Schneider Electric EcoStruxure Process Expert 2020 R2 Platform User Guide
广告
广告
Process Expert
User Guide
EIO0000001114.15
12/2020 www.se.com
Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its subsidiaries referred to in this guide are the property of Schneider Electric SE or its subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and furnished for informational use only. No part of this guide may be reproduced or transmitted in any form or by any means (electronic, mechanical, photocopying, recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide or its content, except for a non-exclusive and personal license to consult it on an "as is" basis. Schneider Electric products and equipment should be installed, operated, serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational content of this material or consequences arising out of or resulting from the use of the information contained herein.
Table of Contents
EIO0000001114.15
Understanding EcoStruxure Process Expert
........................................15
Terminology Used in This Manual.........................................................16
Introducing EcoStruxure Process Expert ....................................................17
EcoStruxure Process Expert ................................................................17
EcoStruxure Process Expert Architecture .............................................18
Object Model Concept.........................................................................19
Object Based Engineering .............................................................19
Object Template Description ..........................................................20
Application Templates....................................................................23
Topological Templates ...................................................................24
Interface Models ...........................................................................24
Instances of Templates ..................................................................25
System Engineering Life Cycle Concept ...............................................26
The System Engineering Life Cycle ................................................26
Platform Components....................................................................27
Global Templates Definition Stage ..................................................28
Instantiation Stage ........................................................................29
Project Definition Stage .................................................................32
Assignment Stage .........................................................................34
Generation Stage ..........................................................................35
Refinement Stage .........................................................................36
Configuration Stage.......................................................................37
Mapping Stage..............................................................................39
Build Stage ...................................................................................40
Deployment Stage.........................................................................41
Execution Stage............................................................................42
Working with the Software
.......................................................................43
Starting and Quitting System Server and Clients .........................................44
Logging In and Out of System Server and Clients ..................................44
Locking and Unlocking the Software.....................................................46
Starting the System Server Again.........................................................46
Client/Server Connection.....................................................................47
Quitting the Software...........................................................................50
Multiuser Functionality.........................................................................52
Notification Panel ..............................................................................54
Hardware and Software Capabilities.....................................................61
Supported Data Types.........................................................................63
Naming Rules.....................................................................................65
3
4
Software Participant Help ....................................................................69
Using Help for Different Versions of Schneider Electric
Help on User-Created Templates .........................................................71
Engineering Client User Interface Description .......................................76
About Dialog Box ...............................................................................78
Engineering Client and Explorer Work Areas.........................................79
Organizing Work Areas .......................................................................82
Working with Panes ............................................................................85
Using Menus ......................................................................................89
Software Participant Windows .............................................................90
Filtering and Sorting Data ....................................................................93
Keyboard Shortcuts ............................................................................96
Engineering a System
..............................................................................97
Quick Reference Guides ...........................................................................98
System Creation Workflow...................................................................98
Task Quick Reference ....................................................................... 101
Organizing Systems .......................................................................... 105
Creating Systems ............................................................................. 106
Creating System Backups ................................................................. 108
Restoring Systems............................................................................ 110
Instantiating Templates...................................................................... 115
Organizing the System Application ............................................... 116
Application Explorer ................................................................. 116
Browsing Application Templates ................................................... 119
Using the Application Browser Pane .......................................... 121
Creating Application Folders ........................................................ 124
Assigning Icons to Application Folders .......................................... 129
Creating Instances ...................................................................... 130
Counting Instances ..................................................................... 133
Accessing Instance Properties ..................................................... 134
Configuring Instances.................................................................. 139
Using the Asset Workspace Pane................................................. 143
Instance Indicators............................................................................ 144
Instance Progress Indicators ........................................................ 144
Instance Validity Indicator ............................................................ 145
Instance Write-Lock Indicator ....................................................... 146
Linking Instances by Using the Asset Workspace Editor....................... 146
Asset Workspace Editor............................................................... 146
Using the Simplified View............................................................. 149
Instance Link Status .................................................................... 150
Linking Instances ........................................................................ 152
Using the RTNS Interface ............................................................ 154
Managing Application Folders and Instances ...................................... 155
Viewing Instance Configuration .................................................... 155
Changing the Application Hierarchy .............................................. 156
Copying and Pasting Application Folders and Instances................. 157
Moving Application Folders and Instances..................................... 158
EIO0000001114.15
EIO0000001114.15
Updating and Replacing Templates of Instances............................ 161
Exporting and Importing Application Objects to CSV and XML
Exporting Folders and Instances to CSV and XML Formats ............ 169
Exporting Asset Workspaces to CSV Format ................................. 171
CSV Application Export File ......................................................... 171
Editing the CSV Application Export File ......................................... 174
XML Application Export File ......................................................... 184
Editing the XML Application Export File to Manage Folders and
Instances.................................................................................... 185
Editing the XML File to Manage Interface Links ............................. 189
Importing a CSV or XML File Into the Application ........................... 191
Project Explorer and Project Browser ............................................. 199
Project Explorer ........................................................................ 200
Project Browser ........................................................................ 201
Control Project Definition Stage ......................................................... 203
Creating Control Projects ............................................................. 203
Creating Control Project Sections ................................................. 206
Managing Control Projects ................................................................ 206
Control Project Section Order....................................................... 207
Exporting Control Projects ........................................................... 207
Importing Control Projects............................................................ 211
Importing a Control Expert Project ................................................ 223
Managing Data Backup Files........................................................ 224
Supervision Project Definition Stage................................................... 226
Internal Supervision Architecture .................................................. 226
Creating Supervision Projects ...................................................... 226
Creating Supervision Project Components.......................................... 229
Creating Clusters ........................................................................ 229
Creating Supervision Servers and Clients ..................................... 230
Creating I/O Devices ................................................................... 232
Creating Communication Ports..................................................... 234
Implementing Redundancy .......................................................... 236
Managing Supervision Projects .......................................................... 238
Exporting a Supervision Project.................................................... 238
Importing a Supervision Project .................................................... 242
Participant Project Indicators ............................................................. 251
Participant Project Progress Indicators ......................................... 251
Participant Project Validity Indicators ............................................ 252
Participant Project Write-Lock Indicator......................................... 254
Viewing the Last Action Summary ................................................ 254
Creating and Managing Sections and Containers ................................ 256
Assignment Editor ....................................................................... 256
Creating Control Project Sections ................................................. 261
Creating Supervision Tag Containers ............................................ 263
Creating Supervision Pages......................................................... 267
Assigning Facets of Instances............................................................ 268
Defining the Control Facet Assignment Mechanism ....................... 268
Previewing Facets Assignments ................................................... 277
5
6
Assigning Control Facets of Instances .......................................... 279
Assigning Supervision Facets of Instances.................................... 281
Assigned Facet Description.......................................................... 282
Automatic Assignment of Remaining Facets.................................. 284
Automatic Assignment of Supervision Facets ................................ 285
Viewing the Application Structure in Control Projects ..................... 287
Managing Assigned Facets................................................................ 292
Facet Actions After Assignment.................................................... 292
Viewing Facet Assignments ......................................................... 294
Order of Control Facets ............................................................... 295
Navigating from Facets to the Instance ......................................... 296
General Description .......................................................................... 297
Generation Process Description ................................................... 297
Control Project Specifics.............................................................. 300
Selecting Versions of Types in Control Facets During
Generation ................................................................................. 305
Statuses of Facets ...................................................................... 319
Generating a Project for the First Time................................................ 321
Generating Entire Projects ........................................................... 321
Generating Sections, Containers, and Nodes ................................ 322
Generating Projects After Changes .................................................... 323
Generating Participant Projects After Changes .............................. 323
Regenerating a Control Project .................................................... 327
Generating Equipment in Supervision Projects.................................... 329
Generating Equipment Based on the Application ........................... 329
Generation Diagnostic Messages....................................................... 331
Generation Diagnostic Messages ................................................. 331
Managing Generated Facets.............................................................. 332
Managing Generated Facets ........................................................ 332
Control Project Refinement Stage ...................................................... 336
Refining the Logical Control Project .............................................. 336
Identifying Code Generated by the Software.................................. 341
Creating and Updating Device DDT Variables in Logical Control
Projects ...................................................................................... 343
Managing Consistency ................................................................ 347
About Variables for Peer to Peer Communication........................... 350
Managing Network Variables........................................................ 357
Supervision Project Refinement Stage................................................ 360
Refining the Supervision Project................................................... 360
Creating the Topology of the System .................................................. 364
Organizing the System Topology .................................................. 365
Selecting Topological Templates................................................... 368
Using Configuration Change on the Fly (CCOTF) .......................... 369
Configuring a Controller ............................................................... 371
Configuring a Station Node .......................................................... 379
Configuring an STB Island ........................................................... 384
Configuring a PROFIBUS Remote Master and Decentralized
Peripherals ................................................................................. 388
EIO0000001114.15
EIO0000001114.15
Configuring Modbus TCP and EtherNet/IP Devices........................ 391
Configuring HART Modules.......................................................... 395
Configuring an Ethernet Network .................................................. 397
Connecting to an Ethernet Network .............................................. 399
Managing the Topology ..................................................................... 406
Moving Topological Folders and Entities........................................ 407
Updating Templates of Topological Entities.................................... 407
Exporting Topological Entities....................................................... 408
Importing Topological Entities....................................................... 411
Control Project Mapping Stage .......................................................... 420
Creating Control Project Executables............................................ 421
Mapping Services ....................................................................... 423
Mapping Communication ............................................................. 424
Mapping Network Variables.......................................................... 435
Mapping Hardware ...................................................................... 442
Exporting and Importing Hardware Mappings...................................... 449
Exporting Hardware Mapping Data ............................................... 449
Editing the Hardware Mapping Export File..................................... 451
Importing Hardware Mappings ..................................................... 455
Supervision Project Mapping Stage.................................................... 457
Creating Supervision Project Executables ..................................... 457
Mapping Services ....................................................................... 459
Mapping Communication ............................................................. 460
Control Project Build Stage ................................................................ 464
Building the Logical Control Participant Project.............................. 464
Changing the Built Control Participant Project ............................... 470
Managing Hardware Abstraction Layer (HAL) Variables and
DFBs.......................................................................................... 472
Supervision Participant Project Build Stage......................................... 475
Building the Supervision Participant Project................................... 475
Changing the Built Supervision Participant Project......................... 479
Control Project Deployment Stage ..................................................... 481
Control Participant Project Deployment Process ............................ 481
Deploying to an Emulated Simulator ............................................. 484
Communication Between the Computer and Engines..................... 487
Managing Passwords of Control Participant Projects ..................... 488
Deploying to Redundant Controllers ............................................. 494
Deploying the Control Participant Project ...................................... 496
Re-Deploying the Control Participant Project ................................. 501
Deploying Data to Controllers and Station Nodes........................... 505
Deploying Control Project Changes .............................................. 509
Changes Requiring to Stop the Controller ..................................... 519
Supervision Project Deployment Stage............................................... 520
Preparing for Deployment ............................................................ 520
Deploying the Built Supervision Participant Project from the
Executable ................................................................................. 521
Deploying the Built Supervision Participant Project from the
Station Node............................................................................... 523
7
8
Deploying Supervision Participant Project Changes ....................... 528
Control Project Execution Stage......................................................... 531
Control Participant Project Execution Process ............................... 531
Execution With Redundant Controllers.......................................... 534
Starting and Stopping Controllers ................................................. 536
Synchronizing Redundant Controllers ........................................... 541
About Changes Made Online ....................................................... 544
Making Changes Online............................................................... 548
Backing Up Controller Data.......................................................... 554
Importing Sections from the Logical Control Participant
Project........................................................................................ 558
Main Redundant Controller Scenarios........................................... 561
Redundant Controller Reservation and Connection
Scenarios ................................................................................... 563
Updating the Logical Control Participant Project and Controller
Configuration .............................................................................. 567
Supervision Project Execution Stage .................................................. 576
Executing the Deployed Supervision Participant Project ................. 576
Engineering M580 Safety Systems .......................................................... 577
Using Modicon M580 Safety Controllers ............................................. 577
M580 Safety Systems in the Instantiation Stage .................................. 578
M580 Safety Systems in the Project Definition Stage ........................... 579
Creating M580 Safety Control Projects ......................................... 579
Exporting and Importing M580 Safety Control Projects................... 581
Importing a Safety Control Project Associated to an Existing
M580 Safety Controller ................................................................ 582
M580 Safety Systems in the Assignment Stage................................... 584
M580 Safety Systems in the Generation Stage.................................... 585
M580 Safety Systems in the Refinement Stage ................................... 585
M580 Safety Systems in the Configuration Stage ................................ 587
Creating and Configuring M580 Safety Controllers......................... 587
Managing the Safety Password .................................................... 588
Exporting and Importing M580 Safety Controllers .......................... 590
M580 Safety Systems in the Mapping Stage ....................................... 592
M580 Safety Systems in the Build Stage............................................. 592
M580 Safety Systems in the Deployment Stage .................................. 593
M580 Systems in the Execution Stage................................................ 594
Using Supervision with M580 Safety Systems ..................................... 595
Managing Communication....................................................................... 597
Communication Through Modbus TCP Ethernet Implicit Messaging (I/
Communicating with Devices Through Modbus TCP Implicit
Messaging (I/O Scanning)............................................................ 598
Communicating with STB Islands Through Modbus TCP Implicit
Messaging.................................................................................. 600
Communicating with PROFIBUS Remote Masters Through
Modbus TCP Implicit Messaging .................................................. 601
Peer to Peer Communication Through Modbus TCP Ethernet
Implicit Messaging....................................................................... 603
EIO0000001114.15
EIO0000001114.15
Communication by Using Modbus TCP Ethernet Explicit
Communication with Devices by Using Modbus TCP Ethernet
Explicit Messaging ...................................................................... 604
Communication by Using EtherNet/IP Explicit Messaging .................... 608
Communication with Devices by Using EtherNet/IP Explicit
Messaging.................................................................................. 608
Communication Through Modbus Explicit Messaging .......................... 611
Communication with Devices Through Modbus Explicit
Messaging.................................................................................. 611
Example Overview ...................................................................... 616
Example A .................................................................................. 619
Example B .................................................................................. 623
Example C.................................................................................. 628
Example D.................................................................................. 634
Monitoring Modbus Device Data Directly from Supervision................... 639
Monitoring Modbus Device Data Directly from Supervision ............. 639
Communication with Devices by Using a PROFIBUS Master
Communication with Devices by Using a PROFIBUS Master
Module ....................................................................................... 642
Managing, Modifying, and Creating Templates
.................................. 644
Global Templates Explorer................................................................. 645
Global Templates Folders .................................................................. 650
Global Templates .............................................................................. 651
Opening Global Templates Editors ..................................................... 653
Opening Global Templates Editors................................................ 653
Interface Editor ........................................................................... 654
Facet and Composite Template Editors............................................... 659
Facet Editor ................................................................................ 659
Composite Editor ........................................................................ 663
Common Template Editor Components .............................................. 666
Common Template Editor Toolbars and Menus.............................. 666
Common Template Editor Panes .................................................. 670
Using the Radar View .................................................................. 672
Using the Simplified View in Template Editors................................ 673
Managing Global Templates .................................................................... 675
Managing Global Templates .............................................................. 675
Saving Changes In Global Templates ........................................... 675
Copying and Pasting Global Templates and Folders ...................... 677
Exporting Templates.................................................................... 677
Importing Templates .................................................................... 680
Purging the Global Templates Library ........................................... 686
Updating, Replacing, and Duplicating Global Templates....................... 688
Template Modification Strategy .................................................... 688
Updating Global Templates and Templates of Elements ................. 689
Replacing the Template of an Element of a Global
Template .................................................................................... 693
9
Duplicating Global Templates ....................................................... 698
Replace Dialog Box .................................................................... 701
Software Services
................................................................................... 702
Content Repository Explorer............................................................ 703
Temporary Contents Repository Files ................................................. 706
Default Keyboard Layout of the Virtual Machine .................................. 707
Virtual Machine System Locale .......................................................... 709
Appendices
.............................................................................................. 711
Linking Instances by Using the Links Editor .............................................. 712
Linking Instances by Using the Links Editor......................................... 715
Glossary
Index
10 EIO0000001114.15
Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
!
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
!
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
!
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and its installation, and has received safety training to recognize and avoid the hazards involved.
EIO0000001114.15
11
About the Book
Document Scope
This manual contains general information about EcoStruxure Process Expert and guides you through the stages to engineer a system.
This manual is organized in five main parts:
• Understanding EcoStruxure Process Expert:
Provides information on the object model and the system engineering life cycle concepts that the implementation of automation systems is based on.
• Working with the software:
Describes the graphical user interface and how to use the different tools that are at your disposal.
• Engineering a system:
Provides step by step instructions to help you implement a system by following the system engineering life cycle.
• Global Templates library and editors:
Describes the Global Templates library, the templates that it can contain, and the editors that allow you to manage them.
• Software services:
Provides information on the content repository and on language settings for software Participants.
It is written for users who are familiar with the engineering of Control and
Supervision systems.
For further information, refer to the related documents that are mentioned in this manual.
Validity Note
This document is valid for EcoStruxure Process Expert 2020 R2 or later. It supersedes any previous version.
Related Documents
Title of documentation
EcoStruxure ™ Process Expert - Security Deployment Guide
EcoStruxure ™ Process Expert - General Purpose Library User Guide
EcoStruxure ™ Process Expert - General Purpose Library Process
Templates Reference Manual
Reference number
EIO0000004234 (eng)
EIO0000004045 (eng)
EIO0000004043 (eng)
EcoStruxure ™ Process Expert - General Purpose Library Device
Templates Reference Manual
EcoStruxure
EcoStruxure
™
™
Process Expert - Process Templates User Guide
Process Expert - Device Templates User Guide
EIO0000004044 (eng)
EIO0000000987 (eng)
EIO0000001308 (eng)
EcoStruxure ™ Process Expert - Communication Templates User Guide EIO0000001311 (eng)
EcoStruxure ™ Process Expert - Diagnostic Templates User Guide EIO0000001526 (eng)
EcoStruxure ™ Process Expert - Foundation Application Templates User
Guide
EcoStruxure ™ Process Expert - Control Participant Services User
Guide
EIO0000002403 (eng)
EIO0000001524 (eng)
12 EIO0000001114.15
Title of documentation
EcoStruxure ™ Process Expert - Supervision Participant Services User
Guide
EcoStruxure ™ Process Expert - Runtime Navigation Services User
Guide
EcoStruxure ™ Process Expert - Global Templates Reference Manual
EcoStruxure ™ Process Expert - Installation and Configuration Guide
EcoStruxure ™ Process Expert - Licensing Guide
Reference number
EIO0000001525 (eng)
EIO0000001574 (eng)
EIO0000001986 (eng)
EIO0000001255 (eng)
EIO0000001261 (eng)
You can download these technical publications at app.schneider-electric.com/ ecostruxure-hybrid-dcs , Document Downloads section.
Registration required.
EcoStruxure Process Expert Support Portal
Visit app.schneider-electric.com/ecostruxure-hybrid-dcs for support, software updates, and latest information on EcoStruxure Process Expert.
Registration required.
Trademarks
Schneider Electric, EcoStruxure, Process Expert, and Control Expert are trademarks of Schneider Electric SE, its subsidiaries, and affiliates.
Citect is a registered trademark of AVEVA Group plc in the United States and/or other countries.
Microsoft and Windows are either registered trademarks or trademarks of
Microsoft Corporation in the United States and/or other countries.
Caché and InterSystems are trademarks of InterSystems Corporation.
Other names are registered trademarks or trademarks of their respective owners.
Product Related Information
The examples in this manual are given for information only.
WARNING
UNINTENDED EQUIPMENT OPERATION
Adapt examples that are given in this manual to the specific functions and requirements of your industrial application before you implement them.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: Templates shown in examples throughout this manual may differ from the actual templates contained in the supplied Schneider Electric libraries.
EIO0000001114.15
13
WARNING
LOSS OF CONTROL
• Perform a Failure Mode and Effects Analysis (FMEA) of your application, and apply preventive and detective controls before implementation.
• Provide a fallback state for undesired control events or sequences.
• Provide separate or redundant control paths wherever required.
• Supply appropriate parameters, particularly for limits.
• Review the implications of transmission delays and take actions to mitigate.
• Review the implications of communication link interruptions and take actions to mitigate.
• Provide independent paths for control functions (for example, emergency stop, over-limit conditions, and fault conditions) according to the safety analysis and applicable codes, and regulations.
• Apply local accident prevention and safety regulations and guidelines.
1
• Test each implementation of a system for proper operation before placing it into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
1 For additional information, refer to NEMA ICS 1.1 (latest edition), Safety
Guidelines for the Application, Installation, and Maintenance of Solid State Control and to NEMA ICS 7.1 (latest edition), Safety Standards for Construction and
Guide for Selection, Installation and Operation of Adjustable-Speed Drive
Systems or their equivalent governing your particular location.
14 EIO0000001114.15
Understanding EcoStruxure Process Expert
What’s in This Part
Introducing EcoStruxure Process Expert .........................................................17
Overview
This part introduces EcoStruxure Process Expert and describes the concepts and underlying mechanisms that are applied to engineer an automation system.
In this manual, software is used to refer to EcoStruxure Process Expert.
EIO0000001114.15
15
General Information
What’s in This Chapter
Overview
This chapter contains general information about the software.
Terminology Used in This Manual
EcoStruxure Process Expert
To make reading easier, the software is sometimes used in place of EcoStruxure
Process Expert throughout this manual.
Item Names
Because you can customize the names of most items that are displayed in the user interface, this manual uses predominantly the default names created by the software to describe items such as:
• Systems
• Topological entities
• Folders
• Projects and their components
• Instances
16 EIO0000001114.15
Introducing EcoStruxure Process Expert
Introducing EcoStruxure Process Expert
What’s in This Chapter
EcoStruxure Process Expert Architecture........................................................18
Overview
This topic introduces EcoStruxure Process Expert and describes its main distinctive features.
EcoStruxure Process Expert
Features
EcoStruxure Process Expert is the next generation process automation system to engineer, operate, and maintain your entire plant.
It is a single environment, which interconnects and manages all the components of the automation architecture:
• Standard field buses.
• Instrumentation.
• Intelligent, connected devices.
• Ethernet-based control networks.
• Controllers.
• Engineering and operator stations.
• Alarm management.
The software delivers everything you need to run a sustainable, productive, and market-agile plant:
• Scalable and powerful automation platform.
• Full process traceability.
• Embedded energy management.
• Fast and efficient engineering and deployment of configurations.
• Powerful native diagnostic features.
• Fast access to process data by using Runtime Navigation Services.
• Integrated and specialized, validated object libraries.
Benefits
Using EcoStruxure Process Expert provides the following benefits, which help you:
• Reuse automation objects with proven, standard designs.
• Reduce commissioning time and cost.
• Reduce engineering and integration risks.
• Put in place appropriate preventive, predictive, and prescriptive maintenance so that unplanned downtime approaches zero.
• Improve quality of production-related decisions and maximize operational profitability.
• Optimize the management of flows and resources to maximize output and profitability.
• Manage regulatory requirements.
EIO0000001114.15
17
Introducing EcoStruxure Process Expert
WARNING
UNINTENDED EQUIPMENT OPERATION
When engineering automation systems by using EcoStruxure Process Expert:
• Identify and understand all implications and consequences of any changes on the automation system.
• Evaluate and simulate any actions that have an influence on the automation system.
• Implement elementary protective measures in the process of engineering automation systems.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
EcoStruxure Process Expert Architecture
Integration with the Plant
EcoStruxure Process Expert offers a scalable architecture, future-ready network with high availability for continuous operation of your plant.
18 EIO0000001114.15
General Concepts
What’s in This Chapter
System Engineering Life Cycle Concept..........................................................26
Overview
This chapter describes the object model concept and how it is applied within the software. It also describes the concept of engineering an automation system in stages.
Object Model Concept
Overview
This section describes the concept of object model and the resulting templates that are used to engineer automation systems by using the software.
Object Based Engineering
Description of the System
In EcoStruxure Process Expert a system is the representation of a physical automation system and is defined by three independent parts:
• The application : Defines the functions of the system and the corresponding process hierarchy.
• Projects : Define the Participant projects that implement the logic and function of the system:
◦ Control Projects
◦ Supervision Projects
• The topology : Defines the hardware and software infrastructure of the system. It consists of:
◦ Controllers
◦ Devices connected to field buses
◦ Networks
◦ Station nodes (their hardware and software components)
Object Model Concept
Object models represent the application and topology of a system.
There are different types of object models representing the application of the system based on their purpose:
• Process objects representing, for example, the I/Os of pumps, valves, and sensors in several tanks.
• Device objects representing, for example, the functions to control a process object such as a motor by using a drive.
• Communication objects representing, for example, the functions to manage communication with device objects through the port of an M580 controller with Modbus TCP explicit messaging.
Likewise, object models representing the topology of the system are called topological objects. They can represent, for example, the CPU module of an M580 controller.
EIO0000001114.15
19
The approach of representing any entity or function that exists in the real world with the use of object models is referred to as object-oriented modeling and is based on the abstraction principle: Process of reducing the information to retain only what is relevant for a particular component or function independently of the context.
The following figure illustrates the application object-oriented modeling of a conveyor.
From Object Model to Object Template
The next step consists in creating, based on the object model, a component that models an item or a function of the real world. This component needs to be generic enough to be reused in different systems.
The standardization principle is used to achieve this objective: Process of finding the common characteristics of different items or functions.
The resulting component is called an object template .
The following figure illustrates the process of standardizing an object model representing a conveyor to create a template, which allows modelling conveyors and similar items (such as a mixer) in different systems.
Object Template Description
Overview
Schneider Electric object templates created from object models are called Global
Templates and are grouped in libraries. When a library is installed, its templates appear in the
Global Templates Explorer , page 645 . These templates can be
used in any system that is created by using EcoStruxure Process Expert.
To make reading easier, the word templates is used to refer to Global Templates.
Templates provide collaboration and data sharing between Participants and the software platform.
20 EIO0000001114.15
By doing so, templates reduce the engineering effort and provide consistency.
Object Template Classification
Templates can be placed one inside the other, linked, and can include several capabilities to model an item or a functionality of the real world. Therefore, the distinction is made between three types of templates:
• Facet templates : They are the smallest templates available. They encapsulate a constituent, which is provided by a specific Participant to deliver the respective service. As such there are:
◦ Control facet templates providing Control services. For example, in the
General Purpose Library, the service that is provided by the $MOTORGP_
UL facet template is the on/off motor management functionality. The functionality is implemented by using the MOTORGP function block, which is encapsulated inside the template.
◦ Supervision facet templates providing Supervision services. For example, in the General Purpose Library, the service that is provided by the
$BlowerLeftGP_m_CG genie facet template is the animated graphical representation of a motorized blower, which can be displayed on an operator station. The animated graphic is encapsulated inside the template.
• Composite templates : They consist of one or more facet templates and/or other composite templates. Composite templates that are included inside another composite template are called composite references.
Depending on their composition, composite templates can be:
◦ Control composite templates: Contain only Control references.
◦ Supervision composite templates: Contain only Control references.
◦ Control module templates: Highest level of composite template, which contains both Control and Supervision references.
NOTE: Facet templates that are included inside a composite template are called facet references.
• Interface models : They are considered as a template because they are generic and can be reused but they are actually a mechanism that allows linking to each other:
◦ Any combination of facet and composite templates.
◦ Instances of templates.
There are different types of interface models depending on the objects that they link. You can configure interface models.
For details, refer to the help of the Schneider Electric libraries for EcoStruxure
Process Expert.
The following figure illustrates a single facet template.
The arrows represent the inputs and outputs of the facet which propagate the data.
EIO0000001114.15
21
The following figure illustrates a composite template including another composite template (composite reference) and two facet templates.
- - Represents interface links
Template Terminology
The following example shows the graphical representation of a sample composite template. The names of elements may vary.
22
NOTE: Interfaces are not represented since they are mechanisms for managing data exchange between references.
The table explains the color coding that is used in the generic composite template
Template .
Color Description
Control facet template, which encapsulates a functionality that is provided by the Control
Participant.
Supervision facet template, which encapsulates a functionality that is provided by the
Supervision Participant.
Composite template, which can contain:
• Control and/or Supervision facet templates
• Other composite templates
NOTE: This color coding is used in the user interface to differentiate the different types of templates and related services.
The table describes the items that compose the generic composite template
Template and the terminology that is used to designate these items depending on the context.
Item
1
2
Description
Template is the highest level composite template and is called a control module because it provides both the Control and Supervision functionalities that are required to manage the object that is modeled by the template.
Control is a Control composite template because it contains Control facet templates. It is also called a composite reference as it is referenced inside the composite template
Template .
EIO0000001114.15
Item
3
4
5
6
7
8, 9
Description
In the context of Template , Control is an element of Template
Service1 is a composite reference.
In the context of composite reference Control , Service1 is an element of Control .
The same applies to composite reference Service2 .
Both Service1 and Service2 are Control composite templates since they contain only
Control facets.
Logic and Signal1 are Control facet references.
In the context of the composite reference Service1 , they are elements of Service1 .
Signal3 is a Control facet reference.
In the context of the control module Template , Signal3 is an element of Template .
Supervision is a Supervision composite reference because it is contained in composite template Template . It contains Supervision elements (composite references Tag and
Genie ).
In the context of the control module Template , Supervision is an element of Template .
Tag is a Supervision composite reference because it is contained in composite
Supervision and contains only a Supervision element ( OnOff ).
Likewise Genie is a Supervision composite reference.
OnOff and Pump are Supervision facet references and elements of templates
SuperTagvision and Genie respectively.
Types of Object Templates
Like object models represent the application and the topology of the system, so do templates.
As a result, the following types of templates exist:
• Application templates : Facet and composite templates, which define the functional components in the application of the system.
• Topological templates : Facet and composite templates, which define hardware and software components of the topology of the system.
Application Templates
Overview
Control and Supervision facet templates encapsulate the respective Participant capabilities:
• For Control:
◦ Logic facet templates: Implement a specific functionality, for example, discrete motor management.
• For Supervision:
◦ Data facet templates: Allow defining tags and user interface messages that are required for acquiring runtime data.
◦ Genie facet templates: Represent runtime data by using an animated graphic.
Facet templates encapsulate the respective Participant capabilities. For Control, these are Logic facet templates, which implement a specific functionality, for example, discrete motor management.
Based on a combination of these, application control module templates have been created, which allow you to model the application of a system in terms of Control and Supervision services.
EIO0000001114.15
23
Topological Templates
Introduction
Topological templates allow you to model the hardware and software infrastructure of the topology of a system by creating topological entities.
They are located in the Foundation library and grouped by category.
Sub-Types of Topological Templates
The following subtypes of topological templates are available:
• Network : Models control and field bus networks.
For example: Ethernet LAN, Modbus, CANopen, Profibus DP, RIO S908, RIO
Ethernet, local bus for controllers and Advantys islands).
• Network devices : Models the field bus devices.
For example: Gateways.
• Station node : This template models the components of the different types of stations that are connected to the Ethernet network.
For example: network interface cards (NICs), Supervision software, OPC
Factory Server (OFS) software, and Control software.
• Controller : Models the controller hardware that is managed by the Control
Participant.
For example: Hardware of the Quantum platform.
• Device I/O : Models devices and remote I/Os including third party devices that can be connected as nodes to Ethernet networks.
For example: Advantys Island I/Os, energy devices, motor starters, and instrumentation devices.
Interface Models
The templates are available in the form of libraries and after installation, appear in the
Global Templates Explorer , page 645
where they are grouped by category.
For details, refer to the help of the Schneider Electric libraries for EcoStruxure
Process Expert.
NOTE: There is a relation between Control and Supervision facet templates because for a given Control service, which is provided by a Control facet, the
Supervision facet represents the part of the service that is visible to the user
(for example supervisory user interface and mode of operation).
Introduction
Interface models allow you to define:
• data exchange between two object instances or two object references.
• dependencies between two object instances or two object references such as compatibility or requirement rules.
Types of Interface Models
The following types of interface models are predefined:
• Physical : Allow data exchange at the physical level (modules) between:
◦ Topological instances
◦ Topological references
• Communication : Allow data exchange at the logical level (I/O scanner, OPC
Factory Server software, Supervision I/O devices) between:
24 EIO0000001114.15
◦ Topological instances
◦ Topological references
• Application : Allow data exchange between:
◦ Application instances/references
◦ Topological instances/references
• Mapping : Allow data exchange during the mapping stage between application objects (representing the logical projection of the hardware) and topological objects (representing the actual hardware defined in the topology).
Instances of Templates
From Templates to Instances
The software lets you create application and topological instances from the corresponding templates.
Because control module templates integrate a range of Control and Supervision services, editable parameters, and expose a set of interfaces, you can customize each instance to fulfill specific requirements.
The process of creating instances from templates and configuring them is called instantiation .
To access and configure their parameters, instances produce facets, which are based on the facet templates that each control module template contains.
During the instantiation, you can:
• Select services among those that the template provides. For Schneider
Electric templates, some services are mandatory (for example, Logic ) and some are optional (for example, Supervision ).
• Edit the values of parameters (for example, provide a high limit value for an analog level sensor).
• Link instances to each other (for example, link a motor instance to the instance representing the functions of the variable speed drive that controls the motor).
When you enable (select) a service, the software creates a facet, which is an instance of the facet template that provides the service. This facet is associated to the instance of the template that references the service.
The other way around, when you disable (unselect) a service, the software deletes the corresponding facet.
The following figure shows an example of several instances with different configurations that you can create from one template.
EIO0000001114.15
25
Only some facets of instances Conv_1, Pump_1, and Pump_2 are shown for illustration purposes.
System Engineering Life Cycle Concept
Overview
The concept of breaking down into stages the workflow to engineer an automation system is referred to as the system engineering life cycle in this manual.
This section provides a general description of each stage using:
• A stage map showing the position of the stage within the system engineering life cycle.
• A definition to explain the purpose of the stage.
• An example to facilitate the understanding.
The System Engineering Life Cycle
Overview
For a description of the representation of a system in EcoStruxure Process Expert, refer to
Object Based Engineering , page 19
.
Graphical Representation
The system engineering life cycle is the representation of the stages of the engineering workflow (from design to operation and maintenance) that you need to complete to
by using the software.
The following figure shows the system engineering life cycle.
26
The stages are grouped into 4 main parts where Topology, Projects, and
Application represent the components of a system. Library represents the Global
Templates, which are used in the other three parts. To each part corresponds an explorer, which provides the functionality to complete each of the stages.
The arrows represent the order in which you need to complete the stages. The horizontal double bars represent the stage gates where the previous stages have to be completed before you can proceed further in the life cycle.
The Assignment and Mapping stages make the link between the different components of the system.
EIO0000001114.15
You can find a list of the stages and the main tasks that you can complete in each stage in
quick reference Guides, page 98 .
Illustrating the Concept
When necessary, to illustrate the concept of a stage, a concrete example is used.
The example is a water tank system that collects rain water. The installation consists of the following equipment:
• 2 electrical pumps, which transfer the water from the tank into a separate reservoir.
• 3 digital switches, which indicate the rain water level in the tank.
The following figure illustrates the water tank system:
1 Pump: Pmp1
2 Pump: Pmp2
3 High-level switch: Lsh1
4 Low-level switch: Lsl1
5 Very low-level switch: Lsll1
6 Rain water tank
7 Reservoir
Pump Management Operating Mode
In the example, 1 of the 2 pumps transfers the rain water into the reservoir. The other pump serves as a back-up pump in case the transfer pump requires maintenance or is out of order. Both pumps exchange their roles periodically and are equipped with a soft starter.
Level Management Operating Mode
In the example, the 3 digital level switches act on the pumps at 3 different water levels: very low, low, and high level. The Lsh1 high level and Lsl1 low-level switches provide information on the level of the water in the tank. The Lsll1 very low-level switch is directly wired to the power supply of both pumps so that they do not run dry.
Platform Components
Overview
The software lets you engineer each part of a system (application, projects, and topology) independently by using specific tools, which provide the necessary functionality.
You can engineer several systems simultaneously.
EIO0000001114.15
27
Platform Managers
The following explorers are available as part of the software platform.
Explorer
Global
Templates
Explorer
Systems
Explorer
Application
Explorer
Project
Explorer
Topology
Explorer
Description
Displays the Global Templates of the installed libraries and those that you have created and/or imported.
They are organized in a folder structure, which makes the templates easily accessible.
The explorer lets you search, create, modify (see EcoStruxure ™ Process Expert,
Global Templates, Reference Manual), and manage Global Templates.
Displays the systems that exist in the database of the system server.
The explorer is the entry point to start engineering systems.
Displays the application of a system in a tree view, which lets you create a hierarchy.
The explorer lets you search, create, configure, and manage the instances that model the application of a system.
Displays, at the platform level, the projects of a system that are managed by the software Participants:
• Control projects
• Supervision projects
The explorer lets you create and manage the Control logic, Supervision data, and the executables of each project.
Displays the topology of a system in the form of a folder structure.
The explorer lets you create and manage the different topological entities that model the hardware infrastructure. Also, it allows you to interact with the controllers, devices, station nodes, and networks of a system.
Global Templates Definition Stage
Stage Map
The following figure shows the position of the Global Templates Definition stage within the system engineering life cycle:
28
Definition
The Schneider Electric application and topological templates that are provided in various libraries allow you to engineer systems. Yet, you have the possibility to modify or create templates.
EIO0000001114.15
The Global Templates Definition is the process of creating and/or modifying templates by:
• Using existing templates from the Global Template library and modifying them to meet your particular requirements.
• Creating new templates by using generic base elements with the help of template editors.
This process is described in a separate manual (see EcoStruxure ™ Process
Expert, Global Templates, Reference Manual).
Instantiation Stage
Stage Map
The following figure shows the position of the Instantiation stage within the system engineering life cycle.
EIO0000001114.15
Definition
The instantiation stage involves modeling:
• The process hierarchy by using a folder structure.
• Functional components by using
of templates.
The resulting folder and instance organization represents the application of the system and is unique.
Once you have created a
, you can create instances from templates that you select among a choice of templates that are available in the
Global Templates library.
Depending on the composition of the template, during the instantiation, the template creates a set of Control and/or Supervision facets, which are associated to the instance and provide specific services.
To fulfill the specific requirements of the application, the instantiation process includes the step of configuring the application folders and the instances that they contain by:
• Selecting/deselecting optional Control and Supervision facets among those that are built into the instance template to enable/disable the corresponding services.
• Editing folder and instance properties and/or parameters.
• Creating links between instances.
29
30
For more information on completing the instantiation stage, refer to the chapter describing its
Example of the Process Hierarchy of the Water Tank System
The following figure shows an example of how you can organize the application of the
water tank automation system, page 27
.
Water tank: Water tank system root folder.
Level: Level management folder, which will contain the instances modeling the water level sensor functionality.
Pumping: Pump management folder.
Pmp1: Folder containing the instances modeling the functionality of the motor of
Pump 1.
Pmp2: Folder containing the instances modeling the functionality of the motor of
Pump 2.
Selecting Templates to Model the Application
The table shows examples of templates of the General Purpose Library that can be used to model the water tank application.
Template Application
$MotorGP Motors of Pump 1 and Pump 2
$ATS48MBGP Altistart 48 progressive starters for Pump 1 and Pump 2
$DigitalInputGP Digital switches (Lsh1, Lsl1, Lsll1)
Example of the Instances Modeling the Water Tank Application
The following figure illustrates the concept of instantiation for the water tank application.
EIO0000001114.15
Selected template
$MotorGP
Instances created from template (1)
Motor_Pmp1
Motor_Pmp2
$ATS48MBGP Motor1_ATS
Motor2_ATS
$DigitalInputGP Lsh1
Lsl1
Lsll1
NOTE: For simplicity, only the following items are represented:
• Pump 1 and level switch objects.
• Instances inside folders Pmp1 and Level.
• Facets of the Motor_Pmp1 instance.
The table describes the instances that are created during instantiation of the templates and gives an example of the configuration possibilities.
Instance description Purpose of the facet contained in the template
(2)
Configuration example (3)
Model the electrical motors of
Pump 1 and Pump 2.
Control facet for on/off logic.
Control facet to manage interlock conditions.
Supervision facet to manage runtime motor on/ off data.
Supervision facet to manage interlock data.
The on/off logic facet is selected by default and cannot be deselected.
The corresponding service is provided for the instance.
You can configure various parameters for this Control service.
The optional interlock condition summary facet is selected, created, and the service is be available for the instance.
The optional Supervision facets are selected, created, and the corresponding services are available for the instance.
You can configure several parameters for these Supervision services.
Model the management of motors for Pump 1 and Pump
2, each by an ATS 48 soft starter device.
Models a digital input for the
Lsh1 high-level detection switch.
Models a digital input for the
Lsl1 low-level detection switch.
Models a digital input for the
Lsll1 low-low-level detection switch.
Not detailed for the example.
Control facet to manage the logic.
Supervision facet for signal data.
Control facet.
(Same as for Lsh1
Supervision facet.
(Same as for
Same as for
Lsh1
Lsh1
)
)
The logic facet is selected by default and cannot be deselected. The corresponding service is provided for the instance.
You can configure several parameters for this Control service.
The optional Supervision facet is selected, created, and the corresponding service are available for the instance.
You can configure several parameters for this Supervision service.
The logic facet is selected by default and cannot be deselected. The corresponding service is provided for the instance.
You can configure several parameters for this Control service.
The optional Supervision facet is selected, created, and the corresponding service is available for the instance.
You can configure several parameters for this Supervision service.
Not detailed for the example.
(1) The name of the instance is user-defined.
(2) The actual templates contain more facet templates than shown in the table.
EIO0000001114.15
31
(3) The facets are created for each instance. The example shows only the configuration for instances Motor_Pmp1 and Lsh1 . In fact, each instance of a template can be configured individually.
Project Definition Stage
Stage Map
The following figure shows the position of the project definition stage within the system engineering life cycle.
32
Definition
The project definition is the process to define the organizational structure of projects that will be integrated into the system through the Participants. You define projects independently from specific hardware components, which gives you flexibility and allows you to use one project with different hardware infrastructures.
Ultimately, towards the end of the system engineering life cycle, to each project will be associated one or more executable files that you can deploy to the topology of the system.
For each system, you can define as many projects as required.
Each project is associated to a Participant and is therefore referred to as a
Participant project .
A system is composed of the following Participant projects:
Control
Supervision
This type of project is specific to a hardware platform (for example,
Modicon M580 platform) and manages the controller program.
This type of project allows you to manage data from the application, represent it graphically, and provide the operator with a user interface to interact with the controller.
NOTE: Supervision projects are optional and you create them depending on the requirements of the system.
Project Structure
The organizational structure of a project is specific to the Participant that it is related to because it reflects the components that the Participant manages.
A Control project consists mainly of nodes representing:
EIO0000001114.15
• The program structure: A Containers node containing FBD and non-FBD program sections, which are referred to generically as containers.
• The binary program: An Executables node providing access to program files and related services.
A Supervision project consists mainly of nodes representing:
• Data: A Containers node containing tag containers for each cluster.
• Graphic elements: A Pages node that contains the user interface visible to the operator.
• Components: A Cluster node for managing servers and communication for data acquisition and representation by cluster.
• The program: An Executables node providing access to services related to the program files.
Types of Projects
As you progress through the system engineering life cycle, a Participant project evolves. To distinguish between the stages that projects go through, specific terminology is used to describe them.
The software manages three types of Participant projects throughout the system engineering life cycle:
Logical Participant projects
Built Participant projects
Deployed Participant projects
Contain the information of the application and the organizational structure of the project with no relation to the hardware infrastructure of the system.
The software creates these projects during the
stage.
Contain the information of the logical Participant project and associate it to the hardware infrastructure of the system. The software creates these projects during the
stage.
Are the built Participant projects that you have deployed to engines of the system (for example, controllers or station nodes). You deploy projects during the
.
The following figure illustrates at which stages of the system engineering life cycle, the different types of projects are managed.
EIO0000001114.15
For more information on completing the project definition stage, refer to the chapter describing its
.
Example
The following projects are defined for the
:
33
Assignment Stage
• A Control project to manage the logic (for example, variables and DFBs,) of the instances of the application. It contains three containers in the MAST task folder corresponding to the folder structure of the application:
◦ Level
◦ Pmp1
◦ Pmp2
• A Supervision project to manage the Supervision services (tags, alarms, supervision pages) of the instances of the application. It contains the following components:
◦ One tag container for the Supervision data facets of the instances of the application.
◦ One page for the Supervision genie facets of the instances of the application.
◦ Components: One of each I/O, alarm, and trend server, and I/O device with its communication port.
Stage Map
The following figure shows the position of the assignment stage within the system engineering life cycle.
34
Definition
The assignment is the process of associating Control and Supervision facets of instances of the application to a container of the corresponding project of the system.
The purpose is to define where the constituents that are encapsulated inside the facets will be generated in the Participant project during subsequent stages of the system engineering life cycle.
You need to assign the two types of facets to the corresponding containers:
• Control facets: To containers of Control projects, which are FBD sections.
• Supervision data facets: To containers of Supervision projects, which are tag containers.
You can assign a facet only to one container per project but you can assign a facet to several projects.
NOTE: Supervision genie facets are assigned to a page of a Supervision project during the refinement stage.
EIO0000001114.15
For more information on completing the assignment stage, refer to the chapter describing its
Example
The table shows an example of assignment of the facets of the instances Motor_
Pmp1 and Lsh1 of the
that you can perform.
Instance
Motor_
Pmp1
Lsh1
Facets
Control facets:
• $MOTORGP_UL : On/off logic data facet
• $INTERLOCKONGP_UL :
Optional interlock condition summary facet
Supervision facet:
• $MOTORGP_CD : Optional on/off data facet
Control facets:
• $MOTORGP_UL : Logic data facet
• $DISignal_UL : Optional digital input signal
Supervision facet:
• $DINPUTGP_CD : Optional data facet
Assigned To
FBD section Pmp1 of the Control project.
Tag container of the Supervision project.
FBD section Level of the Control project.
Tag container of the Supervision project.
Generation Stage
Stage Map
The following figure shows the position of the generation stage within the system engineering life cycle.
EIO0000001114.15
Definition
The generation is an automatic process that creates a logical Participant project by using the constituents of the assigned facets and taking into account the structure of the project. At this point, the logical Participant project has no relation with the topology of the system.
35
Refinement Stage
For more information on completing the generation stage, refer to the chapter describing its
Example
During the generation process of the facets of the
that are assigned to projects, the software creates:
• For Control: The program of the Participant.
• For Supervision: populates the different database files that are used by the
Participant.
Stage Map
The following figure shows the position of the refinement stage within the system engineering life cycle.
36
Definition
Refinement is an optional process during which you can modify and/or add information to a logical Participant project that the software has created during the generation stage.
For example, you can refine a Control project to:
• Add logic between control facets of instances.
• Create new relationships with other constituents such as interlocks or control sequences.
• Add sections in languages supported by the Participant other than FBD.
To facilitate the refinement of Control projects, the software locks and identifies visually code that it has generated.
You can refine a Supervision project, for example, to:
• Assign genie facets to a Supervision page.
• Configure user privileges.
The software opens the respective Participant allowing you to use the interface and some functionalities of the embedded software.
For more information on completing the refinement stage, refer to the chapter describing its
EIO0000001114.15
Example
During the refinement of the Control project of the
you can access and modify the control logic using the embedded editors to create or modify constituents.
The following figure illustrates the refinement of the constituents generated by the
Control logic facet of the Lsh1 high-level switch sensor instance. During this refinement, a new variable is added.
Configuration Stage
Stage Map
The following figure shows the position of the configuration stage within the system engineering life cycle.
EIO0000001114.15
Definition
The configuration stage consists in defining the topology of the system, which models the hardware and software infrastructure.
You can create topological entities by using either of two methods depending on the entity that you are defining:
• In the engineering client user interface by selecting manually the templates to be used to create entities.
• In the Control Participant by using the functionality of the embedded software.
Saving the configuration in the Participant creates the corresponding folders
37
and devices in the Topology Explorer by selecting automatically the appropriate templates of the Foundation library.
For more information on completing the configuration stage, refer to the chapter describing its
Example
For the
water tank system, page 27 , during the configuration stage, you can define
the hardware that will run the program, the Ethernet control network, and the operator station from which the operator will operate the pump, monitor the pumping process, and the water level.
The following figure shows examples of topological entities of the water tank system that you can create during the configuration stage.
38
Controller
STB Island
Operator station
Ethernet network
Gateway
ATS 48
Local rack with an Ethernet based architecture.
Distributed I/Os to which level switches Lsh1, Lsl1, and Lsll1 are connected, communicating with the controller through I/O scanning.
Supervision station to control and monitor the system, configured with its network interface card and the supervision software.
Networks connecting the controller, the STB Island, the gateway, and the station node.
The gateway communication instance is created in the application of the system modeling the communication functions. The device itself is not represented in the topology.
The soft starter instances are created in the application of the system modeling the motor management functions. The device itself is not represented in the topology.
NOTE: When communication with devices is performed by using Modbus TCP explicit or implicit messaging, topological instances of devices are created also in the topology to manage TCP/IP addressing.
EIO0000001114.15
Mapping Stage
Stage Map
The following figure shows the position of the mapping stage within the system engineering life cycle.
EIO0000001114.15
Definition
The mapping stage consists in associating facets of a project to resources of the topology of the system.
You can perform three types of mappings independently for each project:
• Service mapping : Defines which engine executes the project (for example, which controller runs the program or, which station node hosts the I/O server).
• Hardware mapping : For Control projects only. Links the logical projection of the hardware defined in the application (for example, a variable representing an I/O signal of a motor) to the hardware defined in the topology (for example, an I/O channel in an I/O module of the controller).
• Communication mapping : Defines runtime communication (for example, which controller will communicate with the I/O device and through which communication module), communication between controllers (peer to peer communication), and between controllers and devices (for example, communication with STB islands or Modbus TCP Ethernet devices by using I/
O scanning).
NOTE: You can map a project to several different engines, for example:
• To a controller in the laboratory for test purposes.
• To a controller in the production plant.
For more information on completing the mapping stage, refer to the chapter describing its
Example
The table gives examples of the mappings that you can perform for the
Mapping
Control project
Service
Description
Defines to controller the program is associated for deployment and execution.
39
Build Stage
Mapping Description
Hardware If for instance Motor_Pmp1 , you select the optional Running Control service, the software creates the corresponding facet. It creates, for example, a boolean variable that indicates the state of the motor switch.
You can map this variable of the application to the channel of an input module of the STB island.
Communication
Defines the I/O scanner channels that are created for communication between the controller and the STB island.
Supervision project
Service
Communication
Defines the I/O, alarm, and trend servers that are used for the Supervision project and on which operation stations of the topology they are installed.
Defines from which controller I/O data is acquired and which communication module of this controller is used.
Stage Map
The following figure shows the position of the build stage within the system engineering life cycle.
40
Definition
The build stage consists in starting an automated process during which a
Participant merges the following information in order to create the built Participant project:
• The logical Participant project
• Mappings
• The topology
The built Participant project is the executable that you can deploy to engines of the system
The software stores the executable files resulting of this process in the contents repository.
At this point, you can view the complete Control and Supervision projects in the corresponding Participant.
Once built, a project is referred to as the built Participant project, which is the project associated to an engine for execution.
EIO0000001114.15
For more information on completing the build stage, refer to the chapter describing its
Example
During the build process of the
, Participants create the following files.
Participant Generated Files
Control The executable file, which is the binary to be deployed to the controller.
Supervision The master project file (.ctz) to be deployed to the operation server and operator stations.
Files of the included projects (.ctz) to be deployed to the operation server and operator stations.
The OFSOPC/OPC UA configuration files (.xml) to be deployed to the operation server.
Deployment Stage
Stage Map
The following figure shows the position of the deployment stage within the system engineering life cycle.
EIO0000001114.15
Definition
During the deployment stage, you transfer a built Participant project to the corresponding engine that is defined in the topology of the system.
Depending on the project, an engine can be:
• For Control:
◦ a controller
◦ a station node for emulating a simulator
• For Supervision: A station node acting as operation server or operator station.
Once deployed, a project is referred to as the deployed Participant project, which is the project that is loaded into the engine for execution.
The stage also includes the steps of redeploying an already deployed Participant project and to update a deployed Participant project with changes that you have made to the corresponding logical Participant project.
41
Execution Stage
For more information on completing the deployment stage, refer to the chapter describing its
Stage Map
The following figure shows the position of the execution stage within the system engineering life cycle.
42
Definition
The execution stage includes the steps to:
• Start and stop the execution of a deployed Participant project.
• Make online changes to a deployed Participant project.
• Update the corresponding logical Participant project with the changes that you have made online.
The execution stage takes into consideration actions that you can perform with and without stopping the controller to keep you informed of the impact of your changes.
For more information on completing the execution stage, refer to the chapter describing its
Additional runtime services are described in the Navigation Services User Guide
(see EcoStruxure ™ Process Expert, Runtime Navigation Services , User Guide ).
EIO0000001114.15
Working with the Software
What’s in This Part
Starting and Quitting System Server and Clients..............................................44
Overview
This part explains how to access and use the client user interface (UI). It describes the various functionalities of the software and provides general information to help you use them effectively.
EIO0000001114.15
43
Starting and Quitting System Server and Clients
Starting and Quitting System Server and Clients
What’s in This Chapter
Logging In and Out of System Server and Clients ............................................44
Locking and Unlocking the Software ...............................................................46
Overview
This chapter describes how to start and quit the system server and clients after a first start, and describes the client/server connection.
Logging In and Out of System Server and Clients
Overview
Any user who is a member of at least one EcoStruxure Process Expert group can log in to the system server or a client.
These groups are created automatically or must be created manually by the system/network administrator depending on the authentication type that was selected during installation. The administrator must also add users to one or more groups depending on the role of each user.
To be able to use the functionality of a given component, you must be a member of the appropriate group (for example, to use the engineering client, you must be a member of the ESX HDCS Engineer group).
NOTE: For information on how to get started with the software, refer to the topic describing the first steps to perform (see EcoStruxure ™ Process Expert,
Installation and Configuration Guide).
Authentication Domain Selection
When you log in, enter your username without domain name or any prefix.
The system server uses the authentication type setting (see EcoStruxure ™
Process Expert, Installation and Configuration Guide) to validate your credentials either locally or with the Active Directory ® domain service.
NOTE: If Domain is the configured authentication type, the domain controller must be reachable from the computer running the system server.
NOTE: If the computer that runs the client is connected to a Windows ® domain and the connection to the domain network is interrupted, users can log in locally by changing the authentication type setting to local.
For more information, refer to the topic describing role based access control
(see EcoStruxure ™ Process Expert, Installation and Configuration Guide).
Single Login and Logout
The software implements a single-login mechanism. You need to log in when you open the first software component (for example, a client). Thereafter, you are logged in automatically when you open other components on the same computer.
If several components are open on the same computer, you are logged in to all of them at once. You need to log in again only after you log out of a component on the computer.
44 EIO0000001114.15
Starting and Quitting System Server and Clients
The software also implements a single-logout mechanism. Logging out of a software component also logs you out of the other software components to which you are logged in on the same computer.
Logging In
To log in to a software component, enter your username (without domain) and password in the log-in window. The log-in process may take a moment to complete.
The window appears when you start the first component on a computer, open a second component while no user is logged in to the first component, or by clicking
Log In from the
If you close the log-in window without logging in, the component remains open.
NOTE: Logging in to a client is subject to the same log-on policies as those that are defined locally for the computer or for the domain.
Logging Out
To log out of a software component, select the Log Out command from the
To be able to log out, all operations that are in progress for components running on the computer must have completed.
Logging out of a software component:
• Does not quit the component.
◦ The system server is not stopped if it is running. Further, you cannot stop the system server when no user is logged in.
◦ For clients, if you had opened additional windows by using the Open in
New Window
, these windows are closed. Tabs are closed.
• Logs you also out of the other software components to which you are logged in on the same computer.
NOTE: You are logged out of the software on a computer when you quit the last component to which you were logged in on this computer.
Viewing Connected Clients
From any client that is connected to a system server, you can view information about the clients that are connected to this server in the Client Details tab of the about dialog box.
For a description of the dialog box, refer to the topic describing the About
EcoStruxure Process Expert
Tracing Login Attempts and Log Outs
The following actions are recorded:
• Attempts to log in to a component even if they are unsuccessful. The username that is entered is recorded.
•
Locking and unlocking, page 46
a component.
• Logging out of a component.
Actions performed in the system server console appear as notifications in the console and are recorded in the system server log files. Actions performed in a client appear in the notification panel (they also appear in the system server console when client and server are running on the same computer).
For details, refer to the topic describing the
traceability of actions, page 54
.
EIO0000001114.15
45
Starting and Quitting System Server and Clients
Locking and Unlocking the Software
Locking Software Components
To lock a software component, select the Lock command from the
Locking the server still allows clients running on other computers to connect to it or remain connected.
When components are locked, the log-in window opens on top of the main window. The username of the logged-in user shown is in the User Name field in read-only mode. Only the user who has locked the software can unlock it.
Impacts of Locking Software Components
Locking a software component has the following impacts:
• Locking any software component also locks all the other components that are open on the computer and to which you are logged in.
• Dialog boxes and notifications in the notification panel are queued and suppressed. These messages are shown once the component is unlocked.
• You cannot quit a component that is locked.
• You cannot open other EcoStruxure Process Expert components on the computer.
Unlocking Software Components
To unlock a component, enter the password in the login dialog box.
Unlocking any software component also unlocks all the other components that were locked on the computer.
To unlock the software when the domain authentication type is selected requires that the domain controller be reachable from the computer running the system server.
Starting the System Server Again
Temporary Contents Repository Files
When you start the system server, it creates folders to store
from the contents repository to speed up access to these files.
Insufficient Disk Space Notification
When you start the system server, the server console may display a notification about insufficient free disk space (see EcoStruxure ™ Process Expert, Installation and Configuration Guide).
If this notification appears, try to free some disk space.
Starting the System Server
To start the system server after you
stopped it, page 50 , proceed as follows.
Step
1
2
Action
Verify that Caché is running by checking the presence and the color of the Caché icon in the notification area. When Caché is running, its icon is blue.
If the system server console is not open, from the Windows ® Start menu, click
EcoStruxure Process Expert > System Server .
46 EIO0000001114.15
Starting and Quitting System Server and Clients
Step Action
3
4
5
Result: The log-in window opens.
Enter your username without domain or prefix, your password, and click Log In .
Result: The system server console opens.
Click Action > Start .
Result: The system server starts.
Wait until the system server console displays the following message at the bottom of the window to start engineering and operation clients (see EcoStruxure ™ Process Expert,
Installation and Configuration Guide):
Server is ready .
Client/Server Connection
Overview
Clients connect with the system server through an Ethernet cable connection, for example to:
• Access the database.
• Access software Participants.
• Launch tasks that are performed by the system server.
• Receive notifications from the system server.
• Verify digital certificates and license rights.
You cannot use clients while the connection to the system server is interrupted or while the system server is not running.
You can test the client/server connection (see EcoStruxure ™ Process Expert,
Installation and Configuration Guide).
Notifications About Client/Server Connection Interruption
The table describes the various notifications that appear client-side for different scenarios where a client cannot connect to the system server or the virtual machine anymore.
Scenario
1
2
3
4
Operation in progress at the time of the interruption
No
You launch a task while the connection to the system server is interrupted.
Yes
Client notification
No
Notification that the client is unable to connect to the system server.
Notification about an unexpected communication interruption.
Yes. An action is performed in an open software
Participant window.
Corrective action
None
Launch the task again when the connection is reestablished.
Notification that the action in the
Participant cannot be performed and indication of the possible causes.
NOTE: If you are refining a
Control project online (see
EcoStruxure ™ Process
Expert, Control Participant
Services, User Guide) and have clicked the button to build and deploy changes after the connection was interrupted, the changes
If the system server is still running, the action completes server side and the notification of clients is updated when the connection is re-established.
If the system server has stopped, an
.
If the connection to the system server is still functional, save changes, close the Participant window, and start over once the problem is fixed.
If the connection to the system server is interrupted, refer to scenario 3.
If the reason for the connection interruption cannot be determined, you need to contact Schneider Electric
.
EIO0000001114.15
47
Scenario
5
6
Starting and Quitting System Server and Clients
Operation in progress at the time of the interruption
Client notification
The system server is stopped by user intervention.
are not deployed nor saved.
Notification in the
to inform that the server is shutting down.
Corrective action
From this point on, you cannot perform any action on the client.
Restart the system server.
Contact Schneider Electric
Yes. An action is performed in an open software
Participant window.
None.
A message appears in the system server console.
NOTE: Refer also to the topic providing information to help troubleshoot client/ server communication (see EcoStruxure ™ Process Expert, Installation and
Configuration Guide).
The following figure shows an example of the notification that appears for scenario
2. The name or IP address and the port of the system server computer are indicated.
The following figure shows an example of the notification that appears for scenario
3.
The following figure shows an example of the notification that appears for scenario
4.
48 EIO0000001114.15
Starting and Quitting System Server and Clients
The following figure shows an example of the notification that appears for scenario
4 in case you are refining a Control project online.
After Re-establishing the Connection to the System Server
Clients automatically reconnect to the system server when the connection is reestablished or when the system server is running again. After reconnecting, clients display a notification to inform you of the communication interruption.
Unsaved changes are discarded and open windows are reloaded or closed automatically.
EIO0000001114.15
If the system server has stopped, the notification panel is empty when the system server restarts. To view the history of activity up to the interruption of the communication, open the
After an unexpected interruption of the client/server connection, the states of both the engineering client and the system server may have become inconsistent. This can be the case, for example, if at the time of the interruption an operation was in progress such as an import of several Participant projects or pasting of many instances.
NOTICE
LOSS OF COMMUNICATION
After an interruption of the client/server connection, verify that the last operation executed by the software was completed successfully, and if necessary, repeat the last operation.
Failure to follow these instructions can result in unresponsive clients.
You are able to resume using the software when the connection to the system server is re-established or when it is running again.
49
Starting and Quitting System Server and Clients
Restarting Clients After Closing Unexpectedly
If an engineering client closes unexpectedly (for example, because the computer on which it is running stopped working), you do not need to restart the system server. You can restart the client after 60 seconds. This is the time that is required by the system server to terminate a client session, which ended abnormally.
Restarting a client earlier may trigger messages about missing engineering client license, for example.
Quitting the Software
Overview
To quit the software, quit in the following order:
• Any clients that are connected the system server that you are stopping.
• The system server
To restart the system server, quit the software in the same order and the then
start the system server, page 46 .
You cannot quit a component if it is
NOTE: You are logged out of the software on a computer when you quit the last component to which you were logged in on this computer.
Quitting Clients
When you quit a client, it does not close if any task is still in progress.
To quit a client, proceed as follows.
Step
1
2
Action
Verify that any processes are finished executing by checking the information in the notification panel.
Click the close button of the client window.
Result: The client window closes, disconnecting it from the system server.
Stopping the System Server
When you stop the system server, tasks in progress are completed before the server is stopped. If any client is still connected to the system server, a notification is displayed, which indicates the identity of the logged-in user by using the format full name (computer name) .
You cannot use a client when the communication between the system server and the client is interrupted, for example, when the system server is restarted or not running.
NOTICE
LOSS OF COMMUNICATION
Stop the system server only when no client is running.
Failure to follow these instructions can result in unresponsive clients.
To stop the system server, proceed as follows.:
50 EIO0000001114.15
Starting and Quitting System Server and Clients
Step
1
2
3
4
Action
From the menu bar of the system server console, click Actions > Stop .
Result: A dialog box asking you to confirm the system server stop opens.
NOTE: If a client is still running, the full name of the user who is still logged in is displayed in the dialog box.
If a client is still connected, click No ; otherwise proceed to step 4.
Result: The dialog box closes without stopping the system server.
and stop the system server again by starting over this procedure.
When no more client is connected, click Yes .
Result: The system server completes tasks in progress and then stops.
NOTE: Click No to close the dialog box without stopping the system server.
EIO0000001114.15
51
Multiuser Functionality
What’s in This Chapter
Multiuser Functionality
Overview
Several clients can connect to a system server simultaneously, allowing several users to work on the same component or different components of a system at the same time.
For example, User A and User B can work on the application of the system, or
User A can work on the application and User B on the projects of the system.
These operations could also be performed by a single user.
In both cases, the software manages system-wide concurrent user access to editors and other tools to preserve the integrity of data of the system.
It may allow you to view data by granting access to certain editors in read-only mode.
When a user is finished working on a system component (for example, an instance) by closing the corresponding tool (for example, the Instance Editor ), the software allows other users to access components that manage or use data of that component.
As such, users do not need to check out or lock the component that they are working on.
Managing User Activity
At the following stages of the system engineering life cycle, the software indicates the status of objects by using icons:
•
•
At any stage, when the command that you have selected cannot be completed, you can obtain information about the reason through:
• Dialog boxes that clients display when you try to access system data that is being used or edited by another user.
• Information in the notification panel on the activity of any user that is logged in to a client of the same system server.
Virtual Machine Usage Considerations
While the type and number of activated EcoStruxure Process Expert licenses dictate how many clients can connect simultaneously to a system server, users may be restricted in the use of certain commands that require services of a virtual machine (for example, the Refine command of the Project Explorer ). Each virtual machine provides access to a limited number of instances, and each instance to a limited number of software Participant sessions.
For more information, refer to the topic describing virtual machine usage (see
EcoStruxure ™ Process Expert, Installation and Configuration Guide).
Examples
By using examples, the table illustrates some of the locking mechanisms that the software implements when two users work on the same system.
52 EIO0000001114.15
Action executed by User A
Editing properties of Instance A .
Refining the Control Participant project in the
Project Explorer .
Configuring a controller entity in the Topology
Explorer .
Examples of restrictions for User B
Cannot edit Instance A but can open the
Instance Editor in read-only mode.
Can generate the section to which facets of
Instance A are assigned but the facets of
Instance A are not generated. If the section contains other facets, they are generated.
Information is displayed in the notification panel.
Cannot refine the same Participant project or any section of it. Information is displayed in a dialog box.
Cannot generate the same Participant project.
Cannot build the same Participant project.
Cannot configure the same controller entity.
Cannot do mapping (hardware and communication) of the Control executable to which the engine is mapped.
Cannot build the Control Participant project executable to which the engine is mapped.
NOTE: The locking mechanisms apply also when a single user is performing these operations (if applicable).
EIO0000001114.15
53
Action Traceability
What’s in This Chapter
Overview
This chapter describes how to obtain information related to the activity of the system server and clients.
Notification Panel
Overview
The notification panel allows you to view and trace engineering activity. The panel is displayed automatically when you start an engineering client. You can modify its height and show column headers.
The information that is displayed is the same for each engineering client that connects to the same system server. When you open a second engineering client, you can see in its notification panel the history of actions starting from the moment the first engineering client was opened.
Certain system server and virtual machine tasks are displayed also.
An entry is logged when you launch a task and it is updated as the execution of the task progresses. When the task is complete, the status of the task and the actions that the software has executed are indicated.
For each task, a color icon allows you to see the status at a glance.
At any time, the notification The information remains available while the system server to which the client is connected is running. Closing the client or the notification panel does not delete the entries.
You can show/hide the notification panel from the engineering client
Information Availability
At any time, the notification panel can display a maximum of 2000 entries. When this limit is reached, the most recent entries replace the earliest ones on a first-in first-out basis.
The information remains displayed while the system server to which the client is connected is running. Closing the client or the notification panel does not delete the entries.
Aborting Tasks
When you select or confirm certain commands, the icon appears in the Action column of the notification panel. You can click it to cancel the task. Once the task is near completion and cannot be canceled anymore, the icon appears disabled
. Only the user who has initiated the command is allowed to abort it.
The possibility to abort and the behavior when you click the icon is described in the topics documenting the commands for which the abort functionality is
54 EIO0000001114.15
Data Description
available. For example, the Paste
of the Application
Explorer .
Aborted tasks are identified in the notification panel in the Message column with
(Aborted) . When you export data of the notification panel, it is the most recent subtask of the process that is identified with Aborted in the Action column, not the task itself.
The table describes the data that is displayed in the notification panel.
Column header (1)
–
Description
Icons indicate the status of the task:
• Task in progress (spinning).
• Task completed successfully (green).
Success (2)
Start Time
Elapsed Time
Message
Action
User Name
Station Node
System
Domain
Entity Path
Entity Type
Attribute
Old Value
New Value
•
•
Task did not complete (red).
Not successful
Task completed with notifications (yellow).
(2)
Warning (2)
• Information (blue).
Informational (2)
Date and time when the task was initiated.
The time it took to complete the task independently of its final status.
Short description of the task that was executed. The status of the task is indicated in brackets.
A task can have messages for subactions.
Expand the row by clicking the expand icon on the outer left of the row.
Keyword describing the action that was executed. Typically, this corresponds to the command you selected.
Name of the user who is logged in to the client from which the task was executed.
Format: Full name (Username)
Name of the PC on which the client from which the task was executed is installed.
Identifier of the system in which the task was executed.
When the task is not related to a system, the entry is Global .
Identification of the domain or project component on which the task was executed.
When the task is not related to a system component (for example, when a user logs in), the entry is Global .
Path the entity on which the task was executed.
Type of the entity on which the task was executed.
Identifier of the modified attribute (if applicable).
Value of the attribute before the modification was performed (if applicable).
Value of the attribute after performing and/or saving the modification (if applicable).
(1) To show column headers, right-click any row inside the notification panel and click Show Table Headers . Headers are hidden by default.
(2) Corresponding keyword in the
EIO0000001114.15
55
Using the Notification Panel
For each task that you launch, it is good practice to verify in the notification panel if the task is completed and its final status.
Select a task that has subentries and press Enter (or double-click it) to expand/ collapse it. Subentries provide more detailed information about the task.
NOTE: When performing activities on a large number of entities, expanding entries in the notification panel may increase the response time of the engineering client temporarily. Such activities can be, for example, importing or generating 500 or more objects at once.
Filtering and Sorting Activity Data
Use the
on columns to view, for example, only activity of one user by filtering on the User Name column.
By default, the most recent activity is displayed at the top of the list.
Exporting Activity Data
To save the history of actions, export activity data on a regular basis and before stopping the system server.
To export to file (.csv) activity data that is displayed in the notification panel covering a selected period, proceed as follows.
Step
1
2
3
4
Action
Right-click any row inside the notification panel and click Export .
Result: The Export dialog box opens.
In the Destination field, enter a file name and location, or use the default file name and location.
In the Period field, select a start date and time, and an end date and time to define the time span of activity data to export.
NOTE: Only activity data that appears in the notification panel can be exported.
Click OK .
Result: The software creates the export file and opens the folder that contains it.
NOTE: Click Cancel to close the Export dialog box without exporting data.
NOTE: Click Reset to reset the values of the Destination and Period fields to their default values.
NOTE: If a file with the same name exists at the specified location, the software displays a dialog box asking you for confirmation before overwriting the file.
Audit Trail
Configuring Audit Trail
You can from the Audit Trail section of the System Server Configuration
Wizard .
Working Principle
This topic describes the audit trail functionality for system-engineering activities performed by users and the data that is sent to the syslog server.
Once you have enabled and configured audit trail, when the system server is started, it connects to the syslog server and sends audit trail messages.
56 EIO0000001114.15
Messages are sent in chronological order for actions that users perform on systems by using the engineering clients of the infrastructure.
Messages for certain user actions that are performed in the system server or operation clients are also sent.
The audit trail functionality of EcoStruxure Process Expert is independent of the
Event Logging setting of the Control Participant ( Project Settings > PLC
Diagnostics ).
NOTE: Syslog server software needs to be purchased and installed separately.
Scope of the Audit Trail
Typically, audit trail messages that are sent to the syslog server correspond to a user-action entry in the notification panel of the engineering client.
For each child notification pertaining to a parent entry, one message is also sent.
Messages for the main entry and its child notifications have the same Domain value.
No message is sent for system-generated entries and when a user action is canceled.
The following tables outline the type of actions for which messages are sent to the syslog server.
Actions Performed in Engineering Clients
Actions performed at the platform level
Logging in and out of the client.
Locking and unlocking the client.
Actions on systems.
Actions on system components.
Import operations.
Deployment operations.
Actions on global templates.
Actions on content repository data.
Comment
—
—
—
—
—
For example, creating, deleting, or restoring systems.
Application, topology, projects.
—
Actions performed in a
Participant
Control Participant:
• Refinement offline of project and sections
• Controller and PRM configuration
Control Participant: Refinement online.
Comment
Participant-generated messages are sent when changes are saved. Typically, this information does not appear in the notification panel of the engineering client.
Supervision Participant:
•
•
Refinement
Advanced settings
• Page editing
Messages are sent when the Build and Deploy command is used.
A message is sent also when you perform an action that impacts the controller directly (for example, initializing an animation table) even if you close the refinement window without building and deploying changes.
The information that is available is the same as that appearing in the notification panel.
No details are provided about Participant data that is modified.
EIO0000001114.15
57
Actions Performed in Operation Clients
Actions
Logging in and out of the client.
Comment
—
Locking and unlocking the client.
—
Connecting to a controller when using runtime navigation services.
A message is sent for obtaining the controller status when opening the Operation Client Viewer.
Actions Performed in the System Server
Actions
Starting and stopping the system server.
Logging in and out of the system server.
Comment
—
—
Audit Trail Message Format
The content of the message portion (message text or details) of a message that is sent to the syslog server uses the format defined by the syslog protocol (RFC
5424 specification), which is as follows:
<Time stamp> <Machine name> <Application name> – <User> : <Domain> :
<Action> : <Entity> : <Message> : <Attribute> : <Old value> →<New value>
Element
Time stamp
Machine name
Application name
User
Domain
Action
Entity
Attribute
Message
Old value
New value
Description
Date and time when the action was performed.
Format: YYYY-MM-DDThh:mm:ss:ms
Milliseconds (ms) are indicated with 7 digits (0000000 if not available).
The time stamp is based on the system time of the computer on which the
EcoStruxure Process Expert system server is installed in UTC.
Nevertheless, Schneider Electric recommends that the system time of computers on which EcoStruxure Process Expert clients are running be synchronized to the system time of the system server computer.
NOTE: For actions performed inside the Control Participant, the time stamp corresponds to the Participant system time in UTC.
Name of the computer on which the action was performed.
EPE
Name of the user who is logged in to the EcoStruxure Process Expert component on which the action was performed.
Format: Full name (Username) . If the full name is not defined, the username appears instead.
Domain or project component on which the action was performed.
For example, Systems or Application
Description of the action that was performed.
Name of the object on which the action was performed.
Identifier of the modified attribute (if applicable).
Description of the action. Typically, the information that is available in the notification panel of the engineering client.
Value of the attribute before the action was performed.
Value of the attribute after the action was performed.
NOTE: If an element contains no value, it is not shown.
58 EIO0000001114.15
Connection to the Syslog Server
The table describes the actions of the system server when it connects to the syslog server and when the connection is interrupted.
Connection of system server to syslog server
Initial connection
Description
Connection is interrupted
A message is shown in the notification panel and sent to the syslog server to indicate the status of the connection.
In the notification panel, messages related to the connection status show Global in the System and Domain columns and
System in the User Name column.
The system server detects a disconnection when it is not able to send messages to the syslog server. In this case, it attempts to reconnect automatically up to three times. If unsuccessful, a message is shown in the notification panel.
Thereafter, the system server attempts to reconnect at the configured interval.
Connection is reestablished Two messages are shown in the notification panel and sent to the syslog server to indicate the following:
• Date and time the disconnection was interrupted.
• Date and time the connection was reestablished.
NOTE: Actions logged while the connection to the syslog server is interrupted are discarded. Notifications continue to show in the notification panel.
Activity Log Files
Overview
The software records the activity of each component (system server, engineering client, and operation client) by using log files.
In addition, the software maintains a log file that records information related to activated licenses for troubleshooting purposes.
The file size and number of files that the software maintains for each component is limited. This is done to make the log files more user-friendly to view and to save space.
NOTE: For clients, the data that is logged is different from the activity data that is displayed in the
Log File Location
Log files are located at the path C:\Users\ Username \AppData\Roaming\Schneider
Electric\Process Expert x\Logs, where x correponds to the major version of the software that is installed (the R• version suffix does not appear).
Username corresponds to the username that was entered to log on to the current session of Windows ® , independently of the username that was entered to
log in to the client, page 44 .
Log File Name Syntax
The names of log files have the following syntax: ComponentName.File number.
log
Component names are:
• Server for the system server.
• Client for engineering clients.
• OperationClient for operation clients.
EIO0000001114.15
59
• License is used for license-related information.
File numbers:
• The most recent log file has no file number.
• The second latest log file has number 0.
• The log files thereafter have incremental numbers from 1 to 9 where 9 represents the earliest log file containing the oldest information.
For example:
• Server.log
is the current log file in which the software is recording server activity.
• Client.1.log
is the log file in which the software recorded past engineering client activity. The file content is not updated anymore because Client.log
is currently recording activity.
Client.1.log
was created when Client.log
reached its size limit for the second time (the first time, Client.0.log
was created).
Log File Size
The size of any log file cannot exceed 4 Mb. When the size of a log file has reached this limit, the software creates a new file. Existing log file numbers are incremented.
Number of Log Files
The software keeps up to 10 log files per component. When the software needs to create a new log file because the current one has reached the size limit, and the number of files for a component is reached, the software deletes the earliest file for that component before creating the new one.
60 EIO0000001114.15
Software Capabilities
What’s in This Chapter
Hardware and Software Capabilities ...............................................................61
Hardware and Software Capabilities
Overview
The following describes the main hardware and software capabilities of
EcoStruxure Process Expert and additional capabilities of the embedded Control and Supervision software Participants.
For more information on the specific capabilities of the Control Participant and
Supervision Participant, refer to the
help of the respective Participants, page 69
.
Some capabilities and/or features may not be supported by the software.
Hardware Platforms
For information on the integrated and not supported hardware architectures, refer to Configuration Stage (see EcoStruxure ™ Process Expert, Control Participant
Services, User Guide).
NOTE: You can include other hardware platforms in systems engineered by using the software, however, the software will not provide any services for these platforms.
Programming Languages
The software generates the program for controllers by using the Function Block
Diagram (FBD) programming language.
The Control Participant supports additional
programming languages, page 62
for creating the user program, which can be used together in Control projects managed by EcoStruxure Process Expert.
The Supervision Participant supports a structured, proprietary programming language for monitoring and controlling plant equipment, which can be used together in Supervision projects managed by EcoStruxure Process Expert. For more information, refer to the
Supervision Participant help, page 69 .
Template Libraries
The software uses object-oriented modeling for the engineering of applications.
For this purpose, an extensive selection of Schneider Electric templates are provided in various libraries such as templates modeling signals, hardware templates modeling the system infrastructure, up to complex control module templates modeling the entire Control and Supervision functionalities of process objects.
When a library is installed, the templates are available in the Global Templates
Explorer and can be used in explorers and editors specific to the software. The encapsulated Control and Supervision constituents can be viewed in the corresponding software Participants.
For information on architectures, for which templates are available, refer to
Supported Hardware Architectures (see EcoStruxure ™ Process Expert, Control
Participant Services, User Guide).
EIO0000001114.15
61
Function and Function Block Libraries
The Control Participant includes an extensive library, which extends from blocks for simple boolean operations, through blocks for strings and array operations to blocks for controlling complex control loops.
For a better overview, the different blocks are arranged in libraries, which are then broken down into families.
The blocks can be used in the Control Participant in the programming languages
FBD, LD, IL, and ST and be added to Control projects managed by EcoStruxure
Process Expert.
Controller Program
In the software, the controller program is organized in:
• A Master task (MAST)
• A FAST task
• FBD sections, which are assigned to one of the defined tasks
By using the Control Participant, you can add to the controller program:
• Sections, which are assigned to one of the defined tasks
• AUX tasks (depending on the platform)
• Sections, which are assigned to AUX tasks
• Sections for processing time controlled events (Timerx)
• Sections for processing hardware controlled events (EVTx)
• Subroutine sections (SR)
The program components that are supported by the Control Participant, can be added to Control projects managed by the software. However, not all of them can be viewed in the software outside of the Control Participant (for example, non-FBD sections).
Performance Scope
The table shows the main characteristics of the software and its Participants.
Programming languages
Function Block Diagram (FBD)
Ladder Diagram (LD)
Instruction List (IL)
Structured Text (ST)
Sequential Function Chart (SFC)
Ladder Logic 984 (LL984)
Cicode
Schneider Electric Global Templates libraries
Foundation library
–
–
+
+ General Purpose and segment libraries
Function block libraries (1)
Standard library
Control library
Communication library
–
–
–
–
–
+
–
–
EcoStruxure
Process
Expert
+
+
+
+
+
+
–
–
–
+
+
+
Control
Participant
–
–
–
–
–
–
+
–
–
–
–
–
Supervision
Participant
62 EIO0000001114.15
Diagnostics library
I/O Management library
System library
Obsolete library
Memory card file management library
General information
Project browser/explorer
Template explorer
Instance editor
Create and modify object templates
Access control
Simulator
Context-sensitive and PDF help
Control
Encapsulate DFB constituents in templates
Create and use data structures (DDTs)
Create and use derived function blocks (DFBs)
HMI operator screens
Supervision
Encapsulate tags and genies in templates
Design pages, genies, face plates
Use tags and alarms
Clusters
Server and client events
I/O devices
I/O, alarm, trend, and report servers
Redundancy
Load balancing (operation servers)
+
+
–
+
+
+
–
+
+
+
+
+
+
+
-
+
+
+
–
–
–
–
–
–
EcoStruxure
Process
Expert
–
+
+
+
+
+
Control
Participant
–
–
–
–
–
–
–
–
–
+
–
–
–
+
+
+
–
+
+
+
+
+
+
+
+
–
+
+
+
+
–
–
–
+
–
+
–
+
–
–
–
–
–
–
–
Supervision
Participant
+ Available
(1) Availability of the function blocks depends on the hardware platform.
- Not available
Supported Data Types
Data Type Conversion
The software may use data types that are different from the types used by the
Control Participant (see EcoStruxure ™ Process Expert, Control Participant
Services, User Guide).
The conversion to Participant-supported types is done automatically.
EIO0000001114.15
63
Standard Data Types
The software uses the following data types.
Data Type
DateTime
Date
Time
Duration
String
Boolean
Float
Double
Decimal
Byte
Short
Integer
Long
UnsignedByte
UnsignedShort
UnsignedInt
UnsignedLong
Description
A specific instance in time
(1) .
A Gregorian calendar date
(1) .
An instant of time that recurs every day (1) .
hh:mm:ss.ms
A duration of time as specified by Gregorian day, hour, minute, second, and millisecond components (1) .
D.hh:mm:ss.ms
Example: 1.05:10:30.245
If the value contains no day or ms component, they are not shown as 0 values. For example: 11:20:30 is displayed to represent 0 days, 11 hours, 20 min., 30 sec., and 0 ms.
A sequence of unicode characters.
A binary logic value.
Represented by using the
32-bit single-precision IEEE
754 format (1) .
7-digit precision.
Represented by using the
64-bit double-precision
IEEE 754 format (1) .
15 to 16-digit precision.
A fixed-point decimal value with arbitrary precision (1) .
A maximum of 4 digits are allowed after the decimal separator.
8-bit signed integer.
16-bit signed integer.
32-bit signed integer.
64-bit signed integer.
8-bit unsigned integer.
16-bit unsigned integer.
32-bit unsigned integer.
32-bit unsigned integer.
Lower Limit
19-01-01 00:00:00.000
1900-01-01
00:00:00.000
0
1 character of the standard
ASCII table.
False
From approximately -3.4 x
10 38 to -1.5 x 10 -45
From approximately -1.7 x
10 308
-128 to -5.0 x 10
0.0001
-32768
-2,147,483,648
-324
-9223372036854770000
0
0
0
0
(1) Microsoft ® Windows ® Regional Options may apply to the format of the type.
Upper Limit
2100-12-31 23:59:59.999
2100-12-31
23:59:59.999
9,223,372,036,854,775,807 in ticks
NOTE: 1 tick = 100 ns
From approximately 5.0 x 10 -324 to 1.7 x 10 308
922337203685477.5807
127
32767
2,147,483,647
9,223,372,036,854,774,807
255
65,535
4,294,967,295
18446744073709551615
Size
8 bytes
8 bytes
8 bytes
8 bytes n characters of the standard
ASCII table.
True
From approximately 1.5 x 10 -45 to
3.4 x 10 38
1 character =
1 byte
1 byte
4 bytes
8 bytes
12 bytes
1 byte
2 bytes
4 bytes
8 bytes
1 byte
2 bytes
4 bytes
4 bytes
64 EIO0000001114.15
User-Defined Data Types
Data Type
Enum
Variant
Description
An enumeration value is stored as String.
Any data type.
Lower Limit
–
–
Upper Limit
–
–
Size
–
–
Naming Rules
Overview
When you change default parameters such as identifiers or Supervision element properties, EcoStruxure Process Expert validates at different stages of the system engineering life cycle if they satisfy the naming rules that are described in this topic.
These rules can apply at the platform level and/or can be Participant-specific.
NOTE: Other Participant specific rules may apply; however the software does not validate them. For more information, refer to the respective
.
Folder Identifiers
Folder identifiers:
• Can start only with a letter or the $ character.
• Can contain only letters, digits, underscores, the $ character, and spaces (1) .
These rules apply to the following types of folders:
• System folders
• Application folders
• Global Templates folders
• Content containers of the content repository.
Instance Identifiers
Instance identifiers can contain only letters, digits, and underscores.
The maximum character length is set through the Validation property (see
EcoStruxure ™ Process Expert, Global Templates, Reference Manual) of the
$InstanceID parameter of the template that the instance uses.
NOTE: Participants do not accept the use of certain reserved words for object names (for example, DO for the Supervision Participant). While the software allows using these reserved words as identifiers of instances in the application, doing so may prevent the corresponding Participant project from generating successfully when the reserved word is used as name of
Participant project items (for example,
Topological Entity, Device and Folder Identifiers
Topological entity, device, and folder identifiers:
• Can start only with a letter.
• Can contain spaces (1) .
• Cannot contain any special character other than underscore (_).
• Cannot exceed 32 characters in length.
EIO0000001114.15
65
Control and Supervision Participant Project Identifiers
Identifiers of Control and Supervision Participant Projects, and of their components:
• Can start only with a letter.
• Can contain spaces (1) .
• Cannot contain any special character other than underscore (_).
• Cannot exceed 32 characters in length.
Variable Names and Section Identifiers
Names of variables and identifiers of sections that are managed by the Control
Participant, must satisfy the following rules:
• Maximum length: Refer to the maximum length of identifiers as specified under Implementation-Dependent Parameters in the IEC 61131-3 standard
( Appendices of the Languages Reference manual in the Control Participant help).
• Permitted characters: Refer to naming conventions in the glossary of the
Control Participant help, Operating Modes .
Refer to the topic describing
data validation before generating, page 298
.
Supervision Cluster Identifiers
Identifiers of Supervision clusters cannot exceed 16 characters in length.
Supervision Page Identifiers
Identifiers of pages must satisfy the following rules:
• Maximum length: 64 characters
• Can contain spaces (1) .
• Cannot contain these characters: \ / : * ? " < > |
(1) The software automatically removes leading and trailing spaces.
Supervision Field Lengths
For variable tags:
Rule
Maximum field length
Field
Item Name
Address
Raw Zero Scale
Raw Full Scale
Eng Zero Scale
Eng Full Scale
Eng Units
Format
Comment
Deadband
DataType
For trend tags:
8
11
254
11
16
Value
79
254
11
66 EIO0000001114.15
Rule
Maximum field length
Field
Item Name
Expression
Trigger
Format
File Name
No. Files
Comment
Period
Storage Method
Type
Eng Units
For advanced alarm tags:
Rule
Maximum field length
Field
Custom1...
to Custom8...
Paging Group
For digital alarm tags:
Rule
Maximum field length
Field
Comment
Custom1...
to Custom8...
Paging Group
Value
64
80
Value
254
64
80
For reports (and facets assigned to ServerEvents containers):
Rule
Maximum field length
Field
Report Name
Output Device
Report Format File
Comment
Area
Action
Trigger
Time
Period
48
16
16
254
32
32
Value
79
16
253
For events (and facets assigned to ClientEvents containers):
Rule
Maximum field length
Field
Name
Trigger
Event (Action)
Comment
Time
Period
48
32
32
Value
16
254
64
Value
79
254
11
11
253
4
254
32
64
32
8
EIO0000001114.15
67
Supervision Fields Special Characters
The table describes the rules that the software validates during generation with regard to the contents of the following field.
Field
Name
Rule
Tag names need to have the following syntax:
[<alpha> | ’_’] *[<alpha> | <digit> | ’\’ | ’_’]
• Tag names need to begin with either an alpha character (A-Z or a-z) or the underscore.
• Any following characters need to be either of:
◦ alpha characters (A-Z or a-z)
◦ digits
◦ \
◦ _ (underscore)
◦ | (vertical bar)
If you use any other character, the compile process cannot complete successfully.
NOTE: Tag names can only begin with a digit only if the [General]
TagStartDigit parameter of the citect.ini file is set to 1 (the default value is 0).
68 EIO0000001114.15
Using the Help
What’s in This Chapter
Using Help for Different Versions of Schneider Electric Templates.....................69
Help on User-Created Templates....................................................................71
Software Participant Help
Overview
You can open the HTML help of a Participant by clicking Help or the ?
button in the menu of the Participant when the Participant window is open (for example, after you click Configure in the context menu of a topological entity).
You can open the same help also from the Help EcoStruxure Process Expert dialog box without having to open the Participant. To access the dialog box, click the ?
button in the toolbar of a client.
Help is available for these Participants:
• The Control Participant
• The Advantys Configuration Software (ACS)
• The Supervision Participant
NOTE: ACS is used to configure STB islands during the configuration stage.
For simplicity, in this manual ACS is assimilated to the Control Participant.
NOTE: The dialog box lets you also open:
• The help describing how to use the Modicon IEC 61850 Configuration
Tool.
• The help of OPC Factory Server.
• The help of OPC UA Server Expert.
Opening the Help of a Participant
To open the help of a Participant from a client window, proceed as follows.
Step
1
2
Action
In the
of the client window, click the help button ( ?
).
Result: The Help EcoStruxure Process Expert dialog box opens.
In the Software Participant Help section, double-click a Participant name.
Result: The HTML help of the Participant opens in a separate window.
Using Help for Different Versions of Schneider Electric Templates
Overview
For the templates that are included with the software, each software version contains only one version of each template (the latest) and installs the help only for this version. This overwrites the help of an existing previous version if you are upgrading the software. The help is provided in compiled HTML (CHM) format.
However, your application can contain several versions of a same template, for example, if you have migrated your database and have imported a later version of the template afterwards.
EIO0000001114.15
69
Starting from V4.3 of the software (Process Expert), you have the possibility to retain the help that is included with any version of the software to continue using it after you upgrade to a later version.
By verifying the version of a template when you use the context-sensitive help button, the software opens the help for this version if available.
This topic provides recommendation when using several versions of the help and describes how to proceed.
NOTE: For more information on how to obtain help on templates, refer to the topic describing how to .
Considerations When Using Several Versions of the Help
The help of a given version of the software documents the templates and functionalities provided by this version only.
If you open the help for a given template and then, within the same help window, you look up another template or a platform functionality, it may be that the version of the template or the functionality that is documented differs from the version/ functionality that you are using.
This can be the case, for example, if:
• You have migrated your database and have not updated the template used by instances of the Application. In this case, the help that is provided may document a later version of templates.
• You are opening the help of an earlier version of the software. In this case, the templates that are available in the library and the functionalities provided by the platform may be of a later version than those documented.
Schneider Electric recommends the following:
• Open the help for a template only by using the context-sensitive help button, which takes into consideration the version of the template that you are selecting.
• Do not view the help for another template or platform functionality within the help window that you had opened for a template.
• Verify the version of the help you are viewing and which is indicated in the title of the help window.
Location of the HTML Help Files
On the computer running the engineering client, the help files are located in the
User Guides folder at the path C:\Program Files\Schneider Electric\EcoStruxure
\Process Expert.
The User Guides folder also contains ContextualHelpRepository.* files, which are required for the context-sensitive help on templates to work.
Preserving the Current Help Files Before Upgrading the Software
So that the help of the installed version of the software remains available after you upgrade to a later version, before proceeding with the upgrade, you need to copy the complete set of help files and their auxiliary files to a specific location on the computer running the engineering client.
Proceed as follows.
70 EIO0000001114.15
Step
1
2
3
Action
Create the following folder structure if it does not exist yet: %localappdata%\Schneider
Electric\Process Expert\User Guides.
NOTE: By default, the value of the %localappdata% environment variable is C:
\Users\ username \AppData\Local.
A Process Expert x folder, where x corresponds to the installed major version (the
R• version suffix does not appear), may already exist in the Schneider Electric folder but do not use it.
In the User Guides folder, create a subfolder with a name containing the number of the current version. For example, Template Help Files Vx .
Mentioning the version helps you identify for which version of the software you are opening the help in case the same template version is provided and documented in different versions of the software.
Copy all the files contained in the
to the subfolder that you have created in step 2.
Opening the Help for Templates of an Earlier Version
To open the help of a template for which several versions exist, proceed as follows.
Step
1
Action
Click the context-sensitive help button in the
of the engineering client and select a template, an instance of a template, or a facet of an instance of a template.
Result: The software verifies the version of the template and opens:
• The help of the current version from the default location if the template is provided in the current version of the software.
• The help of the earlier version of the software in which the template was provided
(given you have copied the necessary help files to the
).
Only one help window opens at a time.
NOTE:
• If the version of the template was provided with a version of the software for which the help is not present on the computer, not at the required location, or incomplete, no help is shown.
• If the version of the template was provided in both the current and the earlier version of the software, the Contextual Help Conflict dialog box opens, which lets you select which version of the help you want to open.
Help on User-Created Templates
Overview
You can configure the software to open the help in CHM format of a user-created template.
You can also manage the HTML help files of several versions of the same template so that clicking a given version of the template opens the corresponding help.
Only one help window opens at a time.
This topic describes the prerequisites and the steps you need to perform. It does not describe how to create HTML help files in CHM format.
NOTE: By using this feature, you can also associate your own HTML help to a
Schneider Electric global template in addition to the existing help. You can then select which one you want to open.
EIO0000001114.15
71
NOTE: You can also associate help files to templates and their instances that operators can open from the operation client when using runtime navigation services (see EcoStruxure ™ Process Expert, Runtime Navigation Services ,
User Guide ).
Prerequisites
The following are the prerequisites to be able to open help for user-created templates:
• You need to have help files documenting user-created templates in the
Microsoft ® compiled HTML format (.chm).
For more information on creating a help project, refer to the Windows ® online help .
• You need to know the
of the topic documenting the template, which you want to open when you use the context-sensitive help button of the engineering client. If the help file (.chm) documents several templates, you need to have the topic ID that corresponds to each template.
For more information on topics, refer to the Windows ® online help .
Creating a Repository for Help Files of User-Created Templates
So that the help of user-created templates remains on the computer and can be opened after you upgrade the software to a later version, you need to copy your complete set of help files and the ContextualHelpRepository.xml file to a specific location on the computer running the engineering client.
Proceed as follows.
Step
1
2
3
Action
Browse to %localappdata%\Schneider Electric\Process Expert\User Guides.
NOTE: By default, the value of the %localappdata% environment variable is C:
\Users\{username}\AppData\Local.
In the User Guides folder, create a copy of the folder named Sample-Tobecopied in the same location and rename it by using a meaningful name describing its contents and the version of the software that was used to create the template. For example,
<MyReactor Template Help Files for V2020>.
NOTE: You can create as many copies of this folder as needed in case you want to keep the help files of different templates in distinct folders.
Copy all your help files to the subfolder that you have created in step 2.
NOTE: Uninstalling the software removes the folder named Sample-
Tobecopied but not the copies of it.
Identifying the ID of a Topic Inside a CHM Help File
The procedure describes how to identify the ID of a topic inside a CHM help file.
Step
1
2
Action
Open the user-created HTML help,
Select the topic (page) that you want to open when using the context-sensitive help button on the template and right-click somewhere on the page.
Result: The context menu of the page opens.
72 EIO0000001114.15
Step
3
4
Action
Select Properties .
Result: The Properties dialog box opens.
Copy the topic ID.
The topic ID of the page is the part of the string that starts after ::/ in the Address
(URL) attribute.
For example, if the Address (URL) attribute is mk:@MSITStore:C:\PROGRA~2
\XMLNOT~1\Help.chm::/Overview.htm
, the topic ID is Overview.htm
.
Editing the XML File
To edit the ContextualHelpRepository.xml file, proceed as follows.
Step
1
2
3
4
Action
In the
to which you have copied your help files, open the
ContextualHelpRepository.xml file by using Notepad or an XML editor software.
Result: The file that opens contains the following entry, which serves as an example only.
<ContextualHelp Version="1.0">
<Item HelpKey="MyMotor3" FileName="PELbPrTp" MappingId="PELbPrTp_D-SE-
0014236.htm" FileType="CHM" Description="" Version="2.7.2"/>
</ContextualHelp>
Edit the following parameters of the entry:
• HelpKey : Is the identifier of the user-created template.
• FileName : Is the name of the CHM file without file extension.
• MappingId : Is the
of the topic in the CHM file that documents the usercreated template. Include the .htm
file extension.
• FileType : Do not edit this parameter. Default value: CHM.
• Description : Optional. You can enter a short description by using free form text. It is used to describe the entry in the XML file and can appear in the Contextual
Help Conflict
. To use no description, leave it as "".
• Version : Is the version of the user-created template as it appears in the Global
Templates Explorer or in the Templates Browser pane of the Application
Explorer .
Add a new entry for each user-created template for which you want help to open.
To manage the help for different versions of the same template, refer to the
NOTE: The </ContextualHelp> element must be the last entry in the file.
Save your changes.
Updating the Help for a New Version of a User-Created Template
The table describes the actions that you need to perform when you create a new version of a template and want help to open for the various versions that exist.
Two versions of a template are used as an example.
MyReactor 1.0.0
is considered the previous version and MyReactor 1.0.1
the new version.
EIO0000001114.15
73
An updated help file is available to document the new version
No
Action
Yes
1. In the
to which you have copied your help files, edit the ContextualHelpRepository.xml file.
2. Add a new entry that corresponds to the new version of the template by using the same parameter values as for the previous version; except for Version , which needs to correspond to the version of the new template.
1. Browse to the
located at the path % localappdata%\...
2. Create a copy of the folder in which the help files of MyReactor
1.0.0
and the ContextualHelpRepository.xml file are located.
3. Rename the copy of the folder by using a name that allows you to distinguish the previous and the new version.
For example, <MyReactor 1.0.1 Template Help Files for V2018>.
4. In this folder, edit the entry in the ContextualHelpRepository.xml by modifying the value of Version to be equal to the new version (for example, Version="1.0.1" .
Comment
The same help file opens when you use the context-sensitive help button on MyReactor
1.0.0
or MyReactor 1.0.1
.
If you remove the entry for template version
1.0.0, help cannot open when you select it.
Clicking either template version when context-sensitive help is enabled opens the help file that is located in the folder, which also contains the XML file with an entry of the same template identifier and version.
NOTE: It is assumed that the help file name and the topic ID are identical for both template versions.
Opening the Help for User-Created Templates
To open the help of a user-created template, proceed as follows.
Step
1
Action
Click the context-sensitive help button in the
of the engineering client and select the user-created template.
Result: The software verifies the version of the template and opens the corresponding help file according to your
NOTE:
• If the value of any parameter in the ContextualHelpRepository.xml file is incorrect (except for description), if the ContextualHelpRepository.xml file is missing or its location incorrect, or if the location of the folder containing the help files and the XML file is incorrect, no help is shown.
• If the template identifier and version appear in more than one
ContextualHelpRepository.xml file contained in different subfolders of the
User Guides folder, the Contextual Help Conflict dialog box opens, which lets you select from which location you want to open the help.
Associating Other HTML Help Files to Schneider Electric Global Templates
By using an example, this topic describes how to associate your own help file in
CHM format to a sample control module template of a Global Templates library for which the EcoStruxure Process Expert help is already available.
The data used for the example is the following:
• Control module template: $Motor version 1.0.0.
• Name of your help file: MyMotorHelp.chm
• ID of the topic that you want to open: mymotor_description.htm
The table describes the steps that you need to perform to implement the help and select, which file to open.
Step
1
2
Action
Create a
repository for your help, page 72
and copy the MyMotorHelp.chm file to this folder.
Edit the ContextualHelpRepository.xml
located in this folder and add the following entry before the </ContextualHelp> element.
<Item HelpKey="$Motor" FileName="MyMotorHelp" MappingId="mymotor_description.
htm" FileType="CHM" Description="" Version="1.0.0"/>
74 EIO0000001114.15
Step
3
4
Action
Click the context-sensitive help button in the
of the engineering client and select the $Motor template version 1.0.0, and instance, or facet of it.
Result: The Contextual Help Conflict dialog box opens and shows the two help files that are associated to the template: The EcoStruxure Process Expert help and your help.
Select the help file that you want to view and click OK .
EIO0000001114.15
75
User Interface
What’s in This Chapter
Engineering Client User Interface Description..................................................76
Engineering Client and Explorer Work Areas ...................................................79
Overview
This chapter describes the engineering client user interface, its main components, and the common tools that allow you to engineer and navigate a system.
Engineering Client User Interface Description
Overview
When you start the engineering client, it opens one main work area in which the various explorers and editors are displayed.
The engineering client user interface is composed of five main elements:
• The client toolbar
• The tabs bar of the main work area
• Explorer windows
• The Notification Panel
You can
divide the main work area, page 83
of the engineering client.
The explorer that opens when a client is started depends on the group (see
EcoStruxure ™ Process Expert, Installation and Configuration Guide) that the logged-in user is a member of.
76 EIO0000001114.15
User Interface Description
The following figure shows an example of the engineering client user interface.
4
5
2
3
Item
1
Description
Engineering client toolbar
Tabs bar showing the tabs of the explorers and editors that are open
Systems Explorer window
Workspace of the Systems Explorer
Notification Panel
Engineering Client Toolbar Description
The following figure describes the toolbar of the engineering client.
EIO0000001114.15
Item
1
2
Description
Opens the Systems Explorer
window, page 105 , which lets you create, organize, and
navigate systems.
From the Systems Explorer you can open the explorers that are needed to create and manage system components:
• Application Explorer
• Project Explorer
• Topology Explorer
Explorer navigation buttons to open or show the explorer of a system.
From left to right:
• Topology Explorer
• Application Explorer
• Project Explorer
Clicking a button opens the corresponding explorer for either:
• The system that is selected in the Systems Explorer when this explorer is active.
77
5
6
7
3
4
10
11
Item
8
9
Description
• The system for which an explorer or editor is active. For example, if the
Assignment Editor for System_1 is active, clicking the first button opens/shows the Topology Explorer for System_1 .
If the explorer is already open, it is shown.
NOTE: Navigation does not work from the Global Templates Explorer nor the
Contents Repository by using these buttons.
Opens the
Content Repository explorer, page 703
, which contains files related to Global
Templates and the systems that you are engineering.
Opens the
Global Templates Explorer, page 645 , which you can use to browse and
manage templates of the Global Templates library.
NOTE: In this example, the button is shown unavailable because the role of the
does not have the permission to use this explorer.
Opens the
.
Opens the About EcoStruxure Process Expert
.
Opens a dialog box, which lets you access:
• The global software HTML help. It describes how to install, license, and use the software as well as the Global Templates that are included with it.
• The global help of each
.
• Other help files.
Double-click an entry to open the corresponding help.
Opens the HTML help at the topic describing the system engineering life cycle and the system creation workflow.
It gives you an overview of the various stages of the life cycle and helps you identify what is the next step that you need to complete.
Opens context-sensitive HTML help.
Clicking the button enables context-sensitive help and a question mark appears next to the cursor.
Selecting an item opens the help when available. If no help is available for the selected item, the functionality is disabled.
To disable the functionality while the question mark is shown next to the cursor, press
Esc .
For an overview of UI items for which context-sensitive help is available, refer to the topic describing how to open context-sensitive help.
Full name of the logged-in user and name of the computer running the system server to which the client is connected. If the full name is not defined, the username appears instead.
Opens the User menu, which contains the following commands.
Lock
User
Information
Log In /
Log Out
the components to which you are logged in on the local computer.
Opens the User Information dialog box (see EcoStruxure ™ Process
Expert, Installation and Configuration Guide).
Lets you
of the software.
About Dialog Box
Opening the About Dialog Box
To open the dialog box, click:
• The icon in the
toolbar of the engineering or operation client, page 77
.
• Help > About in the menu bar of the system server.
78 EIO0000001114.15
General Tab
The General tab displays information related to:
• Installed EcoStruxure Process Expert and third-party software versions.
• The activated application size license and the total instance count for your database.
• The installation and expiration dates of entity certificates (see EcoStruxure ™
Process Expert, Installation and Configuration Guide) installed on the local computer and of the corresponding root CA.
If no entity certificate is installed, no information is shown.
System Details Tab
The System Details tab displays the
instance count by system, page 133
for the mounted database.
Client Details Tab
The Client Details tab displays information about the clients that are currently connected to the system server with a user being logged in. It shows the computer name, user name, and the type of client.
Support Tab
Contains the contact information of the Schneider Electric support.
The Logs Folder link lets you access the
.
Hotfix Details Tab
The Hotfix Details tab displays information about installed hotfixes.
If no hotfix is installed, the tab is hidden.
Engineering Client and Explorer Work Areas
Overview
By default, in an engineering client only one work area is visible at a time.
The work area is the display area that is below the
where explorers and certain editors open, such as the Systems Explorer and
Composite Editor .
Certain explorers (for example, the Application Explorer or Project Explorer ) also feature a work area in which various windows and editors open, such as
Properties windows or the Instance Editor .
You can
create additional work areas, page 83
and organize them.
NOTE: When no window opens in the work area, it is called a workspace . This applies to editors and certain explorers (for example, the Global Templates
Explorer ).
EIO0000001114.15
79
The following figure shows an example of the work area of the Application
Explorer .
2
3
Item
1
4
5
Description
Tab of the Application Explorer .
Toolbar of the explorer.
Panes of the explorer, which are open in the work area.
Remaining work area of the explorer in which a window and an editor are open. You can select them by using their tab.
Workspace of the editor.
Tabs Bar Description
For each window, explorer, or editor that you open in a work area, a tab is displayed in the tabs bar, which features:
• An icon representing the type of window, explorer, or editor (for example,
Properties window, Application Explorer , or Links Editor ).
• The identifier of the system that is displayed in the corresponding window
(except for the Contents Repository , Global Templates , and Systems
Explorer ).
• A button to close it.
You can rearrange the order of tabs on the tabs bar by dragging them to a new position.
NOTE:
• Closing the last tab in a tabs bar closes the work area (except if the work area is the last one to be open).
• You cannot close the last tab of the last work area that is open.
• To close all windows except one, right-click the tab of the window that you want to leave open and select Close Other Tabs .
80 EIO0000001114.15
The following example describes the tabs bars of the engineering client in which two work areas are open.
4
5
8
9
Item
1
2
3
6
7
Description
Main work area.
Additional work area.
Display all Tabs button.
Displays a list of the tabs that are open in this work area.
Inactive tab.
Maximize/Restore Down button.
The button is available when
more than one work area, page 82
is open. It maximizes the work area in the window or reverts the display to a multiple work area view.
NOTE: When you maximize a work area, the other open work areas are hidden.
Use the Restore Down button to show them again.
Button to close the work area.
The button is available when
more than one work area, page 82
is open. It allows you to close the other work areas.
You cannot close the main work area.
NOTE: Closing the last tab in a work area closes it.
Scroll left button.
Click the button to view hidden tabs that are to the left of the first tab. The scroll increment is one tab.
Active tab.
Scroll right button.
Click the button to view hidden tabs that are to the right of the last tab. The scroll increment is one tab.
Moving the Workspace (Panning)
In editors (for example, the Links Editor ), click an empty area of the workspace and hold down the left mouse button. The pointer turns into a hand icon. You can now drag the workspace in any direction by moving the pointer. This is useful to view items that are outside the visible workspace.
In certain explorers (for example, the Global Templates Explorer ), you can use the following methods to move the workspace.
Action
Mouse wheel up
Mouse wheel down
Shift + Mouse wheel down
Shift + Mouse wheel up
Direction in which the workspace is moved
Down
Up
Left
Right
EIO0000001114.15
81
Magnifying and Reducing the Workspace View
To magnify or reduce the workspace view gradually, use the following method.
Ctrl + Mouse wheel up
Ctrl + Mouse wheel down
Zoom in.
The position of the pointer becomes the center of the magnification.
Zoom out.
The position of the pointer becomes the center of the reduction.
NOTE:
• A zoom selection menu may be available at the bottom of some workspaces. You may also be able to use the radar view.
• In some workspaces, starting out from the default zoom level, you can only zoom in.
• Zooming out beyond a certain level may switch the display to
.
Selecting Multiple Items
The method to select multiple items varies depending on the editor or explorer you are working in:
• In editors (for example, template editors), you can select multiple items in the workspace by using either or a combination of the following methods:
◦ Select an item with the pointer, press and hold Ctrl , and select other items.
◦ Press and hold Ctrl , click the workspace, and hold down the mouse button. Then, drag the pointer to draw a rectangle. Items that overlap with the rectangle are selected when you release the mouse button. Last, release Ctrl .
• In explorers, browsers, and various containers, you can select multiple items by selecting an item with the pointer, pressing and holding Ctrl , and selecting other items. To select contiguous items, select the first one, press and hold
Shift and select the last item. Release Shift .
To unselect an item, press Ctrl and click the item.
NOTE: While you are still holding Ctrl , click a selected item again to unselect it.
Organizing Work Areas
Overview
To work more effectively, you can customize the client UI by
creating additional work areas, page 83
left, right, or below the main one. Inside each work area you can open various explorers and editors.
Each work area has its own
and toolbar (if available).
NOTE: You can also
divide the work area of explorers, page 84
.
82 EIO0000001114.15
The following figure shows an example of an engineering client UI that is divided into three work areas.
Viewing Client Windows on Separate Monitors
To open a new window for the same client, so that you can view it on a separate monitor, proceed as follows.
Step
1
2
3
Action
Verify that, at least, two windows are open in the same or separate work areas.
For example, the Systems Explorer and the Project Explorer windows.
Right-click the tab of a window in the tabs bar and select Open in new Window .
Result: The tab opens in a second, separate client window.
Drag any of the two client windows to the other monitor.
NOTE:
• You can repeat the procedure from any tab of either client window given that two tabs are open in the work area. (The functionality is not available for tabs that are open inside the Application Explorer or Project
Explorer .)
• Notifications about actions that you perform in the additional client windows appear in the Notification Panel of the main client window.
Creating Additional Work Areas
You can create a new work area with an already open explorer by using the docking tabs. The new work area opens on the left, right, or at the bottom of the existing one depending on which docking tab you use.
Once you have created several work areas, you can:
• Drag tabs from one work area to the other.
• Reposition work areas by using the docking tabs.
Refer to the topic describing the
for information on how to manage windows inside a work area.
EIO0000001114.15
83
The following figure illustrates the use of the external docking tabs to create a new work area.
Example of result when you use the bottom docking menu.
To open a new work area, proceed as follows.
Step
1
2
3
Action
Verify that at least two explorers are open in the work area.
Drag a tab from the tabs bar towards the side of the work area where you want to create the new one.
Result: The explorer follows the pointer and the external docking tabs appear.
Keep dragging the pointer over the docking tab where you want the new work area to open and release the mouse button.
Result: A new work area, which contains the explorer opens at the selected location.
NOTE: To cancel the operation, drag the pointer away from the docking tab and release the mouse button.
Creating Additional Work Areas in Explorers
When several windows are open in the work area of the Application Explorer or
Project Explorer , you can create additional work areas by dragging either of the windows to a docking tab.
Refer to the topic describing the
for information on how to manage windows inside work areas.
NOTE: You cannot create a new work area with the pane of an explorer. Refer to the topic describing how to
84 EIO0000001114.15
The following figure illustrates the use of the external docking tabs to create a new work area inside the Application Explorer .
The following figure shows an example of the Application Explorer with two work areas that are open.
To open a new work area, proceed as follows.
Step
1
2
3
Action
Verify that at least two windows or editors are open in the work area of the explorer.
Drag a tab towards the side of the work area where you want to create the new one.
Result: The item follows the pointer and the external docking tabs appear.
Keep dragging the pointer over the docking tab where you want the work area to open and release the mouse button.
Result: A new work area, which contains the window opens at the selected location.
NOTE: To cancel the operation, drag the pointer away from the docking tab and release the mouse button.
Working with Panes
Overview
The software displays panes in various explorers and editors.
You can minimize them automatically when you do not need to see them, resize, and move them as required.
EIO0000001114.15
85
Pane Description
The following figure shows a partial view of two panes in the Application
Explorer .
The following figure shows a floating pane. The pin button is not available.
2
3
Item
1
4
Description
Pane that is pinned and always visible.
Pane that is minimized to a tab.
Extract/retract button. Turns it into a floating pane that you can dock or returns a pane to its previous position (docked or tabbed).
Pin button. Lets you show and hide the pane.
Minimizing, Showing, and Restoring Panes
To minimize, show, and restore a docked or tabbed pane, proceed as follows.
86 EIO0000001114.15
Step
1
2
3
Action
Click the pin button in the title bar of the pane.
Result: The pin button is displayed in a horizontal position and the pane will be minimized to the edge of the screen as a tab.
Move the pointer over the tab.
Result: The pane is shown entirely while the pointer is inside the pane.
NOTE: Click inside the pane so that it remains visible even you move the pointer away from it. Click outside the pane to minimize it again as a tab.
Click the pin button again.
Result: The pin button is displayed in a vertical position and the pane is restored. If there are several overlapping panes, it may be shown only partially.
Extracting Panes
Docking Panes
To make a pane floating, click the extract button or drag it by the title bar.
When panes are docked on top of each other so that their tabs appear at the bottom, dragging either pane by its title bar extracts the complete group. To extract only one pane, drag it by its tab or use its extract button.
You can move docked panes to another area of the workspace or dock floating panes by using the
external docking tabs, page 83 .
When the workspace contains more than one pane and you drag one pane on top of the other, a docking menu appears in the center of the other pane. It lets you position panes in a relative position to each other.
The following figure shows the docking menu.
Item
1
2
Description
The up, right, down, and left arrows let you position the pane on top, to the right, below, or to the left of the other one respectively.
The center pad positions the pane on top of the other one as a tabbed pane. The center pad appears when you move the pointer over the square docking menu but outside one of the arrows.
EIO0000001114.15
87
88
The following figure illustrates the use of the docking menu or external docking tabs to reposition a pane (docked) inside the work area of an explorer.
To dock a pane, proceed as follows.
Step
1
2
Action
Drag the pane by its title bar.
If the pane is already docked,
first.
Result: The docking menu and/or the
external docking tabs, page 83
appear.
Keep dragging the pointer over the docking menu or tab where you want the pane to be positioned and release the mouse button.
Result: The pane is docked.
The following figure shows an example of panes that have been tabbed by using the center pad of the docking menu.
The following figure shows an example of a pane that has been docked below another one by using the down arrow of the center pad of the docking menu.
EIO0000001114.15
The following figure shows an example of a pane that has been docked to the bottom edge of the engineering client window by using the bottom external docking tab.
Resizing Panes
Typically, panes do not feature a maximize button. Instead, resize them to occupy the entire work area.
To resize a pane, proceed as follows.
Step
1
2
Action
Move the pointer over an edge of the pane.
Result: The pointer turns into a double-ended arrow.
Drag the pointer away from the edge.
Result: The pane is resized.
Closing Panes
To close a pane, click the close button in the title bar of the pane (when available).
To open it again, select the corresponding command from the menu of the explorer or editor.
If no close button is available or if it does not allow closing the pane,
to a tab.
Using Menus
Context Menus
For many items of the UI (for example, folders, instances, elements of projects), right-clicking the item opens a context menu containing several commands.
The commands are described in the topic documenting the item.
EIO0000001114.15
89
The figure shows an example of the context menu that opens when you right-click a system in the Systems Explorer , which lets you perform actions on the system.
Item
1
2
Description
You can execute commands that appear in bold also by pressing Enter when the item is selected or double-clicking the item itself (in this example, the item is System_1 ).
For certain commands, you can also use the
that is indicated to the right of the command when the item is selected.
NOTE: To close a context menu, press Esc .
Software Participant Windows
Floating Software Participant Windows
When you open a Participant window, it opens as a floating window and maximized.
You can resize this window, display it on another monitor, or embed it in the client window.
You can open several floating windows simultaneously.
90 EIO0000001114.15
The following figure shows an example of a floating Control Participant window.
The window is shown restored down.
EIO0000001114.15
1 Open the HTML help of EcoStruxure Process Expert
2 Embed the floating Participant window in the client
3
Copy to the local Clipboard, page 92
4 Paste from the local Clipboard
5 Save changes that were made in the Participant
6 Minimize the floating window
7 Maximize the floating window (or restore down the floating window when it is maximized)
8 Close the floating Participant window
NOTE: The other buttons of the Participant window toolbar are task-specific and are described in the topic documenting the task.
While the floating Participant window is open:
• The embedded Participant window is not refreshed and displays the view that was shown when you extracted the floating Participant window.
• You cannot work in the embedded Participant window nor close it.
• Use the icon in the taskbar to display the client user interface when the floating Participant window is maximized.
• The Windows ® snap feature is enabled.
91
Embedded Software Participant Windows
The following figure shows an example of a Control Participant window, which is embedded in the engineering client by using the restore button.
1 Close the Participant window
2 Extract and maximize the Participant window
3 Save changes that were made in the Participant
Showing Software Participant Windows on Separate Monitors
To show a software Participant window on another monitor,
and drag it to the other monitor.
If you experience issues viewing the extracted Participant window on an extended monitor (for example, if the window turns black), try disabling hardware acceleration for Windows ® Presentation Foundation (WPF). The required setting may already be present in the registry and you can modify it; otherwise, you need to add it.
To disable hardware acceleration for WPF, proceed as follows. Follow this procedure only if you are experiencing issues viewing an extracted Participant window on an extended monitor.
Step
1
2
3
4
5
Action
By using the Windows ® Registry Editor of the computer on which the client is installed, go to HKEY_CURRENT_USER > SOFTWARE > Microsoft > Avalon.Graphics
Add a new registry key by right-clicking the Name column and selecting New
DWORD (32-bit) Value .
>
NOTE: If the DisableHWAcceleration registry key is already present, proceed to step 4 if necessary.
Enter DisableHWAcceleration as name.
Right-click DisableHWAcceleration , select Modify , and enter 1 as data value.
Restart the computer.
Copy-Paste Functionality
You may not be able to copy-paste data elements (for example, strings or graphic elements in a Supervision page) between the local computer and a software
92 EIO0000001114.15
Participant by using the Ctrl + C and Ctrl + V keyboard shortcuts or the Copy and
Paste commands of contextual menus.
To do so, use the two
that are located in the toolbar of the software Participant window, which allow you to perform the following actions:
• Copy to local Clipboard button: Copies strings or graphic elements that are selected in the software Participant to the Clipboard of the local computer.
• Paste from local Clipboard button: Pastes strings or graphic elements that you have copied on the local computer to the software Participant.
NOTE: To copy and paste strings or graphic elements between two instances of the same software Participant (for example, two Refine windows of the
Control Participant) or between two different software Participants (for example, the Control and the Supervision Participant), you can use the Ctrl + C and Ctrl + V keyboard shortcuts.
To copy a data element on the local computer and paste it to the software
Participant, proceed as follows.
Step
1
2
Action
On the local computer, select the data element and copy it to the Clipboard ( Ctrl + C or
Copy ).
In the software Participant, position the cursor or pointer at the desired location and click the paste button.
To copy a data element in the software Participant and paste it to the local computer, proceed as follows.
Step
1
2
Action
In the software Participant, select the data element and click the copy button.
On the local computer, position the cursor or pointer at the desired location and paste the data element ( Ctrl + V or Paste ).
Filtering and Sorting Data
Overview
For most columns inside folders and panes, you can open a filter menu that lets you refine data that is displayed according to criteria and/or conditions that you define.
In addition, you can sort data in ascending or descending alphanumerical order.
Filters and sorting are reset when you close the pane, window, or editor in which they appear.
NOTE: When a filter is active, commands that you execute at a parent node level may also execute on data that is not displayed. This can be the case, for example, when you execute a command at the folder level in the Application
Explorer while a filter is applied on the Identifier column of the folder and, as a result, not all the instances contained in the folder are displayed.
EIO0000001114.15
93
Filter Menu Description
The following figure shows an example of the filter menu.
94
Item
1
2
3
4
5
6
Description
Column filter icon.
Click the icon to open the filter menu.
The icon turns dark to indicate that you have applied a filter on the column.
Data field.
The field displays in a flat list one of each of all the entries that the column contains.
That is, if an entry appears more than once in the column, it is displayed only once in the data field. If the column contains only partial data because, for example, a keyword search has been performed, the data field displays also only the partial data.
Select one or more entries. Only entries that you select will be displayed when you apply the filter.
NOTE: If the column contains a tree view (for example, the Templates Browser pane of the Application Explorer ), the content of the data field depends on the type of lowest-level child elements shown in the column:
• A single type of child elements (for example, only templates): The data field displays only child elements that are not part of the tree structure (for example, only templates but no folders).
• Several types of child elements (for example, the Name column of the Import window in the Projects Explorer for a Control project, which contains services and sections as lowest-level child elements): The data field displays only the parent nodes (for example, the system root folder).
Expression builder.
Lets you build custom filter expressions by selecting one or two conditions and an operator from a list.
The conditions apply to any data contained in the column even if it is not shown in the data field. The list of available conditions varies and is adapted to the data type of the column.
NOTE: If you build an expression and select an entry in the data field, your selection is used as an additional condition in the expression with the AND operator. If you select several entries in the data field, each one is treated as OR condition before the result is used as an additional condition.
Match case button.
Click the button to enable case-sensitive filtering as an additional condition.
The button appears only for columns showing data of String type.
Click the button to apply the filter to the column.
NOTE: When the filtered data is modified (for example, new objects have been created or imported, objects have been renamed), the filters do not apply to the modified data. To apply them, open the filter menu again and click Filter .
Click the button to clear the filter for the column.
NOTE: To clear filters for all columns, right-click any column header and select
Clear Filters .
EIO0000001114.15
Example
The following figure shows a filter example consisting of two items selected in the data field and one expression. It is used to filter the contents of the Identifier column.
The resulting filter expression is:
( Motor_1 OR Motor_2 ) AND Identifier contains 2.
The following figure shows the search result once the filter is applied; instances for which the expression is true.
Using Filters
Sorting Data
EIO0000001114.15
To use filters, proceed as follows.
Step
1
2
3
4
Action
Click the filter icon of the row that contains the data that you want to filter.
Result: The filter menu opens.
Select entries in the data field or create a filter using the expression builder.
Click Filter .
Result: The column displays data that matches the criteria and the filter icon turns dark.
NOTE: When columns contain tree views, the parent structure of filtered items is shown.
Close the filter menu.
NOTE: You can use filters for several columns simultaneously. Repeat the above procedure on each column.
The sorting feature is represented by a green triangle inside the column header.
Click a column header to enable sorting of the data that the column contains.
Clicking the column header repeatedly toggles between the following states:
• Arrow up: Sorts in ascending alphanumerical order.
95
• Arrow down: Sorts in descending alphanumerical order.
• No arrow: No sorting. Data is displayed by using the default display order defined for the column.
NOTE:
• Hold Shift to enable sorting of multiple columns.
• To clear sorting on all columns, right-click any column header and select
Clear Sorting .
• If a rule has been defined to display contents of a column, enabling the sorting feature does not override this rule. For example, in the
Application Browser of the Application Explorer folders are shown first, followed by instances. Applying sorting sorts only items within their respective category. It does not change the display order of categories.
Clearing All Filters and Sorting
To clear filters and sorting for all columns, right-click any column header and select Clear All .
Keyboard Shortcuts
Available Keyboard Shortcuts
You can use the following keyboard shortcuts in place of the command in the context menu or the button.
Corresponding command or button Keyboard shortcut
Alt + A
Alt + P
Alt + T
Ctrl + A
Ctrl + C
Ctrl + F
Ctrl + L
Ctrl + V
Del
F2
F4
F12
Shift + F12
Opens or shows the Application Explorer for the system.
Opens or shows the Project Explorer for the system.
Opens or shows the Topology Explorer for the system.
No corresponding command.
Use this keyboard shortcut to select the entire contents of a folder or container, such as instances or facets.
Copy
Find (Global Templates)
Places the cursor in the search field of the Global Templates Explorer.
Edit Links .
Opens the Links Editor of the Application Explorer .
Paste
Delete
Rename
Settings (Global Templates)
Read-only (Global Templates)
Edit (Global Templates)
96 EIO0000001114.15
Engineering a System
What’s in This Part
Engineering M580 Safety Systems ............................................................... 577
Overview
This part describes how to complete the different stages of the system engineering life cycle to engineer a system.
The following figure shows the stages of the system engineering life cycle.
EIO0000001114.15
97
Quick Reference Guides
What’s in This Chapter
System Creation Workflow
Navigation
This page shows the various stages of the system engineering life cycle and which Explorer is used to complete them.
• Click an Explorer to view the main tasks of the workflow.
• Click a stage for detailed information on how to complete it.
NOTE: In the HTML help, use the Back button in the toolbar of the help window to revert to this page.
System Engineering Life Cycle
Application Explorer Project Explorer Topology Explorer
Instantiation
↓
Project Definition
↓
======================================
↓
Assignment
Configuration
↓
↓
↓
Generation
↓
↓
↓
Refinement
↓ ↓
======================================
↓
Mapping
↓
Build → Deployment
↓
Execution
NOTE: Specific transversal workflows are also provided describing how to
implement communication, page 597 .
System Creation Workflow
The following workflow shows the main tasks that you need to perform to complete the system engineering life cycle. Click a task to navigate to the topic describing how to complete it.
98 EIO0000001114.15
Systems Explorer
Create system
↓
Application Explorer
↓
Create application folder structure
↓
Configure folder properties
↓
Browse templates
↓
Create instances
(process/device/communication)
↓
Configure instances
↓
Link instances
↓
Topology Explorer
For Control (simulation)
Configure NIC properties
↓
Create ControlExpert service
↓
Create topology folder structure (optional)
↓
Create a controller entity
↓
Configure the controller (Participant)
↓
Configure controller properties
↓
Configure station node entities
I
↓
I
I
I
I
↓
Create device entities
I
↓
For Supervision
Configure NIC properties
↓
Create Supervision and/or OFS service
EIO0000001114.15
99
MODBUS TCP/EtherNet/IP device entity
Select template
↓
Configure device properties
I
I
I
↓
↓
I
I
PROFIBUS remote master
(PRM) entity
Create PRM entity
↓
Configure PRM properties
↓
Configure the PRM
(Participant)
I
↓
Create an Ethernet network
↓
Create physical connections
↓
I
I
I
I
I
Project Explorer
↓
Control
Create project
↓
Create sections in task folders
↓
Assign facets to sections
↓
Generate project or sections
↓
Refine project or sections (Participant)
↓
Create executable
↓
Perform service mapping
↓
Perform communication mapping
↓
Perform hardware mapping
↓
Build project
↓
View the built project
Distributed I/O entity
Create STB island entity
↓
Configure the STB island
(Participant)
↓
Configure STB island properties
Supervision
Create project
↓
Assign facets to project container
↓
Create Supervision pages
↓
Edit pages / assign genies (Participant)
↓
Generate project
↓
Refine the project (Participant)
↓
Create executable
↓
Perform service mapping
↓
Perform communication mapping
↓
Build project
↓
Deploy the project
(from the executable)
↓
100 EIO0000001114.15
Topology Explorer
↓
Control
(deployment and execution)
Supervision
(deployment from the station node)
Start the simulator (if applicable)
↓
Select the project and executable
↓
Select the IP address
↓
↓
↓
Select the project and executable
↓
Select the IP address
↓
Deploy the built project Deploy the built project
(deploy changes after first iteration)
↓
Refine online
↓
Update Control project
↓
Supervision software running on the station node)
↓
↓
Start over the life cycle from any point
↓
(Execution is performed by using
NOTE: Specific transversal workflows are also provided describing how to
implement communication, page 597
.
Task Quick Reference
Overview
The tables in this topic provide an overview of the main tasks that you can perform by using the software at each stage of the
system engineering life cycle, page 26
and where to find information explaining how to complete the task.
Stages are grouped by explorer.
Systems Explorer Task Quick Reference
Task
(and configuring runtime navigation service (RTNS) parameters)
Creating system backups, page 108
Application Explorer Task Quick Reference
System Engineering
Life Cycle Stage
Task
Browsing instances and folders, page 121
EIO0000001114.15
101
System Engineering
Life Cycle Stage
Task
Configuring instances, page 139
(and associating documents and URLs to instances for use with RTNS)
Viewing facet assignment, page 294
(copy/paste, move, update/replace templates)
Exporting and importing application objects, page 168
Project Explorer Task Quick Reference
System Engineering
Life Cycle Stage
Project Definition stage, page 199
Control Projects Supervision Projects
and
M580 safety projects, page 577
Managing projects and project sections, page 206
(order, export, import, manage data backup files)
Creating project components, page 229
(export, import)
(automatic and manual)
Creating containers (automatic and manual)
Viewing the application structure in projects, page 287
Managing assigned facets, page 292
(view assignments, unassign, move, change order)
Generating for the first time, page 300
–
Generating equipment names, page 329
Generating after changes, page 323
(auto-assign and generate, regenerate)
Managing generated facets, page 332
(unassign, reassign, unlink, move)
Managing versions of types, page 305
–
(viewing the application structure, viewing code generated by facets, managing device DDTs, creating LL984 segments)
Checking consistency, page 347
Creating network variables, page 350
Editing Supervision pages, page 361
Editing advanced project settings, adding included projects, attaching user files, page 362
Creating Control executables, page 421
Mapping communication, page 424
Mapping network variables, page 435
Creating executables, page 457
Mapping communication, page 460
(and connecting
Modbus devices to Supervision)
Exporting/Importing hardware mappings, page 449
(also, generate and build)
(also, generate and build)
Downloading project files, page 478
Viewing the built Participant project, page 469
Refer to the Topology Explorer task quick reference.
Deploying built projects, page 520
and
(to all the station nodes that are service mapped to the project executable)
102 EIO0000001114.15
Topology Explorer Task Quick Reference
System Engineering Life Cycle
Stage
Control Projects
Supervision Projects
Configuring controllers, page 371
and
M580 safety controllers, page 577
Configuring station nodes, page 379
(for Supervision/simulation)
Configuring Modbus TCP and EtherNet/IP devices, page 391
Configuring PROFIBUS PRM Masters and Decentralized Peripherals, page 388
Configuring STB Islands, page 384
Configuring Ethernet networks, page 397
Connecting to Ethernet networks, page 399
Managing the Topology, page 406
(export, import, update templates)
Managing communication, page 597
(Modbus TCP Ethernet implicit (I/O scanning, peer to peer communication)/explicit, EtherNet/IP explicit, Modbus serial)
Using the emulated simulator, page 484
Deploying built projects, page 520
and
(to specific station nodes)
Managing controller passwords for deployment and execution operations, page 488
Deploying built projects, page 481
Re-deploying projects, page 501
Deploying project changes, page 509
(and undoing online changes)
Deploying controller data, page 505
Starting/stopping controllers, page 536
Synchronizing redundant controllers, page 541
(and importing generated changes, viewing the application structure)
Updating Control projects, page 567
Backing up controller data, page 554
Refer to Executing the Deployed Supervision
Project (see EcoStruxure ™ Process Expert,
Supervision Participant Services, User Guide)
Global Templates Explorer Task Quick Reference
System Engineering Life Cycle
Stage
Tasks
Managing Global Templates, page 675
(save, copy, export/import, purge)
Updating, duplicating, and replacing Global Templates, page 688
Content Repository Task Quick Reference
Tasks
Creating content containers (see EcoStruxure ™ Process Expert, Runtime Navigation Services ,
User Guide ) (and editing, copying, moving, exporting and importing them to set up runtime navigation services (RTNS))
EIO0000001114.15
103
Virtual Machine and Participant Task Quick Reference
Tasks
Configuring virtual machines (see EcoStruxure ™ Process Expert, Installation and Configuration
Guide) (sharing a folder of the local computer, keyboards, disabling the use of the virtual machine on the local computer)
Installing extensions in Participants (see EcoStruxure ™ Process Expert, Installation and
Configuration Guide) (DTMs, GSD and EDS files, hotfixes)
Opening the help of a Participant, page 69
, OPC Factory Server, and OPC UA Server Expert
104 EIO0000001114.15
Managing Systems
What’s in This Chapter
Overview
This chapter describes how to manage systems by using the Systems Explorer .
Creating a system is prerequisite to starting the system engineering life cycle.
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
Organizing Systems
Overview
Systems that you create are stored in the database of the system server.
You can access a system from any client that is connected to the server of this infrastructure.
Accessing the Systems Explorer
To access the Systems Explorer , click the Systems icon in the
Systems Explorer Window
The following figure shows the Systems Explorer window.
EIO0000001114.15
1 Systems Explorer root folder
2 System folder
3 Systems
105
Creating System Folders
To organize systems, you can create system folders, which can contain one or more systems.
To create a system folder, proceed as follows.
Step
1
2
Action
Right-click the Systems Explorer root folder and select Create Folder .
Result: The software creates a system folder with the default name in edit mode, and displays it in the tree view.
NOTE: To create a subfolder, repeat step 1 at the system folder level.
To change the name, type it; otherwise click outside the folder to accept the default name.
System Folder Actions
Right-click the root folder or any system folder to open a context menu with the following commands.
When you select...
Create Folder
The software...
creates a system folder or subfolder.
Create System creates a system.
Delete
Rename
Restore deletes the folder.
The command is not available from the root folder.
NOTE: The command is not available if the folder is not empty.
allows you to enter a new folder name.
The command is not available from the root folder.
NOTE: You can also click the folder twice to edit its name.
opens the Restore window, which allows you to select a system backup file (.
sbf) to
in the database.
Creating Systems
Creating a System
To create a system, proceed as follows.
Step
1
2
Action
Right-click the Systems Explorer root folder or a system folder and select Create
System .
Result: The software creates a new system with the default identifier in edit mode, and displays in the tree view.
To change the identifier, type the new one; otherwise click outside the system to accept the default name.
System Actions
Right-click a system to open a context menu with the following commands.
106 EIO0000001114.15
Command
Open
Application (1)
Open
Topology (1)
Open Projects
(1)
Delete
Rename
Back Up
Description
Opens the Application Explorer , which allows you to start the
or access the application of an existing system.
Opens the Topological Explorer , which allows you to start the
or access the topology of an existing system.
Opens the Projects Explorer , which allows you to start the
Project Definition stage, page 199
or access the Control and Supervision projects of an existing system.
Deletes the system including all of its contents.
The command is inactive if either an application, topology, or project window of the system is still open.
Allows you to enter a new system identifier.
NOTE: You can also click the system slowly twice to edit its identifier
Opens the Back Up
, which allows you to create a backup file of the system.
Settings Opens the Settings
, which lets you view and configure various system-related settings.
Properties Opens the
window of the system.
(1) You can also use the
located in the toolbar of the engineering client.
System Settings Window
The Settings window opens when you select the Settings command in the context menu of a system.
Section
Document
Viewers
Description
Lets you enter the command line that the software executes for a given document type. The command is executed when you open, in the operation client, the document that is associated to an instance by using the HyperLink
System Properties
To open the Properties window of the system, right-click the system and select
Properties .
You can view and/or edit the following items.
Item
Identifier
Description
Market
Customer
Site
Description
The identifier must be unique on the system server.
Default value: System_n where n is an incremental number starting at 1.
Optional.
You can enter a description of the system with free form text. The description you enter appears in a tooltip when you move the pointer over the system.
Default value: Blank
Optional.
You can enter a description of the market that the system pertains to with free form text.
Default value: Blank
Optional.
You can enter a description of the customer that the system pertains to with free form text.
Default value: Blank
Optional.
EIO0000001114.15
107
Item Description
You can enter a description of the site that the system pertains to with free form text.
Default value: Blank
Logged-in user who has created the system.
Created By
Creation Date
Time
Modified By
Date and time of the system creation.
Logged-in user who has modified the system properties.
Date and time of the last modification to the system properties.
Modification
Date Time
Change
Description
Optional
Security
Services By
Default
Optional.
You can enter a description of the changes to the system with free form text.
Default value: Blank
The setting has an impact on the default value of the Controller and Simulator password property of
and
station nodes acting as simulator, page 381
that you create in the system:
• Enabled : Sets their property to Enabled by default.
• Disabled : Sets their property to Disabled by default.
Default value: Enabled
NOTE: Modifying the setting does not change the value of the password property of existing station nodes and controllers of the system.
NOTE: This setting does not impact the Safety password property of
M580 safety controllers, page 588
.
Creating System Backups
Overview
You can create a backup file (.sbf) of any system that exists in the Systems
Explorer . This allows you to do the following:
• Save your engineering work on demand so that your data is preserved, for example, in case of a disk problem on the PC on which the system server is installed (refer to the topic describing the contents of a system backup for details).
• Restore your work to an earlier point in time.
• Deliver a system to a site.
You cannot create a backup of a system if a component of the system is open in an engineering or operation client (for example, if the Application Explorer is open or if data of the system is accessed by using runtime navigation services).
Also, while you back up a system, no user can access it from an engineering or operation client.
You can start a new backup while another system is being backed up. You can do this from the same or separate engineering clients.
Version Compatibility
Backup files are version dependent. You cannot use them to restore systems in a different version of the software.
When you back up a system, the version of the software is automatically recorded and is displayed when you restore the system.
NOTE: Backup files are forward compatible with subsequent releases within the same year ( R• versions) and service packs of a same version of the software only if the Participant version is unchanged.
108 EIO0000001114.15
System Backup File Contents
A system backup file contains:
• The definition of all topological and application instances used in a system.
• Participant project and executable files with the related mapping information.
•
Controller data backup files, page 224
.
• Supervision
added by users.
•
added to Supervision projects.
• OPC Factory Server and OPC UA Server Expert
•
Password protection properties, page 373
for topological entities and their value.
•
that you have created in the User Contents folder structure of the system.
It does not contain:
• The templates that are used by the instances of the application.
• The default Supervision included project.
•
Password information, page 488 .
NOTE: To be able to
restore a backup file, page 110 , the items listed above
must be present in the database of the system infrastructure where you want to restore it. For example, typically, templates that you have modified or created are not present in the database of a newly installed or different
EcoStruxure Process Expert infrastructure.
System Backup File Name
A system backup consists of a file with the default name <system identifier> <
(time stamp)>.sbf where time stamp is the date and time when the backup file was created, displayed by using the format YYYYMMDDHHMMSS. Time is indicated by using the 24-hour format.
For example, System_1 (20160625144852).
You can edit the file name when creating the backup.
Aborting System Back Up Tasks
After clicking Save in the Back Up window, the abort icon is displayed in the
. Click the icon to cancel the task. The backup file is not created.
Only the user who has selected the command is allowed to abort it.
NOTE: If you are backing up a small system, the task may complete before you are able to click the icon.
Creating a System Backup File
To create a system backup, proceed as follows.
Step
1
2
3
Action
Right-click the a system in the Systems Explorer and select Back Up .
Result: The Back up window opens.
If you want to create the back up in a different location and/or with a different file name, click the browser button; otherwise, proceed to step 6.
Result: A Save As dialog box opens.
Select a location where to create the back up file and edit the file name if needed.
EIO0000001114.15
109
Step
4
5
6
7
Action
Enter a description (optional).
NOTE: The description appears when you restore the system by using the back up file.
Click Save .
Result: The Save As dialog box closes and the full path to the file is displayed in the
Back up window.
Click Save .
Result: The software creates a backup file of the system and displays information in the notification panel.
NOTE: To cancel the backup task, click the abort icon in the notification panel.
from the root folder of the Global Templates explorer because they are not included in the system backup file but required to restore it.
Restoring Systems
Overview
You can restore a system from a system backup file that you had created by using the Back Up command. This requires that templates that are used by the instances of the application are present in the database of the EcoStruxure
Process Expert infrastructure.
You cannot overwrite an existing system that has the same identifier or merge system data. If a system with the same identifier already exists, the system is restored with a new identifier.
You cannot start a restore task while another system is being restored within the same infrastructure.
Version Compatibility
Backup files are version dependent. You cannot restore system back up files created with another version of the software. The version that was used to create the backup file is displayed when you try to restore a system.
NOTE: Backup files are forward compatible with subsequent releases within the same year ( R• versions) and service packs of a same version of the software only if the Participant version is unchanged. For example, you can restore a backup file created with version 2018 in version 2018 R2. In such case, a dialog box informs you of the version shift and the software makes the restored systems compatible with the installed version.
Detection of Missing Data Before System Restoration
When you restore a system, if the software detects that an item (for example, a template)
is missing in the database, page 109
, it opens the Restore dialog box.
Missing items are reported in the Status column of this dialog box.
To be able to restore the system, first, you need to add the missing item to the database where you want to restore it.
If an include project is missing, you can add it to the content repository by following the steps describing how to add a project file (see EcoStruxure ™
Process Expert, Global Templates Reference Manual). Start from an existing
Supervision genie facet template or create a new one from the Toolbox of the
Global Templates Explorer .
110 EIO0000001114.15
Password Management After Restoring a System
After you restore a system that contains a controller and/or a station node acting as simulator for which
has been enabled, you need to do the following to be able to deploy a Control Participant project:
• If no password was set before creating the backup file, you need to set one.
• If a password had been set before creating the backup file, you need to enter this password when prompted.
For more information, refer to the topic describing how to manage
Control Participant projects, page 488
.
Aborting System Restoration
After clicking Restore in the Restore window, the abort icon is displayed in the
. Click the icon to cancel the task. The system is not restored.
Only the user who has selected the command is allowed to abort it.
NOTE: If you are restoring a small system, the task may complete before you are able to click the icon.
Restoring a System
When you restore a system, its name in the database may be different from the name it had when you created the backup. If this occurs and you had already deployed Supervision projects contained in this system when you created the backup file, the system name that was used as reference by runtime navigation services now refers to a different system. As a result, runtime navigation services may not work or display data of another system.
NOTICE
NAVIGATION TO WRONG SYSTEM
Redeploy Supervision Participant projects after restoring a system.
Failure to follow these instructions can display information of an unexpected system.
NOTE: For details on the possible name change, refer to the topic describing the impact of restoration on system names in the
.
To restore a system from a backup file, proceed as follows.
Step
1
2
3
Action
Right-click the system root folder or any system folder in the Systems Explorer and select Restore .
Result: The Restore window opens.
Browse to the system backup file (.sbf) and click Open .
Result: A confirmation dialog box opens.
Review the information that is displayed and click Restore .
Result: The system is restored. If a system with the same identifier already exists, a dialog box opens, which indicates the new identifier that will be used to restore the system.
NOTE: Click Cancel to close the confirmation dialog box without restoring the system.
EIO0000001114.15
111
Step
4
5
Action
Click OK .
Result: The system is restored.
NOTE: To cancel the restore operation, click the abort icon in the notification panel.
If the system that you have restored contains Supervision Participant projects that you had deployed before creating the backup, redeploy each one of them.
Impact of Restoration on System Names in the Database
Each system that you create has an identifier in the Systems Explorer and also a name in the database, which may be different from the system identifier. Names of systems in the database are assigned by the software incrementally and used in the background by software services for system identification purposes, for example, by runtime navigation services provided by the operation client. The name in the database does not change when you rename a system in the
Systems Explorer .
When you restore a system in the same or another EcoStruxure Process Expert infrastructure, if the name that was originally assigned to it is already used, the system is restored with same identifier in the Systems Explorer but with the next available name in the database.
The following example illustrates the scenario where the name of a system in the database changes after restoring it.
The figure shows two systems that exist in the Systems Explorer and their respective name in the database folder.
112
NOTE: The path to the database folder is C:\ProgramData\Schneider Electric
\Process Expert x\Db, where x corresponds to the installled major version (the
R• version suffix does not appear).
EIO0000001114.15
MySystem is backed up and deleted from the Systems Explorer . Its name in the database is also removed and becomes available for assignment to a new system.
Then, a new system ( System_2 ) is created. The software assigns it the next available name in the database. In this case, it corresponds to the name that was originally assigned to MySystem .
Later, MySystem is restored. The software assigns it the next available name in the database ( System_3 ), which is different from the name it originally had.
EIO0000001114.15
As a result, in this example, the name of MySystem in the database:
• Was System_2 before restoration.
113
• Is System_3 after restoration.
114 EIO0000001114.15
Instantiation Stage
What’s in This Chapter
Linking Instances by Using the Asset Workspace Editor ................................. 146
Managing Application Folders and Instances................................................. 155
Exporting and Importing Application Objects to CSV and XML Formats ........... 168
Overview
This chapter provides information to help you model the entire application of the system according to the process and instrumentation diagram (PID).
The following figure shows the position of the instantiation stage within the system engineering life cycle.
Refer to the
for a description of the purpose of this stage.
Instantiating Templates
Overview
This section describes how to use the Application Explorer to:
• Create a folder structure representing the process hierarchy of the application.
• Create and configure instances by instantiating application templates to model the functional components of the application.
• Link instances to each other to propagate data.
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
EIO0000001114.15
115
Organizing the System Application
Before Starting
Before creating the folder structure for your system application, define the appropriate segmentation, hierarchy, and naming convention for your process.
The Application Explorer lets you use templates of the Global Templates library to create instances that model typical components and functions of the application of a system. For example:
• Process objects: Represent the functions of process hardware, for example, motors and valves. This includes signals from the field and/or variables.
For example, the $Motor template can model the functions of the electrical motor of a pump.
• Device objects: Provide functions required to communicate with, control, and/ or diagnose a range of electrical devices and instrumentation that are connected to field buses.
For example, the $TesysTEM template can model the functions of a TeSys T variable speed drive communicating through Modbus TCP explicit messaging.
• Communication objects: Provide functions to manage communication with device objects connected to field buses.
For example, the $EMPortQ template can model the management of communication through the port of a Quantum controller through Modbus
TCP explicit messaging.
Refer to
Browsing Application Templates , page 119
for additional information on templates that you can instantiate.
Creating an Equipment Hierarchy
When you create instances and folders in the Application Explorer , you create a structure, which is defined by:
• The identifier and location of the application folders.
• The identifier and location of the instances.
By default, this structure is used in the Supervision project to create an
, which allows you to view alarms in the Supervision page in a structure identical to the folder structure of the application.
Therefore,
changes to the structure, page 156
of the application are
reflected on the facets, page 282
of the impacted instances once these facets are assigned to a Supervision project and generated.
Viewing the Application Structure in Control Projects
You can view the folder structure of the application also in relation to Control
Participant project
once you have instantiated templates and assigned facets to the Control project.
The functionality is available also when you
refine a Control project, page 339
and
.
Application Explorer
Overview
The
of the Application Explorer features:
• The Templates Browser pane, which lets you search installed libraries and find the application templates that you need to create the instances of your application.
116 EIO0000001114.15
• The Application Browser pane, which lets you view, search, sort, and filter folders and instances of your application. You can also perform other tasks on folders and instances by using this pane.
• The Asset Workspace pane, which lets you create asset workspaces. These are structural elements that let you group instances in order to create links between them.
• In the form of tabs:
◦ The properties of folders.
◦ The Instance Editor , which lets you view and edit properties of instances.
◦ The Asset Workspace Editor , which lets you view, create, and manage links between instances.
Opening the Application Explorer
To open the Application Explorer , double-click the system in the Systems
Explorer .
NOTE: You can also open the Application Explorer in the following ways:
• Drag the system from the Systems Explorer tree view to the
or to a
.
• Right-click the system in the Systems Explorer and select Open
Application .
• Select the system and click the Open Application Explorer button in the
.
Application Explorer Window
The following figure shows an example of the Application Explorer window.
EIO0000001114.15
6
7
8
4
5
2
3
Item
1
Description
Templates Browser
Application Browser
System root folder
Asset Workspace
of the Application Explorer . It is empty by default.
Properties of a folder
Instance Editor tab
Asset Workspace Editor tab
117
Item
9
10
Description
for folders and instances
Button to open the folder Settings
Searching Instances and Folders by Using the Application
Explorer Search Field
The search field of the Application Explorer lets you find instances and folders in the Application Browser by typing the entire or part of their identifier. You do not need to use wildcards. The search is not case-sensitive. Results are displayed as you type in a pane with columns. Your last three matching search keywords are stored and appear in a keyword menu. The stored keyword entries are systemindependent and persist even after the system server is restarted.
For example, to returns instances and folders that contain to in their identifier, such as instance Motor_1 , and folder Reactor .
By default, results are displayed in ascending alphabetical order with folders shown first, instances next.
The results pane provides basic
information on instances, page 130
and remains open until you close it by clicking the close button. A tooltip provides additional information.
The following figure shows an example of the search results that are displayed when you enter mo in the search field.
118
Right-click a search result in the results pane to open a context menu with the following commands.
Command
Navigate
Edit
Description
• For an instance: Expands the containing folder and highlights the instance.
• For a folder: Expands the folder structure and selects the folder.
You can also double-click the item.
If the item is open in a window in a work area, the corresponding tab is also selected.
NOTE: If the instance is hidden because a filter is applied in the
Application Browser , the instance is not shown and a dialog box opens to inform you.
• For an instance: Opens the Instance Editor tab, which lets you view and edit
parameters of the instance, page 134
.
• For folder: Opens the Properties tab, which lets you view, edit, and create
parameters of the folder, page 126
.
You can
search results.
NOTE: Search results are not updated automatically if instances or folders were created, modified, or deleted in the meantime. You need to start over the search by clicking the search field and pressing Enter .
EIO0000001114.15
Browsing Application Templates
Overview
The Templates Browser pane of the Application Explorer lets you find the application templates of the Foundation library and other libraries that are installed in the database of the system server. These templates let you model the application of the system.
The Templates Browser pane also displays templates that you have created and/ or imported.
To be displayed, a template needs to meet the following criteria:
• Template type: Application
• Usability State (see EcoStruxure ™ Process Expert, Global Templates,
Reference Manual) of either:
◦ Approved
◦ Deprecated
By default, quick filters are applied to display only templates that are:
•
.
• The latest version of the template.
• In the approved state.
You can display additional templates or refine your search by:
• Using the search field.
• Modifying quick filters.
• Using column filters.
NOTE:
• For details on available Schneider Electric application templates, refer to the
of the Schneider Electric libraries for EcoStruxure
Process Expert.
• For information on the naming conventions followed by Schneider Electric templates, refer to the topic describing
Global Templates libraries , page
.
EIO0000001114.15
119
Templates Browser Pane
120
1
(the check mark indicates that the filter is applied).
2 Search results. By default, in tree view, folders are shown first followed by instances. In grid view, instances are shown in a flat list. In both view modes, items are listed in ascending alphanumerical order.
3 Search field.
4 Button to toggle between grid and tree view for the display of search results.
5
Pin button, page 86 . Lets you minimize the
Templates Browser pane to the left edge of the screen. Move the pointer over the Templates Browser tab to display the pane. Click the pin button again to restore the pane.
6
Filters and sorting, page 93 .
Searching Templates by Using the Search Field
The search field of the Templates Browser pane lets you search templates by typing the entire or part of the template identifier. You do not need to use wildcards or type the $ prefix. The search is not case-sensitive. Your last three matching search keywords are stored and appear in a keyword menu. The stored keyword entries are system-independent and persist even after the system server is restarted.
The search field acts like a filter for the active view mode as soon as you enter a string. Results are displayed as you type. To show the entire content, clear the field by clicking the close button or deleting your entry.
For example, val returns templates that contain val in their identifier, such as
$HandValve_UC , $MValve , and $ControlValve .
The table describes the scope of the search and how results are displayed depending on the view mode that is selected.
EIO0000001114.15
View mode
Tree view
Grid view
What you can find
• Templates
• Folders
Templates
What is displayed
Templates and folders matching the search criteria with their entire parent folder structure.
Templates matching the search criteria in a flat list.
NOTE: Click the toggle button to switch between display modes. Search keywords and search results are retained.
Searching Templates by Using Quick Filters
The table describes the filters that are available in the Templates Browser pane to refine the template search.
Filter
Composites
Facets
Last Version
Only
Approved
Only
Description
Displays only templates that are composites, which also include control module templates.
Selected by default
Yes
Displays only templates that are facets.
Displays only the latest version of templates.
No
Yes
Used
Displays only templates that have the approved (see
EcoStruxure ™ Process Expert, Global Templates, Reference
Manual) state.
Displays only the templates that are already used by instances of the application.
Using this filter disables the other filters.
Yes
No
NOTE:
• When you select multiple filters, only templates that match the selected filters are displayed.
• When you select a filter, the software automatically refreshes the result.
The other way around, when the filtered data is modified, the filters are not applied to the modifications.
• Filters are reset when you close the Application Explorer .
Additional Filters and Sorting
You can
apply additional filters and sort the results, page 93
to refine your search.
Using the Application Browser Pane
Overview
The Application Browser pane lets you:
• Create, delete, move, copy-paste, and rename folders and instances.
• Search, sort, and filter folders and instances
• Toggle between tree and grid view mode, the latter showing only instances.
• Customize the display and the order of columns.
• View and edit the properties of folders and instances.
• Add instances to an asset workspace that is open in the Asset Workspace
Editor to create interface links.
• View assignments.
• Export and import application objects.
EIO0000001114.15
121
Application Browser Pane
The following figure shows an example of the Application Browser pane.
122
6
7
8
4
5
2
3
Item
1
9
10
11
Description
You can
(a check mark indicates that the filter is applied).
Button to toggle between tree and grid view mode.
Filters and sorting, page 93 .
which columns appear and in which position.
System root folder. By default, the system root folder is expanded to display its immediate children. Folders are shown first in the order you have arranged them, followed by instances in ascending alphanumerical order.
. Lets you hide the pane and restore it when it is docked.
If the folder has an
alias, page 126 , it is shown in brackets after the folder identifier.
For instances for which the hierarchical naming function is enabled, the alias is shown in front of the
(if applicable).
When you edit the identifier of an instance for which the
hierarchical naming function, page
is enabled, the alias appears to the left of the identifier in read-only mode (if applicable).
.
Using Instance Status Filters
The table describes the impact on the search result when you select instance status filters in the Application Browser pane.
Filter
Needs Attention
Link Invalid
Data Invalid
Progress
Description
Shows only instances that satisfy the three subfilter criteria.
Shows only instances whose Link
is invalid.
Shows only instances whose Data
is invalid.
Shows only instance for which a
appears.
EIO0000001114.15
EIO0000001114.15
NOTE:
• When you select multiple filters, only templates that match the selected filters are displayed. You can combine
and use the search field to refine your search further.
• When you select a filter, the software automatically refreshes the result.
The other way around, when the filtered data is modified, the filters are not applied to the modifications.
• Filters are reset when you close the Application Explorer .
Toggling Between Tree and Grid View
Tree view is the default view mode. You can switch to grid view any time by clicking the toggle button. The item selection in either view mode is retained when you switch and revert to this mode.
In grid view, when no sorting and filter is applied, all the instances of the application are shown in a flat list sorted in ascending alphanumerical order.
The table describes the impact on various features when switching from one view mode to the other.
Feature that is used
Search
Filtering
Sorting
Impact when switching between view modes
The search criteria is carried over.
Is not applied to the other view.
NOTE: In grid view mode:
• Commands of context menus related to folders are not available.
• You cannot create instances by dragging a template to the Application
Browser pane.
Navigating Inside the Browser Pane
The table describes the various methods that you can use to navigate inside the browser pane.
Key or action
Up/down arrow key
Left/right arrow key (1)
Enter (1)
Double-click (1)
Plus (+)/minus (-) key
Result
Moves the selection to the previous/next item.
Expands/collapses the next level of the selected node.
On a node, expands/collapses the next level of the node.
Expands/collapses the entire hierarchy from/up to the node.
(1) The next time you expand the node by using one of these methods, the display reverts to the last expanded view.
Customizing Column Display and Order
You can choose which columns you want to see by right-clicking a column header and selecting Customize . The Identifier and Template columns are always shown.
The Path column is available only in grid view.
When you hide a column for which a filter is applied, the filter is cleared.
When the Customize dialog box is closed, you can change the order of columns by dragging a column to its new position (except for Identifier ).
123
You can configure the column display and order independently in tree and grid view.
For a description of each column, refer to the topic describing the
creation of instances, page 130
.
NOTE: The order of columns is reset each time you open the Customize dialog box and click Apply .
Searching Instances and Folders
The search field of the Application Browser pane lets you search folders and instances by typing the entire or part of their identifier. You do not need to use wildcards. The search is not case-sensitive. Your last three matching search keywords are stored and appear in a keyword menu. The stored keyword entries are system-independent and persist even after the system server is restarted.
For example, entering to returns instances that contain to in their identifier, such as folder Torrefier and instance Motor_1 .
The search field acts like a filter for the active view mode as soon as you enter a string. Results are displayed as you type. To show the entire content, clear the field by clicking the close button or deleting your entry.
The table describes the scope of the search and how results are displayed depending on the view mode that is selected.
View mode
Tree view
Grid view
What you can find
• Instances
• Folders
Instances
What is displayed
Instances and folders matching the search criteria with their entire parent folder structure.
NOTE: When searching for folders, if several folders within the same hierarchical structure match the search criteria, only the highest level parent folder is shown in a collapsed state. You can see whether any child folders match the search criteria by entering the search criteria in the search field of the Application
Explorer . A tooltip indicates the path to folders in the search results.
Templates matching the search criteria in a flat list
Search keywords and search results are retained when you switch between view modes.
By default, results are displayed with folders shown in the order you have arranged them followed by instances in ascending alphanumerical order.
If
sorting and/or filters, page 93
are applied, they are also applied to the search results.
NOTE: Search results are not updated automatically if instances or folders are created, modified, or deleted. For example, if you have entered va in the search field and create a folder, which has Folder_n as default identifier, it will be shown.
Creating Application Folders
Overview
You can create application folders to structure your application by using the
Application Browser .
The software lets you structure the application according to the ISA-S88.01-1995 standard for batch control. You can create and rename the application folders according to the physical assets that you want to represent and
assign icons to the folders, page 129
to define a hierarchy of equipment.
Folders that you create may inherit properties of their parent folder, such as the
Area .
124 EIO0000001114.15
EIO0000001114.15
You can also:
• Create folders also by copying and pasting or
•
with or without changing the folder hierarchy.
•
Assign icons to application folders, page 129 .
Creating Application Folders
To create an application folder, proceed as follows.
Step
1
Action
Right-click the system root folder and select Create Folder .
Result : An application folder is created at the end of existing folders of the same level.
The identifier is in edit mode.
Application Folder Actions
Right-click the root folder, any application folder, or multiple folders to open a context menu with the following commands.
When you select...
Create
Folder
Open
Topology
Open
Project
Delete
The software...
creates an application folder or subfolder.
The command is not available when more than one folder is selected.
opens the
Topological Explorer , page 204
, which allows you to start the configuration stage or access the topology of the system.
The command is available from the root folder only.
Opens the Projects Explorer , which allows you to start the
Project Definition stage, page 199
or access the Control and Supervision projects of an existing system.
The command is available from the root folder only.
opens the Update Instance Template window. It lets you update the template that is used by instances inside the folder and any subfolder with the latest version of that template, which is available in the Global Templates library on the system server.
opens the Replace Instance Template window. It lets you select another template to be used by instances contained in the folder and any subfolders. The template needs to be available in the Global Templates library on the system server.
copies folders, their subfolders, and the instances they contain.
The command is not available from the root folder.
pastes the copied items to the selected locations in the system or in another system of the server.
The command is available if the copied content is valid for the selected target locations.
opens an Export dialog box, which allows you to save the parameters and configuration data of application objects to a file in CSV or XML format.
opens an Open dialog box, which allows you to select an export file in CSV or XML format, display its compatible contents, and select instances to be imported into the application.
The command is not available when more than one folder is selected.
deletes any selected folders and their contents including any subfolders and instances.
The command is not available from the root folder.
NOTE: After confirming the command, the abort icon is displayed in the
. Click the icon to cancel the task. Already deleted instances and/or folders are restored.
Only the user who has selected the command is allowed to abort it.
If you are deleting only a few items, the task may complete before you are able to click the icon.
125
Tab
General
Item
Identifier
126
Alias
When you select...
Rename
The software...
lets you enter a new folder identifier.
NOTE:
• Renaming a folder may affect
the equipment hierarchy, page 116
.
• The command is not available from the root folder and when more than one folder is selected.
• If the folder has an alias, it is not shown while the identifier is in edit mode.
Properties opens the
tab, which allows you to edit the properties of the application folder.
The command is not available from the root folder and when more than one folder is selected.
Moving Folders
You can move one or more folders by dragging them to a new position. A tooltip indicates the result of the action, which can have an impact on instances if the folder hierarchy is changed.
The table describes the tooltips that can appear and the corresponding result.
Tooltip
Move X before Y
Move X before Y
X
Result
The folder and its content is repositioned before or after the other folder.
The folder hierarchy is not changed.
The folder that you are moving and its content becomes a child of the other folder.
The
may be impacted.
The
and
of generated facets may be impacted.
Where:
X Is the identifier of the folder that you are moving.
Y Is the identifier of another folder of the application.
NOTE: When you move several folders, you cannot reposition them and maintain the same hierarchy.
Application Folder Properties
To open the properties of the application folder, right-click the folder and select
Properties . A tab opens inside the
of the Application
Explorer .
You can also open the properties by dragging the folder to the work area, the tabs bar of a work area, or to a
within the Application Explorer .
You can edit the following items.
Description
Designation of the folder.
The identifier must be unique for each subfolder of the same parent folder and satisfy
.
Default value: Folder_n where n is an incremental number starting at 1 for each folder level.
NOTE: Changing the identifier of an application folder may affect
the equipment hierarchy, page 116 .
Optional.
You can assign an abbreviated name to the folder.
The alias is shown in brackets next to the folder identifier.
EIO0000001114.15
Tab Item Description
Manage
Parameters
Description
Area
Parameter_1
...
Parameter_n
Identifier
Description
Value
The software uses the alias for the
hierarchical naming function, page 141 .
You cannot create or modify the alias value if it causes any instance identifier to be non-unique.
Default value: Blank
Optional.
You can enter a description of the folder with free form text. The description you enter appears in a tooltip when you move the cursor over the folder.
Default value: Blank
Optional.
You can assign a folder to an area.
Range: 1...255 (integer)
Default value: Blank
The software attempts to propagate the area value to subfolders and any instances contained in the hierarchy to which no area value has been assigned manually.
For details, refer to the topic describing
area value propagation, page 127 .
NOTE: You can also enter a string instead of an integer value. In such case, you must refine the Supervision project after generating it and use the same string as label to name the area; otherwise, the Supervision project does not build successfully. Refer to the help of the Supervision Participant for details.
NOTE: The area value is also propagated to Supervision elements of instances such as genies.
You can use as many folder parameter sets as you require.
Default value: No parameter
NOTE: Click Add Parameter to add a parameter.
Area Parameter Value Propagation
The software automatically propagates the value (including blank (NULL value)) of the Area parameter of a folder to:
• Existing subfolders and instances that the folder and its subfolders contain unless you have assigned an area value to them manually.
• Subfolders and instances that you create afterwards.
• Subfolders and instances that you add afterwards either by copying or moving them unless an area value had been assigned to them either automatically or manually.
If you change an existing area value of a folder, only the area value that was propagated automatically to the next level of subfolders and their instances is updated. The change is propagated down the folder structure, level after level, until a manual folder area entry is detected.
If the software is not able to propagate the value of the Area parameter to any item because the item is locked, it:
• Displays a notification to inform you which item is locked.
• Rolls back any propagated area value.
• Reverts the Area parameter value that you have entered in the folder properties to its previous value.
EIO0000001114.15
127
128
NOTICE
NO CHANGE PROPAGATION
When the Area parameter value of a folder is not propagated:
• Reenter the Area parameter value in the properties of the folder.
• Verify in the Notification Panel that parameter value propagation completed successfully.
Failure to follow these instructions can result in alarms being signaled in the wrong area during operation.
Examples
The following three examples illustrate the area value propagation to existing subfolders and instances in the Application Explorer . The changes described in these examples are performeds in steps inside the same folder structure.
In a first step, starting from a folder structure and instances without area value, if you change Area of Folder_1 to 1, the value is propagated to Instance_1 , subfolders, and their instances.
In a second step, if you change Area of Instance_2 to 2 and then Area of Folder_1 to 3, value 3 is propagated to Instance_1 , subfolders, and their instances except for Instance_2 because the area was entered manually.
EIO0000001114.15
In a third step, if you change Area of Folder_2 to 4, value 4 is propagated to
Instance_21 , the Folder_4 subfolder and its instance.
Instance_2 remains unchanged because the area was entered manually. If you then change Area of
Folder_1 to 5, value 5 is propagated only to Instance_1 , subfolder Folder_3 , and its instance because the area of other subfolders and instances have either been entered manually (for example, Folder_2 ) or are manual entries that have been propagated (for example, Folder_4 ).
Assigning Icons to Application Folders
Overview
By using the Settings pane, you can assign icons to each level of application folders. The icons appear in the tree view of the Application Browser
You can use this feature, for example, to represent graphically the physical hierarchy of equipment used in a batch process according to the ISA-S88.01-1995 standard.
The settings apply to the system for which you configure them, to any user who opens the system in an engineering client, and persist even if you restart the system server.
NOTE: You cannot assign an icon to the system root folder.
Available Icons
You can choose from the following selection of icons.
Icon Description
Default folder icon
Site
Area
Process cell
Unit
Equipment module
NOTE: Control modules are represented by the instances of the application.
EIO0000001114.15
129
Assigning Icons to Folder Levels
To assign an icon to a folder level, proceed as follows.
Step
1
2
3
4
Action
Click the Explorer Layout Settings
Result: The Settings pane opens.
In the Appearance section, select the folder level to which you want to assign an icon.
In the Style menu, click the icon that you want to use.
Result: The icon is assigned to each existing folder of the selected level and to each new folder that you create in the selected level.
Repeat the procedure for other folder levels.
Creating Instances
130
Overview
Instances that you create in the
of the application are created with the default configuration of their template. Basic information on each instance is available at the folder level.
Once you have created an instance by using the Application Browser , you can perform various actions by using the pointer, accessing the context menu of the instance, or using keyboard shortcuts.
Order of Instantiation
The order in which you create instances inside an application folder may affect the order of the referenced Control facets in a section during
.
Instantiating Application Templates
To instantiate a template in the root folder or in any application folder, proceed as follows.
Step
1
2
3
4
Action
Verify that the folder in which you want to create the instance is displayed in the
Application Browser .
In the Templates Browser , select a template.
Drag the template to the folder.
Result: The folder opens or expands and an instance of the template is created in last position with the default identifier in edit mode.
NOTE: If the folder has an alias, it is shown in a separate cell on the left of the identifier.
To change the identifier, type it; otherwise, press Enter to accept the default name.
NOTE: To keep the default name and create a new instance, you do not need to press Enter ; you can drag another template while the identifier of the instance is still in edit mode.
NOTE: Refer to
Managing Application Folders and Instances , page 155
for information on features that are available when working with many application folders and instances.
Instance Description
The following information of an instance is displayed in the Application Browser when the corresponding
EIO0000001114.15
EIO0000001114.15
Header
Icon
Identifier
Template
Version
Data
Link
Assigned
State
Description
Area
Path
Description
Displays the icon corresponding to the type of template that the instance uses.
For instances, displays the instance identifier (see EcoStruxure ™ Process Expert,
Global Templates, Reference Manual), which must be unique for each instance of the same template. The software calculates the identifier by using the parameter $Name of the instance and the applicable naming conventions.
For folders, displays the folder identifier, which you can edit in the Properties tab or by using the Rename command.
NOTE:
• You can edit the $Name parameter of an instance in the
or by using the Rename command. If the resulting identifier is not unique, the $Name field is outlined in red. In such case, clicking outside of the field reverts the name to its previous value.
• The
hierarchical naming function, page 141
can modify the identifier of an instance.
• Two instances using two different templates cannot have the same identifier if both instances have an element in their composition in common
(for example, the Logic element, which is created by the $DEVCTL_UL facet). In such case, the identifier of the element that both instances have in common would be the same; this is not allowed.
Indicates the identifier of the template that the instance uses.
The field is not used for folders.
Indicates the version of the template that the instance uses.
The field is not used for folders.
Indicates the status of the instance. Possible values:
• Valid
• Invalid
The value is updated when you save changes in the Instance Editor .
The field is not used for folders.
NOTE: You can obtain information about the
of an instance in the Validity Diagnosis window:
• By clicking Invalid .
• When viewing its
Indicates the status of the application interface link of the instance. Possible values:
• Valid
• Invalid
The value is updated when you make a link by using the
Asset Workspace Editor, page 146
or save changes in the Instance Editor that impact the link requirements of the instance.
The field is not used for folders.
NOTE: You can obtain information about the
of an instance in the Validity Diagnosis window:
• By clicking Invalid .
• In the Asset Workspace Editor .
Indicates the
of the facets of the instance. Values:
Assigned : At least 1 facet of the instance is assigned to any project of the system.
Unassigned : No facet of the instance is assigned to any project of the system.
The field is not used for folders.
Displays the content of the $Description parameter the folder or the instance. You can edit the field in the Properties or the
tab respectively.
Displays the value of the $Area parameter for the folder or the instance. You can edit the field in the Properties tab or the
tab respectively.
NOTE: If the value was
assigned automatically, page 127
by the software, it appears between angle brackets. For example, <5>.
Indicates the path to the instance in the application starting from the system root folder.
NOTE: The column is shown only in grid view mode.
131
132
Instance Actions
Right-click an instance to open the instance context menu with the following commands.
Command Description
Properties (1) Opens the
in the work area, which allows you to view and configure parameters, and select services of the instance.
Navigate to
Workspace
(1)
Opens the Show Workspace window, which lists the asset workspaces that the instance belongs to.
Double-clicking an asset workspace opens it in the Asset Workspace Editor and highlights the instance. This lets you create and manage links between instances.
Edit Links (1)
Opens the
, which allows you to view the interface links that exist for the instance.
Opens the View Assignments window, which lets you verify if the facets that are referenced by the instance are assigned to Participant projects:
• If a facet is not assigned, you can select an existing project and open the
Assignment Editor to assign it.
• If a facet is assigned, you can access the container to which the facet is assigned.
For Supervision genie facets, you access the Pages node in either case.
NOTE: The command is not available if the Data or Link status of the instance is Invalid .
Opens the Update Instance Template window. It lets you update the template that is used by the instance with the latest version of that template, which is available in the Global Templates library on the system server.
Opens the Replace Instance Template window. It lets you replace the template that the instance is using by another template, which is available in the Global
Templates library on the system server.
Opens the Inspect Instance window, which provides information on the entire instance configuration, including interface links.
Rename (1)
Delete
Copies the selected instances for pasting within the application of the system or any other system on the server.
Opens an Export dialog box, which allows you to save the instance data to a file in
CSV or XML format.
Sets the identifier of a single instance to edit mode. Type the new identifier and press Enter .
NOTE: The instance identifier is split in two and only the instance name
( $Name ) part is editable if the following conditions are satisfied:
• You have defined an alias for the folder containing the instance or any of its parent folders.
• The
hierarchical naming function, page 141
for the instance is enabled.
The concatenated, non-editable aliases are shown on the left of the instance identifier.
Deletes the instance from the application.
You can select multiple instances within the same folder.
Not available while you edit the instance.
If you have assigned facets of the instance to projects, the
of these facets changes to Deleted .
NOTE: After confirming the command, the abort icon is displayed in the
notification panel, page 54 . Click the icon to cancel the task. Already deleted
instances are restored.
Only the user who has selected the command is allowed to abort it.
If you are deleting only a few instances, the task may complete before you are able to click the icon.
(1) The command is not available when multiple instances are selected.
EIO0000001114.15
Counting Instances
EIO0000001114.15
Overview
The software includes a mechanism, which counts the instances that exist in the application of any system on the system server and compares their number to the maximum number of instances that the application size license that is activated allows.
At any time during the system engineering life cycle, you can view the instance count for each system, the total count, and the maximum number of instances that is allowed.
The software does not allow actions that cause the maximum number of instances of the application to be exceeded.
Viewing Instance Count Information
Instance count and software license information is displayed in the About
EcoStruxure Process Expert
The table describes the information that is displayed in the License Details section of the General tab.
Label
Maximum Instances
Allowed
Current Instance Count
Description
Total number of instances that you can create with the current license.
Total number of instances in the systems that exist on the system server.
The table describes the information that is displayed in the Systems Details tab.
Header
System Name
Instance Count
Description
Identifiers of the systems that exist on the system server.
Total number of instances of the system.
Actions Affecting Instance Count
The following actions that you can perform in the Application Explorer increase and/or reduce the instance count in the application:
• Instantiate
• Paste
• Import
• Delete
The following actions that you can perform in the Systems Explorer increase and/or reduce the instance count in the application:
• Restore
• Delete
Exceeding the Allowed Number of Instances
If one of your actions causes the maximum number of instances that is allowed by the activated license to be exceeded, the software cancels the entire action. It also displays a message to advise you that you have reached the limit of instances allowed by the license.
In such case you have the choice to:
• Delete instances (you can
export the instances, page 169
before deleting them to reuse them later.)
133
• Delete systems (you can
before deleting it to reuse it later.)
• Upgrade the application size license (see EcoStruxure ™ Process Expert,
Licensing Guide).
Accessing Instance Properties
Overview
The Instance Editor tab opens in the inside the
of the
Application Explorer and provides access to:
• Control, Supervision, and documentation
provided by the template that the instance is using.
• Parameter values of the
of the instance.
• The number of parameters that have been modified.
• The status of the instance.
NOTE: More information on the instance configuration is available in the
Inspect Instance
in read-only mode.
Read-Only Mode
You can open the Instance Editor for an instance in read-only mode if either of the following is true:
• The instance is being edited, for example, from another client connected to the same system server.
• The instance is displayed in the Links Editor , either as
The read-only mode allows you to view instance parameters but not to modify them.
Opening the Instance Editor
To open the Instance Editor , double-click the instance that you want to configure in the Application Explorer .
You can also open the Instance Editor in the following ways:
• Right-click the instance and select Properties .
• Drag the instance to either area within the Application Explorer :
◦ The
.
◦ The tabs bar of a work area.
◦ A
.
134 EIO0000001114.15
Instance Editor
The following figure shows an example of instance Motor_1 , which uses template
$Motor open in the Instance Editor .
EIO0000001114.15
5
6
7
8
9
3
4
Item
1
2
10
11
12
13
Description
Instance identifier. It is prefixed with * if you have made a change and not saved it.
Instance validity status indicator. The status is set to Invalid and details are available by clicking the information button if either the Data or Link
is invalid.
Save button. Click to save parameter values and
.]
Instance pane, which allows you to view the services that the instance provides and to enable/disable optional ones. By default, nodes are shown expanded.
Element displayed in bold indicating that the element contains editable parameters.
Check box for element selection.
Counter indicating the number of modified parameters for a node out of the total number of parameters that exist for that node.
Counter indicating the number of modified parameters for an element.
Elements of optional nodes of the instance that are not selected and that have configurable parameters are displayed on a light gray background. This allows identifying easily which are the optional services of the instance that provide additional customization capabilities. Selecting the node removes the gray background.
Parameters pane, which allows you to configure the parameters of the elements of the instance that you have selected.
Optional
Hierarchical naming function, page 141
selection box. The function is enabled by default.
Parameter Filters section, page 138 .
Grouped by sorting function for parameters.
The table describes the fields of the instance pane.
135
136
Header
Name
Icon
Check box
( x / y )
( z )
Description
Template
Description
Shows the composition of the instance by displaying the identifier of the instance and:
• Its core and optional composite elements (nodes)
• Core and optional elements thereof (facets)
Elements (facets) provide the services of the application template, which depend on the template that the instance uses.
For details on the services that are provided by Schneider Electric application templates, refer to the
of the Schneider Electric libraries for EcoStruxure Process Expert.
An item in bold indicates that you can configure parameters of the element.
Move with pointer over an element to see a description of the element in a tooltip.
Indicates the type of template that is used by the instance and its elements.
Indicates that the element is optional and not mandatory for the control module to function. Typically, optional elements correspond to additional functionalities that are built into the template and that you can select to customize the instance according to your needs.
An optional element may contain optional subelements, which you can select individually.
Selecting an element enables it and creates the corresponding facets. If applicable, it allows you to configure parameters of the service that the element provides.
Selecting an optional Control element automatically selects the corresponding Supervision element if it is available. For example, when you select the Interlocks element of the $Motor template, the InterlockTags
Supervision element is selected.
The other way around, clearing a selected Control element automatically clears the corresponding Supervision element.
The following Supervision elements are selected by default:
• Elements corresponding to core Control elements, which are not optional.
• Elements corresponding to optional Control elements, which are selected by default.
Node counter (7). For the instance and for its composite elements, the first number indicates the number of parameters that you have changed in the node ( x ) compared to the default value and the second, the total number of parameters ( y ) that you can change for this node.
Changes to the Instance Name are not counted.
Counters are updated as soon as you confirm your entry by pressing Enter .
For boolean types, when you select or clear them.
NOTE: The counter turns bold to indicate that you have changed a parameter of the element itself. When you change a parameter of any of its child elements, the counter font style remains regular.
Element counter (8). For child elements, indicates the number of parameters that you have changed compared to the default values.
The counter appears even if the element has no editable parameters.
Counters are updated as soon as you confirm your entry by pressing Enter .
Description of the instance or element displayed in the Name column.
For instances and composite elements, indicates the identifier of the template that the instance or composite element is using.
For facet elements, indicates the identifier of the facet template that encapsulates the constituent provided by the Participant to implement the service.
Version of the template that the instance or element uses.
Version
The table describes the fields of the parameters pane.
EIO0000001114.15
EIO0000001114.15
Header
Group By
Element Path
Category
Name
Description
Type
Value
Resolved
Value
Description
Allows you to sort parameters that are displayed in the parameters pane by the following criteria:
• Element Path
• Category
• Type
By default, parameters are grouped as follows:
• For instances based on a composite template: By Element Path , then
Category .
• For instances based on a facet template: By Category .
Click the close button of a criteria to remove if from the grouping. The corresponding column is displayed.
Drag a column header to the green bar to group parameters by the corresponding criteria. You can group by multiple criteria simultaneously.
When multiple criteria are selected, swap their order by dragging a criteria left or right.
When you have selected to group by a criteria, the corresponding column is not displayed anymore.
Path to the element, which provides the parameters, as shown in the instance pane.
Not available for instances based on a facet template.
Category of the parameter.
Identifier of the parameter.
The column is hidden by default.
Right-click any column header and select Show Name to display the column.
Right-click any column header and select Hide Name to hide the column.
Description of the parameter.
Indicates the data type of the parameter.
Default value of the parameter or the value that you have entered.
NOTE: For parameters of the enumerated data type, for each enumerator, both the name and the associated integer are shown (for example, Operator
(2) )
Displays the value after formatting according to the data type.
For example, when the check box of a boolean parameter is selected, the value that is displayed is True .
The column is hidden by default.
Right-click any column header and select Show Resolved Value to display the column. Right-click any column header and select Hide Resolved Value to hide the column.
NOTE: Open the
Inspect Instance window, page 155
to view the resolved value of additional template parameters, which has been calculated by using the value property and any applicable logic defined in the template definition.
Navigating Inside the Instance Pane
The table describes the various methods that you can use to navigate inside the instance pane.
Key or action Result
Up/down arrow key Moves the selection to the previous/next item.
Left/right arrow key
(1)
Expands/collapses the next level of the selected node.
Enter (1)
Double-click (1)
Plus (+)/minus (-) key
On a node, expands/collapses the next level of the node.
Expands/collapses the entire hierarchy from/up to the node.
137
138
(1) The next time you expand the node by using one of these methods, the display reverts to the last expanded view.
Displaying Instance Parameters Using Filters
The table describes the filters that are available in the Parameter Filters section to customize the display of parameters of the selected instance or element.
Filter
Editable
Modified
Show Child
Parameters
None selected
Description
Displays only parameters of the selected instance or element that you can edit.
A parameter may not be editable because it is optional and you have not selected it.
The filter is applied by default.
Displays only parameters of the selected instance or element whose value you have modified compared to their default value.
Displays parameters of the selected instance or element including those of child elements.
No filter is applied. Displays the parameters of the selected instance or element.
NOTE:
• When you select multiple filters, the software displays only parameters that match the selected filters.
• When you select or clear a filter, the software automatically refreshes the result.
To apply default filters, click the filter icon, then click Default .
To clear any filters, click the filter icon, then click Clear Filter .
Instance Data Status
When any of the following conditions apply, the Data status of the instance in the
Instance Editor changes to Invalid :
• Entering a
character that is not allowed, page 65
in the $Name field.
• Entering a number of characters in the $Name field causing the instance identifier to exceed the
length limit that may be defined, page 65 .
• Selecting an invalid combination of optional elements in the instance pane of the Instance Editor .
• Creating an instance that references an element that has the same identifier as an existing element in the application. For example, if you create two instances with the same identifier from two different templates, which have an element in common, such as Interlocks , which uses the $CONDSUM1_UC facet template.
You cannot assign to projects instances that have a Data status that is Invalid .
Furthermore, when facets of an instance are assigned to a Participant project, and later either status of the instance changes to Invalid , the software propagates the invalid status to facets of Participant projects.
While the Data status is displayed as Invalid , click the validity status information button to display the Validity Diagnosis window, which provides information about the cause of the status.
EIO0000001114.15
The following figure shows an example of the Parameter tab of the Validity
Diagnosis window that the software displays when it detects an invalid identifier.
NOTE: For information on the other tabs that are related to the Link status of the instance, refer to the topic describing
NOTE: If the status of an instance is Invalid because of a duplicate element identifier, deleting or modifying the other instance that contains the same element does not change the status back to Valid . After you have solved the conflict, edit the invalid instance and save any change (for example, a modification of the description) to set its status to Valid .
Configuring Instances
Overview
The Instance Editor lets you:
• Enable or disable optional Control, Supervision, and documentation services, which are provided by the template that the instance is using.
• View and configure parameters of the instance.
For more information to help you select and configure instances to meet the requirements of your application, refer to the
of the Schneider
Electric libraries for EcoStruxure Process Expert.
For information on how to link documents, files, and associate web links to instances for use with runtime navigation services, refer to the topic describing how to add user contents (see EcoStruxure ™ Process Expert, Runtime Navigation
Services , User Guide ).
NOTE: When an instance is being edited by using another client of the same system server, this instance can only be opened with the Instance Editor in read-only mode to preserve
.
Modifying Instance Parameters After Assignment
When you modify and save properties of an instance whose facets are already assigned to a Participant project, the software may display a message to inform you that your modifications affect the assignment status of these facets.
This is a generic message that does not take into consideration whether the assigned facets are generated or not.
In fact, only the assignment status of generated facets can be changed to
If facets are only assigned, upon saving your changes:
• Modifications are propagated without affecting the assignment status. (For example, if you change the instance name, the identifier of assigned facets is updated in the Participant project.)
• Entire facets are removed from the container to which they are assigned. (For example, if you clear an element of an instance, the corresponding facet that was assigned is deleted.)
EIO0000001114.15
139
140
Changing the Element Selection of Instances with Assigned
Facets
When you change the element selection of an instance, which has at least one facet that is already assigned and this change results in the creation of new facets, the software can assign candidate facets automatically to the same container.
For more information, refer to the topic describing
automatic facet assignment, page 284
.
Validating Parameter Values
When you edit parameters of the instance, the Instance Editor displays and validates values according to the
, helping you configure the values in accordance with the data type format.
You cannot save the instance properties if the software has detected that a parameter value is not valid.
Certain
use language-specific formatting according to the Regional Options that are set for the operating system of the PC. For example, if your regional settings define . (dot) as decimal delimiter and you enter a decimal value in the format 100,5 by using comma instead of the dot, the software processes this value as 1005.0
.
NOTE: Except for changes to the $Name parameter:
• Changes appear in italics until you save them.
• Values that you enter and that are different from the default value are shown in bold at any time.
WARNING
UNINTENDED EQUIPMENT OPERATION
Verify which Regional Options are configured in the operating system of your computer and follow the applicable formatting rules to enter data in the
Instance Editor .
Failure to follow these instructions can result in death, serious injury, or equipment damage.
In addition, in the Instance Editor the following rules apply when you edit the
$Description parameter and other element parameters of type String of an instance.
Rule
““ returns an empty string.
Conversion of “ into
^” .
To return ^ use ^ .
Example or comment
“ example or example “ is not allowed.
The software converts ” example ” into ^“ example ^“ to return
” example ” .
^ example or example ^ is not allowed.
^^ example ^^ returns ^ example ^ .
Naming Rules for Instance Parameters
When you change instance parameter values, verify that they satisfy the
Participant specific
so that the subsequent generation process can complete successfully.
Further, entering incorrect values may change the Data
of the instance to Invalid when you save the instance configuration.
NOTE: Naming rules may also apply when you use the hierarchical naming function.
EIO0000001114.15
Hierarchical Naming Function
You can use the hierarchical naming function to let the software manage the
of an instance. The function is enabled by default.
When you select the hierarchical naming function, the software creates the identifier of an instance automatically through the concatenation of:
• The
alias of each application folder, page 126
in the path of the instance, starting from the system root folder.
• The
parameter of the instance.
For example, if the $Name of an instance is Motor_1 and the path to its location is:
System Root Folder\Folder_1\Folder_2 .
Plus, you have assigned the aliases F1 and F2 respectively to each folder.
Then, the identifier of the instance becomes F1F2Motor_1 .
NOTE:
• The length of the instance identifier cannot exceed the
maximum length, page 65 ; otherwise the software displays the status of the instance as
.
• The software excludes folders without alias from the hierarchical naming
(for example, if you assign no alias to Folder_1 , the identifier of the instance becomes F2Motor_1 ).
• You cannot assign an alias to the system root folder.
To use the hierarchical naming function, proceed as follows.
Step
1
2
3
4
5
6
7
Action
Right-click the instance and select Properties .
Result: The Instance Editor opens.
Verify that Hierarchical Name is selected, enabling the hierarchical naming function; otherwise select it.
Close the Instance Editor .
Right-click the application folder that is to be considered for the hierarchical naming and select Properties .
Result: The Properties tab of the folder opens.
Assign an alias to the folder in the Alias field.
NOTE: Keep the alias as short as possible to avoid reaching the instance identifier character limit.
Repeat steps 4 and 5 for the other folders that you want to include in the hierarchical naming.
If required, modify the $Name of the instance in the Instance Editor to avoid reaching the instance identifier character limit.
NOTE: The software applies the hierarchical naming when you
, or
instances in the Application Explorer .
Instance Parameters
You can configure the following instance parameters in the parameter pane of the
Instance Editor .
EIO0000001114.15
141
Selection in the instance pane
Instance
Parameter
$Name
Instance
Control node –
Supervision node
–
HyperLink node
NOTE:
Requires using templates of a library that supports this functionality.
–
$Description
$Area
Data type
String
String
Integer (1)
–
–
–
Description
Default value: Template identifier _ n where n is an incremental number starting at 1. For Schneider Electric templates, the $ suffix and the _xy prefix are omitted.
Within the application of one system, the resulting
must be unique for each instance using the same template; otherwise, the
$Name field is outlined in red. Clicking outside of the field reverts the name to its previous value.
Entering a character that is
changes the instance Status to
.
NOTE: If you enter the same value for two instances that use a different template and the resulting instance identifiers are identical, the $Name field is outlined in red if the identifiers of Control facets of the two instances are not unique anymore (for example, when both instances contain the Interlocks element, which is created by the same facet).
NOTE: The software changes the $Name parameter of the instance if the value is not unique anymore within the application following a
or
operation.
Description of the instance.
Default value: Blank.
Area that the instance is assigned to.
Range: 1...255
Default value: Blank.
NOTE: If you have assigned an
area value to the folder, page 127
containing the instance, the software automatically assigns the same value to the instance unless you assign a value manually.
If the software is not able to propagate the value of the Area parameter to any item because the item is locked, it:
• Displays a notification to inform you which item is locked.
• Rolls back any propagated area value.
• Reverts the Area parameter value that you have entered in the folder properties to its previous value.
NOTE: The area value is also propagated to Supervision elements of instances such as genies. However, the change to blank (NULL) from a non-blank value is not propagated to
that are already assigned to a Supervision page (for example, changing the area value from 3 to 4 is propagated but not changing it from 3 to blank).
You can configure the values of the parameters of the core and optional
Control services that the instance provides through the selected elements.
The default values are defined in the respective elements of the template that the instance uses.
For details on parameters of Schneider Electric application templates, refer to the
of the Schneider Electric libraries for EcoStruxure Process
Expert.
You can configure the values of the parameters of the optional Supervision services that the instance provides through the selected elements.
The default values are defined in the respective elements of the template that the instance uses.
For details on parameters of Schneider Electric application templates, refer to the
of the Schneider Electric libraries for EcoStruxure Process
Expert.
You can configure the parameters of the optional Documents service that let you link documents to the instance. You can open these documents on computers running the operation client when using runtime navigation services
(see EcoStruxure ™ Process Expert, Runtime Navigation Services , User Guide
).
You can link up to five documents.
You must add documents that you want to link to the content repository first.
For details, refer to the topic describing how to link documents to instances
(see EcoStruxure ™ Process Expert, Runtime Navigation Services , User Guide
).
142 EIO0000001114.15
Selection in the instance pane
Parameter Data type Description
You can configure the parameters of the optional URL service that let you associate web links and files to the instance. You can open these links on computers running the operation client when using runtime navigation services
(see EcoStruxure ™ Process Expert, Runtime Navigation Services , User Guide
).
You can link up to five files or URLs.
For details, refer to the topic describing how to associate web links and files to instances (see EcoStruxure ™ Process Expert, Runtime Navigation Services ,
User Guide ).
(1) You can also enter a string instead of an integer value. In such case, you must refine the Supervision project after generating it and use the same string as label to name the area; otherwise, the Supervision project does not build successfully. Refer to the help of the
Supervision Participant for details.
Using the Asset Workspace Pane
This topic describes the Asset Workspace pane. It lets you manage asset workspaces and open them in the Asset Workspace Editor to
manage links between instances, page 146
.
Asset Workspace Pane
The following figure shows an example of the Asset Workspace pane, which contains two user-created asset workspaces.
System_1 is the system root node.
EIO0000001114.15
Root Node Actions
The table describes the commands of the context menu of the system root node in an asset workspace.
Command
Create Workspace
Paste
Export
Import
Description
Creates a new empty asset workspace.
This is a structural element that lets you group assets, which are existing instances of the application in order to create links between them.
Lets you create a copy of the asset workspaces and their content that you have added to the Clipboard.
You can paste within the same system only.
Lets you
the data of existing asset workspaces and instances that belong to them to an editable application export file in comma-separated value (CSV) format.
Lets you
the data of workspaces and their instances, which are contained in an application export file (.csv).
143
Asset Workspace Actions
The table describes the commands of the context menu of asset workspaces.
Command
Edit Workspace
Show Instances
Copy
Export
Delete
Rename
Description
Opens the asset workspace, page 146
in the Asset Workspace Editor .
Lets you add and remove instances and edit links between them.
Opens the Show Instances window, which lets you see information about the instances that have been added to this asset workspace.
Double-clicking an instance opens the asset workspace and highlights the instance.
Copies the data of the asset workspace and instances that belong to it to the Clipboard.
Lets you
the data of this asset workspace and instances that belong to it to an editable file in comma-separated value (CSV) format.
Deletes the asset workspace but does not delete the instances from the application nor the links between them.
Lets you rename the asset workspace.
Instance Indicators
Overview
This topic describes the various indicators that appear on folders and instances of the application.
Instance Progress Indicators
Overview
Various icons give an indication of the steps that remain before the instantiation and
stages for each instance are completed.
The color of progress icons is used to indicate
.
A progress icon is not visible while the
is shown.
NOTE: The icons are visible to any user who opens the application.
Meaning of Icons
The following progress information is valid only for instances whose facets are not yet generated.
Icon Condition description
The instance is created or has been pasted without further action.
(0% progress)
Either one applies:
• The
have been modified at least once but no assignments have been performed.
• The instance progress is 50% or 75% and existing
have been removed.
• The instance has been imported without impact on Participant projects.
Either one applies:
144 EIO0000001114.15
Icon
No icon
(100% progress)
Condition description
• Facets of the instance have been assigned but there is still one type of Participant project to which no facet has been assigned (for example, to a Supervision project).
• At least one facet that is assigned has a
other than Assigned .
• The instance has been imported and has changed the assignment status of at least one facet to Out Of Date or Deleted .
At least one facet of the instance has been assigned to a Control and Supervision
Participant project respectively and each one has the Assigned status.
All the facets of the instance have the Assigned status.
How Icons Appear
The following figure shows an example of the Application Browser displaying several instances with various completion states, which are indicated by progress icons.
Instance Validity Indicator
Overview
A dot or
that appears in red color indicates that the configuration of an instance is invalid.
When the icon appears on at least one instance, it appears automatically on folders in the hierarchy of the instance.
NOTE: The indicator icon is visible to any user who opens the application.
Meaning of the Icon
Level Icon color
Instance Red
(progress icon or dot for objects with 100% progress)
Folder Red
(dot)
Condition description
The instance Data
and/or Link
is invalid.
The icon appears on at least one instance in the child structure.
EIO0000001114.15
145
Instance Write-Lock Indicator
Overview
A lock icon lets you see that an instance or folder is being used or modified by another process or user and that you cannot work on it.
Certain objects that are locked can be opened in read-only mode.
NOTE: The indicator icon is visible to any user who opens the application.
Meaning of the Icon
The lock icon is shown, for example, when either operation is performed on an instance or folder:
• Properties are open (instances only)
• Paste
• Rename
• Export/import
• Update/replace template
Linking Instances by Using the Asset Workspace Editor
This topic describes how to add instances to asset workspaces and link them by using their exposed interfaces. It also describes how to manage interface links.
Asset Workspace Editor
Overview
The Asset Workspace Editor lets you link the exposed application interfaces of an instance to the interfaces of other instances that are compatible and respect the cardinality of the roles (for example, 1 to 1, or 1 to n ). The editor lets you
create, modify, or delete links between instances, page 152
that belong to a same asset workspace.
You can use the editor, for example, to map a signal to an application object such as a limit switch signal to the appropriate input of a pump motor.
Some instances require that you link them to other instances based on the interface rules of their templates; otherwise the status of the
of the instance remains Invalid and you cannot proceed further in the system engineering life cycle.
NOTE:
• Linking instances by using the Asset Workspace Editor helps avoid having to create such links later by refining the Control Participant project and provides a level of consistency in terms of Control resource names.
• Linking an instance to itself is not allowed. If this is required, edit the template used by the instance or refine the Control project to which facets of the instance are assigned.
Opening the Asset Workspace Editor
To open the Asset Workspace Editor , right-click an asset workspace and select
Edit Workspace .
146 EIO0000001114.15
Asset Workspace Editor
The following figure shows an example of the Asset Workspace Editor .
EIO0000001114.15
5
6
7
8
9
Item
1
2
3
4
Description
Instances that have been added to the asset workspace by dragging them from the
Application Browser or importing them.
Linked instances that do not belong to the asset workspace are not shown.
An instance can belong to an asset workspace even if it is not linked.
Existing application interface links and new ones.
Only links between instances that belong to the same asset workspace are shown.
Interface link that was converted to a connector by using the link context menu command.
RTNS interfaces, page (runtime navigation services). Appear in blue and are located in the header section of the instance.
RTNS interface links.
Indication of the link status of the instance that is selected and button to open the
Validity Diagnosis window if the status is Invalid .
.
Lets you print the visible portion of the asset workspace.
NOTE: You can also
move the editor background, page 81
.
147
148
Instance Actions
The table describes the commands of the context menu of instances that appear in the Asset Workspace Editor .
Command Description
Show/Hide Disabled Lets you show or hide interfaces that are disabled (gray) and not available for connection.
Show/Hide Unbound Lets you show or hide interfaces that are not connected to another instance in the same asset workspace.
RTNS interfaces are always shown.
Remove Instance
View Assignments
Removes the instance from this asset workspace but does not delete it from the application.
In addition, if the instance is linked to another instance in the same asset workspace, you can perform either action:
• Delete the links that this instance has with any other instances in the same asset workspace. (Links to instances that are not in this asset workspace are maintained.)
• Remove the instance but maintain its links.
Opens the View Assignments
.
Properties
in the Instance Editor .
Link Actions
The table describes the commands of the context menu of links that appear in the
Asset Workspace Editor .
Command
Convert to Connector
Convert to Line
Go to
Description
Lets you toggle between .
Delete
Opens a submenu that indicates the following:
• The identifiers of the two instances that are linked.
• For each instance, the name of the element that exposes the linked interface and its path.
Deletes the link.
Impact of Modification of Instance Properties
When you save changes to an instance in the Instance Editor applicable changes are automatically reflected on the instance in the Asset Workspace
Editor . If a change disables an interface that was linked, the link is automatically removed.
This may set the Link
of either linked instances to Invalid .
Viewing Interfaces and Interface Description
Not all interfaces of instances that are displayed in the Asset Workspace Editor are visible by default. You may need to expand nodes of the interface to show enabled (green) or disabled (gray) interfaces.
To enable an interface, edit the instance and select the element that contains the interface, and/or configure the element parameter that enables it.
Move the pointer over any interface in the editor to display a description of the interface in a tooltip.
NOTE: Verify that disabled and unbound interfaces are shown by using the corresponding commands in the context menu of instances.
EIO0000001114.15
Using the Simplified View
Overview
Zooming out to the lowest level in the Asset Workspace Editor switches the display to the simplified view.
This view mode lets you see at a glance the instances and the relation between them without showing the details of links, interfaces, and elements of instances.
Some engineering functionality is not available.
To exit the simplified view, zoom in.
Restrictions of the Simplified View
The table describes the restrictions that are in effect while the simplified view is active.
Actions or object
Actions related to links such as creating and moving
Elements and interfaces
Multiple links to and from an instance
Restrictions
Actions are not allowed
Are not shown
Are shown as a single line
Description
The following figure shows an example of instances as they normally appear in the Asset Workspace Editor .
EIO0000001114.15
149
The following figure shows the same view when simplified view is active (the view is enlarged for better visibility).
• Instances maintain their relative size and position to preserve the aspect of the layout.
• Links between instances are grouped into a single line.
Instance Link Status
Overview
The Link status of an instance can be one of the following:
• Valid : The interface rules and interface element rules that are defined at the template level are satisfied.
• Invalid : At least one of the defined interface rules or interface element rules are not satisfied.
You cannot assign to projects instances that have a Link status that is Invalid .
When the status is displayed as Invalid , click the validity status information button or Invalid in the Application Browser to open the Validity Diagnosis window, which contains information about the cause of the invalid status.
150 EIO0000001114.15
Validity Diagnosis Window - Interface Rules
The following figure shows an example of the Interface Rules tab of the Validity
Diagnosis window.
EIO0000001114.15
5
6
7
3
4
Item
1
2
8
Description
Tab displaying information on interface rules of the instance with invalid Link status.
Tab displaying information on
rules of interface elements, page 152
of the instance with invalid Link status.
By default, this section displays only the elements of the instance for which at least one interface rule is not satisfied.
Path to the element whose interface rules are shown. You can view the element by
editing the instance, page 134
.
Shows for each element, the rules that are defined and their status.
Select the check box to view elements of the instance for which an interface rule is defined independently if the rule is satisfied or not.
Hover with the pointer over Legend to view an explanation of the statuses displayed in the rule columns.
The table describes the content of the Legend tab of the Validity Diagnosis window.
12
13
14
Item
9
10
11
Description
The link is required to satisfy the rule.
Remove the link; otherwise the Status remains Invalid .
The link is made, which satisfies the rule.
No link is made in accordance with the rule.
The link is optional and a link is made.
The link is optional and no link is made.
151
Validity Diagnosis Window - Interface Element Rules
The figure shows the Interface Element Rules tab, which is available if rules exist for elements of an interface. In this example, interface PVRange , which is one of the interfaces shown in the Interface Rules tab has three elements for which a rule is defined but not satisfied.
Linking Instances
Linking Instances That Are Open for Editing
While an instance is open in the Instance Editor , you can add it to and
the Asset Workspace Editor but you cannot create, modify, nor delete links for it.
Naming Rules for Variable Names
The name of the variable that is created by linking two instances needs to satisfy the
for the subsequent generation process to complete successfully.
152 EIO0000001114.15
EIO0000001114.15
Creating Interface Links
To create an interface link between two or more instances by using the Asset
Workspace Editor , proceed as follows.
Step
1
2
3
4
5
6
Action
Right-click an asset workspace and select Edit Workspace .
Result : The asset workspace opens in the editor.
From the Application Browser pane, drag the instances that you want to link to the editor and position them as needed.
Result : The instances are shown in the editor with their interfaces exposed. If links already exist between these instances, they are shown as well.
From either instance, position the pointer over an interface and when the pointer turns into a hand, click and move the pointer away from it while holding down the left mouse button.
Result : A line appears and follows the pointer. You can release the mouse button.
NOTE: Press ESC to return to the normal pointer function.
Move the pointer over the other instance.
Result : Compatible andenabled interfaces of the instance are automatically highlighted and the line snaps to the nearest matching connector.
Click to confirm the connection or move the pointer to another highlighted interface until the line snaps to it.
Result: A click performs the following actions:
• Links the interfaces of both instances with a line.
• Changes the status of the active instance to Valid if the interface rules are satisfied (if applicable).
NOTE: To delete the link, right-click the line and select Delete .
Verify that the link status of the instances is Valid ; otherwise click Invalid in the Link column of the Application Browser or in the Asset Workspace Editor to open the
Validity Diagnosis window and check which links are required. Create these links for the instance status to become Valid .
Changing the Destination of a Link
A destination interface is represented by a male connector .
It is typically the interface with the REF role.
To change the destination of an interface link, proceed as follows.
Step
1
2
Action
Select the link whose destination you want to change.
Result : A black dot appears on the destination connector.
Drag the black dot to a new compatible destination connector of the same or another instance and release the mouse button.
Result : The link is moved to the new destination.
Enabled Interfaces That Cannot Be Connected
The interface of an instance may appear as enabled, unbound, and be compatible but the link does not snap to it. This can be the case if this interface is linked to another instance that is not in the same asset workspace and the interface accepts only one connection at a time.
To view the links that exist for an instance, open it in the Links Editor so that it is the active instance or open the Inspect Instance
.
153
Using the RTNS Interface
Purpose of the RTNS Interface
When no application link is required between instances, you can use the RTNS interface to link them so that they appear in the Linked Production Assets section of the operation client (see EcoStruxure ™ Process Expert, Runtime
Navigation Services, User Guide ).
The cardinality of the interface is n to n and it can be connected only to another
RTNS interface.
Using the RTNS Interface
You can create a link between any instances that exist in the application by using this interface. The procedure to create an RTNS link is the same as the one to create a regular interface link.
NOTE:
• Creating an RTNS link between two instances that are already linked by an application link has no effect.
• Adding or removing an RTNS link between two instances does not change the
of facets of these instances.
RTNS Interface Identifiers and Roles
Representation Identifier
NullInterfaceRoleA
NullInterfaceRoleB
Role
A
B
Example
In the following example, three instances are linked but no link exists between
R1_EMPortM_1 and R1_Motor_1 . To be able to view also information of R1_
EMPortM_1 in the operation client when accessing runtime navigation services from Motor_1 , you can create an RTNS link with R1_EMPortM_1 (shown here as a dotted line for illustration purposes).
154
The following figure shows the result in the EcoStruxure Process Expert operation client after creating the RTNS link when you access runtime navigation services from R1_Motor_1 . Instance R1_EMPortM_1 also appears in the Linked
Production Assets section because of its RTNS link with R1_Motor_1 .
EIO0000001114.15
Managing Application Folders and Instances
Overview
This section describes the Instance Inspector and the functionalities that are available in the software to manage many application folders and instances.
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
Viewing Instance Configuration
Overview
The Inspect Instance command lets you view the entire composition of any instance of the application along with current values of its parameters, elements, functions, and interfaces.
The functionality does not allow you to change values.
Opening the Inspect Instance Window
In the Application Browser , right-click an instance and select Inspect Instance .
EIO0000001114.15
155
Inspect Instance Window
The following figure shows an example of the Inspect Instance window for an instance of the application.
The table describes the various components of an instance that you can view in the left-hand pane of the Inspect Instance window.
Component
Instance identifier
Elements
Functions
Interfaces
Description
Identifier of the instance from which you have opened the Inspect
Instance window.
Elements of the instance grouped by Participant (for example,
Control)
Inside each category, you can view the hierarchy of elements as they are visible in the Instance Editor down to the constituent level.
Binding functions (see EcoStruxure ™ Process Expert, Global
Templates, Reference Manual) that are used by the parent element.
For example, it lets you view information related to the location of an instance in the application, which can be provided by the LocationGet function.
Interfaces that are referenced by the parent element.
For each interface, you can view its identifier, role used by the element, its template identifier, parameters, and their current value.
The table describes the parameter information that you can view in the right-hand pane of the Inspect Instance window. The data pertains to the component that is selected in the left-hand pane of the window.
Header
Name
Description
Type
Value
Description
Name of the parameters of the element grouped by category.
Description of the parameter.
Data type of the parameter.
Current
resolved value of the parameter, page 135
or property.
Changing the Application Hierarchy
Changes Impacting Assigned and Generated Supervision
Facets
When you change the hierarchy of the application, facets of instances that are assigned to a Supervision project and generated are affected when they
156 EIO0000001114.15
equipment based on this hierarchy, page 329
. The table details these changes and their impact.
Change
Moving an application folder to a different parent folder.
Modifying the identifier of a folder.
Moving an instance to a different folder.
Impact
The assignment status of any facets of any instances that the folder and its subfolders contain is set to Out
Of Date .
The assignment status of any facets of the instance is set to Out Of Date .
For information on steps that you need to take to integrate the changes into the system, refer to
Generating Control or Supervision Projects After Changes, page
Copying and Pasting Application Folders and Instances
Description of the Functionality
You can copy and paste instances and application folders:
• Within the application of a system.
• Between applications of different systems.
The Notification Panel provides detailed information about the result of the paste process.
NOTE: Pasting instances affects the
The table describes the effects of the copy and paste functionality when applied to application folders and instances.
Item
Folders and instances
Folder identifier and instance name
Interface links
Other user-defined configuration data
Effect
The copied folder and any instances that it contains, including any subfolders and their contents are pasted.
NOTE:
• When you select the Copy command for a folder, this folder, any subfolders, and any instances they contain are copied. This is the case even if you initially selected, in addition to the folder, only one of the instances or subfolders it contains with the intention to copy only the selected items.
• If you delete an instance or a folder after copying it, you cannot paste it. Also, if you copy a folder containing several instances and you delete an instance in this folder, when you paste the folder, the instance that you deleted is not pasted.
If the folder identifier already exists at the same hierarchical level, or the instance identifier already exists in the target location, the software changes the folder identifier or the instance name by adding an incremental numerical value as suffix; otherwise the identifier or instance name is not changed.
For example, Motor_1 becomes Motor_1_1 , and Folder_1 becomes
Folder_1_1 ).
NOTE: If the
hierarchical naming function, page 141
is activated for an instance, the software changes the instance identifier according to the new location of the instance and the alias of the folders in its path.
Interface links are maintained between pasted instances like they were defined between the original instances if you copy and paste the instances that are linked at the same time.
Interface links can be copied across systems under the same conditions.
The software does not modify the data during the paste process. Therefore, relative expressions that the software has created at the instantiation stage could produce different results when applied to the new location.
Also, when you paste a folder and/or instance in a folder to which you have assigned an
, this value is propagated to the pasted items if they do not have an area value yet and if they are not locked. For details refer to the topic describing the
propagation of the area parameter value, page 127
.
EIO0000001114.15
157
Aborting Paste Tasks
After selecting the Paste command, the abort icon is displayed in the
. Click the icon to cancel the task. No instances and folders are pasted.
Only the user who has selected the command is allowed to abort it.
NOTE: If you are pasting only a few items, the task may complete before you are able to click the icon.
Copying and Pasting Instances
To copy and paste instances, proceed as follows.
Step
1
2
3
4
Action
Expand the folder that contains the instances that you want to copy.
Select the instances.
You can make multiple selections within one folder by holding:
• The Shift key for contiguous instances.
• The Ctrl key if instances are non-contiguous.
Right-click a selected instance and select Copy .
Right-click the destination folder and select Paste .
You can select multiple folders as targets.
NOTE: If the target is not valid for pasting, the command is not available. Also, you cannot paste in the Application Browser in grid view mode.
Copying and Pasting Application Folders
To copy and paste application folders, proceed as follows.
Step
1
2
Action
Right-click the folder that you want to copy and select Copy .
You can make multiple selections within the Application Browser by holding the Ctrl key.
Right-click the destination folder and select Paste .
You can select multiple folders as targets.
NOTE: If the target is not valid for pasting, the command is not available. Also, you cannot paste in the Application Browser in grid view mode.
Moving Application Folders and Instances
Overview
You can move instances and application folders:
• Within the application of a system.
• Between the applications of different systems.
Both actions change the
structure of the application, page 116 . The software
displays a notification informing you of the possible impact on the assignment status of already assigned facets before executing the move operation.
Once the move operation is completed, if the software had to make changes to folder and/or instance identifiers to satisfy naming rules, it displays the Move
Summary
to inform you of the changes.
158 EIO0000001114.15
EIO0000001114.15
NOTE:
• You cannot move instances within a folder.
• You can change the position of folders
without modifying the hierarchy of the application, page 161 .
Moving Folders and Instances
By using the Application Browser pane, you can select a combination of folders and instances to move them at once. This is possible in tree view mode only.
When you move a folder, this folder, any subfolders, and any instances they contain are moved.
This is the case even if you initially selected, in addition to the folder, only one of the instances or subfolders it contains with the intention to move only the selected items.
NOTE:
• You can make multiple selections by holding the Shift key for contiguous and the Ctrl key for non-contiguous items.
• If sorting and/or filters are applied, they are also applied to instances and folders that you have moved.
Effects of the Move Operation
The table describes the effects of the move operation when applied to application folders and instances.
Item
Folders and instances
Folder identifier and instance name
Interface links
Other userconfigured properties
Effect
Moves the folder and any instances that it contains, including any subfolders and their contents.
If the folder identifier already exists at the same hierarchical level, or the instance identifier already exists in the target application, the software changes the folder identifier or the instance name by adding an incremental numerical value as suffix; otherwise the identifier or instance name is not changed.
For example, Motor_1 becomes Motor_1_1 , and Folder_1 becomes Folder_1_
1 ).
NOTE: If the
hierarchical naming function, page 141
is activated for an instance, the software changes the instance identifier according to the new location of the instance and the alias of the folders in its path.
Interface links are maintained between instances if you move the instances that are linked at the same time.
NOTE: Moving Interface links across systems is supported.
The software does not modify the data during the move process. Therefore, relative expressions that the software has created at the instantiation stage could produce different results when applied to the new location.
Also, when you move a folder and/or instance to a folder to which you have assigned an
area value, page 126 , this value is propagated to the moved items
if they do not have an area value yet and if they are not locked. For details refer to the topic describing the
propagation of the area parameter value, page 127 .
Moving Instances
To move instances, proceed as follows.
Step
1
2
Action
Expand the folder that contains the instances that you want to move.
Select the instances.
You can make multiple selections by holding the Shift key for contiguous and the Ctrl key for non-contiguous instances.
Result : The selected instances are highlighted.
159
Step
3
4
5
Action
NOTE: To move instances across systems, use
two workspaces, page 79 ; one for
each application.
Drag one of the highlighted instances to the target application folder.
Result : The identifiers of the instances you are moving appear in a tooltip.
Release the mouse button.
Result : The software:
• Moves the selected instances to the new location. When no sorting is applied, instances are inserted in ascending alphabetical order among existing instances.
• Displays the Move Summary window if the software has performed a change to comply with applicable naming rules.
Close the Move Summary window.
Moving Application Folders
To move application folders, proceed as follows.
Step
1
2
3
4
Action
Select the folders that you want to move.
You can make multiple selections by holding the Shift key for contiguous and the Ctrl key for non-contiguous folders.
Result : The selected folders are highlighted.
NOTE: To move folders across systems, use
; one for each application.
Drag one of the highlighted folders that you want to move to the target.
Result : The identifiers of the folders you are moving appear in a tooltip.
Release the mouse button.
Result : The software:
• Moves the folders and their contents to the new location. When no sorting is applied, folders are added at the end of existing folders.
• Displays the Move Summary window if the software has performed a change to comply with applicable naming rules.
Close the Move Summary window.
Move Summary Window
The following figure shows an example of the Move Summary window.
160
Path Indicates the path to the folder or instance location after the move.
Description Indicates the name change that the software has performed on the folder and/or instance during the move.
EIO0000001114.15
Changing the Position of Folders Without Changing the
Hierarchy
You can change the position of folders inside the structure without modifying the hierarchy of the application. You can do this one folder at a time.
Step
1
2
3
Action
Verify that no sorting is applied in the Application Browser pane of the Application
Explorer and that tree view mode is selected.
In the Identifier column, start dragging a folder along the folder structure until one of the following messages appears in a tooltip:
• Move X before Y .
• Move X after Y
Where:
• X is the identifier of the folder that you are moving.
• Y is the identifier of the target folder.
Release the mouse button.
Result: The software relocates the folder to the selected position.
NOTE: If you release the mouse button while only the identifier of the folder that you are moving appears in the tooltip, you are
changing the hierarchy of the folder structure, page 158 .
Updating and Replacing Templates of Instances
Overview
In the Application Browser , you can perform the following actions on the template that is used by an instance of the application. The working principle of both commands is the same. The difference resides in the choice of templates provided by each command:
Update Template
Replace Template
Lets you update the template that is used by the instance with the latest available version.
When you select the command from a folder, the command applies to any instance that is contained in the folder and any subfolders, and for which a template of a newer version is available.
Lets you replace the template that is used by one or more instances with another version of this template or a different template.
NOTE: The Update Template command is also available in the Topological
Explorer for certain
topological entities, page 407 .
Updating Versus Replacing Templates
The following examples are given to illustrate the difference between the two commands.
Update Template command:
• The following templates are available in the Global Templates library: $Motor
(2.0.0) , $Motor (2.0.1) , and $Motor (2.0.2)
• Instance Motor_1 uses template $Motor (2.0.0)
• The command lets you update the template that is used by Motor_1 with
$Motor (2.0.2) only (latest version).
Replace Template command:
• The following templates are available in the Global Templates library: $Motor
(2.0.0) , $Motor (2.0.1) , and $Valve (3.0.0)
• Instance Motor_1 uses template $Motor (2.0.1)
• The command lets you replace the template that is used by Motor_1 with either:
EIO0000001114.15
161
◦ $Motor (2.0.0) : Same template, any available version.
◦ $Valve (3.0.0) : Different template.
Using the Commands on a Folder
When you select the Update Template or Replace Template command at the folder level, the command is performed on this folder, any subfolders, and any instances they contain.
This is the case even if you initially selected, in addition to the folder, only one of the instances or subfolders it contains with the intention to perform the command only the selected items.
Accessing the Commands
Update Template
Replace Template
Right-click one instance, a selection of several instances in the same or in various folders, the root folder, or any application folder, and select the command.
The command executes only if a newer version of the template that is used by the instance is available in the Global Templates library.
Right-click one instance or a selection of several instances in the same folder, and select the command.
Description of the Functionality
The software proceeds with the update or replacement of a template in the following order:
• The template that is associated to the instance is updated or replaced.
• Interface links are processed.
The following conditions need to be satisfied:
• The template or template version that you want to use must be available in the Global Templates library.
• It needs to have the usability state Approved (see EcoStruxure ™ Process
Expert, Global Templates, Reference Manual) or Deprecated .
NOTE: Refer to
.
The table describes the effects on the various template components when you update or replace the template that is used by an instance.
Identifier in new template (1) Effect Template component
Element The identifier of the element and its path in the composition of the template is the same as in current template.
The identifier of the element does not exist in the current template or the path to the element is different.
• The element is maintained or updated. If updated, the status of the corresponding facet is set to Out Of Date if the facet was generated.
Refinements that you have made are preserved if the element that creates the facet encapsulates the same constituents.
• The element selection that you have made in the current template is applied to the new template.
For example, in the current and the new template, the Interlocks element is at the path Control\Interlocks. If it was selected in the current template, it is selected in the new template.
• If the identifier of the template used by the corresponding facet ( Facet
Template column) is different, the status of the facet is set to Out Of
Date if the facet was generated.
NOTE: If you replace a control module template (highest level template) by one that has a different identifier but an identical composition, no changes are made to the instance, except for the template identifier.
The element is added and the corresponding facet is created.
An optional element that is not part of the current template keeps its default value (selected or cleared).
NOTE: Any element of the current template whose identifier does not exist in the new template or whose path is different is removed.
162 EIO0000001114.15
Template component
Parameter value
Interface link
Identifier in new template
Is not in current template
–
(1)
Is same as in current template
Effect
Explicitly defined parameters of the current template keep their respective value in the new template.
New parameters that are not part of the current template keep their default value.
The software re-establishes interface links that are valid after the template update or replacement in their original configuration.
The software discards interface links that are not valid after the template update or replacement because, for example:
• The cardinality of the interface role is not respected.
• A linked element does not exist anymore.
• An incompatibility of the type and/or role of the interface.
(1) The term new template refers to either a different version of the same template or a different template
This example illustrates the impact of a template update operation on generated
Control facets of an instance. In this scenario, instance Valve_1 uses template
$Valve version 1.3.9. The optional Maintenance service is selected at the instance level.
The following figure shows the composition of the template as it appears in the
Instance Editor . Elements appear in the Name column and the identifier of the template that is used by the corresponding facet in the Template column.
The following figure shows the Control facets ( Facet column) of instance Valve_1 , which are assigned to a section of a Control project. By relating this information to the one shown in the Instance Editor , you can see, for example, that element
LowLimitSwitch creates facet Valve_1_ZSL by using template $DISignal_UL .
This information is also visible at a glance in the View Assignments
EIO0000001114.15
163
$Valve 1.3.9 is updated to version 1.3.10 by using the Update Template command.
$Valve 1.3.10 has a modified Interlocks service, which is provided by the modified CONDSUM1_UL template. All other elements are identical.
164
The result of the template update operation shows that one facet has a modified assignment status. All facets remain generated.
1 The facet created by the CONDSUM1_UL template ( Interlocks service) has a status of Out Of Date because the already generated constituents (from $Valve
1.3.9) are not consistent with the constituents of the modified CONDSUM1_UL template anymore. Generating the section injects the constituents coming from the modified CONDSUM1_UL template into the logical Control Participant project.
2 The optional Maintenance service remains selected after the template update because it is also available in the latest version of $Valve .
This example illustrates the impact of a template replacement operation on generated Control facets of an instance. In this scenario, instance Motor_1 uses template $Motor .
$Motor has an Interlocks service provided by the CONDSUM1_
UL template. The optional Maintenance service is selected at the instance level.
EIO0000001114.15
$Motor is replaced with $Valve by using the Replace Template command.
Compared to $Motor , $Valve has a modified Interlocks service, which is provided by the modified CONDSUM1_UL template (located at the same path). The
Maintenance service is identical in both and provided by the same template at the same path. Their other elements are either different (for example, $CONDSUM_
UL) or located at a different path (for example, $DEVCTL_UL) in the composition of the control module template.
EIO0000001114.15
The result of the template replacement operation shows that several facets have a modified assignment status.
1 These two facets are deleted because in $Valve , $DEVCTL_UL is at a different path and $CONDSUM_UL does not exist. Generating the section removes the corresponding constituents from the logical Control Participant project.
2 The facet providing the Interlocks service is set to Out Of Date because Valve contains this service (provided also by $CONDSUM1_UL ) but a modified version of it. Already generated constituents (from $Motor ) are not consistent with the constituents of the modified CONDSUM1_UL template anymore. Generating the section injects the constituents coming from the modified CONDSUM1_UL template into the logical Control Participant project.
3 The optional Maintenance service is not affected because it is identical for both templates. The Instance Template column indicates that the facet is now created by the Valve template.
165
166
In the Assignment Editor , you can see the facets that are specific to Valve and that have been created for the Motor_1 instance. You need to assign these to the section as needed. These facets have the Candidate status. By default, the software
assigns them automatically, page 284 .
NOTE: The same that is described in the above examples for Control facets also applies to Supervision facets of the instance.
Updating or Replacing Templates of Linked Instances
When instances are linked by interface links ( Asset Workspace Editor ),
update the templates of these instances at once, page 167
to maintain the links.
Updating or Replacing Templates Containing a New Version of a Type
When you update or replace the template used by an instance and the Control facets that are referenced by the instance are already generated, if the new template that you have selected contains a version of the type that is different from the one that has been generated, the software requires that you select the version to be used when you generate the Control Participant project. In certain cases, generation may not be able to complete successfully. For details, refer to the topic describing the
selection of type versions during generation, page 305
.
NOTE: To view the version of a type that is used by a facet, edit the facet encapsulating the type by using the Global Templates explorer, select the element that represents the type, and click Templatizer . The version of the type is indicated in the Global Types section of the Select Variables window
(for example, DEVCTL 0.01.
Validating Instance Identifiers
When you perform a template replacement operation, the software verifies if the result of the operation satisfies the uniqueness requirement for instance identifiers. If it does not, it displays the Replace Template Summary dialog box, which indicates which instance creates a duplicate identifier, and cancels the replace operation.
This can be the case if:
1. Two instances use a different template but have the same identifier.
2. You replace one of the two templates with the same template that the other instance uses.
For example:
• The application contains two instances:
◦ Valve_1 , which uses template $HandValve
◦ Valve_1 , which uses template $Valve
• If you replace template $HandValve by template $Valve (any version), the two instances use the same template and have the same identifier. This is not allowed.
EIO0000001114.15
EIO0000001114.15
NOTE: When replacing a template creates an element with the same identifier as the element of an existing instance, you can still proceed with the template replacement but the Data status of the instance is set to Invalid .
For example:
• The application contains two instances:
◦ Pump_1 , which uses template $Motor
◦ Pump_1 , which uses template $HandValve
• If you replace template $HandValve by template $Valve (any version), although the two instances do not use the same template, they have the element Logic in common, which has the same identifier ( Pump_1_
DEVCTL ) in both instances because both instances have the same identifier. This is not allowed.
Updating the Template of One Instance
To update the template that is used by one instance, proceed as follows.
Step
1
2
Action
Right-click the instance that you want to update and select Update Template .
Result: The Update Template dialog box opens. It shows the latest version of the template that is available for the update.
Click OK .
Result: The software:
• Updates the template that is used by the selected instance with the latest version of the same template.
• Displays the version of the template that is used by the instance after the update in the Version column.
• Displays the result of the update process in the Notification Panel .
NOTE: Click Cancel to close the dialog box without updating the template.
NOTE: To revert to an earlier version of a template, use the Replace
Template command.
Updating the Templates of Several Instances
To update the templates of several instances of the application at once, proceed as follows.
Step
1
2
3
Action
Right-click the root folder of the application and select Update Template .
Result: The Update Template dialog box opens, which:
• Lists the templates, which are used by instances of the application for which a template of a later version is available. It indicates the current version of the template and the latest version that is available for the update.
• Indicates, for each template, the instances that are using the template with an indication of the location of the instances ( Path) .
Select the instances that you want to update:
• Instance by instance.
• By template.
• Through a combination of both.
Click OK .
Result: The software:
• Proceeds with the update of the template that is used by the selected instances.
• Displays the version of the template that is used by each instance after the update in the Version column.
• Displays the result of the update process in the Notification Panel .
NOTE: Click Cancel to close the dialog without updating the templates.
167
NOTE: If you use a filter in the Name column of the Update Template dialog box and as a result, not all the instances that you had selected are displayed, the update operation is still performed on the entire selection of instances.
Replacing Templates of Instances
To replace the template that is used by one or more instances, proceed as follows.
Step
1
2
3
4
5
Action
Select one or more instances and/or one or more folders.
Result: The software highlights the selected items.
Right-click a highlighted item and select Replace Template .
Result: The Replace Template dialog box opens.
Click the Select Template list.
Result: The software displays the list of templates that are available for the replace operation.
Select the template that you want to use by scrolling or entering a keyword in the field of the menu.
To search by entering the first letter of the template identifier, enter also the $ prefix for
Schneider Electric templates (for example, $m ).
Click OK .
Result: If the result of the replacement operation does not satisfy the identifier uniqueness requirement, the software displays the Replace Template Summary dialog box and cancels the replace operation.
If no conflict is detected, the software:
• Closes the dialog box and replaces the template that is used by the instances with the template that you have selected.
• Displays the identifier and the version of the template used by the instances respectively in the Template and Version columns.
• Displays the result of the replace process in the Notification Panel .
NOTE: Click Cancel to close the dialog without replacing the template.
NOTE: If you use a filter in the Instance column of the Replace Template dialog box and as a result, not all the instances that you had selected are displayed, the replace operation is still performed on the entire selection of instances.
Exporting and Importing Application Objects to CSV and XML
Formats
Overview
The export and import functionality lets you create comma-separated value (CSV) or XML files and import them into the application of the same or another system.
This allows you to do the following:
• Move or copy the entire application or a selection of folders,
asset workspaces (CSV only), page 171
, and instances to another system.
• Perform bulk processes such as creating, modifying and/or deleting instances, folders, asset workspaces (CSV only), and interface links by editing the exported file.
This topic describes how to export objects, edit the export file to perform the required changes, and import it.
168 EIO0000001114.15
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
Exporting Folders and Instances to CSV and XML Formats
Overview
You can export application folders, instances, and interface links by using the
Export command of the Application Explorer .
The application objects and their respective configuration parameters are saved to an export file in
value (CSV) or XML format.
For example, you can use the export file to
the application into another system while modifying some parameters, which helps avoid having to create it from scratch. Also, you can use it to restore instances after deleting them or to restore them to an earlier state.
NOTE: You also need to
that are used by the instances that you are exporting if the same version of template is not present in the Global Templates library of the target system at the time of import.
Instances whose template is not present cannot be imported.
Good Practices
• If you intend to edit the export file, try to limit your export selection to the objects that you want to modify or delete, for example, by using
in the Application Browser . It reduces the steps to manage unwanted objects during import and speeds up the process.
• If you want to create instances, export, at least, one instance that uses the same template. If you want to create interface links, export, at least, two instances that are linked. This lets you use the data as model. For example, you can copy and paste it and modify only necessary location, element, and/ or parameter values.
Export Format Selection
The
and
export files contain similar information and let you perform the same actions.
Data in CSV format can appear more comprehensible and easier to manage by using a spreadsheet editor because of its user-friendly, tabular presentation. Also, it facilitates the integration of existing data, such as an asset list, depending on their format.
Exporting to XML may be preferred by users who are familiar with the use of structured data and more powerful XML editors.
NOTE: You cannot update existing interface links by using the XML format.
Invariant Culture
The software uses the
to format parameter values independently of the language setting that is used on the computer on which you create the export file.
For example, a decimal value that appears as 5,5 (comma separator) in the
Instance Editor because of your regional settings appears as 5.5 (dot separator) in the export file.
EIO0000001114.15
169
170
Software Version Compatibility
You can import into a system instances that were exported from an earlier version of the software.
Some restrictions apply, page 192
.
Object Selection
You can select the following objects to export them:
• One or several instances: Exports the data pertaining to the selected instances and their location in the folder structure of the application. You can select individual instances located in various folders and export them at once.
• One or several application folders: Exports the data pertaining to the selected folders, the instances contained in the folders, and in any subfolders.
• The root folder of the application: Exports any application folders and instances of the system.
An interface link is exported only if both linked instances are exported.
NOTE: When you select the Export command for a folder, this folder, any subfolders, and any instances they contain are exported. This is the case even if you initially selected, in addition to the folder, only one of the instances or subfolders it contains with the intention to export only the selected objects.
Aborting Export Tasks
After confirming the export by clicking Save in the Save As dialog box, the abort icon is displayed in the
notification panel, page 54 . Click the icon to cancel the
task. The export file is not created.
Only the user who has selected the command is allowed to abort it.
NOTE: If you are exporting only a few objects, the task may complete before you are able to click the icon.
Creating the Export File in CSV or XML Format
To export application objects, proceed as follows.
Step
1
2
3
4
Action
In the Application Browser , select the objects that you want to export.
Use
to facilitate the selection.
Right-click your selection and select Export .
Result: The Export dialog box opens.
Select the location, file name, and format for the export file.
Click Save .
Result:
• The export file containing the selected objects is created.
• A summary of the exported objects is displayed in the notification pane.
NOTE: If any object that you have selected for export is open in an editor (for example, the Instance Editor ), accessed for an assignment, update, or replace operation, or if its Properties tab is open, you cannot create the export file.
EIO0000001114.15
Exporting Asset Workspaces to CSV Format
Overview
You can export asset workspaces and the instances that belong to them by using the Export command.
The application objects and their respective configuration parameters are saved to an export file in
comma-separated value (CSV), page 175
format.
NOTE: You also need to
that are used by the instances that you are exporting if the same version of template is not present in the Global Templates library of the target system at the time of import.
Instances whose template is not present cannot be imported.
Object Selection
You can select the following objects to export asset workspaces:
• The root node of the Asset Workspace pane: Exports the existing asset workspaces and the instances that belong to them.
• One or several asset workspaces: Exports the workspaces and the instances that belong to them.
• The root folder of the application: Exports any application folders, asset workspaces, and instances of the system.
Creating the Export File Containing Asset Workspace Data
For information on how to create the export file, refer to the topic describing the
export of folders and instances, page 169
.
CSV Application Export File
Export File Description
When you export application objects to
format
(CSV), two files are created.
File
Application export file
Application interface data supporting file
Default file name
<System identifier>
<System identifier>_Pending
Interfaces where _Pending Interfaces is appended to the file name once the file is created.
Content and purpose
Data of the folders, instances, interface links, and asset workspaces that you have exported.
The data is organized in five types of groups.
You need to
of this file to create, modify, or delete application objects.
Data on application interfaces that the exported instances expose and that are not connected. It includes interfaces that are disabled.
The data is organized by instance name.
It helps you edit data of the
InterfaceLinks group in the application export file by providing the necessary data of each interface that you can connect.
The following table describes the grouping of data in the application export file.
Each group has a group header and a header row, which describes the data of objects.
EIO0000001114.15
171
172
Group header
Folders
TemplateIdentifier=<Template ID>
Version=<Value> where:
• <Template ID> is the identifier of the template that is used by the instance.
• <Value> is the template version.
Example :
TemplateIdentifier=$Motor Version=
3.1.0
InterfaceLinks
Description
Groups that contain
.
More than one group exists when you export folders that have a different number of parameters as part of the optional folder properties.
The number of columns depends on the folder configuration. A column with its header exists for each system parameter and each configured optional parameter.
NOTE: A group header and its header row appear only if the export file contains folder data.
Groups that contain
There are as many groups as templates and versions used by exported instances.
The number of columns depends on the instance configuration. A column with its header exists for each element and parameter of the instance.
NOTE: A group header and its header row appear only if the export file contains instance data.
Workspaces
Group that contains the
data of interface links, page 176 ,
which link exported instances.
The number of columns and their headers are fixed.
NOTE: The group and its header row are always present.
Group that contains the
data of the exported asset workspaces, page 176
.
NOTE: The group and its header row are always present.
WorkspaceIdentifier=<Asset workspace identifier>
Example :
WorkspaceIdentifier=AssetWorkspace_
1
Group that contains the data of instances that belong to an asset workspace.
There are as many groups as exported asset workspaces.
NOTE: The group and its header row are present even if the exported asset workspace contains no instance.
Example of CSV Export Files
The following example shows two instances, which have been linked by an interface link.
EIO0000001114.15
The following figure shows a partial view of the resulting export file when you export folder Cell to CSV format.
2
3
4
5
Item
1
6
7
Description
Export file information that is added by the software.
Group headers.
Header rows.
Element of the instance and its selection state.
Parameter of the instance and its configured value.
Parameters appear right after their parent element.
Parameter of the instance for which no value is configured.
Data rows of exported objects (one row per object, such as a folder, an instance, or an interface link).
The following example shows two asset workspaces that exist in System_2 .
AssetWorkspace_1 contains two linked instances and AssetWorkspace_2 contains none.
EIO0000001114.15
173
The following figure shows the workspace related portion of the resulting export file when you export System_2 to CSV format either from the root node of the
Application Browser or the Asset Workspace .
2
3
4
Item
1
Description
Group headers.
Header rows.
Rows containing data of the exported asset workspaces.
Rows containing data of the instances that belong to each exported asset workspace.
NOTE: The data of their interface links and configuration parameters appears in their respective groups in the same export file.
The following figure shows a partial view of a supporting file that is created in addition to the actual export file.
Editing the CSV Application Export File
Overview
By editing the application export file (.csv), you can create, update, and/or delete application objects.
Various rules and requirements apply when you open and edit CSV export files.
They are described in this topic.
You can use the supporting file ( *_PendingInterfaces.csv
) to help with the editing of interface link data.
174 EIO0000001114.15
The software applies the changes when you
import the edited CSV file, page 191
into the application of the system. At that time, you have the possibility to review and modify the list of imported objects (except interface links).
Good Practices
• Before editing an application export file, create a copy of it. If needed, it lets you restore the original application.
• Edit only an up-to-date export file to help avoid data conflicts when importing.
• Carefully remove from the file objects that are not impacted by the import, for example, instances that you are not updating or deleting.
• When you use data from the supporting file to create or update interface links, cut the data rather than copying it to help avoid connecting the same interface several times.
The other way around, add to the supporting file data of interfaces that you are disconnecting.
Step
1
2
3
4
5
Opening the CSV File by Using a Spreadsheet Editor
When you open a CSV export file by using a spreadsheet editor, some instance parameter values (for example, durations with millisecond values, certain special characters, or strings starting with - (hyphen)) may get modified by the editor.
So that these values remain unchanged, you first need to import the data into a blank workbook in Unicode (UTF-8) format.
Follow this procedure. Microsoft ® Excel ® is used as an example. Menu items and dialog box names may vary depending on the version.
Action
Open a blank workbook.
In the Data menu, select to import from text or CSV.
In the Import Text File dialog box, select the exported CSV file.
Select the following attribute values for the import of data:
• File origin: 65001 : Unicode (UTF-8)
• List separator (delimiter): Comma
• Format for all columns (data type): Text (1)
• Use First Row as Header (1) (depending on version): Open the menu and select this setting even if it is already selected by default.
Load the values to the blank workbook.
NOTE: After loading is completed, the first row of the CSV file must start with ;Export Version=<Software Version> . You may see additional text in columns E and higher of the first row (for example, Column1 , _1 ). This text is treated as
and ignored during import.
The following example shows an extract of a CSV export file after selecting Use First Row as Header and loading values to the blank workbook.
6 Save the workbook in CSV UTF-8 (comma delimited) format (keep saving in this format when you edit the file).
(1) You may need to edit the file during the import process to access the attribute.
Setting the List Separator Format
CSV export files use the comma as list separator (delimiter) independently of the setting that is in effect on the computer on which the file is created.
EIO0000001114.15
175
Type
Decimal separator
Time
Date
Date Time
Duration
If the format of the list separator on the computer is different from comma, data will not be displayed correctly when you open the export file by using a spreadsheet editor.
To verify the setting and change it to comma if necessary, open the Windows ®
Control Panel and click Clock and Region > Region . In the Formats tab, click
Additional settings...
.
NOTE: For information on how to use commas in values of string data types in the CSV file, refer to the topic describing
Using the Invariant Culture
Use the invariant culture to modify or add parameter values in the application export file.
If required, during import the software converts the format according to the language setting that is used on the target computer.
The table describes the formats of the invariant culture that are used in the export file.
Format x.y
hh:mm:ss mm/dd/yyyy mm/dd/yyyy hh:mm:ss
DD.hh:mm:ss.ms
Example
2.5
14:30:00
11/20/2014
11/20/2014 14:30:00
10.12:30:10.15 translating into 10 days
12 hours 30 min 10 sec 15 msec
Application Export File Content Requirements
This topic describes the columns that appear in the each type of group and the requirements for each one. Use this information when you edit existing data, add columns, and/or add entire groups. For details on the format of the group headers, refer to the topic describing the
.
176 EIO0000001114.15
Header
$Action
$InstanceName
$Identifier(Non_Editable)
$IsHierarchical
EIO0000001114.15
Folders
. The information applies to each group that appears in the file or that you add.
Header
$Action
$Location
Description
Action that is performed on the folder during import.
Path to the folder in the application starting from the system root folder.
Example :
Root\Site\Area\Unit_A
NOTE: The name of the
is replaced by Root .
Requirement
Possible values (not case-sensitive):
• Create (default)
• Update
• Delete
• Blank:
◦ Creates the folder if it does not exist yet.
◦ Updates the folder if it exists.
A column with this header and a valid value in each row are required.
The path must exist in the application or be created by the import.
For folders whose parent is the system root folder, enter Root .
$Identifier
$Alias
Folder identifier.
NOTE: You cannot update the identifier of a folder through import.
Folder
A column with this header and a valid value in each row are required.
Column and value are optional.
If a row contains data, it must be valid.
$Description Folder description.
$Area Folder
NOTE: If the value is
inherited from a parent folder, page 127 , it does
not appear in the export file.
Parameter x .$Identifier Identifier of the folder
Parameter x
$Description
Parameter x
.
.$Value
Description of the folder parameter.
Value of the folder parameter.
Column and value are optional.
If a row contains data, it must be valid.
NOTE: The numbering of folder parameters (x) corresponds to the order (top to bottom) in which parameters appear in the properties of the folder when no sorting is applied.
TemplateIdentifier
for instances. The information applies to each group that appears in the file or that you add.
Description
Action that is performed on the instance during import.
Instance
.
.
The value is used to identify the instance or calculated by the software in case of instance creation.
Hierarchical naming function, page 141
.
Requirement
Possible values (not case-sensitive):
• Create (1) (default)
• Update
• Delete
• Blank:
◦ Creates the instance if it does not exist yet.
◦ Updates the instance if it exists.
A column with this header and a valid value in each row are required.
A column with this header is required and:
• To create an instance, the value can be left blank.
• To update or delete an instance, the value must be valid.
Column and value are optional.
Possible values:
177
Header
$Location
$Description
$Area
<Element path>.Enabled
Parameter.<parameter full path>
Description
Path to the instance in the application.
Example :
Root\Site\Area\Unit_A
NOTE: The name of the
is replaced by Root .
Instance description.
Instance
.
NOTE: If the value is
inherited from a parent folder, page 127 , it does not
appear in the export file.
A column exists for each service ( page 172
the
The instance identifier is excluded from the
Example :
Control. Running.Enabled
) of the instance as they appear in
Instance Editor element path.
.
For the Running service that belongs to the
Control element, the column header is:
A column exists for each
that is featured by the instance, including parameters of
disabled services (elements), page 182
and not configured parameters.
Example :
For the DISignalName parameter of the
Running service, the column header is:
Parameter.Control. Running.DISignalName
Requirement
• True
• False
• Blank (or not present):
◦ Equals true for an instance that is created.
◦ Keeps the configured value for an existing instance.
A column with this header and a valid value in each row are required.
The path must exist in the application or be created by the import.
Column and value are optional.
If a row contains data, it must be valid.
Column and value are optional.
Possible values (not case-sensitive):
• True: The service is enabled.
• False: The service is disabled.
• Blank:
◦ Equals false for an instance that is created.
◦ Keeps the configured value for an existing instance.
Mandatory elements (whose check box cannot be cleared in the Instance Editor ) are identified with (Non_
Editable) in the header. If you set the value to false, it is not considered during import and the element remains enabled.
Column and value are optional.
If a row contains data, it must be valid.
When you edit a parameter, verify that the
to which it belongs is set to true; otherwise, the parameter value is not applied during import. This rule does not apply to parameter values of mandatory elements, which are applied even if the element is set to false in the CSV file.
NOTE: To view the hierarchy of elements and parameters of an instance, use the Instance Editor or the View Instance
.
NOTE: For parameters of the
enumerated data type, page 186 , the name is exported as value. For
example, if the parameter
that is configured in the Instance Editor is Operator (2) , the exported value is Operator . To edit the value, you can enter either the name of the enumerator or the associated integer (for example, 3 for an enumerator that is Supervisor (3) ).
(1) Instances with action set to create and that you do not want to import can be unselected during
InterfaceLinks
178 EIO0000001114.15
Parameter
$Action
Description
Action that is performed on the interface link during import.
$SourceLocation Path to the instance that is the source of the link in the
Application Explorer .
The name of the
is replaced by Root .
Example :
For instance Motor_1 of System_1 that is located in Folder_2 , which is a subfolder of Folder_1 , the value is Root\Folder_1\Folder_2 .
$SourceInstanceName Value of the
of the instance that is the source of the link.
$SourceInstance
TemplateIdentifier
$SourceInterfacePath
Identifier of the template that is used by the instance, which is the source of the link.
Path to the source interface in the composition of the instance.
Example :
In the following sample instance, the value for interface ZSHPOS is
Control\Motor\Logic .
Requirement
Possible values (not casesensitive):
• Create (default)
• Update (1)
• Delete
• Blank:
◦ Creates the link if it does not exist yet.
◦ Updates (1) the link destination if the link exists.
A column with this header and a valid value in each row are required.
A column with this header and a valid value in each row are required.
NOTE: For RTNS interfaces, the column is optional and does not contain values.
EIO0000001114.15
$SourceInterfaceIdentifier
$DestinationLocation
Identifier of the interface that is the source of the link.
Path to the instance that is the destination of the link in the
Application Explorer .
The name of the
is replaced by Root .
A column with this header and a valid value in each row are required.
NOTE: Refer to the description of RTNS interfaces for information on their specific
A column with this header and a valid value in each row are required.
$DestinationInstance
Name
Value of the
of the instance that is the destination of the link.
179
180
Parameter
$DestinationInstance
TemplateIdentifier
$DestinationInterface
Path
Description
Identifier of the template that is used by the instance, which is the destination of the link.
Path to the destination interface in the composition of the instance.
Example :
In the following sample instance, the value for interface BoolVar is empty (blank) because it has no parent element.
Requirement
A column with this header and a valid value in each row are required.
NOTE: For RTNS interfaces, the column is optional and does not contain values.
$DestinationInterface
Identifier
$NewDestinationLocation
$NewDestinationInstance Name
$NewDestinationInstance
TemplateIdentifier
$NewDestinationInterface Path
$NewDestinationInterface Identifier
Identifier of the interface that is the destination of the link.
The description is the same as for the $Destination* parameters but the data applies to the new destination interface of the same or another instance.
The parameters are empty by default.
A column with this header and a valid value in each row are required.
NOTE: Refer to the description of RTNS interfaces for information on their specific
.
Columns with these headers are required. Rows can be left blank.
The columns must contain a valid value only when you
change the destination, page 183
of an existing link.
(1) You can only
change the destination, page 183
of an existing link by using the Update command.
Workspaces
.
Header
$Action
$Location
$Identifier
Description Requirement
Action that is performed on the asset workspace during import.
Path to the asset workspace in the Asset Workspace
Root by default.
pane.
Possible values (not case-sensitive):
• Create (default): Creates the asset workspace or updates an existing one based on the information in the
WorkspaceIdentifier=<Asset workspace name> group.
• Delete: Deletes the workspace only. Does not delete from the application the instances that belong to it nor their interface links.
• Blank: Same as Create .
A column with this header and Root as value in each row are required.
Asset workspaces can only be located at the system root node level.
Asset workspace identifier.
NOTE: You cannot update the identifier of an asset workspace through import.
A column with this header and a valid value in each row are required.
EIO0000001114.15
WorkspaceIdentifier
group, page 171 . The information applies to each group that
appears in the file or that you add.
Header
$Action
$InstanceLocation
$InstanceName
$InstanceIdentifier
$TemplateIdentifier
$Position
Description
Action that is performed on the instance in the context of the asset workspace during import.
Path to the instance in the application.
Requirement
Not editable.
To remove an instance from an asset workspace, delete the row.
To add an instance, add a row and enter the required information in each column.
A column with this header and the same value as in the $Location column of the TemplateIdentifier group for this instance are required.
Name of the instance.
Identifier of the instance.
Identifier of the template that is used by the instance.
Position in pixels of the top left corner of the instance representation in the asset workspace .
A column with this header and the same value as in the $InstanceName column of the TemplateIdentifier group for this instance are required.
A column with this header and the same value as in the $Identifier column of the TemplateIdentifier group for this instance are required.
A column with this header and the same template name as in the
TemplateIdentifier group header for this instance are required.
For example, $AnalogInputGP if the header for this instance is :
TemplateIdentifier=$AnalogInputGP
Version=1.0.131
.
Two comma-sperated values indicating the position on the X and Y axis respectively.
For example, 0,0 positions the instance along the left and top borders of the asset workspace.
EIO0000001114.15
181
182
Editing Rules
The table indicates the rules that apply when you edit a CSV application export file.
Item
Header of a group
First header of a header row
Headers of noneditable data
Rows of object data
Empty rows
Comment rows
Order of columns
Empty columns
Interface links
List separator
Values
Rule
Must start with a colon.
You can remove a group header and its header row if the group contains no data.
You can change the order of groups.
Headers of data that does not need to be edited or that is ignored during import are identified by the software with the Non_Editable suffix.
Refer to the
You can delete the row of an object if you do not want to import it or modify it through import.
Can be added anywhere.
Can be added anywhere and must start with a semi-colon.
Comments are ignored during import.
Can be changed within a group given the first header of the row starts with a colon.
Can be added after the first column.
For any
, the data of the linked instances must be included in the application export file even if the instances already exist in the target application.
Only
is accepted.
Use the
To use commas or quotation marks in values of string data types when you edit the file by using a text editor, for example, Notepad, follow these rules:
Expected value after import
Motor, Pump
Motor”Pump
Value to be entered
“Motor, Pump”
“Motor””Pump”
Creating, Updating, and Deleting Folders
To create an instance in a new folder, you must also enter in the CSV file the necessary data to create the folder.
Since each row corresponds to only one folder, to create, for example, the structure Root\Folder_1\Folder_10 , you must configure two rows.
NOTE: It is not possible to rename a folder by using the Update action.
Perform the following steps in the Folders groups of the CSV application export file.
Step
1
2
Action
Edit the rows that contain data of folders and/or create rows. Verify that at least the
required columns and data, page 176
are present.
Specify a value for $Action for each row as needed.
EIO0000001114.15
EIO0000001114.15
Creating, Updating, and Deleting Instances
Perform the following steps in the TemplateIdentifier groups of the CSV application export file.
Step
1
2
3
Action
Edit the rows that contain data of instances and/or create new groups and/or rows.
Verify that at least the
required columns and data, page 176
are present.
Verify that the data for $Location is consistent with the target application and/or
$Location in the Folders group.
Specify a value for $Action for each row as needed.
NOTE: If you update data of instances that are already linked and want the link to be maintained, it is not required to update the row of the InterfaceLinks group that pertains to the link as long as the linked interfaces remain enabled.
This applies even if you change the value of $InstanceName or the instance identifier (for example, by configuring an alias for a folder) for either or both instances.
Creating and Deleting Interface Links
Perform the following steps in the CSV application export file.
Step
1
2
3
4
Action
In the InterfaceLinks group, edit the rows that contain data of the links and/or create new rows. Verify that at least the
required columns and data, page 176
are present.
Verify that the data for $SourceLocation and $DestinationLocation is consistent with the target application and/or $Location in the other groups (if applicable).
Specify a value for $Action for each row as needed.
In the TemplateIdentifier group, verify that the data of the linked instances is entered.
If the linked instances already exist in the target application with the same configuration and you do not want to modify them, change the value of $Action to Update or leave it blank for each instance.
NOTE: If the instances already exist in the target application and you leave the value as Create , the Resolve Uniqueness Conflicts
opens during import and you need to select the Update action for the instances there.
Changing the Destination of An Existing Interface Link
To move the destination of an existing link to a different interface, edit the CSV application export file as follows. The new destination interface must be available for connection during import.
Step
1
2
3
Action
In the InterfaceLinks group, for the row that contains the data of the existing link, change the value of $Action to Update or leave it blank.
Enter the appropriate data in each of the five columns $NewDestinationLocation to
$NewDestinationInterfaceIdentifier .
NOTE: You do not need to edit the data of the existing interface link. If the interface link does not exist in the target application, a link from the specified source to the new destination is created anyway.
In the TemplateIdentifier group, verify that the data of the linked instances is included.
If the instances already exist in the target application with the same configuration and you do not want to modify them, change the value of $Action to Update or leave it blank for each instance.
NOTE: If the instances already exist in the target application and you leave the value as Create , the Resolve Uniqueness Conflicts
opens during import and you need to set the action to Update there.
183
XML Application Export File
Export File Description
The following example shows the structure of an XML application export file
(partial view) that was created by exporting Folder_1 , which contains instance
DISignal_UL_1 .
184
1 Data pertaining to the folder.
2 Data pertaining to the instance.
3 Data of the parameters and elements of the instance.
4 Data of the application
that the instance exposes.
5 Folder identifier.
6 Folder Action parameter
7 $InstanceID parameter of the instance, which is generated by the software. This is the identifier that the software uses to identify the instance for delete and update actions. Do not edit this parameter.
8 $Name parameter of the instance.
9 Instance Action parameter.
EIO0000001114.15
When instances that are linked are exported, the information of the interface links is grouped in the InterfaceLinks element, which appears at the end of the file. The following example shows an extract of an export file, which contains two instances linked by two interface links.
(1) Action parameter plus source and destination information pertaining to the first interface link.
(2) Same information pertaining to the second interface link.
Editing the XML Application Export File to Manage Folders and Instances
Overview
You can edit the XML export file by using any XML editing software to perform one or more of the following actions on application folders and/or instances:
• Create an object by using the parameter values of the export file.
• Update an object that has the same identifier by using the parameter values in the export file.
• Delete an object that has the same identifier as in the export file.
You can also
create and delete interface links, page 189
.
The software applies the changes when you
import the edited XML file, page 191
into the application of the system. At that time, you have the possibility to review and modify the list of imported objects (except interface links).
NOTE: You cannot update the identifier of a folder through import.
Good Practices
• Before editing an application export file, create a copy of it. If needed, it lets you restore the original application.
• Edit only an up-to-date export file to help avoid data conflicts when importing.
Application Export File Content
The table shows the objects and their respective parameters that are exported to the XML file and that are configurable.
Object
Application folder
Instance
Parameters
For the folder and any subfolders
Action
Identifier
Alias
Description
Area (1)
Location
Parameters
For the instances in the folder and its subfolders
EIO0000001114.15
185
186
Object
Interface link
Parameters
Action
TemplateIdentifier
Version
IsHierarchical
Location
$Name
$Description
$Area (1)
Elements that are enabled (selected in the Instance Editor )
Parameters of each element
For parameters of the
enumerated data type, page 186 , the name is
exported as value. For example, if the parameter
that is configured in the Instance Editor is Operator (2) , the exported value is
Operator . To edit the value, you can enter either the name of the enumerator or the associated integer (for example, 3 for an enumerator that is
Supervisor (3) ).
Identifier of exposed interfaces and their path in the composition of the instance. Includes data of disabled and connected interfaces.
When an alias is configured for an interface, both the alias and the identifier are indicated. The alias is the name that appears in the Asset Workspace
Editor or Links Editor .
Parameters of interface links that exist between exported source and destination instances.
Refer to the topic describing how to
edit the XML file to manage interface links, page 189
.
(1) If the value is
inherited from a parent folder, page 127 , it does not appear in the export file.
Action Parameter
Configuring the Action parameter is optional.
Possible values (not case-sensitive):
• Create (default)
• Update (except for
)
• Delete
• Blank:
◦ Creates the object if it does not exist yet.
◦ Updates the object if it exists (except interface links).
NOTE: Instances with action set to create and that you do not want to import can be removed from the list of imported objects during
Using the Invariant Culture
Use the
to modify or add parameter values in the application export file.
Editing Rules for XML Application Export Files
To maintain the consistency of the folder structure and instances contained in the export file, follow these rules.
EIO0000001114.15
Item
Instance
Parameters
Object hierarchy
Rule
Do not modify Identifier of the instance ( $InstanceID parameter) because it is generated by the software.
Modify only the parameters described in the procedures that appear in this topic.
Do not modify the structure of child elements.
For example, a folder must be the parent of an instance and not the opposite.
However, you can modify the order of Elements or Parameters inside an instance ( ApplicationInstance section).
When the export file contains data of a folder structure, do not change the
<Location> parameter of the highest level folder (the folder from which the export file was created). For subfolders, the hierarchy from the export file prevails.
When the export file contains data of a single instance or single folder, do not modify the <Location> parameter.
The following figure shows an extract of an export file of instance Motor_3 , which was exported from Folder_5 . The instance is located in Folder_1 , a subfolder of
Folder_5 . The Location parameters of these folders are highlighted.
EIO0000001114.15
Creating an Instance
To edit the XML export file to create a new instance in an existing folder, proceed as follows.
Step
1
2
3
Action
Change the value of the $Name parameter to the name of the new instance that you want to create.
NOTE: To create multiple instances during import:
• Copy the entire ApplicationInstance section of the export file that contains the data of the instance.
• Paste it at the end of the section that you have copied, as many times as you want to create instances.
• Change the value of $Name to the new name of each instance.
Verify that Action is set to Create ; otherwise replace the value by Create .
Save your changes.
Updating an Instance
To edit the XML export file format to update an existing instance, proceed as follows.
187
188
Step
1
2
3
Action
For the instance that you want to update, change the value of Action from Create to
Update .
Change the value of the
that you want to update.
Save your changes.
NOTE: If you update data of instances that are already linked and want the link to be maintained, it is not required to update the data of the
InterfaceLinks element that pertains to the link as long as the linked interfaces remain enabled. This applies even if you change the value of
$Name or the instance identifier (for example, by configuring an alias for a folder) for either or both instances.
Deleting an Instance And/Or a Folder
To edit the XML export file to delete an existing instance and/or folder, proceed as follows.
Step
1
2
3
4
Action
If you want to delete:
• The instance and the folder containing the instance, verify that the export file also includes the information pertaining to the folder.
• The instance only, proceed to step 3.
For the folder that you want to delete, change the value of Action from Create to Delete .
For the instance that you want to delete, change the value of Action from Create to
Delete .
Save your changes.
Creating Folders
To edit the XML export file to create one or more folders or a folder hierarchy, proceed as follows.
Step
1
2
Action
Verify that Action is set to Create for the folders that you want to import; otherwise replace the value by Create .
Save your changes.
Updating a Folder
To edit the XML export file to update an existing folder, proceed as follows.
EIO0000001114.15
Step
1
2
3
Action
For the folder that you want to update, change the value of Action from Create to
Update .
Change the value of any of the following folder parameters that you want to update:
• Alias
• Description
• Area
• Parameters
If the value of the parameter that you want to update is blank, enter the new value in the following format <Parameter>Value</Parameter> , where Parameter represents one of the four parameters that you can change and Value the new parameter value.
For example, to modify the blank Area parameter of a folder to 100 , enter <Area>100</
Area> .
NOTE: You must not change the Folder Identifier value.
Save your changes.
Editing the XML File to Manage Interface Links
Overview
You can use any XML editing software to edit the export file. This lets you create and delete interface links.
The software applies the configuration when you
import the edited XML file, page
into the application of the system.
If you modify the data of a link that is contained in the export file, the existing link is not deleted after import. The new link is created in addition.
Good Practices
• Before editing an application export file, create a copy of it. If needed, it lets you restore the original application.
• Edit only an up-to-date export file to help avoid data conflicts when importing.
• Use the data of
to create interface links.
Linked Instances Data
For any actions on links, the data of the linked instances must
appear in the application export file, page 185
even if the instances already exist in the target application.
If the linked instances already exist in the target application with the same configuration and you do not want to modify them, change the value of $Action to
Update for each instance.
NOTE: If the instances already exist in the target application and you leave the value as Create , the Resolve Uniqueness Conflicts
opens during import and you need to select the Update action for the instances there.
Contents of the InterfaceLinks Element
The table describes the parameters of the InterfaceLinks
that appears at the end of the XML application export file.
EIO0000001114.15
189
190
Parameter
Action
DestinationPath
DestinationInstanceName
DestinationInstanceTemplateIdentifier
DestinationInstanceIdentifier
DestinationInterfacePath
Description
Action that the software performs by using the interface link data. Possible values:
• Create (default): Creates new links in addition to existing links whose data has been exported.
• Delete: Deletes links whose configuration matches the data in the imported file.
NOTE: To create a new link in place of an existing link, you need to explicitly delete the existing link.
NOTE: Entering Update produces the same result as
Create .
Path to the instance that is the destination of the link in the
Application Explorer .
The name of the
is replaced by
Root .
Value of the
of the instance that is the destination of the link.
Identifier of the template that is used by the instance, which is the destination of the link.
of the instance that is the destination of the link.
Path to the destination interface in the composition of the instance.
Example :
In the following sample instance, value for interface BoolVar is “” (blank) because it has no parent element.
DestinationInterfaceIdentifier Identifier of the interface that is the destination of the link.
IsDestinationInstanceHierarchical
SourcePath
SourceInstanceName
SourceInstanceTemplateIdentifier
SourceInstanceIdentifier
SourceInterfacePath
Indicates if the
hierarchical naming function, page 141
is enabled for the instance.
Path to the instance that is the source of the link in the
Application Explorer .
The name of the
is replaced by
Root .
Example :
For instance Motor_1 of System_1 that is located in Folder_2 , which is a subfolder of Folder_1 , the value is Root\Folder_1
\Folder_2 .
Value of the
of the instance that is the source of the link.
Identifier of the template that is used by the instance, which is the source of the link.
of the instance that is the source of the link.
Path to the source interface in the composition of the instance.
Example :
In the following sample instance, the value for interface
ZSHPOS is Control\Motor\Logic .
EIO0000001114.15
Parameter Description
SourceInterfaceIdentifier Identifier of the interface that is the source of the link.
IsSourceInstanceHierarchical Indicates if the
hierarchical naming function, page 141
is enabled for the instance.
Creating a Link
To edit the XML export file to create a link, proceed as follows.
Step
1
2
3
4
Action
In the InterfaceLinks element, copy the source and destination data that pertains to an existing interface link and paste it inside the element.
Edit the necessary source and destination data.
Verify that the value of Action is Create .
Save your changes.
Deleting a Link
To edit the XML export file to delete a link, proceed as follows.
Step
1
2
Action
In the InterfaceLinks element, locate the source and destination data that pertains to the interface link and change the value of Action to Delete .
Save your changes.
Importing a CSV or XML File Into the Application
Overview
By using the Import command, you can modify the application with the configurations that you have made in the CSV or XML file.
The import process is performed in steps during which the software:
1. Validates the structure of the CSV or XML file.
2. If valid, displays the folders, asset workspaces, and instances contained in the imported file along with the action that you have configured for each one, informs you of detected issues, and lets you select which objects to import.
3. Imports selected objects that satisfy applicable rules (for example, uniqueness of instance identifiers and presence of template).
EIO0000001114.15
191
192
4. For the other objects, informs you of the detected
and lets you resolve them so that you can import these objects.
5. Displays a summary of the import operation, which includes information about incorrect configurations and objects that were not imported.
Creating and deleting instances through import affects the
.
NOTE: Verify that the version of the templates that are used by the instances that you are importing exists in the Global Templates library before you proceed with the import; otherwise you will not be able to import these instances. Refer to the topics describing how to:
•
Browse application templates , page 119 .
•
Export/import templates, page 675 .
Software Version Compatibility
You can import into a system instances that were exported to XML format from
Process Expert 4.0 and later.
If the XML export file was created from a version earlier than Process Expert 4.0, you need to import the file into the version from which it was created, migrate the database in steps to version 4.0, and export the instances again from this version.
Instance Import Behavior
The table describes the default import behavior when you configure the export file to create instances in the following scenarios.
Scenario
An instance parameter value is invalid or no value is configured.
An instance element selection value is invalid or no value is configured.
Result
The instance is created and configured with parameters whose value is valid.
For the invalid or not configured parameter, the default value of the template is used.
The instance is created and configured with element selections whose value is valid.
For the invalid or not configured element selection, the value is set to false. The values that are configured for its parameters are not applied.
Folders
No Folders
or
in the group.
Instance
Data is valid.
Invalid data for at least one folder in the instance path.
Data is valid.
Result
• If the folders exist in the target application: The instance is created.
• If at least one folder in the instance path does not exist: The instance is not created.
• If the folders exist in the target application: The instance is created.
• If the folders do not exist, only those that have valid data and a parent folder with valid data are created.
The instance is created only if the folder that contains it is created.
EIO0000001114.15
EIO0000001114.15
The table describes the import behavior when you configure the export file to update instances in the following scenarios.
Scenario
An instance parameter value is invalid or no value is configured.
An instance element selection value is invalid or no value is configured.
Result
Only parameters whose value is valid are updated.
For the invalid or not configured parameter, the current value of the instance is retained.
Only element selections whose value is valid are updated.
For the invalid or not configured element selection, the current value of the instance is retained.
Folders
No Folders
or
in the group.
Invalid or missing data for at least one folder in instance path.
Instance
Data is valid.
Data is valid.
Result
The instance is updated.
NOTE: When you import an XML file, folders whose data is invalid or missing are tagged with a red dot in the Import window.
Folder Import Behavior
The table describes the default import behavior when you configure the export file to create folders in the following scenarios.
Scenario
The parameter Action for all the folders in the export file is set to Create and the parent folder already exists in the target application.
The data of at least one folder in the folder structure is invalid.
Result
Only its subfolders are created if these do not exist yet.
If a subfolder already exists, it is not created but any lower-level folder in the hierarchy is created if it does not exist yet. And so on.
Only folders that have valid data and a parent folder with valid data are created.
The table describes the import behavior when you configure the export file to update folders in the following scenario.
Scenario
The data of at least one folder in the folder structure is invalid.
Result
Only folders that have valid data are updated.
NOTE: If it is not able to propagate the value of the Area parameter to any object because the object is locked, the software:
• Displays a notification to inform you which object is locked.
• Rolls back any propagated area value.
• Reverts the Area parameter value that you have entered in the folder properties to its previous value.
NOTICE
NO CHANGE PROPAGATION
When the Area parameter value of a folder is not propagated:
• Reenter the Area parameter value in the properties of the folder.
• Verify in the Notification Panel that parameter value propagation completed successfully.
Failure to follow these instructions can result in alarms being signaled in the wrong area during operation.
193
The table describes the import behavior when you configure the export file to delete folders in the following scenario.
Scenario
The folder that you are deleting contains subfolders and instances.
Result
The software deletes the subfolders and instances.
Interface Link Import Behavior
When you import two instances that are linked and select the Relative Path
, which imports the instances to a location that is different from the one that is specified for the source and destination instance in the interface links data group, the link is maintained.
Aborting Import Tasks
After confirming the import by clicking OK in the Import window, the abort icon is displayed in the
. Click the icon to cancel the task.
Only the user who has selected the command is allowed to abort it.
Folders and instances that already appear in the Application Browser at the moment you abort the task are retained given they belong to a tree structure that starts from the system root folder and that is completely imported at the moment the import task is aborted.
If you click the abort icon after clicking OK in the Resolve Uniqueness Conflicts dialog box, instances and folders that you had selected to be created and/or updated are not imported. Already imported objects (non-conflicting ones) are retained.
In any case, links that exist between instances are not recreated when you abort an import task even if these instances are retained. This is because recreating links is the last step performed before completing an import task.
NOTE: If you are importing only a few objects, the task may complete before you are able to click the abort icon.
The following example illustrates two scenarios. Parent folders Folder_1 and
Folder_2 are exported with their respective subfolders from the system root folder
( System_1 ).
194
When you import the two structures into a system, folders are imported in sequence, structure after structure. If the import task is aborted:
• Before Folder_C and its contents is completely imported (displayed), nothing is retained.
• After Folder_C and its contents is completely imported (displayed), only the complete Folder_1 tree structure and the instances therein are retained.
EIO0000001114.15
The following figure shows the objects that are retained when the import task is aborted after Folder_C and its contents has finished importing.
If a link exists, for example, between an instance in Folder_A and an instance in
Folder_C , it is not recreated.
Opening the Application Import Window
To open the application Import window, proceed as follows.
Step
1
2
Action
In the Application Browser , right-click the folder in which you want to import instances or that is to become the parent folder and select Import .
Result: The Open dialog box opens.
Select the application export file and click Open .
Result: The application Import window opens and displays the contents of the file.
NOTE: If you are importing only asset workspaces, you can right-click independently the root node in the Application Browser or Asset
Workspace pane.
Import Window Description
The following figure shows an example of the application Import window. This example illustrates a scenario where three instances and one folder cannot be imported. Details are provided in the legend.
EIO0000001114.15
195
196
7
8
4
5
6
Item
1
2
3
9
10
Description
Full path of the file that you are importing.
You can
data.
Identifier of the folders and asset workspaces and name ( $Name ) of the instances contained in the imported file.
A selected check box indicates that the object is imported if possible.
A colored dot next to each object indicates the import status. Details are shown in a tooltip.
NOTE:
• Instances whose data is invalid are not shown.
• Instances whose data is valid are shown but
.
Refer to the Details section.
Color Colored dot description
Green For instances: The template that is used by the instance (same identifier and version) is available in the Global Templates library.
For folders: Subfolders and instances inside the folder and its subfolders are marked with a green dot.
Red For instances: The template that is used by the instance (same identifier and version) is not available in the Global Templates library. If you proceed, the instance is not imported.
For folders, may appear in these situations:
• Subfolders and instances inside the folder and its subfolders are marked with a red dot.
• The folder data in the CSV file is invalid.
• The folder contains an instance whose data is invalid.
If the location of the instance is not specified, the red dot appears on the system root folder.
Yellow
For asset workspaces, appears if the asset workspace identifier in the
CSV file is invalid.
For folders only: The folder or its subfolders contains at least one subfolder or instance that are marked with a red dot while at least one instance or subfolder is marked with a green dot.
Identifier of the template that instance is using.
Version of the template that the instance is using.
Indicates the action that the software performs on the selected object according to the value of the Action parameter in the imported file.
NOTE: When you create an instance, in the import summary that is shown in the notification panel, the action appears as Create for the instance but as Update for its elements and parameters.
Contents of the $Description parameter of the object.
Import setting. The view is updated to show the impact of your selection.
Absolute
Path
During import, the software maintains the folder structure of the imported file independently from where you select the import command given the required folder data is present in the imported file or the folders exist in the target application.
The system root folder appears as Root .
Relative
Path
During import, the folder from which you select the import command becomes the parent folder of the imported folder structure.
However, folders that do not exist in the target application and whose data is missing in the import file are not imported. This may change the location of instances.
NOTE: To be able to import an asset workspace when you are importing at the folder level, you need to select Absolute Path .
Notification area, which contains information about detected issues.
The message indicates that the instance cannot be imported because its template is not available in the Global Templates library. As a result, the instance is tagged with a red dot.
EIO0000001114.15
Item
11
12
Description
The message indicates that the instance that is located in folder Unit_2 cannot be imported. As a result, the folder is tagged with a red dot and the instance is not shown in the window.
Folder Cell_3 cannot be imported because of missing data in the imported file. As a result, the folder is tagged with a red dot and no action appears for it. Also, instance
MyValve_2 will not be created. It is tagged with a green dot because its template is available in the Global Templates library.
Resolving Conflicts During Import
You can resolve the object-uniqueness conflicts that the software detects during import, for example, if you are importing an instance or asset workspace and one with the same
already exists in the application.
The Resolve Uniqueness Conflicts dialog box opens once non-conflicting objects have been imported. The following figure shows an example for an instance.
EIO0000001114.15
5
6
2
3
Item Description
1 $Name parameter of the instance as it appears in the imported file.
The column can also show the identifier of an asset workspace.
4
Identifier of the instance based on the data of the imported file.
Identifier of the template that the instance uses.
New value for the $Name parameter of the instance that the software will use to satisfy applicable naming rules if you select to create the instance.
The column can also show the new identifier of an asset workspace.
7
Identifier of the object after import if you select to create it.
Buttons that let you select an action for individual objects:
• Skip : The existing instance and its links are not modified or the asset workspace is not imported.
• Update : Default action. Modifies the existing object with the imported parameter and link configuration. The name of the object is not modified.
• Create : Creates a new object with New Instance Name and the imported folder, parameter, and link configuration.
NOTE: Update is disabled if you have selected the Relative Path import setting and, as a result, the instance is imported in a different folder.
Buttons that let you select an action for the conflicting objects as a whole.
The actions are the same as when you select the action for objects individually.
NOTE: Clicking these buttons overrides the selection you have made for individual objects.
197
198
Importing Objects into the Application
To import the content of an application export file into the application of a system, proceed as follows.
Step
1
2
3
4
5
Action
In the application Import window:
• Review information that is shown in the Details pane (if applicable).
• Select the objects that you want to import.
• Select the import settings that you want to apply.
Click OK .
Result: If you select to import with relative path, a confirmation dialog box opens.
NOTE: Click Cancel to close the Import window without importing any object.
Click OK .
Result: If it does not detect conflicting objects, the software:
• Imports the contents of the file and applies the import settings that you have selected.
• Displays the imported objects in the Application Browser .
• Displays a summary of the import process in the notification pane.
If it detects conflicts, the software:
• Imports the objects that satisfy import rules and applies the import settings that you have selected.
• For conflicting objects, opens the Resolve Uniqueness Conflicts dialog box; proceed to step 4.
In the Resolve Uniqueness Conflicts dialog box, select the actions that you want to perform for conflicting objects.
NOTE: Click Cancel to close the Resolve Uniqueness Conflicts dialog box without importing objects for which the software has detected a conflict. Objects that satisfied import rules remain imported.
Click OK .
Result: The software:
• Imports the remainder of the objects with the import settings that you have selected.
• Displays the entirety of the imported objects in the Application Browser .
• Displays a summary of the entire import process in the notification pane.
EIO0000001114.15
Project Definition Stage
What’s in This Chapter
Project Explorer and Project Browser ........................................................ 199
Creating Supervision Project Components .................................................... 229
Overview
This chapter contains information to help you define the Control and Supervision projects of the system.
The following figure shows the position of the Project Definition stage within the system engineering life cycle.
Refer to the
Project Definition stage, page 32
for a description of the purpose of this stage.
Project Explorer and Project Browser
Overview
This section describes the Project Explorer , which features the various editors that let you manage Control and Supervision Participant project components. It also describes the Control Project Browser and Supervision Project Browser , which let you create these projects and open their respective editors.
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
EIO0000001114.15
199
Project Explorer
Opening the Project Explorer
To open the Project Explorer for a system, verify that the system is selected in the Systems Explorer or that at least one explorer/editor is already open for this system. Then, click the Open Project Explorer button in the engineering client toolbar.
Otherwise, right-click the system in the Systems Explorer and select Open
Project .
Project Explorer Window
The following figure shows an example of the Project Explorer for a system in which two Participant projects exist. The Control Project Browser is selected.
The following figure shows an example of the Project Explorer for a system in which two Participant projects exist. The Supervision Project Browser is selected.
200 EIO0000001114.15
Project Browser
4
5
2
3
Item
1
6
Description
Tabs to show the Control Project Browser or Supervision Project Browser
.
System root folder.
Remaining
of the Project Explorer when the project browser pane is pinned. The data that is shown depends on the project browser tab that is selected. The work area is empty by default.
Assignment Editor
. It shows the containers of the Participant projects and lets you assign facets to them.
Executable management, page 420
tab, which lets you view and edit executable properties and perform the various mappings by selecting the corresponding subtabs:
• Service Mapping
• Communication Mapping
• Hardware Mapping (Control only)
Properties
for the Participant projects and their components other than executables.
Description
The project browsers let you see, create, and interact with the Control and
Supervision Participant projects that exist in a system.
The following figure shows an example of the Control Project Browser in which two projects have been created.
The following figure shows an example of the Supervision Project Browser in which one project has been created.
EIO0000001114.15
201
202
4
5
2
3
Item
1
8
9
6
7
Description
Pin button, page 86 . Lets you hide the pane and restore it when it is docked.
You can
which columns appear.
System root folder.
Node giving access to project-level context menu commands.
Node giving access to container-level context menu commands.
Node giving access to cluster-specific context menu commands.
User-created
Project type selection tabs.
Navigating Inside the Project Browser
The keys to navigate are the same as in the Application Browser
.
Customizing Column Display
You can choose which columns you want to see by right-clicking a column header and selecting Customize . Certain columns are always shown.
For a description of the columns, refer to the topic describing properties of
and
Supervision executables, page 458 .
System Root Folder Actions
Right-click the system root folder to open a context menu with the following commands. The availability of commands depends on the tab of the Project
Browser that is selected.
Command
Description
Creates a new Control project that is associated to one of the supported controller families and displays it in the tree view of the Project Explorer .
Opens an Open dialog box, which allows you to create a Control project by importing data of a project that was created with Control Expert. Export files in .
stu or .xef format are supported.
Open
Application
Creates a new Supervision project, and displays it in the tree view of the
Project Explorer .
Open Topology Opens the
Topological Explorer , page 204
, which allows you to start the configuration stage or access the topology of the system.
Export
Opens the
Application Explorer , page 116
, which allows you to start the instantiation stage or access the application of the system.
Import
Opens a Save As dialog box, which allows you to create an export file containing the information of the
and
Supervision projects, page 238
that exist in the system.
Opens an Import dialog box, which allows you to display the compatible contents of an export file (.sbk) in the Import window. You can import entire
and/or
Supervision projects, page 242
, or parts of them into the system.
EIO0000001114.15
Control Project Definition Stage
Overview
This section describes how to create Control projects of a system and their sections.
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
Creating Control Projects
Before Creating a Control Project
At this stage of the system engineering life cycle, you need to know:
• Which
family of controllers, page 371
you will be using to run the Control project.
• How you will organize the function block diagram (FBD) sections of the project.
NOTE: For information on working withControl projects of M580 safety controllers, refer to the topic describing the
engineering of M580 safety systems, page 577 .
Creating Control Projects
To create a Control project, proceed as follows.
Step
1
Action
In the Control Project Browser , right-click the system root folder, select Create
Control Project and the
that is associated to the project.
Result: The Control project is shown in the tree view.
NOTE: In each system, you can create as many Control projects as needed.
For example, you can create a project, which is engineered for a Modicon
M580 controller in the plant and a project, which is engineered for an M340 controller for test purposes in the laboratory.
Control Project Actions
The table describes the Control project context menu commands.
Command
Assign
Facets
Refine
Description
Opens the Assignment Editor , which lets you create and manage sections and assign facets to them.
Applies to
Starts a process to create or update the logic at the project level.
Generation stage
Opens the Control Participant, which allows you to make changes to the logic of the project.
Opens the Manage Network Variables dialog box, which allows creating, modifying, and deleting network variables.
These are variables that are used to share data by using peer to peer communication.
Opens the Manage Data Backup Files dialog box, which lets you view and delete data backup files that exist for Control
Participant project.
Project Definition stage
EIO0000001114.15
203
204
Command Description
Starts a process to recreate the logic from the beginning at the project level.
NOTE: Certain changes that you have made during refinement may be discarded.
Settings
Opens a dialog box that indicates the last action that was performed and a summary of the result.
Opens a Save As dialog box, which allows you to create an export file containing the Control project information.
Opens the Settings
window, page 205 , which lets you configure
various project-related settings.
Rename
Deletes the Control project including:
• Sections
• Assignments
•
Allows you to enter a new
for the project.
Properties Opens the Properties window, which allows you to view and/or edit the properties of the Control project.
–
–
Applies to
Generation stage
Project Definition stage
Assignment stage
–
Containers Node Actions
The table describes the Containers node context menu commands.
Command
Assign
Facets
Create FBD
Section
Generate
ReGenerate
Description
Opens the Assignment Editor , which lets you create and manage sections and assign facets to them.
Lets you
create an FBD section, page 261
in the task folder that you select.
The Assignment Editor opens in the background.
Starts a process to create or update the logic at the section level.
Starts a process to recreate the logic from the beginning at the section level.
NOTE: Certain changes that you have made during refinement may be discarded.
Applies to
Executables Node Actions
The table describes the Executables node context menu commands.
Command
Create
Executable
Description
Creates one or more
, which let you associate one or more controllers to the Control project, map project facets to hardware, and create communication channels by using the I/O scanner service of the controller.
Applies to
Control Project Properties
Right-click the Control project and select Properties .
You can view and/or edit the following items.
Item
General Identifier
Description
The identifier must be unique within the system.
EIO0000001114.15
EIO0000001114.15
Item
Controller
Family
Description
Description Optional.
Value
You can enter a description of the project with free text.
Indicates the controller platform that you have associated to the project at the time of creation.
Possible values:
• M580
• M580 Safety
• M340
• Quantum
Read-only.
NOTE: When you associate a Control project with a controller family, the software limits the assignment of facets to the project to those that have the corresponding attribute (see EcoStruxure ™
Process Expert, Global Templates, Reference Manual) defined.
Deleting a Control Project
When you select the command to delete a Control project, the software displays a confirmation dialog box. Once you have confirmed the deletion, the software executes the following actions in relation to the project that you are deleting:
• Deletes any components of the project and their contents, including any assignments and mappings.
• Deletes any associated files (for example, data backup files and
for container naming rules).
NOTE: You cannot delete a Control project if any executable of the project is
Project Settings Window
The Settings window opens when you select the Settings command in the context menu of a Control or Supervision project.
Section
Container
Naming Rules
Description
Lets you configure
expressions, page 268 , which define how sections are
created and how Control facets are assigned to the project.
The section appears only for Control projects.
Assignment Lets you set the functionality, which can
automatically assign remaining candidate facets, page 284
of instances.
Possible values:
• Enabled
• Disabled
Project Analysis Lets you enable or disable the automatic analysis of the Control project, which is performed when you generate the project/sections or save refinement changes.
When the analysis is disabled:
• The Control
project validity indicators, page 252
are not functional.
• The time required to generate and save refinement changes is reduced.
You can perform an analysis of the Control project manually at any time by refining it offline and clicking Build
>
Analyze on the menu bar. After you click the save button, the project validity indicators indicate the status of the project.
Possible values:
• Enabled
• Disabled: Default value.
The section appears only for Control projects.
NOTE: For M580 safety Control projects, the setting also impacts the
of the associated M580 safety controller.
205
NOTE: The OK and Cancel buttons apply to all the sections of the Settings window.
Creating Control Project Sections
Overview
In the Project Explorer , you can create only FBD sections in a Control Participant project by using context menu commands.
Creating FBD Sections
To create FBD sections in task folders, open the Assignment Editor by selecting
Assign Facets from the context menu of the Containers node in the Control
Project Browser .
For a description of sections and actions that you can perform, refer to the topic describing the
NOTE: You can create FBD sections also by refining the Control Participant project or importing them.
Creating Non-FBD Sections
You can create non-FBD sections by:
•
the Control Participant project and creating the sections.
• Refining the Control Participant project
online, page 548 , creating the
sections, and
the Control project.
•
the sections.
Non-FBD sections are sections in any of the following languages: IL, LD, LL984,
SFC, and ST. They appear also in the Containers pane of the Assignment
Editor .
NOTE: In the following cases, existing non-FBD sections may be displayed only after you make a change by using the Refine
at the project level and save it:
• The Control project is contained in a database of an earlier version of the software that you have migrated.
• The Control project is contained in a system that you have restored by using a backup file created with an
of the software.
Managing Control Projects
Overview
This section describes how to use the Project Explorer to manage entire Control projects or sections of such projects.
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
206 EIO0000001114.15
Control Project Section Order
Overview
The software assigns an order to sections, starting at 0, and displays it in the
Containers
pane, page 257 . The values appear in the
Order column.
It indicates the order in which the software generates the sections of the Control project and thereafter the execution order of the sections by the Control
Participant.
You can change the order of sections inside the Containers pane.
The software applies changes to the order of sections in the logical Control
Participant project when you perform either action:
• Select the Refine command at the project level (it is not required to make a change or save).
•
the entire project or a section of the project.
•
the entire project or a section of the project.
You then need to propagate the change downward in the system engineering life cycle.
NOTE: You can also change the order of sections by
the
Control Participant project or by refining the deployed Control project
and updating the Control Participant project.
Moving Sections
In the Assignment Editor , you can move sections only within the MAST or FAST task folder.
To move sections from the MAST to the FAST task folder or the other way around, refine the Control Participant project.
Changing the Order of Sections
To change the order of sections of a Control project, proceed as follows.
Step
1
2
3
4
Action
In the Containers pane of the Assignment Editor ,
.
Drag one section up or down to a new position.
Result: A tooltip indicates the position that the section will occupy.
NOTE: In the Assignment Editor , you can select multiple, contiguous or noncontiguous sections that belong to the same task folder.
Release the mouse button.
Result: The section is inserted at the selected position and the values of the Order column are updated.
Apply the new order to the logical Control project by performing the necessary action.
NOTE: To change the order of the facets inside an FBD section, refer to
Changing the Facet Order , page 295 .
Exporting Control Projects
Overview
The export functionality lets you create a non-editable export file (.sbk), which contains selected Control project information.
EIO0000001114.15
207
208
You can use this data by using the Control project
functionality to transfer project information to a different system or to merge information from different Control projects.
However, you cannot merge data related to communication mapping during import. You need to import either the complete
communication channel, page 424
and/or peer to peer
that is contained in the export file for selected Control projects or nothing.
NOTE: To export the Control and Supervision projects of a system at once in one export file, right-click the system root folder in either Project Browser , select Export , and follow the project export procedure described in this section. Refer also to the topic describing the export and import of
Supervision projects, page 238 .
Exporting M580 Safety Control Projects
For specific information about exporting M580 safety Control projects, refer to the topic describing how to
engineer systems with M580 safety controllers, page 581 .
Software Version Compatibility
The version of EcoStruxure Process Expert that you use to import the information contained in the export file must be the same as the version that you used to create the export file (a service pack is considered the same version); otherwise you cannot proceed with the import.
Project Related Data
To be able to use the export file to import a project into a different system, verify that the instances, their templates, and topological entities related to the project exist in the target system
before importing the project, page 213 .
NOTE: The parameter values of instances that reference the exported facets are not contained in the export file. However, the export file contains information that allows the software to verify during import if the configuration of an instance is different from when its facets were exported.
Project Export Window
The Control window lets you select, which project information the export file will contain.
EIO0000001114.15
The following figure shows an example of the Export window where the check box for FBDSection_2 has been cleared. To indicate that at least one item of the
Control project is not selected, the check box of parent nodes are filled with a square.
EIO0000001114.15
The table indicates the meaning of the colored dots that appear in the Export window next to items of a Control project.
Color code
Green
Red
Yellow
Description
You can export the item.
You cannot export the item because it contains at least one facet with the following state:
• Deleted
• Unassigned
• Out of Date
• Moved
Generate sections that contain facets with such states in order to export the
Control project.
NOTE: You cannot export items that are tagged with a red dot.
Indicates that the item contains at least one subitem that is tagged with a red dot.
The item can be exported partially only.
NOTE: To expand/collapse a node in the Export window, select the node and press Enter .
Export Settings
The table describes which Control project information you can export.
Item
System_n
ControlProject_n
Tasks folder
Selected for export
By default
Description
By default
By default
Unselecting the item excludes any Control project and disables the creation of the export file.
Unselect the item to exclude the entire project from the export file.
You cannot unselect the item.
209
210
Item Selected for export
By default
Description
You cannot unselect the item.
MAST and FAST task folders
Sections By default
Safe Program
Container Naming Rules
Executables
ControlExecutable_n
Service
Mappings
Hardware
Mappings
Communication
Mappings
Built Participant
Project
Backups
By default
By default
By default
By default
By default
By default
By default
By default
By default
You can unselect sections individually.
Selecting an FBD section automatically selects any facets that are assigned to it.
The item is available only for
M580 safety Control projects, page 577
.
You cannot unselect the item.
Represents the
that are configured.
You cannot unselect expressions.
You cannot unselect the item.
You can unselect each executable and its contents individually.
Selecting an executable automatically selects any associated mapping.
Selecting the item exports any data related to the service mapping including any required contents in the contents repository.
Unselecting the item also unselects both the associated hardware and communication mapping.
You cannot select hardware mappings individually.
Selecting the item also selects the associated control executable and service mapping.
You cannot select communication mappings individually.
Selecting the item also selects the associated executable and exports the complete communication mapping data.
NOTE: If the project contains peer to peer communication data, refer to the topic describing
peer to peer communication export settings, page
Represents the built Control Participant file (.stu).
You can select data backup files individually.
The time stamp and description of each
are shown. The format of the time stamp is
YYYYMMDDHHMMSS.
Peer to Peer Communication Export Settings
To be able to recreate peer to peer communication channels and existing variable mappings at the time of import if the necessary conditions are fulfilled, you need to export all of the following:
• The owner project and its Control executable.
• The consumer project and its communication mappings.
NOTE: Including communication mappings in the export file may also include communication channels other than those for peer to peer communication (for example, communication channels for I/O devices).
Aborting Export Tasks
After confirming the export by clicking Save in the Export window, the abort icon is displayed in the
notification panel, page 54 . Click the icon to cancel the task.
The export file is not created.
EIO0000001114.15
Only the user who has selected the command is allowed to abort it.
NOTE: If you are exporting a small project, the task may complete before you are able to click the icon.
Exporting a Control Project
To export a Control project to file, proceed as follows.
Step
1
2
3
4
Action
In the Control Project Browser , right-click the Control project that you want to export and select Export .
Result: The Export window opens and displays the Control project that you have selected.
NOTE: To be able to export two or more Control projects, for example, to export peer to peer communication data, right-click the system root folder.
Select the project components that you want to export.
NOTE: If you had right-clicked the system root folder, you can select which projects you want to export.
Click OK .
Result: The Export window closes and the Export dialog box opens.
Select a location where you want to save the export file, enter a file name, and click
Save .
Result: The software creates the export file containing the selected Control project information.
NOTE: If you click Cancel , the Export dialog box closes without creating the export file and the selection you have made in the Export window is discarded.
Importing Control Projects
Overview
The Import command lets you import data of a Control project from an export file
(.sbk), which was created by using the
functionality of the
Project Explorer .
If the system into which you are importing a Control project already contains a
Control project with the same identifier, the software compares the data of both projects. It then proceeds with the partial import, according to the import settings that you select and the import rules that are described in this topic.
However, you cannot do a partial import of data related to
communication mapping, page 424
. You need to import either the complete communication channel and/or peer to peer
that is contained in the export file for selected Control projects or nothing. Importing it overrides any existing communication mapping and variable mappings. Specific conditions apply and are described in this topic.
If the software detects conflicts related to communication mapping before import, you have the choice to import the Control without communication mapping or to cancel the operation. If it detects conflicts during the import process, the entire import operation is canceled and rolled back.
NOTE: If the export file also contains information of a Supervision project, you can see the data that is related to the Supervision project, and have the choice to
as well.
Importing M580 Safety Control Projects
For specific information about importing M580 safety Control projects, refer to the topic describing how to
engineer systems with M580 safety controllers, page 581 .
EIO0000001114.15
211
Software Version Compatibility
The version of EcoStruxure Process Expert that you use to import the information contained in the export file must be the same as the version that you used to create the export file (a service pack is considered the same version); otherwise you cannot proceed with the import.
Naming Rules for Variable Names and Section Identifiers
Names of variables and identifiers of sections that you import into a system need to satisfy the
for the generation process to complete successfully.
Checking Consistency After Import
After importing a Control project, perform a consistency check. This allows the software to identify if the constituents of the project into which you have imported are not consistent with the facets that are assigned to the project.
For more information on the process, refer to the topic
Consistency Management, page 347
.
Item
System_n
ControlProject_n
Tasks folder
MAST and FAST task folders
Sections
Safe Program
Import Settings
The table describes which Control project information you can import into a system.
Selected for import (1)
By default
Description
Constituent File (FBD sections only)
Container Naming Rules
Executables
ControlExecutable_n
By default
By default
By default
By default
By default
By default
Project dependent
By default
By default
Unselecting the item excludes any Control project and disables the import of the export file.
Unselect the item to exclude the entire project from the import process.
You cannot unselect the item.
You cannot unselect the item.
You can select sections individually.
Displays the identifier and path of the facets that are assigned to the section.
A Constituent File is associated to each FBD section.
Selecting an FBD section imports any facets that are assigned to this section.
NOTE: A section can be selected only if it is
tagged with a green dot, page 220 .
If the identifier of the imported FBD section already exists in the target project, the selection of the constituent file has an impact on the
NOTE: The Constituent File check box is selected and disabled if the identifier of the imported FBD section does not exist in the target project.
The item is available only for
M580 safety Control projects, page 577 .
Unselect the item to exclude the entire safety program from the import process.
are imported only if a Control project with the same identifier does not exist in the target system.
You cannot unselect the item.
You can select each Control executable and its contents individually.
Selecting the Control executable automatically selects any existing mapping.
212 EIO0000001114.15
Item Selected for import (1)
By default
Description
Service Mappings
Hardware Mappings By default
Any data related to the service mapping including any required contents in the Contents Repository.
Selecting the item automatically selects the associated executable.
You cannot select hardware mappings individually.
Selecting the item automatically selects the associated executable and service mapping.
Communication
Mappings
Built Participant Project
By default
By default
The complete data related to the communication mapping.
Selecting the item automatically selects the associated executable and service mapping.
Represents the Control Participant file (.stu).
It appears and is selected only if the built Participant project was selected at the time of export.
Backups By default You can select data backup files individually
The time stamp and description of the
are shown. The format of the time stamp is YYYYMMDDHHMMSS.
Importing a data backup file makes it available in the Manage Data
Backup File
and Deploy Data
.
(1) The information needs to be contained in the export file to be selected.
Import Rules for Project-Related Objects
Facets assigned to Control projects are related to instances of the application and mappings of project executables are related to entities of the topology. For the
Control project import to complete entirely, these project-related objects need to be present in the system in which you want to import the project.
The table describes the impact on the import operation when project-related objects are not present or have a different configuration. It also describes the corrective action.
Project-related object that is not present or different
An instance whose facets are assigned to the
Control project that you are importing (same identifier, template identifier, template version, and status Valid ) is not present.
Impact if not present in the target system Required action
An element of the instance creating a facet that is being imported is not selected.
You can import the project but not the sections to which such facets are assigned. This requires that the project contains at least one section that
, even empty.
asking you to confirm the partial import.
NOTE: Performing a partial import may cancel the entire import operation if
import rules for peer to peer communication variables, page 218
are not satisfied.
The facet that is normally created by this element is not imported.
The notification panel provides information about the facet that is not imported.
For example, you import a Control project to which the facet created by the Maintenance element of an instance is assigned but in the application of the target system, the
Maintenance element of the same instance is not selected.
Do either of the following first to create missing instances:
• Use the
export/import functionality, page 168
of the
Application Explorer to import missing instances.
• Create instances. This may require importing templates first.
You can obtain information about the missing instances and their templates in the tooltip of the container that is tagged with a red dot.
Edit the instance in the Application
Explorer and select the corresponding element.
EIO0000001114.15
213
Project-related object that is not present or different
The properties of an instance are different from the instance configuration at the time of export.
The difference lies in the
(services) and/or the parameter values, page
.
A topological entity to which you have mapped the executable of the project (service and/or communication) that you are importing (same identifier, same devices, and same services).
Impact if not present in the target system
The assignment status of facets that are imported is set to Out Of Date .
You can import the project but not the Control project executable and any of its associated mappings.
Required action
Generate the project o section to apply the changes.
Use the
export-import functionality, page 408
of the Topology
Explorer first to create the missing topological entities.
Import Rules for Sections
The table describes the import rules that apply to FBD and non-FBD sections with respect to the section order when a Control project with the same identifier already exists in the target system.
Result in Control project of target system after import
Contents of export file selected for import
Section1, order 0
Section2, order 1
Section4, order 2
Section in Control project of target system
Section3, order 0
Section1, order 1
Section3, order 0
Section1, order 1
Section2, order 2
Section4, order 3
The order of existing sections is maintained and imported sections are added at the end.
NOTE: If a section already exists in the target system, its order is maintained even if the order of the section in the export file is different.
The table describes the import rules that apply to non-FBD sections when a
Control project with the same identifier already exists in the target system.
Contents of export file selected for import
Section1
Section in
Control project of target system
Section1
Result in Control project of target system after import
Section1 Section2
Section1 from export file replaces Section1 in the Control project of target of the target system.
Section1 and Section2 exist in the Control project of target of the target system.
214
Import Rules for Facets
The software applies import rules to facets if the system into which you are importing a Control project already contains a Control project with the same identifier.
The following are the general import rules that the software applies if facets with the same identifier contained in FBD sections with the same identifier exist in both the target project and the export file that you are importing:
• If you select the constituent file of the section:
◦ Facets from the export file overwrite facets of the target system and maintain the state they have in the export file.
◦ Facets that exist only in the export file are imported into the target system and maintain the state they have in the export file.
◦ Facets that exist only in the target system become Assigned and Non
Generated . If the status of the facet is deleted, unassigned, or unlinked, the software removes the facet from the section after import.
EIO0000001114.15
EIO0000001114.15
• If you unselect the constituent file of the section:
◦ Facets with the same identifier maintain the state they have in the target system.
◦ Facets that exist only in the export file are imported into the target system and become Assigned and Non Generated unless the generation status of the facet is Unlinked .
◦ Facets that exist only in the target system maintain their state.
NOTE: The software changes the assignment status of any facet of an instance to Out Of Date if a
property of an instance, page 134
is different from what it was at the time of export. The notification panel provides information about the change of the assignment status after import is complete.
The following tables illustrate these import rules based on the different use cases.
The section and facet names are examples, and represent sections and facets in the MAST or FAST task folders of the projects.
If you select the FBD section Constituent File check box.
Contents of export file selected for import
Item in Control project of target system
Section identifier is identical
Section1 Facet1 Section1 –
Section1
Section1
Facet1
Facet1
Section1
Section1
Facet1
Facet2
Result in Control project of target system after import
Facet1 from export file with status from export file.
Facet1 from export file with status from export file.
Facet1 from export file with status from export file.
Facet2 with status non-generated.
The software adds imported facets at the end of existing facets in the target section.
If the status of Facet2 is deleted, unassigned or unlinked, the facet is removed from the section after import.
Section identifier does not exist in target project
Section2 Facet3 – – Section2 with Facet3 from export file with status of export file.
The software adds imported sections at the end of existing sections in the target task folder.
– The item does not exist
If you unselect the FBD section Constituent File check box.
Contents of export file selected for import
Item in Control project of target system
Section identifier is identical
Section1 Facet1 Section1 –
Result in Control project of target system after import
Section1
Section1
Facet1 Section1 Facet1
Facet1 Section1 Facet2
Facet1 from export file with status non-generated unless generation status of Facet1 is Unlinked .
Facet1 from target system with same status.
Facet1 from target system with status nongenerated.
Facet2 from target system with same status.
The software adds imported facets at the end of existing facets in the target section.
– The item does not exist
Import Rules for Executables and Mappings
Communication mapping is created with the mapping information from the export file if the following conditions are fulfilled:
215
216
• For peer to peer communication: The export file contains
of both the consumer and the owner projects and the corresponding elements are selected for import.
• The I/O scanner service of the client controller that is mapped to the imported executable is enabled.
• Sufficient free memory is available in the client and/or server memory length property of the controllers to fit the communication channels that exist in the export file.
• The client and server controllers that are mapped to the imported executables are connected to the same Ethernet network.
• For I/O device communication channels, in addition:
◦ The I/O scanner service that is imported needs to match with the service of the topological I/O device entity with which communication is to be implemented. Refer to the description of the Service column in the Device
IO section of the Communication Mapping Editor
◦ The topological I/O device entity with which communication is to be implemented needs to be connected to the same Ethernet network as the controller.
If the export file contains mapped peer to peer variables, refer to the topic describing
import rules for peer to peer communication variables, page 218 .
If the software is not able to import communication mappings, a
indicating the reason.
The software updates the
of a Built executable after import depending on the scenario.
NOTE: if the system into which you are importing a Control project already contains a Control project and an executable with the same identifier, the software applies import rules to executables and service, hardware, and communication mappings. These rules are described in the following tables.
The table describes the import rules that apply to Built executables based on different scenarios.
Resulting built state in Control project of target system after import
Contents of export file selected for import
Item in Control project of target system
Executable1
Executable1
Executable1
Does not exist
Executable1
Executable2
Out Of Date
Out Of Date
Executable1: Out Of Date.
Executable2: Out Of Date.
The table describes the import rules that apply to mappings based on different scenarios.
Contents of export file selected for import
Service mapping
Hardware mapping
Item in Control project of target system
Result in Control project of target system after import
Exists
Does not exist
Exists
Does not exist
Service mapping of target system is not changed.
Service mapping is created with the mapping information from the export file.
Hardware mapping of the target project is updated with the mapping information from the export file in the following way:
• Existing mappings of the target project are overwritten.
• New mappings are created.
• Mappings of the target project that are not affected by the import process are maintained.
NOTE: Any new mapping for which the required mapping interface from the topological instance of the target project is not present is rejected.
Hardware mapping is created with the mapping information from the export file.
EIO0000001114.15
Contents of export file selected for import
Item in Control project of target system
Result in Control project of target system after import
Communication mapping
Communication mapping
Exists
Does not exist
NOTE: Any mapping for which the required mapping interface from the topological instance of the target project is not present is rejected.
Communication mapping is overwritten as a whole if the following conditions are fulfilled:
• For peer to peer communication: The export file contains
of both the consumer and the owner projects and the corresponding elements are selected for import.
• Sufficient free memory is available in the client and/or server memory length property of the controllers to fit the communication channels that exist in the export file.
• For I/O device communication channels, in addition:
◦ The I/O scanner service that is imported needs to match with the service of the topological I/O device entity with which communication is to be implemented. Refer to the description of the
Service column in the Device IO section of the
Communication Mapping Editor
.
◦ The topological I/O device entity with which communication is to be implemented needs to be connected to the same Ethernet network as the controller.
• If a service mapping exists, it needs to be identical to the service mapping contained in the export file for the
Control project that you want to import.
NOTE: If the export file contains mapped peer to peer variables, refer to the topic describing
import rules for peer to peer communication variables, page 218 .
Communication mapping is created with the mapping information from the export file if the following conditions are fulfilled:
• For peer to peer communication: The export file contains
of both the consumer and the owner projects and the corresponding elements are selected for import.
• The I/O scanner service of the client controller that is mapped to the imported executable is enabled.
• Sufficient free memory is available in the client and/or server memory length property of the controllers to fit the communication channels that exist in the export file.
• The client and server controllers that are mapped to the imported executables are connected to the same
Ethernet network.
• For I/O device communication channels, in addition:
◦ The I/O scanner service that is imported needs to match with the service of the topological I/O device entity with which communication is to be implemented. Refer to the description of the
Service column in the Device IO section of the
Communication Mapping Editor
.
◦ The topological I/O device entity with which communication is to be implemented needs to be connected to the same Ethernet network as the controller.
• If a service mapping exists, it needs to be identical to the service mapping contained in the export file for the
Control project that you want to import.
NOTE: If the export file contains mapped peer to peer variables, refer to the topic describing
import rules for peer to peer communication variables, page 218 .
EIO0000001114.15
217
218
Import Rules for Peer to Peer Communication Variables
To be able to import communication mappings as a whole, the software also needs to be able to create variable mappings that exist in the export file.
If none of the imported Control projects exist in the target system, the necessary variables are created, given that import rules for project-related items are satisfied.
If either Control project that you are importing already exists in the target system but a variable that is mapped to a peer to peer communication channel present in the export file has been modified or deleted, two scenarios are possible:
• The variable was created by refining the Control project. In such case, when you import communication mappings, the software is not able to recreate the variable. Therefore, it cannot create variables mappings and the entire import process is canceled and rolled back. The software displays a dialog box to inform you.
You need to recreate the variable manually to be able to import communication mapping.
• The variable was created by a facet assigned to the Control project. In such case, if you select the constituent file of the section to which the facet is assigned, the import process is able to recreate the required variable and the import succeeds, given that other necessary conditions are fulfilled.
The following example illustrates the second scenario: You have created two
Control projects, Owner and Consumer between which a peer to peer communication channel exists.
Var_1 is mapped to this communication channel.
The variable exists as network variable in Consumer (with P2P as custom attribute) and as variable in Owner .
You have exported both projects with their complete contents and have kept on working on both projects, which altered the communication mapping . After a while, you realize that you are not satisfied with some changes you made and therefore, you want to recover the original projects and communication mapping while keeping some of your changes (for example, you want to keep an FDB section that you have added to Consumer after exporting).
You import the export file in the Projects Explorer where Owner and Consumer
Control exist. However, you have renamed Var_1 in the Owner project.
Because you want to import communication mappings, you have selected both
Control projects in the Import window.
Because Var_1 had been created by a facet that is assigned, for example, to
FBDSection_1 in the Owner Control project, by
selecting the constituent file, page
of FBDSection_1 in the Import window, you are able to recreate the variable and import communication mappings.
NOTE: A network variable can be used only once per project, independently of the number of Control executables that exist in the project.
EIO0000001114.15
The following figure illustrates the import example by using a target system in which the Owner and Consumer projects exist and showing the objects that are selected for import.
EIO0000001114.15
1 FBDSection_1 of Owner Control project showing the facet that creates Var_1
2 Consumer Control project
3 Communication mappings of Consumer
4 Owner Control project
5 Constituent file of FBDSection_1 to which facet that creates Var_1 is assigned
Import Rules for Data Backup Files
When you import a Control project and a Control project with the same identifier already exists in the target system, if you have selected to import the data backup file and a file with the following identical
identification information, page 554
already exists, the file is not imported:
• Time stamp.
• Identifier of the executable.
• Identifier of the controller and role.
• Description.
• Type of data that is backed up.
NOTE: The notification panel displays information about the not imported data backup file.
Opening the Project Import Window
To open the Import window, proceed as follows.
219
Step
1
2
Action
Right-click the system root folder in a Project Browser of the Project Explorer and select Import .
Result: The Import dialog box opens.
Browse to the export file (.sbk) that contains the Control project information that you want to import and click Open .
Result: The Import window opens and displays the contents of the file that you have selected once it has read the data contained in the file. This can take time depending on the number and size of projects contained in the file.
NOTE: You can
Project Import Window
The Import window lets you select Control project information that is contained in an export file and that you can import into an existing system. You can select one or more entire Control Participant project and/or parts of them.
The following figure shows an example of the Import window displaying the contents of a Control project export file. In this example, the check box for FBDSection_2 is cleared because the section cannot be imported. To indicate that at least one item of the Control project is not selected, the check box of parent nodes are filled with a square.
220 EIO0000001114.15
The table indicates the meaning of the colored dots that appear in the Import window next to items of a Control project.
Color code
Green
Red
Yellow
Description
You can import the item.
• At the section level: The section contains at least one facet that is referenced by an instance, which is
not present in the application, page
.
• At the executable level: A
project-related topological object, page 213
is not present in the target system.
A tooltip provides additional information about the issue.
NOTE: You cannot import items that are tagged with a red dot.
The item contains at least one subitem that is tagged with a red dot.
The item can be imported partially only.
NOTE: To expand/collapse a node in the Import window, select the node and press Enter .
Confirmation Dialog Box For Sections That Cannot Be Imported
The following figure shows an example of the dialog box that opens when a section of a Control project selected for import is tagged with a red dot and you click OK in the Import window.
If you are importing also Supervision projects, containers are grouped by
Participant then by project.
EIO0000001114.15
Button
Yes
No
Description
Closes the dialog box, the Import window, and imports the selected projects without sections tagged with a red dot.
Closes the dialog box and reverts to the Import window without importing projects. You can modify the selection of projects or cancel the import operation.
221
Confirmation Dialog Box For Communication Mappings That
Cannot Be Imported
The following figure shows an example of the dialog box that opens when you click OK in the Import window and the software detects that communication mappings selected for import cannot be imported. It indicates the identifier of the project and the corresponding executable, and the reason. The Import window is closed before the dialog box opens.
222
Button
Yes
No
Description
Closes the dialog box and imports the selected projects without communication mappings.
NOTE: This may result in variable mappings being present in the target system while the required variables do not exist.
Closes the dialog box and cancels the import operation.
Aborting Import Tasks
The abort icon is displayed in the
at two different stages of the import process:
• After clicking Open when you
select the export file, page 219 . Clicking the
icon cancels the operation to read the contents of the export file. The Import window does not open.
• After confirming the import by clicking OK in the Import window, the abort icon is displayed. Clicking the icon cancels the task. The project is not imported.
Only the user who has selected the command is allowed to abort it.
NOTE: If you are importing a small project, each task may complete before you are able to click the icon.
Importing a Control Project
To import data of a Control project into an existing system, proceed as follows.
EIO0000001114.15
Step Action
1 In the Import
, select the items that you want to import.
2 Click OK .
3
4
5
Result
-
If applicable rules are satisfied, the software:
• Applies the import rules based on your import selection.
• Proceeds with the import.
• Replaces existing communication mapping if you had selected to import them.
• Displays an import summary dialog box.
The Control Participant window opens.
In the Project Browser , right-click the Control project into which you have made the import and select
Refine .
Click the
consistency check button, page 349
.
Take the necessary
.
The software proceeds with a consistency check and displays a notification to report findings once the check is completed.
-
NOTE: If the software detects incompatibilities during the import process, it cancels and rolls back the import operation, and displays a dialog box to inform you. In such case, take the necessary corrective actions and start the import over. For example, if the incompatibility is related to variable mappings, you can clear the check box next to CommunicationMappings to import
Control project data but no communication mapping.
Importing a Control Expert Project
Overview
The Import Control Project command allows you to create a Control project in the Project Explorer by importing data of a project that was created by using
Control Expert and which is contained in a compatible project file (.stu or .xef
format).
After import, you will have access to the same commands from the project node as if you had created the project in the Project Browser .
Project Compatibility
To be able to import a project created with Control Expert, the following requirements need to be met:
• The version of Control Expert with which the export file was created needs to be identical to the version of the Control Participant. To determine the version of the Control Participant, open it (for example, by refining a Control project) and open the About dialog box from the Help menu.
• The version of the EcoStruxure Control Expert DTM Library that is installed in
Control Expert needs to be the same as the one installed in the Control
Participant. For information on the installed version, refer to the platform release notes.
EIO0000001114.15
223
Imported Data
Project data contained in the file (stu or .xef)
FBD sections
Sections in the following programming languages:
• Ladder Diagram (LD)
• Instruction List (IL)
• Structured Text (ST)
• Sequential Function
Chart (SFC)
• Ladder Logic 984
(LL984)
Constituents of any section
Configuration
Other global project information (for example, variables, types, project settings...)
Project platform
Contained in the
Control
Participant project after import
Yes
Yes
Visible in the Project Explorer after import
Yes
Sections are created in their respective
MAST and FAST task folders in the
Assignment Editor .
Yes
No
Yes
Yes
No
Refine the imported project to view the information.
NOTE: Only data related to the program becomes part of the logical
Control project. Other data (for example, data related to the configuration) is ignored during build although it is visible when you refine the logical project.
Yes
Controller Family
.
NOTE: The name of the file containing the project data becomes the identifier of the Control project that the software creates during the import process.
Importing a Control Expert Project
To import a Control Expert project into an existing system, proceed as follows.
Step
1
2
3
Action
Right-click the system root folder in the Control Project Browser of the Project
Explorer and select Import Control Project .
Result: The Open dialog box opens.
Select the file format that you want to import.
Browse to the location of the Control Expert project file that you want to import and click
Open .
Result: The software creates a Control project and displays it in the Control Project
Browser .
Managing Data Backup Files
Overview
The Manage Data Backup Files dialog box lets you view and delete
that exist for all the executables of a Control Participant project.
The dialog box shows the information that was associated to each backup file at the time of creation, including the type of data that was selected.
By default, backup files are listed in descending order of time stamp (most recent one on top). You can
the information that is displayed.
224 EIO0000001114.15
Opening the Manage Data Backup Files Dialog Box
To open the Manage Data Backup Files dialog box, right-click a Control
Participant project in the Project Browser and select Manage Data Backup
Files .
If no data backup file exists, the command is not available.
Manage Data Backup Files Dialog Box
The following figure shows an example of the Manage Data Backup Files dialog box, which shows the data backup files that have been created for executables of
ControlProject_1 .
EIO0000001114.15
Column header
Description
Time Stamp Date and time of the backup file creation.
Description Description that was entered when the backup file was created.
User Name of the user who was logged on when the backup file was created.
Executable
Controller
%M
%MW
Identifier of the Control executable whose data is contained in the backup file.
Identifier of the controller that was running the executable whose data was backed up.
For redundant controllers, it also indicates the role of the controller that was selected when the backup file was created.
Indicates the memory range of located variables of boolean data type that are contained in the backup file.
If no such data was selected during data backup, the value shown is N/A .
Indicates the memory range of located variables of WORD data type that are contained in the backup file.
If no such data was selected during data backup, the value shown is N/A .
Unlocated
Variables
Unlocated
FBs
True indicates that this type of data was selected during data backup.
Possible values:
• True
• False
Deleting Data Backup Files
To delete a data backup file, select the corresponding row and click Delete . The backup file is deleted after you confirm the command.
You can select more than one backup file at a time.
NOTE: When you delete a Control Participant project or the controller to which it is deployed, the corresponding data backup files are deleted as well.
225
Supervision Project Definition Stage
Overview
This section describes how to create Supervision projects of a system.
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
Internal Supervision Architecture
Task Description
As a reminder, the following figure describes the internal Supervision architecture for the execution of tasks:
1 Report scheduling and execution
2 Alarm acquisition and processing
3 Trend acquisition and storage
4 I/O communications
5 Graphical interface, events, local I/O, and client services
NOTE: Report, alarm, and trend servers also act as clients of the I/O server.
Creating Supervision Projects
Creating Supervision Projects
To create a Supervision project, proceed as follows.
Step
1
Action
In the Supervision Project Browser , right-click the system root folder and select
Create Supervision Project .
Result: The Supervision is shown in the tree view.
NOTE: For each system, you can create as many Supervision projects as needed to meet the requirements of the system.
Supervision Project Actions
The table describes the Supervision project context menu commands.
226 EIO0000001114.15
EIO0000001114.15
Command
Assign
Facets
Description
Creates a new cluster with its default contents and displays it in the tree view.
Opens a dialog box that indicates the last action that was performed and a summary of the result.
Applies to
Project Definition stage
Opens the Assignment Editor , which lets you create and manage tag containers and Supervision pages of the
Supervision project and assign facets to them.
Generate
Refine
Starts a process that creates and/or updates in the
Supervision Participant project the data of the entire
Supervision project.
Opens the Supervision Participant, which allows you to modify the project.
Opens the Supervision Participant, which allows you to change advanced project settings that will be activated in the station nodes where you deploy the Supervision project.
Refinement stage
Opens a dialog box, which allows you to:
• Add external included projects to be deployed to the
Supervision nodes.
• To remove included projects that are attached to the
Supervision and stored in the contents repository.
NOTE: You cannot add an included project if the software has already added to the Participant project an included project with the same name.
Opens a dialog box, which allows you to:
• Attach external files to be deployed to the Supervision nodes.
• To remove files that are attached to the Supervision project and stored in the contents repository.
Opens a Save As dialog box, which allows you to create an export file containing the Supervision project information.
Settings Opens the Settings
window, page 205 , which lets you
configure various project-related settings.
Delete Deletes the Supervision project including components, assignments, and mappings.
Project Definition stage
Assignment stage
–
Rename
Properties
Allows you to enter a new identifier for the project.
Opens the Properties window, which allows you to edit the properties of the Supervision project.
–
–
Containers Node Actions
The table describes the Containers node context menu commands.
Command
Assign
Facets
Create Tag
Container
Create Page
Generate
Description
Opens the Assignment Editor , which lets you create and manage tag containers and Supervision pages of all clusters and assign facets to them.
Lets you
create a tag container, page 263
in an existing cluster.
The Assignment Editor opens in the background.
Opens the Assignment Editor and
creates a Supervision page, page 267
in the project.
Starts a process to create and/or update in the Supervision
Participant project the data for the containers of all clusters that exist in the project.
Applies to
227
228
Pages Node Actions
The table describes the Pages node context menu commands.
Command
Assign
Facets
Create Page
Generate
Description
Opens the Assignment Editor , which lets you create and manage tag containers and Supervision pages of all clusters and assign facets to them.
Opens the Assignment Editor and creates a Supervision page in the project.
Starts a process to create and/or update in the Supervision
Participant project the data for the pages that exist in the project.
Applies to
Cluster Node Actions
For a description of the context menu commands, refer to the topic describing how to
Tags Node Actions
The table describes the Tags node context menu commands.
Command
Assign
Facets
Generate
Description
Opens the Assignment Editor , which lets you create and manage tag containers and Supervision pages of the parent cluster and assign facets to them.
Starts the generation process of tag containers and pages that exist in the parent cluster to populate new tags, update out-of-date tags, and/or remove deleted tags in the
Supervision Participant project.
Applies to
Services Node Actions
The table describes some of the Services node context menu commands. For a description of the other commands, refer to the topic describing how to
Supervision servers and clients, page 230
.
Command
Open
Generate
Description
Opens the Services window, which lets you view and edit properties of the Alarm, report, and trend servers as well as clients that exist in the parent cluster.
Starts a process to create and/or update in the Supervision
Participant project the data related to services.
Applies to
ClientEvents and ServerEvents Node Actions
The table describes the ClientEvents and ServerEvents nodes context menu commands.
Command
Open
Generate
Description
Opens the corresponding window, which lets you view the
Supervision facets that are assigned to client or server events in the parent cluster.
Starts a process to create and/or update in the Supervision
Participant project the data related to services in the parent cluster.
Applies to
EIO0000001114.15
Executables Node Actions
The table describes the Executables node context menu commands.
Command
Create
Executable
Description
Creates one or more
Supervision executables, page 457
, which let you associate the Supervision project infrastructure to stations nodes and the I/O devices to controllers.
Applies to
Mapping Stage
Supervision Project Properties
Right-click the Supervision project and select Properties .
You can edit the following items.
Item
General Identifier
Description
The identifier of the Supervision project, which must be unique within the system.
Description Optional.
You can enter a description of the project with free form text.
Creating Supervision Project Components
Overview
This section describes how to use the Project Explorer to create the components of Supervision projects.
During build, one or more OPC Factory Server and/or OPC UA Server Expert configuration files (.xml) are automatically
based on the configuration of properties of the Supervision project components.
For information on how to create tag containers and Supervision pages, refer to the topic describing the
creation of containers, page 256
in the Assignment stage.
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
Creating Clusters
Creating Clusters
To create a cluster, proceed as follows.
Step
1
Action
Right-click the Supervision project and select Create Cluster .
Result: The software creates a new cluster node and its child nodes.
Cluster Actions
The table describes the cluster context menu commands.
EIO0000001114.15
229
Command
Description
Generate Starts the generation process to populate the database of the Supervision Participant project for this cluster.
Delete Deletes the cluster including its contents and unassigns the assigned Supervision data facets.
Lets you enter a new identifier for the cluster.
Rename
Properties
Opens the Properties window, which allows you to edit the properties of the cluster.
Cluster Properties
To open the Properties window of the cluster, right-click the cluster and select
Properties .
You can edit the following items,
Item
General
Description
Identifier The identifier must be unique within the Supervision project and satisfy applicable
.
NOTE: Changing the identifier of the cluster changes the assignment status of facets that are assigned to a tag container of the cluster to Out Of Date .
Description Optional.
You can enter a description of the cluster with free form text.
Creating Supervision Servers and Clients
Overview
You can create Supervision servers in the Services node of a cluster.
The I/O server instance represents a server that is set up on an operation server
(see EcoStruxure ™ Process Expert, Installation and Configuration Guide), on which Supervision and OPC Factory Server or OPC UA Server Expert software is installed. The operation server is represented in the topology of the system by a
station node, page 379 , which acts as an engine to run the Supervision project.
The alarm, trend, and report server instances represent servers that are set up on a single or distinct operation servers, on which Supervision software is installed.
You can create up to two alarm, report, and trend servers per cluster.
NOTE: Generate the Supervision project after you make changes related to components described in this topic.
Creating Supervision Servers
To create I/O, alarm, trend, and report servers in the cluster, proceed as follows.
Step
1
Action
Right-click the Services node and select the corresponding command.
Result: The new server is created.
NOTE: Only I/O servers are shown in the project browser. To view other servers, open the Services node.
NOTE: The software may automatically create servers during the assignment stage if you have not created them already. For more information, refer to the
Supervision project
.
230 EIO0000001114.15
Supervision I/O Server Properties
To open the Properties window of an I/O server, right-click the server and select
Properties .
You can edit the following items.
Item
General Identifier
Description
Attributes
Port
Legacy Port
Description
The identifier must be unique within the Supervision project.
Optional.
You can enter a description of the server with free form text.
Communication port the server listens on.
Default value: 2082.
Communication port that is used for legacy connections to the server.
Default value: 2078.
Supervision Servers Common Properties
To view the alarm, trend, and report servers that exist in the cluster and their properties, right-click the Services node and select Open .
You can view and/or edit the following items.
Item
General
Attributes
Identifier
Description
Description
The identifier must be unique within the Supervision project.
Default value: Server_n_P where:
• Server is the name of the service provided by the server (for example, Alarm ).
• n is an incremental number starting at 1.
• P stands for primary. The suffix of the second server instance that you create is _S for standby, even if you rename the first instance.
Optional.
You can enter a description of the server with free form text.
Port Communication port the server listens on.
Default value:
• Alarm server: 2080
• Report server: 2084
• Trend server: 2085
Edit the value if you are running more than one server on the station node.
Communication port that is used for legacy connections to the server.
Legacy Port
Default value:
• Alarm server: 2076
• Report server: 2075
• Trend server: 2077
Database Port The attribute is available for alarm servers only.
Communication port the server database listens on.
Default value: 5482
Edit the value if you are running more than one alarm server on the station node.
EIO0000001114.15
231
Item
Mode
Extended
Memory
Description
You can select one of the following values from the menu:
• None
• Primary : Defines the server as the primary server. Default value for the server with _P suffix.
• Standby : Defines the server as the standby server. Default value for the server with _S suffix.
The attribute is available for alarm servers only.
Possible values:
• False : Default value.
• True : The alarm server operates in 64-bit extended memory mode. This allows the alarm server process to utilize memory beyond the 4GB limit.
For more information on this mode of operation, refer to Alarm Server
Process in the help of the Supervision Participant.
Creating Supervision Clients
You can create Supervision Clients in the Services node of a cluster.
The client instance can represent a Supervision client (runtime) that runs:
• On the operation server.
• On an operator station.
To create a client for the Supervision project, proceed as follows.
Step
1
Action
Right-click the Services node and select Create Client .
Result: The client is created but not shown in the project browser.
Supervision Client Properties
To view the clients that exist in the cluster and their properties, right-click the
Services node and select Open .
You can edit the following items.
Item
General Identifier
Description
Description
The identifier must be unique within the Supervision project.
Optional.
You can enter a description of the client with free form text.
Creating I/O Devices
Overview
Typically, an I/O device is created for one controller. If the data is present in two controllers, create an additional I/O device for the second controller manually.
Create a second
for data of the second controller and associate this tag container to the second I/O device.
The software creates
additional I/O devices, page 234
when you create calculated or disk variable tags.
NOTE:
Monitoring data of a device, page 639
communicating by using the
Modbus TCP protocol (or Modbus through an Ethernet gateway) from the
Supervision infrastructure also requires a dedicated I/O device per Modbus device.
232 EIO0000001114.15
Item
General
Attributes
Prerequisites
An I/O server must exist in the cluster.
Creating I/O Devices
To create an I/O device in the cluster, proceed as follows.
Step
1
Action
Expand the Services node and the I/O server, right-click the IODevices node, and select Create IO Device .
Result: The I/O device is created but not shown in the project browser.
NOTE: The software automatically creates the I/O device during the assignment stage if you have not created it already. For more information, refer to the Supervision project
.
Identifier
Description
Address
StartupMode
Priority
Memory
I/O Device Properties
To view the I/O devices that exist in the cluster and their properties, right-click the
IODevices node and select Open .
You can edit the following items.
Description
The identifier must be unique within the Supervision project.
NOTE: Changing the identifier of the I/O device changes the assignment status of facets that are assigned to the tag container that is associated with the I/O device to
Out Of Date if they were generated.
Optional.
You can enter a description of the I/O device with free form text.
The value needs to be compatible with the protocol that is selected for the associated tag container.
The default value is the alias name for OPC Factory Server: Alias_<IODevice_n> where
<IODevice_n> corresponds to the value of Identifier .
NOTE: The attribute is disabled and cleared when Protocol of the associated tag container is set to OPCUA or OPCUA Embedded .
For these two protocols, the following temporary address is created for the I/O device when you generate the Supervision project or the cluster:
• For OPCUA : opc.tcp://127.0.0.x:49152/OPCUAServerExpert
• For OPCUA Embedded : opc.tcp://127.0.0.x:4840
During
, the IP address placeholder (127.0.0.x) and the port value are updated based on the mapping.
Select the role of the I/O device in terms of communication with the controller:
• Primary (default value)
• Standby
• StandbyWrite
• None
You can assign the order in which the I/O device attempts to communicate with the tag container that it is associated with in case more than one I/O device is associated with the container.
Set the values as follows depending on the role of the I/O device:
• Primary: 1 or blank (default value)
• Secondary: 2 or higher
NOTE: If you associate two I/O devices configured as primary to one tag container, verify that Priority is configured with a different value for each.
Select one of the following values depending on how you want the I/O device to communicate with the controller:
False : Default value. The I/O device is online with the controller
EIO0000001114.15
233
Item
Relationships TagContainer
Ports
Description
True : The I/O device is not connected to the controller. Select this setting for testing purposes, for example.
Select the tag container that is associated with the I/O device.
NOTE:
• By default, the software associates the I/O device with the tag container for which the I/O device has been
automatically created, page 281
during the assignment of Supervision data facets.
• Changing the relationship of the I/O device to the tag container changes the assignment status of facets assigned to the tag containers affected by this change to Out Of Date .
Select the
that is associated to the I/O device.
NOTE: By default, the software associates the I/O device with either the communication port that has been
automatically created, page 281
during the assignment of Supervision data facets or with the one that you have created manually.
I/O Devices Created for Calculated and Disk Variable Tags
When you generate a Supervision data facet that references a non-disabled
Calculated Variable Tag or Disk Variable Tag element (see EcoStruxure ™
Process Expert, Global Templates, Reference Manual), one specific I/O device is automatically created per I/O server with the same properties as the default I/O device except for the following. These specific I/O devices are only visible when you refine the Supervision project.
Property
Identifier
Address
Ports
Memory
Persist
For a calculated variable tag
CicodeIODevice_n where is an integer starting at 1 so that the identifier remains unique within the I/
O sever.
Blank
Blank
Same value as default I/O device
For a disk variable tag
Disk_IODeviceID_n where:
• IODeviceID is the identifier of the I/O device that is associated to the tag container to which the data facet is assigned.
• n is an optional integer starting at 1 that is added so that the identifier remains unique within the I/O sever.
Blank
Blank
True
True
Creating Communication Ports
Overview
Before you can create a communication port, you need to create a communication board unless one already exists.
You need to create a communication board for each communication driver that you are using. For example, if you are using both OFSOPC and OPCUA, create one board for each and configure them accordingly.
To view the communication ports that exist, right-click a board and select Open .
Prerequisites
An I/O server must exist in the cluster.
234 EIO0000001114.15
EIO0000001114.15
Creating a Communication Board
To create a communication board, proceed as follows:
Step
1
Action
Expand the Services node and the I/O server, right-click the Communications node, and select Create Board .
Result: The board is created.
NOTE:
• The software automatically creates one communication board and port during the assignment stage if you have not created it already. For more information, refer to the Supervision
.
• Deleting a communication board deletes the associated communication ports.
Communication Board Properties
To open the Properties window of the communication board, right-click it, and select Properties .
You can edit the following items. For details, refer to Board Properties in the help of the Supervision Participant.
Item
General Identifier
Attributes
Description
Protocol
Address
Description
The identifier must be unique within the I/O server.
16 characters maximum.
Optional.
You can enter a description of the board with free form text.
Indicates the protocol for communicating with the I/O device and that is to be used for configuring the I/O device.
When the protocol for the tag container is set to OPCUA Embedded , select OPCUA .
When you configure a
user-defined protocol for a tag container, page
, enter a protocol for the board that is compatible and installed in the Supervision Participant. To verify which ones are installed, refine the Supervision Participant project and expand an entry in the Board
Type column of Components & Mapping in the Topology activity.
Default value:
• Same as Protocol (that is, OFSOPC or OPCUA ) if the value of
Protocol for all the tag containers that are associated to an I/O device whose communication port is associated to the board is the same; otherwise, OFSOPC .
• OFSOPC when you create the board manually.
Default value: 0 when the board is created by the software.
NOTE: The OFSOPC driver configuration implements an automatic and adaptive strategy, creating and deleting OPC groups and OPC items dynamically to maximize throughput. For information on other parameters affecting performance when using this driver configuration, refer to
Performance Considerations (see EcoStruxure ™ Process Expert, Supervision
Participant Services, User Guide).
NOTE: For the OPCUA driver, the software adds driver-specific parameters to the citect.ini file (see EcoStruxure ™ Process Expert, Supervision Participant
Services, User Guide) (for example, subscription and connection parameters), which are configured with default values and apply to a given I/O device. For details, refer to OPCUA Driver in the Driver Reference Help of the Supervision
Participant.
235
Creating Communication Ports
For each communication board, you can create several communication ports.
To create a communication port, proceed as follows.
Step
1
Action
Expand the Services node, right-click the board, and select Create Port .
Result: The port is created but not shown in the project browser.
Communication Port Properties
To view the ports that exist for a board and their properties, right-click the board and select Open .
You can edit the following items.
Item
General
Attributes
Relationships
Identifier
Description
Port Number
Special Opt
IoDevice
Description
The identifier must be unique within the I/O server.
Optional.
You can enter a description of the port with free text.
Interrupt number of the port.
Leave it blank if you are using the COM port of the computer.
Lets you enter any special options that are supported by the board.
32 characters maximum.
For details, refer to Hardware Arrangements in the help of the
Supervision Participant.
Select the I/O devices that are associated with the communication port from the menu.
The
must exist in the Supervision project cluster to be available for selection.
NOTE: By default, the software associates the port with the I/
O device that has been
automatically created, page 281
during the assignment of Supervision data facets. If you have created the I/O device manually, associate it with the port.
Implementing Redundancy
Overview
The Supervision Participant allows you to build redundancy into the system at different levels to help increase the degree of protection and/or reliability. The common ways to implement redundancy are:
• I/O server redundancy
• Alarm, trend, and report server redundancy
• Network redundancy
The following topics describe the additional steps that you need to complete in order to implement such redundancy by starting from a typical Supervision project, which consists of one of each:
• Cluster
• Tag container
• I/O server with its client
• I/O device
• Communication board
236 EIO0000001114.15
EIO0000001114.15
• Communication port
For more information, refer to the topic of the
Supervision Participant help, page
, which describes how to build redundancy into a system.
I/O Server Redundancy
To implement I/O server redundancy, proceed as follows.
5
6
2
3
Step Action
1
4
From the Services node of the Supervision project, create a second I/O server.
From the Services node, create a client for this second I/O server.
From the Communications node of the second I/O server, create a communication board.
From this board, create a communication port.
From the IODevices node of the second I/O server, create an I/O device.
In the properties of the second I/O device, associate the I/O device with the tag container of the Supervision project, which is already associated to the first I/O device.
Result: The software automatically configures the StartupMode of the second I/O device as Standby with Priority 2 (or the next available value).
7
Refer to
Project definition stage
8
9
10
11
12
13
14
15
16
In the same window, configure the Ports property as Port_2 , which is the port of the communication board that you have created in step 4.
In the properties of the communication port of the second I/O server, verify that the port is associated to the standby I/O device under IODevice .
In the properties of the communication board of the second I/O server, configure Protocol with the same values as for the tag container, which is associated to the first I/O device.
From the system root folder, create a station node entity representing the second I/O server.
In the properties of the NIC of this station node, configure the IP address of the NIC.
On this station node, create one Supervision and one OFS service instances.
Connect this station node to the Ethernet network.
Once you have generated the complete Supervision project, from the project executable, perform the service mapping of the second I/O server to the station node that you have created in step 10.
From the project executable, map the standby I/O device to the same controller to which you have mapped the primary I/O device
(communication mapping).
Configuration stage
Mapping stage
Configure the physical computers according to the topology of the system, build, and deploy the Supervision project.
Build and
Deployment stage
Alarm, Trend, or Report Server Redundancy
To implement alarm, trend and/or report server redundancy, proceed as follows.
Step Action
1 From the Services node of the Supervision project, create a second alarm, trend and/or report server.
Result: The software:
• Creates the server with the _s suffix in its identifier.
• Configures its Mode as Standby .
2 From the system root folder, create a station node entity representing each redundant alarm, trend and/or report server.
Refer to
Project definition stage
Configuration stage
237
5
6
Step Action
3 In the Properties window of the NIC of each redundant station node, configure the IP address of each NIC.
4
7
On each redundant station node, create one Supervision service instance.
Connect each redundant station node to the Ethernet network.
Once you have generated the complete Supervision project, from the project executable, map each standby server to the corresponding redundant station node (service mapping).
Configure the physical computers according to the topology of the system, build, and deploy the Supervision project.
Refer to
Mapping stage
Build and
Deployment stage
Network Redundancy
Network redundancy can be implemented for any Supervision station.
To implement network redundancy, for example, on the operation server, proceed as follows.
Step Action
1
2
In the station node entity representing the operation server (I/O server), create a second NIC.
In the Properties window of the second NIC, configure its IP address.
NOTE: It is not required to connect this NIC to an Ethernet network.
3
4
5
Configure the physical computers according to the topology of the system.
Build the Supervision project by using the Build All command.
NOTE: In the service mapping, no additional mapping is required as the engine that is mapped to the IOServer service is the station node.
Deploy the Supervision project either from the executable or from the station node by selecting either NIC.
Result: After restoring the Supervision project on the station node
(operation server), both network addresses are created in the Supervision
Participant and associated to the I/O server.
Refer to
Configuration stage
–
Build and
Mapping stages
Deployment and Execution stages
NOTE: No specific action is required in the Supervision project.
Managing Supervision Projects
Overview
This section describes how to use the Project Explorer to manage Supervision projects and project contents.
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
Exporting a Supervision Project
Overview
The export functionality lets you create a non-editable export file (.sbk), which contains selected Supervision project information.
238 EIO0000001114.15
You can use this data with the Supervision project
functionality to transfer Supervision project information to a different system or merge information from different Supervision projects.
NOTE: To export all the projects (Control and Supervision) of a system at once in one export file, right-click the root folder in either Project Browser , select Export , and follow the export procedure described in this section. Refer also to the topic describing the export and import of
.
Software Version Compatibility
The version of EcoStruxure Process Expert that you use to import the information contained in the export file must be the same as the version that you used to create the export file (a service pack is considered the same version); otherwise you cannot proceed with the import.
Project Related Data
To be able to use the export file for importing a project into a different system, verify that the instances, their templates, and topological entities related to the project exist in the target system
before importing the project, page 244
. Use the
export-import functionality, page 408
of the Topology Explorer first.
NOTE: The parameter values of instances that reference the exported facets are not contained in the export file. However, the export file contains information that allows the software to verify during import if the configuration of an instance is different from when its facets were exported.
Project Export Window
The Supervision project Export window lets you select, which information the export file will contain.
EIO0000001114.15
239
The following figure shows an example of the Export window where the check box for TagContainer_2 has been cleared. To indicate that at least one item of the
Supervision project is not selected, the check box of parent nodes are filled with a square.
240
The table indicates the meaning of the colored dots that appear in the Export window next to items of a Supervision project.
Color code
Green
Red
Yellow
Description
You can export the item.
You cannot export the item because it contains at least one facet with the following state:
• Deleted
• Unassigned
• Out of Date
• Moved
Generate containers that contain facets with such states or clear their check box in the Export window in order to export the Supervision project.
NOTE: You cannot export items that are tagged with a red dot.
Indicates that the item contains at least one subitem that is tagged with a red dot.
The item can be exported partially only.
NOTE: To expand/collapse a node in the Export window, select the node and press Enter .
EIO0000001114.15
EIO0000001114.15
Export Settings
The table describes which Supervision project information you can export.
Item
SupervisionProject_n
Pages node
Pages
Cluster_n
Tags node
Tag containers
Selected for export
Description
By default Unselect the item to exclude the entire project from the export file.
When you select the project, the associated
is exported.
By default You cannot unselect the item.
By default Selecting a page automatically selects any genie facets that are assigned to it.
Selecting a page automatically selects the logical
Participant project.
By default You cannot unselect the item.
By default You cannot unselect the item.
By default You can select tag containers individually.
Selecting a tag container automatically selects any facets that are assigned to it.
Services node
Alarm servers
I/O servers
Communications node
IODevices node
Trend servers
Report servers
Clients
ServerEvents
ClientEvents
Executables
Executable_n
By default You cannot unselect the item.
By default
By default
By default Any associated boards and ports are selected by default.
You cannot unselect the item.
By default Any associated I/O devices are selected by default.
You cannot unselect the item.
By default You cannot unselect the item.
By default
By default
By default
By default
Service
Mappings
By default
By default You can select each executable and its contents individually.
Selecting an executable automatically selects any associated mapping.
By default Contains data related to the service mapping including any required contents in the contents repository.
Communication Mappings
By default Contains data related to the communication mapping.
Built
Participant
Project
By default Represents the Supervision Participant file (.ctz)
(includes the OFS/OPC UA configuration files (.xml)).
It appears and is selected only if its build status is Built or Out Of Date .
Aborting Export Tasks
After confirming the export by clicking Save in the Export dialog box, the abort icon is displayed in the
notification panel, page 54 . Click the icon to cancel the
task. The export file is not created.
241
Only the user who has selected the command is allowed to abort it.
NOTE: If you are exporting a small project, the task may complete before you are able to click the icon.
Exporting a Supervision Project
To export a Supervision project to file, proceed as follows.
Step
1
2
3
4
Action
In the Supervision Project Browser , right-click the Supervision project that you want to export and select Export .
Result: The Export window opens and displays the Supervision project that you have selected.
Select the project components that you want to export.
Click OK .
Result: The Export window clsoes and the Export dialog box opens.
Select a location where you want to save the export file, enter a file name, and click
Save .
Result: The software creates the export file containing the selected Supervision project information.
NOTE: If you click Cancel , the the Export dialog box closes without creating the export file and the selection you have made in the Export window is discarded.
Importing a Supervision Project
Overview
The Import command lets you import data of a Supervision project from an export file (.sbk), which was created by using the
functionality of the
Project Explorer .
If the system into which you are importing a Supervision project already contains a
Supervision project with the same identifier, the software compares the data of both projects. It then proceeds with the partial import according to the import settings that you select and the import rules that are described in this topic.
NOTE: If the export file also contains information of a Control project, you can see the data that is related to the Control project, and have the choice to
as well.
Item
SupervisionProject_n
Pages node
Pages
Software Version Compatibility
The version of EcoStruxure Process Expert that you use to import the information contained in the export file must be the same as the version that you used to create the export file (a service pack is considered the same version); otherwise you cannot proceed with the import.
Import Settings
The table describes which Supervision project information you can import into a system.
Selected for import (1)
By default
By default
By default
Description
Unselect the item to exclude the entire project from the export file.
You cannot unselect the item.
You can select containers (pages) individually (2) .
Selecting a page automatically selects any genie facets that are assigned to it.
242 EIO0000001114.15
Item Selected for import (1)
Description
Cluster_n
Tags node
Tag containers
Tag container Constituent File
By default
By default
By default
By default
Selecting a page automatically selects the logical Participant project.
At least one cluster must be selected.
You cannot unselect a cluster when the export file contains only one cluster.
You cannot unselect the item.
You can select tag containers individually (2) .
Selecting a tag container automatically selects any facets that are assigned to it.
A Constituent File is associated to each tag container.
If the identifier of the imported tag container already exists in the target project, the selection of the constituent file has an impact on the
.
NOTE: The Constituent File check box is selected and disabled if the identifier of the imported tag container does not exist in the target project.
You cannot unselect the item.
Services node
Alarm servers
IOServer_n
Communications node
By default
By default
By default
By default
IODevices node By default
Any associated boards and ports are selected by default.
You cannot unselect the item.
Any associated I/O devices are selected by default.
You cannot unselect the item.
You cannot unselect the item.
Trend servers
Report servers
By default
By default
Clients
ClientEvents
ServerEvents
Executables
Executable_n
By default
By default
By default
By default
By default or not selectable
Service Mappings
Communication
Mappings
By default or not selectable
By default or not selectable
If the target system already contains an executable with the same identifier, you cannot select the executable for import.
Else, you can select each executable and its contents individually.
Selecting an executable automatically selects any associated mapping.
If a service mapping already exists in the target system, you cannot select the service mapping for import.
Contains data related to the service mapping including any required contents in the content repository.
If a communication mapping already exists in the target system, you cannot select the communication mapping for import.
Contains data related to the communication mapping.
Built Participant
Project
By default Represents the built Supervision Participant file (.ctz) (includes the OFS/
OPC UA configuration files (.xml)).
It appears and is selected only if the built Participant project was selected at the time of export.
(1) The information needs to be contained in the export file to be selected
(2) The item is available for selection only if it is tagged with a green dot; otherwise the item cannot be selected.
EIO0000001114.15
243
Import Rules for Included Projects
At the time of import, the software checks whether the content repository of the target system contains an included project that has the same identifier as the one contained in the export file.
The following figure shows an example of the Resolve Content Conflict dialog box that opens if the software detects the presence of an included project with the same identifier.
244
Header
Identifier
Conflicts
Version in contents repository
Version in export file
Description
The identifier of the included project for which a conflict exists.
The identifier of the Supervision Participant projects that exist in the target system and use the version of the included project that is in the content repository.
By selecting this check box, you use the version of the included project that is in the content repository.
Selected by default.
By selecting this check box, you use the version of the included project that is
contained in the export file, page 250
and overwrite the version that is in the repository.
Included projects contain data related to Supervision constituents (for example, genies, tags, and so on), which can be shared by several templates.
Replacing the existing included project has an impact on:
• The templates that use the contents of the included project.
• The Supervision Participant projects to which the included project is associated.
NOTICE
LOSS OF DATA
Resolve an included project conflict that arises during the import of a
Supervision Participant project by selecting the correct version of the included project to be imported.
Failure to follow these instructions can result in unusable Supervision projects.
Import Rules for Project-Related Objects
Facets assigned to Supervision projects are related to instances of the application and mappings of project executables are related to entities of the topology. For the
Supervision project import to complete entirely, these project-related objects need to be present in the system in which you want to import the project.
EIO0000001114.15
The table describes the impact on the import operation when project-related objects are not present or have a different configuration. It also describes the corrective action.
Project-related object that is not present or different
The instances whose facets are assigned to the
Supervision project that you are importing
(same identifier, template identifier, template version, and status Valid ).
An element of the instance creating a facet that is being imported is not selected.
Impact if not present in the target system
You can import the project but not the tag and page containers to which such facets are assigned. This requires that the project contains at least one container that
, even empty.
confirm the partial import.
asking you to
The facet that is normally created by this element is not imported.
The notification panel provides information about the facet that is not imported.
For example, you import a Supervision project to which the data facet created by the
Maintenance element of an instance is assigned but in the application of the target system, the
Maintenance element of the same instance is not selected.
The assignment status of facets that are imported is set to Out Of Date .
Required action
Do either of the following first to create missing instances:
• Use the
export/import functionality, page 168
of the
Application Explorer to import missing instances.
• Create instances. This may require importing templates first.
You can obtain information about the missing instances and their templates in the tooltip of the container that is tagged with a red dot.
Edit the instance in the Application
Explorer and select the corresponding element.
Generate the project or container to apply the changes.
The properties of an instance are different from the instance configuration at the time of export.
The difference lies in the
(services) and/or the parameter values, page
.
Topological entities to which you have mapped the executable of the project (service and/or communication) that you are importing (same identifier, same devices (for example, NIC for a station node), and services).
You can import the project but not the
Supervision project executable and any of its associated mappings.
Use the
export-import functionality, page 408
Explorer of the Topology first to create the missing topological entities.
Import Rules for Equipment
When you import a Supervision project and a project with the same identifier already exists in the target system, for an instance that exists in the same cluster in both the imported file and the Supervision project, the
that is already generated in the Supervision project prevails. This applies independently of the selection of the
of the tag container.
Example :
Equipment in the Participant project after import
Identifier of instance present in imported file and
Supervision project
MyMotor_1 (1)
Equipment name generated by the imported instance
Folder_1.MyMotor_1
(2)
(1) The instance is located in Folder_1 .
(2) Facets of the instance are assigned to TagContainer_1 in Cluster_1 .
Equipment name generated by the instance in the
Supervision project
Folder_2.MyMotor_1
(2) Folder_2.MyMotor_1
Import Rules for Pages
When you select to import a page that is contained in an export file, and a page with the same identifier exists in the target system, the contents of the existing page is overwritten with the content of the page that is in the export file.
EIO0000001114.15
245
246
Import Rules for Facets
The software applies import rules to facets if the system into which you are importing a Supervision project already contains a Supervision project with the same identifier.
The following are the general import rules that the software applies if facets with the same identifier contained in tag containers with the same identifier exist in both the target project and the export file that you are importing:
• If you select the constituent file of the tag container:
◦ Facets from the export file overwrite facets of the target system and maintain the state they have in the export file.
◦ Facets that exist only in the export file are imported into the target system and maintain the state they have in the export file.
◦ Facets that exist only in the target system become Assigned and Non
Generated . If the status of the facet is deleted, unassigned, or unlinked, the software removes the facet from the tag container after import.
• If you unselect the constituent file of the tag container:
◦ Facets with the same identifier maintain the state that they have in the target system.
◦ Facets that exist only in the export file are imported into the target system and become Assigned and Non Generated .
◦ Facets that exist only in the target system maintain their state.
NOTE: The software changes the assignment status of any facet of an instance to Out Of Date if a
property of an instance, page 134
is different from what it was at the time of export. This includes the location of the instance in the application. The notification panel provides information about the change of the assignment status after import is complete.
The following tables illustrate these import rules based on the different use cases.
The tag container and facet names are examples, and represent tag containers and facets in a cluster of the project.
If you select the tag container Constituent File option.
Contents of export file selected for import
Item in Supervision project of target system
Result in Supervision project of target system after import
Tag container identifier is identical
Tag container1
Tag container1
Tag container1
Facet1 Tag container1
Facet1 Tag container1
Facet1 Tag container1
–
Facet1
Facet2
Facet1 from export file with status from export file.
Facet1 from export file with status from export file.
Facet1 from export file with status from export file.
Facet2 with status non-generated.
If the status of Facet2 is deleted, unassigned or unlinked, the facet is removed from the tag container after import.
Tag container identifier does not exist in target project
Tag container2
Facet3 – – Tag container2 with Facet3 from export file with status from export file.
– The item does not exist
If you do not select the tag container Constituent File option.
EIO0000001114.15
EIO0000001114.15
Contents of export file selected for import
Item in Supervision project of target system
Container identifier is identical
Tag container1
Facet1 Tag container1
Tag container1
Tag container1
Facet1 Tag container1
Facet1 Tag container1
–
Facet1
Facet2
Result in Supervision project of target system after import
Facet1 from export file with status non-generated.
Facet1 from target system with same status.
Facet1 from target system with status nongenerated.
Facet2 from target system with same status.
– The item does not exist
Import Rules for Executables and Mappings
The software updates the
of a Built executable after import depending on the scenario.
If the system into which you are importing a Supervision project does not contain a
Supervision project with the same identifier, the state of Built executables that you import changes to Out Of Date .
If the system into which you are importing a Supervision project already contains a
Supervision project and an executable with the same identifier, the software applies import rules to executables, service, and communication mappings. These rules are described in the following tables.
The table illustrates the import rules that apply to a Built executable based on different scenarios.
Contents of export file selected for import
Executable1
Executable1
Executable1
Item in Supervision project of target system
Does not exist
Executable1
Executable2
Resulting built state in Supervision project of target system after import
Out Of Date
Out Of Date
Executable1: Out Of Date
Executable2: Out Of Date
The table illustrates the import rules that apply to mappings based on different scenarios.
Contents of export file selected for import
Service mapping
Item in Supervision project of target system
Exists
Result in Supervision project of target system after import
Communication mapping
Communication mapping
Does not exist
Exists
Does not exist
Service mapping from target system is not changed.
Service mapping is created with the mapping information from the export file.
Communication mapping from target system is not changed.
Communication mapping is created with the mapping information from the export file.
Opening the Project Import Window
To open the Import window, proceed as follows.
247
Step
1
2
Action
Right-click the system root folder in a Project Browser of the Project Explorer and select Import .
Result: The Import dialog box opens.
Browse to the export file (.sbk) that contains the project information that you want to import and click Open .
Result: The Import window opens and displays the contents of the file that you have selected.
NOTE: You can
Project Import Window
The Import window lets you select the information of a Supervision project that is contained in an export file that you want to import into an existing system.
The following figure shows an example of the Import window displaying the contents of a Supervision project export file. In this example, the check boxes for
TagContainer_2 and relate mappings are cleared because the items cannot be imported. To indicate that at least one item of the Supervision project is not selected, the check box of parent nodes are filled with a square.
248
The table indicates the meaning of the colored dots that appear in the Import window next to items of a Supervision project.
EIO0000001114.15
Color code
Green
Red
Yellow
Description
You can import the item.
• At the container level: The container (for example, the tag container or the page) contains at least one facet that is referenced by an instance, which is
not present in the application, page 244 .
• At the executable level:
◦ An executable with the same identifier already exists in the target project.
◦ A
project-related topological object, page 244
is not present in the target system.
A tooltip provides additional information about the issue.
NOTE: You cannot import items that are tagged with a red dot.
The item contains at least one subitem that is tagged with a red dot.
The item can be imported partially only.
NOTE: To expand/collapse a node in the Import window, select the node and press Enter .
Confirmation Dialog Box for Containers That Cannot Be
Imported
The following figure shows an example of the dialog box that opens when a container of a Supervision project selected for import is tagged with a red dot and you click OK in the Import window. If you are also importing Control projects, containers are grouped by Participant then by project.
EIO0000001114.15
Button
Yes
No
Description
Closes the dialog box, the Import window, and imports the selected projects without containers tagged with a red dot.
Closes the dialog box and reverts to the Import window without importing projects. You can modify the selection of projects or cancel the import operation.
249
250
Aborting Import Tasks
After confirming the import by clicking OK in the Import window, the abort icon is displayed in the
. Click the icon to cancel the task. The project is not imported.
Only the user who has selected the command is allowed to abort it.
NOTE: If you are importing a small project, the task may complete before you are able to click the icon.
Importing a Supervision Project
Included projects contain data related to Supervision constituents (for example, genies, tags, and so on), which can be shared by several templates.
Replacing the existing included project has an impact on:
• The templates that use the contents of the included project.
• The Supervision Participant projects to which the included project is associated.
NOTICE
LOSS OF DATA
Resolve an included project conflict that arises during the import of a
Supervision Participant project by selecting the correct version of the included project to be imported.
Failure to follow these instructions can result in unusable Supervision projects.
To import data of a Supervision project into an existing system, proceed as follows.
Step
1
2
3
Action
In the Import
window, page 247 , select the items that you want to import.
Click OK .
Result: The software:
• Applies the import rules based on your import selection.
• If the applicable rules are satisfied, it proceeds with the import; If it detects a conflict with the name of an included project, it displays the Resolve Content
Conflict
.
• Displays a summary of the completed actions and detected incompatibilities in the
Notification Panel .
NOTE: Click Cancel to close the Import window without importing project information.
If the software displays the Resolve Content Conflict dialog box, do one of the following:
• Select Version in export file to overwrite the existing included project with the one contained in the export file that you are importing.
• Select Version in contents repository to keep the existing included project.
Click OK .
Result: The software proceeds according to your selection.
NOTE: Click Cancel to discard your selection in the Resolve Content Conflict dialog box and revert to the Import window.
EIO0000001114.15
Participant Project Indicators
Overview
This topic describes the various indicators that appear on components of Control and Supervision Participant projects.
Participant Project Progress Indicators
Overview
Various icons give an indication of the steps that remain before the system engineering life cycle is completed up to the deployment stage for Control and
Supervision projects.
The progress icon is not visible while the
is shown.
NOTE: The indicator icons are visible to any user who opens the Participant project.
Meaning of Icons
For Control and Supervision projects.
Icon Condition description
Either one applies:
• 0% progress for all project containers.
• At least one facet is
for assignment.
(0% progress)
The progress of at least one container is not 100%.
Either one applies:
• The progress of all containers is 100% and no executable exists.
• The project progress is 75% and executables are deleted.
The progress of at least one executable is not 100%.
No icon
(100% progress)
The progress of at least one executable is 100%.
For sections and containers.
Icon Condition description
Either one applies:
• No assignment is done.
• All assignments have been removed.
(0% progress)
At least one facet is Non Generated .
At least one
is Out Of Date , Deleted , UnAssigned , Moved ,
Inconsistent , or Invalid and no facet is Non Generated .
All facets are Generated but the
analysis detected one or more errors, page 252 .
No icon
(100% progress)
All facets are Generated or Unlinked without detected errors during analysis.
For executables.
EIO0000001114.15
251
Icon
(0% progress)
Condition description
Either one applies:
• The executable is created.
• Executable progress is 100% and
is removed.
• Control: Service mapping is completed.
• Supervision: Service mapping is done for at least one service.
Or, executable progress is 100% and service mapping is modified.
• Control: At least one communication mapping or hardware mapping is done.
• Supervision: Communication mapping is completed.
And the executable state is Not Built .
The executable state is Out Of Date or Built with
No icon
(100% progress)
The executable state is Built .
How Icons Appear
The following figure shows an example of several Control projects and their components that have various completion states, which are indicated by progress icons.
Participant Project Validity Indicators
Overview
A dot or
that appears in red or yellow color indicates an
alert or detected error, page 254
during the analysis of components of a
Participant project.
When both an alert and the detection of an error occur for the same object, the detected error icon prevails.
When an icon appears on at least one component of a project (for example, a section, a container, an executable), it appears automatically at the project level.
The indicator icons are visible to any user who opens the Participant project.
NOTE: The
can help provide information about issues that are not indicated by validity icons.
252 EIO0000001114.15
Meaning of Icons
Icon color
Yellow
(progress icon or dot for objects with 100% progress)
Example :
Level
Project
Section
Red
(progress icon or dot for objects with 100% progress)
Example :
Tag container or page
Page
Executable
Project
Section
Tag container or page
Page
Executable
Condition description
• Control projects: The
of the project or
saving refinement changes, page 339
generated an alert indicating that the build operation may not complete successfully.
• Supervision projects: Saving changes generated an alert.
• All projects: At least one alert was generated for a project component.
The
of the section or
saving refinement changes, page 339
generated an alert indicating that the build operation may not complete successfully.
Generation completed with at least one alert.
Saving changes generated at least one alert.
Build completed with at least one alert.
• Control projects: The
of the project or
saving refinement changes, page 339
detected an error, which prevents the build operation from completing successfully.
• Supervision projects: Saving changes detected an error.
• All projects: There is at least one detected error for a project component.
The
of the section or
saving refinement changes, page 339
detected an error, which prevents the build operation from completing successfully.
Generation completed with at least one detected error.
Saving changes detected at least one error.
Build did not complete successfully.
How Icons Appear
The following figure shows an example of several Control projects and their components that have various validity states, which are indicated by the color of the progress icons.
EIO0000001114.15
1
2
3
Valid project with 50% progress.
Project with 25% progress and at least one alert.
The detected error at the section level is also shown at the project level.
253
Participant Project Write-Lock Indicator
Overview
A lock icon lets you see which Participant project components are being used or modified by other processes or users and that you cannot work on them.
Certain components that are locked can be opened in read-only mode.
NOTE: The indicator icon is visible to any user who opens the Participant project.
Meaning of the Icon
The icon indicates that the project or a component is locked because an operation is in progress, such as:
• Assignment (1)
• Generation
• Refinement
• Editing
• Mapping (1)
• Export/import
• Build
(1) The lock icon appears very briefly while an performed is performed.
Where the Icon Appears
The lock icon can appear at the following levels:
• The Participant project
• Sections
• Containers (such as Supervision pages or tag containers)
• Clusters
• Services node and any of its subcomponents (such as servers, I/O devices)
• ClientEvents and ServerEvents nodes
• Executables
Viewing the Last Action Summary
Overview
The Last Action Summary command lets you view the last action that was performed on a given Participant project component and a summary of the result.
The command is available in the context menu of projects and their components.
For actions that had not completed successfully or with alerts, and/or detected errors, it shows again the information that was displayed originally.
Supported Actions
An action summary is available after you perform either action:
• Generation
• Regeneration
• Build
254 EIO0000001114.15
Particular Conditions
Last action performed
Not a supported action.
A supported action was aborted.
An action summary for aborted actions is not available.
The action summary for the previous action remains available
(if applicable).
Import of a Participant project.
Result
The command is unavailable.
The command is unavailable.
The action summary that existed at the time of export is cleared.
NOTE: The last action summary of the target project is preserved when you perform an incremental import. That is, when you import a project into a system in which a project with the same identifier already exists.
EIO0000001114.15
255
Assignment Stage
What’s in This Chapter
Creating and Managing Sections and Containers........................................... 256
Overview
This chapter describes how to create Control and Supervision containers and assign facets of instances of the application to the corresponding projects that you have created during the Projects Definition stage.
The following figure shows the position of the Assignment stage within the system engineering life cycle.
Refer to the
for a description of the purpose of this stage.
Creating and Managing Sections and Containers
Overview
This section describes the Assignment Editor and how to use it to create and manage Control sections and Supervision containers. It also describes section and container context menu commands and properties.
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
Assignment Editor
Overview
The Assignment Editor lets you create and manage Control and Supervision containers and assign the facets of instances of the application to them.
256 EIO0000001114.15
Section creation
Automatic, user-defined.
With possibility to:
•
• Select which sections to create
Manual
You can assign by facet, instance, folder, or entire application depending on the
extent of the assignment, page 261
that you want to perform.
The editor gives you the flexibility to assign manually, automatically, or by combining both methods.
The following table describes the two methods that you can use to
Facet assignment
Automatic (1) , user-defined, with possibility to
.
Prerequisite
Configure assignment mechanism, page 268 .
Manual
(1) By default, remaining candidate facets are
assigned automatically, page 284
during generation
How to use
Assign objects by dragging them to the project.
Assign objects by dragging them to a section.
The following table describes the methods that you can use to
Supervision projects, page 281 .
Tag container creation
Automatic
With possibility to:
•
Rename tag containers, page 277
• Select the cluster
Manual
Facet assignment
Automatic (1) with possibility to
.
Prerequisite
Create additional clusters, page
as needed.
How to use
Assign objects by dragging them to the project.
Manual
Create
in the Assignment Editor and additional
(as needed).
You have associated a Control project to the tag container.
Assign objects by dragging them to the tag container.
Assigning instances to the
Control project automatically assigns the corresponding
Supervision facets to the tag container.
(1) By default, remaining candidate facets are
assigned automatically, page 284
during generation
Opening the Assignment Editor
In a Control or Supervision project browser of the Project Explorer , double-click the Containers
of the project to which you want to assign facets.
NOTE: You can also open the Assignment Editor by using the
window.
Assignment Editor
The Assignment Editor for Control and Supervision projects is identical except for the color scheme of the Containers and Assignments pane:
• Blue: Displays facets, containers, and assignments of Control projects.
• Orange: Displays facets, containers, and assignments of Supervision projects.
EIO0000001114.15
257
The following figure shows an example of the Assignment Editor for Control projects.
258
The following figure shows an example of the Assignment Editor for Supervision projects. The Instances and Facets panes are minimized to a tab by unpinning the Instances pane.
1
2
3
4
5
6
7
8
9
10
11
Instances pane. Shows the compatible instances of the application that have a valid Data and Link status.
Facets pane. Shows Participant-specific facets, which are referenced by the items that are selected in the Instances pane. The pane is empty by default. Supervision genie facets are not displayed.
Containers pane. Shows the project and its sections or containers. This pane is used to select the target to which you want to assign facets.
Assignments pane. Shows facets that are assigned to the project or container that is selected in the Containers pane. The title bar of the pane is where you drag objects to assign them.
You can select which
you want to see in each pane.
Button to toggle between grid and tree view in the Instances pane.
Button to show or hide
in the Facets pane. The
Instances pane must be pinned.
Button to toggle between grid and tree view in the Containers
Button to
the Instances and Facets panes.
Button to extract or retract the Instances pane.
Project node, which gives you access to project-level context menu commands.
The following tables describe the information that appears in the panes of the
Assignment Editor .
Instances pane.
Description Column header
Instance
Template
Version
Identifier of the instance.
Identifier of the template that the instance is using.
Version of the template that the instance is using.
EIO0000001114.15
EIO0000001114.15
Column header
Assigned
State
Path
Description
• Assigned : At least one Control or Supervision facet of the instance is assigned to a project of the system.
• Unassigned : No facet of the instance is assigned to any project of the system.
Path to the instance in the tree view of the Application Browser .
The column appears only if you have selected the grid view display mode.
Candidate Provides information about the assignment of facets at the instance level:
• Done : The facets of the instance are already assigned to this project.
• Candidate : The instance contains at least one facet that is not yet assigned to this project.
Description
Contents of the $Description parameter of the instance.
Facets pane.
Column header
Instance
Instance
Template
Facet
Facet
Template
Description
Identifier of the instance that references the facet.
Identifier of the template that the instance that references the facet is using.
Identifier of the facet.
Identifier of the template that the facet is using.
Path
System
Project
Path to the facet as it is shown in the
.
Indicates the assignment (1) status of the facet at the system level:
• Assigned : The facet is already assigned to a project of the system.
• Not assigned : The facet is not yet assigned to a project of the system.
Indicates the assignment status of the facet at the project level:
• Candidate : You have not yet assigned the facet to this project.
• Done : You have already assigned the facet (1) .
Type Provides information on the subtype of the facet.
(1) Generating the section that contains the facet may change this status depending on the actions that you have executed on the facet (for example, unassigning it after a first generation). The
Assignment column of the Assignments pane provides you with a more detailed information on the assignment status of the facet.
Containers pane.
Column header
Path
Description
Container
Order
For a Control project, indicates whether the section belongs to the MAST or FAST task folder.
For a Supervision project, indicates to which cluster the container belongs.
Shows the identifier of the project and the sections or containers that it contains.
An icon indicates the language of a section or the type of container.
NOTE: Although Supervision pages appear, you cannot
to them by using the Assignment Editor .
For Control projects, indicates the order in which the software generates the sections.
You can
change the order of sections, page 207 .
For more detailed information on how the software manages the section order, refer to the
generation process description, page 303 .
NOTE: The order is not shown in tree view mode.
For a description of the Assignments pane, refer to the topic
.
259
Customizing Column Display
In the various panes of the editor, you can choose which columns you want to see by right-clicking a column header and selecting Customize . Certain columns are always shown.
When you hide a column for which a filter is applied, the filter is cleared.
If tree and grid view are available, you may be able to configure the column display independently in each view.
Displaying Sections in Tree View Mode
The tree view mode allows you to view sections to which facets are assigned in relation to the folder structure of the application.
For more details, refer to the topic describing the
representation of the application structure in Control projects, page 287
.
The figure shows an example of the Containers pane in tree view mode once facets have been assigned to some FBD sections.
260
2
3 item
1
Description
System root folder and subfolders representing the folder structure of the application.
NOTE:
Predefined folder icons, page 129
that you may have assigned in the application to various folder levels are not represented.
Section identifier.
Special root folders.
Viewing Instances with Facets That Can Be Assigned
To view the instances of the entire application, which have facets that can be assigned to the project, proceed as follows.
Step
1
2
Action
Switch to grid view mode by clicking the button in the Instances pane.
Click the button to show the candidate column in the Instances pane.
Result: The Instances pane displays the instances of the entire application.
Those that have a status of Candidate in the Candidate column have facets that can be assigned to this project.
EIO0000001114.15
NOTE: Use the
instance progress icons, page 144
to see which instances have facets that need to be assigned.
Viewing Facets That Can Be Assigned
To view the facets of the entire application that can be assigned to the project, proceed as follows.
Step
1
2
3
Action
Switch to tree view mode by clicking the button in the Instances pane.
In the Instances pane, select the system root folder.
Click the button to show facets in the Instances pane.
Result: The Facets pane displays the facets of the entire application.
Those that have a status of Candidate in the Project column can be assigned to this project.
NOTE:
• To view only the facets with status Candidate , use the filter on the
Project column.
• To narrow the display to part of the application, select an application folder instead of the system root folder.
Object Selection
The following table describes the scope of the assignment depending on the objects that you drag from the Instances or Facets pane of either Assignment
Editor . Each editor assigns only Participant-specific facets.
Object
One or more facets of the same or several instances.
One or more instances.
One or more folders.
Resulting assignment
These facets only.
Remaining facets are
assigned automatically, page 284 .
The facets of all the selected instances.
The facets of all the instances that are contained in the selected folders.
By dragging the system root folder, you can assign facets of the entire application at once.
NOTE: If the facet that you are trying to assign is not compatible with the selected container, you cannot create the assignment and a tooltip indicates it.
If you are trying to assign multiple items at once and some of them are not compatible, the assignment is created for the compatible ones and information about the other ones is displayed in the notification panel.
Creating Control Project Sections
Overview
In the Assignment Editor , you can create only FBD sections in a Control
Participant project.
This topic describes how to create sections manually. Sections can also be
created automatically, page 268
.
To create non-FBD sections, refer to the topic describing the Project Explorer .
Creating FBD Sections
To create an FBD section in the Assignment Editor , proceed as follows.
EIO0000001114.15
261
262
Step
1
2
Action
Right-click the identifier of the Control project in the Containers pane and select Create
FBD Section .
Result: The Create FBD Section dialog box opens.
Edit the
of the section if required, select the MAST or FAST task folder, and click OK .
Result: A new FBD section is created with the next available
Inserting FBD Sections
To insert an FBD section, proceed as follows.
Step
1
2
Action
In the Containers pane of the Assignment Editor , right-click the section where you want to insert the new one and select Insert FBD Section .
Result: The Insert FBD Section dialog box opens.
Edit the
of the section and click OK .
Result : The newly created section is inserted and has the
of the section that you had right-clicked. The order of the section that you right-clicked and those that follow is incremented by 1.
Section Actions
The table describes the context menu commands of sections.
Command
Insert FBD
Section
Generate
Description
Creates a new FBD section, page 262
at the position of this section.
Refine
ReGenerate
Delete
Rename
Properties
Refer to
The command is only available for FBD sections.
Refer to
The command is not available for LL984 sections.
Refer to
The command is only available for FBD sections.
Deletes the section.
If you have
facets to the section, the software:
•
any facets contained in the FBD section that you are deleting.
• Change the System
of the facets to Not assigned .
NOTE: If the FBD section has been generated, deleting it also removes from the logical Control Participant project the section and constituents that were generated by the facets assigned to the section (for example, variables).
However, derived types that were generated by these facets are not removed
(for example, DFBs and DDTs). To remove these, you can either:
•
the Control project. This discards refinements.
• Purge the types from the Control Participant during refinement. For details, refer to Purge of Unused Instances in the Control Participant help.
Lets you edit the
of the section.
Opens the Properties window of the section.
Section Properties
To open the Properties window of a section, right-click the section and select
Properties .
EIO0000001114.15
You can edit the following items.
Item
General Identifier
Description
Depending on how you create the section, the default identifier can be either:
• FBDSection_n if you create the FBD section manually, using the Create FBD Section command, where n is an incremental number starting at 1.
• The concatenation of instance identifier_instance template identifier if the software creates the section automatically during assignment.
NOTE: For identifiers of Schneider Electric templates, the
$ prefix is omitted.
The identifier must be unique within the Control project.
The software allows only the use of identifiers that satisfy the
Description Optional.
You can enter a description of the section with free form text.
Generated
On
Date and time of the last successful generation or regeneration of the section.
The property is read-only and contains information only for FBD sections.
Creating Supervision Tag Containers
Overview
This topic describes how to create tag containers manually by using the
Assignment Editor , their properties, and context menu commands. The software creates tag containers automatically when you
You need to create, at least, one tag container per controller to assign Supervision data facets of instances of the application.
These data facets represent the tags that are managed by Supervision components and assigned to the I/O device variables to be associated to the
Supervision Participant project:
• Variable tags
• Trend tags
• Alarm tags
Monitoring data of a device, page 639
communicating by using the Modbus TCP protocol (or Modbus through an Ethernet gateway) from the Supervision infrastructure requires creating, in addition, one tag container for each device.
Supervision Data facets representing device-specific data are assigned to each container. Also, a specific communication protocol needs to be defined for these tag containers.
Creating Tag Containers
To create a tag container in the Assignment Editor , proceed as follows.
Step
1
2
Action
Right-click the identifier of the Supervision project in the Containers pane and select
Create Tag Container .
Result: The Create Tag Container dialog box opens.
Edit the
of the tag container if required, select an existing cluster, and click OK .
Result: A new tag container is created.
EIO0000001114.15
263
264
Using a User-Defined Protocol
When you enter a protocol in the Protocol
parameter of the tag container, page
instead of selecting a predefined one, verify the following:
• The protocol is supported by the platform of the controller that is the data source of the variable tags; otherwise, the variables cannot be read and/or written to by Supervision software.
• It is supported by the Supervision Participant and installed; otherwise, you cannot build the Supervision executable.
To verify which protocols are installed in the Supervision Participant, refine the Supervision Participant project and expand an entry in the Protocol column of I/O Devices in the Topology activity.
If the protocol is not installed, contact EcoStruxure Process Expert support .
When using a user-defined protocol, some data generated at the template level, such as variable tag addresses may not be in the required protocol-specific format depending on the template configuration. After generating the Supervision
Participant project, refine it and edit the data as needed. No configuration file (.
xml) is generated when you build the Supervision Participant project.
NOTE: For communication with the I/O server, ensure that the
protocol of the communication board, page 235
is correctly configured.
Tag Container Actions
The table describes the tag container context menu commands.
Command
Create
Tag
Container
Delete
Rename
Properties
Description
Lets you create a new tag container in an existing cluster.
Starts the generation process to populate new tags, update out-of-date tags, and/or remove deleted tags in the Supervision Participant project.
Deletes the tag container.
If you have assigned facets to the container, the software:
• Unassigns the facets contained in the container that you are deleting.
• Changes the system status of the facets to Not assigned .
NOTE: The software does not delete the servers that it may have created during the assignment of Supervision facets.
NOTE: If the container has been generated, deleting it also deletes the data in the logical Participant project when you generate the project again.
Lets you enter a new identifier for the tag container.
Opens the Properties window, which allows you to edit the properties of the tag container.
Tag Container Properties
To open the Properties window of the tag container, right-click the container and select Properties .
You can edit the following items.
EIO0000001114.15
EIO0000001114.15
Item
General Identifier
Description
The identifier must be unique within the Supervision project.
Generated
On
Attributes ScanTime
Default value: TagContainer_n where n is an incremental number starting at 1.
NOTE: When Protocol for the tag container is set to OPCUA , the identifier is used as follows:
• During generation, it becomes part of the variable tag address in the Supervision Participant project. The format of the address is ns=2;s=0:<tag container ID>!<variable name> , where ns indicates the namespace and 2 corresponds to the OPC UA server as defined by
Schneider Electric.
For example, ns=2;s=0:Controller1!InputVar1
• During build, it becomes the alias for the device in the
OFS configuration file, page 475
.
Therefore, it may be useful to rename the tag container with the identifier of the controller that is mapped to the
associated I/O device, page 460
.
Description Optional.
You can enter a description of the container with free text.
Date and time of the last successful generation of the tag container
(read-only).
Protocol
The acquisition time for the tags that are assigned to the container.
msec
Default value: 0
The protocol that is used for communication with the I/O device.
The menu contains the following values:
• OFSOPC (default)
• OPCUA
NOTE: When using the OPC UA protocol with templates of a Schneider Electric library, clear the Use Native Types checkbox of the Unity/Control Expert symbols parameter (selected by default) so that the correct Control
Participant types are used by the OPC UA server. For details, refer to PLC Software Settings in the OPC UA
Server Expert help.
• OPCUA Embedded : When the OPC UA server is embedded in a module (see EcoStruxure ™ Process Expert, Control
Participant Services, User Guide) of the controller. Sets the protocol of the associated I/O device to OPCUA in the
Supervision Participant project.
•
User-defined protocol, page 264
whose name can be entered by using free-form text. 16 characters maximum. Values entered are added to the menu.
When you instantiate Schneider Electric templates and assign their
Supervision facets to the Supervision project, only OFSOPC .
OPCUA , and OPCUA Embedded are supported. This is because, by default, the facets generate Supervision data (variables and tags) that is specific to these protocols. To use another protocol, you can add the protocol-specific Supervision data to the project either by instantiating and configuring the $VariableTag_CD template or by refining the Supervision project.
NOTE: For each additional tag container that you create to monitor data of a device directly from the Supervision runtime, change the value to OPC .
Attributes Direct TCP
IP
Addressing
Mode (1)
For information on the corresponding driver, refer to the driver help. To locate driver help files, look up Driver Reference Help in the
help of the Supervision Participant, page 69
Sets the addressing mode for the TCP IP driver in the OFS/OPC UA configuration file. Select the mode depending on the Modbus TCP
that is mapped to the associated I/O device in the Communication Mapping tab.
The parameter is disabled when Protocol for the tag container is set to OPCUA Embedded .
Possible values:
265
266
Item Description
• Unallocated/Allocated Data, PAC Modicon (/U) (default):
Corresponds to selecting UNITY / Control Expert in the PLCs section of the Device address wizard in the OFS/OPC UA configuration tool. Use this setting when mapping a controller or station node.
• Allocated Data, Offset 0 (/T) : Corresponds to selecting PL7 in the PLCs section.
• Allocated Data, Offset 0 with minimum communication
(/NT) : Corresponds to selecting PL7 in the PLCs section and
Minimum communication profile .
• Allocated Data, Offset 1 (/Q) : Corresponds to selecting
CONCEPT in the PLCs section.
• Allocated Data, Offset 1 with 32 bits swapping (/QW) :
Corresponds to selecting CONCEPT in the PLCs section and
Swap 32-bit Values .
• Allocated Data, Offset 1 (/NQ) : Corresponds to selecting
MODBUS Device in the PLCs section.
The value is available only when Protocol is set to OPCUA .
NOTE: The value shown in brackets corresponds to the suffix that is appended to the device address in the configuration file.
For more information, refer to:
• Editing the Device Network Address in the
.
• Managing Device Aliases in the help of OPC UA Server
Expert.
Attributes Supports
Optimized
Modbus
Frames (1)
Corresponds to the Modbus Request Optimization parameter of
Communication Settings in the OFS configuration tool.
Possible values:
• Off (default): The check box of the parameter is cleared.
• On : The check box of the parameter is selected.
The parameter is not available for the OPCUA protocol.
NOTE: Because in OFS, this parameter applies to all aliases of the OFS configuration file, if you configure several tag containers in a Supervision project and for one of them you select Off , the check box of the parameter in the OFS configuration file is cleared, overriding the On setting that you may have configured for any other tag container.
Select the I/O device that you want to associate with the container.
Relationships
IoDevices
The I/O device appears in the menu once you have created it or assigned facets.
Default value: IODevice_1
NOTE:
• By default, the software associates the tag container with the I/O device that it automatically creates when you
assign Supervision facets to the container, page 281 . If
you
create the I/O device manually, page 232
, associate it with the tag container before or after assigning facets.
• Changing the relationship after assigning facets to the tag container changes their assignment status to Out Of Date .
Associated
Control
Project
Lets you select one existing Control project that will trigger the
automatic assignment, page 285
of Supervision facets to the tag container when you assign Control facets.
You can associate a Control project to several tag containers given they belong to a different Supervision project.
When the associated Control project is renamed, the value is updated. When it is deleted, the value is reset.
Default value: Not Assigned
(1) The parameter becomes read-only when Protocol is different than OFSOPC or OPC UA .
EIO0000001114.15
Creating Supervision Pages
Prerequisites
Generate the Supervision project before creating pages.
Creating Supervision Pages
To create a page in the Assignment Editor , proceed as follows.
Step
1
Action
Right-click the identifier of the Supervision project in the Containers pane and select
Create Page .
Result: A new page is created.
Supervision Page Actions
The table describes the page context menu commands.
Command
Create
Page
Description
Lets you create a new Supervision page.
Opens the Supervision Participant, which allows you to assign to the page animated graphics that are associated with the instances of the Supervision project. It also allows you to add graphic elements to the page to represent process hardware.
Delete
Rename
Properties
Starts the generation process to update out-of-date genies, and/or remove deleted genies in the Supervision Participant project.
Deletes the page including assignments of animated graphics.
Lets you enter a new identifier for the page.
Opens the Properties window, which allows you to edit the properties of the page.
Supervision Page Properties
To access the Properties window of the Supervision page, right-click the page and select Properties .
You can edit the following items.
Item
General Identifier
Description
The identifier must be unique within the Supervision project.
The software allows only the use of identifiers that satisfy the
.
Description Optional.
You can enter a description of the page with free form text.
Generated On Date and time of the last successful generation of the page (readonly).
EIO0000001114.15
267
Assigning Facets of Instances
Overview
This section describes how to use the Assignment Editor to assign facets of instances to their respective Control and Supervision containers. It also details the information that the software provides on the resulting assignments.
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
Defining the Control Facet Assignment Mechanism
Overview
The Container Naming Rules window allows up to four expressions and lets you use either one to define the assignment mechanism of Control facets, which includes:
• The name of sections that are automatically created when you assign facets.
• Which facets are assigned to which section.
Expressions are project-specific.
By default,
one preconfigured expression, page 271
is selected in each project.
The expression is applied when you drag instances or folders containing instances to the Control project in the Assignment Editor .
If the resulting container identifier does not satisfy applicable naming rules, it is
NOTE: You can
the result or override the mechanism by assigning facets to an existing section.
Opening the Container Naming Rules Window
To open the Container Naming Rules window, select Settings in the
of the Control project.
268 EIO0000001114.15
Container Naming Rules Window Description
The following example shows the Container Naming Rules window for a new
Control project with its two preconfigured expressions of which the first one is selected.
EIO0000001114.15
Item Description
1
Preconfigured expression, page 271
(read-only). Select the expression to use it to create sections and assign facets.
You can
and edit the name and description of expressions that you add.
2
3
To create the expression, you can configure up to six tokens. To create the section identifiers, the software concatenates the values that it has calculated for each of the configured tokens.
The tokens that you include in the expression have an impact on the
that are created.
The available tokens are:
• Alias Hierarchy : Corresponds to the
alias of the folder, page 126 .
• Folder Hierarchy : Corresponds to the identifiers of folders that make up the path of the instance.
• Free Text : Free-form text that you can enter. It lets you add a fixed value to all sections that are created or insert a separator. Underscore is the only special character that is allowed.
• Instance ID : Corresponds to the
identifier of the instance, page 130
.
• Template ID : Corresponds to the
identifier of the template, page 130
that is used by the instance.
For Alias Hierarchy and Folder Hierarchy , you can select which levels in the path of the instance to consider.
0 corresponds to the folder that contains the instance. 1 corresponds to its parent folder, and so on.
N corresponds to the highest folder in the structure. The system root folder is excluded
(except for instances that have the system root folder as direct parent).
Maximum value: 99
Example :
For an instance located in System_1\Site_1(S1)\Area_1(A1)\Cell_1(C1)\Unit_1(U1) (where the value in parentheses represents the folder alias):
• 0 = Unit_1 (or its alias, U1 )
• 1 = Cell_1 (or its alias, C1 )
• 2 = Area_1 (or its alias, A1 )
• N = Site_1 (or its alias, S1 )
269
270
Item Description
4
5
6
7
8
9
10
11
12
Configuring the value as 1 to 2 for each token generates the following result:
• For Folder Hierarchy : Cell_1Area_1
• For Alias Hierarchy : C1A1
Optionally, you can define up to two
for each token (except for the first and last token, which support only one condition each).
The following conditions are available:
• Condition 1 :
◦ Remove if previous token resolved value is empty
◦ Remove if all previous tokens resolved value is empty
◦ Remove if previous token resolved value is NOT empty
◦ Remove if all previous tokens resolved value is NOT empty
• Condition 2 :
◦ Remove if next token resolved value is empty
◦ Remove if all next tokens resolved value is empty
◦ Remove if next token resolved value is NOT empty
◦ Remove if all next tokens resolved value is NOT empty
Buttons to add and remove tokens in an expression.
Lets you simulate the resulting section identifier by using the expression that is configured based on a sample folder structure and instance identifier if you were to assign any part of this sample hierarchy to the Control project in the Assignment Editor .
To refresh the result after modifying the expression, click the button again.
Pane showing the sample folder structure and the resulting section identifier.
Values in bracket represent the alias of the folder and the identifier of the template.
Lets you add a custom expression.
You can add up to two expressions but only one expression can be selected at a time.
You can delete expressions that you have added.
When selected, opens the Assignment Viewer
only if the assignment creates at least one new section based on the selected expression.
Additional
preconfigured expression, page 271
(read-only).
User-created expression that can be configured and selected.
Container Creation Principle
The table describes the
that are created depending on the token that the expression contains. When several tokens are included, the one with the lowest granularity determines the number of sections. Tokens are listed in increasing order of granularity.
Token
Instance ID
Folder Hierarchy (1) As many sections as there are folders containing instances in the object that you are dragging (when Value = 0 to N).
This token lets you assign facets of instances located in
several folders of a same level, page 275
to one section.
Alias Hierarchy (1)
Number of sections created
As many sections as there are instances in the object that you are dragging.
As many sections as there are folders that have an alias and that contain instances (instances of subfolders included) in the object that you are dragging.
This token lets you assign facets of instances located in
several folders of different levels, page 276
to one section.
EIO0000001114.15
Token
Template ID
Number of sections created
As many sections as there are templates used by instances in the object that you are dragging.
This token lets you assign facets of several instances that
use the same template, page 274
to one section.
(1) The value that you configure impacts the number of sections that are created and the section identifier
NOTE: The
that are configured may impact the results.
Preconfigured Expressions
The following preconfigured expressions exist and are read-only. The section identifier that they create is composed of three parts where each part is the result of a calculated token.
To use a different expression, create one and select it.
For new Control projects:
The expression creates a section for each folder containing instances.
Example:
Alias1Alias2Alias3_Folder3Folder4
The table describes how the tokens of the expression are used to calculate the different parts of the section identifier.
Token
Alias Hierarchy
Free Text
Folder Hierarchy
Value
From 1 to N
_ (underscore)
From 0 to 1
Result
Concatenation of the folder aliases from the highest level folder down to the level-1 folder in the path of the instance.
An underscore.
NOTE: The condition removes the underscore if no aliases have been configured because a section identifier cannot start with an underscore.
Concatenation of the identifiers of the level-1 and level-0 folders in the path of the instance starting with the level-
1 folder.
For new and migrated Control projects:
The expression creates a section for each instance. The section identifier is the same as the one that was automatically created when assigning facets by using earlier versions of the software.
It is selected by default for migrated projects.
Example:
MyMotor_1_Motor
The table describes how the tokens of the expression are used to calculate the different parts of the section identifier.
Token
Instance ID
Free Text
Template ID
Value n/a
_ (underscore) n/a
Result
The identifier of the instance.
An underscore.
The identifier of the template that is used by the instance
(without $ prefix).
EIO0000001114.15
271
272
Using Conditions in Expressions
You can use conditions to modify container identifiers. Conditions remove a token from an expression based on the value of one or all previous tokens and/or the value of one or all following tokens.
It lets you, for example, show the folder identifier instead of the folder alias in case no alias is defined.
Example of condition based on previous token:
You have configured an expression as < token1 >< token2 >< token3 > and an underscore is defined as free text for token2 .
If the value for token1 is blank, the resulting container identifier starts with an underscore. To avoid that, you can configure the condition Remove if previous token resolved value is empty for token2 . The container identifier is then only token3 .
Example of condition based on next token:
You have configured an expression as < token1 >< token2 >< token3 > and Section_
A is defined as free text for token1 . However, you want this text to appear only when token2 and token3 contain no value.
You can configure the condition Remove if all next tokens resolved value is not empty for token1 to achieve this.
Copying Expressions
You can copy expressions to paste them in the same window or in the window of another project.
Step
1
2
Action
Right-click the header of the expression and select Copy .
Right-click the empty space below an expression and select Paste .
Result : The expression is added to the Container Naming Rules window.
NOTE: You can only paste as many expressions as is allowed to remain within the limit of expressions per project.
Sample Application for Examples
The following figure shows the sample application that is used in the following examples. In each one, Area is dragged to the Control project in the Assignment
Editor
EIO0000001114.15
Example With Instance ID Token
Only Instance ID is configured as token without conditions.
After dragging Area , one section for each instance is proposed. The section identifier is the instance identifier.
Example With Folder Hierarchy and instance ID Tokens
Folder Hierarchy is added to Instance ID as tokens with an underscore as separator. No conditions.
Compared to the
previous example, page 273 , the number of sections remains the
same. Only the identifier of the sections is changed by adding the identifier of the folder containing the instance (level 0) and its parent (level 1) as prefix.
EIO0000001114.15
273
Example With Template ID Token
Instance Motor_1 that is using template $Motor is added to the application so that two instances of the same template exist.
Only Template ID is configured as token without conditions.
One section for each template that is used in the application is proposed. The section identifier is the template identifier (without $ character).
274
Example With Template ID and Alias Hierarchy Tokens
Alias Hierarchy is added to Template ID as tokens with an underscore as separator. No conditions.
EIO0000001114.15
Compared to the
previous example, page 274 , one section has been added
because the two instances of template $Motor are located in folders that have a different alias. The section identifier is the template identifier with the aliases of
Cell1 and Area added as prefix.
NOTE: The same number of folders would have been created if Folder
Hierarchy had been selected as token instead of Alias Hierarchy .
Example to Group Facets of Instances Located in Several
Folders of Same Level
This example illustrates how to use the Folder Hierarchy token to assign to one section the facets of instances located in folders of a same level in the application
( Cell1 and Cell2 ). The following figure shows the sample application that is used.
EIO0000001114.15
Folder Hierarchy is configured as token with value 1 to 1. Because the value represents the parent folder, it creates a section for each folder that contains instances by using the identifier of its parent. When two folders have the same parent, only one section is created. No conditions.
275
After dragging Area to the Control project, two sections are proposed. Section
Area contains the facets of A1HandValve_1 and A1Motor_1 because it is the parent of Cell1 and Cell2 .
NOTE: If the section identifier is not satisfactory, you can
or add a Free Text token to the expression.
Example to Group Facets of Instances Located in Several
Folders of Different Levels
This example illustrates how to use the Alias Hierarchy token to assign to one section the facets of instances located in folders of different levels in the application ( Area and Cell1 ). The following figure shows the sample application that is used.
276
Alias Hierarchy is configured as token with value 0 to 1. This creates a section for each folder that has an alias and contains instances. No conditions.
EIO0000001114.15
After dragging Area to the Control project, one section is proposed, which contains the facets of the three instances of the application.
Cell1 contains instances but has no alias.
Area contains an instance and has an alias. Thus, its alias is used to create the section identifier to which facets of A1Valve_1 are assigned. Facets of any instances contained in subfolders ( Cell1 ) are assigned there as well.
NOTE: If the section identifier is not satisfactory, you can
or add a Free Text token to the expression.
Previewing Facets Assignments
Overview
The Assignment Viewer opens when you drag one or more facets to a project in the Assignment Editor .
It does not open if you drag facets to a container that you have created manually.
The window lets you:
• For Control projects, preview the identifier of newly created sections, which is the result of the
expression that you have selected, page 268
.
• Preview which facets will be assigned to which container.
•
of containers in-place.
• Select in which task folder or cluster to create new containers.
• Select which assignments to perform.
NOTE: For Control projects, you can
to open only if the facets that you are assigning create a new section.
EIO0000001114.15
277
Assignment Viewer Description
The following figure shows an example of the Assignment Viewer when you drag the top level folder of a folder structure containing two instances (1) to a Control project while the
for a new project is selected.
The following figure shows an example of the Assignment Viewer when you drag the top level folder of a folder structure containing two instances (1) to a
Supervision project.
278
5
6
2
3
4
Item
1
7
Shows the identifier of the containers to which the facets of the instances that you have dragged will be assigned. For each container, shows the identifier of the instances whose facets will be assigned.
By default, the order of containers and instances corresponds to the hierarchy of the application.
For Control projects, the number of sections and their identifier depends on the
expression that is selected, page 268
and the object that you have dragged (for example, an instance, a folder, or a folder structure).
For Supervision projects, one tag container is created each time you drag an object to the project independently of the number of instances inside the object.
You can edit the identifier of new sections.
Identifiers of the facets that will be assigned to the container.
Indicates whether the container already exists in the project or if it will be created.
Indicates or, for new containers, lets you select:
• For Control projects: The task folder of the section.
• For Supervision projects: The cluster of the container.
Check box to select all the containers that appear in the window.
Select the check box to create the container (if new) and assign the facets.
Containers whose check box is cleared are ignored.
For Control projects, indicates the name of the
that is selected.
EIO0000001114.15
(1) The following figure shows the application that was used for the two
Assignment Viewer examples.
Editing Container Identifiers
You can edit the identifier of new containers only.
By editing the identifier of a container so that it is the same as an existing container or another container that is proposed in the Assignment Viewer , you can assign the facets of both to a single container.
Container Identifier Validation
Either of the following dots can appear on the container icon:
• A red dot to indicate that the container identifier that is the result of the expression is blank.
• A yellow dot to indicate that the container identifier has been modified to satisfy applicable
(for example, maximum length or allowed characters).
Modifying the Application While the Assignment Viewer is
Open
If the application is modified while the Assignment Viewer is open and the changes impact any result of the expression that is selected, the information in the window is not updated. Also, when you proceed with the assignments, they are performed based on the information that is displayed in the window.
Assigning Control Facets of Instances
Before Starting
To assign Control facets of instances, you must have completed:
• The
• The
Control Project Definition stage, page 203
You can only assign facets of instances that have a valid
Data and Link status, page 130 .
You can assign facets only to FBD sections.
You cannot assign the same facet to more than one FBD section in the same project but you can assign the same facet to several Control Participant projects of the system.
NOTE: You can associate a Control project to a tag container to assign the corresponding Supervision facets
.
EIO0000001114.15
279
280
Facet Assignment Order
Depending on the method that you use to select instances for assignment, the order of the referenced facets varies. The following applies when you assign all facets to the same FBD section.
Assignment method
Instance by instance
Multiple instances at once
By folder
Multiple folders at once
Facet order
The order in which you drag instances to assign them defines the order of the referenced facets. Instances selected first for assignment have facets with the lowest order.
The order in which you select instances defines the order of the referenced facets. Instances selected first have facets with the lowest order.
The order of instantiation defines the order of the referenced facets.
Instances created first have facets with the lowest order.
The order in which you select folders defines the order of the referenced facets. Folders selected first have facets with the lowest order.
If the folders contain multiple instances, the order in which instances where created is not relevant anymore.
NOTE: You can
change the order of facets, page 295
.
Assigning Facets
This procedure describes how to assign facets of instances to sections of the
Control project by using an
.
Step Action
1 Verify that the instances are displayed in tree view mode in the
Instances pane, else click the
.
NOTE: Alternatively, you can assign instances using the grid view mode. The assignment principle remains unchanged.
You can switch between views at any time during assignment by clicking the toggle button.
2
3
Configure the expression depending on the assignment mechanism that you want to use and select it.
In the Containers pane, select the
Control project.
4
Result
The Assignment Editor displays the
instances of the application in tree view mode.
–
From the Instances pane, drag one or more
to the title bar of the Assignments pane.
NOTE: Alternatively, you can drag objects directly to project in the Containers pane.
• The name of the project appears in the title bar of the Assignments pane.
• Any existing sections and the facets already assigned to them are displayed.
The Assignment Viewer
opens.
EIO0000001114.15
Step Action
5
6
Review the information that is displayed, edit section identifiers as needed, and select the task folder for each section.
Click OK .
Result
–
• Sections that do not exist yet are created after existing sections.
• The Control facets that have a status of
Candidate are assigned to the respective FBD sections and displayed in the Assignments pane.
• The software assigns an
to each assigned facet.
• The status of the assigned facets in the
System column of the Facets pane changes to Assigned if the status was Not assigned .
• The status in the Project column of the Facets pane changes from Candidate to Done .
NOTE: By default, remaining facets will be
assigned automatically, page 284
when you generate the project or a section.
Assigning Supervision Facets of Instances
Before Starting
To assign Supervision data facets of instances, you must have completed:
• The
• The
Supervision Project Definition stage, page 226
You can only assign facets of instances that have a valid
Data and Link status, page 130 .
You cannot assign the same facet to more than one tag container in the same project but you can assign the same facet to several Supervision projects of the system.
NOTE: To assign Supervision genies facets to a
Supervision project.
Automatic Supervision Project Component Creation
Each time you drag an object from the Instances pane to the Supervision project, one tag
container is created, page 277
.
In addition, depending on the facets that you assign to the tag container, the software may automatically create and configure the following components under the Services
of the Supervision project cluster:
• One I/O server including:
◦ One I/O device
◦ One communication board and its port
• One alarm and/or one trend server (if facets that create alarm and/or trend tags have been assigned).
NOTE: The I/O server and its components are created only for the first tag container of a cluster whether you create the tag container manually or if the software creates it automatically during the assignment. The other servers are created also when you assign corresponding facets to additional tag containers.
Assigning Facets
This procedure describes how to assign data facets of instances to a Supervision project.
EIO0000001114.15
281
Step Action
1 Verify that the instances are displayed in tree view mode in the
Instances pane, else click the
NOTE: Alternatively, you can assign instances using the grid view mode. The assignment principle remains unchanged.
You can switch between views at any time during assignment by clicking the toggle button.
2 In the Containers pane, select the
Supervision.
3
Result
The Assignment Editor displays the
instances of the application in tree view mode.
• The name of the project appears in the title bar of the Assignments pane.
• Any existing containers and the facets already assigned to them are displayed.
The Assignment Viewer
opens.
4
5
From the Instances pane, drag one or more
to the title bar of the Assignments pane.
NOTE: Alternatively, you can drag objects directly to the project in the Containers pane.
Review the information that is displayed, edit the container identifier as needed, and select the cluster.
Click OK .
–
• Containers that do not exist yet are created.
• Supervision data facets that have a status of
Candidate are assigned to the respective container and displayed in the Assignments pane.
• The status of the assigned facets in the
System column of the Facets pane changes to Assigned if the status was Not assigned .
• The status in the Project column of the
Facets pane changes from Candidate to
Done .
NOTE: If an instance contains a facet of type ClientEvent or ServerEvent , the software assigns the facet to the ClientEvents and ServerEvents
respectively.
NOTE: By default, remaining facets will be
assigned automatically, page 284
when you generate the project or a section.
Assigned Facet Description
Facet Description
The Assignments
of the Assignment Editor provides information on the facets that are assigned to an FBD section or tag container.
To see a list of facets that are assigned to a project, select the project in the
Containers pane.
The following information is displayed in the Assignments pane.
Column header
Description
Container Identifier of the section/container to which the facet is assigned.
Instance
Instance
Template
Identifier of the instance that references the facet.
Identifier of the template that the instance is using.
State State of the facet in the context of the instance.
Possible values:
• Valid
282 EIO0000001114.15
EIO0000001114.15
Column header
Description
Facet
Facet
Template
Path
Order
•
• Deleted : The section is
and you have unselected the corresponding element of the instance in the Instance Editor or deleted the instance itself.
Unique identifier of the facet.
Identifier of the template that the facet is using.
Assignment
Generation
Path to the facet in the
composition of the instance, page 134 .
This column applies to Control projects only.
Indicates the order in which the software generates constituents of the facets inside the section and as such, the order in which the Control Participant executes the constituents inside the section.
You can
change the order of facets, page 295
inside a section.
The software applies the order only during:
• A
• A
For more detailed information on how the software manages the facet order, refer to the
description of the generation functionality, page 303 .
Indicates the status of the facet in relation to the instance that references the facet.
Possible values:
• Assigned
• Unassigned
• Out Of Date
• Deleted
Refer to
Assignment Status of Generated Facets , page 320
for a description of the assignment status.
Indicates the status of the facet in relation to the generation of its constituents in the logical Participant project.
Possible values:
• Non Generated
• Generated
• Moved
• Inconsistent
• Unlinked
Refer to
Generation Status of Facets , page 319
for a description of the generation status.
Changing the Element Selection of Instances After Assignment
If you change the Control or Supervision element selection of an instance in the
Instance Editor window after assigning facets of the instance (before generating), the changes are reflected in the respective Assignment Editor .
The table describes how the changes to the element selection of an instance are reflected in the Assignment Editor .
When you...
Select a new element of an instance
Unselect an element of an instance
Then...
The corresponding facets are added to the existing facets of the instance and you can display them in the Facets pane of the Assignment Editor . Proceed with the assignment as described in the assignment procedure.
The corresponding facets are removed from the list of facets in the Facets pane of the Assignment Editor .
If you had already assigned the facets, then they are also removed from the corresponding container.
283
NOTE: Changes impacting the assignment status of facets that you have generated are described in
Assignment Status of Generated Facets , page
Automatic Assignment of Remaining Facets
Overview
The Project Explorer features a functionality that allows you to assign remaining
Control and Supervision candidate facets of instances, which have at least one facet that is already assigned to a Participant project. The assignment is done automatically by the software when you select a
.
The container to which these facets are assigned depends on where the other facets of the instance are already assigned.
There can be candidate facets remaining because you have:
• Not assigned all the facets to a Participant project yet.
• Unassigned facets.
• Changed the
element selection of the instance, page 139
after assignment, which has created new facets.
Information on facets that the software has assigned automatically is displayed in the notification panel.
NOTE: Automatic assignment does not apply to Supervision genie facets.
Using and Disabling the Functionality
The functionality is enabled by default and remains enabled until you disable it in the settings of a
or
Supervision project, page 226 .
Assignment is triggered, page 299
when you use any generation command at the project or project container level.
NOTE: You can still assign facets manually while the functionality is enabled.
Automatic Assignment Criteria
The table describes how the software assigns remaining candidate facets of an instance, depending on where other facets of the instance are already assigned.
Candidate facet type
Control facet
Facets of same instance are already assigned to one container
Candidate facets are assigned to the same FBD section.
Facets of same instance are already assigned to several containers
Supervision facet Candidate facets are assigned to the same tag container.
Candidate facets are assigned to the FBD section to which other facets of the instance are already assigned and that has the lowest Order number.
• Supervision project with one cluster:
Candidate facets are assigned to the tag container that was created first.
• Supervision project with several clusters: Candidate facets are assigned to each cluster. In each cluster, candidate facets are assigned to the tag container that was created first.
NOTE: Only facets that are available are assigned. If a facet is locked, for example, because the instance referencing it is open in the Instance Editor , it remains unassigned.
Viewing Assignments
To verify to which container facets of an instance are assigned, use the
window.
284 EIO0000001114.15
Examples
In this example, three facets of instance Motor_1 are already assigned to section
FBDSection_1 . A modification of the element selection of Motor_1 has created facet Motor_1_DEVMNT , which is candidate to be assigned. The software assigns
Motor_1_DEVMNT automatically to section FBDSection_1 when you generate the project. (Information has been highlighted in yellow for this example.)
In this example, three facets of instance Motor_1 have been assigned to section
FBDSection_1 . The section was generated and the three facets unassigned.
Thereafter, modification of the element selection of Motor_1 has created facet
Motor_1_DEVMNT , which is candidate to be assigned. The software assigns
Motor_1_DEVMNT automatically to section FBDSection_1 when you generate the project again while the three unassigned facets are removed from it. (Information has been highlighted in yellow for this example.)
Automatic Assignment of Supervision Facets
Overview
This topic describes the functionality that is enabled when you associate a Control project to a tag container by using the Associated Control Project
property of the tag container, page 263 .
Working Principle
When you associate a tag container to a Control project, whenever you drag instances (or a folder) to the Containers pane in the Assignment Editor to assign their Control facets to this Control project, the Supervision data facets of these instances are automatically assigned to the associated tag container.
You can see the details of the Supervision facet assignment in the notification panel.
EIO0000001114.15
285
The automatic assignment of Supervision facets is not performed in the following cases:
• When you drag Control facets from the Facets pane.
• When remaining candidate Control facets are
automatically assigned by the software, page 285
.
• When Control facet assignments are created by means of import.
• The instance has no Supervision data facets. In such case, an entry for unsuccessful facet assignment appears in the notification panel.
Visual Indicator
The following partial view of the Assignment Editor shows two tag containers where only TagContainer_1 is associated to a Control project. It is indicated by a blue icon.
286
Further, when you hover with the pointer over the tag container, a tooltip indicates the identifier of the Control project.
Locked Supervision Projects
If the Supervision project that contains the tag container is locked (for example, because it is open for refinement) when the software attempts to assign the
Supervision facets, a dialog box opens. It gives you the following choices:
• Yes : The dialog box closes and the software will attempt to assign both the
Control and the Supervision facets again after waiting for approximately 1 min.
◦ If, at that moment, the Supervision project is still locked, the dialog box opens again.
◦ If the lock has been released, both facets types are assigned without further notification. You can see the details of the facet assignment in the notification panel.
During the wait time, certain actions that you or other users perform on the
Control and the Supervision projects are queued without further notification.
The software will perform these actions automatically once the initial facet assignment is completed. You can see the details of these actions in the notification panel once they are completed. Such actions can be, for example, assigning additional facets to existing tag containers.
Other actions may be forbidden and a dialog box opens to inform you. For example, refining either project or creating new containers.
• No : Only the Control facets are assigned and you can resume working normally. You need to assign the corresponding Supervision facets manually.
If you click No the second time the dialog box opens, actions that are queued will be performed in sequence.
• Cancel : No assignment is performed.
NOTE: If the instance whose Control facets you are assigning has no
Supervision data facets to be assigned and the Supervision project is locked, the dialog box still opens. In this case, click No .
EIO0000001114.15
NOTE: If the dialog box opens and the Supervision project has already been released when you click Yes , the wait time still needs to elapse before the software performs the assignment of facets.
Unassigning Control Facets
When you unassign Control facets, the corresponding Supervision facets that were assigned automatically remain assigned.
Impact on Supervision Project Export and Import
The value that is selected for the Associated Control Project property is exported.
When you import into a system a Supervision project, which has a tag container that is associated to a Control project, the value of the Associated Control Project property after import is as follows:
• If the system contains no Control project with the same identifier, the value is reset.
• If the system contains a Control project with the same identifier, the value is kept and automatic assignment of Supervision facets is enabled.
Viewing the Application Structure in Control Projects
Overview
Switching to tree view mode in the Containers
of the
Assignment Editor allows you to view FBD sections based on the location of instances whose Control facets are assigned to these sections.
It shows the relationship between the folder structure of the application and the sections of a Control Participant project. This is useful, for example, when you want to view the logic related to a specific area or subdivision of the application or verify that the Control facets of a group of instances are assigned to the right sections of a project.
Any FBD section to which a Control facet is assigned appears in the tree view. A section can appear several times depending on the facets it contains.
Independently of where and how many times an FBD section appears, its contents, which is visible in the Assignments pane, is the same.
Changing the application folder structure, the location of instances, facet assignments, and/or the status of facets has an impact on the position of sections in the tree view.
Empty FBD sections and non-FBD sections are shown as well.
NOTE: You can view the application structure also when
Participant projects, page 339
and
making changes online, page 550
.
Root Folder Description
In tree view mode, up to three root folders can appear in the Containers pane.
EIO0000001114.15
287
288
Root folder identifier Description
<system identifier> (for example, System_1
EmptyContainers
)
The <system identifier> (for example, System_1 ) root folder is the parent folder for the application structure. This structure contains sections to which facets with the following status are assigned:
• Assigned
• Out Of Date
• UnAssigned
• Non Generated
• Generated
• Moved
• Inconsistent
Parent folder for sections to which no facet is assigned because you have performed one or more actions such as:
• Created the section manually.
• Unassigned all non-generated facets from the section. If the facets were already generated, you have unassigned all facets and generated the section.
• Disabled a service, which removed the corresponding nongenerated facet. If the facet was already generated, you have disabled the service and generated the section.
• Deleted any instance referencing a non-generated facet assigned to the section. If the facets were already generated, you have deleted the instances and generated the section.
• Moved all facets to another section.
• The section is a non-FBD section.
DeletedFacetContainers Parent folder for sections to which at least one facet is assigned with the status Deleted .
If the section contains at least one facet with another status, the section also appears under the <system identifier> root folder.
Once you generate the section and the Deleted facet is removed from the section, the section appears only under either of the two other root folders depending on the facets that are assigned to it.
No application folders are shown under this root folder.
NOTE: A root folder appears only if there is a section in its folder structure. For example, if there is no empty section, the EmptyContainers root folder is not shown.
Relation Between Folder Structure and FBD Sections
A folder structure can contain several sections if facets referenced by instances in that folder structure are assigned to multiple sections.
A section can be shown multiple times under different folder structures if the facets assigned to this section are referenced from instances located in various folders.
EIO0000001114.15
In this example, the application contains three folders. The Control facets referenced by each instance are assigned to separate FBD sections.
Folder_2 is empty.
The following is an extract of the Assignment Editor , which shows the corresponding FBD sections in the Containers pane of the Control project in grid view mode . The project node is not shown.
The following figures show how the FBD sections are displayed in relation to the folder structure of the application in the Containers pane in tree view mode .
EIO0000001114.15
289
290
If during assignment, you had assigned one facet of instance Valve_1 also to section Motor_20_Motor , this section would appear twice. Under Folder_20 because of facets of instance Motor_20 and under Folder_1 because of the facet of Valve_1 . The following figure shows this.
Impact of Changes in the Application on the Tree View
In tree view mode, changes to the application are reflected.
Changes that you make to the folder structure of the application are reflected in folder structure shown in the Containers pane.
Changes that you make to the location of instances whose facets are assigned to sections are reflected in the position of these sections in the Containers pane.
Based on the application of the previous example, if you create Folder_3 and move instance AnalogInput_1 to this folder, the tree view is modified as shown in the figure.
EIO0000001114.15
If you delete instance AnalogInput_1 and its facets were generated, the status of the facets changes to deleted. When this happens, section AnalogInput_1_
AnalogInput appears under the DeletedFacetContainers root folder as shown in the figure.
NOTE: Folder_3 is empty and therefore it does not appear in the Containers pane.
Impact of Changes to Assignments on the Tree View
Changes that you make to the assignment of facets are reflected in the position of sections in the Containers pane.
If without changing the application, you move a facet of the Valve_1 instance to the Motor_20_Motor section, the section appears also under Folder_1 because the instance is located in Folder_1 .
EIO0000001114.15
291
If you had generated section AnalogInput_1_AnalogInput , delete the instance, and generate the section again, the Deleted facets are removed from the section and the empty section now appears under the EmptyContainers root folder. The result is shown in the following figure.
Managing Assigned Facets
Overview
This section describes the actions that you can perform on assigned facets by using the Project Explorer and the Application Explorer .
It also describes how to access containers to which facets are assigned and how to open the Assignment Editor from facets that you have not yet assigned to a project.
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
Facet Actions After Assignment
Overview
This topic applies to facets that are assigned but not yet generated.
For information on facets that are generated, refer to the topic describing
management of generated facets, page 332 .
Commands and Actions
Once you have assigned Control or Supervision data facets of instances to the respective project, you can execute the following commands and actions on these facets from the Assignments pane of the Assignment Editor .
292 EIO0000001114.15
EIO0000001114.15
Command/Action
Unassign
Go To Instance
Move the facet
Description
Removes the facet from the section or container.
You cannot unassign facets that have the Assignment status of deleted .
Refer to
Unassigning Facets , page 293 .
NOTE: The actions that the software executes when you select the Unassign command for a non-generated facet is different than if you execute the command on a
Shows the instance that references the facet in the Application
Explorer .
The navigation feature is not available if the Assignment status of the facet is deleted .
Refer to the topic describing how to
navigate from facets to the instance , page 296 .
Changes the assignment of a facet to another FBD section or tag container. Does not apply to
.
Refer to
NOTE: The
and
commands that you can access from the facet context menu become available only once you have completed the generation stage.
Unassigning Facets
To unassign a non-generated facet from a section or container, proceed as follows.
Step Action
1 In the Assignments pane of the Assignment
Editor , right-click the facet and select Unassign .
NOTE: You can select multiple facets to unassign them at once.
Result
The facet is removed from the Assignments pane and:
• The status of the unassigned facet displayed in the
System column in the Facets pane changes from
Assigned to Not assigned if the facet is not assigned to any other project of the system.
• The status of the Project column changes from Done to Candidate .
Moving Facets
To move a non-generated facet from one FBD section/tag container to another, proceed as follows.
Step Action
1 In the Assignments pane of the
Assignment Editor , right-click any one of the column headers to
clear filters and sorting, page 93 .
2 Drag the facet to another FBD section of the same task folder or tag container that is shown in the
Containers pane.
NOTE: You can select multiple facets to move them at once.
Result
-
•
•
The facet is removed from its original container and assigned to the target one.
The assignment status of the facet is unchanged.
NOTE: Control facets that you move are assigned to the new section with the highest order value in the
Order column of the Assignments pane, page 257 .
When you move several facets at once, the facet that you have selected first gets the lowest order out of the ones that are moved.
293
Viewing Facet Assignments
Overview
By opening the View Assignments window for any instance of the application, you can verify if Control facets and Supervision (data and genie) facets are assigned to a project of the system.
For each facet, you can:
• If the facet is not yet assigned:
Open the corresponding Assignment Editor , page 257
for existing projects of the system. For genie facets, you can open the Pages container of existing Supervision projects.
• If the facet is already assigned: Open each container to which it is assigned and locate the facet.
Opening the View Assignments Window
In the Application Browser
, right-click an instance and select
View Assignments .
NOTE: You cannot open the View Assignments window if both conditions are true for the instance:
• Assigned status is Unassigned .
• Data or Link status is Invalid .
View Assignments Window
The following figure shows an example of the View Assignments window for instance MyMotor_1 , whose Control and Supervision data facets are assigned but not its genie facets.
294
4
5
2
3
Item
1
Description
Displays the elements of the selected instance grouped by Participant.
For each Participant, elements are grouped by one or more levels of categories. For example, category Control and subcategory Interlocks contain element Logic .
Indicates the subtype of the facet.
Identifier of the facet that corresponds to the element.
Identifier of the template that the facet is using.
Facet assignment status.
Possible values:
• Unassigned : The facet is not yet assigned to any project of the system.
• Assigned : The facet is assigned to, at least, one project of the system.
EIO0000001114.15
7
8
Item
6
6
Description
For Control facets, the following information is displayed:
• For unassigned facets: A list of existing Control projects in the system to which you can assign the facet.
Click a project in the list to open its Assignment Editor .
• For assigned facets: The list of sections to which the facet is assigned.
Section identifiers are shown in the format: ProjectIdentifier .
SectionIdentifier .
Click a section to show or open the Assignment Editor . The section and facet are highlighted.
NOTE: For unassigned facets, if no Control project exists in the system, the column is empty.
For Supervision data and genie facets, the following information is displayed:
• For unassigned facets: A list of existing Supervision projects in the system to which you can assign the facet.
Click a project in the list to open its Assignment Editor .
• For assigned facets: The list of containers to which the facet is assigned.
Container identifiers are shown in the following format format:
◦ For data facets: ProjectIdentifier .
ClusterIdentifier .
ContainerIdentifier .
◦ For genie facets: ProjectIdentifier .
PageIdentifier .
Click a container to show or open the Assignment Editor . The container and facet are highlighted.
NOTE: For unassigned facets, if no Supervision project exists in the system, the column is empty.
Elements of the instance, which generate a facet and that are shown when you open the Instance Editor .
Elements of the instance, which generate a facet and that are shown when you
inspect the instance, page 155 .
NOTE: The View Assignments window is closed automatically when you navigate to the Assignment Editor .
Order of Control Facets
Overview
The software assigns an
to facets that you assign to an FBD section, starting at 0, and displays it in the Assignments pane. The values appear in the Order column.
The order corresponds to the execution order of the constituents of the facet by the Control Participant inside the section after you generate the section.
You can change the order of facets inside an FBD section.
The software applies the default order or changes to this order only until the
of the section. After you have generated the section a first time, you can still change the order of facets inside the section. However, the change has no effect on the order of already generated facet constituents if you generate the section again. You need to
the section for the software to apply the new facet order.
Changing the Facet Order
To change the order of Control facets inside an FBD section, proceed as follows.
EIO0000001114.15
295
Step
1
2
3
Action
In the Containers pane, select the FBD section that contains the facets that you want to rank.
Result: The facets that are assigned to the selected FBD section appear in the
Assignments pane.
In the Assignments pane, right-click any one of the column headers and
clear filters and sorting, page 93
.
Result: The facets are displayed in increasing order from top to bottom.
Drag a facet up or down to a new position until you see a tooltip, which indicates the position that the facet will occupy when you release the mouse button.
Result: The facet appears in the selected position with a new order value.
NOTE: To change the execution order of the FBD sections, refer to the topic describing how to
change the order of sections , page 207 .
Navigating from Facets to the Instance
Overview
From a facet that is shown in the Assignments pane of the Assignment Editor , you can open the Application Explorer to show the instance that references this facet.
The navigation feature is available for:
• Control facets.
• Supervision data and genie facets.
Conditions Impacting Navigation to the Instance
The table describes the scenarios where navigation to the instance is limited or not possible.
Condition
The Assignment status of its facet is
Deleted .
The instance is not shown in the
Application Browser because a
is applied.
The Application Browser pane is minimized or in the background (if tabbed).
Result
The Go To Instance command is not available.
The Application Explorer opens or is shown but a dialog box informs you that the instance is not visible.
The Application Browser pane remains minimized or in the background.
If the instance is open in the Instance Editor , the corresponding tab is shown.
Navigating to the Instance
To navigate from a facet assigned to a project container to the instance that references this facet, proceed as follows.
Step
1
Action
Rick-click the facet and select Go To Instance .
Result: The software:
• Opens the Application Explorer window if it is not yet open. If it is, the window is shown.
• Expands the application folder containing the instance.
• Selects the instance that references the facet.
296 EIO0000001114.15
Generation Stage
What’s in This Chapter
Generating Projects After Changes............................................................... 323
Generating Equipment in Supervision Projects .............................................. 329
Generation Diagnostic Messages ................................................................. 331
Overview
This chapter describes how to create the logical Control and Supervision
Participant projects of the system.
The following figure shows the position of the Generation stage within the system engineering life cycle.
Refer to the
for a description of the purpose of this stage.
General Description
Overview
This section gives a general description of the generation process of Control and
Supervision Participant projects.
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
Generation Process Description
Overview
Once you have assigned Control and/or Supervision facets to the containers of their respective projects, you need to generate these projects.
EIO0000001114.15
297
298
During the system engineering life cycle, the generation process of Participant projects can encompass up to three steps:
• A
first-time generation, page 321
.
• A
generation after changes, page 323 .
• A Control Participant project
.
You can generate the entire projects or parts of it.
The generation process creates the logical Participant project.
For Control projects the generation process:
• Creates the derived function blocks (DFBs) and variables based on the constituents that are encapsulated inside the facets according to the assignment of the facets in the structure of the project and their
• Creates links between function blocks generated from different facets, which are assigned to the
same FBD section, page 301 . In addition to links that are
defined at the template level, links created in an editor of the Application
Explorer are processed.
For Supervision projects, the generation process populates the native Supervision
Participant database files for:
• Tags from Supervision data facets.
• Report events from Supervision server event facets.
• Events from Supervision client event facets.
• Supervision project components.
• User interface messages.
•
.
NOTE: You can abort the generation of
and their
as well as the
Data Validation Before Generating
When you select the Generate or ReGenerate command for a project or a container, the software first verifies if the constituents of the assigned facets satisfy the applicable
.
The software behaves as follows when it detects that the applicable naming rules are not satisfied:
• For Control facets, it does not generate containers nor constituents in the logical Participant project even those that satisfy the naming rules.
Refer also to the topic describing the
impact of detected errors on generation, page 301 .
• For Supervision facets, it generates only the constituents that satisfy the applicable naming rules.
• For both facet types, it displays a diagnostic message, which contains the identifiers of the containers, assigned facets, and their parameter values that do not satisfy a naming rule.
Generating Facets of the Same Instance Assigned to Several
Projects
You can generate several projects simultaneously even when facets of the same instance are assigned to these project.
The projects can be Control and/or Supervision projects.
EIO0000001114.15
EIO0000001114.15
Generating Automatically Assigned Facets
By default, the software
assigns candidate facets automatically, page 284
when you select any generation command at the project or project container level.
If among the instances whose facets are already assigned to the Participant project, at least one facet remains with the status Candidate , the software opens a dialog box to remind you that the functionality is enabled before executing the command. You have the possibility to cancel generation and disable the automatic assignment of these facets.
If the software is not able to proceed with the automatic assignment of a facet, generation of assigned facets completes but the notification panel displays information on the facets that it could not assign and generate.
If generation does not complete successfully, facets that the software has assigned automatically are unassigned.
NOTE: Generation takes a little longer to complete when the functionality is enabled.
Generating During Build Stage
To save time or if you have made minor changes to a logical Participant project, instead of using the Generate command, you can use the Generate and Build command from the
or
context menu. This performs a generation followed by a build. You need to have completed the system engineering life cycle up to the build stage.
If you generate a complete Participant project and
generation of any section, page
or generation of any container does not complete, build is not started.
Information about the sections/containers that were not generated is displayed in the notification panel.
If build is not started or does not complete successfully, the result of the generation process is the same as if you had selected the Generate command for the Participant project. This means, for example, that for a Control Participant project, sections that were successfully generated remain generated.
The Generate and Build command:
• Cannot be used to perform a
.
• Can be used together with the
automatic facet assignment functionality, page
• Automatically performs a Build or Build All
depending on the type of change that you have made to the Participant project.
NOTE: After selecting the command, the abort icon is displayed in the
notification panel, page 54 . Click the icon to cancel the task. Only the user
who has selected the command is allowed to abort it.
If you cancel the task:
• Before generation completes, the entire generation task is canceled and no sections are generated. Build does not start.
• After generation completes, only the build task is canceled and the software displays a notification to inform you.
If you are generating and building a small project, the whole task may complete before you are able to click the icon.
Generating Facets with State Invalid
If the
has become Invalid after you have assigned it, generating the container or Participant project removes the facet from the container.
This can be the case, for example, when you link instances A and B (where instance A needs to be linked to be valid), assign their facets to a Control project,
299
and then delete the link between the two instances. The facet of instance A becomes invalid because the instance is not linked anymore.
Generating the section to which the invalid facet is assigned removes it from the section.
Skipping Facets During Generation
If a facet is locked, the constituents that it encapsulates cannot be generated. In such case, the locked facets are skipped but generation of the section or the
Participant project completes for the other facets. This may happen, for example, when an instance is open in the Instance Editor .
The generation status of a facet that is skipped does not change.
The notification panel contains information about locked facets that the software could not generate.
Control Project Specifics
Overview
This topic describes the default behavior when generating Control Participant projects and the settings that you can configure to customize the generation process.
Identifying Code Generated by Control Facets
Constituents that are generated from facets assigned to Control projects are locked in the Control Participant project. The locked code is color coded in the
DFB editor of the Control Participant when you
.
Validity Indicators
When you execute any generation command on a logical Control Participant project or any of its containers (including the Generate and Build command) and
project analysis is enabled, page 205 , the software performs an analysis.
If the result of the analysis raises and alert or detects an error, the software displays a
In such case,
the Control Participant project, identify, and fix the issue. When you save your refinement changes, the software performs a new analysis. The result is shown in the Analyze Project tab of the Control Participant window.
300 EIO0000001114.15
EIO0000001114.15
NOTE: It is possible that the software detects inconsistencies that are linked to the default configuration in the Control Participant, which is part of every logical Control project but that is not relevant in the context of the Project
Explorer (except for
M580 safety Control projects, page 579
). These detected errors do not affect the capability to build the project successfully if you configure the topological entities correctly in the Topological Explorer .
This can be the case, for example, when the application contains an instance of a communication port template, which requires that you enter a %MW holding register starting address. During generation, this address is checked against the default address in the CPU of the default configuration . If both addresses are not consistent, a validity icon is displayed. But when you build the logical Control Participant project, this address is checked against the address that you configure in the CPU of the entity in the Topological
Explorer , which needs to be consistent.
It can also happen because the logical Control Participant project is missing
IODDT variables (for example, when the configuration contains HART
Device DDT variables, page 547 , which exist only in
the configuration project until you perform the build or
.
If fixing the inconsistency requires that you change a value in the CPU of the default configuration , you still have to verify that the value in the CPU is configured correctly in the Topological Explorer by using the Configure command for the entity to which the Control Participant project will be mapped.
Generating Graphical Links
Inside the same FBD section, the software generates graphical links between function blocks that use the same variable and that are encapsulated inside different facets only if the following conditions are satisfied:
• The variable is created by a facet (not created manually by the user).
• The resulting link:
◦ Links the output pin and input pin of separate function blocks.
◦ Is not a circular link.
The software breaks any graphical circular link and creates it as variable link.
Impact of Detected Errors or User Action During Generation
When you select the Generate or Generate and Build command for a project containing several sections and the software detects an error, the impact on the generation process depends on the detected error or the user action that is performed.
NOTE: The behavior is the same when you
a Control
Participant project.
Detected error or user action
Variable name conflict (1)
Type version conflict (1)
Clicking Cancel in the Type Version
Conflict
Operation in the Control Participant did not succeed (for example, injecting data in a section through import).
.NET exception occurred (for example, an
Object reference not set diagnostic message is shown).
Impact on the generation process
Generation stops. Code of sections that have been successfully generated remains in the logical Control
Participant project.
The section which contains the detected error and any subsequent sections are not generated.
A summary dialog box indicates the identifier of the section where generation stopped as well as the reason.
301
Detected error or user action
Section overcrowded (1)
Impact on the generation process
Generation completes but any overcrowded section is not generated.
Details are provided in the summary dialog box.
(1) Refer to the topic describing
diagnostic messages, page 331 .
In the following example, ControlProject_2 , which consists of four sections is being generated for the first time but the software stops the generation process because of a variable name conflict in FBDSection_3 (the section name is highlighted for the purpose of the example). As a result, FBDSection_1 and
FBDSection_2 are generated in the logical Control Participant project.
FBDSection_3 is not generated because it contains the conflicting variable and
FBDSection_4 is not either because it is generated only once generation of
FBDSection_3 completes
302
NOTE: If you had selected the Generate and Build command, build would not start because at least one section did not generate.
Control Project Section Size
During generation, FBD sections are created in the Control Participant project with a maximum initial size of 360 rows x 240 columns. You can
.
If additional space is required to fit the function blocks that are generated from the facets assigned to a section, the software adapts the section size by:
• Deleting empty columns on the outer right of the section to add rows at the bottom of the section.
• Deleting empty rows at the bottom of the section to add columns on the outer right of the section.
The software displays a message to inform you of the change in section size.
If you want to reserve some space in the section, you can insert a comment box on the right-hand side of the section and/or at the bottom of the section so that the software does not delete the rows that are left and/or above the comment box when resizing the section.
When the space requirements of the function blocks exceed the maximum section size, the software displays a
diagnostic message, page 331 .
NOTE: The section resizing process applies to a first generation, subsequent generations, and regenerations.
EIO0000001114.15
EIO0000001114.15
Execution Order and Function Block Layout
When you generate a Control project for the first time, the software processes the facets that you have assigned to the project and that have an Assignment
of Assigned . It takes into consideration the
at the project level and the
at the section level.
Refer also to the topic giving an example of section layout management (see
EcoStruxure ™ Process Expert, Control Participant Services, User Guide).
The table describes the process that the software applies during a first generation to manage the order of sections and facets, and the position of function blocks inside a section.
Stage
1
2
3
4
Description
The software detects the
of the project sections and processes the sections starting with the one ranked 0; then the section ranked 1; and so on, until it has processed the sections of the entire project.
For each section, the software detects the
of the first facet of each instance that is assigned to the section.
The software generates the function blocks encapsulated in the facets according to the order that it has detected in stage 2, starting with the facet ranked 0. However, the software groups the function blocks according to the
of the composite referencing the facets.
For example, if a section contains two instances, Instance1 and Instance2, referencing three and one facets respectively, and ordered as follows:
Facet1_Instance1 - Order 0
Facet1_Instance2 - Order 1
Facet2_Instance1 - Order 2
Facet3_Instance1 - Order 3
The software generates Facet1_Instance1 before Facet1_Instance2 but groups function blocks of facets 1, 2 and 3 of Instance1 at the top of the section to respect the layout of the composite template used by Instance1.
Therefore, function blocks of Facet1_Instance2 are placed at the end in spite of the order of the facet, which is 1.
If a function block is generated in a position that is already occupied by another function block, creating an overlap, the function block generated last is moved to the end of the section content.
The block keeps its horizontal position (X axis) as defined by the layout of them template referencing it.
In such case, the software displays a message advising you about the change in position and a possible change in the execution order.
Facet Status After Unsuccessful Generation
The table describes the effect on the status of Control facets when the generation of a section or any facet is not successful.
Generated component
Entire Control project
Control project section
Facet status
The generation status of facets assigned to the entire project reverts to the value it was before generating.
The generation status of facets assigned to the section reverts to the value it was before generating.
Removing Types from the Logical Control Participant Project
Types generated from Control facets remain in the logical Control Participant project even when you
unassign generated facets, page 332
encapsulating them,
303
the facets by deleting the instance, or
to which these facets were assigned.
To remove these types, you can either:
•
the Control Participant project. This discards refinements you have made.
• Purge the types from the Control Participant during refinement. For details, refer to Purge of Unused Instances in the Control Participant help.
Parameter name
ReGenerateNonFbdSections
UnityProIgnoreFbdComments
UnityProMinSpaceTop
UnityProMinSpaceLeft
UnityProMinDistanceX
UnityProMinDistanceY
UnityProUseEffectiveSize
UnityProInsertToEnd
CheckConsistency
True
0
10
5
2
SaveAfterNumberSectionGenerated
30
Configurable Generation Settings
By editing the GenerationSettings.xml file, you can customize the behavior of the generation process of Control Participant projects.
The file is located on the computer on which the system server is installed at the path C:\Program Files\Schneider Electric\EcoStruxure\Process Expert\System
Server.
You need to have administrator rights to be able to edit this file.
NOTE: Changes to the file are applied only after a
.
You can configure the following parameters.
Default value
True
False
True
True
Description
True = The behavior during a regeneration is the following:
• Non-FBD sections that were created during refinement and their contents are retained.
• Refinements that are made in FBD sections to which facets are assigned are discarded.
• Refinements made in FBD sections that were created in the Projects
Explorer are retained if no facets have been assigned to these sections.
False = The behavior during a regeneration is the following:
• Non-FBD sections that were created during refinement and their contents are discarded.
• Refinements that are made in FBD sections are discarded whether facets have been assigned to them or not.
NOTE: The value of this parameter has no impact on the regeneration of data and logic of the safety program of
M580 safety Control projects, page 585
projects.
True = Comments of FBD sections are not generated.
Minimum space that the software leaves above function blocks that are positioned at the top of the section.
Minimum space that the software leaves at the left of any function block that it generates.
Minimum space that the software leaves between two consecutive function blocks along the x axis.
Minimum space that the software leaves between two consecutive function blocks along the y axis.
True = The minimum space around function blocks is decreased to help utilize the space of the section more effectively.
• True = The software puts function blocks that are generated after a first generation at the end of sections independently of the position that they would normally occupy.
• False = The software lays out function blocks according to the default behavior when
generating Control Participant projects after changes, page 326
.
This is not a user-configurable parameter.
Changing the value affects the behavior of the software.
Number of FBD sections that need to generate successfully to trigger a save command in the Control Participant.
304 EIO0000001114.15
Parameter name Default value Description
NumberOfUnitySectionRows
NumberOfUnitySectionColumns
36
24
(1)
(1)
If you are generating a number of sections lower than the value, a save command is executed once generation completed successfully.
NOTE: Reducing this number may increase generation time because the number of save operations is higher. The setting does not alter the
impact of detected errors during generation, page 301 .
Number of rows/columns that the section contains when it is created by generating the Control Participant project or section for the first time or regenerating it.
NumberOfUnitySectionRows allowed range: 24 to 144
NumberOfUnitySectionColumns allowed range: 6 to 36
NOTE: If you modify the default section size or if the Control Participant creates a section that is different from your settings, generation or regeneration may not complete successfully because constituents cannot be
as required.
(1) NumberOfUnitySectionRows x NumberOfUnitySectionColumns =< 864. If this value is exceeded, either 24 or 144 is retained for the number of rows (the value that comes closest to NumberOfUnitySectionRows ) and the number of columns adjusted in consequence, independently of the setting of NumberOfUnitySectionColumns . For example, if you enter 200 and 7 respectively, a section of size 1440 x
60 is created because 200 exceeds the allowed number of rows and is closer to 144 than to 24.
Selecting Versions of Types in Control Facets During Generation
Overview
Because in a logical Control Participant project, only one version of a given type can exist, either of the following situations require that you select which version is generated:
• You are assigning to a Control Participant project facets that encapsulate the same type but different versions of it.
• You have
updated or replaced the template, page 161
that is used by an instance whose facets are already assigned to a Control Participant project and generated. The new template contains the same type (DFBs and/or
DDTs) but of a different version. The assignment status of one or more of these facets has been set to Out Of Date .
If such a case occurs, when you generate the logical Control Participant project to apply the changes, the software detects the presence of several versions for a same type.
As a result, the software opens the Global Constituent Type Version Conflicts dialog box in which you can select either command to select the version that you want to use in the logical Control Participant project:
• Update
• Skip
• Cancel
The software maintains a list of the various versions of a type that it detects during each generation cycle and applies your initial selection when it detects a version again. If the software detects a new version of the same type when it generates the next section, it opens the Global Constituent Type Version Conflicts dialog box again.
The detection of the version change is performed at the facet level and it is irrelevant to which instance a facet belongs.
However, if two or more versions of the same type are detected in the same section, generation stops. In this case, the software informs you about the facets, the type, and the versions that create the conflict. You need to resolve the version conflict at the instance or facet level manually.
This topic contains several examples illustrating the main scenarios that you may encounter.
EIO0000001114.15
305
306
NOTE: Although you select the version at the section level, updating the version of a type impacts all its instances across all sections of the Control
Participant project. Also, the last action that you select for a given type is the one that is applied.
NOTE: The Global Constituent Type Version Conflicts dialog box also opens if the software detects the same version of a type but with a
different signature, page 308 .
Relation Between Type Versions in the Application and in
Control Projects
The version of the type that you select to use in the logical Control Participant project is not necessarily the same as the version that is encapsulated in the template used by instances of the application. Indeed, in the application, instances can use several versions of a same template encapsulating different versions of a type. The version of the type that is used in the logical Control Participant project can only be one of these versions.
This example shows the different versions of a template that are used by three instances of the application. Each template encapsulating a different version of a
DFB. It also shows the single type version that is generated in the Control project.
Template version and encapsulated type version in the application
Template_A [1.0.0], type version 1.2
Template_A [1.0.1], type version 1.3
Template_A [1.0.2], type version 2.0
Type version used in the logical Control project
Type version 1.3
This second example shows that different versions of a type can be used in different Control projects, each project using only a single version.
Template version and encapsulated type version in the application
Type version used in logical Control project 1
Template_A [1.0.0], type version 1.2
Type version 1.3
Template_A [1.0.1], type version 1.3
Template_A [1.0.2], type version 2.0
Type version used in logical Control project 2
Type version 2.0
Impact of Type Version Selection on Links
Selecting Update or Skip for a facet removes links with any instance of the encapsulated type if a pin for which a link exists is impacted in either way:
• The pin is removed.
• The pin is renamed.
The software displays a message informing you of the links that have been removed after generation completes.
EIO0000001114.15
Global Constituent Type Version Conflicts Dialog Box
The following figure shows an example scenario where several DFB and DDT types create a version conflict in FBDSection_1 .
7
8
2
3
4
5
Item
1
6
Description
Identifier of an instance referencing a facet that is assigned to this section and that encapsulates the type. If other facets encapsulating the type and assigned to the section are referenced by different instances, the number of instances is indicated.
Expand the row to view a list of these instances with the template identifier and version each one uses. A tooltip displays the same information when the row is not expanded.
Name of the type encapsulated in the facets for which a version conflict is detected.
Version of the type that is currently used in the logical Control Participant project.
Version of the type that is encapsulated in the facets being generated.
Button that lets you select the Skip action for individual types.
Does not update the type (1) that is currently used in the logical Control project (version X ) to version Y , which is the version encapsulated in the facet. Also, it does not generate the facet.
For each generation cycle, the software maintains a list of the various versions of a same type that it has detected. Based on this list, if other facets encapsulate version X or y of the same type, no dialog box opens and version X is maintained automatically.
If, in another section, the software detects a facet that encapsulates the same type but of a version that is different from version
X and version Y (for example, version Z ), the Global Constituent Type Version Conflicts dialog box opens again. Version Z is added to the list of versions already detected.
The generation status of facets may be set to inconsistent. In such case, when generation completes, the software provides a summary with the name of the facets that are affected and the name of the section they are assigned to.
NOTE: Skip only skips the generation of the facet that encapsulates the type. Other facets belonging to the same instance are generated if their
requires it (for example, if it is Out Of Date ).
Button that lets you select the Update action for individual types.
Generates the facet and updates the type (1) currently used in the logical Control project (version X ) to the version that is encapsulated in the facet (version Y ). The status of the facet becomes Generated .
For each generation cycle, the software maintains a list of the various versions of a same type that it has detected. Based on this list, if other facets encapsulate version X or y of the same type, no dialog box opens and version Y is used automatically.
If, in another section, the software again detects a facet that encapsulates version X of the same type and the facet is not generated, it remains non-generated.
If, in another section, the software detects a facet that encapsulates the same type but of a version that is different from version
X and version Y (for example, version Z ), the Global Constituent Type Version Conflicts dialog box opens again. This allows you to update the current version of the type (for example, version Y ) to version Z . Version Z is added to the list of versions already detected.
The generation status of facets may be set to inconsistent. In such case, when generation completes, the software provides a summary with the name of the facets that are affected and the name of the section they are assigned to.
NOTE: version Y can be a version later or earlier than version X . The same applies to version Z compared to the other versions.
Copies the content of the dialog box to the Clipboard.
Buttons that let you select an action for the conflicting type versions as a whole.
EIO0000001114.15
307
Item Description
9
The actions are the same as when you select the action for types individually.
NOTE: Clicking these buttons overrides the selection you have made for individual types.
Generation of the Control Participant project stops. Code of sections that have been generated successfully remains in the logical Control Participant project. The type (1) version that was used after the generation of the previous section is maintained.
The section in which the version conflicts have been detected and any subsequent sections are not generated.
10 Generates the section by applying your selection of actions for conflicting types.
(1) Includes all the types encapsulated in the facet if more than one, for example the DFB and its DDT. You cannot select to update or skip one and not the other.
NOTE: The status of facets is updated only after the entire generation process is completed.
Setting the Status of Facets to Inconsistent
Updating or skipping the version of a type may set the generation status of a facet to Inconsistent . The assignment status does not change.
The table describes under which conditions the generation status is changed.
Status of the type version
The version has already been detected during this generation cycle but is different from the one currently used in the
Control project.
Required facet status
Assignment: Out Of Date
The version has not yet been detected during this generation cycle.
Assignment: Out Of Date
Required user action
Because the version has already been detected, the Global
Constituent Type Version
Conflicts dialog box does not open; therefore, no action is required.
Refer to
You are selecting Skip for the proposed version change after having already selected Update for the same type in another section during the same generation cycle.
Refer to
NOTE: If the status of the facet is Non Generated , it does not change.
Detecting Types of Same Version But With Different Signature
The Global Constituent Type Version Conflicts dialog box also opens if the software detects in a facet assigned to the Control project and which needs to be generated, the same version of a type as it is already used in the logical Control project but with a different signature.
The following figure shows an example of detection of a type of the same version but with a different signature. A tooltip indicates the nature of the conflict when you position the pointer over the version of the type.
308 EIO0000001114.15
EIO0000001114.15
• Update : The type in the logical Control project is updated with the type and signature that is encapsulated in the facet.
• Skip : The type that is used in the logical Control project continues to be used; no update is performed. The generation status of facets may be set to
.
Independently of the action that you select, the Global Constituent Type Version
Conflicts dialog box opens again if in another section of the same Control project another facet is detected, which encapsulates the same version of the same type and with a signature that is the same as in the previous facet or with yet another signature.
If two or more facets encapsulating the same version of a type but each with a different signature are detected in the same section,
.
Performing a Consistency Check After Version Conflict
Detection
It is recommended to perform a
when the software detects several versions of the same type or the same version with different signature during generation of a Control Participant project.
A consistency check detects which generated facets encapsulate a type whose version or signature is different from the version/signature of the type used in the
Control Participant project. The status of such facets is set to Inconsistent .
The following example illustrates a scenario where a consistency check allows identifying a facet that contains a version of a type that is different from the version used in the Control project after the software detected a version conflict. In this example, v1.0 of DFB_A type was generated in the Control project by Facet_2. A second facet (Facet_1) containing v2.0 of the same type is assigned to a different section and the project is generated again.
Section Facet DBF_
A type version
Facet assignment/ generation status before generating
Section_1 Facet_
1 v2.0
Section_2 Facet_
2 v1.0
Out Of Date/
Generated
Assigned/
Generated
Facet status after generating and performing a consistency check
Assigned/
Generated
Comment
Assigned/
Inconsistent
The software detects a version conflict and you update the type used in the Control project to v2.0 by selecting
Update .
Because the facet encapsulates v1.0 of the type, the consistency check has set the status of the facet to Inconsistent .
Regenerating a Control Participant Project After Type Version
Changes
When you select the Regenerate command after generating a Control Participant project or section in which version conflicts were detected, the behavior is different depending on what you regenerate.
If you regenerate the entire Control Participant project, the software removes the types from the logical Control project and generates the ones that are encapsulated in facets assigned to the Control Participant project sections. If various versions of a same type are detected again, the Global Constituent Type
Version Conflicts dialog box opens.
If you regenerate a section of a Control Participant project, the software
maintains existing types, page 327
in the logical Control project and starts over the generation process. During regeneration, it compares:
309
310
• For the first facet of the section that encapsulates a type, the version of the type.
• The version of this type that exists in the logical Control project.
If they are different, it opens the Global Constituent Type Version Conflicts dialog box.
If they are identical, it performs the comparison with the second facet of the section encapsulating a type, and so on.
In case several versions of the same type are detected
, generation stops.
Examples
The following examples illustrate various type version conflict scenarios when facets are assigned to the same section.
Description
A facet is assigned to an already generated section.
A section contains two facets that are not generated.
A section contains two facets that are generated and one of them is updated to use a different version of the type.
Command used
–
A generated facet is updated while the same section contains a non-generated facet.
This example illustrates a possible solution to examples 1.
Update and Skip
Refer to
The following examples illustrate various type version conflict scenarios when facets are assigned to different sections.
Description
Two different versions of the same type in different sections of a Control project.
Several different versions of the same type in different sections of a Control project.
Two different versions of the same type in different sections of a Control project.
Several different versions of the same type in different sections of a Control project.
Several different versions of the same type in different sections of a Control project.
Two different versions of the same type in different sections of a Control project.
Command used
Update
Skip
Refer to
Update and Skip
Cancel and Update
The Regenerate command is also described.
Example 1a: Two Different Versions of the Same Type in the
Same Section
A facet is assigned to an already generated section.
The starting point is the following:
• One facet is assigned to Section_1 and generated.
• The facet encapsulates DFB_A.
EIO0000001114.15
Facet ID
Facet_0
DFB_A version encapsulated in facet v1.0
Facet assignment/ generation status
Assigned/Generated
DFB_A version used in
Control project v1.0
Facet ID (1)
Facet_0
Facet_1 v1.0
v2.0
Then, another facet encapsulating DFB_A but of a different version is assigned to the same section. The section is generated again to apply the changes.
The table explains the behavior during generation of Section_1 and which version of DFB_A is used in the end.
DFB_A version encapsulated in facet
Facet assignment/ generation status after generation
Assigned/Generated
Assigned/Non Generated
DFB_A version used in
Control project after generation v1.0
Comment
The software detects v2.0
while v1.0
is already generated. Because the conflict arises in the same section,
and DFB_A version v1.0
is maintained.
The status of facets is unchanged.
To be able to generate the section, you can either:
• Unassign one of the facets from the section.
• Update the template used by one of the instances so that both facets
use the same version of DFB_A, page 313 .
• Unlink Facet_0, generate the section, select
Update when the Global Constituent Type
Version Conflicts dialog box opens, then relink Facet_0.
(1) The order of facets in the section is not relevant.
(Back to
example summary table, page 310 .)
Example 1b: Two Different Versions of the Same Type in the
Same Section
A section contains two facets that are not generated.
The starting point is the following:
• Two facets of two different instances are assigned to Section_1.
• Both facets encapsulate DFB_A but of a different version.
• DFB_A does not exist in the Control project.
Facet ID
Facet_0
Facet_1
(1) DFB_A version encapsulated in facet v1.0
v2.0
(1) The order of facets in the section is not relevant.
Facet assignment/generation status
Assigned/Non Generated
Then, the section is generated.
The table explains the behavior during generation of Section_1 and which version of DFB_A is used in the end.
EIO0000001114.15
311
Facet ID
Facet_0
Facet_1
(1) DFB_A version encapsulated in facet v1.0
v2.0
Facet assignment/ generation status after generation
Assigned/Non Generated
DFB_A version used in
Control project after generation
None
Comment
The software detects v1.0
and v2.0
in the same section. Because of this,
and no version of DFB_A is generated.
The status of facets is unchanged.
To be able to generate the section, you can either:
• Unassign one of the facets from the section.
• Update the template used by one of the instances so that both facets
use the same version of DFB_A, page 313
.
(1) The order of facets in the section is not relevant.
(Back to
example summary table, page 310 .)
Example 1c: Two Different Versions of the Same Type in the
Same Section
A section contains two facets that are generated and one of them is updated to use a different version of the type.
The starting point is the following:
• Two facets of two different instances are assigned to Section_1.
• Both facets encapsulate the same version of DFB_A.
Facet ID (1) DFB_A version encapsulated in facet v1.0
Facet assignment/ generation status
Facet_0
Facet_1
Assigned/Generated v1.0
(1) The order of facets in the section is not relevant.
DFB_A version used in
Control project v1.0
Facet ID (1)
Facet_0
Facet_1 v2.0
v1.0
Then, the template used by instance referencing Facet_0 is updated. This results in Facet_0 encapsulating a different version of DFB_A. The section is generated again to apply the change.
The table explains the behavior during generation of Section_1 and which version of DFB_A is used in the end.
DFB_A version encapsulated in facet
Facet assignment/ generation status after generation
Out Of Date/Generated
Assigned/Generated
DFB_A version used in
Control project after generation v1.0
Comment
The software detects v2.0
while v1.0
is already generated. Because the conflict arises in the same section,
and DFB_A version v1.0
is maintained.
The status of facets is unchanged.
To be able to generate the section, you can either:
• Unassign one of the facets from the section.
• Update the template used by the instance referencing Facet_1 so that both facets
use the same version of DFB_A, page 313 .
• Unlink the already assigned and generated facet (Facet_1), generate the section, select
Update when the Global Constituent Type
Version Conflicts dialog box opens, then relink Facet_1.
(1) The order of facets in the section is not relevant.
312 EIO0000001114.15
(Back to
example summary table, page 310 .)
Example 2: Two Different Versions of the Same Type in the
Same Section
A generated facet is updated while the same section contains a non-generated facet.
The starting point is the following:
• Two facets are assigned to Section_1.
• One facet is generated, the other not.
• Both facets encapsulate DFB_A but of a different version.
Facet ID (1) DFB_A version encapsulated in facet v1.0
Facet assignment/generation status
Facet_0
Facet_1
Assigned/Generated
Assigned/Non Generated v2.0
(1) The order of facets in the section is not relevant.
DFB_A version used in
Control project v1.0
Facet ID (1)
Facet_0
Facet_1 v2.0
v2.0
Then, the template used by instance referencing Facet_0 is updated. This results in Facet_0 encapsulating the same version of DFB_A as Facet_1 ( v2.0
). The assignment status of Facet_0 is set to Out Of Date . The section is generated again to apply the change.
The table explains the behavior during generation of Section_1 and which version of DFB_A is used in the end.
DFB_A version encapsulated in facet
Facet assignment/ generation status after generation
Assigned/Generated
Assigned/Generated
DFB_A version used in
Control project after generation v2.0
Comment
The software detects v2.0
and opens the Global
Constituent Type Version Conflicts dialog box.
Update is selected. The facet is generated and the version of DFB_A used in the logical Control project is updated from v1.0
to v2.0
.
(1) The order of facets in the section is not relevant.
NOTE: If you select Skip instead, none of the facets in Section_1 are generated and the version of DFB_A in the logical Control project remains v1.0
.
(Back to
example summary table, page 310 .)
Example 3: Two Different Versions of the Same Type in Different
Sections of a Control Project
This example illustrates the behavior during generation when facets encapsulating two different versions of the same type are assigned to various sections.
The starting point is the following:
• Four facets of four different instances are assigned to separate sections.
• Each facet encapsulates DFB_A.
• All sections are part of the same Control project and generated.
Facet ID DFB_A version used in Control project v1.0
Facet_0
Facet_1
DFB_A version encapsulated in facet v1.0
v1.0
Section ID (1)
Section_0
Section_1
EIO0000001114.15
313
Facet ID DFB_A version encapsulated in facet
Section ID (1)
Facet_2
Facet_3 v1.0
Section_2
Section_3 v1.0
– No facet assigned Section_4
(1) The order of the sections corresponds to the section number.
DFB_A version used in Control project
Then, the following changes are performed:
• The template used by one instance is updated. As a result, one facet encapsulates DFB_A of a different version and its status is set to Out Of
Date .
• A new facet, Facet_4, is assigned to Section_4. It encapsulates version v1.0
of DFB_A and its statuses are Assigned / Non Generated .
The Control project is generated again to apply the changes.
The table explains the behavior during generation of the Control project and which version of DFB_A is used in the end.
Facet ID DFB_A version encapsulated in facet
Section ID (1) DFB_A version used in Control project after facet generation v1.0
Comment
Facet_0 v1.0
Section_0 No change to be generated for the facet.
Facet_1
Facet_2
Facet_3 v2.0
v1.0
v1.0
Section_1
Section_2
Section_3 v2.0
(2) The software detects v2.0
and opens the Global
Constituent Type Version Conflicts dialog box.
Update is selected. The facet is generated and the version of DFB_A used in the logical Control project is updated from v1.0
to v2.0
.
Because v1.0
has already been detected, the previously selected Update command is applied automatically and
DFB_A version v2.0
is maintained.
Facet_4 v1.0
Section_4 Facet_4 is not generated; its statuses remain Assigned /
Non Generated .
NOTE: If the assignment status of Facet_2 or Facet_3 is Out Of Date , its generation status is set to
Inconsistent .
(1) The order of the sections corresponds to the section number.
(2) Version of DFB_A that is used in the end after successful generation of the Control project.
(Back to
example summary table, page 310 .)
Example 4: Several Different Versions of the Same Type in
Different Sections of a Control Project
This example illustrates the behavior during generation when facets encapsulating different versions of the same type are assigned to the various sections.
The starting point is the following:
• Four facets of four different instances are assigned to separate sections.
• Each facet encapsulates DFB_A.
• All sections are part of the same Control project and generated.
314 EIO0000001114.15
Facet ID DFB_A version encapsulated in facet
Section ID (1)
Facet_0
Facet_1
Facet_2
Facet_3 v1.0
v1.0
v1.0
v1.0
Section_0
Section_1
Section_2
Section_3
(1) The order of the sections corresponds to the section number.
DFB_A version used in Control project v1.0
Then, the template used by some instances is updated with various versions. As a result, the facets encapsulate various versions of DFB_A and their status is set to
Out Of Date . The Control project is generated again to apply the changes.
The table explains the behavior during generation of the Control project and which version of DFB_A is used in the end.
Facet ID
Facet_0
Facet_1
Facet_2
DFB_A version encapsulated in facet v1.0
v3.0
v1.0
Section ID
Section_0
Section_1
Section_2
(1) DFB_A version used in Control project after facet generation v1.0
v3.0
Comment
No change to be generated for the facet.
The software detects v3.0
and opens the Global
Constituent Type Version Conflicts dialog box.
Update is selected. The facet is generated and the version of DFB_A used in the logical Control project is updated from v1.0
to v3.0
.
Because v1.0
has already been detected, the previously selected Update command is applied automatically and
DFB_A version v3.0
is maintained.
NOTE: If the assignment status of the facet is Out Of
Date , its generation status is set to Inconsistent .
Facet_3 v4.0
Section_3 v4.0
(2) The software detects v4.0
and opens the Global
Constituent Type Version Conflicts dialog box.
Update is selected. The facet is generated and the version of DFB_A used in the logical Control project is updated from v3.0
to v4.0
.
(1) The order of the sections corresponds to the section number.
(2) Version of DFB_A that is used in the end after successful generation of the Control project.
NOTE: It is possible to update the version of a type to an earlier one. For example, if Facet_3 would encapsulate DFB_A of version v2.0
, the version used in the end would be v2.0
.
(Back to
example summary table, page 310 .)
Example 5: Two Different Versions of the Same Type in Different
Sections of a Control Project
This example illustrates the behavior during generation when facets encapsulating two different versions of the same type are assigned to various sections and the
Skip command is used.
The starting point is the following:
• Four facets of four different instances are assigned to separate sections.
• Each facet encapsulates DFB_A.
• All sections are part of the same Control project and generated.
Facet ID DFB_A version used in Control project v1.0
Facet_0
Facet_1
Facet_2
DFB_A version encapsulated in facet v1.0
v1.0
v1.0
Section ID (1)
Section_0
Section_1
Section_2
EIO0000001114.15
315
Facet ID DFB_A version encapsulated in facet
Section ID (1)
Facet_3 v1.0
Section_3
(1) The order of the sections corresponds to the section number.
DFB_A version used in Control project
Then, the template used by two instances is updated. As a result, two facets encapsulate DFB_A of a different version and their status is set to Out Of Date .
The Control project is generated again to apply the changes.
The table explains the behavior during generation of the Control project and which version of DFB_A is used in the end.
Facet ID DFB_A version encapsulated in facet
Section ID (1) DFB_A version used in Control project after facet generation v1.0
(2)
Comment
Facet_0
Facet_1 v1.0
v2.0
Section_0
Section_1
No change to be generated for the facet.
The software detects v2.0
and opens the Global
Constituent Type Version Conflicts dialog box.
Skip is selected. The facet is not generated and the version of
DFB_A used in the logical Control project remains v1.0
.
Facet_2
Facet_3 v1.0
v2.0
Section_2
Section_3
No change to be generated for the facet.
Because v2.0
has already been detected, the previously selected Skip command is applied automatically. The facet is not generated and DFB_A version v1.0
is maintained.
(1) The order of the sections corresponds to the section number.
(2) Version of DFB_A that is used in the end after successful generation of the Control project.
NOTE: The assignment status of Facet_1 and Facet_3 remains Out Of Date .
(Back to
example summary table, page 310 .)
Example 6: Several Different Versions of the Same Type in
Different Sections of a Control Project
This example illustrates the behavior during generation when facets encapsulating different versions of the same type are assigned to the various sections and the
Skip command is used.
The starting point is the following:
• Four facets of four different instances are assigned to separate sections.
• Each facet encapsulates DFB_A.
• All sections are part of the same Control project and generated.
Facet ID
Facet_0
Facet_1
Facet_2
Facet_3
DFB_A version encapsulated in facet v1.0
v1.0
v1.0
v1.0
Section ID
Section_0
Section_1
Section_2
Section_3
(1)
(1) The order of the sections corresponds to the section number.
DFB_A version used in Control project v1.0
Then, the template used by some instances is updated with various versions. As a result, the facets encapsulate various versions of DFB_A and their status is set to
Out Of Date . The Control project is generated again to apply the changes.
The table explains the behavior during generation of the Control project and which version of DFB_A is used in the end.
316 EIO0000001114.15
Facet ID DFB_A version encapsulated in facet
Section ID (1) DFB_A version used in Control project after facet generation v1.0
(2)
Comment
Facet_0
Facet_1
Facet_2 v1.0
v2.0
v4.0
Section_0
Section_1
Section_2
No change to be generated for the facet.
The software detects v2.0
and opens the Global
Constituent Type Version Conflicts dialog box.
Skip is selected. The facet is not generated and the version of
DFB_A used in the logical Control project remains v1.0
.
The software detects v4.0
and opens the Global
Constituent Type Version Conflicts dialog box.
Skip is selected. The facet is not generated and the version of
DFB_A used in the logical Control project remains v1.0
.
Facet_3 v2.0
Section_3 Because version v2.0
has already been detected (for
Facet_1), the previously selected Skip command is applied automatically. The facet is not generated and the version of
DFB_A used in the logical Control project remains v1.0
.
(1) The order of the sections corresponds to the section number.
(2) Version of DFB_A that is used in the end after successful generation of the Control project.
NOTE: The assignment status of Facet_1, Facet_2, and Facet_3 remains Out
Of Date .
(Back to
example summary table, page 310 .)
Example 7: Several Different Versions of the Same Type in
Different Sections of a Control Project
This example illustrates the behavior during generation when facets encapsulating different versions of the same type are assigned to the various sections and the
Update and Skip commands are used.
The starting point is the following:
• Six facets of six different instances are assigned to separate sections.
• Each facet encapsulates DFB_A.
• All sections are part of the same Control project and generated.
Facet ID
Facet_0
Facet_1
Facet_2
Facet_3
DFB_A version encapsulated in facet v1.0
v1.0
v1.0
v1.0
Section ID
Section_0
Section_1
Section_2
Section_3
(1)
Facet_4
Facet_5 v1.0
v1.0
Section_4
Section_5
(1) The order of the sections corresponds to the section number.
DFB_A version used in Control project v1.0
Then, the template used by the instances is updated with various versions. As a result, the facets encapsulate various versions of DFB_A and their status is set to
Out Of Date . The Control project is generated again to apply the changes.
The table explains the behavior during generation of the Control project and which version of DFB_A is used in the end.
EIO0000001114.15
317
Facet ID DFB_A version encapsulated in facet
Section ID (1) DFB_A version used in Control project after facet generation v4.0
Comment
Facet_0
Facet_1
Facet_2
Facet_3
Facet_4 v4.0
v2.0
v1.0
v4.0
v2.0
Section_0
Section_1
Section_2
Section_3
Section_4 v4.0
(2)
The software detects v4.0
and opens the Global
Constituent Type Version Conflicts dialog box.
Update is selected. The facet is generated and the version of DFB_A used in the logical Control project is updated from v1.0
to v4.0
.
The software detects v2.0
and opens the Global
Constituent Type Version Conflicts dialog box.
Skip is selected. The facet is not generated and version v4.0
of
DFB_A is maintained.
NOTE: The generation status of the facet is set to
Inconsistent because the version of DFB_A has been previously updated when generating Facet_0.
Because version v1.0
has already been detected when generating Facet_0, the previously selected Update command is applied automatically and DFB_A version v4.0
is maintained.
NOTE: If the assignment status of the facet is Out Of
Date , its generation status is set to Inconsistent .
The facet is generated but without the detection of a version change because the version of DFB_A used in the Control project is already v4.0
due to the update when generating
Facet_0.
The previously selected Skip command (for Facet_1) is applied automatically. The facet is not generated and DFB_
A version v4.0
is maintained.
NOTE: The generation status of the facet is set to
Inconsistent because the version of DFB_A has been previously updated when generating Facet_0.
Facet_5 v3.0
Section_5 The software detects v3.0
for the first time and therefore opens the Global Constituent Type Version Conflicts dialog box.
Skip is selected. The facet is not generated and the version of DFB_A used in the logical Control project remains v4.0
.
NOTE: The generation status of the facet is set to
Inconsistent because the version of DFB_A has been previously updated when generating Facet_0.
(1) The order of the sections corresponds to the section number.
(2) Version of DFB_A that is used in the end after successful generation of the Control project.
(Back to
example summary table, page 310 .)
Example 8: Two Different Versions of the Same Type in Different
Sections
This example illustrates the behavior during generation when facets encapsulating different versions of the same type are assigned to the different sections and the
Cancel and Update commands are used.
The starting point is the following:
• Two facets of two different instances are assigned to one section each.
• Each facet encapsulates DFB_A.
• Facets are not yet generated.
Facet ID (1) DFB_A version encapsulated in facet
Section ID
Facet_0
Facet_1 v1.0
v2.0
Section_1
Section_2
(1) The order of the facet in the section corresponds to the facet number.
DFB_A version used in Control project
None
Then, the Control project is generated.
318 EIO0000001114.15
The table explains the behavior during generation of the Control project and which version of DFB_A is used in the end.
Facet ID DFB_A version encapsulated in facet
Section ID DFB_A version used in
Control project after generation
1.0
Comment
Facet_0 v1.0
Section_1 Version v1.0
of DFB_A is generated in the logical Control project.
Facet_1 v2.0
Section_2 1.0
(1) The software detects v2.0
and opens the Global Constituent Type Version
Conflicts dialog box.
Cancel is selected. Generation stops. The facet is not generated and the version of DFB_A used in the logical Control project remains v1.0
.
(1) Version of DFB_A that is used in the end after successful generation of the section.
Then, the Control project is generated a second time.
Facet ID DFB_A version encapsulated in facet
Section ID DFB_A version used in
Control project after generation
1.0
Comment
Facet_0 v1.0
Section_1 No change to be generated for the facet.
Facet_1 v2.0
Section_2 2.0
(1) The software detects v2.0
and opens the Global Constituent Type Version
Conflicts dialog box.
Update is selected. The facet is generated and the version of DFB_A used in the logical
Control project is updated from v1.0
to v2.0
.
(1) Version of DFB_A that is used in the end after successful generation of the section.
NOTE: After the second generation, if you regenerate:
• The entire Control project: A version conflict is detected in Section_2 like during a first generation because type DFB_A is removed from the
Control before regenerating.
• Section_1: A version conflict is detected because the version of DFB_A in the Control project ( v2.0
) is different from the version encapsulated in
Facet_0 ( v1.0
).
• Section_2: No version conflict is detected.
(Back to
example summary table, page 310 .)
Statuses of Facets
EIO0000001114.15
Overview
After the generation process, the generation and assignment statuses of facets provide information on the facet state.
NOTE: For information on the behavior when generating such facets again, refer to the topic describing the
generation of facets after changes, page 323
.
Generation Status of Facets
The generation status indicates the status of the facet in relation to the generation of its constituents in the logical Participant project.
319
320
You can see the generation status in the Generation column of the Assignments
in the Assignment Editor .
The table describes the possible generation statuses of facets following a generation.
Status Description
Non
Generated
You have assigned the facet to the FBD section or container after generating that section/container.
the section/container again to create the constituents of the facet in the logical Participant project.
It can also indicate that the generation process of a facet or its container was unsuccessful.
Generated The software has successfully generated the constituents of the facet into the logical participant project.
NOTE: The software automatically sets the status of Supervision genie facets that you assign to a page during page edit to Generated .
Moved
Inconsistent
Unlinked
You have
the facet to another FBD section of the Control project or another container of the Supervision.
NOTE:
• If you move the facet back to its original FBD section or container, it keeps the status Moved .
• The status does not apply to genie facets.
You have refined, updated, or imported the logical Control Participant project, or relinked a facet, which was unlinked and the software has detected an inconsistency in the facet during the
• You have not yet generated the section containing the facet again in order for the software to
resolve the inconsistency, page 325
and change the status, or
• The software could not solve the inconsistency during a subsequent generation and the status of the facet remains Inconsistent .
NOTE: By default, the status of Supervision genie and data facets changes to
Inconsistent when you
them.
NOTE: This status can also be the result of a type version conflict that the software detected during
generation of Control facets, page 305
.
You have unlinked the facet from its already generated constituents in the logical
Participant project:
• By using the
command.
• By unlinking the facet through the Check Consistency dialog box:
◦ After
refining a Control Participant project, page 336 .
◦ Before
updating a Control Participant project, page 573
.
By unlinking a facet, the software does not change already generated constituents when you generate it again if the status the facet is such that a generation would change its status (for example, if the status of the facet is out of date or inconsistent, generating it would change its status to generated). This allows you to preserve changes that you have made in the logical Participant project to constituents of the facet through refinement or refinement online.
Assignment Status of Generated Facets
The assignment status indicates the status of the facet in relation to the instance that references the facet.
The software may update the Assignment status of the facet when you change the properties of the instance that references the facet.
You can see the assignment status in the Assignment column of the
Assignments
in the Assignment Editor .
The table describes the possible assignment statuses of a facet following a generation.
Status Description
Assigned The facet is assigned to the container.
Unassigned
You have
had assigned it.
a generated facet from the container to which you
NOTE: The facet can still be assigned to other projects of the system.
EIO0000001114.15
Status
Out Of
Date
Deleted
Description
You have changed at least 1 of the following parameter configurations of the instance that references the facet:
• $System parameters (see EcoStruxure ™ Process Expert, Global Templates,
Reference Manual) that affect the facet.
• Element selections and their parameters.
• Instance identifier (including changes made by the software in relation to the hierarchical naming function).
• Links.
• Updated or replaced the template that is used by the instance.
• Other changes made within the application to an instance and that affect its facet.
Furthermore, for Supervision data facets only, you have changed any of the following in the Supervision project:
• The identifier of the cluster or I/O device.
• The identifier of the tag container if Protocol is set to OPCUA .
• The relationship between the tag container and the I/O device.
• The protocol of the tag container.
•
The application structure, page 156
(in the Application Explorer ).
You have unselected the corresponding element in the Instance Editor or deleted the instance that references the facet.
Generating a Project for the First Time
Overview
This section describes how to use the Project Explorer to create a logical Control or Supervision Participant project or part of a project for the first time.
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
Generating Entire Projects
Overview
The generation of the entire project for the first time encompasses:
• For a Control project: The FBD sections of the project and the facets that are assigned to these sections.
• For a Supervision project: The various containers of the clusters of the project to which facets are assigned and any associated components of the Services node.
The status of facets is updated only after the entire generation process is completed.
NOTE: You can generate a project while the generation of another project is still ongoing.
Aborting Project Generation Tasks
After selecting the Generate command, the abort icon is displayed in the
. Click the icon to cancel the task. The project is not generated; what the software had already generated at the time you canceled the task is reverted.
Refer to the notification panel for details.
Only the user who has selected the command is allowed to abort it.
EIO0000001114.15
321
NOTE: If you are generating a small project, the task may complete before you are able to click the icon.
Generating an Entire Project
To generate an entire Participant project, proceed as follows.
Step
1
Action
In the project browser or the Containers pane of the Assignment Editor , right-click the project that you want to generate and select Generate .
Result:
• The software creates the corresponding logical Participant project. Generation is complete when Completed is displayed for the process in the notification panel.
• The status of the Generation column in the Assignments pane changes to
Generated for facets that are assigned to the project.
NOTE: If you are generating the project again, the
of facets that were Unlinked remains unchanged and those that were Inconsistent may remain unchanged.
NOTE: For Control projects, you can configure certain
generation settings, page 304 .
Generating Sections, Containers, and Nodes
Overview
The generation of parts of a project for the first time encompasses:
• For an FBD section of a Control project: The facets that are assigned to the section and the order of the section.
• For a Supervision project:
◦ For the Containers node: The containers of all the clusters of the project.
◦ For tag containers, pages, client and sever event containers: The facets that are assigned to the respective container.
◦ For the Tags containers: The facets that are assigned to the containers of the corresponding cluster.
◦ For a cluster: The containers of the Tags , ClientEvents , and
ServerEvents nodes of the cluster and any components of the Services node.
◦ For the Services node: The components of the node.
NOTE: You can generate several sections or containers of the same project at the same time but the generation process will occur in sequence. If the sections/containers belong to different projects, they are generated in parallel.
Aborting Generation Tasks
After selecting the Generate command, the abort icon is displayed in the
. Click the icon to cancel the task. The container of the
Participant project is not generated; what the software had already generated at the time you canceled the task is reverted.
Refer to the notification panel for details.
Only the user who has selected the command is allowed to abort it.
NOTE: If you are generating a container to which only few facets are assigned, the task may complete before you are able to click the icon.
Generating Part of a Project
To generate part of a project, proceed as follows.
322 EIO0000001114.15
Step
1
Action
In the project browser or in the Containers pane of the Assignment Editor , right-click the item that you want to generate and select Generate .
Result:
• The software generates the contents of the selected item. Generation is complete when Completed is displayed for the process in the notification panel.
• The status of the Generation column in the Assignments pane changes to
Generated for the facets that are assigned to the selected containers.
NOTE: If you are generating this part of the project again, the
of facets that were Unlinked remains unchanged and those that were
Inconsistent may remain unchanged.
NOTE: For Control projects, you can configure certain
.
Generating Projects After Changes
Overview
This section describes how to use the Project Explorer to perform a subsequent generation or to regenerate entire logical Control or Supervision Participant projects, or parts of such projects.
You may be able to
import into the deployed Control Participant project, page 558
sections that you have generated or regenerated after modifying them.
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
Generating Participant Projects After Changes
Overview
You need to generate the logical Participant project that you have created with the first-time generation when you make changes that result in facets having one of the following statuses:
• Assignment status:
◦ Unassigned
◦ Out Of Date
◦ Deleted
• Generation status:
◦ Non Generated
◦ Moved
◦ Inconsistent
You also need to generate it when you perform the following actions on sections of a Control project in the Project Explorer :
• Rename a section.
• Create an FBD section.
• Change the order of sections.
To update the logical Participant project, use one of the following commands:
EIO0000001114.15
323
324
Generate
Regenerate
Only changes that you made to the application and the project since the last generation are generated incrementally into the logical Participant project. Already generated data remains unchanged. However, certain changes that you made during refinement may be discarded.
Applies to
Control projects only, page 327 . Re-creates the logical
Participant project from the beginning based on the current application and Control project settings. Certain changes that you made during refinement are discarded. You can configure certain
.
The software proceeds with the
like it does when generating.
NOTE: To apply to the logical Control project changes that you have made to sections, you can also select the Refine
at the project level.
Generation Function Description
The table indicates the actions that the software executes on facets when you perform a subsequent generation of a project or parts of it, based on the
Assignment and Generation status of the facet.
Facet generation status
Facet assignment status
Assigned
Non
Generated
Generated Moved Inconsistent
Out Of Date
Unassigned
X
–
–
O (1)
X
Del
X
X
–
Deleted – Del –
X Creates the constituent of the facet in the logical Participant project
X
X
Del
Del
Unlinked
O
O
–
–
O No action
Del Removes the facet and its already generated constituents (for example, variables and FB instances) but not derived types (DFBs and DDTs)
– Combination not applicable
(1) Some exceptions apply. Refer to the topic describing the generation of Control projects after refining
NOTE: When you change the order of a facet inside a section that you had generated a first time and generate it again, the software does not propagate the new
to the logical Control Participant project.
Generating Control Projects After Changing the Order of
Sections
When you
of already generated sections and generate again either the entire Control project or a section whose order you have changed, the software propagates the new order to the logical Control Participant project.
NOTE: Generating at the project level may take slightly longer to complete compared to generating at the section level.
Generating Control Projects After Refining
If during refinement you have modified code in a section that was already generated by the software from a facet (for example, you have modified the variable or immediate value on a pin of a DFB), the software reverts your change when you generate the section again if any of the following conditions is true; otherwise your modification is preserved:
EIO0000001114.15
• You assign a facet to this section.
• You unassign a facet in this section.
• You move a facet to or from this section.
• You make a modification, which sets the status of any facet assigned to this section to Out Of Date .
• You perform a consistency check, which sets the status of any facet assigned to this section to Inconsistent .
Your modification is reverted to the code that the software had previously generated from the facet.
If your modification consists in replacing a variable or immediate value on the pin of an FFB by a graphical link, such modification is not reverted by a subsequent generation. If the change is detected as an inconsistency, the generation status of the corresponding facet is set to Inconsistent .
In this example, the immediate value of the ZSHEN input parameter of the
DEVCTL DFB is changed to True during refinement and saved. Section Motor_1_
Motor that contains the facet, which generates the DFB ( Motor_1_DEVCTL ) contains only facets with the Assigned and Generated status. No other changes were made in the Control project. Generating section Motor_1_Motor does not undo your refinement; the immediate value of the ZSHEN input parameter remains True .
However, if section Motor_1_Motor contains, for example, a facet with status Out
Of Date , generating the section undoes the refinement change, setting the
ZSHEN input parameter again to False .
EIO0000001114.15
Generating Supervision Projects After Refining
Generating a Supervision project overrides any changes that you have made in refinement to elements pertaining to the
of the project.
Generating Inconsistent Facets
During generation, the software attempts to restore the generated constituents of facets in the logical Control Participant project that have the Generation status
Inconsistent to be consistent with the related facets of the Control project.
The resulting Generation status of an inconsistent facet can be:
325
326
• Generated : The software completely restored the generated constituents while preserving the refinement that you have made.
• Inconsistent : The software was not able to restore the generated constituents completely because it would require altering the refinement that you have made. The software may have partially restored the constituents and the refinement that you have made was preserved.
This is the case, for example, if during refinement of an FBD section, you replace a variable by a graphical link and such change is detected as an inconsistency. Indeed, the software retains your refinement if you generate the section. Your refinement is discarded if you regenerate the section.
Generating Facets with State Invalid
If the
has become Invalid after you generated it, generating the container or Participant project again does not remove the facet from the container.
This can be the case, for example, when you link instances A and B (where instance A needs to be linked to be valid), assign their facets to a Control project, generate the section, and then delete the link between the two instances. The facet of instance A becomes invalid because the instance is not linked anymore.
You need to either
the section to which the invalid facet is assigned or unassign the facet and generate to remove it from the section.
Function Block Layout
When you generate Control projects or sections again, the software positions function blocks that are encapsulated in facets depending on their status:
• Facets that you had already generated and that have the following status:
◦ Out Of Date : Facets creating a new function block after a change in their properties. The function block is positioned according to the layout defined by the template referencing the facet.
◦ Inconsistent : Function blocks encapsulated in the facet are recreated and positioned in their previously generated position.
For both facets, if the position of the function block is already occupied, the block is moved to the end of the section content (Y axis), keeping its horizontal position (X axis) as defined by the layout of the template referencing the facet.
• Non Generated facets:
◦ Single facets created through an element selection and that you have assigned to the section after generating it: Function blocks encapsulated in the facet are positioned at the end of the section content, on the outer left.
◦ Facets referenced by an instance of which no facets were previously assigned: Function blocks encapsulated in the facets are positioned at the end of the section content while respecting the layout as defined by the template that the instance uses.
This requires that the generation of the corresponding facets completes successfully and that the resulting facet status is Generated .
The software manages
as needed.
For more information, refer to Section Layout Management Example (see
EcoStruxure ™ Process Expert, Control Participant Services, User Guide).
NOTE: To keep the constituents that are generated for an instance grouped, assign all its facets at once.
NOTE: Certain
configurable generation settings, page 304
can affect the position of function blocks.
EIO0000001114.15
Generating a Project Again
Refer to the procedure describing how to generate:
• The
•
Regenerating a Control Project
Control Project Regeneration Description
This process recreates the logical Control Participant project from the beginning based on the current settings:
• Section execution order.
• Facet execution order inside the section.
• Properties of assigned facets.
The following changes made during
are discarded by the regeneration process:
• Any changes to the contents of sections to which facets are assigned.
• Any contents added to such sections.
• If you set the ReGenerateNonFbdSections parameter to false :
◦ Non-FBD sections that you have added during refinement and their contents.
◦ Name changes of FBD sections that are created by the generation process.
◦ FBD sections that you have added during refinement, their contents and any facets that you have assigned to these sections.
You can regenerate the entire Control project or FBD sections individually.
If the software was not able to regenerate a Control project or FBD sections of it, the
can vary.
Types Removed When Regenerating
The following derived types (DFBs and DDTs) are removed from the logical
Control project when you regenerate it:
• Types that were generated from facets that you have unassigned from a project section or whose instance has been deleted.
• Types that remained after deleting the section that contained the facet that generated them.
NOTE: In both cases, such types are not removed when you:
• Regenerate only a section of a Control project.
• Generate the Control project.
Actions on Facets
The table indicates the actions that the software performs on facets when you regenerate a Control project or FBD section, based on the Assignment and
Generation status of the facet.
Facet generation status
Non Generated Generated Moved Inconsistent Unlinked Facet assignment status
Assigned
Out Of Date
X
–
X
X
X
X
X
X
X
X
EIO0000001114.15
327
328
Facet generation status
– Del Unassigned –
Deleted – Del –
X Creates the constituent of the facet in the Participant project
Del Deletes the facet and its already generated constituents
– Combination not applicable
Del
Del
–
–
Control Project Section Size
The software manages
.
Execution Order and Function Block Layout
The process to regenerate the section order and section layout is the same as for a
first-time generation, page 303 , independently of the facet status.
Regenerating Control Projects Containing Non-FBD Sections
When you regenerate a Control project that contains non-FBD sections, a message appears in the notification panel for each one of them informing you that the section was generated because of an order change. This message, which is related to an internal process, appears even if the position of these sections has not changed.
An exception applies to non-FBD sections that have rank 0 ( Order column) when the Regenerate command is used. For these sections, the message does not appear whether their position has changed or not.
Aborting Regeneration of Projects And Sections
After confirming the ReGenerate command, the abort icon is displayed in the
. Click the icon to cancel the task. The Control project or section is not regenerated; what the software had already regenerated at the moment you canceled the task is reverted.
Refer to the notification panel for details.
Only the user who has selected the command is allowed to abort it.
NOTE: If you are regenerating a small project or section, the task may complete before you are able to click the icon.
Regenerating the Entire Control Project
To recreate the entire logical Control Participant project, proceed as follows.
Step
1
2
Action
Configure generation settings, page 304
as needed.
In the project browser or the Containers pane of the Assignment Editor , right-click the
Control project that you want to regenerate and select ReGenerate .
Result:
• The software re-creates the logical Control Participant project. Regeneration is complete when Completed is displayed for the process in the notification panel.
• The status of the Generation column in the Assignments pane changes to
Generated for the facets that are assigned to the project.
EIO0000001114.15
Regenerating an FBD Section Only
The regeneration at the FBD section level allows you to recreate the Control
Participant logic for the facets contained in the selected FBD section only.
To regenerate the logic of an FBD section, proceed as follows.
Step
1
Action
In the Containers pane of the Assignment Editor , right-click the section that you want to regenerate and select ReGenerate .
Result:
• The software re-creates the Control Participant logic of the selected section only.
Regeneration is complete when Completed is displayed for the process in the notification panel.
• The status of the Generation column in the Assignments pane changes to
Generated for the facets that are assigned to the selected FBD section.
Facet Status After Unsuccessful Regeneration
The table describes the effect on the status of Control facets when the regeneration of a section is not successful.
Regenerated project component
Entire Control project
Control project section
Facet status
The generation status of facets assigned to
sections that are not regenerated, page 301
reverts to the value it was before regenerating.
The generation status of facets assigned to this section reverts to the value it was before regenerating.
Generating Equipment in Supervision Projects
Generating Equipment Based on the Application
Overview
By default, generating a Supervision project populates the equipment table of the
Supervision project based on the
structure of the application, page 116
. Each instance of the application creates one equipment instance. This allows you to view alarms during runtime in a structure identical to the hierarchy of the application.
To create equipment names, the software may truncate the identifier of folders and instances to comply with the format of the name field of the equipment database file.
Changes to the structure, page 156
of the application are reflected on generated facets of the project allowing you to update the equipment database file by generating the project again.
NOTE: To view the equipment name that is generated, refine the Supervision project and open the equipment table.
Properties of the Equipment Table
The generation process populates the following properties of the equipment table of the Supervision project.
EIO0000001114.15
329
330
Field
Name
Description
Instance identifier with its path in the application, satisfying the equipment naming rules for the name field (1) . The folder and instance identifiers are dot-separated.
NOTE: The system root folder identifier is not included in the name.
Cluster Identifier of the cluster of the Supervision project to which facets of the instance are associated.
$Description parameter of the instance.
Comment
Area $Area parameter of the instance.
(1) The Supervision Participant does not accept the use of certain reserved words for item names
(for example, DO ). While the software allows using these reserved words as identifiers of instances in the application, doing so prevents the Supervision project from generating successfully because the reserved word becomes the equipment name when the instance is created in the system root folder. For details on the reserved words, look up Reserved Words in the
.
NOTE: You can use the Equipment element (see EcoStruxure ™ Process
Expert, Global Templates, Reference Manual) to populate additional properties of equipment instances without impacting the way the equipment name is generated.
Rules Applying to the Creation of Equipment Names
The software may modify and/or truncate the identifier of folders and instances according to the following rules to populate the Name property of the equipment table of the Supervision project.
Item
Folder levels
Instance path
Rule
7 folders maximum not including the system root folder
125 characters maximum including the instance identifier and dot separators
Folder identifier length
12 characters maximum (1)
Instance identifier length
18 characters maximum (1)
Comment
–
–
–
Identifiers of folders
Can only begin with a letter.
Can only contain alphanumerical characters and underscores ( _ ).
No spaces.
By default, the identifiers of instances of
Schneider Electric templates are limited to 18 characters.
Examples :
$Folder1 and Folder$1 are modified to
Folder1 (or Folder100 if Folder1 already exists)
Folder 2 is modified to Folder2
(1) The software may add an indexer consisting of two digits at the end of identifiers so that the name of each folder having the same parent folder and the name of each instance inside a folder remain unique.
For more information on not allowed characters, refer to the topic describing
NOTE: If the software truncates the instance identifier or path to satisfy the equipment name creation rules, it displays a notification once the generation process is completed.
NOTE: The software does not change the identifier of folders and instances in the application.
Example 1 - Folder Identifier Exceeds Length
If in the Application Explorer , the following instance exists:
• Conveyor_Motor_1
• At path (folder identifiers): System_1\PlantNorthFace\Unit 20
EIO0000001114.15
The generated equipment name is: PlantNorthFa.Unit20.Conveyor_Motor_1
Example 2 - Indexing the Truncated Folder Identifier
If in the Application Explorer , the following two instances exist in two distinct folders:
• Instance_1 at the path System_1\Folder_12345_1 (the application folder name has 14 characters)
• Instance_2 at the path System_1\Folder_12345
The generated equipment names are:
• Folder_1234500.Instance_1
• Folder_12345.Instance_2
Example 3 - Number of Folders Exceeds Limit
If in the Application Explorer , the following instance exists:
• Motor_1
• At path (folder identifiers): System_1\F1\F2\F3\F4\F5\F6\F7\F8\F9
The generated equipment name is: F1.F2.F3.F4.F5.F6.F7.Motor_1
Generation Diagnostic Messages
Generation Diagnostic Messages
Overview
The following tables describe some of the messages that the software displays when applicable rules are not satisfied during the generation of Control and
Supervision projects and propose corrective actions.
In these messages and others,
that are generated by the
Control Participant may be displayed. These notifications provide more detailed information about the reason for which the generation process did not complete successfully.
For Control Projects
Message details
Section is overcrowded
Variable name conflict
Cause
The section cannot accept as many function blocks as the software is trying to
.
Also, you may have changed the position of DFBs during refinement so that the software cannot adapt the size of the section to accommodate the function blocks.
A facet is generating a variable that has the same name as an already existing variable in the project.
Corrective action
Do the following to free up space:
• Move or unassign facets from the FBD section.
• Change the layout of the function blocks inside the section.
• Verify whether a comment box is preventing the software from
adapting the size of the section, page 302
.
Then, generate the project/section again
NOTE: When you move DFBs inside a section, use either method:
• Position DFBs tightly together to use the full width of the grid effectively, leaving empty rows at the bottom of the section.
• Position DFBs to use the entire height of the grid, leaving empty columns on the right side of the section.
• You can
change the section size, page 304
by regenerating it.
You can do either of the following:
• Change the instance
so that the facet creates a variable with a different name. Then, generate the project again.
• If you had already generated the project, refine the project and rename or remove the existing variable. Then, generate the project again.
EIO0000001114.15
331
Message details
Version conflict in the same section
Invalid characters
Cause
The software is trying to generate, within the same section, a version of a DDT and/or DFB that is different from the version that already exists in the Control project.
You may have
updated the template used by an instance, page 166 .
The name of a generated constituent contains a character that is invalid for use with the Control Participant.
Corrective action
•
Regenerate the Control project, page 327
in order to remove the existing variable (for example, if you had created the variable during refinement).
You can do either of the following:
• Update the template used by instances whose facets are assigned to the section so that only one version of the same type is generated.
• Remove the type from the project if it is not used anymore.
• Assign the facet that is generating the new version of the type to another section.
Generate the project again.
For details, refer to the topic describing the
management of type versions in Control facets during generation, page 305 .
Edit the properties of the instance referencing the facet that is mentioned in the message details so that resulting variable names and section identifiers satisfy the
, and generate the project again.
For Supervision Projects
Detected error
Unique equipment name cannot be generated.
Indexer used for uniqueness has reached 99
(maximum limit).
Cause
The number of non-unique truncated folder and instance identifiers during generation exceeds 99.
Corrective action
Change the folder structure of the application or instance identifiers to reduce the number of non-unique identifiers that the software creates through
Managing Generated Facets
Managing Generated Facets
Overview
Following the generation of the Control or Supervision project, or parts of it, you can execute commands and actions on generated facets from the Assignments pane of the Assignment Editor .
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
Generated Facets Actions
The table outlines the commands and actions that you can execute on generated facets.
332 EIO0000001114.15
EIO0000001114.15
Command or action
Unassign
Unlink
Reassign
Relink
Go To Instance
Move
Description
You can unassign facets that have the following Assignment status:
• Assigned
• Out Of Date
If you unassign a Control facet that has the generation status of Unlinked , the facet is removed from the section but the generated constituents pertaining to the facet are not deleted from the logical Control Participant project. If you assign this facet again to the same project, you may receive a notification about a
variable name conflict, page 331
.
The status UnAssigned is described in
Assignment Status of Generated
.
Refer to
Unassigning Generated Facets, page 334 .
NOTE: The actions that the software executes when you select the
Unassign command for a generated facet or a
facet that is not yet generated, page 293
are different.
Refer to
Unlinking Generated Facets, page 334
.
NOTE: The status Unlinked is described in
Generation Status of Facets, page 319 .
You can reassign generated facets that have the status UnAssigned .
The Reassign command assigns a facet to the container in which it is located, allowing you to:
• Apply to the facet changes to the instance that references it.
• Generate its constituents into the logical Participant project.
The software performs a
when available.
When the consistency check is not available, the generation status of facets changes to Inconsistent . This is the case, for example, for Supervision genie and data facets.
Reassigning a facet changes its status to Assigned .
Refer to
.
You can relink generated facets that have the status Unlinked .
The Relink command links a facet again to its already generated constituents, allowing you to:
• Apply to the logical Participant project changes of the facet using the
Generate command.
• Detect inconsistencies by performing a consistency check.
When you relink a facet, the software performs a consistency check if the functionality is available for the facet. Depending on the result, it changes the generation status of the facet to either:
• Generated if it detects no inconsistency.
• Inconsistent if it detects an inconsistency.
When the consistency check is not available, the generation status of facets changes to Inconsistent . This is the case, for example, for Supervision genie and data facets.
Refer to
Allows you to go to the instance that references the facet.
The navigation feature is not available if the Assignment status of the facet is
Deleted .
Refer to
Navigating From Facets to Instance, page 296
.
Refer to
Moving Generated Facets, page 335 .
NOTE: The status Moved is described in
Generation Status of Facets, page 319 .
NOTE: For a description of the effect of a subsequent generation process on the facets that you have acted upon, refer to
.
333
334
Unassigning Generated Facets
To unassign a generated facet from the container to which it is assigned, proceed as follows.
Step Action
1 In the Assignments pane, right-click the facet and select Unassign .
Result :
• The software unassigns the facet from the selected container.
• Its already generated constituents (for example, variables and FB instances for
Control facets and database entries for Supervision facets) are removed from the logical Participant project (except
for Control facets).
• The status of the facet displayed in the Assignment column changes to
UnAssigned .
NOTE: You can select several facets in the same container.
Unlinking Generated Facets
To unlink a facet, proceed as follows.
Step Action
1 In the Assignments pane, right-click the facet and select Unlink .
Result :
• The software unlinks the facet from its already generated constituents.
• The status of the facet displayed in the Generation column changes to Unlinked .
NOTE: You can select several facets in the same container.
Reassigning Facets
To reassign a facet, proceed as follows.
Step Action
1 In the Assignments pane, right-click the facet and select Reassign .
Result :
• The software reassigns the facet to the same container and performs a consistency check.
• The status of the facet displayed in the Assignment column changes to Assigned or Out Of Date .
• The status of the facet displayed in the Generation column changes to
Generated or Inconsistent , page 319
.
NOTE: You can select several facets in the same container.
Relinking Facets
To relink a facet, proceed as follows.
Step Action
1 In the Assignments pane, right-click the facet and select Relink .
Result :
• The software links the facet again to its generated constituents in the logical
Participant project.
• The status of the facet displayed in the Generation column changes to
Generated or Inconsistent , page 319
.
NOTE: You can select several facets in the same container.
EIO0000001114.15
Moving Generated Facets
To move a facet from one container to another, proceed as follows.
Step Action
1 In the Assignments pane, right-click any one of the column headers and select the appropriate command to
clear filters and sorting, page 93 .
2 In the Assignments pane, drag the facet to another container in the Containers pane.
Result :
• The software removes the facet from its original location and assigns it to the target container.
• The status of the facet displayed in the Generation column changes to Moved .
NOTE: You can select several facets in the same container.
NOTE: Control facets that you move are assigned to the new section with the highest order value in the
Order column of the Assignments pane, page 282 .
If you move several facets at once, the facet that you have selected first gets the lowest order out of the ones that are moved.
NOTE: After you have moved a generated facet from one container to another,
the target container again to update the associated logical Participant project.
EIO0000001114.15
335
Refinement Stage
What’s in This Chapter
Supervision Project Refinement Stage .......................................................... 360
Overview
This chapter describes how to modify the logical Participant projects that the software has created during the generation stage to fulfill the requirements of the system.
The refinement stage is not mandatory to be able to proceed to the next stage.
The following figure shows the position of the Refinement stage within the system engineering life cycle.
Refer to
for a description of the purpose of this stage.
Control Project Refinement Stage
Refining the Logical Control Project
Overview
You can refine at the project level, which allows you to view and modify the entire logical Control project with the help of the Control Participant.
You can also refine specific sections only by launching the refinement process from a section (except for LL984 sections). The section does not need to be generated to be refined.
You can import LL984 sections (see EcoStruxure ™ Process Expert, Control
Participant Services, User Guide).
FBD and non-FBD sections that you add during refinement are displayed in the
Control project ( Assignment Editor ) in the order they appear in the Control
Participant. The contents of these sections is not displayed there however.
Once refinement is complete, you can request the software to perform a
336 EIO0000001114.15
At the refinement stage, you can also create and
manage network variables, page
350 , which are used for peer to peer communication.
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
Refining Offline With CCOTF Enabled
For M580 and M580 safety Control projects created in the Project Explorer , the configuration change on the fly (CCOTF) functionality of the Control Participant is enabled by default. That is, the Online modification in RUN or STOP CPU parameter of the default configuration of the Control project is selected.
To complement
CCOTF for offline controller configuration, page 369
, when you refine a Control project offline, the software informs you ahead of time if a modification that you are about to make will require stopping the controller when you
to the controller later on. This information is available again in the Impact on Engine column of the Deploy Changes / Undo
Online Changes window where modifications that can be deployed are listed.
The working principle is the same as for CCOTF when configuring a controller except for the following:
• If you have performed a CCOTF-incompatible modification, save, and close the Control Participant window, the next time you refine the same project offline, you continue receiving notifications about CCOTF-incompatible modifications. This, even if you have not yet deployed the last CCOTFincompatible modification.
• Performing a CCOTF-incompatible modification does not disable the Build nor the Deploy Changes / Undo Online Changes command.
Before performing a CCOTF-compatible modification, refer to the topics describing the CCOTF functionality in the help of the Control Participant for your specific controller platform and follow the recommendations that are given.
NOTE: CCOTF is not supported for Control projects the M340 and Quantum controller families.
NOTE: CCOTF notifications are shown even if you have not yet deployed the
Control project.
Project Refinement Window
The figure shows the Refine Offline window embedding the Control Participant, which opens when you select the Refine command at the Control Participant project level. The window is shown restored.
EIO0000001114.15
337
4
5
2
3
Item
1
Description
Tab of the pane in which you can see the project sections in relation to the structure of the application
Manage network variables button
Access device DDTs of unmapped hardware button
Check consistency button
Save button
Section Refinement Window
The figure shows the Refine Offline window embedding the Control Participant, which opens when you select the Refine command at the section level. The window is shown restored.
338
2
3
Item
1
4
Description
Tab of the Control Participant window.
Tab of the section refinement window.
Tab of another refinement window (for example, a DFB refinement window), which you have opened from the section that is being refined.
Tab of another window that is open in the Project Explorer .
NOTE:
• To switch between open refinement windows, use the tabs at the bottom of the Participant window.
• To close a refinement window, right-click its tab and select Close
Window .
EIO0000001114.15
EIO0000001114.15
Viewing the Application Structure When Refining Control
Participant Projects
While you refine a Control Participant project, the Application Browser pane displays FBD sections based on the location of instances whose Control facets are assigned to these sections.
It shows the relationship between the folder structure of the application and the sections of the Control Participant project. This is useful, for example, when you want to view the logic related to a specific area or subdivision of the application.
You can open sections from the pane.
The pane only shows FBD and non-FBD sections that exist in the logical Control
Participant project at the moment you select the Refine command.
For a general description of the contents of the pane, refer to the topic describing the
application structure view, page 287
.
For information on how to use the pane, refer to the topic describing the refinement of Control Participant projects (see EcoStruxure ™ Process Expert,
Control Participant Services, User Guide).
For general information on how to work with panes, refer to the topic describing the
engineering client workspace, page 85 .
Applying Changes to Generated Control Participant Projects
Selecting the Refine command applies to the logical Control Participant project the following changes that you have made in the Project Explorer to an already generated Control project:
• Renaming a section.
• Creating an FBD section.
• Changing the order of sections.
If the status of the executable of the Control project is Built , it is set to Out Of
Date .
NOTE: You do not need to click the save button in the Control Participant window to apply the above mentioned changes.
Validity Indicators
When you save the logical Control Participant project during refinement and
project analysis is enabled, page 205 , the project is
status of the project is indicated by the
.
Details of the analysis are shown in the Analyze Project tab of the Control
Participant window while it is still open.
If the logical Control project is not open in the Participant and the validity icon is displayed, you need to refine the Control project and analyze it. This allows you to identify the cause of the invalid status. The Control Participant features tools that help you identify validity issues, which
result in an unsuccessful build, page 467 .
For information on troubleshooting Control projects and/or analyzing them, refer to the help of the Control Participant.
NOTE: This verification is performed also when you
generate a logical Control project, page 300
.
Deleting Sections During Project Refinement
The table describes the result when you delete sections during refinement and the action that you need to perform to complete the deletion process depending on the type of section.
339
340
Type of section
Non-generated FBD section that was created in the Project
Explorer .
Non-generated FBD section that was created during refinement.
Result after saving changes and closing the Control Participant window
The section still appears in the
Containers pane but below other existing sections (higher order value) (1) .
Required action
Right-click the section in the Containers pane and select
Delete .
Any non-FBD section.
(1) LL984 segments deleted during refinement appear in last position (highest order value)
Refining Non-Generated Sections
When you refine an FBD section to which facets are assigned but that is not generated yet, you do not see the constituents of these facets in the Control
Participant.
If you add logic to this section during refinement, when you
generate the section or project, page 300 , DFBs that you have added are not moved, and DFBs coming
from assigned facets are laid out around them.
Refining at the Control Project Level
To refine the logical Control project, proceed as follows.
Step
1
2
3
Action
In the Project Explorer , right-click the Control project you want to refine and select
Refine .
Result: The Control Participant opens
and maximized.
Proceed with the refinement.
For more information on the refinement process, refer to Refining the Logical Control
Participant Project (see EcoStruxure ™ Process Expert, Control Participant Services,
User Guide).
Click the save button in the toolbar of the Participant window to save the changes in the logical Control Participant project.
4
5
Perform a
if required.
Click the close button in the Control Participant window.
NOTE: If you have unsaved changes and click the close button in the Participant window, the software displays the Save Refinement dialog box where you have the following choices:
• Yes : Saves changes in the logical Control Participant project and closes the
Participant window.
• No : Discards changes and closes the Participant window.
• Cancel : Does not save changes and leaves the Participant window open.
Refining at the Section Level
To refine a section of the Control project (except for LL984 sections), proceed as follows.
Step
1
2
Action
In the Containers pane of the Assignment Editor , right-click the section that you want to refine and select Refine .
Result: The Control Participant opens
and maximized and displays only the contents of the selected section.
Proceed with the refinement of the section.
EIO0000001114.15
Step Action
3
For more information on the refinement process, refer to Refining the Logical Control
Participant Project (see EcoStruxure ™ Process Expert, Control Participant Services,
User Guide).
Click the save button in the toolbar of the Participant window to save the changes in the logical Control project.
4
5
Perform a
if required.
Click the close button in the tab of the Control Participant window.
NOTE: If you have unsaved changes and click the close button in the Participant window, the software displays the Save Refinement dialog box where you have the following choices:
• Yes : Saves changes in the logical Control Participant project and closes the
Participant window.
• No : Discards changes and closes the Participant window.
• Cancel : Does not save changes and leaves the Participant window open.
Identifying Code Generated by the Software
Overview
Constituents that are generated from facets assigned to Control projects are locked in the Control Participant project. The locked code is color coded in the
DFB editor of the Control Participant.
This feature helps you with the following:
• Distinguish code generated by the software from code that you modify and/or add during refinement.
• Avoid modifying code generated by the software inadvertently and maintain consistency. This is achieved by requiring a confirmation before unlocking code and providing the possibility to lock code again.
Locking of code is managed by the software throughout the system engineering life cycle.
Viewing Locked Code
The following figure shows an example of a Control Participant refinement window showing an FBD section, which contains code that was generated by some sample facets assigned to the section.
EIO0000001114.15
341
342
3
4
Item
1
2
Description
Code that is generated from the facet is locked and shown in purple.
Variable that was added by the user during refinement to code generated by the software. The code is not locked and shown in black.
Literal, previously shown in purple that was unlocked and changed by the user and now shown in black.
Link, previously shown in purple that was unlocked by the user and now shown in black.
Code that Is Locked
The following data is locked when generated from facets assigned to a Control project:
• DFBs and the pins to which an effective parameter is assigned.
• Effective parameters.
• Links (including links created by using an editor of the Application Explorer ).
• EFB and DFB instances.
NOTE: FBD sections that you have generated are also locked but without visual indication.
Code that Is not Locked
The following data is not locked:
• Non-FBD sections.
• Pins of DFBs to which no effective parameter is assigned or that are not connected.
• Formal parameters of DFBs.
• Variables shown in the Data Editor of the Control Participant.
• Any code added by the user during refinement offline and online.
• FBD sections that are generated but to which no facets are assigned.
Modifying Locked Code During Refinement
To modify locked code during refinement offline and online, you need to unlock it first (see EcoStruxure ™ Process Expert, Control Participant Services, User
Guide).
For example, changing the parameter that is assigned to the pin of a generated
DFB.
However, adding code that does not modify generated code can be done without unlocking. For example, assigning a parameter to an empty pin of a generated
DFB or adding an EFB in a section containing generated code.
NOTE: You cannot delete FBD sections that are locked.
Management of Locked Code in the System Engineering Life
Cycle
The fact that code is locked is part of its attributes and managed by the software during the system engineering life cycle.
As such, unlocking code is detected as an inconsistency during a
even if the code itself is unchanged. The status of the facet that generated the code is set to Inconsistent .
Code that was originally locked and that you have unlocked is:
• Locked again when the facet is generated and either condition applies:
EIO0000001114.15
◦ The status of the facet is Inconsistent .
◦ No consistency check was performed but the contents of the section
.
• Detected when you use the following commands:
◦ Deploy Changes / Undo Online Changes
◦ Update Project
Considerations when Migrating Databases
When you refine a Control project of a database that was migrated from a previous version of the software, code generated by the software may not be locked.
However, you can enable the code locking feature for such code in a migrated database if you perform a consistency check and generate the Control project.
Code generated from facets that are assigned to Control projects after the migration is locked.
The table describes the impact on code that is generated by the software and contained in a migrated database depending on the action that you perform and the status of facets.
Actions performed after migration
Result after generating the Control projects
No consistency check was performed.
Status of facets assigned to Control projects in the migrated database
Generated or Unlinked .
Non Generated , Out Of
Date , or Inconsistent .
A consistency check is performed.
All facets are set to
Inconsistent .
No change.
The code of facets that were successfully generated is locked.
FBD sections containing at least one such facet are locked.
The code of facets that were successfully generated is locked.
FBD sections containing at least one such facet are locked.
NOTE: If you use the Regenerate command on the Control project after migrating the database, code that was generated by the software before the migration is locked even if you have not performed a consistency check.
Creating and Updating Device DDT Variables in Logical Control Projects
Overview
In the system engineering life cycle, the software lets you engineer Control projects independently of the hardware that exists in the topology up to the build stage. As a result, device DDT variables, which are associated to hardware modules and managed by the Control Participant are not readily available when you refine a logical Control project offline.
This functionality lets you create in the logical Control project device DDT variables that are associated to the hardware present in the topology of the system. This makes it possible to use device DDT variables in the program during refinement offline, for example, to manage special modules or access hardware diagnostic data.
Using device DDT variables does not replace hardware mapping. Device DDT variables do not appear in the Hardware Mapping Editor .
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
EIO0000001114.15
343
Device DDT Variables Present in the Control Project by Default
When you create a Control project of the M580 platform in the Project Explorer , it contains a default configuration with only a controller (although it is not to be used from the Project Explorer at this stage of the system engineering life cycle).
Therefore, by default, the logical Control Participant project already contains the device DDT variable that is mapped to the M580 CPU module (a lock icon appears next to the DDDT variable). You can use it by refining the logical Control project.
Prerequisites
The topological entities whose device DDT variables you want to create must exist in the topology of the system.
Accessing the Device DDT Variable Wizard
To open the wizard, refine the Control project and click the device DDT wizard
.
Device DDT Variable Wizard - Controller Selection
344
Item
1
2
3
Description
Box to select the controller whose device DDT variables you want to create in the logical
Control project.
When the check box is selected, the menu shows only the controllers that are service mapped to an executable of the Control project. Otherwise, it shows the controllers that exist in the topology of the system.
Proceeds to the next screen and locks the controller in the Topology Explorer so that no other user can change its configuration or delete it.
EIO0000001114.15
Device DDT Variable Wizard - Device DDT Variable Selection
EIO0000001114.15
4
5
6
2
3
Item
1
7
8
Description
Candidate pane that shows device DDT variables of the controller that you have selected and that you can create in the logical Control project. The following can be shown:
• Variables that do not exist in the logical Control project yet.
• Variables and types that already exist but which have been modified in the controller.
NOTE: The following variables do not appear in the candidate pane:
• Device DDT variables of the M580
• Device DDT variables that already exist in the logical Control project with the same name but with a different type. This can be the case, for example, if after having created the device DDT variable for hardware module 1, you remove this module in the topology, add hardware module 2, which creates a device DDT variable of a different type, and rename this device DDT variable to have the same name as the variable that was associated to hardware module 1.
Selected variables panes that shows the device DDT variables that you have selected.
Name of the device DDT variable.
Data type of the device DDT variable.
Either action appears for each device DDT variable:
• Create :
the data type and the variable in the logical Control project.
• Update :
the data type in the logical Control project.
Notification area.
Expand the area to view alerts on device DDT variables of the selected controller.
Reverts to the previous screen.
To be able to select device DDT variables from another controller, you need to complete the process for your current selection first. Any selection that you have not applied is discarded.
Impact of the Create Action on the Logical Control Project
The table describes the impact when you create in the Logical Control Project a device DDT variable that appears in the candidate pane with the Create action.
The impact varies depending on the scenario.
345
346
Scenario
The variable and the type are not yet present in the logical Control project.
A type of the same name already exists in the logical Control project but not the variable.
Impact of the Create Action
Both are created in the logical Control project.
The variable is created.
If the structure of the type of the selected variable is different, it overwrites the type that is present in the
Control project. This may impact other existing variables of that type.
Impact of the Update Action on the Logical Control Project
The table describes the impact when you update in the Logical Control Project a device DDT variable that appears in the candidate pane with the Update action.
The impact varies depending on the scenario.
Scenario
The variable and the type already exist in the logical Control project but the structure of the selected type is different.
The variable and the type already exist in the logical Control project but the version of the selected type is different.
Impact of the Update Action
The structure of the type is updated in the logical
Control project. This may impact other existing variables of that type.
The version of the type is updated in the logical
Control project. This may impact other existing variables of that type.
Creating or Updating Device DDT Variables
To create or update device DDT variables in the logical Control project, proceed as follows.
Step
1
2
3
4
Action
In the device DDT variable wizard, select the controller whose device DDT variables you want to create or update and click Next .
Expand the notification area to view alert messages.
In the candidate pane, select one or more device DDT variables that you want to create/update and click OK .
Result : The selected device DDT variables are processed by applying the corresponding action for each and the wizard is closed.
Save changes by clicking the
in the toolbar of the Control
Participant window frame.
Modifying Device DDT Variables
Device DDT variables that you create in the logical Control project are not locked and you must not modify their structure or name. If you do, the software cannot treat them anymore as device DDT variables associated to the device from which they were created originally.
Deleting Device DDT Variables
You cannot remove a device DDT variable and/or its data type from the logical
Control project by using the device DDT variable wizard.
To remove the variable, select it in the Control Participant window while refining the logical Control project and select Delete . Then, purge the type by using the
Types Library manager
EIO0000001114.15
Considerations When Removing Modules in the Topology
Explorer and Deploying Changes
When the topology of the system contains entities and you had created the corresponding device DDT variables in the logical Control project, built the project, and deployed it, if you delete the source of the device DDT variable from the topology (for example, a module or DTM), verify that the corresponding device
DDT variable is removed in the configuration of the Topology Explorer . If not (for example, when you delete an analog input module), you need to purge the corresponding device DDT variable.
Otherwise, if you build the logical Control project after removing the source of the device DDT variable from the topology, it remains in the built Control project as unmapped variable (while it is present in the deployed Participant project as mapped variable). If you deploy changes, the software proposes to add the unmapped device DDT variable.
Integrating Device DDT Variables in the System Engineering
Life Cycle
To use device DDT variables that you have created logical Control project, follow
the stages of the system engineering life cycle described in this manual ( build, page 466 ,
, deployment,
515 , refinement online, and so on).
Using Device DDT Variables in the Supervision Runtime
Device DDT variables do not have the HMI attribute enabled. To use such a variable in Supervision, you need to connect it to the input pin of a DFB encapsulated in a template that features Supervision services.
Managing Consistency
Overview
Consistency management is a process that encompasses the following steps:
• Launching the consistency check of a logical Control Participant project or
FBD section of such project.
• Indicating if the constituents of facets that the software has generated in such project or FBD section are not consistent with the related facets that are assigned to the Control project or section. In such case, a message informs you of the detected inconsistencies and the Generation status of the related facets is changed to Inconsistent . Otherwise, the software informs you that it did not detect an inconsistency.
• Attempting to fix the detected inconsistencies by restoring the constituents inside the logical Control Participant project or FBD section to a state that is consistent with the related facets of the Control project or section.
The purpose of consistency management is to provide means for you to know whether changes that you have made during refinement affect the logical Control
Participant project that was created during generation and, if desired, to fix inconsistencies when it is possible without modifying the refinements you made.
The software performs a consistency check in the following way when you:
• Generate again an already generated Control project or FBD section:
Depending on the
changes you have made, page 324 .
•
a facet with the status UnAssigned : Automatically (if available).
•
a facet with the status Unlinked : Automatically (if available).
•
Update the logical Control Participant project, page 567
: On request.
NOTE: The software does not perform consistency checks on facets that have the Unlinked
.
EIO0000001114.15
347
348
Rules for Consistency Checks
The table indicates in which cases the software detects and reports an inconsistency when performing a consistency check on constituents that the software has generated in a logical Control Participant project. It also indicates the resulting status of the facet encapsulating the constituent.
Type Change made through refinement
Any change resulting in a new version of the type (1) .
Change causing no version change but resulting in a new type or code signature (1) .
Generation status of the facet
Changes to Inconsistent .
Derived data
(DDT) and function block (DFB) types
Variables Changing an attribute of a variable.
Removing markers created by the software (for example P2P ).
FBD sections
Changing function calls (EFs, EFBs, or DFBs) in an
FBD section.
Changing the relative execution order of function blocks (EFs, EFBs, or DFBs).
No change.
Changing links. Includes changing immediate values and links between variables.
Unlocking
.
Changes to Inconsistent
– Changes to Inconsistent .
(1) The change may also have been made by encapsulating a modified type in a Control facet and updating the template with this facet. However, starting with Process Expert 4.2 SP2, the software does not allow you anymore to save modifications to the type encapsulated in a Control facet if the version of the type is still the same but its type or code signature different.
.
Check Consistency Dialog Box
The figure shows an example of the Check Consistency dialog box.
EIO0000001114.15
EIO0000001114.15
1
2
3
4
5
6
7
8
9
Check box to select all FBD sections and facets that appear in the two categories of the dialog box. By default no section or facet is selected.
Category listing FBD sections containing facets for which inconsistencies related to their DDT and DFB types have been detected. Select the check box to select all sections and facets that appear in this category.
Category listing FBD sections in which inconsistent facets have been detected. Select the check box to select all sections and facets that appear in this category.
Name of a type for which an inconsistency has been detected. Expand the node to view the facets generating this type and the sections to which these facets are assigned.
Identifier of a section to which facets are assigned, which are inconsistent.
Expand the node to view the facets.
Description of the detected inconsistency.
Unlinks the selected facets so that no consistency check is performed on them.
Copies the content of the dialog box to the Clipboard in text format. The status of check boxes is not copied.
Cancels your selection and closes the dialog box.
NOTE: When a section or facet appears in both categories, selecting it in one category automatically selects it in the other, and the other way around, clearing its selection in one category automatically clears it in the other.
Performing a Consistency Check
To perform a consistency check on generated constituents, proceed as follows.
Step
1
Action
In the Project Explorer , right-click the Control project or FBD section that you want to check for consistency and select refine .
Result: The Control Participant opens in a reduced window.
2
3
4
In the toolbar of the window, click the check consistency button .
Result: The software:
• Performs a consistency check.
• Opens the Check Consistency dialog box.
• Changes the Generation status of facets referencing inconsistent constituents to
Inconsistent .
NOTE: The check consistency button is not available when you refine a non-FBD section.
In the Check Consistency dialog box, select inconsistent sections and/or facets that you want to unlink.
Click Unlink to unlink the selected facets.
NOTE: Click Cancel to close the Check Consistency dialog box without unlinking facets. The status of facets that the software has detected as inconsistent remains
Inconsistent .
Managing Inconsistencies
Even though a logical Control Participant project contains inconsistent facets, you can proceed further in the system engineering life cycle.
Regenerate the FBD section or project containing inconsistent facets to revert to a consistent state, which is indicated by the generation status Generated of the facet but certain
changes that you made through refinement are discarded, page
For information on managing inconsistencies without affecting changes made through refinement, refer to
Generating Inconsistent Facets, page 325
.
349
About Variables for Peer to Peer Communication
Overview
The software facilitates the creation of variables to exchange scattered data or sets of data between two or more Control Participant projects by using peer to peer communication. Such variables are called network variables .
You can create network variables in the following ways:
• By assigning facets of instances to different projects.
• By refining both logical Control Participant projects. Refer to Refining the
Logical Control Participant project (see EcoStruxure ™ Process Expert,
Control Participant Services, User Guide).
• By using peer to peer communication templates of the EcoStruxure Process
Expert Foundation Library.
• By using a mix of the above.
Depending on the way that you use to create them, network variables have the candidate status until they are explicitly created for use as network variables by using the Manage Network Variables
.
You can create network variables before proceeding with the service mapping and the creation of
communication channels, page 424 .
Variables used for peer to peer communication are allocated during
based on the
network variable mapping, page 435
.
NOTE: For more information on the steps to implement peer to peer communication by using the I/O scanner function, refer to the topic describing
peer to peer communication by modbus TCP Ethernet implicit messaging, page 597 .
Control Participant Functionality
Peer to peer communication can also be implemented by using the specialized functions of the Control Participant instead of or in addition to using the templates of the EcoStruxure Process Expert Foundation Library.
To do so, refine the client Control project and add the necessary logic.
For details, refer to the topics describing the READ_REMOTE and WRITE_
REMOTE functions in the help of the Communication Library of the Control
Participant.
NOTE: The functions are available for Control projects of the M580 and M340 platforms with compatible CPU firmware version.
Owner/Consumer Project Principle
To help you understand the way peer to peer communication is implemented in the software, this manual uses a particular naming convention to refer to the
Control Participant projects that exchange data.
The logical Control Participant project producing the variables to be shared is the owner project, and the one receiving the variables is the consumer project.
The controller that is mapped to the owner project acts as the server. The one mapped to the consumer project acts as the client.
A network variable allows you to read data from the server by mapping it to a communication channel that exists client-side.
NOTE: You can write data to the server by using a network variable that exists in the owner project and the corresponding variable of same name and type in the consumer project.
350 EIO0000001114.15
The following example illustrates the owner/consumer principle in a system where sample variables DISignal_UL_1V and Valve_1_VALVE_OPV are used for peer to peer communication to read from and write to the server respectively. The variables are generated by facets of the DISignal_UL_1 and Valve_1 sample instances respectively. The specific attributes of the variables of reference data type are shown. The two instances are linked and their facets are assigned to the
Owner_Project and Consumer_Project Control Participant projects. The executable of each project is mapped to the corresponding topological entity. The read from server and write to server actions are performed from the consumer
(client) project.
EIO0000001114.15
Ways to Create Network Variables to Share Scattered Data Oneto-One
The first two scenarios that are shown in the following figure illustrate two common ways to create a network variable to share scattered data between an owner and a consumer project.
Other ways to create network variables exist, page 355 .
351
352
Scenario Description
1 When the instance in the owner project creates a variable (for example, an instance of a hardware abstraction layer (HAL) template), it can be linked directly to the input pin of a DFB (created, for example, by an instance of an application template) in the consumer project.
2 When the instance in the owner project does not create a variable (for example, an instance of an application template), the output pin needs to be linked first to an instance of a peer to peer communication template (for example, Data Out) in the owner project.
The Data Out instance creates a variable, which can be linked directly to the input pin of a DFB (created, for example, by an instance of an application template) in the consumer project.
3 In the first two scenarios, only a network variable candidate is created. You need to create the network variable manually by using the Manage Network Variables
This third scenario shows how to create the network variable automatically by using two peer to peer communication templates (Data Out and Data In).
The following example shows how to implement the first scenario by using sample instances and linking them in the Asset Workspace Editor . Facets of each instance are then assigned to the owner and consumer projects.
The following example shows how to implement the second scenario by using sample instances and linking them in the Asset Workspace Editor . Facets of each instance are then assigned to the owner and consumer projects.
EIO0000001114.15
The following example shows how to implement the third scenario by using two peer to peer communication templates to create the network variable automatically. Instances are linked in the Asset Workspace Editor .
Ways to Create Network Variables to Share Scattered Data Oneto-Many
The following figure illustrates the use of Data In and/or Data Out application templates to share one variable exposed by one owner project with three different consumer projects of the same system.
This example illustrates the scenario by using sample instances and linking them in the Asset Workspace Editor . Facets of each instance are then assigned to the owner and the three consumer projects.
EIO0000001114.15
Ways to Create Network Variables to Share Sets of Data
The following figure illustrates the use of owner and consumer application templates to share physical signals:
• Without signal conditioning.
• With signal conditioning by using a HAL template.
353
354
NOTE: In both cases, the physical signals are linked to the owner template and the HAL templates respectively by using mapping interfaces (dotted lines) during the hardware mapping.
For more information on owner/consumer templates and a usage example, refer to the topic describing these templates (see EcoStruxure ™
Expert , Foundation Application Templates, User Guide).
Process
Properties of Variables for Peer to Peer Communication
Certain attributes of variables that you create through refinement to be mapped to peer to peer communication channels require a specific configuration.
The configuration varies depending on:
• Whether the variable is used to read from the server or
write to the server, page 350 .
• The platform or the communication module that is used by the topological entity acting as client.
The table describes required variable attribute values in the Control Participant when the topological entity acting as client communicates by using a Quantum
CPU module or an NOE communication module (with Quantum or M340 platform).
Usage
Reading data from the server
Writing data to the server
Variable attribute
Designation of the variable in the context of
EcoStruxure Process
Expert
Owner project/Server
Variable
Name
Type
Custom
Any valid name
Any, including the
Reference data type (REF_
TO).
Some
restrictions apply, page 357 .
Custom
Constant (1)
R/W Rights of
Referenced Variable (1)
Designation of the variable in the context of
EcoStruxure Process
Expert
Blank
True (selected)
True (selected)
Network variable
Name
Type
Any valid name
Any, including the
Reference data type (REF_
TO).
Some
restrictions apply, page 357 .
P2P
Consumer project/Client
Network variable
Same name
Same type
P2P
True (selected)
False (cleared)
Variable
Same name
Same type
Blank
EIO0000001114.15
Usage Variable attribute Owner project/Server
Constant (1) True (selected)
R/W Rights of
Referenced Variable (1)
True (selected)
(1) For variables of the Reference data type (REF_TO) only
Consumer project/Client
True (selected)
True (selected)
The table describes required variable attribute values in the Control Participant when the topological entity acting as client communicates by using an M580 CPU module with or without NOC communication module, or a Quantum controller with
NOC communication module.
Usage
Reading data from the server
Variable attribute
Designation of the variable in the context of
EcoStruxure Process
Expert
Name
Type
Owner project/Server
Variable
Consumer project/Client
Network variable
Writing data to the server
Custom
Constant
R/W Rights of
Referenced Variable
Designation of the variable in the context of
EcoStruxure Process
Expert
Name
Type
Any valid name
Reference data type (REF_
TO) only
Blank
True (selected)
True (selected)
Same name
Same type
P2P
True (selected)
False (cleared)
Network variable Variable
Custom
Constant
R/W Rights of
Referenced Variable
Any valid name
Reference data type (REF_
TO) only
P2P
True (selected)
True (selected)
Same name
Same type
Blank
True (selected)
True (selected)
NOTE: For more information on the REF_TO data type, refer to the topic describing the refinement of Control projects (see EcoStruxure ™ Process
Expert, Control Participant Services, User Guide).
Overview of Ways to Create Network Variables
The table provides an overview of the different ways to create network variables in the consumer project to read data from the controller of the owner project, acting as server. It also indicates the status of the variable for each method.
Action in owner project
Instantiate a Data Out template corresponding to the data type to be shared
(for example,
$DOUTBool_UL to share a boolean variable of the
REF_TO ANY_BOOL data type).
Instantiate a peer to peer owner template corresponding to the data
Action in consumer project
-
Instantiate a Data In template corresponding to the data type of the Data Out template (for example, $DINBool_UL ).
Instantiate a peer to peer consumer template matching the peer to peer owner template (for
Status of variable
Once you generate both projects, the Manage Network
Variables dialog box detects the variable as a network variable candidate in the consumer project, with the name of the Data Out template instance.
Create the network variable, page 357
.
The generation process creates a network variable in the consumer project with the name of the Data Out template instance.
NOTE: The Manage Network Variables dialog box shows the variable in the Existing Network Variables pane.
The generation process creates a network variable in the consumer project with the name of the owner template instance.
EIO0000001114.15
355
Action in owner project type to be shared (for example, $Bool16INO to share up to 16 boolean input signals of the REF_
TO data type).
Instantiate a template, which creates a variable during the generation process (for example, a variable of type REF_TO
ANY_BOOL (1) ).
Create a variable shared by using the
Refine
(1) command.
to be
Action in consumer project example, $Bool16INC to receive up to 16 boolean input signals).
Reference a variable of the same name and data type as the one created by the instance in the owner project without declaring it by using the Refine type, and enter command.
Instantiate a template that receives the variable exposed by the instance in the owner project by creating a link between both templates in the Asset Workspace Editor .
Create a variable of the same name and data type as the one created by the instance in the owner project, and enter P2P as Custom attribute by using the Refine command.
Reference a variable of the same name and data type without declaring it, using the
Refine command.
Create a variable of the same name and data
P2P as Custom using the Refine command.
attribute by
Status of variable
NOTE: The Manage Network Variables dialog box shows the variable in the Existing Network Variables pane.
The Manage Network Variables dialog box detects the variable as a network variable candidate in the consumer project.
Create the network variable, page 357
.
The Manage Network Variables dialog box shows the variable in the Existing Network Variables pane.
The Manage Network Variables dialog box detects the variable as a network variable candidate in the consumer project.
Create the network variable, page 357
.
The Manage Network Variables dialog box shows the variable in the Existing Network Variables pane.
(1) Verify that the data type of the variable that is created meets the
requirements to be used for peer to peer communication, page 354 .
NOTE:
• The table does not detail each step required to implement peer to peer communication. For more information, refer to
Communication Through Modbus TCP Implicit Messaging, page 603
.
• To be detected and/or created as network variables by the Manage
Network Variables dialog box, variables need to satisfy the
network variable management rules, page 357 .
Overview of Peer to Peer Templates
The following templates are available from the Global Templates library to create network variables:
• Data IN/Data OUT: Application facet templates that create a network variable in the consumer project. The library contains templates for sharing various variable sizes and data types. Use these templates to share scattered data.
For a detailed description of the templates and how to use them, refer to Data
In/Data Out Templates (see EcoStruxure ™ Process Expert , Foundation
Application Templates, User Guide).
NOTE: To find these templates by using the template browser of the
Application Explorer , select the Facets
, and enter either din or dout in the search field.
• Owner/Consumer: Application composite templates that create a network variable in the consumer project. The library contains templates for sharing up to 16 digital and 8 analog inputs/outputs. Use these templates to share sets of data. Typically, such templates allow you to manage I/O objects exchanged between a Modicon BMX PRA module and a master controller.
For a detailed description of the templates and how to use them, refer to
Owner/Consumer Templates (see EcoStruxure ™ Process Expert , Foundation
Application Templates, User Guide).
NOTE: Network variables created by using peer to peer templates have the
Custom attribute set to P2P by default in the variable properties window of the
Control Participant.
356 EIO0000001114.15
Managing Network Variables
Overview
This topic describes how to use the Manage Network Variables dialog box to manage network variables, which exist or have the candidate status.
Network variable management includes the creation, modification, and deletion of network variables.
General Network Variable Management Rules
The software applies either of the following rules to identify candidate network variables when you open the Manage Network Variables dialog box:
• The variable needs to be referenced from, at least, 1 FBD section but not be declared.
• The variable is created by using a
peer to peer template, page 351 .
In addition, the following are not considered network variable candidates:
• Variables referencing an element of a data structure (for example,
DigitalInput_DINPUT_ST.STW
where STW is a word of the DINPUT_ST structure).
• Function block instances (for example, DigitalInput_DINPUT.PV
where PV is a formal parameter of the DINPUT DFB).
• Types ANY_X where X represents the type (except for the ANY_BOOL data type).
• Inconsistent types (for example, a.b where a and b are variables and one of them is undefined).
• 32-bit data types.
NOTE: In the Manage Network Variables dialog box, it is not taken into account whether the data type of the variable is
compatible with the communication module client-side, page 354
.
Network Variable Properties
Network variables that the software creates by using the Manage Network
Variables dialog box have the following properties:
• They are of the same type as shown in the Type field of the Network
Variables Candidates section.
• They have P2P as Custom attribute in the variable properties window of the
Control Participant.
NOTE: The software does not set the R/W Rights of Referenced Variable attribute for REF_TO type network variables that it creates. If it needs to be enabled, you need to refine the consumer project and set the attribute manually (see EcoStruxure ™ Process Expert, Control Participant Services,
User Guide) in the variable properties window of the Control Participant.
Opening the Manage Network Variables Dialog Box
You can open the Manage Network Variables dialog box either way:
• From the context menu of the Control Participant project in the Project
Explorer by selecting Manage Network Variables .
• From within the Control Participant by clicking the button (see
EcoStruxure ™ Process Expert, Control Participant Services, User Guide).
When you refine at the section level, the button is available only for FBD sections.
Both commands open the Manage Network Variables dialog box. The difference lies in the way you save changes.
EIO0000001114.15
357
Manage Network Variables Dialog Box
The following figure shows an example of the Manage Network Variables dialog box in which several sample variables appear.
358
1 Network Variables section showing existing network variables.
2 Network Variable Candidates section showing the candidate variables that the software has detected in the selected project. These variables satisfy the applicable rules and you can them use as network variables. Certain restrictions apply depending on the communication module used by the topological entity acting as client.
Fields of the Network Variables section.
Header
Action
Name
Type
Comment
Description
• Left/right arrow icon: Existing network variable.
• Minus icon: The variable will be removed from the project.
• Plus icon: The variable will be added to the project.
• Pencil icon: The variable will be modified in the project.
• Lock icon: The variable is already mapped to a peer to peer communication channel in the
communication mapping, page 424
.
Identifier of the variable.
The field is
Data type of the variable
You can enter a comment for the variable using free form text.
Fields of the Network Variable Candidates section.
Header
Name
Type
Description
Identifier of the variable.
When you use HAL or peer to peer templates, the name of the variable is the identifier of the template instance.
Data type of the variable.
NOTE: You can select multiple variables in either sections by selecting the first variable, pressing and holding Ctrl , and selecting the other variables by using the pointer.
EIO0000001114.15
EIO0000001114.15
Saving Changes in the Manage Network Variables Dialog Box
Depending from where you have opened the Manage Network Variables dialog box, the procedure to apply and save your changes varies.
If you have opened the Manage Network Variables dialog box from the context menu of the Control project, proceed as follows to apply and save your changes.
Step
1
2
Action
In the Manage Network Variables dialog box, click OK .
Result : A confirmation dialog box opens.
Click Yes to save your changes.
NOTE:
• Click No to close the Manage Network Variables dialog box without saving changes.
• Click Cancel to leave the Manage Network Variables dialog box open without saving changes.
If you have opened the Manage Network Variables dialog box from within the
Control Participant during refinement, proceed as follows to apply and save your changes.
Step
1
2
Action
In the Manage Network Variables dialog box, click OK to apply the changes to the logical Control project.
Result : The Manage Network Variables dialog box closes.
NOTE: If you open the Manage Network Variables dialog box again before closing the Control Participant, your changes are preserved but are not saved yet.
Click the save button in the toolbar of the Control Participant window to save your changes.
NOTE: Closing the Control Participant without saving does not apply your changes.
Creating Network Variables
To create a network variable by using the Manage Network Variables command from the context menu of the Control project, proceed as follows.
Step
1
2
3
Action
In the Projects Explorer , right-click the logical Control project in which you want the software to identify network variable candidates and select Manage Network
Variables .
Result: The Manage Network Variables dialog box opens. If the software did not detect any candidate or network variables, the corresponding dialog box fields are empty.
In the Network Variable Candidates section, select the candidate variables that you want to create as network variables and drag them to the Network Variables section.
Result: The network variables are shown in the New Network Variables section.
NOTE: Right-click a network variable to open a context menu, which allows you to make
.
Result: The software closes the dialog box, creates the network variables, and displays a summary of the actions in the notification panel.
NOTE: You can see the variable by refining the Control Participant project and double-clicking Elementary Variables in the Variables & FB Instances section of the Project Browser .
359
Modifying Network Variables
NOTE: Depending from where you have opened the Manage Network
Variables dialog box, there are different ways to
You can perform the following modifications on network variables displayed in the
Network Variables section:
Action
Adding a comment
Changing the name of the variable
Description
Double-click the Comment field of the variable and enter a description with free form text.
Double-click the Name of the variable and enter a new name with free form text.
NOTE: You can only change the name of existing network variables that are not yet mapped to a communication channel.
Undoing changes
Deleting a network variable
Right-click a variable and select Undo to discard the changes that you have made.
You can also press Ctrl + Z .
NOTE: You cannot undo changes that you have applied by clicking
OK if you have opened the Manage Network Variables dialog box from within the Control Participant.
Right-click a variable and select Remove to:
• Display the variable again in the Network Variable Candidates section if it has not been created yet.
• Mark the network variable for deletion in the Control Participant project.
If the variable is mapped to a communication channel, the software
.
You can also select a variable and press Del .
Supervision Project Refinement Stage
Refining the Supervision Project
Overview
The refinement process of Supervision Participant projects allows you to:
• View and modify Participant project data by using the Refine command.
Limitations apply to the modification of project data that is managed by the software.
• Add animated graphics to
of the project, using the Edit command.
• Edit Participant project settings by using the Advanced Settings command.
• Add included projects and attach user files.
For each Supervision Participant project, you can use only one of the aforementioned commands at a time. However, you can edit several Supervision pages at the same time. Each command uses one instance of the virtual machine
(see EcoStruxure ™ Process Expert, Installation and Configuration Guide).
NOTE: While you refine the Supervision Participant project or edit advanced settings, commands such as Generate or Delete are not available for pages or containers.
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
360 EIO0000001114.15
Refining the Supervision Project
To refine the Supervision project, proceed as follows.
Step
1
2
3
4
Action
In the Project Explorer , right-click the Supervision project you want to refine and select
Refine .
Result: The Supervision Participant opens
and maximized.
Proceed with the refinement.
For more information on the refinement process and restrictions that apply, refer to the topic describing the refinement of the Supervision project (see EcoStruxure ™ Process
Expert, Supervision Participant Services, User Guide).
Close the Participant window.
Result: The Save Refinement dialog box opens.
Click the appropriate button in the dialog box.
Result:
• Yes : Closes the Supervision Participant window and keeps only changes that you have saved in the Supervision Participant.
• No : Closes the Supervision Participant window and discards all changes, including those that you have saved in the Supervision Participant.
• Cancel : Closes the Save Refinement dialog box and keeps the Supervision
Participant window open.
Editing Supervision Project Pages
The number of pages that you can edit at the same time is limited by the number of virtual machine instances that can run simultaneously (see EcoStruxure ™
Process Expert, Installation and Configuration Guide) for the client and/or system server (for the system server in case the client is installed on the system server computer).
You can save changes to several Supervision pages at the same time by clicking the save button on each Supervision Participant window.
When you add an animated graphic to a page, the software adds the required included project to the Supervision Participant project if it is not yet present. You can
download included projects, page 478
as soon as the software has added them.
To edit a Supervision page, proceed as follows.
Step
1
2
Action
In the Containers pane of the Assignment Editor , right-click the
that you want to edit and select Edit .
Result: The Supervision opens
and maximized with the Instances browser pane next to it.
Edit the page as required.
For more information on adding animated graphics, refer to Editing Supervision Pages
(see EcoStruxure ™ Process Expert, Supervision Participant Services, User Guide).
EIO0000001114.15
361
362
Step
3
Action
Click the save button in the toolbar of the Participant window to save the changes.
4
Result: The facets that encapsulate the animated graphics that you have added to a page appear in the Assignments pane when you select the page. The Assignment and Generation statuses of these facets are Assigned and Generated respectively.
If you have deleted an animated graphic that had already been added to a page, the corresponding facet is removed from the Assignments pane.
Close the Supervision Participant window.
NOTE:
If you have unsaved changes and click the close button on the outer frame of the
Participant window, the software displays the Save Refinement dialog box where you have the following choices:
• Yes : Saves changes you made to the page and closes the Participant window.
• No : Discards changes and closes the Participant window.
• Cancel : Does not save changes and leaves the Participant window open.
Editing Advanced Supervision Project Settings
To edit advanced project settings, proceed as follows.
Step
1
2
3
Action
In the Project Explorer , right-click the Supervision project and select Advanced
Settings .
Result: The Supervision Participant opens
and maximized.
Proceed with changes to the advanced project settings.
For more information, refer to Editing Advanced Project Settings (see EcoStruxure ™
Process Expert, Supervision Participant Services, User Guide).
Click the save button in the toolbar of the Participant window to save the changes.
4 Close the Supervision Participant window.
NOTE:
If you have unsaved changes and you click the close button in the Participant window, the software displays the Save Advanced Settings dialog box where you have the following choices:
• Yes : Saves changes you made to the advanced settings and closes the
Participant window.
• No : Discards changes and closes the Participant window.
• Cancel : Does not save changes and leaves the Participant window open.
NOTE: You need to
the Supervision project to apply changes to advanced project settings.
Adding Included Projects
When you
add an animated graphic, page 361
to a Supervision page, the software automatically adds the required included project to the Supervision Participant project.
You can add additional included projects. However, you cannot add an included project if the software has already added to the Participant project an included project with the same name.
To add additional included projects to a Supervision Participant project, proceed as follows.
EIO0000001114.15
Step
1
2
3
4
Action
In the Project Explorer , right-click the Supervision project to which you want to add an included project and select Include Projects .
Result: The Include Projects window opens.
Click Add .
Result: The Open dialog box opens.
Browse to the location where the included project file (.ctz) is stored, select it, and click
Open .
Result:
• If an included project with the same name already exists in the Participant project, the software displays a notification:
◦ Click OK to acknowledge.
◦ Close the Include Projects window.
• If an included project with the same name already exists in the Global
Constituents folder of the contents repository, the software displays a notification:
◦ Click OK to add the included project that exists in the contents repository.
◦ Click Cancel to cancel the process without adding the included project.
• If no included project with the same name already exists, the software:
◦ Stores the selected file in the contents repository.
◦ Displays the selected file in the window.
NOTE: The software lets you
included project that you add.
Close the Include Projects window.
NOTE: To remove an included project from the Supervision project, select the file in the Include Projects window and click Remove . After you acknowledge the command, the software removes the file and deletes it from the contents repository.
Attaching External Files
To add external files to a Supervision project, proceed as follows.
Step
1
2
3
4
Action
In the Project Explorer , right-click the Supervision project to which you want to add files and select Attach User Files .
Result: The Attach User Files window opens.
Click Add .
Result: The Open dialog box opens.
Browse to the location where the file is stored, select it, and click Open .
Result: The software:
• Stores the selected file in the contents repository.
• Displays the selected file in the window.
NOTE: The software includes files that you attach into the Supervision project, which it deploys during deployment.
Close the Attach User Files window.
NOTE: To remove a file from the Supervision project, select the file and click
Remove . The software removes the file and deletes it from the contents repository . If user files had already been deployed, they are not removed from the location they were deployed to when you
re-deploy the Supervision project, page 523
.
EIO0000001114.15
363
Configuration Stage
What’s in This Chapter
Creating the Topology of the System............................................................. 364
Overview
This chapter provides information to help you model the entire topology of the system, which consists of the hardware and software infrastructure.
The following figure shows the position of the Configuration stage within the system engineering life cycle.
Refer to the
for a description of the purpose of this stage.
Creating the Topology of the System
Overview
This section describes how to use the Topology Explorer to create and configure topological entities modeling the topology of the system.
The software includes templates that allow you to model the following infrastructure components:
• Ethernet networks
• Station nodes
• Controllers
• Ethernet STB islands and devices connected through CANopen extension
• Modbus TCP and EtherNet/IP I/O devices
• PROFIBUS remote masters (PRMs) and their decentralized peripherals
(DPs)
Controllers and station nodes act as engines to which you can deploy Control or
Supervision projects.
364 EIO0000001114.15
For more information on supported architectures, refer to the topic describing integrated architectures (see EcoStruxure ™ Process Expert, Control Participant
Services, User Guide).
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
Organizing the System Topology
Before Starting
The topology of the system is defined through
, which consist of instances of topological templates, called devices. You can organize these entities in the form of a folder structure, which is displayed in the tree view of the Topology Explorer .
Before creating the folder structure for the topology, define the appropriate segmentation and naming convention for the hardware infrastructure of the system.
NOTE: Before selecting another command for an entity, wait for the current task to complete. However, the same command can be executed on distinct entities by one or more clients simultaneously.
Opening the Topology Explorer
To open the Topology Explorer , right-click the system from the Systems
Explorer tree view and select Open Topology .
Topology Explorer Window
The following figure shows an example of the Topology Explorer window.
EIO0000001114.15
1 System root folder
2 Topology folder tree view
3 Station node entity (expanded view to display contents)
4 Ethernet networks
5 Controller entity (collapsed view)
365
366
Topological Entity Description
The following figure shows an example of topological entity.
3
4
Item
1
2
5
Description
Identifier of the entity.
Icon indicating the type of entity.
Show/hide devices button.
Mapping indicator.
The entity is mapped when a check mark is displayed. It is not mapped when a cross is displayed.
Hover with the pointer over the indicator to display in a tooltip the mapping status.
Online refinement indicator.
The icon indicates that you have made changes online to the Control Participant project that is deployed to the engine. These changes need to be applied to the associated logical Control Participant project and controller configuration to make them consistent with the one that is deployed to the engine.
The icon is removed once you successfully
update the associated logical Control
with all the changes that the software has detected in the following sections of the Update Project dialog box:
• Derived Data & FB Types
• Variables & FB Instances
• Sections
If you update the project only partially with these three categories, the icon remains visible.
Hover with the pointer over the indicator to display a tooltip.
NOTE: If you have also made changes pertaining to the Animation Tables and/or
Operator Screens category, it is not relevant whether you select or not any of these two categories as long as you select all the changes in the three aforementioned categories to remove the refinement indicator.
If you have made a change online pertaining only to the Animation Tables and/or
Operator Screens category, you need to select such change to remove the indicator.
Creating Topology Folders
The Topology Explorer allows you to organize the system infrastructure in the form of a folder structure.
To create a topology folder, proceed as follows.
Step
1
Action
Right-click the system root folder in the Topology Explorer and select Create Folder .
Result : A topology folder is created and displayed it in the tree view.
NOTE: To create a subfolder, repeat this step at the topology folder level.
Topology Folder Actions
Right-click the system root folder or a topology folder to open a context menu with the following commands.
EIO0000001114.15
EIO0000001114.15
Command Description
Expand The first time you click Expand , expands the next level in the folder structure or opens the folder/window.
The next time you click Expand , displays the folder structure or contents in its last expanded state.
If the folder is empty, the command has no effect.
Collapse Collapses the folder structure up to the folder or closes the folder/window.
The command is available only if the folder/window is already expanded.
Creates a topology folder or subfolder and displays it in the tree view.
Create
Folder
Open
Application
Opens the
Application Explorer , page 115
, which allows you to start the instantiation stage or access the application of the system.
The command is available from the root folder only.
Open
Project
Opens the Projects Explorer , which allows you to start the
Project Definition stage, page 199
or access the Control and Supervision projects of an existing system.
The command is available from the root folder only.
Creates an Ethernet network entity and displays it in the folder. The entity represents an Ethernet based network of the system.
Creates a station node entity and displays it in the tree view.
For example, a station node can represent a Supervision I/O server or a PC emulating simulator software.
Displays a submenu, which allows you to create a controller entity of the supported platforms (see EcoStruxure ™ Process Expert, Control Participant Services, User
Guide).
The topological entity allows you to configure devices, which represent the CPU, power supply, communication, I/O modules, extended and remote racks, and so on.
Creates an STB island entity and displays it in the tree view.
The topological entity represents the segments, communicator, STB island modules, and devices connected through the CANopen bus of the island once you have configured them.
Creates a PROFIBUS remote master (PRM) entity and displays it in the tree view.
The topological entity allows you to configure the decentralized devices (DPs) connected to the PRM by using device type managers (DTMs) and generic station description (GSD) files.
Opens a submenu containing the following commands:
• Modbus TCP
• EtherNet/IP
Selecting either command opens the Select Template dialog box, which lets you select and instantiate a topological template to create an I/O device entity. The topological entity is used to
manage communication, page 597
between such device and the controller by using Modbus TCP (I/O scanning and explicit) or EtherNet/IP
(explicit) messaging.
Delete
Updates the template that is used by entities inside the folder and any subfolder with the latest version of that template, which is available in the Global Templates library on the system server.
Opens the Export window, which allows you to select the topological entities that you want to export in the form of a topology export file (.sbk).
You can select entities contained in the folder and any subfolders along with their folder hierarchy.
The command is not available from empty topological folders.
Opens the Import window, which allows you to select an export file (.sbk). In a second step, you can select which compatible content of the export file you import in the topology.
Deletes the folder and its contents, including subfolders, their contents, and associated configurations.
The command is not available from the root folder.
367
Command Description
Rename Allows you to type a new folder name.
Properties
The command is not available from the root folder.
Opens the folder Properties window, which allows you to view and edit information of the folder.
The command is not available from the root folder.
Topology Folder Properties
To access the Properties window of the topology folder, right-click the folder and select Properties .
You can edit the following items.
Item
General Identifier
Description
Area
Description
Designation of the folder.
The identifier must be unique for each subfolder of the same parent folder and satisfy
.
Default value: Folder_n where n is an incremental number starting at 1.
Optional.
You can enter a description of the folder with free form text. The description you enter appears in a tooltip when you move the pointer over the folder.
Default value: Blank
Optional.
You can assign an access control number to the folder.
Value: 1...255 (integer).
Default value: Blank
Selecting Topological Templates
Overview
When you create a topological entity, the software displays the Select Template dialog box if more than 1 topological template is available to model a hardware module:
• When you first create the entity: For any module that you add in the Control
Participant.
• When you modify the entity: For modules that you have added or moved since you last configured the entity.
The Select Template dialog box allows you to select the topological template and version that you want to use among the compatible ones that are available.
NOTE: The
Update Templates command, page 407
is available from the context menu of entities after you create them.
Default Selection
By default, the software selects the topological template in the Global Templates library that has the highest version number with the usability state (see
EcoStruxure ™ Process Expert, Global Templates, Reference Manual) of
Approved or Deprecated among those that have a matching Hardware
Reference as attribute.
368 EIO0000001114.15
Selection for Redundant Controllers
When you select a topological template for a module of the primary controller of a redundant configuration, the software applies your selection automatically to the counterpart module of the standby controller.
Select Template Dialog Box
The table describes the fields of the Select Template dialog box and how to select templates.
Column Header Description
Hardware References Module hardware references and network type (see EcoStruxure ™
Process Expert, Global Templates, Reference Manual) for which a choice of topological templates is available.
Templates For each displayed hardware reference, indicates the identifier and version of the default topological template that the software will use to create the device.
• To select a different template: Click the default template to display the other available templates, select the template that you want to use, and click OK to confirm your selection.
• To cancel the configuration process and return to the Control
Participant window, click Cancel .
Using Configuration Change on the Fly (CCOTF)
Before Performing CCOTF Modifications
The CCOTF functionality of the Control Participant is enabled by default when you create a controller of the M580 or M580 safety platform in the Topology Explorer .
That is, the Online modification in RUN or STOP parameter of the CPU is selected.
It allows you to deploy compatible hardware configuration and parameter changes to the controller while it is running without impacting other modules or ongoing tasks.
Before performing a CCOTF-compatible modification, refer to the topics describing the CCOTF functionality in the
help of the Control Participant, page 69
for your specific controller platform and follow the recommendations that are given.
CCOTF with EcoStruxure Process Expert
In EcoStruxure Process Expert, CCOTF already comes into play when you configure a controller (offline) of the M580 or M580 safety platform in the
Topology Explorer to which you have already deployed a built Control project.
When CCOTF is enabled, the software informs you if a configuration or parameter change that you are about to make will require stopping the controller when you deploy changes to the controller later on during the deployment stage. That is, it must be built offline.
NOTE: If you configure drops of the S908 architecture or make changes to an existing drop of this architecture during configuration of the controller (offline), you must use the
and Deploy Built Project commands thereafter, which requires stopping the controller. To perform CCOTFcompatible configurations of drops of the S908 architecture, use the Refine
Online command instead.
NOTE: CCOTF is not supported for controllers of the M340 and Quantum platforms.
EIO0000001114.15
369
370
Enabling and Disabling CCOTF
By configuring the controller, you can disable or enable the Online modification in
RUN or STOP parameter in the Control Participant Configuration section of the
CPU.
If you have already deployed a built Control project to the controller, enabling or disabling the parameter will require that you deploy once to the controller by using the Deploy Built Project command. This requires stopping the controller.
Configuration Changes not Compatible With CCOTF
The following types of changes can be incompatible with CCOTF and require stopping the controller:
• A single change that is saved during controller configuration.
For example, adding a NOC communication module in the local rack of an
M580 controller.
• A series of changes of the same type, which exceeds the number of allowed consecutive changes in a same transaction.
For example, adding five digital input modules to the local rack of an M580 controller (the limit for CCOTF is four modules).
For details on the CCOTF limitations, refer to the Control Participant help on
CCOTF for each controller platform.
Working Principle
When you perform a series of CCOTF compatible changes, you can build the executable of the associated Control project in the Project Explorer between changes. The changes are still part of the same transaction. A transaction is executed and the CCOTF counter is reset when you use the Deploy Changes/
Undo Online Changes or Deploy Built Project command on the controller.
When the software detects that a configuration change will require stopping the controller, a dialog box opens. It gives you the choice to proceed with the change or cancel it. The following table describes the impact of either choice.
Action selected by the user
Yes
Impact on CCOTF
Cancel
Impact on future configuration changes
The configuration change is performed.
If you save the change when closing the
Participant configuration window, the
Deploy Changes/Undo Online
Changes command is disabled and deploying the change by using the
Deploy Built Project command requires stopping the controller.
NOTE: Closing the Participant configuration window without saving discards the change and CCOTF is still available.
NOTE: Undoing the CCOTFincompatible configuration change does not revoke the controller stop if you save your changes.
The configuration change is discarded and you can continue with the configuration of the controller.
You are not informed anymore if you make CCOTF-incompatible configuration changes until you deploy to the controller.
The Build command in the context menu of the executable is disabled. Only Build
All can be used.
You continue to be informed when you make a CCOTF-incompatible configuration change.
NOTE: Using the Deploy Built Project command also resets the CCOTF counter.
EIO0000001114.15
CCOTF in the System Engineering Life Cycle
The following table summarizes the main impact of the CCOTF functionality on the other stages of the system engineering life cycle. For details, refer to the description of each stage.
Stage
Refinement (offline)
Build
Deployment
Execution
Impact of CCOTF
When you perform a
change in the Control project, page 336
that is not
CCOTF-compatible, the software informs you ahead of time that it will require stopping the controller when you deploy changes later on.
Changes related to the topology that are CCOTF-compatible can be
by using the Build command.
Changes related to the topology that are CCOTF-compatible can be
by using the Deploy Changes/Undo Online
Changes command without stopping the controller.
If you have made a CCOTF-incompatible change, only the Deploy Built
Project command is available, which requires stopping the controller.
It is required to
with configuration changes that you have made online to be able to use the Deploy Changes/Undo
Online Changes command.
Configuring a Controller
Overview
Controller entities act as engines for executing Control projects that are defined in the Projects Explorer .
You proceed with the configuration of controller entities from within the Control
Participant, which then transfers the defined configuration to the controller entity of the Topology Explorer by using the appropriate topological templates.
If the software cannot find the corresponding template for a hardware module, it uses the $UnknownModule template. Hardware modules that are modeled with this template do not appear in the Hardware Mapping editor.
NOTE: For additional information on configuring M580 safety controllers, refer to the topic describing the
engineering of M580 safety systems, page 577
.
Virtual Machine Usage
The configuration of one controller entity uses up one session of the Control
Participant of the virtual machine (see EcoStruxure ™ Process Expert, Installation and Configuration Guide).
Device DDTs of Topological Entities
When you add a module to a controller entity, which uses a device type manager
(DTM) (for example, an M580 CPU, a NOC communication module, or a HART analog I/O module), the software automatically creates the corresponding device
DDT. Such variables exist only in the configuration that you can access from the
Topology Explorer and are integrated to the Control Participant project during build.
However, you can
create certain device DDTs, page 343
in a Control Participant project during refinement.
Redundant Controllers
Typically, for redundant controllers that are configured in the topology, only the entity identifier or the identifier of the primary engine is used at the platform level to identify them (for example, in the Physical Connections dialog box when you connect the controller to an Ethernet network). The standby engine is implicitly
EIO0000001114.15
371
372
included. If the standby engine needs to be dealt with explicitly (for example, for deployment tasks), it is identified separately.
Creating a Controller Entity
To create the controller entity, which will contain the controller configuration
(devices), proceed as follows.
Step
1
Action
Right-click the system root folder or a topology folder in the Topology Explorer , select
Create Controller , and select a controller platform.
Result: The controller
is created and displayed in the tree view.
Controller Actions
Right-click the controller entity to open a context menu with the following commands.
Command
Description
Opens the Control Participant, which allows you to configure the controller hardware, in-rack modules, drops, and communication services.
Opens the Physical Connections window, which allows you to connect or disconnect communication modules of the controller that support Ethernet to existing Ethernet networks to represent physical connections to such networks.
Opens the Update Template dialog box, which allows you to update the templates that are used by controller entities with the highest available version of the Global Templates library on the system server.
Opens the Deploy Built Project dialog box, which lets you select a built
Control Participant project and deploy it entirely to the controller.
It can also be used to remove refinements made online.
Deploys to the controller the differences between the deployed Control
Participant project and the corresponding built Control Participant project.
Lets you deploy once again the entire built Control Participant project that you had deployed to the controller last.
The command is available only if you had executed the Deploy Built Project command previously on the controller.
Opens the Deploy Data dialog box in which you can select a controller data backup file that has been created by using the Back Up Data command. It lets you deploy the data contained in the file to the controller.
The command available only if you have deployed a built Control Participant project to the controller.
Starts the execution of the participant project by the controller.
Stops the execution of the participant project by the controller.
Lets you modify the deployed Control Participant project online.
Lets you synchronize the standby controller with the primary one.
The command is available only for redundant controllers.
Updates the logical Control Participant project that is associated to the deployed Control Participant project with the changes that you have made to the deployed project online by using the Refine Online command.
It also requires that you update the controller configuration with hardware changes that you have made during online refinement.
Opens the Back Up Data dialog box, which lets you configure the data that you want to back up and create a controller data backup file.
The command available only if you have deployed a built Control Participant project to the controller.
EIO0000001114.15
EIO0000001114.15
Command
Manage
Password
Clear Password
Description
Opens the Manage Password dialog box, which lets you set and modify the
and/or the
password.
Each command is available only if the corresponding property is enabled in the properties of the controller.
Opens the Clear Password dialog box, which lets you remove the
of the deployed Control Participant project and/or the
password.
Each command is available only if you have set the corresponding password.
Forgot
Password
Opens the Forgot Password dialog box, which contains an authentication code that you need to reset the forgotten
or
password.
Deletes the controller entity including controller devices and related configurations.
NOTE: For M580 safety controllers, deletes also the
associated M580 safety Control project, page 579 .
Rename Lets you change the identifier of the controller entity.
Opens the Export window, which allows you to export the entity and its folder hierarchy in the form of a topology export file (.sbk).
Properties Opens the Properties window in which you can view and edit properties of the controller entity.
NOTE: To view properties of the controller devices representing the hardware modules, refer to
Controller Representation, page 377
.
Controller Properties
Right-click the controller entity and select Properties to open the Properties window in which you can view and edit its properties.
Item
General Identifier
Description
Area
Hot Standby
(1)
ControllerExist
Description
The identifier must be unique within the system and satisfy
.
The entity identifier becomes part of the name of the devices that the software creates inside in the entity:
• Folders ( identifier field)
• Devices ( $Name parameter)
The identifier (or part of it) is also used to create the name of the DTM if it is added during build when the controller is acting as server for
peer to peer communication, page
.
Optional.
You can enter a description of the controller with free form text. The description you enter appears in a tooltip when you move the cursor over the entity.
Default value: Blank
Optional.
You can assign an access control number to the controller entity.
Range: 1...255 (integer)
Default value: Blank
• PrimaryAndStandby : Select this value when both the primary and the standby controllers are physically present and connected by a Hot Standby cable link (default value).
• Primary : Select this value when either of the following applies:
◦ Only the primary controller is physically present.
◦ Both the primary and the standby controllers are physically present but not connected by a
Hot Standby cable link.
373
374
Item
Controller
Family
CpuVersion
$Name of communication module (2)
$Name of communication module (2)
Password
Protection
Value
CpuVersion
Controller
Description
The value has an impact on the behavior during
deployment and execution, page 481
.
Indicates the hardware platform that the controller belongs to.
Read-only.
Indicates the firmware version of the CPU module that is configured.
The read-only property is displayed only after you save the controller configuration.
ServerMemoryStart Holding register address (%MW) for peer to peer data.
(Integer)
Default value: Blank
You can only enter an
for this parameter (for example, 1, 5, 11).
For more information, refer to
O Scanner Parameters, page 376 .
ServerMemory-
Length
Holding register size for peer to peer data.
(Integer)
Default value: Blank.
NOTE: The available memory length is
ServerMemoryLength - 1 because 1 word is reserved to move the channel address for managing the
for peer to peer communication across Modicon M340, M580, and
Quantum platforms.
For more information, refer to
O Scanner Parameters, page 376 .
ClientMemoryStart
(3)
Holding register address (%MW) for I/O scanning.
(Integer)
Default value: Blank.
For more information, refer to
O Scanner Parameters, page 376 .
ClientMemory-
Length (3)
Holding register size in words for I/O scanning
(Integer)
Default value: Blank.
For more information, refer to
O Scanner Parameters, page 376 .
Lets you
manage password protection, page 488
for deployment and execution operations performed on the controller.
• Enabled : Enables password protection.
• Disabled : Disables password protection after you confirm the selection.
By default, the value is set according to the value of the
Optional Security Services By Default
, which is set at the system level.
Default value: Enabled once you configure the controller.
NOTE: To disable the property once you have deployed a Control Participant project with the property set to Enabled , you need to enter the current password, which also clears it.
On the other hand, if you had already deployed a
Control Participant project while the property was set to Disabled , you can enable it and set a password for the already deployed Control project.
EIO0000001114.15
EIO0000001114.15
Item
Safety
Description
The property is available only for M580 safety controllers and lets you
manage safe area password protection, page 588 .
• Enabled (default): Makes the use of a password mandatory when performing operations on the safety configuration and/or safety program of the controller.
• Disabled : Disables password protection after you confirm the selection.
To disable password protection when a password is set, you must enter it. This also clears the password.
(1) The section is displayed only for redundant controller configurations.
(2) The section is displayed when the software has completed the configuration process. A section is displayed for each communication module that you have configured with an IP address in the Control Participant by using the Configure command. The server properties are displayed for CPU modules only.
(3) The client properties are displayed for communication modules, including the
CPU module when the I/O scanner service is enabled. They are not displayed for controllers of the Modicon M580 platform and NOC communication modules.
NOTE: To view properties of the controller devices representing the hardware modules, refer to
Controller Representation, page 377
.
Configuring the Controller
To configure the controller, proceed as follows.
Step
1
2
3
Action
Right-click the controller entity in the Topology Explorer and select Configure .
Result: The Control Participant opens
and maximized.
Proceed with the configuration of the controller inside the Control Participant.
For more information about configuring the controller and working inside the Control
Participant, refer to the Control Participant Services User Guide (see EcoStruxure ™
Process Expert, Control Participant Services, User Guide).
Click the save button in the toolbar of the Participant window.
4
Result: The software saves the changes in the configuration file and transfers the configuration to the Topology Explorer . It may display the
dialog box.
NOTE: If the software detects a configuration issue, it displays a notification, which allows you to change the configuration until you are able to save it.
Close the Control Participant window.
NOTE:
If you change the configuration and you click the close button on the outer frame of the Participant window without saving your changes first, the software displays the
Save Configuration dialog box where you can click the following:
Yes , to save the changes in the configuration file and close the Participant window.
No , to discard your changes and close the Participant window.
Cancel , to leave the Participant open without saving your changes.
Changing the Controller Configuration
To change the configuration of a controller, follow the procedure to configure a controller, and proceed with the changes inside the Control Participant.
375
376
If the controller is mapped to at least 1 executable, saving changes to communication functions that you made from within the Control Participant may delete the existing
communication mapping, page 424
and
of this executable.
In such case, the software displays a notification asking you to confirm the change. Make either selection:
• OK : To save the change to the configuration file of the controller and delete the associated communication and hardware mappings.
• Cancel : To keep the Control Participant window open. Unsaved changes are not discarded
For more information, refer to Configuring the Controller (see EcoStruxure ™
Process Expert, Control Participant Services, User Guide).
Configuring the Controller I/O Scanner Parameters
To use the I/O scanner of the controller and define communication channels between the CPU and/or communication modules and devices connected to the same Ethernet network, configure the read/write zones once the software has completed the configuration process to transfer the controller configuration to the
Topology Explorer .
The software configures the related parameters of the devices representing the
CPU/communication modules and exposes the data in the Communication
Mapping Editor window during the
communication mapping, page 424 .
If you configure overlapping client and server memory areas for a controller and map variables to these overlapping addresses, build does not complete successfully and the software displays a message to inform you.
These settings are an example of values entered in the Properties window of a controller that result in overlapping memory areas:
• ServerMemoryStart : 1
• ServerMemoryLength : 100
• ClientMemoryStart : 51
• ClientMemoryLength : 150
For more information on configuring parameters for I/O scanning, refer to the
Control Participant help.
NOTE: If you reduce the value of the
that is reserved in the client and/or server memory while peer to peer communication channels exist in the controller and you have already built the associated logical Control
Participant project, verify that the new register size meets the requirements of the project. You cannot build the project if the free memory value becomes negative.
NOTE: When you modify a parameter of the client and/or server memory reserved for communication channels and you have already deployed the associated built Control Participant project, you can only apply the change to the engine by using the
Deploy Built Project , page 514
command, which requires stopping the controller. You cannot use the Deploy changes command.
To configure the I/O scanner parameters of the controller, proceed as follows.
Step
1
2
3
Action
In the Topology Explorer , right-click the controller folder and select Properties .
Enter a value in the appropriate fields of the
of the CPU and/ or communication module that you want to use for I/O scanning.
Click the close button to close the Properties window.
EIO0000001114.15
NOTE: For controllers of the Quantum platform configured with a NOC communication module and acting as client, configure the memory size of the
NOC (see EcoStruxure ™ Process Expert, Control Participant Services, User
Guide) by using the Control Participant.
Controller Representation
The Topology Explorer allows you to view the topological devices representing the following hardware components of the controller entity once you have configured it:
• Racks
• Buses
• Power supplies
• CPUs
• Communication modules
• I/O modules
It lets you also view and configure their
.
The following figure shows the representation of a controller entity based on the
Modicon M580 platform with a local rack and one Ethernet RIO drop.
EIO0000001114.15
1 Controller folder representing the controller
2 Controller local bus folder
3 Controller local rack folder
4 Controller local rack module folder
5 Devices modeling the rack, power supply, CPU, communication modules, and I/
O modules of the local rack
6 EIO bus folder
7 EthRIO rack folder
8 EthRIO drop folder
9 Devices modeling the rack, CRA module, and I/O modules of the EthRIO drop
Devices are identified by the $Name parameter, which uses the format <Entity identifier> <Bus number>:<Designation> <Drop number>:D <Rack number>:R
<Position on rack>:<Commercial reference>.
<Designation> is either:
• Local for the local bus of controller platforms that do not support a redundant configuration.
• PriLocal or SecLocal for the local bus of controller platforms that support a redundant configuration. If a standalone controller is configured, the local bus designation is PriLocal .
• EthRIO for the EIO bus of any controller platform supporting remote drops.
377
In this example, the highlighted row in the following figure represents a
BMXDDI1603 digital input module located in position 3 of the local rack of
Controller_1.
In this example, the highlighted row in the following figure represents a
BMXAMO0210 analog output module located in position 2 of the second remote drop of Controller_1.
378
NOTE: For CPUs of the Modicon M580 platform that have an embedded RIO scanner service:
• The parent folder with the name <Entity identifier> <Bus number>: EthRIO is created by default. The folder and the device it contains represent the
RIO scanner service. The status of the device remains invalid until you configure at least one RIO drop.
• The <Entity identifier> <Bus number>: EthRIO device appears in the
Physical Connections
even if you have not yet configured a RIO drop. It is associated to IP Address A of the CPU module. In case of a redundant controller, it also implicitly represents the
RIO scanner service of the CPU designated as B and is associated to IP
Address B .
Properties of Modules
Expand the topological entity folder, right-click a device, and select Properties to open the Device Editor , which lets you view some of its parameters without the need to open the Control Participant. For example:
• Its reference
• Its position on the rack
• IP addresses, ports, and other module-specific communication parameters
• Physical interface links with Ethernet networks
• Implicit connections within the entity
Deleting a Controller Entity
When you select the Delete command for a controller entity, the software notifies you if it detects any of the following:
• Any mappings.
• Any physical interface link with an Ethernet network.
EIO0000001114.15
Once you have confirmed the delete command, the software deletes the following components of the controller entity:
• Physical interface links
• The controller entity, subfolders, and devices contained therein
• The corresponding Control Participant configuration project, including:
◦ Any mapping information
◦
Peer to peer communication channels, page 433
◦ Any deployed Control Participant project related to the engine
To delete the controller entity and its contents, proceed as follows.
Step
1
2
Action
Right-click the controller entity in the Topology Explorer and select Delete .
Result: A dialog box opens.
Verify the information that is displayed and click OK to proceed.
Result: The software deletes the controller entity and its contents, and displays a confirmation message in the notification panel.
Configuring a Station Node
Overview
The station node is a topological entity, which represents the hardware (for example, network interface cards (NICs)) and software (for example, Supervision servers and clients, OPC Factory Server or OPC UA Server Expert) that is installed on a computer workstation, which is connected to the Ethernet control network.
Station nodes act as engines for executing:
• Deployed Supervision projects.
• Deployed Control projects running in an
.
For example, station nodes represent operator stations and operation servers.
You create station node entities in the Topology Explorer and define their devices from the station node folder representing the entity.
Creating a Station Node Entity
To create a station node entity, proceed as follows.
Step
1
Action
Right-click the system root folder or the topology folder in the Topology Explorer and select Create Station Node .
Result: The software creates a station node
and displays it in the tree view.
NOTE: By default, the software creates a Network Interface Card (NIC) device when you create a station node entity. To display the NIC device, open the station node entity folder.
NOTE: The software may display the
dialog box.
Station Node Actions
Right-click the station node folder to open a context menu with the following commands.
EIO0000001114.15
379
380
Command
Create
Supervision
Service
Create OFS
Create Control
Service
Control
Supervision
Delete
Rename
Description
Creates an NIC device and displays it in the station node folder.
The NIC provides connectivity to the Ethernet network through the
dialog box.
Creates a Supervision service instance and displays it in the station node folder.
It lets you select the station node in the
so that you can deploy a Supervision project to it.
Create the service in the stations nodes on which the I/O (1) , Alarm, Trend, and
Report servers as well as the Supervision clients are installed.
You can create one Supervision service per station node.
Right-click the service and select Properties to access its
.
(1) May also require an OFS service.
Creates a protocol-independent OFS service instance and displays it in the station node folder.
Create the service in the station node on which the I/O server and OPC
Factory Server or OPC UA Server Expert are installed. It is required to map the station node to the IOServer service of the Supervision project in the
and to deploy the corresponding
to the station node.
You can create one OFS service per station node.
Right-click the service and select Properties to access its
.
NOTE: Requires also a Supervision service.
NOTE: The OFS service is not required to perform the service mapping with the IOServer service when the OPCUA Embedded protocol is
for all the tag containers associated to the same I/O server.
Creates a Control Expert service instance and displays it in the station node folder.
It allows you to:
•
a built Control Participant project to software emulating a simulator that is running on the computer.
• Select the station node to which you have deployed a Control project in the
communication mapping, page 460 . It lets you use it as data source
(I/O device) for simulating Supervision runtime services.
You can create one ControlExpert service per station node.
Right-click the service and select Properties to access its
.
Opens the Physical Connections window, which allows you to connect or disconnect the station node, through its NIC, to existing Ethernet networks to represent physical connections to such networks.
Opens the Update Template dialog box, which allows you to update the templates that are used by station node entities with the highest available version of the Global Templates library on the system server.
Opens a submenu containing deployment and execution commands.
Opens a submenu that contains the following commands:
• Deploy Built Project : Lets you select a built Supervision Participant project and
deploy it to the station node, page 523
.
The command is available only if you have created the necessary service in the station node, mapped an executable to the station node, and built it.
• Deploy Changes : Lets you
deploy a limited number of changes, page
to the station node.
The command is available only if you have already deployed the built
Supervision Participant project to the station node and if the number and type of changes are supported.
Deletes the station node entity including services and related configurations.
Lets you change the identifier of the station node entity.
EIO0000001114.15
Command Description
Opens the Export window, which allows you to export the entity and its folder hierarchy in the form of a topology export file (.sbk).
Properties Opens the Properties window in which you can view and edit properties of the station node entity.
The following table describes the commands of the Control submenu. Commands in this submenu are available only if you have created the necessary service in the station node, mapped an executable to the station node, and built it. Additional availability conditions may apply; refer to the description of each command.
Command
Deploy Built
Project
Description
Opens the Deploy Built Project dialog box, which lets you select a built
Control Participant project and
deploy it to the station node, page 481
.
Lets you deploy to the station node the differences between the deployed
Control Participant project and the corresponding built Control Participant project.
It can also be used to remove changes made online.
Lets you deploy once again the entire built Control Participant project that you had deployed to the station node last.
The command is available only if you had executed the Deploy Built Project command previously on the station node.
Opens the Deploy Data dialog box in which you can select a controller data backup file that has been created by using the Back Up Data command. It lets you deploy the data contained in the file to the simulator running in the station node.
The command available only if you have deployed a built Control Participant project to the station node.
Starts the execution of the deployed Control Participant project in the simulator.
Stops the execution of the deployed Control Participant project in the simulator.
Lets you change the deployed Control Participant project online.
Manage
Password
Clear Password
Lets you update the logical Control Participant project that is associated to the deployed Control Participant project with the changes that you have made to the deployed project online by using the Refine Online command.
Opens the Back Up Data dialog box, which lets you configure the data that you want to back up and create a controller data backup file.
The command available only if you have deployed a built Control Participant project to the station node.
Opens the Manage Password dialog box, which lets you
a password for deployment and execution operations performed on the simulator and modify it.
The command is available only if the Simulator password property is set to
Enabled .
Opens the Clear Password dialog box, which lets you
the application password of the deployed Control Participant project.
The command is available only if you have set a password.
Parameter
General Identifier
Description
Station Node Properties
Right-click the station node folder and select Properties to open the Properties window in which you can view and edit the station node properties.
Description
The identifier must be unique within the system and satisfy
.
Optional.
EIO0000001114.15
381
Parameter
Control
Expert
Area
Computer Name
Password
Protection
Simulator
Supervision TCP Port
Description
You can enter a description of the station node with free form text. The description you enter appears in a tooltip when you move the cursor over the entity.
Default value: Blank
Optional.
You can assign an access control number to the station node entity.
Range: 1...255 (integer)
Default value: Blank
Optional.
The value is applied to the Computer property in the Network Addresses table of the Supervision Participant project when you build its executable.
The value is required, for example, when you are using encryption with
Supervision.
Default value: Blank
The property is available only once you create a ControlExpert
Lets you
manage password protection, page 488
for deployment and execution operations performed on the simulator.
• Enabled : Enables password protection.
• Disabled : Disables password protection after you confirm the selection.
By default, the value is set according to the value of the Optional Security
Services By Default
property, page 107 , which is set at the system level.
Default value: Enabled .
NOTE: To disable the property once you have deployed a Control
Participant project with the property set to Enabled , you need to enter the current password, which also clears it.
On the other hand, if you had already deployed a Control Participant project while the property was set to Disabled , you can enable it and set a password for the already deployed Control project.
Configure the value to be the same as TCP Listening Port of the OPCUA server that is installed on the station node.
The value is used in the
only when Protocol of the associated tag container is set to OPCUA .
Valid range: 49152 (default) to 65535.
The parameter is available only for station nodes in which an OFS service has been created.
Creating a Network Interface Card (NIC)
To create an NIC device, proceed as follows.
Step
1
Action
Right-click the station node entity in the Topology Explorer and select Create NIC .
Result: The software opens the station node folder and displays the NIC device.
NOTE: The software may display the
dialog box.
NIC Actions
Right-click the NIC device to open a context menu with the following commands.
382 EIO0000001114.15
EIO0000001114.15
Command
Delete
Rename
Properties
Description
Opens the Update Template dialog box, which allows you to update the template that is used by NIC devices with the highest available version of the
Global Templates library on the system server.
deletes the NIC device including related configurations.
allows you to change the identifier of the NIC.
opens the Properties window in which you can view and edit properties of the
NIC.
NIC Properties
Right-click the NIC device and select Properties to open the Device Editor , which lets you view and edit its parameters.
Parameter
$System
NIC Parameters
PhysicalInterface-
LinkX (1)
$Name
Description
The identifier must be unique within the system and satisfy
.
Default value: NIC_n where n is an incremental number starting at 1.
$Description Optional.
You can enter a description of the NIC with free form text.
$Area
IPAddress
Default value: Blank
Optional.
You can assign an access control number to the NIC.
Range: 1...255 (integer)
Default value: Blank
IP address of the NIC on the Ethernet network.
The default IP address of the NIC that is created when you create the station node is 127.0.0.1
, which corresponds to the local host. For additional NICs that you create manually, the default value is blank.
NOTE: For station nodes on which you install software emulating a simulator, enter the
that is displayed by the simulator software running on the station node.
Subnet Mask Subnet mask that is used to define IP addresses on the
Ethernet network that the NIC belongs to.
Destination
Instance
Role
Interface
Default value: Blank
Indicates to which Ethernet network the NIC is connected.
Indicates the identifier of the role of the interface.
Indicates the identifier of the interface that the NIC device exposes for connection to the Ethernet network.
(1) The section is displayed if you have
the station node through its NIC to an Ethernet network of the system. The parameters are not editable.
X represents the number of the physical interface link, which is an incremental number starting at 1.
Station Node Service Actions
Right-click an OFS , ControlExpert, or Supervision service instance to open a context menu with the following commands.
383
Command
Delete
Rename
Properties
Description
Opens the Update Template dialog box, which allows you to update the template that is used by the instance with the highest available version of the
Global Templates library on the system server.
Deletes the instance including related configurations.
Lets you change the identifier of the instance.
Opens the Properties window in which you can view and edit properties of the instance.
Station Node Service Properties
Right-click an OFS , ControlExpert, or Supervision service instance and select
Properties to open the Device Editor , which lets you view and edit its parameters.
Parameter
$System $Name
Description
Identifier of the service, which must be unique within the system and satisfy
.
$Description Optional.
You can enter a description of the instance with free form text.
$Area
Default value: Blank
Optional.
You can assign an access control number to the instance.
Range: 1...255 (integer)
Default value: Blank
Configuring an STB Island
Overview
The topological entity represents an STB island that communicates with the controller through I/O scanning. It contains:
• Modules
• CANopen extensions
• HART devices
The STB island acts as a server.
You configure STB island entities from within the Control Participant, which then transfers the defined configuration to the STB island entity of the Topology
Explorer by using the appropriate topological templates.
If the software cannot find the corresponding template for a hardware module, it uses the $UnknownModule template. Hardware modules that are modeled with this template do not appear in the Hardware Mapping editor.
Virtual Machine Usage
The configuration of one STB island entity uses up one session of the Advantys
Configuration Software (ACS) Participant of the virtual machine (see
EcoStruxure ™ Process Expert, Installation and Configuration Guide).
384 EIO0000001114.15
EIO0000001114.15
Creating an STB Island Entity
To create the STB island entity, which will contain the STB island configuration
(devices), proceed as follows.
Step
1
Action
Right-click the system root folder or a topology folder in the Topology Explorer and select Create STB Island .
Result: The software creates an STB island entity and displays it in the tree view.
STB Island Actions
Right-click the STB island entity to open a context menu with the following commands
Command
Configure
Description
Opens the Control Participant, which allows you to configure hardware, such as modules of the STB island, devices connected through the CANopen bus, and communication modules.
Opens the Physical Connections window, which allows you to connect or disconnect the STB island to existing Ethernet networks to represent physical connections to such networks.
Opens the Update Template dialog box, which allows you to update the templates that are used by STB island entities with the highest available version of the Global Templates library on the system server.
Opens the Export window, which allows you to export the entity and its folder hierarchy in the form of a topology export file (.sbk).
Deletes the STB island entity including its devices and related configurations.
Rename Allows you to change the identifier of the STB island entity.
Properties Opens the Properties window in which you can view and edit properties of the
STB island.
NOTE: To view the parameters of the devices representing the hardware modules of the STB island, refer to
STB Island Representation, page 387 .
STB Island Properties
Right-click the STB island entity and select Properties to open the Properties window in which you can view and edit its properties.
Item
General Identifier
Description
Area
Description
The identifier must be unique within the system and satisfy
.
The folder identifier becomes part of the name of the items that the software creates inside in the entity:
• Subfolders ( identifier field)
• Devices ( $Name parameter)
The identifier (or part of it) is also used to create the name of the DTM if it is added during
Optional.
You can enter a description of the STB island with free form text. The description you enter appears in a tooltip when you move the pointer over the entity.
Default value: Blank
Optional.
You can assign an access control number to the STB island entity.
Range: 1...255 (integer)
Default value: Blank
385
386
Item
Identifier
<communication module
ID> (1)
IPAddress
Subnet Mask
Description
IP address of the communication module of the STB island on the Ethernet network.
Default value: Blank
Subnet mask that is used to define IP addresses on the
Ethernet network that the communication module of the STB island belongs to.
Default value: Blank
(1) The section is displayed once you have closed the Participant window and saved changes.
NOTE: To view the parameters of the devices representing the hardware modules of the STB island, refer to
STB Island Representation, page 387
.
Changing STB Island Properties
Modifying the IP address or subnet mask of an STB island, may delete the
communication mapping, page 424
that exists with this STB island.
In such case, the software displays a notification asking you to confirm the change. Make either selection:
• Yes : To save the change to the properties of the STB island and delete the associated communication mapping.
• No : To discard your changes.
Configuring the STB Island
To configure the STB island, proceed as follows.
Step
1
2
3
Action
Right-click the STB island folder in the Topology Explorer and select Configure .
Result: The Control Participant opens
and maximized.
Proceed with the configuration of the STB island.
For more information about configuring the STB island and working inside the Control
Participant, refer to the Control Participant Services User Guide (see EcoStruxure ™
Process Expert, Control Participant Services, User Guide).
Click the close button in the toolbar of the Participant window.
4
5
6
Result: The software saves the changes in the configuration file, closes the Control
Participant window, and transfers the configuration to the Topology Explorer . It may display the
dialog box.
NOTE: If the software detects a configuration issue, it displays a notification, which allows you to change the configuration until you are able to save it.
NOTE:
If you click the close button on the outer frame of the Participant window, the software displays the Configuration dialog box where you can click the following:
• Yes to save the changes in the configuration file and close the Participant.
• No to discard your changes and close the Participant.
• Cancel to leave the Participant open without saving your changes.
Right-click the STB island entity and select Properties .
Enter the IP address and the subnet mask of the STB island.
Close the Properties window.
NOTE: To change the configuration of an STB island, follow the procedure to configure the STB island, and make the changes inside the Control
Participant.
EIO0000001114.15
Configuring Communication Between Controller and STB
Island
Refer to
Communicating with STB Islands Through Modbus TCP, page 600
for details about implementing communication by using the I/O scanner of the controller.
STB Island Representation
The Topology Explorer displays the devices representing the following hardware components of the STB island entity once you have configured it:
• Segments
• Bus
• Power supply
• CPU
• Communication modules
• I/O modules
• Devices connected through the CANopen fieldbus
It lets you also view and configure their
.
The following figure shows the representation of an STB island entity with a device connected through the CANopen fieldbus:
EIO0000001114.15
1 STB island folder representing the STB island entity
2 STB island bus folder containing the bus device (expanded view)
3 STB island drop folder
4 STB island rack folder containing the devices modeling the STB island modules:
Power supply, I/O modules, NIM, CANopen extension module, termination plate
(expanded view)
5 STB island CANopen fieldbus folder containing the CANopen fieldbus device
(collapsed view)
6 STB island drop folder containing the devices modeling the devices connected to the CANopen fieldbus of the Island (collapsed view)
Deleting an STB Island Entity
When you select the Delete command for an STB island entity, the software notifies you if it detects any physical or mapping interface links with any device that is contained in the STB island folder that you want to delete.
387
Once you have confirmed the delete command, the software executes the following actions in relation to the devices that are being deleted:
• Interface links are deleted.
• The STB island folder, subfolders, and device contained therein are deleted
• The associated STB island profile is deleted.
To delete the STB island entity and its contents, proceed as follows.
Step
1
2
Action
Right-click the STB island entity in the Topology Explorer and select Delete .
Result: A notification dialog box opens.
Verify the information that is displayed and click OK to proceed.
Result: The software deletes the STB island entity and its contents and displays a confirmation message in the notification panel.
Configuring a PROFIBUS Remote Master and Decentralized Peripherals
Overview
The software allows you to model PROFIBUS remote masters (PRMs) and their decentralized peripherals (DPs), which communicate with supported controller platforms through I/O scanning.
You proceed with the configuration of PRM and DPs from within the Control
Participant by using the default device type managers (DTMs) or generic station description (GSD) files that are installed in the virtual machine. Thereafter, the software transfers the defined configuration to the entity of the Topology
Explorer by using the appropriate topological templates.
If the software cannot find the corresponding topological template for a DP, it uses the $GenericPBSlave template. DPs that are modeled with this template use a generic mapping interface that is available in the Hardware Mapping
.
NOTE: You can install additional DTMs and GSD files in the Control
Participant by using the Extensions section (see EcoStruxure ™ Process
Expert, Installation and Configuration Guide) of the System Server
Configuration Wizard .
Virtual Machine Usage
The configuration of one PRM entity uses up one session of the Control
Participant of the virtual machine (see EcoStruxure ™ Process Expert, Installation and Configuration Guide).
Creating a PRM Entity
To create the PRM entity, which will contain the PRM and DP configuration
(devices), proceed as follows.
Step
1
2
3
Action
Right-click the system root folder or a topology folder in the Topology Explorer , select
Create PRM Profibus DP .
Result: The software creates a PRM entity and displays it in the tree view.
Right-click the PRM entity and select Properties .
Result: The Properties window of the PRM entity opens.
Select the controller platform that the PRM is communicating with in the menu of the
ControllerFamily
Result: When you
configure the PRM entity, page 390 , the software loads the
corresponding base configuration.
388 EIO0000001114.15
EIO0000001114.15
PRM Actions
Right-click the PRM entity to open a context menu with the following commands.
Command
Description
Opens the Control Participant, which allows you to configure the PRM and DPs by using DTMs and/or GSD files.
Opens the Physical Connections window, which allows you to connect or disconnect the PRM to existing Ethernet networks to represent physical connections to such networks.
Opens the Update Template dialog box, which allows you to update the templates that are used by PRM entities with the highest available version of the Global Templates library on the system server.
Opens the Export window, which allows you to export the entity and its folder hierarchy in the form of a topology export file (.sbk).
Deletes the PRM entity including DPs and related configurations.
Rename Allows you to change the identifier of the PRM entity.
Properties Opens the Properties window in which you can view and edit properties of the
PRM entity.
NOTE: To view the parameters of the PRM devices representing the hardware modules, refer to
PRM Representation, page 390 .
PRM Properties
Right-click the PRM entity and select Properties to open the Properties window in which you can view and edit the properties of the PRM entity.
Item
General
Controller
Family
Identifier
Description
Area
ControllerFamily
Description
The identifier must be unique within the system and satisfy
The entity identifier becomes part of the name of the devices that the software creates inside in the entity:
• Folders ( identifier field)
• Devices ( $Name parameter)
The identifier (or part of it) is also used to create the name of the DTM if it is added during
.
NOTE: The identifier is not propagated to the PRM
DTM ( Alias name ) in the Control Participant.
Optional.
You can enter a description of the PRM with free form text. The description you enter appears in a tooltip when you move the pointer over the entity.
Default value: Blank
Optional.
You can assign an access control number to the PRM entity.
Range: 1...255 (integer)
Default value: Blank
Indicates the hardware platform of the controller that the
PRM communicates with through I/O scanning.
The value needs to correspond to the family of the controller that you select in the
of the executable of the Control Participant project.
Possible values:
• M340/M580
• Quantum
Default value: Quantum
389
390
NOTE: To view the parameters of the PRM devices representing the hardware modules, refer to
PRM Representation, page 390 .
Configuring the PRM and its DPs
To configure the PRM and its DPs, proceed as follows.
Step
1
2
3
Action
Right-click the PRM entity in the Topology Explorer and select Configure .
Result: The Control Participant opens
and maximized.
Proceed with the configuration of the PRM and its DPs inside the Control Participant.
For more information, refer to the topic describing the configuration of the PRM and DPs
(see EcoStruxure ™ Process Expert, Control Participant Services, User Guide).
Click the save button in the toolbar of the Participant window.
4
Result: The software saves the changes in the configuration file and transfers the configuration to the Topology Explorer . It may display the
dialog box.
NOTE: If the software detects a configuration issue, it displays a notification, which allows you to change the configuration until you are able to save it.
Close the Control Participant window.
NOTE:
If you change the configuration and you click the close button on the outer frame of the Participant window without saving your changes first, the software displays the
Save Configuration dialog box where you can click the following:
• Yes to save the changes in the configuration file and close the Participant window.
• No to discard your changes and close the Participant window.
• Cancel to leave the Participant open without saving your changes.
Changing the PRM Configuration
To change the configuration of a PRM, follow the procedure to configure a PRM, and proceed with the changes within the Control Participant.
Saving changes to communication functions that you made within the Control
Participant, may delete existing
communication mappings, page 424
of the PRM.
In such case, the software displays a notification asking you to confirm the change. Make either selection:
• OK : To save the change to the configuration file of the PRM and delete the associated communication mapping.
• Cancel : To keep the Control Participant window open. Unsaved changes are not discarded.
For more information, refer to
.
PRM and DP Representation
The Topology Explorer allows you to view the topological devices representing the following components of the PRM entity once you have configured it:
• PROFIBUS fieldbus
• PRM master
• PROFIBUS DPs
It lets you also view and configure their
EIO0000001114.15
The following figure shows the representation of a PRM master configuration with one DP communicating with a Quantum controller.
1 PRM folder representing the PRM entity
2 PROFIBUS bus device
3 PRM device
4 DP device
Deleting a PRM Entity
Once you confirm the delete command, the software deletes the following components of the PRM entity:
• Physical interface links
• The PRM entity, subfolders, and devices contained therein
• The corresponding Control Participant configuration project, including:
To delete the PRM entity and its contents, proceed as follows.
Step
1
2
Action
Right-click the PRM entity in the Topology Explorer and select Delete .
Result: A notification dialog box opens.
Verify the information that is displayed and click OK to proceed.
Result: The software deletes the PRM entity and its contents, and displays a confirmation message in the notification panel.
Configuring Modbus TCP and EtherNet/IP Devices
Overview
The Topology Explorer lets you select and instantiate the topological template of devices that communicate with the controller by using either:
• Modbus TCP implicit (I/O scanning) or explicit messaging.
• EtherNet/IP explicit messaging.
Each template creates an I/O device topological entity.
There are two types of I/O device templates:
• Templates that are specific to a Schneider Electric device (see EcoStruxure ™
Process Expert, Device Templates User Guide) (for example, $EATV32HW) , which models an Altivar 32 speed drive).
• Generic templates (for example, $EIPGenericDeviceHW ), which let you model devices for which no specific template is available. For generic
Modbus TCP templates, select one that creates the required number of I/O scanner lines.
Alternatively, instances of the $EGenericDeviceHW template can act as gateways when you implement monitoring of Modbus serial device data directly
from the Supervision infrastructure, page 639 .
EIO0000001114.15
391
Selecting Topological I/O Device Templates
The Select Template dialog box displays templates of the Global Templates library that meet the following criteria:
• Type : Topological
• SubType : Device-I/O
• Usability State (see EcoStruxure ™ Process Expert, Global Templates,
Reference Manual): Approved or Deprecated
The following figure shows an example of the Select Template dialog box for
Modbus TCP I/O device templates in tree view mode.
392
1
2
3
Column header
Template
to search for topological I/O device templates.
Filters, page 121 . The check mark indicates that the filter is applied.
Button to toggle between grid view and tree view.
Description
Identifier of the template.
In tree view mode, the path to the template in the Global Templates library is also shown.
Version of the template.
Usability state (see EcoStruxure ™ Process Expert, Global Templates,
Reference Manual) of the template.
Description of the template.
Version
State
Description
Creating an I/O Device Entity
To create an I/O device entity, proceed as follows.
Step
1
2
Action
In the Topology Explorer , right-click the root or a topological folder and select Create
Device IO > Modbus TCP or EtherNet/IP .
Result: The Select Template dialog box opens displaying the corresponding templates.
Select a template and click OK .
Result: The software creates an instance of the selected template in the folder, which represents the I/O device topological entity.
NOTE: Click Cancel to close the Select Template dialog box without creating the
I/O device entity.
EIO0000001114.15
EIO0000001114.15
Modbus TCP and EtherNet/IP Device Actions
Right-click the I/O device entity to open a context menu with the following commands.
Command
Description
Opens the Physical Connections window, which allows you to connect or disconnect the device to existing Ethernet networks to represent physical connections to such networks.
Opens the Update Template dialog box, which allows you to update the template that is used by Modbus TCP device entities with the highest available version of the Global Templates library on the system server.
Opens the Replace Device Template dialog box, which allows you to replaces the template that is used by the device with another template that meets the
and that is available in the Global Templates library on the system server.
Deletes the device entity including related configurations and mappings.
Rename Allows you to change the identifier of the Modbus TCP device entity.
Opens the Export window, which allows you to export the entity and its folder hierarchy in the form of a topology export file (.sbk).
Properties Opens the Device Editor window in which you can view and edit properties of the device entity.
I/O Device Properties
Right-click the device entity and select Properties to open the Device Editor window in which you can view and edit its parameters.
You can view and/or edit the following parameters.
Parameter
$System $Name
$Description
Description
The identifier must be unique within the system and satisfy
The default value: xHW_n where x is the identifier of the corresponding application template of the device and n an incremental number starting at 1.
The identifier (or part of it) is also used to create the name of the DTM if it is added during
String.
Optional.
You can enter a description of the device with free form text (string).
$Area Optional.
You can assign an access control number to the device entity.
Range: 1...255 (integer)
Communication IPAddress
Subnet Mask
IP address of the device on the Ethernet network.
Default value: Blank
Subnet mask that is used to define IP addresses on the
Ethernet network that the device belongs to.
Default value: Blank
IOScanningLines (1) You can select the number of I/O scanner lines that are generated during build.
Possible values: 1 to n , where n , is the maximum number of lines that a given template can generate.
Default value: Varies by template.
393
394
Parameter
ID (2)
Communication ReadLength (2)
ReadAddress (2)
WriteLength (2)
WriteAddress (2)
Description (2)
Configuration Privilege
IOSType (3)
EnableDHCP
Description
Modbus unit ID, unique identifier of the device. The parameter is provided by the DeviceID element of the
Modbus TCP server interface ( MBTCPServiceServer ), which is referenced by all Schneider Electric Modbus
TCP I/O device hardware templates.
Default value: 255
Valid range: 0 to 255
(UnsignedInt).
For example, for Altivar variable speed drives, the identifier is 255 .
NOTE: You can configure the parameter also in the Communication Mapping
of
Supervision executables.
Number of words to be read (integer).
Enter an appropriate value. The value cannot be null when you implement communication by using I/O scanning with the CPU of an M580 controller or a NOC communication module.
Default value: 0
Remote address (%MW) to be read (integer).
Enter an appropriate value.
Default value: 0
Number of words to be written (integer).
Enter an appropriate value. The value cannot be null when you implement communication by using I/O scanning with the CPU of an M580 controller or a NOC communication module.
Default value: 0
Remote address (%MW) to be written (integer).
Enter an appropriate value.
Default value: 0
Optional.
Enter a description of the device with free form text
(string).
Parameter for access control purposes.
Default value: Blank
(String).
Parameter to select the I/O scanning element to be used:
• TesysTE : To read/write the complete data from/to the device.
• TesysTEFast : To read/write a minimum set of data from/to the device. Default value.
The selection and the device template that is used in the application of the system needs to match; otherwise you cannot proceed with the
.
For example, if you select TesysTEFast for this parameter, instantiate the $TesysTEFast template in the application.
(Enum).
NOTE: Changing this parameter value when the hardware mapping is done removes the mapping.
When true, the device subscribes to a DHCP server service.
EIO0000001114.15
Parameter
PhysicalInterfaceLink1 (4)
IdentifyByDevice-
Name
MACAddress
DTMDeviceName
Destination
Instance
Role
Interface
Description
When true, the DHCP server identifies the device by using DTMDeviceName ; otherwise, it identifies the device by using MACAddress .
MAC address of the device.
Use a hyphen as separator.
Name of the device.
For example, TeSys064 .
Indicates to which Ethernet network the device is connected.
Indicates the identifier of the role of the interface.
Indicates the identifier of the interface that the device exposes for connection to the Ethernet network.
(1) The parameter is displayed only for entities using a generic topological
Modbus TCP device template, which allows selecting the number of I/O scanner lines that are generated (for example, $EGenDev4IOSHW ).
(2) The parameters are available only for entities using a generic topological
Modbus TCP device template (and also for a few Modbus TCP device-specific templates). For generic templates that reference several Modbus TCP server interfaces (for example, $EGenDev4IOSHW ), the set of parameters appears as many times as there are server interfaces in the template.
(3) The parameter is available only for certain Modbus TCP entities (for example, those using the $ETesysTHW template).
(4) The section is displayed if you have
the I/O device entity to an Ethernet network of the system. The parameters are not editable.
Changing I/O Device Properties
Modifying the IP address or subnet mask of an I/O device entity, may delete the
communication mapping, page 424
that exists with this device.
In such case, the software displays a notification asking you to confirm the change.
Make either selection:
• Yes : To save the change to the properties of the I/O device and delete the associated communication mapping.
• No : To discard your changes.
Implementing Communication Between Controllers and I/O
Devices
For details about how to implement communication between controllers and I/O devices by using Modbus TCP or EtherNet/IP, refer to the topic describing how to
manage communication, page 597 .
Configuring HART Modules
Overview
The HART communication protocol can be addressed by using either of these
Modicon eX80 modules:
• BMEAHI0812 HART analog input module.
• BMEAHO0412 HART analog output module.
You can add these HART analog I/O modules to local racks and/or remote drops of controllers of the Quantum and M580 platform. With the Quantum platform, a
NOC communication module is required.
EIO0000001114.15
395
396
You proceed with the configuration of HART modules from within the Control
Participant by using the Configure command on a controller entity.
Thereafter, the software transfers the defined configuration to the entity of the
Topology Explorer by using the appropriate topological templates.
NOTE: Addressing the HART protocol by using a Modicon STB island is also possible with the STBAHI8321 HART
.
Managed Data
The Primary Variable (PV) of HART analog I/O modules is the only variable that is available in the Hardware Mapping Editor later on. During this stage, you can map facets of analog I/O templates (for example, $AnalogInput1 ) instantiated in the application, which represent PV, to the projection of the I/Os of the HART modules.
The other variables and data of the HART modules that you configure are preserved during build and can be deployed to a controller but are not usable at the system level.
NOTE: You need to use an Asset Management System and perform some additional steps (see EcoStruxure ™ Process Expert , Foundation Application
Templates, User Guide) manually to take advantage of the advanced functionality provided by HART analog I/O modules.
HART Module Device DDT Variables
When you add a HART analog I/O module to a configuration, the Participant creates a device DDT (DDDT) variable associated to the I/O the module.
When you add the corresponding HART device type manager (DTM) that is preinstalled, it creates a second DDDT variable associated to the DTM to manage the extended data.
Both variable are present only in the configuration that you can access from the
Topology Explorer and are integrated to the Control Participant project during
. However, if you want to use the two DDDTs in a Control
Participant project during refinement, you can
Configuring HART Modules
To configure HART analog I/O modules, proceed as follows.
Step
1
2
3
Action
Right-click the controller entity in the Topology Explorer and select Configure .
Result: The software displays the Control Participant in a reduced window.
Maximize the Control Participant.
Proceed with the configuration of the HART module inside the Control Participant.
For more information about configuring HART analog I/O module and working inside the
Control Participant, refer to the topic describing the configuration of the controller (see
EcoStruxure ™ Process Expert, Control Participant Services, User Guide).
EIO0000001114.15
Step
4
Action
Click the save button in the toolbar of the Participant window.
5
Result: The software saves the changes in the configuration file and transfers the configuration to the Topology Explorer . It may display the
dialog box.
NOTE: If the software detects a configuration issue, it displays a notification, which allows you to change the configuration until you are able to save it.
Close the Control Participant window.
NOTE:
If you change the configuration and you click the close button on the outer frame of the Participant window without saving your changes first, the software displays the
Save Configuration dialog box where you can click the following:
• Yes to save the changes in the configuration file and close the Participant window.
• No to discard your changes and close the Participant window.
• Cancel to leave the Participant open without saving your changes.
Changing the HART Module Configuration
To change the configuration of a HART analog I/O module, follow the procedure to configure a HART module, and proceed with the changes inside the Control
Participant.
HART Module Representation
The Topology Explorer allows you to view the topological devices representing
HART analog I/O modules.
It lets you also view and configure their
.
The following figure shows the representation of a BMEAHI0812 HART analog I/O module located in the local rack of an M580 controller entity.
1 Device representing the HART module.
NOTE: The HART module is represented similarly in a topological entity based on the Quantum platform.
Configuring an Ethernet Network
Overview
The Ethernet network entity represents a physical or virtual Ethernet local area network (LAN or VLAN) to which you can physically connect topological entities of
EIO0000001114.15
397
398
the system such as controllers, Modbus TCP devices, EtherNet/IP devices, and station nodes.
You create Ethernet network entities and define their parameters in the Topology
Explorer .
Creating an Ethernet Network Entity
To create an Ethernet network entity, proceed as follows.
Step
1
Action
Right-click the system root folder or a topological folder in the Topology Explorer and select Create Ethernet Network .
Result: The software creates an Ethernet network entity and displays it inside the folder.
NOTE: The software may display the
dialog box.
Ethernet Network Actions
Right-click the Ethernet network entity to open a context menu with the following commands.
Command
Description
Opens the Update Template dialog box, which allows you to update the template that is used by the Ethernet network entity with the highest available version of the Global Templates library on the system server.
Opens the Export window, which allows you to export the entity and its folder hierarchy in the form of a topology export file (.sbk).
Delete
Rename
Deletes the entity including related configurations.
Allows you to change the identifier of the Ethernet network entity.
Properties Opens the Device Editor window in which you can view and edit properties of the Ethernet network.
Ethernet Network Properties
Right-click the Ethernet network entity and select Properties to open the Device
Editor window in which you can view and edit parameters of the Ethernet network.
You can view and/or edit the following parameters.
Parameter
$System
PhysicalInterfaceLinkX
(1)
$Name
Description
The identifier must be unique within the system and satisfy
.
Default value: EthernetNetwork_n where n is an incremental number starting at 1.
$Description
$Area
Optional.
You can enter a description of the Ethernet network with free form text.
Default value: Blank
Optional.
You can assign an access control number to the
Ethernet network entity.
Range: 1...255 (integer)
Default value: Blank
Indicates which topological entities and/or devices you have connected to the Ethernet network.
EIO0000001114.15
Parameter Description
A section containing these parameters is displayed for each of the connected topological entities and devices, including connections to standby controllers of redundant configurations.
Destination
Instance
Indicates the $Name of the connected entity or
.
Role
Interface
Indicates the identifier of the role of the interface.
Indicates the identifier of the interface that the Ethernet network entity exposes for connecting with the topological entity or device.
(1) The section is displayed if you have
topological entities or devices to the Ethernet network. The parameters are not editable.
X represents the number of the physical interface link, which is an incremental number starting at 1.
Connecting to an Ethernet Network
Overview
The Physical Connections command allows you to connect topological entities that support Modbus TCP or EtherNet/IP connectivity to an Ethernet network entity of the system.
The physical interface link that is created represents the physical connection of communication modules to a network.
At the platform level, physical connections for entities are required to be able to perform the
communication mapping, page 420
in Control and Supervision executables. They are not required to perform service mapping or deployment and execution tasks.
Devices with which you can create a physical connection are identified by using their $Name
To make a physical connection,
create an Ethernet network first, page 397 .
NOTE: The command also allows you to disconnect an entity from an
Ethernet network.
IP Address Uniqueness Requirement
The IP address of a topological entity and/or its communication module on the
Ethernet network must be unique to make the physical connection possible. This rule applies to:
• CPU modules (including main IP address and IP address A depending on controller platform)
• Communication modules such as:
◦ NOE
◦ NOC (for 140NOC78•00 modules, main IP address only, not IP address A)
◦ CRA
◦ NIC of station nodes
◦ NIM of STB islands
◦ Embedded
RIO scanner services, page 377
of M580 CPUs
• Modbus TCP and EtherNet/IP I/O devices
• PROFIBUS remote masters (PRMs)
NOTE: Refer also to rules for redundant controller
EIO0000001114.15
399
400
Viewing Connections to Ethernet Networks
The PhysicalInterfaceLink parameter allows you to view, which entities are connected to which Ethernet network. Access the parameter by right-clicking either of the following and selecting Properties :
• The
Ethernet network entity, page 398
.
• The communication module of a topological entity
NOTE: You can also right-click an entity and select Physical Connections to view the Ethernet network to which the entity if connected to.
Availability of Ethernet Networks
If the communication or hardware mapping editor is open for an entity, then the
Ethernet network to which this entity is connected is not available. Because of this, you cannot use the Physical Connections command to connect other entities to this Ethernet network or change existing connections to this network.
Close the communication mapping editor to release the Ethernet network.
Managing Conflicting Connections to Ethernet Networks
If the system contains at least 2 entities, each with a communication module physically connected to an Ethernet network, and during the configuration of 1 of the entities, you enter a conflicting IP address for the module, a dialog box opens when you attempt to save the configuration, requiring confirmation to remove the physical connection of the module.
Click either of the following:
• OK to remove the physical connection of the module, disconnecting it from the Ethernet network.
• Cancel to cancel the save operation and keep the Control Participant open, which allows you to change the configuration.
For more information, refer to Considerations When Updating an Existing
Configuration (see EcoStruxure ™ Process Expert, Control Participant Services,
User Guide).
NOTE: Removing the physical connection to an Ethernet network deletes all or part of the existing communication and hardware mapping of the associated
Control Participant project executable.
Connections with Redundant Controllers
For redundant controllers, the rule about uniqueness of the IP address on an
Ethernet network to make the connection possible applies also to:
• For CPU modules:
◦ (Main) IP address +1 (where IP address is the address of the CPU module of the primary controller)
◦ IP address B (M580 platform)
• For BMENOC3•1 communication modules, main IP address +1 only (not IP address B)
• For 140NOC78•00 communication modules, IP address +1 (where IP address is the address of the NOC module of the primary controller)
• For NOE communication modules, IP address +1 (where IP address is the address of the NOE module of the primary controller)
Therefore, when a standalone controller is connected to an Ethernet network and you change the configuration to a redundant one, already connected modules of the controller that has become the primary controller may be disconnected. This affects
The table describes the various scenarios when you change the configuration of a standalone controller to a redundant one depending on the status of the IP
EIO0000001114.15
address of counterpart modules in the standby controller. It is assumed that the standalone controller becomes the primary controller of the redundant configuration.
Status of physical connection of module in standalone configuration
IP address (1) of counterpart module in the standby controller after changing to redundant configuration
Unique
Impact on the physical connection of both modules to the Ethernet network
Connected Both modules are connected.
Connected Already exists Module of the primary controller is disconnected.
Module of the standby controller is not connected.
Not connected irrelevant Both modules are not connected.
(1) If the module has two IP addresses both are considered unless otherwise mentioned.
For example, if the local rack of an M580 standalone controller contains an NOC module, which is connected to an Ethernet network (main IP address) and the
CPU communication module is also connected (Main IP address and IP address
A) if, when you change this configuration to a redundant one, the IP address of the
NOC module of the standby controller (main IP address +1) is not unique on the same network, then it is not connected to the network and the NOC module of the primary controller is disconnected from the network. If the IP addresses of the
CPU communication module of the standby controller are unique, both primary and standby CPU communication modules are connected to the network.
The other way around, when you change the configuration of a redundant controller to a standalone one, the modules that were connected to the Ethernet network remain connected.
Connecting a Controller to an Ethernet Network
You can connect controller entities that offer physical connectivity to existing
Ethernet networks of the system.
To connect a controller to an Ethernet network, proceed as follows.
Step
1
2
Action
Right-click the controller entity in the Topology Explorer and select Physical
Connections .
Result: The software opens the Physical Connections window and displays the identifier of the communication modules of the controller in the Communication
Modules column.
NOTE:
• The identifier only appears if you have assigned an IP address to the communication module in the configuration.
• When connecting a redundant controller, only communication modules of the primary controller are displayed in the Physical Connections window.
• When connecting a controller that has a CRP module or an embedded RIO scanner service (M580 CPUs), the EthRIO bus device that is displayed in the
Physical Connections window represents the physical connection with the remote I/O network. It connects the corresponding communication modules such as CRP and CRA modules, and the embedded RIO scanner service.
Click the field in the Allowed Network(s) column next to the communication module that you want to connect to the network.
Result: The Ethernet networks to which a connection is possible are displayed.
EIO0000001114.15
401
402
Step
3
4
Action
Select a network.
Click OK to save your selection and close the Physical Connections window.
Result: The communication module is connected to the selected Ethernet network.
NOTE:
• For redundant controllers, the software automatically connects the counterpart module of the standby controller to the same Ethernet network.
• For BMENOC3•1 communication modules, IP addresses A and B are not connected.
Disconnecting a Controller from an Ethernet Network
To disconnect a controller from an Ethernet network, proceed as follows.
Step
1
2
3
4
5
Action
Right-click the controller entity in the Topology Explorer and select Physical
Connections .
Result: The software opens the Physical Connections window and displays the identifier of:
• The communication modules of the controller in the Communication Modules column
• The Ethernet network to which the controller is connected in the Allowed Network
(s) column
NOTE:
• When disconnecting a redundant controller, only the communication modules of the primary controller are displayed in the Physical Connections window.
• When disconnecting a controller that as CRP module or an embedded RIO scanner service (M580 CPUs), the EthRIO bus device that is displayed in the
Physical Connections window, represents the physical connection with the remote I/O network. It disconnects the corresponding communication modules, such as CRP and CRA modules, and the embedded RIO scanner service.
The other way around, when the
software disconnects, page 400
, for example, a CRA module because of an IP address conflict, it is the EthRIO bus device that is disconnected.
Click the field in the Allowed Network(s) column next to the communication module that you want to disconnect from the network.
Result: The Ethernet networks to which a connection is possible are displayed.
Select Not Assigned in the Allowed Network(s) menu.
NOTE: You may also select another Ethernet network from the menu (if available) to create a connection with it instead.
Click OK .
Result: If a communication mapping exists for the executable to which the controller is mapped, the software displays a notification, asking you to confirm the disconnection.
Otherwise, the software disconnects the communication module from the selected
Ethernet network, and closes the Physical Connections window.
NOTE: For redundant controllers, the software automatically disconnects the counterpart module of the standby controller from the same Ethernet network.
Click Yes to confirm.
Result: The software:
• Disconnects the communication module from the selected Ethernet network.
• Deletes the
of the executable to which the controller is mapped.
• Changes the status of the executable to which the controller is mapped to Out Of
Date if it is built.
• Closes the Physical Connections window.
NOTE: Click No to close the Physical Connections window without disconnecting the communication module from the Ethernet network.
NOTE: For a redundant controller, the software automatically disconnects the counterpart module of the standby controller from the same Ethernet network.
EIO0000001114.15
EIO0000001114.15
Connecting a Station Node to an Ethernet Network
You can connect or disconnect station node entities to existing Ethernet networks through their NIC devices.
To connect a station node to an Ethernet network, proceed as follows.
Step
1
2
3
4
Action
Right-click the station node entity in the Topology Explorer and select Physical
Connections .
Result: The software opens the Physical Connections window and displays the identifier of the NIC of the station node in the Communication Modules column.
NOTE: The NIC identifier only appears if you have assigned an IP address to the
NIC.
Click the field in the Allowed Network(s) column next to the NIC that you want to connect to the network.
Result: The Ethernet networks to which a connection is possible are displayed.
Select a network.
Click OK to save your selection and close the Physical Connections window.
Result: The station node is connected to the selected Ethernet network.
Disconnecting a Station Node from an Ethernet Network
To disconnect a station node entity from an Ethernet network, proceed as follows.
Step
1
2
3
4
Action
Right-click the station node entity in the Topology Explorer and select Physical
Connections .
Result: The software opens the Physical Connections window and displays the identifier of:
• The NIC of the station node in the Communication Modules column
• The Ethernet network to which the NIC is connected in the Allowed Network(s) column
Click the field in the Allowed Network(s) column next to the NIC that you want to disconnect from the network.
Result: The Ethernet networks to which a connection is possible are displayed.
Select Not Assigned in the Allowed Network(s) menu.
NOTE: You may also select another Ethernet network from the menu (if available) to create a connection with it instead.
Click OK .
Result: The software:
• Disconnects the station node from the selected Ethernet network.
• Deletes the existing
communication mapping, page 424
of the executable to which the station node is mapped.
• Changes the status of the executable to which the station node is mapped to Out
Of Date if it is built.
• Closes the Physical Connections window.
Connecting a Modbus TCP or EtherNet/IP Device to an Ethernet
Network
You can connect or disconnect Modbus TCP and EtherNet/IP device entities to existing Ethernet networks.
To connect an I/O device entity to an Ethernet network, proceed as follows.
403
404
Step
1
2
3
4
Action
Right-click the device entity in the Topology Explorer and select Physical
Connections .
Result: The software opens the Physical Connections window and displays the device entity identifier in the Communication Modules column.
NOTE: The device identifier only appears if you have assigned an IP address to the device.
Click the field in the Allowed Network(s) column next to the device that you want to connect to the network.
Result: The Ethernet networks to which a connection is possible are displayed.
Select a network.
Click OK to save your selection and close the Physical Connections window.
Result: The device is connected to the selected Ethernet network.
Disconnecting a Modbus TCP or EtherNet/IP Device from an
Ethernet Network
To disconnect a Modbus TCP or EtherNet/IP device entity from an Ethernet network, proceed as follows.
Step
1
2
3
4
5
Action
Right-click the device entity in the Topology Explorer and select Physical
Connections .
Result: The software opens the Physical Connections window and displays the identifier of:
• The I/O device in the Communication Modules column
• The Ethernet network to which the device is connected in the Allowed Network(s) column
Click the field in the Allowed Network(s) column next to the device that you want to disconnect from the network.
Result: The Ethernet networks to which a connection is possible are displayed.
Select Not Assigned in the Allowed Network(s) menu.
NOTE: You may also select another Ethernet network from the menu (if available) to create a connection with it instead.
Click OK .
Result: If a hardware or communication mapping exists for the executable of the client controller communicating with the device, the software displays a notification, asking you to confirm the disconnection.
Otherwise, the software disconnects the I/O device from the selected Ethernet network, and closes the Physical Connections window.
Click Yes to confirm.
Result: The software:
• Disconnects the I/O device from the selected Ethernet network.
• Deletes the existing
and
communication mapping, page 424
of the executable of the client controller communicating with the device.
• Changes the status of the client controller communicating with the device to Out
Of Date if it is built.
• Closes the Physical Connections window.
NOTE: Click No to close the Physical Connections window without disconnecting the I/O device from the Ethernet network.
Connecting an STB Island to an Ethernet Network
You can connect or disconnect STB islands to existing Ethernet networks through their NIM.
To connect an STB island to an Ethernet network, proceed as follows.
EIO0000001114.15
EIO0000001114.15
Step
1
2
3
4
Action
Right-click the STB island entity in the Topology Explorer and select Physical
Connections .
Result: The software opens the Physical Connections window and displays the identifier of the communication module of the STB island in the Communication
Modules column.
NOTE: The module identifier only appears if you have assigned an IP address to the NIM.
Click the field in the Allowed Network(s) column next to the communication module that you want to connect to the network.
Result: The Ethernet networks to which a connection is possible are displayed.
Select a network.
Click OK to save your selection and close the Physical Connections window.
Result: The STB island entity is connected to the selected Ethernet network.
Disconnecting an STB Island from an Ethernet Network
To disconnect an STB island entity from an Ethernet network, proceed as follows.
Step
1
2
3
4
5
Action
Right-click the STB island entity in the Topology Explorer and select Physical
Connections .
Result: The software opens the Physical Connections window and displays the identifier of:
• The NIM of the STB island in the Communication Modules column
• The Ethernet network to which the NIM is connected in the Allowed Network(s) column
Click the field in the Allowed Network(s) column next to the NIM that you want to disconnect from the network.
Result: The Ethernet networks to which a connection is possible are displayed.
Select Not Assigned in the Allowed Network(s) menu.
NOTE: You may also select another Ethernet network from the menu (if available) to create a connection with it instead.
Click OK .
Result: If a hardware or communication mapping exists for the executable of the client controller communicating with the STB island, the software displays a notification, asking you to confirm the disconnection.
Otherwise, the software disconnects the STB island entity from the selected Ethernet network, and closes the Physical Connections window.
Click Yes to confirm.
Result: The software:
• Disconnects the STB island entity from the selected Ethernet network.
• Deletes the existing
and
communication mapping, page 424
of the executable of the client controller communicating with the STB island.
• Changes the status of the client controller communicating with the STB island to
Out Of Date if it is built.
• Closes the Physical Connections window.
NOTE: Click No to close the Physical Connections window without disconnecting the communication module from the Ethernet network.
Connecting a PRM to an Ethernet Network
You can connect or disconnect PRM entities to existing Ethernet networks.
To connect a PRM entity to an Ethernet network, proceed as follows.
405
Step
1
2
3
4
Action
Right-click the PRM entity in the Topology Explorer and select Physical Connections .
Result: The software opens the Physical Connections window and displays the PRM entity identifier in the Communication Modules column.
NOTE: The PRM identifier only appears if you have assigned an
to the PRM.
Click the field in the Allowed Network(s) column next to the PRM.
Result: The Ethernet networks to which a connection is possible are displayed.
Select a network.
Click OK to save your selection and close the Physical Connections window.
Result: The PRM is connected to the selected Ethernet network.
Disconnecting a PRM from an Ethernet Network
To disconnect a PRM entity from an Ethernet network, proceed as follows.
Step
1
2
3
4
5
Action
Right-click the PRM entity in the Topology Explorer and select Physical Connections .
Result: The software opens the Physical Connections window and displays the identifier of:
• The PRM in the Communication Modules column
• The Ethernet network to which the PRM is connected in the Allowed Network(s) column
Click the field in the Allowed Network(s) column next to the PRM.
Result: The Ethernet networks to which a connection is possible are displayed.
Select Not Assigned in the Allowed Network(s) menu.
NOTE: You may also select another Ethernet network from the menu (if available) to create a connection with it instead.
Click OK .
Result: If a hardware or communication mapping exists for the executable of the client controller communicating with the PRM, the software displays a notification, asking you to confirm the disconnection.
Otherwise, the software disconnects the PRM from the selected Ethernet network, and closes the Physical Connections window.
Click Yes to confirm.
Result: The software:
• Disconnects the PRM entity from the selected Ethernet network.
• Deletes the existing
and
communication mapping, page 424
of the executable of the client controller communicating with the PRM.
• Changes the status of the client controller communicating with the PRM to Out Of
Date if it is built.
• Closes the Physical Connections window.
NOTE: Click No to close the Physical Connections window without disconnecting the PRM from the Ethernet network.
Managing the Topology
Overview
This section describes how to use the software to manage the topology of the system.
406 EIO0000001114.15
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
Moving Topological Folders and Entities
Moving Topological Folders
You can move any topological folder to another folder, including the system root folder, by dragging it.
Updating Templates of Topological Entities
Overview
By using the Update Template command in the Topology Explorer , you can update the templates that are used by the following topological entities and their devices:
• Controllers
• STB islands
• Station nodes
• Modbus TCP and EtherNet/IP devices
• PROFIBUS Remote Masters and DPs
• Ethernet networks
If the update of one template cannot be completed for an entity, the entire update process is rolled back.
When used at the folder level, the command applies to any entity that is contained in the folder, and in any of its subfolders.
NOTE: The update functionality affects:
• Existing service, communication, and hardware mapping interface links.
• Deployment information related to the executable to which the entity is mapped.
NOTE: No command is available to replace a topological template, such as the $UnknownModule template (see EcoStruxure ™ Process Expert, Control
Participant Services, User Guide).
Accessing the Command
Right-click a folder or an entity, and select Update Template .
Description of the Update Functionality
The software proceeds with the update of templates in the following order:
• The templates that are associated to the entity are updated.
• Interface links are processed.
The table describes the effects on the different template items when you update the templates that are used by a topological entity:
Item Identifier in New Template
Parameter values Is same as in current template
Is not in current template
Action
Explicitly defined parameters of the current template keep their respective value in the new template.
New parameters that are not part of the current template keep their default values.
EIO0000001114.15
407
Item
Physical interface links, page 399
Identifier in New Template
Is same as in current template
Is not the same as in current template
–
Deployment information
–
Action
Physical interface links of the entity are maintained.
New physical interface links can be added. Physical interface links that are not part of the new template or that do not satisfy applicable rules are removed.
The software maintains existing service, communication, and hardware mapping interface links of the Control and Supervision executables to which the entity is mapped if the corresponding mapping interfaces are available, and satisfy applicable rules.
If you had deployed a Control project to a station node or controller entity, the corresponding deployment information is unchanged.
NOTE: When you update the template of a redundant controller entity, the update takes places for both the primary and the standby controller entities.
Default Template Selection
By default, the software selects the topological template with the same identifier that has the highest version number with the Usability State of Approved .
Updating Templates
To update the templates that are used by a topological entity, proceed as follows:
Step Action
1 In the tree view of the Topology Explorer , right-click the entity and select Update
Template .
Result: The Update Device Template dialog box opens. It shows for each device template that can be updated, the new version that will be used.
2 Click OK .
Result: The software:
• Updates the templates that are used by the entity.
• May delete existing mapping information of the corresponding executable of the
Control project.
NOTE: Click Cancel to close the Update Device Template dialog box without updating templates.
NOTE: If you use a filter in the Name column of the Update Device Template dialog box and as a result, only some of the device templates for which a later version exists are displayed, the update operation is still performed on the entire selection of device templates of the entity for which a later version exists.
Exporting Topological Entities
Overview
The Export command allows you to create a non-editable export file (.sbk), which contains information of selected topological entities, their folder hierarchy, and dependencies.
You can use this data with the
functionality of the Topology
Explorer to do the following:
• Transfer project information to a different system or EcoStruxure Process
Expert infrastructure.
• Add and/or modify topological entities.
• Duplicate topological entities.
• Move, remove, replace, and/or add devices of entities.
• Update properties of entities and folders.
408 EIO0000001114.15
• Prepare the topology of a system before importing Control and/or Supervision
Participant projects.
Exporting M580 Safety Controllers
For specific information about exporting M580 safety controllers, refer to the topic describing how to
engineer systems with M580 safety controllers, page 590
.
Software Version Compatibility
The version of EcoStruxure Process Expert that you use to import the information contained in the export file must be the same as the version that you used to create the export file (a service pack is considered the same version); otherwise you cannot proceed with the import.
Export File Contents
You can select the Export command at different levels to export the following:
• For an entity: Exports the data pertaining to this topological entity and its devices. The parent folder hierarchy up to the system root folder is also included.
• For a topological folder: Exports the entities contained in the folder and in any subfolders, and their devices. The parent folder hierarchy up to the system root folder is also included.
• For the system root folder: Exports the entities of the entire system and their devices. The parent folder hierarchy up to the system root folder for any entity is also included.
By default, in each case, the folder hierarchy of the exported entities is selected for export.
You cannot export empty folders or folders that contain entities that are not selected for export. The rule does not apply for folders that are part of the parent folder hierarchy of an exported entity or folder.
NOTE: If physical connections exist for a selected entity at the time of export, these links are automatically included in the export file. This allows recreating the physical connection at the time of import if
applicable rules are satisfied, page 413
.
NOTE:
are not exported. Yet, the
password protection properties, page 373
and their value are exported.
Topological Templates
The export file does not contain the topological templates of the entities and devices that you are exporting. To import entities in a different EcoStruxure
Process Expert infrastructure, the Global Templates library of the target architecture needs to contain the necessary templates with the same version.
Entities for which the template is not present cannot be imported.
For information on how to export templates, refer to the topic that describes
managing Global Templates, page 675
.
Topological Export Window
The topological Export window allows you to select the entities and folders that you export.
EIO0000001114.15
409
The following figure shows an example of the Export window in tree view mode.
410
1 Button to toggle between the grid view and tree view
Header
Name
Type
Path
Description
Description
Shows the identifier of topological entities that you can export.
By default, entities are selected for export.
NOTE: When check boxes of folders are filled with a black square, at least one entity or folder in a sublevel is not selected for export.
Type of the topological entity (controller, station node, Ethernet network, and so on).
Path to the folder or entity.
The column is displayed only in grid view.
Contents of the Description property of the entity.
NOTE: To expand/collapse a node in the Export window, select the node and press Enter .
Aborting Export Tasks
After confirming the export by clicking Save in the Save dialog box, the abort icon is displayed in the
notification panel, page 54 . Click the icon to cancel the task.
The export file is not created.
Only the user who has selected the command is allowed to abort it.
NOTE: If you are exporting only a few entities, the task may complete before you are able to click the icon.
Creating the Export File
To create a topology export file, proceed as follows.
EIO0000001114.15
Step
1
2
3
4
Action
In the Topology Explorer , right-click the folder or entity that you want to export and select Export .
Result: The software opens the Export window and displays the entities that you can export.
Select the entities that you want to export.
Click OK .
Result: The software opens the Save dialog box.
NOTE: Click Cancel to close the Export window without creating the export file.
Select a location where you want to save the export file, enter a file name, and click
Save .
Result: The software creates the export file (.sbk), which contains information of the selected topological entities.
NOTE: Click Cancel to close the Save dialog box and revert to the Export window.
Importing Topological Entities
Overview
The import functionality allows you to import data of topological folders and entities from a topological export file (.sbk), which was created by using the
functionality of the Topology Explorer .
You can import this data into an existing system by using the Import command of the Topology Explorer .
You have the possibility to select which items you want to import out of those contained in the export file.
Before proceeding with the import, the software verifies if importing the selected instances creates a duplicate entity identifier or an IP address conflict. If required, the import operation includes a second step, which allows you to resolve conflicts by selecting an action to perform during import:
• Skip the entity; it is not imported.
• Update the entity of the target system with the configuration of the export file.
• Create the entity with a different, unique identifier.
The notification panel displays information on both the tasks that completed successfully and those that could not be completed.
Applicable import rules are described in this topic. Examples are given to illustrate
NOTE: You cannot proceed with the import of an entity if in the target system one of its dependencies is locked by another operation or user. For example, if in the target system the Hardware Mapping Editor is open, you cannot import into the topology of this system entities that are linked to the Ethernet network because it is locked by the hardware mapping process. However, you could import a station node that has no physical connection.
Importing M580 Safety Controllers
For specific information about importing M580 safety controllers, refer to the topic describing how to
engineer systems with M580 safety controllers, page 590
.
Software Version Compatibility
The version of EcoStruxure Process Expert that you use to import the information contained in the export file must be the same as the version that you used to create the export file (a service pack is considered the same version); otherwise you cannot proceed with the import.
EIO0000001114.15
411
Topological Templates
The export file does not contain the topological templates of the exported entities and devices. If you are importing entities in a different EcoStruxure Process
Expert infrastructure and the required template for an entity is not present, then the entity is skipped during import.
Information on the required templates and template version is indicated in the
Import window.
When the import is finished, the notification panel displays information on the entities that were not imported if applicable.
For information on how to import templates, refer to the topic that describes
managing Global Templates, page 675
.
Identification of Conflicts
The table indicates the meaning of the color coding that the software uses to indicate the status of entities and folders in the Import
in the context of the target system.
Identification method
Tooltip
Tooltip text Description
Tooltip
Tooltip
IP with yellow dot
Ok
Entity already exists
Conflict to be resolved
IP conflict
An entity of the same type with the same name does not exist in the topology of the target system.
If you select if for import, the entity is created.
An entity of the same type with the same name, and with an identical configuration already exists in the topology of the target system. If you select if for import, the entity is created but with a different name to comply with the naming rule of the topology. This rule specifies that identifiers of entities must be unique within a system.
An entity of the same type with the same name already exists in the topology of the target system but the software detected a change, which can, for example, be related to:
• Properties.
• Devices of entities: Properties, position of modules on the rack, configuration, CPU or module type.
• Services of station nodes.
• Physical connections.
If you want to import the entity anyway, you need to select an action for it.
NOTE: Refer to the topic describing
import rules for conflicting entities, page 413 .
At the time of export, the entity that you want to import was connected to an Ethernet network that exists in the target system and its
IP address is already used on this network, page 399 .
In addition, the tooltip text indicates <conflicting IP address in the target system> - <path to the entity in the target system> - <Ethernet network identifier in the target system>.
You can still import the entity but physical connections are impacted. For details, refer to the topic describing
import rules for physical connections, page 413
.
NOTE: If the entity that has the same IP address in the target system also has the same identifier and is of the same type, the software does not indicate an IP address conflict.
General Import Rule for Non-Conflicting Entities and Folders
Each entity that is contained in the export file and that you have selected for import is created in the topology of the target system if the software does not detect a conflict.
Depending on the import path setting that you select, the software may create folders as needed to recreate the original hierarchy.
If a folder with the same identifier already exists in the target system, its properties
(for example, its description or area) are automatically updated with the configuration of the export file.
412 EIO0000001114.15
Entity type
Station node
Controller
STB island
PRM PROFIBUS DP
Ethernet network
Import Rules for Conflicting Entities
The table describes the actions that you can perform for various types of entities when the software detects a conflict, depending if you select Update or Create . To be able to perform the changes that are indicated in the table, the export file needs to contain an entity that has the same identifier as an entity of same type in the target system. The imported entity needs to have a configuration that is different from the target entity. Update actions apply to the entity in the target system.
Create action
Creates the entity with a new identifier.
Creates the entity with a new identifier.
Creates the entity with a new identifier.
Modbus TCP and
EtherNet/IP I/O device
Creates the entity with a new identifier.
Creates the entity with a new identifier.
Update action
• Services are updated.
• Properties of the entity and its services are updated.
• Entity is moved if path in export file differs.
• Properties of the entity and its devices are updated.
• Position of modules are updated.
• Modules are added, replaced, and/or removed.
• Entity is moved if path in export file differs.
NOTE: Action not allowed if the controller is not of the same
•
•
•
•
•
Properties of the entity and its devices are updated.
Position of modules are updated.
Modules are added and/or removed.
Entity is moved if path in export file differs.
Properties are updated.
• Entity is moved if path in export file differs.
• Properties are updated.
• New physical connections are recreated if the entity is also imported and no IP conflict is detected.
• Entity is moved if path in export file differs.
Comments
Removing a service from a station node may affect existing service mappings of related executables.
Moving, adding, replacing, or removing a module of a controller may affect existing service, hardware, and/or communication mappings of the related executables.
This includes:
• Replacing the CPU module of a controller.
• Changing a standalone controller into a redundant one or the other way around.
You can overwrite parameters such as:
• IP address.
• Subnet mask.
• Explicit parameters that are defined in the corresponding templates.
Updating an I/O device may affect existing hardware and/or communication mappings of the related executables.
Existing physical connections in the target system are not maintained.
NOTE: Refer also to the topic describing
import rules for physical connections, page 413
.
Import Rules for Physical Connections
When you import an entity for which a
to an
Ethernet network existed at the time of export and the target system contains no
Ethernet network with the same identifier, the software recreates the physical connection in the target system if the following conditions are true:
• The Ethernet network is included in the export file.
• Both the entity and the Ethernet network are imported successfully with their original identifier (if an entity is created with a new identifier, the physical connection is not recreated).
On the opposite, if an Ethernet network with the same identifier already exists in the target system, the Ethernet network does not need to be contained in the export file and you do not need to select it if it is contained. The physical connection to this Ethernet network is automatically maintained if the IP address of the imported entity is still available on the Ethernet network of the target system.
EIO0000001114.15
413
414
NOTE: As a rule, physical connections that exist in the target system prevail.
When you import an entity that is connected to an Ethernet network, if the
Ethernet network in the target system has the same name and the IP address of the entity is
on this Ethernet network, after import, the entity is not connected to the Ethernet network anymore. The disconnection from the Ethernet network happens whether you create an entity or update an existing one. The IP address of the entity after import is the one contained in the export file.
NOTE: More information on physical connections of redundant controllers is available in the topic describing
connections to Ethernet networks, page 400 .
Password Management After Importing Topological Entities
After you import into a system a controller and/or a station node for which
has been enabled, you need to do the following to be able to deploy a Control Participant project:
• If no password was set, you need to set one.
• If a password was set, you need to enter the password when prompted.
For more information, refer to the topic describing how to manage
Control Participant projects, page 488 .
NOTE: The above applies even if you are importing these topological entities into the same system from which they were exported or if you have not logged out of the engineering client since the export was performed.
Accessing the Topology Import Window
To access the topology Import window, proceed as follows.
Step
1
2
3
Action
From the Systems Explorer , right-click the system into which you want to import topological entities and select Open Topology .
Result: The software opens the Topology Explorer .
Right-click the system root folder and select Import .
Result: The software opens the Import dialog box.
Browse to the topology export file (.sbk) that contains information on the topological entities that you want to import and click Open .
Result: The software opens the Import window and displays the contents of the file that you have selected.
Topology Import Window Description
The topology Import window allows you to select the entities that you want to import in the topology of a system and to take appropriate actions in case of
.
EIO0000001114.15
The following figure shows an example of the Import window displaying the contents of the selected topological export file.
EIO0000001114.15
3
-
4
5
Item
1
2
Description
The check boxes allow you to select the folders and/or entities that you want to import.
Selecting a folder selects any item it contains and the other way around.
By default, items contained in the export file are selected.
NOTE: A check box filled with a black square indicates that at least one item in a sublevel is not selected.
Identifier of the folders and entities contained in the export file ( Name column).
Entities for which the software has detected a conflict are
.
In tree view mode, the column also reflects the hierarchy of the items at the time of export. The hierarchy may be different depending on the import path setting.
Type of the entity.
Path column. which indicates the path to the folder or entity.
The column is displayed only in grid view. Refer to item (6).
Description that comes from the properties of the entity or folder contained in the export file.
OK or Resolve button.
Either button is displayed depending on the status of the instances selected for import in the context of the target system:
• OK : The software did not detect duplicate identifier conflicts and selected instances are created in the target system upon clicking the button.
• Resolve : The software detected at least one duplicate identifier conflict for an instance selected for import. Upon clicking the button, a
new import window opens, page 416
, which displays only entities for which a conflict was detected. It allows you to resolve identifier conflicts.
The other entities for which no conflict was detected and that you have selected remain selected for import.
NOTE: If Resolve is displayed and you clear the check box of instances for which a conflict has been detected, the button changes to OK , and the other way around.
415
Item
6
7
Description
Button to toggle between grid view and tree view.
Import path setting check box:
• Relative Path : Default setting. The folder from which the import command was selected becomes the parent folder of the imported folder structure. The hierarchy of the imported folder structure remains unchanged.
• Absolute Path : When selected, the software maintains the hierarchy that existed at the time of export. The software creates folders as needed to recreate the original hierarchy.
NOTE: The check box is not displayed when you select the import command from the system root folder because in such case, relative and absolute paths are the same.
NOTE: To expand/collapse a node in the Import window, select the node and press Enter .
Resolving Detected Conflicts
The following figure shows an example of the Import window that is displayed when the software has detected conflicts and you click Resolve in the first import window.
416
The table describes the second topology Import window, which opens when you click Resolve .
3
4
Item
1
2
5
Description
Identifier of entities that you have selected for import and for which the software has detected an identifier and/or IP address conflict ( Name column).
The type of conflict is
NOTE: Only grid view mode is available in this window.
New name that will be used to create the entity when you select the Create action for the entity ( New Name column). The software automatically changes the identifier of the entity by adding the _n suffix where n is an incremental number starting at 1. This is for not having two entities with the same identifier in the topology after import.
For example, if the original identifier of the instance is Controller_1 , the new identifier is
Controller_1_1 .
Type of the entity.
Description that comes from the properties of the entity or folder contained in the export file.
Buttons that allow you to select an action for individual instances:
• Skip : The instance is not imported.
• Update : Default action. The instance that has the same identifier in the target system is
with the configuration contained in the export file.
Depending on the type of entity, this update can pertain to descriptions, services,
IP addresses, I/O modules, and so on.
• Create : The instance is created in the target system with the new identifier indicated in the New Name column.
EIO0000001114.15
EIO0000001114.15
Item
6
7
Description
Buttons that allow you to select an action for the conflicting instances as a whole.
The actions are the same as when you select the action for instances individually.
NOTE: Clicking on of these buttons overrides the selection you have made for individual instances.
Back . Click to revert to the first import window.
NOTE: If you modify the default selection in this window and click Back to revert to the first import window, when you click Resolve again in the first import window, the changes you had made to the selection are retained. Instances that you may have unselected in the first import window do not appear anymore, and the other way around.
Aborting Import Tasks
After confirming the import by clicking OK in the Import dialog box, the abort icon is displayed in the
. Click the icon to cancel the task. No entities are imported.
Only the user who has selected the command is allowed to abort it.
NOTE: If you are importing only a few entities, the task may complete before you are able to click the icon.
Importing Topological Entities
To import topological entities into an existing system, proceed as follows.
Step
1
2
3
4
5
Action
In the Import
, select the entities that you want to import.
If you selected the import command from a folder other than the system root folder, select Absolute Path if
If the software has detected an identifier conflict, click Resolve , otherwise proceed to step 5.
Result: The software opens a new import window, which displays entities for which the software has detected a conflict. The other entities for which no conflict was detected and that you have selected remain selected for import.
NOTE: Click Cancel to close the Import window without importing entities.
Select the action that you want to perform for each conflicting entity.
NOTE: Click Back to revert to the first import window. Your selection is retained when you return to this window by clicking Resolve again.
Click OK .
Result: The software:
• Applies the import rules based on your selection and updates the topology of the target system.
• Displays an import summary in the notification panel.
Examples
This topics gives examples of various import scenarios of an entity into a system, which contains an Ethernet network with the same name as the network in the source system.
The table gives an example of an imported entity that creates an identifier conflict.
The Update action is selected in the second step of the import.
Element
Entity identifier
Services
What is in the target system
StationNode_1
ControlExpert
What is Imported
StationNode_1
Supervision
Result
StationNode_1
Supervision
417
Element
Entity identifier
IP address
Physical connection to network_1
Entity identifier
IP address
Physical connection to network_1
Element
Properties
Folder properties
What is in the target system
What is Imported
Description: Station1 Description: Station2
None Description: Control Room
Result
Description: Station2
Description: Control
Room
The table gives two examples of an imported entity that does not create an identifier conflict. In the second example, the software detects an IP address conflict. In both cases, you can import Entity_2 in one step.
What is Imported Result What is in the target system
Entity_1
IP_1
Not connected
Entity_2
IP 1
Entity_1
IP 1
Connected at time of export Not connected
Entity_2
IP 1
Connected
418
Entity_1
IP 1
Connected
Entity_2 Entity_1
IP 1 IP 1
Connected at time of export Connected
Entity_2
IP 1
Not connected
The table gives two examples of an imported entity that creates an identifier conflict but without an IP address conflict. The action that is selected in the second step of the import is indicated.
What is Imported Result Element What is in the target system
Update action is selected
Entity identifier Entity_1
IP address
Physical connection to network_1
IP 1
Connected
Entity_1
IP 1 or any IP
Not connected at time of export
Entity_1
IP address of export file
Not connected
Entity identifier
IP address
Physical connection to network_1
Not connected
Create action is selected
Entity identifier Entity_1
IP address IP 1
Physical connection to network_1
Entity_1
IP 1 (not used on network_1)
Entity_1
IP_1 or any IP address not used on network_1 of target system
Connected at time of export
Entity_1
IP address of export file
Connected
Connected
Entity_1
Any IP address not used on network_1 of target system
Connected at time of export
Entity_1
IP 1
Connected
Entity_1_1
IP address of export file
Not connected
The table gives two examples of an imported entity that creates an IP address conflict. In each example, a different action is selected in the second step of the import.
What is Imported Result Element What is in the target system
Update action is selected
Entity identifier Entity_1 Entity_1 Entity_1
EIO0000001114.15
Element
IP address
What is in the target system
IP 1
Physical connection to network_1
Connected
Create action is selected
Entity identifier Entity_1
IP address
Physical connection to network_1
IP 1
Connected
What is Imported Result
IP address already used on network_1 of target system
Connected at time of export
IP address of export file
Not connected
Entity_1
IP 1
Connected at time of export
Entity_1
IP 1
Connected
Entity_1_1
IP 1
Not connected
EIO0000001114.15
419
Mapping Stage
What’s in This Chapter
Exporting and Importing Hardware Mappings ................................................ 449
Supervision Project Mapping Stage .............................................................. 457
Overview
This chapter describes how to map the Control and Supervision projects to the topological entities of the system, and to create communication channels, which allow you to use the I/O scanner function of controllers.
The following figure shows the position of the Mapping stage within the system engineering life cycle.
Refer to the
for a description of the purpose of this stage.
Control Project Mapping Stage
Overview
This section describes how to use the Project Explorer to map a logical Control
Participant project to one or more topological entities of the system to map the application to hardware channels. It also describes how to create and configure communication channels that allow using the controller I/O scanner function for communication with devices and peer to peer communication.
You must have completed the
and the
of the Control Participant project to proceed with the mapping stage.
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
420 EIO0000001114.15
Creating Control Project Executables
Overview
A Control executable allows you to associate to the logical Control Participant project a topological entity acting as
by mapping the Service .
Based on that, you can further map Hardware (I/O and communication modules) and Communication (communication channels for various communication modules) of this engine.
You can map a logical Control Participant project to several engines of the system.
To do so, create one executable for each engine.
For example, you can map the same logical Control Participant project to both:
• The controller that is in the plant by using executable_A.
• Another controller that is in the laboratory for test purposes by using executable_B.
Executables are associated to an Execution Domain , which serves as a filter for selecting applicable services, for example, to define the boundaries for peer to peer communication or runtime navigation services.
Creating Control Executables
To create a Control executable, proceed as follows.
Step
1
Action
In the Control Project Browser , right-click the Executables node of the Control project that you want to map and select Create Executable .
Result: A Control executable is created under the Executables node.
Control Executable Actions
The table describes the executable context menu commands.
Command
Manage
Build All
Description
Opens the Manage window in the work area of the Project Explorer , which lets you perform the following actions:
•
Service mapping, page 423 : Associates the logical Control Participant
project to an engine of the system.
• View and edit the
of the executable.
•
Communication mapping, page 424 : Defines the Modbus TCP Ethernet
(I/O scanning) communication channels between a controller and devices and/or other controllers for peer to peer communication.
•
: Lets you map the interfaces of the instances of the application that are assigned to the project to hardware channels of the controller.
Starts an automated process to integrate certain changes in the built Control
Participant project by performing an incremental build.
The command is available once you have done the service mapping.
Starts an automated process to
the built Control Participant project the first time or to recreate it to
integrate certain changes, page 470
that you have made to the Control Participant project or the system topology.
The command is available once you have done the service mapping.
Starts a generation of the Control Participant project followed by a build.
If you have not built the logical Control Participant project yet, the build process that is executed is the same as when you select the Build All command.
If the generation process does not complete successfully, no build is performed and information is displayed in the notification panel.
NOTE: After selecting the command, the abort icon is displayed in the
. Click the icon to cancel the task.
EIO0000001114.15
421
422
Command
Delete
Rename
Description
Opens the built Control project in the Control Participant, which allows you to view the program and configuration.
The command is available once you have built the Control Participant project.
Deletes the executable including any associated:
• Service and hardware mappings.
• Communication mappings.
NOTE:
• You cannot delete an executable that you have deployed. The software displays a message to inform you that the command cannot be executed.
• Deleting an executable does not delete
Lets you enter a new
for the executable.
Control Executable Properties
To open the properties of the executable, double-click it.
You can view and edit the following properties.
Property
Identifier
Description
The identifier must be unique within a Control Participant project.
Description
Execution
Domain
Optional.
You can enter a description for the executable with free form text.
Optional.
String.
Default value: Blank.
For the following types of communication, you can exchange data only if these executables have the same execution domain:
• For peer to peer communication: The executable of the owner project and the executable of the consumer project.
• For runtime navigation services (see EcoStruxure ™ Process Expert, Runtime
Navigation Services , User Guide ): The executable of the Control Participant project and the executable of the Supervision Participant project.
Values that you enter remain in the menu and you can select those of executables of other Control and Supervision Participant projects.
You can assign a logical execution domain to the executable with free form text.
You can modify the Execution Domain value at any time during the engineering life cycle.
NOTE: Leaving Execution Domain blank is considered as a value.
Build State Indicates the
of the executable.
Built On
Default value: Not Built
Date and time when you last built the executable successfully by using a build command.
Assigning an Execution Domain
To assign an execution domain to a Control executable, proceed as follows.
Step
1
2
Action
Double-click the executable to open its properties.
Select a value from the Execution Domain menu or enter a new value.
NOTE: To remove or change the associated execution domain, select the empty row at the top of the menu.
EIO0000001114.15
Mapping Services
Overview
The Service Mapping Editor opens within the Manage window when you doubleclick the Control
. It allows you to associate the logical
Control Participant project to entities acting as
through its
Control executable.
These engines are controllers and station nodes that exist in the topology of the system.
NOTE: If the Controller Family is not the same for the entity and the Control
that you want to map, you may not be able to map certain hardware I/O interfaces.
Mapping to Other Topological Entities
The software does not display STB islands, PROFIBUS Remote Masters (PRMs),
Modbus TCP, nor EtherNet/IP I/O devices in the Service Mapping Editor . For these topological entities, you need to map to the Control executable the controller that communicates with the entity.
NOTE: For PRMs, verify that the family of the controller is the same as the family that is selected in the
properties of the PRM, page 389 .
Mapping to a Redundant Controller
The software displays the identifier of the controller entity in the Service Mapping
Editor when you map the Control executable to a redundant controller. The mapping however, is performed with both the primary and the secondary controllers.
Mapping to a Station Node
When you map a Control executable to a station node for simulation purposes, the software displays the station node in the Service Mapping Editor window only if you have
created a ControlExpert service, page 379
in the station node first.
Changing the Service Mapping of Deployed Executables
If you have already deployed the Control executable to an engine of the system, you cannot change nor remove the service mapping of this executable. You need to create a new executable.
Mapping Services
To map the Control executable to an engine, proceed as follows.
EIO0000001114.15
423
Step
1
2
3
Action
Double-click the executable of the Control project that you want to map and select
Manage .
Result: The Service Mapping Editor opens.
Click the Engine menu.
Result: The menu displays the identifiers of compatible entities of the topology of the system.
Select an entity.
Result: The software:
• Maps the Control executable to the selected entity.
• Displays the Hardware Mapping tab at the bottom of the window. If the controller is
connected to an Ethernet network, page 399 , the
Communication Mapping tab appears also.
NOTE: To remove a mapping, in the Service Mapping Editor , right-click an entity and select Unmap .
Mapping Communication
Overview
To open the Communication Mapping Editor , click the Communication
Mapping tab within the Manage
. The tab appears once you have performed the
with a controller that is
connected to an Ethernet network, page 399
.
It allows you to define the communication channels that are used for communication between the controller that you have configured as client and service mapped and:
• Modbus TCP devices.
• STB islands.
• PRMs.
• Other controllers that are mapped to other logical Control Participant projects for peer to peer communication.
This method uses the I/O scanner service of the controller that is configured as client.
A communication channel is the logical representation, at the platform level, of the
Control Participant I/O scanner row.
During the creation of a communication channel, you can configure its
.
For peer to peer communication, the Communication Mapping Editor also allows you to map
to communication channels.
The software creates the I/O scanner lines that correspond to the communication channels in the controller acting as client during the
NOTE: For peer to peer communication, proceed with the communication mapping from the executable of the
NOTE: The communication mapping feature is not supported for executables that you have mapped to a station node that is emulating a simulator.
Prerequisites
For a description of the prerequisites for communication mapping, refer to the topics that describe the steps to complete:
• Communication with
.
•
Peer to peer communication, page 603
.
424 EIO0000001114.15
Communication Mapping Editor
The following figure shows an example of the Communication Mapping Editor window, which displays two peer to peer communication and one Modbus I/O device communication channels. It also indicates that free memory remains in the server counterpart to create additional peer to peer communication channels and/ or increase the size of existing channels.
Item
1
2
3
4
Description
Communication Channels pane, which displays the client memory area of the communication module of the controller that you have mapped to the Control executable.
There is one tab for each communication module (including the CPU communication module) that is configured in the controller and whose I/O scanning service is enabled.
Select a tab to display the communication channels that are configured in the memory area of the corresponding communication module of the controller acting as client.
<controller_identifier> (Server) tab, which displays the communication channels that are configured in the memory area of the controller when acting as server (if applicable). The information is displayed in the Server Memory Map pane.
Server Communication Counterparts - Device IO pane, which displays, topological entities such as Modbus TCP devices, PRMs, and STB islands, acting as servers, and with which you can define a communication channel. Click the arrow in the title bar to expand/collapse the pane
Server Communication Counterparts - Peer to Peer pane, which displays other Control projects, their executable, and the mapped controller entity with which you can define a communication channel. Click the arrow button in the title bar to expand/collapse the pane.
NOTE: When the executable of the Control project is mapped to a redundant controller, the Communication Channels pane displays only the client memory area of the communication module of the primary controller.
The figure shows an example of the Server Memory Map pane, which is displayed when you select the <controller_identifier> (Server) tab. It indicates that one peer to peer communication channel exists in the memory area of the client controller when acting as
EIO0000001114.15
The table describes the fields of the Communication Channels pane when you select the tab of the client communication module.
Column header
Type
Description
System
Indicates in the Size column, the size of memory that is reserved, and in the
Description column, the corresponding usage.
Free
425
426
Column header Description
Service
Server
Direction
Description
Size
Free
Last
Refer to the description of the Size column.
Device IO
Identifies channels that exist to communicate with Modbus TCP Ethernet devices, PRMs, and STB islands.
Peer to Peer
Identifies channels that exist to exchange data between Control Participant projects through the controllers that are mapped to these projects.
• For I/O device communication channels: element category.
communication element
Where element category is the category of the I/O scanner element, and communication element the name of the I/O scanner element for the I/O device.
• For peer to peer communication: project.executable
Where project
executable the identifier of the executable of this project.
Identifier of the server counterpart using the communication channel:
• The I/O device identifier for I/O device channels.
• The controller identifier for peer to peer communication channels.
Indicates the direction of the communication as Read , Write , or Both .
Displays the value of the parameters Read description and Write description that you can view in the
Channel Properties dialog box, page
NOTE: For channels of type System indicates the usage of the reserved memory.
For each channel, indicates the memory size that is allocated for reading from the server and writing to the server. It corresponds to the read and/or write size that you enter when you create a communication channel with a server counter part.
You can create communication channels until there is not enough sufficient memory left.
NOTE:
• For channel type Free , indicates the remaining free memory size that you can use to create communication channels. It is calculated based on the memory size that you have configured in the memory heap of the client by using the ClientMemoryLength
and on the memory allocation of existing communication channels.
Additional words used by the System (for example, for disabling flags) are also deducted from the memory size.
• For controllers of the M580 platform and NOC communication modules of any controller, the size value for channel type Free is not indicated because it is managed
.
Displays the remaining free memory in words for each existing peer to peer communication channel. The size is indicated separately for read and write channels when they exist. It is calculated based on Size and the size of
variables that you have mapped, page 435
to read and/or write communication channels.
For example, if the read channel size is 100 and you have mapped variables to this channel, which use up 10 words, the displayed value is 89. If you have mapped variables that use less than a word (a variable of BOOL data type), the free size can be indicated in decimals. These correspond to 1/16th of a word. For example, a free memory size indicated as 8.14 (out of 10) corresponds to 8 words and 14/16th of a word (2/16th of a word are used by variables of BOOL data type, which use up 1/16th of a word each).
NOTE: 1 word of each channel is reserved to move the channel address to manage the 32-bit alignment for peer to peer communication across
Modicon Quantum and M340 platforms. This word is deducted from the remaining free memory size.
Displays the value of the parameter Last value that you can select and adjust through the
Channel Properties dialog box, page 428
.
EIO0000001114.15
EIO0000001114.15
Column header
Scan
Timeout
Description
Displays the value of the parameter Scan rate that you can adjust through the
Channel Properties dialog box, page 428 .
Displays the value of the parameter Timeout that you can adjust through the
Channel Properties dialog box, page 428 .
The table describes the fields of the Server Communication Counterparts -
Device IO pane.
Field
Service
Server
Description
Read Size
Write Size
Description element category.communication element , where element category is the category of the I/O scanner element, and communication element the name of the I/O scanner element for the I/O device.
Identifier of the STB island, PRM, or Modbus TCP device entity, acting as server and with which you can create a communication channel.
Description of the data to be exchanged through the channel.
Number of words that are read from the server.
Number of words that are written to the server.
The table describes the fields of the Server Communication Counterparts -
Peer to Peer pane.
Field
Service
Server
Free
Description project.executable
Where project is the identifier of the Control Participant project (
350 ) that exposes the variables and
executable the identifier of the executable of this project.
Identifier of the controller mapped to the owner project described in the Service field, which acts as counterpart, and that is available to create a communication channel.
When no communication channel exists, indicates the number of words that you have configured in the memory heap of the controller acting as server, which is defined in the Server field.
When you create a communication channel, the read and write sizes that you define in the Peer to Peer: Properties dialog box are deducted from this value.
Customizing Column Display
In the various panes of the editor, you can choose which columns you want to see by right-clicking a column header and selecting Customize . Certain columns are always shown.
When you hide a column for which a filter is applied, the filter is cleared.
Communication Channel Actions
Right-click a communication channel in the Communication Channels pane to display a context menu with the following commands.
Command Description
Map
Variables
Opens the
variables and define the relative position of such variables in the selected communication channel.
, which allows you to map network
The command is available only for peer to peer communication channels.
Unmap
Removes the selected communication channel, page 433 .
Properties Opens the Device IO: Properties or Peer to Peer: Properties
which lets you view and/or adjust parameter values of the selected communication channel.
427
428
Communication Channel Properties
When you
create a communication channel, page 431
, the software opens the appropriate dialog box, which allows you to adjust the values of the parameters of the communication channel in the memory heap of the client.
NOTE: You can view and/or adjust the values of certain parameters of existing communication channels.
The following figure shows an example of the Device IO: Properties dialog box that the software opens when you create a channel to communicate with an STB island. The dialog box is also displayed when you right-click the existing communication channel and select Properties .
The following figure shows an example of the Peer to Peer: Properties dialog box that the software opens when you create a peer to peer communication channel. The dialog box is also displayed when you right-click the existing communication channel and select Properties .
EIO0000001114.15
EIO0000001114.15
Parameter
Service
Server
Communication Service
Read description
Read size
Write description
Write size
Last value
Description
Refer to the description of the Service column of the Server Communication
Counterparts - Device IO or Server Communication Counterparts - Peer to
Peer pane.
Refer to the description of the Server column of the Server Communication
Counterparts - Device IO or Server Communication Counterparts - Peer to
Peer pane.
The parameter appears only in the Peer to Peer: Properties dialog box.
Identifier of the communication module device through which data is exchanged.
You can select from the communication modules that exist in the server controller and which are connected to the same Ethernet network as the client controller communication module.
Description for the read channel.
NOTE: For peer to peer communication channels, the default value is blank.
You must enter a description.
Number of words that are allocated to the channel and read from the server counterpart.
The corresponding memory size is reserved in both the client and server memory heap.
NOTE: For peer to peer communication channels:
• Default value: 0
• Maximum value: 125
• You can adjust the value:
◦ The total value of columns Read size and Write size cannot exceed the lowest value indicated in either column Free of the Server
Communication Counterparts pane or column Size (row Free ) of the Communication Channels pane.
◦ You cannot set the size to a value that is lower than the total size of variables that are
to the channel.
◦ You can increase the size as long as there is no overlapping channel in the server memory heap within the new size limit.
Description for the write channel.
NOTE: For peer to peer communication channels, the default value is blank. If you enter a value in the Write size field, you must enter a description.
Number of words that are allocated to the channel and written to the server counterpart.
The corresponding memory size is reserved in both the client and server memory heap.
NOTE: For peer to peer communication channels:
• Default value: 0
• Maximum value: 100
• You can adjust the value:
◦ The total value of columns Read size and Write size cannot exceed the lowest value indicated in either column Free of the Server
Communication Counterparts pane or column Size (row Free ) of the Communication Channels pane.
◦ You cannot set the size to a value that is lower than the total size of variables that are
to the channel.
◦ You can increase the size as long as there is no overlapping channel in the server memory heap within the new size limit.
Value that is retained when a communication interruption occurs.
Select between:
• Reset : Set to 0
• Hold : Last value
Default value: Hold
NOTE: This setting applies to the I/O scanner line created in the Control
Participant project. When communicating with an I/O device modeled by a device template, confirm that the DFB contained in the device template supports the selected setting. If not, the value of variables read from the
429
430
Parameter
Scan rate
Timeout
Description device may not be synchronized with the value sent to the Supervision layer by the DFB.
For information on parameters of DFBs of device templates, refer to the help of the corresponding template library, which documents the Control resources
(services).
The rate at which data is scanned in the channel.
Range: 0...65535 ms
Default value: 60 ms
If you change the default value, verify that the new value is a multiple of the repetitive rate step.
For more information, refer to the Control Participant help.
The maximum interval between responses from the entity for the channel. After this time expires, the communication is considered interrupted, and the last value is retained according to the configuration of the Last value parameter.
Range: 1...65535 ms
Interval: 1 ms
Default value: 1000 ms
NOTE: Verify that the TimeOut value is greater than the ScanRate value.
For more information, refer to the Control Participant help.
Server-Side Communication Channel Properties
Once you have created a peer to peer communication channel in the memory heap of the client, you can view properties of the channel server-side by rightclicking the communication channel and selecting Properties .
To view the communication channel, first
the Communication
Mapping Editor from the owner project.
NOTE: You can open the an identical properties dialog box for the communication channel that exists in the client controller when acting as server by selecting the <controller_identifier> (Server) tab from the client-side communication mapping window, right-clicking the communication channel in the Server Memory Map pane, and selecting Properties .
NOTE: When you modify the properties of a communication channel serverside, and you have already deployed the associated built Control Participant project, you can only apply the change to the engine, using the
command, which requires stopping the controller.
The following figure shows an example of the Server Peer to Peer Channel:
Properties dialog box, which indicates properties of the peer to peer communication channel server-side.
EIO0000001114.15
EIO0000001114.15
Parameter
Partner
Client
Description
Direction
Start position
Size
Description project.executable
Where project is the identifier of the Control Participant project (
) that receives the variables and executable the identifier of the executable of this project.
Identifier of the controller entity (server) to which the owner project is mapped.
Description for the read or write channel.
Read or Write .
Starting address of the communication channel in the memory heap of the server.
The value is editable, allowing you to
move communication channels serverside, page 434 .
Number of words that are allocated to the communication channel server-side.
Communication Channel Position
Communication channels are contiguous in the memory area of the controller acting as client.
Communication Channel Order
Device I/O communication channels appear in the memory area reserved for this type of communication channel in the order you create them.
When both peer to peer communication channels and device I/O communication channels exist then device I/O communication channels are positioned after peer to peer communication channels.
Restrictions when Creating Communication Channels
For each communication module of a controller acting as client (a tab of the
Communication Channels pane), you cannot create communication channels with several executables that are mapped to the same controller.
For example, if the following executables appear in the Service column of the
Server Communication Counterparts - Peer to Peer pane and both are mapped (service mapping) to controller Controller_1 ( Server column):
• Project_1.Executable_1
• Project_2.Executable_2
Then, for a given client controller communication module, you can create a communication channel only with either one of these executables.
Creating Communication Channels
When you create a communication channel, and you have already deployed the associated built Control Participant project, you can only apply the change to the engine, using the
Deploy Built Project , page 514
command, which requires stopping the controller.
NOTE: Following the creation of a peer to peer communication channel, you can view it in the memory heap of the server, in the Server Memory Map pane (<controller_Identifier> (server) tab), by
the
Communication Mapping Editor from the counterpart owner project.
Creating a peer to peer communication channel in the executable of the consumer project also affects the executable of the counterpart owner project. To apply changes, you need to start/stop the controllers to which these executables are deployed in the right order; otherwise incorrect data may be read and/or written.
431
432
WARNING
LOSS OF CONTROL
• Deploy the executables to the controllers between which the peer to peer communication channel exists.
• Start/stop controllers in the right order.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
To create a communication channel between the client and the server counterpart, proceed as follows.
Step
1
2
3
Action
From one of the Server Communication Counterparts panes, drag the server counterpart with which you want to create a communication channel to the
Communication Channels pane.
Result: The corresponding communication channel Properties dialog box opens.
Adjust the values of the communication channel properties as required.
Click OK .
Result: The software:
• Creates a communication channel between the selected server counterpart and the client with the parameter values that you have configured in the corresponding
Properties dialog box.
• Shifts the information of the server counterpart to the respective columns in the
Communication Channels pane.
• Updates values of the Size and Free columns.
NOTE: Click Cancel to close the Properties dialog box without creating the communication channel.
NOTE:
• If there is no sufficient space in the memory of the client or server to accommodate the communication channel, the software displays a notification and you cannot create the channel. Adjust the client or server memory properties of the corresponding controller entity and repeat.
• The validation of sufficient space in the memory of the client is not performed for controllers of the M580 platform and NOC communication modules of any controller because the free memory size is managed
.
Modifying Communication Channel Properties
You can view modify the values of certain parameters of existing communication channels in the Properties dialog box of the channel.
When you modify the properties of a communication channel, and you have already deployed the associated built Control Participant project, you can only apply the change to the engine, using the
Deploy Built Project , page 514
command, which requires stopping the controller.
Modifying peer to peer communication channel properties in the executable of the consumer project also affects the executable of the counterpart owner project. To apply changes, you need to start/stop the controllers to which these executables are deployed in the right order; otherwise incorrect data may be read and/or written.
EIO0000001114.15
WARNING
LOSS OF CONTROL
• Deploy the executables to the controllers between which the peer to peer communication channel exists.
• Start/stop controllers in the right order.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
To modify properties of an existing communication channel, proceed as follows.
Step
1
2
3
Action
In the Communication Channels pane, right-click the communication channel and select Properties .
Result: The software opens the Properties dialog box.
NOTE: The Properties dialog box does not open if the Variable Mapping Editor
of this communication channel is open.
Adjust the values of the communication channel properties as required.
Click OK .
Result: The software:
• Adjusts the communication channel properties.
• Updates the values that are displayed in the Communication Mapping Editor .
• Displays information on the modification in the notification panel.
NOTE: Click Cancel to close the Properties dialog box without creating the communication channel.
NOTE: If the software is not able to apply your modification, it displays a notification. The validation of sufficient space in the memory of the client is not performed for controllers of the M580 platform and NOC communication modules of any controller because the free memory size is managed
Unmapping Communication Channels
Unmapping a communication channel has the following impacts:
• The memory size allocated to the channel is released in the memory heap of the client and of the server.
• Other channels that exist in the memory heap of the client are realigned to be contiguous.
• Network variables that are
to the deleted channel are unmapped from the client and server communication channels.
• The
of the Control executable to which the controller is mapped changes to out of date if it is built.
• When you unmap a communication channel and you have already deployed the associated built Control Participant project, you can only apply the change to the engine, using the
Deploy Built Project , page 514
command, which requires stopping the controller.
The executables of both the consumer and the counterpart owner Control projects are affected. To apply changes, you need to start/stop the controllers to which these executables are deployed in the right order; otherwise incorrect data may be read and/or written.
EIO0000001114.15
433
434
WARNING
LOSS OF CONTROL
• Deploy the executables to the controllers between which the peer to peer communication channel exists.
• Start/stop controllers in the right order.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
To unmap a communication channel, proceed as follows.
Step
1
2
Action
In the Communication Channels pane, right-click the communication channel and select Unmap .
Result: The software opens the Unmap dialog box.
Click OK to confirm.
Result: The software:
• Unmaps the communication channel between the selected server counterpart and the client.
• Displays the server counterpart in the corresponding Server Communication
Counterparts pane.
• Updates values of the Size and Free columns.
NOTE: Click No to close the Unmap dialog box without unmapping the channel.
Moving Communication Channels Server-Side
When you move an existing peer to peer communication channel within the memory heap of the server counterpart:
• You can only enter an odd starting address.
• The starting address has to leave enough free memory area to fit the size of the communication channel; otherwise you cannot move the channel.
When you move a communication channel and you have already deployed the associated built Control Participant project, you can only apply the change to the engine, using the
Deploy Built Project , page 514
command, which requires stopping the controller.
Moving a peer to peer communication channel in the executable of the owner project also affects the executable of the consumer counterpart project. To apply changes, you need to start/stop the controllers to which these executables are deployed in the right order; otherwise incorrect data may be read and/or written.
WARNING
LOSS OF CONTROL
• Deploy the executables to the controllers between which the peer to peer communication channel exists.
• Start/stop controllers in the right order.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
To move a peer to peer communication channel in the memory heap of the server counterpart, proceed as follows.
Step
1
2
Action
the Communication Mapping Editor from the
project.
Select the <controller_identifier> (Server) tab to display the memory heap of the server.
EIO0000001114.15
Step Action
3
4
5
Result: The software displays the Server Memory Map pane.
Right-click the communication channel that you want to move and select Properties .
Result: The software opens the Server Peer to Peer Channel: Properties dialog box.
Enter a new positive, odd integer value in the Start position field.
Click OK .
Result: If sufficient free memory is available at the specified position, the software:
• Moves the selected communication channel to the new start position.
• Updates values of the Start Position and Size columns in the Server Memory
Map pane of the Communication Mapping Editor .
If not, the software displays a dialog box informing you that it cannot move the communication channel.
NOTE: Click Cancel to close the Server Peer to Peer Channel: Properties dialog box without moving the channel.
Mapping Network Variables
Overview
The Variable Mapping Editor opens when you right-click a peer to peer communication channel in the Communication Mapping
and select Map Variables .
It allows you to map variables of the consumer project to peer to peer communication channels that exist in the memory heap of the client:
•
Network variables, page 350 : To read data from the server.
• Variables, which are the counterpart to network variables that exist in the owner project: To write data to the server.
You can assign a position manually or let the software manage positions.
The software indicates if variables are already mapped to another channel and lets you open the Variable Mapping Editor of this channel.
NOTE: You can work simultaneously on different communication channels.
The variable mappings that are performed on a channel and that affect other channels are reflected right away on these channels.
NOTE: The first time you open the Variable Mapping Editor and the first time you open it after refining the project, it may take time before the window appears.
Prerequisites
To proceed with the variable mapping, first
create a peer to peer communication channel, page 424
.
EIO0000001114.15
435
Variable Mapping Editor
The following figure shows an example of the Variable Mapping Editor .
436
Item
1
2
3
4
5
Description
Information bar, which displays scan rate and timeout properties of the selected communication channel, as well as the check box to
position variables automatically, page 438
.
Pane that displays the network variables that the client reads from its server counterpart, and that are mapped to the selected communication channel. In this example, network variable Var_3 , which is created in the consumer project is mapped to the communication channel that exists in the client controller.
Pane that displays the network variables that exist in the consumer project and that you can map to the communication channel that is created in the client controller. In this example, network variable Var_2 has already been mapped by opening the
Variable Mapping Editor from the owner project and using its counterpart variable to
write to the server, page 350 . You cannot map it again. You can view its mapping
information by right-clicking Mapped .
Pane that displays the variables that the client writes to its server counterpart, and that are mapped to the selected communication channel. In this example, no variables are mapped.
Pane that displays the variables that exist in the consumer project for which a corresponding network variable exists in the owner project and that you can map to the communication channel. In this example, Var_1 exists as network variable in the owner project and here you can map its counterpart variable to the channel that exists in the client controller to
write to the server, page 350 .
The table describes the fields of the Network Variables and Variables panes.
Column header
Identifier
Type
Size
Description
Description
Identifier of the variable.
Data type of the variable.
If the software detects inconsistencies in the type, the variable is shown in red color and a tooltip provides additional information.
NOTE: When peer to peer communication with the topological entity acting as client is implemented by using an M580 CPU or a NOC communication module, only variables of the
reference type (REF_TO) are shown, page 354 .
Size of the variable in words.
NOTE: For variables of a size of less than 1 word, the size is displayed in corresponding fractions of words (for example, for data type BOOL, the size is displayed in 1/16th of words).
Displays the contents of the Comment property of the Control Participant of the variable in the consumer project.
EIO0000001114.15
EIO0000001114.15
Column header
Status
Description
Map
Description
Indicates the mapping status of the variable.
Possible values:
• Free : The variable is not yet mapped to a communication channel.
• Mapped : The variable is already mapped to another communication channel of the Control executable.
Click the filter icon in the column header to select the statuses that you want to see.
NOTE: You can open the Variable Mapping Editor of the communication channel to which a variable with status Mapped is mapped by right-clicking the variable and selecting Go To Variable Mapping Editor .
For variables that are mapped to another communication channel, displays the content of the Read description or Write description field of this channel; otherwise the field is empty.
The table describes the fields of the Read from Server and Write to Server panes.
Column header
Description
Pane title bar For the Read from Server pane, displays:
• The contents of the field Read description .
• The read size (in words) of the selected channel in the client memory heap and the remaining words available to map variables.
For the Write to Server pane, displays:
• The contents of the field Write description .
• The write size (in words) of the selected channel in the client memory heap and the remaining words available to map variables.
NOTE: One word of each channel is reserved to move the channel address to manage the
for peer to peer communication across
Modicon Quantum, M580, and M340 platforms.
Position Position of the word to which you have mapped the variable within the memory size that you have allocated to the channel or the next available empty position within a word or of the next word.
The position in the communication channel is the same in the client and in the server.
Identifier
For variables of a size of less than 1 word, positions are displayed using the x.y
format where:
• x represents the word
• y represents the position inside the word
Identifier of the mapped variable or Empty .
Empty : Appears for the next available position to which you can map variables.
Type
Size
Description
Type of the mapped variable, of the remaining space in a word, or Any .
To map variables to the remaining space of a word, the data type of the variables needs to match.
Any : Appears when Identifier is Empty . You can map a variable of any data type to this space.
Indicates either, the size of the mapped variable in words, the size of the remaining space inside a word, or the size of the empty space available for mapping.
NOTE: For mapped variables of a size of less than 1 word, the size is displayed in corresponding fractions of words (for example, for data type
BOOL, the size is displayed in 1/16th of words). The empty space of a word is indicated similarly.
Displays the contents of the Comment property of the Control Participant of the variable in the consumer project.
Customizing Column Display
In the various panes of the editor, you can choose which columns you want to see by right-clicking a column header and selecting Customize . Certain columns are always shown.
437
438
When you hide a column for which a filter is applied, the filter is cleared.
Position of Mapped Variables
The Position variables automatically check box lets the software define automatically the position of the variables that you are mapping or moving:
• Selected (default setting): The software automatically maps or moves the variable to the compatible empty position that you have selected.
If you have selected several variables:
◦ If the space in the empty position that you have chosen allows it, variables are mapped or moved contiguously starting from this position.
◦ If there is not sufficient contiguous space in the empty position that you have chosen to map or move all variables but is sufficient for at least one variable, the software opens the Mapping Confirmation dialog box to inform you. You have the following options:
Yes : Maps or moves the variables for which sufficient space is available at the chosen empty position and maps or moves the other ones to the next available position.
No : Maps or moves only the variables for which sufficient space is available at the chosen empty position but does not map or move the other ones. It then opens a dialog box to inform you of which variables it could not map or move. These variables remain in the Network Variables or
Variables section.
Cancel : Cancels the mapping or move operation.
• Cleared: The software opens the Select Memory Position dialog box, which allows you to select any available compatible position to map or move the variable within the read or write size that you have defined for the channel.
If you have selected several variables, the position that you select in the
Select Memory Position dialog box applies to the first variable only. The software then maps or moves the other variables in the contiguous space that is available right after the position hat you have selected. If not sufficient contiguous space is available, it informs you of which variables it was not able to map or move because of insufficient space.
In both cases, the software verifies that the position satisfies the variable mapping rules based on its size. The Mapping Confirmation dialog box opens only if there is empty space in a channel before and after an already mapped variable.
NOTE: You can map 32-bit variables (for example, variables of type REAL or
DWORD) only to odd addresses in the Variable Mapping Editor . The variables are aligned correctly during the
depending on the controller platform.
EIO0000001114.15
Example of Variable Mapping Editor Usage
In this example, network variable Var_1 is already mapped to a peer to peer communication channel and there is one word of free space available before
(position 1) and five words available after (position 3). The Position variables automatically check box is selected.
Var_2 and Var_3 are selected and dragged to be mapped at position 1. Because there is no sufficient space to map both variables but only one of them at position 1, the software displays the Mapping
Confirmation dialog box when you release the mouse button.
If you click Yes , the software maps Var_2 at position 1, which you had selected and Var_3 at position 3, which is the next available space where the variable fits.
If you click No , the software maps only Var_2 at position 1, which is the only variable out of the two selected ones that fits in this position. It then informs you that Var_3 is not mapped by opening a dialog box.
Var_3 remains in the Network
Variables section and is available for mapping.
EIO0000001114.15
Variable Mapping Rules
The software applies the following rules when mapping a variable:
• A variable cannot be mapped to a position overlapping with another mapped variable.
• A variable cannot be mapped if:
439
440
◦ It is split up between two or more positions.
◦ It does not fit entirely inside the communication channel.
Mapping Network Variables
Mapping variables to a peer to peer communication channel affects the executables of both the consumer and the counterpart owner projects. To apply changes, you need to start/stop the controllers to which these executables are deployed in the right order; otherwise incorrect data may be read and/or written.
WARNING
LOSS OF CONTROL
• Deploy the executables to the controllers between which the peer to peer communication channel exists.
• Start/stop controllers in the right order.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
To map network variables (to read from the server) to a communication channel, proceed as follows.
Step Action
1 In the Communication Mapping Editor , right-click the communication channel to which you want to map variables and select
Map Variables .
2
3
Clear the Position variables automatically check box if you want to select the position to map the variable yourself.
In the Network Variables pane, select the variables that you want to map and drag them onto a compatible empty position in the Read from Server pane.
4
Result
Result: The Variable Mapping Editor opens.
Refer to Position of Mapped Variables for
Result: If you have unselected the Map on
Top check box, the software opens the
Select Memory Position dialog box.
Proceed to step 4; otherwise the software:
•
to the available space starting from the position that you have selected and satisfying the mapping rules.
• Displays them in the Read from
Server pane.
• Removes the variable from the
Network Variables pane.
• Informs you if it was not able to map any variable.
-
5
In the Select Memory Position dialog box, click the arrow button of the Memory
Position field and select a position to map the variable.
Click OK .
NOTE: Click Cancel to close the
Select a Memory Position dialog box without mapping the variable.
Result: The software:
•
to the selected position.
• Displays them in the Read from
Server pane.
• Removes the variable from the
Network Variables pane.
• Informs you if it was not able to map any variable.
NOTE: Proceed in the same way to map a variable (to write to the server) to the selected communication channel by using the Variables and Write to
Server panes of the Variable Mapping Editor .
EIO0000001114.15
EIO0000001114.15
Changing a Variable Mapping Position
To change the mapping position of a variable, drag it to the new position.
You can select several variables to move them at once.
Moving variables mapped to a peer to peer communication channel affects the executables of both the consumer and the counterpart owner projects. To apply changes, you need to start/stop the controllers to which these executables are deployed in the right order; otherwise incorrect data may be read and/or written.
WARNING
LOSS OF CONTROL
• Deploy the executables to the controllers between which the peer to peer communication channel exists.
• Start/stop controllers in the right order.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
To change the mapping position of network variables or variables with the Select a Memory Position dialog box selected, proceed as follows.
Step Action
1 Select the variables in the Read from
Server or Write to Server pane and drag them to the new compatible empty position.
Result
Result: The software:
• Unmaps the variables from their current positions, which become available for mapping.
•
to the available space starting from the new position that you have selected and satisfying the mapping rules.
• Informs you if it was not able to map any variable.
To change the mapping position of network variables or variables with the Select a Memory Position dialog box cleared, proceed as follows.
Step Action
1 Select the variables in the Read from
Server or Write to Server pane and drag them to the new compatible empty position.
2
Result
Result: The software:
• Opens the Select Memory Position dialog box.
-
3
In the Select Memory Position dialog box, click the arrow button of the Memory
Position field and select a position to map the variable.
Click OK .
NOTE: Click Cancel to close the
Select a Memory Position dialog box without mapping the variable.
Result: The software:
•
to the selected position.
• Informs you if it was not able to map any variable.
Removing a Variable from a Communication Channel
To remove a mapped variable from the communication channel, unmap it.
Unmapping variables mapped from a peer to peer communication channel affects the executables of both the consumer and the counterpart owner projects. To apply changes, you need to start/stop the controllers to which these executables are deployed in the right order; otherwise incorrect data may be read and/or written.
441
WARNING
LOSS OF CONTROL
• Deploy the executables to the controllers between which the peer to peer communication channel exists.
• Start/stop controllers in the right order.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
To unmap a network variable or variable, proceed as follows.
Step
1
Action right-click the variable in the Read from Server or Write to Server pane and select
Unmap .
Result: The software:
• Unmaps the variable from the selected position, which becomes available for mapping.
• Removes the variable from the corresponding Read from Server or Write to
Server pane.
• Displays the variable in the corresponding Network Variables or Variables pane.
NOTE: You can also right-click the variable and press Del .
Deleting or Changing Mapped Variables
A network variable or variable is unmapped from the communication channel if you delete either:
• The network variable itself.
• The corresponding variable in the owner project.
It is also unmapped from the communication channel if you change any of the following parameters of it, in either the owner or the consumer project:
• Name
• Type (ID or version)
• Size
Corresponding information is displayed in the notification panel.
Mapping Hardware
442
Overview
To open the Hardware Mapping Editor , click the Hardware Mapping tab within the Manage
window, page 421 . The tab appears once you have performed the
with a controller.
It allows you to map the interfaces of instances of the application to compatible hardware interfaces representing the I/O and communication modules of the entity that you have service mapped to the Control executable of the project.
Application objects that expose mapping interfaces are instances of either:
• HAL templates (for example, $DISignal_UL ).
• Communication port templates (for example, $EMPortM ).
• Hardware application templates (for example, $TesysTE or $TSignCptBmx ).
The mapping interfaces of application objects appear in the Hardware Mapping
Editor once you assign their facets to the Control project; even without generating them. They are updated in the mapping editor when you make changes in the application (for example, rename an instance or disable a service) and/or generate the Control project (for example, after setting a facet to Out Of Date or
Deleted ).
EIO0000001114.15
You can map interfaces to modules that are connected:
• Physically (for example, in-rack I/O modules).
Their topological mapping interfaces are updated in the mapping editor when you
in the Control Participant Configuration window.
• Logically (for example, Modbus TCP Device I/Os, PRMs, or STB islands).
Their topological mapping interfaces appear in the mapping editor when you
the device to the same Ethernet network as the controller.
If you have created several executables, proceed with the hardware mapping for each one of them.
To facilitate the management of many mappings, you can
export and import hardware mappings, page 449
.
NOTE: The software
marks variables and DFB instances, page 472
that are used for the hardware mapping when you build the logical Control Participant project.
Mapping Modbus TCP Devices, PRMs, and STB Islands
For the following entities communicating with the controller through Modbus TCP implicit messaging (I/O scanning), and that are connected to the same Ethernet network as the controller, you can proceed with the hardware mapping:
• Modbus TCP I/O devices: Even without existing communication channels.
• STB islands and PRMs: Only after you create a
communication channel, page 424 .
NOTE: You need to instantiate the necessary application templates first. For details, refer to the topic describing how to
.
Mapping Hardware with a Simulator
Hardware mapping is not supported, and not required, for executables that you have mapped to a station node running software emulating a simulator.
Mapping Generic Device Interfaces
When a topological entity uses the $EGenericDeviceHW , $EIPGenericDeviceHW , or $EGenericPBSlave template to model a device, a generic hardware mapping interface is available for this device in the Hardware Mapping Editor . You can use it to map the interface of a project facet to this I/O device. However, because of the generic nature of the interface, the software does not verify if both interfaces are
before proceeding with the mapping.
Opening the Hardware Mapping Editor in Read-Only Mode
The editor can open in read-only mode, for example, if the executable is locked by another process such as the configuration of the controller. In this case, hardware mapping creation, modification, and import are not allowed.
EIO0000001114.15
443
Hardware Mapping Editor
The following figure shows an example of the Hardware Mapping Editor window.
444
4
5
Item
1
2
3
Description
Topological devices pane (left, gray title bar), which displays the interfaces of the controller entity that you have mapped to the executable of the Control project. It also displays interfaces of Modbus TCP/EtherNet/IP device, PRM, and STB island entities that are connected to the same Ethernet network as the controller. A communication mapping for PRM and STB island entities needs to exist.
Project facet pane (right, blue title bar), which displays the mapping interfaces of the facets that you have assigned to the Control project, including interfaces of facets of
Modbus TCP/EtherNet/IP explicit messaging device instances, Modbus serial device instances, and the corresponding communication port instances.
Check box to
display only compatible interfaces, page 445
that meet the selected filter criteria in both panes. The functionality helps locate compatible interfaces when you have many different ones in either pane. The functionality is enabled by default.
Lets you
to file (.csv) the existing hardware mappings and the interfaces of project facets that have not been mapped yet.
Lets you
valid and compatible hardware mappings that you have created outside the Hardware Mapping Editor and that are contained in a file (.csv).
NOTE: When the executable of the Control project is mapped to a redundant controller, the topological devices pane displays only the hardware interfaces of the primary controller.
Editor section
Topological devices pane
Column header
HWInstance
HWTemplate
HWMapping
Interface
Description
Identifier of the topological device.
Displays:
• Controller devices.
• Modbus TCP and EtherNet/IP devices that are physically connected to the same network as the controller.
• PRM entities and STB island devices after you have completed the communication mapping.
NOTE: The designation of devices is described in the topic showing the
representation of topological entities, page
Identifier of the template that is used by the topological device.
Identifier of the facet that models the hardware channel followed by the identifier of the facet template.
HWInterfaceType Type of the mapping interface and role.
AppInstance
AppFacet
These columns are blank before you start the mapping process.
The software moves the information contained in the corresponding columns of the project facet pane to these columns when you map the project facet interface.
AppTemplate
AppMapping
Interface
AppInterface-
Type
EIO0000001114.15
Editor section
Project facet pane
Column header
AppInstance
AppFacet
AppTemplate
AppMapping
Interface
AppInterface-
Type
Description
Identifier of the instance that references the facet.
Identifier of the facet that is assigned to the Control project.
Identifier of the template that is used by the instance.
Identifier of the hardware mapping interface that is exposed by the facet.
Type of the mapping interface and role.
The prefix of the type indicates the type of I/O hardware channel:
• DI : Digital input
• DO : Digital output
• AI : Analog input
• AO : Analog output
Customizing Column Display
In the various panes of the editor, you can choose which columns you want to see by right-clicking a column header and selecting Customize . Certain columns are always shown.
When you hide a column for which a filter is applied, the filter is cleared.
Displaying Compatible Interfaces
To show only interfaces that are compatible in both panes, proceed as follows.
Step
1
2
3
4
Action
Verify that the Display only compatible interfaces on filtering
is selected.
In either pane, click the filter icon of the column that you want to use to filter interfaces.
Result: The
opens.
Enter criteria to be used as filter and click Filter .
Result:
• In the pane in which you have applied the filter, only interfaces that meet the filter criteria are shown.
• In the other pane, a filter is automatically applied to the *InterfaceType column to show only interfaces that are compatible with those that result of the filter that you have applied.
You can apply additional filters in either pane to further refine results.
NOTE:
• When you clear the filter in either pane, a filter is applied to the
*InterfaceType column in the other pane to show only interfaces that are compatible with those displayed in the pane where you have cleared the filter.
• To clear filters in both panes, clear the Display only compatible interfaces on filtering check box.
EIO0000001114.15
445
446
The following example illustrates the use of the automatic filter mechanism to display only compatible interfaces. The figures shows only a partial view of the
Hardware Mapping Editor to simplify the example.
Item
1
2
Description
A controller is configured with an analog input, an analog output, and a digital input module. The corresponding interfaces appear in the HWInterfaceType column of the topological devices pane.
Facets of analog input, digital input and digital output templates are assigned to the project and the template identifiers appear in the AppTemplate column of the project facet pane.
In this step, the objective is to show only topological interfaces that are compatible with digital input interfaces to perform the hardware mapping between the two.
Item
1
2
3
Description
Verify that the
is selected.
The AppTemplate column, a filter was applied to show only interfaces of digital input templates. One interface meets this criteria.
In the topological devices pane, the software has automatically applied a filter to the
HWInterfaceType column to show only interfaces of digital input modules. Interfaces of other modules are not shown anymore. You can map the interface of the project facet to any of these topological input channels.
EIO0000001114.15
In this step, the objective is to show only project facet interfaces that are compatible with the topological interfaces of the modules present in the controller configuration. This can be helpful to verify if any hardware-compatible project facet interfaces have not yet been mapped.
EIO0000001114.15
Item
1
2
3
Description
In the topological devices pane, the filter that the software had automatically applied to the HWInterfaceType column was cleared by the user. The column now shows all the interfaces of the various modules of the controller to which you can map project facet interfaces.
In the project facet pane, the software has cleared the filter of the AppTemplate column.
Instead, it has applied a filter to the AppInterfaceType column to show only interfaces that are compatible with the topological interfaces that are exposed by the configuration. As a result, the interface of the digital output template is not shown anymore because the configuration does not contain a digital output module.
The check box must be selected.
Mapping Hardware
To map facets of the Control project to topological interfaces of an entity, proceed as follows.
Step
1
2
3
Action
In the right-hand project facet pane, locate and select the facets of the Control project that you want to map. Use filters if necessary.
Result: The selected facets are highlighted.
In the left hand, topological device pane, locate the topological interfaces to which you want to map the facets that you have selected in step 1. Use filters if necessary.
Result: The selected instance is highlighted.
NOTE: For the mapping to succeed, the type of the interface that is displayed in both *InterfaceType columns needs to be identical and the interface roles need to be compatible.
For example, interface type $DIChannel with roles HO (Hardware Object) and SO
(Signal Object).
From the project facet pane, drag the selected project facets onto the topological interfaces.
Result: The software shifts the information of the project facets to the respective columns of the topological device pane.
NOTE: If the interfaces do not match, a tooltip opens and they are not mapped.
NOTE: To map an already mapped project facet interface to a different topological device with matching interface, drag the mapped project facet onto another compatible topological device interface.
447
448
Deleting Hardware Mappings
To delete the mapping of one or more already mapped project facet interfaces, proceed as follows.
Step
1
2
Action
In the topological device pane, select the rows that correspond to the mappings.
Proceed either way:
• Drag the selection back to the project facet pane.
• Press Del and confirm the command.
• Right-click the selection, click Unmap , and confirm the command.
Result: The selected facet appear again in the project facet pane.
NOTE: To delete all the mappings at once, click inside the topological device pane, press Ctrl + A , and use Del or Unmap .
Mapping Several Project Facet Interfaces Simultaneously
You can drag more than one project facet interface onto the topological device pane at once by using multiple selection. The software maps the project facet interfaces to contiguous topological interfaces in the order they are displayed in the tooltip while dragging them.
The interfaces of each project facet/topological device pair need to match to complete the mapping process.
If there is a missing or incompatible topological interface in between, the first matching interfaces are mapped but not the remaining ones, which appear again in the right-hand project facet pane. A message informs you of the project facet interfaces that could not be mapped.
NOTE: Use the filters to display topological devices in the desired sequence.
Changing the Application and Projects After Mapping
If you make any of the following changes to a facet that you have already mapped by using the Hardware Mapping Editor , the software deletes the mapping and makes the facet available again for mapping:
•
the facet and generating the project or section.
• Deleting the instance referencing the facet.
• Unselecting the
that corresponds to the facet.
Changing the Topology After Mapping
If you make any of the following changes to topological devices whose interfaces you have already mapped by using the Hardware Mapping Editor , the software may delete the mapping. In such case, it makes the corresponding project facets available again for mapping:
• Deleting the controller entity.
• Changing the CPU module of the controller entity.
• Deleting the I/O device.
• Moving the I/O device.
• Deleting the communication channel with an STB island or a PROFIBUS
PRM Master.
• Updating templates of topological entities.
Changing Hardware Mapping After Deploying
Consider a Control project that contains one or more facets representing signals that need to be mapped to I/O modules.
EIO0000001114.15
You build and deploy the Control project but without doing these hardware mappings.
If you then do the hardware mapping, build the Control project, and select the
Deploy changes / Undo Online Changes command to
to the mapped signals are deployed.
However, the current value of these variables remains unchanged in the deployed
Control project.
The change becomes effective, either through a cold start of the controller or by replacing the current value of the variables in the animation table by their new initial value.
For example, you deploy a Control project without mapping the facet interface representing the signal quality of an AnalogInput instance to the facet interface representing the analog input module channel of the controller.
If you refine the deployed Control project online, the initial value of the variable assigned to the ComStatus pin of the corresponding DFB is displayed as False because the hardware mapping is not done. Its current value is 0 .
If you proceed with the hardware mapping, build the Control project, and execute the Deploy changes / Undo Online Changes command, the initial value of this variable is changed to True .
However, its current value remains 0 .
NOTE: The same applies when you change an existing hardware mapping after deploying it and deploy it, using the Deploy changes / Undo Online
Changes command.
Exporting and Importing Hardware Mappings
Overview
The functionality lets you manage, in a three-step process, a large number of
by:
• Exporting the data that is shown in the Hardware Mapping Editor to commaseparated data format (CSV).
• Editing the file so that it contains the hardware mappings that you want to create or modify.
• Importing the file into the Hardware Mapping Editor of the same or a different Control executable.
Before proceeding with the import, the software validates the data and informs you of invalid entries, which will not be imported.
Exporting Hardware Mapping Data
Overview
In a first step, the export functionality lets you create export files that contain the data of the Hardware Mapping Editor for a given Control executable.
Good Practices
• Before modifying hardware mappings, back up all the existing hardware mappings by exporting them. If needed, it lets you restore the original configuration by importing the file.
• Apply a filter before exporting so that the export file contains only the topological interfaces whose hardware mapping you want to create or modify.
EIO0000001114.15
449
Export File Compatibility
Hardware mapping export files are forward compatible unless mentioned otherwise.
Export File Description
When you export hardware mapping data, two export files are created. Each one contains data in a
format (CSV).
By default, export files are saved at the path %ProgramData%\Schneider Electric
\Process Expert x\Db, where x represents the software version. When this location does not exist (for example, if only clients are installed on the computer), files are saved at either location:
• At the path where you have last exported or imported any file of EcoStruxure
Process Expert.
• If the above does not apply or is not reachable, in the Windows ® Documents folder.
Default file name
<Executable identifier>_HWMapping where
_HWMapping is appended to the file name that you enter once the file is created.
<Executable identifier>_Pending where
_Pending is appended to the file name that you enter once the file is created.
Description
The file contains the same data as shown in the
topological devices pane, page 444
of the Hardware Mapping Editor at the time of export.
It is a snapshot of:
• The mapping interfaces of the topological entity that is mapped to the Control executable (columns A to D (1) ).
• The mapping interfaces of application objects that are already mapped (columns
E to I (1) ).
If you have applied a
before exporting, only the filtered data is exported.
The first row contains the column headers of the editor.
You need to
of this file to create, modify, or delete hardware mappings.
This supporting file contains the same data as shown in the
of the Hardware Mapping Editor at the time of export.
It is a snapshot of the mapping interfaces of application objects that are available for mapping.
If you have applied a
before exporting, only the filtered data is exported.
The first row contains the column headers of the pane in the editor.
You can use this file to perform cut-and-paste operations to move to the <Executable identifier>_HWMapping.csv file the data that corresponds to hardware mappings that you want to create.
(1) When you open the file by using Microsoft ® Excel ®
Example of Export Files
The following figure shows an example of the Hardware Mapping Editor where:
• In the topological devices pane, four interfaces of digital input project facets are mapped to the corresponding hardware channel interfaces.
• In the project facet pane, four interfaces of analog output project facets are shown as available for hardware mapping.
450 EIO0000001114.15
The following figure shows the content of the exported hardware mapping data file
( *_HWMapping.csv
) that corresponds to the previous example.
And the following figure shows the content of the supporting file ( *_Pending.csv
).
Exporting Hardware Mapping Data
To export the data shown in the Hardware Mapping Editor , proceed as follows.
Step Action
1 In the Hardware Mapping Editor
, select the data that you want to export by using the
2 Click the
Result : The Save As dialog box opens.
3 Enter a file name, select a location, and click Save .
Result : The two export files are created.
NOTE: The export files do not contain the Control project and the system identifiers. If required, include this information in the file name.
Editing the Hardware Mapping Export File
Overview
In this second step, the objective is to edit the exported hardware mapping data file ( *_HWMapping.csv
) so that it contains the hardware mappings that you want to create or modify for a Control executable.
You can use the supporting file ( *_Pending.csv
) which contains the project facet interfaces that are available for mapping.
Schneider Electric recommends using a spreadsheet editor to facilitate the editing of data contained in the export files.
EIO0000001114.15
451
452
NOTE: Although you can delete hardware mappings by using the import functionality, you can delete them directly in the Hardware Mapping Editor by using the Unmap
.
Good Practices
• Before modifying hardware mappings, back up all the existing hardware mappings by exporting them. If needed, it lets you restore the original configuration by importing the file.
• Edit only an up-to-date export file to avoid data conflicts.
• Verify that the
list separator format, page 175
is set to comma on the computer if you are using a spreadsheet editor.
• When you use data from the supporting file to create hardware mappings, cut the data rather than copying it to help avoid mapping the same project facet interface several times.
The other way around, add to the supporting file project facet interfaces that you are unmapping.
Compatibility With Hardware Mapping Files of Earlier Versions
You can use hardware mapping data files (topologyexport.csv and supporting file projectexport.csv) that have been exported by using the system server console of earlier versions of the software if you edit the column headers to match the current format.
The table describes which column headers of the topologyexport.csv file need to be updated and their new value (not case-sensitive).
E
F
C
D
Column (1) Header
A
B
Instance
Template
HW Mapping IF
HW Mapping Type
Instance
Project Facet
G
H
Facet Type
HW Interface
I HW Mapping Type
(1) When you open the file by using Microsoft ® Excel ®
Change to
HWInstance
HWTemplate
HWMappingInterface
HWInterfaceType
AppInstance
AppFacet
AppTemplate
AppMappingInterface
AppInterfaceType
Editing the Hardware Mapping Data File
Edit only rows that correspond to topological interfaces whose hardware mapping you want to create, modify, or delete. Refer also to the
.
Entries that exist in the Hardware Mapping Editor but not in the hardware mapping data file (for example, because a filter was applied before exporting or because they have been deleted from the file) are not modified.
The tables describe the result of various editing actions in the
hardware mapping data file, page 450
( *_HWMapping.csv
) once you import the file.
Editing to create, modify, and delete hardware mappings :
EIO0000001114.15
Edited data
Rows of columns
E to I (1)
Action
New, compatible (2) project facet interface data is added by cutting and pasting it from the *_Pending.csv
file.
Result after import
The corresponding hardware mapping is created.
The hardware mapping is valid if the values of the two *InterfaceType columns match (same interface type and compatible roles).
The corresponding hardware mapping is modified.
Existing project facet interface data is modified appropriately.
For example:
• By mapping another project facet interface to the topological interface (the data is cut and pasted from the
*_Pending.csv
file).
• By swapping two mapped project facet interfaces.
Existing project facet interface data is deleted.
(1) When you open the file by using Microsoft ® Excel ®
The corresponding hardware mapping is deleted.
Other editing :
Edited data
Rows of columns
A to D (1)
Action
Existing topology interface data is deleted.
Result after import
If columns E to I (1) for the same row:
• Are empty, no impact.
This lets you remove from the file rows that you do not need to work with.
• Contain data, an invalid entry is reported.
You cannot import the file.
The first row
Other rows
Any columns
The first row is deleted.
A header of columns A to E (1) is deleted or modified.
A row is not edited.
An entire row is deleted.
A row containing a string is added.
Enter the string in column A (1) and start with a semi-colon (for example, ;My comment).
An empty row is added.
The order of complete rows is changed.
The topology or project facet interface data (or both) of a row is duplicated.
A column is added in first position (A (1) ) or between columns A to E (1) .
One or more columns are added after the last column (E (1) ).
No impact given the same row is still present in the
Hardware Mapping Editor .
No impact.
NOTE: This lets you remove from the file rows that you do not need to work with.
No impact.
NOTE: This lets you add comments to the file.
No impact.
You cannot import the original hardware mapping nor its copy.
You cannot import the file.
No impact.
NOTE: This lets you add comments at the end of a row.
No impact.
The order of columns A to E (1) is modified.
(1) When you open the file by using Microsoft ® Excel ®
EIO0000001114.15
453
454
Example of Editing to Create Hardware Mappings
The following example shows how to create hardware mappings with two channels of an analog output module by pasting the corresponding project facet interface data of the supporting file (shown outlined) to the hardware mapping data file.
The following figure shows the result in the topological devices pane of the
Hardware Mapping Editor . Also, the corresponding analog output project facet interfaces have been removed from the project facet pane of the editor (not shown).
Example of Editing to Delete Hardware Mappings
Continuing with the previous example, the figure shows how to delete hardware mappings with two channels of a digital input module by deleting the corresponding project facet interface data (shown outlined) from the hardware mapping data file.
NOTE: It is recommended to cut the project facet interface data and paste it in the supporting file to keep track of project facet interfaces that are available for mapping.
The following figure shows the result in the topological devices pane of the
Hardware Mapping Editor . Also, the corresponding project facet interfaces have been added to the project facet pane of the editor (not shown).
EIO0000001114.15
Example of Editing to Modify Hardware Mappings
Continuing with the previous example, the figure shows how to move an existing hardware mapping with the channel of an analog output module ( Ch_02 ) to another channel ( Ch_01 ). This is achieved by moving the corresponding project facet interface data of AnalogOutput_2 to the other topological interface, thus overwriting the original interface data of AnalogOutput_1 .
NOTE: Before overwriting the project facet interface data of AnalogOutput_1 , it is recommended to cut the data and paste it in the supporting file to keep track of project facet interfaces that are available for mapping.
The following figure shows the result in the topological devices pane of the
Hardware Mapping Editor . The interface of AnalogOutput_2 is now mapped to
Ch_01 . The project facet interface of AnalogOutput_1 has been unmapped and added to the project facet pane of the editor (not shown).
Example of Editing to Add Comments to the Export File
The following figure illustrates the various ways to add comments (shown in bold) to the hardware mapping data file ( *_HWMapping.csv
) so that they are not detected as invalid entries. Comments are not imported.
NOTE: The CSV format does not allow saving special formatting.
Importing Hardware Mappings
Overview
In this third step, the data contained in the hardware mapping data file
( *_HWMapping.csv
) is imported into the topological devices pane Hardware
Mapping Editor that is open for the Control executable.
Each row in the hardware mapping data file is compared to the same row in the
Hardware Mapping Editor and if different, triggers an action that corresponds to the
that you have performed. Rows in the editor that are not present in the hardware mapping data file remain unchanged.
You can import a file into the same or a different system, Control, or executable as long as the prerequisites are fulfilled.
EIO0000001114.15
455
456
Prerequisites
To be able to import hardware mapping data, the following conditions must be fulfilled:
• You must have performed the
for the Control executable.
• Hardware mapping data files that were created by using earlier versions of the software must be
.
• Both the mapping interfaces of the
topological entity and of the application objects, page 450
that are in the hardware mapping data file must exist when you open the Hardware Mapping Editor for the Control executable.
Additional interfaces of both types can appear in the editor and they have no effect on the import.
Invalid Hardware Mapping Log File
When you attempt to import a hardware mapping data file and the software detects invalid mappings, it creates a log file with these mappings.
• The file is located in the folder from where you have imported the hardware mapping data file.
• It has the same name as the imported file but with the _log suffix and .txt file extension.
Thereafter, each time you try to import the same hardware mapping data file
(same file name), invalid mappings that the software detects are added to the log file.
Importing Hardware Mapping Data
To import hardware mapping data in the Hardware Mapping Editor , proceed as follows.
Step Action
1 In the Hardware Mapping Editor , click the
Result : The Open dialog box opens.
2
3
Select the file ( *_HWMapping.csv
) that contains the hardware mapping data and click
Open .
Result : The Import Mappings dialog box opens.
Click Yes .
Result : If the hardware mapping data is valid, the corresponding hardware mappings are performed in the Hardware Mapping Editor ; otherwise, if the software detects
invalid hardware mappings, page 452
in the imported file, a dialog box opens, which contains information about the invalid entries. Proceed to step 4.
NOTE: Once the import operation is completed, you can see a summary in the notification pane.
4
5
Click:
• Yes to import only the valid data; invalid entries will be skipped.
• No to cancel the entire import operation.
NOTE: If you proceed, you can see a summary in the notification pane once the operation is completed.
If required, correct the invalid entries in the hardware mapping file or make the necessary adjustments in the Control project and import the file again.
EIO0000001114.15
Supervision Project Mapping Stage
Overview
This section describes how to use the Project Explorer to map the Supervision project of the system.
You must have completed
and the
stages of the Supervision project to proceed with the mapping.
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
Creating Supervision Project Executables
Overview
The Executables node gives you access to the service and communication mapping functionality of the Supervision Participant project.
As such, it allows you to associate:
• The Supervision infrastructure (I/O, alarm, trend, and/or report servers, and/ or runtime clients) that is defined in the Supervision Participant project to station nodes of the topology representing operation servers and operator stations.
• The I/O device to a controller and its communication module and/or to compatible Modbus TCP devices and their Modbus TCP server service by using the OFSOPC and/or OPCUA communication protocol.
You can create several executables for a Supervision Participant project, associating the Supervision infrastructure to various topological entities, and its I/
O device to various controllers and Modbus TCP devices.
An executable is associated to an Execution Domain , which serves as a filter to select applicable services, for example, to define the boundaries for runtime navigation services.
Creating Executables
To create an executable, proceed as follows.
Step
1
Action
In the Supervision Project Browser , right-click the Executables node of the project and select Create Executable .
Result: A Supervision executable is created under the Executables node.
Executable Actions
The table describes the executable context menu commands.
EIO0000001114.15
457
458
Command
Manage
Build All
Description
Opens the Manage window in the work area of the Project Explorer , which lets you perform the following actions:
•
Service mapping, page 459 : Associates the Supervision servers and
clients to one or more station nodes of the system topology.
• View and edit the
of the executable.
•
Communication mapping, page 460
: Maps the Supervision I/O device to:
◦ A controller and its communication module.
◦ Compatible Modbus TCP devices and their Modbus TCP server service.
Starts an automated process to integrate changes quickly in the built
Supervision Participant project by performing an incremental build. The command applies only for changes that you have made while editing
Supervision pages ( Edit command).
This command becomes available once you have completed the service and communication mapping.
NOTE: If the Supervision Participant project is not built yet, you can use this command in place of Build All indifferently.
Starts an automated process to
the built Supervision
Participant project the first time or to recreate it to
integrate certain changes, page 479
that you have made to the Supervision Participant project.
This command becomes available once you have completed the service and communication mapping.
Starts a generation of the Supervision Participant project followed by a build of the project executable.
If you have not built the executable yet, the build process that is executed is the same as when you select the Build All command.
If the generation process does not complete successfully, no build is performed and information is displayed in the notification panel.
NOTE: After selecting the command, the abort icon is displayed in the
notification panel, page 54 . Click the icon to cancel the task.
Allows you to deploy the built Supervision project to the station nodes that are mapped to the executable.
Delete
Rename
Properties
The command is available only if you have already deployed the built
Supervision project to at least one station node that is mapped to the executable and if the number and type of changes are supported.
Opens the Download Projects tab, which allows you to select Supervision project files individually to save them on the computer, such as:
• The master project (.ctz) with the name ProjectIdentifier_
ExecutableIdentifier , which was created by the last successful build process.
• Included projects (.ctz) that are related to animated graphics assigned to
Supervision pages and those that you have
• OFS/OPC UA configuration files (.xml).
Deletes the executable including the associated configurations.
NOTE: You cannot delete an executable that you have deployed. The software displays a message to inform you that the command cannot be executed.
Lets you to enter a new identifier for the executable.
Opens the Properties tab in which you can view and edit properties of the executable.
Executable Properties
To open the properties of the executable, double-click it.
You can view and/or edit the following items.
EIO0000001114.15
Mapping Services
Property Description
Identifier
Description
The identifier must be unique within a Supervision project.
Optional.
You can enter a description for the Executable with free form text.
Execution
Domain
Optional.
String.
Default value: Blank.
You can use runtime navigation services (see EcoStruxure ™ Process Expert,
Runtime Navigation Services , User Guide ) only if the executable of the Control
Participant project and the executable of the Supervision Participant project have the same execution domain value.
You can assign a logical execution domain to the executable with free form text.
Values that you enter remain in the menu and you can select them from executables of other Control and Supervision Participant projects.
You can modify the Execution Domain parameter at any time during the engineering life cycle.
NOTE: Leaving the Execution Domain parameter empty is considered as a value.
Build State Indicates the
of the executable.
Built On
Default value: Not Built
Date and time when you last built the executable successfully by using a build command.
Assigning an Execution Domain
To assign an execution domain to an executable, proceed as follows.
Step
1
2
Action
Double-click the executable to open its properties.
Select a value from the Execution Domain menu or enter a new value.
NOTE: To remove or change the associated execution domain, select the empty row at the top of the menu.
Overview
The Service Mapping Editor opens within the Manage window when you doubleclick the Supervision
.
The service mapping defines to which station nodes that represent the operation server and operator station computers you
the Supervision project.
Before you proceed with the service mapping, create the necessary station nodes in the topology of the system and configure them with the services as needed:
• A
.
• An OFS
.
You must map all the services of the Supervision Participant project to station nodes in order to complete the
.
NOTE: Install OPC Factory Server or OPC UA Server Expert on the station node that you map to the IOServer service.
EIO0000001114.15
459
Mapping Station Nodes Configured with Several NICs
The service mapping does not let you select a specific NIC for each station node.
The IP address of each NIC is created as a
in the
Supervision Participant project and associated to the I/O server.
For details on the behavior when deploying to a station node that is configured with more than one NIC, refer to the topic describing the
target computer setup, page 520
.
Changing the Service Mapping of Deployed Executables
If you have already deployed a Supervision executable to one or more station nodes of the system, when you change the service mapping of this executable, the software clears the related entry in the Last Deployed On
of the station nodes that you have unmapped. As a result, if you recreate this mapping right away and deploy, it is handled like a first deployment.
NOTE: The service mapping of a station node is unmapped if you delete its
Supervision service. It is unmapped if you delete its OFS
and the station node was mapped to the IOServer service of the Supervision project.
Mapping Services
To map a Supervision server or client to a station node, proceed as follows.
Step
1
2
3
Action
Double-click the executable of the Supervision project that you want to map and select
Manage .
Result: The Service Mapping Editor opens.
Click the Engine menu next to the server or client that you want to map.
Result: The menu displays the identifiers of
compatible station nodes, page 459 .
Select a station node.
Result: The software maps the service to the selected station node.
NOTE: Once you have mapped the I/O server, the Communication Mapping tab is shown at the bottom of the window.
NOTE: To remove a mapping, in the Service Mapping Editor , right-click a service and select Unmap .
Mapping Communication
Overview
To open the Communication Mapping Editor , click the Communication
Mapping tab within the Manage
. The tab appears once you have performed the
with an I/O server.
The communication mapping defines from which topological entity I/O devices acquire data during runtime by using the
The editor lets you map the I/O devices of the Supervision project to:
• A controller of the system and its communication modules. This includes modules that embed an OPC UA server.
• Modbus TCP devices that feature the Modbus TCP server service (for example, Altivar drives, power meters, STB islands, or PRMs).
• Modbus serial devices by using a topological Modbus TCP device acting as gateway.
460 EIO0000001114.15
• A station node acting as an emulated simulator and to which a Control Expert project has been deployed.
For each I/O server that you map, the software creates a protocol-dependent
OFS/OPC UA
configuration file, page 475 . Exceptions apply.
NOTE: Changing the
protocol of a tag container, page 264
whose associated
I/O device is already mapped to a topological entity removes the mapping.
Physical Connection Prerequisites
To be able to proceed with the communication mapping, the following need to be
connected to the same Ethernet network, page 399 :
• The NIC of the station node that is mapped to the I/O server in the
• The communication modules of the controller entity.
• The Modbus TCP device (if present).
Mapping Modbus Devices
Before you can map a Modbus TCP or Modbus serial device to be able to monitor data directly from the Supervision infrastructure that is defined in the Supervision project, you need to perform some additional steps.
For details, refer to the topic describing how to
monitor Modbus device data directly from Supervision, page 639
.
Mapping Modules Embedding an OPC UA Server
When Protocol of the tag container that is associated to the I/O device is set to
OPCUA Embedded , Data Server (Address B) is disabled. You can map only one module per I/O device.
When modules embedding the OPC UA server are mounted in both local racks of a redundant configuration, either module can be selected under Data Server
(Address A) .
To map also the module embedding an OPC UA server located in rack B, create a second I/O device
configured as standby, page 232
and associate it to the same tag container.
Mapping Redundant Communication Ports
For controllers and station nodes, you can map up to two communication ports or
NICs to a same I/O device if the following conditions are satisfied:
• The communication ports/NICs belong to the same topological entity.
• They are connected to the same physical network.
• Direct TCP/IP Addressing Mode of the
that is associated to the I/O device is set to Unallocated/Allocated Data, PAC
Modicon (/U) .
NOTE: When Protocol of the tag container that is associated to the I/O device is set to OPCUA Embedded , communication port redundancy for the same I/O device is not possible.
EIO0000001114.15
461
462
Communication Mapping Tab
The following figure shows an example of the Communication Mapping Editor in which one controller and two Modbus TCP devices are mapped to I/O devices through their communication modules.
Header
IO Device
Topological Entity
Data Server
(Address A)
Data Server
(Address B)
Modbus Unit ID
Description
I/O devices that you have created in the cluster and which is associated to a tag container.
Topological entities that have at least one communication module (data server) connected to the same Ethernet network as the station node to which the I/O server is mapped. These can be controllers, station nodes,
Modbus TCP devices, and generic Modbus TCP device entities acting as gateways for Modbus serial devices.
The selected entity becomes the data source.
NOTE: Restrictions apply when the protocol of the tag container that is associated to the I/O device has the following value:
• OPCUA : Controllers of the Quantum platform are not shown.
• OPCUA Embedded : Only controllers that have a module, which embeds an OPC UA server and that is connected to the
are shown.
Communication modules of the selected topological entity that are connected to the same Ethernet network as the station node to which the I/
O server is mapped.
For Modbus I/O device entities, it is the Modbus TCP server service of the topological entity.
The IP address of the module is set as the primary address in the OFS/OPC
UA configuration file.
NOTE: When the protocol of the tag container that is associated to the
I/O device is set to OPCUA Embedded , only modules that embed an
OPC UA server are shown.
Optional. The menu is available only if the topological address A has been mapped.
Communication modules of the selected topological entity that are connected to the same Ethernet network as the station node to which the I/
O server is mapped excluding the one that has been mapped to address A.
The IP address of the module is set as the secondary address in the OFS/
OPC UA configuration file.
NOTE: The menu is disabled in either case:
• The topological entity is a Modbus TCP device.
• Protocol of the tag container that is associated to the I/O device is set to OPCUA Embedded .
• For Modbus TCP devices, it is the ID parameter of the topological entity. The value corresponds to the default value of the template or to the value that you had configured (when available) before selecting the device and its data server. You can change the value for the device. The change is not propagated to the topological entity.
Changing the value in the topological entity is not propagated to devices that are already mapped.
• For Modbus serial devices, if you have already configured an application template of the device (for example, an instance of
$ATV71MB ), enter the ModbusAddress parameter value of the instance. Otherwise, enter the unique serial slave ID of the device.
Valid range: 0 to 255
Refer to the documentation of the device for information on the parameter configuration.
NOTE:
• The software does not verify the uniqueness of entries.
• The parameter is disabled for station nodes and controllers.
EIO0000001114.15
Mapping Station Nodes
When you map an I/O device to a station node, you can simulate runtime services.
The software displays the station node in the Communication Mapping Editor only if its NIC is connected to an Ethernet network and if you have
Control Expert service, page 379
in the station node.
NOTE:
the Control executable of the corresponding Control
Participant project to the same station node.
Mapping Communication
To map the I/O device to the communication module/card of a topological entity, proceed as follows.
Step
1
2
3
4
5
6
Action
Select the Communication Mapping tab within the Manage window.
Click the Topological Entity menu next to the I/O device you want to map.
Result: The menu displays the identifiers of the compatible entities of the system.
Select an entity.
Click the Data Server (Address A) menu.
Result: The menu displays the identifiers of the available communication modules/ cards of the selected entity.
Select a communication module/card.
If needed, click the Data Server (Address B) menu and select a second communication module/card of the same entity.
NOTE: To remove the entire communication mapping for an I/O device, rightclick a communication module/card in either Data Server column and select
Unmap .
To remove the mapping of one data server only, select Not Assigned from the menu.
EIO0000001114.15
463
Build Stage
What’s in This Chapter
Supervision Participant Project Build Stage ................................................... 475
Overview
This chapter describes how to create the built Control and Supervision Participant projects, which are the executables and project files that you deploy to controllers and/or station nodes of the system.
The following figure shows the position of the Build stage within the system engineering life cycle.
Refer to the
for a description of the purpose of this stage.
Control Project Build Stage
Overview
This section describes how to use the Project Explorer to create the built Control
Participant project for the first time and, in a second step, to integrate changes that you have made to the Control Participant project and to the topology of the system.
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
Building the Logical Control Participant Project
Overview
In this automated process, the software creates a unique built Control Participant project, which merges:
• The logical Control Participant project information, including changes made during refinement.
464 EIO0000001114.15
EIO0000001114.15
• The mapping information, which is associated to the Control executable of the logical project:
◦ Services
◦ Hardware
◦ Communication (if applicable)
• The topological information, which is associated to the mapped services
The software stores the resulting program file (.stu) in the
The build process also:
• Creates the necessary DDDT variables with the number of input and output words that you have configured to allocate memory.
• Creates the I/O scanner lines for the communication channels that exist in the communication mapping given that
sufficient memory is available, page 376 .
• Defines the value of REF_TO data types (see EcoStruxure ™
Control Participant Services, User Guide):
Process Expert,
◦ As REF(%MWx) or REF(%CH<@mod>.<c>) (IODDT) for direct addressing data instances (HAL2.0 variables) that are used in hardware mapping.
◦ As REF(DDDT) for variables that are used in communication mapping.
◦ As REF(PES_CONST_TRUE) for variables that need to be initialized as
TRUE .
• Introduces the REF_TO ANY_BOOL data type because of the legacy feature to convert BOOL to EBOOL, and the other way around becoming obsolete. If you have updated existing Schneider Electric HAL templates in systems with
HAL2.0 templates (see EcoStruxure ™ Process Expert, Control Participant
Services, User Guide), both data types are converted to REF_TO ANY_
BOOL.
NOTE: The conversion does not apply to templates created by users except if they reference Schneider Electric HAL templates (for example,
$DISignal_UL ).
To perform a subsequent build or if the Build command has become unavailable, refer to the topic
Changing the Built Control Participant project, page 470
.
NOTE: You may need to update the firmware version of topological entities to support the ANY_BOOL data type during build. For information on compatible firmware versions, refer to the platform release notes.
Device Type Manager and Device DDT Variables for Modbus
TCP Devices
During build, the software adds a generic Modbus Device device type manager
(DTM) for each Schneider Electric
Ethernet Modbus TCP device, page 391
that you have configured in the topology of the system and which communicates with a controller of the M580 platform or by using a NOC communication module. You do not need to add it.
Modbus TCP devices can be:
• An STB Island
• A PRM
• A Modbus TCP I/O device
The DTM name is composed of four elements. It has the following syntax.
<I/O device name><Counter>_<Client communication module><Position>
Where:
• <I/O device name> is the identifier of the
topological entity, page 364 . The
identifier is truncated not to exceed 10 characters.
465
466
• <Counter> is an incremental 1 or 2-digit number generated by the software so that truncated device names are unique.
• <Client communication module> is the commercial reference of the communication module of the client controller that is used to communicate with the device. The reference is truncated to not exceed 12 characters.
• <Position> is the position of the communication module on the rack.
For example, EATV71HW_11_BMENOC030122 ( 1 in 11th position from the left is the counter and 2 in last position is the position of the module.
EATV71HW_1 is the
I/O device name. BMENOC03012 is the commercial reference of the communication module).
The Control Participant creates the corresponding DDDT variable.
Device Type Manager and Device DDT Variables for Peer to
Peer Communication
During build, the software adds a generic Modbus Device device type manager
(DTM) in the consumer (client) Control project for each communication module of a server counterpart with which a peer to peer communication channel exists. The
DTM is added if the controller acting as client is of the M580 platform or if communication client-side is implemented by using a NOC communication module.
The DTM name is composed of four elements. It has the following syntax.
<Server entity><Counter>_<Server communication module><Position>
Where:
• <Server entity> is the
of the topological entity acting as
. The identifier is truncated to not exceed 10 characters.
• <Counter> is an incremental 1 or 2-digit number generated by the software so that truncated server entity names are unique.
• <Server communication module> is the commercial reference of the communication module of the controller acting as server. The reference is truncated to not exceed 12 characters.
• <Position> is the position of the communication module on the rack.
For example, Controller1_140NOE771012 ( 1 in 11th position from the left is the counter and 2 in last position is the position of the module.
Controller_1 is the server entity name, which has been truncated. 140NOE77101 is the commercial reference of the communication module server side).
The Control Participant creates the corresponding DDDT variable.
Device DDT Variables Created in the Logical Control Project
If you have
created a device DDT variable, page 343
in the logical Control project and this variable does not exist in the controller that is mapped to the executable
(for example, because you have removed the module to which it is associated), the resulting built Control project contains it in unmapped (unlocked) state.
If a device DDT variable with the same name exists in both the logical Control project and the controller that is mapped to the executable but with a different data type or type version, the resulting built Control project contains the variable of either type based on the following rule.
DDDT variable in the controller
Mapped
Unmapped
DDDT variable in the logical Control project
Unmapped
Result in the built Control project
Unmapped
Variable of the same type as in the controller mapped to the executable.
Variable of the same type as in the logical
Control project.
EIO0000001114.15
EIO0000001114.15
Validity Indicators
If a
is displayed, you may not be able to build the project successfully. Some
In such case,
Refine the Control Participant project, page 336
to fix the issue.The
Control Participant features tools that help you identify validity issues.
When you save the Control Participant project after
it and
project analysis is enabled, page 205 , the project is analyzed. The status of the
Control project is indicated by a validity icon.
Building the Control Project for the First Time
Use the Build or Build All command indifferently to create the built Control
Participant project for the first time.
NOTE: If you have not built the Control Participant project yet, you can also use the Generate and Build command. For information on the generation process, refer to the topic describing the
generation of Participant projects, page 297
.
Control Participant Project Settings
When you build a logical Control Participant project by using the Build All command, the software may override some project settings (see EcoStruxure ™
Process Expert, Control Participant Services, User Guide) that you have set during configuration.
To view the Project Settings of the built Control Participant project, use the
Built Project command, page 469 .
NOTE: This applies also when you are using the Generate and Build command to build a Participant project executable for the first time.
Allocation of Memory in I/O Scanner Lines
The build process allocates the memory in the following order: First write, then read.
Read and write addresses are created contiguously for clients of the M580, M340, and Quantum platforms.
The read/write memory allocation varies depending on the platform.
Platform
Quantum
Memory allocation process
M340
M580
The write address should be the end of the read address of the previous channel.
However, for example, if 2 channels exist for entity A, and 1 channel exists for entity B, then the memory allocation is the following:
1. Write memory allocation for any existing channels of entity A.
2. Read memory allocation for any existing channels of entity A.
3. Write memory allocation for the channel of entity B.
4. Read memory allocation for the channel of entity B.
NOTE: The first 8 words are allocated for the device control block.
1. Allocates the memory for writing for any existing channels.
2. Allocates the memory for reading for any existing channels.
NOTE: The software detects an error in the configuration during build if you have not configured sufficient memory for a client controller based on the
Quantum platform with NOC communication module (see EcoStruxure ™
Process Expert, Control Participant Services, User Guide).
467
468
Allocation of Peer to Peer Communication Variables
The build process allocates addresses or values to the network variables that you have
to communication channels.
The start address of a variable in the channel needs to be even and contiguous with the channel. Therefore, if the start address of the communication channel created in the client is:
• Odd:
◦ No variable is allocated to the first word of the client communication channel.
◦ Addressing of variables in this channel starts from the second word.
◦ The offset of the server read/write memory counterpart is the first word of the server communication channel.
• Even:
◦ Addressing of variables in this channel starts from the first word.
◦ Read and write size of the memory is equal to the value of the
ServerMemoryLength parameter - 1.
◦ The offset of the server read/write memory counterpart is the second word of the server communication channel.
NOTE: If by using the Refine command, you delete or change the name, type
(ID or version), or size of any variable or network variable that is mapped to a communication channel, the build process cannot complete successfully. The software displays diagnostic information in a dialog box. In such case, open the Variable Mapping Editor to
the inconsistent variable or undo the changes to the variable. Start the build process over.
The figure shows examples of entries created during build in the
(client based on the M580 platform) for the Value attribute of two sample peer to peer communication variables that are used to read data from the server ( DISignal_UL_1V ) and write data to the server ( Valve_1_VALVE_OPV ).
The figure shows examples of entries created during build in the owner project
(server based on the M580 platform) for the Value attribute of the two counterpart sample peer to peer communication variables.
Aborting Build Tasks
After selecting a build command or confirming it, the abort icon is displayed in the
. Click the icon to cancel the task. No build is performed.
Only the user who has initiated the command is allowed to abort it.
NOTE: If you are building only a small Control Participant project, the task may complete before you are able to click the icon.
Using the Build Commands
To build the Control Participant project, modify the built Participant project through an incremental build, or build it again, proceed as follows.
EIO0000001114.15
EIO0000001114.15
Step
1
2
3
4
Action
Right-click the executable and select
Build , Build All , or Generate and Build depending on the
.
In the confirmation message, click No .
NOTE: Click Yes to proceed with the build anyway; the process may not complete successfully.
Refine the Control Participant project, page 339
to fix the issue.
Start the build process over.
–
–
Result
If no
is displayed, the software executes the following actions; otherwise it displays a confirmation dialog box. In such case, proceed to step 2.
• Proceeds with the creation or update of the built Control Participant project.
• Stores the program file (.stu) in the content repository.
• Displays information in the notification panel.
• Displays a dialog box containing a summary of the build process.
The confirmation dialog box closes without building the Control Participant project.
NOTE: If the build process does not complete successfully, the software displays a notification to inform you and provides indications about the cause.
In such case, make the necessary corrections and build the project again.
Build Status
The table describes the build status of an
.
Status
Not Built
Built
Out Of Date
Description
No built Participant project exists.
Default status when you create an executable.
The built Participant project is up to date.
The built Participant project is out of date and needs to be
.
NOTE: You may need to build the Control Participant project again if you have made certain
to the system even though the software displays the Build State as Built .
Viewing the Built Participant Project
Once you have built the Control Participant project, you can open the project in the
Control Participant to view it.
You may also be able to open the built Control Participant project if the software reports detected errors during the build process to help you with the troubleshooting.
NOTE: Do not make changes to the built Control Participant project from within the Control Participant as the software discards any changes upon closing the reduced Participant window.
To make changes to the system, you can use the following methods:
• Open the system using the corresponding explorer.
•
the logical Control project.
To open the built Control Participant project in the Control Participant, proceed as follows.
469
Step
1
2
Action
Right-click the Control executable and select Open Built Project .
Result: The Control Participant opens
and maximized. You can view the contents of the built executable.
NOTE: For more information, refer to Viewing the Built Control Participant project
(see EcoStruxure ™ Process Expert, Control Participant Services, User Guide).
Close the Control Participant window.
NOTE: To save a copy of the built Control Participant project, use the Save as command of the Content Repository
.
Changing the Built Control Participant Project
Overview
This automated process allows you to change the built Control Participant project by integrating changes that you have made to the Control Participant project, or to the topology of the system.
Depending on the modifications you made, the status of a built Control Participant project changes and you may need to use a specific command to integrate changes.
Changes Modifying the Build Status
The table describes how changes affect the executable of a Control Participant project whose status is Built .
Change
Changes to the topology of the system (for example, properties, controller rack configuration, IP addresses, physical connections, replacing templates of I/O device entities, deleting STB island entities, Ethernet networks entities, safety password, and so on).
Changing the logical Control Participant project and generating it.
Deleting a section in the Project Explorer .
Selecting the Refine command after adding, renaming, or changing the order of sections in the Project Explorer .
Refining the Control Participant project.
Selecting Built Participant Project for an executable when importing a Control
Participant project in the Project Explorer .
It applies in the following cases:
• An executable with the same identifier already exists in the target project and its status is Built .
• You are importing an executable that does not exist yet in the target project and its status was Built at the time of export.
the logical Control Participant project.
Changing the service, communication, or hardware mapping of the Control executable.
For communication mapping, in case a peer to peer communication channel exists, changes include creating, modifying, or deleting a
variable mapping, page 435 (1)
.
Removing the service mapping.
Deleting a controller or station node that is selected in the service mapping, or deleting the ControlExpert
of such a station node.
Resulting build state
Out Of
Date
Not Built
(1) When a communication channel and variable mappings for peer to peer communication exist between two built Control project executables, making a change affecting the communication channel or variable mapping in one executable, which sets its build status to Out Of Date also changes the build
470 EIO0000001114.15
EIO0000001114.15
status of the other executable to Out Of Date . Such change can be, for example, deleting the Control project or its executable, deleting a mapped variable, deleting a section containing a mapped variable, disconnecting a mapped controller entity, and so on.
NOTE: After making a change, which modifies the build status, build the logical Control Participant project again using the
.
Building after Creating, Updating, or Deleting Device DDT
Variables in the Logical Control Project
If you have
created a device DDT variable, page 343
in the logical Control project and this variable does not exist in the built Control project, the updated built
Control project contains it in unmapped (unlocked) state.
The following table describes the result when building changes if a device DDT variable with the same name exists in both the logical and the built Control project but with a different data type or type version.
DDDT variable in the built Control project
Mapped
Unmapped
DDDT variable in the logical Control project
Unmapped
Unmapped
Result in the updated built Control project
Variable of the same type as it was in the built Control project.
Variable of the same type as in the logical
Control project if the type that is updated is not used by a mapped device DDT variable.
The following table describes the result when building changes if a device DDT variable that exists in the built Control project has been deleted from the logical
Control project.
DDDT variable in the built Control project
Mapped
Unmapped
DDDT variable in the logical Control project
Variable is deleted and references to it in code are removed.
Result in the updated built Control project
• The device DDT variable is not removed.
• Code is updated.
• The device DDT variable is removed.
• Code is updated.
Using the Appropriate Command to Integrate Changes
The table indicates which command to use to update the built Control Participant project depending on the change that you have made.
Change
• Adding, deleting, or changing:
◦ Any section (including the order of sections)
◦ Variables (1) (including
device DDT variables, page 343 )
◦ The hardware mapping
•
CCOTF-compatible changes, page 369
in the configuration of a controller (2)
Changing the topology of the system (3) .
Changing the communication or network variable mapping
(3) .
After an import into a Control Participant project (3) .
After regenerating a Control Participant project (3) .
Adding, deleting, or changing:
• Animation tables (4)
Command Action
Build (5) Performs an incremental build.
Build All Performs a complete build.
471
Change
• Operator screens (4)
• DDTs or DFBs (4)
Changing the order of FBD or non-FBD sections in the
Control Participant project by using the Refine command (4) .
Moving FBD or non-FBD sections from one task folder to the other (for example, from MAST to FAST) while refining the Control Participant project ( Refine command).
Changes that
set the build status to Not Built , page 470
.
Command Action
Build or
Build All
Either command performs a complete build.
(1) To integrate changes to attributes of
variables used in hardware mapping, page 472 , use the
Build All command.
(2) Except changes to the S908 architecture, which require using the Build All command to integrate these changes even if the Build command is available.
(3) Such changes disable the Build command. Except for CCOTF-compatible changes.
(4) Using the Build command after such change does not update the built Control
Participant project.
(5) You can also use the Generate and Build
NOTE: When you modify an existing peer to peer communication channel, rebuild the
owner and the consumer, page 350
Control Participant projects.
Performance Considerations
When you have made changes to a built Control Participant project and the appropriate command to update it is Build , in certain cases you may be able to reduce the time required to update the built Participant project by using the Build
All command instead.
This can be the case, for example when you make changes to many sections of a built Control Participant project at once.
Managing Hardware Abstraction Layer (HAL) Variables and DFBs
Overview
The Global Templates library contains HAL application templates, which generate elementary variables representing the value and/or quality of hard-wired signals.
HAL is a mechanism that emulates access to hardware resources to maintain an application device-independent. By using such templates, you can use the elementary variables that they generate although the hardware channels are not yet part of the logical Control Participant project. Data related to the topology is associated to the logical Control project during build.
The following types of templates exist:
• HAL templates generating elementary digital or analog Control Participant variables (for example, signal conditioning templates).
• Special card templates containing DDTs, DFBs, and/or IODDTs, allowing to use the data exchanged with the special in-rack modules (for example,
Modicon M340 high speed counter module device templates).
Facets referenced by these templates are used during the hardware mapping.
For details on these templates, refer to the
of the Schneider Electric libraries for EcoStruxure Process Expert.
472 EIO0000001114.15
Marking HAL Variables and DFBs
When you build the logical Control Participant project, the software marks the following code that is used in the hardware mapping with the Custom attribute
HAL :
• Elementary variables coming from mapped facets of hardware abstraction layer templates or special card templates.
• DFB instances and IODDTs coming from mapped facets of special card templates and that are added to a section during build.
Limitations can apply when you:
• Refine sections containing marked DFB instances, using the Refine Online command (see EcoStruxure ™ Process Expert, Control Participant Services,
User Guide).
•
Update the logical Control Participant project, page 567
with changes made to HAL variables or sections containing marked DFB instances.
NOTE: DFB instances and IODDTs are marked with the attribute HALFB to distinguish them from EDTs.
Properties of HAL Variables
In this example, facets of instance DigitalInput_1 have been assigned to an FBD section and generated. In the hardware mapping, the DigitalInput_1_DINPUT_
DIS facet is mapped to a channel of the digital input module of the controller. The controller entity is based on the M580 CPU. The following figure shows the built
Control Participant project where the software has marked the DigitalInput_1_
DINPUT_DISV variable that is used in the hardware mapping.
EIO0000001114.15
Properties of HAL IODDT Variables and DFBs
In this example, the facet of instance TSignCptBmx_1 (modeling a high speed counter module) has been assigned to an FBD section and generated. In the hardware mapping, the TSignCptBmx_1 facet is mapped to a channel of the high speed counter module of the controller. The following figure shows the built
Control Participant project where the software has added the TSignCptBmx_1
DFB encapsulated in this facet to the section and marked it.
NOTE: The data type and addressing method for variables shown in this example may vary depending on the version of the template generating them.
473
The following figure shows the same built Control Participant project where the software has created the corresponding IODDT TSignCptBmx_1_CHANNEL and marked it.
474
NOTE: A TSignCptBmx_2_DATA facet of another high speed counter instance, for the second channel of the counter module, has been assigned to the FBD section and generated. However, the hardware mapping for the second channel has not been done, thus the second DFB instance and the corresponding IODDT have not been added to the section.
Viewing Sections Containing HAL DFBs and Variables
Once you have built the Control Participant project, use the Open Built Project command to view the HAL attribute, allowing you to identify variables and DFB instances that the software has marked.
NOTE: After deployment, you can also view this attribute by using the Refine
Online command.
NOTE:
This attribute is not visible when you refine the logical Control Participant project by using the Refine command.
Changing HAL Variables
To integrate into the built Control Participant project changes that you make to variables that the software marks as HAL , using the Refine command, refer to
Using the Right Command to Integrate Changes, page 471
.
EIO0000001114.15
Supervision Participant Project Build Stage
Overview
This section describes how to use the Project Explorer to create the built
Supervision Participant project for the first time and, in a second step, to integrate changes that you have made to the Supervision Participant project.
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
Building the Supervision Participant Project
Overview
In this automated process, by using the compilation mechanism of the Supervision
Participant, the software creates a unique built Supervision Participant project, which merges:
• The logical Supervision Participant project information.
• The mapping information, which is associated to the executable of the logical
Participant project:
◦ Services
◦ Communication
• The topology information, which is associated to the mapped services.
The software stores the resulting Supervision project file (.ctz) in the
.
This is the file that you can deploy to computers running Supervision software.
I/O Device Addresses
When the protocol for a tag container is OPCUA or OPCUA Embedded , the build process replaces the
temporary IP address and port value, page 233
in the address of the I/O device that is associated to the container in order to create the actual I/O device address in the Supervision Participant project.
Protocol for tag container
OPCUA
I/O device address format
OPCUA
Embedded opc.tcp://<IP address>:<TCP listening port>/OPCUAServerExpert
Where:
• <IP address> is the IP address of the
that is
to the IOServer service.
• <TCP listening port> is the value that is configured for TCP Port for this station node.
opc.tcp://<IP address>:<TCP listening port>
Where:
• <IP address> is the IPv4 address (see EcoStruxure ™ Process Expert,
Control Participant Services, User Guide) of the communication module embedding the OPCUA server and that is selected in the
communication mapping, page 460
for the I/O device associated to the tag container.
• <TCP listening port> is the value that is configured for this module in the
Control Participant.
NOTE: For other protocols, refer to the Address
of the I/O device.
EIO0000001114.15
475
476
OFSOPC and OPC UA Configuration Files
During the build process, the software generates the necessary OPC Factory
Server and OPC UA Server Expert configuration files and stores them in the contents repository.
One configuration file is created for each station node that is
to an IOServer service. The name of the configuration file contains a suffix that identifies the protocol that is used.
In case more than one protocol is used in the Supervision project, at least one configuration file per protocol is generated.
Protocol used
OFSOPC
OPCUA
Configuration file name
<Topological entity>_DeviceConfig_
OFSDA.xml
For example,
OPCUA.xml
For example,
OperationServer_
DeviceConfig_OFSDA.xml
<Topological entity>_DeviceConfig_
OperationServer_
DeviceConfig_OPCUA.xml
Configuration file aliases
One device alias exists for each I/O device of the same I/O server.
The alias name is Alias_<I/O device> where <I/O device> is the identifier of the
I/O device that is
to the data source.
For example, Alias_IODevice_1 .
One device alias exists for each tag container.
The alias name is the
tag container identifier, page 264 .
For example, TagContainer_1 .
NOTE: The User authentication and X509 user token properties are enabled by default.
For details, refer to User
Authentication and Authorization in the help of OPC UA Server Expert.
OPCUA with OPC
UA server
embedded in module of controller, page 264
No configuration file is generated.
Not required.
The OPC UA server is embedded in a module of the controller that is the data source.
The variable tag address has the format ns=2;s=0:<variable name> where ns indicates the namespace and 2 corresponds to the OPC UA server as defined by Schneider Electric.
For example, ns=2;s=0:InputVar1
Where <Topological entity> is the identifier of the station node to which the IOServer service is mapped in the
If you rename the station node, the name of the configuration file is updated without the need to build the Supervision Participant project.
NOTE: For information on how to generate symbol table files (.xvm), refer to the topic describing the
Control project deployment process, page 484
.
Network Addresses of Supervision Project Components
When you build a Supervision Participant project, and you have not done the
of a server and/or client of the project, the software does not generate an IP address for this component. Because of this, the build process of the Supervision Participant project cannot complete successfully.
Proceed with the service mapping of any Supervision Participant project component that you have created before building the project.
For example, if you have not mapped the alarm server of the project, the network address of the associated topological entity is not generated into the Supervision
Participant project.
EIO0000001114.15
EIO0000001114.15
Building When Instance Identifiers Start with a Digit
When the logical Supervision Participant project that you want to build contains facets referenced by instances whose identifier starts with a digit, you need to set the tagstartdigit parameter of the Supervision Participant configuration file (.ini) to
1 for the build process to complete successfully.
Building the Supervision Project for the First Time
Use the Build or Build All command indifferently to create the built Supervision
Participant project for the first time.
NOTE: If you have not built the Supervision Participant project yet, you can also use the Generate and Build command. For information on the generation process, refer to the topic describing the
generation of Participant projects, page 297 .
Aborting Build Tasks
After selecting a build command, the abort icon is displayed in the
notification panel, page 54 . Click the icon to cancel the task. No build is performed.
Only the user who has initiated the command is allowed to abort it.
NOTE: If you are building only a small Supervision Participant project, the task may complete before you are able to click the icon.
Using the Build Commands
To create the Supervision Participant project, modify it, or to create it again, proceed as follows.
Step Action
1 Right-click the executable and select Build ,
Build All , or Generate and Build depending on the
Result
The software executes the following actions:
• Creates the creation or update of the
Supervision Participant project.
• Stores the project files in the contents repository.
• Displays information in the notification panel.
• Displays a dialog box containing a summary of the build process.
NOTE: Building the Supervision project may take time.
NOTE: If the build process does not complete successfully, the software displays a notification to inform you, and provides indications about the cause.
In such case, make the necessary corrections and build the project again.
Build Status
The table describes the build status of an
.
Status
Not Built
Built
Out Of Date
Description
No built Participant project exists.
Default status when you create an Executable .
The built Participant project is up to date.
The built Participant project is out of date and needs to be built again.
477
478
NOTE: You may need to build the Supervision Participant project again if you have made certain
to the system even though the software displays the Build State as up to date.
Changes Modifying the Build Status
The table describes how changes affect the status of the executable of a
Supervision Participant project that is already built.
Change
Renaming an I/O device or the Supervision project.
Generating the project after making changes.
Creating a page.
Changing the project through refinement.
Any import operation in the Project Explorer .
Changing service or communication mapping of the Supervision executable.
Changes to the topology of the system, for example:
• Changing the IP address of the NIC of a station node or of a module that is selected in the service or communication mapping.
• Deleting the ControlExpert or OFS service, or the NIC instance of a station node that is selected in the communication mapping.
• Deleting the Supervision service of a station node that is selected in the service mapping.
• Deleting a controller that is selected in the communication mapping.
• Changing the TCP Port of a station node that is selected in the service mapping for the I/O server when the protocol that is used for at least one tag container is OPCUA.
Removing all service mappings of the Supervision executable.
Deleting a station node that is selected in the service mapping.
Resulting build state
Out Of Date
Not Built
Downloading Supervision Project Files
After the build process completes successfully, the following files are available for download in the Download Projects
:
• The master project (.ctz) with the name ProjectIdentifier_ExecutableIdentifier
(for example, Supervision_1_Executable_1 ).
The project also contains any
that are attached to the
Supervision Participant project.
• The included projects (.ctz) that are related to animated graphics, which have been added to Supervision
• Any other included project that you have
to the
Supervision Participant project.
• The OFSOPC/OPC UA configuration files (.xml) if you have configured the
driver as OFSOPC or OPCUA .
NOTE: You can download included projects as soon as the software has added them to the Supervision Participant project.
To download a project file, proceed as follows.
EIO0000001114.15
Step
1
2
3
Action
Right-click the executable that you have built and select Download Projects .
Result: The Download Projects window opens and shows the project files associated to the built Supervision Participant project.
Select one file and click Download .
Result: The Save As dialog box opens.
Browse to the location where you want to save the file and click Save .
Changing the Built Supervision Participant Project
Overview
This automated process allows you to change the built Supervision Participant project by integrating changes that you have made to the Supervision Participant project.
For performance considerations, when possible, use the Build command. It requires less time to complete than Build All . However, you can use the Build All command in any case.
NOTE: You can also use the Generate and Build
.
Using the Right Command to Integrate Changes
The table indicates which command to use to update the built Supervision
Participant project depending on the type of change that you have made.
Change
Changes involving Supervision pages:
• Creating or deleting a page.
• Editing a page ( Edit command):
◦ Adding or deleting one or more genies or graphical elements.
◦ Editing page properties.
• Generating a page that contains a genie facet with the status
Out Of Date or Deleted .
Changes involving Supervision data facets (2) :
• Assigning or unassigning a facet from a tag container.
• Moving an existing facet to another tag container.
• Generating a tag container that contains a facet with the status
Out Of Date or Deleted .
Modifying a parameter of the Message
of a
Supervision element of an instance and generating the corresponding Supervision project (for example, modifying the description of an interlock condition of the InterlockTags element under the Supervision node of an instance).
Command Action
Build (1)(2) Performs an incremental compilation.
No compilation is performed.
EIO0000001114.15
479
Change
Other changes, for example, to:
• Clusters.
• The trend, alarm, report, and/or I/O server.
• Service and communication mappings.
• Advanced project settings.
• Generating or refining the Supervision Participant project
(except when generating only changes that involve a
Supervision data facet as described in this table).
• Topological entities, for example, changing the TCP Port of the
I/O server station node when the OPCUA protocol is used or changing the configuration of a module that embeds an OPC
UA server.
Command Action
Build All (2)
(3)
Performs a complete compilation.
(1) You are limited in the number of changes that you can make per Supervision Participant project to be able to use the Build command:
• A maximum of 5 changes involving Supervision pages.
• A maximum of 30 changes involving data facets.
When you exceed either limit, you must use the Build All command.
(2) You can also use the Generate and Build
(3) When you make this type of change, the Build command is not available.
480 EIO0000001114.15
Deployment Stage
What’s in This Chapter
Supervision Project Deployment Stage ......................................................... 520
Overview
This chapter describes how to deploy the built Control and Supervision Participant projects to entities that exist in the topology of the system.
The following figure shows the position of the Deployment stage within the system engineering life cycle.
Refer to
for a description of the purpose of this stage.
Control Project Deployment Stage
Overview
This section describes how to use the Topology Explorer to deploy entire built
Control Participant projects or parts of them to physical controllers or to PCs emulating simulators, which are modeled by engines in the topology of the system.
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
Control Participant Project Deployment Process
Overview
The software allows you to deploy a
built Control Participant project, page 464
to engines by using the following commands:
• Deploy Built Project
• Re-Deploy Last Project
EIO0000001114.15
481
• Deploy Changes / Undo Online Changes
Deployment Flowchart
The following figure illustrates the different steps that are part of the deployment process of the built Control Participant project and their associated commands.
482
(1) Or emulated simulator (station node).
Prerequisites
The following table describes the actions that are prerequisite for using a command.
Command
Deploy Built Project
Actions
Build the Control Participant project and configure the corresponding topological entity.
Deploy the built Control Participant project.
Re-Deploy Last
Project
Deploy Changes /
Undo Online
Changes
Update the project, page 567 with hardware changes made online (if
applicable).
In addition, the following are prerequisite for specific actions:
For Deploy Changes :
• Deploy the built Control Participant project.
• Change the logical Control Participant project and build it.
For Undo Online Changes :
• Deploy the built Control Participant project.
• Change the deployed Control Participant project, using the Refine
Online command.
NOTE: Certain changes
by using the
Deploy Changes command.
For the other actions that are required, for example, mapping the Control executable to a controller, refer to the system engineering life cycle.
Supported Engines for Deployment
The software allows you to deploy/re-deploy a built Control Participant project, and deploy changes to engines representing:
EIO0000001114.15
EIO0000001114.15
• A controller
• A redundant controller of the M580 or Quantum platform.
• A computer running software that emulates a
(modeled by a station node in the topology of the system).
Engines need to exist in the topology of the system and be mapped to a Control executable of the project.
Identifying Engines
The software uses the IP address of each engine to identify it on the Ethernet network.
WARNING
UNINTENDED EQUIPMENT OPERATION
Before deploying to a controller, verify that:
• You have assigned a valid IP address to the controller.
• The IP address corresponds to the physical address printed on the hardware.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: To obtain a list of IP addresses of nodes that are connected to the same physical network and their corresponding physical address (media access control (MAC) address), use the Address Resolution Protocol (ARP).
The procedure describes how to use the ARP to obtain a list of IP addresses of nodes connected to the same physical network and their corresponding physical address (MAC address).
Step Action
1 Write down the MAC address that is printed on the communication module through which you want to deploy or execute.
2 Connect the computer to the Ethernet network to which this communication module is connected and through which you want to deploy or execute.
3
4
On the computer, execute the cmd.exe
program.
Result: A command prompt opens.
Type arp -a and press Enter .
Result: The local ARP cache table opens.
5
6
7
In the table, locate the MAC address matching the one printed on the communication module.
In the table, verify that for this address, the corresponding IP address matches the IP address that you have assigned to the engine in the Control Participant; otherwise proceed to step 7.
Assign to the communication module the IP address that you have assigned to the corresponding engine in the Control Participant and repeat the procedure, starting from step 2.
Client/Server Connection
In case of an unexpected stop of the system server, the notification panel of engineering clients that were connected to the system server before the communication interruption may contain information about operations that did not complete successfully because of this interruption. It may also indicate corrective actions.
After an interruption of the client/server connection, the states of both the engineering client and the system server may have become inconsistent if a deployment operation was in progress.
483
NOTICE
DATA CORRUPTION
After an interruption of the client/server connection, verify that the last operation executed by the software was completed successfully, and if necessary, repeat the last operation.
Failure to follow these instructions can result in equipment damage.
NOTE: For more information on client and server behavior in case of a communication interruption, refer to the topic describing
client/server connection, page 47
.
Start/Stop Commands
The software can send a start or stop command to the controller or software emulating a simulator.
Unintended situations can occur if the operations that are in progress are not known when acting on a controller.
WARNING
UNKNOWN OPERATIONAL STATE OF EQUIPMENT
Before starting or stopping a controller, always positively confirm that there is no critical operation in progress.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Generating Symbol Table Files
You cannot generate symbol table files (.xvm) by selecting the saveXVM property in the project settings of the Control Participant. You need to edit a dedicated configuration file instead before deploying a Control project.
To generate symbol table files (.xvm) of the Control Participant and retrieve them from the content repository, proceed as follows.
Step
1
2
3
4
Action
Open the ControllerSettings.xml file that is located at the path C:\Program Files
\Schneider Electric\EcoStruxure\Process Expert\System Server on the computer on which the system server is installed.
Set the value for the SaveXVM attribute to 1 and save changes.
Result : When you
to a Control project or
refine it online, page 548 , the symbol table file is added to the content repository.
In the content repository, open the XvmHolder folder located under Systems
<System name> > Project > Upro .
>
.
Deploying to an Emulated Simulator
Overview
You can deploy built Control Participant projects to computers for simulation purposes. In the topology of the software, this computer (engine) is represented by a
on which a ControlExpert service is installed.
By default, the simulator is configured to start with a password-protected Control project (see EcoStruxure ™ Process Expert, Installation and Configuration Guide)
484 EIO0000001114.15
EIO0000001114.15
provided with the software. You can start the simulator with a different passwordprotected project file or
of the project that is loaded by default.
NOTE: If your Windows ® session is not the one that was used to install the software, you need to
configure the simulator manually, page 486
to load a password-protected Control project at startup.
Before Deploying to the Simulator
The table describes the actions you need to perform to be able to proceed with the deployment, depending on the computer on which the emulated simulator is running.
Computer selected for deployment
Computer on which a software component is installed.
(Recommended method)
Other computer on which no software component is installed.
Actions
Start the simulator.
1. Install the simulator.
2. Start the simulator.
Refer to the topic describing how to install the Controller Simulator. (see EcoStruxure ™
Process Expert, Installation and
Configuration Guide)
Starting the Emulated Simulator
EcoStruxure Process Expert supports only deployment to the controller simulator that uses port 502.
To start the simulator provided with the software, proceed as follows.
Step
1
Action
Double-click the shortcut of the controller simulator on the desktop.
Result: The emulated simulator starts minimized as an icon in the notification area. By default the password-protected Control project (see EcoStruxure ™ Process Expert,
Installation and Configuration Guide) is loaded.
NOTE: If you had installed the simulator manually, double-click the sim.exe
file located in the PLC_Simulator folder.
NOTE: For information on using the simulator, refer to the simulator help, which is located in the PLC_Simulator folder. You can open the help of the simulator also directly from the simulator panel after starting it.
Starting the Simulator With Another Password-Protected
Control Project
You can modify the way the simulator starts and have it load your own passwordprotected Control project file (.sta).
Once you have configured the simulator to start by loading your own Control project, you will need to
provide the password to use it, page 489
.
To start the simulator by loading a specific password-protected Control project, proceed as follows.
Step
1
2
3
Action
Start the simulator.
Right-click the simulator icon in the Windows ® taskbar and select Options...
.
Result : The Simulator Panel Options dialog box opens.
Select the Use default application to start simulator (enforce security) check box.
485
486
Step
4
5
6
Action
Click the browse button and select your password-protected Control Expert Control project file (.sta).
Click OK .
Result : The simulator stops.
Start the simulator.
Result : The simulator starts by loading the selected Control Expert Control project file.
Starting the Simulator Without Password-Protected Control
Project
You can modify the startup setting and start the simulator without loading a password-protected Control project file (.sta). However, modifying this setting is not recommended because it leaves the Ethernet port of the computer, which is used by the simulator vulnerable to cyber attack.
To start the simulator without loading a password-protected Control project, proceed as follows.
Step
1
2
3
4
Action
Start the simulator.
Right-click the simulator icon in the Windows ® taskbar and select Options...
.
Result : The Simulator Panel Options dialog box opens.
Clear the Use default application to start simulator (enforce security) check box.
Click OK .
Result : You do not require to enter a password to use the simulator.
NOTE: When you restart the simulator, it starts without loading a Control project
(no configuration).
Starting the Simulator Under Another Windows
®
session
Once you have configured the simulator to start by loading a password-protected
Control project, you will need to
provide the password to use it, page 489 .
To start the simulator by loading the default Control project provided with the software or another one when you are logged on to a Windows ® that is different from the one used to install the software, proceed as follows.
Step
1
2
3
4
5
6
Action
Start the simulator.
Right-click the simulator icon in the Windows ® taskbar and select Options...
.
Result : The Simulator Panel Options dialog box opens.
Select the Use default application to start simulator (enforce security) check box.
Click the browse button and select the password-protected Control project file (.sta) that you want to use. This is either of the following files:
• Simulatorprofile.sta that is provided with the software and that you have copied to the computer. The file is located in the AFS folder in the root of the installation package of the software.
• Your own Control Expert Control project file.
Click OK .
Result : The simulator stops.
Start the simulator.
Result : The simulator starts by loading the selected Control project file.
EIO0000001114.15
Obtaining the IP Address of the Simulator
If you leave 127.0.0.1 as IP address for the
on which the simulator is running, it automatically defaults to the simulator that is installed on the system server. To use the simulator that is installed on a computer on which no system server is installed (for example, an engineering station on which only the engineering client is installed), you need to enter the actual IP address of the local computer on the subnet (host IP address).
To obtain the host IP address used by the emulated simulator software, proceed as follows.
Step
1
2
3
Action
Start the software emulating a simulator provided by the software.
Double-click the simulator icon in the notification area.
Result: The Controller Simulator Panel is displayed.
Read the IP address in the Host IP address field.
Using Deployment Commands With the Simulator
The procedure is similar to using deployment commands with a controller. You need to use the commands that appear in the context menu of the station node that you have mapped to the executable of the Control Participant project.
Refer to the description of commands that are documented in this
Communication Between the Computer and Engines
Controllers
To deploy a built Control Participant project, ensure that the computer that is running the virtual machine (VM) can communicate through the Ethernet network with the controller or its communication module, which is modeled by the entity that you want to deploy to.
Depending on the configuration of the software components (see EcoStruxure ™
Process Expert, Installation and Configuration Guide), the computer can be the one on which either software is installed:
• The system server (if the engineering client is using this VM).
• The engineering client (if it is using its local VM).
For more information on connecting controllers to an Ethernet network, refer to the
Control Participant help.
Station Nodes
To deploy a built Control Participant project, ensure that the computer that is running the system server can communicate through the Ethernet network with the computer, which is modeled by the station node that you want to deploy to.
Refreshing Engine Status and Reconnecting Engines
When you use the various deployment and execution commands, a confirmation dialog opens in which you need to select the IP address of the target engine.
The engine needs to be reachable to be able to proceed with the deployment or execution command. Once you have selected the IP address, the status of the engine is indicated in the Status field. If the status of the engine changes while the confirmation dialog box is open, its status is not refreshed.
EIO0000001114.15
487
This can be the case, for example, if the status of the engine is detected as Not
Reachable because a network cable is unplugged. After you reconnect the cable, the status is unchanged. Click the reconnect button to refresh the status of the engine and attempt to establish the connection.
The following figure shows an example of deployment confirmation dialog box featuring the reconnect button.
1 Reconnect button
Managing Passwords of Control Participant Projects
Overview
Using password protection restricts deployment and execution operations for
Control Participant projects that you perform by using an engineering client. It also restricts operations performed by using the operation client.
This topic describes how you can perform the following actions on controllers and the simulator running on a station node:
• Setting a password for the first time.
• Changing a password. This includes changing a password for a controller for which a password was already set by using other applications than the software.
• Clearing a password.
• Resetting the password if you forgot it.
Setting a password is mandatory if you have
enabled password protection, page
for topological entities; otherwise, you cannot deploy Control Participant projects.
NOTE: For information on the default password for the simulator (to be entered in the Current Password text box when you want to set a password), refer to the topic describing how to install the controller simulator (see
EcoStruxure ™ Process Expert, Installation and Configuration Guide).
NOTE: Deploying a Control Participant project after setting or changing the password takes slightly longer than deploying with an existing or without password.
488 EIO0000001114.15
EIO0000001114.15
Scope of the Password Protection
The Controller password that you can set by using the commands in the context menu of the topological entity corresponds to the Application password of the
Control Participant. The corresponding settings are disabled in the Control
Participant ( Protection tab of the properties of the project).
NOTE: Other passwords that are managed by the Control Participant are not supported except for the
for M580 safety controllers.
The table describes which Control projects managed by the software benefit of the password protection.
Control Participant project
Logical Control project
Built Control project
Deployed Control project
Password protection applies
No
No
Yes
Actions That Require Providing the Password
The table outlines the various actions for which you need to provide a password if password protection is enabled for the controller or simulator running on a station node.
Topological entity
Station node/ simulator only
Controller only
Action
Setting the password.
First deployment.
Subsequent deployment and execution operations.
Setting the password.
Password that is required
The password that is used in the Control project file (.
sta) that is loaded when the simulator starts.
By default, this is the Control project file that is provided with the software (see EcoStruxure ™
Process Expert, Installation and Configuration
Guide).
NOTE: The simulator may have been
to load another Control project file when starting or the password may have been
You need to set a password first.
No password required as long as you keep the engineering client open.
If you close the engineering client or lock it and another user logs in, the password that you have set is required.
No password is required.
If a password is already set for the controller (for example, by using an application other than the software), the current password is required to be able to set a new one.
NOTE: Setting the password when no Control
Participant project is deployed to the controller requires stopping the controller.
You need to set a password first.
The current password.
First deployment.
Any deployment and execution operation after setting or changing the password.
Subsequent deployment and execution operations.
Navigating to a section by using Runtime Navigation
No password required as long as you keep the engineering client open.
If you close the engineering client or lock it and another user logs in, the current password is required.
The current password.
489
490
Topological entity
Action Password that is required
Controller or station node/ simulator
Services (operation client).
Resetting the password if you have forgotten it.
Changing the password.
Clearing the password.
If you close the operation client or lock it and another user logs in, the current password is required again.
The temporary password provided by Schneider
Electric support.
The password that is currently set.
The password that is currently set.
Using the
Project
Re-Deploy last command.
The password that is currently set.
NOTE: If before redeploying the initial project
(protected with password A), another project that is protected with password B and belonging to a different system has been deployed from a different client to the same engine, during redeployment of the initial project, you need to enter password B. The deployment operation performed from a different system and client has changed the password that had been set during the initial deployment (password A).
The password that is currently set.
Using the Back Up Data command for the first time after deploying a Control project.
Any deployment and execution operations after importing the controller or station node.
Any deployment and execution operations after restoring a system containing the controller or station node.
Any deployment and execution operations after restoring a database containing a system with the controller or station node.
Recovering from a signature mismatch.
The password that is currently set.
If no password is set yet, you need to set one (or, for a station node, provide the password that is used in the Control project file (.sta) that is loaded when the simulator starts).
The password that is currently set.
Disabling the or Simulator
Controller password property when a Control
Participant project was deployed while the setting was enabled.
The password that is currently set.
NOTE: Disabling the password property opens the Disable Password Protection dialog box.
This also clears the password.
Password Requirements
Your password must contain between 8 and 16 alphanumeric characters.
It can contain lower and upper case as well as special characters.
NOTE: Password strength is increased when it contains a mix of upper and lower case, alphabetical, numerical, and special characters.
Managing Application Passwords with Redundant Controllers
The following are the specific password management rules that apply to redundant controllers:
• Both primary and standby engines of the topological entity must be reachable by using the IP addresses that you have configured and the Hot Standby cable link must be present.
• The same application password is set for the Control project of both engines.
Changing or clearing the password also applies to both engines.
EIO0000001114.15
• When the ControllerExist
of a redundant controller is set to Primary , passwords are managed the same way as for a standalone controller.
The following describes the operating mode for redundant controllers when a password mismatch occurs:
• If setting, changing, or clearing the password for the Control project of the standby controller did not succeed, you need to synchronize it by using the
Sync (Primary→Standby) command. You can still proceed with the deployment to the primary controller.
• When you are prompted to provide the password for security purposes, the password is compared with that of the Control project in both engines. If the password of the project in the standby engine does not match, you cannot perform the operation on the standby engine.
Setting the Application Password of a Control Project
The following are prerequisites to be able to set the application password for a
Control project:
• You have created a topological entity of type controller or station node.
• The topological entity is configured:
◦ For a controller: You have used the Configure command and saved changes.
◦ For a station node: You have created the ControlExpert service.
• The Controller or Simulator password property of the topological entity is enabled.
• The engine of the topological entity must be reachable by using the IP address that you have configured. In case of the simulator, it must be running.
You can set a password even if you have already deployed a Control project while the password protection for the topological entity was disabled. The password is set for the already deployed Control project without stopping the controller.
NOTE: You can use this functionality also to change the password of the
Control project that is loaded when you start the simulator.
The following figure shows the Manage Password dialog box for the simulator running on a station node.
EIO0000001114.15
1 Check box that lets you also
of the Control project that is loaded when you start the simulator.
To set the application password for a Control project, proceed as follows.
491
492
2
3
4
Step
1
5
Action
Right-click the topological entity and select:
• For a controller: Manage Password
For an M580 safety controller, select Controller in the submenu.
• For a station node (simulator): Control > Manage Password
Result: The Manage Password dialog box opens.
Enter the current password in the Current Password text box if
.
Enter the new password and confirm the new password in the corresponding text boxes.
If you want to use this password also in the Control project that is loaded when the simulator starts, select the check box. It replaces the password that is currently used in this Control project file.
Click OK .
Result: The password is saved and set as application password.
Verifying the Password to Perform Deployment and Execution
Tasks
When you select a command and are prompted to enter the password that is set for a controller or simulator running on a station node, proceed as follows.
Step
1
2
Action
In the Verify Password dialog box, enter the required password.
NOTE: Alternatively, you can select the Use last entered password check box. It fills the text box with the last password that you have entered in a Verify Password dialog box during the current engineering client session. The text box becomes read-only.
Click OK .
Result: If the password is correct, the command is executed. If not, an information message is displayed, prompting you to reenter the password. You can enter the password three times before the command is canceled.
NOTE: Click Cancel to cancel the command you had selected.
Changing the Application Password of a Control Project
To be able to change the password, the engine of the topological entity must be reachable by using the IP address that you have configured.
To change the application password for a Control project, proceed as follows.
Step
1
2
3
4
5
Action
Right-click the topological entity and select:
• For a controller: Manage Password
For an M580 safety controller, select Controller in the submenu.
• For a station node (simulator): Control > Manage Password
Result: The Manage Password dialog box opens.
Enter the current password in the Current Password text box.
Enter the new password and confirm the new password in the corresponding text boxes.
If you want to use this password also in the Control project that is loaded when the simulator starts, select the
. It replaces the password that is currently used in this Control project file.
Click OK .
Result: The password is saved and set as application password.
EIO0000001114.15
Clearing the Application Password of a Control Project
To be able to clear the application password, the engine of the topological entity must be reachable by using the IP address that you have configured.
NOTE: Clearing the application password does not clear the password of the
Control project that is loaded when the simulator starts.
To clear the application password for a Control project, proceed as follows.
Step
1
2
3
Action
Right-click the topological entity and select:
• For a controller: Clear Password
For an M580 safety controller, select Controller in the submenu.
• For a station node (simulator): Control > Clear Password
Result: The Clear Password dialog box opens.
Enter the current password in the Current Password text box.
Click OK .
Result: The password is cleared.
Resetting a Forgotten Password
To reset the application password of a Control project, proceed as follows.
Step
1
2
3
4
Action
Right-click the topological entity and select Forgot Password .
For an M580 safety controller, select Controller in the submenu.
Result: The Forgot Password dialog box opens and a number is displayed in the
Authentication Code field.
NOTE: If you close the Forgot Password dialog box and open it again, the same number is displayed.
Contact Schneider Electric
and provide the number.
Result: You receive a temporary password.
NOTE: You can use the temporary password as long as you do not modify the application that is deployed to the controller.
Right-click the topological entity and select Manage Password .
For an M580 safety controller, select Controller in the submenu.
Result: The Manage Password dialog box opens.
Follow the procedure to
and enter the temporary password in the Current Password text box.
Changing the Password of the Control Project Loaded at
Simulator Start-Up
You can change the password of the default Control project file or
that is loaded when the simulator starts if the functionality is enabled.
The folder containing the project file must not be write-protected.
The table indicates from where you can change the password of the Control project file depending on the location of the controller simulator.
EIO0000001114.15
493
Computer on which the controller simulator is running
System server computer.
Software component on which you need to perform the password change
Any engineering client.
The IP address of the NIC of the station node in the Topology
Explorer must correspond to the system server computer.
Engineering client computer.
The local engineering client.
Operation client computer.
Other computer on which the controller simulator was installed manually.
1. Copy the project file loaded in the controller simulator to the local engineering client computer (if the project file loaded in both simulators is different; otherwise, proceed to step 3).
2.
Configure the simulator, page 485
on the local engineering client computer to load this project file at start-up.
3. Change the password of the project file by using the local engineering client.
4. Replace the project file on the operation client or the other computer.
4
5
6
To change the password of the Control project file that is loaded when the simulator starts, proceed as follows.
Step
1
2
3
Action
Start the controller simulator or restart it.
Right-click the station node that represents the computer on which the controller simulator is running and select Control > Manage Password .
Result: The Manage Password dialog box opens.
In the Current Password text box, enter the password of the Control project file that is loaded when the simulator starts.
Enter the new password and confirm the new password in the corresponding text boxes.
Select the
Click OK .
Result: The password is changed in Control project file.
Deploying to Redundant Controllers
Overview
This topic describes aspects that are specific to the deployment of Control
Participant projects to redundant controllers, which are modeled in the topology of the system.
The same commands that are used on standalone configurations are also used for redundant controllers.
Detailed information on the commands that are available as part of the deployment stage are described later in the chapter.
For a description of the sequence of actions that Control performs on the engines, refer to the topic describing
main redundant controller scenarios, page 561 .
ControllerExist Property
Verify that the value of the ControllerExist
that is selected in the properties of the redundant controller entity matches the physical configuration of the hardware.
If the software detects a mismatch, you cannot proceed with the deployment.
NOTE: Selecting PrimaryAndStandby for the ControllerExist property requires that both controllers are reachable and connected by a Hot Standby cable link.
NOTE: The value of the property also affects
.
494 EIO0000001114.15
EIO0000001114.15
Engine Status for Redundant Controllers
When you select a command for a redundant controller, composed of one primary and one standby engine to which IP addresses IP and IP + 1 are assigned respectively, before proceeding with the deployment, the software opens various dialog boxes, depending on the command that you have selected.
Each of these dialog boxes features the Status field, which informs you of the current state of each of the engine roles (A and B) that the software has detected.
States for M580 platform controllers
Run Primary
Run Standby
Wait
Stop
No conf (non-configured state)
States for Quantum platform controllers
Run Primary
Run Standby
Run Offline
Stop Offline
No conf (non-configured state)
NOTE: If you have selected Primary for the ControllerExist property of the controller entity, the status of the standby engine is not available.
General Deployment Behavior for Redundant Controllers
When you deploy to a redundant controller:
• The software deploys to both the primary and the standby engines unless you have selected Primary for the ControllerExist property of the controller entity. You can view and/or select the IP address for the primary engine ( IP ) and the software automatically selects IP address IP + 1 as the standby engine.
• If you select to start the engines after deployment, both engines are started.
If deployment to the first engine ( IP or IP + 1 , depending on the
status of the engine, page 561 ) does not complete successfully, the entire deployment process
is canceled.
If deployment to the second engine ( IP or IP + 1 , depending on the status of the engine) or if synchronization does not complete successfully, logic that was deployed successfully to the first engine is preserved.
NOTE: For controllers of the M580 platform, you cannot perform deployment tasks on the CPU module or a NOC communication module by using IP address A and IP address B . You can only select
Redundant Controller Stop Sequence
When deployment requires to stop the controller and both engines are running, the software stops in the following order:
• The standby engine
• The primary engine
Deploying Changes to Redundant Controllers
If the primary controller is in Running Primary state, and you deploy changes that do not require stopping the controller by using the Deploy Changes / Undo
Online Changes
:
• The software enables the configuration mismatch feature of the controller so that the standby controller does not enter the offline operating mode when changes are deployed to the primary controller.
• The software deploys to the primary controller first, and upon successful completion of the deployment, automatically synchronizes the standby controller.
495
• Then, the software disables the configuration mismatch feature.
When you deploy changes to a redundant controller, although deployment to the primary controller succeeded, it is possible that
synchronization of the standby controller, page 563
does not complete. If an interruption of the connection to the system server or an unexpected stop of the system server is the cause, the notification panel also contains additional information about steps that you must complete when the connection to the system server is re-established. This is the case, for example, when the software cannot disable the configuration mismatch feature. If this feature is enabled and a switchover occurs, the standby controller operates with a program that does not contain the changes that you have deployed to the primary controller.
WARNING
UNINTENDED EQUIPMENT OPERATION
• Verify that deployment to the standby controller completed successfully.
• Do not operate the primary controller if deployment to the standby controller does not complete successfully.
• Synchronize the standby controller manually, using the Sync
(Primary→Standby) command and verify that the synchronization completed successfully.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: If the primary controller is not in Running Primary state, synchronization of the standby controller cannot complete successfully. In such case,
the primary engine synchronizes the standby engine.
Deploying the Control Participant Project
Overview
The Topology Explorer allows you to deploy the complete Control Participant project to a controller or station node that is modeled by an engine in the topology of the system by using the following commands:
• Deploy Built Project : Deploys the built Control Participant project to the controller/station node that is
mapped to the corresponding executable, page
• Re-Deploy Last Project : Deploys the same built Control Participant project that you have deployed to the controller/station node last. This is done by using a mirror of the deployed Participant project, called the last deployed reference, which is stored in the
.
To deploy or redeploy a built Participant project, the controller or the emulated simulator that you are deploying to must be in Stop state before proceeding. If it is not, the software informs you of it, and stops the engine when you proceed with the deployment.
Also, the software gives you the option to start the controller following the deployment.
Built Participant Project Build Status
The software lets you deploy a built Control Participant project whose executable is either marked as being out of date or that you have not built again after
making changes to the system, page 470
, which affect the built Participant project.
The software displays a message in the confirmation dialog boxes of deployment commands if the
of the associated executable is Out Of
Date .
496 EIO0000001114.15
Selecting Participant Project and Control Executable
When you select the Deploy Built Project command for an engine, the software displays the Deploy Built Project dialog box, which allows you to select:
• Project : Any Control project that exists in the system and:
◦ Whose
property has the same value as the engine.
◦ Contains a built or out of date executable that is mapped to the engine.
• Executable : For each project, any Control
that is
mapped to the engine, page 423 .
NOTE: When you select Deploy Built Project from a station node, you can select any Control project that has a Control executable that is mapped to this station node.
Deploying to a Redundant Controller
For information that applies specifically to the deployment to redundant controllers, refer to the related
Control Participant Project Information
Before proceeding with the deployment or redeployment of a built Participant project, the software displays information in the Confirm Deploy Built Project dialog box about:
• The engine that you are deploying to.
• The built Participant project to be deployed.
• The Participant project deployed last to the engine.
EIO0000001114.15
497
The figure shows an example of the Confirm Deploy Built Project dialog box for a redundant controller.
498
The table describes the information that is displayed in the Engine Information section of the Confirm Deploy Built Project dialog box.
Label
Role (1)
Status
Description
Role of the engine: A or B .
If the software cannot communicate with the engine, the role is indicated as Not Detected .
Status of the engine that is selected for deployment.
If the status is Not Reachable you cannot proceed with the deployment. In such case, verify the IP address, the connection to the engine, and the status of the engine.
NOTE: If the status is Running , a notification is displayed in the dialog box to inform you that the engine will be stopped if you proceed with the deployment.
IP Address Identifier of the communication module through which the software will deploy the built
Participant project and its IP address that is configured in the Topology Explorer .
If the topological entity has several communication modules, you can select which one you want to deploy to.
NOTE: For controllers of the M580 platform, you cannot deploy to the CPU module or a NOC communication module by using IP address A . You can only select
(1) Displayed only when you deploy a built Participant project to a redundant controller.
NOTE: To refresh the engine status and attempt to connect to it, click the reconnect
.
The table describes the information that is displayed in the Project Information section of the Confirm Deploy Built Project dialog box. It also describes the check box.
EIO0000001114.15
Name column
System
Project
Executable
Controller
Last Built On
Last Deployed
On
Last Online
Change
Performed On
Last Sync.
Performed On (1)
Selected Project column
Identifier of the system that both the engine and the
Control project, which you have selected belong to.
Identifier of the Control Participant project that you have selected.
Identifier of the Control executable that you have selected and that contains the built Participant project to be deployed.
Identifier of the topological entity to which you are deploying the built Participant project.
Date and time when you successfully built the Control
Participant project to be deployed.
Not applicable
Not applicable
Not applicable
Last Deployed Project column (2)
Identifier of the system that both the engine and the
Control project, from which you have deployed the
Participant project last belong to.
Identifier of the Control Participant project associated to the executable that you have deployed last.
Identifier of the Control executable that contains the built
Participant project that you have deployed last.
Identifier of the topological entity to which you have deployed the built Participant project last.
Date and time when you successfully built the Control
Participant project that you have deployed last.
Date and time when you last deployed the Participant project to the engine or you last completed the Deploy
Changes / Undo Online Changes command, independently if there were changes to be deployed or not.
Date and time when you last changed the deployed
Participant project by using the Refine Online command; otherwise the field is empty.
Date and time when you last synchronized the standby controller with the primary one by using the Synchronize
(Primary→Standby) command.
Start engine after deployment
Select the option if you want to start the controller or emulated simulator when deployment is complete; otherwise the engine remains in stop state.
NOTE: The software stops the engine before proceeding with the deployment if the engine is not yet in stop state.
(1) Displayed only when you deploy a built Participant project to a redundant controller.
(2) When you deploy to a redundant controller, the dialog box shows separate columns for the primary and the standby engine.
NOTE: When you deploy for the first time to an engine, the fields of the Last
Deployed Project section are empty.
Deploying the Control Participant Project
WARNING
UNINTENDED EQUIPMENT OPERATION
Before deploying to a controller, verify that:
• You have assigned a valid IP address to the controller.
• The IP address corresponds to the physical address printed on the hardware.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: For more information, refer to
Identifying Engines, page 483 .
WARNING
UNINTENDED EQUIPMENT OPERATION
Before deploying to an engine, verify that you have selected the correct project files.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Unintended situations can occur if the operations that are in progress are not known when acting on a controller.
EIO0000001114.15
499
500
WARNING
UNKNOWN OPERATIONAL STATE OF EQUIPMENT
Before starting or stopping a controller, always positively confirm that there is no critical operation in progress.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
When deploying to a redundant controller,
deployment to the standby controller, page 563
may not complete successfully. In such case, the software displays a message in the notification panel to inform you.
WARNING
UNINTENDED EQUIPMENT OPERATION
• Verify that deployment to the standby controller completed successfully.
• Do not operate the primary controller if deployment to the standby controller does not complete successfully.
• Synchronize the standby controller manually, using the Sync
(Primary→Standby) command and verify that the synchronization completed successfully.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: For information on the Sync (Primary→Standby) command, refer to the
To deploy the Control Participant project, proceed as follows.
Step
1
2
8
9
6
7
3
4
5
Action
Verify that the engine can
communicate with the PC, page 487
and that it is in Stopped state.
When deploying to a station node, verify that the software emulating the simulator is
In the Topology Explorer , right-click the entity to which you want to deploy the built
Participant project and select Deploy Built Project .
Result: The software displays the Deploy Built Project dialog box.
Click the menu next to Project and select the Control project.
Click the menu next to Executable and select the executable associated to the built
Control project that you want to deploy.
Click OK .
Result: The software displays the Confirm Deploy Built Project dialog box.
NOTE: Click Cancel to close the dialog box without deploying.
Verify the information that is displayed.
Verify the status of the engine in the Status field.
Verify the communication module identification or select one in the IP Address field.
Select Start engine after deployment if you want the software to start the engine after the deployment is complete.
EIO0000001114.15
Step
10
11
Action
Click OK .
Result: The software displays the Reconfirm Deploy Built Project dialog box.
NOTE: Click Cancel to close the Confirm Deploy Built Project dialog box without deploying.
Click OK .
Result: The software:
• Stops the engine if it is running.
• Deploys the Control Participant project.
• Displays Completed in the notification panel once it has successfully completed the deployment process to the engine, which is identified by its IP address.
◦ For a redundant controller, the notification panel displays separate messages for the primary and the standby engines by using their respective IP address to identify them. If deployment to either engine does not complete successfully, the software displays a corresponding message in the notification panel.
• Updates the related date/time field.
• Starts the controller (cold start) or software emulating a simulator if you selected the option.
NOTE: Click Cancel to close the Reconfirm Deploy Built Project dialog box without deploying. This reverts to the Confirm Deploy Built Project dialog box.
NOTE: If the deployment process does not complete successfully and the software has stopped the engine before deploying the Participant project, the engine remains in Stopped state.
Re-Deploying the Control Participant Project
Overview
The Re-Deploy Last Project command for an engine becomes available once you have deployed a project to this engine.
The process of redeploying the Control Participant project is identical to the
with the exception that you cannot select a Control project and an associated Control executable for deployment. The software deploys to the controller or station node emulating a simulator a mirror image of the last deployed Participant project, which is the last deployed reference.
To redeploy a built Participant project, the engine that you are deploying to, must be in Stopped state before proceeding. If it is not, the software informs you of it, and stops the engine when you proceed with the deployment.
NOTE: If you made changes to the deployed Participant project using the
Refine Online and/or if you have deployed changes using the Deploy
Changes commands, then the Participant project that the software redeploys to the controller contains these changes.
Redeploying to a Redundant Controller
For information that applies specifically to the redeployment to redundant controllers, refer to the topic describing
deployment to redundant controllers, page
Control Participant Project Information
Before proceeding with the re-deployment of the last deployed reference, the software displays information in the Confirm Re-Deploy Last Project dialog box about:
• The engine that you are re-deploying to.
• The project to be re-deployed.
• The Participant project deployed last to the engine.
EIO0000001114.15
501
The figure shows an example of the Confirm Re-Deploy Last Project dialog box for a redundant controller.
502
The table describes the information that is displayed in the Engine Information section of the Confirm Re-Deploy Last Project dialog box.
Label
Role (1)
Status
Description
Role of the engine: A or B .
If the software cannot communicate with the engine, the role is indicated as Not Detected .
Status of the engine that is selected for deployment.
If the status is Not Reachable you cannot proceed with the deployment. In such case, verify the IP address, the connection to the engine, and the status of the engine.
NOTE: If the status is Running , a notification is displayed in the dialog box to inform you that the engine will be stopped if you proceed with the deployment.
EIO0000001114.15
Label
IP Address
Description
Identifier of the communication module through which the software will deploy the built
Participant project and its IP address that is configured in the Topology Explorer .
If the topological entity has several communication modules, you can select which one you want to deploy to.
NOTE: For controllers of the M580 platform, you cannot redeploy to the CPU module or a NOC communication module by using IP address A . You can only select
(1) Displayed only when you redeploy a built Participant project to a redundant controller.
NOTE: To refresh the engine status and attempt to connect to it, click the reconnect
.
The table describes the information that is displayed in the Project Information section of the Confirm Re-Deploy Built Project dialog box. It also describes the check box.
Name column
System
Project
(1)
(1)
Executable (1)
Selected Project column Last Deployed Project column (2)
Identifier of the system that both the engine and the Control project, which you have selected belong to.
Identifier of the Control Project that you have selected.
Identifier of the Control executable that you have selected and that contains the built Participant project to be deployed.
Controller (1)
Last Built On
Last Deployed
On
Last Online
Change
Performed On
Last Sync.
Performed On (3)
Identifier of the controller/station node to which you are deploying the built Participant project.
Date and time when you successfully built the Control
Participant project to be deployed.
Not applicable
Date and time when you successfully built the Control
Participant project that you have deployed last.
Date and time when you last deployed the Participant project to the engine or you last completed the Deploy
Changes / Undo Online Changes command, independently if there were changes to be deployed or not.
Not applicable Date and time when you last changed the deployed
Participant project by using the Refine Online command; otherwise the field is empty.
Date and time when you last synchronized the standby controller with the primary one by using the Synchronize
(Primary→Standby) command.
Start engine after deployment
Select the option if you want to start the engine when deployment is complete; otherwise the engine remains in stop state.
NOTE: The software stops the engine before proceeding with the deployment if the engine is not yet in stop state.
(1) The values of the Selected Project and Last Deployed Project fields are identical.
(2) When you redeploy to a redundant controller, the dialog box shows separate columns for the primary and the standby engines.
(3) Displayed only when you redeploy to a redundant controller.
Re-Deploying the Last Deployed Reference
WARNING
UNINTENDED EQUIPMENT OPERATION
Before deploying to a controller, verify that:
• You have assigned a valid IP address to the controller.
• The IP address corresponds to the physical address printed on the hardware.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
EIO0000001114.15
503
504
NOTE: For more information, refer to
Identifying Engines, page 483 .
WARNING
UNINTENDED EQUIPMENT OPERATION
Before deploying to an engine, verify that you have selected the correct project files.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Unintended situations can occur if the operations that are in progress are not known when acting on a controller.
WARNING
UNKNOWN OPERATIONAL STATE OF EQUIPMENT
Before starting or stopping a controller, always positively confirm that there is no critical operation in progress.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
When redeploying to a redundant controller,
re-deployment to the standby controller, page 563
may not complete successfully. In such case, the software displays a message in the notification panel to inform you.
WARNING
UNINTENDED EQUIPMENT OPERATION
• Verify that deployment to the standby controller completed successfully.
• Do not operate the primary controller if deployment to the standby controller does not complete successfully.
• Synchronize the standby controller manually, using the Sync
(Primary→Standby) command and verify that the synchronization completed successfully.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: For information on the Sync (Primary→Standby) command, refer to the
To redeploy the last deployed reference, proceed as follows.
Step
1
2
3
4
5
Action
Verify that the engine can
communicate with the PC, page 487
and that it is in Stopped state.
When redeploying to a station node, verify that the software emulating the simulator is
In the Topology Explorer , right-click the entity to which you want to deploy the built
Participant project and select Re-Deploy Last Project .
Result: The software displays the Confirm Re-Deploy Last Project dialog box.
Verify the information that is displayed.
Verify the status of the engine in the Status field.
Select Start engine after deployment if you want the software to start the engine after the redeployment is complete.
EIO0000001114.15
Step
6
7
Action
Click OK .
The software displays the Reconfirm Re-Deploy Last Project dialog box.
NOTE: Click Cancel to close the Confirm Re-Deploy Last Project dialog box without redeploying.
Click OK .
Result: The software:
• Redeploys the last deployed reference to the engine.
• Displays Complete in the notification panel once it has successfully completed the re-deployment process to the engine, which is identified by its IP address.
◦ For a redundant controller, the notification panel displays separate messages for the primary and the standby engines by using their respective IP address to identify them. If redeployment to either engine does not complete successfully, the software displays a corresponding message in the notification panel.
• Updates the related date/time field.
• Starts the controller (cold start) or software emulating a simulator if you selected the option.
NOTE: Click Cancel to close the Reconfirm Re-Deploy Last Project dialog box without re-deploying. This reverts to the Confirm Re-Deploy Last Project dialog box.
NOTE: If the redeployment process does not complete successfully and the software has stopped the engine before redeploying the Participant project, the engine remains in Stopped state.
Deploying Data to Controllers and Station Nodes
Overview
The Deploy Data command lets you deploy data contained in a
that has been created by using the Back Up Data command.
You can select one file from a list of backup files that have been created for all executables of the same Control Participant project. The selection dialog shows the information that was associated to each backup file at the time of creation, including the type of data that was selected.
By default, backup files are listed in descending order of time stamp (most recent one on top).
NOTE: For more information, refer to Save/Restore Data Between a File and the PLC in the help of the Control
.
Deploying Data to Redundant Controllers
For redundant controllers, deployment of data is possible only to the primary controller.
To be able to deploy data to the primary controller, the standby controller must be reachable at the IP address that is configured. It may not be reachable, for example, because it is switched off or the Hot Standby cable is removed.
Only if the ControllerExist
is set to Primary you can deploy data to the primary controller while the standby controller is not reachable.
NOTE: The status of the standby controller is not shown in the Confirm
Deploy Data dialog box.
Data Backup File Information
Before proceeding with the deployment of controller data, the software displays information in the Confirm Deploy Data dialog box about:
• The deployed Control Participant project.
EIO0000001114.15
505
• The executable that is deployed.
• Executables of this Control project for which a backup file exists.
• The type of data contained in each backup file.
• The backup file identification.
NOTE: If you change the identifier of a controller or executable, or the role of a controller, the identification information of the corresponding backup file is not modified.
You can
the information that is displayed.
The following figure shows an example of the Confirm Deploy Data dialog box for a standalone controller.
The following figure shows an example of the Confirm Deploy Data dialog box for a redundant controller.
506
The table describes the information that is displayed in the Engine Information section of the Deploy Data dialog box.
Label
Controller (1)
Role (1)
Status
Description
You can deploy controller data only to the primary controller.
Default value: Primary
Role of the engine: A or B .
If the software cannot communicate with the engine, the role is indicated as Not Detected .
Status of the engine that is selected for deployment of data.
EIO0000001114.15
EIO0000001114.15
Label Description
IP Address
If the status is Not Reachable , you cannot proceed with the deployment.
In such case, verify the IP address, the connection to the engine, and the status of the engine.
Identifier of the communication module through which the software will deploy data and its IP address that is configured in the Topology
Explorer .
If the topological entity has several communication modules, you can select which one you want to use.
Default value: IP address that was selected for the last deployment operation to this engine.
NOTE: For controllers of the M580 platform, you cannot deploy data to the CPU module or through a NOC communication module by using IP address A . You can only select
(1) Displayed only when you deploy data to a redundant controller.
NOTE: To refresh the engine status and attempt to connect to it, click the reconnect
.
The table describes the information that is displayed in the Project Information section of the Deploy Data dialog box.
Label
Control
Project
Executable
Last
Deployed
On
Description
Identifier of the Control Participant project associated to the executable that you have deployed last.
Identifier of the Control executable to which you are deploying data.
Date and time when you last deployed the Participant project to the engine or you last completed the Deploy Changes / Undo Online Changes command, independently if there were changes to be deployed or not.
The table describes the information that is displayed in the Select Backup Data section of the Confirm Deploy Data dialog box.
Column header
Description
Time Stamp Date and time of the backup file creation.
Description Description that was entered when the backup file was created.
User Name of the user who was logged on when the backup file was created.
Executable
Controller
%M
%MW
Unlocated
Variables
Unlocated
FBs
Identifier of the Control executable whose data is contained in the backup file.
Identifier of the controller that was running the executable whose data was backed up.
For redundant controllers, it also indicates the role of the controller that was selected when the backup file was created.
Indicates the memory range of located variables of boolean data type that are contained in the backup file.
If no such data was selected during data backup, the value shown is N/A .
Indicates the memory range of located variables of WORD data type that are contained in the backup file.
If no such data was selected during data backup, the value shown is N/A .
True indicates that this type of data was selected during data backup.
Possible values:
• True
• False
507
Control Project Signature Verification
Before executing the command, the software compares the Control Participant project that is deployed in the engine with the
last deployed reference, page 482 ,
which is the Control Participant project residing in the software.
If they are identical, the command is executed. If they differ, the software starts a recovery process first. This process may take several minutes to complete.
In case the software displays a notification about a signature mismatch, the command cannot be executed. Contact Schneider Electric
.
Deployed Data Conflicts
Before proceeding with the deployment of data contained in the selected backup file, the software opens a dialog box in case it detects any conflicts in the data to be deployed. It displays the data instances that cannot be deployed.
You have the choice to proceed with the deployment but without the conflicting data instances or to cancel the deployment operation entirely.
The following figure shows an example of the Deploy Data Conflicts dialog box.
508
Deploying Data Contained in a Backup File
Unintended situations can occur if the operations that are in progress are not known when acting on a controller.
Deploying data when the controller is in RUN state may take several scan cycles and corrupt the program data. This adversely affects the execution of the program.
Further, deploying data to the controller may change program data. This affects the execution of the program when the controller is in STOP state and then switched to RUN state after the deployment.
EIO0000001114.15
WARNING
UNINTENDED EQUIPMENT OPERATION
Before deploying data to the controller:
• Verify that the controller state does not jeopardize data integrity when the data is deployed.
• Verify the impact of the deployment on the execution of the program.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: Schneider Electric recommends deploying data while the controller is in STOP state.
To deploy data contained in a backup file to a controller or station node, proceed as follows.
Step
1
2
5
6
7
3
4
8
Action
Verify that the engine can
communicate with the PC, page 487 .
When deploying to a station node, verify that the software emulating the simulator is
In the Topology Explorer , right-click the entity to which you want to deploy data and select Deploy Data .
Result: The software opens the Confirm Deploy Data dialog box.
In the IP Address field, verify that the communication module identification is correct.
Verify the status of the engine in the Status field.
NOTE: Deployment is possible only if the state of the engine is indicated as either
RUN , STOP (recommended), or WAIT ( OFFLINE for Hot Standby controllers of the
Quantum platform).
Verify the information that is displayed in the Project Information section.
Select a backup file.
Click OK .
Result: The Reconfirm Deploy Data dialog box opens.
NOTE: Click Cancel to close the Confirm Deploy Data dialog box without deploying data.
Click OK .
Result:
• If the software detects conflicts in the data to be deployed, it opens the Deploy
Data Conflicts
dialog box, page 508 , which lets you proceed with the deployment
( Yes ) or cancel it ( No ).
• If you select to proceed, the software deploys the data and provides information about the deployment operation in the notification panel (or in a dialog box in case deployment did not succeed).
NOTE: Click Cancel to close the Reconfirm Deploy Data dialog box without deploying data.
Deploying Control Project Changes
Overview
Following a deployment, the Deploy Changes / Undo Online Changes command allows you to deploy to an engine changes that you have made to the logical Control Participant project that corresponds to the built Participant project that you had deployed to the same engine last.
It lets you also deploy
CCOTF-compatible changes, page 369
made to the configuration of a controller.
EIO0000001114.15
509
510
You can deploy changes pertaining to the following categories:
• Animation tables
• Operator screens
• Sections
• Types
• Variables
• Hardware
In addition, for
M580 safety Control projects, page 577 :
• Process (non-safe) program interfaces
• Safe program
• Safety password
To deploy other changes, refer to
Changes that Cannot be Deployed, page 514 .
When you select the Deploy changes / Undo Online Changes command, the software compares the deployed Participant project that is currently loaded in the engine with the corresponding built Participant project and identifies:
• Control project and configuration changes that you can deploy without stopping the engine.
• Control project
changes that require stopping the engine, page 519 . The
software displays a dialog box informing you that an engine stop is required in order to deploy such changes.
You can select, which of the identified changes you want to deploy.
The deployment of changes executes the CCOTF transaction and resets the counter.
The software gives you the option to proceed with a cold start of the engine following the deployment of changes that require stopping the engine.
NOTE:
• You can use the Deploy changes / Undo Online Changes command to discard changes that you made to the deployed Participant project.
• You need to
build the Control project, page 470
before you can deploy changes by using the Deploy changes / Undo Online Changes command.
• You cannot view the result of the deployment of changes before the deployment is actually completed.
Control Project Signature Verification
Before executing the command, the software compares the Control Participant project that is deployed in the engine with the
last deployed reference, page 482 ,
which is the Control Participant project residing in the software.
If they are identical, the command is executed. If they differ, the software starts a recovery process first. This process may take several minutes to complete.
In case the software displays a notification about a signature mismatch, the command cannot be executed. Contact EcoStruxure Process Expert
Undoing Online Changes
If you have changed the logic of the deployed Participant project by using the
Refine Online command, you can use Deploy changes / Undo Online Changes to undo these changes. This is possible only if the following conditions are satisfied:
• You have not changed the configuration online.
• You have not yet updated the Control project with these online changes.
EIO0000001114.15
.
The software identifies the changes you made online and displays them in the
Deploy Changes / Undo Online Changes dialog box. After executing the command, the deployed Control Participant project will be identical to the built
Participant project again.
NOTE: If you have changed and built the logical Control Participant project since the deployment, these changes will be applied to the deployed
Participant project as well unless you unselect them. It is not possible to unselect CCOTF-compatible hardware changes.
Deploying Changes to a Redundant Controller
For information that applies specifically to the deployment of changes to redundant controllers, refer to the topic describing
deployment to redundant controllers, page 494 .
Deployed Project Information
When you select the Deploy Changes / Undo Online Changes command, before you can select the changes that you want to deploy, the software displays the Confirm Deploy Changes / ...
dialog box, which contains information about:
• The engine that you are deploying changes to.
• The Control Participant project that is deployed to the engine.
EIO0000001114.15
511
The figure shows an example of the Confirm deploy changes / Undo Online
Changes dialog box for a redundant controller.
512
The table describes the information that is displayed in the Engine Information section of the Confirm deploy changes / Undo Online Changes dialog box.
Label
Role (1)
Status
IP Address
Description
Role of the engine: A or B .
If the software cannot communicate with the engine, the role is indicated as Not Detected .
Status of the engine that is selected for deployment.
If the status is Not Reachable you cannot proceed with the deployment. In such case, verify the IP address, the connection to the engine, and the status of the engine.
NOTE: If the status is Running , a notification is displayed in the dialog box to inform you that the engine will be stopped if you proceed with the deployment.
Identifier of the communication module through which the software will deploy the built
Participant project and its IP address that is configured in the Topology Explorer .
If the topological entity has several communication modules, you can select which one you want to deploy to.
NOTE: For controllers of the M580 platform, you cannot deploy changes to the
CPU module or a NOC communication module by using IP address A . You can only select
.
(1) Displayed only when you select the command for a redundant controller.
NOTE: To refresh the engine status and attempt to connect to it, click the reconnect
.
The table describes the information that is displayed in the Project Information section of the Confirm Deploy Changes / Undo Online Changes dialog box. It also describes the check box.
EIO0000001114.15
Name column
System
Selected Project column Last Deployed Project column 2
Project
Executable
Controller
Last Built On
Last Deployed
On
Last Online
Change
Performed On
Last Sync.
Performed On (1)
Identifier of the system that both the engine and the
Control project, which you have selected belong to.
Identifier of the Control Project that you have selected.
Identifier of the Control executable that you have selected and that contains the built Participant project to be deployed.
Identifier of the controller/station node to which you are deploying the built Participant project.
Date and time when you successfully built the Control
Participant project to be deployed.
Not applicable
Not applicable
(Primary→Standby) command.
Identifier of the system that both the engine and the
Control project, from which you have deployed the
Participant project last belong to.
Identifier of the Control Project associated to the deployed
Participant project that you have deployed last.
Identifier of the Control executable that contains the built
Participant project that you have deployed last.
Identifier of the controller/station node to which you have deployed the built Participant project last.
Date and time when you successfully built the Control
Participant project that you have deployed last.
Date and time when you last deployed the Participant project to the engine or you last completed the Deploy
Changes / Undo Online Changes command, independently if there were changes to be deployed or not.
Date and time when you last changed the deployed
Participant project by using the otherwise the field is empty.
Refine Online
Date and time when you last synchronized the standby controller with the primary one, using the command;
Synchronize
(1) Displayed only when you select the command for a redundant controller.
(2) When you deploy changes to a redundant controller, the dialog box shows separate columns for the primary and the standby engine.
Deploying Changes Other Than FBD Language
The table describes the effect of the Deploy changes / Undo Online Changes command on items other than FBD language.
Item
Non-
FBD sections
Animation tables
Operator screens
Hardware
Effect
Details of changes inside non-FBD sections that the software has identified are not shown. Only the name of sections that have been added, removed, or inside which the software has identified changes is displayed. Nevertheless, the changes are applied in the logical Control Participant project.
Details of changes to such items that the software has identified are not shown. Only the name of the animation table and/or operator screen is displayed.
The software displays any animation tables and/or operator screens that the built
Participant project contains, including modified and/or new ones. Animation tables and/ or operator screens that you have deleted from the Participant project are not shown.
You cannot select individual items but only the category for deployment.
When selected, animation tables and operator screens of the deployed Participant project are overwritten with the ones contained in the built Participant Project.
By default, both categories are not selected.
NOTE:
• Overwriting of an existing operator screen creates a copy of the screen in the deployed Participant project. Following deployment, use the Refine Online command to edit the categories and make their contents consistent with the logical Control Participant project.
• Animation tables and/or operator screens that you have removed from the logical Participant project are not removed from the deployed Participant project by using the command. Use the Refine Online command to delete them.
Details of CCOTF- compatible configuration changes are shown.
The Hardware category is selected by default (if changes are detected) and is readonly.
EIO0000001114.15
513
514
Considerations When Deploying Hardware Mapping Changes
Consider the information that is provided on the following pages when using the
Deploy changes / Undo Online Changes to deploy changes in the hardware mapping affecting:
•
•
Changes That Cannot Be Deployed
The software only identifies changes that pertain to a category displayed in the
Name column of the Deploy Changes / Undo Online Changes dialog box.
Changes that are not identified are not deployed. For more information, refer to
Changes that Cannot be Deployed, page 514 .
WARNING
UNINTENDED EQUIPMENT OPERATION
Perform Deploy Built Project operation to apply changes that are not identified in the Deploy Changes / Undo Online Changes dialog box.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
The table indicates the types of changes that are not identified by the software and the command that you need to use to apply them to the deployed Control
Participant project directly.
Type of change
Control project settings (refer to the Control Participant help, Operating Modes )
SR sections
Properties of MAST and FAST tasks
Timer and I/O event tasks
IODDT variables
Device DDT variables
Command to use
or
Changes to the
, which you make in the
Topology Explorer and that are not CCOTF-compatible.
Changes to the
communication mapping, page 424
.
Refer to the topic describing the deployment of changes related to device DDT variables, page 515
Deploy Built Project , page 496
Identifying Project and Hardware Changes
Before proceeding with the deployment, the software displays the Deploy
Changes / Undo Online Changes dialog box, which provides information about the differences that it has identified between the built Participant project and the deployed Participant project. It also allows you to select, which changes you want to deploy.
NOTE: When you select a section in order to deploy changes to this section in the deployed Control Participant project, the software overrides the online changes that you have made in this section after the deployment.
EIO0000001114.15
The following figure shows an example of the Deploy Changes / Undo Online
Changes dialog box that the software displays.
EIO0000001114.15
Header
Name
Impact on
Engine
Action
Type
DataType
Description of Change
Description
Identifier of the items that are changed.
Items that are selected are those that the software has identified as changed and that it will deploy.
Items are grouped by categories of the Control Participant program.
NOTE: A black square in a selection box indicates that at least 1 subitem is unselected.
Indicates if the deployment of the item
requires stopping the engine, page 519
.
• Green dot with an arrow: You can deploy the item online.
• Red dot with a square: The software needs to stop the engine to deploy the item.
• Minus icon: The item will be removed from the deployed Participant project.
(For example, because the item is removed from the built Participant project or it had been added to the deployed Participant project but not updated in the logical Participant project.)
• Plus icon: The item will be added to the deployed Participant project.
(for example, because the item is added to the built Participant project or it has been removed from the deployed Participant project during refine online and the change was not updated in the logical Participant project.)
• Pencil icon: The item will be modified in the deployed Participant project.
NOTE: When you select a section, the software deploys any changes that it has identified for this section. You cannot select/unselect changes individually inside a section.
Indicates the type of the item identified as a change.
Indicates the data type that is affected by the change, if applicable.
For FBD sections, variables, types, and hardware, indicates whether the change that the software has identified is an addition, a modification, or a deletion compared to the deployed Participant project.
NOTE: If the software does not detect a change that can be deployed, it displays a notification to inform you.
Deploying Changes Related to Device DDT Variable Creation,
Update, or Deletion
The following table describes which information the software displays if a
is present only in either the built or the deployed Control project.
515
516
DDDT variable in the deployed Control project
Mapped or unmapped
Not present
DDDT variable in the built Control project
Not present
Mapped or unmapped
Information shown in the Deploy
Changes / Undo Online Changes dialog box
No information.
Use the
or
Deploy Built Project , page 496
command to remove the variable in the deployed
Control project
The software detects the following as candidate for deployment:
• The device DDT variable
• Logic related to the variable
• Sections containing the logic
NOTE: The variable is unmapped in the deployed Control project.
The following table describes which information the software displays in a situation where:
• A device DDT variable with the same name exists in both the built and the deployed Control project but with a different data type or type version.
• The built Control project contains updated code using the device DDT variable.
DDDT variable in the deployed Control project
Mapped
Unmapped
DDDT variable in the built Control project
Mapped/unmapped
Unmapped
Information shown in the Deploy
Changes / Undo Online Changes dialog box
The device DDT variable is not shown as candidate for deployment. Modifications to the DDT variable type are not deployed.
Only the changes in code are shown as candidate for deployment.
NOTE:
• A notification is displayed in the
Details section of the dialog box.
• Deployment of changes may not succeed because not all changes are deployed.
The software detects the following as candidate for deployment:
• The device DDT variable
• Logic related to the variable
• Sections containing the logic
The following table describes which information the software displays in a situation where:
• A device DDT variable with the same name exists in both the built and the deployed Control project but with a different data type or type version.
• The device DDT variable is not used in the code of either Control project.
DDDT variable in the deployed Control project
Mapped
Unmapped
DDDT variable in the built Control project
Mapped/unmapped
Unmapped
Information shown in the Deploy
Changes / Undo Online Changes dialog box
The device DDT variable is not shown as candidate for deployment. modifications to the DDT variable type are not deployed.
NOTE: A notification is displayed in the
Details section of the dialog box.
The software detects the device DDT variable as candidate for deployment.
The following table describes which information the software displays in a situation where:
EIO0000001114.15
EIO0000001114.15
• A device DDT variable that exists in the deployed Control project has been deleted from the built Control project.
• The device DDT variable is either:
◦ Used in the code.
◦ Not used in the code.
DDDT variable in the deployed Control project
Mapped
DDDT variable in the built Control project
Variable is deleted and references to it in code are removed.
Information shown in the Deploy
Changes / Undo Online Changes dialog box
The device DDT variable is not shown as candidate for deployment (removal).
Only the changes in code are shown as candidate for deployment.
no information
Unmapped
Variable is deleted. It is not used in code.
Variable is deleted and references to it in code are removed.
Variable is deleted. It is not used in code.
The software detects the following as candidate for deployment:
• The device DDT variable (removal)
• Logic related to the variable
• Sections containing the logic
The software detects the device DDT variable as candidate for deployment
(removal).
Deploying Changes
WARNING
UNINTENDED EQUIPMENT OPERATION
Before deploying to a controller, verify that:
• You have assigned a valid IP address to the controller.
• The IP address corresponds to the physical address printed on the hardware.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: For more information, refer to
Identifying Engines, page 483 .
WARNING
UNINTENDED EQUIPMENT OPERATION
Before deploying to an engine, verify that you have selected the correct project files.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Unintended situations can occur if the operations that are in progress are not known when acting on a controller.
WARNING
UNKNOWN OPERATIONAL STATE OF EQUIPMENT
Before starting or stopping a controller, always positively confirm that there is no critical operation in progress.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
517
518
When you deploy changes to a redundant controller, although deployment to the primary controller succeeded, it is possible that
synchronization of the standby controller, page 563
does not complete. In such case, the software displays a message in the notification panel to inform you. If an interruption of the connection to the system server or an unexpected stop of the system server is the cause, the notification panel also contains additional information about steps that you must complete when the connection to the system server is re-established.
WARNING
UNINTENDED EQUIPMENT OPERATION
• Verify that deployment to the standby controller completed successfully.
• Do not operate the primary controller if deployment to the standby controller does not complete successfully.
• Synchronize the standby controller manually, using the Sync
(Primary→Standby) command and verify that the synchronization completed successfully.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: For information on the deployment of changes to redundant controllers, refer to the topic describing
deployment to redundant controllers, page 495 .
NOTE: For information on the Sync (Primary→Standby) command, refer to the
NOTE: Before deploying a CCOTF-compatible modification, refer to the topics describing the CCOTF functionality in the help of the Control Participant for your specific controller platform and follow the recommendations that they provide.
To deploy changes, proceed as follows.
Step
1
2
3
4
5
6
Action
Verify that the engine can
communicate with the PC, page 487
.
To deploy changes to a station node, verify that the simulator emulation software is
In the Topology Explorer , right-click the engine to which you want to deploy changes and select Deploy Changes /
Undo Online Changes .
Verify the information that is displayed.
Click OK .
NOTE: Click Cancel to close the
Confirm Deploy Changes / Undo
Online Changes dialog box without deploying.
Select the changes that you want to deploy.
Click OK .
NOTE: Click Cancel to close the
Deploy Changes / Undo Online
Changes dialog box without deploying changes. This reverts to the previous Deploy Changes /
Undo Online Changes dialog box.
Result
–
The software displays the Confirm Deploy
Changes / Undo Online Changes dialog box.
–
The software displays the Deploy Changes
/ Undo Online Changes dialog box.
–
The software displays the
/ Undo Online Changes dialog box.
Deploy Changes confirmation
EIO0000001114.15
Step
7
8
Action
If the deployment requires stopping the engine, in the Deploy Changes / Undo
Online Changes confirmation dialog box, select Start engine after deploying built project if you want the software to start the engine after the deployment of changes is complete.
Click OK or Deploy depending on the use case. (Only either button is displayed depending on the deployment use case, without or with engine stop.)
NOTE: Click Cancel to close the
Deploy Changes / Undo Online
Changes dialog box without deploying changes and revert to the selection of changes to deploy.
Result
–
The software:
• Stops the engine (if applicable).
• Deploys the changes that you have selected to the deployed Control
Participant project.
• Displays Completed in the notification panel once it has successfully completed the deployment of changes to the engine, which is identified by its
IP address.
◦ For a redundant controller, the notification panel displays separate messages for the primary and the standby engines by using their respective IP address to identify them. If deployment to either engine does not complete successfully, the software displays a corresponding message in the notification panel.
• Updates the related date/time field.
• Starts the controller (cold start) or software emulating a simulator if you selected the option (if applicable).
NOTE: In case the deployment of changes does not complete successfully, the software displays a notification to inform you. If the software stopped the engine before deploying Participant project changes, the engine remains in
Stopped state.
Changes Requiring to Stop the Controller
Summary of Changes
The table indicates if changes that you deploy by using the Deploy Changes /
Undo Online Changes command, or apply by using the
command require stopping the controller.
Type of change Requires stopping the controller
When deploying, using Deploy
Changes command
When applying, using the Refine
Online command
General
Modifying Control Expert project settings.
N/A Refer to Project Settings for a list of settings that you can change and to
Synthesis of Authorized and
Unauthorized Modifications in the help of the Control Participant.
Program: Task Sections, SR, SFC Action & Transition
Yes Modifying/replacing partially the code of an SFC section (SFC chart, transition, action).
Deleting SFC chart, transition, action.
Adding an SFC section.
Modifying or deleting an LL984 section.
Yes
No
Yes
Refer to Synthesis of Authorized and
Unauthorized Modifications in the help of the Control Participant.
EIO0000001114.15
519
Type of change Requires stopping the controller
Adding an LL984 section.
No
Modifying, deleting, or adding a section in either of the following languages:
• IL
• LD
• ST
No
Used Variables (used even in Animation Tables or Operator Screens)
Modifying the Retain or Exchange On
STBY attribute of a used variable.
Modifying the time stamp attribute of any used variable.
Yes
Yes
Yes
Refer also to Synthesis of Authorized and Unauthorized Modifications help of the Control Participant.
in the
Modifying the structure of a used DDT.
Yes
Used DFBs
Modifying the name of an input, output, or input/output pin (formal parameter) of a used DFB.
Yes Refer also to Synthesis of Authorized and Unauthorized Modifications in the help of the Control Participant.
Adding an input, output, or input/ output pin (formal parameter) to a used DFB.
Deleting an input, output, or input/ output pin (formal parameter) from a used DFB.
Yes
Yes
Supervision Project Deployment Stage
Overview
This section describes the methods that you can use to deploy built Supervision
Participant projects to computers (for example, operation servers, operator stations), which are connected to the Ethernet network. These computers are modeled by the corresponding station nodes in the topology of the system.
It also describes how to deploy only the changes that you have made following a first deployment.
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
Preparing for Deployment
Overview
The software lets you deploy a built Supervision Participant project and related files to the
that you have defined in the topology of the system and
to the executable that is associated to the
Supervision project.
You can deploy either way:
• In the Project Explorer : From the executable of the Supervision project. This deploys a selection of files to the station nodes that are mapped to the executable in the service mapping.
• In the Topology Explorer : From a station node that is mapped to the executable in the service mapping. This deploys a selection of files to this station node only.
520 EIO0000001114.15
The software detects roles of station nodes depending on the
that are configured in the Topology Explorer and considers a station node to be:
• An I/O server when configured with Supervision and OFS services.
• An alarm, trend, or report server, or a Supervision client when configured with the Supervision service only.
The software deploys to the computer that has an IP address matching the IP address of the station node configured in the Topology Explorer .
For information on the required Supervision software, refer to the topic describing software requirements (see EcoStruxure ™ Process Expert, Installation and
Configuration Guide).
Target Computer Setup
To prepare for the deployment, you need to:
• Verify that the configuration of the
in the topology of the system matches the configuration of the target computers (for example, verify that the station node containing the OFS service has the same IP address as the computer that runs the OPC Factory Server or OPC UA
Server Expert).
If a station node is configured with several NICs, each having an IP address:
◦ When deploying from the executable, the first IP address that is reachable from the system server computer is used.
◦ When deploying from the station node, you can select which IP address to use among those that are reachable from the system server computer.
• Create shared folders on each computer to which you deploy the Supervision project.
• Verify that the system server can access these shared folders; otherwise, the deployment cannot complete successfully.
For information on how to set up target computers, refer to the topic describing how to prepare for deployment (see EcoStruxure ™ Process Expert, Supervision
Participant Services, User Guide).
NOTE: When sharing a folder, restrict access by giving permissions only to the user who needs to access the folder. In this case, the user who is logged on to the system server computer.
Deploying the Built Supervision Participant Project from the Executable
Overview
By using the Deploy Built Project command, you can transfer selected files of the built Supervision Participant project to the operation server, and/or operator stations that are connected to the Ethernet network. The deployment is performed to the station nodes that you have mapped to the executable of the Supervision project in the service mapping and which represent these computers.
After a first deployment, you need to restore the deployed Supervision Participant project on each target computer.
Information related to subsequent deployments from the same executable is provided in the topic describing how to
deploy the built Supervision Participant project again, page 523 .
Deployed Files
You can deploy the following files:
• The Supervision master project file (.ctz), for example, Supervision_1_
Executable_1.ctz
), which includes the Supervision computer setup file ( citect.
ini ) (see EcoStruxure ™ Process Expert, Supervision Participant Services,
User Guide).
EIO0000001114.15
521
522
•
Attached user files, page 363 . These are located inside the master project (.
ctz) on the target computer.
• OFSOPC/OPC UA
configuration files (.xml), page 476 : Deployed only to
station nodes mapped to the IOServer service of the Supervision project. If there are several configuration files, each file is deployed to its respective station node only.
• The
You can select not to deploy the configuration file and/or the included project in the
Deployment File Selection
dialog box, page 526 , which is accessible during the
deployment process.
NOTE: Supervision project files that are deployed are already compiled by using the version of the Supervision Participant that is running inside the virtual machine. To verify the version, open a Supervision Participant (for example, by refining a Supervision Participant project), and open the About dialog box.
Deploying Out Of Date Participant Projects
You can deploy a Supervision Participant project whose status is Out Of Date .
Before deploying a built Supervision Participant project, verify its
. Only Supervision Participant projects whose status is Built contain the latest
changes that you have made, page 478
to the system.
Aborting Deployment Tasks
After confirming the command by clicking OK in the Deploy Built Project or
Deployment File Selection dialog box, the abort icon is displayed in the
. Click the icon to cancel the task.
Files that have already been transferred to station nodes at the moment you abort the task are not removed from the target locations. Open the shared folders on each station node to confirm which files have been transferred.
Only the user who has selected the command is allowed to abort it.
NOTE: If you are deploying only a small project, the task may complete before you are able to click the icon.
Deploying the Supervision Files
To deploy selected files pertaining to the built Supervision Participant project to the target computers from the executable, proceed as follows.
Step
1
2
Action
Verify that the target computers are
.
Right-click the executable that you want to deploy and select Deploy Built Project .
Result: The Deploy Built Project dialog box opens, which gives you the possibility to modify the selection of deployed files.
EIO0000001114.15
Step
3
4
Action
Click:
• Yes to open the Deployment File Selection
dialog box, page 526 ; proceed to
step 4 .
• No to deploy only the master Supervision project file (.ctz) but no OFSOPC/OPC
UA configuration file and no included projects.
• Cancel to cancel the deployment.
Result: If you clicked No , the software:
• Deploys the files to the appropriate folders on each target computer.
• Displays deployment information in the notification panel for each target computer, including the IP addresses that were used.
• Opens the Deploy Built Project dialog box, which contains a summary of the deployment process per target computer.
In the Deployment File Selection dialog box, select the files that you want to deploy and click OK .
Result: The software:
• Deploys the files to the appropriate folders on each target computer.
• Displays deployment information in the notification panel for each target computer, including the IP addresses that were used.
• Opens the Deploy Built Project dialog box, which contains a summary of the deployment process per target computer.
NOTE: Click Cancel to cancel the deployment.
Restoring the Supervision Project
After a first deployment, you need to restore the deployed Supervision Participant project on each target computer.
Restoring the project creates a Supervision project folder on the target computer that has the same name as the deployed Supervision master project file (.ctz).
For information on restoring the deployed Supervision project, refer to topic describing how to restore Supervision projects (see EcoStruxure ™ Process
Expert, Supervision Participant Services, User Guide).
Deploying the Built Supervision Participant Project Again
To perform a subsequent deployment of the complete Supervision project from the same executable after you have modified and built it, follow the procedure describing how to
deploy the project files, page 522
.
The software replaces the existing files in the SoCoDeploy , SoCoOfsDeploy , and/ or SoCoOpcUaDeploy shared folders (see EcoStruxure ™ Process Expert,
Supervision Participant Services, User Guide) on the target computers with the version that is contained in the Supervision project that you are deploying again.
Then, to apply the changes, the steps that you need to complete on each of the target computer vary, depending on the changes that you have deployed (for example, updating the OFSOPC/OPC UA configuration data manually). Refer to the topic describing how to execute the deployed Supervision project (see
EcoStruxure ™ Process Expert, Supervision Participant Services, User Guide).
NOTE: If you had already deployed
and you redeploy the same Supervision project after removing one or more of user files, these files remain in the SoCoDeploy shared folder where they had been deployed initially. You need to remove them manually from the shared folder.
Deploying the Built Supervision Participant Project from the Station Node
Overview
The Deploy Built Project command that is available from the station node provides an alternative deployment method. By selecting it, you can transfer selected files of the built Supervision Participant project to a specific computer
EIO0000001114.15
523
524
connected to the Ethernet network (for example, the operation server or an operator station). The deployment is performed from the station node that represents this computer. The station node needs to be mapped (
) to the executable of the Supervision project that you are deploying.
After a first deployment, you need to restore the deployed Supervision Participant project on the target computer.
Information related to subsequent deployments of the same Supervision project is provided in the topic describing how to
deploy the built Supervision Participant project again, page 523
.
Deployed Files
You can deploy the following files:
• The Supervision master project (.ctz file, for example, Supervision_1_
Executable_1.ctz
), which includes the Supervision cocomputer setup file
( citect.ini
) (see EcoStruxure ™ Process Expert, Supervision Participant
Services, User Guide).
•
Attached user files, page 363 . These are located inside the master project (.
ctz) on the target computer.
• The OFSOPC/OPC UA
configuration files (.xml), page 476
that are related to the station node: Deployed only to station nodes mapped to the IOServer service of the Supervision project.
• The
You can select not to deploy the configuration files and/or the included project in the Deployment File Selection
, which is accessible during the deployment process.
NOTE: Supervision project files that are deployed are already compiled by using the version of the Supervision Participant that is running inside the virtual machine. To verify the version, open a Supervision Participant (for example, by refining a Supervision Participant project), and open the About dialog box.
Selecting Participant Project and Control Executable
When you select the Deploy Built Project command for a station node, the software displays the Deploy Built Project dialog box, which allows you to select:
• Project : Any Supervision project that exists in the system whose executable is mapped to at least one
• Executable : For each project, any built or out of date Supervision executable that is mapped to the station node (service mapping).
Built Participant Project Build Status
The software informs you when the built Supervision Participant project that you want to deploy is marked as being out of date. Nevertheless, you can proceed with the deployment.
Before deploying a built Supervision Participant project, verify that its
is up to date and/or that it contains the latest
changes that you have made, page 478
to the system.
Supervision Participant Project Information
Before proceeding with the deployment of a built Participant project, the software displays information in the Confirm Deploy Built Project dialog box about:
• The station node that you are deploying to.
• The built Participant project to be deployed.
EIO0000001114.15
• The Participant project that was deployed last to the engine.
The following figure shows an example of the Confirm Deploy Built Project dialog box.
The tables describe the information that is displayed in the Confirm Deploy Built
Project dialog box.
Description Engine
Information section
Status
IP Address
Status of the station node that is selected for deployment.
If the status is Not Reachable , you cannot proceed with the deployment. In such case, verify the IP address and the connection to the station node.
NOTE: To refresh the engine status and attempt to connect to it, click the
Identifier of the NIC through which the software will deploy the built Participant project and its IP address that is configured in the Topology Explorer .
If the station node has several NICs, you can select which one you want to use for deployment.
Project
Information section
Executable
Selected Project column Last Deployed Project column
Station Node
System
Identifier of the Supervision executable that you have selected and that contains the built Participant project to be deployed.
Identifier of the topological entity to which you are deploying the built Participant project.
Identifier of the system that both the station node and the Supervision project, which you have selected belong to.
Identifier of the Supervision executable that contains the built Participant project that you have deployed last.
Identifier of the topological entity to which you have deployed the built Participant project last.
Identifier of the system that both the engine and the
Supervision project, from which you have deployed the
Participant project last belong to.
Project
Last Built On
Identifier of the Supervision Participant project that you have selected.
Date and time when you successfully built the
Supervision Participant project to be deployed.
Not applicable
Identifier of the Supervision Participant project associated to the executable that you have deployed last.
Date and time when you successfully built the Supervision
Participant project that you have deployed last.
Last Deployed
On
Select OFSOPC/
OPC UA configuration files and/or included projects
Date and time when you last deployed the Participant project from the station node or from the executable associated to the Supervision project.
Check box.
When selected, opens the Deployment File Selection dialog box, where you can select the OFSOPC/OPC UA configuration files and included projects to be deployed in addition to the Supervision master project file (.ctz).
When cleared, the dialog box does not open and only the Supervision master project file (.ctz) is deployed.
EIO0000001114.15
525
Check box
Select OFSOPC/OPC UA configuration files and/or included projects
Description
When selected, opens the Deployment File Selection dialog box, where you can select the OFSOPC/OPC
UA configuration files and included projects to be deployed in addition to the Supervision master project file
(.ctz).
When cleared, the dialog box does not open and only the Supervision master project file (.ctz) is deployed.
NOTE: When you deploy for the first time to a station node, the fields of the
Last Deployed Project section are empty.
Selecting the Files to Deploy
The following figure shows an example of the Deployment File Selection dialog box, which opens when you select the Select OFSOPC/OPC UA configuration files and/or included projects check box and click OK in the Confirm Deploy
Built Project dialog box.
526
1 Supervision master project file (.ctz), which is selected by default. You cannot clear the check box.
2 OFSOPC or OPC UA
that are related to the station node and generated depending on the selected protocol for the tag container.
Configuration files can be selected only for station nodes that are mapped to an I/
O server.
3
that are associated to the master project.
Aborting Deployment Tasks
After confirming the command by clicking OK in the Reconfirm Deploy Built
Project dialog box, the abort icon is displayed in the
.
Click the icon to cancel the task.
Files that have already been transferred to the station node at the moment you abort the task are not removed from the target locations. Open the shared folders on the station node to confirm which files have been transferred.
Only the user who has selected the command is allowed to abort it.
NOTE: If you are deploying only a small project, the task may complete before you are able to click the icon.
Deploying the Supervision Files
To deploy selected files pertaining to the built Supervision Participant project from a station node, proceed as follows.
EIO0000001114.15
EIO0000001114.15
7
8
9
Step
1
4
5
2
3
6
10
11
12
Action
In the Topology Explorer , identify the station node that represents the computer you want to deploy to.
Verify that the target computer is
.
Right-click the station node and click Supervision
>
Deploy Build Project .
Result: The Deploy Built Project dialog box opens.
Click the Project list and select the Supervision project.
Click the Executable list and select the executable associated to the built Supervision project that you want to deploy.
Click OK .
Result: The Confirm Deploy Built Project dialog box opens.
NOTE: Click Cancel to close the dialog box without deploying.
Verify the status of the engine in the Status field.
Verify the NIC identification and IP address or select one in the IP Address field.
Verify the information that is displayed in the Project Information section of the
Confirm Deploy Built Project dialog box.
To modify the selection of files to deploy, select the Select OFS configuration files and/or included projects
and click OK ; otherwise, to exclude configuration files and included projects from the deployed files, clear the check box, click OK , and proceed to step 12 .
Result: The Deployment File Selection dialog box opens.
In the Deployment File Selection dialog box, select the files you want to deploy to the station node and click OK .
Result: The Reconfirm Deploy Built Project dialog box opens.
NOTE: Click Cancel to cancel your file selection and revert to the Confirm Deploy
Built Project dialog box.
Click OK in the Reconfirm Deploy Built Project dialog box.
Result: The software:
• Deploys the selected files to the appropriate folders on the target computer.
• Displays Completed in the notification panel and provides deployment information.
• Updates the related date/time field.
NOTE: Click Cancel to revert to the Confirm Deploy Built Project dialog box.
Restoring the Supervision Project
After a first deployment, you need to restore the deployed Supervision Participant project on the target computer.
Restoring the project creates a Supervision project folder on the target computer that has the same name as the deployed Supervision master project file (.ctz).
For information on restoring the deployed Supervision project, refer to topic describing how to restore Supervision projects (see EcoStruxure ™
Expert, Supervision Participant Services, User Guide).
Process
Deploying the Built Supervision Participant Project Again
To perform a subsequent deployment of the complete Supervision project after you have modified and built it, follow the procedure describing how to
deploy the project files, page 526 .
The software replaces the existing files in the SoCoDeploy and SoCoOfsDeploy shared folders (see EcoStruxure ™ Process Expert, Supervision Participant
Services, User Guide) on the target computer with the version that is contained in the Supervision project that you are deploying again.
527
Then, to apply the changes, the steps that you need to complete on the target computer vary, depending on the changes that you have deployed (for example, updating the OFSOPC/OPC UA configuration data manually). Refer to the topic describing how to execute the deployed Supervision project (see EcoStruxure ™
Process Expert, Supervision Participant Services, User Guide).
NOTE: If you had already deployed
and you redeploy the same Supervision project after removing one or more of user files, these files remain in the SoCoDeploy shared folder where they had been deployed initially. You need to remove them manually from the shared folder.
Deploying Supervision Participant Project Changes
Overview
By using the Deploy Changes command, you can deploy the changes that you have made to an already deployed Supervision Participant project given these changes are supported by the command.
You can deploy changes either from the executable or the station node independently from the method that you have used to perform the previous deployment.
You can select to deploy only the Supervision master project file (.ctz) or also additional files.
Prerequisites
The following conditions must be satisfied to be able to deploy changes by using the Deploy Changes command.
• You must have deployed the complete Supervision Participant project to the station node and restored it by using the Supervision software.
• The Supervision project folder (see EcoStruxure ™ Process Expert,
Supervision Participant Services, User Guide) that was created by restoring the deployed Supervision Participant project must be present on the target computer.
• The changes that can be deployed incrementally are only those that can be applied by using the Build command:
◦ A maximum of 5 changes involving Supervision pages.
◦ A maximum of 30 changes involving data facets.
◦ Modifications of parameters of the Message category of Supervision elements
Refer to the topic describing the build stage for
.
NOTE: Using the Build All command disables the Deploy Changes command.
Deployed Files
The files that you can deploy are the same as for the deployment of the
Supervision Participant project, page 524 .
You can change the selection during the deployment process in the Deployment
File Selection
.
Aborting Deployment Tasks
After confirming the command by clicking OK in the Reconfirm Deploy Changes dialog box, the abort icon is displayed in the
notification panel, page 54 . Click the
icon to cancel the task.
528 EIO0000001114.15
EIO0000001114.15
Files that have already been transferred to station nodes at the moment you abort the task are not removed from the target locations. Open the shared folders on each station node to confirm which files have been transferred.
Only the user who has selected the command is allowed to abort it.
NOTE: If you are deploying only few changes, the task may complete before you are able to click the icon.
Deploying Changes from the Executable
To deploy changes to the Supervision Participant project to the target computers from the executable, proceed as follows.
Step
1
2
3
4
5
Action
Verify that the target computers are
In the Project Explorer , expand the Supervision project that you want to deploy from and open the Executables folder to show existing executables.
Right-click the executable that you want to deploy and select Deploy Changes .
Result: The Deploy Changes dialog box opens, which gives you the possibility to modify the selection of files.
Click:
• Yes to open the Deployment File Selection
dialog box, page 526 ; proceed to
step 5 .
• No to deploy only the master Supervision project file (.ctz) but no OFSOPC/OPC
UA configuration file and no included project.
• Cancel to cancel the deployment.
Result: If you clicked No , the software:
• Deploys the master Supervision project file to the appropriate folders on each target computer.
• Displays deployment information in the notification panel for each target computer, including the IP addresses that were used.
• Opens the Deploy Changes dialog box, which contains a summary of the deployment process per target computer.
In the Deployment File Selection dialog box, select the files that you want to deploy and click OK .
Result: The software:
• Deploys the files to the appropriate folders on each target computer.
• Displays deployment information in the notification panel for each target computer, including the IP addresses that were used.
• Opens the Deploy Changes dialog box, which contains a summary of the deployment process per target computer.
NOTE: Click Cancel to the deployment.
Deploying Changes from the Station Node
To deploy changes to the Supervision Participant project from a station node, proceed as follows.
Step
1
4
5
2
3
Action
In the Topology Explorer , identify the station node that represents the computer you want to deploy to.
Verify that the target computer is
.
Right-click the station node and click Supervision
>
Deploy Changes .
Result: The Confirm Deploy Changes dialog box opens. The information of the last deployed executable and project is indicated in the Executable and Project fields of the
Project Information section.
Verify the status of the engine in the Status field.
Verify the NIC identification and IP address or select one in the IP Address field.
529
Step
6
7
8
Action
If you want to deploy other files in addition to the master Supervision project, select the
Select OFSOPC/OPC UA configuration files and/or included projects
and click OK ; otherwise, to exclude configuration files and included projects from the deployed files, clear the check box, click OK , and proceed to step 8
Result: The Deployment File Selection dialog box opens.
NOTE: Click Cancel to close the dialog box without deploying.
In the Deployment File Selection dialog box, select the files you want to deploy to the station node and click OK .
Result: The Reconfirm Deploy Changes dialog box opens.
NOTE: Click Cancel to cancel your file selection and revert to the Confirm Deploy
Changes dialog box.
Click OK in the Reconfirm Deploy Changes dialog box.
Result: The software:
• Deploys the selected files to the appropriate folders on the target computer.
• Displays Completed in the notification panel and provides deployment information.
• Updates the related date/time field.
NOTE: Click Cancel to revert to the Confirm Deploy Changes dialog box.
530 EIO0000001114.15
Execution Stage
What’s in This Chapter
Supervision Project Execution Stage ............................................................ 576
Overview
This chapter describes how to execute and/or modify the Control and Supervision projects that you have deployed to engines of the system.
The following figure shows the position of the Execution stage within the system engineering life cycle.
Refer to the
for a description of the purpose of this stage.
Control Project Execution Stage
Overview
This section describes how to use the Topology Explorer to change the state of controllers, modify deployed Control Participant projects, and how to transfer changes to the associated logical Participant project in the software.
NOTE: When one or more users work on components of the same system simultaneously (for example, Participant projects, the application, project containers, topological entities), locking mechanisms may restrict certain
concurrent actions, page 52 . In such case, check the
for details.
Control Participant Project Execution Process
Overview
The software allows you to execute a deployed Control Participant project, make changes to the deployed Participant project online, and update the logical Control
Participant source project with these changes.
For this purpose, following the deployment of a built Control Participant project, the following commands become available:
EIO0000001114.15
531
• Start
• Stop
• Refine Online
• Sync (Primary→Standby)
• Update Project
The commands are available for the following engines to which you have deployed a Control Participant project:
• Controllers.
• Station nodes running software emulating a simulator.
Execution Flowchart
The following figure illustrates the different steps that are part of the execution of the deployed Control Participant project and their associated commands.
532
- - - Represents commands pertaining to the
(1) Includes the
section import functionality, page 558
.
(2) The functionality is a sub-command of the Refine Online command within the
Control Participant.
(3) Or emulated simulator (station node).
Prerequisites
The table describes the actions that are prerequisite for using a command.
Command
Start / Stop
Refine Online
Actions
Deploy the built Control Participant project.
Deploy the built Control Participant project.
EIO0000001114.15
EIO0000001114.15
Command
Sync (Primary→
Standby)
Update Project
Actions
• Deploy the built Control Participant project. Either of the following use cases may apply:
◦ Deployment to, or synchronization of the standby engine did not complete successfully following execution of the Deploy , Re-
Deploy , Deploy Changes , or Refine Online command.
◦ Deployment was done to the primary engine only because the
ControllerExist parameter is set to Primary . You need to set the parameter to PrimaryAndStandby , verify that the standby engine is reachable, and that both engines are connected by a Hot
Standby cable link.
• Verify that the status of the primary engine is Running Primary .
• Deploy the built Control Participant project.
• Change the deployed Control Participant project by using the Refine
Online command.
NOTE: Certain changes
cannot be transferred, page 514
to the logical Control Participant project by using the command.
For the other actions that are required, for example, mapping of the Control executable to an engine, refer to the system engineering life cycle that is described in this manual.
Control Project Mismatch Verification
Before executing the Start / Stop , Sync (Primary→Standby) , or Refine Online command, the software compares the Control Participant project that is deployed in the engine with the
last deployed reference, page 532 , which is the Control
Participant project residing in the software.
If they are identical, the command is executed. If they differ, the software starts a recovery process first. This process may take several minutes to complete.
In case the software displays a notification about a signature mismatch, the command cannot be executed. Contact EcoStruxure Process Expert support.
Client/Server Connection
In case of an unexpected stop of the system server, the notification panel of engineering clients that were connected to the system server before the communication interruption may contain information about operations that did not complete successfully because of this interruption. It may also indicate corrective actions.
After an interruption of the client/server connection, the states of both the engineering client and the system server may have become inconsistent if an execution operation was in progress.
NOTICE
DATA CORRUPTION
After an interruption of the client/server connection, verify that the last operation executed by the software was completed successfully, and if necessary, repeat the last operation.
Failure to follow these instructions can result in equipment damage.
NOTE: For more information on client and server behavior in case of a communication interruption, refer to the topic describing
client/server connection, page 47
.
Start/Stop Commands
The software can send a start or stop command to the controller or software emulating a simulator.
533
Unintended situations can occur if the operations that are in progress are not known when acting on a controller.
WARNING
UNKNOWN OPERATIONAL STATE OF EQUIPMENT
Before starting or stopping a controller, always positively confirm that there is no critical operation in progress.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Execution With Redundant Controllers
Overview
This topic describes aspects that are specific to the execution of Control
Participant projects with redundant controllers, which are modeled in the topology of the system.
The same commands that are used on standalone configurations are also used for redundant controllers.
Detailed information on the commands that are available as part of the execution stage are described later in this chapter.
For a description of the sequence of actions that Control performs on the engines, refer to the topic describing
main redundant controller scenarios, page 561 .
NOTE: For controllers of the M580 platform, you cannot perform execution tasks on the CPU module or a NOC communication module by using IP address A and IP address B . You can only select
.
ControllerExist Property
Verify that the ControllerExist parameter is
Engine Status for Redundant Controllers
Refer to the information that is provided in the topic describing deployment to
redundant controllers, page 495 .
Starting/Stopping a Redundant Controller
For redundant controllers, the Start / Stop commands act on the primary and the standby engines, provided that both are reachable.
When you select the Start or Stop command for a
redundant controller, page 563 ,
composed of one primary and one standby engine to which IP addresses IP , and
IP + 1 are assigned respectively, the software displays the Confirm <Command> dialog box (where <Command> represents either Start or Stop ), which provides information on both engines.
NOTE: When you select the Start command and the status of the standby engine is Stop Offline (or Stop for controllers of the M580 platform), the primary engine starts and synchronizes the standby engine so that both engines start.
Redundant Controller Stop Sequence
When you stop the redundant controller and both engines are running, the software stops in the following order:
• The standby engine
534 EIO0000001114.15
EIO0000001114.15
• The primary engine
Refining Online with a Redundant Controller
To proceed with the deployment, the primary engine must be in either Running
Primary or Stop Offline (or Stop for controllers of the M580 platform) state.
The software executes the command on the project that is deployed on the primary engine.
When you deploy online changes that do not require stopping the engine, and the primary engine is in Running Primary state:
• The software enables the configuration mismatch feature of the controller so that the standby engine does not enter the offline operating mode when changes are deployed to the primary engine.
• The software deploys to the primary engine first, and upon successful completion of the deployment, automatically synchronizes the standby engine.
• Then, the software disables the configuration mismatch feature.
When you deploy changes to a redundant controller, although deployment to the primary controller succeeded, it is possible that
synchronization of the standby controller, page 563
does not complete. In such case, the software displays a message in the notification panel to inform you. If an interruption of the connection to the system server or an unexpected stop of the system server is the cause, the notification panel also contains additional information about steps that you must complete when the connection to the system server is re-established. This is the case, for example, when the software cannot disable the configuration mismatch feature. If this feature is enabled and a switchover occurs, the standby controller operates with a program that does not contain the changes that you have deployed to the primary controller.
WARNING
UNINTENDED EQUIPMENT OPERATION
• Verify that deployment to the standby controller completed successfully.
• Do not operate the primary controller if deployment to the standby controller does not complete successfully.
• Synchronize the standby controller manually, using the Sync
(Primary→Standby) command and verify that the synchronization completed successfully.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: If the primary engine is not in Running Primary state, synchronization of the standby engine cannot complete successfully. In such case,
the primary engine synchronizes the standby engine.
Redundant Controller Synchronization Timeout
After you select the Build and Deploy command (see EcoStruxure ™ Process
Expert, Control Participant Services, User Guide), upon successful deployment to the primary engine, the deployed Control Participant project is stored in the contents repository as the
last deployed reference, page 532 .
It avoids
and allows you to synchronize the standby controller, using the Sync (Primary→Standby) command in case the
synchronization timeout is elapsed, page 541 .
535
Starting and Stopping Controllers
Overview
Following the deployment of a built Control Participant project to an engine, you can change the state of the engine by using the following commands:
• Start
• Stop
The commands act on the physical controller or on the software emulating a simulator that is installed on the computer represented by the engine in the topology of the system. The IP address of the controller or of the computer on the
Ethernet network needs to match with the address that is assigned to the corresponding engine.
Confirming Execution
When you select the Start or Stop command for a controller or station node, before proceeding with the execution of the command, the software displays the
Confirm <Command> dialog box (where <Command> represents either Start or
Stop ), which contains information about:
• The engine that you want to start or stop.
• The Control Participant project that is deployed to the engine.
The following figure shows an example of the Confirm Stop dialog box that the software displays when you select the Stop command for a controller that is running.
536 EIO0000001114.15
The following figure shows an example of the Confirm Stop dialog box that the software displays when you select the Stop command for a redundant controller that is running.
The following figure shows an example of the Confirm Start dialog box that the software displays when you select the start command for a controller that is stopped.
EIO0000001114.15
537
The following figure shows an example of the Confirm Start dialog box that the software displays when you select the start command for a redundant controller that is running. The command cannot be executed because the engine is already running.
538
The table describes the information that is displayed in the Engine Information section of the Confirm Start and Confirm Stop dialog boxes.
Label
Role (1)
Status
Description
Role of the engine: A or B .
If the software cannot communicate with the engine, the role is indicated as
Not Detected .
Status of the engine that is selected for execution.
If the status is Not Reachable you cannot proceed with the command. In such case, verify the IP address, the connection to the engine, and the status of the engine.
IP Address Identifier of the communication module through which the software sends the command and its IP address that is configured in the Topology
Explorer .
If the topological entity has several communication modules, you can select through which one you want to start or stop.
NOTE: For controllers of the M580 platform, you cannot start or stop an engine by using IP address A of the CPU module or a NOC communication module. You can only select
.
(1) Displayed only when you select the command for a redundant controller.
NOTE: To refresh the engine status and attempt to connect to it, click the reconnect
.
The table describes the information that is displayed in the Project Information section of the Confirm Start and Confirm Stop dialog boxes.
Name column
System
Project
Executable
Controller
Last Deployed
On
Last Deployed Project column (2)
Identifier of the system that both the engine and the Control project, from which you have deployed the Participant project last belong to.
Identifier of the Control Participant project associated to the deployed
Participant project that you have deployed last.
Identifier of the Control executable that contains the built Participant project that you have deployed last.
Identifier of the topological entity to which you have deployed the built
Participant project last.
Date and time when you last deployed the Participant project to the engine or you last completed the Deploy Changes / Undo Online Changes command, independently if there were changes to be deployed or not.
EIO0000001114.15
EIO0000001114.15
Name column Last Deployed Project column (2)
Date and time when you last started or stopped the engine.
Last Start/Stop
Performed On
Last Online
Change
Performed On
Last Sync.
Performed On (1)
Date and time when you last changed the deployed Participant project by using the Refine Online command; otherwise the field is empty.
Date and time when you last synchronized the standby engine with the primary engine by using the Synchronize (Primary→Standby) command; otherwise the field is empty.
(1) Displayed only when you select the command for a redundant controller.
(2) When you start or stop a redundant controller, the dialog box shows separate columns for the primary and the standby engine.
NOTE: If the software detects that the engine is already running or stopped, it displays information in the dialog box and you cannot execute the command.
Starting an Engine
WARNING
UNINTENDED EQUIPMENT OPERATION
Before starting or stopping a controller, verify that:
• You have assigned a valid IP address to the controller.
• The IP address corresponds to the physical address printed on the hardware.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: For more information, refer to
Identifying Engines, page 483 .
Unintended situations can occur if the operations that are in progress are not known when acting on a controller.
WARNING
UNKNOWN OPERATIONAL STATE OF EQUIPMENT
Before starting or stopping a controller, always positively confirm that there is no critical operation in progress.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
When starting a redundant controller, synchronization of the standby controller may not complete successfully. In such case, the software displays a message in the notification panel to inform you.
WARNING
UNINTENDED EQUIPMENT OPERATION
• Verify that deployment to the standby controller completed successfully.
• Do not operate the primary controller if deployment to the standby controller does not complete successfully.
• Synchronize the standby controller manually, using the Sync
(Primary→Standby) command and verify that the synchronization completed successfully.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
539
540
NOTE: For information on the Sync (Primary→Standby) command, refer to the topic describing
synchronization of redundant controllers, page 541 .
To start the engine, proceed as follows.
Step Action
1 Verify that the engine is
2
3
4
In the Topology Explorer , right-click the engine and select Start .
Verify the information that is displayed.
Click OK .
NOTE: Click Cancel to close the
Confirm Start dialog box without starting the engine.
5
Result
–
The software displays the dialog box.
–
The software displays the dialog box.
Confirm Start
Reconfirm Start
Click OK .
NOTE: Click Cancel to close the
Reconfirm Start dialog box without starting the engine. This reverts to the
Confirm Start dialog box.
The software:
• Starts the engine.
• Displays Completed in the notification panel once it has successfully completed the command for the engine, which is identified by its IP address.
◦ For a redundant controller, the information pane displays separate messages for the primary and the standby engines by using their respective IP address to identify them.
• Updates the Last Start/Stop
Performed On field.
Stopping an Engine
WARNING
UNINTENDED EQUIPMENT OPERATION
Before starting or stopping a controller, verify that:
• You have assigned a valid IP address to the controller.
• The IP address corresponds to the physical address printed on the hardware.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: For more information, refer to
Identifying Engines, page 483 .
Unintended situations can occur if the operations that are in progress are not known when acting on a controller.
WARNING
UNKNOWN OPERATIONAL STATE OF EQUIPMENT
Before starting or stopping a controller, always positively confirm that there is no critical operation in progress.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
To stop the engine, proceed as follows.
EIO0000001114.15
Step Action
1 Verify that the engine is
2 In the Topology Explorer , right-click the engine that you want to stop and select
Stop .
Verify the information that is displayed.
3
4
5
Click OK .
NOTE: Click Cancel to close the
Confirm Stop dialog box without stopping the engine.
Click OK .
NOTE: Click Cancel to close the
Reconfirm Stop dialog box without stopping the engine. This reverts to the Confirm Stop dialog box.
Result
–
The software displays the Confirm Stop dialog box.
–
The software displays the Reconfirm Stop dialog box.
The software:
• Stops the engine to stop the execution of the deployed Control participant project.
• Displays Completed in the notification panel once it has successfully completed the command for the engine, which is identified by its IP address.
◦ For a redundant controller, the information pane displays separate messages for the primary and the standby engines by using their respective IP address to identify them.
• Updates the Last Start/Stop Performed
On field.
Synchronizing Redundant Controllers
Overview
The Sync (Primary→Standby) command allows you to manually transfer the deployed Control Participant project from the primary engine to the secondary redundant engine in case of an application program, configuration, or data mismatch.
Manual synchronization is only possible when the primary engine is running. The state of the standby engine does not matter.
The software verifies if the application program or configuration of the primary and the secondary redundant engines are identical and proceeds with the transfer only if it detects a difference.
It also verifies that there is no
The command is available only for entities of the topology that are configured as redundant controllers.
Refer also to
Redundant Controller Deployment and Execution Scenarios, page
Hot Standby Cable Link
If the Hot Standby cable link between the controllers is broken, synchronization does not complete successfully, and the software displays a message to inform you of the detected error.
Synchronization Timeout
During synchronization of the standby engine, the software compares the signatures of both the primary and the standby engines. When they are identical, it considers that the synchronization completed successfully.
After 3 min, if the comparison does not detect identical signatures, the software displays a dialog box to inform you that synchronization did not complete
EIO0000001114.15
541
successfully and cancels the comparison process. However, the synchronization itself is not canceled and may still complete after the timeout.
You can retry synchronizing by using the Sync (Primary→Standby) command.
Confirming the Synchronization
Before proceeding with the execution of the command, the software displays the
Confirm Sync (Primary→Standby) dialog box, which contains information about:
• The current state of the primary and standby engines.
• The deployed Control Participant project to transfer to the standby controller.
The following figure shows an example of the Confirm Sync (Primary→Standby) dialog box that the software displays when you select the Sync
(Primary→Standby) command with the primary controller in Running Primary state.
542
The table describes the information that is displayed in the Engine Information section of the Confirm Sync (Primary→Standby) dialog box.
Label
Role
Status
IP Address
Description
Role of the engine: A or B .
If the software cannot communicate with the engine, the role is indicated as Not Detected .
Status of the engine that is selected for synchronization.
If the status is Not Reachable you cannot proceed with the command. In such case, verify the IP address, the connection to the engine, and the status of the engine.
Identifier of the communication module through which the software sends the command and its IP address that is configured in the Topology
Explorer .
If the topological entity has several communication modules, you can select through which one you want to synchronize.
NOTE: For controllers of the M580 platform, you cannot synchronize an engine by using IP address A of the CPU module or a NOC communication module. You can only select
NOTE: To refresh the engine status and attempt to connect to it, click the reconnect
.
The table describes the information that is displayed in the Project Information section of the Confirm Sync (Primary→Standby) dialog box.
EIO0000001114.15
Name column
System
Project
Executable
Controller
Last Deployed
On
Last Deployed Project To Primary Engine / Standby Engines columns
Identifier of the system that both the engine and the Control project, from which you have deployed the Participant project last belong to.
Identifier of the Control Participant project associated to the deployed
Participant project that you have deployed last.
Identifier of the Control executable that contains the built Participant project that you have deployed last.
Identifier of the topological entity to which you have deployed the built
Participant project last.
Date and time when you last deployed the Participant project to the engine or you last completed the Deploy Changes / Undo Online Changes command, independently if there were changes to be deployed or not.
Date and time when you last started or stopped the engine.
Last Start/Stop
Performed On
Last Online
Change
Performed On
Last Sync.
Performed On
Date and time when you last changed the deployed Participant project by using the Refine Online command; otherwise the field is empty.
Date and time when you last synchronized the standby engine with the primary engine by using the Synchronize (Primary→Standby) command; otherwise the field is empty.
NOTE: If the software detects that the engine is stopped, it displays the
Confirm Sync (Primary→Standby) dialog box to inform you that the synchronization cannot be completed.
Synchronizing the Standby Controller
WARNING
UNINTENDED EQUIPMENT OPERATION
Before starting or stopping a controller, verify that:
• You have assigned a valid IP address to the controller.
• The IP address corresponds to the physical address printed on the hardware.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: For more information, refer to
Identifying Engines, page 483 .
Unintended situations can occur if the operations that are in progress are not known when acting on a controller.
WARNING
UNKNOWN OPERATIONAL STATE OF EQUIPMENT
Before starting or stopping a controller, always positively confirm that there is no critical operation in progress.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Synchronization of the standby controller, page 563
may not complete, for example, if the primary or the standby engine is reserved. In such case, the software displays a message in the notification panel to inform you.
EIO0000001114.15
543
WARNING
UNINTENDED EQUIPMENT OPERATION
• Verify that deployment to the standby controller completed successfully.
• Do not operate the primary controller if deployment to the standby controller does not complete successfully.
• Synchronize the standby controller manually, using the Sync
(Primary→Standby) command and verify that the synchronization completed successfully.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
To synchronize the standby engine with the primary engine, proceed as follows.
Step
1
2
5
6
3
4
7
Action
Verify that the primary engine is
and its status is
Running Primary .
In the Topology Explorer , right-click the redundant controller that you want to synchronize and select Sync (Primary→Standby) .
Result: The software displays the Confirm Sync (Primary→Standby) dialog box.
Verify the information that is displayed.
Click OK .
NOTE: Click Cancel to close the Confirm Sync (Primary→Standby) dialog box without synchronizing.
The software displays the Reconfirm Sync (Primary→Standby) dialog box.
Click OK .
NOTE: Click Cancel to close the Reconfirm Sync (Primary→Standby) dialog box without synchronizing. This reverts to the Confirm Sync (Primary→Standby) dialog box .
Result: If the software detects no difference in the application program or configuration between the primary and the standby engines, it does not proceed with the transfer, and displays the Sync Operation Result dialog box to inform you of the result.
Otherwise, the software:
• Transfers the deployed Control Participant project from the primary engine to the standby engine.
• Displays Completed in the notification panel once it has successfully completed the command for the engines, which are identified by their respective IP address.
• Updates the related date/time field.
About Changes Made Online
Overview
This topic provides an overview of the workflow of the system engineering life cycle with a focus on changes that you make during online refinement.
After refining the deployed project online, the logical and the deployed Control
Participant projects are different.
If you refine (offline) the logical Control Participant project later on and deploy these changes, the operation may undo your online refinements. You have the possibility to preserve online refinements by transferring them to the logical
Control Participant project. However, some online refinements cannot be transferred or can be transferred only partially.
The table indicates which workflow chart provides the information depending on your objective.
544 EIO0000001114.15
Objective
Making online refinements persistent in the logical Control Participant project and controller configuration by updating the project.
Preserving online refinements that cannot be transferred to the logical Control
Participant project
Updating the logical Control Participant project with references to DDDT variables coming from the topology.
Refer to
Workflow 1
Workflow 2
Workflow 3
NOTE: For details on using the various commands that allow you to
,
, and
update the logical Control project, page 567
, refer to the corresponding topics in the deployment and execution sections.
Workflow 1
The figure illustrates the typical workflow to make online refinements persistent by transferring them to the logical Control Participant project.
EIO0000001114.15
NOTE: Not updating the logical Control Participant project allows you to undo online refinements by deploying changes. The software detects the online refinements as change compared to the logical Control project. However, using the Deploy Changes command to
is not possible if you have made changes to the configuration online.
545
546
This allows you later on to deploy additional changes to the sections that you had modified during refinement online while preserving online refinements. These changes can come from the topology, and/or the application, and/or from refinements of the logical Control Participant project.
Workflow 2
When you make refinements online that you cannot or do not want to transfer to the Control Participant project, you can make these refinements in a new, separate section (section_2 in this example). You can unselect this section when deploying changes later on.
EIO0000001114.15
Making refinements online in a separate section (section_2 in this example) allows you to preserve them when you deploy changes (to topology, application, or in refinement (offline)) by unselecting the section that contains the online refinements (section_2).
EIO0000001114.15
Workflow 3
After you update the logical Control project with the following online refinements, the Control Participant reports a detected error during
because the DDDT variable does not exist in the logical Control project:
• You add a variable that references a DDDT variable, which
exists only in the topology, page 371 .
• You add an instance of an existing DFB type, which references a DDDT variable, which exists only in the topology.
The solution is:
• When you add a variable that references a DDDT variable:
◦ Do not use the variable in code that is generated by assigned facets or modified during refinement (offline) so that a subsequent deployment of changes does not undo online refinement.
◦ Use the variable in a
, which you can unselect during deployment of changes.
• When you add an instance of an existing DFB type, which references a DDDT variable, build the Control project. This integrates variables coming from the topology into the built Control Participant project.
In this example, variable MyVar1 is created during refinement online. It references the MOD_ANA_8_1 DDDT variable of a HART analog input module, which comes from the topology. You cannot transfer MyVar1 nor the MOD_ANA_8_1 DDDT variable to the logical Control project.
547
In this example, the My_DINPUT DFB instance is created during refinement online from the DINPUT DFB type, which exists in the logical Control project.
My_
DINPUT references the MOD_ANA_8_1 DDDT variable of a HART analog input module, which comes from the topology. You can transfer the My_DINPUT DFB instance to the logical Control project but the reference to the DDDT variable is broken.
The figure shows how online refinements that reference DDDT variables coming from the topology affect the deployment and execution workflow.
NOTE: You can create the DDDT variable in the logical Control project by using the
Making Changes Online
Overview
The Refine Online command opens the deployed Control Participant project in the Control Participant, allowing you to change the project when the engine is running or stopped.
You may be able to
of the logical Control Participant project that have been modified and generated since their last deployment.
Online refinement requires using the Build and Deploy subcommand, which is described in Refining the Deployed Control Participant Project Online (see
EcoStruxure ™ Process Expert, Control Participant Services, User Guide).
548 EIO0000001114.15
EIO0000001114.15
When you close the Control Participant after deploying changes online, the software lets you update the associated logical Control Participant project right away with the changes you have made online. Until you do so, an
online refinement indicator, page 365
is displayed in the corresponding topological entity folder. It indicates that the logical and the deployed Control Participant projects are different.
NOTE: To be applied, certain changes that you make online require
stopping the controller, page 519
.
Refining Online with a Station Node
When you select the Refine Online command for a station node, the software may display a notification asking you to
the built Control
Participant project to the station node if the previously deployed project is not loaded anymore into the simulation software that is installed on this station node.
Preserving Changes Made Online
After selecting the Refine Online command, if deployment of the following online changes does not complete successfully, then these changes are not discarded:
• Deployment of changes that do not require stopping the engine.
• Deployment of changes that require stopping the engine.
In such case, select the Refine Online command again and continue your work.
NOTE: If the deployment of online changes requires disconnecting the engine, the changes are discarded.
Updating the Project with Changes Made Online
Once you have successfully deployed changes made online and close the Control
Participant, the software prompts you to update the associated logical Control
Participant project and the controller configuration with these changes. You are not prompted in case you have made changes that require stopping the controller.
If you accept, the software opens the Update Project
here on, you follow the same process as when you select the Update Project command. The same restrictions apply.
If you do not accept, the
online refinement icon, page 366
is displayed in the topological entity folder. It indicates that changes made online need to be applied to the associated logical Control Participant project and/or the controller configuration to make it consistent with the one that is deployed to the engine. The icon is displayed independently of the type of change that you make.
The icon is displayed and the software prompts you to perform the update until you complete the update process.
Refer to the topic describing how to
update logical Control Participant projects, page 567 .
NOTE: If you have changed the configuration online, you must perform the update to be able to use the Deploy changes / Undo Online Changes command.
NOTE: The icon is also displayed if you accept to perform the update but cancel the operation, if you update the project only partially, or if the update does not complete successfully.
Making Changes Online in Separate FBD Sections
When possible, it is good practice to make changes online in separate FBD sections that you create during online refinement. This is because you cannot transfer to the logical Control Participant project certain changes. It also applies
549
550
when you do not update the logical Control Participant project after making changes online.
It helps you preserve changes that you have made online when you
after building the logical Control Participant project.
Viewing the Application Structure When Making Changes
Online
When you modify a Control Participant project online, the Application Browser displays FBD sections based on the location of instances whose Control facets are assigned to these sections.
It shows the relationship between the folder structure of the application and the sections of the Control Participant project. This is useful, for example, when you want to modify the logic related to a specific area or subdivision of the application.
You can open sections from the pane.
The pane only shows FBD and non-FBD sections of the Control Participant project that are deployed at the moment you select the Refine Online command.
For a general description of the contents of the pane, refer to the topic describing the
application structure view, page 287
.
For information on how to use the pane, refer to the topic describing the refinement of Control Participant projects online (see EcoStruxure ™ Process
Expert, Control Participant Services, User Guide).
For general information on how to work with panes, refer to the topic describing the
engineering client workspace, page 85 .
Confirming the Command
When you select the Refine Online command, before you can proceed with the online editing, the software displays the Confirm Refine Online dialog box, which contains information about:
• The engine whose program you want to refine online.
• The Control Participant project that is deployed to the engine.
EIO0000001114.15
The figure shows an example of the Confirm Refine Online dialog box for a redundant controller.
EIO0000001114.15
The table describes the information that is displayed in the Engine Information section of the Confirm Refine Online dialog box.
Label
Role (1)
Status
Description
Role of the engine: A or B .
If the software cannot communicate with the engine, the role is indicated as Not Detected .
Status of the engine that is selected for online refinement.
If the status is Not Reachable or Stop Offline (2) you cannot proceed with the command. In such case, verify the IP address, the connection to the engine, or the status of the engine.
IP Address Identifier of the communication module through which the software sends the command and its IP address that is configured in the
Topology Explorer .
If the engine has several communication modules, you can select one.
NOTE: For controllers of the M580 platform, you cannot connect to an engine by using IP address A of the CPU module or a NOC communication module. You can only select
.
(1) Displayed only when you select the command for a redundant controller.
(2) Stop for controllers of the M580 platform.
NOTE: To refresh the engine status and attempt to connect to it, click the reconnect
.
The table describes the information that is displayed in the Project Information section of the Confirm Refine Online dialog box.
Name column
System
Project
Executable
Controller
Last Deployed
On
Last Online
Change
Performed On
Last Deployed Project column (2)
Identifier of the system that both the engine and the Control project, from which you have deployed the Participant project last belong to.
Identifier of the Control Participant project associated to the deployed
Participant project that you have deployed last.
Identifier of the Control executable that contains the built Participant project that you have deployed last.
Identifier of the topological entity to which you have deployed the built
Participant project last.
Date and time when you last deployed the Participant project to the engine or you last completed the Deploy Changes / Undo Online Changes command, independently if there were changes to be deployed or not.
Date and time when you last changed the deployed Participant project by using the Refine Online command; otherwise the field is empty.
551
552
Name column
Last Sync.
Performed On (1)
Last Deployed Project column (2)
Date and time when you last synchronized the standby engine with the primary engine by using the Synchronize (Primary→Standby) command; otherwise the field is empty.
(1) Displayed only when you select the command for a redundant controller.
(2) When you select the command for a redundant controller, the dialog box shows separate columns for the primary and the standby engines.
Making Changes Online
WARNING
UNINTENDED EQUIPMENT OPERATION
Before deploying to an engine, verify that you have selected the correct project files.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
WARNING
UNINTENDED EQUIPMENT OPERATION
Before starting or stopping a controller, verify that:
• You have assigned a valid IP address to the controller.
• The IP address corresponds to the physical address printed on the hardware.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: For more information, refer to
Identifying Engines, page 483 .
Unintended situations can occur if the operations that are in progress are not known when acting on a controller.
WARNING
UNKNOWN OPERATIONAL STATE OF EQUIPMENT
Before starting or stopping a controller, always positively confirm that there is no critical operation in progress.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
When you deploy changes to a redundant controller, although deployment to the primary controller succeeded, it is possible that
synchronization of the standby controller, page 563
does not complete. In such case, the software displays a message in the notification panel to inform you.
EIO0000001114.15
EIO0000001114.15
WARNING
UNINTENDED EQUIPMENT OPERATION
• Verify that deployment to the standby controller completed successfully.
• Do not operate the primary controller if deployment to the standby controller does not complete successfully.
• Synchronize the standby controller manually, using the Sync
(Primary→Standby) command and verify that the synchronization completed successfully.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
When you make changes by online refinement, the associated logical and built
Control Participant projects do not contain these changes. To preserve these changes during a next deployment, you need to integrate them into the built
Control Participant project first by
changes are discarded.
WARNING
LOSS OF DATA
After building and deploying changes made during online refinement, update the associated logical Control Participant project.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
To edit the deployed Control Participant project online, proceed as follows.
Step Action
1 Verify that the engine is
and that it is running or stopped.
2 In the Topology Explorer , right-click the engine and select Refine Online .
3
4
5
6
7
Result
–
Verify the information that is displayed.
Click OK .
NOTE: Click Cancel to close the Confirm
Refine Online dialog box without editing the
Participant project.
The software displays the Confirm
Refine Online dialog box.
–
The software displays the
Refine Online dialog box.
Reconfirm
Click OK .
NOTE: Click Cancel to close the Reconfirm
Refine Online dialog box without editing the
Participant project. This reverts to the
Confirm Refine Online dialog box.
The Control Participant opens
and maximized.
Proceed with changes or import of sections in the deployed Control project inside the Control
Participant UI (see EcoStruxure ™ Process Expert,
Control Participant Services, User Guide).
Close the Control Participant window.
–
The software displays the Refine
Online dialog box prompting you to update the associated logical Control
Participant project with the changes you have made online if applying these changes did not require stopping the controller.
NOTE: Not updating the associated logical Control
Participant project may result in losing online refinement changes during next deployments.
553
Step Action
8 Click Yes .
NOTE: Click No to close the Refine Online dialog box without updating the logical
Control Participant project and display an
online refinement indicator, page 365
in the associated topological entity folder.
9 Follow the procedure to
Participant projects, page 567
and controller configurations.
Result
The software opens the Update
Project dialog box, which allows you to view and select changes made online that you can transfer to the associated logical Control Participant project and controller configuration.
–
NOTE: If you close the Control Participant window without making changes online, the software may still display the Refine Online online dialog box, which prompts you to update the associated Control project. This is the case if you had made changes online previously, which you have not yet applied to the associated logical Control Participant project. The online refinement icon is also displayed in the associated topological entity folder to indicates this.
Backing Up Controller Data
Overview
The Back Up Data command lets you back up and save to file (.DTX) the following controller data:
• Located data of boolean type ( %M ).
• Located data of WORD type ( %MW ).
• Unlocated variables.
• Unlocated function block instances (DFB and EFB).
The functionality is available once you have deployed a built Control Participant project to a controller or station node of the system.
Data backup files:
• Are associated to information such as a time stamp, which lets you select the correct file to
and
• Retain your backup settings making it easy to reuse the same settings for subsequent backup operations on the same deployed executable.
• Can be
exported and imported, page 206
with the Control Participant project.
NOTE: For more information, refer to Save/Restore Data Between a File and the PLC in the help of the Control
Backing Up Data with Redundant Controllers
For redundant controllers, back up of data is possible only from the primary controller.
To be able to back up data from the primary controller, the standby controller must be reachable at the IP address that is configured. It may not be reachable, for example, because it is switched off or the Hot Standby cable is removed.
Only if the ControllerExist
is set to Primary you can back up data from the primary controller while the standby controller is not reachable.
NOTE: The status of the standby controller is not shown in the Confirm Back
Up Data dialog box.
Backup File Identification
When the software creates a backup file, it associates the following information to the file:
• A date/time stamp.
554 EIO0000001114.15
• A description entered by the user.
• The name of the user who is logged on to the client.
• Identifiers of the controller, the Control Participant project, and the executable.
• The type of data that is backed up.
This information is shown for existing backup files when you select the Deploy
Data command.
NOTE:
• When you delete a Control Participant project or a controller, its data backup files are deleted as well.
• If you change the identifier of a controller or executable, or the role of a controller, the identification information of the corresponding backup file is not modified.
Controller and Controller Data Information
Before proceeding with the backup of controller data, the software displays information in the Confirm Back Up Data dialog box about:
• The executable whose data you want to back up.
• The associated Control Participant project.
• The engine to which the executable is deployed.
This dialog box lets you also select the data that you want to back up.
The following figure shows an example of the Confirm Back Up Data dialog box for a standalone controller.
EIO0000001114.15
555
The following figure shows an example of the Confirm Back Up Data dialog box for a redundant controller.
556
The table describes the information that is displayed in the Engine Information section of the Confirm Back Up Data dialog box.
Label
Controller (1)
Description
You can perform the backup only from the primary controller.
Role (1)
Status
IP Address
Default value: Primary
Role of the selected controller: A or B .
If the software cannot communicate with the engine, the role is indicated as Not Detected .
Status of the engine that is selected for backup.
If the status is Not Reachable , you cannot proceed with the deployment. In such case, verify the IP address, the connection to the engine, and the status of the engine.
NOTE: If the status is Running , a notification is displayed in the dialog box to inform you about a possible desynchronization of the backed up data.
Identifier of the communication module through which the software will back up data and its IP address that is configured in the
Topology Explorer .
If the topological entity has several communication modules, you can select which one you want to use.
Default value: IP address that was selected for the last deployment operation to this engine.
NOTE: For controllers of the M580 platform, you cannot back up data from the CPU module or through a NOC communication module by using IP address A . You can only select
(1) Displayed only when you back up data from a redundant controller.
NOTE: To refresh the engine status and attempt to connect to it, click the reconnect
.
The table describes the information that is displayed in the Project Information section of the Confirm Back Up Data dialog box.
EIO0000001114.15
EIO0000001114.15
Label
Control
Project
Description
Identifier of the Control Participant project associated to the executable that you have deployed last.
Executable Identifier of the Control executable that contains the built Participant project that you have deployed last.
Description You need to enter a description for the backup file by using free form text to be able to proceed with the backup.
The table describes the information that is displayed in the Controller Data section of the Confirm Back Up Data dialog box.
Section
Located
Data
Unlocated
Data
Description
Select the check boxes depending on the type of located variables that you want to back up to file:
• %M : When selected, backs up located boolean variables. You need to provide the memory range to be backed up.
Default range: 0 to maximum configured memory size -1.
• %MW : When selected, backs up located variables of WORD data type. You need to provide the memory range to be backed up.
Default range: 0 to maximum configured memory size -1.
NOTE: The maximum configured memory size depends on the memory configuration of located data of the CPU module of the controller to which the Control project is deployed.
Selecting/clearing the Located Data check box also selects/clears the other check boxes in this section.
Default value for first data backup for an executable: True (selected). If you have already performed a data backup operation for the same executable, your last settings are retained. The settings are reset when you restore a system or import the topology.
Select the check boxes depending on the type of located variables that you want to back up to file:
• Variable instances : When selected, backs up unlocated variable instances.
• Function block instances (DFB and EFB) : When selected, backs up unlocated function block instances.
Selecting/clearing the Unlocated Data check box also selects/clears the other check boxes in this section.
Default value for first data backup for an executable: True (selected). If you have already performed a data backup operation for the same executable, your last settings are retained. The settings are reset when you restore a system or import the topology.
Control Project Signature Verification
Before executing the command, the software compares the Control Participant project that is deployed in the engine with the
last deployed reference, page 482 ,
which is the Control Participant project residing in the software.
If they are identical, the command is executed. If they differ, the software starts a recovery process first. This process may take several minutes to complete.
In case the software displays a notification about a signature mismatch, the command cannot be executed. Contact Schneider Electric
.
Backing Up Controller Data
Unintended situations can occur if the operations that are in progress are not known when acting on a controller.
Backing up data when the controller is in RUN state may take several scan cycles and the backed up data may be desynchronized. This adversely affects program execution when the backed up data is deployed to the controller.
557
WARNING
UNINTENDED EQUIPMENT OPERATION
Before backing up data from the controller, verify that the controller state does not jeopardize data integrity when the data is backed up.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: Schneider Electric recommends backing up data while the controller is in STOP state.
To back up the controller data, proceed as follows.
5
6
7
8
Step
1
2
3
4
9
Action
Verify that the engine can
communicate with the PC, page 487
.
In the Topology Explorer , right-click the entity whose data you want to back up and select the Back Up Data command.
Result: The software opens the Confirm Back Up Data dialog box.
In the IP Address field, verify that the communication module identification is correct.
Verify the status of the engine in the Status field.
NOTE: Backup is possible only if the status of the engine is indicated as either
RUN , STOP (recommended), or WAIT ( OFFLINE for Hot Standby controllers of the
Quantum platform).
Verify the information that is displayed in the Project Information section.
Enter a description for the backup file.
Configure the data that you want to back up in the Controller Data section.
Click OK .
Result: The Reconfirm Back Up Data dialog box opens.
NOTE: Click Cancel to close the Confirm Back Up Data dialog box without backing up data.
Click OK .
Result:
• The software backs up the selected controller data and creates the corresponding backup file.
• It provides information about the backup operation in the notification panel (or in a dialog box in case the operation did not succeed).
NOTE: Click Cancel to close the Reconfirm Back Up Data dialog box without backing up data.
Importing Sections from the Logical Control Participant Project
Overview
It is possible to import FBD sections directly from the logical Control Participant project to help speed up the implementation of changes during commissioning.
This is achieved by skipping the build and deployment stages of the system engineering life cycle.
The import functionality allows you to import into the deployed Control project,
FBD sections of the corresponding logical Control Participant project, which you have modified since they were deployed last. The modifications need to be
to be imported.
The time stamp of the
last generation of a section, page 262
is used as reference.
Changes made to a section by using the Refine command can be imported only if you have generated the section afterwards.
558 EIO0000001114.15
Refining a section by using the Refine command after generating it disables the possibility to import it.
Variables and types that are not used anymore after an import are not removed.
NOTE: If the section that you import has the same name as a section in the deployed Control project, it replaces the existing section. As a result, changes you had made in the section are overwritten.
Section Import Functionality in the System Engineering Life
Cycle
In the following figure, the dotted line shows the scope of the section import functionality in the context of the system engineering life cycle. Modifications that you make after generating a section and that pertain to the refinement, mapping, and build stages cannot be imported.
Section Import Window
The figure shows an example of the section import window, which opens when you click the section import button in the toolbar of the Control Participant window during online refinement.
EIO0000001114.15
2
3
Item
1
Description
Check box to select or clear all the sections displayed in the import window. A black square inside the check box indicates that at least one section is not selected.
Check box to select or clear sections individually.
Identifier of sections of the corresponding logical Control project, which have been modified and generated since the build Control project was last deployed to the engine. A section appears only if the
by the section
559
560
Item
Description import functionality. Sections are listed in ascending Order ( Containers pane of the
Assignment Editor ).
Value of the Generated On property of the section.
for the Section column.
4
5
Attributes Related to HAL and Network Variables
When you import a section that contains a variable generated by a HAL template
(for example, a signal conditioning template) or peer to peer communication templates (for example, $DOUTBool_UL and $DINBool_UL , which generate a variable with P2P as custom attribute), and the section and variable already exist in the deployed Control project, the Address and Value attributes of the variable are not modified by the import operation.
Online Refinement Indicator
When you import a section, build, and deploy the change, the
online refinement icon, page 366
is displayed and you are prompted to update the associated logical Control project. However, if you have not made any other change apart from importing the section, the logical Control project is already up-to-date.
Accepting to update the logical Control project displays a message informing you that no changes are detected.
Changes to Sections That Can Be Imported During Online
Refinement
The table indicates whether a section can be imported during online refinement depending on the change that you have made. It is assumed that the section is generated after making the change (if required to apply the change).
Change description
Assigning a facet to the section.
Unassigning a facet from the section.
Allows importing the section
Yes
Yes
Actions resulting in a change of the status of a facet.
Yes
Comment
–
–
Except unlinking and relinking a facet.
– Regenerating the section (independently if changes were made in the section before regenerating).
Renaming the section.
Yes
Yes
Changing the order of sections.
Creating a new section without assigning facets.
Renaming a variable (for example, by changing the identifier of the instance referencing the facet that creates the variable). The variable and section already exist in the deployed Control project.
Creating a section and making a change by using the Refine command (for example, adding a function block). Then, making a change in the section that can be imported (for example, assigning a facet).
Making a change in a section that can be imported
(for example, assigning a facet) while a section with the same name already exists in the deployed
Control project.
Yes
Yes
Yes
Yes
Yes
The renamed section is imported as a new section.
The section with the original name that existed remains.
–
–
The renamed variable is created as a new variable.
The variable with the original name that existed remains.
The section is imported and also contains the change you had made through refinement.
The section in the deployed
Control project is replaced by the imported section.
EIO0000001114.15
Change description
Changing the order of facets inside the section.
Deleting a section to which facets are assigned and that is generated.
Allows importing the section
No
No
Comment
–
You cannot remove a section from the deployed Control project by using the section import functionality.
– Making a change in the section that can be imported
(for example, assigning a facet), then making a change in the section by using the Refine command
(for example, adding a function block or modifying a variable used in this section).
Making changes in a section that can be imported and deploying these changes by using the Deploy
Changes / Undo Online Changes command.
No
No
1. Deploying a section.
2. In the Project Explorer making a change in the section that can be imported (for example, assigning additional facets).
3. Making a change in this section in the deployed Control project by using the Refine
Online command and applying it by clicking the button to build and deploy (for example, removing a DFB).
No
The changes are already applied to the deployed
Control Participant project.
If you have made changes that can be imported in more than one section but have not selected all these sections during deployment of changes, the sections that you have not selected appear as candidates for import.
You have deployed a change to a section that you want to import after generating this section.
Importing Sections from the Logical Control Participant Project
Refer to the topic describing how to refine the deployed Control project online (see
EcoStruxure ™ Process Expert, Control Participant Services, User Guide).
Main Redundant Controller Scenarios
Overview
This topic outlines the sequence of actions performed by the software when executing commands of the context menu of a redundant controller entity, which is composed of one primary and one standby engine. IP addresses IP and IP + 1 are assigned respectively to each engine.
Other scenarios are described in the topic documenting
redundant Controller reservation and connection scenarios, page 563 .
Deployment and Re-Deployment Sequence of Actions
Various deployment and re-deployment scenarios are considered depending on the status of the engines of the redundant controller before and after successful deployment.
Deployment is considered to require stopping engines.
Scenario 1: Both engines are stopped. No start after deployment.
1
2
Actions
Deployment to IP + 1 .
Deployment to IP .
EIO0000001114.15
561
562
Scenario 2: Both engines are stopped. Engines are started after deployment.
1
2
3
4
Actions
Deployment to IP .
Start of IP .
Synchronization of IP + 1 .
A successful synchronization starts IP + 1 .
Scenario 3: Both engines are running. No start after deployment.
3
4
1
2
Actions
Stop of IP + 1 .
Deployment to IP + 1 .
Stop of IP .
Deployment to IP .
3
4
5
1
2
6
Scenario 4: Both engines are running. Engines are started after deployment.
Actions
Stop of IP + 1 .
Stop of IP .
Deployment to IP .
Start of IP .
Synchronization of IP + 1 .
A successful synchronization starts IP + 1 .
Deployment of Changes and Online Refinement Sequence of
Actions
Various scenarios for deploy changes and refine online are considered depending on:
• The status of the redundant controller before and after successful deployment.
• The need to stop the controller.
• The need to disconnect the engine.
• The status of the redundant controller after successful deployment.
Scenario 5: IP is stopped. Disconnection required. No start after deployment.
1
2
3
Actions
Disconnection of IP .
Project is rebuilt.
Deployment as per deployment scenarios 1 or 2.
Scenario 6: IP is stopped. Disconnection not required. Engines started after deployment.
1
Actions
Deployment as per deployment scenario 2.
Scenario 7: IP is stopped. Disconnection not required. No start after deployment.
EIO0000001114.15
1
Actions
Changes are built in IP .
Scenario 8: IP is stopped. Disconnection not required. No start after deployment.
1
2
Actions
Changes are built in IP .
Deployment to IP + 1 .
Scenario 9: IP is running. Engine stop not required. Disconnection not required.
1
2
Actions
Changes are built in IP .
Synchronization of IP + 1 .
Scenario 10: IP is running. Engine stop required. Disconnection not required.
Engines started after deployment
1
Actions
Deployment as per deployment scenario 4.
Scenario 11: IP is running. Disconnection not required. Engine stop required. No start after deployment
1
2
3
Actions
Stop of IP + 1 .
Stop of IP .
Changes are built in IP .
Scenario 12: IP is running. Disconnection required. Engine stop not required. No start after deployment.
1
2
3
Actions
Disconnection of IP .
Project is rebuilt.
Deployment as per deployment scenarios 3 or 4.
Redundant Controller Reservation and Connection Scenarios
Overview
This topic describes the actions that the software performs on the primary and standby engines for each deployment and execution command, depending on:
• The reservation state of the engine.
• The status of the connection to the engine.
• The status of the engine.
It is considered that the redundant controller is composed of a primary and a standby engine to which IP addresses IP and IP + 1 are assigned respectively.
EIO0000001114.15
563
564
For the Deploy Built Project and Re-Deploy Last Project
Commands
The table describes the actions that the software performs on the primary and standby engines when you select the Deploy Built Project and Re-Deploy Last
Project commands.
Engine
Externally
Reserved
Controller IP
Connected
(Controller
State)
Controller
IP + 1
Connected
(Controller
State)
Action Executed by the software on
Engine
Comment
Primary Standby primary standby standby none none none none true true (stopped) true true (running) true false true (running) false true (stopped) false true indifferent indifferent true no action deployment no action no action no action no action deployment no action deployment to both
Primary engine is reserved.
Standby engine is reserved.
Standby engine is reserved and cannot be stopped.
Unable to connect to controller IP .
Unable to connect to controller IP + 1 .
Unable to connect to controller IP + 1 .
If the engines need to be stopped for the deployment, the software stops the primary engine even if the standby engine is already stopped, given that:
• none of the engines is reserved
• the connection status for both engines is true
For the Deploy Changes/Undo Online Changes Command
The table describes the actions that the software performs on the primary and standby engines when you select the Deploy Changes/Undo Online Changes command.
Engine
Externally
Reserved
Controller IP
Connected
(Controller
State)
Controller
IP + 1
Connected
(Controller
State)
Action Executed by the software on
Engine
Comment
Primary Standby primary none standby true false true indifferent indifferent indifferent no action no action no action
Primary engine is reserved.
Unable to connect to controller IP .
Standby engine is reserved.
EIO0000001114.15
EIO0000001114.15
Engine
Externally
Reserved none
Controller
Connected
(Controller
State)
IP Controller
IP + 1
Connected
(Controller
State) true (stopped) indifferent none true (running) true
Action Executed by the software on
Engine
Comment deployment of changes no action
No synchronization of standby controller because primary controller is stopped.
deployment of changes If the engines need to be stopped for the deployment of changes, the software stops the primary engine even if the standby engine is already stopped, given that:
• none of the engines is reserved
• the connection status for both engines is true
For the Start Command Only
The table describes the actions that the software performs on the primary and standby engines when you select the Start command.
Engine
Externally
Reserved
Controller IP
Connected
(Controller
State)
Controller
IP + 1
Connected
(Controller
State)
Action Executed by the software on
Engine
Comment
Primary Standby primary primary true (running) indifferent true (stopped) indifferent no action no action
Primary engine is already running.
Primary engine is reserved.
Refer to
For the Start and Stop Command, page 566
for additional scenarios.
For the Stop Command Only
The table describes the actions that the software performs on the primary and standby engines when you select the Stop command.
Engine
Externally
Reserved
Controller IP
Connected
(Controller
State)
Controller
IP + 1
Connected
(Controller
State)
Action Executed by the software on
Engine
Comment
Primary Standby primary primary true (stopped) indifferent true (running) indifferent no action no action
Primary engine is already stopped.
Primary engine is reserved.
none standby true (running) true (running) true
(stopped) true
(running)
Stop no action no action
Standby engine is reserved and cannot be stopped.
Stopping primary engine causes switchover.
565
566
Engine
Externally
Reserved none
Controller IP
Connected
(Controller
State) true (running)
Controller
IP + 1
Connected
(Controller
State) false
Action Executed by the software on
Engine no action none true (running) true
(running) stop
Comment
Unable to connect to controller IP + 1 .
The software stops in the following order:
• the standby engine
• the primary engine
Refer to
For the Start and Stop Command, page 566
for additional scenarios.
For the Start and Stop Commands
The table describes the actions that the software performs on the primary and standby engines when you select the Start or Stop command.
Engine
Externally
Reserved
Controller IP
Connected
(Controller
State)
Controller
IP + 1
Connected
(Controller
State)
Action Executed by the software on
Engine
Comment
Primary Standby standby none none true false true true indifferent false no action no action no action
Standby engine is reserved.
Unable to connect to controller IP .
Unable to connect to controller IP + 1 .
For the Refine Online Command
The table describes the actions that the software performs on the primary and standby engines when you select the Refine Online command.
Engine
Externally
Reserved
Controller IP
Connected
(Controller
State)
Controller
IP + 1
Connected
(Controller
State)
Action Executed by the software on
Engine
Comment
Primary Standby primary standby true not required
Standby-
Later (1)
Standby-
Later (2) true true indifferent true indifferent indifferent no action no action no action no action or deployment no action primary engine is reserved.
standby engine is reserved.
standby engine is reserved.
No synchronization of standby because reserved.
Changes may have been deployed to primary engine.
EIO0000001114.15
(1)
(2)
Engine
Externally
Reserved none
Controller IP
Connected
(Controller
State) false
Controller
IP + 1
Connected
(Controller
State) indifferent
Action Executed by the software on
Engine no action none true true deployment of project changes
Comment
Unable to connect to controller IP .
If the engines need to be stopped for the deployment of online changes, the software stops the primary engine even if the standby engine is already stopped, given that:
• none of the engines is reserved
• the connection status for both engines is true
The engine is reserved after the software opens the Control Participant window in the Topology Explorer .
The engine is reserved after the software executes the
subcommand.
For the Sync (Primary→Standby) Command
The table describes the actions that the software performs on the primary and standby engines when you select the Sync (Primary→Standby) command.
Engine
Externally
Reserved
Controller IP
Connected
(Controller
State)
Controller
IP + 1
Connected
(Controller
State)
Action Executed by the software on Engine
Comment primary standby none none true true false true indifferent true indifferent false
Primary no action no action no action no action
Standby synchronize standby primary engine is reserved.
standby engine is reserved.
Unable to connect to controller IP .
–
Updating the Logical Control Participant Project and Controller Configuration
Overview
The Update Project command allows you to apply to the logical Control
Participant project and the controller configuration
changes that you have made online, page 544 . You must have made the changes by using the
command.
An indication that online changes need to be applied is given by an
online refinement icon, page 366
that is displayed in the associated topological entity folder.
You can apply changes pertaining to the following categories:
• Animation tables
• Operator screens
• Sections
EIO0000001114.15
567
568
• Types
• Variables
• Hardware
Applicable restrictions are described in this topic.
In addition, for
M580 safety Control projects, page 577 :
• Process (non-safe) program interfaces
• Safe program
When you select the Update Project command, the software compares the deployed Participant project that is currently loaded in the engine with the corresponding logical Participant project and controller configuration and identifies differences.
The software allows you to select, which of the identified changes you want to apply.
You can request the software to perform a consistency check before updating the logical Participant project.
If you changed the logical Participant project since the deployment, using the
Update Project command may override some of these changes.
NOTE: You need to
build the Participant project, page 464
to which you have applied changes by using the Update Project command to be able to deploy these changes.
Confirming the Command
When you select the Update Project command, before you can proceed with the selection of changes, the software displays the Confirm Update Project dialog box, which contains information about:
• The engine from which you are updating the Control Participant project.
• The Control Participant project that is deployed to the engine.
EIO0000001114.15
The following figure shows an example of the Confirm Update Project dialog box for a redundant controller.
EIO0000001114.15
The table describes the information that is displayed in the Engine Information section of the Confirm Update Project dialog box.
Label
Role (1)
Status
Description
Role of the engine: A or B .
If the software cannot communicate with the engine, the role is indicated as
Not Detected .
Status of the engine that is selected to update the Control Participant project from.
IP Address
If the status is Not Reachable you cannot proceed with the command. In such case, verify the IP address, the connection to the engine, and the status of the engine.
Identifier of the communication module through which the software sends the command and its IP address that is configured in the Topology Explorer .
If the engine has several communication modules, you can select one.
(1) Displayed only when you select the command for a redundant controller.
NOTE: To refresh the engine status and attempt to connect to it, click the reconnect
.
The table describes the information that is displayed in the Project Information section of the Confirm Update Project dialog box.
Name column
System
Project
Executable
Controller
Selected Project column
Identifier of the system that both the engine and the Control project belong to.
Identifier of the Control Participant project associated to the deployed
Participant project.
Identifier of the Control executable that contains the built Participant project.
Identifier of the topological entity from which you are updating the logical
Control Participant project.
Last Deployed On Date and time when you last deployed the Participant project to the engine or you last completed the Deploy Changes / Undo Online Changes command, independently if there were changes to be deployed or not.
Last Online
Change
Performed On
Date and time when you last changed the deployed Participant project by using the Refine Online command; otherwise the field is empty.
569
570
Name column Selected Project column
Last Control
Project Modified
On
Last Sync.
Performed On (1)
Date and time when you last modified the logical Control Participant project by using the Generate or Refine command.
Date and time when you last synchronized the standby engine with the primary engine by using the Synchronize (Primary→Standby) command; otherwise the field is empty.
(1) Displayed only when you select the command for a redundant controller.
NOTE: The Confirm Update Project dialog box is not displayed if you choose to update the logical Control Participant project when prompted after completing a
refine online operation, page 549 .
Updating with Changes Other Than FBD Language
The table describes the effect of the Update Project command on items other than FBD language.
Item
Non-
FBD sections
Animation tables
Operator screens
Hardware
Effect
Details of changes inside non-FBD sections that the software has detected are not shown. Only the name of the section is displayed.
When selected, such sections are either updated, added, or removed from the logical
Control Participant project.
NOTE: If you update the logical Control Participant project with code in LL984 language added during online refinement and you had not selected the Ladder
Logic 984 (LL984) setting in the Control Participant before deploying, the
is displayed after the update.
To be able to build the logical Control Participant project select the Ladder Logic
984 (LL984) setting in project containing the configuration of the controller (see
EcoStruxure ™ Process Expert, Control Participant Services, User Guide) that is mapped to the executable of this Control project.
The software does not detect changes to such items.
The software displays any animation tables and/or operator screens that the deployed
Participant project contains, including modified and/or new ones. Animation tables and/ or operator screens that you have deleted from the deployed Participant project are not shown.
You cannot select individual items but only the category for transfer to the logical
Participant project.
When you select a category, any animation tables or operator screens of the logical
Control Participant project are overwritten with the ones contained in the deployed
Participant Project.
By default, both categories are not selected.
NOTE:
• Overwriting of an existing operator screen creates a copy of the screen in the logical Participant project. Following the update, use the Refine command to edit the categories and make their contents consistent with the deployed
Control Participant project.
• Animation tables and/or operator screens that you have removed from the deployed Participant project are not removed from the logical Participant project by using the command. Use the Refine command to delete them.
Details of configuration are not shown.
The Hardware category is selected by default (if changes are detected) and is readonly.
If the controller configuration is modified because of the update operation, mappings may be deleted.
NOTE: If you have changed the configuration online, performing the update is required to be able to use the Deploy changes / Undo Online Changes command.
EIO0000001114.15
EIO0000001114.15
Updating with Changes to Variables
The table describes the behavior of the software when you update a logical
Control Participant project, depending on the changes that you have made to variables contained in the deployed Control Participant project.
Variables in the Deployed
Control Project
Variables with
or
as Custom attribute.
Variables without
as Custom attribute.
Behavior
No changes to their attributes are updated in the logical
Control Participant project.
Device DDT variables
Any attributes of such variables that you add or modify during refinement online are updated in the logical Control
Participant project, except for the Address or Value attributes if it corresponds to or references a topological address.
NOTE: For more information on variables using the
Value attribute for topological addressing, refer to the topic describing REF_TO type variables (see
EcoStruxure ™ Process Expert, Control Participant
Services, User Guide).
These variables (and any of their attributes) coming from the configuration are not transferred to the logical Control
Participant project.
Therefore, if you
add code during refinement online, page 544
that uses this type of variable, you can update the logical
Control Participant project with that code but not with the variable itself. This causes the code to become invalid.
NOTE: You can create the DDDT variable in the logical
Control project by using the
Updating with Changes to Sections Containing HAL DFBs
You cannot transfer to the logical Control Participant project any changes that you have made or code that you have added to sections containing
Changes That Cannot Be Transferred to Control Projects
You cannot transfer to the logical Control Participant project changes pertaining to any of the following categories:
• Control project settings (refer to the Control Participant help, Operating
Modes ).
• SR sections.
• Properties of MAST and FAST tasks.
• Properties of MAST and FAST sections (1) .
• Timer and I/O event tasks.
• Alias of attribute of variables for Modicon X80 I/O modules (reference to the
Device DDT variable).
(1) Except for changes in the Comment tab.
Identifying Project and Hardware Changes
Before proceeding with the update, the software displays the Update Project dialog box, which provides information about the differences that it has detected between the deployed Participant project and the logical Participant project. It also allows you to select, which changes you want to apply to the logical Control
Participant project.
The software can only update the logical Participant project with changes that pertain to a category displayed in the Name column of the Update Project dialog box. Changes that are not detected or that are detected but that cannot be selected are not transferred.
571
When the software detects no changes, it does not display the Update Project dialog box but instead, shows a message to inform you that it has found no changes. This is the case if, for example, only a timer event was added during online refinement.
NOTE: When you select a section in order to apply changes to this section in the logical Control Participant project, the software overrides the refinements that you made in this section after the deployment. See also the topic that describes the
impact of a Control project update, page 573
on sections that you have created after deployment.
NOTE: Restrictions may apply when
.
The following figure shows an example of the Update Project dialog box.
572
1 Check box to have a
performed on the selected items before proceeding with the update. By default, the option is not selected.
Header Description
Check boxes Select items that you want to update in the logical Control Participant project.
A green square inside the check box in the column header indicates that, at least, 1 item that the software has detected as a difference is still unselected.
NOTE: You cannot select sections that contain
.
Name
Action
Identifier of the item that the software has detected as a difference.
Items are grouped by categories of the Control Participant program.
Indicates the action that the software will carry out for the item:
• Plus icon: The item is added to the logical Participant project/controller configuration.
(for example, because the item has been added during online refinement or removed from the logical Participant project after the last deployment.)
• Minus icon: The item is removed from the logical Participant project/controller configuration.
(for example, because the item has been removed during online refinement or added to the logical Participant project after the last deployment.)
• Pencil icon: The item is modified compared to the logical Participant project.
NOTE: When you select a section, the software applies any changes that it has identified for this section. You cannot select/unselect changes individually inside a section.
Type of the item.
Type
DataType
Change
Description
Data type of the item, if applicable.
For FBD sections, variables and types, indicates whether the change that the software has identified is an addition, a modification, or a deletion compared to the logical Participant project.
EIO0000001114.15
NOTE: If the software does not detect a difference between the deployed
Participant project and the corresponding logical Participant project in a category of the Update Project dialog box, no entry appears under that category.
Checking Consistency
Select the corresponding check box in the Update Project dialog box for the software to perform a
before proceeding with the update of the logical Participant project.
In such case, the software displays the Check Consistency dialog box to show, for the changes that you have selected in the Update Project dialog box:
• The sections that contain constituents that are inconsistent.
• For each section, the facets that are assigned to the section and generate the corresponding constituents.
• For each facet, a description of the inconsistency.
Select the check box next to a facet to
it.
If the check box of a facet is cleared, the generation status of the facet remains
During a subsequent
of the updated logical Participant project, the software:
• Does not modify constituents of facets that are unlinked.
• Attempts to restore constituents of facets that are inconsistent.
By default, no items are selected.
EIO0000001114.15
NOTE: If the software does not detect inconsistencies, it does not display the
Check Consistency dialog box.
Updating After Creating Sections in the Logical Control Project
Without Deploying Them
After updating the logical Control project, a section is moved to the end of sections in this project (highest order value) if the following conditions are fulfilled:
• The logical Control project is deployed.
• You create a section either in the Project Explorer or during refinement
(offline) post deployment.
573
• You do not deploy this section.
• The section that you have created occupies the same position as a section in the deployed Control project or you select the section in the Update Project dialog box (delete).
It can also have an impact on facets that are assigned to this section.
The following example shows how a section created in the logical Control project after deployment can have the same position as a section in the deployed Control project.
Example: The logical Control project contains two sections. It is deployed.
Logical Control project (offline)
Section_1 / order 0
Section_2 / order 1
Deployed Control project (online)
Section_1
Section_2
Then, section_3 is created in between Section_1 and Section_2. It now has the same position as Section_2 in the deployed Control project.
Logical Control project (offline)
Section_1 / order 0
Section_3 / order 1
Section_2 / order 2
Deployed Control project (online)
Section_1
Section_2
The table describes the possible scenarios where updating the logical Control project has an impact on the position of a section that you have created in it post deployment and/or on the status of the facets assigned to this section.
Assignment and generation status
The position of the section conflicts with the position of a section in the deployed project
Yes
Proposed action during Control project update
User selection Result in logical Control project after the update
Facets are assigned to the section but none are generated.
None.
The section created in the logical project is not detected as a difference because it is not generated.
Delete.
Not applicable.
The section that was created in the logical project is moved to the end of sections
(highest order value) (1)(2) .
Facets are assigned to the section and generated.
No
Yes Delete.
Delete.
The section is selected for deletion.
The section is selected for deletion.
The section is not selected (default).
• The section created in the logical project is moved to the end of sections (highest order value) (2) .
• The generation status of facets is changed to Non Generated .
• The section created in the logical project is moved to the end of sections (highest order value) (2) .
• The generation status of facets is changed to Non Generated .
• The section created in the logical project is moved to the end of sections (highest order value) (1) .
• The generation status of facets is unchanged.
(1) After the update is complete, you may be able to preserve the change that you have made in the logical Control project by moving the section back to its original position and propagating the change in the system engineering life cycle.
(2) After the update is complete, to remove the section from the logical Control project, right-click it in the Containers pane of the
Assignment Editor and select Delete .
NOTE: In the above scenarios, it is implied that other changes that you may have made during refinement online are applied to the logical Control project
(for example, adding code to a section or changing the order of sections).
574 EIO0000001114.15
EIO0000001114.15
NOTE: The behavior is the same when you update the logical Control project if you create a section in the Project Explorer , generate, and deploy it and then delete it during refinement online (given the section is not
).
Aborting Project Update Tasks
After confirming the update by clicking OK in the Update Project dialog box, the abort icon is displayed in the
. Click the icon to cancel the task. The project is not updated.
Only the user who has selected the command is allowed to abort it.
NOTE: If you are updating the Control Participant project with only a few changes, the task may complete before you are able to click the icon.
Updating the Project
To update the logical Control Participant project, proceed as follows.
Step
1
2
3
4
5
6
7
8
Action
Verify that the engine is
.
In the Topology Explorer , right-click the controller or station node that contains the deployed Participant project and select Update Project .
Result: The software displays the Confirm Update Project dialog box.
Verify the information that is displayed and click OK .
Result: The software displays the Update Project dialog box.
NOTE: Click Cancel to close the Confirm Update Project dialog box without applying the changes.
Select the changes that you want to update the logical Control Participant project with.
NOTE: Click Cancel to close the Update Project dialog box without updating the
Control Participant project.
Select the Check Consistency check box if you want the software to perform a consistency check; otherwise proceed to step 8.
Click OK .
Result: The software displays the Check Consistency dialog box if you selected the option and if it detects inconsistencies.
In the Check Consistency dialog box, select facets that you want to unlink.
NOTE: Click Cancel to close the Check Consistency dialog box without unlinking facets and revert to the Update Project dialog box.
Click Unlink or OK .
Result: The software:
• Applies the changes that you have selected.
• Changes the status of the associated executable to Out Of Date .
• Displays Completed in the information pane once it has successfully completed the update process.
• Updates the related date/time field.
• Removes the
online refinement icon, page 366
from the associated topological entity only if you had selected to update the Control Participant project with all the detected changes of the following categories; otherwise the indicator remains.
◦ Derived Data & FB Types
◦ Variables & FB Instances
◦ Sections
575
Supervision Project Execution Stage
Executing the Deployed Supervision Participant Project
Overview
You need to execute the deployed Supervision Participant project locally, on each
PC to which you have deployed the Supervision project by using the appropriate
Supervision runtime.
For information on the required software, refer to the topic describing software requirements (see EcoStruxure ™ Process Expert, Installation and Configuration
Guide).
Executing a Deployed Supervision Project
For information on executing the deployed Supervision Participant project on a
PC, refer to Executing the Deployed Supervision Project (see EcoStruxure ™
Process Expert, Supervision Participant Services, User Guide).
576 EIO0000001114.15
Engineering M580 Safety Systems
Engineering M580 Safety Systems
What’s in This Chapter
Using Modicon M580 Safety Controllers........................................................ 577
M580 Safety Systems in the Instantiation Stage............................................. 578
M580 Safety Systems in the Project Definition Stage ..................................... 579
M580 Safety Systems in the Assignment Stage ............................................. 584
M580 Safety Systems in the Generation Stage .............................................. 585
M580 Safety Systems in the Refinement Stage ............................................. 585
M580 Safety Systems in the Configuration Stage........................................... 587
M580 Safety Systems in the Mapping Stage.................................................. 592
M580 Safety Systems in the Build Stage ....................................................... 592
M580 Safety Systems in the Deployment Stage............................................. 593
M580 Systems in the Execution Stage .......................................................... 594
Using Supervision with M580 Safety Systems ............................................... 595
This chapter describes the aspects that are specific to using an M580 safety configuration and its associated Control project (the M580 safety system ) when engineering a system in EcoStruxure Process Expert. The information is grouped by stages of the system engineering life cycle.
Using Modicon M580 Safety Controllers
Certifications
The M580 safety controller (PAC) is certified by TÜV Rheinland Group for use in applications up to and including safety integrity level 3 (SIL3).
For additional information, refer to the topic describing certifications in the
Modicon M580 Safety Manual , which you can find in the
Control Participant of EcoStruxure Process Expert
EcoStruxure Process Expert 2020 R2 uses Control Expert XL Safety V15.0 as
Control Participant.
The safety configuration and safety program of an M580 safety system are created and modified exclusively by the Control Participant.
Only the process (non-safety) areas and the non-safety modules of the M580 safety system are managed by EcoStruxure Process Expert.
Engineering Systems Containing M580 Safety Controllers
When you engineer an EcoStruxure Process Expert system that contains an
M580 safety controller, in addition to following the normal system engineering life cycle, perform the following activities:
• Verify that the reference and version of the Control Participant is certified by the TÜV.
You can look up the TÜV-certified software tools and versions in the Revision
List , which is in the appendices of the M580 Functional Safety Controller
System certificate at www.certipedia.com or www.fs-products.com.
• Verify the integrity of the Control Participant (self-test).
• Use and monitor the safe signature and the safety application ID (SAId).
For details, refer to the topic describing building an M580 safety project in the
Modicon M580 Safety Manual .
EIO0000001114.15
577
Engineering M580 Safety Systems
• Follow the safe application life cycle and apply the safety rules as described in the Modicon M580 Safety Manual , which you can find in the
Control Participant, page 69 .
Information related to the following topics that are described in the Modicon M580
Safety Manual does not apply or applies only partially when working with the
Control Participant.
Difference when using EcoStruxure Process Expert
The
is not supported.
Topic
Usage of Process Namespace project setting
(Refer to the topic describing data separation in an M580 safety project)
Access rights
(Refer to the topic describing workstation security management)
User profiles and access rights for the Control Participant are managed by EcoStruxure Process Expert and cannot be modified.
Users who can log in to the engineering client have full access to the functionality of the Control Participant.
You can switch the M580 safety controller to maintenance mode by using the button in the toolbar of the Participant window when you use the Refine Online command.
Maintenance mode
(Refer to the topic describing workstation security management)
Building an M580 safety Control project
(Refer to the topic describing the operation of an M580 safety system)
Safe signature
(Refer to the topic describing building an M580 safety project)
Safe area password
(Refer to the topic describing application security management)
Transferring M580 safety projects
(Refer to the topic describing modifications to Control Expert for the
M580 safety system)
CCOTF
(Refer to the topic describing modifications to Control Expert for the
M580 safety system)
Saving & restoring data between a file and the PAC
(Refer to the topic describing the modifications to Control Expert for the
M580 safety system)
Use a build command in the context menu of the executable of the Control project in the Project Explorer .
Using a build command, page 592
in the context menu of the executable of a safety Control project generates a new SourceSafeSignature if you have made an applicable configuration or value change.
The
is managed in the
Topology Explorer instead by using the Safety password.
The command to transfer the project from the controller to the Control Participant is disabled.
To transfer the project to the controller, use only the deployment commands in the Topology Explorer .
CCOTF operations can be performed also when you
an M580 safety controller (offline).
The commands are disabled in the Control Participant.
Use the Back Up Data and Deploy Data commands in the Topology Explorer instead.
Additional Information
For more information on M580 safety systems, refer to the Modicon M580 Safety
System Planning Guide , which you can find in the
help of the Control Participant, page 69 .
M580 Safety Systems in the Instantiation Stage
This topic describes the aspects of the instantiation that are specific to using M580 safety systems. For general information, refer to the topic describing the instantiation stage.
578 EIO0000001114.15
Engineering M580 Safety Systems
Systems Explorer
You can use M580 safety controllers and their projects in any EcoStruxure
Process Expert system.
A system can contain both safety and non-safety controllers and Control projects.
Instantiation Stage
No safety-specific templates are provided to create instances in the application of a system that uses an M580 safety controller. The safety data and logic can be created only by refining the safety Control project.
Instances that you create in the application can only be used to generate the following:
• The process data and logic in a safety Control project.
• Supervision project data.
M580 Safety Systems in the Project Definition Stage
This topic describes the aspects of the Control project definition that are specific to using M580 safety systems. For general information, refer to the topic describing the Control project definition stage.
Creating M580 Safety Control Projects
M580 Safety Control Projects
In a system, M580 safety Control projects can coexist with Control projects of any other controller family.
M580 Safety Control Project Content
An M580 safety Control project can contain the following:
• A safety program ( SAFE )
• A non-safety program ( PROCESS )
• Global data
The logic and data that is part of each program is isolated from the other.
Creating M580 Safety Control Projects
To create an M580 safety Control project, right-click the system root folder in the
Project Browser and select M580 Safety .
Creating such a project also creates an M580 safety controller with a default configuration in the Topology Explorer , which is associated to the project.
Conversely, if you have created an M580 safety controller, a blank safety Control project has been created in the Project Explorer .
EIO0000001114.15
579
Engineering M580 Safety Systems
The following figure shows an M580 safety Control project as it appears in the
Project Browser .
580
Creating Sections, Logic, and Data
The following table indicates how to create the various types of program components of a safety Control project and where you can view them.
Type of logic and data
Safety sections, logic, and data
(includes animation tables)
Process sections, logic, and data
Ways to create
By refining the Control Participant project only.
Global data
By following the normal system engineering life cycle.
(Non-FBD sections and logic requires refining the Control
Participant project.)
By refining the Control Participant project only.
Viewing logic and data
Visible only in the refinement window (offline and online) of the
Control Participant.
FBD and non-FBD sections as well as facets assigned to FBD sections are visible in the Assignment
Editor .
Visible only in the refinement window (offline and online) of the
Control Participant.
Deleting M580 Safety Control Projects
Deleting a safety Control project also deletes the associated M580 safety controller entity in the Topology Explorer , and vice versa.
Managing Network Variables
The Manage Network Variables
does not let you manage variables of the safety program.
Supervision Projects
The Supervision projects that you create are independent of the M580 safety system.
You can create instances to be assigned to Supervision projects to
EIO0000001114.15
Engineering M580 Safety Systems
Exporting and Importing M580 Safety Control Projects
This topic describes the aspects of the Control project export and import that are specific to M580 safety Control projects. For general information about
project export and import operations, page 206 , refer to the topic describing how to
manage Control projects of a system.
Exporting M580 Safety ControlProjects
The Export command of the Project Explorer lets you export one or more safety
Control projects and create a non-editable export file (.sbk).
You can also export at the same time Control projects of the other controller families and Supervision projects.
In the Export window, the Safe Program section of safety Control projects is selected by default and read-only. The safety program is exported as a whole.
The associated safety configuration is not exported.
Importing M580 Safety ControlProjects
The Import command of the Project Explorer lets you import the M580 safety
Control projects that are contained in a project export file (.sbk).
The table describes the result when you import an M580 safety Control project in different scenarios.
Target system
An M580 safety Control project with the same identifier does not exist.
Result after import in Project
Explorer
The safety Control project is imported.
If you select to import the safety program, it is imported as a whole.
Impact on topology after import
An M580 safety controller entity is created with the default configuration (1) .
NOTE: If you want to import a safety Control project that is associated to an existing M580 safety controller in the Topology
Explorer , before importing the safety project,
rename the existing safety Control project, page 582
to have the same identifier as the one you will be importing.
The existing M580 safety controller is not impacted and no additional one is created.
An M580 safety Control project with the same identifier already exists.
A Control project with the same identifier but of the M580 ( safety non-
) or another controller family already exists.
If you select to import the safety program, it is imported as a whole.
The
that the software applies with regard to safety sections are the same as those for process sections.
You cannot import the M580 safety Control project.
In the Import window, it is tagged with a red dot (2) .
None.
(1) Schneider Electric recommends verifying that the Global Templates library of the target system contains the necessary topological safety templates (Foundation library) before importing.
Otherwise, you will not be able to save your changes when you configure the associated safety controller in the Topology Explorer .
(2) The same also applies when you import any Control project and an M580 safety Control project with the same identifier already exists in the target system.
NOTE: During import of a safety Control project, the associated M580 safety controller is locked.
EIO0000001114.15
581
Engineering M580 Safety Systems
Importing a Control Expert Project
The Import Control Project command of the Project Explorer lets you create a new M580 safety Control project by using the data of a compatible Control Expert project export file (.stu or . sbk).
The following are created:
• An M580 safety Control project in the Project Explorer .
• An associated M580 safety controller with the same configuration and project settings as in the export file in the Topology Explorer .
The name of the imported file becomes the identifier of the safety Control project that is created. The associated M580 safety controller is created with the default identifier.
Safety Password Management When Importing
When you import one or more M580 safety Control projects, before the import operation starts, the Verify Safety Password window may open prompting you to enter a safety password for each one.
The import operation starts only once all required safety passwords have been entered.
NOTE: The safety password that is referred to is the one that has been set in the Topology Explorer for the
associated M580 safety controller, page 588
.
The following table describes which safety password you need to enter when prompted during the import of an M580 safety Control project. This applies even if you select not to import the safety program.
Target system
An M580 safety
Control project with the same identifier does not exist.
An M580 safety
Control project with the same identifier already exists.
Safety password required
The safety password of the safety
Control project that you are importing (if set).
Impact on safety password after import
The safety password settings are the same as that of the imported safety Control project.
The safety password of the existing safety Control project in the target system (if set).
The safety password and password settings are the same as that of the existing safety Control project in the target system.
For example, if the existing safety
Control project has no safety password but the safety Control project that you are importing has a safety password, after the import, no safety password is set.
The following table describes which safety password you need to enter when prompted during the import of a Control Expert M580 safety Control project.
Target system Safety password required
Irrelevant The safety password of the safety
Control project that you are importing (if set).
Impact on safety password after import
The safety password settings are the same as that of the imported safety Control project.
You can manage the safety password from the controller entity in the Topology Explorer .
Importing a Safety Control Project Associated to an Existing M580 Safety Controller
By using an example, this topic illustrates the required workflow when you want to import an M580 safety Control project that is associated to an existing M580 safety controller or one that you will be importing. The workflow with M580 safety systems differs slightly because the import of a safety controller/project creates the counterpart safety project/controller.
582 EIO0000001114.15
Engineering M580 Safety Systems
Starting Point
You have exported the following to two separate export files (.sbk):
• The configuration of an M580 safety controller MyM580SafetyPAC from the
Topology Explorer
• The associated M580 safety Control project MyM580SafetyProject from the
Project Explorer
The executable of MyM580SafetyProject is mapped to MyM580SafetyPAC in the service mapping and both are exported.
In this example, the objective is to import into a different system the M580 safety controller and its project so that they are still associated and the executable of the project mapped to the controller.
Importing the M580 Safety Controller
After the import of MyM580SafetyPAC , a blank safety Control project is created.
The project is associated to the controller but has the default identifier.
Renaming the Associated M580 Safety Control Project
Rename the associated safety Control project so that it has the same identifier as the project that you are going to import.
EIO0000001114.15
583
Engineering M580 Safety Systems
Importing the Associated M580 Safety Control Project
When you import MyM580SafetyProject and select its executable and service mapping, it is merged with the safety Control project that you have renamed. No new associated safety controller is created. Instead, the service mapping with
MyM580SafetyPAC is recreated.
Importing the Associated Project Without Renaming
The following figure shows the result after importing MyM580SafetyProject if you do not rename ControlProject_1 . Two pairs of controller/Control project are created and MyM580SafetyPAC is not associated nor mapped to
MyM580SafetyProject .
M580 Safety Systems in the Assignment Stage
This topic describes the aspects of the Control project assignment that are specific to using M580 safety systems. For general information, refer to the topic describing the assignment stage.
Creating and Viewing Sections
You can only create FBD sections of the process program by using the
Assignment Editor .
None of the sections of the safety program that you create in refinement appear in the Assignment Editor .
Assigning Facets of Instances
You can only assign facets of instances to FBD sections of the process program by using the Assignment Editor .
584 EIO0000001114.15
Engineering M580 Safety Systems
M580 Safety Systems in the Generation Stage
This topic describes the aspects of the Control project generation that are specific to using M580 safety systems. For general information, refer to the topic describing the generation stage.
Generating M580 Safety Control Projects
The generation process only generates logic and data in the process program of an M580 safety Control project in the same way as it is done for other Control projects.
NOTE: While the safety Control project is being generated, it is locked. This also locks the associated safety controller.
Regenerating M580 Safety Control Projects
Regenerating a safety Control project does not discard changes that you have performed in the safety program.
The process program is impacted in the same way as the logic and data of nonsafety Control projects.
Impact of Generation on the Associated M580 Safety Controller
When you generate a safety Control project and you have not yet configured the associated M580 safety controller, the safety controller entity changes to a configured state in the Topology Explorer . That is, you can expand the node and see the default controller configuration.
M580 Safety Systems in the Refinement Stage
This topic describes the aspects of the offline Control project refinement that are specific to using M580 safety systems. For general information, refer to the topic describing the refinement stage.
Refining M580 Safety Control Projects Offline
Use the Refine command in the Project Explorer to open the project in the
Control Participant. This lets you refine both the safety and the process program.
If a
is set for the controller, before you can modify the safety program, you need to deactivate the safe area password protection in the toolbar of the Participant window and enter the safety password. Safe area password protection is activated automatically when you close the Participant window.
EIO0000001114.15
585
Engineering M580 Safety Systems
The following figure shows an example of the Control Participant window that opens when you refine the safety Control project while safety password protection is enabled.
(1) Button to deactivate/activate the safe area password protection.
NOTE: When you refine a safety Control project, you can view and access the configuration of the associated controller. However, to modify the configuration, follow the normal system engineering life cycle. That is, use the
Configure command in the Topology Explorer .
NOTE: While the Control Participant refinement window is open for the M580 safety project, the associated safety controller is locked.
Impact of Refinement on the Associated M580 Safety Controller
When you refine a safety Control project and you have not yet configured the associated M580 safety controller, the safety controller entity changes to a configured state in the Topology Explorer . That is, you can expand the node and see the default controller configuration.
Control Participant Project Settings
The Usage of Process Namespace project setting of the Control Participant is not supported and it must remain disabled. Otherwise, you cannot save changes that you have made during Control project refinement.
This has an impact on how the operator screen can reach variables of the Process and Global namespaces because you cannot use the PROCESS prefix anymore in case two variables are declared with the same name in these namespaces.
For details, refer to the topic describing how to display data on operator screens
( Animation Tables and Operator Screens ) in the Modicon M580 Safety Manual .
Performing Consistency Checks
When you perform a
consistency check, page 347 , only the logic of the process
program is checked.
Device DDT Variable Wizard
In the toolbar of the Control Participant window, the button that opens the
is not available because any device DDT variables
586 EIO0000001114.15
Engineering M580 Safety Systems
that are created for the hardware that is configured in the associated safety controller are already present and can be used.
Managing Network Variables
The Manage Network Variables
lets you manage only variables of the process program.
M580 Safety Systems in the Configuration Stage
This topic describes the aspects of the configuration that are specific to using
M580 safety systems. For general information, refer to the topic describing the
configuration stage, page 364 .
Creating and Configuring M580 Safety Controllers
Integrated Architectures
For a list of M580 safety CPU modules that can be configured, refer to the topic describing integrated architectures (see EcoStruxure ™ Process Expert, Control
Participant Services, User Guide).
For details on the supported modules, refer to the Modicon M580 Safety Manual .
Creating M580 Safety Controller Entities
To create an M580 safety controller, right-click the system root folder or a topology folder in the Topology Explorer and select M580 Safety .
Creating a safety controller also creates a blank M580 safety Control project in the
Project Explorer , which is associated to the controller.
Conversely, if you have created an M580 safety Control project, a default safety controller entity has been created in the topology.
The following figures shows an M580 safety controller entity as it appears in the
Topology Explorer .
EIO0000001114.15
Deleting M580 Safety Controller Entities
Deleting a safety controller also deletes the associated M580 safety Control project in the Project Explorer , and vice versa.
Configuring an M580 Safety Controller
Use the Configure command to open the Control Participant. This lets you add, change, and configure the hardware of the safety controller:
• The safety CPU and coprocessor modules
• Safety power supply modules
587
Engineering M580 Safety Systems
• Safety I/O modules
• Non-safety modules
• Racks
If the
is enabled for the controller, before you can configure safety modules, you need to disable the safety protection in the toolbar of the Participant window and enter the safety password. Safety protection is enabled automatically when you close the Participant window.
The following figure shows an example of the Control Participant window that opens when you configure an M580 safety controller while safety password protection is enabled.
(1) Button to disable safety protection.
NOTE: When you configure an M580 safety controller, you can view and access both the safe and the process programs of the associated safety
Control project. However, to create or modify any data and logic, use the
Project Explorer .
NOTE: While the Control Participant configuration window is open for the
M580 safety controller, the associated safety Control project is locked.
Analyzing Configuration Changes
By default, when you save the configuration of an M580 safety controller, the
Control Participant does not perform an analysis. To have the configuration analyzed, enable Analyze Project in the
of the M580 safety
Control project. This also analyzes the program areas of the Control project.
Managing the Safety Password
Overview
The safe area password protection function of the Control Participant for M580 safety controllers is managed from the Topology Explorer by using the Safety password function instead. The corresponding property is therefore disabled inside the Control Participant.
The Safety password is not available for a station node running the controller simulator.
For more information about the safe area password function, refer to the topic describing Application Security Management in the Modicon M580 Safety Manual .
588 EIO0000001114.15
Engineering M580 Safety Systems
Scope of the Safety Password
The following table summarizes for which actions you need to enter the safety password when safety password protection is enabled.
Action Description
Configuration of the M580 safety controller.
Unlocking safety protection to be able to configure safety modules.
Offline refinement of the M580 safety
Control project.
Online refinement of the M580 safety
Control project.
Unlocking safety protection to be able to modify safety data and logic.
Switching the controller to maintenance mode to be able to modify safety data and logic online.
This applies also to the controller simulator.
All deployment operations on the M580 safety controller that include the safety program.
Entering the safety password is required to be able to proceed with the deployment only if the safety program has been modified.
This applies also to the controller simulator.
NOTE: A first deployment may require entering the safety password even when the safety program has not been modified.
Safety Password Requirements
Your password must contain between 8 and 16 alphanumeric characters to be accepted.
It can contain lower and upper case as well as special characters.
NOTE: Password strength is increased when it contains a mix of upper and lower case, alphabetical, numeric, and special characters.
Enabling and Disabling the Safety Password
The safety password is enabled by default.
To disable it, use the Safety
of the M580 safety controller.
Setting the Safety Password
To set the safety password, use the Manage Password
in the context menu of the M580 safety controller.
This action sets the build state of the executable of the associated safety Control project to Out Of Date if it was built.
Changing the Safety Password
To change the safety password, use the Manage Password
in the context menu of the M580 safety controller.
This action sets the build state of the executable of the associated safety Control project to Out Of Date if it was built.
Clearing the Safety Password
To clear the safety password, use the Clear Password
in the context menu of the M580 safety controller.
This action sets the build state of the executable of the associated safety Control project to Out Of Date if it was built.
EIO0000001114.15
589
Engineering M580 Safety Systems
Resetting a Forgotten Safety Password
NOTE: If you have also forgotten the Controller password, proceed with the
of that password before resetting the Safety password.
To reset the safety password of an M580 safety controller, proceed as follows.
Step
1
2
3
4
5
6
Action
Right-click the topological entity and select Forgot Password > Safety .
Result: The Forgot Password dialog box opens and a number is displayed in the
Authentication Code field.
NOTE: If you close the Forgot Password dialog box and open it again, the same number is displayed.
Contact Schneider Electric
, provide the number, and specify that you want to reset the safety password..
Result: You receive a temporary password.
NOTE: The temporary password is valid as long as you do not modify the configuration or the associated Control project after requesting it.
Right-click the safety controller and select Manage Password > Safety .
Result: The Manage Password dialog box opens.
Enter the temporary password in the Current Password text box, the new password, and click OK .
Result: The new safety password is set.
Build the executable of the associated safety Control project if its build state is Out Of
Date .
If you had already deployed the project to the safety controller, apply the new safety password to the deployed Control project by using the Deploy Changes/Undo Online
Changes command.
Exporting and Importing M580 Safety Controllers
This topic describes the aspects of the topology export and import that are specific to M580 safety controllers. For general information about
topology export and import operations, page 406 , refer to the topic describing how to manage the
topology of a system.
Exporting M580 Safety Controllers
The Export command of the Topology Explorer lets you export one or more
M580 safety controllers and create a non-editable export file (.sbk).
You can also export at the same time other topological entities of the system.
The associated safety Control project is not exported.
Importing M580 Safety Controllers
The Import command of the Topology Explorer lets you import the M580 safety controllers that are contained in a topology export file (.sbk).
The Global Templates library of the target system must contain the necessary topological safety templates () before importing. These templates may be missing if you have migrated a database of an earlier software version. In that case, you will not be able to save your changes when you configure the safety controller.
590 EIO0000001114.15
Engineering M580 Safety Systems
The table describes the result when you import an M580 safety controller in different scenarios.
Target system
An M580 safety controller with the same identifier does not exists.
An M580 nonsafety controller with the same identifier already exists.
An M580 safety controller with the same identifier already exists.
Action selected in the
Import window to solve the conflict
N/A
Result after import in Topology
Explorer
Create
NOTE:
Update is not available.
Create
The safety controller is created with the same identifier and configuration.
The exported project settings are also retained.
The safety controller is created with a new identifier but the same configuration.
The exported project settings are also retained.
Update
The safety controller is created with a new identifier but the same configuration.
The exported project settings are also retained.
The configuration of the existing safety controller is replaced with that of the imported safety controller.
The project settings are also replaced.
Impact on projects after import
A blank M580 safety Control project is created, which is associated to the safety controller.
A blank M580 safety Control project is created, which is associated to the safety controller.
A blank M580 safety Control project is created, which is associated to the safety controller.
No impact.
NOTE: During import of a safety controller, the associated M580 Control project is locked.
Safety Password Management When Importing
When you import one or more M580 safety controllers, before the import operation starts, the Verify Safety Password window may open prompting you to enter a safety password for each one.
The import operation starts only once all required safety passwords have been entered.
The following table describes which safety password you need to enter when prompted during the import of an M580 safety controller.
Target system Safety password required
An M580 safety controller with the same identifier does not exist.
An M580 safety controller with the same identifier already exists.
The safety password of the safety controller that you are importing (if set).
The safety password of the existing safety controller in the target system (if set).
Impact on safety password after import
The safety password settings are the same as that of the imported safety controller.
The safety password and password settings are the same as that of the existing safety controller in the target system.
For example, if the existing safety controller has no safety password but the safety controller that you are importing has a safety password, after the import, no safety password is set.
EIO0000001114.15
591
Engineering M580 Safety Systems
M580 Safety Systems in the Mapping Stage
This topic describes the aspects of the Control project mapping that are specific to using M580 safety systems. For general information, refer to the topic describing the mapping stage.
Control Executable Service Mapping
You can create a service mapping only with the M580 safety controller that is associated to the safety Control project.
Only one executable of a safety Control project can be mapped to this controller. If you have created additional executables, you can only map them to station nodes on which a ControlExpert service has been created.
Communication Mapping
The table describes the type of peer to peer communication that you can implement by using the Communication Mapping Editor .
Controller 1
M580 safety platform
M580 safety platform
Controller 2
M580, M340, or Quantum platform
M580 safety platform
Peer to peer communication
Possible by using process variables only.
Possible by using process variables only.
To use variables of the safety program, refine the safety Control projects.
Also, communication between an M580 safety CPU and CIP safety devices cannot be implemented by using the Communication Mapping Editor . You need to refine the safety Control project.
Hardware Mapping
The I/O safety modules of the M580 safety controller do not appear in the
Hardware Mapping Editor and therefore cannot be mapped to interfaces of
Control facets.
Mapping of communication interfaces of the CPU and other non-safety communication modules of the safety controller can be performed in the same way as with controllers of the other platforms.
M580 Safety Systems in the Build Stage
This topic describes the aspects of building executables of Control projects in the
Project Explorer that are specific to M580 safety systems. For general information, refer to the topic describing the build stage.
Building M580 Safety Control projects
Using a build command in the context menu of the executable of a safety Control project locks the associated M580 safety controller.
NOTE: Once you have built the executable of a safety Control project by using the Build All command, you cannot modify the service mapping anymore nor delete the executable if it is mapped to the M580 safety controller.
592 EIO0000001114.15
Engineering M580 Safety Systems
Safe Signature
Each time you build the executable of a safety Control project, if you have changed the safety configuration, safety program, or certain project settings, the software generates a SourceSafeSignature.
For a list of actions that generate a SourceSafeSignature change, refer to the
Modicon M580 Safety Manual .
The software uses the SourceSafeSignature to inform you of a change when you use a deployment command.
However, the safe signature cannot be viewed at the platform level. To copy it, open the Control project by using the Open Built Project command in the context menu of its Control executable.
NOTE: The software sets the Safety Signature management setting of the
Control Participant to Automatic when you build an M580 safety Control project ( Tools > Project Settings > General > Build Settings ).
M580 Safety Systems in the Deployment Stage
This topic describes the aspects of the Control project deployment that are specific to using M580 safety systems. For general information, refer to the topic describing the deployment stage.
Deploying to M580 Safety Controllers
Use the Deploy Built Project and Re-Deploy Last Project commands in the
Topology Explorer to deploy the Control project to the M580 safety controller.
This lets you deploy both the safety and the process program.
Deploying Changes to M580 Safety Controllers
Use the Deploy Changes / Undo Online Changes command in the Topology
Explorer to deploy Control project changes to the M580 safety controller. This lets you
to the safety and/or the process program.
However, the changes that appear in the Safe Program section can only be deployed all at once or not at all.
When you deploy changes to the process program that impact the safety program
(for example, a process variable that is used as program interface to exchange data with the safe program), a dialog box opens and allows you to confirm the change or modify the selection.
Safe Signature Changes
Before proceeding with a deployment, re-deployment, or deployment of changes operation that includes the safety program, if the software detects that the
SourceSafeSignature of the application that you are deploying is different from that of the application in the controller, it opens a dialog box to inform you.
You have the choice to acknowledge and proceed with the deployment or cancel the operation.
The SourceSafeSignature itself is not displayed nor can it be copied.
Deploying With Safety Password Protection Enabled
For deployment, re-deployment, and deployment of changes operations that include the safety program, if the
is enabled for the controller and the safety program has been modified, before you can proceed with the deployment, you need to enter the safety password when prompted.
EIO0000001114.15
593
Engineering M580 Safety Systems
M580 Systems in the Execution Stage
This topic describes the aspects of the project online refinement and update that are specific to using M580 safety systems. For general information, refer to the topic describing the execution stage.
Refining M580 Safety Control Projects Online
Use the Refine Online command in the Topology Explorer to modify online both the process program and configuration and safety program and configuration of the deployed Control project.
The controller opens in safety mode.
If a
is set for the controller, before you can modify the safety program or configuration online, you need to switch to maintenance mode by using the button in the toolbar of the Participant window. This requires entering the safety password. Otherwise, if the safety password is disabled, switching to maintenance mode does not require a password.
Safety mode is enabled automatically when you close the Participant window.
The same applies also when you refine online by using the controller simulator.
The following figure shows an example of the Control Participant window that opens when you refine a safety Control project online while safety password protection is enabled.
594
(1) Button to switch between safety mode and maintenance mode.
EIO0000001114.15
Engineering M580 Safety Systems
The following figure shows an example of the Control Participant window that opens when safety password protection is disabled.
(1) Button to switch between safety mode and maintenance mode.
Updating Logical M580 Safety Control Projects
Use the Update Control Project command in the Topology Explorer to update the logical M580 safety Control project and the configuration with changes that you have made online. This lets you
both the process and the safety areas.
However, the changes that appear in the Safe Program section can only be updated all at once or not at all.
If the
is enabled for the controller, before you can update the safety program, you need to enter the safety password.
Using Supervision with M580 Safety Systems
Overview
Because instances of the application cannot be used to create data and logic of the safety program of M580 safety Control projects, you have to create your own
Supervision instances to monitor safety Control data.
For general information on working with Supervision instances, refer to the various
Supervision topics in the description of the system engineering life cycle.
EIO0000001114.15
595
Engineering M580 Safety Systems
Using Supervision Templates
Step Description
1 You can instantiate the following Supervision data facet templates of the Foundation library for each variable of an M580 safety Control project that you want to monitor from the
Supervision runtime.
• $VariableTag_CD
• $AdvancedAlarm_CD
• $DigitalAlarm_CD
• $TrendTag_CD
NOTE: Select Facets as filter in the Browser pane.
2 Configure instances of $VariableTag_CD as follows:
• Addr parameter ( Configuration category): Name of the safety variable in the Control project preceded by the safe.
prefix.
For example, if the variable name is MyVar1 , enter safe.MyVar1
.
• Type parameter ( Configuration category): Data type of the variable.
For example, UINT.
3
4
If you are using trend tags, open the Asset Workspace Editor and link the trend tag instance to the variable tag instance so that the instance status becomes valid.
Follow the system engineering life cycle to complete the other stages for the Supervision project.
596 EIO0000001114.15
Managing Communication
What’s in This Chapter
Communication Through Modbus TCP Ethernet Implicit Messaging (I/O
Communication by Using Modbus TCP Ethernet Explicit Messaging ............... 604
Communication by Using EtherNet/IP Explicit Messaging............................... 608
Communication Through Modbus Explicit Messaging..................................... 611
Monitoring Modbus Device Data Directly from Supervision ............................. 639
Communication with Devices by Using a PROFIBUS Master Module .............. 642
Overview
This chapter contains information describing how to manage communication between devices and controllers depending on the communication protocol that you want to use. It contains examples that use templates of the General Purpose library Classic.
WARNING
LOSS OF CONTROL
• Perform a Failure Mode and Effects Analysis (FMEA) of your application, and apply preventive and detective controls before implementation.
• Provide a fallback state for undesired control events or sequences.
• Provide separate or redundant control paths wherever required.
• Supply appropriate parameters, particularly for limits.
• Review the implications of transmission delays and take actions to mitigate.
• Review the implications of communication link interruptions and take actions to mitigate.
• Provide independent paths for control functions (for example, emergency stop, over-limit conditions, and fault conditions) according to the safety analysis and applicable codes, and regulations.
• Apply local accident prevention and safety regulations and guidelines.
1
• Test each implementation of this library for proper operation before placing it into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
1 For additional information, refer to NEMA ICS 1.1 (latest edition), Safety
Guidelines for the Application, Installation, and Maintenance of Solid State Control and to NEMA ICS 7.1 (latest edition), Safety Standards for Construction and
Guide for Selection, Installation and Operation of Adjustable-Speed Drive
Systems or their equivalent governing your particular location.
NOTE: The software does not verify the status of the communication between controllers and I/O devices.
Communication Through Modbus TCP Ethernet Implicit
Messaging (I/O Scanning)
Overview
This section contains specific procedures to help you configure communication through Modbus TCP Ethernet implicit messaging by using the I/O scanner function. It covers communication between a controller and entities that are configured in the topology of the system, and between several controllers (peer to
EIO0000001114.15
597
peer communication). It contains examples that use templates of the General
Purpose library Classic.
NOTE: For the engineering of a system with the software, it is not relevant how Modbus TCP devices are physically connected to the real Ethernet network. As long as they are connected to the same logical Ethernet network with a valid IP address, you can proceed with the implementation of communication in the software. However, in your physical architecture, you need to confirm that connections are done properly so that devices are indeed reachable.
For example, in an M580 architecture, whether an STB island is connected directly to the service port of the CPU module, to the port of a
BMENOC0301.2 module, or to the service port of a BMXCRA31210 module does not matter. In the software, you configure only the DIO scanner service of the CPU or NOC module to exchange data with the STB island on the same
Ethernet network.
Communicating with Devices Through Modbus TCP Implicit Messaging (I/O Scanning)
Overview
The software supports communication through Modbus TCP Ethernet implicit messaging between common devices and supported controller platforms by using the I/O scanner function.
In addition to configuring the controller as a client and enabling its I/O scanner, you need to instantiate the topological template of the Modbus TCP device.
The topological device instance allows you to assign an IP address to the device and connect it to the Ethernet network to which the controller is connected.
The communication channel between the controller and the device is managed through the
communication mapping, page 424
.
The build process creates the communication channel in the built Control
Participant project.
For a list of available device templates, refer to the Device/Communication Matrix
(see EcoStruxure ™ Process Expert, Communication Control Services User
Guide).
NOTE: Refer to the TVDA document Hot Standby Quantum_EIO for recommendations when using a NOC communication module to implement communication between Modbus TCP devices and Hot Standby controllers of the Quantum platform.
Using Device Application Templates
The device-specific application template of a Modbus TCP device (for example,
$TesysTE ) allows you to edit the Control and Supervision parameters of the device and proceed with the hardware mapping to the controller I/O modules.
It is not required for managing communication with the device using I/O scanning.
Generic Device Templates
If no specific topological template is available for the device that you are using, use one of the
generic topological device templates, page 391
and its application counterpart.
The generic application template lets you create an input and an output variable of required length and data type.
The table indicates which device template to use depending on the module that is used to communication with the device.
598 EIO0000001114.15
EIO0000001114.15
Module used to communicate with device
CPU module of an M580 controller
BMENOC•••• communication module
Topological device template to use
$EGenericDeviceHW
$EGenericDeviceHW
Corresponding application device template to use
$GenNOCDevice
Some manual configuration is required (see EcoStruxure ™
Process Expert, Device
Templates User Guide).
$GenericDevice CPU module of a Quantum controller
140NOE••••• communication module
Implementing Communication
To implement communication between a controller and a device through Modbus
TCP by using I/O scanning, complete these steps.
Step Description
1 Create a Control project in the system.
2
3
Create a Control executable in the project.
Create and configure a
with the I/O scanner enabled and its communication module. Configure the client
memory start and length parameters, page 376
of the communication module.
4
5
6
7
8
9
10
Create and configure, page 391
the topological device entity (configure
IP address and other applicable properties).
NOTE: If the device communicates with a communication module that validates IP addresses based on the subnet mask, verify that the IP addresses of the device and the module belong to the same subnet.
Create an
.
Connect the communication module of the controller, page 399
to the
Ethernet network.
Connect the I/O device, page 404
to the same Ethernet network.
Instantiate the application template that corresponds to the topological device entity and configure its properties.
Map the Control executable of the project
to the controller entity, page
.
Define the communication channel, page 424
between the controller and the device.
Stage
Project
Definition
Configuration
Instantiation
Mapping
(service)
Mapping
(communication)
To complete the other steps to implement the system that contains the controller and the device, follow the system engineering life cycle described in this manual.
NOTE: Refer to the topic describing device communication technologies (see
EcoStruxure ™ Process Expert, Device Control Services User Guide) for configuration and setup details.
Implementing Communication by Using Generic Device
Templates
To implement communication through Modbus TCP by using I/O scanning, between a controller and a device for which no specific topological template exists, complete these steps.
Step Description
1 Create a Control project in the system.
2 Create a Control executable in the project.
Stage
Project
Definition
599
Step Description
3
4
5
6
7
8
9
10
Create and configure a
with the I/O scanner enabled and its communication module. Configure the client
memory start and length parameters, page 376
of the communication module.
Create and configure the
generic topological device entity, page 391 ,
assign an IP address to it, and enter values for the
read/write parameters, page 393 .
NOTE: If the device communicates with a communication module that validates IP addresses based on the subnet mask, verify that the IP addresses of the device and the module belong to the same subnet.
Create an
Connect the communication module of the controller, page 399
to the
Ethernet network.
Connect the I/O device, page 404
to the same Ethernet network.
Instantiate the
generic application device, page 598
template and configure its properties.
Map the Control executable of the project
to the controller entity, page
Define the communication channel, page 424
between the controller and the device.
Stage
Configuration
Instantiation
Mapping
(service)
Mapping
(communication)
To complete the other steps to implement the system that contains the controller and the device, follow the system engineering life cycle described in this manual.
Communicating with STB Islands Through Modbus TCP Implicit Messaging
Overview
The software supports communication through Modbus TCP Ethernet implicit messaging between STB islands and supported controller platforms by using the
I/O scanner function.
The controller acts as client, and its I/O scanner is enabled.
The STB island acts as server, and both are connected to the same Ethernet network, on which they are identified with their respective IP address.
The communication channel between the controller and the STB island is defined through the
communication mapping, page 424
.
The build process creates the communication channel in the built Control
Participant project.
Implementing Communication
To implement communication between a controller and an STB island through
Modbus TCP (I/O scanning), complete these steps.
Step Description
1 Create a Control project in the system.
2
3
4
5
Create a Control executable in the project.
Create and configure a
with the I/O scanner enabled and its communication module. Configure the client
memory start and length parameters, page 376
of the communication module.
Create and configure an
entity and assign an IP address to its NIM.
NOTE: If the NIM communicates with a communication module that validates IP addresses based on the subnet mask, verify that the IP addresses of the NIM and the module belong to the same subnet.
Create an
Stage
Project
Definition
Configuration
600 EIO0000001114.15
Step Description
6
7
8
9
Connect the communication module of the controller, page 401
to the
Ethernet network.
Connect the communication module of the STB island, page 404
to the same Ethernet network.
Map the Control executable of the project
to the controller entity, page
Define the communication channel, page 424
between the controller and the STB island.
Stage
Mapping
(service)
Mapping
(communication)
To complete the other steps to implement the system that contains the controller and the STB island, follow the system engineering life cycle described in this manual.
Communicating with PROFIBUS Remote Masters Through Modbus TCP Implicit
Messaging
Overview
The software supports communication through Modbus TCP implicit messaging between PROFIBUS remote masters (PRMs) and supported controller platforms by using the I/O scanner function.
The topological PRM entity allows you to configure decentralizes devices (DPs) and assign an IP address to the PRM to connect it to the Ethernet network to which the controller is connected.
In addition to configuring the controller as a client with the I/O scanner enabled, you need to instantiate:
• A PRM management application template.
• A device application template that corresponds to the DP that is configured in the PRM entity.
The communication channel between the controller and the PRM is managed through the
communication mapping, page 424
.
The build process creates the communication channel in the built Control
Participant project.
NOTE: The device application templates of the configured DPs allow you to edit the Control and Supervision parameters of the devices and proceed with the hardware mapping to the controller I/O modules. They are not required to manage communication with the DPs by using I/O scanning.
Using several Communication Port Instances
To use one topological communication port with several PRM management instances (application), you need to instantiate the following intermediate templates (fan-out type application templates). Each instance of such template accepts links to n PRM management instances.
PRM management template
$PRMMgtM
$PRMMgtQ
Intermediate template
$EthAddM
$EthAddQ
EIO0000001114.15
601
The following figure shows an example of how to link two instances of the PRM management template to the instance of an intermediate template. During hardware mapping, the interface of the intermediate template instance is mapped to the interface of the Ethernet port of an M340 or M580 controller.
602
Implementing Communication
To implement communication between a controller, a PRM and its DP through
Modbus TCP by using I/O scanning, complete these steps.
Step Description
1
2
3
4
5
6
Create and configure a
with the I/O scanner enabled and its communication module. Configure the client
memory start and length parameters, page 376
of the communication module.
Create and configure, page 388
the PRM entity and its DPs (configure
IP address and other applicable properties).
NOTE: If the PRM communicates with a communication module that validates IP addresses based on the subnet mask, verify that the IP addresses of the PRM and the module belong to the same subnet.
Create an
Connect the communication module of the controller, page 399
to the
Ethernet network.
Connect the PRM entity, page 405
to the same Ethernet network.
In the Application Explorer , instantiate the following templates:
• The PRM management template. One for each PRM entity that is configured:
◦ $PRMMgtQ for a controller of the Quantum platform.
◦ $PRMMgtM for a controller of the M340 or M580 platform.
• One application template for each DP that you have configured
(for example, $ATV71PB for an Altivar 71 DP.
NOTE: If no specific template is available for a given DP, you can instantiate the generic application template $GenericDevice .
7
8
9
If you are using the $PRMMgtQ PRM management template, in the
Instance Editor , configure the StartMemoryHeap parameter.
Refer to the help of the template for details.
If you are using several PRM management instances, instantiate the corresponding
intermediate template, page 601
and link its instance to each PRM management instance by using the Asset Workspace
Editor .
NOTE: A link between the DP instance and the PRM management instance is not required.
Create a Control Participant project in the system.
10
11
12
Assign the necessary facets to the Control Participant project.
Create a Control executable in the project.
Map the Control executable of the project
to the controller entity, page
Stage
Configuration
Instantiation
Project
Definition
Mapping
(service)
EIO0000001114.15
Step
13
14
Description
Define the communication channel, page 424
and the device.
between the controller
Map to their respective topological counterpart (HO) by dragging from right to left:
• The EMPortChM or EMPortChQ interface.
• The PRMCTRLData interface.
• The PRMEthernetAddress interface.
• The interface of the device application facet to the interface of the topological DP device.
Stage
Mapping
(communication)
Mapping
(hardware)
To complete the other steps to engineer the system that contains the controller and the device, follow the system engineering life cycle described in this manual.
NOTE: Refer to the help of the various templates for configuration and setup details.
Peer to Peer Communication Through Modbus TCP Ethernet Implicit Messaging
Overview
Peer to peer communication allows you to share data between two or more
Control Participant projects by using the I/O scanner function for any pair of controllers that are configured in the topology of the system.
Network variables are used to exchange data between the Participant projects to which the controllers are mapped.
Client/server communication channels and network variable mappings are managed through
communication mapping, page 424 .
The build process creates the communication channels and allocates the mapped variables in the respective built Control Participant projects.
For more information about ways to create variables to share data, refer to the topic documenting the
creation of network variables, page 350 .
Implementing Peer to Peer Communication
To implement peer to peer communication through Modbus TCP implicit messaging by using I/O scanning, follow these steps.
Step Description
1 Create two Control projects in the same system.
2 Create a Control executable in each project.
3
4
5
6
7
8
Create the
network variables that will be exchanged, page 350
between the projects.
Create and configure two
with the necessary communication and I/O modules.
In the controller acting as client, enable the I/O scanner function.
In the controller acting as client, configure the client
memory start and length parameters, page 376
of the communication module.
In the controller acting as server, configure the server
memory start and length parameters, page 376
of the communication module.
NOTE: If the server communicates with a communication module that validates IP addresses based on the subnet mask client-side, verify that the IP addresses of the client/server modules belong to the same subnet.
Create an
Connect the communication module, page 401
of each controller to this
Ethernet network.
Stage
Project definition
Refinement
Configuration
EIO0000001114.15
603
Step Description
9
10
11
12
Map the Control executable of the owner project to the
acting as server.
Map the Control executable of the consumer project to the
acting as client.
Define the peer to peer
communication channels, page 424
between the controllers.
Map the network variables, page 435
to the peer to peer communication channels.
Stage
Mapping
(service)
Mapping
(communication)
To complete the other steps to implement the system, follow the system engineering life cycle described in this manual.
Communication by Using Modbus TCP Ethernet Explicit
Messaging
Communication with Devices by Using Modbus TCP Ethernet Explicit Messaging
Overview
This topic contains examples that use templates of the General Purpose library
Classic.
Supported Architectures
The software supports communication by using Modbus TCP Ethernet explicit messaging between common devices and supported controller platforms.
The process requires to instantiate the topological template of the Modbus TCP device, its application counterpart, and the appropriate application template of the communication port.
The communication port instance lets you configure the number of simultaneous requests that are sent per cycle. The configuration depends on the capacity of the communication module. For example, the various M580 CPU modules can send from 16 to 80 requests as client.
The topological device instance lets you assign an IP address to the device and connect it to the Ethernet network to which the controller is connected.
The IP address is exchanged with the application template of the device through the hardware mapping.
For a list of supported communication architectures, refer to the Device/
Communication Matrix (see EcoStruxure ™ Process Expert, Communication
Control Services User Guide).
NOTE: If no device-specific topological template is available for the device that you are using, use a
generic topological device template, page 391
and its application counterpart $EMClient .
Using several Communication Port Instances
To use one topological communication port with several communication port instances (application), you need to instantiate the following intermediate templates (fan-out type application templates). Each instance of such template accepts links to n communication port instances.
Communication port template
$EMPortM
$EMPortQ
Intermediate template
$EthAddM
$EthAddQ
604 EIO0000001114.15
The following figure shows an example of how to link two instances of the communication port template to the instance of an intermediate template. In the hardware mapping, the interface of the intermediate template instance is mapped to the interface of the Ethernet port of an M340 or M580 controller.
EIO0000001114.15
NOTE: The EthIPAddOut interface is not used for Modbus TCP explicit messaging.
605
The following figure shows an example of how to link two instances of the communication port template to the instance of an intermediate template. In the hardware mapping, the interface of the intermediate template instance is mapped to the interface of the Ethernet port of a Quantum controller.
606
NOTE: The EthChAddOut and EthIPAddOut interfaces are not used for
Modbus TCP explicit messaging.
Implementing Communication
To implement communication between a controller and a device by using Modbus
TCP Ethernet explicit messaging, follow these steps.
Step Description
1 Instantiate the process template that corresponds to the piece of equipment that you want the device to communicate with (for example,
$Motor).
2
3
4
Instantiate the Modbus TCP explicit messaging (EM) application template that corresponds to device that you want to use (for example, $TesysTEM).
NOTE: If no device-specific application template exists, use the
$EMClient template. Create as many instances of it as you have requests. For example, for one read and one write request you need two instances.
Instantiate the following communication port template:
• $EMPortQ for a controller of the Quantum platform.
• $EMPortM for a controller of the M340 or M580 platform.
Configure the communication port instance:
• The Control element lets you select a profile, which corresponds to the maximum number of simultaneous requests that the communication module supports.
• The corresponding LogicX service lets you optimize communication by reducing the number of simultaneous requests that are sent depending on your needs.
X corresponds to the last two digits of the profile you select under Control . For example, to EMPortM16 corresponds Loigc16 .
NOTE: If you select a profile that exceeds the capacity of the communication module, you cannot assign the communication port instance to the Control Participant project. Even if you reduce the number of requests under LogicX . For example, if you select
EMPortM32 for a NOC communication module, which can send a maximum of 16 requests simultaneously.
Stage
Instantiation
EIO0000001114.15
EIO0000001114.15
Step Description
5 If you are using one topological communication port with several communication port instances, instantiate the corresponding
intermediate template, page 604
.
6 Open the Asset Workspace Editor from the device instance and link to it:
• The port instance
• The process instance
NOTE: In case of a generic device, the device instance is the
$EMClient template instance.
NOTE: If you use an intermediate template instance, link it to the port instance.
Configure a controller and its communication module.
7
8
9
10
the corresponding topological device entity and configure its IP address and other applicable properties (for example,
$ETesysTHW) .
NOTE: If no device-specific topological template exists, use a generic device template.
Create an Ethernet network.
Connect the communication module of the controller and the topological device entity to the same Ethernet network.
11 Assign the Control facets of the process, device, and communication port instances to the Control Participant project so that the
is as follows:
1. The facet of the Modbus TCP explicit messaging device instance (for example, TesysTEM_1 ).
2. The facet of the communication port instance (for example,
EMPortQ_1 ).
12
13
14
15
Generate the project.
Map the executable of the Control Participant project
to the engine of the controller, page 423
.
Map the EMPortChM or EMPortChQ interface of the communication port instance (or of the intermediate template instance) to its topological counterpart.
Map the interface of the application instance of the device to the interface of the topological device instance.
Stage
Configuration
Assignment
Generation
Mapping
(service)
Mapping
(hardware)
To complete the other steps to engineer the system that contains the controller and the device, follow the system engineering life cycle described in this manual.
NOTE: Refer to the following topics for configuration and setup details of:
• Devices (see EcoStruxure ™ Process Expert, Device Control Services
User Guide)
• Ports (see EcoStruxure ™ Process Expert, Communication Control
Services User Guide)
Examples
The following examples illustrate the configuration of Modbus TCP explicit messaging to connect to 20 devices from clients of two different platforms with different communication capacities.
Example 1
Number of devices
Controller platform
Communication module
Communication port template
Communication port instance configuration ( PortSelection )
20
Modicon Quantum
140NOC77101
$EMPortQ
EMPortQ16
607
Example 1
Requests sent simultaneously ( SimultaneousSends )
Cycles to connect once to the number of devices
Example 2
Number of devices
Controller platform
Communication module
Communication port template
Communication port instance configuration ( PortSelection )
Requests sent simultaneously ( SimultaneousSends )
Cycles to connect once to the number of devices
10 in Logic16
2 (2 x 10)
20
Modicon M580
BMEP582020
$EMPortM
EMPortM32
20 in Logic32
1
Managing IP Address Changes
The topological templates of devices communicating by using Modbus TCP
Ethernet explicit messaging use a variable to define the IP address of the device.
During deployment, the templates set up the initial value of this variable, which is connected to the pin of the DFB implementing the device.
When you change the IP address of a device by changing the hardware mapping of the facet modeling the device and deploy the change by using the Deploy
Changes command, only the initial value, in this case the IP address, is changed online. The current value remains the same.
The IP address change becomes effective, either through a cold start of the controller or by replacing the current value of the variable in the animation table by the new initial value.
Communication by Using EtherNet/IP Explicit Messaging
Communication with Devices by Using EtherNet/IP Explicit Messaging
Overview
This section contains a procedure specifically aimed at managing communication between devices and M580 controllers by using EtherNet/IP explicit messaging. It contains examples that use templates of the General Purpose library Classic.
Supported Architectures
The software supports communication by using EtherNet/IP explicit messaging between common devices and CPU modules of M580 controllers or NOC communication modules.
The process requires to instantiate the topological template of the EtherNet/IP device, its application counterpart, and the appropriate application template of the communication port.
The communication port instance lets you configure the number of simultaneous requests that are sent per cycle. The configuration depends on the capacity of the communication module. For example, the various M580 CPU modules can send from 16 to 80 requests as client.
The topological device instance lets you assign an IP address to the device and connect it to the Ethernet network to which the controller is connected.
608 EIO0000001114.15
The IP address is exchanged with the application template of the device through the hardware mapping.
For a list of supported communication architectures, refer to the help of the
Schneider Electric libraries for EcoStruxure Process Expert.
NOTE: If no device-specific topological template is available for the device that you are using, use a
generic topological device template, page 391
and its application counterpart $EIPMClient .
Using several Communication Port Instances
To use one topological communication port with several communication port instances (application), you need to instantiate the following intermediate templates (fan-out type application templates). Each instance of such template accepts links to n communication port instances.
Communication port template
$EIPMPortM
Intermediate template
$EthAddM
The following figure shows an example of how to link two instances of the communication port template to the instance of an intermediate template. In the hardware mapping, the interface of the intermediate template instance is mapped to the interface of the Ethernet port of an M580 controller.
EIO0000001114.15
609
610
NOTE: The EthIPAddOut interface is not used.
Implementing Communication
To implement communication between a controller and a device by using
EtherNet/IP explicit messaging, follow these steps.
Step Description
1
2
3
Instantiate the EtherNet/IP messaging (EIPM) application template that corresponds to device that you want to use.
NOTE: If no device-specific application template exists, use the
$EIPMClient template. Create as many instances of it as you have requests. For example, for one read and one write request you need two instances.
Instantiate the $EIPMPortM EtherNet/IP communication port template and configure its parameters, such as:
• Port Selection of the Control element: Enables the corresponding
LogicX service where X represents the numeric part of the selected port function. It needs to correspond to the maximum number of simultaneous requests that the communication module supports.
For example, to EIPMPortM16 corresponds Loigc16 .
• Simultaneous Sends of the LogicX service to optimize communication by reducing the number of simultaneous requests that are sent.
If you are using one topological communication port with several communication port instances, instantiate the corresponding
intermediate template, page 609
.
4 Open the Asset Workspace Editor and link the communication port instance to:
• The device instance.
• The intermediate template instance (if used).
NOTE: In case of a generic device, the device instance is the
$EIPMClient template instance.
5
6
Configure an M580 controller and its communication module.
the corresponding topological device entity and configure its IP address and other applicable properties (for example,
$EIPMPMESWTHW) .
NOTE: If no device-specific topological template exists, use the
$EIPGenericDeviceHW) generic device template.
7
8
9
Create an Ethernet network.
Connect the communication module of the controller and the topological device entity to the same Ethernet network.
Assign the Control facets of the device, the communication port instances, and the intermediate template instance to the Control Participant project.
Generate the project.
10
11
12
13
Map the executable of the Control Participant project
to the engine of the controller, page 423 .
Map the EMPortChM interface of the communication port instance (or of the intermediate template instance) to its topological counterpart.
Map the interface of the application instance of the device to the interface of the topological device instance.
Stage
Instantiation
Configuration
Assignment
Generation
Mapping
(service)
Mapping
(hardware)
To complete the other steps to engineer the system that contains the controller and the device, follow the system engineering life cycle described in this manual.
NOTE: For configuration and setup details of devices and communication ports, refer to the help of the Schneider Electric libraries for EcoStruxure
Process Expert.
EIO0000001114.15
Managing IP Address Changes
The topological templates of devices communicating by using Modbus TCP
Ethernet and EtherNet/IP explicit messaging use a variable to define the IP address of the device.
During deployment, the templates set up the initial value of this variable, which is connected to the pin of the DFB implementing the device.
When you change the IP address of a device by changing the hardware mapping of the facet modeling the device and deploy the change by using the Deploy
Changes command, only the initial value, in this case the IP address, is changed online. The current value remains the same.
The IP address change becomes effective, either through a cold start of the controller or by replacing the current value of the variable in the animation table by the new initial value.
Communication Through Modbus Explicit Messaging
Overview
This section contains a procedure describing how to manage communication between devices and M340 or Quantum controllers through Modbus explicit messaging.
It also contains a set of four examples illustrating how to use Modbus serial communication templates and do the required hardware mapping. Each example uses a different architecture based on the M580 platform. The examples use templates of the General Purpose library Classic.
Refer to the example overview and select the one that applies to your situation.
From there, a link allows you to jump directly to the topic describing it.
Communication with Devices Through Modbus Explicit Messaging
About Communication Port Templates for Modbus Explicit
Messaging
The software supports communication through Modbus explicit messaging between common devices and various controller platforms by using specific communication templates.
Controller platform
Modicon M580
Communication module
NOM (1) communication module in the local rack.
NOM (1) communication module in a drop.
Modicon M340
Modicon
Quantum
NOM communication module in the local rack.
NOM communication module in an X80 drop.
(1) For example, BMXNOM0200.2 communication module
Communication port template
$MBPortM
$MBPortM58X80
$MBPortM
$MBPortQX80
Communication through an Ethernet port of the controller is also supported.
For a list of supported communication architectures, refer to the help of the
Schneider Electric libraries for EcoStruxure Process Expert.
NOTE: If no device-specific application template is available for the device that you are using, use the $MBClient template.
EIO0000001114.15
611
612
About Intermediate Templates
Intermediate templates are used when more than one communication port instance is used according to the following rules:
• $MBAddM : When a physical communication module (NOC, NOE, or NOM) needs to pass its port address to more than one communication port instance.
Use one template per physical communication port.
This can be case when you are linking more devices to a communication port instance than this instance can handle requests per cycle. For example, The
DFB of the $MBPortM58X80 communication port template can send a maximum of 4 simultaneous requests per cycle. If you want to send 10 requests per cycle, you need to use 3 instances of the $MBPortM58X80 template. These 3 instances are linked to an instance of the $MBAddM template.
• $EthAddM : When either of these conditions is fulfilled:
◦ A communication module (CPU, NOC, or NOE) needs to pass its Ethernet port address to more than one communication port instance.
◦ A CRA module needs to pass its IP address to more than one communication port instance.
The intermediate templates allow grouping the interfaces coming from several communication port instances to connect them to the corresponding interfaces of the topology. This is because a 1 to N mapping is not possible for topological mapping interfaces.
Together, the $MBAddM and $EthAddM templates expose the same interfaces as one $MBPortM58X80 template.
The table indicates which intermediate templates to instantiate depending on the communication port template that is used and also indicates the data that is transferred to the communication port instance.
Communication port template
$MBPortM
Intermediate template
$MBAddM
Transferred address
$MBPortM58X80
$MBPortQX80
$MBAddM
$EthAddM
$MBAddM
$EthAddQ
Port address of NOM communication module.
Port address of NOM communication module.
Port address of M580 CPU or NOC communication module.
IP address of the CRA module.
Port address of NOM communication module.
Port address of Quantum CPU or NOC communication module.
IP address of the CRA module.
The following figures illustrate the transfer of data between the topology and the application in various scenarios.
EIO0000001114.15
Multiple communication port instances per physical NOM port. In this case, only one NOM port is used and located in a drop.
One communication port instance per physical NOM port. In this case, the two
NOM ports are located in the same drop.
EIO0000001114.15
613
One communication port instance per physical NOM port. In this case, the two
NOM ports are located in separate drops.
614
Implementing Communication with Controllers Through
Modbus Port
To implement communication between an M580, M340, or Quantum controller with Modbus port and devices through Modbus explicit messaging, follow these steps.
Step Description
1 Instantiate the process template that corresponds to the piece of equipment that you want the device to communicate with (for example,
$Motor).
2 Instantiate a Modbus explicit messaging application template that corresponds to the device that you want to use (for example,
$TesysTMB), and configure its Modbus address.
NOTE: If no device-specific application template exists, use the
$MBClient template. Create as many instances of it as you have requests. For example, for one read and one write request you need two instances.
Instantiate the corresponding
communication port template, page 611 .
3
4
5
If you are using one topological communication port with several communication port instances, instantiate the corresponding
intermediate template, page 612
.
Open the Asset Workspace Editor and link the device instance to the communication port and the process instance.
NOTE: In case of a generic device, the device instance is the
$MBClient template instance.
6
7
8
Configure the controller with a Modbus port as master.
Assign the Control facets of the process, device, and communication port instances to the Control Participant project so that the
is as follows:
1. The facet of the Modbus explicit messaging device instance (for example, TesysTMB_1 ).
2. The facet of the communication port instance (for example,
MBPort58X80_1 ).
Generate the project.
Stage
Instantiation
Configuration
Assignment
Generation
EIO0000001114.15
Step Description
9
10
Map the executable of the Control Participant project to the engine of the controller.
If the communication module is in the local rack, map by dragging from right to left:
• The EMPortChM or EMPortChQ interface to its topological counterpart.
• The MBPortChM or MBPortChQ interface to the interface of the
NOM module of the drop.
If the communication module is in a drop, in addition, map by dragging from right to left:
• The CRAIPAddress interface to its topological counterpart.
Stage
Mapping
(service)
Mapping
(hardware)
To complete the other steps to engineer the system, follow the system engineering life cycle described in this manual.
NOTE: For details on Modbus technology, refer to the help of the Schneider
Electric libraries for EcoStruxure Process Expert.
Implementing Communication with Controllers Through
Ethernet Port
To implement communication between an M340, M580, or Quantum controller with Ethernet port and devices through Modbus explicit messaging, follow these steps.
6
7
8
Step Description
1 Instantiate the process template that corresponds to the piece of equipment that you want the device to communicate with (for example,
$Motor).
2
3
4
5
Instantiate a Modbus explicit messaging application template that corresponds to the device that you want to use (for example,
$TesysTMB), and configure the Modbus address.
NOTE: If no device-specific application template exists, use the
$MBClient template. Create as many instances of it as you have requests. For example, for one read and one write request you need two instances.
Instantiate the following communication port templates:
• Gateway template $EGtwMB .
• $EMPortM for a controller of the M340 or M580 platform.
• $EMPortQ for a controller of the Quantum platform.
Open the Asset Workspace Editor and link the device instance to the gateway and the process instances.
NOTE: In case of a generic device, the device instance is the
$MBClient template instance.
In the Asset Workspace Editor , link the gateway instance to the port instance.
Create an Ethernet network.
Configure Ethernet communication of the controller.
9
10
Connect the communication module of the controller to the Ethernet network.
Assign the Control facets of the process, device, and communication port instances to the Control Participant project so that the
is as follows:
1. The facet of the Modbus explicit messaging device instance (for example, TesysTMB_1 ).
2. The facet of the gateway instance (for example, EGtwMB_1 ).
3. The facet of the communication port instance (for example,
EMPortM_1 ).
Generate the project.
Stage
Instantiation
Configuration
Assignment
Generation
EIO0000001114.15
615
Step Description
11
12
Map the executable of the Control Participant project to the engine of the controller.
Map the EMPortChM or EMPortChQ interface of the communication port instance (CO) to its topological counterpart (HO).
Stage
Mapping
(service)
Mapping
(hardware)
To complete the other steps to implement the system that contains the controller and devices, follow the system engineering life cycle described in this manual.
NOTE: For configuration and setup details of gateways, refer to the help of the
Schneider Electric libraries for EcoStruxure Process Expert.
Example Overview
Supported Architectures
These examples are based on a controller of the M580 platform configured with one BMENOC0301.2 communication module.
They can be used also for controllers of the Quantum platform by using the corresponding templates with the Q variant (for example, $EthAddQ or
$MBPortQX80 ).
NOTE: The examples are not meant to represent a functional system. Only the elements that are relevant for the examples are configured and illustrated.
Default identifiers have been edited to be more comprehensible.
About Communication Port Templates for Modbus Explicit
Messaging
Various
Modbus serial communication port templates, page 611
exist depending on the architecture, which contains the BMXNOM0200 communication module and its location.
When the communication module is located in a drop, the $MBPortM58X80 template is used. Its instance exposes three mapping interfaces ( HW Interface column) to transfer the required data to the process objects:
• MBPortChM : The port address of the NOM communication module.
• EMPortChM : The port address of the CPU or NOC communication module.
• CRAIPAddress : The IP address of the CRA module.
Instantiate one $MBPortM58X80 template for each physical communication port used. When you need several communication port templates, use also
intermediate templates, page 612 .
616 EIO0000001114.15
The $MBPortM58X80 template allows mapping with the topology, which exposes the following interfaces in the
Hardware Mapping Editor when the NOM communication module is located in a drop.
1 Port address of the NOC communication module in the local rack
2 IP address of the CRA module
3 Port address of the NOM communication module when the NOM port is configured for Modbus link
Example A
The table indicates the specifics of this example in terms of remote drop configuration and application objects used.
M580 remote drop configuration Application objects
1 BMXNOM0200 communication module.
2 devices communicating through 1 communication port.
Example description
EIO0000001114.15
Example B
The table indicates the specifics of this example in terms of drop configuration and application objects used.
M580 remote drop configuration Application objects
1 BMXNOM0200 communication module.
2 devices, each communicating through
1 communication port (2 ports total).
Example description
617
Example C
The table indicates the specifics of this example in terms of drop configuration and application objects used.
M580 remote drop configuration
2 BMXNOM0200 communication modules
Application objects
For each NOM, 2 devices communicating through 1 communication port.
Example description
618
Example D
The table indicates the specifics of this example in terms of drop configuration and application objects used.
EIO0000001114.15
M580 remote drop configuration
2 drops with 1 BMXNOM0200 communication module in each.
Application objects
For each drop, 1 device communicating through 1 communication port.
Example description
Example A
Example Description
The table indicates the specifics of this example in terms of remote drop configuration and application objects used.
M580 remote drop configuration
1 BMXNOM0200 communication module.
Application objects
2 devices communicating through 1 communication port.
EIO0000001114.15
619
Configuration Stage
The following figure shows the controller configuration with the drop and the communication module.
620
Instantiation Stage
The following Instances are required to implement communication at the application level with two devices (TeSys T motor controllers) by using Modbus serial.
EIO0000001114.15
The MBPortM58X80_NOM1 Modbus serial communication port instance is to be used when the NOM communication module is located in the remote drop of an
M580 controller. In this example, one instance is created because one physical communication port is used.
Application Interface Links
The following links are created in the Asset Workspace Editor for the TeSys T devices.
The process instance ( Motor_n ), the device instance ( TesysTMB_n ), and the communication port instance ( MBPortM58X80_NOM1 ) are linked.
EIO0000001114.15
These steps result in the following links.
621
The communication port instance (MBPortM58X80_NOM1) passes the following data to the process instances:
• Port address of the NOC communication module
• IP address of the CRA module of the drop
• Port address of the NOM communication module
Control Facet Assignment
Facets of the instances are assigned to a Control Participant project in an FBD section.
622
Generation and Service Mapping
The Control Participant project is generated.
An executable is created in the Control Participant and mapped to the M580 controller.
Hardware Mapping
The Hardware Mapping Editor shows the following interfaces.
(Lines have been drawn to show the mappings that you need to do.)
EIO0000001114.15
Example B
NOTE: You do not need to map MBAdress interfaces (for example, of facet
TesysTMB_1_TesysT ).
Completing the System Engineering Life Cycle
Complete the creation of the system by performing the other steps of the system engineering life cycle.
Example Description
The table indicates the specifics of this example in terms of drop configuration and application objects used.
M580 remote drop configuration
1 BMXNOM0200 communication module.
Application objects
2 devices, each communicating through 1 communication port (2 ports total).
EIO0000001114.15
623
Configuration Stage
The following figure shows the controller configuration with the drop and the communication module.
624
Instantiation Stage
The following Instances are required to implement communication at the application level with two devices (a TeSys T motor controller and an Altivar variable speed drive) by using Modbus serial.
The MBPortM58X80_x Modbus serial communication port instances are to be used when the NOM communication module is located in the drop of an M580 controller. In this example, two instances are created, one for each physical communication port used.
Instances are grouped in two folders for clarity, one for each communication port instance.
EIO0000001114.15
These steps result in the following links.
The communication port instance (MBPortM58X80_NOM1) passes the following data to the process instances:
• Port address of the NOC communication module
• IP address of the CRA module of the drop
• Port address of the NOM communication module
Intermediate Template Instances
Only intermediate template $EthAddM_NOC_CRA is used because more than one communication port instance is used. It is common to both communication port instances. Intermediate template $MBAddM is not used because on each
NOM port, only one communication port instance is used.
Creating Links
The following links are created in the Asset Workspace Editor for the TeSys T device.
The process instance ( Motor_1 ), the device instance ( TesysTMB_1 ), and the communication port instance ( MBPortM58X80_Port1 ) are linked.
EIO0000001114.15
Then, link the MBPortM58X80_Port1 instance to both interfaces of the EthAddM_
NOC_CRA Ethernet intermediate template instance.
625
626
The EthAddM_NOC_CRA instance passes the NOC port address as well as the
IP address of the BMECRA312 module to the communication port instance.
Similarly, the following links are created in the Asset Workspace Editor for the
Altivar device.
The following figure show the existing links from the perspective of the intermediate template.
EIO0000001114.15
Control Facet Assignment
Facets of the instances are assigned to a Control Participant project in two separate FBD sections.
Folder B is assigned to FBDSection_1 .
Folder B_2 is assigned to FBDSection_2 .
EIO0000001114.15
Generation and Service Mapping
The Control Participant project is generated.
An executable is created in the Control Participant and mapped to the M580 controller.
Hardware Mapping
The Hardware Mapping Editor shows the following interfaces.
(Lines have been drawn to show the mappings that you need to do.)
627
Example C
NOTE: You do not need to map MBAdress interfaces (for example, of facet
TesysTMB_1_TesysT ).
Completing the System Engineering Life Cycle
Complete the creation of the system by performing the other steps of the system engineering life cycle.
Example Description
The table indicates the specifics of this example in terms of drop configuration and application objects used.
M580 remote drop configuration
2 BMXNOM0200 communication modules
Application objects
For each NOM, 2 devices communicating through 1 communication port.
628
Configuration Stage
The following figure shows the controller configuration with the drop and the communication module.
EIO0000001114.15
EIO0000001114.15
Instantiation Stage
The following Instances are required to implement communication at the application level with four devices (two TeSys T motor controllers and two Altivar variable speed drives) by using Modbus serial.
The MBPortM58X80_x Modbus serial communication port instances are to be used when the NOM communication module is located in the drop of an M580 controller. In this example, two instances are created, one for each physical communication port used.
Instances are grouped in two folders for clarity, one for each communication port instance.
629
630
These steps result in the following links.
The communication port instance (MBPortM58X80_NOM1) passes the following data to the process instances:
• Port address of the NOC communication module
• IP address of the CRA module of the drop
• Port address of the NOM communication module
Intermediate Template Instances
Only intermediate template $EthAddM_NOC_CRA is used because more than one communication port instance is used. It is common to both communication port instances. Intermediate template $MBAddM is not used because on each
NOM port, only one communication port instance is used.
Application Interface Links
The following links are created in the Asset Workspace Editor for both TeSys T devices.
EIO0000001114.15
Then, link the communication port instance MBPortM58X80_NOM1 , which communicates with the NOM communication module located in drop 1 to both interfaces of the intermediate template instance EthAddM_NOC_CRA .
EIO0000001114.15
The EthAddM_NOC_CRA instance passes the physical NOC port address as well as the IP address of the BMECRA312 module to the first communication port instance.
Similarly, the following links are created in the Asset Workspace Editor for both
Altivar devices.
631
Proceed similarly with the communication port instance MBPortM58X80_NOM2 , which communicates with the NOM communication module located in drop 2 by linking it to both interfaces of the intermediate template instance EthAddM_NOC_
CRA .
632
The EthAddM_NOC_CRA instance passes the physical NOC port address as well as the IP address of the BMECRA312 module to the second communication port instance.
The figure shows the existing links from the perspective of the intermediate template.
EIO0000001114.15
Control Facet Assignment
Facets of the instances are assigned to a Control Participant project in two separate FBD sections.
Folder C is assigned to FBDSection_1 .
Folder C_2 is assigned to FBDSection_2 .
EIO0000001114.15
Generation and Service Mapping
The Control Participant project is generated.
An executable is created in the Control Participant and mapped to the M580 controller.
633
Hardware Mapping
The Hardware Mapping Editor shows the following interfaces.
(Lines have been drawn to show the mappings that you need to do.)
Example D
NOTE: You do not need to map MBAdress interfaces (for example, of facet
TesysTMB_10_TesysT ).
Completing the System Engineering Life Cycle
Complete the creation of the system by performing the other steps of the system engineering life cycle.
Example Description
The table indicates the specifics of this example in terms of drop configuration and application objects used.
M580 remote drop configuration
2 drops with 1 BMXNOM0200 communication module in each.
Application objects
For each drop, 1 device communicating through
1 communication port.
634 EIO0000001114.15
Configuration Stage
The following figure shows the controller configuration with the drop and the communication module.
EIO0000001114.15
Instantiation Stage
The following Instances are required to implement communication at the application level with two devices (a TeSys T motor controller and an Altivar variable speed drive) by using Modbus serial.
The MBPortM58X80_x Modbus serial communication port instance are to be used when the NOM communication module is located in the drop of an M580 controller. In this example, two instances are created, one for each physical communication port used.
Instances are grouped in two folders for clarity, one for each communication port instance.
635
These steps result in the following links.
The communication port instance (MBPortM58X80_NOM1) passes the following data to the process instances:
• Port address of the NOC communication module
• IP address of the CRA module of the drop
• Port address of the NOM communication module
Intermediate Template Instances
Only intermediate template $EthAddM_NOC_CRA is used because more than one communication port instance is used. It is common to both communication port instances. Intermediate template $MBAddM is not used because on each
NOM port, only one communication port instance is used.
Application Interface Links
The following links are created in the Asset Workspace Editor for the TeSys T devices.
The process instance ( Motor_1 ), the device instance ( TesysTMB_1 ), and the communication port instance ( MBPortM58X80_NOM1 ) are linked.
636
Then, link the MBPortM58X80_NOM1 instance to the EthPortAddOut interface of the EthAddM_NOC intermediate template instance.
EIO0000001114.15
Similarly, the process instance ( Motor_2 ), the device instance ( ATV61MB_2 ), and the communication port instance ( MBPortM58X80_NOM2 ) are linked.
Then, link the MBPortM58X80_NOM2 instance to the EthPortAddOut interface of the EthAddM_NOC intermediate template instance.
These steps result in the following links.
EIO0000001114.15
The communication port instances ( MBPortM58X80_x ) pass the following data to the process instances:
• IP address of the CRA module of each drop
637
638
• Port address of the NOM communication module of each drop
The intermediate template instance ( EthAddM_NOC ) passes the following data to the process instances:
• Port address of the NOC communication module in the local rack
Control Facet Assignment
Facets of the instances are assigned to a Control Participant project in two separate FBD sections.
Folder D is assigned to FBDSection_1 .
Folder D_2 is assigned to FBDSection_2 .
Generation and Service Mapping
The Control Participant project is generated.
An executable is created in the Control Participant and mapped to the M580 controller.
Hardware Mapping
The Hardware Mapping Editor shows the following interfaces.
(Lines have been drawn to show the mappings that you need to do.)
NOTE: You do not need to map MBAdress interfaces (for example, of facet
TesysTMB_1_TesysT ).
Completing the System Engineering Life Cycle
Complete the creation of the system by performing the other steps of the system engineering life cycle.
EIO0000001114.15
Monitoring Modbus Device Data Directly from Supervision
Monitoring Modbus Device Data Directly from Supervision
Overview
This topic provides specific procedures to help you implement connectivity between Modbus TCP and Modbus serial devices and the Supervision infrastructure that is defined in the system.
For Modbus TCP devices, you can use the OPC or OPC UA driver.
This allows, for example, monitoring additional Modbus device variables without adding load to the controller.
The implementation is possible for the following topological entities:
• Modbus TCP I/O devices.
• STB islands.
• PROFIBUS remote masters (PRMs).
• Third-party I/O devices modeled by using the generic topological device template.
It also allows connecting Modbus serial devices by using the generic Modbus TCP
I/O device acting as gateway.
The implementation supplements the engineering effort to set up communication between the controller and Modbus devices and to operate these devices from the runtime. However, it does not use the application control module templates that come into play in the usual system engineering life cycle but requires creating your own application objects by using Supervision data
.
By following the steps described in this topic, the software generates Supervision tags for variables to be monitored based on the application objects that you have created.
Implementing Monitoring of Modbus TCP Device Data
The table describes the specific steps that you need to perform to be able to monitor data of Modbus TCP devices directly from the Supervision infrastructure.
It is assumed that the required topological entities, Control and Supervision
Participant projects, the application instances, assignments, and mappings to implement
communication with Modbus TCP devices, page 597
already exist.
Step
1
Description
Instantiate a Supervision data facet template for each variable of a Modbus
TCP device that you want to monitor from Supervision. You can use the following templates:
• $VariableTag_CD
• $AdvancedAlarm_CD
• $TrendTag_CD
Configure the identifiers of each instance so that the relationship with the corresponding Modbus TCP device can be easily seen.
NOTE: Select Facets as filter in the Browser pane.
2 Configure instances of $VariableTag_CD as follows:
• Addr parameter ( Configuration category):
◦ For the OPC driver: Address of the variable by using the format
Alias!%MW<i> .
For example, ATV61IOD_IODEVICE_1!%MW3233 .
◦ For the OPC UA driver: Name of the variable in the symbol table.
• Type parameter ( Configuration category): Data type of the variable.
For example, UINT.
NOTE: Alternatively, for OPC, you can specify the address for the device by adding an appropriate entry in the citect.ini file. For details,
Stage
Instantiation
EIO0000001114.15
639
640
Step
Description Stage
3
4
5 refer to OPC Access Path Parameters in the OPC Driver topic of the
Driver Reference Help , which you can open from the Windows ® Start menu or from within the Supervision Participant ( Topology \ I/O
Devices ).
If you are using trend tags, open the Asset Workspace Editor and link the trend tag instance to the variable tag instance so that the instance status becomes valid.
Create additional tag containers, page 263 ; one for each Modbus TCP
device that you want to monitor from Supervision and configure Protocol as either OPC or OPC UA.
Create a dedicated communication board, page 234
and configure Type as either OPC or OPC UA.
Create a communication port for each Modbus TCP device.
Project
Definition
(Supervision)
6
7
8
Create an I/O device, page 232
for each tag container and configure the following parameters:
• Address :
◦ For the OPC driver: Enter Schneider-Aut.OFS
, which corresponds to the Prog ID of the OFS server.
◦ For the OPC UA driver: The address parameter is not used.
• TagContainers : Associate each I/O device to a separate tag container.
• Ports
Assign the Supervision facets related to each device to the corresponding tag container.
For example, if you have created two Modbus TCP devices ( EATV71HW_1 and ETesystHW_1 ) and for each device, you have create one variable tag instance ( ATV71_Var1 and TesysT_Var1 ), then you need to assign:
• ATV71_Var1 to TagContainer_ATV71
• TesysT_Var1 to TagContainer_TesysT
9 Generate the project.
10 In the Communication Mapping
tab, page 460 , perform the following
additional mappings for each I/O device that you have created for a Modbus
TCP device:
• Select the corresponding topological entity (the Modbus TCP device).
• Select its communication service (MBTCPServiceServer or devicespecific service).
• Verify the Modbus Unit ID value for the device and modify it as needed
(refer to the user manual of the device).
11 When using the OPC UA driver, you must create a symbol table (.csv) where the variable name and data type correspond to the values that you have entered for the Addr and Type parameters (see step 2).
For details, refer to Modbus Device Address Space in the help of
EcoStruxure OPC UA Server Expert.
12 Associate the symbol table file to the device alias by using the Symbol table file browse button.
Verify that Symbol table is selected under Preload settings .
Assignment
Generation
Mapping
(communication mapping for
Supervision executables)
EcoStruxure
OPC UA
Server Expert
Configuration
Tool
To complete the other steps to engineer the system, follow the system engineering life cycle described in this manual.
Implementing Monitoring of Modbus Serial Device Data
The table describes the specific steps that you need to perform to be able to monitor data of Modbus serial devices directly from the Supervision infrastructure by using the OPC driver. It is assumed that the required topological entities,
Control and Supervision Participant projects, the application instances, assignments, and mappings to implement
communication with devices by using
Modbus explicit messaging, page 611
already exist.
EIO0000001114.15
Step Description
1
2
3
4
5
6
7
8
9
10
11
12
Create a Modbus TCP device entity by using the $EGenericDeviceHW
. The entity acts as a gateway.
Configure the IPAddress and SubnetMask parameters of the gateway entity.
If you are already using an application template of the Modbus serial device (for example, an instance of $ATV71MB ) and have linked it to an instance of the $EGtwMB gateway application template, enter the
GatewayAdd parameter value of the gateway instance. Otherwise, enter the IP address of the gateway.
NOTE: Enter values for the read/write length and address parameters only if you are going to implement I/O scanning with the gateway entity.
Connect the gateway entity to the same Ethernet network to which the station node that is mapped to the I/O server is connected.
Instantiate a Supervision data facet template for each variable of a Modbus serial device that you want to monitor from Supervision. You can use the following templates:
• $VariableTag_CD
• $AdvancedAlarm_CD
• $TrendTag_CD
Configure the identifiers of each instance so that the relationship with the corresponding Modbus serial device can be easily seen.
NOTE: Select Facets as filter in the Browser pane.
If you are using trend tags, open the Asset Workspace Editor and link the trend tag instance to the variable tag instance so that the instance status becomes valid.
Configure instances of $VariableTag_CD as follows:
• Addr parameter ( Configuration category): Address of the variable by using the format Alias!%MW<i> .
For example, ATV61IOD_IODEVICE_1!%MW3233 .
• Type parameter ( Configuration category): Data type of the variable.
For example, UINT for ATV61IOD_IODEVICE_1%MW3233 .
NOTE: Alternatively, you can specify the address for the device by adding an appropriate entry in the citect.ini file. For details, refer to
OPC Access Path Parameters in the OPC Driver topic of the Driver
Reference Help , which you can open from the Windows ® Start menu or from within the Supervision Participant ( Topology \ I/O Devices ).
Create additional tag containers, page 263 ; one for each Modbus serial
device that you want to monitor from Supervision.
Configure Protocol as OPC .
Create a dedicated communication board, page 234
and configure Type as
OPC .
Create a communication port for each Modbus TCP device.
Create an I/O device, page 232
for each tag container and configure the following parameters:
• Address : Enter Schneider-Aut.OFS
, which corresponds to the Prog
ID of the OFS server.
• TagContainers : Associate each I/O device to a separate tag container.
• Ports
Assign the Supervision facets related to each device to the corresponding tag container.
For example, if you want to monitor two Modbus serial devices and for each device, you have create one variable tag instance ( ATV71MB_Var1 and TesysTMB_Var1 ), then you need to assign:
• ATV71MB_Var1 to TagContainer_ATV71MB
• TesysT_Var1 to TagContainer_TesysT
Generate the project.
Stage
Configuration
Instantiation
Project
Definition
(Supervision)
Assignment
Generation
EIO0000001114.15
641
Step Description
13
14
In the Communication Mapping
, perform the following additional mappings for the first I/O device that you have created for a
Modbus serial device:
• Select the gateway as topological entity (instance of
$EGenericDeviceHW ).
• Select its communication service (MBTCPServiceServer).
• Enter the Modbus Unit ID value for the device. If you have already configured an application template of the device (for example, an instance of $ATV71MB ), enter the ModbusAddress parameter value of the instance. Otherwise, enter a unique serial slave ID for the device.
Repeat step 13 for each additional Modbus serial device by selecting the same gateway entity but entering a new Modbus Unit ID value.
Stage
Mapping
(communication mapping for
Supervision executables)
To complete the other steps to implement the system, follow the system engineering life cycle described in this manual.
Communication with Devices by Using a PROFIBUS Master
Module
Communication with Devices by Using a PROFIBUS Master Module
Overview
The topology supports the PMEPXM0100 PROFIBUS master module. The configuration of the module is performed partially in the Topology Explorer and completed by using the external ProSoft Configurator for Modicon. Additional steps need to be performed in various stages of the system engineering life cycle.
Prerequisites
• Read and understand the PMEPXM0100 ProSoft User Manual , which is located in the Prosoft Installer folder in the root of the EcoStruxure Process
Expert installation package.
• Install ProSoft Configurator for Modicon on a computer.
The installation files are in the Prosoft Installer folder.
• Share a folder with the virtual machine (see EcoStruxure ™ Process Expert,
Installation and Configuration Guide) to be able to import files into the Control
Participant project.
NOTE: For the latest version of the tool and the manual, visit www.se.com/en/ download .
Workflow
The table describes the workflow to integrate a PMEPXM0100 PROFIBUS master module and slave devices into a system by using a standalone or redundant M580 controller.
Step Description
1 Add a PMEPXM0100 PROFIBUS master module to an M580 standalone or redundant controller.
NOTE: For details, including steps that you need to perform when using a redundant controller, refer to the topic describing the configuration of the PMEPXM0100 PROFIBUS master module. (see
EcoStruxure ™ Process Expert, Control Participant Services, User
Guide)
2 If you have templates of PROFIBUS slave devices, create instances thereof and configure them as needed.
Stage
Configuration
Instantiation
642 EIO0000001114.15
Step Description
3
4
5
6
7
8
9
10
11
Stage
NOTE: If you want to use device templates of a Schneider Electric library (for example, $ATV71PB or $TeSysTPB ), refer to the specific procedure describing how to use them.
Assign the facets of application objects to the Control project and generate the project.
Assignment and
Generation
External With the help of the ProSoft Configurator for Modicon, configure the
PMEPXM0100 master and slave devices by following the steps described in the PMEPXM0100 ProSoft User Manual .
NOTE: In the Export EcoStruxure Control Expert Export Options dialog box select Enhanced for I/O Scan Mode and select the folder that is shared with the virtual machine as target location.
Refine the Control project and
create the device DDT variable, page 343
of the PMEPXM0100 module.
NOTE: If you are using a redundant controller, create both device DDT variables.
Copy the exported project file to the folder that is shared with the VM (see
EcoStruxure ™ Process Expert, Installation and Configuration Guide).
Import the exported project file by following the steps described in the
PMEPXM0100 ProSoft User Manual .
NOTE: To access the file in the Control Participant, browse to the folder shared with the VM by using the Network node and select the exported project file.
Analyze the Control project.
Build and deploy the Control project to the controller.
Refinement
–
Refinement
Build and
Deployment
External With the help of the ProSoft Configurator for Modicon, download the master and slave device configuration to the module by following the steps described in the PMEPXM0100 ProSoft User Manual .
Refine the deployed Control project online and follow the steps described in the PMEPXM0100 ProSoft User Manual to set the operating mode of the
PMEPXM0100 module.
Execution
To complete the other steps to engineer the system, follow the system engineering life cycle described in this manual.
EIO0000001114.15
643
Managing, Modifying, and Creating Templates
What’s in This Part
Overview
Creating, modifying, updating, replacing, or duplicating templates may affect the function of these templates and/or systems, and must be performed by qualified personnel.
Refer also to the topic containing information about template design good practices and key aspects (see EcoStruxure ™ Process Expert, Global Templates,
Reference Manual).
WARNING
LOSS OF CONTROL
After creating, updating, or modifying templates:
• Verify that templates generate correct addresses when their mapping interfaces are mapped by using the Hardware Mapping Editor .
• Perform a Failure Mode and Effects Analysis (FMEA) of the system that contains new, updated, or modified templates and apply preventive, detective controls before implementation.
• Provide a fallback state for undesired control events or sequences.
• Provide separate or redundant control paths wherever required.
• Supply appropriate parameters, particularly for limits.
• Review the implications of transmission delays and take actions to mitigate.
• Review the implications of communication link interruptions and take actions to mitigate.
• Provide independent paths for control functions (for example, emergency stop, over-limit conditions, and fault conditions) according to the safety analysis and applicable codes, and regulations.
• Apply local accident prevention and safety regulations and guidelines 1 .
• Test each implementation of a template for proper operation before placing it into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
1 For additional information, refer to NEMA ICS 1.1 (latest edition), Safety
Guidelines for the Application, Installation, and Maintenance of Solid State Control and to NEMA ICS 7.1 (latest edition), Safety Standards for Construction and
Guide for Selection, Installation and Operation of Adjustable-Speed Drive
Systems or their equivalent governing your particular location.
644 EIO0000001114.15
Global Templates Library
What’s in This Chapter
Overview
This chapter describes the Global Templates library, the tools that are available to manage it, and context menu commands.
Global Templates Explorer
Overview
The Global Templates Explorer shows the templates of the Global Templates library, which regroups the Schneider Electric libraries for EcoStruxure Process
Expert that are installed (for example, the Foundation Library, the General
Purpose Library) as well as templates that you create and/or import.
These templates are displayed in a folder structure and can be of the following types:
• Interface models
• Facet templates
• Composite templates
The Global Templates Explorer allows you to perform the following actions on
Global Templates:
• Browse Global Templates.
•
Export and import templates, page 675
.
•
Open template editors, page 653 .
•
Create copies of templates, page 677 .
• Create (see EcoStruxure ™ Process Expert, Global Templates, Reference
Manual) your own
and templates.
•
Update and replace templates, page 688 .
Opening the Global Templates Explorer
Open the Global Templates Explorer by clicking the Global Templates button in the
EIO0000001114.15
645
Global Templates Explorer
The following figure shows an example of the Global Templates Explorer window. The content of the folder structure may vary depending on the libraries that are installed.
2
3
4
Item
1
Description
Toolbox
. The pin button allows you to minimize the Toolbox pane to the left edge of the screen. Move the pointer above the Toolbox tab to display the pane. Click the pin button again to restore the pane.
Global Templates library root folder.
Tree view of the installed libraries. You can open parts of the tree view in new windows.
.
Global Templates Naming Convention
The Schneider Electric Global Templates follow a naming convention:
$NAME_XX
Where
• $ indicates that the template is provided by Schneider Electric.
• NAME is the name of the template
• _XX indicates the type of the template. Control module templates have no suffix.
NOTE: Some templates provided by Schneider Electric may not have the $ prefix to indicate that you can modify them to meet your specific requirements.
The table describes the suffixes that are used to identify types of Global
Templates.
Suffix
_UL
_UH
_UC
_CD
_CG
Description
Control logic facet template.
Control HMI facet template.
Control logic and HMI composite template.
Supervision data composite and facet templates.
Supervision genie composite and facet templates.
646 EIO0000001114.15
Suffix
_CS
_CR
_CC
Description
Supervision composite template.
Supervision server composite template.
Supervision client composite template.
Searching Global Templates
The search field of the Global Templates Explorer lets you find templates and folders by typing the entire or part of their identifier. You do not need to use wildcards. The search is not case-sensitive. Results are displayed as you type in a pane with columns. Your last three matching search keywords are stored and appear in a keyword menu. The stored keyword entries persist even after the system server is restarted.
For example, va returns templates and folders that contain va in their identifier, such as templates $Valve , $HValve_CD , and folder Advantys .
By default, results are displayed in ascending alphabetical order with folders shown first, templates next.
The results pane provides basic information on templates and remains open until you close it by clicking the close button. A tooltip provides additional information.
The following figure shows an example of the search results that can be shown when you enter sign in the search field.
EIO0000001114.15
Right-click a search result in the results pane to open a context menu with the following commands.
Command
Navigate
Open
Inspect
Read-Only
Edit
Description
• For a template: Opens/expands the containing folder and highlights the instance.
• For a folder: Expands the folder structure and selects the folder.
You can also double-click the item.
NOTE: If the template is hidden because a filter is applied, the template is not shown but the border of the folder containing the instance flashes briefly.
The command is available for folders only.
Opens a new Global Templates Explorer workspace and displays only the folder.
NOTE: Searches that you perform by using the search field of this workspace are limited to the contents of the folder.
These commands are available for templates only.
For a description of these commands, refer to the topic describing Global
Templates
647
You can
search results.
NOTE: Search results are not updated automatically if templates or folders were created, modified, or deleted in the meantime. You need to start over the search by clicking the search field and pressing Enter .
Global Templates Toolbox
The Toolbox contains the following base Global Templates, which you can use to
create new templates or modify, page 653
existing ones:
• Interface models
• Facet templates
• Composite templates
Templates are grouped in the following categories:
• Platform : Templates and interface models that are used at the platform level.
These templates can reference components of this category and/or of the other two categories.
• Control : Facet templates that encapsulate constituents of the Control
Participant. You can reference them inside composite templates.
• Supervision : Facet templates that encapsulate constituents of the
Supervision Participant. You can reference them inside composite templates.
The table describes the items that are in the Platform category.
Item
Composite Template
Composite Device IO and Device IO (facet templates)
Composite Generic and Generic templates)
(facet
Interface Model
Description
Generic template that you can use to:
• Reference facet templates and other composite templates.
• Build control module templates.
Topological templates that you can use to model devices and their decentralized I/O modules in the topology of the system:
• Devices (energy and motor devices, instrumentation...)
• STB island I/O modules
NOTE: You can use this type of template to model third-party devices in the topology of a system if they will be connected to the network of such a system as nodes.
Topological templates that you can use to model unknown devices in a generic manner.
Network
Object that you can define to create interfaces, which you can use to:
• Link to each other facet and/or composite templates referenced by a control module template during template creation.
• Expose connectors that allow linking instances to each other during instantiation.
Topological template that you can use to model the following types of networks that are used in the topology of a system:
• Ethernet
• Modbus
• CANopen
• PROFIBUS DP
• RIO S908
• RIO Ethernet
• Local bus of topological entities
648 EIO0000001114.15
Item
Composite Network
Device and Network
Device (facet templates)
Composite Station
Node and Station
Node (facet templates)
Description
Topological templates that you can use to model network devices that are used in the topology of a system (for example, switches, routers, gateways...).
Topological templates that you can use to model the hardware and software components of a workstation in the topology of a system:
• Network interface card (NIC)
• Citect SCADA software
• OPC Factory Server and OPC UA Server Expert software
• Control Expert software
• Platform and platform backup servers
The table describes the templates that are in the Control category.
Item
Composite
Controller and
Controller (facet templates)
HMI
Logic
Description
Topological templates that you can use to model controller hardware modules
(CPUs, power supplies, network cards, I/O modules, and so on) of supported platforms (see EcoStruxure ™ Process Expert, Control Participant Services,
User Guide).
NOTE: Do not use this type of template to model distributed I/O modules such as STB island I/O modules, for example in the topology of a system.
Use a Platform DeviceIO template instead.
Application Control facet template that you can use to model one operator screen.
Application Control facet template that you can use to encapsulate Control constituents to implement a specific function.
For example, you can encapsulate a DFB and one or more variables to manage on/off motor functions.
The table describes the templates that are in the Supervision category:
Item
Client Event
Data
Genie
Server Event
Description
Application client script facet template that you can use to create an event to be executed during runtime in the context of the Supervision client.
Application Supervision facet template that you can use to model tags and user interface messages required for runtime data acquisition.
Application Supervision facet template that you can use to encapsulate an animated graphic (genie), which is contained in a Citect SCADA
and which displays data of the associated control module during runtime.
Application server script facet template that you can use to create an event to be executed during runtime in the Supervision server.
Opening Items in a New Window
You can open part of a folder structure that appears in the Global Templates
Explorer in a new explorer window.
To open a folder structure in a new window, proceed as follows.
Step
1
Action
Drag the folder onto the tabs bar of the work area.
Result: The folder opens in a new window as a parent folder.
NOTE: If several work areas are open, you can drag the folder to the tabs bar of another work area.
EIO0000001114.15
649
The following figure shows an example where by expanding the sample General
Purpose Library folder and dragging the Process folder to the tabs bar, a new explorer window opens in which the Process folder is the parent folder of the structure.
Recovery Folder
When you start the system server, if the software detects missing references in templates, it creates the Recovery folder. You can see the folder in the Global
Templates Explorer .
This folder contains the templates that are missing.
This can be the case, for example, after migrating the database of an earlier version. If the database contains a template that is used by another template
(determined by using the Used By command) but you cannot locate this parent template by searching for it, most likely you can find it in the Recovery folder.
You can work with templates inside the Recovery folder like with any other templates by right-clicking them and selecting an
.
Global Templates Folders
Creating Global Templates Folders
To create a Global Templates folder, proceed as follows.
Step
1
2
Action
Right-click the Global Templates root folder or an existing folder in the Global
Templates Explorer and select Create Folder .
Result : It creates a folder with the identifier in edit mode and displays it in the tree view.
To change the identifier, type it; otherwise, press Enter to accept the default name.
Global Templates Folder Actions
Right-click a Global Templates folder to open a context menu with the following commands.
Command
Create
Folder
Create
Description
Creates a new folder and displays it in the tree view.
Opens a submenu that allows you to create in the folder any base composite and facet template, which is available in the Toolbox .
Copies the folder, any subfolders and their contents.
Pastes the items that you have copied last to a new location.
Opens the Export dialog box, which allows you to select which templates contained in the folder, including any subfolders you want to export to a file in .sbk
format.
650 EIO0000001114.15
Command
Delete
Rename
Description
Opens the Import dialog box, which allows you to select an export file in .sbk
format and displays the compatible contents that you can select for import.
Opens the Purge dialog box, which allows you to select templates to purge in the folder and any subfolder.
Deletes the folder and its contents from the database after you confirm the command.
The command is not available if the folder or any subfolder contains a template.
Lets you enter a new name for the folder.
The command is not available if the folder or any subfolder contains a template.
Global Templates
Global Templates Description
The following fields are displayed in a Global Templates folder in the tree view of the Global Templates Explorer .
Field
Identifier
Version
Type
Subtype
Valid
State
Description
Description
The fields come from the header of the composite/facet template or interface.
Refer to the following topics for a description of the fields for:
• Composite templates (see EcoStruxure ™ Process Expert, Global Templates,
Reference Manual)
• Facet templates (see EcoStruxure ™ Process Expert, Global Templates,
Reference Manual)
• Interface models (see EcoStruxure ™ Process Expert, Global Templates,
Reference Manual)
Global Templates Actions
Right-click a template in the Global Templates Explorer to open a context menu with the following commands.
Command Description
View Opens the template in the corresponding editor in view-only mode.
The editor allows you to view the composition of the template or interface.
NOTE: A password may be required to view a template.
State
Inspect
Opens the template in the corresponding editor in edit mode.
The editor allows you to view and modify the definition and composition of the template or interface.
NOTE: A password may be required to edit a template.
Opens a submenu that allows you to set the usability state (see EcoStruxure ™
Process Expert, Global Templates, Reference Manual) of the template to either
Obsolete or Deprecated .
The command is available only if:
• The template is used by an instance or referenced by another template.
• A higher version of the template exists.
• The usability state of the next highest version of the template is Approved .
Allows you top open the Used By , Dependencies Tree , or External References
in which you can view respectively:
• The templates that reference it.
• Templates that it references. For each reference you can view its interfaces.
• Systems in which an instance of the template exists.
EIO0000001114.15
651
Command Description
Locations Opens a submenu that allows you view where the template is located. If the template is present at more than one location:
• The current location is grayed out.
• You can click the other locations to open the folder and highlight the template.
Copies the template for pasting.
Remove
Opens the file in .sbk
Export format.
dialog box, which allows you to save the template data to an export
Removes the copy of the template.
Delete
The command is available only if
of the template exist.
When only one instance of the template remains, the command is replaced by Delete .
Deletes the template from the database after you confirm the command.
The command is not available if either condition is satisfied:
• The template is referenced by another template, which is not being deleted.
• The template is used by a facet of in a system.
Opens the Update dialog box, which allows you to create a new version of the template by using the latest version of any referenced child templates that exist in the
Global Templates library.
Opens the Duplicate window, which allows you to create, in a single step, a copy or new version of the template with the possibility to keep, duplicate, or replace any child template that is references.
652 EIO0000001114.15
Global Templates Editors
What’s in This Chapter
Opening Global Templates Editors................................................................ 653
Facet and Composite Template Editors ......................................................... 659
Common Template Editor Components ......................................................... 666
Overview
This chapter describes the Global Templates editors, which allow you to view and edit the entire definition of Global Templates. They also allow you to create new templates based on existing ones or by starting from empty base templates.
You can view and edit:
• Composite templates by using the Composite Editor .
• Facet templates by using the Facet Editor .
• Interface models and interfaces by using the Interface Editor .
Starting from the control module template level, you can drill down through the entire composition of the template. At each level, you can view dependencies and which templates reference the one you are viewing or editing.
NOTE: Some of the commands that are described in this chapter may not be available when you open a template editor in read-only mode.
Opening Global Templates Editors
Opening Global Templates Editors
Overview
Modifying Schneider Electric Global Templates or templates created by users may affect the function of these templates and must be performed by qualified personnel. Before proceeding, refer to the
Overview of this part, page 644 .
Opening Global Templates Editors
To open a Global Templates editor, you need to open a template. You cannot open a Global Templates editor without opening a template either in read-only or editing mode.
Step
1
2
Action
In the tree view of the Global Templates Explorer , open the folder that contains the template that you want to view or edit.
Right-click the template and select:
• Read-only to open the template in the corresponding editor in read-only mode.
This mode does not allow you to change the definition of the template.
The background of the workspace has a light shade of gray to distinguish it from the editing mode.
• Edit to open the template in the corresponding editor in editing mode.This mode allows you to modify the entire definition of the template.
NOTE: Double-clicking the template opens the corresponding editor in read-only mode by default.
NOTE: From the Global Templates explorer , you can also look up templates by entering a key word in the
search field, page 646 . In the list of results, right-
click the template and select Read-only or Edit . The software opens the selected template in the corresponding editor in either mode.
EIO0000001114.15
653
Working Copy of Templates
When you open a template in read-only or editing mode, the software creates a temporary working copy of the template with the same identifier and a specific version (see EcoStruxure ™ Process Expert, Global Templates, Reference
Manual). It removes this working copy when you close the template editor.
Interface Editor
Interface Editor
Introduction
The graphical Interface Editor allows you to manage the entire definition of interface models and interfaces.
This topic describes the panes, toolbars, and menus of the Interface Editor .
Certain menus and commands may be available only in editing mode.
NOTE: This topic provides information on the Interface Editor user interface; it does not provide information on the definition of interface models or interfaces (see EcoStruxure ™ Process Expert, Global Templates, Reference
Manual).
654 EIO0000001114.15
Interface Editor
The following figure shows an example of the Interface Editor in edit mode.
EIO0000001114.15
6
7
4
5
8
2
3
Item
1
9
Description
Graphical representation of role A of the interface
Graphical representation of role B of the interface
Interface Header pane
Toolbox pane
Elements and Rules panes for role A of the interface
Elements and Rules panes for role B of the interface
Button to show the interface Browser pane
Editor toolbar containing commands that apply to the interface being viewed or edited
Workspace. You can use the mouse to
.
Editor Panes
The Interface Editor uses various panes to group properties and data that are related. The table describes the purpose of the panes.
Pane
Header
Toolbox
Elements
Rules
Browser
Description
Allows you to view and/or edit general properties of the interface.
Allows you to browse and select transformation functions (see
EcoStruxure ™ Process Expert, Global Templates, Reference Manual) to be used in the template.
Allows you to view, create, and modify elements of a role of the interface.
Allows you to view, create, and modify rules for the elements of a role of the interface.
Allows you to search interface models and interfaces that are available in the Global Templates library.
Move the pointer over the Browser tab to display the pane. Click the pin button to toggle between minimized and visible pane view.
NOTE: The pane is available only in editing mode.
655
656
Pane
Used By (1)
Locations (1)
Description
Allows you to view the templates and interfaces that reference the interface, which is open in the editor. You can right-click a template or interface in the Used By pane to open it in a new editor. You can also view its
or which other templates reference it.
Allows you to view the path to the interface and its
Right-click an entry and select Open Reference Container to open the corresponding folder in the Global Templates explorer.
Changes Log (1) Keeps track of changes that are made to the interface and saved. The pane indicates:
• The action that was performed.
• The state of the interface after the change.
• The mandatory description of changes that is entered when the interface is saved.
• The version of the interface after the change.
• The user name of the user logged in to the engineering client.
(1) Use the corresponding command in the editor menu to open the pane.
NOTE: For information on working with panes, refer to the topic describing the
engineering client workspace, page 85
.
Additional Information
The list indicates where you can find a detailed description of the contents of the
Interface Editor panes:
• Header definition (see EcoStruxure ™ Process Expert, Global Templates,
Reference Manual) and header common definition (see EcoStruxure ™
Process Expert, Global Templates, Reference Manual) (shared among interface models, facet, and composite templates).
• Elements definition (see EcoStruxure ™ Process Expert, Global Templates,
Reference Manual).
• Rules definition editors (see EcoStruxure ™ Process Expert, Global
Templates, Reference Manual).
• Interface toolbox (see EcoStruxure ™ Process Expert, Global Templates,
Reference Manual).
Editor Toolbar
The figure shows the toolbar that is located in the top right-hand corner of the
Interface Editor .
Item
1
2
3
Description
Edit button.
Switches the editor from read-only to editing mode.
Save button.
Opens the Save dialog box.
For more information, refer to the topic describing how to
save changes in templates, page 675 .
Save as button.
Opens the Save as dialog box.
For more information, refer to the topic describing how to
save changes in templates, page 675 .
EIO0000001114.15
Item
4
5
Description
Undo and redo buttons.
Lets you undo and redo most actions.
Opens the editor menu that contains editor-specific commands.
Editor Menu
The table describes the commands that are available in the editor menu of the
Interface Editor .
Command
New...
View
Save
Save As
Export
Show Changes Log
Close
Used By
Locations
Standard
Backup
Various image file formats
Description
Opens the Global Templates dialog box, which contains the same base templates as the Toolbox of the Global Templates explorer. It allows you to create a new template in one or more existing folders of the Global Templates library and open it in edit mode in the corresponding editor.
For more information, refer to the topic describing how to create templates (see EcoStruxure ™ Process Expert, Global Templates,
Reference Manual).
The commands allow you to bring the corresponding pane to the front.
If the pane is closed, the command opens it.
For a description of the panes, refer to the topic describing template editor panes.
Save button.
Opens the Save dialog box.
For more information, refer to the topic describing how to
save changes in templates, page 675 .
Save as button.
Opens the Save As dialog box.
For more information, refer to the topic describing how to
save changes in templates, page 675 .
Opens the Export window, which allows you to export the interface definition to file (.sbk).
You can only export an interface if you have saved changes.
For more information on export feature, refer to the topic describing
Each command opens a Save dialog box, which allows you to create an image file with the corresponding file extension. The image captures the contents of the workspace as if it were shown with the Fit to content display ratio.
Panes and toolbars are not captured.
Opens the Changes Log
.
Closes the template editor.
If you have made changes, opens the Save dialog box.
For more information, refer to the topic describing how to
save changes in templates, page 675 .
Workspace Actions
Right-click an empty area of the workspace to open a context menu with the following commands.
EIO0000001114.15
657
658
When you select...
Inspect
The software...
Show changes log opens a submenu with the
and
commands.
opens the
Interface and Interface Element Actions
Right-click the header of an interface role in the workspace to open a context menu with the following command.
When you select...
Rename
The software...
allows you to modify the identifier of the role.
For more information, refer to the topic describing interface roles (see
EcoStruxure ™ Process Expert, Global Templates, Reference Manual).
Right-click an element of an interface role to open a context menu with the following commands. Commands may vary depending on the role of the element.
When you select...
Switch to
Optional
Switch to
Required
Use as
Consumer
The software...
sets the rule for the element, which is the producer to optional . In such case, the element is not required to provide data for the interface link to be valid.
The default value is required .
NOTE: If you set a role to optional and later you change the role to consumer, the role is reset to required .
sets the rule for the element, which is the producer to required (default value). In such case, the element is required to provide data for the interface link to be valid.
switches the direction from producer to consumer .
NOTE: Using this command resets the element rule to required if it was set to optional .
Use as
Producer switches the direction from consumer to producer .
Switch Mode switches the mode of the link between role A and role B of an element from Direct to Transform and the other way around.
Delete
Right-clicking an element and switching the mode to:
• Transform
◦ Removes the direct link between role A and role B of the element.
◦ Removes the element from the other role.
◦ Requires that you create a new element in the other role with mode
Transform and with the opposite direction.
• Direct
◦ Removes the link between the element and the transformation function.
◦ Creates the element in the other role of the interface.
◦ Creates a direct link between both roles of the element.
◦ Requires that you reconfigure the transformation function, and possibly the elements that are still linked to it.
NOTE: When you switch the mode to Transform , verify that the cardinality that is defined in the Header pane for either role A or role B makes it possible to use transformation functions.
NOTE: The command is not available for nested interfaces.
deletes the element from both roles of the interface.
Right-click a nested interface of an interface role to open a context menu with the following commands. Commands may vary depending on the role of the element.
EIO0000001114.15
When you select...
Switch to
Optional
Switch to
Required
Add to Rules table
Remove from Rules table
The software...
sets the rule for the element to optional . In such case, the element is not required to provide data for the interface link to be valid.
The default value is required .
NOTE: The command is available by default for the Def role of the nested interface. To make the command available for the Ref role, add the element to the Rules table first by using the Add to Rules table command first.
sets the rule for the element, which is the producer to required (default value). In such case, the element is required to provide data for the interface link to be valid.
adds the element that has the Ref role to the Rules table so that you can define a rule for it ( optional or required ).
Inspect
Read-only
Edit
Update
Replace
Delete removes the element that has the Ref role from the Rules table.
NOTE: Removing the element from the Rules table makes the Switch to
Optional and Switch to Required commands unavailable.
opens a submenu with the Used By and
commands.
opens the nested interface in another Interface Editor in read-only mode.
opens the nested interface in another Interface Editor in editing mode.
Allows you to update the version of the nested interface to the latest one, which exists in the Global Templates library.
Opens the Replace dialog box. It allows you to replace the nested interface by a different one, which exists in the Global Templates library.
deletes the nested interface from both roles of the interface.
Viewing Changes to Interfaces
The submenu of the editor menu contains the Show changes log command, which opens the Changes log pane. This pane keeps track of the changes that are made to the template and saved. It indicates:
• The action that was performed.
• The state of the template after the change.
• The mandatory description of changes that is entered when the template is saved.
• The version of the template after the change.
• The user name of the user logged in to the engineering client.
Saving Changes
Refer to
Saving Changes in Global Templates, page 675 .
Facet and Composite Template Editors
Overview
This topic describes the user interface of the Facet Editor and Composite
Editor .
Facet Editor
Overview
The graphical Facet Editor allows you to manage the entire definition of Control and Supervision facet templates.
EIO0000001114.15
659
For a description of panes, toolbars, and menus, refer to the topic describing
common template editor components, page 666 .
NOTE: This topic provides information on the Facet Editor user interface; it does not provide information on the definition of facet templates (see
EcoStruxure ™ Process Expert, Global Templates, Reference Manual).
Facet Editor
The following figure shows an example of the Facet Editor .
660
5
6
7
2
3
Item
1
4
Description
Document Outline , Toolbox , and Browser panes.
Properties and Interface Rules panes.
Parameters pane.
Workspace area displaying a graphical representation of the elements of the template that you are editing.
containing commands that apply to the template being viewed or edited.
.
Workspace Actions
For a description of the context menu that opens when you right-click an empty area of the workspace, refer to the description of the
workspace context menu, page 669
.
Element Actions
Right-click the header of an element in the workspace of the Facet Editor to open a context menu with the following commands.
EIO0000001114.15
Command
Optimize
Bindings
Show/Hide
Unchecked
Description
Reroutes bindings of the element correctly.
Shows or hides properties whose eye icon that is located on the right-hand side is not visible (unchecked).
To uncheck a property, click its icon. The icon disappears.
NOTE: A property that has a binding connected to it cannot be hidden.
Shows or hides properties that have no binding connected.
Show/Hide
Unbound
Go To
Copy
Exclude
Delete
Rename
Properties
Opens a submenu that contains the name and path of other objects and/or their properties that are linked to the element through bindings. It lets you locate them
(see EcoStruxure ™ Process Expert, Global Templates, Reference Manual) easily.
When you select an entry, the object and the binding are highlighted in the workspace.
Copies the element for pasting in this template or another template.
After you confirm the command, removes the element from the workspace and makes it available again in the Elements section of the Document Outline pane.
Any existing bindings with the element are discarded.
NOTE: The command is available only for Control elements.
After you confirm the command, removes the element from the facet template.
Any existing bindings with the element are discarded.
NOTE: The command is available only for certain types of elements.
Allows you to modify the identifier of the element.
Displays the properties of the element in the Properties pane.
Right-click the property of an element in the workspace of the Facet Editor to open a context menu with the following commands.
Command
Create
Parameter
Create Input
Value
Show/Hide
$IsConnected
Description
Allows you to create a parameter that you can customize (see EcoStruxure ™
Process Expert, Global Templates, Reference Manual).
Allows you to enter an absolute value.
Go To
Binding To
Here From...
Binding
From Here
To...
Properties
Displays or hides the $IsConnected property, which outputs the boolean value
TRUE when the interface link is successfully established. This implies that applicable interface and interface element rules are satisfied; otherwise the value is FALSE .
The command is available for interfaces only.
Opens a submenu that contains the name and path of other objects and/or their properties that are linked to this property through bindings. It lets you locate them
(see EcoStruxure ™ Process Expert, Global Templates, Reference Manual) easily.
When you select an entry, the object and the binding are highlighted in the workspace.
Use this command (see EcoStruxure ™ Process Expert, Global Templates,
Reference Manual) on the property that is the destination of the binding to be created.
It enables the Bind to command.
Use this command (see EcoStruxure ™ Process Expert, Global Templates,
Reference Manual) on the object that is the source of the binding to be created.
It enables the Bind from command.
Displays the properties of the element in the Properties pane.
Right-click the header of an interface element in the workspace of the Facet
Editor to open a context menu with the following commands.
EIO0000001114.15
661
662
Command
Switch to
Optional/
Required
Description
Optional : Makes the element optional in the context of the template.
The element is represented with a dotted outline.
Required : Makes the element mandatory in the context of the template.
The element is represented with a solid outline.
Reroutes bindings of the element correctly.
Optimize
Bindings
Show/Hide
Unchecked
Delete
Rename
Properties
Shows or hides properties whose eye icon that is located on the right-hand side is not visible (unchecked).
By default, each property is checked; the icon is visible.
To uncheck a property, click its icon. The icon disappears.
NOTE: A property that has a binding connected to it cannot be hidden even if it is unchecked.
Shows or hides properties that have no binding connected.
Show/Hide
Unbound
Inspect
Read-Only
Edit
Go To
Copy
allows you top open the Used By or Dependencies Tree panes in which you can view respectively:
• The templates that reference it.
• Elements that it references (not applicable for interfaces).
Opens the element in the corresponding editor in read-only mode.
Opens the element in the corresponding editor in edit mode.
Opens a submenu that contains the name and path of other objects and/or their properties that are linked to the element through bindings. It lets you locate them
(see EcoStruxure ™ Process Expert, Global Templates, Reference Manual) easily.
When you select an entry, the object and the binding are highlighted in the workspace.
Copies the element for pasting in this template or another template.
Allows you to update the version of the interface model that is used by the interface to the latest one, which exists in the Global Templates library.
Opens the Replace dialog box. It allows you to replace the interface model that is used by the interface by a different one, which exists in the Global Templates library.
Removes the element from the template.
Allows you to modify the identifier of the element.
Displays the properties of the element in the Properties pane.
Additional Information
The list indicates where you can find a detailed description of the contents of the various panes of the Facet Editor :
• Properties (see EcoStruxure ™ Process Expert, Global Templates, Reference
Manual) and properties common definition (see EcoStruxure ™ Process
Expert, Global Templates, Reference Manual) (shared among interface models, facet, and composite templates).
• Facet Elements (see EcoStruxure ™ Process Expert, Global Templates,
Reference Manual)
• Interfaces Rules (see EcoStruxure ™ Process Expert, Global Templates,
Reference Manual)
• Toolbox: binding functions (see EcoStruxure ™ Process Expert, Global
Templates, Reference Manual) and/or Supervision Participant
• Parameter pane (see EcoStruxure ™ Process Expert, Global Templates,
Reference Manual)
EIO0000001114.15
Composite Editor
Viewing Changes to Templates
Refer to the topic describing the Changes log
Saving Changes
Refer to
Saving Changes in Global Templates, page 675 .
Overview
The graphical Composite Editor allows you to manage the entire composition and definition of composite templates.
For a description of panes, toolbars, and menus, refer to the topic describing
common template editor components, page 666
.
NOTE: This topic provides information on the Composite Editor user interface; it does not provide information on the definition of composite templates (see EcoStruxure ™ Process Expert, Global Templates, Reference
Manual).
Composite Editor
The following figure shows an example of the Composite Editor .
EIO0000001114.15
5
6
7
2
3
Item
1
4
Description
Document Outline , Toolbox , and Browser panes.
Properties , Interface Rules , and Element Rules panes.
Parameters pane.
Workspace area displaying a graphical representation of the elements of the template that you are editing.
containing commands that apply to the template being viewed or edited.
.
.
663
664
Workspace Actions
For a description of the context menu that opens when you right-click an empty area of the workspace, refer to the description of the
workspace context menu, page 669
.
Element Actions
Right-click the header of an element in the workspace of the Composite Editor to open a context menu with the following commands.
Command
Switch to
Optional/
Required
Defer
Description
Optional: makes the element optional in the context of the template.
The element is represented with a dotted outline.
Required: makes the element mandatory in the context of the template.
The element is represented with a solid outline.
Defers items to make them available in the top-level template referencing the composite that you are editing (for example, in the control module).
Selecting the command displays a submenu with the following commands:
• Unbound selection/parameters : Makes available any element selection
(only optional elements) and parameters for which no binding exists.
• Unbound interfaces : Makes available any interfaces for which no binding exists.
• All unbound : Makes available any element selection (only optional elements), parameters, and interfaces for which no binding exists.
Reroutes bindings of the element correctly.
Optimize
Bindings
Show/Hide
Unchecked
Delete
Rename
Properties
Shows or hides properties whose eye icon that is located on the right-hand side is not visible (unchecked).
To uncheck a property, click its icon. The icon disappears.
NOTE: A property that has a binding connected to it cannot be hidden.
Shows or hides properties that have no binding connected.
Show/Hide
Unbound
Inspect
Read-Only
Edit
Go To
Copy
Allows you top open the Used By , Dependencies Tree , or External References
in which you can view respectively:
• The templates that reference it.
• Elements that it references. For each reference, you can view its interfaces.
• Systems in which an instance of the template exists.
Opens the element in the corresponding editor in read-only mode.
Opens the element in the corresponding editor in edit mode.
Opens a submenu that contains the name and path of other objects and/or their properties that are linked to the element through bindings. It lets you locate them
(see EcoStruxure ™ Process Expert, Global Templates, Reference Manual) easily.
When you select an entry, the object and the binding are highlighted in the workspace.
Copies the element for pasting in this template or another template.
Allows you to update the version of the template that is used by the element to the latest one, which exists in the Global Templates library.
In case of an interface element, lets you replace the interface model.
Opens the Replace dialog box. It allows you to replace the template that is used by the element by a different one, which exists in the Global Templates library.
In case of an interface element, lets you replace the interface model.
Removes the element from the template.
Allows you to modify the identifier of the element.
Displays the properties of the element in the Properties pane.
EIO0000001114.15
EIO0000001114.15
Right-click the parameter of an element in the workspace of the Composite
Editor to open a context menu with the following commands.
Command
Create
Deferred
Description
Defers the parameter to make it available in the top-level template referencing the composite that you are editing.
The other commands are described in the table describing the context menu commands of
properties of elements of facet templates, page 660
.
Right-click the interface of an element in the workspace of the Composite Editor to open a context menu with the following commands.
Command
Create
Deferred
Create
Extended
Explode
Implode
Description
Defers the interface to make it available in the top-level template referencing the composite that you are editing.
Shows the interface as an element of the template.
Inspect
Read-Only
Edit
Go To
Properties
• Collapsed state: Makes a connector available that represents the complete interface. The connection is made by using an interface link (shown in orange).
• Expanded state: Makes each element of a multi-element interface available individually for connection to other elements by using bindings (shown in gray).
Allows you top open the Used By or Dependencies Tree panes in which you can view respectively:
• The templates that reference it.
• Nested interfaces that it references.
Opens the interface in the corresponding editor in read-only mode.
Opens the interface in the corresponding editor in edit mode.
Opens a submenu that contains the name and path of other objects and/or their properties that are linked to the interface through bindings. It lets you locate them
(see EcoStruxure ™ Process Expert, Global Templates, Reference Manual) easily.
When you select an entry, the object and the binding are highlighted in the workspace.
Displays the properties of the interface in the Properties pane.
NOTE: Additional commands are described in the topic describing
actions for properties of elements, page 660
in the Facet Editor .
Additional Information
The list indicates where you can find a detailed description of the contents of the various panes of the Composite Editor :
• Properties (Header) (see EcoStruxure ™ Process Expert, Global Templates,
Reference Manual) and properties common definition (see EcoStruxure ™
Process Expert, Global Templates, Reference Manual) (shared among interface models, facet, and composite templates).
• Composite Elements (see EcoStruxure ™ Process Expert, Global Templates,
Reference Manual)
• Interfaces Rules (see EcoStruxure ™
Reference Manual)
Process Expert, Global Templates,
• Toolbox: binding functions (see EcoStruxure ™ Process Expert, Global
Templates, Reference Manual)
• Parameter pane (see EcoStruxure ™ Process Expert, Global Templates,
Reference Manual)
Viewing Changes to Templates
Refer to the topic describing the Changes log
665
Saving Changes
Refer to
Saving Changes in Global Templates, page 675 .
Common Template Editor Components
Overview
The Facet Editor and Composite Editor have several components in common, which are described in this topic. Items that are specific to either editor are pointed out.
Common Template Editor Toolbars and Menus
Overview
The Facet Editor and Composite Editor feature toolbars and menus, which allow you to access the various tools and functions that you require to create and edit Global Templates.
This topic describes toolbars and menus that the Facet Editor and Composite
Editor have in common. Those that are specific to either editor are pointed out.
Certain menus and commands may be available only in editing mode.
NOTE: Toolbars contain commands that apply to the template that is being viewed or edited. To interact with an element of a template, open the context menu of the element by right-clicking it.
Editor Toolbar
The figure shows the editor toolbar that is located in the top right-hand corner of the Facet Editor and Composite Editor .
666
4
7
8
5
6
Item
1
2
3
Description
Edit button.
Switches the editor from read-only to editing mode.
Save button.
Opens the Save dialog box.
For more information, refer to the topic describing how to
save changes in templates, page 675 .
Save as button.
Opens the Save As dialog box.
For more information, refer to the topic describing how to
save changes in templates, page 675 .
Undo and redo buttons.
Lets you undo and redo most actions.
Displays the Parameters pane.
Displays the Dependencies Tree pane.
Displays the Used By pane.
Displays the External References pane.
EIO0000001114.15
Item
9
10
Description
Opens the Select Variables or Select Genie window, which allows you to encapsulate constituents in Control and compatible Supervision facet templates respectively. It also allows you to modify encapsulated elements with the help of the corresponding
Participant.
If a Control facet contains no constituents, the Content Not Found dialog box opens, which allows you to start the encapsulation process.
For more information, refer to the topic describing the configuration of facet templates
(see EcoStruxure ™ Process Expert, Global Templates, Reference Manual).
NOTE: The command is available only in the Facet Editor .
Opens the
that contains editor-specific commands.
NOTE: For a description of the panes mentioned in the table, refer to the topic describing
common template editor panes, page 670
.
Workspace Toolbar
The figure shows the workspace toolbar that is located in the bottom right-hand corner of the Facet Editor and Composite Editor .
EIO0000001114.15
5
6
2
3
4
Item
1
7
8
9
Description
Aligns the left edge of any selected item in the workspace with the left edge of the item that you have selected first.
NOTE: The graphical alignment rules do not apply to parameters and input values, except for the three $System parameters $InstanceID , $Description , and $Area .
Aligns the top edge of any selected item in the workspace with the top edge of the item that you have selected first.
Aligns the right edge of any selected item in the workspace with the right edge of the item that you have selected first.
Aligns the bottom edge of any selected item in the workspace with the bottom edge of the item that you have selected first.
Reverts to the default zoom level (100%).
Adjusts the zoom level to fit the elements of the template inside the visible workspace.
If the layout of the template is very large, some objects may not fit inside the visible workspace. You can use the
to locate these objects.
.
Alternatively, use the minus (-) keyboard key.
When you zoom out to 50%, the display switches to the
. To return to the normal view, zoom in.
Zooms in.
Alternatively, use the plus (+) keyboard key.
Current zoom level.
Use a predefined level by clicking the arrow and selecting a value from the list.
You can set a custom level by double-clicking the value, entering a new one, and pressing Enter . Range: 50 to 200.
NOTE: For information on commands that allow you to select multiple items in the workspace and move the workspace around, refer to the topic describing the
engineering client workspace, page 81
.
667
668
Editor Menu
The table describes the submenus and commands of the menu located in the toolbar of template editors.
Command
New...
Edit
View
Save
Save As
Copy
Paste
Select All
Select None
Invert Selection
Find
Document Outline
Dependencies Tree
Used By
External References
Locations
Parameters
Interface Rules
Element Rules (1)
Toolbox
Browser
Properties
Description
Opens the Global Templates dialog box, which contains the same base templates as the Toolbox of the Global
Templates explorer. It allows you to create a new template in one or more existing folders of the Global Templates library and open it in editing mode in the corresponding editor.
For more information, refer to the topic describing how to create templates (see EcoStruxure ™ Process Expert, Global
Templates, Reference Manual).
Copies the selected element for pasting in this template or another template.
You can copy multiple elements by selecting them first.
Pastes copied elements.
When a naming rule applies to elements, the software uses the _n suffix (where n is an incremental number starting at
1) to create unique names.
Selects any element in the workspace.
Clears any selected element in the workspace.
Selects elements that are not selected and clears any selected element in the workspace.
Displays a search field, which allows you to find strings in any element of the workspace by entering entire or partial key words.
Strings that contain the word you entered appear in a list with an indication of their path.
Right-click a result and select Navigate to highlight it in the workspace.
For example, entering in returns various results, such as:
• The $InstanceID system parameter.
• The $InstanceID parameter of an element.
• The In input of a binding function.
• Interfaces to indicate that an element references interfaces.
The commands allow you to bring the corresponding pane to the front.
If the pane is closed, the command opens it.
For a description of the panes, refer to the topic describing template editor panes.
Save button.
Opens the Save dialog box.
For more information, refer to the topic describing how to
save changes in templates, page 675
.
Save as button.
EIO0000001114.15
EIO0000001114.15
Command Description
Export Standard Backup
Various image file formats
Opens the Save As dialog box.
For more information, refer to the topic describing how to
save changes in templates, page 675
.
Opens the Export window, which allows you to export the template definition to file (.sbk).
You can only export a template if you have saved changes.
For more information on export feature, refer to the topic describing
Each command opens a Save dialog box, which allows you to create an image file with the corresponding file extension.
The image captures the entire layout of the template independently of the zoom level.
Panes and toolbars are not captured.
Print Only Visible Content Opens the Print dialog box, which lets you print on one page, the portion of the template layout that is visible in the current view.
Editor Content On
Single Page
Opens the Print dialog box, which lets you print the entire layout of the template on one page.
Show Changes Log Opens the Changes Log pane.
Close Closes the template editor.
If you have made changes, opens the Save dialog box.
For more information, refer to the topic describing how to
save changes in templates, page 675
.
(1) The command appears only in the menu of the Composite Editor
Workspace Context Menu
Right-click an empty area of the workspace of a template editor to open a context menu with the following commands.
When you select...
Inspect
The software...
Align Left
Edges
Align Top
Edges
Align Right
Edges
Align
Bottom
Edges
Copy opens a submenu with the
and
commands.
Refer to the description of the corresponding commands in the
The commands are available only if two or more elements are selected in the workspace.
Paste copies the selected element for pasting in this template or another template.
You can copy multiple elements by selecting them first.
pastes copied elements.
When a naming rule applies to elements, the software uses the _n suffix (where n is an incremental number starting at 1) to create unique names.
opens the
Show
Changes
Log
Properties brings the Properties pane to the front to display properties of the template that is open in the editor. If the pane is closed, the command opens it.
669
Binding Context Menu
Right-click a binding or its connector (see EcoStruxure ™ Process Expert, Global
Templates, Reference Manual) in the workspace of a template editor to open a context menu with the following commands.
Command
Convert To
Line
Convert to
Connector
Go To
Description
Lets you toggle between binding styles (see EcoStruxure ™ Process Expert, Global
Templates, Reference Manual).
Update
Binding
Delete
For bindings in line style, opens a submenu that contains the name and path of objects and/or their properties that are linked to this object through bindings. It lets you locate them (see EcoStruxure ™ Process Expert, Global Templates, Reference
Manual) easily. When you select an entry, the object and the binding are highlighted in the workspace.
For bindings in connector style, highlights the object that is connected to the other end of the binding.
Opens the Update Binding dialog box, which lets you move the destination (see
EcoStruxure ™ Process Expert, Global Templates, Reference Manual) of the binding to another property or element.
The command is not available for source connectors of bindings.
Deletes the binding after you confirm the command.
Common Template Editor Panes
Introduction
The Facet Editor and Composite Editor use various panes to group properties and data that are related.
This topic describes panes that are common to both. Panes that are specific to either editor are pointed out.
Certain panes may be available only in editing mode.
For information on working with panes, refer to the topic describing the
engineering client workspace, page 85 .
NOTE: This topic provides information on the user interface of the panes only.
It does not provide information on how to define or modify their contents.
Editor Panes
The table describes the purpose of the panes that you can access in the Facet
Editor and Composite Editor .
Pane
Document Outline
Interface Rules
Element Rules (1)
Description
Allows you to view and/or edit:
• Parameters
• Elements
• Interfaces
Click a parameter, element, or interface to display its properties in the
Properties pane. The corresponding item is selected in the workspace.
NOTE: To view and/or edit the properties of the template, click
Parameters .
Allows you to view and define the rules for the interfaces (see
EcoStruxure ™ Process Expert, Global Templates, Reference Manual) referenced by the template.
Allows you to view and define the rules for the elements (see EcoStruxure ™
Process Expert, Global Templates, Reference Manual) referenced by the template.
670 EIO0000001114.15
EIO0000001114.15
Pane
Properties
Toolbox
Browser
Description
Allows you to view and/or edit the properties of the selected element of the template.
Allows you to browse and select binding functions (see EcoStruxure ™
Process Expert, Global Templates, Reference Manual) to be used in the template.
For facet templates of the Supervision category, the Toolbox pane also contains the following elements (see EcoStruxure ™ Process Expert, Global
Templates, Reference Manual):
• For facet templates of the Data subtype:
◦ Advanced Alarm
◦ Calculated Variable Tag
◦ Disk Variable Tag
◦ Digital Alarm
◦ Equipment
◦ Equipment Parameter
◦ Equipment Group of Messages
◦ Local Variable Tag
◦ Message
◦ Time Stamped Digital Alarm
◦ Trend Tag
◦ Variable Tag
• For facet templates of the Genie subtype:
◦ Equipment
◦ Equipment Parameter
◦ Equipment Group of Messages
• For facet templates of the Client Event subtype: Event .
• For facet templates of the Server Event subtype: Report .
These elements contain the same properties as the corresponding elements of the Supervision Participant and allow populating the respective databases.
In the Facet Editor , allows you to browse and select interfaces to be referenced by the template.
In the Composite Editor , allows you to browse and select facet and composite templates, and interfaces to be referenced in the template.
Dependencies Tree In the Facet Editor , allows you to view the interfaces that the template references.
In the Composite Editor , allows you to view the interfaces, facet and composite templates that the template references.
Used By
You can right-click an item to view and/or edit it in a new editor. You can also view the dependencies of the item or which other templates reference it.
Allows you to view the templates that reference the template, which is open in the editor. You can right-click a template in the Used By pane to open it in a new editor. You can also view its dependencies or which other templates reference it.
External
References
Parameters (see
EcoStruxure ™
Process Expert,
Global Templates,
Reference Manual)
Allows you to view:
• In which systems an instance of the template exists.
• For each system, the identifier of the instances using the template.
You can right-click an application instance to:
• Open the folder containing the instance in the Application Explorer .
• Open the
Inspect Instance window, page 155
.
The Parameters pane allows you to:
• View and manage parameter data that is used during instantiation to customize elements of an instance.
• Customize the layout of the parameters that are visible when you edit an instance by using the Instance Editor :
◦ Change the position of parameters within their category.
◦ Change the position of categories.
◦ Assign parameters to another category.
671
Pane
Locations
Description
Allows you to view the path to the template and its
Right-click an entry and select Open reference container to open the corresponding folder in the Global Templates explorer.
Changes log Keeps track of changes that are made to the template and saved. The pane indicates:
• The action that was performed.
• The state of the template after the change.
• The mandatory description of changes that is entered when the template is saved.
• The version of the template after the change.
• The user name of the user logged in to the engineering client.
(1) The pane appears only in the Composite Editor .
Using the Radar View
Overview
The radar view appears in the bottom right corner of certain graphical editors. It shows you which area of the layout of a template or workspace you are seeing in the editor.
You can also use it to navigate the inside the workspace and adjust the zoom level.
Description
The following figure shows an example of the Radar View in a template editor.
672
Item
1
2
3
Description
Shows all the objects that appear in the editor.
The view is refreshed when you modify the layout of objects.
Area that is currently visible in the editor.
You can move the translucent rectangle by dragging it with the pointer. The view inside the editor moves accordingly. Alternatively, click anywhere inside the Radar View to move the center of the translucent rectangle to where you have clicked.
When you change the zoom level, the size of the translucent rectangle adjusts accordingly.
Zoom level adjustment.
Dragging the corner inward or outward lets you zoom in or out respectively.
NOTE: While the pointer is over the Radar View , you can also use the mouse wheel to zoom.
EIO0000001114.15
When the Radar View is collapsed, it appears as a button
Using the Simplified View in Template Editors
Overview
Zooming out to the lowest level in the Composite Editor or Facet Editor switches the display to the simplified view.
This view mode lets you see, at a glance, the elements of a template and the relation between them without showing the details of bindings and element properties.
Some template engineering functionality are not available.
To exit the simplified view, zoom in.
Restrictions of the Simplified View
The table describes the restrictions in the template editor while the simplified view is active.
Action or object
Actions related to bindings (such as creating, moving, deleting, switching styles).
Creating parameters or platform inputs.
Element properties and deferred inputs and outputs.
Multiple bindings to and from an element.
Binding connectors.
Restrictions
Actions are not allowed
Are not shown.
Are shown as a single line.
Are not shown. Bindings are shown in line style instead.
Description
The following figure shows an example of template as it normally appears in the
Facet Editor .
EIO0000001114.15
673
The following figure shows the same template when simplified view is active (the view is enlarged for better visibility).
1 Elements keep their relative size and position to preserve the aspect of the layout.
2 Parameters and platform inputs are shown in their actual position.
3 Bindings to and from each element are grouped into a single line.
674 EIO0000001114.15
Managing Global Templates
What’s in This Chapter
Updating, Replacing, and Duplicating Global Templates ................................. 688
Managing Global Templates
Saving Changes In Global Templates
Overview
When Global Templates are open in their respective
, you can save changes by using the following commands:
Save
Save as
Allows you to save changes to templates that you have created by using various save options. Use the command to rename a template or change its usability state.
The command is available only if the template is not referenced by another template and not used by an instance of the application; otherwise the software opens the Save as dialog box.
Allows you to save changes to Schneider Electric Global Templates, create a new template, or a new version of a template.
When you select the Save as command, you can select one or more locations where to store the template.
NOTE: To save a template with a different identifier and/or version without editing it, use the Duplicate
.
Restrictions When Saving Schneider Electric Templates
Restrictions (see EcoStruxure ™ Process Expert, Global Templates, Reference
Manual) related to the template identifier apply when you save a Schneider
Electric template.
Tracking Saved Changes
When you save a template, the software keeps a record of the save operation.
You can view details in the Changes log pane, which is available in each
.
Save Options
The table describes the items of the Save and Save as dialog boxes that the software displays when you select the respective command.
Item
Keep Version (1)
New Build
New Minor
New Major
Other
Description
Select this versioning scheme to save changes in a template without changing its version number.
Selected by default.
For information on the usage of the different version components, refer to
Version (see EcoStruxure ™ Process Expert, Global Templates, Reference
Manual).
By default, New Build is selected when you open the Save As dialog box.
Selecting this versioning scheme allows you to edit the following parameters in the dialog box before saving the template:
• The identifier.
EIO0000001114.15
675
676
Item
Version
Identifier
Locations
Usability State
New Version
Usability State
Old Version
Usability State
Changes
(3)
Description
(1)
(2)
(2)
Description
• The three version components (major, minor, build number).
Select it to rename the template or create a new template based on the one you are editing.
NOTE: By default, the version that is selected is the same as for New
Build .
For a description of the version format, refer to Version (see EcoStruxure ™
Process Expert, Global Templates, Reference Manual).
Within the Global Templates library, the software requires that the combination of identifier (see EcoStruxure ™ Process Expert, Global Templates, Reference
Manual) and version be unique for each template.
Allows you to select one or more existing folders of the Global Templates library to store the template.
Default value: The current location of the template. If
exist, their location is indicated also.
Click the browse button to open the Select Template Location dialog box, which lets you change locations and create linked copies by selecting additional locations.
For information on the parameter, refer to Usability State (see EcoStruxure ™
Process Expert, Global Templates, Reference Manual).
Default value: Current state of the template.
Allows you to define the usability state of the new template that you are creating.
Default value: Not Approved
For information on the parameter, refer to Usability State (see EcoStruxure ™
Process Expert, Global Templates, Reference Manual).
Allows you to define what will be the usability state of the template that you are currently editing after you create the new template.
Default value: Approved
For information on the parameter, refer to Usability State (see EcoStruxure ™
Process Expert, Global Templates, Reference Manual).
You must enter a description by using free form text to be able to save changes.
The description that you enter is visible in the Changes log of the template editor. Entering a detailed description of changes allows you to keep track of the version history of the template.
(1) The item is displayed only in the Save dialog box.
(2) The item is displayed only in the Save As dialog box for templates that are already referenced or instantiated.
(3) The item is displayed only in the Save As dialog box.
Saving Changes In Global Templates
Modifying Schneider Electric Global Templates or creating templates may affect the function of these templates and/or systems, and must be performed by qualified personnel. Before proceeding, refer to the
.
To save changes in Global Templates, proceed as follows.
Step
1
2
Action
In the template editor, click the Save or Save As button.
Result: The software opens the appropriate dialog box.
Select the versioning scheme that you want to use.
EIO0000001114.15
Step
3
4
Action
Edit the Identifier , Change Description , and/or Usability State as needed.
Click the Save button.
Result: The software:
• For the Save dialog box:
◦ Closes the dialog box.
◦ Saves the changes in the template.
◦ Keeps the template open inside the editor.
• For the Save as dialog box:
◦ Creates a new template, which includes your changes and displays it in the editor.
◦ Closes the source template without saving.
NOTE: Click the Cancel button to close the Save or Save as dialog box without saving changes.
Copying and Pasting Global Templates and Folders
Creating Linked Copies of Templates
Certain commands (for example, copy and paste ) let you place copies of a template in several folders of the Global Templates library. The copies are linked to the source template. Any change that you make to the source template is also made to each copy that you have created.
NOTE: To create an independent copy of a template, use the Save as or
Duplicate command from the corresponding template editor or Global
Templates Explorer .
Locating Copies
To locate the linked copies of a template, use the Locations
Copying Folders
You cannot paste an empty library folder.
When you copy a folder containing templates and you paste it on another folder, the software creates a subfolder with the same identifier, which contains a linked copy of each template of the source folders. Subfolders and their contents are created in the same way.
Exporting Templates
Overview
The Export command of the Global Templates Explorer lets you export templates of the Global Templates library.
The process creates an export file in .sbk
format that contains:
• The selected templates.
• Referenced composite and facet templates, interfaces, and their parameter configuration.
• Local constituents.
• Supervision content.
User contents such as
containing documents and
URLs that are linked to a template are not exported.
The export functionality allows you to copy these templates to another system or platform, or to create a backup.
EIO0000001114.15
677
Aborting Export Tasks
After confirming the export by clicking Save in the Save window, the abort icon is displayed in the
. Click the icon to cancel the task. The export file is not created.
Only the user who has selected the command is allowed to abort it.
NOTE: If you are exporting only a few templates, the task may complete before you are able to click the icon.
Template Export Window
The following figure shows an example of the template window that opens after selecting the Export command from the ON_OFF Devices Control sample folder.
678
Item
1
2
3
Description
Button to show or hide the details pane (shown on the right-hand side of the window).
Select a template by clicking its row in the tree or grid view to view details.
Button to toggle between grid view and tree view. Tree view is the default view (shown here).
Indicates the number of selected templates and the total number of templates contained in the location from which you have selected the Export command.
are not counted even if they are selected.
NOTE: To expand/collapse a node in the Export window, select the node and press Enter .
The table describes the information that appears in the columns of the Export window.
EIO0000001114.15
Column Header
Identifier
Type
Version
State
Description
Description
Displays:
• The folder hierarchy in the Global Templates library (tree view mode only).
• The identifier of templates contained in the location from which you have selected the Export command.
• Check boxes that let you select the templates you want to export.
In grid view mode, only templates are shown, not linked copies.
NOTE: By default, all templates are selected.
Indicates the category of the template.
Refer to the definition header of each template category for a description of the
.
Indicates the version of the template.
Usability state (see EcoStruxure ™ Process Expert, Global Templates,
Reference Manual) of the template (for example, Approved or
Deprecated ).
Description of the template.
The table describes the details pane of the Export window.
Section Header
–
Required Dependencies
Selected Dependencies
Locations
Description
Identifier of the selected template.
NOTE: You can view details even if the check box next to the template identifier is not selected.
Identifier of templates that are required to export the selected template.
The check box of required dependencies is selected and disabled. To enable it, you need to clear the check box of the selected template.
Identifier of templates that reference the selected template.
When you clear the check box of a selected dependency, the template is removed from this section. Once you have cleared the check boxes of all the listed templates of this section, the check box of the selected template is enabled and you can clear it to exclude it from the export file.
As long as selected dependencies are listed, the check box of the selected template remains disabled.
Path of the selected template and any of its linked copies in the
Global Templates library.
For each template and linked copy, the status of the check box in the
Identifier column is duplicated.
Creating the Export File
To export templates and create the export file, proceed as follows.
Step
1
2
Action
From the tree view of the Global Templates Explorer , right-click and select Export on:
• A template if you want to export the template only
• A template folder if you want to export any templates of the folder, subfolders, and any templates contained in these subfolders
Result: The Export window opens.
Select the templates that you want to export.
EIO0000001114.15
679
Step
3
4
Action
Click OK .
Result: The Save dialog box opens.
Enter a name for the export file and select a location, and click Save .
Result: The software exports the selected items and creates an export file in .sbk
format in the location that you have selected.
NOTE: To export the templates of an entire library, create separate export files by selecting various subfolders in the Export window. This creates smaller export files that take less time to import.
Importing Templates
680
Overview
The Import command of the Global Templates Explorer allows you to import new templates, new versions of existing templates, and to modify or update templates or parts of these in the Global Templates library. Importing templates adds them to the database that is mounted.
When you select an export file (.sbk) containing templates, the software compares the information in the export file with the templates contained in the Global
Templates library and applies rules to keep templates unique.
The Import window allows you to select which valid templates of the export file you import. It also allows you to import new and/or updated content that is required by the templates you are importing. Content are project files containing, for example, Supervision resources such as animated graphics (genies) used by
Supervision runtime.
NOTE: Importing many templates may take time.
Export File Location
The export file containing the template information needs to be located in a folder that you can write to.
Import Rules
The table describes the rules that the software applies while comparing templates contained in the export file with those in the Global Templates library before importing templates.
Template identifier
Does not exist in the
Global Templates library.
Already exists in the
Global Templates library.
Template version
Indifferent
Template signature
Indifferent
Already exists in the
Global Templates library.
Already exists in the
Global Templates library.
The signature is different.
Action
The template is imported.
The template is not imported.
The version is unique.
The signature is unique.
The template is not imported and it displays a message about the detected conflict.
The template is imported.
Importing Supervision Included Projects
An included project (.ctz) that is used by a template is only imported if the template itself is imported.
EIO0000001114.15
For example, if you have modified the included project that is used by the MyMotor template v1.0.0 but without making any change to the template itself, you cannot add the modified included project to the
by importing the template if MyMotor v1.0.0 already exists in the Global Templates library.
Since the template already exists, it is not imported.
The table describes the methods that you can use to add a new included project to the content repository.
Method
Modify the template that references the new included project so that it can be imported.
Add the new included project directly to the content repository.
Description
Modify at least one Supervision genie facet template (_CG) of the template.
For example, you can create a
of the genie facet template without changing its content by using the Save As command.
Importing the template allows you to import the new included project and add it to the content repository.
Refer to the procedure that describes how to add project files to the content repository (see EcoStruxure ™ Process Expert, Global Templates,
Reference Manual).
To follow the procedure, edit either facet template:
• A new Supervision genie facet template that you create by using the
Genie template from the Toolbox of the Global Templates
Explorer .
• Any existing Supervision genie facet template (_CG) of the Global
Templates library.
In both cases, you do not need to save the template to be able to add the included project to the content repository.
Accessing the Template Import Window
To access the Import window, proceed as follows.
Step
1
2
3
Action
From the client toolbar, click the Global Templates explorer icon.
Result: The Global Templates Explorer window opens.
Right-click the Global Templates root folder and select Import .
Result: The Import dialog box opens.
NOTE: If you know the exact location where you want to import the templates, you can right-click the corresponding folder in the tree view of the Global Templates
Explorer and select Import .
Select the export file (.sbk) containing the templates that you want to import and click
Open .
Result: The software opens the Import window and displays the contents of the export file.
EIO0000001114.15
681
Template Import Window
The following figure shows an example of the Import window.
682
2
3
Item
1
4
5
Description
Button to show or hide the details pane (shown on the right-hand side of the window).
Select a template by clicking its row in the tree or grid view to view details.
Button to toggle between grid view and tree view, which is shown here. (default view).
Imports templates with the hierarchy of folders that existed at the time of export. Clear the check box to import templates in the same folder without hierarchy. The check box is selected by default. While in grid view, selecting or clearing the check box switches to tree view.
A message appears when the templates were exported from a version of the software that is different from the version you are using.
Indicates the number of selected templates and the total number of templates contained in the export file. Linked copies (templates marked with a blue dot) are not counted even if they are selected.
NOTE: To expand/collapse a node in the Import window, select the node and press Enter .
The table indicates the meaning of the colored dots that appear in the Import window next to template identifiers.
Color code
Green
Gray
Blue
Red
Description
The template does not exist in the Global Templates library and can be imported.
For a node, indicates that the elements of the node can be imported.
The template already exists in the Global Templates library and cannot be imported.
For a node, indicates that at least one element of the node already exists and is identified by a gray dot.
The template already exists in the Global Templates library but a
is created if imported.
Red dot: The template cannot be selected for import because of a detected
signature conflict, page 680 .
EIO0000001114.15
The table describes the information that appears in the columns of the Import window.
Column Header
Identifier
Type
Version
State
Description
Description
Displays:
• The folder hierarchy at the time of export (when Import hierarchy is selected).
• The identifier of templates contained in the export file.
• A colored dot.
• Check boxes allowing you to select the templates that you want to import.
Selecting a template automatically selects any referenced templates that can be imported. It also selects linked copies of referenced templates if the referenced template does not exist in the Global
Templates library yet.
In tree view, when Import hierarchy is not selected, the software can only import one of each template and/or one linked copy of each existing template because any template or linked copy is imported to the same folder.
In grid view, only templates are shown, not linked copies. If a template already exists, its check box is cleared and disabled.
Templates that do not exist have their check box selected by default and enabled (you can clear it).
NOTE: By default, new templates and new template versions are selected.
Indicates the category of templates in the export file.
Refer to the definition header of each template category for a description of the
.
Indicates the version of templates in the export file.
Usability state (see EcoStruxure ™ Process Expert, Global Templates,
Reference Manual) of the template (for example, Approved or
Deprecated ).
Description of templates in the export file.
The table describes the details pane of the Import window.
Section Header
–
Required Dependencies
Selected Dependencies
Locations
Description
Identifier of the selected template.
NOTE: You can view details even if the check box next to the template identifier is not selected.
Identifier of templates that are referenced by the selected template.
Identifier of templates that reference the selected template (only if the selected template can be imported).
When you clear the check box of a selected dependency, it clears the check box of any template and linked copies referencing the selected template. This allows you to clear the check box of the selected template, which would be disabled otherwise.
Path at the time of export of the selected template and any of its linked copies contained in the export file.
For each template and linked copy, the status of the check box in the
Identifier column is duplicated.
NOTE: If you clear Import hierarchy :
• Linked copies are not shown anymore.
• The path does not reflect the hierarchy at the time of export anymore
EIO0000001114.15
683
Resolving Contents Conflicts
When the software detects contents with the same name but a different version in the export file compared to the content that exists in the content repository, it displays the Resolve Contents Conflict dialog box. The following figure shows an example of the dialog box.
684
Header
Identifier
Current
New
Current genies
New genies
Conflicts
Description
Name of the content that conflicts with the current content located in the content repository.
Version of the current content located in the content repository.
Version of the content in the export file.
Animated graphics (genies) that are included in the current content located in the content repository.
Animated graphics that are included in the content in the export file.
Animated graphics that create a conflict if you import the new content.
In the Resolve Contents Conflict dialog box, verify the following before proceeding with the import:
• Refer to the library release notes. The documents contain information about changes that were made to templates of the corresponding library.
• Considerations when importing content:
Selecting new content
Selecting current content
Templates that you are importing and that require the new content will work correctly; however, the current content that is used by existing templates of the Global Templates library and instances thereof may be overwritten.
Also, the status of executables of Supervision projects that use contents of which you are importing a new version may be set to Out
Of Date if it is currently Built . In such case, you need to build these executables to integrate changes of the content in the corresponding
Supervision projects.
The content that is used by existing templates of the Global
Templates library and instances thereof is not affected; however, templates that you are importing will be missing the new content that they require to work properly.
EIO0000001114.15
EIO0000001114.15
NOTE: Refer to the Conflicts section of the Resolve Contents Conflict dialog box.
Aborting Import Tasks
After confirming the import by clicking OK in the Import window or in the Resolve
Contents Conflict dialog box, the abort icon is displayed in the
. Click the icon to cancel the task. No templates and no content are imported.
Only the user who has selected the command is allowed to abort it.
NOTE: If you are importing only a few templates, the task may complete before you are able to click the icon.
Importing Templates
NOTICE
LOSS OF DATA
Resolve a content conflict that arises during the import of templates by selecting the correct version of the content to be imported.
Failure to follow these instructions can result in unusable Supervision projects.
To import templates from an export file (.sbk) into the Global Templates library, proceed as follows.
Step
1
2
3
Action
In the Import window,
select the templates, page 682
that you want to import.
Click OK .
Result: If software detects content with the same name but of a different version, it displays the Resolve Contents Conflict dialog box; otherwise the software proceeds with the import of selected templates from the export file.
NOTE: Click Cancel to close the Import window without importing templates.
If the software displays the Resolve Contents Conflict dialog box, select the version of the content that you want to use, and click OK .
Result:
• The selected templates are imported.
• The import settings that you have selected are applied.
• It displays Completed in the notification panel when the import is complete.
NOTE: Click Cancel to close the Resolve Contents Conflict dialog box without importing the template. This reverts to the Import window.
After Importing Templates
Depending on the number of templates that you are importing and your hardware configuration, the import process may affect the performance of your computer, requiring you to restart the computer.
NOTICE
LOSS OF COMMUNICATION
Stop the system server only when no client is running.
Failure to follow these instructions can result in unresponsive clients.
After importing templates, proceed as follows.
685
Step
1
2
3
Action
.
Stop the system server.
Restart the computer.
Purging the Global Templates Library
Overview
The Purge context menu command of folders of the Global Templates Explorer allows you to remove unused, earlier versions of templates and interface models from the Global Templates library. The process also removes local constituents of deleted templates and unused
global constituents, page 704 .
You can select the templates to remove.
At the end of the purge process, the notification panel provides a summary with information on purged templates.
If the process ends abnormally (for example, by terminating the process), the tool rolls back the process.
Purge Rules
The tool deletes, using an iterative process, any facet, and composite templates, as well as interface models that satisfy the following rules:
• A template with a higher version number, having the same identifier and the
Usability State (see EcoStruxure ™ Process Expert, Global Templates,
Reference Manual) Approved exists in the Global Templates library.
• The template or the interface model is not referenced (used) by any other template of the Global Templates library.
• The template is not used by any instance of the application.
NOTE: The tool does not delete a template if the template is used by a facet that is assigned to a project and the Assignment status of the facet is
.
To delete such template, first generate the project or the container to which the facet is assigned.
686 EIO0000001114.15
Purge Window
The following figure shows an example of the Purge window when the Purge command is selected from the General Purpose Library folder.
EIO0000001114.15
Aborting Purge Tasks
After confirming the Purge command by clicking OK in the Purge window, the abort icon is displayed in the
. Click the icon to cancel the task. No templates are purged.
Only the user who has selected the command is allowed to abort it.
NOTE: If you are purging only a few templates, the task may complete before you are able to click the icon.
Backing Up the Database
You cannot restore Global Templates that you delete from the Global Templates library by using the Purge command.
Before using the command, back up the database. Refer to the topic describing how to back up the database (see EcoStruxure ™ Process Expert, Installation and
Configuration Guide).
Purging Global Templates
NOTICE
LOSS OF DATA
Back up the database before using the Purge command.
Failure to follow these instructions can result in unusable systems or database.
To delete Global Templates that satisfy the purge rules, proceed as follows.
687
Step
1
2
3
Action
Back up the database.
Right-click the parent folder starting from which you want to proceed with the removal and select Purge .
Result: The Purge window opens. After a few moments, it displays the templates that satisfy the purge rules in the selected location.
Select the templates that you want to delete and click OK .
Result: The software:
• Deletes applicable templates and interface models.
• Displays information in the notification panel when the purge is complete.
NOTE: Click Cancel to close the Purge window without purging Global Templates.
Updating, Replacing, and Duplicating Global Templates
Overview
This chapter describes the various commands that are available to modify Global
Templates with or without editing them.
Template Modification Strategy
Overview
Various commands are available that allow you to modify Schneider Electric and/ or user-created templates. Select the appropriate command depending on:
• Whether you want to edit a template or not.
• Whether the identifier of the template or one of its child templates contains the $ prefix (see EcoStruxure ™ Process Expert, Global Templates, Reference
Manual).
• The scope of changes to be performed.
The table shows the commands that are available to modify Global Templates and their specifics.
Command
Update
Replace
Duplicate
Use in
Global Templates
Explorer
Template editors
Template editors
Global Templates
Explorer
Use with
Templates
Elements
Elements
Templates
Purpose
To update a template with the latest version of any child templates that exist in the Global Templates library.
To update the template that is used by a specific element with the latest version that exists in the Global
Templates library.
To update the template that is used by a specific element with a different version or a different template that exists in the Global Templates library.
To create a new template from an existing one with the possibility to keep, duplicate, or replace each child template that is referenced.
Comment
• Cannot be used with templates whose identifier contains the $ prefix.
• The software finds the latest versions of templates with the same identifier automatically.
• Lets you updated the template that is used by a specific element (instance).
• The software finds the latest version automatically.
• Lets you replace the template that is used by a specific element (instance).
• Can be used to undo a template update.
• The replace action impacts all elements (instances) of a given template.
• Can be used in place of the
Update command with templates whose identifier contains the $ prefix.
688 EIO0000001114.15
Impact of Template Update or Replacement
The table describes the impact on the various template components when you update or replace a template.
Current template component
Bindings to the element selection of composite references
Bindings and attributes of the element parameters
Bindings to element interfaces
In new template Impact
Are the same as in current template.
The software maintains the bindings.
Are not the same as in current template.
The software removes the bindings to the element selection of the composites that are not part of the new template.
Are the same as in current template.
The software maintains the bindings and attributes.
Are not the same as in current template.
The software removes the bindings and attributes of the element parameters that are not part of the new template.
Are the same as in current template.
The software maintains the bindings.
Are not the same as in current template.
The software removes the bindings to the element interfaces that are not part of the new template.
Applying Template Modifications to Existing Instances
Modifications to templates need to be propagated to instances of the application to take effect. The method to apply modifications to existing instances depends on the template identifier.
Result of template modification
A new version of the template (same identifier)
A template with a new identifier
Method to apply
Update the template used by instances, page
Replace the template used by instances, page
Updating Global Templates and Templates of Elements
Overview
The Update command lets you perform different actions depending on where you use it.
In the Global Templates Explorer , it lets you create a new version of your template, in the same location, by using the latest approved version of any of the child templates that are referenced by this template.
In the Facet Editor and the Composite Editor , it lets you update the template or interface model that is used by a specific element by the latest available version.
In both cases, the update process allows you to integrate in the composition of your template the latest versions of composite and facet templates, and interface models.
NOTE: The update of the template of an element impacts templates that reference this element and requires
all the higher-level templates.
Restrictions When Updating Schneider Electric Templates
Restrictions (see EcoStruxure ™ Process Expert, Global Templates, Reference
Manual) related to the identifier of the parent template apply when you update a
Schneider Electric template.
You cannot use the Update command in the Global Templates Explorer on a template whose identifier contains the $ prefix. You need to use the Duplicate
instead.
EIO0000001114.15
689
690
Good Practices
• If you know which highest level templates reference templates of which a later version is available, proceed with the update from these highest level templates. Typically, the highest level template is the control module template.
• If you do not know which highest level templates need to be updated, use the
Inspect > Used By context-menu command on the template of which you have created a new version. This allows you to determine which are the highest level templates that you need to update with the new version child template.
Working Principle of the Update Functionality
When the Update command is used on a template in the Global Templates
Explorer , the software proceeds as follows:
• Searches the tree of dependencies of the template for any element with the same identifier and for which a later version exists in the Global Templates library.
• Displays in a dialog box the latest version of templates that it has found in the dependencies and lets you select:
◦ The usability state for the current version of templates after the new versions are created.
◦ The versioning scheme (see EcoStruxure ™ Process Expert, Global
Templates, Reference Manual) and usability state for the new version of templates that are created.
• Once you proceed, creates the new templates, proceeds with the update, and processes bindings (see EcoStruxure ™
Reference Manual).
Process Expert, Global Templates,
When the Update command is used in a template editor, the software proceeds as follows:
• Verifies if a template with a later version exists in the Global Templates library.
• If so, processes bindings and:
◦ If any binding cannot be recreated, informs you and gives you the choice to proceed or cancel the update.
◦ If bindings can be recreated, proceeds with the update of the template.
NOTE: For the template update process to complete, the latest version of the template or interface model must have the Usability State Approved or
Deprecated .
EIO0000001114.15
Update Dialog Box
The following figure shows an example of the Update dialog box in a scenario where the Update command was used on the MyMotor (1.0.0) control module template in the Global Templates Explorer . The template references MyMotor_
UC (1.0.0) . This UC composite template references MyDEVCTL_UC (1.0.0) , which in turn references the MyDEVCTL_UL (1.0.0) facet template.
MyDEVCTL_
UL versions 1.0.1 and 1.0.2 exist in the Global Templates library.
EIO0000001114.15
4
5
6
7
2
3
Item
1
8
Description
Template of which the software has found a later version in the Global Templates library compared to the version that is currently used.
Templates of which the software will automatically create a later version because the version of their child template is being incremented.
Shows the hierarchy of the templates that will be updated and the templates of which a later version exists in the Global Templates library. Other child templates whose version is unchanged are not shown.
At the top level, identifier of the template from which you have selected the Update command.
Type of the template.
Usability state of the current version of the template after the software has created the new version based on the value of the State strategy parameter.
You can select it individually for templates of which the software creates a new version.
Current version of the template from which you have selected the Update command and current version of its child templates.
Version of the template after the update and latest version of child templates with the usability state Approved that the software has found in the Global Templates library.
For parent templates, the version is created by the software during the update based on the value of the Version strategy parameter.
NOTE: You can modify the version number (see EcoStruxure ™ Process Expert,
Global Templates, Reference Manual) manually for each template version that the software creates during the update. Modifying the version number manually sets the Version strategy parameter to Custom . You cannot enter the same value as in Version .
NOTE: If Version for a template that the software will update is already
99.99.9999
, New Version is blank and you need to enter a value manually.
Allows you to select the usability state of the current version ( Version column) of the templates after the software has created a new version of them.
Default value: Custom
691
692
Item
9
10
Description
Allows you to select the usability state of the new version of the templates after the update.
Default value: Approved
NOTE: The usability state applies only to new template versions that the software creates.
Allows you to select the versioning scheme (see EcoStruxure ™ Process Expert, Global
Templates, Reference Manual) for new template versions that the software creates.
Default value: New Build
NOTE: The version strategy applies only to new template versions that the software creates.
Updating Global Templates in the Global Templates Explorer
Updating Schneider Electric or user-created templates may affect the function of these templates and must be performed by qualified personnel. Before proceeding, refer to the
.
To update Global Templates, proceed as follows.
Step
1
2
3
4
5
Action
In the tree view of the Global Templates Explorer , right-click the template that you want to update and select Update .
Result: The Update dialog box opens.
For the current template version and its elements, select the usability state strategy that you want the software to apply from the menu of the State strategy parameter.
NOTE: If you select Custom , select the usability state for each template in the
State column.
For the new template version and its elements, select the usability state strategy that you want the software to apply from the menu of the Usability State parameter.
For the new template version and its elements, select the version strategy that you want the software to apply from the menu of the Version strategy parameter.
NOTE: You can modify the version number manually for each template that the software will create by double-clicking the New Version field:
• If the version number that you have entered is invalid, the software applies the default versioning scheme for new templates.
• To undo your version change, select New Build as the version strategy. This changes the version of new templates to the default value.
Click OK .
Result: The software:
• Proceeds with the update.
• Displays the new templates that it has created in their respective folders within the
Global Templates library.
• Displays Completed in the notification panel when the update process is completed.
NOTE: Click Cancel to close the dialog box without proceeding with the update.
Updating Global Templates in Template Editors
Updating Schneider Electric Global Templates or user-created templates may affect the function of these templates and must be performed by qualified personnel. Before proceeding, refer to the
To update the template or interface model that is used by an element of a facet or composite template, proceed as follows.
EIO0000001114.15
Step
1
2
3
4
5
Action
In the template editor, right-click the element whose template or interface model you want to update and select Update .
Result: If a later version of the same template or interface model with the required usability state exists in the Global Templates library, the software processes binding information; otherwise, the software indicates that the template is already up-to-date.
Result: If any binding cannot be recreated, the Replace Conflicts dialog box opens; otherwise, the update of the template completes and bindings are recreated.
Verify the information that is displayed in the Replace Conflicts dialog box and click:
• Yes : Proceeds with the update of the template, discards conflicting bindings, and recreates the other bindings.
• No : Closes the Replace Conflicts dialog box without updating the template.
Recreate bindings as needed.
NOTE: To undo a template update that you have performed in a template editor, you can use the Replace
.
Replacing the Template of an Element of a Global Template
Overview
In the Facet Editor and Composite Editor , the Replace context-menu command allows you to replace the template that is used by an element with another template of the Global Templates library.
You can replace the template of the following types of elements:
• Composite templates
• Facet templates
• Interfaces
The software informs you if it detects binding-related conflicts before proceeding with the replacement of the template.
The replacement of the template of an element impacts templates that reference this element and requires
all the higher-level templates.
Restrictions When Replacing Schneider Electric Templates
Restrictions (see EcoStruxure ™ Process Expert, Global Templates, Reference
Manual) related to the identifier of parent templates apply when you replace a template.
Before Starting
Depending on the situation, consider the following before starting:
• To replace the template of an element by the latest version of the same template, use the Update
instead.
• You can use the Replace command to undo the
the software was not able to recreate.
Replace Dialog Box
For a description of the template browser that opens, refer to the topic describing the Replace
EIO0000001114.15
693
Replacing The Template That Is Used by an Element
Modifying Schneider Electric Global Templates or user-created templates may affect the function of these templates and must be performed by qualified personnel. Before proceeding, refer to the
To replace the template that is used by an element of a Global Template, proceed as follows.
Step
1
2
3
4
5
6
Action
In a template editor, right-click the element whose template you want to replace and select Replace .
Result: The Replace dialog box opens.
NOTE: Alternatively, you can select the template in the Browser pane and drag it onto the header of the element until Drop to update the reference with x is displayed in a tooltip (where x represents the name and version of the template that you want the element to use).
Select the template that you want the element to use instead and click OK .
Result: The Replace confirmation dialog box opens.
Verify the information that is displayed and click Yes .
Result: If any binding cannot be recreated, the Replace Conflicts dialog box opens; otherwise, the replacement of the template completes and bindings are recreated.
Verify the information that is displayed in the Replace Conflicts dialog box and click:
• Yes : Proceeds with the replacement of the template, discards conflicting bindings, and recreates the other bindings.
• No : Closes the Replace Conflicts dialog box without replacing the template.
Recreate bindings as needed.
.
694 EIO0000001114.15
Example
The following example illustrates the replacement of the template of a composite element, which is referenced by a parent composite reference. The highest level composite template being $AnalogInput (control module).
EIO0000001114.15
2
3
Item
1
Description
$AnalogInput_UC [1.4.9], which references element AnalogInput is opened in edit mode in the Composite Editor .
Element AnalogInput uses template $AINPUT_UC , which is going to be replaced.
Browser pane that allowed locating template $AINPUT1_UC , which is going to replace $AINPUT_UC .
The software displays the list of bindings that cannot be recreated after the template replacement. Write down these bindings so that you can recreate them later on if required.
695
The figure shows the AnalogInput element after template replacement is complete and the template referencing it has been saved.
696
2
3
Item
1
Description
Element AnalogInput now uses template $AINPUT1_UC . Its identifier is unchanged as shown in the element header and the Properties pane.
The bindings that were listed in the Replace Conflicts dialog box have not been recreated.
$AnalogInput_UC [1.4.9] has to be saved with a different identifier (see EcoStruxure ™
Process Expert, Global Templates, Reference Manual) (for example, MyAnalogInput_
UC [1.2.0]) with Usability state approved .
EIO0000001114.15
Once template replacement is complete, you need to update templates that reference $AnalogInput_UC [1.4.9] so that they use MyAnalogInput_UC [1.2.0] instead. To identify these templates, use the Used by command on $AnalogInput_
UC [1.4.9]. In this example, the command returns $AnalogInput [2.3.1], which uses $AnalogInput_UC [1.4.9] for element Control .
The following figure shows in a partial view, element Control referenced by
$AnalogInput [2.3.1].
EIO0000001114.15
697
To update $AnalogInput [2.3.1] with MyAnalogInput_UC [1.2.0], navigate to
$AnalogInput [2.3.1] and use the Duplicate
command, page 698 . This process
creates a copy with a different identifier, which includes MyAnalogInput_UC
[1.2.0]. In this example, duplicating $AnalogInput [2.3.1] creates MyAnalogInput
[1.0.0]. (The template that is replaced is highlighted for the example.)
NOTE: You may need to update application instances that currently use
$AnalogInput [2.3.1] and/or $AnalogInput_UC [1.4.9] to use the new templates MyAnalogInput [1.0.0] and/or MyAnalogInput_UC [1.2.0] respectively. Use the Replace
to perform the update.
Duplicating Global Templates
Overview
The Duplicate command that is available in the context-menu of templates in the
Global Templates Explorer , lets you create a copy or a new version of any template with the original and/or modified child templates.
For each child template, you can select to keep the original, duplicate (rename or change the version), or replace it by another existing template.
The software informs you if it detects binding-related conflicts because of a template replacement before proceeding with the duplication of the template.
NOTE: This command can be used instead of the Update command for templates whose identifier contains the $ prefix. However, you need to know for which child templates a new version already exists and select it manually.
Restrictions When Duplicating Schneider Electric Templates
Restrictions (see EcoStruxure ™ Process Expert, Global Templates, Reference
Manual) related to the template identifiers apply when you duplicate a Schneider
Electric template .
698 EIO0000001114.15
Good Practices
• Use the Duplicate command as a one-step solution to create a copy of a
Schneider Electric template whose child templates you can edit and save without using the $ prefix (see EcoStruxure ™ Process Expert, Global
Templates, Reference Manual).
• Avoid duplicating templates of the Foundation library and interface models because these are low-level resources that are common to all Schneider
Electric templates to make them widely compatible. You can identify foundation templates by their location.
Duplicate Window
The following figure shows an example of the Duplicate window for a $HandValve sample template in which duplication and replacement actions for child templates have been selected.
EIO0000001114.15
5
6
Item
1
2
3
4
Description
You can
data.
Identifier and version of the template from which you have selected the Duplicate command.
Identifier and version of child templates that the template references.
At each level of the template composition, each template is shown only once even if several instances of it exist.
By default, interface models are not shown.
When you replace a template, the child templates of the replacement are shown under the template to be replaced in read-only mode.
of the template.
Action to be performed for each referenced child template. Each type of action is identified by a colored dot:
• Duplicate (green): Creates a new template. If the template references child templates, they are reused without change unless you duplicate all or some of them as well.
• None (gray): No action is performed. The template is reused in the duplicated parent template.
699
700
12
13
14
Item
7
8
9
10
11
15
16
17
Description
For replacement templates and their children, it is the only setting that is allowed.
• Replace (blue): Opens the Replace
dialog box, page 701 , which lets you select an
existing template in the Global Templates library to be used in place of the current template and its child templates. The replacement template is used for all instances of the current template.
The template must have the usability state (see EcoStruxure ™ Process Expert,
Global Templates, Reference Manual) Approved .
Duplicating or replacing a template automatically sets the action of all parent templates to
Duplicate .
Entries in italic indicate a change that is the result of an action that you have selected.
Free form text fields to enter either a prefix or suffix that is added to the identifier of each duplicated template.
Identifier of the template that is proposed by the software for duplicated templates
(editable) or identifier of the replacement template that you have selected.
Version that is proposed by the software for duplicated templates (editable) or version of the replacement template.
Location in the Global Templates library of:
• An original template ( None action). The location is read-only.
• The duplicated template. You can select a different location and/or add additional ones.
The location that you select must exist. When you select more than one location, the software creates
of the template.
In the location selection dialog box, a check box lets you set the same location for all duplicated templates.
• The replacement template. The location is read-only.
• Child templates of a replacement template ( None action). The location is read-only
Button to modify the location of duplicated templates within the Global Templates library.
Button to open the Replace
to select a different template.
Sets the action of all child templates to Duplicate . Applies to interfaces only if they are shown.
This action overrides changes that you have made for child templates for which you have selected the Replace action.
NOTE: You cannot revert this action for all templates at once.
When selected, shows the interface models that are referenced by child templates. You can select an action for each interface model. Toggling the view does not impact changes that you have made.
Lets you select the usability state (see EcoStruxure ™ Process Expert, Global Templates,
Reference Manual) that is set for all duplicated templates.
Free form text field to enter a description of the changes.
Duplicating Global Templates
Duplicating Schneider Electric Global Templates or user-created templates may affect the function of these templates and must be performed by qualified personnel. Before proceeding, refer to the
To duplicate a global template, proceed as follows.
Step
1
2
3
4
5
Action
In the tree view of the Global Templates Explorer , right-click the template that you want to duplicate and select Duplicate .
Result: The Duplicate window opens.
Select an action for referenced child templates as needed.
Configure the parameters for duplicated templates as needed.
Select a usability state for duplicated templates.
Click OK .
EIO0000001114.15
Step Action
6
7
Result: If the software detects no binding-related conflicts, it duplicates the template based on your selections; otherwise, the Replace Conflicts dialog box opens.
Verify the information that is displayed in the Replace Conflicts dialog box and click:
• Yes : Proceeds with the duplication of the template and discards conflicting bindings.
• No : Closes the Replace Conflicts dialog box and reverts to the Duplicate window.
Recreate bindings as needed.
Replace Dialog Box
Overview
The Replace dialog box opens when you select the corresponding command in the Duplicate
or in the context menu of an element in a
.
It lets you browse the Global Templates library to select a replacement template.
Description
The browser of the Replace dialog box behaves like the
of the Global Templates Explorer with the following exceptions:
• The scope of the search is context-sensitive.
• Facet templates are shown by default.
• Only templates with the usability state Approved are shown.
EIO0000001114.15
701
Software Services
What’s in This Part
Overview
This part describes the services that are provided by the software to facilitate the engineering of systems.
702 EIO0000001114.15
Content Repository
What’s in This Chapter
Temporary Contents Repository Files ........................................................... 706
Content Repository Explorer
Overview
The content repository is the place where the software stores:
• Global files used by Global Templates and that are required by the software platform to provide various services (for example, global constituents referenced by templates). These files are associated to the library that is installed during the installation of the software and to optional application libraries.
• System-related files (for example, logical Participant projects or user files attached to a Supervision project or to instances). These files are created during the different stages of the system engineering life cycle.
You cannot add to or remove files directly from the content repository. The software removes from the content repository system-related files such as
Participant project files when they are not required anymore (for example, when you delete a Participant project). An exception exists for documents that you can manage yourself (see EcoStruxure ™ Process Expert, Runtime Navigation
Services , User Guide ).
Each system server possesses one content repository in which the global and system-related files are stored.
The Content Repository explorer is the tool, which lets you view contents in the form of a folder structure and work with the files that are stored in the content repository.
Opening the Content Repository Explorer
To open the Content Repository explorer click the Content Repository icon in the
EIO0000001114.15
703
Content Repository Explorer Window
The following figure shows an example of the Content Repository explorer window.
3
4
5
6
7
1
2
Content repository root folder.
Root folder for global content repository items that are available at the platform level (system independent).
User Contents folders that are the parent folder of the folder structure and content containers that you can add depending on your role.
User-created content container.
Root folder for content repository items that are available to systems.
Root folders for content repository items that are available only to one given system.
User-created content container open in the content editor.
Description of the Contents of the Repository
The following data is stored in the content repository under the Global Root
\Global Templates parent folder.
704 EIO0000001114.15
Node Contains
Global Constituents Global Control and Supervision Participant constituents (such as variables,
DFBs, included projects).
Local Constituents
User Contents
Control facet templates of the Global Templates library and for each facet, the referenced local constituent sources and the referenced global constituents
Documents (files) that can be managed by users having the appropriate role (see EcoStruxure ™ Process Expert, Installation and Configuration
Guide). They are delivered with the software and organized in a predefined folder structure and content containers (see EcoStruxure ™ Process Expert,
Runtime Navigation Services , User Guide ).
These documents can be opened when viewing instance information by using runtime navigation services.
They can be associated either to templates or instances.
The following data is stored in the content repository under the Systems parent folder.
Node
<system identifier>
Project
Topology
Upro
VJC
User Contents
Contains
For each system that exists in the database of the system server, the complete set of files defining the various existing Participant projects, their components, and topological entities.
Data is grouped by Participant.
The logical Participant projects under the folder with the name of the project.
If you update the logical Participant project by using the Update Project command, the project file is updated, reflecting the changes.
For each Participant project, data of the various components of the logical
Participant project such as:
• Section export files under the folder with the name of the section.
• The built Participant projects under the folder with the name of the executable.
Configuration files and profiles of the entities that exist in the topology of the system (under the folder with the name of the entity).
For entities that you configure by using the Control Participant, the corresponding project files.
For each entity of the system, the deployed Participant project. If you do online refinement, the file is updated, reflecting the changes.
For each Supervision Participant project of the system, the various project files such as database and configuration files.
User documents (files) that can be added and managed by users having the appropriate role (see EcoStruxure ™ Process Expert, Installation and
Configuration Guide). They are organized in a user-created folder structure and content containers (see EcoStruxure ™ Process Expert, Runtime
Navigation Services , User Guide ) at the system level.
These documents can be opened when viewing instance information by using runtime navigation services.
They can be associated either to templates or instances.
Content Repository Root Folder Actions
Right-click the Content Repository root folder to open a context menu with the following commands.
Command Description
Export
User
Contents
Opens the Export User Contents
(see EcoStruxure ™ window, which lets you export content containers
Process Expert, Runtime Navigation Services , User Guide ) with the documents they contain as a single file (.cbk).
Import
User
Contents
Opens the import window, which lets you select an export file (.cbk) to import (see
EcoStruxure ™ Process Expert, Runtime Navigation Services , User Guide ) the folders and content containers it contains.
EIO0000001114.15
705
Content Repository File Actions
Starting out from one of the previously mentioned parent folders:
1. Drill down to the lowest level folder of a node until you reach the Contents
List tab (this requires opening the folder).
2. Right-click a content and select View Content Detail .
In the Detail tab, right-click a file to open a context menu with the following commands.
Command Description
View Opens the file by using the program that is associated to it. The program must be installed on the computer.
NOTE: You cannot save changes in the content repository when you open a file by using this command.
Save As Opens a dialog box, which lets you save a copy of the file by selecting a location and a file name.
NOTE: To be able to open a Control Participant project file (.stu) in a standalone installation of Control Expert, the version of Control Expert and of the installed EcoStruxure Control Expert DTM Library need to be the same as the Control Participant. For information on the installed version, refer to the platform release notes.
Temporary Contents Repository Files
Overview
The system server stores temporary files from the content repository inside a folder structure to access the files it needs faster. If needed the software creates the temporary storage folders when you start the system server.
Temporary File Folder Location
The folder is named Process Expert x, where x corresponds to the major version of the software that is installed (the R• version suffix does not appear). It is located on the computer on which the system server is installed, at the path C:\Users
\<UserName>\AppData\Local\Temp\Schneider Electric.
Reclaiming Disk Space
With time, the size of this temporary file folder increases.
You can reclaim disk space by deleting the subfolders and files inside the Process
Expert x folder when the software is not running.
706 EIO0000001114.15
Language Settings
What’s in This Chapter
Default Keyboard Layout of the Virtual Machine............................................. 707
Default Keyboard Layout of the Virtual Machine
Overview
The software is designed in such way that software Participants capture the keyboard layout of the computer on which the engineering client is running.
For this mechanism to work, the keyboard layout used by the computer needs to be available in the operating system of the virtual machine (VM).
Therefore, many keyboard layouts are preloaded in the operating system of the
VM.
It can happen that the computer on which the engineering client is running is configured with a keyboard layout that is not available in the operating system of the VM. In such case, Participants use the default keyboard layout .
If the default keyboard layout ( US ) is not suitable, you have the following choices:
• Select a different default keyboard layout from the list of available layouts that is better suited than the US layout.
• Add a keyboard layout to the ones preloaded in the operating system of the
VM and make it the default one.
You can change the default keyboard layout by using the configuration wizard of the software component, which hosts the VM that the engineering client is using.
For example, if the engineering client uses the VM of the system server, change the keyboard layout by using the configuration wizard of the system server.
Refer to the topic describing the configuration of the virtual machine (see
EcoStruxure ™ Process Expert, Installation and Configuration Guide).
Switching Keyboard Layouts on the Fly
When you change the keyboard layout of your computer while working, you can also apply the change to Participants. Refer to the section providing general information in the corresponding Participant Services User Guide .
Preloaded Keyboard Layouts
You can view the list of keyboard layouts that are preloaded in the operating system of the VM by opening the locales.def
file located at the following path:
For the system server C:\Program Files\Schneider Electric\EcoStruxure\Process Expert\System
Server\Configuration.
For the engineering client
C:\Program Files\Schneider Electric\EcoStruxure\Process Expert
\Engineering Client.
For each language, the information is structured as follows: parameter1 ; parameter2 ; parameter3 ; parameter4 , where:
• parameter1 represents the Default keyboard layout and the System Locale parameters
• parameter2 represents the second System Locale parameter (for example
(en-US) )
• parameter3 represents the system locale code
EIO0000001114.15
707
• parameter4 represents the keyboard layout code
The parameters defining the keyboard layout are parameter1 and parameter4 .
Determining the Current Keyboard Layout
The current keyboard layout is indicated by the Default keyboard layout parameter in the configuration wizard.
NOTE: The default configuration is US .
Changing the Default Keyboard Layout
Changing the default keyboard layout requires that you stop the system server if the engineering client uses the VM of the system server.
NOTICE
LOSS OF COMMUNICATION
Stop the system server only when no client is running.
Failure to follow these instructions can result in unresponsive clients.
To change the default keyboard layout of the operating system of the VM, proceed as follows.
Step
1
2
3
4
Action
Open the configuration wizard of the software component, which hosts the VM that the engineering client is using. Refer to the topic describing the configuration of the virtual machine (see EcoStruxure ™ Process Expert, Installation and Configuration Guide).
In the Virtual Machine section, select a language for the Default keyboard layout parameter.
Click Finish .
Restart the software component, whose configuration wizard you have updated.
Result: The change is applied.
NOTE: Even if you change the default keyboard layout parameter,
Participants continue using the same keyboard layout as the one of the computer running the engineering client, given that this layout is already
loaded in the operating system of the VM, page 707
.
Adding Keyboard Layouts
After you add a keyboard layout to the operating system of the VM, you can select it in the configuration wizard under Default keyboard layout .
Adding a keyboard layout requires that you stop the system server if the engineering client uses the VM of the system server.
NOTICE
LOSS OF COMMUNICATION
Stop the system server only when no client is running.
Failure to follow these instructions can result in unresponsive clients.
To add a keyboard layout to the operating system of the VM, proceed as follows.
708 EIO0000001114.15
Step Action
1 By using a text editing software, open the software component.
of the appropriate
2 Add, at least, the
parameters defining the keyboard layout, page 707 .
NOTE: Even if you enter only 2 parameters, enter the 3 semi-colons (for example:
French;;;0000040c represents only the French keyboard layout).
3
4
Save the changes.
Restart the software component.
Virtual Machine System Locale
Overview
The software allows you to set the system locale setting of the operating system of the VM, which controls the language used to display text in non-Unicode programs, such as the Supervision Participant.
The default system locale is ( US (en-US) ), which allows to display English and some other western languages using characters contained in the Windows-1252 code page layout.
You can change the default keyboard layout by using the configuration wizard of the software component, which hosts the VM that the engineering client is using.
For example, if the engineering client uses the VM of the system server, change the keyboard layout by using the configuration wizard of the system server.
Refer to the topic describing the configuration of the virtual machine (see
EcoStruxure ™ Process Expert, Installation and Configuration Guide).
For information on the system locale setting of the Windows ® operating system, refer to Language for non-Unicode programs by clicking, starting from the
Windows ® Control Panel , Clock, Language, and Region > Region >
Administrative .
Available System Locale
You can view the list of system locale that are preloaded in the operating system of the VM by opening the locales.def
file located at the following path:
For the system server C:\Program Files\Schneider Electric\EcoStruxure\Process Expert\System
Server\Configuration.
For the engineering client
C:\Program Files\Schneider Electric\EcoStruxure\Process Expert
\Engineering Client.
For each language, the information is structured as follows: parameter1 ; parameter2 ; parameter3 ; parameter4 , where:
• parameter1 represents the Default keyboard layout and the System Locale parameters
• parameter2 represents the second System Locale parameter (for example
(en-US) )
• parameter3 represents the system locale code
• parameter4 represents the keyboard layout code
The parameters defining the system locale are parameter1 and parameter3 .
Determining the Current System Locale
The current system locale is indicated by the System Locale parameter in the configuration wizard.
NOTE: The default configuration is US (en-US) .
EIO0000001114.15
709
Changing the System Locale
Changing the system locale requires that you stop the system server if the engineering client uses the VM of the system server.
NOTICE
LOSS OF COMMUNICATION
Stop the system server only when no client is running.
Failure to follow these instructions can result in unresponsive clients.
To change the system locale of the operating system of the VM, proceed as follows.
Step
1
2
3
4
Action
Open the configuration wizard of the software component, which hosts the VM that the engineering client is using. Refer to the topic describing the configuration of the virtual machine (see EcoStruxure ™ Process Expert, Installation and Configuration Guide).
In the Virtual Machine section, select a language for the System Locale parameter.
Click Finish .
Restart the software component, whose configuration wizard you have updated.
Result: The change is applied.
Adding a System Locale
After you add a system locale to the operating system of the VM, you can select it in the corresponding configuration wizard under System Locale .
Adding a system locale requires that you stop the system server if the engineering client uses the VM of the system server.
NOTICE
LOSS OF COMMUNICATION
Stop the system server only when no client is running.
Failure to follow these instructions can result in unresponsive clients.
To add a system locale to the operating system of the VM, proceed as follows:
Step Action
1 By using a text editing software, open the software component.
of the appropriate
2
3
4
Add, at least, the
parameters defining the system locale, page 709
Save the changes.
Restart the software component.
.
710 EIO0000001114.15
Appendices
What’s in This Part
Linking Instances by Using the Links Editor ................................................... 712
EIO0000001114.15
711
Linking Instances by Using the Links Editor
Linking Instances by Using the Links Editor
What’s in This Chapter
Linking Instances by Using the Links Editor ................................................... 715
Links Editor
Overview
The Links Editor lets you link the exposed application interfaces of an instance to the interfaces of other instances that are compatible and respect the cardinality of the roles (for example, 1 to 1, or 1 to n ). The editor also allows you to change or delete existing application links between instances.
You can use the Links Editor , for example, to map a signal to an application object such as a limit switch signal to the corresponding input of a valve motor.
Some instances require that you link them to other instances depending on the interface rules of their templates (for example, you need to link the instance of a motor starter template $TesysTMB to a communication instance such as a port
$MBPortQ ); otherwise the status of the
of the device instance remains Invalid .
Link any instance with an Invalid
status with the Links Editor to change the status to Valid since it is prerequisite to proceed further in the system engineering life cycle.
NOTE:
• Linking instances by using the Links Editor helps avoid having to create such links later by refining the Control Participant project and provides a level of consistency in terms of Control resource names.
• Linking an instance to itself is not allowed. If this is required, edit the template used by the instance or refine the Control project to which facets of the instance are assigned.
Naming Rules for Variable Names
The name of the variable that is created by linking two instances needs to satisfy the
for the subsequent generation process to complete successfully.
Instance and Links Appearance
In the Links Editor , instances appear as follows:
• With a green outline: Applies to the instance for which you have selected the Edit Links command and, which is referred to as active . Only one instance can be active in the same Links Editor tab.
• With a gray outline: Applies to instances that you can link, which are referred to as inactive .
NOTE: Active and inactive instances can be selected in which case a green border appears around them.
The following colors are used for application interface links:
• Orange: Default color.
• Blue: When an instance is selected to highlight links that are connected it.
712 EIO0000001114.15
Linking Instances by Using the Links Editor
Opening the Links Editor
To open the Links Editor , proceed as follows.
Step
1
Action
Right-click the instance that you want to link to one or more other instances, and select
Edit Links .
Result : The Links Editor tab opens inside the
of the Application
Explorer and displays the selected instance in the center of the editor. The instance appears as
NOTE: If the active instance is already linked to other instances, these are shown and appear as inactive.
Links Editor
The following figure shows an example of the Links Editor , which is open in the work area of the Application Explorer .
3
4
5
6
8
9
Item
1
Description
2
7
Application Browser pane of the Application Explorer from which you can drag instances that you want to link.
Indication of the Link status of the active instance and button to display the Validity
Diagnosis window if the status is Invalid .
instance from which you have selected the Edit Links command.
Inactive instance, which was already linked with the active instance or which you have linked.
Application interface link.
Inactive instances, which you have dragged from the Application Browser pane to the editor and which you can link with the active instance.
RTNS interfaces, page (runtime navigation services). Appear in blue and are located in the header section of the instance.
NOTE: You can also
move the editor background, page 81
.
Impact of Modification of Instance Properties
When you edit an instance by using the Instance Editor and saving the change disables an interface that was linked, the link is automatically removed.
EIO0000001114.15
713
Linking Instances by Using the Links Editor
This may set the Link
of either linked instances to Invalid .
Viewing Interfaces and Interface Description
Not all interfaces of instances that are displayed in the Links Editor are visible by default. You may need to expand nodes of the interface to show enabled (green) or disabled (gray) interfaces.
To enabled an interface, edit the instance and select the element that contains the interface, and/or configure the element parameter that enables it.
Move the pointer over any interface of an active or inactive instance in the Links
Editor to display a description of the interface in a tooltip.
NOTE: An interface may be compatible, unbound, and enabled but
.
Viewing Linked Instances
Right-click a link between two instances and select Go to . A submenu opens and displays:
• The identifiers of the two instances that are linked.
• For each instance, the name of the element that exposes the interface and its path.
Click an entry to view the instance and highlight the element in the editor.
714 EIO0000001114.15
Linking Instances by Using the Links Editor
Linking Instances by Using the Links Editor
Creating Interface Links
To create an interface link between two instances, proceed as follows.
Step
1
2
3
4
5
6
7
Action
From the Application Browser pane, drag the instance that you want to link next to the
, which is displayed in the Links Editor .
Result : The instance is shown next to the active instance as inactive.
NOTE: You can drag additional instances to the editor.
From the active or inactive instance, position the pointer over an interface and when the pointer turns into a hand, click and move the pointer away from it while holding down the left mouse button.
Result : A green line appears and follows the pointer. You can release the mouse button.
NOTE: Press ESC to return to the normal pointer function.
Move the pointer over the other instance.
Result : The software automatically highlights compatible and
interfaces of the instance and snaps the green line to the nearest matching connector.
Click to confirm the connection or move the pointer to another highlighted interface until the line snaps to it.
Result: When you click, the software:
• Links the interfaces of both instances with a line.
• Changes the status of the active instance to Valid if the interface rules are satisfied (if applicable).
NOTE: To delete the link, right-click the line and select Delete .
Verify that the status of the active instance is Valid ; otherwise click the validity status information button to display the Validity Diagnosis window and make the required links until the instance status becomes Valid .
NOTE: You can only make links between an active and an inactive instance. To link the inactive instance with another inactive instance, right-click the header of the inactive instance and select Edit Links . The inactive instance becomes active.
Repeat steps 1...5 until you have made the required links.
Close the Links Editor tab.
Removing Instances from the Links Editor
You can remove inactive instances from the Links Editor .
To do so, right-click the header of the inactive instance that you want to remove and select Remove Instance . This also removes links that may exist with the active instance after you confirm the command.
NOTE: The software does not remove interface links that the instance that you are removing may have with other instances, and which are not displayed in the current Links Editor tab.
Enabled Interfaces That Cannot Be Connected
The interface of an
instance may appear as enabled, unbound, and be compatible but the link does not snap to it. This can be the case if a link with the interface exists but is not visible and the interface accepts only one connection at a time.
To view the links of an instance, open it in the Links Editor so that it is the active instance or open the Inspect Instance
EIO0000001114.15
715
Linking Instances by Using the Links Editor
In the following example, interface ILCK of Motor_1 is connected to DISignal_UL_
1 and the Links Editor is closed.
When you open the Links Editor for DISignal_UL_2 and drag Motor_1 to the editor, its ILCK interface appears enabled. Yet, the link being created from
DISignal_UL_2 does not snap to ILCK . This is because Motor_1 is an inactive instance and its links to other instances ( DISignal_UL_1 ) are not shown in this view.
716 EIO0000001114.15
Glossary
EIO0000001114.15
A application interface:
Mechanism that allows sharing data and manage dependencies between 2 instances/references.
The application interface allows you to link:
• applications instances/references to each other
• topological instances/references to each other application link:
Links describing connections between instances of the application that are made by using application interfaces.
application template:
Global Template contained in the Global Templates library that models an object of the application of a system and its associated functions. The template encapsulates the necessary Participant capabilities.
Application templates are instantiated and can be configured to create the application of a system.
application:
The application models the complete functionality provided by the system through an application folder structure and instances of application templates.
area:
The area , when referring to access control, defines a topological, functional, or another user-based rule to restrict access in the scope of an automation system.
B binding:
The binding is the key mechanism that establishes relations between the following items of the facet and composite templates:
• Parameters
• Interfaces
• Elements built Participant project:
The built Participant project is a generated, optionally refined, and built project, which is created by the corresponding Participant and that exists at the platform level in the form of an executable.
For example, files with .stu
and .ctz
extensions that are represented by Control and Supervision executables respectively are built Participant projects.
C cardinality:
The cardinality , in the context of the interface model, is the number of connections that are supported by the objects playing the other role of the interface model.
communication channel:
A communication channel is the logical representation, at the platform level, of communication between controllers or between a controller and devices.
For example, a controller I/O scanner row is modeled by a communication channel for Modbus TCP communication in the executable of the Control project.
717
718 communication interface:
Mechanism that allows sharing data and manage dependencies between 2 instances or references.
Communication interfaces allow the platform to link topological instances/ references at the logical level (for example, I/O scanner, OPC Factory Server,
Supervision I/O devices).
communication link:
Links describing logical connections between topological instances that are made by using communication interfaces.
For example, the communication link between 2 controllers exchanging data.
communication mapping:
The communication mapping process defines the communication aspects of a logical Participant project after being mapped to the topology.
composite template:
The composite template combines the capabilities of 1 or more facet templates, each encapsulating functionalities provided by one software Participant, and/or of other composite templates .
composite:
The composite is an instance of a composite template.
constituent encapsulation:
Process that is performed by using the Facet Editor and that allows you to:
• Select constituents that are created with a software Participant.
• Optionally, modify constituents inside the corresponding Participant.
• Include the selected constituents inside a facet template.
constituent:
Set of data provided by a software Participant, which can be
or
.
contents repository:
The contents repository is a global storage provided by the platform to manage global constituents and other files, such as Participant projects, used by the libraries and the systems.
D deferring mechanism:
Mechanism that allows you to make available in the composite template that is at the highest level optional element selections, parameters, and/or interfaces of its references.
deployed Participant project:
A deployed Participant project is a built project that has been transferred to a controller or other entity of the topology acting as an engine, and that you can execute.
DFB type:
The derived function block type is a programming language element that consists of:
• A data structure definition partitioned into input, output, public, and internal variables.
• A set of operations written in IEC 61131 programming languages to be performed upon the elements of the data structure when an instance of the function block type is started.
EIO0000001114.15
EIO0000001114.15
E
EcoStruxure Process Expert:
Third generation name of the software platform. Formerly, StruxureWare Process
Expert then, EcoStruxure Hybrid DCS.
element:
Element is the term that is used to describe the contents of templates at the next lowest level as well as the contents of interface models:
• For facet templates, elements are the constituents that the facet encapsulates.
• For composite templates, elements are:
◦ Facet references
◦ Composite references
• For interface models, elements are the data that is shared. See interface elements .
You can define properties and rules for elements during the Global Templates definition stage.
engine:
An engine is the projection of the hardware and software defined in the topology that is able to execute the deployed Participant project.
engineering client:
EcoStruxure Process Expert client connecting to the system server that you use to engineer and maintain systems. It can run on the system server and/or an engineering station.
Each client hosts a virtual machine in which the software Participants are running.
engineering station:
The engineering station is a computer running an EcoStruxure Process Expert engineering client to design, and maintain systems that exist on the server to which the engineering client connects.
executable:
The executable is a project component that represents the built Participant project. It contains the mapping information.
execution domain:
Property of the executable of a Participant project, which serves as a filter for selecting the scope of applicable services.
For example, it is used to define the boundaries for runtime navigation services or to restrict the exchange of data through peer to peer communication between projects that have executables with the same execution domain.
F faceplate:
The faceplate is a component of a Supervision genie that provides a user interface to interact with the object that it represents.
facet element:
The facet element is the contents that can be accessed at the system level.
Depending on the type of facet template, such elements can be either:
• The visible part of the constituents stored in the facet templates.
• A set of data defined by the facet template.
facet template:
719
720
The facet template is the smallest available template that encapsulates a specific capability provided by 1 software Participant only.
facet:
The facet is an instance of a facet template.
G genie:
Animated graphic that is assigned to Supervision pages and that represents functionalities of instances of the application during operation.
Genies are encapsulated in Supervision facets.
global constituent:
Set of data provided by a software Participant that is a common resource referenced by several Global Templates. Global constituents are stored in the contents repository.
Global Templates:
Global Templates encapsulate one or more functions that can be customized and reused in any system created with EcoStruxure Process Expert. They are stored in the Global Templates library.
H hardware mapping:
The hardware mapping process links the logical projection of the hardware that is defined in the application and assigned to projects to the hardware defined in the topology of the system.
For example, linking Control variables representing I/O signals to I/O channels of an I/O module.
HMI:
Abbreviation for human machine interface . It is a graphical operator interface for industrial equipment.
I
IEC:
The International Electrotechnical Commission is a non-profit and nongovernmental international standard organization that prepares and publishes international standards for electrical, electronic, and related technologies.
instance element selection:
The instance element selection is a mechanism of the instantiation stage that allows you to customize an instance by selecting services that are provided by the template that the instance uses.
instance parameter:
Instance parameters are properties of the elements of an instance that you may be able to customize.
instance:
Abbreviation for object instance. It is the result of the instantiation of a template.
instantiation naming convention:
The instantiation naming convention defines the naming strategy that the platform applies when you create instances.
EIO0000001114.15
EIO0000001114.15
interface element:
Represents the data that will be shared through an interface. Interface elements are defined during in the interface definition. Interface elements can be transformed by the interface by using expressions.
interface link:
Links describing logical connections between instances that are made by using interfaces.
The following types of links exist:
• Physical links
• Communication links
• Application links
Each type of link is made by using the corresponding interface (physical, communication, or application interface).
interface model:
The interface Model is a type of template that is available in the Global Templates library and that you can configure.
interface:
The interface is a reference, inside a composite or facet template, of an interface model. Interfaces are exposed by the facets of an instance, allowing you to make different types of links with other instances to share data.
In the context of the template definition, interfaces are a mechanism to define the links between references by declaring compatibility and/or requirement rules.
I/O:
Abbreviation for Inputs/Outputs .
L local constituent:
Set of data that is provided by a software Participant, encapsulated inside a facet template but not used at the system level. The local constituent is used to generate the contents of the logical Participant project. An example is Control
Participant code that is encapsulated in a Control facet template.
logical Participant project:
The logical Participant project is a generated and refined project, which is created by the Participant but, which is not associated to the topology.
NOTE: The refinement of the project is optional.
M mapping interface:
Mechanism that allows sharing data between two facets.
Mapping interfaces allow you to perform the hardware mapping. It is the process whereby you link facets assigned to projects to facets representing the hardware defined in the topology through matching mapping interfaces that these facets expose.
MES:
The Manufacturing Execution Systems is a control system for managing and monitoring work-in-process in a factory plant.
721
722
N network variable:
The network variable is a peer to peer communication mechanism allowing you to share data between 2 or more Control projects.
O object template:
An object template is a generic term that covers several reusable templates such as facet or composite templates.
OFS:
Abbreviation for OPC Factory Server.
operation client:
An EcoStruxure Process Expert client connecting to the system server that you can use during runtime to monitor and troubleshoot a system.
operator station:
The operator station is a computer running a Supervision client software.
P
Participant services:
Participant services are the functions provided by a software Participant when interacting with EcoStruxure Process Expert.
peer to peer communication:
Peer to peer communication is a data exchange mechanism between 2 or more
Control projects, which uses the I/O scanner function of the controller acting as client.
physical (interface) link:
Links describing logical connections between topological instances that are made by using physical interfaces.
For example, the connection of a controller to an Ethernet network.
physical connection:
Link between topological entities representing the physical connections between controllers, station nodes, devices, and communication networks.
physical interface:
Physical interfaces allow the platform to link, at a physical level, topological instances to model the topology of the system.
platform:
Abbreviation for system platform. Represents the services that are provided by
EcoStruxure Process Expert apart from the software Participants.
privilege:
Defines groups of functions that are provided by an application and granted to users through access control.
project container:
The project container is an organizational structure of a project to organize the facets that are assigned to it. Such a structure models the ones managed by the corresponding software Participant, and that are visible at the system level.
EIO0000001114.15
EIO0000001114.15
project facet:
Facet that is assigned to a project.
project:
Component of a system associated to a software Participant. Its structure contains elements that are managed by the software participant.
R redundant controller:
Generic term that is used to refer a Quantum Hot Standby controller and/or an
M580 redundant controller.
reference:
Defines facet and composite templates, which are contained inside other facet or composite templates in order to distinguish templates, which are used in the composition of other templates from the highest level templates, such as control modules.
role:
The role can have 2 different meanings,
• For access control:
The role groups functionalities to grant different levels of user rights, which combine areas and privileges to fulfill a set of services.
• For interface models:
The role defines the 2 sides of an interface, role A and role B.
runtime navigation services:
Describes the complete set of functionalities that are provided by EcoStruxure
Process Expert operation client in runtime, such as process monitoring, viewing of instance information, diagnostics.
S service mapping:
The service mapping links the execution capabilities of a project represented by the executable to an engine of the topology.
For example, it can link:
• The I/O server of a Supervision project to a station node representing the operation server.
• The executable of a Control project to a controller.
service:
In the context of projects, the project service is an organizational structure of a project to organize the execution capabilities. It models the structures that are managed by the corresponding software Participant, and that are visible and configured at the system level.
In the context of templates, a service represents a functionality provided by a
Participant under the form of a facet referenced by the template.
software Participant:
An external tool that is running in the virtual machine and which collaborates with the platform. For example, the Control Participant.
software:
Refers to EcoStruxure Process Expert.
station node:
723
724
A station node represents a computer that can act as an engine to execute a
Control project by using software emulating a simulator, or a Supervision project by using Supervision software.
subnet mask:
A 32-bit value that indicates the number of available host addresses on a subnet, which uses TCP/IP knowing that the first and last addresses are reserved (for example, subnet mask 255.255.192.0 allows 317 addresses for classless devices). It also indicates whether addressing is classful or classless. For classful addressing, it indicates the class of the network (for example, 255.255.255.0 is the subnet mask for class C networks).
Supervision client:
Client connecting to the Supervision server that provides runtime services to operate and monitor automation systems. The client runs on an operator station and/or operation server.
Supervision server:
Server running on the operation server or on the system server, and that provides runtime data to Supervision clients.
system engineering life cycle:
The system engineering life cycle represents the stages to engineer a system in
EcoStruxure Process Expert.
system server:
EcoStruxure Process Expert server that hosts:
• A virtual machine running the software Participants
• The database containing template libraries and system data
The system server manages requests from the EcoStruxure Process Expert clients.
system:
Models a physical automation system.
The system consists of the following components:
• Topology
• Application
• Participant projects
T topological entity:
A topological entity is the representation of piece of hardware infrastructure.
For example, a controller.
topology:
Models the hardware and software infrastructure of a system through topological folders and entities.
V virtual machine:
A software implementation emulating the architecture and functions of an actual computer, which supports the execution of an operating system. The EcoStruxure
Process Expert system server hosts a virtual machine (VM) that uses a Microsoft ®
Windows ® operating system to run the software Participants.
EIO0000001114.15
Index
$EGenericDeviceHW template
generic device mapping interfaces .................... 443
$GenericDevice
implementing communication............................ 598
$GenericNOC_UL
implementing communication............................ 598
$GenericPBSlave template
generic device mapping interfaces .................... 443
$GenNOCDevice
implementing communication............................ 598
$PRMMgt templates managing Modbus TCP communication (I/O
scanning)....................................................... 601
$System
$System parameters of instances...................... 141
A aborting
abort task icon ...................................................54
application import command ............................. 194
back up command............................................ 109
build command (control) ................................... 468
build command (supervision) ............................ 477
Deploy Built Project command (supervision station
node)............................................................. 526
Deploy Built Project command (supervision) ...... 522
Deploy Changes command (supervision)........... 528
export command .............................................. 170
export command (control) ................................. 210
export command (supervision) .......................... 241
export command (topology) .............................. 410
folder delete command ..................................... 125
Generate and Build command for projects ......... 299
Generate command for project containers.......... 322
Generate command for projects ........................ 321
import command (control) ................................. 222
import command (supervision) .......................... 250
import command (topology) .............................. 417
instance delete command ................................. 132
paste command ............................................... 158
Purge command .............................................. 687
ReGenerate command for projects .................... 328
restore command ............................................. 111
template export command ................................ 678
template import command ................................ 685
Update Control Project command...................... 575
About Process Expert
About dialog box ................................................78
opening the about dialog box ..............................77
actions
on assigned facets ........................................... 292
on generated facets ......................................... 332
activity
log files .............................................................59
notification panel................................................54
addresses generating network addresses for supervision
components ................................................... 476
identifying engines ........................................... 483
Advantys
selecting templates .......................................... 368
alarm server redundancy
implementing ................................................... 237
analysis
analyzing configuration changes (M580 safety) .. 588
analyze issues
troubleshooting control Participant projects ........ 339
validity indicators ............................................. 467
Analyze Project
control project settings...................................... 205
analyzing
control projects during generation...................... 300
application
import rules for control project-related objects .... 213
import rules for supervision project-related
objects .......................................................... 244
modeling the application of systems .................. 115
Application Browser pane
presentation .................................................... 122
using and customizing ...................................... 121
Application Explorer
accessing ........................................................ 117
opening .............................................................77
presentation .................................................... 117
application export files
using the invariant culture ................................. 176
application folders
actions ............................................................ 125
changing folder structure .................................. 158
changing the application hierarchy .................... 156
copying and pasting ......................................... 157
creating ........................................................... 125
managing ........................................................ 155
moving ............................................................ 158
properties ........................................................ 126
application objects
exporting and importing to XML or CSV ............. 168
application passwords changing the application password of control
projects ......................................................... 492
clearing the application password of control
projects ......................................................... 493
managing passwords of control projects ............ 488
resetting a forgotten application password ......... 493
setting the application password of control
projects ......................................................... 491
application structure
tree view description in Containers pane ............ 287
tree view when refining Control projects............. 339
tree view when refining Control projects online ... 550
application templates
description.........................................................23
Asset Workspace Editor....................................... 146
using the radar view ......................................... 672
using the simplified view ................................... 149
Asset Workspace pane ........................................ 143
asset workspaces
exporting ......................................................... 168
assigned facets
generating automatically assigned facets........... 299
managing assigned facets ................................ 292
unassigning generated facets ........................... 334
assigning
Assignment Viewer description ......................... 277
facets (control)................................................. 279
facets (supervision) .......................................... 281
Assignment Editor
presentation .................................................... 257
assignment stage
completing....................................................... 256
concept .............................................................34
EIO0000001114.15
725
Assignment Viewer
description....................................................... 277
View Assignments window................................ 294
assignments
automatic assignment of remaining facets.......... 284
automatic assignment of Supervision facets....... 285
viewing by instance .......................................... 294
audit trail
functionality description ......................................56
authentication
logging in to server and clients ............................44
automation system
description.........................................................26
automation systems
description.........................................................19
B back up command
aborting........................................................... 109
backing up
backing up systems.......................................... 108
backing up data
backing up controller data ................................. 554
backup password information and settings in system
backups......................................................... 109
backup files
managing data backup files (control) ................. 224
batch
modeling the equipment hierarchy..................... 116
BMENUA0100
variable tag addresses ..................................... 476
boards
creating communication boards (supervision)..... 235
bold formatting
editing instance properties ................................ 140
browsers
Templates Browser presentation ....................... 120
build command
aborting (control).............................................. 468
aborting (supervision)....................................... 477
build stage
completing....................................................... 464
concept .............................................................40
control projects ................................................ 464
supervision project ........................................... 475
build states
when deploying (supervision)............................ 522
build status
actions changing the build status (control).......... 470
building the logical supervision project ............... 477
changes affecting the build status (control)......... 469
verifying before deploying (control) .................... 496
when deploying from station node
(supervision) .................................................. 524
building
building safety control projects .......................... 592
creating the built Control Participant project ....... 464
network addresses of supervision components... 476
building changes (control)
building with device DDT variables .................... 471
building control projects
building with device DDT variables .................... 466
building supervision projects
Generate and Build command........................... 477
built Participant projects
726
changing (control) ............................................ 470
changing (supervision) ..................................... 479
C calculated variable tags
I/O device properties ........................................ 234
canceling canceling generation for version conflict
(control) ......................................................... 301
capabilities
hardware ...........................................................61
programming .....................................................61
CCOTF............................................................... 369
refining projects offline...................................... 337
using CCOTF with S908 architectures ............... 369
certificate validity
About dialog box ................................................78
changes
actions changing the build status (control).......... 470
deploying changes in hardware mappings.......... 514
deploying changes to engines (control).............. 509
managing hardware mappings after deploying ... 448
saving changes in Manage Network Variables dialog
box................................................................ 359
changes log
accessing ........................................................ 670
composite templates ........................................ 665
facet templates ................................................ 663
interfaces ........................................................ 659
saving changes in Global Templates.................. 675
CHM help
HTML help for user-created templates .................71
using the HTML help for several versions of
templates.........................................................69
circular links
generating ....................................................... 301
citect.ini files
deploying ........................................................ 520
deploying from station node .............................. 523
deploying to station nodes from executable........ 521
clients
connection to the server .....................................47
creating (supervision) ....................................... 232
engineering client UI description..........................76
logging in and out...............................................44
notification panel................................................54
quitting ..............................................................50
restarting after closing unexpectedly....................50
supervision client properties.............................. 232
working with several clients.................................52
closing
closing the software ...........................................50
clusters
properties ........................................................ 230
collapsing
nodes in the Application Browser pane .............. 123
nodes in the instance pane ............................... 137
color coding
importing application objects ............................. 195
color indicators
instance color icons.......................................... 144
project color icons ............................................ 251
communicating with devices through Ethernet explicit
messaging ..................................................... 604
EIO0000001114.15
with devices through EtherNet/IP explicit
messaging ..................................................... 608
with devices through Modbus explicit
messaging ..................................................... 611
communication
changing STB islands properties ....................... 386
communicating with the computer for deployment
(control)......................................................... 487
EtherNet/IP explicit messaging ......................... 608
implementing I/O scanning ............................... 597
implementing I/O scanning with devices............. 598
implementing I/O scanning with PRMs............... 601
implementing I/O scanning with STB islands ...... 600
implementing peer to peer communication ......... 603
managing ........................................................ 597
mapping (control) ............................................. 424
Modbus explicit messaging ............................... 611
Modbus TCP explicit messaging ....................... 604
task workflow.....................................................98
Variable Mapping Editor window........................ 436
communication boards
communication channels
actions ............................................................ 427
adjusting properties.......................................... 432
creating ........................................................... 431
moving ............................................................ 434
properties ........................................................ 428
properties server side ....................................... 430
unmapping ...................................................... 433
communication mapping
Communication Mapping Editor ........................ 425
prerequisites (control)....................................... 424
communication module
removing from the configuration ........................ 375
communication networks
connecting a station node to the Ethernet .......... 403
connecting an STB island to the Ethernet........... 404
creating ........................................................... 398
disconnecting a station node from the Ethernet .. 403
disconnecting an STB island from the Ethernet... 405
communication ports
creating (supervision) ....................................... 234
components
creating supervision project components ........... 229
Composite Editor
changes log ..................................................... 670
menus and toolbars.......................................... 666
presentation .................................................... 663
using the radar view ......................................... 672
using the simplified view ................................... 673
composite templates
changes log ..............................................665, 670
description.........................................................21
modification strategy ........................................ 688
configuration
changing STB islands properties ....................... 386
changing the controller configuration ................. 375
changing the PRM configuration........................ 390
configuring M580 safety controllers ................... 587
deploying hardware changes ............................ 513
updating configuration after deploying changes
online ............................................................ 549
updating controller configurations...................... 567
updating hardware changes.............................. 570
viewing instance configuration .......................... 155
configuration change on the fly ............................. 369
configuration file
OFS/OPCUA configuration file description ......... 476
configuration stage
completing....................................................... 364
concept .............................................................37
configuring
configuring HART modules ............................... 395
instance parameters......................................... 139
connection
client-server connection......................................47
physical connection import rules........................ 413
redundant configuration connection scenarios.... 563
consistency checks
after import ...................................................... 212
before updating control projects ........................ 573
code lock feature.............................................. 341
rules ............................................................... 348
consistency management
generating inconsistent facets........................... 325
refining control projects .................................... 347
consumer
about network variables.................................... 350
consumer project
description....................................................... 350
Container Naming Rules
window description........................................... 268
containers
creating and managing ..................................... 256
Containers pane
displaying sections in tree view ......................... 260
content
resolving contents conflicts on import ................ 684
content repository
actions ............................................................ 706
content description ........................................... 704
deleting temporary files .................................... 706
explorer........................................................... 703
opening .............................................................77
root folder actions ............................................ 705
User Contents folder ........................................ 703
Content Repository explorer
opening ........................................................... 703
Control Expert projects
importing a Control Expert project ..................... 223
control modules
description.........................................................21
template modification strategy........................... 688
Control Project Browser
description....................................................... 201
control project sections
actions ............................................................ 262
control projects
actions ............................................................ 203
build stage....................................................... 464
changing built Participant projects ..................... 470
EIO0000001114.15
727
communication mapping import rules................. 215
consistency management ................................. 347
creating ........................................................... 203
creating FBD and non-FBD sections.................. 206
creating FBD sections ...................................... 261
creating M580 safety control projects................. 579
creating the built Participant project ................... 464
data backup file import rules ............................. 219
deleting ........................................................... 205
deploying ........................................................ 481
deploying changes to engines ........................... 509
description of tree view mode............................ 287
executable import rules .................................... 215
executing ........................................................ 531
export settings ................................................. 209
exporting ......................................................... 207
facet import rules ............................................. 214
generating after changes .................................. 323
generation specifics ......................................... 300
hardware mapping import rules ......................... 215
import settings ................................................. 212
importing ......................................................... 211
importing a Control Expert project ..................... 223
managing ........................................................ 206
managing passwords of control projects ............ 488
mapping stage ................................................. 420
peer to peer communication export settings ....... 210
peer to peer communication variable import
rules.............................................................. 218
prerequisites.................................................... 203
Project Explorer ............................................... 203
Project Explorer and Browser............................ 199
project import window....................................... 219
properties ........................................................ 204
refining............................................................ 336
refining locked code ......................................... 341
regenerating .................................................... 327
related project data import rules ........................ 213
section import rules .......................................... 214
selecting type version changes ......................... 305
service mapping import rules ............................ 215
starting the simulator with your control project .... 485
starting the simulator without password
protection ...................................................... 486
task quick reference ......................................... 101
task workflow.....................................................98
tree view mode when refining............................ 339
tree view mode when refining online .................. 550
updating projects after deploying changes
online ............................................................ 549
Control service
creating in station node..................................... 379
ControlExecutables
actions ............................................................ 421
assigning execution domains ............................ 422
creating ........................................................... 421
properties ........................................................ 422
ControlExpert services
actions for station nodes ................................... 383
properties for station nodes............................... 384
controller passwords
resetting a forgotten controller password............ 493
controller stop
when deploying changes .................................. 519
controllers
about network variables.................................... 350
actions ............................................................ 372
assigning IP addresses .................................... 375
backing up controller data ................................. 554
728 changing the application password of control
projects ......................................................... 492
changing the configuration................................ 375
clearing the application password of control
projects ......................................................... 493
communicating with the computer ..................... 487
configuring ...................................................... 375
configuring the I/O scanner ............................... 376
connecting to Ethernet networks ....................... 401
creating ........................................................... 371
creating the system topology............................. 364
deleting ........................................................... 378
deploying built projects ..................................... 496
deploying changes (control) .............................. 509
deploying data ................................................. 505
deploying to redundant controllers..................... 494
disabling the I/O scanner .................................. 375
disconnecting from Ethernet networks ............... 402
execution with redundant controllers.................. 534
exporting ......................................................... 408
import rules ..................................................... 413
importing ......................................................... 411
managing data backup files .............................. 224
managing network variables ............................. 357
mapping (control) ............................................. 423
redeploying built control projects ....................... 501
representation ................................................. 377
selecting templates .......................................... 368
setting the application password of control
projects ......................................................... 491
starting and stopping ........................................ 536
supported platforms ...........................................61
copying
data elements from software Participants.............92
Global Templates and folders............................ 677
counting
counting instances ........................................... 133
CRA modules
connection with device I/Os .............................. 597
creating
Global Template editors .................................... 653
creating M580 safety control projects .................... 579
CSV
application export file description....................... 171
editing the application export file ....................... 174
exporting and importing application objects to XML
or CSV .......................................................... 168
importing CSV files into the application .............. 191
csv export files
using the invariant culture ................................. 176
ctz files
changing (supervision) ..................................... 479
creating (supervision) ....................................... 475
deploying ........................................................ 520
deploying changes to station nodes................... 528
deploying from station node .............................. 523
deploying to station nodes from executable........ 521
redeploying to engines from executable ............. 523
redeploying to engines from station node ........... 527
D data
backing up controller data................................. 554
deploying controller data to engines .................. 505
EIO0000001114.15
instance validity status...................................... 138
managing data backup files (control) ................. 224
sorting data .......................................................93
using filters ........................................................93
data backup
with redundant controllers................................. 554
data backup files
import rules for data backup files (control) .......... 219
managing data backup files (control) ................. 224
data deployment
to redundant controllers .................................... 505
data types
conversion to Participant types............................63
data types used by the software ..........................63
validating instance parameters.......................... 140
DDDT
building changes in control projects ................... 471
building control projects .................................... 466
creating during build ......................................... 465
deploying changes to control projects ................ 515
for peer to peer communication ......................... 466
managing device DDT variables........................ 343
naming convention........................................... 465
naming convention for P2P communication........ 466
DDT
device DDTs in the configuration ....................... 371
delete command
aborting folder delete........................................ 125
aborting instance delete ................................... 132
deleting
control projects ................................................ 205
controllers ....................................................... 378
deleting FBD sections during update Control
project ........................................................... 573
PRMs.............................................................. 391
sections .......................................................... 262
STB islands ..................................................... 387
unmapping hardware mappings ........................ 448
Deploy Built Project command
aborting (supervision station node) .................... 526
aborting (supervision)....................................... 522
Deploy Changes command
aborting (supervision)....................................... 528
deployed control projects
editing online ................................................... 548
deploying
controller data to engines.................................. 505
deploying changes to engines (control) .............. 509
deploying to M580 safety controllers.................. 593
from station node (supervision) ......................... 523
main redundant configuration scenarios............. 561
preparing for deployment .................................. 520
to engines (control) .......................................... 496
to redundant controllers .............................494, 497
to station nodes from executable (supervision) ... 521
deploying changes
changes requiring to stop the controller.............. 519
deploying device DDT variable changes ............ 515
hardware mappings.......................................... 514
main redundant configuration scenarios............. 561
to redundant controllers (control) ....................... 495
to station nodes (supervision) ........................... 528
deploying control projects
supported engines ........................................... 482
deployment
communicating with the computer (control) ........ 487
process flowchart ............................................. 482
deployment stage
completing....................................................... 481
concept .............................................................41
control projects ................................................ 481
supervision project ........................................... 520
device DDT
building changes in control projects ................... 471
building control projects .................................... 466
creating during build ......................................... 465
deploying changes to control projects ................ 515
device DDTs in the configuration ....................... 371
for peer to peer communication ......................... 466
naming convention ........................................... 465
naming convention for P2P communication........ 466
device DDT variables
managing device DDT variables........................ 343
Device Editor
hardware module properties ............................. 378
DeviceConfig.xml file
creating ........................................................... 475
deploying ........................................................ 520
saving ............................................................. 457
devices
assigning IP addresses to topological I/O device
entities .......................................................... 393
changing IP addresses in explicit messaging..... 608,
communicating through Ethernet explicit
messaging ..................................................... 604
communicating through EtherNet/IP explicit
messaging ..................................................... 608
communication through Modbus explicit
messaging ..................................................... 611
connecting to Ethernet networks ....................... 403
connectivity with supervision ............................. 639
disconnecting from Ethernet networks ............... 404
integrating PROFIBUS devices ......................... 642
managing Modbus TCP communication (I/O
scanning)....................................................... 598
mapping I/Os (control) ...................................... 442
selecting topological templates ......................... 368
diagnostic messages
during generation ............................................. 331
DIO scanner
implementing communication by I/O scanning .... 597
disk variable tags
I/O device properties ........................................ 234
docking menus
creating additional work areas.............................83
downloading
controller data to engines.................................. 505
deploying changes to engines (control).............. 509
deploying to engines (control) ........................... 496
main redundant configuration scenarios............. 561
redeploying to engines (control) ........................ 501
to redundant controllers .................................... 494
dragging
moving the workspace around.............................81
drivers
creating communication boards and ports .......... 234
DTM
naming convention ........................................... 465
naming convention for P2P communication........ 466
EIO0000001114.15
729
duplicating
Global Templates ............................................. 698
E editing
deployed control projects online ........................ 548
editing composite templates
changes log ..................................................... 665
editing facet templates
changes log ..................................................... 663
editing instance properties
editing instances
changing element selection after assignment ..... 283
editing interfaces
changes log ..................................................... 659
editing online (control)
changes requiring to stop the controller.............. 519
overview.......................................................... 544
editors
Assignment Editor............................................ 257
Composite Editor ............................................. 663
Facet Editor ..................................................... 659
Interface Editor ................................................ 654
Links Editor ..................................................... 712
opening Global Template editors ....................... 653
elements
definition ...........................................................21
replacing templates of elements ........................ 693
updating templates of elements......................... 689
End User License Agreement
viewing the End User License Agreement ............78
engineering client
engineering client work areas..............................79
engineering clients
engineering client UI description..........................76
engines
backing up controller data ................................. 554
deploying built control projects .......................... 496
deploying data (control) .................................... 505
deploying to redundant controllers..................... 494
execution with redundant controllers.................. 534
managing data backup files (control) ................. 224
mapping (control) ............................................. 423
redeploying built control projects ....................... 501
refreshing engine status and connecting ............ 487
supported engines for deployment (control)........ 482
entities
creating and configuring topological entities ....... 364
entity identifiers
naming rules......................................................65
entity nodes
description....................................................... 366
enumerations
exporting parameter values to CSV ................... 176
exporting parameter values to XML ................... 185
viewing values in the Instance Editor ................. 135
equipment
equipment hierarchy......................................... 116
generating equipment (supervision)................... 329
equipment generation
troubleshooting ................................................ 331
equipment hierarchy
import rules for equipment (supervision) ............ 245
errors
detected errors during generation...................... 301
730
Ethernet
conflicting Ethernet connections........................ 400
connecting controllers to Ethernet networks ....... 401
connecting entities to an Ethernet network ......... 399
disconnecting controllers from Ethernet
networks........................................................ 402
managing EtherNet/IP explicit messaging .......... 608
managing Modbus TCP explicit messaging ........ 604
viewing Ethernet connections............................ 400
Ethernet IP devices
import rules ..................................................... 413
Ethernet networks
actions ............................................................ 398
connecting devices .......................................... 403
connecting PRMs............................................. 405
connecting station nodes .................................. 403
connecting STB islands .................................... 404
creating ........................................................... 398
disconnecting devices ...................................... 404
disconnecting PRMs ........................................ 406
disconnecting station nodes.............................. 403
disconnecting STB islands................................ 405
exporting ......................................................... 408
importing ......................................................... 411
properties ........................................................ 398
selecting templates .......................................... 368
Ethernet RIO drops
connecting to Ethernet networks ....................... 401
disconnecting from Ethernet networks ............... 402
EtherNet/IP devices
changing properties.......................................... 395
creating and configuring devices ....................... 391
EtherNet/IP explicit messaging
EULA
viewing the End User License Agreement ............78
Exclude command
description....................................................... 660
executable files
changing (control) ............................................ 470
creating (control).............................................. 464
creating (supervision) ....................................... 475
deploying (supervision)..................................... 520
modifying (supervision)..................................... 479
executables
actions (control) ............................................... 421
actions (supervision) ........................................ 457
assigning execution domains (control) ............... 422
assigning execution domains (supervision) ........ 459
backing up controller data................................. 554
creating (control).............................................. 421
creating (supervision) ....................................... 457
deploying changes to engines (control).............. 509
deploying changes to station nodes
(supervision) .................................................. 528
deploying controller data to engines (control) ..... 505
deploying from station node (supervision) .......... 523
deploying to engines (control) ........................... 496
deploying to redundant controllers..................... 494
deploying to station nodes (supervision) ............ 521
executable import rules (control) ....................... 215
executable import rules (supervision)................. 247
executing with redundant controllers.................. 534
managing data backup files (control) ................. 224
properties (control) ........................................... 422
properties (supervision) .................................... 458
redeploying to engines (control) ........................ 501
redeploying to engines (supervision) ..........523, 527
EIO0000001114.15
executables (supervision) status change when importing new content
version .......................................................... 684
executing
deployed participant projects (control) ............... 536
to redundant controllers .................................... 534
execution
facet execution order........................................ 295
FBD section execution order ............................. 207
process flowchart ............................................. 532
synchronizing redundant controllers .................. 541
execution domains
assigning to executables (control) ..................... 422
assigning to executables (supervision) .............. 459
execution order
after first generation ......................................... 303
when regenerating ........................................... 328
execution stage
completing....................................................... 531
concept .............................................................42
control projects ................................................ 531
supervision projects ......................................... 576
expanding
nodes in the Application Browser pane .............. 123
nodes in the instance pane ............................... 137
explorers
Application Explorer ......................................... 117
Content Repository explorer ............................. 703
creating work areas in explorers ..........................84
Global Templates Explorer................................ 645
opening .............................................................77
opening the Project Explorer ............................. 200
overview............................................................28
Systems Explorer............................................. 105
task workflow.....................................................98
Topology Explorer ............................................ 365
export command
aborting........................................................... 170
aborting (control).............................................. 210
aborting (supervision)....................................... 241
aborting (topology) ........................................... 410
aborting template export ................................... 678
export files
editing the CSV application export file ................ 174
editing the XML application export file................ 185
editing XML to manage application links ............ 189
using the invariant culture ................................. 176
export settings
control projects ................................................ 209
peer to peer communication export settings ....... 210
supervision projects ......................................... 241
exporting
CSV application export file description ............... 171
editing exported hardware mappings ................. 452
exporting application objects to XML or CSV ...... 168
exporting control projects.................................. 207
exporting hardware mappings ........................... 449
password related information for topological
entities .......................................................... 409
peer to peer communication data ...................... 207
supervision projects ......................................... 238
templates ........................................................ 677
topological entities ........................................... 408
XML application export file description ............... 184
exporting asset workspaces ................................. 168
exporting control projects
software version compatibility ........................... 208
exporting M580 safety controllers ......................... 590
exporting safety control projects ........................... 581
EIO0000001114.15
exporting supervision projects
software version compatibility ........................... 239
expressions
Container Naming Rules window....................... 268
importing expressions for control sections.......... 212
extracted Participant windows
troubleshooting ..................................................92
extracting
software Participant windows ..............................90
F
Facet Editor
changes log ..................................................... 670
description....................................................... 659
menus and toolbars.......................................... 666
using the radar view ......................................... 672
using the simplified view ................................... 673
facet templates
changes log ..............................................663, 670
description.........................................................21
modification strategy ........................................ 688
facets
actions after assigning...................................... 292
actions after generation .................................... 332
assigned facet description ................................ 282
assigning......................................................... 268
assigning (control)............................................ 279
assigning (supervision)..................................... 281
automatic assignment of remaining facets.......... 284
automatic assignment of Supervision facets....... 285
changing order inside section............................ 295
element selection changes of assigned facets .... 283
generating automatically assigned facets........... 299
import rules for control project facets ................. 214
managing assigned facets ................................ 292
moving ............................................................ 293
moving generated facets .................................. 335
navigating to the instance ................................. 296
unassign ......................................................... 293
viewing assignments per instance ..................... 294
FBD
using FBD language with Process Expert.............61
FBD sections
actions ............................................................ 262
changing execution order ................................. 207
creating during generation ................................ 302
creating FBD sections ...................................... 261
deleting ........................................................... 262
import rules for FBD sections ............................ 214
when regenerating ........................................... 328
files
adding external files to supervision projects ....... 363
filters
filtering data.......................................................93
Templates Browser .......................................... 119
to display instance parameters.......................... 138
floating Participant windows
troubleshooting ..................................................92
folder structure
changing application folder hierarchy................. 126
731
changing the position of folders ......................... 161
folders
changing the application hierarchy .................... 156
copying and pasting application folders.............. 157
copying and pasting library folders .................... 677
creating Global Template folders ....................... 650
exporting and importing to XML or CSV ............. 168
moving application folders ................................ 158
moving folders ................................................. 126
moving topological folders ................................ 407
naming rules......................................................65
resolving application import conflicts.................. 197
S88 representation........................................... 129
searching application instances and folders ....... 118
function blocks
layout after first generation................................ 303
layout when generating after changes ............... 326
layout when regenerating ................................. 328
G gateways
using for Modbus explicit messaging ................. 611
Generate and Build command
aborting........................................................... 299
Building control projects the first time................. 467
Building supervision projects the first time .......... 477
description....................................................... 299
Generate command
aborting generation of project containers ........... 322
aborting generation of projects .......................... 321
generated code
identifying software-generated code .................. 341
generated facets
unlinking.......................................................... 334
generating
analyzing control projects ................................. 300
automatically assigned facets ........................... 299
configuring settings (control) ............................. 304
control project specifics .................................... 300
detecting errors during generation ..................... 301
diagnostic messages........................................ 331
entire projects .................................................. 321
equipment (supervision) ................................... 329
facet order ....................................................... 295
FBD section size .............................................. 302
first-time generation ......................................... 321
function block layout during first generation........ 303
function description .......................................... 324
general description........................................... 297
Generate and Build command........................... 299
generating invalid facets again .......................... 326
generating safety control projects ...................... 585
importing sections after generation .................... 323
invalid facets.................................................... 299
part of a project ................................................ 322
projects after changes ...................................... 323
rules for generating graphical links .................... 301
satisfying naming rules ..................................... 298
section order.................................................... 207
statuses of facets ............................................. 319
generation canceling generation for version conflict
(control)......................................................... 301
changing type versions during generation
(control)......................................................... 305
function block layout after changes.................... 326
managing generated facets .............................. 332
skipping facets during generation ...................... 300
732 generation name issues
troubleshooting ................................................ 331
generation stage
completing....................................................... 297
concept .............................................................35
generating inconsistent facets........................... 325
GenerationSettings
configuring generation XML file (control) ............ 304
generic devices communicating through Ethernet explicit
messaging ..................................................... 604
communicating through EtherNet/IP explicit
messaging ..................................................... 608
communication through Modbus explicit
messaging ..................................................... 611
connectivity with supervision ............................. 639
managing Modbus TCP communication (I/O
scanning)....................................................... 598
mapping interfaces........................................... 443
genies
editing supervision pages ................................. 361
Global Template editors
opening ........................................................... 653
Global Templates
actions ............................................................ 651
classification......................................................21
copying and pasting ......................................... 677
description................................................. 20, 651
duplicating....................................................... 698
Global Templates Explorer................................ 645
managing ........................................................ 675
naming convention ........................................... 646
purging the Global Templates library.................. 686
renaming ......................................................... 675
replacing templates of elements ........................ 693
saving changes................................................ 675
updating .......................................................... 689
Global Templates definition
concept .............................................................28
Global Templates Explorer
folder actions ................................................... 650
opening ..................................................... 77, 645
presentation .................................................... 646
Toolbox ........................................................... 648
Global Templates library
viewing in the Global Templates Explorer ........... 645
Go To Instance command
navigating to the instance ................................. 296
graphical links
generation rule................................................. 301
H
HAL DFBs
managing ........................................................ 472
HAL variables
managing ........................................................ 472
HAL variables and DFBs
properties ........................................................ 473
viewing............................................................ 474
hardware
deploying hardware changes ............................ 513
mapping .......................................................... 442
supported components ..................................... 364
updating hardware changes.............................. 570
EIO0000001114.15
I hardware abstraction layer variables
managing ........................................................ 472
hardware mapping
managing HAL variables................................... 472
Hardware Mapping Editor
presentation .................................................... 444
hardware mappings
editing exported hardware mappings ................. 452
exporting hardware mappings ........................... 449
importing hardware mappings ........................... 455
HART
HART communication ...................................... 395
HART modules
configuring HART modules ............................... 395
representation ................................................. 397
help
help button ........................................................77
HTML help for user-created templates .................71
opening the help of software Participants .............69
using the HTML help for several versions of
templates.........................................................69
hierarchical naming ............................................. 141
hot standby
managing data backup files .............................. 224
hot standby controllers
backing up controller data ................................. 554
connecting to Ethernet networks ....................... 400
deploying built control projects .......................... 496
deploying changes to redundant controllers ....... 511
deploying controller data................................... 505
deploying to redundant controllers..............494, 497
disconnecting from Ethernet networks ............... 402
execution ........................................................ 534
identifying........................................................ 371
main deployment and execution scenarios ......... 561
physical connection import rules........................ 413
redeploying to redundant controllers.................. 501
reservation and connection scenarios................ 563
HTML help
HTML help for user-created templates .................71
using the HTML help for several versions of
templates.........................................................69
icons identifiers identifying engines
IL
assigning icons to folders.................................. 129
changing the identifier of Global Templates ........ 675
naming rules......................................................65
using physical addresses.................................. 483
using IL language...............................................61
import
accessing the import window ............................ 414
import command
aborting (control).............................................. 222
aborting (supervision)....................................... 250
aborting (topology) ........................................... 417
aborting application import command ................ 194
aborting template import ................................... 685
import rules
executable import rules (control) ....................... 215
executable import rules (supervision)................. 247
for control project facets ................................... 214
for control project-related objects ...................... 213
EIO0000001114.15
for data backup files (control) ............................ 219
for equipment (supervision) .............................. 245
for included projects ......................................... 244
for mapped peer to peer communication
variables........................................................ 218
for pages of supervision projects ....................... 245
for program sections (control) ........................... 214
for supervision project facets............................. 246
for supervision project-related objects................ 244
mapping import rules (control)........................... 215
mapping import rules (supervision) .................... 247
physical connection import rules........................ 413
import settings
control projects ................................................ 212
supervision projects ......................................... 242
importing
application import settings ................................ 195
checking consistency after importing control
projects ......................................................... 212
color coding when importing application
objects .......................................................... 195
Control Expert projects ..................................... 223
control projects ................................................ 211
expressions for control project sections ............. 212
importing application objects to XML or CSV ...... 168
importing hardware mappings ........................... 455
importing XML or CSV files into the application... 191
password related information for topological
entities .......................................................... 414
resolving contents conflicts for templates ........... 684
sections during online refinement ...................... 558
supervision projects ......................................... 242
templates ........................................................ 680
topological entities ........................................... 411
importing control projects
software version compatibility ........................... 212
importing instances
resolving conflicts ............................................ 197
importing M580 safety controllers ......................... 590
importing safety control projects ........................... 581
importing supervision projects
software version compatibility ........................... 242
included projects
adding or removing .......................................... 362
downloading .................................................... 478
importing ......................................................... 244
importing with templates ................................... 680
saving (supervision) ......................................... 457
inconsistent facets
generating ....................................................... 325
layout of blocks after generation ........................ 326
infrastructure
instance count
About dialog box ................................................78
Instance Editor
accessing ........................................................ 134
presentation .................................................... 135
instance link status .............................................. 150
instance path
viewing instance location information................. 155
instance properties
naming rules......................................................65
instances
accessing the Instance Editor ........................... 134
actions ............................................................ 132
733
changing the application hierarchy .................... 156
color indicators ................................................ 144
configuration parameters .................................. 141
configuring parameters..................................... 139
copying and pasting ......................................... 157
counting for licensing........................................ 133
creating ........................................................... 130
data status ...................................................... 138
element selection changes of assigned facets .... 283
exceeding count of a license ............................. 133
exporting and importing to XML or CSV ............. 168
hierarchical naming .......................................... 141
import rules for control project-related objects .... 213
import rules for supervision project-related
objects .......................................................... 244
moving ............................................................ 158
navigating from facets to the instance ................ 296
of templates.......................................................25
order when creating ......................................... 130
resolving import conflicts .................................. 197
searching ........................................................ 121
searching application instances and folders ....... 118
validating parameters ....................................... 140
viewing facet assignments ................................ 294
instantiating
templates ........................................................ 115
instantiation
order when creating instances........................... 130
structure of the application ................................ 116
instantiation stage
completing....................................................... 115
concept .............................................................29
interface links
editing the XML export file................................. 189
exporting and importing to XML or CSV ............. 168
interface models
types.................................................................24
interfaces
changes log ..................................................... 659
generic device mapping interfaces .................... 443
mapping hardware interfaces ............................ 442
modification strategy ........................................ 688
invalid
instance data validity status .............................. 138
invalid facets
generating ....................................................... 299
generating invalid facets again .......................... 326
invalid link status ................................................. 150
invariant culture
editing the application export file ....................... 176
editing the XML application export file................ 186
I/O device addresses
Build stage ...................................................... 475
I/O devices
communication mapping import rules................. 215
creating I/O devices ......................................... 232
I/O devices for calculated variable tags .............. 234
I/O devices for disk variable tags ....................... 234
properties (supervision) .................................... 233
I/O scanner
configuring for controllers ................................. 376
disabling.......................................................... 375
I/O scanner lines
memory allocation............................................ 467
I/O scanning
connecting devices to Ethernet networks ........... 403
connecting PRMs to Ethernet networks ............. 405
creating and configuring Modbus TCP device..... 391
disconnecting devices from Ethernet networks ... 404
disconnecting PRMs from Ethernet networks ..... 406
implementing communication............................ 597
managing communication with devices .............. 598
managing communication with PRMs ................ 601
managing communication with STB islands........ 600
managing peer to peer communication .............. 603
I/O server redundancy
implementing ................................................... 237
Interface Editor
pane description .............................................. 655
presentation .................................................... 654
IO servers
IP address
assigning to controllers..................................... 375
assigning to PRMs ........................................... 390
assigning to station nodes ................................ 383
assigning to STB islands .................................. 385
changing EtherNet/IP device properties ............. 395
changing for explicit messaging with devices..... 608,
changing Modbus TCP device properties ........... 395
changing STB islands properties ....................... 386
deploying changes to redundant controllers ....... 511
online changes with redundant controllers.......... 550
physical connections to Ethernet networks ......... 399
refreshing engine status and connecting ............ 487
italic formatting
editing instance properties ................................ 140
K keyboard
selecting VM default layout ............................... 707
keyboard shortcuts
using.................................................................96
L languages
VM default keyboard layout............................... 707
VM system locale............................................. 709
layout of function blocks
after first generation ......................................... 303
when generating after changes ......................... 326
LD
when regenerating ........................................... 328
using LD language .............................................61
libraries
viewing in the Global Templates Explorer ........... 645
licensing
link validity status ................................................ 150
Linked Production Assets section
creating links to view instances ......................... 154
linking instances...........................................146, 152
using the Asset Workspace Editor ..................... 146
links creating links to view instance information in
RTNS ............................................................ 154
editing the XML export file................................. 189
exporting and importing to XML or CSV ............. 168
734 EIO0000001114.15
modifying links between instances..................... 152
rules for generating graphical links .................... 301
Links Editor
Asset Workspace Editor ................................... 146
Links Editor ..................................................... 712
presentation .................................................... 713
LL984
updating logical control projects ........................ 570
using LL984 language ........................................61
local computers
pasting data to Participants.................................92
location
viewing instance location information................. 155
locked code
code lock feature.............................................. 341
locked facets
skipping facets during generation ...................... 300
locking
Lock command (engineering client) .....................77
locking mechanisms
multiuser functionalities ......................................52
log files
activity log files ..................................................59
logging in
to server and clients ...........................................44
logging out
of server and clients ...........................................44
logical control projects
updating with online changes ............................ 567
loops
generating circular links .................................... 301
M
M340
creating a control project .................................. 203
creating controllers........................................... 371
creating PRM PROFIBUS DPs.......................... 388
M580
creating a control project .................................. 203
creating controllers........................................... 371
M580 safety systems
implementing ................................................... 577
maintenance mode.............................................. 594
Manage Network Variables saving changes in Manage Network Variables dialog
box................................................................ 359
managers
platform tools.....................................................28
managing
control projects ................................................ 206
supervision projects ......................................... 238
managing network variables
M580 safety controllers .................................... 579
mapping
changing service mappings (control) ................. 423
clients (supervision) ......................................... 459
communication (control) ................................... 424
communication (supervision) ............................ 460
deleting mapping when updating topological
templates....................................................... 407
editing exported hardware mappings ................. 452
exporting hardware mappings ........................... 449
hardware......................................................... 442
importing hardware mappings ........................... 455
I/O devices (supervision) .................................. 460
mapping import rules (control)........................... 215
mapping import rules (supervision) .................... 247
mappings for safety control projects .................. 592
EIO0000001114.15
network variable mapping rules ......................... 439
network variables ......................................435, 451
selecting variable mapping positions ................. 438
servers (supervision) ........................................ 459
services (control) ............................................. 423
services (supervision)....................................... 459
to engines (control) .......................................... 423
topological mapping indicator............................ 366
Variable Mapping Editor window (control)........... 436
mapping stage
completing....................................................... 420
concept .............................................................39
control projects ................................................ 420
exporting and importing hardware mappings ...... 449
supervision projects ......................................... 457
memory allocation
when creating I/O scanner lines ........................ 467
menus
common template editor menus ........................ 666
using menus ......................................................89
migrating databases
code lock feature.............................................. 341
Modbus explicit messaging
Modbus serial
managing communication................................. 611
Modbus serial devices
communication mapping................................... 461
connectivity with supervision ............................. 639
Modbus TCP devices
changing properties.......................................... 395
communication mapping................................... 461
connectivity with supervision ............................. 639
creating and configuring devices ....................... 391
exporting ......................................................... 408
import rules ..................................................... 413
importing ......................................................... 411
Modbus TCP explicit messaging
Modbus TCP implicit messaging
implementing communication............................ 597
implementing communication with devices......... 598
implementing communication with PRMs ........... 601
implementing communication with STB islands .. 600
implementing peer to peer communication ......... 603
modules
hardware module properties ............................. 378
monitoring
Modbus device data from supervision ................ 639
monitors
floating Participant windows................................90
using dual monitors ............................................83
moving
application folders ............................................ 158
changing the position of folders and maintain
hierarchy ....................................................... 161
facets.............................................................. 293
generated facets .............................................. 335
instances......................................................... 158
moving folders ................................................. 126
moving sections (control) .................................. 207
topological folders ............................................ 407
multiple selection
selecting multiple items ......................................82
multiuser
working with several clients.................................52
735
N naming convention
Global Templates naming convention ................ 646
naming instances
hierarchical naming .......................................... 141
naming rules
rules for identifiers and variable names ................65
rules for Supervision data ...................................65
navigating
inside the Application Browser pane .................. 123
inside the instance pane ................................... 137
navigating from facets to the instance ................ 296
navigation services
using after restoring systems ............................ 112
network addresses generating network addresses for supervision
components ................................................... 476
network interface cards
properties ........................................................ 383
network redundancy
implementing (supervision) ............................... 238
network variables
address allocation during build .......................... 468
creating ........................................................... 359
description....................................................... 350
mapping ...................................................435, 451
mapping rules .................................................. 439
modifying ........................................................ 360
properties ........................................................ 357
selecting variable mapping positions ................. 438
Variable Mapping Editor window........................ 436
networks
conflicting Ethernet connections ........................ 400
connecting a station node to the Ethernet .......... 403
connecting an STB island to the Ethernet........... 404
connecting controllers to Ethernet networks ....... 401
connecting devices to Ethernet networks ........... 403
connecting entities to an Ethernet network ......... 399
connecting PRMs to Ethernet networks ............. 405
creating an Ethernet network ............................ 398
disconnecting a station node from the Ethernet .. 403
disconnecting an STB island from the Ethernet... 405
disconnecting controllers from Ethernet
networks........................................................ 402
disconnecting devices from Ethernet networks ... 404
disconnecting PRMs from Ethernet networks ..... 406
viewing Ethernet connections............................ 400
NIC
actions ............................................................ 382
assigning IP addresses .................................... 383
creating ........................................................... 382
properties ........................................................ 383
NOC
configuring memory for I/O scanning ................. 376
NOC communication modules
configuring HART modules ............................... 395
non-FBD sections
notification when regenerating .......................... 328
Not Built
actions changing the build status (control).......... 470
notification panel
abort task icon ...................................................54
description.........................................................54
736
displaying ..........................................................77
performance considerations................................56
O object models
application templates .........................................23
interface models ................................................24
topological templates .........................................24
object templates
classification......................................................21
description.........................................................20
elements ...........................................................21
references .........................................................21
types.................................................................23
objects
object model overview ........................................19
OFS
configuration file description.............................. 476
OFS configuration file
creating ........................................................... 475
deploying ........................................................ 520
saving ............................................................. 457
OFS services
actions for station nodes ................................... 383
creating in station node..................................... 379
properties for station nodes............................... 384
OFSOPC
tag container properties .................................... 264
OFSOPC driver
communication board properties ....................... 235
OFSOPC/OPCUA configuration files
downloading .................................................... 478
online changes
changing the deployed control project................ 548
main redundant configuration scenarios............. 561
overview.......................................................... 544
refining safety control projects online ................. 594
selecting IP addresses ..................................... 550
updating logical control projects ........................ 567
updating projects after deploying changes
online ............................................................ 549
online help
HTML help for user-created templates .................71
using the help for several versions of templates....69
Online modification in RUN or STOP..................... 369
online refinement
importing sections ............................................ 558
online refinement indicator................................ 366
OPC Factory Server
OFS configuration file description ...................... 476
OPC UA Server Expert
configuration file description.............................. 476
OPCUA
configuration file description.............................. 476
OPCUA driver
OPCUA embedded
mapping communication................................... 461
operation clients using navigations services after restoring
systems ......................................................... 112
operation servers
creating in the topology..................................... 379
operator stations
creating in the topology..................................... 379
EIO0000001114.15
order
changing facet order inside section.................... 295
changing FBD section order.............................. 207
order of sections notification when regenerating non-FBD
sections......................................................... 328
Out Of Date
actions changing the build status (control).......... 470
Out Of Date facets
layout of blocks after generation ........................ 326
owner
about network variables.................................... 350
owner project
description....................................................... 350
P pages
actions ............................................................ 267
assigning genie facets ...................................... 361
creating supervision pages ............................... 267
editing ............................................................. 361
properties ........................................................ 267
supervision page import rules ........................... 245
panes
common template editor panes ......................... 670
working with panes.............................................85
panning
moving the workspace around.............................81
parameter pane
in template editors............................................ 670
parameters
accessing instance properties ........................... 134
conditional font formats .................................... 140
configuring instance parameters ....................... 139
hardware module properties ............................. 378
instance configuration ...................................... 141
instance parameter filters ................................. 138
naming rules......................................................65
Participant projects
creating ........................................................... 297
deploying changes to station nodes
(supervision) .................................................. 528
deploying controller data to engines (control) ..... 505
deploying from station node (supervision) .......... 523
deploying to engines (control) ........................... 496
deploying to redundant controllers..................... 494
deploying to station nodes from executable
(supervision) .................................................. 521
executing with redundant controllers.................. 534
managing data backup files (control) ................. 224
redeploying to engines (control) ........................ 501
redeploying to engines from executable
(supervision) ...........................................523, 527
system root folder actions ................................. 202
Participant windows
troubleshooting floating window appearance ........92
Participants
floating Participant windows................................90
opening the Participant help................................69
Participant window description ............................90
pasting data to the local computer .......................92
system locale................................................... 709
VM default keyboard layout............................... 707
password protection
EIO0000001114.15
controller properties ......................................... 373
station node properties ..................................... 381
system properties ............................................ 107
passwords
actions that require providing the password........ 489
changing passwords of project loaded at simulator
startup ........................................................... 493
changing the application password of control
projects ......................................................... 492
clearing the application password of control
projects ......................................................... 493
exporting password related information for
topological entities.......................................... 409
importing password related information for
topological entities.......................................... 414
managing passwords of control projects ............ 488
password information and settings in system
backups......................................................... 109
password information and settings when restoring
systems ......................................................... 111
project loaded at simulator startup ..................... 491
resetting a forgotten controller password............ 493
resetting a forgotten safety password ................ 590
setting the application password of control
projects ......................................................... 491
verifying password to perform operations ........... 492
paste command
aborting........................................................... 158
pasting
data elements to software Participants.................92
Global Templates and folders............................ 677
peer to peer
communication mapping import rules................. 215
mapping network variables ........................435, 451
peer to peer communication export settings ....... 210
peer to peer communication variable import
rules.............................................................. 218
peer to peer communication
about network variables.................................... 350
address allocation during build .......................... 468
client communication channel properties............ 428
communication mapping (control)...................... 424
configuring the I/O scanner of controllers ........... 376
controller memory size configuration ................. 373
creating network variables ................................ 359
exporting control projects.................................. 207
implementing ................................................... 603
managing network variables ............................. 357
modifying network variables.............................. 360
network variable properties ............................... 357
owner and consumer projects ........................... 350
server communication channel properties .......... 430
templates .................................................350, 357
variable properties ........................................... 354
peer to peer communication channels
actions ............................................................ 427
adjusting properties.......................................... 432
creating ........................................................... 431
moving ............................................................ 434
performance
notification panel................................................56
OFSOPC driver configuration............................ 235
physical connections
physical connection import rules........................ 413
P&ID
instantiation stage ............................................ 115
pin button
working with panes.............................................85
platform components
737
platform tools.....................................................28
platforms
supported hardware platforms.............................61
PMEPXM0100 modules
integration workflow ......................................... 642
ports creating additional communication ports
(supervision) .................................................. 236
creating communication ports (supervision) ....... 234
positions
selecting variable mapping positions ................. 438
printing
template layouts............................................... 668
PRM
actions ............................................................ 389
connecting to Ethernet networks ....................... 405
deleting ........................................................... 391
disconnecting from Ethernet networks ............... 406
import rules ..................................................... 413
managing Modbus TCP communication (I/O
scanning)....................................................... 601
properties ........................................................ 389
representation ................................................. 390
PROFIBUS
connecting to Ethernet networks ....................... 405
disconnecting from Ethernet networks ............... 406
managing Modbus TCP communication (I/O
scanning)....................................................... 601
PROFIBUS remote master and DPs
exporting ......................................................... 408
importing ......................................................... 411
PROFIBUS slave devices
integrating in systems....................................... 642
programming languages
supported languages..........................................61
progress indicators
instance color icons.......................................... 144
project color icons ............................................ 251
Project Browser
system root folder actions ................................. 202
project definition stage
completing....................................................... 199
concept .............................................................32
control projects ................................................ 203
Project Browser ............................................... 199
Project Explorer ............................................... 199
supervision projects ......................................... 226
Project Explorer
description....................................................... 200
opening .............................................................77
project files
downloading (supervision) ................................ 478
project settings analyzing M580 safety projects and
configurations ................................................ 588
defining (supervision) ....................................... 362
setting during build (control) .............................. 467
projects
color indicators ................................................ 251
generating ....................................................... 321
generating after changes .................................. 323
types of Participant projects ................................33
properties
accessing instance properties ........................... 134
adjusting peer to peer communication channel
properties ...................................................... 432
application folders ............................................ 126
changing STB islands properties ....................... 386
configuring instance parameters ....................... 139
hardware module properties ............................. 378
I/O devices (supervision) .................................. 233
IO server properties ......................................... 231
properties of sections ....................................... 262
supervision client properties.............................. 232
supervision server properties ............................ 231
systems .......................................................... 107
Protocol
tag container attributes ..................................... 264
Purge command
aborting template purge.................................... 687
purging
Global Templates library ................................... 686
Q
Quantum
creating a control project .................................. 203
creating controllers........................................... 371
creating PRM PROFIBUS DPs.......................... 388
quick reference
system engineering life cycle task workflow..........98
system engineering life cycle tasks.................... 101
quitting
clients ...............................................................50
quitting the software ...........................................50
R radar view
description....................................................... 672
reassigning
facets.............................................................. 334
reconnect button
Recovery
Recovery folder description .............................. 650
redeploying
main redundant configuration scenarios............. 561
to engines (control) .......................................... 501
to engines from executable (supervision) ....523, 527
to redundant controllers .................................... 501
redundancy
implementing (supervision) ............................... 236
redundant alarm servers
implementing alarm server redundancy ............. 237
redundant controllers
backing up controller data................................. 554
connecting to Ethernet networks ....................... 400
deploying changes to (control) .......................... 495
deploying controller data................................... 505
identifying........................................................ 371
physical connection import rules........................ 413
synchronizing .................................................. 541
redundant I/O servers
738 EIO0000001114.15
implementing I/O server redundancy ................. 237
redundant networks implementing network redundancy
(supervision) .................................................. 238
redundant report servers
implementing report server redundancy ............. 237
redundant trend servers
implementing trend server redundancy .............. 237
references
definition ...........................................................21
missing references in Recovery folder ............... 650
refine online
main redundant configuration scenarios............. 561
overview.......................................................... 544
with redundant controllers................................. 534
refinement
consistency management (control) .................... 347
refining locked code ......................................... 341
refinement stage
completing....................................................... 336
concept .............................................................36
control projects ................................................ 336
supervision project ........................................... 360
refining
advanced supervision project settings ............... 362
control projects ................................................ 336
editing supervision pages ................................. 361
managing device DDT variables........................ 343
refining safety control projects........................... 585
refining safety control projects online ................. 594
supervision projects ......................................... 360
validity indicators ............................................. 339
refining safety control projects online .................... 594
ReGenerate command
aborting regeneration of projects and sections.... 328
regenerating
configurable settings (control) ........................... 304
control project sections..................................... 329
control projects ................................................ 327
entire control projects ....................................... 328
functionality description .................................... 327
importing sections after regeneration ................. 323
removing types ................................................ 327
regenerating non-FBD sections
notification when regenerating .......................... 328
regional options
instance parameters......................................... 140
release notes
viewing platform and library release notes............78
relinking
facets.............................................................. 334
removing
removing generated types ................................ 303
removing types when regenerating .................... 327
renaming
Global Templates ............................................. 675
Replace dialog box
description....................................................... 701
Replace Template
command description ....................................... 161
replacing
replacing templates of elements ........................ 693
template of instances ....................................... 161
templates with new type version ........................ 166
replacing templates
validating instance identifier uniqueness ............ 166
report server redundancy
EIO0000001114.15
implementing ................................................... 237
reservation
redundant configuration reservation scenarios ... 563
Resolve Uniqueness Conflicts
dialog box description....................................... 197
restarting
restarting clients that closed unexpectedly ...........50
restore
impact on system names in database ................ 112
password information and settings when restoring
systems ......................................................... 111
restore command
aborting........................................................... 111
restoring deployed Participant project from executable
(supervision) .................................................. 523
deployed Participant project from station node
(supervision) .................................................. 527
restoring systems............................................. 110
rollback
rolling back generation ..................................... 301
RTNS
creating links to view instance information.......... 154
rules
truncation rules for equipment (supervision) ....... 329
run
starting controllers and simulators (control) ........ 536
runtime navigation services
creating links to view instance information.......... 154
using after restoring systems ............................ 112
R/W Rights of Referenced Variable
network variables ............................................. 357
S
S88
assigning icons to folders.................................. 129
modeling the equipment hierarchy..................... 116
S908
building changes.............................................. 471
using CCOTF with S908 architectures ............... 369
safe area password
managing the safety password.......................... 588
safe signature
building safety control projects .......................... 592
deploying to safety controllers ........................... 593
safety controllers
configuring M580 safety controllers ................... 587
implementing M580 safety systems ................... 577
safety password
managing the safety password.......................... 588
safety passwords
resetting a forgotten safety password ................ 590
saving
backing up controller data................................. 554
changes in Manage Network Variables dialog
box................................................................ 359
Global Templates ............................................. 675
saving templates
tracking changes in the changes log .................. 675
sbk file
exporting templates.......................................... 677
searching
application instances and folders....................... 118
instances......................................................... 121
template search ............................................... 119
section layout
configurable settings (control) ........................... 304
section size
739
configurable settings (control) ........................... 304
sections
actions ............................................................ 262
changing execution order ................................. 207
creating and managing ..................................... 256
creating FBD and non-FBD sections.................. 206
creating FBD sections ...................................... 261
creating sections in safety control projects ......... 584
deleting FBD sections during update Control
project ........................................................... 573
import rules for program sections ...................... 214
importing during online refinement..................... 558
inserting FBD sections...................................... 262
moving sections (control) .................................. 207
properties ........................................................ 262
tree view description in Containers pane ............ 287
tree view when refining Control projects............. 339
tree view when refining Control projects online ... 550
security services
system properties ............................................ 107
selecting
selecting multiple items ......................................82
server
connection to clients...........................................47
starting again.....................................................46
stopping ............................................................50
servers
creating servers (supervision) ........................... 230
service mapping
changing (control) ............................................ 423
services
generating network addresses .......................... 476
session overcrowded
troubleshooting ................................................ 331
sessions
restarting clients that closed unexpectedly ...........50
settings
configuring generation settings (control) ............ 304
Settings
Settings pane
changing application folder icons....................... 129
Settings window
Systems Explorer............................................. 107
SFC
using SFC language...........................................61
shortcuts
keyboard shortcuts.............................................96
signature mismatch
actions that require providing the password........ 489
controller data backup ...................................... 557
controller data deployment................................ 508
deployment stage ............................................ 510
execution stage ............................................... 533
simplified view
Asset Workspace Editor ................................... 149
template editors ............................................... 673
simulator
backing up controller data ................................. 554
changing passwords of projects loaded at
startup ........................................................... 493
changing the default project loaded at startup..... 485
deploying built control projects .......................... 496
deploying changes (control) .............................. 509
deploying controller data (control)...................... 505
managing data backup files (control) ................. 224
mapping hardware ........................................... 443
obtaining the IP address ................................... 487
redeploying built control projects ....................... 501
setting passwords of project loaded at simulator
startup ........................................................... 491
starting............................................................ 485
starting without loading a password-protected
project ........................................................... 486
simulator ports .................................................... 485
simulator software
starting and stopping ........................................ 536
skipping
skipping facets during generation ...................... 300
software Participants
floating Participant windows................................90
pasting data to the local computer .......................92
window description.............................................90
sorting
sorting data .......................................................93
ST
using ST language .............................................61
STA
changing the default project loaded at startup..... 485
starting the simulator without password
protection ...................................................... 486
stages
assignment stage concept ..................................34
assignment stage implementation ..................... 256
build stage concept ............................................40
build stage implementation ............................... 464
concept .............................................................26
configuration stage concept ................................37
configuration stage implementation ................... 364
deployment stage concept ..................................41
deployment stage implementation ..................... 481
execution stage concept .....................................42
execution stage implementation ........................ 531
generation stage concept ...................................35
generation stage implementation....................... 297
Global Templates definition stage concept ...........28
instantiation stage concept .................................29
instantiation stage implementation .................... 115
mapping stage concept ......................................39
mapping stage implementation ......................... 420
project definition stage concept ...........................32
project definition stage implementation .............. 199
refinement stage concept ...................................36
refinement stage implementation....................... 336
task quick reference ......................................... 101
starting
controllers and simulators (control) .................... 536
emulated simulator........................................... 484
simulator ......................................................... 485
system server ....................................................46
station nodes
actions ............................................................ 379
backing up controller data................................. 554
connecting to Ethernet networks ....................... 403
creating ........................................................... 379
disconnecting from Ethernet networks ............... 403
exporting ......................................................... 408
import rules ..................................................... 413
importing ......................................................... 411
mapping to emulated simulators (control)........... 423
properties ........................................................ 381
selecting templates .......................................... 368
740 EIO0000001114.15
status
editing instance properties ................................ 140
instance data validity status .............................. 138
refreshing engine status ................................... 487
status of supervision executables status change when importing new content
version .......................................................... 684
STB islands
connecting to Ethernet networks ....................... 404
creating ........................................................... 384
deleting ........................................................... 387
disconnecting from Ethernet networks ............... 405
exporting ......................................................... 408
importing ......................................................... 411
managing Modbus TCP communication (I/O
scanning)....................................................... 600
mapping (control) ............................................. 423
mapping hardware ........................................... 443
properties ........................................................ 385
representation ................................................. 387
stop
changes requiring to stop the controller.............. 519
stopping
controllers and simulators (control) .................... 536
system server ....................................................50
structure of the application
instantiation stage ............................................ 116
STU files
changing (control) ............................................ 470
creating (control).............................................. 464
supervision
connectivity with Modbus devices...................... 639
supervision with M580 safety systems ............... 595
supervision architecture
description of tasks .......................................... 226
supervision clients
properties ........................................................ 232
supervision data
naming rules......................................................65
supervision pages
Supervision Project Browser
description....................................................... 201
supervision projects
actions ............................................................ 226
building ........................................................... 475
changing built Participant projects ..................... 479
communication mapping import rules................. 247
creating ........................................................... 226
creating client .................................................. 232
creating components ........................................ 229
creating I/O devices ......................................... 232
creating servers ............................................... 230
deploying ........................................................ 520
equipment import rules ..................................... 245
executable import rules .................................... 247
executing ........................................................ 576
export settings ................................................. 241
exporting ......................................................... 238
facet import rules ............................................. 246
generating after changes .................................. 323
hardware mapping import rules ......................... 247
implementing redundancy................................. 236
managing ........................................................ 238
mapping stage ................................................. 457
page import rules ............................................. 245
project definition............................................... 226
Project Explorer and Browser............................ 199
project import window....................................... 247
properties ........................................................ 229
refining............................................................ 360
related project data import rules ........................ 244
restoring after deploying from executable........... 523
restoring after deploying from station node......... 527
service mapping import rules ............................ 247
task quick reference ......................................... 101
task workflow.....................................................98
supervision servers
properties ........................................................ 231
Supervision service
creating in station node..................................... 379
supervision services
actions for station nodes ................................... 383
properties for station nodes............................... 384
support
support contact details........................................78
symbol table files
generating symbol table files............................. 484
synchronization
timeout when refining online ............................. 535
synchronizing
description....................................................... 534
when deploying changes (control) ..................... 495
syslog server
audit trail for user activities..................................56
system
description.........................................................26
system backup
password information and settings .................... 109
system engineering life cycle
concept .............................................................26
graphical representation .....................................26
platform components..........................................27
task quick reference ......................................... 101
task workflow.....................................................98
system folders
system locale
selecting.......................................................... 709
system names
impact of system restoration ............................. 112
system restore
password information and settings .................... 111
system server
logging in and out...............................................44
systems
actions ............................................................ 106
backing up....................................................... 108
creating ........................................................... 106
description.........................................................19
engineering .......................................................97
organizing ....................................................... 105
properties ........................................................ 107
restoring.......................................................... 110
Systems Explorer
opening .............................................................77
EIO0000001114.15
741
T
presentation .................................................... 105
tabs bar
description.........................................................80
tag containers
actions ............................................................ 264
creating tag containers ..................................... 263
properties ........................................................ 264
templates
copying and pasting Global Templates............... 677
creating Global Template folders ....................... 650
description.........................................................20
duplicating Global Templates ............................ 698
exporting ......................................................... 677
Global Template editors .................................... 653
Global Templates actions.................................. 651
Global Templates description ............................ 651
Global Templates Explorer................................ 645
HTML help for user-created templates .................71
import rules for control project-related objects .... 213
import rules for supervision project-related
objects .......................................................... 244
importing ......................................................... 680
instances of templates........................................25
instantiating ..................................................... 115
managing ........................................................ 675
modification strategy ........................................ 688
naming convention........................................... 646
purging the Global Templates library.................. 686
renaming Global Templates .............................. 675
replacing templates of elements ........................ 693
saving changes in Global Templates.................. 675
selecting.......................................................... 119
selecting topological templates ......................... 368
templates Import Editor .................................... 680
terminology .......................................................22
updating Global Templates ............................... 689
using the HTML help for several versions of
templates.........................................................69
Templates Browser
browsing templates .......................................... 119
templates of instances
templates of the topology
updating .......................................................... 407
temporary files
content repository ............................................ 706
terminology
for template components ....................................22
terminology used in this manual ..........................16
timeout
synchronizing standby controllers...................... 541
when synchronizing online changes .................. 535
toolbars
common template editor toolbars ...................... 666
description.........................................................77
engineering client UI description..........................76
Toolbox
Global Templates Explorer................................ 648
topological entities
topological entity identifiers
naming rules......................................................65
topological entity nodes
description....................................................... 366
742 topological folders
import rules ..................................................... 413
topological templates
introduction .......................................................24
subtypes ...........................................................24
topology
exporting ......................................................... 408
import rules for control project-related objects .... 213
import rules for supervision project-related
objects .......................................................... 244
importing ......................................................... 411
managing ........................................................ 406
selecting topological templates ......................... 368
supported components ..................................... 364
updating templates........................................... 407
Topology Explorer
opening .............................................................77
presentation .................................................... 365
topology folders
properties ........................................................ 368
tracking changes
template changes log ....................................... 675
transferring deploying changes to station nodes
(supervision) .................................................. 528
deploying from station node (supervision) .......... 523
deploying to station nodes from executable
(supervision) .................................................. 521
redeploying to engines from executable
(supervision) ...........................................523, 527
synchronizing redundant controllers .................. 541
tree view viewing the application structure in control
projects ......................................................... 260
tree view in control projects
description....................................................... 287
when refining ................................................... 339
when refining online ......................................... 550
trend server redundancy
implementing ................................................... 237
troubleshooting
floating Participant window appearance ...............92
generation diagnostic messages ....................... 331
truncation
rules for equipment (supervision) ...................... 329
type versions changing type versions during generation
(control) ......................................................... 305
types
removing generated types ................................ 303
removing when regenerating............................. 327
U unassigned facets
reassigning...................................................... 334
unassigning
facets.............................................................. 293
generated facets .............................................. 334
unlinked facets
relinking .......................................................... 334
unlinking
facets.............................................................. 334
EIO0000001114.15
unmap
unmapping hardware mappings ........................ 448
unmapping
unmapping communication channels................. 433
Update Control Project command
aborting........................................................... 575
Update Template
command description ....................................... 161
updating
control projects after deploying changes online .. 549
controller configurations ................................... 567
Global Templates ............................................. 689
linked application templates .............................. 166
logical control projects ...................................... 567
template modification strategy........................... 688
template of instances ....................................... 161
templates of elements ...................................... 689
templates with new type version ........................ 166
topological templates ....................................... 407
updating control projects
checking consistency ....................................... 573
deleting FBD sections during update Control
project ........................................................... 573
updating safety control projects ......................... 594
with redundant controllers................................. 534
user authentication
OPC UA configuration files ............................... 476
User Contents folder
location in the content repository ....................... 703
user files redeploying from executable after removing user
files (supervision) ....................................523, 527
user interface
engineering client...............................................76
engineering client UI description..........................76
engineering client work areas..............................79
user-created templates
HTML help for user-created templates .................71
users
activity log files ..................................................59
logging in to server and clients ............................44
working with several clients.................................52
version conflict canceling generation for version conflict
(control) ......................................................... 301
troubleshooting ................................................ 331
versions changing type versions during generation
(control) ......................................................... 305
virtual machine
system locale................................................... 709
VM default keyboard layout............................... 707
W windows
floating Participant windows................................90
Participant window description ............................90
pasting data to Participants.................................92
viewing on separate monitors..............................83
work areas
creating additional work areas.............................83
creating work areas in explorers ..........................84
description.........................................................79
organizing .........................................................82
workflow
task workflow to implement communication..........98
workspace
changing the zoom level .....................................82
zooming in and out .............................................82
workspaces
moving the workspace around.............................81
selecting items...................................................82
working with panes.............................................85
X
X509 user token
OPC UA configuration files ............................... 476
XML
application export file description....................... 184
editing the application export file ....................... 185
editing to manage application links .................... 189
exporting and importing application objects to XML
or CSV .......................................................... 168
importing XML files into the application .............. 191
XVM files
generating symbol table files............................. 484
V
Validity Diagnosis window .................................... 150
validity indicators
analyzing control projects during generation....... 300
description....................................................... 467
instance color icons.......................................... 144
project color icons ............................................ 251
refining control Participant projects .................... 339
Variable Mapping Editor
description....................................................... 436
usage example ................................................ 439
variable mappings peer to peer communication variable import
rules.............................................................. 218
variable name conflict
troubleshooting ................................................ 331
variable tag addresses
OPCUA embedded protocol.............................. 476
variables
about network variables.................................... 350
address allocation during build .......................... 468
managing network variables ............................. 357
naming rules......................................................65
properties ........................................................ 354
when updating Control projects ......................... 571
EIO0000001114.15
Z zooming
magnifying and reducing the workspace view .......82
using the radar view ......................................... 672
zooming out
simplified view in Asset Workspace Editor.......... 149
simplified view in template editors ..................... 673
743
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00 www.se.com
As standards, specifications, and design change from time to time, please ask for confirmation of the information given in this publication.
© 2020 – Schneider Electric . All rights reserved.
EIO0000001114.15