Schneider Electric Magelis™ Range Graphic XBT-F/TXBT-F Instruction Sheet
Reklaam
Reklaam
User guide
February
99
Software
XBT-L100_ ver 3.3
Magelis range
Graphic XBT-F / TXBT-F
Instruction Manual
WARNING
UNINTENTIONAL EQUIPMENT OPERATION
• The application of this product requires expertise in the design and programming of control systems. Only persons with such expertise should be allowed to program, install, alter, and apply this product.
• XBT-L100_U ver 3.3 and later software should be used only with hardware date coded 9825 and later or firmware V2.1.15 or greater.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
The date code is located on the back of the keypad on the nameplate following the word "France".
Graphic Magelis i
ii Graphic Magelis
Contents
Man/machine dialog, application structure, application pages, alarm pages, help pages, control system, function keys, PLC/terminal dialog, starter kit.
Application specifications, development with XBT-L1000 software, saving the application, transferring the application to the terminal.
Terminal keys and indicator lights, operating principle, page display, entering and modifying fields, alarms, alarm log, process control, key locking, printing, terminal configuration.
PLC and terminal communications dialog principle, dialog tables, dialog cycle.
Application specifications, page template architecture, creating the applications using XBT-L1000, transferring the application to the terminal, running the application.
Appendices
Introduction
1
Application Development
2
Operating the Terminal
3
PLC and Terminal
Communications Dialog
4
Application Development
Example
5
XBT-F Specifications
A
System Messages
B iii
Index
Graphic Magelis
iv Graphic Magelis
Graphic Magelis
Chapter 1
Introduction
1 - 1
1
1 - 2 Graphic Magelis
Contents
This chapter includes the following sections:
1.1
Man/machine communications dialog using Graphic Magelis terminals .................................... 1-5
1.2
Structure of the applications ........................................ 1-11
1.3
Application pages .......................................................... 1-15
1.3.1
Composition of the application pages ......... 1-15
1.3.2
1.3.3
Accessing the application pages .................. 1-18
Displaying the alarm list ................................ 1-19
1.3.4
1.3.5
Getting help ..................................................... 1-19
Recipe pages ................................................... 1-20
1.4
Alarm pages .................................................................... 1-21
1.5
Help pages ...................................................................... 1-25
1.6
Form pages ..................................................................... 1-26
1.7
Managing the control system ....................................... 1-26
1.8
Static and dynamic function keys ................................ 1-28
1.9
Variable adjustment on the TXBT ................................. 1-29
1.10 PLC/terminal communication dialog ............................ 1-30
1.11 Loading of extension tasks when transferring the application .......................................... 1-33
1.12 Starter kit for the Graphic Magelis application ...................................................................... 1-33
1
Graphic Magelis 1 - 3
Man/machine dialog
1 - 4 Graphic Magelis
Man/machine dialog
1.1
Man/machine communications dialog using Graphic Magelis terminals
The main functions of the terminals are to:
• Display data from the control system
• Modify the control system parameters
• Control the system using discrete commands.
Various terminals are available:
Figure 1-1: XBT-F 5"
XBT-F 5"
• Terminals with LCD screen.
• STN Monochrome,
320x240 pixels.
• 10 static function keys.
• 8 dynamic function keys.
• System and alphanumeric keys.
• Downloadable protocols.
• Printer output (Figure 1-1).
XBT-F 10"
• Terminals with LCD screen.
• STN Monochrome (9.5") or
TFT color (10.4").
• 640x480 pixels.
• 12 static function keys.
• 10 dynamic function keys.
• System and alphanumeric keys.
• Downloadable protocols.
• Printer output
(Figure 1-2 and 1-3).
Figure 1-2: XBT-F 10"
1
Graphic Magelis 1 - 5
1 - 6
Man/machine dialog
TXBT Terminals
• Terminals with LCD screen
(640x480 pixels) either monochrome
(9.5" screen: TXBT-F023) or color
(10.4" screen: TXBT-F024)
• 1.6 Gb hard disk
• Windows 95
• 12 static function keys
• 10 dynamic function keys
• System and alphanumeric keys
• Pointing device (except TXBT-F034)
• Downloadable protocols
• Printer output
• External keyboard connection
• Slots for 2 ISA bus cards
Figure 1-3: TXBT-F 10"
The functions possible from the home screen (Figure 1-4) (using the dynamic keys) are:
• Startup of Graphic Magelis applications
• Access to Windows 95
• Closure of home screen
• Setup: terminal parameters setup
For more information refer to the TXBT documentation.
Figure 1-4: Application home screen
Customizable screen background
Graphic Magelis
Man/machine dialog
Figure 1-5: Man/Machine Dialog with Graphic Magelis Terminal
Displays data from the control system
Annunciates control system faults
Dynamic function keys for:
• Operator input to the control system
• Navigating between the various dialog pages
Communication status indicator light
Key stroke enabled indicator light
Static function keys that can be used for:
• Operator input to the control system
• Navigating between the various dialog pages
Removable
PCMCIA card including all information necessary for running the terminal
1
Records control system faults with time-stamping (alarms, groups of alarms)
Modifies control system parameters Terminal programming with XBT-L1000
Alarms, terminal references and printout forms printing
Graphic Magelis
Communication with the control system:
Modicon, Telémecanique,
AEG, April, Allen Bradley,
Omron, Siemens ... etc. PLCs
1 - 7
1 - 8
Man/machine dialog
Touchscreen terminals
The main functions of the touchscreen terminals are to:
• Display data from the control system,
• Modify the control system parameters,
• Control the system using discrete commands.
Various terminals are available:
Touchscreen XBT-F 5"
Figure 1-6: Touchscreen
XBT-F 5"
• Resistive matrix touchscreen pad.
• 6x8 touchscreen zones.
• Terminals with LCD screen.
• STN monochrome, 320x240 pixels.
• Downloadable protocols.
• Printer output.
Touchscreen XBT-F 10"
• Resistive matrix touchscreen pad.
• 10x13 touch screen zones.
• Terminals with
LCD screen.
• TFT color (10.4" screen)
• 640x480 pixels.
• Downloadable protocols.
• Printer output.
Figure 1-7: Touchscreen
XBT-F 10"
Graphic Magelis
Man/machine dialog
Figure 1-8: Man/Machine Dialog with Graphic Magelis
Touchscreen Terminal
Display of data from the control system.
Notification of control system faults
Touchscreen zones for:
• navigating around the various dialog pages,
• controlling the control system
Indicator light communication control
Indicator light alarm
Indicator light touchscreen pad pressed
Removable
PCMCIA card including all information necessary for running the terminal
To record control system faults with timestamping
(alarms, groups of alarms)
To modify control system parameters
Terminal programming with XBT-L1000
1
Alarms, terminal references and printout forms printing
Graphic Magelis
Communication with the control system:
Schneider, Allen Bradley,
Modicon, Omron, Siemens, ... PLCs
1 - 9
Man/machine dialog
1 - 10
The following application examples may be configured with the
Graphic Magelis:
Production monitoring
R2 R1
R3
Automatic operation
Start hydraulic unit
End of lift of manipulator
Rotation of grip to right
R4
R5 R6
R8 R7
Preventive maintenance
R1
R3
Counting with indication if threshold exceeded:
Number of drillings 3137
Tool change at 4000
R5
R2
R4
R6
R8 R7
Process control
R1
R3
R5
Commands
Pressurizing P
Start Cycle SC
Parameter modification
Level 1 : 556
Limit n12 : 725
R7
R2
R8
Graphic Magelis
Magelis applications
1.2
Structure of the applications
An application represents the entire dialog between the user and the automated process. An application is developed based on the user requirements:
1
User Requirement Control System Interface
• Process control
• Production monitoring
• Preventive maintenance
Operator Concerns
• User interface
• Level of involvement
Developer Concerns
• Program structure
• Data structure
• Debugging
• Updating
These characteristics determine that your application must be structured. An application consists of a series of pages, which form a tree structure as shown in the following example:
Automatic operation
R1 Automatic operation
R3
Start hydraulic unit
R5
End of lift of manipulator
The application is organized into menus and submenus.
End of lift of manipulator
Start hydraulic unit
Graphic Magelis 1 - 11
Magelis applications
1 - 12
Each page may include the following:
• Static alphanumeric text
• Variable fields used to:
Display the values indicating control system status
(status of a bit, a single or double word, a floating point word, or an ASCII string); or
Enter parameters for operating the control system
(modification of bits, single or double words, floating point words, or an ASCII string).
The display format can be binary, decimal, hexadecimal, or alphanumeric.
• Static dynamic graphic objects
• Dynamic function keys objects allowing the user to display other pages directly, or command the process, or start a
Windows 95 application (TXBT).
• A page is identified by a number, and a name (optional).
• Pages may be accessed by pressing the keypad function keys or the control system.
• The arrow keys are used to navigate within a page.
Navigation consists of selecting various input fields.
• Access to pages may be password protected.
Creating pages
The various elements making up pages are defined using the
XBT-L1000 programming software, and then saved in the terminal.
• Application pages may be accessed by pressing a configured function key or using the control system variable to initiate a page change.
Graphic Magelis
Magelis applications
The development page has the same dimensions as the screen in the graphics display of the configuring software. This means that the appearance of the page being developed is exactly the same as the page being run on the XBT (Figure 1-9).
Figure 1-9: Development Page
1
Counting
Number of drillings 3137
Change tool at 4000
Page displayed by
XBT-L1000 on the development PC.
Counting
Number of drillings
Change tool at
3137
4000
Graphic Magelis 1 - 13
Magelis applications
1 - 14
Page types
An application typically includes several types of pages.
• Template pages: The designer has page templates at his disposal. These are background pages containing text and static graphic objects that can be used as a starting point for application page development. Four types of page templates can be configured:
Application template page
Alarm template page
Help template page
Recipe template page
From the basic models, the application developer can create new models using the default basic models.
During editing of the application, alarm, or help pages, the objects of the template will appear to be greyed out and cannot be modified. General rules to follow when configuring an application:
One and only one template is associated with each page.
A dialog application may contain several templates.
Any given template can be associated with several different pages.
A template type (application/alarm/help template) is associated with a page type (application/alarm/help page).
For example, an application template is used to start an application page.
• Application pages: Used to monitor system status, control, command, and control system parameter modification
(see Section 1.3).
• Alarm pages: Used to display control system fault and the corrective actions indicating with display priority
(see Section 1.4).
• Help pages: Used to display information associated with an application or alarm page (see Section 1.5).
• Form pages: Used to print out printout forms (see section 6).
NOTE: Form pages cannot be displayed on the terminal. They are used for printing only.
• System pages: Used to to configure the terminal (language, date, printer link, etc.).
Graphic Magelis
Application pages
1.3
Application pages
The application pages represent the basic dialog architecture and are used to:
• Monitor the control system
• Perform operations on the control system
• Maintain the control system
Structuring the pages
It is advisable to organize the application pages so that they reflect the various stages of the control process. The XBT-L1000 software allows you to do this.
1
1.3.1
Composition of the application pages
An application page consists of 3 parts:
• Application region (Figure 1-10)
• Status line,
• Alarm strip
Figure 1-10: Application Page
Application region
Industrial Bakery Co.
Dough baking
Temperature Temperature monitoring
Status line
Alarm strip
1 - 15 Graphic Magelis
Application pages
The application region may contain the following:
• Static alphanumeric texts
• Variable fields
• Static graphic objects
• Dynamic graphic objects
• Dynamic function keys
• Optional alarm bar showing the last activated alarm
Details concerning variable fields and dynamic graphic objects
When creating an application with XBT-L1000, PLC variables are associated with the variable fields and the dynamic graphic objects.
For XBT-F
Whatever the protocol, the accessible variables are single words, double words, floating words, and word bits.
For TXBT
In the case of XWAY protocols, the accessible variables are:
• Single words, double words, floating words, word bits
• Local and remote input/output bit
• System bit
• Step bit
• Step macro bit
• Step input step bit
• Step macro output step bit
In the case of a protocol other than XWAY, the accessible variables are single words, double words, floating words, and word bits.
1 - 16 Graphic Magelis
Application pages
Status line
This status line appears by default in the page template and may be optional. When it is present, the status line is always on the last line of the display. It provides the user with contextual information and identifiers (Figure 1-11).
Figure 1-11: Status Line
1
Current level of access right
Page type and number
System information messages
Current date and time
Alarm strip
The alarm strip is displayed by default in the page model. It can be moved or deleted. It mainly displays the message of the last alarm displayed (Figure 1-12).
Figure 1-12: Alarm strip
Appearance date and time
Name of the alarm
Number of the bit at the origin
Code for appearance (ON)
Acknowledgment (ACK)
Disappearance without acknowledgment (OFF) of alarm triggering
Absent: no alarm or alarm acknowledged (ACK)
Steady red: alarm at state OFF
Flashing red: alarm at state ON
TXBT screen printout
On the TXBTs, the SHIFT + PRINT keys enable you to print out screen hardcopies.
Graphic Magelis 1 - 17
Application pages
1.3.2
Accessing the application pages
The application pages can be accessed by:
• Pressing a dynamic function key (when configured)
• Pressing a static function key (when configured)
• Selecting a page from the list of pages
• Selecting the page number
• A command from the PLC
Depending on the selected configuration, certain application pages may only be accessible in a protected mode. Protected mode management is controlled by page access passwords (Figure 1-13).
Figure 1-13: Accessing the applications pages
Static function key
(for terminal with keypad)
Application page
Dynamic function key
(for terminal with keypad)
Touchscreen zone
(for touchscreen terminal only)
Page 12
List of pages or page number
PLC command
1 - 18 Graphic Magelis
Application pages
1.3.3
Displaying the alarm list
A list of active alarms may be accessed from any application page.
Access from terminals with keypad
An indicator light and the alarm symbol on the service line indicate that it is possible to access the list of alarms.
The list of alarms can be displayed by pressing the ALARM key
(SHIFT+ENTER).
Access from touchscreen terminals
The list of alarms can be displayed by pressing this icon on the status line.
1
1.3.4
Getting help
The availability of help is indicated by the " ?" key indicator light on the keypad. You can display the help page by pressing this key.
Press the ESC key to exit the help page and return to the page from which you asked for help (Figure 1-14).
Figure 1-14: XBT Keys
Graphic Magelis 1 - 19
Alarm pages then
Press the ESC key (or press the ? key again) or leave a one-minute time-out to exit the help page and return to the page from which you asked for help.
The help page on a touchscreen terminal can be accessed by pressing the help icon to call up the help page.
Help pages can be associated with application pages or alarm pages.
1.3.5
Recipe pages
A recipe page is created from a page model used for a specific application.
It is mainly used to:
• “record” a process status at a given moment,
• manually adjust the setup parameters,
• locally store these values on the terminal,
• re-use the statuses stored.
The main advantage of a recipe page is that it can store up to 5000 variable values in 1 to 125 recordings thus avoiding repetitive entries for the user.
1 - 20 Graphic Magelis
Alarm pages
1.4
Alarm pages
The purpose of the alarm pages is to display a control system's fault indications and a list of possible corrective actions. The advantage of an alarm page is to provide an event-related display. Each alarm page is associated with:
• a description of 32 characters maximum,
• one or several control system word bits. If one of the word bit is set to 1, the alarm is displayed. Control system bits can also be associated with the alarm page on a TXBT.
(example: A sensor fault occurs. The bit associated with the sensor fault changes to 1 in the control system).
1
Sensor fault
PRESSURE SENSOR FAULT
(keyboard)
•
ALARM
(touchscreen)
Alarm indication from an application page
• The status line indicates the last alarm (see Figure 1-10).
• The alarm strip displays the message of the latest alarm activated (see section 1.3.1).
• Alarm indicator light: The "Alarm" indicator light indicates the status of the alarm list to the operator at all times:
Off: the current list of alarms is empty.
On: the list contains alarms that have already been displayed.
Flashing: the list of alarms contains new alarms.
Flashing: the list of alarms contains the latest alarms since last display of the list of alarms by the operator.
Graphic Magelis 1 - 21
1 - 22
Alarm pages
WARNING
UNINTENTIONAL EQUIPMENT OPERATION
The XBT does not support any type of processor nor machine control in association with alarms. It is the designer's responsibility to consider programming PLC logic to account for programmed alarms.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
Composition of the alarm pages
An alarm pages consists of 3 parts:
• Application region
• An alarm strip
• Status line
Application region
The application region of an Alarm page can contain the same objects as an application page (i.e., static alphanumeric texts, variable fields, static graphic objects, dynamic graphic objects, dynamic function keys, and an optional alarm bar). (You cannot access the applications region of an alarm page using a function key).
Example of an alarm page
Application region
Automatic operation
Start hydraulic unit
End of lift of manipulator
Rotation of grip to right
Graphic Magelis
Figure 1-15: Properties Page
Alarm pages
The XBT-L1000 software allows you to define the properties of the alarm pages
(Figure 1-15).
1
Status line
It is identical to the one displayed on the application pages
(see Application pages).
Alarm indicating
• It is possible to force the operator to acknowledge the alarms so that they can be erased from the list of active alarms; this is useful for transient alarms.
• The terminals have a relay output whose contact is closed when an alarm appears. This function can be configured for each alarm page.
Advantages of alarm pages
• It is possible to assign a priority to an alarm page (1 to 16, with 1 as the highest priority).
• It is possible to record (log) alarm pages to help control system troubleshooting.
• The alarms are time-stamped.
Graphic Magelis 1 - 23
Alarm pages
• Alarms may be configured to require an operator to acknowledge an alarm before continuing process operation; this is useful for transient alarms and troubleshooting.
NOTE: This relay opens upon a power loss. The relay's contacts are normally open (N.0.).
• The terminals have a relay output whose contact closes when an alarm appears. This function can be configured for each alarm page.
Group of alarms
A group of alarms is a set of alarms identified by different color attributes. Each defined group may have its own unique colors that indicate the status of the alarm. The alarm active, alarm cleared, and alarm acknowledged colors make the alarm's status easily recognized by the operator. There are 16 groups of alarms. Each group is identified by an 8-character name enabling rapid identification by the operator.
Getting help
The availability of help is indicated by the " ?" key indicator light on the keyboard. Press this key to display the help page.
Press the ESC to exit the help page.
Printing
You can print the alarm page or the alarm log by means of:
• PRINT key,
• PLC command.
then
The print function from the alarm list page or alarm history page on the touchscreen terminal is accessed by pressing the status icon and then by pressing the print icon.
1 - 24 Graphic Magelis
Help pages
1.5
Help pages
Help pages can be associated with an application page or with an alarm page (Figure 1-16). The help page associated with an application page can be used for:
• Information about elements of the page
• Information about process control
The help page associated with an application page can be used to provide operator information about control system faults and a list of corrective actions. A help page consists of three parts:
Figure 1-16: Help Page • Application region
• An alarm strip
• Status line
1
Application region
It can include the following:
• Static alphanumeric texts
• Static graphic object
Status line
The status line is identical to the one displayed on the application pages (see section 1.3.1).
Alarm strip
The alarm strip is identical to the one displayed on the application pages (see section 1.3.1).
+
TXBT screen printout
The SHIFT + PRINT keys enable you to print out screen hardcopies.
Graphic Magelis 1 - 25
Form pages
1.6
1.7
Form pages
The form pages are used for printing only.
They are used for creating measurement and production follow-up reports, labels, etc.
A form page can include:
• texts,
• alphanumeric variables,
• frames for designing tables,
• control codes specific to the printer used (bar codes printing, bold printing, etc.).
Managing the control system
The control system can be managed from the terminal using the static or dynamic function keys. There are two possible types of commands:
• Momentary contact command
• "Push-on/push-off" toggle command
Momentary contact command
A control system bit is activated by pressing a function key. The bit is set to a "1" while the function key is pressed and reset to "0" when the function key is released.
Example: Controlling a motor
Control bit set to "1"
0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0
"1"
Motor
( )
"1"
1 - 26 Graphic Magelis
Managing the control system
"Push-on/push-off" toggle command
The control system is activated by pressing the function key. The control bit associated with the function key is set to a "1" on the first press. The next press of the function key resets the bit to "0".
1
Example: Conveyor belt advance command.
1 = Push
0 = Next Push
0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0
"1"
Conveyor
( )
"1"
The XBT-L1000 software allows you to assign the desired command to each function key.
Graphic Magelis 1 - 27
Function keys
1.8
Static and dynamic function keys
Static function keys
The static function keys are global and their configuration is defined for the entire application. They may be configured to perform the following functions:
• Access a page
• Momentary contact command
• " Push-on/push-off" toggle command
Dynamic function keys
The dynamic function keys are associated with a page. Their configuration and function can therefore change from one page to another (Figure 1-17). Dynamic function keys may be configured to perform the following functions:
• Access a page
• Momentary contact command
• "Push-on/push-off" toggle command
• Selecting an entry field
• Startup of a Windows 95 application (TXBT only)
The function key's configuration is defined by means of the
XBT-L1000 software, and may not be modified in run mode.
Figure 1-17: Configuration of Dynamic Key
XBT TXBT
1 - 28 Graphic Magelis
Function keys
The function keys for the touchscreen terminal application pages are replaced by touch icons. They are defined in the same manner as the dynamic function keys for the keypad terminals using the
XBT-L1000 software and perform the same function:
• access to a page,
• bit control,
• positioning on an entry field.
Example of graphics
1
1.9
An icon is associated with each page access or switch to entry type dynamic key.
Variable adjustment of the PLC register reference value
The TXBT can be used to adjust the register reference value of the connected PLC. Adjustment is available for the following communication protocols:
• UniTelway
• EthWay
• Modbus
• Fipway
• Fipio
• Modbus+
See Chapter 3 for additional information.
XBT
The adjustment page is used to display and modify the register reference values of the connected PLC. The page is directly created on the terminal by selecting the requested variables. Once created, the page is refreshed on a cyclic basis.
The page is locally stored on a PCMCIA card and can thus be reused even if the terminal has been switched off.
Adjustment of the register reference value is available for all communication protocols.
See section 3.14 for more details.
Graphic Magelis 1 - 29
PLC/terminal dialog
1.10
PLC/terminal communication dialog
The man/machine communication dialog between the terminal and the PLC consists of an exchange of data between the two devices.
Various types of data can be exchanged.
Data associated with fields
PLC
Command data from the
PLC to the terminal
Status data from the terminal to the PLC
GRAPHIC
TERMINAL
WARNING
UNINTENTIONAL EQUIPMENT OPERATION
If communications between the XBT and PLC are lost, the operator's control over the machine may be lost partially or completely. It is the designer's responsibility to consider programming the PLC logic to account for this situation. One good technique is to monitor Wn+3 of the dialog table from the PLC table.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
1 - 30 Graphic Magelis
PLC/terminal dialog
Data associated with the fields
The exchange principle for the data associated with the fields depends on the protocol chosen as a function of the type of PLC.
The variables read or written are the single words, double words and word bits.
Master or client terminal
The terminal controls the following transfer exchange regardless of whether or not the terminal is defined as a master or slave:
• Updating of the fields (reading the values in the PLC)
• Entry and modification of fields (writing the values to the PLC)
1
No PLC communication program needs to be written.
Server or slave terminal
The PLC application is responsible for updating the displayed variables by constantly writing the values of the variables that have changed to the terminal.
Principle of terminal "command and status" exchanges
To simplify the communication dialog, the data is grouped together in a memory zone: the dialog table located in the PLC.
• Commands from the PLC to the terminal
• Status data from the terminal to the PLC
Consisting of "n" consecutive words (16-bit words), this table is divided into two parts.
Status table
Status data from the terminal to the PLC
Command table
Commands from the PLC to the terminal
Graphic Magelis 1 - 31
PLC/terminal dialog
The number of words in the table depends on the status data and the commands you choose to process during the dialog. The
XBT-L1000 software allows you to make this choice (Figure 1-18).
WARNING
UNINTENTIONAL EQUIPMENT OPERATION
The PLC memory zone allocated for the XBT dialog table must
NOT be used for anything else. It is the designer's responsibility to properly program the PLC logic.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
Figure 1-18: Configure Dialog Table
1 - 32 Graphic Magelis
Loading extension tasks
1.11
Loading of extension tasks when transferring the application
On a TXBT terminal, you can add functions on top of the basic XBT-
F functions. These extra functions are called extension tasks.
1
The extension tasks supplied as standard for configuring a TXBT are as follows:
• The OLE Automation server (see TXBT manual, Chapter 8)
• The Variables setting module
• The Program diagnostic and dynamic display module
1.12
Starter kit for the Graphic Magelis
application
Development hardware kit
• 1 XBT-F 5", 9.5", or 10.4", TXBT 9.5" or 10.4".
• 1 PC Pentium or equivalent
SVGA screen or higher resolution.
1 serial port operating at 19200 bauds (speed required when transferring)
1 mouse
V2.2
• 1 XBT-Z915 cable and 1 adaptor XBT-Z962 for XBT/PC exchanges and printing
• 1 printer, if necessary
Graphic Magelis 1 - 33
1 - 34
Starter Kit
Development software kit
• Windows 95 or Windows NT
• XBT-L1000 V3.x (graphic Magelis application development software). The downloadable protocols depending on the type of PLC:
XBTL1UTW01 for Télémécanique PLCs
XBTL1MOD01 for April, Modicon and April AEGApril PLCs
XBTL1AEG01 for AEG PLCs
XBTL1SIE01 for SIEMENS PLCs
XBTL1AB01 for Allen Bradley PLCs
XBTL1OMR01 for Omrom PLCs
Several protocols can be installed on the PC at the same time.
Operating hardware kit
• 1 Magelis/PLC cable
-
-
-
TSX07/37/57
TSX17
TSX7
SCM2116
TSXSCA62
Console connector
Console connector
SCI connector
UTW connector
XBTZ968
XBTZ958
XBTZ948
XBTZ918
XBTZ908
Others: refer to the service instructions for the corresponding protocol
• 1 XBT-Z915 cable for printing
• 1 printer, if necessary
• 1 TCCX CB 20002 cable supplied with the TXBTs
Graphic Magelis
Graphic Magelis
Chapter 2
Application Development
2
2 - 1
2 - 2 Graphic Magelis
Contents
The purpose of this chapter is to present a method for implementing an application. It provides information on how to use the XBT-L1000 software. The XBT-L1000 software's menu, submenu, and tool palette structure gives you every latitude when developing your application. The software's on-line help and the instruction manual provides detailed information to assist you in using the XBT-L1000 software.
This chapter includes the following sections:
2.1
Application requirements specification ........................ 2-5
2.2
Development method ....................................................... 2-6
2.3
Application development with the
XBT-L1000 software ......................................................... 2-9
2.3.1
2.3.2
2.3.3
Creating the application ................................... 2-9
Creating the equipment list ........................... 2-10
Loading the PL7 or Concept symbols file ..................................................... 2-10
2.4
Configuring the communications dialog table ........... 2-12
2.5
Creating pages ............................................................... 2-14
2.5.1
The main window ............................................ 2-14
2.5.2
2.5.3
Model pages .................................................... 2-21
Application/Alarm/Help pages ....................... 2-22
2.5.4
2.5.5
Configuring a form page ................................ 2-27
Tree structure control .................................... 2-28
2.6
Translation of the application ....................................... 2-29
2.7
Configuring the terminal parameters ........................... 2-31
2.8
Saving the application ................................................... 2-33
2.9
Application simulation ................................................... 2-34
2.9.1
Terminal simulation window .......................... 2-34
2.9.2
PLC simulation window ................................. 2-35
2.10 Transfering the application to the terminal ................. 2-36
2.10.1
XBT-F terminals .............................................. 2-36
2.10.2
TXBT-F terminals ............................................ 2-36
2.10.3
Import/export file ............................................. 2-38
2
Graphic Magelis 2 - 3
Contents
2.11 Updating the application ............................................... 2-39
2.12 Running the application ................................................ 2-40
2 - 4 Graphic Magelis
Requirements Specification
2.1
Application requirements specification
The requirement specification is the starting point for developing the man/machine dialog application.
It must include all the user's requirements. To achieve this, it is recommended that the requirements be broken down according to certain criteria:
• the criteria linked to the users
Production monitoring
Controlling the control system
Preventive maintenance
Corrective maintenance
...
• the criteria linked to the control system
Man/machine interface
Intervention level
...
• the criteria relative to developing the dialog application itself
Program structure
Data structure
Debugging
Updating
The specification requirements must indicate:
• Dialog architecture as seen by the end user
(navigation, etc.)
• Volume of data to be exchanged between the PLC and
the terminal
• Type of data
• Terminal/PLCs network architecture
Use the specification requirements to validate the development.
2
Graphic Magelis 2 - 5
Development method
2.2
Development method
Phase 0: Control system structure
From the control system structure, define:
• the communication protocol used by the terminal,
• the list of equipment items accessible to the terminal.
Phase 1: Commands from the terminal to the control system
For each command from the terminal to the control system, define the operator’s action mode:
• static function key,
• dynamic function key (define the associated application page).
Phase 2: Commands from the control system to the terminal
Define all the actions performed from the control system to the terminal:
• page call-up by the PLC,
• display of LEDs,
• key locking,
• triggering of curve plotting, etc.
Phase 3: Design of pages
Based on the requirements, design all the pages mentioning for each of them:
• the purpose,
• the type (application, recipe, alarm, help, printout forms),
• the data to be processed.
Phase 4: Dialog table
Phases 0 to 3 are used to determine all the words - exclusive of any other words - which are necessary for the dialog table.
2 - 6 Graphic Magelis
Development method
It is recommended to perform this operation before initiating the
PLC program as any addition or cancellation of a word in the dialog table modifies its structure.
Phase 5: Model pages
Identify the data which are identical on each type of pages: application, help, alarm.
This data can be:
• text, frames, logos, drawings, etc.,
• variables (alphanumeric and/or graphic),
• the status line and/or the alarm strip (displayed by default).
2
It is recommended to use the model pages for:
• simplifying and clarifying the development,
• providing an easy-to-use man/machine interface by the creation of similar “environments”,
• structuring the space available in the terminal memory.
Phase 6: Definition of application pages
Create the application pages and then define navigation. It can be performed via:
• dynamic function keys: for a navigation organized in menus,
• static function keys: for direct access to a page of the structure.
Provide the necessary controls for access to the pages and variables available for entry (see section 2.4 for all details). The zones protected by a password can be configured in specific menus.
Graphic Magelis 2 - 7
Development method
Phase 7: Definition of alarm pages
• Define the equipment items of the control system structure which can be at the origin of alarm triggering.
• Define the size of the alarm tables for all these equipment items. A table includes 1 16-bit word minimum, i.e. 16 alarms maximum per word. Define as many words as necessary.
• Divide the alarms pages into groups according to the control system structure, technologies involved, etc. See section 6.3
for all details.
• Classify the alarms and assign a priority to each of the
(1 to 16).
• For each alarm, define whether it must:
be printed (to keep a hard copy of the faults as soon as they are detected),
be recorded in the history (for sequential analysis of the faults: occurrence, cancellation, acknowledgement),
be displayed (some pages may not be displayed to the operator),
be necessarily acknowledged by the operator (ACK),
trigger energizing of a relay associated with a horn, a lighting column, etc.
Phase 8: Definition of help
• Define the help pages. If necessary, the same help page can be associated with several application or alarm pages.
• Define the help windows for variables requiring a comment, an advice, an explanation, etc.
Phase 9: Translations
State the application languages (3 maximum) and translate the text objects.
2 - 8 Graphic Magelis
Application development
2.3
Application development with the
XBT-L1000 software
2.3.1
Creating the application
Select the File/New menu.
Figure 2-1: File/New Menu
2
Indicate the type of terminal.
Figure 2-2: Type of Terminal Dialog Box
Select and configure the protocol (baud rate, format, etc.). This is the terminal to PLC communications protocol.
When creating an application, it includes by default:
• an empty application page (1: Application page 1),
• an application page model by default (1: Application Model 1),
• a recipe page model (2: Recipe model 2),
• an alarm page model by default (1: Alarm Model 1),
• a list of system pages in the language in which XBT-L1000 is installed.
Graphic Magelis 2 - 9
Creation of application and equipment
2.3.2
Creating the equipment list
Select the Configuration/Equipment symbols menu.
Figure 2-3: Configuration/Equipment Symbols Dialog Box
Define the list of equipment items addressed by the terminal.
2.3.3
Loading the PL7 or Concept symbols file
(special case of Modicon TSX Micro, Premium and Quantum PLCs):
To create a symbols file in PL7:
1. Open the variables editor.
2. Select the File/Export command.
3. Select the disk and/or directory in which the file is to be stored.
4. Enter a filename: for example Appli.SCY.
5. Select the "all types" export mode and validate.
2 - 10 Graphic Magelis
Creation of application and equipment
To create a symbols file in Concept:
1. Select the File/Export command.
2. Choose the target file format. Variables: Text delimited.
3. Choose the separator (by default: “,”).
4. Click on Ok.
5. Select the Drive and/or Folder where the file will be stored.
5. Enter a filename: for example Appli.TXT and click on Ok.
Use the PL7 or Concept symbols file under XBT-L1000:
1. Select the Configuration/Equipment Symbols command.
2. Choose the device corresponding to the variables file.
3. Click on “Modify”.
4. Select the Variables file/Add command.
5. Select the directory in which the symbols are stored, then click on Open.
For a Concept file, choose the same separator as that defined in
Concept.
NOTE: The dialog application under XBT-L1000 must be updated each time the symbols file to be used is updated. To do this, repeat operations 1 to 3, select the Variables file/Delete command and then repeat operations 4 and 5.
2
Graphic Magelis 2 - 11
Dialog table
2.4
Configuring the communications dialog table
When you have defined the various pages, you willl have to define the content of the communications dialog table (Figure 2-4). Chapter
4 provides the information on the various bits and words in the dialog table.
Select the Configure/Dialog table menu.
Figure 2-4: The Dialog Table
2 - 12
Base address
Indicate the address of the beginning of the table (address of the first word in the dialog table).
Composition of table
Add or delete the various elements to/from the table as needed.
Use of the dialog table is optional in applications that do not use alarm pages. Alarm pages require the creation of an alarm table that is defined by the dialog table. For further information on the various dialog table components, consult the XBT-L1000 software on-line help or chapter 4 of this manual.
Cycle
The terminal's read/write period for the dialog table is used to optimize the terminal/PLC exchanges (see chapter 4, section 4.3).
Graphic Magelis
Dialog table
Dialog table security
A word is used in the table for security purposes: the "Authorization" word. Using this word ensures PLC/terminal dialog security.
When this word is not at the correct value, the terminal cannot write any words in the PLC and cannot execute any commands.
It is systematically present in the default dialog table proposed by
XBT-L1000 (see chapter 4, section 4.2). The authorization word may be removed from the dialog table if you choose.
Alarm table
A word bit is associated which each separate alarm. All these words make up the alarm table which is part of the dialog table.
• A terminal can process the alarms from several PLCs.
• The alarm table can be distributed between several of the automated process's PLCs.
• Each PLC in a networked application may have its own alarm table.
• The alarm table associated with a PLC allows the latter to transmit alarms to the terminal (see Chatper 3, Section 3.6)
The dialog table words (see chapter 4, section 4.2)
• "last alarm acknowledged" and
• "last group of alarms acknowledged" are present in each of the PLCs that contain an alarm table.
2
PLC dialog table containing 5 alarm words and 2 acknowledgment words
5 Alarm words
Graphic Magelis
2 Acknowledge words
PLC 1 dialog table containing 3 alarm words and 2 acknowledgment words
2
PLC 2 dialog table containing 4 alarm words and 2 acknowledgment words
3
2
4
2 - 13
Presentation main window
2.5
Creating pages
2.5.1
The main window
The main window that you use to make up the various pages has the following structure (Figure 2-5).
Figure 2-5: Main Window
Toolbar
Tool palette
2 - 14
The toolbar allows you to perform various software functions
(Figure 2-6).
Toolbar
Figure 2-6: Toolbar
Graphic Magelis
Presentation main window
Objects
To configure an object onto a page, select the object on the Object
Selection Bar and drag the cursor to the desired application page location. Click on the mouse button, drag and highlight the desired object window size, and release the mouse button. To define an object's properties, double click the object.
Animating objects
Certain static objects (i.e., text, etc.) can be animated. Animation consists of making an object's color attributes change as a function of the value of an associated PLC variable. This variable must be declared when configuring the object (i.e., 40100). The basic principle consists of drawing up a list of possible values and, for each value, assigning a color to the animated object.
2
The next page presents the different objects:
• Static object: S
• Animated object: A
• Dynamic object: D (this object shows the change in a variable in alphanumeric form or a graph)
Graphic Magelis 2 - 15
Presentation main window
S: static object A: animated object
D: dynamic object showing changes to a variable in alphanumeric or graphic form.
Objects Usage Representation
Text To provide qualitative information.
Maintenance
(S,A)
Line
Graphical representation of an application.
Rectangle
Ellipse
(S,A)
Bitmap
(S)
(D)
(D)
Alphanumeric variable field
Bar-graph
To insert file images for graphical representation of an application
(BMP, WMF, PCX) (a symbols library is available in directory
\XBT-L1000\SYMBOLS)
To display values reflecting the control system status.
To enter values defining parameters for managing the the control system.
Four limits with the possibility to filter the values entered by the operator (Min and Max thresholds only) and to display process overshoots (by changing color).
Temp: 455
°
C
To represent the control system data in a graphical form
(i.e.,: tank level).
Characteristics:
• Vertical
• Horizontal
• Minimum, maximum, high and low limits.
2 - 16 Graphic Magelis
Presentation main window
S: static object A: animated object
D: dynamic object showing changes to a variable in alphanumeric or graphic form.
Objects Usage Representation
(D)
Volume meter
Provides a graphical representation of the control system data (i.e., power supply voltage control).
Minimum, maximum, high and low limits.
To modify the control system variable, graphically (i.e., limit setting).
Minimum, maximum, high and low limits.
(D)
Linear slider potentiometer
Rotary potentiometer
2
Linear slider switch
Rotary switch
To modify the control system variable, graphically (i.e., choice of a type of production using the rotary selector).
(D)
(D)
(D)
Image box
Graphical curve
To display different images according to the value of a variable.
Image file: BMP, WMF, PCX
To monitor control system data changes in real-time (i.e., monitoring a temperature)
Graphic Magelis 2 - 17
Presentation main window
Main characteristics of curve objects
• A curve object can display up to 4 different curve plottings.
These plottings are called pens.
If the address of the object is %MWn (IEC syntax):
the address of the first pen is %MWn
the address of the second pen is %MWn+1
the address of the third pen is %MWn+2
the address of the fourth pen is %MWn+3
• A new curve point is displayed:
periodically every 5, 10 or 30 seconds or every 1.5 or 10 minutes,
when a bit is uploaded in the dialog table (see index on
“Triggering of curve plotting” and “Curve plotting OK").
• Curve write starts:
from the right: each new sampling moves the former values to the left, or,
from the left: each new sampling moves the former values to the right.
• Curve objects can be refreshed (Options tab):
on a cyclic basis: at the specified sampling period but only when the page including the curve is displayed (there is not any plotting on the curve when it is displayed),
on a permanent basis: at the sampling period, including when the object is not displayed.
This option generates permanent data interchange with the PLC and can entail an increase in the response times. Consult section 3.2 for more details.
2 - 18 Graphic Magelis
Presentation main window
Function key objects
Static function keys
Static function keys can be defined for the application to be used as:
Figure 2-7: Configuration of
Dynamic Key
• Access to a page
• Momentary contact command
• "Toggle" command
Dynamic function keys
Dynamic function keys are associated with the page displayed (Figure 2-7).
They can have the following functions:
• Access to a page
• Momentary contact command
• "Toggle" command
• Positioning on an entry field
• Running a Windows 95 executable program (TXBT only)
Touch zones
There are no static and dynamic function keys on touchscreen terminals.They are replaced by touch zones which have the same functions and properties as the dynamic function keys of the terminals with keyboard.
Carry out the following operations:
• click on the button,
• click and slide on the area to determine the location and the size of the touch zone. With the default grid you can create touch zones including the pitch suitable for the physical division of the touchscreen pad,
• double-click on this zone and enter the configuration parameters in the same way as for a dynamic function key of a terminal with keyboard.
Parameters to be defined
Defines the type of function key action
(for terminals with keyboard only).
Type of action:
• Page access: selects an application page
• Momentary contact or "toggle" command: assignment of a command bit in the dialog table (see chapter 3) or elsewhere in the PLC for the dynamic function keys
Graphic Magelis 2 - 19
2
Presentation main window
• Running a Windows 95 application on a TXBT terminal
(definition of executable program path)
Label for the dynamic function keys
This allows you to associate a label with the function key.
• Page access: 1 label (an image)
• Momentary contact or "toggle" command: a label for each status of the associated bit (values 0 and 1, associated with two images representing a released and pressed pushbutton)
By default the size of these images is adapted to the size of the keys (so they can be positioned opposite each other).
Recommendations concerning the use of function keys
• The dynamic function key word bits can be distributed between all the installation's pieces of equipment without any restrictions.
• The static function key word bits are grouped together and defined by the dialog table.
The communication dialog between the terminal and the equipment have better performances if static function key commands are used.
NOTE: It is recommended to use static function keys for control functions, and dynamic function keys for moving around the pages and for entering data.
Running a Windows 95 application on a
TXBT terminal
The TXBT terminal enables you to run Windows 95 applications installed on the terminal (such as the calculator). If the Magelis application is running, it will continue in the background, with pages refreshed and alarms monitored.
Executable program path
This is the path (disk, directory/sub-directory) on the TXBT terminal and not the path on the PC on which XBT-L1000 is installed. If the executable program's location on the TXBT is changed, startup will not work.
Example: D:\WINDOWS95\CALC.EXE
2 - 20 Graphic Magelis
Creating pages
2.5.2
Model pages
The designer has page models at his disposal. These are background pages containing text and static / animated / dynamic graphic objects that can be used for several application, help or alarm pages.
Characteristics
• a dialog application can contain several models,
• one and only one model is associated with each page.
Select Page/New Model. Select the Application, Alarm or Help model type. Configure the model using the editor tools.
NOTE: The model pages can be locked using the “lock icon” icon.
This prevents unintentional modifications of pages.
Figure 2-8: New Model Dialog Box
2
It is possible to change a model from a page by double-clicking on the “Application page” tab (for instance) or by selecting the Page/
Properties menu.
An object or an object selection within a page can be moved:
to the model associated with the page (provided that it is not locked),
to a new model to be created.
Carry out the following operations:
select the object(s),
right click on the mouse or select the Edit/Move menu.
Graphic Magelis 2 - 21
Creating pages
2.5.3
Application/Alarm/Help pages
Creating the page architecture
The designer has page models at his disposal. These are background pages containing text and static graphic objects that can be used as a starting point for multiple application, help, or alarm pages. The following are general rules:
• One and only one page model is associated with each page.
• An application can contain several page models.
• Any given model can be associated with several different pages.
• A model type (application/alarm/help) is associated with a page type (application/alarm/help). For example, each page type has its own model type.
Tool bar buttons:
Keyboard shortcuts:
F7 ( Application)
Shift + F7 ( Alarm)
Ctrl + F7 ( Help)
Ctrl+Shift+F7 ( Form)
Application page
Figure 2-9: Application New
Page Dialog Box
Indicate:
• Name and/or number of the new page
• Page model to be used
• Password (protection) if necessary (Figure 2-9)
2 - 22 Graphic Magelis
Creating pages
Select Page/New Page/Application
Indicates:
• the name and/or number of the new page,
• the page model,
• the protection level if necessary.
The application pages correspond to the “usual” man-machine dialog during normal operation of the terminal. A specific model of the application page can be used to create “recipe” pages. A recipe page represents a file including recordings of the control system setup parameters or variables used to perform a specific type of action.
For instance, an industrial bakery can produce:
• viennese bread and buns: chocolate-filled pastry, croissants, brioches,
• bread: farmhouse bread, whole-wheat bread, rye bread, sticks of French bread,
• cakes: strawberry tarts, lemon tarts.
To make bread corresponds to the selection of a recipe. To make rye bread corresponds to the selection of a recipe recording.
The following four dynamic function keys or touch zones are available by default on the recipe page model:
• a key for freezing/unfreezing the display on the terminal,
• a key for storing the recording displayed on screen in the
PCMCIA card,
• a key for restoring and displaying the recordings previously saved in the PCMCIA card,
• a key for transferring the recording displayed to the control system.
All the application page objects can be used for the recipe pages.
2
Graphic Magelis 2 - 23
Creating pages
Alarm page
The actual display of an alarm depends on the priority that has been assigned to it. Alarms occurring in the process are stored in the
"Alarm list".
When configuring an alarm page, you must indicate:
Figure 2-10: Alarm New Page
Dialog Box
• Name and/or number of the new page (the name of alarm page is the text displayed in the alarm bar)
• Alarm page model to be used (Figure 2-10)
2 - 24
Purpose of alarm pages
An alarm page is used to indicate:
• control system faults
• corrective actions
The advantage of the alarm page is the event-linked display. A control system word bit is associated with each alarm page. If the word bit is in state 1, the alarm is triggered.
Operation advantages
• When a fault appears, it is often the consequence of other faults. The terminal's priority system allows the most serious fault to be displayed first (for example, the fault which has been defined as the most hazardous for the control system).
• The occurence of each fault is time-stamped.
Maintenance advantages
• The terminal store the occurence of faults sequentially (log) thus making it possible to find the origin of the fault.
• Several alarms may therefore occur simultaneously in the process.
Graphic Magelis
Creating pages
The Add button allows you to assign a dialog table alarm bit to the alarm page being configured (Figure 2-11).
• On the XBTs, these alarm words are consecutive and make up the alarm table. In the event of an alarm, the rank of the word bit (in the dialog table) which triggered the alarm is displayed in the alarm strip (see chapter 3, section 3.6.2).
Figure 2-11: Add Alarm Bit
Dialog Box
2
• On the TXBTs, this same principle exists, but it is also possible to assign any bits (internal bit, word bit, etc.)
• If using any other bit as an alarm bit, the field assigned to the
"bit rank" in the alarm strip takes value 1.
• In the PLC\terminal exchanges, the bit is dealt with like a numerical field.
• The 2 types of operation can be used in the same application.
The Extensions button is used to enter the characteristics specific to an alarm page (Figure 2-12):
• Alarm page priority
• Assignment to a group of alarms
• Alarm relay action and operator ackowledgment
• Type of alarm page appearance
(See chapter 3, section 3.8).
Figure 2-12: Alarm New Page
Properties
Dialog Box
Graphic Magelis 2 - 25
Creating pages
Help page
Help pages typically include information on the operation being monitored or controlled. When configuring a help page, indicate:
• Name and/or number of the new page
• Help page model to be used
Associating a help page with a page
Select the Page/Associate Help Page...
menu.
This menu allows you to (Figure 2-13):
• Associate an existing help page with the selected page
• Associate a new help page with the selected page
• Change the help page associated with the selected page
The “New” button allows you to create a new help page.
Figure 2-13: Associate Help Page Dialog Box
2 - 26 Graphic Magelis
Creating pages
2.5.4
Configuring a form page
Select Page/New Page/Form.
Indicate the name and/or the number of the new page.
The form pages can include the following elements:
• text objects,
• semi-graphic characters,
• printer control codes.
Text objects are static texts and alphanumeric variable fields.
These elements are intended for printing only.
Semi-graphic characters are used to create simple or double frames for highlighting printed data (table of values, etc.).
The printer control codes {a} (ex : {1}, {2}, etc.) are used to define printer control sequences (printing of bar codes, bold characters, change of colors, etc.).
2
Graphic Magelis 2 - 27
Tree structure
2.5.5
Tree structure control
The software allows you to display the application's structure in a window (Figure 2-14). The pages are listed in increasing page number order. The Application and System pages have a tree structure. The alarm pages have a "flat" structure.
Figure 2-14: Page Tree Window
2 - 28
The terminal keys allow you to move around the tree structure.
The page types are indicated by various icons. When the mouse pointer is positioned on an icon, a message is displayed indicating the type of page and its characteristics.
Examples
Unprotected application page, with an associated help page.
Application page protected by a password, with an associated help page.
Alarm page with an associated help page.
Unprotected system page.
Graphic Magelis
2.6
Translation of the application
Configuration/Application languages menu.
Translation of the application
2
Add, delete or modify the application languages (3 maximum).
To translate the application, select the required language using the
“Language” combo-box. Then, double-click on each text object and listtype alphanumeric field of the page to be translated.
It is possible to translate system page texts into a language different from one of the five languages available under XBT-L1000.
Graphic Magelis 2 - 29
Translation of the application
2 - 30 Graphic Magelis
Terminal parameters
2.7
Configuring the terminal parameters
Select the Configuration/Terminal parameters menu
(Figure 2-15).
Figure 2-15: Configure Terminal Parameters Dialog Box
Configure the terminal parameters.
2
Page number displayed by default at power up
The 2 possibilities are:
• An application page
• A system title page
See chapter 3, section 3.1
Graphic Magelis 2 - 31
Terminal parameters
Passwords
The “Password” button allows you to configure three passwords - A,
B and C . Each password must consist of four alphanumeric characters. See chapter 3, section 3.5.
Default language
The language to be used by the terminal (system messages).
Date format to be used
dd/mm/yyyy mm, dd, yyyy yyyy, mm, dd used
11 :59 :59
23 :59 :59
(for example, 25/06/1996)
(for example, 06/25/1996)
(for example, 1996/06/25)Time format to be
Printer setup
2 - 32 Graphic Magelis
2.8
Saving the application
Select the File/Save menu (Figure 2-16).
Figure 2-16: Save As Dialog Box
Saving the application
2
Graphic Magelis 2 - 33
Application simulation
2.9
Application simulation
Simulation enables the XBT-L1000 application designer to test the real effect of his application without requiring a complete hardware configuration. This function is accessible via the Simulation menu.
Items simulated:
• Application and alarm pages
• Page sequences
• Variables input (with thresholds, etc.)
• Dialog table and alarms table
NOTE: Help pages, keyboard LEDs, printouts, alarm relay and external application startup (TXBT-F) are not simulated.
Monochrome screen terminals are simulated with the standard color palette.
2.9.1
Terminal simulation window
The window simulates the information on the terminal's screen.
When this window is active, the PC keyboard simulates the terminal's keyboard.
Key equivalents:
Terminal
R1.....
F1.....
Home
Esc
Syst
Menu
Mod
Alarm
Enter
Left/Right/
Up/Down
+1
-1
Del
Alphanumeric
Keypad
PC
F1.....
Shift F1.....
Home
Esc
Page Up
Page Down
Insert
Fin
Enter
Arrow Left/
Right/Up/Down
Shift + Up
Shift + Down
Del
Alphanumeric
Keypad
2 - 34 Graphic Magelis
Application simulation
2.9.2
PLC simulation window
Three tabs can be used to simulate:
• The displayed page variables (initially, a random value is allocated)
• The alarm tables
• The dialog table. Refresh of this window can be inhibited, to enable input of a page change, etc.
2
Graphic Magelis 2 - 35
Transferring the application
2.10
Transferring the application to the terminal
2.10.1
XBT-F terminals
1. Install the terminal.
2. Connect the terminal to the PC as shown in the service instructions (XBT-Z915-V2.2 cable and adaptor XBT-Z962).
3. Turn the power on to the terminal.
When the terminal is switched on, the operating mode is selected automatically depending on the type of cable connected to the terminal:
• Terminal connected to the PC with the XBT-L1000 software: save mode.
• Terminal connected to the PLC: operating mode (with the possibility of switching to password protection mode).
4. Open the application to be transferred.
5. Select the Transfers/Export menu.
6. Answer the questions the software asks. The application is transferred.
2.10.2
TXBT-F terminals
1. Install the terminal as recommended in the TXBT manual.
2. Connection for transfer on a TXBT terminal; two types of transfers are possible:
• Local transfer: The Magelis graphic application is loaded into the TXBT via a direct link to a PC equipped with XBT-
L1000 <-> TXBT; the port used is COM1 (XBT-Z915 V2.2
cable and XBT-Z962 adapter).
• Remote transfer: If the terminal and the PC containing XBT-
L1000 are connected on the PLC network, and if this network is of the Unitelway or Fipway type, then transfer can take place via this network.
The Setup R1 function on the home screen gives access to the parameter settings screen (see chapter 3.3 of the TXBT manuals for selection of the transfer type).
2 - 36 Graphic Magelis
Transferring the application
TXBT network address
The TXBT network address is entered locally on the TXBT using the network configuration utilities supplied (Magelis
Tools Unitelway, Fipway, Isaway). The Start/Program/
Magelis Tools menu gives access to the Magelis Tools
Group, which contains these various utilities. See section 4.3
of the TXBT manual for addressing.
Declaration of remote transfer address with XBT-L1000
When the address is configured in the TXBT, the remote transfer address must be declared in XBT-L1000.
2
3. Switch on the terminal.
When switched on, the terminal will look for the graphic Magelis application on the PCMCIA card and then on the hard disk in the
C:\TXBT\APPLI directory. If the terminal detects an application, it will be automatically started. If the terminal fails to detect an application, the home screen appears, and the terminal waits for a transfer (see TXBT manual, section 4.1).
• Loading extension tasks when transferring the application
On a TXBT terminal, it is possible to add functions on top of the basic functions of an XBT-F. These extra functions are called Extension tasks (see TXBT manual, section 4.5).
• Loading the PL7 symbols file
During the transfer, it is possible to load the PLC application variable symbols file and subsequently use the symbols associated with the variables to modify them when using the extended settings function (see TXBT manual, section 4.7).
• Loading extra files when transferring the application
During the PC -> TXBT transfer, it is possible to load extra files into the TXBT (see TXBT manual, section 4.4).
4. Select the Transfer/Export menu.
Graphic Magelis 2 - 37
Transferring the application
2.10.3
Import/export file
If a PCMCIA card unit is available on a PC that has been loaded with the XBT-L1000 software, the application can be directly written on the card provided for the terminal. The Transfer/Import-export file menu is used to select the name of the PCMCIA unit.
XBT-L1000 -> PCMCIA card export
To export the application, select the Transfers/Export/ to import/
export folder menu. Insert PCMCIA card at the location provided on the terminal.
PCMCIA -> XBT-L1000 card import
To import the application, insert the PCMCIA card into the PC and then the Transfers/Import/from import/export folder menu.
Use the Export/to import/export folder function to import the application.
2 - 38 Graphic Magelis
Updating the application
2.11
Updating the application
When an application that has been saved under an earlier version of the XBT-L1000 software is opened using a later version, the user will be prompted to have the software update the application to the later version.
This operation is used to update new system page formats and enables the designer to incorporate the enhanced functions of the new version into the existing application. Therefore, It is strongly recommended that the user perform the update.
2
NOTE: The model pages for application, alarm and help pages are not updated automatically. Thus, the alarm strip and the status line may have been re-located, deleted or modified by the designer.
Updating the model pages:
1. Perform the updating proposed by XBT-L1000.
2. Create a new model for each type of page (application, alarm, help).
3. Delete the required elements (alarm strip, status line) from the existing models.
4. Cut/paste the elements required from the new models to the existing ones.
Graphic Magelis 2 - 39
Running the application
2.12
Running the application
Refer to chapter 3.
2 - 40 Graphic Magelis
Graphic Magelis
Chapter 3
Operating the Terminal
3
3 - 1
3 - 2 Graphic Magelis
Contents
This chapter includes the following sections:
3.1
Keys and indicator lights ................................................ 3-5
3.2
Operating principle ........................................................ 3-12
3.2.1
Basic principle ................................................ 3-12
3.2.2
3.2.3
3.2.4
Application transfer ........................................ 3-14
Operating mode .............................................. 3-16
Confidential mode, password management .................................. 3-19
3.3
Page display ................................................................... 3-23
3.3.1
Display at powerup ......................................... 3-23
3.3.2
Displaying a page using the directory of pages ........................................... 3-26
3.3.3
3.3.4
Displaying a page using its number ............................................................. 3-27
Displaying a page by means of a dynamic function key .................................. 3-28
3.3.5
3.3.6
Displaying a page by means of a static function key ....................................... 3-29
Displaying a page using a word from the PLC ................................................... 3-30
3.4
Variable fields ................................................................. 3-31
3.4.1
Accessing a field ............................................. 3-32
3.4.2
3.4.3
Field entry ........................................................ 3-34
Field characteristics ....................................... 3-35
3.5
Alarms ............................................................................. 3-39
3.5.1
Principle ........................................................... 3-39
3.5.2
3.5.3
Alarm page parameters .................................. 3-40
Alarm group ..................................................... 3-42
3.5.4
3.5.5
3.5.6
3.5.7
3.5.8
Display priority of the alarm list .................... 3-43
Acknowledging alarms ................................... 3-44
Alarm relay command .................................... 3-45
Description of the alarm list .......................... 3-45
Alarm display by the PLC .............................. 3-46
3.6
Alarm history log ............................................................ 3-47
3.6.1
Principle ........................................................... 3-47
3.6.2
3.6.3
3.6.4
Displaying the alarm history log ................... 3-48
Clearing the alarm history log ....................... 3-48
Printing the alarm history log ........................ 3-48
3
Graphic Magelis 3 - 3
3 - 4
Contents
3.7
Process control using function keys ........................... 3-50
3.7.1
Momentary contact command ....................... 3-50
3.7.2
Push on/push off toggle command ............... 3-50
3.8
Running Windows 95 applications on the TXBT .................................................................... 3-52
3.9
Key locking by the PLC ................................................. 3-54
3.10 Printing ............................................................................ 3-56
3.10.1
General ............................................................. 3-56
3.10.2
Print set-up ...................................................... 3-56
3.10.3
Stop printing .................................................... 3-57
3.10.4
Continuous printing of an alarm page ....................................................... 3-58
3.10.5
Printing the list of active alarms ................... 3-59
3.10.6
Printing a form page ....................................... 3-60
3.10.7
Printing the alarm log ..................................... 3-60
3.10.8
Free format printing ........................................ 3-60
3.11 Terminal configuration .................................................. 3-61
3.12 Variables adjustment on the TXBT ............................... 3-65
3.13 Variables adjustment on the XBT ................................. 3-69
3.14 Use of recipe pages ....................................................... 3-73
3.15 Loading extension tasks at application transfer ............................................................................ 3-74
3.16 Loading extra files at application transfer ............................................................................ 3-74
Graphic Magelis
Keys and indicator lights
3.1
Keys and indicator lights
This section describes the function of the terminal's various keys.
Each key function is described in the following paragraphs, and the corresponding keys are indicated (Figure 3-1).
NOTE: Some functions (example: SYST) can be accessed by simultaneously pressing SHIFT and the associated key
(example: SHIFT + MENU => SYST)
Figure 3-1: Keys and Indicator Lights
3
XBT
TXBT
Graphic Magelis 3 - 5
Keys and indicator lights
Touchscreen terminals
Touchscreen terminals do not have a keypad. An equivalent touch icon is provided for each of the keypad function keys.
Pressing this touch zone called the service touch icon provides access to a context “keyboard”. Depending on the presence of some functions, the “keyboard” may or may not display the corresponding
“buttons”.
Keys and indicator lights
Function of the keys and indicator lights
ENTER: To confirm a choice or an entry, acknowledge an alarm.
Press the ENTER touch icon on the touchscreen terminal to access this function.
Acknowledge an alarm on touchscreen terminals.
3 - 6
MOD: Switch to entry mode on all the applicable fields or graphic objects.
ESC: To cancel an entry, or suspend or stop an action in progress.
To display the preceding pages successively. To exit from alarm display.
Press the service and ESC touch icons to access this function on touchscreen terminals.
SHIFT: To access a key's second function.
No equivalent touch icon is available on touchscreen terminals.
MENU: To access a menu that contains the run-time functions that cannot be accessed directly by means of a key:
• application page selection,
• the "secondary" run-time functions.
Press the service and MENU touch icon to access this function on touchscreen terminals.
Graphic Magelis
Keys and indicator lights
Keys and indicator lights
Functions of the keys and indicator lights
HOME: To return to the page displayed when the terminal is switched on.
Press the service and HOME touch icons to access this function on touchscreen terminals.
SYST : To access the confidential mode that contains the operating functions:
Status of the indicator lights associated with the SYST key:
• Off: the terminal is in running mode.
• On: the terminal is in confidential mode.
• Flashing: PC <-> XBT transfer in progress or no application in the terminal.
Press the service and SYST touch icons to access this function on touchscreen terminals.
For touchscreen terminal
ALARM
ALARM : To display the alarms
Status of the indicator light associated with the key:
• Off: the current list of alarms is empty.
• On: the list contains alarms that have already been displayed.
• Flashing: the list of alarms contains new alarms.
Press the service and ALARM touch icons to access this function on touchscreen terminals.
PRINT: Print command.
Status of the indicator lights associated with each key:
• Off: no printing possible
• On: printing possible (list of alarms, etc.)
• Flashing: printing error.
Press the service and PRINT touch icons to access this function on touchscreen terminals.
The left and right arrow keys are used to:
• To select an object in a page.
• To move during an entry in an alphanumeric field.
• To change the cursor position on a switch or a potentiometer.
Status of the indicator lights associated with each key:
Off: key inactive.
On: indicates the possibility of moving around in a page from field to field.
Graphic Magelis 3 - 7
3
Keys and indicator lights
Keys and indicator lights
Functions of the keys and indicator lights
Flashing: indicates the possibility of moving around in the selected variable alphanumeric field or of changing a cursor position.
The up/down arrow keys are used to:
• To move around in a page.
• To select a value in a list of values.
• To change the cursor position of a swtich or a potentiometer.
Status of the indicator lights associated with each key:
Off: key inactive.
On: indicates the possibility of moving around in a page from field to field.
Flashing: indicates the possibility of moving around in the selected alphanumeric variable field, changing the cursor position or selecting a value in a list.
For touchscreen terminals, press the object icon to select an object in a page. If data entry or cursor moving is valid for the object, touch icons corresponding to the object context are displayed (for example: a numeric pad for entering a numerical value, increment/decrement arrows for a potentiometer, etc.).
Communication indicator light
• On: no cable or incorrect wiring,
• Off: cable correct, no exchange with the PLC,
• Flashing: exchanges with the PLC.
Keypad indicator light
• Off: no keys pressed, on the keypad or on the touchscreen pad.
• On, green: when pressing any key or a touch zone.
• On, red: the terminal is in standby mode. Press any key or the touchscreen pad to exit this mode.
3 - 8 Graphic Magelis
Keys and indicator lights
Keys and indicator lights
Functions of the keys and indicator lights
Entering data in the various fields
The up/down arrow keys combined with the SHIFT key are used to increment or decrement the value in a variable field if the “access” parameter of the object entered has been configured to immediate write
(or immediate read/write). The value is entered in the control system each time the SHIFT + arrow up/down key is pressed.
3
Status of the indicator lights associated with each key:
• Off: key inactive.
• Flashing: indicates the possibility of modifying the value of each digit.
To delete the character to the left of the cursor.
Alphanumeric entry keys
To reverse the sign of the variable field being entered
Decimal point
Combined with the alphanumeric keys, these keys give access to the character situated on the left, in the middle, on the right of the group of letters.The indicator lights indicate if letter entry is possible.
Graphic Magelis 3 - 9
Keys and indicator lights
Keys and indicator lights
Functions of the keys and indicator lights
Contrast and brightness adjustment
Contrast adjustment: press and hold the adjustment key and make the adjustment by means of the up and down arrow keys.
NOTE: The contrast cannot be adjusted on the XBT-F10" color and
TXBT 10" color terminals.
Brightness adjustment: press and hold the adjustment key and
SHIFT, and make the adjustment by means of the up and down arrow keys.
For touchscreen terminals, adjustment can be made on the
“Terminal parameters” system page.
Static keys (see chapter 1, section 1.7).
Dynamic keys (see chapter 1, section 1.7).
Extra keys for TXBT
Access to Windows 95 functions
A PC keyboard equipped as standard for Windows 95 comprises two additional keys; the START and MENU keys. To access the same functions on the TXBT, use the following equivalents:
• Start key: Obtained by pressing Ctrl+Esc on the TXBT, used to start up an application.
• Menu key: Obtained by clicking the mouse right-hand button on the TXBT, used to access the most common functions associated with an icon.
3 - 10 Graphic Magelis
Keys and indicator lights
Keys and indicator lights
Functions of the keys and indicator lights
"Mouse" function with touchscreen pad and right/left click buttons
Used to select a field or an item in a list (for example: list of pages).
Cannot be used to modify a graphic variable field. Gives access to the Windows 95 functions.
External keyboard
An external keyboard can be connected to the DIN 8-pin connector.
The 2 keyboards remain active.
The front of the 2 terminals have QWERTY keyboards. Any external keyboard should also be a QWERTY keyboard.
3
TXBT and external keyboard equivalents
TXBT keyboard keys External keyboard keys
Rx
Fx
?
DEL
HOME
ESC
+1
SYST
MENU
MOD
SHIFT
-1
ALARM
ENTER
CTRL
ALT
Fx
ALT+CTRL+Fx
DEL
HOME,
ESC,
SHIFT + arrow up
SYST
PageDown
ALT+PrtScrn
INSER
SHIFT
SHIFT + arrow down
SHIFT + ENTER or END
ENTER
CTRL
ALT
Graphic Magelis 3 - 11
Operating principle
3.2
Operating principle
3.2.1
Basic principle
The terminals have 3 operating modes:
• Application transfer: This mode enables transfers between the XBT-L1000 and the terminal. ( XBT-L1000 <-> XBT transfer: application and protocol) (Figure 3-2).
Case of XBTs: local transfer XBT-L1000 <-> XBT
Case of TXBTs: local transfer XBT-L1000 <-> XBT or remote transfer via the PLC network (Unitelway, Fipway or
ISAway).
CAUTION
EQUIPMENT DAMAGE HAZARD
Connect the serial link and printer link to the XBT with the power OFF.
Failure to follow this instruction can result in injury or equipment damage.
Figure 3-2: Application Transfer
XBT-L1000
3 - 12
• Operating mode: This mode is used for on-line control of the control system (Figure 3-3):
PLC control
Displaying information, variables, alarms
Entering values
Discrete command
Print, log consultation functions, etc.
Graphic Magelis
Operating principle
Figure 3-3: Operating Mode or
XBT-L1000
Figure 3-4: Confidential Mode
Operating mode
Password
Confidential mode
• Confidential mode: Besides providing access to the running mode functions, this allows you to access advanced functions requiring a password (Figure 3-4).
Access to pages that are protected in run-time mode
Access to system pages
3
Graphic Magelis 3 - 13
Operating principle
3.2.2
Application transfer
In this mode, 2 types of transfers are possible (Figure 3-5).
Figure 3-5: Transfer Mode
Downloading the Man/Machine dialog application and the protocol for communicating with the control system.
3 - 14
RS232 serial link or PLC network (TXBTs)
12345678901234567890123456789012
12345678901234567890123456789012
PC with the XBT-L1000 software
Uploading transfer of an application from the terminal to a
PC with the XBT-L1000 software.
SYST indicator light: the SYST indicator light flashes during the transfer.
XBT-L1000/Terminal transfer procedure
Transfer from XBT-L1000 -> Terminal: select the Transfers/Export/
To Terminal menu.
Transfer from Terminal -> XBT-L1000: select the Transfers/Import/
From Terminal menu
Wiring: Refer to the terminal instructions for the XBT in chapter 2 of the TXBT Magelis Product Line Reference Manual.
Remote transfer for the TXBT
On a TXBT terminal, 2 types of transfers are possible:
• Local transfer: The Magelis graphic application is loaded into the TXBT via a direct PC link equipped with XBT-L1000 <->
TXBT; the port used is COM1.
Graphic Magelis
Operating principle
• Remote transfer: If the terminal and the PC containing
XBT-L1000 are connected on the PLC network, and if this network is a Unitelway, Fipway or Isaway, transfer is possible via this network.
The Setup R1 function on the home screen is used to configure the transfer (see chapter 3.3 of the TXBT Magelis Product Line
Reference Manual for the choice of transfer type.)
Configuration of the TXBT address
The TXBT address on the network is entered locally on the TXBT using the network configuration utilities provided (Magelis tools:
Unitelway, Fipway, Isaway, ModBus+).
The Program menu gives access to the Magelis Tools Group, which contains these various utilities. The XWin32 utility can be used to test the XWAY network.
Remarks:
• If a configuration has already been set up with XBT-L1000, it will be ignored.
• The FPP20 thumbwheel settings are ignored.
• Any coding in a Unitelway is ignored (SCA62).
Refer to Chapter 4.3 of the TXBT Magelis Product Line Reference
Manual for addressing.
3
Entering a remote address in XBT-L1000
This address can be used to export an application to a TXBT via the
XWAY network already in place, instead of the XBTZ915 +
XBTZ962 transfer cable.
When the address is configured in the TXBT, the remote transfer address must be declared in XBT-L1000. To do this:
1. Select the Transfers/Remote Address menu.
2. Define the remote address with:
the address configured locally on the TXBT,
the socket (channel) number chosen or dynamically allocated at transfer SETUP.
Refer to chapter 4.4 of the TXBT Magelis Product Line Reference
Manual for more information.
Graphic Magelis 3 - 15
Operating principle
Other possible loading operations for the TXBT:
See section 14 and 15 in this chapter.
3.2.3
Operating mode
Operating mode is used for on-line control of the control system:
• Page display
• Entry/Modification of the process's parameter values
• Process control (discrete)
• Printing of form pages,
• Consulting and acknowledging alarms
• Consulting the alarm log
• Accessing the terminal configuration (printer link, time-stamp link, link with the control system, languages)
• Accessing the terminal's self-diagnostic functions (keypad, display unit, etc.) (TXBT only).
CAUTION
EQUIPMENT DAMAGE HAZARD
Pressing the MENU key allows the inexperienced and untrained operator to accidentally display the wrong page, modify the terminal configuration, or lose the messages and alarms on the screen. This can lead to confusion, panicking, and, as a consequence, loss of control over the machine. It is strongly recommended that the PLC be programmed to lock the MENU key as well as the other currently unused keys in order to prevent this from happening.
3 - 16
Failure to follow this instruction can result in injury or equipment damage.
Operating configuration
NOTE: See chapter 4, section 4.3, on service instruction from the terminal and communication protocol in use.
Graphic Magelis
Operating principle
Running with a PLC's RS 485 type console connector
(Figure 3-6)
• Terminals with UNITELWAY protocol
• PLC: TELEMECANIQUE PLC with an RS485 type console connector interface (type TSX07, TSX37, TSX57 ...)
• Type of link: RS485 single-point
• Protocol: UNITELWAY
Figure 3-6: PLC's RS 485 Console Connector
RS485 3
Running on a PLC communication network (Figure 3-7)
• PLC: PLC supporting the terminal's communication protocol,
• Type of link: RS422 or RS485 (multipoint),
• Protocol: multipoint protocol (UNITELWAY, FIPWAY)
(refer to the TXBT manual).
Figure 3-7: PLC Communication Network
RS485
Other equipment
Graphic Magelis 3 - 17
Operating principle
Running with direct point-to-point link to the control system
(Figure 3-8)
• The control system designates a system other than the PLC.
• Type of link:
RS422 or RS485
RS232.
• Protocol: depending on the control system.
Figure 3-8: Direct Link to Control System
RS422/RS485
RS232
Control system
Running on a PLC using Modbus Plus (Figure 3-9)
• PLC: Any PLC supporting Modbus Plus
• Type of Link: Modbus Plus
• Protocol: Modbus Plus
Figure 3-9: PLC using Modbus Plus
Modbus Plus
PLC PLC PLC
3 - 18 Graphic Magelis
Operating principle
3.2.4
Confidential mode, password management
To restrict reading and writing of certain data to only those authorized, you can protect access to pages or fields by means of passwords.
CAUTION
EQUIPMENT DAMAGE HAZARD
The XBT should only be installed and used by the authorized personnel that have been assigned the appropriate confidential mode PASSWORDS by the project manager.
Failure to follow this instruction can result in injury or equipment damage.
If the right passwords are not entered, this protection system will then:
• Prevent access to application or system pages. The protected pages are no longer accessible from a static or dynamic function key (the associated labels no longer appear on the terminal screen) and they do not appear in the list of pages.
• Inhibit writing in dynamic variable fields: alphanumeric variable field, linear/rotary potentiometer, linear/rotary switch, image box. The protected fields are displayed as if they were configured in read only mode. The labels associated with the dynamic function keys and enabling access to these fields are no longer displayed on the terminal screen.
NOTE: When a page is protected, access to all the fields of this page is non-protected. The protections that could have been defined with XBT-L1000 are ignored.
3
Graphic Magelis 3 - 19
Operating principle
There are three different passwords: A, B and C.
The value of these passwords is defined in XBT-L1000,
Configuration/Terminal parameters. When the Configure
Terminal parameters window appears, select the Password button to show the Passwords dialog box (Figure 3-10).
Each password is a string of 4 alphanumeric characters
(default value 1111).
Figure 3-10: Passwords Dialog Box
3 - 20
Exit from the confidential mode can be either manual or automatic:
• manual: the operator explicitly requests an exit from the confidential mode,
• automatic: a timer which can be programmed to a value between 1 and 60 minutes is used by the terminal to automatically exit the confidential mode.
Configuration of the parameters for automatic exit of the confidential mode can be performed via the terminal system page “Passwords/ advanced properties”.
When exporting an application to a terminal, the properties are set to the following values: automatic exit from confidential mode: NO.
NOTE: To ensure that your passwords remain confidential, there is
no way of consulting the value from the Magelis terminal.
The only way of finding out the value of a lost or forgotten password is to consult the application using XBT-L1000.
Operating principle
A page or field can be protected by password A and/or B and/or C.
Depending on whether the user has filled out passwords A, B or C on the terminal, he will be able to access the corresponding pages and fields.
Graphic Magelis
Operating principle
Page or field number Protection defined in XBT-L1000
1 none
2
3
4
A
B
A, B
5
6
A, C
A, B, C
• If only A has been entered, the user will be able to access pages or fields 1, 2, 4, 5 and 6.
• If only B has been entered, the user will be able to access pages or fields 1, 3, 4, and 6.
• If C has been entered, the user will be able to access pages or fields 1, 5, and 6.
This operating principle enables protection perimeters to be defined completely free (Figure 3-11).
3
Figure 3-11: Hierarchy Principles
Examples:
C
B
A
A
B
B
A
C
C
The status line informs the user of the passwords entered.
Password entry
Press the MENU or SYST key to display the system page on terminals with keyboard and press the status touch zone then
MENU or SYST for touchscreen terminals (Figure 3-12).
Graphic Magelis 3 - 21
Operating principle
Figure 3-12: System Page
Press the dynamic key (or the touch zone) associated with the
Password icon, to display the Password system page.
3 - 22
Press the dynamic key associated with the Password icon or press the corresponding touch zone on touchscreen terminals.
• Enter the password using the alphanumeric keys and then confirm with ENTER.
The password level appears in the lower strip.
The SYST indicator light comes on.
Disabling the password manually
• Go to the password system page.
• Press the dynamic key corresponding to locking/unlocking of protection mode
(barred key).
The SYST indicator light goes out.
NOTE: Manual disabling of password is available even if automatic exit from confidential mode has been configured.
Graphic Magelis
Page display
3.3
Page display
3.3.1
Display at power up
For the XBTs
When the terminal is switched on, it automatically displays the following information:
• Reference and version of the embedded software,
• Reference of the software downloaded by XBT-L1000.
Then, depending on the configuration chosen when the application was created with XBT-L1000, the terminal will display either:
• an application page that can be selected with XBT-L1000
(see below),
• the MENU page.
This page, displayed at power up, will then be accessible using the
HOME keys.
3
Graphic Magelis 3 - 23
Page display
For the TXBTs
When the terminal is switched on, the home screen appears if the terminal contains no Magelis graphic application.
Customizable screen background
3 - 24
• Home screen background
The screen background can be replaced by simply replacing the TXBT.BMP file in the ....\TXBT\TOOLS directory. The file definition must be 640x480, 256 colors).
The functions possible from the home screen are started using dynamic keys.
• Running the Magelis graphic R2 application.
The Magelis graphic application is run with key R2.
Depending on the configuration chosen when creating the application with XBT-L1000, the terminal displays either:
An application page, or
A home system page.
Graphic Magelis
Page display
• Access to Windows 95, running an application
The CTRL+ESC keys are used to start an application.
• Closing the home screen
The home screen cannot be iconized and keys ALT+R4 are used to close it.
• Setup: The home screen specifies the type of transfer, which can be configured: see TXBT Manual, section 3.3.
Selection of the default page to be displayed with XBT-L1000
To select the default page, the procedure is as follows:
• Select the Configuration/
Terminal Parameters menu
• Select the default page to be displayed.
3
Graphic Magelis 3 - 25
Page display
3.3.2
Displaying a page using the directory of pages
Display the Menu system page using the MENU key
(Figure 3-13) or the status touch zone then the MENU zone on touchscreen terminals.
Figure 3-13: Displaying a Page Using Directory of Pages
Press the dynamic key (or touch zone) associated with the List of
pages icon.
Select the required page with the up and down arrow keys.
3 - 26
Confirm access to the page with the right arrow key.
Graphic Magelis
Page display
3.3.3
Displaying a page using its number
Go to the list of pages (see section 3.3.2).
Press the dynamic key associated with the Page number text or select the touch icon on touchscreen terminals.
or
Display the list of pages by pressing the MENU key (Figure 3-14).
Go to the page number entry field by pressing the MOD key.
Enter the page No. and press ENTER to confirm.
Figure 3-14: Displaying a Page Using its Number
Directory of pages
N
°
: 1021
3 password
NOTE: You can return to the previous page (main menu) by pressing ESC.
Graphic Magelis 3 - 27
Page display
3.3.4
Displaying a page by means of a dynamic function key
The dynamic function keys (Rx) are associated with a page and can be configured to make the terminal change from one page to another. The function key is configured using the XBT-L1000 software and allows a page to be displayed directly (Figure 3-15)
Figure 3-15: Displaying a Page Using Dynamic Function Key
Maintenance level 1
Maintenance level 2
Maintenance level 3
Rx
Maintenance level 2
3 - 28
On touchscreen terminals, a page can be selected by directly pressing on a touch zone associated with this page.
Graphic Magelis
Page display
3.3.5
Displaying a page by means of a static function key
A static function key (Fx) remains the same for all the application pages. The function key is configured using the XBT-L1000 software and allows a page to be displayed directly (Figure 3-16).
Figure 3-16: Displaying a Page Using a Static Function Key
3
Maintenance level 1
Maintenance level 2
Graphic Magelis 3 - 29
Page display
3.3.6
Displaying a page using a word from the PLC
It is possible to display a page using a word in the PLC. A PLC word must be allocated in the dialog table. In this table, a word is reserved in which the program writes the number of the page to be displayed. Refer to Chapter 2, Section 2.2 for the word coding procedure.
Example:
Display of the Maintenance page (application page No. 25) by the PLC
The terminal periodically reads the dialog table in the PLC and displays the desired page; no program has to be written in the PLC to manage communications (Figure 3-17).
Figure 3-17: Display of the Maintenance Page by the PLC
PLC Program
If input 10025 is at 1, display Maintenance page (page No. 25)
Maintenance
Dialog table
25 "Page number to be processed" word
3 - 30 Graphic Magelis
Entry/modification
3.4
Variable fields
See also: Variable adjustment on TXBT, Section 3.12.
Variable fields are zones enabling:
• the display of values reflecting the control system status: status of a word bit, single or double word, floating word, character string, or,
• the entry of parameters allowing the control system to be controlled: modification of word bits, single, double or floating words, character string.
The display format may be binary, decimal, hexadecimal, numbered list, or an ASCII character string.
3
Temperature =
Field
When creating the application with XBT-L1000, controller variables are associated with the variable fields and the dynamic graphic objects.
For the XBT-Fs
Whatever the protocol, the accessible variables are single words, double words, floating words, and word bits.
For the TXBTs
In the case of XWAY protocols, the accessible variables are:
• single words, double words, floating words, word bits
• local and remote input/output bit
• system bit
• step bit
• step macro bit
• step macro input step bit
• step macro output step bit
In the case of a protocol other than XWAY, the accessible variables are singlel words, double words, floating words, and word bits.
Graphic Magelis 3 - 31
Entry/modification
The XBT-L1000 software makes it possible to define different field properties (Figure 3-18).
Figure 3-18: Properties of Alphanumeric Field Dialog Box
3.4.1
Accessing a field
Accessing the various fields in a page
The MOD key allows you to select:
• The first field on the page or
• The last field entered (the last field whose entry was confirmed by ENTER).
The selected field is framed with a dotted box and the cursor is displayed in the variable field.
The arrow keys allow you to move from field to field.
When you are positioned in the desired field, press the MOD key to enable the input mode.
On touchscreen terminals, press the touch icon of the selected field for accessing the fields directly.
3 - 32 Graphic Magelis
Entry/modification
NOTE: When configuring touch zones with XBT-L1000, the objects must be aligned on the XBT-L1000 default grid, otherwise the operator may be unable to select certain objects. If nothing has been entered after one (1) minute, the input mode is cancelled.
NOTE: The order in which the page fields go to entry mode depends on the object alignment under XBT-L1000.
Accessing a field by means of dynamic function keys
It is possible to select a field on a page by configuring a dynamic function key (Rx) associated with the page to select the field.
The same application procedures has access to an application page using the Rx key.
3
Access to a field using the TXBT mouse
A field can be selected using the TXBT mouse by positioning the pointer on the field and clicking.
Request for entry on the initiative of the PLC
The PLC can request an entry in a page variable field (example: request for a set point).
The word “Field number to be entered” is reserved in the dialog table. The program writes the number of the field to be entered in this word. This number is provided by XBT-L1000, Display/Field number menu.
Refer to section ??, for coding of this word.
NOTE: Each field is automatically numbered by XBT-L1000. Numbering starts by number 1 for each page. The PLC program must thus check that the number of the page displayed is correct before requesting a field entry.
Graphic Magelis 3 - 33
Entry/modification
3.4.2
Field entry
Operating mode
Numeric fields
Use the 0 to 9, A to Z and +/- (+/- select, + by default) keys to enter alphanumeric values.
Use the ENTER key to confirm the input value within the fields and send the results to the PLC.
Use the horizontal arrow keys to move from one digit to another within the field.
Deleting characters
The DEL key deletes the character to the left of the fixed digit.
Canceling the entry
You can cancel the entry in progress by pressing ESC; no modification is made to the field.
Entering graphic fields
Modification of a graphic field
Once positioned on the object required, press the MOD key to switch to entry mode or press the touch zone of the object.
Use the up, down, right and left arrows (LEDs flashing) to modify the value of a field.
Press the ENTER key to validate field entry.
3 - 34 Graphic Magelis
Entry/modification
3.4.3
Field Characteristics
Protecting fields
Depending on the selected configuration, certain fields of the application page may not be write-accessed in confidential mode.
Access management for entry to a variable field is ensured by a system with several levels of protection. The XBT-L1000 software can be used to define the various properties of the field
(Figure 3-19).
Figure 3-19: Alphanumeric Properties Dialog Box
3
Variable display rules
• A value that cannot be displayed is represented by # characters (overflow value).
• A value not filled out by the PLC is represented by ? characters.
• A write-only variable is represented by * characters.
Graphic Magelis 3 - 35
Entry/modification
Numbered list
The XBT-L1000 software allows a string of text to be assigned to each value of the variable associated with the field
(Figure 3-20).
Figure 3-20: Numbered List Dialog Box
Example: A field (%MW10) that accepts two values with two associated strings of text (0: CLOSE 1: OPEN).
If you select OPEN using the arrow keys, and confirm by pressing
ENTER, the %MW10 word will take the value 1 in the PLC.
Inversely, if the PLC writes the value 1 on %MW10 the OPEN text will be displayed.
Data types
Word bits, single words, double words, floating point words, character strings.
Alphanumeric display format
Binary, integer, decimal (five digits maximum after the decimal point), hexadecimal, ASCII, text numbered list.
Thresholds
Four thresholds can be set for a variable field: Min (minimum), L
(low), H (high), and Max (maximum).
The value of these thresholds can be:
• constant,
• variable: the value is read when the page is displayed
(read-only).
Min and Max are the absolute display limits for the variable, L and H are its intermediate thresholds (pre-alarm, etc.).
3 - 36 Graphic Magelis
Entry/modification
The value of a variable can be in one of five posssible value zones:
• Value > Max
• H < Value < Max
• L < Value < H
• Min < Value < L
• Value < Min
For each of these zones, the object is given a particular color according to what was defined in XBT-L1000: variable color for alphanumeric objects, dial color for vu-meters, etc. (Figure 3-21).
Figure 3-21: Alphanumeric Properties Dialog Box 3
Color red: max. limit
Color blue: correct value
Color red: min. limit
If the operator enters a value which is > Max or < Min, it is not sent to the controller and a warning message appears.
Graphic Magelis 3 - 37
Entry/modification
Immediate write
Immediate write in a field consists in incrementing or decrementing the field value. It is performed by pressing the shift + “up arrow” key or shift + “down arrow” key on terminals with keyboard or by pressing the touch zones +1 and -1 on touchscreen terminals. The value is transmitted to the PLC each time the key is pressed.
To configure the variables with XBT-L1000, select the Option/
Access tab.
3 - 38
This entry mode is used by the operator to modify a field value in a continuous manner in order to:
• prevent sudden skipping from one value to another,
• view the result of an action "in real time" (adjustment, positioning, etc.).
Graphic Magelis
Alarms
3.5
Alarms
3.5.1
Principle
Alarms are triggered and then displayed when a word bit in the
PLC(s) is ON.
Several alarms may be active simultaneously, and are stored by the terminal in the alarm list.
WARNING
UNINTENTIONAL EQUIPMENT OPERATION
The XBT does not support any type of processor nor machine control in association with alarms. It is the designer's responsibility to consider programming PLC logic to account for programmed alarms.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
3
Example: display on an XBT-F terminal:
•
ALARM on touchscreen terminals
Refer to section 3.7 for the detailed description of the alarm list.
Alarm indicating
• "Alarm" indicator light. The "Alarm" indicator light keeps the operator constantly informed of the alarm list status:
• Off: the current list of alarms is empty.
• On: the list contains alarms that have already been displayed.
• Flashing: the list of alarms contains new alarms.
• On the application pages
The designer can place an alarm bar, corresponding to the last alarm that has occurred, in the alarm pages. This bar is updated whenever a new alarm occurs, whatever its type
(with or without a required acknowledgement) and priority. If several alarms occur simultaneously, the highest priority alarm is displayed; if there are no alarms, the bar remains displayed but is empty.
Graphic Magelis 3 - 39
Alarm page
Name of the alarm
Appearance date and time
Code for appearance (ON),
Acknowledgment (ACK),
Disappearance without acknowledgment (OFF)
Number of the bit at the origin of alarm triggering
Absent: no alarm or alarm acknowledged (ACK)
Steady red: alarm set to OFF
Flashing red: alarm set to ON
Printing on line: See section 3.10.3.
Direct display of the alarm indicated in the strip (without displaying the alarm list) is performed by pressing the keys shown opposite.
On touchscreen terminals, press directly the alarm strip.
• On-line printing: see section 3.10.4.
• Alarm bit: see chapter 3, section 3.3.3.2.
• Alarm relay: see section 3.5.6.
3.5.2
Alarm page parameters
Alarm pages have various parameters:
• A 32-character maximum message. This message will be displayed in the alarm strip, the alarm list and the history that will be printed,
• Text, variable fields, static graphic objects used to indicate the fault and the relevant corrective actions.
Conveyor fault
Turn power off
Remove jammed part
Restart
Variable fields
Static graphic objects
A priority
A request for acknowledgment
An alarm relay command
Assignment to a group of alarms
A type of alarm page appearance
Printing on line
3 - 40
Graphic Magelis
Alarms table
NOTE: The alarm page can remain empty on request of the designer. The management of alarms is then provided by messages only.
• a priority,
• a request for acknowledgement,
• an alarm relay command,
• an assignment to a group of alarms,
• a type of action on alarm appearance (display, printing, storage).
Alarm table
• A word bit is associated which each separate alarm. All these words make up the alarm table which is part of the dialog table.
• A terminal can process the alarms from several PLCs.
• The alarm table can be distributed between several of the automated process's PLCs.
For each PLC, the alarm bits are distributed in packets of 16 alarms, i.e., "n" words of 16 bits per PLC.
The terminal can accept up to 32 words depending on the type of terminal.
3
PLC dialog table containing 5 alarm words and 2 acknowledgment words
PLC 1 dialog table containing 3 alarm words and 2 acknowledgment words
2
PLC 2 dialog table containing 4 alarm words and 2 acknowledgment words
3
2
4
5 Alarm words
2 Acknowledge words
Any given alarm may be triggered by several different bits that may belong to different PLCs.
Graphic Magelis 3 - 41
Alarm group
3.5.3
Alarm group
Alarm groups can be configured in order to group together alarm pages in modules.
An alarm group is a set of alarms identified by different color
attributes per group for the appearance, disappearance and acknowledgment statuses. There are 16 groups numbered 1 to 16.
Each group is identified by an 8-character name allowing quick identification by the operator of a part of the machine or of the installation.
Example:
Group1: cracker1 colors defined:
• appearance: flashing red
• disappearance: steady green
• acknowedgment: flashing cyan
Group2: c onvoy.4
colors defined:
• appearance: steady yellow
• disappearance: flashing magenta
• acknowledgment: flashing blue
According to the colors, the user can quickly identify the control system unit in which the fault has occurred (example: cracker1).
In the list of alarms, it is possible to select:
• display of the alarms from a single group out of the 16.
• display of the alarms from the 16 groups.
The dynamic key or the touch zone associated with the ACK ALL icon is used to acknowledge the alarms of the group(s) present on the screen (see section 3.5.7).
3 - 42
Graphic Magelis
Alarm priority
3.5.4
Display priority in the alarm list
A priority can be allocated to each alarm page using the XBT-L1000 software.
The alarm pages can take different priorities. 16 levels are possible from 1 to 16, with the lowest display priority being priority No. 16.
Alarm list storage principle:
1. Alarms not acknowledged and then alarms already acknowledged, i.e. alarms which were already present the last time the list of alarms was displayed.
2. Alarm priority (1 at the top, 16 at the bottom).
3. When the alarm priority is the same, they are stored in such a way that the oldest one is displayed first. The possible cause of a series of faults can thus be identified rapidly.
3
The list of alarms is displayed after pressing the SHIFT + ENTER keys or the status touch zone and then ALARM for touchscreen
terminals.
The latest alarm displayed appears in the “latest alarm” strip.
Alarm display principle
When an alarm appears:
• The ALARM indicator light flashes. The alarm is stored in the alarm list. The alarm can be acknowledged by the operator directly on the application page by pressing the ENTER key or for touchscreen terminals.
• The alarm relay is closed (if this function is selected).
• The alarm strip is updated.
The alarm can be consulted in the alarm list (see Section 3.5.7).
Graphic Magelis 3 - 43
Alarm acknowledgment
3.5.5
Acknowledging alarms
When designing pages, it is possible to define whether the alarm page should be systematically acknowledged or not. These 2 types of alarms are managed in the following way:
1 - Alarms which must be acknowledged
An alarm which must be acknowledged remains in the list of alarms until it is acknowledged by the operator, even if the cause of the fault is no longer present (the alarm bit is back to 0). Its status is then OFF.
Advantage: transient faults are isolated (instability of a discrete sensor for example).
2 - Alarms with optional acknowledgment
An optional acknowledgment alarm disappears from the list as soon as the cause of the fault is no longer present (the alarm bit is back to 0), whether the alarm has been acknowledged or not.
Advantage: the display is not exclusively dedicated to faults that are considered minor for the application.
Alarm acknowledgement from the alarm strip
Press the ENTER key on the terminal or the touch zone on
touchscreen terminals to acknowledge the alarm displayed in the alarm strip.
The alarm message switches to ACK status.
NOTE: The alarm strip can be displayed on alarm pages.
Acknowledgement will thus be effective on the strip alarm and not on the alarm displayed.
Alarm acknowledgement from the list of alarms
Press the ENTER key on the terminal to acknowledge the alarm selected in the list. The alarm message switches to ACK status. The dynamic key or the touch zone associated with the ACK ALL icon is used to acknowledge the alarms from the group(s) displayed.
3 - 44
Graphic Magelis
Alarm relay
3.5.6
Alarm relay command
The alarm relay option is available for each alarm.
The alarm relay energizes as soon as an alarm defined with the
"alarm relay" option is triggered.
The relay deenergizes as soon as all the active alarms defined with the "alarm relay" option have been acknowledged by the operator(ACK), or have disappeared.
NOTE: In the event of a power loss to the termial, the alarm relay deenergizes.
3.5.7
Description of the alarm list
The alarm list includes:
• the active alarms which are present but not acknowledged by the operator (ON),
• the active alarms acknowledged by the operator (ACK),
• alarms with mandatory acknowledgement and which have not been acknowledged but for which the triggering cause is no longer present (OFF).
3
The alarm list is refreshed whenever an alarm appears or disappears. The alarm list remains displayed awaiting a user action.
Number of the bit at the origin of alarm triggering
(see alarm bit
Section 5.1)
Name of the alarm
Appearance date and time
Code for appearance (ON)
Acknowledgment (ACK)
Disappearance without acknowledgment (OFF)
Absent: no alarm or alarm acknowledged (ACK)
Steady red: alarm set to OFF
Flashing red: alarm set to ON
Graphic Magelis 3 - 45
Alarm list
The function key associated with the "group" icon is used to select an alarm group or all the alarms.
The status line indicates the alarm group and the equipment connected (PLC) which triggered the alarm selected in the list.
Possible actions in the alarm list
ENTER : to acknowledge an alarm, the alarm status becomes ACK.
ACK ALL: allows overall acknowledgment of all the alarms or those of the selected group.
Up and down arrows: to navigate in the alarm list.
SHIFT + up and down arrow or double up/down arrows on
touchscreen terminals: previous page/next page.
Right arrow:to display the alarm page corresponding to the selected alarm.
PRINT: to print the alarm list.
3.5.8
Alarm display by the PLC
The dialog table enables the dialog between the PLC and the terminal. This table contains words which are reserved for alarm display. Refer to chapter 4, section 4.2 for the coding of these words.
3 - 46
Graphic Magelis
Alarm history log
3.6
Alarm history log
3.6.1
Principle
The terminals can manage an alarm page log. The alarm descriptions and state, the equipment data, the date and time status are stored in this log. The alarms are stored one after the other, and when the log is full, the oldest alarms are overwritten by the most recent ones.The log recording capacity is 500 events.
Each alarm event:
• Appearance
• Acknowledgment
• Disappearance is recorded and time-stamped.
The following functions can be performed:
• On the PLC's initiative:
Printing the alarm log
Clearing the alarm log
• On the operator's initiative:
Displaying the alarm log
Printing the alarm log
Clearing the alarm log (in confidential mode)
The log is useful for analysing the sequence of events which has led to a given machine state.
3
Graphic Magelis 3 - 47
Alarm history log
3.6.2
Displaying the alarm history log
The alarms are shown with the most recent alarm displayed first.
The events relative to each alarm are: appearance, acknowledgment, clearing.
MENU: To access the alarm log.
Up and down arrows: To scroll through the alarm log.
SHIFT + up and down arrow or double up/down arrows on
touchscreen terminals: previous page/next page.
PRINT: To print the alarm log.
ESC: To return to the previous page.
3.6.3
Clearing the alarm history log
• At the operator’s initiative
1. Prior display of the history.
2. Press the key or the touch zone Delete history.
3. Validate history clearing: the complete history is cleared.
NOTE: History clearing can be restricted to confidential mode. For this, protect the system page “Delete history” by a password.
• On the PLC initiative
The alarm history is cleared by means of the history reset command word in the dialog table (see chapter 4, section 4. 2).
3.6.4
Printing the alarm history log
• On the operator's initiative
Press the PRINT key and select "Log".
The alarm log is printed sequentially, with the most recent alarm printed first.
• On the PLC's initiative
The alarm log is printed by means of the print command word in the dialog table (see chapter 4, section 4.2).
The alarm log is printed sequentially, with the most recent alarm printed first (Figure 3-25).
3 - 48
Graphic Magelis
Alarm history log
Figure 3-25: Print Format
ALARM HISTORIC !ON (Valid) !ACK
!OFF (Invalid) !EQUIPMENT !GROUP
24/07/97
1024:Text of alarm .
!2407 12:00:00 ! – ! – !MASTER
1024:Text of alarm .
!2407 12:01:00 !2407 12:01:00! –
*1024:Text of alarm . !2407 12:04:00 ! –
!MASTER
!2407 12:05:00 – !MASTER
!CONVEYOR
!CONVEYOR
!CONVEYOR
3
The recommended print format is 132 columns. The following are printed on a single line for each alarm:
• alarm number and page name
• appearance (ON), acknowledgement (ACK), disappearance
(OFF) date and time, alarm group.
An asterisk * at the beginning of a line indicates that information has been lost in the previous line. This happens when the log overflows, in which case the oldest events are overwritten by the most recent events.
Graphic Magelis 3 - 49
Process control
3.7
Process control using function keys
The terminals are used to control the control system using the static
(Fx) or dynamic (Rx) function keys on terminals with keyboard and the touch zones on touchscreen terminals. There are two types of commands:
• Momentary contact
• "Push on/push off" toggle
3.7.1
Momentary contact command
The system is actuated by pressing a function key or the touch zone, which starts an action; if the key or the touch zone is released the action stops.
Example: Controlling a motor
Control bit set to "1"
0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0
"1"
Motor
( )
"1"
3.7.2
Push on/Push off toggle command
The control system is actuated by pressing the function key or the touch zone and the action runs; the action is stopped by pressing the function key or the touch zone again.
Example: Conveyor belt advance command
1 = Push
0 = Next Push
0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0
"1"
Conveyor
( )
"1"
3 - 50
Graphic Magelis
Process control
Control using static function keys
When creating the application, a word bit, defined automatically by the dialog table, is associated with each momentary contact and
"push on/push off" toggle static function key. This word bit will be in the Master PLC.
Control using dynamic function keys
When creating the application, the following are associated with each momentary contact and push on/push off dynamic function key:
• One label comprised of 1 or 2 graphics,
• A word bit whose PLC address must be declared when configuring with XBT-L1000.
Dynamic function keys may be configured to communicate with any
PLC attached to the terminal.
Command using the TXBT mouse
The dynamic function keys can be controlled by positioning the pointer on the corresponding key label and clicking.
Assigning static function keys in the dialog table
The dialog table enables the communication between the PLC and the terminal. In this table, one word is reserved for providing the status of the function keys in the form of a word bit (bit at 1 = key pressed), refer to chapter 4, section 4.2 for the word coding procedure.
3
See chapter 5, section 5.3.6.
Graphic Magelis 3 - 51
Windows 95 applications
3.8
Running Windows 95 applications on the TXBT
The TXBT terminal can be used to run Windows 95 applications installed on the terminal (for example the calculator). If the Magelis application is already running, it will continue to work in the background, the pages are refreshed and the alarms monitored;
The software can be started up in 2 ways.
Startup with a Windows 95 command
Program startup
1. Click on the Start button (or use the CTRL+ESC keys), then select Program.
2. Select the program to be executed
Program startup using the Run command
1. Click on the Start button (or use the CTRL+ESC keys) and then Run.
2. In the Open zone, type in the location and name of the program you want to start.
If you cannot remember the location or name of the program file, click on Browse.
Running using the Rx dynamic function keys
The executable program can be run by pressing an Rx key (for example the calculator).
Configuration with XBT-L1000
For example: starting the calculator with key R4 as soon as the measurement is displayed.
1. Select the page linked to the dynamic key in the Page Tree
Structure window.
2. The configuration screen appears.
3 - 52
Graphic Magelis
Windows 95 applications
3. Select the dynamic function key to be assigned.
R4
The configuration dialog box appears.
4. Select Run Application.
5. Type in the executable program path in the “Open” editing field.
NOTE: Executable program path
This is the path (drive, directory/sub-directories) on the
TXBT terminal and not the path on the PC equipped with
XBT-L1000.
If the location of the executable program on the TXBT is changed, startup will be impossible.
Example: D:\WINDOWS95\CALC.EXE
3
Graphic Magelis 3 - 53
Locking keys
3.9
Key locking by the PLC
In order to prevent the operator from performing certain functions depending on the control system status, the PLC is able to lock out the terminal. There are 3 reserved words in the dialog table that allow various keys to be locked. These keys are:
• static function keys
• system keys
• numeric keys
Word bit at 1 = key locked
Refer to chapter 4, section 4. 2 for the word coding procedure.
CAUTION
EQUIPMENT DAMAGE HAZARD
Pressing the MENU key allows the inexperienced and untrained operator to accidentally display the wrong page, modify the terminal configuration, or lose the messages and alarms on the screen. This can lead to confusion, panicking, and, as a consequence, loss of control over the machine. It is strongly recommended that the PLC be programmed to lock the MENU key as well as the other currently unused keys in order to prevent this from happening.
Failure to follow this instruction can result in injury or equipment damage.
3 - 54
Graphic Magelis
Locking keys
Example:
Locking the F1 and F2 static function keys in the application example, will start up an action in the PLC.
• The function keys must be locked when the following pages are displayed:
Menu
Dough preparation (preparation help)
Dough baking (baking help)
• The function keys must be unlocked when the maintenance page is displayed.
The terminal periodically reads the dialog table in the PLC and locks the keys whose word bit is at 1.
3
F1 and F2 locked
(bit = 1)
Dialog table
1 1
See chapter 5, section 5.3.7.
Graphic Magelis 3 - 55
Printing
3.10
Printing
3.10.1
General
The following information can be printed:
• Printing at the operator’s initiative
Alarm log
List of active alarms.
Form pages,
Screen hardcopies (TXBT only),
Terminal references.
The PRINT key is used to send the command.
Active window capture (TXBT only)
The SHIFT+ALT+PRINT keys are used to send the command.
• Printing at the PLC’s initiative
Alarm log
Free format printing
On-line alarm printing
Form page printing.
NOTE: The recommended printing format for the “Alarm history printing”, “On-line alarm printing” and “Alarm list printing” functions is 132 columns. On a 80-column printer, the “alarm group” and “equipment” information is not printed out.
3.10.2
Print set-up
Case of XBT Terminals
• Printer selection
A serial printer must be used and no declaration in XBT-
L1000 is required. For connection, refer to the service instructions.
• Printer set-up
Printer setup is performed with XBT-L1000 or locally in the terminal. The System menu is used to consult and configure the printer parameters. The printing formats are entered on
XBT-L1000 via the Configure/Parameters menu of the
Printer terminal.
3 - 56
Graphic Magelis
Printing
NOTE: If the printer has been configured with fewer columns than the required printing format, the result will be truncated.
Characters whose ASCII code is < 32 and > 125 will be replaced by “.” characters when printed. Except for free format and form printing.
Case of TXBT terminals
• Printer selection
A parallel printer must be used.
1. Select the Start menu (you can use the CTRL+ESC keys to call up the Start menu).
2. Select the Settings/Printers command
3. Click on the Add printer icon.
4. Execute the Windows 95 procedures and choose LPT1 as the printer port. For connection, refer to the TXBT manual.
• Printer setup
On the TXBT, printer setup is that of Windows 95.
The printing setup screen can be accessed:
Either directly with Windows (Start menu, etc.)
In the Magelis application, using the “System menu”
(SHIFT-MENU) then “Printer parameters” (R5)
3
3.10.3
Stop printing
This function is accessed with the system menu. Any printing in progress (log, continuous, etc.), even if the printer is faulty, will be stopped without any request for confirmation; i.e. the print buffer will be emptied and the print queue will be cancelled.
Graphic Magelis 3 - 57
Printing
3.10.4
Continuous printing of an alarm page
The option must be selected when the page is created using
XBT-L1000 by selecting the "print" option (Figure 3-26).
Figure 3-26: Properties Dialog Box
3 - 58
At each dialog table read cycle, the "printable" alarms are printed with the alarm name.
A header is printed containing the page number and name, and the printing date and time (Figure 3-27).
Graphic Magelis
Printing
Figure 3-27: Print Format
ALARM
24/07/97 12:01:30
!ON (Valid) !ACK
!OFF (Invalid) !EQUIPMENT !GROUP
1024:Text of alarm .
!2407 12:00:00 ! –
1024:Text of alarm .
! –
1024:Text of alarm .
! – ! –
! –
!2407 12:01:00! –
!MASTER
!MASTER
!2407 12:04:00 – !MASTER
!CONVEYOR
!CONVEYOR
!CONVEYOR
3.10.5
Printing the list of active alarms
Press the “Print” key or the PRINT touch zone on display of the “List of alarms” page.
The list of alarms is printed as it is at the time the operator requests the printout. If alarms occur during printing, they will not appear in the list (Figure 3-28 on the next page).
3
Graphic Magelis 3 - 59
Printing
Figure 3-28: Print Format
ALARM
24/07/97
!ON (Valid) !ACK
1024:Text of alarm .
!2407 12:00:00 ! –
1031:Text of alarm .
!2407 12:01:00 ! –
1025:Text of alarm .
!2407 12:04:00 ! –
!OFF (Invalid)
! –
! –
! –
!EQUIPMENT !GROUP
!MASTER
!MASTER
!MASTER
!CONVEYOR
!CONVEYOR
!CONVEYOR
3.10.6
Printing a form page
When form page printing is requested by the user or the control system the object values included in the form page are refreshed and sent to the printer.
Control codes specific to the printer (bold, italic, etc.) can be defined in form pages to enhance their format.
3.10.7
Printing the alarm Log
See section 3.7.4.
3.10.8
Free format printing
Free format printing consists of sending the data contained in the free format printing table, located after the dialog table:
• To the terminal's printer port
• On the PLC's initiative
A dialog table word is used to manage the dialog. Refer to chapter 4, section 4. 2 for the word coding procedure.
3 - 60
Graphic Magelis
Terminal configuration
3.11
Terminal configuration
The terminal configuration parameters can be modified on the terminal directly. They are then saved in the PCMCIA card without using XBT-L1000. However, any modification performed in the terminal cannot be retrieved by XBT-L1000 when importing an application.
The terminal configuration function is accessible from the system menu and is used for consulting or modifying the following parameters:
• terminal data and time and format,
• language,
• screen parameters,
• printer parameters,
• Printer <-> Terminal line parameters.
Press the SYST key or the status touch zone then SYST on touchsreen terminals to display the system menu. If access is protected by a password, enter it (see section 3.2.4).
Figure 3-29: Configuration Screen
3
Graphic Magelis 3 - 61
Terminal configuration
Parameter modification principle
1. Select the parameter by dynamic function keys or pressing the touch zones.
2. Depending on the type of parameter, the modification is performed using:
• Numeric keys
• Arrow keys (for parameter lists)
• Context keyboards displayed on touchscreen terminals.
3. Press ENTER to confirm the modification.
CAUTION
EQUIPMENT DAMAGE HAZARD
Since all alarms are always time/date stamped and the control program may rely on the XBT's real time clock, it is important to set or verify the XBT's date and time after every installation, repair, disassembly, shipment, or battery change.
Failure to follow this instruction can result in injury or equipment damage.
Terminal parameters
Terminal date and time
Time format: 24.mn.ss or 12:mn:ss,
Date format: DD.MM.CCYY or MM.DD.CCYY or CCYY.MM.DD.
Language
To change language: Select the language with the "up" and "down" arrow keys and confirm by pressing ENTER.
Screen
The brightness and contrast of the screen can be adjusted. For terminals with keyboard, the adjustments are identical to those performed using the keyboard keys.
On touchscreen terminals, brightness and contrast can be adjusted using the touch zones (depending on screen technology).
3 - 62
Graphic Magelis
Terminal configuration
Clear screen
A clearing page is provided on touchscreen terminals for de-activating the touchscreen pad in order to clear the screen surface. Simultaneously press the two opposite touch zones to re-activate the pad and exit the clearing page.
Printer
The printer setup parameters, except for the printer control codes used for the forms, can be modified.
Standby
Screens can be damaged if a steady image is displayed for a long time.
It is thus recommended to select the following in the “Terminal parameters” system page:
• Standby: YES
• Wait: 60 minutes.
NOTE: These parameters are initialized to the above values after exporting an application from the PC to the terminals.
3
Parameters of the operations line
• Case of the XBT terminal
The parameters displayed depend on the protocol and some may ormay not be modifiable.
Example: Case of the UNI-TELWAY protocol:
Bit rate: 300 bauds
Parity: even
Address: Master
Error ounter No. 1: 0
Error counter No. 2: 0
Error counter No. 3: 0
Error counter No. 4: 0
Counter reset by dynamic key.
• Case of the TXBT terminal
Protocol parameters
The following parameters are displayed:
Protocol name
Controller names and addresses (max. 15) and status of communications with them (if possible)
Graphic Magelis 3 - 63
Terminal configuration
TXBT local address
Four error counters
Last communication error that appeared
Counter reset by dynamic function key
• Application parameters
The following parameters are displayed:
Application reference and protocol used
Currently running application path: the application can be on the disk in this directory ....\TXBT\APPLI (default directory which can be changed) or on the PCMCIA memory card
Size of PCMCIA memory card (if installed)
The text of the last error which appeared (excluding communication error)
• Password
Declaration of password A, B or C
Printer line parameters
The following parameters are displayed by default:
Printer
Number of columns:
Automatic line skip:YES
Automatic line feed:
132
NO
XBT-Printer serial line
Baudrate (Bauds): 9600
XON/XOFF protocol:
Link:
Duplex :
Stop bits:
Data bits:
Parity:
NO
RS 232
Half Duplex
1 BIT
8 BITS
ODD
3 - 64
Graphic Magelis
Variables adjustment
3.12
Variables adjustment on the TXBT
• Principle
The TXBT can be used to adjust the variables of the connected PLCs.
Adjustment is available for the following communication
-
protocols:
UniTelway
IsaWay
Modbus
-
Fipway
Fipio
Modbus+
• Accessible objects XWAY Protocols
Internal word
Constant word
Internal word bit
Internal double word
Internal bit
Local input/output bit
Remote input/output bit
System bit
Step bit
Step macro bit
Step macro input step bit
Step macro output step bit.
Modbus and Modbus+
The objects accessible for adjustment are input and output
registers, input and output bits, bits extracted from registers.
Adjustment can be via the symbols if the symbol/identifier association has been loaded into the TXBT from
XBT-L1000.
• Loading the PL7 symbols file
Creation of symbols file
To create a symbols file with PL7:
1. Open the variables editor.
2. Select the File/Export command.
3. Select the disk and/or directory in which the file is to be stored.
4. Enter a filename: for example Appli.SCY
5. Select export mode.
3
Graphic Magelis 3 - 65
Variables adjustment
Symbols file transfer to TXBT
The resulting symbols file (e.g. Appli.SCY) must be positioned
on the TXBT terminal. To do this:
1. Select the Configuration/Enclosures menu... then select Files.
2. Select the file(s) (e.g. Appli.SCY) to be loaded onto the TXBT: the file is now a part of the Magelis application and will be exported at each export operation.
3. Select the Transfer/Export menu. The application is then exported, along with the selected file(s).
NOTE: The terminal does not check consistency between the PLC application and the symbols file loaded. A change made to this file will not be automatically accepted. For this, it has to be deleted and added again.
Access to adjustment
The adjustment function can be accessed using the dynamic function keys in 2 ways:
From the system page
To display this page, press the Menu key and then press the dynamic function key associated with the Adjustment item.
From an application page
The adjustment function can be run from an application page, by assigning the variable adjustment tool startup function to a dynamic function key associated with this page.
To configure this function with XBT-L1000:
1. Select the page linked to the dynamic key in the Page Tree
Structure window.
2. Select the Configuration/Function keys menu and the terminal front panel appears.
3. Click (double-click) on the dynamic function to be assigned.
4. Select Execution of Application
5. Click on Open and enter ADJUST.EXE.
3 - 66
Graphic Magelis
Variables adjustment
NOTE: The complete file path is required if the executable program is not in the APPLI directory.
• Procedure
1. Select the device.
2. Enter a variable (New/Edit R1),
3. Start continuous refresh (Refresh R6)
3
Modifying a value
1. Select the cell to be modified.
2. Enter the new value.
3. Confirm entry (Modify R3)
Deleting a variable
1. Select the row.
2. Delete the row (Delete R10).
Graphic Magelis 3 - 67
Variables adjustment
Display format
The data read in the controller can be displayed in the following
formats:
• Signed decimal integers
• Hexadecimal values (0 to 0xFFFFFFFF)
• Bit string
• One place floating point format
• ASCII character string. This contains 1 to 4 characters. The non-ASCII characters are represented by “.”.
List of variables
The list of variables displayed can be saved with key R4 into a
.ALS file and then called back with key R2. The list called up overwrites the current list.
NOTE:
1. If “???” are displayed, this means that the variable could not be accessed.
2. ESC goes back to the Magelis application previous page. Adjustment is not stopped, but its window moves into the background.
3. Alt-R4 (or click on X) stops adjustment.
4. The variable adjustment page is not password protectable.
Protection of the Adjust page from unwanted users can be accomplished by key-locking the system page.
3 - 68
Graphic Magelis
Variables adjustment
3.13
Variable adjustment on the XBT
• Principle
Adjustment is used to modify variables of connected PLCs from an XBT.
• Accessible objects
words,
double words,
word bits,
floating words.
• Access to adjustment
The adjustment function is accessible from the system pages.
An adjustment page is used to display:
• From 26 variables maximum on a 10" touchscreen product to
28 variables maximum on a 10" keyboard product,
• From 5 variables maximum on a touchscreen product to 6 variables maximum on a 5" product.
Up to 16 adjustment pages can be defined, i.e. 416/448 variables maximum for a 10" product (touchscreen/keyboard) and 80/96 variables maximum for a 5" product (touchscreen/keyboard).
3
Graphic Magelis 3 - 69
Variables adjustment
Example: Adjustment page on a 10" product.
3 - 70
Example: Adjustment page on a 5" product.
Graphic Magelis
Variables adjustment
• Creating or modifying the Adjustment page
When the Adjustment page is displayed, the operator can:
1. Select the variable to be modified in the list or add a new variable to this page or delete a variable from this page.
2. From the entry panel, modify the characteristics of the variable selected from the list, i.e.:
The variable type (in compliance with the protocol) which indirectly defines the variable format,
The variable address which must be comprised between:
[Min..Max] for the word, double word, word bit, floating word variables. The minimum and maximum limits depend on the protocol.
[0..15] for the word bit number.
The equipment, selecting it in the equipment list of the current application.
NOTE: XBT cannot be selected.
The display format if it complies with the variable type:
word bit variable: possible display but binary only,
floating variable: possible display but decimal only,
string variable (Jbus protocol): possible display but in
ASCII only,
double word variable: possible displays but decimal, hexadecimal and in ASCII only,
word variable: all types of display are possible.
The format displayed is a multi-language display.
NOTE: For the character string type, another parameter can be used to set up the string length. By default, the length is 16 characters, which is the maximum length possible.
3
Graphic Magelis 3 - 71
Variable adjustment
• Saving an adjustment
An adjustment page can be saved on the PCMCIA card only and cannot be imported to the XBT-L1000.
• Loading an adjustment page
An adjustment page selected must be selected in the list of adjustment pages using the arrows.
NOTE: The variable adjustment page is not password protectable.
Protection of the Adjust page from unwanted users can be accomplished by key-locking the system page.
3 - 72
Graphic Magelis
Use of recipe pages
3.14
Use of recipe pages
• Freezing display
This icon is used to freeze display in the current state. The operator can thus edit the values displayed or enter new values.
• Saving parameters
This icon is used to save the recording of the values displayed on screen to the PCMCIA card under a name selected by the operator.
• Restoring a recording
This icon is used to access the list of recordings.
Select the required recording using the arrow keys.
• Transferring the recording to the control system
The values of the recording are transferred to the control system, in compliance with the transfer rules (see chapter 4, section 4.2 word %MWn+21: recipe transfer not allowed).
3
Graphic Magelis 3 - 73
Loading at application transfer
3.15
Loading extension tasks at application transfer
On a TXBT terminal, it is possible to add functions on top of the basic XBT-F functions. These extra functions are called Extension
tasks (see TXBT manual, chapter 4.6).
3.16
Loading extra files at application transfer
On a TXBT terminal, when making a PC -> TXBT transfer, it is possible to load extra files into the TXBT (see the TXBT manual, chapter 4.5).
3 - 74
Graphic Magelis
Graphic Magelis
Chapter 4
PLC and Terminal
Communications Dialog
4
4 - 1
4 - 2 Graphic Magelis
Contents
This chapter includes the following sections:
4.1
PLC/terminal communications dialog principle ........... 4-5
4.1.1
Data exchanged ................................................ 4-5
4.1.2
Exchange principle for data associated with fields ....................................... 4-7
4.1.3
Principle of the commuincations dialog table ........................................................ 4-8
4.2
Dialog table content ....................................................... 4-10
4.3
PLC/terminal communication dialog cycle ................. 4-29
4.3.1
Processing by the terminal ............................ 4-29
4.3.2
4.3.3
4.3.4
Optimization for communication ................... 4-30
Optimized communication ............................. 4-31
Non-optimized communication ..................... 4-31
4
Graphic Magelis 4 - 3
Dialog principle
4 - 4 Graphic Magelis
Dialog principle
4.1
PLC/terminal communications dialog principle
The communications dialog between the terminal and the PLC consists of an exchange of data between one or several devices.
In all communication situations, the following should be defined:
• Data to be exchanged
• Communication protocol
4.1.1
Data exchanged
Various types of data can be exchanged.
PLC
Data associated with fields
Command data sent from the
PLC to the terminal
Status data sent fron the terminal to the PLC
TERMINAL
4
Graphic Magelis 4 - 5
Data exchanged
4 - 6
Data associated with fields
These are variables which may be:
• displayed on the terminal,
• entered or modified on the terminal.
Command data sent by the PLC to the terminal
This concerns the following commands:
• Display an application or system page,
• Display an alarm page,
• Lock keys,
• Request to enter a variable field,
• Print command,
• Command of indicator lights associated with function keys,
• Clear log command,
• Set time-stamp command,
• Triggers graph plotting.
• etc.
Status data sent by the terminal to the PLC
This concerns the following status:
• Terminal status
confidential mode,
terminal configuration mode,
confirmation of entries by pressing the ENTER key,
cancelled entry by pressing the ESC key,
cancelled entry after a time-out,
print fault.
• Number of the displayed page,
• Number of the last field entered,
• Image of the keypad keys,
• Time-stamp status (date and time),
• Log occupancy rate as a percentage,
• Communication monitoring,
• Number of the last alarm acknowledged,
• Application signature,
• etc.
Graphic Magelis
Data exchanged
4.1.2
Exchange principle for data associated with fields
The exchange principle for the data associated with the fields depends on the protocol chosen according to the type of PLC.
The variables read or written are single words, double words and word bits.
The terminal can be master or slave on the bus but it is always considered as the client and the PLC(s) as the server(s).
This means that the terminal always initiate data interchange to:
• refresh the fields (reading of values in the PLC),
• enter and edit fields (writing of values in the PLC).
NOTE: No PLC communication program needs to be written.
WARNING
UNINTENTIONAL EQUIPMENT OPERATION
PLC memory zone allocated for the XBT dialog table must NOT be used for anything else. It is the designer's responsibility to program the PLC logic properly.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
4
Graphic Magelis 4 - 7
Commands and states
4.1.3
Principle of the communications dialog table
To simplify the communications dialog, all of the following are grouped together in a dialog table:
This table is located in one of the architecture PLCs and composed of n consecutive words (16-bit words).
It includes two parts:
Status table
Status data sent by the terminal to the PLC.
Command table
Commands sent by
the PLC to the terminal
The number of words in the table depends on the choice of status data and commands that are to be processed during the dialog.
The XBT-L1000 software allows you to configure the dialog table
(Figure 4-1).
Figure 4-1: Dialog Table Configuration
4 - 8
NOTE: The words of the dialog table must only be read by the PLC.
It is recommended not to write in this zone.
Graphic Magelis
Commands and states
When configuring the dialog table, you must define the dialog table's start address (basic address). The dialog table is in the PLC. The terminal periodically reads and writes to the table in the PLC.
PLC
TERMINAL
Reading command data
Writing status data
Secure use of the dialog table
A word is used in the table for security purposes: the "dialog table authorization" word.
The use of this word is a security for the PLC/terminal dialog.
When this word is not set to the correct value in the PLC, the terminal does not write any word in the dialog table and does not execute any command.
This value is indicated by XBT-L1000. The PLC program must assign this value to the word “Dialog table authorization” so that the dialog table be processed by the terminal.
4
Graphic Magelis 4 - 9
Dialog table
4.2
Dialog table content
The number of words in the table depends on the choice of states and commands that are to be processed during the dialog. You may add or delete items as you choose.
Notation convention for describing the table
%MWn word of 16 bits with address n.
%MWn, i : bit i of word n.
The address n is taken as the table's start address.
The table comprises a maximum of 135 words.
The description below gives the content of the various dialog table words; refer to the XBT-L1000 software's on-line help for further information on the various words.
PLC <-- XBT: Terminal writes the corresponding word(s) in the PLC.
PLC --> XBT: Terminal reads the corresponding word(s) in the PLC.
PLC <--> XBT: Terminal and the PLC can modify the corrresponding word(s) in the PLC.
4 - 10 Graphic Magelis
Word Functions
%MWn+0
%MWn+1
%MWn+2
%MWn+3
Image of static function keys
Image of system keys
Image of numeric keys
Communication control
%MWn+4 to
%MWn+7
Set PLC clock
%MWn+8
%MWn+9
Number of displayed page
Number of last field entered
%MWn+10 Number of last alarm acknowledged
%MWn+11 Last groups of alarms acknowledged
%MWn+12 Report
%MWn+13 Log filling rate
%MWn+14 Graph plottings performed
%MWn+15 Application checksum
%MWn+16 Number of page to be processed
%MWn+17 Number of field to be entered
%MWn+18 Print command
%MWn+19 Activating graphs plotting
%MWn+20 Table write authorization
Dialog table
Exchange Page
PLC <- XBT
PLC <- XBT
PLC <- XBT
PLC <- XBT
PLC <- XBT
13
13
13
14
14
PLC <- XBT
PLC <- XBT
PLC <- XBT
PLC <- XBT
PLC <- XBT
PLC <- XBT
PLC <- XBT
PLC <- XBT
PLC <-> XBT 18
PLC <-> XBT 20
15
15
15
15
17
17
17
17
PLC <-> XBT 22
PLC -> XBT
PLC -> XBT
23
23
4
Graphic Magelis 4 - 11
Dialog table
Word Functions
%MWn+21 Recipe transfer not allowed
%MWn+22 Clear Log
%MWn+23 Static function keys LEDs llighting.
%MWn+24 Static function keys LEDs flashing.
%MWn+25 Dynamic function keys LEDs lighting.
%MWn+26 Dynamic function keys LEDs flashing.
%MWn+27 Static function keys locking
%MWn+28 System keys locking
%MWn+29 Numeric keys locking
%MWn+30 to
%MWn+90
Alarm table
%MWn+91 to
%MWn+94
Set terminal clock
%MWn+95 to
%MWn+134
Free format print table
Exchange Page
PLC -> XBT
PLC -> XBT
PLC -> XBT
PLC -> XBT
PLC -> XBT
PLC -> XBT
PLC -> XBT
PLC -> XBT
PLC -> XBT
PLC -> XBT
25
25
26
26
24
24
25
25
26
27
PLC -> XBT 28
PLC -> XBT 28
4 - 12 Graphic Magelis
Dialog table
Detailed description
%MWn+0 : Image of static function keys
Images of the keypad keys sent to the PLC.
Bit at 1 = key pressed.
Bit 11 Bit 0
%MWn+0
F12 F1
%MWn+1 : Image of system keys
%MWn+2 : Image of numeric keys
%MWn+1 : system keys
Bit 0 : Up arrow
Bit 1 : Down arrow
Bit 2 : Right arrow
Bit 3 : Left arrow
Bit 4 : MOD
Bit 5 : PRINT
Bit 6 : MENU
Bit 7 : SYST
Bit 8 : ALARM
Bit 9 : ESC
Bit 10 : HOME
Bit 11 : +1
Bit 12 : -1
Bit 13 : ENTER
Bit 14 : Reserved
Bit 15 : Reserved
%MWn+2 : numeric keys
Bit 0 : 0
Bit 1 : 1
Bit 2 : 2
Bit 3 : 3
Bit 4 : 4
Bit 5 : 5
Bit 6 : 6
Bit 7 : 7
Bit 8 : 8
Bit 9 : 9
Bit 10 : .
Bit 11 : +/-
Bit 12 : DEL
Bit 13 : ?
NOTE: There are no images of the dynamic function and alphanumeric keys. See also keys description, chapter 3, section 3.1.
4
Graphic Magelis 4 - 13
Dialog table
Indication to the PLC that the F1 key is pressed
PLC TERMINAL
Dialog table
(1)
F1 key pressed
%MWn: X0
(Bit 0 of word Wn)
1
(2)
4 - 14
WARNING
UNINTENTIONAL EQUIPMENT OPERATION
If communications between the XBT and PLC are lost, the operator's control over the machine may be completely or partially lost. It is the designer's responsibility to consider programming the
PLC logic to account for this situation. An effective method is to monitor Wn+3 of the dialog table from the PLC program.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
%MWn+3 : Communication control
Word incremented by 1 at each processing cycle and used by the
PLC application to monitor the terminal for proper operation.
%MWn+4 to %MWn+7 : Set PLC clock
order of bits 15 8 7 0
%MWn+4 Seconds Day of the week
%MWn+5 Hours Minutes
%MWn+6 Month Day of the month
%MWn+7 Century Year
Graphic Magelis
Dialog table
The terminal writes the time and date in the PLC with the dialog table cycle. There are 2 possible coding formats: Hexadecimal or
BCD (choice made using XBT-L1000).
Day of the week: Monday = 1... Sunday = 7.
%MWn+8: Number of displayed page
See %MWn+16: Number of the page to be processed.
This word contains the page number displayed on the terminal.
When the terminal displays a system page the word “number of the displayed page “ includes:
• in signed decimal: - 16 - N
• in non signed decimal: 65520 - N
• in hexadecimal: H’FFFO’ - N
%MWn+9: Number of last field entered
See %MWn+17: Number of the field to be entered.
This word includes the number of the last field entered on the terminal and sent to the PLC. The entry logics is the following:
4
MSB LSB field number in model page field number in application page
The field number is provided by XBT-L1000: Display/Field
Number menu.
%MWn+10: Number of last alarm acknowledged
%MWn+11: Last groups of alarms acknowledged
See: %MWn+30 to %MWn+90, Table of alarms.
These two words are written together by the terminal when the operator acknowledges:
• a single alarm,
• a group of alarms,
• all the active alarms.
Graphic Magelis 4 - 15
Dialog table
.%MWn+10: Number of the last alarm acknowledged, coded
1 to 1024.
.%MWn+11: Last group of alarms acknowledged with 1 bit per group of alarms (bit 0 = group 1 ...).
The same alarm can be triggered by several bits which may belong to different PLCs (equipment).
The terminal stores the origin of the alarm so that the data related to alarm acknowledgement by the operator can be sent to the proper
PLCs.
Depending on the type of acknowledgement, the terminal writes the following values at next cycle:
Acknowledgement of a single alarm: ENTER or icon ACK for
touchscreen terminals.
%MWn+10: Number of the last alarm acknowledged = No. from
1 to 1024.
%MWn+11: Last group of alarms acknowledged with 1 bit per group of alarms = H’FFFF’.
example: acknowledgement of alarm 5:
%MWn+10 = 5
%mWn+11 = H’FFFF’
Acknowledgement of a group of alarms: ACKALL.
%MWn+10: Number of the last alarm acknowledged = H’FFFF’
Only one group of alarms is selected in the list of alarms.
%MWn+11: Last group of alarms acknowledged with 1 bit per group of alarms = the bit corresponding to the group of alarms acknowledged it set to 0.
example: acknowledgement of group of alarms 2:
%MWn+10 = H’FFFF’
%mWn+11 = H’FFFD’
4 - 16 Graphic Magelis
Dialog table
NOTE: All the active alarms of a group must be triggered by the same PLC to increase the performance levels.
Acknowledgement of all the active alarms: ACKALL.
All the groups of alarms are selected from the list of alarms.
%MWn+10: Number of the last alarm acknowledged = H’FFFF’
Only one group of alarms is selected in the list of alarms.
%MWn+11: Last group of alarms acknowledged with 1 bit per group of alarms = H’0000'
%MWn+12: Report
Bit 0: Confidential mode (Password selected A and/or B and/or C)
Bit 1: Reserved
Bit 2: ENTER on entry
Bit 3: ESC on entry
Bit 4: End of entry on TIME-OUT (1 min)
Bit 5: Printing in progress
Bit 6: Printing fault
Bit 7: Printing stopped
Bit 8: Recipe transfer in progress
Bit 9: Recipe transfer error
Bit 10: Terminal in stand-by
Bits 11 to 15: Reserved
4
%MWn+13: Log filling rate
See %MWn+22: clear history.
Alarm history filling rate on the terminal as a percentage, sent to the PLC.
%MWn+14: Graphs plottings performed
See word %MWn+19: Graph plotting activation.
%MWn+15: Application checksum
The word includes a check sum calculated on the dialog application and which characterises each application version.
Graphic Magelis 4 - 17
4 - 18
Dialog table
%MWn+16: Number of page to be processed
See also %MWn+8: Number of the displayed page.
When the PLC wants to display a page, it indicates its number in word %MWn+16: Number of the page to be processed in compliance with the following:
• from 1 to 64999 for the application pages,
• one of the following values for the system pages:
in signed decimal: - 16 - N
in non signed decimal: 65520 - N
in hexadecimal: H’FFF0' - N
When the display command is executed:
• %MWn+16 = H’FFFF,
• %MWn+8: includes the number of the page displayed in compliance with the above mentioned rules.
CAUTION
UNINTENTIONAL EQUIPMENT OPERATION
The PLC application must check the content of word %MWn+16
(value H"FFFF") to ensure that the command has been processed and check the number of the displayed page to ensure that the command has been correctly executed.
Failure to follow this instruction can result in injury or equipment damage.
Graphic Magelis
Dialog table
Display of page 25 by the PLC
PLC
Program
Display page 25
(1)
Dialog table
%MWn+15
%MWn+8
25
(2) Reading of the table by the terminal
(4) H'FFFF'
(5)
TERMINAL
25
4
(3) Display of page 25
(1) The PLC writes in the dialog table the number of the page to display, 25. (2) The terminal periodically reads the dialog table in the
PLC and (3) displays the required page. Once the command has been processed, (4) the terminal writes H'FFFF' in the word
“Number of the page to be processed” and (5) the number of the displayed page in the word “Number of the displayed page”.
Graphic Magelis 4 - 19
Dialog table
4 - 20
%MWn+17 : Number of field to be entered
See also %MWn+9 : Number of the last field entered,
%MWn+12: Report.
The entry fields are managed by means of 3 words which inform the application of the operator actions:
• %MWn+9 : Number of the last field entered
• %MWn +12 : Report
• %MWn +17 : Number of the field to be entered
MSB number of field in model page
LSB number of field in application page
XBT-L1000 gives the number of field.
CAUTION
UNINTENTIONAL EQUIPMENT OPERATION
The PLC program must check that the page displayed is correct before requesting an entry.
Failure to follow this instruction can result in injury or equipment damage.
PLC request for entry
When the PLC requests an entry in a field, it indicates the number of the field in word %MWn+17: Number of the field to be entered.
The terminal indicates reception of the entry request by resetting the report bits 2, 3, 4 (%MWn+12).
If the entry field exists, the end of entry is indicated by %MWn+17 =
Number of the field to be entered H'FFFF'.
• When the entry is confirmed by ENTER, %MWn+9 “Number of the last field entered contains the number of the field entered.
• When the entry is cancelled by pressing ESC or due to a
Time-Out , no modifications will be made.
The terminal sets one of the 3 status bits according to how the entry was ended (Time-Out, ESC, ENTER).
If the requested field cannot be entered: (unknown field, etc.), the end of the entry is given by 3 informations:
Graphic Magelis
Dialog table
• %MWn+17: Number of the field to be entered = H'FFFF'.
• The 3 status bits (Time-Out, ESC, ENTER) remain at zero.
• The number of the last entry field is reset.
Operator request for entry
The status word and the number of the last entry field are updated in the case of an operator request.
Request by the PLC for a quantity to be produced. The value is entered in field number 25
TERMINAL PLC
Program
Request the quantity to be produced : entry in field no. 25
(1)
(4) Writing of the entry field No.
H'FFFF'
25
%MWn+9
(5) H'FFFF'
25 25
%MWn+17
Dialog table
(2) Reading of the table by the terminal
4
(3) Display of the field for entry and confirmation
Graphic Magelis 4 - 21
4 - 22
Dialog Table
(1) PLC writes in the dialog table, the number of the field to be entered. (2) The terminal periodically reads the dialog table in the
PLC and (3) sets the required field to entry mode. Once the entry has been configured by the operator, the number of the field entered is sent to the PLC (4) and the words "Field to be entered" and
"Report" are updated(5).
%MWn+18 : Print command
15
Print code
8 7
Length of the print table
0
The "print command" word is written by the PLC.
A code is associated with each type of possible printing (MSB).
• Free format printout: H'01xx' (xx = table length in hexadecimal)
• History printout: H'02xx'
• Form printout: H'04xx'.
For form printout, xx represents the number of the form to be printed.
Free format printing consists of sending on the initiative of the PLC, the data contained in the free format printing table, located at the end of the dialog table (%MWn+95 and following), in the least significant byte, the length in bytes of information to be printed (80 bytes maximum).
The word %MWn+18 "Print command" is written to H'FFFF' by the terminal to indicate the end of the print command (see bits 5, 6, 7, of
%MWn+12 "Report").
%MWn+18: H'010A' printing of 10 bytes in the printing table .
Graphic Magelis
Dialog Table
%MWn+19 : Activating graphs plotting
See also %MWn+14: Graph plotting performed
The terminals can monitor the change of a control system data in real time (example: monitoring of an analog value). A curve has 1 to
4 pens with different colors.
The PLC can activate the recording of values and the 4 plottings of a graph simultaneously on a bit rising edge of word %MWn+19. The user can assign one of 16 bits of word %MWn+19 to a curve. He can thus activate 16 graphs (1 word = 16 bits). The bit of word
%MWn+14 with the same order (graph plotting performed) is set to
1 when the graph is plotted (1 to 4 pens).
Word %MWn+14 (graph plotting performed) is used to inform the
PLC of the result of the command (one graph = 1 word bit).
%MWn+20 : Table write authorization
This word serves as a security for the PLC/terminal dialog. When this word is not at the correct value, the terminal cannot write any words in the PLC and cannot execute any commands.
order of bits
15 8 7
Most significant = H'A5' Dialog table length
0
4
The value of this word is indicated (in Hexadecimal) in the dialog table configuration by XBT-L1000.
Example: For a table that is 20 words long, the PLC must write
H'A514' in the authorization word.
A5 = authorization, 14 = number of words in the dialog table (in
Hexadecimal).
Graphic Magelis 4 - 23
Dialog table
4 - 24
%MWn+21: Recipe transfer not allowed
See also %MWn+8: Number of the displayed page and
%MWn+12: Report.
The transfer of configuration parameters from the terminal to the process is a critical operation which must only be performed when the PLC is ready to receive these parameters.
When word %MWn+21 “Recipe transfer not allowed” is set to 0 in the dialog table, the recipe transfer is enabled.
If it is set to 1, transfer is inhibited.
CAUTION
UNINTENTIONAL EQUIPMENT OPERATION
A transfer in progress cannot be interrupted by a change in the status of word %MWn+21 "Recipe transfer not allowed".
Failure to follow this instruction can result in injury or equipment damage.
During a transfer, the recipe page is displayed on the terminal screen. The PLC can thus identify the recipe being transferred using word %MWn+8.
Bits 8 “Recipe transfer in progress” and 9 “Recipe transfer error” of word %MWn+12 “Report” indicate to the PLC that the transfer is in progress. The PLC can then be synchronised on the end of transfer
(bit 8 “Recipe transfer in progress” is set to 0) to restart the process with the new parameters.
Bit 9 “Recipe transfer error’’ of word %MWn+12 “Report” indicates an error during transfer.
%MWn+22: Clear log
See also %MWn+13: Log filling rate.
The PLC must write H'00FF' in word %MWn+22 to clear the log.
• The terminal clears the log and resets the log filling rate word
%MWn+13.
• The PLC must then reset the clear log command %MWn+22.
Graphic Magelis
Dialog table
%MWn+23 : Static function keys LEDs lighting.
Bit 11 Bit 0
%MWn+23 F12 F1
%MWn+24 : Static function keys LEDs flashing.
Bit 11 Bit 0
%MWn+24 F12 F1
%MWn+25 : Dynamic function keys LEDs lighting.
Bit 9 Bit 0
%MWn+25 R10 R1
4
%MWn+26 : Dynamic function keys LEDs flashing.
Bit 9 Bit 0
%MWn+26
R10 R1
If for the same key, the lighting and flashing bit are at 1, the indicator is flashing.
Graphic Magelis 4 - 25
4 - 26
Dialog table
%MWn+27 : Static function keys locking
Bit 11 Bit 0
%MWn+27 F12 F1
%MWn+28 : System keys locking
%MWn+29 : Numeric keys locking
%MWn+28 : system keys %MWn+29 : numeric keys
Bit 0 : Up arrow
Bit 1 : Down arrow
Bit 2 : Right arrow
Bit 3 : Left arrow
Bit 4 : MOD
Bit 5 : PRINT
Bit 6 : MENU
Bit 7 : SYST
Bit 8 : ALARM
Bit 9 : ESC
Bit 10 : HOME
Bit 11 : +1
Bit 12 : -1
Bit 13 : ENTER
Bit 14: Reserved
Bit 15: Reserved
Bit 0 : 0
Bit 1 : 1
Bit 2 : 2
Bit 3 : 3
Bit 4 : 4
Bit 5 : 5
Bit 6 : 6
Bit 7 : 7
Bit 8 : 8
Bit 9 : 9
Bit 10 : .
Bit 11 : +/-
Bit 12 : DEL
Bit 13 : ?
NOTE: If the PLC locks the arrow keys, the terminal automatically switches off the indicator lights on those keys to indicate they are no longer active. The dynamic function and alphanumeric keys cannot be locked.
Graphic Magelis
Dialog table
%MWn+30 to %MWn+90 : Alarm table
See also %MWn+10: number of the last alarm acknowledged (32 words maximum on XBT, 64 words maximum on TXBT).
%MWn+11: Last group of alarms acknowledged.
The display of alarm is commanded by the PLC by setting a word bit to 1.
order of bits
%MWn+30
Bit 15
AL16
%MWn+31
Bit 0
AL1
AL17
Activation of alarm No. 3.
PLC
Program
(1)
Indicate alarm 3
TERMINAL
4
Dialog table
%MWn+30 00...100
(2) Reading of the table
by the terminal
00...100
(1) The PLC writes a 1 to bit 2 of %MWn+30 in the dialog table. (2) The terminal periodically reads the PLC's dialog table and (3) indicates the alarm in the alarm bar.
Graphic Magelis
(3) Alarm 3 displayed in the alarm bar
4 - 27
4 - 28
Dialog table
%MWn+91 to MWn+94 : Set terminal clock
order of bits
15
%MWn+91
%MWn+92
%MWn+93
%MWn+94
Seconds
Hours
Month
Century
8 7
Days of the week
Minutes
Day of the month
Month
0
Whenever one of these words is modified, the terminal is set to the date and time given in this table.
There are 2 possible coding formats: Hexadecimal or BCD (choice made using XBT-L1000).
Day of the week: Monday = 1 ... Sunday = 7.
%MWn+95 to %MWn+134 : Free format print table
See %MWn+18 : print command.
This table is used by the PLC to transfer a character string (80 maximum) to the equipment item (printer, etc.) connected to the terminal.
Graphic Magelis
Dialog cycle
4.3
PLC/terminal communication dialog cycle
4.3.1
Processing by the terminal
Five types of transactions are carried out by the terminal, either intermittently or in a processing cycle:
Dialog table cycle
This comprises reading and writing by the terminal of the parameters selected from the dialog table, including the alarms table, at intervals specified in XBT-L1000.
Permanent variables refresh cycle, at intervals specified in XBT-
L1000.
Displayed page variables refresh cycle
Single reading of variables when calling up a new page
Immediate writing of variable when the function key is pressed or a value entered.
4
Graphic Magelis 4 - 29
Dialog cycle
4.3.2
Optimization for communication
The following recommendations enable terminal/PLC communications to be optimized, thus improving operator dialog response times. They apply, regardless of the communication protocol used.
• make a careful allocation of the variables to single, cyclic or permanent reading, according to how they are used by the terminal,
• use contiguous addresses for the cyclic reading of variables on a page,
• use contiguous addresses for the single reading of variables on a page,
• do not overload the dialog table with words not needed by the application,
• adjust the dialog table period according to the traffic generated by the dialog application on the one hand and the other equipment items of the control system structure on the other hand.
NOTE: The operator actions are processed immediately, independent of the value of the dialog table period.
As a rule, only the words which are useful for the application should be selected to optimize communication.
4 - 30 Graphic Magelis
Dialog cycle
4.3.3
Optimized communication
modif. variable dialog table period variable refresh period on the screen
4.3.4
Non-optimized communication
(Dialog table period too short, variables too widely scattered for page animation).
modif. variable dialog table period variable refresh period on the screen
4
Key:
T dialog table read/write
Ci cyclic reading of n consecutive variables for animating the displayed page
Pi permanent reading of n consecutive variables for recording a curve
E immediate writing of a variable
Graphic Magelis 4 - 31
Dialog cycle
4 - 32 Graphic Magelis
Graphic Magelis
Chapter 5
Example of application implementation
5 - 1
5
5 - 2 Graphic Magelis
Contents
You will be guided step by step through the example, the goal being to create rapidly your first application.
Chapters 2, 3 and the appendix respectively give all the information on the implementation methodology, terminal operation and the various handling procedures.
5.1
Expression of requirements ........................................... 5-5
5.2
Analyzing the expression of requirements ................... 5-9
5.2.1
Application tree structure ................................ 5-9
5.2.2
5.2.3
Application tree structure balance ............... 5-10
Main menu application page .......................... 5-10
5.2.4
5.2.5
5.2.6
5.2.7
5.2.8
5.2.9
Production Menu application page ............... 5-11
Dough preparation application page ............ 5-11
Dough baking application page .................... 5-13
Maintenance page ........................................... 5-14
Static function keys ........................................ 5-15
Data associated with the application ............ 5-15
5.3
Creating the application ................................................ 5-16
5.3.1
Selecting the terminal and protocol ............. 5-16
5.3.2
5.3.3
5.3.4
Creating the page model ................................ 5-17
Creating the various pages ............................ 5-21
Creating navigation between the application pages ............................................ 5-23
5.3.5
5.3.6
5.3.7
5.3.8
5.3.9
Creating the page content ............................. 5-25
Assigning the static function keys ............... 5-31
Locking the static function keys ................... 5-32
Creating the dialog table ................................ 5-33
Alarm processing ............................................ 5-35
5.4
Loading the application in the terminal ....................... 5-37
5.5
Running the application ................................................ 5-38
5
Graphic Magelis 5 - 3
Contents
5 - 4
WARNING
UNINTENTIONAL EQUIPMENT OPERATION
This example application will change register contents in remote devices. This may cause unanticipated change in device status. If this example is used in a functioning system, ensure that all effects of any register changes are fully understood before running this example.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
Graphic Magelis
Example
5.1
Expression of requirements
The Industrial Bakery Co. makes various types of bread. Bread
production consists of two operations:
1. Preparing the dough
The operation consists in mixing water, flour and yeast in a kneader.
Depending on the amount of dough to be made, the operator must indicate: the amounts of water, flour and yeast required.
The weight of the dough obtained must be indicated to the operator.
The operator will have to be assisted when entering the amounts of water, flour and yeast to be used according to the type of dough to be made.
5
2. Baking the dough
The operator selects the baking temperature.
The baking temperature range will be displayed.
If there is a problem (baking temperature too high or too low) an alarm will be activated and the operations to be performed will be indicated to the operator(Figure 5-1).
Figure 5-1: Application diagram
Application diagram
Graphic Magelis 5 - 5
Example
The following two operations are performed besides the production operations:
Installation maintenance
In order to guarantee the quality of the product, daily checks must be performed by the maintenance department. This operation, performed by authorized personnel (maintenance operator), consists in checking the kneader (On/Off). The production operators are not allowed to perform this type of operation.
Management of production
The client wishes to enter the amounts of water, flour, salt and yeast only once per type of bread (filing of these parameters for re-use).
The application will be organized as follows:
Main menu
• Production
• Maintenance
Access authorization
Maintenance
Dough preparation
Recipe use help
Production menu
• Preparation
• Baking
Dough baking
5 - 6 Graphic Magelis
Example
If there are any problems during baking (temperature too high or too low):
• the operator must be informed immediately, whatever screen is displayed,
• he must also be able to access the information indicating the operations to be performed in that case.
5
Additional information
The company wants its name and logo to be displayed on the following screens:
• Dough preparation,
• Dough baking,
• Maintenance.
Industrial Bakery Co.
Navigating between the various screens
The company wants navigation between the:
• main menu,
• maintenance,
• production menu,
• dough preparation,
• dough baking, screens to be indicated to the operator by icons which will be associated with dynamic function keys on the terminal.
Access to main menu.
Access to production menu.
Graphic Magelis 5 - 7
5 - 8
Example
Access to the Maintenance screen.
Access to the Dough Preparation screen.
Access to the Dough Baking screen.
Process control
The F1 static function key is used to start up the process.
Press this key to start the process and press it again to stop it.
Maintenance
For the maintenance operations you will have to:
1. Switch off the kneader by pressing the F2 function key.
2. Check the various parts of the kneader.
3. Switch the kneader back on by pressing F2 again.
Access to the Maintenance screen is protected by a password: PW01.
Locking the Kneader On/Off key
The F2 static function key is locked when the following pages are displayed:
• Menu
• Dough preparation and dough preparation help
• Dough baking and dough baking help and is unlocked when the Maintenance page is displayed.
Graphic Magelis
Example
5.2
Analyzing the expression of requirements
5.2.1
Application tree structure
Analysis of the requirements is used to structure the application in several types of pages:
5
Application page model
Main menu
• Production
• Maintenance
Access authorization
Maintenance
Application page
Recipe application page
Help page
Dough preparation
Recipe use help
Application page
Production
Page menu
• Preparation
• Baking
Application page
Dough baking
Alarm page
Alarms
An application page Model will be used to display the company name and logo on the application pages (Dough preparation, Dough baking, Maintenance).
Navigating between application pages
The dynamic function keys associated with the corresponding icons will be used for navigating between pages.
Graphic Magelis 5 - 9
Example
5.2.2
Application tree structure balance
The application will include:
• 5 application pages:
Main menu
Production menu
Maintenance
Dough preparation
Dough baking
• 1 alarm page
• 2 help pages
Dough preparation help
Dough baking help
5.2.3
Main menu application page
Application model 1 which includes the company name and logo is used for this application page.
Industrial Bakery Co.
Main menu
Production
R4
Access to
Production
Menu screen.
Maintenance
5 - 10
R8
Access to
Maintenance screen.
Graphic Magelis
Example
5.2.4
Production Menu application page
Application model 1 into which the company name and logo are entered is used for this application page.
Industrial Bakery Co.
Production menu
Dough preparation R4
Access to dough preparation screen.
Access to dough baking screen.
5
Dough baking
Main menu
R6
R8
Access to
Main
Menu screen.
5.2.5
Dough preparation application page
The recipe model into which the company name and logo are entered is used for this application page. The four icons for management of the recordings are included in this specific model
(see next page).
Graphic Magelis 5 - 11
Example
Access to Production menu screen using dynamic key R1 associated with the icon.
Industrial Bakery Co.
Dough preparation
R1
Flour Yeast Water
Select the amounts for each product.
Use the ? key for further information.
Enter amount
Flour
Yeast
Water
Amount of dough
Access to the help page associated with the dough preparation application page by pressing the ? key on the keyboard.
Dough preparation
Freeze display
Record parameters
Transfer recording to the control system
Restore recording
Entering the amount
Enter the amounts of flour, yeast and water required.
Press the “Save parameters” key (R8) to record these amounts. Enter the recording name (name of the type of bread). Perform the same procedure for the other types of bread. To restore a recording, press the “Restore recording” (R10) key. Use the arrows to select a recording in the list. Validate. Transfer the parameters using the “Transfer recording” (R9) key.
Access to the baking monitoring screen by pressing the R6 dynamic key associated with the icon.
R6
5 - 12 Graphic Magelis
5.2.6
Dough baking application page
Industrial Bakery Co.
Forming
Dough baking
Temperature selection Temperature monitoring
Example
5
Access to the Production menu screen using dynamic key R1 associated with the icon.
R1
Access to the Dough
Preparation screen using dynamic key
R6 associated with the icon.
R6
Graphic Magelis 5 - 13
Example
5.2.7
Maintenance page
Industrial Bakery Co.
Main menu
Production
Maintenance
Password: PW01
Industrial Bakery Co.
Maintenance
Kneader maintenance
The kneader must be empty when performing this operation
1. Switch off the kneader: F2
2. Check the kneader parts
3. Switch the kneader on: F2
R4
R8
5 - 14 Graphic Magelis
Example
5.2.8
Static function keys
Process control
F1: toggle command
Maintenance (switching off the kneader)
F2: toggle command
Static function keys F1 and F2 are locked when the following pages are displayed:
• Main menu,
• Production menu,
• Dough preparation and dough preparation help,
• Dough baking, and are unlocked when the Maintenance page is displayed.
5
5.2.9
Data associated with the application
Data associated with the alphanumeric and graphic fields
Amount of flour: %MW30.
Amount of water: %MW31.
Amount of yeast: %MW32.
Amount of dough produced: %MW33. (This data is provided by the control system).
Temperature selected with the rotary selector switch: %MW34.
Temperature monitored by the bar graph: %MW35.
Dialog table data
The start address of dialog table is %MW100.
%MW100: word containing the bits associated with the static function keys.
%MW101: word containing the number of the displayed page.
%MW102: word containing the static function key locking command.
%MW104: word containing the alarm bit.
The function of the words will be explained later in this document.
Graphic Magelis 5 - 15
Example
5.3
Creating the application
The XBT-L1000 software and the protocols must be installed on the
PC. Refer to the corresponding service instructions.
5.3.1
Selecting the terminal and protocol
1. Start up the XBT-L1000 software. If an application is already displayed, choose the File/New menu.
Figure 5-2: Terminal Type
Configuration Dialog Box
2. Choose the type of XBT
(example: XBT-F 10")
(Figure 5-2)
Select the protocol (e.g.: ModBus Plus) and confirm by clicking OK.
The default page will then be displayed ( Figure 5-3).
Figure 5-3: Default page window
5 - 16 Graphic Magelis
Example
Save the application using the File/Save menu under the name:
Bakery.DOP; this name will then be displayed in the title bar
(Figure 5-4).
Figure 5-4: Save As Dialog Box
5
5.3.2
Creating the page model
Two model pages are available by default when creating an application: one model for standard application pages and another for the recipe pages. The designer can edit them or create new ones.
Application page model
Reminder: the company wants all the application pages to have the same page background.
Industrial Bakery Co.
Figure 5-5: Page Tree Dialog Box
Choose Application
page model in the tree structure window
(Figure 5-5).
Graphic Magelis 5 - 17
5 - 18
Example
Choose the Page/Properties menu. Indicate the name of the model (MDM1 model) and deselect the Locked option.
Click Ok.
Entering text
Figure 5-6: Select the
(Figure 5-6)
1. Select the Text tool button.
2. Using the mouse, select the required location using the right mouse button.
3. Enter the text: Industrial Bakery Co.
4. Confirm with ENTER.
5. Select the Edit/Text Properties menu (or
Text Object click the right mouse button or press
ALT ENTER).
6. Define the text properties (large character font, bold, yellow) and click
OK to confirm (Figure 5-7).
Figure 5-7: Text Properties Dialog Box
Graphic Magelis
Example
Importing an image
The logo is a *.BMP type file
1. Select the BITMAP tool button.
2. Using the mouse, click and drag the mouse to create an image area. The Insert Image dialog box is displayed (Figure 5-8).
Figure 5-8: Insert Image Dialog Box 5
3. Select an existing image from the Symbols folder. Select Open, press Enter, or double-click to import an existing image.
4. Select the New Image button to open an application to import a new image (Figure 5-9). The list of applications are the programs loaded on the computer.
Figure 5-9: New Image Dialog Box
Graphic Magelis 5 - 19
5 - 20
Example
6. The image is inserted, position it at the desired place.
Industrial Bakery Co.
Now that the model page has been created, we are going to create the pages.
NOTE: The model page created will appear in gray on the
XBT-L1000 background, but will appear in color on the terminal.
Recipe page model
The recipe page models have the same properties as the application page models except that the latter includes the four additional icons for managing “recipe” recordings (Figure 5-10).
Figure 5-10: Recipe Page Model
Industrial Bakery Co.
Graphic Magelis
Example
5.3.3
Creating the various pages
Application page
Figure 5-11: Properties Page
Dialog Box
1. Select the application page type in the Page tree
structure window, a page called Application page 1 exists by default, with the model page displayed in gray in the background.
2. Choose the Page/Properties menu (or click the right mouse button) (Figure 5-11).
The first page to be created in the example is called: MENU.
3. Enter the name of the page, click Protection and, if necessary, deselect the Access with password box and confirm with Ok.
Click Ok again. The menu page has now been created.
4. Choose the Page/New Page menu or click the new page icon and proceed in the same way as in step 3 to create the "Dough preparation" page, and then create the "Dough baking" page in the same way.
5. To access the maintenance page, click Protection and select the checkbox Access by password. Check box A and click on
Passwords..., enter PW01 in the A field. Select Ok, Ok, and Ok.
(Figure 5-12)
Figure 5-12: Protection and Password Pages
5
Help page
Create the help pages (Preparation and Baking) by selecting the
Page/New page/Help menu.
Graphic Magelis 5 - 21
5 - 22
Example
To associate a help page with an application page:
1. Select the application page in the Tree structure page (for example: Dough preparation application page).
2. Select the Page/Associate
help page menu or click the
Figure 5-13: Page/Associate
Help Dialog Box corresponding icon.
3. Select the help page you want to associate
(for example: Preparation) and click OK to confirm. Also associate the Baking help page (Figure 5-13).
Alarm page
Create the alarm pages (Baking problem) in the same way as the application pages by choosing the Page/New page/Alarm menu or by clicking the corresponding icon. Enter the name of the alarm page (Baking fault) and click
OK to confirm. Complete alarm processing is described in section 3.8 (Figure 5-14).
Figure 5-14: Alarm Page
Dialog Box
The page architecture is displayed in the tree structure window
(Figure 5-15).
Figure 5-15: Page Tree Dialog Box
Graphic Magelis
Example
5.3.4
Creating navigation between the application pages
Navigation between the application pages is performed by means of dynamic function keys (example: Main menu page).
5
Industrial Bakery Co.
Production
R4
Maintenance R8
Access to the Production screen: R4 dynamic key associated with the icon
Access to the Maintenance screen: R8 dynamic key associated with the icon
Graphic Magelis 5 - 23
Example
1. Double click the dynamic function key to be assigned
(Figure 5-16).
Figure 5-16: Dynamic Function Key
Example: R4
2. Select Action/Page
access, the destination page (Dough preparation), click Image and insert the image associated with the
R4 key (see Section 5.3.2
importing an image)
(Figure 5-17).
Figure 5-17: Configure
Dynamic Key
5 - 24
Create the navigation between all the application pages in the same way (see analysis in Section 5.2.3,
5.2.4 and 5.2.5). The Tree structure window displays the navigation architecture you have created
(Figure 5-18).
Figure 5-18: Tree Window
Graphic Magelis
Example
5.3.5
Creating the page content
Industrial Bakery Co.
Dough preparation
Select the amounts of each product
Use the ? key for further information
Flour Yeast Water
5
Enter amounts
Flour
Yeast
Water
Amount of dough
Text
Enter the text in the various pages as described in section 5.3.2.
Line, Rectangle, Ellipse
1. Select the tool button.
2. Using the mouse, define the object size.
3. Select the Edit/Property menu (or right mouse click or double click).
4. Define the object properties (filled in or empty, color, etc.).
Alphanumeric fields
The Dough preparation application page has 3 entry fields and one read only field.
1. Select the Create an Alphanumeric Field tool button.
2. Using the mouse, click on the required location.
Graphic Magelis 5 - 25
Example
3. Define the object properties (Figure 5-19).
In the example the
Amount entry fields have
5 characters maximum, and decimal format is used.
Figure 5-19: Properties Dialog Box
Click modify to define the PLC variable representing the content of the field and click Ok to confirm (Figure 5-20).
Figure 5-20: PLC Variable
Dialog Box
Amount of flour: %MW30
Amount of water: %MW31
Amount of yeast: %MW32
5 - 26
Create the "Amount of dough produced" field in the same way. Click Option and set the access field to read
(Figure 5-21).
Figure 5-21: Properties Page
Dialog Box
Amount of dough produced:
%MW33
Graphic Magelis
Example
Reminder of the requirements specification: The amount of dough must be between 2800 and 3000. If the amount is not within these limits, the display will switch to red.
a. Click the Thresholds tab b. Click Limit to set the max. limit to 3000 and the min. limit to
2800 and click Color to define the colors (Figure 5-22).
5
Figure 5-22: Properties Dialog Box
Color red: max. limit
Color blue: correct value
Color red: min. limit c. End entering the "Dough preparation" page as described on the previous page.
The "Dough baking" application page includes:
• Text and drawings, whose input principle has already been described
• One temperature selection rotary switch
• One temperature monitoring bar graph
Graphic Magelis 5 - 27
5 - 28
Example
Industrial Bakery Co.
Dough baking
Temperature selection Temperature monitoring
The "Dough baking" application page includes:
• texts and drawings, whose entry principle has already been described,
• 1 temperature rotary selector switch,
• 1 temperature monitoring bar graph.
Rotary selector switch
1. Select the rotary selector switch tool button.
2. Using the mouse, define the object size.
3. Select the Edit/Rotary Switch Properties menu (or right mouse click or double click).
Figure 5-23: Properties of Rotary Switch Dialog Box
Graphic Magelis
Example
Assign the word %MW34 to the object using the Modify button, click Ok. This word will contain the value selected by means of the rotary selector. Click List and, using the Delete or Add buttons, define the number of positions for the rotary selector and the value to be assigned in the word (4 positions: 0, 300, 400, 500)
(Figure 5-24).
Figure 5-24: Position List Dialog Box
5
Click Ok.
Using the Color button, define the color of the graduations and of the background.
Click Ok twice to confirm, the rotary selector will then be displayed but the graduations will not be identified.
Using the Text tool, enter the values to allow the operator to identify the positions. Refer to the dough baking screen on page 5-28.
Bar graph
1. Select the Bar Graph tool button.
2. Using the mouse, define the object size.
3. Select the Edit/Bar Graph
Properties menu (or right mouse click or double click) (Figure 5-25).
Figure 5-25: Properties of Bar
Graph Dialog Box
Graphic Magelis 5 - 29
Example
Select the type of bar graph (for example: horizontal, large graduation). Assign the word %MW35 to the object using the
Modify button. This word will contain the oven temperature value
(Figure 5-26). Click Ok.
Figure 5-26: Properties of Bar Graph Dialog Box
Click Option and set the object to cyclic reading. The baking temperature must be between 290
°
and 520
°
. If the temperature is outside these limits the display will switch to blue. Click Threshold to define a high threshold (H) of 520 and a low threshold (L) of 290
Figure 5-27: Properties of Bar Graph Dialog Box
Color red: high limit
Color red: low limit
5 - 30 and click Color to define the colors (Figure 5-27).
Click OK to confirm. The bar graph is displayed but the graduations are not identified.
Using the Text tool, enter the values to allow the operator to identify the positions. Refer to the dough baking screen on page 5-28.
Graphic Magelis
Example
5.3.6
Assigning the static function keys
In order to assign the static function keys:
1. Select the Configuration/Function Keys menu. The front panel of the terminal will then be displayed.
2. Double click the required function key (For example: F1).
3. Select the toggle command type.
4. Click Ok to confirm.
5
Bits associated with the dialog static function keys that can be used in the PLC application
A reserved word in the dialog table indicates the status of the function keys in the form of a word bit: bit at 1 = key pressed.
In our example the word %MW100 is used.
Bit 1 Bit 0
%MW100 F2 F1
Bits B0 and B1 are associated with the F1 and F2 command keys.
Graphic Magelis 5 - 31
Example
5.3.7
Locking the static function keys
To perform this function, you must:
• know the number of the displayed page,
• lock or unlock the key as the case may be.
Number of the displayed page
A word in the dialog table contains the number of the displayed page; the Page/property menu gives the number of each page:
Menu: page No. 1
Dough preparation: page No. 2
Dough baking: page No. 3
Maintenance: page No. 4
In our example word %MW101 is used.
Locking the static function keys
A word in the table is assigned to static function key locking. In our
Bit 1 Bit 0
%MW102
F2 F1 example word %MW102 is used.
Set bit B1 to 1 to lock the F2 key.
Key locking by the PLC
The program has the following structure:
If %MW101 (No. of the displayed page) = 1, 2 or 3 set bit B1 of word
%MW102 to 1 (F2 locked).
If %MW101 (No. of the displayed page) = 4 set bit B1 of word
%MW102 to 0 (F2 unlocked).
5 - 32 Graphic Magelis
Example
5.3.8
Creating the dialog table
Several elements of the dialog table have been declared in the preceding chapters:
%MW100: word containing the bits associated with the static function keys.
%MW101: word containing the number of the displayed page.
%MW102: word containing the static function key locking command.
%MW104: word containing the alarm bit.
5
Select the Configuration/Dialog table menu
Check the Use dialog table option (Figure 5-28).
Figure 5-28: Configure/Dialog Table
Click Modify to change the address of the beginning of table %MW100
Graphic Magelis 5 - 33
Example
In the Function selections list, delete or add the functions required by the application by means of the Add Function or Delete
Function buttons to obtain the following list:
Once creation is completed, save the application using the File/
Save menu.
5 - 34 Graphic Magelis
Example
5.3.9
Alarm processing
Reminder of the expression of requirements
If the baking temperature is too high, an alarm will be displayed in a strip on the application pages, the Alarm indicator will flash;
• you can acknowledge the alarm by pressing ENTER,
• or consult the alarm page by pressing SHIFT+ ENTER.
5
PLC command to display the alarm
The dialog table contains words reserved for displaying alarms.
Display is commanded by the PLC by setting a word bit to 1 in the dialog table. In our example, bit B0 of word %W104 is used.
Alarm configuring by the PLC
Go to the alarm page by means of the Page tree structure window, select the Page/Properties menu and click the Extension button in the Property window (Figure 5-29).
Figure 5-29: Properties of Page Dialog Box
Select Type of action: Display (type of action when the alarm is triggered).
Select the ACK box: compulsory acknowledgment of the alarm when it is triggered.
Graphic Magelis 5 - 35
5 - 36
Example
Click Add to assign the alarm bit (bit 0 of word %MW104)
(Figure 5-30).
Bit 15
Bit 0
%MW104 AL16 AL0
Figure 5-30: Alarm Bits Dialog Box
Click bit 0 to assign the alarm.
The word is defined in the dialog table.
Case of TXBT: using any bit
If you want to assign a bit to the alarm, click on Other bit to assign bit 5 from register 40501 (Figure 5-31).
Figure 5-31: TXBT Alarm Bits Dialog Box
Graphic Magelis
Example
5.4
Loading the application in the terminal
1. Switch on the terminal (refer to the terminal service instruction for wiring of power supply).
2. Connect the terminal to the PLC using the relevant cable (ex.:
XBTZ968 for a TSX Micro with Unitelway V2.0).
5
3. Connect cable XBT-Z915, revision index 22 and the XBT-Z962 between the PC and the terminal.
4. Click "Transfers", "Export" to terminal using the software
(application open).
Graphic Magelis 5 - 37
Example
5.5
Running the application
(See chapter 3 for more details).
The dynamic function keys are used to navigate between pages.
After pressing MOD, use the arrow keys to navigate from one field to the other.
Once you are positioned on the desired field, press MOD to select the field.
If you do not enter any value in the field within one minute, the field will exit the entry mode.
Cancelling the entry
Press the ESC key if you want to cancel the current entry; the field will then not be modified in any way.
5 - 38 Graphic Magelis
Graphic Magelis
Appendix A
A
A - 1
A - 2 Graphic Magelis
Contents
A.1
XBT-F Specifications ....................................................... A-5
A.1.1
XBT-F 01 ............................................................. A-5
A.1.2
XBT-F 02 ............................................................. A-9
A.1.3
Touchscreen XBT-F 032 ................................. A-13
A.1.4
Touchscreen XBT-F 034 ................................. A-17
A.1.5
TXBT ................................................................. A-21
A - 3
A
Graphic Magelis
XBT-F specifications
A - 4 Graphic Magelis
A.1
XBT-F Specifications
A.1.1
XBT-F 01
XBT-F specifications
Graphic Magelis A - 5
A
XBT-F specifications
Types of display
Power
Memories
LCD 5.7"
320x240 pixels
STN monochrome, 16 grey levels
24VDC
Voltage limits: 18 to 30 VDC
Ripple: 5 % maximun
Consumption: 35 W
Application+protocol: 4 MB to 10 MB PCMCIA
EPROM card, 50 to 450 pages of applications, alarms and help according to the memory card in use.
Alarm log: 500 events
Recipes: 125 recordings and 5000 values maximum
Serial link
Printer/ XBT-
L1000 link
Keypad
Indicating
Exchange protocols
Time-stamp
RS232/RS485/RS422 asynchronous serial link
RS232 asynchronous serial link
Customizable membrane keypad
1 communication status indicator light
1 indicator light per function key
1 indicator light per service key
1 keypad/standby screen busy indicator light
Downloadable from the protocol diskette using the XBT-L1000 software.
Protocols: UNI-TELWAY, FIPWAY, FIPIO,
Modbus plus, Modbus, Jbus and those used for
AEG, Allen Bradley, GE, Siemens and Omron
PLCs.
yes (no back-up)
A - 6 Graphic Magelis
XBT-F specifications
Alarm relay 1mA/ 5V min AC/DC
0.5A/24V max AC/DC
Weight
Temperature
3.96 lb (1.8 kg)
Operating: +32 to +113
°
F (0 to 45
°
C),
Humidity: 0 to 85%.
Storage: - 4 to +140
°
F (- 20
°
to + 60
°
C)
IP65 per IEC529 and degree 1 per
NFC20-010; UL 4,4x, NEMA 4
Degree of protection
Installation and attachment
Built-in, attached with 10 push latches (provided), on panel 0.06 to 0.24 inches thick (1.6 to 6 mm).
System languages
English, French, German, Italian, Spanish
System pages can be translated in any other language
Static function keys
10
Dynamic function keys
8
A
Graphic Magelis A - 7
XBT-F specifications
A - 8 Graphic Magelis
A.1.2
XBT-F 02
XBT-F specifications
Graphic Magelis A - 9
A
XBT-F specifications
Types of display
Power
Memories
LCD 10.4"
640x480 pixels
STN monochrome (9.5" screen), 16 grey levels and TFT color (10.4" screen), 256 colors.
24VDC
Voltage limits: 18 to 30 VDC
Ripple: 5 % maximun
Consumption: 35 W
Application+protocol: 4 MB to 10 MB PCMCIA
EPROM card, 30 to 300 pages of applications, alarms and help according to the memory card in use.
Alarm log: 500 events
Recipes: 125 recordings and 5000 values maximum
RS232/RS485/RS422 asynchronous serial link
RS232 asynchronous serial link
Serial link
Printer/XBT-
L1000 link
Keypad
Indicating
Exchange protocols
Time-stamp
Customizable membrane keypad
1 communication status indicator light
1 indicator light per function key
1 indicator light per service key
1 keypad/standby screen busy indicator light
Downloadable from the protocol diskette using the XBT-L1000 software.
Protocols: UNI-TELWAY, FIPWAY, FIPIO, Modbus plus, Modbus, Jbus and those used for AEG, Allen
Bradley, GE, Siemens and Omron PLCs.
yes (no back-up)
A - 10 Graphic Magelis
XBT-F specifications
Alarm relay 1mA/ 5V min AC/DC
0.5A/24V max AC/DC
Weight
Temperature
5.95 lb (2.7 Kg)
Operating: +32 to +113
°
F (0 to 45
°
C),
Humidity: 0 to 85%.
Storage : - 4 to +140
°
F (- 20
°
to + 60
°
C)
IP65 per IEC529 and degree 1 per
NFC20-010; UL 4, 4x, NEMA 4
Degree of protection
Installation and attachment
Built-in, attached with 10 push latches (provided), on panel 0.06 to 0.24 inches thick (1.6 to 6 mm).
System languages
English, French, German, Italian, Spanish
System pages can be translated in any other language
Static function keys
12
Dynamic function keys
10
A
Graphic Magelis A - 11
XBT-F specifications
A - 12 Graphic Magelis
A.1.3
Touchscreen XBT-F 032
XBT-F specifications
Graphic Magelis A - 13
A
XBT-F specifications
Types of display
Touchscreen pad
Power
LCD STN 5.7" touchscreen
320x240 pixels
256 colors
Resistive matrix
6x8 touch zones
Memories
Exchange protocols
Time-stamp
24VDC
Voltage limits: 18 to 30VDC
Ripple: 5% maximum
Consumption: 35 W
Application + protocol: 4 MB to 10 MB PCMCIA card 50 to 450 application, alarm and help pages according to the memory card in use
Alarm log: 500 events
Recipes: 125 recordings and 5000 values maximum
RS232/RS485/RS422 asynchronous serial link Serial link
Printer/
XBT-L1000 link
RS232 asynchronous serial link
Indicating 1 communication status indicator light
1 touchscreen pad pressed/standby screen indicator light
1 alarm indicator light
Downloadable from the protocol diskette using the XBT-L1000 software.
Protocols: UNI-TELWAY, FIPWAY, FIPIO,
Modbus plus, Modbus, Jbus and those used for
AEG, Allen Bradley, GE, Siemens and
Omron PLCs yes (no back-up)
A - 14 Graphic Magelis
XBT-F specifications
Alarm relay 1 mA/5V min. AC/DC
0.5A/24V max. AC/DC
Weight
Temperature
Degree of protection
3.53 lb (1.6 kg)
Operating: +32 to +113
°
F (0 to 45
°
C),
Humidity: 0 to 85%.
Storage : - 4 to +140
°
F (- 20
°
to + 60
°
C)
IP65 per IEC529 and degree 1 per NFC20-010;
UL 4, 4x, NEMA 4
Installation and Built-in, attached with 8 push latches (provided), attachment on panel 0.06 to 0.24 inches thick (1.6 to 6 mm).
System languages
English, French, German, Italian, Spanish.
System pages can be translated in any other language.
A
Graphic Magelis A - 15
XBT-F specifications
A - 16 Graphic Magelis
A.1.4
Touchscreen XBT-F 034
XBT-F specifications
Graphic Magelis A - 17
A
XBT-F specifications
Types of display
Touchscreen pad
Power
LCD TFT 10.4", touchscreen
640x480 pixels
256 colors
Resistive matrix
10x13 touch zones
Memories
Exchange protocols
Time-stamp
24VDC
Voltage limits: 18 to 30VDC
Ripple: 5% maximum
Consumption: 35 W
Application + protocol: 4 MB to 10 MB PCMCIA card, 30 to 300 application, alarm and help pages according to the memory card in use
Alarm history: 500 events
Recipes: 125 recordings
RS232/RS485/RS422 asynchronous serial link Serial link
Printer/
XBT-L1000 link
RS232 asynchronous serial link
Indicating 1 communication status indicator light
1 touchscreen pad pressed/standby screen indicator light
1 alarm indicator light
Downloadable from the protocol diskette using the XBT-L1000 software.
Protocols: UNI-TELWAY, FIPWAY, FIPIO,
Modbus plus, Modbus, Jbus and those used for
AEG, Allen Bradley, GE, Siemens and
Omron PLCs yes (no back-up)
A - 18 Graphic Magelis
XBT-F specifications
Alarm relay 1 mA/5V min. AC/DC
0.5A/24V max. AC/DC
Weight
Temperature
Degree of protection
5.29 lb (2.4 kg)
Operating: +32 to +113
°
F (0 to 45
°
C),
Humidity: 0 to 85%.
Storage: - 4 to +140
°
F (- 20
°
to + 60
°
C)
IP65 per IEC529 and degree 1 per NFC20-010;
UL 4, 4x, NEMA 4
Installation and Built-in, attached with 10 push latches (provided), attachment on panel 0.06 to 0.24 inches thick (1.6 to 6 mm).
System languages
English, French, German, Italian, Spanish.
System pages can be translated in any other language.
A
Graphic Magelis A - 19
TXBT specifications
A - 20 Graphic Magelis
A.1.5
TXBT
TXBT specifications
Graphic Magelis A - 21
A
TXBT specifications
Types of display
Power supply
Hard disk
Dynamic RAM
Application memory
Serial link
LCD 10.4”
640x480 pixels
Monochrome, 16 grey levels (9.5" screen) and color
(10.4" screen), 256 colors
24VDC
Voltage limit: 18 to 30 VDC
Ripple: 5% maximum
Consumption: 80 W
1.6 Gb or more
16 Mb expandible to 32 Mb
Application+protocol: 4MB to 10 MB PCMCIA type II card
Faults history: PCMCIA card
PLC: isolated serial link, RS232C/RS485/RS422
PC: Non-isolated serial link, RS232C
Parallel
PS/2 compatible
Printer link
External keyboard
Bus or network
ISA bus cards
Keypad
Indication
Slot for PCMCIA type II and III card
2 format 2/3 slots
Customizable membrane keypad
1 communication status indicator light
1 indicator light per function key
1 indicator light per service key
1 keypad/standby screen busy indicator light
A - 22 Graphic Magelis
TXBT specifications
Signaling
Exchange protocol
Time-stamp
Alarm relay
Weight
Temperature
Degree of protection
Installation and attachment
System language
Static function keys
Dynamic function keys
Application, help and alarm pages
Downloadable from protocol diskette using the
XBT-L1000 software.
Protocols: UNI-TELWAY, FIPWAY, FIPIO,
ISAWAY, Modbus plus, Modbus, Jbus yes (with back-up)
1 mA/5 V min. AC/DC
0.5 A/24 V max. AC/DC
11.2 lb (5.1 kg)
Operating: +32 to +113
°
F (0 to 45
°
C),
Humidity: 0 to 85%.
Storage: - 4 to +140
°
F (- 20
°
to + 60
°
C)
IP65 per Section IEC529 and degree 1 per
NFC20-010; UL 4, 4x, NEMA 4
Built-in, attached with 12 push latches
(supplied), on panel 0.06 to 0.24 inches thick
(1.6 to 6 mm).
French, English, Spanish, Italian, German.
System pages can be translated in any other language
10
A
12
Application, alarm and help pages: limited to disk capacity, maximum of 1024 pages
Graphic Magelis A - 23
A - 24 Graphic Magelis
Graphic Magelis
Appendix B
B - 1
B
B - 2 Graphic Magelis
Contents
B.1
System messages ............................................................ B-5
Graphic Magelis B - 3
B
System messages
B - 4 Graphic Magelis
System messages
B.1
System messages
System messages generated by XBT
(system messages in English, not configurable)
WIRING FAULT
SWITCH POWER OFF: Incorrect cable.
WAITING FOR TRANSFER: Waiting for downloading.
NO PROGRAM: No application in the product.
DOWNLOAD IN PROGRESS: Downloading to XBT in progress.
DOWNLOAD ABORTED: Downloading to XBT cancelled by the operator.
DOWNLOAD FAILED: Unsuccessful downloading to XBT.
DOWNLOAD COMPLETED: Downloading to XBT succesfully completed.
UPLOAD IN PROGRESS: Uploading to the PC in progress.
UPLOAD ABORTED: Uploading to the PC cancelled by the operator.
UPLOAD FAILED: Unsuccessful uploading to the PC.
UPLOAD COMPLETED: Uploading to the PC successfully completed.
CONNECTING: Cable reading and search for the communication configuration in progress.
APPLICATION FAULT: Application error (incoherence).
B
Graphic Magelis B - 5
System messages
B - 6
System messages generated by XBT (5 languages), language selected during configuration.
WRONG PASSWORD: Entry of an incorrect password.
PAGE DOES NOT EXIST: Call-up of a non-existent page.
PROTECTED ACCESS PAGE: Call-up of a page protected by password.
Remedy: enter the password protecting the page.
IMPOSSIBLE TO WRITE VARIABLE: Writing of a non-existent variable or XBT <-> PLC connection problems. Possible cause: equipment address error, variable address error.
Remedy: change the parameters of the variable in XBT-L1000.
OVERFLOW MIN <= VALUE >= MAX: Entry of a value which is outside the limits.
INCORRECT DIALOG TABLE AUTHORIZATION: Incorrect authorization word.
Remedy: write in the word “Authorization” the value given by XBT-
L1000 in the dialog box “Configure dialog table”, "Authorization word=" field.
DIALOG TABLE READING IMPOSSIBLE: Connection problems between XBT <-> PLC.
Same possible cause, same remedy: see “Impossible to write variable”.
DIALOG TABLE WRITING IMPOSSIBLE: Writing to a protected zone or XBT <-> PLC connection problems.
Same possible cause, same remedy: see “Impossible to write variable”.
PRINTING ACKNOWLEDGED: Transient display if printing requested by the user is possible.
IMPOSSIBLE ACTION, PRINTING IN PROGRESS: Transient display when printing is in progress.
Graphic Magelis
System messages
IMPOSSIBLE ACTION, FAULTY PRINTER : Transient display when printer is faulty, or the terminal is still connected to XBT-L1000 or there is no paper in the printer.
SAVING IN PROGRESS: Transient display during saving on the
PCMCIA card of:
• a recipe recording,
• an adjustment page.
SAVING IMPOSSIBLE: Transient display after request for saving on the PCMCIA card of:
• a recipe recording,
• an adjustment page.
Possible cause: PCMCIA card full or zone allocated to storage full.
LOADING IN PROGRESS: Transient display during loading from the PCMCIA card of:
• a recipe recording,
• an adjustment page.
LOADING IMPOSSIBLE: Transient display after request for loading from the PCMCIA card of:
• a recipe recording,
• an adjustment page.
Possible cause: file damaged.
TRANSFER IN PROGRESS: Transient display during transfer to the control system of recipe recording data. The transfer can be aborted by pressing ESC (key or touch zone).
TRANSFER IMPOSSIBLE: Transient display after request for transfer of a recipe recording to the control system.
Possible cause: connection problem between the terminal and the control system.
B
Graphic Magelis B - 7
System messages
NO SAVING OF VALUE FOR OBJECTS SET TO ERROR:
Transient display after saving a recipe recording on the PCMCIA card.
Possible causes: a) the objects could not read their variables (symbol: or ), b) the request for saving has been initiated while all the objects had not read their variables. The objects are not displayed yet.
Remedies: a) - check that the equipment item of the variable(s) associated with the objects set to error is properly connected to the terminal,
- check that the variables of the objects set to error are declared in the PLC.
b) wait for the full page to be displayed before requesting saving.
In both cases: delete incomplete saving, solve the problem, save again.
OBJECTS SET TO ERROR NOT INITIALIZED: Transient display after loading of a recipe recording from the PCMCIA card.
Possible causes: a) some objects were set to error during saving and thus not saved, b) one or several objects have been added to the page since last saving of the recording; no value has thus been recorded by the objects.
Remedy: in both cases, the terminal initializes the relevant objects to 0.
The objects must be set to a correct value.
The recording must be saved again and include the values correctly initialized by the user.
All these actions must be performed before transfer to the control system in order not to transfer erroneous values.
OPERATION IN LOCAL MODE: Display in the status line.
In this mode, the terminal does not indicate the status of the
control system but usually the status of a recipe recording which has just been loaded from the PCMCIA card.
B - 8 Graphic Magelis
Index
A
Accessing application pages
Accessing variable fields
Acknowledging alarms
Adjustment page
Adjustment TXBT
Adjustment XBT
Alarm bit
Alarm group
Alarm log capacity
Alarm log
Alarm indicating
Alarm list
Alarm pages
Alarm relay command
Alarm relay
Alarm strip (alarm page)
Alarm strip (application page)
Alarm table
Alarms
Alphanumeric variable field
Animation
Application
Application pages
Application transfer
B
Bar-graph
Bitmap
C
Calling up the alarm list
Characteristics of the terminals
Clearing the alarm history
Command using the TXBT mouse
Confidential mode
Configuration of terminal
Creating the application
Graphic Magelis
Index
2-16
2-16
1-19
A-5
3-48
3-51
3-20
3-61
2-9
3-47
3-47
3-39
1-19
1-21
3-45
3-45
1-17
1-18
3-32
3-44
1-29
3-65
3-69
2-25
3-42
3-39
3-41
3-39
2-16
2-15
1-11
1-15
3-14
I - 1
Index
I - 2
Index
D
Date (format on the terminal)
Date (format under XBT-L1000)
Default language (on the terminal)
Default language (under XBT-L1000)
Dialog table content
Dialog table
Display at power-up
Display format
Display priority in the alarm list
Displaying a page on the initiative of the PLC
Displaying a page using a function key
Displaying a page using its number
Displaying the alarm Log
Displaying variables
Dynamic function key
Dynamic function keys
E
Ellipse
Entering graphic variable fields
Entering variable fields
Example of application
F
Fields
Form pages
Form
Free format printing
Function key object
G
General on TXBT-F terminals
General on XBT-F terminals
Getting help (alarm pages)
Getting help (application pages)
Getting help (printing)
Graphs
2-16
3-34
3-31
5-5
1-12
1-26
1-26
3-60
2-19
1-6
1-5
1-24
1-19
1-24
2-17
3-43
3-30
3-28
3-27
3-48
3-31
3-28
1-28
3-62
2-32
3-62
2-31
4-10
2-12
3-23
3-31
Graphic Magelis
H
Help
Help pages
I
Image box
Impulse command
Indicator lights
K
Key locking
Keypad keys
L
Label
Line
Linear potentiometer
Linear switch
Link between application pages
List of pages
Loading the PL7 symbol file
Loading at application (transfer)
Log display
Log size
M
Model pages
Modifying parameters
N
Numbered list
O
Objects
On-line printing
Optimized communication
Operating mode
Overall acknowledgement
Graphic Magelis
Index
2-20
2-16
2-17
2-17
2-19
3-26
2-10
3-74
3-48
3-47
2-21
3-32
3-36
2-15
3-56
4-30
3-16
3-46
1-25
1-25
2-17
3-50
3-6
3-54
3-6
I - 3
Index
I - 4
Index
P
Page display by default
Page display using function key
Page display by the PLC
Page number
Page tree structure
Passwords
PC link
PL7 variable import
PLC link
PLC/Terminal dialog
Power up
Printer link
Printer (parameters on the terminal)
Printer parameters
Printing the alarm history
Printing the list of active alarms
Printing
Process control
Protecting fields
Protocol parameters
Push-on/Push-off command
R
Recipe pages
Recipe
Rectangle
Remote transfer
Rotary potentiometer
Rotary switch
Running Windows 95 applications
Run-time mode
S
Saving
Simulation
Static function key
Static function keys
Status line
1-20
1-20
2-16
3-15
2-17
2-17
3-52
3-16
2-33
2-34
3-29
1-28
1-17
3-12
1-30
3-23
3-56
3-64
3-64
3-48
3-59
3-23
3-28
3-30
3-27
2-28
2-32
3-12
3-65
3-56
1-11
3-55
3-63
1-28, 3-50
Graphic Magelis
Status table
Structure of applications
Symbol library
System messages
T
Terminal configuration
Terminal date and time
Terminal parameters
Text (object)
Thresholds
Time (format on the terminal)
Toggle command
Tool palette
Toolbar
Tree structure
TXBT external keyboard
TXBT home screen
TXBT keys
V
VU-meter
W
Windows 95 application
X
XBT-F home screen
XBT-L1000
Index
2- 17
2-20
3-23
2-9
4-8
1-11
2-10
B-5
3-61
3-62
2-31
2-16
3-36
3-62
3-50
2-14
2-14
2-28
1-6
3-24
3-10
Graphic Magelis
I - 5
Index
Index
I - 6
Graphic Magelis
© Copyright Telemecanique 1999. All rights reserved. This document may not be reproduced or copied, in whole or in part, in any form or by any means, graphic, electronic or mechanical, including photocopying, recording, or storage in a retrieval system.
XBT-X000US 1999-02