Schneider Electric Premium, Altivar, Icla Advantys STB and FTB on CANopen System user guide
Annonce
Annonce
Premium Altivar
IclA Magelis
System User Guide
[
source code
]
SEP 2006
Contents
Introduction
This document is intended to provide a quick introduction to the described System.
It is not intended to replace any specific product documentation. On the contrary, it offers additional information to the product documentation, for installing, configuring and starting up the system.
A detailed functional description or the specification for a specific user application is not part of this document. Nevertheless, the document outlines some typical applications where the system might be implemented.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 1
Abbreviations
Word / Expression
AC
Advantys
Altivar
CB
DC
EDS
E-OFF
Harmony
HMI
I/O
IclA (ICLA)
Lexium/Lexium05
Magelis
Micro
PC
Phaseo
PLC
Powersuite
Premium
Preventa
PS
SE
Sycon
Telefast
Tesys U
Twido
TwidoSoft
Unity (Pro)
Vijeo Designer
VSD
WxHxD
XBT-L1000
Signification
Alternating Current
SE product name for a family of I/O modules
SE product name for a family of VSDs
Circuit Breaker
Direct Current
Electronic Data Sheet
Emergency-off switch
SE product name for a family of switches and indicators
Human Machine Interface
Input/Output
SE product name for a compact drive
SE product name for a family of servo-drives
SE product name for a family of HMI-Devices
SE product name for a middle range family of PLCs
Personal Computer
SE product name for a family of power supplies
Programmable Logic Computer
An SE software product for configuring ALTIVAR drives
SE product name for a middle range family of PLCs
SE product name for a family of safety devices
Power Supply
Schneider Electric
SE product name of a Field bus programming software
SE product name for a series of distributed I/O devices
SE product name for a decentralized I/O System (Small Terminal
Block)
SE product name of a middle range family of PLCs
SE product name for a PLC programming software
SE product name for a PLC programming software
An SE software product for programming Magelis HMI devices
Variable Speed Drive
Dimensions : Width, Height and Depth
An SE software product for programming Magelis HMI devices
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 2
Application Source Code
Introduction
Examples of the source code and wiring diagrams used to attain the system function as described in this document can be downloaded from our „Village“ website under this link.
Typical Applications
Introduction
Here you will find a list of the typical applications, and their market segments, where this system or subsystem can be applied:
Industrial
Large automated machine or plant components with decentralized machine modules
Remote automation systems used to supplement large and medium-sized machines
Machines
Packaging systems
Textile and printing machines
Woodworking and metal working
Food & Drug
Filling lines
Application Description Image
Metal working This machine is used for bending sheet metal.
Woodworking machines This application cuts profiles in the edges of wood panelling.
Filling machine As a component of a bottling system, the bottles are aligned and filled.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 3
System
Introduction
The system chapter describes the architecture, the dimensions, the quantities and different types of components used within this system.
Architecture
General
The control section of this application consists of a Premium PLC which can be operated via a connected Magelis HMI panel at the user level. The machine section is implemented using an Altivar 31 variable speed drive and IclA compact drives which are connected to the
PLC via the CANopen bus system. The remote control cubicle consists of the STB I/O platform, motor starters and an additional HMI terminal.
A pre-assembled cable is used between the motor starters and I/O platform. The HMI is connected to the I/O platform directly via Modbus. The STB I/O platform and external FTB
I/O modules communicate with the PLC via the CANopen bus.
The solution illustrated below offers two optional safety packages: A Preventa evaluation unit featuring an emergency-off function that can be accessed via a tamper-proof emergency-off switch and a second evaluation unit of the same type which ensures door safety within the context of this application due to the use of door contact switches.
Layout
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 4
Components
Hardware:
Compact master switch (NSC100N) with undervoltage release
Preventa safety relay
XCS door-safety switch
XALK locking-type emergency-off switch with rotary unlocking (tamper-proof)
TeSys D motor contactor
GV2-ME motor circuit-breaker (short-circuit and overcurrent protection) for the compact drive’s power supply
GV2-L motor circuit-breaker (short-circuit protection) for the variable speed drive
Phaseo ABL7RP and ABL7UPS power supply units
Altivar ATV31 variable speed drive with integrated CANopen interface
Intelligent IclA compact drive with CANopen connection cable
Modular TeSys U load contactors with parallel wiring module
Advantys STB I/O platform with CANopen interface
Advantys FTB I/O module with CANopen (IP67)
Magelis XBT-G full-graphic display terminal and Magelis XBT-N text display terminal
XALD pushbutton housing with control and signaling units and XVB signal beacon
Premium PLC with CANopen card and Ethernet port
Telefast terminal block
Standard AC motors
Software:
Unity Pro XL V2.1
SyCon V2.9
Advantys Configuration Software V2.0
CANopen Symbol Tool V1.4
PowerSuite V2.0
Vijeo-Designer V4.20
XBT-L1000 V4.42
Quantities of
Components
For a complete and detailed list of components, the quantities required and the order numbers, please refer to the components list at the rear of this document.
Degree of
Protection
Technical
Data
Not all the components in this configuration are designed to withstand the same environmental conditions. Some components may need additional protection, in the form of housings, depending on the environment in which you intend to use them. For environmental details of the individual components please refer to the list in the appendix of this document and the appropriate user manual.
Supply voltage
Total supply output
Speed drive rated powers
Motor brake
AC motors
Connector cross-section
Safety category
400 V AC
~ 10 kW
Not fitted
3x 0.18 kW
3x 0.37 kW
5x 2.5mm² (L1, L2, L3, N, PE)
Cat. 3 (optional)
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 5
Safety Note
Dimensions
The standard and level of safety you apply to your application is determined by your system design and the overall extent to which your system may be a hazard to people and machinery.
As there are no moving mechanical parts in this application example, category 3
(according to EN954-1) has been selected as an optional safety level.
Whether or not the above safety category should be applied to your system should be ascertained with a proper risk analysis.
This document is not comprehensive for any systems using the given architecture and does not absolve users of their duty to uphold the safety requirements with respect to the equipment used in their systems or of compliance with either national or international safety laws and regulations
The dimensions of the devices used (e.g., the PLC, variable speed drive and power supply) are suitable for installation inside a control cabinet measuring 1600x600x300 mm
(WxHxD).
In addition, the display and control elements required to control the system can be integrated into the control cabinet door along with an emergency-off switch with an acknowledgement button.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 6
Installation
Introduction
This chapter describes the steps necessary to set up the hardware and configure the software required to fulfill the described function of the application.
Assembly
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 7
Notes
The purpose of configuring this application is to enable operation of the devices used.
The components and programs listed below represent a cross-section of the components required for the purposes of control and signal transmission.
This document does not claim to be comprehensive and does not absolve users of their duty to check the safety requirements of their equipment and to ensure compliance with relevant national and international rules and regulations in this respect.
Safety category 3, which is suggested here as one possible option, is not necessarily required/adequate for all applications. The safety category required is defined by a risk analysis which must be defined and verified for each individual system.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 8
General
Hardware
The components designed for installation in a control cabinet (i.e., safety modules, line circuit breakers, contactors, motor circuit-breakers, and Advantys STB I/O modules) can be snapped onto a 35 mm top-hat rail.
The master switch, Premium PLC, signal beacon, Phaseo power supply unit, and Altivar variable speed drive are screwed directly onto the mounting plate. If you are using the
Altivar 31, these components can also be snapped onto a top-hat rail using an adapter.
The emergency-off and door-safety switches, as well as the housing for the display and acknowledge indicators, are designed for backplane assembly in the field. With the exception of the door-safety switch, all switches can also be installed directly in a control cabinet (e.g., in cabinet door) without their housings.
There are two options for installing XB5 pushbuttons or indicator lamps: These pushbuttons or switches can be installed either in a 22 mm hole, e.g., drilled into the front door of the control cabinet or in a type XALD housing suitable for up to 5 pushbuttons or indicator lamps. The XALD pushbutton housing is designed for both backplane assembly and direct wall mounting.
In the case of the Magelis terminals, a cut-out is required in the front of the housing in order to facilitate securing to the housing by means of brackets/spring clamps.
The IclA compact drive and IP67 I/O modules are mounted outside the control cabinet.
400 V/3~ wiring for load circuits (ATV, TeSys U)
240 V~ wiring for power supplies
24 V- wiring for control circuits and PLC power supply, display terminals, I/O modules,
HMI and compact drives
The individual components must be connected in accordance with the detailed circuit diagram in order to ensure that they function correctly.
CANopen cables are installed for the communication link between the PLC and the devices inside the control cabinet.
CANopen bus cables are also fitted between the PLC and the relevant remote STB I/O islands, IP67 I/O modules and IclA compact drives.
MERLIN GERIN compact master switch
NSC100N
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 9
Preventa safety relay
XPS AF5130
Door-safety switch
XCS TA791
EMERGENCY-OFF
Switch
(tamper-proof)
XALK178G
Contactor
LC1-D12BL
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 10
Motor circuit-breaker
GV2-L08
Motor circuit-breaker
GV2-ME08
Phaseo power supply
ABL-7RP2403
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 11
Phaseo power supply
ABL-7RP2405
Phaseo power supply
ABL-7UPS24200
Altivar 31 variable speed drive
ATV31H018M2
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 12
Berger Lahr IclA intelligent compact drive
IFE71/2CAN-DS
IclA intelligent compact drive
Structure
IclA intelligent compact drive
Connections
1 EC motor
2 Electronic housing
3 Cable-gland slide-in module
4 I/O slide-in module with industrial socket connection
5 DIP switches for settings
6 Electronic housing cover, not to be removed
7 Connector housing cover, to be removed for installation
8 Cover with industrial socket connection for DC supply and field bus IN/OUT connection
9 Electrical interface
1 Power supply
2 Profibus DP field bus interface
3 CAN or RS485 field bus interface
4 24 V signal interface
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 13
IclA intelligent compact drive
Supply voltage connection
PIN Signal Meaning
1
2
V DC
GND
24/35 V DC supply voltage
GND for supply voltage, connected internally to GND of CAN, RS485 and 24 V signal interface
IclA intelligent compact drive
CANopen bus connection
TeSys U module contactor
LUB12, LUCA05BL,
LUFC00, LU9BN11C
PIN Signal Meaning
3
6
4
CAN_H
CAN_L
GND
CAN signal interface
CAN signal interface
Connected internally to the power supply GND
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 14
Advantys STB
I/O platform (IP20)
FTXCNTL12
Advantys STB fieldbus coupler module
CANopen
FTXCNTL12
1 Fieldbus interface
2 Top rotary switch
3 Bottom rotary switch
4 Supply interface
5 LED panel
6 Attachment screw
7 Card slot for memory module
8 Cover for CFG port
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 15
Advantys STB field power supply
STB PDT3100
Advantys STB digital 24 V DC input module
STB DDI3610
1 +24 V DC sensor bus power
2 -24 V DC return line for sensor power supply
3 +24 V DC actuator bus power
4 –24 V DC return line for actuator power supply
1 +24 V DC to sensor 1 (top) and sensor 4 (bottom)
2 Input from sensor 1 (top) and sensor 4 (bottom)
3 +24 V DC to sensor 2 (top) and sensor 5 (bottom)
4 Input from sensor 2 (top) and sensor 5 (bottom)
5 +24 V DC to sensor 3 (top) and sensor 6 (bottom)
6 Input from sensor 3 (top) and sensor 6 (bottom)
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 16
Advantys STB digital 24 V DC output module
STB DDO3600
Advantys STB relay output module
STB DRC3210
1 Output to actuator 1 (top) and actuator 4 (bottom)
2 Field-power-supply return line from actuators 1 and 4
3 Output to actuator 2 (top) and actuator 5 (bottom)
4 Field-power-supply return line from actuators 2 and 5
5 Output to actuator 3 (top) and actuator 6 (bottom)
6 Field-power-supply return line from actuators 3 and 6
1 Relay ground connections
2 NO contact connections
3 NC contact connections
4 Safety ground connection point for field device (bottom)
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 17
Advantys STB analog current input module
STB ACI1230
Advantys STB analog current output module
STB ACO1210
1 Inputs from sensor 1 (top) and sensor 2 (bottom)
2 Return lines from sensor 1 (top) and sensor 2 (bottom)
Premium_Altivar_ICLA_Magelis_EN.doc
1 Outputs to actuator 1 (top) and actuator 2 (bottom)
2 Field-power-return lines from actuator 1 (top) and actuator 2 (bottom)
Schneider Electric 18
Advantys FTB
I/O module (IP67)
FTB1CN12E04SPO
Signal beacon
XVB-C
Magelis text display
XBT-N401
Magelis full-graphic display terminal
XBT-G4330
Ethernet port
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 19
Premium
PLC processor module
TSX P571634
Premium
PLC power supply module
1 Display module
3 TER port
4 AUX port
5 PCMCIA slot
for memory card
6 PCMCIA slot
communication card
8 Ethernet port
10 RESET button
Premium
CANopen machine bus
TSX CPP110
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 20
Premium digital input module
TSX DEY16D2
Premium digital output module
TSX DSY16T2
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 21
Premium analog input module
TSX AEY1600 with
Telefast 2 terminal block
ABE 7CPA02
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 22
Premium analog output module
TSX ASY410
Premium
Ethernet module
TSX ETY4103
Ethernet port
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 23
General
Software
Software is primarily used for programming the Premium PLC and configuring the CANopen communication as well as for generating the visualization displays.
The PLC is programmed using the Unity Pro XL programming tool. The CANopen bus is configured using the SyCon software.
Within the context of the STB I/O module, the Advantys Configuration Software is used for island configuration and to create the EDS file that is essential for the CANopen communication.
The HMI application on the XBT-G4330 Magelis display terminal is configured using Vijeo
Designer. For the XBT-N401 text display, the XBT-L1000 software tool is available.
Although Altivar 31 variable speed drives can be parameterized using the front panel, the
PowerSuite software is a more user-friendly option. As well as providing a convenient means of setting speed-drive parameters, this software also enables data to be saved and archived.
These functions are extremely useful as they mean that parameters can be restored rapidly whenever service tasks need to be performed. The software can also help with online parameter optimization. The software is also supplied with the variable speed drive.
To use the software packages, your PC must have the appropriate Microsoft Windows operating system installed:
Windows 2000 or
Windows XP
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 24
The software tools have the following default installation paths:
Unity Pro XL
C:\Program Files\Schneider Electric\Unity Pro
SyCon
C:\Program Files\Schneider Electric\SyCon
Advantys Configuration Software
C:\Program Files\Schneider Electric\Advantys
PowerSuite ATV31
C:\Program Files\Schneider Electric\PowerSuite.Launch
Vijeo Designer
C:\Program Files\Schneider Electric\VijeoDesigner
XBT-L1000
C:\Program Files\Schneider Electric\XBT-L1000
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 25
General
Communication
The following methods of communication are used between devices:
CANopen
Uni-Telway
Modbus
Parallel cabling
The machine bus enabling communication between the PLC and fieldbus devices is implemented in the form of CANopen .
Uni-Telway is used between the PLC and display terminal (Magelis XBT-G).
Modbus is used for data exchange between the Advantys STB and remote HMI (Magelis
XBT-N).
Parallel cabling uses a pre-assembled cable to connect the I/O platform (Advantys STB) to the motor starter. This rules out the possibility of cabling errors.
Programming Cable
TSX PCX 1031
Serial link between PC with Unity Pro and PLC
(TER/AUX) to enable programming
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 26
Communication Cable
XBT Z968
And
Cable Adapter
XBTZG999
The cable is required to make the connection between the XBTG HMI
(COM1, SUB-D-25) and the PLC (TER or AUX,
MiniDin).
Programming Cable
XBT Z915
Used for programming the XBTN HMI via the serial interface on the
PC, with HMI software.
Programming Cable
STB XCA 4002
To establish a connection between the
Advantys STB and the configuration software, the cable is attached to the CFG port on the
Advantys and the serial interface on the PC.
Data Cable
XBT Z988
The XBTZ988 data cable is required to connect the XBTN HMI to the Advantys STB
( CFG port).
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 27
Programming Cable
VW3 A8 106
The Altivar drives are parameterized via the serial interface on the
PC using PowerSuite.
The cable can be connected to the speed drives directly or to the
CANopen taps via the
PowerSuite port.
CANopen Machine Bus
TSX CPP110
The CANopen interface card (1) is inserted into the second PCMCIA slot on the Premium PLC.
The connector is mounted on a top-hat rail and has a 9-pin sub-D socket.
CANopen Plug
TSX CAN KCDF 90T
Connection of the
CANopen cable to the
TSXCPP110. Plug incl. terminating resistor.
CANopen cable
TSX CAN CD50
Flexible cable.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 28
CANopen tap
VW3 CAN TAP2
Connection of two
Altivar 31 variable speed drives. Port for configuring speed drive using PowerSuite.
Switch-based terminating resistor.
CANopen branching cable
VW3 CAN RR1
Connection between tap and Altivar 31.
Two RJ54 connectors.
CANopen tap
VW3 CAN TDM4
Connection of IclA and
Advantys STB to 9-pin sub-D ports.
Switch-based terminating resistor.
CANopen branching cable
TSX CAN CADD1
Connection between tap and Advantys STB.
Two female 9-pin sub-D connectors.
Pin Description
CH Polarity CAN_H
CL Polarity CAN_L
CG Ground
V+ Optional
power supply
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 29
Power Supply Cable
0062501470030
Open-ended industrial socket connection for
DC supply from IclA compact drive.
Length: 3 m.
CANopen Connector
Set
0062501526001
Connector set for assembly of CANopen cables for industrial socket connections.
1 x M12 male connector
1 x M12 female connector
1 x M12 protective cap
CANopen Bus
Connection Cable
FTXCN3210
Series connection of
FTB modules starting from the VW3 CAN
TDM4 CANopen tap.
Premium_Altivar_ICLA_Magelis_EN.doc
PIN Signal Color
1 Shld -
2 V+ Red
3 GND Black
4 CAN_H White
5 CAN_L Blue
Schneider Electric 30
Power Supply
Connection Cable
FTXDP2210
Linking up the power supply from one FTB module to the next.
Advantys FTB
CANopen Terminating
Resistor
FTXCNTL12
Connection to final FTB module via BUS OUT connector.
Connection Cable
LU9R10
Parallel connection of
LUF C00 communication module on TeSys U with
EPI2145 special module of STB platform.
Two RJ54 connectors.
PIN Signal Wire
1 0 V 1
2 0 V 2
3 PE Green/yellow
4 +24 V DI 3
5 +24 V DO 4
1 EPI2145 STB module
2 LUF C00 communication module on TeSys U
3 LU9R10 connection cable
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 31
Implementation
Introduction
The implementation chapter describes all the steps necessary to initialize, to configure, to program and start-up the system to achieve the application functions as listed below.
Function
Signal
Beacon
Instructions for switching on and functional description
1. Activate all safety devices and motor circuit-breakers.
2. Activate the master mains switch.
3. Clear the emergency off.
4. Establish and acknowledge door safety.
5. Wait until the red lamp goes off.
6. Error messages (which are indicated by the blue lamp) can be reset using the “Reset” button if necessary.
7. Now you can select Auto, HMI or Manu mode on the main screen.
8. A pending bus-node connection error will be indicated by the “CANopen” button lighting up red. Individual bus-node stati are listed in the “CANopen” diagnostics window.
9. Select HMI mode: By selecting individual devices you can access various operational modes and set certain speed and position parameters. Error messages are also shown in more detail.
10. Select Manu mode: In this mode, you can control the TeSys U module contactors using the remote terminal and buttons.
11. Select Auto mode: Once Auto mode has been activated, you can initiate an automatic control process via the Start button. The individual drives are started and stopped one after the other, running in different directions and at various speeds. Auto mode stops whenever an error occurs and starts up again once a restart is made.
The signal beacon indicates the various system states and consists of 5 signaling elements:
Blue lamp:
Red lamp:
CANopen bus or logic error – lamp lights up
Fault indication for emergency-off/safety violations - lamp flashes
Green lamp: State: System ready – lamp lights up
Operation: System running normally – lamp flashes
Yellow lamp: Automatic operation: System running in Auto mode – lamp lights up
Siren: Error or fault pending – siren sounds for 3 seconds (1 Hz)
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 32
Functional
Layout
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 33
Communication
Introduction
This chapter describes the data passed via the communications bus (e.g., Modbus
Plus or TCP/IP) that is not bound directly with digital or analog hardware.
The list contains:
The device links
Direction of data flow
symbolic name and
Bus address of the device concerned.
Device Links
Within the context of this application, the CANopen, Modbus and Uni-Telway bus systems are used along with Ethernet to transfer the configuration.
The following devices are connected via CANopen:
One Premium PLC, bus address 1
Three Altivar 31 variable speed drives, bus addresses 2 – 4
Two IclA IFE7 compact drives, bus addresses 5 and 6
Three Advantys FTB I/O modules, bus addresses 7 - 9
One Advantys STB I/O platform, bus address 10
Only two devices are connected via Modbus:
Advantys STB I/O platform, CFG port, bus address 1
Magelis XBT-N panel (no bus address assigned)
Only two devices communicate with each other via Uni-Telway :
Premium PLC, CPU module AUX port
Magelis XBT-G terminal, COM1
Two devices are configured via Ethernet:
Premium PLC, Ethernet port, IP address 192.168.100.72
Magelis XBT-G terminal, Ethernet port, IP address 192.168.100.73
Startup
Proceed as follows to establish communication between the devices:
Set the CANopen address and transmission rate for all devices
Create the EDS file for the STB island using the Advantys configuration tool
Configure the CANopen bus using the SyCon software
Generate the variable import file for Unity Pro using the CANopen Symbol Tool
Exchange data between the XBT-N terminal and Premium PLC via STB module
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 34
Datalink
Drive_1 <> PLC
Datalink
Drive_2 <> PLC
Datalink
Drive_3 <> PLC
Datalink
IclA_1 <> PLC
Premium-CPU (CANopen-Master, #1) Altivar31_1 (CANopen-Slave#2)
Data Direction ATV -> PLC
Address Name Index Designation
%MW1000
%MW1001
ATV01_STATE / state
ATV01_STATE / rpm
Name
6041
6044
Drivecom status register
Control effort
Data Direction SPS -> ATV
Index Designation Address
%MW1500
%MW1501
ATV01_CTRL / cmd
ATV01_CTRL / rpm
6040
6042
Drivecom command register
Target velocity
Premium-CPU (CANopen-Master, #1) Altivar31_2 (CANopen-Slave#3)
Data Direction ATV -> PLC
Address Name Index Designation
%MW1002
%MW1003
ATV02_STATE / state
ATV02_STATE / rpm
Name
6041
6044
Drivecom status register
Control effort
Data Direction PLC -> ATV
Index Designation Address
%MW1502
%MW1503
ATV02_CTRL / cmd
ATV02_CTRL / rpm
6040
6042
Drivecom command register
Target velocity
Premium-CPU (CANopen-Master, #1) Altivar31_3 (CANopen-Slave#4)
Data Direction ATV -> PLC
Address Name Index Designation
%MW1004
%MW1005
Address
%MW1504
%MW1505
ATV03_STATE / state
ATV03_STATE / rpm
Name
6041 Drivecom status register
Control effort
Data Direction PLC -> ATV
ATV03_CTRL / cmd
ATV03_CTRL / rpm
6044
Index
6040
6042
Designation
Drivecom command register
Target velocity
Premium-CPU (CANopen-Master, #1) IclA_IFE_01 (CANopen-Slave#5)
Data Direction IclA -> PLC
Address Name Index Designation
%MW1006
%MW1007
%MW1008
%MW1009
Address
%MW1506
%MW1507
%MW1508
%MW1509
ICLA01_IN[0]
ICLA01_IN[1]
ICLA01_IN[2]
ICLA01_IN[3]
301E.4
301E.3
301E.7
301E.8 pdo4_driveStat pdo4_modeStat pdo4_Act8 pdo4_Act32
Data Direction PLC -> IclA
Name
ICLA01_OUT[0]
Index
301E.1
Designation pdo4_driveCtrl
ICLA01_OUT[1]
ICLA01_OUT[2]
ICLA01_OUT[3]
301E.2 pdo4_modeCtrl
301E.5 pdo4_Ref16
301E.6 pdo4_Ref32
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 35
Datalink
IclA_2 <> PLC
Datalink
FTB_1 <> PLC
Datalink
FTB_2 <> PLC
Datalink
FTB_3 <> PLC
Premium-CPU (CANopen-Master, #1) IclA_IFE_02 (CANopen-Slave#6)
Data Direction IclA -> PLC
Address Name Index Designation
%MW1010
%MW1011
%MW1012
%MW1013
ICLA02_IN[0]
ICLA02_IN[1]
ICLA02_IN[2]
301E.4 pdo4_driveStat
301E.3 pdo4_modeStat
301E.7 pdo4_Act8
ICLA02_IN[3] 301E.8 pdo4_Act32
Data Direction PLC -> IclA
Name Index Designation Address
%MW1510
%MW1511
%MW1512
%MW1513
ICLA02_OUT[0]
ICLA02_OUT[1]
ICLA02_OUT[2]
ICLA02_OUT[3]
301E.1
301E.2
301E.5
301E.6 pdo4_driveCtrl pdo4_modeCtrl pdo4_Ref16 pdo4_Ref32
Premium-CPU (CANopen-Master, #1) Adv_FTB_01 (CANopen-Slave#7)
Data Direction FTB -> PLC
Address Name Index Designation
%MW1014
Address
%MW1514
Name
6000.1
6000.2
Data Direction PLC -> FTB
Index
6200.1
Digital Input 8 Bits Pin4
Digital Input 8 Bits Pin2
Designation
Write Outputs 5 to 8
Premium-CPU (CANopen-Master, #1) Adv_FTB_02 (CANopen-Slave#8)
Data Direction FTB -> PLC
Address
%MW1015
Name Index
6000.1
Designation
Digital Input 8 Bits Pin4
Address Name
6000.2 Digital Input 8 Bits Pin2
Data Direction PLC -> FTB
Index Designation
%MW1515 6200.1 Write Outputs 5 to 8
Premium-CPU (CANopen-Master, #1) Adv_FTB_03 (CANopen-Slave#9)
Data Direction FTB -> PLC
Address Name Index Designation
%MW1016
Address
%MW1516
Name
6000.1
6000.2
Digital Input 8 Bits Pin4
Digital Input 8 Bits Pin2
Data Direction SPS -> FTB
Index Designation
6200.1 Write Outputs 5 to 8
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 36
Datalink
STB_1 <> PLC
Premium-CPU (CANopen-Master, #1) Adv_STB_01 (CANopen-Slave#10)
Data Direction STB -> PLC
Address Name Index Designation
%MW1017
%MW1018
%MW1019
%MW1020
%MW1021
%MW1022
%MW1023
%MW1024
%MW1025
%MW1026
%MW1027
%MW1028
%MW1029
%MW1030
%MW1031
%MW1032
%MW1033
%MW1034
%MW1035
HMI_SPS_WD1
HMI_SPS_WD2
HMI_SPS_WD3
6000.1
6000.2
6000.3
6000.4
6000.5
6000.6
6000.7
6000.8
6000.9
6000.A
6000.B
6000.C
6000.D
6000.E
6000.F
6000.10
6000.11
6000.12
6000.13
6000.14
6000.15
6000.16
6000.17
Digital Input Block No.1
Digital Input Block No.2
Digital Input Block No.3
Digital Input Block No.4
Digital Input Block No.5
Digital Input Block No.6
Digital Input Block No.7
Digital Input Block No.8
Digital Input Block No.9
Digital Input Block No.10
Digital Input Block No.11
Digital Input Block No.12
Digital Input Block No.13
Digital Input Block No.14
Digital Input Block No.15
Digital Input Block No.16
Digital Input Block No.17
Digital Input Block No.18
Digital Input Block No.19
Digital Input Block No.20
Digital Input Block No.21
Digital Input Block No.22
Digital Input Block No.23
6000.18 Digital Input Block No.24
6000.19 Digital Input Block No.25
6000.1A Digital Input Block No.26
6401.1 Analog Input Block No.1
6401.2
2200
2201
2202
Analog Input Block No.2
2-byte Special Input Object
2-byte Special Input Object
2-byte Special Input Object
HMI_SPS_WD4 2203
Data Direction PLC -> STB
2-byte Special Input Object
Name Index Designation Address
%MW1517
%MW1518
%MW1519
%MW1520
%MW1521
%MW1522
%MW1523
%MW1524
SPS_HMI_WD1
SPS_HMI_WD2
SPS_HMI_WD3
SPS_HMI_WD4
6200.1 Digital Output Block No.1
6200.2 Digital Output Block No.2
6200.3 Digital Output Block No.3
6200.4 Digital Output Block No.4
6411.1 Analog Output Block No.1
6411.2 Analog Output Block No.2
3200
3201
3202
3203
2-byte Special Output Object
2-byte Special Output Object
2-byte Special Output Object
2-byte Special Output Object
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 37
Datalink
HMI <> PLC
Premium SPS (Uni-Telway)
Address Name
XBT-G4330 (Uni-Telway)
Data Direction HMI -> PLC
Address Designation
%MW20.6 ATV01_Right_hmi
%MW20.7 ATV01_Left_hmi
%MW20.8 ATV01_Fast_hmi
%MW21 ATV01_RPM1_hmi
%MW25.6 ATV02_Right_hmi
%MW25.7 ATV02_Left_hmi
%MW25.8 ATV02_Fast_hmi
%MW26 ATV02_RPM1_hmi
%MW30.6 ATV03_Right_hmi
%MW30.7 ATV03_Left_hmi
%MW30.8 ATV03_Fast_hmi
%MW31 ATV03_RPM1_hmi
%MW35.0 ATV_EStop_hmi
%MW35.1 ATV_Ackn_hmi
%MW50.0 Icla01_power_hmi
%MW20:X06 ATV01.ATV_Right
%MW20:X07 ATV01.ATV_Left
%MW20:X08 ATV01.ATV_Fast
%MW21 ATV01.ATV_RPM1
%MW25:X06 ATV02.ATV_Right
%MW25:X07 ATV02.ATV_Left
%MW25:X08 ATV02.ATV_Fast
%MW26 ATV02.ATV_RPM1
%MW30:X06 ATV03.ATV_Right
%MW30:X07 ATV03.ATV_Left
%MW30:X08 ATV03.ATV_Fast
%MW31 ATV03.ATV_RPM1
%MW35:X00 ATV_EStop
%MW35:X01 ATV_Ackn
%MW50:X00 IclA01.IclA_Power
%MW50.1 Icla01_stop_hmi
%MW50.2 Icla01_reset_hmi
%MW50:X01 IclA01.IclA_Stop
%MW50:X02 IclA01.IclA_Reset
%MW50.3 Icla01_start_hmi %MW50:X03 IclA01.IclA_Start
%MW50.4 Icla01_op_dimset_hmi %MW50:X04 IclA01.IclA_op_dimset
%MW50.5 Icla01_op_refmov_hmi %MW50:X05 IclA01.IclA_op_refmov
%MW50.6 Icla01_op_ptpabs_hmi %MW50:X06 IclA01.IclA_op_ptpabs
%MW50.7 Icla01_op_ptprel_hmi
%MW50.8 Icla01_op_vel_hmi
%MW50:X07
%MW50:X08
IclA01.IclA_op_ptprel
IclA01.IclA_op_vel
%MW52
%MW53
Icla01_rpm_hmi
Icla01_dest_hmi
%MW52
%MD53
IclA01.IclA_RPM
IclA01.IclA_Dest
%MW60.0 Icla02_power_hmi
%MW60.1 Icla02_stop_hmi
%MW60.2 Icla02_reset_hmi
%MW60:X00 IclA02.IclA_Power
%MW60:X01 IclA02.IclA_Stop
%MW60:X02 IclA02.IclA_Reset
%MW60.3 Icla02_start_hmi %MW60:X03 IclA02.IclA_Start
%MW60.4 Icla02_op_dimset_hmi %MW60:X04 IclA02.IclA_op_dimset
%MW60.5 Icla02_op_refmov_hmi %MW60:X05 IclA02.IclA_op_refmov
%MW60.6 Icla02_op_ptpabs_hmi %MW60:X06 IclA02.IclA_op_ptpabs
%MW60.7 Icla02_op_ptprel_hmi
%MW60.8 Icla02_op_vel_hmi
%MW62
%MW63
Icla02_rpm_hmi
Icla02_dest_hmi
%MW40.0 TeSysU_1_HMI
%MW40.1 TeSysU_2_HMI
%MW40.2 TeSysU_3_HMI
%MW82.0 Set_Auto_hmi
%MW82.1 Set_HMI_hmi
%MW82.2 Set_Manu_hmi
%MW82.3 Set_AutoStart_hmi
%MW60:X07 IclA02.IclA_op_ptprel
%MW60:X08 IclA02.IclA_op_vel
%MW62
%MD63
IclA02.IclA_RPM
IclA02.IclA_Dest
%MW40:X01 TeSys01.ON
%MW40:X02 TeSys02.ON
%MW40:X03 TeSys03.ON
%MW82:X00 Set_Auto_hmi
%MW82:X01 Set_HMI_hmi
%MW82:X02 Set_Manu_hmi
%MW82:X03 Set_AutoStart_hmi
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 38
Address
%MW20.0
%MW20.1
%MW20.2
%MW20.3
%MW20.4
%MW20.5
%MW23
%MW25.0
%MW25.1
%MW25.2
%MW25.3
%MW25.4
%MW25.5
%MW28
%MW30.0
%MW30.1
%MW30.2
%MW30.3
%MW30.4
%MW30.5
%MW33
%MW51.0
%MW51.1
%MW51.3
%MW51.4
%MW51.5
%MW51.6
%MW55
%MW61.0
%MW61.1
%MW61.3
%MW61.4
%MW61.5
%MW61.6
%MW65
Data Direction PLC -> HMI
Name
ATV01_MotErr
ATV01_MotEs
ATV01_MotFa
ATV01_MotLe
ATV01_MotRi
ATV01_MotSl
ATV01_ASPD
ATV02_MotErr
ATV02_MotEs
ATV02_MotFa
ATV02_MotLe
ATV02_MotRi
ATV02_MotSl
ATV02_ASPD
ATV03_MotErr
ATV03_MotEs
ATV03_MotFa
ATV03_MotLe
ATV03_MotRi
ATV03_MotSl
ATV03_ASPD
%MW1027.8
%MW1027.9
STB_13_EPI2145_1RUN
STB_13_EPI2145_1FLT
%MW1027.10 STB_13_EPI2145_1RDY
%MW1027.11 STB_13_EPI2145_2RUN
%MW1027.12 STB_13_EPI2145_2FLT
%MW1027.13 STB_13_EPI2145_2RDY
%MW1027.14 STB_13_EPI2145_3RUN
%MW1027.15 STB_13_EPI2145_3FLT
%MW1028.8
%MW81.0
%MW81.1
%MW81.2
%MW81.3
%MW81.4
%MW81.5
%MW81.6
Icla01_conf_runs
Icla01_conf_error
Icla01_Powered
Icla01_error
IclA01_stopped
IclA01_finish
IclA01_Position
Icla02_conf_runs
Icla02_conf_error
Icla02_Powered
Icla02_error
IclA02_stopped
IclA02_finish
IclA02_Position
STB_13_EPI2145_3RDY
HMI_Estop
HMI_Door
HMI_Auto_Mode
HMI_HMI_Mode
HMI_Manu_Mode
HMI_Auto_Started
HMI_DriveFault
Address
%MW20:X00
%MW20:X01
%MW20:X02
%MW20:X03
%MW20:X04
%MW20:X05
%MW23
%MW25:X00
%MW25:X01
%MW25:X02
%MW25:X03
%MW25:X04
%MW25:X05
%MW28
%MW30:X00
%MW30:X01
%MW30:X02
%MW30:X03
%MW30:X04
%MW30:X05
%MW33
Designation
ATV01.ATV_MotErr
ATV01.ATV_MotEs
ATV01.ATV_MotFa
ATV01.ATV_MotLe
ATV01.ATV_MotRi
ATV01.ATV_MotSl
ATV01.ATV_ActualSpe
ed
ATV02.ATV_MotErr
ATV02.ATV_MotEs
ATV02.ATV_MotFa
ATV02.ATV_MotLe
ATV02.ATV_MotRi
ATV02.ATV_MotSl
ATV02.ATV_ActualSpe
ed
ATV03.ATV_MotErr
ATV03.ATV_MotEs
ATV03.ATV_MotFa
ATV03.ATV_MotLe
ATV03.ATV_MotRi
ATV03.ATV_MotSl
ATV03.ATV_ActualSpe
ed
%MW51:X00
%MW51:X01
%MW51:X03
%MW51:X04
%MW51:X05
%MW51:X06
%MD55
%MW61:X00
%MW61:X01
%MW61:X03
%MW61:X04
%MW61:X05
%MW61:X06
%MD65
IclA01.IclA_conf_runs
IclA01.IclA_conf_error
IclA01.IclA_Powered
IclA01.IclA_error
IclA01.IclA_stopped
IclA01.IclA_finish
IclA01.IclA_Position
IclA02.IclA_conf_runs
IclA02.IclA_conf_error
IclA02.IclA_Powered
IclA02.IclA_error
IclA02.IclA_stopped
IclA02.IclA_finish
IclA02.IclA_Position
%MW1027:X08 TeSys01.Ready
%MW1027:X09 TeSys01.RUN
%MW1027:X10 TeSys01.Foult
%MW1027:X11 TeSys02.Ready
%MW1027:X12 TeSys02.RUN
%MW1027:X13 TeSys02.Foult
%MW1027:X14 TeSys03.Ready
%MW1027:X15 TeSys03.RUN
%MW1028:X08 TeSys03.Foult
%MW81:X00
%MW81:X01
%MW81:X02
%MW81:X03
%MW81:X04
%MW81:X05
%MW81:X06
HMI_Estop
HMI_Door
HMI_Auto_Mode
HMI_HMI_Mode
HMI_Manu_Mode
HMI_Auto_Started
HMI_DriveFault
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 39
Datalink
HMI <> STB
44097
44098
44099
44100
45416.0
45416.1
45416.2
45416.3
45416.4
45416.5
45416.6
45416.7
45418.0
Advantys STB (Modbus-Master,#1) XBT-N401 (Modbus-Slave)
Data Direction HMI -> STB
Address Name Address Designation
49488
49489
49490
49491
HMI_SPS_WD1
HMI_SPS_WD2
HMI_SPS_WD3
HMI_SPS_WD4
%MW9487
%MW9488
%MW9489
%MW9490
Set Drive
49488.0
49488.1
49488.2
HMI_SPS_WD1, Bit 0
HMI_SPS_WD1, Bit 1
%MW9487:X0 Set TeSysU_1_ON
%MW9487:X1 Set TeSysU_2_ON
HMI_SPS_WD1, Bit 2 %MW9487:X2 Set TeSysU_3_ON
Data Direction STB -> HMI
Address Name Address Designation
SPS_HMI_WD1
SPS_HMI_WD2
SPS_HMI_WD3
SPS_HMI_WD4
%MW4096
%MW4097
%MW4098
%MW4099
State
Mode
EPI_2_13_1_Schalter
EPI_2_13_1_Schaltschütz
%MW5415:X0
%MW5415:X1
TeSysU_1_READY
TeSysU_1_FOULT
EPI_2_13_1_Schutzschalter %MW5415:X2 TeSysU_1_RUN
EPI_2_13_2_Schalter
EPI_2_13_2_Schaltschütz
%MW5415:X3 TeSysU_2_READY
%MW5415:X4 TeSysU_2_FOULT
EPI_2_13_2_Schutzschalter %MW5415:X5 TeSysU_2_RUN
EPI_2_13_3_Schalter %MW5415:X6 TeSysU_3_READY
EPI_2_13_3_Schaltschütz %MW5415:X7 TeSysU_3_FOULT
EPI_2_13_3_Schutzschalter %MW5417:X0 TeSysU_3_RUN
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 40
General
Addressing
The PLC example program uses different hardware, discretes and memory words The following list contains keys to aid the understanding of the addressing system used.
Type Address Comment
Digital Inputs
Digital Outputs
Analog Inputs
%Ir.m.x
%Qr.m.x
Digital inputs are hardware orientated: r as Rack number, m as slot number, x as Input number.
E.g.: Emergency-off response at %I0.3.0
Digital outputs are hardware orientated: r as Rack number, m as slot number, x as output number
E.g.: Manual Mode Indicator at %Q0.5.1
%IWr.m.c Analog inputs are hardware orientated: r as Rack number, m as Slot number, c as channel number.
E.g.: Emergency-off response at %IW0.3.0
Analog Outputs
CANopen Inputs
CANopen Outputs
%QWr.m.c Analog outputs are hardware orientated: r as
Rack number, m as Slot number, c as channel number.
E.g.: Emergency-off response at %QW0.3.0
%MW0 bis
%MW31
%MW100 bis
%MW131
CANopen-Inputs are written as Memory Words, single bits can be accessed as %MWi.x.
E.g.: 2 nd
ATV Status word at %MW2
CANopen-Outputs are read as Memory words, single bits can be accessed as %MWi.x.
E.g.: 3 rd
. ATV control word at %MW104
Data for Visu %MW200 bis
%MW299
Data from Visu
CANopen Status
%MW300 bis
%MW399
%CHr.m.c
Data for the visualization is stored in memory words. Single bits can be written using the function BIT_TO_WORD
E.g.: Motor speed at %MW220
Data from the visualization is stored in memory words. Single bits can be extracted using the function WORD_TO_BIT
E.g.: Motor speed at %MW220
CANopen Status data can be read from the data structure T_COM_CPP110 (IODDT). Channel-
Address: r as Rack number, m as Slot number, c as channel number.
E.g.: Status CANopen %CH0.1.1
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 41
CANopen
Altivar 31
Setting the address and transmission rate
(manually)
The address and transmission rate must be specified for all the devices on the
CANopen bus.
1
The CANopen address and transmission rate are set manually via the control buttons on the device.
2 First, use the control buttons to select the Communication submenu.
In the Communication menu, the CANopen address must be set in the AdC0 parameter. In the example software provided, the values 2 to 4 have been set aside for the three speed drives.
Press ENT to confirm the setting.
In the Communication menu, you must also set the transmission rate in the BdC0 parameter to the value 250.0
(kbaud).
Alternatively, the address and transmission rate can also be parameterized using the
PowerSuite configuration software (see "Devices –
Altivar 31).
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 42
IcIA IFE7
Setting the address and transmission rate
1
The CANopen address and transmission rate are set manually using the DIP switches and the rotary switch in the cable connector of the drive.
The address can be varied between 1 and 127 using switches S1 and S2. S3 can be used in addition to define the drive as the last device on the bus by activating the CAN terminating resistor.
Set the transfer rate using the rotary switch and select a value of 250 kbaud (switch setting 4) to enable operation with the
Premium PLC.
2
The table summarizes the switch settings for the desired
CANopen address. Addresses
5 (000 0101b) and
6 (000 011 b) must be assigned to the drives.
Advantys
FTB
Setting the address and transmission rate
1
The CANopen address and transmission rate are set manually on the modules via rotary switches. There are two rotary switches for the address and one for the transmission rate. In the example software, both FTB modules are configured with the addresses
7 to 9 and the transmission rate is set to 250.0 kbaud.
Alternatively, you can set the system to detect the transmission rate automatically.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 43
Advantys
STB
Setting the address and transmission rate
1
To set the CANopen address and transmission rate, you will need a screwdriver to turn the rotary switches on the
Advantys island head.
2
3
Setting the baud rate:
1 Disconnect island voltage.
2 Set bottom rotary switch
(ONES) to any of the
positions after the number 9
(baud rate).
3 Set the baud rate
on the top rotary
switch (TENS). Select
position 4
for a transmission rate of
250 kbaud.
4 Reconnect island voltage.
Setting the CANopen address:
1 Disconnect island voltage.
2 Set the bottom rotary switch
(ONES) to the position
that corresponds to the
desired address in terms
of the ONES place value. If
the desired address is
010, the correct position is 0.
3 Set the top rotary switch
(TENS) to the position
that corresponds to the
desired address in terms
of the TENS and
HUNDREDS place values.
If the desired address is
01 0, the correct position is 1.
4 Reconnect the island voltage.
Notes:
Although addresses can be set manually, addresses 128 and 129 are not available for selection, as CANopen only supports addresses from 0 to 127.
After configuring the CANopen address, it is recommended that you leave the rotary switches in this address position so that, when the system is switched on, the island is always detected at the same address.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 44
Advantys
Software
Creating a
New Project
The Advantys Configuration Software must be used to make the configuration settings for the Advantys STB island, transfer them to the island and also to create the
EDS file required for CANopen communication.
1
After starting the Advantys software, you must create a new workspace.
2
To do this, you must specify the path, the workspace name and the name of the first island.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 45
Configuring the hardware
1
Select the network interface to serve as the island head for
CANopen STB NCO 2212.
Do this by dragging and dropping from the catalog browser or double-clicking in the catalog browser. The catalog browser is located on the right-hand side of the window.
2
3
Switch to the Parameters view by double-clicking the tab in the header and (as necessary) specify the number of registers to be exchanged via the
Advantys module within the context of communication between the PLC and HMI. For details, please see
“HMI Magelis XBT-N”.
Note: In the example project
4 words are reserved in each case.
Next add the remaining nodes:
STB PDT3100, STB DDI3610,
STB DDO3600, STB XBE1000,
STB XBE1200, STB PDT3100,
STB DRC3210, STB ACI1230,
STB ACO1210, STB EPI2145 and do not forget about bus connection STB XMP 1100.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 46
I/O data image
1
You can use the I/O Image
Overview… menu item (in the
Island menu) or the equivalent icon to call the function for assigning the I/O to the memory areas.
2
The information concerning the selected data is displayed in the description field.
Alternatively, the project can also be printed out. The printout will contain the same information.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 47
Downloading the configuration
1
Start by selecting the Build option in the Island menu or the equivalent icon to generate a machine-readable version from the completed configuration.
2
An information window will appear while the build is in progress. Once the build process is complete, a message will appear in the log window at the bottom of the screen informing you of whether or not the operation was successful.
3
If this is the first time that a connection to the island has been established, the connection settings must first be specified by selecting
Connection Settings from the
Online menu. In the case of a serial connection, the settings must be made as shown in the screenshot here.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 48
4
Connect the STBXCA4002 programming cable so that the configuration can be downloaded.
You can now establish a connection to the island by selecting Connect in the
Online menu.
Notice: If no build has been performed, the software will now initiate an automatic build.
5
6
7
Once the connection has been established, the Advantys software detects that the machine-readable version generated does not match the current configuration in the island and presents you with an option to Download or Upload .
Select Download and confirm the security prompt with YES .
A progress bar appears during download. Once the download process is complete a message appears asking whether the island should now be set to the
Running state. Click OK .
Alternatively, the island can be started by selecting Run from the Online menu.
As soon as the island has been successfully started, you may disconnect.
The island configuration is now complete.
The file with the saved configuration, i.e. the “island” file (STB_CANopen.isl), can be found under the following path:
C:\Program Files\Schneider
Electric\Advantys\Projects\
AdvantysSTB
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 49
Creating the
EDS file for
SyCon
1
As the EDS file is required to integrate the island into a
CANopen network, you should select Export
STB_CANopen from the File menu .
2
You must specify the path and file name. The default setting can generally be left as it is.
Progress can be tracked in the log window and once the export process is complete you can shut the configuration software down.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 50
Sycon
Software
Creating a
New Project
The CANopen bus is configured using the SyCon software. The individual devices are identified as bus nodes, then addresses are assigned and the master function is allocated to the Premium PLC.
Subsequently, the individual device data that is to be transferred during operation
(PDO) is configured and the device configurations (SDO) are defined where applicable.
Finally, the general bus settings are entered, e.g., the baud rate is specified.
1
Start the Sycon software, then start a new project by selecting
File -> New .
Select the CANopen bus in the next dialog.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 51
Importing
*.eds description files into
SyCon
1 In order that the speed drives, compact drives, STB island and FTB modules can be connected to the CANopen bus via the SyCon software, every type of device used must first be integrated into the SyCon software. Do this using the *eds description files (and the three additional image files).
2
After creating the project, select the Copy EDS menu item from the File menu.
Note: Integration is not possible, and this menu is not available, until a new project has been created.
3
In the dialog, select the file for the corresponding Altivar 31
(the last two digits of the file name indicate the version – in this case V1.2) and start the process.
Note: You must repeat the process if more than one device or device type is involved.
4
Confirm the import of the corresponding images.
5
A message appears informing you that integration is complete.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 52
Inserting nodes
1
Add the PLC’s interface card to the project as the master for the CANopen bus by selecting
Master from the Insert menu or pressing the equivalent button.
Select the TSX CPP 110 card in the next dialog. A CANopen address and a name must also be entered.
2
Add each drive to the project as a node using the Node menu item in the Insert menu.
Select the relevant device type in the dialog. A CANopen address and a name must also be entered.
This process must be repeated for each drive and all the other devices.
Note: You can pre-select the manufacturer and profile in the node filter to speed up the search for the devices in the selection list.
3
Once all devices have been added there should be nine nodes in the example project.
Select ID Table in the View menu to call up the identification table which summarizes all the nodes and their addresses, as well as the mapped PDO objects.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 53
Configuring
Nodes
Altivar 31
1
2
Double-click the device to open the Node Configuration window that is used for all busnode settings including configuration of the node when the bus starts up and the transfer of data during operation.
The dialog is divided into three sections: the top section shows the general configuration, the center section shows the predefined PDO
The bottom section shows the
PDOs configured for the given nodes and can also be used for configuration or making changes.
In the example project, you will need to de-select both predefined PDOs by unchecking the relevant boxes or clicking
Delete configured PDO .
3
Now select the Receive PDO6 and Transmit PDO6 PDOs for the Altivar 31 speed drive.
After double-clicking the PDOs to be activated, the dialog for setting the transmission mode appears.
For the Receive PDO, select event triggered with the event when data has changed .
In the case of the Transmit
PDO, select defined in the device profile and set the
Event timer to 100 ms and the
Inhibit time to 5 ms.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 54
4
After the transmission mode has been selected, the PDO is automatically entered as a configured PDO. There is no need for any additional configuration.
You must configure a Type 6
PDO to transmit and receive for each speed drive.
Note: Click the PDO Contents
Mapping button to see the data to be transmitted in the selected PDO. Click the PDO
Characteristics button to return to the transmission mode screen for the PDO.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 55
Configuring
Nodes
IclA IFE
1
2
Double-click the device to open the Node Configuration window that is used for all busnode settings including configuration of the node when the bus starts up and the transfer of data during operation.
Double-click both predefined
PDOs to activate them for the compact drives.
Note: Do not alter the device profile setting (value=0).
If this is altered, communication with the drive is disabled and, once changed, the original setting cannot be restored. To restore the setting, delete the device from the configuration and insert it again.
After double-clicking on the
PDOs to be activated, the dialog for setting the transmission mode appears.
For the Receive PDO, select manufacturer specific with the event when data has changed.
In the case of the Transmit
PDO , select manufacturer specific and set the Event timer to 100 ms and the Inhibit time to 10 ms.
3
After selecting transmission mode, the PDO is automatically entered as a configured PDO.
No additional configuration is needed
You must configure a Type 4
PDO to transmit and receive for each compact drive.
Note: Clicking the PDO
Contents Mapping button displays see the data to be transmitted in the selected
PDO. Click the PDO
Characteristics button to return to the transmission mode screen for the PDO.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 56
Configuring
Nodes
Advantys
FTB
1
Double-click the device to open the Node Configuration dialog that is used for all bus-node settings including configuration of the node when the bus starts up and the transfer of data during operation.
Four PDOs are pre-defined for the FTB modules but only two are required the application.
Here, you should also enter the details of the device object configuration which are to be performed by the bus master before the bus starts up.
2
To call node configuration, click the Object Configuration button. A separate window appears, listing all the objects in the CANopen object library for the device.
Note: The objects only appear in the list if they are also available in the EDS file.
3
4
Pin 2 of an FTB module can be used as either diagnostic or I/O channel. To use pin 2 as an I/O channel, object 2000:01 must be selected in the object configuration by doubleclicking. Once selected, enter the value 00 .
Note: Other objects may need to be configured, e.g., the behaviour of the outputs in the event of an error.
Note: Configuring PDOs automatically configures other objects.
For data transmission, a
Receive PDO and a Transmit
PDO must be activated in each case. the actual I/O data is transferred via the first PDO 1
(objects 1400 and 1800).
Double-click to open the PDO concerned.
Note: The other PDOs that are present (objects 1405 and
1805) transmit additional state information.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 57
5
After double-clicking the PDO you wish to activate, the window for setting the transmission mode appears.
For the Receive PDO, select event triggered with the event when data has changed .
In the case of the Transmit
PDO, select defined in the device profile and set the
Event timer to 1000 ms and the Inhibit time to 10 ms.
6
After the transmission mode has been selected, the PDO is automatically entered as a configured PDO. There is no need for additional configuration.
You must configure a Type 1
PDO to transmit and receive for each FTB module.
Note: Click the PDO Contents
Mapping button to see the data to be transmitted in the selected PDO. Click the PDO
Characteristics button to return to the transmission mode screen for the PDO.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 58
Configuring
Nodes
Advantys
STB
1
Double-click the device to open the Node Configuration window that is used for all busnode settings including configuration of the node when the bus starts up and the transfer of data during operation.
3 Receive PDOs and
4 Transmit PDOs are preconfigured for the configured STB module. In addition, you will need to activate PDOs 5 and 6 by double-clicking them.
2
After double-clicking the PDOs to be activated, the window for setting the transmission mode appears.
For the receive PDO, select event triggered with the event when data has changed .
In the case of the Transmit
PDO, select defined in the device profile and set the
Inhibit time to 10 ms.
In the case of the preconfigured objects, this setting must be checked by pressing the PDO
Characteristics button. This is
3 especially true in the case of the Transmit PDO, where the default Inhibit time is set to
0 ms (and it therefore deviates from the setting required for the example project).
After the transmission mode has been selected, the PDO is automatically entered as a configured PDO. There is no need for additional configuration.
Each and every PDO must be configured for the module.
Note: Click the PDO Contents
Mapping button to see the data to be transmitted in the selected PDO. Click the PDO
Characteristics button to return to the transmission mode screen for the PDO.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 59
Parameterizing the
CANopen
Bus
1
The bus parameter window is called up by selecting Bus
Parameter from the Settings menu. The master has to be selected in the bus view.
2
The transmission rate is the only parameter that needs to be changed (to 250 kbaud).
Then, you must save the
SyCon project.
The project file is stored in the following directory:
C:\Program Files\Schneider
Electric\SyCon\Project\DCI.co.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 60
CANopen
Symbols
Before
Starting the
Tool
The CANopen Symbol Tool enables you to import the variable names and comments from the Advantys STB module configuration into Unity. The symbol names for each
Advantys I/O variable are generated automatically by the tool.
However, this facility is merely an option intended to make handling variables easier.
1
2
The tool requires a Microsoft
Access driver (ODBC driver) so that it can read the ISL and
CO files.
Before starting the tool, make sure that the DSN Microsoft
Access Database already exists. If it does not, you must add it.
Access the ODBC Data
Source Administrator by selecting:
Control Panel
Administrative Tools
Data Sources (ODBC).
Select the System DSN tab in the dialog box that appears.
If the driver is not available, click Add.
In the Create New Data
Source window, select
Microsoft Access Driver
(*.mdb) .
Click Finish to display the
ODBC Microsoft Access
Setup dialog box.
3
Enter MS Access Database under Data Source Name and click OK.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 61
4
Click OK again in the ODBC
Data Source Administrator window.
The setting has now been made.
Note: This information is also available in the tool's User
Guide, which can be called up via the first screen that appears when the tool is started.
Creating the
XSY File for
Unity
1
Start Excel and select Unity as the target software.
2
Enter the data sources on the next worksheet. Do this by clicking the buttons next to the fields to specify the file paths.
Enter 3 in the Bus Alias field
(because the TSX CPP110 bus master has been plugged into slot 3 on the Premium CPU).
3
Click GENERATE UNITY
VARIABLES FILE to create the
XSY file.
You can inspect the file by clicking:
VIEW GENERATED UNITY
VARIABLES FILE.
Note: For a description of how to import the generated file into
Unit, see the section “PLC”.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 62
Modbus
Data is exchanged between the STB module register and the Magelis XBT-N terminal via Modbus . This process is explained below.
The STB
Island’s Data
Image
Register
The XBT-N401 terminal has access to the STB island’s register via Modbus.
Certain data image register blocks are illustrated below. The data starts at register
40001, which also happens to be the flag-address offset for Modbus communication. All the data image registers can be read from the island head’s
CFG port.
The configured registers in block 12 (registers 49488 to 49999), which are intended for communication between the HMI and PLC, can also be written from the terminal at the CFG port.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 63
Mapping
Overview
The fieldbus and Modbus I/O images from the Advantys configuration provide the information that is necessary for read and write access to the register addresses.
The flag addresses can be ascertained from the Modbus image by subtracting
40001 from the register addresses.
The variable addresses of the register entries for the PLC program are determined from the fieldbus image on the basis of the starting words. In the case of bit “ j ” from input word “ i ”, the variable address is “%IW\3.10\0.0.0.
i-1 .
j ”.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 64
HMI
Magelis XBT-N
Introduction
This section describes how to set up visualization on the Magelis text display. The HMI application for the XBT-N401 is created using the XBT-L1000 HMI software.
Proceed as follows to integrate the Human Machine Interface (HMI):
Create a new project
Configure the HMI
Create an application
Use the application
Example application
Creating a new project
1
Start the XBT-L1000 software and then create a new project.
Configuring the HMI
2
A configuration dialog appears.
Select:
Type: XBT-N401(2)
Protocol: Modbus
In the same dialog, select the
Modbus communication protocol parameters.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 65
3
Set the Modbus protocol parameters.
Set the same parameters as those on the Advantys STB
CFG port.
These are:
Speed: 9600 bauds
Parity: Even
Click OK to close this dialog and continue with the parameterization by clicking
Next .
4
Assign the project name and then click Next.
5
6
Enter the symbolic names and the network address for the connected devices in this window.
The network address must match that of the Advantys
STB CFG port.
The default value for this address is 1.
Continue by setting the language.
Here you can choose between different languages for the terminal.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 66
Creating an application
7
Do not make any settings for the terminal and dialogue table .
After completing the basic parameters, click Finish. The application pages must now be created.
1
The XBT-L1000 environment consists of the following elements:
1 – Menu bar
2 – Application window
3 – Window containing field information for the page
2
3 currently being displayed
4 – Toolbar
5 – Navigation window
(directory structure in the form of a page tree)
You can create text objects and links to other pages on an application page by clicking the relevant buttons..
Whenever a new page is created it is assigned a page number and a name.
You can vary the backlight colour to highlight certain pages.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 67
4
Some displays are used to access other displays
You must insert the links for this function.
5
Properties can be assigned to the alphanumeric fields.
First, specify the variable, which is to activate the field.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 68
6
7
Select the source/target from the Equipment drop-down list.
Enter Advantys (the master) here.
After selecting the variable type from the drop-down list on the right and the format, enter the register address for the variable.
“i” indicates the word and “j” the bit within the word.
Note: The Modbus register addresses at the STB port are referenced by means of flags.
For this purpose, an offset must be observed.
Flag word = Reg.add – 40001.
For details about register mapping, see
“Communication”.
Different formats are available for the display. Text is displayed on the basis of a word value.
As well as the text which indicates a certain a value, the numerical value itself can be displayed.
8
The Options tab also indicates whether the variable is readonly, write-only or read/write.
A max imum and min imum value can also be assigned to variables here.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 69
Using the application
1
The application can be simulated offline (without HMI connected) using the simulation function in the
XBT-L1000 software.
Activate the function by selecting
Simulation Activation
from the Simulation menu.
In the variables window, you can set and read variables.
2
3
In order to download the application from the PC to the
Magelis XBT-N401, connect the XBT-Z915 communication cable.
Start the download process by selecting Export from the
Transfers menu.
A message will appear to confirm that the application has been transferred successfully.
To download an application that has already been created first access it by selecting
Open from the File menu and then transfer it to the HMI.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 70
Example application
1
The mode is indicated in the central field on the Main Menu page.
From here, you can switch to the other pages.
2
3
If you select a motor, the page displaying the actual motor status appears.
If Manu Mode is currently active, you can control the motor here using the MOD and
ENTER buttons.
Press ESC to return to the previous page .
By switching to the Time page you can display the date and time.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 71
Magelis XBT-G
Introduction
This application features a Magelis XBT-G 4330 HMI, which is connected to the PLC via the
Uni-Telway protocol.
The Vijeo Designer software is used to program and configure the terminal. The steps to be taken in order to create and upload a program are described on the following pages.
Setting up the HMI is done as follows:
Create a new project
Specify the hardware
Select new driver
Check communication settings
Properties window
Create new variables
Create new screen
Create text
Add switches
Animation setup
Build and download the project
Runtime Installer
Example project
Create a new
Project
1
The Vijeo Designer environment consists of the following elements:
1 - Navigator
2 - Info display
3 - Inspector
4 - Data list
5 - Feedback zone
6 - Toolbox
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 72
2
Start Vijeo Designer and select
Create new Project .
Click Next to access further setting options.
3
Enter the project name.
Only one platform is required for the example application so select Project with Single
Target .
Specify the hardware
4
Enter the details of the terminal that is being used.
Target Name: Touchterminal
Target Type: XBTG Series
XBTG Model: XBTG4330
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 73
Select new driver
5
The terminal is equipped with an Ethernet port so you need to enter the network settings for the terminal here.
You will also need to activate these settings via the touch display when you switch on the terminal for the first time.
Note: The IP address should be assigned in accordance with the local network.
6
In order to exchange data with the PLC, the Magelis terminal requires a communication driver.
On this screen click Add to open up the New Driver Dialog
7
Now select Schneider Electric
Industries SAS as the manufacturer (at the top) and
Uni-Telway as the driver.
Uni-Telway Equipment will now appear automatically under Equipment and will be used for communication with the Premium PLC.
Confirm the settings by clicking
OK .
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 74
8
Once you have added the driver, click Finish to exit the configuration process.
Checking and setting communication parameters
1
Vijeo-Designer now opens the workspace described above with a blank edit screen on the right-hand side.
2
To check the project’s download properties select
Touchterminal in the navigator .
In the Property Inspector, click on Download .
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 75
Property
Inspector
3
You can check the settings here and if applicable select a serial link. However, an
Ethernet connection offers considerable speed advantages.
4
To check the Uni-Telway settings in the Navigator, click the Project tab, then right-click
UnitTelway01 [COM1] under
IO Manager and then select
Configuration.
The Driver Configuration dialog now appears.
5
Set the Transmission Speed to 19200 . Set the remaining interface parameters as follows:
COM Port: COM1
Serial Interface: RS-485
Rcv. Time Out: 3 Sec
The configuration must match the setting for the port on the
Premium PLC.
Confirm the change by clicking
OK.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 76
6
You can rename the equipment to PremiumPLC by rightclicking on
UniTelwayEquipment01 and selecting
Rename.
7
Right-click again on the name
PremiumPLC to configure the communication equipment.
There is no need to change the address settings as the terminal is directly connected to the PLC.
The default values of all the other settings can also be left as they are.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 77
Create New
Variables
1
To create a new variable, you first need to select the Variable tab at the bottom of the navigator .
Then right-click Touchterminal in the menu and select:
New Variable New…
2
To create variables, the following information must be entered:
Variable Name
Data Type
Data Source (= External)
Address in the PLC
To enter the address, click the button next to the device address field.
3
4
Memory bits and words are addressed within the PLC; internal formats such as counters (or similar) have to be transferred to memory words if they are to be displayed on the
Magelis terminal.
With the Discrete data type, bits are addressed. In this case, you will need to enter the word address and the bit number in the word.
Click OK to confirm.
As soon as you confirm the input in the variable dialog by clicking OK , the variable appears in the list of variables.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 78
5
In the case of variables where the data type is Integer and the values can be negative, you must click the IO Settings tab and select 2’s Complement in the Signed field.
Create New
Screen
1
Right-click Graphical Panels in the Navigator to add a new panel.
You can change the name of a panel by right-clicking on the name in the navigator.
Adding text
1
You can add text by clicking the relevant icon in the tool bar.
Once you have set the size, a dialog appears in which you can specify the text content, font, colour etc.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 79
2
If Text has been selected, you can use the Property
Inspector to change the text element’s position, size, colors, etc.
3
To select the Animation function, select a text element and then right-click with the mouse.
You can also edit the animation data in the Property Inspector
(described above).
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 80
Adding a switch
4
You can animate the following properties:
Color
Position
Value
Visible
Select the light bulb icon at the end of the edit box in order to enter variables.
A variable name that has been entered but not recognized appears in red.
After activation you can select a variable for the value animation and the display format.
If additional functions are required (such as trigonometric functions), these can be generated via the calculator icon.
1
You can add a switch by clicking the relevant icon in the menu bar.
Once you have set the size, a dialog appears in which you can specify the switch settings.
2
Here you can define what happens according to the various user actions.
As well as enabling the user to switch panels, switches can also be used to modify variables.
Switches can also be animated, e.g. change colour according to their status.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 81
Build and
Download the Project
1
To analyze the project before downloading it to the Touch
Panel, Select Build from the menu bar followed by Validate
All.
The results are listed in the
Feedback Zone.
You can also the Build All menu item.
Download
Problems
Runtime
Installer
2
Select the project in the navigator.
Use the menu item Download
All (reached via the right mouse button or the Build menu) to transfer the application to the connected
HMI.
The connection selected at the outset (Ethernet) is used.
1
2
If the download fails, you should check the connection and settings. If the terminal is being used for the first time, it may be necessary to transfer a new runtime version to the terminal first.
To do this, go to the Windows
Start menu and select:
Program Files –> Schneider
Electric –> Vijeo-Designer –>
Runtime Installer Tools.
The Runtime Installer starts up.
To ensure successful installation, follow the instructions on the right-hand side of the window.
Afterwards, try downloading the project again.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 82
Example project
1
You can select the operating mode on the startup screen.
This also displays the state of safety equipment and any errors. Certain errors can be reset by pressing the Reset button.
Use the bar at the bottom to switch between the various displays.
2
The CANopen display provides information about the state of the CANopen bus nodes.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 83
Example project
Ctd.
3
4
Use the ATV 31 display to control the speed drive.
The target (Set) speed and direction of rotation can be specified here for each device.
Along with the LEDs, the Actual
Speed provides information about the state of the speed drive.
You can clear an error by pressing Reset . Press STOP to initiate a fast stop.
Use the IclA display to control the compact drive in its various modes. After selecting the display, you will need to enter the target (Set) speed and position.
Use START and STOP to change the operating state.
The buttons above the menu bar can be used to switch between the two drives that have been installed.
5
Select the TeSys U display to control the TeSys U module contactors.
The state of the devices appears here.
Click the relevant buttons to activate and deactivate the devices.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 84
Importing/ exporting a project
1
To import a project you must first go to the Navigator window and click the Vijeo-Manager tab. Right-click the Vijeo-
Manager node and select
Import Project .
Note: It is only possible to import Vijeo frame archive files (*.vdz files).
2
To export a project you must first go to the Navigator window and click the Vijeo-Manager tab. Then you need to rightclick the project file you want to export and select Export
Project .
Note: Projects must first be closed before they can be exported (or renamed). If the selected project is still open, the Export Project will be grayed out. In this case, you should save the project and close it.
3
In the Export Project dialog box, you must specify where you want the *.vdz project file to be saved. Click Save to export the project file.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 85
PLC
Introduction
The PLC chapter describes the steps required for the initialization and configuration and the source program required to fulfill the functions.
Pre-
Before carrying out the steps described below, you must ensure the following:
conditions
That the Unity Pro XL software is installed on the PC
That the CO file from the SyCon configuration has been created
That the Premium PLC is switched on and being supplied with power
That the PLC and the PC are linked to one another via the TSX PCX 1031 programming cable.
Setting up the PLC is done as follows:
Configure Ethernet communication
Configure CANopen communication
Import variables table
Create application program (logic)
Connect to PLC and download program
Creating a
New Project
1
After starting Unity, the first thing you need to do is create a new project. To do so, you must first select the correct
PLC.
2
Double-click Configuration or
X Bus to open a window that will enable you to configure the hardware.
Next, drag and drop the CPU to the correct rack position to allow you to insert the correct power supply from the hardware catalog.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 86
3
4
Right-click on the rack to replace it with a larger one.
Now insert the other hardware modules into the rack by dragging and dropping them from the hardware catalog.
Double-click slot A of the CPU module to add a memory module.
Assign the TSX CPP 110
CANopen communication module to slot B .
Now save the project.
Double-click the CPU module to adjust the number of I/O data items. Data areas are already reserved for this purpose.
In our example, the following settings need to be made:
%M 256
%MW 2000
%KW 1000
Configuring
Ethernet communi- cat-ion
1
First, select New Network under Communication and
Networks in the Project
Browser.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 87
2
In the Add Network window, select Ethernet as the network type and enter a name for the network under Change Name .
Click OK to create the network.
To configure the new network, right-click on it and select
Open .
3
Input the following settings in the exact order in which they appear below:
Select the model family
(regular connection). The tool tips show the devices that belong to each model family.
Specify the IP address and subnetwork mask.
Now close the window and confirm the changes.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 88
Project settings
4
The configured network must be assigned to the hardware.
To do this, switch to the
Hardware view and doubleclick the CPU network connection. The window opposite appears.
The following three settings should be made and then applied:
Select the channel
(in this example, Channel 0)
Select the function
(in this example,
ETH TCP IP)
Select the network link (the configured connection)
Close the window to validate your settings.
1
In the Project Browser, rightclick on Station and then select Project Settings .
2
When the Project Settings dialog opens, click the
Language extensions tab.
Under Data types , check the box next to Allow dynamic arrays […].
Press OK to confirm the setting.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 89
Configuring
CANopen communication
1
In the Project Browser, rightclick CANopen under
Configuration and select
Open to access the
CANopen configuration.
2
A dialog will appear, where you should click Select
Database to load the
CANopen configuration that was created previously.
Alternatively, you can click the Hilscher button to create a configuration in the
SyCon tool.
Once the transfer is complete, the most important data appears underneath the file details.
You can also choose here whether to use Unity or
SyCon for bus configuration.
In the example we are using
Unity.
3
The upper part of the dialog is for selecting the bus startup characteristics and the assignment of addresses for the input and output areas. In the example project, automatic bus startup is configured.
The number of flag words for the inputs and outputs must be adapted in line with the
CANopen configuration. If an incorrect entry is made, the numbers will show up red.
The inputs start at address
%MW1000 and the outputs at %MW1500. For the inputs and outputs, there are 36 and 25 words respectively.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 90
Importing variables tables
4
5
Clicking the Bus configuration button brings up a new dialog where the individual slaves are listed. If you click on one of the slaves in the list, information such as the I/O addresses assigned is displayed on the right.
Note: The addresses are shown from top to bottom in order of their position on the bus in the SyCon software.
The CANopen addresses are disregarded.
The configuration must be confirmed or validated. You can do this either by closing the configuration window or selecting Validate from the
Edit menu.
Note: You can only save, close and build the project after you have validated it.
1
Right-click on Variables & FB instances in the Project
Browser and select the Import option.
2
Only *.XSY and *.TXT files can be used for importing variables.
Select a file and click Import to confirm the process. The variables will now be imported.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 91
2
Double-click on Variables &
FB instances in the Project
Browser to open the Data
Editor , where you can view and modify variables.
Importing FB types
1
In the Project Browser, rightclick on Derived FB Types and then select Import .
2
Only files with the extension
*.XDB can be used for importing FB types. Select a file and click Import to confirm the process. The derived FB type will now be imported together with the associated and derived FB data types.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 92
FB type ATV
1
2
The ATV function block is used to control the Altivar 31 speed drive. The atv_state data type drive status word is applied to
ATV_IN .
Output ATV_OUT (type atv_ctrl) is associated with the drive control word.
The Boolean inputs Left,
Right, Fast, Slow and Estop are used to control the speed drive.
A rising edge at Ackn triggers a speed-drive reset.
The bus state is connected to
CommOk .
The integer inputs RPM1 and
RPM2 are used to set the speed for Fast/Slow operation.
The Mot...
outputs provide binary state information about the speed drive. Spd provides the motor speed as an integer value.
The FB data types relating to the ATV block each contain two words.
The atv_state structure contains the DriveCom state register for the speed drive and the current speed.
The atv_ctrl structure sets the
DriveCom command register and the speed.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 93
FB type ICLA
1
The ICLA function block is used to control the compact drive via CANopen. There is a communication-PDO array
(4 words) for CANopen at both
PDO_IN and PDO_OUT .
2
An edge at Config initiates IcIA configuration.
Control_IO is used to connect the IO inputs.
Address is where the
CANopen address is registered.
AckError is used for resetting error messages.
Inputs Power, Stop, Reset, and Start are supplied by
Boolean values.
A specific byte combination at
Mode sets the operating mode.
RPM is used to set the speed and Dest for entry of the target position.
ConfRuns, ConfErr, Ready,
Error, Stopped, and Finished provide information about the device state and about travel.
State is an error status word.
Position is where the value for the current position may be found.
Only one bit may be set in the input byte for the purpose of setting the operating mode.
Each bit position represents a different mode.
Bit0 – Sets the position
Bit1 – Referencing
Bit2 – Point-to-point, absolute
Bit3 – Point-to-point, relative
Bit5 – Speed profile
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 94
Creating the
Application
Program
1
Right-click on Sections under
MAST , Tasks and Program in the Project Browser and select
New Section .
2
A dialog appears in which you should enter the section name and select the programming language .
3
Right-click in the section window and select the FFB
Input Assistant.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 95
4
Once you have selected an
FFB type, you can assign an instance name.
Click OK to position the function block in the section window.
5
Right-click and select
Properties… or double-click on the block to open the
Properties window.
Here you must define the input data types and input comments.
6
The editor toolbar supports program creation by enabling program components to be selected quickly.
The editor toolbar content changes according to the programming language selected.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 96
Downloading the program
1
Upon completion of the programming, the entire project must be generated (build or rebuild) .
To do this, select the relevant menu item or button.
2
Before transferring the program to the PLC, you must first set the PLC connection address.
Under Media, select UNTLW01 for a Uni-Telway connection.
SYS should be specified as the standard system address.
A connection can also be created via TCP/IP if a program with an IP address is already running on the PLC.
3
Once the connection has been set you can transfer the project to the PLC.
To do this, select Transfer
Project to PLC in the PLC menu.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 97
Devices
Introduction
This chapter describes the steps required to initialize and configure the devices to attain the described system function.
Altivar 31
General
Connecting the device and reading out data
The ATV 31 parameters can also be entered or modified via the front panel. The advantages of using PowerSuite are that
You can save the data onto your PC and duplicate it however you want
You can print out the documentation
It can help you with online parameter optimization
As well as containing the device documentation (installation and programming instructions), the product CD supplied with the Altivar 31 also features a scaled down version of PowerSuite to enable quick and easy parameterization of the variable speed drive.
1
After starting the software, use the Connect function in the
Action menu or the equivalent button to establish a connection with the device.
Note: Prior to this, you must connect the PC and ATV into the PowerSuite port on the
CANopen junction box.
Only one speed drive at a time can be connected to the
CANopen junction box altivar port ( ATV1).
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 98
2
Before the connection is established, you must confirm that you accept the terms of the security warning by pressing
ALT+F.
3
Next, you need to enter the name of the configuration or device.
4
Acknowledge the warning about transferring the parameters from the device.
The current parameters are now transferred from the speed drive to the PC.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 99
Parameterizing and transferring data
1
Once the transfer is complete, the speed drive’s online screen appears.
2
In order to make parameter settings, switch to the configuration screen.
To do this, select
Configuration from the
Display menu…
… or use the equivalent icon on the toolbar
3
Select Fast settings in the configuration view.
As a minimum, you must then check the supply-frequency parameters (BFR) and motor parameters:
Settings/Drive Parameters –>
Motor Characteristics and adjust them as necessary.
4
The CANopen address and baud rate ( trans. speed ) can be set for the speed drive under Communication .
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 100
5
Next, close the configuration view and, in the main window, transfer the data to the speed drive by selecting Configure from the Action menu or by pressing the equivalent button.
6
To start the transfer, confirm the warning message.
1
You can manage the configurations in the view that is displayed once the connection has been closed.
To display an overview of all the configurations created so far, click Display , followed by
Configurations . The overview will appear on the left-hand side.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 101
TeSys U
General
Installation
Basically, the TeSys U motor control unit comprises:
Power base
Control unit
Communication module
Coil wiring kit
Optional: reversing block, I s limiter/isolation block and other modules
Insert the LUCA 05 BL control unit into the LUB12 power base.
To enable communication, slide the
LUF C00 communication module with parallel wiring (1) and the LU9B N11C coil wiring kit (2) in underneath the control unit and connect the wiring kit connector to the communication module.
Notice
Note
The LUF C00 module with parallel wiring enables motor controls to be connected to the I/O modules of PLCs quickly and without the need for tools. It replaces conventional systems using a screw terminal block and single-conductor wiring. The module with parallel wiring collects all information regarding the states and control commands of each motor control. The connection module distributes information from the PLC I/O modules to each connected motor control.
The following points should be taken into account when selecting components:
1. A 24 V DC LUCx xx BL control unit must be used. The BL extension should be observed.
2. Different versions of the coil wiring kit are available, depending on which power base is used. LU9B N11C should be used if the power base has one direction of rotation (LUBxx) and LU9M RC should be used if the power base has two directions of rotation (LU2Bxx).
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 102
Performance
Scan and
Cycle time
At the time of going to press, no measurement results were available with respect to scan and cycle times.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 103
Appendix
Detailed Component List
Hardware-
Pos. Amt. Description
Components
- Master switch 1.1
1.2
1.3
1.4
1.5
1.6
1.7
- 24V supply
Magelis,
Safety
2.1
2.2
1
1
1
2
1
1
1
1
1
Master switch NSC100N TM16D
Terminal covers (2x)
Auxiliary switch OF/SD
Undervoltage release MN 24VDC
Locking device
Undervoltage-release fuse
Control-voltage tap
Phaseo power supply 230 V, 72 W,
24V DC
Primary automatic circuit-breaker,
2-pin, 1 A
- Emergency
off
3.1
3.2
1
1
Preventa safety relay XPS-AF
3.3
3.4
3.5
- Premium PLC 4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8
4.9
4.10
4.11
4.12
4.13
4.14
4.15
4.16
4.17
4.18
1
2
1
1
1
1
2
1
1
2
1
1
1
1
4
2
2
1
3
10
10
Part Number
(MG) 28120
(MG) 28034
(MG) 29450
(MG) 28085
(MG) 29370
(MG) 25020
(MG) 29348
ABL7RP2403
GB2DB06
XPSAF5130
Mushroom button in integrated housing, tamper-proof, with rotary
XALK178G unlocking
Acknowledgement button – integrated XALD102E housing
Contactor 5.5 kW, 24 V operation, GL LC1D12BL
Emergency-off fuse + door safety 2 A (MG) 25021
Backplane for 12 modules
Power supply module 230 V, 26 W
Primary automatic circuit-breaker,
2-pin, 1 A
(transistor 0.5 A)
Analog input module 16 channels
TSXRKY12
TSXPSY2600M
GB2DB06
Processor module (Unity), integrated
Ethernet
TSXP571634
SRAM memory card,768 kB TSXMRPC768K
CANopen bus master, PCMCIA card TSXCPP110
Digital input module, 16 channels
Digital output module, 16 channels,
TSXDEY16D2
TSXDSY16T2
TSXAEY1600
TSXASY410 Analog output module, 4 channels,
11 bit +sign
Ethernet, TCP/IP network module,
I/Oscanner
TSXETY4103
Terminal block 20-pin, I/O cards
Connection cable SUB-D 25-pin
Terminal with integr. microfuse
Microfuse 0.5 A, quick-acting
Microfuse 6.3 A, quick-acting
Telefast terminal block analog input
Telefast terminal blocks analog input
TSXBLY01
ABE7CPA02
TSXCAP030
ABE7CPA02
AB1FUSE435U5X
ABE7FU050
ABE7FU630
Rev./
Vers.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 104
Hardware-
Components
- Magelis XBTG
- Harmony XVB signal beacon 6.2
- Altivar 31 variable speed drive
- IclA compact drive
- Remote control cubicle fuse
- Remote control cubicle 24V supply
- Door safety
Pos.
5.1
5.2
5.3
6.1
6.3
6.4
6.5
6.6
6.7
6.8
7.1
7.2
7.3
7.4
7.5
8.1
8.2
8.3
8.4
8.5
8.6
8.7
9.1
10.1
10.2
11.1
11.2
11.3
11.4
11.5
Amt.
1
1
1
1
1
1
1
1
1
1
1
3
3
3
3
3
2
2
2
1
1
1
2
1
1
1
1
2
2
1
1
Description
XBTG touch panel, 256 colors, 7.4‘‘,
Wall-mounting bracket
Connection element + cover
XBTG4330 serial/Ethernet port
Connection cable: XBTG - PLC 2.5 m XBTZ968
Fuse Magelis XBTG 2 A (MG) 25021
XVBC12
XVBC21
XVBC2B3 Light-emitting diode with continuous light, LED 24 V DC, green
Light-emitting diode with continuous light, LED 24 V DC, red
XVBC2B4
XVBC2B6 Light-emitting diode with continuous light, LED 24 V DC, blue
Light-emitting diode with continuous light, LED 24 V DC, yellow
Audible signal device, 12...48 V
Color-coding kit
XVBC2B8
XVBC9B
XVBC22
ATV31H018M2 Altivar 31, CANopen integr. 230 V,
1~, 0.18 kW
DIN-rail mounting kit
Motor circuit-breaker, 4 A
VW3A11852
Auxiliary-switch attachment for motor circuit-breaker
Contactor up to 9 A, 24 V operation,
GL
VW3A11852
GV2-L08
GVAE11
LC1D09BL
EC motor with positioning control,
CANopen interface, industrial socket connection
Supply cable, industrial socket connection with open lead end, 3 m
Fuse motor current
Phaseo power supply 400 V, 240 W,
24 V DC
Motor circuit-breaker, transformer fuse
Auxiliary-switch attachment for motor circuit-breaker
Contactor up to 9 A, 24 V operation,
GL
Fuse 16 A 3-pin
Phaseo power supply 230 V, 120 W,
24 V DC
Primary automatic circuit-breaker,
2-pin, 1 A
Preventa safety relay XPS-AF
Door-safety switch
Actuator for door-safety switch
Acknowledgement button – integrated housing
Contactor up to 9 A, 24 V operation,
GL, output supply – STB module
Part Number
(BL) IFE71/2
CAN-DS/-QDI54/
V-115KPP54
(BL)
0062501470030
(MG) 25085
ABL7UPS24100
GV2-ME08
GVAE11
LC1D09BL
(MG) 23652
ABL7RP2405
GB2DB06
XPSAF5130
XCSTA791
XCSZ12
XALD102E
LC1D09BL
Rev./
Vers.
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 105
Hardware-
Components
- Advantys STB
I/O platform
Pos.
12.1
12.2
12.3
12.4
12.5
12.6
12.7
12.8
12.9
12.14
12.15
12.16
12.17
Amt.
1
2
6
2
1
1
1
2
1
12.10 1
12.11 1
12.12 1
12.13 2
10
4
1
1
Description Part Number
Fieldbus coupler module for CANopen STB NCO2212
Power feeder module 24 V
Digital input module, 6 channels
Digital output module, 6 channels
EOS extension module
STB PDT3100
STB DDI3610
STB DDO3600
STB XBE1000
BOS extension module
Island bus extension cable 0.3 m
Relay output module, 2 channels
Analog input module, 2 channels
STB XBE1200
STB XCA1001
STB DRC3210
STB ACI1230
Analog output module, 2 channels
Bus terminator module island bus
Backplane for PDT3100
Interface module, 4 x TeSys U, RJ45
STB ACO1210
STB EPI2145
STB XMP1100
STB XBA2200
STB XBA1000 Backplane for DDI3610, DD03600,
AVI1230, AVO1210
Backplane for XBE1000, XBE1200,
DRC3210
STB XBA2000
Backplane for EPI2145
Fuse Advantys STB 4 A
STB XBA3000
(MG) 25023
Rev./
Vers.
- Magelis XBTN 13.1
13.2
13.3
13.4
1
1
1
1
Text display 8 keys, serial
Connection cable: XBTN - STB 2.5 m
Programming cable XBTN - PC
Fuse Magelis XBTN 1A
XBTN401
XBTZ988
XBTZ915
(MG) 25020
- XAL-D
Harmony style 5 pushbutton housing
14.1
14.2
14.3
14.4
14.5
14.6
14.7
14.8
14.9
2
14.10 1
14.11 1
2
1
1
1
14.12 1
14.13 1
14.14 1
14.15 1
2
4
1
1
Empty housing, 4 recesses
Auxiliary switch block 1 NO contact
Lamp holder, LED 24V DC, green
Lamp holder, LED 24 V DC, red
XALD04H7
ZEN-L1111
ZAL-VB3
ZAL-VB4
Lamp holder, LED 24 V DC, yellow
Lamp holder, LED 24 V DC, blue
Indicator lamp, round, flat, green
Indicator lamp, round, flat, red
Indicator lamp, round, flat, yellow
ZAL-VB5
ZAL-VB6
ZB5AV033
ZB5AV043
ZB5AV053
Indicator lamp, round, flat, blue
Illuminated pushbutton, round, flat,
ZB5AV063
ZB5AW353 yellow
Illuminated pushbutton, round, flat, blue ZB5AW363
Pushbutton, round, flat, green “I”
Pushbutton, round, flat, green “O”
Flare nut wrench
ZB5AA331
ZB5AA432
ZB5AZ905
- TeSys U module contactor
15.1
15.2
15.3
15.4
15.5
15.6
3
3
3
3
3
1
TeSys U power base, 12 A
Standard control unit 0.25...1.5 kW
Function module with parallel wiring
LUB12
LUCA05BL
LUFCOO
Coil wiring kit
Connection cable 1 m, 2x RJ45
LU9BN11C
LU9R10 connector
Contactor up to 9 A, 24 V operation, GL LC1D09BL
- Advantys FTB
I/O module
16.1
16.2
3
2
I/O module, IP67, 12 In, 4 Out FTB1CN
12E04SPO
FTXDP2210
16.3
16.4
16.5
16.6
1
1
2
1
Power supply cable 1 m, 5-pin 7/8 connection at both ends
Power supply cable 1.5 m, 5-pin 7/8 with open lead end
Cover cap 7/8 connection
Cover cap M12 connection (10x)
Advantys FTB fuse 2 A
FTXDP2115
FTXC78B
FTXCM12B
(MG) 24886
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 106
Hardware-
Components
- CANopen infrastructure
Pos. Amt. Description
17.1
17.2
17.3
17.4
17.5
17.6
17.7
17.8
17.9
3
2
3
1
2
1
3
1
1
CANopen connector, 9-pin sub-D, female
Altivar junction box, 2x RJ45 ports
Altivar branching cable 1 m,
2x RJ45 connector
Junction box, 4x 9-pin sub-D, male
IclA IFE CANopen connector set,
M12 connector (plug + socket)
Branching cable 1 m, 2x 9-pin sub-D connector
Bus connection cable for FTB 1 m,
5-pin M12 angular connection at both ends
Terminating resistor M12 for FTB
CANopen cable, 50 m
Rev./
Part Number
TSXCANKCDF90T
Vers.
VW3CANTAP2
VW3CANCARR1
VW3CANTDM4
(BL)
0062501526001
TSXCANCADD1
FTXCN3210
FTXCNTL12
TSXCANCD50
Software-
Components
Pos. Amt. Description
18.1
18.2
18.3
18.4
18.5
18.6
18.7
1
1
1
1
1
1
1
Unity Pro XL single-user license
SyCon
Advantys Configuration
Software incl. RS232 cable
CANopen Symbol Tool
PowerSuite ATV31
Vijeo Designer
XBT-L1000
Part Number
UNYSPUFUCD20
Rev./
Vers.
V2.1
SYCSPULFUCD29M
STBSPU1000
V2.9
V2.0
V1.4
V2.0
VJDSPULFUCDV10M V4.20
XBTL1003M V4.42
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 107
Component Protection Classes
Mounting Location / Protection Class
Component
Master switch NSC100N
Safety relay XPSAF
Safety position switch
Emergency-off pushbutton housing
4-button pushbutton housing, empty
Signalers, all colors, flat
Illuminated pushbuttons, all colors, flat
Auxiliary switch module with LED
+ 1 auxiliary switch (1x NO), all colors
Contactor, 24 V DC operated,
3-pole AC 3, 1x NO + 1x NC
Motor circuit-breaker, all types and ratings
Miniature circuit breaker, all types and ratings
Motor circuit-breaker, all types and ratings
Phaseo power supply, all types
Altivar 31 variable speed drive
IclA IFE
In the field
IP55/IP65
X
X
X
TeSys U module contactor
Advantys STB I/O platform
Advantys FTB I/O module
XVB signal beacon
XBT-N display terminal
XBT-G display terminal
Premium PLC, all modules
IP54,
IP41 shaft gland
IP67
X
X
X
X
X
X
X
X
X
X
X
X
X
Cabinet
IP20
IP40
X
X
X
Frontside
IP65
X
X
X
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 108
Component Features
Components
Compact NSC100N circuit-breaker
Max. rated current 100 A, 3 poles, manual operation via rocker arm
Breaking capacity at AC 50/60 Hz 240 V – 42 kA
480 V – 18 kA
600 V – 10 kA
Overload and short-circuit protection via integrated thermo-magnetic tripping system
Temperature range: -25 to +70°C
Specially designed for machine protection
Auxiliary switch, undervoltage release, shunt release, terminal covers, phase separator, rotary drive, locking device (accessory)
Approvals: UL508/IEC 60947-2/CSA 22-2
Preventa safety relays XPSAF5130
Category 4 to EN 954 Part 1
24 V AC/DC
Power consumption < 5VA
Monitoring of emergency-off circuits and position switches
3 safety-oriented switching contacts
3 diagnostic LEDs on front panel
Adjustable start-button monitoring function
Approvals: UL, CSA
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 109
Components
Ctd.
Preventa safety position switch XCSTA
10 A short-circuit protection
No locking of isolated actuator
Convertible operating head, can be operated from 8 directions
2 cable entries
Plastic-clad
Approvals: UL, CSA
XAL-K pushbutton housing: EMERGENCY-OFF pushbutton
Housing for 1-5 front elements, each able to accommodate a maximum of 3 auxiliary-switch blocks
Can be mounted on front element or in housing base
Front elements can be labeled however you want
Approvals: UL Listed, CSA
TeSys Model D contactors
Up to 75 kW at 400 V, AC-3
Integrated quick-acting auxiliary switch, 1 NC contact, 1 NO contact
Various operating voltages, even with low power consumption
Additional auxiliary-switch blocks can be mounted
Approvals: UL, CSA
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 110
Components
Ctd.
GV2-ME08 motor circuit-breaker
Thermo-magnetic tripping
Adjustable tripping current
Lockable
Temperature range: -25 to +70°C
Approvals: UL, CSA, CEBEC, GOST, TSE, BV, GL, LROS,
DNV, PTB, EZU, SETI, RINA
GV2-L08 motor circuit-breaker
Magnetic tripping for short-circuit protection
Rotary drive for door mounting
Lockable
Temperature range: -25 to +70°C
Approvals: UL, CSA, TSE, BV, GL, LROS, DNV
GB2-DB circuit-breaker
Thermal and magnetic protection of transformers, primary
2 poles
Maximum operating voltage: 415 V
Temperature range: -20 to +60°C
CE approval
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 111
Components
Ctd.
Phaseo power supply unit: ABL7RE2403, ABL7RE2405 and ABL7UPS24100
Switched-mode electronic power supply with line filter
100..240 V AC 1~/24 V DC (adjustable)
3 A, 5 A or 10 A, secondary
Slimline design
Indication of input and output voltage (with ABL7RE) via
LEDs
Can be connected in parallel (with ABL7RE)
Short-circuit-proof and protected against overload with manual or automatic reset
Approvals: UL, CSA, TÜV, Ctick (ABL7UPS: cULus, cRLus)
CANopen junction box VW3CANTAP2
2 CANopen slaves can be connected via RJ45
(Altivar/Lexium)
Third port enabling connection of a PC for configuration via
PowerSuite
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 112
Components
Ctd.
Altivar variable speed drive: ATV31H018M2
0.18kW, 200V ...240 V AC single-phase
Integrated class B EMC filter
Temperature range: - 10..+ 50°C
Speed range from 1 to 50 (0...500 Hz)
Speed control with flow vector check
Operation via Modbus or CANopen possible
2 analog inputs plus 1 analog output
6 digital inputs
2 or 3 digital state outputs possible
Protection of drive and motor
Configurable via PowerSuite software
Compact design, side-by-side installation also possible on a
DIN rail using bracket VW3A11852
Approvals: UL, CSA, NOM 117, C-Tick
IclA IFE compact drive
Output power 74/117 W (24/36 V DC incoming supply)
Maximum current consumption: 6 A
Torque range 0.17 Nm; 3.1 ... 11 Nm (with gears)
High current-free latching torque
Speed range of up to 4800 rpm (without gears)
Temperature range: 0..+ 65°C
Compact, as motor and electronics form a single unit
Quick and easy in respect of installation and EMC
Optional industrial plug and socket connection
Equipped for communication via CANopen, Profibus DP or
RS485
Operating modes: referencing, manual running, point-topoint, speed profile
Approvals: cRLus, CE
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 113
Components
Ctd.
TeSys U module contactor
Protection and switching of single or three-phase motors
Protection against overcurrents, short-circuits and thermal overload
Modules can be mounted safely and easily by snapping them onto the power base
Power base for one or two directions of rotation
Various control units, e.g., for application monitoring
(running time, number of errors, motor-current values), log (error memory), alarms
Communication modules for parallel wiring, Modbus and
AS interface; FIPIO, Profibus-DP, DeviceNet also possible, for example, if gateway modules are used
Use of additional auxiliary switches supported
Temperature range: -25..+ 70°C (multifunctional control unit up to +55°C)
Approvals: UL, CSA
Advantys STB I/O module
Open, modular I/O system
Easy to set up using Advantys Configuration Software
Power distribution, signal acquisition and power management via island bus
Fieldbus coupler modules for Ethernet TCP/IP, CANopen,
Modbus Plus, Fipio, INTERBUS, Profibus DP and
DeviceNet
Gateway functionality with CANopen extension module
EMC-protected
Approvals: UL, CSA
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 114
Components
Ctd.
Advantys FTB I/O module
Suitable for use in harsh environments
Also available with metal housing for extreme environments
Communication possible via CANopen, DeviceNet,
Profibus-DP or Interbus
Combined input/output module
Diagnostic state information via LEDs and via the bus for each channel and for the module so that faults can be pinpointed
Possible to connect Desina sensors with integrated diagnostic function
Outputs protected against short-circuits and overvoltages
Temperature range: 0 to +55°C
UL Listed certification
Harmony XVB signal beacon
Visual and audible signal device with continuous, flashing or high-speed flashing light
Green, red, orange, blue, yellow and transparent lights.
A maximum of 5 signaling elements can be combined
Stackable and with twist and lock function for easy installation
Temperature range: -25..+ 50°C
Approvals: CSA, UL
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 115
Components
Ctd.
Magelis XBT-N401 text display
LCD display, backlit, 8 keys (4 of which are freely configurable and allow for flexible assignment)
Compatible with many different devices using Modbus or
Uni-Telway communication
Quick programming with no need for formatting, startup wizard, simulation without PLC
Different languages and fonts can be selected
Optimum dimensions for straightforward installation
2 spring clamps for easy mounting
Temperature range: 0..+ 55°C
Approvals: CE, UL, CSA
Magelis XBT-G4330 display terminal
Touch panels (STN/TFT technology) with 24 V DC supply
Flat design
Brightness and contrast adjustment
Supports communication via Uni-Telway, Modbus and (to some extent) Ethernet TCP/IP
Memory expansion via CF card (for application)
Temperature range: 0..+ 50°C
Approvals: UL, CSA
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 116
Components
Ctd.
Premium PLC
Various communication cards for Fipway, Modbus Plus,
Fipio Agent, Uni-Telway, Modbus/Jbus, CANopen, modem, serial interfaces, Ethernet TCP/IP
Memory expansion via PCMCIA card (RAM or Flash
EPROM)
Real-time clock
Four programming languages in Unity (SFC, LD, ST, IL)
Program can be edited in RUN mode
Digital and analog input/output modules
Control, counter, positioning and communication modules
Temperature range: 0..+ 60°C (+5..+55 to IEC 1131-2)
Approvals: UL, CSA, BV, DNV, GL, LR, RINA
Premium_Altivar_ICLA_Magelis_EN.doc Schneider Electric 117
Contact
Author
Schneider Electric GmbH
Customer & Market
System & Architecture
Architecture Definition
Support
Telephone E-Mail
+49 6182 81 2555 [email protected]
Schneider Electric GmbH
Steinheimer Strasse 117
D - 63500 Seligenstadt
Germany
Premium_Altivar_ICLA_Magelis_EN.doc
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication .