Schneider Electric Modbus offers advanced features for seamless communication and efficient data exchange in industrial automation systems. With its robust design and advanced capabilities, it enables reliable data transmission and control over various industrial networks. The device supports multiple communication protocols, including Modbus RTU, Modbus TCP, and Modbus ASCII, providing flexibility in integrating with different devices and systems.
تبلیغات
تبلیغات
Advantys Device Type Manager
EIO0000000769 04/2016
Advantys Device Type
Manager
STB on Modbus TCP
User Manual
04/2016 www.schneider-electric.com
2
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical, including photocopying, without express written permission of Schneider Electric.
All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to help ensure compliance with documented system data, only the manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must be followed.
Failure to use Schneider Electric software or approved software with our hardware products may result in injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2016 Schneider Electric. All rights reserved.
EIO0000000769 04/2016
Table of Contents
Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 1 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing and Uninstalling Advantys DTM . . . . . . . . . . . . . . . . . . . . .
Chapter 2 Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . .
Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
User Interface of Advantys DTM . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Creating and Modifying Island Configurations. . . . . . . . . . . . . . . . . . .
Online Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Direct Device Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Labeling Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
STB Island States . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
17
18
23
24
25
27
11
12
14
16
9
9
5
7
EIO0000000769 04/2016
3
4
EIO0000000769 04/2016
Safety Information
Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
EIO0000000769 04/2016
5
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and its installation, and has received safety training to recognize and avoid the hazards involved.
6
EIO0000000769 04/2016
About the Book
At a Glance
Document Scope
This document will acquaint you with the Advantys DTM for STB on Modbus TCP as part of the
Advantys Configuration Software. It tells you how to install the DTM Library, which contains a DTM for STB Modbus TCP NIMs.
This manual is written for an Advantys user, who will configure STB Modbus TCP NIMs with the
Advantys DTM.
For basic information about the Advantys Configuration Software, please refer to the Advantys
Configuration Software User Manual.
Validity Note
Advantys DTM is part of Advantys Configuration Software version 5.5 and later.
Related Documents
Title of Documentation
Advantys Configuration Software User Manual
Reference Number
ENG: 33003486
FRE: 33003487
GER: 33003488
ITA: 33003490
SPA: 33003489
You can download these technical publications and other technical information from our website at http://download.schneider-electric.com
EIO0000000769 04/2016
7
8
Product Related Information
WARNING
LOSS OF CONTROL
The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical control functions, provide a means to achieve a safe state during and after a path failure. Examples of critical control functions are emergency stop and overtravel stop, power outage and restart.
Separate or redundant control paths must be provided for critical control functions.
System control paths may include communication links. Consideration must be given to the implications of unanticipated transmission delays or failures of the link.
Observe all accident prevention regulations and local safety guidelines.
1
Each implementation of this equipment must be individually and thoroughly tested for proper operation before being placed into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
1 For additional information, refer to NEMA ICS 1.1 (latest edition), "Safety Guidelines for the
Application, Installation, and Maintenance of Solid State Control" and to NEMA ICS 7.1 (latest edition), "Safety Standards for Construction and Guide for Selection, Installation and Operation of
Adjustable-Speed Drive Systems" or their equivalent governing your particular location.
EIO0000000769 04/2016
Advantys Device Type Manager
Installation
EIO0000000769 04/2016
Installation
Chapter 1
Installation
Installing and Uninstalling Advantys DTM
Installing the Advantys DTM
The installation of the Advantys Configuration Software includes the optional installation of the
Advantys DTM. The Advantys DTM is supplied on the same CD as the Advantys Configuration
Software. During installation of the Advantys Configuration Software you can decide whether you want to install the Advantys DTM or not. By default, the Advantys DTM is installed automatically with the Advantys Configuration Software.
It is not possible to install Advantys DTMs separately, without installing the Advantys Configuration
Software.
Uninstalling the Advantys DTM
Advantys DTMs are uninstalled with the Advantys Configuration Software uninstalling procedure.
It is not possible to uninstall Advantys DTMs separately from the Advantys Configuration Software.
NOTE: For details on the installation / uninstall processes of the Advantys Configuration Software see the Advantys Configuration Software User Manual.
EIO0000000769 04/2016
9
Installation
10
EIO0000000769 04/2016
Advantys Device Type Manager
Functional Description
EIO0000000769 04/2016
Functional Description
Chapter 2
Functional Description
What Is in This Chapter?
This chapter contains the following topics:
Topic
Functional Description
User Interface of Advantys DTM
Creating and Modifying Island Configurations
Online Functions
Direct Device Communication
Labeling Objects
STB Island States
Page
EIO0000000769 04/2016
11
Functional Description
Functional Description
Purpose of Advantys DTM
The Advantys DTM allows you to manage your STB Modbus TCP Island configurations by using
Schneider software tools such as Unity Pro version 6.0 and later.
The Advantys DTM provides the following capabilities:
creating and modifying configurations
configuration upload / download monitoring providing process channels for I/O mapping print configuration
In order to perform some of these functions, the Advantys DTM invokes the Advantys Configuration
Software.
Adding the Advantys DTM to Your Schneider Software Tool
After installing your Advantys DTM, it should be added to the DTM catalog in your Schneider software tool before it can be used. Please refer to your Schneider software tool documentation how to do this.
Adding an Island to Your Network
To add an Island to your network, proceed as follows:
Step
1
2
3
Action
Select the communication module for Modbus TCP and add it to the network view.
Select the device specific Advantys DTM and connect it to the Modbus TCP communication module.
Configure your IP parameters.
12
EIO0000000769 04/2016
Functional Description
Advantys Configuration Software Startup Behavior
In order to perform some functions, the Advantys DTM invokes the Advantys Configuration
Software.
You cannot run multiple instances of the Advantys Configuration Software simultaneously. The
Advantys DTM behaves as described in the following table:
Status
Advantys Configuration
Software is already running as a standalone application – started from the Start menu.
Advantys Configuration
Software is already running – started from the Advantys DTM.
Action
You click the Start Advantys button in
Advantys DTM to start Advantys
Configuration Software.
You try to start Advantys Configuration
Software from the Start menu.
Result
You are prompted to close the standalone application before starting the software from Advantys DTM.
You are prompted to close the running instance before Advantys Configuration
Software is started as standalone application.
Interactions when Running Multiple DTM Instances
Unlike the Advantys Configuration Software, it is allowed to run multiple instances of Advantys
DTM on your PC. If the Advantys Configuration Software is open when you switch between the open Advantys DTM instances, the following interactions are possible:
If...
you have not changed the configuration of the already open Advantys Configuration Software instance, you have changed the configuration of the already open Advantys Configuration Software instance,
Then ...
Advantys Configuration Software automatically closes the already open configuration and opens the new configuration.
you will be prompted to either save or reject your modification before the new configuration is displayed.
EIO0000000769 04/2016
13
Functional Description
User Interface of Advantys DTM
Island Window of Advantys DTM
The Island window of Advantys DTM is similar to the Island window of the Advantys Configuration
Software. You can differentiate the 2 windows by the gray background with its pattern of circles that appears in the DTM window.
14
1 launch Advantys Configuration Software button
2 Island window
3 network address indicator
4 zoom level control
5 status indicator
EIO0000000769 04/2016
Functional Description
Link Status
Multiple instances of the Advantys DTM can be run on your computer, but only one can be linked to the Advantys Configuration Software at the same time. Circles in the background of the
Advantys DTM Island view are used to let you know whether an Advantys DTM is linked to the
Advantys Configuration Software.
The following table indicates the link status between the Advantys DTM and the Advantys
Configuration Software:
Color gray blue orange
Meaning not linked linked
Advantys DTM is linked to Advantys Configuration Software and the current configuration has been modified. The modifications have not been saved yet.
Inoperable Configuration
If you launch the Advantys Configuration Software from the Advantys DTM when the Advantys
DTM contains a configuration that could not be built or that has become invalid, the Island window of Advantys DTM displays the following pattern in its background.
EIO0000000769 04/2016
15
Functional Description
Creating and Modifying Island Configurations
Limitations
WARNING
UNEXPECTED EQUIPMENT OPERATION
Provide meaningful names for the STB DTM instances.
Verify that at any time that you can modify the configuration of the intended Island.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Supported NIMs
The following network interface modules (NIM) are supported by Advantys DTM:
STBNIP2212 V2.••
STBNIP2311 V3.••
The following legacy network interface modules (NIM) are supported by Advantys DTM:
STBNIP2212 V1.••
STBNIP2311 V2.••
Saving your Configuration
Click on Save to save your configuration.
NOTE: If your configuration is not valid, a message box informs you and indicates the reason in the log window.
16
EIO0000000769 04/2016
Functional Description
Online Functions
Availability of the Online Menu in the Advantys Configuration Software
The commands of the Online menu in the Advantys Configuration Software are available only when the Schneider software tool is online.
For a detailed description of the Online menu commands refer to the Advantys Configuration
Software User Manual.
Establishing a Connection to the Island via the Schneider Software Tool
To establish a connection to the Island via the Schneider software tool, right-click the entry of the
Advantys DTM and select the Connect command from the context menu.
This command automatically deactivates the Direct Device Communication function, if it is active, and establishes a connection to the Island via the Schneider software tool. An active connection is indicated in the status bar by the status information Connected.
NOTE: The Advantys Configuration Software does not check the connection status after the connection has been established. If the physical connection is lost, the status indication will not be updated to Disconnected.
Store Data to Device
Storing data to the device can be performed in the following different ways:
via the Download into the Island command of the Online menu in the Advantys Configuration
Software by right-clicking the entry of the Advantys DTM in the Schneider software tool and selecting the
Store data to device function command from the context menu
Both commands initiate the same process.
Load Data From Device
Loading data from device can be done in the following way:
Step
1
2
3
Action
Set the Advantys DTM to online state.
Lauch the Advantys Configuration Software from the DTM.
Select the command Upload from the Island in the Advantys Configuration
Software.
NOTE: The Load data from device function in the context menu of the Advantys DTM is a standard
DTM function but with the Advantys DTM it has no effect.
EIO0000000769 04/2016
17
Functional Description
Direct Device Communication
Overview
When you start commissioning of a system, the controller may not be present. The Direct Device
Connection function allows you to connect directly to the island for creating or modifying your island configuration during this situation. After the controller is present the Direct Device Configuration function should not be used anymore for managing your islands but only for diagnostic purposes.
NOTE: It is strongly recommended to use the Direct Device Configuration function for configuration tasks only in the commissioning phase when the controller is not yet present.
The figure below illustrates the differences between normal connection via the controller (shown in item 3 the upper part of the figure) and direct device connection (in the lower part of the figure):
18
1 Advantys STB
2 Ethernet
3 controller
EIO0000000769 04/2016
Functional Description
Since the changes to the configuration made via Direct Device Communication in test mode or after configuration download directly become effective in the Physical Island, only use this connection mode for commissioning tasks.
Enabling the Direct Device Communication Function
To enable the Direct Device Communication function, proceed as follows:
Step
1
2
Action
Right-click the entry of your Advantys DTM in the Schneider software tool and select Device → Device menu → Additional functions → Direct Device Communication from the context menu.
Select the check box Enable Direct Device Communication.
EIO0000000769 04/2016
19
Functional Description
Step
3
Action
Click the OK button.
Result: Immediately the background of the Advantys DTM changes to a pattern with flashes to indicate that a link to the physical Island exists via direct device communication. Any changes to the configuration made in test mode or after configuration download will directly become effective in the Island.
20
EIO0000000769 04/2016
Functional Description
Disabling the Direct Device Communication Function
To disable the Direct Device Communication function, proceed as follows:
Step
1
2
Action
Right-click the entry of your Advantys DTM in the Schneider software tool and select Device → Device menu → Additional functions → Direct Device Communication from the context menu.
Deselect the check box Enable Direct Device Communication.
EIO0000000769 04/2016
21
Functional Description
Step
3
Action
Click the OK button.
Result: Immediately the background of the Advantys DTM changes back to the standard pattern to indicate that the Direct Connection function was disabled and that the connection between the DTM and the island was aborted.
22
EIO0000000769 04/2016
Functional Description
Labeling Objects
Introduction
The Advantys Configuration Software allows you to assign meaningful names to I/O data objects in your configuration, so-called user defined labels. For this purpose the Advantys Configuration
Software should be launched from the DTM.
The user defined labels can be assigned inside the Advantys Configuration Software:
In the Parameters tab of a module if the data object is a module parameter.
In the I/O Image tab of a module if the data object is an I/O data object.
In the Label Editor of the Advantys Configuration Software
The names for the selected data objects are displayed in the I/O Image Overview and the I/O
Image Animation dialog boxes and in the Module Editor. The labels will also be provided as I/O data in the exposed I/O configuration. For a detailed description how to assign user defined labels to Advantys I/O data objects refer to the Advantys Configuration Software User Manual.
NOTE: If any extended character is present in the labels, the character is replaced by letter x. For example, the characters such as ä, Ü, à, and so on, are replaced by the character x.
Using I/O Labels With a Schneider Software Tool
After naming the definition of user defined labels for Advantys I/O data objects, the DTM for STB on Modbus TCP provides these user defined labels as symbolic variable names to the Schneider software tool.
The following table describes how user defined labels will be displayed inside the Schneider software tool depending on the data object level:
Definition of User Defined Label in the Advantys DTM
No user label defined
Representation of Data Object Inside Schneider software tool
User defined label at Byte level
All I/O data objects will be displayed as variables from type Byte with default symbolic names.
The I/O data objects will be displayed as variables from type Byte with symbolic names based on the entered user defined label.
User defined label only at Bit level The I/O data objects will be displayed as variables from type Bit with symbolic names based on the entered user defined label.
NOTE: The definition of user defined labels at Byte level and Bit level for the same I/O data object is possible. In this case the I/O data object is displayed as variable from type Byte with symbolic name based on the entered user defined label at Byte level.
EIO0000000769 04/2016
23
Functional Description
STB Island States
Different STB Island States
This table lists the possible Island states, shown in the status bar in online mode:
Island State
0x00-Initializing
0x40-Reset
0x60-Configuration
0x62-Auto-Addressing
0x80-Pre-Operational
0x81-Non-Mandatory
Module Mismatch
0x82-Mandatory Module
Mismatch
0x83-Configuration
Mismatch blink 3 blink 3 off
A0-Running
A1-Running (...)
A2-Stopped (...)
C0-Stopped
Green blink 2 off blink 1
Red blink 2 off off off blink 8 blink R off blink 3 on on on blink 4 off blink 3 blink 2 blink R off blink 3 blink 2 off
Description
The Island bus is powering up (self test in progress).
The Island bus is initializing but not started or without power.
The Island bus has been put in the pre-operational state by the RST button, or it has been reset by the software.
The contents of the removable memory card is invalid.
The NIM is configuring or auto-configuring the Island bus, which is not started.
Initialization is complete, the Island bus is configured, the configuration matches – the Island bus is not started.
Configuration mismatch – non-mandatory or unexpected modules in the configuration do not match; the Island bus is not started.
Configuration mismatch – at least 1 mandatory module does not match; the Island bus is not started.
Detected error; so severe that no more communication with the
Island bus is possible and the NIM stops the Island. These are the detected errors:
internally detected error
module ID mismatch incorrect auto-addressing incorrect configuration of mandatory module detected error in process image incorrect auto-configuration/incorrect configuration
detected error in Island bus management detected error in application parameter detected error in receive/transmit queue software overrun
The Island bus is operational.
At least 1 standard module does not match – the Island bus is operational with a configuration mismatch.
Serious configuration mismatch. The Island is in pre-operational mode because of 1 or more mismatched mandatory modules.
The Island bus is stopped, no more communication with it possible.
24
EIO0000000769 04/2016
Advantys Device Type Manager
Glossary
EIO0000000769 04/2016
Glossary
D
DTM
A DTM (Device Type Manager) is a kind of device driver, which is provided by the field device vendor. The DTM contains the device specific information and provides a graphical user interface.
The DTM can be used to perform monitoring tasks and configuration tasks on the specific device.
A DTM is not a standalone application, it requires an FDT Frame Application to run.
F
FDT
The FDT (Field Device Tool) technology standardizes the communication interface between field devices and systems ( www.fdtgroup.org
).
N
NIM network interface module: This module is the interface between an Island bus andthe fieldbus network of which the Island is a part. A NIM enables the I/O on theIsland to be treated as a single node on the fieldbus. The NIM also provides 5 V oflogic power to the Advantys STB I/O modules in the same segment as the NIM.
The following types of NIM are available:
Networking: a group of standard network interface modules (NIMs)
Networking (Basic): a group of basic network interface modules
Networking (Legacy): a group of standard network interface modules with older versions
S
STB smart terminal block
EIO0000000769 04/2016
25
Glossary
26
EIO0000000769 04/2016
Advantys Device Type Manager
Index
EIO0000000769 04/2016
Index
C
creating island configurations, 16
D direct device communications, downloading,
F
I
Island states,
L labeling objects,
M
modifying island configurations, 16
U
user interface,
EIO0000000769 04/2016
27
Index
28
EIO0000000769 04/2016