Schneider Electric TSXNanoPLC User Guide
Reklama
Reklama
General safety advice for users
____________________________________________________________________________
1 General
This manual is intended for personnel technically qualified to install, operate and maintain the products which are described herein. It contains all the necessary information for correct use of the products. However, for advanced use of our products please contact your nearest sales office for additional information.
The contents of this manual are not contractual and cannot under any circumstance extend or restrict contract warranty clauses.
2 Qualification of personnel
Only qualified personnel are authorized to install, operate or maintain the products. Any work performed by a unqualified person or non-observance of the safety instructions in this document or attached to the equipment may risk the safety of personnel and/or cause irreparable damage to equipment. The following personnel may be regarded as being "Qualified" :
• those involved with application design. Design office personnel familiar with control system safety concepts (for example, design engineers, etc),
• those involved with equipment installation. Individuals who are familiar with the installation, connection and startup of control system equipment (for example installers or wiring technicians working during the installation phase, technicians setting up the equipment, etc),
• those involved with operation. Personnel trained to operate and manage control system equipment (for example, operators, etc),
• those performing preventive or corrective maintenance. Personnel who are trained and experienced in the adjustment and repair of control system equipment (for example, installation engineers, after sales service engineers, etc).
3 Warnings
Warnings serve to prevent specific risks encountered by personnel and/or equipment. They are indicated in the documentation and on the products by different warning symbols, according to the severity of the risk :
Danger or Caution or Attention
Indicates that not following instructions or ignoring the warning may cause serious personal injury, death and/or serious damage to equipment.
Warning or Important or !
Indicates that not following a specific instruction may lead to minor injury and/or damage to equipment.
Note or Comment
Highlights important information relating to the product, its operation or its accompanying documentation.
___________________________________________________________________________
1
General safety advice for users
___________________________________________________________________________
4 Conformity of use
The products described in this manual conform to the European Directives (*) to which they are subject (CE marking). However, they can only be used correctly in the context of the applications for which they are intended (described in the various documents) and when connected to approved third party products.
As a general rule, if all handling, transport and storage specifications are observed, and all instructions for installation, operation and maintenance are followed, the products will be used correctly, with no danger to personnel or equipment.
(*) DEMC and DLV Directives, concerning Electromagnetic Compatibility and Low Voltage.
5 Installing and setting up equipment
It is important to observe the following rules when installing and starting up equipment. In addition, if the installation includes digital links, it is essential to follow the basic wiring rules given in the user's guide, reference TSX DG GND, and manual TSX DR NET, part C.
• safety instructions must be followed meticulously. These instructions are in the documentation or on the equipment being installed and set up.
• the type of equipment defines the way in which it should be installed :
- a flush-mountable device (for example, a process control terminal or a cell controller) must be flush-mounted,
- a device which is to be built in (for example, PLC) must be placed in a cabinet or enclosure,
- the casing of a laptop or portable device (for example, a programming terminal or a notebook) must remain closed,
• if the device is permanently connected, its electrical installation must include a device to isolate it from the power supply and a circuit-breaker to protect it against overcurrents and isolation faults. If this is not the case, the power socket must be grounded and be easily accessed. In all cases, the device must be connected to the protective mechanical ground PG using
green/yellow wires (NFC 15 100).
• low voltage circuits (even though they are low voltage) must be connected to the protective ground so that dangerous voltages can be detected.
• before a device is powered up, its nominal voltage must be checked to ensure that it has been adjusted to conform with the supply voltage.
• if the device is supplied with 24 or 48 VDC, the low voltage circuits must be protected. Only use power supplies which conform to the standards currently in force.
• check that the supply voltages remain within the tolerance ranges defined in the technical characteristics of the devices.
• all measures must be taken to ensure that any power return (immediate, warm or cold) does not lead to a dangerous state which may risk personnel or the installation.
• emergency stop devices must remain effective in all the device's operating modes, even those which are abnormal (for example, when a wire becomes disconnected). Resetting these devices must not cause uncontrolled or improper restarts.
• cables which carry signals must be located where they do not cause interference with the control system functions by capacitive, inductive or electromagnetic interference.
• control system equipment and their control devices must be installed in such a way as to ensure that they are protected against unintentional operation.
• appropriate safety measures must be taken for the inputs and outputs, to prevent improper states in the control system device, if no signal is received.
___________________________________________________________________________
2
General safety advice for users
____________________________________________________________________________
6 Equipment operation
The operational safety and availability of a device is its ability to avoid the appearance of faults and to minimize their effects if they occur.
A system is said to be fail-safe if the appearance of faults never causes a dangerous situation.
A fault inside the control system is known as :
• passive, if it results in an open output circuit (no command is sent to the actuators).
• active, if it results in a closed output circuit (an command is sent to the actuators).
From the safety point of view, a given fault is dangerous or not depending on the type of command given during normal operation. A passive fault is dangerous if the normal command is the operation of an alarm. An active fault is dangerous if it maintains or activates an undesirable command.
It is important to note the basic difference between the behavior of an electromechanical relay and an electronic component (for example a transistor) :
• there is a high probability, approximately 90%, that the failure of a relay will cause an open circuit (control circuit powered off).
• there is a 50% probability that the failure of a transistor will cause either an open circuit or a closed circuit.
This is why it is important to correctly estimate the types and consequences of faults when automating a system using electronic products such as PLCs, including when relay output modules are used on PLCs.
The system designer must use devices external to the PLC to protect against active faults inside the PLC, which are not indicated and are judged to be dangerous to the application. This may require solutions from various different technologies such as mechanical, electromechanical, pneumatic or hydraulic devices (for example, directly wiring a limit switch and emergency stop switches to the coil of a movement control contactor).
To protect against dangerous faults which may occur on output circuits or preactuators, it is sometimes beneficial to resort to general principles and use the large processing capacity of
PLCs, for example by using "inputs to check the correct execution of commands requested by the program".
7 Electrical and thermal characteristics
Details of the electrical and thermal characteristics of devices are given in the associated technical documents (installation manuals, service instructions).
___________________________________________________________________________
3
General safety advice for users
___________________________________________________________________________
8 Environmental conditions
Devices, such as TSX Nano PLCs, meet "TC" treatment (1) requirements. For installations in industrial production workshops or in environments which correspond to "TH" treatment (2), these devices should be installed in enclosures with minimum IP54 protection, stipulated by standards
IEC 664 and NF C 20 040.
TSX Nano PLCs, which themselves have IP20 protection, can therefore be installed without enclosures in restricted-access locations which do not exceed pollution level 2 (control room with no machines or dust-producing activities).
(1) "TC" treatment : all climate treatment.
(2) "TH" treatment : treatment for hot and humid environments.
9 Preventive or corrective maintenance
Availability
The availability of a system is its ability, in terms of its combined reliability, maintainability and maintenance logistics, to be in a state to perform a required function, at a given moment and within a defined time period.
Availability is therefore specific to each application, since it is a combination of :
• the architecture of the automatic system,
• the reliability and maintainability : intrinsic characteristics of the equipment (PLCs, sensors, machine, etc),
• maintenance logistics : characteristic intrinsic to the user of the control system (software structure, fault indication, process, on-site replacement parts, training of personnel).
Troubleshooting procedure
• control system equipment should only be repaired by qualified personnel (after sales service engineer, or technician approved by AEG Schneider Automation). Only certified replacement parts or components should be used.
• before performing any operation on equipment (for example opening an enclosure), always cut the power supply off (disconnect the power plug or open the power isolation switch).
• before performing any "mechanical" operation on equipment on site, cut the power supply off and mechanically lock any moving parts.
• before performing an operation on the PLC, modifying a connection, etc, check in the manual whether this should be done with the power off or if it is possible while the device is powered up. Meticulously follow the instructions given in the manual.
• on positive logic outputs or negative logic inputs, take all necessary precautions to prevent a disconnected wire from coming into contact with the mechanical ground (risk of undesirable command).
___________________________________________________________________________
4
Setting up
TSX Nano PLCs
Contents
Part A
Section
The PLC in the control system structure
1.2-2 Summary of catalog references (Discrete I/O)
1.2-3 Main functions of TSX Nano PLCs
1.3-1 Normal (cyclical) operation
Additional information about the I/O
1.7-1 Programmable input filters
1.7-2 Protected transistor outputs on TSX 07 •• •• 12
Status display of the PLC and the I/O
1.11 TSX Nano PLCs with 1 integrated analog input
Page
A
___________________________________________________________________________
A/1
A
Setting up
TSX Nano PLCs
Contents
Part A
Section
1.12-2 Presentation of TSX AMN 4000/4001
1.12-3 Status display of TSXAMN 4000/4001 modules
1.12-4 Presentation of TSX AEN/ASN •••
1.12-5 Summary of catalog references
2 Dimensions/Mounting/Installation
I/O wiring rules and precautions
3.1-1 General precautions and rules
3.1-2 Special precautions for connecting discrete low noise
immunity inputs
3.3-2 Connection of 115 VAC inputs
Connection of discrete outputs 3/8
3.4-1 Connection of relay outputs
3.4-2 Connection of relay outputs on TSX 07 •1 1648 PLC
3.4-3 Connection of negative logic (sinking) transistor outputs 3/10
3.4-4 Connection of positive logic (sourcing) transistor outputs 3/12
3/2
Page
___________________________________________________________________________
A/2
Setting up
TSX Nano PLCs
Contents
Part A
Section
Page
Connection of an analog sensor (TSX 07 32/33 ••28) 3/16
Connection of analog modules (TSX AMN 4000/4001)
3.8-1 Connection of analog modules to the "base PLC" PLC
3.8-2 Connection of analog inputs
3.8-3 Connection of analog outputs
Connection of analog inputs (TSX AEN •••)
3.9-1 Connection with input 0 of the TSX Nano wired as sink
3.9-2 Connection with input 0 of the TSX Nano wired as source
3.10 Connection of analog outputs (TSX ASN •••)
3.10-1 Connection with source output 0 of the TSX Nano
3.10-2 Connection with sink output 0 of the TSX Nano
I/O associated with fast counting
4.4-2 Use as a frequency meter
4.4-3 Use as an up/down counter
___________________________________________________________________________
A/3
A
A
Setting up
TSX Nano PLCs
Contents
Part A
Section
PULSE output : generating a pulse train
PWM output : pulse width modulation
5 Characteristics/Service conditions
24VDC and 115VAC discrete input characteristics
24VDC discrete transistor output characteristics
Discrete relay output characteristics
Characteristics of analog I/O (TSX AMN 4000/4001)
5.5-1 Characteristics of analog inputs
5.5-2 Characteristics of the analog output
Characteristics of analog I/O (TSX AEN/ASN •••)
5.6-1 Characteristics common to analog inputs and outputs
5.6-2 Characteristics of analog inputs
5.6-3 Characteristics of analog outputs
Characteristics of the analog input (TSX 07 32/33 ••28)
5.8-2 Environment, normal service conditions
Page
___________________________________________________________________________
A/4
Setting up
TSX Nano PLCs
Section
Contents
Part A
A
Page
___________________________________________________________________________
A/5
A
Setting up
TSX Nano PLCs
Section
Contents
Part A
Page
___________________________________________________________________________
A/6
1
1 Introduction
1.1
The PLC in the control system structure
A PLC can be divided into four main sections :
• Inputs
• Outputs
• The memory, where the user program instructions and data are stored
• The processor, which reads the input data and controls the outputs according to the user program instructions.
The programming terminal is the tool used to :
• Create and transfer the user program to program memory
• Debug the user program and control system start-up
• Perform installation diagnostics.
A
Programming terminal limit switch proximity sensor
FTX 417/FT 2000 FTX 117
I
N
P
U
T
S
Program memory
Processor
P
U
T
S
O
U
T contactor solenoid valve indicator lamp analog actuator push button
PLC
___________________________________________________________________________
1/1
A
1.2
Discrete I/O TSX Nano PLCs
1.2-1 Presentation
Discrete I/O TSX Nano PLCs are available in four configurations depending on whether extendability is required :
• "base PLC" non-extendable PLCs (14 and 20 I/O).
• "base PLC" non-extendable PLCs with 1 integrated analog input (10, 16 and 24 I/O).
• "I/O extensions" (16 and 24 I/O).
• "base PLC or I/O extension" extendable PLCs (10, 16 and 24 I/O).
10 I/O (6 inputs + 4 outputs)
14 I/O (8 inputs + 6 outputs)
16 I/O (9 inputs + 7 outputs)
16 I/O (9 inputs + 7 outputs) PLC with 115 VAC inputs
20 I/O (12 inputs + 8 outputs)
24 I/O (14 inputs + 10 outputs)
___________________________________________________________________________
1/2
Introduction 1
A
A "base PLC" extendable PLC can be extended by an I/O extension or by an
extendable PLC configured as an I/O extension.
In addition, a maximum of three peer PLCs (extendable PLCs configured as peer PLCs) can be connected to the "base PLC" extendable PLC, communicating via exchange words.
Base PLC I/O extension Peer PLC2 Peer PLC3 Peer PLC4
0 1 5 6 7
650 feet maximum (1)
Discrete I/O TSX Nano PLCs are programmed in PL7 language (Ladder or Instruction
List languages).
These PLCs are programmed via :
• either an FTX 117 terminal (Instruction List)
• or an FTX 417 or PC compatible terminal (Ladder or Instruction List).
(1) See Part A, Section 3.5 for the type of cable to use
___________________________________________________________________________
1/3
A
Description of discrete I/O TSX Nano
1 Hinged cover for access to items 2, 3, and 4.
2 Port for connecting an ASCII or UNI-TELWAY device.
ASCII, RS485 UNI-TELWAY Master or slave protocols.
3 Selector switch for PLC function code :
0 = base PLC, 1 = I/O extension.
5 = Peer PLC no. 2, 6 = Peer PLC no. 3,
7 = Peer PLC no. 4.
4 Potentionmeter :
• 1 on PLCs with 10, 14 or 20 I/O,
• 2 on PLCs with 16 or 24 I/O,
5 Input status display (1),
6 Output status display (1),
7 PLC status display : RUN, ERR, COM, I/O,
8 Power supply connections,
9 Sensor supply on models with 100/240 VAC :
24VDC/150 mA supply.
This supply is not available on the model with 115VAC inputs.
10 Input connections.
11 Output connections.
12 Extension connector I/O Extension
Peer PLC
Modbus Slave (V3)
Analog input channel
13 Removable cover for protecting the terminals.
(1) A maximum of 16 internal bits can be displayed (%S69=1).
1/4
All PLCs
B, B/E
B/E
B, B/E
All PLCs
E, B/E
B/E
B/E see 1.11
All PLCs
Introduction 1
A
1.2-2 Summary of catalog references (Discrete I/O)
No.
PLC Power
I/O type supply isolated
110/240V 24V 24V 115V transistor 24V a relay sink source 24V a c© a æ a c© 24/240V c
B/E
• • •
B/E
6/4 B/E
B/E
B/E
B/E
8/6 B
•
•
•
•
• •
• •
•
•
•
•
Type of inputs Type of outputs
•
•
•
•
•
•
B/E
B/E
9/7 B/E
B/E
•
•
• •
•
•
•
•
•
References
TSX 07 (x)0 1028
TSX 07 (x)0 1008
TSX 07 (x)0 1002
TSX 07 (x)0 1022
TSX 07 (x)0 1012
TSX 07 32 1028
TSX 07 3L 1428
TSX 07 (x)1 1628
TSX 07 (x)1 1648
TSX 07 (x)1 1608
TSX 07 (x)1 1602
B/E
B/E
E
E
B/E
12/8 B
B/E
B/E
B/E
14/10 B/E
B/E
E
E
B/E
•
•
•
•
•
•
•
• •
• •
• •
•
•
• •
•
•
• •
•
• •
• •
• •
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
TSX 07 (x)1 1622
TSX 07 (x)1 1612
TSX 07 EX 1628
TSX 07 EX 1612
TSX 07 33 1628
TSX 07 3L 2028
TSX 07 (x)1 2428
TSX 07 (x)1 2408
TSX 07 (x)1 2402
TSX 07 (x)1 2422
TSX 07 (x)1 2412
TSX 07 EX 2428
TSX 07 EX 2412
TSX 07 33 2428
B : Non-extendable PLC, E : I/O extension, B/E : Extendable PLC.
(x) 2 : V2 models; 3 : V3 models
Note :
TSX 07 33• •••• models have additional software functions to those offered by the TSX 23• •••• models, such as Uni-Telway Master/Slave on the terminal port, Modbus slave PLC on the extension port, connection of analog I/O modules, etc.
___________________________________________________________________________
1/5
`
A
1.2-3 Main functions of TSX Nano PLCs
By default, all I/O are configured as discrete I/O. However, certain I/O can be assigned to specific tasks during configuration (RUN/STOP input, latching inputs, 10 kHz fast counting I/O or 1kHz up/down counting, PLC status (SECURITY) output, pulse train output, pulse width modulation output).
TSX Nano PLCs are programmed in reversible PL7 language (Instruction List or
Ladder) which enables the following functions to be used : schedule blocks (RTC), timers, up/down counters, LIFO/FIFO registers, shift registers, drum controllers, step counters.
Scanning
Scan time
Normal (cyclical) or periodic (2 to 150 ms)
Less than 1 ms for 1000 elementary instructions (3)
Less than 0.6 ms for 100 elementary instructions
`
Execution time 0.2 µs to 2 µs for a single Boolean elementary instruction
Memory capacity Data 256 internal words, 64 constant words, 128 internal bits (64 of these retentive)
Backup
Language
Terminal port
Program - 1000 instructions (battery-backed RAM and EEPROM)
PLC RAM : by battery. Backup duration : 30 days
Reversible PL7 : Instruction List or Ladder
I/O extension
Peer PLCs
Modbus link
Function blocks
RS 485 link, UNI-TE protocol, 9600 bits/s / 19200 bits/s.
Max. distance : FTX 117 : 10 m; UNI-TE : 50 m
1 per PLC.
Max. distance between base PLC and extension : 200 meters
(650 feet) (1)
3, connected to the "base PLC" extendable PLC, and communicating via exchange words. Maximum distance between base
PLC and last peer PLC : 200 meters (650 feet) (1)
Non-isolated RS485 type, length limited to 200 m. ASCII or RTU mode
Schedule blocks (RTC)
Timers
16 (2)
32 time base : 1ms (for the first two), 10ms, 100ms, 1s, 1min with a preset range from 0 to
9999
Up/down counters
LIFO/FIFO registers
16 preset range from 0 to 9999
4 16-word blocks
Shift registers 8 16 bits
(1) See Part A, Section 3.5 for the type of cable to use
(2) Available on all "base PLC" PLCs with 16 and 24 I/O : TSX 07 •• 16/24
To improve performance, it is advisable to deconfigure the unused extensions (see Section A-
1/6
Introduction 1
A
Function blocks
(continued)
Drum controllers
Step counters
4
4
8 steps, 16 control bits
256 steps
Potentiometers 1 (on TSX Nano, 10/14/20 I/O),
2 (on TSX Nano 16/24 I/O)
Analog channel Function specific to certain modules, see Section 1.11
Displaying internal bits
(Memory
Display)
On a "base PLC" PLC or a peer PLC (extendable PLC configured as a peer PLC), it is possible to display the status of 8 internal bits
(TSX Nano with 10 and 16 I/O) or 16 internal bits (TSX Nano with
24 I/O) on the front panel, see Section 1.9.
Programmable On a base PLC or a peer PLC, it is possible to change the input filter input filter time during configuration :
No filtering or filtering at 3 ms or 12 ms (see Section A-1.7).
I/O points are configured in groups.
Special I/O It is possible to assign specific functions to certain I/O during configuration.
Inputs RUN/STOP : 1 of the first 6 inputs of the base or the peer
PLC (%I0.0 to %I0.5).
Latching : the first 6 inputs of the base or the peer PLC
(%I0.0 to %I0.5).
Analog input module connected on %10.0 according to frequency meter
Fast counter : 10 kHz
Frequency meter : 10 kHz
Fast up/down counter : 1 kHz
Outputs PLC status (SECURITY) : 1 of the first 4 outputs of the base or the peer PLC (%Q0.0 to %Q0.3)
PULSE : pulse train (4.9 kHz maximum)
PWM : pulse width modulation (4.9 kHz maximum)
Analog input module connected on %Q0.0 according to
PWM (pulse width modulation)
Threshold outputs : 2 (%Q0.1 and %Q0.2), associated with fast counting, are updated without waiting for an endof-scan update
,
Note :
PULSE and PWM outputs can be used on PLCs with relay outputs as long as the on-off period is greater than the relay's closing response time (approximately 50 Hz). If they are used, the maximum number of permitted operations is likely to be reached very quickly.
We therefore recommend using these outputs mainly on PLCs with transistor outputs.
___________________________________________________________________________
1/7
A
Summary of the main functions according to PLC type
Functions 10/14/16 I/O PLC
(x)0 10 ••
(x)1 16 ••
3L 1428 3(x) ••28
16 I/O PLC 20/24 I/O PLC I/O extension
(x)1 1648 3L 2028 16/24 E/S
(x)1 24 ••
33 2428
EX •• ••
Inputs RUN/STOP
Latching
Counting 10 kHz
•
•
•
Analog/
Frequency meter
Up/down
• counting 1kHz
Outputs PLC status
PULSE
Analog/
•
•
•
PWM
Threshold (fast counters)
Programmable
•
(x)1 16 •• input filters 3L 1428
•
•
•
•
•
•
•
•
•
•
•
•
•
Schedule block (RTC)
Potentiometers
Display of internal bits on I/O indicator lamps
Communication prog.
UNI-TELWAY port ASCII extension I/O Ext. or Peer PLC port Modbus slave
Function Timers
blocks Up/down counters
LIFO/FIFO register blocks
Shift registers
Drum controllers
Step counters
Instruc-Grafcet
tions (1)Master relay
VariaBit strings
bles (1) Word table
Indexing
(x)1 16 ••
(x)0 10 ••
(x)1 16 ••
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
(x)1 24 ••
•
•
•
•
•
(x)1 24 ••
•
(x)1 24 ••
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
1/8
Introduction 1
A
1.3
Program execution
1.3-1 Normal (cyclical) operation
By default, the PLC scan executes cyclically, as follows :
Internal processing :
The system :
• Monitors the PLC :
- checks the execution capability of the program memory
- manages the time ; updates the current schedule block (RTC)
- updates the LEDs : RUN, I/O, ERR,
COM
- detects the RUN/STOP changeover
- monitors other system parameters
• Processes requests from the programming port and the extension port.
Internal processing
Read inputs
(%I)
Read inputs :
• Input memory is updated with the status of the physical inputs (%I).
Execute program :
• The program written by the user is then executed.
Update outputs :
• The states of the physical outputs (%Q) are updated from the output memory.
Program execution
Update outputs
(%O)
The operating cycle
• PLC running
The processor manages the system, reads the inputs, executes the program and updates the outputs.
• PLC stopped
In this case, the processor only manages the system, reads the inputs and updates the output image table.
Warning
Watchdog timer
The scan time of the user program is monitored by the PLC watchdog timer and must not exceed 150 ms. Otherwise a fault appears causing the PLC to stop immediately
(the RUN and ERR LEDs flash).
___________________________________________________________________________
1/9
A
The possibilities :
1 Scan time - watchdog time (150 ms)
Normal operation, the next scan is started
2 Scan time > watchdog time
The PLC stops, the RUN and ERR LEDs flash and system bit %S11=1.
Diagram of cyclical scan time
Program execution
Program execution
Time
I.P.
Scan n time
Key :
I.P.= internal processing
I.P.
Scan n+1 time
%I = read inputs %Q = update outputs
1.3-2 Periodic operation
In this case, reading of inputs, program processing and output updating is executed periodically according to the time defined by the user at configuration (2 to
150 ms).
At the start of the PLC scan, a software timer is set to the value defined during configuration. The PLC scan must finish before the time elapses. The next scan is started when the timer finishes.
When the scan time exceeds the preset time limit, system bit %S19 is set to 1. This bit can be tested and reset by the user or by the user program.
Start
of period
Read inputs
(%I)
Program execution
Update outputs
(%Q)
Internal processing
End of period
___________________________________________________________________________
1/10
Introduction 1
A
Warning
Watchdog timer
The scan time of the user program is monitored by the PLC watchdog timer and must not exceed 150 ms. Otherwise a fault appears causing the PLC to stop immediately
(the RUN and ERR LEDs flash).
The possibilities :
1 Scan time - preset time limit
Normal operation, the next scan is launched as soon as the programmed period has elapsed.
2 Preset time limit < scan time - watchdog time
The system bit %S19 is set to 1 by the system and the program user is responsible for resetting it to 0. The PLC remains in RUN.
3 Scan time > watchdog time
The PLC stops, the RUN and ERR LEDs flash and system bit %S11=1.
Diagram of periodic execution time
Program execution
Program execution
I.P.
I.P.
Period
Key :
I.P.= internal processing %I = read inputs
Period
I.P.
%Q = update outputs
___________________________________________________________________________
1/11
A
1.4
The I/O extension
"Base PLC" extendable PLCs can be extended using an I/O extension. This extension is created using a "base PLC" extendable PLC (10, 16 or 24 I/O) configured as an I/O extension (10 or 24 I/O).
Base PLC I/O extension
Extension link
The configuration of a "base PLC" extendable PLC is defined by the position of the selector switch, as shown in the diagram above :
• Selector switch at position 0 = base PLC.
• Selector switch at position 1 = I/O extension.
An I/O extension module does not require any particular configuration since it is dedicated for this use only.
The extension link between the base PLC and the I/O extension should be a shielded twisted pair cable.
The maximum distance between the base PLC and the I/O extension is 200 meters
(650 feet).
Cable product reference : TSX CA0 003 (length 30 cm - 12 inches).
For distances greater than this, the user should use a cable whose characteristics are defined in Part A, Section 3.5.
Recommended input and output distribution between the base PLC and the I/O extension :
To accommodate any slight variation in update times, critical I/O points should be assigned to the base PLC. This will ensure optimum operation of the control system.
___________________________________________________________________________
1/12
1.5
I/O addressing
An I/O address is defined by the following characters :
% I or Q 0 or 1 symbol I = input
Q = output
0 = base PLC or peer PLC
1 = I/O extension point
•
Introduction 1
A i
i= I/O point number
(see table below)
Base PLC I/O extension
Examples
%I0.3
: Input, I/O point n°3 on the base PLC
%Q1.6 : Output, I/O point n°6 on PLC used as I/O extension
Numbers of I/O points for the various PLC types
PLC model Number of I/O Inputs
TSX 07 •• 10 ••
TSX 07 3L 1428
TSX 07•• 16••
TSX 07 3L 2028
TSX 07•• 24••
10 (6I + 4O)
14 (8I + 6O)
16 (9I + 7O)
20 (12I + 8O)
24 (14I + 10O) i = 0 to 5 i = 0 to 7 i = 0 to 8 i = 0 to 11 i = 0 to 13 i = 0 to 3 i = 0 to 5 i = 0 to 6 i = 0 to 7 i = 0 to 9
Outputs
___________________________________________________________________________
1/13
A
1.6
Special I/O
Introduction
By default, all I/O are configured as discrete I/O. However, certain I/O of a "base PLC"
PLC or an extendable PLC configured as a peer PLC can be assigned to specific functions during configuration. An I/O point already used for one function cannot be used for another.
Special inputs
Input functions
Base PLC or Peer PLC inputs
%I0.0
%I0.1
%I0.2
%I0.3
%I0.4 %I0.5 %I0.6 to %I0.13
RUN/STOP
Latching
Inputs linked with fast up/ down counting
Upcounting
Counter set
• • • • • •
_
• • • • • •
_
•
_ _ _ _ _ _
_
•
_ _ _ _ _
Fast counter
(FC) enable
_ _
•
_ _ _ _
Analog input
Downcounting _
FC read _
_
_
_
_
•
_ _ _
_
•
_ _
•
_ _ _ _ _ _
Special outputs
Output functions (1)
PLC status (SECURITY)
PULSE : pulse train
PWM : pulse width modulation
Analog output
Outputs linked with fast up/ down counting
FC OUT 0
FC OUT 1
•
Base PLC or Peer PLC outputs
•
•
•
%Q0.0
%Q0.1 %Q0.2 %Q0.3
• • •
_
_
_
_
_
_
_
_
_ _ _
•
_ _
_
•
_
%Q0.4 % to %Q0.10
_
_
_
_
_
_
(1) Outputs %Q0.0, %Q0.1, %Q0.2 and %Q0.3, when configured as special outputs, must not be used as outputs in the application program (for example, with Boolean instructions (ST, STN,
S, R) with the command bits for drum controller blocks %DRi) or as outputs assigned to the
Schedule blocks RTC.
___________________________________________________________________________
1/14
Introduction 1
Definition
Use of these I/O is defined in detail in Part A, Section 4. The description below simply defines each I/O function.
• RUN/STOP input (see Section 4.1)
Via an external switch, this input :
- starts program execution (RUN),
- stops program execution (STOP).
• Latching input (see Section 4.3)
This input is used to store a pulse which lasts for less than a scan, so that it is taken into account in the following scan.
• Inputs linked with fast counting (see Section 4.4)
Upcounting input
This input enables the counting of pulses to be taken into account, at a maximum frequency of :
- 5 or 10 kHz if configured as a fast counter or frequency meter
- 1 kHz if configured as a fast up/down counter.
One of the applications is the management of an analog input module (see Section 1.11)
Set counting input
This input is used :
- either to reset the counter to 0 when using it as a fast counter.
- or to preset it to a value defined at configuration when using it as an up/down counter.
Fast counter enable input
This input ensures that signals received at the up/down counting inputs are taken into account.
Downcounting input
This input enables downcounting pulses to be taken into account at a maximum frequency of 1kHz.
Fast counter value read input
This input enables the current value to be read during the scan, rather than when the scan is completed.
• PLC status (SECURITY) output (see Section 4.2)
Normally set at 1, it changes to 0 on a PLC fault and can therefore be used in external safety circuits.
• PULSE output (see Section 4.5)
Used to generate a signal lasting for a variable period but with a constant duty cycle, or on to off ratio, equal to 50% of the period.
• PWM output (see Section 4.6)
Used to generate a signal lasting for a constant period with the option of varying the duty cycle, or on to off ratio.
One of the applications is the management of an analog input module (see Section 1.11)
• Fast Counter threshold outputs (see Section 4.4)
Linked to fast counting, these outputs enable data to be read during the scan, without waiting for an update at the end of the scan.
___________________________________________________________________________
1/15
A
A
1.7
Additional information about the I/O
1.7-1 Programmable input filters
Input filtering on a "base PLC" PLC or an extendable PLC configured as a peer PLC may be configured from the terminal by altering the filter time. The values which can be configured are as follows :
• 12 ms : filter contact bounce and electrical noise
• 3 ms : filter contact bounce and electrical noise
• No filtering : reading short signals for fast applications but with increased sensitivity to filter contact bounce or electrical noise. In this case the use of volt-free contacts is not advised.
Important
Each type of configurable filter value can be considered as three zones separated by 2 values : the immunity value and the recognition value. Any signal with a duration less than or equal to the immunity value will be rejected. Any signal with a duration greater than or equal to the recognition value will be accepted. Any signal with a duration between these 2 values may accepted or rejected. If no filtering has been configured on an input, the immunity and recognition values are set for inputs %I0.8 to %I0.13 but for inputs %I0.0 to %I0.7 they will depend on whether or not the counting function or the frequency meter function has been configured on input %I0.0.
Filter configured
12 ms
3 ms
No filtering and %FC not configured
No filtering and %FC configured as
5 khz counter or
5 khz frequency meter
No filtering and %FC configure as
10 khz counter or
10 khz frequency meter
Immunity
10 ms
Recognition
13 ms
2 ms 4 ms
0.125 ms for %I0.8 to %I0.13
0.375 ms for %I0.8 to %I0.13
0.025 ms for %I0.0 to %I0.7
0.100 ms for %I0.0 to %I0.7
0.125 ms for %I0.8 to %I0.13
0.375 ms for %I0.8 to %I0.13
0.025 ms for %I0.0 to %I0.7
0.100 ms for %I0.0 to %I0.7
0.125 ms for %I0.8 to %I0.13
0.375 ms for %I0.8 to %I0.1.
0.007 ms for %I0.0 to %I0.7
0.037 ms for %I0.0 to %I0.7
Important
Where no filtering has been configured, and the recognition values are less than the PLC scan time (and thus the scan time of the inputs), to ensure that a signal with a duration greater than the recognition time is processed, use the input which handles this signal to capture the pulses.
___________________________________________________________________________
1/16
Introduction 1
A
• Discrete inputs
By default, all inputs on a "base PLC" PLC or an extendable PLC configured as an I/O extension or peer PLC are configured with a filter time of 12 ms. This time can be modified for each I/O point group on a base or peer PLC.
• Latching inputs
Each of the first 6 inputs (%I 0.0 to %I 0.5) on a "base PLC" PLC or an extendable PLC configured as a peer PLC can be configured individually as latching inputs. This type of operation is used to memorize any pulse with a duration less than the PLC scan time.
In this case, the immunity and recognition values also depend on the configuration of the fast counting function %FC.
Inputs %I0.0 to %I0.5 in read mode Immunity Recognition
%FC not configured
%FC configured as 5 khz counter or 5 khz frequency meter
%FC configured as 10 khz counter or 10 khz frequency meter
0.025 ms
0.025 ms
0.007 ms
0.100 ms
0.100 ms
0.037 ms
• Fast counting inputs
If a fast counter, a frequency meter or an up/down counter is declared at the time of configuration, the following inputs are automatically assigned to the counting pulse input.
- %I0.0 for fast counting and frequency meter,
- %I0.0 and %I0.3 for up/down counting.
Used for fast counting or as frequency meter :
Two operating modes can be configured : a 10 khz mode and a 5 khz mode. Input %I0.0
then counts the pulses, which must respect the characteristics of the minimum duration and the minimum separation between pulses to be taken into account.
Mode Immunity Min. pulse duration Min. sep. between pulses
5 Khz
10 Khz
0.025 ms
0.004 ms
0.100 ms
0.045 ms
0.100 ms
0.045 ms
___________________________________________________________________________
1/17
A
Used for up/down counting :
Inputs %I0.0 and %I0.3 upcount and downcount the pulses, which must respect the characteristics of the minimum duration and the minimum separation between pulses to be taken into account. The maximum frequency is 1 khz.
%I0.0 and %I0.3
Immunity Min. duration of pulse Min. sep. between pulses
0.025 ms 0.100 ms 0.100 ms
Important
• While counter input %I0.0 is at state 1, no downcounting action will be processed on input %I0.3.
• While counter input %I0.3 is at state 1, no upcounting action will be processed on input %I0.0.
1.7-2 Protected transistor outputs on TSX 07 •• •• 12
Protection against overloads and short-circuits
TSX 07 •• •• 12 PLCs have 4, 7 or 10 transistor outputs which are protected against overloads of up to 1A and short-circuits.
0.5A transistor outputs have an electronic device which enables an overload or a shortcircuit to be detected on any active output. The appearance of this type of fault causes :
• current limitation (typically 1A) of the affected output,
• tripping of all the outputs in the block (base PLC or I/O extension)
• activation with a steady light of the I/O LED on the base PLC (if base PLC outputs tripped) or LEDs on the base PLC and I/O extension (if I/O extension outputs tripped)
• setting the I/O fault system bit %S10 to 0, and system bits %S118, %S119, %SW118:X0 and %SW119:X0 to change state (see sections B 5.1, B 5.2 and B 6.2).
Reactivating transistor outputs
When a fault has caused tripping of the PLC outputs, they need to be reset. Since tripping of outputs results in downgraded operation of the process being controlled by the PLC, it is advisable to make resetting transistor outputs conditional upon manual intervention. The operator can then, before performing the reset, take any necessary precautions with regard to the control system and personnel, (for example, request changeover to manual mode). The recommended programming is described in section
B 6.2.
Note :
If the process being controlled by the PLC is the responsibility of the user, it is possible to program an automatic reset (see section B 6.2).
Important
Cold restart of the PLC (set %S0) removes the tripping fault and attempts system reactivation.
___________________________________________________________________________
1/18
Introduction 1
A
1.8
Potentiometers
Principle
An analog/digital converter translates the voltage at the terminals of a potentiometer into a digital value (0 to 255) which is then stored in a word. This value can then, for example, be used as the preset value for a timer that the user can manually adjust without the need for a programming terminal. An example of software start-up is described in Part B, Section 3.2.
Adjustment potentiometer
Analog
Digital
Analog/digital converter value 0 to 255
Storage in a system word %SW
Potentiometers can only be used on "base PLC" PLCs and extendable PLCs configured as peer PLCs.
The number of potentiometers varies depending on the type of PLC :
• 1 on PLCs with 10, 14 and 20 I/O, labelled 0
• 2 on PLCs with 16 and 24 I/O, labelled 0 and 1.
Storage word depending on the potentiometers
Potentiometer 0 Storage word Potentiometer 1 Storage word
Position of the potentiometers
PLC with 10, 14 and 20 PLC with 16 or 24 I/O
___________________________________________________________________________
1/19
A
1.9
Status display of the PLC and the I/O
• Displaying the status of the PLC
The results of the self-tests performed continually by TSX Nano modules are displayed on the front panel via 4 LEDs :
RUN, ERR, I/O and COM.
LED LED status
Base PLC or peer PLC
RUN on
(green) flashing
ERR
(red) off on flashing off
PLC in RUN
PLC in STOP or execution fault
Application not executable
OK
I/O extension
Same as base PLC
Same as base PLC
Not powered or application not executable Incorrectly or not connected
Internal faults (watchdog, etc) Same as base PLC
- - - - - - - - - - -
OK
COM on
(yellow) flashing off
I/O
(red) on flashing
Exchanges present on extension link (1) Same as base PLC
Exchanges present on Modbus slave (1)
No exchanges on extension link or Modbus
- - - - - - - - - - -
I/O fault (outputs tripped, sensor supply) Same as base PLC
_ OK off OK
(1) Operation of the I/O or Modbus is exclusive
_
• Displaying the I/O
The status of each I/O point is displayed on the front panel of the PLC via a red LED for
PLCs version V3.0 or earlier, and a green LED for PLCs version V3.0 or later.
PLC with 10 I/O PLC with 14/16 I/O
LED on : I/O on
LED off : I/O off
PLC with 20/24 I/O
When switched on, all LEDs are lit for approximately 1s.
___________________________________________________________________________
1/20
Introduction 1
A
• Displaying internal bits
When system bit %S69 is set to 1, TSX Nano PLCs can display the status of 8 or 16 internal bits, rather than displaying the I/O status. The numbering of memory bits is fixed from 112-127.
The corresponding display on the front panel is shown below :
10 I/O PLC
Flashing (1)
14/16 I/O PLC
Flashing (1)
20/24 I/O PLC
Flashing (1)
(1) series of 5 short flashes, once every second
___________________________________________________________________________
1/21
A
1.10
Peer PLCs
A maximum of three extendable PLCs configured as peer PLCs which communicate via exchange words (%IW and %QW) can be connected to the "base PLC" extendable
PLC. In this case, only the base PLC can have an I/O extension.
Base PLC Peer PLC2 Peer PLC3 Peer PLC4
I/O extension extension link
Note :
The order in which they are cabled does not affect operation.
The function of each PLC is defined by the position of the selector switch, as shown in the diagram above :
PLC function
Selector position
Link address
Base I/O TSX Micro extension Peer Peer Peer
PLC Ext.
(module TSX STZ10) PLC2 PLC3 PLC4
0
0
1
1
2
2
3
3
4
4
5
2
6
3
7
4
I/O addressing for peer PLCs 2, 3, and 4 is identical to that for the base PLC (%I0.i and
%Q0.i)
The extension link between the base PLC and the extensions (I/O and/or PLCs) should be a shielded twisted pair cable (see Part A, Section 3.5 for the type of cable to use).
The maximum distance between the PLC base and the last peer PLC is 200 meters
(650 feet).
Important :
The position of the selector switch is only taken into account when the PLC is powered up.
___________________________________________________________________________
1/22
Introduction 1
A
In order to optimize the communication exchange between the base PLC and the peer
PLCs or I/O extension, the number of devices to be scanned and the baud rate on the link must be defined. See Part C, Section 3.2 for information on baud rate configuration.
Overall duration of exchange scan (complete scan)
3
4
1
2
Number of extensions scanned
Transmission speed
9600 bits/s (1)
17 to 19 ms
34 to 35 ms
53 to 55 ms
72 to 74 ms
19200 bits/s
6 to 8 ms
16 to 18 ms
26 to 28 ms
35 to 36 ms
Note :
System bit %S72 can be used to prevent any scanning of peer PLCs. It takes priority over selections made during configuration.
Important
Bits X1, X2, X3 and X4 of system word %SW71 enable the status of communication with each peer PLC to be tested on the extension link (at state 1, communication is OK). Using PL7-07 data animation at 19200 bit/s may lead to reduced performance.
The same speed must be configured for all PLCs in the same Nanet network.
___________________________________________________________________________
1/23
A
1.11
TSX Nano PLCs with 1 integrated analog input
1.11-1 Presentation
TSX 07 32/33 •• •• PLCs include a non-isolated 0/10V analog input channel. They have the same characteristics and functions as TSX07 30/31 •• •• (see Section 1.2-3). In particular, they allow use of an external analog input or output channel.
The analog input channel replaces the extension port function in TSX 07 30/31•• ••. TSX
07 32/33 PLCs cannot therefore be connected to other PLCs or to a Modbus slave type link.
The analog input channel is managed via system word %SW112 in the application. A potentiometer P0 is used to correct any errors caused by the analog measurement circuit in some applications.
Potentiometer P0
Sensor
For details on managing the analog input channel of TSX 07 32/33 •• see Part B Section
3.3.
___________________________________________________________________________
1/24
Introduction 1
A
1.12 Analog modules
1.12-1 Presentation
TSX 07 30/31 •• •• "base PLC" PLCs with discrete I/O (starting from version V3) are able to manage analog I/O modules.
There are three types of analog module in the TSX Nano offer :
• TSX AMN 4000/4001 analog I/O modules managed via the I/O extension link.
• TSX AEN••• modules with one analog input using input %I0.0 of the "base PLC" PLC in frequency meter mode.
• TSX ASN••• modules with one analog output managed via the PWM output (base
PLCs must be fitted with transistor outputs).
1.12-2 Presentation of TSX AMN 4000/4001
TSX AMN 4000/4001 analog modules are available in two configurations depending on the power supply required. Each module includes 3 input channels and one output channel.
These modules are managed by the "base PLC" PLC as peer PLCs (maximum of 3).
Analog modules and peer PLCs can be mixed on the same link.
Base PLC
I/O extension
Analog module 1
Analog module 2
Analog module 3
200 meters maximum
Addressing I/O in TSX AMN 400• analog modules is defined by setting the selector switch as shown in the table below.
PLC function / analog module
Selector switch position 0
Link address 0
Base I/O TSX Micro Extension Analog Analog Analog
PLC Ext. (TSX STZ10 module) mod. 1 mod. 2 mod. 3
1
1
2
2
3
3
4
4
5
2
6
3
7
4
Important
The position of the selector switch is only taken into account when the PLC is powered up.
___________________________________________________________________________
1/25
A
Analog modules are configured in the PL7-07 configuration menu.
Exchanges between the "base PLC" PLC and analog modules are managed via exchange words %IW and %QW.
For details on managing the analog I/O modules of TSX 07 AMN 4000/4001 see Part
B Section 4.2.
1.12-3 Status display of TSXAMN 4000/4001 modules
• Display of the PLC status
The results of the self-tests performed continually by analog modules are displayed on the front panel via 4 LEDs :
RUN, ERR, COM and I/O.
LED
RUN
LED status on
(green) off
ERR
(red) on
Meaning
Application in RUN
Not powered or application not executable
Internal faults (autocalibration fault or self-tests not OK) flashing Incorrect module addressing
COM off on
(yellow) off
I/O
(red) on off
Functioning OK
Communication present
No exchanges present
High and low stops on analog inputs exceeded
Functioning OK
___________________________________________________________________________
1/26
Introduction 1
A
1.12-4 Presentation of TSX AEN/ASN •••
Each "base PLC" PLC can support a maximum of one input module and one output module.
The analog input module is managed via the fast counting input on the PLC.
The analog output module is managed via the PWM output on the PLC (base PLCs must be fitted with transistor outputs).
Fast input counter
TSX Nano
1 ANA input module
1 ANA output module
Pulse output (PWM)
The fast counting input and the PWM output are configured in the PL7-07 configuration menu.
Management of the control of input functions, the value of the analog input read, the control of output functions and the analog output value to be generated are determined by reading and writing system words %SW100 to %SW103 in the application.
For details on managing the analog I/O modules see Part B Section 4.3 and 4.4.
___________________________________________________________________________
1/27
A
1.12-5 Summary of catalog references
Supply voltage
100/240 V 24 V c© a
•
1I
•
1I
I/O Range Resolution module 0-10V 4-20mA +/-10V 8 8/12 10/12 bits bits bits
•
• •
•
References
TSX AEN 101
TSX AEN 102
•
TSX AEN 105
•
•
1I
•
1O
•
•
1O
•
1O
3I/1O
• •
•
3I/1O
• •
•
•
•
•
• •
•
•
•
•
TSX ASN 101
TSX ASN 102
TSX ASN 105
TSX AMN 4000
TSXAMN 4001
___________________________________________________________________________
1/28
Section 2
2
2 Dimensions/Mounting/Installation
2.1
Dimensions
• TSX 07 •• 10 ••, TSX 07 32 1028 , TSX AMN4000/4001
A
• TSX 07 •• 16 •• except TSX 07 • 1 1648, TSX 07 3L 1428
• TSX 07 •• 24 •• with 16 I/O : TSX 07 • 1 1648, TSX 07 2028
• TSX AEN 10 • and TSX ASN 10 •
___________________________________________________________________________
2/1
A
2.2
Mounting
TSX Nano PLCs and analog modules can be mounted on :
• a mounting plate or panel using 2 Ø M3 screws (not supplied)
• a 35 mm DIN mounting rail.
• Mounting on a mounting plate or panel using screws
PLCs /
Analog modules
X
TSX 07 •• 10 •• TSX 07 •• 16 •• TSX 07 • 1 1648 TSX 07 •• 24 ••
TSX 07 32 1028 TSX 07 3L 1428
TSX AMN 400 •
TSX 07 2028
86 mm
3.38 inches
116 mm
4.56 inches
146 mm
5.74 inches
146 mm
5.74 inches
• Mounting on a 35 mm DIN rail
Mounting Removal
Position the PLC and clip it on to the DIN rail as shown in the above diagram.
1 With a screwdriver, release the latch at the back which locks the PLC onto the DIN rail.
2 Keeping the latch open, pivot the PLC as shown in the above diagram.
Warning
When mounting PLCs and analog modules on a DIN rail, use 2 end stops, type
AB1-AB8P35 or equivalent.
___________________________________________________________________________
2/2
Dimensions/Mounting/Installation 2
A
2.3
Installation rules
TSX Nano PLCs and analog modules should be mounted on a vertical plane and at the minimum distances shown on the figure below, in order to maintain a natural circulation of air.
• Mounting positions
- Vertical plane
1 End stops AB1-AB8P35
2 Cover
- Horizontal plane : Do not mount on a horizontal plane.
• Minimum clearances to be observed
1 Switchgear, enclosure or machine frame.
2 Cable ducting or clips.
a > 20 mm
b > 40 mm
Avoid mounting heat generating devices (transformers, power supplies, contactors, etc) beneath the PLCs.
___________________________________________________________________________
2/3
A
___________________________________________________________________________
2/4
3
3 Connections
3.1
I/O wiring rules and precautions
3.1-1 General precautions and rules
The connection terminals on TSX Nano PLCs are protected by a removable cover which protects users when the PLC is powered up. Each terminal can take up to two
1 mm 2 (16 AWG) wires fitted with open or closed cable ends. Coupling torque of terminal screws : max. 0.5 Nm.
Dimensions :
1 5.5 mm
2 3.2 mm
3 5 mm
When using closed cable ends, it is necessary to remove the cover in order to take out the screw needed for fixing the cable ends.
Removing the cover
A
TSX Nano PLCs have integral protective devices on the I/O, which give them a good resistance to industrial environments. However, certain rules must be observed so as to maintain this immunity.
• Discrete inputs
All multi-core cables carrying sensor data must include the sensor common.
• Discrete outputs
Relay outputs : the following must be connected in parallel with the terminals of the output :
- An RC or MOV (ZNO) protection circuit for AC.
- A freewheel diode for DC.
• Cable routing
- External to the device
All I/O wiring must be routed in cable ducting which is separate from those carrying high voltage cables, and at least 100 mm (4 inches) from parallel power cables.
- Inside the device
Power cables (power supply, contactors, etc) must be kept separate from input
(sensors) and output wiring.
If possible, I/O wiring should be routed in separate cable ducting.
____________________________________________________________________
3/1
A
3.1-2 Special precautions for connecting discrete low noise immunity inputs
Some inputs can be configured as :
• Fast counters or frequency meter inputs, with a frequency of 5 or 10 kHz (input %I0.0).
• Up/down counter inputs, 1 kHz (inputs : upcounter %I0.0, downcounter %I0.3).
• Latching inputs (inputs %I0.0 to %I0.5).
• Discrete inputs without filter (%I0.0 to %I0.3 and %I0.4 to %I0.7).
The noise immunity of the inputs which have been configured in this way is reduced, and certain connection precautions must be taken.
• Input %I0.0 used as a fast counter or frequency meter input (5 or 10 kHz), 1 kHz counter input, latching input or discrete input without filter :
A shielded cable must be used with :
- the cable shield connected to terminal C (COM), the input common (to the power supply - with positive logic (sinking) inputs or to the power supply + with negative logic (sourcing) inputs),
- terminal C (COM) connected to the machine protected ground.
Example : Wiring diagram for connecting input %I0.0 to a 3-wire sensor wired for positive logic
Sensor supply
3-wire sensor shielded cable
PLC supply shield connection < 20 cm protected machine ground
Note :
When using the 1 kHz up/down counting function, input %I0.3, which is used as the downcounting input, will be connected following the same principle as for input %I0.0
___________________________________________________________________________
3/2
Connections 3
A
• Other inputs used as latching inputs (%I0.1 to %I0.5) or discrete inputs without filter (%I0.1 to I0.7) :
The general principle is to group together on the same cable all the wires relating to the sensor which is controlling the input. Thus one cable is used per I/O point.
Example : Wiring diagram with inputs wired for positive logic (sinking)
3-wire sensor
Sensor supply
3-wire sensor
PLC supply cable cable
____________________________________________________________________
3/3
A
3.2
Connection of power supply
• 24 VDC power supply to DC power input terminals to a output power supply
TSX 07 •• ••• 2
Q Master switch
KM Line contactor or circuit breaker (not essential on small installations)
TSX AMN 4001
Q Master switch
KM Line contactor or circuit breaker (not essential on small installations)
Key : c AC, a DC
___________________________________________________________________________
3/4
Connections 3
A
• 100 to 240 VAC power supply
Note :
The 24VDC power input is not available on the TSX 07
21 1648 115 VAC input model.
to DC power input terminals to c output power supply
TSX 07 •• ••• 8
Q Master switch
KM Line contactor or circuit breaker (not essential on small installations)
TSX AMN 4000
Q Master switch
KM Line contactor or circuit breaker (not essential on small installations)
Key : c
AC, a
DC
____________________________________________________________________
3/5
A
3.3
Discrete input connection
3.3-1 24V input connections
• Connection of the positive logic (sinking) inputs
On PLCs with AC supply :
- 10 I/O : TSX 07 • 0 1008, TSX 07 •• 1028
- 14 I/O : TSX 07 3L 1428
- 16 I/O : TSX 07 • 1 1608, TSX 07 •• 1628
- 20 I/O : TSX 07 3L 2028
- 24 I/O : TSX 07 • 1 2408, TSX 07 •• 2428
3-wire prox. sens.
2-wire prox. sens.
Inputs
TSX 07 •• •• 08/28
On PLCs with DC supply :
- 10 I/O : TSX 07 • 0 1002, TSX 07 • 0 1012, TSX 07 • 0 1022
- 16 I/O : TSX 07 • 1 1602, TSX 07 07 •• 1612, TSX 07 • 1 1622
- 24 I/O : TSX 07 • 1 2402, TSX 07 07 •• 2412, TSX 07 • 1 2422
3-wire prox. sens.
2-wire prox. sens.
Inputs
TSX 07 •• •• 02/12/22
___________________________________________________________________________
3/6
Connections 3
A
• Connection of the negative logic (sourcing) inputs
On PLCs with AC supply :
- 10 I/O : TSX 07 • 0 1008, TSX 07 •• 1028
- 14 I/O : TSX 07 3L 1428
- 16 I/O : TSX 07 • 1 1608, TSX 07 •• 1628
- 20 I/O : TSX 07 3L 2028
- 24 I/O : TSX 07 • 1 2408, TSX 07 •• 2428
3-wire prox. sens.
2-wire prox. sens.
Inputs
TSX 07 •• •• 08/28
On PLCs with DC supply :
- 10 I/O : TSX 07 • 0 1002, TSX 07 • 0 1012, TSX 07 • 0 1022
- 16 I/O : TSX 07 • 1 1602, TSX 07 •• 1612, TSX 07 • 1 1622
- 24 I/O : TSX 07 • 1 2402, TSX 07 •• 2412, TSX 07 • 1 2422
3-wire prox. sens.
2-wire prox. sens.
Inputs
TSX 07 •• •• 02/12/22
____________________________________________________________________
3/7
A
3.3-2 Connection of 115 VAC inputs
• PLC : TSX 07 • 1 1648
Inputs
3.4
Connection of discrete outputs
3.4-1 Connection of relay outputs
(except TSX 07 • 1 1648)
• PLCs with 10 I/O : TSX 07 • 0 1022, TSX 07 •• 1028
TSX 07 •• 1022/1028
Outputs
TSX 07 •1 1648
* : fuse rated for load
___________________________________________________________________________
3/8
Connections 3
A
Connection of relay outputs (continued)
• PLCs with 14 I/O : TSX 07 3L 1428
16 I/O : TSX 07 •1 1622, TSX 07 •• 1628
TSX 07 •• 1428/1622/1628
Outputs
Does not exist on
TSX07 3L 1428
* : fuse rated for load
• PLCs with 20 I/O : TSX 07 3L 2028
24 I/O : TSX 07 •1 2422, TSX 07 •• 2428
Outputs
TSX 07 •• 2028/2422/2428
Does not exist on
TSX07 3L 2028
* : fuse rated for load
Essential protection for each output terminal
• An RC circuit or MOV (ZNO) suppressor circuit for AC
• A freewheel diode for DC
(AC) (DC)
____________________________________________________________________
3/9
A
3.4-2 Connection of relay outputs on TSX 07 •1 1648 PLC
TSX 07 • 1648
Outputs
* : fuse rated for load
Essential protection for each output terminal
• An RC circuit or MOV (ZNO) suppressor for AC
• A freewheel diode for DC
(AC)
3.4-3 Connection of negative logic (sinking) transistor outputs
• PLCs with 10 I/O : TSX 07 • 0 1002 and TSX 07 •0 1008
TSX 07•0 1002/1008
Outputs
(DC)
* : fuse rated for load
___________________________________________________________________________
3/10
Connections 3
A
Connection of negative logic (sinking) transistor outputs (continued)
• PLCs with 16 I/O : TSX 07 •1 1602 and TSX 07 •1 1608
TSX 07 •1 1602/1608
Outputs
* : fuse rated for load
• PLCs with 24 I/O : TSX 07 • 1 2402 and TSX 07 • 1 2408
TSX 07 •1 2402/2408
Outputs
* : fuse rated for load
____________________________________________________________________
3/11
A
3.4-4 Connection of positive logic (sourcing) transistor outputs
• PLC with 10 I/O : TSX 07 • 0 1012
TSX 07 •0 1012
Outputs
* : fuse rated for load
• PLC with 16 I/O : TSX 07 •• 1612
Outputs
TSX 07 •1 1612
* : fuse rated for load
___________________________________________________________________________
3/12
Connections 3
A
Connecting positive logic transistor (sourcing) outputs (continued)
• PLC with 24 I/O : TSX07 •• 2412
TSX 07•1 2412
Outputs
* : fuse rated for load
____________________________________________________________________
3/13
A
3.5
I/O extension connections
The I/O extension is connected to the "base PLC" PLC via a shielded twisted pair cable :
• Cable length 30 cm (12 inches) : reference TSX CA 0003.
• If a longer cable is required, use :
- either a UNI-TELWAY shielded twisted double pair cable :
TSX STC 50 : length 50 meters (165 feet), or TSX STC 200 : length 200 meters (650 feet)
- or a shielded twisted pair cable, the main characteristics of which are defined below :
Mechanical characteristics :
Tinned copper core, 18 to 24 gauge, tinned copper shield
Structure
Electrical characteristics :
Load resistance per unit length of one wire : - 85
Ω
/ Km
Load resistance per unit length of shield :
- 12
Ω
/ Km copper core
PVC insulation tinned copper shield
PVC insulation
The maximum authorized distance between the base PLC and the I/O extension is
200 meters (650 feet).
Base PLC
TSX Nano
I/O extension
TSX Nano blue green extension link white shielded twisted pair cable
Note :
Colors shown refer to connection using cable TSX CA 0003 white green blue shield
___________________________________________________________________________
3/14
Connections 3
A
3.6
Connection of peer PLCs
Peer PLCs are connected to the "base PLC" PLC in the same way as I/O extensions, that is via a shielded twisted pair cable (for the cable to use see the previous page).
The maximum permitted distance between the base PLC and the last peer PLC is
200 meters (650 feet).
• Connection of an I/O extension to the "base PLC" PLC, and a peer PLC.
Base PLC
TSX Nano
I/O extension
TSX Nano
Peer PLC 2
TSX Nano shield shielded twisted pair cable shielded twisted pair cable
Note :
If peer PLCs 3 and 4 are used, the continuity of the extension link is provided by a shielded twisted pair cable with identical connections to those between the I/O extension and peer PLC 2.
• Connection of peer PLCs only to the "base PLC" PLC.
Base PLC
TSX Nano
Peer PLC 2
TSX Nano
Peer PLC 3
TSX Nano shield shielded twisted pair cable shielded twisted pair cable
Note :
If peer PLC 4 is being used, the continuity of the extension link is provided by a shielded twisted pair cable with identical connections to those between the I/O extension and peer PLCs 2 and
3.
____________________________________________________________________
3/15
A
3.7
Connection of an analog sensor (TSX 07 32/33 ••28)
The analog sensor is connected to the analog input channel of the PLC via a shielded twisted pair cable (cable identical to the one used to connect an I/O extension, see
Section 3.5).
The maximum permissible distance between the sensor and the analog channel of the
PLC is :
• isolated sensor
• non-isolated sensor
< 30 m (99 feet) with shielded cable,
< 10 m (33 feet) with shielded cable.
TSX Nano PLC
analog module
TSX Nano PLC
analog module
Do not use the NC terminal
Isolated sensor (1)
Non-isolated sensor
(2)
(1) Floating with respect to ground.
(2) Grounding the - of the analog input is recommended.
(3) If a non-isolated sensor is used, the - of the analog input must be grounded.
(3)
___________________________________________________________________________
3/16
Connections 3
A
3.8
Connection of analog modules (TSX AMN 4000/4001)
3.8-1 Connection of analog modules to the "base PLC" PLC
Like discrete I/O extensions, TSX AMN 400• analog modules are connected to the PLC via a shielded twisted pair cable (cable identical to the one used to connect an I/O extension, see Section 3.5).
The maximum permissible distance between the "base PLC" PLC and the last analog module is 200 meters (650 feet).
TSX Nano
"base PLC" PLC
TSX Nano
I/O extension
Analog module 1 shielding shielded twisted pair cable shielded twisted pair cable
Note :
If analog modules 2 and 3 are used, continuity of the extension link is provided by a shielded twisted pair cable with connections identical to those made between the I/O extension and analog module 1.
3.8-2 Connection of analog inputs
The analog input channels of the TSX AMN 400• module can take sensors with either a voltage output or a current output.
The example below illustrates one type of configuration.
Sensor w.
voltage output 1
(1)
Sensor w.
current output 2
(1)
Sensor w.
voltage output 3
(1)
TSX AMN 400•
(1) Maximum 50 meters with Ø 0.5 mm shielded cable (shielding connected at module end)
____________________________________________________________________
3/17
A
3.8-3 Connection of analog outputs
The analog output channel of the TSX AMN 400• module allows connection to an actuator with either a voltage input or a current input.
TSX AMN 400• TSX AMN 400•
Actuator with voltage input
Actuator with current input
(1) Maximum 50 meters with Ø 0.5 mm shielded cable (shielding connected at module end)
___________________________________________________________________________
3/18
Connections 3
A
3.9
Connection of analog inputs (TSX AEN •••)
3.9-1 Connection with input 0 of the TSX Nano wired as sink (positive logic)
24 VDC supply
(1)
TSX 07 •• ••••
(except TSX 07 •1 1648)
(2)
Sensor
(1) Maximum 2 meters with Ø 0.5 mm shielded cable
(2) Maximum 50 meters with Ø 0.5 mm shielded cable (shielding connected at module end)
3.9-2 Connection with input 0 of the TSX Nano wired as source (negative logic)
24 VDC supply
(1)
TSX 07 •• ••••
(except TSX 07 •1 1648)
(2)
Sensor
(1) Maximum 2 meters with Ø 0.5 mm shielded cable
(2) Maximum 50 meters with Ø 0.5 mm shielded cable (shielding connected at module end)
____________________________________________________________________
3/19
A
3.10
Connection of analog outputs (TSX ASN •••)
3.10-1 Connection with source output 0 of the TSX Nano (positive logic)
TSX 07 3• ••12
(1)
24 VDC supply
(2)
Speed controller
(1) Maximum 2 meters with Ø 0.5 mm shielded cable
(2) Maximum 50 meters with Ø 0.5 mm shielded cable (shielding connected at module end)
3.10-2 Connection with sink output 0 of the TSX Nano (negative logic)
TSX 07 3• ••02/08
(1)
24 VDC supply
(2)
Speed controller
(1) Maximum 2 meters with Ø 0.5 mm shielded cable
(2) Maximum 50 meters with Ø 0.5 mm shielded cable (shielding connected at module end)
___________________________________________________________________________
3/20
4
4 Special functions
4.1
RUN/STOP input
Principle
The RUN/STOP input is used to start or stop program execution.
On a base or peer PLC, one of the first 6 inputs (%I0.0 to %I0.5) may, after configuration via the terminal, be assigned to this function.
When powering up the PLC, the PLC state is determined by the RUN/STOP input (if configured) :
• PLC in STOP if the configured RUN/STOP input is at state 0,
• PLC in RUN if the configured RUN/STOP input is at state 1.
While the PLC is powered, a rising edge on the RUN/STOP input sets the PLC to RUN.
The PLC is forced to STOP if the RUN/STOP input is at 0. If the RUN/STOP input is at state 0, a RUN command from a connected terminal will be ignored by the PLC.
Example : RUN/STOP switch on input %I0.3
A
Base PLC
PLC status
Status %I0.3
4.2
PLC status (SECURITY) output
Principle
When the PLC is powered up and if no PLC error (blocking fault see appendix A.6) is detected, the PLC status (security) output changes to 1. It can be used in safety circuits external to the PLC, for example to control :
• The power supply to output devices.
• The PLC power supply.
On a base or peer PLC, one of the first 4 outputs (%Q0.0 to %Q0.3) may, after configuration via the terminal, be assigned to the PLC status (SECURITY) function.
Base PLC
PLC running
PLC stopped or faulty
Output %Q0.0
Example : output %Q0.0 configured as PLC status
(SECURITY) output
Appearance of a fault which stops the PLC
Power supply to outputs
___________________________________________________________________________
4/1
A
4.3
Latching inputs
Principle
When a pulse is shorter than one scan and has a value greater than or equal to
100 µs (1), the PLC latches the pulse, which is then updated in the next scan.
On a base PLC or peer PLC, each of the first 6 inputs (%I0.0 to %I0.5) can be assigned to the special latching function, after configuration via the terminal.
Base PLC
PLC scan
PLC scan
PLC scan
PLC scan
PLC scan
PLC scan
Physical input status
Latching of the physical input status for processing during next scan
Key :
• I : read inputs
• P : process program
• O : update outputs.
Note :
A pulse which lasts longer than one scan will be treated as a pulse received at a standard input.
(1) see Part A, Section 1.7-1
___________________________________________________________________________
4/2
Special functions 4
A
4.4
I/O associated with fast counting
The TSX Nano PLC has a fast counter which can be used in three different ways :
• As a fast counter (maximum frequency 10 kHz).
• As a frequency meter (maximum frequency 10 kHz) which can, in particular, be used to manage an analog input module.
• As a fast up/down counter (maximum frequency 1 kHz).
Sensors with transistor outputs must be used with up/down counter inputs %I0.0 and
%I0.3. NOTE : Do not use sensors with contact outputs with fast counter inputs, as this kind of sensor is susceptible to bounce because of low noise immunity.
Proximity sensor
Photoelectric sensor
Pulse generator (3)
Base PLC
Functions
Upcounter
Counter set
(reset counter to 0)
Enable
Downcounter
_
_
Read the current value (2) _
Threshold output 0 (HSC_Out) _
Threshold output 1 (HSC_Out) _
•
Inputs
%I0.0
%I0.1 %I0.2 %I0.3
%I0.4
_
_ _ _ _
•
(1) _ _ _
_
_
_
_
_
•
_
_
_
_
(1) _
_
_
_
_
•
•
_
_
_
(1)
_
_
_
_
Outputs
%Q0.1%Q0.2
_
_
_
_
_ _
•
(1) _
_
•
(1)
The parameters of the function to be performed (fast counter, frequency meter, up/down counter) are set using a special %FC function block (see Part B, Section 3.4-5).
(1) These I/O are optional. Their use must be declared during configuration.
4/3
A
4.4-1 Use as a fast counter
The fast counter (FC) function enables counting at a maximum frequency of 10 kHz or
5 kHz depending on the selection made at configuration, with the possibility of counting from 0 to 65535 pulses.
Set input to 0
Counting input Enable counter input
Base PLC
(1) 50 µs at 10 kHz
100µs at 5 kHz
FC threshold output 0
FC threshold output 1
The counter receives the pulses to be counted at the PLC input (%I0.0). If the counter enable input (%I0.2) is configured and at state 1, the pulses are counted by the counter and the counting value (current value FC.V) is constantly compared to 1 or 2 thresholds,
FC.S0 and FC.S1, which are defined during configuration but can be modified by the program.
Resetting the counter to 0 is prompted by the rising edge of the input (%I0.1).
The FC threshold outputs 0 and 1 (%Q0.1 and %Q0.2) are controlled directly by the fast counter (without waiting for the outputs to be updated at the end of the scan) according to a matrix defined during configuration.
Output FC.V < thresh. 0 < thresh. 1 thresh. 0 < FC.V < thresh. 1 thresh. 0 < thresh. 1 < FC.V
%Q0.1 0 or 1 0 or 1 0 or 1
%Q0.2 0 or 1 0 or 1 0 or 1
Certain commands (enable counter, set current value to 0), can also be executed from the user program via specific instructions.
Note :
The software setup (configuration, special instructions, etc) and the timing diagram of the fast counter operation are explained in Part B, Section 3.4-5.
___________________________________________________________________________
4/4
Special functions 4
A
4.4-2 Use as a frequency meter
The frequency meter function measures the frequency of a periodic signal (in Hz). The principle of this measurement is to count the number of pulses received within a specified period or time base. The frequency range which can be measured is from 1
Hz to 10 kHz. This function can, in particular, be used to manage an analog input module.
Time base
100ms
1s
Measurement range
10Hz-10kHz
1Hz-10kHz
Accuracy
0.1% for 10kHz
10% for 100Hz
Refresh
10 times per second
0.01% for 10kHz Once per second
10% for 10Hz
Counting input Enable counter input
Base PLC
The frequency meter receives pulses at the PLC input (%I0.0). If the counter enable input (%I0.2) is configured and at state 1, the pulses are accepted by the counter, and the counting value (current value FC.V) changes throughout the measuring period. At the end of the measuring period, the current value FC.V corresponding to the frequency is read.
Input (%I0.1) resets the current value FC.V to 0.
This command (enable counter) can also be executed from the user program.
Note :
The software setup (configuration, special instructions) and the timing diagram of the frequency meter operation are explained in Part B, Section 3.4-5.
___________________________________________________________________________
4/5
A
4.4-3 Use as an up/down counter
The fast up/down counter function counts up or down at a maximum frequency of 1 kHz with the possibility of counting from 0 to 65535 pulses.
Set input Enable up/down counter input
Counting input
Down counting input
Read current value input
Base PLC
FC threshold output 0
FC threshold output 1
The counter receives the pulses to be upcounted at PLC input (%I0.0) and the pulses to be downcounted at PLC input (%I0.3). If the up/down counting enable input (%I0.2) is configured and at state 1, the pulses are taken into account and the up/down counting value (current value FC.V) is constantly compared to 1 or 2 thresholds FC.S0 and
FC.S1, which are defined during configuration and can be modified by the program.
Information about whether the counter is counting up or down is available as a bit in system word SW111.
The preset value (0 to 65535), which is defined during configuration and can be changed by the program, is loaded into the current value on the rising edge of the input
(I0.1).
Input (%I0.4) is used to read the current value FC.V on the fly.
Fast counter threshold outputs 0 and 1 (%Q0.1 and %Q0.2) are controlled directly by the fast up/down counter (without waiting for the outputs to be updated at the end of the scan).
The user can program outputs to be either 0 or 1 under any of the following conditions :
- when FC.V < threshold 0 < threshold 1Z
- when threshold 0 - FC.V - threshold 1
- when threshold 0 < threshold 1 < FC.V
Certain commands (up/down counter enable, set) can also be executed from the user program.
Note :
The software setup (configuration, special instructions) and the timing diagram of the up/down counter operation are explained in Part B, Section 3.4-5.
___________________________________________________________________________
4/6
Special functions 4
A
4.5
PULSE output : generating a pulse train
On a base or peer PLC, output %Q0.0 can be assigned to the special "PULSE" function, after configuration via the terminal.
Principle
A user-defined function block (%PLS) can generate a signal on output %Q0.0. This signal has a variable period but has a constant duty cycle, or on to off ratio, of 50% of the period.
Constant on to off ratio
Variable period
The value of period T and the number of pulses to be generated are defined by configuration of function block %PLS.
Configuration parameters :
• Definition of the period : T = TB x %PLS.P
TB = time base
- 0.1 ms (can only be used on a PLC with transistor outputs)
- 10 ms (default value), or 1s.
%PLS.P = preset value :
- 0 - %PLS.P < 32767 with TB = 10ms or 1s
- 0 - %PLS.P < 255 with TB = 0.1ms
• Definition of number of pulses to be generated on output %Q0.0 : %PLS.N
The number of pulses to be generated in period T (%PLS.N) can be limited or unlimited depending on the definition made at configuration :
- 0 < %PLS.N <32767
- %PLS.N=0 : unlimited generation
Range of periods available include :
• 0.2 ms to 26 ms in steps of 0.1ms (38 Hz to 4.9 kHz).
• 20 ms to 5.45 min in steps of 10 ms
• 2 s to 9.1 hours in steps of 1s.
Note :
The complete parameter setting for function block %PLS is defined in Part B, Section 3.4-4.
Example of application : control of a stepper motor
Base PLC
%PLS function block
Stepper
Amplifier/ translator
Stepper motor
___________________________________________________________________________
4/7
A
4.6
PWM output : pulse width modulation
On a base or peer PLC, output %Q0.0 can be assigned to the specific "PWM" function, after configuration via the terminal. This function, from TSX07 version V3 or later, can be used, in particular, to manage analog output modules.
Principle
A user-definable function block (%PWM) generates a signal on output %Q0.0. This signal has a constant period with the possibility of varying the duty cycle, or on to off ratio.
Variable on to off ratio
Constant period
The value of period T and the percentage of the signal at state 1 in a period are defined in the configuration of function block %PWM :
Configuration parameters :
• Definition of period : T = TB x %PWM.P
TB = time base :
- 0.1ms (obligatory for analog output management; can only be used on a PLC with transistor outputs),
- 10ms (default value), or 1s
%PWM.P = preset value (not used for analog output management) :
- 0 < %PWM.P - 32767 with time base 10ms or 1s
- 0 < %PWM.P - 255 with time base 0.1ms
• Definition of period ratio : %PWM.R = Tx(%PWM.R/100)
%PWM.R gives the percentage of signal at state 1 in a period (0<%PWM.R-100).
Range of periods available :
• 0.2 ms to 26 ms in steps of 0.2 ms (38 Hz to 4.9 kHz).
• 20 ms to 5.45 min in steps of 10 ms.
• 2 s to 9.1 hours in steps of 1s.
Note :
The complete parameter setting for function block %PWM is defined in Part B, Section 3.4-3.
Example of application : control of a dimmer switch
Base PLC
%PWM function block
___________________________________________________________________________
4/8
5
A
5 Characteristics/Service conditions
5.1
Power supply characteristics
PLC
Power supply
Supply voltage
Frequency
Power required nominal limit nominal limit
TSX 07 •• •• 08/28/48
TSX AMN 4000 c (AC)
100 to 240V
85 to 264V
50/60 Hz
47 to 63 Hz
-30VA
TSX 07 •• •• 02/12/22
TSX AMN 4001 a (DC)
24V
19.2 to 30V
_
_
-14W
Inrush current typical 20 A for 1 ms, max 40 A
Integral and electronically fused (1) sensor supply a
24V /150 mA
Micro-cuts duration -10ms
Primary/ground isolation
IEC 1131-2 conformity
2000V rms -50/60 Hz yes
_
-1 ms
2000V rms -50/60 Hz yes
5/1
A
5.2
24VDC and 115VAC discrete input characteristics
PLC
Type
TSX 07 •• ••02/08/12/22/28 a
24V (resistive)
TSX 07 •1 1648 c
115V (capacitive)
Logic (1) pos. (sink) neg. (source) _
Sensor common
Type
Nominal input values voltage current peak current on activation sensor supply to + of supply isolated
24V
7 mA (2)
_ to - of supply _
24V
7mA (2)
_ isolated
110/120V
10 mA
300 mA (at 110V)
19.2 to 30V (including ripple) _
Input limit values
Filtering frequency _ current limitation N/A state 1 voltage current state 0 voltage current
• 11V
• 2.5 mA at 11V
5V
- 1.2 mA
_
- 1.5A
50 to 60 Hz
N/A
- 8V
•
2.5
mA at 8V
•
•
79 V
4mA at 79V
Vps - 5V - 20V
-
1.2
mA - 2 mA frequency _ _ _ 47 to 63 Hz
0 to 1 12 ms 12 ms 12 ms default values
1 to 0 12 ms 12 ms 12 ms
0 to 1 100µs/3ms/12ms on %I0.0 to %I0.7
_ programmable values
375µs/3ms/12ms on %I0.8 to %I0.13
1 to 0 100µs/3ms/12ms on %I0.0 to %I0.7
_
_
375µs/3ms/12ms on %I0.8 to %I0.13
_
Isolation between input and grounding
1500V rms -50/60 Hz
Compatibility 2-wire prox sens yes (TE) yes (TE)
Compatibility yes
IEC 1131-2 conformity yes (type 1) yes
N/A
1500V rms -50/60 Hz yes (TE)
_ yes (type 1)
Note : The I/O characteristics are given for a load rate of 100% for PLCs with 10 I/O and 80% for PLCs with 16 and 24 I/O.
Load = total number of I/O simultaneously at state 1 divided by total number of I/O in the PLC.
(1) Positive or negative logic depending on the wiring (sink or source).
5/2
Characteristics/Service conditions
5.3
24VDC discrete transistor output characteristics
PLC TSX 07 •• •• 02/08 TSX 07 •• •• 12
Type
DC load
Limit values nominal voltage nominal current tungsten filament lamp voltage (including ripple) current
Unfused transistors (sink) a
24V
0.5 A
10W
19.2 to 30V
0.625 A at 30V
Protected transistor transistors (source) c
24V
0.5 A
10W
19.2 to 30V
0.625 A at 30V
Logic
Load common
Leakage current at state 0
Voltage drop at state 1
Response time on resistive load
Electronic fusing for
0 to 1
1 to 0 short-circuits and overloads overvoltages negative (sink) to + of power supply
- 1 mA
- 1.5 V (for I = 0.5 A)
1 ms
1 ms none (fit 1 fuse per output common) yes positive (source) to - of power supply
- 1 mA
- 2V (for I = 0.5 A)
1 ms
1 ms yes yes yes polarity inversions yes
Isolation betw. output and grounding 1500V rms -50/60 Hz
IEC 1131-2 conformity N/A
1500V rms -50/60 Hz yes
Notes :
• The I/O characteristics are given for a load rate of 100% for PLCs with 10 I/O and 80% for PLCs with 16 and 24 I/O.
Load rate = total number of I/O simultaneously at state 1 divided by total number of I/O in the PLC.
• In this case, it is possible to place 2 outputs in parallel. A discharge diode must be placed on the PLC output terminals (not the load terminals).
5
A
___________________________________________________________________________
5/3
A
5.4
Discrete relay output characteristics
PLC TSX 07 •• •• 22/28/48
Type
AC load relay
AC12 resistive duty voltage c
24V current 2A (1)
1A (2)
AC15 inductive
(continuous) duty voltage c
24V current 1A (1)
0.5A (3) c
48V
1A (2) c
48V
0.5A (3)
0.2A (5) c
110V
1A (2)
0.5A (4) c
110V c
220V
1A (3)
0.5A (4) c
220V
0.45A (3) 0.22A (3)
0.090A (5) 0.045A (5)
DC load
Response time
DC12 resistive duty
DC13 inductive duty opening closing
Electronic fusing for overloads and short-circuits inductive c overvoltages inductive a overvoltages voltage current 1A (1) voltage a
24V current 0.4A (3)
-
a
24V
5 ms
10 ms
_
_
_
_
_
_
_
_
_
_
_
_ none, fit 1 fuse per I/O point or group of I/O points none, an RC circuit or an MOV (ZNO) suppressor must be fitted in parallel with the terminals of each output none, a freewheel diode must be fitted in parallel with the terminals of each output
Isolation betw. output and grounding 1500V rms - 50/60 Hz
IEC 1131-2 conformity yes yes yes yes
Note :
The I/O characteristics are given for a load rate of 100% for PLCs with 10 I/O and 80% for PLCs with 16 and 24 I/O.
Load rate = total number of I/O simultaneously at state 1 divided by total number of I/O in the PLC
(1) 0.3 x 10 6 operations
(2) 0.5 x 10 6 operations
(3) 1 x 10 6 operations
(4) 2 x 10 6 operations
(5) 10 x 10 6 operations
___________________________________________________________________________
5/4
Characteristics/Service conditions
5.5
Characteristics of analog I/O (TSX AMN 4000/4001)
5.5-1 Characteristics of analog inputs
Input
Resolution channel number input range input impedance permissible voltage without damage channel 0 channel 1 channel 2
3 (high level)
0..10 V, +/-10 V
0..20 mA, 4..20 mA
100 K
Ω
(1) 125
Ω
(2)
+/- 30 V as voltage
+/- 7.5 V as current
11 bits (+ sign at +/- 10 V)
(4000 points at +/- 10 V)
7 bits (+ sign at +/- 10 V) (4)
11 bits (+ sign at +/- 10 V) (3)
(250 points at +/- 10 V) (4)
(4000 points at +/- 10 V) (3)
7 bits (+ sign at +/- 10 V)
(250 points at +/- 10 V)
10 ms per channel
0.5% of the full scale c
2000 V
Conversion
Isolation conversion time maximum error from 0 to 60 °C voltage between supply and input channels voltage between input channels resistance between input channels and ground
(1) Voltage type input
(2) Current type input
(3) Value when channels 0 and 1 are configured
(4) Value when channels 0, 1 and 2 are configured c 1000 V
> 10 M
Ω
5
A
___________________________________________________________________________
5/5
A
5.5-2 Characteristics of the analog output
Output
Resolution channel number output range load impedance permissible voltage without damage
Conversion
Isolation
(1) Voltage type output
(2) Current type output conversion time max. error from 0 to 60 °C as voltage max. error from 0 to 60 °C as current voltage between supply and the output channel voltage between I/O channels resistance between output channel and ground
1 (high level)
0..10 V, +/-10 V
0..20 mA, 4..20 mA
> 2 K
Ω
(1)
,
< 600
Ω
(2)
+/- 30 V (1), +/- 12 V (2)
11 bits (+ sign at +/- 10 V)
(4000 points at +/- 10 V)
2 ms
1% of the full scale
1.5% of the full scale c
2000 V c
1000 V
> 10 M
Ω
___________________________________________________________________________
5/6
Characteristics/Service conditions 5
A
5.6
Characteristics of analog I/O (TSX AEN/ASN
•••
)
5.6-1 Characteristics common to analog inputs and outputs
Supply nominal voltage
Isolation
Shocks
Vibrations
Climatic environment limit voltages nominal current at 24V a
24V a
21V to 30V
104 mA inrush current 10 A max power drawn 2.5 W voltage between supply and ground voltage between input or output and ground resistance between supply and ground (500V) c
1500 V c
1500 V
> 10 M
Ω resistance between input or output and ground (500V) > 10 M
Ω
300 m/s
2
, 3 shocks per axis, 3 axes
5 to 55Hz, 60 m/s
2
, 2 hours per axis, 3 axes operating temperature storage temperature relative humidity (without condensation) altitude
5.6-2 Characteristics of analog inputs
0 to 60 °C
-25 °C to 70 °C
45 to 85 %
0 to 2000m
Input
Conversion channel number input impedance permissible voltage without damage conversion method resolution conversion time precision (full scale)
Frequency output nominal voltage logic (switch on front panel)
Isolation
1 (high level)
6.6 M
Ω
(1) 250
Ω
(2)
+/- 16 V
U (V)
∅
F (HZ)
10 bits or 12 bits
125 ms (3) /500ms (4)
+/- 1% 0 to 60 °C a
24V positive or negative protection against short-circuits no voltage between input and frequency output c
500 V resistance between input and frequency output >10 M
Ω
(1) 0/10V and -10/+10V modules (2) 4/20 mA module
(3) 10-bit resolution (4) 12-bit resolution
___________________________________________________________________________
5/7
A
5.6-3 Characteristics of analog outputs
Output
Conversion channel number output signal value load impedance permissible voltage without damage protection against short-circuits conversion method resolution conversion time
1 (high level)
0/10 V
-5 K
Ω
(1) -250
Ω
(2)
+/- 12 V yes (continuous)
F (Hz)
∅
U (V)
8 bits from 0 to 90%: 500ms max
Isolation precision (full scale)
Frequency input nominal voltage
+/- 1% 0 to 60 °C a
24V positive or negative logic (switch on front panel) input frequency 312.5 Hz voltage between output and frequency input c
500 V resistance between output and frequency input >10 M
Ω
(1) 0/10V and -10/+10V modules (2) 4/20 mA module
___________________________________________________________________________
5/8
Characteristics/Service conditions 5
A
5.7
Characteristics of the analog input (TSX 07 32/33 ••28)
Analog input
Conversion
Isolation channel number 1 (high level) input signal value 0 / 10 V value of an LSB input impedance
40 mV
16 K
Ω < Ζ <
18 K
Ω maximum permissible voltage without damage +/- 16 V protection against polarity inversion conversion method resolution conversion time precision at full scale yes approx. successive
8 bits
1 PLC scan
+/- 0.8% at 25 °C
+/- 2% at 60 °C drift repeatability at full scale between analog channel and CPU
0.34% / 10 °C
+/- 0.8% from 0 to 60 °C none distance between sensor and analog input : isolated sensor < 30 m with shielded cable non-isolated sensor < 10 m with shielded cable
Important
If using a sensor which is not isolated from ground, the - of the analog input must be grounded.
___________________________________________________________________________
5/9
A
5.8
Service conditions
5.8-1 Standards
TSX Nano PLCs have been developed to comply with the main national and international standards concerning electronic industrial control devices.
• Specific PLC requirements : operating characteristics, filtering, ruggedness, safety, etc.
EN61131-2 (IEC1131-2), CSA 22.2,
UL508
• Strict limitation of electromagnetic interference generated : CE marking
(European Directives on Low Voltage and EMC) EN 50081-1, class B.
• Electrical qualities and selfextinguishing capability of insulating materials : UL 746C, UL 94, etc.
• Marine certification
- Bureau Veritas
- DNV
- GL (pending)
5.8-2 Environment, normal service conditions
• Climatic environment, normal conditions
Temperature
Operating temperature : 0 to 60°C (1)
Storage temperature : - 25°C to + 70°C
Humidity and altitude
Relative humidity : 5% to 95% (2)
(non-condensing)
Altitude : 0 to 2000 meters (0-6500 feet)
• Resistance to vibration : In accordance with IEC 68-2-6 FC tests
• Resistance to mechanical shocks : In accordance with IEC 68-2-27 EA tests
(1) 0 to 55°C with TSX 07 •• •• 12 when mounting vertically (on vertical plane)
(2) 45% to 85% for TSX AMN 4000/4001 modules
___________________________________________________________________________
5/10
6
6 Setup
A
6.1
Procedure for first power-up
The TSX Nano incorporates several selftests which continually monitor its operation.
The results of these self-tests are displayed on the front panel of the PLC. They can be made more detailed using the terminal. (1)
The diagram below shows the procedure for powering up the PLC for the first time.
TSX Nano PLC
Power up, outputs not powered
T e r m i nals
(see Part D,
Section 1)
(see Part D,
Section 1)
Initialize the PLC memory memory initialized by the terminal
• Connect the terminal.
• Initialize PLC memory by clearing the whole memory (Prg menu, Clr command).
"new" application and transfer it to the PLC.
Possible actions
• Check I/O connections.
• Configure and enter the program from the terminal :
- either directly into PLC memory (TSX mode)
- or into terminal memory (FTX mode), then transfer to the PLC memory.
• Set to RUN using RUN/STOP input %10.
• if it is configured, or via the terminal.
Key
LED flashing
LED lit continuously
(1) herein, the word "terminal" represents the FTX 117 Handheld terminal, or a PC compatible terminal or FTX 417/517/FT 2000 running PL7-07 PC programming software for the TSX Nano
6/1
A
Summary
Power up the PLC
Connect the terminal and clear the PLC memory from the terminal (FTX 117) or create a new application
Configure the application and enter program from the terminal :
• either directly into PLC memory (TSX)
• or into terminal memory (FTX)
No
Enter program in terminal memory
Yes
Transfer the program to the PLC
RAM and EEPROM memories
Start program execution using the RUN command :
• either by the RUN/STOP input if it has been configured
• or from the terminal, using the RUN command
___________________________________________________________________________
6/2
Setup 6
A
6.2
Checking the I/O connections
• Principle
This check ensures that :
- data from the sensors is received by the inputs and transmitted to the processor,
- commands from the processor activate the outputs and are transmitted to the corresponding output devices.
• Recommendations
In order to avoid any random movement of the machine, it is recommended that :
- power fuses be removed from the motor controls,
- pneumatic and hydraulic inputs be closed.
• Procedure
- Power up for the first time, as shown in Section 6.1. Ensure that the I/O
LED is not lit continuously.
- Leave the PLC in STOP.
- Select the Data Editor on the FTX 117 terminal, or the PL7-07 software.
TSX Nano PLC
- Change the state of system bit %S8 (PLC status output) to state 0.
Terminals
- Check the inputs by activating each sensor :
- Check that the LED on the front panel for the corresponding input changes state.
- Check on the terminal screen that the corresponding bit also changes state.
- Check the outputs using the terminal :
- Force the bit corresponding to each output to state 1.
- Check that the LED for the corresponding output changes state, as well as the associated output device.
- Using the terminal :
- Remove all forcing
- Reset system bit %S8 to state 1 (the outputs are set at 0).
Note :
If the PLC does not contain the application program, this entire procedure can be performed in
RUN. In this case, bit %S8 can remain at state 1 (default state).
___________________________________________________________________________
6/3
A
___________________________________________________________________________
6/4
7
7 Addendum
7.1
Power outages and returns
• Characteristics of power outages
- If power outages < power supply ridethrough : normal execution of the program
- If power outages > power supply ridethrough : processor powered down with context (data & program) saved.
• Warm restart : PLC restarts with the contents of the data memory in the same state as at the time of the power outage.
List of possible causes :
- PLC restart after power outage > power supply ridethrough
- System bit %S1 set to state 1 by the program or the terminal
Consequences upon return of power
- System bit %S1 set to state 1,
- Non-forced input bits set to state 0 (warning : setting to zero generates a "false"
rising edge on an input physically at 1 during a warm restart, see part B, section
2.1-2).
- All I/O bits set to 0,
- All unsaved internal bits set to state 0 (%M64 to %M127)
- The state of the stored internal bits (%M0 to %M63) and current values of the function blocks (timers, counters, etc) are maintained
- The scan is restarted from the point at which it stopped at the power outage, without updating the outputs at the end of the scan. The scan is then restarted normally :
Reading the inputs
∅
program processing
∅
updating the outputs and setting system bit %S1 to 0
• Cold restart : PLC restarts with loss of contents of the data memory
List of possible causes :
- Back-up battery defective or absent
- System bit %S0 set to 1 by the program or the terminal
- Initialization of the PLC by the terminal
Consequences upon return of power
- System bit %S0 set to state 1
- All internal bits, I/O bits and internal words set to state 0
- The current values of the function blocks (timers, counters, etc), registers and step counters set to state 0
- Adjustment values modified by the terminal lost, and preset values defined during configuration recalled
- System bits and words initialized (except %S0 and the schedule block (RTC) data)
- Forcing cancelled
- Grafcet reinitialized
- Scan restarted from the beginning :
Reading the inputs
∅
program processing
∅
updating the outputs and setting system bit %S0 to 0.
A
___________________________________________________________________________
7/1
A
Programming example
In order to avoid automatic restarting of the control system when power returns, the program below enables manual intervention by pressing a "RESTART" button and keeps the outputs at 0 during the power outage. This program must be added to the application program.
One part of this program must be at the start of the program (pre-processing zone), the other part must be at the end of the program (post-processing zone).
End of program
000 LD %S0 If %S0 is at logic level 1: cold restart
001 OR %S1 OR %S0 is at logic level 1: warm restart
002 OR %M10 OR %M10 is at logic level 1: latch
003 S %M10 Set internal bit %M10 to 1
004 ST %S9 Set outputs to 0
005 JMPC %L0 Jump to label %L0 if %S9 is at 1
006
007
----
----
098
099
100 %L0 : Jump address
101 LD %M10 If %M10 is at logic level 1
102 AND %I0.1 AND input 1 is at logic level 1: RESTART
103 R %M10 Set internal bit %M10 to 0
104 END End of program in preprocessing zone (start of program)
Application program in post-processing zone (end of program)
___________________________________________________________________________
7/2
Addendum 7
A
7.2
Initializing the PLC
Presentation
The PLC can be initialized by the program by setting system bit %S0 to 1, which corresponds to a cold restart (see Section 7.1). During a warm restart, it may be necessary to initialize the PLC. The example below shows how this can be programmed. Initialization can also be requested from the terminal using the INIT command.
Programming
LD %S1
ST %S0
If %S1 = 1 (warm restart), set %S0 to 1 to initialize the PLC. These two bits are reset to 0 by the system at the end of the following scan.
IMPORTANT
System bit %S0 must not be set to 1 for more then one PLC scan.
7.3
Saving the program and data
Saving in the RAM
The user program and the data are contained in the PLC RAM memory. A battery in the PLC provides the memory with independent operation for 30 days.
WARNING
This independence is ensured only if the battery is charged for at least 6 consecutive hours before the PLC is stopped.
___________________________________________________________________________
7/3
A
EEPROM storage
It avoids the risk of corrupting the program held in the RAM during a battery failure or a power outage lasting longer than 30 days.
On power-up, the PLC checks the integrity of the programs contained in the RAM and
EEPROM memories. In the event of data corruption, the program contained in the
EEPROM is automatically transferred to the RAM if the MST option (autoloading) has been selected (see part C, section 12.4).
PLC memory
RAM program and data
EEPROM program
WARNING
Once the application has been debugged, it is advisable to transfer it into EEPROM with the MST option selected
___________________________________________________________________________
7/4
Description of Instruction List Contents and Ladder languages Part B
Section Page
1.2 Instruction List (List or IL) 1/1
1.4-1 Programming principles 1/6
1.4-3 Reversible List programming conventions 1/9
2 Combinational and sequential instructions 2/1
2.1-1 Definition of the main bit objects 2/1
2.1-2 Introduction to Boolean instructions 2/2
2.1-3 Load instructions LD, LDN, LDR, LDF 2/4
2.1-4 Assignment instructions ST, STN, S, R 2/4
2.1-5 Logic AND instructions : AND, ANDN, ANDR, ANDF 2/5
2.1-6 Logic OR instructions : OR, ORN, ORR, ORF 2/5
2.1-7 Exclusive OR instructions : XOR, XORN, XORR, XORF 2/6
2.1-10 Instructions MPS, MRD, MPP 2/9
2.1-11 Special Ladder instructions OPEN and SHORT 2/10
2.2 Standard function blocks 2/11
2.2-1 Bit and word objects associated with standard function blocks 2/11
2.2-2 Programming principles 2/12
2.2-3 Timer function blocks %TMi 2/13
2.2-4 Up/down counter function blocks %Ci 2/17
2.2-5 LIFO/FIFO register function blocks %Ri 2/20
2.2-6 Drum controller function block %DRi 2/23
___________________________________________________________________________
B/1
B
Description of Instruction List and Ladder languages
Contents
Part B
B
Section
2.4-1 Program end instructions END, ENDC, ENDCN
2.4-3 Jump instructions JMP, JMPC, JMPCN to a label %Li:
2.4-4 Subroutine instructions SRn, SRn:, RET
2.4-5 Master control relay instructions MCR and MCS
Page
3 Numerical and special instructions
3.1-1 Definition of word objects
3.1-3 Introduction to numerical instructions
Analog channel (TSX 07 32/33 •• ••)
3.4-1 Bit and word objects associated with dedicated function blocks
3.4-3 Pulse width modulation output % PWM
3.4-4 Pulse generator output % PLS
___________________________________________________________________________
B/2
Description of Instruction List and Ladder languages
Contents
Part B
Section
3.4-5 Fast counting functions, frequency meter and up/down counter %FC
3.4-6 Transmitting/Receiving messages and controlling data exchanges
3.4-7 Shift bit register function blocks %SBRi
3.4-8 Step counter function blocks %SCi
Page
Communication between PLCs 3/49
TSX AMN 4000/4001 analog modules 4/2
4.2-1 Operating principle of analog modules
4.2-2 Programming analog modules
4.2-3 Using %IW words in the user program
4.2-4 Diagnostics of communication status with analog modules 4/6
Analog input modules TSX ASN •••
4.3-1 Configuring analog inputs
4.3-2 Programming analog inputs
4.3-4 Example of analog input programming
4.3-3 Response time of analog inputs
4.3-5 Characteristics of analog inputs
Analog output modules TSX AEN •••
4.4-1 Configuring analog outputs
4.4-2 Programming analog outputs
4.4-3 Response time of analog outputs
4.4-4 Example of analog output programming
4.4-5 Characteristics of analog outputs
___________________________________________________________________________
B/3
B
Description of Instruction List and Ladder languages
Contents
Part B
B
Section
5.4-1 Setting the date and time using the terminal
5.4-2 Updating date and time using system words
6 Role of system bits and words
6.1-2 Detailed description of system bits
6.2-2 Detailed description of system words
Reactivating protected transistor outputs on TSX 07•• •• 12
Page
___________________________________________________________________________
B/4
Preface
Part B contains 2 levels of information :
• That which enables the user to carry out simple functions. In this case, it is not necessary to read the entire manual, only to refer to the paragraphs in gray.
• That which enables the user to carry out all the functions offered by the TSX Nano. In this case, the whole manual is relevant.
B
1
A
B
2
1 Introduction
1.1
General
The control decisions a PLC makes are based on a control program that you create.
Creating a TSX Nano PLC control program consists of writing a program in one of the control languages supported by the TSX07 PLCs.
The FTX 117 Handheld Terminal supports the List Programming Language. The List language is a line based textual boolean-like language which can also process numerical operations.
The PL7-07 PC Programming Software supports the List and Ladder programming languages. Ladder is a rung-based graphical Boolean language. Further, PL7-07 allows you to reverse a program from Ladder to List and from List to Ladder.
B
In addition, the TSX Nano PLCs support Grafcet List instructions.
1.2
Instruction List (List or IL)
Program structure
A program in PL7 language comprises a series of instructions (up to 1000 instructions) of various types.
Each program line has a number which is generated automatically, an instruction code and a bit or word type operand.
Example of an instruction : 003 LD %I0.1
Number
Instruction code
Operand
Ladder diagrams are a graphical means of displaying a logical expression. An alternative to a Ladder diagram is an Instruction List program. An Instruction List program is a series of logical expressions written as a sequence of Boolean instructions. All the Boolean instructions, except for LOAD, STORE and NOT, operate on two operands, which can be either TRUE or FALSE, and produce a single value, either TRUE or FALSE.
As written, List instructions have only one explicit operand; the other is implied. The implied operand is the Boolean accumulator. In operation, a List instruction performs the specified operation on the contents of the accumulator and the operand, and replaces the contents of the accumulator with the result.
For example, the operation AND %I1.2 would perform a logical AND between the contents of the accumulator and Input 1.2, and would replace the contents of the accumulator with that result.
___________________________________________________________________________
1/1
B
The LOAD and STORE instructions either load the accumulator with the value of the operand, or store the accumulator to the operand, respectively. The NOT instruction has no explicit operands and simply inverts the state of the accumulator.
Instructions
Types of instruction
• Bit instruction
• Block instruction
• Word instruction
• Program instruction
• Grafcet instruction
Example
004 LD %M10
008 IN %TM0
Reads internal bit %M10
Starts the timer %TM0
010 [%MW10 := %MW50+100] Addition
015 SR5 Calls up subroutine #5
020 -*-8 Step #8
___________________________________________________________________________
1/2
Introduction
1
1.3
Grafcet
Grafcet is an analytical method which divides any sequential control system into a series of steps, with which actions, transitions and conditions are associated.
PL7-07 language has specific Grafcet instructions.
Graphical Grafcet is not supported in PL7-07 PC Programming Software.
B
Graphical Grafcet
-*-
LD
#
#
-*-
LD
#
-*-
LD
#
...
Grafcet list
3
%M10
4
5
4
%I0.7
6
5
%M15
7
Grafcet Ladder
___________________________________________________________________________
1/3
B
1.4
Ladder diagrams
Ladder diagrams are similar to relay logic diagrams used to represent relay control circuits. The main differences between the two are that in ladder programming, all inputs are represented by contact symbols ( -| |- ) and all outputs are represented by coil symbols ( -( )- ), and that numerical operations are included in the graphical Ladder instruction set.
The figure above illustrates a simplified wiring diagram of a relay logic circuit and its equivalent Ladder diagram. Notice that in the Ladder diagram, all inputs associated with a switching device in the relay logic diagram are shown as contacts. The M1 output coil in the relay logic diagram is represented with an output coil symbol in the Ladder diagram. The address numbers appearing above each contact/coil symbol in the
Ladder diagram reference the location of the external input/output connections to the
PLC.
A program written in Ladder is composed of rungs—sets of specific graphical instructions drawn between the two vertical outer bars representing potential—that are executed sequentially by the PLC. The set of graphical instructions represent :
• the inputs/outputs of the PLC (push buttons, sensors, relays, pilot lights...),
• the functions of the PLC (timers, counters...),
• the math and logic operations (addition, division, and, xor...),
• the comparison operators and other numerical operations (A < B, A = B, shift, rotate...),
• the internal variables in the PLC (bits, words...).
___________________________________________________________________________
1/4
These graphical instructions are arranged with vertical and horizontal connections leading ultimately to one or several outputs and/or actions.
A rung cannot support more than one group of linked instructions.
For example, this Ladder program is composed of two rungs.
Introduction
1
B
___________________________________________________________________________
1/5
B
1.4-1 Programming principles
Each Ladder rung is comprised of 7 lines and 11 columns and are organized in two zones :
Lines
Test Zone
Action Zone
• a test zone which contains the conditions that must be true for an action to take place.
• an action zone which contains the output or operation that results from the tests connected to it.
The rung is visualized by a 7 by 11 programming grid, starting in the upper-leftmost cell of the grid. You program test instructions, comparisons, and functions in the test zone and these test instructions are left-justified. This test logic then provides continuity to the action zone where you program coils, numerical operations and program flow control instructions. These action instructions are right-justified. The rung is solved, or executed (tests made and outputs assigned), from top to bottom and from left to right.
In addition to the rung, there is the Rung Header that appears directly above the rung.
The rung header is used to document the logical intent of the rung. The rung header contains the rung number, any labels (%Li:) or subroutine declarations (SRi:), the rung title, and rung comments. For more information about the Rung Header, and its correspondence to List Line Comments, see section B.1.4-3.
___________________________________________________________________________
1/6
Introduction
1
• Contacts, coils and program flow instructions
Contacts, coils and program flow (jump and call) instructions occupy a single cell of the programming grid. Function blocks,
Comparison blocks and Operate blocks occupy multiple cells.
• Function Blocks
Function blocks are placed in the Test
Zone of the programming grid. The block must appear in the first line; no Ladder instructions or lines of continuity may appear above or below the Function block.
Ladder test instructions lead to the Function block's input side, and test instructions and/or action instructions lead from the block's output side.
Function blocks are vertically orientated and occupy 2 columns by 4 rows of the programming grid.
• Comparison Blocks
Comparison blocks are placed in the Test
Zone of the programming grid. The block may appear in any line or column in the test zone as long as the entire length of the instruction resides in the test zone.
Comparison blocks are horizontally orientated and occupy 2 columns by 1 row of the programming grid.
• Operate Blocks
Operate blocks are placed in the Action
Zone of the programming grid. The block may appear in any line in the action zone.
The instruction is right-justified; therefore, it appears on the right and ends in the last column.
Operate blocks are horizontally orientated and occupy 4 columns by 1 row of the programming grid.
___________________________________________________________________________
1/7
B
B
1.4-2 Reversibility
In this manual, the term reversibility refers to the ability of the PL7-07 Programming software for the TSX Nano to convert TSX Nano application programs from the Ladder programming language to the List language and back again. PL7-07 programs can be displayed in either format at will by setting a preference for one or the other. You can even convert (reverse) individual Ladder rungs to List and back simply by selecting the
Tools menu’s Toggle Ladder/List option.
LD %I0.5
OR %I0.4
ST %Q0.4
Understanding of reversibility lies in the relationship of the “Rung”—the collection of
Ladder programming instructions that constitute a logical expression—and the
“Sequence”—the collection of List programming instructions that accomplish the same. The figure above demonstrates an example of a common rung in Ladder in any user program. Next to the Ladder rung is the equivalent program logic expressed as a List sequence.
In essence, the program you write, whether it be in Ladder or List, is kept internally as
List. PL7-07 takes advantage of the program structure similarities between the two languages and uses this internal List image of your program to display it in the List /
Ladder Viewer and Editors as either a List program (its basic form), or graphically as a Ladder diagram, depending upon the preference you select. Therefore, everything created in Ladder can always be reversed to List, but some List logic may not reverse to Ladder. To ensure reversibility from List to Ladder, it is important to follow the set of
List programming conventions contained in section B.1.4-3.
___________________________________________________________________________
1/8
Introduction
1
1.4-3 Reversible List programming conventions
The structure of a reversible function block in List language requires the use of certain specific instructions. They are :
- BLK which marks the block start, and defines the beginning of the rung and the start of the input portion to the block,
- OUT_BLK (marks the beginning of the output portion of the block)
- END_BLK (obviously, marks the end of the block and the rung).
The use of the reversible Function Block instructions are not mandatory for a properly functioning List program. For some instructions it is possible to program in List which is not reversible. Non-reversible List programming is described in the Function Block descriptions in section B2.2.
Another important convention is to avoid the use of certain List instructions, or certain combinations of instructions and operands, which have no equivalence in Ladder. For example, the N instruction (bit Not inverses the boolean accumulator) has no equivalent Ladder instruction. In the table below is a listing of all the List programming instructions that will not reverse to Ladder.
List Instruction
JMPCN
N
ENDCN
XORN
Operand
%Li none none any
Description
Jump Conditional Not
Negation (NOT)
End Conditional Not
XORN preceded by OR logic
Unconditional rungs also follow a List programming convention to ensure List-to-Ladder reversibility. An unconditional rung is a rung in which there are no tests or conditions; the output and/or action instruction(s) is (are) energized, or executed, all the time. The figure below illustrates unconditional rungs and List equivalent sequences.
B
LD
ST
LD
1
%Q0.4
1
[%MW5 := 0]
JMP %L6
___________________________________________________________________________
1/9
B
Notice that each of the unconditional List sequences, with one exception, begin with a Load instruction followed by the number 1. The combination sets the boolean accumulator value to one, and therefore sets the coil (store instruction) to one and sets
%MW5 to zero on every scan of the program. The exception is the unconditional jump instruction. This List instruction is executed regardless of the value of the accumulator, and consequently does not need the accumulator set to one as do the previous two examples.
If you try to reverse a List program that is not completely reversible, the reversible portions are displayed in Ladder and the irreversible portions are displayed in “Ladder
List Rungs.” Ladder List Rungs function just like a small list editor, enabling you to view and modify the irreversible parts of a Ladder program.
Program Documentation
The List editor allows you to document your program with List Line Comments. These comments may appear on the same line as programming instructions, or they may appear on lines of their own. The Ladder Editor allows you to document your program with Rung Headers found directly above the rung.
PL7-07 uses these comments for reversibility. When reversing a program from List to
Ladder, PL7-07 uses some of the List comments to construct a Rung Header. Simply, the comments that may be found between List sequences are used for the Rung
Headers.
___________________________________________________________________________
1/10
Introduction
1
The first comment found on a line by itself (no instruction appears on the line with it) after the end of a List sequence is used for the Rung Title. Then, the next comments found after the first, if any exist, are used for the body of the rung. Once the body lines of the header are occupied, then the rest of the line comments between List sequences are ignored, as are any comments that are found on List lines that also contain List instructions.
When a Ladder rung that contains a Rung Header is reversed to List, the Rung Header documentation is inserted between the List sequences. Any labels or subroutine declarations (%Li: or SRi:) are placed on the next line following the header, immediately prior to the beginning of the List Sequence. If the rung that is reversed was originally written in List, and there were comments ignored when List was reversed to Ladder, those comments will reappear in the List Editor.
B
___________________________________________________________________________
1/11
B
___________________________________________________________________________
1/12
2 Combinational and sequential instructions
2.1
Boolean processing
2.1-1 Definition of the main bit objects
• I/O bits
The addressing system for these bits is described in Part A, Section 1.5.
These bits are the "logical images" of the electrical state of the I/O. They are stored in the data memory and updated during each scan of the program logic.
• Internal bits
Internal bits are internal storage areas available to the user for program use.
Note : I/O bits which are not in use cannot be used as internal bits.
• System bits
System bits %S0 to %S127 are used to monitor the correct operation of the PLC as well as the correct execution of the application program. The role and use of these bits are explained in Part B, Section 6.
• Step bits
Bits %X1 to %X62 are the bits associated with the Grafcet steps. Step bit Xi is set to 1 when the corresponding step is active, and to 0 when the step is deactivated.
• Bits extracted from words : see Section 3.1-1
List of operand bits
The following table lists all types of operand bits.
Type Address
(or value)
Immediate value
Maximum number
0 or 1
Bits
Bits
Bits input output internal system
%I0.i or %I1.i (2)
%Q0.i or %Q1.i (2)
%Mi
% S i
% X i Bits of Grafcet steps (5)
Bits of function blocks
%TMi.Q, %DRi.F, etc
Bits of reversible function blocks
E,D,F,Q,TH0,TH1
Bits word extracts varies
Write access (1)
_
28
20
128 (3)
128
62 varies
See
Sect.
_ no yes yes depends on i yes no (4) no varies
_
1.5
Pt. A
5.1
2.3-1
2.2-1
3.3-1
3.1-1
B
(1) Written by the program or in the Data editor by the terminal.
(2) Where i = 0 for a PLC base or a peer PLC, i = 1 for an I/O extension, and j = I/O point. I/O bits can be forced to 0 or 1 in the Data editor.
(3) The first 64 are saved in the event of a power outage.
(4) Except for %SBRi.j and %SCi.j, these bits can be read and written.
___________________________________________________________________________
2/1
B
2.1-2 Introduction to Boolean instructions
Boolean instructions can be compared to Ladder language elements.
Test elements, example : the LD (LOAD) instruction is equivalent to an open contact.
LD %I0.0
Boolean equation :
LD %I0.0
AND %I0.1
ST %Q0.0
Contact closed when the controlling bit is at state 1.
Action elements, example : the ST (STORE) instruction is equivalent to a coil.
ST %Q0.0
The associated bit object takes the logical value of the bit accumulator (result of previous logic).
The Boolean result of the test elements is applied to the action element.
Rising and falling edge
Test instructions can be used to detect rising or falling edges on the PLC inputs. An edge is detected when the state of an input has changed between scan n-1 and the current scan n, and it remains detected during the current scan.
The LDR instruction (R : Rising edge) is equivalent to a rising edge detection contact :
LDR %I0.0
(1)
Rising Edge : detects a change of the controlling input from 0 to 1.
The LDF instruction (F : Falling edge) is equivalent to a falling edge detection contact :
LDF %I0.0
(2)
Falling Edge : detects a change of the controlling input from 1 to 0.
time
Boolean result
1 PLC scan time
Boolean result time
1 PLC scan time
Instructions on a rising or falling edge apply to inputs %I, but it is possible to
LD %M0
ANDN %M10 detect edges on any other bit (or Boolean result) using 2 internal bits.
ST %M11
LD %M0
In the example opposite, bit %M11 records the rising edge of bit %M0.
ST %M10
(1) Positive transition sensing contact
(2) Negative transition sensing contact
(3) On a cold or warm restart, the application detects a rising edge even if the input has remained at 1. This phenomenon can be masked by starting the program on LD %S1 and
ENDC instructions.
___________________________________________________________________________
2/2
Combinational and sequential instructions
2
Instruction format
The Boolean instruction described appears in bold type. Each equation is illustrated by the corresponding Ladder diagram.
B
Load instructions LD, LDN, LDR, LDF
The instructions LD, LDN, LDR and LDF correspond respectively to the open, closed, rising edge and falling edge contacts.
LD
ST
%I0.1
%Q0.3
LDN %M0
ST %Q0.2
LDR %I0.2
ST %Q0.4
LDF %I0.3
ST %Q0.5
Code Operand
LD 0/1,%I,%Q,%M,%S,%X,%BLK.x,%•:Xk,[
LDN %I,%Q,%M,%S,%X,%BLK.x,%•:Xk,[
LDR %I
LDF%I
List of operands
0/1
%I
% Q
%M
%S immediate value 0 or 1
PLC input %Ii.j
PLC output %Qi.j
internal bit %Mi system bit %Si
%X step bit %Xi
%BLK.xfunction block bit, e.g. %TMi.Q
[
%•:Xk word bit, e.g. %MWi:Xk
Comparison expression e.g. [%MWi<1000]
Timing diagram
The 4 timing diagrams have been grouped together.
Timing diagram for the LD instruction
Input state
Output state
___________________________________________________________________________
2/3
B
2.1-3 Load instructions LD, LDN, LDR, LDF
The instructions LD, LDN, LDR and LDF correspond respectively to the open, closed, rising edge and falling edge contacts (LDR and LDF only on PLC inputs).
LD %I0.1
ST %Q0.3
LDN %M0
ST %Q0.2
LDR %I0.2
ST %Q0.4
LDF %I0.3
ST %Q0.5
Code Operand
LD 0/1,%I,%Q,%M,%S,%X,%BLK.x,%•:Xk,[
LDN %I,%Q,%M,%S,%X,%BLK.x,%•:Xk,[
LDR %I
LDF %I
2.1-4 Assignment instructions ST, STN, S, R
The instructions ST, STN, S and R correspond respectively to the direct, inverse, set and reset coils.
LD %I0.1
ST %Q0.3
STN %Q0.2
S %Q0.4
LD %I0.2
R %Q0.4
Code Operand
ST %Q,%M,%S,%BLK.x,%•:Xk
STN %Q,%M,%S,%BLK.x,%•:Xk
S %Q,%M,%S,%X,%BLK.x,%•:Xk
R %Q,%M,%S,%X,%BLK.x,%•:Xk
___________________________________________________________________________
2/4
Combinational and sequential instructions
2
2.1-5 Logic AND instructions : AND, ANDN, ANDR, ANDF
These instructions perform a logic AND between the operand (or its inverse, or its rising or falling edge) and the Boolean result of the preceding instruction.
LD %I0.1
AND %M1
ST %Q0.3
LD %M2
ANDN %I0.2
ST %Q0.2
LD %I0.3
ANDR %I0.4
S %Q0.4
LD %M3
ANDF %I0.5
S %Q0.5
Code Operand
AND 0/1,%I,%Q,%M,%S,%X,%BLK.x,%•:Xk,[
ANDN %I,%Q,%M,%S,%X,%BLK.x,%•:Xk,[
ANDR %I
ANDF %I
B
2.1-6 Logic OR instructions : OR, ORN, ORR, ORF
These instructions perform a logic OR between the operand (the inverse of the operand, a rising or falling edge) and the Boolean result of the preceding instruction.
LD
O R
ST
%I0.1
%M1
%Q0.3
LD %M2
ORN %I0.2
ST
LD
%Q0.2
%M3
ORR %I0.4
S %Q0.4
LDF %I0.5
ORF %I0.6
S %Q0.5
Code Operand
OR 0/1, %I,%Q,%M,%S,%X,%BLK.x,%•:Xk
ORN %I,%Q,%M,%S,%X,%BLK.x,%•:Xk
ORR %I
ORF %I
___________________________________________________________________________
2/5
B
2.1-7 Exclusive OR instructions : XOR, XORN, XORR, XORF
These instructions perform an exclusive OR between the operand (the inverse of the operand, a rising or falling edge) and the Boolean result of the preceding instruction.
The XOR instruction can be used in either of the following ways, for example :
LD %I0.1
XOR %M1
ST %Q0.3
LD %I0.1
ANDN %M1
OR( %M1
)
ANDN %I0.1
ST %Q0.3
Code Operand
XOR %I,%Q,%M,%S,%X,%BLK.x,%•:Xk
XORN %I,%Q,%M,%S,%X,%BLK.x,%•:Xk
XORR %I
XORF %I
Special cases
• In Ladder, XOR contacts cannot be
- situated at the left (first position) of a rung,
- placed in parallel.
For example, attempting to enter the following rung will generate a Validation error.
___________________________________________________________________________
2/6
Combinational and sequential instructions
2
2.1-8 NOT instruction : N
This instruction negates the Boolean result of the preceding instruction.
LD %I0.1
O R %M2
ST %Q0.2
N
AND %M3
ST %Q0.3
B
Code Operand
N _
Note : The instruction N is not reversible.
2.1-9 Using parentheses
The instructions AND and OR can use parentheses. These parentheses are used for parallel branches in Ladder diagrams. Opening the parenthesis is associated with the
AND or OR instruction. Closing the parenthesis is an instruction, which must be given for each open parenthesis.
Example : AND(...)
LD %I0.0
AND %I0.1
O R %I0.2
ST %Q0.0
LD %I0.0
AND( %I0.1
O R %I0.2
)
ST %Q0.0
Example : OR(...)
LD %I0.0
AND %I0.1
OR( %I0.2
AND %I0.3
)
ST %Q0.0
___________________________________________________________________________
2/7
B
The following modifiers can be assigned to parentheses N, F, R or [ :
• N negation, for example, AND(N or OR(N
• R rising edge, for example, AND(R or OR(R
• F falling edge, for example, AND(F or OR(F
• [ comparison, see Section 3.1-5
LD %I0.0
AND %I0.1
OR(N %I0.2
)
AND %I0.3
ST %Q0.0
Nesting parentheses
It is possible to nest up to 8 levels of parentheses.
Example
LD %I0.0
AND( %I0.1
)
OR(N %I0.2
AND %M3
)
ST %Q0.0
Example
LD %I0.1
AND( %I0.2
AND %I0.3
OR( %I0.5
)
AND %I0.6
AND %I0.4
OR( %I0.7
AND %I0.8
)
)
ST %Q0.0
Note :
• Each parenthesis opened must be closed again.
• %Li: labels and SRi: subroutines must not be placed in expressions between parentheses. This is also the case for jump (JMP), subroutine (SRi) and function block instructions. See Section
2.4-3 for more information.
• Assignment instructions ST, STN, S and R must not be programmed between parentheses.
___________________________________________________________________________
2/8
Combinational and sequential instructions
2
2.1-10 Instructions MPS, MRD, MPP
These 3 types of instruction are used to process the routing to the coils.
They use a temporary storage area referred to as the stack which can store up to 8
Boolean expressions.
The instruction MPS pushes the accumulator (the result of the last logical operation) onto the top of the stack and shifts the other values towards the bottom of the stack.
The instruction MRD reads the top of the stack into the accumulator.
The instruction MPP pops the top of the stack into the accumulator and shifts the other values towards the top of the stack.
Examples :
LD %I0.0
AND %M0
MPS
AND %I0.1
ST %Q0.0
MRD
AND %I0.2
ST %Q0.1
MRD
AND %I0.3
ST
MPP
%Q0.2
AND %I0.4
ST %Q0.3
B
LD
MPS
%I0.0
AND %I0.1
MPS
AND( %I0.3
)
O R %M0
ST %Q0.0
MPP
ANDN %M1
ST %Q0.1
<
MRD
AND %I0.4
ST %Q0.2
<
MPP
AND %M10
ST %Q0.3
<
>
>
<
<
>
>
Note : These instructions cannot be used within an expression between parentheses.
___________________________________________________________________________
2/9
B
2.1-11 Special Ladder instructions OPEN and SHORT
As a special convenience to the Ladder programmer, there are two instructions that can be used during, debugging and troubleshooting. The OPEN and SHORT instructions provide a means to alter the logic of a rung by either "shorting" the continuity of the rung
(allow continuity to pass through the rung regardless of the result of the last logical operation), or by "opening" the continuity of the rung (discontinuing the continuity of the rung regardless of the result of the last logical operation).
In list, the OR and AND instructions accompanied by the immediate values of 1 and 0 are used to create the OPEN and SHORT instructions.
LD %I0.1
O R %Q1.5
ANDN %M3
AND 0
ST %Q0.1
LD %I0.9
O R
ST
1
%Q1.6
___________________________________________________________________________
2/10
Combinational and sequential instructions
2
2.2
Standard function blocks
2.2-1 Bit and word objects associated with standard function blocks
Function blocks set up bit objects and specific words.
• Bit objects :
These correspond to the block outputs.
They can be accessed by Boolean test instructions.
They can be addressed :
- either directly (for example, LD E) if they are wired to the block in reversible programming (see Section 2.2-2),
- or by specifying the block type (for example, LD %Ci.E),
Inputs can be accessed in the form of instructions.
Up/down counter block
• Word objects :
These correspond to :
- The block configuration parameters. These parameters can be accessed (for example, preset parameter) or not (for example, time base) by the program.
- The current values (for example, %Ci.V current count value).
List of function block bit and word objects which can be accessed by the program
Standard function blocks
Associated words and bits
Timer
%TMi (i=0 to 31)
Word
Up/down counter
Bit
Word
%Ci (i=0 to 15) Bit
Current value
Preset value
Timer output
Current value
Preset value
Underflow output (empty)
Preset output reached
Overflow output (full)
LIFO/FIFO register Word
%Ri (i= 0 to 3)
Bit
Drum controller Word
Access to register
Register output
Register output full
Register output empty
Current step number
Address Write access
%TMi.V
no
%TMi.P
yes
%TMi.Q
no
%Ci.V
%Ci.P
no yes
%Ci.E
%Ci.D
%Ci.F
no no no
%Ri.I
%Ri.O
%Ri.F
yes yes no
%Ri.E
no
%DRi.S
yes
See
Sect.
2.2-3
2.2-4
2.2-5
2.2-6
%DRi (i=0 to 3) Bit Last step equals current step %DRi.F
yes
___________________________________________________________________________
2/11
B
B
2.2-2 Programming principles
Standard function blocks can be programmed in two different ways :
• Using function block instructions (for example, BLK %TM2): This reversible method of programming for the Ladder language enables operations to be performed on the block in a single place in the program.
• Using specific instructions (for example, CU %Ci): This non-reversible method enables operations to be performed on the block's inputs in several places in the program (for example, line 100 CU %C1, line 174 CD %C1, line 209 LD %C1.D).
Principles of reversible programming of standard function blocks
This programming uses instructions BLK, OUT_BLK and END_BLK.
BLK indicates the start of the function block.
OUT_BLK is used to directly "wire" the block outputs.
END_BLK indicates the end of the block.
Example of reversible programming with wired outputs
BLK %C8
LDF %I1.1
R
LD %I1.2
AND %M0
CU
OUT_BLK
LD D
AND %M1
ST %Q0.4
END_BLK
Input processing
Output processing
Example of reversible programming without output wiring
BLK %C8
LDF %I1.1
R
LD %I1.2
AND %M0
CU
END_BLK
LD %C8.D
AND %M1
ST %Q0.4
Input processing
Output processing
Note :
Only test and input instructions on the relevant block can be placed between BLK and OUT_BLK instructions (or between BLK and END_BLK, when OUT_BLK is not programmed).
___________________________________________________________________________
2/12
Combinational and sequential instructions
2
2.2-3 Timer function blocks %TMi
Timer block
There are 3 types of timer :
• TON : this type of timer is used to control on-delay actions. This delay is programmable and can be modified via the terminal.
• TOF : this type of timer is used to control off-delay actions. This delay is programmable and can be modified by the terminal.
• TP : this type of timer is used to create a pulse of an exact duration. This duration is programmable and can be modified by the terminal.
B
Note : The larger the preset value, the greater the timer accuracy.
Characteristics
Timer number
Type
Time base
Current value
Preset value
Data Editor
Setting input
(or instruction)
Timer output
%TMi
TON
TOF
TP
TB
%TMi.V
%TMi.P
Y/N
IN
Q
0 to 31
• on-delay (by default)
• off-delay
• pulse (monostable)
1min (by default), 1s, 100ms, 10ms, 1ms (for
TM0 and TM1).
Word which increments from 0 to %TMi.P
when the timer is running. Can be read and tested but not written by the program (1).
0-%TMi.P-9999. Word which can be read, tested and written by the program. It is set to
9999 by default. The length or delay generated is equal to %TMi.P x TB.
Y : possibility of changing the preset value
%TMi.P in the Data editor.
N : no access in the Data editor.
The timer starts on a rising edge (type TON or TP) or a falling edge (type TOF).
Associated bit %TMi.Q is set to 1 depending on the function performed : TON, TOF or TP
(1) %TMi.V can be modified via the terminal in the Data editor.
___________________________________________________________________________
2/13
B
Using as an on-delay timer : type TON
The timer is started on a rising edge at input
IN (1) : the current value %TMi.V increases from 0 to %TMi.P by one unit for each pulse of the time base TB. Output bit %TMi.Q
changes to 1 when the current value reaches %TMi.P and then remains at 1 as long as a falling edge is not detected at input IN.
When a falling edge is detected at input IN
(2), the timer is stopped, even if the timer has not reached % TMi.P.
Using as an off-delay timer : type TOF
The current value %TMi.V is set to 0 on a rising edge at input IN (1) (even if the timer is still running). When the falling edge is detected on input IN, the timer is started.
The current value increases to %TMi.P by one unit on each pulse of the time base TB.
Output bit %TMi.Q changes to 1 when a rising edge is detected on input IN and the timer returns to 0 when the current value reaches %TMi.P.
Using as a pulse : type TP
The timer is started on a rising edge at input
IN (1) : the current value %TMi.V is set to 0 if the timer has not already started.
The current value increases from 0 to
%TMi.P by one unit for each pulse of the time base TB. Output bit %TMi.Q changes to 1 when the timer is started and returns to 0 when the current value reaches
%TMi.P.
This timer cannot be reset. Once %TMi.V
equals %TMi.P, and the input IN is at state
0, %TMi.V is set to 0.
(1) Or activation of instruction IN.
(2) Or deactivation of instruction IN.
___________________________________________________________________________
2/14
Combinational and sequential instructions
2
Programming and configuration
Timer function blocks are programmed in the same way irrespective of how they are to be used. The function TON, TOF, and TP is selected during configuration.
Reversible programming
BLK %TM1
LD %I0.1
IN
OUT_BLK
LD
ST
Q
%Q0.3
END_BLK
B
Configuration
The following parameters must be entered during configuration.
• Type : TON, TOF or TP
• TB : 1min, 1s, 100ms, 10ms or 1ms
• %TMi.P : 0 to 9999
• Adjust : Y or N
Non-reversible programming
LD
IN
LD
ST
%I0.1
%TM1
%TM1.Q
%Q0.3
Special cases
• Effect of a cold restart : (%S0=1)
- forces the current value to 0,
- sets output %TMi.Q to 0,
- the preset value is reset to the value defined during configuration.
• Effect of a warm restart : (%S1=1) has no effect on the current value of the timer, nor on the preset value. The current value does not change during a power outage.
• Effect of a PLC stop : stopping the PLC does not freeze the current value.
• Effect of a program jump : Jumping over a timer block does not freeze the timer. The timer will continue to increment until it reaches the preset value (%TMi.P). At that point, the done bit (%TMi.Q) assigned to output Q of the timer block changes state; however, the associated output wired directly to the block output is not activated and not scanned by the PLC.
• Testing of bit %TMi.Q (done bit) : it is advisable to test bit %TMi.Q only once in the program.
• Effect of master control relay instructions MCS/MCR : a timer block programmed between 2 MCS/MCR instructions is reset when the MCS instruction is active.
• Effect of modifying the preset %TMi.P : modifying the preset value via an instruction or by adjusting it only takes effect when the timer is next activated.
___________________________________________________________________________
2/15
B
Timers with 1ms time base (TSX 07 3• ••••)
The 1 ms time base is only available on %TM0 and %TM1 timers.
If the user so requires, he can use the four system words %SW76, %SW77, %SW78 and %SW79 as "hourglasses".
These four system words are decremented individually by the system every millisecond
if they have a positive value.
Multiple timing can be achieved by successive loading of one of these words or by testing the intermediate values.
If one of these four system words is less than 0, it will not be modified, a timer can thus be "frozen" by setting corresponding bit 15 to 1 then "unfrozen" by resetting it to 0.
Programming example :
LDR%I0.1
(launching the timer on rising edge of %I0.1)
[%SW76:=XXXX] (XXXX= required value)
LD %I0.2
ST %SW76:X15
(optional management of the freeze, input I0.2 freezes)
LD [%SW76=0] (timer end test)
ST %M0
...........
___________________________________________________________________________
2/16
Combinational and sequential instructions
2
2.2-4 Up/down counter function blocks %Ci
The up/down counter function block is used to up/down count events. These two operations can be simultaneous.
B in
Up/down counter block
Characteristics
Counter number
Current value
Preset value
Edit via terminal
%Ci
%Ci.V
%Ci.P
Y/N
0 to 15
Word incremented or decremented according to inputs (or instructions) CU and CD.
Can be read and tested but not written by the program (1).
0-%Ci.P-9999. Word can be read, tested and written (default value: 9999).
Y : possibility of modifying the preset value the Data editor. N : no access in the Data editor.
At state 1 : %Ci.V = 0.
Reset input (or instruction)
Set input
(or instruction)
Upcount input
(or instruction)
Downcount input
(or instruction)
Underflow output
R
S
CU
CD
At state 1: %Ci.V = %Ci.P.
Increments %Ci.V on a rising edge.
Decrements %Ci.V on a rising edge.
Preset output reached
Overflow output
E (Empty)
D (Done)
F (Full)
The associated bit %Ci.E=1, when downcounter %Ci.V changes from 0 to
9999 (set to 1 when %Ci.V reaches 9999, and reset to 0 if the counter continues to count down).
The associated bit %Ci.D=1, when
%Ci.V=%Ci.P.
The associated bit %Ci.F =1 when %Ci.V
changes from 9999 to 0 (set to 1 when
%Ci.V reaches 0, and reset to 0 if the counter continues to count up).
(1) %Ci.V can be modified via the terminal in the Data editor.
___________________________________________________________________________
2/17
B
Operation
• Upcount : when a rising edge appears at the upcounting input CU (or instruction CU is activated), the current value is incremented by one unit. When this value is equal to the preset value %Ci.P, the "preset reached" output bit %Ci.D assigned to output
D changes to state 1. Output bit %Ci.F (upcount overflow) changes to state 1 when
%Ci.V changes from 9999 to 0, and is reset to 0 if the counter continues to count up.
• Downcount : when a rising edge appears at the downcounting input CD (or instruction CD is activated), the current value %Ci.V is decremented by one unit.
Output bit %Ci.E (underflow) changes to state 1 when %Ci.V changes from 0 to 9999, and is reset to 0 if the counter continues to count down.
• Up/downcount : to use both the upcount and the downcount functions simultaneously
(or to activate instructions CD and CU), the two corresponding inputs CU and CD must be controlled. These two inputs are then scanned in succession. If they are both at
1, the current value remains unchanged.
• Reset : when this input is set to state 1 (or the instruction is activated), the current value
%Ci.V is forced to 0, outputs %Ci.E, %Ci.D and %Ci.F are at 0. The reset input has priority.
• Set : if input S is at state 1 (or instruction S is active) and the reset input is at state 0
(or instruction R is inactive), the current value %Ci.V takes the value of %Ci.P, and output %Ci.D is set to 1.
Special cases
• Effect of a cold restart : (%S0=1)
- The current value %Ci.V is set to zero.
- Output bits %Ci.E, %Ci.D and %Ci.F are set to zero.
- The preset value is initialized with the value defined during configuration.
• Effect of a warm restart (%S1=1), of a PLC stop : this has no effect on the current value of the counter (%Ci.V).
• Effect of modifying the preset %Ci.P : modifying the preset value via an instruction or by adjusting it takes effect when the block is processed by the application
(activation of one of the inputs).
___________________________________________________________________________
2/18
Combinational and sequential instructions
2
Configuration and programming
Example : Count a number of items up to 5000. Each pulse on input %I1.2 (when internal bit %M0 is at 1) increments the upcounter %C8 up to its final preset value (bit
%C8.D=1). The counter is reset by input %I1.1.
Configuration
The following parameters must be entered during configuration :
• %Ci.P, set to 5000 in this example
• Adjust : Y
B
Reversible programming
BLK %C8
LD %I1.1
R
LD %I1.2
AND %M0
CU
END_BLK
LD %C8.D
ST %Q0.0
Non-reversible programming
LD %I1.1
R %C8
LD %I1.2
AND %M0
CU %C8
LD %C8.D
ST %Q0.0
___________________________________________________________________________
2/19
B
2.2-5 LIFO/FIFO register function blocks %Ri
A register is a memory block which is used to store up to 16 words of 16 bits in two different ways :
• Queue (First In, First Out) known as FIFO.
• Stack (Last In, First Out) known as LIFO.
Input word
Register block
Characteristics
Register number
Type
%Ri
FIFO
LIFO
%Ri.I
Output word %Ri.O
Storage input
(or instruction)
Retrieval input
(or instruction)
Reset input
(or instruction)
I (In)
O (Out)
R (Reset)
Empty output
Full output
E (Empty)
F (Full)
0 to 3
Queue (default selection)
Stack
Register input word. Can be read, tested and written.
Register output word. Can be read, tested and written.
On a rising edge, stores the contents of word %Ri.I in the register.
On a rising edge, loads a data word into word
%Ri.O.
At state 1 initializes the register.
The associated bit %Ri.E indicates that the register is empty. Can be tested.
The associated bit %Ri.F indicates that the register is full. Can be tested.
___________________________________________________________________________
2/20
Combinational and sequential instructions
2
Operation
FIFO (First In, First Out)
The first data item entered is the first to be retrieved.
When a storage request is received (rising edge at input I or activation of instruction I), the contents of input word %Ri.I (which have already been loaded) are stored at the top of the queue
(Fig a).
When the queue is full (output F=1), no further storage is possible.
When a retrieval request is received (rising edge at input O or activation of instruction O) the data word lowest in the queue is loaded into output word %Ri.O and the contents of the register are moved down one place in the queue (Fig b).
When the register is empty (output E=1) no further retrieval is possible. Output word %Ri.O
does not change and retains its value.
The queue can be reset at any time (state 1 at input R or activation of instruction R).
Example :
Storage of the contents of %Ri.I at the top of the queue.
% R i . I
(a)
Retrieval of the first data item which is then loaded into %Ri.O
(b)
%Ri.O
B
LIFO (Last In, First Out)
The last data item entered is the first to be retrieved.
When a storage request is received (rising edge at the input or activation of instruction I), the contents of input word %Ri.I (which have already been loaded) are stored at the top of the stack (Fig c).
When the stack is full (output F at 1), no further storage is possible.
When a retrieval request is received (rising edge at input O or activation of instruction O) the highest data word (last word to be entered) is loaded into word %Ri.O (Fig d).
When the register is empty (output E=1), no further retrieval is possible. Output word %Ri.O
does not change and retains its last value. The stack can be reset at any time (state 1 at input R or activation of instruction R). The element indicated by the pointer is then the highest in the
Example :
Storage of the contents of %Ri.I at the top of the stack.
%Ri.I
(c)
Retrieval of the data word highest in the stack.
%Ri.O
(d)
2/21
B
Special cases
• Effect of a cold restart : (%S0=1) initializes the contents of the register Output bit
%Ri.E, assigned to output E, to 1 and resets %Ri.I and %Ri.O words to 0.
• Effect of a warm restart : (%S1=1) has no effect on the contents of the register, nor on the state of its output bits.
Programming and configuration
The programming example shows word
%MW34 being loaded into %R2.I at the storage request %I0.2, if register R2 is not full (%R2.F=0). The storage request in the register is made by %M1. The retrieval request is made by input %I0.3 and %R2.O
is loaded into %MW20 if the register is not empty (%R2.E=0).
Configuration
The only parameter which must be entered during configuration is the type of register :
FIFO (default) or LIFO.
Reversible program
BLK %R2
LD %M1
I
LD %I0.3
O
END_BLK
LD %I0.3
ANDN %R2.E
[%MW20:=%R2.O]
LD %I0.2
ANDN %R2.F
[%R2.I:=%MW34]
ST %M1
Non-reversible program
LD %M1
I %R2
LD %I0.3
O %R2
ANDN %R2.E
[%MW20:=%R2.O]
LD %I0.2
ANDN %R2.F
[%R2.I:=%MW34]
ST %M1
___________________________________________________________________________
2/22
Combinational and sequential instructions
2
2.2-6 Drum controller function block %DRi
Drum controller block
The drum controller operates on a similar principle to an electromechanical drum controller, which changes step according to external events. On each step, the high point of a cam gives a command which is executed by the control system. In the case of a drum controller, these high points are symbolized by state 1 for each step and are assigned to output bits %Qi.j or internal bits %Mi, known as control bits.
B
Characteristics
Number
Current step number
%DRi
%DRi.S
Number of steps
Return to step 0 input (or instruction)
Advance input
(or instruction)
R (RESET)
U (UP)
Output
Control bits
F (FULL)
0 to 3
0-%DRi.S-7. Word which can be read and tested.
Can only be written in the program with a decimal immediate value.
1 to 8 (default)
At state 1, sets the drum controller to step
0.
On a rising edge, causes the drum controller to advance by one step and updates the control bits.
Indicates that the current step equals the last step defined. The associated bit
%DRi.F can be tested (for example,
%DRi.F=1 if %DRi.S= number of steps configured - 1).
Outputs or internal bits associated with the step (16 control bits) and defined in the Configuration editor.
___________________________________________________________________________
2/23
B
Operation
The drum controller comprises :
• A matrix of constant data (the cams) organized in 8 steps (0 to 7) and 16 data bits (state of the step) arranged in columns numbered 0 to F.
• A list of control bits (1 per column) corresponding either to outputs %Q0.i or %Q1.i, or to internal bits %Mi. During the current step, the control bits take on the binary states defined for this step.
The table below summarizes the main characteristics of the drum controller.
Column
Control bits
Step 0
Step 1
Step 5
Step 6
Step 7
In the example above, step 5 is the current step, control bits %Q0.1; %Q0.3 and %Q1.5
are set to state 1; control bits %Q0.6; %Q0.5 and %Q1.0 are set to state 0.
The current step number is incremented on each rising edge at input U (or on activation of instruction U). The current step can be modified by the program.
Operating diagram
Input
Input
Step No.
Output
Special cases
• Effect of a cold restart : (%S0=1) resets the drum controller to step 0 (updating the control bits).
• Effect of a warm restart : (%S1=1) updates the control bits, after the current step.
• Effect of a program jump : If the drum controller is not scanned, the control bits are not reset to 0.
• Updating the control bits : only occurs when there is a change of step or in the case of a warm or cold restart.
• Effect of master control relay instructions MCS/MCR : Having a drum controller between 2 MCS/MCR instructions means that the control bits are reset to 0 if the
Boolean result of the instruction preceding the MCS instruction is 0.
___________________________________________________________________________
2/24
Combinational and sequential instructions
2
Programming and configuration
In this example, the first 6 outputs %Q0.0 to %Q0.5 are activated in succession, each time input %I0.1 is set to 1.
Input I0.0 resets the outputs to 0.
Reversible programming
BLK %DR1
LD %I0.0
R
LD %I0.1
U
OUT_BLK
LD F
ST %Q0.8
END_BLK
B
Configuration
The following information is defined during configuration :
• The number of steps : 6
• The output states (control bits) for each drum controller step.
Q0. 1: 2: 3: 4: 5:
Step 1 : 0 0 0 0 0
Step 2 : 1 0 0 0 0
Step 3 : 0 1 0 0 0
Step 4 : 0 0 1 0 0
Step 5 : 0 0 0 1 0
Step 6 : 0 0 0 0 1
• Assignment of the control bits
1 : %Q0.0
2 : %Q0.2
3 : %Q0.4
4 : %Q0.1
5 : %Q0.3
6 : %Q0.5
Non-reversible programming
LD
R
LD
U
LD
ST
%I0.0
%DR1
%I0.1
%DR1
%DR1.F
%Q0.8
___________________________________________________________________________
2/25
B
2.3
Grafcet instructions
2.3-1 Description
Grafcet instructions in PL7 language offer a simple method of translating a control sequence (Grafcet chart).
The PL7 language comprises a maximum of 62 steps, including the initial step(s). The number of steps active at any one time is limited only by the total number of steps.
The table below lists all the instructions and objects required to program a Grafcet chart.
Graphic representation
Transcription in PL7 language
Role
Initial step
Transition
Step
=*= i
# i
-*- i
#
#Di
=*= POST
%Xi
Start the initial step (1)
Activate step i after deactivating the current step
Start step i and validate the associated transition (1)
Deactivate the current step without activating any other steps
Deactivate step i and the current step
Start post-processing and end sequential processing
Bit associated with step i, can be tested and written (max. no. of steps : 62).
LD %Xi,
AND %Xi, ANDN %Xi
OR %Xi,
XOR %Xi, XORN %Xi
S %Xi
R %Xi
LDN %Xi, Test the activity of step i
ORN %Xi
Activate step i
Deactivate step i
(1) The first step =*=i or -*-i written indicates the start of sequential processing and thus the end of preprocessing.
___________________________________________________________________________
2/26
Combinational and sequential instructions
2
Examples
Linear sequence
=*=
LD %I0.1
# 2
-*- 2
LD %I0.2
# 3
1
Alternative sequence
-*- 4
LD %I0.3
# 5
LD %I0.4
# 6
-*- 5
LD %I0.5
# 7
-*- 6
LD %I0.6
# 7
Simultaneous sequences
-*- 8
LD %I0.7
# 9
# 10
-*- 9
LD %I0.8
# 11
-*- 10
LD %I0.9
# 12
Note : -*- 11
For a Grafcet Chart to be operational, at least one active step must be declared using the =*=i instruction (initial step) or the chart should be prepositioned during preprocessing using system bit
%S23 and the instructions S %Xi.
See example of prepositioning a chart in
LD %M0
AND %X12
#D 12
#
-*- 12
LD %M0
AND %X11
#D 11
#
13
13 appendix A.10 part G.
___________________________________________________________________________
2/27
B
B
2.3-2 Program structure
A PL7 Grafcet program has 3 parts, each of which has a specific role.
Processing Example
Preprocessing
This comprises a series of instructions for processing :
• power returns
• faults
• changes of operating mode
• prepositioning Grafcet steps
• input logic
000 LDN
001 S
002 ST
003 LDR
004 S
Preprocessing ends with the first =*= or -*- instruction which occurs.
%I0.6
%S22
%M0
%I0.6
%S21
Sequential processing
This comprises the chart
(instructions representing the chart) :
• steps
• actions associated with steps (see Appendix A.11
Part G)
• transitions
• transition conditions
Sequential processing ends with execution of the =*=POST instruction
005 =*= 1
006 LD %I0.2
007 ANDN %I0.3
008 #
009 LD
2
%I0.3
010 ANDN %I0.2
011 # 3
012 -*-
013 LD
014 #
015 -*-
016 LD
017 #
2
%I0.4
1
3
%I0.5
1
Post-processing
This comprises a series of instructions for processing :
• commands from the sequential processing for controlling the outputs
• safety interlocks specific to the outputs.
018 =*= POST
019 LD %X1
020 ST
021 LD
%Q0.1
%X2
022 ST
023 LD
%Q0.2
%X3
024 OR( %M1
025 ANDN %I0.2
026 AND %I0.7
027 )
028 ST %Q0.3
Note :
The scan cycle is that defined in Part A, Section 1.3. In sequential processing, only active steps at the start of the scan and their associated instructions are executed.
___________________________________________________________________________
2/28
Combinational and sequential instructions
2
2.4
Program instructions
2.4-1 Program end instructions END, ENDC, ENDCN
The end of the execution of a program scan is defined using the instructions END, ENDC and ENDCN :
END : unconditional end of program
ENDC : end of program if Boolean result of preceding test instruction is 1
ENDCN : end of program if Boolean result of preceding test instruction is 0.
By default (normal mode) when the end of program is activated, the outputs are updated and the next scan is started.
If scanning is periodic, when the end of period is reached the outputs are updated and the next scan is started.
Example :
LD %M1
ST %Q0.1
LD %M2
ST %Q0.2
.....................
END
B
LD %M1
ST %Q0.1
LD %M2
ST %Q0.2
.....................
LD %I0.2
ENDC
LD %M2
ST %Q0.2
....................
END
If %I0.2 =1, end of program scanning.
If %I0.2 =0, continues program scanning until new END instruction.
2.4-2 NOP Instruction
The NOP instruction does not perform any operation. It is used for "reserving" lines in a program which allow the user to insert instructions later without modifying the line numbers.
___________________________________________________________________________
2/29
B
2.4-3 Jump instructions JMP, JMPC, JMPCN to a label %Li:
Instructions JMP, JMPC and JMPCN cause the execution to be interrupted immediately and the program to be continued from the line after the program line containing label
%Li (i = 0 to 15).
JMP : unconditional program jump
JMPC : program jump if Boolean result of preceding logic is 1
JMPCN : program jump if Boolean result of preceding logic is 0.
Examples :
000 LD %M15
001 JMPC %L8
002 LD [%MW24>%MW12]
003 ST %M15
004 JMP %L12
005 %L8:
006 LD %M12
<
007 AND %M13
008 ST %M2
009 JMPCN %L12
010 OR %M11
011 S
012 %L12:
%Q0.0
013 LD %I0.0
.......................................
<
Jump to label %L8 if %M15 is at 1
Unconditional jump to label
%L12 :
Jump to label %L12 if %M2 is at 0
Note :
• These instructions are not permitted between parentheses, and they must not be placed between the instructions AND(, OR(, and a close parenthesis instruction ")".
• The label can only be placed before a LD, LDN, LDR, LDF or BLK instruction.
• The label number of label %Li must be defined only once in a program.
• The program jump is performed to a line of programming which is downstream or upstream. When the jump is upstream, attention must be paid to the program scan time. Extended scan time can cause the watchdog timer to expire.
___________________________________________________________________________
2/30
Combinational and sequential instructions
2
2.4-4 Subroutine instructions SRn, SRn:, RET
The SRn instruction calls the subroutine referenced by label SRn: if the result of the preceding Boolean instruction is 1.
The RET instruction placed at the end of the subroutine commands the return to the main program.
The subroutine is referenced by a label SRn: with n=0 to 15.
Example :
000 LD %M15
001 AND %M5
002 ST
003 LD
004 SR8
005 LD
%Q0.0
[%MW24>%MW12]
%I0.4
006 AND %M13
007 _
<
008 _
009 _
010 END
<
011 SR8:
012 LD 1
013
014
IN
LD
%TM0
%TM0.Q
%M10 015 ST
016 RET
.......................................
Note :
• A subroutine should not call up another subroutine.
• This instruction is not permitted between parentheses, and thus it must not be placed between the instructions AND(, OR(, and a close parenthesis instruction ")".
• The label can only be placed before a LD or BLK instruction marking the start of a Boolean equation
(or rung).
• Calling the subroutine must not be followed by an assignment (e.g. output or transfer) instruction, example :
LD %I0.0
SR0
ST %Q0.0
B
LD %I0.0
ST %Q0.0
SR0
___________________________________________________________________________
2/31
B
2.4-5 Master control relay instructions MCR and MCS
When the Boolean result of the instruction preceding the MCS instruction is 0, the execution of the program lines following this instruction are modified as shown in the table below until the MCR instruction is (unconditional) executed.
Instructions / blocks
ST, STN
S, R
SRi, JMP, JMPC, JMPCN
%TMi
%DRi
%FC
% PWM, %PLS
Other function blocks
Operation blocks
Behavior
Associated object set to 0
Instructions not executed
Not executed
Reinitialized
Control bits set to 0
Counter stopped and threshold outputs reset to 0
Generation of output signals stopped
Not executed (maintain their current state)
Not executed
Example :
...............
002 LD %I0.1
003 MCS
004 LD %M1
005 ST %Q0.1
006 LD %l0.2
007 S %Q0.2
007 MCR
...............
When %I0.1 is at 0, the MCS instruction is activated, %Q0.1 is forced to 0, and output
%Q0.2 is maintained.
It is possible to use several MCS instructions for a single MCR instruction. All the MCS instructions are deactivated by a single MCR instruction.
When %I0.1 is at 0, sequences 1 and 2 are modified, sequence 3 is executed normally.
When %I0.1 is at 1 and %I0.2 is at 0, sequence
2 is modified, and sequences 1 and 3 are executed normally.
If no MCR instruction is programmed after an
MCS instruction, the MCS instruction is effective until the END instruction or the end of the program.
Important
Sequence 1
Sequence 2
Sequence 3
Do not use MCS and MCR instructions in subroutines, transition conditions or Grafcet actions.
___________________________________________________________________________
2/32
3 Numerical and special instructions
3.1
Numerical processing
3.1-1 Definition of word objects
Word objects are addressed in the form of words of 16 bits, which are stored in the data memory, and which can contain an integer value between -32768 and 32767 (except for the fast counter which is between 0 and 65535).
B
Immediate values
These are integer values of the same format as the 16-bit words, which enable values to be assigned to these words. They are stored in the program memory and contain a value between -32768 and 32767.
Word formats
The contents of the words or values are stored in the user memory in 16-bit binary code
(two's complement) using the following convention :
Bit position
Bit state
Bit value
:
In signed binary notation, bit 15 is allocated by convention to the sign of the coded value
• Bit 15 at 0 : the content of the word is a positive value.
• Bit 15 at 1 : the content of the word is a negative value (negative values are expressed in two's complement logic).
Words and immediate values can be entered or retrieved in the following format :
• Decimal
• Hexadecimal
1579 (max : 32767, min :-32768)
16#A536 (max : 16#FFFF, min : 16#0000) alternate syntax : #A536.
%MW0 Internal words
Internal words are used to store values during the operation.
They are stored in the data memory.
Words %MW0 to %MW255 are read or written to directly by the program. They are used as working words.
%MW255
16 bits
___________________________________________________________________________
3/1
B
Constant words
Constant words store constant values or alphanumeric messages. Their contents can only be written or modified by the terminal (in the CONFIGURATION editor).
Constant words %KW0 - %KW63 have read-only access by the program.
%KW0
%KW63
16 bits
I/O exchange words
I/O exchange words %IW/QW are assigned to PLCs connected by extension cable.
They are used for exchanges between PLCs (see Section 3.5).
System words
These 16-bit words have several functions. They provide access to data coming directly from the PLC by reading %SWi words (for example, potentiometers). They are used to perform operations on the application (for example, adjusting the schedule blocks).
The role of each of these words is explained in Section 6.
Bit objects extracted from words
It is possible to extract one of the 16 bits from some words. The position of the extracted bit separated by a colon is added to the word address.
Syntax : % Word object : Xk where k = 0 to 15 position of the bit in the object word.
Example : %MW5:x6 : bit position 6 of internal word %MW5.
List of word operands
Maximum Write number access
No
See
Sect.
Type Address
(or value)
Immediate values
• base 10
• base 16
Internal words
Constant words
System words example : 2103 example : 16#AF0D
% M W i
% K W i
% S W i
Function block words
%TMi.P %Ci.P etc.
Exchange words
Input words
Output words
%IWi.j
%QWi.j
Bits extracted from words
• internal %MWi:Xk
• system
• constant
• input
• output
% S W i : X k
% K W i : X k
%IWi.j:Xk
%QWi.j:Xk
8
8
256
64
128
256 x 16
128 x 16
64 x 16
8 x 16
8 x 16
Y e s
No (1)
Depends on i
No
Y e s
Y e s
Depends on i
No
No
Y e s
_
_
5.2
2.2-1
3.3
3.5
(1) constant words are entered in configuration mode.
___________________________________________________________________________
3/2
Numerical and special instructions
3
3.1-2 Structured objects
Bit string
Bit strings are series of adjacent object bits of the same type and of a defined length :
L.
Example of bit strings :
%M8 %M9 %M10 %M11 %M12 %M13
%M8:6 (1)
B
Type
Discrete input bits
Discrete output bits
System bits
Grafcet Step bits
Internal bits
Address
%I0:L or %I1:L
%Q0:L or %Q1:L
%Si:L with i multiple of 8
%Xi:L with i multiple of 8
%Mi:L with i multiple of 8
Maximum size
0<L<17
0<L<17
0<L<17 and i+L-128
0<L<17 and i+L-63
0<L<17 and i+L-128
Write access
No
Yes
Depending on i
Yes (by program)
Yes
Bit strings can be used with the assignment instruction := (see assignment instruction,
Section 3.1-4).
Word tables
Word tables are series of adjacent words of the same type and of a defined length : L.
Example of word tables :
%KW10 16 bits
%KW10:7
%KW16
Type
Internal words
Constant words
System words
Address
%MWi:L
%KWi:L
%SWi:L
Maximum size
0<L<256 and i+L-256
0<L and i+L-64
0<L and i+L-128
Write access
Yes
No
Depending on i
Word tables can be used with the assignment instruction := (see assignment instruction,
Section 3.1-4).
(1) %M8:6 is acceptable (8 is a multiple of 8)
%M10:16 is unacceptable (10 is not a multiple of 8)
___________________________________________________________________________
3/3
B
Indexed words
• Direct addressing
The addressing of an object is said to be direct when the address of the objects is fixed and defined when the program is written.
Example : %M26 (internal bit with the address 26)
• Indexed addressing
In indexed addressing, an index is added to the direct address of an object : the content of the index is added to the object address. The index is defined by an internal word
%MWi. The number of "index words" is unlimited.
Example : %MW108[%MW2] : word with direct address 108 + contents of word
%MW2.
If word %MW2 has a value of 12, writing to %MW108[%MW2] is equivalent to writing to %MW120.
Type
Internal words
Constant words
Address
%MWi[%MWj]
%KWi[%MWj]
Maximum size
0-i+%MWj<256
0-i+%MWj<64
Write access
Yes
No
Indexed words can be used with the assignment instruction := (see assignment instruction, Section 3.1-4) and in comparison instructions (see comparison instructions Section 3.1-5).
This type of addressing enables series of objects of the same type (internal words, constant words, etc) to be scanned in succession, by modifying the content of the index word via the program.
• Index overflow, system bit %S20
There is an overflow of the index when the address of an indexed object exceeds the limits of the memory zone containing the same type of object, that is to say when :
• The object address + the content of the index is less than 0,
• The object address + the content of the index is greater than 255 (for words %MWi) or 63 (for words %KWi).
In the event of an index overflow, the system sets system bit %S20 to 1 and the object is assigned an index value of 0.
Note : The user is responsible for monitoring any overflow : bit %S20 must be read by the user program for possible processing. The user must see that it is reset to 0.
%S20 (initial state = 0) :
• On index overflow : set to 1 by the system.
• Acknowledgment of overflow : set to 0 by the user, after modifying the index.
___________________________________________________________________________
3/4
Numerical and special instructions
3
3.1-3 Introduction to numerical instructions
Numerical instructions generally apply to 16-bit words (see Section 3.1-1). They are written between square brackets. If the result of the preceding logical operation was true (the Boolean accumulator = 1), the numerical instruction is executed. If the result of the preceding logical operation was false (the Boolean accumulator = 0), the numerical instruction is not executed and the operand remains unchanged.
Note : Numerical instructions are displayed in 2 or 3 lines on an FTX117 terminal.
B
3.1-4 Assignment instructions
These are used to load operand Op2 into operand Op1
Syntax : [Op1:=Op2] <=> Op2->Op1
The following assignment operations can be performed :
• On bit strings
• On words
• On word tables
Assignment of bit strings (see bit string object in Section 3.1-2)
Operations can be performed on the following bit strings : bit string -> bit string (ex 1) bit string -> word (ex 2) word -> bit string (ex 3) immediate value -> bit string
Examples
LD 1
[%Q0:8:= %M64:12]
LD %I0.2
[%MW100:= %I0:16 ]
LDR %I0.3
[%M104:16:=%KW0]
(ex 1)
(ex 2)
(ex 3)
Usage rules
• For bit string -> word assignment : the bits in the string are transferred to the word starting on the right (first bit in the string to bit 0 in the word), and the word bits which are not involved in the transfer (length<16) are set to 0.
• For word -> bit string assignment : the word bits are transferred from the right (word bit 0 to the first bit in the string).
___________________________________________________________________________
3/5
B
Syntax
Operator
:=
Syntax
[Op1: = Op2 ]
Operand 1 (Op1) Operand 2 (Op2 )
%MWi,%QWi, %SWi Immediate value, %MWi,
%MWi[MWi], %KWi,%IW,%QW,%SWi,
Operand 1 (Op1) assumes %Mi:L,%Qi:L,%Si:L, %BLK.x,%MWi[MWi], the value of operand 2 (Op2) %Xi:L %KWi[MWi], %Mi:L,%Qi:L,
%Si:L,%Xi:L, %Ii:L
Note : The abbreviation %BLK.x (e.g. %C0.P) is used to describe any function block word.
Assignment of words
Assignment operations can be performed on the following words : word -> word (ex 1) indexed word -> word word -> indexed word indexed word -> indexed word (ex 2) immediate value -> word (ex 3) bit string -> word immediate value -> indexed word word -> bit string
Examples :
LD 1
[%SW112 := %MW100] (ex 1)
LD %I0.2
[%MW0[%MW10] :=
%KW0[%MW20] ]
LDR %I0.3
[%MW10:=100]
(ex 2)
(ex 3)
Syntax
Operator
:=
Syntax Operand 1 (Op1) Operand 2 (Op2 )
[Op1: = Op2 ] %MWi,%QWi, %SWi Immediate value, %MWi,
%MWi[MWi], %KWi, %IW, %QW, %SWi,
Operand 1 (Op1) assumes %Mi:L,%Qi:L,%Si:L, %BLK.x, %MWi[MWi], the value of operand 2 (Op2) %Xi:L %KWi[MWi], %Mi:L,%Qi:L,
%Si:L,%Xi:L,%Ii:L
Notes :
• The abbreviation %BLK.x (e.g. R3.I) is used to describe any function block word.
• For bit strings %Mi:L, %Si:L and %Xi:L, the base address of the first of the bit string must be a multiple of 8 (0, 8, 16, …, 96, …).
___________________________________________________________________________
3/6
Numerical and special instructions
3
Assignment of word tables (see word table object in Section 3.1-2)
Assignment operations can be performed on the following word tables : immediate value -> word table (ex 1) word -> word table (ex 2) word table -> word table (ex 3)
Examples
LD 1
[%MW0 :10:= 100]
LD %I0.2
[%MW0:10 := %MW11]
LDR %I0.3
[%MW10:20=%KW30:20]
(ex 1)
(ex 2)
(ex 3)
B
Syntax
Operator
:=
Syntax
[Op1: = Op2 ]
Operand 1 (Op1) assumes the value of operand 2 (Op2)
Operand 1 (Op1)
%MWi:L,%SWi:L
Operand 2 (Op2 )
%MWi:L, %KWi:L, %SWi:L lmmediate value, %MWi,
%KWi, %IW, %QW, %SWi,
%BLK.x
___________________________________________________________________________
3/7
B
3.1-5 Comparison instructions
Comparison instructions are used to compare two operands.
> : test if operand 1 is greater than operand 2.
>= : test if operand 1 is greater than or equal to operand 2.
< : test if operand 1 is less than operand 2.
<= : test if operand 1 is less than or equal to operand 2.
= : test if operand 1 is equal to operand 2.
<> : test if operand 1 is different from operand 2.
Structure
The comparison is executed inside square brackets following instructions LD, AND and
OR. The result is 1 when the comparison requested is true.
LD [%MW10 > 100]
ST %Q0.3
LD %M0
AND [%MW20 < %KW35]
ST %Q0.2
LD %I0.2
OR [%MW30 >= %MW40]
ST %Q0.4
Syntax
Operator
>,>=,<,<=
=, <>
Syntax
LD[ Op1 Operator Op2]
AND[ Op1 Operator Op2]
OR[Op1 Operator Op2]
Operand 1 (Op1)
%MWi,%KWi,%IW,
Operand 2 (Op2)
Immediate value, %MWi,
%QWi,%SWi,%BLK.x
%KWi,%IW,%QW,%SWi,
%BLK.x,%MWi[%MWi],
%KWi[%MWi]
Note
Comparison instructions can be used within parentheses.
Example :
LD %M0
AND( [%MW20>10]
OR %I0.0
)
ST %Q0.1
___________________________________________________________________________
3/8
Numerical and special instructions
3
3.1-6 Arithmetic instructions
These instructions are used to perform arithmetic operations between two operands or on one operand.
+ : add two operands
: subtract two operands
* : multiply two operands
/ : divide two operands
REM
DEC
: remainder of division of the two operands
SQRT : square root of an operand
INC : increment an operand
: decrement an operand
Structure
Arithmetic operations are performed as follows :
LD %M0
[%MW0 := %MW10 + 100]
LD %I0.2
[%MW0 := SQRT(%MW10) ]
LDR %I0.3
[INC %MW100]
Syntax
This depends on the operators used : see the table below.
Operator Syntax Operand 1 (Op1) Operands 2 and 3 (Op2 & 3)
+,-,*,/,REM (1) [Op1: = Op 2 Operator Op3] %MWi,%QWi, %SWi Immed.value (2),%MWi,%KWi,
SQRT
INC, DEC
[Op1: = SQRT(Op2)]
[Operator Op1]
%IW,%QW,%SWi,%BLK.x
Rules for use
• Addition : Overflow during operation
If the result exceeds the limits of -32768 or +32767, bit %S18 (overflow) is set to 1. The result is then, in itself, not correct (see next page). The user program manages bit %S18.
Example :
LD %M0
[%MW0 := %MW1+ %MW2]
LDN %S18
[%MW10 := %MW0 ]
LD %S18
[%MW10 := 32767 ]
R %S18
If %MW1 =23241 and %MW2=21853, the real result (45094) cannot be expressed in one 16-bit word, bit %S18 is set to 1 and the result obtained (-20442) is incorrect. In this example when the result is greater than 32767, its value is fixed at 32767.
(1) with TSX 07s V2.2 or lower, the result (Op1) of division (/) or of the remainder (REM) is not significant when the contents of operand 3 (Op3) is greater then 255.
(2) with SQRT, Op2 cannot be an immediate value.
___________________________________________________________________________
3/9
B
B
Absolute overflow of the result (unsigned arithmetic) :
During certain calculations, it may be necessary to interpret an operand in unsigned arithmetic (bit 15 then represents the value 32768). The maximum value for an operand is 65535. Adding 2 absolute values (unsigned) whose result is greater than 65535 causes an overflow. This is signaled by system bit %S17 (carry) changing to 1, which represents the value 65536.
Example 1 : [%MW2:=%MW0 + %MW1] where %MW0 =65086, %MW1=65333
Word %MW2 contains the number 64883. Bit %S17 is set to 1 and represents the value
65536. The unsigned arithmetic result is then equal to :
65536 + 64883 = 130419.
Example 2 : [%MW2:=%MW0 + %MW1] where %MW0 =45736 (that is, a signed value of -19800), %MW1=38336 (that is, a signed value of 27200).
The two system bits %S17 and %S18 are set to 1. The signed arithmetic result (+18536) is incorrect. In unsigned arithmetic, the result (18536 + the value of %S17, that is 84072) is correct.
• Subtraction :
Negative result
If the result of a subtraction is less than 0, system bit %S17 is set to 1.
• Multiplication :
Overflow during operation
If the result exceeds the capacity of the result word, bit %S18 (overflow) is set to 1 and the result is not significant.
• Division/Remainder :
Division by 0
If the divider is 0, the division is impossible and system bit %S18 is set to 1. The result is then incorrect.
Overflow during operation
If the division quotient exceeds the capacity of the result word, bit %S18 is set to 1.
• Square root extraction :
Square root extraction is only performed on positive values. Thus, the result is always positive. If the square root operand is negative, system bit %S18 is set to 1 and the result is incorrect.
Note :
The user program is responsible for managing system bits %S17 and %S18. These are set to
1 by the PLC and must be reset by the program so that they can be reused (see previous page for example).
___________________________________________________________________________
3/10
Numerical and special instructions
3
3.1-7 Logic instructions
The associated instructions are used to perform a logic operation between two word operands or on one word operand.
AND : AND (bit-wise) between two operands
OR : Logic OR (bit-wise) between two operands
XOR : Exclusive OR (bit-wise) between two operands
NOT : Logic complement (bit-wise) of an operand
B
Structure
Logic operations are performed as follows :
LD %M0
[%MW0 := %MW10 AND 16#FF00]
LD 1
[%MW0 := %KW5 OR %MW10]
LD %I0.3
[%MW102:= NOT (%MW100)]
Syntax
This depends on the operators used : see table below.
Operator Syntax Operand 1 (Op1) Operands 2 and 3 (Op2 & 3)
AND, OR, XOR [Op1: = Op2 Operator Op3] %MWi,%QWi, %SWi Immed. val. (1), %MWi,%KWi,
NOT [NOT (Op2)] %IW,%QW,%SWi, %BLK.x
Example : [%MW15:=%MW32 AND %MW12]
(1) with NOT, Op2 cannot be an immediate value.
___________________________________________________________________________
3/11
B
3.1-8 Shift instructions
Shift instructions consists of moving bits of an operand a certain number of positions to the right or to the left.
There are two types of shift operation :
• Logic shift :
- SHL(op2,i) logic shift of i positions to the left.
- SHR(op2,i) logic shift of i positions to the right.
Structure
Logic operations are performed as follows :
• Rotate shift :
- ROL(op2,i) rotate shift of i positions to the left.
- ROR(op2,i) rotate shift of i positions to the right.
As the operand to be shifted is a single length operand, the variable i must be between 1 and 16.
The state of the last output bit is stored in bit %S17.
LDR %I0.1
[%MW0 := SHL(%MW10,5)]
LDR %I0.2
[%MW10 := ROR(%KW9,8)]
Syntax
This depends on the operators used : see the table below.
Operator
SHL, SHR
ROL, ROR
Syntax
[Op1: = Operator(Op2,i)]
Operand 1 (Op1)
%MWi,%QWi, %SWi
Operand 2 (Op2)
%MWi,%KWi,
%IW,%QW,%SWi, %BLK.x
___________________________________________________________________________
3/12
Numerical and special instructions
3
3.1-9 Conversion instructions
There are two types of conversion instruction :
• BTI : BCD --> Binary conversion
• ITB : Binary --> BCD conversion
Review of the BCD code :
The BCD code (Binary Coded Decimal) represents a decimal digit (0 to 9) by coding
4 bits. A 16-bit word object can thus contain a number expressed in four digits
(0 - N - 9999).
During a conversion, if the value isn't a BCD one, the system bit %S18 is placed at 1.
This bit must be tested and reset to 0 by the user program.
B
Decimal
BCD
0 1 2 3 4 5 6 7 8
0000 0001 0010 0011 0100 0101 0110 0111 1000
9
1001
Example :
• Word %MW5 expresses the BCD value "2450" which corresponds to the binary value : 0010 0100 0101 0000
• Word %MW12 expresses the decimal value "2450" which corresponds to the binary value : 0000 1001 1001 0010
Word %MW5 is converted to word %MW12 by using instruction BTI.
Word %MW12 is converted to word %MW5 by using instruction ITB.
Structure
Conversion operations are performed as follows :
LD %M0
[%MW0 := BTI (%MW10)]
LD %I0.2
[%MW10 := ITB (%KW9)]
Syntax
This depends on the operators used : see the table below.
Operator Syntax Operand 1 (Op1)
BTI, ITB [Op1: = Operator (Op2)]
Operand 2 (Op2)
%MWi,%QWi, %SWi %MWi,%KWi, %IW,%QW,
%SWi, %BLK.x
Application examples
The BTI instruction is used to process a setpoint value at PLC inputs via BCD encoded thumbwheels.
The ITB instruction is used to display numerical values (for example, the result of a calculation, the current value of a function block) on BCD coded displays.
___________________________________________________________________________
3/13
B
3.2
Potentiometers
Review from Part A, Section 1.8 :
"Base PLC" TSX Nano PLCs have on the front panel :
• One potentiometer for TSX Nano PLCs with 10, 14 and 20 I/O.
• Two potentiometers for TSX Nano PLCs with 16 and 24 I/O.
Programming
The numerical values from 0 to 255 corresponding to the analog values provided by these potentiometers are contained in the following two system words :
• %SW112 for the first potentiometer (leftmost, potentiometer no.0)
• %SW113 for the second potentiometer (rightmost, potentiometer no.1)
These words can be used in arithmetic operations. They can be used for any type of adjustment, for example, presetting a time-delay or a counter, adjusting the frequency of the pulse generator or machine preheating time.
Example :
Adjusting the duration of a time-delay from 5 to 10s using potentiometer no.0.
For this adjustment practically the entire adjustment range of the potentiometer from 0 to 250 is used.
The following parameters are selected at configuration for the time-delay block
%TM0 :
• Type TON
• Time base TB : 10ms
The preset value of the time-delay is calculated from the adjustment value of the potentiometer using the following equation %TM0.P :=2*%SW112+500.
LD 1
[%MW0:=2*%SW112]
[%TM0.P:=%MW0+500]
BLK %TM0
LD
IN
%I0.0
OUT_BLK
LD Q
ST %Q0.0
END_BLK
___________________________________________________________________________
3/14
Numerical and special instructions
3
3.3
Analog channel (TSX 07 32/33 •• ••)
TSX Nano TSX 07 32/33 •• •• PLCs include a non-isolated 0/10 V analog channel.
Principle
An analog to digital converter converts the input voltage 0-10 V to a digital value from
0 to 255 which is stored in system word %SW112.
Input voltage
0 V
40 mV
•
80 mV
•
9.96 V
10 V
10.2 V
%SW112
0
1
•
2
•
249
250
255
The digital value 255 is used to detect whether the maximum value of the input signal has been exceeded.
Potentiometer P0, located on the front panel, can be used to correct any errors caused by the analog measurement circuit in some applications.
Programming example
Controlling the temperature of an oven.
The cooking temperature is set at 315 °C.
A variation of +/- 3.6 °C results in tripping of outputs %Q0.1 and %Q0.2 respectively.
Practically all of the possible setting range of the potentiometer from 0 to 250 is used in this example.
LD [%SW112 = 175]
ST %Q0.0
LD [%SW112 <= 173]
ST %Q0.1
LD [%SW112 >= 177]
ST %Q0.2
0 °C -> 0 V -> %SW112 = 0
311.4 °C -> 6.92 V -> %SW112 = 173
315 °C -> 7 V -> %SW112 = 175
318.6 °C -> 7.08 V -> %SW112 = 177
450 °C -> 10 V -> %SW112 = 250
B
___________________________________________________________________________
3/15
B
3.4
Dedicated function blocks
3.4-1 Bit and word objects associated with dedicated function blocks
Dedicated function blocks use the same type of dedicated words and bits as standard function blocks (See Section 2.2).
Function block bit and word objects accessible by the program
Dedicated function blocks
Sect.
Pulse width modulation output
%PWM
Pulse generator
%PLS
Fast counter %FC
Send message %MSG
Shift bit register
%SBRi (i=0 to 7)
Step counter
%SCi (i=0 to 7)
Associated words and bits
Word
Word
Bit
Word
Bit
Bit
Bit
Bit
% of pulse at 1 in relation to the total period
Preset period
Preset value
No. of pulses to generate
Current output
Generation done output
Threshold i (i = 0 or 1)
Current value
Preset value
%FC.Si
%FC.V
%FC.P
yes no yes
Overrun output %FC.F
no
Overrun threshold i output %FC.THi
no
Comm. fault output
Comm. done output
Register bit, j=0 to 15
%MSG.E
%MSG.D
%SBRi.j
no no yes
Step counter bit, j=0 to 255
Address
%PWM.R
%PWM.P
No
%PLS.P
%PLS.N
%PLS.Q
%PLS.D
%SCi.j
Write access yes yes yes no no no
See
3.4-3
3.4-4
3.4-5
3.4-6
3.4-7
3.4-8
3.4-2 Programming principles
As with standard function blocks, special function blocks can be programmed in 2 different ways :
• Non-reversible programming : using special instructions.
• Reversible programming : by simulating Ladder language function blocks.
See Section 2.2-2.
___________________________________________________________________________
3/16
Numerical and special instructions
3
3.4-3 Pulse width modulation output % PWM
The %PWM function block is used to generate a square wave signal on PLC output %Q0.0. The signal width (duty cycle) can be varied by the program (for description, see
Part A, Section 4.6).
This function can also be used to control an analog output module wired to the output %Q0.0 (see Section B-4.4).
B
%PWM block programmable width fixed period which can be configured
Characteristics
Time base TB 0.1ms (1), 10ms, 1s (default value)
Preset period %PWM.P 0<%PWM.P-32767 if time base is 10ms or 1s.
0<%PWM.P-255 if time base is 0.1ms
(0= function not in use)
The preset value and the time base can be modified during configuration. They are used to fix the signal period T = %PWM.PxTB.
The lower the ratios to be obtained, the greater the selected %PWM.P must be.
Range of periods obtained :
• 0.2 to 26ms in steps of 0.1ms
• 20ms to 5.45 min in steps of 10ms
• 2s to 9.1 hours in steps of 1s
Ratio of the
Pulse generation input
(or instruction)
IN
Warning :
%PWM.R 0-%PWM.R-100 (2), this word gives the period percentage of the signal at state 1 in a period ( 0 = default value).
The "width" Tp is thus equal to : Tp = T x (%PWM.R/100)
Word %PWM.R is written by the user program. It is this word which performs the width modulation.
At state 1, the pulse width modulated signal is generated at output %Q0.0.
At state 0, output %Q0.0 is set to 0.
The algorithm for processing width modulation %PWM has been refined between versions V3.0
and V3.1 of TSX Nano. For the same %PWM.R, this may result in a different duty cycle at the output between the two versions.
(1) This time base is not advisable for TSX Nano PLCs with relay outputs.
(2) Values greater than 100 will be considered as being equal to 100.
___________________________________________________________________________
3/17
B
Operation
The frequency of output signal %Q0.0 is set during configuration by selecting the time base TB and the preset %PWM.P. The width of the signal is modulated by modifying the %PWM.R ratio in the program.
Input IN
Ratio %PWM.R
Output %Q0.0
Programming and configuration
In this example, the signal width is modified by the program according to the state of
PLC inputs %I0.0 and %I0.1.
The signal period is set at 500 ms during configuration. (See configuration note below.)
If %I0.0 and %I0.1 are set to 0, the %PWM.R ratio is set at 20%, the duration of the signal at state 1 is then : 20% x 500 ms = 100 ms.
If %I0.0 is set to 0 and %I0.1 is set to 1, the %PWM.R ratio is set at 50% (duration 250 ms).
If %I0.0 and %I0.1 are set to 1, the %PWM.R ratio is set at 80% (duration 400 ms).
LDN %I0.0
ANDN %I0.1
[%PWM.R:=20]
LD %I0.0
ANDN %I0.1
[%PWM.R:=50]
LD %I0.0
AND %I0.1
[%PWM.R:=80]
BLK %PWM
LD %I0.2
IN
END_BLK
Configuration
Output %Q0.0 = output %PWM TB= 10ms %PWM.P=50
Special cases
• Effect of a cold restart : (%S0=1) sets the %PWM.R ratio to 0
• Effect of a warm restart : (%S1=1) has no effect
• Effect of a PLC stop :
The output %Q0.0 is set to 0 regardless of the state of system bit %S8. For PLCs, version 2.2 or lower, the output %Q0.0 is set to 0 if %S8 is at 1 or maintained (signal generation) if %S8 = 0.
• With 0.1 ms time base, forcing output %Q0.0 using a programming device does not
3/18
Numerical and special instructions
3
3.4-4 Pulse generator output % PLS
Adjust
The %PLS function block generates a square wave signal (on to off ratio, or duty cycle, of 50%) at PLC output
%Q0.0.
This signal can be :
• of limited length, the number of pulses and the period are written by the program (or during configuration).
• of unlimited length, the period is written by the program or during configuration.
(see description in Part A, Section 4.5).
B
%PLS block
Variable period
Characteristics
Time base
Preset
Number of pulses
Adjustment via the terminal
Pulse generation input (or instruction)
Reset input
(or instruction)
Current pulse generation output
Pulse generation done output
PLS counter (2)
TB
%PLS.P
%PLS.N
0.1 ms (1), 10ms, 1s (default value)
0<%PLS.P<32767 if TB =10 ms or 1s.
0<%PLS.P<255 if TB = 0.1ms (1)(2)
(0 = output at 0, 1 = output at 1). The preset value is used to modulate the signal period T = %PLS.PxTB.
Range of periods obtained :
• 0.2 to 26ms in steps of 0.1ms
• 20ms to 5.45 min in steps of 10ms
• 2s to 9.1 hours in steps of 1s.
Note : %PLS.P must be an even number
0<%PLS.N-32767, this word gives the number of pulses of the train to be generated.
0 = square wave signal of unlimited length (by default).
%PLS.N is tested and written by the program.
Y/N
IN
R
%PLS.Q
Y : possible to modify the preset value
%PLS.P.N in the Data editor.
N : no access in the Data editor
At state 1, generates the signal on output %Q0.0.
At state 0 sets output %Q0.0 to 0.
At state 1, resets the number of pulses of outputs %PLS.Q, and %PLS.D to zero
State 1, pulse signal is generated at %Q0.0.
%PLS.D
State 1, signal generation is done
N=no, Y=yes. This option enables input %I0.0 to be used as a counting input.
(1) This time base is not advisable for TSX 07s with relay outputs.
(2) The PLS counting option is required when a time base of 0.1 ms is selected. In order for the PLS to work properly, it is necessary to physically loop output %Q0.0 to input %I0.0. In this type of operation, the %PLS.P must be greater than or equal to 6 (max. freq. =1.6 Khz) to ensure correct operation of the function.
___________________________________________________________________________
3/19
Operation
Input IN
B
Number of pulses
Output %Q0.0
Output %PLS.Q
Output %PLS.D
Special cases
• Effect of a cold restart : (%S0=1) sets the value of %PLS.P to that defined during configuration
• Effect of a warm restart : (%S1=1) : no effect
• Effect of a PLC stop : see effect of a PLC stop page 3/18.
• Effect of modifying the preset %PLS.P : modifying the preset value %PLS.P via an instruction or by adjusting it takes effect instantly
• With the time base of 0.1 ms, forcing the loop input %I0.0 does not stop generation.
Comment :
Using a time base of 0.1 ms may create a discrepancy of one pulse between the number of pulses requested (%PLS.N) and the number actually generated.
To overcome this, the function must be reset once generation is complete :
LD %Mi
IN %PLS
N
R %PLS
However, this action restarts generation of %PLS.N pulses once input IN changes to 1.
___________________________________________________________________________
3/20
Numerical and special instructions
3
3.4-5 Fast counting functions, frequency meter and up/down counter %FC
The %FC function block can be used to perform one of the three following functions :
• Fast counting
• Frequency meter
• Up/down counting
(see detailed description, Part A, Section 4.4). The function is selected during configuration.
Note : Fast counting functions can be used without any programming, simply by configuring the I/O and the parameters.
%FC block
Characteristics of block %FC
The function block offers a group of words, input and output bits which are used to generate the 3 counting functions. To fully understand the role of each object in the function to be performed, refer to the detailed description of the function.
Current value %FC.V
Word incremented or decremented according to the inputs and the function selected.
Can be read and tested but not written.
Preset value %FC.P
Threshold value S0 (1) %FC.S0
Only used by the up/down counting function :
0-%FC.P-65535. Word can be read, tested and written.
0-%FC.S0-65535 word containing the value of threshold 0, defined during configuration can be read and written by the program.
Threshold value S1 (1) %FC.S1
Enable input
(or instruction)
Set input
(or instruction)
Overflow output
Threshold bit 0 (2)
Threshold bit 1 (2)
IN
S
%FC.F
0-%FC.S1-65535 word containing the value of threshold 1, defined during configuration can be read and written by the program.
At state 1, validates the current function.
At state 0, inhibits the current function.
At state 1 :
• sets the current value to the preset value (up/
down counting function) or resets the current
value to 0.
• initializes operation of the threshold outputs
(HSC_Out)
• takes into account threshold values %FC.S0
and %FC.S1 modified by the program.
State 1, when the current value %FC.V exceeds
65535. %FC.F can be cleared by a Preset (%I0.1
or S instruction) or a cold restart.
%FC.TH0
State 1, when the current value is greater than or equal to the threshold value %FC.S0
%FC.TH1
State 1, when the current value is greater than or equal to the threshold value %FC.S1
(1) Threshold value %FC.S0 must be less than threshold value %FC.S1.
(2) It is advisable to test bit %FC.THx only once in the program.
___________________________________________________________________________
3/21
B
B
Fast counting function
The fast counting function counts at a maximum frequency of 10 kHz in fast mode (or
5 kHz in normal mode, selected during configuration), with a range of 1- 65535.
The counter receives the signals to be counted at PLC input %I0.0. The counting value
(current value %FC.V) is compared to 2 thresholds %FC.S0 and %FC.S1, which are defined during configuration and can be modified by the program (modification is taken into account when the Set input is activated).
Fast counter
Diagram :
Counting input
Counter
Enable inputs
Set inputs
(preset to 0)
Instruction [READ %FC.V]
Current value
Overflow output
Current value
Threshold value 0
Threshold value 1
C o m p a r i son
Threshold bit 0
Threshold bit 1
Threshold output 0
Threshold output 1
Enable
Comment : Apart from counting input %I0.0, all other function block discrete I/O are optional (they can be selected during configuration). The equivalent programming objects and instructions are available for each of these (marked by a box on the diagram).
Threshold outputs : Threshold outputs are controlled directly by the fast counter
(without waiting for the outputs to be updated at the end of the scan) according to the settings established by the user during configuration.
Output
%Q0.1
%Q0.2
FC.V< thres.0<thres.1
0 or 1
0 or 1 thres.0-FC.V-thres.1 thres.0<thres.1<FC.V
0 or 1
0 or 1
0 or 1
0 or 1
When they are initialized the threshold outputs must be enabled by a fast counter preset command. Programming example :
BLK %FC
LD %S0
S
END_BLK
LD %S0
S %SW111:X1 (enable bit %SW111:X is set to 1)
___________________________________________________________________________
3/22
Numerical and special instructions
3
Reading the current value
The current %FC.V value is updated at the end of each PLC scan. %FC.V can also be updated by the READ instruction : syntax : [READ %FC.V] Timing diagram
Counter input (%I0.0)
65535
Threshold 1 %FC.S1
Threshold 0 %FC.S0
B
Current value %FC.V
Enable input
IN or %I0.2
Set input
S or %I0.1 (1)
Overflow
%FC.F
Threshold bit 0
%FC.TH0
Threshold bit 1
%FC.TH1
Threshold output 0
%Q0.1 (2)
Threshold output 1
%Q0.2 (2)
(1) Input %I0.1 operates on a rising edge (see timing diagram), while input S operates on a state.
(2) In this timing diagram the status matrix configured by the user is as follows :
Output
%Q0.1
%Q0.2
FC.V< thresh 0<thresh 1 thresh 0-FC.V-thresh 1 thresh0<thresh 1<FC.V
0 1 0
1 0 0
___________________________________________________________________________
3/23
B
Frequency meter function
The frequency meter function is used to measure the frequency of a periodic signal in Hz on input %I0.0. There is a choice of two modes : fast (10kHz filtering) or normal
(5kHz filtering).
The frequency range which can be measured is from 1Hz to 10kHz. The user can choose between 2 time bases, the choice being made by system bit %SW111:X2 (1
= time base of 100 ms, 0 = time base of 1s).
Time base
100ms
1s
Measurement range
100Hz-10kHz
10Hz-10kHz
Precision
0.1% for 10kHz
10% for 100Hz
Update
10 times per second
0.01% for 10kHz Once per second
10% for 10Hz
System bit %SW111:X3 is set to 1 during an update of the current value. The user program must reset the system bit to 0.
Frequency meter
Diagram :
Counter input
Counter
Enable inputs
(1)
Set inputs
(current value to 0)
Select the time base
Current
Value
Overflow output
Current value (2)
Update
(1) Input %I0.2 is optional, its use is selected during configuration.
(2) Current value FC.V is expressed in Hz.
Note :
This function can also be used to obtain the value of the analog module wired to input %I0.0 (see part B Section 4.3 : managing analog I/O).
Timing diagram
Counter input (%I0.0)
Enable input
(IN or %I0.2)
Set input (S)
Time base TB
3/24
Numerical and special instructions
3
Up/down counting function
The up/down counting function counts up or down at a maximum frequency of 1 kHz, with an up/down counting range of 0 to 65535.
The counter receives the signals to be upcounted on PLC input %I0.0, and the signals to be downcounted on PLC input %I0.3. It provides an output indicating the direction of movement : whether the counter is upcounting %SW111:X0 = 1 or downcounting
%SW111:X0 = 0. The up/down counting value (current value %FC.V) is compared with
2 thresholds, %FC.S0 and %FC.S1, which are defined during configuration and can be modified by the program (modification is taken into account when the preset input is activated).
Diagram :
Up/down counter
Upcounter input
Downcounter input
Upcounter downcounter direction of movement
Enable inputs
B
Preset value
Set inputs
Read input
Instruction [READ %FC.V]
Threshold value 0
Threshold value 1
Preset value
Current value
Enable
C o m p a r i son
Overflow output
Current value
Capture value
Threshold bit 0
Threshold bit 1
Threshold output 0
Threshold output 1
Apart from upcounting input %I0.0 and downcounting input %I0.3, all other function block discrete I/O are optional (they can be selected during configuration). The equivalent programming instructions and objects are available for each of these
(marked by a box on the diagram).
Preset : the preset value of 0 to 65535 is defined during configuration and can be modified by the program. The current value is loaded with the preset value on a rising edge at input %I0.1 or at state 1 of input S.
Threshold outputs : see fast counting function
Reading the current value
The value %FC.V is updated automatically at the end of the scan. %FC.V can also be updated by the READ instruction, syntax : [READ %FC.V]
A rising edge on Read input %I0.4 causes the value %FC.V to be copied to %SW110.
___________________________________________________________________________
3/25
B
Upcounter input %I0.0
Downcounter input %I0.3
65535
Threshold 1 %FC.S1
Threshold 0 %FC.S0
Preset value %FC.P
Current value %FC.V
Enable input
IN or %I0.2
Set input
S or %I0.1 (1)
Direction of movement
%SW111:X0
Overflow
%FC.F (2)
Threshold bit 0
%FC.TH0
Threshold bit 1
%FC.TH1
Threshold output %Q0.1 (3)
Threshold output %Q0.2 (3)
(1) Input %I0.1 operates on a rising edge, while input S operates on a state.
(2) The overflow output %FC.F is reset to zero after reinitialization of the counter.
(3) See status matrix for the fast counting function.
Important :
If one of the 4 inputs %I0.0, %I0.1, %I0.3, or %I0.4, on a rising or falling edge is at state 1, no action linked to the other 3 will be performed.
___________________________________________________________________________
3/26
Numerical and special instructions
3
Special cases (fast counting, frequency meter and up/down counter)
• Effect of a cold restart : (%S0=1) changes the current value, outputs %FC.F,
%FC.TH0, %FC.TH1 and enable bit of the threshold outputs (%SW111:X1) to 0, and copies the values defined during configuration to words %FC.P,%FC.S0/S1.
• Effect of a warm restart : (%S1=1) and PLC stop : has no effect on the current value.
After an activated master control relay instruction MCS, high-speed outputs are set to 0, after deactivation of the MCS, they are only reset after the threshold is crossed in upcounting mode or after an up/down counting action in downcounting mode.
• Displayed %FC values :
For all values related to the %FC function block, values are displayed :
- by the FTX 117 terminal as two's complement numbers (Decimal) or as a direct value
(Hexadecimal).
- by PL7-07 as direct value (Decimal or Hexadecimal).
For example :
%FC.V
Displayed values
(PL7-07) (FTX 117) (PL7-07 - FTX 117)
0
1
2
•
•
•
32766
32767
•
•
32768
•
65533
65534
65535
0
0
1
2
•
•
•
32766
32767
•
•
•
65533
65534
65535
0
0
1
2
•
•
•
32766
32767
•
•
-32768
•
-3
-2
-1
0
0000
0001
0002
•
•
•
7FFE
7FFF
•
•
8000
•
FFFD
FFFE
FFFF
0
B
___________________________________________________________________________
3/27
B
Example of the fast counting function
Description of the application
T
Photo-electric cell
M
A-
A+
V
T1
T2
STORE
REJECT
START
The parts to be measured are put on a conveyor belt driven continuously without slipping by a motor to which a rotary incremental encoder is attached. The measurement is made by counting the number of pulses during the time cell C detects the moving part. A cylinder V controls the lateral movement of belt T so as to position it opposite conveyor T1 or conveyor T2, according to the measurement results.
The number of pulses measured is compared to 2 extreme values (length measurement tolerance)
Beam
Pulse
• If it is between these 2 values, the part is directed towards the
STORE (belt T1, control A+ on cylinder V)
• If this is not the case, the part is directed towards the reject bin
(belt T2, control A- on cylinder V)
1 part corresponds to
10000 pulses
The START pushbutton is used to start the whole operation.
Assigning the I/O
Inputs
• %I0.0 counter input connected to the incremental encoder
• %I0.1 reset input connected to the photoelectric cell
• %I0.2 enable input connected to the start button
Outputs
• %Q0.1 cylinder A+ control output
• %Q0.2 cylinder A- control output
• %Q0.0 belt control output
___________________________________________________________________________
3/28
Numerical and special instructions
3
Processing the application
The fast counting function can be processed without the need to program the PLC by configuring only the %FC function block.
%FC : counter
Mode : fast
Counting input : %I0.0
Set : %I0.1
Enable input : %I0.2
%FC.S0
%FC.S1
: 9950 threshold 0 corresponds to the minimum tolerance level
: 10000 threshold 1 corresponds to the maximum tolerance level
Output matrix
Output FC.V< thresh 0<thresh 1
%Q0.1
%Q0.2
0
1 thresh 0-FC.V-thresh 1
1
0 thresh 0<thresh 1<FC.V
0
1
B
Program
LD
ST
%I0.2
%Q0.0
LDF %I0.1
S %SW111:X1
LDR %I0.1
ORN %I0.2
R %SW111:X1
Operation
Input %I0.0 counts the number of pulses sent from the incremental encoder as soon as the enable input %I0.2 (start button) is activated.
On a rising edge at input %I0.1, the current value of the counter is reset to 0.
When the cell (input %I0.1) detects that there are no more parts on the conveyor belt, outputs %Q0.1 and %Q0.2 are enabled (by bit %SW111:X1) and set to 0 or 1 at this moment depending on the current value of the counter %FC.V (according to the output matrix).
Output %Q0.1 is set to 1 when the part is within tolerance. It controls the output of positioning cylinder A on conveyor belt T1 (see the output matrix).
Output %Q0.2 is set to 1 when the part is outside tolerance (return cylinder A to belt T2).
___________________________________________________________________________
3/29
B
3.4-6 Transmitting/Receiving messages and controlling data exchanges
The TSX Nano can communicate with a programming terminal (either the FTX117 or the PL707 software) and with other UNI-TELWAY devices connected to the terminal port. The TSX Nano can also be configured to send and/or receive messages in character mode (ASCII protocol).
PL7 language offers for this :
• EXCH instruction to transmit/receive messages,
• %MSG function block to control the data exchanges.
The TSX Nano determines the protocol according to the pinout of the cable being used, and provides this information to the system bit %S100 (management of /DPT).
An overview of UNI-TELWAY compatible products and configurations appears in Part
F of this manual.
EXCH instruction
The SEND instruction allows the TSX Nano to send and/or receive information to/from
UNI-TELWAY or ASCII devices. The user defines a table of words (%MWi:L or %KWi:L) containing the data to be sent and/or received (up to 64 data words in transmission and/ or reception). The format for the word table is described in the paragraphs about each protocol (ASCII and UNITELWAY).
A message exchange is performed using the EXCH instruction.
Syntax: [EXCH %MWi:L] (1) or [EXCH %KWi:L]
Note : Devices such as XBT or CCX man-machine interfaces, or Inductel identification devices, which support UNI-TELWAY protocol, can send information to, or get information from the TSX
Nano without any special TSX Nano programming.
The TSX Nano must finish the exchange from the first EXCH instruction before a second can be launched. The %MSG block must be used when sending several messages.
(1) L : Number of words in the word table.
Values of the internal word table %MWi:L are such as i+L - 255.
Note
The PL7-07 V1 software can only be used for transmission, using the SEND instruction for TSX07 V1 and V2.
TSX Nano V3 PLCs (TSX 07 3• •• ••) authorize transmission and/or reception of messages using the EXCH instruction (the EXCH instruction in reception mode on
TSX 07 3• 10 •• PLCs is only possible in version V3.1).
(For PL7-07 V1, the EXCH instruction is called SEND).
___________________________________________________________________________
3/30
Numerical and special instructions
3
%MSG function block
The use of the %MSG function block is optional; it can be used to manage data exchanges. The %MSG function block has three purposes :
• Communications error checking
The error checking verifies that the block length (word table) programmed with the
EXCH instruction is large enough to contain the length of the message to be sent
(compare with length programmed in the least significant byte of the first word of the word table). It also verifies that a UNI-TELWAY message was received by the UNI-
TELWAY device.
• Coordination of multiple messages
To ensure the coordination when sending multiple messages, the %MSG function block provides the information required to determine when a previous message is complete.
• Transmission of priority messages
The %MSG function block allows current message transmissions to be stopped, in order to allow the immediate sending of an urgent message.
Exchange control block
The %MSG function block manages exchanges.
Programming it is optional.
B
%MSG block
Characteristics of the %MSG block
Reset input
(or instruction)
Comm. done output
R
%MSG.D
Fault (Error) output %MSG.E
At state 1, reinitializes communication,
%MSG.E = 0 and %MSG.D = 1
State 1, comm. done if :
• End of transmission if transmission,
• End of reception (end character received),
• Error,
• Reset the block.
State 0, request in progress
State 1 if :
• Bad command,
• Table incorrectly configured
• Incorrect character received (speed, parity, etc)
• Reception table full (not updated)
State 0, message length OK, link OK
If an error occurs when using an EXCH instruction, bits %MSG.D and %MSG.E go to
1 and system word %SW69 contains the error code. See Section 6.2-2.
___________________________________________________________________________
3/31
B
Reset input (R) : When the Reset input is set to 1, it immediately stops any messages that are being transmitted, resets the Fault (Error) output to 0 and sets the Done bit to 1.
A new message can now be sent.
Fault (Error) output (%MSG.E) : The error output is set to 1 either because of a communications programming error or a message transmission error. The error output is set to 1 if the number of bytes defined in the data block associated with the EXCH instruction (word 1, least significant byte) is greater than 128 (80 in hexadecimal).
The error output is also set to 1 if a problem exists in sending a UNI-TELWAY message to a UNI-TELWAY device. In this case, the user should check wiring, and that the destination device supports UNI-TELWAY communication.
Communications Done output (%MSG.D) : When the Done output is set to 1, the TSX
Nano is ready to send another message. Use of the %MSG.D bit is recommended when multiple messages are sent. If it is not used, messages may be lost.
Transmission of several successive messages
Execution of the EXCH instruction activates a message block in the application program.
The message is transmitted if the message block is not already active (%MSG.D=1). If several messages are sent in the same cycle, only the first message is transmitted. The user is responsible for managing the transmission of several messages using the program.
Example : Transmission of 2 messages in succession.
LDR %I0.0
AND %MSG.D
[EXCH %MW2:4]
S %M0
LD %MSG.D
AND %M0
[EXCH %MW8:3]
R %M0
Reinitializing exchanges
An exchange is cancelled by activating the input (or instruction) R. This input initializes communication and resets output %MSG.E to 0 and output %MSG.D to 1. It is possible to reinitialize an exchange if a fault is detected.
Example : BLK %MSG
LD %M0
R
END_BLK
Special cases
• Effect of a cold restart : (%S0=1) forces a reinitialization of the communication.
___________________________________________________________________________
3/32
Numerical and special instructions
3
• Effect of a warm restart : (%S1=1) has no effect.
• Effect of a PLC stop : if a message transmission is in progress, the PLC stops its transfer and reinitializes the outputs %MSG.D and %MSG.E.
Characteristics of ASCII mode
The ASCII output communications mode is selected by jumpering pins on the terminal port (see Part F for specific information). Status bit %S100 is set to 1 when the TSX Nano is in ASCII mode. It also confirms that, with the necessary jumpers, the cable is connected.
B
The three possible uses of this instruction are :
• Transmission
• Transmission / Reception
• Reception
The maximum size of the frames transmitted and/or received is 128 bytes.
The word table associated with the EXCH instruction is composed of transmission and reception tables.
Most significant byte
Command
Byte transmitted 1
...
...
Byte transmitted n+1
Byte received 1
...
...
Byte received p+1
Least significant byte
Length LgT / LgR
Byte transmitted 2
...
Byte transmitted n
Byte received 2
...
Byte received p
Control
Transmission table
Reception table
The Length byte (LgT) contains the length to be transmitted, which is overwritten by the number of characters received (LgR) at the end of reception.
The command byte must contain one of the following values :
• 0 : Transmission
• 1 : Transmission followed by reception
• 2 : Reception
___________________________________________________________________________
3/33
B
The table can only be type %KWi in the case of transmission.
Reception ends when the end of frame byte is received (1). The value of this byte can be modified by the user (least significant byte of system word %SW68). The default value of this word is H'0D' (carriage return).
(1) Warning :
The system does not manage a reception time-out
Sending a message to an ASCII device : Pure transmission
The content of the data block associated with the SEND instruction needed to write data to an ASCII device (such as a display or printer) is as follows :
Most significant byte
0 (transmission)
Least significant byte
Length of message (bytes)
ASCII data
The maximum length of a message is 128 bytes.
Example 1 : request to display message "FAULT 10" on a printer using ASCII protocol.
LDR %I0.0
AND %MSG.D
[EXCH %KW10:7]
Word table contents :
Word
%KW10
%KW11
%KW12
%KW13
%KW14
%KW15
%KW16
Contents
12
'DE'
'FA'
'UT'
' 1'
'0 '
16#0A0D
Most significant byte
0
ASCII text
Least significant byte
Length LgT in bytes
Line return Carriage return
___________________________________________________________________________
3/34
Numerical and special instructions
3
ASCII Transmission / Reception
At the end of transmission, the TSX Nano switches to wait for reception, then after receiving a response, copies it into the %MWi zone contiguous with the transmission table if the status of the reception is OK and if the length of the question (LgT) and the response (LgR) is less than the %MWi reserved zone (length L). If this is not the case, bit %MSG.E changes to 1.
Reception is ended when the end code is detected (H'0D' by default but may be modified in %SW68) or when the reception table is full.
There is no reception time-out management.
Note
TSX Nano V1 or V2 cannot receive ASCII messages.
B
The contents of the word table associated with the EXCH instruction necessary for transmission / reception of ASCII data is described below : m
Most significant byte
1 (transmission / reception)
Byte to be transmitted 1
...
...
Byte to be transmitted n+1
Byte received 1
...
...
Byte received p+1
Notes
%KWi type words are prohibited.
Least significant byte
Length LgT or LgR
Byte to be transmitted 2
...
Byte to be transmitted n
Byte received 2
...
Byte received p
End code (H'0D')
Control
Transmission table
Reception table
When the exchange is finished (end of frame character received), the transmission length byte (LgT) contains the number of characters received (LgR).
The transmission length byte must therefore be updated before each exchange.
The message reception zone is aligned to the word following the transmission zone.
___________________________________________________________________________
3/35
B
Example :
Words
%MW10
%MW11
%MW12
%MW13
%MW14
Most signif.
Least signif.
16#0001
'V'
'L'
16#0007
'A'
'U'
'E'
':'
' ' not used
Associated program :
LDR %I0.0
AND %MSG.D
[EXCH %MW10:9]
This program transmits the following frame: VALUE : 7 bytes and waits to receive a response (8 bytes maximum).
The characters received are accessible in the words %MW15 to %MW18.
Calculation of the length of the word table
LgT = 7
LgR = 8
L = 1 + LgT + LgT%2 + LgR + LgR%2 = 9
2 2
Note
TSX 07 2
● ●●●●
Nano-PLCs cannot receive ASCII messages.
___________________________________________________________________________
3/36
Numerical and special instructions
3
Receiving a message from an ASCII device
On execution of the EXCH block, which has been set for reception, the TSX Nano switches to wait for reception, then copies the response into the %MWi zone if the status of the reception is OK and if the length of the response (LgR) is less than the %MWi reserved zone (length L). If this is not the case, bit %MSG.E is set to 1.
Reception is ended when the end code is detected (16#0D by default but may be modified in %SW68) or when the reception table is full.
There is no reception time-out management.
Note
The TSX Nano V1 or V2 cannot receive an ASCII message.
B
The contents of the word table associated with the EXCH instruction necessary for receiving ASCII data is described below :
Most significant byte
2 (reception)
Byte received 1
...
...
Byte received p+1
Least significant byte
0 (1)
Byte received 2
...
Byte received p
End code (H'0D')
Control
Reception table
Note
%KWi type words are prohibited.
The communication type is managed in the first word of the table.
(1) In reception mode, this least significant byte is not taken into account.
___________________________________________________________________________
3/37
B
Exchange control
Exchange control is performed using the %MSG function block and system word
%SW69.
After each exchange, %SW69 (report of EXCH block) is updated and takes one of the following values :
• 0: Exchange OK.
• 1: Transmission table too large (LgT>128).
• 2: Transmission table too small (LgT=0).
• 3: Word table too small (1).
• 7: Bad ASCII command (command byte <> 0, 1 or 2).
• 8: Not used
• 9: Reception error (problem with communication format (speed, parity)).
• 10: %KWi table prohibited in reception or transmission / reception.
(1) L < 1 + LgT + LgT%2 + LgR + LgR%2
2 2
where L in words
LgT and LgR in bytes
___________________________________________________________________________
3/38
Numerical and special instructions
3
Dialog with a UNI-TELWAY device
The word table associated with the EXCH instruction used to send a request to a UNI-
TELWAY device such as ATV speed controllers or man-machine interface devices
(CCX 17 or XBT) is made up of transmission and reception tables.
B
Most significant byte
Target address
Category code
First word (MSB)
...
Word n-1 (MSB)
Word n (MSB)
00 (forced)
Data received 2
...
Data received p-1
Least significant byte
Length LgT / LgR (bytes)
Request code
First word (LSB)
...
Word n-1 (LSB)
Word n (LSB)
Response code received
Data received 1
...
...
Data received p
Control
Transmission table
Reception table
The maximum size of the messages transmitted and received is 128 bytes.
The message reception zone is always aligned on the word following the transmission zone.
The EXCH block reads the length to be transmitted (LgT) in the transmission length field.
When the exchange has finished, it writes the length of the message received there (LgR).
The transmission length byte must therefore be updated before each transmission.
The response code received is written in the least significant byte of the first word of the reception table. The most significant byte of this word is forced to 0. The following data, if there is any, is aligned on the next word.
Important
From TSX Nano V3, the order for transmitting data from a UNI-TE request becomes
Most Significant byte then Least Significant byte.
Applications operating with TSX Nano V1 or V2 must be modified to take account of this inversion if they are loaded onto a TSX Nano V3.
___________________________________________________________________________
3/39
B
Unitelway Master
In this mode, the TSX Nano normally manages two devices distributed over 5 slave addresses. It is possible to control 2 devices and a PL7 07 programming terminal, if the programming terminal is configured on a single address.
The TSX Nano does not manage slave to slave routing.
The TSX Nano Master can transmit a request to any slave address from 1 to 5, using the EXCH block. It uses the source address 0.254.16.
The target address coded in the word table associated with the EXCH block must be one of the following :
• 0: Transmission of a request to slave 4 (compatible with TSX07 2.).
• 1 to 5: Transmission and reception of a request to a slave with address 1 to 5.
If the target address is 0, the characteristics of the EXCH block are as follows :
• The reception buffer is not used,
• The table can be situated in zone %KWi,
• Bit %MSG.D changes to 1 when the response from the slave is received,
• The response from the slave is ignored.
• Only Write and non-solicited Data requests can be used.
If the target address is between 1 and 5 :
• The reception table is obligatory (1 word minimum),
• The word table must be situated in zone %MWi,
• Bit %MSG.D changes to 1 when the response from the slave is received,
• The response from the slave is copied into the reception table.
Example of use :
Transmission of the request "Read word" %MW513 (16#0201) to a device at address
2 :
Words
%MW10
%MW11
%MW12
Most signif.
Least signif.
02
07
02
04
04
01
Associated program :
LDR %I0.0
AND %MSG.D
[EXCH %MW10:5]
The EXCH block uses %MWi:L as parameters :
• i indicates the number of the first word in the table
• L indicates the number of words in the word table.
___________________________________________________________________________
3/40
Numerical and special instructions
3
When bit %MSG.D = 1 and bit %MSG.E = 0, the table contains the following data :
Words
%MW10
%MW11
%MW12
%MW13
%MW14
Most signif.
Least signif.
02
07
02
04
04
01
00
'AB'
34
'CD'
The data in bold signifies :
• 4 bytes received,
• response code received = 16#0034,
• value of word %MW513 = 16#ABCD.
B
___________________________________________________________________________
3/41
B
Unitelway Slave
Any device (local or remote) can question the system server from the TSX Nano Slave using Ad0 (server) as a target address.
A TSX Nano slave can transmit (client) a request to any Master or Slave device (address
0 to 98) using the EXCH block (when the master is a TSX 37/57 PLC).
The target address coded in the word table associated with the EXCH block must be between 100 and 198 (when the master is a TSX 47/67/87/107 PLC).
The characteristics of the EXCH block are as follows :
• The reception table is obligatory (1 word minimum),
• The word table must be situated in zone %MWi,
• Bit %MSG.D changes to 1 when the response from the slave is received,
• The response is copied into the reception table.
Example of use :
Transmission of the request "Read word" %MW513 to the Master :
Words
%MW10
%MW11
%MW12
Most signif.
Least signif.
00 04
07
02
04
01
Associated program :
LDR %I0.0
AND %MSG.D
[EXCH %MW10:5]
The EXCH block uses %MWi:L as parameters :
• i indicates the number of the first word in the table
• L indicates the number of words in the word table.
When bit %MSG.D = 1 and bit %MSG.E = 0, the table contains the following data :
Words
%MW10
%MW11
%MW12
%MW13
%MW14
Most signif.
Least signif.
00 04
07
02
00
'AB'
04
01
34
'CD'
___________________________________________________________________________
3/42
Numerical and special instructions
3
The data in bold signifies :
• 4 bytes received,
• response code received = 16#0034,
• value of word %MW513 = 16#ABCD.
Other example :
Transmission of the request "Read word" %MW513 to slave 32 :
Words
%MW10
%MW11
%MW12
Most signif.
Least signif.
20 04
07
02
04
01
Associated program :
LDR %I0.0
AND %MSG.D
[EXCH %MW10:5]
The EXCH block uses %MWi:L as parameters :
• i indicates the number of the first word in the table
• L indicates the number of words in the word table.
When bit %MSG.D = 1 and bit %MSG.E = 0, the table contains the following data :
Words
%MW10
%MW11
%MW12
%MW13
%MW14
Most signif.
Least signif.
20
07
02
04
04
01
00
'AB'
34
'CD'
The data in bold signifies :
• 4 bytes received,
• response code received = 16#0034,
• value of word %MW513 = 16#ABCD.
B
___________________________________________________________________________
3/43
B
Exchange control
Exchange control is performed using the %MSG function block and system word
%SW69.
Bit %MSG.D is set to 1 in the following cases :
• When the response has been received.
• If there is a transmission error (negative acknowledgment)
• If the block is reinitialized.
• If the response does not arrive within 7 seconds (application time-out).
Bit %MSG.D changes to 1 for any other errors (detailed in word %SW69) :
After each exchange, word %SW69 (report of EXCH block) is updated and takes one of the following values :
• 0 : Exchange OK.
• 1 : Transmission table too large (LgT>128).
• 2 : Transmission table too small (LgT=0).
• 3 : Word table too small (1).
• 4 : Incorrect Unitelway address (target address does not belong to [0...98] or
[100...198] in UNI-TELWAY Slave mode or to [1...5] in UNI-TELWAY Master.
• 5 : Time-out expired.
• 6 : Transmission error (target responds with Nack).
• 7 : Bad ASCII command (command byte <> 0, 1 or 2).
• 8 : Not used
• 9 : Reception error (problem with communication format (speed, parity)).
• 10 : %KWi table prohibited in reception or transmission / reception.
(1) L < 1 + LgT + LgT%2 + LgR + LgR%2
2 2
where L in words
LgT and LgR in bytes
___________________________________________________________________________
3/44
Numerical and special instructions
3
3.4-7 Shift bit register function blocks %SBRi
A shift bit register is used to enter binary data (0 or 1) and to move them in one direction or the other.
B
Shift register block
C haracteristics
Register number
Register bit
%SBRi
%SBRi.j
Reset input
(or instruction)
Shift to left input (or instruction)
Shift to right input (or instruction)
Operation
Initial state
CU %SBRi performs a shift to the left
Bit 15 is lost
R
CU
CD
0 to 7
Bits 0 to 15 (j=0 to 15) of the shift register can be tested by a test instruction and written by an assignment instruction.
On a rising edge, set register bits 0 to 15
%SBRi.j to 0.
On a rising edge, shift a register bit to the left.
On a rising edge, shift a register bit to the right.
This is also true of a request to shift a bit to the right (bit 15 to bit 0) using instruction CD.
Bit 0 is lost.
If a 16-bit register is not adequate, it is possible, using the program, to cascade several registers.
___________________________________________________________________________
3/45
Programming
Example : Shift a bit to the left every second : bit 0 assumes the opposite state to bit 15.
Reversible programming
B
LDN %SBR0.15
ST %SBR0.0
BLK %SBR0
LD
CU
%S6
END_BLK
Non-reversible programming
LDN %SBR0.15
ST %SBR0.0
LD %S6
CU %SBR0
Special cases
• Effect of a cold restart : (%S0=1)
- sets all the bits of the register word to 0
• Effect of a warm restart : (%S1=1) has no effect on the bits of the register word.
___________________________________________________________________________
3/46
Numerical and special instructions
3
3.4-8 Step counter function blocks %SCi
A step counter is a series of steps to which actions can be assigned. Moving from one step to another depends on external or internal events. Each time that a step is active, the associated bit is set to 1. Only one step of a step counter can be active at a time.
B
Step counter function block
C haracteristics
Step counter number %SCi
Step counter bit %SCi.j
Reset input
(or instruction)
Increment input
(or instruction)
Decrement input
(or instruction)
Operation
CU input
CD input
N° inactive
R
CU
CD
0 to 7
Step counter bits 0 to 255 (j=0 to 255) can be tested by an LD logical operation and written by an assignment instruction.
On a rising edge, resets the step counter.
On a rising edge, increments the step counter by one step.
On a rising edge, decrements the step counter by one step.
___________________________________________________________________________
3/47
B
Programming
Example : To program the step counter 0 incremented by input %I0.2. It is reset to 0 by input %I0.3 or when it arrives at step 3.
Step 0 controls output %Q0.1, step 1 controls output %Q0.2 and step 2 controls output
%Q0.3.
Reversible programming
BLK %SC0
LD %SC0.3
OR %I0.3
R
LD
CU
%I0.2
END_BLK
LD %SC0.0
ST
LD
ST
%Q0.1
%SC0.1
%Q0.2
LD
ST
%SC0.2
%Q0.3
Non-reversible programming
LD
ST
LD
ST
LD %SC0.3
OR %I0.3
R %SC0
LD %I0.2
CU %SC0
LD
ST
%SC0.0
%Q0.1
%SC0.1
%Q0.2
%SC0.2
%Q0.3
Special cases
• Effect of a cold restart : (%S0=1)
- initializes the step counter
• Effect of a warm restart : (%S1=1) has no effect on the step counter.
___________________________________________________________________________
3/48
Numerical and special instructions
3
3.5
Communication between PLCs
Words %IW and %QW are used to exchange data between PLCs. The diagram below illustrates the exchange words for each PLC.
Base
PLC
Peer
PLC #2
Peer
PLC #3
Peer
PLC #4
B
%IW2.0
%IW2.1
%QW2.0
%QW2.1
%IW3.0
%IW3.1
%QW3.0
%QW3.1
%IW4.0
%IW4.1
%QW4.0
%QW4.1
<
<
<
%QW0.0
%QW0.1
>
%IW0.0
%IW0.1
%QW0.0
%QW0.1
%IW0.0
>
%IW0.1
%QW0.0
%QW0.1
>
%IW0.0
%IW0.1
These exchange words are updated automatically when the PLCs are in RUN mode.
The user program for each PLC is limited to :
• Writing to output words %QWi.j
• Reading input words %IWi.j
The update cycle for %IW/%QW words is synchronized with the PLC scan. System bit
%S70 is set to 1 when a complete update cycle has taken place. It is reset to 0 by the program or the terminal.
Bits %S71 / %S72 and word %SW71 are also used to control data exchanges (see
Section 5).
Note : Each PLC address is defined according to the position of the selector switch located on the PLC front panel, and this position is taken into account on every power-up.
___________________________________________________________________________
3/49
B
Example 1 : The base PLC transmits data to peer PLC #2 indicating the end of production (bit %M0=1). Once it has received this data, the peer PLC starts a materials handling machine by activating output %Q0.0.
Base PLC programming
LD %M0
ST %QW2.0:X0
Peer PLC programming
LD %IW0.0:X0
ST %Q0.0
Example 2 :
The base PLC transmits the current value of the counter 0 to peer PLC #4. When this current value is higher than the threshold contained in word %MW0, the peer PLC stops a machine by deactivating output %Q0.1.
Base PLC programming
LD 1
[%QW4.0:=%C0.V]
Peer PLC programming
LD [%IW0.0>%MW0]
STN %Q0.1
___________________________________________________________________________
3/50
4
4 Managing analog modules
4.1
Presentation
TSX 07 30/31 •• •• "base PLC" PLCs with discrete I/O (starting from version V3) are able to manage analog I/O modules.
There are three types of analog module in the TSX Nano offer :
• TSX AMN 4000/4001 analog I/O modules :
These modules communicate with the "base PLC" PLC via the I/O extension link.
They are managed via exchange words %IW and %QW.
• Input module :
These modules perform a voltage/frequency conversion which requires the use of input
%I0.0 in frequency meter mode on the PLC. A single input module can be connected by the PLC. The module is managed from the application program via system words
%SW100 and %SW101.
• Output module :
These modules perform a PWM/voltage conversion, by integrating the signal sent to output %Q0.0 of the PLC (pulse width modulation). A single module can be connected per PLC (base PLCs fitted with transistor outputs).
The module is managed from the application program via system words %SW102 and
%SW103.
B
___________________________________________________________________________
4/1
B
4.2
TSX AMN 4000/4001 analog modules
4.2-1 Operating principle of analog modules
Words %IW and %QW are used to exchange application data between a "base PLC"
PLC and TSX AMN 400 • analog modules.
This data, which is limited to four words (two in read mode, two in write mode) for both the "base PLC" PLC and analog modules, can be exchanged in both directions.
The figure below shows the words exchanged for each PLC.
Base
PLC
Analog module 1
Analog module 2
Analog module 3
%IW2.0
%IW2.1
%QW2.0
%QW2.1
%IW3.0
%IW3.1
%QW3.0
%QW3.1
%IW4.0
%IW4.1
%QW4.0
%QW4.1
<
<
<
>
%QW0.0
%QW0.1
%IW0.0
%IW0.1
>
%QW0.0
%QW0.1
%IW0.0
%IW0.1
>
%QW0.0
%QW0.1
%IW0.0
%IW0.1
These exchange words are automatically updated when the "base PLC" PLC is in RUN mode. For each PLC, the user program is limited to :
• writing to output words %QWi.j
• reading input words %IWi.j
The updating scan for %IW/%QW words is synchronous with the PLC scans. System bit %S70 is set to 1 when a complete scan has taken place. It is reset by the program or terminal.
Note
The address of each PLC is defined according to the position of the selector switch located on the PLC's front panel. Its position is taken into account whenever the PLC is powered up.
___________________________________________________________________________
4/2
Managing analog I/O 4
4.2-2 Programming analog modules
TSX AMN 400• analog I/O modules are programmed using 2 sets of exchange words :
%QWi.0, %QWi.1 and %IWi.0, %IWi.1.
Exchange word %QWi.0
This word is used to configure the analog input channels of a module.
It contains :
• the number of input channels used,
• the type of input for each channel,
• the type of filtering for each channel.
Chann. 2 Chann. 1 Chann. 0 Chann. 2 Chann. 1 Chann. 0 Conf.
B
Un
0
1
0
1
1
0
C0
0
1 fn0
0
1
0
1 fn1
0
0
1
1
In
0
0
1
1
Bit
0
1
C1
0
1
Number of input channels used
None
Channel 0
Channel 0 and channel 1
Channel 0, channel 1 and channel 2
Type of input for channel n
Voltage input +/-10 V
Voltage input 0..10 V
Current input 0..20 mA
Current input 4..20 mA
Type of filter for channel n (digital filter of the 1st order)
Hard filtering
75 ms
300 ms
1.5 s ns : not significant
___________________________________________________________________________
4/3
B
Exchange word %QWi.1
This 16-bit word contains the value of analog output 0 in a module.
Bit n° x0 to x14 x15
Meaning
Value of output 0 coded on 15 bits
Sign bit
Exchange word %IWi.0
This 16-bit word contains the value of analog input 0 and the module status.
Bit n° x0 to x10 x11 x12 = 1 x13 = 1 x14 = 1 x15 = 1
Meaning
Value of input 0 coded on 11 bits
Sign bit of channel 0
Self-calibration fault
Stop overshoot channel 0
Stop overshoot channel 1
Stop overshoot channel 2
Exchange word %IWi.1
This 16-bit word either contains the value of analog input 1 or the values of analog inputs
1 and 2 in a module.
Bit n° Meaning when inputs
0 and 1 are configured
0 to 6
7
8 to 14
15
Value of input 1 coded on 15 bits
Sign bit of channel 1
Meaning when inputs
0, 1 and 2 are configured
Value of input 1 coded on 7 bits
Sign bit of channel 1
Value of input 2 coded on 7 bits
Sign bit of channel 2
___________________________________________________________________________
4/4
Managing analog I/O 4
Range of values of input modules
Type of input
-10 V / +10 V
0 / 10 V
0 / 20 mA
4 / 20 mA
Range of values
7 bits + sign 11 bits + sign
-125 ..125
0 .. 125
-2000 .. 2000
0 .. 2000
0 .. 125
25 .. 125
0 .. 2000
0 .. 2000
Overshoot detection threshold for low and high stops
+/- 2.5% of the full scale
+/- 2.5% of the full scale
+/- 2.5% of the full scale
+/- 2.5% of the full scale
All stop overshoot faults are signaled by setting one of the status bits in word %IWi.0
of the module to 1. For the 4/20 mA range, a fault is declared if the current is less than
3.5 mA, but the module is capable of feeding back values up to -0.5 mA.
B
Range of values of output modules
Type of output
-10 V / +10 V
0 / 10 V
0 / 20 mA
4 / 20 mA
Values written in word %QWi.1
-2000 .. 2000
0 .. 2000
0 .. 2000
400 .. 2000
Max. overshoot values of low and high stops
+/- 2.5% of the full scale
+/- 2.5% of the full scale
+/- 2.5% of the full scale
+/- 2.5% of the full scale
If an internal fault occurs, the output is set to fallback mode by the module (0 V for the voltage output, 0 mA for the current output, whatever the range).
Warning
When the PLC is set to STOP, the analog output is maintained at the value it had before the STOP. There is no automatic fallback in this case.
4.2-3 Using %IW words in the user program
In order for %IW exchange words to be manipulated by PL7-07 instructions, they must be converted to a 15-bit + sign format.
The table overleaf shows the conversion operations to be inserted in the user program :
___________________________________________________________________________
4/5
B
1
0
1
Value of the 7-bit word 11-bit word Channel n° sign bit + sign + sign
0 %IWi.0
0
1
%IWi.1
%IWi.1
%IWi.1
%IWi.1
%IWi.0
1
1
2
2
Conversion to 15-bit
+ sign format
%MW0:= %IWi.0 AND 16#0FFF
%MW0:= %IWi.0 OR 16#F000
%MW0:= %IWi.1 AND 16#00FF
%MW0:= %IWi.1 AND 16#00FF
%MW1:= %MW0 OR 16#FF00
%MW0:= %IWi.1 AND 16#FF00
%MW1:= ROR (%MW0,8)
%MW0:= %IWi.1 AND 16#FF00
%MW1:= ROR (%MW0,8)
%MW2:= %MW1 OR 16#FF00
Note :
Internal words %MW0, %MW1 and %MW2 are used as examples of logging variables in the conversion operations.
Example of a user program
Compares the analog value of channel 2 in module 1, all the inputs of which are configured, with a threshold contained in word %MW100 (hexadecimal value 16#05C4).
Output Q0.1 in the "base PLC" PLC is set to 1 when the value is equal to or greater than the threshold.
LD 1
[%MW100 := 16#05C4]
LD 1
[%MW0 := %IW2.1 AND 16#FF00]
LD 1
[%MW1 := ROR ( %MW0, 8 )]
LD %IW2.1:X15
[%MW2 := %MW1 OR 16#FF00]
LDN %IW2.1:X15
[%MW2 := %MW1]
LD [%MW0 >= %MW100]
ST %Q0.1
4.2-4 Diagnostics of communication status with analog modules
These diagnostics are identical to those carried out on a peer PLC and are indicated by word %SW71 (see Part B Section 6.2-2).
___________________________________________________________________________
4/6
Managing analog I/O 4
4.3
Analog input modules TSX ASN •••
4.3-1 Configuring analog inputs
Using input %I0.0 in frequency meter mode to connect the analog input module requires the following parameter settings :
B
• Fast counter type :
• Max. frequency : to be set to Frequency to use the input in frequency meter mode to be set to 10 KHz
4.3-2 Programming analog inputs
The input module is programmed using the two system words %SW100 and %SW101 and by enabling the fast counter %FC (see example in Section 4.4-4).
• %SW100 : analog input functions command word
• %SW101 : acquired value of analog input
The operating mode is selected by writing, via the program, word %SW100 and the acquired value of the analog input can be read in word %SW101.
These two words are reset to zero by the system on a cold restart.
Depending on the choice of operating mode, the system offers a scaling function. This scaling is within a range of 0 to +10 000 for unipolar modules (4/20mA and 0/10V input modules) and -10 000 to +10 000 for bipolar modules (-10/+10V).
%SW100 Operation
0
1
Disable analog input function on %I0.0
Operate without scaling
Value range of %SW101
0
2
3
4
5
Scale for unipolar range
(4/20mA, 0/10V)
Scale for bipolar range
(-10/+10V)
Scale for unipolar range
(4/20mA, 0/10V)
Scale for bipolar range
(-10/+10V)
0...1 000
Period of measurement 125 ms
0...10 000
Period of measurement 125 ms
-10 000 ... +10 000
Period of measurement 125 ms
0...10 000
Period of measurement 500 ms
-10 000 ... +10 000
Period of measurement 500 ms
___________________________________________________________________________
4/7
B
The raw or scaled analog value is available in %SW101 if %SW100 is written with a value of 1 to 5. The validity of this measurement can be checked using system bit
%SW111:X3 (set to 1 by the system if the measurement is valid).
If system bit %SW111:X3 is set to zero by the application, an analog acquisition function is launched, measurement acquisitions continue to be made when the PLC is in STOP.
The raw frequency measurement remains available in word %FC,V associated with input %I0.0 but it is a measurement which is a function of the measurement period (eg : the full scale 8KHz will give 1000 for 125ms and 4000 for 500ms). It is therefore recommended, to simplify the application program, that system word %SW101 is used by preference.
Note
The period of measurement can be modified during operation by rewriting word
%SW100 but this mode of use is not recommended because the first measurement after the change in period may be wrong.
Using analog input modules on V2 PLCs
It is possible to use analog input modules on TSX 07 2 iii V2 PLCs, according to the following rules :
• use of input %I0.0 as frequency meter (enabling of operation by instruction IN %FC)
• configuration of the measurement period by the application writing bit %SW111:X2.
%SW111:X2=0 measurement every second (default)
%SW111:X2=1 measurement every 100 ms
• the image of the analog input value is available in object %FC,V; the value is interpreted in the following way :
Range
0/10V
4/20 mA
-10/+10V
Formula
U(V) = 1.25 x (%FC,V x 10 -3 )
I(mA) =2 x [(%FC,V x 10 -3 ) + 2]
U(V) = 2.5 x [(%FC,V x 10
-3
) - 4]
Note
In the case of a 4/20 mA module, the frequency is zero between 0 and 4 mA.
___________________________________________________________________________
4/8
Managing analog I/O 4
4.3-3 Response time of analog inputs
The response time IRT in acquiring an analog input, between the actual variation of the electrical value at the module terminals and the correspondence in word %SW101 of the measured value, depends essentially on the measurement period selected
(125/500 ms) and less so on the PLC scan time. The variation of the electrical value has a negligible effect on the response time.
• For acquisition at a period of 125 ms : IRT is less than 500 ms.
• For acquisition at a period of 500 ms : IRT is less than 1.2 s.
Note
A change in the operating mode (changing %SW100) is taken into account by the system on each scan or immediately on a rising edge of "IN %FC". The measurements are linked in realtime one after another at the chosen period (125 ms or 500 ms). The result of the last measurement taken is transmitted at the beginning of the PLC scan to %SW101. The value of this word does not change during the PLC scan.
4.3-4 Example of analog input programming
(* ENABLE ANALOG INPUT FUNCTIONS *)
LD 1 (* ANA INPUT MODE 0..1000 ON 125 MS *)
[%SW100 := 1]
BLK %FC
(* SELECTED MODE TAKEN INTO ACCOUNT *)
LD 1
IN
END_BLK
(* ACQUISITION OF MEASUREMENT*)
LD %SW111:X3 (* MEASUREMENT VALID *)
[%MW1 := %SW101]
R %SW111:X3
S %M1
(* MEMO MEASUREMENT *)
(* MEASUREMENT ACKNOWLEDGED*)
(* MEASUREMENT INDEX VALID *)
(* USE OF THE MEASUREMENT, DEPENDING ON THE APPLICATION *)
LD %M1
...
B
___________________________________________________________________________
4/9
B
4.3-5 Characteristics of analog inputs
Type Input value
4/20mA 4 m A
12mA
20mA
0/10V 0V
10V
-10/+10V -10V
+10V
%SW101 value Resolution (1) %SW101 value Resolution (1) period 125ms /increment period 500ms /increment
0
5000
10000
0
10000
-10000
10000
16µA/10 lsb
10mV/10 lsb
20mV/10 lsb
0
5000
10000
0
10000
-10000
10000
The values of %SW101 are given for the operating mode with scaling.
4µA/2.5 lsb
2.5mV/ 2.5 lsb
5mV/ 2.5 lsb
(1) Resolution : Minimum value of the input variation to obtain a measurement variation. The measurement variation varies in "steps" called increments.
___________________________________________________________________________
4/10
Managing analog I/O 4
4.4
Analog output modules TSX AEN •••
4.4-1 Configuring analog outputs
Using output %Q0.0 to connect the analog output requires the following parameter settings :
• Output %Q0.0 :
• Time base :
• Preset : to be used for pulse width modulation %PWM.
to be set to 0.1 ms.
must be set to 249 so that operation remains enabled after a warm restart.
Adjustment of this parameter is only appropriate for
"base PLC" TSX Nano PLCs (V3.0).
B
4.4-2 Programming analog outputs
The output module is programmed using the two system words %SW102 and %SW103 and by enabling output %PWM (see example in Section 4.3-4).
• %SW102 : analog output functions command/status word
• %SW103 : value of analog output to be generated
The operating mode is selected by writing, by the application program, word %SW102 and the value of the analog output to be generated must be written in word %SW103.
These two words are reset to zero by the system on a cold restart.
Depending on the choice of operating mode, the system offers a scaling function. This scaling is within a range of 0 to +10 000 for unipolar modules (4/20mA and 0/10V input modules) and -10 000 to +10 000 for bipolar modules (-10/+10V).
___________________________________________________________________________
4/11
B
%SW102 Operation
0 Disable analog output function on %Q0.0
1
2
Operate without scaling
Scale for unipolar range
(4/20mA, 0/10V)
3 Scale for bipolar range
(-10/+10V)
Value range of %SW103
Not used
5...249
0...10 000
-10 000 ... +10 000
The effective resolution of the analog outputs is 245 points.
If the value written in %SW103 is less than the minimum value (eg : less than 0 in unipolar mode), the minimum value in the range will be applied to the output module.
If the value written in %SW103 is greater than the maximum value (eg : greater than
10000 in unipolar mode), the maximum value in the range will be applied to the output module.
These two types of programming error are not indicated to the application.
Important
In the fallback conditions of discrete outputs, the PWM is no longer generated and a signal is no longer sent to the output modules.
From this, the bipolar modules take their lowest value ( -10V).
This fallback mode must be taken into account by the user.
4.4-3 Response time of analog outputs
The response time ORT of an analog output, between writing the setpoint in word
%SW103 and reaching the voltage (and/or current) corresponding to the module terminals, depends on the amplitude of the variation and the PLC scan time.
• For a full scale variation, ORT is less than 500 ms.
The shorter the PLC scan time and the lower the setpoint variation, the shorter the response time will be. For a scan time of 10 ms and a variation of1/10th of the full scale, this response time will go down to approximately 50 ms.
Note
A change in the operating mode (changing %SW102) is taken into account on a rising edge of input IN of the PWM (execution of the instruction "IN %PWM") or if setpoint %SW103 is changed.
A change of setpoint (%SW103) is taken into account by the system on each scan and becomes effective from the next application program scan (Max. delay of 3ms).
___________________________________________________________________________
4/12
Managing analog I/O 4
4.4-4 Example of analog output programming
(* ENABLE ANALOG OUTPUT FUNCTION *)
LD 1
[%SW102 := 1]
IN %PWM
(* ANA OUTPUT RAW MODE 5..249 *)
(* MODE TAKEN INTO ACCOUNT *)
(* GENERATION OF SETPOINT IN PWM *)
....
(* SETP. CALC. DEPENDING ON APPLICATION *)
LD 1
[%SW103 := %MW0] (* APPLICATION OUTPUT SETPOINT *)
B
4.4-5 Characteristics of analog outputs
Type Value %SW103 value to be generated to be written by at output application program
Resolution output module
65µA 4/20mA 4 m A
12mA
20mA
0/10V 0V
5V
10V
-10/+10V -10V
0V
+10V
0
5000
10000
0
5000
10000
-10000
0
10000
40mV
81mV lsb resolution (1)
%SW103
40
40
81
Values of %SW103 are given for the operating mode with scaling.
(1) LSB resolution : Minimum variation to be applied to %SW103 to obtain a variation of the output module equal to its resolution.
___________________________________________________________________________
4/13
B
___________________________________________________________________________
4/14
5 Clock functions
5.1
Introduction
TSX 07 •1 16/24 •• PLCs have a time-of-day clock which is used to perform three functions :
• Schedule blocks are used to control actions at predefined or calculated times.
• Time/date stamping is used to date events and measure duration.
The TSX Nano schedule blocks and the time-of-day clock can be accessed from the
TSX PLC operations menu. Additionally, the time-of-day clock can be set by the program. They continue to operate for up to 30 days when the PLC is switched off if the battery has been charged for at least 6 consecutive hours before the PLC is switched off.
The time-of-day clock has a 24-hour format and takes leap years into account.
5.2
Schedule blocks
The schedule block is used to control actions at a particular predefined time.
A maximum of 16 schedule blocks can be used, each one performing this function.
These blocks do not require any program entry. They can be configured (see operating modes, Part C).
5.2-1 Characteristics
Schedule block number
Output
RTC : n n=0 to 15
Start date
End date
Day
Start hour
End hour
Q :
DD:MMM
DD:MMM
Output assignment is activated by schedule block : %Mi or %Qj.k.
This output is set to 1 when the current date and time are between the setting of the start of the active period and the setting of the end of the active period.
Shows the day from 1 to 31 and the month Jan to Dec of the start of activation of schedule block.
Shows the day from 1 to 31 and the month Jan to Dec of the end of activation of schedule block.
MTWTFSS Shows the days of activation in the week
(M : Monday to S : Sunday) hh:mm Shows in hours (0 to 23) and minutes (0 to 59) the start of activation of schedule block.
hh:mm Shows in hours (0 to 23) and minutes (0 to 59) the end of activation of schedule block.
___________________________________________________________________________
5/1
B
B
The bits of system word %SW114 enable (bit set to 1) or disable (bit set to 0) the operation of each of the function blocks.
%SW114
Schedule block #15 Schedule block #0
By default (or after a cold restart) all bits of this system word are set to 1. Use of these
bits by the program is optional.
Comments :
• If the same output (%Mi or %Qj.k) is assigned by several blocks, it is the "OR" of the results of each of the blocks which is finally assigned to this object (which means it is possible to have several "operating ranges" for the same output).
Example : Configuration of a schedule block, for summer month spray program.
• RTC 6 : schedule block #6
• Q : %Q0.2 : output activated by the schedule block
• 21 -Jun -> 21-Sep : period of activation
• M•W•F•• : activation days (Monday, Wednesday and Friday)
• 21 : 00 - 22 : 00 : scheduled activation period
RTC:6 Q: %Q0.2
21-Jun --> 21-Sep
M•W•F••
21 : 00 - 22 : 00
LD %I0.1
ST %SW114:X6
21 June
M W F M W F M W F
In this example the user can disable the schedule block using a switch or a humidity detector wired to input %I0.1.
Note :
It is important to check the state of bit %S51 which shows any schedule block errors.
5.2-2 Time dating by program
Date and time are both available in system words %SW50 to %SW53 (see Section 6.2).
It is therefore possible to perform time and date stamping by the PLC program by making arithmetic comparisons between the current date and time and the immediate values or words %MWi (or %KWi) which can contain setpoints.
___________________________________________________________________________
5/2
Clock functions
5
5.3
Time/date stamping
System words %SW50 to %SW53 (see Section 6.2) contain the current date and time in BCD format, which is useful for display on or transmission to a peripheral device.
These system words can be used to store the date and time of an event.
To date an event it is sufficient to use assignment operations, to transfer the contents of system words to internal words and then process these internal words (for example, transmission to display unit by EXCH instruction).
Example :
B
...
LDR %I0.1
[%MW12:4 :=%SW50:4]
...
Once an event is detected, the word table contains :
Coding : Most significant Least significant Example : Monday 19 April 1994 byte byte In hex 13H, 40min, 30s
%MW12 Second
%MW13 Hour
Day of the week(1) 3000
Minute 1340
30s, 0=Monday
13H, 40min
%MW14 Month
%MW15 Century
Day
Year
0419
1994
4=April, 19
1994
(1) Where 0=Monday, 1=Tuesday, 2=Wednesday, 3=Thursday, 4=Friday, 5=Saturday, 6=Sunday
Reading the date and time of the last stop using system words
System words %SW54 to %SW57 (see Section 6.2) contain the date and time of the last stop, and word %SW58 contains the code showing the cause of the last stop, in
BCD format.
___________________________________________________________________________
5/3
B
5.4
Setting the date and time
5.4-1 Setting the date and time using the terminal
When the programming terminal is in TSX (online) mode, the date and time can be updated quickly and easily (see operating modes, Part C).
5.4-2 Updating date and time using system words
System words offer 2 other possibilities for updating the date and time :
Updating using system words %SW50 to %SW53
(see Section 6.2)
For this, bit %S50 must be set to 1. This bit :
• cancels the update of words %SW50 to %SW53 via the internal clock
• transmits the values written in words %SW50 to %SW53 to the internal clock.
LD
R
%S50
%S50
LDR %I0.1
[%SW50:=%MW10]
[%SW51:=%MW11]
[%SW52:=%MW12]
[%SW53:=%MW13]
S %S50
Words %MW10 to %MW13 will contain the new date and time in BCD format and will correspond to the coding of words %SW50 to 53.
The word table must contain the new date and time.
Coding : Most significant Least significant Example : Monday 19 April 1994 byte
%MW10 Second byte
Day of the week (1)
Hex
3000
13H 40min 30s
30s, 0=Monday
%MW11 Hour
%MW12 Month
%MW13 Century
Minute
Day
Year
1340
0419
1994
13H, 40min
4=April, 19
1994
(1) Where 0=Mon., 1=Tues., 2=Wednes., 3=Thurs., 4=Fri., 5=Satur., 6=Sun.
To ensure that the realtime clock is updated on a TSX Nano V1, V2 or V3.0 at the changeover to the year 2000, the PLC must be powered up during this time. It is however, possible to update the realtime clock via the program.
To do this, add the following to the application :
LD [%SW53]=16#1900
ST %S50
[%SW53:=16#2000]
___________________________________________________________________________
5/4
Clock functions
5
Updating using system word %SW59
Another method of updating is to use enable bit %S59 and adjustment word %SW59.
Setting bit %S59 to 1 enables adjustment of the current date and time by word %SW59.
Word %SW59 is described in Section 6.2. It increments or decrements each of the date and time components on a rising edge.
Example : A front panel is created in order to modify the hour, minutes and seconds of the internal clock.
Hours
Minutes
Seconds
LD
ST
LD
%M0
%S59
%I0.2
ANDR %I0.0
ST
LD
%SW59:X3
%I0.2
ANDR %I0.1
ST %SW59:X11
LD %I0.3
ANDR %I0.0
ST %SW59:X2
LD %I0.3
ANDR %I0.1
ST %SW59:X10
LD %I0.4
ANDR %I0.0
ST %SW59:X1
LD %I0.4
ANDR %I0.1
ST %SW59:X9
(hour)
(minute)
(second)
• Inputs %I0.2, %I0.3 and %I0.4 are controlled by the Hours/Minutes/Seconds switch.
• Incrementation is performed by input %I0.0, pushbutton +.
• Decrementation is performed by input %I0.1, pushbutton -.
B
___________________________________________________________________________
5/5
B
___________________________________________________________________________
5/6
6 Role of system bits and words
6.1 System bits
6.1-1 List of system bits
Bit Function Init state Control
%S0 1 = cold restart (power return with 0 S or U->S loss of data)
%S1 1 = warm restart (power return without 0 S or U->S loss of data)
%S4, %S5 Time base 10ms, 100ms - S
%S6, %S7 Time base 1s, 1min - S
%S8 0 = outputs saved when the PLC stops 1 U
%S9 1 = PLC outputs reset to zero if the 0 U
PLC is running
%S10 0 = I/O fault 1 S
%S11 1 = watchdog overflow - S
%S13 1 = first scan after setting to RUN 1 S
%S17 1 = overflow of an unsigned arithmetic 0 S - > U operation or rotate shift
%S18 1 = arithmetic overflow or error 0 S - > U
%S19 1 = scan period overshoot 0 S - > U
%S20 1 = index overflow 0 S - > U
%S21 1 = Grafcet initialization : sets the steps 0 U - > S to 0 and the initial steps to 1
%S22 1 = reset Grafcet to zero 0 U - > S
%S23 1 = enable Grafcet presetting. 0 U - > S
If held at 1, Grafcet freezes
%S49 1 = request to reset every 10s 0 U - > S transistor outputs which have been tripped by overcurrent or short-circuit
%S50 1 = set schedule block (RTC) 0 U
%S51 1 = schedule block not initialized or error 0 S
0 = schedule block are set
%S59 1 = adjust current date 0 U
%S69 1 = display internal bits 0 U
%S70 1 = update exchange words %IW/OW on 0 S extension. Process Modbus request
%S71 1 = exchange via extension link 0 S
%S72 0 = scanning of peer PLCs 0 U
%S100 State of /DPT - S
%S118 1 = base PLC fault 0 S
%S119 1 = peer PLC fault 0 S
S = controlled by the system, U = controlled by the user, U->S = set to 1 by the user, reset to 0 by the system, S->U = set to 1 by the system, reset to 0 by the user.
B
6/1
B
6.1-2 Detailed description of system bits
TSX 07 PLCs have system bits %Si which indicate the status of the PLC or enable the user to intervene in its operation.
These bits can be tested in the user program in order to detect any operating event which requires special processing. Some of them must be reset to their initial or normal state by the program. However, the system bits which have been reset to their initial or normal state by the system must not be reset by the program or the terminal.
System Function Description bits
%S0 Cold Normally at 0. It is set to 1 by : restart • A power return with loss of data (battery fault)
• The user program
• The terminal (in the Data editor).
This bit is set to 1 during the first complete scan. It is reset to 0 before the next scan.
For operating information : see Part A, Section 7.1.
%S1 Warm Normally at 0. It is reset to 1 by : restart • A power return with saving of data
• The user program
• The terminal (in the Data editor).
It is reset to 0 by the system at the end of the first complete scan and before updating of the outputs.
For operating information : see Part A, Section 7.1.
Time Changes in the status of these bits are controlled by an bases internal clock. They are not synchronized with
%S4 10ms the PLC scan.
%S5 100ms
%S6 1s Example : %S4
%S7 1min
5ms 5ms
6/2
Role of system bits and words 6
System Function Description bits
%S8 Output Initially at 1, it can be set to 0 by the program freeze or by the terminal (in the Data editor) :
• At state 1 PLC outputs are set to 0 if the program is not being executed normally or if the PLC changes to STOP
• At state 0 PLC outputs are kept in their existing state if a program operation fault occurs or if the PLC changes to STOP.
%S9 Reset Normally at 0. It can be set to 1 by the program outputs or by the terminal (in the Data editor) :
• At state 1 outputs are forced to 0 when the PLC is in RUN mode
• At state 0 outputs are updated normally.
%S10 I/O Normally at 1. It is set to 0 when a I/O fault is detected on fault the base PLC or the peer PLC (configuration fault, exchange fault, hardware fault). Bits %S118 and %S119 indicate in which PLC the fault is and words %SW118 and %SW119 detail the nature of the fault (see Section 5.2).
Bit %S10 is reset to 1 when the fault disappears.
%S11 Watch- Normally at 0, it is set to 1 by the system when the program execution dog time (scan time) exceeds the maximum scan time (software watchdog).
overflow Watchdog overflow causes the PLC to change to STOP.
B
%S13 First Normally at 0, it is set to 1 by the system during the first scan scan after the PLC has been changed to RUN.
%S17 Carry Normally at 0, it is set to 1 by the system : overflow • In the case of carry overflow during a non-signed arithmetic operation (remainder)
• During a rotate or shift operation it indicates the output of a bit at
1. It must be tested by the user program after each operation where there is a risk of overflow, then reset to 0 by the user if an overflow occurs.
6/3
B
System Function Description bits
%S18 Arithmetic Normally at 0. It is set to 1 in the case of an overflow overflow when a 16 bit operation is performed, that is : or error • A result greater than + 32767 or less than - 32768
• Division by 0
• The square root of a negative number
• BTI or ITB conversion not significant : BCD value out of limits
It must be tested by the user program after each operation where there is a risk of an overflow, then reset to 0 by the user if an overflow occurs.
%S19 Scan Normally at 0, this bit is set to 1 by the system in the event period of a scan period overrun (scan time greater than overrun than the period defined by the user at configuration or
(periodic programmed in %SW0).
scan) This bit is reset to 0 by the user.
%S20 Index Normally at 0, it is set to 1 when the address of the overflow indexed object becomes less than 0 or more than the maximum size of an object.
It must be tested by the user program after each operation where there is a risk of overflow, then reset to 0 if an overflow occurs.
%S21 GRAFCET Normally at 0, it is set to 1 by : initialization • A cold restart, %S0=1
• The user program, in the preprocessing program part only, using a Set Instruction (S %S21) or a set coil -(S)- %S21.
• The terminal.
At state 1, it causes GRAFCET initialization. Active steps are deactivated and initial steps are activated.
It is reset to 0 by the system after GRAFCET initialization.
6/4
Role of system bits and words 6
System Function Description bits
%S22 GRAFCET Normally at 0, it can only be set to 1 by the program in reset pre-processing.
At state 1 it causes the active steps of the entire GRAFCET to be deactivated. It is reset to 0 by the system at the start of the execution of the sequential processing.
%S23 Preset Normally at 0, it can only be set to 1 by the user program and freeze in the pre-processing program module.
GRAFCET At state 1, it validates the presetting of the GRAFCET chart.
Maintaining this bit at 1 freezes the GRAFCET (freezes the chart).
It is reset to 0 by the system at the start of the execution of the sequential processing to ensure that the GRAFCET chart moves on from the frozen situation.
%S49 Reactivate Normally at 0, it is set to 1 by the user to request a reactivation every transistor 10 s of the transistor outputs which have been tripped by an outputs overcurrent or short-circuit, the first attempt occurring 10 s after the outputs have been tripped.
%S50 Updating Normally at 0, this bit can be set to 1 or to 0 by the program the date or the terminal.
and time • At 0, the date and time can be read.
using words • At 1, the date and time can be updated.
%SW50 to 53
%S51 Time-of-day • At 0, the date and time are set.
clock status • At 1, the date and time must be set by the user.
When this bit is set to 1, the time of day clock data is not valid. The date and time may never have been configured, or the battery may be low.
%S59 Updating Normally at 0, this bit can be set to 1 or to 0 by the the date program or the terminal.
and time • At 0, the date and time remain unchanged.
using word • At 1, the date and time are incremented or decremented
%SW59 according to the control bits set in %SW59.
%S69 Displaying Normally at 0, this bit can be set to 1 or to 0 by the internal program or the terminal.
bits on the • At 0 : the PLC LEDs display the status of the I/O front panel • At 1 : the status of 8 internal bits (TSX 07 10, 14 and 16 I/O) or 16 of the PLC internal bits (TSX 07 20 and 24 I/O) is displayed on the PLC LEDs
(see Part A, Section 1.9).
The LED farthest to the right flashes to indicate that displaying internal bits has been selected.
B
6/5
B
System Function Description bits
%S70 Update For the base PLC, this bit is set to 1 as soon as the PLC of has performed a complete cycle of transmitting exchange exchange words %IW/%QW to the peer PLCs.
words For each peer PLC, this bit is set to 1 as soon as the peer PLC has received and transmitted the exchange words with the base PLC.
This bit is reset to 0 by the program or by the terminal.
Process This bit is set to 1 when a Modbus request is processed.
Modbus It can be used by the operator.
request This bit is reset to zero by the program or terminal.
%S71 Exchange Initially set to 0. Set to 1 until an exchange via the via extension link is detected.
extension This bit is set to 0 when no exchange is performed via link the extension link. Word %SW71 of the base PLC shows the list and status of the available extensions.
%S72 Scanning Applies only to PLCs version 2.2 or lower.
of peer Normally at 0. Can be set to 1 by the program or the terminal.
PLCs • At 0 the base PLC communicates with the peer PLCs
• At 1 communication is disabled
%S100 State of Shows the state of INL/DPT strap on the terminal port :
/DPT signal • No strap : UNI-TELWAY master protocol (%S100 = 0)
• Strap present : (/DPT at 0V) protocol defined by the application
configuration (%S100 = 1)
%S118 Base Normally at 0. It is set to 1 when an I/O fault is detected
PLC on the base PLC. Word %SW118 determines the nature fault of the fault.
Bit %S118 is reset to 0 when the fault disappears.
%S119 Peer Normally at 0. It is set to 1 when an I/O fault is detected
PLC on the I/O extension. Word %SW119 determines the fault nature of the fault.
Bit %S119 is reset to 0 when the fault disappears.
6/6
Role of system bits and words 6
6.2 System words
6.2-1 List of system words
Word Function Control
%SW0 Value of PLC scan period (periodic task) U
%SW11 Software watchdog time S
%SW14 UNITELWAY time-out S and U
%SW15 PLC version and UI S
%SW30 Time of last PLC scan cycle S
%SW31 Maximum time of PLC scan cycle S
%SW32 Minimum time of PLC scan cycle S
%SW50 Schedule block (RTC) function : words containing current date and S and U
%SW51 time values (in BCD)
%SW52 %SW50 = seconds and day of the week
%SW53 %SW51 = hour and minute
%SW52 = month and day
%SW53 = century and year
%SW54 Schedule block (RTC) function : words containing the data and time S
%SW55 of the last power failure or PLC stop (in BCD)
%SW56 %SW54 = seconds and fault code
%SW57 %SW55 = hour and minute
%SW56 = month and day
%SW57 = century and year
%SW58 Identification code of last stop S
%SW59 Adjust current date U
%SW67 Value of Modbus end of frame character in ASCII mode U
%SW68 End of frame character value (reception) in ASCII mode (TER port) U
%SW69 EXCH block error code S
%SW70 Function and type of TSX 07 PLC S
%SW71 Devices on extension link S
%SW76 Timer 1 ms S
%SW77 Timer 1 ms S
%SW78 Timer 1 ms S
%SW79 Timer 1 ms S
%SW100 Analog module input function command word U
%SW101 Value of acquired analog module input S
%SW102 Analog module output function command word U
%SW103 Value of analog module output to be generated U
%SW110 Read counter value S
%SW111 Fast counting functions S and U
%SW112 Value of potentiometer 0 S
6/7
B
B
Word Function Control
%SW113 Value of potentiometer 1 S
%SW114 Enable schedule blocks (RTC) U
%SW118 Base PLC status word S
%SW119 Peer PLC status word S
S = controlled by the system,
U = controlled by the user.
6/8
Role of system bits and words 6
6.2-2 Detailed description of system words
TSX Nano PLCs use the following system words :
System Function Description words
%SW0 PLC scan Modifies PLC scan period defined at configuration via the user period program or the terminal (in the Data editor).
%SW11 Watchdog Reads watchdog time (150ms).
time
%SW14 Unitelway Is used to modify the value of the UNITELWAY time-out, via the time-out user program (see part F Section 1.6)
%SW15 PLC version From versions V3.1 upwards, is used to show the version of and UI the PLC (most significant byte) and its UI (least significant byte).
Eg : 0x000 : version before V3.1
0x3119 : PLC is version V3.1 and UI : 25
%SW30 Last Shows execution time of the last PLC scan cycle scan (in ms).
time (1)
%SW31 Max Shows execution time of the longest PLC scan cycle scan since the last cold start (in ms).
time (1)
%SW32 Min Shows execution time of shortest PLC scan cycle scan since the last cold start (in ms).
time (1)
%SW50 Schedule System words containing current values of the date and
%SW51 block time (in BCD) :
%SW52 function %SW50 : SSXN Seconds and day of the week with
%SW53 (N= 0 for Monday to 6 for Sunday)
%SW51 : HHMM Hour and Minute
%SW52 : MMDD Month and Day
%SW53 : CCYY Century and Year.
These words are controlled by the system when bit %S50 is at
0. These words can be written by the user program or by the terminal when bit %S50 is set to 1.
%SW54 Schedule System words containing the date and time of the last
%SW55 block power failure or PLC stop (in BCD) :
%SW56 function %SW54 : Seconds and day of the week
%SW57 %SW55 : Hour and minute
%SW56 : Month and day
%SW57 : Century and year.
(1) This time corresponds to the time elapsed between the start (acquisition of inputs) and the end (update of outputs) of a scan cycle.
B
6/9
B
System Function Description words
%SW58 Code of Displays code giving cause of last stop : last 1= Terminal switch changed from RUN to STOP stop 2= Stop at software fault (PLC scan overshoot)
4= Power outage
5= Stop at hardware fault
%SW59 Adjust Contains two sets of 8 bits to adjust current date.
current The operation is always performed on rising edge of date the bit. This word is enabled by bit %S59.
Increment Decrement Parameter bit 0 bit 8 Day of the week bit 1 bit 9 Seconds bit 2 bit 10 Minutes bit 3 bit 11 Hours bit 4 bit 12 Days bit 5 bit 13 Months bit 6 bit 14 Years bit 7 bit 15 Centuries
%SW67 End of Modbus Is used to set 'LF' at the end of the Modbus frame in ASCII mode.
frame This word is written at 16#000A by the system on a cold start. The user can modify this word using the program or Adjust mode when the Master uses an end of frame character other than 16#000A.
%SW68 End of Is used to set the parameters for the value of the end of frame byte
Reception frame in ASCII mode. Reception ends as soon as this is received.
ASCII mode The default value is 16#000D.
%SW69 EXCH block If an error occurs when using the EXCH block, output bits error code %MSG.D and %MSG.E change to 1. This system word contains the error code. The possible values are as follows :
0 : No error, exchange correct
1 : Transmission buffer too large
2 : Transmission buffer too small
3 : Table too small
4 : Incorrect Unitelway address (Unitelway mode only)
5 : Time - out elapsed (Unitelway mode only)
6 : Transmission error (Unitelway mode only)
7 : Bad ASCII command (ASCII mode only)
8 : Not used
9 : Reception error (ASCII mode only)
10 : Table %KWi prohibited.
This word is set to 0 every time the EXCH block is used.
6/10
Role of system bits and words 6
System Function Description words
%SW70 Address Contains the following information : and type • bit 0 : 0=TSX 07 3L ••28 model of PLC 1= other models
• bit 2 : 1=presence of schedule block (RTC)
• bit 4 bit 3 PLC type TSX 07
0 0 TSX Nano with 6 inputs/ 4 outputs (10 I/O)
0 1 TSX Nano with 9 inputs/ 7 outputs (16 I/O)
1 0 TSX Nano with 14 inputs/ 10 outputs (24 I/O)
1 1 TSX Nano with AC inputs (16 I/O)
• bits 7, 6 and 5 : address of PLC (copied from address
code selector).
If there is an I/O extension :
• bits 12 and 11 : I/O extension type (same coding as
bits 3 and 4)
• bits 13 : 1 = there is an I/O extension
The unused bits are at 0.
%SW71 Devices Shows the communication status of each extension on with the base PLC : extension bit 1 : I/O extension link bit 2 : peer PLC or analog module #2 bit 3 : peer PLC or analog module #3 bit 4 : peer PLC or analog module #4
Bit at 0 if there is no extension or peer, no power, or a fault.
Bit at 1 if there is an extension and exchange with the base PLC.
%SW76 Downcounting These 4 words serve as 1 ms timers.
to Words They are decremented individually by the system every
%SW78 1 ms millisecond if they have a positive value. This gives 4 downcounters downcounting in milliseconds, which is equal to an operating range of 1 ms to 32767 ms. Setting bit 15 to 1 can be used to stop decrementation.
%SW100 Analog Analog input functions command word.
input Value : 0 Analog input not valid
Value : 1 Operation without scaling
Value : 2 Unipolar scale range (period 125ms)
Value : 3 Bipolar scale range (period 125ms)
Value : 4 Unipolar scale range (period 500ms)
Value : 5 Bipolar scale range (period 500ms)
Writing this word is the responsibility of the application program.
B
6/11
B
System Function Description words
%SW101 Analog Word containing the value of the acquired analog input. The value input range depends on the selection of operation made in %SW100.
%SW100=0 %SW101=0
%SW100=1 %SW101 varies from 0 to 1000
%SW100=2 or 4 %SW101 varies from 0 to 1000
%SW100=3 or 5 %SW101 varies from -10000 to 10000
%SW102 Analog Analog output functions command word.
output Value : 0 Normal %PWM operation
Value : 1 Operation without scaling
Value : 2 Unipolar scale range analog
%PWM
Value : 3 Bipolar scale range
Writing this word is the responsibility of the application program
%SW103 Analog Word containing the value to be applied to the analog output. The output value range depends on the selection of operation made in
. %SW102.
%SW102=0 %SW103=0
%SW102=1 %SW103 between 5 and 249
%SW102=2 %SW103 between 0 and 10000
%SW102=3 %SW103 between -10000 and 10000
Writing this word is the responsibility of the application program
%SW110 Up/down Read value of the counter on a rising edge at input %I0.4
counter
%SW111 Fast Bit 0 : counting direction (1= upcounting, 0= downcounting) counter Bit 1 : 1= enable HSC (direct) outputs
Bit 2 : 1= select frequency meter time base
(1=100ms, 0=1s)
Bit 3 : 1= update %FC frequency (also indicates the validity of the acquired value on the analog input module)
This bit is reset to 0 by the user.
%SW112 Value of Contains the conversion on 8 bits (0 to 255) of the position potentiometer 0 of potentiometer number 0.
%SW113 Value of Contains the conversion on 8 bits (0 to 255) of the position potentiometer 1 of potentiometer number 1.
%SW114 Schedule Enables or disables operation of schedule blocks (RTC) block by the user program or the terminal.
enable bit 0 : 1 = enables schedule block #0
......................................................
bit 15 : 1 = enables schedule block #15
Initially all schedule blocks are enabled.
6/12
Role of system bits and words 6
System Function Description words
%SW118 Base PLC Shows faults detected on base PLC.
status bit 0 : 0= tripping of one of the outputs (1) bit 3 : 0= sensor supply fault bit 8 : 0= TSX Nano internal fault or hardware fault bit 9 : 0= external fault or comm. fault bit 11 : 0= PLC performing self-tests bit 13 : 0= configuration fault (I/O extension configured but absent or faulty)
All the other bits of this word are at 1 and are reserved. Thus, for a PLC which has no fault, the value of this word is :
16#FFFF.
%SW119 I/O peer Shows faults detected on I/O peer PLC (this word is only used by
PLC the base PLC). The bit assignment of this word is identical status to that of word %SW118, except for :
• bit 13 : not significant
• bit 14 : peer PLC now missing although it was present at
initialization (2)
(1) after a shortcircuit or overload of the protected transistor outputs.
B
6/13
B
6/14
7
7 Programming guide
7.1
Operating modes
PL7 language is used to take into account the three main operating mode groups (1) :
• Checking.
• Running or production.
• Stopping.
B
These different operating modes can be obtained around or starting from Grafcet using the following methods :
• Grafcet initialization.
• Prepositioning of steps.
• Maintaining a situation.
• Freezing charts.
Preliminary processing and use of system bits ensure effective operating mode management without complicating and overburdening the user program.
Structuring preliminary processing
The diagram below shows the structure which should be assigned to preliminary processing so that each processing operation is performed in order of importance for the following :
• Powering up yes
• Changing operating
mode
Powering up initialization no
Request for mode change no yes
Processing
Processing
• Input logic
Input logic
Grafcet system bits
Use of bits %S21, %S22 and %S23 is reserved for preliminary processing only. These bits are automatically reset by the system. They must be written by operation code S only.
Initializing Grafcet, %S21
Causes :
• on cold restart
• setting %S21 to 1 via the program or terminal.
Consequences : deactivation of all active steps and activation of all initial steps.
(1) These operating modes are defined in the "Design Guide for Operating and Stoppping Modes" produced by the Applied Industrial Automation Development Agency.
7/1
A
B
Resetting Grafcet, %S22
Causes : %S22 set to 1 via the program or terminal.
Consequences :
• deactivation of all active steps
• scanning of sequential processing stopped.
Prepositioning Grafcet, %S22 and %S23
Procedure :
• reset Grafcet by setting %S22 to 1
• preposition the steps to be activated by a series of S Xi instructions
• enable prepositioning by setting %S23 to 1.
Freezing a situation :
• in initial situation : by maintaining %S21 at 1 by program
• in "empty" situation : by maintaining %S22 at 1 by program
• in situation determined by maintaining %S23 at 1.
7.2
Programming advice
Handling program jumps
Use program jumps with caution to avoid loops which are too long and can increase scan time. Avoid program jumps towards instructions which are located upstream.
Programming of outputs
An output bit or internal bit can only be controlled once in the program. In the case of output bits, only the last value scanned is taken into account when the outputs are updated.
Using directly-wired emergency stop sensors
Sensors used directly for emergency stops must not be processed by the PLC. They must be connected directly to the corresponding outputs.
Handling power returns
Make power returns conditional on a manual operation, as an automatic restart of the installation could cause unexpected operation of equipment (use system bits %S0,
%S1 and %S9).
Time and schedule block management
The state of bit %S51, which indicates any schedule block faults, should be checked.
Note : When the program is entered, the terminal checks the syntax of the instructions, the operands and their association. The terminal diagnostics function checks programming errors
(see Appendices, Part G).
7/2
Programming guide 7
Additional notes on using parentheses
• Assignment operations should not be placed within parentheses.
)
LD %I0.0
AND %I0.1
OR( %I0.2
ST %Q0.0
AND %I0.3
ST %Q0.1
In order to perform the same function, the following equations must be programmed :
LD %I0.0
MPS
AND( %I0.1
)
OR( %I0.2
AND %I0.3
)
ST %Q0.1
MPP
AND %I0.2
ST %Q0.0
B
• If several contacts are placed in parallel, they should either be nested within one another or totally dissociated from each other.
Example 1
Example 2
The following schematics cannot be programmed.
Example 3 Example 4
7/3
A
B
In order to execute schematics equivalent to those on the preceding page, they must be modified as follows :
Example 5 (see example 3) Example 6 (see example 4)
LD %I0.0
AND( %I0.1
OR( %I0.2
AND %I0.3
)
)
OR( %I0.4
)
AND %I0.3
ST %Q0.1
LD %I0.0
AND( %I0.1
OR( %I0.2
)
AND %I0.3
AND %I0.5
OR( %I0.2
AND %I0.4
)
)
ST %Q0.1
7.3
Reactivating protected transistor outputs on TSX 07•• •• 12
When a channel fault has caused all the PLC outputs to trip (base PLC or I/O extension), they need to be reactivated. The reset may be :
• requested by an operator command. This is the recommended type of reactivation
(see Part A Section 1.7-2)
• automatic. When using this procedure, it is essential to know in advance how automatic reactivation of the outputs will effect the process or machine being controlled.
This selection is made by programming system bit %S49.
Output tripping
The appearance of an overload or short-circuit on an output causes :
• current limitation of the affected output
• tripping of all the outputs in the block (base PLC or I/O extension)
• activation with a steady light of the I/O lamp on the base PLC (if base PLC outputs tripped) or lamps on the base PLC and I/O extension (if I/O extension outputs tripped)
• setting to 0 of I/O fault system bit %S10
• setting to 1 of the system bit %S118 (tripping of base PLC outputs) or system bit
%S119 (tripping of I/O extension outputs),
• setting to 0 of system word bit %SW118:X0 (tripping of base PLC outputs) or system word bit %SW119:X0 (tripping of I/O extension outputs).
7/4
Programming guide 7
Manual reactivation of outputs (dependent on an operator command)
System bit %S49 is set to 1 by an external action. System bit %S49 must be reset to 0 after the outputs have been reset :
L D N % S W 1 1 8 : X 0
O R N % S W 1 1 9 : X 0
A N D %I0.3
(input I0.3 for example)
S % S 4 9
L D % S W 1 1 8 : X 0
A N D % S W 1 1 9 : X 0
R % S 4 9
B
The minimum time between two reactivate commands allowed by the system is 10s.
If the fault which caused tripping has disappeared :
• the outputs are once again active in the state defined by the program
• the I/O lamps are extinguished
• the system bits and system word bits are set to their default state (normal state) :
%S10, %SW118:X0, %SW119:X0 at state 1, %S118 and %S119 at state 0 (see Part B
Section 6.2).
Automatic reactivation of outputs
System bit %S49 is permanently set to 1 by the following program :
L D 1
S T % S 4 9
Reactivation is automatically requested every 10 seconds. When reactivation occurs, the behavior of the outputs, the indicator lamps and system words and bits is identical to that described for manual reactivation.
7/5
A
B
7.4
Reversibility conditions
The following conditions must be checked so that a program can be fully reversible (1) :
• The following instructions should not be used for reversibility : XOR, XORN,
XORF, XORR, JMPCN, ENDCN, or N.
• Function blocks must be programmed in such a way as to be reversible (see
Section 2.2-2).
• Function blocks cannot be cascaded or nested.
• Assignment instructions are prohibited between BLK and OUT_BLK instructions, and BLK and END_BLK instructions (if OUT_BLK is not programmed).
Permitted programming
Prohibited programming
BLK %TM0
LD %I0.0
ST %Q0.1
IN
END_BLK
BLK %TM0
LD %I0.0
IN
END_BLK
LD
ST
%I0.0
%Q0.1
(1) Note : When a sequence of instructions is not reversible, it remains in List Language, while the remainder of the reversible program is converted into Ladder diagrams.
7.5
Reversibility rules
• A canonical rung cannot exceed a height of 7 cells, and a width of 11 cells (7x11 grid).
• A sentence beginning with LD must end with a conditional action instruction.
• JMPCN, ENDCN, NOP, and N instructions are not reversible.
• Action instructions within parentheses are not reversible.
• Stack instructions within parentheses are not reversible.
• An OR instruction after an action instruction is not reversible.
• RET, JMP, and END instructions are unconditional. No other instructions can be in the rung.
• Function block inputs and outputs can only be accessed through reversible standard function block instructions. Direct access instructions for function blocks are not reversible.
7/6
Programming guide 7
• Instructions after an END_BLK in a sequence cause the sequence to be nonreversible.
• Function block outputs used with AND and OR instructions are not reversible.
• An OR instruction inside a function block output rung must be inside parentheses.
• An unconditional action instruction between a BLK and an END_BLK is not reversible.
• An OUT_BLK must be followed by a LD of a valid function block output or an
END_BLK.
• An instruction preceding an MRD or MPP instruction must be either a conditional action instruction or a stack operation.
• A non-nested OR instruction between an MPS and MPP pair is not reversible.
• An OR instruction after an MPS, MRD, or MPP instruction is not reversible.
• An MCS instruction cannot be used in the same rung with any other action instruction.
• A subroutine call or JMPC instruction must be the last action instruction of a rung.
• When putting a title and comments before a List instruction, there can only be 1 title line and up to 4 comment lines. If a blank line is placed anywhere between the title and the List instruction, part of the header may not show up in the corresponding
Ladder rung header.
• If more than 4 lines of comments are placed ahead of the List instruction, the 5th comment line will be interpreted as a title line and the comment lines above will not appear in the corresponding Ladder rung header.
When a sequence of instructions is not reversible, it remains in List Language, while the remainder of the reversible program is converted into Ladder diagrams as shown below.
B
7/7
A
B
7/8
PL7-07 PC programming software
Contents
Part C
Section
Features of the PL7-07 PC programming software
2 Installing PL7-07 PC programming software
2.2-1 Connection of power supply
2.2-2 Connection of communication cable from PC to PLC
2.2-3 Connection of communication cable from FTX 417 /
FTX 507/517 / FT 2000 terminals to PLC
Installing the PL7-07 PC programming software
Installing the UNI-TELWAY driver in Windows NT
2.5-3 Making directories for the application and data files
2.5-4 Import/Export information
2.5-5 Importing symbols and comments
Page
C
___________________________________________________________________________
C/1
PL7-07 PC programming software
Contents
Part C
C
Section
Running the PL7-07 PC programming software
2.6-1 Starting the PL7-07 PC programming software
2.6-4 Exiting the PL7-07 PC programming software
Using the PL7-07 PC programming software
3.2-2 Selecting a toolbar item
3.3-1 Using the List and Ladder editors
3.3-3 Using the Configuration editor
PL7-07 PC programming software operating states
3.6-2 Adjusting and debugging phase
Page
___________________________________________________________________________
C/2
PL7-07 PC programming software
Contents
Part C
Section
Creating a new application file
Opening an existing application file
5.1-1 Configuration menu on the main menu bar
5.1-2 Configuration Editor, accessed from the View menu
5.1-3 Configuring a resource from the Ladder Editor or
5.1-4 Configuring a resource from the Symbol Editor window
Page
C
___________________________________________________________________________
C/3
PL7-07 PC programming software
Contents
Part C
C
Section
Page
___________________________________________________________________________
C/4
PL7-07 PC programming software
Contents
Part C
Section
Using the Symbol Editor Tools menu
Using the Symbol Editor Edit menu
7 Developing a Ladder program 7/1
Inserting a graphic instruction
7.4-1 Rules for inserting graphic instructions
7.4-2 Inserting graphic instructions using the mouse
7.4-3 Inserting graphic instructions using the keyboard
Inserting specific contacts, coils, and function blocks
7.5-2 Inserting a coil or jump/subroutine call
7.5-3 Inserting a timer or counter block
7.5-4 Inserting and removing a down connector
___________________________________________________________________________
C/5
Page
C
PL7-07 PC programming software
Contents
Part C
C
Section
7.5-5 Inserting a comparison block
7..5-6 Inserting an operate block
7.5-7 Inserting special instructions from the Extended
Inserting an operand or symbol
Inserting a rung title, label, or comments
Using the Ladder Editor Tools menu
Using the Ladder Viewer Tools menu
7.9-8 1 Line Address or Symbol
7.9-9 3 Lines Address or Symbol
7.9-10 3 Lines Address and Symbol
7.9-15 Table of Grafcet steps (see Section 9.3 Part C )
Page
___________________________________________________________________________
C/6
PL7-07 PC programming software
Contents
Part C
Section
7.10 Using the Ladder Viewer Edit menur
Using the List Editor Tools menu
8.4-4 Grafcet Step Table (see Section 9.3 Part C )
Using the List Editor Edit menu
___________________________________________________________________________
C/7
Page
C
PL7-07 PC programming software
Contents
Part C
C
Section
10 Validating and reversing a program
10.2 Viewing validation errors
12 Transferring an application 12/1
12.2 Transferring an application
12.2-4 EEPROM => PLC (EEPROM to PLC)
___________________________________________________________________________
C/8
Page
PL7-07 PC programming software
Contents
Part C
Section
14 Debugging and adjusting an application 14/1
14.2-1 Animating a Ladder program
14.2-2 Animating a List program
14.4 Using the Data Editor Tools menu
14.4-1 Editing a data variable
___________________________________________________________________________
C/9
Page
C
PL7-07 PC programming software
Contents
Part C
C
Section
14.5 Modifying the program in RUN mode
15.3-1 Configuration Print Settings
15.3-3 Cross Reference Print Settings
16 Cross referencing an application
16.2 Generating a new Cross Reference list
16.3 Updating an existing Cross Reference list
17 Exporting source files 17/1
___________________________________________________________________________
C/10
Page
Section 1
1 Overview
1.1
Introduction
Part C describes how to use the PL7-07 PC programming software to develop and manage applications for TSX Nano PLCs.
1.2
Features of the PL7-07 PC programming software
The PL7-07 PC programming software is a graphical development environment for writing and maintaining applications for the TSX Nano PLCs.
The PL7-07 PC programming software is a Windows-like development tool that is used to develop applications on IBM-AT compatible PCs with MS-DOS 3.3 or later. Among the PL7-07 PC programming software features are :
• multi-windows capability (up to 3)
• easy use with keyboard or mouse
• reversible Ladder and List programming
• two-step, point and click Ladder programming
• offline and online programming
• program and/or data animation
• easy configuration by simply selecting desired functions in dialog boxes,
• cut, copy, and paste program editing
• symbolic programming
• independent data files
• import/export features
• cross referencing
• print-out
- program in List and/or Ladder
- configuration
C
1.3
Other information
Part G contains appendices that are referenced in part C. The following is a list of the appendices :
A.1
Boolean List and control instructions with Ladder equivalent
A.2
Tool bar and instruction bar menu options
1/1
C
A.3
PL7-07 PC programming software variables
A.4
Security features
A.5
Instruction scan time and memory usage
A.6
Importing and Exporting ASCII program files and symbol files
A.7
Transferring applications from FTX 117 terminal to PC with TSX Nano or memory card
A.8
Troubleshooting installation problems
A.9
Running PL7-07 under Windows
A.10 Example of prepositioning Grafcet steps
A.11 Actions associated with steps
1.4
Conventions
The following typographic conventions are used in part C :
Format Represents bold A word or phrase shown in bold text indicates that you should enter the word or phrase exactly as it appears. The names of menu options and dialog box fields are also shown in bold type.
italics
<carats>
A word in italics indicates a place holder for information that you must provide. A word in italics also indicates a new term, which is then followed by a definition.
A word in <carats> indicates the name of a key on the keyboard, such as <delete>.
1/2
2
2 Installing PL7-07 PC programming software
2.1
System requirements
2.1-1 Machine compatibility
The following class and/or types of computers can run the PL7-07 PC programming software :
• IBM PC-AT compatible machines
• Programming terminals
- FTX 417 20 / 417 40 (1) / FT 2000 (1)
- FTX 507 or FTX 517 (1)
(1) recommended terminals for optimal performance
C
2.1-2 System requirements
The computer system should meet these minimum requirements :
• 20MHz 286 microprocessor
• 640 KB of RAM and 2 megabytes of available extended memory
• 3 megabytes of available hard disk space
• EGA, VGA, or SVGA monitor
• One available COM serial port - COM1 through COM4
• One parallel port for printing - LPT1 through LPT4
• MS-DOS version 3.3 or higher
Typical configuration :
• 386 microprocessor or higher
Although the PL7-07 PC programming software will run on a computer with the minimum requirements above, you may experience slow performance if you have multiple windows open simultaneously, a large amount of animated data, or a very large application.
___________________________________________________________________________
2/1
2.2
Connections
The connections specific to the PC or FTX 417/FTX 507 terminals (display, keyboard, mouse, and printer) are described in their documentation. This section describes the following :
• connection of power supply
• connection of communications cable.
WARNING
A communication cable should never be connected to the PLC port before being connected to the peripheral device (programming terminal, operating terminal etc).
C
2.2-1 Connection of power supply
See part A, section 3.2 for connection of the power supply.
2.2-2 Connection of communication cable from PC to PLC
This connection requires communication cable TSX PCU 1030 (2.5 meters long), supplied with TLX L PL7 07P 30E software. For a 25-pin serial connector, use the
TSX CTC 07 adaptor with communication cable TSX PCU 1030.
Supply
FT 2000
PC-compatible
TSX Nano
TSX PCU 1030
Supply
COM
serial port
TSX PCU 1030
2.2-3 Connection of communication cable from FTX 417 / FTX 507/517 / FT 2000 terminals to PLC
This connection requires communication cable T FTX CBF 020 (2 meters long), supplied with software TLX L PL7 07F 30E.
Supply FTX 417
COM
serial port
2/2
T FTX CBF 020
T FTX CBF 020
Supply Supply
FTX 507/517
Installing PL7-07 PC programming software 2
2.3
Installing the PL7-07 PC programming software
The PL7-07 PC programming software is contained on two, high-density 3.5" disks. To install the PL7-07 PC programming software :
1. With the DOS prompt at c:, insert installation Disk #1 in the 3.5" floppy disk drive.
2. Select the disk drive by typing a: or b: at the DOS prompt and press <enter>.
3. Type install and press <enter> to launch the PL7-07 PC programming software.
4. Select the language for installing the program. The PL7-07 PC programming software can be installed in one of the following five standard languages : English,
French, German, Italian, and Spanish. Other languages can be installed using a
3.5" disk (supplied separately) containing the files translated into the required language.
Note :
Contact your nearest SCHNEIDER distributor to obtain information on how to install PL7-07 in a language other than E/F/G/I/S.
The PL7-07 PC programming software can operate in only one language at a time.
If support for multiple languages is required, create a new directory with a different name and reinstall the software in the new directory. If you reinstall the software in the same directory as the original installation, the newly-installed version will overwrite the old one.
5. When prompted, select a target drive for installing the PL7-07 software.
6. When prompted, select a name for the PL7-07 PC programming software directory.
The default subdirectory is <drive>:\PL707.
7. If the operating system used is DOS or Windows 3.1/95/98, when prompted select a communication port for the PLC.
If the operating system used is Windows NT, the communication port for the PLC will be selected using the XWAY drivers manager (see Section 2.4).
8. The program decompresses the installation files and writes the PL7-07 PC programming software files to the selected drive.
9. When prompted, insert installation Disk #2 in the floppy drive.
10. Respond Yes (or No, see note) to the prompt : "May I create/modify your CONFIG.SYS
file if needed (Y/N)?
11. Respond Yes (or No, see note) to the prompt : "May I create/modify your
AUTOEXEC.BAT file if needed (Y/N)?
12. When prompted, insert installation Disk #1 in the floppy disk drive.
C
___________________________________________________________________________
2/3
C
13. When prompted, press any key to terminate the installation program and reboot the computer.
Note : If you replied No in steps 10 and 11, write down the data displayed at the end of the installation program to manually update your configuration files. Before terminating the installation program, modify your configuration files as follows :
1. Display your AUTOEXEC.BAT file in a text editor. Insert the statement, C:\PL707, to the path statement :
PATH=C:\WINDOWS;C:\DOS;C:\PL707 where C: is the drive selected and \PL707 is the name selected for the PL7-07 PC programming software directory.
2. Display your CONFIG.SYS file in a text editor. Insert these statements :
FILES=30 or more
DEVICE=C:\PL707\DUNTLW.EXE PROFILE=C:\PL707\DUNTLW.001
COM1 is the default communications port. To change the COM port setting, edit
DUNTLW.001 in directory C:\PL707. In the Basic Parameters section, change the COM setting in the line PORT=COM1:O,8,1 to the desired COM port.
3. Reboot the computer.
Note :
The PL7-07 installation software, INSTALL.EXE, requires at least 370 Kb of available memory in the 640 Kb of RAM memory to run correctly.
2/4
Installing PL7-07 PC programming software 2
2.4
Installing the UNI-TELWAY driver in Windows NT
The NT version of the UNI-TELWAY communication driver, supplied on a 3.5" highdensity floppy disk, has its own installation procedure which is different from that of
PL7.07 V3.0.
The UNI-TELWAY driver can be installed before or after installation of PL7.07 software.
To install the UNI-TELWAY driver :
1. Insert the UNI-TELWAY driver floppy disk in the disk drive.
2. In the Start/Run menu, select A:\Setup.exe and click OK.
3. Confirm the welcome screen by clicking Next.
4. Select a target drive for installation of the UNI-TELWAY software.
5. Define the program group (the software suggests the Modicon
Telemecanique group by default).
6. Select the language.
7. Configure the communication port by selecting :
- the communication port for the PLC
- the transmission speed
- the UNI-TELWAY address then save the configuration.
C
8. Close the dialog box by clicking on ,
9. Reboot the computer.
The configuration parameters of the UNI-TELWAY driver can be displayed and/or modified using the XWAY drivers manager located in the program group defined during installation (Modicon Telemecanique by default).
___________________________________________________________________________
2/5
C
This tool is made up of XWAY Manager, UNI-TELWAY Driver and XWAY Test tabs.
The XWAY Manager tab :
- provides information on the driver(s) installed
- can be used to install, update or uninstall a driver.
The Unitelway Driver tab is used to modify the configuration parameters of the UNI-
TELWAY driver.
The XWAY Test tab is used to test the link of the driver selected :
Driver group
• Name : Name of the driver to be used for the UNI-TELWAY test.
• Driver instance : Instance number of the driver to be used for the test (usually 1).
• Remote address : XWAY address of the remote station in “network.station.port” format. The address “0.254.0” is the default address (terminal port for example).
Request group
• Type : Type of request. Different sizes of mirror requests are provided.
• Time-out : Time-out in ms of the response to the request sent.
• State : Connection status : “disconnected”, “connecting…” or “connected”.
(3) Control buttons
• Connect : Opens an internal communication channel on the driver selected.
• Start : Starts sending requests to the station defined in the “Remote address” field of the “Driver” group. This button is active in online mode only.
• More info… : Displays system information on the driver. This button is active in online mode only.
• About : Displays the version and copyright of the XWAY drivers manager.
2/6
Installing PL7-07 PC programming software 2
2.5
File management
2.5-1 Types of files
Seven different types of file are used in the PL7-07 PC programming software. The following describes the file types and how they are used :
Application file
(.PL7 extension)
This file type (.PL7 extension) is used for storing applications developed in the PL7-07 PC programming software. Application files are accessed from the File menu.
Binary file This file type (.APP extension) is used for storing applications
( .APP extension) developed in the PL7-07 PC programming software to a format that allows the file to be transferred to the FTX 117 terminal using a memory card or vice versa.
Data files
(.DAT extension)
This file type (.DAT extension) is used for storing data pages developed in the Data Editor. Data files are accessed from the
Tools menu when the Data Editor window is displayed. The .dat
extension allows for these files to be transferred to the FTX 117 terminal via the memory card without saving them as a binary file type.
Symbol files This file type (.SYM extension) is used when exporting symbols
(.SYM extension) from PL7-07 application to another
ASCII text files
(.TXT extension)
Export files
(.IL extension)
Export files
(.LD extension)
This file type (.TXT extension ) is used when importing and exporting List program files.
This file type (.IL extension) is used when exporting PL7-07
List source programs to PL7 Micro.
This file type (.LD extension) is used when exporting PL7-07
Ladder source programs to PL7 Micro.
C
2.5-2 Backup files
When changes are made to an application file (.pl7 extension) and the file is saved, a backup file is automatically generated with a .bak extension. The .bak file is the latest version of the application file before the changes were made. The .bak file is stored in the same directory as the application file. If you desire to use a different backup extension, change the setting in the "BackupExtension=" line of the "AppDefaults" section of the PL707.INI file using the DOS editor. If you do not want to automatically generate a backup file, leave the space blank after "BackupExtension=".
If you want to use the .bak file, select All (*.*) from the List Files of Type field in the File
Selection dialog box. All the files in the selected directory will be displayed. Select the
.BAK file for the desired application.
___________________________________________________________________________
2/7
2.5-3 Making directories for the application and data files
To assist in managing the application and data files created during the development of an application, it is recommended that separate directories be created for the application (.PL7) and data (.DAT) files.
Note : The following access paths assume the PC programming software has been installed in the default directory C:\PL707.
1. At the prompt C:\PL707, type MKDIR APPS to create a subdirectory for the application files. The full path designation is C:\PL707\APPS\filename.
2. At the prompt C:\PL707, type MKDIR DATA to create a subdirectory for the data files.
The full path designation is C:\PL707\DATA\filename.
C
2.5-4 Import/Export information
The PL7-07 PC programming software allows you to import and export ASCII Program files and Symbols files. It also allows source programs (List or Ladder ) to be exported to PL7-Micro. The Import and Export options are accessed from the File menu. The following describes the files that can be imported and exported :
1. List programs can be developed by external ASCII text editors. ASCII Program
Import and Export allows you to import and export these files between the PL7-07 software and the ASCII text editor.
2. Symbols Import and Export allows you to copy symbols from one PL7-07 software application to another. This type of import/export uses an internal file format with the file extension .SYM. This file type is not usable by any external tools such as text editors and spreadsheets. Symbols Import and Export also allow you to create default Symbols files for common applications.
3. A current PL7-07 application source program can be exported to PL7-Micro in reversible List or Ladder. The extension used, IL (List) or LD (Ladder), determines in which programming language it is exported. The default extension is that of the current editor selected.
When the LD extension is used, the export file contains the program, the rung headers (only the titles are exported in Ladder), the symbols and configuration data.
Objects which cannot be interpreted by PL7-Micro (fast counter, Grafcet instructions, etc) are replaced by an empty line.
When the IL extension is used, the export file contains the program, the comment lines, the symbols and the configuration data. Instructions comments are not exported.
2.5-5 Importing symbols and comments
The PL7-07 PC programming software enables you to import program comments and symbols from a file in another application. This option is used to import object symbols and comments from a standard program without having to re-enter them.
This option is a sub menu of the "Import" function which can be accessed from the "File" menu. An application must be open to use this option. When the option is launched, a screen appears, enabling the source application file to be selected.
2/8
Installing PL7-07 PC programming software 2
The symbols loaded from the source application file are placed in the symbol table of the current application. The comments (placed at the end of the program line or a whole line) are merged with the current application.
Rules for importing symbols and comments :
• The current application should not include any symbols or comments for the import operation to be performed successfully.
• End of line comments are placed in a rung and line with the same number and row as the source application.
• If the rung line row does not exist in the current application, the end of line comment is inserted as a whole line comment at the end of this rung.
• If the rung number does not exist in the current application, the end of line comment is inserted as a whole line comment at the end of the program.
• Whole line comments are inserted as a new line in a rung and line with a number and row equivalent to the source application.
• If the rung line row does not exist in the current application, the whole line comment is inserted at the end of this rung.
• If the rung number does not exist in the current application, the whole line comment is inserted at the end of the program.
Example
• Application 1 containing symbols and comments :
(* FIRST LINE COMMENT AT START OF APPLICATION*)
(* SECOND LINE COMMENT AT START OF APPLICATION*)
LD INPUT_1
ST OUTPUT_1 (* PROGRAM COMMENT*)
C where %I0.1=INPUT_1 and %Q0.1=OUTPUT_1
• Current application without symbols or comments :
LD %I0.0
AND %I0.1
ST %Q0.1
• After importing symbols and comments from application 1, the current application becomes :
(* FIRST LINE COMMENT AT START OF APPLICATION*)
(* SECOND LINE COMMENT AT START OF APPLICATION*)
LD %I0.0
AND
ST
INPUT_1
OUTPUT_1
(* PROGRAM COMMENT*)
The comments are inserted in the program and the objects are linked to the imported symbols.
___________________________________________________________________________
2/9
C
2.6
Running the PL7-07 PC programming software
2.6-1 Starting the PL7-07 PC programming software
1. At the prompt C:\PL707 (or other specified subdirectory), type PL707 to run the
PL7-07 programming software.
2. The first time the PL7-07 programming software is run, a PL7-07 Registration dialog box is displayed. After entering your name and company, select Ok to open the program in the initial state.
When the program is subsequently run, the PL7-07 Registration dialog box is displayed briefly and the program is automatically opened at the initial state.
2.6-2 Opening an application
To open a new or existing application, see sections 4.2 and 4.3.
2.6-3 Closing an application
Only one application can be open at a time. If you try to open a second application with one already open, an Information dialog box is displayed with the following message :
"Please close your application before opening another."
To close an application :
1. Select Close from the File menu.
If the application file is not saved before it is closed, a Warning Exit dialog box appears.
2. Select Yes to save changes and exit the application file or No to close the file without saving the changes. Select Cancel to return to the application file.
2/10
Installing PL7-07 PC programming software 2
2.6-4 Exiting the PL7-07 PC programming software
To exit the PL7-07 PC programming software :
1. Select Exit (CTRL Q) from the File menu.
2. If Exit is selected from the initial state, the program is immediately closed and the system returns to DOS.
3. If an application with unsaved changes is open, in either the offline or online state, a Warning Exit dialog box is displayed.
4. Select Yes to save changes and exit the application file or No to close the file without saving the changes. Select Cancel to return to the application file.
For information on executing PL7-07 in a Windows environment, see Appendix A.9.
C
___________________________________________________________________________
2/11
C
2/12
Section 3
3 Software features
3.1
Introduction
This section explains the concepts needed to develop and manage applications with the PL7-07 PC programming software.
3.1-1 Glossary of terms
Active window The window being currently used or currently selected. Only one window can be active at a time. Keystrokes and commands affect the active window. If a window is active, its title bar changes color to differentiate it from other windows.
Application file
Binary file
Check box
Choose
The PL7-07 application file is the main storage file for TSX Nano programs within the PL7-07 software. In the file is the source code, comments, and symbols for the program. Application files are distinguished by the .pl7 file extension.
A file containing information that is in machine-readable form— it can only be read by the TSX Nano PLC, the FTX 117 handheld programmer, and the PL7-07 software. The binary file contains the program that was compiled (validated) from an application file. It contains the PLC instructions in machine language form.
No comments or symbols (program documentation) are contained in this file. Binary files are distinguished by the .app file extension.
A small, square box that appears in a dialog box that can be selected or cleared. When the check box is selected, an X appears in the box. A check box represents an option that can be turned on or off.
To use the mouse or keyboard to pick an item that begins an action in the PL7-07 software. Menu options are chosen to perform tasks.
Clear
Click
Clipboard
Close
To turn off an option by removing the X from a check box. A check box is cleared by clicking it, or selecting it and pressing the
<spacebar>.
To press and release the mouse button quickly.
A temporary storage location used to transfer program segments between areas of the program and between applications. Program segments are transferred to the clipboard by using the Copy or Cut option from the Edit menu. Program segments are transferred from the clipboard by using the Paste option from the Edit menu.
To remove a window or dialog box , or to remove an application from memory.
3/1
C
C
Command button In a dialog box, a button that carries out an action. A command button has a label in it to describe the action carried out (for example, Cancel, Help, or Ok).
Copy To duplicate a selected program segment into the clipboard to be transferred to another location. The program segment selected is not removed from its original location.
Cursor
Cursor keys
Cut
Device
The place where text or programming instructions are inserted.
The PL7-07 software uses a vertical, flashing cursor for most text insertions. The Ladder editor uses a square cursor the size of one cell of the programming grid.
On the computer keyboard, the keys used to navigate around the screen. These include the <home>, <end>, <page up>, <page down>, up arrow, down arrow, right arrow, and left arrow keys.
To remove a selected program segment and place it in the clipboard.
A component of the computer hardware configuration, such as a modem, printer, mouse, or PLC.
Device driver
Dialog box
Double-click
File
The software that controls how a computer communicates with a device, such as a PLC. For example, the PL7-07 device driver translates information from the computer into information the PLC can understand.
A small window that appears temporarily to request information.
Many dialog boxes have multiple options. An option must be chosen before the PL7-07 software can continue with an action or command.
To rapidly press and release a mouse button twice without moving the mouse.
A collection of information that has been named and stored on a disk.
File name
Grayed-out
Inactive window
List box
The name of a file. The PL7-07 software uses the MS-DOS file naming conventions.
A dimmed button, option, or menu that is displayed in light gray instead of black. The button, option, or menu cannot be chosen.
Any open window not currently being used.
Within an application window or dialog box, a type of box that lists available choices—for example, a list of files in a directory. If all the choices do not fit in the list box, there is a scroll bar present to the right of the box.
3/2
Software features 3
Menu
Menu bar
Mouse pointer
Option
Paste
Point
Radio button
Scroll
Scroll arrow
Scroll bar
Scroll box
Select
Shortcut key
Status bar
System button
A list of available options, summarized by the items in the menu bar at the top of the PL7-07 software main window. A menu is opened by selecting the menu name.
The horizontal bar near the top of the PL7-07 software main window containing the names of the PL7-07 software menus. The menu bar appears below the title bar.
The arrow-shaped cursor on the screen that follows the movement of the mouse. The mouse pointer indicates which area of the screen will be affected when you press the mouse button.
A choice in a menu. For example, for File/Open, Open is an option in the File menu.
To copy the contents of the clipboard at the location of the cursor.
To position the mouse pointer to the desired location on the screen.
A small, round, option button that appears in a dialog box. Within a group of related radio buttons, only one can be selected.
To move through lists and program displays (up and down) in order to view the entire contents of the list or program.
An arrow on either end of a scroll bar that is used to scroll through the contents of the window or list.
A bar that appears at the right edge of a window or list box when the contents exceed the capacity of the display. Each scroll bar contains a scroll box and two scroll arrows.
In a scroll bar, the small box that shows the position of the information in the window or list box relative to the contents of the entire amount of information to be displayed.
To highlight and pick the desired option from a menu, window, or dialog box. This can be done with either the mouse or keyboard.
A key or key combination that is pressed to carry out a command or menu option. If an option has a shortcut key, the key combination is listed to the right of the option name on the menu.
A bar that appears at the bottom of the PL7-07 software screen.
It displays information and error messages, available memory in the PLC, whether the PLC is running or stopped, and the status of the application with respect to the PLC (initial, offline, online, or monitor).
A button located at the left side of the title bar that is used to close a window by clicking on it with the mouse pointer.
C
3/3
Text box
Title bar
Window
A box located in a dialog box in which you type information needed to carry out an option or action. The text box may be blank or may contain text when the dialog box is opened.
The horizontal bar (at the top of a window) that contains the title of the window or dialog box.
A rectangular area on the screen in which you view programs, data, and documentation. A window can be opened, closed, and have its vertical size changed. Up to 3 windows can be opened at a time. For EGA monitors, only 2 windows can be opened at a time.
C
3.2
Using the PL7-07 PC programming software
You can use the PL7-07 PC programming software with either a mouse and keyboard, or keyboard only. This section describes how to perform some of the most common actions for both methods.
3.2-1 Selecting a menu option
1. To select a menu option with a mouse, position the cursor on the desired menu name and select it with the left mouse button. A menu appears. Position the cursor on the desired option and select it with the left mouse button.
2. To select a menu option using keystrokes, hold down the <alt> key and enter the letter that is underlined on the menu name. A menu appears. To select the option from the menu, enter the letter that is underlined on the menu option name.
3. To select a menu option using a "quick key", hold down the combination of keys for the desired option. See the tables in appendix A.2 of part G for the options that have quick keys.
3.2-2 Selecting a toolbar item
To select a tool bar option, position the cursor on the desired "button" and select it with the left mouse button. See the tables in appendix A.2 of part G for the description of the tool bar buttons.
3.2-3 Menu charts
The following two illustrations show the PL7-07 software Main menu options and the
Tools menu options. The Tools menu options vary depending on the window that is open.
3/4
Software features 3
C
3/5
C
3/6
Software features 3
3.3
Using the editors
The PL7-07 PC programming software is used to develop applications for the TSX
Nano PLC. The term application includes a program, configuration data, symbols, and comments.
The PL7-07 software makes use of four editors in constructing an application—List/
Ladder editor, Data editor, Configuration editor, and Symbol editor. For example, you write or edit a software program in the List/Ladder editor, construct and save data pages in the Data editor, enter or modify symbols in the Symbol editor, and enter or modify configuration data in the Configuration editor. Developing each application part in a separate editor makes the application development process more systematic, resulting in more clearly defined applications.
You can construct the application in any order. For example, you can choose to define configuration data first, then define data variables, and then write the program instructions—or complete these tasks in the reverse order. There is no prescribed order. The sections that follow describe each application part in detail.
C
3.3-1 Using the List and Ladder editors
The List and Ladder editors are used to develop the main program—the core of the application. The development of the main program includes:
• assigning addresses to the inputs and outputs being used for the program..
• selecting the pre-defined data variables to be used for the program.
• constructing the order in which the program is to be executed.
You can write a program for the PLC in either the List or Ladder format. Selecting one method over the other is a matter of preference and does not affect the application.
Ladder is a diagrammatic language that uses both graphic elements and text. Each segment of a Ladder diagram is called a rung. For more information on developing a
Ladder program, see section 7.
List is a Boolean text-based instruction set. For more information on developing a List program, see section 8.
In either Ladder or List, you write the program in the logical order required to control a machine or process. You can automatically convert or reverse Ladder instructions to List instructions. You can also reverse List to Ladder instructions, if the structure of the program and the instructions comply with the reversibility rules. (See Section 10 of Part C.)
You can document your program using comments in both the List and Ladder Editors.
Comments are notes that you put into your program instructions in free-format text.
Comments are used primarily to document the meaning and purpose of program instructions.
3/7
3.3-2 Using the Data editor
The Data editor is used to construct and save data pages. A data page is used for listing all or part of the data variables used in the main program. The data page consists of variable addresses, current values, retained values, and associated symbols. This is useful for adjusting and debugging an application. For more information on using the
Data editor, see section 14.
C
3.3-3 Using the Configuration editor
The Configuration editor is used to assign specific values to the hardware and software resources of the PLC—timers, counters, latched inputs, external run/stop switches, etc.—to control the behavior of these resources. The assigned values are called configuration data. For more information on configuring PLC resources, see section 5.
3.3-4 Using the Symbol editor
The Symbol editor is used to document a program by assigning tag words (symbols) to the data variables used in the program. Symbols are an optional part of an application. Symbols can be used in writing the program instructions, rather than the associated memory variable address. Symbols and their associations are defined and edited in the Symbol Editor. For more information on the Symbol editor, see section 6.
Note that only certain parts of an application reside in the PLC. For example, while you have an application online in the PLC, the symbols and comments remain in the PC memory, while the program and configuration data are maintained in the PLC memory.
PL7-07 PC programming software maintains the relationship between the parts of the application.
3.4
PL7-07 PC programming software operating states
The PL7-07 PC programming software has four operating states:
• Initial
• Offline
• Online
• Monitor
The following describes the significance and attributes of each operating state.
3.4-1 Initial State
The PL7-07 software is in the initial state when the program is first started or when an application is closed. When in the initial state, the word “Initial” appears on the right side of the status bar at the bottom of the screen.
3/8
Software features 3
3.4-2 Offline State
When you open a new or existing application, the PL7-07 software changes from the initial to the offline state. An application in the offline state is not connected to the PLC and exists completely within the PC memory. In the offline state, you can create and edit program instructions and configuration data, and modify data variables, symbols, and comments. When you open an application in the offline state, the word “Offline” appears on the right side of the status bar at the bottom of the screen.
From the offline state, select Connect from the PLC menu to make an online connection.
The flow chart shows the decisions made by the software when the Connect option is chosen.
3.4-3 Online State
An application in the online state is directly connected to the PLC memory. In the online state, you have unrestricted access to an application, unless the application is protected. Changes that you make to the application program, configuration data, and data variables are written directly to the PLC memory. Program documentation, such as symbols and comments, remain in the PC memory.
Online, you have complete access to all PL7-07 software features. When the PL7-07 software has an application in the online state, the word “Online” appears on the right side of the status bar at the bottom of the screen.
If you want to return to the offline state, select Disconnect from the PLC menu. You can also select the Close option from the File menu to return to the initial state, without passing through the offline state. If you select Close, you will be prompted to save your changes.
C
3.4-4 Monitor State
The monitor state provides access to the operating states and to the adjustment of the
PLC. For instance, you may start, stop or reboot the PLC and view, modify, or transfer data in the Data Editor. However, the List/Ladder Editor, Symbol Editor, and Configuration Editor are not available in the monitor state. If the application in the PLC is protected (see section 12.4), the monitor state is the only online state available.
If you are in the offline state, and the application in the PLC is not protected—but is different than the application in the PC's offline memory you may choose to enter the monitor state. This allows you to monitor the PLC while maintaining the application in the PC's offline memory.
When the PL7-07 software is in the monitor state, the word “Monitor” appears on the right side of the status bar at the bottom of the screen. In the monitor state, select
Disconnect from the PLC menu to change from the monitor state to the offline state.
3/9
C
3.5
Status bar
The status bar appears at the bottom of the PL7-07 software screen. The following shows the different parts of the status bar:
(1) Information and error messages. For a complete description of the message, click on this area of the status bar.
(2) Available memory in the PLC (in bytes).
(3) Whether the PLC is running or stopped.
(4) The state of the PL7-07 software (initial, offline, online, or monitor).
(1) (2) (3) (4)
3.6
Developing an application
3.6-1 Design phase
The following flowchart shows the recommended steps and associated sections for creating an application in List or Ladder using the PL7-07 PC programming software.
Analysis
• Program
• Requirements
1 Configuring PLC resources, section 5
2
Enter configuration
Application
Function blocks
Inputs
Outputs
Constants
Configure schedule blocks
3 Enter program
• Create
• Insert
• Modify
• Delete
• Duplicate
Configuring PLC resources, section 5
Developing a
Ladder program, section 7
Developing a
List program, section 8
4 Backup
• On hard drive
• On floppy disk
Archiving an application, section 11
Optional, enabling the application being created to be customized. This operation can also be performed in parallel with operation 3.
3/10
Software features 3
3.6-2 Adjusting and debugging phase
The adjusting and debugging phase is done in the online or monitor state. The following flow chart shows the recommended steps and associated sections for adjusting and debugging an application.
Application in online mode
Application in offline mode
Transfer the application Transferring an application, section12
Starting up an application, section 13
Start up
• Adjust clock
• Initialize
• RUN application
Debug and adjust
• Data entry
• Data table entry
• Forcing
• Modification in RUN
Archive
• in EEPROM memory
• on hard disk
and/or floppy disk
Debugging and adjusting an application, section 14
Archiving an application, section 11
Transferring an application section 12
C
3/11
C
3/12
Section 4
4 Getting started
4.1
Introduction
From the initial state, you can:
• create a new application file.
• open an existing application file.
• transfer an application to or from the PC, the PLC, or the EEPROM.
• connect the PC to the PLC.
• open a binary file.
4.2
Creating a new application file
Select New from the File menu to create a new application file. Selecting New changes the menu bar display. Menu bar items that were previously grayed out are active. In addition, the application state displayed in the status bar is changed from initial to offline state. PL707 V3.0 or later automatically opens the List editor or the Ladder viewer according to the choice made in the Preferences dialog box. The Ladder viewer is open by default.
C
4.3
Opening an existing application file
From the File menu, select Open to access an existing application file. A File Selection dialog box is displayed.
To select a file:
1. If the drive that stores the file you want to open is not the current drive, open the
Drives field selection box by selecting the down arrow, and select a drive.
4/1
C
2. In the Directories field, select the directory containing the file that you want to open.
3. In the List Files of Type field, open the list box by selecting the down arrow. Select:
• Application (*.pl7) file type to display application files
• Binary (*.app) file type to display binary files
• All (*.*) to display all files in the directory.
4. In the Filename list box, select a file to display in the Filename field or type the name of the file you want to open.
5. Select Ok to open the file. When the file is opened, the application state changes from initial to offline. Select Cancel to close the File Selection dialog box without selecting a file.
4.4
Transferring an application
In the offline state, select Transfer from the PLC menu to copy an application between the PC and the PLC. You can also select Transfer to copy an application between the
PLC and the EEPROM. The EEPROM is a permanent memory area in the PLC where an application can be stored.
For detailed information about the Transfer option, see section 12, "Transferring an application."
4.5
Connecting the PC to a PLC
In the offline state, select Connect from the PLC menu to initiate communication between the PC and the PLC. For detailed information about the Connect option, see section 13.1.
4.6
Opening a binary file
A binary file has an .app file extension and contains the program and the configuration data in binary machine code.
Generally, a binary file is opened from a PC card (memory card). You can use the PC card to transfer an application from the FTX 117 terminal to the PC (TFTX REM/RSM cards only). For more information, see appendix A.7 in part G.
4/2
Section 5
5 Configuring PLC resources
5.1
Introduction
The Configuration options are the hardware and software resources of the PLC. You can configure these resources before you write a program, while you write a program, or after you have completed a program.
The Configuration option can be selected by one of the following :
1. A resource can be configured from the Configuration menu on the main menu bar.
2. A resource can be configured from the Configuration Editor, accessed from the View menu.
3. A function block can be configured directly from the Ladder Editor or Ladder Viewer window.
4. A resource can be configured from the Object Browser dialog box in the Symbol
Editor.
C
5.1-1 Configuration menu on the main menu bar
You configure resources from the Configuration menu on the main menu bar. Use the Configuration menu when you want to configure single objects as you construct other parts of the application.
5.1-2 Configuration Editor, accessed from the View menu
A resource can be configured from the Configuration Editor, which you access from the
View menu. When you use the Configuration Editor, the Configuration Editor tool bar is displayed.
The buttons on the tool bar correspond to resources in the Configuration menu and
Tools menu. Appendix A.2-1 in part G lists the options on the Configuration and Tools menu with the corresponding buttons on the tool bar.
When a resource is selected with the Configuration Editor window open, the current configuration of the selected resource appears. To configure Timers, Counters,
Constants, and LIFO/FIFO Registers, select the resource directly from the list displayed.
For Change PLC Version, the PLC Version Management dialog box appears instead of a list. To configure the other resources, select configuration editor from the View menu to display the appropriate dialog box.
5/1
5.1-3 Configuring a resource from the Ladder Editor or Ladder Viewer window
A resource can be configured directly from the Ladder Editor or Ladder Viewer window.
Select the desired resource by double-clicking with the mouse or pressing <enter> on the resource in the Ladder program. The dialog box that appears allows you to configure the resource.
C
5.1-4 Configuring a resource from the Symbol Editor window
A resource can be configured from the Symbol Editor window via the Object Browser dialog box. The Symbol Editor window is selected from the View menu. Select the desired resource from the Symbol Editor list. The Object Browser dialog box appears.
Select the Configure radio button to configure the resource.
5.2
Validate Program
Validate Program is available from the Tools menu when the Configuration Editor is displayed. See Section 10.1 for a full description of Validate Program.
5.3
Validate Configuration
Validate Configuration is available from the Tools menu when the Configuration Editor is active.
After changes or additions have been made to the configuration information :
1. Select Validate Configuration from the Tools menu. An Exit Warning dialog box appears.
Note : After configuration information is changed or added, Validate Configuration must be run to commit the new configuration information to the application. If you try to print, transfer, or save the application without running Validate Configuration, the previous information will be used.
5/2
Configuring PLC resources 5
2. Select Yes to accept the changes and exit the Configuration Editor. Select Cancel to return to the Configuration Editor.
3. If Validate Configuration is not run after changes have been made, and you attempt to exit the Configuration Editor window, an Exit Warning dialog box appears.
4. Select Yes to accept the changes and exit the Configuration Editor. Select No to discard the changes and exit the Configuration Editor. Select Cancel to return to the Configuration Editor.
C
5.4
Cancel Configuration
Select Cancel Configuration to exit the Configuration Editor window without making any configuration changes to the application file.
5.5
Application Name
The Application Name is printed on the first line of an application printout. The application name and the file name can be the same name or a different name.
Using a method described in Sections 5.1-1 through 5.1-4, select Application Name to display the current name of the application. Select Edit to display the Application
Name dialog box.
1. Enter or change the name for the current application.
Range : 1-8 characters
Default : No default value.
2. Select Ok to commit the name entered. Select Cancel to close the dialog box without entering or changing the application name.
5/3
5.6
Timers
For general information about Timers, see Section 2.2-3 in Part B.
Using a method described in Sections 5.1-1 through 5.1-4, select Timers. All of the
Timers are listed. Select the Timer to be configured. The Timers dialog box appears.
C
1. Enter the Timer number, if it is different from the one selected. For example, to identify timer %TM0, enter 0 in the Timer field.
Range : 0-31
2. The Symbol field is not active in this dialog box. This field is for information only.
You can only assign a symbol to a data variable in the Symbol Editor. For more information, see Section 6.
3. Select a Timer Type.
Range : TON (Timer On-delay), TOF (Timer Off-delay), TP (Timer Pulse).
Default : TON.
4. Select the Timebase value, which is the unit of time of the Timer.
Range : 1 millisecond (%TM0 and %TM1 only), 10 milliseconds, 100 milliseconds,
1 second, 1 minute.
Default : 1 minute
5. Select the Adjust value. Select Yes or No to indicate whether a user can adjust the
Preset value in the Data Editor.
Default : Yes
6. Select Previous or Next to scroll to the Timer listed just before or after the current
Timer without closing the Timers dialog box. These buttons are only shown when the Timers resource is accessed from the Configuration Editor window.
7. Select the Preset value.
Range : 0 to 9999
Default : 9999
8. Select Ok to commit the values selected or Cancel to close the dialog box without changing the configuration.
5/4
Configuring PLC resources 5
5.7
Counters
For general information about Counters, see Section 2.2-4 in Part B.
Using a method described in Sections 5.1-1 through 5.1-4, select Counters. All of the
Counters are listed. Select the Counter to be configured. The Counters dialog box appears.
1. Enter the Counter number, if it is different from the one selected. For example, to identify Counter %C8, enter 8 in the Counter field.
Range : 0 to 15
2. The Symbol field is not active in this dialog box. This field is for information only.
You can only assign a symbol to a data variable in the Symbol Editor. For more information, see Section 6.
3. Select the Adjust value. Select Yes or No to indicate whether a user can adjust the
Preset value in the Data Editor.
Default : Yes
4. Select a Preset value.
Range : 0 to 9999
Default : 9999
5. Select Previous or Next to scroll to the Counter listed just before or just after the current Counter without closing the Counters dialog box. These buttons are only shown when the Counters resource is accessed from the Configuration Editor window.
6. Select Ok to commit the values selected or Cancel to close the dialog box without changing the configuration.
C
5.8
Constants
For general information about Constants, see Section 3.1-1 in Part B.
Using a method described in Sections 5.1-1 through 5.1-4, select Constants. All of the
Constants are listed. Select the Constant to be configured. The Constants dialog box will display.
1. Enter the Constant number, if it is different from the one selected. For example, to identify Constant %KW2, enter 2 in the Constant field.
Range : 0-63
5/5
C
2. The Symbol field is not active in this dialog box. This field is for information only.
You can only assign a symbol to a data variable in the Symbol Editor. For more information, see Section 6.
3. Select a Value Format.
Range : Decimal, Hexadecimal, Binary, or ASCII.
Default : Decimal
4. Enter a value for the Value field, which is the value of the Constant.
Decimal Range : -32768 to 32767
Hexadecimal Range : 0000 - FFFF
Binary Range : 0000000000000000 to 1111111111111111
ASCII Range : Any ASCII character
Default : 0, decimal
5. Select Previous or Next to scroll to the Constant listed just before or after the current
Constant without closing the Constants dialog box. These buttons are only shown when the Constants resource is accessed from the Configuration Editor window.
6. Select Ok to commit the values selected or Cancel to close the dialog box without changing the configuration.
5.9
LIFO/FIFO Register
For general information about LIFO/FIFO Registers, see Section 2.2-5 in Part B.
Using a method described in Sections 5.1-1 through 5.1-4, select LIFO/FIFO Registers.
All of the registers are listed. Select the register to be configured. The LIFO/FIFO
Registers dialog box will display.
5/6
Configuring PLC resources 5
1. Enter the LIFO/FIFO Register number, if it is different from the one selected. For example, to identify LIFO/FIFO Register %R0, enter 0 in the Register field.
Range : 0-4
2. The Symbol field is not active in this dialog box. This field is for information only.
You can only assign a symbol to a data variable in the Symbol Editor. For more information, see Section 6.
3. Select the Register Type :
FIFO - The first data item entered in the register is the first to be retrieved, also known as a queue.
LIFO - The last data item entered in the register is the first to be retrieved, also known as a stack.
Default : FIFO
4. Select Previous or Next to scroll to the register listed just before or after the current register without closing the LIFO/FIFO Registers dialog box. These buttons are only shown when the LIFO/FIFO Register resource is accessed from the Configuration
Editor window.
5. Select Ok to commit the values selected or Cancel to close the dialog box without changing the configuration.
C
5.10
Drum Controllers
For general information about Drum Controllers, see Section 2.2-6 in Part B.
Using a method described in Sections 5.1-1 through 5.1-4, select Drum Controllers.
1. Enter the Drum number. For example, to identify Drum Controller %DR2, enter 2 in the Drum field.
Range : 0 to 3
2. The Symbol field is not active in this dialog box. This field is for information only.
You can only assign a symbol to a data variable in the Symbol Editor. For more information, see Section 6.
3. In the Num. Steps field, enter the number of steps in the drum.
The check boxes for the number of steps you define remain active. The other check boxes are grayed out. For example, if four steps are defined in the Num. Steps field, then the first four rows of check boxes are enabled.
Range : 1 to 8
4. In the Command bits field, assign either a physical bit or a memory bit to each of the 16 (0-15) logical bits that you want to use.
5/7
C
Range :
%Q0.0-%Q0.9 : Output bit on the base PLC.
%Q1.0-%Q1.9 : Output bit on an I/O PLC extension.
%M0-%M127 : Internal memory bit.
Default : No default values
5. For each step that you defined, click on the check boxes for each logical bit that you want to activate in each step. For example, if you run Step 0, three logical bits are activated : %Q0.1, %Q0.3, and %M8, as indicated by the "1" or ON indicator in each check box.
6. Select Previous or Next to scroll to the Drum Controller listed just before or just after the current Drum Controller without closing the Drum dialog box. These buttons are only shown when the Constants resource is accessed from the Configuration Editor window.
7. Select Ok to commit the values selected or Cancel to close the dialog box without changing the configuration.
5.11
Fast Counter
The Fast Counter is a single resource, which you can configure as one of three counter types : an Up Counter, a Frequency Meter, or an Up/Down Counter. For more information about the Fast Counter, see Section 4.4 in Part A and Section 3.4-5 in Part
B.
Using a method described in Sections 5.1-1 through 5.1-4, select Fast Counter.
5/8
Configuring PLC resources 5
5.11-1 Up Counter
For the Up Counter, the counting input is always from input %I0.0. The counting input is not configurable. When the state of input %I0.0 changes from 0 to 1, then the current value of the Fast Counter (%FC.V) is incremented by 1.
C
1. Select Up Counter in the Fast Counter Type field. The following fields become active.
• Preset Input
• Enable Input
• Threshold Outputs
• Threshold Zero
• Threshold One
• Max Frequency
2. The Symbol field is not active in this dialog box. This field is for information only.
You can only assign a symbol to a data variable in the Symbol Editor. For more information, see Section 6.
3. In the Preset Input field, select %I0.1 to dedicate input %I0.1 for the Up Counter function. When the state of input %I0.1 changes from 0 to 1, the current value of the
Up Counter (%FC.V) is set to 0. Select None if you do not want to use input %I0.1
as a dedicated input.
4. In the Enable Input field, select %I0.2 to dedicate input %I0.2 to the Up Counter function. If the state of %I0.2 is 1, the Up Counter is turned on; the counter counts pulses from input %I0.0 and updates the current value of the count. If the state of
%I0.2 is 0, then the Up Counter is disabled and the pulses at %I0.0 are ignored.
Select None if you do not want to use input %I0.2 as a dedicated input.
5/9
5. In the Threshold Outputs field, select %Q0.1 _%Q0.2 to dedicate these outputs for the Up Counter function. The state of these two outputs is a function of the Threshold
Zero and Threshold One values' (%FC.S0 and %FC.S1, respectively) relationship to the Fast Counter current value (%FC.V) as defined in the %Q0.1-2 States field.
For example, in the %Q0.1-2 States field shown :
C
When %FC.V is less than %FC.S0, output %Q0.1 is 1 and output %Q0.2 is 0.
When %FC.V is greater than %FC.S0 and less than %FC.S1, output %Q0.1 is 0 and output %Q0.2 is 1.
When %FC.V is greater than %FC.S1, output %Q0.1 is 1 and output %Q0.2 is 0.
Select None if you do not want to use outputs %Q0.1 and %Q0.2 as dedicated outputs.
6. In the Threshold Zero and Threshold One fields, enter the desired values.
Range : 0 to 65535
Default : 65535
7. In the Max Frequency field, select 5 kHz for normal mode or 10 kHz for fast mode.
8. Configure the relationship between %FC.S0-S1 and %Q0.1-2 in the %Q0.1-2
States field. %Q0.1 _%Q0.2 must be selected in the Threshold Outputs field for this field to be active. In each box, enter 0 or 1, as desired.
9. Select Ok to commit the values selected or Cancel to close the dialog box without changing the configuration.
5.11-2 Frequency Meter
For the Frequency Meter, the frequency counting input is from input %I0.0 and is not configurable.
1. Select Frequency in the Fast Counter Type field. The following fields become active.
• Enable Input
• Max Frequency
2. The Symbol field is not active in this dialog box. This field is for information only.
You can only assign a symbol to a data variable in the Symbol Editor. For more information, see Section 6.
3. For the Enable Input field, select %I0.2 to dedicate input %I0.2 to the frequency meter function. If %I0.2 is at 1, the frequency meter is turned on; that is, the input counts pulses and updates the current value of the count. If %I0.2 is 0, then the frequency meter is disabled and the pulses at %I0.0 are ignored. Select None if you do not want to use input %I0.2 as a dedicated input.
5/10
Configuring PLC resources 5
4. In the Max Frequency field, select 5 kHz for normal mode or 10 kHz for fast mode.
5. Select Ok to commit the values you selected or Cancel to close the dialog box without changing the configuration.
5.11-3 Up/Down Counter
For the Up/Down Counter, the up counting input is from input %I0.0. The down counting input is from %I0.3. Neither input is configurable.
1. Select Up/Down Counter in the Fast Counter Type field. The following fields become active.
• Preset
• Read Counter Input
• Preset Input
• Enable Input
• Threshold Outputs
• Threshold Zero
• Threshold One
• Adjust
2. The Symbol field is not active in this dialog box. This field is for information only.
You can only assign a symbol to a data variable in the Symbol Editor. For more information, see Section 6.
3. In the Preset field, select the number of events to be counted by the Up/Down
Counter.
4. In the Read Counter Input field, select %I0.4 to dedicate input %I0.4 for the Up/
Down Counter function. When input %I0.4 is 1 or ON, the current value of the fast counter is written to a system memory word in the program. Select None if you do not want to use input %I0.4 as a dedicated input.
5/11
C
C
5. In the Preset Input field, select %I0.1 to dedicate input %I0.1 for the Up/Down
Counter function. When the state of input %I0.1 changes from 0 to 1, the current value of the Up/Down Counter (%FC.V) is set to 0. Select None if you do not want to use input %I0.1 as a dedicated input.
6. In the Enable Input field, select %I0.2 to dedicate input %I0.2 to the Up/Down
Counter function. If the state of %I0.2 is 1, the Up/Down Counter is turned on; the counter counts pulses from inputs %I0.0 and %I0.3 and updates the current value of the count. If the state of %I0.2 is 0, then the Up/Down Counter is disabled and the pulses at %I0.0 and %i0.3 are ignored. Select None if you do not want to use input
%I0.2 as a dedicated input.
7. In the Threshold Outputs field, select %Q0.1 _%Q0.2 to dedicate these outputs for the Up/Down Counter function. The state of these two outputs is a function of the
Threshold Zero and Threshold One values' (%FC.S0 and %FC.S1, respectively) relationship to the Fast Counter current value (%FC.V) as defined in the %Q0.1-2
States field.
For example, in the %Q0.1-2 States field shown :
When %FC.V is less than %FC.S0, output %Q0.1 is 1 and output %Q0.2 is 0.
When %FC.V is greater than %FC.S0 and less than %FC.S1, output %Q0.1 is 0 and output %Q0.2 is 1.
When %FC.V is greater than %FC.S1, output %Q0.1 is 1 and output %Q0.2 is 0.
Select None if you do not want to use outputs %Q0.1 and %Q0.2 as dedicated outputs.
8. In the Threshold Zero and Threshold One fields, enter the desired values.
Range : 0 to 65535
Default : 65535
5/12
Configuring PLC resources 5
9. In the Adjust field, select Yes or No to indicate whether a user can adjust the Preset value in the Data Editor.
10. Configure the desired relationship between %FC.S0-S1 and %Q0.1-2 in the
%Q0.1-2 States field. %Q0.1 _%Q0.2 must be selected in the Threshold Outputs field for this field to be active. In each box, enter 0 or 1, as desired.
11. Select Ok to commit the values selected or Cancel to close the dialog box without changing the configuration.
5.12
%PLS
The %PLS/%PWM Pulse Generator function block is used as a square wave generator.
For %PLS, the on time equals the off time for a period (50% duty cycle). For %PWM, the signal width (duty cycle) can be varied. For more information about the Pulse
Generator, see Sections 4.5 and 4.6 in Part A and Sections 3.4-3 and 3.4-4 in Part B.
Using a method described in Sections 5.1-1 through 5.1-4, select %PLS/%PWM.
C
5.12-1 %PLS Configured
For the %PLS pulse generator, the output is from %Q0.0 and is not configurable.
1. In the %PLS/%PWM Configured field, select %PLS Configured. The following fields become active.
• Timebase
• Preset
• Adjust
2. The Symbol field is not active in this dialog box. This field is for information only.
You can only assign a symbol to a data variable in the Symbol Editor. For more information, see Section 6.
Note : If you configure either the %PLS or the %PWM, output %Q0.0 is dedicated to %PLS or
%PWM processing and should not be assigned to any other function in the program.
5/13
C
3. For the Timebase field, select the unit of time. When .1 ms is selected the %PLS
Counting Loop field becomes active.
Range : .1 ms, 10 ms, or 1 sec
Default : 1 second
4. In the Preset field, specify the length of the period in timebase units.
Range : If Timebase = 10 ms or 1 second, the value can be between 0 and 32767.
If Timebase = 0.1 ms, the value can be between 0 and 255.
Default : 0
5. Select the Adjust value and then select Yes or No to indicate whether a user can adjust the Preset value in the Data Editor.
6. If .1 ms was selected in the Timebase field, the %PLS Counting Loop field becomes active.
Select Yes to implement the Fast Counter. The period of the pulse is less than the total scan time, requiring auxiliary processing from the Fast Counter. For the %PLS to work properly, physically loop output %Q0.0 to input %I0.0.
Select No if you choose not to loop to the Fast Counter to perform auxiliary processing.
7. Select Ok to commit the values selected or Cancel to exit the dialog box without changing the configuration.
5.12-2 %PWM Configured
For the %PWM pulse generator, the output is from %Q0.0. This is not configurable.
1. In the %PLS/%PWM Configured field, select %PWM Configured. The following fields become active.
• Timebase
• Preset
2. The Symbol field is not active in this dialog box. This field is for information only.
You can only assign a symbol to a data variable in the Symbol Editor. For more information, see Section 6.
3. For the Timebase field, select the unit of time.
Range : .1 ms, 10 ms, or 1 sec
Default : 1 second
5/14
Configuring PLC resources 5
4. In the Preset field, specify the length of the period in timebase units.
Range : 0 to 9999
Default : 0
5. Select Ok to commit the values selected or Cancel to close the dialog box without changing the configuration.
5.13
Input Filters
Input Filters is used to reduce the effect of noise on the input. For more information, see
Section 1.7-1 in Part A.
Using a method described in Sections 5.1-1 through 5.1-4, select Input Filters.
C
1. In each input field, %I0.0-3, %I0.4-7, and %I0.8-13, select No Filter, 3 ms, or 12 ms.
If No Filter is selected, the input filtering device is not activated on the inputs.
If 3 ms is selected, any pulses which are 3 ms or less in duration are filtered.
If 12 ms is selected, any pulses which are 12 ms or less in duration are filtered.
Default : 12 ms
2. Select Ok to commit the values selected or Cancel to exit the dialog box without changing the configuration.
5.14
Latch Input
Latch Input captures and records an incoming pulse on an input. For more information, see Section 4.3 in Part A.
Using a method described in Sections 5.1-1 through 5.1-4, select Latch Input. The current Latch Input configuration is displayed. Select Edit to display the Latch Input dialog box.
5/15
C
1. For each input, %I0.0 through %I0.5 :
Select Yes to enable Latch Input processing for the selected input.
Select No to disable Latch Input processing for the selected input.
Default : No
2. Select Ok to commit the values selected or Cancel to exit the dialog box without changing the configuration.
5.15
Run/Stop Input
Run/Stop is used to start or stop the PLC from an external input. A stop command from the PL7-07 PC programming software or the FTX 117 overrides a run command from the Run/Stop input. For more information, see Section 4.1 in Part A.
Using a method described in Sections 5.1-1 through 5.1-4, select Run/Stop Input.
1. Select the desired input to the PLC for the Run/Stop input.
Range : Inputs %I0.0 through %I0.5
Default : None
2. Select Ok to commit the values selected or Cancel to exit the dialog box without changing the configuration.
5/16
Configuring PLC resources 5
5.16
PLC Status (Security)
Use PLC Status (Security) to configure an output to indicate whether the PLC is running.
For more information, see Section 4.2 in Part A.
Using a method described in Sections 5.1-1 through 5.1-4, select PLC Status
(Security).
1. In the PLC Status (Security) field, select a designated output to provide the status of the PLC.
Range : Outputs %Q0.0 through %Q0.3
Default : None
2. Select Ok to commit the values selected or Cancel to exit the dialog box without changing the configuration.
5.17
Scan Mode
Use Scan Mode to define whether you want to scan your program in normal or periodic mode. For more information, see Section 1.3 in Part A.
Using a method described in Sections 5.1-1 through 5.1-4, select Scan Mode.
C
1. In the Scan Mode field :
Select Normal to scan a program one operational cycle after another, regardless of the length of the scan.
5/17
Select Periodic to define the minimum rate at which the CPU scans a program in the PLC. You define the minimum rate in the Period field.
Default : Normal
2. In the Period field, type a value from 2 to 150 milliseconds.
Default : None
3. Select Ok to commit the values selected or Cancel to exit the dialog box without changing the configuration.
C
5.18
Schedule Blocks
For general information about Schedule Blocks, see Section 5.2 in Part B.
Using a method described in Sections 5.1-1 through 5.1-4, select Schedule Blocks.
1. Select the Configured box to activate all fields in the dialog box.
2. Enter the Schedule Block Number. You can define up to 16 schedule blocks in a program.
Range : 0-15.
3. Enter an Output Bit address. For example, if you are configuring a sprinkler to turn on, enter the address of the output terminal connected to the sprinkler system.
4. Select the Start Month (the month that you want to activate the schedule block output).
5. Select the End Month (the month that you want to de-activate the schedule block output).
6. Select the Start Date (the day of the month that you want to activate the schedule block output).
7. Select the End Date (the day of the month that you want to de-activate the schedule block output).
5/18
Configuring PLC resources 5
8. Select the Days of Week that you want to activate the schedule block output.
Checked boxes indicate the days that the output device is activated.
9. Enter the Start Time (the hour that you want to activate the schedule block output).
Default : 00:00
10. Enter the End Time (the hour that you want to de-activate the schedule block output).
Default : 23:59
11. Select Previous or Next to scroll to the Schedule Block listed just before or just after the current Schedule Block without closing the Schedule Block dialog box. These buttons are only shown when the Schedule Block resource is accessed from the
Configuration Editor window.
12. Select Ok to commit the values selected or Cancel to exit the dialog box without changing the configuration.
C
5.19
Extension Port
Use Extension Port to define the PLC communications configuration.
Using a method described in Sections 5.1-1 through 5.1-4, select Extension Port.
Select PLC Extension to configure the I/O extension link or Modbus Slave for a Modbus
Slave type link.
PLC Extension :
1. The Extension field is used to detect communication errors with the I/O extension.
Select Yes if you want the base PLC to generate an error when communication is not possible with the I/O extension.
5/19
Configuring PLC resources 5
C
Select No if you do not want the base PLC to generate an error when no communication is received from one of the PLCs defined in the dialog box.
Default : No
2. In the Bits/sec field, indicate the speed at which you want connected PLC units to communicate. Communication quality decreases, or becomes less reliable, as distance increases or as electrical noise in the environment increases. Therefore, when communicating across large distances or in a noisy environment, decrease the communication rate to increase reliability.
Note
The same speed must be configured for all PLCs in the same Nanet network.
Select 9600 bits per second if the distance between PLC units is relatively large or if there is a substantial amount of electrical noise in the environment.
Select 19200 bits per second if the distance between PLC units is relatively short or if there is relatively little electrical noise in the environment.
Default : 19200
3. In the I/O Extension field, indicate whether you have a PLC configured and connected as an I/O extension. The I/O Extension supplies additional inputs and outputs to the base PLC. For more information, see Section 3.5 in Part A.
Default : No
5. In the PLC2, PLC3, and PLC4 fields, select Yes or No to indicate whether you have a corresponding PLC configured as a peer PLC connected to the base PLC.
Defaults : No
6. Select Ok to commit the values selected or Cancel to exit the dialog box without changing the configuration.
Modbus Slave : (see Section F-2.1)
1. The Bits/sec field indicates the data rate of the Modbus link.
2. The Slave Address field configures the address of the TSX Nano Modbus slave
(1 to 98).
3. The Time-out (Char) field sets the parameters for the intercharacter time (1 to 127 characters).
4. The Data Bits field selects ASCII mode (7 bits) or RTU mode (8 bits).
It specifies the size of the data on the line.
5. The Parity field defines the addition or not of a parity bit as well as its type.
6. The Stop Bits field specifies the number of stop bits used.
Note
These parameters should be the same as those for the Modbus link Master.
5/20
5.20
Programming Port
Use the programming port box to select the type of protocol for the TSX Nano PLC programming port.
ASCII mode
Select ASCII to configure the TSX Nano terminal port in ASCII mode.
1: The Bits/sec field specifies the transmission speed of data on the line.
Available speeds are : 1200, 2400, 4800, 9600 and 19200 bits/second.
2: The Data Bits field selects the size of the data exchanged on the line.
3: The Parity field defines the addition or not of a parity bit as well as its type.
4: The Stop Bits specifies the number of stop bits used.
5: The UNI-TELWAY Time-out (Char.) field is used to set the value of the Uni-telway time-out.
UNI-TELWAY Slave mode
Select UNI-TELWAY Slave to configure the TSX Nano terminal port in UNI-TELWAY
Slave mode :
1: The UNI-TELWAY slave address field is used to select the AD0 link address of the
TSX Nano.
The PLC uses 2 consecutive logic addresses :
AD0 : base address (configuration address) is the server address, which all the
UNI-TELWAY bus devices use to send requests to the TSX Nano.
AD1: AD0+1 is the client address used by the EXCH block to send requests to other
UNI-TELWAY bus devices.
2: The other fields are the same as for ASCII mode and should be identical to those of the UNI-TELWAY bus Master.
5/21
C
UNI-TELWAY Master mode
The format of this protocol is fixed. Only the Time-out can be configured (30 to 255).
To configure Time-out in UNI-TELWAY Master mode, modify its value in the UNI-TELWAY
Time-out (Char.) field.
5.21
Change PLC Version
C
Use the Change PLC Version options to specify the model number or version of the
TSX Nano Programmable Logic Controller that you are using as the base PLC.
Using a method described in Sections 5.1-1 through 5.1-4, select Change PLC
Version. The PLC Version Management dialog box appears.
1. Locate the model number or version of your TSX Nano PLC on the left side panel :
TSX 2A/2B : version 1 of the TSX Nano PLC.
TSX 2x or 3x without MCR/MCS : Provides all functionality, except the Master
Control Relay functions.
TSX 2x or 3x with MCR/MCS : Provides all functionality, including the Master Control
Relay functions. Use of this function will slightly improve performance.
Default : TSX 2x or 3x without MCR/MCS
2. Select Ok to commit the values selected or Cancel to exit the dialog box without changing the PLC version.
5/22
Section 6
6 Defining symbols
6.1
Introduction
In the Symbol Editor, you assign easily recognizable alphanumeric names, called symbols, to data variables in your program. Symbols can help you quickly examine and analyze your program logic, greatly simplifying the development and testing process.
You can display the Symbol Editor offline and online, but it is restricted in the monitor state.
6.2
Selecting the Symbol Editor
To display the Symbol Editor window, select Symbol Editor from the View menu.
C
6.3
Using the Symbol Editor Tools menu
The Symbol Editor window is used for defining symbols for the program addresses. The table in appendix A.2-2 in part G lists the options on the Symbol Editor Tools menu and the corresponding buttons on the tool bar.
6.3-1 Validate Program
Validate Program is used to compile a program and check for errors. For more information, see section 10.1, "Validating a program."
6/1
6.3-2 Insert
Insert is used to add an object to the symbol table.
1. From the Symbol Editor window, select Insert. The Object Browser dialog box is displayed.
C
2. In the Address field, enter the variable address that you want the symbol to represent. You can enter an address in two ways.
• If you know the address, you can type it directly in the Address field selection box.
• To assist you in selecting the correct address, open the Filter list box and select a variable type.
The Address list box automatically lists all instances of the type selected.
3. In the Symbol field, type a symbol that describes the variable, such as
BOTTLE_COUNTER.
Guidelines:
• A symbol cannot be longer than 32 characters.
• A symbol can only contain letters (A-Z), numbers (0-9), underscores (_) and some accented characters. When an unauthorized character is entered, a dialog box appears on the screen to help the user. The authorized characters correspond to page 850 of the code.
( u n d e r l i n i n g )
• A symbol must start (first character) with an alphabetical or accented character.
• A symbol cannot have any spaces or special characters.
• A symbol is not case sensitive. For example, the symbol names Pump1 and
PUMP1 are the same symbol and can only occur once in an application.
4. In the Comment field, type a description of the variable up to 128 characters.
5. If you want to configure the defined variable, select the Configure button. The appropriate dialog box appears. For more information, see section 5.
6. Select Previous or Next to select the object just before or after the current object in the symbol table.
7. Select Ok to commit the values or Cancel to exit the dialog box and return to the
Symbol Editor window.
6/2
Defining symbols 6
6.3-3 Delete
Delete is used to remove an object from the symbol table.
1. Select the object to be removed from the symbol table. Select Delete. A Warning dialog box appears to prompt you to confirm the deletion.
2. Select Ok to delete the object or Cancel to exit the dialog box and return to the
Symbol Editor window.
6.3-4 Sort by Address
Sort by Address is used to list the symbol table, in alphabetic and numeric order, by address.
1. From the Symbol Editor window, select Sort by Address.
2. The symbol table is listed, in alphabetic and numeric order, by address.
C
6.3-5 Sort by Symbol
Sort by Symbol is used to list the symbol table, in alphabetic order, by symbol.
1. From the Symbol Editor window, select Sort by Symbol.
2. The symbol table is listed, in alphabetic order, by symbol.
6.4
Using the Symbol Editor Edit menu
With the Symbol Editor window open, Find is the only function that is available from the
Edit menu.
Find is used to locate a symbol or address in the symbol table.
1. From the Symbol Editor window, select Find. The Find dialog box is displayed.
2. In the Find dialog box, enter the symbol or address to be located.
3. Select Ok to initiate the search or Cancel to return to the symbol table.
If the symbol or address is found, the symbol table is displayed with the line containing the symbol or address highlighted.
6/3
4. For the case where you are trying to locate by symbol, if the symbol is not found, a Warning dialog box is displayed with the message: "Symbol not found. Would you like to create it?"
Select Ok to display the Object Browser dialog box to create the symbol. Select
Cancel to return to the symbol table.
5. For the case where you are trying to locate by address, if the address is not found, the Object Browser dialog box is displayed with the desired address shown in the
Address field.
C
6.5
Editing a symbol
A symbol that has no variable address is an unresolved symbol. You can write a program with unresolved symbols, while you design your program logic, and then complete the symbol table after you complete the program. You can also choose to define symbols in the Symbol Editor before you write a program or while you write a program.
For example, in the program function block displayed in the List Editor, the symbol
BOTTLE_COUNTER has no assigned address and is an unresolved symbol.
Select Symbol Editor from the View menu to display the symbol, BOTTLE_COUNTER, in the symbol field.
To define (or resolve) the symbol with an address:
1. Select the symbol in the Symbol Editor window to display the Object Browser dialog box.
6/4
Defining symbols 6
2. In the Address field, assign an address to the symbol. If the address is already assigned, an Error dialog box is displayed indicating a duplicate entry exists. Select
Ok to return to the Object Browser dialog box to assign another address.
3. After assigning the address to the symbol and making any other entries in the Object
Browser dialog box, select Ok to commit the values or Cancel to exit the dialog box without making any changes.
4. After assigning addresses to unresolved symbols, Validate Program must be run to allow you to toggle between Show Addresses and Show Symbols in the List Editor window.
Note: When editing an existing symbol, if you re-name the symbol to a name not previously used as a symbol and use an address that is already assigned to an existing symbol, the new symbol name will be assigned to the existing address.
C
6/5
C
6/6
Section 7
7 Developing a Ladder program
7.1
Introduction
The PL7-07 PC programming software provides a user-friendly method for programming in the Ladder format.
A ladder program is framed vertically by the power and return rails. Ladder rungs start on the left with the first connection of the rung to the power rail and end on the right with the outputs connected to the return rail.
Easily distinguishable icons located on tool bars and instruction bars allow the programmer to quickly and accurately build and edit the Ladder program. The selection and placement of the Ladder elements can be done with either the mouse or the keyboard.
Editing of the Ladder diagram is done using a two-window format. The top window is the Ladder Editor and the bottom window is the Ladder Viewer. You use the Ladder
Editor to insert and edit rungs. The Ladder Viewer window is used to scroll through and view a program. Before you begin to write a program, the Ladder Viewer displays the first rung number, Rung 0, and the END OF PROGRAM delimiter.
C
7/1
7.2
Configuring the Ladder Editor
To configure the Ladder editor :
1. Select Preferences from the View menu to display the Preferences dialog box.
C
2. In the Editing field, select Ladder.
3. After selecting Ladder in the Editing field, the Ladder Information field becomes active.
Select 1 line to display one line of either the symbol or address, depending on which one is selected in the Display Attributes field, defined in step 5.
Select 3 lines (symbols AND addresses) to display three lines with the symbol and the address at the same time. This option affects coils and contacts only. List rungs, compare blocks, and operate blocks will show only one line; either Symbols or
Addresses depending on which one is selected in the Display Attributes field.
Select 3 lines (symbols OR addresses) to display three lines of either the symbol or the address, depending on which one is selected in the Display Attributes field, defined in step 5. This option affects coils and contacts only. List rungs, compare blocks, and operate blocks will show only one line; either Symbols or Addresses depending on which one is selected in the Display Attributes field.
4. You animate a program to display the current value of a variable in the PLC.
In the List/Ladder Animation box, select Hexadecimal or Decimal format for displaying the current values when the program is animated.
5. In the Display Attributes field, select the desired attribute, either Symbols or
Addresses, to be displayed. When 3 lines (symbols AND addresses) is selected in the Ladder Information field, both attributes are displayed. Only coils and contacts are affected. List rungs, compare blocks, and operate blocks will show only one line.
6. Select Display Toolbars to display the tool bars in all editor windows.
7. Select Close Ladder viewer on Edit rung to display the full-screen Ladder editor when program modifications are being entered. The Ladder viewer will automatically reopen when the Ladder editor window is closed.
8. Select Ok to commit the values you selected. Select Cancel to exit the dialog box without changing the preferences selected.
7/2
(1)
(2)
(3)
(4)
(5)
Developing a Ladder program 7
7.3
Using the Ladder Editor
1. Select Ladder Editor from the View menu. The Ladder Viewer window is displayed.
2. To display the Ladder Editor, select Insert Rung from the Tools menu.
Above each rung is a rung header. The rung header displays the rung number and can, optionally, display a title, a label or subroutine declaration, and comments. In the Ladder Viewer window the rung header can be toggled on or off using Toggle Rung Header.
The status bar is located at the bottom of the screen. The left side displays any error or informational messages that may occur from the entry of a program rung.
The two-window Ladder programming environment has two tool bars and one instruction bar.
C
(6)
(1) Ladder Editor tool bar
(2) Ladder Editor instruction bar
(3) Rung header
(4) Programming grid
(5) Ladder Viewer tool bar
(6) Error message status bar
The icons on the tool bars correspond to options in the Tools menu. The Tools menu changes depending on which window is active. The Ladder Editor and Ladder Viewer each have a separate Tools menu.
The tables shown in appendix A.2-3 and A.2-3.1 in part G list the instructions that are available from the Ladder Editor instruction bar. The right side of the Ladder Editor instruction bar gives the name of the instruction that is selected.
7/3
7.4
Inserting a graphic instruction
extended ladder palette
left section middle section right section
C
7.4-1 Rules for inserting graphic instructions
The following are rules for inserting graphic instructions in a Ladder rung :
1. From left to right, there are eleven columns in the grid. The graphic instructions located in the left section of the Ladder Editor instruction bar cannot be inserted in the last column of the grid. Additionally, the compare block instruction, which takes up two cells, cannot be inserted in the last two columns of the grid.
2. The coil, inverse coil, reset coil, set coil, and jump/subroutine call instruction can only be inserted in the last column of the grid. If you try to insert these instructions anywhere else, a horizontal connector line is automatically inserted from that point to the last column, where the instruction will be inserted.
3. The operate block, which takes up four cells, can only be inserted in the last four columns of the grid. If you try to insert this instruction anywhere else, a horizontal connector line is automatically inserted from that point to the last four columns, where the block will be inserted.
4. The timer and counter blocks, each which take up two horizontal cells, cannot be inserted in the first column of the grid or the last two columns of the grid.
5. The special contacts, located on the left side of the Extended Ladder Palette, cannot be inserted in the first and last column of the grid. The exceptions to this are the Open and Short special contacts, which can be inserted in the first column of the grid.
6. The function blocks, located on the Extended Ladder Palette, each of which take up two horizontal cells, cannot be inserted in the first column or the last two columns of the grid.
There can only be one function block per rung.
7/4
Developing a Ladder program 7
7. The special coils, located on the right side of the Extended Ladder Palette, can only be inserted in the last column of the grid. If you try to insert these instructions anywhere else, a horizontal connector line is automatically inserted from that point to the last column, where the instruction will be inserted.
The Ladder Editor instruction bar is used for inserting graphic instructions.
To insert graphic instructions from the Ladder Viewer window :
1. Select Insert Rung from the Tools menu to display the Ladder Editor above the
Ladder Viewer window.
2. If you want the programming grid to show, toggle the grid on from the Tools menu or from the icon in the Ladder Editor tool bar.
The graphic instructions can be entered either by using the mouse or the keyboard.
C
7.4-2 Inserting graphic instructions using the mouse
1. Select an instruction from the instruction bar by pointing to the instruction and clicking the left mouse button. The instruction name appears in the right section of the Ladder Editor instruction bar.
For instructions on the Extended Ladder Palette, select the graphic instruction for the palette from the instruction bar. The Extended Ladder Palette display appears.
Select the desired instruction from the palette using the left mouse button. The
Ladder Editor window appears with the selected instruction's name listed in the right section of the instruction bar.
2. Place the instruction by pointing to the cell and clicking the right mouse button.
The instruction selected stays active until another instruction is selected. To insert the same instruction in another cell, point to the cell and click the right mouse button.
If you insert an instruction in a cell that already has an instruction, the previous instruction is overwritten.
3. Press <delete> to remove an instruction from a selected cell.
7.4-3 Inserting graphic instructions using the keyboard
1. Select an instruction from the instruction bar using the listed function key. For example, press F2 to select a normally open contact. The name of the instruction will appear in the right section of the instruction bar.
For instructions on the Extended Ladder Palette, hold down the <shift> key and press F10. The Extended Ladder Palette appears. Select the desired instruction.
The Ladder Editor window appears with the selected instruction's name listed in the right section of the instruction bar.
2. Select a cell in the Ladder Editor window using the arrow keys. Insert the instruction in the cell by pressing the <spacebar>.
The instruction selected stays active until another instruction is selected. To insert the instruction in another cell, select the cell and press the <spacebar>.
7/5
If you insert an instruction in a cell that already has an instruction, the previous instruction is overwritten.
3. Press <delete> to remove an instruction from a selected cell.
The following summarizes how to select and insert a graphic instruction, using either the mouse or the keyboard.
Select
Select Place
C
PlaceCursor
Keys
7.5
Inserting specific contacts, coils, and function blocks
7.5-1 Inserting a contact
A contact can be inserted in any column except the last column of the grid. To insert a normally open contact, normally closed contact, rising edge contact, or falling edge contact :
1. Select the contact from the instruction bar or by pressing the corresponding function key.
2. Place the contact by clicking the right mouse button in a cell. Or, select a cell with the cursor keys and press the <spacebar>.
3. To complete the programming of the contact, insert an operand or symbol as described in Section
7.6.
7/6
Developing a Ladder program 7
7.5-2 Inserting a coil or jump/subroutine call
A coil or jump/subroutine call can only be inserted in the last column of the grid. To insert a coil, inverse coil, reset coil, set coil, or jump/subroutine call :
1. Select the coil or jump/ subroutine call from the instruction bar or by pressing the <shift> key plus the corresponding function key.
C
2. Select the cell after the last graphic instruction in the rung.
3. Place the coil or jump/ subroutine call by clicking the right mouse button in the cell, or select the cell with the cursor keys and press the <spacebar>.
The horizontal connector is inserted automatically and the coil is inserted in the last cell.
4. To complete the programming of the coil, insert an operand or symbol as described in Section 7.6.
7/7
7.5-3 Inserting a timer or counter block
A timer or counter block cannot be inserted in the first column or the last two columns of the grid.
1. Select the timer or counter block from the instruction bar or by pressing the <shift> key plus the corresponding function key.
C
2. Place the contact by clicking the right mouse button in a cell. Or, select a cell with the cursor keys and press the <spacebar>.
The timer or counter block is inserted
3. To complete the programming of the timer or counter block, configure the block as described in Section 5.
7/8
Developing a Ladder program 7
7.5-4 Inserting and removing a down connector
To insert a down connector :
1. Insert the desired instruction, such as a normally open contact, in the rung.
2. Select the down connector from the instruction bar or by pressing F7.
3. The down connector appears on the right side of the cell just below the cell selected.
Point to the highlighted cell and click the right mouse button. Click the right mouse button again if you want to remove the down connector.
C
4. To remove a down connector after it has already been placed, select erase down connector from the instruction bar or by pressing F8.
5. Point to the cell above and to the left of the down connector and click the right mouse button.
7.5-5 Inserting a comparison block
A comparison block cannot be inserted in the last two columns of the grid.
1. Select the comparison block from the instruction bar or by pressing F10.
7/9
2. Place the comparison block by clicking the right mouse button in the cell. Or, select the cell with the cursor keys and press the <spacebar>.
The comparison block is inserted.
3. To complete the programming of the comparison block, insert an operation string as described in Section 7.6.
C
7.5-6 Inserting an operate block
An operate block is used for numerical instructions. An operate block can only be inserted in the last four columns of the grid. If you try to insert this instruction anywhere else, a horizontal connector line is automatically inserted from that point to the last four columns, where the block is inserted.
1. Select the operate block from the instruction bar or by pressing <shift>
+ F7.
2. Place the operate block by clicking the right mouse button in the cell.
Or, select the cell with the cursor keys and press the <spacebar>.
The operate block is inserted.
3. To complete the programming of the operate block, insert an operation string as described in Section
7.6.
7/10
Developing a Ladder program 7
7.5-7 Inserting special instructions from the Extended Ladder Palette
The Extended Ladder Palette contains special contacts, function blocks, and special coils. To insert an instruction from the Extended Ladder Palette :
1. Select the Extended Ladder Palette (+... instruction) from the instruction bar or by pressing <shift> + F10. The Extended Ladder Palette appears.
C
2. Select the desired instruction. The Extended Ladder Palette closes and the selected instruction's name appears on the right side of the instruction bar.
3. Place the instruction in the desired location.
7.6
Inserting an operand or symbol
Simple Ladder instructions, such as contacts and coils, use a single operand. However, some instructions, such as compare and operate blocks, require multiple operands with operators or option calls, called operation strings. For example, "%MW50 :=
%MW3 + %KW5" in an operate block or "%MW15<0" in a compare block are operation strings. You enter operation strings directly from the keyboard, just as you do when you specify a single operand.
To insert an operand or a symbol above a contact or coil instruction :
1. Select the cell and double-click with the mouse pointer or use the arrow keys to select the cell and press
<enter>. A rectangular box appears above the instruction.
Note : The % character appears automatically when Show Addresses is selected in the Ladder Viewer Tools menu
7/11
2. Type the operand or symbol in the rectangular box. Press <enter>. The rectangular box closes and the operand or symbol appears above the instruction.
C
To insert an operation string in a comparison or operate block :
1. Select the comparison or operate block and double-click with the mouse pointer or use the arrow keys to select the cell and press <enter>. A rectangular box appears in the block.
2. Type the operation string in the rectangular box. Press <enter>. The rectangular box closes and the operand appears in the comparison or operate block.
Note :
When it is not possible to see the online instruction or symbol in the rung, the whole instruction or symbol is displayed in the status bar at the bottom of the editor (Ladder Viewer).
7/12
Developing a Ladder program 7
7.7
Inserting a rung title, label, or comments
1. Select a rung header by double-clicking with the mouse pointer or use the arrow keys to select the rung header and press <enter>. The Rung Header dialog box appears.
2. In the Rung Header Type field, select one of three options :
Select Standard to display only the rung number, the title, and comments.
Select Label to designate the rung as a jump destination. A label (%Li:) is used with a jump instruction as a jump destination. The label is displayed beneath the rung number in the header. See Section 2.4-3 in part B for more information about jump instructions.
Select Subroutine to designate the rung as a call destination. The subroutine label
(SRn:) is used in a program as a call destination. See Section 2.4-3 in part B for more information about subroutine instructions.
3. If either the Label or Subroutine header type is selected, the Label or Subroutine
Number field becomes active.
In the Label or Subroutine Number field, declare the identifying number for the label or subroutine. For example, to declare subroutine number 7, select the
Subroutine header type and enter 7 in the Label or Subroutine Number field. If you enter a value that is already used elsewhere in the program, an error message is displayed when you press Ok.
4. In the Title field, enter up to 122 characters to describe the purpose of the rung.
5. In the Comment field, enter up to 4 lines of 122 characters of text to further document the purpose of the rung.
6. Select Ok to close the Rung Header dialog box and update the Ladder Viewer.
Select Cancel to close the dialog box, leaving the rung header unchanged.
C
7/13
7.8
Using the Ladder Editor Tools menu
The Ladder Editor window is used for inserting, creating, and editing rungs in a ladder program. The table shown in appendix A.2-4 in part G lists the options on the Ladder
Editor Tools menu and the corresponding buttons on the tool bar.
C
7.8-1 Validate Program
Use Validate Program to compile a program and check for errors. See Section 10.1 for more details on validating a program.
7.8-2 Validate Rung
Use Validate Rung to validate an individual rung from the Ladder Editor window.
1. Select Validate Rung from the Ladder Editor Tools menu or the Ladder Editor tool bar.
2. If the rung does not have any errors, the Ladder Editor window closes and the
Ladder Viewer window is updated with the validated rung.
3. If the rung has errors, an error message appears describing the error.amme.
7.8-3 Cancel Rung
Use Cancel Rung to exit the Ladder Editor window and return to the Ladder Viewer window, without adding any changes to the current rung.amme.
7.8-4 New Rung
Use New Rung to validate and store the current rung in the Ladder program and start a new rung.
1. Select New Rung from the Ladder Editor tools menu or the Ladder Editor tool bar.
2. The Ladder Editor window is cleared for the insertion of a new rung. The rung number will be the next sequential number in the Ladder program. The Ladder
Viewer window displays the validated rung updated from the Ladder Editor window.
7/14
Developing a Ladder program 7
7.8-5 Clear Rung
Use Clear Rung to clear the current rung in the Ladder Editor window. The Ladder Editor window remains open with an empty programming grid.
1. Select Clear Rung from the Ladder Editor tools menu or the Ladder Editor tool bar.
2. The Ladder Editor window displays the current rung cleared of all previous instructions.
7.8-6 Previous Rung
Use Previous Rung to validate and store the current rung and select the preceding rung.
1. Select Previous Rung from the Ladder Editor tools menu or Ladder Editor tool bar.
2. The current rung is validated and stored to the Ladder program. The Ladder Editor window then displays the rung preceding the current rung.
C
7.8-7 Next Rung
Use Next Rung to validate and store the current rung and select the following rung in the Ladder program.
1. Select Next Rung from the Ladder Editor tools menu or the Ladder Editor tool bar.
2. The current rung is validated and stored to the Ladder program. The Ladder Editor window then displays the following rung.
7.8-8 Toggle Grid
Use Toggle Grid to switch from having the grid displayed to having it not displayed in the Ladder Editor window.
1. Select Toggle Grid from the Ladder Editor Tools menu or from the Ladder Editor tool bar.
2. The Ladder Editor window is displayed without the grid. Select Toggle Grid again to display the grid.
7/15
7.9
Using the Ladder Viewer Tools menu
The Ladder Viewer window is used to display and view a program. The Tools menu for this window has a few editing options and many display options. The table in appendix A.2-5 in part G lists the options on the Ladder Viewer Tools menu and the corresponding buttons on the tool bar.
C
7.9-1 Validate Program
Use Validate Program to compile a program and check for errors. See Section 10.1 for more details on validating a program.
7.9-2 Insert Rung
Use Insert Rung to insert a new rung just before the rung selected in the Ladder Viewer window.
To insert a rung :
1. Select the location where the new rung will be inserted. Select Insert Rung from the Ladder Viewer Tools menu or from the Ladder Viewer tool bar. The Ladder
Editor window appears above the Ladder Viewer window.
7.9-3 Insert List
Use Insert List to insert a new rung just before the rung selected using the List Rung
Editor.
1. Select the location where the new rung will be inserted. Select Insert List from the
Ladder Viewer Tools menu. The List Rung Editor window appears.
2. After entering the desired instructions in the List Rung Editor window, select
Validate to check the new rungs for errors and reversibility warnings. Select Ok to return to the Ladder Viewer window with the new rung shown in the Ladder format.
Select Cancel to return to the Ladder Viewer window without adding the new rung.
If the rung inserted using the List editor is not reversible, the new rung in the Ladder
Viewer window displays the List instructions instead of the Ladder format. Reversibility rules are explained in Sections 7.4 and 7.5 of part B.
7/16
Developing a Ladder program 7
7.9-4 Edit Current Rung
Use Edit Current Rung to make changes to the selected rung.
1. Select the rung to be edited. Select Edit Current Rung from the Ladder Viewer Tools menu or from the Ladder Viewer tool bar. The selected rung is displayed in the
Ladder Editor window. It is also possible to open the Ladder Editor window by double-clicking on the rung with the left-hand mouse button.
C
7.9-5 Delete Current Rung
Use Delete Current Rung to remove the selected rung or block of rungs (highlighted) from the Ladder program. This includes the rung, rung header, and any label or subroutine declarations.
1. Select the rung to be deleted. Select Delete Current Rung from the Ladder Viewer
Tools menu or from the Ladder Viewer tool bar.
2. The Ladder Viewer window will update with the selected rung deleted.
7.9-6 Show Symbols
Use Show Symbols to display the symbols for instructions in the Ladder program. Either one or three lines of symbols are displayed, depending upon the option selected as described in Sections 7.9-8, 7.9-9, or 7.9-10.
1. Select Show Symbols from the Ladder Viewer Tools menu or from the Ladder
Viewer tool bar.
2. The symbols will be displayed above the instructions in either a one-line or threeline format.
7.9-7 Show Addresses
Use Show Addresses to display the address for instructions in the Ladder program.
Either one or three lines of addresses are displayed, depending upon the option selected as described in Sections 7.9-8, 7.9-9, or 7.9-10.
1. Select Show Addresses from the Ladder Viewer Tools menu or from the Ladder
Viewer tool bar.
2. The address will be displayed above the instructions in either a one-line or threeline format.
7/17
7.9-8 1 Line Address or Symbol
Use 1 Line Address or Symbol to display one line of either the address or symbol, depending on which one is selected as described in Sections 7.9-6 and 7.9-7.
1. Select 1 Line Address or Symbol from the Ladder Viewer Tools menu or from the
Ladder Viewer tool bar.
2. The addresses or symbols will be displayed above the instructions in a one-line format.
C
7.9-9 3 Lines Address or Symbol
Use 3 Lines Address or Symbol to display three lines of either the address or symbol, depending on which one is selected as described in Sections 7.9-6 and 7.9-7. This option affects coils and contacts only. List rungs, compare blocks, and operate blocks will show only one line; either Symbols or Addresses depending on which one is selected in the Display Attributes field of the Preferences dialog box.
1. Select 3 Lines Address or Symbol from the Ladder Viewer Tools menu or from the
Ladder Viewer tool bar.
2. The addresses or symbols will be displayed above the instructions in a three-line format.
7.9-10 3 Lines Address and Symbol
Use 3 Lines Address and Symbol to display three lines of both the address and symbol.
This option affects coils and contacts only. List rungs, compare blocks, and operate blocks will show only one line; either Symbols or Addresses depending on which one is selected in the Display Attributes field of the Preferences dialog box.
1. Select 3 Lines Address and Symbol from the Ladder Viewer Tools menu or from the Ladder Viewer tool bar.
2. The addresses and symbols will be displayed above the instructions in a three-line format. The symbols will be listed above the addresses.
7.9-11 Toggle Rung Header
Use Toggle Rung Header to switch from having the rung headers displayed to having them not displayed.
1. Select Toggle Rung Header from the Ladder Viewer Tools menu or from the Ladder
Viewer tool bar.
2. The Ladder Viewer window will be displayed without the rung headers. Select
Toggle Rung Header again to display the rung headers.
7.9-12 Toggle Grid
Use Toggle Grid to switch from having the grid displayed to having it not displayed.
1. Select Toggle Grid from the Ladder Viewer Tools menu or from the Ladder Viewer tool bar.
7/18
Developing a Ladder program 7
2. The Ladder Viewer window will be displayed without the grid. Select Toggle Grid again to display the grid.
7.9-13 Toggle Ladder/List
Use Toggle Ladder/List to switch between the Ladder format and the List format for the selected rung or rungs. To toggle the entire program between the two formats, select
List Editor or Ladder Editor from the View menu.
If a rung is being toggled to go from the List format to the Ladder format and the reversibility rules are not met, the rung will stay in the List format. See part B for an explanation of the reversibility rules.
1. Select the rung to be toggled. Select Toggle Ladder/List from the Ladder Viewer
Tools menu.
2. The selected rung will change from the Ladder format to the List format. For the selected rung, select Toggle Ladder/List again to return to the Ladder format.
C
7.9-14 Show All As Ladder
Use Show All As Ladder to display the entire program in the ladder format. This would be used if some of the rungs had been toggled to the List format and you wanted to switch the entire program back to the Ladder format without proceeding one rung at a time.
If a rung is in the List format and the reversibility rules are not met, that rung will stay in the List format. See part B for an explanation of the reversibility rules.
1. Select Show All As Ladder from the Ladder Viewer Tools menu.
2. The Ladder Viewer window appears with all reversible rungs in the Ladder format.
All non-reversible rungs will stay in the List format.
7.9-15 Table of Grafcet steps (see Section 9.3 Part C )
7.10
Using the Ladder Viewer Edit menur
7.10-1 Introduction
In the Ladder Viewer window, you can edit a program using the options in the Edit menu.
A table in appendix A.2-8 in part G lists the Edit menu options and how they are selected.
7/19
7.10-2 Marking a block
To use the Cut or Copy options, you need first to "mark" or highlight the rungs that you want to cut or copy. You cannot mark a portion of a rung; you must mark the entire rung.
To mark a Ladder block :
1. Position the cursor at the beginning of the first rung you want to mark.
2. Hold down the <shift> key.
3. Use the up or down arrow keys to move to the end of the last rung you want to mark.
4. Release the <shift> key. The highlighted area is the marked block.
C
7.10-3 Undo
Use Undo to reverse the last Cut, Paste, or Delete operation performed. For example, use Undo to restore a block of rungs that you cut, or to delete a block of rungs that you pasted from the clipboard.
From the Ladder Viewer window :
1. Select Undo from the Edit menu.
2. The last editing operation will be reversed.
7.10-4 Cut
Use Cut to move rungs from one place to another within the same program or from one program to another. Cut can be used in the offline or online stopped states.
The clipboard is an internal memory buffer that stores blocks of lines that you cut or copy.
If you close one program file and open another, the contents of the clipboard are retained. The contents of the clipboard are overwritten if you cut or copy another block of rungs.
From the Ladder Viewer window :
1. Mark the block of rungs you want to cut as described in Section 7.10-2.
2. Select Cut from the Edit menu. The marked block is deleted from the Ladder program, but retained in the clipboard.
If you want to delete the marked block without copying it to the clipboard, press <delete>.
Use <delete> when you want to remove rungs that you do not intend to use elsewhere in the program. When you use <delete>, the contents of the clipboard remain the same.
Additionally, the current rung in a program can be removed by pressing <delete>. The rung does not have to be marked for this to occur.
When any program rung is deleted, the Ladder Viewer window closes the rung and automatically re-numbers the remaining program rungs.
7/20
Developing a Ladder program 7
7.10-5 Copy
Use Copy to duplicate a marked block from the program to the clipboard. Copy does not remove the block of marked rungs. Copy is used with the Paste option to duplicate rungs within the same program or to copy a block of rungs from one program to another.
Copy can be used in the offline or online stopped states.
From the Ladder Viewer window :
1. Mark the block of rungs you want to copy as described in Section 7.10-2.
2. Select Copy from the Edit menu. The marked block is copied to the clipboard for a future Paste operation.
7.10-6 Paste
Use Paste to insert rungs cut or copied to the clipboard at a new location in the program or in a different program. The Paste option does not change the contents of the clipboard. Paste can be used in the offline or online stopped states.
From the Ladder Viewer window :
1. Cut or copy a marked block as described in Sections 7.10-2, 7.10-4, and 7.10-5.
2. Select the rung where you want to insert the marked block.
3. Select Paste from the Edit menu. The marked block is inserted before the rung selected in the Ladder program.
Paste can be used to copy rungs from one part of a program into another part of a program. It can also be used to copy lines from a source program to a completely separate target program.
C
7.10-7 Find
Use Find to locate each occurrence of an operand, rung, or comment string in a Ladder program. The Find option can be used in the offline, online stopped, or online running states.
For operands :
• There is no implicit inheritance; that is, if function block %TM0 is to be found, only
function block %TM0 will be found. 'AND %TM0.Q' will not be found.
• Subroutines SRn: and labels %Li: are treated as operands.
For Comment Strings, the search operates on comments, operands, operators, labels, and subroutines.
From the Ladder Viewer window :
1. If you want only to search a specified portion of the Ladder program, mark the block of rungs to be searched.
2. Select Find from the Edit menu. The Find dialog box appears.
7/21
C
3. In the Find field, select Operand, Rung, or Comment String. Operand is used to find an address or symbol in the Ladder program. It does not matter whether addresses or symbols are shown for a search to be conducted for the other. For example, if addresses are currently shown in the Ladder program, you can conduct a search for a symbol.
Rung is used to locate a specific rung in the Ladder program by rung number. If a rung number is entered that is greater than the last rung number of the program, the last rung appears.
Comment String is used to locate each occurrence of a specific string of text in the rung headers.
Range : Operand, Rung, or Comment String
Default : Operand
Note : If the program was originally written in List and reversed to Ladder, comments may be present in the program that are "hidden"; that is, they are not shown on the Ladder rung header.
However, if a search is conducted for a Comment String that includes any of these comments, they will be found in the search.
4. In the blank field under the Find field, enter the value for Operand, or the Rung number to be found. For a Comment String, enter the text to be found.
If Operand is selected in the Find field, enter an address or symbol.
If Rung is selected in the Find field, enter a program rung number.
If Comment String is selected in the Find field, enter a specific string of text.
5. In the Options field :
Select Search All to search from the beginning of the program, or in a marked block.
Select Search From Cursor to search from the current position of the cursor up to the end of the program. Do not select Search From Cursor to search in a marked block of rungs.
Select Search Selected Region to search only in a marked block.
7/22
Developing a Ladder program 7
6. Select Ok to begin a search. Select Cancel to return to the Ladder Viewer window.
For each instance of the value that is found in the Ladder program, the following dialog box is displayed.
7. After the last instance of the value or text is found or if the search does not find any instance of the value or text you specified, an Information dialog box will appear stating "Item not found." Select Ok to end the search and return to the Ladder Viewer window.
C
7.10-8 Replace
Use Replace to locate each occurrence of an operand or comment string and replace it with another operand or comment string. Replace can be used in the offline or online stopped states.
For operands, you can only replace :
• bits by bits (for example, %I0.0 with %M2),
• words by words (for example, %MW100 with %SW12)
• function blocks with like type function blocks (for example, %TM0 with %TM2 is allowed, whereas %TM0 with %C3 is not allowed)
• immediate values with other immediate values.
There is no implicit inheritance; that is, if function block %TM0 is replaced with %TM2, only the function blocks are replaced. %TM0.Q is not replaced with %TM2.Q.
Replace will not work if either the source or target operand is an unresolved symbol.
Replace label and subroutine will not operate on the declaration of the label or subroutine. A label or subroutine declaration may be replaced with another label or subroutine declaration.
For Comment Strings, anything that can be found by a string in the Ladder can be replaced.
From the Ladder Viewer window :
1. If you want only to find and replace an operand or comment string in a specified portion of the Ladder program, mark the block of rungs to be searched.
2. Select Replace from the Edit menu. The Replace dialog box appears.
3. In the Find field, select either Operand or Comment String.
Operand is used to find and replace an address or symbol in the Ladder program.
Comment String is used to find and replace a specific string of text in the rung headers.
7/23
C 4. In the blank field under the Find field, enter the value for the Operand, or the text for the Comment String, to be found and replaced.
If Operand is selected in the Find field, enter an address or symbol.
If Comment String is selected in the Find field, enter a specific string of text.
5. In the Replace with: field, enter the value or text that is to replace the found value or text.
If Operand is selected in the Find field, enter an address or symbol.
If Comment String is selected in the Find field, enter a specific string of text.
6. In the Options field :
Select Search All to find and replace from the beginning of the program, or in a marked block.
Select Search From Cursor to find and replace from the current position of the cursor up to the end of the program. Do not select Search From Cursor to search in a marked block of rungs.
Select Search Selected Region to find and replace only in a marked block.
7. Select Replace All to find each occurrence of the specified value or text and replace with the value or text specified in the Replace with: field. These operations are performed automatically. After all of the occurrences have been found and replaced, an Information dialog box appears stating the number of occurrences replaced.
Select Ok to return to the Ladder Viewer window.
7/24
Developing a Ladder program 7
8. Select Ok to begin the find and replace operation. Select Cancel to return to the
Ladder Viewer window.
For each instance of the value or text that is found in the Ladder program, the
Replace dialog box is displayed.
9. In the Replace dialog box, select Replace, Find Next, Replace All, or Cancel.
Replace changes the current value or text to the value or text specified in the
Replace with: field.
Find Next makes no changes to the value or text currently highlighted and searches for the next occurrence of the value or text.
Replace All finds each occurrence of the specified value or text and replaces each occurrence with the value or text specified in the Replace with: field. After all of the occurrences have been found and replaced, an Information dialog box appears stating the number of occurrences replaced. Select Ok to return to the Ladder
Viewer window.
Cancel exits the find and replace operation and an Information dialog box appears stating the number of occurrences replaced. Select Ok to return to the Ladder
Viewer window.
C
10. After the last occurrence has been found and replaced, an Information dialog box appears stating the number of occurrences replaced. Select Ok to return to the
Ladder Viewer window.
7/25
C
7/26
Section 8
8 Developing a List program
8.1
Introduction
The List Editor is a simple line editor for writing and editing List programs. The List Editor is selected using the Preferences option from the View menu.
You can use the List Editor in the online or offline state. However, in the online run state, you can only insert, delete, or modify certain instructions and use certain options.
Some instructions require balancing or complementary instructions. For example, a
BLK instruction requires an END_BLK instruction. An instruction modified by a parenthesis requires a closing parenthesis—all in the same scan.
To maintain an effective scan rate, the PLC accepts a single instruction line at a time.
Consequently, there is no mechanism to write these complex instructions without severely diminishing the performance of the PLC. Therefore, you cannot insert, modify, or delete some instructions while the PLC is in the online state and running.
C
8.2
Configuring the List Editor
To configure the List Editor:
1. Select Preferences from the View menu to display the Preferences dialog box.
2. In the Editing field, select List. The Ladder Information field is not active when List is selected.
3. After selecting List in the Editing field, the Auto Line Validate field becomes active.
In the online state, program lines are automatically validated as you enter them.
Select Auto Line Validate to automatically validate program lines as you enter them in the offline state.
Use Auto Line Validate to help debug a program as it is written. Auto Line Validate does not replace the Validate Program option. Before you transfer a program to the
PLC, run Validate Program.
8/1
C
Do not select Auto Line Validate if you prefer to write a program with syntactical errors and unresolved symbols. If Auto Line Validate is selected, errors and unresolved symbols must be corrected before you can exit the line.
Default: Auto Line Validate is not selected.
4. You animate a program to display the current value of a variable in the PLC. In the
List/Ladder Animation box, select the number format for displaying the current values when the program is animated.
Range: Hexadecimal or Decimal
Default: Decimal
5. In the Display Attributes field, select the desired attribute, either Symbols or
Addresses, to be displayed with the line number and operator.
Default: Addresses
6. Select Display Toolbars to display the tool bars in all editor windows.
7. Select Ok to commit the values you selected. Select Cancel to exit the dialog box without changing the preferences selected.
8.3
Using the List editor
1. Select the List Editor from the View menu. The List Editor window is displayed.
2. Type instructions directly from the keyboard or select operators and operands from the instruction bar using either the keyboard or a mouse. Maintain a space between the operator and the symbol or between the operator and an address.
The List instruction bar displays the most commonly used List operators and operands. The instruction bar enhances the speed and accuracy of writing a List program. For more information about the instructions in the bar, see appendix A.2-
6 in part G.
3. You can enter a symbol, such as START_SWITCH, rather than an address, such as %I0.7. For more information about using symbols in your program, see section
6, "Defining symbols."
8/2
Developing a List program 8
4. Optionally, you can enter a line comment at the end of a program line. A line comment is free-format text you enter to document a program. Write the comment between two markers or comment delimiters. The comment delimiters are an open parenthesis followed by an asterisk (* before the comment and an asterisk followed by a close parenthesis *) after the comment, as shown below:
(*THIS IS A COMMENT.*)
5. Maintain at least one space between the operator, operand, and comments, as shown below:
LD START_SWITCH (*START CONVEYOR*)
6. After you write a line, press <Enter>.
PL7-07 PC Programming Software automatically reformats the line for you and assigns the completed line a line number. The cursor advances to a new line.
The number to the left of a program line is called a program line number. These numbers help you locate individual program lines when you want to debug problems found during Validate Program. These numbers correspond to the program line numbers in the FTX 117 Hand Held Programmer.
C
8.4
Using the List Editor Tools menu
The List Editor Tools menu is used for validating the program and showing either symbols or addresses.
8.4-1 Validate Program
Use Validate Program to compile a program and check for errors. See section 10.1 for more details on validating a program.
8.4-2 Show Symbols
Use Show Symbols to display symbols, instead of addresses, in the List Editor. If an address has a corresponding symbol, the symbol appears in the program. If an address has no corresponding symbol, the address appears.
8/3
Use Show Symbols in either the offline or online state. Selecting Show Symbols does not restrict your ability to insert symbols or addresses in any way.
To display symbols in the List Editor, select Show Symbols from the Tools menu.
Symbols, rather than addresses, are displayed.
C
8.4-3 Show Addresses
Use Show Addresses to display addresses, instead of symbols, in the List Editor. The address appears in the program whether or not it has a corresponding symbol.
Use Show Addresses in either the offline or online state. Selecting Show Addresses does not restrict your ability to insert addresses or symbols in any way.
To display addresses in the List Editor, select Show Addresses from the Tools menu.
Addresses, instead of symbols, are displayed.
8.4-4 Grafcet Step Table (see Section 9.3 Part C )
8.5
Using the List Editor Edit menu
8.5-1 Introduction
In the List Editor window, you can edit a program using the options in the Edit menu.
A table in appendix A.2-8 in part G lists the Edit menu options and how they are selected.
8/4
Developing a List program 8
8.5-2 Marking a block
To use the Cut or Copy options, you need first to mark or highlight the lines that you want to cut or copy. You cannot mark a portion of a line; you must mark the entire line.
To mark a List block:
1. Position the cursor at the beginning of the first line you want to mark.
2. Hold down the <shift> key.
3. Use the up or down arrow keys to move to the end of the last line you want to mark.
4. Release the <shift> key. The highlighted area is the marked block.
8.5-3 Undo
Use Undo to reverse the last Cut, Paste, or Delete operation performed. For example, use Undo to restore a block of lines that you cut or to delete a block of lines that you pasted from the clipboard.
From the List Editor window:
1. Select Undo from the Edit menu.
2. The last Cut, Paste, or Delete operation will be reversed.
C
8.5-4 Cut
Use Cut to move lines from one place to another within the same program or from one program to another. Cut can be used in the offline or online stopped states.
The clipboard is an internal memory buffer that stores blocks of lines that you cut or copy.
If you close one program file and open another, the contents of the clipboard are retained. The content of the clipboard is overwritten if you cut or copy another block of lines.
From the List Editor window:
1. Mark the block of lines you want to cut as described in section 8.5-2.
2. Select Cut from the Edit menu. The marked block is deleted from the List program, but retained in the clipboard.
If you want to delete the marked block without copying it to the clipboard, press <delete>.
Use <delete> when you want to remove lines that you do not intend to use elsewhere in the program. When you use <delete>, the contents of the clipboard remain the same.
Additionally, the current line in a program can be removed by pressing <delete>. The line does not have to be marked for this to occur.
When any program line is deleted, the List Editor window closes the line and automatically re-numbers the remaining program lines.
8/5
8.5-5 Copy
Use Copy to duplicate a marked block from the program to the clipboard. Copy does not remove the block of marked lines. Copy is used with the Paste option to duplicate lines within the same program or to copy a block of lines from one program to another.
Copy can be used in the offline or online stopped states.
From the List Editor window:
1. Mark the block of lines you want to copy as described in section 8.5-2.
2. Select Copy from the Edit menu. The marked block is copied to the clipboard for a future Paste operation.
C
8.5-6 Paste
Use Paste to insert lines cut or copied to the clipboard at a new location in the program or in a different program. The Paste option does not change the contents of the clipboard. Paste can be used in the offline or online stopped states.
From the List Editor window:
1. Cut or copy a marked block as described in sections 8.5-2, 8.5-4, and 8.5-5.
2. Select the line where you want to insert the marked block.
3. Select Paste from the Edit menu. The marked block is inserted into the List program.
Paste can be used to copy lines from one part of a program into another part of a program. It can also be used to copy lines from a source program to a completely separate target program.
8.5-7 Find
Use Find to locate each occurrence of an operand, line, or string in a List program. The
Find option can be used in the offline, online stopped, or online running states.
For operands:
• It is not necessary to qualify the operand by a specific instruction (for example, find
%M1 in all occurrences of LD).
• There is no implicit inheritance, that is, if function block %TM0 is to be found, only function block %TM0 will be found. 'AND %TM0.Q' will not be found.
• Subroutines SRn: and labels %Li: are treated as operands.
For Text Strings, the search operates on comments, operands, operators, labels, and subroutines.
From the List Editor window:
1. If it is desired to only search a specified portion of the List program, mark the block of lines to be searched.
2. Select Find from the Edit menu. The Find dialog box appears.
8/6
Developing a List program 8
3. In the Find field, select Operand, Line, or Text String.
Use Operand to find an address or symbol in the List program. It does not matter whether addresses or symbols are shown for a search to be conducted for the other.
For example, if addresses are currently shown in the List program, you can conduct a search for a symbol.
Use Line to locate a specific line in the List program by line number.
Use Text String to locate each occurrence of a specific string of text in the program lines.
Range: Operand, Line, or Text String
Default: Operand
4. In the blank field under the Find field, enter the value for the Operand or Line number to be found. For a Text String, enter the text to be found.
If Operand is selected in the Find field, enter an address or symbol.
If Line is selected in the Find field, enter a program line number.
If Text String is selected in the Find field, enter a specific string of text.
5. In the Options field:
Select Search All to search from the beginning of the program, or in a marked block.
Select Search From Cursor to search from the current position of the cursor up to the end of the program. Do not select Search From Cursor to search in a marked block of rungs.
Select Search Selected Region to search only in a marked block.
6. Select Ok to begin a search. Select Cancel to return to the List Editor window.
For each instance of the value that is found in the List program, the following dialog box appears.
C
8/7
7. After the last instance of the value or text is found or if the search does not find any instance of the value or text you specified, an Information dialog box appears stating
"Item not found". Select Ok to end the search and return to the List Editor window.
C
8.5-8 Replace
Use Replace to locate each occurrence of an operand or text string and replace it with another operand or text string. Replace can be used in the offline or online stopped states.
For operands, you can only replace:
• bits by bits (i.e. %I0.0 with %M2),
• words by words (i.e. %MW100 with %SW12)
• function blocks with like type function blocks (i.e. %TM0 with %TM2 is allowed, whereas %TM0 with %C3 is not allowed)
• immediate values with other immediate values
There is no implicit inheritance; that is, if function block %TM0 is replaced with %TM2, only the function blocks are replaced. %TM0.Q is not replaced with %TM2.Q.
Replace will not work if either the source or target operand is an unresolved symbol.
Replace label and subroutine will not operate on the declaration of the label or subroutine. A label or subroutine declaration may be replaced with another label or subroutine declaration.
For Text Strings, anything that can be found by a string in the List can be replaced.
From the List Editor window:
1. If it is desired to only find and replace an operand or text string in a specified portion of the List program, mark the block of lines to be searched.
2. Select Replace from the Edit menu. The Replace dialog box appears.
8/8
Developing a List program 8
3. In the Find field, select either Operand or Text String.
Operand is used to find and replace an address or symbol in the List program.
Use Text String to find and replace a specific string of text in the line headers.
Range: Operand or Text String
Default: Operand
4. In the blank field under the Find field, enter the value for the Operand or the text for the Text String to be found and replaced.
If Operand is selected in the Find field, enter an address or symbol.
If Text String is selected in the Find field, enter a specific string of text.
5. In the Replace with: field, enter the value or text that is to replace the found value or text.
If Operand is selected in the Find field, enter an address or symbol.
If Text String is selected in the Find field, enter a specific string of text.
6. In the Options field:
Select Search All to search from the beginning of the program, or in a marked block.
Select Search From Cursor to search from the current position of the cursor up to the end of the program. Do not select Search From Cursor to search in a marked block of rungs.
Select Search Selected Region to search only in a marked block.
7. Select Replace All to find each occurrence of the specified value or text and replace with the value or text specified in the Replace with: field without confirming each instance. After all of the occurrences have been found and replaced, an Information dialog box is displayed stating the number of occurrences replaced. Select Ok to return to the List Editor window.
8. Select Ok to begin the find and replace option. Select Cancel to return to the List
Editor window.
For each instance of the value or text that is found in the List program, the Replace dialog box appears.
C
8/9
C
9. In the Replace dialog box, select Replace, Find Next, Replace All, or Cancel.
Replace changes the current value or text to the value or text specified in the
Replace with: field.
Find Next makes no changes to the value or text currently highlighted and searches for the next occurrence of the value or text.
Replace All finds each occurrence of the specified value or text and replaces each occurrence with the value or text specified in the 'Replace with:' field. After all of the occurrences have been found and replaced, an Information dialog box is displayed stating the number of occurrences replaced. Select Ok to return to the List Editor window.
Cancel exits the find and replace operation and an Information dialog box appears stating the number of occurrences replaced. Select Ok to return to the List Editor window.
10. After the last occurrence has been found and replaced, an Information dialog box appears stating the number of occurrences replaced. Select Ok to return to the List
Editor window.
8/10
9
9 Grafcet Help
9.1
Introduction
This section describes the Grafcet help functions available from Ladder.
9.2
Showing Grafcet instructions
Grafcet instructions can be divided into two types.
Group 1
= * = i
Group 2
#
_ * _ i # i
= * = POST # Di
Type 1 instructions are treated as labels or subroutines. Declarations of steps or postprocessing are shown continuously in the rung headers.
C
These instructions are available in the rung header dialog box. When incorrect data is entered (value or declaration of an existing step), an error message is displayed in the status bar after clicking on OK.
___________________________________________________________________________
9/1
C
Type 2 instructions are shown as reversible instructions having the same properties as coils (S, ST ...). These Grafcet objects are available on the Extended Ladder Editor
Palette.
9.3
Grafcet Step Table
In order to facilitate displaying the Grafcet status, a table of Grafcet steps is available from the Tools menu in the List or Ladder editors.
This table shows the list of steps defined in the program in ascending order of steps.
The initial step is represented by a double square (example: step 1).
If the software is online, the window is animated and the active step or steps are highlighted.
It is possible to move through the various steps using the keyboard (keys and
¬) or the mouse. The selected step is outlined in red. By double-clicking on this step or pressing <Enter>, the part of the program associated with this step can be directly accessed in the List or Ladder editor.
___________________________________________________________________________
9/2
Section 10
10 Validating and reversing a program
10.1
Validating a program
Validate Program compiles a program and checks it for errors. Compiling a program means to translate a program into binary machine code, a low-level language which can be executed by the PLC.
In addition to compiling a program, Validate Program also :
• checks that the syntax of each program line or rung is correct.
• checks that each symbol used in a program has a corresponding address.
• checks that the structure of the program is correct.
• creates a binary program file.
• posts messages in the Validation Errors window.
You can validate a program, in the offline or online states, using these options :
1. Validate Program (Offline)—In the offline state, select Validate Program from the
Tools menu to check and compile a program at any time, from any editor.
2. Validate Program (Online)—In the online state, each program line you enter is automatically validated, before it is sent to the PLC. Therefore, you do not need to run Validate Program, although you can choose to run it.
After you run Validate Program, one of two messages is displayed.
If the program has no errors, the following appears :
C
If the Validate Program process detects an error, the following appears :
10/1
10.2
Viewing validation errors
Validation Errors displays error and warning messages posted by the Validate
Program process.
1. Select Validation Errors from the View menu to display the Validation Errors window.
C
The format of each message is :
• type of message— error or warning.
• the number of the offending line or rung.
• an explanation of the problem.
There are two types of messages— error and warning messages. An error message indicates a problem in the application that prevents the creation of an executable program. A warning message indicates instructions that are not reversible, or instructions that, in relation to other instructions, may cause operational uncertainties.
10.3
Reversing a program
An application program written in Ladder can be converted - or reversed - to List.
Likewise, a program written in List can be reversed to Ladder if certain reversibility rules are observed. These rules are further explained in Sections 7.3 and 7.4 of Part B.
Note :
In the case where a program written in List is reversed to Ladder and the rules are not met, the corresponding rungs in the Ladder Editor window will display the List instructions instead of the
Ladder format.
To reverse from the List Editor to the Ladder Editor :
• Select Ladder Editor in the View menu
• Adjust the display by selecting Preferences in the View menu
To return from Ladder Editor to List Editor :
• Simply select List Editor in the View menu.
10/2
Section 11
11 Archiving an application
11.1
Introduction
An application file is archived by selecting either Save or Save As from the File menu.
A binary file *.APP is archived by selecting Save As from the File menu.
• Save is used to commit changes to an existing application.
• Save As is used to save the current application or binary file to a new file.
11.2
Save
To commit changes to an existing application file:
1. Select Save from the File menu. The file will be saved to the current directory.
C
11.3
Save As
To save the current application or binary file to a new file:
1. Select Save As from the File menu. The File Selection dialog box appears.
2. In the List Files of Type field, open the selection box and select either the .pl7 or
.app file type. The .pl7 file extension identifies application files. The .app file type identifies binary files.
A binary file (.app extension) is used for transferring a file to the FTX 117 terminal via a PC card (memory card). See appendix A.7 in part G for more information.
3. In the Drives field, select the drive where you want to store the file.
11/1
C
4. In the Directories field, select the directory where you want to save the file.
5. In the Filename field, over type the asterisk (*) with a standard DOS file name.
If a filename does not comply with DOS file naming conventions, an "Invalid
Filename" message appears.
If you type a filename that already exists in the directory, an error message appears:
"The file selected already exists. Overwrite?" Select Ok or Cancel.
6. Select Ok to save the file. Select Cancel to close the File Selection dialog box without saving the file.
11/2
Section 12
12 Transferring an application
12.1
Introduction
PL7-07 software provides 2 methods of protecting the application while it is being debugged :
• Total read and write protection.
This option particularly prohibits duplicating programs thus guaranteeing the inviolability of the programmer's expertise.
It is executed when the application is transferred into the PLC memory.
• A write protection, with access to the application display and to the variable settings.
A password provides this protection (see Section G-A.4).
C
12.2
Transferring an application
Select Transfer from the PLC menu to copy an application to one of three hardware storage areas :
1. PC RAM (Random Access Memory).
2. PLC RAM.
3. The PLC EEPROM (Electrically Erasable Programmable Read-Only Memory), a secondary or backup memory storage area on the PLC.
The Transfer option in the PLC menu displays four sub-menu options :
12.2-1 PLC => PC
Select PLC => PC to transfer the application from the PLC RAM to the PC RAM :
If you begin from the initial state, with no application open :
1. Select PLC => PC.
From the initial state, the transferred application becomes the current application.
The word default appears in the title bar of the application.
12/1
C
If you begin from the offline state, with an application open :
1. Select PLC => PC.
The PLC application overwrites the program and configuration in the PC, but keeps the symbols.
If the application is password protected, you are prompted to change security levels.
1. Select Ok to display the Security dialog box. In the Enter Password field, type the correct password. Select Ok. The application is displayed at the supervisor level.
2. Select Cancel to display the application at the operator level.
For more information about software Security features, see appendix A.4 in part G.
12.2-2 PC => PLC
Select PC => PLC to copy the current application on the PC to the PLC.
To transfer the application from the PC RAM to the PLC RAM :
1. Open the application file (.pl7) or binary file (.app) that you want to transfer.
2. Select PC => PLC.
3. If the application and PLC versions are not the same, the message, "The application and PLC are different versions" appears.
Select Ok to continue transfer.
Select Cancel to change the version of the PLC. For more information, see Section
5.21.
4. If the application in the PLC contains a password, you are prompted to confirm transfer of the application.
If you know the password, select Ok to transfer over the protected application.
If you don't know the password, select Cancel to end the transfer process.
5. If you select Ok, a Security dialog box appears. Enter the correct password and select Ok.
6. If the PLC and PC applications are different, then you are prompted to select whether you want to overwrite the application in the PLC.
Select Ok to overwrite the application.
Select Cancel to end the transfer process. (To back up the PLC application to the
PC, see Section 12.2-1.)
7. You are prompted to select whether you want to protect the application.
Select Yes to protect the application in the PLC or No to leave the application unprotected.
8. When the transfer to the PLC is completed, the message, "Transfer Successful," appears in the status bar.
12/2
Transferring an application 12
12.2-3 PLC => EEPROM
Select PLC => EEPROM to copy an application from the PLC RAM to the PLC EEPROM.
The PLC EEPROM can store one application. It is strongly recommended to transfer an application into the EEPROM as soon as it has been debugged.
To transfer the application from the PLC RAM to the PLC EEPROM :
1. Select PLC => EEPROM from the Transfer sub-menu.
2. The PLC => EEPROM dialog box has two options :
C
The Protected option lets you protect the application in the PLC, unless you have already protected it during the PC => PLC transfer process. If protected in the PLC, an error message warns you that you cannot copy or write the application to the
EEPROM because neither read or write is allowed.
The Master option lets you set the application in the EEPROM as the master, which means that each time you power up, the PLC compares the application which is present in RAM with that in EEPROM and, if a difference is detected, the application stored in EEPROM is copied to the PLC RAM, and the PLC is set to RUN (unless an R/S input configured in the application is at STOP).
To modify a master application :
• retrieve the application to the PLC or PC RAM
• modify the application then validate the modifications
• transfer the application back to EEPROM by selecting the Master option.
3. After the application is transferred from the PLC RAM to the EEPROM, the message,
"Transfer Successful," appears in the status bar.
12/3
C
12.2-4 EEPROM => PLC (EEPROM to PLC)
Select EEPROM => PLC to transfer the application that you backed up to the EEPROM to the PLC primary storage area.
To transfer an application stored in the EEPROM to the PLC, simply select PLC =>
EEPROM from the Transfer sub-menu. After the application is transferred, the status bar displays the message "Transfer Successful."
12/4
Section 13
13 Starting up an application
13.1
PLC Address
In order to be able to communicate directly with a TSX Nano UNI-TELWAY Slave, PL7
07 software enables the target address to be defined.
After having chosen this address, the user selects the required action in the PLC menu
(Transfer, Connect, PLC Operations).
The default address offered is the system address 0.254.0.
The user must then enter the address of the PLC to which he wishes to connect using the following format : Network.Station.Gate.Rack/Module.Slave Address:
• Network is the number of the network which enables the target address to be reached
(0 to 127), the default value is 0.
• Station is the number of the station on the network (0 to 254), the default value is 254.
• Gate is the mechanism which enables the unit of communication within the selected station to be chosen. As 0 is the station system gate (its UNITE server), 5 is the gate which enables communication with a remote PLC. The default value is 0 (in this case it is not necessary to complete the other fields).
• Rack/Module is used if the gate number is 5. It corresponds to the physical situation of the UNI-TELWAY Master module. The default value is 254 and means that the
TSX Nano is connected to the same UNI-TELWAY bus as the PL7 07.
The value 0 indicates another UNI-TELWAY bus (PCMCIA for example).
• Slave address is the address of the TSX Nano PLC on the UNI-TELWAY bus.
The default value is 4 in local mode and 104 in remote mode.
To help the user, 3 key words are available and can be entered directly :
• SYS corresponds to the system address 0.254.0,
• LOC corresponds to the local address 0.254.5.254.4. The slave address 4 should be changed if it does not correspond with that of the target PLC.
• REM corresponds to the remote address 0.254.5.0.104. The Rack/Module and Slave addresses should correspond to the address of the target TSX Nano.
OK validates the values entered.
Cancel exits without changing the address values.
13/1
C
13.2
Connect
C
Select Connect from the PLC menu to initiate communication between the PC and the
PLC.
To connect the PC to the PLC :
1. Select Connect from the PLC menu.
2. If the applications in the PC and the PLC are the same and the application in the
PLC is not protected, the PC connects to the PC and the application state changes from offline to online.
3. If the application in the PLC is protected, you are prompted to choose whether you want to monitor the PLC. Select Ok to monitor the PLC or Cancel to end the connection process and return to the offline or initial state.
4. If the applications in the PC and the PLC are different and the application in the PLC is not protected, the Connect to PLC dialog box appears. Select an option :
Select PLC -> PC to transfer the application in the PLC to the PC. The application state changes from offline to online.
Select PC -> PLC to transfer the application open on the PC to the PLC. An
Information dialog box appears informing you that you are about to overwrite the
PLC application. Select Ok to continue the transfer or Cancel to abort. If you select
Ok, the transfer is completed and the PC connects to the PLC. The application state changes from offline to online.
Select Monitor if you only want access to the application data pages and do not want to modify the application program, configuration, or symbols. The application state changes from offline to monitor.
Select Cancel to end the connection process and return to the offline state.
13/2
13.3
Stop/Run/Init
From the PLC menu it is possible to run, stop or initialize the PLC without displaying the PLC operations window. To do this, directly select the actions RUN, STOP or INIT.
A dialog box confirming these choices will appear before the request is executed.
13.4
PLC Operations
Select PLC Operations from the PLC menu to display the PLC Operations dialog box.
C
The fields are numbered and described below :
(1) The Status field check boxes indicate whether :
One or more input or output bit is forced either 1 or 0.
An executable application is stored in the PLC RAM.
The PLC RAM protection bit was set to 1 during the Transfer process.
(2) The Switches field displays the settings you selected for the controls on the PLC.
For information about setting the PLC function code and potentiometer switches, see Sections 1.8 and 1.10 in Part A.
13/3
Starting up an application 13
(3) The Scan Time (msec) field, displays the minimum, current, and maximum scan time, expressed in milliseconds. For more information about program execution, see Section 1.3 in Part A.
(4) The Real Time Clock displays the current date and time. You can change the date and time by selecting the Set Time pushbutton at the bottom of the window. For more information, see Section 13.4-2.
(5) The LEDs in the PLC Operations window simulate the LEDs on the base PLC. For more information, see Section 1.9 in Part A.
(6) The Stop/Run/Init/Set Time/Advanced/Close pushbuttons let you control application execution on the PLC and view PLC system information.
C
13.4-1 Stop/Run/Init
To start executing an application in the PLC :
1. Select Run.
2. A warning message prompts you to confirm your decision to execute the application on the PLC.
Select Ok to run the PLC. Select Cancel to return to the PLC Operations dialog box, leaving the state of the PLC unchanged.
To stop executing an application in the PLC :
1. Select Stop.
2. A warning message prompts you to confirm your decision to stop the execution of the application in the PLC.
Select Ok to stop the PLC. Select Cancel to return to the PLC Operations dialog box, leaving the status of the PLC unchanged.
Select Init to initialize the PLC RAM. The initialization resets all memory variables.
1. Select Init.
2. A warning message dialog box prompts you to confirm your decision to initialize the PLC.
Select Ok to initialize the PLC. Select Cancel to return to the PLC Operations dialog box, leaving the status of the PLC unchanged.
13.4-2 Set Time
To set the PLC real time clock :
1. Select Set Time from the PLC Operations window.
2. In the PLC Date field, enter the current date, displayed as month/day/year.
3. In the PLC Time field, enter the current time. The time value appears in military format, hours:minutes:seconds. For example, 12 noon is 12:00:00, 2:15 PM is
14:15:00, and midnight is 00:00:00.
13/4
4. Select Ok to update the PLC date and time. Select Cancel to return to the PLC dialog box.
13.4-3 Advanced
Select Advanced to display read-only PLC system information, which you can view but cannot change.
A checked box indicates that the state is active. Use this information to check the PLC
RAM and PLC EEPROM status and to diagnose problems.
C
RAM options
Valid
Executable
Indicates whether there is an application stored in the PLC RAM.
Indicates whether the application in the PLC RAM is executable.
Protected Indicates whether you chose to protect the PLC RAM during the transfer from PC to PLC. (See Section 12.4)
Compatible with OS Indicates whether the PLC version declared in the application configuration is the same as the target PLC operating system.
Different than EEPROM Indicates whether the application in the PLC is different from the application in the EEPROM.
13/5
Starting up an application 13
EEPROM options
Valid
Executable
Indicates whether there is an application stored in the PLC
EEPROM.
Indicates whether the application in the EEPROM is executable.
C
Protected Indicates whether you chose to protect the EEPROM during the
PLC => EEPROM transfer process. (For more information, see
Section 12.4.)
Compatible with OS Indicates whether the PLC version declared in the application configuration is the same as the target PLC operating system.
Master (Autoload) Indicates whether you selected the Master option during the PLC
=> EEPROM transfer process. (For more information, see Section
12.4.)
PLC options
GRAFCET over-run Indicates whether the time needed to execute the Grafcet structure was greater than the scan time allowed.
Watchdog Time out Indicates whether the scan time of a program exceeded 150 ms, causing the Watch dog timer to stop the PLC. (For more information, see Section 1.3 in Part A.)
Clock Calender present Indicates whether the PLC has the Real Time clock feature.
Some I/O is forced Indicates whether one or more input or output bits is forced ON or OFF.
13/6
Section 14
14 Debugging and adjusting an application
14.1
Introduction
This section explains the various features of the PL7-07 PC programming software that can assist you in debugging and adjusting an application. These include animating a program, working with data variables, and using data pages.
14.2
Animating a program
Animating a program allows you to view the values of the variables when a program is online, either running or stopped. This is useful for debugging because it allows you to view the change in values as the program runs to compare the actual values against expected values.
C
14.2-1 Animating a Ladder program
With the Ladder Viewer window displayed and the program online, either running or stopped :
1. Select Toggle Animation from the PLC menu.
2. The Ladder Viewer window is displayed with the following :
• the title bar shows the word, "animating".
• contacts, coils, and special objects with a logical result of 1 are highlighted.
• the data variables of function blocks, compare block, and operate blocks are shown. This includes current and preset values. For other than binary values, the number is displayed in either hexadecimal or decimal, depending on the format selected in the Preferences dialog box.
3. When the Ladder Viewer window is animated, select Toggle Animation from the
PLC menu to turn off animation.
14/1
C
14.2-2 Animating a List program
With the List Editor window displayed and the program online, either running or stopped :
1. Select Toggle Animation from the PLC menu.
2. The List Editor window is displayed with an additional column just to the right of the line number. The column contains the value of the operand for that line. When an instruction line has more than one operand, the value of each of the operands is displayed and separated by slashes. Additionally, the title bar shows the word,
"animating".
Binary operands are displayed as either 1 or 0. Word operands are displayed in either decimal or hexadecimal format, depending on the format selected in the Preferences dialog box.
The following values are not animated, but rather are represented by an asterisk :
• labels (%Li)
• subroutines (SRn)
• instructions that require no operand, NOT, NOP, END
• immediate values
• indexed words
• bits extracted from words
• table of words
• string of bits, such as %M0:5
Forced bits are displayed with an 'f', paired with the forced state, either 0 or 1. A bit operand that is forced on, is displayed as 'f 1', and a bit operand that is forced off, is displayed as 'f 0'. See Sections 14.4-7 through 14.4-10 for more information on forced values.
3. When the List Editor window is animated, select Toggle Animation from the PLC menu to turn off animation.
14/2
Debugging and adjusting an application 14
14.3
Using the Data Editor
The PL7-07 PC programming software uses the variables listed in appendix A.3 of part
G to assist in writing the program. The Data Editor is used to view and modify these variables to assist in debugging a program. Additionally, the Data Editor can be used to force the values of input or output bits.
In the Data Editor window, you can define a list of PLC variables that you want to monitor and save. This list is called a "data page".
To display the Data Editor window, select Data Editor from the View menu.
C
The following gives an explanation of each column of the data page.
Address A specific location in memory, always preceded by a percent sign (%).
Current Value The actual value of the variable in the PLC. The value of the variable changes as the program runs. In the online state, you can animate the data page and watch the Current Value change as the program runs. An asterisk (*) appears in this column before the first time the data page is animated. After the first time the data page is animated and subsequently turned off, the Current Value column retains the last updated value.
Retained Value The value specified as an initial value. When the Write Retained V
Values function is performed, these values are written to the PLC.
Symbol The name assigned to an address in the Symbol Editor to identify the purpose of the variable.
14.3-1 Animating a data page
Animating a data page displays and updates the Current Value column of the data page as the PLC program runs.
1. Before the data page is animated for the first time, the Current Value column contains asterisks (*).
14/3
2. With the data page displayed and the PLC online, either running or stopped, select
Toggle Animation from the PLC menu to animate the data page.
3. The Current Value column is displayed with the current values from the PLC for the addresses listed in the data page. The title bar shows the word, "Animating".
C
4. When the data page is animated, select Toggle Animation from the PLC menu to turn off animation. The Current Value column retains the last updated value.
14.4
Using the Data Editor Tools menu
The Data Editor Tools menu is used to construct, edit, and save a data page.
Additionally, from the Data Editor Tools menu you can modify and force values for selected variables in the program. The table in appendix A.2-7 of part G lists the options in the Data Editor Tools menu and the corresponding buttons on the tool bar.
14.4-1 Editing a data variable
To edit a single data variable on a data page :
1. With the data page displayed, double-click or press <enter> on the row with the data variable to be edited. The Data Object Edit dialog box appears.
14/4
Debugging and adjusting an application 14
2. The Address and Symbol fields display the address and symbol for the data variable to be edited. A symbol must have an assigned address, however, an address does not necessarily have an assigned symbol.
3. In the Display Format field, select the number format to determine how the value appears on the data page.
Range : Decimal, Hexadecimal, Binary, ASCII
Default : Decimal
4. In the Retained Value field, enter the desired initial value for the variable. This value is written to the PLC with all the other initial values of the data page when you perform the Write Retained Value operation.
5. Select Ok to commit the changes to the data variable displayed in the dialog box or Cancel to return to the Data Editor window without making any changes.
C
14.4-2 Validate Program
Use Validate Program to compile a program and check for errors. See Section 10.1 for more details on validating a program.
14.4-3 Insert
Use Insert to add a variable to the data page.
1. From the Data Editor window, select Insert. The Data Object Edit dialog box appears.
14/5
C
2. In the Address or Symbol to Insert field, enter the address or symbol to be added to the data page.
Symbol names must have an associated symbol in the symbol table to be used in the data page. If a symbol name is entered that is not in the symbol table, an Error dialog box appears stating, " Invalid or Undefined symbol or address". Select Ok to return to the Data Object Edit dialog box. For more information on symbols, see
Section 6, "Defining symbols."
3. The Address and Symbol fields are used to display the corresponding symbol for an address entered in step 2 or display the corresponding address for a symbol entered in step 2. A symbol must have an assigned address, however, an address does not necessarily have an assigned symbol.
4. In the Display Format field, select the number format to determine how the value will be displayed on the data page.
Range : Decimal, Hexadecimal, Binary, ASCII
Default : Decimal
5. In the Retained Value field, enter the initial value for the variable. This value is written to the PLC with all the other retained values on the data page when you perform the Write Retained Values operation.
6. Select Ok to commit the values to the data page or Cancel to exit and return to the
Data Editor window.
14.4-4 Delete
Use Delete to remove a variable from the data page.
With a data page displayed, highlight the variable to be removed. Select Delete. The variable is removed from the data page.
14.4-5 Add Next Instance
Use Add Next Instance to add the following sequential instance of the variable highlighted on the data page.
With a data page displayed, highlight the desired variable of the same type to be added.
Select Add Next Instance. A new variable of the same type is added to the data page with the following sequential number.
For example, if %I0.3 is currently highlighted, selecting Add Next Instance adds the variable %I0.4 to the data page.
14.4-6 Add Previous Instance
Use Add Previous Instance to add the preceding sequential instance of the variable highlighted on the data page.
With a data page displayed, highlight the desired variable of the same type to be added.
Select Add Previous Instance. A new variable of the same type is added to the data page with the previous sequential number.
14/6
Debugging and adjusting an application 14
For example, if %I0.3 is currently highlighted, selecting Add Previous Instance adds the variable %I0.2 to the data page.
14.4-7 Force 1
Use Force 1 to set or force an input or output bit to 1, even if the calculated value is different from the forced value. When a variable's value is forced, the value stays forced until it is cleared—even if the PC is disconnected from the PLC and you exit the PL7-07 PC programming software.
Force 1 is available when the PLC is online, either running or stopped. The Current Value column in the data page has a 'F' next to the value if it is a forced value and the data page is animated. The table in appendix A.3 in part G lists the variables that can be forced.
With a data page displayed and animated, select Force 1. The selected variable displays a 'F' next to the current value of 1. For example, the following shows input %I0.3 with a forced value of 1.
C
14.4-8 Force 0
Use Force 0 to set or force an input or output bit to 0, even if the calculated value is different from the forced value. When a variable's value is forced, the value stays forced until it is cleared—even if the PC is disconnected from the PLC and you exit the PL7-07 PC programming software.
Force 0 is available when the PLC is online, either running or stopped. The Current Value column in the data page has a 'F' next to the value if it is a forced value and the data page is animated. The table in appendix A.3 in part G lists the variables that can be forced.
With a data page displayed and animated, select Force 0. The selected variable displays a 'F' next to the current value of 0.
14.4-9 Clear Force
Use Clear Force to remove a forced value from a variable on the data page. Clear Force is available when the PLC is online, either running or stopped.
1. With a data page displayed and animated, select Clear Force to remove the forced value for the highlighted variable .
2. The Data Editor window displays the variable with the forced value removed.
14.4-10 Clear All Force
Use Clear All Force to remove all forced values from a data page. Clear All Force is available when the PLC is online, either running or stopped.
14/7
1. With a data page displayed and animated, select Clear All Force to remove the forced values for the entire data page.
2. The Data Editor window displays the data page with all forced values removed.
C
14.4-11 Read Retained Values
Use Read Retained Values to transfer the Current Values from the PLC to the Retained
Values on the data page. Read Retained Values is available when the PLC is online, either running or stopped.
1. With a data page displayed and animated, select Read Retained Values to transfer the values in the Current Value column to the Retained Value column.
2. The data page appears with the Retained Value column updated with the values from the Current Value column.
14.4-12 Write Retained Values
Use Write Retained Values to transfer the Retained Values on the data page to the
Current Values in the PLC. Write Retained Values is available when the PLC is online, either running or stopped.
1. With a data page displayed and animated, select Write Retained Values to transfer the values in the Retained Value column to the Current Value column for all variables on the data page.
2. The Current Value column appears with the values from the Retained Value column, unless they changed immediately after being written to the Current Value column.
14.4-13 Write Data Value
Use Write Data Value to momentarily send, or write, a single data value to the PLC. Write
Data Value is available when the PLC is online, either running or stopped. The table in appendix A.3 in part G lists the variables that can have values written to them.
Write Data Value is available from the Data Editor window, whether or not a data page is opened.
1. With the Data Editor window open, select Write Data Value. The Write Data Value dialog box appears.
14/8
Debugging and adjusting an application 14
2. Enter the data variable in the Data Object field.
3. The Current Value field displays the current value for the selected variable.
4. Select the display format for the value. This format selection is only for the display of the value being entered in the Write Data Value dialog box.
Range : Decimal, Hexadecimal, Binary, ASCII
Default : Decimal
5. In the Write Data Value field, enter the value you want to write to the PLC for the data variable.
6. Select Ok to write the value to the PLC or Cancel to return to the data page without writing the value to the PLC.
14.4-14 Open Data Page
Use Open Data Page to open a data page that was previously saved.
1. With the Data Editor window displayed, select Open Data Page from the Tools menu. The File Selection dialog box appears.
C
2. In the List Files of Type field, open the selection box and select either the .dat file type or select to have all file types listed (*.*).
Default : .dat
3. In the Drives field, select the drive where the data files are stored.
4. In the Directories field, select the PL7-07 directory or the directory where the data files are stored.
5. In the Filename field, select the data file to be opened.
6. Select Ok to open the data file or Cancel to return to the Data Editor window.
14/9
C
14.4-15 Save Data Page
Use Save Data Page to save changes to an existing data page file.
After making the desired changes to a data page, select Save Data Page to save the changes to the data page file.
14.4-16 Save Data Page As
Use Save Data Page As to save a data page to a new file.
1. With the Data Editor window open and a data page displayed, select Save Data
Page As. The File Selection box appears.
2. In the List Files of Type field, select the default file extension, .dat.
3. In the Drives field, select the drive where the data file will be stored.
4. In the Directories field, select the PL7-07 directory or the directory where the data files will be stored.
5. In the Filename field, over type the asterisk (*) with a standard DOS file name.
If the file name does not comply with DOS file naming conventions, an "Invalid
Filename" message is displayed.
If a file name is selected that already exists in the directory, an error message is displayed : "The file selected already exists. Overwrite?" Select Ok to overwrite the file or Cancel to return to the File Selection dialog box.
6. Select Ok to save the data file or Cancel to return to the Data Editor window.
14/10
Debugging and adjusting an application 14
14.5
Modifying the program in RUN mode
The List program editor allows the List program to be modified when the PLC is in RUN mode.
CAUTION
UNEXPECTED EQUIPMENT OPERATION
For obvious safety reasons, it is advisable to program a PLC in STOP.
It is possible, however, to program a PLC which is in RUN mode so that program modifications not requiring the application to be stopped can be performed.
However, these modifications remain the responsibility of the user.
Before any modifications are performed, certain conditions for programming a PLC while running must be fulfilled. It is essential to know the consequences of the modifications on the application, and to take any necessary actions to determine what these are.
Failure to observe this precaution can result in equipment damage, severe personal injury, or death.
Modifying in RUN mode
The process for modifying in RUN mode is identical to that for programming in RUN mode. The modification takes effect as soon as the current entry is confirmed.
Restrictions
The following table shows the restrictions on use and on modification when the PLC is in RUN mode :
Mode/Function
Configuration
Programming
Access
Access to display only
All modifications/insertions/cancellations of instructions are permitted, except for instructions which modify the structure of the program :
• parentheses
• Grafcet instructions
• labels
• jump : JMP and SR subroutine calls
• master control relays MCR and MCS
• block instructions : BLK, OUT_BLK, END_BLK
• MPS, MPP
The following instructions are not active :
• find and replace
• program transfer to EEPROM
C
14/11
C
14/12
Section 15
15 Printing
15.1
Introduction
PL7-07 PC Programming Software can print the whole or part of an application.
15.2
Print Setup
Print Setup is used to define a printer ID or file name and the page layout.
To setup a printout:
1. Select Print Setup from the File menu. The Print Setup dialog box appears.
C
2. In Printer Setup open the printer selection box to select a printer type:
Values: Text Printer, HP Compatible, Epson Printer.
Default: Epson Printer
The lines Send Before Print and Send After Print enable specific commands to be sent to the printer before exiting the file and after printing.
Default : None.
3. Select the printing format in Paper Size:
Values: A4 (21 x 29.7 cm), Letter 8 1/2 x 11
Default: A4
4. In the Output to (printer or file) field, type either the printer ID, such as LPT2 (parallel port #2) , or a file name, such as PRINTOUT.TXT, using a standard DOS file name.
Default: LPT1 (parallel port #1)
___________________________________________________________________________
15/1
5. To define the page header and footer, select the Header/Footer button to display the following window:
C
You can type up to three lines of text to display at the top of each page. You can also type up to three lines of text to display at the bottom of each page.
Similarly, it is possible to print at the bottom of the page the name of the originator, the company and the program as well as the date, the version and the type of PLC used.
6. To define the cover page of the application file, select the Cover Page button in the
Print Setup dialog box:
Enter a title of up to 20 characters and the development history of the application:
Date, author, version and comments.
___________________________________________________________________________
15/2
7. If a comments page is required at the beginning of the application file, select the
Comments button in the Print Setup dialog box:
This editor enables a page of 60 lines of 70 characters each to be entered.
Line advance is obtained by using carriage return (ENTER) when entering.
8. In Margins, enter a number in the field Adjust Page Left to increase or decrease the width of the left margin by the number of characters required. Enter a number in the field Page Adjust Top Edge to increase or decrease the top margin by the number of lines required.
9. In Margins, define the width of the left and right margins in numbers of characters.
Define the width of the top and bottom margins in numbers of lines.
It is necessary to make sure that the number of margin lines correspond with the header and footer.
10. Select Save Default to save the printer and page layout values you selected as the default values for future printing operations.
11. Select Restore Default to overwrite the current values with the values that you saved earlier by using the Save Default button.
12. Select Ok to save your settings. Select Cancel to exit without saving the settings you defined.
___________________________________________________________________________
15/3
C
15.3
Select Print from the File menu. The Print dialog box appears.
Printing 15
C
The options in the Print dialog box let you define the scope of your printout. Select Print
All to print the entire application. Or, print only specific application parts by selecting the appropriate checkboxes. Select Ok to print. Select Cancel to exit the Print dialog box without printing.
15.3-1 Configuration Print Settings
If you want to print some, but not all, configuration data:
1. In the Print dialog box, select the Configuration Settings button to display the
Configuration Print Settings dialog box.
2. Select the checkboxes for the Configuration data that you want to print. Select Print
All to print all configuration data for an application.
Default: All configuration data items selected.
3. Select Ok to save your changes. Select Cancel to return to the Print dialog box
15/4
15.3-2 Symbols Print Settings
To define a printout of application symbols:
1. In the Print dialog box, select the Symbols Settings button to display the Symbols
Print Settings dialog box.
2. In the Order By field, select Resolved Address to sort the operands by address or select Symbol Name to sort the operands by symbol name.
Default: Resolved Address
3. Select Ok to save your changes. Select Cancel to return to the Print dialog box without saving your selections.
15.3-3 Cross Reference Print Settings
To define a printout of cross reference program elements:
1. In the Print dialog box, select the Cross Reference Settings button to display the
Cross Reference Print Settings dialog box.
C
2. In the Program Elements field, select All to print all elements of a program or
Selected to only print those elements that you selected in the Generate Cross
Reference dialog box. If you want to re-select those elements, select Cross
Reference from the View menu and regenerate the cross reference.
Default: All
3. Select Ok to save your changes. Select Cancel to return to the Print dialog box without saving your selection.
___________________________________________________________________________
15/5
Printing 15
15.3-4 List Print Settings
To define a printout of List program lines:
1. In the Print dialog box, select the List Settings button to display the List Print Settings dialog box.
C
2. In the Range field, select All to print all list lines. Or, select By Lines and enter the first and last numbers of the program block that you want to print.
Default: All
3. In the Attributes field, select:
• 1 Column with Addresses to print the application code with the addresses of the objects.
• 1 Column with Symbols to print the application code with the symbols associated with the objects.
• 2 Columns with Addresses to print the code in a condensed form in two columns with the addresses of the objects.
Default : 1 Column with Addresses.
4. Select Ok to save your changes. Select Cancel to return to the Print dialog box without saving your changes.
15.3-5 Ladder Print Settings
To define a printout of Ladder rungs:
1. In the Print dialog box, select the Ladder Settings button to display the Ladder Print
Settings dialog box.
___________________________________________________________________________
15/6
2. In the Range field, select All to print all ladder rungs in the file. Or, select By Rung and enter the first and last rung numbers of the Ladder block that you want to print.
Default: All
3. In the Attributes field, select:
• 4 lines with Addresses + Symbols to print the application code with the symbols and addresses of the objects. 3 lines are available to display the entire symbol and one line for the address. These 4 lines are displayed above the graphic element in the Ladder rung.
• 1 line with Addresses to print the application code with the addresses of the objects.
• 1 line with Symbols to print the application code with the symbols associated with the objects.
Default : 4 lines with Addresses + Symbols.
4. Select Ok to save your changes. Select Cancel to return to the Print dialog box without saving your selections.
C
___________________________________________________________________________
15/7
C
___________________________________________________________________________
15/8
Section 16
16 Cross referencing an application
16.1
Introduction
The cross reference list provides a useful list of the operands, symbols, lines and operators. For example, during troubleshooting or debugging, it allows the item of interest to be easily located and cross referenced to other locations in the program without having to search through the entire program.
16.2
Generating a new Cross Reference list
To generate a cross reference list for the first time after an application has been opened:
1. Select Cross Reference from the View menu. An Information dialog box appears.
Select Ok to display the Generate Cross Reference dialog box. Selecting Cancel will display the Cross Reference window without generating the cross reference list.
C
Note:
It is advisable to validate the program before generating cross references.
The cross reference list is not saved when the application is closed. Therefore, when the application is re-opened, the cross reference list must be generated.
2. In the Reference By field, select whether you want to reference by ladder rung number or list line number.
3. In the Range field, define the scope of the display.
Select All to display all list lines or all ladder rungs in a program.
16/1
C
Select Start/End to mark a specific block of the program that you want to display.
The range for both fields is 0 to 999. For Start, the default value is 0. For End, the default value is 999.
4. In the Sort By field, select one field to act as the key field when the cross reference list is displayed. These options correspond to the Sort options in the Tools menu.
Values: Operand, Symbol, Line/Rung Number, Operator
Default: Operand
For example, if Sort by Operand is selected, the following window appears—sorted alphabetically and numerically by operand.
When Sort By Operand or Sort By Symbol is selected, a separation line frames each operand or symbol so that the information is easier to read.
5. In the Elements field, select the check boxes that correspond to the program items that you want listed.
The selection of specific program items from the Elements field allow you to define the scope of your display more narrowly. For example, you can choose to list only program lines or rungs that have timer function blocks.
___________________________________________________________________________
16/2
Cross referencing an application 16
16.3
Updating an existing Cross Reference list
An existing cross reference list will need to be regenerated in the following cases:
• Modification of the Rung Number system of reference to Line Number or vice versa in the Reference By field,
• Modification of the range of the cross reference,
• Modification of the current cross reference list (adding or deleting elements),
• Any change to the application program and/or symbols.
1. If the cross reference list is to be updated while the cross reference list is displayed, select Generate Cross Reference from the Tools menu.
The Generate Cross Reference dialog box will appear. After selecting all the desired fields in the dialog box, select Ok to generate a new cross reference list.
Select Cancel to return to the existing cross reference list.
2. If you do not have the cross reference list displayed, select Cross Reference from the View menu.
The current cross reference list will be displayed. Select Generate Cross Reference from the Tools menu. The Generate Cross Reference dialog box will appear.
After selecting all the desired fields in the dialog box, select Ok to generate a new cross reference list. Select Cancel to return to the existing cross reference list.
3. If you only desire to re-order the existing cross reference list by a different key field
(while the cross reference list is displayed), select the desired key field from the
Tools menu.
The options are Sort by Operand, Sort by Symbol, Sort by Line/Rung, and Sort by
Operator.
After the desired key field is selected, the program will re-order the cross reference list by the selected key field.
C
___________________________________________________________________________
16/3
C
___________________________________________________________________________
16/4
17
17 Exporting source files
17.1 Introduction
Using a PL7-07 application it is possible to generate a text file using a source program export function. This text file is compatible with the PL7 Micro import function.
This operation transfers a PL7-07 application for TSX Nano PLC to the PL7 Micro programming software for TSX Micro PLCs.
17.2 Principle
To perform the export, the application must previously have been open in PL7-07. The function can be accessed from the File-Export-Source program menu:
C
A browser window is used to select the name and the target directory where the file to be exported will be placed.
The file extension, *.IL for List or *.LAD for Ladder, is automatically selected according to the editor selected in preferences. If the user changes the export file extension, the format (List or Ladder) of the file will change. It is therefore possible to select the format of the export file independently of the language chosen to create the application.
Note
The application to be exported must be valid in List or reversible List/Ladder.
___________________________________________________________________________
17/1
C
An export file contains:
• An information header
• The List or Ladder program
• The configuration objects compatible with PL7 Micro : %TMi, %Ci, %Ri, %DRi, %Kwi
• The symbols associated with objects compatible with PL7 Micro : %Mi, %MWi, %Si,
%SWi, %Ii.j, %Qi.j
The contents of the exported program, to conform with the application structure of PL7
Micro do not contain:
• Line or end of line comments placed in the rung
• Subroutines
• Grafcet steps
• Post-Grafcet processing (POST)
• Objects which are not compatible with PL7 Micro : Fast counters, etc.
In the exported program, positions containing unsupported object addresses are replaced by a blank.
___________________________________________________________________________
17/2
Diagnostics/Maintenance Contents
Part D
Section
1 Troubleshooting and fault analysis
Troubleshooting using status LEDs
1.1-1 Troubleshooting the "base PLC" PLC or peer PLC
1.1-2 Troubleshooting the I/O extension
1.1-3 Troubleshooting the "base PLC" PLC, peer PLC or I/O extension
1.1-4 Troubleshooting TSX AMN 4000/4001 analog modules
Fault analysis using system bits and words
Page
D
___________________________________________________________________________
D/1
D
Diagnostics/Maintenance
Section
Contents
Part D
Page
___________________________________________________________________________
D/2
1
1 Troubleshooting and fault analysis
1.1
Troubleshooting using status LEDs
The user is informed about the operating mode together with any PLC operating faults by the status LEDs on the front panel.
Note :
Each time the PLC is switched on, all the LEDs are lit for a period of approximately one second corresponding to the self-test phase. Outputs are not activated.
1.1-1 Troubleshooting the "base PLC" PLC or peer PLC
LED status
RUN
LED
Meaning
PLC off or application not executable
PLC in STOP
Probable cause
PLC not powered or syntactically invalid application.
PLC in RUN
Required stop (control using RUN/STOP
%I0.
● input or the terminal) or stop caused by an execution fault (watchdog timeout, or use of a function which has not been implemented or is prohibited).
Normal operation.
ERR
LED
Operation OK Normal operation.
Application not executable
Internal faults
Application not present, invalid, checksum fault, watchdog timeout.
• Hardware watchdog timeout.
• Self-tests indicate a fault (Prob accessing
RAM, EEPROM or schedule block).
• Mis-wiring on extension port
I/O
LED
Operation OK
I/O fault
Normal operation.
I/O faults :
• Outputs failed
• Sensor supply fault.
• Configuration fault.
COM
LED
No exchange present on extension link
Exchanges present on extension link
Exchanges present on
Modbus link
LED flashing LED off LED lit continuously
___________________________________________________________________________
1/1
D
D
1.1-2 Troubleshooting the I/O extension
LED status
RUN
LED
ERR
LED
Meaning
Extension off or not connected to extension link
Base PLC in STOP
(same as base PLC
LED)
Base PLC in RUN
(same as base PLC
LED)
Operation OK
Internal faults
I/O
LED
Operation OK
Extension I/O fault
COM
LED
LED off
No exchange present on extension link
Exchanges present on extension link
LED flashing
Probable cause
Extension not powered, not connected or connection error on extension connection cable.
Identical to those of base PLC.
Normal operation.
Normal operation.
• Hardware watchdog timeout.
• Self-tests show a fault.
• Mis-wiring on the extension port
Normal operation.
I/O faults :
• Outputs failed
• Sensor supply fault.
LED lit continuously
___________________________________________________________________________
1/2
Troubleshooting and fault analysis 1
1.1-3 Troubleshooting the "base PLC" PLC, peer PLC or I/O extension
LED status
LED
I0 to I13
Meaning
Input not active
Probable cause
Normal operation if sensor not conducting.
Input active Normal operation if sensor is conducting
LED
O0 to O9
Output not active Normal operation if output not activated.
Output active Normal operation if output activated.
D
LED off LED lit continuously
If LEDs I5 (TSX Nano 10 I/0), I7 (TSX Nano 14 I/O), I8 (TSX Nano 16 I/0), I11 (TSX Nano
20 I/O) or I13 (TSX Nano 24 I/0) are flashing (series of 5 short flashes every second), the memory display mode is enabled. (1)
LEDs I0 to I7 and O0 to O7 show state 0 (off) or 1 (lit) of internal bits %M112 to %M127.
I2
I3
I4
I5
LED
I0
I1
I6
I7
Meaning
%M112
%M113
%M114
%M115
%M116
%M117
%M118
%M119
Type
TSX Nano
10/14/16
20/24 I/O
TSX Nano
20/24 I/O
LED
O 0
O 1
O 2
O 3
O 4
O 5
O 6
O 7
Meaning
%M120
%M121
%M122
%M123
%M124
%M125
%M126
%M127
Type
TSX Nano
10/14/16
20/24 I/O
TSX Nano
20/24 I/O
(1) In this case, system bit %S69 is at state 1.
___________________________________________________________________________
1/3
D
1.1-4 Troubleshooting TSX AMN 4000/4001 analog modules
LED status
RUN
LED
Meaning
Module off or application not executable
Probable cause
Module not powered or connected
ERR
LED
I/O
LED
COM
LED
Application in RUN
Operation OK
Normal operation.
Normal operation.
Incorrect module addressing
Internal faults
Operation OK
High or low stops exceeded on analog inputs
Communication in progress
Modify the position of the selector switch on the front panel of the module
• Self-calibration fault.
• Self-tests indicate a fault.
Normal operation.
LED off
Exchanges in progress on extension link
LED flashing LED lit continuously
___________________________________________________________________________
1/4
Troubleshooting and fault analysis 1
1.2
Fault analysis using system bits and words
If a fault is detected, the PLC system sets a system bit or word corresponding to the error which has been detected. The application program can use this information.
The FTX 117 terminal or PL7-07 Data editor (on FTX 417/507, FT 2000 or compatible
PC) can display system bits (%S key) and system words (%SW key). See Data editor,
Part C, Section 9 in the FTX 117 manual, or Part C, Section 14 of the PL7-07.
1.2-1 System bits
System Function bit
%S10 I/O fault
%S11
Description
Watchdog timeout
Normally at 1. It is set to state 0 when an I/O fault is detected on the base PLC or the peer PLC (configuration fault, exchange fault, hardware fault, disconnection of protected solid state output). Bits
%S118 and %S119 indicate in which PLC the fault is and words
%SW118 and %SW119 detail the nature of the fault. (See Section 5.2)
Bit %S10 is reset to state 1 when the fault is cleared.
Normally at 0, it is set to state 1 by the system when the program execution time (scan time) exceeds the maximum scan time (150 ms software watchdog). Watchdog timeout causes PLC to change to STOP).
D
%S19
%S71
%S118
%S119
Scan period overrun
(periodic task)
Normally at 0, this bit is set to 1 by the system in the event of a scan period overrun (scan time greater than the period defined by the user at configuration or programmed in SW0).
This bit must be reset to 0 by the user.
E x c h a n g e via extension link
Initially set to 0. It is set to 1 when an exchange via the extension link is detected. This bit is set to 0 when no exchange is performed via the extension link. Word %SW71 in the base PLC shows the list and status of the available extensions.
I/O fault on base
PLC
I/O fault on peer
PLC
Normally at 0. It is set to 1 when an I/O fault is detected on the base
PLC. Word %SW118 determines the nature of the fault. Bit %S118 is reset to 0 when the fault is cleared.
Normally at 0. It is set to 1 when an I/O fault is detected on the peer
PLC. Word %SW119 determines the nature of the fault. Bit %S119 is reset to 0 when the fault is cleared.
___________________________________________________________________________
1/5
D
1.2-2 System words
System Function word
%SW71 Devices on
PLC comm link
%SW118 Base
PLC status
%SW119 Peer
PLC status
Description
Shows the comm status of each peer PLC and I/O ext. with the base PLC : bit 1 : I/O extension bit 2 : peer PLC n°2 bit 3 : peer PLC n°3 bit 4 : peer PLC n°4
Bit at 0 if there is no extension or peer, no power, not wired or a fault.
Bit at 1 peer PLC present and exchange with the base PLC.
Shows faults detected on the base PLC.
bit 0 : 0= failure of one of the outputs (1) bit 3 : 0= sensor supply fault bit 8 : 0= TSX 07 internal fault or hardware fault bit 9 : 0= external fault or comm. fault bit 11 : 0= PLC performing self-tests bit 13 : 0= configuration fault
All other bits of this word are at 1 and are reserved. Thus, for a PLC which has no fault, the value of this word is : 16#FFFF.
Shows faults detected on peer PLC (this word is only used by the base PLC). The bit assignment of this word is identical to that of word
%SW118, except for : bit 13 : not significant bit 14 : peer PLC now missing although it was present at initialization
(1) after a shortcircuit or overload of the protected transistor outputs.
___________________________________________________________________________
1/6
Application example Contents
Part E
Section
1 Specifications : automatic car wash
Description of the application
Graphic representation of the wash cycle
Page
3 Solution using TSX Nano PLC with 16 I/O 3/1
Programming the RTC schedule block 3/7
___________________________________________________________________________
E/1
E
E
Application example Contents
Part E
Important
The example described in this section is for information only. When used in an industrial application it will require modifications depending on the safety rules which apply to the sector of activity concerned.
___________________________________________________________________________
E/2
1
1 Specifications : automatic car wash
1.1
Description of the application
A car wash comprises :
• A gantry supporting a horizontal roller and vertical rollers, driven by a motor with two operating directions (forward and reverse).
• A motor to rotate the horizontal roller and vertical rollers.
• A motor to raise and lower the horizontal roller.
Limit switches control :
• Upper limit of the horizontal roller
• Forward and rear limit of the gantry.
Rotation of rollers
Gantry forward
Raise gantry
Gantry reverse
Roller upper
limit switch
Move gantry down
E
Gantry forward limit switch
Cycle indicator lamp
Manual raise roller pushbutton
Vehicle present proximity sensor
Start pushbutton
Manual gantry reverse pushbutton
Gantry rear limit switch
Stop pushbutton
___________________________________________________________________________
1/1
E
1.2
Application operation
1.2-1 Automatic wash cycle
Initial conditions : The gantry is at the "rear" position (rear limit switch) and the horizontal roller is in the raised position (upper limit switch). A vehicle is present in the washing area (vehicle present proximity sensor).
When the initial conditions are fulfilled, pressing the start pushbutton starts the following cycle :
• Cycle indicator lamp is lit, followed by a ten second wait period (KA0).
• The horizontal roller moves down (KM1) for five seconds (KA1).
• The rollers start to rotate (KM3) and the gantry moves forward (KM4). It is presumed in this example that the water spray pumps are activated at the same time as the motor which rotates the rollers.
• Forward movement of the gantry is stopped by the gantry forward limit switch and the gantry reverse command is given (KM5).
• Gantry reverse and rotation of the rollers are stopped by the gantry rear limit switch.
The command is given to raise the horizontal roller (KM2) up to the upper limit switch which ends the cycle.
A real-time clock controls the times (Monday to Saturday, 8.00 to 19.30). Outside these times, no start request is accepted.
A weekly counter counts the number of washes performed. It is automatically reset to zero every Monday at 8.00 a.m. Another module counts the total number of washes performed over the weeks.
1.2-2 Manual immediate stop
A latching pushbutton can stop the cycle at any time (immediate stop of all motors). To start a new cycle, the following operations must be performed :
• Raise the horizontal roller to the upper position (to upper limit switch) by holding down the manual raise roller pushbutton.
• Return the gantry to the rear position (up to rear limit switch) by holding down the manual gantry reverse pushbutton.
• Release the stop pushbutton.
___________________________________________________________________________
1/2
Application example 1
1.3
Graphic representation of the wash cycle
The Grafcet chart below is a graphic representation of the automatic operation of the car wash.
Vehicle waiting
Initial conditions and start pushbutton
10 s time delay start cycle
Indicator lamp lit
10 s time delay (KA0)
Move roller down (KM1)
5 s time delay
5 s time delay (KA1)
Rotate rollers
(KM3)
Rear limit switch
Raise roller
(KM2)
Upper limit switch
Washing counter
Gantry forward
(KM4)
Forward limit switch
Gantry reverse
(KM5)
___________________________________________________________________________
1/3
E
E
___________________________________________________________________________
1/4
2.1
Power circuit
2
2 Hard-wired solution
Raise/move down roller
Rotate rollers
Gantry forward/reverse
Control circuit
2.2
Control circuit
The diagram overleaf shows the automatic operation and manual stop. The real-time clock and totalling counter are not shown in this diagram.
Two control relays with mechanical latching memories (KA0 and KA2) memorize the stage reached in the cycle. This means that after a power outage, the cycle continues from the state where it stopped. The two time delays are provided by two time-delay options on KA0 and KA1.
The rear and forward limit switches require two additional control relays (KA3 and KA4) due to the large number of contacts used in the layout.
E
___________________________________________________________________________
2/1
Immediate stop
Cycle pushbutton
Vehicle present
Rear limit switch
Upper limit switch
Manual raise
E
Move roller down
Raise roller
Fwd. limit switch
Rear limit switch Fwd.
limit switch
Manual
return
Upper limit switch
Rear limit switch
Rotate rollers
Gantry forward
Gantry reverse
___________________________________________________________________________
2/2
3
3 Solution using TSX Nano PLC with 16 I/O
3.1
Power circuit
This layout is identical to that for the hard-wired logic solution. The 110VAC supply to the TSX Nano PLC is provided via a 440VAC(or 380 VAC)/110VAC transformer. The supply voltage to the outputs is 24VAC and provided by a second transformer.
Raise/lower roller
Rotate rollers
Gantry forward/reverse
TSX Nano
PLC
E
___________________________________________________________________________
3/1
3.2
PLC connection diagram
Manual gantry reverse
Manual raise roller
Upper limit switch
Rear limit switch
Forward limit switch
Stop cycle
Start cycle
Vehicle present
Fu
E
Fu
TSX Nano with 16 I/O
Extension
Gantry reverse
Gantry forward
Rotate rollers
Raise roller
Move roller down
Cycle indicator lamp
___________________________________________________________________________
3/2
Solution using TSX Nano PLC with 16 I/O 3
3.3
Parts list
3.3-1 PLC inputs
Item
Vehicle present
Start cycle
Stop
Forward limit switch
Rear limit switch
Upper limit switch
Manual raise
Manual return
Address
%I0.0
%I0.1
%I0.2
%I0.3
%I0.4
%I0.5
%I0.7
%I0.8
Description
Vehicle proximity sensor
Start pushbutton
Stop pushbutton
Gantry forward limit switch
Gantry rear limit switch
Roller upper limit switch
Manual raise roller pushbutton
Manual gantry reverse pushbutton
3.3-2 PLC outputs
Item
Indicator lamp
KM1
KM2
KM3
KM4
KM5
Address
%Q0.0
%Q0.1
%Q0.2
%Q0.3
%Q0.4
%Q0.5
Description
Cycle indicator lamp
Move roller down contactor
Raise roller contactor
Rotate rollers contactor
Gantry forward contactor
Gantry reverse contactor E
3.3-3 PLC internal variables
Type Address
Internal bit
Internal bit
Internal bit
Internal bit
Internal bit
Internal bit
Internal bit
Internal bit
System word
System word
Timer function
Timer function
Counter function
%M0
%M1
%M2
%M3
%M4
%M5
%M6
%M7
%MW0
%SW50
%TM0
%TM1
%C0
Description
Start latch variable (KA0)
Move roller down variable (KA1)
Gantry forward latch variable (KA1)
Schedule block output variable
Monday test variable
Variable to create pulse on %M4
Variable to create pulse on %M
Variable to test timer output on %TM1
Wash number totalling counter
Real-time clock current seconds/day
Start time delay
Move roller down time delay
Weekly wash counter
3/3
E
3.4
Equivalent electrical scheme
The circuit diagram modified for the PLC solution, which is directly based on the control circuit of the hard-wired solution in Section 2.2, is as follows.
Stop
Cycle pushbutton
Vehicle present
Move roller down
Raise roller
Rotate rollers
Gantry forward
Gantry return
Control relays KA0, KA1 and KA2 are replaced by internal bits %M0, %M1 and %M2.
Control relays KA3 and KA4 are not applicable, since the number of tests on a single
PLC variable is not limited in a program.
The rising edge at internal bit %M4, set to state 1 every Monday (by testing the first four bits of system word %SW50) sets the weekly wash counter (counter %C0) to zero.
The totalling counter for the total number of washes (internal word %MW0) is automatically reset to 1 when it reaches 30 001.
___________________________________________________________________________
3/4
Solution using TSX Nano PLC with 16 I/O 3
3.5
Ladder program
The reversible Ladder program is as follows:
START_PB PROX_SEN
SCHED
_BLOCK_VAR
RUL
_SWITCH
GRL
_SWITCH
%I0.1
GANTRY_FOR
_LATCH_VAR
%I0.0
RUL
_SWITCH
%M3 %I0.5
%I0.4
%M2
STOP_PB
%I0.5
%I0.2
START_LATCH
%M0
IND_LAMP START_TIME_DELAY
IN
%TM0
Q
%Q0
START_TIME
_DELAY_Q
%TM0.Q
ROLL_DOWN
_VAR
ROLL_DOWN_TIME_DELAY
IN
%TM1
Q
%M1
START_LATCH
S
%M0
START_LATCH
R
%M0
IND_LAMP
%Q0
ROLL_DOWN
_VAR
%Q0
E
STOP_PB ROLL_DOWN
_VAR
ROLL_DOWN
_TIME_DELAY
ROLL_RAISE
%I0.2
GANTRY_FOR
_LATCH_VAR
%M1 %TM1.Q
%Q0.2
GRL
_SWITCH
RUL
_SWITCH ROLL_DOWN
%M2 %I0.5
STOP_PB
MAN_RAISE
%I0.2
%I0.7
ROLL_DOWN
_VAR
ROLL_DOWN
_TIME_DELAY.Q
ROLL
_RAISE
%M1 %TM1.Q
%Q0.2
ROLL_DOWN
%Q0.1
ROLL_RAISE
%Q0.2
ROLL_ROTATE
%Q0.3
___________________________________________________________________________
3/5
E
STOP_PB ROLL
_ROTATE
GANTRY_FOR
_LATCH_VAR
GFL
_SWITCH
GANTRY
_REV
%Q0.5
%I0.2
%Q0.3
%M2 %I0.3
GFL_SWITCH
STOP_PB ROLL
_ROTATE
%I0.3
GANTRY_FOR
_LATCH_VAR
GRL
_SWITCH
GANTRY
_FOR
%I0.2
STOP_PB
%Q0.3
MAN_RET
%M2 %I0.4
%Q0.4
%I0.2
START_LATCH
%I0.8
%TM0
SCHED
_BLOCK
CURRENT:
X0
SCHED
_BLOCK
CURRENT:
X1
SCHED
_BLOCK
CURRENT:
X2
SCHED
_BLOCK
CURRENT:
X3
%SW50:X0 %SW50:X1 %SW50:X2 %SW50:X3
MONDAY
_TEST_VAR
%M4
GANTRY_FOR
_LATCH_VAR
PULSE_VAR WEEKLY_COUNTER
%C0
R E
%M5
S
D
CU F
%M2
CD
MONDAY_TEST
_VAR
%M4
GANTRY_FOR_PULSE_VARI
_LATCH_VAR
%M2
MONDAY_TEST
_VAR
%M6
%M2
COMPARE
%MW0=30001
GANTRY
_FOR
%Q0.4
GANTRY_FOR
_LATCH_VAR
S
%M2
GANTRY_REV
%Q0.5
GANTRY_FOR
_LATCH_VAR
R
%M2
MONDAY
_TEST_VAR
%M4
PULSE_VAR
%M5
OPERATE
INC %MW0
PULSE_VARI
%M6
OPERATE
%MW0:=1
END
___________________________________________________________________________
3/6
Solution using TSX Nano PLC with 16 I/O 3
3.6
Function block configuration
The function blocks can be configured for timers %TM0 and %TM1and counter %C0 from the Configuration menu.
• Start time delay %TM0
• Move roller down time delay %TM1
• Weekly wash counter %C0
3.7
Programming the RTC schedule block
The schedule block RTC0 is configured from the Configuration menu. This programming corresponds to the opening of the car wash :
• From 2 January
to 31 December
• Monday,Tuesday,
Wednesday, Thursday,
Friday, and Saturday
• From 8:00 to 19:30.
___________________________________________________________________________
3/7
E
E
___________________________________________________________________________
3/8
Products which can be connected Contents
Part F
Section
1 Terminal port communications
Characteristics of the terminal port
General information about the terminal port
UNI-TELWAY Time-out (TSX 07 3•)
XBT operating terminals or CCX 17 operator panels
UNI-TE requests supported by TSX Nano (server)
2 Extension port communications 2/1
Characteristics of the MODBUS / JBUS extension port 2/1
2.2-2 Configuring the MODBUS link
2.2-3 Requests supported by the TSX Nano in MODBUS
2.2-5 Associated bits and system words
2.3-1 Reading n internal bits %Mi
2.3-2 Reading n internal words %MWi
2.3-3 Writing an internal bit %Mi
2.3-4 Writing an internal word %MWi
___________________________________________________________________________
F/1
F
Page
F
Products which can be connected Contents
Part F
Section
2.3-5 Writing n internal bits %Mi
2.3-6 Writing n internal words %MWi
2.3-8 Algorithm for calculating CRC 16
Access requests by the TSX Nano to the UNITE server
Page
___________________________________________________________________________
F/2
1 Terminal port communications
1.1
Characteristics of the terminal port
• Characteristics
Type of link
Protocol
Baud rate
: RS485
: UNI-TE format V2
(V1 format for TSX Nano < V3.1).
: 9600/19200 bits/s
Type of connector
Max. link distance
FTX117
1 start bit, 8 bit data, odd parity, 1 stop bit
: 8-pin rapid connect mini-DIN
: 10 m
UNITELWAY devices : 10 m (without junction box)
ASCII devices : 10 m
• Connector pinout - UNI-TELWAY devices
1 D+
2 D-
3 Not connected
4 /DE
5 /DPT
6 Not connected
7 0 V
8 5 V
The signal /DPT is used to select the operating mode of the terminal port :
/DPT = 1 UNI-TELWAY Master mode
/DPT = 0 UNI-TELWAY Slave mode or ASCII mode.
Connect pins 5 to 7 to select ASCII mode.
F
Notes :
Equipment should be connected with the power off (except for programming terminals).
The use of ASCII and UNI-TELWAY devices is exclusive.
An ASCII device must be disconnected to allow the use of a programmer (FTX117 or PC).
___________________________________________________________________________
1/1
F
1.2
General information about the terminal port
The TSX Nano terminal port can operate in three different modes :
• UNI-TELWAY Master (TSX 07 2
•
TSX 07 3
•
),
• UNI-TELWAY Slave (TSX 07 3
•
only),
• ASCII (TSX 07 2
•
TSX 07 3
•
).
The operating mode of the terminal port is selected by software configuration and using signal /DPT (pin n°5) on the Mini DIN socket :
• When signal /DPT is at 1 (pin n°5 not connected), the terminal port is in UNI-TELWAY
Master mode.
• When signal /DPT is at 0 (pin n°5 connected to pin n°7=0V), the terminal port is in
ASCII mode or UNI-TELWAY Slave mode. The selection is made by software configuration using the programming tools PL707 and FTX 117 (ASCII mode by default).
The state of /DPT is shown by system bit %S100.
Configuration screen :
___________________________________________________________________________
1/2
Terminal port communications
1
1.3
TSX Nano in ASCII mode
This character mode, simplified on the TSX Nano is used to transmit (TSX 07 2
•
and TSX
07 3
•
) and/or receive (TSX 07 3
•
only) a character string to/or from a simple device (printer or terminal) without flux control.
This mode is designed to operate in a point-to-point link.
The terminal port configuration can be modified on TSX 07 3
•
modifications are made in the PLC configuration screen :
• Type :
• Speed :
Half-Duplex
1200, 2400, 4800, 9600 or 19200 bds
• Format : 1 start bit, 7 or 8 data bits, 1 or 2 stop bits
• Parity : even, odd, none.
The values in bold are the default values, they cannot be modified on TSX 07 2
•
.
ASCII configuration screen :
Programming in ASCII mode is possible using the EXCH instruction, as well as the exchange control function block %MSG. See section 3.4-6, part B.
___________________________________________________________________________
1/3
F
1.4
TSX Nano Master on UNI-TELWAY
The TSX Nano is compatible with other UNI-TELWAY devices such as man-machine interfaces (MMI), identification devices and drives. This section provides general guidelines for connecting these devices on the UNI-TELWAY bus. Refer to the user manuals for the devices to obtain specific information.
When the TSX Nano is the UNITELWAY communication master for slave devices which are connected to the TSX Nano terminal port, it controls the network and polls the slave devices at periodic intervals.
Example of architecture
TSX Nano Master
Client Client/server
F
The TSX Nano is normally a UNI-TE server. However it can provide limited UNI-TE client services for TSX 07 2
•
:
• Configurations
Most UNI-TELWAY devices require the use of two addresses. The first address is configured physically by the user using microswitches; the second address is generally the physical address +1. The TSX Nano can communicate with a programming terminal and up to two additional UNI-TELWAY devices.
Address assignment :
0 : TSX07 (communication master)
1
2-3-5 :
: programmer (FTX117 hand-held terminal or PL7-07 software) client device only (TSX 07 2•)
4 :
2-3-4-5: client and/or server device (TSX 07 2•) client and/or server devices (TSX 07 3•)
___________________________________________________________________________
1/4
Terminal port communications
1
Summary of devices that can be connected to various addresses.
Reference
Device 1
Permissible Addresses
2,3 4,5
Programming terminal
FTX117
PL7-07
Yes No No
MMI
Identification devices
XBT-8
CCX17
XGS
No
No
Yes
Yes
Yes
Yes
Speed controller ATV No Yes (1) Yes
(1) TSX Nano V3 only
The terminal port configuration cannot be modified in UNI-TELWAY Master mode. It manages 5 slave link addresses depending on the transmission format as follows :
• Type :
• Speed :
Half-Duplex
9600 bds
• Format : 1 start bit, 8 data bits, 1 stop bit
• Parity : odd.
The Time-out parameters can be set in the configuration screen.
• UNI-TE server function :
The TSX Nano responds to commands initiated by the client. A client is an intelligent device which can initiate communication with the TSX Nano. It can write data to or read data from the TSX Nano.
TSX Nano
Server
Request
F
Confirmation report
Client
Addressing
The TSX Nano is always address 0 (master).
Client
• The TSX Nano polls for addresses 1 to 5
• The programmer (either the FTX117 or the PL707 software) is always address 1
• Generally, the address of a UNI-TELWAY device is set by microswitches at a junction box or by cable connection.
___________________________________________________________________________
1/5
Notes :
- Communication between slaves is not possible when the bus master is a TSX
Nano.
- The TSX 07 2
•
cannot be a UNI-TELWAY slave.
All the bus devices can interrogate the TSX Nano server system by using the target address 0.254.0. The TSX Nano UNITE server only responds to frames sent to this address. Messages containing a different target address will be ignored.
• TSX Nano as a client :
The TSX Nano initiates communication with the server. The server is an intelligent device which executes the commands sent by the TSX Nano.
TSX Nano
Client
Confirmation report
(TSX 07 2
•
)
Request
Server
F
The TSX 07 3• Master can send a request to any slave with an address between 1 and
5 using the EXCH instruction. It uses source address 0.254.16.
The TSX 07 2• can only send a request to slave at address 4 (using the EXCH instruction). Consequently, only WRITE and UNSOLICITED DATA (unconfirmed) requests may be used. Source address 0.254.10 is used.
WARNING :
The UNI-TE client function of the TSX 07 3
•
reverses the data transmitted (most significant/ least significant) in relation to TSX 07 2
•
. Applications which operate with TSX 07 2
•
must be modified to take account of this reversal if they are loaded onto a TSX 07 3
•
.
Programming in UNI-TELWAY Master mode is possible using the EXCH instruction, as well as the exchange control function block %MSG. See section 3.4-6, part B.
___________________________________________________________________________
1/6
Terminal port communications
1
1.5
TSX Nano Slave on UNI-TELWAY
This protocol is only available with TSX Nano version 3 or later (TSX 07 3
•
).
It is used for simultaneous, multidrop connection of several devices (PLC, programming terminal, MMI device, speed controller, etc.).
Example of architecture
Unlike Master mode, the terminal port configuration can be modified by the user in
UNI-TELWAY slave mode using the programming tools PL7 07 or FTX 417 in the PLC configuration screen :
• Type :
• Speed :
Half-duplex
1200, 2400, 4800, 9600 or 19200 bds
• Format : 1 start bit, 7 or 8 data bits, 1 or 2 stop bits
• Time-out : 30 to 255 (see section 1.6)
• Address : 4 (1 to 97)
• Parity : even, odd or none.
The values in bold are the default values.
The TSX Nano uses 2 consecutive logic addresses :
• AD0 : base address (that of the configuration), known as server address. Any device
(local or remote) can address the TSX Nano system server using AD0 as target address.
• AD1 = AD0 + 1 known as client address. With this address the TSX Nano can transmit a request to any UNI-TELWAY bus device (Master or Slave) using the EXCH instruction.
See section 3.4-6 part B.
F
___________________________________________________________________________
1/7
The modification of terminal port characteristics made in the configuration screen is only taken into account on a power restart or on modification of the signal /DPT on the Mini DIN socket (disconnection / reconnection of the terminal port).
F
1.6
UNI-TELWAY Time-out (TSX 07 3
•
)
The link layer of the UNI-TELWAY protocol (Master or Slave) uses a time-out.
This Time-out corresponds to the duration of the transmission of a number of characters sent on the line :
• TSX 07 3
•
: 30 characters by default. This duration is increased to 125 characters if the TSX Nano does not have an application.
Once a frame has been transmitted, a device (Master or Slave) declares a Time-out.
If no acknowledgment is received before the end of the time-out, the exchange is not acknowledged.
The transmitter repeats its frame as soon as the protocol allows.
The terminal port configuration screen is used to configure a Time-out of between
30 and 8000 characters.
Values between 30 and 250 inclusive correspond to an equivalent number of characters. Values between 251 and 255 inclusive correspond to the following values :
• 251 = 500 characters
• 254 = 4000 characters
• 252 = 1000 characters
• 255 = 8000 characters.
• 253 = 2000 characters
On power-up or on modification of the signal /DPT, the configured value is loaded into the least significant bit of system word %SW14 (the most significant bit is ignored).
Thus, the Time-out value can be fine-tuned by writing the new value in the system word
%SW14. It will be taken into account at the end of the PLC scan.
A longer Time-out allows the TSX Nano to be connected to slow devices, for example modem type.
It is possible to reduce the value of the Time-out to 10 characters by using system word %SW14.
___________________________________________________________________________
1/8
Terminal port communications
1
Important :
When connecting certain devices (eg modems) to a TSX Nano via the UNI-TELWAY link, their response times mean that the time-out parameters must be set to value
255 (approximately 8 s at 9600 bd/s).
This value prevents all subsequent communication between the TSX Nano and a programming terminal using the UNI-TELWAY link with standard parameters.
It is therefore necessary to :
- modify the value of the AUTOSPEED parameter (0 instead of 1) and the number of UNI-TELWAY addresses (5 instead of 3) in the DUNTLW.001 file under DOS,
Windows 3.1/95/98 or using the XWAY tool under Windows NT.
- modify the timeout value of the PLC UNI-TELWAY link,
- reassign the initial values in DUNTLW.001 under DOS, Windows 3.1/95/98 or using the XWAY tool under Windows NT.
___________________________________________________________________________
1/9
F
1.7
XBT operating terminals or CCX 17 operator panels
• PLC connection
The XBT operating terminal or CCX 17 operator panel is connected via the TSX Nano
PLC terminal port using cable XBT Z968.
TSX Nano PLC
XBT-Z968 cable
F
• Characteristics of the link
- RS 485 link
- UNI-TE protocol
• XBT terminals which can be connected via the TSX Nano PLC terminal port
- XBT-A8 • - XBT-C8 • - XBT - H
- XBT-B8 •
- XBT-BB8 •
- XBT-K8 •
- XBT-M8 •
- XBT - P
- XBT - E
- XBT-A8 •
• CCX 17 operator panels which can be connected via the TSX Nano PLC terminal port
- TCCX 17 20 F - TCCX 17 20 L - TCCX 17 30 L
- TCCX 17 20 FW
- TCCX 17 20 FPS
- TCCX 17 20 LW
- TCCX 17 20 LPS
- TCCX 17 30 LW
- TCCX 17 30 LPS
• Setup :
- XBT operator terminal :
(see technical documentation relating to the XBT being used)
- TSX Nano / XBT exchanges
The PL7 program sends messages to the XBT terminal via :
- EXCH instruction : to transmit messages
- %MSG function block : to control data exchanges
(see Part B, Section 3.4-6 : transmitting messages and controlling data exchanges).
• Comments
XBT and TSX 07 data syntax (1)
Data
Internal bit
XBT or CCX17 syntax
Bi
TSX Nano syntax
%Mi
Internal word Wi %MWi
(1) except XBT - H/P/E.
___________________________________________________________________________
1/10
Terminal port communications
1
1.8
UNI-TE requests supported by TSX Nano (server)
Standard requests
Service Request
Data
(read)
Data
(write)
Operating modes
Read a bit
Read a word
Read objects
Write a bit
Write a word
Write objects
RUN
Request Confirm Meaning
Hex. Dec. Hex. Dec.
00 00 30 48 Read a %Mi bit.
04 04 34 52 Read a %MWi word.
36 54 66 102 Read objects (%Mi, %Mi:L,
%Mwi, %Mwi:L).
10 16 FE 254 Write a %Mi bit
14 20 FE 254 Write a %MWi word.
37 55 FE 254 Write objects (%Mi, %Mi:L,
%Mwi, %Mwi:L).
24 36 FE 254 Set device to RUN.
STOP 25 37 FE 254 Set device to STOP.
Special requests
Service Request Request Confirm
Hex. Dec. Hex. Dec.
Meaning
Data
(read)
Read a system bit
Read a constant word
Read a system word
Read Grafcet steps
01 01 31 49 Read a %Si bit
05 05 35 53 Read a %KWi word
06 06 36 54 Read a %SWi system word
2A 42 5A 90 Read %Xi Grafcet steps
Data
(write)
Write a system bit
Write a system word
11 17 FE 254 Write a %Si bit
15 21 FE 254 Write a %SWi word
___________________________________________________________________________
1/11
F
F
___________________________________________________________________________
1/12
2
2 Extension port communications
2.1
Characteristics of the MODBUS / JBUS extension port
The extension port of the TSX 07 3
●
can be used to connect other TSX Nano PLCs as
I/O extension (see part A, section 1.4) or even as peer PLC (part A, section 1.10).
From TSX 07 3
●
, this extension port allows a MODBUS Slave type link.
Characteristics of the MODBUS link:
• Physical layer: RS485 non isolated, maximum length 200 meters
• Link layer: Asynchronous transmission
ASCII frame (7 bits) or RTU (8 bits)
Data rate: 1200, 2400, 4800, 9600 or 19200 bds
Parity: Even, odd or none
Number of stop bits: 1 or 2
Inter-character time: 3 (1 to 127) characters
• Physical configuration: 28 devices max.
98 logic addresses (1 to 98)
• Services: Bits: 128 bits on request
Words: 120 words of 16 bits on request
Safety: on control parameter (CRC16) for each frame (in RTU).
The values in bold are the default values.
Note: Devices should be connected with the power off.
F
___________________________________________________________________________
2/1
2.2
MODBUS / JBUS on TSX Nano
2.2-1 General
The data exchange services offered (%Mi and %MWi) are common to MODBUS and
JBUS, which allows MODBUS devices to communicate with JBUS devices.
The MODBUS / JBUS protocol allows data exchange between a Master and Slaves, it does not allow direct communication between Slave devices, nor network transparency.
MODBUS communication in ASCII mode:
• Operation in ASCII mode is designed for connecting simple devices (screens, etc).
The frame is complete but the frames are twice as long as in RTU mode.
Detail of an ASCII frame:
Header(3A) Slave no. Function code Data
1 byte 2 bytes 2 bytes 2n bytes
LRC CR LF*
2 bytes 1 byte 1 byte
F
*The system word %SW67 can be used to set the parameters of the end delimiter character (LF). It is written to 16#000A by the system on a cold start.
The user can modify this system word by program or by adjustment when the Modbus
Master uses an end delimiter character other than 16#000A.
MODBUS communication in RTU mode:
• A frame in RTU mode does not have a header byte nor an end of message delimiter byte:
Slave no.
Function code
1 byte 1 byte
Data
n bytes
CRC16
2 bytes
___________________________________________________________________________
2/2
Extension port communications 2
Example of connection
By daisy chaining
TSX SCP 114
TSX SCP CU 4030
TSX SCA 50
200 M max.
28 slave devices maximum
D (B)
D (A)
OVL
OVL
TSX SCA 50
TSX Nano
A B SG
___________________________________________________________________________
2/3
F
2.2-2 Configuring the MODBUS link
The extension link in MODBUS / JBUS is configured from the Configuration menu of the PL7 07 by selecting Extension port.
The following dialog box appears:
F
In dynamic operation, the parameters (speed and format) cannot be modified.
There is no mechanism for adapting the speed of the TSX Nano Slave in relation to the speed of the Master.
Any modification made to the speed and protocol format is taken into account by the TSX
Nano as soon as the configuration screen is enabled.
The Extension, I/O Extension, AP2, AP3 and AP4 fields are not significant if MODBUS protocol is selected.
See part C section 5.19 for more details.
___________________________________________________________________________
2/4
Extension port communications 2
2.2-3 Requests supported by the TSX Nano in MODBUS
The TSX Nano supports the requests listed below, others will be rejected with the exception code 01: Function not known:
The MODBUS function only processes one request at a time, as in MODBUS protocol the Master must wait for a response from the slave or for a time-out to be triggered before sending a new request to the slave.
Standard MODBUS requests :
• 01 / 02 : Read n consecutive internal bits : Access to bits %M0 to %M127
• 05
• 15
: Write an internal bit : Access to bits %M0 to %M127
: Write n consecutive internal bits: Access to bits %M0 to %M127
• 03 / 04
• 06
: Read n consecutive words : Access to words %MW0 to %MW255
: Write an internal word: Access to words %MW0 to %MW255
• 16 : Write n consecutive words: Access to words %MW0 to %MW255.
Details of these requests are given in section 2.3.
Access requests to the UNITE server of the TSX Nano:
• 0F : Identification
• 4F : Read CPU
• 24 : RUN
• 25 : STOP
• 33 : INIT
Details of these requests are given in section 2.4.
Exception codes:
An exception code is returned by the slave when it does not know how to process the request.
The response frame thus contains:
• The function code received, incremented by the value 16#0080
• The exception code which depends on the type of error.
The two exception codes processed by the TSX Nano are:
• 01: Function not known (request not supported by the TSX Nano)
• 03: Invalid data (bit or word number not managed by the TSX Nano, writing a bit with a value other than 16#FF00 or 16#0000 etc).
F
___________________________________________________________________________
2/5
F
2.2-4 Managing the COM LED
Once the response to a request has been sent, the TSX Nano switches on the communication LED for 50ms.
The LED then flashes, the frequency of the flashes depends on the exchanges between the Master and the TSX Nano .
2.2-5 Associated bits and system words
When a MODBUS request is processed, the TSX Nano sets the system bit %S70 to 1.
This bit can be used by the user. Reset to 0 is the responsibility of the user.
The system word %SW67 can be used to set the parameters of the end of frame delimiter character (LF) in ASCII mode.
It is written to 16#000A by the system on a cold start.
The user can modify this system word by programming or by adjustment when the
Master uses an end of frame delimiter character other than 16#000A.
___________________________________________________________________________
2/6
Extension port communications 2
2.3
Standard MODBUS requests
These requests can be used to exchange MODBUS objects by accessing objects %Mi and %MWi of the TSX Nano.
The requests are detailed below in RTU mode. In ASCII mode, the data is the same,
CRC 16 is replaced by LRC.
2.3-1 Reading n internal bits %Mi
Function 01 or 02
Question :
Slave number
1 byte
Response :
1 or 2
1 byte
No. of 1st bit
PF Pf
2 bytes
Number of bit
PF Pf
2 bytes
CRC 16
2 bytes
Slave number
1 byte
1 or 2
1 byte
Number of bytes read
2 bytes
Value
Example : reading bit %M3 from Slave 2
Question 02 01 0003
••••••••
0001
Value
CRC 16
CRC 16
2 bytes
Response 02 01 01 xx CRC 16
00 if %M3 = 0
01 if %M3 = 1
F
___________________________________________________________________________
2/7
F
2.3-2 Reading n internal words %MWi
Function 03 or 04
Question :
Slave number
1 byte
Response :
3 or 4
1 byte
No. of 1st word
PF Pf
2 bytes
No. of word
PF Pf
2 bytes
CRC 16
2 bytes
Slave number
1 byte
3 or 4
Number of bytes read
1 byte
Value of 1st word
PF Pf
2 bytes
••••••••••••
Value of last word
PF Pf
2 bytes 1 byte
Example : reading words %MW20 to %MW24 from Slave 6
Question 06 04 14 05 CRC 16
CRC 16
2 bytes
Response 06 04 0A xxxx •••••••••••• xxxx
Value of %MW20
Value of %MW24
CRC 16
___________________________________________________________________________
2/8
Extension port communications 2
2.3-3 Writing an internal bit %Mi
Function 05
Question :
Slave number
5
No. of bit
PF Pf
Value of bit CRC 16
1 byte 1 byte 2 bytes 2 bytes 2 bytes
The "Value of bit" field has two possible values to the exclusion of all others :
• bit at 0 = 0000,
• bit at 1 = FF00.
Response :
Slave number
1 byte
5
No. of bit
PF
2 bytes
Pf
Value of bit CRC 16
1 byte 2 bytes 2 bytes
Example : writing the value 1 in the bit %M3 of Slave 2
Question 02 05 03 FF00 CRC 16
Response 02 05 03 FF00 CRC 16
F
___________________________________________________________________________
2/9
2.3-4 Writing an internal word %MWi
Function 06
Question :
Slave number
1 byte
Response :
6
1 byte
No. of word
PF Pf
2 bytes
Value of word
PF Pf
2 bytes
CRC 16
2 bytes
Slave number
1 byte
6
No. of word
PF Pf
2 bytes
Value of word
PF Pf
2 bytes
CRC 16
2 bytes 1 byte
Example : writing the value 16#3A15 in the word %MW12 of Slave 5
Question 05 06 0C 3A15 CRC 16
Response 05 06 0C 3A15 CRC 16
F
2.3-5 Writing n internal bits %Mi
Function 15
Question :
Slave number
0F
Address of 1st
bit to write
Number of bits to write
Number of bytes
Value of bits to write
CRC 16
1 byte 1 byte
Response :
Slave number
0F
2 bytes 2 bytes
Address of
1st bit written
1 byte
Number of bits written n bytes
CRC 16
2 bytes
1 byte 1 byte 2 bytes 2 bytes 2 bytes
___________________________________________________________________________
2/10
Extension port communications 2
2.3-6 Writing n internal words %MWi
Function 16 (H'10')
Question :
Slave number
1 byte
10
1 byte
Number of 1st word
Number of words
2 bytes 2 bytes
Number of bytes
Value of 1st word
•••••••••••• CRC 16
1 byte 2 bytes 2 bytes
Response :
Slave number
1 byte
10
1 byte
Number of 1st word
Number of words
CRC 16
2 bytes 2 bytes 2 bytes
Example : Writing values 1 and 2 to words %MW16 and %MW17 of Slave 11
Question 0B 10 0010 0002 04 0001 0002 CRC 16
Response 0B 10 0010 0002 CRC 16
2.3-7 Calculation of LRC
LRC: sum in hexadecimal, modulo FF, of the contents of the frame, excluding headers, two's complemented and coded in ASCII.
Example of frame
ASCII frame
3A 30 31 30 38 30 30 30 30 36 31 36 32 33 34 0D 0A
Equivalent binary frame
01 08 00 00 61 62 4872
F
Calculation of LRC
Sum in hexa, modulo FF, of the contents of the frame:
01 + 08 + 00 + 00 + 61 + 62 = CC
H
= 1100 1100 one's complement: add 1:
Hexadecimal conversion
Coding in ASCII
0011 0011
+ 1
0011 0100
3 4
33 34 LRC = 3334
___________________________________________________________________________
2/11
2.3-8 Algorithm for calculating CRC 16
Hex FFFF -> CRC 16
CRC 16
Byte -> CRC 16 n = 0
Shift to right CRC 16
Carry over
CRC 16
POLY -> CRC 16 n = n + 1 n > 7
F
Next byte
Message ended
= or exclusive n = Number of data bits
End
POLY = polynomial CRC 16 calculation = 1010 0000 0000 0001
(polynomial generator = 2 = x 2 = x 15 = x 16 )
In CRC 16, the 1st byte transmitted is the least significant.
___________________________________________________________________________
2/12
Extension port communications 2
2.4
Access requests by the TSX Nano to the UNITE server
The principle consists of coding a UNITE request within a MODBUS request in order to interrogate the UNITE server normally servicing the terminal port.
This mechanism uses the specific function code: 65.
Principle:
MODBUS Master request to Slave
Function code: 65 Request code Category code Data
MODBUS Slave response to Master
Function code: 65 Response code Response data
The category code is always 7.
The UNITE response code can be used to find out the result of the operation performed by the server.
There are three cases :
• Request response code = Request code + 30 H: The operation has been performed by the server, additional information gives exact details of the result of the operation.
• Positive response code = 16#00FE: The operation has been performed correctly and no additional information is transmitted in the response.
• Negative response code = 16#00FD: The server has not been able to perform the operation (request not known, out of range value etc.).
F
___________________________________________________________________________
2/13
2.4-1 Identification
This service can be used to provide identification and structuring information on the device which is targeting a request to the UNITE server.
The Identification request also provides basic diagnostic information, by showing the state of the LEDs and the device and module Status.
F
Request code: 0F
Response code: 3F
Report format: 27 bytes
• Identification type (byte): Byte always equal to H'FF'.
• Product range (byte): This parameter identifies the product range to which the device belongs: H'0B' = TSX Nano range.
• Version (byte): Version number of the device, coded in two BCD 4-bit bytes: H'30' for
TSX07 30/31.
• ASCII string (character string): Specifies the product reference.
On the TSX Nano it consists of one byte (H'10') followed by ASCII text (16 bytes) as follows:
'TSX 07 3'
'1-' if schedule block is present, '0-' if schedule block is not present
'10 ' if 10 I/O, '16 ' if 16 I/O, '16AC' if 16 I/O AC, '24 ' if 24 I/O
H'20'
H'20'
• Device status (byte): Byte always equals 0 for the TSX Nano
• State of LEDs (8 bit table): This byte indicates the state of the 4 indicator LEDs of the
TSX Nano:
RUN (bits 0 and 1), ERR (bits 2 and 3), I/O (bits 4 and 5), COM (bits 6 and 7).
Each LED is coded on 2 bits:
00: Unlit
01: flashing
10: Lit
11: Not significant.
• Base module type (byte): Byte equal to H'30' (type = CPU)
• Manufacturer's reference (byte): Byte equal to H'09'
• Catalogue reference (byte): Defines the type of device:
H'01': Module 10 I/O
H'11': Module 16 I/O
H'21': Module 24 I/O
H'12': Module 16 I/O AC
___________________________________________________________________________
2/14
Extension port communications 2
Bit no.
0
1
3
2
3
4
5
6
7
• Base module status (8 bit table): The values of these fields meet the standard for configurable devices. A bit positioned at 1 indicates a fault.
Class
ERR-INT
ERR-EXT
Reserved
MOD-At
Reserved
ERR-CNF
Reserved
Reserved
Comments
1: TSX Nano hardware fault
1: Sensor supply fault
1: Module in selftest
1: Extension configured but absent or NOK
• Number of components (byte): Byte equal to 0 because the module does not have any submodules.
2.4-2 Read-CPU
This service is used to diagnose the state of a TSX Nano PLC processor.
Request code: 4F
Response code: 7F
Format of report (14 bytes):
• Extension (byte): This field is used to transmit a transaction number: Not significant.
• State of LEDs (8-bit table): see Identification request.
• PLC status (8-bit table): Describes the physical state of the PLC:
Bit 0: RUN (1), STOP (0)
Bit 1: Application executable (1)
Bit 2: Cartridge present (always 1)
Bit 3: Forcing in progress (1)
Bit 4: Reserved: 0
Bit 5: Software fault (1)
Bit 6: Reserved: 0
Bit 7: Reserved: 0
• Address of the reserver (6 byte table): Describes the network address of the application entity which has reserved the processor. On the TSX Nano, this value is fixed at 16#00FF for each byte, to indicate that the processor is not reserved.
F
___________________________________________________________________________
2/15
• Type of application error (byte): Byte always at 0.
• Debug information (8-bit table):
Bit 0: State of forcing (1: Active, 0: No forcing)
Bits 1 to 7: Always at 0.
• Product range (byte): This parameter identifies the product range to which the device belongs: H'0B' = TSX Nano range.
• Application / PLC information (8-bit table):
Bit 0: Application present in RAM (1)
Bit 1: Program in RAM with checksum OK (1)
Bit 2: Program in RAM executable (1)
Bit 3: Program in RAM protected (1)
Bit 4: Program in RAM differs from EEPROM program (1)
Bit 5: Application compatible with OS (1)
Bit 6: Schedule block present (1)
Bit 7: 0
• Backup information (8-bit table):
Bit 0: Application present (1)
Bit1: Checksum OK (1)
Bit 2: EEPROM application executable (1)
Bit 3: EEPROM application protected (1)
Bit 4: Auto load application (1)
Bit 5: Application compatible with OS (1)
Bit 6: 0
Bit 7: 0
F
2.4-3 RUN request
Request code: 24
Response code: FE
Negative result if:
• RUN / STOP input configured in STOP
• Application cannot be executed
• Software fault (watchdog overrun, launching nonexistent G7 step).
Sending this request to a TSX Nano already in RUN is not considered an error.
___________________________________________________________________________
2/16
Extension port communications 2
2.4-4 STOP request
Request code: 25
Response code: FE
Negative result if the application in RAM cannot be executed.
A STOP instruction to a TSX Nano already in STOP is not considered an error.
2.4-5 INIT request
Request code: 33
Response code: 63
• Type of initialization (byte to transmit): Must always be at 1.
• Report: Indicates the result of the initialization operation:
00: Initialization OK
01: Type of initialization other than 1
F
___________________________________________________________________________
2/17
2.5
Limitations
The TSX Nano Slave on MODBUS has the following limitations:
• Physical layer: RS485 only. Does not automatically adapt to the speed of the Master.
• Selector position: The MODBUS protocol is only enabled if the position of the PLC rotary selection switch (automatically read on power-up) shows that TSX Nano is being used as a PLC (positions 0, 5, 6 and 7).
• Protocol: The protocol is Slave only.
• Communication between Slaves: Direct communication between Slaves is not possible. It can only be performed via the application program of the Master.
• Changing, dynamically, from ASCII mode to RTU mode is not possible.
F
___________________________________________________________________________
2/18
Appendices Contents
Part G
Section
Page
Boolean instructions in List language with Ladder equivalent
Tool bar and instruction bar menu options
A.2-1 Configuration Editor menu options
A.2-2 Symbols Editor tools menu options
A.2-3 Ladder Editor instruction bar options
A.2-3.1Extended Ladder Palette options
A.2-4 Ladder Editor Tools menu options
A.2-5 Ladder Viewer Tools menu options
A.2-6 List Editor instruction bar options
A.2-7 Data Editor Tools menu options
PL7-07 PC programming software variables
A.4-1 Entering a password for the first time
A.4-3 Changing from operator level to supervisor level
A.4-5 Password protection for files transferred to an
Instruction scan time and memory usage
Importing and Exporting ASCII program files and symbols files 1/19
Transferring applications between a PC and the FTX 117 terminal1/22
G
___________________________________________________________________________
G/1
Appendices Contents
Part G
Section Page
Troubleshooting installation problems
A.8-1 Installing PL7-07 PC programming software on a
A.8-2 Software installation problems
A.8-3 COM port problems during installation 1/27
A.8-4 Communication error when connecting the PC to the PLC 1/27
A.8-5 Video Display problems 1/28
A.9-1 Running PL7-07 under Windows 3.1
A.9-2 Running PL7-07 under Windows 95/98/NT
A.10 Example of prepositioning Grafcet steps 1/32
A.11 Actions associated with steps
G
___________________________________________________________________________
G/2
Appendices
Appendices
A.1 Boolean instructions in List language with Ladder equivalent
LIST Instruction LADDER Equivalent Description
ST, STN, R, S
AND, ANDN, ANDR, ANDF
OR, ORN, ORR, ORF
R
P N
S Store
Logical Bit 'AND'
Logical Bit 'OR'
P N
AND(, OR( (nest 8 levels) Parentheses
XOR, XORN, XORR, XORF
XOR XORN XORR XORF
Exclusive 'OR'
N Not Reversible Logical 'NOT'
END, ENDC, ENDCN
ENDCN is not reversible
%Li
JMP, JMPC, JMPCN
JMPCN is not reversible
SRn
RET
MCR, MCS
NOP
END
%Li
SRi
END
%Li
End of Program
Label Definition
Jump to Label
0< i <16
Subroutine Call
RET
MCR MCS
Return
Master Control
Relay
Not Reversible No Operation
A.2 Tool bar and instruction bar menu options
In the following tables, the Keys refer to the keystrokes necessary to step through the menus. The Quick Keys are used to shortcut the menu to activate the desired function.
G
A/1
G
A.2-1 Configuration Editor menu options
Button
None
Description
Application Name
Timers
Counters
Constants
LIFO/FIFO Registers
Drum Controllers
Fast Counter
%PLS/%PWM
Input Filter
Latch Input
Run/Stop
PLC Status (Security)
Scan Mode
Terminal port
Extension Port
Schedule Block
Change PLC Version
Validate Configuration
Cancel Configuration
Alt + C, I
Alt + C, A
Alt + C, U
Alt + C, L
Alt + C, D
Alt + C, I
Alt + C, X
Keys
Alt + C, N
Alt + C, T
Alt + C, C
Alt + C, O
Alt + C, R
Alt + C, D
Alt + C, F
Alt + C, P
Alt + C, S
Alt + C, H
Alt + T, L
Alt + T, C
None
None
None
None
None
None
None
None
None
None
None
Quick Keys
None
None
None
None
None
None
None
None
A/2
Appendices
Help
A.2-2 Symbols Editor tools menu options
Button Description
Insert
Delete
Sort by Address
Sort by Symbol
Find
A.2-3 Ladder Editor instruction bar options
Button Description
None
Keys
Keys
Alt + T, I
Alt + T, D
Alt + T, A
Alt + T, S
Alt + E, F
Help text window
Contact
Negated Contact
Rising Edge Contact
Falling Edge Contact
Horizontal Connector
Down Connector
Erase Down Connector
Horizontal Connector fill
Compare Block
Coil
Negated Coil
F 1
F 2
F 3
F 4
F 5
F 6
F 7
F 8
F 9
F10
Shift + F2
Shift + F3
F1
Quick keys
Insert key
Delete key
None
None
Ctrl + F
Quick keys
None
None
B.3.1-5
B.2.1-4
B.2.1-4
None
B.2.1-3
B.2.1-3
B.2.1-3
B.2.1-3
None
None
A/3
G
A.2-3 Ladder Editor instruction bar options (continued)
Button Description
Reset Coil
Set Coil
Jump or Subroutine Call
Operate Block
Timer function block
Counter function block
Extended Ladder Palette
Keys
Shift + F4
Shift + F5
Shift + F6
Shift + F7
Shift + F8
Shift + F9
Shift + F10
G
A.2-3.1Extended Ladder Palette options
Button
XOR
XORN
XORR
XORF
OPEN
SHORT
%Ri
%SBRi
%DRi
%SCi
%FC
%PLS
Description
Exclusive OR
Exclusive OR negation
Exclusive OR rising edge
Exclusive OR falling edge
Open contact
Short contact
LIFO/FIFO register function block
Shift bit register function block
Drum controller function block
Step counter function block
Fast counter function block
Pulse generator function block
Keys
Alt + X
Alt + O
Alt + R
Alt + F
Alt + P
Alt + H
Alt + G
Alt + B
Alt + U
Alt + N
Alt + A
Alt + L
Reference
B.2.1-7
B.2.1-7
B.2.1-7
B.2.1-7
None
None
B.2.2-5
B.3.4-7
B.2.2-6
B.3.4-8
B.3.4-5
B.3.4-4
Reference
B.2.1-4
B.2.1-4
B.2.4-3, B.2.4-4
B.3.1-3 - .1-9
B.2.2-3
B.2.2-4
None
A/4
Appendices
A.2-3.1
Button
%PWM
%MSG
RET
END
MCS
MCR
-( # )-
-( #i )-
-( #D )-
Extended Ladder Palette options (continued)
Description
Pulse width modulation
Message block
Keys
Alt + W
Alt + K
Return to program from subroutine Alt + T
Unconditional end of a program Alt + E
Master control start Alt + S
Master control relay
Deactivate current step without activating any other step
Activate step i after deactivating current step
Alt + M
None
None
Deactivate step i and the current step None
A.2-4 Ladder Editor Tools menu options
Button
None
Description
Validate Program
Validate Rung
Cancel Rung
New Rung
Clear Rung
Previous Rung
Next Rung
Toggle Grid
Keys
Alt + T, V
Alt + T, R
Alt + T, C
Alt + T, N
Alt + T, L
Alt + T, P
Alt + T, X
Alt + T, G
Reference
B.3.4-3
B.3.4-6
B.2.4-4
B.2.4-1
B.2.4-5
B.2.4-5
B.2.3-1
B.2.3-1
B.2.3-1
Quick Keys
None
Ctrl + Enter
None
Ctrl + A
None
Ctrl + Up
Ctrl + Down
None
A/5
G
A.2-5 Ladder Viewer Tools menu options
Button
None
None
Description
Validate Program
Insert Rung
Insert List
Edit Current Rung
Delete Current Rung
Show Symbols
Show Addresses
1 Line Address or Symbol
3 Lines Address or Symbol
3 Lines Address and Symbol
Toggle Rung Header
Toggle Grid
Toggle Ladder/List
Show All As Ladder
G
Table of Grafcet steps
A.2-6 List Editor instruction bar options
Button Description
Help
Load
Store
A/6
Keys
F1
F2
F3
Keys
Alt + T, V
Alt + T, R
Alt + T, L
Alt + T, E
Alt + T, D
Alt + T, S
Alt + T, A
Alt + T, 1
Alt + T, 3
Alt + T, N
Alt + T, H
Alt + T, G
Alt + T, T
Alt + T, W
Alt + T, F
Ctrl + D
Ctrl + F2
Ctrl + F3
None
None
None
Ctrl + H
None
None
None
None
Quick Keys
None
Ins
Ctrl + Ins
Ctrl + E
Reference
None
B.2.1-3
B.2.1-4
Appendices
A.2-6 List Editor instruction bar options (continued)
Button Description
AND
OR
Exclusive OR
Enable input / instruction
Memory push
Begin function block
Call or declare subroutine
Jump
Input bit of module 0
Output bit of module 0
Memory bit
System bit
Timer variable
Memory read
Wires block outputs
Return from a subroutine
Label
Input word
Output word
Shift + F3
Shift + F4
Shift + F5
Shift + F7
Shift + F8
Shift + F9
Shift + F10
Alt + F1
Alt + F2
Alt + F3
F7
F8
F9
F5
F6
Keys
F4
F10
Shift + F1
Shift + F2
Reference
B.2.1-5
B.2.1-6
B.2.1-7
B.2.2-3
B.2.1-10
B.2.2-2
B.2.4-4
B.2.4-3
B.3.1-1
B.3.1-1
B.2.1-10
B.2.2-2
B.2.4-4
B.2.4-3
B.3.1-2
B.3.1-2
B.3.1-2
B.3.1-2
G
A/7
G
A.2-6 List Editor instruction bar options (continued)
Button Description
Memory word
System word
Constant word
Counter
Move top of stack to accumulator
End of function block
Keys
Alt + F4
Alt + F5
Alt + F6
Alt + F7
Alt + F8
Alt + F9
Alt + F10 End of program
A.2-7 Data Editor Tools menu options
Button
None
Description
Validate Program
Insert
Delete
Add Previous Instance
Add Next Instance
Force 1
Force 0
Clear Force
Clear All Force
Read Retained Values
Keys
Alt + T, V
Alt + T, I
Alt + T, D
Alt + T, P
Alt + T, N
Alt + T, 1
Alt + T, 0
Alt + T, C
Alt + T, L
Alt + T, R
None
None
None
None
Quick Keys
None
Ins
Del
Ctrl + Up
Ctrl + Down
None
Reference
B.3.1-1
B.3.1-1
B.3.1-1
B.2.2-4
B.2.1-10
B.2.2-2
B.2.4-1
A/8
Appendices
A.2-7 Data Editor Tools menu options (continued)
Button
None
None
None
Description
Write Retained Values
Write Data Value
Open Data Page
Save Data Page
Save Data Page As
Help
Toggle Number Format
Toggle Animation
Keys
Alt + T, W
Alt + T, T
Alt + T, O
Alt + T, S
Alt + T, A
None
None
None
A.2-8 Edit menu options
Edit menu options
Undo
Cut
Copy
Paste
Find
Replace
Keys
Alt + E, U
Alt + E, C
Alt + E, O
Alt + E, P
Alt + E, F
Alt + E, R
Quick Keys
None
None
None
None
None
None
None
None
Quick keys
Ctrl + Z
Ctrl + X
Ctrl + C
Ctrl + V
Ctrl + F
Ctrl + R
G
A/9
A.3 PL7-07 PC programming software variables
Variable Type Description Read/Write/Force
Counters (%C0-%C15)
%Ci.PPreset value R,W (2)
%Ci.VCurrent value R,W
%Ci.EUnderflow output (empty) R
%Ci.D Preset output reached R
%Ci.FOverflow output (full) R
Drum Controllers (%DR0-%DR3)
%DRi.S Current step number R
%DRi.F Full (last step reached) R
Fast Counter %FC
%FC.P Preset value R,W (2)
%FC.V Current value R,W
%FC.S0 Threshold value S0 R,W
%FC.S1 Threshold value S1 R,W
%FC.TH0 Threshold bit 0 R
%FC.TH1 Threshold bit 1 R
G
%FC.F Overflow output R
Grafcet Step Bits(%X1-%X62) R
Input Bits (%I0.0-%I0.13 and %I1.0-%I1.13) R,F (3)
Input Words (%IWj.0-%IWj.1 where j=0,1,2,3,4) R,W
A/10
Appendices
A.3 PL7-07 PC programming software variables (continued)
Variable Type Description Read/Write/Force
Constant Words (%KW0-%KW63) R
LIFO/FIFO Registers (%R0-%R3)
%Ri.O Output word R
%Ri.I I Input word R,W
%Ri.ERegister empty R
%Ri.FRegister full R
Memory Bits (%M0-%M127) R,W
Memory Words (%MW0-%MW255) R,W
Message (%MSG)
%MSG.E Communication error output R
%MSG.D Communication done output R
Pulse Generator (%PLS)
%PLS.P Preset value R,W (2)
%PLS.N Number of pulses R,W
%PLS.Q Current pulse generation output R
%PLS.D Pulse generation done output R
Pulse Width Modulation (%PWM)
%PWM.P Preset period R,W
%PWM.R Ratio of the period R,W
Output Bits (%Q0.0-%Q0.9 and %Q1.0-%Q1.9) R,W,F (3)
A/11
G
G
A.3 PL7-07 PC programming software variables (continued)
Variable Type Description Read/Write/Force
Output Words (%QWj.0-%QWj.1 where j=o,1,2,3,4) R,W
System Bits (%S0-%S127) R,W (1)
Shift Bit Register(%SBRi.0-%SBRi.15, where i=0-7) R
Step Counter (%SCi.0-%SCi.255, where i=0-7) R
System Words (%SW0-%SW127) R,W (1)
Timers (%TM0-%TM31)
%TMi.V Current value R
%TMi.P Preset value R,W (2)
%TMi.Q Timer done R
(1) Certain bits and system words cannot be written. No specific messages warn the user in the List/Ladder editor. The Write on these bits or words has no effect in the
PLC.
(2) These variables can be written if the Adjust Option is selected in the configuration.
If the Adjust Option is not selected, the Write access in the Data editor will display a message, "PLC operation not available".
(3) Forcing the Run/Stop input or PLC status (security) output is authorized by the programming tools, the input or output is signaled as being forced but the PLC does not take the forcing into account.
Note: For all the variables that are not allowed to Write, a message warns the user in the
Data editor.
A/12
Appendices
A.4 Security features
The security features for the PL7-07 PC programming software includes password protection to prevent unauthorized changes to an application and the ability to change security levels. When you define a password, you restrict access to an application by creating the following two levels of security:
• Supervisor Level—allows you to modify any part of the application.
• Operator Level—allows you to modify symbols and data pages, but does not allow you to modify the application program and configuration data. An application that is password-protected defaults to the operator level each time it is opened.
A.4-1 Entering a password for the first time
1. Open the application to be password protected.
2. Select Security from the File menu. Select Change Password from the Security sub-menu. The Change Password dialog box appears.
3. Do not enter any information in the Enter Old Password field. Tab to the Enter New
Password field and type a password from 1 to 8 characters.
4. In the Confirm New Password field, re-type the same password.
5. Select Ok to use the new password. The application title bar displays the words,
"Supervisor Level".
Select Cancel to close the dialog box without defining the password.
6. The application must be saved for the new password to take effect.
A.4-2 Changing a password
1. Select Security from the File menu. Select Change Password from the Security sub-menu. The Change Password dialog box appears.
2. In the Enter Old Password field, enter the old password. Tab to the Enter New
Password field and type a new password from 1 to 8 characters.
3. In the Confirm New Password field, re-type the same password.
4. Select Ok to use the new password. Select Cancel to close the dialog box without changing the password.
5. The application must be saved for the new password to take effect.
A/13
G
G
A/14
A.4-3 Changing from operator level to supervisor level
1. Select Security from the File menu. Select Supervisor Level from the Security submenu. The Security dialog box appears.
2. Type the password. Select Ok to change to the supervisor level. Select Cancel to return to the operator level.
A.4-4 Removing a password
1. To remove a password, select Security from the File menu. Select Change
Password from the Security sub-menu.
2. At the Change Password dialog box, type in the current password in the Enter Old
Password field.
3. Tab through the Enter New Password and Confirm New Password fields without entering any information.
4. Select Ok to remove the password. Select Cancel to return to the application with the password still in effect.
A.4-5 Password protection for files transferred to an FTX 117 terminal
The FTX 117 terminal only has keys for entering the alphanumeric characters 0 through
9 and A through F. If a file is transferred from a PC to the FTX 117 terminal with a password that has characters other than 0 through 9 and A through F, then the password will not be able to be entered. Changes to the file will not be possible from the FTX terminal.
Appendices
A.5 Instruction scan time and memory usage
Times is expressed in
µ s.
Size is expressed in bytes.
Boolean instructions
I nstructions With bit operands
%I,%Q %M, %S, %X, 0/1, %MWi:Xi... (1)
Time Size Time Size
LD, LDN 0.2 2 0.4 4
LDR, LDF 0.5 4 - -
AND, ANDN 0.2 2 0.6 4
ANDR,ANDF 0.8 4 - -
AND(, AND(N 6.3 8 7 10
AND(R,AND(F 7 10 - -
OR, ORN 0.4 2 0.7 4
ORR, ORF 0.8 4 - -
OR(, OR(N 6.3 8 6.6 10
OR(R, OR(F 6.7 10 - -
XOR,XORN 0.2 2 0.6 4
XORR,XORF 0.8 4 - -
ST, STN (2) 0.2 (0.8) 2 0.9 (1.5) 4
S,R (2) 0.8 (1.2) 4 1.5 (1.8) 6
N 0.6 4
) 15 8
MPS 0.6 4
MRD 0.2 2
MPP 0.2 2
These times must be multiplied by 3 when the instructions are written after program line
099.
(1) For word extract bits %MW16 to %MW255 and for all other types (%KWi:Xj,%SWi:Xj) these times are multiplied by 1.5 and the sizes are increased by 2 bytes.
(2) The times given in parentheses are the scan times for the instructions when the application has been initialized to use MCS/MCR instructions.
Summary : the choice of whether to use master relay instructions or not is made when the application memory is cleared (see Part C, Section 4.6 of the FTX 117 manual, or Part C, Section 5.21 of the PL7-07 manual).
G
A/15
Instructions on function blocks (in reversible programming)
Instruction Scan time (in
µµµµµ s) Memory usage (in bytes)
BLK %TMi 8 4
BLK %Ci 8 4
BLK %Ri 8 4
BLK %SBRi 8 4
BLK %SCi 8 4
BLK %DRi
BLK %FC 8 4
BLK %MSG 8 4
BLK %PMW 8 4
BLK %PLS 8 4
OUT_BLK 200 2
END_BLK 180 2
IN 1.2 4
R 0.6 4
CU 0. 7 4
I
CD 0.7 4
1 4
O 1 4
U
S 0.7 4
G
Instructions on function blocks (in non-reversible programming)
Instruction Scan time (in
µµµµµ s) Memory usage (in bytes)
IN %TMi 48 4
CD %Ci (CU %Ci) 46 4
S %Ci 49 4
R %Ci 47 4
U %DRi
R %DRi
LD %SCi.j 9 6
CD %SCi (CU %SCi) 38 4
ST %SCi.j 10 6
R %SCi 36 4
BLK %PMW 42 4
BLK %PLS 53 4
CD %SBRi (CU %SBRi) 39 4
R %SBRi 37 4
I %Ri (O %Ri) 49 4
R %Ri 48 4
IN %PWM 36 4
IN %PLS 46 4
S %PLS 42 4
R %PLS 58 4
IN %FC 43 4
S %FC 69 4
READ 9.8 6
EXCH 160 - 700 8
R %MSG 25 4
A/16
Appendices
Numerical instructions
Instruction Scan time (in
µµµµµ s) Memory usage (in bytes)
:= 29.5 10
+ 34 12
/
-
*
38
49
48
12
12
12
REM 49 12
INC 28 6
DEC 28 6
AND 37 12
O R 37 12
XOR 37 12
NOT 29 8
SHL 34 10
SHR 34 10
ROL 35 10
ROR 35 10
BTI 40 8
ITB 40 8
SQRT 80 8
Comparison instructions
Instruction Scan time (in
µµµµµ s) Memory usage (in bytes)
LD[word1 comp word2] 18 8
AND[word1 comp word2]19 10
AND([word1 comp word2] 24 14
OR[word1 comp word2] 21 10
OR([word1 comp word2] 25 14 comp : comparison operations =>,<=,<>,=,>=,>
Grafcet instructions
Instruction Scan time (in
µµµµµ s) Memory usage (in bytes)
=*= i 4
# 4
#i 4
#Di 6
=*=POST 4
-*- i 6
G
A/17
G
A/18
Instructions on programs
Instruction Scan time ( µµµµµ s) Memory usage (in bytes)
END 0.4 2
ENDC, ENDCN 0.6 4
SR 14 4
RET 2 6
NOP 0.4 2
JMP 7.8 4
JMPC, JMPCN 8 6
%Ln : 0.6 4
%SRn : 2 4
MCR 0.5 2
MCS 2.5 12
Appendices
A.6 Importing and Exporting ASCII program files and symbols files
The PL7-07 PC programming software allows you to import and export ASCII program files and symbols files.
A.6-1 ASCII program files
List programs can be developed by external ASCII text editors. ASCII format program import and export allows you to transfer these files between the PL7-07 software and the ASCII text editor.
To import an ASCII program file:
1. With a new or existing application open, select Import from the File menu. Select
ASCII Program from the Import sub-menu. The File Selection dialog box appears.
2. In the Drives field, select the drive where the text file is located.
3. In the Directories field, select the directory containing the text file to be imported.
4. In the List Files of Type field, select either Text (*.txt) or All (*.*) to display the files in the selected directory.
5. In the Filename field, select the file name of the text file to be imported.
6. Select Ok to import the file. Select Cancel to close the dialog box without importing the file.
To export an ASCII program file:
1. With an application open, select Export from the File menu. Select ASCII Program from the Export sub-menu. The File Selection dialog box is displayed.
2. In the List Files of Type field, select either Text (*.txt) or All (*.*). The .txt file extension identifies text editor files.
3. In the Drives field, select the drive where you want to store the file.
4. In the Directories field, select the directory where you want to save the file.
5. In the Filename field, over type the asterisk (*) with a standard DOS file name.
If the file name does not comply with DOS file naming conventions, an "Invalid
Filename" message is displayed.
G
A/19
If you type a file name that already exists in the selected directory, an error message appears: "The file selected already exists. Overwrite?" Select Ok or Cancel.
6. Select Ok to export the file. Select Cancel to close the dialog box without exporting the file.
A.6-2 Symbols files
Symbols files can be created for common applications. Symbols import and export allows you to transfer the symbols files between applications.
To import a symbols file:
1. With a new or existing application open, select Import from the File menu. Select
Symbols from the Import sub-menu. The File Selection dialog box appears.
G
2. In the Drives field, select the drive where the symbols file is located.
3. In the Directories field, select the directory containing the symbols file to be imported.
4. In the List Files of Type field, select either Symbol (*.sym) or All (*.*) to display the files in the selected directory.
5. In the Filename field, select the file name of the symbols file to be imported.
6. Select Ok to import the file. Select Cancel to close the dialog box without importing the file.
7. If Ok is selected in step 6, a message appears in the status bar.
A/20
Appendices
To export a symbols file:
1. With an application open, select Export from the File menu. Select Symbols from the Export sub-menu. The File Selection dialog box appears.
2. In the List Files of Type field, select either Symbol (*.sym) or All (*.*). The .sym file extension identifies symbols files.
3. In the Drives field, select the drive where you want to store the file.
4. In the Directories field, select the directory where you want to save the file.
5. In the Filename field, over type the asterisk (*) with a standard DOS file name.
If the file name does not comply with DOS file naming conventions, an "Invalid
Filename" message appears.
If you type a file name that already exists in the selected directory, an error message appears: "The file selected already exists. Overwrite?" Select Ok or Cancel.
6. Select Ok to export the file. Select Cancel to close the dialog box without exporting the file.
7. If Ok is selected in step 6, a message appears in the status bar.
A/21
G
A.7 Transferring applications between a PC and the FTX 117 terminal
A.7-1 Application files
An application can be transferred from a PC to a FTX 117 terminal by the following ways:
• transfer the program from the PC to the Nano-PLC and then transfer from the PLC to the FTX 117 terminal.
• save the program in the PC to a binary file (.app extension), and transfer the file to the FTX 117 terminal via a PC memory card (T FTX REM 3216, T FTX RSM 3216, OR
T FTX RSM 12816). The memory card must be formatted on the FTX 117 terminal.
Note : When a program is saved and transferred to the FTX 117 terminal (as a binary file), symbols and comments are not saved or transferred.
Section 12, Transferring an application, details how to transfer from the PC to the PLC.
The TSX 07 Nano PLC FTX 117 Terminal manual details how to transfer from the PLC to the FTX 117 terminal.
To transfer an application from a PC to a FTX terminal via a memory card requires the application to be saved as a binary file (.app extension). When the application is saved as a binary file, the symbols and comments are not saved. Therefore, if the application is later transferred back to the PC, the symbols and comments will not appear.
Additionally, the word "DEFAULT" replaces the file name in the title bar. To re-name the file, select Save As from the File menu and save the file with the desired file name.
For more information on Save As, see Section11.3.
To transfer an application from the PC to the FTX 117 terminal via a FTX 117 formattted memory card:
1. With the application open, select Save As from the File menu. A File Selection dialog box appears.
G
2. In the List Files of Type field, open the selection box and select the Binary (*.app) file type.
3. In the Drives field, select the memory card drive.
A/22
Appendices
4. In the Directories field, select the directory where you want to save the file.
5. In the Filename field, over type the asterisk (*) with a standard DOS file name.
If the file name does not comply with DOS file naming conventions, an "Invalid
Filename" message is displayed.
If you type a file name that already exists in the selected directory, an error message appears: "The file selected already exists. Overwrite?" Select Ok or Cancel.
6. Select Ok to save the binary file. Select Cancel to close the dialog box without saving the file.
To transfer an application from the FTX 117 terminal to the PC via a memory card:
1. Select Open from the File menu. A File Selection dialog box appears.
2. In the List Files of Type field, open the selection box and select the Binary (*app) file type.
3. In the Drives field, select the memory card drive.
4. In the Directories field, select the directory that contains the file to be transferred.
5. In the Filename field, select the file to be opened.
6. Select Ok to open the binary file. Select Cancel to exit the dialog box without opening the file.
The application transferred is now available on the PL7-07 software screen.
A.7-2 Data page files
Data page files (.dat extension) in the PC have the same file format as data table files in the FTX 117 terminal. However, a data table in the FTX 117 terminal contains 16 data objects whereas a data page contains 64 data objects. The PL7-07 PC programming software data page can hold up to 4 FTX 117 data pages.
A data page file is transferred to the FTX 117 terminal via a FTX 117 formatted memory card. Use Save Data Page As (Section14.4-16) and save the file to a memory card.
G
A/23
A.8 Troubleshooting installation problems
A.8-1 Installing PL7-07 PC programming software on a 5.25" drive
PL7-07 PC programming software is shipped on 3.5" diskettes. You can install the software on a computer with a 5.25" disk drive, if you have another IBM-compatible computer with both a 3.5" and 5.25" disk drive. You also need three to six formatted 5.25" diskettes, depending on the language selected.
1. On the computer with both the 3.5" and 5.25" disk drive, install installation Disk #1 in the 3.5" floppy disk drive.
2. With the DOS prompt at c:, select the drive letter for the 3.5" floppy drive, this is typically a:.
3. At the a: prompt, type install and press <enter>.
4. Select the language for installing the program. The PL7-07 PC programming software can be installed in one of five languages—English, French, German,
Italian, and Spanish.
The PL7-07 PC programming software can operate in only one language at a time.
If support for multiple languages is required, create a new directory with a different name and re-install the software in the new directory. If you re-install the software in the same directory as the original installation, the newly-installed version will overwrite the old one.
5. Select the disk drive where the program is to be installed.
6. Enter the disk destination subdirectory. The default subdirectory is \PL707.
7. Select the COM port to be used by the computer for communicating with the PLC.
G
8. The program files are automatically decompressed and written to the subdirectory specified.
9. When prompted by the installation program, insert installation Disk #2.
10. The installation program prompts you with the following:
May I create/modify your AUTOEXEC.BAT file if needed (Y/N)? Select No.
May I create/modify your CONFIG.SYS file if needed (Y/N)? Select No.
11. When prompted by the installation program, re-insert installation Disk #1.
12. After the installation is finished, the following information is displayed:
Make sure the changes were made to CONFIG.SYS:
FILES=30 (or higher)
DEVICE=C:\PL707\DUNTLW.EXE PROFILE=C:\PL707\DUNTLW.001
A/24
Appendices and AUTOEXEC.BAT:
PATH=....;C:\PL707
Record this information. This information will be used to update the CONFIG.SYS
and AUTOEXEC.BAT files in the destination computer with the 5.25" disk drive.
COM1 is the default communications port. To change the COM port setting, edit
DUNTLW.001 in directory C:\PL707. In the Basic Parameters section, change the
COM setting in the line PORT=COM1:0,8,1 to the desired COM port.
13. Remove the 3.5" installation diskette and insert a blank formatted 5.25" diskette in the appropriate drive.
14. Type cd\ to return to the root directory.
15. To transfer the installed software to the 5.25" diskettes, type backup C:\PL707 b:/
s and press <enter>.
Backup is a DOS command. For more information about this command, refer to your
DOS instruction manual.
16. You are prompted for additional diskettes, as needed. Label or keep the diskettes in the order in which they are backed up.
17. After the backup is complete, take the diskettes to the destination computer and insert the first diskette in the 5.25" disk drive.
18. From the c:\ prompt, type restore a: c:\ /s. Follow the instructions displayed until all information is restored. This assumes that a is the drive designation for the 5.25" disk drive.
19. Add the information recorded in step 12 to the CONFIG.SYS and AUTOEXEC.BAT
files.
20. Reboot the computer.
A.8-2 Software installation problems
If you encounter a problem during or after installing the PL7-07 PC programming software, check the following conditions.
1. Check that these PL7-07 PC programming software files are installed:
DIALOG.ZNC ERRORS.MDX PRINTERS.DBF
DUNTLW 001 HELP.ZNC PRINTERS.DBT
DUNTLW.386 PAGES.DBF PRINTERS.MDX
DUNTLW.EXE PAGES.MDX RESWORD.TBL
ERRORS.DBF PL707.EXE PL707.ICO
ERRORS.DBT PL707.INI
2. Do not install the PL7-07 PC programming software deep in the DOS directory tree structure, such as 10 levels down from the root directory.
3. If you encounter either memory or communications errors while running the PL7-
07 software, you may need to reconfigure your memory manager or add lines to your
CONFIG.SYS file. Use the following guidelines for reconfiguring EMM386.EXE,
QEMM, and 386MAX.
A/25
G
A.8-2.1 EMM386.EXE
EMM386.EXE is part of MS-DOS, versions 5.0 and later. EMM386.EXE supports VCPI, but does not support DPMI.
You do not need to have EMM386.EXE installed. However, if you encounter
EMM386.EXE error messages when running PL7-07 software and EMM386.EXE is installed, add the following line to your CONFIG.SYS file:
DEVICE=EMM386.EXE FRAME=NONE
The FRAME=NONE option leaves the EMS and VCPI interfaces active, but prevents
EMM386.EXE from allocating any page frames.
Regardless of the version you are using, you must be careful when selecting EMM386 configuration options. Some options conflict with one another and choosing them can cause EMM386.EXE to conflict with Phar Lap's 286 | DOS-Extender.
One set of conflicting options is the NOEMS/FRAME=xxxx/RAM/Mx group. Each of these EMM386.EXE switches affects the creation of an EMS page frame. Do not use the options together, but rather, select only one option. Specifying FRAME=NONE is satisfactory for most users.
A.8-2.2 QEMM
QEMM, by Quarterdeck Office systems, supports VCPI, but does not support DPMI. We suggest that you add the following line to your CONFIG.SYS file:
DEVICE=QEMM.SYS FRAME=NONE
The FRAME=NONE option leaves the EMS and VCPI interfaces active, but prevents
QEMM from allocating any page frames.
Do not specify the QEMM configuration option NOEMS, if you want to run Phar Lap's
286 | DOS-Extender. This option disables the VCPI interface, so that Phar Lap's 286
| DOS-Extender cannot communicate, resulting in the following error message:
Fatal Error 286.1020: This program requires VCPI or DPMI in V86 mode.
G
A.8-2.3 386MAX
386MAX, by Qualitas, supports both VCPI and DPMI. If you encounter an error message, we suggest you add the following line to your CONFIG.SYS file:
DEVICE=C:\386MAX\386MAX.SYS PROFILE=C:\386MAX\386MAX.PRO
where 386MAX.PRO is a profile file.
You can use either the NOFRAME or EMS=0 option without significantly affecting the performance of Phar Lap's 286 | DOS-Extender. The NOFRAME option keeps the EMS and VCPI interfaces active, but prevents 386MAX from allocating a 64 KB page frame for EMS. The EMS=0 option also keeps the EMS and VCPI interfaces active, while making all remaining memory available as extended (XMS) memory.
A/26
Appendices
A.8-3 COM port problems during installation
In order for the PL7-07 PC programming software in your PC to communicate with the
PLC, you must have serial communications capability between the PC and the PLC.
When the PL7-07 PC programming software (DOS or Windows 3.1/95/98) or the XWAY communication tool (Windows NT) is first installed on your computer, the software checks to see which serial COM ports (COM1 - COM4) are available. During the installation, a listing of the available COM ports is displayed and you are asked to select the desired COM port. If the word "None" is the only thing displayed, then no serial COM ports are available. The following are the likely problems and the suggested actions to take :
• There is no serial communications card in your computer. You need to install a serial communications card and assign a COM port designation.
or
• All of the existing COM parts are being used. The following choices are recommended :
• disable a device assigned to the COM port you would like to use for the PLC and assign the PLC the COM port.
If installing PL7-07 under DOS or Windows 3.1/95/98, in the Basic Parameters section of the DUNTLW.001 file, ensure PORT=COM?:O,8,1 is set to the desired
COM port, where ? is the COM port number.
If installing PL7-07 under Windows NT, install the UNI-TELWAY driver.
• share the COM port with another device. However, the PLC and the other device cannot be operated at the same time. For example, if you share a COM port with a modem, the PLC cannot be connected to the PC when the modem is being used.
If installing PL7-07 under DOS or Windows 3.1/95/98, in the Advance Parameters section of the DUNTLW.001 file, ensure COMSHARE=YES.
If installing PL7-07 under Windows NT, the system sets this parameter automatically.
• install another serial communications card and assign a COM port designation.
A.8-4 Communication error when connecting the PC to the PLC
If a communication error is detected when you attempt to connect the PC to the PLC, an Error dialog box appears. Select Ok to acknowledge the Error dialog box.
G
A/27
1. Check to ensure the cable is properly connected between the PC and the PLC and that power is available to the PLC.
2. In the CONFIG.SYS file, ensure the following line is present:
DEVICE=C:\PL707\DUNTLW.EXE PROFILE=C:\PL707\DUNTLW.001
3. In the CONFIG.SYS file, ensure FILES=30 (or higher)
4. Ensure there is no IRQ (interrupt) conflict between the PLC and any other device.
5. In the DUNTLW.001 file located in the c:\PL707 directory, ensure the proper port is designated in the line PORT=COM?:O,8,1, where ? is the COM port number.
6. If your computer uses EMM386, it may be necessary to add REM at the beginning of the line in the CONFIG.SYS file that designates EMM386 as a device. The REM prevents the line from being read.
A.8-5 Video Display problems
(Software version V1.0 only)
If you are experiencing video display problems such that the characters in the dialog boxes or the List Editor seem to be scrambled, it may be because your PC is using a different font than the standard IBM character font. You may have to adjust your
CONFIG.SYS and AUTOEXEC.BAT files to use what is referred to by some PC manufacturers as the "Material Font" in order to fix the problem. This is accomplished by changing to the DOS code page.
For instance, changing the code page for DOS 6.2 in some PCs would be something like the following example.
Using a text editor, edit the CONFIG.SYS file to include this statement :
G
DEVICE = C:\DOS\DISPLAY.SYS CON: = (EGA,437,1)
Again using a text editor, edit the AUTOEXEC.BAT file to include the following statements :
C:\DOS\NLSFUNC
MODE CON CP PREPARE = ((850) C:\DOS\EGA.CPI)
CHCP 850
For more information on changing the code page, consult the DOS documentation that came with your PC.
A/28
A.9 Running PL7-07 in Windows
PL7-07 PC Programming Software for the TSX Nano runs in DOS, and therefore can be run under Windows within the same constraints as other graphical DOS applications. Following the suggestions listed below should allow successful operation under
Windows.
A.9-1 Running PL7-07 under Windows 3.1
You should be running Windows 3.1 on a PC that has at least 4 Mb of memory.
Preferably, the PC should have 8 Mb of memory if other Windows applications, drivers, and the like are open simultaneously. Further, faster CPUs and video cards in the PC will only enhance performance of PL7-07.
A PIF file should be created for PL7-07 using Windows 3.1's PIF File Editor. The PIF file tells Windows what kind of application PL7-07 is, and determines the PC resources that Windows 3.1 will give to PL7-07. You can then "run" the PIF file while in Windows
3.1 which in turn will set up Windows for PL7-07, and then automatically run PL7-07.
For more information, see the Windows 3.1 documentation on creating and editing PIF files.
The following parameters should be used when creating a PIF File for PL7-07:
The Program Filename must include the DOS directory path to PL707.EXE. The path in the above example is the default path created at installation time for PL707. If you didnot choose to accept the default directory during installation of PL7-07, then enter the directory path you had provided . The same directory should be used as the Start up directory.
G
A/29
Video memory should be set to text. PL7-07 will configure the video for you. Enter -
1 for the Memory Requirements. This will indicate to Windows 3.1 that PL7-07 should be given all the conventional PC memory possible. PL7-07 only makes use of Extended
Memory. Therefore, set EMS Memory Required and Desired to zero, and set XMS
Memory Required to at least 2Mb. Set XMS Memory Desired to 4Mb if running on a
PC with at least 8Mb of RAM memory; otherwise set it to 2Mb.
Set the Display Usage to Full Screen. PL7-07 is a graphical environment under DOS, and Windows requires that it be run as a full screen, as opposed to a window. If you do not set this parameter in the PIF file to full screen, Windows 3.1 will provide an error message and suspend the running of PL7-07 until the window is turned into a full screen. This can be accomplished by pressing <alt><enter> together (holding done the Alt key and pressing the Enter key).
It should be noted that some VGA or SVGA video cards, especially older models, do not restore the full screen window properly after having either been minimized or turned into a window. Please be sure that you are using the latest video driver for your video card, available from the manufacturer of the video card. On some models, if the screen is restored improperly, selecting a PL7-07 menu item can sometimes clean up the display, but this is not always the case.
Leave the Execution parameters Background and Exclusive un-checked. It is also advisable to set the Close Window on Close Window checkbox. In this way, the termination of PL7-07 will automatically close the full screen window and return you to Windows 3.1's Program Manager.
Select the Advanced button to obtain the PIF file Advanced Options dialog box. The only parameters that need to be changed are the Display Options. For the best video performance, only the Text checkbox should be set in the Display Options box.
Otherwise, the rest of the Advanced Options parameters can remain at their default values.
G
Installing the PL7-07 icon under Windows 3.1
Select or create the Modicon Telemecanique Group
To create a group:
1 In Program Manager, select the File/New command.
2 In the New dialog box, select Group of programs then confirm by clicking on OK.
3 Enter the name of the group then confirm again by clicking on OK.
Install the PL7-07 icon
1 In Program Manager, select the File/New command.
2 In the New dialog box, select Program then confirm by clicking on OK.
A/30
In the Program items properties dialog box:
3 Enter the name of the software "PL7-07".
4 Enter the command line C:\PL707\PL707.EXE (C being for example the disk drive where PL7-07 is installed).
5 Select Change icon.
The message "No icon available in the file" appears.
6 Confirm by clicking on OK.
In the Change icon dialog box:
7 Fill in the Name field by entering the command line C:\PL707\PL707.ICO (C being for example the disk drive where PL7-07 is installed) then confirm the various dialog boxes by clicking on OK.
A.9-2 Running PL7-07 under Windows 95/98/NT
The user does not need to set any particular parameters to run PL7-07 under Windows
95/98/NT.
Installing the PL7-07 icon under Windows 95/98/NT
Select or create the Modicon Telemecanique Group
To create a group :
1 In the Start menu, go to the C:\Windows\Start menu\Programs directory.
2 Select the File/New/Folder command.
3 Enter the name of the group then confirm again by clicking on OK.
Install the PL7-07 icon
From the Modicon Telemecanique directory
1 Select the File/New/Shortcut command.
2 Enter the full path for the PL707.EXE program and click on Next.
3 Select a name for the shortcut and click on Next.
4 Select an icon for the shortcut and confirm by clicking on Close.
G
A/31
G
A.10 Example of prepositioning Grafcet steps
In this example, no initial step (=*=) is programmed, the chart is initialized on the rising edge of input %I0.7 in preprocessing part of the program.
The example given in SectionB2.3-2 is repeated below.
Preprocessing
In the preprocessing part of the program (area prior to the first Grafcet step), state 0 of input %I0.7
prompts a reset of the
Grafcet chart (sets system bit %S22 to 1) which deactivates the active steps.
The rising edge of input
%I0.7 pre-positions the chart (activation of step X1 associated with resetting system bit %S23 to 1).
Sequential processing
No initial step is declared; since step 1 has been initialized by input I0.7 in preprocessing.
000 LDN %I0.7
001 S %S22
002 ST %M0
003 LDR %I0.7
004 S %X1
005 S %S23
Post-processing
(The Post-processing part of the program is the area following the =*= POST instruction).
006 -*- 1
007 LD %I0.2
008 ANDN %I0.3
009 # 2
010 LD %I0.3
011 ANDN %I0.2
012 # 3
013 -*- 2
014 LD %I0.4
015 # 1
016 -*- 3
017 LD %I0.5
018 # 1
019 =*= POST
020 LD %X1
021 ST %Q0.1
022 LD %X2
023 ST %Q0.2
024 LD %X3
025 OR( %M1
026 ANDN %I0.2
027 AND %I0.6
028 )
029 ST %Q0.3
A/32
A.11 Actions associated with steps
The actions associated with steps can be programmed in two ways :
• By List sentences or ladder rungs associated with the step. In this case the List sentence or ladder rung is not scanned unless the step is active.
• In the Post-processing module by using the step bit %Xi (see chapter B 2.3-2) scanned on each cycle. Therefore, it is preferable for the actions to be pro- grammed in the Post-processing module.
020 -*- 3
021 LD 1
022 S %Q0.5
023 LD %M10
024 # 4
025 -*- 4
026 LD 1
027 R %Q0.5
028 •••
029 •••
The actions can be saved to logic conditions and are entered in the form of latched instructions or coils (SET). Each SET instruction or coil must be reset to zero by a RESET coil.
A/33
G
A.12 Index
G
A
Address selector switch A 1/3, A 1/12
Addressing
Adjusting and debugging phase C 3/11
Analog I/O A 1/24, A 1/25, B3/16, B 4/1
Analog input
Presentation A 1/24, A 1/25, B 4/1
Animating a program C 8/2, C 14/1, C 14/3
.app files (binary files)
C 2/7, C 3/3, C 4/2, C 11/1, G A/22
Application files (.pl7)
Application name (entry of) C 5/3
Application protection C 12/3, C 13/2
ASCII communications(see communication)
Assigning symbols to data variablesC 14/6
AUTOEXEC.BAT file C 2/3, G A/24
Auto Line Validate C 8/1, C 8/2
B
Baud rate
BCD conversion (instruction) B 3/13
Binary files (.app)
memory G A/11 output A 1/13, G A/11
C
Cables and accessories A 3/13, F 1/4
CD
Clear force, clear all force C 14/7
Combinational and sequential
Comments
A/34
Communication (ASCII)
Communication (inter-PLC)
Communication (UNI-TELWAY)
Comparison (instruction) B 3/8
CONFIG.SYS file C 2/3, G A/26, G A/28
Configuration Editor C 3/8, C 5/1, G A/1
Configuration print settings C 15/3
Configuring PLC resources
from Configuration menu C 5/1 from Configuration Editor C 5/1
from Ladder Editor/Viewer C 5/2 from Symbol Editor C 5/2
Connections
analog inputs A 1/24, A 3/16, A 3/17
Connecting a PC to a PLC C 2/2, C 4/2
Connecting an FTX 417/FTX 507/FT 2000
Constants B 3/2, C 5/5, G A/11
Convert (see also reversibility) B 3/13, C 3/7
Creating new application files C 4/1
Cross referencing an applicationC 16/1, C 16/3
CU
D
D
Data Editor Tools menu options G A/8
Data files (.dat ) C 2/7, C 14/8, G A/23
Date and time (current) C 13/4
Date and time of last stop B 5/4, C 13/5
Debugging and adjustment C 3/11, C 14/1
Description
Developing an application C 3/10
Directories, PL7-07 C 2/3, C2/7
Display
read-only PLC system info C 13/4
Drum controllers B 2/22, C 5/7, G A/10
A/35
G
G
E
Executing PL7-07 software C 2/10
Exporting files (see Importing/Exporting files)
Exporting source program to PL7 Micro C 17/1
Extended Ladder Palette C 7/11, G A/4
F
Fast counter
Find
Forcing C 13/6, C 14/2, C 14/7
Frequency meter
Function blocks
programming B 2/11, B 2/12, C 7/6
G
Grafcet
presentation B 2/26, C 10/1, G A/10
Grid, programming C 7/3, C 7/4, C 7/15
H
I
Importing/Exporting files
ASCII program C 2/7, G A/19 symbol C 2/7, G A/19
IN
INC
B 3/9
Inputs
A/36
Inputs (24 VDC)
Inputs (115 VAC)
Insert
coil or jump/subroutine call C 7/7
graphic instruction C 7/4, C 7/12
rung title, label, or comments C 7/13
Installing PL7-07 software C 2/3 on 3.5" drive C 2/3
Instruction List language B 1/1
Instruction memory usage G A/15
Instructions (ladder, list) G A/1, G A/9
I/O extension
J
K
Keyboard, using the C 3/4, C 7/5
L
Tools menu C 7/14, G A/3, G A/6
Ladder Viewer
Languages, PL7-07 support for C 2/3
LIFO/FIFO B 2/21, C 5/6, G A/11
List Editor instruction bar G A/6
Logic operation on words B 3/11
M
MCS, MCR
Memory Display Mode (MD) A 1/20
Memory
PLC EEPROM
G
A/37
G
N
Nano-PLC extensions
O
Opening an existing application file C 4/1
Operands
Operate blocks
Operating states, PL7-07
monitor C 3/9 offline C 3/9 online C 3/9
Outputs
Outputs (relay)
Outputs (24 VDC, sink)
Outputs (24 VDC, source)
Overflow
P
Password protection C 12/3, G A/13
Paste
PC card
(memory card, PCMCIA) C 2/4, C 4/2
PCMCIA (see PC card)
Peer PLC
.pl7 files (application files)
PL7-07 PC software
using mouse/keyboard C 3/4, C 7/5
PL7 Micro
PLC communications, configuring
PLC resources, configuring C 3/8, C 5/1
PLC status (Security) A 4/1, C 5/17
PLS pulse generator C 5/13, G A/11
Post-processing (Grafcet) B 2/25
Potentiometers
A/38
Power supply (TSX 07) A 3/4, A 5/1
Pre-processing (Grafcet) B 2/27
Printing
Program
create C 7/1, C 8/1 modify C 7/1, C 8/1
Program animation C 14/1, C 14/3
Programmable input filters A 1/16, C 5/15
Protected outputs A 1/18, B 7/4
Protected transistor output A 1/19, B 6/4
PWM pulse generator
Q
Q (output)
R
R (reset)
Read-only system information C 13/4
Real time clock, setting the C 13/4
Reconfiguring memory managers G A/25
Reflex outputs A 4/3, B 3/22, C 5/10
Register (function blocks) B 2/20
Relay outputs
Replacing
comment strings C 7/23 operands C 7/23, C 8/8
Retained values, in data page C 14/8
Reversibility B 7/6, C 3/7, C 10/2
Rung header C 7/3, C 7/13, C 7/18
S
S (set)
Scan time
description A 1/9, G A/15, G A/18
Schedule Block (RTC) B 5/1, C 5/18
Security features
Security (PLC status) A 4/1, C 5/17
Selecting
A/39
G
G
toolbar items C 3/4 using mouse/keyboard C 3/4, C 7/5
Sequential processing (Grafcet) B 2/27
Shift (SHR, SHL, ROL, ROR) B 3/12
Software variables, PL7-07 G A10, G A12
Sorting symbols
by address C 6/3 by symbol C 6/3
Square wave generator (PLS) C 5/13
Starting/stopping the PLC
(see Stopping/starting the PLC)
Status bar C 3/1, C 3/10, C 7/3
Stopping/starting the PLC
by RUN/STOP input A 4/1, C 5/16
Symbol Editor C 3/8, C 6/1, G A/3
System words B 3/2, B 6/7, B 6/13, G A/12
T
TB (time base)
Threshold Outputs A 4/3, B 3/21, C 5/10
Time-of-day clock
date-stamping, meas. of durationB 5/3
setting date and time B 5/4, C 13/4
Titles, using with Print C 15/2
Transferring applications
TSX AMN 400 i
U
UNI-TELWAY communications C 2/5, F 1/1
Updating an existing
Up/down counter
Using the PL7-07 editors
A/40
List/Ladder C 3/7, C 7/1, C 7/ 8
Using mouse or keyboard C 3/4, C 7/5
V
Validate Program
Variables, PL7-07 G A/10, G A/12
Viewing validation errors C 10/2
W
Warnings (reversibility) C 10/2
Words (definition, list) B 3/1
X
%Ci
B 2/17, C 5/5
3 lines (symbols AND addresses)
3 lines (symbols OR addresses)
G
A/41
G
A/42