Schneider Electric Software PLC Application-Specific Functions, Junior/Pro, 4.5 User Guide
Advertisement
Advertisement
PL7 Junior/Pro
Premium PLC Applications
Process control
eng May 2007
2
35012329 02 May 2007
Document Set
Document set This manual consists of 8 volumes: z Volume 1 z z
Shared application-specific functions
Discrete application z z z
AS-i installation
MMI application
Volume 2 z Counting application z z z z
Volume 3 z Axis command application
Volume 4 z Step by step axis command application
Volume 5 z Electronic cam application
Volume 6 z SERCOS(r) application z z
Volume 7 z Analog application z z
PID control application
Weighing application
Volume 8 z Process control application
35012329 02 May 2007
3
Document Set
4
35012329 02 May 2007
Table of Contents
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Part I
Introduction to the process control application . . . . . . 13
Chapter 1
Process control in an automated system. . . . . . . . . . . . . . . . . 15
The place of the process control application in an automation application . . . . . 15
Chapter 2
Hardware and software introduction . . . . . . . . . . . . . . . . . . . . 17
2.1
Features of Processors with built-in process control. . . . . . . . . . . . . . . . . . . . . . 19
2.2
How to access process control application parametering . . . . . . . . . . . . . . . . . . 23
Description of loop controller parametering screens . . . . . . . . . . . . . . . . . . . . . . 25
2.3
Chapter 3
Procedure for installing a process control . . . . . . . . . . . . . . . 37
Part II
Installing the process control application . . . . . . . . . . . 41
Chapter 4
Introduction to loop controllers . . . . . . . . . . . . . . . . . . . . . . . . 43
4.1
35012329 02 May 2007
5
6
4.2
4.3
The Split Range or Heat / Cool (PID or IMC) loop controller . . . . . . . . . . . . . . . . 64
4.4
Guaranteed dwell time of a setpoint programmer . . . . . . . . . . . . . . . . . . . . . . . . 74
How to link a setpoint programmer to a control loop . . . . . . . . . . . . . . . . . . . . . . 82
4.5
Description of the global parameters of process control loops . . . . . . . . . . . . . . 85
Chapter 5
Calculation functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
5.1
35012329 02 May 2007
5.2
5.3
5.4
5.5
Operating process examples of the Servo function. . . . . . . . . . . . . . . . . . . . . . 173
Chapter 6
Control loop configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
6.1
Configuring the inputs and outputs associated with the process control loops . 186
35012329 02 May 2007
7
8
6.2
Configuring MMI ( Man-Machine Interface) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
How to associate the process control loops to the MMI
Chapter 7
Control loop adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
7.1
7.2
Role and influence of the parameters of a PID during a loop adjustment . . . . . 208
7.3
Steps to follow to adjust the model loop controller. . . . . . . . . . . . . . . . . . . . . . . 213
Instructions for adjusting dead time or delay T_DELAY . . . . . . . . . . . . . . . . . . 215
Chapter 8
Debugging a process control loop. . . . . . . . . . . . . . . . . . . . . 219
Chapter 9
Operating the process control loops . . . . . . . . . . . . . . . . . . . 227
9.1
9.2
35012329 02 May 2007
Setpoint programmer adjustment screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248
9.3
XBT-F02 and TXBT-F02 process control screens . . . . . . . . . . . . . . . . . . . . . . 250
Setpoint programmer adjustment screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262
9.4
Parameter setting zone for a setpoint programmer. . . . . . . . . . . . . . . . . . . . . . 278
Chapter 10
Operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 285
10.1
10.2
Handling process control operations according to PLC operating mode . . . . . 290
Handling process control operations according to the PLC operating mode . . 290
10.3
Common operating modes for process control loops . . . . . . . . . . . . . . . . . . . . 292
Loop execution in manual and automatic modes . . . . . . . . . . . . . . . . . . . . . . . 293
Auto / Manual and Manual / Auto switching . . . . . . . . . . . . . . . . . . . . . . . . . . . 295
10.4
Operating modes for each process control loop . . . . . . . . . . . . . . . . . . . . . . . . 297
Single loop operating modes (3 single loops) . . . . . . . . . . . . . . . . . . . . . . . . . . 299
35012329 02 May 2007
9
10
Chapter 11
Process control language objects . . . . . . . . . . . . . . . . . . . . . 307
11.1
Language objects associated with the process control channels . . . . . . . . . . . 308
Setpoint programmer command word (%MWxy.i.7) . . . . . . . . . . . . . . . . . . . . . 318
Summary of selection and command words . . . . . . . . . . . . . . . . . . . . . . . . . . . 319
11.2
Language objects associated with the process loop . . . . . . . . . . . . . . . . . . . . . 320
11.3
Language objects associated with the 3 single loops . . . . . . . . . . . . . . . . . . . . 337
11.4
Language objects associated with the single loop cascade . . . . . . . . . . . . . . . 359
11.5
Language objects associated with the self-selective loop . . . . . . . . . . . . . . . . . 380
11.6
Language objects associated with the setpoint programmer. . . . . . . . . . . . . . . 402
Fault and Diagnostics Language Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 412
35012329 02 May 2007
About the Book
At a Glance
Document Scope This manual describes the software installation of the process control application in
Premium PLCs: PMX version < 5.0 and TSX version > 5.0.
Validity Note The update of this documentation takes into account the functionalities of PL7 V4.5.
However, it can also be used for the implementation of earlier versions of PL7.
Related
Documents
Title of Documentation
Hardware installation manual
Reference Number
TSX DM 57E
User Comments We welcome your comments about this document. You can reach us by e-mail at [email protected].
35012329 02 May 2007
11
About the Book
12
35012329 02 May 2007
Introduction to the process control application
I
At a Glance
Subject of this part
What's in this
Part?
This part introduces the principles of process control and the associated software and hardware solutions.
This part contains the following chapters:
Chapter
1
2
3
Chapter Name
Process control in an automated system
Hardware and software introduction
Procedure for installing a process control
Page
13
35012329 02 May 2007
Introduction
14
35012329 02 May 2007
Process control in an automated system
1
The place of the process control application in an automation application
General introduction
Introduction to the operator dialog
In Premium processors prior to version 5.0, the process control application was integrated in the processors with references PMX… In version 5.0 and above, the process control application is integrated as standard in the TSX and PCX CPUs
(See
Features of Processors with built-in process control, p. 19 ).
Processors possessing process control functionality software channels called process control channels which can be configured in order to perform process control algorithms for industrial processes.
z z
The processes are as follows: process loop, cascade loop, z z auto selector loop, z single control loop, setpoint programmer.
The input/output interfaces required for process control processing are the analog or discrete module channels of the PLC.
Control loop parameters are set during processor configuration via the application screens.
z z z
The operator dialog needed for all process control is carried out via the:
PL7 debug and adjustment screens, graphical pages of the magelis XBT-F Man-Machine interface terminals, graphical pages of the TXBT Windows Man-Machine Interface terminals.
15
35012329 02 May 2007
Introduction to process control in an automated system
16
35012329 02 May 2007
Hardware and software introduction
2
At a Glance
Subject of this chapter
What's in this
Chapter?
This chapter introduces the hardware solutions, which allow the implementation of the process control application, built-in to the Premium programmable PLCs.
This chapter contains the following sections:
Section
2.1
2.2
2.3
Topic
Introduction to the process control processors
Introduction to the process control software tools
Compatibility
Page
17
35012329 02 May 2007
Hardware and software introduction
18
35012329 02 May 2007
2.1
Hardware and software introduction
Introduction to the process control processors
Features of Processors with built-in process control
At a Glance
Processor features
Processors used for process control have the same technical features as those described in the standard hardware manual. The features specific to process control are: z z
The number of process control channels,
The process control functions supported.
This table gives the references and features of the processors, which support the process control functions.
References Process control functions Number of process control channels
10 TSX P57 203/2623
TSX P57 253/2823
TSX P57 303/3623
TSX P57 353
TSX P57 453/4823
T PCX 57 203
T PCX 57 353
15
20
15
Process loop
Setpoint programmer
3 single loops
Cascade loop
Auto selector loop
35012329 02 May 2007
19
Hardware and software introduction
2.2
Introduction to the process control software tools
At a Glance
Subject of this
Section
What's in this
Section?
This section introduces the PL7, XBT and run-time screens editor software used to install the process control application.
This section contains the following topics:
Topic
How to select and configure the processor
How to access process control application parametering
Description of loop controller parametering screens
Runtime screens adjustment tools
Operating control loops with XBT terminals
Autotuning the control loops
Setpoint programmer
Page
20
35012329 02 May 2007
Hardware and software introduction
How to select and configure the processor
At a Glance Software installation generic to the applications is described in the manual Common functions ((see PL7 Junior/Pro Modicon Premium PLC Applications Standard applications)). However the specifics, such as the selection of the processor and its configuration, are described here.
Note: using process control in an application imposes a MAST task of the periodic type.
How to select the processor
This table describes the procedure for selecting the processor.
Step
1
Action
Select the command File
→
New…
Result : the following screen appears.
New
Micro
Premium
Processors :
PCX 571012V3.0...
PCX 573512V3.0...
PMX 57102 V3.0.
..
TSX 5710 V1.5...
TSX 57102 V3.0...
TSX 5720 V1.5...
TSX 57202 V3.0...
TSX 57252 V3.0...
TSX 57302 V3.0...
Memory cards :
None
32 Kmots
64 Kmots
2
3
OK
Cancel
Select Premium plus the desired processor type and version which has the process control application built-in (see Features of Processors with built-in
).
Confirm your selection by clicking on OK .
Result : the PL7 software creates a new application with the selected processor.
35012329 02 May 2007
21
Hardware and software introduction
How to configure the processor
This table describes how to configure a periodic MAST task.
Step
1
Action
Open the hardware configuration editor from the application browser .
Result : the following screen appears.
Configuration
PMX 57102 V3.0
XMWI
XTI..
2 3 4
0
0
0
2
6
P
S
Y
0
P
M
X
1
0
5
7
2
1
1
2 Double click on the processor module (avoid the Loops, Fipio or Comm zones).
Result : the following screen appears.
PMX 57102 [RACK 0 POSITION 0]
Configuration
Designation: PROCESSEUR PMX 57102
Operating mode
Run/Stop input
Automatic start inRun
%MWi reset on cold start
Memory card
None
Tasks
MAST
Cyclic
Periodic
Watchdog
FAST
Période :
Watchdog
250
20 ms ms
Fipio mode
Network cycle time (calculated)
Controlled
Free ms
100
5 ms ms
Fipio mode
Network cycle time (calculated)
Controlled
Free ms
3
4
In the MAST tasks zone, select the Periodic button and indicate the period value in ms.
Confirm the modification by clicking on the enable icon in the toolbar:
22
35012329 02 May 2007
Hardware and software introduction
How to access process control application parametering
At a Glance The method of software installation for process control channels is the same as that used for PL7 application specific functions.
An application specific function has: z z z dedicated screens, specific instructions, language objects (see
Process control language objects, p. 307
).
Installation of a process control starts with accessing the parametering screens, consisting of: z z configuration screens (in offline and online mode), debug screens (in online mode).
35012329 02 May 2007
23
Hardware and software introduction
How to access the configuration screen
What to do to access the configuration screen
Step
1
Action
Open the hardware configuration editor from the application browser .
Result : the following screen appears.
Configuration
PMX 57102 V3.0 XMWI
XTI..
0
2
6
0
0
P
S
Y
0
P
M
X
5
7
1
0
2
1 2 3 4
1
2 Double click on the Loops zone in the processor module.
Result : the following screen appears, the zone not displayed here is empty.
PMX 57102 [RACK 0 POSITION 0 ]
Configuration
Désignation : PROCESSEUR PMX P 57102
Configuration du DOP
Symbole :
Régulateur :
Régulateur4
Fonction :
Aucune
3 Select a loop controller and an associated function.
Result : a description of the control loop and its features (see Description of
loop controller parametering screens, p. 25
) appears.
24
35012329 02 May 2007
Hardware and software introduction
Description of loop controller parametering screens
At a Glance There are two types of loop control parametering screens: z z configuration screens, debug screens.
Illustration of the configuration screen
The configuration screen is as follows.
1
PMX 57102 [RACK 0 POSITION 0]
Configuration
Designation: PROCESSOR PMX P 57102
DOP configuration
2
Symbol:
Loop Controller:
Loop controller4 - LOOP0
Function:
Process loop
3
LOOP 0
Loop
Loop parameters
Process value
Setpoint
Loop controller
Feed Forward
Output 1
Standard
Single
PID
No
Analog
Functions
Instrumentation
Execution
Parameters
Loop name
Unit
Low scale (phy.)
High scale (phy.)
PV
SP1
R
L
0.0
I
P
D
0.0
LOOP0
0.0
100.0
OUT 1
35012329 02 May 2007
25
Hardware and software introduction
Description of the configuration screen
The configuration screen is made up of three zones.
Zone
1
2
3
Description
Module zone: this zone indicates the module concerned,
Here the processor module as well as the type of screen: Configuration .
Channel zone: this zone has a menu for selecting a loop controller, as well as z z z z z a menu for selecting the function to be associated with the loop controller: a process loop, a cascade loop, an auto selector loop, three single loops, a setpoint programmer.
Parametering zone: this zone is used to select the calculation functions of each z z processing branch. It consists of: a function selection zone, a display and parametering zone for the loop controller block diagram.
Illustration of the debug screen.
The following is the debug screen.
PMX 57102 [RACK 0 POSITION 0]
Debug
Designation: PROCESSOR PMX P 57102
DOP configuration
Symbol:
Loop Controller: Function:
Loop controller4 - LOOP0 Process loop
Alarms
DL DH LL L H HH
LOOP 0
Loop
Loop parameters
Process value
Setpoint
Loop controller
Feed Forward
Output 1
Loop Scale
Low: 0.0
PV
5000
SP1
63.0
Standard
Single
Heat / Cool
Yes
Analog
High: 100.0
R
L
45.0
44.845
FF
3547 LL 35.47
Functions
Format
Filter
Fct generator
Alarms
Simulation
I
P
D
Parameters
Time constant (s)
Gain
Output
28.585
0.0
10.0
1.0
4484.536
DIAG...
DIAG...
WARNING
OUT 1
2858
0
OUT 2
26
35012329 02 May 2007
Hardware and software introduction
Utilities which can be accessed via the debug screen:
The following are the utilities that can be accessed via the debug screen: z z z z z simulation of input values (process value, Feed forward, etc ), animation of the block diagram, modification of the adjustment parameters of calculation functions, modification and saving of all parameters, sending of autotuning and manual commands, etc.
35012329 02 May 2007
27
Hardware and software introduction
Runtime screens adjustment tools
At a Glance The runtime screens editor allows the use of bar charts and specific library objects for the operation of control loops. Animation is automatic and is a simple process.
To find out which objects are available and how to use them, please refer to the
Runtime screens editor user manual ((see Runtime screens editor User manual)).
Example of the adjustment tools
Example of the process control interfaces offered by the runtime screens editor.
S/R Cascade
R
Text
R
L
ON OFF 3
R L
C O
A M
PV SP OV1 OV2
A
Text
PV
SP
0.000
0.000
SP Internal
Unit
OUT
1
*xxxxx
0.00
2 0.00
M
THRESHOLD HIGH
THRESHOLD LOW
HYST
0.000
0.000
0.000
PV
SP
OUT
0.000
Unit
0.000
0 0 1 OUT 0 0 1
Auto Selective C P I D
Kp
Ti (s )
Td (s.)
0.000
0.000
0.000
Te (s )
OUTBIAS
DBAND
0.000
0.000
0.000
PV
SP
OUT
0.000
0.000
#xxxx.x
Unit
R L
F
AS C
A M
28
35012329 02 May 2007
Hardware and software introduction
Operating control loops with XBT terminals
At a Glance
Control page
Some Magelis XBT-F terminals are able to manage control loops.
Note: when these tools are used, to make the XBT/PLC dialog transparent, exchanges are made by default in the word zones %MW3228 to %MW3242 and
%MW3350 to %MW4090 (see
Using the Man-Machine Interface, p. 192
).
In addition to the services offered by the XBT-L1000 software and the Magelis terminals, the XBT-F terminal offers specialized pages to manage each control loop: z z z z z control page, operating page, adjustment page, monitoring page, alarm page.
Control pages are used to control each control loop, manual mode, automatic mode, autotuning, etc.
TC_0001
AUTO
10000-
H DH LOCAL
AT
PV
SP
OV
:
:
:
96.00
65.00
31.00
AM
0-
2
OV1 :
Alarm page 1
31.00
IR
ON
35012329 02 May 2007
29
Hardware and software introduction
Operating page Operating pages are used to display the evolution of the setpoint and measurement.
TC_0001
AUTO H DH LOCAL
PV
SP :
: 96.00
65.00
2
AM
OV
OV1 :
: 31.00
31.00
Alarm page 1
LK
ON
Adjustment page Adjustment pages are used to adjust the parameters of each loop: process control coefficients, limits, etc.
AT
TC_0001
AUTO
KP
TI (s)
TD (s)
O_BIAS
DBAND
KD
ORATE1
:
:
:
:
:
:
:
H
1.0
0.0
0.0
0.0
0.0
10.0
0.0
DH
SP_SUP
SP_INF
TS (s)
PV_H
PV_L
INTBND :
:
:
:
:
:
:
LOCAL
100.0
0.0
0.30
95.0
5.0
0.0
Sa
2 Alarm page 1 ON
30
35012329 02 May 2007
Hardware and software introduction
Monitoring page The monitoring page groups together the main information about the control loop process. It is the process control operating input screen. It is used to access each loop’s operating pages.
AUTO TC_0003 LOCAL
100.0
AT
Alarm page
1/8
Pr
Ack
9/16
Sa
26mn
KP
TI (s)
TD (s)
O_BIAS
DBAND
INTBND
KD
2
2
:
:
:
:
:
:
:
20mn
1.0
0.0
0.0
0.0
0.0
0.0
10.0
Loop 1 Alarm (s)
KP Pr
TI Pr
TD Pr
ATSTEP
ATTMAX
ATPERF
:
:
:
:
:
:
10mn
1.0
0.0
0.0
10.00.
100.0.
0.50
SP_SUP
SP_INF
TS (s)
PV_H
PV_L
ORATE1
:
:
:
:
:
:
100.0
0.0
0.0
0.30
95.0
PV
SP
OV
5.0
0.0
OV1
06/05/98
:
:
:
:
:
60.0
20.0
40.0
40.0
DH
15:01:29
06/051998
ON
AM
LR
15:41
The alarm pages are linked to each loop (HH, H, L, LL). They are integrated into XBT alarm management.
D H
N°1
AT
3
4
5
1
2
6
7
8
TC_0001
TC_0002
TC_0003
L
L
SPP
2 Alarm page 1 ON
35012329 02 May 2007
31
Hardware and software introduction
Autotuning the control loops
At a Glance Autotuning is applied to most of the processes, such as temperature regulation, flow regulation, pressure regulation, etc.
The loop controllers built into these control loops are used to calculate a set of adjustment parameters (Kp, Ti, Td) on autotune request.
These parameters can be accessed via: z z z
PL7 debug screens, an animation table, an adjustment screen specific to an XBT-F terminal.
XBT-F autotuning page
This page is used to autotune a control loop.
TC_0001
AUTO
KP
TI
TD :
:
:
H DH
ACTUAL
1.0
0.0
0.0
LOCAL
PREV
1.0
0.0
0.0
Step
Tmax (s)
Perf
:
:
:
10.0
100.0
0.50
2 Alarm page 1
AT
Sa
Pr
ON
32
35012329 02 May 2007
Hardware and software introduction
Setpoint programmer
At a Glance All process control channels can be configured using the setpoint programmer.
The features of a setpoint programmer are as follows: z z z
1 to 6 profiles, a maximum of 48 segments distributed over the configured profiles,
Profiles can be assigned to several control loops.
Note: when the setpoint programmer is interfaced to a single loop, the PV measurement tracking function can be used.
Note: the XBT-F terminal offers an adjustment page and an operating page specifically for the setpoint programmer. These pages are used to modify the desired setpoint profiles.
35012329 02 May 2007
33
Hardware and software introduction
Configuration screen for a setpoint programmer
Profiles are assigned to a control loop via a configuration screen.
PMX 57352 [RACK 0 POSITION 0]
Configuration
Designation: PROCESSOR PMX P 57352
Loop controller 5 - SPP_1
Name: SPP_1
Function:
Setpoint programmer
Task:
MAST
Segmentation:
8-8-8-8-8-8
PROFIL_1 PROFIL_2 PROFIL_3
Segments Execution
3
4
1
2
Guaranteed Dwell Time at threshold 5.0
Segment x SP x VAL x
Ramp
Stage
Ramp
Stage
50.0
50.0
80.0
80.0
40.0
20.0
40.0
40.0
PROFIL_4 PROFIL_5 PROFIL_6
Number of segments: 8 on 8
Deviation on input
Pq S0 S1 S2 S3 S4 S5 S6 S7 Unit
Second
Second
Second
Second on
PV %MF24
80.0
DOP configuration
34
35012329 02 May 2007
Hardware and software introduction
2.3
Compatibility
Compatibility
Description There is ascending compatibility between all of the following PMX P57 and TSX P57 processors: z z z
TSX P57 203/2623/253/2823,
TSX P57 303/303A/3623/3623A/353/353A,
TSX P57 453/453A/4823/4823A.
All applications from a PMX P57 processor are compatible with the abovementioned
TSX P57 processors.
35012329 02 May 2007
35
Hardware and software introduction
36
35012329 02 May 2007
Procedure for installing a process control
3
At a Glance
Subject of this chapter
What's in this
Chapter?
This chapter describes the steps required to install a process control with the aid of a Premium processor with the process control application built-in and an XBT terminal.
This chapter contains the following topics:
Topic
How to install a process control using PL7
How to install a process control with an XBT
Page
37
35012329 02 May 2007
Procedure for installing a process control
How to install a process control using PL7
At a Glance
Procedure with
PL7
Installing a process control involves a certain number of steps as described in the following procedure.
This table describes the steps to be carried out to install a process control using the
PL7 software.
Step
1
2
3
4
5
6
7
Action Mode z z
Configure the processor using the application browser.
Hardware configuration
Software configuration z z z z
Configure the process control channels.
Select type of loop
Select calculation functions
Enter the configuration parameters
...
If necessary, symbolize the variables associated with the control loops using the variables editor.
PL7 offline
Program the PLC applications by creating specialized program sections.
PL7 on or offline
Transfer the application to the PLC to debug the program and each application-specific function (I/O, process control, communication etc.).
Debug and adjust the control loops by modifying and saving the values of the control loop adjustment parameters.
PL7 online
Print the application documentation that contains information relating to the different application-specific functions (including process control functions): configuration parameters, adjustment parameters, etc.
PL7 on or offline
38
35012329 02 May 2007
Procedure for installing a process control
How to install a process control with an XBT
At a Glance An XBT terminal is generally used to install the Man-Machine interface in a process control. Process control algorithms, acquisition and command are carried out via and adjustment, operation and monitoring are carried out via the graphic pages of an XBT-F. The steps of this installation are shown in the following table.
Procedure using an XBT
This table describes the steps to follow to install a process control using an XBT terminal.
Step
1
2
3
4
Action
Program the XBT application using the XBT-L1000 software, the directory tree of pages, contents, dialog tables, etc.
Transfer the application to the XBT in order to debug the control loops.
Debug and adjust the control loops by modifying and saving the control loop adjustment parameter values, using the preset pages and XBT application pages.
Work in runtime in order to control the process loops of the machine using the
XBT preset pages.
35012329 02 May 2007
39
Procedure for installing a process control
40
35012329 02 May 2007
Installing the process control application
II
At a Glance
Aim of this Part
What's in this
Part?
This part describes the different control loops and functions, as well as their installation, from configuration to debugging.
This part contains the following chapters:
Chapter
4
5
6
7
8
9
10
11
Chapter Name
Introduction to loop controllers
Calculation functions
Control loop configuration
Control loop adjustment
Debugging a process control loop
Operating the process control loops
Operating modes
Process control language objects
Page
35012329 02 May 2007
41
Installation
42
35012329 02 May 2007
Introduction to loop controllers
4
At a Glance
Subject of this
Chapter
What's in this
Chapter?
z z z z
This chapter introduces the different loop controllers: types, structure, processing branches, parameters.
This chapter contains the following sections:
Section
4.1
4.2
4.3
4.4
4.5
Topic
Definition and structure of a loop controller
Description of the types of loop controllers
Description of the processing branches
The setpoint programmer
Global parameters of control loops
Page
35012329 02 May 2007
43
Introduction to loop controllers
4.1
Definition and structure of a loop controller
Structure of loop controllers
At a Glance
Illustration
Loop controller is a generic term used to designate a processor process control channel. A loop controller can be made up of several control loops.
Example: a master loop and a slave loop.
A loop controller is thus made up of control loops, themselves made up of: z branches or blocks (process value processing, etc.) made up of: z calculation functions (gain, filtering, square root, etc.) which are defined by a certain number of parameters.
The PL7 configuration screen is allows you to carry out this hierarchical breakdown.
This figure represents a configuration screen, which allows this hierarchical breakdown, as well as the parametering of the process control channels.
1
Loop Controller (Channel)
3 Loop
4
Branch
Process control type
7
Loop schema
5
Function
2
Parameter
6
Description This table describes the hierarchical structure of a process control channel.
Number
1
2
3
6
7
4
5
Description
Module zone (processor)
Channel or loop controller zone
Loop tab
List of branches
List of functions
List of parameters
Process control loop block diagram
44
35012329 02 May 2007
4.2
Introduction to loop controllers
Description of the types of loop controllers
At a Glance
Subject of this
Section
What's in this
Section?
This section introduces the different loop controllers as well as their structure.
This section contains the following topics:
Topic
Types of process control
Introduction to the process loop
Introducing the single loop
Introduction to the cascade loop
Introduction to the Auto Selector loop
Page
35012329 02 May 2007
45
Introduction to loop controllers
Types of process control
At a Glance For a process control channel, it is possible to select from 5 predefined profiles: z z z a process loop, three single loops, z z a cascade loop, an auto selector loop, a setpoint programmer (See
The setpoint programmer, p. 71
).
Each loop offers default parameters, with the exception of the setpoint programmer.
The use of the different functions built into the algorithms (square root, function generator, etc.) is predefined, as is the initial value of each parameter.
Description of the control loops
The control loops are made up 5 processing branches which will create the required z z algorithm: the process value processing branch, the Feed forward processing branch, z z the setpoint processing branch, z the loop controller branch, the output processing branch.
The operation of each processing branch (See Description of the processing
branches, p. 51 ) is the same, irrespective of the process control type which is
selected.
46
35012329 02 May 2007
Introduction to loop controllers
Introduction to the process loop
At a Glance
Loop diagram
The process loop is a loop with only one loop controller.
This schema illustrates the process paths of the process loop.
Autotuning
Setpoint
Processing setpoint
Process value
Processing process value
Feed forward
Processing
Feed forward
Loop controller and command processing
Auto
Manual
Processing output
Manual command
Tracking
35012329 02 May 2007
47
Introduction to loop controllers
Introducing the single loop
At a Glance
Loop diagram
The single loop profile automatically links three single loops to the loop controller, in order to increase the number of loops. These loops operate independently of each other.
This schema illustrates the process branches for the single loop.
Autotuning
Setpoint
Processing setpoint
Process value
Processing process value
Loop controller and command processing
Auto
Manual
Processing output
Manual command
Tracking
48
35012329 02 May 2007
Introduction to loop controllers
Introduction to the cascade loop
At a Glance
Loop diagram
The cascade loop is made up of two dependent loops: a master loop and a slave loop. The master loop output is the setpoint for the slave loop.
This schema illustrates the process paths of the cascade loop.
Autotuning
Setpoint
Processing setpoint
Process value
Processing process value
Loop controller and command processing
Autotuning
Setpoint
Process value
Loop controller and command processing
Processing
Feed forward
Feed forward
Manual command
Manual command
Tracking
Output
35012329 02 May 2007
49
Introduction to loop controllers
Introduction to the Auto Selector loop
At a Glance
Loop diagram
The Auto Selector loop, which is also called the restricted loop is made up of two z z parallel loops: the main loop, the secondary loop.
The output is selected according to a precise algorithm.
The secondary loop is a single loop.
This schema illustrates the process paths of the Auto Selector loop.
Autotuning
Setpoint
Process value
Feed forward
Setpoint
Process value
Manual command
Tracking
Processing setpoint
Processing process value
Feed forward
Processing setpoint
Processing process value
Loop controller and processing command
Autotuning
Loop controller and processing command
C
T
I
O
N
L
E
S
E
Processing output
50
35012329 02 May 2007
4.3
Introduction to loop controllers
Description of the processing branches
At a Glance
Subject of this
Section
What's in this
Section?
This section introduces the different processing branches that make up the loop controller loops.
This section contains the following topics:
Topic
Introduction to built-in functions
Process value processing branch
Setpoint processing branch
Feed forward processing branch
Loop controller and command branch
The ON OFF 2 or 3 states loop controller
The PID or IMC loop controller
The Split Range or Heat / Cool (PID or IMC) loop controller
Output processing branch
Servo drive output branch
PWM branch output
Loops summary table
Page
35012329 02 May 2007
51
Introduction to loop controllers
Introduction to built-in functions
At a Glance
Process value branch
The processing branches each have calculation functions built-in. These calculation functions are represented in the block diagram by icons. Each type of branch has specific calculation functions.
List of calculation functions.
Icon Description
First order filtering
Square root
Function generator
Scale limiter
=
= Alarms on level
Totalizer
Set to scale
52
35012329 02 May 2007
Setpoint branch List of calculation functions.
Icon Description
Selection
Ratio
Setpoint limiter
SP
Track
Process value setpoint tracker
Speed limiter
Set to scale
Introduction to loop controllers
35012329 02 May 2007
53
Introduction to loop controllers
Loop controller List of calculation functions.
Icon Description
2 state ON OFF
3 state ON OFF
I
P
D
I
M
C
1 2
I
P
D
I
M
C
1 2
I
M
C
I
P
D
PID
Internal model loop controller
Heat / Cool
Split Range
Feed Forward branch
List of calculation functions.
Icon Description
Set to scale
LL Leadlag
54
35012329 02 May 2007
Output loop controller
List of calculation functions.
Icon Description
Set to scale
Analog output
Servo drive output
M
PWM
Pulse output
Output limiter
Introduction to loop controllers
35012329 02 May 2007
55
Introduction to loop controllers
Process value processing branch
At a Glance
Standard process value z z
There are two types of process value:
Standard process value,
External process value.
The external process value allows you to input to the loop controller a process value
PV which has been processed outside the control loop. This solution is offered for cases where calculation of the process value requires specific or customized functions which are not available in standard process value processing.
Block diagram of the standard process value branch.
%MW,
%IWxy.i
Simulation
PV_SIM
Filter
FILT_OUT SQR_OUT
Function generator
Scales
Totalizer
Limiter
Alarms
OUT_TOT
PV z z z z z z
The first order filtering function has a gain coefficient.
There are four thresholds for the Alarms on process value block with a hysteresis of 1% of the full scale.
Two input formats may be used: unipolar or bipolar.
There is no bump when switching to simulated mode; the initial simulation value retained is the last process value read.
The function generator has scaling built-in.
It is possible to limit the process value to the scale limits.
External process value
Block diagram of the external process value branch.
Simulation
%MF,
%MFxy.i
Totalizer
Limiter
Alarms
OUT_TOT
PV
56
35012329 02 May 2007
Introduction to loop controllers
How the initialization works z z z
On start-up, the associated data is first updated before the launch of the first process of this branch.
If the process value input address is not set, processing is performed on the simulated value initially set to zero.
On initialization, there is a consistency check on the configuration entered. If there is a problem with the configuration, the loop remains in a state of initialization.
Operation of execution check
The two serious faults checked by process value processing are parameter and internal calculation errors (division by zero, overflow, etc.).
If … a serious error has been detected the error disappears there is a serious error on process value processing during a cold start the scale values are incorrect (nonfloating value) during a cold start
Then … the loop processing switches to fallback state : z the value of the calculated process value PV is frozen, z the control loop outputs are frozen.
the loop resumes in the previous operating mode, without bumps on the outputs.
the loop remains in its initialization position and does not start.
the loop remains in its initialization position and does not start.
following an error, the loop remains in its initialization position and does not start.
the problem must be eliminated so that it will start automatically.
there is an error on the scale values during operation.
the process value processing is performed with the former, correct scale values which are replaced in the current parameters of the scale. The scale parameters are updated when the check is correct.
35012329 02 May 2007
57
Introduction to loop controllers
Setpoint processing branch
At a Glance
Definition
There are four types of setpoint: z z z the ratio setpoint, the selection setpoint, z the single setpoint (remote with scaling), the setpoint programmer.
Only the two last setpoints can be used with the 3 single loops or the Auto Selector loop.
A local setpoint is a setpoint written by a Man-Machine Interface.
A remote setpoint is a setpoint produced by a process.
Block diagram of the branch
Block diagram of the setpoint processing branch.
Input
Remote 1
Input
Remote 2
Selection
Programmer
OR
Ratio
OR
Scale
OR
Scale
Remote/Local
Limiter
SP
Limiter speed
How the initialization works z z z z z
The local value tracks the value of the remote setpoint in order to avoid bumps on the change of operation.
If the address of the remote setpoint is not given, local mode is forced .
To avoid changes which are too abrupt, the speed of the setpoint can be limited.
By default, the setpoint is limited to the loop scale. A more restrictive limit can be fixed.
When the loop controller is in manual mode, the setpoint can track the process value.
z z z
On start-up, the associated data is first updated before the launch of the first process of this branch.
If the process value input address is not set, processing is performed on the simulated value initially set to zero.
On initialization, there is a consistency check on the configuration entered. If there is a problem with the configuration, the loop remains in a state of initialization.
58
35012329 02 May 2007
Introduction to loop controllers
Operation of execution check z z
The two faults checked by setpoint processing are parameter errors (not written in floating point format) and internal calculation errors (division by zero, overflow, etc.). z z
When such a fault appears:
The result of the SP setpoint processing is frozen.
Warnings are displayed.
z These errors are not considered to be serious at the level of the control loop; loop controller and output value calculation is performed with the value of the frozen setpoint.
Calculation of the SP setpoint restarts as soon as the fault disappears.
Other faults associated with the built-in setpoint functions are indicated. They are detailed in the description of each function (See
Calculation functions, p. 87 ).
35012329 02 May 2007
59
Introduction to loop controllers
Feed forward processing branch
At a Glance In a classic process control using PID , the loop controller reacts to the variations to the process output (closed loop process control). For this reason, if there is a disruption, the loop controller does not begin to react until the process value moves away from the setpoint.
The Feed Forward function is used to compensate for a measurable disruption as soon as it appears.
This open loop function anticipates the effect of the disruption: this is therefore referred to as an anticipating action (or Feed forward).
Block diagram of the branch
Block diagram of the Feed forward processing branch.
Simulation
%MW,
%IWxy.i
FF_SIM Leadlag Scale OUT_FF
How the initialization works
If the Feed forward branch address is not defined, processing is performed on the simulated value initially set to zero.
Operation of execution check z z
The two faults checked by setpoint processing are parameter errors (not written in floating point format) and internal calculation errors (division by zero, overflow, etc.).
When such a fault appears: z The result of the processing of this setpoint is frozen.
z These errors are not considered to be serious at the level of the control loop, loop controller and output value calculation is performed with the frozen Feed forward z value.
Specific warnings are displayed.
The value OUT_FF on the loop controller input is updated as soon as the fault disappears.
Other faults associated with the built-in setpoint functions are indicated. They are detailed in the description of each function (See
Calculation functions, p. 87 ).
60
35012329 02 May 2007
Loop controller and command branch
At a Glance z z z z z z z
There are 8 types of loop controller:
Autotuning PID loop controller,
Discrete mode loop controller: z z
2 states,
3 states,
Heat/Cool PID loop controller,
Split Range PID loop controller,
Internal model loop controller,
Heat/Cool internal model loop controller,
Split Range internal model loop controller,
Introduction to loop controllers
35012329 02 May 2007
61
Introduction to loop controllers
The ON OFF 2 or 3 states loop controller
At a Glance This type of branch contains only the ON OFF function with 2 or 3 states according to the selection. It is available in the process loops and 3 single loops . When this type of branch is selected, there is neither an output branch, nor a Feed forward branch.
The loop controller output is copied into the status bit STS_RAISE1 for the ON OFF
2 states loop controller and also into the status bit STS_LOWER1 for the ON OFF 3 states loop controller.
The internal variables are updated by recognizing the previous value of the command.
Block diagram of the 2 states loop controller
Block diagram of the branch with an ON OFF 2 states loop controller.
Auto/Manu
PV
SP
ON OFF
2 states
STS_RAISE1 %M, %Q
Updating of internal variables
Block diagram of the 3 states loop controller
Block diagram of the branch with an ON OFF 3 states loop controller.
Auto/Manu
STS_RAISE1
PV
SP
ON OFF
3 states
STS_LOWER1
%M, %Q
%M, %Q
Updating of internal variables
62
35012329 02 May 2007
Introduction to loop controllers
The PID or IMC loop controller
At a Glance The diagram below illustrates the standard PID branch. There are variants, depending on the loops. Each variant is dealt with in the description of the different loops (See
Operating modes for each process control loop, p. 297 ).
For certain functions, the internal variables are updated by recognizing the previous value of the command. This enables switching to be made without bumps and enables integral action overflow to be avoided by recognizing the output limitations.
The output limitations apply in all loop controller operating modes.
Note: the RCPY input (external input address) only exists on the model loop controller.
Note: in manual mode, if the gradient limit is used, the OUT_MAN value (target value before limitation) may temporarily be different from the command applied on output.
Block diagram of the PID or IMC loop controller
Block diagram of the PID or IMC loop controller.
Updating of internal variables
Autotuning
Autotuning
Auto/Manu
PV
SP
RCPY
OUT_FF
TR_I
PID or
IMC
Tracking
Calculate enabling
OUT_SUP
Limiter
OUT_INF
OUT_MAN
OUTD
Gradient limiter
OUT_RATE
35012329 02 May 2007
63
Introduction to loop controllers
The Split Range or Heat / Cool (PID or IMC) loop controller
At a Glance The IMC function is identical to the IMC single loop controller.
The PID function is identical to the PID single loop controller.
The only differences are: z z z the absence of autotuning, the limiting of OUT_MAN between 0 and 100, the value of OUT_BIAS is fixed at 0 and cannot be parameterized.
The OUT_MAN command is recalibrated according to the limitations which are applied (as with a single PID), in order to avoid problems with overflow of the integral action and with the operation of the Split Range or Heat/Cool function.
Each output of the Split Range or Heat/Cool function has its own limitations with regard to level and gradient.
The operating mode acts on the output of the OUT_MAN loop controller.
Block diagram of the Split Range or Heat/Cool loop controller
Block diagram of the Split Range or Heat/Cool loop controller (PID or IMC).
PV
SP
RCPY
OUT_FF
TR_I
PID or
IMC
Auto/Manu
100.0
Limiter
0.0
OUT_MAN
Tracking
Split Range or
Heat / Cool
OUT_RATE
Gradient limiter
Gradient limiter
OUT_RATE2
OUT1_SUP
Limiter
OUT1_INF
OUT2_SUP
Limiter
OUT2_INF
OUT1
OUT2
How the initialization works z z z
There is a consistency check on the configuration selected. If there is a problem with the configuration: z the loop remains in initialization state, z the error is indicated in the status words.
On cold start-up, the parameters and input values PV, SP, etc. associated with this branch are first updated before the launch of the first loop controller process.
It is possible to select the initial loop controller operating modes, by creating parameters in the configuration screen or by sending commands in a sequential program. The loop can thus start in manual or automatic mode.
64
35012329 02 May 2007
Introduction to loop controllers
Operation of execution check z z z
The two faults checked by setpoint processing are parameter errors (not written in floating point format) and internal calculation errors (division by zero, overflow, etc.).
When such a fault appears: z Loop controller processing goes into a fallback position: z the calculated value of the OUT command is frozen, z z the control loop outputs are maintained.
The state returns to normal as soon as the fault disappears. The loop then starts off again on the outputs without bumps.
The input and output scale values are checked.
In case of inconsistency on a cold start, the loop switches to serious error mode.
Warnings are generated in the status words.
35012329 02 May 2007
65
Introduction to loop controllers
Output processing branch
At a Glance
Analog output
There are three types of output: z z z analog output,
Servo drive output,
PWM output (pulse modulation).
Whatever type of output is used, the OUT_MAN command calculated by the loop controller crosses a limiter whose lower OUTi_INF and upper OUTi_SUP limits are used to define the range of output variation. These limits define the output scale.
Apart from the limitation aspect, there is no function specific to this process. The calculated floating point value is converted into an integer in order to be sent on an analog channel (%QW) or in a memory word (%MW).
z z
There are two floating point formats: unipolar [ 0 , 10000], default format, bipolar [ -10000 , 10000].
66
35012329 02 May 2007
Introduction to loop controllers
Servo drive output branch
At a Glance This output is made up of a SERVO function with or without a copy of the actuator’s z z position. z After a Split Range or Heat/Cool PID, only the SERVO with copy position is z available.
With this type of output, the loop controller output scale must be OUTi_INF and
OUTi_SUP in the interval [ 0 , 100 ].
Its output period is the task period.
If the loop controller is in automatic mode, the SERVO output takes into account the new loop controller output value in each sampling period. In the other modes, it is in each cycle of the task.
Block diagram of a SERVO output with position copy
Block diagram of a Servo drive output branch with position copy (RCPY).
Updating of internal variables
Autotuning
PID or
IMC
Auto/Manu
Autotuning
100.0
Limiter
Gradient limiter
0.0
OUT_MAN
OUT_RATE
RCPY
SERVO
Tracking
Information The SERVO function inputs are the output OUT_MAN of the loop controller and the position copy of the actuator RCPY.
When the SERVO output follows a Split Range or Heat/Cool function, the copy input is indispensable. SERVO function inputs are then OUT1 or OUT2 and RCPY.
Block diagram of a SERVO output without position copy
Block diagram of a Servo drive output branch without position copy (RCPY).
Updating of internal variables
Enable
Calculation
OUTD
SERVO
Autotuning
Auto/Manu
Autotuning
100.0
Limiter
Gradient limiter
OUT_RATE
PID or
IMC
0.0
OUT_MAN
Tracking
35012329 02 May 2007
67
Introduction to loop controllers
Information The Servo function entry is a variation of the OUTD command of the PID.
Note: OUTD is not affected by limiting output OUT_MAN. This can be used to perform a floating process control - the command calculated by the PID has no direct link with the actual position of the actuator. In particular, it is possible to continue opening or closing a motorized valve even when OUT_MAN is saturated.
68
35012329 02 May 2007
Introduction to loop controllers
PWM branch output
At a Glance
How the initialization works
Operation of execution control
This output consists of a PWM function in which the input is the command: z z
OUT_MAN in the case of a PID loop controller,
OUT1 or OUT2 in the case of Heat/Cool or Split Range loop controllers.
With this type of output branch, the output scale must be OUTi_INF and OUTi_SUP in the interval [ 0 , 100 ].
Its output period is the task period and is independent of the operating mode of the loop controller.
z z z
On startup the parameters and output branch input value are updated before the first processing.
If the output address is not filled in, the processing is carried out but the output conversion is not performed.
There is a consistency check on the configuration entered. If there is a problem with the configuration, the loop remains in initialization state.
The two faults checked by setpoint processing are parameter errors (not written in floating point format) and internal calculation errors (division by zero, overshoot, z z etc.). On appearance of such a fault:
The result of the output is frozen.
When an error disappears, the status reverts to normal and the output is recalculated without bumps.
z z
During a cold start, if the values of the scale are not correct (non-floating value), the loop stays in its initialization position and does not restart. Therefore, the outputs conserve their initial value.
The loop starts when the error disappears.
35012329 02 May 2007
69
Introduction to loop controllers
Loops summary table
Table
Branch
Process standard process value
Single standard process value
Feed Forward
Single setpoint
SPP profile setpoint
Selection setpoint
Setpoint with ratio
ON OFF 2 states loop controller
ON OFF 3 states loop controller
PID loop controller
Heat / Cool PID loop controller (2)(3)
Split Range PID loop controller
IMC loop controller
Heat / Cool IMC loop controller (2)(3)
Split Range IMC loop controller
Analog output
SERVO output
PWM output
This table summarizes the elements associated with each type of loop.
Single loop Process loop
Cascade loop Auto selector loop
No Yes
Master
Yes (1)(2)
Slave
No
Main
Yes
Secondary
No
Yes
No
Yes
Yes
No
No
Yes
Yes
Yes
No
No
Yes
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
-
-
-
Yes
Yes
Yes
Yes
Yes
No
No
Yes
-
-
Yes (1)(3)
Yes (1)
Yes (1)
Yes
No
-
-
-
-
No
No
Yes
Yes
Yes
Yes (1)
Yes (1)
Yes (1)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
-
-
Yes
No
No
Yes (1)
Yes (1)
Yes (1)
Yes
Yes
Yes
Yes
No
Yes
Yes
No
No
-
-
Yes
-
-
-
-
-
Yes (1)
Yes (1)
Yes (1)
(1) One loop controller, either master or slave.
(2) The totalizing function does not exist on the process value branch of the master loop.
(3) The autotuning function is not built into the PID/IMC Heat/Cool loop controllers.
70
35012329 02 May 2007
Introduction to loop controllers
4.4
The setpoint programmer
At a Glance
Subject of this
Section
What's in this
Section?
This section describes the operation of the setpoint programmer.
This section contains the following topics:
Topic
Description of the setpoint programmer
Guaranteed dwell time of a setpoint programmer
Control outputs
Bumpless start
Executing a profile
How to link a setpoint programmer to a control loop
Parameters of the setpoint programmer
Operation initialization and monitoring
Page
35012329 02 May 2007
71
Introduction to loop controllers
Description of the setpoint programmer
At a Glance
Illustration
The setpoint programmer generates a setpoint, which evolves over time according z z to a parameterized profile: a maximum of 6 profiles can be configured, made up of a total of
48 segments numbered from 1 to 48.
z z
The segments are defined by the following parameters:
SPi (%MF), target setpoint,
VALi (%MF), duration or slope of segment, z z
A segment can be configured as: a ramp, a step (in this case Spi = Spi-1).
Each segment can be configured in seconds, minutes or hours.
This diagram illustrates the introductory remarks.
Setpoint
SPi
SPi-1
Si
VALi
Time
72
35012329 02 May 2007
Introduction to loop controllers
Mapping
Profiles/
Segments z z z z z z z
The possible configurations are as follows:
1 profile with a maximum of 48 segments,
1 profile with a maximum of 32 segments and 1 profile with a maximum of 16 segments,
2 profiles with a maximum of 24 segments,
3 profiles with a maximum of 16 segments,
4 profiles with a maximum of 12 segments,
6 profiles with a maximum of 8 segments,
1 profile with 24 segments, 1 profile with 16 segments and 1 profile with 8 segments.
Memory mapping of parameters and setpoints
The 48 target setpoints, as well as their associated duration, are stored in the words
%MFxy.i.50 to %MFxy.i.240 respectively. The number of configured profiles does not alter this mapping.
For 3 profiles with 16 segments the mapping is as follows: z z z z z the first setpoint of the first profile is in %MFxy.i.50 (SP1), the first setpoint of the second profile is in %MFxy.i.114 (SP17), the first setpoint of the third profile is in %MFxy.i.178 (SP33).
For 2 profiles with 24 segments the mapping is as follows: the first setpoint of the first profile is in %MFxy.i.50 (SP1), the first setpoint of the second profile is in %MFxy.i.146 (SP25),
35012329 02 May 2007
73
Introduction to loop controllers
Guaranteed dwell time of a setpoint programmer
At a Glance
Illustration
The reaction of a process to a setpoint change is more or less rapid. It does not necessarily follow the variation of the setpoint calculated by the programmer.
However, it is still possible to follow the evolution of a process value and to guarantee the period of dwell at the selected setpoint: downcounting of the dwell period starts when the deviation between the setpoint and the process value is less than a defined threshold THLD.
This guarantee can be obtained by: z z z high deviation overflow, low deviation overflow, high and low setpoint deviation overflow,
In these cases, downcounting of the dwell period is frozen during each overflow.
This figure illustrates the operation of the guaranteed dwell time.
SP
SP3 = SP4
S3
S4
Point from which the process is considered as SP3
+THLD
-THLD
VAL4
SP
Process reaction (PV)
Time
VAL4
74
35012329 02 May 2007
Introduction to loop controllers
Procedure for configuring a guaranteed dwell time
To configure a guaranteed dwell time, follow the following steps.
Step
1
2
3
4
5
6
Action
Select a loop controller.
Select the Setpoint programmer function.
Select use of the function by checking the Guaranteed Dwell Time box.
z z z z
Fill in the threshold value THLD and the type of overflow required: high deviation, PV > dwell + THLD low deviation, PV < dwell - THLD high deviation, PV > dwell + THLD or PV < dwell - THLD input deviation, deviation only at start of dwell.
In the GDT column, check the dwell on which this function is performed.
Enter the address of the process value to be monitored in the entry field PV .
Note: If the address of the process value is not entered, the Guaranteed Dwell
Time function is not used, even if the latter is configured. During execution, it is possible to inhibit this function by command (See
35012329 02 May 2007
75
Introduction to loop controllers
Control outputs
At a Glance The setpoint programmer has 8 logic bit outputs (%MWxy.i.3:X0 to X7), which can be associated to the segments in order to generate discrete actions.
These outputs are called S0 to S7 on the PL7 configuration screen.
Illustration of the configuration screen
This illustration supplies an example of parametering for logic outputs associated to the segments of a setpoint programmer.
5
6
7
3
4
1
2
Segment x
Ramp
Stage
Ramp
Stage
Ramp
Stage
Ramp
50.0
50.0
80.0
80.0
40.0
40.0
10.0
SP x
40.0
20.0
40.0
40.0
35.0
40.0
20.0
VAL x Unit
Second
Second
Second
Second
Second
Second
Second
Pq S0 S1 S2 S3 S4 S5 S6 S7
76
35012329 02 May 2007
Introduction to loop controllers
Timing diagram of operation
This timing diagram describes the position of the outputs in relation to the current segment.
Setpoint
SP3 = SP4
SP1 = SP2
SP0
S1
S2
S3
S4
S5
S6
Time
%MWxy.i.3:X0
1
0
%MWxy.i.3:X1
1
0
Time
Time
35012329 02 May 2007
77
Introduction to loop controllers
Bumpless start
At a Glance A setpoint profile starts on an initial setpoint value SP0, defined in the Execution tab. To avoid a bump on starting, the profile can start from the measured value PV and rejoin the setpoint SP1 according to the characteristics of the first segment.
Before a profile starts, the calculated setpoint is, by default, equal to SP0 (or PV depending on the profile configuration). In cases where the selected profile is changed, the calculated setpoint can be updated by performing the Reset command on this profile.
This functionality is also used to carry out profile loop iterations. To select these functions, simply check the corresponding boxes in the Execution tab window.
Timing diagram of operation
This timing diagram describes the operation of a bumpless start.
Setpoint
PV
SP0
Segment 1 Segment 2 Segment 3 Time
78
35012329 02 May 2007
Execution configuration window
Introduction to loop controllers
This figure shows an example of a configuration screen that is used to configure the bumpless, start up and loop iteration functionality.
PMX 57202 [RACK 0 POSITION 0 ]
Configuration
Designation: PROCESSOR PMX P 57202
DOP configuration
Function:
Loop controller 5 - SPP_0 Setpoint programmer
Name: SPP_0
PROFIL_1 PROFIL_2
Segments
Start:
Execution
Setpoint SP_0: 10.0
Process value (bumpless)
PROFIL_3
Task:
MAST
Segmentation:
16-16-16
Number of segments:
Execute 3
Execute to infinity
Resume at segment no.: times
1
16 on 16
Bumpless
PV
100.0
0.0
35012329 02 May 2007
79
Introduction to loop controllers
Executing a profile
At a Glance A profile can be: z z z executed once, reproduced a certain number of times, continuously relooped.
The number of repetitions is set in the word NB_RT_PFi whose limits are 1 and
32767.
Note: the first loop iteration segment is not necessarily the first of the profile; its configuration is carried out in the configuration screen, in the Execution tab. The point is to be able to define, for a given profile, segments which will only execute once on start up (initialization segments).
How to launch a profile execution command
The following table indicates the steps to follow to launch the execution of a profile using a software command.
Step
1
2
3
Action
Assign the value of the command to the word %MWxy.i.7.
Note : the list of commands is given in the following table.
Indicate the number of the profile concerned in the double word %MDxy.i.8 (1 to 6).
Launch the command WRITE_CMD %CHyx.i.
Note : transmission of this command is done by explicit exchange (See
).
80
35012329 02 May 2007
Introduction to loop controllers
Profile execution commands
Only one profile can be launched and executed at any given moment. The following table shows the commands corresponding to the hexadecimal value assigned to the word %MWxy.i.7.
Command
START
STOP
RESET
NEXT
BACK
HOLD
DEHOLD
HOLD_PG
DEHOLD_PG
Hexadecimal value Comment
16#0002 Triggers execution of the selected profile.
16#0003
16#0001
Stops execution of the selected profile.
Reinitializes the setpoint programmer and makes it await START.
16#0006
16#0007
16#0004
16#0005
16#0008
16#0009
Jumps to the following segment.
Jumps to the previous segment.
Freezes setpoint evolution and time lapse.
Unfreezes the profile in progress.
Inhibits the guaranteed dwell time function on the profile in progress.
Activates the guaranteed dwell time function on the profile in progress.
Conditions of execution
Control via the master screen z z z z z
The commands have conditions of execution: the RESET command is always accepted, the START command is only accepted if the programmer is running, the NEXT and BACK commands are refused if the profile is not frozen, the STOP command is refused if the programmer is in initialization mode, the HOLD_PG and DEHOLD_PG commands are refused if the function is not used.
Each profile can be controlled from its master screen, using the command buttons below.
INIT
STOP
RUN
HOLD
NEXT
BACK
HOLD_PG/DEHOLD_PG
35012329 02 May 2007
81
Introduction to loop controllers
How to link a setpoint programmer to a control loop
Procedure The steps in the following table show how to associate a setpoint programmer to a control loop.
Step
1
2
3
4
Action
Access the hardware configuration via the application browser.
Double click on the Loop block for the processor.
Select a loop controller.
Select Choose the required function .
Result : this type of screen appears:
LOOP 0
Loop
Loop parameters
Measurement
Setpoint
Loop controller
Feed Forward
Output 1
Standard
Hot/Cold
Yes
Analog
Functions
Scale
Limiter
Velocity limiter
Tracking
Parameters
Low input scale (phy)
High input scale (phy)
0.0
100.0
5
6
Select Programmer as the type of setpoint.
Enter as the setpoint input address (SP1 in the block schema) the output address of the setpoint programmer, that is %MFxy.i.20, where i is the number of the loop controller selected as the setpoint programmer.
82
35012329 02 May 2007
Introduction to loop controllers
Parameters of the setpoint programmer
Internal parameters
Table of internal function parameters.
Meaning
Number of reiterations of profile number i
Symbolization Type of data
NB_RT_PFi
Value of the guaranteed dwell time threshold of profile number i
THLD_PFi
Value of initial setpoint of profile number i
Setpoint to be reached by segment number i
SPO_PFi
SPi
Value of the time or speed for segment number i
VALi
Word
Floating point
Floating point
Floating point
Floating point
Variation range
0/32767
0.0/3.4 E38
-3.4 E38/3.4 E38
-3.4 E38/3.4 E38
-3.4 E38/3.4 E38
0.0
0.0
0.0
Default value R/W
1 R/W
0.0
R/W
R/W
R/W
R/W
Output parameters
Table of output function parameters.
Meaning
Current number of profile
Number of current segment
Number of current iteration
Value of calculated setpoint
Value of total time elapsed
(including frozen time)
Value of ime elapsed on the segment in progress
(including frozen time)
Symbolization Type of data
CUR_PF
SEG_OUT
CUR_ITER
Word
Word
Word
SP Floating point
TOTAL_TIME Floating point
CUR_TIME Floating point
Variation range
0/32767
0/32767
0/32767
-3.4 E38/3.4 E38
0.0/3.4 E38
0.0/3.4 E38
Default value R/W
0
0
0
-
-
R
R
R
R
R
0.0/3.4 E38 R
35012329 02 May 2007
83
Introduction to loop controllers
Operation initialization and monitoring
How the initialization works
On initialization, there is a coherence check on the configuration entered. If there is a problem with the configuration, the setpoint programmer indicates the error and remains in initialization state.
Operation of execution check
The two serious faults checked by the process value processing are parameter errors (not written in floating point format) and internal calculation errors (division by zero, overshoot, etc.).
If … an error in the calculation of the setpoint has been detected
Then … the result of the setpoint is frozen the error disappears a ramp has two identical setpoints normal status is resumed.
a warning is displayed, calculation of the setpoint continues to be performed. There is an immediate switch to the next segment if the programmer is on the faulty segment.
a ramp has a rising or falling speed of zero (0.0) a warning is displayed, calculation of the setpoint continues to be performed. The calculated setpoint is frozen if the programmer is on the faulty segment.
a dwell has two distinct setpoints a warning is displayed, calculation of the setpoint continues to be performed. There is a rise or a fall depending on the setpoint values if the programmer is on the faulty segment.
the guaranteed dwell time is configured with a threshold value of
0.0
a warning is displayed, calculation of the setpoint continues to be performed. Processing of the guaranteed dwell time is suppressed if the programmer is on the faulty segment.
z z
When the setpoint programmer is on the faulty segment, an additional warning is displayed with the following message: "Error on current segment".
Caution , for these warnings to be displayed, it is imperative that the execution time for each segment is greater than the execution time of the PLC task.
84
35012329 02 May 2007
4.5
Introduction to loop controllers
Global parameters of control loops
Description of the global parameters of process control loops
At a Glance
Execution parameters z z
Some of the general parameters associated with the process control channels can be classified in two categories: parameters linked to loop execution, parameters which characterize the process control loop.
This table describes the execution parameters for a process control loop.
Parameter
Task
Sampling period
Description
The process control channels must be assigned to a task of the PLC
(MAST or FAST). The MAST task is selected by default, the FAST task must be selected when you wish to improve the sampling speed and execution priority.
This is the processing period of the loop controller in automatic mode.
The default value is 0.3 seconds. This value must be a modulo value of the task period. Otherwise, the process control processing period will be to the nearest modulo value.
Example: T_MAST = 0.1 s, T_ECH = 0.124 s T_ECH true = 0.1 s
If Then the sampling period is less than the task period the true sampling period is automatically fixed to that of the task period.
Period calculations are made taking into account the true value of
T_ECH. If the task processing execution time exceeds the theoretical period, the %S19 bit shows this error.
35012329 02 May 2007
85
Introduction to loop controllers
Instrumentation parameters
This table describes the instrumentation parameters of a process control loop.
Parameter
Name
Description
This name is included in the constants (%KW) and can be given to each loop. It is made up of a maximum of eight characters and is automatically retrieved by the runtime screens dedicated to controlling the XBTs.
Unit This parameter, made up of a maximum of 6 characters, is included in the constants (%KW). These characters define the process control loop unit
(Example: DEGRE). This parameter is automatically retrieved by the runtime screens dedicated to controlling the XBTs.
Application ID This parameter is used to identify the process control loop configuration. To check their authenticity, these application IDs can be compared with each other. They are a digital representation of the configuration constants of the loop.
High scale
Low scale
Double word
"command order"
Any change in the parameter settings of the KP unit leads to a major evolution of the application ID. However, the following particularities concerning cascade and autoselector loops should be noted: z cascade loop: A change in the parameter settings of one of the loops
(master or slave) of the KP unit simultaneously changes this parameter in both loops. However, the application ID is only changed for the slave z loop . auto selector loop: A change in the parameter settings of one of the loops (main or autoselector) of the KP unit simultaneously changes this parameter in both loops. However, the application ID is only changed for the secondary loop .
These thresholds define the physical scale in which the loop exerts its control. The upstream branch calculations (process value and setpoint) are both set to the same scale.
Note : in the setpoint branch there is a scale function which gives the scale range of the variable defined at the time the setpoint was input. This function is useful when process loops are sequenced to produce a cascade. By default, this scale must be identical to the physical scale defined by the loop.
Note : it is also possible to set the output branch (See Output scaling,
) to a specific scale.
The order of command double word (See Double word "Order of
Command", p. 312 ) is used to manage the loop operation. It replaces the
use of the WRITE_CMD function. For the first 16 bits, this double word is identical to the status word of the process control loop.
86
35012329 02 May 2007
Calculation functions
5
At a Glance
Subject of this
Chapter
What's in this
Chapter?
This chapter describes the calculation functions of the different processing z z z z branches:
Functions of the process value branch,
Functions of the setpoint branch,
Functions of the Feed forward branch, z
Functions of the loop controller branch,
Functions of the output branch.
This chapter contains the following sections:
Section Topic
5.1
Functions of the process value branch
5.2
5.3
Functions of the setpoint branch
Feed forward branch functions
5.4
5.5
Functions of the loop controller branch
Functions of the output branch,
Page
87
35012329 02 May 2007
Calculation functions
5.1
Functions of the process value branch
At a Glance
Subject of this
Section
What's in this
Section?
z z z z z z z z
This section describes the calculation functions of the process value processing branch:
Input format,
Filter,
Square root,
Function generator,
Scaling,
Scale limiter,
Alarms on level,
Totalizer.
This section contains the following topics:
Topic
Input format
First order filtering
Square root
Function generator
Scaling
Scale limiter
Level alarms
Totalizer
Page
88
35012329 02 May 2007
Calculation functions
Input format
Description
Process value input address
The "input format" function is used solely for a standard type process value. It provides the gross value of the analog input of the loop. For this, you must configure the format to comply with the type of analog input channel.
z z
Two range formats are possible:
Unipolar: 0 to 10000 (selection by default),
Bipolar: -10000 to +10000.
You must define the process value input address on the on the PL7 process control configuration screen. For a standard type process value, this must be an %IW input word or an internal %MW word.
The input address is entered in the graphic section of the screen:
PMX 57102 [RACK 0 POSITION 0]
Configuration
Designation: PROCESSOR PMX P 57102
DOP configuration
Symbol:
Loop Controller:
Loop Controller 4 – LOOP0
Function:
Process loop
LOOP 0
Loop
Loop parameters
Process value Standard
PV
%MW1
SP1
Functions
Format
Filter
P
I
Range
Parameters
Unipolar
OUT 1
%MW6
35012329 02 May 2007
89
Calculation functions
Function parameters
Input parameter:
Parameter
Process value input
/
Symbol
Internal parameter:
Parameter
Range
Symbol
PV_UNI_BIP
Output parameter:
Parameter Symbol
Input enabled PV_SIM
Type
%IW
%MW
Type
%KW bit
Type
Word
Limits
-32768 / 32767 /
Default value R/W
R
/
Limits Default value R/W
0 (Unipolar) R
Limits Default value R/W
-32768 / 32767 0 R/W
Operation monitoring
For an external process value
If you do not enter the input address, the value read is the simulation value. This value is initially at 0.
For an external type process value, the "input format" function is not used, because this is directly of integer type. This input is then recopied into the process value floating variable (PV) on entering the loop controller.
90
35012329 02 May 2007
Calculation functions
First order filtering
Description This function performs first order filtering with a time constant T. The transfer function of the filer is as follows:
FILT_OUT = GAIN_FILT x
1
1 + pT_FILT x PV_SIM with :
PV_SIM : Input value of the function
T_FILT : Time constant
FILT_OUT : Result of the function p : Laplace operator
GAIN_FILT : Proportional coefficient
This first order filter is applied directly to the input process value.
Value of
PV_SIM and FILT_OUT
GAIN_FILTxPV_SIM
FILT_OUT
Time
T_FILT
35012329 02 May 2007
91
Calculation functions
Function parameters
Input parameter:
Parameter Symbol
Input enabled PV_SIM
Internal parameters:
Parameter Symbol
Filtering time
(ms)
Gain
T_FILT
GAIN_FILT
Output parameter:
Parameter Symbol
Output value FILT_OUT
Type
Word
Limits Default value R/W
-32768 / 32767 0 R/W
Type Limits
Floating point 0.0 / 3.4E38
Default value
0.0
Floating point -3.4E38 / 3.4E38
1.0
R/W
R/W
R/W
Type Limits
Floating point -3.4 E38 / 3.4E38
/
Default value
R/W
R
Operation monitoring
Note: If the function is not selected, the filter output value is the same is as its input value.
Monitoring the parameters of this function is integrated into the error management of the process value branch. If the time constant is negative, its value is set at 0.0.
92
35012329 02 May 2007
Calculation functions
Square root
Description
Function parameters
This function calculates the square root of a numerical size. The square root extract is typically used to linearize an output process value produced by a deprimogenous unit
The function performs the following calculation:
OUT = 100 FILT_OUT
OUT = 0 if FILT_OUT > 0 if FILT_OUT < 0
Input parameter:
Parameter Symbol
Function input FILT_OUT
Output parameter:
Parameter Symbol
Output value SQRT_OUT
Type Limits
Floating point -3.4E38 / 3.4E38
/
Default value
R/W
R
Type Limits
Floating point -3.4 E38 / 3.4E38
/
Default value
R/W
R
Operation monitoring
Note: If the function is not selected, the value of its output is the same as its input value.
There is no specific check dedicated to this function. The monitoring of the parameters is integrated into the error management of the process value branch.
35012329 02 May 2007
93
Calculation functions
Function generator
Description The generator corrects the non-linear readings of the process value input signal.
Correcting this non-linearity is done via 7 linear adjacent segments, in variable increments, defined by the coordinates of their points.
The function also performs a scaling which is exclusive to the process value scaling function, described below.
The output is calculated by the linear interpolation between the 2 points whose abcissae contain the input parameter value.
PV = f(x) = {(X1,Y1), …, (X7,Y7)} where:
X1 = 0 or -10000 and Y1= PV_INF (low limit of the loop scale),
X7 = 10000 et Y7= PV_SUP (high limit of the loop scale).
Function generation diagram:
PV
E7_OUT
E5_OUT, E6_OUT
PV_SUP
E4_OUT
E2_OUT, E3_OUT
PV_INF
0 or
-10000
E2_IN E3_IN E4_IN
E5_IN
E6_IN E7_IN 10000
Outside the input scale, it is possible using configuration to extrapolate or limit the value of the measurement value calculated on the process value scale.
94
35012329 02 May 2007
Parameters
Calculation functions
Input parameter:
Parameter Symbol
Function input SQRT_OUT
Internal parameters:
Parameter Symbol
Extrapolation EXTRAPOL
Abcissa 1 /
Abscissa 2
Abscissa 3
Abscissa 4
Abscissa 5
E2_IN
E3_IN
E4_IN
E5_IN
Abscissa 6
Abscissa 7
E6_IN
E7_IN
Abscissa 8 /
Coordinate 1 PV_INF
Coordinate 2 E2_OUT
Coordinate 3 E3_OUT
Coordinate 4 E4_OUT
Coordinate 5 E5_OUT
Coordinate 6 E6_OUT
Coordinate 7 E7_OUT
Coordinate 8 PV_SUP
Output parameter:
Parameter Symbol
Process value PV
Type Limits
Floating point -3.4E38 / 3.4E38
/
Default value
Type Limits
Floating point -3.4E38 / 3.4E38
/
Default value
R/W
R
Type Limits
Bit constant /
Floating point -3.4E38 / 3.4E38
Floating point -3.4E38 / 3.4E38
Floating point -3.4E38 / 3.4E38
Floating point -3.4E38 / 3.4E38
Floating point -3.4E38 / 3.4E38
Floating point -3.4E38 / 3.4E38
Floating point -3.4E38 / 3.4E38
Floating point -3.4E38 / 3.4E38
Floating point -3.4E38 / 3.4E38
Floating point -3.4E38 / 3.4E38
Floating point -3.4E38 / 3.4E38
Floating point -3.4E38 / 3.4E38
Floating point -3.4E38 / 3.4E38
Floating point -3.4E38 / 3.4E38
Floating point -3.4E38 / 3.4E38
Floating point -3.4E38 / 3.4E38
Default value
0 (no)
0.0 or
-1000.0
1428.0
2857.0
4285.0
5714.0
7143.0
8571.0
10000.0
0.0
14.28
28.57
42.85
57.14
71.43
85.71
100.0
R/W
/
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
/
R/W
R/W
R/W
R/W
R
Note: Parameters PV_INF and PV_SUP are defined within the global parameters of the loop.
35012329 02 May 2007
95
Calculation functions
Operation monitoring
The monitoring of the parameters is integrated into the error management of the process value branch.
The coordinates of the abcissae must be ascending. For example, if Ej+1_IN < Ej_IN, a warning message is displayed. Nonetheless the calculation is done with the current parameters.
96
35012329 02 May 2007
Calculation functions
Scaling
At a Glance The process value branch is scaled automatically from the global parameters of the loop: PV_INF and PV_SUP (See Description of the global parameters of process
).
35012329 02 May 2007
97
Calculation functions
Scale limiter
Description This function is used to limit the process value in relation to the physical scale defined for the process control loop.
If this function is activated, the scaling is only done in the range PV_INF to PV_SUP.
Outside of this range, the output is limited to the scale values.
Value on limiter output:
PV on limiter output
PV_SUP
PV
PV_INF
Process value
PV_INF PV PV_SUP
98
35012329 02 May 2007
Calculation functions
Level alarms
Description This function monitors the progress of the process value by comparing its value to the 4 thresholds PV_LL, PV_L, PV_H and PV_HH.
Each alarm possesses an associated status bit.
These alarms are controlled by a fixed hysteresis of 1% in relation to the scale defined in the global parameters of the loop.
Alarms for crossing threshold PV_H or PV_L:
PV
PV_H
Hyst (1%)
STS_PV_H t t
PV
STS_PV_L
Hyst (1%)
PV_L t t
35012329 02 May 2007
99
Calculation functions
Parameters
Operation monitoring
Input parameter:
Parameter Symbol Type Limits
Floating point -3.4 E38 / 3.4E38
/
Default value
R/W
Process value PV
Internal parameters:
Parameter Symbol
R
Type Limits Default value
Floating point -3.4 E38 / 3.4E38
5.0
R/W
Very low threshold
PV_LL
Low threshold PV_L
High threshold
PV_H
Very high threshold
PV_HH
Floating point -3.4 E38 / 3.4E38
5.0
Floating point -3.4 E38 / 3.4E38
95.0
Floating point -3.4 E38 / 3.4E38
95.0
Output parameters:
Parameter Symbol Type
Very low limit STS_PV_LL_LIM Bit
Low limit STS_PV_L_LIM Bit
High limit STS_PV_H_LIM Bit
Very high limit STS_PV_HH_LIM Bit
Or alarms (*) STS_ALARMS Bit
/
/
/
/
/
Limits
/
/
/
/
/
Default value
(*) Or bit logic of alarms upon crossing threshold and alarms on deviation.
R/W
R/W
R/W
R/W
R/W
R
R
R
R
R
The monitoring of the parameters is integrated into the error management of the process value branch.
100
35012329 02 May 2007
Calculation functions
Totalizer
Description
Function principle
This function includes the input value (typically a negative) according to time, and returns a cumulative (typically a volume).
For this, it uses a partial internal accumulator Acc which includes the PV value and is automatically reset to 0 each time it reaches an adjustable threshold THLD.
The number of resets is recorded in order to enable the recomposing of the global cumulative OUT_TOT.
On each execution the accumulator Acc and the cumulative OUT_TOT are calculated using the algorithm:
Acc(new) = Acc(old) + PV. DT
SI Acc(new) >= THLD ALORS
Acc(new) = Acc(new) - THLD
CptInit = CptInit + 1
FINSI
OUT_TOT = CptInit x THLD + Acc(new) where:
CptInit = number of resets
DT = task period
ACC (old) = value of accumulator Acc on the previous cycle
Adjusting the integration threshold THLD
Time Base
Generally, integration threshold value corresponds to an easily determined process characteristic (the capacity of a tank, for example). During a cycle, a status bit is set to 1 each time the partial accumulator reaches the integration threshold.
The function can also be used to integrate small input value, even when the result of the integration is very large. In this case, the values to be integrated may become negligible to the accumulated value and are therefore no longer taken into consideration.
To avoid this, we advise you to limit the accumulator to a threshold THLD, so that the value to be integrated is never negligible in relation to this partial accumulator.
When the threshold THLD is equal to 0, the function does not integrate a value and the function remains fixed.
In order to integrate the new process value, the relationship between the cumulative value and the PV value must be less than 10
9
.
35012329 02 May 2007
101
Calculation functions
Associated commands
Timing graph
Two commands are associated to the function: z Reset: the OUT_TOT function output is set to 0, as are all the internal variables
(following a phase change in production, for example).
z Hold: integration is paused. The function output retains its former value.
In this mode the user can modify the cumulative value OUT_TOT, prompting a new calculation of the internal variables. This allows the cumulative value to be recalibrated (after an automation stop, for example).
Totalizer Function:
THLD
STS_THLD_TOT OVER_TOT = 1 OVER_TOT = 1
OUT_TOT
THLD
102
35012329 02 May 2007
Parameters
Operation monitoring
Calculation functions
Input parameter:
Parameter Symbol
Process value PV
Internal parameters:
Parameter Symbol
Type Limits
Floating point -3.4E38 / 3.4E38
/
Default value
Totalizing threshold
Time Base (h) /
THLD
Output parameters:
Parameter Symbol
Totalizing value
Threshold reached
OUT_TOT
STS_THLD_TOT
Type Limits
Floating point 0.0 / 3.4E38
%KW bit / /
Default value
1.0E38
Type Limits
Floating point 0.0 / 3.4E38
Default value
0.0
Bit / /
R/W
R
R/W
R
R
R/W
R/W
R
The monitoring of the parameters is integrated into the error management of the process value branch.
35012329 02 May 2007
103
Calculation functions
5.2
Functions of the setpoint branch
At a Glance
Subject of this
Section
What's in this
Section?
z z z z z z
This section describes the calculation functions of the setpoint processing branch:
Ratio,
Selection,
Scaling,
Setpoint limiter,
Tracking setpoint,
Speed limiter
This section contains the following topics:
Topic
Ratio
Selection
Scaling
Setpoint limiter
Tracking setpoint
Speed limiter
Page
104
35012329 02 May 2007
Calculation functions
Ratio
Description The Ratio function is used to carry out the report process control; in other words, to assign a size to the value of the external input (control value).
The Ratio function calculates the loop controller setpoint according to the control value, by applying the following formula:
SP = RATIO x (SP Remote 1) + RATIO_BIAS where:
SP Remote 1 = control value.
It is possible to define maximum and minimum limitations on the ratio reports.
Note: The size connected to the SP Remote 1 input is an external process value rather than a setpoint.
Functional diagram of the Ratio function:
RATIO_MAX
RATIO
RATIO_MIN
Remote %MF X
RATIO_BIAS
+
+
X SP
35012329 02 May 2007
105
Calculation functions
Parameters Input parameter:
Parameter Symbol Type Limits
-3.4E38 / 3.4E38
/
Default value
Setpoint input /
Internal parameters:
Parameter Symbol
%MFi
Ratio value
Min ratio value
Max ratio value
Ratio bias
RATIO
RATIO_MIN
RATIO_MAX
RATIO_BIAS
Output parameters:
Parameter Symbol
Type Limits
Floating point -3.4E38 / 3.4E38
Floating point -3.4E38 / 3.4E38
Default value
1.0
0.0
Floating point -3.4E38 / 3.4E38
100.0
Floating point -3.4E38 / 3.4E38
0.0
Type Limits
Setpoint value SP
Scale error RATIO_WARN
Floating point -3.4E38 / 3.4E38
Bit / /
/
Default value
R/W
R
R/W
R/W
R/W
R/W
R/W
R/W
R
R
Operation monitoring
Monitoring the parameters is integrated into the error management of the setpoint branch.
106
35012329 02 May 2007
Calculation functions
Selection
Description
Operation monitoring
The selection function is used to select a setpoint by comparing two numerical inputs. This selection can be: z Max selection: the Remote 1 setpoint input is greater than the Remote 2 setpoint z input,
Min selection: the Remote 1 setpoint input is smaller than the Remote 2 setpoint z input,
"Switch" selection: the input is selected by an explicit command.
The switch is straightforward and is done without hysteresis.
Monitoring this function is integrated into the error management of the setpoint branch.
35012329 02 May 2007
107
Calculation functions
Scaling
Description This function is used to express a setpoint value in the process value scale defined by PV_INF and PV_SUP (loop parameters).
It takes into account the input range of the setpoint (INP_INFRi, INP_SUPRi) and is applied to the Remote 1 and Remote 2 setpoints.
The Scaling function performs the following calculation:
SP = (IN - INP_INFRi) x
PV_SUP - PV_INF
INP_SUPRi - INP_INFRi
+PV_INF
This function is optional and can be used to track two loops (to cascade two process loops, for example).
In the absence of this function: INP_INFRi = PV_INF and INP_SUPRi = PV_SUP.
Functional diagram of the Scaling function:
Process value
10000
0
PV_SUP = 250°C
Loop controller
Setpoint
INP_SUPRi = 250.0
INP_INFRi = 10.0
PV_INF = 10°C
Changing the setpoint according to Remote setpoint input
PV_SUP
SP
SP
PV_INF
Remote Input
INP_INFRi %MF INP_SUPRi
108
35012329 02 May 2007
Parameters
Operation monitoring
Calculation functions
Input parameter:
Parameter Symbol
Setpoint input /
Internal parameters:
Parameter Symbol
Low input scale
High input scale
INP_INFRi
INP_SUPRi
Output parameter:
Parameter Symbol
Setpoint value SP
Type
%MFi
Limits
-3.4E38 / 3.4E38
/
Default value
R/W
R/W
Type Limits
Floating point -3.4E38 / 3.4E38
Default value
0.0
Floating point -3.4E38 / 3.4E38
100.0
R/W
R/W
R/W
Type Limits
Floating point -3.4E38 / 3.4E38
/
Default value
R/W
R
Monitoring the parameters of this function is integrated into the error management of the setpoint branch. Si INP_INFRi >= INP_SUPRi, the setpoint output remains unchanged. An error bit is set to 1 in the status words.
35012329 02 May 2007
109
Calculation functions
Setpoint limiter
Description
Parameters
When this function is activated, the scaling is only done in the range limits, defined by the parameters SP_MIN and SP_MAX. When this function is not activated, the setpoint value is limited to the physical scales of the regulation loop.
The interval (SP_MIN / SP_MAX) must be included in the interval (PV_INF /
PV_SUP).
The interval [SP_MIN / SP_MAX] must be in the interval (PV_INF / PV_SUP).
SP
PV_SUP
SP_MAX
SP
SP_MIN
PV_INF
INP_INFRi %MF INP_SUPRi
Remote
Input
Input parameter:
Parameter Symbol
Setpoint value SP
Internal parameters:
Parameter Symbol
Low setpoint limit
High setpoint limit
SP_MIN
SP_MAX
Output parameter:
Parameter Symbol
Setpoint value SP
Type Limits
Floating point -3.4E38 / 3.4E38
/
Default value
R/W
R
Type Limits
Floating point -3.4E38 / 3.4E38
Default value
0.0
Floating point -3.4E38 / 3.4E38
100.0
R/W
R/W
R/W
Type Limits
Floating point -3.4E38 / 3.4E38
/
Default value
R/W
R
110
35012329 02 May 2007
Operation monitoring
Calculation functions
Monitoring the parameters of this function is integrated into the error management of the setpoint branch.
If SP_MIN >= SP_MAX, SP_MIN < PV_INF or SP_MAX > PV_SUP, the setpoint output remains unchanged and a bit is set to state 1 in the status words.
35012329 02 May 2007
111
Calculation functions
Tracking setpoint
Description
Function not configured
In local setpoint mode and when the corrector is not in automatic mode, this function prompts the tracking of the measurement by the local setpoint. This avoids bumps on the corrector output when it returns to automatic mode.
Change of the output when the function is not configured:
PV
SP
PV
SP
OUT
OUT
Setpoint change
Switch into manual mode
Switch into Auto mode t t
112
35012329 02 May 2007
Function configured
Change of the output when the function is configured:
PV
SP
PV
SP
OUT
OUT
Setpoint change
Switch into manual mode
Switch into Auto mode t t
Calculation functions
35012329 02 May 2007
113
Calculation functions
Speed limiter
Description This function is used, when changing setpoint, to reach the new value while respecting a speed limit. Rising and descending speed limits can be different.
When the requested value on input is greater than the current value of the output
SP, the function increases the value of this output at the speed R_RATE, until the value SP is equal to that requested.
If the value R_RATE is nil, there is no slope and SP is a direct copy of the input value.
When the input value changes as the slope is being generated the function attempts to reach this new target.
Function diagram:
Setpoint
Rising ramp
RSP
SP
Ramp: falling
Time
114
35012329 02 May 2007
Parameters
Operation monitoring
Calculation functions
Input parameter:
Parameter Symbol Type Limits
Floating point -3.4E38 / 3.4E38
/
Default value
R/W
R Setpoint value SP
Internal parameters:
Parameter Symbol
Rising speed limit
Descending speed limit
R_RATE
D_RATE
Output parameter:
Parameter Symbol
Limited setpoint value
SPEED_LM_OUT
Type Limits
Floating point 0.0 / 3.4E38
Floating point 0.0 / 3.4E38
Default value
0.0
0.0
R/W
R/W
R/W
Type Limits
Floating point
-3.4E38 / 3.4E38
/
Default value
R/W
R/W
Note: R_RATE and D_RATE at 0.0 mean there is no limit.
This function can be applied to the Remote setpoint and the local setpoint or only to the local setpoint, according to the chosen configuration.
Monitoring the parameters of this function is integrated into the error management of the setpoint branch.
35012329 02 May 2007
115
Calculation functions
5.3
Feed forward branch functions
At a Glance
Subject of this
Section
What's in this
Section?
z z z
This section describes the calculation functions of the Feed forward processing branch:
Scaling,
Leadlag,
Alarm on deviation.
This section contains the following topics:
Topic
Scaling
Leadlag
Alarm on deviation
Page
116
35012329 02 May 2007
Calculation functions
Scaling
Description This function is used to change the scale of the digital value of the Feed forward input.
The Scaling function performs the following transfer function:
OUTFF = (FF - in_min) x
(OUTFF_SUP - OUTFF_INF)
(in_max - in_min)
+ OUTFF_INF where: in_min = 0 or -10000 in_max = 10000
Feed forward value:
High scale
(OUTFF_SUP)
OUTFF
Low scale
(OUTFF_INF)
0 or -10000 FF 10000
Feed forward input
35012329 02 May 2007
117
Calculation functions
Parameters Input parameter:
Parameter Symbol Type Limits
/
Default value
Feed forward input
/
Internal parameters:
Parameter Symbol
%IW
%MW
-32768 / 32767
Feed forward value
OUT_FF
Type Limits
Low scale
High scale
OUT_FF_INF
OUT_FF_SUP
Output parameter:
Parameter Symbol
Floating point -3.4E38 / 3.4E38
Floating point -3.4E38 / 3.4E38
Type Limits
Default value
0.0
100.0
Floating point -3.4E38 / 3.4E38
/
Default value
R/W
R
R/W
R/W
R/W
R/W
R/W
Operation monitoring
Monitoring the parameters of this function is integrated into the error management of the Feed forward branch.
There is no monitoring on the scale parameter order. The lower limit can have a greater value than that of the upper limit.
118
35012329 02 May 2007
Calculation functions
Leadlag
Description
Phase advance
The Leadlag function performs an advance/delay phase type transfer function. This can be used to make a model of the influence of disruptions and therefore perform a process control in an open loop by anticipation.
The Leadlag function performs the following transfer function:
OUTFF =
1 + p x T1_FF
1 + p x T2_FF x FF where:
FF = size of analog input: internal variable (disruption process value)
T1_FF = time constant corresponding to forward motion of phase
T2_FF = time constant corresponding to phase delay p = Laplace operator
OUTFF = calculated size
For a graded input, the output response is a function of T1_FF and T2_FF (phase z z advance or delay):
If T1_FF > T2_FF, a phase advance is performed.
If T1_FF < T2_FF, a phase delay is performed.
The Leadlag function is configured in phase advance (T1_FF > T2_FF): the output
OUTFF is ahead of the input.
Value of
OUTFF
Feed forward input
OUTFF
Time
35012329 02 May 2007
119
Calculation functions
Phase delay The Leadlag function is configured in phase delay (T1_FF < T2_FF): The output
OUTFF is behind the input.
Value of
OUTFF
Feed forward input
OUTFF (T1_FF = T2_FF/2)
OUTFF
OUTFF (T1_FF = 0)
Time
Parameters Input parameter:
Parameter Symbol
Feed forward input
/
Internal parameters:
Parameter Symbol
Time 1 (s)
Time 2 (s)
T1_FF
T2_FF
Output parameter:
Parameter Symbol
Feed forward value
OUTFF
Type Limits
Floating point -3.4E38 / 3.4E38
/
Default value
R/W
R
Type Limits
Floating point -3.4E38 / 3.4E38
Floating point -3.4E38 / 3.4E38
Default value
0.0
0.0
R/W
R/W
R/W
Type Limits
Floating point -3.4E38 / 3.4E38
/
Default value
R/W
R
Operation monitoring
Monitoring the parameters of this function is integrated into the error management of the Feed forward branch.
120
35012329 02 May 2007
Calculation functions
Alarm on deviation
Description This function monitors changes in the deviation between the process value (PV) and the setpoint (SP), by comparing these 2 values to 2 thresholds (high deviation threshold and low deviation threshold).
These alarms are controlled by a fixed hysteresis of 1% of the full scale of the loop.
Note: The threshold values must be greater than the hysteresis (1%), otherwise the alarms will still be active.
Alarm on deviation function diagram:
STS_DEV_H
Time
STS_DEV_L
Time
PV-SP
DEV_H
DEV_L
Hyst (1%)
Time
Hyst (1%)
35012329 02 May 2007
121
Calculation functions
Parameters Input parameters:
Parameter Symbol
Measurement value
PV
Setpoint value SP
Internal parameters:
Parameter Symbol
Type Limits
Floating point -3.4E38 / 3.4E38
/
Default value
Floating point -3.4E38 / 3.4E38
/
Type Limits
High deviation threshold
DEV_H
Low deviation threshold
DEV_L
Output parameters:
Parameter Symbol
Floating point 0.0 / 3.4E38
Floating point -3.4E38 / 0.0
Type
High limit
Low limit
STS_DEV_H
STS_DEV_L
Or alarms (*) STS_ALARMS
Bit
Bit
Bit
Limits
/
/
/
Default value
5.0
-5.0
/
/
/
Default value
R/W
R
R
R
R/W
R
R
R/W
R/W
R/W
Operation monitoring
Note: (*) Or alarms = Or bit logic on level alarms and alarms on déviation.
Monitoring the parameters is integrated into the error management of the
Measurement branch.
122
35012329 02 May 2007
5.4
Calculation functions
Functions of the loop controller branch
At a Glance
Subject of this
Section
What's in this
Section?
z z z z z z z
This section describes the calculation functions of the loop controller branch:
ON OFF 2 states,
ON OFF 3 states,
PID,
Model loop controller,
Autotuning,
Split Range,
Heat/Cool,
This section contains the following topics:
Topic
ON OFF 2 states loop controller
ON OFF 3 states loop controller
PID
PID parameters
Detailed PID equations
Model loop controller
Model loop controller parameters
Autotuning
Autotuning parameters
Autotuning process
Autotuning operating modes
Diagnostics parameters
Aborting autotuning
Split Range
Heat/Cool
Page
35012329 02 May 2007
123
Calculation functions
ON OFF 2 states loop controller
Description The ON OFF 2 states loop controller is used to process simple process controls, for which discrete 2 position monitoring is adequate.
Actuator control is performed according to process value/setpoint deviation in relation to 2 thresholds (a high threshold and a low threshold).
Functional diagram:
STS_RAISE1
PV-SP
ONOFF_H
ONOFF_L
Time
124
35012329 02 May 2007
Parameters
Calculation functions
Input parameters:
Parameter Symbol Type Limits
Floating point -3.4E38 / 3.4E38
/
Default value
Measurement value
PV
Setpoint value SP
Internal parameters:
Parameter Symbol
Floating point -3.4E38 / 3.4E38
/
Low threshold ONOFF_L
High threshold
ONOFF_H
Output parameters:
Parameter Symbol
Type Limits
Floating point -3.4E38 / 3.4E38
Floating point -3.4E38 / 3.4E38
Default value
-5.0
5.0
Type
Bit /
Limits
Command status
STS_RAISE1
Auto_Manu
State
Command
STS_M_A
/
Process value
/ Setpoint deviation
DEV
Bit
Bit
/
/
Floating point -3.4E38 / 3.4E38
/
/
/
/
Default value
R/W
R
R
R/W
R/W
R/W
R
R
R
R/W
R
Process value /
Setpoint deviation
As soon as the Process value/Setpoint deviation (DEV = PV – SP) becomes smaller than the low threshold ONOFF_L, the logic output passes to state 1. If the deviation starts to increase again, it must pass the threshold ONOFF_H for the output to pass to state 0.
STS RAISE1
%M, %Q
SP
-
+
DEV_L DEV_H
PV
35012329 02 May 2007
125
Calculation functions
Operating modes The ON OFF 2 states loop controller has two operating modes: z z
Automatic mode: the output is calculated by the loop controller.
Manual mode: the loop controller does not set the output. You can directly modify the value of the variable connected to the output.
On a cold start the output in manual mode is at state 0.
Operation monitoring z z
An error in execution is signaled in the following cases:
A non-floating input data item is detected on one of the parameters.
A problem appears in the floating-point calculation.
z z
Low threshold > 0.
High threshold < 0.
In each case, the error is considered to be serious. The regulation loop output is frozen and the faults are signaled in the status words.
126
35012329 02 May 2007
Calculation functions
ON OFF 3 states loop controller
Description The ON OFF 3 states loop controller is used to process simple process controls, for which discrete 3 position monitoring is adequate.
Control of the 2 actuators is performed according to the position of process value/ setpoint deviation in relation to 2 thresholds (a high threshold and a low threshold).
This threshold management integrates a parameterized hysteresis. This loop controller can, for example, be used to regulate, as discrete a heat /cool process.
For more complex process controls, it is preferable to use a PID loop controller.
Functional diagram:
STS_ RAISE1
STS_ LOWER1
DEV = PV - SP
ONOFF_H
HYST
Time
HYST
ONOFF_L
35012329 02 May 2007
127
Calculation functions
Parameters Input parameters:
Parameter Symbol
Process value PV
Setpoint value SP
Internal parameters:
Parameter Symbol
Type Limits
Floating point -3.4E38 / 3.4E38
Floating point -3.4E38 / 3.4E38
/
/
Default value
Low threshold ONOFF_L
High threshold
ONOFF_H
Hysteresis HYST
Type Limits
Floating point -3.4E38 / 3.4E38
Floating point -3.4E38 / 3.4E38
Default value
-5.0
5.0
Floating point ONOFF_L /
ONOFF_H
0.0
Output parameters:
Parameter Symbol Type Limits
Process value
/ setpoint deviation
DEV
STS_RAISE1 OUT1 command status
OUT2 command status
Auto_Man
STS_LOWER1
STS_M_A
OUT1
Floating point -3.4E38 / 3.4E38
Bit
Bit
Bit
Bit
/
/
/
/
Command value
Command value
OUT2 Bit /
/
/
/
/
/
/
Default value
R/W
R
R
R/W
R
R
R
R
R
R
R/W
R/W
R/W
R/W
128
35012329 02 May 2007
Calculation functions
Operating modes The ON OFF 3 states loop controller has two operating modes: z Automatic mode: the STS_LOWER1 and STS_RAISE1 outputs are calculated by the loop controller.
z Manual mode: the loop controller does not set the outputs. You are able to modify directly the value of the variable connected to the STS_LOWER1 et
STS_RAISE1 outputs.
Operating modes and associated commands:
STS_RAISE1
HY
%M,%Q
ONOFF_L
SP
-
PV
+
ONOFF_H
%M,%Q
STS_LOWER1
Operation monitoring z z z z
An error in execution is signaled in the following cases:
A non-floating input data item is detected on one of the parameters.
A problem appears in the floating point calculation.
Low threshold > 0.
High threshold < 0.
In each case, the error is considered to be serious. The regulation loop output is frozen and the faults are signaled in the status words.
35012329 02 May 2007
129
Calculation functions
PID
Description The PID function executes a PID algorithm with a mixed (serial / parallel) or parallel z z z z z z z z z z z z structure. It has the following functions: z Calculation of proportional, integral and derivative actions in incremental or absolute format.
Antisaturation of the integral action.
Direct or inverse action.
Derivative from the process value or from the deviation.
Parametering of the transient gain of the derivative.
Integral band
Feed forward action to compensate for interference.
Dead band on deviation.
High and low limitation of the output signal.
Limit of the gradient of the output signal.
Output shifting, also called manual integrated.
Selecting Automatic / Manual operating mode.
z
Tracking Mode.
Autotuning of the principle coefficients.
Transfer function The PID transfer function depends on the structure used (mixed or parallel structure):
Mixed structure
OUT = kp
⋅
⎜
⎛
⎜
⎜
⎝
1 + + ----------------------------
1 + td kd
⋅ p ⎠
⎟
⎟
⎞
⎟
⋅
IN
Parallel structure
OUT =
⎜
⎜
⎛
⎜
⎝ kp +
α ⋅
----------ti p
+
α ⋅
----------------------------
1 + td kd
⋅ p ⎠
⎟
⎟
⎞
⎟
⋅
IN
α
= scale factor =
OUT_SUP - OUT_INF
PV_SUP - PV_INF
Note : The user parameter Kp can be specified :
• even in physical scale, so kp = KP,
• or on a standardized scale, so kp =
α
KP
130
35012329 02 May 2007
Functional diagram of the mixed PID
Calculation functions
This diagram illustrates the principle of the mixed structure PID. It does not represent the implementation of the algorithm in incremental format.
OUTFF
PV_SUP
-
SP
PV_INF
DEV
+
DBAND
Integral action ti, K,
INT_BAND
+
+
+
Proportional action kp
PV
Derivative
action td, kd, K
Manu / Auto
PV
SP
OUT_MAN
TR_I
Autotuning
OUT_MAN
Tracking
OUT_SUP
Limiter
OUT_INF
Gradient limiter
OUTRATE
+
Direct
Reverse +
+
OUTBIAS
35012329 02 May 2007
131
Calculation functions
Function diagram of the parallel PID
This diagram illustrates the principle of the PID parallel structure. It does not represent the implementation of the algorithm in incremental form.
OUTFF
Proportional action kp
OUTFF_INF OUTFF_SUP
DEV + +
PV_SUP
-
SP
PV_INF
+
DBAND
Integral action ti, K, INT_BAND
+
+
Direct
Reverse +
+
OUTBIAS
PV
Derivative action td, kd, K
Manu / Auto
OUT_MAN
PV
SP
OUT_MAN
Autotuning
TR_I
Tracking
OUT_SUP
Limiter
OUT_INF
Gradient limiter
OUTRATE
132
35012329 02 May 2007
Calculation functions
PID parameters
Mixed or parallel structure z z
When the loop controller has a mixed structure (default configuration), the proportional action is applied downstream of the integral and derived actions. The gain K applied to these actions is then equal to kp (See
).
When the loop controller has a parallel structure, the proportional action is applied parallel to the integral and derived actions. In this case the gain kp is not applied to the integral and derived actions. The gain K is simply equal to the relation between the output scale and the process value scale.
Direct or inverse action
The direction of the PID loop controller can be adapted to that of the actuator/ process pair. The action can be defined in the opposite direction (default configuration) or in the same direction.
If the action is direct a positive gap (PV – SP) leads to an output increase.
If the action is inverse a positive gap (PV – SP) leads to an output decrease.
Derivative action The derivative action can act upon the process value or the gap.
Manu / Auto switching
The absolute form of the algorithm allows Manu / Auto switching without bumps (See
Common operating modes for process control loops, p. 292 ).
35012329 02 May 2007
133
Calculation functions
Adjustment parameters
Internal parameters:
Parameter Symbol
Lower limit of the process value scale
High limit of the process value scale
PV_INF
PV_SUP
Lower limit of the output scale
OUT_INF
High limit of the output scale
Proportional gain
OUT_SUP
KP
Integration time
(s)
TI
Derivation time
(s)
TD
Derivative gain KD
Dead band on deviation
DBAND
Manual compensation of the static gap
OUTBIAS
OUTRATE Limiting the output variation, in units s
Integral band INT_BAND
Type Limits
Floating point -3.4E38 / 3.4E38
Default value
0.0
R/W
R/W
Floating point -3.4E38 / 3.4E38
100.0
R/W
Floating point -3.4E38 / 3.4E38
0.0
Floating point -3.4E38 / 3.4E38
100.0
Floating point 0.0 / 3.4E38
Floating point 0.0 / 3.4E38
1.0
0.0
Floating point 0.0 / 3.4E38
Floating point 1.0 / 3.4E38
Floating point 0.0 / 3.4E38
Floating point -3.4E38 / 3.4E38
0.0
0.0
10.0
0.0
R/W
R/W
R/W
R/W
R/W
R/W
R/W
Floating point 0.0 / 3.4E38
Floating point 0.0 / 3.4E38
0.0
0.0
R/W
R/W
R/W
134
35012329 02 May 2007
Dead band on deviation
Calculation functions
The dead band on deviation (DBAND) is used to limit small recovery bumps to actuator to the function point. As long as the gap remains smaller than DBAND (in absolute value), the loop controller assumes it to be nil for its calculations.
Modified deviation
DEV
DBAND
Integral band The integral band defines a zone (around the setpoint) in which the integral action is calculated. When the process value / setpoint gap is greater than this band the integral action is frozen.
The integral band is limited to the proportional band (100 / Kp).
SP
Time
INT_BAND
BIAS on the command
If the integral action is not used (Ti = 0), the use of BIAS on the PID command
(OUTBIAS), is used to guarantee precision of the function point.
If Ti is different from 0, OUTBIAS is not taken into account.
35012329 02 May 2007
135
Calculation functions
Detailed PID equations
136
35012329 02 May 2007
Introduction
35012329 02 May 2007
Calculation functions
The PID algorithm uses the loop controller parameters (See
) as well as the intermediate variables and the following functions.
Intermediate variables and functions:
Variable/Function
TermP
TermI
TermD
TermFF
(new)
(old) kp
Description
Proportional action value.
Integral action value.
Derived action value.
Feed forward action value (disruption compensation).
Indicates a calculated value during the current execution of the algorithm.
Indicates a value calculated during the previous execution of an algorithm.
Proportional gain. This user parameter can be specified either on a physical scale or on a standardized scale:
• Physical scale : kp = KP
• Standardized scale : kp =
α
. KP
K Integral and derived action gains. The gain varies according to the loop controller structure (mixed or parallel) and the presence of the proportional action:
• If the structure is mixed and kp <>0, then
K = kp
• If the structure is parallel or kp=0, then
K =
α
= scale factor =
OUT_SUP - OUT_INF
PV_SUP - PV_INF
VAR
Direction
T_ECH
Function
Δ
Limit function z z
Variable used in the derived action formula. Its value depends on the "Derived action" parameter:
VAR = PV if the derived action is on the process value.
VAR = DEV if the derived action is in the deviation.
z z
Direction = +1 if action is direct. A positive deviation (PV -
SP) leads to an output increase.
Direction = -1 if action is inverse. A positive gap (PV - SP) leads to an output decrease.
Sampling period.
Δ
(x(t)) = x(t) - x(t-1)
Corrector output limit function.
137
Calculation functions
Absolute form of the algorithm
If Ti = 0 , the absolute form of the algorithm is used. The loop controllers are of type
P or PD.
OUT = TermP + TermD + TermFF + OUTBIAS
OUTD = OUTP(new) - OUTP(old)
OUT = limit (OUT) (not implemented)
TermP = sens kp DEV
TermD = td TermD old
)
+ sens K td kd kd dt +
⋅ td
(
VAR new
)
– VAR old
) )
Incremental form of the algorithm
If Ti <> 0 , the incremental form of the algorithm is used. The loop controllers are of type PID.
OUTD =
Δ
TermP + TermI +
Δ
TermD +
Δ
TermFF
OUT = OUT(old) + OUTD(new), default mode
OUT = RCPY + OUTD(new), actuator position copy mode. This mode is used in certain special cases where the actuator position can be different from the calculated output of the PID (SERVO output, cascaded loop or auto selector loop).
OUT = limit (OUT)
Δ
TermP =
⋅ ⋅ Δ (
DEV
)
Δ
TermD =
Δ
⎛
⎝ td TermD old
)
+
⋅ ⋅ ⋅ kd dt +
⋅ td
(
VAR new
)
– VAR old
) ) ⎞
⎠
Antisaturation
Pure integral mode
The integral antisaturation mechanism is implicit in the algorithm.
The loop controller is able to work in pure integral mode (kp = 0). In this case the equations are as follows:
OUTD = TermI + TermFF
OUT = OUT(old) + OUTD(new), default mode
OUT = RCPY + OUTD(new), actuator position copy mode
OUT = limit (OUT)
TermI = sens .
α
. T_ECH/TI . DEV
138
35012329 02 May 2007
Operation monitoring
Calculation functions
A running error is signaled in the following cases: z z z
A non-floating input datum is detected on one of the parameters.
A problem appears in calculating in floating-point mode.
The output scale is incoherent on cold start of the PLC (OUT_INF >= OUT_SUP).
In each case, the error is considered to be serious. The loop output is frozen and the faults are signaled in the status words.
35012329 02 May 2007
139
Calculation functions
Model loop controller
Description
Diagram of the principal
The model loop controller is used where there are significant pure delays in relation to the time constant of the process, a case which cannot be processed satisfactorily by classic PID process control. The model loop controller is also useful for regulating a non-linear process.
The model is first order + delay. Nevertheless, this loop controller can process any z z z z stable or aperiodic process, whatever its order. The parameters to be given are:
The static gain (delta process value/delta command ratio in open loop).
The equivalent time constant (response time/3).
The process pure delay value (estimated value).
The time constant in open loop/time constant in closed loop ratio.
The diagram of principal of the model loop controller algorithm is as follows:
FF
SP
-
+
PV
-
1
Ks
+
+
OUTP
PROCESS
RCPY
DMO
MODEL
PROCESS
140
35012329 02 May 2007
Installing the loop controller
Calculation functions
Installing the model loop controller is similar to installing a PID loop controller. The adjustment of PID parameters KP, TI and TD being replaced by gain adjustment, the time constant, the pure delay of the process model and the ratio of the time constants in open and closed loop.
The model loop controller has the same inputs and outputs as a PID (PV, RSP, FF,
OUTP). It also has the RCPY optional input (model external input) which can be used to input the process’s real input (the flow measured on output from a valve, for example).
Note: The DMO model output is not directly comparable to the PV process value.
At this level, the model does not take into account Ks static gain and possible compensation (BIAS).
Functions z z z z z z z z
The functions other than the command calculation are identical to those of the PID:
Direct or inverse action.
Feed forward action to compensate for disruptions.
Dead band on deviation.
High and low limit of the output signal.
Limit of the output gradient.
Selecting Automatic / Manual operating mode.
Tracking Mode.
Autotuning of the main coefficients.
35012329 02 May 2007
141
Calculation functions
Delay management
In the processs used by this loop controller, the delay is either: z Variable (transfer of matter according to the flow in a circuit, speed of the transport base, for example). z Very large.
These two cases are processed using a register (buffer) of size which can be parameterized. According to the size of this register, it will be possible to sample either all the sampling periods, one period in two, or one period in three etc.
It is possible to increase or decrease the delay T_DELAY during the execution of the program. The new delay is applied instantly, as long as it is compatible with the size of the register. The sampling period of the delay remains unchanged.
If the value of T_DELAY becomes too large compared to the size of the register it becomes impossible to store enough input values to reach the required delay, if the sampling is done in the same period. Therefore, the sampling period of the delay is recalculated and the output is only valid after a time equal to the new delay. To avoid this problem, you are advised to set the size of the register, taking into account the possible increases in the delay T_DELAY.
If the delay decreases by default the sampling does not change. All the same, it is possible to order a new sampling calculation if necessary.
In the case of a dynamic modification of the task time or the sampling period, the output is only valid after a time equal to the delay.
All dynamic modifications of T_DELAY between 0 s and 30 s is taken into account immediately without changing the sampling of the register.
Example
Sampling period
Size of delay register
Delay
Therefore, the delay register is sampled every 2 T_ECH
T_ECH = 300 ms
50
T_DELAY = 25 s
50 x 2 x 0,3 = 30 s > 25 s
142
35012329 02 May 2007
Function diagram
Calculation functions
The function diagram of the model loop controller is as follows:
OUTFF
OUTFF_INF OUTFF_SUP
Feed forward
Model e
-T_DELAY.p
1
1+OL_TIME.p
PV_SUP
-
SP
PV_INF
+
DEV
DBAND
+
-
PV
1/Ks
Direct
Reverse +
+
1+OL_TIME.p
1+
OL_TIME
CL_PERF
.p
OUT_SUP
RCPY
Limiter
OUT_INF
Manu / Auto
PV
SP
OUT_MAN
Autotuning
TR_I
OUT_MAN
Tracking
OUT_SUP
Limiter
OUT_INF
Gradient limiter
OUTRATE
35012329 02 May 2007
143
Calculation functions
Model loop controller parameters
Direct or inverse action
The direction of the PID loop controller can be adapted to that of the actuator torque
/ process. The action can be defined in the opposite direction (default configuration) or in the same direction.
144
35012329 02 May 2007
Adjustment parameters
Calculation functions
Internal parameters:
Parameter Symbol Type Limits Default value
0.0
R/W
Lower limit of the output scale
High limit of the output scale
OUT_INF
OUT_SUP
Static gain of the process in open loop
KS
Time constant of the process in open loop
OL_TIME
Ratio of natural time constant
(open loop) to desired time constant
(closed loop)
CL_PERF
Current pure delay of the process(s)
T_DELAY
Dead band on deviation
DBAND
Command copy input
(optional)
RCPY
Model output
(optional)
Delay register
(obligatory)
/
DMO
Floating point -3.4E38 / 3.4E38
Floating point -3.4E38 / 3.4E38
Floating point 0.0 / 3.4E38
Floating point 0.0 / 3.4E38
Floating point 0,1 / 3.4E38
Floating point 0.0 / 3.4E38
Floating point 0.0 / 3.4E38
%IW, %MW -32768 / 32767
%MF
%MF:n (**) /
-3.4E38 / 3.4E38
/
/
/
100.0
1.0 (*)
1.0 (*)
1.0
0.0
0.0
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R
(*) KS and OL_TIME cannot take the value 0 (inconsistent value). They will be forced to the value 1.0.
(**) n corresponds to the size of the register and must be greater than 0.
35012329 02 May 2007
145
Calculation functions
Dead band on deviation
Output parameters
Limits
Operation monitoring
Dead band on deviation is identical to the PID loop controller (See PID parameters,
).
You can access the value of the command OUT_MAN, but also the delayed output value of the DMO model.
The integrating processes are not managed by the model loop controller.
You can use a Servo drive without output copy because the model loop controller does not implement an incremental algorithm (the command value is calculated and then the command variation).
z z z
A running error is signaled in the following cases:
A non-floating point input data item is detected on one of the parameters.
A problem appears in the floating-point calculation.
The output scale is inconsistent on cold start of the PLC (OUT_INF >=
OUT_SUP).
In each case, the error is considered to be serious. The loop output is frozen and the faults are signaled in the status words.
146
35012329 02 May 2007
Calculation functions
Autotuning
Description The autotuning function is used to gain time during the start-up of an installation by guaranteeing a stable adjustment.
The autotuning algorithm is based on a method of Ziegler-Nichols type: z Analysis of the procedure for checking if this is first order with delay. The length of this analysis is 2.5 times the response time of open loops.
z Calculation of PID adjustment parameters (KP, TI, TD) or those of the model loop controller (KS, T1, T_DELAY). The range of set parameters is moduled by performance criteria in order to prioritize the response time to disruptions or stability.
Process types z z z
The algorithm processes the following process types:
Single input and single output processes.
Naturally stable processes or integrators.
Asymmetric processes in the limits allowed by the PID algorithm.
Autotuning types There are two possible autotuning types: warm or cold autotuning. The first phase of autotuning is the same for each of these: Noise and stability test of the process of length 0.5x AT_TMAX during which the outputs remain constant. The following phases depend on the type of autotuning. The selection is made automatically by the algorithm.
35012329 02 May 2007
147
Calculation functions
Cold autotuning Cold autotuning is performed if the deviation between process value and setpoint exceeds 40% and if the process value is less than 30%. Two scales in the same direction are then applied to the loop controller output (OUT_MAN). Each scale has a length of AT_MAX.
When autotuning is complete, the loop assumes its previous operating mode.
SP
PV
AT_MAX AT_MAX
AT_MAX/2
OUT_MAN
Mode
Programmed or Manual mode
Adjustment mode
STS_AT_RUNNING
Automatic or Manual mode
Time
148
35012329 02 May 2007
Calculation functions
Warm autotuning If cold autotuning conditions are not fullfilled, warm autotuning is performed. A scale is applied to the loop controller output (OUT_MAN), then an inverse scale. Each scale has a length of AT_MAX.
When autotuning is complete, the loop assumes its previous operating mode.
AT_MAX/2 AT_MAX AT_MAX
PV
SP
OUT_MAN
STS_AT_RUNNING
Mode
Programmed or Manual mode
Adjustment mode Automatic or Manual mode
35012329 02 May 2007
149
Calculation functions
Autotuning parameters
Internal parameters
Internal parameters of the autotuning function are as follows:
Parameter Symbol Type Limits
Floating point -100.0 / 100.0
Default value
10.0
Size of command division (%)
Duration of the scale (s)
Criteria for autotuning performance
Proportional gain
Integral time
(s) (*)
Derivation time (s) (**)
Model gain
(***)
Model time constant (s)
(***)
Model delay
(s) (***)
AT_STEP
AT_TMAX
AT_PERF
KP
TI
TD
KS
T1
T_DELAY
Floating point 4,0 / 3.4E38
Floating point 0.0 / 1.0
Floating point 0.0 / 3.4E38
Floating point 0.0 / 3.4E38
Floating point 0.0 / 3.4E38
Floating point 0.0 / 3.4E38
Floating point 0.0 / 3.4E38
Floating point 0.0 / 3.4E38
100.0
0.5
1.0
0.0
0.0
1.0
0.0
0.0
(*) According to the loop controller used (PID or model loop controller).
(**) See PID loop controller (See
).
(***) See model loop controller (See
).
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
150
35012329 02 May 2007
Output parameters
Calculation functions
For the output parameters, the range of variation (limits) and default value have no object. Therefore, these columns have not been given in the table in order to make it more readable.
Output parameters of the autotuning function are as follows:
Parameter
Value before proportional co-efficient autotuning or model gain
Symbol
KP_PREV
Value before integral coefficient autotuning or time constant model
Value before derived coefficient autotuning or model delay
Autotuning in progress
Autotuning failed
Autotuning diagnostics interrupted
Autotuning diagnostics parameter error
TI_PREV
TD_PREV
STS_AT_RUNNING
AT_FAILED
AT_ABORTED
AT_ERR_PARAM
Autotuning diagnostics system error or power failure
Autotuning diagnostics process value or actuator saturation
AT_ERR_PWF_OR_SYS_FAILURE
AT_ERR_SATUR
Autotuning diagnostics insufficient process value deviation
AT_ERR_DV_TOO_SMALL
Autotuning Diagnostics sampling period too large
AT_ERR_TSAMP_HIGH
AT_ERR_INCONSISTENT_RESPONSE Autotuning diagnostics inconsistent response
Autotuning diagnostics process value initially unstable
Autotuning diagnostics scale period too small
AT_ERR_NOT_STAB_INIT
AT_ERR_DV_TOO_SMALL
Floating point
Floating point
Bit
Bit
Bit
Type
Floating point
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
R
R
R
R/W
R
R
R
R
R
R
R
R
R
R
R
35012329 02 May 2007
151
Calculation functions
Parameter
Autotuning diagnostics process value noise too high
Autotuning diagnostics division period too large
Autotuning diagnostics overshoot > 10%
Autotuning diagnostics minimum phase undershoot
Autotuning diagnostics procedure too nonsymmetrical
Autotuning diagnostics integrating process
Symbol
AT_ERR_NOISE_TOO_HIGH
AT_ERR_TMAX_TOO_HIGH
AT_WARN_OVERSHOOT
AT_WARN_UNDERSHOOT
AT_WARN_UNSYMETRICAL_PLANT
AT_WARN_INTEGRATING_PLANT
Type
Bit
Bit
Bit
Bit
Bit
Bit
R
R
R
R
R
R/W
R
152
35012329 02 May 2007
Calculation functions
Autotuning process
Adjustment mode
Step function parametering
Maximum duration of the step function z z
Analysis of the process is divided into 3 stages:
Noise and stability analysis of the process.
First analysis of the response to a step function which provides a first identification model. From this first estimate a filter is calculated to be used in the second analysis.
z A second analysis of the response to a second step function, refined by using a data filter. A full process model is thus obtained.
After each of these two analyses, a set of loop controller parameters to be adjusted is calculated. The equations giving these loop controller parameters are based on the gain and the ratio of response time to process delay.
If the difference between these two analyses is too great, the model’s estimate is rejected and autotuning fails. The loop controller output is set back to its value before the start of autotuning.
On a robust level, the algorithm must be capable of supporting the gain and time constant changes in a ratio 2, without losing its stability. The asymmetrical processes are supported as long as they follow these constarints. If this is not the case, an error is signaled by the diagnostics.
The 2 step functions applied to the output during the autotuning process are z z characterized by 2 parameters:
The duration of the step function AT_TMAX, which must be greater than 4 s.
The amplitude of the step function AT_STEP, which must be greater than 1% of the output scale (OUT_INF, OUT_SUP).
The function also checks that the output does not go beyond the output scale limits.
This checking is done as the autotuning starts.
The maximum value of AT_TMAX is limited by the task cycle time into which the loop is configured. This value, in seconds , can be configured to a maximum of 65.5 x task cycle time (en ms) .
For example, if the task MAST = 50 ms, AT_TMAX = 65.5 x 50 = 3275 seconds maximum.
35012329 02 May 2007
153
Calculation functions
Parameter values
As an indication, the following table gives the parameter values for some classic process control types:
Scheme type
Liquid flow or pressure
Gas pressure
Level
Steam temperature or pressure
Composition
AT_TMAX (s)
5 - 30
60 - 300
120 - 600
600 - 3600
600 - 3600
AT_STEP (%)
10 - 20
10 - 20
20
30 - 50
30 - 50
Performance criterion
The loop controller adjustment can be done according to the performance criterion value AT_PERF.
The AT_PERF parameter varies between 0 and 1, which means it is possible to prioritize stability for AT_PERF close to 0 or to obtain a more dynamic adjustment
(and therefore to optimize response time to disruptions) by pushing AT_PERF towards 1.
Note: The parameters AT_PERF, AT_TMAX et AT_STEP are unique to each process control channel. There is therefore more than one set of parameters for the 3 single, cascade or auto-selector loop controllers. Consequently, for one process control channel, one autotuning operation can be activated and executed at a given instant.
154
35012329 02 May 2007
Calculation functions
Autotuning operating modes
Autotuning commands
Different commands are used to drive the autotuning function: z Starting autotuning (%MWxy.i.11 = 16#000E)
This command is used to start the autotuning process. It can be directly activated z from the autotuning function grid.
Stopping autotuning (%MWxy.i.11 = 16#000F)
This command is used to stop the autotuning process. In this case the PID parameters are not modified and a diagnostic is performed.
z Return to the previous tuning event (%MWxy.i.11 = 16#0010)
This command is used to swap the current loop controller parameters with the previous ones (KP_PREV, TI_PREV, TD_PREV). This command is not allowed if an autotuning event is in progress.
Autotuning operating modes z z
At the start of autotuning, the loop controller can be in automatic or manual mode.
When the autotuning begins, it passes into adjustment mode and the output keeps the last imposed or calculated value. At the end of the autotuning:
If it has succeeded, the loop reverts to its previous mode (automatic or manual).
If the autotuning has failed, the output is initialized to the value from before the autotuning, the adjustments are not done and the loop reverts to its previous mode (automatic or manual).
The direction of loop controller action is checked and compared with model’s gain sign. If there is incompatibility an error is signaled.
35012329 02 May 2007
155
Calculation functions
Diagnostics parameters
Autotuning diagnostics z z z
For different reasons the autotuning process can: not be started, be aborted during execution, fail by proposing a set of parameters (or not) according to the cause of failure.
Acknowledgment The diagnostics message acknowledgement function is accessible from the PL7 screen or by the acknowledgement commands.
Note: The diagnostics message is unique to each process control channel. There is only one message for the 3 loops of the 3 single loop controllers, or for the 2 loops of the Cascade and Auto-selector loop controllers.
Reasons for the autotuning not starting
The following errors cause the autotuning not to start: z Parameter error (Bit 2: AT_ERR_PARAM)
The possible causes of a parameter error are as follows: z Duration of division too small (AT_MAX < 4 s).
z z
Amplitude too small (AT_STEP < 1% of output scale).
Impossible test protocol. If the current output + n times the size of the scale (n
= 1 for a hot autotuning and n = 2 for a cold autotuning) is outside the output scale (OUT_INF, OUT_SUP), the test protocol will no longer be applicable. z
STEP_AMPL must be set to a value compatible with the current function point.
Incorrect sampling period (Bit 6 : AT_ERR_TSAMP_HIGH)
If the sampling period is too large in relation to the length of the scale (greater than AT_TMAX/25), the analysis of the response will not be precise enough and the autotuning is inhibited. This case is specific to very quick process controls
(AT_TMAX increasing the process’s stabilization time by some seconds). TMAX can therefore be increased, as the algorithm is not very sensitive to this parameter (in a ratio from 1 to 3) or adjust the sampling period.
Reasons for the autotuning being aborted
Several causes lead to the autotuning abort (See
Aborting autotuning, p. 157 ).
156
35012329 02 May 2007
Calculation functions
Aborting autotuning
Stopping after a system fault
Bit 3: AT_ERR_PWF_OR_SYS_FAILURE
Autotuning is aborted if a system PLC event appears, not allowing the sequence to progress completely. For example, disconnection will automatically stop the autotuning function when the power returns.
Saturation of the process value
Bit 4: AT_ERR_SATUR
If the process value leaves the interval of the full scale (PV_INF, PV_SUP), autotuning is aborted and the loop controller reverts to its previous mode. Predicting the future process value even allows the autotuning to be stopped before the overflow occurs (when a first model has been identified).
Insuffiecient variation
Bit 5: AT_ERR_DV_TOO_SMALL
The amplitude of the step function is not large enough to cause a significant process reaction. Therefore it is possible to increase AT_STEP.
PV
PV < 2% t
35012329 02 May 2007
157
Calculation functions
Inconsistent response
Bit 7: AT_ERR_INCONSISTENT_RESPONSE
The process response is inconsistent (gains of different sign). This can be due to a significant disruption, coupling with other loops, etc. The autotuning is stopped and a diagnostic is generated.
PV t
Noise too high Bit 10: AT_ERR_NOISE_TOO_HIGH
The process reaction to the step function is not large enough in relation to the noise.
Filter the process value or increase AT_STEP
PV t
158
35012329 02 May 2007
Calculation functions
Duration of the division
(AT_TMAX) too short
Bit 9: AT_ERR_TMAX_TOO_SMALL
The response is not stabilized until the initial command returns. The calculated parameters are therefore false.
PV
Division test Process reaction t
Process value initially not stabilized
Bit 8: AT_ERR_NOT_STAB_INIT
Starting autotuning happens while the process value was not stabilized. If the process value variation is significant in relation to the division, the test results will be false.
PV t
35012329 02 May 2007
159
Calculation functions
Duration of division
(AT_TMAX) too long
Bit 11: AT_ERR_TMAX_TOO_HIGH
AT_TMAX determines the taking into account frequency of the process values which are used to calculate the co-efficients. The AT_TMAX must be between 1 and 5 times the process ascent time.
PV t
Large overshoot process
Bit 12: AT_WARN_OVERSHOOT
This bit is positioned in state 1 if the reaction to a command division prompts an excessive process value overshoot (greater than 10%). The process does not correspond to the models treated by the algorithm.
Non-minimum phase process
Bit 13: AT_WARN_UNDERSHOOT
This bit is positioned in state 1 if the reaction to a command scale prompts a response inversion in its initial phase (undershoot greater than 10%). The process does not correspond to the models treated by the algorithm.
Non-symmetrical process
Bit 14: AT_WARN_UNSYMETRICAL_PLANT
The process is non-symmetrical.
PV
160 t
35012329 02 May 2007
Integrating process
Calculation functions
Bit 15: AT_WARN_INTEGRATING_PLANT
Either it is an integrating process or AT_TMAX is too small and the process nonsymmetrical. The calculated co-efficients correspond to the integrating process. If this is not the case, restart autotuning having increased AT_TMAX.
PV t
35012329 02 May 2007
161
Calculation functions
Split Range
Description
Function parametering
This function is useful if two actuators are used to cover the whole print range of the adjustment spectrum. It is placed downstream of the loop controller.
The Split Range function also has the following functions: z z
It manages overlaps as well as dead bandwidths between the two actuators.
Manual command and a manual order (consistent with a single PID) can be used.
The Split Range function is used to manage analog outputs as well as servo drives with copy. It cannot be used to manage servo drives without copy.
When this function is used, the loop controller output scale must be (0.100).
Parametering the function defines the characteristics of each actuator, in other words, the way in which the two outputs should vary between the two thresholds.
The output value varies in a linear fashion. Outside the two thresholds, output is limited to pre-set thresholds.
Commands
OUT1_SUP
OUT2_SUP
OUT1
OUT2_INF
OUT1_INF
0% OUT1_TH1 with OUTi_THj: output i threshold j
OUT2_TH1
OUT1_TH2
OUT2
OUT_MAN (%)
OUT2_TH2 100%
162
35012329 02 May 2007
Function parameters
35012329 02 May 2007
Calculation functions
Input parameter:
Parameter Symbol
Command value
OUT_MAN
Internal parameters:
Parameter Symbol
Value of OUT1 for OUT_MAN =
OUT1_TH1
OUT1_INF
Value of OUT1 for OUT_MAN =
OUT1_TH2
OUT1_SUP
Value of OUT2 for OUT_MAN =
OUT2_TH1
OUT2_INF
Value of OUT2 for OUT_MAN =
OUT2_TH2
OUT2_SUP
Input value for which OUT1 =
OUT1_INF
OUT1_TH1
OUT1_TH2 Input value for which OUT1 =
OUT1_SUP
Input value for which OUT2 =
OUT2_INF
OUT2_TH1
Input value for which OUT2 =
OUT2_INF
OUT2_TH2
Output parameters:
Parameter Symbol
Limiting the output 1 variation in %/s
OUTRATE
Type Limits
Floating point
0.0 / 100.0
/
Default value
R/W
R/W
Type Limits
Floating point
-3.4E38 / 3.4E38
Default value
0.0
Floating point
-3.4E38 / 3.4E38
100.0
Floating point
-3.4E38 / 3.4E38
0.0
Floating point
-3.4E38 / 3.4E38
100.0
Floating point
0.0 / 100.0
0.0
50.0
Floating point
0.0 / 100.0
Floating point
0.0 / 100.0
50.0
Floating point
0.0 / 100.0
100.0
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
Type Limits
Floating point
0.0 / 3.4E38
Default value
0.0
R/W
R/W
163
Calculation functions
Operation monitoring
Parameter Symbol
Limiting the output 2 variation in %/s
OUTRATE2
Type Limits
Floating point
0.0 / 3.4E38
Default value
0.0
R/W
R/W
A running error is signaled in the following cases: z z
A non-floating input datum is detected on one of the parameters.
A problem appears in a calculation in floating point mode.
In all cases, the error is considered to be serious. The loop output is frozen and the faults are signaled in the status words. A (warning) fault is also signaled if the
OUT1_TH1, OUT1_TH2, OUT2_TH1 and OUT2_TH2 thresholds are not between 0 and 100%.
164
35012329 02 May 2007
Calculation functions
Heat/Cool
Description
Function parametering
This function is useful if two opposing actuators are used to cover the whole range of the adjustment spectrum. It is placed downstream of the loop controller.
The Heat/Cool function also has the following operating processes: z z
It manages overlaps as well as dead bandwidths between the two actuators.
Manual command and a manual order (consistent with a single PID) can be used.
The Heat/Cool function is used to manage analog outputs as well as servo drives with copy. It cannot be used to manage servo drives without copy.
When this function is used, the loop controller output scale must be (0.100).
Function parametering defines the characteristics of each actuator, in other words, the way in which the two outputs should vary between the two thresholds.
The output value varies in a linear fashion. Outside the two thresholds, the output is limited to pre-set thresholds.
Output 1 manages the "cool" and output 2 manages the "heat".
Commands
OUT1_SUP
OUT2_SUP
OUT2_INF
OUT1_INF
OUT1
0% OUT1_TH1 OUT1_TH2 OUT2_TH1
OUT2
OUT_MAN (%)
OUT2_TH2 100% with OUTi_THj: output i threshold j
35012329 02 May 2007
165
Calculation functions
Function parameters
Input parameter:
Parameter Symbol
Command value OUT_MAN
Type Limits
Floating point
0.0 / 100.0
/
Default value
R/W
R/W
Internal parameters:
Parameter Symbol
Value of OUT1 for
OUT_MAN =
OUT1_TH1
OUT1_INF
Value of OUT1 for
OUT_MAN =
OUT1_TH2
OUT1_SUP
Value of OUT2 for
OUT_MAN =
OUT2_TH1
OUT2_INF
Value of OUT2 for
OUT_MAN =
OUT2_TH2
OUT2_SUP
Input value for which OUT1 =
OUT1_INF
OUT1_TH1
OUT1_TH2 Input value for which OUT1 =
OUT1_SUP
Input value for which OUT2 =
OUT2_INF
OUT2_TH1
Input value for which OUT2 =
OUT2_INF
OUT2_TH2
Output parameters:
Parameter Symbol
Limiting the output 1 variation in %/s
OUTRATE
Type Limits
Floating point
0.0 / 3.4E38
Type Limits
Floating point
-3.4E38 / 3.4E38
Default value
0.0
Floating point
-3.4E38 / 3.4E38
100.0
Floating point
-3.4E38 / 3.4E38
0.0
Floating point
-3.4E38 / 3.4E38
100.0
Floating point
0.0 / 100.0
50.0
0.0
Floating point
0.0 / 100.0
Floating point
0.0 / 100.0
50.0
Floating point
0.0 / 100.0
100.0
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
Default value
0.0
R/W
R/W
166
35012329 02 May 2007
Operation monitoring
Parameter Symbol
Limiting the output 2 variation in %/s
OUTRATE2
Type Limits
Floating point
0.0 / 3.4E38
Calculation functions
Default value
0.0
R/W
R/W
A running error is signaled in the following cases: z z
A non-floating input datum is detected on one of the parameters.
A problem appears in a calculation in floating point mode.
In each case, the error is considered to be serious. The loop output is frozen and the faults are signaled in the status words. A (warning) fault is also signaled if the
OUT1_TH1, OUT1_TH2, OUT2_TH1 and OUT2_TH2 thresholds are not between 0 and 100%.
35012329 02 May 2007
167
Calculation functions
5.5
Functions of the output branch,
At a Glance
Subject of this section
What's in this
Section?
z z z z
This section describes the calculation functions of the output processing path:
Servo,
PWM,
Output scaling,
Output format.
This section contains the following topics:
Topic
Servo
Operating process examples of the Servo function
PWM
Output scaling
Output limiter
Output format
Page
168
35012329 02 May 2007
Calculation functions
Servo
Description This function is used to perform process control with the electric servo drives with or without copy position. It uses the loop controller’s digital output to generate 2 logic outputs, RAISE and LOWER.
When this function uses the copy position, it performs a loop control of the actuator position. When the copy position is not used, the loop controller and the associated servo function perform a floating point process control.
If the servo function is used, the loop controller output scale must be (0, 100).
35012329 02 May 2007
169
Calculation functions
Function parameters
Input parameters:
Parameter Symbol
Command value OUT_MAN
Command value
(*)
OUTi
Upper stop
Lower stop
Copy position
/
/
/
Command variation value
OUTD
Floating point
Floating point
Bit
Bit
Floating point
Floating point
(*) With Heat/Cool or Split Range
Internal parameters:
Parameter Symbol Type
0.0 / 100.0
0.0 / 100.0
/
/
0.0 / 3.4E38
-100.0 / 100.0
Limits
Opening time
(s)
Minimum time
(s)
T_MOTORi
T_MINIi
Output parameters:
Parameter Symbol
Type
Floating point
Floating point
0.0 / 3.4E38
0.0 / 3.4E38
Type
Limits
Limits
Open command status
Close command status
STS_RAISEi Bit
STS_LOWERi Bit /
/
/
/
/
/
/
/
Default value
R
R
R
R
R/W
R
R
Default value
10.0
0.0
R/W
R/W
R/W
/
/
Default value
R/W
R
R
170
35012329 02 May 2007
Calculation functions
Servo with copy position (RCPY)
The Servo function operates differently, depending on whether the copy position is used or not.
When the copy position is used, the Servo function generates a binary RAISE or
LOWER command for each new OUT_MAN output value produced by the loop controller. The duration of this command is proportional to the deviation between the loop controller command and the copy position value, which then performs a loop control proportional to the actuator position.
Note: When the calculated period exceeds the loop sampling period (in automatic mode) or the task cycle time (in other operating modes), this is not stored for the next cycles.
Servo without copy position
Pulse period
If copy position is not used, the Servo function generates a binary RAISE or LOWER command for each new command variation value produced by the loop controller.
The duration of this command is proportional to the output variation from the OUTD loop controller.
Note: When the calculated period exceeds the loop sampling period (in automatic mode) or the task cycle time (in other operating modes), the remaining application period is added onto the new period calculation. This enables it to be processed on several cycles.
The Servo function associated to the loop controller is used to perform a floating point process control. The algorithm does not use the loop controller’s absolute output, but the output variation. The RAISE output (or LOWER, depending on the variation sign) is set at 1 for a length of time proportional to the valve opening time
(T_MOTOR) and the OUTD variation value.
The pulse period (T_IMP) to be applied to the output is calculated with the following principle: z An initial theoretical value is given by the formula:
T_IMP = (OUT_MAN - RCPY) (%) x T_MOTOR (with copy position) z z
T_IMP = (T_IMP + OUTD) (%) x T_MOTOR (without copy position)
In order not to generate pulses that are too short, pulses are limited to a minimum time period T_MINI.
When the pulse time calculation gives a value less than T_MINI, the Servo z function does not generate a pulse but stores the value for the next calculation.
This enables correct processing where the output variations of a loop controller are insignificant but lasting.
Without copy position, it is advisable to connect and use position stops in order to prevent the algorithm from becoming saturated.
35012329 02 May 2007
171
Calculation functions
Actuator opening time
Minimum pulse period
Position stops
T_MOTOR actuator opening time enables the function to adapt to different servo drives.
Pulse time to be applied to RAISE or LOWER is proportional to the full scale actuator opening time.
The minimum pulse period T_MINI is used to avoid generating pulses that are too short, and generally harmful to actuators.
When the calculated pulse time to be applied to RAISE or LOWER is less than
T_MINI, the function does not generate a pulse. In all cases, every pulse started lasts for at least the T_MINI period.
When position stop is reached, the RAISE and LOWER outputs are set to 0. The algorithm no longer takes into account the actions going in the direction of the stop.
Operation monitoring z z
An error in execution is signaled in the following cases:
A non-floating input data item is detected on one of the parameters.
A problem appears in a calculation in floating point mode.
In each case, the error is considered to be serious. The loop output is frozen and the faults are signaled in the status words.
If T_MOTOR and T_MINI time parameters are negative, their value is forced to 0.0.
When the loop controller is in manual mode, its OUT_MAN output also controls the
Servo function outputs.
172
35012329 02 May 2007
Operating process examples of the Servo function
Automatic mode with position copy
Operation in automatic mode with copy position .
T_MOTOR = 25 s, T_MINI = 1 s and sampling period = 4 s
OUT_MAN-RCPY deviation
Calculation functions
20%
RAISE
10%
-
2% -2%
LOWER
1 2 3 4
For each step, the operating principle is as follows:
Step
1
2
3
4
Operating principle
The deviation between OUT_MAN and RCPY is 20%. A pulse of 5 s (25 s x
20%) is generated on the RAISE output.
The deviation is 10%. A pulse of 2.5 s (25 s x 10%) is generated on the Raise output, without accounting for the second which remained from the previous pulse.
The deviation is –2%, which would correspond to a pulse of 0.5 s (25 s x 2%) on the LOWER output. As T_MINI equals 1 s, no pulse is generated (in contrast, the 0.5 s duration is stored.
The deviation is always -2%. The corresponding pulse (0.5 s) is added to the previously stored pulse (0.5 s) to give 1 s. As this duration is at least equal to
T_MINI, the pulse is therefore applied to the LOWER output.
35012329 02 May 2007
173
Calculation functions
Automatic mode without position copy
Operating in automatic mode without position copy .
T_MOTOR = 25 s and T_MINI = 1 s
OUTD
20% 22%
2% 2%
RAISE
-24%
LOWER
5s 1s
1 2 3
1s
4 5
In this case, the command variation value is taken into account each time the Servo function is operated.
For each step, the operating principle is as follows:
Step
1
2
3
4
5
Operating principle
The PID output variation is +20%. A pulse of 5 s (25 s x 20%) is generated on the RAISE output.
The PID variation is +2%, which would correspond to a pulse of 0.5 s. As this pulse is less than T_MINI (=1 s.),it does not affect the outputs.
This second PID output variation is +2%. In order to be calculated, the function adds this variation to the previous variation (which was below the minimum value), corresponding to a global variation of +4%. A pulse of 1 s (25 s x 4%) is generated on the RAISE output.
The PID output variation is -24%. A pulse of 6 s (25 s x 24%) is generated on the LOWER output.
Before completion of the following second, a further variation of +22% on the
PID output restores the system to a global variation of –2%. As this variation corresponds to a pulse of 0.5 s (below T_MINI), the function ends by carrying out the minimum pulse of 1 s.
174
35012329 02 May 2007
Calculation functions
Manual mode without position copy
In the case of operating in manual mode without copy position , the opening or closing bit moves to 1 during a period of time which corresponding to the command difference (proportional to period of opening time).
For example, T_MOTOR = 10 s. If the command moves from 30% to 40% then the
RAISE output = 1 during 1 s (10 s x (40%-30%)).
35012329 02 May 2007
175
Calculation functions
PWM
Description This function is used to control a discrete actuator in period modulation. The logic output is set at 1 following a period proportional to the command calculated by the
PID and to the given period modulation. The cyclic ratio of this type of output is defined as being the output activity rate, meaning the time ratio when the output is active throughout the whole period. The cyclic ratio (expressed in %) of a PMW output is therefore equal to the command calculated by the loop controller
(expressed in %).
When the PMW function is used, the loop controller output scale must be (0, 100).
(OUT_MAN/100)xT_ECH
Function parameters
T_PERIOD
T_ECH
Input parameters:
Parameter
Command value
Command value (*)
Symbol Type Limits
OUT_MAN Floating point 0.0 / 100.0
OUTi Floating point 0.0 / 100.0
(*) In the case of Heat / Cool or Split Range
Internal parameter:
Parameter Symbol Type Limits
/
/
Default value R/W
R
R
Default value
0.0
Minimum time (s) T_MINIi Floating point
Output parameter:
Parameter
Command status
Symbol Type
STS_RAISE1 Bit
0.0 / 3.4E38
/
Limits
/
Default value
R/W
R/W
R/W
R
Function period The function period must be chosen according to the characteristics of the actuator.
Therefore it is logical that the function period is equal to the loop controller sampling period because the actuator would not be in a position to take faster account of a sampling command.
176
35012329 02 May 2007
Time base
Resolution
Operation monitoring
Calculation functions
The time base used for modulation is the MAST task period or the FAST task period.
In other words, the smallest available pulse lasts for the task period. However, the user is able to define a minimum pulse that is greater using the T_MINI parameter, so that the actuator constraints may be respected.
The larger the PMW resolution function, the more precise the command carried out will be. The resolution is defined by the relationship between: sampling period / task period. A minimum of 10 is recommended.
For example, if the sampling period = 2 s (chosen according to actuator characteristics), the task period must not exceed 200 ms.
A running error is signaled in the following cases: z z
A non-floating input datum is detected on one of the parameters.
A problem appears in calculating in floating-point mode.
In each case, the error is considered to be serious. The loop output is frozen and the faults are signaled in the status words.
35012329 02 May 2007
177
Calculation functions
Output scaling
Description This function is used to scale the output to the calculated command.
The scaling function is optional. It is used to select the scale according to specific outputs.
If this function is used, it introduces a scale factor. It performs the following calculation:
OUT = (OUT_MAN - OUT_INF) x
OUT_MAX - OUT_MIN
OUT_SUP - OUT_INF
+ OUT_MIN where: OUT_MAN = 0 or -10000 and: OUT_MAX = 10000
OUTi
10000
OUTi
0 or -10000
OUT_MAN
OUT_INFi OUT_MAN OUT_SUPi
178
35012329 02 May 2007
Function parameters
Operation monitoring
Calculation functions
Input parameters:
Parameter
Command value
Symbol Type Limits
OUT_MAN Floating point -3.4E38 / 3.4E38
/
Command value (*) OUTi Floating point -3.4E38 / 3.4E38
/
Default value R/W
R
R
(*) In the case of Heat/Cool or Split Range
Internal parameters:
Parameter Symbol Type Limits
Low scale OUT_INFi Floating point -3.4E38 / 3.4E38
High scale OUT_SUPi Floating point -3.4E38 / 3.4E38
Default value R/W
0.0
R/W
100.0
R/W
Note: In the configuration editor, the symbols OUT_INF and OUT_SUP are called
Lower limit (%) and Upper limit (%).
Output parameter:
Parameter Symbol Type Limits
Command value OUT_MAN Floating point -3.4E38 / 3.4E38
/
Default value R/W
R
Monitoring the parameters of this function is integrated into the error management of the output branch.
35012329 02 May 2007
179
Calculation functions
Output limiter
Description This function is exclusive to the scale output function.
When this function is selected, it enables the scaling of output between the limits of the range defined by the parameters OUT_INFi and OUT_SUPi. In this case, the output scale is between 0% and 100%.
If this function is not activated, the value of the output is limited to the scale of the output defined by OUT_INFi and OUT_SUPi.
The limiter is selected by default with the values for the low limit of 0% and for the high limit of 100%.
OUTi
10000
OUTi
0 or -10000
OUT_MAN
0% OUT_MAN
OUT_INFi OUT_SUPi
100%
180
35012329 02 May 2007
Function parameters
Execution monitoring
Calculation functions
Input parameters:
Parameter Symbol Type Limits
Command value OUT_MAN
Command value
(*)
OUTi
Floating -3.4E38 / 3.4E38
Floating -3.4E38 / 3.4E38
(*) Heat/Cool or Split Range case
Internal parameters:
Parameter Symbol Type Limits
Low scale
High scale
OUT_INFi
OUT_SUPi
/
/
Default value
Floating -3.4E38 / 3.4E38
Floating -3.4E38 / 3.4E38
Default value
0.0
100.0
R/W
R
R
R/W
R/W
R/W
Note: In the configuration editor, the symbols OUT_INF and OUT_SUP are called
Low limit (%) and High limit (%), with:
-5% < OUT_INFi < 105% and -5% < OUT_SUPi < 105%.
Output parameter:
Parameter Symbol Type Limits R/W
Command value OUT_MAN Floating -3.4E38 / 3.4E38
/
Default value
R
The monitoring the parameters of this function is built into the error management of the output branch.
35012329 02 May 2007
181
Calculation functions
Output format
Description This function is used to set the analog output value. 2 formats (or ranges) are z z possible:
Unipolar: 0 / 10000 (default selection).
Bipolar: -10000 / 10000.
Output address assignment
The output address is defined in the graphic section of the configuration screen. You should enter a word type variable (%QW of analog output or %MW).
Function parameters
Input parameters:
Parameter Symbol Type Limits
Command value OUT_MAN
Command value
(*)
OUTi
Floating point
Floating point
-3.4E38 / 3.4E38
-3.4E38 / 3.4E38
(*) In the case of Heat/Cold or Split Range
Internal parameter:
Parameter Symbol Type Limits
/
/
Default value
Range / %KW bit / /
Default value
R/W
R
R
R/W
R/W
182
35012329 02 May 2007
Control loop configuration
6
At a Glance
Subject of this
Chapter
What's in this
Chapter?
This Chapter describes the methods for installing and configuring a control loop in an automation application with a Premium.
This chapter contains the following sections:
Section
6.1
6.2
Topic
Configuring the loop and the inputs/outputs
Configuring MMI ( Man-Machine Interface)
Page
183
35012329 02 May 2007
Configuration
6.1
Configuring the loop and the inputs/outputs
At a Glance
Subject of this section
What's in this
Section?
This section describes the methodology which should be applied to create a process control application with PL7 and the configuration method, and how to use the inputs/outputs associated with the loop controllers.
This section contains the following topics:
Topic
How to configure a process control loop
Configuring the inputs and outputs associated with the process control loops
Page
184
35012329 02 May 2007
Configuration
How to configure a process control loop
At a Glance
Procedure
A process control loop is configured according to a precise methodology which ensures nothing is overlooked.
For each process control loop that is to be implemented, you must follow these steps:
Step
1
2
5
6
3
4
7
8
Action
Give an exact definition of the process control structure to be used (single loop, process loop, cascade loop, self-selective loop).
Define the algorithm of the various processing branches (process value, setpoint, loop controller, etc.).
Select the various functions and parameters for each processing branch.
Enter the input and output interfaces.
Fix the initial values of the adjustment parameters.
If necessary, symbolize the associated language objects.
If necessary, configure the exchanges for level 2 (supervision for example).
Confirm the global configuration.
35012329 02 May 2007
185
Configuration
Configuring the inputs and outputs associated with the process control loops
At a Glance A process control loop must have inputs and outputs in order to operate. The inputs are used to obtain the process values of the procedure and the outputs are used to act on the procedure to be regulated. The inputs are generally analog inputs and the outputs are either analog outputs or discrete outputs (SERVO or PWM function).
The inputs and outputs always belong to modules configured in the PLC.
Note: it is also possible to use words and internal bits which will then be copied in words and output bits, and internal words in which there will already be a copied input value.
How to assign inputs and outputs to a process control loop
The following steps describe the procedure for assigning inputs and outputs to a process control loop.
Step
1
2
Action
Configure the necessary Input/Output modules.
From the configuration screen, enter the addresses of the inputs and outputs in the diagram of the process control loop.
Result : the following figure gives an example of assignment.
PV
%IW4.0
SP1
%MF2
R
L
0.0
I
P
D
0.0
OUT 1
%QW5.0
186
35012329 02 May 2007
Checks
Interface types
Configuration
On assignment of the inputs and outputs, the following checks are perfomed: z In order to be able to confirm the assignment of a module input or output in a block diagram, the corresponding module configuration must have been z confirmed.
No coherence check is performed at the level of input and output assignment to a particular task (MAST or FAST). It is advisable to assign all the inputs and outputs of one same loop to the same task.
z z
If an I/O module is moved, the address is not automatically modified in the process control loop screens.
If a language object used by a process control loop no longer exists (for example owing to suppression of the module), an error message appears on global confirmation.
This table gives the permitted language objects according to the type of interface.
Interface types
Standard input process value
External input process value
Setpoint input Remote 1
Setpoint input Remote 2
Feed forward input
Analog output
Servo, PWM output
Permitted language objects
%IW, %MW
%MF
%MF
%MF
%IW, %MW
%QW, %MW
%Q, %M
Object type
Word
Floating point
Floating point
Floating point
Word
Word
Bit with edge management
35012329 02 May 2007
187
Configuration
6.2
Configuring MMI ( Man-Machine Interface)
At a Glance
Subject of this section
What's in this
Section?
This section describes the functions which must be implemented to configure the
MMI (Man-Machine Interface) associated with the process control loops.
This section contains the following topics:
Topic
How to associate the process control loops to the MMI (Man-Machine
Interface)
Description of exchange zone
Using the Man-Machine Interface
Configuration in multi-station operation
Page
188
35012329 02 May 2007
Configuration
How to associate the process control loops to the MMI (Man-Machine Interface)
At a Glance It is possible to associate the process control loops to an MMI (Man-Machine
Interface) terminal such as the magelis XBT-F. This association is made transparently; simply indicate which loop controllerlers are concerned and assign them an order number.
Note: the maximum number of loops used by the XBT-F terminal is 16.
Procedure The steps described in this table enable the user to associate certain process control loops to an MMI (Man-Machine Interface) terminal.
Step
1
Action
Open the configuration window of the process control function from the PLC hardware configuration.
Result : the following window appears.
PMX 57102 [RACK 0 POSITION 0 ]
Configuration
Designation : PROCESSEUR PMX P 57102
Configure MMI
Symbol :
Loop controller :
Loop controller 4-LOOP0
Function :
Boucle process
2
3
Click on DOP configuration .
Result : a window appears so that the process control loops concerned can be determined by the MMI (Man-Machine Interface) as well as their order of appearance in the XBT-F operating terminal pages.
Configuration Man-Machine Interface
Loop controller to be used
Loop name
Loop controller 4 - LOOP0
Loop controller 5 - LOOP1_1
Loop controller 5 - LOOP1_2 3
4
1
2
Loop controller 5 - LOOP1_3
Loop controller 6 - LOOP2_S
Loop controller 7 - SPP_3
Loop controller 8 - SPP_4
5
6
Order Order prog.
1
2
OK
Cancel
Reset List
Details
T bl lti l é
Select the loops to be linked to the MMI (Man-Machine Interface); the order is fixed automatically according to the order of selection of the loops.
35012329 02 May 2007
189
Configuration
Description of exchange zone
At a Glance
Illustration
All the variables associated with a control loop have different exchange needs with the operating terminal. z Exchanges can be contextual according to the screen to be displayed, for example Kp, Ti and Td for the adjustment screen.
z z
Some variables must be permanently exchanged, regardless of which screen is being displayed, such as the archive and alarm management screens.
Other variables do not need to be displayed on the operating terminal, such as the time constant of the filtering function.
In order to structure the communication, whilst at the same time avoiding any programming, exchange tables associated with process control channels are implicitly reserved and structured in the PLC’s internal memory (%MW).
These tables have been created to optimize exchange between the PLC and the
MMI terminal.
The following figure describes the exchange zones.
Process control channels
%MFxy.i
Loop 1
Loop 2
Loop 3
Periodic zone
%MW
PV.SP...
Loop 1
PV.SP...
Loop 2
PV.SP...
Loop 3
Exchanges continuous
XBT
API
Kp
Ti
Td
...
...
Exchanges contextual
190
35012329 02 May 2007
Description
Configuration
Description of the illustration representing the exchange zone.
Memory zone
Periodic table
Description
It is a word table of 6%MF for each operational loop, grouping the process value (PV), the setpoint (SP),the commands (OUTi),the alarms and the status information for all control loops.
Parameter setting zone
XBT table
Alarm table
This zone, which is permanently visible, is used to establish the archives, the outlines, the alarm management and the status of each loop.
If more than 16 loops are selected, the first 16 will be processed in a periodic exchange table. To process more than 16 loops, you must define the zone Loops (17 and +) (See Using the Man-Machine
Interface, p. 192 ) of the details screen.
There are two parameter setting zones: z The loop adjustment zone is a table of 52 %MF (which is
104 %MW). It groups all the adjustment parameters associated z with the control loop during display. This table is unique to each loop. Its settings management is used to limit the number of memory words used. However, it is simple for the user to operate.
The setpoint programmer parameter setting zone is a 125 %MW table. It is unique and brings together all existing setpoint programmers.
This table groups the label, the unit, the scales and the status of each control loop, including the setpoint programmers. This table is read in a unique or a cyclic manner according to choice.
This is a 1 %MB loop table for each loop grouping all the alarms of all the loops. With the XBT, the management of the alarms occurs through the dialog table. This zone should therefore agree with the
XBT dialog table.
35012329 02 May 2007
191
Configuration
Using the Man-Machine Interface
At a Glance
Standard use z z
MMI, which is associated with process control, can be used in two ways: standard use, customized use.
When default configuration is used, the process control applications provided with the XBT-F terminal immediately operate with the preset table addresses. A maximum of sixteen loops is used. It is sufficient to select process control loops to be linked to the MMI. On connection of the XBT-F terminal to the PLC, exchanges are automatically carried out via the preset tables.
Default table addresses.
Table
Alarm table
SPP parameter setting zone
Loop periodic table
Loop adjustment zone
XBT tables
Start address
%MW3228
%MW3350
%MW3500
%MW3700
%MW3810
End address
%MW3242
%MW3474
%MW3691
%MW3803
%MW4090
Maximum size
15
125
192
104
281
192
35012329 02 May 2007
Configuration
Customized use If the default memory partition must be altered, the runtime applications for the
XBT-F man-machine interface must also be completely altered.
To operate more than 16 loops, the XBT application must be altered in order to create operating pages dedicated to additional loops. It is also necessary to fill in the address of the new periodic exchanges table, the Loops (17 and +) field of the following screen.
MMI configuration
Loop controllers to be used
Loop name
Loop Controller 4 – LOOP0
Loop controller 5 - LOOP1_1
Loop controller 5 - LOOP1_2
Loop controller 5 - LOOP1_3
Loop controller 6 - LOOP2_M
Loop controller 6 - LOOP2_S
Loop controller 7 - SPP_3
Loop controller 8 - SPP_4
Loop order
1
2
3
4
5
6
Prog. order
1
2
OK
Cancel
Reset List
Details
Parameter setting zone
Loops:
SPPs:
Periodic exchange zone
Loops (16 max):
Loops (17 and +):
XBT zone
Loops and
SPPs:
Alarm zone
Loops:
104 %MW from 3700
125 %MW from 3350
(6°6) MF from 3500
281 %MW from 3810
(6°1/2) MF from 3228 to 3803 to 3474 to 3570 to 4090 to 3230
Open
35012329 02 May 2007
193
Configuration
Configuration in multi-station operation
At a Glance For non-multiplexed use, several operation terminals manage the process control loops. The parameter adjustment tables are also duplicated and dedicated to each loop. One table per process control loop or per setpoint programmer.
194
35012329 02 May 2007
Configuration
How to configure multi-station operation
This table describes the steps required for configuring multi-station process control.
Steps
1
2
Action
Click in the DOP configuration box.
Result : the MMI configuration screen appears.
Click on the Details button to access the details screen.
Result : this type of screen appears.
Configure HMI
Loop controller to be used
Loop name
Loop control. 4 - LOOP0
Loop control. 5 - LOOP1_1
Loop control. 5 - LOOP1_2
Loop control. 5 - LOOP1_3
Loop control. 6 - LOOP2_M
Loop control. 6 - LOOP2_S
Loop control. 7 - SPP_3
Loop control. 8 - SPP_4
4
5
6
Loops Order
1
2
3
SPP order
1
2
OK
Cancel
Reset List
Details
Parameter setting zone
Loops :
SPPs :
104 %MW from
125 %MW from
Periodic exchange zone
Loops (16 max): (6°6) MF from
Loops (17 and +):
XBT zone
Loops and
SPPs :
Alarm zone
Loops :
281 %MW from
(6°1/2) MF from
3700
3350
3500
3810
3228 to 3803 to 3474 to 3570 to 4090 to3230
Open
3 Click on the Open button.
Result: the tables configuration screen appears.
Opening : Exchange Zone per Loop
Selected and ordered loops and SPPs
Loop name
Loop controller 4 - LOOP0
Loop controller 5 - LOOP1_1
Loop controller 5 - LOOP1_2
Loop controller 5 - LOOP1_3
Loop controller 6 - LOOP2_M
Loop controller 6 - LOOP2_S
Loop controller 7 - SPP_3
Loop controller 8 - SPP_4 from %MW to %MW
1000
1150
1300
1450
1560
1670
1780
1910
1103
1253
1403
1553
1663
1773
1904
2034
OK
Cancel
These tables have exactly the same structure as those used in multiplexed addressing (See
Description of exchange zone, p. 190
).
35012329 02 May 2007
195
Configuration
196
35012329 02 May 2007
Control loop adjustment
7
At a Glance
Subject of this
Chapter
What's in this
Chapter?
z z z
This Chapter describes the adjustment methods for:
Feed forward,
PID, model loop controller.
This chapter contains the following sections:
Section
7.1
7.2
7.3
Topic
Adjust Feed forward
PID adjustment
Model loop controller adjustment
Page
35012329 02 May 2007
197
Adjustment
7.1
Adjust Feed forward
At a Glance
Subject of this section
What's in this
Section?
z z
This section describes the procedures necessary for adjusting a Feed forward: gain adjustment,
Leadlag adjustment.
This section contains the following topics:
Topic
Gain adjustment
Leadlag adjustment
Page
198
35012329 02 May 2007
Adjustment
Gain adjustment
At a Glance
Procedure
Debugging a Feed forward branch firstly requires a Gain adjustment The following procedure describes the procedure to be respected.
This table describes the steps required in order to adjust the gain of a Feed forward branch.
Step
1
2
3
Action
Put the loop controller into manual mode.
Position T1_FF and T2_FF at zero.
Establish a disruption scale and stabilize the gain so that the disruption measured when Feed forward is inputted is compensated entirely.
Note : the gain on the Feed forward branch occurs according to scale values.
Example of gain adjustment z z
If one says that: the PV variation is at –10% for a disruption variation of 5%, the process value variation is at 7% for a command variation of 5%, then the gain deducted will be (-10/5) / (7/5) which is -1.4
.
For a Feed forward input between 0 and 10000 and FF_INF = 0.0 then FF_SUP = -140.0, for a command scale where OUT_INF = 0.0 and OUT_SUP=100
35012329 02 May 2007
199
Adjustment
Leadlag adjustment
At a Glance
Procedure
Debugging a Feed forward branch requires Leadlag adjustment The following procedure and example describe the procedure to be respected.
This table describes the steps required in order to adjust the Leadlag of a Feed forward branch.
Step
1
2
3
4
5
Action
Put the loop controller into manual mode.
Position T1_FF at the time constant value for the process.
Position T2_FF at the time constant value for the disruption.
Carry out a disruption grade: z if the overshoot is positive, reduce T1_FF, and similarly, if the overshoot is z negative, increase T1_FF, if the overshoot starts positively, increase T2_FF, and similarly, if the overshoot starts negatively, reduce T2_FF.
Repeat step 4 until the overshoot is cancelled out.
200
35012329 02 May 2007
Example of
Leadlag adjustment
Adjustment
An adjustment of the PV2 output temperature on the secondary circuit of the exchanger is required. A PID controls the incoming hot air valve according to PV2 and the SP setpoint. The cold water temperature acts as a measurable disruption in relation to this process control.
The Feed forward function can be used to react as soon as the cold water temperature fluctuates and not if PV2 has decreased.
Illustration of the example:
-
SP
+ PV
TT2
PV2
PID
Transfer function
FF
+
+
Qc
Steam
TT1
Disruption
Condenser
The working hypotheses are as follows: z The output temperature of the condenser (temperature of the cold water) fluctuates between 5 and 25 degrees Celsius, with an average value of 15 z z degrees.
A DT variation in this temperature affects the exchanger output temperature entirely.
In order to compensate for an increase or decrease of 5 degrees Celsius in the exchanger output temperature, the controlling steam valve must be opened or closed by 10%.
z z
Adjustments to the Feed forward input parameters must be such that the contribution of the cold water temperature to the valve controlling the steam flow rate is: zero to 15 degrees Celsius, in a ratio of 10% /5 degrees Celsius between 5 and 25 degrees.
35012329 02 May 2007
201
Adjustment
The following figure illustrates the adjustment.
Output variation in %
20
10
-10
-20
5 10 15 20 25
Cold water temperature in degrees celsius
202
35012329 02 May 2007
Adjustment
7.2
PID adjustment
At a Glance
Subject of this section
What's in this
Section?
z z
This section describes the methods for adjusting a PID: closed loop adjustment, open loop adjustment.
As well as the role and the effects of each parameter: Kp, Ti et Td.
This section contains the following topics:
Topic
PID parameter adjustment method
Role and influence of the parameters of a PID during a loop adjustment
Page
35012329 02 May 2007
203
Adjustment
PID parameter adjustment method
Introduction Numerous methods to adjust the PID parameters exist, we suggest Ziegler and z z
Nichols which have two variants: closed loop adjustment, open loop adjustment.
Before implementing one of these methods, you must set the PID action direction: z z if an increase in the OUT output causes an increase in the PV measurement, make the PID inverted (KP > 0), on the other hand, if this causes a PV reduction, make the PID direct (KP < 0).
204
35012329 02 May 2007
Closed loop adjustment
Adjustment
This principal consists of using a proportional command (Ti = 0, Td = 0 ) to start the process by increasing production until it starts to oscillate again after having applied a level to the PID corrector setpoint. All that is required is to raise the critical production level (Kpc) which has caused the non damped oscillation and the oscillation period (Tc) to reduce the values giving an optimal regulation of the regulator.
Measure
Tc time
According to the kind of (PID or PI) regulator, the adjustment of the coefficients is executed with the following values:
-
PID
PI
Kp
Kpc/1,7
Ti
Tc/2
Kpc/2,22 0,83 x Tc -
Td
Tc/8 where Kp = proportional production, Ti = integration time and TD = diversion time.
Note: This adjustment method provides a very dynamic command which can express itself through unwanted overshootsduring the change of setpoint pulses.
In this case, lower the production value until you get the required behaviour.
35012329 02 May 2007
205
Adjustment
Open loop adjustment
As the regulator is in manual mode, you apply a level to the output and make the procedure response start the same as an integrator with pure delay time. .
Output
S t
Measure
Integrator Process response
M = S
Tu Tg t
The intersection point on the right hand side which is representative of the integrator with the time axes, determines the time Tu. Next, Tg time is defined as the time necessary for the controlled variable (measurement) to have the same variation size
(% of the scale) as the regulator output.
According to the kind of (PID or PI) regulator, the adjustment of the coefficients is executed with the following values:
-
PID
PI
Kp
-1,2 Tg/Tu
-0,9 Tg/Tu
Ti
2 x Tu
3,3 x Tu
Td
0,5 x Tu
where Kp = proportional production, Ti = integration time and TD = diversion time.
Note: Attention to the units. If the adjustment is carried out in PL7, multiply the value obtained for KP by 100.
206
35012329 02 May 2007
Adjustment
This adjustment method also provides a very dynamic command, which can express itself through unwanted overshoots during the change of setpoints’ pulses. In this case, lower the production value until you get the required behavior. The method is interesting because it does not require any assumptions about the nature and the order of the procedure. You can apply it just as well to the stable procedures as to real integrating procedures. It is really interesting in the case of slow procedures
(glass industry,…) because the user only requires the beginning of the response to regulate the coefficients Kp, Ti and Td.
35012329 02 May 2007
207
Adjustment
Role and influence of the parameters of a PID during a loop adjustment
Proportional action influence
Proportional action enables the process response speed to be matched. The higher the gain, the more the response will accelerate and the static error will reduce (in purely proportional terms), but the greater the deterioration of stability will be. A compromise between speed and stability must be found. The following is the influence of integral action on the process response:
Kp too large
Kp correct
C
Static error
Kp too small t
208
35012329 02 May 2007
Influence of integral action
Adjustment
Integral action ensures that static error (the deviation between the process value the and setpoint) is canceled out. The higher the integral action (Ti small), the greater the acceleration of the response and the more stability deteriorates. A compromise must be found between speed and stability. The influence of integral action on process response at a grade is as follows:
Ti too large
Ti correct
C
Ti too small t
Note: Small Ti represents a high integral action.
Kp = proportional gain, Ti = integration time and TD = derivative time.
35012329 02 May 2007
209
Adjustment
Influence of derivative action
Derivative action is anticipatory. It adds a term that accounts for the speed variation of the difference, which enables anticipation by accelerating the process response when the deviation increases, and slowing it down when the deviation decreases.
The higher the derivative action (large Td), the more the response accelerates. Here again, a compromise between speed and stability must be found. The influence of derivative action on the process response at a division is as follows:
Td too large
C
Td too small
Td correct t
210
35012329 02 May 2007
Adjustment
Limits of PID process control
If the process is assimilated to a first command with pure time delay, of transfer function:
H(p) = K
1 +
θ p with:
τ
= model delay,
θ
= model time constant,
100%
Measure = M
0
+
Δ
M
Δ
M
Measure = M
0
τ θ t
The process control performances are dependent on the ratio
θ
PID process control is suitable in the following area: 2 < = < 20
θ
θ τ the PID process control is not suitable and more advanced algorithms must be used.
θ
For > 20, a threshold process control with hysteresis is sufficient.
35012329 02 May 2007
211
Adjustment
7.3
Model loop controller adjustment
At a Glance
Contents of this
Section z z z
This section describes the adjustment principles of a model loop controller and develops the following points: static gain adjustment, dead time or delay adjustment, time constant adjustment.
What's in this
Section?
This section contains the following topics:
Topic
Steps to follow to adjust the model loop controller
Instructions for regulating Ks static gain
Instructions for adjusting dead time or delay T_DELAY
How to regulate the time constant
Page
212
35012329 02 May 2007
Adjustment
Steps to follow to adjust the model loop controller
Procedure The steps in this table describe the action to be taken in order to adjust a model loop controller.
Step
1
4
5
2
3
Action
Use a graphic method based on an indexed response, such as the Broida method. This directly provides the parameters for a first order model with pure delay, in order to identify the process model.
Enhance the adjustment by running the IMC loop controller in automatic mode.
To check whether the model is adapted to the process, set CL_PERF to 1.0
(time constant of closed loop = time constant of open loop).
Proceed to the point of operation and run the loop controller in automatic mode.
Result : If the model parameters are correct, the measurement should rejoin the setpoint without overflow and the OUT_MAN command signal should be z z z almost one division. If this is not the case, a correction must be made, which means: adapting the static gain, adapting the dead time adapting the time constant.
35012329 02 May 2007
213
Adjustment
Instructions for regulating Ks static gain
At a Glance
Illustration of the adjustment
The following figure illustrates the static gain adjustment.
U(t)
Δ U1
Ks too small
U(t)
Δ U1
Ks too large
U(t)
Δ U1
Ks correct
Δ U2 t
Δ U2 t
Δ U2 t
214
35012329 02 May 2007
Adjustment
Instructions for adjusting dead time or delay T_DELAY
At a Glance Observe the adjustment unit measurement and control signals for a recording. If we z z
τ
τ
Note: gain and delay adjustments can be carried out during the same test.
τ model lower
τ
The following figure describes this scenario, T_DELAY takes on the value of A.
Δ C
C = M t0
Inflection point
Tangent
Process value signal
A approximately τ process
Command signal
Δ U
τ model Δτ
35012329 02 May 2007
215
Adjustment
τ model greater
τ
The following figure describes this scenario, T_DELAY takes on the value of A.
Inflection point
Tangent
Process value signal Δ C
C = M t0 approximately τ process
A
Command signal
Δ U
τ model Δτ
216
35012329 02 May 2007
Adjustment
How to regulate the time constant
At a Glance Having regulated dead time and static gain, the model time constant must be successively regulated by observing the command signal U(t) record.
z θ z θ
This figure illustrates the two cases.
U(t)
θ model < θ procedure
Δ U2 t
Δ U1
θ model > θ process t0
Signal speed when OL_TIME <
θ process
The following figure describes the signal speed.
SP (t) and PV (t)
OL_TIME <
θ process
PV
OL_TIME = θ process
Δ SP
SP = SP
U (t) t0
Δ SP.OL_TIME
Ks.
θ process
PV = SP t
Δ SP
Ks
35012329 02 May 2007 t0 t
217
Adjustment
Signal speed during OL_TIME
The following figure describes the signal speed.
SP (t) and PV (t)
OL_TIME = θ process
PV
SP = SP
Δ SP t0
PV = SP
OL_TIME > θ process
U (t)
Δ SP.OL_TIME
Ks.
θ process
Δ SP
Ks t0 t t
Closed loop time constant selection
Having determined the model to be used, the closed loop time constant selection remains to be made. Its value is dependent on the response speed of the required closed loop.
For processes that correspond to a first order model with delay, by choosing a time constant CL_PERF relation between 1.05 and 1.15, the system response is improved without running the risk of destabilising the process.
CL_PREF = OL_TIME / required closed loop time constant.
All CL_PERF increases correspond to an increase in response speed (it is a more important action of the adjustment unit), but also to an increased sensitivity to modeling errors.
218
35012329 02 May 2007
Debugging a process control loop
8
At a Glance
Subject of this chapter
What's in this
Chapter?
This chapter describes the process control loop debugging screens as well as the associated operational processes.
This chapter contains the following topics:
Topic
Description of the debugging screen
Modifying the parameters of each loop
Functional modification of each loop
Debugging the setpoint programmer
Data storage
Page
219
35012329 02 May 2007
Debugging
Description of the debugging screen
At a Glance
Illustration z z z z z z
In online mode, the process control debugging screens are used to: display and animate the loop schema, display the process alarms and channel faults, modify the adjustment parameters of each function, simulate input interface values, add, delete, and replace calculation functions, modify configuration parameters of each PID reverse/forward mode type z function, modify loop controller operation modes.
This diagram shows a process control loop debugging screen.
PMX 57102 [RACK 0 POSITION 0 ]
Mise au point
Désignation : PROCESSEUR PMX P 57102
Configuration du DOP
Symbole :
Régulateur :
Régulateur4 - LOOP0
Fonction :
Boucle process
Alarmes
DL DH LL L H HH
LOOP 0
Boucle
Paramètres boucle
Mesure
Consigne
Correcteur
Feed Forward
Sortie 1
Standard
Simple
Chaud/Froid
Oui
Analogique
Echelle de la boucle
Basse : 0.0
Haute : 100.0
PV
5000
SP1
63.0
R
45.0
44.845
L
FF
3547 LL 35.47
Fonctions
Format
Filtrage
Générateur Fct
Alarmes
Simulation
Constante de temps (s)
Gain
Sortie
Paramètres
10.0
1.0
4484.536
I
P
D
28.585
0.0
DIAG...
DIAG...
WARNING
OUT 1
2858
0
OUT 2
220
35012329 02 May 2007
Description
Debugging
This table describes the main fields of the debugging screen.
Address Description
Alarms If the alarm functions have been configured, all the loop-associated alarms are z z displayed.
the DIAG LED groups together the serious errors, the WARNING LED displays warning messages pertaining to the process control loop function.
When the LEDs are on, a window displays error diagnostics messages.
A %MWxy.i:Xj word bit is linked to each diagnostic. These bits are detailed in the Fault and diagnostics language objects parts of the chapter describing all the process control language objects (See Process control language
Loop 0
Block schema
Only the configured functions are shown in this tab. Their associated parameter values are animated. They can be modified in online mode.
The schema shows the intermediary calculation values (corrector input measurement, for example).
Auto/Manu and Remote/Local changes are made by clicking the mouse once.
The associated command values or setpoint values are entered directly in the entry fields.
The grayed out entry fields are not active.
35012329 02 May 2007
221
Debugging
Modifying the parameters of each loop
Principles The adjustment parameters can be modified in online and offline mode from PL7 z z software: task screens, data editor, z z runtime screens, z z variable tables,
UNITE server,
...
Modifications do not require global reconfiguration and the save mechanism (initial parameters, current parameters) is applied to the parameters of each process control loop (See
222
35012329 02 May 2007
Debugging
Functional modification of each loop
At a Glance
Principles
Functions can be added to or deleted from the process control loops in online mode .
The PLC can be in RUN mode during modifications to process control loop functions.
DANGER
For safety reasons, modifying these functions and some configuration parameters such as extrapolating the generator function from the function, and limiter lopping, etc. require channel reconfiguration.
Failure to follow this precaution will result in death, serious injury, or equipment damage.
After the modifications have been made, the loop starts in a determined state: z If modifications are made at Measurement, Setpoint, and Feed forward branch level, the loop performs a warm start.
z If modifications are made at corrector or output level, the loop restarts using the initial operating modes which were defined during configuration.
Note: addition or modification of I/O addresses or memory words in online mode is prohibited. Modifying some branches, and replacing a simple setpoint with a ratio setpoint is also prohibited.
Note: the totalizer function can not be added in online mode. Its output is a %MF address.
It is not necessary to switch to configuration mode to modify the initial adjustment parameter values Kp, Ti, and Td.
Operating mode : z In debugging mode, all modification of the adjustment parameters from the task z screen updates the current and initial values of these parameters.
For the 3 simple loops loop controller alone, an initial value modification without configuration parameter modification is not taken into account (for example, adding a function).
35012329 02 May 2007
223
Debugging
Debugging the setpoint programmer
At a Glance Setpoint programmers have their own debugging screen. They have all the reconfiguration and data saving services in online mode.
Note: any reconfiguration in online mode causes the setpoint programmer to stop operating.
Illustration This diagram shows an example of the setpoint programmer in Debugging mode.
PMX 57352 [RACK 0 POSITION 0]
Debug
Designation: PROCESSOR PMX P 57352
DOP configuration
DIAG...
Symbol:
Loop Controller:
Name: SPP_1
Function:
Loop controller 5 - SPP_1 Setpoint programmer
0 1 2
Task:
MAST
3 4 5
Segmentation:
8-8-8-8-8-8
6 7
DIAG...
WARNING
PROFIL_1 PROFIL_2 PROFIL_3
Segments Execution
3
4
1
2
Guaranteed Dwell Time at threshold 5.0
Segment x
Ramp
Stage
Ramp
Stage
50.0
50.0
80.0
80.0
SP x
40.0
20.0
40.0
40.0
VAL x
PROFIL_4 PROFIL_5 PROFIL_6
Number of segments:
Unit
Second
Second
Second
Second on Deviation on input
8 on 8
Pq S0 S1 S2 S3 S4 S5 S6 S7
Process value
Setpoint 13.47494
80.0
Current
Profile 1
Total time elapsed
Segment
10.78006
1 No repetition 1
Time elapsed in current segment 10.78006
224
35012329 02 May 2007
Operating principle
Debugging z z z z
Profile execution is displayed dynamically. The information provided is as follows: the segment number in progress (SEG_OUT), the iteration number in progress (CUR_ITER), the execution time of the segment in progress (TIME_SEG), the total time (TIME_TOTAL).
z z z
Notes on the operation:
The TIME_SEG and TIME_TOTAL times change even if the profile is frozen.
The state of monitoring outputs is directly displayed in the channel zone.
Each profile can be controlled directly from the command button located in the tab.
z z
When the profile is frozen, the %MFxy.i.20 setpoint values and control outputs,
%MWxy.I.3:X0 to X7, are not updated during use of NEXT and BACK commands.
They are refreshed once the profile has been unfrozen.
Neither the target setpoint value to be reached (SPi) nor the length of the segment in progress can be modified.
35012329 02 May 2007
225
Debugging
Data storage
At a Glance
Saving adjustment parameters
Backup application z z
Two data save solutions are provided: saving adjustment parameters, the backup application.
z z z z
All modifications of the adjustment parameters from the PL7 process control screens update the current and initial values.
Modifying an adjustment parameter from the application or from an animation table affects the current value but does not modify the initial value. The
SAVE_PARAM explicit instruction must be used to save this new value.
A modification from the XBT-F runtime screens affects the current value but does not modify the initial value. An explicit save command, which is available in these screens, is used for updating.
On cold restart (%S0) and application loading, the current parameters are replaced by the initial parameters.
Premium PLCs provide the option of saving the application (program and data memory) on a Backup card. The content of this card can reload the RAM memory.
Note: A backup card cannot be used if the Premium PLC is already using a
PCMCIA card.
226
35012329 02 May 2007
Operating the process control loops
9
At a Glance
Subject of this
Chapter
What's in this
Chapter?
This Chapter describes the various solutions for operating the process control application from the dialog terminals.
This chapter contains the following sections:
Section
9.1
9.2
9.3
9.4
Topic
Operating applications for XBT-F
The XBT-F01 process control screens
XBT-F02 and TXBT-F02 process control screens
Exchange tables
Page
35012329 02 May 2007
227
Operating
228
35012329 02 May 2007
Operating
9.1
Operating applications for XBT-F
At a Glance
Subject of this
Section
What's in this
Section?
This Section introduces the applications provided with XBT-F terminals, page models and how to use them.
This section contains the following topics:
Topic
Magelis applications offered
Operating page models
Browsing in the various view formats
How to load an XBT-F application
Page
35012329 02 May 2007
229
Operating
Magelis applications offered
At a Glance The disk provided with the XBT-F and TXBT products includes 4 operating applications programmed with the XBT-L1000 tool: z z z z
The RFX01MFRUTW.DOP file application intended for XBT-F 5 inches (XBT-
F01 family) configured with the Uni-Telway protocol.
The RFX01MFRFIP.DOP file application intended for XBT-F 5 inches (XBT-F01 family) configured with the Fipio protocol.
The RFX02MFRUTW.DOP file application intended for XBT and TXBT 10 inches
(XBT-F02 and TXBT-F02 family) configured with the Uni-Telway protocol.
The RFX02MFRFIP.DOP file application intended for XBT and TXBT 10 inches
(XBT-F02 and TXBT-F02 family) configured with the Fipio protocol.
Note: the process control pages built into the XBT-1000 applications, which are provided on the disk, are guaranteed by the manufacturer to operate correctly as long as they are not modified by the user.
XBT-F01 application
Applications in the process control part include: z z z z z z z z z
1 monitoring screen,
1 parameter setting front panel screen,
1 control screen for each loop (trends),
1 parameter setting adjustment screen,
1 parameter setting autotuning screen,
1 setpoint programmer selection screen,
1 parameter setting adjustment screen dedicated to setpoint programmers,
1 parameter setting setpoint programmer screen, associated alarm pages.
Note: the number of loops used is limited to 8.
230
35012329 02 May 2007
XBT-F02 and
TXBT-F02 application
Operating
Applications in the process control part include: z z z z z z z
1 monitoring screen,
1 adjustment screen with front panel and parameter setting autotuning (bar charts),
1 control screen for each loop (trends),
1 setpoint programmer selection screen,
1 parameter setting adjustment screen dedicated to setpoint programmers,
1 parameter setting setpoint programmer screen, associated alarm pages.
Note: the number of loops used is limited to 16.
35012329 02 May 2007
231
Operating
Operating page models
At a Glance
Model of XBT-
F01 pages
All the operating pages are designed from the same presentation model: z z
An alarm panel at the bottom of the screen indicates the active alarm.
The dynamic function keys perform one function and one function only: z z accessing the adjustment page, starting autotuning, z z z browsing, selecting a loop,
...
These models can be modified or retrieved to expand the other personal operating pages.
This diagram describes a model for XBT-F01 pages.
Loop name Loop controller type
AAAAAAAA LLLLLLLLLLLLLLLL
TRACK LL HH DL AAAAAA REMOTE
Memory use log
State of alarms
9999
N° of alarm displayed
Unit
Local/Remote Indication
LLL
State of alarm
232
35012329 02 May 2007
Model of XBT-
F02 pages
This diagram describes a model for XBT-F02 pages.
Operating mode
Loop name
Loop controller type
Indication
TRACK AAAAAAAA
LLLLLLLLLLLLLLLLLLLLLLLLLLLLLL
IIIIIIIIIIIIIIII REMOTE
+yyyy. y AAAAAA
Message regarding autotune diagnostics
Memory use log N° of alarm displayed Alarm label
Maximum curves / bar charts
Unit
Date / time of alarm state
9999
99999
Group n°
Indication password
System message
AAAAAAAAAAAAA LLL
AAAAAAAAAAAAAAAAA
Date / time of terminal
Operating
35012329 02 May 2007
233
Operating
Browsing in the various view formats
At a Glance Dynamic function keys are used to browse between the various view formats.
The browsing offered can be modified.
234
35012329 02 May 2007
Browsing in an
XBT-F01 application
Operating
The following diagram illustrates browsing between the screens of an XBT-F01 application.
Monitoring screen
AT
5
6
7
8
1
2
3
4
TC_0001
TC_0002
TC_0003
2 Alarm page 1
D
L
L
H
N°1
SPP
ON
AT
Front panel screen
TC_0001
AUTO
10000-
H DH LOCAL
0-
2
PV
SP
OV
:
:
:
96.00
65.00
31.00
OV1 :
Alarm page 1
31.00
AM
LR
ON
Autotuning screen
KP
TI
TD
TC_0001
AUTO
:
:
:
H DH
ACTUAL
1.0
0.0
0.0
Step
Tmax (s)
Perf
:
:
:
LOCAL
PREV
1.0
0.0
0.0
10.0
100.0
0.50
2 Alarm page 1
AT
Sa
Pr
ON
AT
Adjustment screen
TC_0001
AUTO
KP
TI (s)
TD (s)
O_BIAS
DBAND
KD
ORATE1
:
:
:
:
:
:
:
H DH
1.0
0.0
0.0
0.0
0.0
10.0
0.0
SP_SUP
SP_INF
TS (s)
PV_H
PV_L
INTBND
:
:
:
:
:
:
LOCAL
100.0
0.0
0.30
95.0
5.0
0.0
2 Alarm page 1
Sa
ON
TC_0001
AUTO
Control screen
H DH LOCAL
PV
SP :
: 96.00
65.00
2
AM
OV
OV1 :
: 31.00
31.00
Alarm page 1
LR
ON
35012329 02 May 2007
235
Operating
Browsing in an
XBT-F02 application
The following diagram illustrates browsing between the screens of an XBT-F02 application.
Monitoring screen
Process control
AAAAAAAAAA
AAAAAAAAAA
AAAAAAAAAA
AAAAAAAAAA
AAAAAAAAAA
AAAAAAAAAA
AAAAAAAAAA
AAAAAAAAAA
AAAAAAAAAA
AAAAAAAAAA
AAAAAAAAAA
AAAAAAAAAA
AAAAAAAAAA
AAAAAAAAAA
AAAAAAAAAA
R
R
R
R
R
R
R
R
AT
AT
AT
AT
AT
AT
AT
AT
AT
AT
AT
AT
AT
AT
AT
R
R
R
R
R
R
R
SPP
99999 LLLLLLLLLLLLLLLLLLLLLLLLL AAAAAAAA
9
11
History curve access
AAAAAAAA
MAGELIS
AAAAAAAA
AAAAAAAA AAAAAAAA
AAAAAAAA
AAAAAAAA
13
AAAAAAAA AAAAAAAA
15
10
12
14
16
99999 LLLLLLLLLLLLLLLLLLLLLLLLL
1/8
AAAAAAAA
Adjustment Screen
TRACK
AAAAAAAA
REMOTE
LLLLLLLLLLLLLLLLLL +9999.9 AAAA
AM
PV:+9999.9
SP:+9999.9
OV:+9999.9
LR
AAAAAAAA
Control screen
TRACK
AAAAAAAA
REMOTE
LLLLLLLLLLLLLLLLLL +9999.9 AAAA
1/8
9/16
1/8
9/16
AM
PV:+9999.9
SP:+9999.9
OV:+9999.9
LR
AAAAAAAA
236
35012329 02 May 2007
Operating
How to load an XBT-F application
How to load the application
This table describes the steps for loading an XBT-F application.
Step
1
2
Action
Open the required application using XBT-L1000 software from the disk provided.
Use the XBT-L1000 software Transfer command to load the application in the
PCMCIA card of the XBT terminal.
35012329 02 May 2007
237
Operating
9.2
The XBT-F01 process control screens
At a Glance
Subject of this
Section
What's in this
Section?
This Section describes the XBT-F01 runtime screens, dedicated to process control.
This section contains the following topics:
Topic
Monitoring screen
Front panel screen
Trend screen
Parameter adjustment screen
Autotuning screen
Setpoint programmer selection screen
Setpoint programmer runtime screen
Setpoint programmer adjustment screen
Operating the alarm pages
Page
238
35012329 02 May 2007
Operating
Monitoring screen
At a Glance The monitoring screen is the input point for the process control application. This view provides a summary of all the loops used.
Note: No entries can be made from this view.
Illustration
Description
Note: to optimize communication, loop labels are read only on displaying the screen. This can cause inconsistencies when the data are modified by the PLC.
Redisplaying the screen will update the new values. If communication is not limited, data can be configured in cyclic read mode and not in read only mode.
This diagram shows a monitoring screen.
AT
1
4
5
2
3
6
7
8
TC_0001
TC_0002
TC_0003
2 Alarm page 1
D
L
L
H
N°1
SPP
ON
The information displayed for each loop is as follows: z z z z the loop label, the Auto/Manual operating mode, autotuning is running (or not), the sum of the alarms.
The following table shows the function of the dynamic selection keys.
Key Description
These dynamic keys are used to select the required loop for the adjustment screens.
35012329 02 May 2007
239
Operating
Front panel screen
At a Glance This is a table loop controller view. It is used to globally display a process control loop. From this screen, the loop can be controlled in manual mode and the setpoint in local mode.
Note: the refresh period is 5 seconds. The total save period is 26 minutes.
Illustration
Description
This diagram shows a front panel screen.
TC_0001
AUTO
10000-
H DH LOCAL
AT
PV
SP
OV
:
:
:
96.00
65.00
31.00
AM
0-
2
OV1 :
Alarm page 1
31.00
LR
ON
The following table shows the function of the dynamic selection keys.
Key Description
This key is used to access the previous loop.
AM
This key is used to access the next loop.
This key is used to switch the loop into automatic or manual mode. The OV command can be modified.
LR
This key is used to switch the setpoint into Remote or Local mode. The SP command can be modified.
240
35012329 02 May 2007
Operating
Trend screen
At a Glance
Illustration
This view includes the same level of information as the loop view, as well as displaying the 4 characteristic trends of the loop. The recent trend history is saved.
There is no history management on XBT-F.
As with the front panel screen, the command can be controlled in manual mode and the setpoint in local mode.
This diagram shows a trend screen.
TC_0001
AUTO H DH LOCAL
Description
PV
SP :
: 96.00
65.00
2
AM
OV
OV1 :
: 31.00
31.00
Alarm page 1
LR
ON
The following table shows the function of the dynamic selection keys.
Key Description
This key is used to switch the loop into automatic or manual mode.
AM
This key is used to switch the setpoint into Remote or Local mode.
LR
35012329 02 May 2007
241
Operating
Parameter adjustment screen
At a Glance This view is used to adjust the loop controller.
CAUTION
Loops must only be adjusted by an authorized person.
Failure to follow this instruction can result in injury or equipment damage.
No default password is provided for these adjustment screens. It is always possible to add one using the XBT-L1000 software.
Note: Even if the setpoint limiter is not configured, the associated parameters,
SP_INF and SP_SUP appear in this adjustment screen. Their modification is not acknowledged. In the PL7 configuration screen, the parameters associated with the setpoint limiter are called SP_MIN and SP_MAX.
Illustration This diagram shows a parameter adjustment screen.
AT
TC_0001
AUTO
KP
TI (s)
TD (s)
O_BIAS
DBAND
KD
ORATE1
:
:
:
:
:
:
:
H
1.0
0.0
0.0
0.0
0.0
10.0
0.0
DH
SP_SUP
SP_INF
TS (s)
PV_H
PV_L
INTBND
:
:
:
:
:
:
LOCAL
100.0
0.0
0.30
95.0
5.0
0.0
Sa
2 Alarm page 1 ON
242
35012329 02 May 2007
Description
Operating
The following table shows the function of the dynamic selection keys.
Key Description
This key is used to access the previous loop.
Sa
This key is used to access the next loop.
This key is used to save the current values of the parameters in the initial values.
CAUTION: Saving this does not update the PL7 application in the PC which may be connected.
35012329 02 May 2007
243
Operating
Autotuning screen
At a Glance This view is dedicated to autotuning and is used to start loop autotuning. It is also used to return to the old parameter values that existed prior to autotuning.
Note: the autotuning diagnostics messages are global in the process control channel. They concern only one of the 3 loops of a loop controller with 3 single loops or only one of the 2 loops of a cascade or autoselector loop controller
(even if these messages are globally displayed).
Illustration
Description
This diagram shows an autotuning screen.
TC_0001
AUTO
KP
TI
TD
:
:
:
H DH
ACTUAL
1.0
0.0
0.0
Step
Tmax (s)
Perf
:
:
:
LOCAL
PREV
1.0
0.0
0.0
10.0
100.0
0.50
AT
Sa
Pr
2 Alarm page 1 ON
The following table shows the function of the dynamic keys.
Key Description
This key is used to start or stop autotuning.
AT
This key is used to save the current values of the parameters in the initial values.
Sa
This key is used to return to the set of previous parameters.
Pr
This key is used to acknowledge the diagnostics.
Ack
244
35012329 02 May 2007
Operating
Setpoint programmer selection screen
At a Glance This screen is used to: z z
Display the various setpoint programmers with the current state (INIT, RUN,
STOP) and if a profile is started, the number of the profile which is running.
Select a setpoint programmer.
Note: to optimize communication, loop labels are read only on displaying the screen. This can cause inconsistencies when the data are modified by the PLC.
Redisplaying the screen will update the new values. If communication is not limited, data can be configured in cyclic read mode and not in read only mode.
Illustration
Description
This diagram shows a setpoint programmer selection screen.
7
8
5
6
3
4
1
2
9
10
SPP_3
SPP_4
SPP_5
2 Alarm page 1
RUN
INIT
STOP
PF 1
PF 1
N°1
ON
The following table shows the function of the dynamic selection keys.
Key Description
These dynamic keys are used to select the required loop for the adjustment screens. It is also possible to enter the loop number directly.
35012329 02 May 2007
245
Operating
Setpoint programmer runtime screen
At a Glance This screen is used to: z z z z select one of the setpoint programmer profiles, control the selected profile, display the output values of the profile running, z segment running, z z segment type, time elapsed, z calculated setpoint, display and modify the execution parameters, z z z
SP_O, threshold, number of repetitions.
How to perform an action
This table describes the steps to be followed for performing an action from the setpoint programmer runtime screen.
Step
1
2
3
4
Action
Select a profile using the MOD key.
Press the dynamic key required.
Result : a second screen is displayed.
To confirm, press the dynamic key associated with the required command.
If you wish to return to the runtime screen, press the R1 key.
Illustration This diagram shows a setpoint programmer runtime screen.
>>
<<
SPP
SEG
SPP_3
RUN 1
SP: 37.5
PV: 0.0
Seg time:
Tot time:
Profile 1
Segment: 5 / 16
N° Cycle: 1
10 s
74 s
Start: SP
SP_O: 10.0
Threshold: 2.00
2
Execute
Alarm page 1 to infinity
Restart on 2
STOP
RST
ON
246
35012329 02 May 2007
Description
Operating
The following table shows the function of the dynamic keys.
Key
STOP
Description
This dynamic key is used to activate the RUN or STOP command, if a profile is running.
This dynamic key is used to activate the RESET command.
RST
This dynamic key is used to activate the HOLD or DEHOLD command.
This dynamic key is used to activate the Disable/Enable command of the guaranteed dwell time . This command does not appear when the guaranteed dwell time has not been configured on the current profile.
This dynamic key is used to activate the NEXT command.
SPP
SEG
This dynamic key is used to activate the BACK command.
This dynamic key is used to access the setpoint programmer selection screen.
This dynamic key is used to access the setpoint programmer adjustment screen.
35012329 02 May 2007
247
Operating
Setpoint programmer adjustment screen
At a Glance
Illustration
Description
This screen is used to display and modify the setpoint and time (or ramp) values of the segments from the selected profile.
This diagram shows a setpoint programmer adjustment screen.
SPP
SPP_3 Profile 1
4
5
6
Segments used: 16
SY
1
SP
100.0
VAL Unit Type
20.0
p/s /
2
3
100.0
20.0
5.0
200.0
s p/m
- =
/
7
8
2
20.0
50.0
50.0
80.0
0.1
0.2
5.0
5.0
80.0
4.0
Alarm page 1 m m s s s
- =
/
- =
/
-
Sa
ON
The following table shows the function of the dynamic selection keys.
Key Description
These dynamic keys are used to display the next/previous segments. They are active when the number of segments from the selected profile is greater than the number of displayable segments.
Sa
This dynamic key is used to save the parameters. This command must be confirmed.
248
35012329 02 May 2007
Operating
Operating the alarm pages
At a Glance
Alarm types
The alarm pages and their management are identical to the XBT alarm pages (for further details, see the XBT-L1000 software documentation). In the applications offered, all the process control alarms are in the same group.
There are 6 alarm types per process control loop: z z z z z z process value very high threshold overflow, process value high threshold overflow, process value low threshold overflow, process value very low threshold overflow, high deviation overflow between process value and setpoint, low deviation overflow between process value and setpoint.
35012329 02 May 2007
249
Operating
9.3
XBT-F02 and TXBT-F02 process control screens
At a Glance
Subject of this
Section
What's in this
Section?
This Section describes the XBT-F02 and TXBT-F02 runtime screens, dedicated to process control.
This section contains the following topics:
Topic
Monitoring screen
Control screen
Adjustment screen
Setpoint programmer selection screen
Setpoint programmer runtime screen
Setpoint programmer adjustment screen
Operating the alarm pages
Page
250
35012329 02 May 2007
Operating
Monitoring screen
At a Glance The monitoring screen is the input point for the process control application. This view provides a summary of all the loops used.
Note: No entries can be made from this view.
Illustration
Note: to optimize communication, loop labels are read only on displaying the screen. This can cause inconsistencies when the data are modified by the PLC.
Redisplaying the screen will update the new values. If communication is not limited, data can be configured in cyclic read mode and not in read only mode.
This diagram shows a monitoring screen.
CONTROL LOOP SELECTION
1 TC_0001
2
TC_0002
TC_0003
1/8
3
4
5
6
7
D
D
9/16
8
9
10
11
12
1
2
13
14
15
16
Loop 1 Alarm(s) 06/05/98
L
H
15 :01 :29
06/05/1998
N°1
SPP
SELECT
ON
15 : 13
35012329 02 May 2007
251
Operating
Description The information displayed for each loop is as follows: z z z z the loop label, the Auto/Manual operating mode, autotuning is running (or not), the sum of the alarms.
The following table shows the function of the dynamic selection keys.
Key Description
These dynamic keys are used to select the required loop for the adjustment screens.
252
35012329 02 May 2007
Operating
Control screen
At a Glance This screen is used to globally display a process control loop. The loop can be controlled in manual mode and the setpoint in local mode.
This screen also serves: z z as the adjustment screen, as the autotuning screen,
CAUTION
Loops must only be adjusted by an authorized person.
Failure to follow this instruction can result in injury or equipment damage.
No default password is provided for these adjustment screens. It is always possible to add one using the XBT-L1000 software.
Note: the autotuning diagnostics messages are global in the process control channel. They concern only one of the 3 loops of a loop controller with 3 single loops or only one of the 2 loops of a cascade or autoselector loop controller (even if these messages are globally displayed).
35012329 02 May 2007
253
Operating
Illustration This diagram shows a control screen.
AUTO TC_0003
100.0
LOCAL
Description
1/8
9/16
26mn 20mn 10mn
06/05/98
AM
0.0
PV:
SP:
OV:
60.0
20.0
40.0
OV1: 40.0
15 :01 :29
06/05/1998
DH
ON
15 : 41
LR
2
2 Loop 1 Alarm(s)
The following table shows the function of the dynamic keys.
Key Description
This key is used to switch the loop into automatic or manual mode.
AM
This key is used to switch the setpoint into Remote or Local mode.
LR
254
35012329 02 May 2007
Operating
Adjustment screen
At a Glance This screen is used to globally display a process control loop. It is used to control the loop in manual mode and the setpoint in local.
The recent change history of the process value, the setpoint and the commands is outlined on the screen.
Note: the refresh period is 5 seconds. The total save period is 26 minutes.
Illustration
Note: Even if the setpoint limiter is not configured, the associated parameters,
SP_INF and SP_SUP appear in this adjustment screen. Their modification is not acknowledged. In the PL7 configuration screen, the parameters associated with the setpoint limiter are called SP_MIN and SP_MAX.
This diagram shows an adjustment screen.
AUTO TC_0003 LOCAL
100.0
AT
Pr
1/8
Ack
9/16
Sa
26mn 20mn
KP
TI (s)
TD (s)
O_ BIAS
DBAND
INTBND
KD
2
2
:
:
:
:
:
:
:
1.0
0.0
0.0
0.0
0.0
0.0
10.0
Loop 1 Alarm(s)
KP Pr
TI Pr
TD Pr
ATSTEP
ATTMAX
ATPERF
:
:
:
:
:
:
10mn
1.0
0.0
0.0
10.0
100.0
0.50
SP_SUP
SP_INF
TS (s)
PV_H
PV_L
ORATE 1
:
:
:
:
:
:
100.0
0.0
0.30
95.0.
5.0
0.0
0.0
PV:
SP:
OV:
OV1:
06/05/98
60.0
20.0
40.0
40.0
AM
15 :01 :29
06/05/1998
DH
ON
15 : 41
LR
35012329 02 May 2007
255
Operating
Description The following table shows the function of the dynamic keys.
Key
AM
Description
This key is used to switch the loop into automatic or manual mode. The OV command can be modified.
LR
This key is used to switch the setpoint into Remote or Local mode. The SP command can be modified.
This key is used to start or stop autotuning.
AT
This key is used to return to the set of previous parameters.
Pr
This key is used to acknowledge the diagnostics.
ACK
256
35012329 02 May 2007
Operating
Setpoint programmer selection screen
At a Glance This screen is used to: z z
Display the various setpoint programmers with the current state (INIT, RUN,
STOP) and if a profile is started, the number of the profile which is running.
Select a setpoint programmer.
Note: to optimize communication, loop labels are read only on displaying the screen. This can cause inconsistencies when the data are modified by the PLC.
Redisplaying the screen will update the new values. If communication is not limited, data can be configured in cyclic read mode and not in read only mode.
Illustration This diagram shows a setpoint programmer selection screen.
SETPOINT PROGRAMMER SELECTION
7
8
5
6
9
10
3
4
1
2
SPP_3
SPP_4
SPP_5
N°1
2
23
Loop 1 Alarm(s) 06/05/98 15 :01 :29
06/05/1998
ON
15 : 50
35012329 02 May 2007
257
Operating
Description The following table shows the function of the dynamic selection keys.
Key Description
These dynamic keys are used to select the required loop for the adjustment screens. It is also possible to enter the loop number directly.
258
35012329 02 May 2007
Operating
Setpoint programmer runtime screen
At a Glance This screen is used to: z z z z select one of the setpoint programmer profiles, control the selected profile, display the output values of the profile running, z segment running, z z segment type, time elapsed, z calculated setpoint, display and modify the execution parameters, z z z
SP_O, threshold, number of repetitions.
How to perform an action
This table describes the steps to be followed for performing an action from the setpoint programmer runtime screen.
Step
1
2
3
4
Action
Select a profile using the MOD key.
Press the dynamic key required.
Result : a second screen is displayed.
To confirm, press the dynamic key associated with the required command.
If you wish to return to the runtime screen, press the R1 key.
35012329 02 May 2007
259
Operating
Illustration This diagram shows a setpoint programmer runtime screen.
SPP_3 PROFILE N° 1
RUN Profile 1 GUARANTEED DWELL TIME FREEZE
SPP
SEGMENT
SP : 35.25
PV : 0.00
Segment time:
Total time :
6 sec
1994 sec
Segment: 5 / 16
N° Cycle: 1
STOP
RST
SPP
SELECT
Start: SP
SP_INF: 10.00
THRESHOLD: 2.00
2
24
Loop 1 Alarm (s)
Repetition:
Execute to infinity
Resume at segment n° 2
06/05/98 15 :01 :29
06 / 05 / 1998
ON
15 : 55
260
35012329 02 May 2007
Description
Operating
The following table shows the function of the dynamic keys.
Key
STOP
Description
This dynamic key is used to activate the RUN or STOP command, if a profile is running.
This dynamic key is used to activate the RESET command.
RST
This dynamic key is used to activate the HOLD or DEHOLD command.
This dynamic key is used to activate the Disable/Enable command of the guaranteed dwell time . This command does not appear when the guaranteed dwell time has not been configured on the current profile.
This dynamic key is used to activate the NEXT command.
This dynamic key is used to activate the BACK command.
SPP
SEGMENT
SPP
SELECT
This dynamic key is used to access the setpoint programmer selection screen.
This dynamic key is used to access the setpoint programmer adjustment screen.
35012329 02 May 2007
261
Operating
Setpoint programmer adjustment screen
At a Glance
Illustration
Description
This screen is used to display and modify the setpoint and time (or ramp) values of the segments from the selected profile.
This diagram shows a setpoint programmer adjustment screen.
SPP_3
RUN
Segments used: 16
Profile 1
Profile n°1
GUARANTEED DWELL TIME FREEZE
SPP
SELECT
SEGMENT
1
4
5
2
3
6
7
8
9
10
11
12
13
14
15
16
2
25
Loop 1 Alarm(s)
90.0
20.0
20.0
45.0
45.0
80.0
80.0
30.0
30.0
90.0
SP
100.0
100.0
20.0
20.0
50.0
50.0
5.00
4.00
4.00
0.10
5.00
5.00
10.00
0.20
4.00
5.00
VAL
20.00
5.00
200.00
0.10
0.20
5.00
m s s
06 / 05 / 98 s s m s s s
TYPE phy/s s phy/m m m s s
UNIT
Ramp
Step =
Ramp
Step =
Ramp
Step
Ramp
Step =
Ramp
Step =
Ramp
Step
Ramp
Step
Ramp
Step
15:01:29 ON
06 / 05 / 1998
Sa
15:57
The following table shows the function of the dynamic selection keys.
Key Description
These dynamic keys are used to display the next/previous segments. They are active when the number of segments from the selected profile is greater than the number of displayable segments.
Sa
This dynamic key is used to save the parameters. This command must be confirmed.
262
35012329 02 May 2007
Operating
Operating the alarm pages
At a Glance
Alarm types
The alarm pages and their management are identical to the XBT alarm pages (for further details, see the XBT-L1000 software documentation). In the applications offered, all the process control alarms are in the same group.
There are 6 alarm types per process control loop: z z z z z z process value very high threshold overflow, process value high threshold overflow, process value low threshold overflow, process value very low threshold overflow, high deviation overflow between process value and setpoint, low deviation overflow between process value and setpoint.
35012329 02 May 2007
263
Operating
9.4
Exchange tables
At a Glance
Subject of this
Section
What's in this
Section?
This Section describes the operating exchange tables.
This section contains the following topics:
Topic
Parameter setting zone for a loop
Periodic data zone
Alarm table (loop only)
Specific XBT zone
Parameter setting zone for a setpoint programmer
Default addresses
Page
264
35012329 02 May 2007
Parameter setting zone for a loop
Operating
35012329 02 May 2007
265
Operating
Description This table is used by the front panel adjustment and autotuning screen pages (for an XBT-F01), and by the adjustment screen page (for an XBT-F02). The first 4 words (non-multiplexing) are used by the monitoring pages.
Rank
%MWn+0
%MWn+1
%MDn+2
%MWn+4
%MWn+5
Parameter Exchange
Number of loop selected (1 word)
From 0 to 29. This word lets you select the loop managed by the parameter setting zone if the specific XBT table is not configured. Otherwise it is not used.
This word is driven by the word %MWn+5 or is directly written
(overshooting the last or first loop makes it return to the first or last loop respectively). On initialization it is set to 0.
PLC <->
XBT
Identifier (1 word) PLC -> XBT
Bar chart number indicator (1 double word)
Each bit is associated with a loop. A bit set to 0 means the loop has only one output. A bit set to 1 means the loop has two outputs.
PLC -> XBT
Write access prohibited (1 word)
Write access to this table is only taken into account by the PLCs if this word is set to 0. This word is managed by the user application (Default = 0)
PLC -> XBT
Loop number increment/decrement (1 word)
The dynamic buttons in pulse mode of the XBT set to 1 the word bits controlling the incrementation or decrementation of the loop number.
X0: incrementation of the loop number (XBT-F01)
X1: decrementation of the loop number (XBT-F01)
X2: incrementation of the loop number (XBT-F02)
X3: decrementation of the loop number (XBT-F02)
X15: loop change latch (internal management). These bits are processed by the channel containing the currently selected loop. The bit is acknowledged on a rising edge.
PLC <->
XBT
Internal PLC
266
35012329 02 May 2007
35012329 02 May 2007
Operating
Rank
%MWn+6
%MWn+7
%MWn+8
Parameter Exchange
Command word for "toggle" buttons (1 word)
Each bit of the word lets you send a command to the selected loop, on change of status. This word is not used.
X0: 0 = switch to local setpoint ; 1 = switch to remote setpoint
X1: 0 = switch to manual mode; 1 = switch to automatic mode
X2: 0 = autotuning stopped; 1 = autotuning X3 started: return to previous adjustment
X4: acknowledgement of autotuning diagnostics
X5: 0 = remote setpoint 1 selected; 1 = remote setpoint 2 selected
X6: 0 = RAISE1 output deactivated; 1= RAISE1 output activated
X7: 0 = LOWER1 output deactivated; 1= LOWER1 output activated
X15: Save parameters
The selected loop acknowledges the command on a rising or falling edge. The associated buttons are in "toggle" mode. The word is updated by the PLC according to the current status of the loop (for bits allowing two distinct commands to be sent).
PLC <->
XBT
PLC <- XBT Command word for push buttons (1 word)
Each bit of the word lets you send a command to the loop selected. The first 4 bits are associated with dynamic buttons.
The following exist for opening:
X0: Change of setpoint mode
(remote -> local or local -> remote depending on the current mode)
X1: change in operating mode
(manu -> auto or auto -> manu depending on the current operating mode)
X2: start or stop autotuning, depending on whether an autotuning is in progress or not
X3: return to previous adjustment
X4: acknowledgement of autotuning diagnostics
X5: selection of remote setpoint 1
X6: selection of remote setpoint 2
X7: activation of the RAISE1 output
X8: deactivation of the RAISE1 output
X9: activation of the LOWER1 output
X10: deactivation of the LOWER1 output
X15: Save parameters. The selected loop acknowledges the command on a rising edge. The buttons are in pulse mode.
Loop label (4 words)
Updated by the loop when it is selected
PLC -> XBT
267
Operating
268
Rank Parameter
%MWn+12 Loop unit (3 words)
Updated by the loop when it is selected
%MWn+15 Loop identifier (1 word)
1H: single/process loop: nothing
2H: master cascade: M CASCADE
3H: slave cascade: S CASCADE
4H: autoselector, main loop: AUTOSELECTOR 0
5H: autoselector, constraint: AUTOSELECTOR 1
Updated by the loop when this is selected. Used to show the nature of the loop in the various screens.
%MWn+16 Loop controller identifier (1 word) xx1H: PID xx2H: single PID xx3H: ON OFF 2 states xx4H: ON OFF 3 states xx5H: IMC
Updated by the loop when this is selected.
Exchange
PLC -> XBT
PLC -> XBT
PLC -> XBT
%MWn+17 Alarm word (1 word)
Each bit defines a different alarm:
X0: STS_SIGMA_ALA (sum of the alarms)
X1: STS_HH (process value very high threshold exceeded)
X2: STS_H (process value high threshold exceeded)
X3: STS_L (process value low threshold exceeded)
X4: STS_LL (process value very low threshold exceeded)
X5: STS_DEV_H (positive deviation threshold exceeded)
X6: STS_DEV_L (negative deviation threshold exceeded)
X14: AT_NOT_AUTHORIZED
X15: NB_BARGRAPHS_OUT (0 = 1 bar chart; 1 = 2 bar charts)
This word is updated on every cycle.
%MWn+18 PV in the scale of 0-10000 (1 word)
PLC -> XBT
PLC -> XBT
%MWn+19 SP in the scale of 0-10000 (1 word) PLC -> XBT
%MWn+20 OUT1 in the scale of 0-10000 (1 word)
%MWn+21 OUT2 in the scale of 0-10000 (1 word)
%MFn+22 OUT_MAN
%MFn+24
%MFn+26
%MFn+28
%MFn+30
PV
SP
OUT1
OUT2
PLC -> XBT
PLC -> XBT
PLC <->
XBT
PLC -> XBT
PLC <->
XBT
PLC -> XBT
PLC -> XBT
35012329 02 May 2007
35012329 02 May 2007
Operating
Rank
%MFn+32
Parameter
STATUS1
X0: STS_M_A (0 = manu, 1 = auto)
X1: STS_TR_S1 (1 = tracking)
X2: STS_AT_RUNNING (1 = autotuning in progress)
X3: STS_R_L (0 = remote, 1 = local)
X4: STS_RAISE1 (output 1 of ON OFF or SERVO)
X5: STS_LOWER1 (output 2 of ON OFF 3 states or SERVO)
X6: STS_RAISE2 (output 1 of SERVO2)
X7: STS_LOWER2 (output 2 of SERVO2)
X8: STS_R1_R2 (0 = SP1 is selected, 1 = SP2 is selected)
X9: STS_AS (1 = autoselector in autoselection mode)
X10: STS_DIR1 (1 = autoselector in direct main loop mode)
X11: STS_DIR2 (1 = autoselector in direct secondary loop mode)
X12: STS_SEL_PID1 (0 = PID2 output selected,
1 = PID1 output selected)
Exchange
PLC -> XBT
%MWn+33 STATUS2 = autotuning diagnostics
X0 = autotuning in progress (STS_AT_RUNNING)
X1 = autotuning aborted (by the user or by the program)
(AT_ABORTED)
X2 = AT: parameter error (incorrect parameter, or modification of value while autotuning in progress)
(AT_ERR_PWF_OR_SYS_FAILURE)
X3 = AT: power outage (or system failure)
(AT_ERR_PWF_OR_SYS_FAILURE)
X4 = AT: saturation of PV or OV (AT_ERR_SATUR)
X5 = AT: deviation too small (AT_ERR_DV_TOO_SMALL)
X6 = AT: under-sampling (AT_ERR_TSAMP_HIGH)
X7 = AT: inconsistent response
(AT_ERR_INCONSISTENT_RESPONSE)
X8 = AT: PV unstable on initialization
(AT_ERR_NOT_STAB_INIT)
X9 = AT: TMAX too small (AT_ERR_TMAX_TOO_SMALL)
X10 = AT: noise too high (AT_ERR_NOISE_TOO_HIGH)
X11 = AT_TMAX too high (AT_ERR_TMAX_TOO_HIGH)
X12 = AT: process overshoot (AT_WARN_OVERSHOOT)
X13 = AT: process undershoot (AT_WARN_UNDERSHOOT)
X14 = AT: process unsymmetrical
(AT_WARN_UNSYMETRICAL_PLANT)
X15 = AT: integrating process
(AT_WARN_INTEGRATING_PLANT)
%MFn+34 SPEED_LIM_OUT
Refreshed on every cycle
PLC -> XBT
269
Operating
270
Rank
%MFn+36 to
%MFn+74
%MFn+76 to
%MFn+86
Parameter
Controller adjustment zone (20 floating point words) (*)
%MFn+36: T_ECH,
%MFn+38: OUT1_INF (read-only),
%MFn+40: OUT1_SUP (read-only),
%MFn+42: SP_INF (read-only),
%MFn+44: SP_SUP (read-only),
%MFn+46: OUT2_INF (read-only),
%MFn+48: OUT2_SUP (read-only),
%MFn+50: PV_INF (read only),
%MFn+52: PV_SUP(read only),
%MFn+54: KP (PID) / ONOFF_L (ON OFF) / KS (IMC),
%MFn+56: TI (PID) / ONOFF_H (ON OFF) / OL_TIME (IMC),
%MFn+58: TD (PID) / HYST (ON OFF 3 states) / T_DELAY
(IMC),
%MFn+60: OUTBIAS (PID) / CL_PERF (IMC),
%MFn+62: INT_BAND (PID),
%MFn+64: DBAND (PID, IMC)
%MFn+66: KD (PID except single PID)
%MFn+68: OUTRATE1 (PID, IMC),
%MFn+70: OUTRATE2,
%MFn+72: PV_L,
%MFn+74: PV_H
Autotuning adjustment zone (6 floating point words) (*)
%MFn+76: AT_STEP,
%MFn+78: AT_TMAX,
%MFn+80: AT_PERF,
%MFn+82: KP_PREV (PID) / KS_PREV (IMC), (read only)
%MFn+84: TI_PREV (PID) / T1_PREV (IMC), (read only)
%MFn+86: TD_PREV (PID) / T_DELAY_PREV (IMC) (read only)
Exchange
PLC <->
XBT
PLC <->
XBT
%MFn+88 to
%MFn+102
This zone is only managed if the autotuning function exists (PID,
IMC).
Output and alarm adjustment zone (8 floating point words)
(*)
%MFn+88: OUT1_TH1,
%MFn+90: OUT1_TH2,
%MFn+92: OUT2_TH1,
%MFn+94: OUT2_TH2,
%MFn+96: PV_LL,
%MFn+98: PV_HH,
%MFn+100: DEV_L,
%MFn+102: DEV_H
PLC <->
XBT
35012329 02 May 2007
Operating
(*) : Zone tested by checksum every second at the start of processing. If any changes are made, the modified parameters are written in the loop parameters. The zone is updated every second at end of processing using the loop parameters.
Parameter adjustment table
The parameter adjustment tables have the same structure as the multiplexing tables.
z z
Several controllers are configured with the same address. Operation is then the same as for the multiplexing table.
Each controller is configured with an independent address (without overlapping of the fields). This enables several controllers to be viewed simultaneously.
35012329 02 May 2007
271
Operating
Periodic data zone
Description This zone is used by the Trend screens.
Rank
%MWn+0 to
%MWn+11
Parameter
Loop 1 data (6 floating point words)
%MWn+0: OUT_MAN,
%MWn+2: PV,
%MWn+4: SP,
%MWn+6: OUT1,
%MWn+8: OUT2,
%MWn+10: STATUS1
%MWn+11: STATUS2
The STATUS words are identical to those in the parameter setting zone. This zone is updated at every cycle.
Exchange
API -> XBT
%MWn+12 Loop 2 data (6 floating point words)
%MWn+24 Etc, depending on the number of loops configured for the
XBT
API -> XBT
API -> XBT
This table takes up 12 x words (number of loops) configured for the XBT, up to a maximum of 192 words (%MW) for 16 loops.
Note: The OUT1 and OUT2 fields can be found in both the parameter setting zone and in the periodic zone. If the loop only has one output, the output is in OUT1 and the associated bar chart is magenta. When there is Heat/Cool, the cold output is stored in OUT2 and the warm output in OUT1. Process control channel variables are then reversed. This enables the warm output to be displayed in magenta and the cold output in blue.
272
35012329 02 May 2007
Operating
Alarm table (loop only)
Description This table is situated in the XBT terminal dialog table.
Rank
%MWn+0
%MWn+1
%MWn+i
Parameter Exchange
Loop 1 alarm word (1 byte)
Each bit defines a different alarm:
X0: STS_SIGMA_ALA (sum of the alarms)
X1: STS_HH (process value very high threshold exceeded)
X2: STS_H (process value high threshold exceeded)
X3: STS_L (process value low threshold exceeded)
X4: STS_LL (process value very low threshold exceeded)
X5: STS_DEV_H (positive deviation threshold exceeded)
X6: STS_DEV_L (negative deviation threshold exceeded)
This word is updated on every cycle. It is identical to that of the parameter setting zone.
PLC -> XBT
Loop 2 data (1 byte) PLC -> XBT
Etc, depending on the number of loops configured for the
XBT
PLC -> XBT
35012329 02 May 2007
273
Operating
Specific XBT zone
274
35012329 02 May 2007
Description
Operating
This table is used by the PLC to control the XBT.
Rank
%MWn+0
%MWn+1
Parameter
Status of loop 1 monitoring screen (1 word)
This word lets you display a list of possible states:
X0: 0 = there is no loop (the complete word is invalid in this case); 1 = the loop exists
X1: 0 = loop in manual mode; 1 = loop in automatic mode
X2: high level alarm on process variable
X3: low level alarm on process variable
X4: alarm on deviation
Exchange
Selected loop number (1 word)
From loop 1 to loop 16.
This number defines the loop managed by the parameter setting zone.
This word is driven by the word %MWn+5 of the parameter setting zone (overshooting the last or first loop makes it return to the first or last loop respectively). On initialization, it is set to 0. This word can also be written directly.
PLC <-> XBT
PLC -> XBT
%MWn+2
N.b.: X2 and X3 are exclusive.
Status of loop 2 monitoring screen (1 word) etc, up to loop 16
%MWn+17 Loop 1 label (4 words)
Update on initialization
%MWn+21 Loop 2 label (4 words )
Update on initialization etc, up to loop 16
%MWn+81 Loop 1 unit (3 words)
Update on initialization
%MWn+84 Loop 1 identifier (1 word)
1H: single/process loop: nothing
2H: master cascade: M CASCADE
3H: slave cascade: S CASCADE
4H: autoselector, main loop: AUTOSELECTOR 0
5H: autoselector, constraint: AUTOSELECTOR 1
Update on selection of loop
%MFn+85 to
%MFn+87
Loop 1 scale parameters (2 floating points)
%MFn+85: PV_INF
%MFn+87: PV_SUP
PLC -> XBT
PLC -> XBT
PLC -> XBT
PLC -> XBT
PLC -> XBT
PLC -> XBT
35012329 02 May 2007
275
Operating
276
Rank Parameter Exchange
%MWn+89 Command word for "toggle" buttons of loop 1 (1 word)
Each bit of the word lets you send a command to the selected loop, on change of status.
X0: 0 = switch to local setpoint ; 1 = switch to remote setpoint
X1: 0 = switch to manual mode; 1 = switch to automatic mode
X2: 0 = autotuning stopped; 1 = autotuning started
X3: return to previous adjustment
X4: acknowledgement of autotuning diagnostics
X5: 0 = remote setpoint 1 selected; 1 = remote setpoint 2 selected
X6: 0 = RAISE1 output deactivated; 1= RAISE1 output activated
X7: 0 = LOWER1 output deactivated; 1= LOWER1 output activated
X15: Save parameters
The loop acknowledges the command on a rising or falling edge. The associated buttons are in "toggle" mode. The word is updated by the PLC according to the current status of the loop (for bits allowing two distinct commands to be sent).
PLC <-> XBT
%MWn+90 Command word for push buttons of loop 1 (1 word)
Each bit of the word lets you send a command to the loop selected. The first 4 bits are associated with dynamic buttons.
The following exist for opening:
X0: Change of setpoint mode (remote -> local or local -> remote depending on the current mode)
X1: change of operating mode (manu -> auto or auto
-> manu depending on the current operating mode)
X2: start or stop autotuning, depending on whether an autotuning is in progress or not
X3: return to previous adjustment
X4: acknowledgement of autotuning diagnostics
X5: selection of remote setpoint 1
X6: selection of remote setpoint 2
X7: activation of the RAISE1 output
X8: deactivation of the RAISE1 output
X9: activation of the LOWER1 output
X10: deactivation of the LOWER1 output
X15: Save parameters
The loop acknowledges the command on a rising edge. The buttons are in pulse mode.
PLC <- XBT
35012329 02 May 2007
Operating
Rank
%MWn+91
...
Parameter
Loop 2 unit (3 words)
Loop 2 identifier (1 word)
Loop 2 scale parameters (2 floating points)
Command word for "toggle" buttons of loop 2 (1 word)
Command word for loop 2 push buttons (1 word) etc, up to loop 16
%MWn+241 Programmer 1 label (4 words)
%MWn+245 SPP2 label (4 words) etc, up to loop 16
Exchange
PLC <-> XBT
PLC -> XBT
PLC -> XBT
This table occupies 281 words, regardless of the number of loops and SPP configured.
35012329 02 May 2007
277
Operating
Parameter setting zone for a setpoint programmer
278
35012329 02 May 2007
Description
35012329 02 May 2007
Operating
This table describes the multiplexing parameters for a setpoint programmer.
Address
%MWn+0
%MWn+1
%MWn+2
Default value
Configured in PL7
0
0
Description
Write access prohibited.
Write access prohibited.
Write access to this zone is only taken into account if this word is set to 0.
SPP number increment/decrement (X0, X1 bits) and displayed segment packet number increment/decrement
(X2, X3 bits)
%MWn+3 0
%MWn+4 1
%MWn+5 1
%MWn+6 0
%MWn+7
%MWn+8
SPP number selected (0: first SPP).
CUR_PF
SEG_OUT
CUR_ITER
Configuring 1 st
SPP profile 1
NB_RT_PFi
Configuring 1 st
SPP profile 1
Profile configuration:
%MWn+8:X0: guaranteed dwell time
%MWn+8:X1 to X2: holding type (not used),
%MWn+8:X3: start (0: SP; 1: PV),
%MWn+8:X4: continuous retries (1),
%MWn+8: start of retries (0 : SP).
%MWn+9
%MWn+10
%MWn+9:X9 =1
%MWn+9:X13 = 1
Profile state:
%MWn+9:X0 to X7: discrete outputs
%MWn+9:X8: HOLD_PF
%MWn+9:X9: INIT
%MWn+9:X10: RUN
%MWn+9:X11: STOP
%MWn+9:X12: HOLD_PAG
%MWn+9:X13: this bit is used to display the execution parameters of the displayed profile.
Configuring 1 st
SPP profile 1
Number of segments used
%MWn+11
Configuring 1 st
SPP profile 1
Restart segment number for retries
%MFn+12 0.0
%MFn+14 Not applicable
SP
PV
%MFn+16 0.0
%MFn+18 0.0
TOTAL_TIME
CUR_TIME
279
Operating
Address
%MFn+20
Default value
Configuring 1 st
SPP profile 1
Description
THLD_PFi
%MFn+22
%MWn+24 1
%MWn+25 0
Configuring 1 st
SPP profile 1
SP0_PFi
Displayed profile selection
Command word:
Pulse-based commands
%MWn+25:X0: RESET
%MWn+25:X1: START / STOP
%MWn+25:X2: HOLD_PF / DEHOLD_PF
%MWn+25:X3: NEXT_SG
%MWn+25:X4: BACK_SG
%MWn+25:X5: HOLD_PAG / DEHOLD_PAG
%MWn+25:X6: SAVE_PARAM
"Toggle" commands
%MWn+25:X8: RESET
%MWn+25:X9: START / STOP
%MWn+25:X10: HOLD_PF / DEHOLD_PF
(1 = HOLD_PF; 0 = DEHOLD_PF)
%MWn+25:X11: NEXT_SG
%MWn+25:X12: BACK_SG
%MWn+25:X13: HOLD_PAG / DEHOLD_PAG
(1 = HOLD_PAG; 0 = DEHOLD_PAG)
%MWn+25:X15: SAVE_PARAM
%MWn+26 1
%MWn+27
Configuring 1 st
SPP profile 1
%MFn+28 to
%MFn+90
Configuring 1 profile 1 st
SPP
Displayed profile number (from 1 to 6)
Number of segments in displayed profile
32%MF exchange zone of segments from the displayed profile (SPi, VALi, SPi+1, VALi+1, ...)
280
35012329 02 May 2007
35012329 02 May 2007
Operating
Address
%MWn+92 to
%MWn+99
Default value
Configuration
Description
Configuration (8 %MWi, or 16 x 8 bits)
Segment 1:
%MWn+92:X0 (1: second)
%MWn+92:X1 (1: minute)
%MW3443:X2 (1: hour)
%MWn+92:X3 (1: physical unit)
%MWn+92:X4 (ramp/dwell time)
%MWn+92:X5 (guaranteed dwell time)
Segment 2:
%MWn+92:X8 (1: second)
%MWn+92:X9 (1: minute)
%MWn+92:X10 (1: hour)
%MWn+92:X11 (1: physical unit)
%MWn+92:X12 (ramp/dwell)
%MWn+92:X13 (guaranteed dwell time)
Segment 3:
%MWn+93:X0 (1: second)
%MWn+93:X1 (1: minute)
%MWn+93:X2 (1: hour)
%MWn+92:X3 (1: physical unit)
%MWn+93:X4 (ramp/dwell)
%MWn+93:X5 (guaranteed dwell time)
Segment 4:
%MWn+93:X8 (1: second), etc.
Label of selected SPP (4%MWi) %MWn+10
0
%MWn+10
4
%MWn+10
5
%MWn+10
6
Configuration Current segment type:
X3 X2 X1 define the type of guaranteed dwell time
1 0 0 maintain on input deviation
1 0 1 maintain on high deviation
1 1 0 maintain on low deviation
1 1 1 maintain on deviation
X4 = 1 Dwell
X5 = 1 Rising ramp
X6 = 1 Falling ramp
%MWn+105:X4 = 1 SPP1 state:
%MWn+105:X4 = 1 INIT
%MWn+105:X5 = 1 RUN
%MWn+105:X6 = 1 STOP
0 Number of the current profile SPP1:
0 : (no profile running) or 1 to 6
281
Operating
Address
%MWn+10
7
%MWn+10
8
...
%MWn+12
3
%MWn+12
4
Default value
%MWn+107:X4 = 1 SPP2 state:
%MWn+107:X4 = 1 INIT
%MWn+107:X5 = 1 RUN
%MWn+107:X6 = 1 STOP
0
Description
...
Number of the current profile SPP2:
0 : (no profile running) or 1 to 6
...
%MWn+123:X4 = 1 SPP10 status:
%MWn+123:X4 = 1 INIT
%MWn+123:X5 = 1 RUN
%MWn+123:X6 = 1 STOP
0 Number of the current profile SPP10:
0 : (no profile running) or 1 to 6
282
35012329 02 May 2007
Operating
Default addresses
Description This table describes:
Table
Loop periodic zone
Loop adjustment zone
XBT zone
Start address End address
Alarm table %MW3228
Programmer parameter setting zone %MW3350
%MW3500
%MW3700
%MW3810
%MW3242
%MW3474
%MW3691
%MW3803
%MW4090
Max. size
(%MW)
15
125
192
104
281
Note: During modification of the dialog zone in XBT-L1000, the start address of this zone must be adjusted in order for the alarm zone start address to remain
%MW3228.
35012329 02 May 2007
283
Operating
284
35012329 02 May 2007
Operating modes
10
At a Glance
Subject of this
Chapter
What's in this
Chapter?
This Chapter describes the process control operating modes: PLC and control loop operating modes.
This chapter contains the following sections:
Section
10.1
10.2
10.3
10.4
Topic
Operating process control channels
Handling process control operations according to PLC operating mode
Common operating modes for process control loops
Operating modes for each process control loop
Page
285
35012329 02 May 2007
Operating modes
10.1
Operating process control channels
At a Glance
Subject of this
Section
What's in this
Section?
This section describes how process control handling is distributed and synchronized for the best possible results in processor loading.
This section contains the following topics:
Topic
Distribution of process control handling
Synchronizing pre- and post- processing
Multitasking application
Page
286
35012329 02 May 2007
Operating modes
Distribution of process control handling
MAST task and loop sampling
Optimizing processor loading
Example
The processing task period and the control loop sampling periods are different.
By default, the MAST task lasts 20 ms, while the process control channel sampling times are 300 ms.
To optimize processor loading, the periodic processing of different process control channels is distributed over several task cycles.
Distribution of the processing in this way is an entirely automatic operation and does not require programming .
The order of loop distribution over the task cycles follows the order in which the loops were created.
z z
Let there be 18 loops configured in the following manner:
14 loops configured to 300 ms (loops 1 to 14),
2 loops configured to 200 ms (loops 15 and 16), z 2 loops configured to 100 ms (loops 17 and 18).
Distribution of the processing operation:
Tn = 50ms Tn+2 = 150ms
Tn+1 = 100ms
Tn+4 = 250ms
Tn+3 = 200ms
Tn+6 = 350ms
Tn+5 = 300ms Tn+7 = 400ms
MAST
Reg seq
Reg seq
Reg seq
Reg seq
Reg seq
Reg seq
Reg seq
Reg seq
Loops 17, 18
+ loops 1, 2, 3
Loops 17, 18
+ loops 7, 8
Loops 15, 16
+ loops 4, 5, 6
Loops 17, 18
+ loops 11, 12
Loops 9, 10
Loops 17, 18
+ loops 1, 2, 3
Loops 15, 16
+ loops 13, 14
35012329 02 May 2007
287
Operating modes
Synchronizing pre- and post- processing
Trigger bits
Example
If you wish to closely synchronize the sequential processing with the periodical execution of each control loop, for each loop with 2 bits contained in the status words there is: z z
STS_TOP_NEXT_CYCLE: pre-processing trigger bit.
STS_TOP_CUR_CYCLE: post-processing trigger bit.
These two bits can act as enabling conditions for processing operations written in structured text or ladder language.
This synchronization can be useful for Stop/Run operating modes, or for variation or compensation calculations.
The pre-processing status bit is on 1 during the task cycle before the control processing cycle.
The post-processing status bit is on 1 during the entire task cycle which follows the control handling cycle.
To correctly synchronize the sequential handling with the process control calculations, processing operations must be integrated within the same task.
In manual or tracking mode, the command is generated in all processing cycles.
These synchronizing bits are always on 1 while in these modes.
For example, Loop on 200 ms with a MAST task on 50 ms:
250 300 350 400 450 500
MAST
1
0
1
0
REG
STS_TOP_NEXT_CYCLE
STS_TOP_CUR_CYCLE
REG
288
35012329 02 May 2007
Operating modes
Multitasking application
Optimum functioning level
For the optimum and determinist operating level, in a given control channel you are z z advised to assign to the same task:
Inputs/outputs channels,
Sequential pre- and post processing, z Sequential processing managing the PLC’s operating modes.
35012329 02 May 2007
289
Operating modes
10.2
Handling process control operations according to
PLC operating mode
Handling process control operations according to the PLC operating mode
At a Glance
PLC power-up
PLC behavior can be altered either by user intervention or by a fault. In this case, the process control channels follow a preset downgraded functioning mode. The following PLC operating modes can alter process control operations.
On PLC power-up, the system searches for a valid application in the user memory space.
If the application is valid, the system changes to a state of configuration and each process control channel is called. The channel context is then set on initial values which can be used on application.
If the application is not valid, the system changes to standby mode to wait for a reconfiguration request.
Processor in
RUN mode z z z z
In RUN mode, the processor carries out successively on each cycle:
The reading of input channels,
The execution of setpoint programs,
The execution of process control loops,
The processing of sequential programming, z The writing of outputs.
All process control channels are called in each task cycle: z Calculation of the process value, (PV), calculation of the Feed Forward
(OUT_FF), alarm management, operating modes, setpoint programmers and z generation of Manu or Tracking mode commands are all carried out on each cycle.
Loop commands in Auto mode are generated and setpoints are calculated during the sampling period.
Switch to STOP mode
The process control channels do not directly initiate the STOP mode for the processor or the task. Switching to STOP mode means that all the current functions in progress stop.
The process control channels are no longer carried out. They refuse all commands
(in Auto or Manu, etc.). The calculation results remain in their current state. Physical outputs take on the fallback value set in the configuration.
Inputs are always refreshed. Parameters may therefore be altered. The validity check is carried out on the next start-up.
290
35012329 02 May 2007
Cold restart
Warm restart
Operating modes
A cold restart can be initiated in several ways: z z z
Changing the cartridge (cold start),
A reconfiguration ( by loading a program, transferring a new application, etc.),
A new configuration.
A cold restart is indicated by the %S0 system bit.
The process control channels monitor their configuration, and initialize their parameters and status as from the first cycle. Algorithm processing is executed from the second cycle.
All commands generated in a sequential operation from the first cycle are accepted, except for orders to track or autotune on the loop controller. The command is refused.
A warm restart happens on a power cut followed by a power restart.
At the moment of the power cut, parameters are saved. The system and application contexts (e.g. application data, operating modes) are retained.
Any autotuning in progress will be aborted. The process control channels are carried out as from the first cycle.
35012329 02 May 2007
291
Operating modes
10.3
Common operating modes for process control loops
At a Glance
Subject of this
Section
What's in this
Section?
This Section describes the operating modes which are common to all process control loops: loop control in manual mode, starting autotuning, execution in
Tracking mode, etc.
This section contains the following topics:
Topic
Loop execution in manual and automatic modes
Autotuning and Tracking mode
Auto / Manual and Manual / Auto switching
Behavior of loops during I/O errors
Page
292
35012329 02 May 2007
Operating modes
Loop execution in manual and automatic modes
Control in manual mode
Manual mode enables the user to directly apply a value to the loop controller output.
This mode can be selected from the PL7 Debug screens. It can also be controlled from the different XBT-F terminal screens.
The user can switch to manual mode by sending a command. When this command is accepted, manual mode is indicated by the status bit STS_AUTO_MANU.
Control of the loop or loop controller command can then be engaged. When the command is a digital value, it is subject to the high and low limits as well as the speed limit. Output is processed on each task cycle.
Controlling
Servo output without position copy in manual mode
Manual control is always carried out on the OUT_MAN variable. This is limited between 0 and 100. However, if OUT_MAN does not have a direct link with the actual position of the actuator, the actuator must be able to be opened or closed, even if OUT_MAN has reached one of its limits. To do this, it is possible to enter a value into OUT_MAN which is beyond its limits: OUT_MAN will be limited, but the change in the calculated command will be accepted by the Servo function.
For example, OUT_MAN = 100.0, the actuator is open at 50%. To apply an opening of 70%, you must enter OUT_MAN = 120.0. OUT_MAN will then take on the limited value of 100.00.
Execution in automatic mode
In automatic mode, the command value is calculated by the loop controller from the setpoint value and the PV value.
Switching to automatic mode is carried out from the PL7 or XBT-F screens. It can also be carried out by sending a command. When this command is taken into account, automatic mode is indicated by the status bit STS_AUTO_MANU. Output is processed on each sampling cycle.
35012329 02 May 2007
293
Operating modes
Autotuning and Tracking mode
Autotuning execution
Tracking mode execution
Before autotuning, you must first enter step function duration, performance and amplitude of the desired command.
If these parameters have too small or too large values, autotuning will not be executed.
The loop controller can be in automatic or manual mode before autotuning is executed. Sending a command starts the autotuning process. During the autotuning process (2.5 times the step function period), the function controls the loop controller output. This output cannot be modified.
The autotuning function automatically sets loop controller coefficients. The diagnostics word shows any possible faults detected during autotuning. When autotuning is complete, the loop controller assumes its operating mode prior to the autotuning operation.
If the loop controller is in automatic mode, it uses the new parameters. The
Previous adjustment command returns you to the previous parameters.
This operating mode is used to force a process control loop’s digital outputs. This is often used when closing an open loop to prevent a bump occurring in the command units.
Tracking mode is also used in back-up architectures composed of one active and one passive PLC. Here it makes the passive PLC outputs identical to the active PLC outputs.
Tracking mode uses a parameter (%MF address) and a command (send command): z Switching to Tracking mode is done by sending a command. The command is z refused if the address containing the Tracking value is not entered.
If the order is sent, the process control loop output value is replaced by the
Tracking output value. The internal variables are regularly initialized with the output value.
z If the order is given to abort Tracking mode, the loop controller returns to its previous operating mode without output bump.
Tracking mode has higher priority than automatic, manual and autotuning modes.
Tracking mode is not available for all loop controllers (characteristics none). For example, the ON OFF loop controller does not have this mode.
Tracking mode is global on cascade and auto selector loops.
294
35012329 02 May 2007
Operating modes
Auto / Manual and Manual / Auto switching
Auto / Manual
Switching
Manual / Auto
Switching
The manual command is continuously updated: it tracks the command output. On
Auto / Manual switching, the first manual value given is the last value calculated by the loop controller; which prevents bumps.
Manual / Auto switching (for any loop controller other than ON OFF) is bumpless on the output command, on condition that the BUMPLESS option is selected on configuration. For the PID, two scenarios can be distinguished: z Scenario: PID with integral action (Ti <> 0) :
The PID algorithm in incremental form guarantees there will be no bumps during the transition from Manual to Auto. In this case, the PID algorithm always tracks z the applied actual output.
Scenario: PID without integral action (Ti = 0) :
It is possible to obtain a bumpless Manual/Auto transition if the mode is configured as bumpless in the PID function parameters (if the PID has an integral action, this configuration has no object).
The OUTBIAS manual integral parameter is calculated during the switch so that deviation between the actual output and the output calculated by the PID algorithm in absolute format is accepted.
If bumpless mode is not selected, OUTBIAS is not recalculated on switch.
35012329 02 May 2007
295
Operating modes
Behavior of loops during I/O errors
Description By design, the process control loops do not accept possible errors that could occur on I/O cards. A loop’s operating mode can be made conditional during an I/O error, through the sequential program. Application monitoring, associated module bits and diagnostic words can generate the appropriate command for this loop.
296
35012329 02 May 2007
10.4
Operating modes
Operating modes for each process control loop
At a Glance
Subject of this
Section
What's in this
Section?
This section describes operating modes for each of the process control loops: process loop, single loop, cascade loop and auto selector loop.
This section contains the following topics:
Topic
Process loop operating modes
Single loop operating modes (3 single loops)
Cascade loop operating modes
Auto selector loop operating modes
Page
35012329 02 May 2007
297
Operating modes
Process loop operating modes
At a Glance
Initial operating mode
The initial operating mode of the loop can be configured on cold start. You can z z specify:
Whether the setpoint is local or remote, as well as the initial local setpoint value.
Whether the loop controller starts in automatic or manual mode. The initial manual value, if the loop controller is not an ON OFF loop controller
Process loop with a PID loop controller
Depending on loop controller type, this loop can have 2, 3 or 4 different operating modes (eg. automatic, manual, autotuning, Tracking modes).
Autotuning can be launched if the loop controller is in automatic or manual mode.
Switching to Tracking mode has priority and will possibly cancel the autotuning in progress.
The following diagram illustrates a process loop with a PID loop controller:
Updating of internal variables
Autotuning
KP, TI, TD
Process value branch
Setpoint branch
Feedforward branch
PID or
IMC
Auto / Manual
TR_I
AT_START
AT_STOP
OUT_MAN
Tracking
Output
Branch
If the output branch sends dotted lines back to OUT_MAN, the limits have been accepted.
If the loop controller is Split Range or Heat/Cool type, there are 2 output branches.
In this instance, autotuning and Servo type output without copy are not available.
If the loop controller is an ON OFF type in 2 or 3 states, there is no Feed forward branch or output branch.
298
35012329 02 May 2007
Operating modes
Single loop operating modes (3 single loops)
At a Glance The 3 single loops are independent and are represented by a diagram equivalent to z z that of the process loop, with the exception of:
The Feed forward branch does not exist.
A Split Range or Heat/Cool loop controller cannot be configured.
z The Process Value and Setpoint branches are simplified.
Single loop with a PID loop controller
The following diagram illustrates a single loop with a PID loop controller:
Updating of internal variables
Autotuning
KP, TI, TD
Process value branch
Setpoint branch
PID or
IMC
Auto / Manual
AT_START
AT_STOP
OUT_MAN
Output
Branch
Tracking
TR_I
Only one autotuning operation can be launched at a time on the 3 loops from the process control channel. If a second autotuning operation is requested, it is refused.
35012329 02 May 2007
299
Operating modes
Cascade loop operating modes
At a Glance
Closing the cascade
Cold start
All the switches are done without bumps on the loop controller outputs. Slave loop operating mode management is identical to process loop operating mode management: this loop behaves as if it were alone.
z z
However, there are mechanisms specific to the master loop:
Manual mode and Auto/Manu switching are identical to those of the process loop.
If the loop controller is in automatic mode (default mode), 2 cases must be distinguished: z z
The slave loop controller is in automatic mode and uses the remote setpoint.
In this case, the cascade is closed, so the master loop is really in automatic mode.
The slave loop controller is in automatic mode and uses the local setpoint, autotuning is running, loop controller is in tracking mode. In this case, the master loop controller is in tracking mode.
As the aim is to avoid a bump on cascade close, there are various situations: z If the slave loop controller uses the local setpoint, the master loop controller follows the slave’s local setpoint.
z z
If not, if the slave loop controller has an integral action, the master loop controller follows the slave loop process value.
Finally, if not, the slave loop controller is a P or LF. The master loop output is optimally calculated to prevent a bump during cascade close (according to the slave loop controller output and its parameters).
On cold start, the master loop controller always starts in automatic mode. However, the initial operating mode for the slave loop controller and setpoint type for each loop
(Remote/Local) can be configured.
Freezing output change
When the master is in automatic mode and the slave output is becoming saturated, the master loop has an additional function, which freezes the master output change in the direction the slave is being saturated. This function limits saturation of the master’s integral action. It is thus only active if the master loop controller has an integral action.
For example, when the slave loop controller is in automatic mode, it is configured in reverse action and its output is at its maximum limit. To move the output from its limit by acting on the setpoint, the setpoint must be lowered. The master output is then slanting in a rising direction.
300
35012329 02 May 2007
Cascade loop with a PID loop controller
Restrictions
Operating modes
The following schema shows a cascade loop with a PID loop controller:
Updating of internal variables
Autotuning
KP, TI, TD
Process value branch
Setpoint branch
PID / IMC
Master
Feedforward branch
Auto / Manual
AT_START
AT_STOP
Updating of internal variables
OUT_MAN
Autotuning
Setpoint branch
KP, TI, TD
SP
PID / IMC
Slave
Process value branch
Auto / Manual
AT_START
AT_STOP
OUT_MAN
Output
Branch
Tracking
TR_I
The cascade loop is globally made from 2 process loops with some restrictions and some additional functions.
The OUT_MAN master loop output is the remote setpoint of the slave loop setpoint branch. OUT_MAN output is thus expressed in the slave loop scale. It is subject to the slave loop Setpoint branch level limit.
The slave loop controller can be Split Range or Heat/Cool.
The Auto/Manual operating mode and the value of the master loop manual command cannot be accessed from the PL7 process control screens. They can however be accessed via the user program.
z z z z z
Restrictions are as follows:
No totalizer on master loop process value branch.
No Feed forward branch on slave loop.
No ON OFF loop controller on any of the loops.
The slave loop Setpoint branch is a single branch, with no scaling.
Only one model loop controller can be configured on the master or slave loop.
35012329 02 May 2007
301
Operating modes
Auto selector loop operating modes
At a Glance This loop causes 2 loop controllers to work on the same output. Each loop controller produces an action and a (minimum or maximum) comparator selects the action to be applied. The auto selector loop consists of a main loop made from a process loop and a secondary loop made from a single loop. The two loops share one single output branch.
For example, the auto selector loop is used to implement a restricted process control. The main loop is used to monitor the main value and the secondary loop is used to prevent an auxiliary value from exceeding a limit (or restriction), specified by this loop’s setpoint.
Inhibiting one of the loops
One of the following commands can be used to inhibit a loop to have either a process loop, or a single loop: direct output 1 or direct output 2.
The 2 loop controllers have the same sampling period.
Auto selector loop configuration
An auto selector loop can be configured in 2 ways: z Case 1: one single Auto/Manual at output branch level after selector. The z
OUT_MAN manual command value is thus directly applied on the loop output.
Case 2: an Auto/Manual on the output of each loop controller. Each loop controller’s operating mode is then independent. Each loop controller’s output value can be manually set upstream of the selector.
302
35012329 02 May 2007
Operating modes
Case 1: one single Auto/
Manual at output branch level
The following schema shows an auto selector loop with only one Auto/Manual at output branch level:
Updating of internal variables
Autotuning
KP, TI, TD
Process value branch
Setpoint branch
PID or
IMC
Main
Feedforward branch
DIR1
Auto / Manual
AS
Autotuning
KP, TI, TD
Process value branch
Setpoint branch
PID or
IMC secondary
DIR2
AT_START
AT_STOP
OUT_MAN
Output
Branch
Tracking
TR_I
In this case, the 2 loop controllers are always in automatic mode and track the applied OUT_MAN command. When the loop is in automatic mode, the output of these loop controllers is accepted. If this is not the case, the output is not accepted.
As the loop controllers are trackers of the actual output, there is no risk of bump on switching if the loop controller’s integral action is used.
The initial loop operating mode and initial setpoint type (Remote/Local) for each loop controller can be configured.
35012329 02 May 2007
303
Operating modes
Case 2: An Auto/
Manual on the output of each loop controller
The following schema shows an auto selector loop with one Auto/Manual on each loop controller’s output:
Updating of internal variables
Autotuning
KP, TI, TD
Process value branch
Setpoint branch
PID or
IMC
Feedforward branch
Auto / Manual
OUT_MAN1
Updating of internal variables
DIR1
AS
Autotuning
KP, TI, TD
Process value branch
Setpoint branch
PID or
IMC
Auto / Manual
OUT_MAN2
DIR2
AT_START
AT_STOP
OUT_MAN
Output
Branch
Tracking
TR_I
In this case, in manual mode, you do not act directly on the actuator command, but at the level of each loop controller’s output (OUT_MAN1 and OUT_MAN2).
As long as at least one loop controller is in automatic mode, output selection is made during the loop sampling period. If both loop controllers are in manual mode, selection is made on each task cycle.
Both loop controllers permanently track the OUT_MAN actual output. In automatic mode, if they are using an integral action, they take the previous OUT_MAN output value into account. This signifies that on Manual/Auto switching, the loop controller will not use its last manual value, but the last OUT_MAN actual output value.
The initial operating mode and initial setpoint type (Remote/Local) for each loop controller can be configured.
304
35012329 02 May 2007
Operating modes
Starting autotuning forces the auto selector to the direct position of the autotuned loop. At the end of autotuning, the auto selector must be reset to the required position, if it is different from the one imposed.
35012329 02 May 2007
305
Operating modes
306
35012329 02 May 2007
Process control language objects
11
At a Glance
Subject of this
Chapter
What's in this
Chapter?
This Chapter describes the various language objects associated with inputs/outputs and process control channel parameters.
This chapter contains the following sections:
Section
11.1
11.2
11.3
11.4
11.5
11.6
Topic
Language objects associated with the process control channels
Language objects associated with the process loop
Language objects associated with the 3 single loops
Language objects associated with the single loop cascade
Language objects associated with the self-selective loop
Language objects associated with the setpoint programmer
Page
307
35012329 02 May 2007
Process control language objects
11.1
Language objects associated with the process control channels
At a Glance
Subject of this
Section
What's in this
Section?
This section describes the language objects associated with the process control channels.
This section contains the following topics:
Topic
Introduction
Double word "Order of Command"
Control loops command word
Setpoint programmer command word (%MWxy.i.7)
Summary of selection and command words
Page
308
35012329 02 May 2007
Process control language objects
Introduction
At a Glance All the variables associated with a process control channel (for example: Kp,
T_FILT, ...) are in default read and/or write.
z z z z
The language object %CH is used to simplify explicit reads and writes. It is used to:
Read module and channel status words.
Write parameters.
Save parameters.
Send commands.
35012329 02 May 2007
309
Process control language objects
Sending commands
Explicit instructions are applied to the language object of the %MWxy.i.j channel.
Example 1: sending an autotune order to the first loop of a 3 single loops loop controller. This word contains the explicit command acting on the control loop.
(*autotuning command*)
(*on 1 st
loop*)
(*send command *)
%M100
%Mwxy.i.13:=16#000E
%MDxy.i.14:=1
WRITE_CMD %CH0x.i
There is no limit to the number of commands on a PLC cycle. The recognition of the instruction and the updating of the states of the process control channel concerned come into effect on the next cycle of the task.
Note: Orders associated with the operating mode of the loop controller (Auto,
Manu, Tracking, Autotuning) cannot be sent at the same time in the same cycle
(only the last instruction carried out in the cycle is recognized). In contrast, complementary orders (of the types Remote, freeze Totalizer function , etc.) can be sent in the same cycle.
Example 2: sending Manu mode to the slave loop of a cascade type channel.
! (*slave loop selection*)
%MDxy.i.12: =2;
! (*switching to manual mode*)
%MWxy.i.11: =16#0023;
! (*send command*)
IF %M100 THEN WRITE_CMD %CHx.i;
END_IF;
310
35012329 02 May 2007
Values
Process control language objects
Command parameter or selection word (%MDxy.i.j) values z z z
Setpoint programmer
%MDxy.i.8 = j profile j j ={1, ..., 6}
Cascade loop
%MDxy.i.12 = 1 master loop
%MDxy.i.12 = 2 slave loop
Auto selector loop
%MDxy.i.12 = 1 main loop
%MDxy.i.12 = 2 secondary loop
%MDxy.i.12 = 4 global loop
As the process loop has only one loop, the %MDxy.i.12 command parameter has no significance.
z 3 single loops loop controller
%MDxy.i.14 = j profile j j ={1, 2, 3}
35012329 02 May 2007
311
Process control language objects
Double word "Order of Command"
At a Glance The double word order of command , defined in the configuration of each loop, enables one or more operating mode change commands to be sent.
The required double word %MD is entered with loop parameters of the configuration screen.
The first sixteen bits of X0 to X15 are the same as those of the status word of the periodic data table. This single word is copied into the fist part of the double word order of command .
Note: if the option Reset %MWi on cold restart is checked on the processor configuration screen, the X28 bit of the order of command double word will be reset to zero during the first cycle following cold restart. It is therefore mandatory that the
X28 bit is set to 1 by the application in the processing section of the cold restart
(application operating mode management).
312
35012329 02 May 2007
Process control language objects
%MDi:X0
%MDi:X1
%MDi:X2
%MDi:X3
%MDi:X4
%MDi:X5
%MDi:X6
%MDi:X7
%MDi:X8
%MDi:X9
%MDi:X10
%MDi:X11
%MDi:X12
%MDi:X13
%MDi:X14
%MDi:X15
%MDi:X16
%MDi:X18
%MDi:X19
%MDi:X20
%MDi:X21
%MDi:X22
%MDi:X23
%MDi:X24
%MDi:X25
%MDi:X26
%MDi:X27
%MDi:X28
Description
Double word bit
%MDi:X17
This table describes each bit of the order of command double word.
Associated simple word bit
%MWi:X0
%MWi:X1
%MWi:X2
%MWi:X3
%MWi:X4
%MWi:X5
%MWi:X6
%MWi:X7
%MWi:X8
%MWi:X9
%MWi:X10
%MWi:X11
%MWi:X12
%MWi:X13
%MWi:X14
%MWi:X15
%MWi+1:X0
Description Indication
0 : Manu, 1 : Auto
Tracking
Autotuning
0 : Remote, 1 : Local
Output 1 of ON OFF or of SERVO
Output 2 of ON OFF3 or of SERVO
Output 1 of SERVO2
Output 2 of SERVO2
SP1 or SP2 selection
Auto-selector in auto-selection mode
Auto-selector in direct main loop mode
Auto-selector in direct secondary loop mode
PID1 or PID2 output selected
Reserved
Reserved
Reserved
0 : copy not used,
1 : copy used
%MWi+1:X1
%MWi+1:X2
%MWi+1:X3
%MWi+1:X4
%MWi+1:X5
%MWi+1:X6
%MWi+1:X7
%MWi+1:X8
%MWi+1:X9
0 : unfreezing of the totalization, 1: freezing of the totalization
X
Re-initialization of the totalization
Return to previous adjustments
Autotuning diagnostics acknowledgement
SERVO1 re-initialization
SERVO2 re-initialization
Save parameters
Reserved
Reserved
%MWi+1:X10 Reserved
%MWi+1:X11 Reserved
%MWi+1:X12 0 : Writing of command word prohibited,
1 : writing of command word authorized
-
-
X
-
-
-
-
-
-
-
-
-
-
X
-
X
X
X
X
X
X
X
X
X
X
X
X
X
-
X
-
-
Command
(1)
X
X
X
X
X
X
X
X
-
-
X(2)
X(2)
X
-
-
X
X(3)
X(3)
X(3)
X(3)
-
-
X(3)
X(3)
35012329 02 May 2007
313
Process control language objects
Double word bit
%MDi:X29
%MDi:X30
%MDi:X31
Associated simple word bit
Description
%MWi+1:X13 Reserved
%MWi+1:X14 Reserved
%MWi+1:X15 Reserved
Key
X : Yes
- : No
(1) : the command is only acknowledged if the X28 bit is at 1
(2) : for the function, there is no associated command, it is simply for information
(3) : the bit is automatically rest to zero
-
-
-
Indication Command
(1)
-
-
-
314
35012329 02 May 2007
Control loops command word
Process control language objects
35012329 02 May 2007
315
Process control language objects
Value of the command word
%MWxy.i.11 is the command word for process, cascade and auto selector loops.
%MWxy.i.13 is the command word for the 3 single loops loop controller.
Value
16#0001
16#0002
16#0003
16#0004
16#0005
16#0006
16#0007
16#0008
16#0009
16#000A
16#000B
16#000C
16#000D
16#000E
16#000F
16#0010
16#0011
16#0012
16#0013
16#0014
16#0015
16#0016
16#0017
16#0018
Meaning
Switches to Simulation or Non-simulation mode for the process value input
Switches to Remote or Local mode
Switches to Manual or Automatic mode
Freezes Totalizer function
Unfreezes Totalizer function
Resets Totalizer function
Selects Remote1 setpoint
Selects Remote2 setpoint
Not used
Not used
Switches to Simulation or Non-simulation for Feed Forward input
Switches to Tracking mode
Switches to Non-tracking mode
Starts autotuning
Stops autotuning
Returns to previous adjustments
Uses copy (Cannot be used after a Split Range or Heat/Cool PID)
Does not use copy (Cannot be used after a Split Range or Heat/Cool PID)
Acknowledges autotuning diagnostics
Activates RAISE
Deactivates RAISE
Activates LOWER
Deactivates LOWER
Not used
16#0020
16#0021
16#0022
16#0023
16#0024
16#0025
16#0026
Resets Servo2
Selects the setpoint in Local mode
Selects the setpoint in Remote mode
Switches to Manu
Switches to Auto
Position of selector in auto selector
Position of selector in the main loop
316
35012329 02 May 2007
Value
16#0027
Meaning
Position of selector in the secondary loop
Process control language objects
35012329 02 May 2007
317
Process control language objects
Setpoint programmer command word (%MWxy.i.7)
Value of the command word
%MWxy.i.7 is the setpoint programmer command word.
Value
16#0001
16#0002
16#0003
16#0004
16#0005
16#0006
16#0007
16#0008
16#0009
16#000A
16#000B
Meaning
Resets the setpoint programmer (action on the current profile)
Triggers the selected profile
Stops the selected profile
Freezes evolution of the profil
Unfreezes current profile
Jumps to the following segment
Jumps to the previous segment
Inhibits the guaranteed dwell time function
Activates the guaranteed dwell time function
Freezes / Unfreezes profile evolution
Freezes / Unfreezes the guaranteed dwell time function
318
35012329 02 May 2007
Process control language objects
Summary of selection and command words
Type of channel: This table reiterates the selection and command words for each type of loop.
Type of loop
Process Loop
Cascade Loop
Auto Selector Loop
3 single loops
Setpoint programmer
Command word Command parameter or Selection word
%MWxy.i.11
%MWxy.i.11
%MWxy.i.11
%MWxy.i.13
%MWxy.i.7
None
%MDxy.i.12 = j
(j = 1: master, 2: slave)
%MDxy.i.12 = j
(j = 1: main, 2: secondary, 4: global loop)
%MDxy.i.14 = j
(j = 1,2 or 3 according to loop number)
%MDxy.i.8 = j
(j = 1, 2, ... 6 according to profile number)
35012329 02 May 2007
319
Process control language objects
11.2
Language objects associated with the process loop
At a Glance
Subject of this
Section
What's in this
Section?
This section describes the different language objects associated with the process loop.
This section contains the following topics:
Topic
Configuration language objects
Error and diagnostics language objects
Process control language objects
Page
320
35012329 02 May 2007
Configuration language objects
Process control language objects
35012329 02 May 2007
321
Process control language objects
Description This table describes all the language objects associated with the process loop.
Address
%KWxy.i.0
%KWxy.i.0:X0
%KWxy.i.0:X1
%KWxy.i.0:X2
%KWxy.i.0:X3
%KWxy.i.0:X4
%KWxy.i.0:X8
%KWxy.i.0:X9
%KWxy.i.0:X10 PV_UNI_BIP
%KWxy.i.0:X11 PV_EXTERN
%KWxy.i.0:X13 TOTALISATEUR
%KWxy.i.0:X14 TOTALISATEUR
%KWxy.i.1
%KWxy.i.1:X0
%KWxy.i.1:X1
%KWxy.i.1:X2
%KWxy.i.1:X3
Parameter name
CONFIG_0
FILTRAGE
GENERATEUR DE
FONCTION
TOTALISATEUR
RACINE CARREE
ALARMES
PV_CLIP
EXTRAPOL
SANS Objet
SP_SIMPLE
SP_SELECTION
SPEED_LIMITEUR
SP_SPP
Default value
No Object
Missing (0)
Missing (0)
Missing (0)
Missing (0)
Present
Comment
Word grouping together the different Process Value configuration bits
Filtering function of the process value branch
Function generator of the process value branch
Totalizer function of the process value branch
Square root function of the process value branch
Alarm function of the process value branch
Missing (0)
No (0)
Unipolar (0)
Missing (0)
Clipping or non-clipping of the process value
Extrapolation of function generator
Type of process value: unipolar/bipolar
Choice of Standard process value (0) / External process value (1)
1
0
No Objet
(X13=0, X14 =0): phys/ms
(X13=1, X14 =0): phys/ms
(X13=0, X14 =1): phys/ms
(X13=1, X14 =1): phys/ms
Word grouping together the different setpoint configuration bits
Selected (1) Type of setpoint selected: single
Not selected (0) Type of setpoint: selection
Not selected (0) Speed limiter on the setpoint not selected (0) Type of setpoint selected: programmer
322
35012329 02 May 2007
35012329 02 May 2007
Process control language objects
Address
%KWxy.i.1:X4
%KWxy.i.1:X8
%KWxy.i.1:X9
%KWxy.i.1:X10
%KWxy.i.1:X11
%KWxy.i.1:X12
%KWxy.i.1:X13
%KWxy.i.1:X14
%KWxy.i.1:X15
%KWxy.i.2
%KWxy.i.2:X0
%KWxy.i.2:X1
%KWxy.i.2:X2
Parameter name
RL/L
SEL_MIN
SEL_MAX
SEL_SWITCH
R/L_INIT
R1/R2_INIT
SP_RATIO
SP_LIMITEUR
SP_FOLW
CONFIG_2
PID
ONOFF2
ONOFF3
%KWxy.i.2:X3 SPLRG/CHFROID
%KWxy.i.2:X4
%KWxy.i.2:X5
%KWxy.i.2:X6
%KWxy.i.2:X7
SPLIT RANGE
CHAUD/FROID
ALARMES_DEV
FEED FORWARD
Default value
Remote local (0) Speed limiter either on the local setpoint or on Remote/
Local
Missing (0)
Comment
Missing (0)
Present on selection
Local (1)
Function selected if there is a selection setpoint
Function selected if there is a selection setpoint
Function selected if there is a selection setpoint
R1 (0)
Initial value of the Remote/
Local selected setpoint
Initial value of the status of the selected setpoint
Not selected (0) Type of setpoint selected: ratio
Not present
Non tracking setpoint (0)
Setpoint limiter (e.g.:
PARAM_SP)
Tracking setpoint
No Object Word grouping together the different loop controller and
FF configuration bits
Present
Missing (0)
Missing (0)
PID function of the loop controller branch
2 state ON OFF loop controller branch
3 state ON OFF loop controller branch
No Object
Missing (0)
Not selected
Present
Missing (0)
OR for presence bits Heat/
Cool and Split Range
Loop controller branch Split
Range function
Heat/Cool function of the loop controller branch
Alarm on deviation function of the loop controller branch
Presence of a Feed forward input
323
Process control language objects
324
Address
%KWxy.i.2:X8
%KWxy.i.2:X9
%KWxy.i.2:X10
%KWxy.i.2:X11
%KWxy.i.2:X12
%KWxy.i.2:X13
%KWxy.i.2:X14
%KWxy.i.2:X15
%KWxy.i.3
%KWxy.i.3:X0
%KWxy.i.3:X1
%KWxy.i.3:X2
%KWxy.i.3:X3
%KWxy.i.3:X4
%KWxy.i.3:X5
%KWxy.i.3:X8
%KWxy.i.3:X9
Parameter name
BUMP
PWM1
PWM2
POT_REV1
POT_REV2
%KWxy.i.3:X10 POT_VAL1_INIT
%KWxy.i.3:X11 POT_VAL2_INIT
%KWxy.i.3:X12 ANALOG1_UNI_BIP Unipolar
%KWxy.i.3:X13
PV_DEV
MIX_PAR
REV_DIR
MANU/AUTO_INIT
LEAD LAG
FF_UNI_BIP
IMC
CONFIG_3
SERVO
SERVO2
ANALOGIQUE1
ANALOGIQUE2
ANALOG2_UNI_BIP
Default value
With bumps (1)
Comment
Management of bumps when changing operating mode
On process value
(0)
Type of derived action
PID parallel series
PID backward action (0)
Manu (0)
Type of loop controller mixed or parallel
Type of loop controller action
Missing (0) unipolar
Missing (0)
No Object
Selected
Selected
Selected
Initial value of loop controller operating mode
Leadlag function of the Feed forward branch
Type of Feed forward process value: unipolar / bipolar
IMC function of the loop controller branch
Word grouping together the different output configuration bits
Type of output selected:
Servo
Type of output selected:
Servo
Type of output selected:
Analog
Selected
Selected
Selected
Direct (0)
Direct (0)
No (0)
Yes (1)
Type of output selected:
Analog
Type of output selected: PWM
Type of output selected: PWM
Servo copy direction
Servo copy direction
Presence of Servo copy
Presence of (Reserved) Servo copy
Unipolar (0)
Type of analog output: unipolar / bipolar
Type of analog output: unipolar / bipolar
35012329 02 May 2007
Address
%KWxy.i.4
%KWxy.i.8
Process control language objects
Parameter name
NOM DE LA
BOUCLE
UNITE DE LA
BOUCLE
Default value Comment
Loop i with i [0;9] Loop name
Loop unit
35012329 02 May 2007
325
Process control language objects
Error and diagnostics language objects
326
35012329 02 May 2007
Description
35012329 02 May 2007
Process control language objects
This table describes the error and diagnostics language objects associated with the process loop.
Address Parameter name Default value
Comment
%MWxy.i.0
EXCH_STS
%MWxy.i.1
%MWxy.i.2
EXCH_ERR
CH_FLT
%MWxy.i.2:X4 INTERNAL_FLT
%MWxy.i.2:X5 CONF_FLT
%MWxy.i.2:X6 MISSING_ADDR
%MWxy.i.2:X7 WARN
%MWxy.i.2:X8 STS_ERR_CALC_CORR
%MWxy.i.2:X9 STS_ERR_FLOT_CORR
%MWxy.i.2:X10 STS_ERR_CALC_PV
%MWxy.i.2:X11 STS_ERR_FLOT_PV
%MWxy.i.2:X12 STS_ERR_CALC_OUT
%MWxy.i.2:X13 STS_ERR_FLOT_OUT
Exchange management status
Exchange report status
Channel standard fault
Serious internal error
Configuration error
Address of IMC register missing
Sum of errors
Loop controller branch calculation error
Loop controller branch floating point error
PV branch calculation error
PV branch floating point error
OUT branch calculation error
OUT branch floating point error
%MWxy.i.3
CH_STATUS2
%MWxy.i.3:X0 STS_ERR_SCALE_PV
%MWxy.i.3:X1 STS_ERR_TH_SPLRG
%MWxy.i.3:X2 STS_ERR_SCALE_OUT1
%MWxy.i.3:X3 STS_ERR_SCALE_OUT2
%MWxy.i.3:X4 STS_ERR_COPY_POS
%MWxy.i.4
STATUS1
%MWxy.i.4:X0 STS_HOLD_TOT
%MWxy.i.4:X1 STS_PV_SIM
%MWxy.i.4:X2 STS_PV_H_LIM
%MWxy.i.4:X3 STS_PV_L_LIM
%MWxy.i.4:X4 STS_SP_H_LIM
PV branch incorrect scale
Split Range function thresholds incorrect
OUT1 branch scale incorrect
OUT2 branch scale incorrect
Servo copy address missing
Word grouping together the different Process Value/
Setpoint status bits
Freezes Totalizer function
Simulated process value
Process value high limit
Process value low limit
Setpoint high limit
327
Process control language objects
Address
%MWxy.i.4:X8
Parameter name
%MWxy.i.4:X5 STS_SP_L_LIM
%MWxy.i.4:X6 STS_L_R
%MWxy.i.4:X7 STS_R1_R2
STS_ALARMS
%MWxy.i.4:X9 STS_HH
%MWxy.i.4:X10 STS_H
%MWxy.i.4:X11 STS_L
%MWxy.i.4:X12 STS_LL
%MWxy.i.4:X13 STS_DEVH
%MWxy.i.4:X14 STS_DEVL
%MWxy.i.4:X15 STS_THLD_DONE
%MWxy.i.5
STATUS2
%MWxy.i.5:X0 STS_AT_RUNNING
%MWxy.i.5:X1 STS_TR_S
%MWxy.i.5:X2
%MWxy.i.5:X3 STS_M_A
%MWxy.i.5:X4 STS_RAISE1
%MWxy.i.5:X5 STS_LOWER1
%MWxy.i.5:X6 STS_RAISE2
%MWxy.i.5:X7 STS_LOWER2
%MWxy.i.5:X8 STS_OUT_L_LIM
%MWxy.i.5:X9 STS_OUT_H_LIM
%MWxy.i.5:X10 STS_TOP_NEXT_CYCLE
%MWxy.i.5:X11 STS_TOP_CUR_CYCLE
Default value
Comment
R/L Init
Setpoint low limit
Remote Setpoint (0) Local
Setpoint (1)
Remote2 Setpoint (1)
Remote1 Setpoint (0)
OR logic of process value alarms
Very high alarm
High alarm
Low alarm
Very low alarm
High alarm for Process
Value/Setpoint deviation (>0)
Low alarm for Process
Value/Setpoint deviation (<0)
Totalizer threshold reached
No Object Word grouping together the different Loop controller/
Feed forward status bits
Autotuning in progress
Tracking in progress
Status of PID Operating mode
Open command
Close command
Branch output 2 open command
Branch output 2 close command
Sampling pulse on next cycle
Sampling pulse in current cycle
328
35012329 02 May 2007
35012329 02 May 2007
Address Parameter name
%MWxy.i.5:X12 STS_FF_SIM
%MWxy.i.6
STATUS3
%MWxy.i.6:X0 POT_VAL1
%MWxy.i.6:X1 POT_VAL2
%MWxy.i.6:X2 RAISE STOP1
%MWxy.i.6:X3 LOWER STOP1
%MWxy.i.6:X4 RAISE STOP2
%MWxy.i.6:X5 LOWER STOP2
%MWxy.i.7
STATUS4
%MWxy.i.7:X0 SP_MIN_WARN
%MWxy.i.7:X1 XI_WARN
%MWxy.i.7:X2 Yi_WARN
%MWxy.i.7:X6 OVER_TOT_WARN
%MWxy.i.7:X8 INP_INFR1_WARN
%MWxy.i.7:X9 INP_INFR2_WARN
%MWxy.i.7:X10 RATIO_WARN
%MWxy.i.7:X11 SP_CALC_WARN
%MWxy.i.7:X12 SP_FLOAT_WARN
%MWxy.i.7:X13 FF_CALC_WARN
Process control language objects
Default value
Comment
Status of simulation of the FF process value
No Object Word grouping together the different Servo status bits
Servo operation with copy position
Servo operation with copy position (Reserved)
Servo drive open stop reached (Reserved)
Servo drive close stop reached (Reserved)
Servo drive open stop reached (Reserved)
Servo drive close stop reached (Reserved)
No Object Word grouping together the fine diagnostics of different errors (process value, setpoint, FF)
SP_MIN and SP_MAX parameters check error
Xi parameters check error
Yi parameters check error
Totalizer overflow error
INP_INFR1 and INP_SUPR1 parameters check error
INP_INFR2 and INP_SUPR2 parameters check error
RATIO_MIN and
RATIO_MAX parameters check error
Setpoint calculation error
Setpoint floating point error
Feed forward calculation error
329
Process control language objects
330
Address
%MWxy.i.7:X14 FF_FLOAT_WARN
%MWxy.i.8
%MWxy.i.8:X0
%MWxy.i.8:X1
%MWxy.i.8:X2
Parameter name
AT_FAILED
AT_ABORTED
%MWxy.i.8:X3 AT_PWF_OR_EFB_FAILURE
%MWxy.i.8:X4
STATUS5
AT_ERR_PARAM
AT_ERR_SATUR
Default value
Comment
Feed forward floating point error
No Object Word grouping together autotuning diagnostics
Autotuning failed
Autotuning diagnostics interrupted
Autotuning Diagnostics parameter error
Autotuning Diagnostics system error or power outage
Autotuning Diagnostics saturation of process value
%MWxy.i.8:X5 AT_DV_TOO_SMALL
%MWxy.i.8:X6
%MWxy.i.8:X7
%MWxy.i.8:X8
%MWxy.i.8:X9
AT_TSAMP_HIGH
AT_INCONSIST_RESP
AT_NOT_STAB_INIT
AT_TMAX_TOO_SMALL
%MWxy.i.8:X10 AT_NOISE_TOO_HIGH
%MWxy.i.8:X11 AT_TMAX_TOO_HIGH
Autotuning Diagnostics insufficient process value deviation
Autotuning Diagnostics sampling period too long
Autotuning Diagnostics inconsistent response
Autotuning Diagnostics process value unstable initially
Autotuning Diagnostics step function duration too short
Autotuning Diagnostics process value noise too high
Autotuning Diagnostics step function duration too long
%MWxy.i.8:X12 AT_OVERSHOOT
%MWxy.i.8:X13 AT_UNDERSHOOT
%MWxy.i.8:X14 AT_UNSYMETRICAL_PT
%MWxy.i.8:X15 AT_INTEGRATING_PT
Autotuning Diagnostics overshoot above 10%
Autotuning Diagnostics nonminimum phase too large
Autotuning Diagnostics process too non-symmetrical
Autotuning Diagnostics integrating process
35012329 02 May 2007
Address
%MWxy.i.9
%MWxy.i.10
%MWxy.i.11
%MDxy.i.12
Parameter name
Reserved
Reserved
ORDER_COMMAND
PARAM_COMMAND
Process control language objects
Default value
Comment
Command order
Command parameter
35012329 02 May 2007
331
Process control language objects
Process control language objects
332
35012329 02 May 2007
Description
Process control language objects
This table describes the process control language objects associated with the process loop.
Address Parameter name
%MWxy.i.14
PV_SIM
%MWxy.i.15
FF_SIM
%MFxy.i.16
%MFxy.i.18
T_ECH
OUT1
%MFxy.i.20
%MFxy.i.22
%MFxy.i.24
%MFxy.i.26
%MFxy.i.28
%MFxy.i.30
%MFxy.i.32
%MFxy.i.34
%MFxy.i.36
%MFxy.i.38
%MFxy.i.40
%MFxy.i.42
%MFxy.i.44
%MFxy.i.46
%MFxy.i.48
%MFxy.i.50
%MFxy.i.52
%MFxy.i.54
%MFxy.i.56
%MFxy.i.58
%MFxy.i.60
%MFxy.i.62
%MFxy.i.64
%MFxy.i.66
OUT2
OUTD
OUTFF
OUT_MAN
DEV
PV
SP
PV_INF
PV_SUP
KP
TI
TD
OUTBIAS
INT_BAND
DBAND
KD
OUTRATE
OUTRATE2
OUT1_INF
OUT1_SUP
SP_MIN
SP_MAX
OUT2_INF
OUT2_SUP
0.0
0.0
100.0
0.0
100.
0.0
100.0
0.0
0.0
0.0
0.0
10.0
0.0
Default value
Comment
No Object Simulated process value
No Object Simulated Feed forward input
0,3 Sampling period
No Object Value of output 1 for Heat/Cool or Split
Range
No Object Value of output 2 for Heat/Cool or Split
Range
No Object Value of command variation
No Object Value of Feed forward action on physical scale
No Object Command value
No Object Process value setpoint deviation
No Object Value of process value on physical scale
No Object Value of setpoint on physical scale
0.0
100.0
1.0
0.0
Process value low limit
Process value high limit
Proportional co-efficient
Integral time
Derivative time
Bias on PID loop controller output
Integral band
Dead band on deviation
Filtering of the derivative
Limit of output 1 speed variation
Limit of output 2 speed variation
Output 1 low limit
Output 1 high limit
Setpoint low limit
Setpoint high limit
Output 2 low limit
Output 2 high limit
35012329 02 May 2007
333
Process control language objects
334
Address
%MFxy.i.68
%MFxy.i.70
%MFxy.i.72
%MFxy.i.74
%MFxy.i.76
%MFxy.i.78
%MFxy.i.80
%MFxy.i.82
%MFxy.i.84
%MFxy.i.86
%MFxy.i.88
%MFxy.i.90
%MFxy.i.92
%MFxy.i.94
%MFxy.i.96
%MFxy.i.98
%MFxy.i.100
%MFxy.i.102
%MFxy.i.104
%MFxy.i.106
%MFxy.i.108
%MFxy.i.122
%MFxy.i.124
Parameter name
OUT1_TH1
OUT1_TH2
OUT2_TH1
OUT2_TH2
PV_LL
PV_L
PV_H
PV_HH
RATIO
RATIO_MIN
RATIO_MAX
RATIO_BIAS
ONOFF_L
ONOFF_H
HYST
DEV_L
DEV_H
T_FILTER
K_FILTER
FILT_OUT
SQRT_OUT
%MFxy.i.110
E2_IN
%MFxy.i.112
E3_IN
%MFxy.i.114
E4_IN
%MFxy.i.116
E5_IN
%MFxy.i.118
E6_IN
%MFxy.i.120
E7_IN
E2_OUT
E3_OUT
1428.0
2857.0
4285.0
5714.0
7143.0
8571.0
14.28
28.57
Default value
0.0
Comment
50.0
50.0
100.0
5.0
5.0
95.0
95.0
1.0
0.0
100.0
0.0
5.0
5.0
Threshold 1 for output 1 for Heat/Cool or
Split Range
Threshold 2 for output 1 for Heat/Cool or
Split Range
Threshold 1 for output 2 for Heat/Cool or
Split Range
Threshold 2 for output 2 for Heat/Cool or
Split Range
Process value very low threshold
Process value low threshold
Process value high threshold
Process value very high threshold
Ratio value
Ration minimum value
Ratio maximum value
Value of Ratio bias
ON OFF loop controller low threshold
ON OFF loop controller high threshold
0.0
5.0
5.0
Hysteresis of 3 state ON OFF loop controller
Deviation low threshold
Deviation high threshold
0.0
Process value filtering time
1.0
Multiplication co-efficient on process value filtering
No Object Value of filtering output
No Object Value of square root output
Abcissae of first point of Segment S2
Abcissae of first point of Segment S3
Abcissae of first point of Segment S4
Abcissae of first point of Segment S5
Abcissae of first point of Segment S6
Abcissae of first point of Segment S7
Coordinates of first point of Segment S2
Coordinates of first point of Segment S3
35012329 02 May 2007
35012329 02 May 2007
Process control language objects
Address
%MFxy.i.126
E4_OUT
%MFxy.i.128
E5_OUT
%MFxy.i.130
%MFxy.i.132
Parameter name
E6_OUT
E7_OUT
%MFxy.i.134
THLD
%MFxy.i.136
R_RATE
Default value
42.85
57.14
71.43
85.71
1E+8
0.0
Comment
Coordinates of first point of Segment S4
Coordinates of first point of Segment S5
Coordinates of first point of Segment S6
Coordinates of first point of Segment S7
Totalizer limit
Setpoint rise speed limit
%MFxy.i.138
D_RATE 0.0
Setpoint descent speed limit
%MFxy.i.140
SPEED_LIM_OUT No Object Value of setpoint speed limiter output
%MFxy.i.142
INP_INFR1
%MFxy.i.144
INP_SUPR1
%MFxy.i.146
INP_INFR2
%MFxy.i.148
INP_SUPR2
0.0
100.0
0.0
100.0
R1 setpoint low scale
R1 setpoint high scale
R2 setpoint low scale
R2 setpoint high scale
%MFxy.i.150
T1_FF
%MFxy.i.152
T2_FF
%MFxy.i.154
OUT_FF_INF
%MFxy.i.156
OUT_FF_SUP
%MFxy.i.158
T_MOTOR1
%MFxy.i.160
%MFxy.i.162
%MFxy.i.164
T_MINI1
T_MOTOR2
T_MINI2
0.0
0.0
0.0
100.0
10.0
0.0
10.0
0.0
Feed forward process value filtering time
Feed forward process value filtering time
Feed forward action low limit
Feed forward action high limit
Opening time for valve controlled by the servo drive
Minimum opening time for valve controlled by the servo drive
Opening time for valve controlled by the servo drive
Minimum opening time for valve controlled by the servo drive
%MFxy.i.166
AT_STEP
%MFxy.i.168
AT_TMAX
%MFxy.i.170
AT_PERF
%MFxy.i.172
KP_PREV
%MFxy.i.174
%MFxy.i.176
%MFxy.i.178
%MFxy.i.180
TI_PREV
TD_PREV
KS
OL_TIME
10.0
100.0
0.5
Autotuning step function amplitude
Autotuning step function duration
Autotuning stability criterion
No Object Value before proportional co-efficient autotuning
No Object Value before integral co-efficient autotuning
No Object Value before derived co-efficient autotuning
1.0
1.0
IMC static gain
Time constant in BO
335
Process control language objects
Address
%MFxy.i.182
%MFxy.i.184
Parameter name
T_DELAY
CL_PERF
%MFxy.i.186
Reserved
%MFxy.i.188
Reserved
%MFxy.i.190
Reserved
%MFxy.i.192
Reserved
Default value
0.0
1.0
Comment
Current pure delay time
Time ratio OL / CL
336
35012329 02 May 2007
11.3
Process control language objects
Language objects associated with the 3 single loops
At a Glance
Subject of this
Section
What's in this
Section?
This section describes the language objects of the 3 single loops.
This section contains the following topics:
Topic
Configuration language objects
Default and diagnostics language objects
Process control language objects
Page
35012329 02 May 2007
337
Process control language objects
Configuration language objects
338
35012329 02 May 2007
Description
35012329 02 May 2007
Process control language objects
This table describes the process control language objects associated with the 3 single loops.
Address
%KWxy.i.0
%KWxy.i.0:X0
%KWxy.i.0:X1
%KWxy.i.0:X2
%KWxy.i.0:X3
%KWxy.i.0:X4
%KWxy.i.0:X8
%KWxy.i.0:X9
%KWxy.i.0:X10
%KWxy.i.0:X11
%KWxy.i.0:X12
%KWxy.i.0:X13
%KWxy.i.0:X14
%KWxy.i.1
%KWxy.i.1:X0
%KWxy.i.1:X1
%KWxy.i.1:X2
%KWxy.i.1:X3
Parameter name
CONFIG_0_B1
FILTRAGE
GENERATEUR DE
FONCTION
TOTALISATEUR
RACINE CARRÉE
ALARMES
PV_CLIP
EXTRAPOL
PV_UNI_BIP
Default value Comment
No Object Word bringing together the different configuration bits of the process value
Not configurable
(0)
Filtering function of the process value branch
Not configurable
(0)
Function generator of the process value branch
Missing (0)
Square Root
Totalizer function of the process value branch
Root function of the process value branch
Present
Missing (0)
Not configurable(0)
Unipolar (0)
Alarm function of the process value branch
Clipping or non-clipping of the process value
Extrapolation of function generator
Type of process value: unipolar/bipolar
PV_EXTERN
VALID_C1
TOTALISATEUR:
UNITE MESURE
TOTALISATEUR:
UNITE MESURE
CONFIG_1_B1
SP_SIMPLE
Missing (0)
Enabled (1)
1
0
No Object
Selected (1)
Choice of Standard process value (0) / External process value (1)
Loop used (1) / not used (0)
(X13=0, X14 =0): phys/ms
(X13=1, X14 =0): phys/s
(X13=0, X14 =1): phys/mn
(X13=1, X14 =1): phys/ms
Word grouping the different setpoint configuration bits
Type of setpoint selected: single
SP_SELECTION Not configurable
(0)
Type of setpoint selected: selection
SPEED_LIMITEUR Not selected (0) Speed limiter on the setpoint
SP_SPP Not selected (0) Type of setpoint selected:
Programmer
339
Process control language objects
340
Address
%KWxy.i.1:X4
%KWxy.i.1:X8
%KWxy.i.1:X9
%KWxy.i.1:X10
%KWxy.i.1:X11
%KWxy.i.1:X12
%KWxy.i.1:X13
%KWxy.i.1:X14
%KWxy.i.1:X15
%KWxy.i.2
%KWxy.i.2:X0
%KWxy.i.2:X1
%KWxy.i.2:X2
%KWxy.i.2:X3
%KWxy.i.2:X4
%KWxy.i.2:X5
%KWxy.i.2:X6
%KWxy.i.2:X7
%KWxy.i.2:X8
Parameter name
RL/L
SEL_MIN
SEL_MAX
SEL_SWITCH
R/L_INIT
R1/R2_INIT
SP_RATIO
SP_LIMITEUR
SP_FOLW
CONFIG_2_B1
PID
ONOFF2
ONOFF3
SPLRG/CHFROID
SPLIT/RANGE
CHAUD/FROID
ALARMES_DEV
FEED FORWARD
BUMP
Default value Comment
Remote local (0) Speed limiter either on the local setpoint or on Remote/
Local
Not configurable
(0)
Function selected if there is a selection setpoint
Not configurable
(0)
Function selected if there is a selection setpoint
Not configurable
(0)
Function selected if there is a selection setpoint
Local (1) Initial value of the Remote/
Local selected setpoint
Not configurable Initial value of the status of the selected setpoint
Not configurable
(0)
Type of setpoint selected:
Ratio not selected (0) Setpoint limiter (e.g.
PARAM_SP)
No tracking
No Object
Tracking (0)
Word bringing together the different configuration bits of the loop controller and FF
Present
Missing (0)
PID function of the loop controller branch
ON OFF 2 states branch of loop controller
Missing (0) ON OFF 3 states branch of loop controller
Not configurable
(0)
OR Heat/Cool and Split Range presence bits
Not configurable
(0)
Loop controller branch Split
Range function
Not configurable
(0)
Loop controller branch Heat/
Cool function
Present Alarm function on deviation of the loop controller branch
Not configurable
(0)
Presence of a Feed forward input
With bumps (1) Management of bumps when changing operating mode
35012329 02 May 2007
35012329 02 May 2007
Process control language objects
Address
%KWxy.i.2:X9
%KWxy.i.2:X10
%KWxy.i.2:X11
%KWxy.i.2:X12
%KWxy.i.2:X13
%KWxy.i.2:X14
%KWxy.i.2:X15
%KWxy.i.3
%KWxy.i.3:X0
%KWxy.i.3:X1
%KWxy.i.3:X2
%KWxy.i.3:X3
%KWxy.i.3:X4
%KWxy.i.3:X5
%KWxy.i.3:X8
%KWxy.i.3:X9
%KWxy.i.3:X10
%KWxy.i.3:X11
%KWxy.i.3:X12
%KWxy.i.3:X13
Parameter name
PV_DEV
MIX_PAR
REV_DIR
MANU/AUTO_INIT
LEAD LAG
FF_UNI_BIP
IMC
CONFIG_3_B1
SERVO
SERVO2
ANALOGIQUE1
Default value Comment
On process value (0)
Type of derivative action
PID parallel series
Mixed or parallel loop controller type
Type of loop controller action PID reverse action (0)
Manu (0) Initial value of loop controller operating mode
Not configurable
(0)
Leadlag function of the Feed forward branch
Not configurable
(0)
Type of Feed forward process value: unipolar/bipolar
Missing (0)
No Object
Not selected
IMC function of the loop controller branch
Word grouping together the different output configuration bits
Type of output selected: Servo
Not configurable
(0)
Type of output selected: Servo
Selected Type of output selected:
Analog
ANALOGIQUE2
PWM1
PWM2
POT_REV1
Not configurable
(0)
Type of output selected:
Analog
Not selected Type of output selected: PWM
Not configurable
(0)
Type of output selected: PWM
Direct (0) Servo copy direction
POT_REV2 Not configurable
(0)
Servo copy direction
No (0) Presence of Servo copy POT_VAL1_INIT
POT_VAL2_INIT Not configurable
(0)
Presence of (Reserved) Servo copy
ANALOG1_UNI_BIP Unipolar Type of analog output: unipolar/bipolar
ANALOG2_UNI_BIP Not configurable
(0)
Type of analog output: unipolar/bipolar
341
Process control language objects
%KWxy.i.15
%KWxy.i.19
%KWxy.i.22
%KWxy.i.23
%KWxy.i.24
%KWxy.i.25
%KWxy.i.26
%KWxy.i.30
Address
%KWxy.i.4
%KWxy.i.8
%KWxy.i.11
%KWxy.i.12
%KWxy.i.13
%KWxy.i.14
Parameter name
NOM DE LA
BOUCLE
UNITE DE LA
BOUCLE
IDEM BOUCLE 1
%KW0
IDEM BOUCLE 1
%KW1
IDEM BOUCLE 1
%KW2
IDEM BOUCLE 1
%KW3
IDEM BOUCLE 1
%KW4
IDEM BOUCLE 1
%KW8
IDEM BOUCLE 1
%KW0
IDEM BOUCLE 1
%KW1
IDEM BOUCLE 1
%KW2
IDEM BOUCLE 1
%KW3
IDEM BOUCLE 1
%KW4
IDEM BOUCLE 1
%KW8
Default value Comment
Loop i with i [0;9] Loop name
Loop unit
Loop 2 process value. Unused functions have their bit at 0
Loop 2 setpoint
Loop 2 loop controller and FF
Loop 2 output
Loop i with i [0;9] Loop name
Loop unit
Loop 3 process value. Unused functions have their bit at 0
Loop 3 setpoint
Loop 3 loop controller and FF
Loop 3 output
Loop i with i [0;9] Loop name
Loop unit
342
35012329 02 May 2007
Default and diagnostics language objects
Process control language objects
35012329 02 May 2007
343
Process control language objects
Description This table describes the diagnostics and default language objects associated with the 3 single loops.
Address Parameter name
%MWxy.i.0
%MWxy.i.1
%MWxy.i.2
%MWxy.i.2:X4
%MWxy.i.2:X5
%MWxy.i.2:X6
%MWxy.i.2:X7
%MWxy.i.2:X8
%MWxy.i.2:X9
EXCH_STS
EXCH_ERR
INTERNAL_FLT_B1
CONF_FLT_B1
MISSING_ADDR_B1
WARN
STS_ERR_CALC_COR_B1
STS_ERR_FLOT_COR_B1
STS_ERR_CALC_PV_B1
%MWxy.i.2:X10 STS_ERR_FLOT_PV_B1
%MWxy.i.2:X11 STS_ERR_CALC_OUT_B1
%MWxy.i.2:X12 STS_ERR_FLOT_OUT_B1
%MWxy.i.2:X13 STS_ERR_SCALE_OUT1_B1
%MWxy.i.2:X14 STS_ERR_SCALE_PV_B1
%MWxy.i.2:X15 CH_FLT_B2
%MWxy.i.3
%MWxy.i.3:X4
INTERNAL_FLT_B2
CONF_FLT_B2
Default value
Comment
Exchange management status
Exchange report status
Standard channel fault on loop 1
Serious internal fault on loop 1
Configuration fault on loop
1
IMC register address missing on loop 1 or Servo copy address missing
Sum of errors
Loop controller branch calculation error on loop 1
Loop controller branch floating point error on loop
1
PV branch calculation error on loop 1
PV branch floating point error on loop 1
OUT branch calculation error on loop 1
OUT branch floating point error on loop 1
OUT1 branch incorrect scale on loop 1
PV branch incorrect scale on loop 1
No Object Standard channel fault on loop 2
Serious internal fault on loop 2
344
35012329 02 May 2007
35012329 02 May 2007
Process control language objects
Address
%MWxy.i.3:X5
%MWxy.i.3:X6
%MWxy.i.3:X8
%MWxy.i.3:X9
%MWxy.i.3:X10
%MWxy.i.3:X11
%MWxy.i.3:X12
Parameter name
MISSING_ADDR_B2
Exchange in progress
STS_ERR_CALC_COR_B2
STS_ERR_FLOT_COR_B2
STS_ERR_CALC_PV_B2
STS_ERR_FLOT_PV_B2
STS_ERR_CALC_OUT_B2
%MWxy.i.3:X13 STS_ERR_FLOT_OUT_B2
%MWxy.i.3:X14 STS_ERR_SCALE_OUT1_B2
%MWxy.i.3:X15
%MWxy.i.4
%MWxy.i.4:X4
%MWxy.i.4:X5
%MWxy.i.4:X8
%MWxy.i.4:X9
%MWxy.i.4:X10
%MWxy.i.4:X11
STS_ERR_SCALE_PV_B2
CH_FLT_B3
INTERNAL_FLT_B3
CONF_FLT_B3
STS_ERR_CALC_COR_B3
STS_ERR_FLOT_COR_B3
STS_ERR_CALC_PV_B3
STS_ERR_FLOT_PV_B3
Default value
Comment
Configuration fault on loop
2
IMC register address missing on loop 2 or Servo copy address missing
Loop controller branch calculation error on loop 2
Loop controller branch floating point error on loop
2
PV branch calculation error on loop 2
PV branch floating point error on loop 2
OUT branch calculation error on loop 2
OUT branch floating point error on loop 2
OUT1 branch incorrect scale on loop 2
PV branch incorrect scale on loop 2
Standard channel fault on loop 3
Serious internal fault on loop 3
Configuration fault on loop
3
Loop controller branch calculation error on loop 3
Loop controller branch floating point error on loop
3
PV branch calculation error on loop 3
PV branch floating point error on loop 3
345
Process control language objects
Address
%MWxy.i.4:X12
%MWxy.i.4:X13
Parameter name
STS_ERR_CALC_OUT_B3
STS_ERR_FLOT_OUT_B3
%MWxy.i.4:X14 STS_ERR_SCALE_OUT1_B3
%MWxy.i.4:X15
%MWxy.i.5
%MWxy.i.5:X0
%MWxy.i.5:X1
%MWxy.i.5:X2
%MWxy.i.5:X3
%MWxy.i.5:X4
%MWxy.i.5:X5
%MWxy.i.5:X6
%MWxy.i.5:X7
%MWxy.i.5:X8
%MWxy.i.5:X9
%MWxy.i.5:X14
STS_ERR_SCALE_PV_B3
STATUS1_B1
HOLD_TOT_B1
PV _SIM_B1
STS_PV_H_LIM_B1
STS_PV_L_LIM_B1
STS_SP_H_LIM_B1
STS_SP_B_LIM_B1
STS_L_R
STS_TR_S_B1
STS_ALARMS_B1
STS_HH_B1
%MWxy.i.5:X10 STS_H_B1
%MWxy.i.5:X11 STS_L_B1
%MWxy.i.5:X12 STS_LL_B1
%MWxy.i.5:X13 STS_DEV_H_B1
STS_DEV_L_B1
Default value
Comment
OUT branch calculation error on loop 3
OUT branch floating point error on loop 3
OUT1 branch incorrect scale on loop 3
PV branch incorrect scale
No Object Word grouping the different Process value/
Setpoint status bits
Totalizer function state
Process value simulation state
High limit on process value branch (PV_SUP)
Low limit on process value branch (PV_INF)
High limit on setpoint branch
Low limit on setpoint branch
R/L Init State of the Remote/Local selected setpoint
Tracking status bit
Sum of process value alarms
Very high alarm
High alarm
Low alarm
Very low alarm
High threshold for Process value/Setpoint deviation
(>0)
Low threshold for Process value/Setpoint deviation
(<0)
346
35012329 02 May 2007
35012329 02 May 2007
Process control language objects
Address
%MWxy.i.6:X0
%MWxy.i.6:X1
%MWxy.i.6:X2
%MWxy.i.6:X3
%MWxy.i.6:X4
%MWxy.i.6:X5
Parameter name
%MWxy.i.5:X15 STS_THLD_DONE_B1
%MWxy.i.6
STATUS2_B1
STS_AT_RUNNING_B1
STS_M_A_B1
STS_RAISE1_B1
STS_LOWER1_B1
STS_OUT_L_LIM_B1
STS_OUT_H_LIM_B1
%MWxy.i.6:X6
%MWxy.i.6:X7
POT_VAL_B1
RAISE_STOP_B1
%MWxy.i.6:X8 LOWER_STOP_B1
%MWxy.i.6:X9 STS_TOP_NEXT_CYC_B1
%MWxy.i.6:X10 STS_TOP_CUR_CYC_B1
%MWxy.i.6:X11 OVER_TOT_WARN_B1
%MWxy.i.6:X12
%MWxy.i.6:X13
%MWxy.i.6:X14
%MWxy.i.6:X15
INP_INF_WARN_B1
SP_MIN_WARN_B1
SP_CALC_WARN_B1
SP_FLOAT_WARN_B1
Default value
Comment
Totalizer threshold reached
No Object Word grouping the different Loop controller/ output status bits
Autotuning in progress
(common to 3 loops)
PID operating mode state
Open command
Close command
The calculated output of the PID is greater than or equal to OUT_SUP
The calculated output of the PID is smaller than or equal to OUT_INF
Servo with copy operation
Open limit reached on
Servo drive (Reserved)
Close limit reached on
Servo drive (Reserved)
Sampling pulse on next cycle
Sampling pulse in current cycle
Totalizer overflow error
(T_MOTOR1_WARN suppressed)
INP_INF and INP_SUP loop 1 parameter check error
SP_MIN and SP_MAX loop 1 parameter check error
Setpoint calculation error
Setpoint floating point error
347
Process control language objects
Address
%MWxy.i.7
Parameter name
STATUS1_B2
%MWxy.i.7:X0
%MWxy.i.7:X1
HOLD_TOT_B2
PV _SIM_B2
%MWxy.i.7:X2 STS_PV_H_LIM_B2
%MWxy.i.7:X3 STS_PV_L_LIM_B2
%MWxy.i.7:X4 STS_SP_H_LIM_B2
%MWxy.i.7:X5 STS_SP_B_LIM_B2
%MWxy.i.7:X6 STS_L_R_B2
%MWxy.i.7:X7
%MWxy.i.7:X8
STS_TR_S_B2
STS_ALARMS_B2
%MWxy.i.7:X9 STS_HH_B2
%MWxy.i.7:X10 STS_H_B2
%MWxy.i.7:X11 STS_L_B2
%MWxy.i.7:X12 STS_LL_B2
%MWxy.i.7:X13 STS_DEV_H_B2
%MWxy.i.7:X14 STS_DEV_L_B2
%MWxy.i.7:X15 STS_THLD_DONE_B2
%MWxy.i.8
STATUS2_B2
%MWxy.i.8:X0 STS_AT_RUNNING_B2
%MWxy.i.8:X1 STS_M_A_B2
348
Default value
Comment
No Object Word grouping the different Process value/
Setpoint status bits
Totalizer function state
Process value simulation state
High limit on process value branch (PV_SUP)
Low limit on process value branch (PV_INF)
High limit on setpoint branch
R/L Init
Low limit on setpoint branch
State of the Remote/Local selected setpoint
Tracking status bit
Sum of process value alarms
Very high alarm
High alarm
Low alarm
Very low alarm
High threshold for Process value/Setpoint deviation
(>0)
Low threshold for Process value/Setpoint deviation
(<0)
Totalizer threshold reached
No Object Word grouping the different loop controller/ output status bits
Autotuning in progress
(common to 3 loops)
PID operation state
35012329 02 May 2007
35012329 02 May 2007
Process control language objects
Address
%MWxy.i.8:X2
%MWxy.i.8:X3
%MWxy.i.8:X4
%MWxy.i.8:X5
%MWxy.i.8:X6
%MWxy.i.8:X7
%MWxy.i.8:X8
%MWxy.i.8:X9
STS_RAISE1_B2
STS_LOWER1_B2
STS_OUT_L_LIM_B2
STS_OUT_H_LIM_B2
LOWER STOP_B2
STS_TOP_NEXT_CYC_B2
%MWxy.i.8:X10 STS_TOP_CUR_CYCLE_B2
%MWxy.i.8:X11 OVER_TOT_WARN_B2
%MWxy.i.8:X12
%MWxy.i.8:X13
%MWxy.i.8:X14
%MWxy.i.8:X15
%MWxy.i.9
%MWxy.i.9:X0
%MWxy.i.9:X1
%MWxy.i.9:X2
Parameter name
POT_VAL_B2
RAISE STOP_B2
INP_INF_WARN_B2
SP_MIN_WARN_B2
SP_CALC_WARN_B2
SP_FLOAT_WARN_B2
STATUS1_B3
STS_HOLD_TOT_B3
STS_PV _SIM_B3
STS_PV_H_LIM_B3
Default value
Comment
Open command
Close command
The calculated output of the PID is greater than or equal to OUT_SUP
The calculated output of the PID is smaller than or equal to OUT_INF
Servo with copy operation
Open limit reached on servo drive (reserved)
Close limit reached on servo drive (Reserved)
Sampling pulse on next cycle
Sampling pulse in current cycle
Totalizer overflow error
(T_MOTOR1_WARN suppressed)
INP_INF and INP_SUP loop 2 parameter check error
SP_MIN and SP_MAX loop 2 parameter check error
Setpoint calculation error
Setpoint floating point error
Word grouping the different loop 3 Process value/Setpoint status bits
Totalizer function state
Process value simulation state
High limit on process value branch (PV_SUP)
349
Process control language objects
Address Parameter name
%MWxy.i.9:X3 STS_PV_L_LIM_B3
%MWxy.i.9:X4 STS_SP_H_LIM_B3
%MWxy.i.9:X5 STS_SP_B_LIM_B3
%MWxy.i.9:X6
%MWxy.i.9:X7
%MWxy.i.9:X8
STS_L_R_B3
STS_TR_S_B3
STS_ALARMS_B3
%MWxy.i.9:X9 STS_HH_B3
%MWxy.i.9:X10 STS_H_B3
%MWxy.i.9:X11 STS_L_B3
%MWxy.i.9:X12 STS_LL_B3
%MWxy.i.9:X13 STS_DEV_H_B3
%MWxy.i.9:X14 STS_DEV_L_B3
%MWxy.i.9:X15 STS_THLD_DONE_B3
%MWxy.i.10
STATUS2_B3
%MWxy.i.10:X0 STS_AT_RUNNING_B3
%MWxy.i.1:X1 STS_M_A_B3
%MWxy.i.10:X2 STS_RAISE1_B3
%MWxy.i.10:X3 STS_LOWER1_B3
%MWxy.i.10:X4 STS_OUT_L_LIM_B3
%MWxy.i.10:X5 STS_OUT_H_LIM_B3
%MWxy.i.10:X6 POT_VAL_B3
350
Default value
Comment
R/L Init
Low limit on process value branch (PV_INF)
High limit on setpoint branch
Low limit on setpoint branch
Setpoint state
Tracking status bit
Sum of process value alarms
Very high alarm
High alarm
Low alarm
Very low alarm
High threshold for Process value/Setpoint deviation
(>0)
Low threshold for Process value/Setpoint deviation
(<0)
Totalizer threshold reached
No Object Word grouping the different Process value/
Setpoint status bits
Autotuning in progress
(common to 3 loops)
PID operation state
Open command
Close command
The calculated output of the PID is greater than or equal to OUT_SUP
The calculated output of the PID is smaller than or equal to OUT_INF
Servo with copy operation
35012329 02 May 2007
35012329 02 May 2007
Process control language objects
Address
%MWxy.i.10:X7
%MWxy.i.10:X8
%MWxy.i.10:X9
%MWxy.i.10:X10 STS_TOP_CUR_CYC_B3
%MWxy.i.10:X11 OVER_TOT_WARN_B3
%MWxy.i.10:X12 INP_INF_WARN_B3
%MWxy.i.10:X13 SP_MIN_WARN_B3
%MWxy.i.10:X14 SP_CALC_WARN_B3
%MWxy.i.10:X15 SP_FLOAT_WARN_B3
%MWxy.i.11
%MWxy.i.11:X0
%MWxy.i.11:X1
%MWxy.i.11:X2
Parameter name
RAISE_STOP_B3
LOWER_STOP_B3
STS_TOP_NEXT_CYC_B3
STATUS4
AT_FAILED
AT_ABORTED
AT_ERR_PARAM
%MWxy.i.11:X3 AT_PWF_OR_EFB_FAILURE
%MWxy.i.11:X4
%MWxy.i.11:X5
AT_SATUR
AT_DV_TOO_SMALL
Default value
Comment
Open limit reached on servo drive (reserved)
Close limit reached on servo drive (Reserved)
Sampling pulse on next cycle
Sampling pulse in current cycle
Totalizer overflow error
(T_MOTOR1_WARN suppressed)
INP_INF and INP_SUP loop 3 parameter check error
SP_MIN and SP_SUP loop 3 parameter check error
Setpoint calculation error
Setpoint floating point error
No Object Word grouping end of different errors diagnostics
Autotuning failed
Autotuning diagnostics interrupted
Autotuning diagnostics parameter error
Autotuning diagnostics system error or power failure
Autotuning diagnostics process value saturation
Autotuning diagnostics insufficient process value deviation
351
Process control language objects
Address Parameter name
%MWxy.i.11:X6 AT_TSAMP_HIGH
%MWxy.i.11:X7
%MWxy.i.11:X8
%MWxy.i.11:X9
AT_INCONSIST_RESP
AT_NOT_STAB_INIT
AT_TMAX_TOO_SMALL
%MWxy.i.11:X10 AT_NOISE_TOO_HIGH
%MWxy.i.11:X11 AT_TMAX_TOO_HIGH
%MWxy.i.11:X12 AT_OVERSHOOT
%MWxy.i.11:X13 AT_UNDERSHOOT
%MWxy.i.11:X14 AT_UNSYMETRICAL_PT
%MWxy.i.11:X15 AT_INTEGRATING_PLANT
Default value
Comment
Autotuning Diagnostics sampling pulse period too long
Autotuning diagnostics inconsistent response
Autotuning diagnostics: initially unstable process value
Autotuning diagnostics scale period too small
Autotuning diagnostics process value noise too high
Autotuning diagnostics scale period too long
Autotuning diagnostics overshoot above 10%
Autotuning diagnostics non-minimum phase undershoot
Autotuning diagnostics procedure too nonsymmetrical
Autotuning diagnostics integrating process
%MWxy.i.12
%MWxy.i.13
%MDxy.i.14
Reserved
ORDER_COMMAND
PARAM_COMMAND
Command order
Command parameter
352
35012329 02 May 2007
Process control language objects
Process control language objects
35012329 02 May 2007
353
Process control language objects
Description
354
This table describes the different process control language objects associated with the 3 single loops.
Address Parameter name Comment
%MFxy.i.16
%MFxy.i.18
%MFxy.i.20
%MFxy.i.22
%MFxy.i.24
%MFxy.i.26
%MFxy.i.28
%MFxy.i.30
%MFxy.i.32
%MFxy.i.34
%MFxy.i.36
%MFxy.i.38
%MFxy.i.40
%MFxy.i.42
%MFxy.i.44
%MFxy.i.46
%MFxy.i.48
%MFxy.i.50
%MFxy.i.52
%MFxy.i.54
%MFxy.i.56
%MFxy.i.58
%MFxy.i.60
%MFxy.i.62
%MFxy.i.64
%MFxy.i.66
%MFxy.i.68
%MFxy.i.70
AT_STEP
AT_TMAX
AT_PERF
T_ECH_B1
OUT_MAN_B1
DEV_B1
PV_B1
SP_B1
PV_INF_B1
PV_SUP_B1
KP_B1
TI_B1
TD_B1
OUTBIAS_B1
INT_BAND_B1
DBAND_B1
OUTRATE_B1
OUT1_INF_B1
OUT1_SUP_B1
SP_INF_B1
SP_SUP_B1
PV_LL_B1
PV_L_B1
PV_H_B1
PV_HH_B1
ONOFF_L_B1
ONOFF_H_B1
HYST_B1
Default value
10.0
100.0
0.5
0.3
No Object
No Object
No Object
0.0
100.0
0.0
100.
5.0
5.0
95.0
95.0
0.0
0.0
0.0
0.0
No Object
0.0
100.0
1.0
0.0
0.0
-5.0
5.0
0.0
Autotuning step function amplitude
Autotuning step function duration
Criteria for autotuning Stability
Sampling period
Command value
Process value setpoint deviation
Process control value on physical scale
Value of setpoint on physical scale
Low process control limit
High process control limit
Proportional coefficient
Integral time
Derivative time
Bias on PID loop controller output
Integral band
Dead band on deviation
Limit of output variation speed
Low limit of Output 1
High limit of Output 1
Low setpoint limit
High setpoint limit
Very low process control threshold
Low process control threshold
High process control threshold
Very high process control threshold
Low threshold of ON OFF Loop
Controller
High threshold of ON OFF Loop
Controller
Hysteresis of 3 state ON OFF Loop
Controller
35012329 02 May 2007
35012329 02 May 2007
Process control language objects
Address
%MFxy.i.72
%MFxy.i.74
%MFxy.i.76
%MFxy.i.78
%MFxy.i.80
%MFxy.i.82
%MFxy.i.84
%MFxy.i.86
%MFxy.i.88
%MFxy.i.90
%MFxy.i.92
%MFxy.i.94
%MFxy.i.96
%MFxy.i.98
%MFxy.i.100
%MFxy.i.102
%MFxy.i.104
%MFxy.i.106
%MFxy.i.108
%MFxy.i.110
%MFxy.i.112
%MFxy.i.114
%MFxy.i.116
%MFxy.i.118
%MFxy.i.120
%MFxy.i.122
%MFxy.i.124
%MFxy.i.126
%MFxy.i.128
Parameter name
DEV_L_B1
DEV_H_B1
THLD_B1
R_RATE_B1
Default value
-5.0
5.0
1E+8
0.0
D_RATE_B1 0.0
SPEED_LIM_OUT_B1 No Object
INP_MINR_B1
INP_MAXR_B1
T_MOTOR_B1
0.0
100.0
0.0
Comment
T_MINI_B1
KP_PREV_B1
TI_PREV_B1
TD_PREV_B1
T_ECH_B2
OUT_MAN_B2
DEV_B2
PV_B2
SP_B2
PV_INF_B2
PV_SUP_B2
KP_B2
TI_B2
TD_B2
OUTBIAS_B2
INT_BAND_B2
DBAND_B2
OUTRATE_B2
OUT1_INF_B2
OUT1_SUP_B2
0.0
No Object
No Object
No Object
0.3
No Object
No Object
No Object
No Object
0.0
100.0
1.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
100.0
Low deviation threshold
High deviation threshold
Totalizing limit
Speed limiter ascent speed value
Speed limiter descent speed value
Speed limiter output value
Remote setpoint loop 1 low scale
Remote setpoint loop 1 high scale
Open time for valve controlled by the servo drive
Minimum open time for valve controlled by the servo drive
Value before proportional coefficient autotuning
Value before integral coefficient autotuning
Value before derivative coefficient autotuning
Sampling period
Command value
Process value setpoint deviation
Value of process control on physical scale
Value of setpoint on physical scale
Low process control limit
High process control limit
Proportional coefficient
Integral time
Derivative time
Bias on PID loop controller output
Integral band
Dead band on deviation
Limit of output variation speed
Low limit of Output 1
High limit of Output 1
355
Process control language objects
356
Address
%MFxy.i.130
%MFxy.i.132
%MFxy.i.134
%MFxy.i.136
%MFxy.i.138
%MFxy.i.140
%MFxy.i.142
%MFxy.i.144
%MFxy.i.146
%MFxy.i.148
%MFxy.i.150
%MFxy.i.152
%MFxy.i.154
%MFxy.i.156
%MFxy.i.158
%MFxy.i.160
%MFxy.i.162
%MFxy.i.164
%MFxy.i.166
%MFxy.i.168
%MFxy.i.170
%MFxy.i.172
%MFxy.i.174
%MFxy.i.176
%MFxy.i.178
%MFxy.i.180
Parameter name
SP_INF_B2
SP_SUP_B2
PV_LL_B2
PV_L_B2
PV_H_B2
PV_HH_B2
ONOFF_L_B2
ONOFF_H_B2
HYST_B2
T_MINI_B2
KP_PREV_B2
TI_PREV_B2
TD_PREV_B2
T_ECH_B3
OUT_MAN_B3
DEV_B3
PV_B3
Default value
0.0
100.0
5.0
5.0
95.0
95.0
-5.0
5.0
0.0
DEV_L_B2
DEV_H_B2
THLD_B2
R_RATE_B2
D_RATE_B2
-5.0
5.0
1E+8
0.0
0.0
SPEED_LIM_OUT_B2 No Object
INP_MINR_B2 0.0
INP_MAXR_B2 100.0
T_MOTOR_B2 0.0
0.0
No Object
No Object
No Object
0.3
No Object
No Object
No Object
Comment
Low setpoint limit
High setpoint limit
Very low process control threshold
Low process control threshold
High process control threshold
Very high process control threshold
Low threshold of ON OFF Loop
Controller
High threshold of ON OFF Loop
Controller
Hysteresis of 3 state ON OFF Loop
Controller
Low deviation threshold
High deviation threshold
Totalizing limit
Speed limiter ascent speed value
Speed limiter descent speed value
Speed limiter output value
Remote setpoint loop 2 low scale
Remote setpoint loop 2 high scale
Open time for valve controlled by the servo drive
Minimum open time for valve controlled by the servo drive
Value before proportional coefficient autotuning
Value before integral coefficient autotuning
Value before derivative coefficient autotuning
Sampling period
Command value
Setpoint process control deviation
Value of process control on physical scale
35012329 02 May 2007
35012329 02 May 2007
Process control language objects
Address
%MFxy.i.182
%MFxy.i.184
%MFxy.i.186
%MFxy.i.188
%MFxy.i.190
%MFxy.i.192
%MFxy.i.194
%MFxy.i.196
%MFxy.i.198
%MFxy.i.200
%MFxy.i.202
%MFxy.i.204
%MFxy.i.206
%MFxy.i.208
%MFxy.i.210
%MFxy.i.212
%MFxy.i.214
%MFxy.i.216
%MFxy.i.218
%MFxy.i.220
%MFxy.i.222
%MFxy.i.224
%MFxy.i.226
%MFxy.i.228
%MFxy.i.230
%MFxy.i.232
%MFxy.i.234
%MFxy.i.236
%MFxy.i.238
%MFxy.i.240
SP_B3
PV_INF_B3
PV_SUP_B3
KP_B3
TI_B3
TD_B3
OUTBIAS_B3
INT_BAND_B3
DBAND_B3
OUTRATE_B3
OUT_INF_B3
OUT_SUP_B3
SP_INF_B3
SP_SUP_B3
PV_LL_B3
PV_L_B3
PV_H_B3
PV_HH_B3
ONOFF_L_B3
Parameter name
ONOFF_H_B3
HYST1_B3
DEV_L_B3
DEV_H_B3
THLD_B3
R_RATE_B3
-5.0
5.0
1E+8
0.0
D_RATE_B3 0.0
SPEED_LIM_OUT_B3 No Object
INP_MINR_B3
INP_MAXR_B3
T_MOTOR_B3
0.0
100.0
0.0
0.0
0.0
0.0
0.0
0.0
100.0
0.0
100.0
Default value
No Object
0.0
100.0
1.0
0.0
0.0
5.0
5.0
95.0
95.0
-5.0
Comment
5.0
0.0
Value of setpoint on physical scale
Low process value limit
High process value limit
Proportional coefficient
Integral time
Derivative time
Bias on PID loop controller output
Integral band
Dead band on deviation
Limit of output variation speed
Low limit of output 1
High limit of output 1
Low setpoint limit
High setpoint limit
Very low measurement threshold
Low measurement threshold
High measurement threshold
Very high measurement threshold
Low threshold of ON OFF Loop
Controller
High threshold of ON OFF Loop
Controller
Hysteresis of 3 state ON OFF Loop
Controller
Low deviation threshold
High deviation threshold
Totalizing limit
Speed limiter ascent speed value
Speed limiter descent speed value
Speed limiter output value
Remote setpoint loop 3 low scale
Remote setpoint loop 3 high scale
Open time for valve controlled by the servo drive
357
Process control language objects
Address
%MFxy.i.242
%MFxy.i.244
%MFxy.i.246
Parameter name
T_MINI1_B3
KP_PREV_B3
TI_PREV_B3
%MFxy.i.248
TD_PREV_B3
%MWxy.i.250
PV_SIM_B1
%MWxy.i.251
PV_SIM_B2
%MWxy.i.252
PV_SIM_B3
Default value
0.0
Comment
No Object
No Object
No Object
No Object
No Object
No Object
Minimum open time for valve controlled by the servo drive
Value before proportional coefficient autotuning
Value before integral coefficient autotuning
Value before derivative coefficient autotuning
Simulated measurement value loop 1
Simulated measurement value loop 2
Simulated measurement value loop 3
358
35012329 02 May 2007
11.4
Process control language objects
Language objects associated with the single loop cascade
At a Glance
Subject of this section
What's in this
Section?
This section describes the cascade loop language objects.
This section contains the following topics:
Topic
Configuration language objects
Fault and diagnostics language objects
Process control language objects
Page
35012329 02 May 2007
359
Process control language objects
Configuration language objects
Description This table describes the configuration language objects associated with the single loop cascade.
Address
%KWxy.i.0
Parameter name
CONFIG_0_M
Default value
No Object
Comment
Word bringing together the different configuration bits of the process value
%KWxy.i.0:X0
%KWxy.i.0:X1
%KWxy.i.0:X2
%KWxy.i.0:X3
%KWxy.i.0:X4
%KWxy.i.0:X8
%KWxy.i.0:X9
%KWxy.i.0:X10
%KWxy.i.0:X11
%KWxy.i.1
%KWxy.i.1:X0
%KWxy.i.1:X1
%KWxy.i.1:X2
%KWxy.i.1:X3
%KWxy.i.1:X4
Filtering
Function generator
Totalizer
Square root
Alarms
PV_CLIP
EXTRAPOL
PV_UNI_BIP
PV_EXTERNE
CONFIG_1_M
SP_Simple
SP_Selection
Speed_Limiteur
SP_SPP
RL/L
Missing (0)
Missing (0)
No Object
Missing (0)
Present
Missing (0)
Filtering function of the process value branch
Function generator of the process value branch
Totalizer function of the process value branch
Square root function of the process value branch
Alarm function of the process value branch
Lopping or non-lopping of the process value
No (0) Extrapolation of function generator
Unipolar (0)
Not selected (0) Choice of standard process value (0) / external process value (1)
No Object
Type: unipolar/bipolar of the process value
Word grouping the different setpoint configuration bits
Selected (1) Type of setpoint selected: single
Not selected (0) Type of setpoint: selection
Not selected (0) Speed limiter on the setpoint
Not selected (0) Type of setpoint selected:
Programmer
Local remote (0) Speed limiter either on the local setpoint or in Remote/Local mode
360
35012329 02 May 2007
35012329 02 May 2007
Process control language objects
Address
%KWxy.i.1:X8
%KWxy.i.1:X9
%KWxy.i.1:X10
%KWxy.i.1:X11
%KWxy.i.1:X12
%KWxy.i.1:X13
%KWxy.i.1:X14
%KWxy.i.1:X15
%KWxy.i.2
%KWxy.i.2:X0
%KWxy.i.2:X1
%KWxy.i.2:X2
%KWxy.i.2:X3
%KWxy.i.2:X4
%KWxy.i.2:X5
%KWxy.i.2:X6
%KWxy.i.2:X7
%KWxy.i.2:X8
%KWxy.i.2:X9
Parameter name
Sel_Min
Sel_Max
SEL_SWITCH
R/L_INIT
R1/R2_INIT
SP_Ratio
SP_Limiteur
SP_Folw
CONFIG_2_M
PID
ONOFF2
Default value
Missing (0)
Missing (0)
Comment
Function selected for setpoint type Selection
Function selected for setpoint type Selection
Function selected for setpoint type Selection
Present on
Selection
Local (1)
R1 (0)
Initial value of the Remote/Local selected setpoint
Initial value of the status of the selected setpoint
Not selected (0) Type of setpoint selected: Ratio
Not present Setpoint limiter (e.g.
PARAM_SP)
No setpoint
No Object
Tracking setpoint (0)
Word bringing together the different loop controller configuration bits and Feed
Forward
Present (always) PID function of the loop controller branch
No Object ON OFF 2 states branch of loop controller
ONOFF3
SPLRG/HOTCOLD
Split/Range
Hot/Cold
ALARMES_DEV
Feed Forward
BUMP
PV_DEV
No Object
No Object
No Object
No Object
Present
Missing (0)
ON OFF 3 states branch of loop controller
OR Hot/Cold and Split Range presence bits
Loop controller branch Split
Range function
Hot/Cold function of the loop controller branch
Alarm function on diversion of the loop controller branch
Presence of a Feed forward input
With bumps (1) Management bumps when changing operating mode
On process value (0)
Type of derived action
361
Process control language objects
Address
%KWxy.i.2:X11
%KWxy.i.2:X12
Parameter name
%KWxy.i.2:X10 MIX_PAR
REV_DIR
MANU/AUTO_INIT
Default value
PID parallel series
PID action
Auto (1)
Comment
Mixed or parallel loop controller type
Type of inverse loop controller action (0)
Initial value of loop controller operating mode
%KWxy.i.2:X13
%KWxy.i.2:X14
Lead lag
FF_UNI_BIP
Missing (0)
Unipolar
%KWxy.i.2:X15
%KWxy.i.3
%KWxy.i.7
%KWxy.i.10
%KWxy.i.10:X0
%KWxy.i.10:X1
IMC
Loop name
Loop unit
CONFIG_0_E
Filtering
Function generator
Missing (0)
Loop i with i [0.9] Loop name
Loop unit
No Object
IMC function of the loop controller branch
Missing (0)
No Object
Word grouping the different
Process value configuration bits
Filtering function of the process value branch
Function generator of the process value branch
%KWxy.i.10:X2 Totalizer Missing (0)
Leadlag function of the Feed forward branch
Type of Feed forward process value: unipolar or bipolar
%KWxy.i.10:X3
%KWxy.i.10:X4
%KWxy.i.10:X8
Square root
Alarms
PV_CLIP
Missing (0)
Present
Missing (0)
Totalizer function of the process value branch
Square root function of the process value branch
Alarm function of the process value branch
Lopping or non-lopping of the process value
%KWxy.i.10:X9 EXTRAPOL
%KWxy.i.10:X10 PV_UNI_BIP
%KWxy.i.10:X13 Totalizer: Process
%KWxy.i.11
value unit
%KWxy.i.10:X14 Totalizer: Process value unit
CONFIG_1_E
No Object
Unipolar (0)
1
0
No Object
Extrapolation of function generator
Type of process value: unipolar or bipolar
(X13=0, X14 =0): phys/ms
(X13=1, X14 =0): phys/s
(X13=0, X14 =1): phys/mn
(X13=1, X14 =1): phys/h
Word grouping the different setpoint configuration bits
362
35012329 02 May 2007
35012329 02 May 2007
Process control language objects
Address Parameter name
%KWxy.i.11:X0 SP_Simple
%KWxy.i.11:X1 SP_Selection
%KWxy.i.11:X2 Speed_Limiteur
%KWxy.i.11:X3 SP_SPP
%KWxy.i.11:X4
%KWxy.i.11:X8
%KWxy.i.11:X9
RL/L
Sel_Min
Sel_max
%KWxy.i.11:X10 Sel_switch
%KWxy.i.11:X11 R/L_INIT
%KWxy.i.11:X12 R1/R2_INIT
%KWxy.i.11:X13 SP_Ratio
%KWxy.i.11:X14 SP_Limiteur
%KWxy.i.11:X15 SP_Folw
%KWxy.i.12
%KWxy.i.12:X0
%KWxy.i.12:X1
%KWxy.i.12:X2
%KWxy.i.12:X3
%KWxy.i.12:X4
CONFIG_2_E
PID
ONOFF2
ONOFF3
SPLRG/HotCold
Split/Range
Default value
Selected (1)
Comment
Type of setpoint selected:
Single
No Object Type of setpoint: Selection
Not selected (0) Speed limiter on the setpoint
No Object
Local remote (0) Speed limiter either on the local setpoint or in Remote/Local mode
No Object
Type of setpoint selected:
Programmer
No Object
No Object
Function selected for setpoint type Selection
Function selected for setpoint type Selection
Function selected for setpoint type Selection
Local (1)
No Object
Initial value of the Remote/Local selected setpoint
Initial value of the status of the selected setpoint
Type of setpoint selected: Ratio No Object
Not present Setpoint limiter (e.g.
PARAM_SP)
Tracking setpoint Non tracking setpoint (0)
No Object Word bringing together the different loop controller configuration bits and Feed forward
Present (always) PID function of the loop controller branch
No Object ON OFF 2 states branch of loop controller
No Object ON OFF 3 states branch of loop controller
No Object
Missing (0)
Or Hot/Cold and Split Range presence bits
Loop controller branch Split
Range function
363
Process control language objects
Address
%KWxy.i.12:X6
%KWxy.i.12:X7
%KWxy.i.12:X8
%KWxy.i.12:X9
Parameter name
%KWxy.i.12:X5 Hot/Cold
Alarmes_DEV
Feed Forward
BUMP
PV_DEV
%KWxy.i.12:X10 MIX_PAR
%KWxy.i.12:X11 REV_DIR
Default value
Not selected
Present
No Object
With bumps (1) Management of bumps when changing operating mode
On process value (0)
Type of derived action
PID parallel series
PID action
Mixed or parallel loop controller type
Type of inverse loop controller action (0)
%KWxy.i.12:X12 MANU/AUTO_INIT Manu (0)
Comment
Hot/Cold function of the loop controller branch
Alarm function on diversion of the loop controller branch
Presence of a Feed forward input
%KWxy.i.12:X13 Lead lag
%KWxy.i.12:X14 FF_UNI_BIP
%KWxy.i.12:X15 IMC
No Object
No Object
Missing (0)
Initial value of loop controller operating mode
Leadlag function of the Feed forward branch
Type of Feed forward process value: unipolar or bipolar
IMC function of the loop controller branch
%KWxy.i.13
CONFIG_3_E No Object
%KWxy.i.13:X0
%KWxy.i.13:X1
%KWxy.i.13:X2
%KWxy.i.13:X3
%KWxy.i.13:X4
%KWxy.i.13:X5
%KWxy.i.13:X8
%KWxy.i.13:X9
Servo
Servo2
Analog1
Analog2
PWM1
PWM2
POT_REV1
POT_REV2
%KWxy.i.13:X10 POT_VAL1_INIT
%KWxy.i.13:X11 POT_VAL2_INIT
Not selected
Not selected
Not selected
Not selected
Not selected
Not selected
Direct (0)
Direct (0)
No (0)
Yes (1)
%KWxy.i.13:X12 ANALOG1_UNI_BIP Unipolar
Word grouping the different output configuration bits
Type of output selected: Servo
Type of output selected: Servo
Type of output selected: Analog
Type of output selected: Analog
Type of output selected: PWM
Type of output selected: PWM
Servo copy direction
Servo copy direction
Presence of Servo copy
Presence of (Reserved) Servo copy
Type of analog output: unipolar or bipolar
364
35012329 02 May 2007
Process control language objects
Address
%KWxy.i.14
%KWxy.i.18
Parameter name
Loop name
Loop unit
Default value
%KWxy.i.13:X13 ANALOG2_UNI_BIP Unipolar (0)
Comment
Type of analog output: unipolar or bipolar
Loop i with i [0.9] Loop name
Loop unit
35012329 02 May 2007
365
Process control language objects
Fault and diagnostics language objects
366
35012329 02 May 2007
Description
35012329 02 May 2007
Process control language objects
This table shows the fault and diagnostics language objects associated with the single loop cascade.
Address Parameter name Default value
Comment
%MWxy.i.0
%MWxy.i.1
%MWxy.i.2
%MWxy.i.2:X4
%MWxy.i.2:X5
%MWxy.i.2:X6
%MWxy.i.2:X7
%MWxy.i.2:X8
%MWxy.i.2:X9
EXCH_ERR
CH_FLT
INTERNAL_FLT
CONF_FLT
MISSING_ADDR_M
%MWxy.i.2:X10 STS_ERR_CALC_PV_M
%MWxy.i.2:X11 STS_ERR_FLOT_PV_M
%MWxy.i.2:X12 STS_ERR_SCALE_PV_M
%MWxy.i.3
%MWxy.i.3:X0
%MWxy.i.3:X1
%MWxy.i.3:X2
%MWxy.i.3:X3
%MWxy.i.3:X4
%MWxy.i.3:X5
%MWxy.i.3:X6
EXCH_STS
WARN
STS_ERR_CALC_CORR_M
STS_ERR_FLOT_CORR_M
CH_STATUS2
STS_ERR_CALC_OUT
STS_ERR_FLOT_OUT
STS_ERR_TH_SPLRG
STS_ERR_SCALE_OUT1
STS_ERR_SCALE_OUT2
STS_ERR_COPY_POS
MISSING_ADDR_E
Exchange management status
Exchange report status
Channel standard fault
Serious internal error
Configuration fault
Missing IMC master loop register address
Sum of errors
Master loop controller branch calculation error
Master loop controller branch floating point error
Master PV branch calculation error
Master PV branch floating point error
Master PV branch incorrect scale
Channel state
OUT branch calculation error
OUT branch floating point error
Split Range function thresholds incorrect
OUT1 branch scale incorrect
OUT2 branch scale incorrect
Missing position copy address
Missing IMC slave loop register address
367
Process control language objects
Address
%MWxy.i.3:X8
Parameter name
STS_ERR_CALC_CORR
%MWxy.i.3:X9 STS_ERR_FLOT_CORR_E
%MWxy.i.3:X10 STS_ERR_CALC_PV_E
%MWxy.i.3:X11 STS_ERR_FLOT_PV_E
%MWxy.i.3:X12 STS_ERR_SCALE_PV_E
%MWxy.i.4
STATUS1_M
%MWxy.i.4:X1
%MWxy.i.4:X2
%MWxy.i.4:X3
%MWxy.i.4:X4
%MWxy.i.4:X5
%MWxy.i.4:X6
%MWxy.i.4:X7
%MWxy.i.4:X8
%MWxy.i.4:X9
STS_PV_SIM_M
STS_PV_H_LIM_M
STS_PV_L_LIM_M
STS_SP_H_LIM_M
STS_SP_L_LIM_M
STS_L_R_M
STS_R1_R2_M
STS_ALARMS_M
STS_HH_M
%MWxy.i.4:X10 STS_H_M
%MWxy.i.4:X11 STS_L_M
%MWxy.i.4:X12 STS_LL_M
%MWxy.i.4:X13 STS_DEV_H_M
Default value
Comment
R/L Init
Slave loop controller branch calculation error
Slave loop controller branch floating point error
Slave PV branch calculation error
Slave PV branch floating point error
Slave PV branch incorrect scale
Word grouping the different Process value/
Setpoint status bits
Process value simulation state
High limit on process value branch (PV_SUP)
Low limit on process value branch (PV_INF)
High limit on setpoint branch (SP_SUP)
Low limit on setpoint branch (SP_INF)
State of the Remote/
Local selected setpoint
State of selected setpoint
Sum of process value alarms
Very high alarm
High alarm
Low alarm
Very low alarm
High threshold for
Process value/Setpoint deviation (>0)
368
35012329 02 May 2007
35012329 02 May 2007
Address
%MWxy.i.4:X14 STS_DEV_L_M
%MWxy.i.5
STATUS2_M
%MWxy.i.5:X0
%MWxy.i.5:X1
STS_AT_RUNNING_M
STS_TR_S_M
%MWxy.i.5:X3
%MWxy.i.5:X8
STS_M_A_M
STS_OUT_L_LIM_M
%MWxy.i.5:X9 STS_OUT_H_LIM_M
%MWxy.i.5:X10 STS_TOP_NEXT_CYC_M
%MWxy.i.5:X11 STS_TOP_CUR_CYC_M
%MWxy.i.5:X12 STS_FF_SIM_M
%MWxy.i.5:X13 STS_OUT_CLAMP_LOW
%MWxy.i.5:X14 STS_OUT_CLAMP_HIGH
%MWxy.i.6
STATUS3_M
%MWxy.i.6:X0
%MWxy.i.6:X1
%MWxy.i.6:X2
%MWxy.i.6:X3
Parameter name
Xi_WARN_M
Yi_WARN_M
INP_INFR1_WARN_M
INP_INFR2_WARN_M
Process control language objects
Default value
Comment
Low threshold for Process value/Setpoint deviation
(<0)
No Object Word grouping the different status bits of the slave loop controller
Autotuning in progress
PID in tracking mode
(open cascade)
PID operation state
Low limit of output reached
High limit of output reached
Sampling pulse on next cycle
Sampling pulse in current cycle
Simulation state of Feed forward process value
Output of slanting master in falling direction
Output of slanting master in rising direction
No Object Word grouping end of different errors diagnostics (Feed forward process value/ setpoint)
Xi parameter check error
Yi parameter check error
INP_INFR1 and
INP_SUPR1 parameters check error
INP_INFR2 and
INP_SUPR2 parameters check error
369
Process control language objects
Address
%MWxy.i.6:X4
Parameter name
RATIO_WARN_M
%MWxy.i.6:X5 FF_CALC_WARN_M
%MWxy.i.6:X6
%MWxy.i.6:X7
FF_FLOAT_WARN_M
OUT_FF__WARN_M
%MWxy.i.6:X9 SP_MIN_WARN_M
%MWxy.i.6:X10 SP_CALC_WARN_M
%MWxy.i.6:X11 SP_FLOAT_WARN_M
%MWxy.i.7
STATUS1_E
%MWxy.i.7:X0
%MWxy.i.7:X1
STS_HOLD_TOT
STS_FORCAGE_PV_E
%MWxy.i.7:X2
%MWxy.i.7:X3
STS_PV_H_LIM_E
STS_PV_L_LIM_E
%MWxy.i.7:X4 STS_SP_H_LIM_E
%MWxy.i.7:X5
%MWxy.i.7:X6
%MWxy.i.7:X8
STS_SP_L_LIM_E
STS_L_R_E
STS_ALARMS_E
%MWxy.i.7:X9 STS_HH_E
%MWxy.i.7:X10 STS_H_E
%MWxy.i.7:X11 STS_L_E
%MWxy.i.7:X12 STS_LL_E
370
Default value
Comment
R/L Init
RATIO_MIN and
RATIO_MAX parameter check error
Feed forward calculation error
Feed forward floating point error
OUTFF_INF and
OUTFF_SUP parameters check error
SP_MIN and SP_MAX parameter check error
Setpoint calculation error
Setpoint floating point error
Word grouping the different slave Process value/Setpoint status bits
Totalizer function state
Process value simulation state
High limit on process value branch (PV_SUP)
Low limit on process value branch (PV_INF)
High limit on setpoint branch (SP_SUP)
Low limit on setpoint branch (SP_INF)
State of the Remote/
Local selected setpoint
Sum of process value alarms
Very high alarm
High alarm
Low alarm
Very low alarm
35012329 02 May 2007
35012329 02 May 2007
Address Parameter name
%MWxy.i.7:X13 STS_DEV_H_E
%MWxy.i.7:X14
%MWxy.i.7:X15
%MWxy.i.8
%MWxy.i.8:X0
%MWxy.i.8:X1
%MWxy.i.8:X2
%MWxy.i.8:X3
%MWxy.i.8:X4
%MWxy.i.8:X5
%MWxy.i.8:X6
%MWxy.i.8:X7
%MWxy.i.8:X8
%MWxy.i.8:X9
STS_DEV_L_E
STS_THLD_DONE_E
STATUS2_E
STS_AT_RUNNING_E
STS_TR_S_E
STS_TR_S
STS_M_A_E
STS_RAISE1_E
STS_LOWER1_E
STS_RAISE2_E
STS_LOWER2_E
STS_OUT_L_LIM_E
STS_OUT_H_LIM_E
Process control language objects
Default value
Comment
High threshold for
Process value/Setpoint deviation (>0)
Low threshold for Process value/Setpoint deviation
(<0)
Totalizer threshold reached
No Object Word grouping the different status bits of the slave loop controller
Autotuning in progress
Tracking mode switch
No Object Tracking mode switch
(Reserved)
PID operation state
Open command
Close command
Branch output 2 open command
Branch output 2 close command
The calculated output of the PID is greater than or equal to OUT_SUP
The calculated output of the PID is smaller than or equal to OUT_INF
%MWxy.i.8:X10 STS_TOP_NEXT_CYC_E
%MWxy.i.8:X11 STS_TOP_CUR_CYC_E
%MWxy.i.9
STATUS3_E
%MWxy.i.9:X0
%MWxy.i.9:X1
STS_POT_VAL1_E
STS_POT_VAL2_E
%MWxy.i.9:X2 STS_RAISE_STOP1_E
No Object Word grouping the output diagnostics
Servo with copy operation
No Object Servo with copy operation
(Reserved)
Open limit reached on servo drive
371
Process control language objects
Address
%MWxy.i.9:X3
%MWxy.i.9:X4
%MWxy.i.9:X5
%MWxy.i.9:X8
%MWxy.i.9:X9
%MWxy.i.9:X10
%MWxy.i.9:X11
%MWxy.i.10
%MWxy.i.10:X0
%MWxy.i.10:X1
%MWxy.i.10:X2
Parameter name
STS_SP_CALC_WARN_E
STS_SP_FLOAT_WARN_E
STS_AT_FAILED
STS_AT_ABORTED
%MWxy.i.10:X3 STS_AT_PWF_OR_EFB_FAIL
%MWxy.i.10:X4
%MWxy.i.10:X5
%MWxy.i.10:X6
%MWxy.i.10:X7
%MWxy.i.10:X8
STS_LOWER_STOP1_E
STS_RAISE_STOP2_E
STS_LOWER_STOP2_E
STS_OVER_TOT_WARN_E
STS_SP_MIN_WARN_E
STATUS4
STS_AT_ERR_PARAM
STS_AT_ERR_SATUR
STS_AT_DV_TOO_SMALL
STS_AT_TSAMP_HIGH
STS_AT_INCONSIST_RESP
STS_AT_NOT_STAB_INIT
Default value
Comment
Close limit reached on servo drive
Open limit reached on servo drive
Close limit reached on servo drive
Output capacity overshoot error on
Totalizer
SP_MIN and SP_MAX parameter check error
Setpoint calculation error
Setpoint floating point error
No Object Word grouping autotuning diagnostics
Autotuning failed
Autotuning diagnostics interrupted
Autotuning diagnostics parameter error
Autotuning diagnostics system error or power failure
Autotuning diagnostics process value saturation
Autotuning diagnostics insufficient process value deviation
Autotuning Diagnostics sampling pulse period too long
Autotuning diagnostics inconsistent response
Autotuning diagnostics: initially unstable process value
372
35012329 02 May 2007
35012329 02 May 2007
Process control language objects
Address Parameter name
%MWxy.i.10:X9 STS_AT_TMAX_TOO_SMALL
Default value
Comment
%MWxy.i.10:X10
%MWxy.i.10:X11
%MWxy.i.10:X12
%MWxy.i.10:X13
%MWxy.i.10:X14
%MWxy.i.10:X15
%MWxy.i.11
%MDxy.i.12
STS_AT_NOISE_TOO_HIGH
STS_AT_TMAX_TOO_HIGH
STS_AT_OVERSHOOT
STS_AT_UNDERSHOOT
STS_AT_UNSYMETRICAL_PT
STS_AT_INTEGRATING_PT
ORDER _COMMAND
PARAM_COMMAND
Autotuning diagnostics scale period too small
Autotuning diagnostics process value noise too loud
Autotuning diagnostics scale period too long
Autotuning diagnostics overshoot above 10%
Autotuning diagnostics non-minimum phase too large
Autotuning diagnostics procedure too nonsymmetrical
Autotuning diagnostics integrating process
Command order
Command parameter
373
Process control language objects
Process control language objects
374
35012329 02 May 2007
Description
35012329 02 May 2007
Process control language objects
This table describes the different process control language objects of the cascade loop.
Address Parameter name Comment
%MFxy.i.14
%MFxy.i.16
%MFxy.i.18
%MFxy.i.20
%MFxy.i.22
%MFxy.i.24
%MFxy.i.26
%MFxy.i.28
%MFxy.i.30
%MFxy.i.32
%MFxy.i.34
%MFxy.i.36
%MFxy.i.38
%MFxy.i.40
%MFxy.i.42
%MFxy.i.44
%MFxy.i.46
%MFxy.i.48
%MFxy.i.50
%MFxy.i.52
%MFxy.i.54
%MFxy.i.56
%MFxy.i.58
%MFxy.i.60
%MFxy.i.62
%MFxy.i.64
%MFxy.i.66
%MFxy.i.68
%MFxy.i.70
%MFxy.i.72
AT_STEP
AT_TMAX
AT_PERF
T_ECH_M
OUTFF_M
OUT_MAN_M
DEV_M
PV_M
SP_M
PV_INF_M
PV_SUP_M
KP_M
TI_M
TD_M
OUTBIAS_M
INT_BAND_M
DBAND_M
KD_M
SP_MIN_M
SP_MAX_M
PV_LL_M
PV_L_M
PV_H_M
PV_HH_M
RATIO_M
RATIO_MIN_M
RATIO_MAX_M
RATIO_BIAS_M
DEV_L_M
DEV_H_M
Default value
10.0
100.0
0.5
0.3
No Object
No Object
No Object
No Object
1.0
0.0
100.0
0.0
0.0
0.0
0.0
10.0
0.0
100.0
5.0
5.0
95.0
95.0
0.0
0.0
0.0
0.0
No Object
0.0
100.0
1.0
Size of autotuning scale
Autotuning scale period
Criteria for autotuning stability
Master loop sampling period
Value of Feed forward action on physical scale
Command value
Setpoint process value deviation
Value of process value on physical scale
Value of setpoint on physical scale
Low process value limit
High process value limit
Proportional co-efficient
Integral time
Derived time
Bias on PID loop controller output
Integral band
Dead band on deviation
Filtering the derived item
Low master setpoint limit
High master setpoint limit
Very low process value threshold
Low process value threshold
High process value threshold
Very high process value threshold
Ratio value
Minimum Ratio value
Maximum Ratio value
Value of Ratio bias
Low deviation threshold
High deviation threshold
375
Process control language objects
Address
%MFxy.i.74
%MFxy.i.76
%MFxy.i.78
%MFxy.i.80
%MFxy.i.82
%MFxy.i.84
%MFxy.i.86
%MFxy.i.88
%MFxy.i.90
%MFxy.i.92
%MFxy.i.94
%MFxy.i.96
%MFxy.i.98
%MFxy.i.100
%MFxy.i.102
%MFxy.i.104
%MFxy.i.106
%MFxy.i.108
%MFxy.i.110
%MFxy.i.112
%MFxy.i.114
Parameter name
T_FILTER_M
K_FILTER_M
FILT_OUT_M
SQRT_OUT_M
E2_IN_M
E3_IN_M
Default value
0.0
1,0
E4_IN_M
E5_IN_M
E6_IN_M
E7_IN_M
E2_OUT_M
E3_OUT_M
E4_OUT_M
E5_OUT_M
E6_OUT_M
42.85
57.14
71.43
E7_OUT_M 85.71
R_RATE_M
D_RATE_M
SPEED_LIM_OUT_M
0.0
0.0
INP_INFR1_M
INP_SUPR1_M
0.0
100.0
1428.0
2857.0
4285.0
5714.0
7143.0
8571.0
14.28.0
28.57
376
Comment
Process value filtering time
Multiplication coefficient of process value filtering
Value of filter output
Output value of square root
Abcissae of first pulse of Segment
S2
Abcissae of first pulse of Segment
S3
Abcissae of first pulse of Segment
S4
Abcissae of first pulse of Segment
S5
Abcissae of first pulse of Segment
S6
Abcissae of first pulse of Segment
S7
Coordinate of first pulse of
Segment S2
Coordinate of first pulse of
Segment S3
Coordinate of first pulse of
Segment S4
Coordinate of first pulse of
Segment S5
Coordinate of first pulse of
Segment S6
Coordinate of first pulse of
Segment S7
Setpoint ascent speed limit
Setpoint descent speed limit
Value of setpoint speed limiter output
Low scale of the master loop R1 setpoint
High scale of the master loop R1 setpoint
35012329 02 May 2007
35012329 02 May 2007
OUT1_E
OUT2_E
T_ECH_E
OUT_MAN_E
DEV_E
PV_E
SP_E
PV_INF_E
PV_SUP_E
KP_E
TI_E
TD_E
OUTBIAS_E
INT_BAND_E
DBAND_E
KD_E
OUTRATE_E
Parameter name
INP_INFR2_M
INP_SUPR2_M
T1_FF_M
T2_FF_M
OUT_FF_INF_M
OUT_FF_SUP_M
KP_PREV_M
TI_PREV_M
TD_PREV_M
Address
%MFxy.i.116
%MFxy.i.118
%MFxy.i.120
%MFxy.i.122
%MFxy.i.124
%MFxy.i.126
%MFxy.i.128
%MFxy.i.130
%MFxy.i.132
%MFxy.i.134
%MFxy.i.136
%MFxy.i.138
%MFxy.i.140
%MFxy.i.142
%MFxy.i.144
%MFxy.i.146
%MFxy.i.148
%MFxy.i.150
%MFxy.i.152
%MFxy.i.154
%MFxy.i.156
%MFxy.i.158
%MFxy.i.160
%MFxy.i.162
%MFxy.i.164
%MFxy.i.166
Process control language objects
100.0
0.0
0.0
0.0
0.0
0.0
0.0
100.0
1.0
0.0
10.0
0.0
Default value
0.0
0.0
0.0
100.0
No Object
No Object
No Object
No Object
No Object
0.3
No Object
No Object
No Object
No Object
Comment
Low scale of the master loop R2 setpoint
High scale of the master loop R2 setpoint
Filtering time for Feed forward process value
Filtering time for Feed forward process value
Low limit of Feed forward action
High limit of Feed forward action
Value before proportional coefficient autotuning
Value before integral co-efficient autotuning
Value before derived co-efficient autotuning
Value of output command 1
Value of output command 2
Slave loop sampling period
Slave loop command value
Setpoint process value deviation
Value of process value on
Physical scale
Value of setpoint on Physical scale
Low process value limit
High process value limit
Proportional co-efficient
Integral time
Derived time
Bias on PID loop controller output
Integral band
Dead band on deviation
Filtering the derived item
Limit of output variation speed
377
Process control language objects
Address
%MFxy.i.168
%MFxy.i.170
%MFxy.i.172
%MFxy.i.174
%MFxy.i.176
%MFxy.i.178
%MFxy.i.180
%MFxy.i.182
%MFxy.i.184
%MFxy.i.186
%MFxy.i.188
%MFxy.i.190
%MFxy.i.192
%MFxy.i.194
%MFxy.i.196
%MFxy.i.198
%MFxy.i.200
%MFxy.i.202
%MFxy.i.204
%MFxy.i.206
%MFxy.i.208
%MFxy.i.210
%MFxy.i.212
%MFxy.i.214
%MFxy.i.216
%MFxy.i.218
%MFxy.i.220
Parameter name
OUTRATE2_E
OUT1_INF_E
OUT1_SUP_E
SP_MIN_E
SP_MAX_E
OUT2_INF_E
OUT2_SUP_E
OUT1_TH1_E
OUT1_TH2_E
OUT2_TH1_E
OUT2_TH2_E
PV_LL_E
PV_L_E
PV_H_E
PV_HH_E
DEV_L_E
DEV_H_E
T_FILTER_E
K_FILTER_E
T_MOTOR1_E
T_MINI1_E
Default value
0,0
0.0
100.0
0.0
100.0
0.0
100.0
0.0
50.0
50.0
100.0
5.0
5.0
95.0
95.0
0.0
0.0
0.0
1.0
FILT_OUT_E
SQRT_OUT_E
THLD_E
R_RATE_E
No Object
No Object
1E+8
0.0
D_RATE_E 0.0
SPEED_LIM_OUT_E No Object
10.0
0.0
Comment
Limit of output 2 variation speed
Low limit of output 1
High limit of output 1
Low setpoint limit
High setpoint limit
Low limit of Output 2
High limit of Output 2
Threshold 1 for Hot/Cold or Split
Range output 1
Threshold 2 for Hot/Cold or Split
Range output 1
Threshold 1 for Hot/Cold or Split
Range output 2
Threshold 2 for Hot/Cold or Split
Range output 2
Very low process value threshold
Low process value threshold
High process value threshold
Very high process value threshold
Low deviation threshold
High deviation threshold
Process value filtering time
Multiplication coefficient of process value filtering
Value of filter output
Output value of square root
Totalizer limit
Setpoint ascent speed limit
Setpoint descent speed limit
Value of setpoint speed limiter output
Open time for valve controlled by the servo drive
Minimum open time for valve controlled by the servo drive
378
35012329 02 May 2007
35012329 02 May 2007
Address
%MFxy.i.222
%MFxy.i.224
%MFxy.i.226
%MFxy.i.228
%MFxy.i.230
%MFxy.i.232
%MFxy.i.234
%MFxy.i.236
%MFxy.i.238
%MFxy.i.240
%MFxy.i.242
Parameter name
T_MOTOR2_E
T_MINI2_E
KP_PREV_E
TI_PREV_E
TD_PREV_E
KS
OL_TIME
T_DELAY
CL_PERF
T_MOTOR_B3
T_MINI_B
%MFxy.i.244
%MFxy.i.246
%MWxy.i.248
%MWxy.i.249
%MWxy.i.250
KP_PREV_B3
TI_PREV_B3
PV_SIM_M
PV_SIM_E
FF_SIM_M
Process control language objects
Default value
10.0
0.0
No Object
No Object
No Object
1.0
1.0
0.0
0.1
No Object
No Object
No Object
No Object
No Object
No Object
No Object
Comment
Open time for valve controlled by the servo drive
Minimum open time for valve controlled by the servo drive
Value before proportional coefficient autotuning
Value before integral co-efficient autotuning
Value before derived co-efficient autotuning
IMC static gain
Time constant in BO
Current pure delay time
BO / BF time report
Open time for valve controlled by the servo drive loop 3
Minimum open time for valve controlled by the servo drive loop
3
Value before proportional coefficient autotuning loop 3
Value before integral co-efficient autotuning loop 3
Simulated process value value
Simulated process value value
Simulated Feed forward input
379
Process control language objects
11.5
Language objects associated with the selfselective loop
At a Glance
Subject of this section
What's in this
Section?
This section describes the language objects of the self-selective loops.
This section contains the following topics:
Topic
Configuration language objects
Fault and diagnostics language objects
Process control language objects
Page
380
35012329 02 May 2007
Configuration language objects
Process control language objects
35012329 02 May 2007
381
Process control language objects
Description This table describes the configuration language objects associated with the autoselector loop.
Address
%KWxy.i.0
%KWxy.i.0:X0
%KWxy.i.0:X1
%KWxy.i.0:X2
%KWxy.i.0:X3
%KWxy.i.0:X4
%KWxy.i.0:X8
%KWxy.i.0:X9
%KWxy.i.0:X10
%KWxy.i.0:X11
%KWxy.i.0:X13
%KWxy.i.0:X14 Totalizer process
%KWxy.i.1
%KWxy.i.1:X0
%KWxy.i.1:X1
%KWxy.i.1:X2
%KWxy.i.1:X3
Parameter name
CONFIG_0_C1
Filtering
Function generator
Totalizer
Square root
Alarms
PV_CLIP
EXTRAPOL
PV_UNI_BIP
PV_EXTERNE
Totalizer process value unit value unit
CONFIG_1_C1
SP_Simple
SP_Selection
Speed_Limiteur
SP_SPP
Default value
No Object
Missing (0)
Missing (0)
Missing (0)
Missing (0)
Present
Missing (0)
No (0)
Unipolar (0)
Comment
Word grouping the different configuration bits of the C1 process value
Filtering function of the process value branch
Function generator of the process value branch
Totalizer function of the process value branch
Square root function of the process value branch
Alarm function of the process value branch
Lopping or non-lopping of the process value
Extrapolation of function generator
Type of process value: unipolar or bipolar
Missing (0) Choice of standard process value (0) / external process value (1)
1
0
No Object
Selected (1)
(X13=0, X14 =0): phys/ms
(X13=1, X14 =0): phys/s
(X13=0, X14 =1): phys/mn
(X13=1, X14 =1): phys/h
Word grouping the different configuration bits of the C1
Setpoint
Type of setpoint selected:
Single
Not selected (0) Type of setpoint: Selection
Not selected (0) Setpoint speed limiter
Not selected (0) Type of setpoint selected:
Programmer
382
35012329 02 May 2007
35012329 02 May 2007
Process control language objects
Address
%KWxy.i.1:X4
Parameter name
LR/L
%KWxy.i.1:X8
%KWxy.i.1:X9
%KWxy.i.1:X10
%KWxy.i.1:X11
%KWxy.i.1:X12
%KWxy.i.2
%KWxy.i.2:X0
%KWxy.i.2:X1
%KWxy.i.2:X2
%KWxy.i.2:X3
%KWxy.i.2:X4
%KWxy.i.2:X5
%KWxy.i.2:X6
%KWxy.i.2:X7
%KWxy.i.2:X8
Sel_Min
Sel_Max
Sel_Switch
R/L_INIT
R1/R2_INIT
%KWxy.i.1:X13 SP_Ratio
%KWxy.i.1:X14 SP_Limiteur
%KWxy.i.1:X15 SP_Folw
CONFIG_2_C1
PID
ONOFF2
ONOFF3
SPLRG/HotCold
Split/Range
Hot / Cold
ALARMES_DEV
Feed Forward
BUMP
Default value
Local Remote
(0)
Comment
Speed limiter either on the local setpoint or in Remote/Local mode
Missing (0)
Missing (0)
Present on selection
Local (1)
R1 (0)
Function selected in the event of a Selection setpoint
Function selected in the event of a Selection setpoint
Function selected in the event of a Selection setpoint
Initial value of the Remote/Local selected setpoint
Initial value of the status of the selected setpoint
Not selected (0) Type of setpoint selected: Ratio
Not present Setpoint limiter (e.g.
PARAM_SP)
No tracking
No Object
Tracking (0)
Word grouping the different loop controller configuration bits and C1 Feed forward
Always present PID function of the loop controller branch
No Object
No Object
No Object
Missing (0)
Not selected
Present
ON OFF 2 states branch of loop controller
ON OFF 3 states branch of loop controller
OR Hot/Cold and Split Range presence bits
Split Range function for branch selected
Hot/Cold function for the branch selected
Alarm function on diversion of the loop controller branch
Missing (0) Presence of a Feed forward input
With bumps (1) Management of bumps when changing operating mode
383
Process control language objects
Address
%KWxy.i.2:X9
%KWxy.i.2:X10
Parameter name
PV_DEV
MIX_PAR
Default value
On process value (0)
PID parallel series
%KWxy.i.2:X11 REV_DIR PID backward action (0)
%KWxy.i.2:X12 MANU/AUTO_INIT Auto (1)
Comment
Type of derived action
Mixed or parallel loop controller type
Type of loop controller action
%KWxy.i.2:X13
%KWxy.i.2:X14
%KWxy.i.2:X15
Lead lag
FF_UNI_BIP
IMC
Missing (0)
Unipolar
Missing (0)
Initial value of loop controller operating mode
Leadlag function of the Feed forward branch
Type of Feed forward process value: unipolar or bipolar
Model loop controller in branch loop controller
%KWxy.i.3
%KWxy.i.7
%KWxy.i.10
%KWxy.i.10:X0
Loop name
Loop unit
CONFIG_0_C2
Filtering
Loop i with i [0.9] Loop name
Loop unit
No Object
No object
Word grouping the different configuration bits of the C2 process value
Filtering function of the process value branch
%KWxy.i.10:X1 Function generator No Object
%KWxy.i.10:X2
%KWxy.i.10:X3
%KWxy.i.10:X4
%KWxy.i.10:X8
Totalizer
Square root
Alarms
PV_CLIP
Missing (0)
Missing (0)
Present
Missing (0)
Function generator of the process value branch
Totalizer function of the process value branch
Square root function of the process value branch
Alarm function of the process value branch
Lopping or non-lopping of the process value
%KWxy.i.10:X9 EXTRAPOL
%KWxy.i.10:X10
%KWxy.i.10:X11
PV_UNI_BIP
PV_EXTERNE
No object
Unipolar (0)
Missing (0)
Extrapolation of function generator
Type of process value: unipolar or bipolar
Choice of Standard Process value (0) / External Process value (1)
384
35012329 02 May 2007
35012329 02 May 2007
Process control language objects
Address
%KWxy.i.10:X13 Totalizer process
%KWxy.i.10:X14 Totalizer process
%KWxy.i.11
%KWxy.i.11:X0
%KWxy.i.11:X1
%KWxy.i.11:X2
%KWxy.i.11:X3 SP_SPP
%KWxy.i.11:X4
%KWxy.i.11:X8
%KWxy.i.11:X9
%KWxy.i.11:X10
%KWxy.i.11:X11
%KWxy.i.11:X12
%KWxy.i.11:X13
%KWxy.i.11:X14
%KWxy.i.11:X15
%KWxy.i.12
%KWxy.i.12:X0
%KWxy.i.12:X1
Parameter name value unit value unit
CONFIG_1_C2
SP_Simple
SP_Selection
SPEED_LIMITEUR
LR/L
SEL_MIN
SEL_MAX
SEL_SWITCH
R/L_INIT
R1/R2_INIT
SP_RATIO
SP_LIMITEUR
SP_FOLW
CONFIG_2_C2
PID
ONOFF2
Default value
1
0
No Object
Selected (1)
No Object
Missing (0)
No Object
Local Remote
(0)
No Object
No Object
No Object
Local (1)
Comment
(X13=0, X14 =0): phys/ms
(X13=1, X14 =0): phys/s
(X13=0, X14 =1): phys/mn
(X13=1, X14 =1): phys/h
Word grouping the different configuration bits of the C2
Setpoint
Type of setpoint selected:
Single
Type of setpoint selected:
Selection
Setpoint speed limiter
Type of setpoint selected:
Programmer
Speed limiter either on the local setpoint or in Remote/Local mode
Function selected for setpoint type Selection
Function selected for setpoint type Selection
Function selected for setpoint type Selection
Initial value of the Remote/Local selected setpoint
No Object Initial value of the status of the selected setpoint
Type of setpoint selected: Ratio No Object
Not present (0) Setpoint limiter (e.g.
PARAM_SP)
No setpoint Tracking (0)
No Object Word grouping the different loop controller configuration bits and C2 Feed forward
Present
(always)
No Object
PID function of the loop controller branch
ON OFF 2 states branch of loop controller
385
Process control language objects
386
Address
%KWxy.i.12:X3
%KWxy.i.12:X4
Parameter name
%KWxy.i.12:X2 ONOFF3
SPLRG/HOTCOLD
Split/Range
Default value
No Object
No Object
No Object
Comment
ON OFF 3 states branch of loop controller
OR Hot/Cold and Split Range presence bits
Loop controller branch Split
Range function
%KWxy.i.12:X5
%KWxy.i.12:X6
%KWxy.i.12:X7
%KWxy.i.12:X8
%KWxy.i.12:X9
Hot / Cold
ALARMES_DEV
Feed Forward
BUMP
PV_DEV
No Object
Present
No Object Presence of a Feed forward input
With bumps (1) Management of bumps when changing operating mode
On process value (0)
Type of derived action
%KWxy.i.12:X10
%KWxy.i.12:X11
MIX_PAR
REV_DIR
PID parallel series
PID backward action (0)
%KWxy.i.12:X12 MANU/AUTO_INIT Auto (1)
Hot/Cold function of the loop controller branch
Alarm function on diversion of the loop controller branch
Mixed or parallel loop controller type
Type of loop controller action
Initial value of loop controller operating mode
%KWxy.i.12:X13 Lead lag
%KWxy.i.12:X14
%KWxy.i.12:X15
%KWxy.i.13
FF_UNI_BIP
IMC
CONFIG_3_C2
No Object
No Object
Missing (0)
No Object
Leadlag function of the Feed forward branch
Type of Feed forward process value: unipolar or bipolar
Model loop controller in branch loop controller
Word grouping the different output configuration bits
Type of output selected: Servo %KWxy.i.13:X0 Servo
%KWxy.i.13:X1 Servo2
%KWxy.i.13:X2 Analog 1
%KWxy.i.13:X3 Analog 2
%KWxy.i.13:X4 PWM1
%KWxy.i.13:X5 PWM2
%KWxy.i.13:X8
%KWxy.i.13:X9
POT_REV1
POT_REV2
Not selected
Not selected
Not selected
Not selected
Not selected
Not selected
Direct (0)
Direct (0)
Type of output selected: Servo
Type of output selected: Analog
Type of output selected: Analog
Type of output selected: PWM
Type of output selected: PWM
Servo copy direction
Servo copy direction
35012329 02 May 2007
35012329 02 May 2007
Process control language objects
Address
%KWxy.i.13:X10 POT_VAL1_INIT
%KWxy.i.13:X11 POT_VAL2_INIT
%KWxy.i.14
%KWxy.i.18
%KWxy.i.21
Parameter name
Loop name
Loop unit
CONFIG_0_G
Default value
No (0)
No (0)
%KWxy.i.13:X12 ANALOG1_UNI_BIP Unipolar (0)
%KWxy.i.13:X13
%KWxy.i.21:X0
%KWxy.i.21:X1
%KWxy.i.21:X2
%KWxy.i.21:X8
%KWxy.i.21:X9
%KWxy.i.21:X10
%KWxy.i.21:X11
ANALOG2_UNI_BIP Unipolar (0)
MANU/
AUTO_G_INIT
AM_G_PID
MIN_MAX
AS_INIT
DIR1_INIT
DIR2_INIT Missing (0)
Comment
Presence of Servo copy
Presence of Servo copy
Type of analog output: unipolar or bipolar
Type of analog output: unipolar or bipolar
Loop i with i [0.9] Loop name
Loop unit
No Object
Manu (0)
Word grouping the different configuration bits of the global loop
Initial operating value of global loop
On the global loop (0)
Min (0)
Present (1)
Managing A/M blocks initially: on A/M block 0 on the global loop
At 1: A/M blocks on each PID
Initial behavior of the autoselector
Output obtained by restriction on initialization = auto-selector output
Missing (0) Output obtained by restriction on initialization = PID n°1 output
Output obtained by restriction on initialization = PID n°2 output
387
Process control language objects
Fault and diagnostics language objects
Description This table describes the fault and diagnostics language objects associated with the auto-selector loop.
Address Parameter name Default value
Comment
%MWxy.i.0
%MWxy.i.1
%MWxy.i.2
%MWxy.i.2:X4
%MWxy.i.2:X5
%MWxy.i.2:X6
%MWxy.i.2:X7
%MWxy.i.2:X8
%MWxy.i.2:X9
EXCH_ERR
CH_FLT
INTERNAL_FLT
CONF_FLT
MISSING_ADDR_2
WARN
STS_ERR_CALC_CORR_B2
%MWxy.i.2:X10 STS_ERR_CALC_PV_B2
%MWxy.i.2:X11 STS_ERR_FLOT_PV_B2
%MWxy.i.2:X12 STS_ERR_SCALE_PV_B2
%MWxy.i.3
CH_STATUS2
%MWxy.i.3:X0 STS_ERR_CALC_OUT
%MWxy.i.3:X1
%MWxy.i.3:X2
%MWxy.i.3:X3
%MWxy.i.3:X4
%MWxy.i.3:X6
EXCH_STS
STS_ERR_FLOT_CORR_B2
STS_ERR_FLOT_OUT
STS_ERR_TH_SPLRG
STS_ERR_CALC_CONT
STS_ERR_COPY_POS
MISSING_ADDR_1
Exchange management status
Exchange report status
Channel standard fault
Serious internal error
Configuration fault
Missing secondary loop
IMC register address
Sum of warnings
Loop controller branch calculation error
Loop controller branch floating point error
PV branch calculation error
PV branch floating point error
PV1 branch scale incorrect
Channel state
OUT branch calculation error
OUT branch floating point error
Split Range function thresholds incorrect
Secondary branch calculation error
Missing position copy address
Missing main loop IMC register address
388
35012329 02 May 2007
35012329 02 May 2007
Process control language objects
Address Parameter name
%MWxy.i.3:X8 STS_ERR_CALC_CORR_1
Default value
%MWxy.i.3:X10 STS_ERR_CALC_PV_1
%MWxy.i.3:X11 STS_ERR_FLOT_PV_1
%MWxy.i.3:X12 STS_ERR_SCALE_PV_1
%MWxy.i.3:X13 STS_ERR_SCALE_OUT1
%MWxy.i.3:X14 STS_ERR_SCALE_OUT2
%MWxy.i.3:X15 STS_ERR_SCALE
%MWxy.i.4
STATUS1_C1
%MWxy.i.4:X0
%MWxy.i.4:X1
%MWxy.i.4:X2
%MWxy.i.4:X3
%MWxy.i.4:X4
%MWxy.i.4:X5
%MWxy.i.4:X6
%MWxy.i.4:X7
%MWxy.i.4:X8
%MWxy.i.4:X9
%MWxy.i.4:X14
STS_HOLD_TOT_C1
STS_PV_SIM_C1
STS_PV_H_LIM_C1
STS_PV_L_LIM_C1
STS_SP_H_LIM_C1
STS_SP_L_LIM_C1
STS_L_R_C1
STS_R1_R2_C1
STS_ALARMS_C1
STS_HH_C1
%MWxy.i.4:X10 STS_H_C1
%MWxy.i.4:X11 STS_L_C1
%MWxy.i.4:X12 STS_LL_C1
%MWxy.i.4:X13 STS_DEV_H_C1
STS_DEV_L_C1
R/L Init
Comment
Loop controller branch calculation error
PV branch calculation error
PV branch floating point error
PV branch incorrect scale
C1 branch incorrect scale
C2 branch incorrect scale
OR scale errors
Word grouping the different Process value/
Setpoint status bits of the main loop
Totalizer function freeze
Simulated process value
High limit on process value
Low limit on process value
High limit on setpoint
Low limit on setpoint
Remote Setpoint (1) Local
Setpoint (0)
Remote2 Setpoint (1)
Remote1 Setpoint (0)
OR logic of process value alarms
Very high alarm
High alarm
Low alarm
Very low alarm
High alarm for Process value/Setpoint deviation
(>0)
Low alarm for Process value/Setpoint deviation
(<0)
389
Process control language objects
Address Parameter name
%MWxy.i.4:X15 STS_THLD_DONE_C1
%MWxy.i.5
STATUS2_C1
%MWxy.i.5:X0
%MWxy.i.5:X1
%MWxy.i.5:X2
STS_AT_RUNNING_C1
STS_M_A_C1
STS_FF_SIM_C1
%MWxy.i.5:X6 STS_TOP_NEXT_CYCLE
%MWxy.i.5:X7 STS_TOP_CUR_CYCLE
%MWxy.i.5:X8 STS_TR_S
%MWxy.i.5:X9 STS_M_A
%MWxy.i.5:X10 STS_RAISE1
%MWxy.i.5:X11 STS_LOWER1
%MWxy.i.5:X12 STS_RAISE2
%MWxy.i.5:X13 STS_LOWER2
%MWxy.i.5:X14 STS_OUT_L_LIM
%MWxy.i.5:X15
%MWxy.i.6
%MWxy.i.6:X0
%MWxy.i.6:X1
STS_OUT_H_LIM
STATUS3_C1
Xi_WARN_C1
Yi_WARN_C1
Default value
Comment
Totalizer threshold reached
No Object Word grouping the different Loop controller status bits of the main loop
Autotuning in progress
PID operation state
Simulation state of Feed forward process value
Sampling pulse on next cycle
Sampling pulse in current cycle
Tracking in progress on the global loop
Global Manu / Auto
Open command (global loop)
Close command (global loop)
Output 2 branch open command (global loop)
Output 2 branch close command (global loop)
Upper limit reached for the
PID output selected (global loop)
Low limit reached for the
PID output selected (global loop)
No Object Word grouping end of different diagnostics warnings (process value, setpoint, Feed forward) main loop
Xi parameter check error
Yi parameter check error
390
35012329 02 May 2007
35012329 02 May 2007
Address
%MWxy.i.6:X2
%MWxy.i.6:X3
%MWxy.i.6:X4
%MWxy.i.6:X5
%MWxy.i.6:X8
%MWxy.i.6:X9
%MWxy.i.6:X10 SP_MIN_WARN_C1
%MWxy.i.6:X11 SP_CALC_WARN_C1
%MWxy.i.6:X12 SP_FLOAT_WARN_C1
%MWxy.i.6:X13 OVER_TOT_WARN_C1
%MWxy.i.7
STATUS1_C2
%MWxy.i.7:X1
%MWxy.i.7:X2
%MWxy.i.7:X3
%MWxy.i.7:X4
%MWxy.i.7:X5
%MWxy.i.7:X6
Parameter name
RATIO_WARN_C1
FF_CALC_WARN_C1
FF_FLOAT_WARN_C1
OUT_FF__WARN_C1
INP_INFR1_WARN_C1
INP_INFR2_WARN_C1
STS_PV_SIM_C2
STS_PV_H_LIM_C2
STS_PV_L_LIM_C2
STS_SP_H_LIM_C2
STS_SP_B_LIM_C2
STS_L_R_C2
Process control language objects
Default value
Comment
RATIO_MIN and
RATIO_MAX parameter check error
Feed forward calculation error
Feed forward floating point error
OUTFF_INF and
OUTFF_SUP parameters check error
INP_INFR1 and
INP_SUPR1 parameters check error
INP_INFR2 and
INP_SUPR2 parameters check error
SP_MIN and SP_MAX parameter check error
Setpoint calculation error
Setpoint floating point error
Error on totalizer overflow
No Object Word grouping the different Process value/
Setpoint status bits of the
Secondary loop
Process value simulation status
High limit on process value branch (PV_SUP)
Low limit on process value branch (PV_INF)
High limit on setpoint branch
R/L Init
Low limit on setpoint branch
Remote Setpoint (1) Local
Setpoint (0)
391
Process control language objects
392
Address
%MWxy.i.7:X8
%MWxy.i.7:X9
%MWxy.i.7:X14
%MWxy.i.7:X15
%MWxy.i.8
Parameter name
STS_ALARMS_C2
STS_HH_C2
%MWxy.i.7:X10 STS_H_C2
%MWxy.i.7:X11 STS_L_C2
%MWxy.i.7:X12 STS_LL_C2
%MWxy.i.7:X13 STS_DEV_H_C2
STS_DEV_L_C2
STS_THLD_DONE_C2
STATUS2_C2
%MWxy.i.8:X0
%MWxy.i.8:X1
%MWxy.i.8:X8
STS_AT_RUNNING_C2
STS_M_A_C2
INP_INFR1_WARN_C2
%MWxy.i.8:X9
%MWxy.i.8:X10 SP_MIN_WARN_C2
%MWxy.i.8:X11 SP_CALC_WARN_C2
%MWxy.i.8:X12 SP_FLOAT_WARN_C2
%MWxy.i.8:X13 OVER_TOT_WARN_C2
%MWxy.i.9
STATUS3
%MWxy.i.9:X0 STS_POT_VAL1
%MWxy.i.9:X1 STS_POT_VAL2
%MWxy.i.9:X2 STS_RAISE STOP1
Default value
Comment
Sum of process value alarms
Very high alarm
High alarm
Low alarm
Very low alarm
High threshold for Process value/Setpoint deviation
(>0)
Low threshold for Process value/Setpoint deviation
(<0)
Totalizer threshold reached
No Object Word grouping the different loop controller/ setpoint status bits of the
Secondary loop
Autotuning in progress
PID operation state
INP_INFR1 and
INP_SUPR1 parameters check error
SP_MIN and SP_MAX parameter check error
Setpoint calculation error
Setpoint floating point error
Totalizer overflow error
No Object Word grouping the different output bits
Servo with copy operation
(global loop)
Servo with copy operation
(global loop)
Open limit reached on
Servo drive (global loop)
35012329 02 May 2007
35012329 02 May 2007
Address
%MWxy.i.9:X3
%MWxy.i.9:X4
%MWxy.i.9:X5
%MWxy.i.9:X8
%MWxy.i.9:X9
%MWxy.i.9:X10
%MWxy.i.9:X11
Parameter name
STS_LOWER STOP1
STS_RAISE STOP2
STS_LOWER STOP2
STS_AS
STS_DIR1
STS_DIR2
STS_SEL_PID1
%MWxy.i.10
STATUS4
%MWxy.i.10:X0 AT_FAILED
%MWxy.i.10:X1 AT_ABORTED
%MWxy.i.10:X2 AT_ERR_PARAM
%MWxy.i.10:X3 AT_PWF_OR_EFB_FAIL
%MWxy.i.10:X4
%MWxy.i.10:X5
%MWxy.i.10:X6
%MWxy.i.10:X7
AT_ERR_SATUR
AT_DV_TOO_SMALL
AT_TSAMP_HIGH
AT_INCONSIST_RESP
Process control language objects
Default value
Comment
Close limit reached on
Servo drive (global loop)
Open limit reached on
Servo drive (global loop)
Close limit reached on
Servo drive (global loop)
Selector positioned on the auto-selector
Selector positioned on
PID1 output
Selector positioned on
PID2 output
1: Selected output = PID1 output
0: Selected output = PID2 output
No Object Word grouping autotuning diagnostics
Autotuning failed
Autotuning diagnostics interrupted
Autotuning diagnostics parameter error
Autotuning diagnostics system error or power failure
Autotuning diagnostics process value saturation
Autotuning diagnostics insufficient process value deviation
Autotuning Diagnostics sampling pulse period too long
Autotuning diagnostics inconsistent response
393
Process control language objects
Address Parameter name
%MWxy.i.10:X8 AT_NOT_STAB_INIT
%MWxy.i.10:X9 AT_TMAX_TOO_SMALL
%MWxy.i.10:X10 AT_NOISE_TOO_HIGH
%MWxy.i.10:X11 AT_TMAX_TOO_HIGH
%MWxy.i.10:X12 AT_OVERSHOOT
%MWxy.i.10:X13 AT_UNDERSHOOT
%MWxy.i.10:X14 AT_UNSYMETRICAL_PT
%MWxy.i.10:X15 AT_INTEGRATING_PT
%MWxy.i.11
%MDxy.i.12
ORDER_COMMAND
PARAM_COMMAND
Default value
Comment
Autotuning diagnostics: initially unstable process value
Autotuning diagnostics grade period too small
Autotuning diagnostics process value noise too loud
Autotuning diagnostics grade period too long
Autotuning diagnostics overshoot above 10%
Autotuning diagnostics non-minimum phase too large
Autotuning diagnostics procedure too nonsymmetrical
Autotuning diagnostics integrating process
Order Command
Parameter Command
394
35012329 02 May 2007
Process control language objects
Process control language objects
35012329 02 May 2007
395
Process control language objects
Description This table describes the process control language objects associated with the autoselector loop channel.
Address Parameter name
%MFxy.i.14
%MFxy.i.16
%MFxy.i.18
%MFxy.i.20
%MFxy.i.22
%MFxy.i.24
%MFxy.i.26
%MFxy.i.28
%MFxy.i.30
%MFxy.i.32
%MFxy.i.34
%MFxy.i.36
%MFxy.i.38
%MFxy.i.40
%MFxy.i.42
%MFxy.i.44
%MFxy.i.46
%MFxy.i.48
%MFxy.i.50
AT_STEP
AT_TMAX
AT_PERF
T_ECH
OUT1
OUT2
OUTD
OUT_MAN
OUTFF_C1
OUT_MAN_C1
DEV_C1
PV_C1
SP_C1
PV_INF_C1
PV_SUP_C1
KP_C1
TI_C1
TD_C1
OUTBIAS_C1
1.0
0.0
0.0
0.0
Default value
10.0
Comment
100.0
0.5
0.3
No object
Autotuning step function amplitude
Autotuning step function duration
Autotuning stability criterion
Sampling period (common to the two PID)
Heat/Cool or Split Range output 1 command value
No object
No object
Heat/Cool or Split Range output 2 command value
Global loop command variation value
No object Value of global command
(loop controller output value selected after processing via OUTRATE and limitations)
No Object Value of Feed forward action on main loop
Physical scale
No object Main loop command value
No Object Main loop process value setpoint deviation
No Object PV value on physical scale
No Object Setpoint value on Physical scale
0.0
Process value low limit
100.0
Process value high limit
Proportional coefficient
Integral time
Derivative time
Bias on main loop PID loop controller output
396
35012329 02 May 2007
35012329 02 May 2007
Parameter name
INT_BAND_C1
DBAND_C1
KD_C1
SP_MIN_C1
SP_MAX_C1
PV_LL_C1
PV_L_C1
PV_H_C1
PV_HH_C1
RATIO_C1
RATIO_MIN_C1
RATIO_MAX_C1
RATIO_BIAS_C1
DEV_L_C1
DEV_H_C1
T_FILTER_C1
K_FILTER_C1
FILT_OUT_C1
SQR_OUT_C1
E2_IN_C1
E3_IN_C1
E4_IN_C1
E5_IN_C1
E6_IN_C1
E7_IN_C1
E2_OUT_C1
E3_OUT_C1
E4_OUT_C1
E5_OUT_C1
E6_OUT_C1
Address
%MFxy.i.52
%MFxy.i.54
%MFxy.i.56
%MFxy.i.58
%MFxy.i.60
%MFxy.i.62
%MFxy.i.64
%MFxy.i.66
%MFxy.i.68
%MFxy.i.70
%MFxy.i.72
%MFxy.i.74
%MFxy.i.76
%MFxy.i.78
%MFxy.i.80
%MFxy.i.82
%MFxy.i.84
%MFxy.i.86
%MFxy.i.88
%MFxy.i.90
%MFxy.i.92
%MFxy.i.94
%MFxy.i.96
%MFxy.i.98
%MFxy.i.100
%MFxy.i.102
%MFxy.i.104
%MFxy.i.106
%MFxy.i.108
%MFxy.i.110
Process control language objects
Default value
0.0
0.0
10.0
0.0
100.0
5.0
0.0
-5.0
5.0
0.0
1.0
95.0
1.0
0.0
100.0
Comment
5.0
95.0
No object
No object
1428.0
2857.0
4285.0
5714.0
7143.0
8571.0
14.28
28.57
42.85
57.14
71.43
Integral band
Dead band on deviation
Derivative filtering
Setpoint low limit
Setpoint high limit
Process value threshold very low
Process value threshold low
Process value threshold high
Process value threshold
Ratio Value
Minimum Ratio value
Maximum Ratio value
Ratio bias Value
Deviation low threshold
Deviation high threshold
Process value filtering time
Multiplication coefficient of process value filtering
Filtering output value
Square root output value
Segment S2 input value
Segment S3 input value
Segment S4 input value
Segment S5 input value
Segment S6 input value
Segment S7 input value
Segment S2 output value
Segment S3 output value
Segment S4 output value
Segment S5 output value
Segment S6 output value
397
Process control language objects
%MFxy.i.126
%MFxy.i.128
%MFxy.i.130
%MFxy.i.132
%MFxy.i.134
%MFxy.i.136
%MFxy.i.138
%MFxy.i.140
%MFxy.i.142
%MFxy.i.144
%MFxy.i.146
%MFxy.i.148
%MFxy.i.150
Address
%MFxy.i.112
%MFxy.i.114
%MFxy.i.116
%MFxy.i.118
%MFxy.i.120
%MFxy.i.122
%MFxy.i.124
Parameter name
E7_OUT_C1
THLD_C1
R_RATE_C1
D_RATE_C1
SPEED_LIM_OUT_C1
INP_INFR1_C1
INP_SUPR1_C1
INP_INFR2_C1
INP_SUPR2_C1
T1_FF_C1
T2_FF_C1
OUT_FF_INF_C1
OUT_FF_SUP_C1
KP_PREV_C1
TI_PREV_C1
TD_PREV_C1
OUT_MAN_C2
DEV_C2
PV_C2
SP_C2
398
Default value
85.71
1E+8
0.0
0.0
No object
0.0
100.0
0.0
Comment
Segment S7 output value
Totalizing limit
Setpoint speed increase limit
Setpoint speed decrease limit
Setpoint velocity limiter output value
Main loop R1 setpoint low scale
Main loop R1 setpoint high scale
Main loop R2 setpoint low scale
100.0
0.0
0.0
0.0
100.0
Main loop R2 setpoint high scale
Feed forward process value filtering time
Feed forward process value filtering time
Feed forward process value low limit
Feed forward process value high limit
No Object Value before proportional co-efficient autotuning
No Object Value before integral coefficient autotuning
No Object Value before derived coefficient autotuning
No Object Secondary loop command value
No Object Process value/setpoint deviation
No Object PV value on physical scale
No Object Setpoint value on Physical scale
35012329 02 May 2007
35012329 02 May 2007
%MFxy.i.180
%MFxy.i.182
%MFxy.i.184
%MFxy.i.186
%MFxy.i.188
%MFxy.i.190
%MFxy.i.192
%MFxy.i.194
%MFxy.i.196
%MFxy.i.198
Address
%MFxy.i.152
%MFxy.i.154
%MFxy.i.156
%MFxy.i.158
%MFxy.i.160
%MFxy.i.162
%MFxy.i.164
%MFxy.i.166
%MFxy.i.168
%MFxy.i.170
%MFxy.i.172
%MFxy.i.174
%MFxy.i.176
%MFxy.i.178
Parameter name
PV_INF_C2
PV_SUP_C2
KP_C2
TI_C2
TD_C2
OUTBIAS_C2
INT_BAND_C2
DBAND_C2
SP_MIN_C2
SP_MAX_C2
PV_LL_C2
PV_L_C2
PV_H_C2
PV_HH_C2
DEV_L_C2
DEV_H_C2
SQRT_OUT_C2
THLD_C2
R_RATE_C2
D_RATE_C2
SPEED_LIM_OUT_C2
INP_INFR1_C2
INP_SUPR1_C2
KP_PREV_C2
Process control language objects
1.0
0.0
0.0
0.0
Default value
0.0
100.0
Comment
0.0
0.0
0.0
100.0
5.0
5.0
95.0
95.0
-5.0
5.0
No object
1E+8
0.0
0.0
No object
0.0
100.0
Process value low limit
Process value high limit
Proportional coefficient
Integral time
Derivative time
Bias on PID loop controller output
Integral band
Dead band on deviation
Setpoint low limit
Setpoint high limit
Process value threshold very low
Process value threshold low
Process value threshold high
Process value threshold very high
Deviation low threshold
Deviation high threshold
Square root output value
Totalizing limit
Setpoint speed increase limit
Setpoint speed decrease limit
Setpoint velocity limiter output value
Secondary loop R1 setpoint low scale
Secondary loop R1 setpoint high scale
No Object Value before proportional co-efficient autotuning
399
Process control language objects
Address
%MFxy.i.200
%MFxy.i.202
%MFxy.i.204
%MFxy.i.206
%MFxy.i.208
%MFxy.i.210
%MFxy.i.212
%MFxy.i.214
%MFxy.i.216
%MFxy.i.218
%MFxy.i.220
%MFxy.i.222
%MFxy.i.224
%MFxy.i.226
Parameter name
TI_PREV_C2
TD_PREV_C2
OUTRATE
OUTRATE2
OUT1_INF
OUT1_SUP
OUT2_INF
OUT2_SUP
OUT1_TH1
OUT1_TH2
OUT2_TH1
OUT2_TH2
T_MOTOR1
T_MINI1
%MFxy.i.228
%MFxy.i.230
T_MOTOR2
T_MINI2
%MFxy.i.232
%MFxy.i.234
%MFxy.i.236
%MFxy.i.238
%MFxy.i.240
%MFxy.i.242
%MFxy.i.244
%MFxy.i.246
KS
OL_TIME
T_DELAY
CL_PERF
400
Default value
Comment
No Object Value before integral coefficient autotuning
No Object Value before derived coefficient autotuning
0.0
0.0
0.0
100.0
Output 1 speed limit
Output 2 speed limit
Low limit of Output 1
High limit of Output 1
0.0
100.0
0.0
50.0
50.0
100.0
10.0
0.0
10.0
0.0
1.0
1.0
Low limit of Output 2
High limit of Output 2
Threshold 1 for Hot/Cold or
Split Range output 1
Threshold 2 for Hot/Cold or
Split Range output 1
Threshold 1 for Hot/Cold or
Split Range output 2
Threshold 2 for Hot/Cold or
Split Range output 2
Open time for servo drive controlled valve
Minimum open time for servo drive controlled valve
Open time for servo drive controlled valve
Minimum open time for servo drive controlled valve
IMC static gain
Time constant in BO
Current pure delay time
Ratio OL/CL
0.0
0.1
No Object
No Object
No Object
No Object
35012329 02 May 2007
Address
%MWxy.i.248
%MWxy.i.249
%MWxy.i.250
Parameter name
Simulated PV_C1
Simulated PV_C2
Simulated FF_C1
Process control language objects
Default value
Comment
No Object Simulated process value
No Object Simulated process value
No Object Simulated Feed forward input
35012329 02 May 2007
401
Process control language objects
11.6
Language objects associated with the setpoint programmer
At a Glance
Subject of this section
What's in this
Section?
This section describes the language objects associated with the setpoint programmers.
This section contains the following topics:
Topic
Configuration language objects
Fault and Diagnostics Language Objects
Process control language objects
Page
402
35012329 02 May 2007
Configuration language objects
Process control language objects
35012329 02 May 2007
403
Process control language objects
Description This table describes the configuration language objects associated with the setpoint programmer.
Address Parameter name
%KWxy.i.0
%KWxy.i.0:X0
%KWxy.i.0:X1
%KWxy.i.0:X2
%KWxy.i.0:X3
%KWxy.i.0:X4
%KWxy.i.0:X5
%KWxy.i.1
%KWxy.i.1:X0
%KWxy.i.1:X1
%KWxy.i.1:X2
%KWxy.i.1:X3
%KWxy.i.1:X4
%KWxy.i.1:X5
%KWxy.i.2
CONFIG_1
Guaranteed dwell time
Dwell type
Dwell type
Start
Retry
Retry type
CONFIG_2
Guaranteed dwell time
Dwell type
Dwell type
Start
Retry
Retry type
CONFIG_3
Default value
Comment
No (0)
0
Word which brings together the different configuration bits for profile 1
Confirmation of guaranteed dwell time function (0: no, 1: yes)
Holding type on guaranteed dwell time: 2 bits
0
With bumps
(0)
Start with bumps (0: SP0) or bumpless (1: PV)
Noncontinuous
(0)
Retry of continuous profile (1) or non-continuous (0)
With bumps
(0)
Retry with bumps (0: SPi) or bumpless (1: PV)
No (0)
0
Word which brings together the different configuration bits for profile 2
Confirmation of guaranteed dwell time function (0: no, 1: yes)
Holding type on guaranteed dwell time: 2 bits
0
With bumps
(0)
Start with bumps (0: SP0) or bumpless (1: PV)
Noncontinuous
(0)
Retry of continuous profile (1) or non-continuous (0)
With bumps
(0)
Retry with bumps (0: SPi) or bumpless (1: PV)
Word which brings together the different configuration bits for profile 3
404
35012329 02 May 2007
35012329 02 May 2007
Address Parameter name
%KWxy.i.2:X0 Guaranteed dwell time
%KWxy.i.0
%KWxy.i.2:X1
%KWxy.i.2:X2
%KWxy.i.2:X3
%KWxy.i.2:X4
%KWxy.i.2:X5
%KWxy.i.3
CONFIG_1
Dwell type
Dwell type
Start
Retry
%KWxy.i.3:X0 Guaranteed dwell time
%KWxy.i.3:X1
%KWxy.i.3:X2
%KWxy.i.3:X3
%KWxy.i.3:X4
%KWxy.i.3:X5
%KWxy.i.4
Retry type
CONFIG_4
Dwell type
Dwell type
Start
Retry
Retry type
CONFIG_5
%KWxy.i.4:X0 Guaranteed dwell time
Process control language objects
Default value
No (0)
Comment
0
Confirmation of guaranteed dwell time function (0: no, 1: yes)
Word which brings together the different configuration bits for profile 1
Holding type on guaranteed dwell time: 2 bits
0
With bumps
(0)
Start with bumps (0: SP0) or bumpless (1: PV)
Noncontinuous
(0)
Retry of continuous profile (1) or non-continuous (0)
With bumps
(0)
Retry with bumps (0: SPi) or bumpless (1: PV)
No (0)
0
Word which brings together the different configuration bits for profile 4
Confirmation of guaranteed dwell time function (0: no, 1: yes)
Holding type on guaranteed dwell time: 2 bits
0
With bumps
(0)
Start with bumps (0: SP0) or bumpless (1: PV)
Noncontinuous
(0)
Retry of continuous profile (1) or non-continuous (0)
With bumps
(0)
Retry with bumps (0: SPi) or bumpless (1: PV)
No (0)
Word which brings together the different configuration bits for profile 5
Confirmation of guaranteed dwell time function (0: no, 1: yes)
405
Process control language objects
Address
%KWxy.i.4:X1
%KWxy.i.4:X2
%KWxy.i.4:X3
%KWxy.i.4:X4
%KWxy.i.4:X5
%KWxy.i.5
Parameter name
Dwell type
Dwell type
Start
Retry
Retry type
CONFIG_6
%KWxy.i.5:X0 Guaranteed dwell time
%KWxy.i.5:X1
%KWxy.i.5:X2
%KWxy.i.5:X3
%KWxy.i.5:X4
Dwell type
Dwell type
Start
Retry
%KWxy.i.5:X5 Retry type
%KWxy.i.6
%KWxy.i.7
%KWxy.i.8
%KWxy.i.9
%KWxy.i.10
USED_PF1
USED_PF2
USED_PF3
USED_PF4
USED_PF5
Default value
0
Comment
Holding type on guaranteed dwell time: 2 bits
0
With bumps
(0)
Start with bumps (0: SP0) or bumpless (1: PV)
Noncontinuous
(0)
Retry of continuous profile (1) or non-continuous (0)
With bumps
(0)
Retry with bumps (0: SPi) or bumpless (1: PV)
No (0)
0
Word which brings together the different configuration bits for profile 6
Confirmation of guaranteed dwell time function (0: no, 1: yes)
Holding type on guaranteed dwell time: 2 bits
0
With bumps
(0)
Start with bumps (0: SP0) or bumpless (1: PV)
Noncontinuous
(0)
Retry of continuous profile (1) or non-continuous (0)
With bumps
(0)
1
Retry with bumps (0: SPi) or bumpless (1: PV)
9
Number of 1 st
segment of profile 1
Number of 1 st
segment of profile 2
17
25
33
Number of 1 st
segment of profile 3
Number of 1 st
segment of profile 4
Number of 1 st
segment of profile 5
406
35012329 02 May 2007
35012329 02 May 2007
Address
%KWxy.i.11
%KWxy.i.12
%KWxy.i.13
%KWxy.i.14
%KWxy.i.15
%KWxy.i.16
%KWxy.i.17
%KWxy.i.18
%KWxy.i.19
%KWxy.i.20
%KWxy.i.21
%KWxy.i.22
%KWxy.i.23
%KWxy.i.24
Parameter name
USED_PF6
NB_SEG_PF1
NB_SEG_PF2
NB_SEG_PF3
NB_SEG_PF4
NB_SEG_PF5
NB_SEG_PF6
NO_SEG_RT1
NO_SEG_RT2
NO_SEG_RT3
NO_SEG_RT4
NO_SEG_RT5
NO_SEG_RT6
CONF_SEG1
%KWxy.i.25
CONF_SEG2
%KWxy.i.26
CONF_SEG3
%KWxy.i.27
CONF_SEG4
25
33
9
17
41
0
8
1
8
8
8
8
8
Default value
41
0
0
0
Process control language objects
Comment
Number of 1 st
segment of profile 6
Number of used segments in profile 1
Number of used segments in profile 2
Number of used segments in profile 3
Number of used segments in profile 4
Number of used segments in profile 5
Number of used segments in profile 6
Number of start segment for repetition of profile 1
Number of start segment of retry of profile 2
Number of start segment of retry of profile 3
Number of start segment of retry of profile 4
Number of start segment of retry of profile 5
Number of start segment of retry of profile 6
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3)of segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of segment
407
Process control language objects
Address
%KWxy.i.28
Parameter name
CONF_SEG5
%KWxy.i.29
CONF_SEG6
%KWxy.i.30
CONF_SEG7
%KWxy.i.31
CONF_SEG8
%KWxy.i.32
CONF_SEG9
%KWxy.i.33
CONF_SEG10
%KWxy.i.34
CONF_SEG11
%KWxy.i.35
CONF_SEG12
%KWxy.i.36
CONF_SEG13
%KWxy.i.37
CONF_SEG14
%KWxy.i.38
CONF_SEG15
%KWxy.i.39
CONF_SEG16
%KWxy.i.40
CONF_SEG17
408
Default value
0
0
0
0
0
0
0
0
0
0
0
0
0
Comment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
35012329 02 May 2007
35012329 02 May 2007
Address
%KWxy.i.41
Parameter name
CONF_SEG18
%KWxy.i.42
CONF_SEG19
%KWxy.i.43
CONF_SEG20
%KWxy.i.44
CONF_SEG21
%KWxy.i.45
CONF_SEG22
%KWxy.i.46
CONF_SEG23
%KWxy.i.47
CONF_SEG24
%KWxy.i.48
CONF_SEG25
%KWxy.i.49
CONF_SEG26
%KWxy.i.50
CONF_SEG27
%KWxy.i.51
CONF_SEG28
%KWxy.i.52
CONF_SEG29
%KWxy.i.53
CONF_SEG30
Default value
0
0
0
0
0
0
0
0
0
0
0
0
0
Process control language objects
Comment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 03) of the segment
409
Process control language objects
Address
%KWxy.i.54
Parameter name
CONF_SEG31
%KWxy.i.55
CONF_SEG32
%KWxy.i.56
CONF_SEG33
%KWxy.i.57
CONF_SEG34
%KWxy.i.58
CONF_SEG35
%KWxy.i.59
CONF_SEG36
%KWxy.i.60
CONF_SEG37
%KWxy.i.61
CONF_SEG38
%KWxy.i.62
CONF_SEG39
%KWxy.i.63
CONF_SEG40
%KWxy.i.64
CONF_SEG41
%KWxy.i.65
CONF_SEG42
%KWxy.i.66
CONF_SEG43
410
Default value
0
0
0
0
0
0
0
0
0
0
0
0
0
Comment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 03) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
35012329 02 May 2007
35012329 02 May 2007
Address
%KWxy.i.67
Parameter name
CONF_SEG44
%KWxy.i.68
CONF_SEG45
%KWxy.i.69
CONF_SEG46
%KWxy.i.70
CONF_SEG47
%KWxy.i.71
CONF_SEG48
%KWxy.i.72
%KWxy.i.73
%KWxy.i.74
%KWxy.i.75
SPP_NAME1
SPP_NAME2
SPP_NAME3
SPP_NAME4
Default value
0
0
0
0
0
Process control language objects
Comment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
Outputs (bits 8-15) PG (bit 5)
Type (bit 4) Unit (bits 0-3) of the segment
8 characters over 4 times 2 bytes
411
Process control language objects
Fault and Diagnostics Language Objects
412
35012329 02 May 2007
Description
35012329 02 May 2007
Process control language objects
The following table describes the fault and diagnostics language objects associated with the setpoint programmer.
Address Parameter name:
MWxy.i.0
MWxy.i.1
MWxy.i.2
MWxy.i.2:X7
MWxy.i.2:X8
MWxy.i.2:X9
MWxy.i.3
MWxy.i.3:X0
MWxy.i.3:X1
MWxy.i.3:X2
MWxy.i.3:X3
MWxy.i.3:X4
MWxy.i.3:X5
MWxy.i.3:X6
MWxy.i.3:X7
MWxy.i.3:X8
MWxy.i.3:X9
MWxy.i.3:X10
MWxy.i.3:X11
MWxy.i.3:X12
MWxy.i.3:X15
MWxy.i.4
MWxy.i.4:X0
MWxy.i.4:X1
EXCH_STS
EXCH_ERR
CH_FLT
WARN
ERR_CALC
ERR_FLOAT
STATUS2
STOR0
STOR1
STOR2
STOR3
STOR4
STOR5
STOR6
STOR7
STS_SPP_HOLD
STS_INIT
STS_RUN
STS_STOP
STS_HOLD_PG
STS_ERR_SEG
STATUS3
WRN1_RMP_SP
WRN1_RMP_0
Default value
Comment
1
0
0
0
0
0
0
0
0
0
0
Exchange in progress
Exchange report in progress
Standard channel fault
Error sum
Computation error
Floating error
State of monitoring outputs,
SPP freeze, profile state
State of monitoring output 0
State of monitoring output 1
State of monitoring output 2
State of monitoring output 3
State of monitoring output 4
State of monitoring output 5
State of monitoring output 6
State of monitoring output 7
Freeze of setpoint programmer function
1: All profiles are in INIT
1: The profile in progress is in
RUN
0
0
0
Not applicable
Not applicable
1: The profile in progress is in
STOP
1: The guaranteed dwell time is inhibited
Parameter error on the segment in progress
Indication of errors for profiles 1 to 4
A profile 1 ramp with 2 identical setpoints
A profile 1 ramp at zero speed
413
Process control language objects
Address
MWxy.i.4:X2
MWxy.i.4:X3
Parameter name:
WRN1_PLR_SP
WRN1_PLR_THLD
MWxy.i.4:X4
MWxy.i.4:X5
MWxy.i.4:X6
MWxy.i.4:X7
WRN2_RMP_SP
WRN2_RMP_0
WRN2_PLR_SP
WRN2_PLR_THLD
MWxy.i.4:X8
MWxy.i.4:X9
MWxy.i.4:X10
MWxy.i.4:X11
WRN3_RMP_SP
WRN3_RMP_0
WRN3_PLR_SP
WRN3_PLR_THLD
MWxy.i.4:X12
MWxy.i.4:X13
MWxy.i.4:X14
MWxy.i.4:X15
WRN4_RMP_SP
WRN4_RMP_0
WRN4_PLR_SP
WRN4_PLR_THLD
MWxy.i.5
MWxy.i.5:X0
MWxy.i.5:X1
STATUS4
WRN5_RMP_SP
WRN5_RMP_0
414
Default value
Not applicable
Not applicable
Not applicable
Not applicable
Not applicable
Not applicable
Not applicable
Not applicable
Not applicable
Not applicable
Not applicable
Not applicable
Not applicable
Not applicable
Not applicable
Not applicable
Comment
A profile 1 dwell with 2 different setpoints
Guaranteed dwell time configured on profile 1 and
THLD zero
A profile 2 ramp with 2 identical setpoints
A profile 2 ramp at zero speed
A profile 2 dwell with 2 different setpoints
Guaranteed dwell time configured on profile 2 and
THLD zero
A profile 3 ramp with 2 identical setpoints
A profile 3 ramp at zero speed
A profile 3 dwell with 2 different setpoints
Guaranteed dwell time configured on profile 3 and
THLD zero
A profile 4 ramp with 2 identical setpoints
A profile 4 ramp at zero speed
A profile 4 dwell with 2 different setpoints
Guaranteed dwell time configured on profile 4 and
THLD zero
Indication of errors for profiles 5 and 6
A profile 5 ramp with 2 identical setpoints
A profile 5 ramp at zero speed
35012329 02 May 2007
35012329 02 May 2007
Address
MWxy.i.5:X2
MWxy.i.5:X3
Parameter name:
WRN5_PLR_SP
WRN5_PLR_THLD
MWxy.i.5:X4
MWxy.i.5:X5
MWxy.i.5:X6
MWxy.i.5:X7
WRN6_RMP_SP
WRN6_RMP_0
WRN6_PLR_SP
WRN6_PLR_THLD
MWxy.i.5:X8 WRN_PV_START
MWxy.i.5:X9 WRN_PV_PAG
MWxy.i.6
MWxy.i.7
MDxy.i.8
MWxy.i.10
MWxy.i.11
MWxy.i.12
MWxy.i.13
MWxy.i.14
MWxy.i.15
MWxy.i.16
CMD_ORDER
CMD_PARAM
CUR_PF
SEG_OUT
CUR_ITER
NB_RT_PF1
NB_RT_PF2
NB_RT_PF3
NB_RT_PF4
Process control language objects
Default value
Not applicable
Not applicable
Not applicable
Not applicable
Not applicable
Not applicable
Comment
A profile 5 dwell with 2 different setpoints
Guaranteed dwell time configured on profile 5 and
THLD zero
A profile 6 ramp with 2 identical setpoints
A profile 6 ramp at zero speed
Not applicable
Not applicable
A profile 6 dwell with 2 different setpoints
Guaranteed dwell time configured on profile 6 and
THLD zero
A bumpless start is configured on a profile or the PV address is not configured.
A guaranteed dwell time is configured on a profile or the PV address is not configured.
Reserved
Command order (single word)
Command parameter (double word)
Number of the current profile Not applicable
Not applicable
Not applicable
1
Number of the current segment
Number of the current repetition
1
1
1
Number of the profile 1 repetition
Number of the profile 2 repetition
Number of the profile 3 repetition
Number of the profile 4 repetition
415
Process control language objects
Address
MWxy.i.17
MWxy.i.18
MWxy.i.19
MWxy.i.19:X1
Parameter name:
NB_RT_PF5
NB_RT_PF6
Type of dwell
MWxy.i.19:X2
MWxy.i.19:X3
Type of dwell
Guaranteed dwell time
MWxy.i.19:X4
MWxy.i.19:X5
MWxy.i.19:X6
Dwell
Ramp type
Ramp type
0
0
Default value
1
Comment
1
0
0
Number of the profile 5 repetition
Number of the profile 6 repetition
Type of segments currently being executed
Type of guaranteed dwell time:
2 bits z z z
Bit coding:
Up: X2=0 and X1=1
Down: X2=1 and X1=0
High and Low: X2=1 and z
X1=1
No guaranteed dwell time:
X2=0 and X1=0
0
0
0
1: The guaranteed dwell time is configured or a segment is currently being executed
1: The dwell is currently being executed
1: An ascending ramp is currently being executed
1: A falling ramp is currently being executed
416
35012329 02 May 2007
Process control language objects
Process control language objects
35012329 02 May 2007
417
Process control language objects
Description This table describes the process control language objects associated with the setpoint programmer.
Address Parameter name Comment
MFxy.i.20
MFxy.i.22
SP
TOTAL_TIME
Default value
No object
No object
MFxy.i.24
MFxy.i.26
MFxy.i.28
MFxy.i.30
MFxy.i.32
MFxy.i.34
MFxy.i.36
MFxy.i.38
MFxy.i.40
MFxy.i.42
MFxy.i.44
MFxy.i.46
MFxy.i.48
MFxy.i.50
MFxy.i.52
MFxy.i.54
MFxy.i.56
MFxy.i.58
CUR_TIME
THLD_PF1
THLD_PF2
THLD_PF3
THLD_PF4
THLD_PF5
THLD_PF6
SP0_PF1
SP0_PF2
SP0_PF3
SP0_PF4
SP0_PF5
SP0_PF6
SP1
VAL1
SP2
VAL2
SP3
No object
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Calculated setpoint (output) value
Value of total time elapsed
(including freeze times)
Value of total time elapsed on the segment in progress (including freeze times)
Value of the guaranteed dwell time threshold of profile 1
Value of the guaranteed dwell time threshold of profile 2
Value of the guaranteed dwell time threshold of profile 3
Value of the guaranteed dwell time threshold of profile 4
Value of the guaranteed dwell time threshold of profile 5
Value of the guaranteed dwell time threshold of profile 6
Value of initial setpoint of profile 1
Value of initial setpoint of profile 2
Value of initial setpoint of profile 3
Value of initial setpoint of profile 4
Value of initial setpoint of profile 5
Value of initial setpoint of profile 6
Setpoint to be reached by segment
1
Value of the time or speed for segment 1
Setpoint to be reached by segment
2
Value of the time or speed for segment 2
Setpoint to be reached by segment
3
418
35012329 02 May 2007
35012329 02 May 2007
MFxy.i.70
MFxy.i.72
MFxy.i.74
MFxy.i.76
MFxy.i.78
MFxy.i.80
MFxy.i.82
Address
MFxy.i.60
MFxy.i.62
MFxy.i.64
MFxy.i.66
MFxy.i.68
MFxy.i.84
MFxy.i.86
MFxy.i.88
MFxy.i.90
MFxy.i.92
MFxy.i.94
MFxy.i.96
VAL9
SP10
VAL10
SP11
VAL11
SP12
VAL12
SP6
VAL6
SP7
VAL7
SP8
VAL8
SP9
Parameter name
VAL3
SP4
VAL4
SP5
VAL5
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Default value
0.0
0.0
0.0
Process control language objects
Comment
Value of the time or speed for segment 3
Setpoint to be reached by segment
4
Value of the time or speed for segment 4
Setpoint to be reached by segment
5
Value of the time or speed for segment 5
Setpoint to be reached by segment
6
Value of the time or speed for segment 6
Setpoint to be reached by segment
7
Value of the time or speed for segment 7
Setpoint to be reached by segment
8
Value of the time or speed for segment 8
Setpoint to be reached by segment
9
Value of the time or speed for segment 9
Setpoint to be reached by segment
10
Value of the time or speed for segment 10
Setpoint to be reached by segment
11
Value of the time or speed for segment 11
Setpoint to be reached by segment
12
Value of the time or speed for segment 12
419
Process control language objects
MFxy.i.108
MFxy.i.110
MFxy.i.112
MFxy.i.114
MFxy.i.116
MFxy.i.118
MFxy.i.120
Address
MFxy.i.98
MFxy.i.100
MFxy.i.102
MFxy.i.104
MFxy.i.106
MFxy.i.122
MFxy.i.124
MFxy.i.126
MFxy.i.128
MFxy.i.130
MFxy.i.132
MFxy.i.134
420
SP19
VAL19
SP20
VAL20
SP21
VAL21
SP22
VAL15
SP16
VAL16
SP17
VAL17
SP18
VAL18
Parameter name
SP13
VAL13
SP14
VAL14
SP15
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Default value
0.0
0.0
0.0
Comment
Setpoint to be reached by segment
13
Value of the time or speed for segment 13
Setpoint to be reached by segment
14
Value of the time or speed for segment 14
Setpoint to be reached by segment
15
Value of the time or speed for segment 15
Setpoint to be reached by segment
16
Value of the time or speed for segment 16
Setpoint to be reached by segment
17
Value of the time or speed for segment 17
Setpoint to be reached by segment
18
Value of the time or speed for segment 18
Setpoint to be reached by segment
19
Value of the time or speed for segment 19
Setpoint to be reached by segment
20
Value of the time or speed for segment 20
Setpoint to be reached by segment
21
Value of the time or speed for segment 21
Setpoint to be reached by segment
22
35012329 02 May 2007
35012329 02 May 2007
MFxy.i.146
MFxy.i.148
MFxy.i.150
MFxy.i.152
MFxy.i.154
MFxy.i.156
MFxy.i.158
Address
MFxy.i.136
MFxy.i.138
MFxy.i.140
MFxy.i.142
MFxy.i.144
MFxy.i.160
MFxy.i.162
MFxy.i.164
MFxy.i.166
MFxy.i.168
MFxy.i.170
MFxy.i.172
VAL28
SP29
VAL29
SP30
VAL30
SP31
VAL31
SP25
VAL25
SP26
VAL26
SP27
VAL27
SP28
Parameter name
VAL22
SP23
VAL23
SP24
VAL24
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Default value
0.0
0.0
0.0
Process control language objects
Comment
Value of the time or speed for segment 22
Setpoint to be reached by segment
23
Value of the time or speed for segment 23
Setpoint to be reached by segment
24
Value of the time or speed for segment 24
Setpoint to be reached by segment
25
Value of the time or speed for segment 25
Setpoint to be reached by segment
26
Value of the time or speed for segment 26
Setpoint to be reached by segment
27
Value of the time or speed for segment 27
Setpoint to be reached by segment
28
Value of the time or speed for segment 28
Setpoint to be reached by segment
29
Value of the time or speed for segment 29
Setpoint to be reached by segment
30
Value of the time or speed for segment 30
Setpoint to be reached by segment
31
Value of the time or speed for segment 31
421
Process control language objects
MFxy.i.184
MFxy.i.186
MFxy.i.188
MFxy.i.190
MFxy.i.192
MFxy.i.194
MFxy.i.196
Address
MFxy.i.174
MFxy.i.176
MFxy.i.178
MFxy.i.180
MFxy.i.182
MFxy.i.198
MFxy.i.200
MFxy.i.202
MFxy.i.204
MFxy.i.206
MFxy.i.208
MFxy.i.210
422
SP38
VAL38
SP39
VAL39
SP40
VAL40
SP41
VAL34
SP35
VAL35
SP36
VAL36
SP37
VAL37
Parameter name
SP32
VAL32
SP33
VAL33
SP34
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Default value
0.0
0.0
0.0
Comment
Setpoint to be reached by segment
32
Value of the time or speed for segment 32
Setpoint to be reached by segment
33
Value of the time or speed for segment 33
Setpoint to be reached by segment
34
Value of the time or speed for segment 34
Setpoint to be reached by segment
35
Value of the time or speed for segment 35
Setpoint to be reached by segment
36
Value of the time or speed for segment 36
Setpoint to be reached by segment
37
Value of the time or speed for segment 37
Setpoint to be reached by segment
38
Value of the time or speed for segment 38
Setpoint to be reached by segment
39
Value of the time or speed for segment 39
Setpoint to be reached by segment
40
Value of the time or speed for segment 40
Setpoint to be reached by segment
41
35012329 02 May 2007
35012329 02 May 2007
MFxy.i.222
MFxy.i.224
MFxy.i.226
MFxy.i.228
MFxy.i.230
MFxy.i.232
MFxy.i.234
Address
MFxy.i.212
MFxy.i.214
MFxy.i.216
MFxy.i.218
MFxy.i.220
MFxy.i.236
MFxy.i.238
MFxy.i.240
MFxy.i.242
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Default value
0.0
0.0
0.0
SP44
VAL44
SP45
VAL45
SP46
VAL46
SP47
Parameter name
VAL41
SP42
VAL42
SP43
VAL43
VAL47
SP48
VAL48
TIME_SEG
Process control language objects
Comment
Value of the time or speed for segment 41
Setpoint to be reached by segment
42
Value of the time or speed for segment 42
Setpoint to be reached by segment
43
Value of the time or speed for segment 43
Setpoint to be reached by segment
44
Value of the time or speed for segment 44
Setpoint to be reached by segment
45
Value of the time or speed for segment 45
Setpoint to be reached by segment
46
Value of the time or speed for segment 46
Setpoint to be reached by segment
47
Value of the time or speed for segment 47
Setpoint to be reached by segment
48
Value of the time or speed for segment 48
Value of time remaining on the current segment
423
Process control language objects
424
35012329 02 May 2007
Index
Numerics
3 single loop controller
3 single loop controllers
Default and diagnostics objects, 343
3 single loops loop controller
A
Adjust
Adjustment
Model loop controller, 212, 213, 214
Auto Selector loop
Auto-selector
Auto-selector loop
Fault and diagnostics object, 388
35012329 02 May 2007
A C
Autotuning
Duration of division too long, 160
Duration of division too short, 159
Non-mimimum phase process, 160
Process value not initially stabilized, 159
Saturation of the process value, 157
Step function parametering, 153
Stopping after a system fault, 157
B
Behavior of loops during I/O errors, 296
425
Index
Branch
Built-in functions
C
Cascade loop
Fault and diagnostics objects, 366
Command parameter
3 single loops loop controller, 309
Configuration
Control loops command word, 315
Controlling Servo output without position copy in manual mode, 293
Corrector
426
D
Dead band on deviation, 135, 146
Debug
Feed forward gain adjustment, 199
Debugging
Distribution of process control handling, 287
F
Feed forward
H
Handling process control operations according to the PLC operating mode, 290
I
Inputs
Installation
35012329 02 May 2007
L
Loop controller
Loop controllers
M
Man-Machine Interface
Model loop controller
Optimizing operation functions, 289
O
Operating modes
Optimizing processor loading, 287
35012329 02 May 2007
Output
Output address assignment, 182
Output scaling
Outputs
Index
P
Parameters
PID
Process control
Process control channels
Process control handling
Process control loop
Process control loops
Execution in automatic mode, 293
427
Index
Process loop
Error and diagnostics objects, 326
Process value
Processors
S
Servo
Automatic mode with position copy, 173
Automatic mode without copy position,
Manual mode without position copy, 175
Servo drive without output copy, 146
Setpoint
428
Setpoint programmer
Fault and diagnostics objects, 412
Setpoint programmer command word, 318
Setpoint programmer screen, 245, 246, 248,
Single loop
Synchronization
Synchronizing pre- and post- processing,
T
W
X
35012329 02 May 2007
Download