Schneider Electric Modicon Quantum Reference guide
विज्ञापन
विज्ञापन
Modicon Quantum
Automation Series
Hardware Reference Guide
840 USE 100 00 Version 11.0
ii
840 USE 100 00 11/2004
Document Set
At a Glance This manual consists of two volumes.
Volume 1 z z z z z z z z z z z z z z z z z
Quantum Automation System Overview
Quantum Configurations
Network Configurations
System Specifications for Quantum Modules
Hardware Specifications for Quantum Modules
Power Supply Modules
CPU Modules
Quantum Field Bus Modules
Distributed I/O (DIO) for Quantum Modules
Quantum Remote I/O Communication Modules
Quantum Modbus Plus Network Option Modules
Quantum Modbus Plus Networking on Fiber Module
Quantum Ethernet Modules
Intelligent/Special Purpose Modules for Quantum
Quantum Intrinsically Safe Analog/Digital, Input/Output Modules
Quantum Simulator Modules
Quantum Battery Module z z z z z z z z
Volume 2
Quantum I/O Modules
Miscellaneous Components
Spare Parts
Hardware Installation
Power and Grounding Guidelines
CableFast Cabling
Error Stopped Codes
Agency Approvals
840 USE 100 00 11/2004 iii
iv
840 USE 100 00 11/2004
Table of Contents
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xi
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xiii
Part I
Quantum Automation System Overview . . . . . . . . . . . . . 1
Chapter 1
Modicon Quantum Automation System Overview . . . . . . . . . . 3
Modicon Quantum Automation Series Overview. . . . . . . . . . . . . . . . . . . . . . . . . . 4
Quantum Communication Interface Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Quantum Intelligent/Special Purpose I/O Modules . . . . . . . . . . . . . . . . . . . . . . . 11
Quantum Battery, Backplanes, and CableFast Cabling . . . . . . . . . . . . . . . . . . . 13
Part II
Quantum System Configurations . . . . . . . . . . . . . . . . . . 15
Chapter 2
Quantum Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Quantum Local I/O, Remote I/O and Distributed I/O Configurations. . . . . . . . . . 18
Chapter 3
Network Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Quantum Network Interface Techniques. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Quantum Modbus and Modbus Plus Communications . . . . . . . . . . . . . . . . . . . . 37
Part III
Quantum System Specifications . . . . . . . . . . . . . . . . . . 41
Chapter 4
System Specifications for the Quantum Module . . . . . . . . . . 43
840 USE 100 00 11/2004 v
vi
Part IV
Quantum Module Specifications and Configuration . . . 47
Chapter 5
Hardware Specifications for the Quantum Modules. . . . . . . . 49
Chapter 6
Power Supply Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
140CPS11100 AC Power Supply 115/230 Vac 3 A Module . . . . . . . . . . . . . . . . 60
140CPS11100 AC Power Supply 115/230 Vac 3 A Module (PV01 or Greater) . 63
140CPS11400 AC Power Supply, 115/230 Vac, 8 A Module . . . . . . . . . . . . . . . 66
140CPS11410 AC Summable Power Supply 115/230 Vac, 8 A . . . . . . . . . . . . . 69
140CPS11420 AC Summable Power Supply 115/230 Vac, 11 A . . . . . . . . . . . . 72
140CPS12400 AC Redundant Power Supply, 115/230 Vac 8 A Module . . . . . . 75
140CPS12420 AC Redundant Power Supply, 115/230 Vac 11 A Module . . . . . 78
140CPS21100 DC Power Supply, 24 Vdc, 3 A Module. . . . . . . . . . . . . . . . . . . . 81
140CPS21400 DC Summable Power Supply, 24 Vdc, 8 A Module. . . . . . . . . . . 84
140CPS22400 DC Redundant Power Supply, 24 Vdc, 8 A Module . . . . . . . . . . 87
140CPS41400 DC Summable Power Supply, 48 Vdc, 8 A Module. . . . . . . . . . . 90
140CPS42400 DC Redundant Power Supply, 48 Vdc, 8 A Module . . . . . . . . . . 93
140CPS51100 DC Power Supply, 125 Vdc, 3 A Module. . . . . . . . . . . . . . . . . . . 96
140CPS52400 DC Standalone/Redundant Power Supply, 125 Vdc, 8 A . . . . . . 99
Chapter 7
CPU Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Chapter 8
Quantum Field Bus Modules . . . . . . . . . . . . . . . . . . . . . . . . . 189
140CRP81100 Profibus DP Master Communications Module. . . . . . . . . . . . . . 190
140EIA92100 Quantum AS-i Master Module. . . . . . . . . . . . . . . . . . . . . . . . . . . 195
140NOA6XXXX Quantum InterBus Communications Modules . . . . . . . . . . . . . 201
140NOL911X0 Quantum LonWorks Network Option Modules . . . . . . . . . . . . . 208
Chapter 9
Distributed I/O (DIO) for the Quantum Modules . . . . . . . . . . 213
140CRA21X10 Quantum Distributed I/O (DIO) Modules. . . . . . . . . . . . . . . . . . 214
140CRA21X20 Quantum Distributed I/O (DIO) Modules. . . . . . . . . . . . . . . . . . 219
Chapter 10
Quantum Remote I/O Communication Modules . . . . . . . . . . 225
140CRP93X00 Remote I/O (RIO) Head Single and Dual Channel Module. . . . 226
140CRA93X00 Quantum RIO Adapter Drop Single and Dual Channel Module 230
Chapter 11
Quantum Modbus Plus Network Option Modules . . . . . . . . 235
140NOM21X00 Quantum Modbus Plus Network Option Modules . . . . . . . . . . 235
840 USE 100 00 11/2004
Chapter 12
Quantum Modbus Plus Networking on Fiber Module . . . . . . 245
140NOM25200 Quantum Networking Modbus Plus on Fiber Module . . . . . . . 245
Chapter 13
Quantum Ethernet Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . 265
140NOE2X100 Quantum Ethernet TCP/IP Module . . . . . . . . . . . . . . . . . . . . . 266
140NOE3X100 Quantum Ethernet SY/MAX Modules. . . . . . . . . . . . . . . . . . . . 270
140NOE5X100 Quantum Ethernet MMS Modules . . . . . . . . . . . . . . . . . . . . . . 273
Chapter 14
Intelligent/Special Purpose Modules for the Quantum . . . . . 289
140EHC10500 High Speed Counter Module . . . . . . . . . . . . . . . . . . . . . . . . . . 290
140EHC20200 High Speed Counter Module . . . . . . . . . . . . . . . . . . . . . . . . . . 319
140ESI06210 ASCII Interface Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 332
140HLI34000 High Speed Interrupt Module . . . . . . . . . . . . . . . . . . . . . . . . . . . 338
140MSB/MSC10100 Quantum MSX Motion Modules. . . . . . . . . . . . . . . . . . . . 342
140XBE10000 Backplane Expander and Cable . . . . . . . . . . . . . . . . . . . . . . . . 352
140CHS11000 Hot Standby Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357
Chapter 15 Quantum Intrinsically Safe Analog/Digital, Input/Output
Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 361
15.1
Intrinsically Safe Modules - General Information. . . . . . . . . . . . . . . . . . . . . . . . 362
Intrinsically Safe Modules – General Description . . . . . . . . . . . . . . . . . . . . . . . 362
15.2
I/O Configuration for Intrinsically Safe Analog Modules . . . . . . . . . . . . . . . . . . 367
140AII33000 Intrinsically Safe Analog Input Module. . . . . . . . . . . . . . . . . . . . . 375
140AII33010 Intrinsically Safe Current Input Module . . . . . . . . . . . . . . . . . . . . 387
140AIO33000 Intrinsically Safe Analog Output Module . . . . . . . . . . . . . . . . . . 393
15.3
I/O Configuration for Intrinsically Safe Discrete Modules . . . . . . . . . . . . . . . . . 400
140DII33000 Intrinsically Safe Discrete Input Module. . . . . . . . . . . . . . . . . . . . 402
140DIO33000 Intrinsically Safe Discrete Output Module . . . . . . . . . . . . . . . . . 408
Chapter 16
Quantum Simulator Modules. . . . . . . . . . . . . . . . . . . . . . . . . . 415
140XSM00200 Quantum Point Discrete Simulator Module . . . . . . . . . . . . . . . 416
140XSM01000 Analog Simulator Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 417
Chapter 17
Quantum Battery Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 421
I/O Configuration for the 140XCP90000 Battery Module . . . . . . . . . . . . . . . . . 422
140XCP90000 Quantum Battery Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 423
Chapter 18 Quantum I/O Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 429
18.1
Overview of I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 430
Quantum I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 431
I/O Map Status Byte . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 442
18.2
Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 444
I/O Configuration for Analog Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . 445
840 USE 100 00 11/2004 vii
viii
140ACI03000 I/O Analog In Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 461
140ACI04000 High Density Analog in I/O Module . . . . . . . . . . . . . . . . . . . . . . . 464
140ARI03010 I/O RTD Input 8 Channel Module . . . . . . . . . . . . . . . . . . . . . . . . 467
140ATI03000 I/O Thermocouple Input 8 Channel Module . . . . . . . . . . . . . . . . 470
140AVI03000 I/O Analog IN 8 Channel Bipolar Module . . . . . . . . . . . . . . . . . . 473
18.3
Analog Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 477
I/O Configuration for Analog Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . 478
140ACO02000 Quantum I/O Analog Current Out Module. . . . . . . . . . . . . . . . . 482
140ACO13000 High Density Analog Out I/O Module . . . . . . . . . . . . . . . . . . . . 486
140AVO02000 Quantum I/O Analog Voltage Out Module. . . . . . . . . . . . . . . . . 489
18.4
Analog Input/Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 493
Configuration of the 140AMM09000 Analog Input/Output Module . . . . . . . . . . 494
140AMM09000 Analog Input/Output Module. . . . . . . . . . . . . . . . . . . . . . . . . . . 498
18.5
Discrete Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 504
I/O Configuration for Discrete Input Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . 505
140DAI34000 Quantum I/O 24 VAC IN Module. . . . . . . . . . . . . . . . . . . . . . . . . 509
140DAI35300 Quantum I/O AC Input 24 Vac Module . . . . . . . . . . . . . . . . . . . . 512
140DAI44000 Quantum I/O 48 VAC IN Module. . . . . . . . . . . . . . . . . . . . . . . . . 515
140DAI45300 Quantum I/O AC Input 48 Vac 4x8 Module. . . . . . . . . . . . . . . . . 518
140DAI54000 Quantum I/O 115 VAC In Module . . . . . . . . . . . . . . . . . . . . . . . . 521
140DAI54300 Quantum I/O AC Input 115 Vac 2x8 Module. . . . . . . . . . . . . . . . 524
140DAI55300 Quantum I/O AC Input 115 Vac 4x8 Module. . . . . . . . . . . . . . . . 527
140DAI74000 Quantum I/O AC Input 230 Vac 16x1 Module. . . . . . . . . . . . . . . 530
140DAI75300 Quantum I/O AC Input 230 Vac 4x8 Module. . . . . . . . . . . . . . . . 533
140DDI15310 Quantum I/O DC Input 5 V TTL 4x8 Source Module . . . . . . . . . 536
140DDI35300 Quantum I/O DC Input 24 Vdc 4x8 Sink Module . . . . . . . . . . . . 538
140DDI35310 Quantum I/O DC Input 24 Vdc True Low 4x8 Input Module . . . . 540
140DDI36400 I/O DC Input 24 VDC 6x16 Telefast Input Module . . . . . . . . . . . 542
140DDI67300 Quantum I/O DC Input 125 Vdc 3x8 Sink Module . . . . . . . . . . . 546
140DDI84100 Quantum I/O DC Input 10 ... 60 Vdc 8x2 Sink Module . . . . . . . . 550
140DDI85300 Quantum I/O DC Input 10 ... 60 Vdc 4x8 Sink Module . . . . . . . . 553
18.6
Discrete Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 556
I/O Configuration for Discrete Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . 557
140DAO84000 I/O AC Output 24 ... 230 Vac 16x1 Module. . . . . . . . . . . . . . . . 564
140DAO84010 I/O AC Output 24 ... 115 Vac 16x1 Module. . . . . . . . . . . . . . . . 568
140DAO84210 Quantum I/O AC Output 100 ... 230 Vac 4x4 Module . . . . . . . . 572
140DAO84220 Quantum I/O AC Output 24 ... 48 Vac 4x4 Module . . . . . . . . . . 577
140DAO85300 Quantum I/O AC Output 24 ... 230 Vac 4x8 Module . . . . . . . . . 582
140DDO15310 I/O DC Output 5 V TTL 4x8 Sink Module . . . . . . . . . . . . . . . . . 586
140DDO35300 Quantum I/O DC Output 24 Vdc 4x8 Source Module . . . . . . . . 590
140DDO35301 I/O DC Output 24 VDC 4x8 Discrete Source Module . . . . . . . . 594
140DDO35310 I/O DC Output 24 Vdc 4x8 Sink Module . . . . . . . . . . . . . . . . . . 597
140DDO36400 I/O DC Output 24VDC 6x16 Telefast Output Module . . . . . . . . 601
140DDO84300 Quantum I/O DC Output 10 ... 60 Vdc 2x8 Source Module . . . 606
140DDO88500 Quantum I/O DC Output 24-125 Vdc 2x6 Source Module . . . . 609
840 USE 100 00 11/2004
140DRA84000 Quantum I/O Relay Output 16x1 Normally Open Module. . . . . 613
140DRC83000 Quantum I/O Relay Output 8x1 Normally Open/
Normally Closed Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 616
18.7
Discrete Verified Output Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 619
I/O Configuration for the Discrete Verified Output Module – 140DVO85300 . . 620
140DVO85300 I/O Verified 10-30 VDC Out Module . . . . . . . . . . . . . . . . . . . . . 625
18.8
Discrete Supervised Input Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 629
I/O Configuration for the Discrete Supervised Input Module – 140DSI35300 . . 630
140DSI35300 I/O DC 24V Supervised Input Module . . . . . . . . . . . . . . . . . . . . 631
18.9
Discrete Input/Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 634
I/O Configuration for Discrete Input/Output Modules . . . . . . . . . . . . . . . . . . . . 635
140DAM59000 Quantum I/O AC Input 115 Vac 2x8 /
AC Output 115 Vac 2x4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 639
140DDM39000 I/O DC Input 24 Vdc 2x8 Sink/DC Output 24 Vdc 2x4
Source Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 646
140DDM69000 I/O 125 VDC Input/High Power Output Module . . . . . . . . . . . . 651
Appendices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 657
Appendix A Miscellaneous Components . . . . . . . . . . . . . . . . . . . . . . . . . . 659
Appendix B Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 669
Appendix C Hardware Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 673
Hardware Installation – Selecting Backplanes . . . . . . . . . . . . . . . . . . . . . . . . . 674
Hardware Installation – Mounting Brackets. . . . . . . . . . . . . . . . . . . . . . . . . . . . 681
Hardware Installation – Space Requirements for the Quantum System . . . . . . 684
Hardware Installation – Mounting Quantum Modules . . . . . . . . . . . . . . . . . . . . 686
Appendix D Power and Grounding Guidelines. . . . . . . . . . . . . . . . . . . . . . 691
Power and Grounding Considerations for AC and DC Powered Systems . . . . 692
System Design Considerations for Quantum Power Supplies . . . . . . . . . . . . . 703
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 710
Closed System Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 712
840 USE 100 00 11/2004 ix
x
Appendix E CableFast Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 715
Features of the CableFast Cabling System . . . . . . . . . . . . . . . . . . . . . . . . . . . . 716
140 CFA 040 00 Quantum CableFast Cabling Block. . . . . . . . . . . . . . . . . . . . . 722
140 CFB 032 00 Quantum CableFast Cabling Block. . . . . . . . . . . . . . . . . . . . . 724
140 CFC 032 00 Quantum CableFast Cabling Block . . . . . . . . . . . . . . . . . . . . 727
140 CFD 032 00 Quantum CableFast Cabling Block . . . . . . . . . . . . . . . . . . . . 733
140 CFE 032 00 Quantum CableFast Cabling Block. . . . . . . . . . . . . . . . . . . . . 735
140 CFG 016 00 Quantum CableFast Cabling Block . . . . . . . . . . . . . . . . . . . . 737
140 CFH 008 00 Quantum CableFast Cabling Block . . . . . . . . . . . . . . . . . . . . 742
140CFI00800 Quantum CableFast Cabling Block . . . . . . . . . . . . . . . . . . . . . . . 746
140CFJ00400 Quantum CableFast Cabling Block . . . . . . . . . . . . . . . . . . . . . . 750
140CFK00400 Quantum CableFast Cabling Block . . . . . . . . . . . . . . . . . . . . . . 754
CableFast Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 758
CableFast Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 763
Appendix F Error Stopped Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 765
Appendix G Agency Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 769
Index
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xv
840 USE 100 00 11/2004
Safety Information
Important Information
NOTICE Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists, which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death, serious injury, or equipment damage.
WARNING
WARNING indicates a potentially hazardous situation, which, if not avoided, can result in death, serious injury, or equipment damage.
CAUTION
CAUTION indicates a potentially hazardous situation, which, if not avoided, can result in injury or equipment damage.
xi
840 USE 100 00 11/2004
Safety Information
PLEASE NOTE Electrical equipment should be serviced only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. This document is not intended as an instruction manual for untrained persons.
© 2004 Schneider Electric. All Rights Reserved.
xii
840 USE 100 00 11/2004
About the Book
At a Glance
Document Scope This manual is a reference guide for the hardware of the Quantum automation system.
Validity Note The data and illustrations found in this book are not binding. We reserve the right to modify our products in line with our policy of continuous product development. The information in this document is subject to change without notice and should not be construed as a commitment by Schneider Electric.
Product Related
Warnings
Schneider Electric assumes no responsibility for any errors that may appear in this document. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical, including photocopying, without express written permission of
Schneider Electric.
All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to ensure compliance with documented system data, only the manufacturer should perform repairs to components.
When controllers are used for applications with technical safety requirements, please follow the relevant instructions.
Failure to use Schneider Electric software or approved software with our hardware products may result in improper operating results.
Failure to observe this product related warning can result in injury or equipment damage.
User Comments We welcome your comments about this document. You can reach us by e-mail at [email protected]
840 USE 100 00 11/2004 xiii
About the Book xiv
840 USE 100 00 11/2004
Quantum Automation
System Overview
I
At a Glance
Overview
What’s in this
Part?
This part provides an overview of the Quantum Automation System.
This part contains the following chapters:
Chapter
1
Chapter Name
Modicon Quantum Automation System Overview
Page
840 USE 100 00 11/2004
1
Quantum Overview
2
840 USE 100 00 11/2004
Modicon Quantum Automation
System Overview
1
At a Glance
Introduction
What’s in this
Chapter?
This chapter provides an overview of the Modicon Quantum Automation System, which includes Modicon Quantum software support.
This chapter contains the following topics:
Topic
Modicon Quantum Automation Series Overview
Quantum Power Supplies
Quantum CPU Modules
Quantum I/O Modules
Quantum Communication Interface Modules
Quantum Intelligent/Special Purpose I/O Modules
Quantum Simulator Modules (XSM)
Quantum Battery, Backplanes, and CableFast Cabling
Quantum Programming Packages
Page
3
840 USE 100 00 11/2004
4
Modicon Quantum Overview
Modicon Quantum Automation Series Overview
Overview z z z z z z z z z
The Modicon Quantum system is a special-purpose computing system with digital processing capabilities. Modicon Quantum is designed for real time control in industrial and manufacturing applications in a modular, expandable architecture employing the following modules.
Power Supply
CPU
I/O
I/O Network Interface
Intelligent/Special Purpose I/O
Simulator (XSM)
Battery
Backplanes
CableFast Cabling
Modicon
Quantum System
Block Diagram
The following figure is a block diagram of a typical Modicon Quantum system.
/RFDO,2'URS
Ethernet TCP/IP
P/S CPU RIO
Head
NOM NOE I/O I/O I/O I/O I/O
Modbus Plus DIO
Twisted Pair Cable
',2'URS
MB+
Tap
MB+
Tap
RIO Coaxial
Modbus Plus Cable
5,2'URS
DIO
Drop
I/O I/O
P/S RIO
Drop
I/O I/O I/O I/O
MB+
Tap
RIO
Tap
840 USE 100 00 11/2004
Modicon Quantum Overview
Quantum Power Supplies
Overview
Power Supply
Modes
Quantum power supplies are used to supply system power to all modules inserted into the backplane, including: z z z
Quantum CPU modules
Quantum Interface modules
Quantum I/O modules
Depending upon the system configuration, the option exists of using the power supply in three different modes.
The following table shows the power supply modes.
Power Supply Type
Standalone
Usage
For 3 A, 8 A or 11 A configurations that do not require fault tolerant or redundant capabilities.
Standalone Summable For configurations consuming more than the rated current of one supply, two summing power supplies can be installed in the same backplane.
Redundant For configurations requiring power for uninterrupted system operation. Two redundant power supplies are required for redundancy.
&$87,21
6\VWHP6DIHW\
Exercise caution when considering a combination of power supplies in a backplane. Use only like power supplies with the exceptions noted in 6\VWHP
'HVLJQ&RQVLGHUDWLRQVIRU4XDQWXP3RZHU6XSSOLHVS
.
)DLOXUHWRIROORZWKLVSUHFDXWLRQFDQUHVXOWLQLQMXU\RUHTXLSPHQWGDPDJH
840 USE 100 00 11/2004
5
6
Modicon Quantum Overview
Quantum CPU Modules
Overview The Quantum CPU is a module residing on the Quantum local I/O backplane. The
CPU is a digitally operating electronic system, which uses a programmable memory for the internal storage of user instructions. These instructions are used to implement specific functions such as: z z z z z
Logic
Process sequencing
Timing
Coupling
Arithmetic
These instructions allow control through digital and analog outputs, for various types of machines and processes.
The Quantum CPU serves as a bus master controlling the local, remote, and distributed I/O of the Quantum system.
840 USE 100 00 11/2004
Modicon Quantum Overview
Quantum I/O Modules
Overview Quantum I/O modules are electrical signal converters that convert signals to and from field devices to a signal level and format, which can be processed by the CPU, such as: z z z z z
Limit switches
Proximity switches
Temperature sensors
Solenoids
Valve actuators
All I/O modules are optically isolated to the bus, ensuring safe and trouble-free operation. All I/O modules are also software configurable.
840 USE 100 00 11/2004
7
8
Modicon Quantum Overview
Quantum Communication Interface Modules
Overview
Network
Interface
Modules
Nine types of communication interface modules are available and presented in the table below, and are described in the following text.
The following table shows the communication interface modules.
Type
RIO
DIO
NOM
Description
Single and dual channel Remote I/O interface modules (RIO heads and drops) connected via a coaxial cable network.
Single and dual channel Distributed I/O interface modules connected via a twisted pair Modbus Plus cable network.
Single and dual channel Network Option Modules (NOM) connected via a twisted pair Modbus Plus cable network.
Fiber Optic
Modbus Plus
Modbus Plus on fiber module connected via a fiber optic Modbus Plus cable network.
Ethernet TCP/
IP
Single channel Ethernet TCP/IP interface module connected via a twisted pair or fiber optic cable network.
InterBus
SY/MAX
Ethernet
LonWorks
MMS
Ethernet
Profibus
AS-i
InterBus Interface module connected via a twisted pair network.
SY/MAX Ethernet module connected via a twisted pair or fiber optic cable network.
LonWorks module connected via a twisted-pair network.
MMS Ethernet module connected via a fiber optic cable network.
Profibus Master module connected via a Profibus RS-485 port.
AS-i module connected via a two-wire AS-i port.
840 USE 100 00 11/2004
Modicon Quantum Overview
RIO Modules
(CRA/CRP)
DIO Module
(CRA)
Quantum RIO head and drop modules use a S908-based networking I/O configuration. Communication is done via single or dual coaxial cabling up to 15,000 z z z z z feet away. This configuration supports a mix of the following product lines:
SY/MAX
200 Series
500 Series
800 Series
Quantum I/O
When Quantum RIO is required, the Quantum controller may support up to 31 RIO drops. In an RIO configuration, an RIO head module is connected with coaxial cable to RIO drop modules at each remote drop.
Quantum DIO is implemented over a Modbus Plus network. The CPU or NOMs module may be the network head via their Modbus Plus ports.
Quantum DIO Modbus Plus drop adaptors are specifically designed to link Quantum
I/O modules to the head via twisted pair shielded cable (Modbus Plus). The DIO drop modules also provide the I/O with power (maximum 3A) from a 24 Vdc or a 115/
230 Vac source. Each DIO network supports up to 63 distributed drops using repeaters.
Network Option
Module (NOM)
Quantum NOM modules provide extended communication capabilities for the
Quantum system within a Modbus Plus configuration.
Modbus Plus on
Fiber Module
(NOM)
Quantum Modbus Plus on Fiber modules provides connectivity to Modbus Plus nodes by fiber cable without fiber optic repeaters, and allows the creation of a pure fiber optic network or a mixed fiber optic/twisted-pair network (with the use of a
490NRP254 Fiber Optic Repeater).
Ethernet TCP/IP
(NOE) Modules
Quantum Ethernet TCP/IP modules make it possible for a Quantum controller to communicate with devices on an Ethernet network using TCP/IP – the de facto standard protocol. An Ethernet module may be inserted into an existing Quantum system and connected to existing Ethernet networks via fiber optic or twisted pair cabling.
SY/MAX Ethernet
Modules (NOE)
Quantum-SY/MAX-Ethernet modules are Quantum CPU network option modules that can be placed in a Quantum backplane to connect Quantum controllers to SY/
MAX devices and applications.
840 USE 100 00 11/2004
9
Modicon Quantum Overview
MMS-Ethernet
Modules (NOE)
Quantum-MMS-Ethernet modules are Quantum CPU network option modules that can be placed in a Quantum backplane to connect Quantum controllers to MMS devices and applications.
InterBus
Interface Module
(NOA)
The Quantum InterBus is the interface module to the InterBus bus. The InterBus bus is a fieldbus network designed for I/O blocks and intelligent devices used in manufacturing. It offers a master/slave topology that permits deterministic I/O servicing over it’s 13 km twisted pair network.
LonWorks
Modules (NOL)
Profibus
Interface Module
(CRP)
Quantum Profibus module is the interface module to Profibus-DP networks. The interface modules use Type A, shielded twisted pair to join inline connectors, with or without service ports and bus terminators.
AS-i Interface
Module
Quantum NOL modules provide connectivity between a Quantum controller and a
LonWorks network, based on Echelon’s LonWorks technology. The NOL module is offered in three models for different transceiver types, and supports three twistedpair media types with different network topologies or data transfer speeds.
Quantum AS-i modules provide connectivity between a Quantum controller and ASi networks. AS-i bus cable is an unshielded flat two-wire link on which communication and power are transmitted to connected devices. The media insulation is self-healing to accommodate junction block removal.
10
840 USE 100 00 11/2004
Modicon Quantum Overview
Quantum Intelligent/Special Purpose I/O Modules
Overview z z z z z
Quantum Intelligent/Special Purpose I/O modules operate with minimum intervention from the Quantum controller after initially downloading module parameters or programs. The Quantum intelligent/special purpose I/O modules include the following.
High Speed Counter modules (EHC)
ASCII Interface module (ESI)
High Speed Interrupt module (HLI)
Single Axis Motion Modules (MSx)
Multi-Axis Motion Modules (MMS)
840 USE 100 00 11/2004
11
Modicon Quantum Overview
Quantum Simulator Modules (XSM)
Overview
Discrete and
Analog
Simulators
There are two types of simulator modules, as described below.
The following table shows discrete and analog simulators.
Type
Discrete 16 Point
Simulator
(140XSM00200)
Analog Simulator
(140XSM01000)
Description
The Discrete Simulator (16 points) is used to generate up to 16 binary input signals to the 140DAI54000 and the 140DAI74000 AC input modules.
The Analog Simulator (2 channels in, 1 channel out) module is used for simulating 4 ... 20 mA field current loops used with current input
Quantum modules.
12
840 USE 100 00 11/2004
Modicon Quantum Overview
Quantum Battery, Backplanes, and CableFast Cabling
Battery Module
(XCP)
The Quantum battery module provides RAM backup power for the Quantum expert module.
Backplanes
(XBP)
CableFast
Cabling
Quantum backplanes may be used in all locations of local, remote, or distributed I/
O. There are six backplanes available in 2, 3, 4, 6, 10, and 16 slot versions. All I/O slots are usable with any module able to be used in any slot.
The Quantum CableFast wiring system consists of pre-wired Quantum field wiring terminal strips and DIN rail-mounted terminal blocks, offered in straight through or special application versions.
840 USE 100 00 11/2004
13
Modicon Quantum Overview
Quantum Programming Packages
Overview Quantum controllers support several editors.
Quantum Editors The following table shows the editors for the Quantum controllers.
Editor
Modsoft V2.6
Concept V2.5
ProWORX NXT V2.1
ProWORX 32
(V 1.0 minimum)
ProWORX Plus
(V 1.0 minimum)
Modicon State Language
(V1.2 minimum)
Where Discussed
For more information on Modsoft, refer to the Modicon Modsoft
Programmer User Manual (890USE11500).
For more information on Concept, refer to the Concept User
Manual (840USE49300).
For more information on ProWorX, refer to the ProWorX User
Manual (372SPU68001 NMAN)
For more information on ProWORX 32, refer to the ProWORX
32 Programming Software for PLCs User Guide (372SPU780
01EMAN)
For more information on ProWORX Plus, refer to the
ProWORX Plus for Modicon Reference Manual
(371SPU68001 PMAN).
For more information on Modicon State Language, refer to the
Modicon State Language User Manual (GM-MSL1-001).
14
840 USE 100 00 11/2004
Quantum System Configurations
II
At a Glance
Overview
What’s in this
Part?
This part provides information on Quantum system configurations.
This part contains the following chapters:
Chapter
2
3
Chapter Name
Quantum Configurations
Network Configurations
Page
840 USE 100 00 11/2004
15
Quantum Configurations
16
840 USE 100 00 11/2004
Quantum Configurations
2
At a Glance
Introduction
What’s in this
Chapter?
The following chapter provides information on the Quantum configurations, including Local I/O, Remote I/O (RIO), and Distributed I/O (DIO).
This chapter contains the following topics:
Topic
Quantum Local I/O, Remote I/O and Distributed I/O Configurations
Quantum Local I/O
Quantum Remote I/O (RIO)
Quantum Distributed I/O (DIO)
Page
840 USE 100 00 11/2004
17
Quantum Configurations
Quantum Local I/O, Remote I/O and Distributed I/O Configurations
Overview The following information contains a description of the Local I/O, Remote I/O and
Distributed I/O and their configurations.
These configurations (see the configuration table below for valid Quantum z z z z z configurations) can be equipped with a combination of:
Quantum CPUs
Power supplies
I/O interfaces
Expert modules
I/O modules
1RWH Refer to
S for a complete list of part numbers for all Quantum modules.
Local, RIO, and
DIO
Configuration
The following table provides valid Quantum configurations, including backplanes and modules.
If Configuration
Type Is
Local
Backplane Types
(Typical) Are
6, 10, 16 slots
Required
Modules Are
Power Supply
CPU
Optional
Modules Are
RIO Head, I/O,
NOx*
Modules Not
Permitted Are
RIO Drop, DIO
Drop
RIO**
DIO
6, 10, 16 slots
2, 3, 4, 6 slots
Power Supply
RIO Drop
DIO Drop
I/O CPU, RIO Head,
DIO Drop NOx*
Power Supply,
I/O
CPU, RIO Head,
RIO Drop NOx*
*NOM, NOA, and NOE.
**Remote I/O is typically used for large (number of modules) drops 6, 10, or 16 slot backplanes. Distributed I/O is typically used for small drops using 2, 3, 4, or 6 slot backplanes.
1RWH Every Quantum module requires power from the backplane (except power supply and DIO modules). For a valid configuration, add up the required backplane current (in mA) for every module, and ensure that this number is less than the available power in the selected power supply.
18
840 USE 100 00 11/2004
Quantum Configurations
Local, Remote and Distributed
I/O Configuration
Depending on the type of configuration—Local, Remote, or Distributed I/O, a variety of features will apply, as shown in the following table.
Feature Configuration
Local I/O Remote I/O Distributed I/O
Maximum I/O Words
Per drop
Per network
Maximum Physical Discretes
Per drop
Maximum drops per network
Media
Speed
Maximum distance without repeaters
Scan synched I/O servicing
Momentum I/O support
Hot Standby support
Modbus Plus compatible
64 in / 64 out 64 in / 64 out 30 in / 32 out
1,984 in / 1,984 out 500 in / 500 out
*864 any mix *864 any mix
31
Coax
1.5 Mhz
448 any mix
63
Twisted Pair
1 MHz
15,000 ft. (4,573 m) 1,500 ft. (457 m)
Yes
No
Yes
No
No
Yes
No
Yes
*Requires use of backplane expander, Telefast module excepted (27 modules x 32 points = 864). May be limited by bus power requirements.
840 USE 100 00 11/2004
19
Quantum Configurations
Quantum Local I/O
Overview A local I/O configuration is contained in one rack and includes all Quantum modules mounted in a standard Quantum backplane. Quantum Local I/O can be as few as one I/O module (in a three slot backplane), or as many as 14, along with a CPU and power supply in a single 16 slot backplane.
If required for the application, system interface modules are also included in the
Local I/O backplane. These modules could consist of one RIO processor or network option modules.
I/O Configuration The following figure is an example of a typical local I/O configuration.
PS CPU I/O I/O I/O I/O I/O I/O I/O I/O I/O I/O I/O I/O I/O I/O
2 Slot
3 Slot
4 Slot
6 Slot
10 Slot
16 Slot
1RWH A maximum of 448 digital I/O points (14, 4x8 digital I/O modules), or a maximum of 48 analog input channels (six 8-channel analog in modules) and 32 analog output channels (eight 4-channel analog out modules) may be serviced in a single local I/O rack.
20
840 USE 100 00 11/2004
Quantum Configurations
Quantum Remote I/O (RIO)
Overview Quantum RIO can be set up in single or dual cable configurations (refer to the following two figures) and is contained in one rack at each RIO drop. When RIO is used, the Quantum CPU may support several drops (a drop can be either Quantum,
SY/MAX, 200, 500, or 800 Series I/O systems).
1RWH As stated above, the Quantum provides connectivity to other Modicon I/O products via the same system. It will connect to 800 series I/O via the J890, J892,
P890, or P892 remote I/O adapters; 200 series I/O via J290 and J291 remote I/O adapters; 500 series I/O via 29X/J540 remote I/O adapters; and SY/MAX
8030CRM931
Related
Documentation
For more information on use and installation of Quantum RIO, see Modicon Remote
I/O Cable System Planning and Installation Guide , Part Number 890USE10100
For more information on Hot Standby systems, see the Quantum Hot Standby
Installation and Planning Guide , Part Number 840USE10600.
Single Cable RIO
Configuration
The following figure is an example of a single cable Quantum RIO configuration.
PS
&38
5,2
+HDG I/O I/O I/O
Local I/O
Drop
Up to 31 Drops
RIO Tap
Terminator
RIO Tap
PS
5,2
'URS
I/O I/O I/O I/O
RIO Tap
PS
5,2
'URS
I/O I/O I/O I/O
P81 J890
RIO Drop # m RIO Drop # n
*A RIO tap is required for every RIO drop in the system.
B800 Series Drop
840 USE 100 00 11/2004
21
Quantum Configurations
Dual Cable RIO
Configuration
The following figure is an example of a dual cable Quantum RIO configuration.
PS CPU
RIO
Head
I/O I/O I/O
Local I/O
Drop
Up to 31 Drops
*RIO
Tap
*RIO
Tap
*RIO Tap
*RIO
PS
RIO
Drop
I/O I/O I/O I/O
*RIO Tap and
Terminator
PS
RIO
Drop
I/O I/O I/O
*RIO Tap and
Terminator (#52-0422-000)
P81 J890
Hot Standby
System
RIO Drop # m RIO Drop # n B800 Series
*An RIO tap (# MA-0185-100) is required for every RIO drop in the system.
1RWH The dual cable option is provided for systems that require added protection against cable breaks or damaged connectors. With two cables connected between the host and each node, no single cable break will disrupt communications.
The Quantum Hot Standby system is designed for use with remote I/O networks. A
Quantum Hot Standby system may be set-up using single or dual cable configurations (refer to the following two figures).
22
840 USE 100 00 11/2004
Quantum Configurations
Single Cable Hot
Standby
Configuration
The following figure is an example of a single cable Quantum Hot Standby configuration.
Primary Controller
PS PLC RIO CHS
Standby Controller
PS PLC RIO CHS
Self-terminating
F adapter
Fiber Optic Cable
Coaxial Cable
Splitter
#MA-0186-100
RIO Drop # 2
PS RIO I/O I/O I/O
Trunk
Cable
Self-terminating F adapter
#52-0411-000
(for quad shield cable)
#52-0399-000
(for non-quad shield cable)
Tap
#MA-0185-100
Last RIO Drop
PS RIO I/O I/O I/O
Trunk Terminator
#52-0422-000
Tap
840 USE 100 00 11/2004
23
Quantum Configurations
Dual Cable Hot
Standby
Configuration
The following figure is an example of a dual cable Quantum Hot Standby configuration.
Primary PLC
PS PLC RIO CHS
Standby PLC
PS PLC RIO CHS
Self-terminating
F adapters Coaxial Cable
Coaxial Cable
Splitter
#MA-0186-100
RIO Drop # 2
PS RIO I/O I/O I/O
Trunk
Line
A
Fiber Optic Cable
Trunk
Line
B
Splitter #MA-0186-100
Drop Cable
Tap
#MA-0185-100
Self-terminating F adapters
#52-0411-000
(for quad shield cable)
#52-0399-000
(for non-quad shield cable)
Last RIO Drop
PS RIO I/O I/O I/O
Trunk Terminator
#52-0422-000
Trunk Terminator
#52-0422-000
Drop Cable
24
840 USE 100 00 11/2004
Quantum Configurations
Quantum Distributed I/O (DIO)
Overview Quantum DIO can be set up in standard single or dual cable configurations (refer to the following two figures). The Quantum DIO architecture is based on Modicon’s
Modbus Plus technology. When DIO is utilized, the Quantum system may support up to three distributed networks of up to 64 drops (using a repeater) each.
Communication between the various nodes and the Modbus Plus head, in both single and dual cable DIO configurations, is done by twisted pair cabling from the head to the DIO adapters at the drops.
For detailed information concerning the Quantum DIO systems, refer to the
MODBUS Plus I/O Servicing User Guide , part number 840USE10400.
Related
Documentation
Single Cable DIO
Configuration
The following figure is an example of a single cable Quantum DIO configuration.
PS CPU I/O I/O I/O I/O I/O I/O I/O I/O
Local I/O
* Tap
DIO
Drop
I/O I/O I/O
* Tap
Up to 31 drops (64 with repeater)
DIO
Drop
I/O I/O I/O
840 USE 100 00 11/2004
Quantum Drop # m
** Drop Cable
Quantum Drop # n
** Drop Cable
* A MODBUS Plus tap is required for every participant on the network.
** A drop cable is required for each drop from the MODBUS Plus tap.
(Cables are not included with the mopdules and need to be ordered.)
25
Quantum Configurations
Dual Cable DIO
Configuration
The following figure is an example of a dual cable Quantum DIO configuration.
PS CPU NOM I/O I/O I/O I/O I/O I/O I/O
Local I/O
*Tap
*Tap
Trunk Cable
Trunk Cable
*Tap
*Tap
DIO
Drop
I/O I/O I/O
Up to 31 Nodes (63 with repeater)
Up to 31 Nodes (63 with repeater)
DIO
Drop
I/O I/O I/O
Quantum Drop # m Quantum Drop # n
***Drop Cables ***Drop Cables
*A MODBUS Plus tap (plastic, Part # 990NAD23000; ruggedized, Part # 990NAD23010) is required for every participant on the network.
***A drop cable (8 ft/2.4 m, Part # 990NAD21110; 20 ft/6 m, Part # 990NAD21130) is required for each drop from the MODBUS Plus tap. Cables are not included with the modules and need to be ordered.
1RWH The dual cable option is provided for systems that require added protection against cable breaks or damaged connectors. With two cables connected between the host and each node, no single cable break will disrupt communications.
26
840 USE 100 00 11/2004
Part Numbers
Quantum Configurations
MODBUS Plus taps that can be used for single and dual cable DIO configurations include: z z
Part Number 990NAD23000, plastic; and
Part Number 990NAD23010, ruggedized.
z z z z z
The following MODBUS Plus trunk cables can be used with these DIO configurations:
Part Number 490NAA27101 (100 ft/30 m)
Part Number 490NAA27102 (500 ft/152 m)
Part Number 490NAA27103 (1000 ft/304 m)
Part Number 490NAA27104 (1500 ft/456 m)
Part Number 490NAA27105 (5000 ft/1520 m)
Drop cables that can be used for these configurations include: z z
Part Number 990NAD21110 (8 ft/2.4 m)
Part Number 990NAD21130 (20 ft/6 m)
840 USE 100 00 11/2004
27
Quantum Configurations
28
840 USE 100 00 11/2004
Network Configurations
3
At a Glance
Introduction
What’s in this
Chapter?
The following chapter provides information on the Quantum network support, network interface techniques, and Modbus and Modbus Plus communications.
This chapter contains the following topics:
Topic
Quantum Network Support
Quantum Network Interface Techniques
Quantum Modbus and Modbus Plus Communications
Page
840 USE 100 00 11/2004
29
Network Configurations
Quantum Network Support
Overview Quantum systems provide multiple choices for open, standards-based networking z z z z z z z z z and fieldbus connectivity requirements. The Quantum supported networks include:
Modbus
Modbus Plus
Remote I/O
TCP/IP Ethernet
SY/MAX Ethernet
MMS Ethernet
Interbus
LonWorks
SERCOS
Combinations of these networks can be used to provide simple, high performance communication architectures which meet the tightly integrated needs of computer and controller connectivity. A summary of the services available on these networks is shown in the following table.
30
840 USE 100 00 11/2004
840 USE 100 00 11/2004
Network Configurations
Quantum
Supported
Networks
The following table shows the Quantum supported networks.
Service
Description
Native to
Quantum
CPU
Available on a
Network
Module
Y
Modbus Modbus
Plus
Remote
I/O
Ethernet
TCP/
IP
SY/
MAX
Y Y N N N
Y Y Y Y
CPU
Programming
CPU
Executive
Firmware
Loading
Support
Y
Y
1
1
Y
Y
1
N
N
Y
N
N
N
Y Y Y Y Module
Firmware
Loaded From
CPU
Y
Report By
Exception
Communications
Multi-node
Broadcast
Communications y Y
N
2
Synchronized
I/O Scanning
N
N NonSynchronized I/O
Scanning
Quantum I/O
Drops
N
Hot Standby
Quantum I/O
Drop Support
N
Y
Y
N
Y
Y
N
1
1
1
N
N
Y
N
Y
Y
Y
N
N
N
N
N
Y
N
N
N
N
N
MMS
N
Y
N
N
Y
Y
N
N
N
N
N
5
5
Interbus LonWorks SERCOS Profibus
N
Y
N
N
N
N
N
N
Y
N
N
6
N
Y
N
N
N
N
N
N
Y
N
N
N
Y
N
N
Y
N
N
Y
N
N
N
N
Y
N
N
Y
N
N
Y
N
N
N
31
Network Configurations
Service
Description
Hot Standby
Data
Communicati ons Support
Y
Optional Dual
Cabling
N
Modbus Modbus
Plus
Remote
I/O
Ethernet
TCP/
IP
SY/
MAX
Y N Y N
Y
1 Y N N
MMS
N
N
Interbus LonWorks SERCOS Profibus
N
N
N
N
N
N
N
N
Optional
Fiber Optics
Momentum I/
O Drops
Variable
Speed Drives
Y
N
Y
3
3
Servo Motion
Control
N
HMI: Displays
& Panels
Y
Y
Y
Y
Y
Y
1
1
1
1
1
Y
N
N
N
Y
Y
N
N
N
N
Y
N
N
N
N
Y
N
N
N
N
5
Y
Y
Y
Y
Y
3
3
3
3
Y
N
Y
Y
Y
4
4
4
4
Y
N
N
Y
N
4 N
Y
Y
Y
N
HMI: Workstations
Y
Y
1 N Y Y
Y
N
Y
4 N N
1.
Refer to the Modbus Plus portion of the Quantum Specifier’s guide section for details of available services on
140NOM2XXX00 Modbus Plus Network modules
2.
Service is only available on the native controller Modbus port when the XMIT loadable is used.
3.
Available from third parties.
4.
The SERCOS network standard is fiber optics.
5.
The software for this module is a modConnect product.
6.
Module firmware loaded through serial port on module.
32
840 USE 100 00 11/2004
Network Configurations
Quantum Network Interface Techniques
Overview
Direct CPU
Driver
Quantum communication and networking modules use a variety of different techniques to interface to the Quantum controller over the local backplane.
This technique allows the CPU to control high speed data transfers to and from the communication and networking modules, maximizing throughput and performance.
This technique is used extensively by the Remote I/O network and Hot Standby system to ensure highly deterministic synchronization of the CPU and I/O scans.
1RWH Only one Remote I/O Head Interface is supported for each Quantum CPU.
Option Module
Interface
CPU Interface
Support
This technique allows the communication and networking modules to control data transfers to and from the CPU, maximizing the flexibility of the communications interface.
This technique is used extensively by the Modbus Plus and Ethernet peer-to-peer network modules. The number of option module interfaces supported by each CPU model is described in the following table.
The following table shows the summary of Quantum CPU option module interface support in standalone configurations.
Quantum Controller Model Number Available Option Module Interfaces Supported
Per CPU
140CPU53414(A)
140CPU43412(A)
6
6
140CPU42402
140CPU21304
140CPU11303
140CPU11302
6
2
2
2
1RWH Refer to
S for details of available services on 140NOM2XX00 Modbus
Plus Network modules.
840 USE 100 00 11/2004
33
Network Configurations
I/O Map Interface Some network and communication modules are interfaced to the controller through the standard I/O map configuration tables. In the following table, note that some network and communication modules require a Loadable instruction which enhances the standard controller Executive to support certain unique features of individual modules.
In addition, some loadables allow the communication and networking modules to be controlled by means of user-application code. The number of loadables and associated modules that can be handled by an individual CPU depends upon its memory size, the size of the application program, and the size of the loadables.
34
840 USE 100 00 11/2004
Network Configurations
Communications and Networking
Model Number
140CRP81100
140CRP93100
140CRP93200
140CHS21000
140NOA61110
140NOM21100
140NOM21200
140NOM25200
140NOE21100
140NOE25100
140NOE31100
140NOE35100
140NOE510 0
1
140NOE5510 0
1
The following table shows the Quantum communications and networking modules.
Description
Profibus
Module
Interface
Technique
Direct CPU
Driver
Direct CPU
Driver
Remote I/O
Head Interface, single cable
Remote I/O
Head Interface, dual cable
Direct CPU
Driver
Hot Standby
Processor Kit
Direct CPU
Driver
Interbus Master Direct CPU
Driver
Option
Module
Modbus Plus
Options, single cable
Modbus Plus
Option, dual cable
Option
Module
Modbus Plus
Option, single channel fiber
Option
Module
Ethernet TCP/IP
Twisted Pair
Option
Module
Ethernet TCP/IP
Fiber Optic
Option
Module
Ethernet SY/
MAX Twisted
Pair
Option
Module
Ethernet SY/
MAX Fiber Optic
Option
Module
Ethernet MMS
Twisted Pair
Ethernet MMS
Fiber Optic
Option
Module
Option
Module
Loadable
Required
N
N
N
Y
Y
N
N
N
N
N
N
N
N
N
Backplane Support
Local RIO DIO
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
Bus Power mA
1200
780
780
700
700
780
780
900
1000
1000
1000
1000
1000
1000
840 USE 100 00 11/2004
35
Network Configurations
Model Number Description Module
Interface
Technique
140NOE77100/1 Ethernet TCP/IP
10/100 TX/FX
N
140NOE77110/1 Ethernet TCP/IP
10/100 TX/FX
Factory Cast
N
140MMS42500 Multi-Axis Motion
Controller w/
SERCOS
Option
Module
140NOL91100
140NOL91110
Loadable
Required
N
N
N
LonWorks
Interface, twisted pair FTT10
I/O Map (16/
16)
Y
LonWorks
Interface, twisted pair TPT/XF-78
I/O Map (16/
16)
Y
140NOL91120 LonWorks
Interface, twisted pair TPT/XF-
1250
I/O Map (16/
16)
Y
Backplane Support
Local RIO DIO
Y
Y
Y
Y
Y
Y
N
N
N
Y
Y
Y
N
N
N
N
N
N
1. The software for this module is a ModConnect product.
Bus Power mA
750
750
2500
950
950
950
36
840 USE 100 00 11/2004
Network Configurations
Quantum Modbus and Modbus Plus Communications
Overview
Modbus and
Modbus Plus
Features
Each Quantum CPU includes both a Modbus and Modbus Plus communications port. The features offered by both these communication protocols are listed in the following table.
The following table shows the Modbus and Modbus Plus features.
Features
Technique
Speed
Electrical
Modbus
Slaves polled by a master
19.2K typical
RS-232, various others
Distance without repeater RS-232, 50 ft. (15 m)
Media Various
Max nodes per network
Max network traffic
247
300 registers/sec @ 9.6 Kb
Programming
Read/Write data
Global data
Peer Cop
Yes
Yes
No
No
Yes
Yes
Yes
Yes
Modbus Plus
Peer-to-peer, token rotation
1 M
RS-485
1,500 ft. (457 m)
Twisted pair, Fiber optics
64
20,000 registers/sec
Modbus Modbus, a master/slave protocol, is a de facto industry standard with support from over 500 industrial suppliers.
On-line programming or data acquisition applications are easily supported directly from the serial port of any computer.
Modbus can be used in either a simple point-to-point manner with a pair of devices, or in a network architecture with up to 247 slave devices.
840 USE 100 00 11/2004
37
Network Configurations
Modbus Plus Modbus Plus combines high speed, peer-to-peer communication and easy installation to simplify applications and reduce installation costs.
It allows host computers, controllers and other data sources to communicate as peers throughout the network via low-cost twisted pair cable or optional fiber optic cable.
As a deterministic token-passing network, Modbus Plus communicates at one megabaud for fast access to process data. It’s strength is its ability to control realtime control devices like I/O and drives, without degraded performance due to loading or traffic.
Bridging between Modbus and Modbus Plus is done automatically on CPUs and
Modbus Plus network modules.
The bridge mode redirects Modbus messages onto the Modbus Plus network for easy connectivity between Modbus and Modbus Plus devices.
A summary of the available services on Quantum Modbus and Modbus Plus ports is given in the following table.
38
840 USE 100 00 11/2004
Network Configurations
Modbus and
Modbus Plus
Services
Type
The following table shows the Quantum Modbus and Modbus Plus services.
Service Description Native CPU Ports NOM 1-2 Ports NOM 3-6 Ports
Modbus
Services
Default Modbus Port Parameters Y
Configurable Modbus Port
Parameters
Y
Modbus Modbus
Plus
-
-
Modbus to Modbus Plus Bridging
Y
2 -
Modbus
Plus
Services
Local CPU Programming
Remote CPU Programming over
Modbus Plus
Modbus access to local CPU
Modbus access to remote CPU over Modbus Plus
Y
Y
Y
4
Modbus Network Slave Support Y
Modbus Master support with
XMIT Loadable
Y
Y Executive Firmware Loading
Support
MSTR read/write register messagin g
6
-
MSTR read/write Global Data messaging
MSTR get/clear local/remote statistics
Config Extension Global Data
Support
Config Extension Peer Cop
Support
Distributed I/O Support
CPU Programming
-
-
-
-
-
-
Y
4
Executive Firmware Loading
Support
-
-
-
-
-
-
-
-
Y
Y
Y
Y
Y
Y
Y
4
Y
N
N
Y
Y
Y
Y
Modbus Modbus
Plus
-
-
Modbus Modbus
Plus
Y -
-
Y
5
N
-
-
-
-
-
-
-
-
Y
Y
Y
3
4
4
-
-
-
-
-
-
-
-
Y
Y
Y
Y
Y
Y
Y
4
N
N
N
-
-
-
-
-
-
-
N
N
N
Y
-
Y
Y
3
2
-
-
-
-
-
-
-
-
Y
Y
Y
N
N
N
Y
4
N
840 USE 100 00 11/2004
39
Network Configurations
1RWH
Only supported on the 140CPU42402, 140CPU42412(A) and 140CPU53414(A)
Quantum Controllers.
The native CPU Modbus port can be disabled from bridge mode operation with the native Modbus Plus Port.
Modbus ports on NOMs are always in bridge mode with their associated
Modbus Plus port.
Only one programmer connection can be logged in at a time to any CPU, and only one program monitor can be attached at a time to any CPU.
Modbus port parameters on NOMs 3-6 are defined by Modbus Port 3 in Concept and Modsoft when the comm parameter selector switch is in mem.
Up to 4 MSTR read/write register instructions can be serviced per CPU scan per
Modbus Plus port.
40
840 USE 100 00 11/2004
Quantum System Specifications
III
At a Glance
Overview
What’s in this
Part?
This part provides system specifications for the Quantum automation system.
This part contains the following chapters:
Chapter
4
Chapter Name
System Specifications for the Quantum Module
Page
840 USE 100 00 11/2004
41
System Specifications
42
840 USE 100 00 11/2004
System Specifications for the
Quantum Module
4
Quantum System Specifications
Overview
Mechanical
Specifications
All modules are designed to the following system specifications, which include: z z z mechanical electrical
AC/DC power supplies
It shows the I/O modules operating voltages for: z z less than 24 Vac or Vdc between 24 and 48 Vac or Vdc z greater than 48 Vac or Vdc
Also given are the operating and storage conditions as well as agency approvals.
The following table shows individual Quantum module mechanical specifications.
Weight
Dimensions (H x D x W)
2 lbs. (1 kg) max
9.84 in. x 4.09 in. x 1.59 in. (250 mm x 103.85 mm x
40.34 mm)
Wire Size 1-14 AWG or 2-16 AWG max. 20 AWG min.
Material (Enclosures and Bezels) Polycarbonates
Space Requirements 1 backplane slot
Electrical
Specifications
The following table shows the Quantum electrical specifications.
RFI Immunity (IEC 1000-4-3)
Ground Continuity (IEC 1000-4-5)
Electrostatic Discharge (IEC 1000-4-2)
Flammability
80 ...1000 MHz, 10 V/m
2 kV shield to ground
8 kV air / 4 kV contact
Wiring Connector: 94V-0 Module Enclosure: 94V-
1
840 USE 100 00 11/2004
43
System Specifications
AC/DC Power
Supplies
The following table shows the Quantum AC/DC power supplies.
Fast Transients (IEC 1000-4-4)
Damped Oscillatory Transients
Surge Withstand Capability (Transients)
(IEC 1000-4-5)
Non Periodic Peak Input Voltage
2 kV common mode
2 kV common mode
1 kV differential mode
2 kV common mode
1 kV differential mode
2.3 times nominal for 1.3 ms (Nominal = DC average or AC peak)
I/O Modules -
Table 1
The following table shows the Quantum function I/O modules with operating voltages less than 24 Vac or Vdc.
Fast Transients (IEC 1000-4-4)
Damped Oscillatory Transients
Surge Withstand Capability (Transients)
(IEC 1000-4-5)
0.5 kV common mode
1 kV common mode
0.5 kV differential mode
1 kV common mode
0.5 kV differential mode
I/O Modules -
Table 2
The following table shows the Quantum I/O modules with operating voltages between 24 and 48 Vac or Vdc.
Fast Transients (IEC 1000-4-4)
Damped Oscillatory Transients
Surge Withstand Capability (Transients)
(IEC 1000-4-5)
1 kV
2 kV common mode
1 kV differential mode
1 kV common mode
0.5 kV differential mode
I/O Modules -
Table 3
The following table shows the Quantum I/O modules with operating voltages greater than 48 Vac or Vdc.
Fast Transients (IEC 1000-4-4)
Damped Oscillatory Transients
Surge Withstand Capability (Transients)
(IEC 1000-4-5)
2 kV
2 kV common mode
1 kV differential mode
2 kV common mode
1 kV differential mode
44
840 USE 100 00 11/2004
Operating
Conditions
System Specifications
The following table shows the Quantum operating conditions.
Temperature 0 ... 60° C (32 ... 140° F)
Humidity 0 ... 95 percent RH non-condensing at 60° C
Chemical
Interactions
Altitude
Enclosures and terminal strips are made of polycarbonates. This material can be damaged by strong alkalis and various hydrocarbons, esters, halogens and ketones in combination with heat. Common products containing these include detergents, PVC products, petroleum products, pesticides, disinfectants, paint removers, and spray paints.
2,000 meters. When the altitude exceeds this, reduce the 60°C maximum operating temperature by 6°C per 1000 meters of additional elevation.
Vibration
Shock
10 ... 57 Hz at 0.075 mm d.a. 57 ... 150 Hz at 1 g
+/-15 g peak, 11 ms, half-sine wave
Gas Resistance in Conformally
Coated Modules
The following table shows gas resistance data for conformally coated Quantum modules.
Mixed Flowing Gas Test, 22 days exposure
Standard
EIA364-65 Level lll
ISA-S71.04 (GX
Severe)
Gas
CL
2
(Chlorine)
Test Requirement
20 PPB, +/- 5 PPB
Actual Exposure
20 PPB
NO
2
(Nirtic Oxide) 200 PPB, +/- 50 PPB 1250 PPB
H
2
S (Hydrogen Sulfide) 100 PPB, +/- 20 PPB 100 PPB
SO
2
(Sulfur Oxide) N/A 300 PPB
CL
2
(Chlorine) 10 PPB 20 PPB
1250 PPB NO
2
((Nitric Oxide) 1250 PPB
H
2
S (Hydrogen Sulfide) 50 PPB
O
2
(Sulfur Oxide) 300 PPB
100 PPB
300 PPB
Storage
Conditions
The following table shows the Quantum storage conditions.
Temperature
Humidity
Free Fall
-40 ... 85° C (-40 ... 185° F)
0 ... 95 percent RH non-condensing at 60° C
3 ft. (1 m)
840 USE 100 00 11/2004
45
System Specifications
Agency
Approvals
The following table shows the agency approvals.
UL 508
CSA 22.2-142
Factory Mutual Class 1, Div 2
European Directives (CE) 89/336/EEC, 73/23/EEC and amendments
1RWH All Quantum system modules contain static-sensitive components. Each module is labeled with the following static-sensitive symbol.
The following figure shows the static sensitive symbol.
46
840 USE 100 00 11/2004
Quantum Module Specifications and Configuration
IV
At a Glance
Overview
What’s in this
Part?
This part provides information on Quantum module specifications as well as configuration of the modules.
This part contains the following chapters:
16
17
18
12
13
14
15
Chapter
5
6
7
10
11
8
9
Chapter Name
Hardware Specifications for the Quantum Modules
Power Supply Modules
CPU Modules
Quantum Field Bus Modules
Distributed I/O (DIO) for the Quantum Modules
Quantum Remote I/O Communication Modules
Quantum Modbus Plus Network Option Modules
Quantum Modbus Plus Networking on Fiber Module
Quantum Ethernet Modules
Intelligent/Special Purpose Modules for the Quantum
Quantum Intrinsically Safe Analog/Digital, Input/Output Modules
Quantum Simulator Modules
Quantum Battery Module
Quantum I/O Modules
429
Page
840 USE 100 00 11/2004
47
Specifications and Configuration
48
840 USE 100 00 11/2004
Hardware Specifications for the
Quantum Modules
5
Quantum Hardware Specifications
Overview
Power Supply
Specifications z z z z z
This section shows the specifications for Quantum hardware modules including:
Power Supplies
CPUs
Networking
Intelligent/Special Purpose
I/O
The following table shows the power supplies for local and RIO Drops.
Part Number Source Voltage Type
140CPS11100 115 ... 230 Vac Standalone
140CPS11400 115 ... 230 Vac
140CPS11410 115 ... 230 Vac
Standalone
Standalone/Summable
140CPS11420 115 ... 230 Vac
140CPS12400 115 ... 230 Vac
140CPS12420 115 ... 230 Vac
140CPS21100 24 Vdc
Standalone/Summable
Standalone/Redundant
Standalone/Redundant
Standalone
140CPS21400 24 Vdc
140CPS22400 24 Vdc
140CPS41400 48 Vdc
140CPS42400 48 Vdc
140CPS51100 100 ... 150 Vdc
140CPS52400 125 Vdc
Standalone/Summable
Standalone/Redundant
Standalone/Redundant
Standalone/Redundant
Standalone
Standalone/Redundant
8 A
8 A
8 A
8 A
3 A
8 A
Bus Current Provided
3 A
8 A
8 A
11A/16A/20A
3 A
8A/10A/11A
3 A
49
840 USE 100 00 11/2004
Hardware Specifications
CPU
Specifications
The following table shows specifications for the CPUs.
Part Numbers
140CPU11302
140CPU11303
140CPU21304
140CPU42402
140CPU43412
140CPU43412A
140CPU53414
140CPU53414A
Max IEC
Program
109 k
368 k
606 k
570 k
896 k
896 k
2.5 M
2.5 M
SRAM
Size
256 k
512 k
768 k
2 M
2 M
2 M
4 M
4 M
Ladder
Logic
8 k
16 k
Available
Registers
10 k
10 k
Bus Current
Required
780 mA
790 mA
32 k or 48 k 64 k or 32 k 900 mA
64 k 64 k 1.8 A
64 k
64 k
57 k
57 k
1.8 A
1.25 A
64 k
64 k
57 k
57 k
1.8 A
1.25A
Networking
Modules – RIO
The following table shows specifications for RIO Networking modules.
Part Numbers (RIO)
140CRA93100
140CRA93200
140CRP93100
140CRP93200
Drop Location
Remote (Drop)
Remote (Drop)
Local (Head)
Local (Head)
1
2
1
2
Communication
Channel(s)
Bus Current
Provided
600 mA
750 mA
600 mA
750 mA
Field Bus
Modules
The following table shows specifications for field bus modules.
Part Number Communication Channel(s)
140CRP81100 1 Profibus port, 1 RS-232 port (db 9 pin)
140EIA92100 1 AS-i
140NOA61100 1InterBus, LED display, gen 3
140NOA61110 1 InterBus, 7 segment display, gen 3
140NOA62200 1 InterBus, LED, gen 4
140NOL91100 2 free topology, twisted pair; 78,000 BPS, LonWorks
140NOL91110 2 linear topology, twisted pair, transformer isolated,
78,000 BPS, LonWorks
140NOL91120 2 linear topology, twisted pair, transformer isolated, 1.25
BBPS, LonWorks
Bus Current
Required
1.2 A
250mA
700 mA
700 mA
800 mA
400 mA
400 mA
400 mA
50
840 USE 100 00 11/2004
Networking
Modules – DIO
(Modbus Plus)
Hardware Specifications
The following table shows specifications for DIO Networking modules.
Part Numbers (DIO) Source Voltage Communication Channel(s) Bus Current
Provided
140CRA21110
140CRA21210
115 Vac
115 Vac
1
2
3 A
3 A
140CRA21120
140CRA21220
24 Vdc
24 Vdc
1
2
3 A
3 A
Networking
Modules –
Ethernet
The following table shows specifications for ethernet modules.
Part Numbers Communication Channels
140NOE21100 1 10BASE-T Ethernet network (RJ-45) port
140NOE25100 1 10BASE-FL Ethernet network (ST-style) port
140NOE31100 1 10BASE-T Ethernet network (RJ-45) port
140NOE35100 2 10BASE-FL Ethernet network (ST-style) ports
140NOE51100 1 10BASE-T Ethernet network (RJ-45) port
140NOE55100 2 10BASE-FL Ethernet network (ST-style) ports
140NOE771xx 1 10/100 BASE-TX Ethernet network (RJ-45) port
1 100 BASE-FX (MT-RJ connector) fiber optic port
Bus Current
Required
1 A
1 A
1 A
1 A
1 A
1 A
750 mA
Networking
Modules – NOM
The following table shows specifications for Modbus Plus NOM Networking modules.
Part Numbers (NOM) Communication Channels
140NOM21100 1, twisted pair, 1 Modbus, 9-pin D-Sub
140NOM21200
140NOM25200
2, twisted pair, 1 Modbus, 9-pin D-Sub
Bus Current Required
780 mA
780 mA
2, fiber optic (ST-style); 1 Modbus (RJ-45) 780 mA
Intelligent/
Special Purpose
– Hot Standby
Module
The following table shows specifications for the Hot Standby module.
Part Number Communication Channel Bus Current Required Special Features
140CHS11000 Fiber Optic 700 mA Use kit P/N -
140 CHS21000
840 USE 100 00 11/2004
51
Hardware Specifications
Counter Modules The following table shows specifications for the high speed Counter modules.
Part Number Function
140EHC10500 High Speed
Counter (100 kHz)
140EHC20200 High Speed
Counter (500 kHz)
Points/
Channels
5
2
Bus Current
Required
250 mA
Special Features
650 mA
35 kHz @ 24 Vdc 100 kHz @ 5 Vdc
500 kHz, Incremental or Quadrature
ASCII Interface
Module
The following table shows specifications for the ASCII Interface Module.
Part
Numbers
Function
140ESI06210 Intelligent, Bi-directional,
ASCII Interface
Communication
Channels
Bus Current
Required
2 300 mA
Special
Features
1 Port @
19.2 kbps
High Speed
Interrupt Module
The following table shows specifications for the High Speed Interrupt module.
Part Number Function Points/Channels Bus Current
Required
140HLI34000 High Speed, Latch, and Interrupt 16 400 mA
Single Axis
Motion Modules
The following table shows specifications for the Single Axis Motion modules.
Part Numbers Function
140MSB10100 Motion Controller, Single
Axis Bi-directional,
ASCII Interface
1
Channels Bus Current
Required
750 mA
140MSC10100 Motion Controller, Single
Axis
1 1000 mA
Special Features
Dual Encoder
Feedback
Dual Encoder
Feedback and
Resolver Feedback
52
840 USE 100 00 11/2004
I/O Modules –
Discrete In
Hardware Specifications
The following table shows specifications for the Discrete In modules.
Type/Part
Number
Function
140DAI34000 24 Vac
140DAI35300 24 Vac
140DAI44000 48 Vac
140DAI45300 48 Vac
140DAI54000 115 Vac
140DAI54300 115 Vac
140DAI55300 115 Vac
140DAI74000 230 Vac
140DAI75300 230 Vac
140DDI15310 5 Vdc
140DDI35300 24 Vdc
140DSI35300 24 Vdc
140DDI35310 24 Vdc
140DDI36400 24 Vdc
32
96
140DDI67300 125 Vdc 24
140DDI84100 10 ... 60 Vdc 16
140DDI85300 10 ... 60 Vdc 32
140DSI35300 24 Vdc 32
32
16
32
32
32
32
16
32
16
16
Points/
Channels
16
32
8
8
8
2
8
16
8
8
8
8
8
N/A
N/A
8
N/A
8
Points per
Group
N/A
8
Bus Current
Required
180 mA
250 mA
180 mA
250 mA
180 mA
180 mA
250 mA
180 mA
250 mA
170 mA
330 mA
250 mA
330 mA
270 mA
200 mA
200 mA
300 mA
250 mA
Special
Features
Isolated
Grouped
Isolated
Grouped
Isolated
Grouped
Grouped
Islolated
Grouped
Grouped
Grouped
Supervised inputs grouped
Grouped
Grouped
Grouped
Grouped
Grouped
Supervised
Inputs Grouped
840 USE 100 00 11/2004
53
Hardware Specifications
I/O Modules –
Discrete Out
The following table shows specifications for the Discrete Out modules.
Special Features Type/Part
Number
140DAO84000
Function
24 ... 230 Vac
Points/
Channels
16
Points per
Group
N/A
Bus
Current
Required
350 mA
140DAO84010 24 ... 115 Vac 16
140DAO84210 115 ... 230 Vac 16
140DAO84220 24 ... 48 Vac
140DAO85300 230 Vac
140DDO15310 5 Vdc
140DDO35300 24 Vdc
140DDO35301 24 Vdc
140DDO35310 24 Vdc
140DDO36400 24 Vdc
140DDO84300 10 ... 60 Vdc
140DDO88500 24 ... 125 Vdc 12
140DRA84000 N.O. Relay
140DRC83000 N.O./N.C.
Relay
140DVO85300 10 ... 30 Vdc
16
32
32
32
32
32
96
16
16
8
32
N/A
4
4
8
8
8
8
8
16
8
6
1
1
8
350 mA
350 mA
350 mA
1A
350 mA
330 mA
250 mA
330 mA
250 mA
160 mA
6 points:
375 mA
12 points:
650 mA
1,100 mA
560 mA
500 mA
4 A per point, isolated
4 A per point, isolated
4 A per point, group fused
4 A per point, group fused
1 A per point, group fused
0.5 A per point, group fused
0.5 A per point, group fused
0.5 A per point
0.5 A per point, group fused
0.5 A per point, group fused
2 A per point, group fused
0.5 A per point with short circuit protection,
Group fused
2 A per point
5 A per point
0.5 A per point, verified output, group fused
54
840 USE 100 00 11/2004
I/O Modules –
Discrete In/Out
Hardware Specifications
The following table shows specifications for the Discrete In/Out modules.
Type/Part
Number
Type/Part
Number
140DAM59000 115 Vac
Points/ channels
16 In
8 Out
140DDM39000 24 Vdc
140DDM69000 125 Vdc
16 In
8 Out
4 In
4 Out
8
4
8
4
Points per group
Bus current required
Special features
250 mA
330 mA
0.5 A per point on outputs, grouped fused
0.5 A per point on outputs, grouped fused
4
N/A
350 mA Inputs: Grouped
Outputs: 4 A per point isolated
I/O Modules –
Analog In/Out
The following table shows specifications for the Analog In/Out module.
Type/Part
Number
Function
140AMM09000 Inputs
Vdc:
+/- 10
+/- 5
0 ... 10
0 ... 5
1 ... 5 mA:
+/- 20
0 ... 20
4 ... 20
Outputs
4 ... 20 mA
Points/
Channels
4 In
Points per group
Bus Current
Required
Special Features
N/A 350 mA Mixed inputs, current or voltage
2 Out N/A Isolated
840 USE 100 00 11/2004
55
Hardware Specifications
I/O Modules –
Analog In
The following table shows specifications for the Analog In modules.
Type/Part
Number
Function
140ACI03000 4 ... 20 mA
1 ... 5 Vdc
140ACI04000 0 ...25 mA
0 ... 20 mA
4 ... 20 mA
140ARI03010 RTD: Pt, Ni,
Ohms
140AVI03000 0 ... 20 mA,
+/- 20 mA
+/- 10 Vdc
+/- 5 Vdc
140ATI03000 T/C: B, E, J,
K, R, S, T
Points/
Channels
8
16
Points per
Group
Bus Current
Required
Special Features
1 240 mA
16 360 mA
Mixed inputs, current or voltage
High density
8
8
8
1
1
1
200 mA
280 mA
280 mA
IEC/American
Mixed inputs, current or voltage
CJC INT/EXT
I/O Modules –
Analog Out
The following table shows specifications for the Analog Out modules.
Type/ Part
Number
Function
140ACO02000 4 ... 20 mA
140ACO13000 0 ... 25 mA
0 ... 20 mA
4 ... 20 mA
140AVO02000 0 ... 10 Vdc,
+/1 10 Vdc
0 ... 5 Vdc
+/- 5 Vdc
4
8
Points/
Channels
Points per group
N/A
8
Bus Current
Required
Special Features
480 mA
550 mA
Channels isolated
High density
4 N/A 700 mA Mixed outputs
56
840 USE 100 00 11/2004
Hardware Specifications
Intrinsic Safe
Analog Modules
The following table shows specifications for the Intrinsic Safe analog modules.
Type/Part
Number
Function
140AII33000 TC: B, E, J,
K, R, S, T
RTD: Pt, Ni
Ohms
8
Points/
Channels
8 140AII33010 0 ... 25 mA
0 ... 20 mA
4 ... 20 mA
140AIO33000 0 ... 25 mA
0 ... 20 mA
4 ... 20 mA
8
Points per
Group
Bus Current
Required
Special Features
1 400 mA CJC INT/EXT
IEC/American
8
8
1.5 A
2.5 A
Mixed inputs, current. Internal power supply.
Internal power supply.
Intrinsic Safe
Discrete
Modules
The following table shows the specifications for the Intrinsic Safe discrete modules.
Type/Part
Number
Function
140DII33000 Discrete In
140DIO33000 Discrete Out
Points/
Channels
8
8
Points per
Common
Bus Current
Required
Special
Features
8 400 mA
8 2.2 A
Internal power supply
Internal power supply
Miscellaneous
Modules
The following table shows specifications for miscellaneous modules.
Type/Part Number
140XBE10000
140XCP90000
140XSM01000
Function
Backplane expander
Battery backup
Analog simulator
Bus Current Required
500 mA
None
None
840 USE 100 00 11/2004
57
Hardware Specifications
58
840 USE 100 00 11/2004
Power Supply Modules
6
At a Glance
Overview
What’s in this
Chapter?
The following chapter describes the Quantum power supplies, including: specifications, LED indicators and descriptions, and wiring diagrams. Where applicable, it includes operating curves and hold-up capacitor timing charts.
This chapter contains the following topics:
Topic
140CPS11100 AC Power Supply 115/230 Vac 3 A Module
140CPS11100 AC Power Supply 115/230 Vac 3 A Module (PV01 or Greater)
140CPS11400 AC Power Supply, 115/230 Vac, 8 A Module
Page
140CPS11410 AC Summable Power Supply 115/230 Vac, 8 A
140CPS11420 AC Summable Power Supply 115/230 Vac, 11 A
140CPS12400 AC Redundant Power Supply, 115/230 Vac 8 A Module
140CPS12420 AC Redundant Power Supply, 115/230 Vac 11 A Module
140CPS21100 DC Power Supply, 24 Vdc, 3 A Module
140CPS21400 DC Summable Power Supply, 24 Vdc, 8 A Module
140CPS22400 DC Redundant Power Supply, 24 Vdc, 8 A Module
140CPS41400 DC Summable Power Supply, 48 Vdc, 8 A Module
140CPS42400 DC Redundant Power Supply, 48 Vdc, 8 A Module
140CPS51100 DC Power Supply, 125 Vdc, 3 A Module
140CPS52400 DC Standalone/Redundant Power Supply, 125 Vdc, 8 A
840 USE 100 00 11/2004
59
Power Supplies
140CPS11100 AC Power Supply 115/230 Vac 3 A Module
Overview
Power Supply
Module
The following provides information on the AC Power Supply, 115/230 Vac, 3 A module (Product Version 01 or greater).
The following figure shows the power supply module components.
LED Area
Model Number
Module Description
Color Code
Customer Identification Label
(Fold label and place it inside door)
Removable Door
Field Wiring
Connector
Field Wiring
Connector Cover
5
6
7
1
2
3
4
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
4
5
1
2
3
6
7
115Vac
115Vac
AC L
AC N
X
1RWH When field wiring the power supply module, the maximum wire size that should be used is 1 - 14 AWG or 2 - 16 AWG; the minimum is 20 AWG.
60
840 USE 100 00 11/2004
Specifications
Power Supplies
The following table shows the specifications for the CPS11100 115/230 VAC power supply module.
Specifications
Input Requirements
Input Voltage
Input Frequency
Input Voltage Total Harmonic
Distortion
Input Current
Inrush Current
VA Rating
Input Power Interruption
Fusing (external)
93 ... 132 Vac (jumper installed)
170 ... 264 Vac (no jumper)
47 ... 63 Hz
Less than 10% of the fundamental ms value
0.4 A @ 115 Vac. 0.2 A @ 230 Vac
13 A @ 115 Vac. @ 25°C first power up
23 A @ 230 Vac. @ 25°C first power up
50 VA
1/2 cycle @ full load and minimum rated line voltage / frequency. No less than 1 second between interruptions.
1.5 A slo-blo recommended (Part # 043502515 or equivalent)
Output to Bus
Voltage
Maximum Current
Minimum Current
5.1 Vdc
3 A
None required
Over Current, Over Voltage Protection
General
Field Wiring Connector (included) 7 point terminal strip (Part # 043506326)
Internal Power Dissipation 6 Watts typ.
Operating Mode Standalone
840 USE 100 00 11/2004
61
Power Supplies
LED Indicator and Description
The following figure shows the CPS11100 LED indicator.
Pwr ok
62
1RWH For "Closed System" installations, connector 140XTS00 500 must be used
(see
S
).
The following table shows the CPS11100 LED description.
LED Description
LEDs Color
Pwr ok Green
Indication when On
Power is supplied to the bus.
Wiring Diagram
1
4
5
2
3
6
7
The following figure shows the CPS11100 wiring diagram.
Internally connected
}
Do not connect any external wiring to these points
Install jumper for 115 Vac operation only
AC L
AC N
1RWH See S for power and grounding wiring guidelines and operational information.
840 USE 100 00 11/2004
Power Supplies
140CPS11100 AC Power Supply 115/230 Vac 3 A Module (PV01 or Greater)
Overview
Power Supply
Module
The following provides information on the AC Power Supply, 115/230 Vac, 3 A module (PV01 or greater).
The following figure shows the power supply module (PV01 or greater) components.
LED Area
Model Number
Module Description
Color Code
Customer Identification Label
(Fold label and place it inside door)
Removable Door
Field Wiring
Connector
Field Wiring
Connector Cover
5
6
7
1
2
3
4
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
4
5
1
2
3
6
7
115Vac
115Vac
AC L
AC N
X
1RWH When field wiring the power supply module, the maximum wire size that should be used is 1 - 14 AWG or 2 - 16 AWG; the minimum is 20 AWG.
840 USE 100 00 11/2004
63
Power Supplies
Specifications The following table shows the specifications for the CPS11100 115/230 VAC power supply module (PV01 or greater).
Specifications
Input Requirements
Input Voltage
Input Frequency
Input Voltage Total Harmonic
Distortion
Input Current
Inrush Current
VA Rating
Input Power Interruption
Fusing (external)
100 ... 276 Vac
47 ... 63 Hz
Less than 10% of the fundamental ms value
0.4 A @ 115 Vac. 0.2 A @ 230 Vac
10 A @ 115 Vac. 20 A @ 230 Vac
50 VA
1/2 cycle @ full load and minimum rated line voltage / frequency. No less than 1 second between interruptions.
1.5 A slo-blo recommended (Part # 043502515 or equivalent)
Output to Bus
Voltage
Maximum Current
Minimum Current
Protection
General
Field Wiring Connector
(included)
Internal Power Dissipation
Operating Mode
5.1 Vdc
3 A
0.3 A
Over Current, Over Voltage
7 point terminal strip (Part # 043506326)
2.0 + 3.0 x I
OUT
= Watts (where I
OUT
is in Amperes)
Standalone
64
840 USE 100 00 11/2004
LED Indicator and Description
Power Supplies
The following figure shows the CPS11100 (PV01 or greater) LED indicator.
Pwr ok
1RWH For "closed system" installations, connector 140XTS00 500 must be used
(see
S
).
The following table shows the CPS11100 (PV01 or greater) LED description.
LED Description
LEDs Color
Pwr ok Green
Indication when On
Power is supplied to the bus.
Wiring Diagram The following figure shows the CPS11100 (PV01 or greater) wiring diagram.
1
}
Internally connected. Do not connect any external wiring to these points.
2
3
Install jumper for 115 VAC operation only.
4
AC L
5
AC N
6
7
1RWH See S for power and grounding wiring guidelines and operational information.
65
840 USE 100 00 11/2004
Power Supplies
140CPS11400 AC Power Supply, 115/230 Vac, 8 A Module
Overview
Power Supply
Module
The following provides information on the AC Power Supply, 115/230 Vac, 8 A module.
The following figure shows the power supply module components.
LED Area
Model Number
Module Description
Color Code
Customer Identification Label
(Fold label and place it inside door)
Removable Door
Field Wiring
Connector
Field Wiring
Connector Cover
5
6
7
1
2
3
4
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
4
5
1
2
3
6
7
115Vac
AC L
AC N
X
1RWH When field wiring the power supply module, the maximum wire size that should be used is 1 - 14 AWG or 2 - 16 AWG; the minimum is 20 AWG.
66
840 USE 100 00 11/2004
Specifications
Power Supplies
The following table shows the specifications for the CPS11400 115/230 VAC power supply module.
Specifications
Input Requirements
Input Voltage
Input Frequency
Input Voltage Total Harmonic
Distortion
Less than 10% of the fundamental ms value
Input Current
Inrush Current
VA Rating
Input Power Interruption
Fusing (external)
93 ... 138 Vac. 170 ... 276 Vac
47 ... 63 Hz
1.1 A @ 115 Vac. 0.6 A @ 230 Vac
38 A @ 115 Vac. 19 A @ 230 Vac
130 VA
1/2 cycle @ full load and minimum-rated line voltage / frequency. No less than 1 second between interruptions.
2.0 A slo-blo recommended (Part # 57-0089-000 or equivalent)
Output to Bus
Voltage
Maximum Current
Minimum Current
5.1 Vdc
8 A @ 60° C (See the operating curve below)
None required
Over Current, Over Voltage Protection
General
Field Wiring Connector
(included)
Internal Power Dissipation
Operating Mode
7 point terminal strip (Part # 043506326)
6.0 + 1.5 x I
Standalone out
= Watts (where I out
is in Amperes)
840 USE 100 00 11/2004
67
68
Power Supplies
LED Indicator and Description
The following figure shows the CPS11400 LED indicator.
Pwr ok
The following table shows the CPS11400 LED description.
LED Description
LEDs
Pwr ok
Color
Green
Indication when On
Power is supplied to the bus.
Wiring Diagram and Operating
Curve
1
2
3
4
5
6
7
The following figures show the CPS11400 Wiring Diagram (left) and operating curve
(right).
Internally connected.
}
Do not connect any external wiring to these points.
Install jumper for 115 VAC operation only
AC L
AC N
12
10
8
6
4
2
40 45 50 55 60
Ambient Temperature (C)
1RWH See S for power and grounding wiring guidelines and operational information.
840 USE 100 00 11/2004
Power Supplies
140CPS11410 AC Summable Power Supply 115/230 Vac, 8 A
Overview
Power Supply
Module
The following provides information on the AC power supply, 115/230 Vac, 8 A module.
The following figure shows the power supply module and its components.
LED Area
Model Number
Module Description
Color Code
Customer Identification Label
(Fold label and place it inside door)
Removable Door
Field Wiring
Connector
Field Wiring
Connector Cover
5
6
3
4
7
1
2
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
4
5
1
2
3
6
7
$ODUP
5HOD\
115 VAC
115VAC
AC L
AC N
X
840 USE 100 00 11/2004
69
Power Supplies
Specifications The following table shows the specifications for the CPS11410 115/230 VAC power supply module.
Specifications
Input Requirements
Input Voltage
Input Frequency
Input Voltage Total Harmonic
Distortion
Input Current
Inrush Current
VA Rating
Input Power Interruption
Fusing (external)
93 ... 138 Vac. 170 ... 276 Vac
47 ... 63 Hz
Less than 10% of the fundamental rms value
1.1 A @ 115 Vac. 0.6 A @ 230 Vac
38 A @ 115 Vac. 19 A @ 230 Vac
130 VA
1/2 cycle @ full load and minimum rated line voltage / frequency. No less than 1 second between interruptions.
2.0 A slo-blo recommended (Part # 57-0089-000 or equivalent)
Output to Bus
Voltage
Maximum Current
Minimum Current
Protection
General
Field Wiring Connector
(included)
Internal Power Dissipation
Operating Mode
5.1 Vdc
8 A @ 60° C
None required
Over Current, Over Voltage
7 point terminal strip (Part # 043506326)
6.0 + 1.5 x I
OUT
= Watts (where I
Standalone / Summable
OUT
is in Amperes)
70
840 USE 100 00 11/2004
LED Indicator and Description
The following figure shows the CPS11410 LED indicator.
Pwr ok
Power Supplies
The following table shows the CPS11410 LED description.
LED Descripton
LEDs
Pwr ok
Color
Green
Indication when On
Power is supplied to the bus.
Wiring Diagram The following figures shows the 140CPS11410.
1
4
5
2
3
6
7
} Internally connected.
Do not connect any external wiring to these points.
AC L
AC N
Install jumper for 115 VAC operation only
1RWH See S for power and grounding wiring guidelines and operational information.
71
840 USE 100 00 11/2004
Power Supplies
140CPS11420 AC Summable Power Supply 115/230 Vac, 11 A
Overview
Power Supply
Module
The following provides information on the AC power supply, 115/230 Vac, 11 A module.
The following figure shows the power supply module and its components.
LED Area
CPS 114 20
PS 115/230 VAC
Model Number
Module Description
Color Code
Customer Identification Label
(Fold label and place it inside door)
Removable Door
Field Wiring
Connector
Field Wiring
Connector Cover
1
5
6
7
2
3
4
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
5
6
7
1
2
3
4
Alarm
Relay
115 VAC
115 VAC
AC L
AC N
X
72
840 USE 100 00 11/2004
Specifications
Power Supplies
The following table shows the specifications for the CPS11420 115/230 VAC power supply module.
Specifications
Input Requirements
Input Voltage
Input Frequency
Input Voltage Total Harmonic
Distortion
Input Current
93 ... 132 Vac.
170 ... 264 Vac
47 ... 63 Hz
Less than 10% of the fundamental rms value
Inrush Current @ 25° C (first power up)
VA Rating
Input Power Interruption
Fusing (external)
1.2 A @ 115 Vac.
0.7 A @ 230 Vac
≤
20 A @ 115 Vac.
≤
25 A @ 230 Vac
160 VA @ 11 A
1/2 cycle @ full load and minimum rated line voltage / frequency. No less than 1 second between interruptions.
2.0 A slo-blo recommended (Part # 57-0089-000 or equivalent)
Output to Bus
Voltage
Maximum Current
5.1 Vdc
Stand alone configuration: 11 A @ 60° C
Summable configuration (Two 140CPS11420): 20 A @ 60°
C (Total load capacity)
Summable configuration (One 140CPS11420 and one
140CPS11410): 16A @ 60° C (Total load capacity)
None required
Over Current, Over Voltage
Minimum Current
Protection
General
Field Wiring Connector
(included)
Internal Power Dissipation
Operating Mode
7 point terminal strip (Part # 043506326)
Less than 12 W at full load
Standalone / Summable
840 USE 100 00 11/2004
73
Power Supplies
LED Indicator and Description
The following figure shows the CPS11420 LED indicator.
Pwr ok
The following table shows the CPS11420 LED description.
LED Description
LEDs Color
Pwr ok Green
Indication when On
Power is supplied to the bus.
Wiring Diagram The following figures shows the CPS11420.
1
2
3
4
5
6
7
Power loss alarm
AC L
Install jumper for 115 VAC operation only
AC N
1RWH A normally closed relay contact rated at 220 Vac, 6A / 30 Vdc, 5A is available on terminals 1 and 2 of the power terminal strip. This contact set may be used to signal input power OFF. The relay will de-energize when input power drops below
8 Vdc.
1RWH See S for power and grounding wiring guidelines and operational information.
74
840 USE 100 00 11/2004
140CPS12400 AC Redundant Power Supply, 115/230 Vac 8 A Module
Power Supplies
Overview
Power Supply
Module
The following provides information on the AC redundant power supply, 115/230 Vac,
8 A module.
The following figure shows the power supply module components.
LED Area
Model Number
Module Description
Color Code
Customer Identification Label
(Fold label and place it inside door)
Removable Door
Field Wiring
Connector
Field Wiring
Connector Cover
5
6
7
1
2
3
4
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
4
5
1
2
3
6
7
115 VAC
115 VAC
AC L
AC N
X
1RWH When field wiring the power supply module, the maximum wire size that should be used is 1 - 14 AWG or 2 - 16 AWG; the minimum is 20 AWG.
840 USE 100 00 11/2004
75
Power Supplies
Specifications The following table shows the specifications for the CPS12400 PS 115/230 VAC power supply module.
Specifications
Input Requirements
Input Voltage
Input Frequency
Input Voltage Total Harmonic
Distortion
Input Current
Inrush Current
VA Rating
Input Power Interruption
Fusing (external)
93 ... 138 Vac. 170 ... 276 Vac
47 ... 63 Hz
Less than 10% of the fundamental rms value
1.1 A @ 115 Vac. 0.6 A @ 230 Vac
38 A @ 115 Vac. 19 A @ 230 Vac
130 VA
1/2 cycle @ full load and minimum rated line voltage / frequency. No less than 1 second between interruptions.
2.0 A slo-blo recommended (Part # 57-0089-000 or equivalent)
Output to Bus
Voltage
Maximum Current
Minimum Current
Protection
General
Field Wiring Connector
(included)
Internal Power Dissipation
Operating Mode
5.1 Vdc
8 A @ 60° C
None required
Over Current, Over Voltage
7 point terminal strip (Part # 043506326)
6.0 + 1.5 x I out
= Watts (where I out
is in Amperes)
Standalone / Redundant
76
840 USE 100 00 11/2004
LED Indicator and Description
The following figure shows the CPS12400 LED indicator.
Pwr ok
Power Supplies
The following table shows the CPS12400 LED description.
LED Description
LEDs Color
Pwr ok Green
Indication when On
Power is supplied to the bus.
Wiring Diagram The following figure shows the 140CPS12400 wiring diagram.
1
6
7
4
5
2
3
} Internally connected.
Do not connect any external wiring to these points.
AC L
Install jumper for 115 VAC operation only
AC N
1RWH See S for power and grounding wiring guidelines and operational information.
77
840 USE 100 00 11/2004
Power Supplies
140CPS12420 AC Redundant Power Supply, 115/230 Vac 11 A Module
Overview
Power Supply
Module
The following provides information on the AC redundant power supply, 115/230 Vac,
11 A module.
The following figure shows the power supply module components.
LED Area
&36
369$&
Model Number
Module Description
Color Code
Customer Identification Label
(Fold label and place it inside door)
Removable Door
Field Wiring
Connector
Field Wiring
Connector Cover
3
4
5
6
7
1
2
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
4
5
1
2
3
6
7
Power loss alarm
115 VAC
115 VAC
AC L
AC N
X
1RWH
When field wiring the power supply module, the maximum wire size that should be used is 1 - 14 AWG or 2 - 16 AWG; the minimum is 20 AWG.
78
840 USE 100 00 11/2004
Specifications
Power Supplies
The following table shows the specifications for the CPS12420 PS 115/230 VAC power supply module.
Specifications
Input Requirements
Input Voltage
Input Frequency
Input Voltage Total Harmonic
Distortion
Input Current
93 ... 132 Vac.
170 ... 264 Vac
47 ... 63 Hz
Less than 10% of the fundamental rms value
Inrush Current
VA Rating
Input Power Interruption
Fusing (external)
1.2 A @ 115 Vac
0.7 A @ 230 Vac
≤
20 A @ 115 Vac @ 25° C first power up
≤
25 A @ 230 Vac
160 VA @ 11 A
1/2 cycle @ full load and minimum rated line voltage / frequency. No less than 1 second between interruptions.
2.0 A slo-blo recommended (Part # 57-0089-000 or equivalent)
Output to Bus
Voltage
Maximum Current
5.1 Vdc
Standalone configuration: 11 A @ 60° C
Redundant configuration (two 140CPS12420): 10 A @ 60°
C (total load capacity)
Redundant configuration (one 140CPS12420 and one
140CPS22400): 8 A @ 60° C (total load capacity)
Redundant configuration (one 140CPS12420 and one
140CPS42400): 8 A @ 60° C (total load capacity)
None required
Over Current, Over Voltage
Minimum Current
Protection
General
Field Wiring Connector
(included)
Internal Power Dissipation
Operating Mode
7 point terminal strip (Part # 043506326)
Less than 12 W at full load
Standalone / Redundant
840 USE 100 00 11/2004
79
Power Supplies
LED Indicator and Description
The following figure shows the CPS12420 LED indicator.
Pwr ok
The following table shows the CPS12420 LED description.
LED Description
LEDs Color
Pwr ok Green
Indication when On
Power is supplied to the bus.
Wiring Diagram The following figure shows the CPS12420 wiring diagram.
1
2
3
4
5
6
7
Power loss alarm
AC L
Install jumper for 115 VAC operation only
AC N
1RWH A normally closed relay contact rated at 220 Vac, 6A / 30 Vdc, 5A is available on terminals 1 and 2 of the power terminal strip. This contact set may be used to signal input power OFF. The relay will de-energize when input power drops below
8 Vdc.
1RWH See S for power and grounding wiring guidelines and operational information.
80
840 USE 100 00 11/2004
Power Supplies
140CPS21100 DC Power Supply, 24 Vdc, 3 A Module
Overview
Power Supply
Module
The following provides information on the DC power supply, 24 Vdc, 3 A module.
The following figure shows the power supply module components.
LED Area
&36
369'&
Model Number
Module Description
Color Code
Customer Identification Label
(Fold label and place it inside door)
Removable Door
Field Wiring
Connector
Field Wiring
Connector Cover
3
4
5
6
7
1
2
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X 4
5
1
2
3
6
7
24Vdc-
24Vdc+
X
1RWH When field wiring the power supply module, the maximum wire size that should be used is 1 - 14 AWG or 2 - 16 AWG; the minimum is 20 AWG.
840 USE 100 00 11/2004
81
Power Supplies
Specifications The following table shows the specifications for the CPS21100 PS 24 VDC power supply module.
Specifications
Input Requirements
Input Voltage
Input Current
Inrush Current
Input Power Interruption
Fusing (external)
20 ... 30 Vdc
1.6 A
30 A
1.0 ms max @ 20 V. 20.0 ms max @ 24 V
2.5 A slo-blo recommended (Part # 043502516 or equivalent)
Output to Bus
Voltage
Maximum Current
Minimum Current
Protection
General
Field Wiring Connector (included)
Internal Power Dissipation
Operating Mode
5.1 Vdc
3 A
0.3 A
Over Current, Over Voltage
7 point terminal strip (Part # 043503328)
2.0 + 3 x I out
= Watts (where I out
is in Amperes)
Standalone
LED Indicator and Description
The following figure shows the CPS21100 LED indicator.
Pwr ok
82
The following table shows the CPS21100 LED description.
LED Description
LEDs Color
Pwr ok Green
Indication when On
Power is supplied to the bus.
840 USE 100 00 11/2004
Power Supplies
Wiring Diagram The following figure shows the 140CPS21100 wiring diagram.
1
4
5
2
3
6
7
Not used
Not used
-24 Vdc (Common)
+24 Vdc
Not used
Not used
1RWH See S for power and grounding wiring guidelines and operational information.
840 USE 100 00 11/2004
83
Power Supplies
140CPS21400 DC Summable Power Supply, 24 Vdc, 8 A Module
Overview
Power Supply
Module
The following provides information on the DC summable power supply, 24 Vdc, 8 A module.
The following figure shows the power supply module components.
LED Area
&36
369'&
Model Number
Module Description
Color Code
Customer Identification Label
(Fold label and place it inside door)
Removable Door
Field Wiring
Connector
Field Wiring
Connector Cover
3
4
5
6
7
1
2
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
5
6
7
3
4
1
2
Alarm
Relay
24Vdc-
24Vdc+
+ cap
-
X
1RWH When field wiring the power supply module, the maximum wire size that should be used is 1 - 14 AWG or 2 - 16 AWG; the minimum is 20 AWG.
84
840 USE 100 00 11/2004
Specifications
Power Supplies
The following table shows the specifications for the 140CPS21400 PS 24 Vdc power supply module.
Specifications
Input Requirements
Input Voltage
Input Current
Inrush Current
Input Ripple
20 ... 30 Vdc
3.8 A max
25 A @ 24 Vdc. 14 A @ 20 Vdc
2.4 Vdc max, 94 ... 189 Hz
Input Power Interruption 1 ms max @ 24 Vdc (see the hold-up capacitor timing chart)
Fusing (external) 5.0 A slo-blo recommended (Part # 043502405 or equivalent)
Output to Bus
Voltage
Maximum Current
Minimum Current
5.1 Vdc
8 A
None required
Over Current, Over Voltage Protection
General
Field Wiring Connector 7 point terminal strip (Part # 043503328)
Internal Power Dissipation 6.0 + 1.8 x I
OUT
= Watts (where I
OUT
is in Amperes)
Operating Mode Standalone / Summable
LED Indicator and Description
The following figure shows the CPS21400 LED indicator.
Pwr ok
840 USE 100 00 11/2004
The following table shows the CPS21400 LED description.
LED Description
LEDs Color
Pwr ok Green
Indication when On
Power is supplied to the bus.
85
86
Power Supplies
Wiring Diagram and Timing Chart
1
4
5
2
3
6
7
The following figures show the CPS214 wiring diagram (left) and the hold-up capacitor timing chart (right).
} Power Loss
Alarm
-24 Vdc (Common)
+24 Vdc
+
-
Capacitor
(Optional)
100
90
Capacitor Size (millifarads)
100 68 47
22
80
70
Times/ms 60
50
40
30
20
10
0
20 21 22 23 24 25 26 27 28 29 30
Input Voltage
10
5.8
1
0
4.7
2.2
Capacitor
Size
(millifarads)
1RWH
A normally closed relay contact rated at 220 Vac, 6A / 30 Vdc, 5A is available on terminals 1 and 2 of the power terminal strip. This contact set may be used to signal input power OFF. The relay will de-energize when input power drops below 8 Vdc.
Tolerance to input interruptions may be increased by adding a ≥ 50 Vdc electrolytic capacitor between 5 and 6 of the power terminal strip. Refer to the hold-up capacitor timing chart for capacitor values.
1RWH See S for power and grounding wiring guidelines and operational information.
840 USE 100 00 11/2004
Power Supplies
140CPS22400 DC Redundant Power Supply, 24 Vdc, 8 A Module
Overview
Power Supply
Module
The following provides information on the DC Redundant Power Supply, 24 Vdc, 8
A module.
The following figure shows the power supply module components.
LED Area
&36
369'&
Model Number
Module Description
Color Code
Customer Identification Label
(Fold label and place it inside door)
Removable Door
Field Wiring
Connector
Field Wiring
Connector Cover
5
6
7
1
2
3
4
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X 4
5
1
2
3
6
7
Alarm
Relay
24Vdc-
24Vdc+
+ cap
-
X
1RWH When field wiring the power supply module, the maximum wire size that should be used is 1 - 14 AWG or 2 - 16 AWG; the minimum is 20 AWG.
840 USE 100 00 11/2004
87
Power Supplies
Specifications The following table shows the specifications for the 24 Vdc, 8 A DC redundant power supply.
Specifications
Input Requirements
Input Voltage
Input Current
Inrush Current
Input Ripple
Input Power Interruption
Fusing (external)
20 ... 30 Vdc
3.8 A max
25 A @ 24 Vdc. 14 A @ 20 Vdc
2.4 Vdc max, 94 ... 189 Hz
1 ms max @ 24 Vdc
5.0 A slo-blo recommended (Part # 043502405 or equivalent)
Output to Bus
Voltage
Current
Protection
General
Surge Withstand
Field Wiring Connector
Internal Power Dissipation
Operating Mode
5.1 Vdc
8 A
Over Current, Over Voltage
2.3 x Maximum Rated Input Voltage for 1.3 ms
7 point terminal strip (Part # 043503328)
6.0 + 1.8 x I out
= Watts (where I out
is in Amperes)
Standalone / Redundant
LED Indicator and Description
The following figure shows the CPS22400 LED indicator.
Pwr ok
88
The following table shows the CPS22400 LED description.
LED Description
LEDs Color
Pwr ok Green
Indication when On
Power is supplied to the bus.
840 USE 100 00 11/2004
Power Supplies
Wiring Diagram and Timing Chart
The following figures show the 140CPS22400 wiring diagram (left) and the
140CPS22400 hold-up capacitor timing chart (right).
1
4
5
2
3
6
7
} Power Loss
Alarm
-24 Vdc (Common)
+24 Vdc
+
-
Capacitor
(Optional)
100
Capacitor Size (millifarads)
100 68 47
90
22
80
70
Times/ms
60
50
40
30
20
10
0
20 21 22 23 24 25 26 27 28 29 30
Input Voltage
10
5.8
1
0
4.7
2.2
Capacitor
Size
(millifarads)
1RWH
A normally closed relay contact rated at 220 Vac, 6A / 30 Vdc, 5A is available on terminals 1 and 2 of the power terminal strip. This contact set may be used to signal input power OFF, or a power supply failure. The relay will de-energize when input power drops below 8 Vdc.
Tolerance to input interruptions may be increased by adding a ≥ 50 Vdc electrolytic capacitor between 5 and 6 of the power terminal strip. Refer to the hold-up capacitor timing chart (above) for capacitor values.
1RWH See S for power and grounding wiring guidelines and operational information.
89
840 USE 100 00 11/2004
Power Supplies
140CPS41400 DC Summable Power Supply, 48 Vdc, 8 A Module
Overview
Power Supply
Module
The following provides information on the DC summable power supply, 48 Vdc, 8 A module.
The following figure shows the power supply module components.
LED Area
&36
369'&
Model Number
Module Description
Color Code
Customer Identification Label
(Fold label and place it inside door)
Removable Door
Field Wiring
Connector
Field Wiring
Connector Cover
3
4
5
6
7
1
2
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
5
6
7
3
4
1
2
Alarm
Relay
48Vdc-
48Vdc+
+ cap
-
X
1RWH When field wiring the power supply module, the maximum wire size that should be used is 1 - 14 AWG or 2 - 16 AWG; the minimum is 20 AWG.
90
840 USE 100 00 11/2004
Specifications
Power Supplies
The following table shows the specifications for the CPS41400, 48 VDC power supply module.
Specifications
Input Requirements
Input Voltage
Input Current
Inrush Current
Input Power Interruption
Fusing (external)
40 ... 72 Vdc
1.2 A @ 48 Vdc
25 A @ 40 Vdc
13 ms @ 48 Vdc
2.0 A medium time-lag recommended (Part # 57-0089-
000 or equivalent)
Output to Bus
Voltage
Current
Protection
General
Field Wiring Connector
Internal Power Dissipation
Operating Mode
5.1 Vdc
8 A (see operating curve)
Over Current, Over Voltage
7 point terminal strip (Part # 043503328)
15.6 W @ 8 A
Standalone / Summable
LED Indicator and Description
The following figure shows the CPS41400 LED indicator.
Pwr ok
840 USE 100 00 11/2004
The following table shows the CPS41400 LED description.
LED Description
LEDs Color
Pwr ok Green
Indication when On
Power is supplied to the bus.
91
92
Power Supplies
Wiring Diagram
1
2
3
4
5
6
7
The following figure shows the CPS41400 wiring diagram.
}
Power Loss
Alarm
-48 ... -60 Vdc (Common)
+48 ... +60 Vdc
+
-
Capacitor
(Optional)
1RWH
A normally closed relay contact rated at 220 Vac, 6A / 30 Vdc, 5A is available on terminals 1 and 2 of the power terminal strip. This contact set may be used to signal input power OFF, or a power supply failure.
1RWH See S for power and grounding wiring guidelines and operational information.
Operating Curve and Timing Chart
The following figures show the CPS41400 operating curve (left) and the hold-up capacitor timing chart (right).
Capacitor size/mF
47 22 10 6.8
4.7
12
100
90 2.2
10
8
6
4
2
80
70
60
1
0
50
40
40 45 50 55
Ambient Temperature (C)
60
30
20
10
0
40 45 50 55
Input Voltage
60 65 70
1RWH
Tolerance to input interruptions may be increased by adding a
≥
80 Vdc electrolytic capacitor between 5 and 6 of the power terminal strip. Refer to the hold-up capacitor timing chart (above) for capacitor values.
840 USE 100 00 11/2004
Power Supplies
140CPS42400 DC Redundant Power Supply, 48 Vdc, 8 A Module
Overview
Power Supply
Module
The following provides information on the DC redundant power supply, 48 Vdc, 8 A module.
The following figure shows the power supply module components.
LED Area
&36
369'&
Model Number
Module Description
Color Code
Customer Identification Label
(Fold label and place it inside door)
Removable Door
Field Wiring
Connector
Field Wiring
Connector Cover
5
6
7
1
2
3
4
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
5
6
7
1
2
3
4
Alarm
Relay
48Vdc-
48Vdc+
+ cap
-
X
1RWH When field wiring the power supply module, the maximum wire size that should be used is 1 - 14 AWG or 2 - 16 AWG; the minimum is 20 AWG.
1RWH Tolerance to input interruptions may be increased by adding an 80 Vdc electrolytic capacitor between 5 and 6 of the power terminal strip. Refer to the holdup capacitor timing chart (above) for capacitor values.
840 USE 100 00 11/2004
93
Power Supplies
Specifications The following table shows the specifications for the 140CPS42400 PS 48 VDC RED power supply module.
Specifications
Input Requirements
Input Voltage
Input Current
Inrush Current
Input Power Interruption
Fusing (external)
40 ... 72 Vdc
1.3 A @ 48 Vdc
25 A @ 48 Vdc
13 ms @ 48 Vdc
2.0 A medium time-lag recommended (Part # 57-0089-
000 or equivalent)
Output to Bus
Voltage
Current
Protection
General
Field Wiring Connector
Internal Power Dissipation
Operating Mode
5.1 Vdc
8 A (see operating curve)
Over Current, Over Voltage
7 point terminal strip (Part # 043503328)
17.2 W @ 8 A
Standalone / Redundant
LED Indicator and Description
The following figure shows the CPS42400 LED indicator.
Pwr ok
94
The following table shows the CPS42400 LED description.
LED Description
LEDs Color
Pwr ok Green
Indication when On
Power is supplied to the bus.
840 USE 100 00 11/2004
Power Supplies
Wiring Diagram
1
2
3
6
7
4
5
The following figure shows the CPS42400 wiring diagram.
}
Power Loss
Alarm
-48 ... -60 Vdc (Common)
+48 ... +60 Vdc
+
-
Capacitor
(Optional)
1RWH
See
S
for power and grounding wiring guidelines and operational information.
1RWH
A normally closed relay contact rated at 220 Vac, 6A / 30 Vdc, 5A is available on terminals 1 and 2 of the power terminal strip. This contact set may be used to signal input power OFF, or a power supply failure.
Operating Curve and Timing Chart
The following figures show the CPS42400 operating curve (left) and the hold-up capacitor timing chart (right).
Capacitor size/mF
12
10
8
6
4
2
40 45 50 55
Ambient Temperature (C)
60
100
90
80
70
60
50
40
30
20
10
0
40
47
45
22
50
10 6.8
55
Input Voltage
60
4.7
65 70
2.2
1
0
1RWH Tolerance to input interruptions may be increased by adding a ≥ 80 Vdc electrolytic capacitor between 5 and 6 of the power terminal strip. Refer to the hold-up capacitor timing chart (above) for capacitor values.
95
840 USE 100 00 11/2004
Power Supplies
140CPS51100 DC Power Supply, 125 Vdc, 3 A Module
Overview
Power Supply
Module
The following provides information on the DC power supply, 125 Vdc, 3 A module.
The following figure shows the power supply module components.
LED Area
&36
369'&
Model Number
Module Description
Color Code
Customer Identification Label
(Fold label and place it inside door)
Removable Door
Field Wiring
Connector
Field Wiring
Connector Cover
3
4
5
6
7
1
2
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
5
6
7
3
4
1
2
125Vdc-
125Vdc+
X
1RWH When field wiring the power supply module, the maximum wire size that should be used is 1 - 14 AWG or 2 - 16 AWG; the minimum is 20 AWG.
96
840 USE 100 00 11/2004
Specifications
Power Supplies
The following table shows the specifications for the CPS51100 125 Vdc power supply module.
Specifications
Input Requirements
Input Voltage
Input Current
Inrush Current
Input Power Interruption
Fusing (external)
100 ... 150 Vdc including ripple
0.4 A
10 A
1.0 ms max
1.5 A slo-blo recommended (Part # 043502515 or equivalent)
Output to Bus
Voltage
Maximum Current
Minimum Current
Protection
General
Field Wiring Connector
(included)
Internal Power Dissipation
Operating Mode
5.1 Vdc
3 A
0.3 A
Over Current, Over Voltage
7 point terminal strip (Part # 043506325)
2.0 + 3 x I out
= Watts (where I out
is in Amperes)
Standalone
840 USE 100 00 11/2004
97
Power Supplies
LED Indicator and Description
The following figure shows the CPS51100 LED indicator.
Pwr ok
The following table shows the CPS51100 LED description.
LED Description
LEDs Color
Pwr ok Green
Indication when On
Power is supplied to the bus.
Wiring Diagram
1
4
5
2
3
6
7
The following figure shows the CPS51100 wiring diagram.
Not used
Not used
Not used
Not used
125 VDC +
125 VDC - (Common)
1RWH See S for power and grounding wiring guidelines and operational information.
98
840 USE 100 00 11/2004
140CPS52400 DC Standalone/Redundant Power Supply, 125 Vdc, 8 A
Power Supplies
Overview
Power Supply
Module
The following provides information on the DC Standalone/Redundant power supply,
125 Vdc, 8 A module.
The following figure shows the power supply module components.
LED Area
&36
369'&
Model Number
Module Description
Color Code
Customer Identification Label
(Fold label and place it inside door)
Removable Door
Field Wiring
Connector
Field Wiring
Connector Cover
3
4
5
6
7
1
2
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
4
5
1
2
3
6
7
125 Vdc-
125 Vdc+
X
1RWH When field wiring the power supply module, the maximum wire size that should be used is 1 - 14 AWG or 2 - 16 AWG; the minimum is 20 AWG.
840 USE 100 00 11/2004
99
Power Supplies
Specifications The following table shows the specifications for the CPS52400 125 VDC power supply module.
Specifications
Input Requirements
Input Voltage
Input Current
Inrush Current
Input Power Interruption
Fusing (external)
100 ... 150 Vdc including ripple
0.5 A @ 125 Vdc
28 A @ 125 Vdc
1.0 ms max
2 A slo-blo recommended (Part # 57-0089-000 or equivalent)
Output to Bus
Voltage
Maximum Current
Minimum Current
Protection
General
Field Wiring Connector
(included)
Internal Power Dissipation
Operating Mode
5.1 Vdc
8 A @ 60° C
None required
Over Current, Over Voltage
7 point terminal strip (Part # 043506325)
6.0 + 1.5 x |
OUT
= Watts (where |
OUT
is in Amperes)
Standalone / Redundant
100
840 USE 100 00 11/2004
LED Indicator and Description
The following figure shows the CPS52400 LED indicator.
Pwr ok
Power Supplies
The following table shows the CPS52400 LED description.
LED Description
LEDs Color
Pwr ok Green
Indication when On
Power is supplied to the bus.
Wiring Diagram
1
2
3
6
7
4
5
The following figure shows the CPS52400 wiring diagram.
}
Internally connected.
Do not connect any external wiring to these points.
Not used
Not used
125VDC +
125 VDC - (Common)
1RWH See S for power and grounding wiring guidelines and operational information.
101
840 USE 100 00 11/2004
Power Supplies
102
840 USE 100 00 11/2004
CPU Modules
7
At a Glance
Introduction This chapter provides information on the specifications, LED indicators and description and error codes for the Quantum CPU modules.
The following table shows an overview of the Quantum CPU modules.
CPU SRAM
(bytes)
140CPU11302 256 k
140CPU11303 512 k
140CPU21304 768 k
Ladder Registers Extended 984 Ladder
Performance
8 k
16 k
10 k
10 k
32 k or
48 k
57 k or
28 k * none none
0.3 - 1.4 ms/k
0.3 - 1.4 ms/k
80 k or 0 k * 0.3 - 1.4 ms/k
Max IEC
Program
109 k
368 k
606 k
140CPU42402 2 M
140CPU43412 2 M
140CPU43412A 2 M
140CPU53414 4 M
64 k
64 K
64K
64 K
57 k
57 K*
57 K*
57 K*
96 k *
96 k
96 k
96 k
0.1 - 0.5 ms/k
0.1 - 0.5 ms/k
0.1 - 0.5 ms/k
570 k
896 k
896 k
0.9 - 0.45 ms/k 2.5 M
140CPU53414A 4 M 64 K 57 K* 96K 0.1 - 0.5 ms/k 2.5 M
*Refer to the individual specification pages for detailed information.
103
840 USE 100 00 11/2004
CPU Modules
What’s in this
Chapter?
This chapter contains the following topics:
Topic
140CPU11302 CPU Module
140CPU11303 CPU Module
140CPU21304 CPU Module
140CPU42402 CPU Module
140CPU43412 CPU Module
140CPU43412A CPU Module
140CPU53414 CPU Module
140CPU53414A CPU Module
Page
104
840 USE 100 00 11/2004
CPU Modules
140CPU11302 CPU Module
Overview
CPU Module
The following provides information on the 140CPU11302 Controller module –
CPU 256 K, 1xModbus Plus, Max IEC Program 109 K (requires IEC-only Exec.)
The following figure shows the CPU Module and its components.
LED Area
Battery
Memory Protect and
Comm parameter
Slide Switches
Modbus
Connector
Modbus Plus
Connector
Chan A
&38
CONTROLLER
Modbus
Modbus
Plus
Chan A
Model Number
Module Description
Color Code
Removable door
Part #043513804
Customer Identification Label
(Fold label and place it inside door) Part #043502480
Date
Installed
Batt.
Batt.
Spare mem prt off not used
ASCII
RTU mem
Modbus
Modbus
Plus
Network
Node
X
840 USE 100 00 11/2004
105
CPU Modules
Specifications The following table shows the specifications for the 140CPU11302 CONTROLLER module.
Specifications
984 Ladder Logic
Reference Capacity
Discrete
8 k words max
8192 In and 8192 Out max
Local I/O (Main Backplane)
Maximum I/O Words
Maximum Number of I/O Racks
Remote I/O
Maximum I/O Words per Drop
Maximum Number of Remote Drops
Distributed I/O
Maximum Number of Networks per
System
64 In and 64 Out*
2 (Requires expander)
64 In / 64 Out*
31
3**
Maximum Words per Network (For every
DIO drop, there is a minimum of two words input of overhead.)
500 In and 500 Out
Maximum Words per Node
Watchdog Timer
30 In and 32 Out
250 ms (S/W adjustable)
Logic Solve Time
Battery
Service Life
Shelf Life
0.3 ms / k to 1.4 ms / k
3 V Lithium
1200 mAh
10 years with 0.5% loss of capacity per year
Battery Load Current @ Power-off
Typical
Maximum
Communication
Modbus (RS-232)
Modbus Plus (RS-485)
5
μ
A
110
μ
A
1 serial port (9-pin D-shelf)
1 network port (9-pin D-shell)
106
840 USE 100 00 11/2004
840 USE 100 00 11/2004
CPU Modules
Specifications
General
Diagnostics
Bus Current Required
Power Dissipation
TOD Clock
Maximum Number of NOM, NOE, and
MMS modules (any combination)
Power Up Runtime
RAM RAM
RAM Address
Executive Checksum
RAM Address
Executive Checksum
User Logic Check User Logic Check
Processor
780 mA
3.9 W
+/- 8.0 seconds/day 0 ... 60° C
2
* This information can be a mix of Discrete or Register I/O. For each word of register
I/O configured, one word of I/O words must be subtracted from the total available.
The same holds true for each block of 8 bits or 16 bits of Discrete I/O configured – one word of Register I/O must be subtracted from the total available.
**Requires the use of the 140NOM2x00 Option Processor.–
107
CPU Modules
LED Indicators and Descriptions
The following figure shows the CPU LED indicators.
Ready
Run
Modbus
Modbus +
Bat Low
Error A
Mem Prt
The following table shows the LED descriptions.
LED Descriptions
LEDs Color
Ready
Run
Green
Green
Modbus
Modbus +
Mem Prt
Bat Low
Error A
Green
Green
Amber
Red
Red
Indication when On
The CPU has passed powerup diagnostics.
The CPU has been started and is solving logic. (See the following table for Run LED error codes).
Communications are active on the Modbus port.
Communications are active on the Modbus Plus port.
Memory is write protected (the memory protect switch is on).
The battery needs replacing.
Indicates a communications error on the Modbus Plus network.
108
840 USE 100 00 11/2004
CPU Modules
LED Error Codes The following table show the number of times the Run LED blinks for each type of error, and the crash codes possible for that group (all codes are in hex) for the
140CPU11302 module.
LED Error Codes
Number of Blinks
Continuous
2
3
4
623
624
625
626
61F
620
621
622
617
618
619
61E
609
614
615
616
605
606
607
608
72C
72F
730
604
82E
769
72A
72B
Code
0000
80B
80C
Error requested kernel mode ram error during sizing run output active failed
MB command handler stack error bus grant received not master asic on cpu master config write bad quantum bus DPM write failure plc asic loopback test plc asic BAD_DATA
UPI timeout error bad UPI response opcode
UPI bus diagnostic error modbus cmd-buffer overflow modbus cmd-length is zero modbus abort command error mbp bus interface error bad mbp response opcode timeout waiting for mbp mbp out of synchronization mbp invalid path page 0 not paragraph aligned bad external uart hardware bad external uart interrupt bad receive comm state bad transmit comm state bad comm state trn_asc bad comm state trn_rtu bad comm state rcv_rtu bad comm state rcv_asc bad modbus state tmr0_evt
840 USE 100 00 11/2004
109
CPU Modules
Front Panel
Switches
5
6
7
8
LED Error Codes
Number of Blinks
300
301
8001
8002
8003
Code
627
628
631
503
52D
402
Error bad modbus state trn-int bad modbus state rcv-int bad interrupt ram address test error
P.O.S.T BAD MPU ERROR ram data test error
EXEC not loaded
EXEC Checksum
Kernal prom checksum error flash prog / erase error unexpected executive return
Two, three-position slide switches are located on the front of the CPU. The left switch is used for memory protection when in the top position and no memory protection in the middle and bottom positions. The three-position slide switch on the right is used to select the communication parameter settings for the Modbus (RS-
232) ports.
The following figure shows the three options that are available for the CPU11302. mem prt off not used
ASCII
RTU mem
1RWH The CPU hardware defaults to bridge mode when the front panel switch is set to RTU or ASCII mode. When networking controllers, a panel device connected to the CPU Modbus port can communicate with the controller to which it is connected, as well as log into any nodes on the Modbus Plus network.
110
840 USE 100 00 11/2004
840 USE 100 00 11/2004
CPU Modules
Setting the slide switch to the top position assigns ASCII functionality to the port; the following communication parameters are set and cannot be changed.
ASCII Communication Port Parameters
Baud 2,400
Parity
Data Bits
Even
7
Stop Bits
Device Address
1
Rear panel rotary switch setting
Setting the slide switch to the middle position assigns remote terminal unit (RTU) functionality to the port; the following communication parameters are set and cannot be changed.
RTU Communication Port Parameters
Baud 9,600
Parity
Data Bits
Even
8
Stop Bits
Device Address
1
Rear panel rotary switch setting
Setting the slide switch to the bottom position gives you the ability to assign communication parameters to the port in software; the following parameters are valid.
Valid Communication Port Parameters
Baud 19,200
9,600
7,200
4,800
3,600
2,400
2,000
Data Bits
Stop Bits
Parity
Device Address
1,800
7 / 8
1 / 2
Enable/Disable Odd/Even
1 ... 247
1,200
600
300
150
134.5
110
75
50
111
CPU Modules
Rear Panel
Switches
Two rotary switches are located on the rear panel of the CPU. They are used for setting the Modbus Plus node and Modbus port addresses.
1RWH The highest address that may be set with these switches is 64.
SW1 (the top switch) sets the upper digit (tens) of the address; SW2 (the bottom switch) sets the lower digit (ones) of the address. The illustration below shows the correct setting for an example address of 11.
The following figure shows SW1 and SW2.
8
9
0
1
2
6
5
4
8
9
0
1
2
6
5
4
SW 1 (TOP)
SW 2 (BOTTOM)
The following table shows the SW1 and SW2 address settings.
SW1 and SW2 Address Settings
Node Address SW1
1 ... 9
10 ... 19
0
1
20 ... 29
30 ... 39
40 ... 49
50 ... 59
60 ... 64
4
5
2
3
6
SW2
1 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 4
1RWH If "0" or an address greater than 64 is selected, the Modbus + LED will be
"on" steady, to indicate the selection of an invalid address.
112
840 USE 100 00 11/2004
Modbus
Connector
Pinouts
CPU Modules
All Quantum CPUs are equipped with a nine-pin RS-232C connector that supports
Modicon’s proprietary Modbus communication protocol. The following is the Modbus port pinout connections for nine-pin and 25-pin connections.
1RWH Although the Modbus ports electrically support existing Modbus cables, it is recommended that a Modbus programming cable (Part # 990NAA2620 or
990NAA26350) be used. This cable has been designed to fit under the door of a
Quantum CPU or NOM module.
Modbus Ports
Pinout
Connections
The following figure shows the Modbus port pinout connections for nine-pin and 25pin connections.
IBM-AT
9-Pin Female
CD 1
RX
TX
DTR
GRND
DSR
RTS
CTS
4
5
2
3
6
7
8
4
5
2
3
6
7
8
9
Quantum
9-Pin Male
1 SHIELD
RX
TX
DTR
GRND
DSR
RTS
CTS
NC
TX
RX
RTS
CTS
DSR
GRND
NC
DTR
IBM-XT
25-Pin Female
SHIELD 1
4
5
2
3
6
7
8
20
4
5
2
3
6
7
8
9
Quantum
9-Pin Male
1 SHIELD
RX
TX
DTR
GRND
DSR
RTS
CTS
NC
840 USE 100 00 11/2004
113
CPU Modules
Modbus Ports
Pinout
Connections for
Portable
Computers
The following figure shows the Modbus port pinout connections for nine-pin portable
(laptop) computers.
IBM-AT
9-Pin Female
Quantum
9-Pin Male
CD
RX
TX
DTR
GRND
DSR
RTS
CTS
NC
SHIELD
RX
TX
DTR
GRND
DSR
RTS
CTS
NC
The following is the abbreviation key for the above figures.
TX: Transmitted Data
RX: Received Data
RTS: Request to Send
DSR: Data Set Ready
DTR: Data Terminal Ready
CTS: Clear to Send
NC: No Connection
CD: Carrier Detect
114
840 USE 100 00 11/2004
CPU Modules
140CPU11303 CPU Module
Overview
CPU Module
The following provides information on the 140CPU11303 Controller module –
CPU 512 k, 1xModbus Plus, Max IEC Program 368 K (requires IEC Exec.)
The following figure shows the CPU Module and its components.
LED Area
Battery
Memory Protect and
Comm parameter
Slide Switches
Modbus
Connector
Modbus Plus
Connector
Chan A
Modbus
Modbus
Plus
Chan A
Model Number
Module Description
Color Code
Removable door
Customer Identification Label
(Fold label and place it inside door)
Date
Installed
Batt.
Batt.
Spare mem prt off not used
ASCII
RTU mem
Modbus
Modbus
Plus
Network
Node
X
840 USE 100 00 11/2004
115
CPU Modules
Specifications The following table shows the specifications for the 140CPU11303 CONTROLLER module.
Specifications
984 Ladder Logic
Reference Capacity
Discrete
16 k words max
8192 In and 8192 Out max
Local I/O (Main Backplane)
Maximum I/O Words
Maximum Number of I/O Racks
Remote I/O
Maximum I/O Words per Drop
Maximum Number of Remote Drops
Distributed I/O
Maximum Number of Networks per
System
Maximum Words per Network (For every DIO drop, there is a minimum of two words input of overhead.)
Maximum Words per Node
Watchdog Timer
Logic Solve Time
Battery
Service Life
Shelf Life
Battery Load Current @ Power-off
Typical
Maximum
Communication
Modbus (RS-232)
Modbus Plus (RS-485)
64 In and 64 Out*
2 (Requires expander)
64 In / 64 Out*
31
3**
500 In and 500 Out
30 In and 32 Out
250 ms (S/W adjustable)
0.3 ms / k to 1.4 ms / k
3 V Lithium
1200 mAh
10 years with 0.5% loss of capacity per year
7
μ
A
210
μ
A
1 serial port (9-pin D-shell)
1 network port (9-pin D-shell)
116
840 USE 100 00 11/2004
840 USE 100 00 11/2004
CPU Modules
Specifications
General
Diagnostics
Bus Current Required
Power Dissipation
TOD Clock
Maximum Number of NOM, NOE, and
MMS modules (any combination)
Power Up Runtime
RAM RAM
RAM Address
Executive Checksum
RAM Address
Executive Checksum
User Logic Check User Logic Check
Processor
790 mA
3.95 W
+/- 8.0 seconds/day 0 ... 60° C
2
* This information can be a mix of Discrete or Register I/O. For each word of register
I/O configured, one word of I/O words must be subtracted from the total available.
The same holds true for each block of 8 bits or 16 bits of Discrete I/O configured - one word of Register I/O must be subtracted from the total available.
**Requires the use of the 140NOM21x00 Option Processor.
117
CPU Modules
LED Indicators and Descriptions
The following figure shows the CPU11303 LED indicators.
Ready
Run
Modbus
Modbus +
Bat Low
Error A
Mem Prt
The following table shows the CPU11303 LED descriptions.
LED Descriptions
LEDs Color
Ready
Run
Green
Green
Modbus
Modbus +
Mem Prt
Bat Low
Error A
Green
Green
Amber
Red
Red
Indication when On
The CPU has passed powerup diagnostics.
The CPU has been started and is solving logic (see the following table for Run LED error codes).
Communications are active on the Modbus port.
Communications are active on the Modbus Plus port.
Memory is write protected (the memory protect switch is on).
The battery needs replacing.
Indicates a communications error on the Modbus Plus network.
118
840 USE 100 00 11/2004
CPU Modules
LED Error Codes The LED Error Codes table shows the number of times the Run LED blinks for each type of error and the crash codes possible for that group (all codes are in hex). The following table shows the blinking run LED error codes.
LED Error Codes
Number of Blinks
Continuous
2
3
4
623
624
625
626
61F
620
621
622
617
618
619
61E
609
614
615
616
605
606
607
608
72C
72F
730
604
82E
769
72A
72B
Code
0000
80B
80C
Error requested kernel mode ram error during sizing run output active failed
MB command handler stack error bus grant received not master asic on cpu master config write bad quantum bus DPM write failure plc asic loopback test plc asic BAD_DATA
UPI timeout error bad UPI response opcode
UPI bus diagnostic error modbus cmd-buffer overflow modbus cmd-length is zero modbus abort command error mbp bus interface error bad mbp response opcode timeout waiting for mbp mbp out of synchronization mbp invalid path page 0 not paragraph aligned bad external uart hardware bad external uart interrupt bad receive comm state bad transmit comm state bad comm state trn_asc bad comm state trn_rtu bad comm state rcv_rtu bad comm state rcv_asc bad modbus state tmr0_evt
840 USE 100 00 11/2004
119
CPU Modules
Front Panel
Switches
6
7
LED Error Codes
Number of Blinks
5
8
300
301
8001
8002
8003
Code
627
628
631
503
52D
402
Error bad modbus state trn-int bad modbus state rcv-int bad interrupt ram address test error
P.O.S.T BAD MPU ERROR ram data test error
EXEC not loaded
EXEC Checksum
Kernal prom checksum error flash prog / erase error unexpected executive return
Two, three-position slide switches are located on the front of the CPU. The left switch is used for memory protection when in the top position and no memory protection in the middle and bottom positions. The three-position slide switch on the right is used to select the communication parameter settings for the Modbus (RS-
232) ports.
The following figure shows the three options that are available. mem prt off not used
ASCII
RTU mem
1RWH The CPU hardware defaults to bridge mode when the front panel switch is set to RTU or ASCII mode. When networking controllers, a panel device connected to the CPU Modbus port can communicate with the controller to which it is connected, as well as log into any nodes on the Modbus Plus network.
120
840 USE 100 00 11/2004
840 USE 100 00 11/2004
CPU Modules
Setting the slide switch to the top position assigns ASCII functionality to the port; the following communication parameters are set and cannot be changed. The following table shows the ASCII communication port parameters.
ASCII Communication Port Parameters
Baud 2,400
Parity
Data Bits
Even
7
Stop Bits
Device Address
1
Rear panel rotary switch setting
Setting the slide switch to the middle position assigns remote terminal unit (RTU) functionality to the port; the following communication parameters are set and cannot be changed.
RTU Communication Port Parameters
Baud 9,600
Parity
Data Bits
Even
8
Stop Bits
Device Address
1
Rear panel rotary switch setting
Setting the slide switch to the bottom position gives you the ability to assign communication parameters to the port in software; the following parameters are valid.
Valid Communication Port Parameters
Baud 19,200
9,600
7,200
4,800
3,600
2,400
2,000
Parity
Data Bits
Stop Bits
Device Address
1,800
Enable/Disable Odd/Even
7 / 8
1 / 2
1 ... 247
1,200
600
300
150
134.5
110
75
50
121
CPU Modules
Rear Panel
Switches
Two rotary switches (refer to the illustration and table that follow) are located on the rear panel of the CPU. They are used for setting the Modbus Plus node and Modbus port addresses.
1RWH The highest address that may be set with these switches is 64.
SW1 (the top switch) sets the upper digit (tens) of the address; SW2 (the bottom switch) sets the lower digit (ones) of the address. The illustration below shows the correct setting for an example address of 11.
The following figure shows SW1 and SW2 switches.
8
9
0
1
2
6
5
4
8
9
0
1
2
6
5
4
SW1 (TOP)
SW2 (BOTTOM)
The following table shows the SW1 and SW2 address settings.
SW1 and SW2 Address Settings
Node Address SW1
1 ... 9
10 ... 19
0
1
20 ... 29
30 ... 39
40 ... 49
50 ... 59
60 ... 64
4
5
2
3
6
SW2
1 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 4
1RWH If "0" or an address greater than 64 is selected, the Modbus + LED will be
"on" steady, to indicate the selection of an invalid address.
122
840 USE 100 00 11/2004
Modbus
Connector
Pinouts
CPU Modules
All Quantum CPUs are equipped with a nine-pin RS-232C connector that supports
Modicon’s proprietary Modbus communication protocol. The following is the Modbus port pinout connections for nine-pin and 25-pin connections.
1RWH Although the Modbus ports electrically support existing Modbus cables, it is recommended that a Modbus programming cable (Part # 990NAA26320 or
990NAA26350) be used. This cable has been designed to fit under the door of a
Quantum CPU or NOM module.
Modbus Ports
Pinout
Connections
The following figure shows the Modbus port pinout connections for nine-pin and 25pin connections.
IBM-AT
9-Pin Female
CD 1
RX
TX
DTR
GRND
4
5
2
3
DSR
RTS
CTS
6
7
8
Quantum
9-Pin Male
1 SHIELD
2
3
RX
TX
4
5
DTR
GRND
6 DSR
7
8
9
RTS
CTS
NC
IBM-XT
25-Pin Female
SHIELD 1
TX
RX
2
3
RTS
CTS
DSR
GRND
NC
DTR
4
5
6
7
8
20
4
5
2
3
6
7
8
9
Quantum
9-Pin Male
1 SHIELD
RX
TX
DTR
GRND
DSR
RTS
CTS
NC
840 USE 100 00 11/2004
123
CPU Modules
Modbus Ports
Pinout
Connections for
Portable
Computers
The following figure shows the Modbus port connections for nine-pin portable computer connections.
IBM-AT
9-Pin Female
Quantum
9-Pin Male
CD
RX
TX
SHIELD
RX
TX
DTR
GRND
DSR
RTS
CTS
NC
DTR
GRND
DSR
RTS
CTS
NC
The following is the abbreviation key for the above figures.
TX: Transmitted Data
RX: Received Data
RTS: Request to Send
DSR: Data Set Ready
DTR: Data Terminal Ready
CTS: Clear to Send
N/C: No Connection
CD: Carrier Detect
124
840 USE 100 00 11/2004
CPU Modules
140CPU21304 CPU Module
Overview
CPU Module
The following provides information on the 140CPU21304 Controller module –
CPU 768 K, MATH, 1xModbus Plus, Max IEC Program 606 K.
The following figure shows the CPU Module and its parts.
LED Area
Battery
Memory Protect and
Comm parameter
Slide Switches
Modbus
Connector
Modbus Plus
Connector
Chan A
&38
CONTROLLER
Modbus
Modbus
Plus
Chan A
Model Number
Module Description
Color Code
Removable door
Part #043513804
Customer Identification Label
(Fold label and place it inside door) Part #043502480
Date
Installed
Batt.
Batt.
Spare mem prt off not used
ASCII
RTU mem
Modbus
Modbus
Plus
Network
Node
X
840 USE 100 00 11/2004
125
CPU Modules
Specifications The following table shows the specifications for the CPU21304 controller module.
Specifications
User Logic/Reference
Capacity
984 Ladder Logic Discrete Register Extended
Register
32 k words
48 k words
64 k
64 k
57 k
28 k
80 k
0 k
57,766 4XX registers max
Only if:
0XXX = 16 and
1XXX = 16 and
3XXX =16
64 k - any mix Discrete
Local I/O (Main Backplane)
Maximum I/O Words 64 In and 64 Out*
Maximum Number of I/O Racks 2 (Requires expander)
Remote I/O
Maximum I/O Words per Drop
Maximum Number of Remote
Drops
Distributed I/O
64 In and 64 Out*
31
Maximum Number of Networks per System
Maximum Words per Network
(For every DIO drop, there is a minimum of words input of overhead.)
Maximum Words per Node
Watchdog Timer
Logic Solve Time
Battery
3**
500 In and 500 Out
30 In and 32 Out
250 ms (software adjustable)
0.3 ms / k to 1.4 ms / k
3 V Lithium
Service Life
Shelf Life
1200 mAh
10 years with 0.5% loss of capacity per year
Battery Load Current @ Power-off
Typical
Maximum
5
μ
A
110
μ
A
Communication
Modbus (RS-232) 1 serial port (9-pin D-shell)
126
840 USE 100 00 11/2004
840 USE 100 00 11/2004
CPU Modules
Specifications
Modbus Plus (RS-485)
General
Diagnostics
1 network port (9-pin D-shell)
Bus Current Required
Power Dissipation
TOD Clock
Maximum Number of NOM,
NOE, and MMS modules (any combination)
Power Up Runtime
RAM RAM
RAM Address
Executive Checksum
RAM Address
Executive Checksum
User Logic Check User Logic Check
Processor
900 mA
4.5 W
+/- 8.0 seconds/day 0 ... 60° C
2
*This information can be a mix of Discrete or Register I/Os. For each word of
Register I/O configured, one word of I/O words must be subtracted from the total available. The same holds true for each block of 8 bits or 16 bits of Discrete I/O configured - one word of Register I/O must be subtracted from the total available.
**Requires the use of the 140NOM2x00 Option Processor.
127
CPU Modules
LED Indicators and Descriptions
The following figure shows the CPU LED indicators.
Ready
Run
Modbus
Modbus +
Bat Low
Error A
Mem Prt
The following table shows the CPU LED descriptions.
LED Descriptions
LEDs Color
Ready
Run
Green
Green
Modbus
Modbus +
Mem Prt
Bat Low
Error A
Green
Green
Amber
Red
Red
Indication when On
The CPU has passed powerup diagnostics.
The CPU has been started and is solving logic (see the following table for Run LED error codes).
Communications are active on the Modbus port.
Communications are active on the Modbus Plus port.
Memory is write-protected (the memory protect switch is on).
The battery needs replacing.
Indicates a communications error on the Modbus Plus network.
128
840 USE 100 00 11/2004
CPU Modules
LED Error Codes The Blinking Run LED Error Codes table shows the number of times the Run LED blinks for each type of error and the crash codes possible for that group (all codes are in hex).
The following table shows the run LED error codes for the 140CPU21304.
LED Error Codes
Number of Blinks
Continuous
2
3
4
61F
620
621
622
623
624
617
618
619
61E
609
614
615
616
605
606
607
608
72C
72F
730
604
82E
769
72A
72B
Code
0000
80B
80C
Error requested kernel mode ram error during sizing run output active failed
MB command handler stack error bus grant received not master asic on cpu master config write bad quantum bus DPM write failure plc asic loopback test plc asic BAD_DATA
UPI timeout error bad UPI response opcode
UPI bus diagnostic error modbus cmd-buffer overflow modbus cmd-length is zero modbus abort command error mbp bus interface error bad mbp response opcode timeout waiting for mbp mbp out of synchronization mbp invalid path page 0 not paragraph aligned bad external uart hardware bad external uart interrupt bad receive comm state bad transmit comm state bad comm state trn_asc bad comm state trn_rtu bad comm state rcv_rtu
840 USE 100 00 11/2004
129
CPU Modules
Front Panel
Switches
5
6
7
8
LED Error Codes
Number of Blinks
52D
402
300
301
8001
8002
8003
Code
625
626
627
628
631
503
Error bad comm state rcv_asc bad modbus state tmr0_evt bad modbus state trn-int bad modbus state rcv-int bad interrupt ram address test error
P.O.S.T BAD MPU ERROR ram data test error
EXEC not loaded
EXEC Checksum
Kernal prom checksum error flash prog / erase error unexpected executive return
Two, three-position slide switches are located on the front of the CPU. The left switch is used for memory protection when in the top position and no memory protection in the middle and bottom positions. The three-position slide switch on the right is used to select the communication parameter settings for the Modbus (RS-
232) ports.
The following figure shows the three options that are available.
ASCII mem prt off RTU not used mem
1RWH The CPU hardware defaults to bridge mode when the front panel switch is set to RTU or ASCII mode. When networking controllers, a panel device connected to the CPU Modbus port can communicationunicate with the controller to which it is connected, as well as log into any nodes on the Modbus Plus network.
130
840 USE 100 00 11/2004
840 USE 100 00 11/2004
CPU Modules
Setting the slide switch to the top position assigns ASCII functionality to the port; the following communication parameters are set and cannot be changed
ASCII Communication Port Parameters
Baud 2,400
Parity
Data Bits
Even
7
Stop Bits
Device Address
1
Rear panel rotary switch setting
Setting the slide switch to the middle position assigns remote terminal unit (RTU) functionality to the port; the following communication parameters are set and cannot be changed.
RTU Communication Port Parameters
Baud 9,600
Parity
Data Bits
Even
8
Stop Bits
Device Address
1
Rear panel rotary switch setting
Setting the slide switch to the bottom position gives you the ability to assign communication parameters to the port in software; the following parameters are valid.
Valid Communication Port Parameters
Baud 19,200
9,600
7,200
4,800
3,600
2,400
2,000
Parity
Data Bits
Stop Bits
Device Address
1,800
Enable/Disable Odd/Even
7 / 8
1 / 2
1 ... 247
1,200
600
300
150
134.5
110
75
50
131
CPU Modules
Rear Panel
Switches
Two rotary switches (refer to the illustration and table below) are located on the rear panel of the CPU. They are used for setting Modbus Plus node and Modbus port addresses.
1RWH The highest address that may be set with these switches is 64.
SW1 (the top switch) sets the upper digit (tens) of the address; SW2 (the bottom switch) sets the lower digit (ones) of the address. The illustration below shows the correct setting for an example address of 11.
The following figure shows SW1 and SW2.
8
9
0
1
2
4
6
5
8
9
0
1
2
4
6
5
SW1 (TENS)
SW2 (ONES)
The following table shows the SW1 and SW2 address settings.
SW1 and SW2 Adress Settings
Node Address
1 ... 9
10 ... 19
20 ... 29
30 ... 39
40 ... 49
50 ... 59
60 ... 64
4
5
6
1
2
3
SW1
0
SW2
1 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 4
1RWH If "0" or an address greater than 64 is selected, the Modbus + LED will be
"on" steady, to indicate the selection of an invalid address.
132
840 USE 100 00 11/2004
Modbus
Connector
Pinouts
CPU Modules
All Quantum CPUs are equipped with a nine-pin RS-232C connector that supports
Modicon’s proprietary Modbus communication protocol. The following is the Modbus port pinout connections for nine-pin and 25-pin connections.
1RWH Although the Modbus ports electrically support existing Modbus cables, it isrecommended that a Modbus programming cable (Part # 990NAA26320 or
990NAA26350) be used. This cable has been designed to fit under the door of a
Quantum CPU or NOM module.
Modbus Ports
Pinout
Connections
The following figure shows the Modbus port pinout connections for nine-pin and 25pin connections.
IBM-AT
9-Pin Female
CD 1
RX
TX
DTR
GRND
DSR
RTS
CTS
4
5
2
3
6
7
8
4
5
2
3
6
7
8
9
Quantum
9-Pin Male
1 SHIELD
RX
TX
DTR
GRND
DSR
RTS
CTS
NC
IBM-XT
25-Pin Female
SHIELD 1
TX
RX
2
3
RTS
CTS
DSR
GRND
NC
DTR
4
5
6
7
8
20
4
5
6
7
8
9
2
3
Quantum
9-Pin Male
1 SHIELD
RX
TX
DTR
GRND
DSR
RTS
CTS
NC
840 USE 100 00 11/2004
133
CPU Modules
Modbus Ports
Pinout
Connections for
Portable
Computers
The follwing figure shows the Modbus port pinout connections for nine-pin portable computers.
IBM-AT
9-Pin Female
Quantum
9-Pin Male
CD
RX
TX
DTR
GRND
DSR
RTS
CTS
SHIELD
RX
TX
DTR
GRND
DSR
RTS
CTS
NC NC
The following is the abbreviation key for the above figures.
TX: Transmitted Data
RX: Received Data
RTS: Request to Send
DSR: Data Set Ready
DTR: Data Terminal Ready
CTS: Clear to Send
NC: No Connection
CD: Carrier Detect
134
840 USE 100 00 11/2004
CPU Modules
140CPU42402 CPU Module
Overview
CPU Module
The following provides information on the140CPU42402 Controller module –
CPU 2 M, MATH, 2xModbus Plus, Max IEC Program 570 K.
The following figure shows the CPU module and its components.
LED Area
Battery
Memory Protect and
Comm parameter
Slide Switches
Modbus
Connector
Modbus Plus
Connector
Chan A
Modbus Plus
Connector
Chan B*
Modbus
Modbus
Plus
Chan A
Modbus
Plus
Chan B
X
&38
486 CONTROLLER
Model Number
Module Description
Color Code
Removable door
Part #043513804
Customer Identification Label
(Fold label and place it inside door) Part #043506673
Date
Installed
Batt.
Batt.
Spare mem prt off not used
ASCII
RTU mem
Modbus
Modbus
Plus
Modbus
Plus
Network
Node
840 USE 100 00 11/2004
135
CPU Modules
Specifications The following table shows the specifications for the 140CPU42402 CONTROLLER module.
Specifications
User Logic/Reference
Capacity
984 Ladder
Logic
64 k words
Discrete
64 k
57,766 4XX registers max
Only if:
0XXX = 16 and
1XXX = 16 and
3XXX = 16
Reference Capacity
Discrete
Local I/O (Main Backplane)
Maximum I/O Words
Maximum Number of I/O
Racks
Distributed I/O
Maximum Number of
Networks per System
64 k - any mix
64 In and 64 Out*
2 (Requires expander)
Remote I/O
Maximum I/O Words per Drop 64 In and 64 Out*
Maximum Number of Remote
Drops
31
3**
Register
57 k
Maximum Words per Network
(For every DIO drop, there is a minimum of words input of overhead.)
500 In and 500 Out
Maximum Words per Node
Watchdog Timer
30 In and 32 Out
250 ms (S/W adjustable)
Logic Solve Time
Battery
Service Life
Shelf Life
0.1 ms / k to 0.5 ms / k
3 V Lithium
1200 mAh
10 years with 0.5% loss of capacity per year
Battery Load Current @ Power-off
Typical
Maximum
7
μ
A
210
μ
A
Extended
Register
96 k
136
840 USE 100 00 11/2004
840 USE 100 00 11/2004
CPU Modules
Specifications
Communication
Modbus (RS-232)
Modbus Plus (RS-485)
General
Diagnostics
1 serial port (9-pin D-shell)
2 (redundant) network ports (9-pin D-shell)
Power Up Runtime
RAM RAM
RAM Address
Executive Checksum
RAM Address
Executive Checksum
Bus Current Required
Power dissipation
User Logic Check
Processor
1.8 A
9 W
TOD Clock +/- 8.0 seconds/day 0 ... 60 °C
Maximum Number of NOM,
NOE, and MMS modules (any combination)
6
User Logic Check
*This information can be a mix of Discrete or Register I/Os. For each word of
Register I/O configured, one word of I/O words must be subtracted from the total available. The same holds true for each block of 8 bits or 16 bits of Discrete I/O configured-one word of Register I/O must be subtracted from the total available.
**Requires the use of the 140NOM2x00 Option Modules.
137
CPU Modules
LED Indicators and Descriptions
The following figure shows the CPU LED indicators.
Ready
Run
Modbus
Modbus +
Bat Low
Error A
Error B
Mem Prt
The following table shows the CPU LED descriptions.
LED Descriptions
LEDs
Ready
Color
Green
Run Green
Modbus
Modbus +
Mem Prt
Bat Low
Error A
Error B
Green
Green
Amber
Red
Red
Red
Indication when On
The CPU has passed powerup diagnostics.
The CPU has been started and is solving logic (see the following table for Run LED error codes).
Communications are active on the Modbus port.
Communications are active on the Modbus Plus port.
Memory is write protected (the memory protect switch is on).
The battery needs replacing.
Indicates a communications error on the redundant Modbus Plus port A (140CPU42402 only).
Indicates a communications error on the redundant Modbus Plus port B (140CPU42402 only).
138
840 USE 100 00 11/2004
LED Error Codes The following table shows the run LED error codes for the CPU42402.
LED Error Codes
Number of Blinks
Continuous
2
3
4
623
624
625
626
627
61F
620
621
622
617
618
619
61E
609
614
615
616
605
606
607
608
72C
72F
730
604
82E
769
72A
72B
Code
0000
80B
80C
Error requested kernel mode ram error during sizing run output active failed
MB command handler stack error bus grant received not master asic on cpu master config write bad quantum bus DPM write failure plc asic loopback test plc asic BAD_DATA
UPI timeout error bad UPI response opcode
UPI bus diagnostic error modbus cmd-buffer overflow modbus cmd-length is zero modbus abort command error mbp bus interface error bad mbp response opcode timeout waiting for mbp mbp out of synchronization mbp invalid path page 0 not paragraph aligned bad external uart hardware bad external uart interrupt bad receive comm state bad transmit comm state bad comm state trn_asc bad comm state trn_rtu bad comm state rcv_rtu bad comm state rcv_asc bad modbus state tmr0_evt bad modbus state trn-int
CPU Modules
840 USE 100 00 11/2004
139
CPU Modules
Front Panel
Switches
5
6
7
8
LED Error Codes
Number of Blinks Code
628
631
503
52D
402
300
301
8001
8002
8003
Error bad modbus state rcv-int bad interrupt ram address test error
P.O.S.T BAD MPU ERROR ram data test error
EXEC not loaded
EXEC Checksum
Kernal prom checksum error flash prog / erase error unexpected executive return
Two, three-position slide switches are located on the front of the CPU. The left switch is used for memory protection when in the top position and no memory protection in the middle and bottom positions. The three-position slide switch on the right is used to select the comm parameter settings for the Modbus (RS-232) ports.
The following figure shows the three options that are available for the CPU42402 module.
ASCII mem prt off RTU not used mem
1RWH The CPU hardware defaults to bridge mode when the front panel switch is set to RTU or ASCII mode. When networking controllers, a panel device connected to the CPU Modbus port can communicate with the controller to which it is connected, as well as log into any nodes on the Modbus Plus network.
140
840 USE 100 00 11/2004
840 USE 100 00 11/2004
CPU Modules
Setting the slide switch to the top position assigns ASCII functionality to the port; the following comm parameters are set and cannot be changed.
ASCII Comm Port Parameters
Baud 2,400
Parity
Data Bits
Even
7
Stop Bits
Device Address
1
Rear panel rotary switch setting
Setting the slide switch to the middle position assigns remote terminal unit (RTU) functionality to the port; the following comm parameters are set and cannot be changed.
RTU Comm Port Parameters
Baud 9,600
Parity
Data Bits
Even
8
Stop Bits
Device Address
1
Rear panel rotary switch setting
Setting the slide switch to the bottom position gives you the ability to assign comm parameters to the port in software; the following parameters are valid.
Valid Comm Port Parameters
Baud
Parity
Data Bits
Stop Bits
Device Address
19,200
9,600
7,200
4,800
3,600
2,400
2,000
1,800
Enable/Disable Odd/Even
7 / 8
1 / 2
1 ... 247
1,200
600
300
150
134.5
110
75
50
141
CPU Modules
Rear Panel
Switches
Two rotary switches (refer to the following illustration) are located on the rear panel of the CPU. They are used for setting Modbus Plus node and Modbus port addresses.
1RWH The highest address that may be set with these switches is 64.
SW1 (the top switch) sets the upper digit (tens) of the address; SW2 (the bottom switch) sets the lower digit (ones) of the address. The illustration below shows the correct setting for an example address of 11.
The following figure shows SW1 and SW2.
8
9
0
1
2
6
5
4
8
9
0
1
2
6
5
4
SW1 (TOP)
SW2 (BOTTOM)
The following table shows the SW1 and SW2 address settings.
SW1 and SW2 Address Settings
Node Address SW1
1 ... 9
10 ... 19
0
1
20 ... 29
30 ... 39
40 ... 49
50 ... 59
60 ... 64
4
5
2
3
6
SW2
1 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 4
1RWH If "0" or an address greater than 64 is selected, the Modbus + LED will be
"on" steady, to indicate the selection of an invalid address.
142
840 USE 100 00 11/2004
Modbus
Connector
Pinouts
CPU Modules
All Quantum CPUs are equipped with a nine-pin RS-232C connector that supports
Modicon’s proprietary Modbus communication protocol. The following is the Modbus port pinout connections for nine-pin and 25-pin connections.
1RWH Although the Modbus ports electrically support existing Modbus cables, it is recommended that a Modbus programming cable (Part # 990NAA26320 or
990NAA26350) be used. This cable has been designed to fit under the door of a
Quantum CPU or NOM module.
Modbus Ports
Pinout
Connections
The following figure shows the Modbus port pinout connections for nine-pin and 25pin connections.
IBM-AT
9-Pin Female
CD 1
RX
TX
2
3
DTR
GRND
DSR
4
5
6
RTS
CTS
7
8
Quantum
9-Pin Male
1 SHIELD
2
3
RX
TX
4
5
6
7
8
9
DTR
GRND
DSR
RTS
CTS
NC
IBM-XT
25-Pin Female
SHIELD 1
TX
RX
2
3
RTS
CTS
DSR
GRND
NC
DTR
7
8
20
4
5
6
7
8
9
4
5
6
2
3
Quantum
9-Pin Male
1 SHIELD
RX
TX
DTR
GRND
DSR
RTS
CTS
NC
840 USE 100 00 11/2004
143
CPU Modules
Modbus Ports
Pinout
Connections for
Portable
Computers
The following figure shows the Modbus port pinout connections for nine-pin portable computers
IBM-AT
9-Pin Female
Quantum
9-Pin Male
CD
RX
TX
DTR
GRND
DSR
SHIELD
RX
TX
DTR
GRND
DSR
RTS
CTS
NC
RTS
CTS
NC
The following is the abbreviation key for the above figures.
TX: Transmitted Data
RX: Received Data
RTS: Request to Send
DSR: Data Set Ready
DTR: Data Terminal Ready
CTS: Clear to Send
NC: No Connection
CD: Carrier Detect
144
840 USE 100 00 11/2004
CPU Modules
140CPU43412 CPU Module
Overview
CPU Module
The following provides information on the 140CPU43412 Controller module –
CPU 2M, 1xModbus Plus, Max IEC Program – 896 k.
The following figure shows the CPU Module and its components.
LED Area
Battery
Key Switch
Modbus
Connector
Modbus
Connector
Modbus Plus
Connector
&38
486 CONTROLLER
Slide
Model Number
Module Description
Color Code
Removable door
Part #043513804
Customer Identification Label
(Fold label and place it inside door)
Part #31000226
Batt.
Date
Installed
Dey sw
ASCII
RTU mem Switch
Modbus
Comm 1
Modbus
Comm 2
Modbus
Plus
Network
Node
X
840 USE 100 00 11/2004
145
CPU Modules
Specifications The following table shows the specifications for the CPU43412 CONTROLLER module.
Specifications
User Logic/Reference Capacity 984 Ladder
Logic
Discrete Register
64 k words 64 k
57,766 4XX registers max
Only if:
0XXX = 16
1XXX = 16 and
3XXX = 16
57 k
Reference Capacity
Discrete
Local I/O (Main Backplane)
Maximum I/O Words
64 k - any mix
Maximum Number of I/O Racks
Remote I/O
64 In and 64 Out*
2 (Requires expander)
Maximum I/O Words per Drop 64 In and 64 Out*
Maximum Number of Remote Drops 31
Extended
Register
96 k
Distributed I/O
Maximum Number of Networks per
System
3**
Maximum Words per Network (for every DIO drop, there is a minimum of words input of overhead.)
500 In and 500 Out
Maximum Words per Node 30 In and 32 Out
Maximum Number of Option Module
Interfaces
Supports up to six network modules (i.e., Modbus
Plus, Ethernet and Multi-Axis Motion option modules) using the option module interface technique
(see
Note : Only two Modbus Plus modules can have full functionality, including Quantum DIO support.
Watchdog Timer
Logic Solve Time
250 ms (S/W adjustable)
0.1 ms / k to 0.5 ms / k
Battery
Service Life
3 V Lithium
1200 mAh
Shelf Life
Battery Load Current at Power-off
10 years with 0.5% loss of capacity per year
146
840 USE 100 00 11/2004
840 USE 100 00 11/2004
CPU Modules
Specifications
Typical
Maximum
Communication
Modbus (RS-232)
Modbus Plus (RS-485)
General
Diagnostics
7
μ
A
210
μ
A
2 serial port (9-pin D-shell)
1 network port (9-pin D-shell)
Bus Current Required
Power Dissipation
TOD Clock
Operating Temperature
Power Up Runtime
RAM RAM
RAM Address
Executive Checksum
RAM Address
Executive Checksum
User Logic Check User Logic Check
Processor
1.8 A
9W
+/- 8.0 seconds/day 0 ... 60° C
0 ... 60° C
*This information can be a mix of Discrete or Register I/Os. For each word of register
I/O configured, one word of I/O words must be subtracted from the total available.
The same holds true for each block of 8 bits or 16 bits of Discrete I/O configured – one word of Register I/O must be subtracted from the total available.
**Requires the use of two 140NOM21x00 Option Modules.
147
CPU Modules
LED Indicators and Descriptions
The following figure shows the LED indicators.
Ready
Run
Bat1 Low
Modbus
Modbus + Error A
Mem Prt
The following table shows the LED descriptions.
LEDS
Ready
Run
Bat Low
Modbus
Modbus +
Error A
Mem Prt
Color
Green
Green
Red
Green
Green
Red
Amber
Indication when On
The CPU has passed power-up diagnostics.
The CPU has been started and is solving logic.
The battery needs replacing or is not present.
Communications are active on the Modbus port 1 or 2.
Communications are active on the Modbus Plus port.
Indicates communications error on the Modbus Plus port.
Memory is write-protected (the memory protect switch is on).
148
840 USE 100 00 11/2004
CPU Modules
LED Error Codes The following table shows the run LED error codes for the 140CPU43412.
LED Error Codes
Number of Blinks
Continuous
2
3
4
623
624
625
626
627
61F
620
621
622
617
618
619
61E
609
614
615
616
605
606
607
608
72C
72F
730
604
82E
769
72A
72B
Code
0000
80B
80C
Error requested kernel mode ram error during sizing run output active failed
MB command handler stack error bus grant received not master asic on cpu master config write bad quantum bus DPM write failure plc asic loopback test plc asic BAD_DATA
UPI timeout error bad UPI response opcode
UPI bus diagnostic error modbus cmd-buffer overflow modbus cmd-length is zero modbus abort command error mbp bus interface error bad mbp response opcode timeout waiting for mbp mbp out of synchronization mbp invalid path page 0 not paragraph aligned bad external uart hardware bad external uart interrupt bad receive comm state bad transmit comm state bad comm state trn_asc bad comm state trn_rtu bad comm state rcv_rtu bad comm state rcv_asc bad modbus state tmr0_evt bad modbus state trn-int
840 USE 100 00 11/2004
149
CPU Modules
Front Panel
Switches
5
6
7
8
LED Error Codes
Number of Blinks Code
628
631
503
52D
402
300
301
8001
8002
8003
Error bad modbus state rcv-int bad interrupt ram address test error
P.O.S.T BAD MPU ERROR ram data test error
EXEC not loaded
EXEC Checksum
Kernal prom checksum error flash prog / erase error unexpected executive return
Two, three-position slide switches are located on the front of the CPU. The left switch is used for memory protection when in the top position and no memory protection in the middle and bottom positions. The three-position slide switch on the right is used to select the comm parameter settings for the Modbus (RS-232) ports.
The following figure shows the three options that are available for the 140CPU43412 module.
ASCII mem prt off not used
RTU mem
1RWH The CPU hardware defaults to bridge mode when the front panel switch is set to RTU or ASCII mode. When networking controllers, a panel device connected to the CPU Modbus port can communicate with the controller to which it is connected, as well as log into any nodes on the Modbus Plus network.
150
840 USE 100 00 11/2004
840 USE 100 00 11/2004
CPU Modules
Setting the slide switch to the top position assigns ASCII functionality to the port; the following comm parameters are set and cannot be changed.
ASCII Comm Port Parameters
Baud 2,400
Parity
Data Bits
Even
7
Stop Bits
Device Address
1
Rear panel rotary switch setting
Setting the slide switch to the middle position assigns remote terminal unit (RTU) functionality to the port; the following comm parameters are set and cannot be changed.
RTU Comm Port Parameters
Baud 9,600
Parity
Data Bits
Even
8
Stop Bits
Device Address
1
Rear panel rotary switch setting
Setting the slide switch to the bottom position gives you the ability to assign comm parameters to the port in software; the following parameters are valid.
Valid Comm Port Parameters
Baud
Parity
Data Bits
Stop Bits
Device Address
19,200
9,600
7,200
4,800
3,600
2,400
2,000
1,800
Enable/Disable
Odd/Even
7 / 8
1 / 2
1 ... 247
1,200
600
300
150
134.5
110
75
50
151
CPU Modules
Rear Panel
Switches
Two rotary switches (see the following illustration and table) are located on the rear panel of the CPU. They are used for setting Modbus Plus node and Modbus port addresses.
1RWH The highest address that may be set with these switches is 64.
SW1 (the top switch) sets the upper digit (tens) of the address; SW2 (the bottom switch) sets the lower digit (ones) of the address. The illustration below shows the correct setting for an example address of 11.
The following figure shows SW1 and SW2.
8
9
0
1
2
6
5
4
8
9
0
1
2
6
5
4
SW1 (TOP)
SW2 (BOTTOM)
1RWH If "0" or an address greater than 64 is selected, the Modbus + LED will be
"on" steady, to indicate the selection of an invalid address.
The following table shows the SW1 and SW2 address settings.
SW1 and SW2 Address Settings
Node Address SW1
1 ... 9
10 ... 19
0
1
20 ... 29
30 ... 39
40 ... 49
50 ... 59
60 ... 64
4
5
2
3
6
SW2
1 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 4
152
840 USE 100 00 11/2004
Key Switch
CPU Modules
The key switch is used to protect memory from programming changes while the controller is in operation. The following figure shows the key switch.
Stop
Mem
Prt
Start
Stop
Mem
Prt
Start
1RWH The key switch positions shown next to the switch (above) are for reference only and are marked on the module as indicated on the right.
The following table shows the key switch information.
Key Switch Description
Key switch
Position
Stop
Controller Status
Controller is stopped and disables
Programmer changes.
Y
Memory
Protected
From
Programmer
Changes
N
Will Accept
Programmer
Stop or Start
Key switch
Transition
Mem Prt Controller may be either stopped or running and
Programmer changes are disabled. User cannot write to unlocated variables.
Y N
From Start or
Memory Protect:
Stops controller, if running, and disables
Programmer changes
From Stop or
Start: Prevents
Programmer changes, controller run status is not changed
840 USE 100 00 11/2004
153
CPU Modules
Modbus
Connector
Pinouts
Key Switch Description
Key switch
Position
Start
Controller Status
Controller may be either stopped or running. Programmer may make changes and start/stop the controller
Memory
Protected
From
Programmer
Changes
N
Will Accept
Programmer
Stop or Start
Key switch
Transition
Y From Stop:
Enables
Programmer changes, starts controller.
From Memory
Protect: Enables programmer changes, starts controller if stopped.
All Quantum CPUs are equipped with a nine-pin RS-232C connector that support
Modicon’s proprietary Modbus communication protocol. The following is the Modbus port pinout connections for nine-pin and 25-pin connections.
1RWH Although the Modbus ports electrically support existing Modbus cables, it is recommended that a Modbus programming cable (Part # 990NAA26320 or
990NAA26350) be used. This cable has been designed to fit under the door of a
Quantum CPU or NOM module.
Modbus Port
Modem Support
Modbus Port 1 has full modem interfacing ability. Modbus Port 2 RTS/CTS connections function properly for normal non-modem communications but do not support modems.
154
840 USE 100 00 11/2004
Modbus Ports
Pinout
Connections
CPU Modules
The following figure shows the Modbus port pinout connections for 9-pin and 25-pin connections.
IBM-AT
9-Pin Female
CD 1
Quantum
9-Pin Male
1 SHIELD
IBM-XT
25-Pin Female
SHIELD 1
Quantum
9-Pin Male
1 SHIELD
RX
TX
DTR
GRND
DSR
RTS
CTS
4
5
2
3
6
7
8
4
5
2
3
6
7
8
9
RX
TX
DTR
GRND
DSR
RTS
CTS
NC
TX
RX
RTS
CTS
DSR
GRND
NC
DTR
4
5
2
3
6
7
8
20
4
5
2
3
6
7
8
9
RX
TX
DTR
GRND
DSR
RTS
CTS
NC
Modbus Ports
Pinout
Connections for
Portable
Computers
The following figure shows the Modbus port pinout connections for 9-pin portable computers.
IBM-AT
9-Pin Female
Quantum
9-Pin Male
CD
RX
TX
SHIELD
RX
TX
DTR
GRND
DSR
DTR
GRND
DSR
RTS
CTS
RTS
CTS
NC NC
The following is the abbreviation key for the above figures.
TX: Transmitted Data
RX: Received Data
RTS: Request to Send
DSR: Data Set Ready
DTR: Data Terminal Ready
CTS: Clear to Send
NC: No Connection
CD: Carrier Detect
840 USE 100 00 11/2004
155
CPU Modules
140CPU43412A CPU Module
Overview
CPU Module
The following provides information on the specifications, LED indicators and description and error codes for the 140CPU43412A Controller Module.
This module is functionally identical to the non-"A" version, however, the following z z z should be considered: z If you are using the module in a Hot Standby topology, then you must use either two non-"A" models or two "A" models.
The "A" version requires a new flash executive.
The "A" version and non-"A" flash executives are not interchangeable.
Schneider Automation software (Concept, ProWORX, and Modsoft) supports the
"A" version. Any existing or new 140CPU43412 program configuration will load into a 140CPU43412A without any modifications.
The following figure shows the CPU Module and its components.
LED Area
Battery
Key Switch
Modbus
Connector
Modbus
Connector
Modbus Plus
Connector
140
CPU 434 12A
486 CONTROLLER
Slide
Model Number
Module Description
Color Code
Removable door
Part #043513804
Customer Identification Label
(Fold label and place it inside door) Part #31002249
Date
Batt.
Installed
Dey
ASCII
RTU mem Switch
Modbus
Comm 1
Modbusm
Comm 2
Modbus
Plus
Network
Node
X
156
840 USE 100 00 11/2004
Specifications
CPU Modules
The following table shows the specifications for the CPU43412A Controller module.
Specifications
User Logic/Reference
Capacity
984
Ladder
Logic
Discrete Register Extended
Register
IEC
Application
96 k 800 k 64 k words
64 k 57 k
57,766 4XX registers max
Only if:
0XXX = 16 and
1XXX = 16 and
3XXX = 16
Reference Capacity
Discrete 64 k - any mix
Local I/O
Maximum I/O Words 64 In and 64 Out*
Maximum Number of I/O Racks 2 (Requires Expander)
Remote I/O
Maximum I/O Words per Drop
Maximum Number of Remote
Drops
Distributed I/O
64 In and 64 Out*
31
Maximum Number of Networks per System
Maximum Words per Network
(for every DIO drop, there is a minimum of words input of overhead.)
Maximum Words per Node
3**
500 In and 500 Out
30 In and 32 Out
*This information can be a mix of Discrete or Register I/O. For each word of register I/O configured, one word must be subtracted from the total available. The same holds true for each block of 8 bits or 16 bits of Discrete I/O configured--one word must be subtracted from the total available.
**Requires the use of two140NOM21X00 Option Modules.
Maximum Number of Network
Module Interfaces
6
Watchdog Timer
Logic Solve Time
250 ms (software adjustable)
0.1 ms / k to 0.5 ms / k
840 USE 100 00 11/2004
157
CPU Modules
Specifications
Battery
Type
Service Life
Shelf Life
3 V Lithium
1200 mAh
10 years with 0.5% loss of capacity per year
Battery Load Current at Power-off
Typical
Maximum
7
μ
A
210
μ
A
Communication
Modbus (RS-232)
Modbus Plus (RS-485)
Programming Software
Capability
2 serial port (9-pin D-shell)
1 network port (9-pin D-shell)
Modsoft, version 2.6 minimum
Concept, version 2.1 with B2.1 patch
Concept 2.2 with SR2
ProWORX NxT, version 2.0 minimum
ProWORX Plus, version 1.05 minimum
ProWORX 32, version 1.0 minimum
General
Diagnostics
Bus Current Required
Power Dissipation
TOD Clock
Operating Temperature
Power Up
RAM
RAM Address
Executive
Checksum
User Logic Check
Processor
Runtime
RAM
RAM Address
Executive Checksum
User Logic Check
1.25 A
6.25 W
+/- 8.0 seconds/day 0 ... 60° C
0 ... 60° C
158
840 USE 100 00 11/2004
CPU Modules
LED Indicators and Descriptions
The following figure shows the LED indicators.
Ready
Run
Bat low
Modbus
Modbus + Error A
Mem Prt
The following table provides a description of the LED indicators for the
140CPU43412A module.
LEDS
Ready
Run
Bat Low
Modbus
Modbus +
Error A
Mem Prt
Color
Green
Green
Red
Green
Green
Red
Amber
Indication when On
The CPU has passed power-up diagnostics.
The CPU has been started and is solving logic.
The battery needs replacing or is not present.
Communications are active on the Modbus port 1 or 2.
Communications are active on the Modbus Plus port.
Indicates communications error on the Modbus Plus port.
Memory is write-protected (the memory protect switch is on).
840 USE 100 00 11/2004
159
CPU Modules
LED Error Codes The following table shows the run LED error codes for the 140CPU43412A.
LED Error Codes
Number of Blinks
Continuous
2
3
4
623
624
625
626
627
61F
620
621
622
617
618
619
61E
609
614
615
616
605
606
607
608
72C
72F
730
604
82E
769
72A
72B
Code
0000
80B
80C
Error requested kernel mode ram error during sizing run output active failed
MB command handler stack error bus grant received not master asic on cpu master config write bad quantum bus DPM write failure plc asic loopback test plc asic BAD_DATA
UPI timeout error bad UPI response opcode
UPI bus diagnostic error modbus cmd-buffer overflow modbus cmd-length is zero modbus abort command error mbp bus interface error bad mbp response opcode timeout waiting for mbp mbp out of synchronization mbp invalid path page 0 not paragraph aligned bad external uart hardware bad external uart interrupt bad receive comm state bad transmit comm state bad comm state trn_asc bad comm state trn_rtu bad comm state rcv_rtu bad comm state rcv_asc bad modbus state tmr0_evt bad modbus state trn-int
160
840 USE 100 00 11/2004
CPU Modules
5
6
7
8
LED Error Codes
Number of Blinks Code
628
631
503
52D
402
300
301
8001
8002
8003
Error bad modbus state rcv-int bad interrupt ram address test error
P.O.S.T BAD MPU ERROR ram data test error
EXEC not loaded
EXEC Checksum
Kernal prom checksum error flash prog / erase error unexpected executive return
1RWH Information in the Code column is visible only with the Flash download utility.
Front Panel Slide
Switch
The slide switch is used to select the comm parameter settings for the Modbus
(RS232) ports. Three options are available:
1.
Setting the switch to the top position assigns ASCII functionality to the port.
2.
Setting the switch to the middle position assigns remote terminal unit (RTU) functionality to the port.
3.
Setting the switch to the bottom position lets you assign comm parameters to the port in software.
The figure shows the three options that are available on the front panel slide switch.
ASCII
RTU mem
1RWH The CPU hardware defaults to bridge mode when the front panel switch is set to RTU or ASCII mode. When networking controllers, a panel device connected to the CPU Modbus port can communicate with the controller to which it is connected, as well as log into any nodes on the Modbus Plus network.
840 USE 100 00 11/2004
161
CPU Modules
The following table shows the ASCII comm port parameters.
ASCII Comm Port Parameters
Baud 2,400
Parity
Data Bits
Even
7
Stop Bits
Device Address
1
Rear panel rotary switch setting
The following table shows the RTU comm port parameters. The comm parameters are set and cannot be changed.
RTU Comm Port Parameters
Baud 9,600
Parity
Data Bits
Even
8
Stop Bits
Device Address
1
Rear panel rotary switch setting
The following table shows the valid comm port parameters.
Valid Comm Port Parameters
Baud 19,200
9,600
7,200
4,800
3,600
2,400
Parity
Data Bits
Stop Bits
Device Address
2,000
1,800
Enable/Disable
Odd/Even
7 / 8
1 / 2
1 ... 247
1,200
600
300
150
134.5
110
75
50
162
840 USE 100 00 11/2004
Key Switch
CPU Modules
The key switch protects memory from programming changes while the controller is in operation. The following figure shows the key switch.
Mem
Prt
Stop Start
Mem
Prt
Stop Start
1RWH The key switch positions shown next to the switch (above) are for reference only and are marked on the module as indicated on the right.
The CPU43412A has 1435KByte of Flash EPROM memory, which can be used to save the program and the initial values of variables. On power up, if you have a program in flash memory, you can choose the desired operating mode using the
PLC MEM switch on the processor front panel. The 140CPU43412A has a key switch with Run, Mem Prt, and Stop positions.
Stop position
Mem Prt position
Start position
The application in Flash is not transferred to internal RAM: warm restart of the application.
The application in Flash is not transferred to internal RAM: warm restart of the application.
The application in Flash is automatically transferred to internal
RAM when the PLC processor is powered up: cold restart of the application.
840 USE 100 00 11/2004
163
CPU Modules
Rear Panel
Address Switch
The following figure shows the SW1 and SW2 settings for the Address Switch located on the rear panel.
8
9
0
1
2
4
6
5
8
9
0
1
2
6
5
4
SW1 (TENS)
SW2 (ONES)
SW1 sets the upper digit (tens) of the address. SW2 sets the lower digit (ones) of the address. The following table shows the SW1 and SW2 address settings.
SW1 and SW2 Address Settings
Node Address SW1
1 ... 9
10 ... 19
0
1
20 ... 29
30 ... 39
40 ... 49
50 ... 59
60 ... 64
4
5
2
3
6
SW2
1 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 4
1RWH If "0" or an address greater than 64 is selected, the Modbus + LED will be
"on" steady, to indicate the selection of an invalid address.
164
840 USE 100 00 11/2004
Key Switch
Description
Modbus
Connector
Pinouts
CPU Modules
The following table shows the key switch information.
Key Switch Description
Key switch
Position
Controller Status Memory
Protected
From
Programmer
Changes
Stop Controller is stopped and disables
Programmer changes.
Y
Mem Prt
Start
Controller may be either stopped or running and
Programmer changes are disabled. User cannot write to unlocated variables.
Y
Controller may be either stopped or running.
Programmer may make changes and start/stop the controller.
N
Will Accept
Programmer
Stop or Start
Key switch
Transition
N
N
Y
From Start or Memory
Protect: Stops controller, if running, and disables
Programmer changes
From Stop or Start:
Prevents
Programmer changes, controller run status is not changed
From Stop: Enables
Programmer changes, starts controller.
From Memory
Protect: Enables programmer changes, starts controller if stopped.
All Quantum CPUs are equipped with a nine-pin RS-232 connector that support
Modicon’s proprietary Modbus communication protocol. The following is the Modbus port pinout connections for nine-pin and 25-pin connections.
1RWH
Although the Modbus ports electrically support existing Modbus cables, it is recommended that a Modbus programming cable (Part # 990NAA26320 or
990NAA26350) be used. This cable has been designed to fit under the door of a
Quantum CPU or NOM module.
840 USE 100 00 11/2004
165
CPU Modules
Modbus Port
Modem Support
Modbus Port 1 has full modem interfacing ability. Modbus Port 2 RTS/CTS connections function properly for normal non-modem communications but do not support modems.
Modbus Ports
Pinout
Connections
Figure
The following figure shows the Modbus port pinout connections for 9-pin and 25-pin connections.
IBM-AT
9-Pin Female
CD 1
Quantum
9-Pin Male
1 SHIELD
IBM-XT
25-Pin Female
SHIELD
1
Quantum
9-Pin Male
1 SHIELD
RX
TX
2
3
2
3
RX
TX
TX
RX
2
3
2
3
RX
TX
DTR
GRND
4
5
4
5
DTR
GRND
RTS
CTS
DSR
4
5
6
4
5
6
DTR
GRND
DSR DSR
RTS
CTS
6
7
8
6
7
8
9
DSR
RTS
CTS
NC
GRND
NC
DTR
7
8
20
7
8
9
RTS
CTS
NC
Modbus Ports
Pinout
Connections for
Portable
Computers
The following figure shows the Modbus port pinout connections for portable (laptop) computers.
IBM-AT
9-Pin Female
Quantum
9-Pin Male
CD
RX
TX
DTR
GRND
DSR
RTS
CTS
SHIELD
RX
TX
DTR
GRND
DSR
RTS
CTS
NC NC
The following is the abbreviation key for the above figures.
TX: Transmitted Data
RX: Received Data
RTS: Request to Send
DSR: Data Set Ready
DTR: Data Terminal Ready
CTS: Clear to Send
NC: No Connection
CD: Carrier Detect
166
840 USE 100 00 11/2004
CPU Modules
140CPU53414 CPU Module
Overview
CPU Module
The following provides information on the 140CPU53414 Controller module –
CPU 4M, 1xModbus Plus, Max IEC Program – 2.5 M.
The following figure shows the CPU Module and its components.
LED Area
Battery
Key Switch
Modbus
Connector
Modbus
Connector
Modbus Plus
Connector
&38
586 CONTROLLER
Model Number
Module Description
Color Code
Removable door
Part #043513804
Slide
Switch
Customer Identification Label
(Fold label and place it inside door) Part #31000226
Date
Installed
Batt.
Batt.
Spare mem prt off not used
ASCII
RTU mem
Modbus
Modbus
Modbus
Plus
Network
Node
X
840 USE 100 00 11/2004
167
CPU Modules
Specifications
168
The following table shows the specification for the 140CPU53414 CONTROLLER module.
Specifications
User Logic/Reference Capacity 984 Ladder
Logic
64 k words
Discrete
64 k
57,766 4XX registers max
Only if:
0XXX = 16 and
1XXX = 16 and
3XXX = 16
Register
57 k
Extended
Register
96 k
Reference Capacity
Discrete
Local I/O (Main Backplane)
Maximum I/O Words
64 k - any mix
Maximum Number of I/O Racks
Remote I/O
64 In and 64 Out*
2 (Requires Expander)
Maximum I/O Words per Drop 64 In and 64 Out*
Maximum Number of Remote Drops 31
Distributed I/O
Maximum Number of Networks per
System
3**
Maximum Words per Network. (For every DIO drop, there is a minimum of words input of overhead.)
500 In and 500 Out
Maximum Words per Node
Maximum Number of Option
Module Interfaces
30 In and 32 Out
Supports up to six network modules (i.e., Modbus Plus,
Ethernet and Multi-Axis Motion option modules) using the option module interface technique.
Note: Only two Modbus Plus modules can have full functionality, including Quantum DIO support.
Watchdog Timer
Logic Solve Time
Battery
Service Life
250 ms (S/W adjustable)
0.1 ms/k to 0.5 ms/k
3 V Lithium
1200 mAh
Shelf Life
Battery Load Current @ Power-off
10 years with 0.5% loss of capacity per year
Typical 14
μ
A
840 USE 100 00 11/2004
840 USE 100 00 11/2004
CPU Modules
Specifications
Maximum
Communication
Modbus (RS-232)
Modbus Plus (RS-485)
General
Diagnostics
420
μ
A
2 serial port (9-pin D-shell)
1 network port (9-pin D-shell)
Bus Current Required
Power dissipation
TOD Clock
Operating Temperature
Power Up Runtime
RAM RAM
RAM Address
Executive Checksum
RAM Address
Executive Checksum
User Logic Check User Logic Check
Processor
1.8 A
9 W
+/- 8.0 seconds/day 0 ... 60° C
0 ... 45° C
*This information can be a mix of Discrete or Register I/Os. For each word of
Register I/O configured, one word of I/O words must be subtracted from the total available. The same holds true for each block of 8 bits or 16 bits of Discrete I/O configured – one word of Register I/O must be subtracted from the total available.
**Requires the use of two 140NOM21x00 Option Modules.
169
CPU Modules
LED Indicators and Descriptions
The following figure shows the LED indicators.
Ready
Run
Bat Low
Modbus
Modbus + Error A
Mem Prt
The following table shows the LED descriptions.
LED Descriptions
LEDS Color
Ready
Run
Green
Green
Bat Low
Modbus
Modbus +
Error A
Mem Prt
Red
Green
Green
Red
Amber
Indication when On
The CPU has passed power-up diagnostics.
The CPU has been started and is solving logic.
The battery needs replacing or is not present.
Communications are active on Modbus port 1 or 2.
Communications are active on the Modbus Plus port.
Indicates communications error on the Modbus Plus port.
Memory is write-protected (the memory protect switch is on).
170
840 USE 100 00 11/2004
CPU Modules
LED Error Codes The following table shows the run LED error codes for the 140CPU53414 module.
LED Error Codes
Number of Blinks
Continuous
2
3
4
623
624
625
626
627
61F
620
621
622
617
618
619
61E
609
614
615
616
605
606
607
608
72C
72F
730
604
82E
769
72A
72B
Code
0000
80B
80C
Error requested kernel mode ram error during sizing run output active failed
MB command handler stack error bus grant received not master asic on cpu master config write bad quantum bus DPM write failure plc asic loopback test plc asic BAD_DATA
UPI timeout error bad UPI response opcode
UPI bus diagnostic error modbus cmd-buffer overflow modbus cmd-length is zero modbus abort command error mbp bus interface error bad mbp response opcode timeout waiting for mbp mbp out of synchronization mbp invalid path page 0 not paragraph aligned bad external uart hardware bad external uart interrupt bad receive comm state bad transmit comm state bad comm state trn_asc bad comm state trn_rtu bad comm state rcv_rtu bad comm state rcv_asc bad modbus state tmr0_evt bad modbus state trn-int
840 USE 100 00 11/2004
171
CPU Modules
5
6
7
8
LED Error Codes
Number of Blinks Code
628
631
503
52D
402
300
301
8001
8002
8003
Error bad modbus state rcv-int bad interrupt ram address test error
P.O.S.T BAD MPU ERROR ram data test error
EXEC not loaded
EXEC Checksum
Kernal prom checksum error flash prog / erase error unexpected executive return
Front Panel Slide
Switch
The slide switch, located on the front panel of the CPU, is used to select the communication parameter settings for the Modbus (RS-232) ports. Three positions are available:
1.
Setting the switch to the top position assigns ASCII functionality to the port.
2.
Setting the switch to the middle position assigns remote terminal unit (RTU) functionality to the port.
3.
Setting the switch to the bottom position lets you assign comm parameters to the port in software.
The slide switch:
ASCII
RTU mem
1RWH The CPU hardware defaults to bridge mode when the front panel switch is set to RTU or ASCII mode. When networking controllers, a panel device connected to the CPU Modbus port can communicate with the controller to which it is connected, as well as log into any nodes on the Modbus Plus network.
172
840 USE 100 00 11/2004
840 USE 100 00 11/2004
CPU Modules
Setting the slide switch to the top position assigns ASCII functionality to the port; the following communication parameters are set and cannot be changed.
ASCII Communication Port Parameters
Baud 2,400
Parity
Data Bits
Even
7
Stop Bits
Device Address
1
Rear panel rotary switch setting
Setting the slide switch to the middle position assigns remote terminal unit (RTU) functionality to the port; the following communication parameters are set and cannot be changed.
RTU Communication Port Parameters
Baud 9,600
Parity
Data Bits
Even
8
Stop Bits
Device Address
1
Rear panel rotary switch setting
Setting the slide switch to the bottom position gives you the ability to assign communication parameters to the port in software; the following parameters are valid.
Valid Communication Port Parameters
Baud 19,200
9,600
7,200
Parity
4,800
3,600
2,400
2,000
1,800
Enable/Disable
Odd/Even
Data Bits
Stop Bits
Device Address
7 / 8
1 / 2
1 ... 247
1,200
600
300
150
134.5
110
75
50
173
CPU Modules
Key Switch
Key Switch
Description
The key switch, located on the front of the CPU, is used to protect memory from programming changes while the controller is in operation. The following figure shows the key switch.
Stop
Stop
Mem
Prt
Start
Mem
Prt
Start
1RWH The key switch positions shown on the switch (above, left) are for reference only and are marked on the module as indicated on the right.
The following table provides descriptions of the key switch information.
Key Switch Description
Key
Switch
Position
Stop
Controller Status
Controller is stopped and disables
Programmer changes.
Mem Prt Controller may be either stopped or running and
Programmer changes are disabled. The user cannot write to unlocated variables.
Y
Memory
Protected
From
Programmer
Changes
Will Accept
Programmer
Stop or Start
Key Switch Transition
Y N
N
From Start or Memory
Protect: Stops controller, if running, and disables
Programmer changes
From Stop or Start:
Prevents Programmer changes, controller run status is not changed
Start Controller may be either stopped or running.
Programmer may make changes and start/stop the controller
N Y From Stop: Enables
Programmer changes, starts controller.
From Memory Protect:
Enables programmer changes, starts controller if stopped.
174
840 USE 100 00 11/2004
Rear Panel
Switches
CPU Modules
Two rotary switches (refer to the following illustration and table) are located on the rear panel of the CPU. They are used for setting Modbus Plus node and Modbus port addresses.
1RWH The highest address that may be set with these switches is 64.
SW1 (the top switch) sets the upper digit (tens) of the address; SW2 (the bottom switch) sets the lower digit (ones) of the address. The illustration below shows the correct setting for an example address of 11.
The following figure shows SW1 and SW2.
8
9
0
1
2
6
5
4
8
9
0
1
2
6
5
4
SW1 (TOP)
SW2 (BOTTOM)
The following table shows the SW1 and SW2 address settings.
Node Address
1 ... 9
10 ... 19
20 ... 29
30 ... 39
40 ... 49
50 ... 59
60 ... 64
5
6
3
4
1
2
SW1
0
SW2
1 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 4
1RWH
If "0" or an address greater than 64 is selected, the Modbus + LED will be
"on" steady, to indicate the selection of an invalid address.
Modbus Port
Modem Support
Modbus Port 1 has full modem interfacing ability. Modbus Port 2 RTS/CTS connections function properly for normal non-modem communications but do not support modems.
840 USE 100 00 11/2004
175
CPU Modules
Modbus
Connector
Pinouts
All Quantum CPUs are equipped with a 9-pin RS-232C connector that supports
Modicon’s proprietary Modbus communication protocol. The following is the Modbus port pinout connections for 9-pin and 25-pin connections.
1RWH Although the Modbus ports electrically support existing Modbus cables, it is recommended that a Modbus programming cable (Part # 990NAA26320 or
990NAA26350) be used. This cable has been designed to fit under the door of a
Quantum CPU or NOM module.
Modbus Ports
Pinout
Connections
The following figure shows the Modbus port pinout connections for 9-pin and 25-pin connections.
IBM-AT
9-Pin Female
CD 1
RX
TX
DTR 4
GRND 5
2
3
DSR
RTS
CTS
6
7
8
Quantum
9-Pin Male
1
2
3
4
5
6
7
8
9
SHIELD
RX
TX
DTR
GRND
DSR
RTS
CTS
NC
IBM-XT
25-Pin Female
SHIELD
TX
RX
RTS
CTS
DSR
GRND
NC
DTR
1
2
3
4
5
6
7
8
20
Quantum
9-Pin Male
1 SHIELD
6
7
8
9
4
5
2
3
RX
TX
DTR
GRND
DSR
RTS
CTS
NC
176
840 USE 100 00 11/2004
CPU Modules
Modbus Ports
Pinout
Connections for
Portable
Computers
The following figure shows the Modbus port pinout connections for 9-pin portable
(laptop) computers.
IBM-AT
9-Pin Female
Quantum
9-Pin Male
CD
RX
TX
DTR
GRND
DSR
RTS
CTS
NC
SHIELD
RX
TX
DTR
GRND
DSR
RTS
CTS
NC
The following is the abbreviation key for the above figures.
TX: Transmitted Data
RX: Received Data
RTS: Request to Send
DSR: Data Set Ready
DTR: Data Terminal Ready
CTS: Clear to Send
NC: No Connection
CD: Carrier Detect
840 USE 100 00 11/2004
177
CPU Modules
140CPU53414A CPU Module
Overview
CPU Module
This unit provides information on the specifications, LED indicators and description and error codes for the 140CPU53414A Controller Module.
This module is functionally identical to the non-"A" version, however, the following z z z should be considered: z If you are using the module in a Hot Standby topology, then you must use either two non-"A" models or two "A" models.
The "A" version requires a new flash executive.
The "A" version and non-"A" flash executives are not interchangeable.
Schneider Automation software (Concept, ProWORX, and Modsoft) supports the
"A" version. Any existing or new 140CPU53414 program configuration will load into a 140CPU53414A without any modifications.
The following figure shows the CPU Module and its components.
LED
Area
Battery
Key Switch
Modbus
Connector
Modbus
Connector
Modbus Plus
Connector
140
CPU 534 14A
586 CONTROLLER
Slide
Model Number
Module Description
Color Code
Removable door
Part #043513804
Customer Identification Label
(Fold label and place it inside door) Part #31002249
Date
Batt.
Installed
Switch
Modbus
Comm 1
Modbus
Comm 2
Modbus
Plus
ASCII
RTU mem
Network
Node
X
178
840 USE 100 00 11/2004
Specifications
CPU Modules
The following table shows the specifications for the CPU53414A Controller module.
Specifications
User Logic/Reference Capacity 984
Ladder
Logic
Discrete Register Extended
Register
IEC
Application
Memory
96 k 2.7M
64 k words
64 k 57 k
57,766 4XX registers max
Only if:
0XXX = 16 and
1XXX = 16 and
3XXX = 16
Reference Capacity
Discrete 64 k - any mix
Local I/O )
Maximum I/O Words 64 In and 64 Out*
Maximum Number of I/O Racks 2 (Requires Expander)
Remote I/O
Maximum I/O Words per Drop
Maximum Number of Remote
Drops
Distributed I/O
64 In and 64 Out*
31
Maximum Number of Networks per System
3**
Maximum Words per Network (for every DIO drop, there is a minimum of words input of overhead.)
500 In and 500 Out
Maximum Words per Node
Maximun Number of Network
Option Module Interfaces
30 In and 32 Out
*This information can be a mix if Discrete or Register I/O. For each word of register I/O configured, one word of I/O words must be subtracted from the total available. The same holds true for each block of 8 bits or 16 bits of Discrete I/O configured---one word Register I/
O must be subtracted from the total available.
**Requires the use of two 140NOM21X00 Option Modules.
Supports up to six network modules (i.e., Modbus Plus,
Ethernet and Multi-Axis Motion option modules) using the option module interface technique (see
).
Note : Only two Modbus Plus modules can have full functionality, Including Quantum DIO support.
840 USE 100 00 11/2004
179
CPU Modules
Specifications
Watchdog timer
Logic Solve Time
250 ms (software adjustable)
0.1 ms/k to 0.5 ms/k
Battery
Type
Service Life
Shelf Life
3 V Lithium
1200 mAh
10 years with 0.5% loss of capacity per year
Battery Load Current at Power-off
Typical
Maximum
14
μ
A
420
μ
A
Communication
Modbus (RS-232)
Modbus Plus (RS-485)
Programming Software
Capability
2 serial port (9-pin D-shell)
1 network port (9-pin D-shell)
Modsoft, version 2.6
Concept, version 2.1 with B2.1 patch exec
Concept 2.2 with SR2
ProWorx NxT, version 2.0
ProWorx Plus, version 1.05
General
Diagnostics
Bus Current Required
Power dissipation
TOD Clock
Operating Temperature
Power Up
RAM
RAM Address
Executive
Checksum
User Logic Check
Processor
Runtime
RAM
RAM Address
Executive Checksum
User Logic Check
1.25 A
6.25 W
+/- 8.0 seconds/day 0 ... 60° C
0 ... 50° C
180
840 USE 100 00 11/2004
CPU Modules
LED Indicators and Descriptions
The following figure shows the LED indicators.
Ready
Run
Bat Low
Modbus
Modbus + Error A
Mem Prt
The following table provides a description of the LED indicators for the
140CPU53414A module.
LED Descriptions
LEDS Color
Ready
Run
Green
Green
Bat Low
Modbus
Modbus +
Error A
Mem Prt
Red
Green
Green
Red
Amber
Indication when On
The CPU has passed power-up diagnostics.
The CPU has been started and is solving logic.
The battery needs replacing or is not present.
Communications are active on Modbus port 1 or 2.
Communications are active on the Modbus Plus port.
Indicates communications error on the Modbus Plus port.
Memory is write-protected (the memory protect switch is on).
840 USE 100 00 11/2004
181
CPU Modules
LED Error Codes The following table shows the run LED error codes for the 140CPU53414A.
LED Error Codes
Number of Blinks
Continuous
2
3
4
623
624
625
626
627
61F
620
621
622
617
618
619
61E
609
614
615
616
605
606
607
608
72C
72F
730
604
82E
769
72A
72B
Code
0000
80B
80C
Error requested kernel mode ram error during sizing run output active failed
MB command handler stack error bus grant received not master asic on cpu master config write bad quantum bus DPM write failure plc asic loopback test plc asic BAD_DATA
UPI timeout error bad UPI response opcode
UPI bus diagnostic error modbus cmd-buffer overflow modbus cmd-length is zero modbus abort command error mbp bus interface error bad mbp response opcode timeout waiting for mbp mbp out of synchronization mbp invalid path page 0 not paragraph aligned bad external uart hardware bad external uart interrupt bad receive comm state bad transmit comm state bad comm state trn_asc bad comm state trn_rtu bad comm state rcv_rtu bad comm state rcv_asc bad modbus state tmr0_evt bad modbus state trn-int
182
840 USE 100 00 11/2004
CPU Modules
5
6
7
8
LED Error Codes
Number of Blinks Code
628
631
503
52D
402
300
301
8001
8002
8003
Error bad modbus state rcv-int bad interrupt ram address test error
P.O.S.T BAD MPU ERROR ram data test error
EXEC not loaded
EXEC Checksum
Kernal prom checksum error flash prog / erase error unexpected executive return
1RWH Information in the Code column is visible only with the Flash download utility.
Front Panel Slide
Switch
The slide switch, located on the front of the CPU, is used to select the comm parameter settings for the Modbus (RS232) ports. Three options are available.
1.
Setting the switch to the top position assigns ASCII functionality to the port.
2.
Setting the switch to the middle position assigns remote terminal unit (RTU) functionality to the port.
3.
Setting the switch to the bottom position lets you assign comm parameters to the port in software.
Slide switch::
ASCII
RTU mem
1RWH The CPU hardware defaults to bridge mode when the front panel switch is set to RTU or ASCII mode. When networking controllers, a panel device connected to the CPU Modbus port can communicate with the controller to which it is connected, as well as log into any nodes on the Modbus Plus network.
840 USE 100 00 11/2004
183
CPU Modules
The following table shows the ASCII comm port parameters.
ASCII Comm Port Parameters
Baud 2,400
Parity
Data Bits
Even
7
Stop Bits
Device Address
1
Rear panel rotary switch setting
The following table shows the RTU comm port parameters. The comm parameters are set and cannot be changed.
RTU Comm Port Parameters
Baud 9,600
Parity
Data Bits
Even
8
Stop Bits
Device Address
1
Rear panel rotary switch setting
The following table shows the valid comm port parameters.
Valid Comm Port Parameters
Baud 19,200
9,600
7,200
4,800
3,600
2,400
Parity
Data Bits
Stop Bits
Device Address
2,000
1,800
Enable/Disable
Odd/Even
7 / 8
1 / 2
1 ... 247
1,200
600
300
150
134.5
110
75
50
184
840 USE 100 00 11/2004
CPU Modules
Key Switch The following figure shows the key switch.
Mem
Prt
Mem
Prt
Stop Start
Stop Start
1RWH The key switch positions shown next to the switch (above, left) are for reference only and are marked on the module as indicated on the right.
The CPU53414A has 1435KByte of Flash EPROM memory, which can be used to save the program and the initial values of variables. On power up, if you have a program in flash memory, you can choose the desired operating mode using the
PLC MEM switch on the processor front panel. The 140CPU53414A has a key switch with Run, Mem Prt, and Stop positions.
Stop position The application in Flash is not transferred to internal RAM: warm restart of the application.
Mem Prt position The application in Flash is not transferred to internal RAM: warm restart of the application.
Start position The application in Flash is automatically transferred to internal RAM when the PLC processor is powered up: cold restart of the application.
840 USE 100 00 11/2004
185
CPU Modules
Key Switch
Description
The following table provides a description of the key switch information.
Key Switch Description
Key
Switch
Position
Stop
Controller Status
Controller is stopped and disables
Programmer changes.
Y
Memory
Protected
From
Programmer
Changes
Will Accept
Programmer
Stop or Start
Key Switch Transition
N
N
From Start or Memory
Protect: Stops controller, if running, and disables
Programmer changes
From Stop or Start:
Prevents Programmer changes, controller run status is not changed
Mem Prt Controller may be either stopped or running and
Programmer changes are disabled. The user cannot write to unlocated variables.
Y
Start Controller may be either stopped or running. Programmer may make changes and start/stop the controller
N Y From Stop: Enables
Programmer changes, starts controller.
From Memory Protect:
Enables programmer changes, starts controller if stopped.
186
840 USE 100 00 11/2004
Rear Panel
Switches
CPU Modules
The following figure shows the SW1 and SW2 settings.
8
9
0
1
2
4
6
5
8
9
0
1
2
4
6
5
SW1 (TOP)
SW2 (BOTTOM)
SW1 sets the upper digit (tens) of the address. SW2 sets the lower digit (ones) of the address. The following table shows the SW1 and SW2 address settings.
SW1 and SW2 Address Settings
Node Address SW1
1 ... 9
10 ... 19
0
1
20 ... 29
30 ... 39
40 ... 49
50 ... 59
60 ... 64
4
5
2
3
6
SW2
1 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 4
Modbus
Connector
Pinouts
1RWH If "0" or an address greater than 64 is selected, the Modbus + LED will be
"on" steady, to indicate the selection of an invalid address.
All Quantum CPUs are equipped with a nine-pin RS-232 connector that support
Modicon’s proprietary Modbus communication protocol. The following is the Modbus port pinout connections for nine-pin and 25-pin connections.
1RWH Although the Modbus ports electrically support existing Modbus cables, it is recommended that a Modbus programming cable (Part # 990NAA26320 or
990NAA26350) be used. This cable has been designed to fit under the door of a
Quantum CPU or NOM module.
Modbus Port
Modem Support
Modbus Port 1 has full modem interfacing ability. Modbus Port 2 RTS/CTS connections function properly for normal non-modem communications but do not support modems.
840 USE 100 00 11/2004
187
CPU Modules
Modbus Ports
Pinout
Connections
The following figure shows the Modbus port pinout connections for 9-pin and 25-pin connections.
IBM-AT
9-Pin Female
CD 1
Quantum
9-Pin Male
1 SHIELD
IBM-XT
25-Pin Female
SHIELD 1
Quantum
9-Pin Male
1 SHIEL
RX
TX
2
3
2
3
RX
TX
TX
RX
2
3
2
3
RX
TX
DTR
GRND
4
5
4
5
DTR
GRND
RTS
CTS
4
5
4
5
DTR
GRND
DSR 6 6 DSR DSR 6
6 DSR
RTS
CTS
7
8
7
8
9
RTS
CTS
NC
GRND 7
NC
DTR
8
20
7
8
9
RTS
CTS
NC
Modbus Ports
Pinout
Connections for
Portable
Computers
The following figure shows the Modbus port pinout connections for 9-pin portable computers.
IBM-AT
9-Pin Female
Quantum
9-Pin Male
CD
RX
TX
DTR
GRND
DSR
RTS
CTS
SHIELD
RX
TX
DTR
GRND
DSR
RTS
CTS
NC NC
The following is the abbreviation key for the above figures.
TX: Transmitted Data
RX: Received Data
RTS: Request to Send
DSR: Data Set Ready
DTR: Data Terminal Ready
CTS: Clear to Send
NC: No Connection
CD: Carrier Detect
188
840 USE 100 00 11/2004
Quantum Field Bus Modules
8
At a Glance
Overview
What’s in this
Chapter?
This chapter contains information on various Quantum Field Bus Modules.
This chapter contains the following topics:
Topic
140CRP81100 Profibus DP Master Communications Module
140EIA92100 Quantum AS-i Master Module
140NOA6XXXX Quantum InterBus Communications Modules
140NOL911X0 Quantum LonWorks Network Option Modules
Page
840 USE 100 00 11/2004
189
Quantum Field Bus Modules
140CRP81100 Profibus DP Master Communications Module
Overview The following information describes the 140CRP81100 Field Bus Communication
Module, which provides interface to Profibus-DP networks for the Quantum
Automation Series systems.
Related
Documentation
For a detailed discussion of the planning, installation and use of a Quantum Profibus system, refer to the Modicon TSX Quantum Profibus-DP Under Modsoft User
Manual (840 USE 468 00), Profibus-DP Under Concept Manual (840 USE 487 00), and the Profibus-DP Configutator for CRP 811 (840 USE 469 00).
Communicatons
Module
View of the 140CRP81100 communications module and the Profibus tap:
Module Model
Number
LED Status Display
Customer Identification Label
(Fold label and place it inside door)
Removable Door
Part #043513804
RS-232C port
PCMCIA Card
(467NHP911)
PROFIBUS RS-485 Port
Profibus Tap (490NAE911)
190
840 USE 100 00 11/2004
LED Status
Quantum Field Bus Modules
The following figure shows the LED Status display.
Active
Ready Fault
Backplane
PROFIBUS
DP S/R
Load
The following table provides descriptions of the Status LEDs.
LEDs
Active
Ready
Fault
Backplane
PROFIBUS
DP S/R
Load
Color
Green
Green
Red
Green
Green
Function
On
Flashing
On
On
Flashing
Flashing
Description
Indicates bus communication is present
The flash ram load operation is active
Module is operational
Indicates fault. Refer to LED fault codes in manual 840USE46800.
Indicates fault. Refer to LED fault codes in manual 840USE46800.
Erroneous configuration data or
PROFIBUS fault
Green Fast flashing frequency Sending/receiving DP bus data
Medium flashing frequency Slaves are configuring
Slow flashing frequency
Flashing with fault code
Yellow Flashing
Waiting for configuration data
Erroneous configuration data
Flashing with fault code
Configuration data load operation active
Load operation fault
840 USE 100 00 11/2004
191
Quantum Field Bus Modules
&$87,21
5HVHWWLQJ)DXOW/('
To reset the fault LED the CRP811 must be power cycled or hot swapped.
)DLOXUHWRIROORZWKLVSUHFDXWLRQFDQUHVXOWLQLQMXU\RUHTXLSPHQWGDPDJH
:$51,1*
+RW6ZDSSLQJ5HVWULFWLRQ
Modules may be hot swapped when the area is known to be non-hazardous. Do not hot swap modules in a Class 1, Division 2 environment.
)DLOXUHWRIROORZWKLVSUHFDXWLRQFDQUHVXOWLQGHDWKVHULRXVLQMXU\RU
HTXLSPHQWGDPDJH
PROFIBUS RS-
485 Port d-Sub pinouts
Below are the pinouts for the PROFIBUS RS-485 port.
6
8
3
5
Pin
1
5
9
4
8
3
7
2
6
1
Legend to pinouts for the RS-485 port:
Signal
Shield
RxD/TxD-P
DGND
VP
RxD/TxD-N
Function
Shield, Protective Ground
Receive/Transmit-Data-P (+)
5 V common
+5 V
Receive/transmit-data-N(-)
192
840 USE 100 00 11/2004
RS-232C Port Below are pinouts for the RS-232C port
1
6
2
7
3
8
4
5
9
Legend to pinouts for the RS-232C port:
7
8
3
5
Pin
2
Signal
RXD
TXD
GND
RTS
CTS
Function
Received Data
Transmitted Data
Signal Ground
Request to Send
Clear to Send
Quantum Field Bus Modules
840 USE 100 00 11/2004
193
Quantum Field Bus Modules
Specifications The following table shows the technical specifications for the 140CRP81100
Communication Module:
Specifications
Programming software
Bus current required
Power dissipation
Data Interface
RS-232C
Modsoft version 2.32 or greater
Concept version 2.2 or greater
1.2 A
6.5 W
9 pin D-shell non-isolated, Shielded cable, 3 m max; 19.2 Kbps default.
Profibus, up to 12 Mbps
Local backplane only
RS-485
Installation
Bus Specifications
Bus nodes
Bus lenths, transmission rates (for 12 Mbps cable)
Transmission media
Connection interface
Node type
Bus access procedure
Transmission procedure
Frame length
Data unit length
Data security
Node addresses max. 32 max. 1.2 km at 9.6 Kbps max 1.2 km at 19.2 Kbps max. 1.2 km at 93.75 Kbps max 1.0 km at 187.5 Kbps max 0.5 km at 500 Kbps max 0.2 km at 1.5 Mbps max 0.1 km at 3 Mbps max 0.1 km at 6 Mbps max 0.1 km at 12 Mbps shielded twisted pair
EIA RS-485
Master class 1
Master/slave to dP bus slaves half-duplex
Max. 255 bytes
Max. 246 bytes
Hamming distance, HD = 4
1 ... 126
194
840 USE 100 00 11/2004
Quantum Field Bus Modules
140EIA92100 Quantum AS-i Master Module
Overview
Related
Documentation
The 140EIA92100 field bus communications module provides communications interface to AS-i networks for the Quantum Automation Series systems.
For more detailed information see Modicon Quantum AS-i Master Module manual, part number 840USE11700, or start the newmod.hlp from your Concept CD. To locate it, go to the root of your Concept Installation directory. Example of path:
Drive_X:\Concept\*.hlp
1RWH The newmod help system on your Concept CD contains a hyperlink labeled
"Back to Main Content." This link will not return you to Concept 2.5 Help.
840 USE 100 00 11/2004
195
Quantum Field Bus Modules
Communications
Module
The following diagram provides a view of the 140EIA92100 communications module.
1
2
3
4
5
6
7
1 LED Display
2 AS-i (Red): ON shows the module is not powered. Flashing shows automatic addressing enabled.
3 SLV/BUS (Green): ON when LEDs 0-31 are in bus display mode.
4 I/O Status (Green): ON when LEDs 0-31 are in slave display mode.
5 Mode (Push Button): Press and hold this button to change from slave mode to bus mode.
6 Address (Push Button): Press this button to scroll through the 32 slaves. Hold to reverse direction of the scroll.
7 AS-i Channel Cable Connector: Connects module to AS-i cable and AS-i power supply.
196
840 USE 100 00 11/2004
Quantum Field Bus Modules
LED Display and
Descriptions
Diagram of the LED display:
5
6
3
4
7
0
B
1
2
11
12
13
14
15
8
Active
16
9
10
17
18
19
20
21
22
23
F
24
25
26
27
28
29
30
31
The following table provides LED descriptions.
LED Descriptions
LED Color
Active
F
Green
Red
B
0-31
Green
Green
Description
Bus communication is present.
Fault on the AS-i bus.
Steady: module fault
Flashing: bad bus configuration or slave address
Communication exists between master and slaves.
Slave indicators.
LED Bus Mode z z
Each indicator lamp 1-31 corresponds to a slave address on the bus.
On: Slave is present.
Flashing: Slave is mapped but not detected, or detected but not mapped. It may also be projected and detected, but not activated (bad profile or I/O code).
z Off: Slave is neither mapped nor detected.
Example:
On
Off
Flashing
10
11
12
8
9
13
14
15
2
3
4
0
1
5
6
7
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
SLV/BUS
I/O STATUS
Select with mode pushbutton
840 USE 100 00 11/2004
197
198
Quantum Field Bus Modules
LED Slave I/O
Mode
Slave mode (SLV) figure:
Display of the address of the selected slave:
On: number of the selected slave
A short press on the address button will change the selected slave.
Slave 3 selected
0 8 7 24
1 9 0 25
2 10 18 26
11 19 27
4 12 20 28
5 13 21 29
6 14 22 30
7 15 23 31
SLV/BUS
I/O STATUS
Long press on the address push button
Display of the state of the I/O bits of the selected slave:
0-3: displays the state of the input bits
4-7: displays the state of the output bits
On: bit = 1
Off: bit = 0 or not significant
Input bits
{
Output bits
{
8 16 24
9 17 25
10 18 26
11 19 27
12 20 28
13 21 29
14 22 30
15 23 31
SLV/BUS
I/O STATUS
840 USE 100 00 11/2004
Quantum Field Bus Modules
LED Diagnostics State of Indicator Lamps:
B Active F
X X
X
(1)
X
(2)
X
X
Meaning
Module switched off.
Corrective Action
Switch the device on.
Operating in Protected
Mode (normal). Displaying
Outputs.
Operating in Protected
Mode (normal). Displaying
Inputs.
Fault on AS-i bus (selfprogramming possible).
⎯
⎯
Replace the faulty slave with a new identical slave.
Fault on AS-i bus (selfprogramming not possible).
Connect the terminal.
AS-i power supply fault or no slave on the AS-i bus.
Module self-tests in progress.
1. Check AS-i power supply.
2. Check the continuity of the
AS-i bus cable.
⎯
Indicator lamp is on.
Indicator lamp is off.
(1) Faulty slave ID is flashing.
(2) No slave ID numbers are flashing.
X
Indicator lamp is flashing.
X
Indicator lamp is in indeterminate state.
840 USE 100 00 11/2004
199
Quantum Field Bus Modules
AS-i Cable
Connection
The following figure shows the AS-i cable connection:
Brown wire
AS-i cable
Connector
AS-i
−
(Blue)
AS-i+
(Brown)
Blue wire
Specifications The following table provides specifications for the 140EIA92100 AS-i module:
Specifications
Master profile
Bus length
I/O
# slaves
Power supply
Scan time
Transmission
Polarity reversal
Bus current required
Power dissipation
Installation
Programming software
M2
100m max, no repeaters
124IN/124OUT
31 max
30Vdc @ 120mA max
156 msec x (n+2) if n < 31
156 msec x (n+1) if n = 31
167 kbits/sec
Non-destructive
250mA max
2.5W max
Local, RIO, DIO
Concept v2.5
ProWORX Nxt v2.1
Modsoft v2.61
200
840 USE 100 00 11/2004
Quantum Field Bus Modules
140NOA6XXXX Quantum InterBus Communications Modules
Overview This section includes information for the NOA6XXXX InterBus communications modules which provide interface to InterBus networks for the Quantum Automation
Series systems.
Related
Documentation
For more detailed information on the installation and use of Quantum InterBus modules, see the Modicon TSX Quantum 140NOA61110 User Manual
(840 USE 419 00; the Modicon TSX Quantum 140NOA61100 User Manual
(840 USE 418 00); and the TSX Quantum 140NOA62200 User Manual
(840 USE 497 00).
InterBus
Communications
Module
The following figure shows the NOA6XXXX InterBus Communications module.
Model Number
Module Description
Color Code
LED Display
12$;;;;;
CONTROLLER
Removable Door Customer Identification Label
(Fold label and place it inside door)
Seven Segment
Display
Reset Push Button
RS-232C Port
InterBus Port
X
840 USE 100 00 11/2004
201
Quantum Field Bus Modules
Specifications The following table shows the InterBus specifications.
Specifications
Data Interface
InterBus RS-485, isolated (500 V test voltage)
RS-232C maximum cable length As per DIN 66 020, non-isolated 20 m shielded
Data Transfer Frequency
Connection Styles
500 kbaud
Interbus
RS-232C (Use cable part number 990NAA26320 or
990NAA26350)
Bus Current Required
Power Dissipation
Installation
700 mA
Max. 3.7 W, typically 2.5 W
Local backplane only
202
840 USE 100 00 11/2004
Quantum Field Bus Modules
LED Indicators and Descriptions for NOA611X0
The following figure shows the NOA611X0 LED indicators.
R
IB-S Run
Active F
Master
RBUS
LBUS
Slave
DEA202
Memory
Start Up
BS Off
The following table shows the NOA611X0 LED descriptions.
LED Descriptions
LEDs Color
R Green
Active
F
IB-S Run
BS Off
Master
RBUS
LBUS
Slave
DEA202
Memory
Start Up
Red
Red
Red
Red
Green
Red
Green
Yellow
Red
Red
Red
Function
Ready. The firmware is running correctly and the module is ready for service.
Bus communication is active.
Fault. A fault occurred on the module.
The InterBus is functioning normally and carrying data.
One or more bus segments are shut down.
Processor fault. Fault on the InterBus processor or the communications processor has failed.
Remote bus fault. The remote bus has been diagnosed as defective.
Peripheral bus fault. The peripheral bus has been diagnosed as defective.
An InterBus node has reported a (module) fault.
Initialization fault with the DEA 202.
Memory fault.
The InterBus master is not operational.
840 USE 100 00 11/2004
203
Quantum Field Bus Modules
LED Indicators and Descriptions for NOA62200
The following figure shows the NOA62200 LED indicators.
140
NOA 622 00
INTERBUS Master
R Active
IBS-RUN
F
Slave
The following table shows the NOA62200 LED descriptions.
LED Descriptions
LEDs
R
Color
Green
Status
On
Meaning
Ready. The switch-on routine was completed successfully. The firmware is running correctly and the module is ready for operations. RAM and checksum are ok.
Flashing
Off
Green On
No firmware; or firmware is being loaded.
Module error.
Active The communication with the TSX Quantum CPU is active.
Fault. An error has occurred on the INTERBUS.
F
IB-S Run
Slave
Red
Green
Red
On
On The INTERBUS is functioning, normal data transfer.
Flashing cyclically.
The INTERBUS is ready.
No cyclic flashing.
No INTERBUS configuration (error message).
On An INTERBUS node is indicating a module error.
204
840 USE 100 00 11/2004
Quantum Field Bus Modules
Seven Segment
Display
The seven segment display is only applicable to the NOA61110 module.
Display
0
– | | –
– –
RBUS LED on
LBUS LED on
RBUS & LBUS
LEDs on
Slave LED on
Meaning
Interbus is not able to run.
Interbus is able to run but stopped.
Interbus is running.
Number of the defective remote bus segments.
Number of the defective peripheral bus.
Bus segment fault, interbus comm stopped. Faulted bus segment number (or next segment) displayed.
Bus segment number containing a faulted module.
Front Panel
Connections and
Controls
The InterBus module is equipped with an InterBus port and a Modbus Plus port, both are female 9-pin D connectors (see below for pinouts), and a reset push button.
InterBus Port Connect the remote bus cable to the female connector port labeled interbus. The following figure shows the InterBus port connection.
840 USE 100 00 11/2004
The following table shows the key to the remote bus.
6
7
4
5
2
3
Pin
1
Signal
DO
DI
GND
GND (NOA622 only)
VCC (NOA622 only)
DO
DI
Function
Data Out (+)
Data In (+)
Comm
F/O Interface
F/O Interface
Data Out (-)
Data In (-)
8
9
VCC (NOA622 only)
RBST (NOA622 only)
Auxiliary Supply for F/O Interface
RBST Coupling
Black circle = Pin occupied. White circle = N/C
205
Quantum Field Bus Modules
RS-232C Port Use a Modbus data cable, Part Number 990NAA26320 (2.7 m) or Part Number
990NAA26350 (15.5 m). The following figure shows the RS-232C port connection.
Reset Push
Button
Required
Loadables
The following table shows the key to the RS-232C port.
3
5
7
Pin
2
Signal
D2 (RXD)
D1 (TXD)
E2 (GND)
S2 (RTS)
8 M2 (CTS)
Black circle = Pin occupied. White circle = N/C
Function
Received Data
Transmitted Data
Signal Ground
Request to Send
Clear to Send
The reset push button performs a hardware reset of the module which must be done each time new firmware has been downloaded. This button allows you to reset the module without removing it from the backplane.
Loadables are accessible from Groupe Schneider’s World Wide Web site at http:// www.schneiderautomation.com. Click on the appropriate software under the
"Control Software" section on the home page.
1RWH 140CPU11302 does not support the 140NOA61110 or the 140NOA62200 module.
206
840 USE 100 00 11/2004
Quantum Field Bus Modules
Comparison of
NOA61100,
61110, and 62200
Modules
The following table provides a comparison of the NOA61100, 61110, and 62200 modules.
Characteristics
Physical Addressing
Logical Addressing
PCP Channel
NOA61100
Y
N
N
NOA61110
Y
Y
Y
Y
Y
NOA62200
Y
Y Startup Check of
Configuration
Support of Remote Bus
Branch
Y
Possible via user- program triggering one of the active bits 10 ... 15
Y
Y
N
3
Support for Hot Standby N
Number of NOAs in
Local Drop
3
Interbus Compatibility
Maximum Slaves
Configuration Tool
Generation 3
512
Phoenix Contact CMD
V1.21 or V1.30
Y
N
2 (140CPU11303)
6 (140CPUX341XA)
Generation 3
512
Generation 4
251
Phoenix Contact
CMD V1.21 or
V1.30
Sycon
TLX L FBC 10M
V2.725
Software Versions
Modsoft Rev. (min.)
Concept Rev. (min.)
ProWORX (min.)
2.4
2.0
2.0
2.4
2.1
2.0
N/A
2.5 SR2
N/A
840 USE 100 00 11/2004
207
Quantum Field Bus Modules
140NOL911X0 Quantum LonWorks Network Option Modules
Overview The NOL modules provide connectivity between a Modicon Quantum controller and a control network based on Echelon’s LonWorks technology. Once the NOL module has been installed in a Quantum backplane and configured, it can be bound to an existing LonWorks network, and installed as a standard node.
1RWH The NOL module requires a valid LonWorks configuration file (.XIF) loaded into it to define the LonWorks network variables to which it will be bound.
1RWH You must have a LonWorks compliant network management tool, such as
Metra Vision, to install an NOL module on a LonWorks network.
Related
Documentation
For more detailed information, see the Quantum Automation Series Network Option
Module for LonWorks (840 USE 109 00).
LonWorks
Network Option
Modules
The following figure shows the NOL911X0 LonWorks Network Option Module.
Model Number
Module Description
Color Code
LED Display
12/
CONTROLLER
Removable Door
Customer Identification Label
(Fold label and place it inside door)
Neuron ID
RS- 232 Serial
Port
Service Pin
Reset Button
Auxiliary LonWorks
Comm Port
Primary LonWorks
Comm Port
Domain
Subset 1
Subset 2
Node ID
Executive
Vers
X
208
840 USE 100 00 11/2004
Specifications
Quantum Field Bus Modules
The following table shows the specifications for the NOL911X0 module.
Specifications
Data Transfer Frequency 78 Kbps (140 NOL 911 10)
Connection Styles
Bus Current Required
Quantum Controllers
Remote I/O
Screw terminals, telephone jack
400 mA
V2.0 at a minimum
V2.0 at a minimum
LED Indicators,
Descriptions, and Status
The condition of the NOL module is indicated by the status (off, on, or blinking) of the LED indicators. The following figure shows the LED indicators.
Ready
Active
MSG In
MSG Out
Wink
Srvc
The following table shows the LED descriptions.
LED Descriptions
LEDs Function
Active
Ready
MSG In
Bus communication is present.
Module has passed internal diagnostics, and is configured.
MSG Out
Flashes every 10 ms when an update message for a bound network variable is received by the NOL module from the LonWorks network.
Flashes every 10 ms when an update message for a bound network variable is transmitted by the NOL module to the LonWorks network.
Wink
Srvc
Flashes briefly when the NOL module receives a wink message from the
LonWorks network. Also used to display internal error codes defined in the
Wink LED Error Codes table.
Indicates status of LonWorks network service.
840 USE 100 00 11/2004
209
Quantum Field Bus Modules
The following table shows the LED Indicator Status.
LED Indicator Status
LED Color Condition of NOL Module
Powered Up
Not Configured
Not Programmed
Powered Up
Configured
Not Programmed
Normal Operation
Configured
Programmed
Active Green Off Off On
Error
Condition
Ready
MSG In
MSG Out
Wink
Srvc
Green
Green
Green
Green
Yellow
Blink
Off
Off
Off
Off
On
Off
Off
Off
Blink
On
Blink
Blink
Blink on command
Off
Off
1
Off
2
N/A
N/A
Blink
3
N/A z z z
If not lit, either the LON module requires configuration and mapping or is not communicating with the CPU by way of the DX Loadable.
If a LON module is inserted into the backplane and the Ready LED does not illuminate, the Wink LED should be observed for an error code.
See the following Wink LED error codes.
Wink LED Error
Codes
The Wink LED is used to display error conditions. The following table shows the number of times the LED blinks for each type of error.
1
2
3
4
LED Error Codes
Number of Blinks Error Condition
Module is in the bootloader
Error in writing to flash memory
Error in initializing the Lon Works network
Error in the module configuration
Front Panel Push
Buttons
Two push buttons are located on the front of the NOL module. The service pin push button initiates the LonWorks network installation. When depressed, it causes the
Service LED to illuminate, and forces the Neuron Chip in the module to output its unique 48-bit ID and Program ID.
The reset push button performs a hardware reset of the module, and must be done each time new firmware has been downloaded.
1RWH
The Reset push-button is recessed and requires a paper clip or similar tool to activate.
210
840 USE 100 00 11/2004
Front Panel
Connectors
RS-232
Configuration
Port
Quantum Field Bus Modules
There are three connectors located on the front of the NOL module. These are the
RS-232 configuration port; the primary LonWorks communication port; and the auxiliary LonWorks configuration port.
z z z z
This 9 pin, D-shell, female, RS-232 compatible serial port’s attributes are:
Configured at a fixed rate of 9600 baud, 8 data bits, 1 stop bit, and no parity.
Used to download configuration and new firmware to the module.
Supports XMODEM protocol with an ASCII terminal based command processor.
Can be directly connected to a PC serial communications port.
The following figure shows the 9-pin configuration port.
3
4
1
2
5
6
7
8
9
The following table shows the key to the RS-232C port.
3
5
Pin
2
Signal
RXD
TXD
GND
Black circle = Pin occupied. White circle = N/C
Function
Received Data
Transmitted Data
Signal Ground
Modbus cables 990NAA26320 and 990NAA26350 are suitable for connection between the PC serial port and NOL module RS-232 port.
Primary
LonWorks
Communication
Port
This is the primary interface for wiring into a LonWorks network. The connector is a two-position 5.08 mm screw terminal.
840 USE 100 00 11/2004
211
Quantum Field Bus Modules
Auxiliary
LonWorks
Communication
Port
This is the auxiliary interface for wiring into a LonWorks network. The connector is an eight position RJ-45 (phone jack) socket. The figure below shows the Pin 1 connector.
Pin 1
NOL Module
Media Types
1RWH
The Auxiliary LonWorks Communications Port is not intended to be connected to any public telecommunications network.
Both the Primary and Secondary ports provide standard interfaces to LonWorks networks and are wired in parallel for flexibility. The connections are not polarity sensitive.
z z z
The NOL module supports three twisted pair media types with different network topologies or data transfer speeds.
140NOL91100
140NOL91110
140NOL91120
The following table shows the transceiver types supported by each module are as follows:
NOL Model Number Transceiver Type
140NOL91100*
140NOL91110
140NOL91120*
TP/FTT-10
TP/XF-78
TP/XF-1250
Configuration Data Transfer
Rate
Free topology, twisted pair 78,000 BPS
Linear topology, twisted pair, transformer isolated
78,000 BPS
Linear topology, twisted pair, transformer isolated
1.25 MBPS
*Not actively sold after 10/00.
:$51,1*
,QFRPSDWLELOLW\
NOL modules are not compatible in Quantum Distributed I/O (DIO) racks.
)DLOXUHWRIROORZWKLVSUHFDXWLRQFDQUHVXOWLQGHDWKVHULRXVLQMXU\RU
HTXLSPHQWGDPDJH
212
840 USE 100 00 11/2004
Distributed I/O (DIO) for the
Quantum Modules
9
At a Glance
Introduction
What’s in this
Chapter?
z z z z
This chapter provides information on the distributed I/O (DIO) modules. This information includes specifications, LED indicators and descriptions, rear panel switches, and wiring diagrams for the following modules:
140CRA21110
140CRA21210
140CRA21120
140CRA21220
This chapter contains the following topics:
Topic
140CRA21X10 Quantum Distributed I/O (DIO) Modules
140CRA21X20 Quantum Distributed I/O (DIO) Modules
Page
213
840 USE 100 00 11/2004
DIO
140CRA21X10 Quantum Distributed I/O (DIO) Modules
Overview
DIO Module
This section includes specifications and wiring diagrams for the Modbus Plus
Distributed I/O AC powered single (CRA21110) and dual (CRA21210) channel modules.
The following figure shows the parts of the distributed I/O (DIO) module.
LED Area
Modbus
Plus
X
Model Number
Module Description
Color Code
Customer Identification Label
(Fold label and place it inside door)
Removable Door
Part #043505673
0RGEXV
3OXV
Network
Node Field Wiring
Connector
Field Wiring
Connector Cover
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
5
6
7
1
2
3
4
Not used
Not used
Not used
Not used
AC L
AC N
214
840 USE 100 00 11/2004
Specifications
DIO
The following specifications are for the Modbus Plus CRA21110 and CRA21210 AC powered single and dual channel DIO modules.
Specifications
Input Requirements
Input Voltage
Input Frequency
Input Voltage Total Harmonic
Distortion
Input Current
Inrush Current
VA Rating
Input Power Interruption
85 ... 276 Vac
47 ... 63 Hz
Less than 10% of the fundamental rms value
0.4 A @ 115 Vac. 0.2 A @ 230 Vac
10 A @ 115 Vac. 20 A @ 230 Vac
50 VA
1/2 cycle at full load and minimum rated line voltage / frequency. No less than 1 second between interruptions.
1.5 A (Part #043502515 or equivalent)
Standalone or not powered (see p. 691 ).
Fusing (external)
Operating Mode
Output to Bus
Voltage
Current
Minimum Load
Protection
Communication
Modbus Plus
General
Specifications
5.1 Vdc
3 A
0 A
Over Current, Over Voltage
1 port (single cable); 2 ports (dual cable)
Diagnostics
Field Wiring Connector
Internal Power Dissipation
I/O Type:
Modules/Drop:
Words:
Quantum
Depends on bus current loading and word count
30 In / 32 Out. (Two additional input words are reserved for drop status.)
Power Up Runtime
RAM Data/Address
Executive Checksum
7 point terminal strip (Part # 043506326)
2.0 V + 3.0 V x I
BUS
= Watts (where IBUS is in Amperes)
840 USE 100 00 11/2004
215
DIO
Wiring Diagram The following figure shows the wiring diagram for the 140CRA21110 and 21210 wiring diagram.
NOT USED
NOT USED
NOT USED
NOT USED
AC L
AC N
1RWH See S for power and grounding wiring guidelines and operational information.
216
840 USE 100 00 11/2004
DIO
LED Indicators and Descriptons
The following figure shows the LED panel.
Ready Fault
Pwr ok
Modbus +
Error A
Error B
The following table shows the DIO LED indicators and descriptions.
LED Descriptions
LEDS Color Indication when On
Ready
Fault
Green The module has passed power-up diagnostics.
Red A communications error exists between the DIO module and one or more
I/O modules, or an output module is not being written to, over the Modbus
Plus network.
Pwr ok Green Bus power is present.
Modbus + Green Communications are active on the Modbus Plus port.
Error A
Error B
Red
Red
Communication error on the Modbus Plus Channel A (dual cable only).
Communication error on the Modbus Plus Channel B (dual cable only).
840 USE 100 00 11/2004
217
DIO
Rear Panel
Switches
Two rotary switches (refer to the following illustration and table) are located on the rear panel of the CPU. They are used for setting Modbus Plus node addresses for the unit.
SW1 (the top switch) sets the upper digit (tens) of the address; SW2 (the bottom switch) sets the lower digit (ones) of the address. The illustration below shows the correct setting for an example address of 11.
SW1 (Top)
8
9
0
1
2
4
6
5
8
9
0
1
2
6
5
4
SW2 (Bottom)
The following table shows the node addresses of the SW1 and SW2 switches.
SW1 and SW2 Switches
Node Address
1 ... 9
10 ... 19
20 ... 29
30 ... 39
40 ... 49
50 ... 59
60 ... 64
5
6
3
4
1
2
SW1
0
SW2
1 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 4
1RWH If "0" or an address greater than 32 is selected, the RIO module displays a flashing Error A and Error B LED to indicate an error condition. Only addresses 1-
32 are valid.
218
840 USE 100 00 11/2004
DIO
140CRA21X20 Quantum Distributed I/O (DIO) Modules
Overview
DIO Module
This section includes specifications and wiring diagrams for the Modbus Plus
Distributed I/O DC powered single (CRA21120) and dual (21220) channel modules.
The following figure shows the parts of the Distributed I/O (DIO) module.
LED Area
Modbus
Plus
X
Model Number
Module Description
Color Code
Customer Identification Label
(Fold label and place it inside door)
Removable Door
Part #043504640
0RGEXV
3OXV
Network
Node Field Wiring
Connector
Field Wiring
Connector Cover
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
5
6
7
1
2
3
4
Not used
Not used
Not used
Not used
ACL
ACN
840 USE 100 00 11/2004
219
DIO
Specifications The following specifications are for the Modbus Plus CRA21120 and CRA21220 DC powered single and dual channel DIO modules.
Specifications
Input Requirements
Input Voltage
Input Current
Inrush Current
Input Power Interruption
Fusing (external)
Operating Mode
Output to Bus
Voltage
Current
Minimum Load
Protection
Communication
Modbus Plus
General
Specifications
20 ... 30 Vdc
1.6 A
30 A
1.0 ms max
2.5 A (Part #043503948 or equivalent)
Standalone or not powered (see p. 691 ).
5.1 Vdc
3 A
0 A
Over Current, Over Voltage
1 port (single cable). 2 ports (dual cable)
Diagnostics
Field Wiring Connector
Internal Power Dissipation
I/O Type
Words
Quantum
Modules/Drop Depends on bus current loading and word count
30 In / 32 Out. (Two additional input words are reserved for drop status)
Power Up Runtime
RAM Data/Address
Executive Checksum
7 point terminal strip (Part #043503328)
2.0 V + 3.0 V x I
BUS
= Watts (where I
BUS
is in Amperes)
220
840 USE 100 00 11/2004
Wiring Diagram
DIO
The following figure shows the wiring diagram for the 140CRA21110 and 21210 wiring diagram.
NOT USED
NOT USED
–24VDC (Common)
+24VDC
AC L
AC N
1RWH See S for power and grounding wiring guidelines and operational information.
840 USE 100 00 11/2004
221
DIO
LED Indicators and Descriptions
The following figure shows the LED panel.
Ready Fault
Pwr ok
Modbus +
Error A
Error B
The following table shows the DIO LED indicators and descriptions.
LED Descriptions
LEDS Color Indication when On
Ready
Fault
Green The module has passed power-up diagnostics.
Red A communications error exists between the DIO module and one or more
I/O modules or an output module is not being written to over the Modbus
Plus network.
Pwr ok Green Bus power is present.
Modbus + Green Communications are active on the Modbus Plus port.
Error A
Error B
Red
Red
Communication error on the Modbus Plus Channel A (dual cable only).
Communication error on the Modbus Plus Channel B (dual cable only).
222
840 USE 100 00 11/2004
Rear Panel
Switches
DIO
Two rotary switches (refer to the illustration and table that follow) are located on the rear panel of the CPU. They are used for setting Modbus Plus node addresses for the unit.
SW1 (the top switch) sets the upper digit (tens) of the address; SW2 (the bottom switch) sets the lower digit (ones) of the address. The illustration shows the correct setting for an example address of 11.
SW1 (Top)
8
9
0
1
2
6
5
4
8
9
0
1
2
6
5
4
SW2 (Bottom)
The following table shows the node addresses of the SW1 and SW2 switches.
SW1 and SW2 Switches
Node Address
1 ... 9
10 ... 19
20 ... 29
30 ... 39
40 ... 49
50 ... 59
60 ... 64
3
4
5
6
SW1
0
1
2
SW2
1 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 4
1RWH If "0" or an address greater than 32 is selected, the RIO module displays a flashing Error A and Error B LED to indicate an error condition. Only addresses 1-
32 are valid.
840 USE 100 00 11/2004
223
DIO
224
840 USE 100 00 11/2004
Quantum Remote I/O
Communication Modules
10
At a Glance
Introduction
What’s in this
Chapter?
Quantum networking modules provide open, standards-based networking and fieldbus connectivity using Modbus, Modbus Plus, Ethernet, InterBus, SY/MAX and
LonWorks networks. Specifications for these modules are included below.
This chapter contains the following topics:
Topic
140CRP93X00 Remote I/O (RIO) Head Single and Dual Channel Module
140CRA93X00 Quantum RIO Adapter Drop Single and Dual Channel Module
Page
225
840 USE 100 00 11/2004
Networking
140CRP93X00 Remote I/O (RIO) Head Single and Dual Channel Module
Overview The Remote I/O Head Single and Dual Channel modules are installed in the same backplane as the system controlling CPU modules. The RIO head is used to transfer data bi-directionally between the CPU and RIO drop modules installed in separate backplanes. A coaxial cable network is used to interconnect the RIO head module and one or more RIO drop modules.
RIO Head Module The following figure shows the Remote I/O (RIO) module’s parts. The specific module illustrated is the 140CRP93200.
LED Area
Version Label
Model Number
Module Description
Color Code
Removable Door
Part #043513804
Customer Identification Label
(Fold label and place it inside door)
Part #043504680
Remote I/O
DROP N0.
RIO Coax
Connector
X
226
840 USE 100 00 11/2004
Specifications
Networking
The following table shows the specifications for the Remote I/O Head Single and
Dual Channel modules.
Specifications
Drop Type
Drops
Words/Drop
ASCII
Quantum, 200 Series, 500 Series, 800 Series, or SY/MAX
(any mix)
31 max
64 In / 64 Out
Coax Termination
Coax Shield
Data Transfer Rate
Dynamic Range
2 ports/drop, 32 ports (16 drops) max
Requires the use of AS-P892-000, AS-J892-101/102, or
AS-J290-0X0 at the RIO drops.
Internal 75
Ω
Tied to chassis ground
1.544 mb
35 dB
500 Vdc coaxial cable center conductor to ground Isolation
External Connections
One Channel (CRP93100) One "F" type female connector with a right angle adapter
Two Channels (CRP93200) Two "F" type female connectors with a right angle adapter
General
Diagnostics Power Up
Dual Port Memory Check
LAN Controller Check
1 Maximum Number of CRPs
Supported by the Controller
Bus Current Required
(Typical)
Single Channel: 600 mA
Dual Channel: 750 mA
Power Dissipation (Typical) Single Channel: 3 W
Dual Channel: 3.8 W
Power Up and Runtime
Executive Checksum
RAM Address/Data
840 USE 100 00 11/2004
227
Networking
&$87,21
&RQQHFWLYLW\&RPSOLDQFH
To maintain CE compliance with the European Directive on EMC (89/336/EEC), the RIO head module must be connected using quad shielded cable (see the
Remote I/O Cable System Planning and Installation Guide, 890USE10000, V2.0).
)DLOXUHWRIROORZWKLVSUHFDXWLRQFDQUHVXOWLQLQMXU\RUHTXLSPHQWGDPDJH
LED Indicators and Descriptions
The following figure shows the LED indicators for the RIO Head module.
Ready
Com Act
Error A
Error B
The following table shows the LED descriptions for the RIO Head module.
LED Descriptions
LEDS Color
Ready
Com Act
Error A
Green
Green
Red
Error B Red
Indication When On
The module has passed powerup diagnostics.
The module is communicating on the RIO network.
There is a loss of communication on Channel A with one or more of the drops.
There is a loss of communication on Channel B with one or more of the drops (dual cable only).
228
840 USE 100 00 11/2004
Networking
LED Error Codes The Blinking Com Act LED error codes for the RIO Head module table show the number of times the Com Act LED on the RIO Head module blinks for each type of error and the crash codes for each (all codes are in hex).
5
6
7
3
4
LED Error Codes
Number of Blinks
Slow (steady)
2
8
6729
6616
6617
6619
681A
681C
6847
6849
684A
684B
684C
6503
6402
6300
6301
8001
8002
8003
682A
682B
682C
6840
6841
6842
Code
0000
6820
6822
6823
6843
6844
6845
6846
Error
Requested Kernel Mode hcb frame pattern error head cntrl blk diag error mod personality diag error fatal start I/O error bad read I/O pers request bad execute diag request
ASCII input xfer state
ASCII output xfer state
I/O input comm. state
I/O output comm. state
ASCII abort comm. state
ASCII pause comm. state
ASCII input comm. state
ASCII output comm. state building 10 byte packet building 12 byte packet building 16 byte packet illegal I/O drop number
984 interface bus ack stuck high coax cable initialization error coax cable dma xfer error coax cable dumped data error coax cable DRQ line hung coax cable DRQ hung ram address test error ram data test error prom checksum error (Exec not loaded) prom checksum error
Kernal prom checksum error
Flash prog / erase error
Unexpected executive return
840 USE 100 00 11/2004
229
Networking
140CRA93X00 Quantum RIO Adapter Drop Single and Dual Channel Module
Overview The Remote I/O Drop Single and Dual Channel modules are used to transfer data bi-directionally over a coaxial cable network between I/O modules installed in the same (RIO drop) backplane and the RIO head installed in the CPU backplane.
RIO Drop Module The following figure shows the components of the Remote I/O (RIO) drop module.
The specific module shown is the CRA93200.
LED Area
Version Label
Model Number
Module Description
Color Code
Customer Identification Label
(Fold label and place it inside door)
Part #043504680
Removable Door (Part #043513804)
Remote I/O
DROP N0.
RIO Coax
Connector
X
230
840 USE 100 00 11/2004
Specifications
Networking
The following table shows the specifications for the Remote I/O Drop Single and
Dual Channel modules.
Specifications
I/O Type
Words/Drop
Coax Termination
Coax Shield
Data Transfer Rate
Dynamic Range
Isolation
External Connections
One Channel (CRA93100)
Two Channels (CRA93200)
Quantum
64 In / 64 Out
Internal 75
Ω
Capacitor to ground
1.544 mb
35 dB
500 Vdc coaxial cable center conductor to ground
One "F" type female connector with a right angle adapter
Two "F" type female connectors with a right angle adapter
General
Holdup Time
Diagnostics
Bus Current Required (Typical)
Power Dissipation (Typical)
Software configurable
Note: In the event of a communication loss with the remote processor, this is the time that output modules will retain their last operating state. Input module data will be held in the system controlling CPU. After this time, output modules will assume their predefined time-out states, and inputs will be zeroed by the CPU.
Power Up Power Up and Runtime
Dual Port Memory Check Executive Checksum
LAN Controller Check
Single Channel: 600 mA
RAM Address/Data
Dual Channel: 750 mA
Single Channel: 3 W
Dual Channel: 3.8 W
840 USE 100 00 11/2004
231
Networking
&$87,21
&RQQHFWLRQ&RPSOLDQFH
To maintain CE compliance with the European Directive on EMC (89/336/EEC), the RIO Head module must be connected using quad shielded cable (see the
Remote I/O Cable System Planning and Installation Guide, 890USE10100, V2.0).
)DLOXUHWRIROORZWKLVSUHFDXWLRQFDQUHVXOWLQLQMXU\RUHTXLSPHQWGDPDJH
LED Indicators and Description
The following figure shows the LED indicators for the Drop module.
Ready Fault
Com Act
Error A
Error B
The following table shows the RIO Drop module LED descriptions.
LED Descriptions
LEDS Color
Ready
Com Act
Green
Green
Fault
Error A
Error B
Red
Red
Red
Indication when On
The module has passed power-up diagnostics.
The module is communicating on the RIO network.
Unable to communicate with one or more I/O modules.
Communication error on Channel A.
Communication error on Channel B (dual cable only).
232
840 USE 100 00 11/2004
Networking
LED Error Codes Blinking Com Act LED error codes for the RIO Drop module table show the number of times the Com Act LED on the RIO Drop module blinks for each type of error and the crash codes for each (all codes are in hex).
5
6
7
3
4
LED Error Codes
Number of Blinks
6607H
6608H
6609H
660AH
660BH
660CH
660DH
6501H
6401H
6301H
Code
6701H
6601H
6602H
6603H
6604H
6605H
6606H
Description of Error asic test failure power down interrupt
82588 lan chip test error receive abort timeout transmission loop timeout transmission dma error cable a initialization error cable a dma xfer error cable b dma xfer error cable a dumped data error cable a DRQ line hung cable b DRQ line hung cable a or b DRQ hung power-up lan controller error ram address test error ram data test error prom checksum error
840 USE 100 00 11/2004
233
Networking
Rear Panel
Switches
Two rotary switches are located on the rear panel of the RIO Drop Modules and are used for setting RIO drop addresses (refer to the following illustration and table).
SW1 (top switch) sets the upper digit (tens); SW2 (bottom switch) sets the lower digit
(ones). The illustration below shows the correct setting for an example address of
11.
SW1 (Tens)
8
9
0
1
2
4
6
5
8
9
0
1
2
4
6
5
SW2 (Ones)
The following table shows the node addresses of the SW1 and SW2 switches.
SW1 and SW2 Address Settings
Node Address
1 ... 9
10 ... 19
20 ... 29
30 ... 39
40 ... 49
50 ... 59
60 ... 64
SW1
0
1
2
3
4
5
6
SW2
1 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 4
1RWH If "0" or an address greater than 32 is selected, the module displays a flashing ERROR A and ERROR B LED indicating an error condition. Only addresses 2 - 32 are valid.
234
840 USE 100 00 11/2004
Quantum Modbus Plus
Network Option Modules
11
140NOM21X00 Quantum Modbus Plus Network Option Modules
Overview
Modbus Plus
Module
The following information describes the single and dual channel twisted-pair cable
NOM21X00 modules, which provide interface to Modbus Plus networks.
The following figure shows the components of the Modbus Plus 140NOM21X00 modules.
LED Area
120;
CONTROLLER
Model Number
Module Description
Color Code
Removable door
Customer Identification Label
(Fold label and place it inside door)
Part #043504417
Comm Parameter
Slide Switch
Modbus
Connector
Modbus Plus
Connector
Chan A
Modbus Plus
Connector
Chan B
Modbus
Comm 1
Modbus
Comm 2
Modbus
Plus
Network
Node
ASCII
RTU mem
X
235
840 USE 100 00 11/2004
Modbus Plus NOMs
Specifications The Modbus Plus Head Single and Dual Channel modules provide extended communication capabilities for the Quantum system within a Modbus Plus configuration. The following table shows the specifications show the Modbus Plus single and dual channel modules.
Specifications
Communication Ports
NOM21100
NOM21200
Both Modules
Diagnostics
1 Modbus Plus network (RS-485) port (9-pin connector)
2 Modbus Plus network (RS-485) ports (9-pin connectors) for dual connectivity on a single Modbus Plus network. These ports handle identical versions of all inbound and outbound transactions and keep track of the data paths used for these transactions.
1 Modbus (RS-232) serial port (9-pin connector)
A bridge mode capability in the module permits a panel device connected to this port to access nodes on the Modbus Plus network or to access the local PLC directly without having to go out onto the network.
Power Up
RAM
Runtime
RAM
RAM Address
Executive Checksum
Processor
4 W
RAM Address
Executive Checksum
Power Dissipation
(Typical)
Bus Current Required
NOM21100
NOM21200
780 mA
780 mA
236
840 USE 100 00 11/2004
Modbus Plus NOMs
LED Indicators and Descriptions
The following figure shows the Modbus Plus NOM LED indicators.
Ready
Run
Modbus
Modbus + Error A
Error B
The following table shows the Modbus Plus NOM LED Descriptions.
LED Descriptions
LEDs Color
Ready
Run
Green
Green
Modbus
Modbus+
Error A
Error B
Green
Green
Red
Red
Indication when On
The module has passed power-up diagnostics.
Indicates that the unit is in kernel mode–should always be OFF during normal operations.
Indicates communication is active on the single RS-232 serial port.
Indicates communication is active on the Modbus Plus port.
There is an error condition on Cable A of a dual cable Modbus Plus network (140NOM21200 only).
There is an error condition on Cable B of a dual cable Modbus Plus network (140NOM21200 only).
840 USE 100 00 11/2004
237
Modbus Plus NOMs
LED Error Codes The blinking Run LED error codes for the NOM module shows the number of times the Run LED on the NOM module blinks for each type of error and the crash codes for each (all codes are in hex).
LED Error Codes
Number of Blinks Code
Steady
2
3
014H
815
49H
4BH
4CH
4DH
4EH
52H
4
53H
56H
59H
5AH
5BH
616h
617h
618h
627H
628H
629H
62aH
62bH
62cH
62dH
619h
61AH
621H
622H
623H
624H
625H
626H
Error normal power down event ram sequence error illegal data command received by bypass code diagnostics test pattern invalid in the icb block diagnostics test pattern invalid in the page 0 icb address not the same as found in hcb bad code selected for mstrout_sel proc config table exec_id is different than the sys table exec_id got a pupinit hook for neither S985 nor S975 addr did not get bus ack form 984 interface within 400 ms unexpected modbus port state in send command to 680 proc system table missing bad DPM critical byte write bad or unexpected interrupt loopback error on modbus port 1 parity error set port greater than 21 controller ram size is less than 8k modbus cmd-buffer overflow modbus cmd-length is zero modbus abort command error bad modbus state trn-int bad modbus state rcv-int bad comm state trn_asc transmit underflow error bad comm state trn_tru bad comm state rcv_asc bad comm state rcv_rtu bad transmit comm state bad receive comm state bad modbus state tmr0_evt
238
840 USE 100 00 11/2004
840 USE 100 00 11/2004
Modbus Plus NOMs
5
6
7
LED Error Codes
Number of Blinks Code
62eH
631H
632H
633H
634H
635H
636H
637H
638H
639H
63AH
681h
68ah
68bh
691h
692h
6AIh
6A2h
6A3h
6A4h
682h
683h
684h
685h
686h
687h
688h
689h
6A5h
513h
412h
311h
Error bad uart interrupt
UPI timeout error bad UPI response opcode
UPI bus diagnostic error mbp bus interference error bad mbp response opcode timeout waiting for mbp mbp out of synchronization mbp invalid path peer did not respond with complement of the opcode peer unable to come out of transitions at power-up bad master state bad slave state unknown routing failure to send bad port number in set () proc bad port number in reset () proc bad port number in getport () proc bad port number in bitpos () proc bad port number in enable_transmit_interrupt () proc bad port number in enable_receive_interrupt () proc bad port number in disable_transmit_interrupt () proc bad port number in privilege flag is not reset in the session timeout proc bad port number in chkmst_hdw () proc unknown controller type in reset busy flag unknown function code in generate_poll_cmd () proc unknown function code in generate_logout_msg () proc slave link timeout on port other than port #9 illegal bypass command received by bypass code ram address test error ram data test error prom checksum error
239
Modbus Plus NOMs
Rear Panel
Switches
Two rotary switches are located on the rear panel of the modules. They are used together to set the Modbus Plus node and Modbus port address for the unit.
1RWH The highest address that may be set with these switches is 64.
Rotary SW1 (top switch) sets the upper digit (tens), and rotary SW2 (bottom switch) sets the lower digit (ones) of the Modbus Plus node address. The illustration below shows the setting for an example address of 11.
SW1 (Top)
8
9
0
1
2
4
6
5
8
9
0
1
2
4
6
5
SW2 (Bottom)
1RWH
If "0," or an address greater than 64 is selected, the Modbus + LED will be
"on" steady, to indicate the selection of an invalid address.
The following table shows the address settings for the SW1 and SW2 switches.
SW1 and SW2 Address Settings
Node Address SW1
1 ... 9
10 ... 19
0
1
20 ... 29
30 ... 39
40 ... 49
50 ... 59
60 ... 64
4
5
2
3
6
SW2
1 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 9
1 ... 4
240
840 USE 100 00 11/2004
Front Panel
Switches
Modbus Plus NOMs
Two, three-position slide switches are located on the front of the unit. The switch on the left is not used. The three-position slide switch on the right is used to select the comm parameter settings for the Modbus (RS-232) port provided with the Modbus
Plus option module. Three options are available, as shown in the following illustration.
ASCII
Switch not used
RTU mem
1RWH
The NOM hardware defaults to bridge mode when the front panel switch is set to RTU or ASCII mode. When networking controllers, a panel device connected to the NOM Modbus port can communicate with the controller to which it is conected, as well as log into any nodes on the Modbus Plus network.
Setting the slide switch to the top position assigns ASCII functionality to the port. The following comm parameters are set and cannot be changed.
ASCII Comm Port Parameters
Baud
Parity
Data Bits
Stop Bits
Device Address
7
1
2,400
Even
Rear panel rotary switch setting
Setting the slide switch to the middle position assigns remote terminal unit (RTU) functionality to the port; the following comm parameters are set and cannot be changed.
RTU Comm Port Parameters
Baud
Parity
Data Bits
Stop Bits
Device Address
8
1
9,600
Even
Rear panel rotary switch setting
840 USE 100 00 11/2004
241
Modbus Plus NOMs
Setting the slide switch to the bottom position gives you the ability to assign comm parameters to the port in software; the following parameters are valid.
Valid Comm Port Parameters
Baud
Data Bits
Stop Bits
Parity
Device Address
19,200
9,600
7,200
4,800
3,600
2,400
2,000
1,800
7 / 8
1 / 2
Enable/Disable Odd/Even
Rear panel rotary switch setting
1,200
600
300
150
134.5
110
75
50
Modbus
Connector
Pinouts
The NOM modules are equipped with a nine-pin RS-232C connector that supports
Modicon’s proprietary Modbus communication protocol. The following figure shows the Modbus port pinout connections for 9-pin (left) and 25-pin (right) connections.
IBM-AT
9-Pin Female
CD 1
RX
TX
2
3
DTR 4
GROUND 5
DSR
RTS
CTS 8
6
7
Quantum
9-Pin Male
1 SHIELD
2
3
RX
TX
4 DTR
5 GROUND
6 DSR
7 RTS
8 CTS
9 NC
IBM-XT
25-Pin Female
SHIELD 1
TX
RX
2
3
RTS
CTS
DSR 6
GROUND 7
NC
DTR
4
5
8
20
6
7
8
9
4
5
2
3
Quantum
9-Pin Male
1 SHIELD
DSR
RTS
CTS
NC
RX
TX
DTR
GROUND
242
840 USE 100 00 11/2004
Modbus Plus NOMs
Modbus Ports
Pinout
Connections for
Portable
Computers
The following figure shows the Modbus port pinout connections for nine-pin portable
(laptop) computers.
IBM-AT
9-Pin Female
Quantum
9-Pin Male
CD
RX
TX
SHIELD
RX
TX
DTR
GRND
DSR
RTS
CTS
NC
DTR
GRND
DSR
RTS
CTS
NC
The following is the abbreviation key for the above figures.
TX: Transmitted Data
RX: Received Data
RTS: Request to Send
DSR: Data Set Ready
DTR: Data Terminal Ready
CTS: Clear to Send
NC: No Connection
CD: Carrier Detect
840 USE 100 00 11/2004
243
Modbus Plus NOMs
244
840 USE 100 00 11/2004
Quantum Modbus Plus
Networking on Fiber Module
12
140NOM25200 Quantum Networking Modbus Plus on Fiber Module
Overview
Related
Documentation
The following information pertains to the Modbus Plus on Fiber module,
140NOM25200. The Modbus Plus on Fiber module provides connectivity to Modbus
Plus nodes by fiber cable.
There are many benefits that result from the use of fiber optics. Some of these include: z Longer distances between nodes (up to 3 km), thereby, increasing the total length of the network.
z Fiber optic medium is not susceptible to the effects of electromagnetic interference, RF interference, and lightning.
z Intrinsically safe links that are required in many hazardous industrial environments.
z Total electrical isolation between terminal points on the link.
For more detailed information on fiber optic network repeaters, see the Fiber
Repeater User Guide (GM-FIBR-OPT).
245
840 USE 100 00 11/2004
Modbus Plus NOM
Modbus Plus on
Fiber Module
The following figure shows the parts of the Modbus Plus 140NOM25200 module.
LED Area
Modbus Connector
Comm Parameter
Slide Switch
Port 2 TX and RX
Connectors
Port 1 TX and RX
Connectors
TX1
Fiber
Port 1
RX1
X
TX2
Fiber
Port 2
RX2
0RGEXV
3RUW
ASCII
RTU mem
120
CONTROLLER
Model Number
Module Description
Color Code
Removable Door
Customer Identification Label
(Fold label and place it inside door)
Part #043504417)
0RGEXV
3OXV
TX2
Fiber
Port 2
RX2
ASCII
RTU mem
RX1
Fiber
Port 1
TX1
246
840 USE 100 00 11/2004
Modbus Plus NOM
LED Indicators and Descriptions
The following figure shows the Modbus Plus on Fiber LED indicators.
Ready
Run
Modbus
Modbus+
Fport 1
Fport 2
FRNGoff
The following table shows the Modbus Plus on Fiber LED descriptions.
LED Descriptions
LEDs Color
Ready
Run
Green
Green
Modbus
Modbus+
Fport1
Fport2
FRNGoff
Green
Green
Green
Green
Red
Indication when On
The module has passed powerup diagnostics.
Indicates that the unit is in kernel mode – should always be OFF during normal operations. Note : The table for the NOM 21X 00 shows the number of times the RUN LED on the Modbus Plus on
Fiber Module blinks for each type of error and the crash codes for each (all codes are in hex).
Indicates communication is active on the single RS-232 serial port.
Indicates communication is active on the Modbus Plus port.
Indicates an optical signal has been received on fiber optic Port 1.
Indicates an optical signal has been received on fiber optic Port 2.
Indicates the first break in a self healing ring.
Specifications
840 USE 100 00 11/2004
The following table shows the specifications for the NOM25200 module.
Specifications
General Communication Ports
Optical Ports
Modbus Port
Transmission/Data Rate
Optical Interface
Pulse Width Distortions and Jitter
2 (consisting of an optical receiver and transmitter)
1 RJ45 (phone jack-type) connector
1 Mbit/second for Modbus Plus with Bi-Phase S encoded data
ST-Type connectors
5 ns or better
247
Modbus Plus NOM
Specifications
Wavelength
Power Loss Budget (includes 3 dB of system margins).
820 nm
50/125 micron fiber - 6.5 dB
62.5/125 micron fiber - 11 dB
100/140 micron fiber - 16.5 dB
Maximum Distance for point-topoint connection
2 km over 50 micron fiber
3 km over 62.5 micron fiber
3 km over 100 micron fiber
10 km over 62.5 micron fiber Maximum System Length in Self
Healing Ring Configuration
Optical Transmitter Specifications
Optical Power (Measured with 1 m test fiber)
-12.8 ... -19.8 dBm average power in 50/125 micron fiber cable
-9.0 ... -16 dBm average power in 62.5/125 micron fiber cable
-3,5 ... -10.5 dBm average power in 100/140 micron fiber cable
20 ns or better
-43 dBm
Rise/Fall Time
Silence (OFF leakage)
Optical Receiver Specifications
Receiver Sensitivity
Dynamic Range
Detected Silence
Miscellaneous Specifications
Diagnostics
-30 dBm average power
-20 dB
-36 dBm
Power Dissipation
Bus Current Required
External Power
Power Up
RAM
Runtime
RAM
RAM Address RAM Address
Executive Checksum Executive Checksum
Processor
4 W
750 mA max
Not required for this module
248
840 USE 100 00 11/2004
Front Panel
Switch
Modbus Plus NOM
A three-position slide switch is located on the front of the unit. This switch is used to select the comm parameter settings for the Modbus (RS-232) port. The three options that are available, as shown in the figure below, include setting the slide switch in the top position (ASCII), middle position (RTU), or bottom position (Valid mem comm port parameters).
ASCII
RTU mem
Setting the slide switch to the top position assigns ASCII functionality to the port. The following table shows the ASCII comm port parameters, which are set and cannot be changed.
ASCII Comm Port Parameters
Baud
Parity
Data Bits
Stop Bits
Device Address
7
1
2,400
Even
Rear panel rotary switch setting
840 USE 100 00 11/2004
249
Modbus Plus NOM
Setting the slide switch to the middle position assigns remote terminal unit (RTU) functionality to the port; the following RTU comm parameters are set and cannot be changed.
RTU Comm Port Parameters
Baud
Parity
Data Bits
Stop Bits
Device Address
8
1
9,600
Even
Rear panel rotary switch setting
Setting the slide switch to the bottom position gives you the ability to assign comm parameters to the port in software. The following parameters are valid.
Valid Mem Comm Port Parameters
Baud
Data Bits
Stop Bits
Parity
Device Address
19,200
9,600
7,200
4,800
3,600
2,400
2,000
1,800
7 / 8
1 / 2
Enable/Disable Odd/Even
Rear panel rotary switch setting
1,200
600
300
150
134.5
110
75
50
250
840 USE 100 00 11/2004
Rear Panel
Switches
Modbus Plus NOM
Two rotary switches are located on the rear panel of the modules. They are used together to set the Modbus Plus node and Modbus port address for the unit.
1RWH The highest address that may be set with these switches is 64.
Rotary SW1 (top switch) sets the upper digit (tens), and rotary SW2 (bottom switch) sets the lower digit (ones) of the Modbus Plus node address. The following illustration shows the setting for an example address of 11.
SW1 (Tens)
8
9
0
1
2
6
5
4
8
9
0
1
2
6
5
4
SW2 (Ones)
The following figure shows the node address settings for the SW1 and SW2 switches.
SW1 and SW2 Address Settings
Node Address SW1
1 ... 9
10 ... 19
0
1
20 ... 29
30 ... 39
40 ... 49
50 ... 59
60 ... 64
4
5
2
3
6
SW2
1 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 9
0 ... 9
1 ... 4
1RWH If "0" or an address greater than 64 is selected, the Modbus + LED will be
"on" steady, to indicate the selection of an invalid address.
840 USE 100 00 11/2004
251
Modbus Plus NOM
Modbus
Connector
The NOM25200 module is equipped with an RS-232 port (see below) located on the front of the module. This port uses an eight-position RJ45 (phone jack-type) connector. The following figure shows the NOM25200 Pin 1 connector.
Pin 1
1RWH A D-shell adapter is available from Modicon for NOM 252 00-to-computer connections: a (110 XCA 20 300) 9-pin adapter for PC-AT type computers (see the illustration pinout table below).
The following figures show the 9-pin adapter front view (left) and side view (right).
252
Pin 1
Pin 9
110XCA20300
Front View
50.8mm
(2 in)
Side View
The following figure shows the 9-pin RJ45 connector schematic.
Connectors Pinouts
RJ45
Connector
1
TXD 3
RXD 4
DSR 2
GND 5
CTS 7
RTS 6
Chassis 8
Ground
9-pin D-shell
1 DCD
2 RXD
3 TXD
4 DTR
5 GDN
6 DRS
7 RTS
8 CTS
9 RI
Case of the
Connector
840 USE 100 00 11/2004
RJ45 Cable
Types
Modbus Plus NOM
This following figure shows the RJ45 connector, Modicon Part #110XCA2820X cable. The table provides part numbers and cable lengths.
RJ45
Connector
RJ45
Connector
Modicon Part # 110 XCA 282 0X
Cable Part Numbers
110XCA28201
110XCA28202
110XCA28203
Cable Lengths
3 ft. (0.91 m)
10 ft. (3 m)
20 ft. (6 m)
840 USE 100 00 11/2004
253
Modbus Plus NOM
Fiber Optic Cable
Connections
The NOM25200 module is connected in the Quantum system by a fiber optic cable
(see the following figure). The cable has two strands. Each module transmits a signal in one direction. For this reason, each strand must be connected to the transmit port on one module and the receive port on the other.
One strand of the fiber optic cable is labelled every 10 inches with the manufacturer’s name and the cable specifications. This is the only way to distinguish the two strands.
Module A Module B
From Previous
NOM Receive
Transmit
Fiber
Port2
Receive
Transmit
Fiber
Port2
Receive
To Next
NOM Receive
From Previous
NOM Transmit
To Next
NOM Transmit
Receive
Fiber
Port1
Transmit
Receive
Fiber
Port1
Transmit
254
840 USE 100 00 11/2004
Modbus Plus NOM
Connecting the
Fiber Optic Cable
The following steps show how to connect the fiber optic cable.
Step
1
Action
Remove the protective plastic coverings from the cable ports and the tips of the cable. Snap one of the fiber cable clasps (shipped with the module) over the cable so that the wider end of the tool is closest to the cable end.
Protective Coverings Cable Fiber Cable Clasp
2 Turn the connection ring so that one of the arrows on the side of the ring lines up with the ridge inside.
Cable Connection Ring
CableTip
Ridge
Arrow
3 a. Slide the tool up to the connection ring. b. Gripping the cable with the plastic cable clasp, slide the cable end onto the lower cable port. The arrow and the ridge on the connection ring should lineup with the slot on the left of the cable port.
c. Use the clasp to push the cable over the tab on top of the port. d. Turn the cable to the right, so that the tab locks securely e. Remove the clasp. f. Repeat this process with the remaining strand of cable.
Cable Port
Tab
Cable Connection Ring
Fiber Cable Clasp
3 m Cable
(Part # 990XCA65609)
840 USE 100 00 11/2004
255
Modbus Plus NOM
Fiber Optic
Configurations
Point-to-Point
Configuration z z z z
The following represent four typical configurations that show the wide range of the network architecture:
Point-to-Point connection
Bus configuration
Tree and Star configurations
Self Healing Ring configuration
Point-to-point configuration (see the following figure) allows communication over the distance of up to 3 km through harsh industrial environments. The following figure shows the point-to-point configuration.
P/S
Node # 1
CPU I/O NOM NOM
Node # 2
CPU I/O P/S
Fiber Optic Cables
Bus
Configuration
This type of configuration is used when it is required to connect a number of fiber nodes and can be used to increase the distance of a standard Modbus Plus network by changing to a fiber medium. This kind of network allows the connection of up to
32 Quantum NOM252 nodes over the distance of 5 km.
The following illustrations show the NOM25200 module in a mixed fiber optic/twisted pairs bus configuration network and a pure fiber optic bus configuration network.
&$87,21
(TXLSPHQW)DLOXUH
The loss of a single node in this configuration disables the rest of the network. It is suggested that the Self Healing Ring configuration be used to avoid this problem.
)DLOXUHWRIROORZWKLVSUHFDXWLRQFDQUHVXOWLQLQMXU\RUHTXLSPHQWGDPDJH
256
840 USE 100 00 11/2004
Modbus Plus NOM
The following figure shows the mixed fiber optic/copper network.
1RGH
P/S CPU NOM I/O I/O P/S
1RGH
CPU NOM I/O I/O
/HJHQG
MB+ Cable
Fiber Optic
Cable
MB+ Tap with
Terminator
MB+ Tap
(Terminator not required)
490NRP254 Fiber Optic Repeater
1RGH
P/S CPU NOM I/O I/O
1RGH
P/S CPU NOM I/O I/O
To Node # n
1RGH
P/S CPU NOM I/O I/O
840 USE 100 00 11/2004
The following figure shows the pure fiber optic network.
Fiber Optic Cable
1RGH
P/S CPU NOM I/O I/O
1RGH
P/S CPU NOM I/O I/O
To Node # n
1RGH
P/S CPU NOM I/O I/O
To Node # n
Fiber Optic Cable
1RWH The distance between nodes on fiber is limited by the maximum allowable power loss from end-to-end (3 km over 62.5 mm fiber). Power loss includes the fiber optic cable attenuation, connector losses at the Fiber Optic Receiver and
Transmitter ports, and the system margin of 3 dB.
The end NOM25200 in this configuration will have the FRNGoff LED active and will display the Cable B Framing error in the MBPSTAT (in ladder logic).
257
Modbus Plus NOM
Tree
Configuration
The use of a tree configuration can provide flexibility in the layout of Modbus Plus and NOM 25200 networks. The following illustration shows an example of a tree configuration. Additional repeaters can be connected in order to extend communication between electrical links.
1RGH
P/S CPU NOM I/O
/HJHQG
MB+ Cable
Fiber Optic
Cable
MB+ Tap with
Terminator
MB+ Tap
490NRP254 Fiber Optic Repeaters
1RGH
P/S CPU NOM I/O
1RGH
P/S CPU NOM I/O
1RGH
P/S CPU NOM I/O
1RGH
P/S CPU NOM I/O
P/S CPU
1RGH
NOM I/O
1RGH
P/S CPU NOM I/O
1RGH
P/S CPU NOM I/O
1RGH
P/S CPU NOM I/O
258
840 USE 100 00 11/2004
Modbus Plus NOM
Self Healing Ring
Configuration
This configuration can be achieved by connecting the unused fiber optic ports of the first and last NOM25200 directly or through the fiber optic repeater, if a mixed fiber optic/twisted pairs network is used. This type of connection has all the advantages of the previously described configurations, along with built-in redundancy. A broken connection between any two Quantum modules in the ring will automatically reconfigure the network to the Bus Configuration and continue the communication.
1RGH
P/S CPU NOM I/O I/O
1RGH
P/S CPU NOM I/O I/O
/HJHQG
MB+ Cable
Fiber Optic
Cable
MB+ Tap with
Terminator
MB+ Tap
490NRP254 Fiber Optic Repeater
1RGH
P/S CPU NOM I/O I/O
1RGH
P/S CPU NOM I/O I/O
1RGH
P/S CPU NOM I/O I/O
840 USE 100 00 11/2004
259
Modbus Plus NOM
Hot Standby
Systems
The following figure shows the self healing ring configuration for hot standby systems example.
PC with SA85 Card
490NR25400 Fiber Optic Repeater for Modbus Plus
/HJHQG
MB+ Cable
Fiber Optic Cable
RIO Cable
MB+ Tap with
Terminator
MB+ Tap
Remote I/O
1RGH
3ULPDU\6\VWHP
P/S CPU CRP NOM CHS P/S
6WDQGE\6\VWHP
P/S CPU CRP NOM CHS P/S
1RGH
P/S CPU NOM I/O I/O
Coaxial RIO Link
To Other
RIO Drops
P/S CPU I/O I/O I/O
490NR95400 Fiber Optic Repeaters (for RIO)
7\SLFDO+RW6WDQGE\6\VWHPZLWK5HPRWH,25,2
Remote I/O Drop
260
840 USE 100 00 11/2004
Modbus Plus NOM
Network Status
Recommended
Materials for
Fiber Optic Links
Modicon does not manufacture fiber optic products such as cables, connectors, or special tools. However, we have experience with third party suppliers of materials and can give some guidelines on what will work with our products.
Connectors
The information about the condition of the network is presented in the form of
Network Status. This information indicates the loss of connection (the first break in the self healing ring) and is similar to the way existing 140NOM21200 reports the loss of redundant cable.
The break of the fiber cable will be detected by the module not receiving the signal from the side where the cable is broken and will be reported as a Cable B Framing error by MBPSTAT. This condition will also activate the FRNGoff LED on the front of the module.
The following table shows the connector types
Connector Type
ST Bayonet (Epoxy)
ST Bayonet (Hot Melt)
ST Bayonet (Epoxy)
Part Number
3M 6105
Operating Temperature
-40 ... +80° C
3M 6100 -40 ... +60° C
AMP 501380-5 Series -30 ... +70° C
ST Bayonet (Epoxy)
Light_Crimp ST Style
AMP 503415-1 Series
AMP 503453-1 Series
Mechanical Line Splice (one size fits all) 3M 2529 Fiberlok1 II
-20 ... +75° C
-20 ... + 60° C
-40 ... +80° C
1RWH All connectors must have a short boot for strain relief.
Termination Kits The following table shows the termination kits.
Kit Type
Bayonet ST (Epoxy)
Part Number Description
AMP 503746-1 For all epoxy type ST style
Light_Crimp XTC AMP 50330-2 For all Light_Crimp
Mechanical Line Splice 3M 2530 Fiber Splice Prep Kit, complete with cleaving tool
3M Hot Melt 3M 05-00185
3M 05-00187
110 V Termination Kit
220 V Termination Kit
Optical Star
Passive
Couplers
The AMP Model 95010-4 is a pig-tail option and must be used with an enclosure
(use AMP Model 502402-4, a 19 in rack-mount enclosure, 1.7 in high).
840 USE 100 00 11/2004
261
Modbus Plus NOM
Other Tools The following table shows other tools that may be needed for fiber optic links.
Product
3M (Photodyne) Optical Source
Driver
3M (Photodyne) Optical Light
Source
3M (Photodyne) Power Meter
3M Optical Light Source, 660 nm, visible
3M FC/ST Patch Cord
3M Bare Fiber Adapter, STcompatible
Part Number
9XT
1700-0850-T
17XTA-2041
7XE-0660-J
Description/Use
Hand-held optical source driver
(requires a light source)
850 nm Light Source, ST Connectors for 9XT
Hand-held Fiber Optic Power Meter
Use with 9XT to troubleshoot raw fiber, requires FC/ST patch cord
BANAV-FS-0001 Connects FC connector on 7XE to ST
8194 Permits use of above source and meter to test raw fiber (two required)
Cables It is recommended that you use 62.5/125
μ m cable (such as AMP 503016-1, AMP
502986-1, or equivalent) with a maximum attenuation of 3.5 dB/km in most of the configurations.
1RWH Modicon recommends using the 990XCA65609 cable.
When passive star couplers are used, 100/140 micron cable (such as
AMP503016-3, AMP502986-3, or equivalent) with a maximum attenuation of 5.0 dB/km is recommended because higher optical power can be pumped in 100 μ m cable and as a result, greater distance (up to 1 km) between units can be achieved.
1RWH All cables must have a maximum cable diameter of not more than 3 mm at the terminal side.
262
840 USE 100 00 11/2004
Connections
Modbus Plus NOM
The following information discusses connecting the NOM25200 on fiber cable, adding a new mode to the network, and repairing the break in the cable.
1RWH When a new network is assembled, it is recommended that you connect all cables before powering up the system. Connect fiber optic cables as described previously in this section.
Adding a New
Node to the
Network
If a new node is added to an existing network in order to extend the network (at the end of any configuration), then a new node may be connected first by fiber cable and then hot-swapped to the backplane to avoid errors to the existing network.
If a new mode is added to the middle of the network, the fiber optic cables need to be disconnected from one side of the existing NOM252 module and connected to port 1 or 2 of a new node. Additional fiber optic cable then needs to be connected to the second port of the new NOM252 and to the next NOM252 in the network, the new NOM252 then has to be hot-swapped to the backplane.
:$51,1*
+RW6ZDSSLQJ5HVWULFWLRQ
Modules may be hot swapped when the area is known to be non-hazardous. Do not hot swap modules in a Class 1, Division 2 environment.
)DLOXUHWRIROORZWKLVSUHFDXWLRQFDQUHVXOWLQGHDWKVHULRXVLQMXU\RU
HTXLSPHQWGDPDJH
840 USE 100 00 11/2004
263
Modbus Plus NOM
Repairing the
Break in the
Cable
Because the NOM25200 will stop transmitting in the direction from which it is not receiving the signal, the replacement of a broken fiber optic cable and the reconnection of it will not re-establish communication over that segment. The hot swap of only one NOM252 at the repaired connections is required to complete the connection.
1RWH The break of any fiber connectors or fiber optic cables is the equivalent to the break of the trunk cable in a Modbus Plus network on copper.
For the self healing ring configuration, the repair of the first break in the fiber optic network has to be scheduled to the time when one of the units on either side of the repaired break can be hot-swapped without creating the problem by disconnecting the node.
1RWH
Self healing configurations are not considered redundant networks. High system availability can be achieved with redundant networks.
Calculating
Number of
Modules in a
Fiber Network
Calculate the number of NOM25200 modules in a fiber network using the following method:
Step
1
2
3
4
Action
The total allowable pulse width distortions and jitter are limited to 20% of the bit period and is 200 nsec for the full fiber optic network.
The jitter contributed by the NOM252 is 5 nsec max.
Jitter contributed by fiber optic repeaters (if used) is 40 nsec.
The formula to determine the number (N) of chained repeaters is:
N =
200nsec – X L nsec
5nsec
– 40nsec
+ 1 where "L" is the total cable length (km), and "X" is the jitter (added by the fiber optic cable) in nsec/km:
X = 3 ns/km for 50/125 μ m
5 ns/km for 62.5/125
μ m
7.5 ns/km for 100/140 μ m
264
840 USE 100 00 11/2004
Quantum Ethernet Modules
13
At a Glance
Introduction
What’s in this
Chapter?
This chapter provides information on the NOE2X1 TCP/IP, NOE3X1 SY/MAX,
NOE5X100 MMS, and NOE771xx Ethernet modules.
This chapter contains the following topics:
Topic
140NOE2X100 Quantum Ethernet TCP/IP Module
140NOE3X100 Quantum Ethernet SY/MAX Modules
140NOE5X100 Quantum Ethernet MMS Modules
140NOE771xx Ethernet Modules
Page
840 USE 100 00 11/2004
265
Ethernet Modules
140NOE2X100 Quantum Ethernet TCP/IP Module
Overview The Quantum NOE2X1TCP/IP is described in this section. This includes specifications for the NOE21100 and NOE25100 modules.
Ethernet TCP/IP
Module
The following figure shows the Ethernet TCP/IP NOE2X100 module.
Model Number
Module Description
Color Code
LED Display Removable Door
Customer Identification Label
(Fold label and place it inside door
Global Address Label
Global
Address
Fiber Optic
10 base FL
Global
Address
Fiber
Optic
10 base
Transmit Cable
Connector
Receive Cable
Connector
X
Specifications
266
The Ethernet TCP/IP modules for twisted pair and fiber optic cabling provide an interface to Ethernet networks for the Quantum Automation Series system.
Specifications
Communication Ports
Ethernet ports transmit and receive Modbus commands encapsulated in TCP/IP protocol:
NOE 211 00 1, 10BASE-T Ethernet network (RJ-45) port. NOE 251 00 1, 10BASE-FL
Ethernet network (ST-style) port
Data Transfer Frequency
Power Dissipation
Bus Current Required
Compatibility
10 mb
5 W
1 A
Programming Software
Quantum Controllers
Modsoft V2.32 or Concept 2.0 at a minimum
All, V2.0 at a minimum
840 USE 100 00 11/2004
LED Indicators and Descriptions
The following figure shows the NOE2X100 LED indicators.
Ready
Run
Link
Active
Fault
Coll
Ethernet Modules
Kernel Appl
The following table describes the meaning of each NOE2X100 LED indicator.
LED Descriptions
LEDs Color Indication when On
Active Green Module is communicating with backplane.
Ready Green Module has passed internal diagnostic tests.
Run
Link
Green
Green
Flashes during normal operation.
Ethernet link to hub is ok.
Kernel Amber If steady, module is operating in kernel mode. If flashing, module is waiting for download.
Fault
Coll
Red
Red
An error has been detected, a download has failed or a reset is in process.
If steady, cable is not connected. If flashing, Ethernet collisions are occurring.
Appl Amber Entry exists in crash log.
840 USE 100 00 11/2004
267
Ethernet Modules
Installing the
NOE Module
Quantum Ethernet TCP/IP modules come fully configured. However, before installing your module, you should make sure the default configuration is appropriate for your network.
If the module will be communicating on an open network, consult your network administrator to obtain a unique IP network address. You must enter this address in the Modsoft Ethernet TCP/IP configuration extension screen before installing the module.
If the module will be communicating on a local network, make sure the default IP network address is not already in use on that network. To determine the default IP network address, locate the global address label on the front panel of the module.
Convert the rightmost eight digits from hexadecimal to decimal. The result should be a decimal number in the form, 84.xxx.xxx.xxx, where each group of xxx is a number from 0 to 255. This is the default IP network address.
Installation
Example:
Discovering the
Default IP
Network Address
The following example shows the steps for discovering the default IP network address.
Step
1
Action
Locate the global address label on the front panel of the module.
,(((*/2%$/$''5(66
2
0000540B72A8
Note the rightmost eight digits.
5 4 0 B 7 2 A 8
3
4
84.11.114.168
Convert them from hexadecimal to decimal. Each pair of hexadecimal numbers will result in a decimal number between 0 and 255. This is the default IP address.
If you use the default IP network address and if your network uses Ethernet II framing and if you do not need to specify the default gateway or a subnet mask, then you may install the module without changing the default configuration.
268
840 USE 100 00 11/2004
840 USE 100 00 11/2004
Ethernet Modules
&$87,21
6\VWHP(UURU
Do not connect this module to your network until you have ensured that its IP address will be unique on the network.
)DLOXUHWRIROORZWKLVSUHFDXWLRQFDQUHVXOWLQLQMXU\RUHTXLSPHQWGDPDJH
&$87,21
+DUGZDUH5HVWULFWLRQV
The cable for an Ethernet module must be routed through an Ethernet hub for the network to function properly. Do not connect the module directly to another device.
)DLOXUHWRIROORZWKLVSUHFDXWLRQFDQUHVXOWLQLQMXU\RUHTXLSPHQWGDPDJH
269
Ethernet Modules
140NOE3X100 Quantum Ethernet SY/MAX Modules
Overview
Related
Documentation
Ethernet SY/
MAX Module
This section includes information for the NOE31100 and 35100 SY/MAX Ethernet modules. The Quantum SY/MAX Ethernet modules for twisted pair and fiber optic cabling provide an interface for the Quantum Automation Series system to SY/MAX devices via Ethernet.
For more detailed information, see Quantum-SY/MAX-Ethernet Module User Guide
(840 USE 111 00).
The following figure shows the NOE3X100 SY/MAX Ethernet modules.
Model Number
Module Description
Color Code
LED Display
12(
CONTROLLER
Customer Identification Label
(Fold label and place it inside door)
Removable Door
Global Address Label
Transmit Cable
Connector
Receive Cable
Connector
Global
Address
Fiber Optic
10 base FL
Tx
Rx
X
Rx
Port 1
Tx
1RWH
The NOE31100 is equipped with one RJ-45 connector instead of the fiber optic connectors (as shown above on the NOE35100).
270
840 USE 100 00 11/2004
Specifications
Ethernet Modules
The following table shows the specifications for the SY/MAX Ethernet modules
NOE31100 and 35100.
Specifications
Communication Ports
NOE31100
NOE35100
Cable Type
10Base-2 or ThinWire Ethernet
1 10BASE-T Ethernet network (RJ-45) port
2 10BASE-FL Ethernet network (ST-style) ports
RG58a/u or RG58C/U coaxial (Belden 9907/82907 or equivalent)
2, 3, 4, or 6 twisted pairs with a solid copper core 10Base-T (twisted pair)
Wire Size
10Base-2 or ThinWire Ethernet
10Base-T (twisted pair)
Topology
10Base-2 or ThinWire Ethernet
10Base-T (twisted pair)
Connector
20 AWG
22, 24, 26 AWG
Bus
Star
10Base-2 or ThinWire Ethernet
10Base-T (twisted pair)
BNC (UG-274)
Modular RJ-45 (4 pins of 8 are used by 10Base-T)
Backplane Compatibility (Requires
Quantum CPU)
3, 4, 6, 10, and 16 position backplanes
Compatible SY/MAX 802.3 Devices and Software
Model 450
Model 650
SFI160
SFW390-VAX
Streamline Version 1.3
Bus Current Required 1 A
840 USE 100 00 11/2004
271
Ethernet Modules
LED Indicators and Descriptions
The following figure shows the NOE3X100 LED indicators.
Ready
Run
Link
Active
Fault
Collision
SY/MAX
Addressing
272
Kernel Appl
The following table describes the meaning of each NOE3X100 indicator.
LED Descriptions
LEDs
Active
Ready
Color
Green
Green
Run
Link
Kernel
Fault
Collision
Green
Green
Amber
Red
Red
Appl Amber
Indication when On
Module is communicating with backplane.
Module has passed internal diagnostic tests.
Flashes during normal operation.
Ethernet connection is made.
On during download.
An error condition has occurred.
If steady, an error condition exists. If flashing, packet collisions are occurring on the network during data transmission.
A fatal error has occurred.
Be sure that the module is assigned a unique SY/MAX drop number during configuration.
:$51,1*
3HUVRQDOLQMXU\RUHTXLSPHQWGDPDJH
Failure to assign a unique SY/MAX drop number during configuration can cause severe personal injury or equipment damage.
)DLOXUHWRIROORZWKLVSUHFDXWLRQFDQUHVXOWLQGHDWKVHULRXVLQMXU\RU
HTXLSPHQWGDPDJH
840 USE 100 00 11/2004
Ethernet Modules
140NOE5X100 Quantum Ethernet MMS Modules
Overview
Ethernet MMS
Module
The section includes information for the NOE5X100 MMS Ethernet modules,
NOE51100 and NOE55100. The Quantum MMS Ethernet modules for twisted pair and fiber optic cabling provide an interface for the Quantum Automation Series system to MMS devices via Ethernet.
The following figure shows the NOE5X100 MMS Ethernet modules.
Model Number
Module Description
Color Code
LED Display
Removable Door
Customer Identification Label
(Fold label and place it inside door)
Global Address Label
Transmit Cable
Connector
Receive Cable
Connector
Global
Address
Fiber
Optic
Tx
Rx
X
Rx
Port 1
Tx
1RWH The NOE51100 is equipped with one RJ45 connector instead of the fiber optic connectors (as shown above on the NOE55100).
840 USE 100 00 11/2004
273
Ethernet Modules
Specifications The following table shows the MMS Ethernet specifications.
Specifications
Communication Ports
NOE51100
NOE55100
Cable Type
10Base-2 or ThinWire Ethernet
10Base-T (twisted pair)
1 10BASE-T Ethernet network (RJ-45) port
2 10BASE-FL Ethernet network (ST-style) ports
2, 3, 4, or 6 twisted pairs with a solid copper core
RG58a/u or RG58C/U coaxial (Belden 9907/82907 or equivalent)
Wire Size
10Base-2 or ThinWire Ethernet
10Base-T (twisted pair)
Topology
10Base-2 or ThinWire Ethernet
10Base-T (twisted pair)
Connector
10Base-2 or ThinWire Ethernet
10Base-T (twisted pair)
Backplane Compatibility (Requires
Quantum CPU)
Data Transfer Frequency
Bus Current Required
20 AWG
22, 24, 26 AWG
Bus
Star
BNC (UG-274)
Modular RJ-45 (4 pins of 8 are used by 10Base-T)
3, 4, 6, 10, and 16 position backplanes
10 mb
1 A
274
840 USE 100 00 11/2004
LED Indicators and Descriptions
The following table shows the NOE5X100 LED indicators.
Ready
Run
Link
Active
Fault
Collision
Ethernet Modules
Kernel Appl
The following table describes the meaning of each NOE5X100 indicator.
LED Descriptions
LEDs Color
Active
Ready
Green
Green
Run
Link
Kernel
Fault
Green
Green
Amber
Red
Collision Red
Appl Amber
Indication when On
Module is communicating with backplane.
Module has passed internal diagnostic tests.
Flashes during normal operation.
Ethernet connection is made.
On during download.
An error condition has occurred.
If steady, an error condition exists. If flashing, packet collisions are occurring on the network during data transmission.
A fatal error has occurred.
840 USE 100 00 11/2004
275
Ethernet Modules
140NOE771xx Ethernet Modules
Overview The following provides information on the Quantum ethernet modules
140NOE77100, 140NOE77101, 140NOE77110, and 140NOE77111.
Related
Documentation
Refer to Quantum NOE 771 xx Ethernet Modules User Guide (840 USE 116 00) for more detailed information on the installation and use of Quantum ethernet modules.
Ethernet Module The following figure shows the NOE77100 Ethernet module. The other NOE771xx
Ethernet modules are the same in appearance except for the model number.
Model Number
Module Description
Color Code
LED Display
12(
(WKHUQHW
5HDG\
5XQ
$FWLYH
)DXOW
&ROO
/LQN
7[$FW
5[$FW
0%
0%)GXSOH[
.HUQHO$SSO
Removable Door
IP Address
Writable Area
Global Address Label
100 Base Fx
MT-RJ Cable Connector
10/100 Base-T
RJ-45 Cable Connector
%DVH
)[
7
276
840 USE 100 00 11/2004
Specifications
Ethernet Modules
The main specifications for the Quantum 140NOE771xx Ethernet Modules are described in the following table
Specifications
Communication Ports
Bus Current Required
Power Dissipation
Fuse
Programming Software
Type and version
One auto-sensing 10/100Base-T shielded twisted pair (RJ-45 connector) port and one 100Base-FX
(MT-RJ connector) port. Both ports transmit and receive Modbus commands encapsulated in TCP/IP protocol. Only one port can be used at a time.
750 mA
3.8 W
None
Concept, Ver. 2.2 or higher (NOE77100/10)
Concept, Ver 2.5 or higher (NOE77101/11)
Modsoft, Ver. 2.6 or higher (NOE77100/10)
ProWORX NxT, Ver 2.1 or higher (NOE77100/10)
ProWORX NxT, Ver 2.2 or higher (NOE77101/11)
Firmware
CPU Type and version
NOE Upgradeable
Operating Conditions
Temperature
Humidity
Altitude
Vibration
Quantum Executive, Ver. 2.0, or higher
Field Upgradeable via FTP or Programming Panel.
0 to +60° C
0 to 95% Rh non-condensing @ 60° C
15,000 ft (4500 m)
10-57 Hz @ 0.0075 mm d.a
57-150 Hz @ 1 g
Storage Conditions
Temperature
Humidity
Free Fall
Shock
-40 to +85°C
0 to 95% Rh non condensing @ 60°C
1 m unpackaged
3 shocks / axis, 15 g, 11 ms
840 USE 100 00 11/2004
277
Ethernet Modules
LED Indicators and Descriptions
The following figure shows the NOE771xx LED indicators.
Ready
Run
Link
Tx Act
Rx Act
10MB
Active
Fault
Coll
100MB
Kernel
Fduplex
Appl
The following table describes the meaning of each NOE771xx LED indicator.
LED Descriptions
LED Color Description
Active Green Indicates the backplane is configured.
Ready Green Indicates module is healthy.
Fault
Run
Red During a crash while going through a reset.
If Duplicate IP address is detected.
If no link is available.
While going through BOOTP sequence.
Green Flashes to indicate diagnostic code, as described in "Run LED Status"
(following table).
Coll.
Link
TxAct
RxAct
Red
Green
Green
Green
Flashes when Ethernet collisions occur.
On when Ethernet link is active.
Flashes to indicate Ethernet transmission.
Flashes to indicate Ethernet reception.
Kernel Amber On when in Kernel Mode.
Flashing while in download mode.
10MB Green On when the module is connected to a 10 Megabit network.
100MB Green On when the module is connected to a 100 Megabit network.
Fduplex Green On when Ethernet is operating in the full duplex mode.
Appl Green On when crash log entry exists.
278
840 USE 100 00 11/2004
Run LED Status
Ethernet Modules
The following table lists each available state of the Run LED indicator and provides diagnostic information for that state
Indicator State Status
On (steady) Normal operation: The NOE module is ready for network communication.
Number of flashes in sequence one Not used two three four five
Not used
No Link: the network cable is not connected or is defective.
Duplicate IP address: The module will stay off-line.
No IP address: The module is attempting to obtain an IP address from a
BOOTP server.
six seven eight
Using default IP address
No valid executive NOE present
Invalid IP configuration. Likely cause: Default gateway is not on the same subnet mask as the NOE>
Key Features The key features of the 140 NOE 771 (-00, -01, -10, -11) models are listed below:
HTTP Server
FTP Server
Flash File System
BOOTP Client
BOOTP Server
SNMP V2 Agent
MODBUS Messaging
I/O Scanner
Hot Standby
Global Data - Publish / Subscribe
Bandwidth Monitoring
Faulty Device Replacement (DHCP Server)
Enhanced Web Diagnostics
Schneider Private MIB
FactoryCast Application
User Programmable Web Pages
X
X
X
X
X
X
X
X
-00
X
X
X
X
X
X
X
-01
X
X
X
X
X
X
X
In Version 2.0 X
X
X
X
X
X
X
X
X
-10
X
X
X
X
X
X
X
-11
X
X
X
X
X
X
X
X
X
In Version 2.0
840 USE 100 00 11/2004
279
Ethernet Modules
MODBUS I/O
Scanner
The functionality of the NOE771xx module is further enhanced by the addition of a
MODBUS I/O Scanner that can be configured with either the Modsoft, Concept, or
ProWorx programming panel. This allows the user a means to transfer data between network nodes without using the MSTR instruction.
z z
The NOE771 MODBUS I/O Scanner can be configured by either of the following two methods:
Peer Cop (Available on NOE77100 only)
Ethernet I/O Scanner
1RWH
It is recommended that the enhanced MODBUS I/O Scanner be used for all new installations. Peer Cop functionality is provided only as an easy migration path for an existing installation. The enhanced MODBUS I/O Scanner provides greater functionality than the
Peer Cop based I/O scanner.
Peer Cop Based
I/O Scanner
The following table lists the characteristics of the Peer Cop based MODBUS I/O
Scanner, which is available only on the NOE77100.
Parameter
Max. No. of Devices
Max. No. of Input Words
Max. No. of Output Words
Value
64
500
500
HealthTimeout Value
Input TimeOutState
Global Setting (20 Msec to 2 Secs in 20 mSec increments)
Global Setting (Zero or Hold)
IP Address Derived from MODBUS Address (must be on NOE’s Subnet)
Remote Register Reference Not configurable - 400001 is used
280
840 USE 100 00 11/2004
Enhanced
Modbus I/O
Scanner
Ethernet Modules
The following table lists the characteristics of the Enhanced based MODBUS I/O
Scanner, which is available on the NOE77100, NOE77101, and NOE77111.
Parameter
Max. No. of Devices
Max. No. of Input Words
Max. No. of Output Words
Value
128: NOE77100, NOE77101 and NOE77111.
4000
4000
HealthTimeout Value
Input TimeOutState
Individual Setting (1 Msec to 2 Secs in 1 mSec increments)
Individually Settable
IP Address Individually Settable
Remote Register Reference Configurable
Min. Update Rate Settable
Refer to the Quantum NOE 771 xx Ethernet Modules User Guide (840 USE 116 00) to learn how to configure the MODBUS I/O Scanner.
The following information describes the functionality of the MODBUS/TCP Server.
MODBUS/TCP
Server
Introduction –
Client
Introduction –
Server
All NOE771xx Quantum Ethernet TCP/IP modules provide the user with the capability of transferring data to and from nodes on a TCP/IP network through the use of a communication instruction. All PLCs that support networking communication capabilities over Ethernet can use the MSTR Ladder Logic instruction to read or write controller information or can also use IEC communication blocks.
All NOE771xx Quantum Ethernet TCP/IP modules provide the user with the ability to access data from the controller using the standard MODBUS/TCP protocol. Any device: PC, HMI package, another PLC, or any MODBUS/TCP compliant device can access data from the PLC. The MODBUS/TCP Server also allows programming panels to log into the controller over Ethernet.
840 USE 100 00 11/2004
281
Ethernet Modules
Limitations
Performance
The NOE771xx supports up to 64 simultaneous MODBUS/TCP Server connections.
The NOE771xx allows only one Programming Panel to be logged in at a time to guarantee consistency of changes to the controller configuration.
The following MODBUS/TCP commands are supported by the NOE: z z z z z z
Read Data
Write Data
Read/Write Data
Get Remote Statistics
Clear Remote Statistics
MODBUS 125 Commands (used by programming panels to download a new
Exec to the NOE)
The following table shows the performance characteristics of the NOE771xx’s
MODBUS/TCP Server.
Parameter
Typical Response Time (ms)
Number of MODBUS connections (Client and Server)
Number of simultaneous login channels
Value
0.6
64 (-01, -11)
16 (Client -00)
32 (Server -10)
1
1RWH NOE771xx MODBUS/TCP performance measurements are made with
Quantum 140CPU53414 PLC.
FTP and HTTP
Server
FTP Server
The following information describes services provided by the FTP and HTTP servers.
The NOE771xx’s File Transfer Protocol (FTP) Server is available as soon as the module receives an IP address. Any FTP client can log on to the module, if the client uses the correct user name and password.
The FTP Server provides the following services: z z z
Update the NOE’s firmware by downloading a new Exec
Provides error log visibility by uploading error log files
Upload/download BOOTP Server and SNMP configuration files
The default user name is USER, and the default password is USERUSER. Both the user name and password are case sensitive. Refer to the Quantum NOE 771 xx
Ethernet Modules User Guide for instructions about how to change the password, and how to add or delete user names to the FTP Server.
There should be only one FTP client per module.
282
840 USE 100 00 11/2004
HTTP Server
Ethernet Modules
The NOE771xx’s HyperText Transport Protocol (HTTP) Server is available as soon as the module receives an IP address. It can be used with version 4.0 or greater of either the Internet Explorer or Netscape browser.
The NOE771xx’s HyperText Transport Protocol (HTTP) Server allows you to view z z z z the following information:
Module’s Ethernet statistics
Controller and I/O information
BOOTP/DHCP/FDR (Faulty Device Replacement) Server information
Global Data (Publish / Subscribe)
The HTTP Server’s HTML pages allow you to configure the module’s BOOTP/
DHCP/FDR Server and SNMP Agent.
The HTTP Server is protected with a default name and password. The default name and password are both USER, and both are case sensitive. They can both be changed via the Configuration page on the NOE 771 0x’s Web Embedded Pages
(see the Installing the Module chapter in the Quantum NOE 771 xx Ethernet
Modules User Guide ).
For the NOE7711x modules, they can be changed via the FactoryCast Configurator.
The NOE771xx supports a maximum of 32 HTTP simultaneous connections.
1RWH Browsers may open multiple connections so 32 HTTP connections does not indicate 32 simultaneous users.
1RWH The NOE7710x module does not support user downloaded Web pages. You will need to purchase the 140NOE7711x module to support that requirement.
Address Servers The following information describes the services provided by the Address Servers: z z
BOOTP Server
DHCP Server
840 USE 100 00 11/2004
283
Ethernet Modules
BOOTP Server
Your NOE
BOOTP Server
1RWH The BOOTP Server is available on the 140NOE771 -00 and -10 models.
The BOOTstrap Protocol (BOOTP) software, compliant with RFC 951, is used to assign IP addresses to nodes on an Ethernet network. Devices (hosts) on the network issue BOOTP requests during their initialization sequence, and a BOOTP
Server that receives the request will extract the required IP address information from its database and place it in BOOTP response messages to the requesting devices.
The devices will use the assigned IP addresses, received from the BOOTP Server, for all communication occurring on the network.
Your NOE x0 module comes supplied with a BOOTP Server. This feature allows you to provide IP addresses to all the I/O devices being serviced by the NOE771x0.
Providing a BOOTP Server that is built into your NOE771x0 module eliminates the need for you to have a dedicated PC on your I/O network acting as a BOOTP Server.
1RWH
The NOE771x0’s BOOTP Server cannot be used to provide its own IP address.
You can configure your NOE771x0’s BOOTP Server from the module’s HTTP Web page. Using this feature allows you to add, remove, and edit devices to the BOOTP
Server’s database, which is maintained on the modules non-volatile memory.
284
840 USE 100 00 11/2004
DHCP Server
Ethernet Modules
1RWH The DHCP Server is available on the 140NOE771x1 models.
Dynamic Host Configuration Protocol (DHCP) is a superset of the BOOTP Protocol.
Your 140NOE771x1 has a DHCP Server. The DHCP Server is compliant with RFC
1531. The DHCP Server can be used to provide the IP configuration to devices using BOOTP or devices using DHCP.
The DHCP Server has entries that use the MAC address to serve the IP configuration and entries in the Server that use the role name to serve the IP configuration. See the Address Server Configuration/Faulty Device Replacement chapter in the Quantum NOE 771 xx Ethernet Modules User Guide for details on configuring your NOE’s address Server.
If you are migrating a BOOTP configuration from a 140NOE771x0 module to the new 140 NOE 771 x1 module, see the Address Server Configuration/Faulty Device
Replacement chapter in the Quantum NOE 771 xx Ethernet Modules User Guide for details on automatic upgrade of your configuration for the new DHCP Server.
1RWH OPERATING ON A CORPORATE NETWORK
Before placing the NOE on a corporate network, Schneider Automation recommends that you discuss the installation with your MIS department. It is likely that your company’s corporate network has at least one DHCP Server running already. If the NOE’s DHCP Server is running on the same network, it may disturb the network.
To avoid any possible problem related to the NOE’s DHCP Server on the corporate network, you must ensure that the DHCP Server is not running in the NOE by not having address entries in the configuration. If there are no configured devices in the address Server configuration page, then the NOE will not start the DHCP
Server.
840 USE 100 00 11/2004
285
Ethernet Modules
Global Data Global Data service is a real time Publisher/Subscriber mechanism providing the most efficient data exchange for PLC application coordination.
Devices supporting Global Data are arranged in a distribution group for the purpose of application variable exchange and synchronization. Each Global Data device can publish up to one network (application) variable and subscribe up to 64 network
(application) variables.
The Quantum NOE’s embedded Web Global Data Configuration Page provides a configuration screen to determine which and how many application variables are exchanged with this service. After configuration, the exchanges between all stations belonging to the same distribution group are done automatically.
The Global Data service uses the 4x register space for Global Data exchanges.
Key Features of
Global Data z z z z z z z
The main features for Global Data are:
One Publisher and many Subscribers
A device can publish one network variable of up to 512 registers
A device can subscribe to several network variables of up to 2048 4x registers
A device subscribes to the complete network variable
One distribution group per network IP address
Application defined publication rate
Up to 64 Global Data network variables (numbered from 1 to 64) can be part of z the data distribution group
An NOE has only one multicast address; consequently, it can only publish and z subscribe inside the group
A device can participate in several distribution groups by using multiple NOEs in the rack
Global Data has an advantage over Client/Server services when more than one
Subscriber is receiving the same data since only one transaction is necessary for all
Subscribers to receive the data. z z
This advantage offers two benefits:
Reduce overall network traffic
Ensure tighter synchronization of multiple subscribers
Bandwith
Monitoring
Bandwidth Monitoring allows you to monitor the NOE’s CPU allocation for each of the following services: Global Data, I/O Scanning, and Messaging. The Bandwidth
Monitoring service retrieves workload data and returns one of two pieces of information: whether the module has free resources or whether the module is z z working at capacity. Knowing the resource allocation helps you:
Decide about allocating your resources
Determine the number of NOEs needed in a system
286
840 USE 100 00 11/2004
Available
Services
Ethernet Modules z z z
The services accessed and monitored are:
Global Data
I/O Scanner
Modbus Messaging
If you use Bandwidth Monitoring, you do not need to develop a new set of access functions. The actual NOE CPU load is computed each second.
Bandwidth
Monitoring Load
Rates
The Bandwidth Monitoring service checks once a second and computes four (4) values in private data: z z z z
Percentage of NOE’s CPU allocated to
Percentage of NOE’s CPU allocated to
Global Data
Percentage of NOE’s CPU allocated to the I/O Scanner
Messaging
Percentage of NOE’s CPU allocated to other services and idle
Results are returned as percentages. CPU time spent in other services is shown as
"Other" or "Free." Bandwidth Monitoring uses the same functions as used by SNMP.
The three service rates, Global Data, I/O Scanner, and Messaging, are computed using the following formula:
(Current load * 100) / Maximum Load
Table of Maximum Load Rates
Diagnostic Service Workload Data Returned
Global Data
I/O Scanner
Messaging
Number of published variables per second
Number of transactions per second
Number of messages treated per second
Maximum load for NOE 771 x1
800
4200
410
The current load is computed dynamically.
1RWH The loads are dependent on controller scan time. Each application has an expected scan time. Therefore, when evaluating the loads, you should ensure that the controller scan time is set to the expected scan time for the application being modelled.
840 USE 100 00 11/2004
287
Ethernet Modules
Enhanced Web
Diagnostics
1RWH These services are available on the 140NOE771x1 modules.
The embedded Web server provides Web pages that you may use to diagnose
Transparent Factory / Real Time services.
Those diagnostic services are listed below:
1.
Global Data diagnostics z Status of all Global Data services z Status of all subscribed and published variables z Publication / Subscription rate
2.
I/O Scanning diagnostics z z
Status of all I/O Scanning services
Status of individual scanned devices z Actual I/O scanning rate
3.
Messaging diagnostics z Diagnostic information for Port 502 messaging
4.
Bandwidth Monitoring z Throughput measurement of NOE by service
1RWH
All these pages are protected by the general HTTP password.
288
840 USE 100 00 11/2004
Intelligent/Special Purpose
Modules for the Quantum
14
At a Glance
Introduction
What’s in this
Chapter?
z z z z z z
This chapter provides information on the following intelligent/special purpose modules:
Five Channel High Speed Counter Module
Two Channel High Speed Counter Module
ASCII Interface Module
High Speed Interrupt Module
Single Axis Motion Modules
Hot Standby Module
This chapter contains the following topics:
Topic
140EHC10500 High Speed Counter Module
I/O Configuration for 140EHC20200
140EHC20200 High Speed Counter Module
140ESI06210 ASCII Interface Module
140HLI34000 High Speed Interrupt Module
140MSB/MSC10100 Quantum MSX Motion Modules
140XBE10000 Backplane Expander and Cable
140CHS11000 Hot Standby Module
Page
840 USE 100 00 11/2004
289
Intelligent/Special Purpose
140EHC10500 High Speed Counter Module
Overview This section provides specifications and descriptions of the high speed counter modules EHC10500, Five Channel Discrete High Speed Counter. The High Speed
Counter module is a discrete counter for proximity and magnetic pickups.
Related
Documentation
For more detailed information on the planning, installation and use of this module, refer to the Quantum Automation Series 140EHC10500 Module User Guide
(840 USE 443 00).
EHC10500
Counter Module
The following figure shows the EHC10500 Five Channel Discrete High Speed
Counter module.
LED Area
X
Model Number
Module Description
Color Code
Field Wiring
Terminal Strip
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Customer Identification Label
(Fold label and place it inside the door)
Removable Door
32
34
36
38
40
24
26
28
30
2
4
6
8
10
12
14
16
18
31
33
35
37
39
7
9
11
13
15
17
1
3
5
25
27
29
19
21
23
290
840 USE 100 00 11/2004
Specifications
Intelligent/Special Purpose
The following table shows the specifications for the EHC10500 high speed counter.
Specifications
Number of Channels
LEDs
Required Addressing
5 counter inputs, 8 digital inputs, and 8 digital outputs
Active
F
R (Green) -
1 ... 8 (Green - left column) -
Module is ready
Discrete Inputs
(IN1 ... IN8)
C1 ... C5 (Green - middle column) - Discrete Counter Inputs
(C1 ... C5)
1 ... 8 (Green - right column) Discrete Outputs
(OUT1 ... OUT8)
24 Vdc is present P (Green) -
13 Words In
13 Words Out
Discrete Counter Inputs
Count Frequency
Input Thresholds
Input Current
Duty Cycle
Data Formats
Operation Modes
Max Continuous Input
Voltage
Discrete Inputs
VREF Supply + 24 Vdc
100 kHz max @ 5Vdc
35 kHz max @ 24Vdc
On
+3.1 ... +5V
+15 ... +30V
7 mA
1 : 1
16 Bit Counter: 65,535 Decimal
32 Bit Counter: 2,147,483,647 Decimal
Discrete incremental counter
30 Vdc
Off
0 ... 1.15V@5 Vdc
-3 ... +5V@24 Vdc
On State (Vdc)
-3.0 ... 5.0.
5 mA
Off State (Vdc)
15.0 ... 30.0
Input Current (typical)
Discrete Outputs
FET Switch ON
FET Switch OFF
Max Load Current (each output)
Output Off State Leakage
20 ... 30 Vdc
0 Vdc (ground reference)
210 mA max
0.1 mA max @ 30 Vdc
840 USE 100 00 11/2004
291
Intelligent/Special Purpose
Specifications
Output On State Voltage
Drop
Miscellaneous
Isolation (Channel to Bus)
Fault Detection
Power Dissipation
Bus Current Required
External 24 Vdc Power
Supply
External Fusing
Compatibility
1.25 Vdc @ 0.5 A
500 Vac rms for 1 minute
Loss of output field power, output short circuit
≤ 6 W
250 mA
19.2 ... 30 Vdc, 24 Vdc nominal, 60 mA required plus the load current for each output
User discretion
Programming Software: Modsoft V2.32 or Concept 2.0 at a minimum
Quantum Controllers: All, V2.0 at a minimum
LED Indicators and Descriptions
The following figure shows the LED indicators for the EHC10500 high speed counter.
2
3
4
5
6
7
8
R Active
C1
C2
C3
C4
C5
1
2
3
4
5
6
7
8
F
P
292
The following table shows the LED descriptions for the EHC10500 high speed counter.
LED Descriptions
LEDs
Active
F
R
Color Indication when On
Green Bus communication is present
Red Lights upon any defined hardware, firmware, and process error.
Green Indicates firmware initialization is complete and the module is ready for service.
1 ... 8 (left column) Green Digital inputs IN1 ... IN8
C1 ... C5 Green Counter inputs xxC1 ... xxC5 (xx=5/24)
1 ... 8 (right column) Green Digital outputs OUT1 ... OUT8
P Green 24 Vdc is present
840 USE 100 00 11/2004
Intelligent/Special Purpose
Wiring Diagram The following figure show the EHC10500 wiring diagram.
N/C
2 1
N/C
4 3
N/C
6 5
N/C
8 7
N/C
10
M11
12
M12
14
M13
16
M14
18
M15
20
IN2
22
IN4
24
IN6
26
IN8
28
Common
30
OUT2
32
OUT4
34
OUT6
36
OUT8
38
External Power Supply
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
40 39
5 Vdc C1
5 Vdc C2
5 Vdc C3
5 Vdc C4
5 Vdc C5
24 Vdc C1
24 Vdc C2
24 Vdc C3
24 Vdc C4
24 Vdc C5
IN1
IN3
IN5
IN7
Common
OUT1
OUT3
OUT5
OUT7
Return
+ –
+
5 Vdc Counter
Input Signals
(C1...C5)
+ –
5 Vdc
To M11
24 Vdc Counter
Input Signals
(C1...C5)
+ –
24 Vdc
To M11
–
24 Vdc
24 Vdc
Input Signals
(IN1...IN8)
24 Vdc
Output Signals
(OUT1...OUT8)
24 Vdc
1RWH
N / C = Not Connected.
Terminals 29 and 30 are common and are jumpered together.
840 USE 100 00 11/2004
293
Intelligent/Special Purpose
I/O Configuration for 140EHC20200
Overview This section describes configuration of the 140EHC20200 high speed counter module which operates in pulse or quadrature mode and accepts single ended or differentiated inputs.
I/O Map Register
Assignment
The 140EHC20200 high speed counter requires six contiguous output (4X) and six contiguous input (3X) registers in the I/O map.
The 4X registers perform the same configuration tasks as the Modzoom screenassigned parameters. Also, the preset and the enable inputs connected to the field wiring terminal block perform the same functions as those software command z z control bits. When both methods are used to:
Preset a counter—the last preset executed has precedence.
Enable/disable a counter—it will only be enabled when both the hardware enable input and software enable control bit are in the enable state.
For simple applications, the zoom screens rather than the I/O mapped registers can be used to configure the module. Zoom screens are used only while the PLC is stopped. The selected parameters take effect when the PLC is set to run. For applications that require that module parameters be changed while the system is running, user logic can modify the I/O map-assigned registers to override the previously selected zoom parameters.
When using either zoom screens or I/O map registers, the maximum values specified in the Load Values Command section are the largest values that can be used by the module.
The I/O Mapped registers discussed in this section are
4x output registers that: z z z z
Preset and enable/disable input counters.
Load setpoint and maximum values to define output turn on points.
Set mode of operation, count, or rate sample.
Enable output switches and configures their mode of operation.
3X input registers that: z z z
Hold count or rate sample data.
Display field power status.
Echo 4X command data after the command is executed by the module.
294
840 USE 100 00 11/2004
EHC20200
Operations
Command 1
CONFIGURES the Module
Intelligent/Special Purpose z z z z
Four operations can be performed:
Command 1 CONFIGURES the Module
Command 2 LOADS VALUES
Command 3 READ INPUT COUNTER
Command 4 READS RATE SAMPLE or LAST INPUT COUNT BEFORE
PRESET
Each operation uses one or more of both types of registers assigned to the module.
In addition to the command definition byte, the first 4X register for all commands contain control bits to preset and enable/disable counters of either channel.
Command 1 uses three 4X registers and six 3X registers as shown in the following figure.
4X
4X+1
4X+2
3X
3X+1
3X+2
3X+3
3X+4
3X+5 z z
This command does the following: z z
Sets up the module for pulse or quadrature input.
Sets up the module for count or rate-sample mode. Counters cannot be separately configured.
Defines counter register length—16 or 32 bit.
Enables output assertion including module communication loss state. Output assertion is available if configured for two 16 bit, or one 32 bit counter. No output z assertion is available if two 32 bit counters are defined, or in rate-sample mode.
Defines output assertion point.
840 USE 100 00 11/2004
295
Intelligent/Special Purpose
Command 2
LOAD VALUES
Command 3
READ INPUT
COUNTER
There are four formats for this command. It uses up to six 4X registers and six 3X registers as shown in the following figure.
4X
4X+1
4X+2
4X+3
4X+4
4X+5
3X
3X+1
3X+2
3X+3
3X+4
3X+5
Values loaded may be: z z z
Maximum count and setpoint (i.e., output turn on times).
Output assertion ON time duration (one input only).
Rate sample time interval.
Command 3 uses one 4X register and six 3X registers as shown in the following figure.
4X 3X
3X+1
3X+2
3X+3
3X+4
3X+5
296
840 USE 100 00 11/2004
Intelligent/Special Purpose
Command 4
READS RATE
SAMPLE or LAST
INPUT COUNT
BEFORE
PRESET
Command 4 uses one 4X register and six 3X registers as shown in the following figure.
4X 3X
3X+1
3X+2
3X+3
3X+4
3X+5
1RWH 4X register formats for the commands are described first. The 3X register contents after issuing Command 1 or 2 are listed after the 4X register description for Command 2, since the responses are the same for both. The 3X responses for
Commands 3 and 4 immediately follow those commands.
1RWH When Command 0 (4X = 00XX) or any other undefined commands are asserted in the 4X register, the 3X registers will contain the count inputs if in count mode (same as Command 3) and the rate sample values when in rate-sample mode (same as Command 4).
Command
Words Described
The following describes the command words and responses.
840 USE 100 00 11/2004
297
Intelligent/Special Purpose
Command 1 -
CONFIGURE,
Output Register
Format
(4X = 01XX hex)
The following figure shows the 4x output register for command 1.
;
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
1 = Preset Counter 1
1 = Enable Counter 1
1 = Disable Counter 1
1 = Preset Counter 2
1 = Enable Counter 2
1 = Disable Counter 2
Configure Command Bit
The following figure shows the 4x+1 output register for command 1 (4X+1).
;
16 15 14 13 12 11 10 9
0
0
1
1
0
1
0
1
8 7 6 5 4 3 2 1
0/1 = Pulse/Quadrature Input Counter 1
0/1 = Pulse/Quadrature Input Counter 2
Two 16 bit counters, Output Assertion ON
One 32 bit counter, Output Assertion ON
Two 16 bit counters, Output Assertion ON
Two 32 bit counters, Output Assertion OFF
0/1 = Rate Sample Mode OFF/ON
When = 1, automatically sets bits 11 and 12
(i.e., two 32 bit counters, no Output Assert)
0/1 = Comm Lost Output Assert OFF/ON
When = 0, if module communication with the bus is lost, outputs are disabled. When = 1, outputs continue to operate as configured.
298
840 USE 100 00 11/2004
840 USE 100 00 11/2004
Intelligent/Special Purpose
The following figure shows the 4x+2 output register for command 1.
;
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Output 2A Operating Mode
Output 2B Operating Mode
Output 1A Operating Mode
Output 1B Operating Mode
%LWV
000
001
010
011
100
101
110
111
0RGH
0
1
2
5
6
3
4
7
'HVFULSWLRQ
Disable Output
ON if Count = Setpoint
Latched ON if Count = Setpoint. Hardware RESET required to turn OFF
ON if Count = Maximum Count
Latched ON if Count = Maximum Count. Hardware RESET required to turn OFF
ON when Count = Setpoint for time specified in Command 2 register
ON when Count = Maximum Count for time specified in Command 2 register
Not Used
&$87,21
0RGXOHGLVDEOHSRVVLELOLW\
The Output ON time specified in the Command 2 registers may be used by only one of the four outputs. When more than one output is set to mode 5 or 6, the module firmware will operate the first one encountered, and disable the other outputs set to modes 5 or 6.
)DLOXUHWRIROORZWKLVSUHFDXWLRQFDQUHVXOWLQLQMXU\RUHTXLSPHQWGDPDJH
299
Intelligent/Special Purpose
Command 2.
LOAD VALUES,
Output Register
Format
(4X = 02XX hex)
The LOAD VALUES 4X register format depends on the Counter/Rate Sample mode selected in Command 1, Register 4X+1, bits 11 and 12.
If configured for two 16 bit Counters, Output Assert ON, the following figures, which shows counters for registers 4X through 4X+5, are displayed.
;
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
1 = Preset Counter 1
1 = Enable Counter 1
1 = Disable Counter 1
1 = Preset Counter 2
1 = Enable Counter 2
1 = Disable Counter 2
Load Values Command
Bit
;
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Maximum Count for Counter 1 (max = FFFF hex)
;
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
300
Setpoint for Counter 1 (max = FFFF hex)
;
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Maximum Count for Counter 2 (max = FFFF hex)
;
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Setpoint for Counter 2 (max = FFFF hex)
;
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Output Assert ON Time (milliseconds, max = 3FFF hex)
1RWH
Zero set into any 4X register means no change.
840 USE 100 00 11/2004
840 USE 100 00 11/2004
Intelligent/Special Purpose
If configured for one 32 bit Counter, Output Assert ON, the following figures, which show the counters for registers 4X through 4X+5, with low and high word, are displayed.
;
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
1 = Preset Counter 1
1 = Enable Counter 1
1 = Disable Counter 1
1 = Preset Counter 2
1 = Enable Counter 2
1 = Disable Counter 2
Load Values Command
Bit
;/RZ:RUG
;+LJK:RUG
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Maximum Count for Counter 1 (max = 7FFFFFFF hex)
;/RZ:RUG
;+LJK:RUG
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Setpoint for Counter 1 (max = 7FFFFFFF hex)
;
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Output Assert ON Time (milliseconds, max = 3FFF hex)
1RWH Zero set into any 4X register pair for 32 bit values or any 4X register means no change.
301
Intelligent/Special Purpose
If configured for two 32 bit Counters - NO Output Assert, the following figures, which show the 4X through 4X+4 counters, with low and high word, are displayed.
;
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
1 = Preset Counter 1
1 = Enable Counter 1
1 = Disable Counter 1
1 = Preset Counter 2
1 = Enable Counter 2
1 = Disable Counter 2
Load Values Command
Bit
;/RZ:RUG
;+LJK:RUG
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Maximum Count for Counter 1 (max = 7FFFFFFF hex)
;/RZ:RUG
;+LJK:RUG
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Maximum Count for Counter 2 (max = 7FFFFFFF hex)
1RWH Zero set into any 4X register pair for 32 bit values or any 4X register means no change.
302
840 USE 100 00 11/2004
Intelligent/Special Purpose
If configured for Rate Sample Mode, the following figures, which show the 4X through 4X+2 counters, are displayed.
;
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
1 = Preset Counter 1
1 = Enable Counter 1
1 = Disable Counter 1
1 = Preset Counter 2
1 = Enable Counter 2
1 = Disable Counter 2
Load Values Command
Bit
;
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Rate Sample Timer Value, Counter 1 (milliseconds, max = 3FFF hex)
;
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Rate Sample Timer Value, Counter 2 (milliseconds, max = 3FFF hex)
1RWH Zero set into any 4X register or any 4X register pair for 32 bit values means no change.
Command 1 and
Command 2
Response
Formats
The following figures show the 3X through 3X+5 response formats.
;
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Configure or
Load Values
Command Byte
;WR;
echoes 4X+1 to 4X+4 register contents.
;
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
1 = Field Power Lost
840 USE 100 00 11/2004
303
Intelligent/Special Purpose
Command 3,
READ INPUT
COUNTER,
Output Register
Format (4X =
03XX hex)
The following figure shows the 4X register for Command 3, READ INPUT
COUNTER, output register format.
;
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
1 = Preset Counter 1
1 = Enable Counter 1
1 = Disable Counter 1
1 = Preset Counter 2
1 = Enable Counter 2
1 = Disable Counter 2
Read Counter Inputs Command Bits
Command 3
Response
Format
The following figure shows the Command 3 response format.
;
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Read Counter Inputs
Command Byte
;DQG;
= Counter 1’s 16 or 32 bit Current Count.
;DQG; = Counter 2’s 16 or 32 bit Current Count.
;
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
1 = Field Power Lost
Command 4,
READ RATE
SAMPLE or
READ LAST
COUNT VALUE
BEFORE MOST
RECENT
PRESET, Output
Register Format
(4X = 04XX hex)
The following figure shows the 4x counters for Command 4.
;
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
1 = Preset Counter 1
1 = Enable Counter 1
1 = Disable Counter 1
1 = Preset Counter 2
1 = Enable Counter 2
1 = Disable Counter 2
Read Rate/Last Count
Command Bit
304
840 USE 100 00 11/2004
Command 4
Response
Format
Intelligent/Special Purpose
The following figures show the counters for 3X through 3X+5 for command 4.
;
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
I/O Map Status
Byte
;DQG; = Counter 1’s 32 bit Rate Sample / Last Count Before Preset.
;DQG;
= Counter 2’s 32 bit Rate Sample / Last Count Before Preset.
Read Rate Sample/
Last Count
Command Byte
;
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
1 = Field Power Lost
The most significant bit in the I/O Map status byte is used for the 140EHC20200
High Speed Counter Module. The following figure shows the map status byte register.
8 7 6 5 4 3 2 1
1 = Internal Fuse Blown or External Output Supply Lost
840 USE 100 00 11/2004
305
Intelligent/Special Purpose
Using I/O
Mapped
Registers to
Operate the High
Speed Counter
COUNT UP Example
Field connections for this example are illustrated in the EHC202 wiring diagrams 1–
4 in this section. The maximum allowable Vref value is 30 Vdc. Input pulse on-off threshold levels for the 5 ... 24 Vdc Vref range are listed in the module specification table. The minimum differential input is 1.8 V.
The following user logic: z z z z z
Configures the module to count up from zero.
Turns an output on for one count at a setpoint value of 50.
Continues counting to 100.
Rolls over to zero and turn on a second output for one count.
Repeats the operation.
See
for counter timing diagrams illustrating output on times.
The following table shows the I/O Map register assignments.
Module
140EHC20200
Input Ref
300001-300006
Output Ref
400001-400006
Description
EHC20200 High Speed
In this example, block moves are used to load the operating parameters into the module. This requires pre-defined tables be established. Register values are in HEX format.
Module
Configuration
The following table shows the module configurations.
400101
400102
400103
0140
0000
3100
CONFIGURE command, Disable Counter 2
Pulse input, two 16 bit counters, output assert on Rate Sample
OFF, disable outputs at bus communication loss
Output 1A on at setpoint, Output 1B on at maximum count +1
Output 2A and 2B are disabled
400104
400105
400106
0000
0000
0000
Not used by this command
306
840 USE 100 00 11/2004
Load Values
Response for
Configuration
Command
Intelligent/Special Purpose
The following table shows the load values.
400201 0243
400202
400203
400204
400205
400206
0064
0032
0000
0000
0000
LOAD VALUES command, disable Counter 2, preset and enable
Counter 1
Counter 1 maximum count, count after which Output 1B turns on
Counter 1 setpoint, count when Output 1A turns on
Counter 2 maximum count (not used in this example)
Counter 2 setpoint (not used in this example)
Output Assert Time (Not used in this example, one output only, if used)
Zeros in the 4X registers also mean no change. Setpoint, maximum count and assert time can only be set to zero using the Modzoom screens. When the registers in this example are echoed, zeros will appear but the actual content in the module will be unchanged from previous values. In this example, Counter 2 is disabled and its outputs and timed assert have not been selected. Registers 400204 - 6 have no meaning.
After the module executes the Configure and Load Value’s commands, they are echoed in the I/O mapped 3X registers except for the command register’s low 8 bits.
Command execution time by the module is 1 ms. Actual time between the 4X register block move and the echo response display in the 3X registers is dependent on User Logic and hardware configuration. An echo of the Configuration command registers would appear as follows:
The following table shows the echo response for the configuration command.
Register
300001
300002
300003
300004
300005
300006
Value
0100
0000
3100
0000
0000
0000
840 USE 100 00 11/2004
307
Intelligent/Special Purpose
Read Input
Counter
Command
3x Register
Content
The following table shows the read input registers.
READ INPUT COUNTER command 40301
40302
40303
40304
40305
40306
0300
0000
0000
0000
0000
0000
Not used by this command
When this command is issued, the content of the input pulse counter is retrieved.
The 3X register content would appear as shown in the following table.
Register
300001
300002
300003
Value
0300
XXXX
0000
300004
300005
300006
0000
0000
0X00
Description
Command echo
Current input count
Zeros as the count will not exceed 100. For counts above 65,536, this register is a multiplier. As an example: 30002 has a value of 324 and
30003 a value of 3.The total count is (65,536 x 3) + 324 = 196,932
Counter 2 is disabled
Counter 2 is disabled
X is the field power indicator
Reset of Latched
Outputs
If register 400103 in the Module Configuration Table has been set to 4200, Output
1A would have been latched on at setpoint and Output 1B latched on at maximum count. Wiring Diagrams 2 and 4 show how the encoder Z outputs could be used to reset the latched outputs. The minimum pulse width to reset outputs is 1 μ s.
308
840 USE 100 00 11/2004
User Logic
840 USE 100 00 11/2004
Intelligent/Special Purpose
The User Logic illustrated accomplishes the module’s configuration and then causes the input counter to be displayed after the first three successive scans by the PLC when it is in RUN mode.The following figure shows the module’s configuration in
RUN mode.
Load Configuration
400101
/RDG&RQILJXUDWLRQ'RQH
000010 000010
400001
BLKM
#00006
000010
P
000011
Load Values
400201
400001
BLKM
#00006
P
000012
Read Counter
400301
400001
BLKM
#00006
Check Configuration
300001
#00256
TEST
#00001
000011
Check Load Values Echo
300001
#00512
TEST
#00001
000012
&RQILJXUDWLRQ'RQH
/RDG9DOXHV'RQH
309
Intelligent/Special Purpose
COUNT DOWN
Example
RATE SAMPLE
Example for
Either Pulse or
Quadrature Input
Field connections for this example are illustrated in Wiring Diagrams1–4. The connections on terminals 15 and 16 are optional, depending on the use requirements of the outputs. Terminals 39 and 40 always require the 24 Vdc supply connections. The maximum allowable Vref value is 30 Vdc. Input pulse on-off threshold levels for the 5 ... 24 Vdc Vref range are listed in the module specification table. The minimum differential input is 1.8 V.
As with count examples, tables are set up and transferred to the module using block moves. The User Logic for Rate Sample is the same as that used for Pulse Input
Count Up/Down.
Module
Configuration
The COUNT DOWN example uses the same wiring as in the count up example, except the Input 1B+ level is changed to common (connected to Vref-) for Pulse
Inputs illustrated in Wiring Diagrams 1 and 2. For Quadrature Inputs, no wiring change is required as the count direction is decoded internally by sensing the phase shift change between inputs A and B.
The User Logic is the same as for the count example. The actual operation of the module is different in that the output associated with maximum count turns on after zero count has been reached.
The example configures the module to decrement the input count from the maximum value, turn on an output at a setpoint value of 50, and turn on a second output after the input counter had reached zero and rolled over to the maximum count; the operation is then repeated. The initial loading of the maximum count will not cause its associated output to turn on.
The following table shows the module configurations.
400101
400102
400103
400104
400105
400106
0140
1000
0000
0000
0000
0000
CONFIGURE command, Disable Counter 2
Pulse input, Rate Sample ON, disable outputs at bus communication loss (Note: Bits 11 and 12 were not required.)
Not used by this command
310
840 USE 100 00 11/2004
Load Values
Read Rate
Sample
Response to
Read Rate
Sample
Command
Intelligent/Special Purpose
The following table shows the load values.
400201 0243 LOAD VALUES command, disable Counter 2, preset and enable Counter 1
400202 XXXX Counter 1 Rate Sample Time in milliseconds
400203 0000 Counter 2 Rate Sample Time in milliseconds (Not used in this example)
400204 0000 Not used by this command
400205 0000
400206 0000
1RWH Command echoes are the same as described in the Pulse Input Count Up/
Down examples.
The following table shows a read rate sample.
READ INPUT COUNTER command 40030
400302
400303
400304
400305
400306
0400
0000
0000
0000
0000
0000
Not used by this command
When this command is issued, the input pulse counter content is retrieved. The 3X register content is the count over the time period selected in the Load Values registers 4X + 1 and 4X + 2. The 3X response to the Read-Rate Sample command in register 40301 is as follows.
The following table shows the responses to the read rate sample command.
Register
300001
300002
300003
300004
300005
300006
Value
0400
XXXX
XXXX
0000
0000
0X00
Description
Command echo
Counter 1 Input rate low word
Counter 1 Input rate high word: this register is a multiplier. As an example: 30002 has a value of 324 and 30003 a value of 3. The total count is (65,536 x 3) + 324 = 196,932
Counter 2 is disabled
Counter 2 is disabled
X is the field power indicator
840 USE 100 00 11/2004
311
Intelligent/Special Purpose
Rate Sample
Mode Caution
If a version 02.00 or higher module replaces a module which has a version number less than 02.00 in a Rate Sample mode application, extra software configuration may be required.
Rate Sample mode is set using Command 1, CONFIGURE (01XX), 4X+1 register, bit 13 = 1 (see the description of Command 1 in this section).
1RWH To verify the version of the module, reference the indicated label found on the top front of the module.
The following figure shows the module’s label.
High Speed CTR 2CH
500KHz 02.00
Note: Modules labeled with
PV and SV designations are newer than 02.00 marked models
In modules prior to V02.00, when Rate Sample mode was selected, input was always handled as if it were generated by a pulse encoder. For example, 60 count per revolution encoders, either pulse or quadrature types, would give a rate of 60 for a one-second revolution when the interval was set for one second.
Users are cautioned that beginning with V2.00 modules, if a quadrature type encoder is used to provide count input and Pulse/Quadrature Input Counter 1 and
2, bits 9 or 10, are set to 1, the module will detect all edges. The result is four times the rate sample value as would be accumulated with an equivalent pulse encoder input. In the example in the above paragraph, the rate sample would be equal to
240.
Encoder type selection is set using Command 1, CONFIGURE (01XX), 4X+1 register, bits 9 or 10 (see the description of Command 1 in this section).
If the Encoder Type select bits are set to 0, either type of encoder will produce the
Rate Sample, as did versions of the module that were lower than V02.00.
312
840 USE 100 00 11/2004
Intelligent/Special Purpose
Wiring Diagram 1 The following figure shows the EHC20200 wiring diagram 1.
INPUT 1A+
. . . .
VREF
OV
INPUT 1A-
INPUT 1B-
2 1
4 3
INPUT 1B+
Pulse
PRESET 1C-
6 5
PRESET 1C+
+
8 7
OUTPUT RESET 10+
+
–
–
VREF
N/C
ENABLE 1-
10
12
9
11
N/C
ENABLE 1+
N/C
OUTPUT 1A
14
16
LO FILTER SEL 1
18
13
N/C
15
OUTPUT 1B
VREF1
17
N/C
INPUT 2A-
20
22
INPUT 2B-
24
PRESET 2C-
OUTPUT RESET 20-
26
28
19 N/C
21
INPUT 2A+
23
INPUT 2B+
25
PRESET 2C+
OUTPUT RESET 20+
27
N/C
ENABLE 2-
30
32
29
31
N/C
ENABLE 2+
N/C
OUTPUT 2A
34 33
36 35
LO FILTER SEL 2
38
OUTPUT SUPPLY
37
40 39
N/C
OUTPUT 2B
VREF2
RETURN
+ –
24 Vdc
1RWH
Notes on Wiring Diagram 1.
Single ended pulse input.
Constant enable.
Count up.
Outputs 1A and 1B operate relays.
Counter 2 not used.
N/C = Not Connected.
840 USE 100 00 11/2004
313
Intelligent/Special Purpose
Wiring Diagram 2 The following figure shows the EHC20200 wiring diagram 2.
INPUT 1A-
INPUT 1B-
2
4
PRESET 1C-
OUTPUT RESET 10-
6
8
INPUT
1
3
INPUT B1+ A+
A-
PRESET 1C+
5
7
OUTPUT RESET 10+
N/C
ENABLE 1-
10
12
9
11
N/C
ENABLE 1+
N/C
OUTPUT 1A
14
16
LO FILTER SEL 1
18
N/C
INPUT 2A-
20
22
INPUT 2B-
24
PRESET 2C-
26
OUTPUT RESET 20-
28
13
N/C
OUTPUT 1B
15
17
VREF1
19
N/C
INPUT 2A+
21
23
INPUT 2B+
25
PRESET 2C+
27
OUTPUT RESET 20+
N/C
ENABLE 2-
30
32
29
31
N/C
ENABLE 2+
N/C
OUTPUT 2A
34 33
36 35
LO FILTER SEL 2
38
OUTPUT SUPPLY
37
40 39
N/C
OUTPUT 2B
VREF2
RETURN
+ –
24 Vdc
1.8 V
MIN
A
A
Z
Z
–
+
+
VREF
–
1RWH Notes on Wiring Diagram 2
Differential pulse input.
Constant enable.
Zero pulse resets outputs 1A and 1B.
Count up.
Outputs a and B operate relays.
Counter 2 not used.
N/C = Not Connected.
314
840 USE 100 00 11/2004
Intelligent/Special Purpose
Wiring Diagram 3 The following figure shows the EHC20200 wiring diagram 3.
INPUT 1A-
2
INPUT 1B-
4
PRESET 1C-
6
OUTPUT RESET 10-
8
1
INPUT 1A+
INPUT 1B+
3
5
PRESET 1C+
7
OUTPUT RESET 10+
N/C
ENABLE 1-
10
12
9
11
N/C
ENABLE 1+
N/C
OUTPUT 1A
14
16
LO FILTER SEL 1
18
N/C 20
INPUT 2A-
22
INPUT 2B-
24
PRESET 2C-
26
OUTPUT RESET 20-
28
13
N/C
15
OUTPUT 1B
VREF1
17
19 N/C
21
INPUT 2A+
23
INPUT 2B+
25
PRESET 2C+
OUTPUT RESET 20+
27
N/C
ENABLE 2-
30
32
29
31
N/C
ENABLE 2+
N/C 34
OUTPUT 2A
36
33
35
LO FILTER SEL 2
OUTPUT SUPPLY
38 37
40 39
N/C
OUTPUT 2B
VREF2
RETURN
+ –
24 Vdc
A
B
+
–
+
VREF
–
1RWH
Notes on Wiring Diagram 3
Quadrature input.
Constant enable.
Outputs 1A and 1B operate relays.
Counter 2 not used
N/C = Not Connected.
840 USE 100 00 11/2004
315
Intelligent/Special Purpose
Wiring Diagram 4 The following figure shows the EHC20200 wiring diagram 4.
B
A
A
B
Z
Z
+
– INPUT 1A-
2
INPUT 1B-
4
PRESET 1C-
OUTPUT RESET 10-
6
8
1
INPUT 1A+
INPUT 1B+
3
5
7
PRESET 1C+
OUTPUT RESET 10+
N/C
ENABLE 1-
10
12
9
11
N/C
ENABLE 1+
N/C
OUTPUT 1A
14
16
LO FILTER SEL
18
N/C
INPUT 2A-
20
22
INPUT 2B-
24
PRESET 2C-
26
OUTPUT RESET 20-
28
13
15
N/C
OUTPUT 1B
VREF1
17
19
N/C
INPUT 2A+
21
23
INPUT 2B+
25
PRESET 2C+
27
OUTPUT RESET 20+
N/C
ENABLE 2-
30
32
29
31
N/C
ENABLE 2+
N/C
OUTPUT 2A
34 33
36 35
LO FILTER SEL 2
38
OUTPUT SUPPLY
37
40 39
N/C
OUTPUT 2B
VREF2
RETUR
+ –
24 Vdc
VREF
– z z z z z z
1RWH Notes on Diagram 4.
Differential quadrature input.
Constant enable.
Zero pulse reset Output 1A and 1B.
Output 1A and 1B operate relays.
Counter 2 not used.
N/C = Not Connected.
316
840 USE 100 00 11/2004
Module Zoom
Selections
Push <Enter> to display and select applicable parameters.
The following figure shows the module zoom selections.
Intelligent/Special Purpose
Counter X mode control: Incremental
Quadrature
Number of counters, output assertion:
Comm lost output assert override:
2x16 w/ Output
2x32 w/ Output
2x32 No Output
Rate Sample Mode
Off
On
Note: When OFF, outputs are disabled when communication with the bus is lost. When
ON, outputs continue to operate as configured.
Counter X output mode
Output Coil X mode:
Setpoint
Latched Setpoint
Terminal Count
Latched Terminal
Timed Setpoint
Timed Terminal
Note: Only one output should be configured as timed (Setpoint or
Terminal).
Number of counters, output assertion: 2x16 Assert Outp
2x32 Assert Outp
2x32 No Assert
Rate Sample Mode
The next lines apply ONLY IF the counter is in 2x16, Output Assert Mode:
Counter X Maximum Count:
Counter X Setpoint (alarm):
Time Output On:
* 0 DEC
* 0 DEC
0 DEC milliseconds (16383 maximum)
840 USE 100 00 11/2004
317
Intelligent/Special Purpose
*Refer to Load Values Command section for the maximum values that may be used by the module.
The next lines apply ONLY IF the counter is in 1x32, Output Assert Mode:
Counter 2 Maximum Count:
Counter 2 Setpoint (alarm):
Time Output On:
* 0 DEC
* 0 DEC
0 DEC milliseconds (16383 maximum)
*Refer to Load Values Command section for the maximum values that may be used by the module.
The following figure shows the number of counters in output assertion.
Number of counters, output assertion: 2x16 Assert Outp
2x32 Assert Outp
2x32 No Assert
Rate Sample Mode
The next lines apply ONLY IF the counter is in 2x32, No Output Assert Mode:
Words 2-3: Counter 1 Maximum Count:
Words 4-5: Counter 2 Maximum Count:
* 0 DEC
* 0 DEC
*Refer to Load Values Command section for the maximum values that may be used by the module.
The next line applies ONLY IF the counter is in Rate Sample Mode:
Rate Sample Timer X: 0 DEC milliseconds (65535 maximum)
1RWH Any 1XPEHURIFRXQWHUVRXWSXWDVVHUWLRQ selection pop-up menu can be used as they reflect each other.
318
840 USE 100 00 11/2004
Intelligent/Special Purpose
140EHC20200 High Speed Counter Module
Overview The EHC20200 offers the following features: z Two counters that operate in pulse or quadrature mode and accept single- ended or differential inputs.
z Two FET output switches for each counter — turned on when the counter reaches programmed setpoint or maximum values, and turned off by changes in counter values, software commands, or a hard wired reset from the field.
See
p. 294 for configuring and operating the EHC20200 with Modsoft.
EHC20200 High
Speed Counter
Module
The following figure shows the EHC20200 Two Channel High Speed Counter module.
LED Area
(+&
10 80 vdc out
X
Model Number
Module Description
Color Code
Field Wiring
Terminal Strip
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Customer Identification Label
(Fold label and place it inside the door)
Removable Door
10
12
14
16
18
6
8
2
4
24
26
28
30
32
34
36
38
40
1
15
17
19
21
7
9
3
5
11
13
23
25
27
29
31
33
35
37
39
840 USE 100 00 11/2004
319
Intelligent/Special Purpose
Specifications The following table shows the specifications for the EHC20200 High Speed Counter module.
Specifications
Number of Channels
LEDs
Count Frequency
Registers Required
2 with 2 outputs each
Active
F
8 Input Status LEDs (Green)
4 Output Status LEDs (Green)
500 kHz max with differential inputs. 250 kHz max with single-ended inputs.
6 Words In
6 Words Out
Data Formats
16 Bit Counter
32 Bit Counter
Discrete Inputs
Operation Modes
65,535 Decimal
2,147,483,647 Decimal
Incremental
Quadrature
Max Continuous Input Voltage 30 Vdc
Input Threshold
Single Ended Mode
VREF Supply
+ 5 Vdc
+ 12 Vdc
+ 24 Vdc
On State (Vdc)
0 ... 2.0
0 ... 5.0
0 ... 11.0
Off State (Vdc)
3.5 ... 5.0
7.0 ... 12.0
13.0 ... 24.0
Differential Mode (Minimum)
Input Resistance
Discrete Outputs
Output Levels (1A, 1B, 2A, 2B)
1.8 Vdc
10 k
FET Switch ON
FET Switch OFF
Supply - 0.4 Vdc
0 Vdc (ground reference)
Max Load Current (each output) 0.5 A
Output Off State Leakage 0.4 mA max @ 30 Vdc
Output On State Voltage Drop 0.4 Vdc @ 0.5 A
Output Protection 36 V transorb for transient voltage suppression
Miscellaneous
Isolation (Channel to Bus) 1780 Vac rms for 1 minute
320
840 USE 100 00 11/2004
Intelligent/Special Purpose
Specifications
Fault Detection
Power Dissipation
Bus Current Required
Blown fuse detect, loss of outputs 1A, 1B, 2A, 2B field power
4.0 W + 0.4 x total module load current
650 mA
External 24 Vdc Power Supply 19.2 ... 30 Vdc, 24 Vdc nominal, 50 mA required, plus the load current for each output
Fusing Internal: 2.5 A fuse, (Part # 043503948 or equivalent)
External: User discretion
Compatibility Programming Software: Modsoft V2.32 or Concept 2.0 at a minimum
Quantum Controllers: All, V2.0 at a minimum
Fuse Location The following figure shows the fuse location.
Fuse
Location
X
840 USE 100 00 11/2004
1RWH Turn off power to the module and remove the field wiring terminal strip to gain access to the fuse.
321
Intelligent/Special Purpose
LED Indicators and Descriptions
The following figure shows the LED indicators for the EHC20200 High Speed
Counter module.
Active
In 1
En 1
Pre C1
Res 01
Out 1A
Out 1B
F
In 2
En 2
Pre C2
Res 02
Out 2A
Out 2B
The following table shows the LED descriptions for the EHC20200 high speed counter.
In 2
En 2
Pre C2
Res 02
Out 1A
Out 1B
Out 2A
Out 2B
LED Descriptions
LEDs Color
Active
F
Green
Red
In 1
En 1
Pre C1
Res 01
Green
Green
Green
Green
Green
Green
Green
Green
Green
Green
Green
Green
Indication when On
Bus communication is present
Indicates internal fuse blown or loss of output power supply
Counter 1 input
Enable Counter 1 input
Preset Counter 1 input
Reset Output 1A, 1B
Counter 2 input
Enable Counter 2 input
Preset Counter 2 input
Reset Output 2A, 2B
Counter 1A output
Counter 1B output
Counter 2A output
Counter 2B output
322
840 USE 100 00 11/2004
Intelligent/Special Purpose
Controlling the
Module
Hardware inputs from the field can be used to: z Increment/decrement the input counters with serial pulses from encoders or other z z square wave sources.
Set direction of count.
Reset the outputs.
Hardware inputs from the field and software commands are used together to: z z z z z z z z z z Enable the count input.
z
Hardware inputs from the field or software commands can be used to:
Preset the input counter to zero or maximum count.
Software commands can be used to:
Configure the counters for pulse (tachometer) or quadrature mode.
Configure for 16 or 32 bit counters, with or without output assertion.
Configure the module to operate in either count or rate-sample mode.
Option for outputs to operate or not operate if backplane bus communication is z lost (i.e., a fault condition).
Option for outputs to switch on when setpoint and/or maximum values are reached.
Define the setpoint and maximum count values.
Define ON time for outputs.
Disable outputs.
Read the input counter totalizing or rate sample values.
Retrieve the old (previous) input counter value after the counter has been preset.
840 USE 100 00 11/2004
323
Intelligent/Special Purpose
Timing Diagrams and Parameters
This section includes timing diagrams and parameters for the 140EHC20200 counter modules. Timing diagrams and a timing parameter table for the
140EHC20200 counter module are shown below.
EHC20200 Timing Diagrams
Tpw 1
Count Input
Thold
Tst
Enable
Tpw 2 Tst
Preset
Tpw 1 Tst
Reset
Tdly2
Tdly1
Output Assertion
The following table shows the EHC20200 timing parameters.
Tdly1
Tdly2
Tpw1
Tpw2
Tst
Thold
Timing Parameters
Count to Output Assertion Delay (MAX)
Preset/Reset to Output Delay (MAX)
Limits
Filter
200 Hz
4.8 ms
4.8 ms
Count/Reset Pulse Width (MIN)
Preset Pulse Width (MIN)
2.5 ms
2.5 ms
Enable/Reset/Preset to Count Setup Time (MIN) 2.5 ms
Enable/Reset to Count Hold Time (MIN) 2.5 ms
No Filter
500 khz
40
μ s
40 μ s
1
μ s
500
μ s
2
μ s
2
μ s
Module
Functions
1RWH The timing parameter limits are measures at the module field terminal connector at the logic low threshold level.
The following functions apply to the EHC202 high speed counter module.
324
840 USE 100 00 11/2004
COUNT UP
COUNT DOWN
REMOVE
ENABLE
OUTPUTS
COUNTER
PRESET
Intelligent/Special Purpose
The input counter is reset to zero if the count direction input is UP and a preset
(hardware or software) or Load Value command is sent to the module.
When counting in the UP direction, the input counter increments to the maximum value, the next input pulse sets the counter to zero and it continues counting back up to the maximum value.
The input counter is set to maximum count if the count direction is down and a preset
(hardware or software) or Load Value command is sent to the module.
When counting in the DOWN direction, the input counter is decremented from the maximum value to zero. The next pulse resets the input counter to the Maximum value and the increment down starts again.
This function disables the input counter, causing it to stop incrementing and hold the count accumulated prior to disabling.
When configured in the count mode, outputs will turn on for defined times when setpoints or maximum values have been reached.
No output assertion in two 32 bit counter mode or rate sample.
Programmed ON time for outputs can be set for one channel, one output and one trigger point only.
In a running controller, latched outputs are turned off only by a hardware RESET input. If no reset is provided, the outputs latched on will turn off when the controller is stopped.
This is both a hardware and software function. In the event that both methods are used, the last one executed has precedence. An input counter will be automatically preset whenever a new maximum value or rate sample time is loaded.
COUNTER
ENABLE
RATE SAMPLE
VALUE
Both hardware and software enables are required for an input counter to operate.
An input counter will be automatically software enabled whenever a new maximum value is loaded or a preset (hardware or software) is sent to it.
The rate sample value is held and may be accessed during count operations. The value read is from the last configured and completed rate sample interval.
840 USE 100 00 11/2004
325
Intelligent/Special Purpose
QUADRATURE
MODE
Miscellaneous
Information
When the module is configured for quadrature mode operation, the counter requires encoder pulses on inputs A and B.
In quadrature mode, all input signal edges are counted. A 60 count/revolution encoder will produce a count of 240 for one shaft rotation.
Field wire to Counter 2 inputs and outputs, when configured for one 32 bit counter with output assertion. The unused Counter 1 must have its + (plus) inputs connected to VREF+.
Input counts and parameters are not maintained in the module at power down. The rewrite of parameters at power up must be done with either user logic or Modzoomtype preset panel selections.
The 200 Hz filter for each counter can be activated by strapping the Lo Filter Sel terminal to the Return terminal. This function provides noise immunity for low frequency applications and can also be used for relay debounce.
Operation
Rate Sample
Pulse Count
The following information describes the operation of various module functions.
z z z z
To rate sample, the module must be:
Configured for pulse or quadrature mode.
Configured for Rate Sample mode.
Loaded with the Rate Sample time value.
Enabled to count, using hardwired input and software control bits.
z z z z
To count pulses, the module must be:
Configured for pulse or quadrature mode.
Configured for counter display: two 16 bit, one 32 bit, or two 32 bit counters.
Loaded with the maximum count.
Enabled to count, using hardwired input and software control bits.
Pulse Count and
Turning Outputs
On/Off z z z z z
To count pulses and turn outputs on and off, the module must be:
Configured for pulse or quadrature mode.
Configured for two 16 bit or one 32 bit counter.
Configured to assert or not assert outputs at the programmed count values when the module loses communication with the bus (fault condition).
z Configured to specify if outputs turn on at a setpoint or maximum count, turn on at those points for a specific amount of time, or remain latched. If latched, outputs can only be reset by a hard wired input.
Loaded with setpoint values, maximum count values, and output assert time.
Enabled to count using hardwired input and software control bits.
326
840 USE 100 00 11/2004
Intelligent/Special Purpose
Counter Rollover
Examples for
Pulse Input
([DPSOH&RXQW8S
3XOVH,QSXW
,QSXW&RXQWHU
2XWSXW$
2XWSXW%
Count is from 0 -> 10 (Maximum Count)
Output A turns on at Setpoint = 5
Output B turns on after Input Count = Maximum (Terminal) Count = 10
([DPSOH&RXQW'RZQ
3XOVH,QSXW
,QSXW&RXQWHU
2XWSXW$
2XWSXW%
Count is from 10 (Maximum Count) -> 0
Output A turns on at Setpoint = 5
Output B turns on after Input Count = 0
1RWH Outputs are not latched.
840 USE 100 00 11/2004
327
Intelligent/Special Purpose
Counter Rollover
Examples for
Quadrature Input
([DPSOH&RXQW8S
,QSXW$
,QSXW%
,QSXW
&RXQWHU
2XWSXW$
2XWSXW%
Count is from 0 -> 10 (Maximum Count)
Output A turns on at Setpoint = 5. Output B turns on after Input Count = Maximum
(Terminal) Count = 10
([DPSOH&RXQW'RZQ
,QSXW$
,QSXW%
,QSXW
&RXQWHU
2XWSXW$
2XWSXW%
Count is from 10 (Maximum Count) -> 0
Output A turns on at Setpoint = 5
Output B turns on after Input Count = 0
1RWH Outputs are not latched.
328
840 USE 100 00 11/2004
Intelligent/Special Purpose
Wiring Diagram
Signal
Descriptions
The following table shows the wiring diagram for signal descriptions.
Parameter Description/Usage
INPUT A Single ended or differential count input or Phase A for quadrature mode.
INPUT B
Single ended (active low only) uses Input 1A+ and/or Input 2A+.
Input 1A- and/or Input 2A- are not connected. Differential input encoders use both plus (+) and minus (-) inputs.
Direction level for non-quadrature devices or Phase B for quadrature mode.
Direction inputs for non-quadrature input devices are:
Count Up = High Voltage Level
Count Down = Low Voltage Level
For single ended Input devices, only Input 1B+ and/or Input 2B+ are used. Input
1B- and 2B- are not connected. Differential input encoders use both plus (+) and minus (-) inputs.
PRESET C Presets count register(s). Low level causes preset.
OUTPUT
RESET 0
For single ended Preset inputs, only Preset 1C+ and/or Preset 2B+ are used.
Preset 1C- and 2C- are not connected. Differential input encoders use both plus
(+) and minus (-) inputs.
Low level resets Outputs 1A, 1B, 2A, and 2B to OFF if latched.
ENABLE
For single ended Reset inputs, only Reset 10+ and/or Reset 20+ are used.
Reset 10- and 20- are not connected. Differential input encoders use both plus
(+) and minus (-) inputs.
Low level enables counting.
VREF
For single ended Enable inputs, only Enable 1+ and/or Enable 2+ are used.
Enable 1- and 2- are not connected. Differential input encoders use both plus
(+) and minus (-) inputs.
Field input device power source connection. Also, connect any unused (+) inputs to the group VREF terminal or the one in use (30 Vdc max).
Group A = Terminal 17
Group B = Terminal 37
Group A and Group B VREF supplies can be different voltage levels.
LO FILTER
SEL
Enables the internal 200 Hz filter when connected to Return Terminal 39.
OUTPUT
POWER
SUPPLY
Internal FET switches connect the output supply wired to Terminal 40 to the
Output 1A, 1B, 2A, 2B terminals at output assert times.
External 24 Vdc power supply (+) connection. Required for the module interface and for Outputs 1A, 1B, 2A, and 2B.
RETURN External 24 Vdc power supply (-) connection. Required for the module interface and for Outputs 1A, 1B, 2A, and 2B.
840 USE 100 00 11/2004
329
Intelligent/Special Purpose
Wiring Diagram The following figure shows the 140EHC20200 wiring diagram.
INPUT 1A-
2
INPUT 1B-
4
PRESET 1C-
6
OUTPUT RESET 10-
8
......
1
INPUT 1A+
INPUT 1B+
3
PRESET 1C+
5
OUTPUT RESET 10+
7
N/C 10
ENABLE 1-
12
9
11
N/C
ENABLE 1+
N/C
14
OUTPUT 1A
16
LO FILTER SEL 1
18
N/C 20
INPUT 2A-
22
INPUT 2B-
24
PRESET 2C-
26
OUTPUT RESET 20-
28
13
N/C
15
OUTPUT 1B
VREF1
17
19 N/C
21
INPUT 2A+
INPUT 2B+
23
PRESET 2C+
25
OUTPUT RESET 20+
27
N/C
ENABLE 2-
30
32
29
31
N/C
ENABLE 2+
N/C 34
OUTPUT 2A
36
LO FILTER SEL 2
38
POWER SUPPLY
33
35
37
40 39
N/C
OUTPUT 2B
VREF2
RETURN
+ –
VREF
0V
24 Vdc
+
+
Pulse
–
–
VREF
330
840 USE 100 00 11/2004
840 USE 100 00 11/2004
Intelligent/Special Purpose
The preceding wiring diagram shows single ended connections for:.
Terminal 1
Terminal 3
Terminal 5
Terminal 7
Terminal 11
Pulse encoder input (sinking device)
Input 1B count UP direction
Unused hardwire Preset tied high
Output Reset tied high, not required; outputs not used
Hardware enabled (software enable also required using predefined
Modzoom or 4X register
Required Vref+ connection
Counter 2 not used. These terminals must be connected VREF+.
Terminal 17
Terminal 21
Terminal 23
Terminal 25
Terminal 27
Terminal 31
Terminal 37
Terminal 39
Terminal 40
Required Output Supply Return
Required Output Supply
See
p. 294 for both differential pulse encoder input and single ended or differential
quadrature encoder input wiring diagrams.
331
Intelligent/Special Purpose
140ESI06210 ASCII Interface Module
Overview
Related
Documentation
ASCII Interface
Module
The ASCII Interface Two Channel module is a Quantum communications interface z z z module used to:
Input messages and/or data from an ASCII device to the CPU.
Output messages and/or data from the CPU to an ASCII device.
Bi-directionally exchange messages and/or data between an ASCII device and the CPU.
For more detailed information on use of the ASCII interface module, refer to the
Quantum Automation Series 140ESI06210 ASCII Interface Module User Guide
(840 USE 108 00).
The following figure shows the ESI06210 ASCII interface module components.
LED Area
(6,
10 80 vdc
Model Number
Module Description
Color Code
Customer Identification Label
(Fold label and place it inside door)
Removable Door
RS-232
Port 1/Port 0
Reset Button
RS-232 Port 2
Reset
Port 2
RS232C
X
332
840 USE 100 00 11/2004
Specifications
Intelligent/Special Purpose
The following table shows the specifications for the ASCII interface two channel module.
Specifications
Data Interface
RS-232C 2 serial ports (9-pin D-shell), non-isolated
Cabling (Maximum cable length
20 m shielded)
990NAA26320, Modbus Programming Cable, RS-232, 12 ft. (2.7 m)
990NAA26350, Modbus Programming Cable, RS-232, 50 ft. (15.5 m)
Firmware Specifications
Port Performance
Depth of Nested Messages
Buffer Size
Number of Messages
Maximum Message Length
Burst Speed: 19.2 k baud each port. Continuous Speed:
Application dependent
8
255 Input. 255 Output
255
127 characters plus 1 checksum
Memory
RAM
Flash-ROM
Power Dissipation
Bus Current Required
Fusing
Internal
External
Required Addressing
256 kb for data and program + 2 kb dual port ram
128 kb for program and firmware
2 W max
300 mA
None
User discretion
12 Words In
12 Words Out
Compatibility
Programming Software
Data Formats Supported
Quantum Controllers
Battery Backup Module
Modsoft V2.4 or Concept 2.0 at a minimum
Text, Decimal, Fixed Point, Nested Write Message, Set
Register Pointer, Print Time/Date, Repeat, Space,
Newline, Control Code, Flush Buffer
All, Executive V2.0 at a minimum
140XCP90000
840 USE 100 00 11/2004
333
Intelligent/Special Purpose
LED Indicators and Descriptions
The following figure shows the ESI06210 LED indicators.
R
Rx1
Tx1
Active
Error 1
F
Rx2
Tx2
Error 2
Status
The following table shows the ESI06210 LED descriptions.
Rx1
Tx1
Rx2
Tx2
LEDs
R
Active
F
Status
Error 1
Error 2
Color
Green
Green
Red
Green
Green
Green
Green
Yellow
Red
Red
Indication when On
The module has passed powerup diagnostics
Bus communication is present
The module has detected a fault
Received data on RS-232C Port 1
Transmitted data on RS-232C Port 1
Received data on RS-232C Port 2
Transmitted data on RS-232C Port 2
Status
There is an error condition on Port 1
There is an error condition on Port 2
334
840 USE 100 00 11/2004
LED Blinking
Sequence
Status LED
Crash Codes
Intelligent/Special Purpose
The following table shows the blinking sequence of the F, Status, Error 1, and Error
2 LEDs.
LEDs and Blinking Sequence
F Status Error 1 Error 2 Description
F Status
OFF ON
Error 1
OFF
Error 2
OFF
Description
Programming mode
OFF
OFF
OFF
OFF
N/A Blinking
(See the next table)
ON
N/A
OFF
N/A
ON
OFF
Serial Port 1 incurred a buffer overrun
Serial Port 2 incurred a buffer overrun
The ASCII module is in kernal mode and may have an error
The following table shows a table of Status LED crash codes.
Code (in hex) Error
5
6
7
Number of Blinks
(one per second)
Steady
4
8
0000
6631
6503
6402
6300
6301
630A
630B
8000
8001
8002
8003
Requested kernal mode
Bad micro controller interrupt
RAM address test error
RAM data test error
PROM checksum error (EXEC not loaded)
PROM checksum error
Flash-message checksum error
Executive watchdog timeout error
Kernal other error
Kernal PROM checksum error
Flash program error
Unexpected executive return
840 USE 100 00 11/2004
335
Intelligent/Special Purpose
Front Panel
Connectors and
Switches
The ESI has two serial ports which it uses to communicate with serial devices. The following is the pinout connections for the ASCII module serial ports.
1
6
2
3
7 Connection
No Connection
8
4
9
5
RS-232C Serial
Ports
The following table shows the pin number and description for the RS-232C serial ports.
6
7
4
5
2
3
Pin Number
1
8
9
Shield
Signal Name
DCD
RXD
TXD
N/A
GND
N/A
RTS
N/A
N/A
N/A
Description
Carrier Detect
Receive Data
Transmit Data
Not Connected
Signal Ground
Not Connected
Request to Send
Not Connected
Not Connected
Chassis Ground
The serial port interface allows the user to configure the module and to program the
ASCII messages into the module. This is only activated when the module enters into its programming mode via the front panel push button.
1RWH The serial port is capable of communicating with either a dumb terminal or a
PC using terminal emulation software (i.e., PROCOMM).
336
840 USE 100 00 11/2004
Intelligent/Special Purpose
Serial Port Setup When programming mode is entered, one of the RS-232 serial ports is set to a standard terminal communication’s configuration to communicate with the user on the programming terminal via a Modbus. This communication configuration consists of the following.
Baud rate:
Data bits:
Stop bits:
Parity bit:
Keyboard Mode:
XON/XOFF:
9600
8
1
None (disabled)
ON (Character echo)
ON
The serial port configuration has been set this way so that the configuration of the port is a known configuration and may or may not be the same configuration that is used when the module is running.
Front Panel
Reset Push
Button
A recessed push button on the front of the module is used to reset the module.
5(6(7
840 USE 100 00 11/2004
337
Intelligent/Special Purpose
140HLI34000 High Speed Interrupt Module
Overview
Related
Documentation
The High Speed Latch and Interrupt 24 Vdc 16x1 Sink/Source Input module accepts
24 Vdc inputs and is for use with 24 Vdc sink/source input devices.
For more detailed information on the use of a Quantum High Speed Interrupt module, refer to the Quantum Automation Series 140HLI34000 High Speed
Interrupt I/O Module User Guide (840 USE 112 00).
High Speed
Interrupt Module
The following figure shows the components of the HLI34000 high speed interrupt module.
LED Area
X
Model Number
Module Description
Color Code
Field Wiring
Terminal Strip
Customer Identification Label
(Fold label and place it inside the door)
Part #31000207
Removable Door
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
8
10
12
14
16
18
2
4
6
24
26
28
30
32
34
36
38
40
1
3
11
13
15
5
7
9
17
19
21
23
25
27
29
31
33
35
37
39
338
840 USE 100 00 11/2004
Specifications
Intelligent/Special Purpose
The following table shows the specifications for the HLI34000 high speed interrupt module.
Specifications
Number of Input Points
LEDs
Required Addressing
Operating Voltages and Currents
16 isolated points
Active 1 ... 16 (Green) - Indicates point status
1 Word In
ON (voltage)
OFF (voltage)
15 ... 30 Vdc
-3 ... +5 Vdc
ON (current)
OFF (current)
Absolute Maximum Input
Continuous
2.0 ... 8.0 mA
0 ... 0.5 mA
30 Vdc
Response
OFF - ON
ON - OFF
Input Protection
Isolation
Point to Point
Point to Bus
Fault Detection
Bus Current Required
Power Dissipation
External Power
Fusing
Internal
External
30
μ
130 s (max)
μ
30 Vdc reverse polarity
500 Vac rms for 1 minute
1780 Vac rms for 1 minute
None
400 mA
2.0 W + 0.30 W x the number of points on
Not required for this module
None s (max)
User discretion
840 USE 100 00 11/2004
339
Intelligent/Special Purpose
LED Indicators and Descriptions
The following figure shows the LED indicators for the HLI34000 high speed interrupt module.
6
7
4
5
8
1
2
3
ACTIVE
12
13
14
15
16
9
10
11
The following table shows the LED descriptions for the HLI34000 high speed interrupt module
LED Descriptions
LEDs Color
Active
1 ... 16
Green
Green
Indication when On
Bus communication is present.
The indicated point or channel is turned on.
1RWH
Due to the speed of the module, LED indications do not represent the state of the input signal, when the input signal is a short duration pulse.
340
840 USE 100 00 11/2004
Intelligent/Special Purpose
Wiring Diagram The following figure shows the wiring diagram for the HLI 340 00 High Speed
Interrupt module.
+
24 Vdc
−
–
24 Vdc
+
INPUT 1(+)
2
INPUT 2(+)
4
INPUT 3(+)
6
INPUT 4(+)
8
1
INPUT 1(-)
INPUT 2(-)
3
INPUT 3(-)
5
INPUT 4(-)
7
Sourcing Field Device N/C
INPUT 5(+)
10
12
INPUT 6(+)
14
INPUT 7(+)
16
INPUT 8(+)
18
9
11
13
INPUT 6(-)
INPUT 7(-)
15
INPUT 8(-)
17
N/C
INPUT 5(-)
N/C
INPUT 9(+)
20
22
INPUT 10(+)
24
INPUT 11(+)
26
INPUT 12(+)
28
19 N/C
INPUT 9(-)
21
INPUT 10(-)
23
INPUT 11(-)
25
27
INPUT 12(-)
N/C
INPUT 13(+)
30
32
INPUT 14(+)
34
INPUT 15(+)
36
INPUT 16(+)
38
29
N/C
INPUT 13(-)
31
33
INPUT 14(-)
INPUT 15(-)
35
INPUT 16(-)
37
N/C 40 39 N/C
Sinking Field Device
840 USE 100 00 11/2004
1RWH
Either shielded or unshielded signal cables may be used (the user should consider using shielded wire in a noisy environment). Shielded types should have a shield tied to earth ground near the signal source end.
N / C = Not Connected
341
Intelligent/Special Purpose
140MSB/MSC10100 Quantum MSX Motion Modules
Overview
Related
Documentation
MSX Motion
Modules
The Quantum single axis motion (MSX) modules are incremental encoder
(140MSB10100) or resolver and encoder (140MSB/MSC10100) feedback-only modules contained in a single-width housing. It works with servo motors that use
Cyberline drives and other types of DC and brushless drives from other manufacturers.
For detailed information on the use of MSX motion modules, refer to the Quantum
Automation Series 140MSX10100 Single Axis Motion Module Reference Guide
(840 USE 105 00).
The following figure shows the components of the MSX motion modules.
LED Area
06%
10 80 vdc out
Model Number
Module Description
Color Code
Removable Door
Customer Identification Label
(Fold label and place it inside door)
Modbus
Connector
Servo Port
Connector
X
342
840 USE 100 00 11/2004
Operational
Specifications
Intelligent/Special Purpose
The following table shows the operational specifications for the servo.
Servo
Commutation Update Rate
Velocity Loop Update Rate
Velocity Loop Bandwidth
Velocity Range
Position Loop Update rate
Position Accuracy - Resolver
Position Repeatability - Resolver
Position Accuracy - Encoder
0.25 ms
0.5 ms
> 100 Hz
0 - 6000 rpm
1 ms
+/- 10 arc minutes typical, +/- 15 arc minutes max
+/- 5 arc minutes max
Encoder dependent, 0.5 arc minutes max
The following table shows the operations specifications for communication.
Communication
Protocol
Address (set by software)
Required Addressing
Baud Rate (set by software)
Modbus
1 default
6 Words In, 6 Words Out
300 - 19200 baud, 9600 default
The following table shows the operational specifications for the application program.
Application Program
Execution Rate
Storage
See note below
650 instructions
1RWH A majority of the instructions typically take 1 ms to execute. The execution time of an instruction, though, is not constant. The execution time can increase due to factors such as: if the Sync Ratio Mode is on, how often the position generator must execute to plan out new moves, how many "whenever"s are enabled, and the number of sources requesting commands to be executed (e.g., backplane, internal program, Modbus port), etc. If timing is extremely critical to an application, actual time must be determined experimentally by running the actual application program.
840 USE 100 00 11/2004
343
Intelligent/Special Purpose
The following table shows the operational specifications for high speed input.
High Speed Input
Position Capture Time
Isolation
Pulse Width
Minimum Time Between Successive Captures
250
μ s max
500 V to system bus
25
μ s
20 ms
The following table shows the operational specifications for discrete inputs.
Discrete Inputs
Number
Scan Time
Isolation
7
1.5 ms
500 V to system bus
The following table shows the operational specifications for discrete outputs.
Discrete Outputs
Number
Update Time
Isolation
Reset State
On State
Output Type
Protection
Fault
3
10 ms max
500 V to system bus
0 V, nominal
24 V, nominal
Totem pole (sink/source)
Short circuit, overvoltage
Overcurrent detected
The following table shows the operational specifications for analog input.
Analog Input
Number
Scan Time
Data
Range
Accuracy
1
15 ms
User configurable
+/- 10 V
+/- 100 mV, plus offset
344
840 USE 100 00 11/2004
840 USE 100 00 11/2004
Intelligent/Special Purpose
The following table shows the operational specifications for analog output.
Analog Output
Number
Scan Time
Data
Range
Accuracy
1
20 ms
User configurable
+/- 10 V
+/- 50 mV, plus offset
The following table shows the operational specifications for the resolver feedback
(fully configured version).
Resolver Feedback (Fully Configured Version)
Conversion Method Tracking
Resolver Style
Excitation Frequency
Transmit
5 kHz
Excitation Amplitude
Excitation Current
Loss of Feedback
Automatically adjusted
120 mA
Detected within 40 ms
The following table shows the operational specifications for the incremental encoder feedback.
Incremental Encoder Feedback
Resolution 4 times line count
Signals
Signal Frequency
A, B, Mark
200 kHz, up to 500 kHz with reduced noise immunity
Encoder Output style
Loss of Feedback
Differential, 5 V
Detected within 40 ms
The following table shows the operational specifications for compatibility.
Compatibility
Programming Software
Quantum Controllers
Modsoft V2.32 or Concept 2.0 at a minimum
All, V2.0 at a minimum
345
Intelligent/Special Purpose
Electrical
Specifications
The following table shows the electrical specifications for discrete inputs and high speed input.
Discrete Inputs and High Speed Input
Input Impedance
Inputs On
3.5 k
Ω
15 Vdc min
Inputs Off
Isolation
5 Vdc max
500 Vac to system bus
The following table shows the electrical specifications for discrete output.
Discrete Output
Drive Capability
Protection
Isolation
150 mA at user supplied. 19.2 ... 30 Vdc resistive
Current limit, thermal
500 Vac to system bus
The following table shows the electrical specifications for analog input.
Analog Input
Resolution
Input Impedance
Offset
Accuracy
10 bits
30 k
Ω
+/- 50 mV
+/- 100 mV, plus offset
The following table shows the electrical specifications for analog output.
Analog Output
Resolution
Drive Capability
Offset
Accuracy
12 bits
3 mA
+/- 50 mV
+/- 50 mV, plus offset
The following table shows the electrical specifications for the resolver interface.
Resolver Interface
Reference 5 +/- 0.05 kHz, 1.6 ... 5.5 V rms. 50 mA drive capability
Sine / Cosine Input Impedance 3 k
Ω
Resolution 16 bits to 300 rpm. 14 bits to 1350 rpm. 12 bits to 6000 rpm
Accuracy 10 arc minutes, typical, resolver dependent
346
840 USE 100 00 11/2004
840 USE 100 00 11/2004
Intelligent/Special Purpose
The following table shows the electrical specifications for the motor temperature input.
Motor Temperature Input
Normal State
Fault State
Isolation
Short circuit, 2 mA sink max
Open circuit
500 Vac to system bus
The following table shows the electrical specifications for the encoder feedback interface.
Encoder Feedback Interface
Input Range
Input Impedance
Differential Signals, High
Differential Signals, Low
-0.7 ... 7 Vdc
145
Ω
, nominal
+2 V differential, min
-2 V differential, min
Maximum Encoder Frequency 200 kHz square wave (55% ... 45% with less than 15 degrees of quadrature error)
Isolation 500 Vac to system bus with external power supply
Minimum Encoder Pulse Width 1 ms
The following table shows the electrical specifications for the drive interface.
Drive Interface
Drive Fault Input
Drive Enable Relay
Current Command Voltages
Current Command Summing Accuracy
Current Commands
True high, TTL compatible relative to remote common, 10 K internal pull-up resistor
Form C contacts. 120 Vac @ 0.1 A resistive. 30
Vdc @ 0.5 A resistive
+/- 10 Vdc
0 +/- 0.1 Vdc
3 mA drive capability
The following table shows the electrical specifications for power requirements.
Power Requirements
Main Power Input
Main Power Input
Hot Swap Surge Current
Bus Current Required
5 V +/- 5% @ 750 mA
(with no encoders or resolvers attached, output off)
5 V +/- 5% @ 1000 mA
(with maximum encoder and resolver load, outputs on)
Less than 5 A
MSB Module: 700 mA. MSC Module: 1000 mA
347
Intelligent/Special Purpose
Front Panel
Indicators and
Descriptions
There are 17 LED indicators visible on the front panel. The following figure shows the front panel LED indicators.
Active
Ready
+ Lim ok
- Lim ok
Home
In 4
In 5
In 6
In 7
Drv Flt
Drv En
Out 1
Out 2
Out 3
Modbus
Moving
In Pos
Front Panel
Connectors
The following table shows the 140MSX10100 LED descriptions.
In 6
In 7
Drv Flt
Drv En
Out 1
Out 2
Out 3
Modbus
Moving
In Pos
LEDs
Active
Ready
+ Lim ok
- Lim ok
Home
In 4
In 5
Green
Green
Red
Green
Green
Green
Green
Green
Amber
Amber
Color
Green
Green
Green
Green
Green
Green
Green
Indication when On
Bus communication is present.
The module has passed powerup diagnostics.
Digital Input 1 active.
Digital Input 2 active.
Digital Input 3 active.
Digital Input 4 active.
Digital Input 5 active.
Digital Input 6 active.
Digital Input 7 active.
Fault signal from drive.
Drive enabled.
Digital Output 1 active.
Digital Output 2 active.
Digital Output 3 active.
Communications are active on the Modbus port.
Motor is moving.
Motion is within the in position of the final target.
There are two connectors located on the front of the module: the Modbus Connector and the Servo Connector.
348
840 USE 100 00 11/2004
Modbus
Connectors
Intelligent/Special Purpose
The MSX modules are equipped with a 9-pin, RS-232C connector that supports
Modicon’s proprietary Modbus communication protocol. The following is the Modbus port pinout connections for 9-pin and 25-pin connections.
The following figure shows the MSX Modbus port pinouts to 9-pin connectors (AS-
W956-xxx).
0V[0RGEXV3RUW3LQRXWVWR3LQ&RQQHFWRUV$6:[[[
Signal
TXD
RXD
GND
DTR
DSR
RTS
CTS
MSx
Pin
7
8
5
6
3
4
1
2
No Connection
Computer
Pin Signal Function
7
8
6
4
2
5
1
3 RXD
TXD
GND
DSR
DTR
RTS
CTS
Shield
Serial data
Serial data
Ground
Control line
Control line
Control line
Control line
The following figure shows the MSX Modbus port pinouts for 25-pin connectors (AS-
W955-xxx).
0V[0RGEXV3RUW3LQRXWVIRU3LQ&RQQHFWRUV$6:[[[
Signal
TXD
RXD
GND
DTR
DSR
RTS
CTS
MSx
Pin
6
7
4
5
8
1
2
3
No Connection
Computer
Pin Signal Function
7
6
20
4
5
1
2
3
RXD
TXD
GND
DSR
DTR
RTS
CTS
Shield
Serial data
Serial data
Ground
Control line
Control line
Control line
Control line
Servo Connector The MSX is also equipped with a 50-pin servo connector for communication with feedback devices.
1RWH
The tables below show the 50-pin servo connector signals. Pin numbers correspond to both the MSB and MSC modules. When the signals differ from each other, they are shown separated by a slash (i.e., Pin Number 34, MSB/MSC).
840 USE 100 00 11/2004
349
Intelligent/Special Purpose
The following figure shows the server connector signals (from left to right) 50 - 34. Server
Connector
Signals
50 49 48 47 46 45 44 43 42 41 40 39 38 37 36 35 34
The following figure shows the server connector signals (from left to right) 33 - 18.
33 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18
The following figure shows the server connector signals (from left to right) 17 - 1.
17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
350
840 USE 100 00 11/2004
Rear Panel
Switches
Intelligent/Special Purpose
The MSX has an RS-232 serial port to connect the module to an IBM PC (or compatible) running the Modicon Motion Development Software (MMDS). A twoposition Dip switch is located on the rear panel of the module (see the following illustration). SW1 is used to specify the module’s operating mode (984 or MMDS control). SW2 is used to specify the communication characteristics of the Modbus port upon power-up.
The following figure shows the two-position Dip switch.
CLOSED OPEN
The following table shows the settings for the Dip switch settings.
Switch
SW1
SW2
Setting
*Closed
Open
Closed
*Open
Function
MMDS control
PLC control
Programmed baud
Modbus default
*Factory setting
1RWH SW1 and SW2 are open when they are switched away from the internal PCB of the module.
840 USE 100 00 11/2004
351
Intelligent/Special Purpose
140XBE10000 Backplane Expander and Cable
Backplane
Expander
Backplane
Expander
Illustration
With the 140XBE10000 Backplane Expander you can add a second backplane to a local or remote drop. A custom communications cable, 3.0 meters maximum, provides the data communication transfer.
The following figure shows the components of the backplane expander.
140
XBE 100 00
XBP EXPANDER
Model Number
Module Description
Color Code
Removable Door
Connector
X
352
840 USE 100 00 11/2004
Specifications
Intelligent/Special Purpose
Specifications for the 140XBE10000 Backplane Expander are below.
Specifications
Number of Connected
Backplanes
Maximum Distance
Backplane Requirements
Size
Slots used
Number of Backplane Expander modules allowed
LEDs
Required Addressing
2
3 meters
All backplane sizes – 3, 4, 6, 10 and 16 slot.
1
1 per backplane
None.
The Backplane Expander will look like an unfilled slot in the PLC I/O map.
Power Requirements
Power Consumption
Bus Current Required
Connector
Compatibility
Primary Backplane
Secondary Backplane
2.5 watts
500 mA
37 pin D-type
Programming Software
Executive Firmware
No restrictions
All types of Quantum I/O modules can be used in the secondary backplane, unless otherwise noted in the I/O documentation.
Modsoft V 2.6 or Concept V 2.2 at a minimum
140CPUX130X - Version 2.2
140CPUX341X - Version 1.03
140CPUx341xA - Any version
140CPU42402 - Version 2.15
140CRA93X0X - Version 1.2
Words per Drop The following tables shows Words per drop.
Maximum words per drop
Local I/O
Remote I/O
64 in /64 out
64 in /64 out
840 USE 100 00 11/2004
353
Intelligent/Special Purpose
Cable
Specifications
Specifications for the the three possible Expander Cables are below.
Part Number
140 XCA 71703
140 XCA 71706
140 XCA 71709
Length
1 meter
2 meters
3 meters
Basic
Configuration
The backplane containing the the CPU or RIO drop adapter is designated the
‘Primary’ backplane and the adjacent backplane is designated the ‘Secondary’ backplane. Each backplane requires its own power supply.
Power
Supply CPU or RIO
Adapter
Backplane Expander
140 XBE 100 00
Cable end marked ³3ULPDU\´
Power
Supply
3ULPDU\%DFNSODQH
Backplane Expander Cable
140XCA7170X
Backplane Expander
140XBE10000
354
6HFRQGDU\%DFNSODQH
1RWH Cable must be installed before powering up the backplanes.
&$87,21
3RVVLEOHFRPPXQLFDWLRQVFDEOHIDLOXUH
Do not Hot Swap a Backplane Expander module into a powered backplane unless the communications cable has first been connected to the module.
)DLOXUHWRIROORZWKLVSUHFDXWLRQFDQUHVXOWLQLQMXU\RUHTXLSPHQWGDPDJH
840 USE 100 00 11/2004
840 USE 100 00 11/2004
Intelligent/Special Purpose
&$87,21
3RVVLEOHFRPPXQLFDWLRQVIDLOXUH
The cable is polarized. Ensure that the cable end marked "Primary" is connected to the backplane that has the CPU or RIO adapter.
)DLOXUHWRIROORZWKLVSUHFDXWLRQFDQUHVXOWLQLQMXU\RUHTXLSPHQWGDPDJH
:$51,1*
+RW6ZDSSLQJ5HVWULFWLRQ
Modules may be hot swapped when the area is known to be non-hazardous. Do not hot swap modules in a Class 1, Division 2 environment.
)DLOXUHWRIROORZWKLVSUHFDXWLRQFDQUHVXOWLQGHDWKVHULRXVLQMXU\RU
HTXLSPHQWGDPDJH
&$87,21
8VHU'HILQHG2XWSXWV
If the primary backplane power supply goes OFF and the secondary backplane power supply remains ON the behavior of the outputs on the secondary backplane is not guaranteed. Outputs could either go to off state or take their Time out state as defined by the user. If the power supply of the secondary backplane goes OFF and the primary backplane power supply remains ON , the IO Health bit of the modules located in this backplane could indicate a healthy module. It is recommended that all modules in the secondary backplanes, regardless of configuration, have their Time out state configured as USER DEFINED with
VALUE 0. Additionally using the same primary power source for primary and secondary backplanes could reduce the effect of this issue.
)DLOXUHWRIROORZWKLVSUHFDXWLRQFDQUHVXOWLQLQMXU\RUHTXLSPHQWGDPDJH
355
Intelligent/Special Purpose
Backplane
Expander
Guidelines z z z z z z z z z z z
The same 140XBE10000 Backplane Expander modules are used for the primary and secondary backplanes. The end of the Backplane Expander cable marked
"Primary" always connects to the Backplane Expander module in the Primary
Backplane.
The system can use any Quantum type power supply. Each backplane can have a different type of power supply.
Loss of power in the secondary backplane will not shut down the entire drop. Only modules located in the Secondary backplane will lose power.
Backplane expander modules can be located in any slot in the backplane and do not have to be placed in corresponding slots in the primary and secondary backplanes.
I/O modules that have downloadable executive firmware, such as the ESI module, are allowed in the secondary backplane except when downloading their execs. Executive firmware cannot be downloaded to modules in the secondary backplane.
It may be necessary to update the CPU or RIO drop executive firmware. See
Executive Firmware section in the Specifications table.
The Backplane Expander will not be recognized by the programming panel software. It will look like an unfilled slot in the PLC I/O map.
The Backplane Expander will allow configuration or I/O mapping of additional modules in the local drop containing a CPU or RIO drop adapter up to the drop word limit or physical slot address limitation.
Option modules, such as NOMs, NOEs and CHSs must reside in the primary backplane.
Any Interrupt module can be located in the secondary backplane, but the interrupt mode is not supported.
The Backplane Expander module cannot be Hot Swapped into a powered backplane without first attaching the communications cable. To install the
Backplane Expander in a powered backplane, first connect the cable to the
Backplane Expander module, then mount the module into the powered backplane.
356
840 USE 100 00 11/2004
Intelligent/Special Purpose
140CHS11000 Hot Standby Module
Overview
Related
Documentation
Hot Standby
Module
This section describes the Hot Standby Module 140CHS11000. The Quantum Hot
Standby system is designed for use with remote I/O networks when downtime cannot be tolerated.
For more detailed information on the use of the Hot Standby module, refer to the
Quantum Automation Hot Standby System Planning and Installation Guide
(840 USE 106 00).
The following figure shows the Hot Standby Module components.
LED Display
&+6
C
ONTROLLER
Model Number
Module Description
Color Code
Removable door
Customer Identification
Label (Fold label and place it inside door)
Part #31000264
Keyswitch
A/B Designation Slide Switch
Program Update Button
Transmit Cable Connector
Receive Cable Connector
X
840 USE 100 00 11/2004
357
Intelligent/Special Purpose
Specifications The following table shows the specifications for the Quantum Hot Standby system.
Specifications
I/O Type Quantum
Fiber Optic Communication Ports 2 (Transmit and Receive)
Compatibility
Programming Software
Quantum Controllers
Bus Current Required (Typical)
Modsoft V2.32 or Concept 2.0 at a minimum
All, V2.0 at a minimum. (Check the version label of the top front of the module for the proper revision level.)
700 mA
LED Indicators and Descriptions
The following figure shows the LED indicators.
Ready
Com Err
Com Act
Primary
Standby
The following table shows the LED descriptions.
LEDs
Ready
Color Indication when On
Green If steady: Power is being supplied to the module and it has passed initial internal diagnostic tests. If blinking: Module is trying to recover from an interface error.
Com Act Green If steady: CHS 110 modules are communicating. If blinking: An error has been detected.
Primary Green Module is supporting primary controller.
Com Err Red Module is retrying communications or communications failure has been detected.
Standby Amber If steady: Module is supporting the standby controller, which is ready to assume the primary role if needed. If blinking: Program update is in progress.
358
840 USE 100 00 11/2004
Error Codes
Front Panel
Controls
Intelligent/Special Purpose
The following table shows the number of times the Com Act LED blinks for each type of error and the codes possible for that group (all codes are in hex).
4
7
8
5
6
Number of Blinks
1
2
6503
6402
6301
C101
C102
C103
C200
Code
6900
6801
6802
6803
6804
6604
6605
Error error in additional transfer calculation
ICB frame pattern error head control block error bad diagnostic request greater than 128 MSL user loadables powerdown interrupt error
UART initialization error
RAM address test error
RAM data test error
PROM checksum error no hook timeout read state RAM timeout write state RAM timeout powerup error
The Hot Standby module has three controls on the front panel: a function keyswitch, a designation slide switch, and an update button.
840 USE 100 00 11/2004
359
Intelligent/Special Purpose
Keyswitch and
Program Update
Button
The following figure shows the keyswitch and program update button.
Off line
Xfer
Run z z
The keyswitch has three positions: off line, xfer, and run:
Off line – Putting the key in this position takes the controller out of service.
Xfer – When the key on the standby unit is in this position, the standby is prepared to receive a full program update from the primary controller. The update is initiated by pressing the program update button, which is located on the front panel between the function keyswitch and the cable connectors. If you turn the z key on the primary unit to xfer, the system will ignore your action.
Run – The switch should be in this position except when initiating a full program update or taking the module off line.
A/B Designation
Slide Switch
The slide switch is used to designate the controller as A or B. The slide switch on one Hot Standby module in every pair must be set to A; the switch on the other must be set to B. The controller designated A will begin as the primary controller as long as it reaches the ready state before or at the same time as controller B. If the switches are set to the same position, the system will refuse to recognize the second controller at startup.The following figure shows the A/B designation slide switch.
A
B
360
840 USE 100 00 11/2004
Quantum Intrinsically Safe
Analog/Digital, Input/Output
Modules
15
At a Glance
Introduction
What’s in this
Chapter?
This chapter provides information on the Intrinsically Safe Analog Input/Output, and
Digital Input/Output Modules.
This chapter contains the following sections:
Section
15.1
15.2
15.3
Topic
Intrinsically Safe Modules - General Information
Intrinsically Safe Analog Modules
Intrinsically Safe Discrete Modules
Page
361
840 USE 100 00 11/2004
Intrinsically Safe Modules
15.1
Intrinsically Safe Modules - General Information
Intrinsically Safe Modules – General Description
Introduction
Intrinsic Safety
The following information is specifically concerned with the application of intrinsic safety with regards to the installation and field wiring of the Quantum Intrinsically
Safe series of modules. It provides a general description of intrinsic safety and how it is accomplished in Quantum modules, how they should be installed, precautions that should be observed, and wiring and grounding practices that must be followed.
Intrinsic safety is a technique for ensuring that electrical energy supplied to circuits in a hazardous area is too low to ignite volatile gases either by spark or thermal means. Intrinsically safe circuits use energy limiting devices known as intrinsically safe barriers to prevent excess electrical energy from being applied to electrical equipment located in the hazardous area.
Module Location The Quantum Intrinsically Safe family of modules are entity certified to be installed in safe areas to monitor/control intrinsically safe apparatus located In hazardous areas.
Intrinsically Safe
Barriers
All Quantum Intrinsically Safe modules use galvanic isolation to provide the intrinsically safe barrier between them and the field devices located in hazardous areas. Opto-isolators are located within the modules between the field side and the
Quantum backplane bus circuitry. The maximum agency specified intrinsically safe parameters are:
V oc
≤ 28 Vdc and I sc
≤ 100mA
Intrinsically Safe
Power Supply
DC/DC converters in Quantum Intrinsically Safe modules provide intrinsically safe power to field devices located in hazardous areas. No external field power is required where these modules are installed.
Installation of
Quantum
Intrinsically Safe
Modules
Quantum Intrinsically Safe modules are designed to fit into a standard
140XBPOXX00 Quantum backplane. The modules can be installed in any slot position in the backplane. (The first slot is normally reserved for the power supply module.)
362
840 USE 100 00 11/2004
Hot Swapping
Intrinsically Safe Modules
Hot swapping Quantum Intrinsically Safe modules is not allowed per intrinsic safety standards.
:$51,1*
+RW6ZDS
Do not attempt to hot swap a Quantum Intrinsically Safe module.
)DLOXUHWRIROORZWKLVSUHFDXWLRQFDQUHVXOWLQGHDWKVHULRXVLQMXU\RU
HTXLSPHQWGDPDJH
Safe Area Wiring
Practices
Intrinsically safe wiring between Quantum Intrinsically Safe modules and the field z z devices located in the hazardous area must be separated from all other wiring. This can be accomplished by the following methods:
Separate blue wire ducts, raceways or conduits
Grounded metal or insulated partitions between the intrinsically safe and non- z intrinsically safe wiring
a separation of two inches (50 mm) of air space between the intrinsically safe and non-intrinsically safe wiring. With this method, the intrinsically safe and nonintrinsically safe wires must be tied down in separate bundles to maintain the required separation.
Identification and Labeling
Intrinsically safe wiring must be properly identified and labeled. Light blue color coding should be used for all intrinsically safe wiring. The terminal strip wiring connector on all Quantum Intrinsically Safe modules is colored blue to distinguish it from all non-intrinsically safe modules.
All wire ducts, raceways, cable trays, and open wiring must be labeled "Intrinsically
Safe Wiring" with a maximum spacing of 25 ft. between labels.
Wiring Type and
Grounding
Shielded twisted pair wires shall be used for each of the input or output pairs connected to the Quantum Intrinsically Safe module blue terminal strip. The wire gauge size can be between AWG 20 and AWG 12. Each twisted pair wire shield must be connected to the ground screws on the backplane, at the module end, and left open at the field device connection end in the hazardous area. The instruction sheet packaged with each Quantum Intrinsically Safe module contains a wiring diagram applicable to that type of module.
840 USE 100 00 11/2004
363
Intrinsically Safe Modules
Module Figure The following diagram is a view of a typical input or output module.
LED Area
[[[[[[[
X
Model Number
Module Description
Color Code
Field Wiring
Terminal Strip
Part# 140XTS33200
Customer Identification Label
(Fold label and place it inside the door)
Removable Door
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
24
26
28
30
32
34
36
38
40
2
4
6
8
10
12
14
16
18
13
15
17
7
9
11
1
3
5
31
33
35
37
39
19
21
23
25
27
29
Agency
Approvals z z z z
CENELEC Zone 1, Gas Group IIC, IIB, and IIA
CSA Class 1, Div 1, Gas groups A, B, C, and D
FM Class 1, Div 1, Gas groups A, B, C, and D
UL Class 1, Div 1, Gas groups A, B, C and D
364
840 USE 100 00 11/2004
Intrinsically Safe Modules
Intrinsically Safe
Wiring Diagram
The following diagram illustrates a Quantum Intrinsically Safe module using a separate raceway to isolate its external wiring to the hazardous area. This is just one of the possible ways of field wiring the module. Other methods would include bundling and laying the intrinsically safe wires in the same wiring trough with the bundled non-intrinsically safe wires, with each bundle tied down and separated by minimum of two inches of air space through out the wiring runs.
5
'
2
8
6
=
$
+
$
(
$
$
5
)
(
6
$
STANDARD I/O
WIRING
PS C
P
U
BACKPLANE
STD
I/O
M
O
D
U
L
E
STD
I/O
M
O
D
U
STD
I/O
M
O
D
U
L
E
L
E
8
/
(
,6
0
2
'
,QWULQVLFDOO\6DIH
INTRINSICALLY
SAFE WIRING
IN SEPARATE
BLUE RACEWAY
SAFE
WIRING
(
$
$
5
INTRINSICALLY
SAFE WIRING
LABELS
SAFE
WIRING
Questions
Regarding
Intrinsically Safe
Wiring Practices
The information concerning intrinsic safety wiring practices, is general in nature and is not intended to cover installation requirements for any specific site. Questions regarding intrinsic safety wiring requirements for your site should be referred to the approval agencies listed.
840 USE 100 00 11/2004
365
Intrinsically Safe Modules
15.2
Intrinsically Safe Analog Modules
At a Glance
Overview
What’s in this
Section?
This section provides information on the intrinsically safe analog modules,
140AII33000, 140AII33010, and 140AIO33000.
This section contains the following topics:
Topic
I/O Configuration for Intrinsically Safe Analog Modules
140AII33000 Intrinsically Safe Analog Input Module
140AII33010 Intrinsically Safe Current Input Module
140AIO33000 Intrinsically Safe Analog Output Module
Page
366
840 USE 100 00 11/2004
Intrinsically Safe Modules
I/O Configuration for Intrinsically Safe Analog Modules
Overview
140AII33000
This section provides information on the I/O configuration of the intrinsically safe analog modules, 140AII33000, 140AII33010, and 140AIO33000.
The following information pertains to configuration of the 140AII33000 intrinsically safe analog input module.
I/O Map register
Assignment
Register assignments depend on module configuration. This module may be configured as an RTD/Resistance or a Thermocouple input module.
840 USE 100 00 11/2004
367
Intrinsically Safe Modules
RTD I/O Map
Register
Assignments
When the 140AII33000 is configured as a RTD/Resistance input module, it requires nine contiguous input (3x) registers assigned as follows.
Register 1 Channel 1 data
Register 2 Channel 2 data
Register 3 Channel 3 data
Register 4 Channel 4 data
Register 5 Channel 5 data
Register 6 Channel 6 data
Register 7 Channel 7 data
Register 8 Channel 8 data
Register 9 Input Status Word
1 = Broken Wire or out of range on channel 8
1 = Broken Wire or out of range on channel 7
1 = Broken Wire or out of range on channel 6
1 = Broken Wire or out of range on channel 5
1 = Broken Wire or out of range on channel 4
1 = Broken Wire or out of range on channel 3
1 = Broken Wire or out of range on channel 2
1 = Broken Wire or out of range on channel 1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 = Range warning on Channel 8
1 = Range warning on Channel 7
1 = Range warning on Channel 6
1 = Range warning on Channel 5
1 = Range warning on Channel 4
1 = Range warning on Channel 3
1 = Range warning on Channel 2
1 = Range warning on Channel 1
368
840 USE 100 00 11/2004
Thermocouple/
Millivolt Map
Register
Assignments
Intrinsically Safe Modules
When the 140AII33000 is configured as a Thermocouple/Millivolt input module, it requires ten contiguous input (3x) registers assigned as follows.
Register 1 Channel 1 data
Register 2 Channel 2 data
Register 3 Channel 3 data
Register 4 Channel 4 data
Register 5 Channel 5 data
Register 6 Channel 6 data
Register 7 Channel 7 data
Register 8 Channel 8 data
Register 9 Input Status Word
1 = Broken Wire or out of range on channel 8
1 = Broken Wire or out of range on channel 7
1 = Broken Wire or out of range on channel 6
1 = Broken Wire or out of range on channel 5
1 = Broken Wire or out of range on channel 4
1 = Broken Wire or out of range on channel 3
1 = Broken Wire or out of range on channel 2
1 = Broken Wire or out of range on channel 1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 = Range warning on Channel 8
1 = Range warning on Channel 7
1 = Range warning on Channel 6
1 = Range warning on Channel 5
1 = Range warning on Channel 4
1 = Range warning on Channel 3
1 = Range warning on Channel 2
1 = Range warning on Channel 1
Register 10 Remote Junction Temperature
840 USE 100 00 11/2004
369
Intrinsically Safe Modules
I/O Map Status
Byte
The I/O map status byte is used by the 140AII33000 module as follows.
MSB
8 7 6 5 4 3 2
LSB
1
Channel 1 out of range or short circuit
Channel 2 out of range or short circuit
Channel 3 out of range or short circuit
Channel 4 out of range or short circuit
Channel 5 out of range or short circuit
Channel 6 out of range or short circuit
Channel 7 out of range or short circuit
Channel 8 out of range or short circuit
Modsoft Module
Zoom Selections
Use Modsoft’s Zoom feature to select the module input type and then configure the eight channels appropriate to the input type selected.
RTD/Resistance
TC/mV
)RU57'5HVLVWDQFH,QSXW )RU7&P9,QSXW
1.0 Deg 1.0 Deg
Resolution (Temp): Resolution (Temp):
0.1 Deg 0.1 Deg
Output Unit (Temp):
Celsius
Fahrenheit
Value Type:
Temperature
Raw Value
Output Unit (Temp):
Celsius
Fahrenheit
Cold Junction Compensator:
On Board
Channel 1
370
840 USE 100 00 11/2004
140AII33010
Intrinsically Safe Modules
Configure each channel (1 through 8) appropriate to the module input type selected.
)RU57'0RGXOH,QSXW
Channel Enable/Disable:
4-Wire /3-Wire /2-Wire:
Enable
Disable
4 Wire
3 Wire
2 Wire
RTD Type (Pt, Ni,
R, A Pt)
Pt100, -200 to 850
Pt200, -200 to 850
Pt500, -200 to 850
Pt1000, -200 to 850
Ni 100, -60 to 180
Ni 200, -60 to 180
Ni 500, -60 to 180
Ni1000, -60 to 180
R, 0 to 766.66 OHM
R, 0 to 4000 OHM
APt100, -100 to 450
APt200, -100 to 450
APt500, -100 to 450
APt1000, -100 t0 450
)RU7&P90RGXOH,QSXW
Undefined
J, gain=25
K, gain=25
Open circuit test:
Thermocouple Type:
E, gain=25
T, gain=100
S, gain=100
R, gain=100
B, gain=100
Raw output, amplifier gain:
(see Note)
1RWH
A gain of 25 produces readings with + 100mV.
A gain of 100 produces readings with + 25mV.
This channel installed:
No
Yes
25
100
Yes
No
The following information pertains to configuration of the 140AII33010 intrinsic safe analog input module.
840 USE 100 00 11/2004
371
Intrinsically Safe Modules
I/O Map Register
Assignments
The 140AII33010 module requires nine contiguous input (3x) registers assigned as follows.
Register 1 Channel 1 data
Register 2 Channel 2 data
Register 3 Channel 3 data
Register 4 Channel 4 data
Register 5 Channel 5 data
Register 6 Channel 6 data
Register 7 Channel 7 data
Register 8 Channel 8 data
Register 9 Input Status Word
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 = Broken Wire (4 ... 20 mA only) or out of range on Channel 8
1 = Broken Wire (4 ... 20 mA only) or out of range on Channel 7
1 = Broken Wire (4 ... 20 mA only) or out of range on Channel 6
1 = Broken Wire (4 ... 20 mA only) or out of range on Channel 5
1 = Broken Wire (4 ... 20 mA only) or out of range on Channel 4
1 = Broken Wire (4 ... 20 mA only) or out of range on Channel 3
1 = Broken Wire (4 ... 20 mA only) or out of range on Channel 2
1 = Broken Wire (4 ... 20 mA only) or out of range on Channel 1
I/O Map Status
Byte (Inputs)
The most significant bit in the I/O map status byte is used for this module.
MSB
1 2 3 4 5 6 7 8
1= Broken wire (4 ... 20 mA only) on one or more input channels
Modsoft Module
Zoom Selections
Use Modsoft’s Module Zoom feature to display and select the input range.
Channel x Range Selection
4 to 20mA 0 - 16,000
4 to 20mA 0 - 4095
0 to 20mA 0 - 20,000
0 to 25mA 0 - 25,000
372
840 USE 100 00 11/2004
140AIO33000
I/O Register
Assignments
Intrinsically Safe Modules
The following information pertains to configuration of the 140AIO33000 intrinsic safe analog output module.
The 140AIO33000 module requires eight contiguous output (4x) registers assigned as follows:
Register 1 Channel 1 data
Register 2 Channel 2 data
Register 3 Channel 3 data
Register 4 Channel 4 data
Register 5 Channel 5 data
Register 6 Channel 6 data
Register 7 Channel 7 data
Register 8 Channel 8 data
I/O Map Status
Byte
The I/O map status byte for this module is as follows.
8 7 6 5 4 3 2 1
Channel 1 loop broken wire (4 ... 20 mA)
Channel 2 loop broken wire (4 ... 20 mA)
Channel 3 loop broken wire (4 ... 20 mA)
Channel 4 loop broken wire (4 ... 20 mA)
Channel 5 loop broken wire (4 ... 20 mA)
Channel 6 loop broken wire (4 ... 20 mA)
Channel 7 loop broken wire (4 ... 20 mA)
Channel 8 loop broken wire (4 ... 20 mA)
840 USE 100 00 11/2004
373
Intrinsically Safe Modules
Modsoft Module
Zoom Selections
Use Modsoft’s Module Zoom feature to display and select the module channel ranges and time-out state. Time-out state is assumed when system control of the module is stopped.
The following figure shows the time-out state for the Modsoft module zoom feature.
Channel X Range Selection:
4 to 20 mA 0 - 16,000
4 to 20 mA 0 - 4,095
0 to 20 mA 0 - 20,000
0 to 25 mA 0 - 25,000
Channel X Time-out State:
Disabled
Last Value
User Defined
User Defined Time Out Value is in Percentage:
50.00% should be entered as 5000:
Channel X User Defined Time Out Value: 0 DEC
374
840 USE 100 00 11/2004
Intrinsically Safe Modules
140AII33000 Intrinsically Safe Analog Input Module
Overview The Quantum 140AII33000 Intrinsically Safe Analog Input module will interface with eight intrinsically safe analog inputs, which are software-configurable on a module basis with either RTD/Resistance or thermocouple/millivolt inputs.
When it is configured as an RTD/Resistance Input module, it supports 100
Ω
, 200
Ω
,
500 Ω , and 1000 Ω platinum (American or European) and nickel sensors. The module also allows any mix and match of sensor type or resistance inputs that can be configured by the software.
When it is configured as a Thermocouple/Millivolt Input module, it accepts B, J, K,
E, R, S and T type thermocouples. The module also allows any mix and match of thermocouple or millivolt inputs that can be configured by the software.
RTD/Resistance
Module
Specifications
Specifications for the Quantum140AII33000 module configured as an Intrinsically
Safe RTD/Resistance input module are as follows.
RTD/Resistance Module Specifications
Number of Channels 8
LEDs Active
F (Red)
1 - 8 (Red) Indicated channel is out of range - includes broken wire and short circuit conditions.
RTD Types (Configurable)
Platinum (American and European)
– PT100, PT200, PT500, PT1000
-200° C to +850° C
Nickel – N100, N200, N500, N1000 -60° C to +180° C
Measurement Current
PT100, PT200, N100, N200
PT500, PT1000, N500, N1000
Input Impedance
Linearity
2.5 mA
0.5 mA
>10 M
Ω
+/- 0.003% of full scale (0 ... 60° C)
Resolution
Absolute Accuracy
Accuracy Error @ 25°C
Input Filter
Isolation
12 bits plus sign (0.1° C)
+/- 0.5 °C (25° C)
+/- 0.9 °C (0 .. 60° C)
Typical: +/- 0.05% of full scale Maximum: +/- 0.1% of full scale
> 100 dB @ 50/60 Hz
840 USE 100 00 11/2004
375
Intrinsically Safe Modules
RTD/Resistance Module Specifications
Channel to Channel
Channel to Bus
None
1780 Vac @ 47-63 Hz or 2500 Vdc for 1 min.
Update Time (All Channels)
3-wire
2 or 4-wire
Bus Current Required
Power Dissipation
External Power
Fault Detection
Hot Swap
Fusing
Programming Software
1.35 sec.
750 m sec.
400 mA
2 W
Not required for this module
Out of range or broken wire conditions
Not allowed per intrinsic safety standards
Internal-not user accessible
Modsoft Ver. 2.61 or higher
Thermocouple/
Millivolt Module
Specifications
The following table shows the specifications for the Thermocouple/Millivolt module.
Thermocouple/Millivolt Module Specifications
Number of Channels 8
LEDs Active
F (Red)
1 ... 8 (Red). Indicated channel is out of range - Broken wire condition is detected.
TC Types and Ranges
Types J K E T S R B
Millivolt Ranges
Ranges (°C) -210 ... +760
-270 ... +1370
-270 ... +1000
-270 ... +400
-50 ... +1665
-50 ... +1665
+130 ... +1820
-100 mV ... +100 mV*
-25 mV ... +25 mV*
*Open circuit detect can be disabled on these ranges
200
Ω
max for rated accuracy TC Circuit Resistance/Max
Source Resistance
Input Impedance
Input Filter
Normal Noise Rejection
>1M
Ω
60 Hz
Single low pass @ nominal 20 Hz. Plus notch filter at 50/
120 dB min @ 50 or 60 Hz
376
840 USE 100 00 11/2004
840 USE 100 00 11/2004
Intrinsically Safe Modules
Thermocouple/Millivolt Module Specifications
Cold Junction Compensation
(CJC)
Internal CJC operates 0 ... 60° C (errors are included in the accuracy specification). The connector door must be closed. Remote CJC can be implemented by connecting the TC (which monitors the external junction block temperature) to channel 1. Types J, K, and T are recommended for best accuracy.
Programming Software
Resolution
Modsoft Ver. 2.61or higher
TC Ranges
Millivolt Ranges
Choice of: 1° C (Default) 0.1° C 1° F 0.1° F
+/- 100 mV range, 3.05
μ
V (16 bits)
+/- 25 mV range, 0.76
μ
V (16 bits)
TC Absolute Accuracy (see Note 1)
Types J, K, E, T (see Note 2)
Types S, R, B (see Note 3)
Millivolt Absolute Accuracy
@ 25°C
+/- 2° C +/- 0.1% of reading
+/- 4° C +/- 0.1% of reading
Accuracy Drift w/ Temperature
Isolation
Channel to Channel
Channel to Bus
Update Time
Fault Detection
Bus Current Required
Power Dissipation
External Power
Hot Swap
Fusing
Programming Software
+/- 20
μ
V +/- 0.1% of reading
0.15
μ
V/°C + 0.0015% of reading/°C max.
None
1780 Vac @ 47-63 Hz or 2500 Vdc for 1 min.
1 sec. (all channels)
Out of range or broken wire
400 mA
2 W
Not required for this module
Not allowed per intrinsic safety standards
Internal - not user accessible
Modsoft Ver. 2.6 or higher or Concept Ver. 2.2 or higher
Notes :
1. Absolute accuracy includes all errors from the internal CJC, TC curvature, offset plus gain, for module temperature of 0 ... 60° C. User-supplied TC errors not included.
2. For type J and K, add 1.5° C inaccuracy for temperatures below -100° C.
3. Type B cannot be used below 130° C.
4. All TC ranges have an open TC detect and upscale output. This results in a reading 7FFFh or 32767 decimal when an open TC is detected.
377
Intrinsically Safe Modules
Field Wiring Field wiring to the module shall consist of separate shielded twisted pair wires. The acceptable field wire gauge shall be AWG 20 to AWG 12. In a 2-wire field configuration, the maximum field wire length is a function of the required accuracy.
Wiring between the module and the intrinsically safe field device should follow intrinsically safe wiring practices to avoid the transfer of unsafe levels of energy to the hazardous area.
RTD/Resistance
Input Wiring
When the Universal Input module is configured as a RTD/Resistance Input module, the maximum wire length (distance to a sensor) for a 3 or 4-wire configuration is 200 meters.
Thermocouple/
Millivolt Input
Wiring
Fixed Wiring
System
When the module is configured as a Thermocouple/Millivolt Input module, the sum of thermocouple source or voltage source impedance and wire resistance should not exceed 200 ohms for rated accuracy.
The Quantum140AII33000 Intrinsically Safe Analog Input module is designed with a fixed wiring system where the field connections are made to a 40-pin, fixed position, blue terminal strip which is plugged into the module.
Terminal Strip
Color and Keying
Assignment
The module’s 140XTS33200 field wiring terminal strip is color-coded blue to identify it as an intrinsically safe connector.
The terminal strip is keyed to prevent the wrong connector from being applied to the module. The keying assignment is given below.
Module Class
Intrinsically Safe
Module Part Number Module Coding Terminal Strip Coding
140AII33000 CDF ABE
378
840 USE 100 00 11/2004
Intrinsically Safe Modules
Agency
Approved Wiring
Diagrams
The following is a Cenelec certified wiring diagram for this module configured with an RTD/Resistance connection.
&(1(/(&&(57,),&$7,21
(QWLW\3DUDPHWHUV
SHU&KDQQHO
V o
= 15.5 Vdc
I o
= 276 mA/ch
P o
C
L o o
= 1.07 W/ch
= 0.508 μ F/ch
= 466 μ H/ch
I Source 1 (+)
V Sense 1 (+)
NON-HAZARDOUS LOCATION
I Source 1 (-)
V Sense 1 (-)
+$=$5'286/2&$7,21
=21(
*URXS,,$,,%,,&
(SEE NOTE 1)
4 Wire RTD/Resistor
Connection
1&
I Source 2 (+)
V Sense 2 (+)
I Source 3 (+)
V Sense 3 (+)
1&
I Source 4 (+)
V Sense 4 (+)
I Source 5 (+)
V Sense 5 (+)
1&
I Source 2 (-)
V Sense 2 (-)
I Source 3 (-)
V Sense 3 (-)
1&
I Source 4 (-)
V Sense 4 (-)
I Source 5 (-)
V Sense 5 (-)
Chassis
Ground
(SEE NOTE 1)
2 Wire RTD/Resistor
Connection
1&
I Source 6 (+)
V Sense 6 (+)
I Source 7 (+)
V Sense 7 (+)
1&
I Source 8 (+)
V Sense 8 (+)
I.S. Module AII 330 00
Blue Terminal Strip
1&
I Source 6 (-)
V Sense 6 (-)
I Source 7 (-)
V Sense 7 (-)
1&
I Source 8 (-)
V Sense 8 (-)
Chassis
Ground
1RWH Only shielded twisted pair cables should be used for connections. Shields should be left open at the field end and connected to chassis ground at the ground screws on the backplane.
(SEE NOTE 1)
3 Wire RTD/Resistor
Connection
1RWH Pins marked “N/C”
(Not Connected) are not electronically connected to the module.
Chassis
Ground
31001362 Rev 00 140 AII 330 00 RTD Wiring Diagram
840 USE 100 00 11/2004
379
Intrinsically Safe Modules
The following is a Cenelec certified wiring diagram for this module when configured with a Thermocouple connection.
&(1(/(&&(57,),&$7,21
(QWLW\3DUDPHWHUV
SHU&KDQQHO
Vo = 15.5 Vdc
Io = 276 mA/ch
Po = 1.07 W/ch
C0 = 0.508
μ
F/ch
Lo = 466 μ H/ch
I Source 1 (+)
V Sense 1 (+)
NON-HAZARDOUS LOCATION
+$=$5'286/2&$7,21
=21(
*5283,,$,,%,,&
(See Note 1)
Thermocouple Type
J, K, E, T, R, S, B
(See Note 2)
1&
I Source 2 (+)
V Sense 2 (+)
I Source 3 (+)
V Sense 3 (+)
1&
I Source 4 (+)
V Sense 4 (+)
I Source 5 (+)
V Sense 5 (+)
1&
I Source 6 (+)
V Sense 6 (+)
I Source 7 (+)
V Sense 7 (+)
1&
I Source 8 (+)
V Sense 8 (+)
I Source 1 (-)
V Sense 1 (-)
1&
I Source 2 (-)
V Sense 2 (-)
I Source 3 (-)
V Sense 3 (-)
1&
I Source 4 (-)
V Sense 4 (-)
I Source 5 (-)
V Sense 5 (-)
1&
I Source 6 (-)
V Sense 6 (-)
I Source 7 (-)
V Sense 7 (-)
1&
I Source 8 (-)
V Sense 8 (-)
I.S. Module AII 330 00
Blue Terminal Strip
Chassis
Ground
Chassis
Ground
(See Note 1)
(+) mV Source
(-)
1RWH Only shielded twisted pair cables should be used for connections. Shields should be left open at the field end and connected to chassis ground at the ground screws on the backplane.
1RWH Thermocouple tip may be grounded, if required.
1RWH Pins marked “N/C” (Not
Connected) are not electronically connected to the module.
31001362 Rev 00 140 AII 330 00 TC Wiring Diagram
380
840 USE 100 00 11/2004
Intrinsically Safe Modules
The following is a CSA certified wiring diagram for this module when configured with an RTD/resistor connection.
1RWHVUHODWHGWR
&6$FHUWLILFDWLRQ
IRUWKLVPRGXOH
1RWH
Entity parameters per channel: V oc
= 15.5 V
I sc
= 123 mA
C a
L a
= 0.47 uf
= 1.0 mH
NON-HAZARDOUS LOCATION
I Source 1 (+)
V Sense 1 (+)
I Source 1 (-)
V Sense 1 (-)
1RWH Maximum nonhazardous area voltage must not exceed 250 V.
1RWH Install in accordance with Canadian Electrical Code,
Part I for installation in Canada.
1RWH Install in accordance with the NEC (ANSI/NFPA 70) and ANSI/ISA RP 12.6 for installation in the United States.
1RWH To maintain intrinsic safety, shield for each cable must be grounded and must extend as close to the terminals as possible.
N/C
I Source 2 (+)
V Sense 2 (+)
I Source 3 (+)
V Sense 3 (+)
N/C
I Source 4 (+)
V Sense 4 (+)
I Source 5 (+)
V Sense 5 (+)
N/C
I Source 2 (-)
V Sense 2 (-)
I Source 3 (-)
V Sense 3 (-)
N/C
I Source 4 (-)
V Sense 4 (-)
I Source 5 (-)
V Sense 5 (-)
1RWH Intrinsically Safe (I.S) cables of one module must be routed separately from I.S.
cables of another module.
1RWH I.S. devices when connected to I.S. terminals must satisfy the following conditions:
V oc
< V max
I sc
< I max
C a
L
> C i
+ C cable a
> L i
+ L cable
V Sense 7 (+)
N/C
I Source 8 (+)
V Sense 8 (+)
1RWH
This module is certified as a component for mounting in a suitable enclosure where the suitability of the final combination is subject to acceptance by CSA or an inspection authority having the jurisdiction.
N/C
I Source 6 (+)
V Sense 6 (+)
I Source 7 (+)
N/C
I Source 6 (-)
V Sense 6 (-)
I Source 7 (-)
V Sense 7 (-)
N/C
I Source 8 (-)
V Sense 8 (-)
I.S. Module AII 330 00
Blue Terminal Strip
CHASSIS
GROUND
CHASSIS
GROUND
CHASSIS
GROUND
+$=$5'286/2&$7,21
&ODVV'LYLVLRQ
*URXS$%&'
(SEE NOTE 1)
4 Wire RTD/Resistor
Connection
1RWH Only shielded twisted pair cables should be used for connections. Shields should be left open at the field end and connected to chassis ground at the ground screws on the backplane.
(SEE NOTE 1)
2 Wire RTD/Resistor
Connection
1RWH Pins marked “N/C” (Not
Connected) are not electronically connected to the module.
1RWH Only Quantum
140 XBP 0X 00 backplanes should be used for mounting this module.
(SEE NOTE 1)
3 Wire RTD/Resistor
Connection
31001362 Rev 00 140 AII 330 00 RTD Wiring Diagram
840 USE 100 00 11/2004
381
Intrinsically Safe Modules
The following is a CSA certified wiring diagram for this module when configured with a thermocouple connection.
1RWHVUHODWHGWR
&6$FHUWLILFDWLRQ
IRUWKLVPRGXOH
1RWH
Entity parameters per channel: Voc = 15.5 V
Isc= 123 mA
Ca = 0.47
μ f
La = 1.0 mH
NON-HAZARDOUS LOCATION
+$=$5'286/2&$7,21
&ODVV'LYLVLRQ
*URXS$%&'
(SEE NOTE 1)
1RWH This module is certified as a component for mounting in a suitable enclosure where the suitability of the final combination is subject to acceptance by CSA or an inspection authority having the jurisdiction.
I Source 1 (+)
V Sense 1 (+)
1RWH . Maximum nonhazardous area voltage must not exceed 250 V.
1RWH,QVWDOOLQDFFRUGDQFH
ZLWK&DQDGLDQ(OHFWULFDO
&RGH3DUW,IRULQVWDOODWLRQLQ
&DQDGD
1RWH Install in accordance with the NEC (ANSI/NFPA 70) and ANSI/ISA RP 12.6 for installation in the United States.
N/C
I Source 2 (+)
V Sense 2 (+)
I Source 3 (+)
V Sense 3 (+)
N/C
I Source 4 (+)
1RWH To maintain intrinsic safety, shield for each cable must be grounded and must extend as close to the terminals as possible.
V Sense 4 (+)
I Source 5 (+)
V Sense 5 (+)
1RWH
Intrinsically Safe (I.S) cables of one module must be routed separately from I.S.
cables of another module.
N/C
I Source 6 (+)
V Sense 6 (+)
I Source 7 (+)
1RWH I.S. devices when connected to I.S. terminals must satisfy the following conditions:
V oc
< V max
I sc
< I max
C a
> C i
+ C cable
L a
> L i
+ L cable
V Sense 7 (+)
N/C
I Source 8 (+)
V Sense 8 (+)
I Source 1 (-)
V Sense 1 (-)
N/C
I Source 2 (-)
V Sense 2 (-)
I Source 3 (-)
V Sense 3 (-)
N/C
I Source 4 (-)
V Sense 4 (-)
I Source 5 (-)
V Sense 5 (-)
N/C
I Source 6 (-)
V Sense 6 (-)
I Source 7 (-)
V Sense 7 (-)
N/C
I Source 8 (-)
V Sense 8 (-)
I.S. Module AII 330 00
Blue Terminal Strip
31001362 Rev 00
Chassis
Ground
Chassis
Ground
Thermocouple
Type J, K, E, T, R, S, B
(SEE NOTE 2)
1RWH Only shielded twisted pair cables should be used for connections. Shields should be left open at the field end and connected to chassis ground at the ground screws on the backplane.
1RWH Thermocouple tip may be grounded if required.
(SEE NOTE 1)
(+) mV Source
(-)
1RWH Pins marked “N/C” (Not
Connected) are not electronically connected to the module.
1RWH Only Quantum
140 XBP 0X 00 backplanes should be used for mounting this module.
140 AII 330 00 TC Wiring Diagram
382
840 USE 100 00 11/2004
Intrinsically Safe Modules
The following is a FM certified wiring diagram for this module when configured as a
RTD/resistor connection.
N/C
I Source 4 (+)
V Sense 4 (+)
I Source 5 (+)
V Sense 5 (+)
1RWHV5HODWHGWR)0&HUWLILFDWLRQ
This IS field device should meet Note 5 or should be FM approved with entity concept in Note 4 appropriate for connection with RTD/TC IN Module with Concept Parameters listed below. The entity parameters are per Channel.
Voc = 15.5 VDC
Isc = 276 mA/Ch
Ca = 500 nf/Ch
La = 0.3 mH/Ch
Po = 1070 mW/Ch
+$=$5'286/2&$7,21
&ODVV,'LY*URXS$%&'
I Source 1 (+)
V Sense 1 (+)
N/C
I Source 2 (+)
V Sense 2 (+)
I Source 3 (+)
V Sense 3 (+)
N/C
I Source 6 (+)
V Sense 6 (+)
I Source 7 (+)
V Sense 7 (+)
N/C
I Source 8 (+)
V Sense 8 (+)
I Source 1 (-)
V Sense 1 (-)
N/C
I Source 2 (-)
V Sense 2 (-)
I Source 3 (-)
V Sense 3 (-)
N/C
I Source 4 (-)
V Sense 4 (-)
I Source 5 (-)
V Sense 5 (-)
N/C
I Source 6 (-)
V Sense 6 (-)
I Source 7 (-)
V Sense 7 (-)
N/C
I Source 8 (-)
V Sense 8 (-)
I.S. Module AII 330 00
Blue Terminal Strip
Chassis
Ground
Chassis
Ground
+$=$5'286/2&$7,21
&ODVV,'LY,*URXS$%&'
&ODVV,,'LY,*URXS()*
&ODVV,,,'LY,
1RWH Only shielded cables should be used for connections.
Shields should be left open at the field end and connected to chassis ground at the Module end.
4 Wire
RTD/Resistor
Connection
2 Wire
RTD/Resistor
Connection
1RWH Pins marked N/C are not electronically connected to the Module.
1RWH Only 140XBP0xx00 backplanes should be used for mounting this module.
1RWH The Entity Concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc for the associated apparatus are less than or equal to Vmax and Imax for the intrinsically safe apparatus and the approved values of Ca and La for the associated apparatus must be equal to or are greater than Ci and Li for the intrinsically safe apparatus plus all cable parameters.
Ca
≥
Ci + Ccable; La
≥
Li + Lcable; Voc
≤
Vmax; Isc
≤
Imax
1RWH Simple Apparatus is defined as a device which will neither generate nor store more than 1.2V, 0.1A, 20uJ, or 25 mW.
For examples, switches, Thermocouples, LEDs and RTDs, etc.
1RWH Wiring methods must be in accordance with National
Electrical Code NFPA 70, Article 504 and ANSI/ISA RP 12.6
“Wiring Practices for Hazardous (classified) Locations
Instrumentation Part I: Intrinsic Safety.”
1RWH Control room equipment connected to associated apparatus should not use or generate more than 250 Vrms.
1RWH All modules must be installed in an enclosure that meets the requirements of ANSI/ISA S82.01.
1RWH No revision to this drawing without prior FMRC approval.
1RWH For Schneider Electric internal use only. For control sheet, refer to 19-100986 Rev 1.
1RWH For Division 2 installation, the apparatus shall be installed in compliance with the enclosure, mounting, spacing, and segregation requirements of the ultimate application, including access only by the use of a tool and provision for Division 2 wiring methods.
Chassis
Ground
3 Wire
RTD/Resistor
Connection
31001362 Rev 01
140AII33000 RTD Wiring Diagram
840 USE 100 00 11/2004
383
Intrinsically Safe Modules
The following is a FM certified wiring diagram for this module when configured with a thermocouple connection.
1RWHV5HODWHGWR)0&HUWLILFDWLRQ
This IS field device should meet Note 5 or should be FM approved with entity concept in Note 4 appropriate for connection with IS RTD/TC IN Module with Concept Parameters listed below. The entity parameters are per Channel.
Voc = 15.5 VDC
Isc = 276 mA/Ch
Ca = 500 nf/Ch
La = 0.3 mH/Ch
Po = 1070 mW/Ch
+$=$5'286/2&$7,21
&ODVV,'LY*URXS$%&'
+$=$5'286/2&$7,21
&ODVV,'LY,*URXS$%&'
&ODVV,,'LY,*URXS()*
&ODVV,,,'LY,
384
I Source 1 (+)
V Sense 1 (+)
I Source 1 (-)
V Sense 1 (-)
N/C
I Source 2 (+)
V Sense 2 (+)
I Source 3 (+)
V Sense 3 (+)
N/C
I Source 4 (+)
V Sense 4 (+)
I Source 5 (+)
V Sense 5 (+)
N/C
I Source 6 (+)
V Sense 6 (+)
I Source 7 (+)
V Sense 7 (+)
N/C
I Source 8 (+)
V Sense 8 (+)
N/C
I Source 2 (-)
V Sense 2 (-)
I Source 3 (-)
V Sense 3 (-)
N/C
I Source 4 (-)
V Sense 4 (-)
I Source 5 (-)
V Sense 5 (-)
N/C
I Source 6 (-)
V Sense 6 (-)
I Source 7 (-)
V Sense 7 (-)
N/C
I Source 8 (-)
V Sense 8 (-)
I.S. Module AII 330 00
Blue Terminal Strip
140AII33000 TC Wiring Diagram
31001362 Rev 01
Thermocouple
Type J, K, E, T, R, S, B
Chassis
Ground
1RWH Only shielded cables should be used for connections.
Shields should be left open at the field end and connected to chassis ground at the Module end. Thermocouple tips may be grounded if required.
1RWH Pins marked N/C are not electronically connected to the Module.
1RWH Only 140 XBP 0xx 00 backplanes should be used for mounting this module.
1RWH The Entity Concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc for the associated apparatus are less than or equal to Vmax and Imax for the intrinsically safe apparatus and the approved values of Ca and La for the associated apparatus must be equal to or are greater than Ci and Li for the intrinsically safe apparatus plus all cable parameters.
Ca ≥ Ci + Ccable; La ≥ Li + Lcable; Voc ≤ Vmax; Isc ≤ Imax
(+) mV Source
(-)
Chassis
Ground
1RWH
Simple Apparatus is defined as a device which will neither generate nor store more than 1.2V, 0.1A, 20uJ, or 25 mW.
For examples, switches, Thermocouples, LEDs and RTDs, etc.
1RWH Wiring methods must be in accordance with National
Electrical Code NFPA 70, Article 504 and ANSI/ISA RP 12.6
“Wiring Practices for Hazardous (classified) Locations
Instrumentation Part I: Intrinsic Safety.”
1RWH
Control room equipment connected to associated apparatus should not use or generate more than 250 Vrms.
1RWH All modules must be installed in an enclosure that meets the requirements of ANSI/ISA S82.01.
1RWH No revision to this drawing without prior FMRC approval.
1RWH For Schneider Electric internal use only. For control sheet, refer to 19-100986 Rev 1.
1RWH For Division 2 installation, the apparatus shall be installed in compliance with the enclosure, mounting, spacing, and segregation requirements of the ultimate application, including access only by the use of a tool and provision for Div 2 wiring methods.
840 USE 100 00 11/2004
Intrinsically Safe Modules
The following is a UL certified wiring diagram for this module when configured with an RTD/resistor connection.
1RWHVUHODWHGWR
8/FHUWLILFDWLRQ
IRUWKLVPRGXOH
NON-HAZARDOUS LOCATION
I Source 1 (-)
V Sense 1 (-)
+$=$5'286/2&$7,21
&ODVV'LYLVLRQ
*5283$%&'
(SEE NOTE 1) 1RWH Entity parameters per channel: V
I oc
= 15.5 V sc
C
L a a
= 123 mA
= 0.47 uf
= 466 uH
I Source 1 (+)
V Sense 1 (+)
1RWH
Maximum nonhazardous area voltage must not exceed 250 V.
N/C
I Source 2 (+)
1RWH If the electrical parameters of the cable are unknown, the following values must be used for Ccable and Lcable:
Capacitance 60 Pf/ft
Inductance 0.20 uH/ft
V Sense 2 (+)
I Source 3 (+)
V Sense 3 (+)
N/C
I Source 2 (-)
V Sense 2 (-)
I Source 3 (-)
V Sense 3 (-)
Chassis
Ground
4 Wire RTD/Resistor
Connection
1RWH
Install in accordance with the NEC (ANSI/NFPA 70) and ANSI/ISA RP 12.6 for installation in the United States.
N/C
I Source 4 (+)
N/C
I Source 4 (-)
(SEE NOTE 1)
V Sense 4 (+)
N/C
I Source 6 (+)
V Sense 4 (-)
N/C
I Source 6 (-)
2 Wire RTD/Resistor
Connection
1RWH To maintain intrinsic safety, shield for each cable must be grounded and must extend as close to the terminals as possible.
1RWH Intrinsically Safe (I.S) cables of one module must be routed separately from I.S.
cables of another module.
I Source 5 (+)
V Sense 5 (+)
V Sense 6 (+)
I Source 7 (+)
I Source 5 (-)
V Sense 5 (-)
V Sense 6 (-)
I Source 7 (-)
Chassis
Ground
1RWH Only shielded twisted pair cables should be used for connections. Shields should be left open at the field end and connected to chassis ground at the ground screws on the backplane.
1RWH I.S. devices when connected to I.S. terminals must satisfy the following conditions:
V oc
I sc
< V max
< I max
C a
L a
> C
> L i
+ C i
+ L cable cable
V Sense 7 (+)
N/C
I Source 8 (+)
V Sense 7 (-)
N/C
I Source 8 (-)
(SEE NOTE 1)
V Sense 8 (+) V Sense 8 (-)
3 Wire RTD/Resistor
Connection
I.S. Module AII 330 00
Blue Terminal Strip
31001362 Rev 00
1RWH Pins marked “N/C” (Not
Connected) are not electronically
Chassis
Ground connected to the module.
1RWH Only Quantum
140 XBP 0X 00 backplanes should be used for mounting this module along with the following UL listed modules:
140 CPU xxx xx
140 AII 330 00 RTD Wiring Diagram
140 CPS xxx xx
840 USE 100 00 11/2004
385
Intrinsically Safe Modules
The following is a UL certified wiring diagram for this module when configured with a thermocouple connection.
1RWHVUHODWHGWR
8/FHUWLILFDWLRQ
IRUWKLVPRGXOH
1RWH Entity parameters per channel: V oc
= 15.5 V
I sc
= 123 mA
C a
L a
= 0.47 uf
= 466
μ
H
NON-HAZARDOUS LOCATION
I Source 1 (+)
V Sense 1 (+)
I Source 1 (-)
V Sense 1 (-)
1RWH
Maximum nonhazardous area voltage must not exceed 250 V.
1RWH,IWKHHOHFWULFDO
SDUDPHWHUVRIWKHFDEOHDUH
XQNQRZQWKHIROORZLQJYDOXHV must be used for Ccable and
Lcable:
Capacitance
Inductance
60 Pf/ft
0.20 uH/ft
1RWH Install in accordance with the NEC (ANSI/NFPA 70) and ANSI/ISA RP 12.6 for installation in the United States.
1RWH To maintain intrinsic safety, shield for each cable must be grounded and must extend as close to the terminal as possible.
1RWH Intrinsically Safe (I.S) cables of one module must be routed separately from I.S.
cables of another module.
1RWH I.S. devices when connected to I.S. terminals must satisfy the following conditions:
V oc
< V max
I sc
< I max
C a
> C i
+ C cable
L a
> L i
+ L cable
N/C
I Source 2 (+)
V Sense 2 (+)
I Source 3 (+)
V Sense 3 (+)
N/C
I Source 4 (+)
V Sense 4 (+)
I Source 5 (+)
V Sense 5 (+)
N/C
I Source 6 (+)
V Sense 6 (+)
I Source 7 (+)
V Sense 7 (+)
N/C
I Source 8 (+)
V Sense 8 (+)
N/C
I Source 2 (-)
V Sense 2 (-)
I Source 3 (-)
V Sense 3 (-)
N/C
I Source 4 (-)
V Sense 4 (-)
I Source 5 (-)
V Sense 5 (-)
N/C
I Source 6 (-)
V Sense 6 (-)
I Source 7 (-)
V Sense 7 (-)
N/C
I Source 8 (-)
V Sense 8 (-)
I.S. Module AII 330 00
Blue Terminal Strip
Chassis
Ground
Chassis
Ground
+$=$5'286/2&$7,21
&/$66',9,6,21
*5283$%&'
(SEE NOTE 1)
Thermocouple
Type J, K, E, T, R, S, B
(See Note 2)
1RWH Only shielded twisted pair cables should be used for connections. Shields should be left open at the field end and connected to chassis ground at the ground screws on the backplane.
1RWH Thermocouple tip may be grounded if required.
(See Note 1)
(+) mV Source
(-)
1RWH Pins marked “N/C” (Not
Connected) are not electronically connected to the module.
1RWH2QO\4XDQWXP
;%3;EDFNSODQHV
VKRXOGEHXVHGIRUPRXQWLQJ
WKLVPRGXOHDORQJZLWKWKH
IROORZLQJ8/OLVWHGPRGXOHV
140 CPU xxx xx
140 CPS xxx xx
31001362 Rev 00 140 AII 330 00 TC Wiring Diagram
386
840 USE 100 00 11/2004
Intrinsically Safe Modules
140AII33010 Intrinsically Safe Current Input Module
Overview
Specifications
840 USE 100 00 11/2004
The Quantum 140AII33010 Intrinsically Safe Current Input module interfaces with eight intrinsically safe analog inputs which are software-configurable. The module accepts 0 ... 20 mA, 0 ... 25 mA, and 4 ... 20 mA inputs. The module allows any mix and match of current input ranges that can be configured by the software. The module provides power to intrinsically safe transmitters located in hazardous areas.
Specifications for the Quantum 140AII33010 Intrinsically Safe Current Input module are as follows.
Specifications
Number of Channels 8
LEDs Active
F (Red)
1 ... 8 (Red), 1 per channel
Note : This module produces a fault signal F if any one channel detects a broken wire condition or an out-ofrange condition (4 ... 20 mA only).
Current Input
Linear Measuring Range
Absolute Maximum Input
Input Impedance
Resolution
Available Voltage
4 ... 20 mA
0 ... 20 mA
0 ... 25 mA
25 mA internally limited
100
Ω
+/- 0.1% between V+ and signal terminals
4 ... 20 mA, 0 to 4,095 counts
4 ... 20 mA0 to 16,000 counts
0 ... 20 mA, 0 to 20,000 counts
0 ... 25 mA, 0 to 25,000 counts
Terminals V+, V-, :~ 14.5 Vdc at 25 mA
Terminals V+, Signal :~ 13.6 Vdc at 20 mA
Accuracy Error @ 25°C Typical: +/- 0.05% of full scale
Maximum: +/- 0.1% of full scale
+ 0.003% of full scale Linearity
Accuracy Drift w/ Temperature Typical: +/- 0.0025% of full scale /°C
Maximum: +/- 0.005% of full scale /°C
Common Mode Rejection
Input Filter
Isolation
Channel to Channel
> 100 dB @ 50/60 Hz
Single pole low pass, -3 dB cutoff @ 15 Hz, +/- 20%
None
387
Intrinsically Safe Modules
Specifications
Channel to Bus
Update Time
Fault Detection
Bus Current Required
Power Dissipation
External Power
Hot Swap
Fusing
Programming Software
1780 Vac @ 47-63 Hz or 2500 Vdc for 1 min.
750 ms for all channels
Broken wire (4 ... 20 mA mode)
1.5 A
7.5 W
Not required
Not allowed per intrinsic safety standards
Internal-not user accessible
Modsoft Ver. 2.61 or higher
Field Wiring Field wiring to the module consists of separate shielded, twisted pair wires. The acceptable field wire gauge is AWG 20 to AWG 12. Wiring between the module and the intrinsically safe field device should follow intrinsically safe wiring practices to avoid the transfer of unsafe levels of energy to the hazardous area.
Fixed Wiring
System
The Quantum 140AII33010 Intrinsically Safe Current Input module is designed with a fixed wiring system, where the field connections are made to a 40-pin, fixed position, blue terminal strip which is plugged into the module.
Terminal Strip
Color and Keying
Assignment
The module’s 140XTS33200 field wiring terminal strip is color-coded blue to identify it as an intrinsically safe connector.The terminal strip is keyed to prevent the wrong connector from being applied to the module. The keying assignment is given below.
Module Class
Intrinsically Safe
Module Part Number Module Coding Terminal Strip Coding
140AII33010 CEF ABD
388
840 USE 100 00 11/2004
Intrinsically Safe Modules
Agency
Approved Wiring
Diagrams
The following is a Cenelec certified wiring diagram for this module.
&(1(/(&&(57,),&$7,21
(QWLW\3DUDPHWHUV
SHU&KDQQHO
Vo = 23.8 Vdc
Io = 112 mA/ch
Po = 622 mW/ch
Co = 127 nf/ch
Lo = 2.9 mH/ch
V1 (-)
N/C
V2 (-)
N/C
N/C
V5 (-)
N/C
V6 (-)
N/C
N/C
V7 (-)
N/C
V3 (-)
N/C
V4 (-)
N/C
N/C
V8 (-)
N/C
N/C N/C
I.S. Module AII 330 10
Blue Terminal Strip
NON-HAZARDOUS LOCATION
I.S. + 14.5 Vdc
+$=$5'286/2&$7,21
=21(
*5283,,$,,%,,&
(SEE NOTE 1)
I.S. 3 WIRE
TRANSMITTER
V1 (+)
Signal 1
V2 (+)
Signal 2
N/C
V3 (+)
Signal 3
V4 (+)
Signal 4
N/C
V5 (+)
Signal 5
V6 (+)
Signal 6
N/C
V7 (+)
Signal 7
V8 (+)
Signal 8
(SEE NOTE 1)
I.S. 2 WIRE
TRANSMITTER
1RWH Only shielded twisted pair cables should be used for connections. Shields should be left open at the field end and connected to chassis ground at the ground screws on the backplane.
1RWH . A dropping resistor 100
Ohms is across the signal and V(-) pins of each channel. V(-) is internally connected to I.S. ground.
1RWH
Three wire transmitters should be provided power RQO\ from the module. An external power supply
VKRXOGQRW
be used.
1RWH Pins marked “N/C” (Not
Connected) are not electronically connected to the module.
31001363 Rev 00
840 USE 100 00 11/2004
140 AII 330 10 Wiring Diagram
389
Intrinsically Safe Modules
The following is a CSA certified wiring diagram for this module.
1RWHVUHODWHGWR
&6$FHUWLILFDWLRQ
IRUWKLVPRGXOH
1RWH(QWLW\
SDUDPHWHUVSHUFKDQ
QHO
V oc
= 23.8 V
I sc
= 112 mA
C a
= 127nf
1RWH0D[LPXPQRQ
KD]DUGRXVDUHDYROWDJH
PXVWQRWH[FHHG9
1RWH,QVWDOOLQ
DFFRUGDQFHZLWK
&DQDGLDQ(OHFWULFDO
&RGH3DUW,IRULQVWDOOD
WLRQLQ&DQDGD
1RWH,QVWDOOLQ
DFFRUGDQFHZLWKWKH1(&
$16,1)3$DQG
$16,,6$53IRU
LQVWDOODWLRQLQWKH8QLWHG
6WDWHV
1RWH7RPDLQWDLQ
LQWULQVLFVDIHW\VKLHOGIRU
HDFKFDEOHPXVWEH
JURXQGHGDQGPXVW
H[WHQGDVFORVHWRWKH
WHUPLQDOVDVSRVVLEOH
1RWHLQWULQVLFDOO\
6DIH,6FDEOHVRIRQH
PRGXOHPXVWEHURXWHG
VHSDUDWHO\IURP,6
FDEOHVRIDQRWKHU
module.
1RWH,6GHYLFHVZKHQ
FRQQHFWHGWR,6WHUPL
QDOVPXVWVDWLVI\WKHIRO
ORZLQJFRQGLWLRQV
V oc
< V max
I sc
< I max
C a > Ci
+ C cable
L a > Li
+ L cable
1RWH7KLVPRGXOHLV
FHUWLILHGDVDFRPSRQHQW
IRUPRXQWLQJLQDVXLWDEOH
HQFORVXUHZKHUHWKHVXLW
DELOLW\RIWKHILQDOFRPEL
QDWLRQLVVXEMHFWWR
DFFHSWDQFHE\&6$RUDQ
LQVSHFWLRQDXWKRULW\KDY
LQJWKHMXULVGLFWLRQ
V1 (-)
(See Note 2)
N/C
V2 (-)
N/C
N/C
V5 (-)
N/C
V6 (-)
N/C
N/C
V3 (-)
N/C
V4 (-)
N/C
N/C
V7 (-)
N/C
V8 (-)
N/C
N/C
NON-HAZARDOUS LOCATION
V1 (+)
Signal 1
V2 (+)
Signal 2
N/C
V3 (+)
Signal 3
V4 (+)
Signal 4
N/C
V5 (+)
Signal 5
V6 (+)
Signal 6
N/C
V7 (+)
Signal 7
V8 (+)
Signal 8
N/C
I.S. Module AII 330 10
Blue Terminal Strip
31001363 Rev 00
I.S. + 14.5 Vdc
Chassis
Ground
(See Note 1)
Chassis
Ground
(See Note 1)
+$=$5'286/2&$7,21
=21(
*5283,,$,,%,,&
(SEE NOTE 1)
I.S. 3 wire transmitter
1RWH Only shielded twisted pair cables should be used for connections. Shields should be left open at the field end and connected to chassis ground at the ground screws on the backplane.
1RWH A dropping resistor 100
Ohms is across the signal and V(-) pins of each channel. V(-) is internally connected to I.S. ground.
1RWH
Three wire transmitters should be provided power RQO\ from the module. An external power supply VKRXOGQRW be used.
1RWH Pins marked “N/C” (Not
Connected) are not electronically connected to the module.
1RWH Only Quantum
140 XBP 0X 00 backplanes should be used for mounting this module.
140 AII 330 10 Wiring Diagram
(SEE NOTE 1)
I.S. 2 wire transmitter
390
840 USE 100 00 11/2004
Intrinsically Safe Modules
The following is a FM certified wiring diagram for this module.
1RWHV5HODWHGWR)0&HUWLILFDWLRQ
This IS field device should meet note 6 or should be FM approved with entity concept in Note 5 appropriate for connection with IS Analog Current IN Module with Concept Parameters listed below. The entity parameters are per channel.
Voc = 23.8 VDC
Isc = 112 mA/Ch
Ca = 127 nf/CH
La = 2.9 mH/Ch
Po = 622 mW/CH
+$=$5'286/2&$7,21
&ODVV,'LY*URXS$%&'
+$=$5'286/2&$7,21
Class I Div I Group A, B, C, D
Class II Div I Group E, F, G
Class III Div I
N/C
V5 (-)
N/C
V6 (-)
N/C
N/C
V7 (-)
N/C
V8 (-)
N/C
V1 (-)
N/C
V2 (-)
N/C
N/C
V3 (-)
N/C
V4 (-)
N/C
V1 (+)
Signal 1
V2 (+)
Signal 2
N/C
V3 (+)
Signal 3
V4 (+)
Signal 4
N/C
V5 (+)
Signal 5
V6 (+)
Signal 6
N/C
V7 (+)
Signal 7
V8 (+)
Signal 8
N/C N/C
I.S. Module AII 330 10
Blue Terminal Strip
31001363 Rev 01
140 AII 330 10 Wiring Diagram
I.S. + 14.5 Vdc @ 25 mA
Chassis
Ground
I.S. 3 wire transmitter
1RWH
Only shielded cables should be used for connections.
Shields should be left open at the field end and connected to chassis ground at the Module end.
1RWH Pins marked N/C are not electronically connected to the Module.
1RWH Only 140 XBP 0xx 00 backplanes should be used for mounting this module.
1RWH
Three wire transmitters should be provided power only from the Module. External Power Supply should not be used.
Chassis
Ground
I.S. 2 wire transmitter
1RWH The Entity Concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc for the associated apparatus are less than or equal to Vmax and Imax for the intrinsically safe apparatus and the approved values of Ca and La for the associated apparatus must be equal to or are greater than Ci and Li for the intrinsically safe apparatus plus all cable parameters.
Ca ≥ Ci + Ccable; La ≥ Li + Lcable; Voc ≤ Vmax; Isc ≤ Imax
1RWH Simple Apparatus is defined as a device which will neither generate nor store more than 1.2V, 0.1A, 20uJ, or 25 mW.
For examples, switches, Thermocouples, LEDs and RTDs, etc.
1RWH
Wiring methods must be in accordance with National
Electrical Code NFPA 70, Article 504 and ANSI/ISA RP 12.6
“Wiring Practices for Hazardous (classified) Locations
Instrumentation Part I: Intrinsic Safety.”
1RWH
Control room equipment connected to associated apparatus should not use or generate more than 250 Vrms.
1RWH All modules must be installed in an enclosure that meets the requirements of ANSI/ISA S82.01.
1RWH No revision to this drawing without prior FMRC approval.
1RWH
For Schneider Electric internal use only. For control sheet, refer to 19-100986 Rev 1.
1RWH For Division 2 installation, the apparatus shall be installed in compliance with the enclosure, mounting, spacing, and segregation requirements of the ultimate application, including access only by the use of a tool and provision for Division 2 wiring methods.
840 USE 100 00 11/2004
391
Intrinsically Safe Modules
The following is a UL certified wiring diagram for this module.
1RWHVUHODWHGWR
8/FHUWLILFDWLRQ
IRUWKLVPRGXOH .
1RWH Entity parameters per channel: V cc
= 24.3 V
I sc
= 112 mA
C a
= 127 nf
L a
= 1.5 mH
NON-HAZARDOUS LOCATION
+$=$5'286/2&$7,21
&/$66,',9,6,21,
*5283$%&'
(SEE NOTE 1)
1RWH
Maximum nonhazardous area voltage must not exceed 250 V.
V1 (-)
(See Note 2)
N/C
V2 (-)
V1 (+)
Signal 1
V2 (+)
Signal 2
I.S. + 14.5 Vdc
I.S. 3 wire transmitter
1RWH If the electrical parameters of the cable are unknown, the following values must be used for Ccable and Lcable:
Capacitance 60Pf/ft
Inductance 0.20 uH/ft
N/C
N/C
V3 (-)
N/C
V3 (+)
Signal 3
1RWH Install in accordance with the NEC (ANSI/NFPA 70) and ANSI/ISA RP 12.6 for installation in the United States.
1RWH To maintain intrinsic safety, shield for each cable must be grounded and must extend as close to the terminals as possible.
N/C
V4 (-)
N/C
N/C
V5 (-)
N/C
V6 (-)
V4 (+)
Signal 4
N/C
V5 (+)
Signal 5
(SEE NOTE 1)
I.S. 2 wire transmitter
1RWH Only shielded twisted pair cables should be used for connections. Shields should be left open at the field end and connected to chassis ground at the ground screws on the backplane.
V6 (+)
Signal 6
1RWH Intrinsically Safe (I.S) cables of one module must be routed separately from I.S.
cables of another module.
N/C
N/C
V7 (-)
N/C
V7 (+)
1RWH A dropping resistor of 100
Ohms is across the Signal and V
(-) pins of each channel. V (-) is internally connected to I.S. ground.
1RWH I.S. devices when connected to I.S. terminals must satisfy the following conditions:
V cc
< V
I sc
< I max
C a
> C i max
+ C cable
L a
> L i
+ L cable
N/C
V8 (-)
N/C
Signal 7
V8 (+)
Signal 8
1RWH
Three Wire Transmitters should be provided power RQO\ from the module. An external power supply VKRXOGQRW be used.
N/C N/C
1RWH Pins marked “N/C” (Not
Connected) are not electronically connected to the module.
I.S. Module AII 330 10
Blue Terminal Strip
31001363 Rev 00
1RWH Only Quantum
140 XBP 0X 00 backplanes should be used for mounting this module along with the following UL listed modules:
140 CPU xxx xx
140 CPS xxx xx
140 AII 330 10 Wiring Diagram
392
840 USE 100 00 11/2004
Intrinsically Safe Modules
140AIO33000 Intrinsically Safe Analog Output Module
Overview
Specifications
The Quantum 140AIO33000 Intrinsically Safe Analog Output module controls and monitors current loops in intrinsically safe applications. The module provides 8 dualended output channels that are referenced over sense resistors to a single
Common. The output ranges are 4 ... 20 mA, 0 ... 20 mA, and 0 ... 25 mA. This module detects broken wires on a per-channel basis indicates their location on the front panel LEDs, and transmits the status to the PLC.
Specifications for the Quantum 140AIO33000 Intrinsically Safe Analog Output module are as follows.
Specifications
Number of Channels
LEDs
8
Active (Green)
F (Red)
1 ... 8 (Green) - Module output switched ON
1 ... 8 (Red) - Broken wire on indicated Channel
(4 ... 20 mArange)
Loop Resistance
Ranges
500 ohms maximum
4 ... 20 mA (0 to 4095) 4 ... 20 mA (0 to 16000)
0 ... 20 mA (0 to 20000) 0 ... 25mA (0 to 25000)
15 bits within 4 ... 20 mA Resolution
Accuracy Drift w/
Temperature
Typical: 40 PPM/°C.
Maximum: 70 PPM/°C
Accuracy Error @ 25°C +/- 0.2% of full scale
Linearity +/- 1 LSB
Isolation
Channel to Channel
Channel to Bus
Update Time
Settling Time
Bus Current Required
Power Dissipation
External Power
Fault Detection
None
1780 Vac RMS for 1 minute
4 ms - for all channels
1 ms to +/- 0.1% of the final value
2.5 Amp
12.5 W
Not required for this module
Open circuit in 4 ... 20 mA range
Voltmeter Monitor Specifications
Range 0.250 ... 1.250 V
840 USE 100 00 11/2004
393
Intrinsically Safe Modules
Specifications
Scaling
V
OUT (Volts) =
I
LOOP (mA) x 0.0625
Output Impedance
Wire Length
Hot Swap
Fusing
62.5 W Typical
1 m maximum
Not allowed per intrinsic safety standards
Internal - not user accessible
Programming Software Modsoft Ver. 2.61or higher
Field Wiring
Fixed Wiring
System
Field wiring to the module should consist of separate shielded, twisted pair wires.
The acceptable field wire gauge should be AWG 30 to AWG 18. Wiring between the module and the intrinsically safe field device should follow intrinsically safe wiring practices to avoid the transfer of unsafe levels of energy to the hazardous area.
The Quantum140AIO33000 Intrinsically Safe Analog Output module is designed with a fixed wiring system where the field connections are made to a 40-pin, fixed position, blue terminal strip which is plugged into the module.
Terminal Strip
Color and Keying
Assignment
The module’s 140XTS33200 field wiring terminal strip is color-coded blue to identify it as an intrinsically safe connector.
The terminal strip is keyed to prevent the wrong connector from being applied to the module. The keying assignment is given below.
Module Class Module Part Number Module Coding Terminal Strip Coding
Intrinsically Safe 140AIO33000 CEF ABD
394
840 USE 100 00 11/2004
Intrinsically Safe Modules
Agency
Approved Wiring
Diagrams
The following is a CSA certified wiring diagram for this module.
1RWHVUHODWHGWR
&6$FHUWLILFDWLRQ
IRUWKLVPRGXOH
1RWH Entity parameters per channel: V cc
= 29.42 V
I sc
= 93 mA
C a
= 71 nf
L a
= 2.0 mH
1RWH Maximum nonhazardous area voltage must not exceed 250 V.
1RWH
Install in accordance with Canadian Electrical Code,
Part I for installation in Canada.
1RWH Install in accordance with the NEC (ANSI/NFPA 70) and ANSI/ISA RP 12.6 for installation in the United States.
1RWH
To maintain intrinsic safety, shield for each cable must be grounded and must extend as close to the terminals as possible.
1RWH
Intrinsically Safe (I.S.) cables of one module must be routed separately from I.S.
cables of another module.
1RWH
I.S. devices when connected to I.S. terminals must satisfy the following conditions:
V cc
< V max
I sc
< I max
C a
> C i +
C cable
L a
> L i +
L cable
1RWH
This module is certified as a component for mounting in a suitable enclosure where the suitability of the final combination is subject to acceptance by CSA or an inspection authority having the jurisdiction.
NON-HAZARDOUS LOCATION
Output 1 (-)
N/C
Output 2 (-)
Monitor 1 (-)
Output 1(+)
Monitor 2 (-)
N/C
Output 3 (-)
N/C
Output 4 (+)
Output 2 (+)
Monitor 3 (-)
Output 3 (+)
Monitor 4 (-)
Output 4 (+)
N/C
N/C
N/C
N/C
N/C
N/C
Output 5 (-)
N/C
Output 6 (-)
N/C
Monitor 5 (-)
V
Output 5 (+)
Monitor 6 (-)
N/C
Output 7 (-)
Output 6 (+)
Monitor 7 (-)
N/C
Output 8 (-)
Output 7 (+)
Monitor 8 (-)
Output 8 (+)
N/C
N/C
N/C
I.S. Module AIO 330 00
Blue Terminal Strip
Chassis
Ground
(See Note 3)
31001364 Rev 00
+$=$5'286/2&$7,21
&/$66',9,6,21
*5283$%&'
(SEE NOTE 1)
I.S. Field Device
R-500 OHMS Max
(SEE NOTE 2)
1RWH Only shielded cables should be used for connections.
Shields should be left open at the field end and connected to chassis ground at the module end.
1RWH More than one device can be connected as long as they have differential input and total input resistance is less than 500 ohms.
1RWH The voltmeter is optional and reads voltage proportional to the current.
Length of wiring to this terminal is limited to 1 Meter.
1RWH Unused channels will show open loop unless outputs are shorted as shown for channel 8.
1RWH Pins marked “N/C” (Not
Connected) are not electronically connected to the module.
1RWH
Only Quantum
140 XBP 0X 00 backplanes should be used for mounting this module.
140 AIO 330 00 Wiring Diagram
840 USE 100 00 11/2004
395
Intrinsically Safe Modules
The following is a FM certified wiring diagram for this module.
1RWHV5HODWHGWR)0&HUWLILFDWLRQ
This IS field device should meet Note 7 or should be FM approved with entity concept in Note 6 appropriate for connection with IS RTD/TC IN Module with concept parameters listed below. The entity parameters listed are per channel.
Voc = 29.5 VDC
Isc = 94 mA/Ch
Ca = 68 nf/Ch
La = 4.2 mH/Ch
Po = 520 mW/Ch
+$=$5'286/2&$7,21
&ODVV,'LY*URXS$%&'
+$=$5'286/2&$7,21
&/$66,',9,*5283$%&'
&/$66,,',9,*5283()*
&/$66,,,',9,
396
Output 1 (-) Monitor 1 (-)
Output 1 (+)
N/C
Output 2 (-) Monitor 2 (+)
Output 2 (+)
N/C
Output 3 (-)
N/C
Output 4 (-)
Monitor 3 (-)
Output 3 (+)
Monitor 4 (-)
Output 4 (+)
N/C
N/C
N/C
N/C
Output 5 (-)
N/C
N/C
N/C
Monitor 5 (-)
Output 5 (+)
Monitor 6 (-)
V
N/C
Output 6 (-)
Output 6 (+)
N/C
Output 7 (-)
N/C
Output 8 (-)
N/C
N/C
I.S. Module
Terminal Strip
N/C
Monitor 7 (-)
Output 7 (+)
Monitor 8 (-)
Output 8 (+)
Chassis
Ground
140 AIO 330 00 Wiring Diagram
31001364 Rev 01
I.S. Field Device
R-500 OHMS Max
1RWH
Only shielded cables should be used for connections. Shields should be left open at the field elnd and connected to chassis ground at the
Module end.
1RWH Pins marked N/C are not electronically connected to the Module.
1RWH Only 140 XBP 0xx 00 backplanes should be used for mounting this module.
1RWH More than one device can be connected in series as long as they have differential input and total load resistance is less than 500 ohms.
1RWH Voltmeter is an optional Voltmeter shown to read voltage proportional to the current. Wiring to this terminal is limited to 1 meter.
Unused channels will show Open Loop unless shorted as
Shown in Channel 8.
1RWH The Entity Concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and
Isc for the associated apparatus are less than or equal to Vmax and
Imax for the intrinsically safe apparatus and the approved values of
Ca and La for the associated apparatus must be equal to or are greater than Ci and Li for the intrinsically Safe apparatus plus all cable parameters.
Ca
≥
Ci + Ccable; La
≥
Li + Lcable; Voc
≤
Vmax; Isc
≤
Imax
1RWH Simple Apparatus is defined as a device which will neither generate nor store more than 1.2V, 0.1A, 20uJ, or 25 mW. For examples switches, Thermocouples, LEDs and RTDs, etc.
1RWH
Wiring methods must be in accordance with National Electrical
Code NFPA 70, Article 504 and ANSI/ISA RP12.6, “Wiring Practices for Hazardous (classified) Locations Instrumentation
Part I: Intrinsic Safety”.
1RWH Control room equipment connected to associated apparatus should not use or generate more than 250Vrms.
1RWH All modules must be installed in an enclosure that meets the requirements of ANSI/ISA S82.01
1RWH No revisions to this drawing without prior FMRC Approval.
1RWH For Schneider Electric internal use only. For control sheet, refer to 19-100986 Rev 1.
1RWH
For Division 2 installation, the apparatus shall be installed in compliance with the enclosure, mounting, spacing, and segregation requirements of the ultimate application, including access only by the use of a tool and provision for Division 2 wiring methods.
840 USE 100 00 11/2004
Intrinsically Safe Modules
The following is a UL certified wiring diagram for this module.
1RWHVUHODWHGWR
8/FHUWLILFDWLRQ
IRUWKLVPRGXOH
NON-HAZARDOUS LOCATION +$=$5'286/2&$7,21
&/$66',9,6,21
*5283$%&'
1RWH Entity parameters per channel: V cc
I sc
= 29.5 V
= 93 mA
C a
= 68 nf
L a
= 2.0 mH
Output 1 (-) Monitor 1 (-)
Output 1(+)
(SEE NOTE 1)
I.S. Field Device
R-500 OHMS Max
(SEE NOTE 2)
N/C
1RWH Maximum nonhazardous area voltage must not exceed 250 V.
Output 2 (-)
N/C
Monitor 2 (-)
Output 2 (+)
1RWH
If the electrical parameter of the cable are unknown, the following values must be used for Ccable and
Lcable:
Capacitance 60 Pf/ft
Inductance 0.20 uH/ft
Output 3 (-)
N/C
Output 4 (-)
Monitor 3 (-)
Output 3 (+)
Monitor 4 (-)
Output 4 (+)
Chassis
Ground
1RWH Only shielded cables should be used for connections.
Shields should be left open at the field end and connected to chassis ground at the module end.
1RWH Install in accordance with the NEC (ANSI/NFPA 70) and ANSI/ISA RP 12.6 for installation in the United States.
1RWH To maintain intrinsic safety, shield for each cable must be grounded and must extend as close to the terminals as possible.
N/C
N/C
N/C
N/C
Output 5 (-)
N/C
Output 6 (-)
N/C
Output 7 (-)
N/C
N/C
N/C
Monitor 5 (-)
Output 5 (+)
Monitor 6 (-)
Output 6 (+)
Monitor 7 (-)
V
(See Note 3)
1RWH
More than one device can be connected as long as they have differential input and total input resistance is less than 500 ohms.
1RWH The voltmeter is optional and reads voltage proportional to the current.
Length of wiring to this terminal is limited to 1 Meter.
1RWH
Unused channels will show open loop unless outputs are shorted as shown for channel 8.
1RWH Intrinsically Safe (I.S.) cables of one module must be routed separately from I.S.
cables of another module.
N/C
Output 8 (-)
Output 7 (+)
Monitor 8 (-)
1RWH
Pins marked “N/C” (Not
Connected) are not electronically connected to the module.
1RWH I.S. devices when connected to I.S. terminals must satisfy the following conditions:
V cc
< V max
I sc
< I max
C a
> C i +
C cable
L a
> L i +
L cable
N/C
N/C
I.S. Module AIO 330 00
Blue Terminal Strip
31001364 Rev 00
Output 8 (+)
N/C
1RWH Only Quantum
140 XBP 0X 00 backplanes should be used for mounting this module along with the following UL listed modules:
140 CPU xxx xx
140 CPS xxx xx
140 AIO 330 00 Wiring Diagram
840 USE 100 00 11/2004
397
Intrinsically Safe Modules
&(1(/(&&(57,),&$7,21
(QWLW\3DUDPHWHUV
SHUFKDQQHO
Vo = 29.5 Vdc
Io = 94 mA/Ch
Po = 520 mW/ch
Co = 68 nf/ch
Lo = 4.2 mH/ch
The following is a Cenelec certified wiring diagram for this module.
NON-HAZARDOUS LOCATION
Output 1 (-)
N/C
Output 2 (-)
Monitor 1 (-)
Output 1(+)
Monitor 2 (-)
N/C
Output 3 (-)
N/C
Output 4 (-)
Output 2 (+)
Monitor 3 (-)
Output 3 (+)
Monitor 4 (-)
Output 4 (+)
N/C
N/C
N/C
N/C
N/C
N/C
Output 5 (-)
N/C
Output 6 (-)
N/C
Monitor 5 (-)
V
Output 5 (+)
Monitor 6 (-)
Output 6 (+)
Monitor 7 (-)
N/C
Output 7 (-)
N/C
Output 8 (-)
Output 7 (+)
Monitor 8 (-)
Output 8 (+)
N/C
N/C
N/C
I.S. Module AIO 330 00
Blue Terminal Strip
Chassis
Ground
(See Note 3)
+$=$5'286/2&$7,21
&/$66',9,6,21
*5283$%&'
(SEE NOTE 1)
I.S. Field Device
R-500 OHMS Max
(SEE NOTE 2)
1RWH
Only shielded cables should be used for connections.
Shields should be left open at the field end and connected to chassis ground at the module end.
1RWH More than one device can be connected as long as they have differential input and total input resistance is less than 500 ohms.
1RWH The voltmeter is optional and reads voltage proportional to the current.
Length of wiring to this terminal is limited to 1 Meter.
1RWH Unused channels will show open loop unless outputs are shorted as shown for channel 8.
1RWH Pins marked “N/C” (Not
Connected) are not electronically connected to the module.
31001364 Rev 00
AIO 330 00 Wiring Diagram (Analog Output)
398
840 USE 100 00 11/2004
15.3
Intrinsically Safe Discrete Modules
Intrinsically Safe Modules
At a Glance
Overview
What’s in this
Section?
This section provides information on the intrinsically safe discrete modules,
140DII33000 and 140DIO33000.
This section contains the following topics:
Topic
I/O Configuration for Intrinsically Safe Discrete Modules
140DII33000 Intrinsically Safe Discrete Input Module
140DIO33000 Intrinsically Safe Discrete Output Module
Page
840 USE 100 00 11/2004
399
Intrinsically Safe Modules
I/O Configuration for Intrinsically Safe Discrete Modules
Overview This section provides information on the I/O configuration of the intrinsically safe discrete modules, 140DII33000 and 140DIO33000.
Intrinsically Safe
Discrete Input
Module
The following is the intrinsically safe discrete input module: z 140DII33000 (DC, intrinsic safe)
I/O Map Register
Assignment
This 8-point input module can be configured as either 8 contiguous discrete input
(1x) references or as one 3x register. The following figure shows an I/O map register.
1 2 3 4 5 6 7 8
&$87,21
,20DSSLQJ5XOHV
When I/O mapping input modules using discrete (1x) references in remote drops, users should not split discrete words between drops. The lowest discrete reference for a drop should start on a word boundary.
)DLOXUHWRIROORZWKLVSUHFDXWLRQFDQUHVXOWLQLQMXU\RUHTXLSPHQWGDPDJH
I/O Map Status
Byte
There is no I/O map status byte associated with this module.
Modsoft Module
Zoom Selections
Push <Enter> to display and select the input type. The following figure shows the input type display. input Type: BIN
BCD
400
840 USE 100 00 11/2004
Intrinsically Safe Modules
Intrinsically Safe
Discrete Output
Module
The following shows the 8-point discrete output module: z 140DIO33000 (DC, Intrinsic Safe
I/O Map Register
Assignment
The ouput modules listed above can be configured as either eight contiguous discrete output (0x) references or as one output (4x) register. The following figure shows the format for the output modules.
1 2 3 4 5 6 7 8
I/O Map Status
Byte
Module Zoom
Selections
There is no I/O Map status byte associated with this module.
Push <Enter> to display and select the output type and timeout state for the module.
Timeout state isassumed when system control of the module is stopped.
Output Type:
BIN
BCD
Timeout State:
Last Value
User Defined
User Defined Timeout State Points 1- 8: 00000000
840 USE 100 00 11/2004
401
Intrinsically Safe Modules
140DII33000 Intrinsically Safe Discrete Input Module
Overview
Specifications
The Quantum 140DII33000 Intrinsically Safe Discrete Input module provides safe power to dry contact closures e.g., push buttons, selector switches, float switches, flow switches, limit switches, etc., in a hazardous area, and receives the proportional current to indicate an on/off state. The received current is converted into digital signals that is transferred to the PLC.
The following table provides specifications for the DII33000 Intrinsically Safe
Discrete Input module.
Specifications
Number of Input Points 8
1 ... 8 (Green) – Indicates point status
Operating Voltages and Currents
No load voltage (between input + and input -)
8 Vdc
Short circuit current
Switching point
Switching hysteresis
Switching Frequency
Response
8 mA
1.2 mA ... 2.1 mA
0.2 mA
100 Hz maximum
402
Isolation
Channel to Channel
Channel to Bus
Internal Resistance
Input Protection
Fault Detection
Bus Current Required
Power Dissipation
External Power
Hot Swap
Fusing
Programming Software
None
1780 Vac, 47-63 Hz or 2500 Vdc for 1 min.
2.5 K
Ω
Resistor limited
None
400 mA
2 W
Not required
Not allowed per intrinsic safety standards
Internal - not user accessible
Modsoft Ver. 2.61 or higher
840 USE 100 00 11/2004
Fixed Wiring
System
Intrinsically Safe Modules
The DII33000module is designed with a fixed wiring system where the field connections are made to a 40-pin, fixed position, blue terminal strip which is plugged into the module.
Field Wiring Field wiring to the module consists of separate shielded twisted pair wires. The acceptable field wire gauge is AWG 20 to AWG 12. Wiring between the module and the intrinsically safe field device should follow intrinsically safe wiring practices, to avoid the transfer of unsafe levels of energy to the hazardous area.
Terminal Strip
Color and Keying
Assignment
The module’s 140XTS33200 field wiring terminal strip is color-coded blue to identify it as an intrinsically safe connector.
The terminal strip is keyed to prevent the wrong connector from being applied to the module. The keying assignment is given below.
Module Class
Intrinsically Safe
Module Part Number Module Coding Terminal Strip Coding
140 DII 330 00 CDE ABF
840 USE 100 00 11/2004
403
Intrinsically Safe Modules
Agency
Approved Wiring
Diagrams
The following is a Cenelec certified wiring diagram for this module.
&(1(/(&&(57,),&$7,21
(QWLW\3DUDPHWHUV
SHU&KDQQHO
Vo = 9.6 Vdc
Io = 80 mA/ch
Po = 192 mW/ch
Co = 450 nf/ch
Lo = 694 microH/ch
Input 1 (+)
N/C
Input 2 (+)
N/C
Input 3 (+)
N/C
Input 4 (+)
NON-HAZARDOUS LOCATION
Input 1 (-)
N/C
Input 2 (-)
N/C
Input 3 (-)
N/C
Input 4 (-)
Chassis
Ground
+$=$5'286/2&$7,21
=21(
*5283,,$,,%,,&
(SEE NOTE 1)
I.S. +8 Vdc
I.S. Field
Device
N/C
N/C
N/C
N/C
Input 5 (+)
N/C
N/C
N/C
N/C
Input 5 (-)
1RWH
Only shielded cables should be used for connections.
Shields should be left open at the field end and connected to chassis ground at the ground screws on the backplane.
1RWH
Pins marked “N/C” are not electronically connected to the module.
1RWH All “INPUT (- )S” are connected together internally.
N/C
Input 6 (+)
N/C
Input 7 (+)
N/C
Input 6 (-)
N/C
Input 7 (-)
N/C
Input 8 (+)
N/C
Input 8 (-)
N/C N/C
31001365 Rev 00
I.S. Module
DII 330 00
Blue Terminal Strip
140 DII 330 00 Wiring Diagram
404
840 USE 100 00 11/2004
Intrinsically Safe Modules
The following is a CSA certified wiring diagram for this module.
1RWHVUHODWHGWR
&6$FHUWLILFDWLRQ
IRUWKLVPRGXOH
1RWH Entity parameters per module: V oc
I sc
= 9.6 V
= 80 mA
C a
= 450 nf
L a
= 694 mH
1RWH Maximum nonhazardous area voltage must not exceed 250 V.
1RWH Install in accordance with Canadian Electrical Code,
Part I, for installation in Canada.
1RWH Install in accordance with the NEC (ANSI/NFPA 70) and ANSI/ISA RP 12.6 for installation in the United States.
1RWH To maintain intrinsic safety, shield for each cable must be grounded and must extend as close to the terminals as possible.
1RWH
Intrinsically Safe (I.S.) cables of one module must be routed separately from I.S.
cables of another module.
Input 1 (+)
N/C
Input 2 (+)
N/C
Input 3 (+)
N/C
Input 4 (+)
N/C
N/C
N/C
N/C
N/C
Input 5 (+)
NON-HAZARDOUS LOCATION
Input 1 (-)
N/C
Input 2 (-)
N/C
Input 3 (-)
N/C
Input 4 (-)
N/C
N/C
N/C
N/C
N/C
Input 5 (-)
Chassis
Ground
+$=$5'286/2&$7,21
&/$66',9,6,21
*5283$%&'
(See Note 1)
I.S. +8 Vdc
I.S. Field
Device
N/C
Input 6 (+)
N/C
Input 6 (-)
1RWH I.S. devices when connected to I.S. terminals must satisfy the following conditions:
V oc
< Vmax
I sc
< Imax
C a
> C i +
C cable
L a
> L i +
L cable
1RWH
This module is certified as a component for mounting in a suitable enclosure where the suitability of the final combination is subject to acceptance by CSA or an inspection authority having the jurisdiction.
N/C
Input 7 (+)
N/C
Input 8 (+)
N/C
Input 7 (-)
N/C
Input 8 (-)
N/C N/C
I.S. Module
DII 330 00
Blue Terminal Strip
31001365 Rev 00 140 DII 330 00 Wiring Diagram
1RWH
Only shielded cables should be used for connections.
Shields should be left open at the field end and connected to chassis ground at the ground screws on the backpalne.
1RWH Pins marked “N/C” (Not
Connected) are not electronically connected to the module.
1RWH Only Quantum
140 XBP oX oo backplanes should be used for mounting this module.
840 USE 100 00 11/2004
405
Intrinsically Safe Modules
Input 1 (+)
N/C
Input 2 (+)
N/C
Input 3 (+)
N/C
Input 4 (+)
The following is a FM certified wiring diagram for this module.
1RWHV5HODWHGWR)0&HUWLILFDWLRQ
This IS field device should meet Note 5 or should be FM approved or connection with IS RTD/TC IN Modules with
Concept Parameters listed below. The entity parameters are per Channel.
Voc = 9.6 VDC
Isc = 80 mA/Module
Ca = 450 nf/Ch
La = 0.694 mH/Ch
Po = 192 mW/Module
+$=$5'286/2&$7,21
&ODVV,'LY*URXS$%&'
+$=$5'286/2&$7,21
&/$66,',9,*5283$%&'
&/$66,,',9,*5283()*
&/$66,,,',9,
I.S. +8 Vdc
I.S. Field
Device
Input 1 (-)
N/C
Input 2 (-)
N/C
Input 3 (-)
N/C
Input 4 (-)
Chassis
Ground
N/C
N/C
N/C
N/C
N/C
Input 5 (+)
N/C
Input 6 (+)
N/C
Input 7 (+)
N/C
Input 8 (+)
N/C
N/C
N/C
N/C
N/C
Input 5 (-)
N/C
Input 6 (-)
N/C
Input 7 (-)
N/C
Input 8 (-)
1RWH Only shielded cables should be used for connections. Shields should be left open at the field end and connected to chassis ground at the
Module end.
1RWH Pins marked N/C are not electronically connected to the Module.
1RWH Only 140 XBP 0xx 00 backplanes should be used for mounting this module.
1RWH The Entity Concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and
Isc for the associated apparatus are less than or equal to Vmax and
Imax for the intrinsically safe apparatus and the approved values of
Ca and La for the associated apparatus must be equal to or are greater than Ci and Li for the intrinsically Safe apparatus plus all cable parameters.
Ca ≥ Ci + Ccable; La ≥ Li + Lcable; Voc ≤ Vmax; Isc ≤ Imax
1RWH
Simple Apparatus is defined as a device which will neither generate nor store more than 1.2V, 0.1A, 20uJ, or 25 mW. For examples switches, Thermocouples, LEDs and RTDs, Etc.
1RWH Wiring methods must be in accordance with National Electrical
Code NFPA 70, Article 504 and ANSI/ISA RP12.6, “Wiring Practices for Hazardous (classified) Locations Instrumentation
Part I: Intrinsic Safety”.
1RWH Control room equipment connected to associated apparatus should not use or generate more than 250Vrms.
1RWH All modules must be installed in an enclosure that meets the requirements of ANSI/ISA S82.01
1RWH No revision to this drawing without prior FMRC Approval.
1RWH For Schneider Electric internal use only. For control sheet, refer to 19-100986 Rev 1.
1RWH For Division 2 installation, the apparatus shall be installed in compliance with the enclosure, mounting, spacing, and segregation requirements of the ultimate application, including access only by the use of a tool and provision for Division 2 wiring methods.
N/C N/C
I.S. Module
DII 330 00
Blue Terminal Strip
31001365 Rev 01
140 DII 330 00 Wiring Diagram
406
840 USE 100 00 11/2004
Intrinsically Safe Modules
The following is a UL certified wiring diagram for this module.
1RWHVUHODWHGWR
8/FHUWLILFDWLRQ
IRUWKLVPRGXOH
1RWH Entity parameters per channel: V oc
I sc
= 9.5 V
= 80 mA
C a
= 450 nf
L a
= 0.175 mH
1RWH Maximum nonhazardous area voltage must not exceed 250 V.
1RWH If the electrical parameters of the cable are unknown, the following values must be used for Ccable and
Lcable:
Capactance 60 Pf/ft
Inductance 0.20 uH/ft
1RWH
Install in accordance with the NEC (ANSI/NFPA 70) and ANSI/ISA RP 12.6 for installation in the United States.
Input 1 (+)
N/C
Input 2 (+)
N/C
Input 3 (+)
N/C
Input 4 (+)
N/C
N/C
N/C
N/C
Input 5 (+)
NON-HAZARDOUS LOCATION
Input 1(-)
N/C
Input 2 (-)
N/C
Input 3 (-)
N/C
Input 4 (-)
N/C
N/C
N/C
N/C
Input 5 (-)
Chassis
Ground
+$=$5'286/2&$7,21
&/$66',9,6,21
*5283$%&'
(SEE NOTE 1)
I.S. +8 Vdc
I.S. Field
Device
1RWH
To maintain intrinsic safety, shield for each cable must be grounded and must extend as close to the terminals as possible.
N/C
Input 6 (+)
N/C
Input 6 (-)
N/C
Input 7 (+)
N/C
Input 7 (-)
1RWH Intrinsically Safe (I.S.) cables of one module must be routed separately from I.S.
cables of another module.
N/C
Input 8 (+)
N/C
Input 8 (-)
1RWH I.S. devices when connected to I.S. terminals must satisfy the following conditions:
V oc
< V max
I sc
< I max
C a
> C i +
C cable
L a
> L i +
L cable
N/C
N/C
31001365 Rev 00
N/C
N/C
I.S. Module
DII 330 00
Blue Terminal Strip
140DII33000 Wiring Diagram
1RWH Only shielded cables should be used for connections.
Shields should be left open at the field end and connected to chassis ground at the ground screws on the backplane.
1RWH Pins marked “N/C” (Not
Connected) are not electronically connected to the module.
1RWH
Only Quantum
140 XBP 0X 00 backplanes should be used for mounting this module along with the following UL listed modules:
140 CPU xxx xx
140 CPS xxx xx
840 USE 100 00 11/2004
407
Intrinsically Safe Modules
140DIO33000 Intrinsically Safe Discrete Output Module
Overview
Specifications
The Quantum 140DIO33000 Intrinsically Safe Discrete Output module switches intrinsically safe power to a variety of components such as solenoid valves, LEDs, etc., that are located in a hazardous area. This module is for use with sink devices only.
Specifications for the DIO33000 module are as follows.
Specifications
Number of Output Points
Output Voltage
Maximum Load Current
8
LEDs Active-1
1 ... 8 (Green) – Indicates point status
24 V (open)
Each Point
Per Module
45 mA
360 mA
Off State Leakage/Point
Response (Resistive Loads)
0.4 mA
OFF-ON 1 ms
Output Protection (Internal)
Isolation
Channel to Channel
Channel to Bus
Fault Detection
Bus Current Required
Power Dissipation
External Power
Hot Swap
Fusing
Programming Software
Transient voltage suppression
None
1780 Vac, 47-63 Hz or 2500 Vdc for 1 min.
None
2.2 Amp (full load)
5 W (full load)
Not required
Not allowed per intrinsic safety requirements
Internal - not user accessible
Modsoft Ver. 2.61 or higher
408
840 USE 100 00 11/2004
Fixed Wiring
System
Intrinsically Safe Modules
The DIO33000 module is designed with a fixed wiring system where the field connections are made to a 40-pin, fixed position, blue terminal strip, which is plugged into the module.
Field Wiring Field wiring to the module consists of separate shielded, twisted pair wires. The acceptable field wire gauge is AWG 20 to AWG 12. Wiring between the module and the intrinsically safe field device should follow intrinsically safe wiring practices, to avoid the transfer of unsafe levels of energy to the hazardous area.
Terminal Strip
Color and Keying
Assignment
The module’s 140XTS33200 field wiring terminal strip is color-coded blue to identify it as an intrinsically safe connector.
The terminal strip is keyed to prevent the wrong connector from being applied to the module. The keying assignment is given below.
Module Class
Intrinsically Safe
Module Part Number Module Coding Terminal Strip Coding
140DIO33000 CDE ABF
840 USE 100 00 11/2004
409
Intrinsically Safe Modules
Agency
Approved Wiring
Diagrams
The following is a Cenelec certified wiring diagram for this module.
&(1(/(&&(57,),&$7,21
(QWLW\3DUDPHWHUV
SHU&KDQQHO
Vo = 27.9 Vdc
Io = 121 mA/ch
Po = 840 mW/ch
Co = 84 nf/ch
Lo = 2.2 mH/ch
Output 1 (+)
NON-HAZARDOUS LOCATION
Output 1 (-)
+$=$5'286/2&$7,21
=21(
*5283,,$,,%,,&
(See Notes 1 & 2)
I.S. +8 Vdc
I.S. Field
Device
N/C
Output 2 (+)
N/C
Output 2 (-)
CHASSIS
GROUND N/C
Output 3 (+)
N/C
Output 4 (+)
N/C
Output 3 (-)
N/C
Output 4 (-)
N/C
N/C
N/C
N/C
Output 5 (+)
N/C
Output 6 (+)
N/C
N/C
N/C
N/C
Output 5 (-)
N/C
Output 6 (-)
1RWH Only shielded cables should be used for connections.
Shields should be left open at the field end and connected to chassis ground at the module end.
1RWH Pins marked “N/C” are not electronically connected to the module.
1RWH All “Output (- )s” are connected together internally
N/C
Output 7 (+)
N/C
Output 7 (-)
N/C
Output 8 (+)
N/C
Output 8 (-)
N/C N/C
N/C N/C
I.S. Module
DIO 330 00
Blue Terminal Strip
31001366 Rev 00 140 DIO 330 00 Wiring Diagram
410
840 USE 100 00 11/2004
Intrinsically Safe Modules
The following is a CSA certified wiring diagram for this module.
1RWHVUHODWHGWR
&6$FHUWLILFDWLRQ
IRUWKLVPRGXOH
1RWH Entity parameters per channel: V oc
= 27.9 V
I sc
= 119 mA
C a
= 84 nf
L a
= 1.0 mH
1RWH Maximum nonhazardous area voltage must not exceed 250 V.
1RWH
Install in accordance with Canadian Electrical Code,
Part I, for installation in Canada.
1RWH Install in accordance with the NEC (ANSI/NFPA 70) and ANSI/ISA RP 12.6 for installation in the United States.
1RWH
To maintain intrinsic safety, shield for each cable must be grounded and must extend as close to the terminals as possible.
1RWH Intrinsically safe (I.S.) cables of one module must be routed separately from I.S.
cables of another module.
1RWH I.S. devices when connected to I.S. terminals must satisfy the following conditions:
V oc
< Vmax
I sc
< Imax
C a
> C i +
C cable
L a
> L i +
L cable
1RWH This module is certified as a component for mounting in a suitable enclosure where the suitability of the final combination is subject to acceptance by CSA or an inspection authority having the jurisdiction.
Output 1 (+)
N/C
Output 2 (+)
N/C
Output 3 (+)
N/C
Output 4 (+)
N/C
N/C
N/C
N/C
Output 5 (+)
N/C
Output 6 (+)
N/C
Output 7 (+)
N/C
Output 8 (+)
NON-HAZARDOUS LOCATION
I.S. +24 Vdc @ NO LOAD
Output 1 (-)
N/C
Output 2 (-)
N/C
Output 3 (-)
N/C
Output 4 (-)
N/C
N/C
N/C
N/C
Output 5 (-)
N/C
Output 6 (-)
N/C
Output 7 (-)
N/C
Output 8 (-)
N/C N/C
N/C N/C
I.S. Module
DIO 330 00
Blue Terminal Strip
31001366 Rev 00
Chassis
Ground
+$=$5'286/2&$7,21
&/$66',9,6,21
*5283$%&'
(See Notes 1 & 2)
I.S. Field
Device
1RWH Only shielded cables should be used for connections.
Shields should be left open at the field end and connected to chassis ground at the ground screws on the backpalne.
1RWH All negative output terminals - Output 1 (-) thru
Output B (-) are internally connected to I.S. ground
1RWH Pins marked “N/C” (Not
Connected) are not electronically connected to the module.
1RWH Only Quantum
140 XBP oX oo backplanes should be used for mounting this module.
140 DIO 330 00 Wiring Diagram
840 USE 100 00 11/2004
411
Intrinsically Safe Modules
The following is a FM certified wiring diagram for this module.
1RWHV5HODWHGWR)0&HUWLILFDWLRQ
This IS field device should meet Note 5 or should be FM approved with entity concept in Note 4 appropriate for connection with IS RTD/TC IN Module with Concept Parameters LIsted below. The entity parameters are per Channel.
Voc = 27.9 VDC
Isc = 121 mA/Ch
Ca = 84 nf/Ch
La = 2.2 mH/Ch
Po = 840 mW/Ch
+$=$5'286/2&$7,21
&ODVV,'LY*URXS$%&'
+$=$5'286/2&$7,21
&/$66,',9,*5283$%&'
&/$66,,',9,*5283()*
&/$66,,,',9,
I.S. +24 Vdc@ NO LOAD
I.S. Field
Device
Output 1 (+)
N/C
Output 2 (+)
N/C
Output 3 (+)
N/C
Output 4 (+)
N/C
N/C
N/C
N/C
Output 5 (+)
Output 1 (-)
N/C
Output 2 (-)
N/C
Output 3 (-)
N/C
Output 4 (-)
N/C
N/C
N/C
N/C
Output 5 (-)
Chassis
Ground
N/C
Output 6 (+)
N/C
Output 6 (-)
N/C
Output 7 (+)
N/C
Output 7 (-)
N/C
Output 8 (+)
N/C
N/C
Output 8 (-)
N/C
N/C N/C
I.S. Module
DIO 330 00
Blue Terminal Strip
31001366 Rev 01
1RWH Only shielded cables should be used for connections. Shields should be left open at the field end and connected to chassis ground at the
Module end.
1RWH
Pins marked N/C are not electronically connected to the Module.
1RWH Only 140 XBP 0xx 00 backplanes should be used for mounting this module.
1RWH The Entity Concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and
Isc for the associated apparatus are less than or equal to Vmax and
Imax for the intrinsically safe apparatus and the approved values of
Ca and La for the associated apparatus must be equal to or are greater than Ci and Li for the intrinsically Safe apparatus plus all cable parameters.
Ca
≥
Ci + Ccable; La
≥
Li + Lcable; Voc
≤
Vmax; Isc
≤
Imax
1RWH Simple Apparatus is defined as a device which will neither generate nor store more than 1.2V, 0.1A, 20uJ, or 25 mW. For examples switches, Thermocouples, LEDs and RTDs, Etc.
1RWH Wiring methods must be in accordance with National Electrical
Code NFPA 70, Article 504 and ANSI/ISA RP1.2.6, “Wiring Practices for Hazardous (classified) Locations Instrumentation
Part I: Intrinsic Safety.”
1RWH Control room equipment connected to associated apparatus should not use or generate more than 250Vrms.
1RWH All modules must be installed in an enclosure that meets the requirements of ANSI/ISA S82.01
1RWH
No revision to this drawing without prior FMRC Approval.
1RWH For Schneider Electric internal use only. For control sheet, refer to 19-100986 Rev 1.
1RWH For Division 2 installation, the apparatus shall be installed in compliance with the enclosure, mounting, spacing, and segregation requirements of the ultimate application, including access only by the use of a tool and provision for Division 2 wiring methods.
140 DIO 330 00 Wiring Diagram
412
840 USE 100 00 11/2004
Intrinsically Safe Modules
The following is a UL certified wiring diagram for this module.
1RWHVUHODWHGWR
8/FHUWLILFDWLRQ
IRUWKLVPRGXOH
NON-HAZARDOUS LOCATION
1RWH Entity parameters per channel: V oc
= 27.9 V
I sc
= 119 mA
C a
= 84 nf
L a
= 1.0 mH
Output 1 (+)
1RWH Maximum nonhazardous area voltage must not exceed 250 V.
N/C
Output 2 (+)
N/C
Output 3 (+)
1RWH If the electrical parameters of the cable are unknown, the following values must be used for Ccable and
Lcable:
Capacitance 60 Pf/ft
Inductance 0.20 uH/ft
N/C
Output 4 (+)
N/C
N/C
1RWH
Install in accordance with the NEC (ANSI/NFPA 70) and ANSI/ISA RP 12.6 for installation in the United States.
N/C
N/C
Output 5 (+)
1RWH To maintain intrinsic safety, shield for each cable must be grounded and must extend as close to the terminals as possible.
N/C
Output 6 (+)
N/C
Output 7 (+)
1RWH Intrinsically Safe (I.S.) cables of one module must be routed separately from I.S.
cables of another module.
N/C
Output 8 (+)
I.S. +24 Vdc @ NO LOAD
Output 1(-)
N/C
Output 2 (-)
N/C
Output 3 (-)
N/C
Output 4 (-)
N/C
N/C
N/C
N/C
Output 5 (-)
N/C
Output 6 (-)
N/C
Output 7 (-)
N/C
Output 8 (-)
Chassis
Ground
1RWH I.S. devices when connected to I.S. terminals must satisfy the following conditions:
V cc
< V max
I sc
< I max
C a
> C i +
C cable
L a
> L i +
L cable
+$=$5'286/2&$7,21
&/$66',9,6,21
*URXS$%&'
(See Notes 1 & 2)
N/C
N/C
N/C
N/C
I.S. Module
DIO 330 00
Blue Terminal Strip
31001366 Rev 00 140 DIO 330 00 Wiring Diagram
I.S. Field
Device
1RWH Only shielded cables should be used for connections.
Shields should be left open at the field end and connected to chassis ground at the ground screws on the backplane.
1RWH All negative output terminals—Output 1 (-) thru
Output 8 (-)—are internally connected to I.S. ground
1RWH Pins marked “N/C” (Not
Connected) are not electronically connected to the module.
1RWH Only Quantum
140 XBP 0X 00 backplanes should be used for mounting this module along with the following UL listed modules:
140 CPU xxx xx
140 CPS xxx xx
840 USE 100 00 11/2004
413
Intrinsically Safe Modules
414
840 USE 100 00 11/2004
Quantum Simulator Modules
16
At a Glance
Introduction
What’s in this
Chapter?
This chapter provides information on discrete and analog simulator modules.
This chapter contains the following topics:
Topic
140XSM00200 Quantum Point Discrete Simulator Module
140XSM01000 Analog Simulator Module
Page
840 USE 100 00 11/2004
415
Simulator Modules
140XSM00200 Quantum Point Discrete Simulator Module
Overview The 140XSM00200 module consists of 16 toggle switches which are used to generate up to 16 binary input signals to the 140DAI54000 and the 140DAI74000
AC input modules.
&$87,21
(OHFWULFDO6KRFN+D]DUG
When using this simulator module with the 140DAI54000 or 140DAI74000 input modules, you should be careful not to come in contact with the supplied 115 or 230 VAC located at the bottom of the simulator module.
)DLOXUHWRIROORZWKLVSUHFDXWLRQFDQUHVXOWLQLQMXU\RUHTXLSPHQWGDPDJH
16 Point Discrete
Simulator
Module
The following figure shows the 140XSM00200 16 Point Discrete Simulator module.
X
416
6ZLWFK
3RVLWLRQ
Right
Middle
Left
)XQFWLRQ
Momentary Signal
Off
Constant Signal
X
Power
Connector
N L Power Connector Label
1RWH Voltage source range is 24 ... 230 Vac.
840 USE 100 00 11/2004
Simulator Modules
140XSM01000 Analog Simulator Module
Overview The 140XSM010module is used for simulating 4 ... 20 mA field current loops used with current input Quantum modules. It provides two adjustable 4 ... 20 mA analog signals and one fixed 24 Vdc output. The simulator also measures and displays voltages from 0 ... 5 Vdc. z z z
The simulator module includes the following:
An internal 24 Vdc power supply
A 0 ... 5 Vdc meter
Two 10-turn potentiometers
The following figure shows the XSM01000 Analog Simulator module. Analog
Simulator
Module
;60
Analog simulator
Removable Door
X
Voltmeter
X
Analog out
Potentiometers
Analog in1
Analog in2
X
Color Coded Leads
840 USE 100 00 11/2004
417
Simulator Modules
1RWH The 140XSM01000 can be placed in any slot in the Quantum.
1RWH The 140XSM01000 is not a functional module and should be used only for testing, simulating, and calibrating current input Quantum modules.
Specifications The following table shows the specifications for the XSM 010 00 analog simulator module.
Specifications
Voltage
Operating Voltage
Output Continuous
Operating Current
Voltmeter Range
10-Turn Potentiometer Output Variable Current/Voltage
Internal Fusing
Bus Current Required
100 ... 240 Vac, 50/60 Hz
24 Vdc, 400 mA max
300 mA @ 120 Vac
0 ... 5 Vdc
4 ... 20 mA
1 ... 5 Vdc
None
None
418
840 USE 100 00 11/2004
Simulator Modules
Wiring Diagram The following figure shows the 140XSM01000 generic wiring diagram for the
140Axl03000 input modules, 140Ax002000 output modules, and the 140AMM09000 input/output module.
:LULQJ([DPSOH
$QDORJ6LPXODWRU
;60
$QDORJ2XWSXW
Red
1
9
+
Black
White
2
Monitor
(Typical)
–
7
0-5 Vdc
9
249
Ohms
Blue
10
(Load for illustration purposes)
IN 1
Yellow
Violet
$QDORJ,QSXW
3
5
6
7
1
2
Input X
(Typical)
Input Y
(Typical)
IN 2
– +
24 Vdc
L
N
Black
White
Green/Yellow
115...240 Vac
840 USE 100 00 11/2004
140XSM01000 Generic Wiring Diagram for the 140AxI03000 Input Modules,
140AxO02000 Output Modules, and the 140AMM09000 Input/Output Module
1RWH The preceding diagram shows a typical connection between the simulator, a
140ACI03000 input module, and a 140ACO02000 output module. The simulator provides a variable 4 ... 20 mA input to the analog in module. The input can then be read by a Quantum
CPU, and, if required, outputted through an analog out module. For the output module to operate properly, the main current loop must be active, and, as shown above, 24 Vdc is supplied between terminals 9 and 10 with a 249 Ohms voltage drop resistor. (For a more detailed description of these modules, refer to S )
419
Simulator Modules
420
840 USE 100 00 11/2004
Quantum Battery Module
17
At a Glance
Overview
What’s in this
Chapter?
The following chapter provides information on the battery module, its installations and replacement considerations.
This chapter contains the following topics:
Topic
I/O Configuration for the 140XCP90000 Battery Module
140XCP90000 Quantum Battery Module
Page
840 USE 100 00 11/2004
421
Battery Module
I/O Configuration for the 140XCP90000 Battery Module
Overview The following provides information on the Battery module, 140XCP90000 (Battery
Backup).
I/O Map Register
Assignment
There is no I/O Map register assignment associated with this module.
I/O Map Status
Byte
The two least significant bits in the I/O Map status byte are used as follows:
8 7 6 5 4 3 2 1
Bat1 Low
Bat2 Low
Module Zoom
Selections
There are no Module Zoom selections required for this module.
422
840 USE 100 00 11/2004
Battery Module
140XCP90000 Quantum Battery Module
Overview
Battery Module
This section describes the battery module, its installation and replacement considerations.
The following figure shows the battery module components.
LED Area
Battery Slot 1
(with battery installed)
Battery Access Tape
(for removal/replacement)
Battery Slot 2
(with battery installed)
Battery Access Tape
(for removal/replacement)
;&3
%$77(5<%$&.83
Module Number
Module Description
Color Code
Removable Door
Customer
Identification
Label
Battery 1
Changed:
Battery2
Changed:
840 USE 100 00 11/2004
423
Battery Module
Battery Backup The 140XCP90000 provides RAM backup power for expert modules. One nonrechargeable 3.6 V lithium battery is provided and is accessible from the front of the module in Battery Slot 1 (the upper slot) for easy removal when it is necessary to change it.
1RWH Extended backup protection is provided when a second battery is installed in Battery Slot 2 (the lower slot).
Specifications The following table shows the specifications for the battery module.
Specifications
Battery Type
Maximum Load Current
Service Life
Shelf Life
Battery Part Number
C, 3 V lithium
100 mA
8000 mAh
10 years with 0.5% loss of capacity per year
990XCP99000
1RWH The formula to calculate the life cycle of one battery in the battery module is:
Life cycle = 1 / (4 x I) days where I (in Amps) is the total battery current load of all modules in the backplane.
424
840 USE 100 00 11/2004
Battery Module
LED Indicators and Descriptions
The following figure shows the LED indicators.
Active
Bat1 Low
Bat2 Low
The following table shows the LED descriptions.
LED Descriptions
LEDs Color
Active
Bat1 Low
Bat2 Low
Green
Red
Red
Indication when On
Bus communication is present.
Battery 1 voltage is low.
Battery 2 voltage is low.
1RWH The Bat1 Low and Bat2 Low LEDs turn ON when a battery is not installed, installed backwards, or in need of replacement.
Battery
Installation and
Replacement
Considerations
The following procedure describes the installation of a battery.
Step
1
2
3
Action
Remove the insulating strip from the plus (+) pole of the battery before inserting it into the module. This strip is used to insulate the battery when on the shelf.
Note: The battery installed in the module, when shipped, has the insulating strip in place. Remove this strip and re-install the battery before operation.
When single battery backup is required, install the battery in Battery Slot 1. The circuitry is designed so Battery 1 supplies the current until it is used up. Battery
2 (when installed) then assumes the load requirement without interruption.
Battery status is indicated via LEDs and Modsoft status bytes.
When the controller is in operation, the batteries can be replaced at any time.
Note: When the controller is powered OFF, battery replacement can be done without RAM loss only when a second functioning battery is installed.
840 USE 100 00 11/2004
425
Battery Module
Installing/
Removing a
Battery
The following procedure describes how to install or remove a battery.
Step
1
2
Action
Remove the insulating strip from the new battery.
If necessary, remove the old battery. Detach it from its housing (on the front of the module), by pulling the battery access strip (see below) until the battery pops out.
Insulating Strip
Battery
&$87,21
Pull on this tape to remove battery. Do not use metallic tool.
Batt. install date
Access Strip
3 Replace it with the new battery using the reverse of the procedure in step 2.
426
:$51,1*
0D\FDXVHSHUVRQDOLQMXU\RUGDPDJHWRHTXLSPHQW
Do not use any metallic tools (i.e., pliers, screwdriver, etc.) when removing or replacing a battery in this module. Using tools during removal and replacement may cause personal injury and/or damage to the battery and this module.
)DLOXUHWRIROORZWKLVSUHFDXWLRQFDQUHVXOWLQGHDWKVHULRXVLQMXU\RU
HTXLSPHQWGDPDJH
:$51,1*
0D\FDXVHSHUVRQDOLQMXU\RIGDPDJHWRHTXLSPHQW
Ensure that proper polarity is maintained when connecting and inserting new batteries into the XCP90000. Inserting the battery improperly may cause personal injury and/or damage to this module.
)DLOXUHWRIROORZWKLVSUHFDXWLRQFDQUHVXOWLQGHDWKVHULRXVLQMXU\RU
HTXLSPHQWGDPDJH
840 USE 100 00 11/2004
Battery Module
&$87,21
+D]DUGRXVZDVWH
Used batteries (hazardous waste) must be disposed of according to local rules and regulations governing hazardous waste.
)DLOXUHWRIROORZWKLVSUHFDXWLRQFDQUHVXOWLQLQMXU\RUHTXLSPHQWGDPDJH
840 USE 100 00 11/2004
427
Battery Module
428
840 USE 100 00 11/2004
,QGH[
Numerics
140 CFA 040 00 application notes, 722 description, 722 dimensions, 723 terminal block illustration, 722 wiring diagram, 723
140 CFB 032 00 application notes, 724 description, 724 terminal block illustration, 724 wiring for input modules, 725
140 CFC 032 00 wiring diagram for 140 DDI 353 00, 729
140 CFC 032 00 application notes, 728 description, 727 dimensions, 728 terminal block illustration, 727 wiring diagram for 140 DAI 353 00, 729 wiring diagram for 140 DAI 453 00, 729 wiring diagram for 140 DAI 553 00, 729 wiring diagram for 140 DDI 153 10, 730 wiring diagram for 140 DDI 853 00, 729 wiring diagram for 140 DDO 153 10, 731 wiring for 140 DDO 353 0X, 732 wiring for output module, 726
$
&
140 CFD 032 00 application notes, 733 description, 733 dimensions, 733 terminal block illustration, 733 wiring diagram, 734
140 CFE 032 00 dimensions, 735
140 CFE 032 00 application notes, 735 description, 735 terminal block illustration, 735 wiring diagram, 736
140 CFG 016 00 application notes, 737 description, 737 dimensions, 737 terminal block illustration, 737 wiring diagram
(grouped AC output mode), 740 wiring diagram
(grouped DC output mode), 741 wiring diagram
(isolated AC input mode), 738 wiring diagram
(isolated output mode), 739
840 USE 100 00 11/2004 xv
Index
140 CFH 008 00 application notes, 742 description, 742 dimensions, 742 terminal block illustration, 742 wiring diagram (chassis grounding), 745 wiring diagram
(instrument grounding), 744 wiring diagram (source grounding), 743
A
ACI03000 configuration, 445 description, 461
I/O map status byte, 447 register assignment, 446 specifications, 462 wiring diagram, 463
ACI04000 description, 464
I/O map status byte, 448 module zoom selections, 448 register assignment, 447 specifications, 465 wiring diagram, 466
ACO02000 configuration, 478 description, 482
I/O map status byte, 478 module zoom selections, 479 register assignments, 478 specifications, 482 voltmeter monitor specifications, 483 wiring diagram, 484
ACO13000 configuration, 479 description, 486
I/O map status byte, 480 module zoom selections, 480 register assignments, 479 specifications, 486 wiring diagram, 488 xvi
Agency approvals
ASCII interface, 773 backplane expander, 777 backplanes, 776 battery module, 774 counters, 773
CPUs, 770
DIO drops, 770 field bus modules, 771 high speed interrupts, 773
Hot Standby, 772
I/O, 775 intrinsically safe modules, 774
NOEs, 772
NOMs, 772 power supplies, 769
RIO heads and drops, 771 simulators, 774 single axis motion, 773
AII33000
I/O map register assignment, 367
I/O map status byte, 370 module zoom selections, 370
RTD/resistance module specifications, 375
terminal color and keying assignment, 378
thermocouple/millivolt map register assignment, 369
Thermocouple/Millivolt module specification, 376
wiring diagram (Cenelec/RTD), 379
wiring diagram (Cenelec/TC), 380
wiring diagram (CSA/RTD), 381 wiring diagram (CSA/TC), 382
840 USE 100 00 11/2004
AII33010
field wiring, 388 fixed wiring, 388
map status byte (inputs), 372 module zoom selections, 372 register assignment, 372
terminal strip color and keying assignment, 388
AIO33000
field wiring, 394 fixed wiring system, 394
terminal strip color and keying assignment, 394
AMM09000
3x registers, 494
4x registers, 496 common specifications, 501 configuration, 494 description, 498
I/O map status byte, 497 input specifications, 499 linear measuring ranges, 496 module zoom selections, 497 output specifications, 500 register assignments, 494 status warning, 495 topology specifications, 498 wiring diagram, 502
840 USE 100 00 11/2004
Index analog input modules configuration, 445 analog input/output module AMM09000, 498 analog output modules configuration, 478
analog simulator module XSM01000, 417
ARI03010 configuration, 448 description, 467
I/O map status byte, 450 module zoom selections, 450 register assignment, 449 specifications, 468 wiring diagram, 469
ASCII interface module ESI06210, 332
AS-i master module EAI92100, 195
ATI03000 configuration, 451 description, 470
I/O map status byte, 454 measurement ranges, 454, 455 module zoom selections, 456 register assignment, 452 specifications, 470 wiring diagram, 472
AVI03000 configuration, 457 description, 473
I/O map status byte, 459 linear measuring ranges, 459, 475 module zoom selections, 460 register assignment, 457 specifications, 474 wiring diagram, 476
AVO02000 configuration, 480 description, 489 module zoom selections, 481 register assignments, 481 specifications, 489 wiring diagram, 492 xvii
Index
B
backplane expander XBE10000, 352
backplanes four position, 677 mounting hardware specifications, 674 part numbers, 674 selecting, 674 six position, 678 sixteen position, 680 ten position, 679 three position, 676 two positions, 675
C
CableFast cable lengths, 759 cable selections (XTS), 760 cable specifications, 758 description, 716
I/O connector for Quantum, 761
I/O connector illustration, 762 inner wire color codes, 759 quantum modules and backplane illustration, 716 specifications, 717 terminal block descriptions, 720 terminal block features, 721 terminal block selection, 718 terminal block stacking convention, 721
XCA102xx pigtail, 761
XTS102xx pigtail, 762
CableFast accessories jumper, fuse replacement, 763 part numbers, 763 terminal block common strip, 763 cables part numbers, 659
CE closed system installation
AC & DC powered systems, 712
AC/DC installation illustration, 712 line filter connections, 713 protective cover, 713 xviii
CFB03200 terminal block dimensions, 724
CFI00800 application notes, 746 description, 746 dimensions, 746 wiring diagram (chassis grounding), 749 wiring diagram
(instrument grounding), 748 wiring diagram (source grounding), 747
CFJ00400 application notes, 750 description, 750 dimensions, 750 terminal block illustration, 750 wiring diagram (chassis grounding), 753 wiring diagram
(instrument grounding), 752 wiring diagram (source grounding), 751
CFK00400 application notes, 754 description, 754 dimensions, 754 terminal block illustration, 754 wiring diagram (chassis grounding), 757 wiring diagram
(instrument grounding), 756 wiring diagram (source grounding), 755
CHS11000
A/B designation slide switch, 360
blinking Com Act LED error codes, 359
description, 357 illustration, 357
keyswitch and update button, 359
LED indicators, 358 specifications, 358
communication interface modules
InterBus interface modules, 10
SY/MAX-Ethernet, 9 twisted-pair wiring, 9
840 USE 100 00 11/2004
connector types, for fiber optic links, 261
CPS11100
description, 60 illustration, 60
LED indicator, 62 wiring diagram, 62
CPS11100 (PV01 or greater)
description, 63 illustration, 63
LED indicator, 65 wiring diagram, 65
CPS11400
description, 66 illustration, 66
CPS11410
description, 69 illustration, 69
CPS11420
description, 72 illustration, 72
CPS12400
description, 75 illustration, 75
840 USE 100 00 11/2004
Index
CPS12420
description, 78 illustration, 78
CPS21100
description, 81 illustration, 81
LED indicator, 82 specifications, 82
CPS21400
description, 84 illustration, 84
LED indicator, 85 specifications, 85
CPS22400
description, 87 illustration, 87
LED indicator, 88 specifications, 88
CPS41400
description, 90 illustration, 90
operating curve and timing chart, 92
operating curve and timing chart, 95
xix
Index
CPS51100
description, 96 illustration, 96
CPS52400
description, 99 illustration, 99
CPU
hardware specifications, 50 part numbers, 50
CPU11302
ASCII communication port parameters, 111
Modbus ports pinout connections, 113
Modbus ports pinout connections for portable computers, 114
rear panel rotary switches, 112
RTU communication port parameters, 111
SW1 and SW2 address settings, 112
valid communication port parameters, 111
CPU11303
ASCII communication port parameters, 121
Modbus ports pinout connections, 123
Modbus ports pinout connections for portable computers, 124
RTU communication port parameters, 121
SW1 and SW2 address settings, 122
valid communication port parameters, 121
CPU21304
ASCII communication port parameters, 131
Modbus ports pinout connections, 133
Modbus ports pinout connections for portable computers, 134
RTU communication port parameters, 131
SW1 and SW2 address settings, 132
valid communication port parameters, 131
xx
840 USE 100 00 11/2004
CPU42402
ASCII communication port parameters, 141
Modbus ports pinout connections, 143
Modbus ports pinout connections for portable computers, 144
RTU communication port parameters, 141
SW1 and SW2 address settings, 142
valid communication port parameters, 141
ASCII comm port parameters, 151
Modbus ports pinout connections, 155
Modbus ports pinout connections for portable computers, 155
rear panel rotary switches, 152
SW1 and SW2 address settings, 152
valid comm port parameters, 151
Index
CPU43412A
ASCII communication port parameters, 162
Modbus pinout connections for portable computers, 166
Modbus ports pinout connections, 166
RTU communication port parameters, 162
SW1 and SW2 address settings, 164
valid communication port parameters, 162
CPU53414
ASCII communicaton port parameters, 173
Modbus ports pinout connections, 176
Modbus ports pinout connections for portable computers, 177
RTU communication port parameters, 173
SW1 and SW2 address settings, 175
valid communication port parameters, 173
840 USE 100 00 11/2004 xxi
Index
CPU53414A
ASCII communication port parameters, 184
Modbus ports pinout connections, 188
Modbus ports pinout connections for portable computers, 188
RTU communication port parameters, 184
SW1 and SW2 address settings, 187
valid communication port parameters, 184
CRA21X10
description, 214 illustration, 214
CRA21X20
description, 219 illustration, 219
CRA93200
xxii
CRA93X00
SW1 and SW2 address settings, 234
CRP81100
description, 190 illustration, 190
CRP93X00
D
DAI34000 description, 509 specifications, 510 wiring diagram, 511
DAI35300 description, 512 specifications, 513 wiring diagram, 514
DAI44000 description, 515 specifications, 516 wiring diagram, 517
DAI45300 description, 518 specifications, 519 wiring diagram, 520
DAI54000 description, 521 specifications, 522 wiring diagram, 523
840 USE 100 00 11/2004
DAI54300 description, 524 specifications, 524 wiring diagram, 525
DAI55300 description, 527 specifications, 527 wiring diagram, 528
DAI74000 description, 530 specifications, 531 wiring diagram, 532
DAI75300 description, 533 specifications, 534 wiring diagram, 535
DAM59000 common specifications, 642 description, 639 fuse locations, 643 input specifications, 640 output specifications, 641 topology specifications, 639 wiring diagram, 644
DAO84000 description, 564 specifications, 564 wiring diagram, 566
DAO84010 description, 568 specifications, 568 wiring diagram, 570, 575
DAO84210 description, 572 specifications, 572
DAO84220 description, 577 fuse locations, 579 specifications, 577 wiring diagram, 580
DAO85300 description, 582 fuse locations, 584 specifications, 582 wiring diagram, 584
840 USE 100 00 11/2004
Index
DD035301 fuse locations, 595
DD036400 recommended cables, 604
DDI15310 description, 536 logic states, 537 specifications, 536 wiring diagram, 537
DDI35300 description, 538 specifications, 538 wiring diagram, 539
DDI35310 description, 540 specifications, 540 wiring diagram, 541
DDI36400 color codes for input groups, 544 compatible connection sub-bases, 545 description, 542 front view illustration, 543
LEDs, 544 recommended cables, 544 specifications, 542
DDI67300 description, 546 minimum version levels, 547 specifications, 546 wiring diagram, 549
DDI84100 description, 550 specifications, 551 wiring diagram, 552
DDI85300 description, 553 specifications, 554 wiring diagram, 555
DDM39000 common specifications, 648 description, 646 fuse locations, 649 input specifications, 646 output specifications, 647 topology, 646 wiring diagram, 650 xxiii
Index
DDM69000 common specifications, 653 description, 651
I/O map register (outputs), 636
I/O map status byte (outputs), 636 input specifications, 651 module zoom selections (inputs), 636 module zoom selections (outputs), 637 output specifications, 652 register assignments, 635 topology, 651 version levels, 654 wiring diagram, 655
DDO15310 description, 586 fuse locations, 588 specifications, 587 wiring diagram, 589
DDO35300 description, 590 fuse locations, 592 specifications, 590 wiring diagram, 593
DDO35301 description, 594 specifications, 594 wiring diagram, 596
DDO35310 description, 597 fuse locations, 599 specificatons, 597 wiring diagram, 600
DDO36400 color codes for input groups, 604 compatible output adapter sub-bases,
605 description, 601 front view illustration, 603 selecting point status indicator
LEDs, 604 specifications, 601
DDO84300 description, 606 fuse locations, 607 specifications, 606 wiring diagram, 608 xxiv
DDO88500 description, 609 fuse locations, 611 specifications, 609 wiring diagram, 612
DII33000
terminal strip color and keying assignment, 403
DIO configuration
DIO modules CRA21X10 or CRA21X20, 214
DIO33000
description, 408 specifications, 408
terminal strip color and keying assignment, 409
direct CPU driver
network interface techniques, 33
discrete I/O true high illustration, 441 discrete I/O true low illustration, 441 discrete input (16-point) modules description, 505 module zoom selections, 505 register assignments, 505 discrete input (24-point) modules description, 505
I/O map register assignment, 506 module zoom selections, 506
840 USE 100 00 11/2004
discrete input (32-point) modules description, 506
I/O map register assignment, 507 module zoom selections, 507 discrete input (8-point) module
module zoom selections, 400 register assignments, 400
discrete input (96-point) modules description, 507 module zoom selections, 508 register assignments, 508 discrete input modules description, 505 discrete input/output (16/8 point) modules
I/O map assignments (outputs), 638 module zoom selections (inputs), 638 module zoom selections (outputs), 638 register assignments, 637 discrete input/output modules configuration, 635 discrete output (12-point) module description, 558 register assignments, 558 discrete output (16-point) modules description, 559 module zoom selections, 560 register assignments, 559 discrete output (32-point) modules description, 560 module zoom selections, 561 register assignments, 561 discrete output (8-point) modules
I/O map register assignment, 401, 557 module zoom selections, 401, 557
module zoom selections (outputs), 558 discrete output (96-point) module, 562 module zoom selections, 563 register assingment, 562
discrete simulator module XSM00200, 416
discrete verified output module
DVO85300, 625 distributed I/O
840 USE 100 00 11/2004
Index
DRA84000 description, 613 specifications, 613 wiring diagram, 615
DRC83000 description, 616 specifications, 616 wiring diagram, 618
DSI35300 description, 631 specifications, 632 wiring diagram, 633 dual cable configuration
RIO in a Hot Standby configuration, 24
DVO85300 configuration, 620 description, 625
Modsoft zoom screen selections, 621 register assignments, 620 specifications, 625 wiring diagram, 628
E
EHC10500
description, 290 illustration, 290
xxv
Index
EHC20200
Command 1 and Command 2 response formats, 303
Command 3 read input counter, 304
Command 3 response format, 304
Command 4 output register format, 304
Command 4 response format, 305
I/O map register assignment, 294
module configuration, 306, 310
read input counter command, 308
response for configuration command, 307
xxvi
response to read rate sample command, 311
timing diagrams, 324 timing parameters, 324
using I/O mapped registers, 306
EIA92100
AS-i cable connection illustration, 200
error stopped codes definitions, 766 list, 765
ESI06210
front panel connectors and switches, 336
Ethernet MMS modules NOE5X100, 273
Ethernet SY/MAX modules NOE3X100, 270
Ethernet TCP/IP module NOE2X100, 266
840 USE 100 00 11/2004
F
fiber optic cable
fiber optic network
calculating number of modules, 264
point-to-point configuration, 256
self healing ring configuration, 259
fuses description, 671
H
hardware specifications
ASCII interface module, 52 counter modules, 52
high speed interrupt module, 52
I/O modules (discrete in/out), 55
I/O modules (discrete out), 54
intrinsic safe analog modules, 57 intrinsic safe discrete modules, 57 miscellaneous modules, 57
power supplies for local and RIO drops, 49
single axis motion modules, 52
high speed counter (5 channel)
840 USE 100 00 11/2004
Index
high speed counter module (2 channel)
high speed interrupt modules HLI34000, 338
HLI34000
description, 338 illustration, 338
Hot Standby configuration
Hot Standby module CHS11000, 357
I
I/O map interface
network interface techniques, 34
I/O map status byte description, 442 illustration, 442 table/module configuration, 443
I/O modules
discrete I/O true high/true low circuit, 441 illustration, 431
LED descriptions, 431
LED descriptions for 16 point modules, 432
LED descriptions for 24 point input modules, 433
LED descriptions for 32 point I/O modules, 433
LED descriptions for bi-directional modules, 434
LED descriptions for discrete 12 point modules with fault indication, 436
LED indicators for 16 point modules, 432
LED indicators for 24 point input modules, 433
LED indicators for 32 point I/O modules, 433
LED indicators for bi-directional
xxvii
Index
LED indicators for discrete 12 point modules with fault indication, 436 primary keys, 437 secondary keying and backplane position codes, 439 terminal strip key codes, 437 terminal strip/module keying, 436 intelligent/special purpose I/O modules
InterBus interface modules
communication interface modules, 10
Intrinsically safe analog input module
intrinsically safe analog output module
intrinsically safe current input module
intrinsically safe discrete input module
intrinsically safe discrete output module
intrinsically safe modules
identification and labeling, 363
installation, 362 intrinsic safety, 362 safe barriers, 362
safe wiring practices, 363 wiring and grounding, 363
L
local I/O
local I/O configuration
description, 20 illustration, 20
LonWorks modules
communication interface modules, 10
xxviii
M
miscellaneous components battery, 664 cable connector orientation, 660 cables, 659 coding kit, 660
CPU battery, 664 description, 659 empty module, 660 empty module with door cover, 661 field wiring terminal strip, 662
I/O conversion connector, 666
IP 20 compliant field wiring terminal strips, 663
Modbus Plus ruggedized tap, 665
Modbus Plus tap, 664 remote I/O BNC connector, 667 remote I/O splitter, 667 remote I/O tap, 666
RG-11 remote I/O F connector, 667
RG-6 remote I/O F connector, 667 terminal strip jumper kit, 661
MMS interface
Modbus and Modbus Plus communications
Modbus communications
Modbus connector
Modbus connector pinouts
nine-pin connections, 176
MODBUS I/O Scanner functionality, 280
Modbus Plus communications
Modbus Plus network option modules
Modbus Plus on Fiber NOM25200, 245
840 USE 100 00 11/2004
module mounting procedure description, 686
I/O terminal strip mounting procedure, 689 illustration, 687 installing jumper clips, 688 removing Quantum module door, 690 mounting brackets
125 mm, 682
20 mm, 683 description, 681 part numbers, 681
MSX motion modules MSX10100, 342
MSX10100
(electrical specifications), 346
(operational specifications), 344
(electrical specifications), 346
(operational specifications), 345
(operational specifications), 343 communications
(operational specifications), 343
(operational specifications), 345
(operational specifications), 344
discrete inputs and high speed input
(electrical specifications), 346 discrete output
(electrical specifications), 346
(operational specifications), 344
(electrical specifications), 347
electrical specifications, 346
840 USE 100 00 11/2004
(electrical specifications), 347
high speed input (operational specifications), 344
incremental encoder feedback, 345
motor temperature input (electrical specifications), 347
operational specifications, 343
power requirements (electrical specifications), 347
resolver feedback (fully configured version), 345
resolver interface (electrical specifications), 346
Index
N
network interface techniques
CPU interface support, 33 description, 33 direct CPU driver, 33
network modules
NOA61110
NOA611X0
required loadables, 206 reset push button, 206
NOA62200
xxix
Index
NOE2X100
description, 266 illustration, 266
installation, 268 installation example, 268
NOE3X100
description, 270 illustration, 270
NOE5X100
description, 273 illustration, 273
NOE77100
peer cop based I/O scanner, 280
NOE771x0
NOE771x1
xxx
NOE771xx
enhanced MODBUS I/O scanner, 281
Quantum Ethernet TCP/IP modules, 281
NOL911X0
auxiliary LonWorks communication
primary LonWorks communication port, 211
RS-232 configuration port, 211
NOM modules
Modbus Plus on Fiber, 9 twisted-pair wiring, 9
NOM21X00
ASCII comm port parameters, 241
840 USE 100 00 11/2004
Modbus ports pinout connections for portable computers, 243
SW1 and SW2 address settings, 240
valid comm port parameters, 242
NOM25200
ASCII comm port parameters, 249
calculating modules in a fiber network, 264
fiber optic configurations, 256
hot standby systems example, 260
LED topology and descriptions, 247
materials for fiber optic links, 261
mixed fiber optic/copper network, 256
network status, 261 optical star passive couplers, 261
point-to-point configuration, 256
self healing ring configuration, 259
O
option module interface
network interface techniques, 33
840 USE 100 00 11/2004
Index
P
part numbers
ASCII interface module, 52 counter modules, 52
high speed interrupt module, 52
single axis motion modules, 52
Peer Cop
MODBUS I/O Scanner characteristics, 280
point-to-point configuration, 256
power and grounding considerations
125 Vdc powered systems, 700
AC powered systems, 693
AC powered systems for CE compliance, 696
CE compliance installation instructions for AC systems, 695
CE compliance installation instructions for Vdc systems, 698
DC powered systems, 694 description, 692 power and grounding guidelines chassis grounding, 710
Modbus Plus communication tap installation for CE compliance, 710 other equipment grounding, 711
power supply ground connection, 710 systems with multiple power feeds, 711
power supplies compatibility issues, 709
description, 5, 703 modes, 5 redundant, 5
xxxi
Index
Q
Quantum Automation Series
block diagram, 4 capabilities, 4
Quantum configurations
description, 18 distributed I/O, 18 local I/O, 18 remote I/O, 18
Quantum editors
Quantum network support
Quantum simulator modules
R
redundant power supplies description, 707 register assignment
ACI03000, 446
ACI04000, 447
ARI03010, 449
ATI03000, 452
AVI03000, 457 remote I/O
RIO configuration
RIO drop modules CRA93X00, 230
RIO head modules CRP93X00, 226
RIO in a Hot Standby configuration
dual cable configuration illustration, 24
single cable configuration illustration, 23
RIO modules
communication interface modules, 9
xxxii
S
self healing ring configuration, 259
signal descriptions
single cable configuration
RIO in a Hot Standby configuration, 23
spare parts description, 670
840 USE 100 00 11/2004
specifications
ACI03000, 462
ACI04000, 465
ACO02000, 482
ACO13000, 486
ARI030010, 468
ATI03000, 470
AVI03000, 474
AVO02000, 489
CableFast, 717
CPS11100 (PV01 or greater), 64
DAI34000, 510
DAI35300, 513
DAI44000, 516
DAI45300, 519
DAI54000, 522
DAI54300, 524
DAI55300, 527
DAI74000, 531
840 USE 100 00 11/2004
DAI75300, 534
DAO84000, 564
DAO84010, 568
DAO84210, 572
DAO84220, 577
DAO85300, 582
DDI15310, 536
DDI35300, 538
DDI35310, 540
DDI36400, 542
DDI67300, 546
DDI84110, 551
DDI85300, 554
DDM39000, 646
DDM69000, 651
DDO15310, 587
DDO35300, 590
DDO35301, 594
DDO35310, 597
DDO36400, 601
DDO84300, 606
DDO88500, 609
DRA84000, 613
DRC83000, 616
DSI35300, 632
DVO85300, 625
standalone power supplies models, 704 summable power supplies description, 705
Index xxxiii
Index system configurations
system space requirements dimensions, 684 illustration, 685 locations, 684 minimum spacing, 684 system specifications
description, 43 electrical, 43
(between 24 and 48 Vac or Vdc), 44
(greater than 48 Vac or Vdc), 44
operating conditions, 45 storage conditions, 45
T
Telefast Input DDI36400, 542
Telefast Output DDO36400, 601 terminal strip/module keying description, 436 illustration, 437 primary keying, 436 secondary keying, 437
V
version levels
DDM69000, 654 xxxiv
W
wiring diagram
140 CFA 040 00, 723
140 CFB 032 00, 725
140 CFD 032 00, 734
140 CFG 016 00, 738, 739, 740, 741
140 CFH 008 00, 743
ACI03000, 463
ACI04000, 466
ACO02000, 484
ACO13000, 488
AMM09000, 502
ARI03010, 469
ATI03000, 472
AVI03000, 476
AVO02000, 492
CFC03200, 729
CFI00800, 747
CFJ00400, 751
CFK00400, 755, 756, 757
CPS11100 (PV01 or greater), 65
DAI34000, 511
DAI35300, 514
DAI44000, 517
DAI45300, 520
DAI54000, 523
DAI54300, 525
DAI55300, 528
840 USE 100 00 11/2004
DAI74000, 532
DAI75300, 535
DAM59000, 644
DAO84000, 566
DAO84010, 570, 575
DAO84220, 580
DAO85300, 584
DDI15310, 537
DDI35300, 539
DDI35310, 541
DDI67300, 549
DDI84110, 552
DDI85300, 555
DDM39000, 650
DDM69000, 655
DDO15310, 589
DDO35300, 593
DDO35301, 596
DDO35310, 600
DDO84300, 608
DDO88500, 612
DRA84000, 615
DRC83000, 618
DSI35300, 633
DVO85300, 628
intrinsically safe modules, 365
X
XBE10000
configuration illustration, 354
840 USE 100 00 11/2004
Index
XCP90000
description, 423 illustration, 423
installing and removing a battery, 425
XSM00200
description, 416 illustration, 416
XSM01000
description, 417 illustration, 417
xxxv
Index xxxvi
840 USE 100 00 11/2004