Schneider Electric Process Expert System 4.3 Foundation Library User Guide
Annonce
Annonce
Process Expert
EIO0000002403 06/2017
Process Expert
Foundation Application Templates
User Guide
06/2017 www.schneider-electric.com
2
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical, including photocopying, without express written permission of Schneider Electric.
All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to help ensure compliance with documented system data, only the manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must be followed.
Failure to use Schneider Electric software or approved software with our hardware products may result in injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2016 Schneider Electric. All Rights Reserved.
EIO0000002403 06/2017
Table of Contents
Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Foundation Application Templates . . . . . . . . . . . . . . . . . . . . . . . . . . .
Naming Convention . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
List of Foundation Application Templates . . . . . . . . . . . . . . . . . . . . . .
Chapter 2 Signal Conditioning and Processing . . . . . . . . . . . . . . . .
2.1 Signal Conditioning - Hardware Abstraction Layer . . . . . . . . . . . . . . .
$AISignal_UL - Analog Input Signal Conditioning . . . . . . . . . . . . . .
$AOSignal_UL - Analog Output Signal Conditioning. . . . . . . . . . . . .
$CounterSignal_UL - Counter Signal Conditioning . . . . . . . . . . . .
$DISignal_UL - Digital Input Signal Conditioning. . . . . . . . . . . . . . .
$DOSignal_UL - Digital Output Signal Conditioning . . . . . . . . . . . . .
2.2 HART. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
$AHISignal_UL - HART Device Signal Mapping . . . . . . . . . . . . . . .
$AISignalHART_UL - HART Input Signal Conditioning (M580) . . . .
2.3 Time Stamping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
$TSDInput - Time Stamped Information of Field Signals . . . . . . . . .
2.4 Peer to Peer Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Owner/Consumer Templates. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Data In/Data Out Templates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.5 STAHL Control Module Templates . . . . . . . . . . . . . . . . . . . . . . . . . . .
$STAHLAI8 for STAHL 8-channel Analog Input Modules. . . . . . . . . .
$STAHLAO8 for STAHL 8-Channel Analog Output Modules . . . . . . . .
$STAHLDI16 for STAHL 16-Channel Digital Input Modules . . . . . . . .
$STAHLDO8 for STAHL 8-Channel Digital Output Modules . . . . . . . .
$STAHLAI8HART for STAHL 8-channel Analog Input Modules with
HART Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.6 Using STAHL Control Module Templates . . . . . . . . . . . . . . . . . . . . . .
Use Case Architecture. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Instantiation and Application Links . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring Instances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
31
33
34
35
22
25
27
29
15
16
19
21
13
14
5
9
49
53
54
56
36
36
39
40
58
60
62
65
66
68
69
EIO0000002403 06/2017
3
4
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Finalizing the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The Logical Control Participant Project . . . . . . . . . . . . . . . . . . . . . . . .
STAHL Remote I/O System Configuration. . . . . . . . . . . . . . . . . . . . . .
Chapter 3 Special Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Special Card Application Templates Approach . . . . . . . . . . . . . . . . . .
$QEHC10500 - Quantum High Speed 5-Channel Counter Module . . .
$QEHC20200 - Quantum High Speed 2-Channel Counter Module . . .
$QERT85410 - Quantum Expert Time Stamp Module . . . . . . . . . . . . .
$QERT85420 - Quantum Expert Time Stamp Module . . . . . . . . . . . . .
$TUnsignCptBmx - M340 High Speed Counter Module UnSign . . . .
$TSignCptBmx - M340 High Speed Counter Module Sign . . . . . . . .
$EPITesysUAS - Advantys Special Module for Handling TeSys U
Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
$BMXEHC - M580 and X80 High Speed Counter Module . . . . . . . . . .
98
100
Chapter 4 Variable Templates . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
101
Elementary Variable Templates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
87
89
90
91
73
75
76
79
92
94
96
97
Array Variable Templates. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Data Type Variable Templates . . . . . . . . . . . . . . . . . . . . . .
107
Chapter 5 Using HART Analog I/O Signals. . . . . . . . . . . . . . . . . . . .
109
Getting Started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
102
105
Configuration Stage (Topology Explorer). . . . . . . . . . . . . . . . . . . . . . .
Instantiation Stage (Application Explorer) . . . . . . . . . . . . . . . . . . . . . .
Project Definition Stage (Project Explorer). . . . . . . . . . . . . . . . . . . . . .
Deployment Stage (Topology Explorer) . . . . . . . . . . . . . . . . . . . . . . . .
Related Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
110
111
116
118
119
121
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
123
EIO0000002403 06/2017
Safety Information
Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
EIO0000002403 06/2017
5
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and its installation, and has received safety training to recognize and avoid the hazards involved.
6
BEFORE YOU BEGIN
Do not use this product on machinery lacking effective point-of-operation guarding. Lack of effective point-of-operation guarding on a machine can result in serious injury to the operator of that machine.
WARNING
UNGUARDED EQUIPMENT
Do not use this software and related automation equipment on equipment which does not have point-of-operation protection.
Do not reach into machinery during operation.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
This automation equipment and related software is used to control a variety of industrial processes.
The type or model of automation equipment suitable for each application will vary depending on factors such as the control function required, degree of protection required, production methods, unusual conditions, government regulations, etc. In some applications, more than one processor may be required, as when backup redundancy is needed.
Only you, the user, machine builder or system integrator can be aware of all the conditions and factors present during setup, operation, and maintenance of the machine and, therefore, can determine the automation equipment and the related safeties and interlocks which can be properly used. When selecting automation and control equipment and related software for a particular application, you should refer to the applicable local and national standards and regulations. The
National Safety Council's Accident Prevention Manual (nationally recognized in the United States of America) also provides much useful information.
In some applications, such as packaging machinery, additional operator protection such as pointof-operation guarding must be provided. This is necessary if the operator's hands and other parts of the body are free to enter the pinch points or other hazardous areas and serious injury can occur.
Software products alone cannot protect an operator from injury. For this reason the software cannot be substituted for or take the place of point-of-operation protection.
Ensure that appropriate safeties and mechanical/electrical interlocks related to point-of-operation protection have been installed and are operational before placing the equipment into service. All interlocks and safeties related to point-of-operation protection must be coordinated with the related automation equipment and software programming.
EIO0000002403 06/2017
NOTE: Coordination of safeties and mechanical/electrical interlocks for point-of-operation protection is outside the scope of the Function Block Library, System User Guide, or other implementation referenced in this documentation.
START-UP AND TEST
Before using electrical control and automation equipment for regular operation after installation, the system should be given a start-up test by qualified personnel to verify correct operation of the equipment. It is important that arrangements for such a check be made and that enough time is allowed to perform complete and satisfactory testing.
WARNING
EQUIPMENT OPERATION HAZARD
Verify that all installation and set up procedures have been completed.
Before operational tests are performed, remove all blocks or other temporary holding means used for shipment from all component devices.
Remove tools, meters, and debris from equipment.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Follow all start-up tests recommended in the equipment documentation. Store all equipment documentation for future references.
Software testing must be done in both simulated and real environments.
Verify that the completed system is free from all short circuits and temporary grounds that are not installed according to local regulations (according to the National Electrical Code in the U.S.A, for instance). If high-potential voltage testing is necessary, follow recommendations in equipment documentation to prevent accidental equipment damage.
Before energizing equipment:
Remove tools, meters, and debris from equipment.
Close the equipment enclosure door.
Remove all temporary grounds from incoming power lines.
Perform all start-up tests recommended by the manufacturer.
EIO0000002403 06/2017
7
OPERATION AND ADJUSTMENTS
The following precautions are from the NEMA Standards Publication ICS 7.1-1995 (English version prevails):
Regardless of the care exercised in the design and manufacture of equipment or in the selection and ratings of components, there are hazards that can be encountered if such equipment is
improperly operated.
It is sometimes possible to misadjust the equipment and thus produce unsatisfactory or unsafe operation. Always use the manufacturer’s instructions as a guide for functional adjustments.
Personnel who have access to these adjustments should be familiar with the equipment manufacturer’s instructions and the machinery used with the electrical equipment.
Only those operational adjustments actually required by the operator should be accessible to the operator. Access to other controls should be restricted to prevent unauthorized changes in operating characteristics.
8
EIO0000002403 06/2017
About the Book
At a Glance
Document Scope
This document describes the Foundation templates, and the Control services that they provide.
For a more detailed description of their associated Control services and its parameters, refer to the user guides mentioned in this document.
This document is for users with knowledge of Process Expert, and its Control and Supervision
Participants.
Validity Note
This document is valid for Process Expert 4.3 or later. It supersedes any previous version.
Related Documents
Title of Documentation
Process Expert Foundation Control Services User Guide
Process Expert Process Control Services User Guide
Process Expert Device Control Services User Guide
Process Expert User Guide
Process Expert Global Templates Reference Manual
Reference Number
EIO0000002404
EIO0000000988
EIO0000001306
EIO0000001114
EIO0000001986 (eng)
You can download these technical publications and other technical information from our website at http://www.schneider-electric.com/en/download
PES Technical Support
Visit www.pes.schneider-electric.com for support, software updates, and latest information.
Registration required.
EIO0000002403 06/2017
9
Product Related Information
WARNING
LOSS OF CONTROL
Perform a Failure Mode and Effects Analysis (FMEA) of your application, and apply preventive and detective controls before implementation.
Provide a fallback state for undesired control events or sequences.
Provide separate or redundant control paths wherever required.
Supply appropriate parameters, particularly for limits.
Review the implications of transmission delays and take actions to mitigate.
Review the implications of communication link interruptions and take actions to mitigate.
Provide independent paths for control functions (for example, emergency stop, over-limit conditions, and fault conditions) according to the safety analysis and applicable codes, and regulations.
Apply local accident prevention and safety regulations and guidelines. 1
Test each implementation of this library for proper operation before placing it into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
1 For additional information, refer to NEMA ICS 1.1 (latest edition), Safety Guidelines for the
Application, Installation, and Maintenance of Solid State Control and to NEMA ICS 7.1 (latest edition), Safety Standards for Construction and Guide for Selection, Installation and Operation of
Adjustable-Speed Drive Systems or their equivalent governing your particular location.
The application of this product requires expertise in the design and operation of control systems.
WARNING
UNINTENDED EQUIPMENT OPERATION
Allow only authorized personnel with expertise in the design and operation of control systems to program, install, alter, and apply this product.
Follow local and national safety codes and standards.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Examples described in this manual are provided for information only.
10
EIO0000002403 06/2017
WARNING
UNINTENDED EQUIPMENT OPERATION
Adapt examples that are given in this manual to the specific functions and requirements of your industrial application before you implement them.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
EIO0000002403 06/2017
11
12
EIO0000002403 06/2017
Process Expert
Overview
EIO0000002403 06/2017
Overview
Chapter 1
Overview
What Is in This Chapter?
This chapter contains the following topics:
Topic
Foundation Application Templates
Naming Convention
List of Foundation Application Templates
Page
14
15
16
EIO0000002403 06/2017
13
Overview
Foundation Application Templates
Description
The Process Expert Foundation library provides resources that have been pre-configured and tested by Schneider Electric. Foundation application templates provide standardized elementary resources that are used in control module templates of the General Purpose library. It also provides additional services that are required to manage data transmission within a system.
The resources provided by Foundation application templates are encapsulated in facet or composite templates. You can customize the services provided by these templates at the instance level.
You can link Foundation application templates to compatible process and device templates.
Foundation Application Template Services
Foundation application templates provide the following services:
Control Includes core services plus additional, optional services, which you can activate if needed.
Function blocks and variables are the resources that are encapsulated in these templates to provide such services.
Exposed Interfaces
Foundation application templates expose interfaces that allow you to make the following types of connections:
To topological instances (mapping interfaces)
To other application instances (application interfaces)
Exposed interface can have the following roles:
Ref Role receiving data from the linked object. This role is represented graphically as male.
Def Role providing data to the linked object. This role is represented graphically as female.
CO Is used from the application templates representing communications objects (CO) that receive the data provided from the system configuration. This role is represented graphically as male.
DO Is used from the application templates representing device objects (DO) that receive the data provided from the system configuration. This role is represented graphically as male.
HO Is used from the topological template (also called hardware objects (HO)) to expose the information provided by the hardware (for example, topological addresses, slave number, and so on) to the project facets. This role is represented graphically as female.
SO Is used from the application templates representing the signal objects (SO) or I/O module objects that receive the data provided from the system configuration. This role is represented graphically as male.
14
EIO0000002403 06/2017
Naming Convention
Prefix
The $ character is used as prefix for templates made by Schneider Electric.
Suffixes
The following suffixes are used to identify types of templates:
No suffix: Control module template (composite).
UC : Control composite template.
UL : Control facet template.
Overview
EIO0000002403 06/2017
15
Overview
List of Foundation Application Templates
List of Families
The templates described in this document are grouped by family.
The table lists the control module templates of each family:
Family name
Signal conditioning -
Hardware Abstraction
Layer (HAL)
Time stamping
Unity Peer to Peer
Templates
$AISignal_UL
( see page 22 )
$AOSignal_UL
( see page 25 )
$DISignal_UL
( see page 29 )
$TSDInput_UL
( see page 36 )
$DOSignal_UL
( see page 31 )
$AHISignal_UL
( see page 34 )
$AISignalHART_UL
( see page 35 )
$CounterSignal_UL
( see page 27 )
(
$TSDInput see page 36
$TSDInput8
)
,
( see page 36 ) ,
$TSDInput16
( see page 36 ) and
$TSDInput32
( see page 36 )
Data In/Data Out
( see page 49 )
Owner/Consumer
( see page 40 )
Description
Analog input signal conditioning
Analog output signal conditioning
Digital input signal conditioning
Time stamped information of field signals
Digital output signal conditioning
HART device signal mapping
HART input signal conditioning
(M580)
Counter signal conditioning
Time stamped information of field signals
Data In/Out templates
Owner/Consumer templates
16
EIO0000002403 06/2017
Family name
STAHL
Unity Special In Rack
Cards
Variable templates
Templates
$STAHLAI8
( see page 54 )
$STAHLAO8
( see page 56 )
$STAHLDI16
( see page 58 )
Description
For STAHL 8-channel analog input modules
For STAHL 8-channel analog output modules
For STAHL 16-channel digital input modules
$STAHLDO8
( see page 60 )
$STAHLAI8HART
( see page 62 )
$QEHC10500
( see page 90 )
$QEHC20200
( see page 91 )
$QERT85410
( see page 92 )
For STAHL 8-channel digital output modules
For STAHL 8-channel analog input modules with 4 or 8 HART signals.
Quantum high speed 5-channel counter module
Quantum high speed 2-channel counter module
Quantum expert time stamp module
$QERT85420
( see page 94 )
$TUnsignCptBmx
( see page 96 )
$TSignCptBmx
( see page 97 )
$EPITesysUAS
( see page 98 )
Quantum Expert Time Stamp Module
M340 high speed counter module
UnSign
M340 high speed counter module
Sign
Advantys special module for handling
TeSys_U information
$BMXEHC ( see page 100 ) M580 and X80 high speed counter module
Unity Elementary variables ( see page 102
Unity Array variables
( see page 105 )
Unity REF_TO Variables
( see page 107 )
)
Elementary variable templates
Array variable templates
Reference data type variable templates
Overview
EIO0000002403 06/2017
17
Overview
Location of Templates
Templates of the following families are located at the path indicated in the table:
Template family
Signal conditioning
STAHL templates
Hart
Peer to peer communication
Unity Special In Rack Cards
Path
Global Templates/Foundation Library/Application/Control
Modules/Unity/Unity Signal Conditioning
Global Templates/Foundation Library/Application/Control
Modules/STAHL
Global Templates/Foundation Library/Application/Control
Modules/Unity/Unity Signal Conditioning
Global Templates/Foundation Library/Application/Control
Modules/Unity/Unity Peer to Peer
Global Templates/Foundation Library/Application/Control
Modules/Unity/Unity Special In Rack Cards
18
EIO0000002403 06/2017
Process Expert
Signal Conditioning and Processing
EIO0000002403 06/2017
Signal Conditioning and Processing
Chapter 2
Signal Conditioning and Processing
Overview
This chapter describes the functionality of Foundation application templates for signal conditioning and processing, and their composition.
These templates do not reflect any specific installation.
WARNING
LOSS OF CONTROL
Perform a Failure Mode and Effects Analysis (FMEA) of your application, and apply preventive and detective controls before implementation.
Provide a fallback state for undesired control events or sequences.
Provide separate or redundant control paths wherever required.
Supply appropriate parameters, particularly for limits.
Review the implications of transmission delays and take actions to mitigate.
Review the implications of communication link interruptions and take actions to mitigate.
Provide independent paths for control functions (for example, emergency stop, over-limit conditions, and fault conditions) according to the safety analysis and applicable codes, and regulations.
Apply local accident prevention and safety regulations and guidelines. 1
Test each implementation of this library for proper operation before placing it into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
1 For additional information, refer to NEMA ICS 1.1 (latest edition), Safety Guidelines for the
Application, Installation, and Maintenance of Solid State Control and to NEMA ICS 7.1 (latest edition), Safety Standards for Construction and Guide for Selection, Installation and Operation of
Adjustable-Speed Drive Systems or their equivalent governing your particular location.
What Is in This Chapter?
This chapter contains the following sections:
Section
2.1
2.2
2.3
2.4
Topic
Signal Conditioning - Hardware Abstraction Layer
HART
Time Stamping
Peer to Peer Communication
Page
21
33
36
39
EIO0000002403 06/2017
19
Signal Conditioning and Processing
Section
2.5
2.6
Topic
STAHL Control Module Templates
Using STAHL Control Module Templates
Page
53
65
20
EIO0000002403 06/2017
Signal Conditioning and Processing
Signal Conditioning - Hardware Abstraction Layer
Section 2.1
Signal Conditioning - Hardware Abstraction Layer
Overview
This section explains the basic functionality of the hardware abstraction layer (HAL) templates
(signal objects) and their composition.
Hardware abstraction layer is a mechanism that emulates access to hardware resources to maintain an application device-independent. These HAL templates generate elementary digital or analog Control Participant variables, which represent the value and/or quality of hard-wired signals.
You can use these variables in the program and map them to the hardware that is configured in the topology. The mapping generates the corresponding topological addresses automatically.
What Is in This Section?
This section contains the following topics:
Topic
$AISignal_UL - Analog Input Signal Conditioning
$AOSignal_UL - Analog Output Signal Conditioning
$CounterSignal_UL - Counter Signal Conditioning
$DISignal_UL - Digital Input Signal Conditioning
$DOSignal_UL - Digital Output Signal Conditioning
27
29
31
Page
22
25
EIO0000002403 06/2017
21
Signal Conditioning and Processing
$AISignal_UL - Analog Input Signal Conditioning
Description
The $AISignal_UL hardware abstraction layer facet template creates variables and elementary function blocks (EFBs) to model the value, and optionally, the quality of analog input signals.
Alternatively, the template can process an external variable of Int or Real data type in which case it acts as a pass-through without generating encapsulated constituents.
Parameters
The table describes the parameters of the $AISignal_UL facet template that you can configure.
Type Default value Description Name
Configuration
Type Boolean
AISignalName
ChannelDataType
String
Enum
False (check box cleared)
Blank
Int
Select this parameter to process signal quality in addition to signal value.
NOTE: The parameter is selected by default when ChannelDataType is Real.
Enter a name to be used for the generated EFB and variables.
Select the data type of the signal to be acquired:
Int
Real
The table describes the logic generated by the facet template depending on its parameter configuration.
Value of the Type parameter
Value of the
ChannelDataType parameter
Int
Generated logic
AISignalCond1 EFB is generated along with a variable.
False (check box cleared)
True (check box selected)
False (check box cleared)
True (check box selected)
Real
AISignalCond1 EFB is generated along with variables
( SIGNALVALUE , ERROR , COMSTATUS , MODULESTATUS , and
NOTMODULESTATUS ) to provide signal quality information.
AISignalCondReal1 EFB is generated along with variables
( SIGNALVALUE , ERROR , COMSTATUS , MODULESTATUS , and
NOTMODULESTATUS ) to provide signal quality information.
NOTE: During the build, the number of variables created varies depending on the hardware to which the facet template is mapped.
22
EIO0000002403 06/2017
Signal Conditioning and Processing
Analog Signal Acquisition and Transmission
The table describes the interfaces exposed by the facet template to acquire an analog input signal depending on the signal type that is configured and the signal source.
Signal type
Int
Real
Signal from an I/O channel
AIChannel: Mapping interface to be used in the Hardware
Mapping Editor.
Acquires signal with or without signal quality.
AIChannelReal: Mapping interface to be used in the
Hardware Mapping Editor.
Acquires signal with or without signal quality.
Variable from another instance
IntVar: Application interface to be used in the Links Editor.
Acquires signal value only.
Type/role: $Int / Ref
When the interface is connected, the template serves only as a pass-through and no logic is generated from it.
AINPUTSignalExt: Application interface to be used in the
Links Editor. Acquires signal value with signal quality.
Type/role: $AINPUTSignal / HO
To enable the interface, select to acquire also signal quality by setting the Type parameter to true.
RealVar: Application interface to be used in the Links Editor.
Acquires signal value with or without signal quality.
Type/role: $Real / Ref
When the interface is connected, the template serves only as a pass-through and no logic is generated from it.
NOTE: Connecting an application interface disables the other application interfaces as well as the corresponding mapping interface. For example, if the signal type is Int and the Type parameter true, connecting the IntVar interface disables the AINPUTSignalExt interface and the AIChannel mapping interface.
The table describes the interfaces exposed by the facet template to transmit an analog input signal depending on the interface that receives the signal and the type of the signal.
Signal transmission interface
AISignal
Type/role
/ Def
Description
AINPUTSignal
AISignalReal
AINSPUTSignalReal
/ DO
/ Def
/ DO
Transmits the name of the variable holding the signal value when the signal is acquired by using the IntVar interface.
Transmits the names of the variables holding the signal value and signal quality when the signal is acquired by using the AINPUTSignalExt or
AIChannel (mapping) interfaces.
Transmits the name of the variable holding the signal value when the signal is acquired by using the RealVar interface.
Transmits the names of the variables holding the signal value and signal quality when the signal is acquired by using the RealVar or AIChannelReal
(mapping) interfaces.
EIO0000002403 06/2017
23
Signal Conditioning and Processing
Composition
The template encapsulates the AISignalCond1 and AISignalCondReal1 EFBs, which provide the core Control services.
Control Resource Description
Refer to the AISignalCond1 and AISignalCondReal1 - Analog Input Signal Conditioning
(see Process Expert , Foundation Control Services User Guide) for more details.
24
EIO0000002403 06/2017
Signal Conditioning and Processing
$AOSignal_UL - Analog Output Signal Conditioning
General Description
The $AOSignal_UL hardware abstraction layer facet template creates variables to model the value, and optionally the quality of analog output signals.
Alternatively, the template can process an external variable of Int data type in which case it acts as a pass-through.
Applying the Analog Signal
The table describes the options offered by the facet template to apply an analog output signal:
Hardware mapping Links Signal applied to
I/O Channel
Signal quality no yes
Variable no yes
AOChannel/SO mapping interface
–
IntVar PO interface: Signal value only
IntVar PO interface: Signal value only
AOUTPUTSignalExt PO interface: Signal quality
IntVar and AOSignal interfaces. Signal value only.
IntVar and AOSignal interfaces: Signal value only.
AOUTPUTSignalExt and AOUTPUTSignal interfaces: Signal quality
NOTE: Using a PO interface disables the mapping interface.
Parameters
The table describes the parameters of the $AOSignal_UL facet template that you can configure:
Type Default value Description Name
Configuration
Type Boolean 0
AOSignalName
ChannelDataType
String
Enum empty
Int
Select this parameter to process signal quality in addition to signal value.
Enter a name to be used for the generated DFB and variables.
Select the data type of the signal to be acquired:
Int
Real
EIO0000002403 06/2017
25
Signal Conditioning and Processing
The table describes the logic generated by the facet template depending on the Include Signal
Quality and Conditioning parameter configuration:
Type value Generated logic
False
(check box cleared)
A variable and AOSIGNALMOVE DFB are generated.
True (check box selected)
AOSIGNALCOND DFB is generated along with variables
( SIGNALVALUE , ERROR , COMSTATUS , MODULESTATUS , and
NOTMODULESTATUS ) to provide signal quality information.
NOTE: During the build, the number of variables created varies depending on the hardware to which the facet template is mapped.
Composition
The HAL template encapsulates the AOSIGNALCOND and AOSIGNALMOVE DFBs, which provide the core Control services.
Control Resource Description
Refer to the AOSIGNALCOND - Analog Output Signal Conditioning (see Process Expert ,
Foundation Control Services User Guide) for more details.
26
EIO0000002403 06/2017
Signal Conditioning and Processing
$CounterSignal_UL - Counter Signal Conditioning
General Description
The $CounterSignal_UL hardware abstraction layer facet template creates variables to model the value, and optionally the quality of counter signals.
Counter Signal Acquisition
The table describes the options offered by the $CounterSignal_UL facet template to acquire a counter signal depending on the channel data type as shown below:
Signal acquired from
Variable
Channel Data
Type
UDINT
Hardware mapping Links
UINT
-
-
CounterChannelUDINT/SO mapping interface
CounterSignalUDINT and
CounterSignal interfaces:
Signal value only.
CounterSignalUDINTExt and CounterSignal interfaces: Signal quality
-
CounterSignalUINT and
CounterSignal interfaces:
Signal value only.
CounterSignalUINTExt and CounterSignal interfaces: Signal quality
Counter Channel
( BMXEHC0200/BMXEHC0800/
BMXERT1604T/140QEHC10500
/140QEHC20200 )
UDINT
Counter Channel
( 140QEHC10500/
140QEHC20200 )
UINT CounterChannelUINT/SO mapping interface
-
EIO0000002403 06/2017
27
Signal Conditioning and Processing
Parameters
The table describes the parameters of the $CounterSignal_UL facet template that you can configure:
Type Default value Description Name
Configuration
CounterSignalName String Empty
ChannelDataType Enum UDINT
Enter a name to be used for the generated EFB and variables.
Selects the channel data type of the signal to be acquired
UDINT
UINT
NOTE: During the build, the number of variables created varies depending on the hardware to which the facet template is mapped.
Composition
The HAL template encapsulates the CounterSignalCondUDInt and CounterSignal-
CondUInt EFBs, which provide the core Control services.
Control Resource Description
Refer to the CounterSignalCondUDInt and CounterSignalCondUInt - Counter Signal
Conditioning (see Process Expert , Foundation Control Services User Guide) for more details.
28
EIO0000002403 06/2017
Signal Conditioning and Processing
$DISignal_UL - Digital Input Signal Conditioning
General Description
The $DISignal_UL hardware abstraction layer facet template creates variables to model the value, and optionally the quality of digital input signals.
Alternatively, the template can process an external variable in which case it acts as a pass-through without generating encapsulated constituents.
Digital Signal Acquisition
The table describes the options offered by the facet template to acquire a digital input signal depending on the signal source:
Hardware mapping Links Signal acquired from
I/O Channel
Signal quality no yes
Variable no yes
DIChannel/SO mapping interface
–
BoolVar PO interface: Signal value only
BoolVar PO interface: Signal value only
DINPUTSignalExt PO interface: Signal quality
BoolVar and DISignal interfaces. Signal value only.
BoolVar and DISignal interfaces: Signal value only.
DINPUTSignalExt and DINPUTSignal interfaces: Signal quality
NOTE: Using a PO interface disables the mapping interface.
Parameters
The table describes the parameters of the $DISignal_UL facet template that you can configure:
Type Default value Description Name
Configuration
Negate
Type
DISignalName
Boolean
Boolean
String
False
0
Empty
True = Negates the input or output signal.
Select this parameter to process signal quality in addition to signal value.
Enter a name to be used for the generated EFB and variables.
EIO0000002403 06/2017
29
Signal Conditioning and Processing
Name
TimeStamping
PLCHMIVar
Type
Enum
Boolean
Default value Description
None Sets the Time stamping variable providing the signal value.
Possible values:
Both edges .
Rising edges .
Falling edges .
None .
attributes of the generated
False
NOTE: By default, Process Expert uses the System time stamping mode, which supports only the both
Edges setting.
The other values are supported by the Applicative time stamping mode. Refer to the topic describing
Unity Pro Settings (see Process Expert, Control
Participant Services, User Guide) .
Sets the HMI variable attribute of the generated variable providing the signal value.
NOTE: Set this parameter to True if you change the default value for TimeStamping ; otherwise, the Time stamping attribute of the generated variable is set to
None independently of your selection.
The table describes the logic generated by the facet template depending on the Include Also
Quality Signal parameter configuration:
Type value
False (check box cleared)
True (check box selected)
Negate value Generated logic
0 or 1 A variable and DISignalCond1 EFB are generated.
0 or 1
(
DISignalCond1
SIGNALVALUE ,
EFB is generated along with variables
ERROR , COMSTATUS , MODULESTATUS , and
NOTMODULESTATUS ) to provide signal quality information.
NOTE: During the build, the number of variables created varies depending on the hardware to which the facet template is mapped.
Composition
The HAL template encapsulates the DISignalCond1 EFB, which provides the core Control services.
Control Resource Description
Refer to the DISignalCond1 - Digital Input Signal Conditioning (see Process Expert , Foundation
Control Services User Guide) for more details.
30
EIO0000002403 06/2017
Signal Conditioning and Processing
$DOSignal_UL - Digital Output Signal Conditioning
General Description
The $DOSignal_UL hardware abstraction layer facet template creates variables to model the value, and optionally the quality of analog output signals.
Alternatively, the template can process an external variable in which case it acts as a pass-through.
Applying the Digital Signal
The table describes the options offered by the facet template to apply a digital output signal:
Signal applied to
I/O Channel
Variable
Signal quality no yes no yes
Hardware mapping Links
DOChannel/SO mapping interface
–
BoolVar PO interface: Signal value only
BoolVar PO interface: Signal value only
DOUTPUTSignalExt PO interface: Signal quality
BoolVar and DOSignal interfaces. Signal value only.
BoolVar and DOSignal interfaces: Signal value only.
DOUTPUTSignalExt and DOUTPUTSignal interfaces: Signal quality
NOTE: Using a PO interface disables the mapping interface.
Parameters
The table describes the parameters of the $DOSignal_UL facet template that you can configure:
Type Default value Description Name
Configuration
Negate
Type
DOSignalName
Boolean
Boolean
String
False
0
Empty
True = Negates the input or output signal.
Select this parameter to process signal quality in addition to signal value.
Enter a name to be used for the generated DFB and variables.
EIO0000002403 06/2017
31
Signal Conditioning and Processing
The table describes the logic generated by the facet template depending on the Include Also
Quality Signal parameter configuration:
Type value
False
(check box cleared)
True
(check box selected)
Generated logic
A variable and DOSIGNALMOVE DFB are generated.
DOSIGNALCOND DFB is generated along with variables
( SIGNALVALUE , ERROR , COMSTATUS , MODULESTATUS , and
NOTMODULESTATUS ) to provide signal quality information.
NOTE: During the build, the number of variables created varies depending on the hardware to which the facet template is mapped.
Composition
The HAL template encapsulates the $DOSIGNALCOND and DOSIGNALMOVE DFBs, which provide the core Control services.
Control Resource Description
Refer to the DOSIGNALCOND - Digital Output Signal Conditioning (see Process Expert ,
Foundation Control Services User Guide) for more details.
32
EIO0000002403 06/2017
Signal Conditioning and Processing
HART
Section 2.2
HART
Overview
This section describes the functionality of HART templates and their composition.
What Is in This Section?
This section contains the following topics:
Topic
$AHISignal_UL - HART Device Signal Mapping
$AISignalHART_UL - HART Input Signal Conditioning (M580)
Page
34
35
EIO0000002403 06/2017
33
Signal Conditioning and Processing
$AHISignal_UL - HART Device Signal Mapping
Description
The $AHISignal_UL facet template models the value and/or quality of signals of HART devices that are part of the Krohne instrumentation library. It allows mapping these signals to the four channels of an STBAHI8321 HART interface module, using one mapping interface.
You can also use this template together with the $AnalogInput or $AnalogInput1 templates to map signals of custom Krohne-like templates.
For more information, refer to the description of the various use cases (see Process Expert ,
Process Templates User Guide) .
NOTE: This facet template is referenced by templates of the Krohne instrumentation library.
Composition
The $AHISignal_UL template encapsulates the AHISIGNAL DFB (see Process Expert ,
Foundation Control Services User Guide) , which provides core Control services.
Interfaces
The template exposes the following interfaces:
Interface identifier
HARTChData
PAISignalReal
PAINPUTSignalReal
SAISignalReal
SAINPUTSignalReal
TAISignalReal
TAINPUTSignalReal
QAISignalReal
QAINPUTSignalReal
Type/role
$HARTChData/Def
Description
Channel data from AHISIGNAL to HART DFB.
$Real/Def
$Real/Def
Provides the name of the primary variable.
$AinputSignalReal/DO Provides the name of the primary variable with signal quality.
Provides the name of the secondary variable.
$AinputSignalReal/DO Provides the name of the secondary variable with signal quality.
$Real/Def Provides the name of the tertiary variable.
$AinputSignalReal/DO Provides the name of the tertiary variable with signal quality.
$Real/Def Provides the name of the quaternary variable.
$AinputSignalReal/DO Provides the name of the quaternary variable with signal quality.
34
EIO0000002403 06/2017
Signal Conditioning and Processing
$AISignalHART_UL - HART Input Signal Conditioning (M580)
Description
The Hardware Mapping Editor of Process Expert allows you to map only 1 signal per channel of a supported HART analog I/O module, which is configured in the topology. The HART module is acting as a regular I/O module and the signal corresponds to the Primary Variable (PV). The other
HART signals, for example, Secondary Variable (SV), Tertiary Variable (TV), and/or Quarternary
Variable (QV), and so on are not available.
The $AISignalHART_UL facet template allows you to use all HART signals (including PV) coming from supported HART analog input and output modules by allocating manually state RAM addresses to variables representing these HART signals.
Parameters
The table describes the parameters of the $AISignalHART_UL facet template that you can configure:
Name
AISignalVar_Add
AISignalError_Add
Type
String
String
AISignalModStatus_Add String
AISignalName
Type
String
Boolean
Default value
0
0
0
0
0
Description
HART AI signal value address excluding %MW
HART Detected error in AI signal address excluding %MW
HART AI signal mod status address excluding
%MW
Enter a name to be used for the generated EFB and variables.
Select this parameter to process signal quality in addition to signal value.
Composition
The template encapsulates the following constituents, which provide the Control services:
AISignalHart1
AISignalErrorBOOL
AISignalModStBOOL
AISignalVar
EIO0000002403 06/2017
35
Signal Conditioning and Processing
Time Stamping
Section 2.3
Time Stamping
$TSDInput - Time Stamped Information of Field Signals
General Description
The $TSDInput control module template receives time stamped information of field signals and passes this information on to alarm pages of the Supervision runtime.
NOTE:
Apart from the single-channel time stamping template, 8-, 16-, 32 channel time stamping templates are also available.
$TSDInput8 : This template receives time stamped information from 8-channel time stamping
modules.
$TSDInput16 : This template receives time stamped information from 16-channel time stamping modules.
$TSDInput32 : This template receives time stamped information from 32-channel time stamping modules.
The configuration of these templates is similar to the single-channel time stamping template.
36
EIO0000002403 06/2017
Signal Conditioning and Processing
Parameters
Configuration
The table describes the Configuration parameters that you can configure:
Element Name Name
Control Negate
Type
DISignalName
TimeStamping
Type
Boolean
Boolean
String
Enum
Default value Description
False
False
True = Negates the input or output signal.
Refer to DISignal_UL ( see page 29 ) .
–
Both Edges
Enter a name to be used for the generated
EFB and variables.
Sets the Time stamping attributes of the generated variable providing the signal value.
Possible values:
Both edges .
Rising edges .
Falling edges .
None .
NOTE: By default, Process Expert uses the
System time stamping mode, which supports only the Both Edges setting.
The other values are supported by the
Applicative time stamping mode. Refer to the topic describing Unity Pro Settings
(see Process Expert, Control Participant
Services, User Guide) .
Composition
The $TSDInput template references composite and facet templates, which provide the following services:
Control Includes core services input signal.
Supervision These services complement the Control services.Supervision Services are optional.
The table describes the services that are available from the $TSDInput control module and the corresponding facet, which implements the service:
Control
Services
Facet template Facet template
Control $DISignal_UL
Control service description
Refer to
$DISignal_UL
(see Process Expert
, Foundation Control
Services User Guide)
Associated
Supervision services
Corresponding facet template
Supervision $TSDISignal
_CD
Control
Services
Control $DISignal
_UL
EIO0000002403 06/2017
37
Signal Conditioning and Processing
The table describes the services that are available from the $TSDInput8 , $TSDInput16 ,
$TSDInput32 control module and the corresponding facet, which implements the service:
Control Services
( $TSDISignalx_UC )
Control TSDISignal
_1 to
TSDISignal
_x
Facet template
$DISignal_
UL
Control service description
Refer to
$DISignal_UL
(see Process
Expert ,
Foundation
Control
Services User
Guide)
Where x represents the number of channels (8, 16, or 32)
Associated Supervision services
($TSDISignalx_CS)
TSDISignal_CD1 to
TSDISignal_CDx
Corresponding facet template
$TSDISignal_CD
Interfaces
The time stamping templates expose the following application interfaces:
Interface identifier
DISignal
DINPUTSignal
Type/role
$Bool/Def
$DINPUTSignal/Def
Description
Provides the name of the parameter, which holds the digital input signal value.
Provides the name of the parameters, which hold the digital input signal value and signal quality.
NOTE: There are as many pairs of interfaces as there are channels.
38
EIO0000002403 06/2017
Signal Conditioning and Processing
Peer to Peer Communication
Section 2.4
Peer to Peer Communication
Overview
This section describes the functionality of peer to peer communication templates and their composition.
What Is in This Section?
This section contains the following topics:
Topic
Owner/Consumer Templates
Data In/Data Out Templates
Page
40
49
EIO0000002403 06/2017
39
Signal Conditioning and Processing
Owner/Consumer Templates
Description
Owner-consumer templates allow you to exchange, using peer to peer communication, sets of data between two Control projects, one being the owner, the other the consumer communicate different data types.
(see Process Expert,
User Guide) , and the consumer template to the consumer project. Several templates exist to
The owner template is assigned to the owner project, which provides the data: Either physical I/O signals or external variables (logical signals).
The owner template gets data through the following ways:
Hardware mapping for physical I/O signals
Interface links with other instances (Links Editor) or refinement for logical signals
You can use only 1 type of link at once for each channel.
Both data value and detected failure value are transported between the owner and the consumer.
In addition to the detected failure value provided by the owner, you can configure it to also include the quality of the signal.
1 pair of owner/consumer templates exists for each of the following use cases:
Digital signals:
Exchange of up to 16 boolean input signals
Exchange of up to 16 boolean output signals
Analog signals:
Exchange of up to 8 integer input signals
Exchange of up to 8 integer output signals
NOTE: A typical use case for these templates is to implement distributed I/Os with the Modicon
M340 PRA module. In such use case, the Control project deployed to the PRA acts as owner, and the Control project executing the logic acts as the consumer.
Template Naming Convention
The templates follow a naming convention:
$<data type><amount of data><signal type>_<role>
Where:
<data type> is Bool or Int
<amount of data> is 8 or 16
<Signal type> is IN for inputs (from owner to consumer) or OUT for outputs (from consumer to owner)
<role> is O for the owner side and C for the consumer side
40
EIO0000002403 06/2017
Signal Conditioning and Processing
Configuring the Communication Timeout
An internal mechanism is present in the templates to verify if the peer to peer communication is working correctly. A continuously increasing internal counter keeps sending the count value to the counterpart controller, which monitors this count value and detects whether the count value is stalled within a time-out value.
You can configure the Communication Time Out parameter in the instance of the consumer template, using the Properties window. Enter a value in seconds, depending on the architecture that is used.
List of Templates
The following owner/consumer templates are available:
Identifier
$Bool16INO
$Bool16INC
$Bool16OUTO
$Bool16OUTC
$Int8INO
$Int8INC
$Int8OUTO
$Int8OUTC
Description
Packs and exposes up to 16 boolean input signals from the owner project and exposes them to the consumer.
Unpacks and consumes up to 16 boolean input signals that are received from the owner project.
Packs and exposes up to 16 boolean output signals from the owner project and exposes them to the consumer.
Unpacks and consumes up to 16 boolean output signals that are received from the owner project.
Packs and exposes up to 8 integer input signals from the owner project and exposes them to the consumer.
Unpacks and consumes up to 8 integer input signals that are received from the owner project.
Packs and exposes up to 8 integer output signals from the owner project and exposes them to the consumer.
Unpacks and consumes up to 8 integer output signals that are received from the owner project.
EIO0000002403 06/2017
41
Signal Conditioning and Processing
$Bool16INO
The template exposes the following interfaces:
Name
Bool16InO
DISignalxx
DINPUTSignalxx
Type/role Description
$Bool16InData/Def Application interface to link to the related consumer template.
$Bool/Ref Application interface for digital signal value. This interface only provides the name of the variable holding the digital signal value.
Linking this interface disables the
DINPUTSignalxx interface for the channel.
$DINPUTSignal/Ref Application interface for external signal and detected failure value.
Linking this interface disables the DISignalxx interface for the channel.
NOTE: xx represents the channel number in the template, from 01 to 16.
$Bool16INC
The template exposes the following interfaces:
Name
Bool16InC
$DISignalxx
$DINPUTSignalxx
Type/role
$Bool16InData/Ref
$Bool/Def
$DInputSignal/Def
Description
Application interface to link to the related owner template.
Application interface for digital signal value.
Application interface for signal and detected failure value.
NOTE: xx represents the channel number in the template, from 01 to 16.
$Bool16OUTO
The template exposes the following interfaces:
Name
Bool16OutData
BoolVarxx
DOUPUTSignalxx
Type/role
$Bool16OutData/Def
$Bool/Def
$DOUTPUTSignal/PO
Description
Application interface to link to the related consumer template.
Application interface for digital signal value.
Application interface for external signal and detected failure value.
NOTE: xx represents the channel number in the template, from 01 to 16.
42
EIO0000002403 06/2017
Signal Conditioning and Processing
$Bool16OUTC
The template exposes the following interfaces:
Name
Bool16OutData
BoolVarxx
DOUTPUTSignalxx
Type/role
$Bool16OutData/Ref
$Bool/Ref
$DOUTPUTSignal/DO
Description
Application interface to link to the related owner template.
Application interface for digital signal value.
Application interface for signal and detected failure value.
NOTE: xx represents the channel number in the template, from 01 to 16.
$Int8INO
The template exposes the following interfaces:
Name
Int8InO
AISignalxx
AINPUTSignalxx
Type/role
$Int8InData/Def
$Int/Ref
$AINPUTSignal/HO
Description
Application interface to link to the related consumer template.
Application interface for analog signal value.
Linking this interface disables the
AINPUTSignalxx interface for the channel.
Application interface for external signal and detected failure value.
Linking this interface disables the
AISignalxx interface for the channel.
NOTE: xx represents the channel number in the template, from 01 to 08.
$Int8INC
The template exposes the following interfaces:
Name
Int8InC
$AISignalxx
$AINPUTSignalxx
Type/role
$Int8InData/Ref
$Int/Def
$AINPUTSignal/DO
Description
Application interface to link to the related owner template.
Application interface for analog signal value.
Application Interface for signal and detected failure value.
NOTE: xx represents the channel number in the template, from 01 to 08.
EIO0000002403 06/2017
43
Signal Conditioning and Processing
$Int8OUTO
The template exposes the following interfaces:
Name
Int8OutData
IntVarxx
AOUTPUTSignalxx
Type/role
$Int8OutData/Def
$Int/Def
$AOUTPUTSignal/PO
Description
Application interface to link to the related consumer template.
Application interface for analog signal value.
Application interface for external signal and detected failure value.
NOTE: xx represents the channel number in the template, from 01 to 08.
$Int8OUTC
The template exposes the following interfaces:
Name
Int8OutData
IntVarxx
AOUTPUTSignalxx
Type/role
$Int8OutData/Ref
$Int/Ref
$AOUTPUTSignal/DO
Description
Application interface to link to the related owner template.
Application interface for analog signal value.
Application interface for signal and detected failure value.
NOTE: xx represents the channel number in the template, from 01 to 08.
Reference Documents
Refer to Owner/Consumer more information.
(see Process Expert , Foundation Control Services User Guide) for
44
EIO0000002403 06/2017
Signal Conditioning and Processing
Using the Digital Input Owner/Consumer Templates
The following example explains how to use the digital input owner/consumer templates
( $Bool16INO / $Bool16INC ):
Step
1
2
3
4
5
Action
Instantiate $Bool16INO and $Bool16INC in the Application Explorer.
In the Links Editor, link the Bool16INO interface from the owner to the consumer.
Link BoolVar interface of $Bool16INO to a boolean variable in the Links Editor if required or else you can perform hardware mapping to actual digital input card in the Projects Explorer.
NOTE: You can link the channel only once. If you link the channel to a variable, the channel is not available anymore during hardware mapping.
Refer to the following figure.
You can link the consumer output interfaces DISignal to variables and
DInputSignal to DigitalInput instances, using the Links Editor. To link a
DigitalInput instance to a DInputSignal interface, set the Include also
Quality Signal parameter to 1.
Refer to the figures below.
Refer to the Peer to Peer Communication Through Modbus TCP (see Process
Expert, User Guide) for information on the other steps that you need to complete to implement peer to peer communication.
EIO0000002403 06/2017
45
Signal Conditioning and Processing
The following figure shows how to link to the DISignal01Var interface of an instance of Bool16INO interface of $Bool16INO to the MotorOP interface of an instance of $Motor and how to link the
$Bool16INO interface to the Bool16INC interface of an instance of $Bool16INC.
46
EIO0000002403 06/2017
Signal Conditioning and Processing
The following figure shows how to link the consumer output interface DINPUTDSignal01 to the
DINPUTSignalExt interface of an instance of $DigitalInput .
EIO0000002403 06/2017
47
Signal Conditioning and Processing
The following figure shows how include also signal quality by setting the Type parameter of the
DISignal element to true in the Instance Editor window of the Application Explorer.
48
EIO0000002403 06/2017
Signal Conditioning and Processing
Data In/Data Out Templates
Description
The Data In/Data Out facet templates allow you to exchange, by using peer to peer communication, scattered data between two or more Control projects, one being the owner, the others the consumer (see Process Expert, User Guide) . The Data Out template is assigned to the owner project and the Data In template to the consumer project. Several templates exist to communicate data of different data types between projects.
There are 2 different types of templates:
Data Out templates create a variable in the owner that can be accessed from 1 consumer.
Instantiate as many Data Out templates as there are consumers that need to access the shared data.
Data In templates create a network variable to receive data from the owner.
(see Process Expert, User Guide) in the consumer
Number of templates:
There are 11 Data Out templates and 11 corresponding Data In templates.
The 11 templates correspond to 11 different data types, which are Bool , Int , Dint , Word ,
Real , Array[1..8] of Int , Array[1..100] of Int , Array[1..125
of Int ,
Array[1..8] of Real , Array[1..50] of Real , and Array[1..62] of Real .
NOTE: You can use a Data Out template only to link directly to the functional variable input pin of any instance assigned to the consumer project. In such case, you need to create the network variable in the consumer, using the Manage Network Variables dialog box (see Process Expert,
User Guide) .
List of Templates
The following Data In/Data Out templates are available:
Identifier
$DINBool_UL
$DOUTBool_UL
$DINInt_UL
$DOUTInt_UL
$DINDInt_UL
$DOUTDInt_UL
$DINReal_UL
$DOUTReal_UL
$DINWord_UL
$DOUTWord_UL
Description
Data In template for Bool data type.
Data Out template for Bool data type.
Data In template for Int data type.
Data Out template for Int data type.
Data In template for DInt data type.
Data Out template for DInt data type.
Data In template for Real data type.
Data Out template for Real data type.
Data In template for Word data type.
Data Out template for Word data type.
EIO0000002403 06/2017
49
Signal Conditioning and Processing
Identifier
$DIN8Int_UL
$DOUT8Int_UL
$DIN99Int_UL
$DOUT99Int_UL
$DIN124Int_UL
$DOUT124Int_UL
$DIN8Real_UL
$DOUT8Real_UL
$DIN49Real_UL
$DOUT49Real_UL
$DIN62Real_UL
$DOUT62Real_UL
Description
Data In template for Array[1..8] of Int data type.
Data Out template for Array[1..8] of Int data type.
Data In template for Array[1..100] of Int data type.
Data Out template for Array[1..100] of Int data type.
Data In template for Array[1..125] of Int data type.
Data Out template for Array[1..125] of Int data type.
Data In template for Array[1..8] of Real data type.
Data Out template for Array[1..8] of Real data type.
Data In template for Array[1..50] of Real data type.
Data Out template for Array[1..50] of Real data type.
Data In template for Array[1..62] of Real data type.
Data Out template for Array[1..62] of Real data type.
Data Out Interfaces
The $DOUTBool_UL template exposes the following interfaces:
Name
IN
OUT
Type/role
$Bool/Ref
$Bool/Def
Description
Application Interface to link to any variable in the owner that is to be exchanged through the network, including pins of DFBs.
Application interface to link to the related DataIn instance, which will consume the variable or to the functional variable input pin of any other instance.
NOTE: Identical interfaces are present in the other 10 templates with the type changing according to their respective data types, which are Int , Dint , Word , Real , Array[1..8] of Int ,
Array[1..100] of Int , Array[1..125] of Int , Array[1..8] of Real , Array[1..50] of
Real , Array[1..62] of Real .
Data In Interfaces
The $DINBool_UL template exposes the following interfaces:
Name
IN
Type/role
$Bool/Ref
Description
Application interface to link to the variable from the owner. It receives the name of the network variable that is created in the owner project.
50
EIO0000002403 06/2017
Signal Conditioning and Processing
Name
OutToVar
Out
Type/role
$Bool/Ref
$Bool/Def
Description
This interface is used to provide the name of a variable of same type to which the value coming from the owner project needs to be passed on.
Otherwise, link the Out interface to one or more instances assigned to the consumer project.
Application interface to link to 1 or more input pins of a DFB in the consumer. The interface provides the name of the variable.
NOTE: Identical interfaces are present for the remaining 10 templates with the role identifiers changing according to their respective data types, which are Int , DInt , Word , Real ,
Array[1..8] of Int , Array[1..100] of Int , Array[1..125] of Int , Array[1..8] of Real , Array[1..50] of Real , and Array[1..62] of Real .
Reference Document
Refer to Move_<type> DFBs more information.
(see Process Expert , Foundation Control Services User Guide) for
Using Data In/Out Templates
The following example explains how to use the Data In/Out templates
( $DINBool_UL\$DOUTBool_UL ) to exchange a boolean variable (represented by the $Bool_UL template):
Step Action
1 In the Application Explorer, instantiate $DINBool_UL , $DOUTBool_UL , Motor , and $Bool_UL .
2 Link the OUT interface of $DOUTBool_UL to the IN interface of $DINBool_UL .
Refer to the figure below.
3 In the Links Editor, link the IN interface of $DOUTBool_UL to the MotorOP interface of $Motor .
4 Link the OutToVar interface of $DINBool_UL to $Bool_UL .
5 Refer to the Peer to Peer Communication Through Modbus TCP (see Process
Expert, User Guide) for information on the other steps that you need to complete to implement peer to peer communication.
EIO0000002403 06/2017
51
Signal Conditioning and Processing
The following figure shows how to link the OUT interface of $DOUTBool_UL to the IN interface of
$DINBool_UL .
52
EIO0000002403 06/2017
Signal Conditioning and Processing
STAHL Control Module Templates
Section 2.5
STAHL Control Module Templates
Overview.
This section describes the basic functionality of the STAHL templates and their composition.
What Is in This Section?
This section contains the following topics:
Topic
$STAHLAI8 for STAHL 8-channel Analog Input Modules
$STAHLAO8 for STAHL 8-Channel Analog Output Modules
$STAHLDI16 for STAHL 16-Channel Digital Input Modules
$STAHLDO8 for STAHL 8-Channel Digital Output Modules
$STAHLAI8HART for STAHL 8-channel Analog Input Modules with HART Signals
58
60
62
Page
54
56
EIO0000002403 06/2017
53
Signal Conditioning and Processing
$STAHLAI8 for STAHL 8-channel Analog Input Modules
General Description
The $STAHLAI8 control module template allows reading the analog input signal value and signal quality data from 8 input channels of a STAHL analog input module.
Parameters
Each instance of this template allows you to configure the offset between a range of values for the function block that it generates. If you configure offset parameter values incorrectly, a mismatch can occur between the field device and the generated function block, which leads to the exchange of incorrect information.
WARNING
LOSS OF CONTROL
1. Allow only qualified personnel to configure offset parameter values.
2. Conduct a safety analysis for the application and equipment installed.
3. Verify that the offset parameter values match the STAHL configuration values.
4. Verify the offset parameter values for each input pin of the function block that is generated by an instance of the template.
5. Validate offset parameter values under simulated conditions before deployment in the field.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Element
Name
Control
The table describes the Configuration parameters, which you can configure.
Name Type Default value Description
InputModuleDataOffset SHORT 0
InputModuleStatusOffset SHORT 0
Offset of input data in context of STAHL IS1 Remote
I/O system.
Offset of status data in context of STAHL
IS1 Remote I/O system.
54
EIO0000002403 06/2017
Signal Conditioning and Processing
Composition
The $STAHLAI8 template references composite and facet templates that provide the following services:
Control Core services.
The table describes the services that are available from the $STAHLAI8 control module and the corresponding facet, which implements the service:
Control services
Composite template
Corresponding facet template
Control service description
Associated
Supervision services
Corresponding facet template
Supervision service description
Core services
– – – – – $STAHLAI8_UL Refer to the
STAHLAI8CH DFB
(see Process Expert ,
Foundation Control
Services User Guide) .
The control module template exposes the following interfaces.
Interface identifier
VarName
AISignal01...AISignal08
Type/role
VarName/B
$Int/Def
AINPUTSignal01...AINPUT
Signal08
$AINPUTSignal/DO
Description
Receives the variable name.
Provides the analog input signal value of channels 0 to 7.
Provides the analog input signal value and diagnostic information of channels 0 to 7.
EIO0000002403 06/2017
55
Signal Conditioning and Processing
$STAHLAO8 for STAHL 8-Channel Analog Output Modules
General Description
The $STAHLAO8 control module template allows writing the analog output signal value to 8 output channels of a STAHL analog output module. It also reads the signal quality data from each channel.
Parameters
Each instance of this template allows you to configure the offset between a range of values for the function block that it generates. If you configure offset parameter values incorrectly, a mismatch can occur between the field device and the generated function block, which leads to the exchange of incorrect information.
WARNING
LOSS OF CONTROL
1. Allow only qualified personnel to configure offset parameter values.
2. Conduct a safety analysis for the application and equipment installed.
3. Verify that the offset parameter values match the STAHL configuration values.
4. Verify the offset parameter values for each input pin of the function block that is generated by an instance of the template.
5. Validate offset parameter values under simulated conditions before deployment in the field.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Element
Name
Control
Configuration
The table describes the Configuration parameters, which you can configure.
Name
OutputModuleDataOffset
Type
SHORT
Default value
0
Description
OutputModuleStatusOffset SHORT 0
Offset of output data in context of STAHL
IS1 Remote I/O system.
Offset of output status data in context of STAHL
IS1 Remote I/O system.
56
EIO0000002403 06/2017
Signal Conditioning and Processing
Composition
The $STAHLAO8 template references composite and facet templates that provide the following services:
Control Core services.
The table describes the services that are available from the $STAHLAO8 control module and the corresponding facet, which implements the service:
Control services
Composite template
Corresponding facet template
Control service description
Associated
Supervision services
Corresponding facet template
Supervision service description
Core services
– – $STAHLAO8_UL – – – Refer to the
STAHLAO8CH DFB
(see Process Expert ,
Foundation Control
Services User Guide) .
The control module template exposes the following interfaces:
Interface identifier
VarName
AOSignal01...AOSignal08
Type/role
VarName/B
$Int/Ref
AOUTPUTSignal01...AOUTPUT
Signal08
$AOUTPUTSignal/DO
Description
Variable name.
Provides the analog output signal value of channels 0 to 7.
Provides the analog output signal value and diagnostic information of channels 0 to 7.
EIO0000002403 06/2017
57
Signal Conditioning and Processing
$STAHLDI16 for STAHL 16-Channel Digital Input Modules
General Description
The $STAHLDI16 control module template allows reading the digital input signal value and signal quality data from 16 input channels of a STAHL digital input module.
Parameters
Each instance of this template allows you to configure the offset between a range of values for the function block that it generates. If you configure offset parameter values incorrectly, a mismatch can occur between the field device and the generated function block, which leads to the exchange of incorrect information.
WARNING
LOSS OF CONTROL
1. Allow only qualified personnel to configure offset parameter values.
2. Conduct a safety analysis for the application and equipment installed.
3. Verify that the offset parameter values match the STAHL configuration values.
4. Verify the offset parameter values for each input pin of the function block that is generated by an instance of the template.
5. Validate offset parameter values under simulated conditions before deployment in the field.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Element
Name
Control
Configuration
The table describes the Configuration parameters, which you can configure.
Name Type Default value Description
InputModuleDataOffset SHORT 0
InputModuleStatusOffset SHORT 0
Offset of input data in context of STAHL IS1 Remote
I/O system.
Offset of status data in context of STAHL
IS1 Remote I/O system.
58
EIO0000002403 06/2017
Signal Conditioning and Processing
Composition
The $STAHLDI16 template references composite and facet templates that provide the following services:
Control Core services.
The table describes the services that are available from the $STAHLDI16 control module and the corresponding facet, which implements the service:
Control services
Composite template
Corresponding facet template
Control service description
Associated
Supervision services
Corresponding facet template
Supervision service description
Core services
– – – – – $STAHLDI16_UL Refer to the
STAHLDI16CH DFB
(see Process Expert ,
Foundation Control
Services User Guide) .
The control module template exposes the following interfaces:
Interface identifier
VarName
DISignal01...DISignal16
Type/role
VarName/B
$Bool/Def
DINPUTSignal01...DINPUT
Signal16
$DINPUTSignal/Def
Description
Received the variable name.
Provides the digital input signal value of channels 0 to 15.
Provides the digital input signal value and diagnostic information of channels 0 to 15.
EIO0000002403 06/2017
59
Signal Conditioning and Processing
$STAHLDO8 for STAHL 8-Channel Digital Output Modules
General Description
The $STAHLDO8 control module template allows writing the digital output signal value to 8 output channels of a STAHL digital output module. It also reads the signal quality data from each channel.
Parameters
Each instance of this template allows you to configure the offset between a range of values for the function block that it generates. If you configure offset parameter values incorrectly, a mismatch can occur between the field device and the generated function block, which leads to the exchange of incorrect information.
WARNING
LOSS OF CONTROL
1. Allow only qualified personnel to configure offset parameter values.
2. Conduct a safety analysis for the application and equipment installed.
3. Verify that the offset parameter values match the STAHL configuration values.
4. Verify the offset parameter values for each input pin of the function block that is generated by an instance of the template.
5. Validate offset parameter values under simulated conditions before deployment in the field.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Element
Name
Control
Configuration
The table describes the Configuration parameters, which you can configure.
Name Type Description
OutputModuleDataOffset SHORT
Default value
0
OutputModuleStatusOffset SHORT 0
Offset of output data in context of STAHL
IS1 Remote I/O system.
Offset of output status data in context of STAHL
IS1 Remote I/O system.
60
EIO0000002403 06/2017
Signal Conditioning and Processing
Composition
The $STAHLDO8 template references composite and facet templates that provide the following services:
Control Core services.
The table describes the services that are available from the $STAHLDO8 control module and the corresponding facet, which implements the service:
Control services
Composite template
Corresponding facet template
Control service description
Associated
Supervision services
Corresponding facet template
Supervision service description
Core services
– – $STAHLDO8_UL – – – Refer to the
STAHLDO8CH DFB
(see Process Expert ,
Foundation Control
Services User Guide) .
The control module template exposes the following interfaces:
Interface identifier
VarName
DOSignal01...DOSignal08
Type/role
VarName/B
$Bool/Ref
DOUTPUTSignal01...DOUTPUT
Signal08
$DOUTPUTSignal/DO
Description
Variable name.
Provides the digital output signal value of channels 0 to 7.
Provides the digital output signal value and diagnostic information of channels 0 to 7.
EIO0000002403 06/2017
61
Signal Conditioning and Processing
$STAHLAI8HART for STAHL 8-channel Analog Input Modules with HART Signals
General Description
The $STAHLAI8HART control module template allows reading the analog input signal value and signal quality data from 8 input channels of a STAHL analog input module HART. It also processes four or eight HART signals.
Parameters
Each instance of this template allows you to configure the offset between a range of values for the function block that it generates. If you configure offset parameter values incorrectly, a mismatch can occur between the field device and the generated function block, which leads to the exchange of incorrect information.
WARNING
LOSS OF CONTROL
1. Allow only qualified personnel to configure offset parameter values.
2. Conduct a safety analysis for the application and equipment installed.
3. Verify that the offset parameter values match the STAHL configuration values.
4. Verify the offset parameter values for each input pin of the function block that is generated by an instance of the template.
5. Validate offset parameter values under simulated conditions before deployment in the field.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Element Name
Control.STAHLAI8
Control.STAHLAI8
Control.STAHLHV4 InputModuleDataOffset
Control.STAHLHV8 InputModuleDataOffset
Control
Configuration
The table describes the Configuration parameters, which you can configure.
Name
InputModuleDataOffset
Type
SHORT
InputModuleStatusOffset SHORT
SHORT
SHORT
InputModuleStatusOffset SHORT
Default value Description
0 Offset of input data in context of
STAHL IS1 Remote I/O system.
0
0
Offset of status data in context of
STAHL IS1 Remote I/O system.
Offset of input data in context of
STAHL IS1 Remote I/O system.
0
1
Offset of input data in context of
STAHL IS1 Remote I/O system.
Offset of status data in context of
STAHL IS1 Remote I/O system.
NOTE: You can only select either of the two elements.
62
EIO0000002403 06/2017
Signal Conditioning and Processing
Composition
The $STAHLAI8HART template references composite and facet templates that provide the following services:
Control Includes core services plus additional, optional services, which you can activate if needed.
The table describes the services that are available from the $STAHLHV4 control module and the corresponding facet, which implements the service:
Control services
Composite template
Corresponding facet template
Control service description
Core services
Control $STAHLAI8HART
_UC
$STAHLAI8_UL Refer to the
STAHLAI8CH DFB
(see Process Expert ,
Foundation Control
Services User
Guide) .
–
Optional services
Control $STAHLAI8HART
_UC
Associated
Supervision services
Corresponding facet template
Supervision service description
–
–
–
– $STAHLHV4_UL Refer to the
STAHLHARTVal4
DFB
(see Process Expert ,
Foundation Control
Services User
Guide) .
$STAHLHV8_UL Refer to the
STAHLHARTVal8
DFB
(see Process Expert ,
Foundation Control
Services User
Guide) .
–
– – –
The control module template exposes the following interfaces.
Interface identifier
VarName
AISignal01...AISignal08
Type/role
VarName/B
$Int/Def
AINPUTSignal01...AINPUT
Signal08
$AINPUTSignal/DO
Description
Receives the variable name.
Provides the analog input signal value of channels 0 to 7.
Provides the analog input signal value and diagnostic information of channels 0 to 7.
In addition, the control module template exposes the following interfaces, depending on the element selection.
EIO0000002403 06/2017
63
Signal Conditioning and Processing
When you select the STAHLHV4 element:
Interface identifier
HARTSignal01...HART
Signal04
Type/role
$Real/Def
When you select the STAHLHV8 element:
Interface identifier
HARTSignal01...HART
Signal08
Type/role
$Real/Def
Description
Provides the HART signal value of channels 0 to 3.
Description
Provides the HART signal value of channels 0 to 7.
64
EIO0000002403 06/2017
Using STAHL Control Module Templates
Section 2.6
Using STAHL Control Module Templates
Signal Conditioning and Processing
Example Use Case
Using an example, this section describes the steps to configure a IS1 Remote I/O system, which communicates with a Quantum controller through I/O scanning.
The implementation of this system requires both Process Expert and Unity Pro.
NOTE: This use case focuses on the configuration of the controller and the IS1 Remote
I/O system, and on the communication between the two. It does not describe the entire system engineering life cycle.
What Is in This Section?
This section contains the following topics:
Topic
Use Case Architecture
Instantiation and Application Links
Configuring Instances
Configuration
Finalizing the System
The Logical Control Participant Project
STAHL Remote I/O System Configuration
73
75
76
79
Page
66
68
69
EIO0000002403 06/2017
65
Signal Conditioning and Processing
Use Case Architecture
Physical Architecture Description
The architecture that is modeled in this use case consists of the following components:
Module/Hardware
Quantum CPU 651 50
STAHL IS1 remote I/O system CPU
DIM16
DOM8
8AIH
Particular configuration IP address
I/O scanner 192.168.10.68
– 192.168.10.30
Templates
Automatic selection through bottom-up process.
$GenericDevice (Application template)
$EGenericDeviceHW (Topological template)
$STAHLDI16
$STAHLDO8
$STAHLAI8
8AIH
8AIH
Process Expert system server/engineering station
–
–
Configured as 8-channel analog input module.
Configured as 8-channel analog output module.
Configured as 8-channel analog input module with
4 HART values.
Process Expert and Unity
Pro installed
–
–
–
–
–
–
$STAHLAO8
$STAHLAI8HART
–
NOTE: The Quantum controller, STAHL IS1 Remote I/O system, and Process Expert workstation are connected to the Ethernet control network.
66
EIO0000002403 06/2017
Architecture Representation
Signal Conditioning and Processing
EIO0000002403 06/2017
67
Signal Conditioning and Processing
Instantiation and Application Links
Instantiating Templates
Instantiate the necessary STAHL templates and the $GenericDevice application template in the Application Explorer.
NOTE: The $GenericDevice application template is used to pass the input/output data variable name to the STAHL templates through the VarName interface.
The following figure shows instances of the necessary templates in the Application Explorer:
Linking Instances
Open the instance of the $GenericDevice template in the Links Editor and connect its VarName interface to the VarName interface of each STAHL template instance. After this process, the Link status of each STAHL template then becomes Valid.
68
EIO0000002403 06/2017
Signal Conditioning and Processing
Configuring Instances
Overview
Each instance of a STAHL control module template allows you to configure the offset between a range of values for the function block that it generates. If you configure offset parameter values incorrectly, a mismatch can occur between the field device and the generated function block, which leads to the exchange of incorrect information.
WARNING
LOSS OF CONTROL
1. Allow only qualified personnel to configure offset parameter values.
2. Conduct a safety analysis for the application and equipment installed.
3. Verify that the offset parameter values match the STAHL configuration values.
4. Verify the offset parameter values for each input pin of the function block that is generated by an instance of the template.
5. Validate offset parameter values under simulated conditions before deployment in the field.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
To be able to configure the STAHL template instances in the Properties window of the Application
Explorer, you need to calculate the value of the following parameters:
InputModuleDataOffset
InputModuleStatusOffset
OutputModuleDataOffset
OutputModuleStatusOffset
In addition, for the $STAHLAI8HART template instance, you need to calculate the value of the
InputModuleDataOffset parameter for HART data.
To be able to configure the $GenericDevice template instance in the Properties window of the
Application Explorer, you need to calculate the value of the following parameters:
Input Data Length
Output Data Length
Calculating STAHL Parameter Values
Two tables are used to calculate parameter values to configure the STAHL instances in the context of STAHL IS1 Remote I/O system:
Input/output module status offset: This table shows how to calculate the values to set the module status offset parameters.
Input/output module data offset : This table shows how to calculate the values to set the module data offset parameters.
EIO0000002403 06/2017
69
Signal Conditioning and Processing
This example shows the parameters of the STAHLDI16_1 instance that you need to configure:
70
Slot
Slot 1 - DIM 16
Slot 2 - DOM 8
Slot 3 - AI 8
Slot 4 - AO 8
Slot 5 - AI 8 +
4 HART
Slot 6 - Empty
Slot 7 - Empty
Slot 8 - Empty
Slot 9 - Empty
Slot 10 - Empty
Slot 11 - Empty
Slot 12 - Empty
Slot 13 - Empty
Modbus address Data
1013
1014
1015
1016
1017
1018
1019
1020
1021
1022
1023
1024
1025
Slot 14 - Empty
Slot 15 - Empty
1026
1027
Slot 16 - Empty 1028
CPU status register 1029–1031
Status (S15–S0)
Status (S15–S0)
Status (S15–S0)
Status (S15–S0)
Status (S15–S0)
Status (S15–S0)
Status (S15–S0)
Status (S15–S0)
Status (S15–S0)
Status (S15–S0)
Status (S15–S0)
Status (S15–S0)
Status (S15–S0)
Status (S15–S0)
Status (S15–S0)
Status (S15–S0)
CPU status
9
10
11
12
7
8
5
6
13
14
15
16–18
3
4
1
2
Input/output module status offset
0
EIO0000002403 06/2017
Signal Conditioning and Processing
Slot
Slot 1 - DIM 16
Modbus address
1032
1033
Slot 2 - DOM 8 32
1034
Slot 3 - AI 8
Slot 4 - AO8
1035–1042
1043
33–40
1044
Data
Data (DI31–DI0)
Status (S15–S0)
Data (DO31–DO0)
Status (S15–S0)
Data (AI7–AI0)
Status (S7–S0)
Data AO7–AO0)
Status (S7–S0)
Input module data offset
19
20
–
–
Output module data offset
–
21
22–29
30
–
31
1
–
–
–
2–8
–
Slot 5 - AI 8 +
4 HART
1045–1052
1053
1054–1060
Data (AI7–AI0)
Status (S7–S0)
HART data
32–39
40
41–48
–
–
–
Calculating STAHL HART Parameter Values
The following figure shows the STAHLAI8HART_1 instance and the two parameters of the
STHALAI8 element, which you calculate in the same way as for the STHALAI8_1 instance:
EIO0000002403 06/2017
71
Signal Conditioning and Processing
The following figure shows the InputModuleDataOffset parameter of the STHALHV4 element, which you calculate using the module data offset table:
Calculating the GenericDevice Instance Parameter Values
Calculate the value of the parameters of the $GenericDevice application instance as follows:
Input Data Length: Total number of read/input registers in the context of STAHL IS1 remote I/O
system.
Output Data Length : Total number of write/output registers in the context of STAHL IS1 remote
I/O system.
NOTE: You have to enter the length of the input/output data variable greater than or equal to 2, to avoid detected errors in project build.
72
EIO0000002403 06/2017
Signal Conditioning and Processing
Configuration
Overview
The Quantum controller and the STAHL IS1 Remote I/O system communication through Modbus
TCP Ethernet implicit message by using the I/O scanner service of the controller. A generic
Modbus TCP I/O device entity (which is the counterpart of the generic device instance create in the Application) allows you to perform the communication mapping with the controller.
Configuring the Topology
Step
1
2
3
Action
In the Topological Explorer, create a Quantum controller entity and configure it with the I/O scanner enabled.
Configure the client memory properties with suitable values.
NOTE: The configuration of the STAHL IS1 Remote I/O system is performed outside of Process Expert.
Create a Modbus TCP I/O device entity by using the $EGenericDeviceHW template and configure its properties.
EIO0000002403 06/2017
73
Signal Conditioning and Processing
The following figure shows the properties of the generic Modbus TCP I/O device entity after configuring its parameters:
The parameters are calculated as follows in the context of the STAHL IS1 Remote I/O system:
ReadLength = Total number of read/input registers. The actual number is 49 but it is rounded
off to 50.
WriteLength = Total no of write/output registers. The actual number is 8 but it is rounded off to
10.
For detailed information on ReadAddress and WriteAddress parameters, refer to the Operating_in structions_IS1_ModTCP manual .
Connecting to the Control Network
Create an Ethernet network and make a physical connection with the controller and the generic device entities.
74
EIO0000002403 06/2017
Signal Conditioning and Processing
Finalizing the System
To complete the system engineering life cycle, complete the following steps:
Step
1
2
3
4
5
Action
Create a Control project.
Assign facets of the $GenericDevice and STAHL instances to the Control project
Generate the project.
Create an executable and proceed with:
Service mapping.
Communication mapping: To configure data exchange between the controller and the STAHL IS1 Remote I/O system system by I/O scanning.
Hardware mapping: To map the application facet of the $GenericDevice instance to the toplogical facet of the generic Modbus TCP I/O device entity.
Build the project.
The following figure shows the communication mapping:
The following figure shows the hardware mapping:
EIO0000002403 06/2017
75
Signal Conditioning and Processing
The Logical Control Participant Project
The following figures show as an example FBD section to which a facet of two STAHL instances was assigned after generating it. It contains the DFB, which is encapsulated in each facet and logical references to the generic device data variables:
76
EIO0000002403 06/2017
Signal Conditioning and Processing
This figure shows the STAHLDI16CH DFB, which is encapsulated in the facet of the STAHLDI16_1 instance (digital input template):
EIO0000002403 06/2017
77
Signal Conditioning and Processing
This figure shows the STAHLDO8CH DFB, which is encapsulated in the facet of STAHLDO8_1 instance (digital output template):
78
EIO0000002403 06/2017
Signal Conditioning and Processing
STAHL Remote I/O System Configuration
Overview
You need to do the STAHL IS1 Remote I/O system configuration on a local Unity Pro application with the help of a DTM.
This topic describes the configuration of the STAHL IS1 Remote I/O system, which contains one
Modbus TCP interface and the five I/O modules.
Two configuration scenarios can be considered:
Scenario1: The STAHL IS1 Remote I/O system is connected to the network, the digital and
analog modules are plugged on to the BusRail and an IP address is assigned to the STAHL
IS1 Remote I/O system CPU. In this case, the Unity Pro DTM Browser field bus discovery feature is used, allowing the appropriate modules to be automatically selected.
Scenario 2: The STAHL IS1 Remote I/O system is not reachable. In this case, the digital and analog I/O modules are manually selected by using the Unity Pro DTM Catalog.
Installing the STAHL IS1 Remote I/O System DTM
In any case, you need to install the STAHL IS1 Remote I/O system DTM on the PC on which you are running Unity Pro first. A DTM installs like traditional software.
You can download the STAHL IS1 Remote I/O system DTM from the STAHL http://www.rstahl.com
Updating the Unity Pro DTM Catalog
After the DTM is installed, you have to update the Unity Pro DTM catalog.
Refer to Updating the Unity Pro Hardware Catalog in the Unity Pro online help.
Configuring the STAHL IS1 Remote I/O System - Common Steps
The table describes the steps of the configuration that are common to both scenarios:
Step
1
Action
In the DTM Browser, right click the Host PC folder, and select Add to open the DTM catalog.
EIO0000002403 06/2017
79
Signal Conditioning and Processing
Step
2
Action
Select the 9441/1x-00-00 CPM Z1 24V Eth Modbus TCP/IP DTM, which corresponds to the selected CPU, and click Add DTM.
3 You can change the Alias name. In this guide IS1 is used as alias.
80
4 Double-click the IS1 instance to open the DTM.
EIO0000002403 06/2017
Step
5
Signal Conditioning and Processing
Action
Enter the selected IP address of the module in the Address field.
6 Click OK to apply the modifications and close the DTM.
EIO0000002403 06/2017
81
Signal Conditioning and Processing
Configuring the STAHL IS1 Remote I/O System - Scenario 1
For scenario 1, you have to be able to reach the IS1 module by using a ping command from the
PC on which Unity Pro is running.
The table describes the steps of the configuration that are specific to scenario 1:
Step
1
Action
In the DTM Browser, right click and select Connect.
82
NOTE: The field bus discovery service is available only when the DTM is connected to the corresponding physical device. For details refer to
DTM Browser in the Unity Pro online help.
EIO0000002403 06/2017
Step
2
Signal Conditioning and Processing
Action
Once connected, right click IS1 again and select Field bus discovery:
EIO0000002403 06/2017
83
Signal Conditioning and Processing
Step
3
Action
Select the slot number to discover. Start with the first slot, which corresponds to the first I/O module inserted in the BusRail. In this case, the D9470_3x_16_xx_DIM_16 DIM 16 STAHL module is inserted in
Slot01.
4
5
6
7
Click OK to launch the discovery. The Field bus discovery dialog box is displayed. It lists the scanned and matched devices.
From the Matched Devices pane, select the module and click the + button to add it to the selected devices pane.
Click OK to insert the module into the Unity Pro DTM Browser.
Repeat steps 2 to 6 for the remaining DTM/slot pairs.
Configuring the STAHL IS1 Remote I/O System - Scenario 2
For scenario 2, the field bus discovery feature cannot be used and you need to select the modules manually.
The table describes the steps of the configuration that are specific to scenario 2:
Step
1
2
Action
In the DTM Browser, right click IS1 and click Add… to open the DTM catalog.
Select the appropriate DTM and click Add DTM to validate. A window opens to select the slot number on the BusRail where the selected DTM is physically inserted.
84
EIO0000002403 06/2017
Step
3
4
5
Signal Conditioning and Processing
Action
Click OK to confirm the slot number. The Properties window opens. In this window, you can change the alias name.
Click OK to complete the DTM instantiation .
Repeat steps 1 to 5 for the remaining DTM slot pairs.
EIO0000002403 06/2017
85
Signal Conditioning and Processing
86
EIO0000002403 06/2017
Process Expert
Special Cards
EIO0000002403 06/2017
Special Cards
Chapter 3
Special Cards
Overview
This chapter explains the basic functionality of the special card templates and their composition.
These function blocks do not reflect any specific installation.
WARNING
LOSS OF CONTROL
Perform a Failure Mode and Effects Analysis (FMEA) of your application, and apply preventive and detective controls before implementation.
Provide a fallback state for undesired control events or sequences.
Provide separate or redundant control paths wherever required.
Supply appropriate parameters, particularly for limits.
Review the implications of transmission delays and take actions to mitigate.
Review the implications of communication link interruptions and take actions to mitigate.
Provide independent paths for control functions (for example, emergency stop, over-limit conditions, and fault conditions) according to the safety analysis and applicable codes, and regulations.
Apply local accident prevention and safety regulations and guidelines. 1
Test each implementation of this library for proper operation before placing it into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
1 For additional information, refer to NEMA ICS 1.1 (latest edition), Safety Guidelines for the
Application, Installation, and Maintenance of Solid State Control and to NEMA ICS 7.1 (latest edition), Safety Standards for Construction and Guide for Selection, Installation and Operation of
Adjustable-Speed Drive Systems or their equivalent governing your particular location.
NOTE:
1 User has to verify that Counter module has been mounted properly and standard connections are done per the manual.
2 In case of any detected error and if required, user to implement suitable diagnostic message to provide information.
EIO0000002403 06/2017
87
Special Cards
What Is in This Chapter?
This chapter contains the following topics:
Topic
Special Card Application Templates Approach
$QEHC10500 - Quantum High Speed 5-Channel Counter Module
$QEHC20200 - Quantum High Speed 2-Channel Counter Module
$QERT85410 - Quantum Expert Time Stamp Module
$QERT85420 - Quantum Expert Time Stamp Module
$TUnsignCptBmx - M340 High Speed Counter Module UnSign
$TSignCptBmx - M340 High Speed Counter Module Sign
$EPITesysUAS - Advantys Special Module for Handling TeSys U Information
$BMXEHC - M580 and X80 High Speed Counter Module
97
98
100
92
94
96
Page
89
90
91
88
EIO0000002403 06/2017
Special Cards
Special Card Application Templates Approach
Naming Convention
The following naming convention is applied for interface and template identifiers of special cards, taking the example of the high speed counter with 5 channels:
Topological template: '$Q<model>'. For instance, $Q140EHC10500 .
Mapping interface definition name: '$Q<model>Mapping'. For instance,
$Q140EHC10500Mapping .
Role names: 'HO' for the topological role and 'SO' for the project facet.
DDT Type name: 'Q<model>_DDT'. For instance, Q140EHC10500_DDT .
DFB Type name: 'Q<model>_DFB'. For instance, Q140EHC10500_DFB .
Application facet template: '$Q<model>_UL'. For instance, $Q140EHC10500_UL .
Application interface definition: '$Q<model>_DDT'. For instance, $Q140EHC10500_DDT .
EIO0000002403 06/2017
89
Special Cards
$QEHC10500 - Quantum High Speed 5-Channel Counter Module
General Description
The $QEHC10500 special card template allows you to manage the high speed counter with 5 channels that utilizes 5 equivalent, independently usable counters.
The mapping value is 12 %IW-3X and 12 %MW-4X.
Parameters
The $QEHC10500 template features no configurable parameters other than the general $System parameters ($Name, $Description, and $Area).
Composition
The special card template $QEHC10500 is composed of composite and facet templates, which provide the core Control services.
The following table describes the services that are available from the $QEHC10500 control module and the corresponding facet, which implements the service:
Control
Services
Composite
Template
Logic $QEHC10500
_UC
Corresponding
Facet Template
Control Service
Description
$QEHC10500 _UL Refer to the
Q140EHC10500_DFB
DFB
(see Process Expert ,
Foundation Control
Services User
Guide) .
Associated
Supervision
Services
–
Corresponding
Facet
Template
–
Supervision
Service
Description
–
90
EIO0000002403 06/2017
Special Cards
$QEHC20200 - Quantum High Speed 2-Channel Counter Module
General Description
The $QEHC20200 special card template allows you to manage the high speed counter with 2 channels.
This template is a two-channel module suited for high-speed counting applications up to 500 kHz or for applications that require a quadrature counter interface.
The mapping value is 6 %IW-3X and 6 %MW-4X.
Parameters
The $QEHC20200 template features no configurable parameters other than the general $System parameters ($Name, $Description, and $Area).
Composition
The special card template $QEHC20200 is composed of composite and facet templates, which provide the core Control services.
The following table describes the services that are available from the $QEHC20200 control module and the corresponding facet, which implements the service:
Control
Services
Logic
Composite
Template
$QEHC2020_
UC
Corresponding
Facet
Template
$QEHC20200_
UL
Control Service
Description
Refer to the
Q140EHC20200_DFB
DFB
(see Process Expert ,
Foundation Control
Services User Guide) .
Associated
Supervision
Services
–
Corresponding
Facet
Template
–
Supervision
Service
Description
–
EIO0000002403 06/2017
91
Special Cards
$QERT85410 - Quantum Expert Time Stamp Module
General Description
The $QERT85410 special card template allows you to manage and configure the 140ERT85410 module as a counter and discrete application. Time stamp application has to be independently managed by the user.
This template is for the intelligent 32 point input module and Counter module of Quantum controllers that allow configuration of inputs and evaluates the input signal status every 1 ms.
For every Q140ERT85410 module being used in the configuration, one instance of the
$QERT85410 application template has to be used.
Parameters
Configuration
The table describes the Configuration parameters of the template that you can configure:
Element Name
Logic
Name
ModulexFunction (where x= 1, 2, 3, 4)
Type
Enum
ModulexType (where x= 1,
2, 3, 4)
Boolean
Default value
Discrete
False
Description
Below configuration can be set for these parameters:
Discrete
Counter
NOTE: When configuring this module as a 1, 2 or 8 point with
Time tag in topology, select he
Enum value as Discrete.
False = Without quality
DISignal , the interfaces are generated.
True = With quality DISignal , the interfaces are generated.
NOTE:
Values of boolean parameters are set by using check boxes:
Selected = True
Cleared = False
92
EIO0000002403 06/2017
Special Cards
Composition
The special card template $QERT85410 is composed of composite and facet templates, which provide the core Control services.
The following table describes the services that are available from the $QERT85410 control module and the corresponding facet, which implements the service:
Control
Services
Logic
Composite
Template
–
Corresponding
Facet Template
$QERT85410_
UL
Control Service
Description
Refer to the
Q140ERT85410_DFB
DFB
(see Process Expert ,
Foundation Control
Services User Guide) .
Associated
Supervision
Services
–
Corresponding
Facet Template
–
Supervision
Service
Description
–
The control module template exposes the following interfaces:
Interface Identifier
QERT85410Mapping
CRPMapping
DISignalChannelx
(where x = 1 to 32)
Interface Model/Role Identifier
$Q140ERT85410Mapping
$CRPMapping
$Bool
Description
Mapping interface to pass the
QERT85410 module information from topology
Application interface to map to the
$CRPPortAddress if the
Q140ERT85410 module is connected on a RIO/ERIO drop
Application interface is exposed when the module is configured as a digital input
DInputChannelx x = 1 to 32)
(where $DInputSignal Application interface is exposed when the module is configured as a digital input with quality signal enabled
ERTCNTChannelx (where x = 1 to 32)
$Q140ERT85410_CNTData Application interface is exposed when the module is configured as a counter.
For a device, role identifiers other than DO, Ref, and Def link to a communication object.
A DO role identifier links to a process object.
EIO0000002403 06/2017
93
Special Cards
$QERT85420 - Quantum Expert Time Stamp Module
General Description
The $QERT85420 special card template allows you to manage and configure the 140ERT85420 module as a counter and discrete application. Time stamp application has to be independently managed by the user.
This template is for the intelligent 32 point input module and Counter module of Quantum controllers that allow configuration of inputs and evaluates the input signal status every 1 ms.
For every Q140ERT85420 module being used in the configuration, one instance of the
$QERT85420 application template has to be used.
Parameters
Configuration
The table describes the Configuration parameters of the template that you can configure:
Element Name
Logic
Name
ModulexFunction (where x= 1, 2, 3, 4)
Type
Enum
ModulexType (where x= 1,
2, 3, 4)
Boolean
Default value
Discrete
False
Description
Below configuration can be set for these parameters:
Discrete
Counter
NOTE: When configuring this module as a 1, 2 or 8 point with
Time tag in topology, select the
Enum value as Discrete.
False = Without quality
DISignal , the interfaces are generated.
True = With quality DISignal , the interfaces are generated.
NOTE:
Values of boolean parameters are set by using check boxes:
Selected = True
Cleared = False
94
EIO0000002403 06/2017
Special Cards
Composition
The special card template $QERT85420 is composed of composite and facet templates, which provide the core Control services.
The following table describes the services that are available from the $QERT85420 control module and the corresponding facet, which implements the service:
Control
Services
Logic
Composite
Template
–
Corresponding
Facet
Template
$QERT85420_
UL
Control Service
Description
Refer to the
Q140ERT85420_DFB
DFB
(see Process Expert ,
Foundation Control
Services User Guide) .
Associated
Supervision
Services
–
Corresponding
Facet Template
–
Supervision
Service
Description
–
The control module template exposes the following interfaces:
Interface Identifier
QERT85420Mapping
CRPMapping
DISignalChannelx
(where x = 1 to 32)
Interface Model/Role Identifier
$Q140ERT85420Mapping
$CRPMapping
$Bool
Description
Mapping interface to pass the
QERT85420 module information from topology
Application interface to map to the
$CRPPortAddress if the
Q140ERT85420 module is connected on a RIO/ERIO drop
Application interface is exposed when the module is configured as a digital input
DInputChannelx x = 1 to 32)
(where $DInputSignal Application interface is exposed when the module is configured as a digital input with quality signal enabled
ERTCNTChannelx (where x = 1 to 32)
$Q140ERT85420_CNTData Application interface is exposed when the module is configured as a counter.
For a device, role identifiers other than DO, Ref, and Def link to a communication object.
A DO role identifier links to a process object.
EIO0000002403 06/2017
95
Special Cards
$TUnsignCptBmx - M340 High Speed Counter Module UnSign
General Description
This template helps you to manage the data of the special cards:
A specific topological template per special card model is defined for providing the base
addresses and the mapping model, based on the retrieved data from the configuration in the topology of the system.
Each channel has equal number of mapping interface. 2 set of mapping interfaces for 2 channels are available for 2 channels and 8 set of mapping interfaces are available for 8
channels in topological template.
For each type of channel configuration, you can generate a specific DFB (signed or un signed) for data reading (from Hardware Module) and packaging.
Use this template for the T_UNSIGN_CPT_BMX IODDT depending on the mode that is configured for the counter channel. Refer to Overview tab of the counter module in the Control
Participant for details.
Parameters
The $TUnsignCptBmx template features no configurable parameters other than the general
$System parameters ($Name, $Description, and $Area).
Composition
The following table describes the services that are available from the $TUnsignCptBmx template and the corresponding facet, which implements the service:
Control
Services
$TUnsignCptBmx
–
Composite
Template
Corresponding
Facet Template
Control Service
Description
$TUnsignCptBmx
_UL
Refer to
T_UNSIGN_CPT_BMX
_DFB
(see Process Expert ,
Foundation Control
Services User Guide)
Associated
Supervision
Services
–
Corresponding
Facet
Template
–
Supervision
Service
Description
–
The control module template $T_UNSIGN_CPT_BMX_DFB exposes the following interfaces:
Interface Identifier Role Identifier
UNSIGN_CPT_BMX_DDT $T_UNSIGN_CPT_BMX_DDT / Def
Description
UNSIGN_CPT_BMX_MAP $T_UNSIGN_CPT_BMXMapping / SO Mapping interface to map to the topological template
Application interface, which contains DDT information for the user
96
EIO0000002403 06/2017
Special Cards
$TSignCptBmx - M340 High Speed Counter Module Sign
General Description
This template helps you to manage the data of the special cards:
A specific topological template per special card model is defined for providing the base
addresses and the mapping model, based on the retrieved data from the configuration in the topology of the system.
Each channel has equal number of mapping interface. 2 set of mapping interfaces for 2 channels are available for 2 channels and 8 set of mapping interfaces are available for 8
channels in topological template.
For each type of channel configuration, you can generate a specific DFB (signed or unsigned) for data reading (from Hardware Module) and packaging.
Use this template for the T_SIGN_CPT_BMX IODDT depending on the mode that is configured for the counter channel. Refer to Overview tab of the counter module in the Control Participant for details.
Parameters
The $TSignCptBmx template features no configurable parameters other than the general
$System parameters ($Name, $Description, and $Area).
Composition
The following table describes the services that are available from the $TSignCptBmx template and the corresponding facet, which implements the service:
Control
Services
$TSignCptBmx
–
Composite
Template
Corresponding
Facet Template
$TSignCptBmx_
UL
Control Service
Description
Refer to
T_SIGN_CPT_BMX_
DFB
(see Process Expert ,
Foundation Control
Services User Guide)
Associated
Supervision
Services
–
Corresponding
Facet
Template
–
Supervision
Service
Description
–
The control module template $TSignCptBmx exposes the following interfaces:
Interface Identifier
SIGN_CPT_BMX_MAP
SIGN_CPT_BMX_DDT
Role Identifier
$T_SIGN_CPT_BMXMapping / SO
$T_SIGN_CPT_BMX_DDT / Def
Description
Mapping interface to map to the topological template
Application interface, which contains DDT information for the user
EIO0000002403 06/2017
97
Special Cards
$EPITesysUAS - Advantys Special Module for Handling TeSys U Information
General Description
The $EPITesysUAS template is the device template to manage the TeSys U with EPI2145 module on an Advantys STB I/O island.
Parameters
Configuration
The table describes the Configuration parameters of the template that you can configure:
Element name
Logic
Name
ResetMode
Type
Boolean
Default value
False
Description
False = Manual reset.
True = Automatic reset.
NOTE:
Values of boolean parameters are set by using check boxes:
Selected = True
Cleared = False
Time
The table describes the Time parameters of the template that you can configure:
Element name
Logic
Name
MaxResetTime
CommandCtrlWindow
Type
Duration
Duration
Default value
00:01:00
00:00:05
Description
The maximum time between two automatic resets of the DFB.
Time the device takes to execute commands.
Composition
The following table describes the services that are available from the $EPITesysUAS control module and the corresponding facet, which implements the service:
Control
Services
Composite template
Corresponding facet template
Control Service description
Associated
Supervision
Services
Corresponding facet template
Supervision
Service description
Core Services
Logic – – – $EPITesysUAS
_UL
Refer to
EPITESYSU DFB.
(see Process Expert ,
Foundation Control
Services User Guide)
–
98
EIO0000002403 06/2017
Special Cards
Control
Services
Composite template
Corresponding facet template
Control Service description
Associated
Supervision
Services
Corresponding facet template
Supervision
Service description
Mapping Interface
$EPI2145Data/DO
The control module template $EPITesysUAS exposes the following interfaces:
Interface identifier
$DEV1S1D
Interface Model/Role identifier
$DEV1S1D/DO
Description
Links to a process object
$DEV1S2D $DEV1S2D/DO Links to a process object
For a device, role identifiers other than DO, Ref, and Def link to a communication object.
A DO role identifier links to a process object.
EIO0000002403 06/2017
99
Special Cards
$BMXEHC - M580 and X80 High Speed Counter Module
General Description
This template helps you to manage the data of the special cards:
A specific topological template per special card model is defined for providing the base
addresses and the mapping model, based on the retrieved data from the control configuration
(during the bottom-up process of the topological manager).
Each channel has equal number of mapping interface. 2 set of mapping interfaces for 2 channels are available for 2 channels and 8 set of mapping interfaces are available for 8
channels in topological template.
For each type of channel configuration, you can generate a specific DFB for data reading (from
Hardware Module) and packaging.
Parameters
The $BMXEHC template features no configurable parameters other than the general $System parameters ($Name, $Description, and $Area).
Composition
The following table describes the services that are available from the $BMXEHC template and the corresponding facet, which implements the service:
Control
Services
Composite
Template
$BMXEHC $BMXEHC
Corresponding
Facet
Template
Control Service
Description
$BMXEHC_UL Refer to BMXEHC
DFB
(see Process Expert ,
Foundation Control
Services User Guide)
Associated
Supervision
Services
–
Corresponding
Facet Template
–
Supervision
Service
Description
–
The control module template of $BMXEHC exposes the following interfaces:
Interface Identifier
CHANNEL_MAP
Role Identifier
$T_M_CPT_STD_CH_INMapping
COUNTER_CHANNEL_DDDT $T_M_CPT_STD_CH_DDDT
Description
Mapping interface to map to the topological template.
Application interface, which contains DDT information for the user.
100
EIO0000002403 06/2017
Process Expert
Variable Templates
EIO0000002403 06/2017
Variable Templates
Chapter 4
Variable Templates
What Is in This Chapter?
This chapter contains the following topics:
Topic
Elementary Variable Templates
Array Variable Templates
Reference Data Type Variable Templates
Page
102
105
107
EIO0000002403 06/2017
101
Variable Templates
Elementary Variable Templates
Overview
These templates generate an elementary variable of the corresponding data type of the Control
Participant.
The name of the variable is the identifier of the instance.
Parameters
The table describes the Configuration parameters of elementary variable templates that you can configure.
Template
All templates except
$Range_UL
( see page 16 )
Name
Address
Type (1)
String
Default Value
Blank
Description/comment
Memory address of the variable
$Bool_UL
$Byte_UL
$Date_UL
$Time_UL
$DInt_UL
$DT_UL
$DWord_UL
$EBool_UL
$Int_UL
$Real_UL
$String_UL
$UDInt_UL
$UInt_UL
$Word_UL
InitValue Boolean
UnsignedByte
Data
Duration
Integer
DateTime
UnsignedInt
Boolean
Short
Float
String
UnsignedInt
UnsignedShort
UnsignedShort
0
0
“”
0
0
0.0
False (check box cleared)
0
1/1/1900
00:00:00
–
–
Format: dd/mm/yyyy
Valid range for year:
1990 to 2099
Format: dd.hh:mm:ss.mss
0
01/01/1900 00:00:00 Format: dd/mm/yyyy
Valid range for year:
1990 to 2099
0
False (check box cleared)
–
(1) Process Expert converts the data types automatically to Control Participant supported types
(see Process Expert, Control Participant Services, User Guide) .
102
EIO0000002403 06/2017
Variable Templates
Template
$Range_UL
Name
Low
High
EU
Format
Type (1)
Float
Float
String
String
Default Value
0.0
100.0
%
###.#EU
Description/comment
Low end of the range measured in engineering units.
High end of the range measured in engineering units.
Engineering units.
Format that is used to display the process value.
(1) Process Expert converts the data types automatically to Control Participant supported types
(see Process Expert, Control Participant Services, User Guide) .
NOTE: $TOD_UL only has the Address parameter.
Interfaces
The elementary variable templates shows the following application interfaces:
Template
$Bool_UL
$Byte_UL
$Date_UL
$Time_UL
$DInt_UL
$DT_UL
$DWord_UL
$EBool_UL
$Int_UL
$Real_UL
$String_UL
$UDInt_UL
$UInt_UL
$Word_UL
$TOD_UL
EBool
Int
Real
String
UDInt
UInt
Word
TOD
Interface identifier Type/role
Bool $Bool/Def
Byte
Date
$Byte/Def
$Date/Def
Time
Dint
DT
DWord
$Time/Def
$DInt/Def
$DT/Def
$DWord/Def
$EBool/Def
$Int/Def
$Real/Def
$String/Def
$UDInt/Def
$UInt/Def
$Word/Def
$TOP/Def
Description
Provides the name of the variable, which is the instance identifier.
EIO0000002403 06/2017
103
Variable Templates
Template
$Range
Interface identifier
AnalogRange
Type/role
$Range/Def
Description
Provides the following data:
Name of the variable, which is the
instance identifier.
The value of the Configuration parameters:
Low
High
EU
Format
104
EIO0000002403 06/2017
Variable Templates
Array Variable Templates
Overview
These templates generate a 1-dimensional array of the corresponding data type of the Control
Participant.
The name of the variable is the identifier of the instance.
NOTE: The $AryItem_UC template allows writing/reading a data item in a 1-dimensional array by providing a string which refers to a specific element of the array (for example, MyArray[2]).
Parameters
The table describes the Configuration parameters of array variable templates that you can configure.
Template
All templates
All templates except
$AryString_UL
( see page 16 )
$AryItem_UC
Name
Address
FirstItem
LastItem
$AryString_UL FirstItem
LastItem
Item_1
Type
(1)
String
Integer
Integer
Integer
Integer
Integer
Default Value Description/comment
Blank
1
10
1
16
Blank
Memory address of the variable
Starting index value of the array
Ending index value of the array
Starting index value of the array
Ending index value of the array
Defines the index of the element in the array to be accessed.
For example, 2 defines the second element of
ARRAY[1...10] of BOOL.
(1)
Process Expert converts the data types automatically to Control Participant supported types
(see Process Expert, Control Participant Services, User Guide) .
EIO0000002403 06/2017
105
Variable Templates
Interfaces
The array variable templates shows the following application interfaces:
Template
$AryBool_UL
$AryByte_UL
$AryDint_UL
$AryDT_UL
$AryDWord_UL
$AryEBool_UL
$AryInt_UL
Interface identifier
ArrayBool
ArrayByte
ArrayDInt
ArrayDT
ArrayDWord
ArrayEBool
ArrayInt
$AryItem_UC
$AryReal_UL
ArrayItem
ArrayReal
$AryString_UL ArrayString
$AryTime_UL ArrayTime
$AryTOD_UL
$AryUDInt_UL
$AryUInt_UL
$AryWord_UL
$AryItem_UC
ArrayTOD
ArrayUDInt
ArrayUInt
ArrayWord
Array_DataType_1 where DataType corresponds to the type of existing array templates
For example,
Array_Bool_1
Array_DataTypeValue_1 where DataType corresponds to the type of existing array templates
For example,
Array_BoolValue_1
Type/role
$Array_Bool/Def
$Array_Byte/Def
$Array_DInt/Def
$Array_DT/Def
$Array_DWord/Def
$Array_EBool/Def
$Array_Int/Def
$Array_Item/Def
$Array_Real/Def
$Array_String/Def
$Array_Time/Def
$Array_TOD/Def
$Array_UDInt/Def
$Array_UInt/Def
$Array_Word/Def
$Array_DataType/Ref where DataType corresponds to the type of existing array templates
For example,
Array_Bool/Ref
$Array_DataType/Def where DataType corresponds to the type of existing array templates
For example,
$Bool/Def
Description
Provides the name of the variable, which is the instance identifier.
Receives the name of the array from which a data item is to be read or written.
Linking an interface of type Ref enables the corresponding interface of type Def.
Provides the name of the array whose interface is connected to a
Ref interface of the corresponding type concatenated with the element index configured in the instance.
For example, AryBool_UL_1[2.
106
EIO0000002403 06/2017
Variable Templates
Reference Data Type Variable Templates
Overview
These templates generate an elementary variable of reference data type of the Control Participant.
The name of the variable is the identifier of the instance.
Parameters
The table describes the Configuration parameters (Name) of reference data type variable templates that you can configure.
Template
All templates
( see page 16 )
Name
InitValue
Type
String
Default Value Description/comment
Blank Memory address of the variable
(Value attribute of the variable in the
Control Participant)
Example 1: For InitValue =
%MW100, Value = REF(%MW100)
Example 2: For InitValue =
MOD_DIS_16_2.DIS_CH_OUT[15].
VALUE, Value =
REF(MOD_DIS_16_2.DIS_CH_OU
T[15].VALUE) where
MOD_DIS_16_2 is a device DDT variable.
Example 3: For InitValue = blank,
Value = blank
Interfaces
The reference data type variable templates shows the following application interfaces:
Interface identifier
DATATYPE where DATATYPE corresponds to the type of existing reference data type variable templates
For example, WORD
Type/role
$DataType/Def where DataType corresponds to the type of existing reference data type variable templates
For example, $Word/Def
Description
Provides the name of the dereferenced variable by using the caret postfix (^).
For example, REF_TO_WORD_UL_1^
EIO0000002403 06/2017
107
Variable Templates
108
EIO0000002403 06/2017
Process Expert
Using HART Analog I/O Signals
EIO0000002403 06/2017
Using HART Analog I/O Signals
Chapter 5
Using HART Analog I/O Signals
What Is in This Chapter?
This chapter contains the following topics:
Topic
Getting Started
Configuration Stage (Topology Explorer)
Instantiation Stage (Application Explorer)
Project Definition Stage (Project Explorer)
Deployment Stage (Topology Explorer)
Related Information
Page
110
111
116
118
119
121
EIO0000002403 06/2017
109
Using HART Analog I/O Signals
Getting Started
Overview
The Hardware Mapping Editor of Process Expert allows you to map only 1 signal per channel of a supported HART analog I/O module, which is configured in the topology. The HART module is acting as a regular I/O module and the signal corresponds to the Primary Variable (PV). The other
HART signals, for example, Secondary Variable (SV), Tertiary Variable (TV), and/or Quarternary
Variable (QV), and so on are not available.
Additional steps are required to be able to use all HART signals (including PV) coming from supported HART analog I/O modules by allocating manually state RAM addresses to variables representing these HART signals.
The manual configuration varies depending on the controller platform. It involves importing HART application templates and using the Topology Explorer, the Application Explorer, and the Project
Explorer of the engineering client.
Refer to the Related Information section for a description of limitations and other information related to the use of HART signals by implementing this procedure ( see page 121 ) .
NOTE: For instructions how to configure HART modules in the topology, refer to the Process
Expert User Guide (see Process Expert, User Guide) .
Prerequisites
One or more HART analog I/O module exists in the Topology Explorer in a controller of the
M580 or Quantum platform, which contains a NOC communication module.
The corresponding HART I/O module device type manager (DTM) is added and configured
(except for the configuration of process data, which is described in this procedure). Refer to the
Process Expert Control Participant Services User Guide (see Process Expert, Control
Participant Services, User Guide) .
The necessary HART device DTMs are installed in Process Expert. This is required to be able to configure or monitor HART devices. If the devices are already configured, the installation of device DTMs is not necessary. (Contact vendor to obtain the device DTM if necessary).
110
EIO0000002403 06/2017
Using HART Analog I/O Signals
Configuration Stage (Topology Explorer)
Configuring HART DTM Process Data
1. Right-click the controller entity containing the HART analog I/O module and select Configure.
2. Open the DTM of the HART analog I/O module. In the Process Data section of the DTM, select the variables (primary, secondary, tertiary, and so on) that you need to use for each channel that is enabled.
Allocating State RAM Addresses
Click the button in the toolbar of the Participant window. This builds the application and allocates state RAM addresses to the DDDT variables created through the HART module DTM based on the enabled channels and their process data configuration.
EIO0000002403 06/2017
111
Using HART Analog I/O Signals
The following example shows the configuration of a controller of the M580 platform and the DDDT variable that was created when adding the HART analog input module DTM. Topological addresses are not assigned automatically to the DDDT structure. Some additional programming is required ( see page 113 ) .
The following example shows the configuration of a controller of the Quantum platform and the
DDDT variable that was created when adding the HART analog input module DTM. Topological addresses are automatically assigned to the DDDT structure.
112
EIO0000002403 06/2017
Using HART Analog I/O Signals
Transferring to FDR Server
Verify that the HART module is available and transfer of FDR is possible.
Adding Code for Controllers of the M580 Platform
If the controller containing the HART analog I/O module is of the M580 platform, you need to:
1. Add a new section (FBD or ST) in the Program section that you can see in the Participant window opened in the Topology Explorer. Give it a special name, such as DoNotDelete or
DoNotUpdate so that you can differentiate it easily from sections created in the Project Explorer.
2. Add code to read the configured HART DTM device DDT variable length by using the SIZEOF function block. This is because the DDDT variable length varies based on the configuration of channels and their process data.
Assign to the IN input of the SIZEOF function block, the
BME_AHI_0812.Inputs
).
Inputs structure of the HART module
DDDT variable (For example, in the BMEAHI0812 HART analog input module, the name is by default
3. Create a variable of type ARRAY OF REAL with, at least, the length as determined by the function SIZEOF divided by 4, and allocate the variable to state RAM memory address (for example,%MW200).
NOTE: When allocating the variable to state RAM, avoid overlapping of the memory address with, for example, memory used in I/O scanner lines that are created for communication with other devices or controllers.
NOTE: If you modify the number of enabled channels and/or the configuration of process data, the size of the corresponding DDDT variable changes. In such case, you need to modify the size of the array assigning the topological address to the variable, avoid overlapping of the memory address with, for example, I/O scanner lines that are created for communication with other devices or controllers.
EIO0000002403 06/2017
113
Using HART Analog I/O Signals
4. Add an instance of the EXTRACT function block, which allows copying the HART device DTM
DDDT variable to an array of equivalent length.
Link the OUT pin of the SIZEOF function block to the CPY_NELEM input.
Assign to the SRC input of the EXTRACT function block, the same structure as you have assigned to the IN input of the SIZEOF function block.
Assign to the DST output of the EXTRACT function block, the variable of type ARRAY OF REAL that you have created previously.
The following example shows the code of the DoNotDelete section, which corresponds to steps
2 to 4. The size of the HART module DDDT variable is shown as 140. The variable of type
ARRAY[0..34] OF REAL created in step 3 is named Output.
114
EIO0000002403 06/2017
Using HART Analog I/O Signals
5. Perform steps 2 to 4 for each HART input (AHI) and output (AHO) module.
The following figure shows the structure of the Output variable. It allows you to determine the state RAM address of the HART signals and the various status signals that you have configured by comparing this structure with the structure of the HART module DDDT that is shown
( see page 113 ) (for a controller of the M580 platform).
From this example, you can determine that the address of the G_ModuleStatus variable is
%MW200 (it corresponds to address of Output(0)) and consequently, the address of the
P_Channel0_PV variable is %MW206 (it corresponds to address of Output(3)).
EIO0000002403 06/2017
115
Using HART Analog I/O Signals
Instantiation Stage (Application Explorer)
Importing HART Application Templates
Import the AISignalHART_x.sbk
template export file provided (where x is a 3-digit version index).
It contains the $AISignalHART_UL application facet template.
The instances of the $AISignalHART_UL allow mapping the configured HART signals to state RAM addresses.
NOTE: For HART analog output modules, you need to instantiate, in addition, the $AOSignal_UL facet or $AnalogOuput composite template to send the signal (PV) to the HART device. Map the interface of the facet by using the Hardware Mapping Editor. Instances of the $AISignal-
HART_UL template allow reading data from HART devices (for example, the % open position feedback).
Configuring HART Application Template Instances
Create as many instances of it as you have enabled HART signals for each channel of a module.
For example, if you have enabled PV and SV for channel 0 and PV, SV, and TV for channel 1, you need to create 5 instances of the template. Each instance creates one variable corresponding to one signal of a channel of a HART analog I/O module. Other variables and/or a DFB instance are created depending on the configuration of the instance.
NOTE: You need to select the Facets filter in the Browser pane of the Application Explorer to see the template.
Edit each instance and configure its parameters ( see page 35 ) .
The following examples show the configuration of the AI101_PV and AI101_SV instances, which represent the Primary and Secondary variables respectively of channel 0 of a HART analog input module. The topological addresses are taken from the Output structure ( see page 113 ) .
116
EIO0000002403 06/2017
Using HART Analog I/O Signals
EIO0000002403 06/2017
117
Using HART Analog I/O Signals
Project Definition Stage (Project Explorer)
Assigning Facets and Building the Control Project
1. Assign the instances to a control project and generate it.
2. For instances of the $AISignalHART_UL template, no more hardware mapping is required.
3. Build the Control project. If you had already built the Control project a first time, use the Build
All command.
Verifying the Built Control Project
Open the built Control project by using the Open Built Project command and verify that:
1. For projects mapped to a controller of the M580 platform, the section that you have created in the configuration (refer to step 5 of Configuration Stage) is present and in first position in the
Structural View of the Project Browser.
2. The HART module DDDT variable and ARRAY[0..x] of REAL type variable (M580 only) created in the topological configuration are available and addresses are as configured.
3. The variables created in the logical Control project by the assigned instances of the $AISignal -
HART_UL template have the correct state RAM addresses.
The following example shows the Output controllers of the M580 platform only (
variable (created a step in Configuration Stage, for see page 113 ) ), the three variables created by the AI101_PV instance (signal, detected error in channel, and module status), and the variable created by the
AI101_SV, AI101_TV, and AI101_QV instances respectively.
118
EIO0000002403 06/2017
Using HART Analog I/O Signals
Deployment Stage (Topology Explorer)
Deploying the Built Control Project
1. Deploy the built Control project to the controller.
2. You can use the Refine Online command to verify the logic and values online.
The following example shows the values of parameters of the function block that is created when you select the Type parameter of the instance of the $AISignalHART_UL template.
EIO0000002403 06/2017
119
Using HART Analog I/O Signals
The following example shows the values of the variables representing the signals of the HART analog input module in the animation table of the Control Participant::
When you close the online refinement, you may be prompted to perform an update of the Control project. If you do so, do not select the checkbox of the section that you have created in the configuration ( see page 113
( see page 121 ) .
) . Refer to Related Information, Topology topic for details
120
EIO0000002403 06/2017
Using HART Analog I/O Signals
Related Information
Modifying an Existing System
If you are already using a HART analog I/O module in your system and are accessing PV by using an instance of $AnalogInput1 or $AISignal_UL through the hardware mapping, you can access the other HART signals by using the procedure described in this document. You do not need to modify the way you have implemented PV. Both methods can coexist in the same system.
Topology
State RAM memory consumption may increase based on the number of HART analog I/O modules used and channels enabled, which are implemented by using this procedure.
When you update the logical Control project, do not select the checkbox of the section that you have created in the configuration (refer to step 5 of Configuration Stage). Selecting it adds the section to the logical Control project but causes the build diagnostic indicator to appear on the
Control project in the Project Explorer. This is because the DDDT variables used in the section come from the configuration of the topology and do not exist in the logical Control project. If you have added the section to the logical Control project, delete the section from the logical Control project to turn off the indicator.
Control Projects
When you build the logical Control project, the section that you have added in the configuration
(refer to step 5 of Configuration Stage) appears in first position in the Structural View of the
Control Participant. For HART analog output modules, this results in a delay of one controller execution cycle because the output data will be calculated in cycle n and be sent only in cycle n+1 when the code of the first section is executed again.
If you configure HART signals in an existing topology or modify the configuration of these signals, you need to use the Build All command to apply the configuration or modifications to it.
The code that you add in the section that you have created in the configuration cannot be deployed to the Unity Pro simulator.
Because the section that you have added in the configuration of the controller is part of the topology, the code therein is available in any executable that is mapped to the controller once you build it. In such case, if you do not need this section, you can delete it during online refinement after deploying the built Control project to another controller.
Starting with Process Expert 4.1 hardware abstraction layer (HAL) 2.0 templates use the
Reference data type. As a result, the addresses generated for these variables appear in the
Value field of a variable (not the Address field) and are shown as REF(%MW<i>).
EIO0000002403 06/2017
121
Using HART Analog I/O Signals
122
EIO0000002403 06/2017
Process Expert
Index
EIO0000002403 06/2017
Index
Symbols
$AHISignal_UL template description,
$AISignal_UL template description,
$AOSignal_UL template description,
$CounterSignal_UL template description,
$DISignal_UL template description,
$DOSignal_UL template description,
$Q140ERT85410 template description,
$Q140ERT85420 template description,
$Q1EHC10500 template description,
$QEHC20200 template description,
$STAHLAI8 template description,
$STAHLAI8HART template description,
$STAHLAO8 template description,
$STAHLDI16 template description,
$STAHLDO8 template description,
$TSDInput template description,
34
22
25
27
29
31
92
94
90
91
54
62
56
58
60
36
D
device templates special card application templates ap proach, 89
EIO0000002403 06/2017
F
foundation application templates list of templates, 16
G
General Purpose library location of process control module tem plates, 18
H
hardware abstraction layer templates
$AHISignal_UL,
$AISignal_UL,
$AOSignal_UL,
DOSignal_UL,
HART
25
$CounterSignal_UL,
$DISignal_UL,
27 mapping input signals to STB modules,
34
22
34
29
31
K
Krohne field instruments mapping input signals to STB modules,
34
P
process templates control module template location, 18
S
setpoint management
$TSDInput, 36
123
Index signals
$AISignal_UL template,
$DISignal_UL template,
$DOSignal_UL template, special cards
$Q140ERT85410,
62
54
90
91
56
58
60
92
94
65
25
29
31
27
$Q140ERT85420,
$QEHC10500,
$QEHC20200,
STAHL
$STAHLAI8,
$STAHLAI8HART with 4 or 8 HART sig nals,
$STAHLAO8,
$STAHLDI16,
$STAHLDO8, example use case,
22