual
20001700
Internally powered Frequency Output wiring on Channel B
00042
A
A. Counter
Output voltage versus load resistance
72
Maximum output voltage = 15 VDC ± 3%
A. High level output voltage (volts)
B. Load resistance (ohms)
Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
10.6
I/O wiring for 2700 with configurable input/outputs
October 2022
Externally powered Frequency Output wiring on Channel B
A
B
000042
C
A. Pull-up resistor
B. External DC power supply (3–30 VDC)
C. Counter
NOTICE
Exceeding 30 VDC can damage the transmitter. Terminal current must be less than 500 mA.
Recommended pull-up resistor versus supply voltage
Installation Manual
A. External pull-up resistor range (ohms)
B. Supply voltage (volts)
73
I/O wiring for 2700 with configurable input/outputs
October 2022
10.7
Installation Manual
20001700
Internally powered FO wiring on Channel C
Figure 10-1: Internally powered FO wiring on Channel C
A
A. Counter
00042
74
Maximum output voltage = 15 VDC ± 3%
A. High level output voltage (volts)
B. Load resistance (ohms)
Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
10.8
I/O wiring for 2700 with configurable input/outputs
October 2022
Externally powered Frequency Output wiring on Channel C
A
B
000042
C
A. Pull-up resistor
B. External DC power supply (3–30 VDC)
C. Counter
NOTICE
Exceeding 30 VDC can damage the transmitter. Terminal current must be less than 500 mA.
Recommended pull-up resistor versus supply voltage
Installation Manual
A. External pull-up resistor range (ohms)
B. Supply voltage (volts)
75
I/O wiring for 2700 with configurable input/outputs
October 2022
10.9
Installation Manual
20001700
Internally powered Discrete Output wiring on
Channel B
A
A. Total load
Output voltage versus load resistance
76
Maximum output voltage = 15 VDC ± 3%
A. High level output voltage (volts)
B. Load resistance (ohms)
Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
I/O wiring for 2700 with configurable input/outputs
October 2022
10.10
Externally powered Discrete Output wiring on
Channel B
B
A
A. External DC power supply (3–30 VDC)
B. Pull-up resistor or DC relay
NOTICE
Exceeding 30 VDC can damage the transmitter. Terminal current must be less than 500 mA.
Recommended pull-up resistor versus supply voltage
Installation Manual
A. External pull-up resistor range (ohms)
B. Supply voltage (volts)
77
I/O wiring for 2700 with configurable input/outputs
October 2022
Installation Manual
20001700
10.11
Internally powered Discrete Output wiring on
Channel C
A
A. Total load
Output voltage versus load resistance
78
Maximum output voltage = 15 VDC ± 3%
A. High level output voltage (volts)
B. Load resistance (ohms)
Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
I/O wiring for 2700 with configurable input/outputs
October 2022
10.12
Externally powered Discrete Output wiring on
Channel C
B
A
A. External DC power supply (3–30 VDC)
B. Pull-up resistor or DC relay
NOTICE
Exceeding 30 VDC can damage the transmitter. Terminal current must be less than 500 mA.
Recommended pull-up resistor versus supply voltage
Installation Manual
A. External pull-up resistor range (ohms)
B. Supply voltage (volts)
79
I/O wiring for 2700 with configurable input/outputs
October 2022
Installation Manual
20001700
10.13
Internally powered Discrete Input wiring
A
A. Switch
10.14
Externally powered Discrete Input wiring
80
A
B C
A. PLC or other device
B. Bipolar negative-positive-negative (NPN) transistor
C. Direct DC input
Power is supplied by either a PLC/other device or by direct DC input.
Table 10-2: Input voltage ranges for external power
VDC
3–30
0–0.8
0.8–3
Range
High level
Low level
Undefined
Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700
11
11.1
I/O wiring for 2700 with F OUNDATION fieldbus or PROFIBUS-PA
October 2022
I/O wiring for 2700 with F OUNDATION fieldbus or PROFIBUS-PA
F OUNDATION fieldbus wiring
See the following wiring diagram, and refer to the F OUNDATION fieldbus wiring specification.
Important
The transmitter is either FISCO or FNICO approved. For FISCO-approved transmitters, a barrier is required.
Figure 11-1: F OUNDATION fieldbus wiring diagram
A B
C
D
E
11.2
A. Bus power supply
B. F OUNDATION fieldbus network per F OUNDATION fieldbus wiring specification
C. Spur to network per F OUNDATION fieldbus wiring specification
D. Terminals 1 and 2
E. Terminals 3 – 6 (unused)
Note
The fieldbus communication terminals (1 and 2) are not polarity-sensitive.
PROFIBUS-PA wiring
See the following wiring diagram, and refer to the PROFIBUS-PA User and Installation
Guideline published by PNO.
Important
• The transmitter is FISCO approved.
• For intrinsically safe wiring, see the PROFIBUS-PA User and Installation Guideline .
Installation Manual 81
I/O wiring for 2700 with F OUNDATION fieldbus or PROFIBUS-PA
October 2022
Figure 11-2: PROFIBUS-PA wiring diagram
A B
C
E
D
Installation Manual
20001700
A. Bus power supply
B. PROFIBUS-PA segment per PROFIBUS-PA User and Installation Guideline
C. Spur to PROFIBUS-PA segment per PROFIBUS-PA User and Installation Guideline
D. Terminals 1 and 2
E. Terminals 3 – 6 (unused)
Note
The PROFIBUS communication terminals (1 and 2) are not polarity-sensitive.
82 Micro Motion 1700 and 2700 Transmitters
Installation Manual
20001700 October 2022
Installation Manual 83
For more information: www.emerson.com
© 2022 Micro Motion, Inc. All rights reserved.
The Emerson logo is a trademark and service mark of Emerson
Electric Co. Micro Motion, ELITE, ProLink, MVD and MVD Direct
Connect marks are marks of one of the Emerson Automation
Solutions family of companies. All other marks are property of their respective owners.
*20001700*
20001700
Rev. CH
2022
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 5 Before you begin
- 5 1.1 About this document
- 5 1.2 Hazard messages
- 5 1.3 Related documentation
- 7 Planning
- 7 2.1 Meter components
- 7 2.2 Installation types
- 12 2.3 Maximum cable lengths between sensor and transmitter
- 13 2.4 Output options
- 14 2.5 Electrical connections
- 14 2.6 Environmental limits
- 15 2.7 Hazardous area classifications
- 15 2.8 Power requirements
- 17 Mounting
- 17 3.1 Mounting for integral installations
- 17 3.2 Orientation
- 17 3.3 Accessibility for maintenance
- 17 3.4 Mounting options
- 23 3.5 Rotate the transmitter on the sensor (optional)
- 24 3.6 Rotate the user interface on the transmitter (optional)
- 27 Preparing the wires
- 27 4.1 Prepare the 4-wire cable
- 30 4.2 Prepare the 9-wire cable
- 37 Wiring the transmitter to the sensor
- 37 5.1 Wire the transmitter to the sensor (4-wire)
- 38 5.2 Wire the transmitter to the remote core processor (4-wire)
- 40 5.3 Wire the remote core processor to the sensor using jacketed cable (9-wire)
- 42 5.4 Wire the remote core processor to the sensor using shielded or armored cable (9-wire)
- 45 5.5 Sensor and remote core processor/transmitter terminals
- 49 Grounding
- 49 6.1 Ground the meter components
- 51 Wiring the power supply
- 51 7.1 Wire the power supply
- 53 I/O wiring for transmitters with analog outputs
- 53 8.1 Basic analog wiring