Schneider Electric Modicon M251 User Guide
விளம்பரம்
விளம்பரம்
SQL Gateway
EIO0000002417 04/2020
Modicon M251
Logic Controller
User Guide
08/2022 www.se.com
Table of Contents
1 Modicon M251 Logic Controller - Programming Guide. . . . . . . . . . . .
Part I
2 Modicon M251 Logic Controller - System Functions and Variables
PLCSystem Library Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Part II
3 Modicon M251 Logic Controller - Hardware Guide. . . . . . . . . . . . . . .
Part III
EIO0000004273.03 08/2022
2
Modicon M251
Logic Controller
Programming Guide
EIO0000003089.05
05/2022 www.se.com
Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its subsidiaries referred to in this guide are the property of Schneider Electric SE or its subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and furnished for informational use only. No part of this guide may be reproduced or transmitted in any form or by any means (electronic, mechanical, photocopying, recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide or its content, except for a non-exclusive and personal license to consult it on an "as is" basis. Schneider Electric products and equipment should be installed, operated, serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational content of this material or consequences arising out of or resulting from the use of the information contained herein.
As part of a group of responsible, inclusive companies, we are updating our communications that contain non-inclusive terminology. Until we complete this process, however, our content may still contain standardized industry terms that may be deemed inappropriate by our customers.
© 2022 – Schneider Electric. All rights reserved.
Table of Contents
EIO0000003089.05
About the Modicon M251 Logic Controller ..................................................13
M251 Logic Controller Description........................................................13
How to Configure the Controller .................................................................15
How to Configure the Controller ...........................................................15
Supported Standard Data Types ................................................................18
Supported Standard Data Types ..........................................................18
Controller Memory Organization...........................................................19
RAM Memory Organization..................................................................20
Non-Volatile Memory Organization .......................................................22
Relocation Table .................................................................................25
Maximum Number of Tasks .................................................................28
Task Configuration Screen...................................................................28
System and Task Watchdogs ...............................................................32
Default Task Configuration...................................................................33
Controller States and Behaviors ................................................................35
Controller State Diagram .....................................................................35
Controller States Description ...............................................................38
State Transitions and System Events ...................................................40
Controller States and Output Behavior ............................................41
Commanding State Transitions ......................................................43
Error Detection, Types, and Management .......................................50
Remanent Variables ......................................................................51
Controller Parameters .........................................................................53
Communication Settings......................................................................54
Ethernet Services ...............................................................................57
Expansion Modules Configuration..............................................................67
TM4/TM3/TM2 Expansion Modules Configuration .................................67
TM3 I/O Configuration General Description...........................................68
TM3 I/O Bus Configuration ..................................................................71
Optional I/O Expansion Modules ..........................................................72
Ethernet Features, Functions and Services...........................................75
Presentation .................................................................................75
IP Address Configuration ...............................................................77
Modbus TCP Client/Server ............................................................81
Web Server ..................................................................................82
3
4
FTP Server ...................................................................................92
FTP Client ....................................................................................93
SNMP ..........................................................................................93
Controller as a Target Device on EtherNet/IP...................................94
Controller as a Slave Device on Modbus TCP ............................... 112
Changing the Modbus TCP Port ................................................... 116
Firewall Configuration ....................................................................... 117
Introduction ................................................................................ 117
Dynamic Changes Procedure....................................................... 119
Firewall Behavior ........................................................................ 119
Firewall Script Commands ........................................................... 121
Industrial Ethernet Manager .................................................................... 125
Industrial Ethernet............................................................................. 125
DHCP Server ................................................................................... 128
Fast Device Replacement.................................................................. 128
Serial Line Configuration ................................................................... 129
Machine Expert Network Manager ..................................................... 130
Modbus Manager.............................................................................. 131
ASCII Manager ................................................................................. 134
Modbus Serial IOScanner.................................................................. 135
Adding a Device on the Modbus Serial IOScanner............................... 137
ControlChannel: Enables or Disables a Communication
Adding a Modem to a Manager .......................................................... 144
CANopen Configuration .......................................................................... 145
CANopen Interface Configuration....................................................... 145
J1939 Interface Configuration ............................................................ 148
OPC UA Server Configuration ................................................................. 151
OPC UA Server Overview.................................................................. 151
OPC UA Server Configuration............................................................ 152
OPC UA Server Symbols Configuration .............................................. 154
OPC UA Server Performance ............................................................ 155
Post Configuration Presentation......................................................... 158
Post Configuration File Management.................................................. 159
Post Configuration Example .............................................................. 161
Connecting a Modicon M251 Logic Controller to a PC ............................... 164
Connecting the Controller to a PC ...................................................... 164
SD Card Commands ......................................................................... 167
Firmware Management ........................................................................... 173
Updating Modicon M251 Logic Controller Firmware ............................. 173
Updating TM3 Expansion Modules Firmware ...................................... 175
Software and Firmware Compatibilities ............................................... 178
Appendices
.............................................................................................. 179
EIO0000003089.05
Functions to Get/Set Serial Line Configuration in User Program ................. 182
GetSerialConf: Get the Serial Line Configuration ................................. 182
SetSerialConf: Change the Serial Line Configuration ........................... 183
SERIAL_CONF: Structure of the Serial Line Configuration Data
Processing Performance ................................................................... 186
Glossary
Index
EIO0000003089.05
5
Safety Information
Important Information
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
!
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
!
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
!
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
Please Note
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and its installation, and has received safety training to recognize and avoid the hazards involved.
EIO0000003089.05
7
About the Book
Document Scope
The purpose of this document is to help you program and operate your Modicon
M251 Logic Controller with the EcoStruxure Machine Expert software.
NOTE: Read and understand this document and all
before installing, operating, or maintaining your Modicon M251 Logic
Controller.
The Modicon M251 Logic Controller users should read through the entire document to understand its features.
Validity Note
This document has been updated for the release of EcoStruxure TM Machine
Expert V2.0.3.
The technical characteristics of the devices described in the present document also appear online. To access the information online, go to the Schneider Electric home page www.se.com
.
The characteristics that are described in the present document should be the same as those characteristics that appear online. In line with our policy of constant improvement, we may revise content over time to improve clarity and accuracy. If you see a difference between the document and online information, use the online information as your reference.
8 EIO0000003089.05
Related Documents
Title of Documentation
EcoStruxure Machine Expert Programming
Guide
Reference Number
EIO0000002854 (ENG)
EIO0000002855 (FRE)
EIO0000002856 (GER)
EIO0000002858 (SPA)
EIO0000002857 (ITA)
EIO0000002859 (CHS)
Modicon M251 Logic Controller Hardware Guide EIO0000003101 (ENG)
EIO0000003102 (FRE)
EIO0000003103 (GER)
EIO0000003104 (SPA)
EIO0000003105 (ITA)
EIO0000003106 (CHS)
EcoStruxure Machine Expert Industrial Ethernet
User Guide
EIO0000003053 (ENG)
EIO0000003054 (FRE)
EIO0000003055 (GER)
EIO0000003056 (SPA)
EIO0000003057 (ITA)
EIO0000003058 (CHS)
Modicon TM4 Expansion Modules Programming
Guide
Modicon TM3 Modules Configuration
Programming Guide
Modicon TM3 Bus Coupler - Programming
Guide (EcoStruxure Machine Expert)
EIO0000003149 (ENG)
EIO0000003150 (FRE)
EIO0000003151 (GER)
EIO0000003152 (SPA)
EIO0000003153 (ITA)
EIO0000003154 (CHS)
EIO0000003119 (ENG)
EIO0000003120 (FRE)
EIO0000003121 (GER)
EIO0000003122 (SPA)
EIO0000003123 (ITA)
EIO0000003124 (CHS)
EIO0000003635 (ENG)
EIO0000003636 (FRA)
EIO0000003637 (GER)
EIO0000003638 (SPA)
EIO0000003639 (ITA)
EIO0000003640 (CHS)
Modicon TM2 Modules Configuration
Programming Guide
EIO0000003432 (ENG)
EIO0000003433 (FRE)
EIO0000003434 (GER)
EIO0000003435 (SPA)
EIO0000003436 (ITA)
EIO0000003437 (CHS)
EIO0000003089.05
9
10
Title of Documentation
Modicon M251 Logic Controller System
Functions and Variables PLCSystem Library
Guide
Modicon TM3 Expert I/O Modules - HSC Library
Guide
EcoStruxure Machine Expert -
FtpRemoteFileHandling Library Guide
EcoStruxure Machine Expert - SnmpManager
Library Guide
EcoStruxure Machine Expert - Manage a Cyclic
Task Interval - Toolbox_Advance Library Guide
EcoStruxure Machine Expert - Data Logging
Functions - DataLogging Library Guide
EcoStruxure Machine Expert - Modem
Functions - Modem Library Guide
EIO0000002797 (ENG)
EIO0000002798 (FRE)
EIO0000002799 (GER)
EIO0000002801 (SPA)
EIO0000002800 (ITA)
EIO0000002802 (CHS)
EIO0000000946 (ENG)
EIO0000000947 (FRE)
EIO0000000948 (GER)
EIO0000000950 (SPA)
EIO0000000949 (ITA)
EIO0000000951 (CHS)
EIO0000002938 (ENG)
EIO0000002939 (FRE)
EIO0000002940 (GER)
EIO0000002942 (SPA)
EIO0000002941 (ITA)
EIO0000002943 (CHS)
Reference Number
EIO0000003095 (ENG)
EIO0000003096 (FRE)
EIO0000003097 (GER)
EIO0000003098 (SPA)
EIO0000003099 (ITA)
EIO0000003100 (CHS)
EIO0000003683 (ENG)
EIO0000003684 (FRE)
EIO0000003685 (GER)
EIO0000003686 (SPA)
EIO0000003687 (ITA)
EIO0000003688 (CHS)
EIO0000003689 (POR)
EIO0000003690 (TUR)
EIO0000002779 (ENG)
EIO0000002780 (FRE)
EIO0000002781 (GER)
EIO0000002783 (SPA)
EIO0000002782 (ITA)
EIO0000002784 (CHS)
EIO0000000552 (ENG)
You can download these technical publications and other technical information from our website at www.se.com/ww/en/download/ .
EIO0000003089.05
Product Related Information
WARNING
LOSS OF CONTROL
• The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical control functions, provide a means to achieve a safe state during and after a path failure. Examples of critical control functions are emergency stop and overtravel stop, power outage and restart.
• Separate or redundant control paths must be provided for critical control functions.
• System control paths may include communication links. Consideration must be given to the implications of unanticipated transmission delays or failures of the link.
• Observe all accident prevention regulations and local safety guidelines.
1
• Each implementation of this equipment must be individually and thoroughly tested for proper operation before being placed into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
1 For additional information, refer to NEMA ICS 1.1 (latest edition), "Safety
Guidelines for the Application, Installation, and Maintenance of Solid State
Control" and to NEMA ICS 7.1 (latest edition), "Safety Standards for Construction and Guide for Selection, Installation and Operation of Adjustable-Speed Drive
Systems" or their equivalent governing your particular location.
WARNING
UNINTENDED EQUIPMENT OPERATION
• Only use software approved by Schneider Electric for use with this equipment.
• Update your application program every time you change the physical hardware configuration.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Terminology Derived from Standards
The technical terms, terminology, symbols and the corresponding descriptions in this manual, or that appear in or on the products themselves, are generally derived from the terms or definitions of international standards.
In the area of functional safety systems, drives and general automation, this may include, but is not limited to, terms such as safety , safety function , safe state , fault , fault reset , malfunction , failure , error , error message , dangerous , etc.
EIO0000003089.05
11
12
Among others, these standards include:
Standard
IEC 61131-2:2007
ISO 13849-1:2015
EN 61496-1:2013
ISO 12100:2010
EN 60204-1:2006
ISO 14119:2013
ISO 13850:2015
IEC 62061:2015
IEC 61508-1:2010
IEC 61508-2:2010
IEC 61508-3:2010
IEC 61784-3:2016
2006/42/EC
2014/30/EU
2014/35/EU
Description
Programmable controllers, part 2: Equipment requirements and tests.
Safety of machinery: Safety related parts of control systems.
General principles for design.
Safety of machinery: Electro-sensitive protective equipment.
Part 1: General requirements and tests.
Safety of machinery - General principles for design - Risk assessment and risk reduction
Safety of machinery - Electrical equipment of machines - Part 1: General requirements
Safety of machinery - Interlocking devices associated with guards -
Principles for design and selection
Safety of machinery - Emergency stop - Principles for design
Safety of machinery - Functional safety of safety-related electrical, electronic, and electronic programmable control systems
Functional safety of electrical/electronic/programmable electronic safetyrelated systems: General requirements.
Functional safety of electrical/electronic/programmable electronic safetyrelated systems: Requirements for electrical/electronic/programmable electronic safety-related systems.
Functional safety of electrical/electronic/programmable electronic safetyrelated systems: Software requirements.
Industrial communication networks - Profiles - Part 3: Functional safety fieldbuses - General rules and profile definitions.
Machinery Directive
Electromagnetic Compatibility Directive
Low Voltage Directive
In addition, terms used in the present document may tangentially be used as they are derived from other standards such as:
Standard
IEC 60034 series
IEC 61800 series
IEC 61158 series
Description
Rotating electrical machines
Adjustable speed electrical power drive systems
Digital data communications for measurement and control – Fieldbus for use in industrial control systems
Finally, the term zone of operation may be used in conjunction with the description of specific hazards, and is defined as it is for a hazard zone or danger zone in the
Machinery Directive ( 2006/42/EC ) and ISO 12100:2010 .
NOTE: The aforementioned standards may or may not apply to the specific products cited in the present documentation. For more information concerning the individual standards applicable to the products described herein, see the characteristics tables for those product references.
EIO0000003089.05
About the Modicon M251 Logic Controller
About the Modicon M251 Logic Controller
Introduction
This chapter provides information about the Modicon M251 Logic Controller and devices that EcoStruxure Machine Expert can configure and program.
M251 Logic Controller Description
Overview
The M251 Logic Controller has various powerful features and can service a wide range of applications.
Software configuration, programming, and commissioning are achieved with the
EcoStruxure Machine Expert software described in the EcoStruxure Machine
Expert Programming Guide and in the
M251 Logic Controller Programming Guide, page 8
.
Programming Languages
The M251 Logic Controller is configured and programmed with the EcoStruxure
Machine Expert software, which supports the following IEC 61131-3 programming languages:
• IL: Instruction list
• ST: Structured text
• FBD: Function block diagram
• SFC: Sequential function chart
• LD: Ladder diagram
EcoStruxure Machine Expert software can also be used to program this controller using CFC (continuous function chart) language.
Power Supply
The power supply of the M251 Logic Controller is 24 Vdc.
Real Time Clock
The M251 Logic Controller includes a Real Time Clock (RTC) system (see
Modicon M251 Logic Controller, Hardware Guide).
Run/Stop
The M251 Logic Controller can be operated by the following:
• a hardware Run/Stop switch
• an EcoStruxure Machine Expert software command
EIO0000003089.05
13
About the Modicon M251 Logic Controller
Memory
This table describes the different types of memory:
Memory Type
RAM
Flash
Size
64 Mbytes, of which 8 Mbytes available for the application
128 Mbytes
Used
To execute the application.
To save the program and data in case of a power interruption.
Removable Storage
M251 Logic Controllers include an embedded SD card slot (see Modicon M251
Logic Controller, Hardware Guide).
The main uses of the SD card are:
• Initializing the controller with a new application
•
Updating the controller and expansion module firmware, page 173
•
Applying post configuration files to the controller, page 158
• Applying recipes
• Receiving data logging files
•
Backup Data Logging File, page 25
Embedded Communication Features
The M251 Logic Controller native communication ports include (depending on the controller reference):
• CANopen Master
• Ethernet
• USB Mini-B
• Serial Line
Expansion Module and Bus Coupler Compatibility
Refer to the compatibility tables in the EcoStruxure Machine Expert - Compatibility and Migration User Guide.
M251 Logic Controllers
Reference
TM251MESC
TM251MESE
Digital Inputs Digital Outputs Communication Ports
0 0 1 serial line port
1 USB mini-B programming port
0 0
1 dual port Ethernet switch
1 CANopen port
1 serial line port
1 USB mini-B programming port
1 dual port Ethernet switch
1 Ethernet port for fieldbus
14 EIO0000003089.05
How to Configure the Controller
How to Configure the Controller
Introduction
This chapter shows the default configuration of a project.
How to Configure the Controller
Introduction
First, create a new project or open an existing project in the EcoStruxure Machine
Expert software.
Refer to the EcoStruxure Machine Expert Programming Guide for information on how to:
• add a controller to your project
• add expansion modules to your controller
• replace an existing controller
• convert a controller to a different but compatible device
Devices Tree
The Devices tree presents a structured view of the hardware configuration. When you add a controller to your project, a number of nodes are added to the Devices tree , depending on the functions the controller provides.
EIO0000003089.05
Item
IO_Bus
COM_Bus
Ethernet_x
Serial_Line_x
CAN_x
Use to Configure...
Expansion modules connected to the logic controller
Communications bus of the logic controller
Embedded Ethernet, serial line, or CANopen communications interfaces
NOTE: Ethernet and CANopen are only available on some references.
15
How to Configure the Controller
Applications Tree
The Applications tree allows you to manage project-specific applications as well as global applications, POUs, and tasks.
Tools Tree
The Tools tree allows you to configure the HMI part of your project and to manage libraries.
16 EIO0000003089.05
Libraries
Introduction
This chapter describes the default libraries of the Modicon M251 Logic Controller.
Libraries
Introduction
Libraries provide functions, function blocks, data types, and global variables that can be used to develop your project.
The Library Manager of EcoStruxure Machine Expert provides information about the libraries included in your project and allows you to install new ones. For more information on the Library Manager , refer to the EcoStruxure Machine Expert
Programming Guide.
Modicon M251 Logic Controller
Library Name
IoStandard
Standard
Util
M251 PLCSystem
PLCCommunication
Relocation Table
ModbusTCPIOScanner
EtherNetIP Scanner
EtherNetIP Explicit Messaging
Additional libraries:
• 3S CANopenStack
• FDT_CANOpenDriver
• CAA CiA 405
When you select a Modicon M251 Logic Controller for your application,
EcoStruxure Machine Expert automatically loads these libraries:
Description
CmpIoMgr configuration types, ConfigAccess , Parameters, and help functions: manages the I/Os in the application.
Contains functions and function blocks that are required matching IEC61131-3 as standard POUs for an IEC programming system. The standard POUs must be tied to the project (standard.library).
Analog Monitors, BCD Conversions, Bit/Byte Functions, Controller Datatypes, Function
Manipulators, Mathematical Functions, Signals.
Contains functions and variables to get information and send commands to the controller system.
(See Modicon M251 Logic Controller, System Functions and Variables, PLCSystem Library Guide).
SysMem, Standard . These functions facilitate communications between specific devices. Most of them are dedicated to Modbus exchange. Communication functions are asynchronously processed regarding the application task that called the function. (See EcoStruxure Machine Expert, Modbus and ASCII Read/Write Functions, PLCCommunication Library Guide).
The relocation table allows you to organize data to optimize exchanges between the Modbus client and the controller, by regrouping non-contiguous data into a contiguous table of registers. See
TM251MESE only. Provides Modbus TCP IOScanner function blocks. (See ModbusTCPIOScanner
EcoStruxure Machine Expert Modbus TCP, User Guide).
TM251MESE only. Infrastructure function blocks to establish and close CIP connections and to build
Explicit Messaging request over EtherNet/IP. (See EcoStruxure Machine Expert EtherNet/IP, User
Guide).
TM251MESE only. Explicit Messaging over EtherNet/IP, to communicate with generic devices (e.g.
cameras) for which EcoStruxure Machine Expert does not offer a device integration. (See
EcoStruxure Machine Expert EtherNet/IP, User Guide).
The CAA CiA 405 library offers a set of function blocks to meet the requirements of the CiA405 for the access to the CANopen network from the application (IEC61131-3 program) of the controller
(CANopen master).
EIO0000003089.05
17
Supported Standard Data Types
Introduction
This chapter provides the different IEC data types supported by the controller.
Supported Standard Data Types
Supported Standard Data Types
The controller supports the following IEC data types:
Data Type
BOOL
BYTE
WORD
DWORD
LWORD
SINT
USINT
INT
UINT
DINT
UDINT
LINT
ULINT
REAL
LREAL
STRING
WSTRING
TIME
Lower Limit
FALSE
0
0
0
0
-128
0
-32,768
0
-2,147,483,648
0
-2 63
0
1.175494351e-38
2.225073858507201-
4e-308
1 character
1 character
0
Upper Limit
TRUE
255
65,535
4,294,967,295
2 64 -1
127
255
32,767
65,535
2,147,483,647
4,294,967,295
2 63 -1
2 64 -1
3.402823466e+38
1.797693134862315-
8e+308
–
–
4294967295
Information Content
1 Bit
8 Bit
16 Bit
32 Bit
64 Bit
8 Bit
8 Bit
16 Bit
16 Bit
32 Bit
32 Bit
64 Bit
64 Bit
32 Bit
64 Bit
1 character = 1 byte
1 character = 1 word
32 Bit
For more information on ARRAY , LTIME , DATE , TIME , DATE_AND_TIME , and
TIME_OF_DAY , refer to the EcoStruxure Machine Expert Programming Guide.
18 EIO0000003089.05
Memory Mapping
Introduction
This chapter describes the memory maps and sizes of the different memory areas in the Modicon M251 Logic Controller. These memory areas are used to store user program logic, data and the programming libraries.
Controller Memory Organization
Introduction
The controller memory is composed of two types of physical memory:
• The
contains files (application, configuration files, and so on).
• The
Random Access Memory (RAM), page 20
is used for application execution.
Files Transfers in Memory
EIO0000003089.05
19
Item
1
Controller State
–
File Transfer Events
Initiated automatically at
Power ON and Reboot
Connection
Internal
Description
Files transfer from non-volatile memory to RAM.
2 All states except
INVALID_OS (1)
Initiated by user Ethernet or USB programming port
The content of the RAM is overwritten.
Files can be transferred via:
•
•
• Controller Assistant
• EcoStruxure Machine Expert (see
EcoStruxure Machine Expert, Programming
Guide)
3 All states Initiated automatically by script (data transfer) or by power cycle (cloning) when an SD card is inserted
SD card Up/download with SD card (1) .
(1) If the controller is in the INVALID_OS state, the only accessible memory is the SD card and only for firmware upgrades.
NOTE: The modification of files in non-volatile memory does not affect a running application. Any changes to files in non-volatile memory are taken into account at the next reboot.
RAM Memory Organization
Introduction
This section describes the RAM (Random Access Memory) size for different areas of the Modicon M251 Logic Controller.
Memory Mapping
The RAM size is 64 Mbytes.
The RAM is composed of 2 areas:
• dedicated application memory
• OS memory
20 EIO0000003089.05
This table describes the dedicated application memory:
Area
System area
192 Kbytes
User area
8 Mbytes
Element
System Area Mappable Addresses
%MW0...%MW59999
System and diagnostic variables, page 21
(%MW60000...%MW60199)
This memory is accessible through Modbus requests only.
These must be read-only requests.
Dynamic Memory Area: Read Relocation Table, page 25
(%MW60200...%MW61999)
This memory is accessible through Modbus requests only.
These must be read-only requests.
System and diagnostic variables, page 21
(%MW62000...%MW62199)
This memory is accessible through Modbus requests only.
These can be read or write requests.
Dynamic Memory Area: Write Relocation Table, page 25
(%MW62200...%MW63999)
This memory is accessible through Modbus requests only.
These can be read or write requests.
%MW64000…%MW65535
Reserved
Retain and Persistent data, page 23
Symbols
Variables
Application
Libraries
Size
128 Kbytes
64 Kbytes
Dynamic allocation
System and Diagnostic Variables
Variables
PLC_R
PLC_W
ETH_R
ETH_W
PROFIBUS_R
SERIAL_R
SERIAL_W
TM3_MODULE_R
Description
Structure of controller read-only system variables.
Structure of controller read/write system variables.
Structure of Ethernet read-only system variables.
Structure of Ethernet read/write system variables.
Structure of PROFIBUS DP read-only system variables.
Structure of Serial Lines read-only system variables.
Structure of Serial Lines read/write system variables.
Structure of TM3 modules read-only system variables.
For more information on system and diagnostic variables, refer to Modicon M251
Logic Controller System Functions and Variables PLCSystem – Library Guide .
EIO0000003089.05
21
Memory Addressing
This table describes the memory addressing for the address sizes Double Word
(%MD), Word (%MW), Byte (%MB), and Bit (%MX):
Words Bytes Bits Double
Words
%MD0 %MW0
%MD1
%MD2
%MW1
%MW2
%MW3
%MW4
...
%MB6
%MB7
...
...
%MB8
...
%MB0
%MB1
%MB2
%MB3
%MB4
%MB5
%MX0.7
%MX1.7
%MX2.7
%MX3.7
%MX4.7
%MX5.7
%MX6.7
%MX7.7
...
...
%MX8.7
...
...
...
...
...
...
...
...
...
...
...
...
...
%MX0.0
%MX1.0
%MX2.0
%MX3.0
%MX4.0
%MX5.0
%MX6.0
%MX7.0
...
...
%MX8.0
...
Example of overlap of memory ranges:
%MD0 contains %MB0 (...) %MB3, %MW0 contains %MB0 and %MB1, %MW1 contains %MB2 and %MB3.
NOTE: The Modbus communication is asynchronous with the application.
Non-Volatile Memory Organization
Introduction
The non-volatile memory contains the file system used by the controller.
22 EIO0000003089.05
File Type
The Modicon M251 Logic Controller manages the following file types:
Type
Boot application
Application source
Post configuration
Description
This file resides in non-volatile memory and contains the compiled binary code of the executable application. Each time the controller is rebooted, the executable application is extracted from the boot application and copied into the controller RAM (1) .
Source file that can be uploaded from non-volatile memory to the PC if the source file is not available on the PC (2) .
File that contains Ethernet, serial line, and firewall parameters.
The parameters specified in the file override the parameters in the executable application at each reboot.
Files in which the controller logs events as specified by the application.
HTML pages displayed by the web server for the website embedded in the controller.
Data logging
HTML page
Operating System (OS) Controller firmware that can be written to non-volatile memory. The firmware file is applied at next reboot of the controller.
Remanent variables Retain variable
Retain-persistent variable
(1) : The creation of a boot application is optional in EcoStruxure Machine Expert, according to application properties. Default option is to create the boot application on download. When you download an application from EcoStruxure Machine Expert to the controller, you are transferring only the binary executable application directly to RAM
(2) : EcoStruxure Machine Expert does not support uploading of either the executable application or the boot application to a PC for modification. Program modifications must be made to the application source. When you download your application, you have the option to store the source file to non-volatile memory.
EIO0000003089.05
23
File Organization
Disk
/sys
/usr
/usr
/usr
Directory
OS
Web
App
Cfg
Log
Rcp
Syslog
Fdr/FDRS (4) only for
TM251MESE
/data –
...
–
/sd0 –
–
–
User files
(1) : v_XX.YY represents the version
(2) : if any
(3) : if
is configured
(4) : the Fdr/FDRS directory is hidden
File
This table shows the file organization of the non-volatile memory:
M241M251FW1v_XX.YY
(1)
M241M251FW2v_XX.YY
(1)
Version.ini
Index.htm
Conf.htm
Application.app
Application.crc
Application.map
Archive.prj
(2) settings.conf
(3)
OpcUASymbolConf.map
(3)
Machine.cfg
(2)
CodesysLateConf.cfg
(2)
UserDefinedLogName_1 .log
UserDefinedLogName_n .log
crashC1.txt
(2) crashC2.txt
(2) crashBoot.txt
(2)
PlcLog.txt
(2)
FwLog.txt
Device1.prm
Device2.prm
Content Up/Downloaded
Data Type
Firmware Firmware of core 1
Firmware of core 2
Control file for firmware version
HTML pages served by the web server for the website embedded in the controller.
Boot application
Application source
OPC UA configuration
OPC UA symbols configuration
Post configuration file, page 158
• Name of application to launch
• Routing table (main/sub net)
All *.log files created using the data logging functions (see EcoStruxure Machine Expert -
Data Logging Functions - DataLogging Library
Guide). You must specify the total number of files created and the names and contents of each log file.
Main directory for recipe
This file contains a record of detected system errors. For use by Schneider Electric Technical
Support.
–
–
Website
–
Application
–
Configuration
Configuration
Configuration
Configuration log file
–
–
Log file
This file contains system event data that is also visible online in EcoStruxure Machine Expert by viewing the Log tab of the
–
This file contains a record of firmware system events. For use by Schneider Electric Technical
Support.
–
Parameter files stored by the FDR client device1
Parameter files stored by the FDR client device2
–
Retained and persistent data
SD card. Removable
–
–
–
–
NOTE: For more information on libraries and available function blocks, refer to
.
24 EIO0000003089.05
Files Redirection
When system, program or certain user activity creates specific file types, the M251
Logic Controller examines the file extension and automatically moves the file to a corresponding folder in non-volatile memory.
The following table lists the file types that are moved in this way and the destination folder in non-volatile memory:
File extensions
*.app, *.ap_, *.err, *.crc, *.frc, *.prj
*.cfg, *.cf_
*.log
*.rcp, *.rsi
Non-volatile memory folder
/usr/App
/usr/Cfg
/usr/Log
/usr/Rcp
Backup Data Logging File
Data logging files can become large to the point of exceeding the space available in the file system. Therefore, you should develop a method to archive the log data periodically on an SD card. You could split the log data into several files, for example LogMonth1, LogMonth2 , and use the ExecuteScript (see Modicon
M251 Logic Controller, System Functions and Variables, PLCSystem Library
Guide) command to copy the first file to an SD card. Afterwards, you may remove it from the internal file system while the second file is accumulating data. If you allow the data logging file to grow and exceed the limits of the file size, you could lose data.
NOTICE
LOSS OF APPLICATION DATA
• Backup SD card data regularly.
• Do not remove power or reset the controller, and do not insert or remove the
SD card while it is being accessed.
Failure to follow these instructions can result in equipment damage.
Relocation Table
Introduction
The Relocation Table allows you to organize data to optimize communication between the controller and other equipment by regrouping non-contiguous data into a contiguous table of located registers, accessible through Modbus.
NOTE: A relocation table is considered as an object. Only one relocation table object can be added to a controller.
Relocation Table Description
This table describes the Relocation Table organization:
Register
60200...61999
62200...63999
Description
Dynamic Memory Area: Read Relocation Table
Dynamic Memory Area: Write Relocation Table
EIO0000003089.05
25
For further information, refer to Modicon M251 Logic Controller PLCSystem –
Library Guide .
Adding a Relocation Table
This table describes how to add a Relocation Table to your project:
Step
1
2
Action
Select the Application node in the Applications tree tab.
3
4
Click .
Click Add other objects > Relocation Table...
.
Result: The Add Relocation Table window is displayed.
Click Add .
Result: The new relocation table is created and initialized.
NOTE: As a relocation table is unique for a controller, its name is Relocation Table and cannot be changed.
Relocation Table Editor
The relocation table editor allows you to organize your variables in the relocation table.
To access the relocation table editor, double-click the Relocation Table node in the Tools tree tab:
26 EIO0000003089.05
This picture describes the relocation table editor:
EIO0000003089.05
Icon Element
New Item
Move Down
Move Up
Delete Item
Copy
Paste
Description
Adds an element to the list of system variables.
Moves down the selected element of the list.
Moves up the selected element of the list.
Removes the selected elements of the list.
Copies the selected elements of the list.
Pastes the elements copied.
-
-
-
-
-
Erase Empty
Item
ID
Variable
Address
Length
Validity
Removes all the elements of the list for which the "Variable" column is empty.
Automatic incremental integer (not editable).
The name or the full path of a variable (editable).
The address of the system area where the variable is stored (not editable).
Variable length in word.
Indicates if the entered variable is valid (not editable).
NOTE: If a variable is undefined after program modifications, the content of the cell is displayed in red, the related Validity cell is False, and Address is set to -1.
27
Tasks
Introduction
The Task Configuration node in the Applications tree allows you to define one or more tasks to control the execution of your application program.
The task types available are:
• Cyclic
• Freewheeling
• Event
• External event
This chapter begins with an explanation of these task types and provides information regarding the maximum number of tasks, the default task configuration, and task prioritization. In addition, this chapter introduces the system and task watchdog functions and explains its relationship to task execution.
Maximum Number of Tasks
Maximum Number of Tasks
The maximum number of tasks you can define for the Modicon M251 Logic
Controller is:
• Total number of tasks = 19
• Cyclic tasks = 5
• Freewheeling tasks = 1
• Event tasks = 8
• External event task = 1 (TM251MESC only)
Special Considerations for Freewheeling
A
does not have a fixed duration. In Freewheeling mode, each task scan starts when the previous scan has been completed and after a period of system processing (30% of the total duration of the Freewheeling task). If the system processing period is reduced to less than 15% for more than 3 seconds due to interruptions by other tasks, a system error is detected. For more information, refer to the
NOTE: You may wish to avoid using a Freewheeling task in a multi-task application when some high priority and time-consuming tasks are running.
Doing so may provoke a task Watchdog Timeout. You should not assign
CANopen to a freewheeling task. CANopen should be assigned to a cyclic task.
Task Configuration Screen
Screen Description
This screen allows you to configure the tasks. Double-click the task that you want to configure in the Applications tree to access this screen.
28 EIO0000003089.05
Each configuration task has its own parameters that are independent of the other tasks.
The Configuration window is composed of 4 parts:
Field Name
Priority
Type
Watchdog
POUs
The table describes the fields of the Configuration screen:
Definition
Configure the priority of each task with a number from 0 to 31 (0 is the highest priority, 31 is the lowest).
Only one task at a time can be running. The priority determines when the task runs: a higher priority task pre-empts a lower priority task.
NOTE: Do not assign tasks with the same priority. If there are yet other tasks that attempt to pre-empt tasks with the same priority, the result could be indeterminate and unpredictable. For important information, refer to
These task types are available:
•
•
•
•
To configure the
watchdog, page 32 , define these 2 parameters:
• Time : enter the timeout before watchdog execution.
• Sensitivity : defines the number of expirations of the watchdog timer before the controller stops program execution and enters a HALT state.
The list of POUs (Programming Organization Units) controlled by the task is defined in the task configuration window:
• To add a POU linked to the task, use the command Add Call and select the POU in the Input Assistant editor.
• To remove a POU from the list, use the command Remove Call .
• To replace the selected POU of the list by another one, use the command Change Call .
• POU s are executed in the order shown in the list. To move the POU s in the list, select a POU and use the command Move Up or Move Down .
NOTE: You can create as many POUs as you want. An application with several small POUs, as opposed to one large POU, can improve the refresh time of the variables in online mode.
EIO0000003089.05
29
Task Types
Introduction
The following section describes the various task types available for your program, along with a description of the task type characteristics.
Cyclic Task
A Cyclic task is assigned a fixed cycle time using the interval setting in the type section of the configuration subtab for that task. Each Cyclic task type executes as follows:
30
1.
2.
3.
4.
Read Inputs: The physical input states are written to the %I input memory variables and other system operations are executed.
Task Processing: The user code (POU, and so on) defined in the task is processed. The %Q output memory variables are updated according to your application program instructions but not yet written to the physical outputs during this operation.
Write Outputs: The %Q output memory variables are modified with the output forcing that has been defined; however, the writing of the physical outputs depends upon the type of output and instructions used.
For more information on defining the bus cycle task, refer to the
EcoStruxure Machine Expert Programming Guide and
Remaining Interval time: The controller firmware carries out system processing and other lower priority tasks.
NOTE: If you define too short a period for a cyclic task, it will repeat immediately after the write of the outputs and without executing other lower priority tasks or any system processing. This will affect the execution of all tasks and cause the controller to exceed the system watchdog limits, generating a system watchdog exception.
NOTE: When the task cycle time is set to a value less than 3 ms, the actual task duration should first be monitored through the Task Monitoring screen during commissioning to ensure that it is consistently lower than the configured task cycle time. If greater, the task cycle may not be respected without causing a task cycle watchdog time-out and the controller transitioning to a HALT state. To avoid this condition to a certain degree, when the task cycle time is set to a value of less than 3 ms, real limits of +1 ms are imposed if, on any given cycle, the calculated cycle time slightly exceeds the configured cycle time.
NOTE: Get and set the interval of a Cyclic Task by application using the
GetCurrentTaskCycle and SetCurrentTaskCycle function. (Refer to
EcoStruxure Machine Expert- Manage a Cyclic Task Interval - Toolbox_
Advance Library Guide for further details.)
EIO0000003089.05
Freewheeling Task
A Freewheeling task does not have a fixed duration. In Freewheeling mode, each task scan begins when the previous scan has been completed and after a short period of system processing. Each Freewheeling task type executes as follows:
Event Task
1.
2.
3.
4.
Read Inputs: The physical input states are written to the %I input memory variables and other system operations are executed.
Task Processing: The user code (POU, and so on) defined in the task is processed. The %Q output memory variables are updated according to your application program instructions but not yet written to the physical outputs during this operation.
Write Outputs: The %Q output memory variables are modified with the output forcing that has been defined; however, the writing of the physical outputs depends upon the type of output and instructions used.
For more information on defining the bus cycle task, refer to the
EcoStruxure Machine Expert Programming Guide and
.
System Processing: The controller firmware carries out system processing and other lower priority tasks (for example: HTTP management, Ethernet management, parameters management).
NOTE: If you want to define the task interval, refer to
This type of task is event-driven and is initiated by a program variable. It starts at the rising edge of the boolean variable associated to the trigger event unless preempted by a higher priority task. In that case, the Event task will start as dictated by the task priority assignments.
For example, if you have defined a variable called my_Var and would like to assign it to an Event, proceed as follows:
Step Action
1 Double-click the TASK in the Applications tree .
Select Event from the Type list in the Configuration tab.
2
3
4
Click the Input Assistant button to the right of the Event field.
Result : The Input Assistant window appears.
Navigate in the tree of the Input Assistant dialog box to find and assign the my_Var variable.
NOTE: When the event task is triggered at an excessive frequency, the controller will go to the HALT state (Exception). The maximum rate of events is
6 events per millisecond. If the event task is triggered at a higher frequency than this, the message 'ISR Count Exceeded' is logged in the application log page.
EIO0000003089.05
31
External Event Task
This type of task is event-driven and is initiated by the detection of a hardware or hardware-related function event. It starts when the event occurs unless preempted by a higher priority task. In that case, the External Event task will start as dictated by the task priority assignments.
The external event task is associated with the CAN Sync event. To associate the
CAN_1_SYNC event to an external event task, select it from the External event dropdown list in the Configuration tab.
NOTE: CAN Sync is a specific event object, depending on the CANopen manager configuration.
System and Task Watchdogs
Introduction
Two types of watchdog functionality are implemented for the Modicon M251 Logic
Controller:
• System Watchdogs : These watchdogs are defined in and managed by the controller firmware. These are not configurable by the user.
• Task Watchdogs : These watchdogs are optional watchdogs that you can define for each task. These are managed by your application program and are configurable in EcoStruxure Machine Expert.
System Watchdogs
Three system watchdogs are defined for the Modicon M251 Logic Controller. They are managed by the controller firmware and are therefore sometimes referred to as hardware watchdogs in the EcoStruxure Machine Expert online help. When one of the system watchdogs exceeds its threshold conditions, an error is detected.
The threshold conditions for the 3 system watchdogs are defined as follows:
• If all of the tasks require more than 85% of the processor resources for more than 3 seconds, a system error is detected. The controller enters the HALT state.
• If the total execution time of the tasks with priorities between 0 and 24 reaches 100% of processor resources for more than 1 second, an application error is detected. The controller responds with an automatic reboot into the
EMPTY state.
• If the lowest priority task of the system is not executed during an interval of 10 seconds, a system error is detected. The controller responds with an automatic reboot into the EMPTY state.
NOTE: System watchdogs are not configurable by the user.
Task Watchdogs
EcoStruxure Machine Expert allows you to configure an optional task watchdog for every task defined in your application program. (Task watchdogs are sometimes also referred to as software watchdogs or control timers in the
EcoStruxure Machine Expert online help). When one of your defined task watchdogs reaches its threshold condition, an application error is detected and the controller enters the HALT state.
32 EIO0000003089.05
When defining a task watchdog, the following options are available:
• Time : This defines the maximum execution time for a task. When a task takes longer than this, the controller will report a task watchdog exception.
• Sensitivity : The sensitivity field defines the number of task watchdog exceptions that must occur before the controller detects an application error.
To access the configuration of a task watchdog, double-click the Task in the
Applications tree .
NOTE: For more information on watchdogs, refer to EcoStruxure Machine
Expert Programming Guide.
Task Priorities
Task Priority Configuration
You can configure the priority of each task between 0 and 31 (0 is the highest priority, 31 is the lowest). Each task must have a unique priority. Assigning the same priority to more than one task leads to a build error.
Task Priority Suggestions
• Priority 0 to 24: Controller tasks. Assign these priorities to tasks with a high availability requirement.
• Priority 25 to 31: Background tasks. Assign these priorities to tasks with a low availability requirement.
Task Priorities of TM2/TM3 Modules and CANopen I/Os
You can select the task that drives TM3 and CANopen physical exchanges. In the
PLC settings , select Bus cycle task to define the task for the exchange. By default, the task is set to MAST . This definition at the controller level can be overridden by the
I/O bus configuration, page 71 .
During the read and write phases, all physical I/Os are refreshed at the same time.
TM3/TM2 and CANopen data is copied into a virtual I/O image during a physical exchanges phase, as shown in this figure:
Inputs are read from the I/O image table at the beginning of the task cycle.
Outputs are written to the I/O image table at the end of the task.
NOTE: Event tasks cannot drive the TM3/TM2 bus cycle.
Default Task Configuration
Default Task Configuration
The MAST task can be configured in Freewheeling or Cyclic mode. The MAST task is automatically created by default in Cyclic mode. Its preset priority is medium (15), its preset interval is 20 ms, and its task watchdog service is activated with a time of 100 ms and a sensitivity of 1. Refer to
for more information on priority settings. Refer to
for more information on watchdogs.
EIO0000003089.05
33
Designing an efficient application program is important in systems approaching the maximum number of tasks. In such an application, it can be difficult to keep the resource utilization below the system watchdog threshold. If priority reassignments alone are not sufficient to remain below the threshold, some lower priority tasks can be made to use fewer system resources if the
SysTaskWaitSleep function is added to those tasks. For more information about this function, see the optional SysTask library of the system / SysLibs category of libraries.
NOTE: Do not delete or change the name of the MAST task. Otherwise,
EcoStruxure Machine Expert detects an error when you attempt to build the application, and you will not be able to download it to the controller.
34 EIO0000003089.05
Controller States and Behaviors
Controller States and Behaviors
Introduction
This chapter provides information on controller states, state transitions, and behaviors in response to system events. It begins with a detailed controller state diagram and a description of each state. It then defines the relationship of output states to controller states before explaining the commands and events that result in state transitions. It concludes with information about Remanent variables and the effect of EcoStruxure Machine Expert task programming options on the behavior of your system.
Controller State Diagram
Controller State Diagram
This diagram describes the controller operating mode:
EIO0000003089.05
Legend:
• Controller states are indicated in ALL-CAPS BOLD
• User and application commands are indicated in Bold
• System events are indicated in Italics
• Decisions, decision results, and general information are indicated in normal text
35
Note 1
Note 2
Note 3
Note 4
Note 5a
Note 5b
Note 6
36
Controller States and Behaviors
(1) For details on STOPPED to RUNNING state transition, refer to
(2) For details on RUNNING to STOPPED state transition, refer to
The Power Cycle (Power Interruption followed by a Power ON) deletes all output forcing settings. Refer to
Controller State and Output Behavior, page 41
for further details.
The outputs will assume their hardware initialization values.
In some cases, when a system error is detected, it will cause the controller to reboot automatically into the EMPTY state as if no Boot application were present in the non-volatile memory. However, the Boot application is not deleted from the non-volatile memory. In this case, the ERR LED (red) flashes regularly.
After verification of a valid Boot application the following events occur:
• The application is loaded into RAM.
• The
file settings (if any) are applied.
During the load of the boot application, a Check context test occurs to verify that the Remanent variables are valid. If the Check context test is invalid, the boot application will load but the controller will transitions to the
The Starting Mode is set in the PLC settings tab of the
Not applicable
During a successful application download the following events occur:
• The application is loaded directly into RAM.
• By default, the Boot application is created and saved into the non-volatile memory.
EIO0000003089.05
Controller States and Behaviors
Note 7
The default behavior after downloading an application program is for the controller to enter the STOPPED state irrespective of the switch position or the last controller state before the download.
However, there are 2 considerations in this regard:
Online Change An online change (partial download) initiated while the controller is in the RUNNING state returns the controller to the
RUNNING state if successful and provided the Run/Stop switch is set to Run. Before using the Login with online change option, test the changes to your application program in a virtual or non-production environment and confirm that the controller and attached equipment assume their expected conditions in the RUNNING state.
WARNING
UNINTENDED EQUIPMENT OPERATION
Always verify that online changes to a RUNNING application program operate as expected before downloading them to controllers.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Multiple
Download
NOTE: Online changes to your program are not automatically written to the Boot application, and will be overwritten by the existing Boot application at the next reboot. If you wish your changes to persist through a reboot, manually update the Boot application by selecting Create boot application in the online menu (the controller must be in the STOPPED state to achieve this operation).
EcoStruxure Machine Expert has a feature that allows you to perform a full application download to multiple targets on your network or fieldbus. One of the default options when you select the Multiple Download...
command is the Start all applications after download or online change option, which restarts all download targets in the RUNNING state, irrespective of their last controller state before the multiple download was initiated. Deselect this option if you do not want all targeted controllers to restart in the RUNNING state. In addition, before using the Multiple Download option, test the changes to your application program in a virtual or non-production environment and confirm that the targeted controllers and attached equipment assume their expected conditions in the RUNNING state.
WARNING
UNINTENDED EQUIPMENT OPERATION
Always verify that your application program will operate as expected for all targeted controllers and equipment before issuing the "Multiple Download..." command with the "Start all applications after download or online change" option selected.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: During a multiple download, unlike a normal download, EcoStruxure Machine Expert does not offer the option to create a Boot application. You can manually create a Boot application at any time by selecting Create boot application in the Online menu on all targeted controllers.
Note 8
The EcoStruxure Machine Expert software platform allows many powerful options for managing task execution and output conditions while the controller is in the
STOPPED or HALT states. Refer to
Controller States Description, page 38
for further details.
Note 9
To exit the HALT state it is necessary to issue one of the Reset commands (Reset
Warm, Reset Cold, Reset Origin), download an application or cycle power.
In case of non-recoverable event (hardware watchdog or internal error), a power cycle is mandatory.
EIO0000003089.05
37
Controller States and Behaviors
Note 10
The RUNNING state has 2 exception conditions:
• RUNNING with External Error: this exception condition is indicated by the I/O
LED, which displays solid red. You may exit this state by clearing the external error (probably changing the application configuration). No controller commands are required, but may however include the need of a power cycle of the controller. For more information, refer to
.
• RUNNING with Breakpoint: this exception condition is indicated by the RUN
LED, which displays a single green flash. Refer to
for further details.
Note 11
The boot application can be different from the application loaded. It can happen when the boot application was downloaded through SD card, FTP, or file transfer or when an online change was performed without creating the boot application.
Controller States Description
Introduction
This section provides a detailed description of the controller states.
WARNING
UNINTENDED EQUIPMENT OPERATION
• Never assume that your controller is in a certain controller state before commanding a change of state, configuring your controller options, uploading a program, or modifying the physical configuration of the controller and its connected equipment.
• Before performing any of these operations, consider the effect on all connected equipment.
• Before acting on a controller, always positively confirm the controller state by viewing its LEDs, verifying the presence of output forcing, and reviewing the controller status information via EcoStruxure Machine Expert.
(1)
Failure to follow these instructions can result in death, serious injury, or equipment damage.
(1) The controller states can be read in the PLC_R.i_wStatus system variable of the M251 PLCSystem library (see Modicon M251 Logic Controller, System
Functions and Variables, PLCSystem Library Guide)
38 EIO0000003089.05
Controller States and Behaviors
Controller States Table
Controller State
BOOTING
INVALID_OS
EMPTY
EMPTY after a system error detected
RUNNING
RUNNING with breakpoint
RUNNING with external error detected
STOPPED
STOPPED with external error detected
HALT
Boot Application not saved
The following table describes the controller states:
Description
The controller executes the boot firmware and its own internal self-tests. It then checks the checksum of the firmware and user applications.
LED
RUN
(Green)
OFF
OFF
OFF
OFF
ERR
(Red)
OFF
ON
ON
Regular flash
There is not a valid firmware file present in the non-volatile memory. The controller does not execute the application. Refer to
to restore a correct state.
The controller has no application.
OFF
This state is the same as the other EMPTY state. However the application is present, and is intentionally not loaded. A reboot (power cycle), or a new application download, restores a correct state.
The controller is executing a valid application.
This state is same as the RUNNING state with the following exceptions:
• The task-processing portion of the program does not resume until the breakpoint is cleared.
• The LED indications are different.
For more information on breakpoint management, refer to EcoStruxure Machine
Expert Programming Guide.
The controller is executing a valid application and a configuration, TM3, SD card, or other I/O error is detected.
When I/O LED is ON, the details about the detected error can be found in PLC_
R.i_lwSystemFault_1
and PLC_R.i_lwSystemFault_2
. Any of the detected error conditions reported by these variables cause the I/O LED to be ON.
The controller has a valid application that is stopped. See details of the
for an explanation of the behavior of outputs and field buses in this state.
The controller is executing a valid application and a configuration, TM3, SD card, or other I/O error is detected.
OFF
ON
Single flash
ON
Regular flash
Regular flash
Single flash
Fast flash
OFF
OFF
OFF
OFF
OFF
I/O
(Red)
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
– The controller stops executing the application because it has detected an application error.
The controller has an application in memory that differs from the application in non-volatile memory. At next power cycle, the application will be changed by the one from non-volatile memory.
Regular flash
ON or regular flash
ON
Single flash
OFF
This timing diagram shows the difference between the fast flash, regular flash and single flash:
EIO0000003089.05
39
Controller States and Behaviors
Details of the STOPPED State
The following statements are true for the STOPPED state:
• Ethernet, Serial (Modbus, ASCII, and so on), and USB communication services remain operational and commands written by these services can continue to affect the application, the controller state, and the memory variables.
• All outputs initially assume their configured default state ( Keep current values or Set all outputs to default ) or the state dictated by output forcing if used. The subsequent state of the outputs depends on the value of the
Update IO while in stop setting and on commands received from remote devices.
Task and I/O Behavior When
Update IO While In Stop Is
Selected
When the Update IO while in stop setting is selected:
• The Read Inputs operation continues normally. The physical inputs are read and then written to the %I input memory variables.
• The Task Processing operation is not executed.
• The Write Outputs operation continues. The %Q output memory variables are updated to reflect either the Keep current values configuration or the Set all outputs to default configuration, adjusted for any output forcing, and then written to the physical outputs.
CAN Behavior When Update
IO While In Stop Is Selected
Task and I/O Behavior When
Update IO While In Stop Is Not
Selected
The following is true for the CAN buses when the Update IO while in stop setting is selected:
• The CAN bus remains operational. Devices on the CAN bus continue to perceive the presence of a functional CAN Master.
• TPDO and RPDO continue to be exchanged.
• The optional SDO, if configured, continue to be exchanged.
• The Heartbeat and Node Guarding functions, if configured, continue to operate.
• If the Behaviour for outputs in Stop field is set to Keep current values , the TPDOs continue to be issued with the last values.
• If the Behaviour for outputs in Stop field is Set all outputs to default the last values are updated to the default values and subsequent TPDOs are issued with these default values.
When the Update IO while in stop setting is not selected, the controller sets the I/O to either the Keep current values or Set all outputs to default condition (as adjusted for output forcing if used). After this, the following becomes true:
• The Read Inputs operation ceases. The %I input memory variables are frozen at their last values.
• The Task Processing operation is not executed.
• The Write Outputs operation ceases. The %Q output memory variables can be updated via the
Ethernet, Serial, and USB connections. However, the physical outputs are unaffected and retain the state specified by the configuration options.
CAN Behavior When Update
IO While In Stop Is Not
Selected
The following is true for the CAN buses when the Update IO while in stop setting is not selected:
• The CAN Master ceases communications. Devices on the CAN bus assume their configured fallback states.
• TPDO and RPDO exchanges cease.
• Optional SDO, if configured, exchanges cease.
• The Heartbeat and Node Guarding functions, if configured, stop.
• The current or default values, as appropriate, are written to the TPDOs and sent once before stopping the CAN Master.
State Transitions and System Events
Overview
This section begins with an explanation of the output states possible for the controller. It then presents the system commands used to transition between controller states and the system events that can also affect these states. It concludes with an explanation of the Remanent variables, and the circumstances under which different variables and data types are retained through state transitions.
40 EIO0000003089.05
Controller States and Behaviors
Controller States and Output Behavior
Introduction
The Modicon M251 Logic Controller defines output behavior in response to commands and system events in a way that allows for greater flexibility. An understanding of this behavior is necessary before discussing the commands and events that affect controller states.
The possible output behaviors and the controller states to which they apply are:
• Managed by Application Program
• Keep current values
• Set all outputs to default
• Hardware Initialization Values
• Software Initialization Values
• Output Forcing
Managed by Application Program
Your application program manages outputs normally. This applies in the
RUNNING and RUNNING with External Error Detected states.
NOTE: An exception to this is if the RUNNING with External Error Detected state has been provoked by a I/O expansion bus error. For more information, refer to
I/O Configuration General Description, page 68
.
Keep Current Values
Select this option by choosing Controller Editor > PLC settings > Behavior for outputs in Stop > Keep current values . To access the Controller Editor, rightclick on the controller in the Devices tree and select Edit Object .
This output behavior applies in the STOPPED controller state. It also applies to
CAN bus in the HALT controller state. Outputs maintain their state, although the details of the output behavior vary greatly depending on the setting of the Update
I/O while in stop option and the actions commanded via configured fieldbusses.
Refer to
Controller States Description, page 38
for more details on these variations.
Set All Outputs to Default
Select this option by choosing Controller Editor > PLC settings > Behavior for outputs in Stop > Set all outputs to default . To access the Controller Editor , right-click on the controller in the Devices tree and select Edit Object .
This output behavior applies:
• when the controller is going from RUNNING state to STOPPED state.
• if the controller is going from RUNNING state to HALT state.
• after application download.
• after reset warm/cold command.
• after a reboot.
It also applies to CAN bus in the HALT controller state. Outputs maintain their state, although the details of the output behavior vary greatly depending on the setting of the Update I/O while in stop option and the actions commanded via configured fieldbusses. Refer to
Controller States Description, page 38
for more details on these variations.
EIO0000003089.05
41
Controller States and Behaviors
Hardware Initialization Values
This output state applies in the BOOTING, EMPTY (following power cycle with no boot application or after the detection of a system error), and INVALID_OS states.
In the initialization state, analog, transistor, and relay outputs assume the following values:
• For an analog output: Z (high impedance)
• For a fast transistor output: Z (high impedance)
• For a regular transistor output: 0 Vdc
• For a relay output: Open
Software Initialization Values
This output state applies when downloading or when resetting the application. It applies at the end of the download or at the end of a reset warm or cold.
The software Initialization Values are the initialization values of outputs images
(%I, %Q, or variables mapped on %I or %Q).
By default, they are set to 0 but it is possible to map the I/O in a GVL and assign to the outputs a value different than 0.
Output Forcing
The controller allows you to force the state of selected outputs to a defined value for the purposes of system testing, commissioning, and maintenance.
You are only able to force the value of an output while your controller is connected to EcoStruxure Machine Expert.
To do so, use the Force values command in the Debug menu.
Output forcing overrides other commands (except write immediate) to an output irrespective of the task programming that is being executed.
When you logout of EcoStruxure Machine Expert when output forcing has been defined, you are presented with the option to retain output forcing settings. If you select this option, the output forcing continues to control the state of the selected outputs until you download an application or use one of the Reset commands.
When the option Update I/O while in stop , if supported by your controller, is checked (default state), the forced outputs keep the forcing value even when the controller is in STOPPED state.
Output Forcing Considerations
The output you wish to force must be contained in a task that is currently being executed by the controller. Forcing outputs in unexecuted tasks, or in tasks whose execution is delayed either by priorities or events has no effect on the output.
However, once the task that had been delayed is executed, the forcing takes effect at that time.
Depending on task execution, the forcing could impact your application in ways that may not be obvious to you. For example, an event task could turn on an output. Later, you may attempt to turn off that output but the event is not being triggered at the time. This would have the effect of the forcing being apparently ignored. Further, at a later time, the event could trigger the task at which point the forcing would take effect.
42 EIO0000003089.05
Controller States and Behaviors
WARNING
UNINTENDED EQUIPMENT OPERATION
• You must have a thorough understanding of how forcing will affect the outputs relative to the tasks being executed.
• Do not attempt to force I/O that is contained in tasks that you are not certain will be executed in a timely manner, unless your intent is for the forcing to take affect at the next execution of the task whenever that may be.
• If you force an output and there is no apparent affect on the physical output, do not exit EcoStruxure Machine Expert without removing the forcing.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Commanding State Transitions
Run Command
Effect: Commands a transition to the RUNNING controller state.
Starting Conditions: BOOTING or STOPPED state.
Methods for Issuing a Run Command:
• Run/Stop switch goes from stop to run.
• EcoStruxure Machine Expert Online Menu: Select the Start command.
• RUN command from Web Server
• By an external call via Modbus request using the PLC_W.q_wPLCControl and
PLC_W.q_uiOpenPLCControl system variables of the M251 PLCSystem library (see Modicon M251 Logic Controller, System Functions and Variables,
PLCSystem Library Guide).
• Login with online change option: An online change (partial download) initiated while the controller is in the RUNNING state returns the controller to the RUNNING state if successful.
• Multiple Download Command: sets the controllers into the RUNNING state if the Start all applications after download or online change option is selected, irrespective of whether the targeted controllers were initially in the
RUNNING, STOPPED, or EMPTY state.
• The controller is restarted into the RUNNING state automatically under certain conditions.
Refer to
Controller State Diagram, page 35
for further details.
Stop Command
Effect: Commands a transition to the STOPPED controller state.
Starting Conditions: BOOTING, EMPTY, or RUNNING state.
EIO0000003089.05
43
Reset Warm
44
Controller States and Behaviors
Methods for Issuing a Stop Command:
• Run/Stop switch goes from run to stop.
• EcoStruxure Machine Expert Online Menu: Select the Stop command.
• STOP command from WebServer
• By an internal call by the application or an external call via Modbus request using the PLC_W. q_wPLCControl and PLC_W. q_uiOpenPLCControl system variables of the M251 PLCSystem library (see Modicon M251 Logic
Controller, System Functions and Variables, PLCSystem Library Guide).
• Login with online change option: An online change (partial download) initiated while the controller is in the STOPPED state returns the controller to the STOPPED state if successful.
• Download Command: implicitly sets the controller into the STOPPED state.
• Multiple Download Command: sets the controllers into the STOPPED state if the Start all applications after download or online change option is not selected, irrespective of whether the targeted controllers were initially in the
RUNNING, STOPPED, or EMPTY state.
• REBOOT by Script: The file transfer script on an SD card can issue a
REBOOT as its final command. The controller is rebooted into the STOPPED state provided the other conditions of the boot sequence allow this to occur.
Refer to
for further details.
• The controller is restarted into the STOPPED state automatically under certain conditions.
Refer to
Controller State Diagram, page 35
for further details.
Effect: Resets the variables, except for the remanent variables, to their default values. Places the controller into the STOPPED state.
Starting Conditions: RUNNING, STOPPED, or HALT states.
Methods for Issuing a Reset Warm Command:
• EcoStruxure Machine Expert Online Menu: Select the Reset warm command.
• By an internal call by the application or an external call via Modbus request using the PLC_W. q_wPLCControl and PLC_W. q_uiOpenPLCControl system variables of the M251 PLCSystem library (see Modicon M251 Logic
Controller, System Functions and Variables, PLCSystem Library Guide).
Effects of the Reset Warm Command:
1. The application stops.
2. Forcing is erased.
3. Diagnostic indications for errors are reset.
4. The values of the retain variables are maintained.
5. The values of the retain-persistent variables are maintained.
6. The non-located and non-remanent variables are reset to their initialization values.
7. The values of the first 1000 %MW registers are maintained.
8. The values of %MW1000 to %MW59999 registers are reset to 0.
9. The fieldbus communications are stopped and then restarted after the reset is complete.
10. The inputs are reset to their initialization values. The outputs are reset to their software initialization values or their default values if no software initialization values are defined.
11. The Post Configuration file is
For details on variables, refer to
.
EIO0000003089.05
Controller States and Behaviors
Reset Cold
Effect: Resets the variables, except for the retain-persistent type of remanent variables, to their initialization values. Places the controller into the STOPPED state.
Starting Conditions: RUNNING, STOPPED, or HALT states.
Methods for Issuing a Reset Cold Command:
• EcoStruxure Machine Expert Online Menu: Select the Reset cold command.
• By an internal call by the application or an external call via Modbus request using the PLC_W. q_wPLCControl and PLC_W. q_uiOpenPLCControl system variables of the M251 PLCSystem library (see Modicon M251 Logic
Controller, System Functions and Variables, PLCSystem Library Guide).
Effects of the Reset Cold Command:
1. The application stops.
2. Forcing is erased.
3. Diagnostic indications for errors are reset.
4. The values of the retain variables are reset to their initialization value.
5. The values of the retain-persistent variables are maintained.
6. The non-located and non-remanent variables are reset to their initialization values.
7. The values of the first 1000 %MW registers are maintained.
8. The values of %MW1000 to %MW59999 registers are reset to 0.
9. The fieldbus communications are stopped and then restarted after the reset is complete.
10. The inputs are reset to their initialization values. The outputs are reset to their software initialization values or their default values if no software initialization values are defined.
11. The Post Configuration file is
For details on variables, refer to
.
Reset Origin
Effect: Resets all variables, including the remanent variables, to their initialization values. Erases all user files on the controller, including user rights and certificates.
Reboots and places the controller into the EMPTY state.
Starting Conditions: RUNNING, STOPPED, or HALT states.
Methods for Issuing a Reset Origin Command:
• EcoStruxure Machine Expert Online Menu: Select the Reset origin command.
EIO0000003089.05
45
Controller States and Behaviors
Effects of the Reset Origin Command:
1. The application stops.
2. Forcing is erased.
3. The web visu files are erased.
4. The user files (Boot application, data logging, Post Configuration, user rights and certificates) are erased.
5. Diagnostic indications for errors are reset.
6. The values of the retain variables are reset.
7. The values of the retain-persistent variables are reset.
8. The non-located and non-remanent variables are reset.
9. The values of the first 1000 %MW registers are reset to 0.
10. The values of %MW1000 to %MW59999 registers are reset to 0.
11. The fieldbus communications are stopped.
12. The other inputs are reset to their initialization values.
The other outputs are reset to their hardware initialization values.
13. The controller reboots.
For details on variables, refer to
.
Reset Origin Device
Effect: Resets all variables, including the remanent variables, to their initialization values. Places the controller into the EMPTY state if PLC Logic is selected.
Starting Conditions: RUNNING, STOPPED, or HALT states.
Methods for Issuing a Reset Origin Device Command:
• EcoStruxure Machine Expert Online Menu: Right-click My controller > Reset
Origin Device command.
Result: a dialog box allows you to select the items to remove:
◦ User Management
◦ PLC Logic
◦ Certificates
Machine Expert Logic Builder
Do you really want to reset the device to its original state?
Resetting the device will delete all of the selected items below.
Deleting just a subset of items may render other items inoperable.
Depending on the configuration of the device, additional items may also get deleted.
Delete item
User Management
PLC Logic
Certificates
Yes No
When User Management is selected:
• User and groups are reset to default value.
46 EIO0000003089.05
Controller States and Behaviors
NOTE: If the controller user rights are disabled before this command is used, you can connect to the controller without login prompt afterwards. Use the dedicated command in Online menu: Security > Reset user rights management to default to enforce again the use of user management.
When PLC Logic is selected:
1. The application stops.
2. Forcing is erased.
3. The web visu files are erased.
4. Diagnostic indications for errors are reset.
5. The values of the retain variables are reset.
6. The values of the retain-persistent variables are reset.
7. The non-located and non-remanent variables are reset.
8. The fieldbus communications are stopped.
9. Embedded Expert I/O are reset to their previous user-configured default values.
10. The other inputs are reset to their initialization values.
The other outputs are reset to their hardware initialization values.
11. System Logs are maintained.
When Certificates is selected, certificates used for Webserver and FTP server are reset.
For details on variables, refer to
.
EIO0000003089.05
47
Reboot
48
Controller States and Behaviors
Effect: Commands a reboot of the controller.
Starting Conditions: Any state.
Methods for Issuing the Reboot Command:
• Power cycle
• REBOOT by
Effects of the Reboot:
1. The state of the controller depends on a number of conditions: a. The controller state is RUNNING if:
The Reboot was provoked by a power cycle and:
- the Starting Mode is set to Start in run , and if the Run/Stop input is not configured, and if the controller was not in HALT state before the power cycle, and if the remanent variables are valid.
- the Starting Mode is set to Start in run , and if the Run/Stop input is configured and set to RUN, and if the controller was not in HALT state before the power cycle, and if the remanent variables are valid.
- the Starting Mode is set to Start as previous state , and Controller state was RUNNING before the power cycle, and if the Run/Stop input is not configured and the boot application has not changed and the remanent variables are valid.
- the Starting Mode is set to Start as previous state , and Controller state was RUNNING before the power cycle, and if the Run/Stop input is configured and is set to RUN and the remanent variables are valid.
The Reboot was provoked by a script and:
- the Starting Mode is set to Start in run , and if the Run/Stop input is configured and set to RUN, or the switch is set to run, and if the controller was not in HALT state before the power cycle, and if the remanent variables are valid.
b. The controller state is STOPPED if:
The Reboot was provoked by a power cycle and:
- the Starting Mode is set to Start in stop .
- the Starting Mode is set to Start as previous state and the controller state was not RUNNING before the power cycle.
- the Starting Mode is set to Start as previous state and the controller state was RUNNING before the power cycle, and if the Run/Stop input is not configured, and if the boot application has changed.
- the Starting Mode is set to Start as previous state and the controller state was RUNNING before the power cycle, and if the Run/Stop input is not configured, and if the boot application has not changed, and if the remanent variables are not valid.
- the Starting Mode is set to Start as previous state and the controller state was RUNNING before the power cycle, and if the Run/Stop input is configured and is set to STOP.
- the Starting Mode is set to Start in run and if the controller state was
HALT before the power cycle.
- the Starting Mode is set to Start in run , and if the controller state was not HALT before the power cycle, and if the Run/Stop input is configured and is set to STOP.
- the Starting Mode is set to Start as previous state and if the Run/Stop input is configured and set to RUN, or the switch is set to run, and if the controller was not in HALT state before the power cycle.
- the Starting Mode is set to Start as previous state and if the Run/Stop input is not configured, and if the controller was not in HALT, or the switch is set to run state before the power cycle.
EIO0000003089.05
Controller States and Behaviors
c. The controller state is EMPTY if:
- There is no boot application or the boot application is invalid, or
- The reboot was provoked by specific System Errors.
d. The controller state is INVALID_OS if there is no valid firmware.
2. Forcing is maintained if the boot application is loaded successfully. If not, forcing is erased.
3. Diagnostic indications for errors are reset.
4. The values of the retain variables are restored if saved context is valid.
5. The values of the retain-persistent variables are restored if saved context is valid.
6. The non-located and non-remanent variables are reset to their initialization values.
7. The values of the first 1000 %MW registers are restored if saved context is valid.
8. The values of %MW1000 to %MW59999 registers are reset to 0.
9. The fieldbus communications are stopped and restarted after the boot application is loaded successfully.
10. The inputs are reset to their initialization values. The outputs are reset to their hardware initialization values and then to their software initialization values or their default values if no software initialization values are defined.
11. The Post Configuration file is
12. The controller file system is initialized and its resources (sockets, file handles, and so on) are deallocated.
The file system employed by the controller needs to be periodically reestablished by a power cycle of the controller. If you do not perform regular maintenance of your machine, or if you are using an Uninterruptible Power
Supply (UPS), you must force a power cycle (removal and reapplication of power) to the controller at least once a year.
NOTICE
DEGRADATION OF PERFORMANCE
Reboot your controller at least once a year by removing and then reapplying power.
Failure to follow these instructions can result in equipment damage.
For details on variables, refer to
.
NOTE: The Check context test concludes that the context is valid when the application and the remanent variables are the same as defined in the Boot application.
NOTE: If you make an online change to your application program while your controller is in the RUNNING or STOPPED state but do not manually update your Boot application, the controller detects a difference in context at the next reboot, the remanent variables are reset as per a Reset cold command, and the controller enters the STOPPED state.
Download Application
Effect: Loads your application executable into the RAM memory. Optionally, creates a Boot application in the non-volatile memory.
Starting Conditions: RUNNING, STOPPED, HALT, and EMPTY states.
EIO0000003089.05
49
Controller States and Behaviors
Methods for Issuing the Download Application Command:
• EcoStruxure Machine Expert:
2 options exist for downloading a full application:
◦ Download command.
◦ Multiple Download command.
For important information on the application download commands, refer to
Controller State Diagram.
• FTP: Load Boot application file to the non-volatile memory using FTP. The updated file is applied at the next reboot.
• SD card: Load Boot application file using an SD card in the controller. The updated file is applied at the next reboot. Refer to
File Transfer with SD Card, page 172
for further details.
Effects of the EcoStruxure Machine Expert Download Command:
1. The existing application stops and then is erased.
2. If valid, the new application is loaded and the controller assumes a STOPPED state.
3. Forcing is erased.
4. Diagnostic indications for errors are reset.
5. The values of the retain variables are reset to their initialization values.
6. The values of any existing retain-persistent variables are maintained.
7. The non-located and non-remanent variables are reset to their initialization values.
8. The values of the first 1000 %MW registers are maintained.
9. The values of %MW1000 to %MW59999 registers are reset to 0.
10. The fieldbus communications are stopped and then the configured fieldbus of the new application is started after the download is complete.
11. The inputs are reset to their initialization values. The outputs are reset to their hardware initialization values and then to their software initialization values or their default values if no software initialization values are defined, after the download is complete.
12. The Post Configuration file is
For details on variables, refer to
.
Effects of the FTP or SD Card Download Command:
There are no effects until the next reboot. At the next reboot, the effects are the same as a reboot with an invalid context. Refer to
.
Error Detection, Types, and Management
Error Management
The controller detects and manages three types of errors:
• External errors
• Application errors
• System errors
50 EIO0000003089.05
Controller States and Behaviors
This table describes the types of errors that may be detected:
Type of Error
Detected
External Error
Application Error
Description
External errors are detected by the system while RUNNING or STOPPED but do not affect the ongoing controller state. An external error is detected in the following cases:
• A connected device reports an error to the controller.
• The controller detects an error with an external device, for example, when the external device is communicating but not properly configured for use with the controller.
• The controller detects an error with an output.
• The controller detects a communication interruption with a device.
• The controller is configured for an expansion module that is not present or not detected, and has not otherwise been declared as an optional module
(1) .
• The boot application in non-volatile memory is not the same as the one in
RAM.
An application error is detected when improper programming is encountered or when a task watchdog threshold is exceeded.
Resulting Controller State
RUNNING with External Error
Detected
Or
STOPPED with External Error
Detected
HALT
System Error A system error is detected when the controller enters a condition that cannot be managed during runtime. Most such conditions result from firmware or hardware exceptions, but there are some cases when incorrect programming can result in the detection of a system error, for example, when attempting to write to memory that was reserved during runtime, or when a system watchdog occurs.
NOTE: There are some system errors that can be managed by runtime and are therefore treated like application errors.
BOOTING → EMPTY
(1) Expansion modules may appear to be absent for any number of reasons, even if the absent I/O module is physically present on the bus.
For more information, refer to
I/O Configuration General Description, page 68 .
NOTE: Refer to the Modicon M251 Logic Controller PLCSystem – Library
Guide for more detailed information on diagnostics.
Remanent Variables
Overview
Remanent variables can either be reinitialized or retain their values in the event of power outages, reboots, resets, and application program downloads. There are multiple types of remanent variables, declared individually as retain or persistent, or in combination as retain-persistent.
NOTE: For this controller, variables declared as persistent behave in the same way as variables declared as retain-persistent.
EIO0000003089.05
51
Controller States and Behaviors
This table describes the behavior of remanent variables in each case:
Action
Online change to application program
VAR
X
–
VAR RETAIN
X
VAR GLOBAL RETAIN PERSISTENT
X
Online change modifying the boot application (1)
Stop
X
X
X
X
Power cycle
Reset warm
Reset cold
Reset origin
X
–
–
–
–
X
X (2)
–
–
X
X
X
–
– Reset origin device
Download of application program using
EcoStruxure Machine Expert (3)
–
–
–
– X
Download of application program using an SD card (3)
– – –
(X) The value is maintained.
(–) The value is reinitialized.
(1) Retain variable values are maintained if an online change modifies only the code part of the boot application (for example, a:=a+1; => a:=a+2; ). In all other cases, retain variables are reinitialized.
(2) For more details on VAR RETAIN, refer to
Effects of the Reset warm Command, page 44
.
(3) If the downloaded application contains the same retain-persistent variables as the existing application, the existing retain variables maintain their values.
NOTE: The first 1000 %MW are automatically retained and persistent if no variable is associated to them. Their values are kept after a reboot / Reset warm / Reset cold. The other %MW are managed as VAR.
For example, if you have in your program:
VAR myVariable AT %MW0 : WORD; END_VAR
%MW0 behaves like myVariable (not retained and not persistent).
Adding Retain-Persistent Variables
Declare retain-persistent ( VAR GLOBAL PERSISTENT RETAIN ) variables in the
PersistentVars window:
Step
1
2
3
4
Action
In the Applications tree , select the Application node.
Click the right mouse button.
Choose Add Objects > Persistent variables
Click Add .
Result: The PersistentVars window is displayed.
52 EIO0000003089.05
Controller Device Editor
Introduction
This chapter describes how to configure the controller.
Controller Parameters
Controller Parameters
To open the device editor, double-click MyController in the Devices tree :
MyController
Communication settings Applications Files Log PLC Settings Services IEC Objects Task Deployment Ethernet Services Users and Groups Access Rights Symbol Rights OPC UA Server Configuration Status Information
C...
Controller ProjectName NodeName ProjectAuthor FW_Version IP_Address TimeSinceBoot
Tabs Description
Tab
Communication Settings , page 54
Applications
Log
IEC Objects
Task deployment
Description
Manages the connection between the PC and the controller:
• helping you find a controller in a network,
• presenting the list of available controllers, so you can connect to the selected controller and manage the application in the controller,
• helping you physically identify the controller from the device editor,
• helping you change the communication settings of the controller.
The controller list is detected through NetManage or through the Active Path based on the communication settings. To access the Communication settings , click Project
>
Project Settings...
in the menu bar. For more information, refer to the EcoStruxure
Machine Expert Programming Guide ( Communication Settings ).
Presents the application running on the controller and allows removing the application from the controller.
File management between the PC and the controller.
Only one logic controller disk at a time can be seen through this tab. When an SD card is inserted, this file displays the content of the SD card. Otherwise, this tab displays the content of the /usr directory of the internal non-volatile memory of the controller.
View the controller log file.
Configuration of:
• application name
• I/O behavior in stop
• bus cycle options
Lets you configure the online services of the controller (RTC, device identification).
Allows you to access the device from the IEC application through the listed objects.
Displays a monitoring view in online mode. For more information, refer to IEC Object in
CODESYS Online Help .
Displays a list of I/Os and their assignments to tasks.
Restriction
Online mode only
Online mode only
Online mode only
Online mode only
–
Online mode only
–
After compilation only
Ethernet Services The IP Routing tab allows you to configure the routes and the cross network transparency through IP Routing options.
NOTE: This tab is empty if no Ethernet connection is available in the configuration.
EIO0000003089.05
53
Tab
Users and Groups
Access Rights
Symbol Rights
OPC UA Server
Configuration
Status
Information
Description
The Users and Groups tab is provided for devices supporting online user management. It allows setting up users and access-rights groups and assigning them access rights to control the access on EcoStruxure Machine Expert projects and devices in online mode.
For more details, refer to the EcoStruxure Machine Expert Programming Guide.
The Access Rights tab is provided for devices supporting online user management. It serves to grant or deny the currently defined user groups certain permissions, thus defining the access rights for users on files or objects (for example, an application) on the controller during runtime.
For more details, refer to the EcoStruxure Machine Expert Programming Guide.
Allows the Administrator to configure Users and Groups access to the symbol sets.
For more information, refer to Symbol Configuration in CODESYS Online Help .
Displays the
OPC UA Server Configuration, page 152
window.
Restriction
–
–
–
–
Not used.
Displays general information about the device (name, description, provider, version, image).
–
–
Communication Settings
Introduction
This tab allows you to manage the connection from the PC to the controller:
• Helping you find a controller in a network.
• Presenting the list of controllers, so you can connect to the selected controller and manage the application inside the controller.
• Helping you physically identify the controller from the device editor.
• Helping you change the communication settings of the controller.
You can change the display mode of the Communication Settings tab:
• Simple mode . Refer to EcoStruxure Machine Expert, Programming Guide.
• Classic mode . Refer to EcoStruxure Machine Expert, Programming Guide.
• Controller selection mode . Refer to EcoStruxure Machine Expert,
Programming Guide.
Edit Communication Settings
In Controller selection mode , the Edit communication settings window lets you change the Ethernet communication settings. To do so, click Communication
Settings tab. The list of controllers available in the network appears. Select and right-click the required row and click Edit communication settings ...
in the contextual menu.
54 EIO0000003089.05
You can configure the Ethernet settings in the Edit communication settings window in 2 ways:
• Without the Save settings permanently option:
Configure the communication parameters and click OK . These settings are immediately taken into account and are not kept if the controller is reset. For the next resets, the communication parameters configured into the application are taken into account.
• With the Save settings permanently option:
You can also activate the Save settings permanently option before you click
OK . Once this option is activated, the Ethernet parameters configured here are always taken into account on reset instead of the Ethernet parameters configured into the EcoStruxure Machine Expert application.
For more information on the Communication Settings view of the device editor, refer to the EcoStruxure Machine Expert Programming Guide.
PLC Settings
Overview
The figure below presents the PLC Settings tab:
Element
Application for I/O handling
PLC settings Update IO while in stop
Behavior for outputs in Stop
Description
By default, set to Application because there is only one application in the controller.
If this option is activated (default), the values of the input and output channels are also updated when the controller is stopped.
From the selection list, choose one of the following options to configure how the values at the output channels should be handled in case of controller stop:
• Keep current values
• Set all outputs to default
By default, set to Enabled 1 (use bus cycle task if not used in task) and not editable.
Bus cycle options
Always update variables
Bus cycle task This configuration setting is the parent for all Bus cycle task parameters used in the application Devices tree .
Some devices with cyclic calls, such as a CANopen manager , can be attached to a specific task. In the device, when this setting is set to Use parent bus cycle setting , the setting set for the controller is used.
The selection list offers all tasks currently defined in the active application. The default setting is the MAST task.
NOTE: <unspecified> means that the task is in "slowest cyclic task" mode.
EIO0000003089.05
55
Element
Additional settings
Starting mode
Options
Generate force variables for IO mapping
Enable Diagnosis for devices
Show I/O warnings as errors
Starting mode
Description
Not used.
Not used.
Not used.
This option defines the starting mode on a power-on. For further information, refer to
State behavior diagram, page 35
.
Select with this option one of these starting modes:
• Start as previous state
• Start in stop
• Start in run
Services
Services Tab
The Services tab is divided in three parts:
• RTC Configuration
• Device Identification
• Post Configuration
The figure below shows the Services tab:
56
NOTE: To have controller information, you must be connected to the controller.
EIO0000003089.05
Element
RTC
Configuration
PLC Time
Read
Local Time
Write
Device Identification
Post Configuration
Synchronize with local date/time
Description
Displays the date and time read from the controller when the Read button is clicked, with no conversion applied. This read-only field is initially empty. If Write as UTC is selected,
PLC Time is in Coordinated Universal Time (UTC).
Reads the date and time saved on the controller and displays the values in the PLC Time field.
Lets you define a date and a time that are sent to the controller when the Write button is clicked. If necessary, modify the default values before clicking the Write button. A message box informs you about the result of the command. The date and time fields are initially filled with the current PC settings.
Writes the date and time defined in the Local time field to the logic controller. A message box informs you of the result of the command. Select the Write as UTC checkbox before running this command to write the values in UTC format.
Lets you directly send the PC settings. A message box informs you of the result of the command. Select Write as UTC before running this command to use UTC format. Use
UTC time when using secure communication.
Displays the Firmware Version , the Boot Version , and the Coprocessor Version of the selected controller, if connected.
Displays the application parameters overwritten by the
Post configuration, page 158 .
Ethernet Services
IP Routing
The IP Routing subtab allows you to configure the IP routes in the controller.
The parameter Enable IP forwarding :
• recalls the option sets or not on the configuration page of the Ethernet network (Ethernet 1) for TM251MESE logic controller.
• is empty as not supported forTM251MESC logic controller.
When deactivated, the communication is not routed from a network to another one. The devices on the device network are no longer accessible from the control network and related features like Web pages access on device or commissioning of device via DTM, EcoStruxure Machine Expert - Safety and so on are not possible.
The M251 Logic Controller can have up to two Ethernet interfaces. Using a routing table is necessary to communicate with remote networks connected to different
Ethernet interfaces. The gateway is the IP address used to connect to the remote network, which needs to be in local network of the controller.
Use the routing tables to manage the IP forwarding.
EIO0000003089.05
57
To add a route, double click My controller then click Ethernet Services > IP
Routing > Add Route .
MyController
Communication Settings Applications Files Log PLC settings Services
IP Routing
Routing Table
Network Destination Network Mask Gateway
IEC Objects Task Deployment Ethernet Services Users and Groups
Edit route
Network Destination
Network Mask
Gateway
10 . 100 . 100 . 0
255 . 255 . 255 . 0
172 . 16 . 4 . 0
Ok Cancel
Add Route...
Delete Route...
Edit Route...
For reasons of network security, TCP/IP forwarding is disabled by default.
Therefore, you must manually enable TCP/IP forwarding if you want to access devices through the controller. However, doing so may expose your network to possible cyberattacks if you do not take additional measures to protect your enterprise. In addition, you may be subject to laws and regulations concerning cybersecurity.
WARNING
UNAUTHENTICATED ACCESS AND SUBSEQUENT NETWORK INTRUSION
• Observe and respect any an all pertinent national, regional and local cybersecurity and/or personal data laws and regulations when enabling
TCP/IP forwarding on an industrial network.
• Isolate your industrial network from other networks inside your company.
• Protect any network against unintended access by using firewalls, VPN, or other, proven security measures.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Users Rights
Introduction
58
Users rights contain the following elements: User , Group , Object , Operation ,
User Rights , Access rights . These elements allow you to manage users accounts and users access rights to control the access on the global projects.
• A User is a person or a service with specific User Rights .
• A Group is a Persona or a Function . It is predefined or added. Each Group provides accesses thanks to Object .
• An Object is composed by predefined accesses thanks to Operation .
• An Operation is the elementary action possible.
• User Rights are the possible Access rights : VIEW , MODIFY , EXECUTE and ADD–REMOVE for the dedicated operation.
For more informations, refer to the EcoStruxure Machine Expert Programming
Guide.
EIO0000003089.05
Login and passwords
Server/feature
EcoStruxure
Machine Expert
Web server
FTP server
OPC-UA
Change Device
Name feature
Login and password are not set by default. This table describes how to log in:
First connection or connection after reset to default / reset origin / reset origin device
You must first create your login and your password.
NOTE: The login and the password that you create during the first connection have administrator privileges.
NOTE: For information on lost login and passwords, see
.
User Rights enabled
Connection after User Rights disabled
Login : configured login
Password : configured password
No login or password required.
No login possible
No login possible
No login possible
No login possible
Login : configured login
Password : configured password
Login : configured login
Password : configured password
Login : configured login
Password : configured password
Login : configured login
Password : configured password
Login : Anonymous
Password : no password required.
Login : Anonymous
Password : Anonymous
Login : Anonymous
Password : Anonymous
No login or password required.
WARNING
UNAUTHORIZED DATA AND/OR APPLICATION ACCESS
• Secure access to the FTP/Web/OPC-UA server(s) using User Rights.
• If you disable User Rights, disable the server(s) to prevent any unwanted or unauthorized access to your application and/or data.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: Anonymous login can be restored by disabling the user rights in User
Management
page of the web server, page 90
.
NOTE: The following characters are supported by the controller:
• login: a...z A...Z 0...9 – = [ ] \ ; ‘ , . / @ # $ % ^ & * ( ) _ + { } | : “ < > ? ` ~
• password: a...z A...Z 0...9 – = [ ] \ ; ‘ , . / @ # $ % ^ & * ( ) _ + { } | : “ < > ?
` ~ and space
The length is limited to 60 characters.
EIO0000003089.05
59
Default users and groups
This table indicates the name and description of the predefined default groups :
Group Name
Administrator
Group Description
• Manages all the user rights.
• Is created at first connection.
Persona
Persona Designer/
Programmer
Persona Operator
Persona Web Designer
Persona Communication
Persona Maintenance
Function
Function External Media
Function File Access
Function FTP
Function Symbol
Configuration
Function Web Access
Function Monitor
Function OPC UA
Function Variable
Group dedicated to the design of the application.
Group dedicated to the usage of the application.
Group dedicated to the management of the Web server.
Group dedicated to the management of communication features.
Group dedicated to the maintenance of the application.
Group to allow the usage of External Command (from SD Card).
Group to allow permissions on files tab.
Group to allow usage of FTP.
Group to allow access to Symbol Configuration .
Group to allow command on Web server.
Group to allow monitoring of IEC variables.
Group to allow access to OPC UA server.
Group to allow read/write of IEC variables.
NOTE: Administrator can define a new Group if needed.
Object Names
Object name
Device
ExternalCmd
FTP
Logger
OPC_UA
PlcLogic
Settings
UserManagement
Web
FileSystem
This table indicates the name and description of the predefined objects:
Object Description
Object related to the connection of the controller through EcoStruxure Machine Expert.
Object related to script command ( Clone and CloneCheck ).
Object related to FTP access (connection, upload and download on FTP server).
Object related to the message logger.
Object related to OPC UA server (connection, read and write variables).
Object related to the application on the controller.
Object related to the settings of the controller (nodename…).
Object related to User rights Management.
Object related to the access of the Web server.
Object related to the file access (when accessing through the controller Files tab).
60 EIO0000003089.05
Operation Functions
This list indicates the name of the possible predefined operations:
• SD Card command
◦ Script Command: Reboot
◦ Script Command: SET_NODE_NAME
◦ Script Command: FIREWALL_INSTALL
◦ Script Command: Delete
◦ Script Command: Download
◦ Script Command: Upload
◦ Script Command: UpdateBoot
◦ Clone operation (clone controller contents to empty SD card)
• FTP server command
◦ Connection to FTP server
◦ List Directory
◦ Change Directory
◦ Create Folder
◦ Rename Folder
◦ Suppress Folder
◦ Create File
◦ Rename File
◦ Suppress File
◦ Download File
◦ Upload File
• OPC UA server command
◦ Connection to OPC UA server
◦ Read Variable
◦ Write Variable
• Web server command
◦ Connection to Web server
◦ List Variables
◦ Read Variable
◦ Write Variable
◦ Access to File System
◦ Access to logger
• EcoStruxure Machine Expert command
◦ Reset Origin Device
◦ Login
◦ Set Node Name
◦ Update Logger
◦ Create Application
◦ Download application
◦ Pass RUN / STOP
◦ Reset (Cold / Warm / Origin)
◦ Delete Application
◦ Create Boot Application
◦ Save Retain Variables
EIO0000003089.05
61
◦ Restore Retain Variables
◦ Add Group
◦ Remove Group
◦ Add User
◦ Remove User
◦ Read User Rights
◦ Import User Rights
◦ Export User Rights
Access Rights
For each Group linked with an Object , User Rights are predefined with specifics
Access Rights .
This table indicates the Access Rights :
Access Rights
VIEW
MODIFY
ADD_REMOVE
EXECUTE
Access Rights Description (depends on the Object. See
Access Rights Needed by Object and Associated Operations, page 65
).
Allow to read only parameters and applications.
Allow to write, modify and download parameters and applications.
Allow to add and remove files, scripts and folders.
Allow to execute and start applications and scripts.
Predefined Access Rights for Group Persona
For each Group , several Objects are predefined with preset Access Rights :
Group: Administrator
Object name Access Rights
Device
FTP
VIEW
VIEW
/
/
MODIFY
MODIFY
/
/
ADD_REMOVE
ADD_REMOVE
/ EXECUTE
Logger
OPC_UA
PlcLogic
Settings
UserManagement
Web
FileSystem
VIEW
VIEW
VIEW
VIEW
VIEW
/
/
/
/
MODIFY
MODIFY
MODIFY
MODIFY
/ ADD_REMOVE
VIEW / MODIFY / EXECUTE
VIEW / MODIFY / ADD_REMOVE
/ EXECUTE
62 EIO0000003089.05
Group: Designer / Programmer persona
Object name
Device
FTP
Logger
OPC_UA
PlcLogic
Settings
UserManagement
Web
FileSystem
Access Rights
VIEW
VIEW
VIEW
VIEW
VIEW
VIEW
VIEW
VIEW
VIEW
/
/
/
/
/
/
/
ADD_REMOVE
MODIFY
MODIFY
MODIFY
MODIFY
MODIFY
MODIFY
/
/
/
/
ADD_REMOVE
ADD_REMOVE
EXECUTE
ADD_REMOVE
/ EXECUTE
Group: Operator persona
Object name Access Rights
Device
Logger
VIEW
VIEW
PlcLogic
Settings
UserManagement
Web
VIEW
VIEW
VIEW
VIEW
/
/
MODIFY
MODIFY
/
/
EXECUTE
EXECUTE
Group: Designer / Web designer persona
Object name
Device
FTP
Logger
OPC_UA
PlcLogic
Settings
UserManagement
Web
FileSystem
Access Rights
VIEW
VIEW / MODIFY / ADD_REMOVE
VIEW
VIEW
VIEW
VIEW
VIEW
VIEW / MODIFY / EXECUTE
VIEW / MODIFY / ADD_REMOVE
Group: Communication expert persona
Object name Access Rights
Device
FTP
VIEW
VIEW / MODIFY / ADD_REMOVE
Logger
OPC_UA
PlcLogic
Settings
UserManagement
Web
FileSystem
VIEW
VIEW
VIEW
VIEW
VIEW
/
/
MODIFY
MODIFY / EXECUTE
VIEW / MODIFY / EXECUTE
VIEW / MODIFY / ADD_REMOVE
EIO0000003089.05
63
Group: Maintenance persona
Object name
Device
FTP
Logger
OPC_UA
PlcLogic
Settings
UserManagement
Web
FileSystem
Access Rights
VIEW
VIEW / MODIFY / ADD_REMOVE
VIEW
VIEW
VIEW / EXECUTE
VIEW
VIEW
VIEW / MODIFY / EXECUTE
VIEW / MODIFY / ADD_REMOVE
Predefined Access Rights for Group Function
For each Group , several Objects are predefined with predefined Access Rights :
Group: Function External Media (1)
Object name Access Rights
ExternalCmd VIEW / MODIFY / ADD_REMOVE / EXECUTE
(1) NOTE: Enabling the objects in the group External Media will allow the access rights regardless of the user. That is to say, that the rights governing SD cards are global and are not confined to defined users
Group: Function File Access
Object name Access Rights
Logger
FileSystem
VIEW
VIEW / MODIFY / ADD_REMOVE
Group: Function FTP Access
Object name Access Rights
FTP
Logger
VIEW
VIEW
/ MODIFY / ADD_REMOVE
Group: Function Symbol Configuration Access
Object name Access Rights
Logger
OPC_UA
VIEW
VIEW / MODIFY
PlcLogic
Web
VIEW / MODIFY / ADD_REMOVE / EXECUTE
VIEW / MODIFY / EXECUTE
Group: Function Web Access
Object name Access Rights
Logger
Web
VIEW
VIEW / MODIFY / EXECUTE
64 EIO0000003089.05
Group: Function Monitor Access
Object name
Logger
Access Rights
VIEW
OPC_UA
PlcLogic
Web
VIEW
VIEW
VIEW
Group: Function OPC UA Access
Object name Access Rights
Logger
OPC_UA
VIEW
VIEW / MODIFY
Group: Function Variable Access
Object name Access Rights
Logger
OPC_UA
VIEW
VIEW
PlcLogic
Web
VIEW / MODIFY / ADD_REMOVE / EXECUTE
VIEW
Predefined Access Rights Needed by Object and Associated
Operations
Object Name
Device
ExternalCmd
FTP
ADD_REMOVE
Reset origin device
–
MODIFY
Set node name
Download
Access Rights
VIEW
Login
Upload
Clone
EXECUTE
–
Delete
Reboot
Set Node Name
Firewall install
Clone Check
–
Logger
OPC_UA
Connection to FTP
Server
Create file
Create folder
Upload file
Upload folder
Download file
Download folder
Delete file
Delete folder
–
–
Connection to FTP
Server
Download file
Download folder
Rename File
Rename Folder
Connection to FTP
Server
List directory
Change directory
Download file
Download folder
–
Connection OPC_UA
Read Variable
Write Variable
Update logger
Connection OPC_UA
Read Variable
–
–
EIO0000003089.05
65
Object Name
PlcLogic
Settings
UserManagement
Web
ADD_REMOVE
Create application
Download application
Delete application
Create Boot application
–
–
–
–
MODIFY
Write Variable
Access Rights
VIEW
Read Variable
Save retain variables
Reject / Trust Certificate
Set Node Name
Add Group
Remove Group
Add User
Remove User
Edit User Rights
Import User Rights
Reset Origin Device
Set Variables
–
–
Read User Rights
Export User Rights
Connection to Web
Server
Monitor Variables
Access Files System
–
EXECUTE
Pass Run / Stop
Reset
Restore Retains Var
–
–
Execute Command
– FileSystem
Symbol Rights
The Symbol Rights tab (see
) allows you to configure user group access to the symbol sets. It consists in a customizable set of symbols allowing to separate functions and associate them with a user right. If supported by the target device, you can combine different symbol sets from the symbols of the application in the symbol configuration editor. The information about the symbol sets is downloaded to the controller. Then you can define the user group that has access to each symbol set.
Troubleshooting
The only way to gain access to a controller that has user access-rights enabled and for which you do not have the password(s) is by performing an Update
Firmware operation. This clearing of User Rights can only be accomplished by using a SD card or USB key (depending on the support of your particular controller) to update the controller firmware. In addition, you may clear the User
Rights in the controller by running a script (for more information, refer to
EcoStruxure Machine Expert Programming Guide). This effectively removes the existing application from the controller memory, but restores the ability to access the controller.
66 EIO0000003089.05
Expansion Modules Configuration
Expansion Modules Configuration
Overview
This chapter describes how to configure the TM4, TM3, and TM2 expansion modules for the Modicon M251 Logic Controller.
TM4/TM3/TM2 Expansion Modules Configuration
Introduction
The Modicon M251 Logic Controller supports the following expansion modules:
• TM4 expansion modules
• TM3 expansion modules
◦ Digital I/O modules
◦ Analog I/O modules
◦ Expert I/O modules
◦ Safety modules
◦ Transmitter and receiver modules
• TM2 expansion modules
◦ Digital I/O modules
◦ Analog I/O modules
◦ Expert modules
◦ Communication modules
For further information about the TM4, TM3 and TM2 expansion modules configuration, refer to the TM4 Expansion Modules Configuration Programming
Guide, TM3 Expansion Modules Configuration Programming Guide and TM2
Expansion Modules Configuration Programming Guide respectively.
WARNING
UNINTENDED EQUIPMENT OPERATION
• Only use software approved by Schneider Electric for use with this equipment.
• Update your application program every time you change the physical hardware configuration.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Adding an Expansion Module
To add an expansion module to your controller, select the expansion module in the
Hardware Catalog , drag it to the Devices tree , and drop it on one of the highlighted nodes.
For more information on adding a device to your project, refer to:
• Using the Hardware Catalog
• Using the Contextual Menu or Plus Button
EIO0000003089.05
67
TM3 I/O Configuration General Description
Expansion Modules Configuration
Introduction
In your project, you can add I/O expansion modules to your M251 Logic Controller to increase the number of digital and analog inputs and outputs to the controller.
You can add either TM3 or TM2 I/O expansion modules to the logic controller, and further expand the number of I/O via TM3 transmitter and receiver modules to create remote I/O configurations. Special rules apply in all cases when creating local and remote I/O expansions, and when mixing TM2 and TM3 I/O expansion modules (refer to Maximum Hardware Configuration (see Modicon M251 Logic
Controller, Hardware Guide)).
The I/O expansion bus of the M251 Logic Controller is created when you assemble the I/O expansion modules to the logic controller. I/O expansion modules are considered as external devices in the logic controller architecture and, as such, are treated differently than the embedded I/Os of the logic controller.
I/O Expansion Bus Errors
If the logic controller cannot communicate with one or more I/O expansion modules contained in the program configuration, and those modules are not configured as optional modules (refer to
Optional I/O Expansion Modules, page
72 ), the logic controller detects it as an I/O expansion bus error. The unsuccessful
communication may be detected during the startup of the logic controller or during runtime, and there may be any number of causes. Causes of communication exceptions on the I/O expansion bus include, among other things, disconnection of or physically missing I/O modules, electromagnetic radiation beyond published environmental specifications, or otherwise inoperative modules.
If an I/O expansion bus error is detected:
• The system status LED I/O of the logic controller is illuminated indicating an I/
O error.
• When EcoStruxure Machine Expert is in online mode, a red triangle appears next to the TM3 expansion module or modules in error and next to the IO_
Bus node on the Devices tree window:
68
The following diagnostic information is also available:
• Bit 0 and bit 1 of the PLC_R.i_lwSystemFault_1
system variable are set to 0.
• The PLC_R.i_wIOStatus1
and PLC_R.i_wIOStatus2
system variables are set to PLC_R_IO_BUS_ERROR .
• The TM3_MODULE_R[i].i_wModuleState
system variable, where [i] identifies the TM3 expansion module in error, is set to TM3_BUS_ERROR .
• The TM3_GetModuleBusStatus function block returns the TM3_ERR_BUS error code.
Refer to PLC_R (see Modicon M251 Logic Controller, System Functions and
Variables, PLCSystem Library Guide) and TM3_MODULE_R (see Modicon M251
EIO0000003089.05
Expansion Modules Configuration
Logic Controller, System Functions and Variables, PLCSystem Library Guide) structures for details on system variables.
Active I/O Expansion Bus Error Handling
The TM3_BUS_W.q_wIOBusErrPassiv
system variable is set to ERR_ACTIVE by default to specify the use of active I/O error handling. The application can set this bit to ERR_PASSIVE to use passive I/O error handling instead.
By default, when the logic controller detects a TM3 module in bus communication error, it sets the bus to a "bus off" condition whereby the TM3 expansion module outputs, the input image value and the output image value are set to 0. A TM3 expansion module is considered to be in bus communication error when an I/O exchange with the expansion module has been unsuccessful for at least two consecutive bus task cycles. When a bus communication error occurs, the TM3_
MODULE_R[i].i_wModuleState
system variable, where [i] is the expansion module number in error, is set to TM3_BUS_ERROR . The other bits are set to
TM3_OK .
Normal I/O expansion bus operation can only be restored after eliminating the source of the error and performing one of the following:
• Power cycle
• New application download
• Restarting the I/O Bus by setting the TM3_BUS_W.q_wIOBusRestart
system variable to 1. The bus is restarted only if no expansion modules are in error ( TM3_MODULE_R[i].i_wModuleState
= TM3_BUS_ERROR ). Refer to
Restarting the I/O Expansion Bus, page 70
.
• Issuing a Reset Warm or Reset Cold command with
.
Passive I/O Expansion Bus Handling
The application can set the system variable TM3_BUS_W.q_wIOBusErrPassiv
to ERR_PASSIVE to use passive I/O error handling. This error handling is provided to afford compatibility with previous firmware versions.
When passive I/O error handling is in use, the logic controller attempts to continue data bus exchanges with the modules during bus communication errors. While the expansion bus error persists, the logic controller attempts to re-establish communication on the bus with incommunicative modules, depending on the type of I/O expansion module:
• For TM3 I/O expansion modules, the value of the I/O channels is maintained
( Keep current values ) for approximately 10 seconds while the logic controller attempts to re-establish communication. If the logic controller cannot re-establish communications within that time, the affected TM3 I/O expansion outputs are set to 0.
• For TM2 I/O expansion modules that may be part of the configuration, the value of the I/O channels is maintained indefinitely. That is to say, the outputs of the TM2 I/O expansion modules are set to “Keep current values” until either power is cycled on the logic controller system, or you issue a Reset Warm or
Reset Cold command with
EcoStruxure Machine Expert, page 43 .
In either case, the logic controller continues to solve logic and, if your controller is so equipped, the embedded I/O continues to be managed by the application
(“
managed by application program, page 41 ”) while it attempts to re-establish
communication with the incommunicative I/O expansion modules. If the communication is successful, the I/O expansion modules resume to be managed by the application. If communication with the I/O expansion modules is unsuccessful, you must resolve the reason for the unsuccessful communication, and then cycle power on the logic controller system, or issue a Reset Warm or
Reset Cold command with
EcoStruxure Machine Expert, page 43 .
EIO0000003089.05
69
Expansion Modules Configuration
The value of the incommunicative I/O expansion modules input image is maintained and the output image value is set by the application.
Further, if the incommunicative I/O module(s) disturb the communication with unaffected modules, the unaffected modules are also considered to be in error and the TM3_MODULE_R[i].i_wModuleState
system variable (where [i] is the expansion module number) is set to TM3_BUS_ERROR . However, with the ongoing data exchanges that characterize the Passive I/O Expansion Bus Error
Handling, the unaffected modules apply the data sent, and do not apply the fallback values as for the incommunicative module.
Therefore, you must monitor within your application the state of the bus and the error state of the module(s) on the bus, and take the appropriate action necessary given your particular application.
WARNING
UNINTENDED EQUIPMENT OPERATION
• Include in your risk assessment the possibility of unsuccessful communication between the logic controller and any I/O expansion modules.
• If the “Keep current values” option deployed during an I/O expansion module external error is incompatible with your application, use alternate means to control your application for such an event.
• Monitor the state of the I/O expansion bus using the dedicated system variables and take appropriate actions as determined by your risk assessment.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
For more information on the actions taken upon startup of the logic controller when an I/O expansion bus error is detected, refer to
.
Restarting the I/O Expansion Bus
When active I/O error handling is being applied, that is, embedded and TM3 outputs set to 0 when a bus communication error is detected, the application can request a restart of the I/O expansion bus while the logic controller is still running
(without the need for a Cold Start, Warm Start, power cycle, or application download).
The TM3_BUS_W. q_wIoBusRestart system variable is available to request restarts of the I/O expansion bus. The default value of this bit is 0. Provided at least one TM3 expansion module is in error ( TM3_MODULE_R[i].i_
wModuleState set to TM3_BUS_ERROR ), the application can set TM3_BUS_W.
q_wIoBusRestart to 1 to request a restart of the I/O expansion bus. On detection of a rising edge of this bit, the logic controller reconfigures and restarts the I/O expansion bus if all of the following conditions are met:
• The TM3_BUS_W.q_wIOBusErrPassiv
system variable is set to ERR_
ACTIVE (that is, I/O expansion bus activity is stopped)
• Bit 0 and bit 1 of the PLC_R.i_lwSystemFault_1
system variable are set to 0 (I/O expansion bus is in error)
• The TM3_MODULE_R[i].i_wModuleState
system variable is set to TM3_
BUS_ERROR (at least one expansion module is in bus communication error)
If the TM3_BUS_W.q_wIoBusRestart
system variable is set to 1 and any of the above conditions is not met, the logic controller takes no action.
70 EIO0000003089.05
Expansion Modules Configuration
Match Software and Hardware Configuration
The I/O that may be embedded in your controller is independent of the I/O that you may have added in the form of I/O expansion. It is important that the logical I/O configuration within your program matches the physical I/O configuration of your installation. If you add or remove any physical I/O to or from the I/O expansion bus or, depending on the controller reference, to or from the controller (in the form of cartridges), then you must update your application configuration. This is also true for any field bus devices you may have in your installation. Otherwise, there is the potential that the expansion bus or field bus no longer function while the embedded I/O that may be present in your controller continues to operate.
WARNING
UNINTENDED EQUIPMENT OPERATION
Update the configuration of your program each time you add or delete any type of I/O expansions on your I/O bus, or you add or delete any devices on your field bus.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Presentation of the Optional Feature for I/O Expansion Modules
I/O expansion modules can be marked as optional in the configuration. The
Optional module feature provides a more flexible configuration by the acceptance of the definition of modules that are not physically attached to the logic controller. Therefore, a single application can support multiple physical configurations of I/O expansion modules, allowing a greater degree of scalability without the necessity of maintaining multiple application files for the same application.
You must be fully aware of the implications and impacts of marking I/O modules as optional in your application, both when those modules are physically absent and present when running your machine or process. Be sure to include this feature in your risk analysis.
WARNING
UNINTENDED EQUIPMENT OPERATION
Include in your risk analysis each of the variations of I/O configurations that can be realized marking I/O expansion modules as optional, and in particular the establishment of TM3 Safety modules (TM3S…) as optional I/O modules, and make a determination whether it is acceptable as it relates to your application.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: For more details about this feature, refer to
.
TM3 I/O Bus Configuration
Overview
TM3 I/O bus configuration enables you to select the task that drives TM3 physical exchanges. It can also override the configuration defined in the
bus cycle task.
EIO0000003089.05
71
Configuring the I/O Bus
Follow these steps to configure the TM3 I/O bus:
Step Description
1 In the Devices tree , double-click IO_Bus
Result : The IO_Bus editor tab appears:
.
Expansion Modules Configuration
2 Set the Bus cycle task from the list to either of the following:
• Use parent bus cycle setting (default)
Sets the task for bus exchange as defined in the PLC settings .
• MAST
Sets the Master task for bus exchange irrespective of the task defined in the PLC settings .
Optional I/O Expansion Modules
Presentation
I/O expansion modules can be marked as optional in the configuration. The
Optional module feature provides a more flexible configuration by the acceptance of the definition of modules that are not physically attached to the controller. Therefore, a single application can support multiple physical configurations of I/O expansion modules, allowing a greater degree of scalability without the necessity of maintaining multiple application files for the same application.
Without the Optional module feature, when the controller starts up the I/O expansion bus (following a power cycle, application download or initialization command), it compares the configuration defined in the application with the physical I/O modules attached to the I/O bus. Among other diagnostics made, if the controller determines that there are I/O modules defined in the configuration that are not physically present on the I/O bus, an error is detected and the I/O bus does not start.
With the Optional module feature, the controller ignores the absent I/O expansion modules that you have marked as optional, which then allows the controller to start the I/O expansion bus.
The controller starts the I/O expansion bus at configuration time (following a power cycle, application download, or initialization command) even if optional expansion modules are not physically connected to the controller.
The following module types can be marked as optional:
• TM3 I/O expansion modules
• TM2 I/O expansion modules
NOTE: TM3 Transmitter/Receiver modules (the TM3XTRA1 and the
TM3XREC1) and TMC4 cartridges cannot be marked as optional.
72 EIO0000003089.05
Expansion Modules Configuration
You must be fully aware of the implications and impacts of marking I/O modules as optional in your application, both when those modules are physically absent and present when running your machine or process. Be sure to include this feature in your risk analysis.
WARNING
UNINTENDED EQUIPMENT OPERATION
Include in your risk analysis each of the variations of I/O configurations that can be realized marking I/O expansion modules as optional, and in particular the establishment of TM3 Safety modules (TM3S…) as optional I/O modules, and make a determination whether it is acceptable as it relates to your application.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Marking an I/O Expansion Module as Optional
To add an expansion module and mark it as optional in the configuration:
Step
1
2
3
4
Action
Add the expansion module to your controller.
In the Devices tree , double-click the expansion module.
Select the I/O Configuration tab.
In the Optional module line, select Yes in the Value column:
Shared Internal ID Codes
Controllers and bus couplers identify expansion modules by a simple internal ID code. This ID code is not specific to each reference, but identifies the logical structure of the expansion module. Therefore, different references can share the same ID code.
You cannot have two modules with the same internal ID code declared as optional without at least one mandatory module placed between them.
EIO0000003089.05
73
Expansion Modules Configuration
This table groups the module references sharing the same internal ID code:
Modules sharing the same internal ID code
TM2DDI16DT, TM2DDI16DK
TM2DRA16RT, TM2DDO16UK, TM2DDO16TK
TM2DDI8DT, TM2DAI8DT
TM2DRA8RT, TM2DDO8UT, TM2DDO8TT
TM2DDO32TK, TM2DDO32UK
TM3DI16K, TM3DI16, TM3DI16G
TM3DQ16R, TM3DQ16RG, TM3DQ16T, TM3DQ16TG, TM3DQ16TK, TM3DQ16U, TM3DQ16UG,
TM3DQ16UK
TM3DQ32TK, TM3DQ32UK
TM3DI8, TM3DI8G, TM3DI8A
TM3DQ8R, TM3DQ8RG, TM3DQ8T, TM3DQ8TG, TM3DQ8U, TM3DQ8UG
TM3DM8R, TM3DM8RG
TM3DM24R, TM3DM24RG
TM3SAK6R, TM3SAK6RG
TM3SAF5R, TM3SAF5RG
TM3SAC5R, TM3SAC5RG
TM3SAFL5R, TM3SAFL5RG
TM3AI2H, TM3AI2HG
TM3AI4, TM3AI4G
TM3AI8, TM3AI8G
TM3AQ2, TM3AQ2G
TM3AQ4, TM3AQ4G
TM3AM6, TM3AM6G
TM3TM3, TM3TM3G
TM3TI4, TM3TI4G
TM3TI4D, TM3TI4DG
TM3TI8T, TM3TI8TG
TM3XHSC202, TM3XHSC202G
Optional Modules Diagnostic
The following diagnostic information is available: TM3_MODULE_R[i].i_
wModuleState system variable, where [i] identifies the absent TM3 optional expansion module, is set to TM3_MISSING_OPT_MOD .
74 EIO0000003089.05
Ethernet Configuration
Introduction
This chapter describes how to configure the Ethernet network interface of the
Modicon M251 Logic Controller.
Ethernet Features, Functions and Services
Presentation
Ethernet Features, Functions and Services
The controller supports the following services:
•
•
•
•
•
•
Controller as Target Device On EtherNet/IP, page 94
•
Controller as Slave Device On Modbus TCP, page 112
•
• Web visualization
•
TM251MESE Specific Considerations
The TM251MESE has two different Ethernet networks. Each one gets its own and unique IP and MAC address.
The two Ethernet networks are called Ethernet 1 and Ethernet 2:
• Ethernet 1 is a dual port Ethernet switch dedicated to communication between machines or with the control network.
• Ethernet 2 is a separate Ethernet port dedicated to device network connections.
For example, you can:
• Connect your PC to the Ethernet 1.
• Use a Modbus TCP I/O scanner with the Ethernet 2.
The Network Variables List (NVL) communication works on the:
• Ethernet 1 port.
• Ethernet 2 port only if the Ethernet 1 port has a valid IP address and is connected to a device.
EIO0000003089.05
75
Ethernet Protocols
The controller supports the following protocols:
• IP (Internet Protocol)
• UDP (User Datagram Protocol)
• TCP (Transmission Control Protocol)
• ARP (Address Resolution Protocol)
• ICMP (Internet Control Messaging Protocol)
• IGMP (Internet Group Management Protocol)
Connections
This table shows the maximum number of connections:
Connection Type
Modbus Server
Modbus Client
EtherNet/IP Target
FTP Server
Web Server
Machine Expert Protocol (EcoStruxure Machine
Expert software, trace, Web visualization, HMI devices)
4
10
8
Maximum Number of Connections
8
8
16
NOTE: When at least one EtherNet/IP target is configured, the total number of connections (EtherNet/IP plus Modbus TCP) is limited to 16. Only if the
Modbus TCP IOScanner is exclusively used may the total number of slave devices can be up to 64. These maximums are controlled for at build time.
Each connection based on TCP manages its own set of connections as follows:
1. When a client tries to open a connection that exceeds the poll size, the controller closes the oldest connection.
2. If all connections are busy (exchange in progress) when a client tries to open a new one, the new connection is denied.
3. The server connections stay open as long as the controller stays in operational states ( RUNNING , STOPPED , HALT ).
4. The server connections are closed when leaving operational states
( RUNNING , STOPPED , HALT ), except in case of power outage (because the controller does not have time to close the connections).
Connections can be closed when the originator of the connection requests to close the connection it had previously opened.
Services Available
With an Ethernet communication, the IEC VAR ACCESS service is supported by the controller. With the IEC VAR ACCESS service, data can be exchanged between the controller and an HMI.
The NetWork variables service is also supported by the controller. With the
NetWork variables service, data can be exchanged between controllers.
NOTE: For more information, refer to the EcoStruxure Machine Expert
Programming Guide.
76 EIO0000003089.05
IP Address Configuration
Introduction
There are different ways to assign the IP address to the added Ethernet interface of the controller:
• Address assignment by DHCP server
• Address assignment by BOOTP server
• Fixed IP address
•
Post configuration file, page 158
. If a post configuration file exists, this assignment method has priority over the others.
The IP address can also be changed dynamically through the:
• Communication Settings (see EcoStruxure Machine Expert, Programming
Guide) tab in EcoStruxure Machine Expert
• changeIPAddress
NOTE: If the attempted addressing method is unsuccessful, the link uses a
derived from the MAC address.
Carefully manage the IP addresses because each device on the network requires a unique address. Having multiple devices with the same IP address can cause unintended operation of your network and associated equipment.
WARNING
UNINTENDED EQUIPMENT OPERATION
• Verify that there is only one master controller configured on the network or remote link.
• Verify that all devices have unique addresses.
• Obtain your IP address from your system administrator.
• Confirm that the IP address of the device is unique before placing the system into service.
• Do not assign the same IP address to any other equipment on the network.
• Update the IP address after cloning any application that includes Ethernet communications to a unique address.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: Verify that your system administrator maintains a record of assigned IP addresses on the network and subnetwork, and inform the system administrator of any configuration changes performed.
EIO0000003089.05
77
Address Management
This diagram shows the different types of address systems for the controller:
78
NOTE: If a device programmed to use the DHCP or BOOTP addressing methods is unable to contact its respective server, the controller uses the default IP address. It repeats its request constantly.
The IP process restarts in the following cases:
• Controller reboot
• Ethernet cable reconnection
• Application download (if IP parameters change)
• DHCP or BOOTP server detected after a prior addressing attempt was unsuccessful.
EIO0000003089.05
Ethernet Configuration
In the Devices tree , double-click Ethernet_1 :
Configured Parameters
Network Name my_Device
IP Address by DHCP
IP Address by BOOTP fixed IP Address
IP Address
Subnet Mask
Gateway Address
Ethernet Protocol
Transfer Rate
95 . 16 . 221 . 17
255 . 0 . 0 . 0
0 . 0 . 0 . 0
Ethernet 2
Auto
Security Parameters
Protocol inactive
FTP Server
IP Forwarding
Modbus Server
SNMP protocol
Web Visualisation protocol
>>
<<
Protocol active
Discovery protocol
Machine Expert protocol
Secured Web Server (HTTPS)
Current Settings
Network Name my_Device
IP Address by DHCP
IP Address by BOOTP fixed IP Address
IP Address
Subnet Mask
Gateway Address
Ethernet Protocol
Transfer Rate
95 . 16 . 221 . 17
255 . 0 . 0 . 0
0 . 0 . 0 . 0
Ethernet 2
100 MBit full
Security Parameters
Protocol inactive
FTP Server
IP Forwarding
Modbus Server
SNMP protocol
Web Visualisation protocol
>>
<<
Protocol active
Discovery protocol
Machine Expert protocol
Secured Web Server (HTTPS)
Configured Parameters
Network Name
IP Address by DHCP
IP Address by BOOTP
Fixed IP Address
Ethernet Protocol
Transfer Rate
Slave device identification
DHCP Server active
When active, each device that will be added to the fieldbus, can be configured in order to be identified by its name or MAC Address, instead of its IP Address.
Adapter Status
MAC Address
Network Status
00:80:F4:0B:2E:45
Data Exchanges
Note: If you are in online mode, you see the two windows. You cannot edit them. If you are in offline mode, you see the Configured Parameters window. You can edit it.
This table describes the configured parameters:
Description
Used as device name to retrieve IP address through DHCP, maximum 15 characters.
IP address is obtained by DHCP server.
IP address is obtained by BOOTP server.
IP address, Subnet Mask, and Gateway Address are defined by the user.
Protocol type used (Ethernet 2).
Speed and Duplex are in auto-negotiation mode.
Default IP Address
The default IP addresses are:
• 10.11.x.x. for Ethernet_1
• 10.10.x.x. for Ethernet_2 (only available on TM251MESE)
NOTE: The two IP addresses must not be in the same IP network.
The last two fields in the default IP address are composed of the decimal equivalent of the last two hexadecimal bytes of the MAC address of the port.
The MAC address of the port can be retrieved on the label placed on the front side of the controller.
The default subnet mask is Default Class A Subnet Mask of 255.0.0.0.
NOTE: A MAC address is written in hexadecimal format and an IP address in decimal format. Convert the MAC address to decimal format.
Example: If the MAC address is 00.80.F4.01.80.F2, the default IP address is
10.10.128.242.
EIO0000003089.05
79
Address Classes
The IP address is linked:
• to a device (the host)
• to the network to which the device is connected
An IP address is always coded using 4 bytes.
The distribution of these bytes between the network address and the device address may vary. This distribution is defined by the address classes.
The different IP address classes are defined in this table:
Address Class
Class A
Class B
Class C
Class D
Class E
Byte1
1
1
0
1
1
Byte 2 Byte 3 Byte 4
1
1
Network ID
0 Network ID
1
0
1
1
Network ID
0
1 0
Host ID
Multicast Address
Host ID
Host ID
Address reserved for subsequent use
Subnet Mask
The subnet mask is used to address several physical networks with a single network address. The mask is used to separate the subnetwork and the device address in the host ID.
The subnet address is obtained by retaining the bits of the IP address that correspond to the positions of the mask containing 1, and replacing the others with
0.
Conversely, the subnet address of the host device is obtained by retaining the bits of the IP address that correspond to the positions of the mask containing 0, and replacing the others with 1.
Example of a subnet address:
IP address
Subnet mask
Subnet address
192 (11000000)
255 (11111111)
192 (11000000)
1 (00000001)
255 (11111111)
1 (00000001)
17 (00010001)
240 (11110000)
16 (00010000)
11 (00001011)
0 (00000000)
0 (00000000)
NOTE: The device does not communicate on its subnetwork when there is no gateway.
Gateway Address
The gateway allows a message to be routed to a device that is not on the same network.
If there is no gateway, the gateway address is 0.0.0.0.
The gateway address can be defined on Ethernet_1 interface. The traffic to unknown networks is sent through this gateway address, or to address configured on
80 EIO0000003089.05
Security Parameters
This table describes the different security parameters:
Security Parameters Description
Discovery protocol
FTP Server
This parameter deactivates Discovery protocol. When deactivated, Discovery requests are ignored.
This parameter deactivates the FTP Server of the controller. When deactivated, FTP requests are ignored.
Machine Expert protocol This parameter deactivates the Machine Expert protocol on Ethernet interfaces. When deactivated, any Machine Expert request from any device is rejected, including those from the UDP or TCP connection. Therefore, no connection is possible on Ethernet from a PC with
EcoStruxure Machine Expert, from an HMI target that wants to exchange variables with this controller, from an OPC server, or from Controller Assistant.
Modbus Server This parameter deactivates the Modbus Server of the controller. When deactivated, any
Modbus request to the controller is ignored.
IP Forwarding
SNMP protocol
This parameter deactivates the IP forwarding service of the controller. When deactivated, devices on the device network are no longer accessible from the control network (Web pages, DTM, and so on).
NOTE: This parameter is only available on the Ethernet_1 network.
This parameter deactivates the SNMP server of the controller. When deactivated, SNMP requests are ignored.
Secured Web Server
(HTTPS)
WebVisualisation protocol
This parameter deactivates the Web Server of the controller. When deactivated, HTTPS requests to the controller Web Server are ignored.
This parameter deactivates the Web visualization pages of the controller. When deactivated,
HTTP requests to the logic controller WebVisualisation protocol are ignored.
Default settings
Active
Active
Active
Inactive
Inactive
Inactive
Active
Inactive
Slave Device Identification
When DHCP Server active is selected, devices added to the fieldbus can be configured to be identified by their name or MAC address, instead of their IP address. Refer to
.
NOTE: This parameter is only available on the Ethernet_2 network.
Modbus TCP Client/Server
Introduction
Unlike Modbus serial link, Modbus TCP is not based on a hierarchical structure, but on a client/server model.
The Modicon M251 Logic Controller implements both client and server services so that it can initiate communications to other controllers and I/O devices, and to respond to requests from other controllers, SCADA, HMIs, and other devices. By default, Modbus Server functionality is not active.
Without any configuration, the embedded Ethernet port of the controller supports
Modbus server.
The Modbus client/server is included in the firmware and does not require any programming action from the user. Due to this feature, it is accessible in
RUNNING, STOPPED and EMPTY states.
EIO0000003089.05
81
Modbus TCP Client
The Modbus TCP client supports the following function blocks from the
PLCCommunication library without any configuration:
• ADDM
• READ_VAR
• SEND_RECV_MSG
• SINGLE_WRITE
• WRITE_READ_VAR
• WRITE_VAR
For further information, refer to the Function Block Descriptions (see EcoStruxure
Machine Expert, Modbus and ASCII Read/Write Functions, PLCCommunication
Library Guide).
Modbus TCP Server
The Modbus server supports the Modbus requests:
Function Function Code
Dec (Hex)
1 (1)
2 (2)
3 (3)
6 (6)
8 (8)
15 (F)
16 (10)
23 (17)
43 (2B)
–
–
–
–
–
–
Subfunction
Dec (Hex)
–
–
14 (E)
Read digital outputs (%Q)
Read digital inputs (%I)
Read holding register (%MW)
Write single register (%MW)
Diagnostic
Write multiple digital outputs (%Q)
Write multiple registers (%MW)
Read/write multiple registers (%MW)
Read device identification
NOTE: The embedded Modbus server only ensures time-consistency for a single word (2 bytes). If your application requires time-consistency for more than 1 word,
add and configure a Modbus TCP Slave Device , page 112
so that the contents of the %IW and %QW buffers are time-consistent in the associated IEC task (MAST by default).
Web Server
Introduction
As standard equipment, the controller provides an embedded Web server with a predefined, built-in website. You can use the pages of the website for module setup and control as well as application diagnostics and monitoring. These pages are ready to use with a Web browser. No configuration or programming is required.
The Web server can be accessed by the web browsers listed below:
• Google Chrome (version 87 or greater)
• Mozilla Firefox (version 62 or greater)
The Web server is limited to 10
.
NOTE: The Web server can be disabled by unchecking the Web Server active parameter in the
Ethernet Configuration tab, page 79 .
82 EIO0000003089.05
The Web server is a tool for reading and writing data, and controlling the state of the controller, with access to all data in your application. However, if there are security concerns over these functions, you must at a minimum assign a secure password to the Web Server or disable the Web server to prevent unauthorized access to the application. By enabling the Web server, you enable these functions.
The Web server allows you to monitor a controller and its application remotely, to perform various maintenance activities including modifications to data and configuration parameters, and change the state of the controller. Care must be taken to ensure that the immediate physical environment of the machine and process is in a state that will not present safety risks to people or property before exercising control remotely.
WARNING
UNINTENDED EQUIPMENT OPERATION
• Define a secure password for the Web Server and do not allow unauthorized or otherwise unqualified personnel to use this feature.
• Ensure that there is a local, competent, and qualified observer present when operating on the controller from a remote location.
• You must have a complete understanding of the application and the machine/process it is controlling before attempting to adjust data, stopping an application that is operating, or starting the controller remotely.
• Take the precautions necessary to assure that you are operating on the intended controller by having clear, identifying documentation within the controller application and its remote connection.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Web Server Access
Access to the Web server is controlled by User Rights when they are enabled in the controller. For more information, refer to Users and Groups
.
To access the Web server you must first connect to the controller with
EcoStruxure Machine Expert or Controller Assistant.
WARNING
UNAUTHORIZED DATA ACCESS
• Secure access to the FTP/Web server using User Rights.
• If you disable User Rights, disable the FTP/Web server to prevent any unwanted or unauthorized access to data in your application.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
In order to change the password, go to Users and Groups tab of the device editor. For more information, refer to the EcoStruxure Machine Expert
Programming Guide (see EcoStruxure Machine Expert, Programming Guide).
NOTE: The only way to gain access to a controller that has user access-rights enabled and for which you do not have the password(s) is by performing an
Update Firmware operation. This clearing of User Rights can only be accomplished by using a SD card or USB key (depending on the support of your particular controller) to update the controller firmware. In addition, you may clear the User Rights in the controller by running a script (for more information, refer to EcoStruxure Machine Expert Programming Guide (see
EcoStruxure Machine Expert, Programming Guide)) . This effectively removes the existing application from the controller memory, but restores the ability to access the controller.
EIO0000003089.05
83
Home Page Access
To access the website home page, type in your navigator the IP address of the controller.
This figure shows the Web Server site login page:
This figure shows the home page of the Web Server site once you have logged in:
84
NOTE: Schneider Electric adheres to industry best practices in the development and implementation of control systems. This includes a
"Defense-in-Depth" approach to secure an Industrial Control System. This approach places the controllers behind one or more firewalls to restrict access to authorized personnel and protocols only.
EIO0000003089.05
WARNING
UNAUTHENTICATED ACCESS AND SUBSEQUENT UNAUTHORIZED
MACHINE OPERATION
• Evaluate whether your environment or your machines are connected to your critical infrastructure and, if so, take appropriate steps in terms of prevention, based on Defense-in-Depth, before connecting the automation system to any network.
• Limit the number of devices connected to a network to the minimum necessary.
• Isolate your industrial network from other networks inside your company.
• Protect any network against unintended access by using firewalls, VPN, or other, proven security measures.
• Monitor activities within your systems.
• Prevent subject devices from direct access or direct link by unauthorized parties or unauthenticated actions.
• Prepare a recovery plan including backup of your system and process information.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Monitoring: Data Parameters
Monitoring Web Server Variables
To monitor Web server variables, you must add a Web Data Configuration object to your project. Within this object, you can select all variables you want to monitor.
This table describes how to add a Web Data Configuration object:
Step
1
2
3
Action
Right click the Application node in the Applications tree tab.
Click Add Object > Web Data Configuration...
.
Result: The Add Web Data Configuration window is displayed.
Click Add .
Result: The Web Data Configuration object is created and the Web Data
Configuration editor is open.
NOTE: As a Web Data Configuration object is unique for a controller, its name cannot be changed.
Web Data Configuration Editor
Click the Refresh button to be able to select variables, this action will display all the variables defined in the application.
EIO0000003089.05
85
Select the variables you want to monitor in the web server:
86
NOTE: The variable selection is possible only in offline mode.
Monitoring: Data Parameters Submenu
The Data Parameters submenu allows you to create and monitor some lists of variables. You can create several lists of variables (maximum 10 lists), each one containing several variables of the controller application (maximum 20 variables per list).
Each list has a name, and a refresh period. The lists are saved in the non-volatile memory of the controller, so that a created list can be accessed (loaded, modified, saved) from any Web client application accessing this controller.
The Data Parameters submenu allows you to display and modify variable values:
EIO0000003089.05
Element
Add
Del
Refresh period
Refresh
Description
Adds a list description or a variable
Deletes a list description or a variable
Refreshing period of the variables contained in the list description (in ms)
Load
Save
Enables I/O refreshing:
• Gray button: refreshing disabled
• Orange button: refreshing enabled
Loads saved lists from the controller non-volatile memory to the Web server page
Saves the selected list description in the controller ( /usr/web directory)
NOTE: The IEC objects ( %IX , %QX ) are not directly accessible. To access IEC objects you must first group their contents in located registers (refer to
).
NOTE: Bit memory variables ( %MX ) cannot be selected.
Monitoring: IO Viewer Submenu
The IO Viewer submenu allows you to display and modify the I/O values:
EIO0000003089.05
Element
Refresh
1000 ms
<<
>>
Description
Enables I/O refreshing:
• Gray button: refreshing disabled
• Orange button: refreshing enabled
I/O refreshing period in ms
Goes to previous I/O list page
Goes to next I/O list page
87
Monitoring: Oscilloscope Submenu
The Oscilloscope submenu can display up to 2 variables in the form of a recorder time chart:
Element
Reset
Refresh
Load
Save
Item0
Item1
Min
Max
Period(ms)
Description
Erases the memorization
Starts/stops refreshing
Loads parameter configuration of Item0 and Item1
Saves parameter configuration of Item0 and Item1 in the controller
Variable to be displayed
Variable to be displayed
Minimum value of the variable axis
Maximum value of the variable axis
Page refresh period in milliseconds
88 EIO0000003089.05
Diagnostics: Ethernet Submenu
This figure shows the remote ping service:
Diagnostics: Scanner Status Submenu
The Scanner Status submenu displays status of the Modbus TCP I/O Scanner
(IDLE, STOPPED, OPERATIONAL) and the health bit of up to 64 Modbus scanned devices.
For more information, refer to EcoStruxure Machine Expert Modbus TCP User guide.
Diagnostics: EtherNet/IP Status Submenu
The EtherNet/IP Status submenu displays the status of the EtherNet/IP Scanner
(IDLE, STOPPED, OPERATIONAL) and the health bit of up to 16 EtherNet/IP target devices.
For more information, refer to EcoStruxure Machine Expert EtherNet/IP User guide.
Maintenance Page
The Maintenance page provides access to the controller data for maintenance capabilities.
EIO0000003089.05
89
Maintenance: Post Conf Submenu
The Post Conf submenu allows you to update the
saved on the controller:
Step
1
2
3
Action
Click Load .
Modify the parameters, page 160 .
Click Save .
NOTE: The new parameters will be considered at next
Post Configuration file reading, page 158
.
Maintenance: EIP Config Files Submenu
The file tree only appears when the Ethernet IP service is configured on the controller.
Index of /usr :
File
My Machine Controller.gz
My Machine Controller.ico
My Machine Controller.eds
Description
GZIP file
Icon file
Electronic Data Sheet file
Maintenance: User Management Submenu
The User Management submenu displays a screen that allows you to access two different actions, all restricted by using secure protocol (HTTPS):
90 EIO0000003089.05
• User accounts management :
Allows you to manage user accounts management, removing all password and returning all user accounts on the controller to default settings.
Disable
Users accounts management
Reset to default
Click Disable to deactivate all user rights on the controller. (Passwords are saved and are restored if you click Enable .)
Click OK on the window that appears to confirm. As a result:
• Users no longer have to set and enter a password to connect to the controller.
• FTP, HTTP, and OPC UA server connections accept anonymous user connections. See
Login and passwords table, page 59 .
NOTE: The Disable button is only active if the user has administrator privileges.
Users accounts management
Enable Reset to default
Click Enable to restore the previous user rights saved on the controller.
Click OK on the window that appears to confirm. As a result, users have to enter the password previously set to connect to the controller. See
Login and passwords table, page 59 .
NOTE: The Enable only appears if the user rights were disabled and the user rights backup file is available on the controller.
Click Reset to default to return all user accounts on the controller to their default setting state.
Click OK on the window that appears to confirm.
NOTE: Connections to FTP, HTTP, and the OPC UA server are blocked until a new password is set.
• Clone management :
Allows you to control whether user rights are copied and applied to the target controller when cloning a controller with an
.
Clone management
Exclude users rights Include users rights
Click Exclude users rights to exclude copying user rights to the target controller when cloning a controller.
NOTE: By default, the users rights are excluded.
Click Include users rights to copy user rights to the target controller when cloning a controller. A popup prompts you to confirm copying the user rights. Click
OK to continue.
NOTE: The Exclude users rights and Include users rights buttons are only active if the current user is connected to the controller using a secure protocol.
EIO0000003089.05
91
FTP Server
Introduction
Any FTP client that is connected to the controller (Ethernet port), without
EcoStruxure Machine Expert installed, can be used to transfer files to and from the data storage area of the controller.
NOTE: Schneider Electric adheres to industry best practices in the development and implementation of control systems. This includes a
"Defense-in-Depth" approach to secure an Industrial Control System. This approach places the controllers behind one or more firewalls to restrict access to authorized personnel and protocols only.
WARNING
UNAUTHENTICATED ACCESS AND SUBSEQUENT UNAUTHORIZED
MACHINE OPERATION
• Evaluate whether your environment or your machines are connected to your critical infrastructure and, if so, take appropriate steps in terms of prevention, based on Defense-in-Depth, before connecting the automation system to any network.
• Limit the number of devices connected to a network to the minimum necessary.
• Isolate your industrial network from other networks inside your company.
• Protect any network against unintended access by using firewalls, VPN, or other, proven security measures.
• Monitor activities within your systems.
• Prevent subject devices from direct access or direct link by unauthorized parties or unauthenticated actions.
• Prepare a recovery plan including backup of your system and process information.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: Make use of the security-related commands (see EcoStruxure
Machine Expert, Menu Commands, Online Help) which provide a way to add, edit, and remove a user in the online user management of the target device where you are currently logged in.
FTP Access
Files Access
Access to the FTP server is controlled by User Rights when they are enabled in the controller. For more information, refer to Users and Groups
To access the FTP server you must first connect to the controller with EcoStruxure
Machine Expert or Controller Assistant and activate the user rights or create the user for the first login.
NOTE: FTPS (explicit over TLS FTP) is set by default. Simple FTP (non secure) access is not possible at first connection. Set the parameter 1106 to 0 in the post configuration and reboot the controller to allow Simple FTP connection.
See
.
92 EIO0000003089.05
FTP Client
Introduction
The FtpRemoteFileHandling library provides the following FTP client functionalities for remote file handling:
• Reading files
• Writing files
• Deleting files
• Listing content of remote directories
• Adding directories
• Removing directories
NOTE: Schneider Electric adheres to industry best practices in the development and implementation of control systems. This includes a
"Defense-in-Depth" approach to secure an Industrial Control System. This approach places the controllers behind one or more firewalls to restrict access to authorized personnel and protocols only.
WARNING
UNAUTHENTICATED ACCESS AND SUBSEQUENT UNAUTHORIZED
MACHINE OPERATION
• Evaluate whether your environment or your machines are connected to your critical infrastructure and, if so, take appropriate steps in terms of prevention, based on Defense-in-Depth, before connecting the automation system to any network.
• Limit the number of devices connected to a network to the minimum necessary.
• Isolate your industrial network from other networks inside your company.
• Protect any network against unintended access by using firewalls, VPN, or other, proven security measures.
• Monitor activities within your systems.
• Prevent subject devices from direct access or direct link by unauthorized parties or unauthenticated actions.
• Prepare a recovery plan including backup of your system and process information.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
For further information, refer to FtpRemoteFileHandling Library Guide.
SNMP
Introduction
The Simple Network Management Protocol (SNMP) is used to provide the data and services required for managing a network.
The data is stored in a Management Information Base (MIB). The SNMP protocol is used to read or write MIB data. Implementation of the Ethernet SNMP services is minimal, as only the compulsory objects are handled.
EIO0000003089.05
93
SNMP Server
This table presents the supported standard MIB-2 server objects:
Object sysDescr
Description
Text description of the device sysName Node administrative name
Access
Read
Read/
Write
Value
SCHNEIDER M241-51 Fast
Ethernet TCP/IP
Controller reference
The size of these character strings is limited to 50 characters.
The values written are saved to the controller via SNMP client tool software. The
Schneider Electric software for this is ConneXview. ConneXview is not supplied with the controller or bus coupler. For more details, refer to www.se.com
.
SNMP Client
The M251 Logic Controller supports an SNMP client library to allow you to query
SNMP servers. For details, refer to the EcoStruxure Machine Expert
SnmpManager, Library Guide.
Controller as a Target Device on EtherNet/IP
Introduction
This section describes the configuration of the M251 Logic Controller as an
EtherNet/IP target device.
For further information about EtherNet/IP, refer to the www.odva.org
website.
EtherNet/IP Target Configuration
To configure your M251 Logic Controller as an EtherNet/IP target device, you must:
Step
1
2
Action
Select EthernetIP in the Hardware Catalog .
Drag and drop it to the Devices tree on one of the highlighted nodes.
For more information on adding a device to your project, refer to:
• Using the Hardware Catalog
• Using the Contextual Menu or Plus Button
EtherNet/IP Parameters Configuration
To configure the EtherNet/IP parameters, double-click Ethernet_1 (Ethernet
Network) > EthernetIP in the Devices tree .
94 EIO0000003089.05
This dialog box is displayed:
The EtherNet/IP configuration parameters are defined as:
• Instance :
Number referencing the input or output Assembly.
• Size :
Number of channels of an input or output Assembly.
The memory size of each channel is 2 bytes that stores the value of an %IWx or %QWx object, where x is the channel number.
For example, if the Size of the Output Assembly is 20, it represents that there are 20 input channels (IW0...IW19) addressing %IWy...%IW(y+20-1), where y is the first available channel for the Assembly.
Element
Output
Assembly
Input Assembly
Instance
Size
Instance
Size
Admissible Controller
Range
150...189
2...120
100...149
2...120
EcoStruxure Machine Expert
Default Value
150
20
100
20
EDS File Generation
You can generate an EDS file to configure EtherNet/IP cyclic data exchanges.
To generate the EDS file:
Step
1
2
3
Action
In the Devices tree , right-click the EthernetIP node and choose the Export as EDS command from the contextual menu.
Modify the default file name and location as required.
Click Save .
NOTE: The Major Revision and Minor Revision objects of the EDS file, defined in the file, are used to ensure uniqueness of the EDS file. The values of these objects do not reflect the actual controller revision level.
A generic EDS file for the M251 Logic Controller is also available on the Schneider
Electric website. You must adapt this file to your application by editing it and defining the required Assembly instances and sizes.
EIO0000003089.05
95
EthernetIP Slave I/O Mapping Tab
Variables can be defined and named in the EthernetIP Slave I/O Mapping tab.
Additional information such as topological addressing is also provided in this tab.
The table below describes the EthernetIP Slave I/O Mapping configuration:
Channel
Input IW0
IWxxx
Output
QW0
QWxxx
Type
WOR-
D
Default
Value
-
Description
Command word of controller outputs (%QW)
WOR-
D
State of controller inputs (%IW)
The number of words depends on the size parameter configured in
Target Configuration, page 94 .
Output means OUTPUT from Originator controller (= %IW for the controller).
Input means INPUT from Originator controller (= %QW for the controller).
Connections on EtherNet/IP
To access a target device, an Originator opens a connection which can include several sessions that send requests.
One explicit connection uses one session (a session is a TCP or UDP connection).
One I/O connection uses 2 sessions.
96 EIO0000003089.05
The following table shows the EtherNet/IP connections limitations:
Characteristic
Explicit connections
I/O connections
Connections
Sessions
Simultaneous requests
8
16
32
Maximum
8 (Class 3)
1 (Class 1)
NOTE: The M251 Logic Controller supports cyclic connections only. If an
Originator opens a connection using a change of state as a trigger, packets are sent at the RPI rate.
Profile
Object class
Message Router Object, page 100
TCP/IP Interface Object, page 104
Ethernet Link Object, page 105
Diagnostic List Object, page 111
04
06
F5
F6
350
351
352
353
354
The controller supports the following objects:
Class ID (hex)
01
02
Cat.
1
1
Number of Instances Effect on Interface Behavior
1 Supports the reset service
1 Explicit message connection
2
–
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
Defines I/O data format
–
TCP/IP configuration
Counter and status information
–
–
–
–
–
EIO0000003089.05
97
2
3
4
Identity Object (Class ID = 01 hex)
Attribute ID (hex)
1
6
7
Access
Get
Get
Get
Get
Get
Get
The following table describes the class attributes of the Identity Object:
Name Data Type Details
Revision UINT
Value
(hex)
01
Max Instances UINT
Number of Instances UINT
Optional Instance
Attribute List
UINT, UINT [ ]
Max Class Attribute
Max Instance
Attribute
UINT
UINT
01
01
00
07
07
Implementation revision of the Identity
Object
The largest instance number
The number of object instances
The first 2 bytes contain the number of optional instance attributes. Each following pair of bytes represents the number of other optional instance attributes.
The largest class attributes value
The largest instance attributes value
The following table describes the Class Services:
Name Description Service Code
(hex)
01
0E
Get Attribute All
Get Attribute Single
Returns the value of all class attributes
Returns the value of the specified attribute
The following table describes the Instance Services:
Name Description Service Code
(hex)
01
05
0E
Get Attribute All
Reset (1)
Get Attribute Single
Returns the value of all class attributes
Initializes EtherNet/IP component (controller reboot)
Returns the value of the specified attribute
(1) Reset Service description:
When the Identity Object receives a Reset request, it:
• determines whether it can provide the type of reset requested
• responds to the request
• attempts to perform the type of reset requested
NOTE: The reset command is rejected by the controller if an active EtherNet/
IP connection exists.
The Reset common service has one specific parameter, Type of Reset (USINT), with the following values:
Value
0
1
2
3...99
100...199
200...255
Type of Reset
Reboots the controller
NOTE: This is the default value if this parameter is omitted.
Not supported
Not supported
Reserved
Vendor specific
Reserved
98 EIO0000003089.05
5
6
7
3
4
1
2
Attribute ID
(hex)
Get
Get
Get
Access
Get
Get
Get
Get
The following table describes the Instance attributes:
Name Details
Vendor ID
Device type
Product code
Revision
Status
Serial number
Product name
Data Type
UINT
UINT
UINT
Struct of
USINT, USINT
Value
(hex)
F3
0E
1002
–
WORD
UDINT
Struct of
USINT,
STRING
–
–
–
Schneider Electric ID
Controller
Controller product code
Product revision number of the controller (1) .
Equivalent to the 2 low bytes of the controller version
Status word (2)
Serial number of the controller:
XX + 3 LSB of MAC address
–
(1) Mapped in a WORD:
• MSB: minor revision (second USINT)
• LSB: major revision (first USINT)
Example: 0205 hex means revision V5.2.
(2) Status word (Attribute 5):
Bit
0
1
2
3
4...7
8
9
10
11
12...-
15
Name
Owned
Reserved
Configured
Reserved
Extended
Device Status
Minor
Recoverable
Fault
Minor
Unrecoverable
Fault
Major
Recoverable
Fault
Major
Unrecoverable
Fault
Reserved
Description
Unused
–
TRUE indicates the device application has been reconfigured.
–
• 0: Self-testing or undetermined
• 1: Firmware update in progress
• 2: At least one invalid I/O connection detected
• 3: No I/O connections established
• 4: Non-volatile configuration invalid
• 5: Unrecoverable error detected
• 6: At least one I/O connection in RUNNING state
• 7: At least one I/O connection established, all in idle mode
• 8: Reserved
• 9...15: Unused
TRUE indicates the device detected an error, which, under most circumstances, is recoverable.
This type of event does not lead to a change in the device state.
TRUE indicates the device detected an error, which, under most circumstances, is unrecoverable.
This type of event does not lead to a change in the device state.
TRUE indicates the device detected an error, which requires the device to report an exception and enter into the HALT state.
This type of event leads to a change in the device state, but, under most circumstances, is recoverable.
TRUE indicates the device detected an error, which requires the device to report an exception and enter into the HALT state.
This type of event leads to a change in the device state, but, under most circumstances, is not recoverable.
–
EIO0000003089.05
99
Message Router Object (Class ID = 02 hex)
Attribute ID (hex)
1
2
3
4
5
6
7
Access
Get
Get
Get
Get
Get
Get
Get
The following table describes the class attributes of the Message Router object:
Name Data Type Details
Revision UINT
Value
(hex)
01
UINT 02
Implementation revision number of the Message
Router Object
The largest instance number Max
Instances
Number of
Instance
Optional
Instance
Attribute List
Optional
Service List
UINT 01
Struct of UINT,
UINT [ ]
02
UINT 0A
07
The number of object instances
The first 2 bytes contain the number of optional instance attributes. Each following pair of bytes represents the number of other optional instance attributes (from 100 to 119).
The number and list of any implemented optional services attribute (0: no optional services implemented)
The largest class attributes value Max Class
Attribute
Max Instance
Attribute
UINT
UINT 02 The largest instance attributes value
The following table describes the Class services:
Name Description Service Code
(hex)
01
0E
Get_Attribute_All
Get_Attribute_Single
Returns the value of all class attributes
Returns the value of the specified attribute
Attribute ID (hex)
1
Access
Get
2 Get
The following table describes the Instance services:
Name Description Service Code
(hex)
01
0E
Get_Attribute_All
Get_Attribute_Single
Returns the value of all class attributes
Returns the value of the specified attribute
The following table describes the Instance attributes:
Name
Implemented Object List
Data Type
Struct of UINT,
UINT [ ]
Value
–
Number available UINT 512
Description
Implemented Object list. The first 2 bytes contain the number of implemented objects. Each 2 bytes that follow represents another implemented class number.
This list contains the following objects:
• Identity
• Message Router
• Assembly
• Connection Manager
• Parameter
• File Object
• Modbus
• Port
• TCP/IP
• Ethernet Link
Maximum number of concurrent CIP
(Class 1 or Class 3) connections supported
100 EIO0000003089.05
Assembly Object (Class ID = 04 hex)
2
3
4
Attribute ID (hex)
1
5
6
7
Access
Get
Get
Get
Get
Get
Get
Get
The following table describes the class attributes of the Assembly object:
Name
Revision
Max Instances
Number of Instances
Optional Instance
Attribute List
Optional Service List
Max Class Attribute
Max Instance Attribute
Data Type
UINT
UINT
UINT
Struct of:
UINT
UINT [ ]
UINT
UINT
UINT
Value (hex) Details
02 Implementation revision of the Assembly
Object
BE
03
The largest instance number
The number of object instances
01
04
Not supported
07
04
The first 2 bytes contain the number of optional instance attributes. Each following pair of bytes represents the number of other optional instance attributes.
The number and list of any implemented optional services attribute (0: no optional services implemented)
The largest class attributes value
The largest instance attributes value
The following table describes the Class Services:
Name Description Service Code
(hex)
0E Get Attribute Single Returns the value of the specified attribute
The following table describes the Instance Services:
Name Description Service Code
(hex)
0E
10
Get Attribute Single
Set Attribute Single
Returns the value of the specified attribute
Modifies the value of the specified attribute
Instances Supported
Output means OUTPUT from Originator controller (= %IW for the controller).
Input means INPUT from Originator controller (= %QW for the controller).
The controller supports 2 Assemblies:
Name
Controller Output (%IW)
Controller Input (%QW)
Instance
Configurable: must be between 100 and
149
Configurable: must be between 150 and
189
Data Size
2...40 words
2...40 words
NOTE: The Assembly object binds together the attributes of multiple objects so that information to or from each object can be communicated over a single connection. Assembly objects are static.
The Assemblies in use can be modified through the parameter access of the network configuration tool (RSNetWorx). The controller needs to recycle power to register a new Assembly assignment.
EIO0000003089.05
101
The following table describes the Instance attributes:
Access Name Data Type Value Description Attribute ID
(hex)
3 Get/Set Instance Data
4 Get Instance Data Size
ARRAY of
Byte
UINT
– Data Set service only available for Controller output
4...80
Size of data in byte
Access from a EtherNet/IP Scanner
When a EtherNet/IP Scanner needs to exchange assemblies with a M251 Logic
Controller, it uses the following access parameters ( Connection path ):
• Class 4
• Instance xx where xx is the instance value (example: 2464 hex = instance
100).
• Attribute 3
In addition, a configuration assembly must be defined in the Originator.
For example: Class 4, Instance 3, Attribute 3, the resulting Connection Path will be:
• 2004 hex
• 2403 hex
• 2c<xx> hex
102 EIO0000003089.05
Connection Manager Object (Class ID = 06 hex)
Attribute ID (hex)
1
2
3
4
6
7
Access
Get
Get
Get
Get
Get
Get
The following table describes the class attributes of the Assembly Object:
Name Data Type Details
Revision UINT
Value
(hex)
01
Max Instances
Number of
Instances
Optional
Instance
Attribute List
UINT
UINT
Struct of:
UINT
UINT [ ]
01
01
–
Implementation revision of the Connection Manager
Object
The largest instance number
The number of object instances
UINT 07
The number and list of the optional attributes. The first word contains the number of attributes to follow and each following word contains another attribute code.
Following optional attributes include:
• total number of incoming connection open requests
• the number of requests rejected due to nonconforming format of the Forward Open
• the number of requests rejected because of insufficient resources
• the number of requests rejected due to parameter value sent with the Forward Open
• the number of Forward Close requests received
• the number of Forward Close requests with an invalid format
• the number of Forward Close requests that could not be matched to an active connection
• the number of connections that have timed out because the other side stopped producing, or a network disconnection occurred
The largest class attributes value Max Class
Attribute
Max Instance
Attribute
UINT 08 The largest instance attributes value
The following table describes the Class Services:
Name Description Service Code
(hex)
01
0E
Get Attribute All
Get Attribute Single
Returns the value of all class attributes
Returns the value of the specified attribute
The following table describes the Instance Services:
Name Description Service Code
(hex)
01
0E
4E
52
54
Get Attribute All
Get Attribute Single
Forward Close
Unconnected Send
Forward Open
Returns the value of all instance attributes
Returns the value of the specified attribute
Closes an existing connection
Sends a multi-hop unconnected request
Opens a new connection
EIO0000003089.05
103
4
5
6
7
Attribute ID (hex)
1
Access
Get
2 Get
3 Get
8
Get
Get
Get
Get
Get
The following table describes the Instance attributes:
Name
Open Requests
Open Format Rejects
Open Resource Rejects
Open Other Rejects
Close Requests
Close Format Requests
Close Other Requests
Connection Timeouts
Data Type
UINT
UINT
ARRAY of
Byte
UINT
UINT
UINT
UINT
UINT
Value
–
–
–
–
–
–
–
–
Description
Number of Forward Open service requests received
Number of Forward Open service requests which were rejected due to invalid format
Number of Forward Open service requests which were rejected due to lack of resources
Number of Forward Open service requests which were rejected for reasons other than invalid format or lack of resources
Number of Forward Close service requests received
Number of Forward Close service requests which were rejected due to invalid format
Number of Forward Close service requests which were rejected for reasons other than invalid format
Total number of connection timeouts that have occurred in connections controlled by this Connection Manager
TCP/IP Interface Object (Class ID = F5 hex)
Access
This object maintains link specific counters and status information for an Ethernet
802.3 communications interface.
The following table describes the class attributes of the TCP/IP Interface Object:
Name Data Type Value Details Attribute ID
(hex)
1 Get Revision UINT 4
2
3
Get
Get
Max Instances
Number of Instances
UINT
UINT
2
2
Implementation revision of the TCP/IP Interface
Object
The largest instance number
The number of object instances
The following table describes the Class Services:
Name Description Service Code
(hex)
01
0E
Get Attribute All
Get Attribute Single
Returns the value of all class attributes
Returns the value of the specified attribute
Instance Codes
Only instance 1 is supported.
The following table describes the Instance Services:
Service Code
(hex)
01
0E
Name
Get Attribute All
Get Attribute Single
Description
Returns the value of all instance attributes
Returns the value of the specified instance attribute
104 EIO0000003089.05
Attribute ID
(hex)
1
2
3
4
5
6
Access
The following table describes the Instance Attributes:
Name Data Type Value Description
Get Status DWORD Bit level
Get
Get
Get
Get
Get
Configuration
Capability
Configuration
Physical Link
Interface configuration
Host Name
DWORD
DWORD
UINT
Padded
EPATH
UDINT
UDINT
UDINT
UDINT
UDINT
STRING
STRING
Bit level
Bit level
Path size
Path
IP Address
Network
Mask
Gateway
Address
Primary
Name
Secondary
Name
Default
Domain
Name
–
–
–
• 0: The interface configuration attribute has not been configured.
• 1: The interface configuration contains a valid configuration.
• 2...15: Reserved.
• 0: BOOTP Client
• 1: DNS Client
• 2: DHCP Client
• 5: Configured in EcoStruxure Machine
Expert
All other bits are reserved and set to 0.
• 0: The interface configuration is valid.
• 1: The interface configuration is obtained with BOOTP.
• 2: The interface configuration is obtained with DHCP.
• 3: reserved
• 4: DNS Enable
All other bits are reserved and set to 0.
Number of 16 bits word in the element Path
Logical segments identifying the physical link object. The path is restricted to one logical class segment and one logical instance segment. The maximum size is 12 bytes.
–
–
0: no secondary name server address has been configured.
0: no Domain Name is configured
ASCII characters.
0: no host name is configured
Ethernet Link Object (Class ID = F6 hex)
2
3
Attribute ID
(hex)
1
Access
Get
Get
Get
This object provides the mechanism to configure a TCP/IP network interface device.
The following table describes the class attributes of the Ethernet Link object:
Name Data Type Details
Revision UINT
Value
(hex)
4
Max Instances
Number of Instances
UINT
UINT
3
3
Implementation revision of the Ethernet Link
Object
The largest instance number
The number of object instances
EIO0000003089.05
105
1
2
Attribute ID
(hex)
3
The following table describes the class services:
Name Description Service Code
(hex)
01
0E
Get Attribute All
Get Attribute Single
Returns the value of all class attributes
Returns the value of the specified attribute
Instance Codes
Only instance 1 is supported.
The following table describes the instance services:
Name Description Service Code
(hex)
01
0E
Get Attribute All
Get Attribute Single
Returns the value of all instance attributes
Returns the value of the specified instance attribute
Access
Get
Get
Get
The following table describes the instance attributes:
Name Data Type Value Description
Interface Speed
Interface Flags
Physical Address
UDINT
DWORD
ARRAY of 6
USINT
–
–
Bit level
Speed in Mbit/s (10 or 100)
• 0: link status
• 1: half/full duplex
• 2...4: negotiation status
• 5: manual setting / requires reset
• 6: local hardware error detected
All other bits are reserved and set to 0.
This array contains the MAC address of the product.
Format: XX-XX-XX-XX-XX-XX
EtherNet/IP Interface Diagnostic Object (Class ID = 350 hex)
1
2
Attribute ID
(hex)
Access
Get
Get
The following table describes the class attributes of the EtherNet/IP Interface
Diagnostic object:
Name Data Type Details
Revision
Max Instance
UINT
UINT
Value
(hex)
01
01
Increased by 1 on each new update of the object
Maximum instance number of the object
106 EIO0000003089.05
Attribute ID
(hex)
1
Access
Get
2
3
4
Get
Get Clear
Get Clear
The following table describes the instance attributes of the EtherNet/IP Interface
Diagnostic object:
Name Data Type Details
Protocols supported
UINT Protocol(s) supported (0=not supported, 1=supported):
• Bit 0: EtherNet/IP
• Bit 1: Modbus TCP
• Bit 2: Modbus Serial
• Bits 3...15: Reserved, 0
Connection Diag
Max CIP IO
Connections opened
Current CIP IO
Connections
Max CIP Explicit
Connections opened
Current CIP
Explicit
Connections
CIP Connections
Opening Errors
CIP Connections
Timeout Errors
Max EIP TCP
Connections opened
Current EIP TCP
Connections
IO Messaging
Diag
IO Production
Counter
IO Consumption
Counter
IO Production
Send Errors
Counter
IO Consumption
Receive Errors
Counter
Explicit
Messaging Diag
Class3 Msg Send
Counter
Class3 Msg
Receive Counter
UCMM Msg Send
Counter
UCMM Msg
Receive Counter
STRUCT of
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
STRUCT of
UDINT
UDINT
UINT
UINT
STRUCT of
UDINT
UDINT
UDINT
UDINT
Maximum number of CIP I/O connections opened.
Number of CIP I/O connections currently opened.
Maximum number of CIP explicit connections opened.
Number of CIP explicit connections currently opened
Incremented on each unsuccessful attempt to open a CIP connection.
Incremented when a CIP connection times out.
Maximum number of TCP connections opened and used for
EtherNet/IP communications.
Number of TCP connections currently open and being used for
EtherNet/IP communications.
Incremented each time a Class 0/1 CIP message is sent.
Incremented each time a Class 0/1 CIP message is received.
Incremented each Time a Class 0/1 message is not sent.
Incremented each time a consumption is received that contains an error.
Incremented each time a Class 3 CIP message is sent.
Incremented each time a Class 3 CIP message is received.
Incremented each time a UCMM message is sent.
Incremented each time a UCMM message is received.
EIO0000003089.05
107
Attribute ID
(hex)
5
Access
Get
6
7
Get
Get
Name Data Type
Com Capacity
Max CIP
Connections
Max TCP
Connections
Max Urgent priority rate
Max Scheduled priority rate
Max High priority rate
STRUCT of
UINT
UINT
UINT
UINT
UINT
Max Low priority rate
Max Explicit
Messaging rate
Bandwidth Diag
Current sending
Urgent priority rate
Current reception
Urgent priority rate
Current sending
Scheduled priority rate
Current reception
Scheduled priority rate
Current sending
High priority rate
Current reception
High priority rate
Current sending
Low priority rate
Current reception
Low priority rate
UINT
UINT
STRUCT of
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
Current sending
Explicit
Messaging rate
Current reception
Explicit
Messaging rate
Modbus Diag
Max. Modbus
TCP Connections opened
Current Modbus
TCP Connections
Modbus TCP Msg
Send Counter
Modbus TCP Msg
Receive Counter
UINT
UINT
STRUCT of
UINT
UINT
UDINT
UDINT
Details
Maximum number of supported CIP connections.
Maximum number of supported TCP connections.
Maximum number of CIP transport class 0/1 Urgent priority message packets per second.
Maximum number of CIP transport class 0/1 Scheduled priority message packets per second.
Maximum number of CIP transport class 0/1 High priority message packets per second.
Maximum number of CIP transport class 0/1 Low priority message packets per second.
Max CIP transport class 2/3 or other EtherNet/IP messages packets per second
CIP transport class 0/1 Urgent priority message packets sent per second.
CIP transport class 0/1 Urgent priority message packets received per second.
CIP transport class 0/1 Scheduled priority message packets sent per second.
CIP transport class 0/1 Scheduled priority message packets received per second.
CIP transport class 0/1 High priority message packets sent per second.
CIP transport class 0/1 High priority message packets received per second.
CIP transport class 0/1 Low priority message packets sent per second.
CIP transport class 0/1 Low priority message packets received per second.
CIP transport class 2/3 or other EtherNet/IP message packets sent per second.
CIP transport class 2/3 or other EtherNet/IP message packets received per second.
Maximum number of TCP connections opened and used for
Modbus communications.
Number of TCP connections currently opened and used for
Modbus communications.
Incremented each time a Modbus TCP message is sent.
Incremented each time a Modbus TCP message is received.
108 EIO0000003089.05
The following table describes the class services:
Name Description Service Code
(hex)
01
0E
4C
Get_Attributes_All Returns the value of all class attributes.
Get_Attribute_Single Returns the value of a specified attribute.
Get_and_Clear Gets and clears a specified attribute.
IOScanner Diagnostic Object (Class ID = 351 hex)
Attribute ID (hex) Access
1
2
Get
Get
The following table describes the class attributes of the IOScanner Diagnostic object:
Name Data Type Details
Revision UINT
Value
(hex)
1
Max Instance UINT 1
Increased by 1 on each new update of the object.
Maximum instance number of the object.
Attribute ID (hex) Access
1 Get
The following table describes the instance attributes of the IOScanner Diagnostic object:
Name
IO Status Table
Size
Status
Data Type Details
STRUCT of
UINT Size in bytes of the Status attribute.
ARRAY of UINT I/O status. Bit n, where n is instance n of the object, provides the status of the I/O exchanged on the I/O connection:
• 0: The input or output status of the I/O connection is in error, or no device.
• 1: The input or output status of the I/O connection is correct.
The following table describes the class services:
Name Description Service Code
(hex)
01 Get_Attributes_All Returns the value of all class attributes.
IO Connection Diagnostic Object (Class ID = 352 hex)
Attribute ID (hex) Access
1
2
Get
Get
The following table describes the class attributes of the IO Connection Diagnostic object:
Name Data Type Details
Revision UINT
Value
(hex)
01
Max Instance UINT 01
Increased by 1 on each new update of the object.
Maximum instance number of the object
0...n
where n is the maximum number of CIP I/O connections.
NOTE: There is an IO Connection
Diagnostic object instance for both O->T and T->O paths.
EIO0000003089.05
109
Attribute ID (hex) Access
1 Get Clear
2 Get
The following table describes the instance attributes of the I/O Connection
Diagnostic object:
Name
IO Com Diag
Data Type Details
STRUCT of
IO Production Counter UDINT
UDINT IO Consumption
Counter
IO Production Send
Errors Counter
IO Consumption
Receive Errors
Counter
CIP Connection
TimeOut Errors
CIP Connection
Opening Errors
UINT
UINT
UINT
UINT
CIP Connection State
CIP Last Error General
Status
CIP Last Error
Extended Status
Input Com Status
UINT
UINT
UINT
UINT
UINT Output Com Status
Connection Diag STRUCT of
Incremented each time a production is sent.
Incremented each time a consumption is received.
Incremented each time a production is not sent due to an error.
Incremented each time a consumption is received that contains an error.
Incremented each time a connection times out.
Incremented on each unsuccessful attempt to open a connection.
State of the CIP IO connection.
General status of the last error detected on the connection.
Extended status of the last error detected on the connection.
Communication status of the inputs.
Communication status of the outputs.
Connection ID for production.
Production Connection
ID
Consumption
Connection ID
Production RPI
Production API
UDINT
UDINT
UDINT
UDINT
Consumption RPI
Consumption API
Production Connection
Parameters
Consumption
Connection
Parameters
Local IP
Local UDP Port
UDINT
UDINT
UDINT
UDINT
UDINT
UINT
Remote IP
Remote UDP Port
UDINT
UINT
Production Multicast IP UDINT
Consumption Multicast
IP
Protocols supported
UDINT
UINT
Connection ID for consumption.
Requested Packet Interval (RPI) for productions, in μs.
Actual Packet Interval (API) for productions.
RPI for consumptions.
API for consumptions.
Connection parameters for productions.
Connection parameters for consumptions.
Local IP address for I/O communication.
Local UDP port number for I/O communication.
Remote IP address for I/O communication.
Remote UDP port number for I/O communication.
Multicast IP address for productions, or 0 if multicast is not used.
Multicast IP address for consumptions, or 0 if multicast is not used.
Protocol(s) supported (0=not supported, 1=supported):
• Bit 0: EtherNet/IP
• Bit 1: Modbus TCP
• Bit 2: Modbus Serial
• Bits 3...15: Reserved, 0
110 EIO0000003089.05
Instance Attributes
The following table describes the class services:
Name Description Service Code
(hex)
01
0E
4C
Get_Attributes_All Returns the value of all class attributes.
Get_Attribute_Single Returns the value of the specified attribute.
Get_and_Clear Gets and clears a specified attribute.
4
5
6
7
8
2
3
Attribute ID
(hex)
1
Explicit Connection Diagnostic Object (Class ID = 353 hex)
Attribute ID (hex)
1
2
Access
Get
Get
The following table describes the class attributes of the Explicit Connection
Diagnostic object:
Name
Revision
Max Instance
Data Type
UINT
UINT
Value
(hex)
01
Details
0...n
(maximum number of
CIP IO connections)
Increased by 1 at each new update of the object.
Maximum instance number of the object.
Access
The following table describes the instance attributes of the Explicit Connection
Diagnostic object:
Name Data Type Details
Get
Get
Get
Get
Get
Get
Get
Get
Originator
Connection ID
Originator IP
UDINT
UDINT
UINT Originator TCP
Port
Target Connection
ID
Target IP
UDINT
UDINT
UINT Target TCP Port
Msg Send Counter UDINT
Msg
ReceiveCounter
UDINT
O to T Connection ID
T to O Connection ID
Incremented each time a Class 3 CIP Message is sent on the connection
Incremented each time a Class 3 CIP Message is received on the connection
Explicit Connections Diagnostic List Object (Class ID = 354 hex)
Attribute ID (hex) Access
1
2
Get
Get
The following table describes the class attributes of the Explicit Connections
Diagnostic List object:
Name Data Type Details
Revision
Max Instance
UINT
UINT
Value
(hex)
01
0...n
Increased by 1 at each new update of the object.
n is the maximum number of concurrent list accesses supported.
EIO0000003089.05
111
Attribute ID (hex) Access
1 Get
2 Get
The following table describes the instance attributes of the Explicit Connections
Diagnostic List object:
Name
Number of Connections
Explicit Messaging
Connections Diagnostic List
Originator Connection ID
Originator IP
Originator TCP Port
Target Connection ID
Target IP
Target TCP Port
Msg Send Counter
Msg Receive Counter
Data Type
UINT
ARRAY of
STRUCT
UDINT
UDINT
UINT
UDINT
UDINT
UINT
UDINT
UDINT
Details
Total number of open Explicit connections
Contents of instantiated Explicit Connection
Diagnostic objects
Originator to Target connection ID
Originator to Target IP address
Originator to Target port number
Target to Originator connection ID
Target to Originator IP address
Target to Originator port number
Incremented each time a Class 3 CIP message is sent on the connection
Incremented each time a Class 3 CIP message is sent on the connection
The following table describes the class services:
Name Description Service Code
(hex)
08 Create
09
33
Delete
Creates an instance of the Explicit Connections
Diagnostic List object.
Deletes an instance of the Explicit Connections
Diagnostic List object.
Explicit corrections diagnostic read object.
Explicit_
Connections_
Diagnostic_Read
Controller as a Slave Device on Modbus TCP
Overview
This section describes the configuration of the M251 Logic Controller as a
Modbus TCP Slave Device .
The Modbus TCP Slave Device adds another Modbus server function to the controller. This server is addressed by the Modbus client application by specifying a configured Unit ID (Modbus address) in the range 1...247. The embedded
Modbus server of the slave controller needs no configuration, and is addressed by specifying a Unit ID equal to 255. Refer to
Modbus TCP Configuration, page 113
.
To configure your M251 Logic Controller as a Modbus TCP Slave Device , you must add Modbus TCP Slave Device functionality to your controller (see Adding a Modbus TCP Slave Device thereafter). This functionality creates a specific I/O area in the controller that is accessible with the Modbus TCP protocol. This I/O area is used whenever an external master needs to access the %IW and %QW objects of the controller. This Modbus TCP Slave Device functionality allows you to furnish to this area the controller I/O objects which can then be accessed with a single Modbus read/write registers request.
Only one Modbus TCP Slave Device at a time can be configured on one of the
Ethernet ports of the M251 Logic Controller ( Ethernet_1 or Ethernet_2 ). Once configured, however, the Modbus TCP slave device can be addressed through both Ethernet ports.
Inputs/outputs are seen from the slave controller: inputs are written by the master, and outputs are read by the master.
112 EIO0000003089.05
The Modbus TCP Slave Device can define a privileged Modbus client application, whose connection is not forcefully closed (embedded Modbus connections may be closed when more than 8 connections are needed).
The watchdog associated to the privileged connection allows you to verify whether the controller is being polled by the privileged master. If no Modbus request is received within the timeout duration, the diagnostic information i_byMasterIpLost is set to 1 (TRUE). For more information, refer to the Ethernet Port Read-Only
System Variables (see Modicon M251 Logic Controller, System Functions and
Variables, PLCSystem Library Guide).
For further information about Modbus TCP, refer to the www.odva.org
website.
Adding a Modbus TCP Slave Device
To configure your M251 Logic Controller as a Modbus TCP slave device, you must:
Step
1
2
Action
Select Modbus TCP Slave Device in the Hardware Catalog .
Drag and drop it to the Devices tree on one of the highlighted nodes.
For more information on adding a device to your project, refer to:
• Using the Hardware Catalog
• Using the Contextual Menu or Plus Button
Modbus TCP Configuration
To configure the Modbus TCP slave device, double-click Ethernet_x >
ModbusTCP_Slave_Device in the Devices tree .
This dialog box appears:
EIO0000003089.05
113
Element
IP Master Address
Watchdog
Slave Port
Unit ID
Holding Registers (%
IW)
Input Registers (%
QW)
Description
IP address of the Modbus master
The connections are not closed on this address.
Watchdog in 500 ms increments
NOTE: The watchdog applies to the IP master Address unless the address is 0.0.0.0.
Modbus communication port (502)
NOTE: The port number can be modified using the
changeModbusPort script command, page 116
.
Sends the requests to the Modbus TCP slave device (1...247), instead of to the embedded Modbus server (255).
Number of %IW registers to be used in the exchange (2...120) (each register is 2 bytes)
Number of %QW registers to be used in the exchange (2...120) (each register is 2 bytes)
Modbus TCP Slave Device I/O Mapping Tab
The I/Os are mapped to Modbus registers from the master perspective as follows:
• %IWs are mapped from register 0 to n-1 and are R/W (n = Holding register quantity, each %IW register is 2 bytes).
• %QWs are mapped from register n to n+m -1 and are read only (m = Input registers quantity, each %QW register is 2 bytes).
Once a Modbus TCP Slave Device has been configured, Modbus commands sent to its Unit ID (Modbus address) are handled differently than the same command would be when addressed to any other Modbus device on the network.
For example, when the Modbus command 3 (3 hex) is sent to a standard Modbus device, it reads and returns the value of one or more registers. When this same command is sent to the
Slave, it facilitates a read operation by the external I/O scanner.
Once a Modbus TCP Slave Device has been configured, Modbus commands sent to its Unit ID (Modbus address) access the %IW and %QW objects of the controller instead of the regular Modbus words (accessed when the Unit ID is
255). This facilitates read/write operations by a Modbus TCP IOScanner application.
The Modbus TCP Slave Device responds to a subset of the Modbus commands with the purpose of exchanging data with the external I/O scanner. The following
Modbus commands are supported by the Modbus TCP slave device:
Function
Code Dec
(Hex)
3 (3)
Function Comment
6 (6)
16 (10)
23 (17)
Other
Read holding register Allows the master to read %IW and %QW objects of the device
Write single register Allows the master to write %IW objects of the device
Allows the master to write %IW objects of the device Write multiple registers
Read/write multiple registers
Not supported
Allows the master to read %IW and %QW objects of the device and write %IW objects of the device
–
NOTE: Modbus requests that attempt to access registers above n+m-1 are answered by the 02 - ILLEGAL DATA ADDRESS exception code.
114 EIO0000003089.05
To link I/O objects to variables, select the Modbus TCP Slave Device I/O
Mapping tab:
Channel
Input
Output
IW0
...
IWx
QW0
...
QWy
Type Description
WORD Holding register 0
...
...
WORD Holding register x
WORD Input register 0
...
...
WORD Input register y
The number of words depends on the Holding Registers (%IW) and Input
Registers (%QW) parameters of the Modbus TCP tab.
NOTE: Output means OUTPUT from Originator controller (= %IW for the controller). Input means INPUT from Originator controller (= %QW for the controller).
NOTE: The Modbus TCP Slave Device refreshes the %IW and %QW registers as a single time-consistent unit, synchronized with the IEC tasks (MAST task by default). By contrast, the embedded Modbus TCP server only ensures time-consistency for 1 word (2 bytes). If your application requires timeconsistency for more than 1 word (2 bytes), use the Modbus TCP Slave
Device .
The parameter Always update variables is set to Enabled 1 (use bus cycle task if not used in any task) and is not editable.
Bus Cycle Options
In the Modbus TCP Slave Device I/O Mapping tab, select the Bus cycle task to use:
• Use parent bus cycle setting (the default),
• MAST
• An existing task of the project : you can select an existing task and associate it to the scanner. For more information about the application tasks, refer to the EcoStruxure Machine Expert Programming Guide.
NOTE: There is a corresponding Bus cycle task parameter in the I/O mapping editor of the device that contains the Modbus TCP Slave Device .
This parameter defines the task responsible for refreshing the %IW and %QW registers.
EIO0000003089.05
115
Changing the Modbus TCP Port changeModbusPort Command
The changeModbusPort command can be used to change the port used for data exchanges with a Modbus TCP master.
The current Modbus Slave Port is displayed on the
Modbus TCP configuration window, page 113 .
The default Modbus port number is 502.
Command changeModbusPort “portnum”
Description portnum is the new Modbus port number to use and is passed as a string of characters.
Before running the command, refer to
to ensure that portnum is not being used by any other TCP/UDP protocols or processes.
An error is logged in the /usr/Syslog/FWLog.txt
file if the specified port number is already in use.
To limit the number of open sockets, the changeModbusPort command can only be run twice.
A power cycle of the logic controller returns the Modbus port number to the default value (502). The changeModbusPort command must therefore be executed after each power cycle.
NOTE: After changing the port number, protocol active selection for the
Modbus Server in the Security Parameters group on the
is no longer valid.
Running the Command from an SD Card Script
2
3
4
Step
1
Action
Create a
, for example:
; Change Modbus slave port changeModbusPort “1502”;
Name the script file Script.cmd
.
Copy the script file to the SD card.
Insert the SD card in the controller.
Running the Command Using ExecuteScript Function Block
The changeModbusPort command can be run from within an application using the
ExecuteScript function block (see Modicon M251 Logic Controller, System
Functions and Variables, PLCSystem Library Guide).
116 EIO0000003089.05
The following sample code changes the Modbus TCP slave port from the default
(502) to 1502.
IF (myBExe = FALSE AND (PortNum <> 502)) THEN myExecSc( // falling edge for a second change xExecute:=FALSE , sCmd:=myCmd , xDone=>myBDone , xBusy=> myBBusy, xError=> myBErr, eError=> myIerr); string1 := 'changeModbusPort "'; string2 := WORD_TO_STRING(PortNum); myCmd := concat(string1,string2); myCmd := concat(myCmd,'"'); myBExe := TRUE;
END_IF myExecSc( xExecute:=myBExe , sCmd:=myCmd , xDone=>myBDone , xBusy=> myBBusy, xError=> myBErr, eError=> myIerr);
Firewall Configuration
Introduction
This section describes how to configure the firewall of the Modicon M251 Logic
Controller.
Introduction
Firewall Presentation
In general, firewalls help protect network security zone perimeters by blocking unauthorized access and permitting authorized access. A firewall is a device or set of devices configured to permit, deny, encrypt, decrypt, or proxy traffic between different security zones based upon a set of rules and other criteria.
Process control devices and high-speed manufacturing machines require fast data throughput and often cannot tolerate the latency introduced by an aggressive security strategy inside the control network. Firewalls, therefore, play a significant role in a security strategy by providing levels of protection at the perimeters of the network. Firewalls are an important part of an overall, system level strategy. By default, firewall rules do not allow the transfer of incoming IP telegrams from a controller network to a fieldbus network.
NOTE: Schneider Electric adheres to industry best practices in the development and implementation of control systems. This includes a
"Defense-in-Depth" approach to secure an Industrial Control System. This approach places the controllers behind one or more firewalls to restrict access to authorized personnel and protocols only.
EIO0000003089.05
117
WARNING
UNAUTHENTICATED ACCESS AND SUBSEQUENT UNAUTHORIZED
MACHINE OPERATION
• Evaluate whether your environment or your machines are connected to your critical infrastructure and, if so, take appropriate steps in terms of prevention, based on Defense-in-Depth, before connecting the automation system to any network.
• Limit the number of devices connected to a network to the minimum necessary.
• Isolate your industrial network from other networks inside your company.
• Protect any network against unintended access by using firewalls, VPN, or other, proven security measures.
• Monitor activities within your systems.
• Prevent subject devices from direct access or direct link by unauthorized parties or unauthenticated actions.
• Prepare a recovery plan including backup of your system and process information.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Firewall Configuration
There are three ways to manage the controller firewall configuration:
• Static configuration
• Dynamic changes
• Application settings
Script files are used in the static configuration and for dynamic changes.
Static Configuration
The static configuration is loaded at the controller boot.
The controller firewall can be statically configured by managing a default script file located in the controller. The path to this file is /usr/Cfg/FirewallDefault.cmd
.
Dynamic Changes
After the controller boot, the controller firewall configuration can be changed by the use of script files.
There are two ways to load these dynamic changes using:
• A physical
• A
in the application.
118 EIO0000003089.05
Dynamic Changes Procedure
Using an SD Card
This table describes the procedure to execute a script file from an SD card:
Step
1
2
3
4
Action
Create a valid
For example, name the script file FirewallMaintenance.cmd
.
Load the script file on the SD card.
For example, load the script file in the usr/Cfg folder.
In the file Sys/Cmd/Script.cmd
, add a code line with the command
Firewall_install ”/pathname/FileName”
For example, the code line is
Firewall_install ”/sd0/usr/Cfg/FirewallMaintenance.cmd”
Insert the SD card on the controller.
Using a Function Block in the Application
This table describes the procedure to execute a script file from an application:
Step
1
2
3
Action
Create a valid
For example, name the script file FirewallMaintenance.cmd
.
Load the script file in the controller memory.
For example, load the script file in the usr/Syslog folder with FTP.
Use an ExecuteScript (see Modicon M251 Logic Controller, System Functions and
Variables, PLCSystem Library Guide) function block.
For example, the [SCmd] input is ‘Firewall_install “/usr/Syslog/
FirewallMaintenance.cmd”’
Firewall Behavior
Introduction
The firewall configuration depends on the action done on the controller and the initial configuration state. There are five possible initial states:
• There is no default script file in the controller.
• A correct script file is present.
• An incorrect script file is present.
• There is no default script file and the application has configured the firewall.
• A dynamic script file configuration has already been executed.
EIO0000003089.05
119
No Default Script File
If...
Boot of the controller
Execute dynamic script file
Execute dynamic incorrect script file
Download application
Then ...
Firewall is not configured. No protection is activated.
Firewall is configured according to the dynamic script file.
Firewall is not configured. No protection is activated.
Firewall is configured according to the application settings.
Default Script File Present
If...
Boot of the controller
Execute dynamic script file
Execute dynamic incorrect script file
Download application
Then ...
Firewall is configured according to the default script file.
The whole configuration of the default script file is deleted.
Firewall is configured according to the dynamic script file.
Firewall is configured according to the default script file.
The dynamic script file is not taken into account.
The whole configuration of the application is ignored.
Firewall is configured according to the default script file.
Incorrect Default Script File Present
If...
Boot of the controller
Execute dynamic script file
Execute dynamic incorrect script file
Download application
Then ...
Firewall is not configured. No protection is activated
Firewall is configured according to the dynamic script file.
Firewall is not configured. No protection is activated.
Firewall is configured according to the application settings.
Application Settings with No Default Script File
If...
Boot of the controller
Execute dynamic script file
Then ...
Firewall is configured according to the application settings.
The whole configuration of the application settings is deleted.
Firewall is configured according to the dynamic script file.
Execute dynamic incorrect script file Firewall is configured according to the application settings. The dynamic script file is not taken into account.
Download application The whole configuration of the previous application is deleted.
Firewall is configured according to the new application settings.
120 EIO0000003089.05
Execute Dynamic Script File Already Executed
If...
Boot of the controller
Execute dynamic script file
Then ...
Firewall is configured according to the dynamic script file configuration (see note).
The whole configuration of the previous dynamic script file is deleted.
Firewall is configured according to the new dynamic script file.
Execute dynamic incorrect script file Firewall is configured according to the previous dynamic script file configuration. The dynamic incorrect script file is not taken into account.
Download application The whole configuration of the application is ignored
Firewall is configured according to the dynamic script file.
NOTE: If an SD card containing a cybersecurity script is inserted into the controller, booting is blocked. First remove the SD card to correctly boot the controller.
Firewall Script Commands
Overview
This section describes how script files (default script files or dynamic script files) are written so that they can be executed during the booting of the controller or during a specific command triggered.
NOTE: The MAC layer rules are managed separately and have more priority over other packet filter rules.
Script File Syntax
The syntax of script files is described in
Script Syntax Guidelines, page 167
.
General Firewall Commands
Command
Firewall Enable
Firewall Disable
Firewall Ethx Default Allow
(1)
Firewall Ethx Default Reject
(1)
The following commands are available to manage the Ethernet firewall of the
M251 Logic Controller:
Description
Blocks the frames from the Ethernet interfaces. If no specific IP address is authorized, it is not possible to communicate on the Ethernet interfaces.
NOTE: By default, when the firewall is enabled, the frames are rejected.
Firewall rules are not applied. Frames are not blocked
Frames are accepted by the controller.
Frames are rejected by the controller.
NOTE: By default, if this line is not present, it corresponds to the command
Firewall Eth1 Default Reject .
(1) Where Ethx =
For TM251MESC:
• Eth1: Ethernet_1
For TM251MESE:
• Eth1: Ethernet_1
• Eth2: Ethernet_2
EIO0000003089.05
121
Specific Firewall Commands
Command
Firewall Eth1 Allow
IP •.•.•.•
Firewall Eth1
Reject IP •.•.•.•
Firewall Eth1 Allow
IPs •.•.•.• to •.•.
•.•
Firewall Eth1
Reject IPs •.•.•.• to •.•.•.•
Firewall Eth1 Allow port_type port Y
Firewall Eth1
Reject port_type port Y
Range
• = 0...255
The following commands are available to configure firewall rules for specific ports and addresses:
• = 0...255
• = 0...255
• = 0...255
Y = ( destination port numbers, page 124 )
Y = ( destination port numbers, page 124 )
Description
Frames from the specified IP address are allowed on all port numbers and port types.
Frames from the specified IP address are rejected on all port numbers and port types.
Frames from the IP addresses in the specified range are allowed for all port numbers and port types.
Frames from the IP addresses in the specified range are rejected for all port numbers and port types.
Frames with the specified destination port number are allowed.
Frames with the specified destination port number are rejected.
NOTE: When IP forwarding is activated, rules with reject port only filter frames with current controller as destination. They are not applied for the frames routed by the current controller.
Frames with a destination port number in the specified range are allowed.
Firewall Eth1 Allow port_type ports Y1 to Y2
Firewall Eth1
Reject port_type ports Y1 to Y2
Firewall Eth1 Allow
IP •.•.•.• on port_ type port Y
Y = ( destination port destination port numbers, page 124
Firewall Eth1
Reject IP •.•.•.• on port_type port Y
Firewall Eth1 Allow
IP •.•.•.• on port_ type ports Y1 to Y2
Firewall Eth1
Reject IP •.•.•.• on port_type ports Y1 to Y2
Firewall Eth1 Allow
IPs •1.•1.•1.•1 to
•2.•2.•2.•2 on port_type port Y
Firewall Eth1
Reject IPs •1.•1.
•1.•1 to •2.•2.•2.
•2 on port_type port
Y
Firewall Eth1 Allow
IPs •1.•1.•1.•1 to
•2.•2.•2.•2 on port_type ports Y1 to Y2
Firewall Eth1
Reject IPs •1.•1.
•1.•1 to •2.•2.•2.
•2 on port_type ports Y1 to Y2
• = 0...255
Y = ( destination port numbers, page 124 )
• = 0...255
Y = ( destination port numbers, page 124 )
• = 0...255
Y = ( destination port numbers, page 124 )
• = 0...255
Y = ( destination port numbers, page 124 )
• = 0...255
Y = ( destination port numbers, page 124 )
• = 0...255
Y = ( destination port numbers, page 124 )
• = 0...255
Y = ( destination port numbers, page 124 )
• = 0...255
Y = ( destination port numbers, page 124 )
Frames with a destination port number in the specified range are rejected.
Frames from the specified IP address and with the specified destination port number are allowed.
Frames from the specified IP address and with the specified destination port number are rejected.
Frames from the specified IP address and with a destination port number in the specified range are allowed.
Frames from the specified IP address and with a destination port number in the specified range are rejected.
Frames from an IP address in the specified range and with the specified destination port number are allowed.
Frames from an IP address in the specified range and with the specified destination port number are rejected.
Frames from an IP address in the specified range and with a destination port number in the specified range are allowed.
Frames from an IP address in the specified range and with a destination port number in the specified range are rejected.
122 EIO0000003089.05
Command
Firewall Eth1 Allow
MAC ••:••:••:••:••:
••
Range
• = 0...F
Firewall Eth1
Reject MAC ••:••:
••:••:••:••
• = 0...F
Description
Frames from the specified MAC address ••:••:••:••:•• are allowed.
NOTE: When the rules to allow the MAC address are applied, only the listed MAC addresses can communicate with the controller, even if other rules are allowed.
Frames with the specified MAC address ••:••:••:••:•• are rejected.
NOTE: The port_type can be TCP or UDP.
Script Example
; Enable FireWall. All frames are rejected;
FireWall Enable;
; Allow frames on Eth1
FireWall Eth1 Default Allow;
; Block all Modbus Requests on all IP address
Firewall Eth1 Reject tcp port 502;
; Reject frames on Eth2
FireWall Eth2 Default Reject;
; Allow FTP active connection for IP address 85.16.0.17
FireWall Eth2 Allow IP 85.16.0.17 on tcp ports 20 to 21;
NOTE: IP addresses are converted to CIDR format.
For example:
“FireWall Eth2 Allow IPs 192.168.100.66 to 192.168.100.99 on tcp port 44818;” , is separated into 7:
• 192.168.100.66/31
• 192.168.100.68/30
• 192.168.100.72/29
• 192.168.100.80/28
• 192.168.100.96/27
• 192.168.100.128/26
• 192.168.100.192/29
To prevent a firewall error, use the entire subnet configuration.
NOTE: Characters are limited to 200 per line, including comments.
EIO0000003089.05
123
Ports Used
Protocol
Machine Expert
FTP
HTTP / HTTPS
Destination Port Numbers
UDP 1740, 1741, 1742, 1743
TCP 1105
TCP 21
TCP 80, 443 (Web server)
TCP 8080 (Web visualization)
Modbus
OPC UA
Machine Expert Discovery
TCP 502 (1)
TCP 4840
UDP 27126, 27127
SNMP
NVL
EtherNet/IP
UDP 161, 162
UDP Default value: 1202
UDP 2222
TCP 44818
UDP 69 (used for FDR server only) TFTP
(1) The default value can be changed using the change
ModbusPort command, page 116 .
124 EIO0000003089.05
Industrial Ethernet Manager
Introduction
This chapter describes how to add and configure the Industrial Ethernet.
Industrial Ethernet
Overview
Industrial Ethernet is the term used to represent the industrial protocols that use the standard Ethernet physical layer and standard Ethernet protocols.
NOTE: The following information only applies to the TM251MESE controller.
On an Industrial Ethernet network, you can connect:
• industrial devices.(industrial protocols)
• non-industrial devices (other Ethernet protocols)
For more information, refer to Industrial Ethernet User Guide (see EcoStruxure
Machine Expert Industrial Ethernet Overview, User Guide).
Industrial Ethernet Architecture
This figure presents a typical Industrial Ethernet architecture:
EIO0000003089.05
A
B
1
2
3
4
5
6
2, 4, and 5
Control network
Device network
Logic controller (see EcoStruxure Machine Expert Industrial Ethernet
Overview, User Guide)
Daisy-chained devices
Ethernet switch
I/O island (Modbus TCP)
Vision sensor (EtherNet/IP)
PC and HMI (TCP/UDP)
Industrial Ethernet slave devices (EtherNet/IP / Modbus TCP)
125
This architecture is configurable with EcoStruxure Machine Expert.
Industrial Ethernet Description
TM251MESE logic controller
Features Description
Topology
Bandwidth
EtherNet/IP Scanner
Performance
Number of connections
Number of input words
Daisy chain and Star via switches
10/100 Mbit/s
Up to 16 EtherNet/IP target devices managed by the logic controller, monitored within a timeslot of 10 ms
0...16
0...1024
0...1024
Number of output words
I/O communications EtherNet/IP Scanner service
Function block for configuration and data transfer
Originator/Target
Modbus TCP IOScanner
Performance
Number of connections
Number of input words
Number of output words
I/O communications
Other services
Up to 64 Modbus TCP server devices managed by the logic controller, monitored within a timeslot of 35 ms.
0...64
0...2048
0...2048
Modbus TCP IOScanner service
Function block for data transfer
Client/Server
FDT/DTM/EDS management
FDR (Fast Device Replacement)
DHCP server
Security management (refer to
and
Firewall Configuration, page 117 )
Modbus TCP server
Modbus TCP client
EtherNet/IP adapter (controller as a target on EtherNet/IP)
EtherNet/IP Originator
Modbus TCP server (controller as a slave on Modbus TCP)
FTP Server (FTP and TFTP protocols), page 92
Additional features
IEC VAR ACCESS
Possible to mix up to 16 EtherNet/IP and Modbus TCP server devices.
Devices can be directly accessed for configuration, monitoring, and management purposes.
Network transparency between control network and device network (logic controller can be used as a gateway).
NOTE: Using the logic controller as a gateway can impact the performance of the logic controller.
126 EIO0000003089.05
EtherNet/IP Overview
EtherNet/IP is the implementation of the CIP protocol over standard Ethernet.
The EtherNet/IP protocol uses an Originator/Target architecture for data exchange.
Originators are devices that initiate data exchanges with Target devices on the network. This applies to both I/O communications and service messaging. This is the equivalent of the role of a client in a Modbus network.
Targets are devices that respond to data requests generated by Originators. This applies to both I/O communications and service messaging. This is the equivalent of the role of a server in a Modbus network.
EtherNet/IP Adapter is an end-device in an EtherNet/IP network. I/O blocks and drives can be EtherNet/IP Adapter devices.
The communication between an EtherNet/IP Originator and Target is accomplished using an EtherNet/IP connection.
Modbus TCP Overview
The Modbus TCP protocol uses a Client/Server architecture for data exchange.
The Modbus TCP explicit (non-cyclic) data exchanges are managed by the application.
Modbus TCP implicit (cyclic) data exchanges are managed by the Modbus TCP
IOScanner. The Modbus TCP IOScanner is a service based on Ethernet that polls slave devices continuously to exchange data, status, and diagnostic information.
This process monitors inputs and controls outputs of slave devices.
Clients are devices that initiate data exchange with other devices on the network.
This applies to both I/O communications and service messaging.
Servers are devices that address any data requests generated by a Client. This applies to both I/O communications and service messaging.
The communication between the Modbus TCP IOScanner and the slave device is accomplished using Modbus TCP channels.
Adding the Industrial Ethernet Manager
The Industrial_Ethernet_manager must be present on the Ethernet_2 (Device
Network) node of the Devices tree to activate these functions and services:
• EtherNet/IP Scanner
• Modbus TCP IOScanner
The Industrial_Ethernet_manager is available by default under the Ethernet_2
(Device Network) node. It is automatically added when a slave device is added on the Ethernet_2 (Device Network) node.
EIO0000003089.05
127
To manually add the Industrial_Ethernet_manager to the Ethernet_2 (Device
Network) :
Step
1
2
3
4
Action
In the Devices tree , select Ethernet_2 (Device Network) and click the green plus button of the node or right-click Ethernet_2 (Device Network) and execute the Add
Device...
command from the context menu.
Result : The Add Device dialog box displays.
In the Add Device dialog box, select Protocol Managers manager .
>
Industrial Ethernet
Click the Add Device button.
Click the Close button.
For more information, refer to Industrial Ethernet Manager Configuration (see
EcoStruxure Machine Expert EtherNet/IP, User Guide), EtherNet/IP Target
Settings (see EcoStruxure Machine Expert EtherNet/IP, User Guide) and Modbus
TCP Settings (see EcoStruxure Machine Expert Modbus TCP, User Guide).
DHCP Server
Overview
It is possible to configure a DHCP server on the Ethernet 2 network of the
TM251MESE.
The DHCP server offers addresses to the devices connected on the Ethernet 2 network. The DHCP server only delivers static addresses. A unique identified slave gets a unique address. DHCP slave devices are identified either by their
MAC address or their DHCP device name. The DHCP server configuration table defines the relation between addresses and identified slave devices.
The DHCP server addresses are given with an infinite lease time. There is no need for the slave devices to refresh the leased IP address.
For more information, refer to IP Addressing Methods (see EcoStruxure Machine
Expert Modbus TCP, User Guide).
Fast Device Replacement
Overview
The Fast Device Replacement (FDR) helps facilitate replacing and reconfiguring a network device. This function is available on the Ethernet 2 port of the
TM251MESE.
For more information, refer to Slave Device Replacement with FDR (see
EcoStruxure Machine Expert Modbus TCP, User Guide).
128 EIO0000003089.05
Serial Line Configuration
Introduction
This chapter describes how to configure the serial line communication of the
Modicon M251 Logic Controller.
Serial Line Configuration
Introduction
The Serial Line configuration window allows you to configure the physical parameters of a serial line (baud rate, parity, and so on).
Serial Line Configuration
To configure a Serial Line, double-click Serial line in the Devices tree .
The Configuration window is displayed as below:
EIO0000003089.05
The following parameters must be identical for each serial device connected to the port.
Element
Baud rate
Parity
Data bits
Stop bits
Physical
Medium
Polarization
Resistor
Description
Transmission speed in bits/s
Used for error detection
Number of bits for transmitting data
Number of stop bits
Specify the medium to use:
• RS485 (using polarisation resistor or not)
• RS232
Polarization resistors are integrated in the controller. They are switched on or off by this parameter.
The serial line ports of your controller are configured for the Machine Expert protocol by default when new or when you update the controller firmware. The
Machine Expert protocol is incompatible with that of other protocols such as
Modbus Serial Line. Connecting a new controller to, or updating the firmware of a
129
controller connected to, an active Modbus configured serial line can cause the other devices on the serial line to stop communicating. Make sure that the controller is not connected to an active Modbus serial line network before first downloading a valid application having the concerned port or ports properly configured for the intended protocol.
NOTICE
INTERRUPTION OF SERIAL LINE COMMUNICATIONS
Be sure that your application has the serial line ports properly configured for
Modbus before physically connecting the controller to an operational Modbus
Serial Line network.
Failure to follow these instructions can result in equipment damage.
This table indicates the maximum baud rate value of the managers:
Manager
Machine Expert Network Manager
Modbus Manager
ASCII Manager
Modbus IOScanner
Maximum Baud Rate (Bits/S)
115200
Machine Expert Network Manager
Introduction
Use the Machine Expert Network Manager to exchange variables with a XBTGT/
XBTGK Advanced Panel with Machine Expert software protocol, or when the
Serial Line is used for EcoStruxure Machine Expert programming.
Adding the Manager
To add a Machine Expert Network Manager to your controller, select the Machine
Expert-Network Manager in the Hardware Catalog , drag it to the Devices tree , and drop it on one of the highlighted nodes.
For more information on adding a device to your project, refer to:
• Using the Hardware Catalog
• Using the Contextual Menu or Plus Button
Configuring the Manager
There is no configuration for Machine Expert Network Manager.
Adding a Modem
To add a modem to the Machine Expert Network Manager, refer to
Modem to a Manager, page 144 .
130 EIO0000003089.05
Modbus Manager
Introduction
The Modbus Manager is used for Modbus RTU or ASCII protocol in master or slave mode.
Adding the Manager
To add a Modbus manager to your controller, select the Modbus Manager in the
Hardware Catalog , drag it to the Devices tree , and drop it on one of the highlighted nodes.
For more information on adding a device to your project, refer to:
• Using the Hardware Catalog
• Using the Contextual Menu or Plus Button
Modbus Manager Configuration
To configure the Modbus Manager of your controller, double-click Modbus
Manager in the Devices tree .
The Modbus Manager configuration window is displayed as below:
Modbus_Manager
Configuration Status Information
Modbus
Transmission Mode:
Addressing:
RTU
Slave
Time between Frames (ms):
Serial Line Settings
Baud Rate: 38400
Parity: None
10
Data Bits:
Stop Bits:
8
1
Physical Medium: RS485
ASCII
Address [1...247]: 1
EIO0000003089.05
131
Set the parameters as described in this table:
Element
Transmission
Mode
Addressing
Address
Time between
Frames (ms)
Serial Line
Settings
Description
Specify the transmission mode to use:
• RTU: uses binary coding and CRC error-checking (8 data bits)
• ASCII: messages are in ASCII format, LRC error-checking (7 data bits)
Set this parameter identical for each Modbus device on the link.
Specify the device type:
• Master
• Slave
Modbus address of the device, when slave is selected.
Time to avoid bus-collision.
Set this parameter identical for each Modbus device on the link.
Parameters specified in the Serial Line configuration window.
Modbus Master
When the controller is configured as a Modbus Master, the following function blocks are supported from the PLCCommunication Library:
• ADDM
• READ_VAR
• SEND_RECV_MSG
• SINGLE_WRITE
• WRITE_READ_VAR
• WRITE_VAR
For further information, see Function Block Descriptions (see EcoStruxure
Machine Expert, Modbus and ASCII Read/Write Functions, PLCCommunication
Library Guide) of the PLCCommunication Library.
Modbus Slave
When the controller is configured as Modbus Slave, the following Modbus requests are supported:
Function Function Code
Dec (Hex)
1 (1 hex)
2 (2 hex)
3 (3 hex)
6 (6 hex)
8 (8 hex)
15 (F hex)
16 (10 hex)
23 (17 hex)
43 (2B hex)
–
–
–
–
–
–
Sub-Function
Dec (Hex)
–
–
14 (E hex)
Read digital outputs (%Q)
Read digital inputs (%I)
Read multiple register (%MW)
Write single register (%MW)
Diagnostic
Write multiple digital outputs (%Q)
Write multiple registers (%MW)
Read/write multiple registers (%MW)
Read device identification
132 EIO0000003089.05
This table contains the sub-function codes supported by the diagnostic Modbus request 08:
Function
11
12
13
14
15
16
17
18
Sub-Function Code
Dec
10
Hex
0A
0B
0C
0D
0E
0F
10
11
12
Clears Counters and Diagnostic Register
Returns Bus Message Count
Returns Bus Communication Error Count
Returns Bus Exception Error Count
Returns Slave Message Count
Returns Slave No Response Count
Returns Slave NAK Count
Returns Slave Busy Count
Returns Bus Character Overrun Count
This table lists the objects that can be read with a read device identification request (basic identification level):
Object ID
00 hex
01 hex
Object Name
Vendor code
Product code
02 hex Major / Minor revision
Type
ASCII String
ASCII String
ASCII String
Value
Schneider Electric
Controller reference for example: TM251MESE aa.bb.cc.dd (same as device descriptor)
The following section describes the differences between the Modbus memory mapping of the controller and HMI Modbus mapping. If you do not program your application to recognize these differences in mapping, your controller and HMI will not communicate correctly. Thus it will be possible for incorrect values to be written to memory areas responsible for output operations.
WARNING
UNINTENDED EQUIPMENT OPERATION
Program your application to translate between the Modbus memory mapping used by the controller and that used by any attached HMI devices.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
When the controller and the Magelis HMI are connected via Modbus (HMI is master of Modbus requests), the data exchange uses simple word requests.
There is an overlap on simple words of the HMI memory while using double words but not for the controller memory (see following diagram). In order to have a match between the HMI memory area and the controller memory area, the ratio between double words of HMI memory and the double words of controller memory has to be 2.
EIO0000003089.05
133
The following gives examples of memory match for the double words:
• %MD2 memory area of the HMI corresponds to %MD1 memory area of the controller because the same simple words are used by the Modbus request.
• %MD20 memory area of the HMI corresponds to %MD10 memory area of the controller because the same simple words are used by the Modbus request.
The following gives examples of memory match for the bits:
• %MW0:X9 memory area of the HMI corresponds to %MX1.1 memory area of the controller because the simple words are split in 2 distinct bytes in the controller memory.
Adding a Modem
To add a Modem to the Modbus Manager, refer to
Adding a Modem to a Manager, page 144
.
ASCII Manager
Introduction
The ASCII manager is used on a Serial Line, to transmit and/or receive data with a simple device.
Adding the Manager
To add an ASCII manager to your controller, select the ASCII Manager in the
Hardware Catalog , drag it to the Devices tree , and drop it on one of the highlighted nodes.
For more information on adding a device to your project, refer to:
• Using the Hardware Catalog
• Using the Contextual Menu or Plus Button
ASCII Manager Configuration
To configure the ASCII manager of your controller, double-click ASCII Manager in the Devices tree .
134 EIO0000003089.05
The ASCII Manager configuration window is displayed as below:
Set the parameters as described in this table:
Parameter
Start
Character
First End
Character
Description
If 0, no start character is used in the frame. Otherwise, in Receiving Mode , the corresponding character in ASCII is used to detect the beginning of a frame. In
Sending Mode , this character is added at the beginning of the frame.
If 0, no first end character is used in the frame. Otherwise, in Receiving Mode , the corresponding character in ASCII is used to detect the end of a frame. In
Sending Mode , this character is added at the end of the frame.
Second End
Character
Frame Length
Received
Frame
Received
Timeout (ms)
Serial Line
Settings
If 0, no second end character is used in the frame. Otherwise, in Receiving
Mode , the corresponding character in ASCII is used to detect the end of a frame.
In Sending Mode , this character is added at the end of the frame.
If 0, this parameter is not used. This parameter allows the system to conclude an end of frame at reception when the controller received the specified number of characters.
Note: This parameter cannot be used simultaneously with Frame Received
Timeout (ms) .
If 0, this parameter is not used. This parameter allows the system to conclude the end of frame at reception after a silence of the specified number of ms.
Parameters specified in the
Serial Line configuration window, page 129
.
NOTE: In the case of using several frame termination conditions, the first condition to be TRUE terminates the exchange.
Adding a Modem
To add a Modem to the ASCII manager, refer to
Adding a Modem to a Manager, page 144 .
Modbus Serial IOScanner
Introduction
The Modbus IOScanner is used to simplify exchanges with Modbus slave devices.
EIO0000003089.05
135
Add a Modbus IOScanner
To add a Modbus IOScanner on a Serial Line, select the Modbus_IOScanner in the Hardware Catalog , drag it to the Devices tree , and drop it on one of the highlighted nodes.
For more information on adding a device to your project, refer to:
• Using the Hardware Catalog
• Using the Contextual Menu or Plus Button
Modbus IOScanner Configuration
To configure a Modbus IOScanner on a Serial Line, double-click Modbus
IOScanner in the Devices tree .
The configuration window is displayed as below:
Modbus Master Configuration Modbus Master I/O Mapping Status Information
Modbus-RTU/
ASCII
Transmission Mode RTU ASCII
Response Timeout (ms)
Time between Frames (ms)
1000
10
Set the parameters as described in this table:
Element
Transmission
Mode
Description
Specifies the transmission mode to use:
• RTU: uses binary coding and CRC error-checking (8 data bits)
• ASCII: messages are in ASCII format, LRC error-checking (7 data bits)
Set this parameter identical for each Modbus device on the network.
Timeout used in the exchanges.
Response
Timeout (ms)
Time between
Frames (ms)
Delay to reduce data collision on the bus.
Set this parameter identical for each Modbus device on the network.
NOTE: Do not use function blocks of the PLCCommunication library on a serial line with a Modbus IOScanner configured. This disrupts the Modbus
IOScanner exchange.
Bus Cycle Task Selection
The Modbus IOScanner and the devices exchange data at each cycle of the chosen application task.
136 EIO0000003089.05
To select this task, select the Modbus Master IO Mapping tab. The configuration window is displayed as below:
The Bus cycle task parameter allows you to select the application task that manages the scanner:
• Use parent bus cycle setting : associate the scanner with the application task that manages the controller.
• MAST : associate the scanner with the MAST task.
• Another existing task: you can select an existing task and associate it to the scanner. For more information about the application tasks, refer to the
EcoStruxure Machine Expert Programming Guide (see EcoStruxure Machine
Expert, Programming Guide).
The scan time of the task associated with the scanner must be less than 500 ms.
Adding a Device on the Modbus Serial IOScanner
Introduction
This section describes how to add a device on the Modbus IOScanner.
Adding a Device on the Modbus IOScanner
To add a device on the Modbus IOScanner, select the Generic Modbus Slave in the Hardware Catalog , drag it to the Devices tree , and drop it on the Modbus_
IOScanner node of the Devices tree .
For more information on adding a device to your project, refer to:
• Using the Hardware Catalog
• Using the Contextual Menu or Plus Button
NOTE: The variable for the exchange is automatically created in the %IWx and
%QWx of the Modbus Serial Master I/O Mapping tab.
EIO0000003089.05
137
Configuring a Device Added on the Modbus IOScanner
Step
1
To configure the device added on the Modbus IOScanner, proceed as follows:
Action
In the Devices tree , double-click Generic Modbus Slave .
Result: The configuration window is displayed.
Generic_Modbus_Slave
General Modbus Slave Channel Modbus Slave Init
Modbus-RTU/ASCII
Slave Address [1..247]
Response Timeout [ms]
1
1000
Modbus Master I/O Mapping Status Information
2
3
Enter a Slave Address value for your device (choose a value from 1 to 247).
Choose a value for the Response Timeout (in ms).
138 EIO0000003089.05
Step
1
To configure the Modbus Slave Channels , proceed as follows:
Action
Click the Modbus Channels tab:
2 Click the Add Channel button:
ModbusChannel
Channel
Name
Access Type
Trigger
Comment
Channel 0
Read Holding Registers (Function Code 3)
Cyclic Cycle Time (ms) 100
READ Register
Offset
Length
Error Handling
0x0000
1
Keep last Value
WRITE Register
Offset
Length
0x0000
1
OK Cancel
EIO0000003089.05
139
140
Step
3
4
Action
Configure an exchange:
In the area Channel , you can add the following values:
• Name : Enter a name for your channel.
• Access Type : Choose the exchange type: Read or Write or Read/Write multiple requests. See
.
• Trigger : Choose the trigger of the exchange. It can be CYCLIC with the period defined in Cycle Time (ms) field, started by a RISING EDGE on a boolean variable (this boolean variable is then created in the Modbus Master I/O
Mapping tab), or by the Application .
• Comment : Add a comment about this channel.
In the area READ Register (if your channel is Read or Read/Write one), you can configure the %MW to be read on the
Modbus slave. Those are mapped on %IW (see Modbus Master I/O Mapping tab):
• Offset : Offset of the %MW to read. 0 means that the first object that is read is %MW0 .
• Length : Number of %MW to be read. For example, if Offset = 2 and Length = 3, the channel reads %MW2, %MW3 and
%MW4 .
• Error Handling : choose the behavior of the related %IW in case of loss of communication.
In the area WRITE Register (if your channel is Write or Read/Write one), you can configure the %MW to be written to the
Modbus slave. Those are mapped on %QW (see Modbus Master I/O Mapping tab):
• Offset : Offset of the %MW to write. 0 means that the first object that is written is %MW0 .
• Length : Number of %MW to be written. For example, if Offset = 2 and Length = 3, the channel writes %MW2, %MW3 and %MW4 .
Click OK to validate the configuration of this channel.
NOTE: You can also:
• Click the Delete button to remove a channel.
• Click the Edit button to change the parameters of a channel.
Result: The configured channels are displayed:
Library Manager SR_Main TM3BC_ModbusTCP TM3BC_ModbusSL
General Modbus Slave Channel Modbus Slave Init Modbus Master I/O Mapping
Generic_Modbus_Slave Modbus_IOScanner
Modbus Master IEC Objects Status Information
Name Access Type Trigger
0 Channel 0 Read Holding Registers (Function Code 03) Cyclic, t#100ms
READ Offset Length Error Handling
16#0000 1 Keep last value
WRITE Offset Length Comment
1 Channel 1 Write Multiple Registers (Function Code 16) Cyclic, t#100ms 16#0000 1
EIO0000003089.05
Step
1
To configure your Modbus Initialization Value , proceed as follows:
Action
Click the Modbus Slave Init tab:
2 Click New to create a new initialization value:
3
The Initialization Value window contains the following parameters:
• Access Type : Enter the exchange type: Write requests
• Register Offset : Register number of register to be initialized.
• Length : Number of %MW to be read. For example, if 'Offset' = 2 and 'Length' = 3, the channel reads %MW2, %MW3 and
%MW4 .
• Initialization Value : Value the registers are initialized with.
• Comment : Add a comment about this channel.
Click OK to create a new Initialization Value .
NOTE: You can also:
• Click Move up or Move down to change the position of a value in the list.
• Click Delete to remove a value in the list.
• Click Edit to change the parameters of a value.
EIO0000003089.05
141
Step
1
To configure your Modbus Master I/O Mapping , proceed as follows:
Action
Click the Modbus Master I/O Mapping tab:
2
3
Double-click in a cell of the Variable column to open a text field.
Enter the name of a variable or click the browse button [...] and chose a variable with the Input Assistant .
For more information on I/O mapping, refer to EcoStruxure Machine Expert Programming Guide.
Access Types
This table describes the different access types available:
Function
Read Coils
Read Discrete Inputs
Read Holding Registers (default setting for the channel configuration)
Read Input Registers
Write Single Coil
4
5
Function Code Availability
1
2
3
ModbusChannel
ModbusChannel
ModbusChannel
Write Single Register
Write Multiple Coils
Write Multiple Registers (default setting for the slave initialization)
Read/Write Multiple Registers
6
15
16
23
ModbusChannel
ModbusChannel
Initialization Value
ModbusChannel
Initialization Value
ModbusChannel
Initialization Value
ModbusChannel
Initialization Value
ModbusChannel
142 EIO0000003089.05
ControlChannel: Enables or Disables a Communication
Channel
Function Description
This function allows you to enable or disable a communication channel.
A channel managed by this function is reinitialized to its default value after a reset
(cold/warm).
After a stop or after a start, the channel remains disabled if it was disabled before.
On the contrary, after a reset, the channel is enabled even if it was disabled before.
In the case of the TM3BCSL Modbus Serial Line bus coupler, there are multiple, separate and independent communication channels.
WARNING
UNINTENDED EQUIPMENT OPERATION
Ensure that the Modbus serial line communication channels of the TM3BCSL bus coupler are set to the same state, either enabled or disabled.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: Use ChannelID value -1 to apply the ControlChannel on all channels configured on the TM3BCSL Modbus Serial Line bus coupler.
Graphical Representation
ControlChannel channelID
INT
enable
BOOL
INT
ControlChannel
I/O Variable Description
This table describes the input variables:
Input
ControlChannel
ChannelID
Type
INT
INT
Comment
Return 0 on success, a negative value on error.
The channel number (visible in the first column of the configuration page).
Or -1 to apply the command on all channels of this device.
This table describes the output variable:
Output
Enable
Type
BOOL
Comment
Enable or disable command.
EIO0000003089.05
143
Adding a Modem to a Manager
Introduction
A modem can be added to the following managers:
• ASCII Manager
• Modbus Manager
• Machine Expert Network Manager
NOTE: Use a modem which implements Hayes commands if you need a modem connection with Machine Expert Network Manager.
Adding a Modem to a Manager
To add a modem to your controller, select the modem you want in the Hardware
Catalog , drag it to the Devices tree , and drop it on the manager node.
For more information on adding a device to your project, refer to:
• Using the Hardware Catalog
• Using the Contextual Menu or Plus Button
For further information, refer to Modem Library Guide (see EcoStruxure Machine
Expert, Modem Functions, Modem Library Guide).
144 EIO0000003089.05
CANopen Configuration
Introduction
This chapter describes how to configure the CAN interface offered within the controller.
In order to use the CANopen interface, the M251 Logic Controller has 1 CAN connection (CAN0) that supports a CANopen manager.
CANopen Interface Configuration
CAN Bus Configuration
To configure the CAN bus of your controller, proceed as follows:
Step
1
2
Action
In the Devices tree , double-click CAN_1 .
Configure the baudrate (by default: 250000 bits/s):
NOTE: The Online Bus Access option allows you to block SDO, DTM, and NMT sending through the status screen.
When connecting a DTM to a device using the network, the DTM communicates in parallel with the running application. The overall performance of the system is impacted and may overload the network, and therefore have consequences for the coherency of data across devices under control.
WARNING
UNINTENDED EQUIPMENT OPERATION
Place your machine or process in a state such that DTM communications will not impact its performance.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
EIO0000003089.05
145
CANopen Manager Creation and Configuration
If the CANopen Manager is not already present below the CAN node, proceed as follows to create and configure it:
Step Action
1
Click the Plus Button next to the CAN_1 node in the Devices tree . In the Add Device window, select CANopen Performance and click the Add Device button.
For more information on adding a device to your project, refer to:
• Using the Hardware Catalog
• Using the Contextual Menu or Plus Button
2 Double-click CANopen_Performance .
Result: The CANopen Manager configuration window appears:
146
NOTE: If Enable Sync Producing is checked, the CAN_x_Sync task is added to the Application > Task Configuration node in the Applications tree tab.
Do not delete or change the Type or External event attributes of CAN_x_
Sync tasks. If you do so, EcoStruxure Machine Expert will detect an error when you attempt to build the application, and you will not be able to download it to the controller.
If you uncheck the Enable Sync Producing option on the CANopen
Manager subtab of the CANopen_Performance tab, the CAN0_Sync task is automatically deleted from your program.
EIO0000003089.05
Adding a CANopen Device
Refer to the EcoStruxure Machine Expert Programming Guide for more information on Adding Communication Managers and Adding Slave Devices to a
Communication Manager.
CANopen Operating Limits
The Modicon M251 Logic Controller CANopen master has the following operating limits:
Maximum number of slave devices
Maximum number of Receive PDO (RPDO)
Maximum number of Transmit PDO (TPDO)
63
252
252
WARNING
UNINTENDED EQUIPMENT OPERATION
• Do not connect more than 63 CANopen slave devices to the controller.
• Program your application to use 252 or fewer Transmit PDO (TPDO).
• Program your application to use 252 or fewer Receive PDO (RPDO).
Failure to follow these instructions can result in death, serious injury, or equipment damage.
CAN Bus Format
The CAN bus format is CAN2.0A for CANopen.
EIO0000003089.05
147
J1939 Configuration
J1939 Interface Configuration
CAN Bus Configuration
To configure the CAN bus of your controller, refer to
.
The CAN bus format is CAN2.0B for J1939.
J1939 Manager Creation and Configuration
Proceed as follows to create and configure a J1939 Manager, if not already present, below the CAN_1 node:
Action Step
1
2
3
4
Click the Plus button next to the CAN_1 node in the Devices tree .
In the Add Device window, select J1939_Manager and click the Add Device button.
For more information on adding a device to your project, refer to:
• Using the Hardware Catalog
• Using the Contextual Menu or Plus Button
Close the Add Device window.
Double-click J1939_Manager (J1939_Manager) .
Result: The J1939_Manager configuration window appears:
5 To configure the J1939_Manager , refer to Programming with EcoStruxure Machine
Expert / Device Editors / J1939 Configuration Editor / J1939 Manager Editor / Manager
Editor found in the EcoStruxure Machine Expert online help.
148 EIO0000003089.05
ECU Creation and Configuration
Proceed as follows to create and configure Electronic Control Units (ECUs):
Action Step
1
2
3
4
Click the Plus button
Devices tree .
next to the J1939_Manager (J1939_Manager) node in the
In the Add Device window, select J1939_ECU and click the Add Device button.
For more information on adding a device to your project, refer to:
• Using the Hardware Catalog
• Using the Contextual Menu or Plus Button
Close the Add Device window.
Double-click J1939_ECU (J1939_ECU) .
Result: The J1939_ECU configuration window appears:
5 To configure the J1939_ECU , refer to
Configuring J1939 ECUs, page 149 .
Configuring J1939 ECUs
As an overview, the following tasks must be generally accomplished:
• Add one J1939_ECU node for each physical J1939 device connected on the
CAN bus.
• For each J1939 device, specify a unique Preferred Address in the range
1...253.
• For each J1939 device, configure the signals (SPNs) in the TX Signals tab.
These signals are broadcast by the J1939 device to the other J1939 devices.
Refer to the device documentation for information on the supported SPNs.
• Associate the SPN signals with variables in the J1939 I/O Mapping tab so that they can be processed by the application.
EIO0000003089.05
149
• When signals have been added, verify their settings in the Conversion window of the TX signals tab, for example, Scaling , Offset , and Unit . The
J1939 protocol does not directly support REAL values, which are instead encoded in the protocol and so must be converted in the application.
Similarly, in J1939 units are defined according to the International System of
Units (SI) and therefore may need to be converted to values of other unit systems.
Examples:
◦ The Engine Speed signal of parameter group EEC1 has a property
Scaling=0.125
that is encoded into a raw variable of type ARRAY[0..1]
OF BYTE . Use the following ST code to convert this to a REAL variable: rRPM:=(Engine_Speed[1]*256 + Engine_Speed[0])*0.125;
◦ The Total Vehicle Distance signal has properties Scaling=0.125
and
Unit=km , which are received in a (raw) variable of type ARRAY[0..3] OF
BYTE . Use the following ST code to convert this to a REAL variable in mile units: rTVD := (Total_Vehicle_Distance[3]*EXPT(256,3) +
Total_Vehicle_Distance[2]*EXPT(256,2) + Total_Vehicle_
Distance[1]*256 +
Total_Vehicle_Distance[0])*0.125*0.621371;
◦ The Engine Coolant Temperature signal of parameter group ET1 has properties Offset=-40 and Unit=C(Celsius) , which are received in a (raw) variable of type BYTE . Use the following ST code to convert it to a REAL variable in Fahrenheit units: rEngineCoolantTemperature := (Engine_Coolant_
Temperature - 40)*1.8 + 32;
For more details on how to configure the J1939_ECU , refer to Programming with
EcoStruxure Machine Expert / Device Editors / J1939 Configuration Editor / J1939
ECU Editor / ECU Editor found in the EcoStruxure Machine Expert online help.
Configuring the M251 Logic Controller as an ECU Device
The controller can also be configured as a J1939 ECU device:
Step
1
2
3
4
5
6
Action
Add a J1393_ECU node to the J1939_Manager . Refer to
.
Select the Local Device option in the General tab.
Configure signals sent from the controller to other J1939 devices in the TX Signals tab.
Parameter groups are either of type Broadcast , that is, sent to all devices, or P2P
(Peer-to-Peer), that is, sent to one specified device.
For P2P signals, configure the Destination Address of the receiving J1939 ECU device in the parameter group properties window.
Add P2P signals sent by another J1939 device to the controller in the RX Signals
(P2P) tab of the J1939 (local) device representing the controller.
Configure the Source Address of the parameter group by specifying the address of the sending J1939 device.
150 EIO0000003089.05
OPC UA Server Configuration
Introduction
This chapter describes how to configure the OPC UA server of the M251 Logic
Controller.
OPC UA Server Overview
Overview
The OPC Unified Architecture server (OPC UA server) allows the M251 Logic
Controller to exchange data with OPC UA clients. Server and client communicate through sessions.
The monitored items of data (also referred to as symbols) to be shared by the
OPC UA server are manually selected from a list of the IEC variables used in the application.
OPC UA uses a subscription model; clients subscribe to symbols. The OPC UA server reads the values of symbols from devices at a fixed sampling rate, places the data in a queue, then sends them to clients as notifications at a regular publishing interval. The sampling interval can be shorter than the publishing interval, in which case notifications may be queued until the publishing interval elapses.
Symbols that have not changed value since the previous sample are not republished. Instead, the OPC UA server sends regular KeepAlive messages to indicate to the client that the connection is still active.
User and Group Access Rights
Access to the OPC UA server is controlled by user rights. Refer to
.
OPC UA Services
The following table describes the supported OPC UA services:
OPC UA Service
Address Space Model
Session services
Attribute services
Monitored item services
Queued items
Subscription services
Publishing method
Description
Yes
Yes
Yes
Yes
Yes
Yes
Yes
EIO0000003089.05
151
OPC UA Server Configuration
Introduction
The OPC UA Server Configuration window allows you to configure the OPC UA server.
Optionally, you can customize the OPC UA server name via the post configuration. Refer to
.
Accessing the OPC UA Server Configuration Tab
To configure the OPC UA Server:
Step
1
2
Action
In the Devices tree , double-click MyController .
Select the OPC UA Server Configuration tab.
OPC UA Server Configuration Tab
The following figure shows the OPC UA Server Configuration window:
152 EIO0000003089.05
OPC UA Server Configuration Description
Value
This table describes the OPC UA Server Configuration parameters:
Default value Description Parameter
Security Settings
Disable anonymous login Enabled/
Disabled
Disabled By default, this checkbox is cleared, meaning that OPC UA clients can connect to the server anonymously. Select this checkbox to require that clients provide a valid user name and password to connect to the
OPC UA server.
Server Configuration
Server port 0...65535
4840
Max. subscriptions per session
Min. publishing interval
Max. monitored items per subscription
Min. KeepAlive interval
1...1000
500...5000
Max. number of sessions
Identifier type
1...100
200...5000
1...4
Numeric
String
20
1000
100
500
2
Numeric
The port number of the OPC UA server. OPC UA clients must append this port number to the TCP URL of the controller to connect to the
OPC UA server.
Specify the maximum number of subscriptions allowed within each session.
The publishing interval defines how frequently the OPC UA server sends notification packages to clients. Specify the minimum time that must elapse between notifications, in ms.
The maximum number of monitored items in each subscription that the server assembles into a notification package.
The OPC UA server only sends notifications when the values of monitored items of data are modified. A KeepAlive notification is an empty notification sent by the server to inform the client that although no data has been modified, the subscription is still active. Specify the minimum interval between KeepAlive notifications, in ms.
The maximum number of clients that can connect simultaneously to the OPC UA server.
Certain OPC UA clients require a specific format of unique symbol identifier (node ID). Select the format of the identifiers:
• Numeric values
• Text strings
Diagnostic
Enable trace Enabled/ disabled
Enabled
Sampling rates (ms) 200...5000
500
1000
2000
Select this checkbox to include OPC UA diagnostic messages in the controller log file. Traces are available from the Log tab or from the
System Log File of the Web Server.
You can select the category of events to write to the log file:
• None
• Error
• Warning
• System
• Information
• Debug
• Content
• All (default)
The sampling rate indicates a time interval, in milliseconds (ms).
When this interval has elapsed, the server sends the notification package to the client. The sampling rate can be shorter than the publishing interval, in which case notifications are queued until the publishing interval has elapsed.
Sampling rates must be in the range 200...5000 (ms).
Up to 3 different sampling rates can be configured.
Double-click on a sampling rate to edit its value.
To add a sampling rate to the list, right-click and choose Add a new rate .
To remove a sampling rate from the list, select the value and click .
Click Reset to default to return the configuration parameters on this window to their default values.
EIO0000003089.05
153
OPC UA Server Symbols Configuration
Introduction
Symbols are the items of data shared with OPC UA clients. Symbols are selected from a list of all the IEC variables used in the application. The selected symbols are then sent to the logic controller as part of the application download.
Each symbol is assigned a unique identifier. As certain client types may require a specific format, identifiers can be configured to be in either string or numeric format.
The OPC UA server supports the following IEC variable types:
• Boolean
• Byte
• Int16, Int32, Int64
• UInt16, UInt32, UInt64
• Float
• Double
• String (255 bytes)
• Sbyte
Bit memory variables (%MX) cannot be selected.
Displaying the List of Variables
To display the list of variables:
Step
1
2
Action
On the Applications tree tab, right-click Application and choose Add object
UA Symbol Configuration .
> OPC
Result: The OPC UA Symbols window is displayed. The logic controller starts the OPC
UA server.
Click Add .
NOTE: The IEC objects %MX , %IX , %QX are not directly accessible. To access
IEC objects you must first group their contents in located registers (refer to
).
Selecting OPC UA Server Symbols
The OPC UA Symbols window displays the variables available for selection as symbols:
154
Select IoConfig_Globals_Mapping to select all the available variables.
Otherwise, select individual symbols to share with OPC UA clients. A maximum of
1000 symbols can be selected.
EIO0000003089.05
Each symbol has the following properties:
Name
Symbols
Type
Access type
Comment
Description
The variable name followed by the address of the variable.
The data type of the variable.
Click repeatedly to specify the access rights of the symbol: read-only (
) (default), write-only ( ), or read/write ( ).
NOTE: Click in the Access type column of IoConfig_Globals_
Mapping to set the access rights of all the symbols at once.
An optional comment.
Click Refresh to update the list of available variables.
OPC UA Server Performance
Overview
As an example, the following provides capacity and performance information for the OPC UA server of the M251 Logic Controller. Design considerations are also provided to help you consider the optimal conditions for the performance of the
OPC UA server. Of course, the performance realized by your application depend on many variables and conditions, and may differ from this example.
System Configurations Used to Evaluate Performance
OPC UA server performance is determined by the system configuration, the number of symbols being published, and the percentage of symbols being refreshed.
The following table presents the number of elements in small, medium, and large sample configurations used for evaluating OPC UA server performance:
Elements
EtherNet/IP adapters
Expansion modules
CANopen slave devices
PTO functions
HSC functions
Profibus connections
Modbus TCP slave devices
0
0
0
0
0
0
Small
0
5
1
0
6
4
8
Medium
7
Large
0
7
63
4
8
1
64
This table presents average read/write request times for each of the sample configurations and for different numbers of symbols:
Average Read/Write Request Times
Configuration
Small
Medium
Large
Number of Symbols
50
42 ms
73 ms
520 ms
100
70 ms
121 ms
895 ms
250
151 ms
265 ms
2045 ms
400
232 ms
412 ms
3257 ms
500
284 ms
514 ms
4071 ms
1000
554 ms
1024 ms
7153 ms
EIO0000003089.05
155
The following tables present the average time required to refresh a monitored set of symbols using a sampling rate of 200 ms and a publishing interval of 200 ms.
This table presents the average time required to refresh 100% of symbols for each of the sample configurations:
Average Time to Refresh 100% of Symbols
Number of Symbols
Configuration
Small
Medium
Large
100
214 ms
224 ms
324 ms
400
227 ms
250 ms
330 ms
1000
254 ms
292 ms
800 ms
This table presents the average time required to refresh 50% of symbols for each of the sample configurations:
Average Time to Refresh 50% of Symbols
Configuration
Small
Medium
Large
Number of Symbols
100
211 ms
219 ms
284 ms
400
220 ms
234 ms
300 ms
1000
234 ms
254 ms
660 ms
This table presents the average time required to refresh 1% of symbols for each of the sample configurations:
Average Time to Refresh 1% of Symbols
Number of Symbols
Configuration
Small
Medium
Large
100
210 ms
215 ms
270 ms
400
210 ms
217 ms
277 ms
1000
212 ms
220 ms
495 ms
Optimizing OPC UA Server Performance
The OPC UA server functionality is dependent on external communication networks, external device performance, and other external parameters. Data transmitted may be delayed or other possible communication errors may arise that impose practical limits on machine control. Do not use the OPC UA server functionality for safety-related data or other time-dependent purposes.
WARNING
UNINTENDED EQUIPMENT OPERATION
• Do not allow safety-related data in OPC UA server data exchanges.
• Do not use OPC UA server data exchanges for any critical or timedependent purposes.
• Do not use OPC UA server data exchanges to change equipment states without having done a risk analysis and implementing appropriate safetyrelated measures.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
156 EIO0000003089.05
The above tables can be useful in determining whether OPC UA server performance is within acceptable limits. Be aware, however, that other external factors influence overall system performance, such as the volume of Ethernet traffic.
To optimize OPC UA server performance, consider the following:
• Minimize Ethernet traffic by setting the Min. publishing interval to the lowest value that yields an acceptable response time.
• The
configured for the M251 Logic Controller must be less than the configured Min. publishing interval value.
• Configuring a Max. number of sessions (the number of OPC UA clients that can simultaneously connect to the OPC UA server) value of greater than 1 decreases the performance of all sessions.
• The sampling rate determines the frequency at which data is exchanged.
Tune the Sampling rates (ms) value to product the lowest response time that does not adversely affect the overall performance of the logic controller.
EIO0000003089.05
157
Post Configuration
Introduction
This chapter describes how to generate and configure the post configuration file of the Modicon M251 Logic Controller.
Post Configuration Presentation
Introduction
Post configuration is an option that allows you to modify some parameters of the application without changing the application. Post configuration parameters are defined in a file called Machine.cfg
, which is stored in the controller.
By default, all parameters are set in the application. The parameters defined in the
Post Configuration file are used instead of the corresponding parameters defined in the application. Not all parameters have to be specified in the Post
Configuration file (for example: one parameter can change the IP address without changing the Gateway Address).
Parameters
The Post Configuration file allows you to change network parameters.
OPC UA parameters:
• Server name
NOTE: The following characters are supported by the server name parameter: a...z A...Z 0...9 - _
The length is limited to 30 characters.
Ethernet parameters:
• IP Address
• Subnet Mask
• Gateway Address
• Transfer Rate
• IP Config Mode
• Device Name
•
Serial Line parameters, for each serial line in the application (embedded port or
PCI module):
• Baud rate
• Parity
• Data bits
• Stop bit
FTP:
• FTP encryption setting parameter
Profibus parameters, for each Profibus in the application (TM4 module):
• Station address
• Baud rate
158 EIO0000003089.05
NOTE: Parameter updates with a Post Configuration file that impacts parameters used by other devices via a communication port are not updated in the other devices.
For example, if the IP address used by an HMI is updated in the configuration with a Post Configuration file, the HMI uses the previous address. You must update the address used by the HMI independently.
Operating Mode
The Post Configuration file is read after:
• A
• A
• A
• An
Refer to
Controller States and Behaviors, page 35
for further details on controller states and transitions.
Post Configuration File Management
Introduction
The file Machine.cfg
is located in the directory /usr/cfg .
Each parameter is specified by a variable type, variable ID, and value. The format is: id[moduleType].pos[param1Id].id[param2Id].param[param3Id].
paramField=value
Each parameter is defined on three lines in the Post Configuration file:
• The first line describes the internal 'path' for this parameter.
• The second line is a comment describing the parameter.
• The third line is the definition of the parameter (as described above) with its value.
Post Configuration File Generation
The Post Configuration file ( Machine.cfg
) is generated by EcoStruxure Machine
Expert.
To generate the file, proceed as follows:
2
3
Step
1
Action
In the menu bar, choose Build > Post Configuration > Generate...
Result: An explorer window is displayed.
Select the destination folder of the Post Configuration file.
Click OK .
When you use EcoStruxure Machine Expert to create a Post Configuration file
( Generate ), it reads the value of each parameter assigned in your application program and then writes the values to the Machine.cfg
Post Configuration file.
After generating a Post Configuration file, review the file and remove any parameter assignments that you wish to remain under the control of your application. Keep only those parameter assignments that you wish changed by
EIO0000003089.05
159
the Post Configuration function that are necessary to make your application portable and then modify those values appropriately.
Post Configuration File Transfer
After creating and modifying your Post Configuration file, transfer it to the /usr/ cfg directory of the controller. The controller does not read the Machine.cfg
file unless it is in this directory.
You can transfer the Post Configuration file by the following methods:
•
(with the proper script)
• Download through the
• Download with EcoStruxure Machine Expert
controller device editor, page 53
Modifying a Post Configuration File
If the Post Configuration file is located in the PC, use a text editor to modify it.
NOTE: Do not change the text file encoding. The default encoding is ANSI.
To modify the Post Configuration file directly in the controller, use the Setup menu of the
.
To modify the Post Configuration file in the controller with EcoStruxure Machine
Expert in online mode:
Step
1
2
5
6
3
4
Action
In the Devices tree , click the controller name.
Click Build > Post Configuration > Edit...
Result: The Post Configuration file opens in a text editor.
Edit the file.
If you want to apply the modifications after saving them, select Reset device after sending .
Click Save as .
Click Close .
NOTE: If the parameters are invalid, they are ignored.
Deleting the Post Configuration File
You can delete the Post Configuration file by the following methods:
• SD card (with the delete script)
• Through the
• Online with
EcoStruxure Machine Expert controller device editor, page 53
,
Files tab
For more information on Files tab of the Device Editor, refer to EcoStruxure
Machine Expert Programming Guide.
NOTE: The parameters defined in the application are used instead of the corresponding parameters defined in the Post Configuration file after:
• A
• A
• A
• An
160 EIO0000003089.05
Post Configuration Example
Post Configuration File Example for the TM251MESE
# TM251MESE / FTP Encryption
# 1=encryption enforced, 0 otherwise
.param[1106] = 1
# TM251MESE / OPCUA server name
# Only ASCII letters, digits, '-' and '_', 30 char max
.param[1204] = ''
# TM251MESE / Ethernet_1 / IPAddress
# Ethernet IP address id[45000].pos[2].id[45111].param[0] = [192, 168, 1, 20]
# TM251MESE / Ethernet_1 / SubnetMask
# Ethernet IP mask id[45000].pos[2].id[45111].param[1] = [255, 255, 255, 0]
# TM251MESE / Ethernet_1 / GatewayAddress
# Ethernet IP gateway address id[45000].pos[2].id[45111].param[2] = [192, 168, 1, 1]
# TM251MESE / Ethernet_1 / IPConfigMode
# IP configuration mode: 0:FIXED 1:BOOTP 2:DHCP id[45000].pos[2].id[45111].param[4] = 0
# TM251MESE / Ethernet_1 / DeviceName
# Name of the device on the Ethernet network id[45000].pos[2].id[45111].param[5] = 'my_Device'
# TM251MESE / Ethernet_2 / IPAddress
# Ethernet IP address id[45000].pos[3].id[111].param[0] = [85, 100, 108, 241]
# TM251MESE / Ethernet_2 / SubnetMask
# Ethernet IP mask id[45000].pos[3].id[111].param[1] = [255, 0, 0, 0]
EIO0000003089.05
161
# TM251MESE / Ethernet_2 / GatewayAddress
# Ethernet IP gateway address id[45000].pos[3].id[111].param[2] = [0, 0, 0, 0]
# TM251MESE / Ethernet_2 / IPConfigMode
# IP configuration mode: 0:FIXED 1:BOOTP 2:DHCP id[45000].pos[3].id[111].param[4] = 0
# TM251MESE / Ethernet_2 / DeviceName
# Name of the device on the Ethernet network id[45000].pos[3].id[111].param[5] = 'my_Device'
# TM251MESE / Serial_Line_1 / Serial Line Configuration /
Baudrate
# Serial Line Baud Rate in bit/s id[45000].pos[4].id[40101].param[10000].Bauds = 115200
# TM251MESE / Serial_Line_1 / Serial Line Configuration /
Parity
# Serial Line Parity (0=None, 1=Odd, 2=Even) id[45000].pos[4].id[40101].param[10000].Parity = 0
# TM251MESE / Serial_Line_1 / Serial Line Configuration /
DataBits
# Serial Line Data bits (7 or 8) id[45000].pos[4].id[40101]
.param[10000].DataFormat = 8
# TM251MESE / Serial_Line_1 / Serial Line Configuration /
StopBits
# Serial Line Stop bits (1 or 2) id[45000].pos[4].id[40101].param[10000].StopBit= 1
Post Configuration File Example for the TM251MESC
# TM251MESC / FTP Encryption
# 1=encryption enforced, 0 otherwise
.param[1106] = 1
# TM251MESC / OPCUA server name
# Only ASCII letters, digits, '-' and '_', 30 char max
.param[1204] = 1
# TM251MESC / Ethernet_1 / IPAddress
162 EIO0000003089.05
# Ethernet IP address id[45000].pos[2].id[45111].param[0] = [192, 168, 1, 2]
# TM251MESC / Ethernet_1 / SubnetMask
# Ethernet IP mask id[45000].pos[2].id[45111].param[2] = [255, 255, 255, 0]
# TM251MESC / Ethernet_1 / GatewayAddress
# Ethernet IP gateway address id[45000].pos[2].id[45111].param[2] = [192, 168, 1, 1]
# TM251MESC / Ethernet_1 / IPConfigMode
# IP configuration mode: 0:FIXED 1:BOOTP 2:DHCP id[45000].pos[2].id[45111].param[4] = 0
# TM251MESC / Ethernet_1 / DeviceName
# Name of the device on the Ethernet network id[45000].pos[2].id[45111].param[5] = 'my_Device'
# TM251MESC / Serial_Line_1 / Serial Line Configuration /
Baudrate
# Serial Line Baud Rate in bit/s id[45000].pos[3].id[40101].param[10000].Bauds = 115200
# TM251MESC / Serial_Line_1 / Serial Line Configuration /
Parity
# Serial Line Parity (0=None, 1=Odd, 2=Even) id[45000].pos[3].id[40101].param[10000].Parity = 0
# TM251MESC / Serial_Line_1 / Serial Line Configuration /
DataBits
# Serial Line Data bits (7 or 8) id[45000].pos[3].id[40101].param[10000].DataFormat = 8
# TM251MESC / Serial_Line_1 / Serial Line Configuration /
StopBits
# Serial Line Stop bits (1 or 2) id[45000].pos[3].id[40101].param[10000].StopBit = 1
EIO0000003089.05
163
Connecting a Modicon M251 Logic Controller to a PC
Connecting a Modicon M251 Logic Controller to a
PC
Introduction
This chapter shows how to connect a Modicon M251 Logic Controller to a PC.
Connecting the Controller to a PC
Overview
To transfer, run, and monitor the applications, connect the controller to a computer, that has EcoStruxure Machine Expert installed, using either a USB cable or an Ethernet connection (for those references that support an Ethernet port).
NOTICE
INOPERABLE EQUIPMENT
Always connect the communication cable to the PC before connecting it to the controller.
Failure to follow these instructions can result in equipment damage.
USB Powered Download
In order to execute limited operations, the M251 Logic Controller has the capability to be powered through the USB Mini-B port. A diode mechanism avoids having the logic controller both powered by USB and by the normal power supply, or to supply voltage on the USB port.
When powered only by USB, the logic controller executes the firmware and the boot project (if any) and the I/O board is not powered during boot (same duration as a normal boot). USB powered download initializes the internal non-volatile memory with some firmware or some application and parameters when the controller is powered by USB. The preferred tool to connect to the controller is the
Controller Assistant . Refer to the EcoStruxure Machine Expert Controller
Assistant User Guide .
The controller packaging allows easy access to USB Mini-B port with minimum opening of the packaging. You can connect the controller to the PC with a USB cable. Long cables are not suitable for the USB powered download.
WARNING
INSUFFICENT POWER FOR USB DOWNLOAD
Do not use a USB cable longer than 3m (9.8 ft) for USB powered download.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: It is not intended that you use the USB Powered Download on an installed controller. Depending on the number of I/O expansion modules in the physical configuration of the installed controller, there may be insufficient power from your PC USB port to accomplish the download.
164 EIO0000003089.05
Connecting a Modicon M251 Logic Controller to a PC
USB Mini-B Port Connection
Cable Reference
BMXXCAUSBH018:
TCSXCNAMUM3P:
Details
Grounded and shielded, this USB cable is suitable for long duration connections.
This USB cable is suitable for short duration connections such as quick updates or retrieving data values.
NOTE: You can only connect 1 controller or any other device associated with
EcoStruxure Machine Expert and its component to the PC at any one time.
The USB Mini-B Port is the programming port you can use to connect a PC with a
USB host port using EcoStruxure Machine Expert software. Using a typical USB cable, this connection is suitable for quick updates of the program or short duration connections to perform maintenance and inspect data values. It is not suitable for long-term connections such as commissioning or monitoring without the use of specially adapted cables to help minimize electromagnetic interference.
WARNING
UNINTENDED EQUIPMENT OPERATION OR INOPERABLE EQUIPMENT
• You must use a shielded USB cable such as a BMX XCAUSBH0•• secured to the functional ground (FE) of the system for any long-term connection.
• Do not connect more than one controller or bus coupler at a time using USB connections.
• Do not use the USB port(s), if so equipped, unless the location is known to be non-hazardous.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
The communication cable should be connected to the PC first to minimize the possibility of electrostatic discharge affecting the controller.
2
3
4
To connect the USB cable to your controller, follow the steps below:
Step
1
Action
1a If making a long-term connection using the cable BMXXCAUSBH018, or other cable with a ground shield connection, be sure to securely connect the shield connector to the functional ground (FE) or protective ground (PE) of your system before connecting the cable to your controller and your PC.
1b If making a short-term connection using the cable TCSXCNAMUM3P or other nongrounded USB cable, proceed to step 2.
Connect your USB cable to the computer.
Open the protective cover for the USB mini-B slot on the controller.
Connect the mini-B connector of your USB cable to the controller.
EIO0000003089.05
165
Connecting a Modicon M251 Logic Controller to a PC
Ethernet Port Connection
You can also connect the controller to a PC using an Ethernet cable.
To connect the controller to the PC, do the following:
Step
1
2
Action
Connect the Ethernet cable to the PC.
Connect the Ethernet cable to any of the Ethernet ports on the controller.
166 EIO0000003089.05
SD Card
Introduction
This chapter describes how to transfer firmware, application, using an SD card to the Modicon M251 Logic Controller.
Script Files
Overview
The following describes how to write script files (default script file or dynamic script file) to be executed from an SD card or by an application using the ExecScript function block.
Script files can be used to:
•
Configure the Ethernet firewall, page 121
.
• Perform file transfer operations. The script files for these commands can be generated automatically and the necessary files copied to the SD card using the Mass Storage (USB or SD Card) command.
• Change the
for Modbus TCP data exchanges.
Script Syntax Guidelines
The following describes the script syntax guidelines:
• End every line of a command in the script with a " ; ".
• If the line begins with a " ; ", the line is a comment.
• The maximum number of lines in a script file is 50.
• The syntax is not case-sensitive.
• If the syntax is not respected in the script file, the script file is not executed.
This means, for example, that the firewall configuration remains in the previous state.
NOTE: If the script file is not executed, a log file is generated. The log file location in the controller is /usr/Syslog/FWLog.txt
.
SD Card Commands
Introduction
The Modicon M251 Logic Controller allows file transfers with an SD card.
To upload or download files to the controller with an SD card, use one of the following methods:
• The
(use of an empty SD card)
• A script stored in the SD card
When an SD card is inserted into the SD card slot of the controller, the firmware searches and executes the script contained in the SD card (/sys/cmd/Script.cmd).
NOTE: The controller operation is not modified during file transfer.
For file transfer commands, the Mass Storage (USB or SDCard) editor lets you generate and copy the script and all necessary files into the SD card.
EIO0000003089.05
167
NOTE: The Modicon M251 Logic Controller accepts only SD cards formatted in FAT or FAT32.
The SD card must have a label. To add a label, insert the SD card in your PC, right-click on the drive in Windows Explorer and choose Properties .
WARNING
UNINTENDED EQUIPMENT OPERATION
• You must have operational knowledge of your machine or process before connecting this device to your controller.
• Ensure that guards are in place so that any potential unintended equipment operation will not cause injury to personnel or damage to equipment.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
If you remove power to the device, or there is a power outage or communication interruption during the transfer of the application, your device may become inoperative. If a communication interruption or a power outage occurs, reattempt the transfer. If there is a power outage or communication interruption during a firmware update, or if an invalid firmware is used, your device will become inoperative. In this case, use a valid firmware and reattempt the firmware update.
NOTICE
INOPERABLE EQUIPMENT
• Do not interrupt the transfer of the application program or a firmware change once the transfer has begun.
• Re-initiate the transfer if the transfer is interrupted for any reason.
• Do not attempt to place the device into service until the file transfer has completed successfully.
Failure to follow these instructions can result in equipment damage.
Clone Function
The clone function allows you to upload the application from one controller and to download it only to a same controller reference.
This function clones every parameter of the controller (for example applications, firmware, data file, post configuration). Refer to
NOTE: User access rights can only be copied if the Include User Rights button has previously been clicked on the Clone Management subpage of the
By default, clone is allowed without using the function block FB_ControlClone . If you want to restrict access to the clone feature, you can remove the access rights of the ExternalCmd object on ExternalMedia group. Refer to
Default users and groups, page 60
. As a result, cloning will be not allowed without using FB_
ControlClone . For more details about this function block, refer to the Modicon
M251 Logic Controller, System Functions and Variables, PLCSystem Library
Guide (see Modicon M251 Logic Controller, System Functions and Variables,
PLCSystem Library Guide). For more details about Access Rights, refer to the
EcoStruxure Machine Expert Programming Guide.
If you wish to control access to the cloned application in the target controller, you must use the Include users rights button (on the Clone Management subpage of the
Web Server, page 90 ) of the source controller before doing the clone
operation. For more details about Access Rights, refer to the EcoStruxure
Machine Expert Programming Guide.
168 EIO0000003089.05
This procedure describes how to upload the application stored in the source controller to your SD card:
3
4
5
Step Action
1 Erase an SD card and set the card label as follows:
CLONExxx
NOTE: The label must begin with ‘ CLONE ’ (not case sensitive), optionally followed by up to 6 unaccented alphanumeric characters (a...z, A...Z, 0...9).
2 Select if you want to clone the Users Rights . Refer to the Clone Management
of the web server.
6
Remove power from the controller.
Insert the prepared SD card in the controller.
Restore power to the controller.
Result: The clone procedure starts automatically. During the clone procedure, the PWR and I/O LEDs are ON and the SD LED flashes regularly.
NOTE: The clone procedure lasts 2 or 3 minutes.
Result: At the end of the clone procedure, the SD LED is ON and the controller starts in normal application mode. If an error was detected, the ERR LED is ON and the controller is in STOPPED state.
Remove the SD card from the controller.
This procedure describes how to download the application stored in the SD card to your target controller:
Step
1
2
3
4
5
Action
Remove power from the controller.
Insert the SD card into the controller.
Restore power to the controller.
Result: The download procedure starts and the SD LED is flashing during this procedure.
Wait until the end of the download:
• If the SD LED (green) is ON, and the ERR LED (red) flashes regularly, the download ended successfully.
• If the SD LED (green) is OFF, and the ERR and I/O LEDs (red) flash regularly, an error is detected.
Remove the SD card to restart the controller.
NOTE: If you wish to control access to the cloned application in the target controller, you will need to enable and establish user access-rights, and any
Web Server/FTP passwords, which are controller-specific. For more details about Access Rights, refer to the EcoStruxure Machine Expert Programming
Guide.
NOTE: Downloading a cloned application to the controller will first remove the existing application from controller memory, regardless of any user accessrights that may be enabled in the target controller.
EIO0000003089.05
169
Script and Files Generation with Mass Storage
Click Project > Mass Storage (USB or SDCard) in the main menu:
Element
New
Open
Macros
Generate
Command
Source
Destination
Add New
Move Up/
Down
Delete
Description
Create a new script.
Open a script.
Insert a Macro.
A macro is a sequence of unitary commands. A macro helps to perform many common operations such as upload application, download application, and so on.
Generate the script and all necessary files on the SD card.
Basic instructions.
Source file path on the PC or the controller.
Destination directory on the PC or the controller.
Add a script command.
Change the script commands order.
Delete a script command.
170 EIO0000003089.05
Command
Download
SetNodeName
Upload
Delete
Reboot
Commands descriptions:
Description
Downloads a file from the
SD card to the controller.
Source
Select the file to download.
Sets the node name of the controller.
Resets the node name of the controller.
Uploads files contained in a controller directory to the
SD card.
Deletes files contained in a controller directory.
NOTE: Delete "*" does not delete system files.
Removes the UserRights from the controller.
Deletes the files contained in the SD card or a folder of the SD card
New node name.
Default node name.
Select the directory.
Select the directory and enter a specific file name
Important: by default, all directory files are selected.
-
-
Destination
Select the controller destination directory.
Controller node name
Controller node name
-
-
-
-
Syntax
’Download “/usr/Cfg/
*”’
’SetNodeName “Name_
PLC”’
’SetNodeName “”’
’Upload “/usr/*”’
’Delete “/usr/SysLog/
*”’
’Delete “/usr/*”’
’Delete “/sd0/*”’ or
’Delete “/sd0/folder name”’
’Reboot’ Restarts the controller (only available at the end of the script).
-
NOTE: When User Rights are activated on a controller and if the user is not allowed to read/write/delete file system, scripts used to Upload / Download /
Delete files are disabled. It includes the clone operation.
This table describes the macros:
Macros
Download App
Upload App
Description
Download the application from the SD card to the controller.
Upload the application from the controller to the SD card.
Directory/Files
/usr/App/*.app
/usr/App/*.crc
/usr/App/*.map
/usr/App/*.conf
(1)
Download Sources
Upload Sources
Download Multi-files
Download the project archive from the SD card to the controller.
Upload the project archive from the controller to the SD card.
Download multiple files from the SD card to a controller directory.
Upload Log Upload the log files from the controller to the
SD card.
(1) If
is configured.
/usr/App/*.prj
Defined by user
/usr/Log/*.log
Reset the User Rights to Default
You can manually create a script to remove the user rights, along with the application, from the controller. This script must contain this command:
Format “/usr/”
Reboot
NOTE: This command also removes user application and data.
EIO0000003089.05
171
Step Action
1 Remove power from the controller.
2
3
Insert the prepared SD card in the source controller.
Restore power to the source controller.
4
5
Result: The operation starts automatically. During the operation, the PWR and I/O LEDs are ON and the SD LED flashes regularly.
Wait until the operation is completed.
Result:
• The SD LED is ON if the operation is successful.
• The ERR LED is ON and the controller does not start if an error is detected.
Remove the SD card from the controller.
NOTE: The controller reboots with the default user rights.
Transfer Procedure
WARNING
UNINTENDED EQUIPMENT OPERATION
• You must have operational knowledge of your machine or process before connecting this device to your controller.
• Ensure that guards are in place so that any potential unintended equipment operation will not cause injury to personnel or damage to equipment.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Step Action
1 Create the script with the Mass Storage (USB or SDCard) editor.
2
3
4
5
Click Generate...
and select the SD card root directory.
Result : The script and files are transferred on the SD card.
Insert the SD card into the controller.
Result: The transfer procedure starts and the SD LED is flashing during this procedure.
Wait until the end of the download:
• If the SD LED (green) is ON, and the ERR LED (red) flashes regularly, the download ended successfully.
• If the SD LED (green) is OFF, and the ERR and I/O LEDs (red) flash regularly, an error is detected.
Remove the SD card from the controller.
NOTE: Changes will be applied after next restart.
When the controller has executed the script, the result is logged on the SD card
(file /sys/cmd/Cmd.log
).
WARNING
UNINTENDED EQUIPMENT OPERATION
Consult the controller state and behavior diagram in this document to understand the state that will be assumed by the controller after you cycle power.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
172 EIO0000003089.05
Firmware Management
Overview
The firmware update for the controller and the expansion modules are available on the Schneider Electric website (in .zip or seco format).
Updating Modicon M251 Logic Controller Firmware
Introduction
Updating the firmware is possible by:
• Using an SD card with a compatible script file
• Using the Controller Assistant
Performing a firmware update deletes the application program in the device, including the configuration files, the user management, the user rights, the certificates and the Boot Application in non-volatile memory.
NOTICE
LOSS OF APPLICATION DATA
• Perform a backup of the application program to the hard disk of the PC before attempting a firmware update.
• Restore the application program to the device after a successful firmware update.
Failure to follow these instructions can result in equipment damage.
If you remove power to the device, or there is a power outage or communication interruption during the transfer of the application, your device may become inoperative. If a communication interruption or a power outage occurs, reattempt the transfer. If there is a power outage or communication interruption during a firmware update, or if an invalid firmware is used, your device will become inoperative. In this case, use a valid firmware and reattempt the firmware update.
NOTICE
INOPERABLE EQUIPMENT
• Do not interrupt the transfer of the application program or a firmware change once the transfer has begun.
• Re-initiate the transfer if the transfer is interrupted for any reason.
• Do not attempt to place the device into service until the file transfer has completed successfully.
Failure to follow these instructions can result in equipment damage.
The serial line ports of your controller are configured for the Machine Expert protocol by default when new or when you update the controller firmware. The
Machine Expert protocol is incompatible with that of other protocols such as
Modbus Serial Line. Connecting a new controller to, or updating the firmware of a controller connected to, an active Modbus configured serial line can cause the other devices on the serial line to stop communicating. Make sure that the controller is not connected to an active Modbus serial line network before first downloading a valid application having the concerned port or ports properly configured for the intended protocol.
EIO0000003089.05
173
NOTICE
INTERRUPTION OF SERIAL LINE COMMUNICATIONS
Be sure that your application has the serial line ports properly configured for
Modbus before physically connecting the controller to an operational Modbus
Serial Line network.
Failure to follow these instructions can result in equipment damage.
Updating Firmware by SD Card
Follow these steps to update the firmware by an SD card:
Step
1
2
3
4
5
6
Action
Extract the .zip file to the root of the SD card.
NOTE: The SD card folder \sys\cmd\ contains the download script file.
Remove power from the controller.
Insert the SD card into the controller.
Restore power to the controller.
NOTE: The SD LED (green) is flashing during the operation.
Wait until the end of the download:
• If the SD LED (green) is ON, and the ERR LED (red) flashes regularly, the download ended successfully.
• If the SD LED (green) is OFF, and the ERR and I/O LEDs (red) flash regularly, an error is detected.
Remove the SD card from the controller.
Result : The controller restarts automatically with new firmware if the download ended successfully.
Updating Firmware by Controller Assistant
To update the firmware, you must open the Controller Assistant . Click Tools >
External Tools > Open Controller Assistant .
174 EIO0000003089.05
To execute a complete firmware update of a controller without replacing the Boot application and data, proceed as follows:
Step
1
2
3
4
5
6
Action
On the Home dialog box, click the Read from...
controller button.
Result : The Controller selection dialog box opens.
Select the required connection type and controller and click the Reading button.
Result : The image is transmitted from the controller to the computer.
After this has been accomplished successfully, you are automatically redirected to the
Home dialog box.
Click the button New / Process...
and then Update firmware...
.
Result : The dialog box for updating the firmware opens.
Execute individual steps for updating the firmware in the current image (Changes are only effected in the image on your computer).
In the final step, you can decide whether you want to create a backup copy of the image read by the controller.
Result : Following the update of the firmware, you are automatically returned to the
Home dialog box.
On the Home dialog box, click the Write on....
controller button.
Result : The Controller selection dialog box opens.
Select the required connection type and controller and click the Write button.
Result : The image is transmitted from your computer to the controller.
After the transmission, you are automatically returned to the Home dialog box.
For more information about the firmware update and creating a new flash disk with firmware, refer to Project Settings - Firmware Update and
.
Updating TM3 Expansion Modules Firmware
Downloading Firmware to TM3 Expansion Modules
The firmware can be updated in:
• TM3XHSC202 and TM3XHSC202G
• TM3D• with firmware version (SV) ≥ 2.0, except TM3DM16R and TM3DM32R
• TM3A• and TM3T• with firmware version (SV) ≥ 2.0
NOTE: The firmware version (SV) is found on the packaging and product labels.
Firmware updates are performed if, during a power on, at least one firmware file is present in the /usr/TM3fwupdate/ directory of controller. You can download the file(s) to the controller using the SD card, an FTP file transfer or through
EcoStruxure Machine Expert.
The controller updates the firmware of the TM3 expansion modules on the I/O bus, including those that are:
• Connected remotely, using a TM3 Transmitter/Receiver module.
• In configurations comprising a mix of TM3 and TM2 expansion modules.
EIO0000003089.05
175
4
5
6
7
Step
1
2
3
8
9
10
11
12
The following table describes how to download firmware to one or more TM3 expansion modules using an SD card:
Action
Insert an empty SD card into the PC.
Create the folder path /sys/Cmd and create a file called Script.cmd
.
Edit the file and insert the following command for each firmware file you wish to transfer to the controller:
Download "usr/TM3fwupdate/<filename>"
Create the folder path /usr/TM3fwupdate/ in the SD card root directory and copy the firmware files to the TM3fwupdate folder.
Ensure that power is removed from controller.
Remove the SD card from the PC and insert it into the SD card slot of the controller.
Restore power to the controller. Wait until the end of the operation (until the SD LED is green ON).
Result: The controller begins transferring the firmware file(s) from the SD card to the /usr/TM3fwupdate in the controller.
During this operation, the SD LED on the controller is flashing. A SCRIPT.log
file is created on the SD card and contains the result of the file transfer. If an error is detected, the SD and ERR LEDs flash and the detected error is logged in
SCRIPT.log
file.
Remove power from the controller.
Remove SD card from the controller.
Restore power to the controller.
Result: The controller transfers the firmware file(s) to the appropriate TM3 I/O module(s).
NOTE: The TM3 update process adds approximately 15 seconds to the controller boot duration.
Verify in the message logger of the controller that the firmware is successfully updated: Your TM3 Module X successfully updated . X corresponds to the position of the module on the bus.
NOTE: You can also obtain the logger information in the PlcLog.txt
file in the /usr/Syslog/ directory of the controller file system.
NOTE: If the controller encounters an error during the update, the update terminates with that module.
If all targeted modules were successfully updated, delete the firmware file(s) from /usr/TM3fwupdate/ folder on the controller.
You can delete the files directly using EcoStruxure Machine Expert or by creating and executing a script containing the following command:
Delete "usr/TM3fwupdate/*"
NOTE: If a targeted module was not updated successfully, or there are no message logger messages for all the targeted modules, see the
below.
Recovery Procedure
If you remove power to the device, or there is a power outage or communication interruption during the transfer of the application, your device may become inoperative. If a communication interruption or a power outage occurs, reattempt the transfer. If there is a power outage or communication interruption during a firmware update, or if an invalid firmware is used, your device will become inoperative. In this case, use a valid firmware and reattempt the firmware update.
NOTICE
INOPERABLE EQUIPMENT
• Do not interrupt the transfer of the application program or a firmware change once the transfer has begun.
• Re-initiate the transfer if the transfer is interrupted for any reason.
• Do not attempt to place the device into service until the file transfer has completed successfully.
Failure to follow these instructions can result in equipment damage.
176 EIO0000003089.05
Step
1
2
3
4
5
6
7
8
9
10
If, during the reattempted firmware update, the update prematurely terminates with an error, it means that the communication interruption or power outage had damaged the firmware of one of your modules in your configuration, and that module must be reinitialized.
NOTE: Once the firmware update process detects an error with the firmware in the destination module, the update process is terminated. After you have reinitialized the damaged module following the recovery procedure, any modules that followed the damaged module remain unchanged and will need to have their firmware updated.
The following table describes how to reinitialize the firmware on TM3 expansion modules:
Action
Ensure that the correct firmware is present in the /usr/TM3fwupdate/ directory of the controller.
Remove power from the controller.
Disassemble from the controller all TM3 expansion modules that are functioning normally, up to the first module to recover.
Refer to the hardware guides of the modules for disassembly instructions.
Apply power to the controller.
NOTE: The TM3 update process adds approximately 15 seconds to the controller boot duration.
Verify in the message logger of the controller that the firmware is successfully updated: Your TM3 Module X successfully updated . X corresponds to the position of the module on the bus.
Remove power from the controller.
Reassemble the TM3 expansion module configuration to the controller. Refer to the hardware guides of the modules for assembly instructions.
Restore power to the controller.
Result: The controller transfers the firmware file(s) to the appropriate and yet to be updated TM3 I/O module(s).
NOTE: The TM3 update process adds approximately 15 seconds to the controller boot duration.
Verify in the message logger of the controller that the firmware is successfully updated: Your TM3 Module X successfully updated . X corresponds to the position of the module on the bus.
NOTE: You can also obtain the logger information in the Sys.log
file in the /usr/Log directory of the controller file system.
Delete the firmware file(s) from /usr/TM3fwupdate/ folder on the controller.
EIO0000003089.05
177
Compatibility
Software and Firmware Compatibilities
EcoStruxure Machine Expert Compatibility and Migration
Software and Firmware compatibilities are described in the EcoStruxure Machine
Expert Compatibility and Migration User Guide.
178 EIO0000003089.05
Appendices
What’s in This Part
How to Change the IP Address of the Controller.............................................. 180
Functions to Get/Set Serial Line Configuration in User Program....................... 182
Overview
This appendix lists the documents necessary for technical understanding of the
Modicon M251 Logic Controller Programming Guide.
EIO0000003089.05
179
How to Change the IP Address of the Controller
How to Change the IP Address of the Controller
What’s in This Chapter
changeIPAddress: Change the IP address of the controller............................. 180
changeIPAddress: Change the IP address of the controller
Function Block Description
The changeIPAddress function block provides the capability to change dynamically a controller IP address, its subnet mask and its gateway address. The function block can also save the IP address so that it is used in subsequent reboots of the controller.
NOTE: Changing the IP addresses is only possible if the IP mode is configured to fixed IP address . For more details, refer to
.
NOTE: For more information on the function block, use the Documentation tab of EcoStruxure Machine Expert Library Manager Editor. For the use of this editor, refer to EcoStruxure Machine Expert Functions and Libraries User
Guide.
Graphical Representation
Parameter Description
Input xExecute xSave eChannel i_abyIPAddress i_abyIPMask i_abyIPGateway
Type
BOOL
BOOL changeIPAddress_
Channel
ARRAY[0..3] OF BYTE
ARRAY[0..3] OF BYTE
ARRAY[0..3] OF BYTE
Comment
• Rising edge: action starts.
• Falling edge: resets outputs. If a falling edge occurs before the function block has completed its action, the outputs operate in the usual manner and are only reset if either the action is completed or in the event that an error is detected. In this case, the corresponding output values ( xDone , xError , iError ) are present at the outputs for exactly one cycle.
TRUE: save configuration for subsequent reboots of the controller.
The input eChannel is the Ethernet port to be configured. Depending on the number of the ports available on the controller in changeIPAddress_Channel
(0 or 1).See
changeIPAddress_Channel : Ethernet port to be configured, page 181 .
The new IP Address to be configured. Format: 0.0.0.0.
NOTE: If this input is set to 0.0.0.0 then the controller
is configured.
The new subnet mask. Format: 0.0.0.0
The new gateway IP address. Format: 0.0.0.0
180 EIO0000003089.05
How to Change the IP Address of the Controller
Output xDone xBusy xError eError xSaved q_abyIPAddress q_abyIPMask q_abyIPGateway
Type
BOOL
BOOL
BOOL changeIPAddress_
Error
BOOL
ARRAY[0..3] OF BYTE
ARRAY[0..3] OF BYTE
ARRAY[0..3] OF BYTE
Comment
TRUE: if IP Addresses have been successfully configured or if default IP
Addresses have been successfully configured because input i_abyIPAddress is set to 0.0.0.0.
Function block active.
• TRUE: error detected, function block aborts action.
• FALSE: no error has been detected.
Error code of the detected error, page 181 .
Configuration saved for the subsequent reboots of the controller.
Current controller IP address. Format: 0.0.0.0.
Current subnet mask. Format: 0.0.0.0.
Current gateway IP address. Format: 0.0.0.0.
changeIPAddress_Channel : Ethernet port to be configured
Enumerator
CHANNEL_ETHERNET_NETWORK
CHANNEL_DEVICE_NETWORK
The changeIPAddress_Channel enumeration data type contains the following values:
Value
0
1
Description
M241, M251MESC, M258, LMC058, LMC078: Ethernet port
M251MESE: Ethernet_2 port
M241: TM4ES4 Ethernet port
M251MESE: Ethernet_1 port
changeIPAddress_Error : Error Codes
Enumerator
ERR_NO_ERROR
ERR_UNKNOWN
ERR_INVALID_MODE
ERR_INVALID_IP
ERR_DUPLICATE_IP
ERR_WRONG_CHANNEL
ERR_IP_BEING_SET
ERR_SAVING
ERR_DHCP_SERVER
The changeIPAddress_Error enumeration data type contains the following values:
Value
00 hex
01 hex
02 hex
03 hex
04 hex
05 hex
06 hex
07 hex
08 hex
Description
No error detected.
Internal error detected.
IP address is not configured as a fixed IP address.
Invalid IP address.
The new IP address is already used in the network.
Incorrect Ethernet communication port.
IP address is already being changed.
IP addresses not saved due to a detected error or no non-volatile memory present.
A DHCP server is configured on this Ethernet communication port.
EIO0000003089.05
181
Functions to Get/Set Serial Line Configuration in User
Functions to Get/Set Serial Line Configuration in
User Program
What’s in This Chapter
GetSerialConf: Get the Serial Line Configuration ........................................... 182
SetSerialConf: Change the Serial Line Configuration ..................................... 183
SERIAL_CONF: Structure of the Serial Line Configuration Data Type ............. 185
Overview
This section describes the functions to get/set the serial line configuration in your program.
To use these functions, add the M2xx Communication library.
For further information on adding a library, refer to the EcoStruxure Machine
Expert Programming Guide.
GetSerialConf: Get the Serial Line Configuration
Function Description
GetSerialConf returns the configuration parameters for a specific serial line communication port.
Graphical Representation
Parameter Description
Input
Link
PointerToSerialConf
Type
LinkNumber (see
EcoStruxure Machine
Expert, Modbus and
ASCII Read/Write
Functions,
PLCCommunication
Library Guide)
Comment
Link is the communication port number.
PointerToSerialConf is the address of the configuration structure (variable of SERIAL_CONF type) in which the configuration parameters are stored. The
ADR standard function must be used to define the associated pointer. (See the example below.)
Output
GetSerialConf
Type
WORD
Comment
This function returns:
• 0: The configuration parameters are returned
• 255: The configuration parameters are not returned because:
◦ the function was not successful
◦ the function is in progress
182 EIO0000003089.05
Functions to Get/Set Serial Line Configuration in User
Example
Refer to the
example.
SetSerialConf: Change the Serial Line Configuration
Function Description
SetSerialConf is used to change the serial line configuration.
Graphical Representation
NOTE: Changing the configuration of the Serial Line(s) port(s) during programming execution can interrupt ongoing communications with other connected devices.
WARNING
LOSS OF CONTROL DUE TO CONFIGURATION CHANGE
Validate and test all the parameters of the SetSerialConf function before putting your program into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Parameter Description
Input
Link
PointerToSerialConf
Type
LinkNumber (see
EcoStruxure Machine
Expert, Modbus and
ASCII Read/Write
Functions,
PLCCommunication
Library Guide)
Output
SetSerialConf
Type
WORD
Comment
LinkNumber is the communication port number.
PointerToSerialConf is the address of the configuration structure (variable of SERIAL_CONF type) in which the new configuration parameters are stored.
The ADR standard function must be used to define the associated pointer. (See the example below.) If 0, set the application default configuration to the serial line.
Comment
This function returns:
• 0: The new configuration is set
• 255: The new configuration is refused because:
◦ the function is in progress
◦ the input parameters are not valid
EIO0000003089.05
183
Example
Functions to Get/Set Serial Line Configuration in User
VAR
MySerialConf: SERIAL_CONF result: WORD;
END_VAR
(*Get current configuration of serial line 1*)
GetSerialConf(1, ADR(MySerialConf));
(*Change to modbus RTU slave address 9*)
MySerialConf.Protocol := 0; (*Modbus RTU/Machine
Expert protocol (in this case CodesysCompliant selects the protocol)*)
MySerialConf.CodesysCompliant := 0; (*Modbus RTU*)
MySerialConf.address := 9; (*Set modbus address to
9*)
(*Reconfigure the serial line 1*) result := SetSerialConf(1, ADR(MySerialConf));
184 EIO0000003089.05
Functions to Get/Set Serial Line Configuration in User
SERIAL_CONF: Structure of the Serial Line Configuration
Data Type
Structure Description
Variable
Bauds
InterframeDelay
FrameReceivedTimeout
FrameLengthReceived
Protocol
Address
Parity
Rs485
ModPol (polarization resistor)
DataFormat
StopBit
CharFrameStart
CharFrameEnd1
CharFrameEnd2
CodesysCompliant
CodesysNetType
The SERIAL_CONF structure contains configuration information about the serial line port. It contains these variables:
Type
DWORD
WORD
WORD
WORD
BYTE
BYTE
BYTE
BYTE
BYTE
BYTE
BYTE
BYTE
BYTE
BYTE
BYTE
BYTE
Description baud rate minimum time (in ms) between 2 frames in Modbus (RTU, ASCII)
In the ASCII protocol, FrameReceivedTimeout allows the system to conclude the end of a frame at reception after a silence of the specified number of ms. If 0 this parameter is not used.
In the ASCII protocol, FrameLengthReceived allows the system to conclude the end of a frame at reception, when the controller received the specified number of characters. If 0, this parameter is not used.
0: Modbus RTU or Machine Expert (see CodesysCompliant )
1: Modbus ASCII
2: ASCII
Modbus address 0 to 255 (0 for Master)
0: none
1: odd
2: even
0: RS232
1: RS485
0: no
1: yes
7 bits or 8 bits
1: 1 stop bit
2: 2 stop bits
In the ASCII protocol, 0 means there is no start character in the frame. Otherwise, the corresponding ASCII character is used to detect the beginning of a frame in receiving mode. In sending mode, this character is added at the beginning of the user frame.
In the ASCII protocol, 0 means there is no end character in the frame. Otherwise, the corresponding ASCII character is used to detect the end of a frame in receiving mode. In sending mode, this character is added at the end of the user frame.
In the ASCII protocol, 0 means there is no second end character in the frame.
Otherwise, the corresponding ASCII character is used (along with
CharFrameEnd1 ) to detect the end of a frame in receiving mode. In sending mode, this character is added at the end of the user frame.
0: Modbus RTU
1: Machine Expert (when Protocol = 0) not used
EIO0000003089.05
185
Controller Performance
What’s in This Chapter
This chapter provides information about the Modicon M251 Logic Controller processing performance.
Processing Performance
Introduction
This chapter provides information about the M251 processing performance.
Logic Processing
This table presents logic processing performance for various logical instructions:
IL Instruction Type
Addition/subtraction/multiplication of INT
Addition/subtraction/multiplication of DINT
Addition/subtraction/multiplication of REAL
Division of REAL
Operation on BOOLEAN, for example, Status:= Status and value
LD INT + ST INT
LD DINT + ST DINT
LD REAL + ST REAL
64 μs
49 μs
50 μs
Duration for 1000 Instructions
42 μs
41 μs
336 μs
678 μs
75 μs
Communication and System Processing Time
The communication processing time varies, depending on the number of sent/ received requests.
186 EIO0000003089.05
Glossary
EIO0000003089.05
A
analog output:
Converts numerical values within the logic controller and sends out proportional voltage or current levels.
application source:
The collection of human-readable controller instructions, configuration data, HMI instructions, symbols, and other program documentation. The application source file is saved on the PC and you can download the application source file to most logic controllers. The application source file is used to build the executable program that runs in the logic controller.
application:
A program including configuration data, symbols, and documentation.
ARP:
( address resolution protocol ) An IP network layer protocol for Ethernet that maps an IP address to a MAC (hardware) address.
ASIC:
( application specific integrated circuit ) A silicon processor (chip) custom designed especially for an application.
B
BCD:
( binary coded decimal ) The format that represents decimal numbers between 0 and 9 with a set of 4 bits (a nybble/nibble, also titled as half byte). In this format, the 4 bits used to encode decimal numbers have an unused range of combinations.
For example, the number 2,450 is encoded as 0010 0100 0101 0000 .
BOOL:
( boolean ) A basic data type in computing. A BOOL variable can have one of these values: 0 ( FALSE ), 1 ( TRUE ). A bit that is extracted from a word is of type BOOL ; for example, %MW10.4
is a fifth bit of memory word number 10.
Boot application:
( boot application ) The binary file that contains the application. Usually, it is stored in the controller and allows the controller to boot on the application that the user has generated.
BOOTP:
( bootstrap protocol ) A UDP network protocol that can be used by a network client to automatically obtain an IP address (and possibly other data) from a server. The client identifies itself to the server using the client MAC address. The server, which maintains a pre-configured table of client device MAC addresses and associated IP addresses, sends the client its pre-configured IP address. BOOTP was originally used as a method that enabled diskless hosts to be remotely booted over a network. The BOOTP process assigns an infinite lease of an IP address. The BOOTP service utilizes UDP ports 67 and 68.
byte:
A type that is encoded in an 8-bit format, ranging from 00 hex to FF hex.
187
188
C
CFC:
( continuous function chart ) A graphical programming language (an extension of the IEC 61131-3 standard) based on the function block diagram language that works like a flowchart. However, no networks are used and free positioning of graphic elements is possible, which allows feedback loops. For each block, the inputs are on the left and the outputs on the right. You can link the block outputs to the inputs of other blocks to create complex expressions.
configuration:
The arrangement and interconnection of hardware components within a system and the hardware and software parameters that determine the operating characteristics of the system.
continuous function chart language:
A graphical programming language (an extension of the IEC61131-3 standard) based on the function block diagram language that works like a flowchart.
However, no networks are used and free positioning of graphic elements is possible, which allows feedback loops. For each block, the inputs are on the left and the outputs on the right. You can link the block outputs to inputs of other blocks to create complex expressions.
control network:
A network containing logic controllers, SCADA systems, PCs, HMI, switches, ...
Two kinds of topologies are supported:
• flat: all modules and devices in this network belong to same subnet.
• 2 levels: the network is split into an operation network and an inter-controller network.
These two networks can be physically independent, but are generally linked by a routing device.
controller:
Automates industrial processes (also known as programmable logic controller or programmable controller).
CRC:
( cyclical redundancy check ) A method used to determine the validity of a communication transmission. The transmission contains a bit field that constitutes a checksum. The message is used to calculate the checksum by the transmitter according to the content of the message. Receiving nodes, then recalculate the field in the same manner. Any discrepancy in the value of the 2 CRC calculations indicates that the transmitted message and the received message are different.
cyclic task:
The cyclic scan time has a fixed duration (interval) specified by the user. If the current scan time is shorter than the cyclic scan time, the controller waits until the cyclic scan time has elapsed before starting a new scan.
D
data log:
The controller logs events relative to the user application in a data log .
device network:
A network that contains devices connected to a specific communication port of a logic controller. This controller is seen as a master from the devices point of view.
EIO0000003089.05
EIO0000003089.05
DHCP:
( dynamic host configuration protocol ) An advanced extension of BOOTP. DHCP is more advanced, but both DHCP and BOOTP are common. (DHCP can handle
BOOTP client requests.)
DINT:
( double integer type ) Encoded in 32-bit format.
DNS:
( domain name system ) The naming system for computers and devices connected to a LAN or the Internet.
DTM:
( device type manager ) Classified into 2 categories:
• Device DTMs connect to the field device configuration components.
• CommDTMs connect to the software communication components.
The DTM provides a unified structure for accessing device parameters and configuring, operating, and diagnosing the devices. DTMs can range from a simple graphical user interface for setting device parameters to a highly sophisticated application capable of performing complex real-time calculations for diagnosis and maintenance purposes.
DWORD:
( double word ) Encoded in 32-bit format.
E
EDS:
( electronic data sheet ) A file for fieldbus device description that contains, for example, the properties of a device such as parameters and settings.
equipment:
A part of a machine including sub-assemblies such as conveyors, turntables, and so on.
Ethernet:
A physical and data link layer technology for LANs, also known as IEEE 802.3.
expansion bus:
An electronic communication bus between expansion I/O modules and a controller or bus coupler.
F
FBD:
( function block diagram ) One of 5 languages for logic or control supported by the standard IEC 61131-3 for control systems. Function block diagram is a graphically oriented programming language. It works with a list of networks, where each network contains a graphical structure of boxes and connection lines, which represents either a logical or arithmetic expression, the call of a function block, a jump, or a return instruction.
189
190
FE:
(functional Earth ) A common grounding connection to enhance or otherwise allow normal operation of electrically sensitive equipment (also referred to as functional ground in North America).
In contrast to a protective Earth (protective ground), a functional earth connection serves a purpose other than shock protection, and may normally carry current.
Examples of devices that use functional earth connections include surge suppressors and electromagnetic interference filters, certain antennas, and measurement instruments.
firmware:
Represents the BIOS, data parameters, and programming instructions that constitute the operating system on a controller. The firmware is stored in nonvolatile memory within the controller.
freewheeling:
When a logic controller is in freewheeling scan mode, a new task scan starts as soon as the previous scan has been completed. Contrast with periodic scan mode .
FTP:
( file transfer protocol ) A standard network protocol built on a client-server architecture to exchange and manipulate files over TCP/IP based networks regardless of their size.
H
HE10:
Rectangular connector for electrical signals with frequencies below 3 MHz, complying with IEC 60807-2.
I
I/O:
( input/output )
ICMP:
( Internet control message protocol ) Reports errors detected and provides information related to datagram processing.
IEC 61131-3:
Part 3 of a 3-part IEC standard for industrial automation equipment. IEC 61131-3 is concerned with controller programming languages and defines 2 graphical and
2 textual programming language standards. The graphical programming languages are ladder diagram and function block diagram. The textual programming languages include structured text and instruction list.
IEC:
( international electrotechnical commission ) A non-profit and non-governmental international standards organization that prepares and publishes international standards for electrical, electronic, and related technologies.
IL:
( instruction list ) A program written in the language that is composed of a series of text-based instructions executed sequentially by the controller. Each instruction includes a line number, an instruction code, and an operand (refer to IEC 61131-
3).
EIO0000003089.05
EIO0000003089.05
instruction list language:
A program written in the instruction list language that is composed of a series of text-based instructions executed sequentially by the controller. Each instruction includes a line number, an instruction code, and an operand (see IEC 61131-3).
INT:
( integer ) A whole number encoded in 16 bits.
IP:
( Internet protocol Part of the TCP/IP protocol family that tracks the Internet addresses of devices, routes outgoing messages, and recognizes incoming messages.
K
KeepAlive:
Messages sent by the OPC UA server to keep a subscription active. This is necessary when none of the monitored items of data have been updated since the previous publication.
L
ladder diagram language:
A graphical representation of the instructions of a controller program with symbols for contacts, coils, and blocks in a series of rungs executed sequentially by a controller (see IEC 61131-3).
LD:
( ladder diagram ) A graphical representation of the instructions of a controller program with symbols for contacts, coils, and blocks in a series of rungs executed sequentially by a controller (refer to IEC 61131-3).
LED:
( light emitting diode ) An indicator that illuminates under a low-level electrical charge.
LINT:
( long integer ) A whole number encoded in a 64-bit format (4 times INT or 2 times
DINT ).
LRC:
( longitudinal redundancy checking ) An error-detection method for determining the correctness of transmitted and stored data.
LREAL:
( long real ) A floating-point number encoded in a 64-bit format.
LWORD:
( long word ) A data type encoded in a 64-bit format.
M
MAC address:
( media access control address ) A unique 48-bit number associated with a specific piece of hardware. The MAC address is programmed into each network card or device when it is manufactured.
191
192
MAST:
A processor task that is run through its programming software. The MAST task has 2 sections:
• IN: Inputs are copied to the IN section before execution of the MAST task.
• OUT: Outputs are copied to the OUT section after execution of the MAST task.
MDT:
NOTE:
( master data telegram ) On Sercos bus, an MDT telegram is sent by the master once during each transmission cycle to transmit data (command values) to the servo drives (slaves).
MIB:
( management information base ) An object database that is monitored by a network management system like SNMP. SNMP monitors devices are defined by their MIBs. Schneider Electric has obtained a private MIB, groupeschneider
(3833).
monitored items:
In OPC UA, the items of data (samples) made available by the OPC UA server that clients subscribe to.
MSB:
( most significant bit/byte The part of a number, address, or field that is written as the left-most single value in conventional hexadecimal or binary notation.
ms:
( millisecond )
%MW:
According to the IEC standard, %MW represents a memory word register (for example, a language object of type memory word).
N
network:
A system of interconnected devices that share a common data path and protocol for communications.
NMT:
( network management ) CANopen protocols that provide services for network initialization, detected error control, and device status control.
node:
An addressable device on a communication network.
notifications:
In OPC UA, messages sent by the OPC UA server to inform clients that new items of data are available.
NVM:
( Non-volatile memory ) A non-volatile memory that can be overwritten. It is stored on a special EEPROM that can be erased and reprogrammed.
EIO0000003089.05
EIO0000003089.05
O
OS:
( operating system ) A collection of software that manages computer hardware resources and provides common services for computer programs.
P
PCI:
( peripheral component interconnect ) An industry-standard bus for attaching peripherals.
PDO:
( process data object ) An unconfirmed broadcast message or sent from a producer device to a consumer device in a CAN-based network. The transmit
PDO from the producer device has a specific identifier that corresponds to the receive PDO of the consumer devices.
PE:
( Protective Earth ) A common grounding connection to help avoid the hazard of electric shock by keeping any exposed conductive surface of a device at earth potential. To avoid possible voltage drop, no current is allowed to flow in this conductor (also referred to as protective ground in North America or as an equipment grounding conductor in the US national electrical code).
post configuration:
( post configuration ) An option that allows to modify some parameters of the application without changing the application. Post configuration parameters are defined in a file that is stored in the controller. They are overloading the configuration parameters of the application.
program:
The component of an application that consists of compiled source code capable of being installed in the memory of a logic controller.
protocol:
A convention or standard definition that controls or enables the connection, communication, and data transfer between 2 computing system and devices.
publishing interval:
In OPC UA, the frequency at which the OPC_UA server sends notifications to clients informing them that data updates are available.
R
REAL:
A data type that is defined as a floating-point number encoded in a 32-bit format.
RJ45:
A standard type of 8-pin connector for network cables defined for Ethernet.
RPDO:
( receive process data object ) An unconfirmed broadcast message or sent from a producer device to a consumer device in a CAN-based network. The transmit
PDO from the producer device has a specific identifier that corresponds to the receive PDO of the consumer devices.
193
194
RPI:
( requested packet interval) The time period between cyclic data exchanges requested by the scanner. EtherNet/IP devices publish data at the rate specified by the RPI assigned to them by the scanner, and they receive message requests from the scanner with a period equal to RPI.
RSTP:
( rapid spanning tree protocol ) A high-speed network protocol that builds a loopfree logical topology for Ethernet networks.
RTC:
( real-time clock ) A battery-backed time-of-day and calender clock that operates continuously, even when the controller is not powered for the life of the battery.
RTP:
( real-time process ) The real-time process is the most important system task. It is responsible for executing all real-time tasks at the correct time. Real-time processing is triggered by the Sercos real-time bus cycle.
run:
A command that causes the controller to scan the application program, read the physical inputs, and write to the physical outputs according to solution of the logic of the program.
S
sampling rate:
In OPC UA, the frequency at which the OPC UA server reads items of data from connected devices.
scan:
A function that includes:
• reading inputs and placing the values in memory
• executing the application program 1 instruction at a time and storing the results in memory
• using the results to update outputs
SDO:
( service data object ) A message used by the field bus master to access (read/ write) the object directories of network nodes in CAN-based networks. SDO types include service SDOs (SSDOs) and client SDOs (CSDOs).
SFC:
( sequential function chart ) A language that is composed of steps with associated actions, transitions with associated logic condition, and directed links between steps and transitions. (The SFC standard is defined in IEC 848. It is IEC 61131-3 compliant.)
SINT:
( signed integer ) A 15-bit value plus sign.
SNMP:
( simple network management protocol ) A protocol that can control a network remotely by polling the devices for their status and viewing information related to data transmission. You can also use it to manage software and databases remotely. The protocol also permits active management tasks, such as modifying and applying a new configuration.
STOP:
A command that causes the controller to stop running an application program.
EIO0000003089.05
EIO0000003089.05
string:
A variable that is a series of ASCII characters.
ST:
( structured text ) A language that includes complex statements and nested instructions (such as iteration loops, conditional executions, or functions). ST is compliant with IEC 61131-3.
symbol:
A string of a maximum of 32 alphanumeric characters, of which the first character is alphabetic. It allows you to personalize a controller object to facilitate the maintainability of the application.
system variable:
A variable that provides controller data and diagnostic information and allows sending commands to the controller.
T
task:
A group of sections and subroutines, executed cyclically or periodically for the
MAST task or periodically for the FAST task.
A task possesses a level of priority and is linked to inputs and outputs of the controller. These I/O are refreshed in relation to the task.
A controller can have several tasks.
NOTE:
TCP:
( transmission control protocol ) A connection-based transport layer protocol that provides a simultaneous bi-directional transmission of data. TCP is part of the
TCP/IP protocol suite.
terminal block:
( terminal block ) The component that mounts in an electronic module and provides electrical connections between the controller and the field devices.
TPDO:
( transmit process data object ) An unconfirmed broadcast message or sent from a producer device to a consumer device in a CAN-based network. The transmit
PDO from the producer device has a specific identifier that corresponds to the receive PDO of the consumer devices.
U
UDINT:
( unsigned double integer ) Encoded in 32 bits.
UDP:
( user datagram protocol ) A connectionless mode protocol (defined by IETF RFC
768) in which messages are delivered in a datagram (data telegram) to a destination computer on an IP network. The UDP protocol is typically bundled with the Internet protocol. UDP/IP messages do not expect a response, and are therefore ideal for applications in which dropped packets do not require retransmission (such as streaming video and networks that demand real-time performance).
UINT:
( unsigned integer ) Encoded in 16 bits.
195
V
variable:
A memory unit that is addressed and modified by a program.
W
watchdog:
A watchdog is a special timer used to ensure that programs do not overrun their allocated scan time. The watchdog timer is usually set to a higher value than the scan time and reset to 0 at the end of each scan cycle. If the watchdog timer reaches the preset value, for example, because the program is caught in an endless loop, an error is declared and the program stopped.
WORD:
A type encoded in a 16-bit format.
196 EIO0000003089.05
Index
getting the serial line configuration .................... 182
A
ASCII Manager ................................................... 134
H
Hardware Initialization Values.................................42
C
changeModbusPort
ControlChannel ................................................... 143
Enables or disables a communication channel ... 143
Controller Configuration
Communication Settings.....................................54
PLC Settings .....................................................55
Services ............................................................56
cyclic data exchanges, generating EDS file for.........95
I
I/O bus configuration .............................................71
I/O configuration general information
general practices ...............................................68
Industrial Ethernet
overview.......................................................... 125
IP address
changeIPAddress............................................. 180
J
J1939
creating ECU for .............................................. 149
interface configuration ...................................... 148
D
DHCP server ...................................................... 128
Download application ............................................49
K
KeepAlive (OPC UA) ........................................... 151
KeepAlive interval (OPC UA)................................ 153
E
ECU, creating for J1939....................................... 149
EDS file, generating...............................................95
Enables or disables a communication channel
ControlChannel................................................ 143
Ethernet
changeIPAddress function block........................ 180
FTP Server........................................................92
Modbus TCP Client/Server .................................81
Modbus TCP slave device ................................ 112
Services ............................................................75
SNMP ...............................................................93
Web server........................................................82
EtherNet
EtherNet/IP device .............................................94
ExecuteScript example ........................................ 116
External Event ......................................................32
L
libraries ................................................................17
Libraries
FTPRemoteFileHandling ....................................93
M
M2•• communication
GetSerialConf.................................................. 182
SetSerialConf .................................................. 183
Memory Mapping ..................................................19
Modbus
Protocols ...........................................................81
Modbus Ioscanner............................................... 136
Modbus Manager ................................................ 131
Modbus TCP Client/Server
Ethernet ............................................................81
Modbus TCP port, changing ................................. 116
monitored items (OPC UA)................................... 151
F
Fast Device Replacement .................................... 128
features
key features.......................................................13
file transfer with SD card ...................................... 167
firewall
script commands.............................................. 121
firmware
downloading to TM3 expansion modules ........... 175
FTP client .............................................................93
FTP Server
Ethernet ............................................................92
FTPRemoteFileHandling library..............................93
O
OPC UA server
configuration.................................................... 152
KeepAlive interval ............................................ 153
overview.......................................................... 151
Output Behavior ....................................................42
Output Forcing ......................................................42
G
GetSerialConf
EIO0000003089.05
P
197
Example.......................................................... 161
file management .............................................. 159
IP address ....................................................... 158
IP configuration mode ...................................... 158
programming languages
IL, LD, grafcet ....................................................13
protocols
SNMP ...............................................................93
Protocols ..............................................................75
IP......................................................................77
Modbus .............................................................81
publishing interval (OPC UA).........................151, 153
Watchdogs ........................................................32
TM3 analog I/O modules
downloading firmware to................................... 175
U
updating the firmware of TM3 expansion
modules............................................................ 175
W
Web server
Ethernet ............................................................82
R
Reboot .................................................................48
Remanent variables ..............................................51
Reset cold ............................................................45
Reset origin ..........................................................45
Reset origin device ................................................46
Reset warm ..........................................................44
Run command ......................................................43
S
sampling interval (OPC UA) ..........................151, 153
script commands
firewall ............................................................ 121
script file
syntax rules ..................................................... 167
SD card
commands ...................................................... 167
serial line
ASCII Manager ................................................ 134
GetSerialConf.................................................. 182
Modbus Manager ............................................. 131
SetSerialConf .................................................. 183
SERIAL_CONF ................................................... 185
SNMP
Ethernet ............................................................93
protocols ...........................................................93
Software Initialization Values ..................................42
State diagram .......................................................35
Stop command......................................................43
symbols (OPC UA) .............................................. 154
T
Task
Cyclic task .........................................................30
Event task .........................................................31
External Event Task ...........................................32
Freewheeling task..............................................31
Types................................................................30
198 EIO0000003089.05
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00 www.se.com
As standards, specifications, and design change from time to time, please ask for confirmation of the information given in this publication.
© 2022 Schneider Electric . All rights reserved.
EIO0000003089.05
Modicon M251
Logic Controller
System Functions and Variables
PLCSystem Library Guide
EIO0000003095.03
10/2021 www.se.com
Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its subsidiaries referred to in this guide are the property of Schneider Electric SE or its subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and furnished for informational use only. No part of this guide may be reproduced or transmitted in any form or by any means (electronic, mechanical, photocopying, recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide or its content, except for a non-exclusive and personal license to consult it on an "as is" basis. Schneider Electric products and equipment should be installed, operated, serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational content of this material or consequences arising out of or resulting from the use of the information contained herein.
As part of a group of responsible, inclusive companies, we are updating our communications that contain non-inclusive terminology. Until we complete this process, however, our content may still contain standardized industry terms that may be deemed inappropriate by our customers.
© 2021 Schneider Electric. All rights reserved
System Functions and Variables
Table of Contents
EIO0000003095.03
M251 System Variables.............................................................................10
System Variables: Definition and Use ...................................................10
Understanding System Variables....................................................10
Using System Variables ................................................................. 11
PLC_R and PLC_W Structures ............................................................12
PLC_R : Controller Read-Only System Variables..............................13
PLC_W : Controller Read/Write System Variables ............................15
SERIAL_R and SERIAL_W Structures .................................................15
SERIAL_R[0...1] : Serial Line Read-Only System Variables ...............15
SERIAL_W[0...1] : Serial Line Read/Write System Variables .............16
ETH_R and ETH_W Structures............................................................17
ETH_R : Ethernet Port Read-Only System Variables ........................18
ETH_W : Ethernet Port Read/Write System Variables .......................20
TM3_MODULE_R Structure ................................................................20
TM3_MODULE_R[0...13] : TM3 Modules Read-Only System
Variables ......................................................................................20
TM3_BUS_W Structure .......................................................................21
TM3_BUS_W : TM3 Bus System Variables ......................................21
PROFIBUS_R Structure ......................................................................21
PROFIBUS_R : PROFIBUS Read-Only System Variables.................21
M251 System Functions............................................................................23
M251 Read Functions .........................................................................23
GetRtc : Get Real Time Clock .........................................................23
IsFirstMastColdCycle : Indicate if this Cycle is the First MAST
Cold Start Cycle ............................................................................23
IsFirstMastCycle : Indicate if this Cycle is the First MAST
Cycle............................................................................................24
IsFirstMastWarmCycle : Indicate if this Cycle is the First MAST
Warm Start Cycle .........................................................................25
M251 Write Functions .........................................................................26
InhibitBatLed : Enables or Disable the Battery Led............................26
SetRTCDrift : Set Compensation Value to the RTC ...........................26
M251 User Functions ..........................................................................28
FB_ControlClone : Clone the Controller ...........................................28
DataFileCopy : Copy File Commands ..............................................29
ExecuteScript : Run Script Commands ............................................31
M251 Disk Space Functions ................................................................32
FC_GetFreeDiskSpace : Gets the Free Memory Space ....................32
FC_GetLabel : Gets the Label of Memory ........................................33
FC_GetTotalDiskSpace : Gets the Size of Memory ...........................33
TM3 Read Functions ...........................................................................34
TM3_GetModuleBusStatus : Get TM3 Module Bus Status.................34
TM3_GetModuleFWVersion : Get TM3 Module Firmware
Version.........................................................................................35
TM3_GetModuleInternalStatus : Get TM3 Module Internal
Status ..........................................................................................36
3
System Functions and Variables
4
M251 PLCSystem Library Data Types ........................................................38
PLC_RW System Variables Data Types................................................38
PLC_R_APPLICATION_ERROR : Detected Application Error
Status Codes ................................................................................39
PLC_R_BOOT_PROJECT_STATUS : Boot Project Status
Codes ..........................................................................................40
PLC_R_IO_STATUS : I/O Status Codes ..........................................40
PLC_R_SDCARD_STATUS : SD Card Slot Status Codes .................40
PLC_R_STATUS : Controller Status Codes......................................41
PLC_R_STOP_CAUSE : From RUN State to Other State
Transition Cause Codes ................................................................42
PLC_R_TERMINAL_PORT_STATUS : Programming Port
Connection Status Codes ..............................................................43
PLC_R_TM3_BUS_STATE : TM3 Bus Status Codes ........................43
PLC_W_COMMAND : Control Command Codes..............................43
DataFileCopy System Variables Data Types .........................................43
DataFileCopyError : Detected Error Codes ......................................44
DataFileCopyLocation : Location Codes ..........................................44
ExecScript System Variables Data Types..............................................44
ExecuteScriptError : Detected Error Codes ......................................44
ETH_RW System Variables Data Types................................................45
ETH_R_FRAME_PROTOCOL : Frame Transmission Protocol
Codes ..........................................................................................45
ETH_R_IP_MODE : IP Address Source Codes.................................45
ETH_R_PORT_DUPLEX_STATUS : Transmission Mode
Codes ..........................................................................................45
ETH_R_PORT_IP_STATUS : Ethernet TCP/IP Port Status
Codes ..........................................................................................46
ETH_R_PORT_LINK_STATUS : Communication Link Status
Codes ..........................................................................................46
ETH_R_PORT_SPEED : Communication Speed of the Ethernet
Port Codes ...................................................................................46
ETH_R_RUN_IDLE : Ethernet/IP Run and Idle States Codes ............46
TM3_MODULE_RW System Variables Data Types ...............................46
TM3_ERR_CODE : TM3 Expansion Module Detected Error
Codes ..........................................................................................47
TM3_MODULE_R_ARRAY_TYPE : TM3 Expansion Module Read
Array Type ....................................................................................47
TM3_MODULE_STATE : TM3 Expansion Module State
Codes ..........................................................................................47
TM3_BUS_W_IOBUSERRMOD : TM3 bus error mode .....................47
System Function Data Types ...............................................................48
RTCSETDRIFT_ERROR : SetRTCDrift Function Detected Error
Codes ..........................................................................................48
Appendices
................................................................................................49
Function and Function Block Representation .............................................50
Differences Between a Function and a Function Block ...........................50
How to Use a Function or a Function Block in IL Language ....................51
How to Use a Function or a Function Block in ST Language ...................53
Glossary
EIO0000003095.03
System Functions and Variables
Index
EIO0000003095.03
5
Safety Information
System Functions and Variables
Important Information
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
!
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
!
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
!
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
Please Note
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and its installation, and has received safety training to recognize and avoid the hazards involved.
EIO0000003095.03
7
8
System Functions and Variables
About the Book
Document Scope
This document acquaints you with the system functions and variables offered within the Modicon M251 Logic Controller. The M251 PLCSystem library contains functions and variables to get information from and send commands to the controller system.
This document describes the data type functions and variables of the M251
PLCSystem library.
The following knowledge is required:
• Basic information on the functionality, structure, and configuration of the
M251 Logic Controller
• Programming in the FBD, LD, ST, IL, or CFC language
• System variables (global variables)
Validity Note
This document has been updated for the release of EcoStruxure TM Machine
Expert V2.0.1.
Related Documents
Title of Documentation
EcoStruxure Machine Expert Programming
Guide
Reference Number
EIO0000002854 (ENG) ;
EIO0000002855 (FRE) ;
EIO0000002856 (GER) ;
EIO0000002858 (SPA) ;
EIO0000002857 (ITA) ;
EIO0000002859 (CHS)
Modicon M251 Logic Controller Hardware Guide EIO0000003101 (ENG) ;
EIO0000003102 (FRE) ;
EIO0000003103 (GER) ;
EIO0000003104 (SPA) ;
EIO0000003105 (ITA) ;
EIO0000003106 (CHS)
Modicon M251 Logic Controller Programming
Guide
EIO0000003089 (ENG) ;
EIO0000003090 (FRE) ;
EIO0000003091 (GER) ;
EIO0000003092 (SPA) ;
EIO0000003093 (ITA) ;
EIO0000003094 (CHS)
You can download these technical publications and other technical information from our website at www.se.com/ww/en/download/ .
EIO0000003095.03
Product Related Information
System Functions and Variables
WARNING
LOSS OF CONTROL
• The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical control functions, provide a means to achieve a safe state during and after a path failure. Examples of critical control functions are emergency stop and overtravel stop, power outage and restart.
• Separate or redundant control paths must be provided for critical control functions.
• System control paths may include communication links. Consideration must be given to the implications of unanticipated transmission delays or failures of the link.
• Observe all accident prevention regulations and local safety guidelines.
1
• Each implementation of this equipment must be individually and thoroughly tested for proper operation before being placed into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
1 For additional information, refer to NEMA ICS 1.1 (latest edition), "Safety
Guidelines for the Application, Installation, and Maintenance of Solid State
Control" and to NEMA ICS 7.1 (latest edition), "Safety Standards for Construction and Guide for Selection, Installation and Operation of Adjustable-Speed Drive
Systems" or their equivalent governing your particular location.
WARNING
UNINTENDED EQUIPMENT OPERATION
• Only use software approved by Schneider Electric for use with this equipment.
• Update your application program every time you change the physical hardware configuration.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
EIO0000003095.03
9
System Functions and Variables
M251 System Variables
Overview
This chapter:
• gives an
introduction to the system variables, page 10
•
describes the system variables, page 13
included with the M251 PLCSystem library
System Variables: Definition and Use
Overview
This section defines system variables and how to implement them in the Modicon
M251 Logic Controller.
Understanding System Variables
Introduction
This section describes how system variables are implemented. System variables:
• allow you to access general system information, perform system diagnostics, and command simple actions.
• are structured variables conforming to IEC 61131-3 definitions and naming conventions. You can access the system variables using the IEC symbolic name PLC_GVL . Some of the PLC_GVL variables are read-only (for example, PLC_R ) and some are read/write (for example, PLC_W ).
• are automatically declared as global variables. They have system-wide scope and can be accessed by any Program Organization Unit (POU) in any task.
Naming Convention
The system variables are identified by:
• a structure name that represents the category of system variable. For example, PLC_R represents a structure name of read-only variables used for the controller diagnostic.
• a set of component names that identifies the purpose of the variable. For example, i_wVendorID represents the controller vendor ID.
You can access the system variables by typing the structure name of the variables followed by the name of the component.
Here is an example of system variable implementation:
VAR myCtr_Serial : DWORD; myCtr_ID : DWORD; myCtr_FramesRx : UDINT;
END_VAR myCtr_Serial := PLC_GVL.PLC_R.i_dwSerialNumber; myCtr_ID := PLC_GVL.PLC.R.i_wVendorID; myCtr_FramesRx := SERIAL_R[0].i_udiFramesReceivedOK
NOTE: The fully-qualified name of the system variable in the example above is PLC_GVL.PLC_R
. The PLC_GVL is implicit when declaring a variable using the Input Assistant , but it may also be entered in full. Good programming practice often dictates the use of the fully-qualified variable name in declarations.
10 EIO0000003095.03
System Functions and Variables
System Variables Location
Two system variables are defined for use when programming the controller:
• located variables
• unlocated variables
They are used in EcoStruxure Machine Expert programs according to the structure_name.component_name
convention explained previously. %MW addresses from 0 to 59999 can be accessed directly. Addresses greater than this are considered out of range by EcoStruxure Machine Expert and can only be accessed through the structure_name.component_name
convention.
The located variables:
• have a fixed location in a static %MW area: %MW60000 to %MW60199 for read-only system variables.
• are accessible through Modbus TCP, Modbus serial, and EtherNet/IP requests both in RUNNING and STOPPED states.
The unlocated variables:
• are not physically located in the %MW area.
• are not accessible through any fieldbus or network requests unless you locate them in the relocation table, and only then these variables can be accessed in
RUNNING and STOPPED states. The relocation table uses the following dynamic %MW areas:
◦ %MW60200 to %MW61999 for read-only variables
◦ %MW62200 to %MW63999 for read/write variables
Using System Variables
Introduction
This section describes the steps required to program and to use system variables in EcoStruxure Machine Expert.
System variables are global in the application scope, and you can use them in all the Program Organization Units (POUs) of the application.
System variables do not need to be declared in the Global Variable List (GVL).
They are automatically declared from the controller system library.
EIO0000003095.03
11
System Functions and Variables
Using System Variables in a POU
EcoStruxure Machine Expert has an auto-completion feature. In a POU , start by entering the system variable structure name ( PLC_R , PLC_W ...) followed by a dot. The system variables are displayed in the Input Assistant . You can select the desired variable or enter the full name manually.
NOTE: In the example above, after you type the structure name PLC_R.
,
EcoStruxure Machine Expert offers a pop-up menu of possible component names/variables.
Example
The following example shows the use of some system variables:
VAR myCtr_Serial : DWORD; myCtr_ID : WORD; myCtr_FramesRx : UDINT;
END_VAR myCtr_Serial := PLC_R.i_dwSerialNumber; myCtr_ID := PLC_R.i_wVendorID; myCtr_FramesRx := SERIAL_R[0].i_udiFramesReceivedOK;
PLC_R and PLC_W Structures
Overview
This section lists and describes the different system variables included in the
PLC_R and PLC_W structures.
12 EIO0000003095.03
System Functions and Variables
PLC_R
: Controller Read-Only System Variables
Variable Name
Variable Structure
This table describes the parameters of the PLC_R system variable ( PLC_R_
STRUCT type):
Type Comment Modbus
Address (1)
60000 i_wVendorID
60001
60002
60004
60006
60008
60010
60012
60013
60014
60015
60016
60025
60026 i_wProductID i_dwSerialNumber i_byFirmVersion i_byBootVersion i_dwHardVersion i_dwChipVersion i_wStatus i_wBootProjectStatus i_wLastStopCause i_wLastApplicationError i_lwSystemFault_1 i_wIOStatus2 i_wClockBatterystatus
WORD
WORD
DWORD
ARRAY[0..3] OF
BYTE
ARRAY[0..3] OF
BYTE
Controller Vendor ID.
101A hex = Schneider Electric
Controller Reference ID.
NOTE: Vendor ID and Reference ID are the components of the Target ID of the controller displayed in the communication settings view
(Target ID = 101A XXXX hex).
Controller Serial Number
Controller Firmware Version [aa.bb.cc.dd] :
• i_byFirmVersion[0] = aa
• ...
• i_byFirmVersion[3] = dd
Controller Boot Version [aa.bb.cc.dd] :
• i_byBootVersion[0] = aa
• ...
• i_byBootVersion[3] = dd
Controller Hardware Version.
Controller Coprocessor Version.
State of the controller.
DWORD
DWORD
LWORD
Returns information about the boot application stored in non-volatile memory.
Cause of the last transition from RUN
Cause of the last controller exception.
to another state.
Bit field FFFF FFFF FFFF FFFF hex indicates no error detected.
A bit at low level means that an error has been detected:
• bit 0 = Reserved
• bit 1 = TM3 error detected
• bit 2 = Ethernet IF1 error detected
• bit 3 = Ethernet IF2 error detected
• bit 4 = Reserved
• bit 5 = Reserved
• bit 6 = CAN 1 error detected
• bit 7 = Reserved
• bit 8 = Reserved
• bit 9 = TM4 error detected
• bit 10 = SD Card error detected
• bit 11 = Firewall error detected
• bit 12 = DHCP server error detected
• bit 13 = OPC UA server error detected
TM3 I/O status.
WORD Status of the battery of the RTC:
• 0 = Battery change needed
• 100 = Battery fully charged
Other values (1...99) represents the percentage of charge. For example, if the value is 75, it represents that the battery charge is 75%.
EIO0000003095.03
13
System Functions and Variables
Modbus
Address (1)
60028
Variable Name i_dwAppliSignature1
60030 i_dwAppliSignature2 n/a n/a n/a n/a n/a
60032
60034 i_dwAppliSignature3 i_dwAppliSignature4 i_sVendorName i_sProductRef i_sNodeName i_dwLastStopTime i_dwLastPowerOffDate n/a n/a n/a n/a n/a n/a n/a i_uiEventsCounter i_wTerminalPortStatus i_wSdCardStatus i_wUsrFreeFileHdl i_udiUsrFsTotalBytes i_udiUsrFsFreeBytes i_uiTM3BusState n/a n/a n/a i_ExpertIO_RunStop_Input i_x10msClk i_x100msClk
14
Type Comment
DWORD
DWORD
DWORD
DWORD
First DWORD of 4 DWORD signature (16 bytes total).
The application signature is generated by the software during build.
Second DWORD of 4 DWORD signature (16 bytes total).
The application signature is generated by the software during build.
Third DWORD of 4 DWORD signature (16 bytes total).
The application signature is generated by the software during build.
Fourth DWORD of 4 DWORD signature (16 bytes total).
STRING(31)
STRING(31)
STRING(99)
DWORD
DWORD
UINT
WORD
The application signature is generated by the software during build.
Name of the vendor: “Schneider Electric”.
Reference of the controller.
Node name on EcoStruxure Machine Expert Network.
The time of the last detected STOP in seconds beginning with January 1, 1970 at 00:00 UTC.
The date and time of the last detected power off in seconds beginning with January 1, 1970 at 00:00 UTC.
NOTE: Convert this value into date and time by using the function SysTimeRtcConvertUtcToDate .
For more information about Time and Date conversion, refer to the Systime Library Guide (see
EcoStruxure Machine Expert, Getting & Setting
Real Time Clock, SysTimeRtc and SysTimeCore
Library Guide).
Reserved
Status of the USB Programming Port (USB Mini-B).
Status of the SD card.
UDINT
UDINT
BYTE
BOOL
BOOL
Number of available File Handles.
A File Handle is the resource allocated by the system when you open a file.
User FileSystem total memory size (in bytes).
It is the size of the non-volatile memory for the directory
/usr/ .
User FileSystem free memory size (in bytes).
TM3 bus state.
i_uiTM3BusState can have the following values:
• 1: TM3_CONF_ERROR
Configuration mismatch between physical configuration and EcoStruxure Machine Expert configuration.
• 3: TM3_OK
Physical configuration matches EcoStruxure
Machine Expert configuration.
• 4: TM3_POWER_SUPPLY_ERROR
TM3 bus is not powered (for example when the
Logic Controller is powered by USB).
Reserved
TimeBase bit of 10 ms.
This variable is toggling On/Off with period = 10 ms. The value toggles when the logic controller is in Stop and in
Run state.
TimeBase bit of 100 ms.
This variable is toggling On/Off with period = 100 ms.
The value toggles when the logic controller is in Stop and in Run state.
EIO0000003095.03
System Functions and Variables
Modbus
Address (1) n/a
Variable Name i_x1sClk
Type
BOOL
Comment
TimeBase bit of 1 s.
This variable is toggling On/Off with period = 1 s. The value toggles when the logic controller is in Stop and in
Run state.
(1) means that the Modbus Address is not accessible through the application.
n/a means there is no pre-defined Modbus address mapping for this system variable.
PLC_W
: Controller Read/Write System Variables
Variable Structure
This table describes the parameters of the PLC_W system variable ( PLC_W_
STRUCT type):
%MW n/a n/a n/a
Variable Name q_wResetCounterEvent q_uiOpenPLCControl q_wPLCControl
Type
WORD
UINT
Comment
Transition from 0 to 1 resets the events counter ( PLC_
R.i_uiEventsCounter
).
To reset the counter again, it is necessary to write 0 to this variable before another transition from 0 to 1 can take place.
When the value of the variable passes from 0 to 6699, the command previously written in the following PLC_W.
q_wPLCControl is executed.
Controller RUN / STOP command executed when the system variable PLC_W.q_uiOpenPLCControl
value passes from 0 to 6699.
n/a means that there is no pre-defined %MW mapping for this system variable
SERIAL_R and SERIAL_W Structures
Overview
This section lists and describes the different system variables included in the
SERIAL_R and SERIAL_W structures.
SERIAL_R[0...1]
: Serial Line Read-Only System Variables
Introduction
SERIAL_R is an array of two SERIAL_R_STRUCT type. Each element of the array returns diagnostic system variables for the corresponding serial line.
For the M251 Logic Controller:
• Serial_R[0] refers to serial line
• Serial_R[1] is reserved
EIO0000003095.03
15
System Functions and Variables
Variable Structure
This table describes the parameters of the SERIAL_R[0...1] system variables:
%MW
Serial Line n/a n/a n/a
Variable Name i_udiFramesTransmittedOK i_udiFramesReceivedOK i_udiRX_MessagesError
Type
UDINT
UDINT
UINT
Comment
Number of frames successfully transmitted.
Number of frames received without any errors detected.
Number of frames received with errors detected
(checksum, parity).
Modbus Specific n/a i_uiSlaveExceptionCount n/a i_udiSlaveMsgCount
UINT
UINT
Number of Modbus exception responses returned by the logic controller.
Number of messages received from the Master and addressed to the logic controller.
n/a n/a n/a i_uiSlaveNoRespCount i_uiSlaveNakCount i_uiSlaveBusyCount
UINT
UINT
UINT
Number of Modbus broadcast requests received by the logic controller.
Not used
Not used n/a i_uiCharOverrunCount UINT Number of character overruns.
n/a means that there is no predefined %MW mapping for this system variable
Not used means that the variable is not maintained by the system, and that if the value of the variable is non-zero, it should be considered extraneous
The SERIAL_R counters are reset on:
• Download.
• Controller reset.
• SERIAL_W[x].q_wResetCounter
command.
• Reset command by Modbus request function code number 8.
SERIAL_W[0...1]
: Serial Line Read/Write System Variables
Introduction
SERIAL_W is an array of two SERIAL_W_STRUCT type. Each element of the array resets the SERIAL_R system variables for the corresponding serial line to be reset.
For the M251 Logic Controller:
• Serial_W[0] refers to serial line
• Serial_W[1] is reserved
%MW n/a
Variable Name q_wResetCounter
Variable Structure
This table describes the parameters of the SERIAL_W[0...1] system variable:
Type
WORD
Comment
Transition from 0 to 1 resets all SERIAL_R[0...1] counters.
To reset the counters again, it is necessary to write 0 to this variable before another transition from 0 to 1 can take place.
n/a means that there is no predefined %MW mapping for this system variable.
16 EIO0000003095.03
ETH_R and ETH_W Structures
Overview
System Functions and Variables
This section lists and describes the different system variables included in the
ETH_R and ETH_W structures.
EIO0000003095.03
17
System Functions and Variables
ETH_R
: Ethernet Port Read-Only System Variables
%MW
60050
60052
60054
60056
60059 n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a
Variable Structure
Variable Name i_byIPAddress i_bySubNetMask i_byGateway i_byMACAddress i_sDeviceName i_wIpMode i_byFDRServerIPAddress i_udiOpenTcpConnections i_udiFramesTransmittedOK i_udiFramedReceivedOK i_udiTransmitBufferErrors i_udiReceiveBufferErrors i_wFrameSendingProtocol i_wPortALinkStatus i_wPortASpeed i_udiPortACollisions i_byIPAddress_If2
This table describes the parameters of the ETH_R system variable ( ETH_R_
STRUCT type): i_wPortADuplexStatus
Type
ARRAY[0..3] OF
BYTE
ARRAY[0..3] OF
BYTE
ARRAY[0..3] OF
BYTE
ARRAY[0..5] OF
BYTE
Comment
IP address [aaa.bbb.ccc.ddd] :
• i_byIPAddress[0] = aaa
• ...
• i_byIPAddress[3] = ddd
Subnet Mask [aaa.bbb.ccc.ddd] :
• i_bySub-netMask[0] = aaa
• ...
• i_bySub-netMask[3] = ddd
Gateway address [aaa.bbb.ccc.ddd] :
• i_byGateway[0] = aaa
• ...
• i_byGateway[3] = ddd
MAC address [aa.bb.cc.dd.ee.ff] :
• i_byMACAddress[0] = aa
• ...
• i_byMACAddress[5] = ff
Name used to get IP address from server.
Method used to obtain an IP address.
STRING(15)
ARRAY[0..3] OF
BYTE
UDINT
UDINT
UDINT
UDINT
UDINT
UDINT
ARRAY[0..3] OF
BYTE
The IP address [aaa.bbb.ccc.ddd] of the DHCP or
BootP server:
• i_byFDRServerIPAddress[0] = aaa
• ...
• i_byFDRServerIPAddress[3] = ddd
Equals 0.0.0.0 if Stored IP or Default IP used.
Number of open TCP connections.
Number of frames successfully transmitted. Reset at
Power ON or with reset command ETH_W.q_
wResetCounter .
Number of frames successfully received. Reset at
Power ON or with reset command ETH_W.q_
wResetCounter .
Numbers of frames transmitted with detected errors.
Reset at Power ON or with reset command ETH_W.q_
wResetCounter .
Numbers of frames received with detected errors. Reset at Power ON or with reset command ETH_W.q_
wResetCounter .
Ethernet protocol configured for frames sending (IEEE
802.3 or Ethernet II).
Link of the Ethernet Port (0 = No Link, 1 = Link connected to another Ethernet device).
Ethernet Port network speed (10Mb/s, 100Mb/s).
Ethernet Port duplex status (0 = Half or 1 = Full duplex).
Number of frames involved in one or more collisions and subsequently transmitted successfully. Reset at Power
ON or with reset command ETH_W.q_
wResetCounter .
IP address of the Ethernet or Ethernet_2 interface
[aaa.bbb.ccc.ddd] :
• i_byIPAddress[0] = aaa
• ...
• i_byIPAddress[3] = ddd
18 EIO0000003095.03
System Functions and Variables
%MW n/a n/a n/a n/a n/a n/a n/a n/a n/a i_byGateway_If2 i_byMACAddress_If2
Modbus TCP/IP Specific n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a
Variable Name i_bySubNetMask_If2 i_sDeviceName_If2 i_wIpMode_If2 i_wPortALinkStatus_If2 i_wPortASpeed_If2 i_wPortADuplexStatus_If2 i_wPortAIpStatus_If2 i_udiModbusMessageTransmitted i_udiModbusMessageReceived i_udiModbusErrorMessage
EtherNet/IP Specific i_udiETHIP_IOMessagingTransmitted i_udiETHIP_IOMessagingReceived i_udiUCMM_Request i_udiUCMM_Error i_udiClass3_Request i_udiClass3_Error i_uiAssemblyInstanceInput
Type
ARRAY[0..3] OF
BYTE
ARRAY[0..3] OF
BYTE
ARRAY[0..3] OF
BYTE
STRING(15)
Comment
Subnet Mask of the Ethernet or Ethernet_2 interface
[aaa.bbb.ccc.ddd] :
• i_bySub-netMask[0] = aaa
• ...
• i_bySub-netMask[3] = ddd
Gateway address of the Ethernet or Ethernet_2 interface [aaa.bbb.ccc.ddd] :
• i_byGateway[0] = aaa
• ...
• i_byGateway[3] = ddd
MAC address of the Ethernet or Ethernet_2 interface
[aa.bb.cc.dd.ee.ff] :
• i_byMACAddress[0] = aa
• ...
• i_byMACAddress[5] = ff
Name used to get IP address from server.
Method used to obtain an IP address.
Link of the Ethernet Port (0 = No Link, 1 = Link connected to another Ethernet device).
Ethernet Port network speed (10Mb/s or 100Mb/s).
Ethernet Port duplex status:
• 0: Half
• 1: Full duplex
Ethernet TCP/IP port stack status.
UDINT
UDINT
UDINT
UDINT
UDINT
UDINT
UDINT
UDINT
UDINT
UINT
Number of Modbus messages transmitted.
Reset at Power ON or with reset command ETH_W.q_
wResetCounter .
Number of Modbus messages received.
Reset at Power ON or with reset command ETH_W.q_
wResetCounter .
Modbus detected error messages transmitted and received.
Reset at Power ON or with reset command ETH_W.q_
wResetCounter .
EtherNet/IP Class 1 frames transmitted.
Reset at Power ON or with reset command ETH_W.q_
wResetCounter .
EtherNet/IP Class 1 frames received.
Reset at Power ON or with reset command ETH_W.q_
wResetCounter .
EtherNet/IP Unconnected Messages received.
Reset at Power ON or with reset command ETH_W.q_
wResetCounter .
EtherNet/IP invalid Unconnected Messages received.
Reset at Power ON or with reset command ETH_W.q_
wResetCounter .
EtherNet/IP Class 3 requests received.
Reset at Power ON or with reset command ETH_W.q_
wResetCounter .
EtherNet/IP invalid class 3 requests received.
Reset at Power ON or with reset command ETH_W.q_
wResetCounter .
Input Assembly Instance number. See the appropriate
Programming Guide of your controller for more information.
EIO0000003095.03
19
System Functions and Variables
%MW n/a n/a n/a n/a n/a n/a n/a
Variable Name i_uiAssemblyInstanceInputSize i_uiAssemblyInstanceOutput i_uiAssemblyInstanceOutputSize i_uiETHIP_ConnectionTimeouts i_ucEipRunIdle i_byMasterIpTimeouts i_byMasterIpLost
Type
UINT
UINT
UINT
UINT
BYTE
BYTE n/a i_wPortAIpStatus
n/a means that there is no predefined %MW mapping for this system variable.
Comment
Input Assembly Instance size. See the appropriate
Programming Guide of your controller for more information.
Output Assembly Instance number. See the appropriate
Programming Guide of your controller for more information.
Output Assembly Instance size. See the appropriate
Programming Guide of your controller for more information.
Number of connection timeouts. Reset at Power ON or with reset command ETH_W.q_wResetCounter
.
Run (value = 1)/Idle(value = 0) flag for EtherNet/IP class
1 connection.
Ethernet Modbus TCP Master timeout events counter.
Reset at Power ON or with reset command ETH_W.q_
wResetCounter .
Ethernet Modbus TCP Master link status: 0 = link OK, 1
= link lost.
Ethernet TCP/IP port stack status.
ETH_W
: Ethernet Port Read/Write System Variables
%MW n/a
Variable Name q_wResetCounter
Variable Structure
This table describes the parameters of the ETH_W system variable ( ETH_W_
STRUCT type):
Type
WORD
Comment
Transition from 0 to 1 resets all ETH_R counters.
To reset again, it is necessary to write 0 to this variable before another transition from 0 to 1 can take place.
n/a means that there is no predefined %MW mapping for this system variable.
TM3_MODULE_R Structure
Overview
This section lists and describes the different system variables included in the
TM3_MODULE_R structure.
TM3_MODULE_R[0...13]
: TM3 Modules Read-Only System Variables
Introduction
The TM3_MODULE_R is an array of 14 TM3_MODULE_R_STRUCT type. Each element of the array returns diagnostic system variables for the corresponding
TM3 expansion module.
For the Modicon M251 Logic Controller:
• TM3_MODULE_R[0] refers to the TM3 expansion module 0
• ...
• TM3_MODULE_R[13] refers to the TM3 expansion module 13
20 EIO0000003095.03
System Functions and Variables
Variable Structure
The following table describes the parameters of the TM3_MODULE_R[0...13] system variable:
%MW n/a
Var Name i_wProductID
Type
WORD n/a i_wModuleState
n/a means that there is no predefined %MW mapping for this system variable.
Comment
TM3 expansion module ID.
Describes the state of the TM3 module.
TM3_BUS_W Structure
Overview
This section lists and describes the different system variables included in the
TM3_BUS_W structure.
TM3_BUS_W
: TM3 Bus System Variables
Var Name q_wIOBusErrPassiv q_wIOBusRestart
Variable Structure
This table describes the parameters of the TM3_BUS_W system variable ( TM3_
BUS_W_STRUCT type):
Type Comment
TM3_BUS_W_IOBUSERRMOD When set to ERR_ACTIVE (the default), bus errors detected on TM3 expansion modules stop I/O exchanges.
TM3_BUS_W_IOBUSINIT
When set to ERR_PASSIVE , passive I/O error handing is used: the controller attempts to continue data bus exchanges.
When set to 1, restarts the I/O expansion bus. This is only necessary when q_wIOBusErrPassiv is set to ERR_ACTIVE and at least one bit of
TM3_MODULE_R[i] .i_wModuleState
is set to TM3_BUS_ERROR .
For more information, refer to I/O Configuration General Description (see Modicon
M251 Logic Controller, Programming Guide).
PROFIBUS_R Structure
PROFIBUS_R
: PROFIBUS Read-Only System Variables
Variable Structure
This table describes the parameters of the PROFIBUS_R system variable
( PROFIBUS_R_STRUCT type):
%MW n/a n/a n/a
Var Name i_wPNOIdentifier i_wBusAdr i_CommState
Type
WORD
UINT
UDINT
Comment
Slave identification code (1...126).
PROFIBUS slave address.
Value representing the state of the PROFIBUS module:
• 0x00: Undeterminable
• 0x01: Not configured
• 0x02: Stop
• 0x03: Idle
• 0x04: Operate
EIO0000003095.03
21
System Functions and Variables
%MW n/a
Var Name i_CommError
Type
UDINT n/a i_ErrorCount UDINT n/a means that there is no predefined %MW mapping for this system variable.
Comment
If the value is non-zero, a communication error was detected by the Profibus Module indicated by an error code (see TM4 Expansion Modules - Programming
Guide).
Communication error counter.
22 EIO0000003095.03
M251 System Functions
Overview
System Functions and Variables
This chapter describes the system functions included in the M251 PLCSystem library.
M251 Read Functions
Overview
This section describes the read functions included in the M251 PLCSystem library.
GetRtc
: Get Real Time Clock
Function Description
This function returns RTC time in seconds in UNIX format (time expired in seconds since January 1, 1970 at 00:00 UTC).
Graphical Representation
IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter
Function and Function Block Representation , page 50 .
I/O Variable Description
The following table describes the I/O variable:
Output
GetRtc
Type
DINT
Comment
RTC in seconds in UNIX format.
Example
The following example describes how to get the RTC value:
VAR
MyRTC : DINT := 0;
END_VAR
MyRTC := GetRtc();
IsFirstMastColdCycle
: Indicate if this Cycle is the First MAST Cold Start Cycle
Function Description
This function returns TRUE during the first MAST cycle after a cold start (first cycle after download or reset cold).
EIO0000003095.03
23
System Functions and Variables
Graphical Representation
IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter
Function and Function Block Representation , page 50
.
I/O Variable Description
The table describes the output variable:
Output
IsFirstMastColdCycle
Type
BOOL
Comment
TRUE during the first MAST task cycle after a cold start.
Example
Refer to the function
.
IsFirstMastCycle
: Indicate if this Cycle is the First MAST Cycle
Function Description
This function returns TRUE during the first MAST cycle after a start.
Graphical Representation
24
IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter
Function and Function Block Representation , page 50
.
I/O Variable Description
Output
IsFirstMastCycle
Type
BOOL
Comment
TRUE during the first MAST task cycle after a start.
Example
This example describes the three functions IsFirstMastCycle ,
IsFirstMastColdCycle and IsFirstMastWarmCycle used together.
Use this example in MAST task. Otherwise, it may run several times or possibly never (an additional task might be called several times or not called during 1
MAST task cycle):
VAR
MyIsFirstMastCycle : BOOL;
EIO0000003095.03
System Functions and Variables
MyIsFirstMastWarmCycle : BOOL;
MyIsFirstMastColdCycle : BOOL;
END_VAR
MyIsFirstMastWarmCycle := IsFirstMastWarmCycle();
MyIsFirstMastColdCycle := IsFirstMastColdCycle();
MyIsFirstMastCycle := IsFirstMastCycle();
IF (MyIsFirstMastWarmCycle) THEN
(*This is the first Mast Cycle after a Warm Start: all variables are set to their initialization values except the
Retain variables*)
(*=> initialize the needed variables so that your application runs as expected in this case*)
END_IF;
IF (MyIsFirstMastColdCycle) THEN
(*This is the first Mast Cycle after a Cold Start: all variables are set to their initialization values including the Retain Variables*)
(*=> initialize the needed variables so that your application runs as expected in this case*)
END_IF;
IF (MyIsFirstMastCycle) THEN
(*This is the first Mast Cycle after a Start, i.e. after a
Warm or Cold Start as well as STOP/RUN commands*)
(*=> initialize the needed variables so that your application runs as expected in this case*)
END_IF;
IsFirstMastWarmCycle
: Indicate if this Cycle is the First MAST Warm Start Cycle
Function Description
This function returns TRUE during the first MAST cycle after a warm start.
Graphical Representation
IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter
Function and Function Block Representation , page 50 .
I/O Variable Description
This table describes the output variable:
Output
IsFirstMastWarmCycle
Type
BOOL
Comment
TRUE during the first MAST task cycle after a warm start.
Example
Refer to the function
EIO0000003095.03
25
System Functions and Variables
M251 Write Functions
Overview
This section describes the write functions included in the M251 PLCSystem library.
InhibitBatLed
: Enables or Disable the Battery Led
Function Description
This function enables or disables the display of the battery LED indicator, regardless of its charge level.
Graphical Representation
Inhibit BOOL
InhibitBatLed
INT InhibitBatLed
IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter
Function and Function Block Representation , page 50
.
I/O Variable Description
The following table describes the input variable:
Input
Inhibit
Type
BOOL
Comment
If TRUE , disables the display of the battery
LED.
If FALSE , enables the display of the battery
LED.
The following table describes the output variable:
Output
InhibitBatLed
Type
INT
Comment
A value of 0 indicates that no error was detected while executing the function block. A non-zero indicates that an error was detected.
Example
This example describes how to disable the battery led display:
(* Disable Battery LED Information *)
SEC.InhibitBatLed(TRUE);
SetRTCDrift
: Set Compensation Value to the RTC
Function Description
This function accelerates or slows down the frequency of the RTC to give control to the application for RTC compensation, depending on the operating environment
(temperature, …). The compensation value is given in seconds per week. It can be positive (accelerate) or negative (slow down).
26 EIO0000003095.03
System Functions and Variables
NOTE: The SetRTCDrift function must be called only once. Each new call replaces the compensation value by the new one. The value is kept in the controller hardware while the RTC is powered by the main supply or by the battery. If both battery and power supply are removed, the RTC compensation value is not available.
Graphical Representation
EIO0000003095.03
IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter
Function and Function Block Representation , page 50 .
I/O Variables Description
This table describes the input parameters:
Inputs
RtcDrift
Type
SINT(-36...+73)
Comment
Correction in seconds per week (-36 ... +73).
NOTE: The parameters Day , Hour , and Minute are used only to ensure backwards compatibility.
NOTE: If the value entered for RtcDrift exceeds the limit value, the controller firmware sets the value to its maximum value.
This table describes the output variable:
Output
SetRTCDrift
Type
Comment
Returns RTC_OK (00 hex) if command is correct otherwise returns the ID code of the detected error.
Example
In this example, the function is called only once during the first MAST task cycle. It accelerates the RTC by 4 seconds a week (18 seconds a month).
VAR
MyRTCDrift : SINT (-36...+73) := 0;
MyDay : DAY_OF_WEEK;
MyHour : HOUR;
MyMinute : MINUTE;
END_VAR
IF IsFirstMastCycle() THEN
MyRTCDrift := 4;
MyDay := 0;
MyHour := 0;
MyMinute := 0;
SetRTCDrift(MyRTCDrift, MyDay, MyHour, MyMinute);
END_IF
27
System Functions and Variables
M251 User Functions
Overview
This section describes the FB_Control_Clone , DataFileCopy and ExecuteScript functions included in the M251 PLCSystem library.
FB_ControlClone
: Clone the Controller
Function Block Description
Cloning is by default possible by SD card or Controller Assistant . When user rights are enabled and the View right ExternalCmd is denied for the
ExternalMedia group, the cloning function is not allowed. In this case, the function block enables cloning functionality one time on the next controller power on.
NOTE: You can choose whether user rights are included in the clone on the
Clone Management page of the Web server (see Modicon M251 Logic
Controller, Programming Guide).
This table shows how to set the function block and the user rights:
Function block setting xEnable = 1 xEnable = 0
When user rights enabled
Cloning is allowed
Cloning is not allowed
When user rights disabled
Cloning is allowed
Cloning is not allowed
Graphical Representation
IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter
Function and Function Block Representation , page 50
.
I/O Variable Description
The following table describes the input variables:
Input xEnable
Type
BOOL
Comment
If TRUE , enables the cloning functionality one time.
If FALSE , disables the cloning functionality.
The following table describes the output variables:
Output xError
Type
UDINT
Comment
A value of 0 indicates that no error was detected while executing the function block. A non-zero indicates that an error was detected.
28 EIO0000003095.03
System Functions and Variables
DataFileCopy
: Copy File Commands
Function Block Description
This function block copies memory data to a file and vice versa. The file is located either within the internal file system or an external file system (SD card).
The DataFileCopy function block can:
• Read data from a formatted file or
• Copy data from memory to a formatted file. For further information, refer to
Non-Volatile Memory Organization (see Modicon M251 Logic Controller,
Programming Guide).
Graphical Representation
Input xExecute
Type
BOOL sFileName xRead
STRING
BOOL xSecure BOOL iLocation INT
IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter
Function and Function Block Representation , page 50 .
I/O Variable Description
This table describes the input variables:
Comment
On rising edge, starts the function block execution.
On falling edge, resets the outputs of the function block when any ongoing execution terminates.
NOTE: With the falling edge, the function continues until it concludes its execution and updates its outputs. The outputs are retained for one cycle and reset.
File name without extension (the extension .DTA
is automatically added). Use only a...z, A...Z,
0...9 alphanumeric characters.
TRUE: copy data from the file identified by sFileName to the internal memory of the controller.
FALSE: copy data from the internal memory of the controller to the file identified by sFileName .
TRUE: The MAC address is always stored in the file. Only a controller with the same MAC address can read from the file.
FALSE: Another controller with the same type of memory can read from the file.
0: the file location is /usr/DTA in internal file system.
1: the file location is /usr/DTA in external file system (SD card).
NOTE: If the file does not already exist in the directory, the file is created.
EIO0000003095.03
29
System Functions and Variables
Input uiSize dwAdd
Output xDone xBusy xError eError
Type
UINT
DWORD
Comment
Indicates the size in bytes. Maximum is 65534 bytes.
Only use addresses of variables conforming to IEC 61131-3 (variables, arrays, structures), for example:
Variable : int; uiSize := SIZEOF (Variable);
Indicates the address in the memory that the function will read from or write to.
Only use addresses of variables conforming to IEC 61131-3 (variables, arrays, structures), for example:
Variable : int; dwAdd := ADR (Variable);
WARNING
UNINTENDED EQUIPMENT OPERATION
Verify that the memory location is of the correct size and the file is of the correct type before copying the file to memory.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Type
BOOL
BOOL
BOOL
This table describes the output variables:
Comment
TRUE = indicates that the action is successfully completed.
TRUE = indicates that the function block is running.
TRUE = indicates that an error is detected and the function block aborted the action.
Indicates the type of the data file copy detected error.
NOTE: If you modify data within the memory (variables, arrays, structures) used to write the file, a CRC integrity error results.
Example
This example describes how to copy file commands:
VAR
LocalArray : ARRAY [0..29] OF BYTE; myFileName: STRING := ‘exportfile’;
EXEC_FLAG: BOOL;
DataFileCopy: DataFileCopy;
END_VAR
DataFileCopy( xExecute:= EXEC_FLAG, sFileName:= myFileName, xRead:= FALSE, xSecure:= FALSE, iLocation:= DFCL_INTERNAL, uiSize:= SIZEOF(LocalArray), dwAdd:= ADR(LocalArray), xDone=> , xBusy=> , xError=> , eError=> );
30 EIO0000003095.03
System Functions and Variables
ExecuteScript
: Run Script Commands
Function Block Description
This function block can run the following SD card script commands:
• Download
• Upload
• SetNodeName
• Delete
• Reboot
• ChangeModbusPort
For information on the required script file format, refer to Script Files for SD Cards.
Graphical Representation
Input xExecute sCmd
Output xDone xBusy xError eError
IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter
Function and Function Block Representation , page 50 .
Type
BOOL
STRING
I/O Variable Description
This table describes the input variables:
Comment
On detection of a rising edge, starts the function block execution.
On detection of a falling edge, resets the outputs of the function block when any on-going execution terminates.
NOTE: With the falling edge, the function continues until it concludes its execution and updates its outputs. The outputs are retained for one cycle and reset.
SD card script command syntax.
Simultaneous command executions are not allowed: if a command is being executed from another function block or from an SD card script then the function block queues the command and does not execute it immediately.
NOTE: An SD card script executed from an SD card is considered as being executed until the
SD card has been removed.
Type
BOOL
BOOL
BOOL
This table describes the output variables:
Comment
TRUE indicates that the action is successfully completed.
TRUE indicates that the function block is running.
TRUE indicates error detection; the function block aborts the action.
Indicates the type of the execute script detected error.
EIO0000003095.03
31
System Functions and Variables
Example
This example describes how to execute an Upload script command:
VAR
EXEC_FLAG: BOOL;
ExecuteScript: ExecuteScript;
END_VAR
ExecuteScript( xExecute:= EXEC_FLAG, sCmd:= ‘Upload "/usr/Syslog/*"’, xDone=> , xBusy=> , xError=> , eError=> );
M251 Disk Space Functions
Overview
This section describes the disk space functions included in this library.
FC_GetFreeDiskSpace
: Gets the Free Memory Space
Function Description
This function retrieves the amount of free memory space of a memory medium
(user disk, system disk, SD card) in bytes.
The name of the memory medium is transferred:
• User disk = “/usr”
• System disk = “/sys”
• SD card = “/sd0”
The free memory space of a remote device cannot be accessed. If a remote device is specified as parameter, then the function returns "-1".
Graphical Representation
32
IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter
Function and Function Block Representation , page 50
.
I/O Variable Description
This table describes the input variables:
Input i_sVolumeName iq_uliFreeDiskSpace
Data type
STRING[80]
ULINT
Description
Name of the device whose free memory space must be accessed
Free memory space in bytes
This table describes the output variables:
EIO0000003095.03
Output
FC_GetFreeDiskSpace
Data type
DINT
System Functions and Variables
Description
0: The amount of free memory space was retrieved successfully
-1: Error when attempting to access the amount of free memory. For example, an invalid device or remote device was selected
-318: Invalid parameter ( i_sVolumeName )
FC_GetLabel
: Gets the Label of Memory
Function Description
This function retrieves the label of a memory medium. If a device has no label, then an empty string is returned.
The name of the memory medium (user disk, system disk, SD card) is transferred:
• User disk = “/usr”
• System disk = “/sys”
• SD card = “/sd0”
Graphical Representation
IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter
Function and Function Block Representation , page 50 .
I/O Variable Description
This table describes the input variables:
Input i_sVolumeName iq_sLabel
Data type
STRING[80]
STRING[11]
Description
Name of the device whose label must be accessed
Label of the device
This table describes the output variables:
Output
FC_GetLabel
Data type
DINT
Description
0: The label was retrieved successfully
-1: Error when accessing the label
-318: Invalid parameter
FC_GetTotalDiskSpace
: Gets the Size of Memory
Function Description
This function retrieves the size of a memory medium (user disk, system disk, SD card) in bytes.
The name of the memory medium is transferred:
• User disk = “/usr”
EIO0000003095.03
33
System Functions and Variables
• System disk = “/sys”
• SD card = “/sd0”
The size of a remote device cannot be accessed. If a remote device is specified as parameter, then the function returns "-1".
Graphical Representation
IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter
Function and Function Block Representation , page 50
.
I/O Variable Description
This table describes the input variables:
Input i_sVolumeName iq_uliTotalDiskSpace
Data type
STRING[80]
ULINT
Description
Name of the device whose memory size must be accessed
Size of the memory medium in byte
This table describes the output variables:
Output
FC_GetTotalDiskSpace
Data type
DINT
Description
0: Size was retrieved successfully
-1: Error when reading the size
-318: At least one of the parameters is invalid
TM3 Read Functions
Overview
This section describes the TM3 read functions included in the M251 PLCSystem library.
TM3_GetModuleBusStatus
: Get TM3 Module Bus Status
Function Description
This function returns the bus status of the module. The index of the module is given as an input parameter.
Graphical Representation
34 EIO0000003095.03
System Functions and Variables
IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter
Function and Function Block Representation , page 50 .
I/O Variable Description
The following table describes the input variable:
Input
ModuleIndex
Type
BYTE
Comment
Index of the module (0 for the first expansion, 1 for the second, and so on).
The following table describes the output variable:
Output
TM3_GetModuleBusStatus
Type
Comment
Returns TM3_OK (00 hex) if command is correct otherwise returns the ID code of the detected error.
TM3_GetModuleFWVersion
: Get TM3 Module Firmware Version
Function Description
This function returns the firmware version of a specified TM3 module.
Graphical Representation
EIO0000003095.03
IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter
Function and Function Block Representation , page 50 .
I/O Variable Description
The following table describes the input variables:
Input
ModuleIndex
Type
BYTE
Comment
Index of the module (0 for the first expansion, 1 for the second, and so on).
The following table describes the output variable:
Output
TM3_GetModuleFWVersion
Type
UINT
Comment
Returns the firmware version of the module, or FFFF hex if the information cannot be read.
For example, 001A hex indicates firmware version 26.
35
System Functions and Variables
TM3_GetModuleInternalStatus
: Get TM3 Module Internal Status
Function Description
This function selectively reads the I/O channel status of a TM3 analog or temperature module, indicated by ModuleIndex . The function block writes the status for each requested channel starting at the memory location pointed to by pStatusBuffer .
NOTE: This function block is intended to be used with analog and temperature
I/O modules. To get status information for digital I/O modules, see
.
Graphical Representation
IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter
Function and Function Block Representation , page 50
.
I/O Variable Description
Each analog/temperature I/O channel of the requested module requires one byte of memory. If there is not sufficient memory allocated to the buffer for the number of I/O module channel statuses requested, it is possible that the function will overwrite memory allocated for other purposes, or perhaps attempt to overwrite a restricted area of memory.
WARNING
UNINTENDED EQUIPMENT OPERATION
Ensure that pStatusBuffer is pointing to a memory area that has been sufficiently allocated for the number of channels to be read.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
The following table describes the input variables:
Input
ModuleIndex
StatusOffset
StatusSize pStatusBuffer
Type
BYTE
Comment
Index of the expansion module (0 for the module closest to the controller, 1 for the second closest, and so on)
BYTE
BYTE
Offset of the first status to be read in the status table.
Number of bytes to be read in the status table.
POINTER TO BYTE Buffer containing the read status table.
The following table describes the output variable:
36 EIO0000003095.03
System Functions and Variables
Output
TM3_GetModuleInternalStatus
Type
Comment
Returns TM3_NO_ERR (00 hex) if command is correct otherwise returns the ID code of the error. For the purposes of this function block, any returned value other than zero indicates that the module is not compatible with the status request, or that the module has other communication issues.
Example
The following examples describe how to get the module internal status:
VAR
TM3AQ2_Channel_0_Output_Status: BYTE;
END_VAR
TM3AQ2 is on position 1
Status of channel 0 is at offset 0
We read 1 channel
TM3_GetModuleInternalStatus(1, 0, 1, ADR(TM3AQ2_Channel_0_
Output_Status)); status of channel 0 is in TM3AQ2_Channel_0_Output_Status
TM3AQ2 module (2 outputs)
Getting the status of first output QW0
• StatusOffset = 0 (0 inputs x 2)
• StatusSize = 1 (1 status to read)
• pStatusBuffer needs to be at least 1 byte
VAR
TM3AM6_Channels_1_2_Input_Status: ARRAY[1..2] OF BYTE;
END_VAR
TM3AM6 is on position 1
Status of channel 1 is at offset 9
We read 2 consecutive channels
TM3_GetModuleInternalStatus(1, 9, 2, ADR(TM3AM6_Channels_1_
2_Input_Status)); status of channel 1 is in TM3AM6_Channels_1_2_Input_Status
[1] status of channel 2 is in TM3AM6_Channels_1_2_Input_Status
[2]
TM3AM6 module (4 inputs, 2 outputs)
Getting the status of input IW1 & IW2 (IW0 being the first one)
• StatusOffset = 9 (4 inputs x 2 + 1 to skip IW0 status)
• StatusSize = 2 (2 statuses to read)
• pStatusBuffer needs to be at least 2 bytes
EIO0000003095.03
37
System Functions and Variables
M251 PLCSystem Library Data Types
M251 PLCSystem Library Data Types
Overview
This chapter describes the data types of the M251 PLCSystem Library.
There are 2 kinds of data types available:
• System variable data types are used by the
of the
M251 PLCSystem Library ( PLC_R , PLC_W ,...).
• System function data types are used by the read/write
of the M251 PLCSystem Library.
PLC_RW System Variables Data Types
Overview
This section lists and describes the system variable data types included in the
PLC_R and PLC_W structures.
38 EIO0000003095.03
M251 PLCSystem Library Data Types
System Functions and Variables
PLC_R_APPLICATION_ERROR
: Detected Application Error Status Codes
Enumerator
PLC_R_APP_ERR_UNKNOWN
PLC_R_APP_ERR_NOEXCEPTION
PLC_R_APP_ERR_WATCHDOG
PLC_R_APP_ERR_
HARDWAREWATCHDOG
PLC_R_APP_ERR_DIVIDE_REAL_BY_
ZERO
PLC_R_APP_ERR_EXPIO_EVENTS_
COUNT_EXCEEDED
PLC_R_APP_ERR_APPLICATION_
VERSION_MISMATCH
Enumerated Type Description
The PLC_R_APPLICATION_ERROR enumeration data type contains the following values:
PLC_R_APP_ERR_IO_CONFIG_ERROR
PLC_R_APP_ERR_UNRESOLVED_
EXTREFS
PLC_R_APP_ERR_IEC_TASK_CONFIG_
ERROR
PLC_R_APP_ERR_ACCESS_VIOLATION
PLC_R_APP_ERR_DIVIDE_BY_ZERO
PLC_R_APP_ERR_PROCESSORLOAD_
WATCHDOG
Value
FFFF hex
0000 hex
0010 hex
0011 hex
0012 hex
0018 hex
0025 hex
PLC_R_APP_ERR_ILLEGAL_INSTRUCTION 0050 hex
0051 hex
0102 hex
0105 hex
0152 hex
4E20 hex
4E21 hex
Comment
Undefined error detected.
No error detected.
Task watchdog expired.
System watchdog expired.
Incorrect I/O configuration parameters detected.
Undefined functions detected.
Incorrect Task configuration parameters detected.
Undefined instruction detected.
Attempted access to reserved memory area.
Integer division by zero detected.
Processor overloaded by Application
Tasks.
Real division by zero detected.
Too many events on expert I/Os are detected.
Mismatch in the application version detected.
What to do
Contact your Schneider Electric service representative.
–
Check your application. A reset is needed to enter Run mode.
If the problem is reproducible, verify that there are no configured but disconnected communication ports. If the problem persists, update the firmware. Otherwise, contact your Schneider Electric service representative.
Your application might be corrupted. To resolve this issue, use one of the methods:
1.
Build > Clean All
2. Export/Import your application.
3. Upgrade EcoStruxure
Machine Expert to the latest version.
Delete the unresolved functions from the application.
Your application might be corrupted. To resolve this issue, use one of the methods:
1.
Build
>
Clean All
2. Export/Import your application.
3. Upgrade EcoStruxure
Machine Expert to the latest version.
Debug your application to resolve the problem.
Debug your application to resolve the problem.
Debug your application to resolve the problem.
Reduce the application workload by improving the application architecture. Increase the task cycle duration. Reduce event frequency.
Debug your application to resolve the problem.
Reduce the number of event tasks.
The application version in the logic controller does not match the version in EcoStruxure
Machine Expert. Refer to
Applications (see EcoStruxure
Machine Expert, Programming
Guide).
EIO0000003095.03
39
System Functions and Variables
M251 PLCSystem Library Data Types
PLC_R_BOOT_PROJECT_STATUS
: Boot Project Status Codes
Enumerated Type Description
The PLC_R_BOOT_PROJECT_STATUS enumeration data type contains the following values:
Enumerator
PLC_R_NO_BOOT_PROJECT
PLC_R_BOOT_PROJECT_CREATION_IN_
PROGRESS
PLC_R_DIFFERENT_BOOT_PROJECT
Value
0000 hex
0001 hex
0002 hex
Comment
Boot project does not exist in non-volatile memory.
Boot project is being created.
PLC_R_VALID_BOOT_PROJECT FFFF hex
Boot project in non-volatile memory is different from the project loaded in memory.
Boot project in non-volatile memory is the same as the project loaded in memory.
PLC_R_IO_STATUS
: I/O Status Codes
Enumerated Type Description
The PLC_R_IO_STATUS enumeration data type contains the following values:
Enumerator
PLC_R_IO_OK
PLC_R_IO_NO_INIT
PLC_R_IO_CONF_FAULT
PLC_R_IO_SHORTCUT_FAULT
PLC_R_IO_POWER_SUPPLY_FAULT
Value
FFFF hex
0001 hex
0002 hex
0003 hex
0004 hex
Comment
Inputs/Outputs are operational.
Inputs/Outputs are not initialized.
Incorrect I/O configuration parameters detected.
Inputs/Outputs short-circuit detected.
Inputs/Outputs power supply error detected.
PLC_R_SDCARD_STATUS
: SD Card Slot Status Codes
Enumerator
NO_SDCARD
SDCARD_READONLY
SDCARD_READWRITE
SDCARD_ERROR
Enumerated Type Description
The PLC_R_SDCARD_STATUS enumeration data type contains the following values:
Value
0000 hex
0001 hex
0002 hex
0003 hex
Comment
No SD card detected in the slot or the slot is not connected.
SD card is in read-only mode.
SD card is in read/write mode.
Error detected in the SD card. More details are written to the file FwLog.
txt.
40 EIO0000003095.03
M251 PLCSystem Library Data Types
System Functions and Variables
PLC_R_STATUS
: Controller Status Codes
Enumerated Type Description
The PLC_R_STATUS enumeration data type contains the following values:
Enumerator
PLC_R_EMPTY
PLC_R_STOPPED
PLC_R_RUNNING
PLC_R_HALT
PLC_R_BREAKPOINT
Value
0000 hex
0001 hex
0002 hex
0004 hex
0008 hex
Comment
Controller does not contain an application.
Controller is stopped.
Controller is running.
Controller is in a HALT state (see the controller state diagram in your controller programming guide (see Modicon M251 Logic Controller,
Programming Guide)).
Controller has paused at a breakpoint.
EIO0000003095.03
41
System Functions and Variables
M251 PLCSystem Library Data Types
PLC_R_STOP_CAUSE
: From RUN State to Other State Transition Cause Codes
Enumerated Type Description
The PLC_R_STOP_CAUSE enumeration data type contains the following values:
Enumerator
PLC_R_STOP_REASON_ UNKNOWN
PLC_R_STOP_REASON_HW_ WATCHDOG
PLC_R_STOP_REASON_RESET
PLC_R_STOP_REASON_EXCEPTION
PLC_R_STOP_REASON_USER
PLC_R_STOP_REASON_IECPROGRAM
PLC_R_STOP_REASON_DELETE
PLC_R_STOP_REASON_DEBUGGING
PLC_R_STOP_FROM_NETWORK_
REQUEST
PLC_R_STOP_FROM_INPUT 0B hex
PLC_R_STOP_FROM_RUN_STOP_SWITCH 0C hex
PLC_R_STOP_REASON_RETAIN_
MISMATCH
0D hex
PLC_R_STOP_REASON_BOOT_APPLI_
MISMATCH
PLC_R_STOP_REASON_POWERFAIL
Value
00 hex
01 hex
02 hex
03 hex
04 hex
05 hex
06 hex
07 hex
0A hex
0E hex
0F hex
Comment
Initial value or stop cause is indeterminable.
Stopped after hardware watchdog timeout.
Contact your local
Schneider Electric representative.
Stopped after reset.
See reset possibilities in
Controller State Diagram.
Stopped after exception.
What to do
Contact your local
Schneider Electric representative.
Stopped after a user request.
Verify your application, and correct if necessary.
See System and Task
Watchdogs. A reset is needed to enter Run mode.
Refer to Stop Command in
Commanding State
Transitions (see Modicon
M251 Logic Controller,
Programming Guide).
– Stopped after a program command request
(for example: control command with parameter PLC_W.q_wPLCControl:=PLC_
W_COMMAND.PLC_W_STOP; ).
Stopped after a remove application command.
Stopped after entering debug mode.
Stopped after a request from the network, the controller Web server, or PLC_W command.
Stop required by a controller input.
Stop required by the controller switch.
See the Applications tab of the Controller Device
Editor (see Modicon M251
Logic Controller,
Programming Guide).
–
–
–
–
Stopped after an unsuccessful check context test during rebooting.
There are retained variables in non-volatile memory that do not exist in the executing application.
Stopped after an unsuccessful compare between the boot application and the application that was in the memory before rebooting.
Stopped after a power interruption.
Verify your application, correct if necessary, then reestablish the boot application.
Create a valid boot application.
–
For more information on the reasons why the controller has stopped, refer to the
Controller State Description (see Modicon M251 Logic Controller, Programming
Guide).
42 EIO0000003095.03
M251 PLCSystem Library Data Types
System Functions and Variables
PLC_R_TERMINAL_PORT_STATUS
: Programming Port Connection Status Codes
Enumerated Type Description
The PLC_R_TERMINAL_PORT_STATUS enumeration data type contains the following values:
Enumerator
TERMINAL_NOT_CONNECTED
TERMINAL_CONNECTION_IN_PROGRESS
TERMINAL_CONNECTED
TERMINAL_ERROR
Value
00 hex
01 hex
02 hex
0F hex
Comment
No PC is connected to the programming port.
Connection is in progress.
PC is connected to the programming port.
Error detected during connection.
PLC_R_TM3_BUS_STATE
: TM3 Bus Status Codes
Enumerated Type Description
Enumerator
TM3_CONF_ERROR
TM3_OK
TM3_POWER_SUPPLY_ERROR
The PLC_R_TM3_BUS_STATE enumeration data type contains the following values:
Value
01 hex
03 hex
04 hex
Comment
Error detected due to mismatch in the physical configuration and the configuration in EcoStruxure Machine Expert.
The physical configuration and the configuration in EcoStruxure Machine
Expert match.
Error detected in power supply.
PLC_W_COMMAND
: Control Command Codes
Enumerated Type Description
The PLC_W_COMMAND enumeration data type contains the following values:
Enumerator
PLC_W_STOP
PLC_W_RUN
PLC_W_RESET_COLD
PLC_W_RESET_WARM
Value
0001 hex
0002 hex
0004 hex
0008 hex
Comment
Command to stop the controller.
Command to run the controller.
Command to initiate a Controller cold reset.
Command to initiate a Controller warm reset.
DataFileCopy System Variables Data Types
Overview
This section lists and describes the system variable data types included in the
DataFileCopy structures.
EIO0000003095.03
43
System Functions and Variables
M251 PLCSystem Library Data Types
DataFileCopyError
: Detected Error Codes
Enumerated Type Description
The DataFileCopyError enumeration data type contains the following values:
Enumerator
ERR_NO_ERR
ERR_FILE_NOT_FOUND
ERR_FILE_ACCESS_REFUSED
ERR_INCORRECT_SIZE
ERR_CRC_ERR
ERR_INCORRECT_MAC
Value
00 hex
01 hex
02 hex
03 hex
04 hex
05 hex
Description
No error detected.
The file does not exist.
The file cannot be opened.
The request size is not the same as size read from file.
The CRC is not correct and the file is assumed to be corrupted.
The controller attempting to read from the file does not have the same
MAC address as that contained in the file.
DataFileCopyLocation
: Location Codes
Enumerated Type Description
The DataFileCopyLocation enumeration data type contains the following values:
Enumerator
DFCL_INTERNAL
DFCL_EXTERNAL
DFCL_TBD
Value
00 hex
01 hex
02 hex
Description
Data file with DTA extension is located in /usr/Dta directory.
Data file with DTA extension is located in /sd0/usr/Dta directory.
Not used.
ExecScript System Variables Data Types
Overview
This section lists and describes the system variable data types included in the
ExecScript structures.
ExecuteScriptError
: Detected Error Codes
Enumerated Type Description
The ExecuteScriptError enumeration data type contains the following values:
Enumerator
CMD_OK
ERR_CMD_UNKNOWN
ERR_SD_CARD_MISSING
ERR_SEE_FWLOG
ERR_ONLY_ONE_COMMAND_ALLOWED
CMD_BEING_EXECUTED
Value
00 hex
01 hex
02 hex
03 hex
04 hex
05 hex
Description
No error detected.
The command is invalid.
SD card is not present.
There was an error detected during command execution, see FwLog.
txt . For more information, refer to File Type (see Modicon M251 Logic
Controller, Programming Guide).
An attempt was made to execute several scripts simultaneously.
A script is already in progress.
44 EIO0000003095.03
M251 PLCSystem Library Data Types
ETH_RW System Variables Data Types
Overview
System Functions and Variables
This section lists and describes the system variable data types included in the
ETH_R and ETH_W structures.
ETH_R_FRAME_PROTOCOL
: Frame Transmission Protocol Codes
Enumerator
ETH_R_802_3
ETH_R_ETHERNET_II
Enumerated Type Description
The ETH_R_FRAME_PROTOCOL enumeration data type contains the following values:
Value
00 hex
01 hex
Comment
The protocol used for frame transmission is IEEE 802.3.
The protocol used for frame transmission is Ethernet II.
ETH_R_IP_MODE
: IP Address Source Codes
Enumerated Type Description
The ETH_R_IP_MODE enumeration data type contains the following values:
Enumerator
ETH_R_STORED
ETH_R_BOOTP
ETH_R_DHCP
ETH_DEFAULT_IP
Value
00 hex
01 hex
02 hex
FF hex
Comment
Stored IP address is used.
Bootstrap protocol (BOOTP) is used to get an IP address.
DHCP protocol is used to get an IP address.
Default IP address is used.
ETH_R_PORT_DUPLEX_STATUS
: Transmission Mode Codes
Enumerator
ETH_R_PORT_HALF_DUPLEX
ETH_R_FULL_DUPLEX
ETH_R_PORT_NA_DUPLEX
Enumerated Type Description
The ETH_R_PORT_DUPLEX_STATUS enumeration data type contains the following values:
Value
00 hex
01 hex
03 hex
Comment
Half duplex transmission mode is used.
Full duplex transmission mode is used.
No duplex transmission mode is used.
EIO0000003095.03
45
System Functions and Variables
M251 PLCSystem Library Data Types
ETH_R_PORT_IP_STATUS
: Ethernet TCP/IP Port Status Codes
Enumerator
WAIT_FOR_PARAMS
WAIT_FOR_CONF
DATA_EXCHANGE
ETH_ERROR
DUPLICATE_IP
Enumerated Type Description
The ETH_R_PORT_IP_STATUS enumeration data type contains the following values:
Value
00 hex
01 hex
02 hex
03 hex
04 hex
Comment
Waiting for parameters.
Waiting for configuration.
Ready for data exchange.
Ethernet TCP/IP port error detected (cable disconnected, invalid configuration, and so on).
IP address already used by another equipment.
ETH_R_PORT_LINK_STATUS
: Communication Link Status Codes
Enumerator
ETH_R_LINK_DOWN
ETH_R_LINK_UP
Enumerated Type Description
The ETH_R_PORT_LINK_STATUS enumeration data type contains the following values:
Value
00 hex
01 hex
Comment
Communication link not available to another device.
Communication link available to another device.
ETH_R_PORT_SPEED
: Communication Speed of the Ethernet Port Codes
Enumerator
ETH_R_SPEED_NA
ETH_R_SPEED_10_MB
ETH_R_100_MB
Enumerated Type Description
The ETH_R_PORT_SPEED enumeration data type contains the following values:
Value
0 dec
10 dec
100 dec
Comment
Network speed is not available.
Network speed is 10 megabits per second.
Network speed is 100 megabits per second.
ETH_R_RUN_IDLE
: Ethernet/IP Run and Idle States Codes
Enumerated Type Description
The ETH_R_RUN_IDLE enumeration data type contains the following values:
Enumerator
IDLE
RUN
Value
00 hex
01 hex
Comment
EtherNet/IP connection is idle.
EtherNet/IP connection is running.
TM3_MODULE_RW System Variables Data Types
Overview
This section lists and describes the system variable data types included in the
TM3_MODULE_R and TM3_MODULE_W structures.
46 EIO0000003095.03
M251 PLCSystem Library Data Types
System Functions and Variables
TM3_ERR_CODE
: TM3 Expansion Module Detected Error Codes
Enumerated Type Description
The TM3_ERR_CODE enumeration data type contains the following values:
Enumerator
TM3_NO_ERR
TM3_ERR_FAILED
TM3_ERR_PARAMETER
TM3_ERR_COK
TM3_ERR_BUS
Value
00 hex
01 hex
02 hex
03 hex
04 hex
Comment
Last bus exchange with the expansion module was successful.
Error detected due to the last bus exchange with the expansion module was unsuccessful.
Parameter error detected in the last bus exchange with the module.
Temporary or permanent hardware error detected on one of the TM3 expansion modules.
Bus error detected in the last bus exchange with the expansion module.
TM3_MODULE_R_ARRAY_TYPE
: TM3 Expansion Module Read Array Type
Description
The TM3_MODULE_R_ARRAY_TYPE is an array of 0...13
TM3_MODULE_R_
STRUCT .
TM3_MODULE_STATE
: TM3 Expansion Module State Codes
Enumerated Type Description
The TM3_MODULE_STATE enumeration data type contains the following values:
Enumerator
TM3_EMPTY
TM3_CONF_ERROR
TM3_BUS_ERROR
TM3_OK
TM3_MISSING_OPT_MOD
Value
00 hex
01 hex
02 hex
03 hex
05 hex
Comment
No module.
Physical expansion module does not match with the one configured in
EcoStruxure Machine Expert.
Bus error detected in the last exchange with the module.
Last bus exchange with this module was successful.
Optional module is not physically present.
TM3_BUS_W_IOBUSERRMOD
: TM3 bus error mode
Enumerator
IOBUS_ERR_ACTIVE
IOBUS_ERR_PASSIVE
Enumerated Type Description
The TM3_BUS_W_IOBUSERRMOD enumeration data type contains the following values:
Value
00 hex
01 hex
Comment
Active mode. The logic controller stops all I/O exchanges on the TM3 bus on detection of a permanent error. Refer to I/O Configuration
General Description (see Modicon M251 Logic Controller, Programming
Guide).
Passive mode. I/O exchanges continue on the TM3 bus even if an error is detected.
EIO0000003095.03
47
System Functions and Variables
System Function Data Types
Overview
M251 PLCSystem Library Data Types
This section describes the different system function data types of the M251
PLCSystem library.
RTCSETDRIFT_ERROR
:
SetRTCDrift
Function Detected Error Codes
Enumerator
RTC_OK
RTC_BAD_DAY
RTC_BAD_HOUR
RTC_BAD_MINUTE
RTC_BAD_DRIFT
RTC_INTERNAL_ERROR
Enumerated Type Description
The RTCSETDRIFT_ERROR enumeration data type contains the following values:
Value
00 hex
01 hex
02 hex
03 hex
04 hex
05 hex
Comment
RTC drift correctly configured.
Not used.
Not used.
Not used.
RTC Drift parameter out of range.
RTC Drift settings rejected on internal error detected.
48 EIO0000003095.03
System Functions and Variables
Appendices
What’s in This Part
Function and Function Block Representation ...................................................50
Overview
This appendix extracts parts of the programming guide for technical understanding of the library documentation.
EIO0000003095.03
49
System Functions and Variables
Function and Function Block Representation
Function and Function Block Representation
What’s in This Chapter
Differences Between a Function and a Function Block .....................................50
How to Use a Function or a Function Block in IL Language ...............................51
How to Use a Function or a Function Block in ST Language .............................53
Overview
Each function can be represented in the following languages:
• IL: Instruction List
• ST: Structured Text
• LD: Ladder Diagram
• FBD: Function Block Diagram
• CFC: Continuous Function Chart
This chapter provides functions and function blocks representation examples and explains how to use them for IL and ST languages.
Differences Between a Function and a Function Block
Function
A function:
• is a POU (Program Organization Unit) that returns one immediate result.
• is directly called with its name (not through an instance).
• has no persistent state from one call to the other.
• can be used as an operand in other expressions.
Examples: boolean operators ( AND ), calculations, conversion ( BYTE_TO_INT )
Function Block
A function block:
• is a POU (Program Organization Unit) that returns one or more outputs.
• needs to be called by an instance (function block copy with dedicated name and variables).
• each instance has a persistent state (outputs and internal variables) from one call to the other from a function block or a program.
Examples: timers, counters
50 EIO0000003095.03
Function and Function Block Representation
System Functions and Variables
In the example, Timer_ON is an instance of the function block TON :
How to Use a Function or a Function Block in IL Language
General Information
This part explains how to implement a function and a function block in IL language.
Functions IsFirstMastCycle and SetRTCDrift and Function Block TON are used as examples to show implementations.
Using a Function in IL Language
This procedure describes how to insert a function in IL language:
2
3
Step Action
1 Open or create a new POU in Instruction List language.
NOTE: The procedure to create a POU is not detailed here. For more information, refer to Adding and Calling POUs (see EcoStruxure Machine Expert, Programming Guide).
Create the variables that the function requires.
If the function has 1 or more inputs, start loading the first input using LD instruction.
4
5
6
Insert a new line below and:
• type the name of the function in the operator column (left field), or
• use the Input Assistant to select the function (select Insert Box in the contextual menu).
If the function has more than 1 input and when Input Assistant is used, the necessary number of lines is automatically created with ???
in the fields on the right. Replace the ???
with the appropriate value or variable that corresponds to the order of inputs.
Insert a new line to store the result of the function into the appropriate variable: type ST instruction in the operator column (left field) and the variable name in the field on the right.
To illustrate the procedure, consider the Functions IsFirstMastCycle (without input parameter) and SetRTCDrift (with input parameters) graphically presented below:
EIO0000003095.03
51
System Functions and Variables
Graphical Representation Function without input parameter:
IsFirstMastCycle with input parameters:
SetRTCDrift
Function and Function Block Representation
Function
IL example of a function without input parameter:
IsFirstMastCycle
In IL language, the function name is used directly in the operator column:
Representation in POU IL Editor
IL example of a function with input parameters:
SetRTCDrift
Using a Function Block in IL Language
This procedure describes how to insert a function block in IL language:
2
3
Step Action
1 Open or create a new POU in Instruction List language.
NOTE: The procedure to create a POU is not detailed here. For more information, refer to Adding and Calling POUs (see EcoStruxure Machine Expert, Programming Guide).
Create the variables that the function block requires, including the instance name.
Function Blocks are called using a CAL instruction:
• Use the Input Assistant to select the function block (right-click and select Insert Box in the contextual menu).
52 EIO0000003095.03
Function and Function Block Representation
Function Block
TON
System Functions and Variables
4
5
Step Action
• Automatically, the CAL instruction and the necessary I/O are created.
Each parameter (I/O) is an instruction:
• Values to inputs are set by " := ".
• Values to outputs are set by " => ".
In the CAL right-side field, replace ???
with the instance name.
Replace other ???
with an appropriate variable or immediate value.
To illustrate the procedure, consider this example with the TON Function Block graphically presented below:
Graphical Representation
Function Block
TON
In IL language, the function block name is used directly in the operator column:
Representation in POU IL Editor
How to Use a Function or a Function Block in ST Language
General Information
This part explains how to implement a Function and a Function Block in ST language.
Function SetRTCDrift and Function Block TON are used as examples to show implementations.
Using a Function in ST Language
This procedure describes how to insert a function in ST language:
EIO0000003095.03
53
System Functions and Variables
Function
SetRTCDrift
Function and Function Block Representation
2
3
Step
1
Action
Open or create a new POU in Structured Text language.
NOTE: The procedure to create a POU is not detailed here. For more information, refer to Adding and Calling POUs (see EcoStruxure Machine Expert, Programming
Guide).
Create the variables that the function requires.
Use the general syntax in the POU ST Editor for the ST language of a function. The general syntax is:
FunctionResult:= FunctionName(VarInput1, VarInput2,.. VarInputx);
To illustrate the procedure, consider the function SetRTCDrift graphically presented below:
Graphical Representation
Function
SetRTCDrift
The ST language of this function is the following:
Representation in POU ST Editor
PROGRAM MyProgram_ST
VAR myDrift: SINT(-29..29) := 5; myDay: DAY_OF_WEEK := SUNDAY; myHour: HOUR := 12; myMinute: MINUTE; myRTCAdjust: RTCDRIFT_ERROR;
END_VAR myRTCAdjust:= SetRTCDrift(myDrift, myDay, myHour, myMinute);
Using a Function Block in ST Language
This procedure describes how to insert a function block in ST language:
Step Action
1 Open or create a new POU in Structured Text language.
NOTE: The procedure to create a POU is not detailed here. For more information on adding, declaring and calling POUs, refer to the related documentation (see
EcoStruxure Machine Expert, Programming Guide).
2 Create the input and output variables and the instance required for the function block:
• Input variables are the input parameters required by the function block
• Output variables receive the value returned by the function block
3 Use the general syntax in the POU ST Editor for the ST language of a Function Block. The general syntax is:
FunctionBlock_InstanceName(Input1:=VarInput1, Input2:=VarInput2,...
Ouput1=>VarOutput1, Ouput2=>VarOutput2,...);
To illustrate the procedure, consider this example with the TON function block graphically presented below:
Graphical Representation Function Block
TON
54 EIO0000003095.03
Function and Function Block Representation
Function Block
TON
System Functions and Variables
This table shows examples of a function block call in ST language:
Representation in POU ST Editor
EIO0000003095.03
55
Glossary
EIO0000003095.03
System Functions and Variables
A
%:
According to the IEC standard, % is a prefix that identifies internal memory addresses in the logic controller to store the value of program variables, constants, I/O, and so on.
application:
A program including configuration data, symbols, and documentation.
ARRAY:
The systematic arrangement of data objects of a single type in the form of a table defined in logic controller memory. The syntax is as follows: ARRAY
[<dimension>] OF <Type>
Example 1: ARRAY [1..2] OF BOOL is a 1-dimensional table with 2 elements of type BOOL .
Example 2: ARRAY [1..10, 1..20] OF INT is a 2-dimensional table with 10 x
20 elements of type INT .
B
BOOL:
( boolean ) A basic data type in computing. A BOOL variable can have one of these values: 0 ( FALSE ), 1 ( TRUE ). A bit that is extracted from a word is of type BOOL ; for example, %MW10.4
is a fifth bit of memory word number 10.
Boot application:
( boot application ) The binary file that contains the application. Usually, it is stored in the controller and allows the controller to boot on the application that the user has generated.
BOOTP:
( bootstrap protocol ) A UDP network protocol that can be used by a network client to automatically obtain an IP address (and possibly other data) from a server. The client identifies itself to the server using the client MAC address. The server, which maintains a pre-configured table of client device MAC addresses and associated IP addresses, sends the client its pre-configured IP address. BOOTP was originally used as a method that enabled diskless hosts to be remotely booted over a network. The BOOTP process assigns an infinite lease of an IP address. The BOOTP service utilizes UDP ports 67 and 68.
byte:
A type that is encoded in an 8-bit format, ranging from 00 hex to FF hex.
C
CAN:
( controller area network ) A protocol (ISO 11898) for serial bus networks, designed for the interconnection of smart devices (from multiple manufacturers) in smart systems and for real-time industrial applications. Originally developed for use in automobiles, CAN is now used in a variety of industrial automation control environments.
CFC:
( continuous function chart ) A graphical programming language (an extension of the IEC 61131-3 standard) based on the function block diagram language that works like a flowchart. However, no networks are used and free positioning of
57
System Functions and Variables graphic elements is possible, which allows feedback loops. For each block, the inputs are on the left and the outputs on the right. You can link the block outputs to the inputs of other blocks to create complex expressions.
configuration:
The arrangement and interconnection of hardware components within a system and the hardware and software parameters that determine the operating characteristics of the system.
control network:
A network containing logic controllers, SCADA systems, PCs, HMI, switches, ...
Two kinds of topologies are supported:
• flat: all modules and devices in this network belong to same subnet.
• 2 levels: the network is split into an operation network and an inter-controller network.
These two networks can be physically independent, but are generally linked by a routing device.
CRC:
( cyclical redundancy check ) A method used to determine the validity of a communication transmission. The transmission contains a bit field that constitutes a checksum. The message is used to calculate the checksum by the transmitter according to the content of the message. Receiving nodes, then recalculate the field in the same manner. Any discrepancy in the value of the 2 CRC calculations indicates that the transmitted message and the received message are different.
D
DHCP:
( dynamic host configuration protocol ) An advanced extension of BOOTP. DHCP is more advanced, but both DHCP and BOOTP are common. (DHCP can handle
BOOTP client requests.)
DWORD:
( double word ) Encoded in 32-bit format.
E element:
The short name of the ARRAY element.
equipment:
A part of a machine including sub-assemblies such as conveyors, turntables, and so on.
EtherNet/IP:
( Ethernet industrial protocol ) An open communications protocol for manufacturing automation solutions in industrial systems. EtherNet/IP is in a family of networks that implement the common industrial protocol at its upper layers. The supporting organization (ODVA) specifies EtherNet/IP to accomplish global adaptability and media independence.
Ethernet:
A physical and data link layer technology for LANs, also known as IEEE 802.3.
F
FB:
58 EIO0000003095.03
EIO0000003095.03
System Functions and Variables
( function block ) A convenient programming mechanism that consolidates a group of programming instructions to perform a specific and normalized action, such as speed control, interval control, or counting. A function block may comprise configuration data, a set of internal or external operating parameters and usually
1 or more data inputs and outputs.
firmware:
Represents the BIOS, data parameters, and programming instructions that constitute the operating system on a controller. The firmware is stored in nonvolatile memory within the controller.
function block diagram:
One of the 5 languages for logic or control supported by the standard IEC 61131-
3 for control systems. Function block diagram is a graphically oriented programming language. It works with a list of networks where each network contains a graphical structure of boxes and connection lines representing either a logical or arithmetic expression, the call of a function block, a jump, or a return instruction.
function block:
A programming unit that has 1 or more inputs and returns 1 or more outputs. FBs are called through an instance (function block copy with dedicated name and variables) and each instance has a persistent state (outputs and internal variables) from 1 call to the other.
Examples: timers, counters function:
A programming unit that has 1 input and returns 1 immediate result. However, unlike FBs, it is directly called with its name (as opposed to through an instance), has no persistent state from one call to the next and can be used as an operand in other programming expressions.
Examples: boolean (AND) operators, calculations, conversions (BYTE_TO_INT)
G
GVL:
( global variable list ) Manages global variables within an EcoStruxure Machine
Expert project.
H hex:
( hexadecimal )
I
I/O:
( input/output )
ID:
( identifier/identification )
IEC 61131-3:
Part 3 of a 3-part IEC standard for industrial automation equipment. IEC 61131-3 is concerned with controller programming languages and defines 2 graphical and
2 textual programming language standards. The graphical programming languages are ladder diagram and function block diagram. The textual programming languages include structured text and instruction list.
IEC:
59
System Functions and Variables
( international electrotechnical commission ) A non-profit and non-governmental international standards organization that prepares and publishes international standards for electrical, electronic, and related technologies.
IEEE 802.3:
A collection of IEEE standards defining the physical layer, and the media access control sublayer of the data link layer, of wired Ethernet.
IL:
( instruction list ) A program written in the language that is composed of a series of text-based instructions executed sequentially by the controller. Each instruction includes a line number, an instruction code, and an operand (refer to IEC 61131-
3).
INT:
( integer ) A whole number encoded in 16 bits.
IP:
( Internet protocol Part of the TCP/IP protocol family that tracks the Internet addresses of devices, routes outgoing messages, and recognizes incoming messages.
L
LD:
( ladder diagram ) A graphical representation of the instructions of a controller program with symbols for contacts, coils, and blocks in a series of rungs executed sequentially by a controller (refer to IEC 61131-3).
LED:
( light emitting diode ) An indicator that illuminates under a low-level electrical charge.
LWORD:
( long word ) A data type encoded in a 64-bit format.
M
MAC address:
( media access control address ) A unique 48-bit number associated with a specific piece of hardware. The MAC address is programmed into each network card or device when it is manufactured.
MAST:
A processor task that is run through its programming software. The MAST task has 2 sections:
• IN: Inputs are copied to the IN section before execution of the MAST task.
• OUT: Outputs are copied to the OUT section after execution of the MAST task.
Modbus:
The protocol that allows communications between many devices connected to the same network.
%MW:
According to the IEC standard, %MW represents a memory word register (for example, a language object of type memory word).
60 EIO0000003095.03
EIO0000003095.03
System Functions and Variables
N network:
A system of interconnected devices that share a common data path and protocol for communications.
NVM:
(Non-volatile memory) A non-volatile memory that can be overwritten. It is stored on a special EEPROM that can be erased and reprogrammed.
P
PCI:
( peripheral component interconnect ) An industry-standard bus for attaching peripherals.
PLC:
( programmable logic controller ) An industrial computer used to automate manufacturing, industrial, and other electromechanical processes. PLCs are different from common computers in that they are designed to have multiple input and output arrays and adhere to more robust specifications for shock, vibration, temperature, and electrical interference among other things.
POU:
( program organization unit ) A variable declaration in source code and a corresponding instruction set. POUs facilitate the modular re-use of software programs, functions, and function blocks. Once declared, POUs are available to one another.
program:
The component of an application that consists of compiled source code capable of being installed in the memory of a logic controller.
protocol:
A convention or standard definition that controls or enables the connection, communication, and data transfer between 2 computing system and devices.
R
RTC:
( real-time clock ) A battery-backed time-of-day and calender clock that operates continuously, even when the controller is not powered for the life of the battery.
run:
A command that causes the controller to scan the application program, read the physical inputs, and write to the physical outputs according to solution of the logic of the program.
S
SINT:
( signed integer ) A 15-bit value plus sign.
STOP:
A command that causes the controller to stop running an application program.
string:
A variable that is a series of ASCII characters.
ST:
61
System Functions and Variables
( structured text ) A language that includes complex statements and nested instructions (such as iteration loops, conditional executions, or functions). ST is compliant with IEC 61131-3.
system variable:
A variable that provides controller data and diagnostic information and allows sending commands to the controller.
T task:
A group of sections and subroutines, executed cyclically or periodically for the
MAST task or periodically for the FAST task.
A task possesses a level of priority and is linked to inputs and outputs of the controller. These I/O are refreshed in relation to the task.
A controller can have several tasks.
TCP:
( transmission control protocol ) A connection-based transport layer protocol that provides a simultaneous bi-directional transmission of data. TCP is part of the
TCP/IP protocol suite.
U
UDINT:
( unsigned double integer ) Encoded in 32 bits.
UINT:
( unsigned integer ) Encoded in 16 bits.
unlocated variable:
A variable that does not have an address (refer to located variable ).
V variable:
A memory unit that is addressed and modified by a program.
W watchdog:
A watchdog is a special timer used to ensure that programs do not overrun their allocated scan time. The watchdog timer is usually set to a higher value than the scan time and reset to 0 at the end of each scan cycle. If the watchdog timer reaches the preset value, for example, because the program is caught in an endless loop, an error is declared and the program stopped.
WORD:
A type encoded in a 16-bit format.
62 EIO0000003095.03
Index
System Functions and Variables
ExecuteScriptError
Data Types ........................................................44
B
Battery led
InhibitBatLed .....................................................26
C cycle
IsFirstMastColdCycle .........................................23
IsFirstMastCycle ................................................24
IsFirstMastWarmCycle .......................................25
D
Data Types
DataFileCopyError .............................................44
DataFileCopyLocation ........................................44
ETH_R_FRAME_PROTOCOL............................45
ETH_R_IP_MODE .............................................45
ETH_R_PORT_DUPLEX_STATUS .....................45
ETH_R_PORT_IP_STATUS ...............................46
ETH_R_PORT_LINK_STATUS ...........................46
ETH_R_PORT_SPEED......................................46
ETH_R_RUN_IDLE ...........................................46
ExecuteScriptError.............................................44
PLC_R_APPLICATION_ERROR ........................39
PLC_R_BOOT_PROJECT_STATUS...................40
PLC_R_IO_STATUS ..........................................40
PLC_R_SDCARD_STATUS................................40
PLC_R_STATUS ...............................................41
PLC_R_STOP_CAUSE......................................42
PLC_R_TERMINAL_PORT_STATUS..................43
PLC_R_TM3_BUS_STATE.................................43
PLC_W_COMMAND..........................................43
RTCSETDRIFT_ERROR....................................48
TM3_BUS_W_IOBUSERRMOD .........................47
TM3_ERR_CODE..............................................47
TM3_MODULE_R_ARRAY_TYPE ......................47
TM3_MODULE_STATE......................................47
DataFileCopy
copying data to or from a file ...............................29
DataFileCopyError
Data Types ........................................................44
DataFileCopyLocation
Data Types ........................................................44
I
F
FB_ControlClone
function block ....................................................28
FC_GetFreeDiskSpace
function .............................................................32
FC_GetLabel
function .............................................................33
FC_GetTotalDiskSpace
function .............................................................33
file copy commands
DataFileCopy.....................................................29
function
FC_GetFreeDiskSpace ......................................32
FC_GetLabel .....................................................33
FC_GetTotalDiskSpace ......................................33
function blocks
FB_ControlClone ...............................................28
functions differences between a function and a function
block ...............................................................50
how to use a function or a function block in IL
language .........................................................51
how to use a function or a function block in ST
language .........................................................53
G
GetRtc
getting real time clock (RTC) value ......................23
InhibitBatLed
Enabling or disabling the Battery led ....................26
IsFirstMastColdCycle
first cold start cycle.............................................23
IsFirstMastCycle
first mast cycle ...................................................24
IsFirstMastWarmCycle
first warm start cycle...........................................25
E
ETH_R
system variable..................................................18
ETH_R_FRAME_PROTOCOL
Data Types ........................................................45
ETH_R_IP_MODE
Data Types ........................................................45
ETH_R_PORT_DUPLEX_STATUS
Data Types ........................................................45
ETH_R_PORT_LINK_STATUS
Data Types ........................................................46
ETH_R_PORT_SPEED
Data Types ........................................................46
ETH_W
system variable..................................................20
ExecuteScript
running script commands....................................31
M
M251 PLCSystem
DataFileCopy.....................................................29
ExecuteScript ....................................................31
GetRtc ..............................................................23
InhibitBatLed .....................................................26
IsFirstMastColdCycle .........................................23
IsFirstMastCycle ................................................24
IsFirstMastWarmCycle .......................................25
P
PLC_R
system variable..................................................13
PLC_R_APPLICATION_ERROR
Data Types ........................................................39
PLC_R_BOOT_PROJECT_STATUS
Data Types ........................................................40
PLC_R_IO_STATUS
Data Types ........................................................40
EIO0000003095.03
63
System Functions and Variables
PLC_R_SDCARD_STATUS
Data Types ........................................................40
PLC_R_STATUS
Data Types ........................................................41
PLC_R_STOP_CAUSE
Data Types ........................................................42
PLC_R_TERMINAL_PORT_STATUS
Data Types ........................................................43
PLC_R_TM3_BUS_STATE
Data Types ........................................................43
PLC_W
system variable..................................................15
PLC_W_COMMAND
Data Types ........................................................43
PROFIBUS_R
system variable..................................................21
getting the bus status of a TM3 module................34
TM3_GetModuleFWVersion
getting the firmware version of a TM3 module ......35
TM3_GetModuleInternalStatus
getting the internal status of a TM3 module ..........36
TM3_MODULE_R
system variable..................................................20
TM3_MODULE_R_ARRAY_TYPE
Data Types ........................................................47
TM3_MODULE_STATE
Data Types ........................................................47
R real time clock
GetRtc ..............................................................23
SetRTCDrift.......................................................26
RTC
GetRtc ..............................................................23
SetRTCDrift.......................................................26
RTCSETDRIFT_ERROR
Data Types ........................................................48
S script commands
ExecuteScript ....................................................31
SERIAL_R
system variable..................................................15
SERIAL_W
system variable..................................................16
SetRTCDrift
accelerating or slowing the RTC frequency ..........26
system variable
ETH_R..............................................................18
ETH_W .............................................................20
PLC_R ..............................................................13
PLC_W .............................................................15
PROFIBUS_R ...................................................21
SERIAL_R.........................................................15
SERIAL_W ........................................................16
TM3_BUS_W ....................................................21
TM3_MODULE_R..............................................20
System Variables
Definition...........................................................10
Using ................................................................ 11
T
TM3 module bus status
TM3_GetModuleBusStatus.................................34
TM3 module firmware version
TM3_GetModuleFWVersion................................35
TM3 module internal status
TM3_GetModuleInternalStatus ...........................36
TM3_BUS_W
system variable..................................................21
TM3_BUS_W_IOBUSERRMOD
Data Types ........................................................47
TM3_ERR_CODE
Data Types ........................................................47
TM3_GetModuleBusStatus
64 EIO0000003095.03
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00 www.se.com
As standards, specifications, and design change from time to time, please ask for confirmation of the information given in this publication.
© 2021 – Schneider Electric . All rights reserved.
EIO0000003095.03
Modicon M251
Logic Controller
Hardware Guide
EIO0000003101.03
05/2022 www.se.com
Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its subsidiaries referred to in this guide are the property of Schneider Electric SE or its subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and furnished for informational use only. No part of this guide may be reproduced or transmitted in any form or by any means (electronic, mechanical, photocopying, recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide or its content, except for a non-exclusive and personal license to consult it on an "as is" basis. Schneider Electric products and equipment should be installed, operated, serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational content of this material or consequences arising out of or resulting from the use of the information contained herein.
As part of a group of responsible, inclusive companies, we are updating our communications that contain non-inclusive terminology. Until we complete this process, however, our content may still contain standardized industry terms that may be deemed inappropriate by our customers.
© 2022 – Schneider Electric. All rights reserved.
Table of Contents
EIO0000003101.03
Qualification of Personnel......................................................................5
Modicon M251 Logic Controller Introduction
........................................13
M251 General Overview............................................................................14
M251 Logic Controller Description........................................................14
Maximum Hardware Configuration .......................................................16
TM2 Expansion Modules .....................................................................18
TM3 Expansion Modules .....................................................................21
TM3 Bus Couplers ..............................................................................28
TM4 Expansion Modules .....................................................................29
TM5 Fieldbus Interfaces ......................................................................29
TM5 CANopen Fieldbus Interfaces.......................................................30
TM7 CANopen Fieldbus Interfaces.......................................................30
Real Time Clock (RTC)........................................................................32
M251 Logic Controller General Rules for Implementing..........................38
Environmental Characteristics........................................................38
Certifications and Standards ..........................................................40
M251 Logic Controller Installation ........................................................40
Installation and Maintenance Requirements ....................................40
M251 Logic Controller Mounting Positions and Clearances ..............42
Top Hat Section Rail (DIN rail) ........................................................44
Installing and Removing the Controller with Expansions ...................46
Direct Mounting on a Panel Surface................................................48
M251 Electrical Requirements .............................................................48
Wiring Best Practices ....................................................................48
DC Power Supply Characteristics and Wiring ..................................50
Grounding the M251 System..........................................................53
Modicon M251 Logic Controller
..............................................................55
TM251MESC Presentation ..................................................................56
TM251MESE Presentation ..................................................................59
Modicon M251 Logic Controller Communication
.................................62
Integrated Communication Ports................................................................63
CANopen Port ....................................................................................63
TM251MESE Specific Considerations ..................................................67
USB Mini-B Programming Port.............................................................68
Connecting the M251 Logic Controller to a PC ............................................72
Connecting the Controller to a PC ........................................................72
3
Glossary
Index
4 EIO0000003101.03
Safety Information
Important Information
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
!
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
!
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
!
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
Please Note
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and its installation, and has received safety training to recognize and avoid the hazards involved.
Qualification of Personnel
Only appropriately trained persons who are familiar with and understand the contents of this manual and all other pertinent product documentation are authorized to work on and with this product.
The qualified person must be able to detect possible hazards that may arise from parameterization, modifying parameter values and generally from mechanical, electrical, or electronic equipment. The qualified person must be familiar with the standards, provisions, and regulations for the prevention of industrial accidents, which they must observe when designing and implementing the system.
EIO0000003101.03
5
Intended Use
The products described or affected by this document, together with software, accessories, and options, are programmable logic controllers (referred to herein as “logic controllers”), intended for industrial use according to the instructions, directions, examples, and safety information contained in the present document and other supporting documentation.
The product may only be used in compliance with all applicable safety regulations and directives, the specified requirements, and the technical data.
Prior to using the product, you must perform a risk assessment in view of the planned application. Based on the results, the appropriate safety-related measures must be implemented.
Since the product is used as a component in an overall machine or process, you must ensure the safety of persons by means of the design of this overall system.
Operate the product only with the specified cables and accessories. Use only genuine accessories and spare parts.
Any use other than the use explicitly permitted is prohibited and can result in unanticipated hazards.
6 EIO0000003101.03
About the Book
Document Scope
Use this document to:
• Install and operate your M251 Logic Controller.
• Connect the M251 Logic Controller to a programming device equipped with
EcoStruxure Machine Expert software.
• Interface the M251 Logic Controller with I/O expansion modules, HMI and other devices.
• Familiarize yourself with the M251 Logic Controller features.
NOTE: Read and understand this document and all related documents before installing, operating, or maintaining your controller.
Validity Note
This document has been updated for the release of EcoStruxure TM Machine
Expert V2.0.3.
For product compliance and environmental information (RoHS, REACH, PEP,
EOLI, etc.), go to www.se.com/ww/en/work/support/green-premium/ .
The technical characteristics of the devices described in this manual also appear online ( https://www.se.com/ ).
The characteristics that are described in the present document should be the same as those characteristics that appear online. In line with our policy of constant improvement, we may revise content over time to improve clarity and accuracy. If you see a difference between the document and online information, use the online information as your reference.
Related Documents
Title of Documentation
Modicon M251 Logic Controller - Programming
Guide
EcoStruxure Machine Expert Industrial Ethernet
User Guide
Reference Number
EIO0000003089 (ENG)
EIO0000003090 (FRE)
EIO0000003091 (GER)
EIO0000003092 (SPA)
EIO0000003093 (ITA)
EIO0000003094 (CHS)
EIO0000003053 (ENG)
EIO0000003054 (FRE)
EIO0000003055 (GER)
EIO0000003056 (SPA)
EIO0000003057 (ITA)
EIO0000003058 (CHS)
EIO0000003101.03
7
8
Title of Documentation
Modicon TM3 Digital I/O Modules - Hardware
Guide
Modicon TM3 Expert I/O Modules - Hardware
Guide
Reference Number
EIO0000003125 (ENG)
EIO0000003126 (FRE)
EIO0000003127 (GER)
EIO0000003128 (SPA)
EIO0000003129 (ITA)
EIO0000003130 (CHS)
EIO0000003425 (TUR)
EIO0000003424 (POR)
EIO0000003137 (ENG)
EIO0000003138 (FRE)
EIO0000003139 (GER)
EIO0000003140 (SPA)
EIO0000003141 (ITA)
EIO0000003142 (CHS)
EIO0000003429 (TUR)
EIO0000003428 (POR)
Modicon TM3 Safety Modules - Hardware Guide EIO0000003353 (ENG)
EIO0000003354 (FRE)
EIO0000003355 (GER)
EIO0000003356 (SPA)
EIO0000003357 (ITA)
EIO0000003358 (CHS)
EIO0000003359 (POR)
EIO0000003360 (TUR)
Modicon TM3 Transmitter and Receiver
Modules - Hardware Guide
EIO0000003143 (ENG)
EIO0000003144 (FRE)
EIO0000003145 (GER)
EIO0000003146 (SPA)
EIO0000003147 (ITA)
EIO0000003148 (CHS)
EIO0000003431 (TUR)
EIO0000003430 (POR)
Modicon TM3 Bus Coupler - Hardware Guide EIO0000003635 (ENG)
EIO0000003636 (FRE)
EIO0000003637 (GER)
EIO0000003638 (SPA)
EIO0000003639 (ITA)
EIO0000003640 (CHS)
EIO0000003641 (POR)
EIO0000003642 (TUR)
EIO0000003101.03
Title of Documentation
Modicon TM4 Expansion Modules - Hardware
Guide
Modicon TM5 Fieldbus Interface - Hardware
Guide
Reference Number
EIO0000003155 (ENG)
EIO0000003156 (FRE)
EIO0000003157 (GER)
EIO0000003158 (SPA)
EIO0000003159 (ITA)
EIO0000003160 (CHS)
EIO0000003715 (ENG)
EIO0000003716 (FRE)
EIO0000003717 (GER)
EIO0000003718 (SPA)
EIO0000003719 (ITA)
EIO0000003720 (CHS)
HRB59604 M251 Logic Controller - Instruction Sheet
You can download these technical publications and other technical information from our website at www.se.com/ww/en/download/ .
Product Related Information
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Disconnect all power from all equipment including connected devices prior to removing any covers or doors, or installing or removing any accessories, hardware, cables, or wires except under the specific conditions specified in the appropriate hardware guide for this equipment.
• Always use a properly rated voltage sensing device to confirm the power is off where and when indicated.
• Replace and secure all covers, accessories, hardware, cables, and wires and confirm that a proper ground connection exists before applying power to the unit.
• Use only the specified voltage when operating this equipment and any associated products.
Failure to follow these instructions will result in death or serious injury.
DANGER
POTENTIAL FOR EXPLOSION
• Only use this equipment in non-hazardous locations, or in locations that comply with Class I, Division 2, Groups A, B, C and D.
• Do not substitute components which would impair compliance to Class I,
Division 2.
• Do not connect or disconnect equipment unless power has been removed or the location is known to be non-hazardous.
• Do not use the USB port(s), if so equipped, unless the location is known to be non-hazardous.
Failure to follow these instructions will result in death or serious injury.
EIO0000003101.03
9
WARNING
LOSS OF CONTROL
• The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical control functions, provide a means to achieve a safe state during and after a path failure. Examples of critical control functions are emergency stop and overtravel stop, power outage and restart.
• Separate or redundant control paths must be provided for critical control functions.
• System control paths may include communication links. Consideration must be given to the implications of unanticipated transmission delays or failures of the link.
• Observe all accident prevention regulations and local safety guidelines.
1
• Each implementation of this equipment must be individually and thoroughly tested for proper operation before being placed into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
1 For additional information, refer to NEMA ICS 1.1 (latest edition), "Safety
Guidelines for the Application, Installation, and Maintenance of Solid State
Control" and to NEMA ICS 7.1 (latest edition), "Safety Standards for Construction and Guide for Selection, Installation and Operation of Adjustable-Speed Drive
Systems" or their equivalent governing your particular location.
WARNING
UNINTENDED EQUIPMENT OPERATION
• Only use software approved by Schneider Electric for use with this equipment.
• Update your application program every time you change the physical hardware configuration.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Terminology Derived from Standards
The technical terms, terminology, symbols and the corresponding descriptions in this manual, or that appear in or on the products themselves, are generally derived from the terms or definitions of international standards.
In the area of functional safety systems, drives and general automation, this may include, but is not limited to, terms such as safety , safety function , safe state , fault , fault reset , malfunction , failure , error , error message , dangerous , etc.
Among others, these standards include:
Standard
IEC 61131-2:2007
ISO 13849-1:2015
EN 61496-1:2013
ISO 12100:2010
EN 60204-1:2006
Description
Programmable controllers, part 2: Equipment requirements and tests.
Safety of machinery: Safety related parts of control systems.
General principles for design.
Safety of machinery: Electro-sensitive protective equipment.
Part 1: General requirements and tests.
Safety of machinery - General principles for design - Risk assessment and risk reduction
Safety of machinery - Electrical equipment of machines - Part 1: General requirements
10 EIO0000003101.03
Standard
ISO 14119:2013
ISO 13850:2015
IEC 62061:2015
IEC 61508-1:2010
IEC 61508-2:2010
IEC 61508-3:2010
IEC 61784-3:2016
2006/42/EC
2014/30/EU
2014/35/EU
Description
Safety of machinery - Interlocking devices associated with guards -
Principles for design and selection
Safety of machinery - Emergency stop - Principles for design
Safety of machinery - Functional safety of safety-related electrical, electronic, and electronic programmable control systems
Functional safety of electrical/electronic/programmable electronic safetyrelated systems: General requirements.
Functional safety of electrical/electronic/programmable electronic safetyrelated systems: Requirements for electrical/electronic/programmable electronic safety-related systems.
Functional safety of electrical/electronic/programmable electronic safetyrelated systems: Software requirements.
Industrial communication networks - Profiles - Part 3: Functional safety fieldbuses - General rules and profile definitions.
Machinery Directive
Electromagnetic Compatibility Directive
Low Voltage Directive
In addition, terms used in the present document may tangentially be used as they are derived from other standards such as:
Standard
IEC 60034 series
IEC 61800 series
IEC 61158 series
Description
Rotating electrical machines
Adjustable speed electrical power drive systems
Digital data communications for measurement and control – Fieldbus for use in industrial control systems
Finally, the term zone of operation may be used in conjunction with the description of specific hazards, and is defined as it is for a hazard zone or danger zone in the
Machinery Directive ( 2006/42/EC ) and ISO 12100:2010 .
NOTE: The aforementioned standards may or may not apply to the specific products cited in the present documentation. For more information concerning the individual standards applicable to the products described herein, see the characteristics tables for those product references.
EIO0000003101.03
11
Modicon M251 Logic Controller Introduction
What’s in This Part
EIO0000003101.03
13
M251 General Overview
What’s in This Chapter
Maximum Hardware Configuration..................................................................16
TM5 CANopen Fieldbus Interfaces .................................................................30
TM7 CANopen Fieldbus Interfaces .................................................................30
Overview
This chapter provides general information about the M251 Logic Controller system architecture and its components.
M251 Logic Controller Description
Overview
The M251 Logic Controller has various powerful features and can service a wide range of applications.
Software configuration, programming, and commissioning are achieved with the
EcoStruxure Machine Expert software described in the EcoStruxure Machine
Expert Programming Guide (see EcoStruxure Machine Expert, Programming
Guide) and in the M251 Logic Controller Programming Guide.
Programming Languages
The M251 Logic Controller is configured and programmed with the EcoStruxure
Machine Expert software, which supports the following IEC 61131-3 programming languages:
• IL: Instruction list
• ST: Structured text
• FBD: Function block diagram
• SFC: Sequential function chart
• LD: Ladder diagram
EcoStruxure Machine Expert software can also be used to program this controller using CFC (continuous function chart) language.
Power Supply
The power supply of the M251 Logic Controller is
Real Time Clock
14
The M251 Logic Controller includes a
Real Time Clock (RTC) system, page 32
.
EIO0000003101.03
Run/Stop
The M251 Logic Controller can be operated externally by the following:
• A hardware
• An EcoStruxure Machine Expert software command
• The system variable PLC_W in a Relocation Table
• The Web server
Memory
This table describes the different types of memory:
Memory Type
RAM
Flash
Size
64 Mbytes, of which 8 Mbytes available for the application
128 Mbytes
Used to
Execute the application.
Save the program and data in case of a power interruption.
Removable Storage
M251 Logic Controllers include an embedded
.
The main uses of the SD card are:
• Initializing the controller with a new application
• Updating the controller firmware
• Applying post configuration files to the controller
• Applying recipes
• Receiving data logging files
Embedded Communication Features
The M251 Logic Controller native communication ports include (depending on the controller reference):
•
•
•
•
Expansion Module and Bus Coupler Compatibility
Refer to the compatibility tables in the EcoStruxure Machine Expert - Compatiblity and Migration User Guide.
EIO0000003101.03
15
M251 Logic Controllers
Reference
Digital Inputs
0
0
Digital Outputs
0
0
Communication Ports
1 serial line port
1 USB mini-B programming port
1 dual port Ethernet switch
1 CANopen port
1 serial line port
1 USB mini-B programming port
1 dual port Ethernet switch
1 Ethernet port for fieldbus
Maximum Hardware Configuration
Introduction
The M251 Logic Controller is a control system that offers a scalable solution with optimized configurations and an expandable architecture.
Local and Remote Configuration Principle
The following figure defines the local and remote configurations:
(1) Local configuration
(2) Remote configuration
M251 Logic Controller Local Configuration Architecture
Optimized local configuration and flexibility are provided by the association of:
• M251 Logic Controller
• TM4 expansion modules
• TM3 expansion modules
• TM2 expansion modules
Application requirements determine the architecture of your M251 Logic Controller configuration.
16 EIO0000003101.03
The following figure represents the components of a local configuration:
(A) Expansion modules (3 maximum)
(B) Expansion modules (7 maximum)
NOTE: It is prohibited to mount a TM2 module before any TM3 module as indicated in the following figure:
M251 Logic Controller Remote Configuration Architecture
Optimized remote configuration and flexibility are provided by the association of:
• M251 Logic Controller
• TM4 expansion modules
• TM3 expansion modules
• TM3 transmitter and receiver modules
Application requirements determine the architecture of your M251 Logic Controller configuration.
NOTE: You cannot use TM2 modules in configurations that include the TM3 transmitter and receiver modules.
The following figure represents the components of a remote configuration:
(1) Logic controller and modules
(C) TM3 expansion modules (7 maximum)
Maximum Number of Modules
The following table shows the maximum configuration supported:
EIO0000003101.03
17
References
TM251••••
TM251••••
TM3XREC1
Maximum
7 TM3 / TM2 expansion modules
3 TM4 expansion modules
7 TM3 expansion modules
Type of Configuration
Local
Local
Remote
NOTE: TM3 transmitter and receiver modules are not included in a count of the maximum number of expansion modules.
NOTE: The configuration with its TM4, TM3, and TM2 expansion modules is validated by EcoStruxure Machine Expert software in the Configuration window.
NOTE: In some environments, the maximum configuration populated by high consumption modules, coupled with the maximum distance allowable between the TM3 transmitter and receiver modules, may present bus communication issues although the EcoStruxure Machine Expert software allows for the configuration. In such a case you will need to analyze the power consumption of the modules chosen for your configuration, as well as the minimum cable distance required by your application, and possibly seek to optimize your choices.
TM2 Expansion Modules
Overview
You can expand the number of I/Os of your M251 Logic Controller by adding TM2
I/O expansion modules.
The following types of electronic modules are supported:
• TM2 digital I/O expansion modules
• TM2 analog I/O expansion modules
For more information, refer to the following documents:
• TM2 Digital I/O Expansion Modules Hardware Guide
• TM2 Analog I/O Expansion Modules Hardware Guide
NOTE: TM2 modules can only be used in the local configuration, and only if there is no TM3 transmitter and receiver modules present in the configuration.
NOTE: It is prohibited to mount a TM2 module before any TM3 module. The
TM2 modules must be mounted and configured at the end of the local configuration.
TM2 Digital Input Expansion Modules
Reference
TM2DAI8DT
TM2DDI8DT
TM2DDI16DT
The following table shows the compatible TM2 digital input expansion modules with the corresponding channel type, nominal voltage/current, and terminal type:
Channels Channel Type Terminal Type
8
8
16
Regular inputs
Regular inputs
Regular inputs
Voltage
Current
120 Vac
7.5 mA
24 Vdc
7 mA
24 Vdc
7 mA
Removable screw terminal block
Removable screw terminal block
Removable screw terminal block
18 EIO0000003101.03
Reference
TM2DDI16DK
TM2DDI32DK
Channels Channel Type
16
32
Regular inputs
Regular inputs
Voltage
Current
24 Vdc
5 mA
24 Vdc
5 mA
Terminal Type
HE10 (MIL 20) connector
HE10 (MIL 20) connector
TM2 Digital Output Expansion Modules
Reference
TM2DRA8RT
TM2DRA16RT
TM2DDO8UT
TM2DDO8TT
TM2DDO16UK
TM2DDO16TK
TM2DDO32UK
TM2DDO32TK
The following table shows the compatible TM2 digital output expansion modules with the corresponding channel type, nominal voltage/current, and terminal type:
Channels Channel type Terminal type
8
16
8
8
16
16
32
32
Relay outputs
Relay outputs
Regular transistor outputs (sink)
Regular transistor outputs (source)
Regular transistor outputs (sink)
Regular transistor outputs (source)
Regular transistor outputs (sink)
Regular transistor outputs (source)
Voltage
Current
30 Vdc / 240 Vac
2 A max
30 Vdc / 240 Vac
2 A max
24 Vdc
0.3 A max per output
24 Vdc
0.5 A max per output
24 Vdc
0.1 A max per output
24 Vdc
0.4 A max per output
24 Vdc
0.1 A max per output
24 Vdc
0.4 A max per output
Removable screw terminal block
Removable screw terminal block
Removable screw terminal block
Removable screw terminal block
HE10 (MIL 20) connector
HE10 (MIL 20) connector
HE10 (MIL 20) connector
HE10 (MIL 20) connector
TM2 Digital Mixed Input/Output Expansion Modules
Reference
TM2DMM8DRT
TM2DMM24DRF
The following table shows the compatible TM2 digital mixed I/O expansion modules with the corresponding channel type, nominal voltage/current, and terminal type:
Channels Channel type
4
4
16
Regular inputs
Relay outputs
Regular inputs
Voltage
Current
24 Vdc
7 mA
24 Vdc / 240 Vac
7 A maximum per common line / 2 A maximum per output
24 Vdc
7 mA
Terminal type
Removable screw terminal block
Non-removable spring terminal block
EIO0000003101.03
19
Reference Channels Channel type
8 Relay outputs
Voltage
Current
24 Vdc / 240 Vac
7 A maximum per common line / 2 A maximum per output
Terminal type
TM2 Analog Input Expansion Modules
Reference
TM2AMI2HT
TM2AMI2LT
TM2AMI4LT
TM2AMI8HT
TM2ARI8HT
TM2ARI8LRJ
TM2ARI8LT
The following table shows the compatible TM2 analog input expansion modules with the corresponding channel type, nominal voltage/current, and terminal type:
Channels Channel type Terminal Type
2
2
4
8
8
High-level inputs
Low-level inputs
Analog inputs
Analog inputs
Analog inputs
Voltage
Current
0...10 Vdc
4...20 mA
Thermocouple type J,
K,T
0...10 Vdc
0...20 mA
PT100/1000
Ni100/1000
0...20 mA
0...10 Vdc
NTC / PTC
Removable screw terminal block
Removable screw terminal block
Removable screw terminal block
Removable screw terminal block
8
8
Analog inputs
Analog inputs
PT100/1000
PT100/1000
Removable screw terminal block
RJ11 connector
Removable screw terminal block
TM2 Analog Output Expansion Modules
Reference
TM2AMO1HT
TM2AVO2HT
The following table shows the compatible TM2 analog output expansion modules with the corresponding channel type, nominal voltage/current, and terminal type:
Channels Channel type Terminal Type
1
2
Analog outputs
Analog outputs
Voltage
Current
0...10 Vdc
4...20 mA
+/- 10 Vdc
Removable screw terminal block
Removable screw terminal block
TM2 Analog Mixed Input/Output Expansion Modules
The following table shows the compatible TM2 analog mixed I/O expansion modules with the corresponding channel type, nominal voltage/current, and terminal type:
20 EIO0000003101.03
Reference
TM2AMM3HT
TM2AMM6HT
TM2ALM3LT
Channels Channel type
4
2
2
1
2
1
Analog inputs
Analog outputs
Analog inputs
Analog outputs
Low-level inputs
Analog outputs
Voltage
Current
0...10 Vdc 4...20 mA
0...10 Vdc 4...20 mA
0...10 Vdc 4...20 mA
0...10 Vdc 4...20 mA
Thermo J,K,T, PT100
0...10 Vdc 4...20 mA
Terminal Type
Removable screw terminal block
Removable screw terminal block
Removable screw terminal block
TM3 Expansion Modules
Introduction
The range of TM3 expansion modules includes:
• Digital modules, classified as follows:
◦
◦
◦
Mixed input/output modules, page 23
• Analog modules, classified as follows:
◦
◦
◦
Mixed input/output modules, page 26
•
•
•
Transmitter and Receiver modules, page 28
For more information, refer to the following documents in
:
• TM3 Digital I/O Modules Hardware Guide
• TM3 Analog I/O Modules Hardware Guide
• TM3 Expert I/O Modules Hardware Guide
• TM3 Safety Modules Hardware Guide
• TM3 Transmitter and Receiver Modules Hardware Guide
TM3 Digital Input Modules
Reference
TM3DI8A
TM3DI8
TM3DI8G
The following table shows the TM3 digital input expansion modules, with corresponding channel type, nominal voltage/current, and terminal type:
Channels Channel Type Terminal Type / Pitch
8
8
8
Regular inputs
Regular inputs
Regular inputs
Voltage
Current
120 Vac
7.5 mA
24 Vdc
7 mA
24 Vdc
7 mA
Removable screw terminal block / 5.08 mm
Removable screw terminal block / 5.08 mm
Removable spring terminal block / 5.08 mm
EIO0000003101.03
21
Reference
TM3DI16
TM3DI16G
TM3DI16K
TM3DI32K
16
16
32
Channels Channel Type
16 Regular inputs
Regular inputs
Regular inputs
Regular inputs
Voltage
Current
24 Vdc
7 mA
24 Vdc
7 mA
24 Vdc
5 mA
24 Vdc
5 mA
Terminal Type / Pitch
Removable screw terminal blocks / 3.81 mm
Removable spring terminal blocks / 3.81 mm
HE10 (MIL 20) connector
HE10 (MIL 20) connector
TM3 Digital Output Modules
Reference
TM3DQ8R
TM3DQ8RG
TM3DQ8T
TM3DQ8TG
TM3DQ8U
TM3DQ8UG
TM3DQ16R
TM3DQ16RG
TM3DQ16T
The following table shows the TM3 digital output expansion modules, with corresponding channel type, nominal voltage/current, and terminal type:
Channels Channel Type Terminal Type / Pitch
8
8
8
8
8
8
16
16
16
Relay outputs
Relay outputs
Regular transistor outputs (source)
Regular transistor outputs (source)
Regular transistor outputs (sink)
Regular transistor outputs (sink)
Relay outputs
Relay outputs
Regular transistor outputs (source)
Voltage
Current
24 Vdc / 240 Vac
7 A maximum per common line / 2 A maximum per output
24 Vdc / 240 Vac
7 A maximum per common line / 2 A maximum per output
24 Vdc
4 A maximum per common line/0.5 A maximum per output
24 Vdc
4 A maximum per common line/0.5 A maximum per output
24 Vdc
4 A maximum per common line/0.5 A maximum per output
24 Vdc
4 A maximum per common line/0.5 A maximum per output
24 Vdc / 240 Vac
8 A maximum per common line / 2 A maximum per output
24 Vdc / 240 Vac
8 A maximum per common line / 2 A maximum per output
24 Vdc
8 A maximum per common line / 0.5 A maximum per output
Removable screw terminal block / 5.08 mm
Removable spring terminal block / 5.08 mm
Removable screw terminal block / 5.08 mm
Removable spring terminal block / 5.08 mm
Removable screw terminal block / 5.08 mm
Removable spring terminal block / 5.08 mm
Removable screw terminal blocks / 3.81 mm
Removable spring terminal blocks / 3.81 mm
Removable screw terminal blocks / 3.81 mm
22 EIO0000003101.03
Reference
TM3DQ16TG
TM3DQ16U
TM3DQ16UG
TM3DQ16TK
TM3DQ16UK
TM3DQ32TK
TM3DQ32UK
Channels
16
16
16
16
16
32
32
Channel Type
Regular transistor outputs (source)
Regular transistor outputs (sink)
Regular transistor outputs (sink)
Regular transistor outputs (source)
Regular transistor outputs (sink)
Regular transistor outputs (source)
Regular transistor outputs (sink)
Voltage
Current
24 Vdc
8 A maximum per common line / 0.5 A maximum per output
24 Vdc
8 A maximum per common line / 0.5 A maximum per output
24 Vdc
8 A maximum per common line / 0.5 A maximum per output
24 Vdc
2 A maximum per common line / 0.1 A maximum per output
24 Vdc
2 A maximum per common line / 0.1 A maximum per output
24 Vdc
2 A maximum per common line / 0.1 A maximum per output
24 Vdc
2 A maximum per common line / 0.1 A maximum per output
Terminal Type / Pitch
Removable spring terminal blocks / 3.81 mm
Removable screw terminal blocks / 3.81 mm
Removable spring terminal blocks / 3.81 mm
HE10 (MIL 20) connector
HE10 (MIL 20) connector
HE10 (MIL 20) connectors
HE10 (MIL 20) connectors
TM3 Digital Mixed Input/Output Modules
Reference
TM3DM8R
TM3DM8RG
TM3DM16R (1)
Channels
4
4
4
4
8
8
This following table shows the TM3 mixed I/O modules, with corresponding channel type, nominal voltage/current, and terminal type:
Channel Type
Regular inputs
Relay outputs
Regular inputs
Relay outputs
Regular inputs
Relay outputs
Voltage
Current
24 Vdc
7 mA
24 Vdc / 240 Vac
7 A maximum per common line / 2
A maximum per output
24 Vdc
7 mA
24 Vdc / 240 Vac
7 A maximum per common line / 2
A maximum per output
24 Vdc
5 mA
24 Vdc / 240 Vac
4 A maximum per common line / 2
A maximum per output
Terminal Type / Pitch
Removable screw terminal block /
5.08 mm
Removable spring terminal block /
5.08 mm
Removable screw terminal block /
3.81 mm
EIO0000003101.03
23
Reference
TM3DM24R
Channels
16
8
Channel Type
Regular inputs
Relay outputs
Voltage
Current
24 Vdc
7 mA
24 Vdc / 240 Vac
7 A maximum per common line / 2
A maximum per output
TM3DM24RG
TM3DM32R (1)
16
8
16
16
Regular inputs
Relay outputs
Regular inputs
Relay outputs
24 Vdc
7 mA
24 Vdc / 240 Vac
7 A maximum per common line / 2
A maximum per output
24 Vdc
5 mA
24 Vdc / 240 Vac
4 A maximum per common line / 2
A maximum per output
(1) This expansion module is available only in selected countries.
Terminal Type / Pitch
Removable screw terminal block /
3.81 mm
Removable spring terminal block /
3.81 mm
Removable screw terminal block /
3.81 mm
TM3 Analog Input Modules
Reference
TM3AI2H
TM3AI2HG
TM3AI4
TM3AI4G
The following table shows the TM3 analog input expansion modules, with corresponding resolution, channel type, nominal voltage/current, and terminal type:
Resolution Channels Mode
16 bit, or 15 bit
+ sign
2
16 bit, or 15 bit
+ sign
2
12 bit, or 11 bit
+ sign
4
12 bit, or 11 bit
+ sign
4
Channel
Type inputs inputs inputs inputs
0...10 Vdc
-10…+10 Vdc
0...20 mA
4...20 mA
0...10 Vdc
-10…+10 Vdc
0...20 mA
4...20 mA
0...10 Vdc
-10…+10 Vdc
0...20 mA
4...20 mA
0...10 Vdc
-10…+10 Vdc
0...20 mA
4...20 mA
Terminal Type /
Pitch
Removable screw terminal block / 5.08
mm
Removable spring terminal block / 5.08
mm
Removable screw terminal block / 3.81
mm
Removable spring terminal blocks / 3.81
mm
24 EIO0000003101.03
Reference
TM3AI8
TM3AI8G
TM3TI4
TM3TI4G
TM3TI4D
TM3TI4DG
TM3TI8T
TM3TI8TG
Resolution Channels
12 bit, or 11 bit
+ sign
8
12 bit, or 11 bit
+ sign
16 bit, or 15 bit
+ sign
16 bit, or 15 bit
+ sign
8
4
4
Channel
Type inputs
Mode inputs inputs inputs inputs
0...10 Vdc
-10…+10 Vdc
0...20 mA
4...20 mA
0...20 mA extended
4...20 mA extended
0...10 Vdc
-10…+10 Vdc
0...20 mA
4...20 mA
0...20 mA extended
4...20 mA extended
0...10 Vdc
-10…+10 Vdc
0...20 mA
4...20 mA
Thermocouple
PT100/1000
NI100/1000
0...10 Vdc
-10…+10 Vdc
0...20 mA
4...20 mA
Thermocouple
PT100/1000
NI100/1000
Thermocouple 16 bit, or 15 bit
+ sign
4
16 bit, or 15 bit
+ sign
4
16 bit, or 15 bit
+ sign
8 inputs inputs
Thermocouple
16 bit, or 15 bit
+ sign
8 inputs
Thermocouple
NTC/PTC
Ohmmeter
Thermocouple
NTC/PTC
Ohmmeter
Terminal Type /
Pitch
Removable screw terminal block / 3.81
mm
Removable spring terminal blocks / 3.81
mm
Removable screw terminal block / 3.81
mm
Removable spring terminal blocks / 3.81
mm
Removable screw terminal block / 3.81
mm
Removable spring terminal blocks / 3.81
mm
Removable screw terminal block / 3.81
mm
Removable spring terminal blocks / 3.81
mm
TM3 Analog Output Modules
The following table shows the TM3 analog output modules, with corresponding resolution, channel type, nominal voltage/current, and terminal type:
EIO0000003101.03
25
Reference
TM3AQ2
TM3AQ2G
TM3AQ4
TM3AQ4G
Resolution Channels
12 bit, or 11 bit
+ sign
2
12 bit, or 11 bit
+ sign
12 bit, or 11 bit
+ sign
12 bit, or 11 bit
+ sign
2
4
4
Channel
Type outputs outputs outputs outputs
Mode
0...10 Vdc
-10…+10 Vdc
0...20 mA
4...20 mA
0...10 Vdc
-10…+10 Vdc
0...20 mA
4...20 mA
0...10 Vdc
-10…+10 Vdc
0...20 mA
4...20 mA
0...10 Vdc
-10…+10 Vdc
0...20 mA
4...20 mA
Terminal Type / Pitch
Removable screw terminal block / 5.08 mm
Removable spring terminal block / 5.08 mm
Removable screw terminal block / 5.08 mm
Removable spring terminal block / 5.08 mm
TM3 Analog Mixed Input/Output Modules
Reference
TM3AM6
TM3AM6G
TM3TM3
This following table shows the TM3 analog mixed I/O modules, with corresponding resolution, channel type, nominal voltage/current, and terminal type:
Resolution Channels Mode Terminal Type / Pitch
12 bit, or 11 bit + sign
4
2
Channel
Type inputs outputs
Removable screw terminal block / 3.81 mm
12 bit, or 11 bit + sign
4
2
16 bit, or 15 bit
+ sign
2
12 bit, or 11 bit + sign
1 inputs outputs inputs outputs
0...10 Vdc
-10...+10 Vdc
0...20 mA
4...20 mA
0...10 Vdc
-10...+10 Vdc
0...20 mA
4...20 mA
0...10 Vdc
-10...+10 Vdc
0...20 mA
4...20 mA
Thermocouple
PT100/1000
NI100/1000
0...10 Vdc
-10...+10 Vdc
0...20 mA
4...20 mA
Removable spring terminal block / 3.81 mm
Removable screw terminal block / 5.08 mm
26 EIO0000003101.03
Reference
TM3TM3G
Resolution Channels
16 bit, or 15 bit
+ sign
2
12 bit, or 11 bit + sign
1
Channel
Type inputs outputs
Mode
0...10 Vdc
-10...+10 Vdc
0...20 mA
4...20 mA
Thermocouple
PT100/1000
NI100/1000
0...10 Vdc
-10...+10 Vdc
0...20 mA
4...20 mA
Terminal Type / Pitch
Removable spring terminal block / 5.08 mm
TM3 Expert Modules
Reference
TM3XTYS4
TM3XHSC202
TM3XHSC202G
The following table shows the TM3 expert expansion modules, with corresponding terminal types:
Description
TeSys module
High Speed Counting (HSC) module
High Speed Counting (HSC) module
Terminal Type / Pitch
4 front connectors RJ-45
1 removable power supply connector
/ 5.08 mm
Removable screw terminal blocks /
3.81 mm
Removable spring terminal blocks /
3.81 mm
TM3 Safety Modules
Reference
TM3SAC5R
TM3SAC5RG
TM3SAF5R
This table contains the TM3 safety modules, with the corresponding channel type, nominal voltage/current, and terminal type:
Channel type Terminal type Function
Category
1 function, up to category 3
Channels
1 or 2 (1)
Start (2)
3 in parallel
1 function, up to category 3
1 or 2 (1)
Start (2)
3 in parallel
1 function, up to category 4
2 (1)
Start
3 in parallel
Safety input
Input
Relay outputs
Normally open
Safety input
Input
Relay outputs
Normally open
Safety inputs
Input
Relay outputs
Normally open
Voltage
Current
24 Vdc
100 mA maximum
24 Vdc / 230 Vac
6 A maximum per output
24 Vdc
100 mA maximum
24 Vdc / 230 Vac
6 A maximum per output
24 Vdc
100 mA maximum
24 Vdc / 230 Vac
6 A maximum per output
3.81 mm (0.15 in.) and
5.08 mm (0.20 in.), removable screw terminal block
3.81 mm (0.15 in.) and
5.08 mm (0.20 in.), removable spring terminal block
3.81 mm (0.15 in.) and
5.08 mm (0.20 in.), removable screw terminal block
EIO0000003101.03
27
Reference
TM3SAF5RG
TM3SAFL5R
TM3SAFL5RG
TM3SAK6R
TM3SAK6RG
Function
Category
1 function, up to category 4
Channels
2 (1)
Start
3 in parallel
2 functions, up to category 3
2 (1)
Start
3 in parallel
2 functions, up to category 3
2 (1)
Start
3 in parallel
3 functions, up to category 4
1 or 2 (1)
Start
3 in parallel
3 functions, up to category 4
1 or 2 (1)
Start
3 in parallel
Channel type
Safety inputs
Input
Relay outputs
Normally open
Safety inputs
Input
Relay outputs
Normally open
Safety inputs
Input
Relay outputs
Normally open
Safety inputs
Input
Relay outputs
Normally open
Safety inputs
Input
Relay outputs
Normally open
Voltage
Current
24 Vdc
100 mA maximum
24 Vdc / 230 Vac
6 A maximum per output
24 Vdc
100 mA maximum
24 Vdc / 230 Vac
6 A maximum per output
24 Vdc
100 mA maximum
24 Vdc / 230 Vac
6 A maximum per output
24 Vdc
100 mA maximum
24 Vdc / 230 Vac
6 A maximum per output
24 Vdc
100 mA maximum
24 Vdc / 230 Vac
6 A maximum per output
(1) Depending on external wiring
(2) Non-monitored start
Terminal type
3.81 mm (0.15 in.) and
5.08 mm (0.20 in.), removable spring terminal block
3.81 mm (0.15 in.) and
5.08 mm (0.20 in.), removable screw terminal block
3.81 mm (0.15 in.) and
5.08 mm (0.20 in.), removable spring terminal block
3.81 mm (0.15 in.) and
5.08 mm (0.20 in.), removable screw terminal block
3.81 mm (0.15 in.) and
5.08 mm (0.20 in.), removable spring terminal block
TM3 Transmitter and Receiver Modules
Reference
TM3XTRA1
TM3XREC1
The following table shows the TM3 transmitter and receiver expansion modules:
Description
Data transmitter module for remote I/O
Data receiver module for remote I/O
Terminal Type / Pitch
1 front connector RJ-45
1 screw for functional ground connection
1 front connector RJ-45
Power supply connector / 5.08 mm
TM3 Bus Couplers
Introduction
The TM3 bus coupler is a device designed to manage fieldbus communication when using TM2 and TM3 expansion modules in a distributed architecture.
For more information, refer to the Modicon TM3 Bus Coupler Hardware Guide
(see Modicon TM3 Bus Coupler, Hardware Guide).
28 EIO0000003101.03
Modicon TM3 Bus Couplers
The following table shows the TM3 bus couplers, with ports and terminal types:
Reference
TM3BCEIP
TM3BCSL
TM3BCCO
Port
2 isolated switched
Ethernet ports
1 USB port
2 isolated RS-485 ports (daisy-chained)
1 USB port
2 isolated CANopen ports (daisy-chained)
1 USB port
Communication type
EtherNet/IP
Modbus TCP
USB 2.0
Serial Line
Modbus
USB 2.0
CANopen
USB 2.0
Terminal type
RJ45
USB mini-B
RJ45
USB mini-B
RJ45
USB mini-B
TM4 Expansion Modules
Introduction
The range of TM4 expansion modules includes communication modules.
For more information, refer to the TM4 Expansion Modules Hardware Guide.
TM4 Expansion Modules
The following table shows the TM4 expansion module features:
Module reference
TM4ES4
TM4PDPS1
Type
Ethernet communication
PROFIBUS DP slave communication
Terminal type
4 RJ45 connectors
1 screw for functional ground connection
1 SUB-D 9 pins female connector
1 screw for functional ground connection
NOTE: The TM4ES4 module has two applications: expansion or standalone. For more information, refer to TM4 Compatibility.
TM5 Fieldbus Interfaces
Introduction
The TM5 fieldbus interfaces are devices designed to manage EtherNet/IP communication when using TM5 System and TM7 expansion modules with a controller in a distributed architecture.
For more information, refer to the Modicon TM5 System Interface – Hardware
Guide.
EIO0000003101.03
29
TM5 Fieldbus Interfaces
The following table shows the TM5 fieldbus interfaces with ports and terminal type:
Reference
TM5NEIP1
Port Communication type
2 Ethernet switched ports EtherNet/IP
Terminal type
RJ45
TM5 CANopen Fieldbus Interfaces
Introduction
The TM5 fieldbus module is a CANopen interface with built-in power distribution and is the first TM5 distributed I/O island.
For more information, refer to the Modicon TM5 CANopen Interface Hardware
Guide.
Modicon TM5 CANopen Fieldbus Interfaces
The following table shows the TM5 CANopen fieldbus interfaces:
Reference
TM5NCO1
Communication type
CANopen
Terminal type
1 SUB-D 9, male
TM7 CANopen Fieldbus Interfaces
Introduction
The TM7 fieldbus modules are CANopen interfaces with 24 Vdc digital configurable input or output on 8 or 16 channels.
For more information, refer to the Modicon TM7 CANopen Interface I/O Blocks
Hardware Guide.
Modicon TM7 CANopen Fieldbus Interfaces
Reference
TM7NCOM08B
TM7NCOM16A
TM7NCOM16B
The following table shows the TM7 CANopen fieldbus interfaces:
Number of channels
8 inputs
8 outputs
16 inputs
16 outputs
16 inputs
16 outputs
Voltage/Current
24 Vdc / 4 mA
24 Vdc / 500 mA
24 Vdc / 4 mA
24 Vdc / 500 mA
24 Vdc / 4 mA
24 Vdc / 500 mA
Communication type
CANopen
CANopen
CANopen
Terminal type
M8 Connector
M8 Connector
M12 Connector
30 EIO0000003101.03
Accessories
Overview
This section describes the accessories and cables.
Accessories
Reference
TMASD1
TMAT2PSET
NSYTRAAB35
TM2XMTGB
TM200RSRCEMC
Description
Set of 5 removable screw terminal block
End brackets
Grounding Bar
Shielding take-up clip
Use
Use to update the controller firmware, initialize a controller with a new application or clone a controller, manage user files, etc.,.
Connects 24 Vdc power supply.
Quantity
1
1
Helps secure the controller or receiver module and their expansion modules on a top hat section rail (DIN rail).
Connects the cable shield and the module to the functional ground.
Mounts and connects the ground to the cable shielding.
1
1
25 pack
Cables
Reference
TCSXCNAMUM3P
TCSMCN3M4F3C2
TCSMCN3M4M3S2
490NTW000••
490NTW000••U
TCSECE3M3M••S4
TCSECU3M3M••S4
VW3A8306R••
Description
Terminal port/USB port cordset
RS-232 serial link cordset
1 RJ45 connector and 1 SUB-D 9 connector
RS-232 serial link cordset
1 RJ45 connector and 1 SUB-D 9 connector
Ethernet shielded cable for DTE connections
Details
From the USB mini-B port on the M251 Logic Controller to USB port on the PC terminal.
For DTE terminal (printer).
For DCE terminal (modem, converter).
Length
3 m
(10 ft)
3 m
(9.84 ft)
3 m
(9.84 ft)
2 RJ45 connectors
Standard cable, equipped with RJ45 connectors at each end for DTE.
CE compliant.
Standard cable, equipped with RJ45 connectors at each end for DTE.
UL compliant.
Cable for harsh environment, equipped with RJ45 connectors at each end.
CE compliant.
Cable for harsh environment, equipped with RJ45 connectors at each end.
UL compliant.
Cable equipped with RJ45 connectors at each end for
Modbus serial link.
2, 5, 12, 40, or 80 m
(6.56, 16.4, 39.37, 131.23 or
262.47 ft)
2, 5, 12, 40, or 80 m
(6.56, 16.4, 39.37, 131.23, or
262.47 ft)
1, 2, 3, 5, or 10 m
(3.28, 6.56, 9.84, 16.4, 32.81
ft)
1, 2, 3, 5, or 10 m
(3.28, 6.56, 9.84, 16.4, 32.81
ft)
0.3, 1, or 3 m
(0.98, 3.28, or 9.84 ft)
EIO0000003101.03
31
M251 Features
What’s in This Chapter
Overview
This chapter describes the Modicon M251 Logic Controller features.
Real Time Clock (RTC)
Overview
The M251 Logic Controller includes an RTC to provide system date and time information, and to support related functions requiring a real-time clock. To continue keeping time when power is off, a non-rechargeable battery is required
(see reference below). A battery LED on the front panel of the controller indicates if the battery is depleted or absent.
This table shows how RTC drift is managed:
RTC Characteristics
RTC drift
Description
Less than 60 seconds per month without any user calibration at
25 °C (77 °F)
Battery
The controller has one battery.
In the event of a power interruption, the backup battery maintains the RTC for the controller.
This table shows the characteristics of the battery:
Characteristics
Use
Backup life
Battery monitoring
Replaceable
Controller battery type
Description
In the event of a transient power outage, the battery powers the RTC.
At least 2 years at 25 °C maximum (77 °F). At higher temperatures, the time is reduced.
Yes
Yes
Lithium carbon monofluoride, type Panasonic BR2032
Installing and Replacing the Battery
While lithium batteries are preferred due to their slow discharge and long life, they can present hazards to personnel, equipment and the environment and must be handled properly.
32 EIO0000003101.03
DANGER
EXPLOSION, FIRE, OR CHEMICAL BURNS
• Replace with identical battery type.
• Follow all the instructions of the battery manufacturer.
• Remove all replaceable batteries before discarding unit.
• Recycle or properly dispose of used batteries.
• Protect battery from any potential short-circuit.
• Do not recharge, disassemble, heat above 100 °C (212 °F), or incinerate.
• Use your hands or insulated tools to remove or replace the battery.
• Maintain proper polarity when inserting and connecting a new battery.
Failure to follow these instructions will result in death or serious injury.
To install or replace the battery, follow these steps:
Step Action
1 Remove power from your controller.
2 Use an insulated screw-driver to pull out the battery holder.
EIO0000003101.03
3
4
Side out the battery holder of the controller.
Remove the battery from the battery holder.
5 Insert the new battery into the battery holder in accordance with the polarity markings on the battery.
33
Step Action
6 Slide in the battery holder of the controller and verify that the latch clicks into place.
7
8
Power up your M251 Logic Controller.
Set the internal clock. For further details on the internal clock, refer to M251 Logic
Controller Programming Guide (see Modicon M251 Logic Controller, Programming Guide).
NOTE: Replacement of the battery in the controllers other than with the type specified in this documentation may present a risk of fire or explosion.
WARNING
IMPROPER BATTERY CAN PROVOKE FIRE OR EXPLOSION
Replace battery only with identical type: Panasonic Type BR2032.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Run/Stop
Run/Stop
The M251 Logic Controller can be operated externally by the following:
• A hardware Run/Stop switch.
• An EcoStruxure Machine Expert software command.
• The system variable PLC_W in a Relocation Table (see Modicon M251 Logic
Controller, Programming Guide).
• The Web server (see Modicon M251 Logic Controller, Programming Guide).
34 EIO0000003101.03
The M251 Logic Controller has a Run/Stop hardware switch, which puts the controller in a RUN or STOP state.
SD Card
Overview
EIO0000003101.03
When handling the SD card, follow the instructions below to help prevent internal data on the SD card from being corrupted or lost or an SD card malfunction from occurring:
NOTICE
LOSS OF APPLICATION DATA
• Do not store the SD card where there is static electricity or probable electromagnetic fields.
• Do not store the SD card in direct sunlight, near a heater, or other locations where high temperatures can occur.
• Do not bend the SD card.
• Do not drop or strike the SD card against another object.
• Keep the SD card dry.
• Do not touch the SD card connectors.
• Do not disassemble or modify the SD card.
• Use only SD cards formatted using FAT or FAT32.
Failure to follow these instructions can result in equipment damage.
The M251 Logic Controller does not recognize NTFS formatted SD cards. Format the SD card on your computer using FAT or FAT32.
When using the M251 Logic Controller and an SD card, observe the following to avoid losing valuable data:
• Accidental data loss can occur at any time. Once data is lost it cannot be recovered.
• If you forcibly extract the SD card, data on the SD card may become corrupted.
• Removing an SD card that is being accessed could damage the SD card, or corrupt its data.
• If the SD card is not positioned correctly when inserted into the controller, the data on the card and the controller could become damaged.
35
36
NOTICE
LOSS OF APPLICATION DATA
• Backup SD card data regularly.
• Do not remove power or reset the controller, and do not insert or remove the
SD card while it is being accessed.
Failure to follow these instructions can result in equipment damage.
This figure shows the SD card slot:
It is possible to set the Write-Control Tab to prevent write operations to the SD card. Push the tab up, as shown in the example on the right-hand side, to release the lock and enable writing to the SD card. Before using an SD card, read the manufacturer's instructions.
EIO0000003101.03
Step
1
Action
Insert the SD card into the SD card slot:
2 Push until you hear it “click”:
Ethern et 2
SD Card Slot Characteristics
Topic
Supported type
Global memory
Characteristics
Standard Capacity
High Capacity
Size
TMASD1 Characteristics
Characteristics
Card removal durability
File retention time
Flash type
Memory size
Ambient operation temperature
Storage temperature
Relative humidity
Write/Erase cycles
Description
SD (SDSC)
SDHC
16 GB max.
Description
Minimum 1000 times
10 years @ 25 °C (77 °F)
SLC NAND
256 MB
–10 … +85°C (14...185 °F)
–25 … +85°C (–13...185 °F)
95% max. non-condensing
3,000,000 (approximately)
EIO0000003101.03
37
M251 Installation
What’s in This Chapter
M251 Logic Controller General Rules for Implementing ....................................38
Overview
This chapter provides installation safety guidelines, device dimensions, mounting instructions, and environmental specifications.
M251 Logic Controller General Rules for Implementing
Environmental Characteristics
Enclosure Requirements
M251 Logic Controller system components are designed as Zone B, Class A industrial equipment according to IEC/CISPR Publication 11. If they are used in environments other than those described in the standard, or in environments that do not meet the specifications in this manual, the ability to meet electromagnetic compatibility requirements in the presence of conducted and/or radiated interference may be reduced.
All M251 Logic Controller system components meet European Community (CE) requirements for open equipment as defined by IEC/EN 61131-2. You must install them in an enclosure designed for the specific environmental conditions and to minimize the possibility of unintended contact with hazardous voltages. Use metal enclosures to improve the electromagnetic immunity of your M251 Logic
Controller system. Use enclosures with a keyed locking mechanism to minimize unauthorized access.
Environmental Characteristics
All the M251 Logic Controller module components are electrically isolated between the internal electronic circuit and the input/output channels within the limits set forth and described by these environmental characteristics. For more information on electrical isolation, see the technical specifications of your particular controller found later in the current document. This equipment meets CE requirements as indicated in the table below. This equipment is intended for use in a Pollution Degree 2 industrial environment.
WARNING
UNINTENDED EQUIPMENT OPERATION
Do not exceed any of the rated values specified in the environmental and electrical characteristics tables.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
The following table shows the general environmental characteristics:
38 EIO0000003101.03
Characteristic
Standard compliance
Ambient operating temperature
Storage temperature
Relative humidity
Degree of pollution
Degree of protection
Corrosion immunity
Operating altitude
Storage altitude
Vibration resistance
Mechanical shock resistance
–
–
Minimum
Specification
IEC/EN 61131-2
IEC/EN 61010-2-
201
–
–
IEC/EN 60664-1
–
–
IEC/EN 61131-2
–
IEC/EN 61131-2
–
Tested Range
–
Horizontal installation –10...55 °C (14...131 °F)
Vertical installation
–25...70 °C (- 13...158 °F)
–10...35 °C (14...95 °F)
Transport and storage 10...95 % (non-condensing)
Operation 10...95 % (non-condensing)
2
IP20 with protective covers in place
Atmosphere free from corrosive gases
0...2000 m (0...6560 ft)
0...3000 m (0...9843 ft)
Panel mounting or mounted on a top hat section rail (DIN rail)
3.5 mm (0.13 in) fixed amplitude from
5...8.4 Hz
9.8 m/s 2 (32.15 ft/s 2 ) (1 g n
) fixed acceleration from 8.4...150 Hz
10 mm (0.39 in) fixed amplitude from
5...8.7 Hz
29.4 m/s 2 (96.45 ft/s 2 ) (3 g n
) fixed acceleration from 8.7...150 Hz
147 m/s 2 or 482.28 ft/s 2 (15 g n
) for a duration of 11 ms
NOTE: The tested ranges may indicate values beyond that of the IEC Standard. However, our internal standards define what is necessary for industrial environments. In all cases, we uphold the minimum specification if indicated.
Electromagnetic Susceptibility
Characteristic
Electrostatic discharge
Radiated electromagnetic field
Fast transients burst
The M251 Logic Controller system meets electromagnetic susceptibility specifications as indicated in the following table:
Minimum Specification
IEC/EN 61000-4-2
IEC/EN 61131-2
IEC/EN 61000-4-3
IEC/EN 61131-2
IEC/EN 61000-4-4
IEC/EN 61131-2
Tested Range
8 kV (air discharge)
4 kV (contact discharge)
10 V/m (80...1000 MHz)
3 V/m (1.4...2 GHz)
1 V/m (2...3 GHz)
24 Vdc main power lines
24 Vdc I/Os
2 kV (CM 1 and DM
2 kV (clamp)
1 kV (clamp) Relay output
Digital I/Os 1 kV (clamp)
Communication line 1 kV (clamp)
2 )
EIO0000003101.03
39
Characteristic
Surge immunity
Minimum Specification
IEC/EN 61000-4-5
IEC/EN 61131-2
Tested Range
–
DC Power lines
Relay Outputs
24 Vdc I/Os
Shielded cable
(between shield and ground)
CM 1
0.5 kV
–
–
1 kV
DM
–
2
0.5 kV
–
–
Induced electromagnetic field IEC/EN 61000-4-6
IEC/EN 61131-2
IEC 61000-6-4
10 Vrms (0.15...80 MHz)
Conducted emission
Radiated emission
IEC/EN 61131-2
IEC 61000-6-4
IEC/EN 61131-2
• 10...150 kHz: 120...69 dBμV/m QP
• 150...1500 kHz: 79...63 dBμV/m QP
• 1.5...30 MHz: 63 dBμV/m QP
30...230 MHz: 40 dBμV/m QP
230...1000 MHz: 47 dBμV/m QP
1 Common Mode
2 Differential Mode
NOTE: The tested ranges may indicate values beyond that of the IEC Standard. However, our internal standards define what is necessary for industrial environments. In all cases, we uphold the minimum specification if indicated.
Certifications and Standards
Introduction
For information on certifications and conformance to standards, go to www.se.
com .
For product compliance and environmental information (RoHS, REACH, PEP,
EOLI, etc.), go to www.se.com/green-premium .
M251 Logic Controller Installation
Installation and Maintenance Requirements
Before Starting
Read and understand this chapter before beginning the installation of your system.
The use and application of the information contained herein require expertise in the design and programming of automated control systems. Only you, the user, machine builder or integrator, can be aware of all the conditions and factors present during installation and setup, operation, and maintenance of the machine or process, and can therefore determine the automation and associated equipment and the related safeties and interlocks which can be effectively and properly used. When selecting automation and control equipment, and any other related equipment or software, for a particular application, you must also consider any applicable local, regional or national standards and/or regulations.
Pay particular attention in conforming to any safety information, different electrical requirements, and normative standards that would apply to your machine or process in the use of this equipment.
40 EIO0000003101.03
Disconnecting Power
All options and modules should be assembled and installed before installing the control system on a mounting rail, onto a mounting plate or in a panel. Remove the control system from its mounting rail, mounting plate or panel before disassembling the equipment.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Disconnect all power from all equipment including connected devices prior to removing any covers or doors, or installing or removing any accessories, hardware, cables, or wires except under the specific conditions specified in the appropriate hardware guide for this equipment.
• Always use a properly rated voltage sensing device to confirm the power is off where and when indicated.
• Replace and secure all covers, accessories, hardware, cables, and wires and confirm that a proper ground connection exists before applying power to the unit.
• Use only the specified voltage when operating this equipment and any associated products.
Failure to follow these instructions will result in death or serious injury.
Programming Considerations
WARNING
UNINTENDED EQUIPMENT OPERATION
• Only use software approved by Schneider Electric for use with this equipment.
• Update your application program every time you change the physical hardware configuration.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Operating Environment
In addition to the Environmental Characteristics , refer to Product Related
Information in the beginning of the present document for important information regarding installation in hazardous locations for this specific equipment.
WARNING
UNINTENDED EQUIPMENT OPERATION
Install and operate this equipment according to the conditions described in the
Environmental Characteristics.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
EIO0000003101.03
41
Installation Considerations
WARNING
UNINTENDED EQUIPMENT OPERATION
• Use appropriate safety interlocks where personnel and/or equipment hazards exist.
• Install and operate this equipment in an enclosure appropriately rated for its intended environment and secured by a keyed or tooled locking mechanism.
• Use the sensor and actuator power supplies only for supplying power to the sensors or actuators connected to the module.
• Power line and output circuits must be wired and fused in compliance with local and national regulatory requirements for the rated current and voltage of the particular equipment.
• Do not use this equipment in safety-critical machine functions unless the equipment is otherwise designated as functional safety equipment and conforming to applicable regulations and standards.
• Do not disassemble, repair, or modify this equipment.
• Do not connect any wiring to reserved, unused connections, or to connections designated as No Connection (N.C.).
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: JDYX2 or JDYX8 fuse types are UL-recognized and CSA approved.
M251 Logic Controller Mounting Positions and Clearances
Introduction
This section describes the correct mounting positions for the M251 Logic
Controller.
NOTE: Keep adequate spacing for proper ventilation and to maintain the operating temperature specified in the
Environmental Characteristics, page
.
Correct Mounting Position
To obtain optimal operating characteristics, the M251 Logic Controller should be mounted horizontally on a vertical plane as shown in the figure below:
42 EIO0000003101.03
Acceptable Mounting Positions
The M251 Logic Controller can also be mounted vertically on a vertical plane as shown below.
NOTE: Expansion modules must be mounted above the controller.
Incorrect Mounting Position
The M251 Logic Controller should only be positioned as shown in the Correct
Mounting Position figure. The figures below show the incorrect mounting positions.
Minimum Clearances
WARNING
UNINTENDED EQUIPMENT OPERATION
• Place devices dissipating the most heat at the top of the cabinet and ensure adequate ventilation.
• Avoid placing this equipment next to or above devices that might cause overheating.
• Install the equipment in a location providing the minimum clearances from all adjacent structures and equipment as directed in this document.
• Install all equipment in accordance with the specifications in the related documentation.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
The M251 Logic Controller has been designed as an IP20 product and must be installed in an enclosure. Clearances must be respected when installing the product.
There are 3 types of clearances to consider:
• The M251 Logic Controller and all sides of the cabinet (including the panel door).
EIO0000003101.03
43
• The M251 Logic Controller terminal blocks and the wiring ducts to help reduce potential electromagnetic interference between the controller and the duct wiring.
• The M251 Logic Controller and other heat generating devices installed in the same cabinet.
The following figure shows the minimum clearances that apply to all M251 Logic
Controller references:
Top Hat Section Rail (DIN rail)
Dimensions of Top Hat Section Rail DIN Rail
You can mount the controller or receiver and their expansions on a 35 mm (1.38
in.) top hat section rail (DIN rail). The DIN rail can be attached to a smooth mounting surface or suspended from a EIA rack or mounted in a NEMA cabinet.
Symmetric Top Hat Section Rails (DIN Rail)
The following illustration and table indicate the references of the top hat section rails (DIN rail) for the wall-mounting range:
Reference
NSYSDR50A
NSYSDR60A
NSYSDR80A
NSYSDR100A
A
A
A
Type
A
Rail Length (B)
450 mm (17.71 in.)
550 mm (21.65 in.)
750 mm (29.52 in.)
950 mm (37.40 in.)
44 EIO0000003101.03
The following illustration and table indicate the references of the symmetric top hat section rails (DIN rail) for the metal enclosure range:
Reference
NSYSDR60
NSYSDR80
NSYSDR100
NSYSDR120
Type
A
A
A
A
Rail Length (B-12 mm)
588 mm (23.15 in.)
788 mm (31.02 in.)
988 mm (38.89 in.)
1188 mm (46.77 in.)
The following illustration and table indicate the references of the symmetric top hat section rails (DIN rail) of 2000 mm (78.74 in.):
Reference Type
NSYSDR200 1 A
NSYSDR200D 2
1 Unperforated galvanized steel
A
2 Perforated galvanized steel
Rail Length
2000 mm (78.74 in.)
Double-Profile Top Hat Section Rails (DIN rail)
The following illustration and table indicate the references of the double-profile top hat section rails (DIN rails) for the wall-mounting range:
EIO0000003101.03
45
Reference
NSYDPR25
NSYDPR35
NSYDPR45
NSYDPR55
NSYDPR65
NSYDPR75
Type
W
W
W
W
W
W
Rail Length (B)
250 mm (9.84 in.)
350 mm (13.77 in.)
450 mm (17.71 in.)
550 mm (21.65 in.)
650 mm (25.60 in.)
750 mm (29.52 in.)
The following illustration and table indicate the references of the double-profile top hat section rails (DIN rail) for the floor-standing range:
Reference
NSYDPR60
NSYDPR80
NSYDPR100
NSYDPR120
F
F
F
Type
F
Rail Length (B)
588 mm (23.15 in.)
788 mm (31.02 in.)
988 mm (38.89 in.)
1188 mm (46.77 in.)
Installing and Removing the Controller with Expansions
Overview
This section describes how to install and remove the controller with its expansion modules from a top hat section rail (DIN rail).
To assemble expansion modules to a controller or receiver module, or to other modules, refer to the respective expansion modules hardware guide(s).
Installing a Controller with its Expansions on a DIN Rail
The following procedure describes how to install a controller with its expansion modules on a top hat section rail (DIN rail):
46 EIO0000003101.03
Step
1
2
Action
Fasten the top hat section rail (DIN rail) to a panel surface using screws.
Position the top groove of the controller and its expansion modules on the top edge of the DIN rail and press the assembly against the top hat section rail (DIN rail) until you hear the top hat section rail (DIN rail) clip snap into place.
1
3
2
3
Place 2 terminal block end clamps on both sides of the controller and expansion module assembly.
NOTE: Type NSYTRAAB35 or equivalent terminal block end clamps help minimize sideways movement and improve the shock and vibration characteristics of the controller and expansion module assembly.
Removing a Controller with its Expansions from a Top Hat Section Rail
(DIN Rail)
The following procedure describes how to remove a controller with its expansion modules from a top hat section rail (DIN rail):
Step
1
2
Action
Remove all power from your controller and expansion modules.
Insert a flat screwdriver into the slot of the top hat section rail (DIN rail) clip.
EIO0000003101.03
3
4
Pull down the DIN rail clip.
Pull the controller and its expansion modules from the top hat section rail (DIN rail) from the bottom.
47
Direct Mounting on a Panel Surface
Overview
This section shows how to install M251 Logic Controller on a panel surface using the mounting holes.
Mounting Hole Layout
This diagram shows the mounting hole layout for M251 Logic Controller:
M251 Electrical Requirements
Wiring Best Practices
Overview
This section describes the wiring guidelines and associated best practices to be respected when using the M251 Logic Controller system.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Disconnect all power from all equipment including connected devices prior to removing any covers or doors, or installing or removing any accessories, hardware, cables, or wires except under the specific conditions specified in the appropriate hardware guide for this equipment.
• Always use a properly rated voltage sensing device to confirm the power is off where and when indicated.
• Replace and secure all covers, accessories, hardware, cables, and wires and confirm that a proper ground connection exists before applying power to the unit.
• Use only the specified voltage when operating this equipment and any associated products.
Failure to follow these instructions will result in death or serious injury.
48 EIO0000003101.03
WARNING
LOSS OF CONTROL
• The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical control functions, provide a means to achieve a safe state during and after a path failure. Examples of critical control functions are emergency stop and overtravel stop, power outage and restart.
• Separate or redundant control paths must be provided for critical control functions.
• System control paths may include communication links. Consideration must be given to the implications of unanticipated transmission delays or failures of the link.
• Observe all accident prevention regulations and local safety guidelines.
1
• Each implementation of this equipment must be individually and thoroughly tested for proper operation before being placed into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
1 For additional information, refer to NEMA ICS 1.1 (latest edition), "Safety
Guidelines for the Application, Installation, and Maintenance of Solid State
Control" and to NEMA ICS 7.1 (latest edition), "Safety Standards for Construction and Guide for Selection, Installation and Operation of Adjustable-Speed Drive
Systems" or their equivalent governing your particular location.
Wiring Guidelines
This rules must be applied when wiring an M251 Logic Controller system:
• Communication wiring must be kept separate from the power wiring. Route these 2 types of wiring in separate cable ducting.
• Verify that the operating conditions and environment are within the specification values.
• Use proper wire sizes to meet voltage and current requirements.
• Use copper conductors (required).
• Use twisted pair, shielded cables for networks, and fieldbus.
Use shielded, properly grounded cables for all communication connections. If you do not use shielded cable for these connections, electromagnetic interference can cause signal degradation. Degraded signals can cause the controller or attached modules and equipment to perform in an unintended manner.
WARNING
UNINTENDED EQUIPMENT OPERATION
• Use shielded cables for all communication signals.
• Ground cable shields for all communication signals at a single point 1 .
• Route communication separately from power cables.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
1 Multipoint grounding is permissible if connections are made to an equipotential ground plane dimensioned to help avoid cable shield damage in the event of power system short-circuit currents.
For more details, refer to
Grounding Shielded Cables, page 53 .
EIO0000003101.03
49
NOTE: Surface temperatures may exceed 60 °C (140 °F).
To conform to IEC 61010 standards, route primary wiring (wires connected to power mains) separately and apart from secondary wiring (extra low voltage wiring coming from intervening power sources). If that is not possible, double insulation is required such as conduit or cable gains.
Rules for Removable Screw Terminal Block
The following tables show the cable types and wire sizes for a 5.08 pitch removable screw terminal block (power supply):
The use of copper conductors is required.
DANGER
LOOSE WIRING CAUSES ELECTRIC SHOCK
Tighten connections in conformance with the torque specifications.
Failure to follow these instructions will result in death or serious injury.
DANGER
FIRE HAZARD
Use only the correct wire sizes for the maximum current capacity of the power supplies.
Failure to follow these instructions will result in death or serious injury.
DC Power Supply Characteristics and Wiring
Overview
This section provides the characteristics and the wiring diagrams of the DC power supply.
DC Power Supply Voltage Range
If the specified voltage range is not maintained, outputs may not switch as expected. Use appropriate safety interlocks and voltage monitoring circuits.
50 EIO0000003101.03
DANGER
FIRE HAZARD
• Use only the correct wire sizes for the maximum current capacity of the I/O channels and power supplies.
• For relay output (2 A) wiring, use conductors of at least 0.5 mm 2 (AWG 20) with a temperature rating of at least 80 °C (176 °F).
• For common conductors of relay output wiring (7 A), or relay output wiring greater than 2 A, use conductors of at least 1.0 mm 2 (AWG 16) with a temperature rating of at least 80 °C (176 °F).
Failure to follow these instructions will result in death or serious injury.
WARNING
UNINTENDED EQUIPMENT OPERATION
Do not exceed any of the rated values specified in the environmental and electrical characteristics tables.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
DC Power Supply Requirements
The M251 Logic Controllerand associated I/O (TM2, TM3, with a nominal voltage of 24 Vdc. The 24 Vdc power supplies must be rated Safety Extra Low Voltage
(SELV) or Protective Extra Low Voltage (PELV) according to IEC 61140. These power supplies are isolated between the electrical input and output circuits of the power supply.
WARNING
POTENTIAL OF OVERHEATING AND FIRE
• Do not connect the equipment directly to line voltage.
• Use only isolating PELV power supplies and circuits to supply power to the equipment 1 .
Failure to follow these instructions can result in death, serious injury, or equipment damage.
1 For compliance to UL (Underwriters Laboratories) requirements, the power supply must also conform to the various criteria of NEC Class 2, and be inherently current limited to a maximum power output availability of less than 100 VA
(approximately 4 A at nominal voltage), or not inherently limited but with an additional protection device such as a circuit breaker or fuse meeting the requirements of clause 9.4 Limited-energy circuit of UL 61010-1. In all cases, the current limit should never exceed that of the electric characteristics and wiring diagrams for the equipment described in the present documentation. In all cases, the power supply must be grounded, and you must separate Class 2 circuits from other circuits. If the indicated rating of the electrical characteristics or wiring diagrams are greater than the specified current limit, multiple Class 2 power supplies may be used.
Controller DC Characteristics
This table shows the characteristics of the DC power supply required for the controller:
EIO0000003101.03
51
Characteristic
Rated voltage
Power supply voltage range
Power interruption time
Maximum inrush current
Power consumption
Isolation between DC power supply and internal logic between DC power supply and protective earth ground (PE)
(1) Controller + 7 TM3 expansion modules
Value
24 Vdc
19.2...28.8 Vdc
10 ms at 24 Vdc
50 A
32.6 W, max. 40.4 W (1)
Not isolated
500 Vac
Power Interruption
The duration of power interruptions where the M251 Logic Controller is able to continue normal operation varies depending upon the load to the power supply of the controller, but a minimum of 10 ms is maintained as specified by IEC standards.
When planning the management of the power supplied to the controller, you must consider the power interruption duration due to the fast cycle time of the controller.
There could potentially be many scans of the logic and consequential updates to the I/O image table during the power interruption, while there is no external power supplied to the inputs, the outputs or both depending on the power system architecture and power interruption circumstances.
WARNING
UNINTENDED EQUIPMENT OPERATION
• Individually monitor each source of power used in the controller system including input power supplies, output power supplies and the power supply to the controller to allow appropriate system shutdown during power system interruptions.
• The inputs monitoring each of the power supply sources must be unfiltered inputs.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
DC Power Supply Wiring Diagram
This figure shows the power supply terminal block removal procedure:
52 EIO0000003101.03
The following figure shows the wiring of the DC power supply:
* Type T fuse
For more information, refer to the 5.08 pitch
Rules for Removable Screw Terminal block, page 50
.
Grounding the M251 System
Overview
To help minimize the effects of electromagnetic interference, cables carrying fieldbus communication signals must be shielded.
WARNING
UNINTENDED EQUIPMENT OPERATION
• Use shielded cables for communication signals.
• Ground cable shields for communication signals at a single point 1 .
• Always comply with local wiring requirements regarding grounding of cable shields.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
1 Multipoint grounding is permissible if connections are made to an equipotential ground plane dimensioned to help avoid cable shield damage in the event of power system short-circuit currents.
The use of shielded cables requires compliance with the following wiring rules:
• For protective ground connections (PE), metal conduit or ducting can be used for part of the shielding length, provided there is no break in the continuity of the ground connections. For functional ground (FE), the shielding is intended to attenuate electromagnetic interference and the shielding must be continuous for the length of the cable. If the purpose is both functional and protective, as is often the case for communication cables, the cable must have continuous shielding.
• Wherever possible, keep cables carrying one type of signal separate from the cables carrying other types of signals or power.
Protective Ground (PE) on the Backplane
The protective ground (PE) should be connected to the conductive backplane by a heavy-duty wire, usually a braided copper cable with the maximum allowable cable section.
Shielded Cables Connections
Cables carrying fieldbus communication signals must be shielded. The shielding must be securely connected to ground. The fieldbus communication cable shields
EIO0000003101.03
53
must be connected to the protective ground (PE) with a connecting clamp secured to the conductive backplane of your installation.
The shielding of the Modbus cable must be connected to the protective ground
(PE).
DANGER
HAZARD OF ELECTRIC SHOCK
• The grounding terminal connection (PE) must be used to provide a protective ground at all times.
• Make sure that an appropriate, braided ground cable is attached to the PE/
PG ground terminal before connecting or disconnecting the network cable to the equipment.
Failure to follow these instructions will result in death or serious injury.
WARNING
ACCIDENTAL DISCONNECTION FROM PROTECTIVE GROUND (PE)
• Do not use the TM2XMTGB Grounding Plate to provide a protective ground
(PE).
• Use the TM2XMTGB Grounding Plate only to provide a functional ground
(FE).
Failure to follow these instructions can result in death, serious injury, or equipment damage.
54 EIO0000003101.03
Modicon M251 Logic Controller
What’s in This Part
EIO0000003101.03
55
TM251MESC
What’s in This Chapter
Overview
This chapter describes the TM251MESC logic controller.
TM251MESC Presentation
Description
This figure shows the different components of the TM251MESC logic controller:
6
7
4
5
8
2
3
N°
1
9
10
11
12
13
14
15
56
Description
Dual port Ethernet switch
CANopen port
Serial line port / Type RJ45 (RS-232 or RS-485)
Run/Stop switch
Status LEDs
TM4 bus connector
TM3/TM2 bus connector
SD card slot
Refer to
TM4 Expansion Modules, page 29
TM3 Expansion Modules, page 21
USB mini-B programming port / For terminal connection to a programming
PC (EcoStruxure Machine Expert)
Surface mounting lugs
Clip-on lock for 35 mm (1.38 in.) top hat section rail (DIN-rail)
24 Vdc power supply
Protective cover (SD card slot and USB mini-B programming port)
Locking hook (Hook not included)
Battery holder
USB Mini-B Programming Port , page 68
–
DC Power supply Characteristics and Wiring, page 50
–
–
Real Time Clock (RTC), page 32
EIO0000003101.03
Status LEDs
This figure shows the status LEDs:
I/O
SD
BAT
ETH
Label
PWR
RUN
ERR
SL
TM4
Function Type Color
Power Green
Machine status Green
Internal Error
I/O error
Red
Red
The following table describes the system status LEDs:
Green
Status
On
Off
On
Flashing
1 flash
Off
On
Fast flashing
Slow flashing
On
On
Description
Indicates that power is applied.
Indicates that power is removed.
Indicates that the controller is running a valid application.
Indicates that the controller has a valid application that is stopped.
Indicates that the controller has paused at BREAKPOINT.
Indicates that the controller is not programmed
Indicates that an operating system error has been detected
Indicates that the controller has detected an internal error
Indicates either that a minor error has been detected if RUN is ON or that no application has been detected
Indicates device errors on the serial line, SD card, TM4 bus, TM3 bus,
Ethernet port(s) or CANopen port.
Indicates that the SD card is being accessed SD card access
Battery Red
Ethernet port status
Serial line
Error on TM4 bus
Green
Green
Red
On
Flashing
On
3 flashes
4 flashes
5 flashes
6 flashes
Flashing
Off
On
Off
Indicates that the battery needs to be replaced.
Indicates that the battery charge is low.
Indicates that the ethernet port is connected and the IP address is defined.
Indicates that the ethernet port is not connected.
Indicates that the IP address is already in used.
Indicates that the module is waiting for BOOTP or DHCP sequence.
Indicates that the configured IP address is not valid.
Indicates the
status of serial line, page 71
Indicates no serial communication
Indicates that an error has been detected on the TM4 bus
Indicates that no error has been detected on the TM4 bus
EIO0000003101.03
57
Label
CAN-R
CAN-E
Function Type Color
CANopen running status
Green
CANopen error Red
Status
On
Off
Flashing
1 flash per second
On
Off
Flashing
1 flash per second
2 flashes per second
Description
Indicates that the CANopen bus is operational.
Indicates that the CANopen master is configured.
Indicates that the CANopen bus is being initialized.
Indicates that the CANopen bus is stopped.
Indicates that the CANopen bus is stopped (BUS OFF).
Indicates no CANopen detected error.
Indicates that the CANopen bus is not valid.
Indicates that the controller has detected that the maximum number of error frames has been reached or exceeded.
Indicates that the controller has detected either a Node Guarding or a
Heartbeat event.
NOTE: All the LEDs flash when the logic controller is being identified. For more details, refer to the EcoStruxure Machine Expert Programming Guide.
Dimensions
This figures shows the external dimensions of the logic controller:
58 EIO0000003101.03
TM251MESE
What’s in This Chapter
Overview
This chapter describes the TM251MESE logic controller.
TM251MESE Presentation
Description
This figure shows the different components of the TM251MESE logic controller:
10
11
12
13
14
15
4
5
2
3
N°
1
8
9
6
7
Description
Dual port Ethernet switch
Ethernet port 2
Serial line port / Type RJ45 (RS-232 or RS-485)
Run/Stop switch
Status LEDs
TM4 bus connector
TM3/TM2 bus connector
SD card slot
TM4 Expansion Modules, page 29
TM3 Expansion Modules, page 21
USB mini-B programming port / For terminal connection to a programming
PC (EcoStruxure Machine Expert)
USB Mini-B Programming Port , page 68
Surface mounting lugs
Clip-on lock for 35 mm (1.38 in.) top hat section rail (DIN-rail)
–
24 Vdc power supply
Refer to
Protective cover (SD card slot and USB mini-B programming port)
Locking hook (Hook not included)
Battery holder
DC Power supply Characteristics and Wiring, page 50
–
–
Real Time Clock (RTC), page 32
EIO0000003101.03
59
Status LEDs
This figure shows the status LEDs:
Label
PWR
RUN
ERR
I/O
SD
BAT
ETH.1
ETH.2
SL
TM4
Function Type Color
Power Green
Machine status Green
Internal Error
I/O error
Red
Red
The following table describes the system status LEDs:
Green
Status
On
Off
On
Flashing
1 flash
Off
On
Fast flashing
Slow flashing
On
On
Description
Indicates that power is applied.
Indicates that power is removed.
Indicates that the controller is running a valid application.
Indicates that the controller has a valid application that is stopped.
Indicates that the controller has paused at BREAKPOINT.
Indicates that the controller is not programmed
Indicates that an operating system error has been detected
Indicates that the controller has detected an internal error
Indicates either that a minor error has been detected if RUN is ON or that no application has been detected
Indicates device errors on the serial line, SD card, TM4 bus, TM3 bus,
Ethernet port(s) or CANopen port.
Indicates that the SD card is being accessed SD card access
Battery Red
Ethernet port status
Serial line
Error on TM4 bus
Green
Green
Red
On
Flashing
On
3 flashes
4 flashes
5 flashes
6 flashes
Flashing
Off
On
Off
Indicates that the battery needs to be replaced.
Indicates that the battery charge is low.
Indicates that the Ethernet port is connected and the IP address is defined.
Indicates that the Ethernet port is not connected.
Indicates that the IP address is already in use.
Indicates that the module is waiting for BOOTP or DHCP sequence.
Indicates that the configured IP address is not valid.
Indicates the
status of serial line, page 71
Indicates no serial communication
Indicates that an error has been detected on the TM4 bus
Indicates that no error has been detected on the TM4 bus
NOTE: All the LEDs flash when the logic controller is being identified. For more details, refer to the EcoStruxure Machine Expert Programming Guide.
60 EIO0000003101.03
Dimensions
This figure shows the external dimensions of the logic controller:
EIO0000003101.03
61
Modicon M251 Logic Controller Communication
What’s in This Part
Connecting the M251 Logic Controller to a PC..................................................72
62 EIO0000003101.03
Integrated Communication Ports
Integrated Communication Ports
What’s in This Chapter
TM251MESE Specific Considerations.............................................................67
CANopen Port
CANopen Capabilities
The Modicon M251 Logic Controller CANopen master has the following features:
Feature
Maximum number of slaves on the bus
Maximum length of CANopen fieldbus cables
Maximum number of PDOs managed by the master
Description
63 CANopen slave devices
According to the CAN specification (see
Transmission Speed and Cable Length, page
).
252 TPDOs + 252 RPDOs
For each additional CANopen slave:
• the application size increases by an average of 10 kbytes, which conceivably could result in exceeding memory limits.
• the configuration initialization time at the startup increases, which conceivably could result in watchdog timeout.
Although EcoStruxure Machine Expert does not restrict you from doing so, do not exceed more than 63 CANopen slave modules (and/or 252 TPDOs and 252
RPDOs) in order to have a sufficient performance tolerance and avoid any performance degradation.
WARNING
UNINTENDED EQUIPMENT OPERATION
Do not connect more than 63 CANopen slave devices to the controller to avoid system overload watchdog condition.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTICE
DEGRADATION OF PERFORMANCE
Do not exceed more than 252 TPDOs and 252 RPDOs for the Modicon M251
Logic Controller.
Failure to follow these instructions can result in equipment damage.
J1939 Capabilities
The Modicon M251 Logic Controller J1939 master has the following features:
EIO0000003101.03
63
Integrated Communication Ports
Feature
Maximum number of ECUs (slaves) on the bus
Maximum length of J1939 fieldbus cables
Maximum number of PGNs managed by the master
Description
Limited only by the address range of 0...253 for
Electronic Control Units (ECUs).
According to the CAN specification (see
Speed and Cable Length, page 65
). For J1939, the
CAN bus must be configured to run at 250 Kbps.
Given implicitly by the maximum number of input bits (%
I) and output bits (%Q) available on the Modicon M251
Logic Controller: 4096 input bits and 4096 output bits.
This results in a maximum of 512 single-packet PGNs
(most PGNs are single-packet, containing 8 bytes of data).
For each additional ECU with approximately 10 configured (single frame)
Parameter Group Numbers (PGNs):
• the application size increases by an average of 15 Kbytes. This figure includes the memory consumed by implicitly-generated variables for configured Suspected Parameter Numbers (SPNs). This application size increase could result in exceeding memory limits.
• the number of input bits (%I) used on the logic controller increases in proportion to the number and size of PGNs configured as "TX Signals" in a non-local ECU or "RX Signals" in a local ECU.
• the number of output bits (%Q) used on the logic controller increases in proportion to the number and size of PGNs configured as "TX Signals" in a local ECU.
NOTE: Thoroughly test your application regarding the number of configured
J1939 ECUs connected to the controller, and the number of PGNs configured on each ECU, to avoid a system overload watchdog condition or performance degradation.
For more information, refer to J1939 Interface Configuration (see Modicon M251
Logic Controller, Programming Guide).
CAN Wiring Diagram
The CAN plug is a male sub-D9 terminal block:
64
8
9
6
7
Pin
1
2
3
4
5
* To be connected externally to the protective earth
Signal
–
CAN_L
CAN_GND
–
(CAN_SHLD)
GND
CAN_H
–
(CAN_V+)
Description
Reserved
CAN_L bus line
CAN ground
Reserved
Optional CAN shield
Ground
CAN_H bus line
Reserved
Optional CAN external positive supply
EIO0000003101.03
Integrated Communication Ports
WARNING
UNINTENDED EQUIPMENT OPERATION
Do not connect wires to unused terminals and/or terminals indicated as “No
Connection (N.C.)”.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Transmission Speed and Cable Length
Transmission speed is limited by the bus length and the type of cable used.
The following table describes the relationship between the maximum transmission speed and the bus length (on a single CAN segment without a repeater):
Maximum transmission baud rate
1000 Kbps
800 Kbps
500 Kbps
250 Kbps
125 Kbps
50 Kbps
20 Kbps
Bus length
20 m (65 ft)
40 m (131 ft)
100 m (328 ft)
250 m (820 ft)
500 m (1,640 ft)
1000 m (3280 ft)
2500 m (16,400 ft)
NOTE: The CAN cable must be shielded.
Ethernet Port
Overview
The M251 Logic Controller is equipped with Ethernet communications ports:
Reference
TM251MESC
TM251MESE
Number of Ports
2 (one dual Ethernet port switch)
2 (one dual Ethernet port switch)
1
Port Name
Ethernet
Ethernet 1
Ethernet 2
Characteristics
This table describes the different Ethernet characteristics:
Characteristic
Function
Connector type
Auto negotiation
Description
Modbus TCP/IP, Machine Expert protocol, EtherNet I/P
RJ45 from 10 M half duplex to 100 M full duplex
EIO0000003101.03
65
Integrated Communication Ports
Characteristic
Cable type
Automatic cross-over detection
Description
Shielded
Yes
Pin Assignment
This figure shows the RJ45 Ethernet connector pin assignment:
Status LED
This table describes the RJ45 Ethernet connector pins:
Pin N°
6
7
4
5
8
1
2
3
Signal
TD+
TD-
RD+
-
-
RD-
-
-
NOTE: The controller supports the MDI/MDIX auto-crossover cable function. It is not necessary to use special Ethernet crossover cables to connect devices directly to this port (connections without an Ethernet hub or switch).
NOTE: Ethernet cable disconnection is detected every second. In case of disconnection of a short duration (< 1 second), the network status may not indicate the disconnection.
This figure shows RJ45 connectors status LED:
66
This table describes the Ethernet status LEDs:
EIO0000003101.03
Integrated Communication Ports
Label Description
1 Ethernet link
2 Ethernet activity
LED
Color
Green/Yellow
Green
Status
Off
Solid yellow
Solid green
Off
On
Description
No link
Link at 10 Mbit/s
Activity at 100 Mbit/s
No activity
Transmitting or receiving data
TM251MESE Specific Considerations
Ethernet Ports
The TM251MESE has two different Ethernet networks. Each has its own unique
IP and MAC addresses.
The two Ethernet networks are called Ethernet 1 and Ethernet 2:
• Ethernet 1 is made of two switched Ethernet ports dedicated to communication between machines or with the control network.
• Ethernet 2 is made of one Ethernet port dedicated to the device network and supporting industrial Ethernet connections.
Industrial Ethernet Architecture
This figure presents a typical industrial Ethernet architecture:
EIO0000003101.03
2
3
4
5
A
B
1
Control network
Device network
Logic controller (see EcoStruxure Machine Expert Industrial Ethernet,
User Guide)
Daisy-chained slaves
Ethernet switch
I/O island (Modbus TCP)
Vision sensor (EtherNet/IP)
67
6
2, 4, and 5
Integrated Communication Ports
PC and HMI (TCP/UDP)
Industrial Ethernet slave devices (EtherNet/IP / Modbus TCP)
Industrial Ethernet Connections with Modbus TCP IOScanner
Architecture
For example, you can:
• Connect your PC to Ethernet 1.
• Use a Modbus TCP IOScanner or EtherNet/IP Scanner with the Ethernet 2.
This figure is an example of an industrial Ethernet architecture with the
TM251MESE.
USB Mini-B Programming Port
Overview
The USB Mini-B Port is the programming port you can use to connect a PC with a
USB host port using EcoStruxure Machine Expert software. Using a typical USB cable, this connection is suitable for quick updates of the program or short duration connections to perform maintenance and inspect data values. It is not suitable for long-term connections such as commissioning or monitoring without the use of specially adapted cables to help minimize electromagnetic interference.
68 EIO0000003101.03
Integrated Communication Ports
WARNING
UNINTENDED EQUIPMENT OPERATION OR INOPERABLE EQUIPMENT
• You must use a shielded USB cable such as a BMX XCAUSBH0•• secured to the functional ground (FE) of the system for any long-term connection.
• Do not connect more than one controller or bus coupler at a time using USB connections.
• Do not use the USB port(s), if so equipped, unless the location is known to be non-hazardous.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Characteristics
This table describes the characteristics of the USB Mini-B programming port:
Parameter
Function
Connector type
Isolation
Cable type
USB Programming Port
Compatible with USB 2.0
Mini-B
None
Shielded
Serial Line
Overview
The serial line:
• Can be used to communicate with devices supporting the Modbus protocol as either master or slave, ASCII protocol (printer, modem...) and Machine Expert
Protocol (HMI,...).
• provides a 5 Vdc power distribution.
EIO0000003101.03
69
Integrated Communication Ports
Characteristics
Characteristic
Function
Connector type
Isolation
Maximum baud rate
Cable Type
Maximum length (between the controller and an isolated junction box)
Polarization
5 Vdc power supply for RS485
Description
RS485 or RS232 software configured
RJ45
Non-isolated
1200 up to 115 200 bps
Shielded
15 m (49 ft) for RS485
3 m (9.84 ft) for RS232
Software configuration is used to connect when the node is configured as a master.
560 Ω resistors are optional.
Yes
NOTE: Some devices provide voltage on RS485 serial connections. Do not connect these voltage lines to your controller as they may damage the controller serial port electronics and render the serial port inoperable.
NOTICE
INOPERABLE EQUIPMENT
Use only the VW3A8306R•• serial cable to connect RS485 devices to your controller.
Failure to follow these instructions can result in equipment damage.
Pin Assignment
The following figure shows the pins of the RJ45 connector:
70
This table describes the pin assignment of the RJ45 connector:
6
7
8
2
3
4
5
Pin
1
RS232
RxD
TxD
N.C.
N.C.
N.C.
N.C.
N.C. *
Common
RS485
N.C.
N.C.
N.C.
D1
D0
N.C.
5 Vdc
Common
*: 5 Vdc delivered by the controller, do not connect.
N.C.: No connection
RxD: Received data
EIO0000003101.03
Integrated Communication Ports
TxD: Transmitted data
WARNING
UNINTENDED EQUIPMENT OPERATION
Do not connect wires to unused terminals and/or terminals indicated as “No
Connection (N.C.)”.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Status LED
This table describes the serial line status LED:
Label Description
SL Serial line
LED
Color
Green
Status
Flashing
Off
Description
Indicates the activity of the serial line.
Indicates no serial communication.
EIO0000003101.03
71
Connecting the M251 Logic Controller to a PC
Connecting the M251 Logic Controller to a PC
What’s in This Chapter
Connecting the Controller to a PC
Overview
To transfer, run, and monitor the applications, connect the controller to a computer, that has EcoStruxure Machine Expert installed, using either a USB cable or an Ethernet connection (for those references that support an Ethernet port).
NOTICE
INOPERABLE EQUIPMENT
Always connect the communication cable to the PC before connecting it to the controller.
Failure to follow these instructions can result in equipment damage.
USB Powered Download
In order to execute limited operations, the M251 Logic Controller has the capability to be powered through the USB Mini-B port. A diode mechanism avoids having the logic controller both powered by USB and by the normal power supply, or to supply voltage on the USB port.
When powered only by USB, the logic controller executes the firmware and the boot project (if any) and the I/O board is not powered during boot (same duration as a normal boot). USB powered download initializes the internal flash memory with some firmware or some application and parameters when the controller is powered by USB. The preferred tool to connect to the controller is the Controller
Assistant . Refer to the EcoStruxure Machine Expert Controller Assistant User
Guide .
The controller packaging allows easy access to USB Mini-B port with minimum opening of the packaging. You can connect the controller to the PC with a USB cable. Long cables are not suitable for the USB powered download.
WARNING
INSUFFICENT POWER FOR USB DOWNLOAD
Do not use a USB cable longer than 3m (9.8 ft) for USB powered download.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: It is not intended that you use the USB Powered Download on an installed controller. Depending on the number of I/O expansion modules in the physical configuration of the installed controller, there may be insufficient power from your PC USB port to accomplish the download.
72 EIO0000003101.03
Connecting the M251 Logic Controller to a PC
USB Mini-B Port Connection
Cable Reference
BMXXCAUSBH018:
TCSXCNAMUM3P:
Details
Grounded and shielded, this USB cable is suitable for long duration connections.
This USB cable is suitable for short duration connections such as quick updates or retrieving data values.
NOTE: You can only connect 1 controller or any other device associated with
EcoStruxure Machine Expert and its component to the PC at any one time.
The USB Mini-B Port is the programming port you can use to connect a PC with a
USB host port using EcoStruxure Machine Expert software. Using a typical USB cable, this connection is suitable for quick updates of the program or short duration connections to perform maintenance and inspect data values. It is not suitable for long-term connections such as commissioning or monitoring without the use of specially adapted cables to help minimize electromagnetic interference.
WARNING
UNINTENDED EQUIPMENT OPERATION OR INOPERABLE EQUIPMENT
• You must use a shielded USB cable such as a BMX XCAUSBH0•• secured to the functional ground (FE) of the system for any long-term connection.
• Do not connect more than one controller or bus coupler at a time using USB connections.
• Do not use the USB port(s), if so equipped, unless the location is known to be non-hazardous.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
The communication cable should be connected to the PC first to minimize the possibility of electrostatic discharge affecting the controller.
2
3
4
To connect the USB cable to your controller, follow the steps below:
Step
1
Action
1a If making a long-term connection using the cable BMXXCAUSBH018, or other cable with a ground shield connection, be sure to securely connect the shield connector to the functional ground (FE) or protective ground (PE) of your system before connecting the cable to your controller and your PC.
1b If making a short-term connection using the cable TCSXCNAMUM3P or other nongrounded USB cable, proceed to step 2.
Connect your USB cable to the computer.
Open the protective cover for the USB mini-B slot on the controller.
Connect the mini-B connector of your USB cable to the controller.
Ethernet Port Connection
You can also connect the controller to a PC using an Ethernet cable.
EIO0000003101.03
73
Connecting the M251 Logic Controller to a PC
To connect the controller to the PC, do the following:
Step
1
2
Action
Connect the Ethernet cable to the PC.
Connect the Ethernet cable to any of the Ethernet ports on the controller.
74 EIO0000003101.03
Glossary
A
application:
A program including configuration data, symbols, and documentation.
ASCII:
( American standard code for Information Interchange ) A protocol for representing alphanumeric characters (letters, numbers, certain graphics, and control characters).
B
bps:
( bit per second ) A definition of transmission rate, also given in conjunction with multiplicator kilo (kbps) and mega (mbps).
C
CANopen:
An open industry-standard communication protocol and device profile specification (EN 50325-4).
CFC:
( continuous function chart ) A graphical programming language (an extension of the IEC 61131-3 standard) based on the function block diagram language that works like a flowchart. However, no networks are used and free positioning of graphic elements is possible, which allows feedback loops. For each block, the inputs are on the left and the outputs on the right. You can link the block outputs to the inputs of other blocks to create complex expressions.
configuration:
The arrangement and interconnection of hardware components within a system and the hardware and software parameters that determine the operating characteristics of the system.
continuous function chart language:
A graphical programming language (an extension of the IEC61131-3 standard) based on the function block diagram language that works like a flowchart.
However, no networks are used and free positioning of graphic elements is possible, which allows feedback loops. For each block, the inputs are on the left and the outputs on the right. You can link the block outputs to inputs of other blocks to create complex expressions.
controller:
Automates industrial processes (also known as programmable logic controller or programmable controller).
D
DIN:
( Deutsches Institut für Normung ) A German institution that sets engineering and dimensional standards.
EIO0000003101.03
75
76
E
EIA rack:
( electronic industries alliance rack ) A standardized (EIA 310-D, IEC 60297, and
DIN 41494 SC48D) system for mounting various electronic modules in a stack or rack that is 19 inches (482.6 mm) wide.
EN:
EN identifies one of many European standards maintained by CEN ( European
Committee for Standardization ), CENELEC ( European Committee for
Electrotechnical Standardization ), or ETSI ( European Telecommunications
Standards Institute ).
F
FBD:
( function block diagram ) One of 5 languages for logic or control supported by the standard IEC 61131-3 for control systems. Function block diagram is a graphically oriented programming language. It works with a list of networks, where each network contains a graphical structure of boxes and connection lines, which represents either a logical or arithmetic expression, the call of a function block, a jump, or a return instruction.
FE:
(functional Earth ) A common grounding connection to enhance or otherwise allow normal operation of electrically sensitive equipment (also referred to as functional ground in North America).
In contrast to a protective Earth (protective ground), a functional earth connection serves a purpose other than shock protection, and may normally carry current.
Examples of devices that use functional earth connections include surge suppressors and electromagnetic interference filters, certain antennas, and measurement instruments.
H
HE10:
Rectangular connector for electrical signals with frequencies below 3 MHz, complying with IEC 60807-2.
I
I/O:
( input/output )
IEC 61131-3:
Part 3 of a 3-part IEC standard for industrial automation equipment. IEC 61131-3 is concerned with controller programming languages and defines 2 graphical and
2 textual programming language standards. The graphical programming languages are ladder diagram and function block diagram. The textual programming languages include structured text and instruction list.
IEC:
( international electrotechnical commission ) A non-profit and non-governmental international standards organization that prepares and publishes international standards for electrical, electronic, and related technologies.
IL:
( instruction list ) A program written in the language that is composed of a series of text-based instructions executed sequentially by the controller. Each instruction includes a line number, an instruction code, and an operand (refer to IEC 61131-
3).
EIO0000003101.03
EIO0000003101.03
instruction list language:
A program written in the instruction list language that is composed of a series of text-based instructions executed sequentially by the controller. Each instruction includes a line number, an instruction code, and an operand (see IEC 61131-3).
IP 20:
( ingress protection ) The protection classification according to IEC 60529 offered by an enclosure, shown by the letter IP and 2 digits. The first digit indicates 2 factors: helping protect persons and for equipment. The second digit indicates helping protect against water. IP 20 devices help protect against electric contact of objects larger than 12.5 mm, but not against water.
L
ladder diagram language:
A graphical representation of the instructions of a controller program with symbols for contacts, coils, and blocks in a series of rungs executed sequentially by a controller (see IEC 61131-3).
LD:
( ladder diagram ) A graphical representation of the instructions of a controller program with symbols for contacts, coils, and blocks in a series of rungs executed sequentially by a controller (refer to IEC 61131-3).
M
master/slave:
The single direction of control in a network that implements the master/slave mode.
Modbus:
The protocol that allows communications between many devices connected to the same network.
N
NEMA:
( national electrical manufacturers association ) The standard for the performance of various classes of electrical enclosures. The NEMA standards cover corrosion resistance, ability to help protect from rain, submersion, and so on. For IEC member countries, the IEC 60529 standard classifies the ingress protection rating for enclosures.
P
PDO:
( process data object ) An unconfirmed broadcast message or sent from a producer device to a consumer device in a CAN-based network. The transmit
PDO from the producer device has a specific identifier that corresponds to the receive PDO of the consumer devices.
PE:
( Protective Earth ) A common grounding connection to help avoid the hazard of electric shock by keeping any exposed conductive surface of a device at earth potential. To avoid possible voltage drop, no current is allowed to flow in this conductor (also referred to as protective ground in North America or as an equipment grounding conductor in the US national electrical code).
77
78 program:
The component of an application that consists of compiled source code capable of being installed in the memory of a logic controller.
R
RJ45:
A standard type of 8-pin connector for network cables defined for Ethernet.
RPDO:
( receive process data object ) An unconfirmed broadcast message or sent from a producer device to a consumer device in a CAN-based network. The transmit
PDO from the producer device has a specific identifier that corresponds to the receive PDO of the consumer devices.
RS-485:
A standard type of serial communication bus, based on 2 wires (also known as
EIA RS-485).
RxD:
The line that receives data from one source to another.
S
SFC:
( sequential function chart ) A language that is composed of steps with associated actions, transitions with associated logic condition, and directed links between steps and transitions. (The SFC standard is defined in IEC 848. It is IEC 61131-3 compliant.)
ST:
( structured text ) A language that includes complex statements and nested instructions (such as iteration loops, conditional executions, or functions). ST is compliant with IEC 61131-3.
T
terminal block:
( terminal block ) The component that mounts in an electronic module and provides electrical connections between the controller and the field devices.
TPDO:
( transmit process data object ) An unconfirmed broadcast message or sent from a producer device to a consumer device in a CAN-based network. The transmit
PDO from the producer device has a specific identifier that corresponds to the receive PDO of the consumer devices.
TxD:
The line that sends data from one source to another.
EIO0000003101.03
Index
L
logic/motion controller installation ...........................40
A
accessories ..........................................................31
B
bus coupler
specifications.....................................................28
M
M251
TM251MESC.....................................................56
TM251MESE .....................................................59
mounting positions ................................................42
C
CANopen communication ......................................63
certifications and standards....................................40
communication
CANopen ..........................................................63
Communication Ports ............................................63
Ethernet Port .....................................................65
Serial Line 1 ......................................................69
USB Programming Port ......................................68
connections
to CANopen slaves ............................................63
to J1939 ECUs ..................................................63
P
PGNs, max. number of J1939 ................................63
Power Supply........................................................50
presentation
TM251MESC.....................................................56
TM251MESE .....................................................59
programming languages
IL, LD, grafcet ....................................................14
Q
qualification of personnel .........................................5
D
digital I/O modules
specifications............................................... 18–19
Digital I/O modules
Specifications ....................................................19
R
real time clock .......................................................32
Run/Stop ..............................................................34
E
ECUs, max. number of J1939.................................63
Electrical Requirements
Installation.........................................................48
Electromagnetic Susceptibility ................................39
Environmental Characteristics ................................38
S
SD Card ...............................................................35
Serial Line 1
Communication Ports .........................................69
specifications
digital I/O modules .............................................18
Specifications
Digital I/O modules.............................................19
F
features
key features.......................................................14
fieldbus interface
specifications.....................................................29
U
USB Programming Port
Communication Ports .........................................68
W
wiring ...................................................................48
G
Grounding ............................................................53
I
installation
logic/motion controller installation........................40
Installation ............................................................38
Electrical Requirements......................................48
intended use ...........................................................6
J
J1939
capabilities ........................................................63
EIO0000003101.03
79
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00 www.se.com
As standards, specifications, and design change from time to time, please ask for confirmation of the information given in this publication.
© 2022 Schneider Electric . All rights reserved.