Schneider Electric TSXD24004 Reference manual
विज्ञापन
विज्ञापन
Contents
Uni-Telway - Reference Manual
Section
1.
Introduction
2.
Installation
3.
UNI-TE Services
4.
Operating Principles
5.
Appendix
Sub-section
1.1
Documentation Presentation
1.2
General
1.3
Communication Principles
1.4
Characteristics
Page
2
3
5
7
2.1
General
2.2
Implementing the Hardware
2.3
Diagnostics
3.1
General
3.2
List of Requests
4.1
Addressing System
4.2
Controlling the Uni-Telway Link
4.3
Bus Performance
5.1
Connection Block and Subscriber Socket
Coding
5.2
ASCII Code Table
5.3
Request Coding
5.4
Decimal/Hexadecimal Conversion
5.5
Connecters
5.6
Frame Code Information
72
73
74
32
33
34
18
19
21
25
31
8
12
16
1
1 Introduction
1.1
Documentation Presentation
The Uni–Telway documentation is designed for users implementing the
Uni--Telway industrial bus.
The complete documentation set and the points it covers are described below:
This Reference Manual covers:
. Uni-Telway bus operating principles,
. Bus installation and diagnostics principles,
. Procedures for communication between the various devices,
. Bus performance,
. Standard UNI-TE requests, describing those available.
Specialized User's Manuals:
Are available for each device or family of devices that can be connected to the
Un-i-Telway bus. Devices that can be connected to Uni-Telway include TSX 17,
TSX 47-20, TSX 67/87 PLCs, ATV5 variable speed drives and XBT industrial terminals. The main points covered by these manuals include:
. Product description,
. Uni-Telway implementation for each product (connection),
. How to use Uni-Telway, its features and the client/server functions,
. System and device performance,
. A description of standard device requests and, if necessary, a list of specific device requests.
A specialized A5 format manual is supplied with each device.
The Reference Manual is supplied in an A5 format binder with dividers provided for inserting the various specialized manuals. It is supplied with the TSX SCM 21.6
Uni-Telway module.
XBT-B8
ATV.5
TSX
UNI-TELWAY
TSX
Uni-Telway Bus
Reference Manual
TSX
TSX 17 ACC5
Uni-Telway Adapter for TSX 17-20 Micro-PLCs
TSX
TSX SCM 21.6 Channel 1
Uni-Telway Bus
User's Manual
2
1 Introduction
1.2
General
Uni-Telway
Used as a multidrop bus, Uni-Telway is the standard means of communication between Telemecanique's control devices including: PLCs, operator dialog terminals, variable speed drives, numerical controls, weighing indicators.
Uni-Telway can also simplify communication with devices from other vendors, such as supervision and control computers.
Uni-Telway can be used for two types of application:
. Control and surveillance of system devices by PLC
Devices such as ATV5 variable speed drives, LT8 protection relays, ASN specialized couplers, numerical controls.
ALTIVAR 45
ATV 45
Variable speed drive
XGS On
On
L1
L2
DEF1
DEF2
IN1
IN2
OUT1
OUT2
XGS
Inductel
NUM 760
Numerical control
NUM 760
TSX 47-30
UNI-TELWAY
. Man-Machine dialog and supervision
Devices such as XBT operator dialog terminals or Monitor 77 and the capacity to support open communications with networks and computers from other vendors.
TSX 47-30
MONITOR 77
TSX 47-30
CONTRAST DEGAUSS ON.OFF
Reset
Keyboard
ON
OFF
UNI-TELWAY UNI-TELWAY
Uni-Telway requires:
. 1 Master
This device supervises the data link and checks its operation. It controls the allocation of bus access time to the various connected stations. This entity comprises a modular TSX Series 7 PLC equipped with a TSX SCM 21.6 serial communication module.
. 1 to 27 slaves
3
1 Introduction
General (Cont'd)
Uni-Telway's transparent, peer to peer type of communication permits the transmission of messages from master to slave, slave to master and slave to slave without the need for any application program in the master.
a
Master bus controller
(with TSX SCM 21.6 module) b c
Slave
1
Slave
2
Slave
3
Slave n
Slave to slave communication involves two steps that are automatically synchronized:
. message transmission to the master module: from slave 2 to the TSX SCM 21.6,
. automatic message routing to the destination address: from the TSX SCM 21.6
module to slave 3 (without requiring involvement of the processor or the application program of the PLC of the master).
The Uni-Telway bus and its UNI-TE protocol ensure the coordination of activity between the various intelligent devices:
. application to application communication, between PLCs for example (text block to text block exchange),
. application to device communication, reading data bits, words, controlling operating modes, for example.
4
1 Introduction
1.3
Communication Principles
Uni-Telway is fully integrated into the TSX Series 7 Communication architecture.
This architecture corresponds to the OSI model with an application layer (UNI-TE) and a network layer (addressing system) that are common to various communication interfaces: programming port, Telway 7 network and Uni-Telway industrial bus.
The presentation, session and transport layers (6, 5 and 4) are not supported as they are seldom used in automation applications.
7
APPLICATION
6
PRESENTATION
5
SESSION
4
TRANSPORT
3
NETWORK
2
DATA LINK
1
PHYSICAL
UNI-TE
TE NETWORK
PROGRAMMING
PORT
TELWAY 7 UNI-TELWAY
Uni-Telway
. The UNI-TE application layer
This is a list of requests that are common to all devices (standard requests) or specific to one device (specific PLC or NC requests).
The following services are supported:
- read/write data objects (bits, words, etc.),
- control of operating modes (INIT, RUN, STOP),
- bus and device diagnostics,
- file and program up/download.
. The TSX7 network layer
This layer ensures all message routing functions to ensure that the message travels from the sender to the destination address. Each entity is identified by its own network address.
5
1 Introduction
Communication Principles (Cont'd)
. The Uni-Telway data link layer
This layer controls access to the bus by the various devices through a master/ slave procedure. A slave is identified by its data link address(es). The fixed master allows sequential access to the bus and allocates the line to any slave address.
. The Physical Layer
An RS-485 isolated multidrop bus with a standard speed of 9600 bps that can interconnect 2 to 28 devices on a trunkline of up to 1000 meters in length to which drops of up to 20 meters can be connected.
6
1 Introduction
1.4
Characteristics
Physical Layer
Topology
Interface
Bus cable
Bus length
Drop length
Number of devices
Speed
Character format
- bus,
- RS-485 isolated,
- shielded, double twisted pairs,
- cable resistance: 85 ohms/km,
- shield resistance: 12 ohms/km,
- capacitance between conductors: 100pF/m,
- characteristic differential impedance: 85 ohms,
- attenuation per km: 13 dB/km from 0 to 20kHz.
- 1000 meter trunkline, excluding drops,
- 20 meters max.,
- 28 max. connected to the bus,
- 9600 bps standard (configurable up to 19200 bps, depending on the device (refer to the appropriate documentation),
- 8 data bits,
- odd parity,
- 1 stop bit.
Data Link Layer
Data link
Access method
Checks
- asynchronous serial link,
- fixed master,
- polls up to 255 slave data link addresses (a single device can use several data link addresses).
- BCC,
- Retries.
UNI-TE Application Layer
Messages - Peer to peer message exchange, 128 characters max.
7
2 Installation
2.1
General
Uni-Telway Bus Connection
The Uni-Telway bus is an isolated RS-485 line that must be fitted with a line adapter or terminator at one end. There are two ways of connecting to the bus:
. by daisy-chaining the devices together (as shown by device B in the example),
. by T-Junction and passive drops, as shown by device C in the example, making the connection of intermediate devices easier.
≤
1000 m
≤
20 m
Device a
Device b
Device c
Device d
Connection Accessories
Various accessories are available for connecting devices to the Uni-Telway multidrop bus.
TSX SCA 50 Tap Junction
This component is a passive junction box containing a printed circuit board fitted with three sets of screw terminals. It connects a device via a passive drop to the main Uni-Telway trunkline. It can be mounted anywhere on the bus (e.g. in the cable duct). It ensures:
. electrical signal continuity in all three directions including shielding,
. end of line terminating when it is located at the end of the trunkline.
Telemecanique
TSX SCA 60/61 Connection Blocks
For connecting standard Uni-Telway devices (TSX SCM, XBT, NUM, VW3
A45 103 coupler, etc.) with 1 15-pin male
D-type connecter in either a daisy-chain or multidrop layout. Designed for use with devices such as VW3 A45 103 couplers for variable speed drives. Address coding is set by the micro-switches located in the connecters. In addition, the TSX SCA 61 acts as an end of line terminator.
TSX SCA 60 TSX SCA 61
The pin arrangement for these connecters is shown in the Appendix (Sub-section
5.1).
8
2 Installation
General (Cont'd)
TSX SCA 62 Subscriber Socket
This component is a passive Y-junction box containing a printed circuit board fitted with screw terminals and 2 15-pin female connecters. It is used to connect two devices that cannot use TSX SCA 60 and TSX SCA 61 Connection Blocks to the
Un-Telway bus. Included in this unit are:
. bus address coding for both devices,
. end of line terminating when it is located at the end of the trunkline.
Telemecanique
THIS DEVICE CODES THE ADDRESS, THEREFORE THE DISTANCE BET-
WEEN THE SOCKET AND THE DEVICE IS RESTRICTED TO 1.5 METERS.
TSX SCA 72 Adapter box
An active component for connecting equipment not fitted with an RS-485 interface, but which does use the higher layers of the protocol to connect to the
Uni-Telway bus. This box adapts RS-232-/RS-485 signals (electrical adaptation and signal isolation).
It does not provide address coding for the devices, nor will it provide end of line terminating).
Uni-Telway bus
Télémécanique
A shielded, double twisted pair cable is used. It is available in three different lengths:
. TSX CSA 100
. TSX CSA 200
. TSX CSA 300 length 100 meters, length 200 meters, length 500 meters.
Connection Cables
. Standard connection cable TSX CSE 015.
This cable is used to connect a TSX SCA 62 and any device fitted with a 15-pin connecter that meets the requirements described in the Appendix, Sub-section
5.1).
. Special connection cables
These cables are used to connect various devices to the TSX SCA 62
Subscriber Socket. These cables are described in the documentation supplied with each product.
TSX CSB 015
XBT Z908
TSX SCA 62 <--> TSX SCM 21.6 (15-pin/25-pin, len. 1.5m)
TSX SCA 62 <--> XBT 8...
(15-pin/25-pin, len. 1.5m)
TSX M77CB2 015 TSX SCA 62 <--> Monitor 77
TSX CSB 015 TSX SCA 62 <--> TSX 17 ACC5
(15-pin/15-pin, len. 1.5m)
(15-pin/15-pin, len. 1.5m)
9
2 Installation
General (Cont'd)
Connecting the Devices
Daisy-chain connection
When the subscriber socket (or the cable connecter) is directly connected to the
Uni-Telway bus trunkline. The TSX SCA 62 Subscriber Socket ensures device address coding.
Example of connection to a PLC
TSX 87-30
UNI-TELWAY
TSX SCM 20
OK
F
3
TSX SCM 21.6
Ch0
5
Ch1
TSX CSB 015
1.5m
Telemecanique
TSX SCA 62
Subscriber Socket
Drop connection
This kind of connection requires that the drop cable be the same as the main
Un-Telway cable and that its length not exceed 20 meters.
Signal continuity, including that of the shielding is ensured by the junction box.
Address coding is set in the TSX SCA 60 Connection Block.
Example of connection to an ATV 45 variable speed drive.
ALTIVAR 45
ATV 45
Variable speed drive
UNI-TELWAY
VW3 A45 103
Coupler
Télémécanique
Telemecanique
TSX SCA 50
TSX SCA 60
It is possible to combine the various types of connections on the same Uni–Telway bus.
10
2 Installation
General (Cont'd)
End of Line Terminating
The Uni-Telway bus must absolutely be fitted with an end of line terminator at each end of the line. The TSX SCA 50 Tap Junction and the TSX SCA 62 Subscriber
Socket can be set by jumper to provide line terminator functions. The TSX SCA 61
Connection Block has a built-in end of line terminator. The terminator ensures end of line impedance matching.
Terminator location examples
TSX SCA 50
TSX SCA. 00
TSX SCA 62
Terminator
TSX SCA 62
Terminator
Device Device Device
TSX SCA 50
Device
TSX SCA. 00
TSX SCA 62
Device
TSX SCA 61
(Terminator)
Device
Connection Examples
TSX Series 7 PLC
TSX SCA 62
Telemecanique
Device
TSX 87
Device
TSX SCA 60
Device
TSX 7 PLC -> XBT B8 Terminal
XBT B8 TSX 87
Device
TSX CSB 015
TSX 17 PLC
UNI-TELWAY
XBT Z918
TSX SCA 62
Telemecanique
TSX CSC 015
TSX 17
11
2 Installation
2.2
Implementing the Hardware
Installing the Line
Within the same facility no special precautions need be taken when installing the cable. The cable must never be run on the outside of a building.
Over long distances, avoid running the cable close to high voltage lines.
The term Uni-Telway line refers to the bus cable with a trunkline of up to 1000 meters, to which drops of up to 20 meters can be connected.
Connecting the Shield
The shield should be grounded through the connecter and the ground on each device.
When remote devices are connected, to meet electrical safety requirements and ensure protection of personnel, it is necessary to check the voltage level between the various grounding points. Having a difference in the voltage level between the various points on the bus can cause personnel and equipment safety hazards.
If any such problems occur, improve the quality of the grounding.
TSX SCA 50
Mounting:
This unit can be mounted on an AM1
PA.. mounting plate.
AM1 - PA..
=
2 x Ø5.5
50 End of line terminator
When the TSX SCA 50s are directly connected to a device at the end of the line then end of line terminating must be selected by setting the jumper to the ON position as illustrated opposite
(The device is supplied with the jumper set to the OFF position).
=
ON
OFF
Wiring
Position the seals supplied and connect to the bus as shown in the figure opposite.
Shield
OVL OVL D(A) D(B)
1 2 3 4
White Red White Blue
5
Insulating sleeve
(mandatory)
12
2 Installation
Implementing the Hardware (Cont'd)
TSX SCA 60/61
Mounting
These connection blocks are mounted on the device to be connected to the
Uni-Telway bus.
Addressing
The address of a device on the Uni-
Telway bus is coded by setting the microswitches located on the printed circuit board.
The code value is set by moving the switches to the OFF position.
The addressing system switches are assigned binary weights of 1-2-4-8-16.
Each switch set to OFF takes a binary value of 1 (0 for ON).
The address is used with a parity switch that must always be set to ensure that an odd number of switches are set to OFF.
The example opposite shows the coding for addresses 5 and 11. For additional information refer to Subsection 5.2 in the Appendix where the coding for all addresses from 0
(master) to 31 (slave) are listed.
TSX SCA 60
Parity
Binary weight
ON OFF
TSX SCA 61
ON OFF
Address
ON
1 2 3 4 5 6
P 16 8 4 2 1
OFF
End of line terminator
End of line terminating is automatically provided by the TSX SCA 61
Connection Block.
Device 5
ON
1 2 3 4 5 6
P 16 8 4 2 1
OFF
Device 11
1 2 3 4 5 6
P 16 8 4 2 1
ON
OFF
Wiring
Shield
Position the seals supplied and connect to the bus as shown in the figure opposite.
Insulating sleeve
(mandatory)
OVL OVL D(A) D(B)
1 2 3 4
White Red White Blue
5
13
2 Installation
Implementing the Hardware (Cont'd)
TSX SCA 62
Mounting
This unit can be mounted on an AM1
PA.. mounting plate or an AM1 DE/DP
Omega rail with mounting plate LA9
D09976.
35
=
2 x Ø5,5
50
=
Addressing
The address of a device on the Uni-
Telway bus is coded by setting the microswitches located on the printed circuit board.The code value is set by moving the switches to the OFF position.
The addressing system switches are assigned binary weights of 1-2-4-8-16.
Each switch set to OFF takes a binary value of 1 (0 for ON).
The address is used with a parity switch that must always be set to ensure that an odd number of switches are set to
OFF.
Parity
Binary weight
The example opposite shows the coding for addresses 5 and 11. For additional information refer to Sub-section
5.2 in the Appendix where the coding for all addresses from 0 (master) to 31
(slave) are listed.
Device 5
End of line terminator channel 2
1 2 3 4 5 6
ON
OFF
SW2
ON
OFF channel 1
SW1
ON
OFF
Address
1 2 3 4 5 6
P 16 8 4 2 1
Master
1 2 3 4 5 6
P 16 8 4 2 1
Device 11
1 2 3 4 5 6
When the subscriber sockets are directly connected to a device at the end of the line, terminating must be provided.
Set the jumper to the ON position as shown opposite. (As supplied, devices are set to the OFF position).
P 16 8 4 2 1
ON
OFF
P 16 8 4 2 1
SW1
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Wiring
Position the seals supplied and connect to the bus as shown in the figure opposite.
Shield
1
OVL OVL D(A)
2 3 4
White Red White Blue
D(B)
5
Insulating sleeve
(mandatory)
14
2 Installation
Implementing the Hardware (Cont'd)
TSX SCA 72
The TSX SCA 72 Adapter Box comprises:
. an RS-232/Uni-Telway adapter box,
. a mains power cord.
Configuration
The TSX SCA 72 Adapter Box is factory configured for a 220V supply, be sure to change this setting if necessary, before powering-up, as an incorrect configuration can terminally damage the device. To check the position of the switches and jumpers proceed as follows:
Remove the cover from the box, then:
Select the position of switch S4 (220V or 110V) as necessary.
Check that the 5 dip-switches and the
3 jumpers are set as shown opposite.
6
5
8
7
X6
3
4
1
2 1
2
3
X7
ON
S5
Connecting a TSX SCA 50 and TSX SCA 72
This connection uses a TSX CSA .00 available from Telemecanique.
OFF
LINE
OVL
OVL
D(A)
D(B)
J1/J2/J3
Shield
1
White
2
Red
3
White
4
5
Blue
White
Blue
White
Red
1
2
3
4
5
D(A)
D(B)
OVL
TSX SCA 50
TSX SCA 72
As end of line terminating is automatically ensured by the TSX SCA 72 Adapter
Box, the terminator jumper from TSX SCA 50 must be set to OFF, even if located at the end of the line.
Connecting a TSX SCA 72 and an RS-232 Device
The type of cable selected depends on the device to be connected. The cables listed below are available from Telemecanique:
. TSX CSF 050 (2 male 25-pin connecters),
. TSX M77 CB0 615 (1 male 25-pin connecter and 1 female 15-pin connecter, used to connect Monitor 77).
15
2 Installation
Implementing the Hardware (Cont'd)
2.3 Diagnostics
General
The TSX TS4 310 Uni-Telway operating cartridge simplifies implementation and maintenance of the Uni-Telway bus and the devices connected to it.
This multilingual cartridge can be installed in any
TSX T407 terminal which itself can be connected to the programming port of any TSX Series 7 PLC.
In addition to its Uni-Telway diagnostics, the cartridge can also be used to access the PL7-1, PL7-2,
PL7-3 addressable objects in all TSX Series 7
PLCs (from the TSX 17 to the TSX 87).
Telemecanique
TSX TS4 31
Uni-Telway Function
A TSX T407 terminal with a TSX TS4 310 Uni-Telway operating cartridge, connected to any PLC enables the user to:
. Identify Uni-Telway master or slave modules installed in the PLC,
. Read and change the configuration of these modules,
. Perform data link diagnostics (read and reset the transmission error counters for each module).
If the terminal is connected to a Uni-
Telway bus master PLC, it can in addition:
. Display a list of stations present on the bus,
. Logically connect each slave to the bus (data link addressing), for:
. Identification of the type of device connected at this address,
. Data link diagnostics (error counter contents) as seen by this device,
. Access to normal PLC operating functions if one of the devices connected to the data link is a TSX Series 7 PLC. The functions available are listed on the next page:
16
2 Installation
Implementing the Hardware (Cont'd)
Operating Function
The TSX TS4 310 cartridge provides the following services for TSX Series 7
PLCs.
Connection
It is possible to connect to a local or remote PLC via a Telway 7 network.
Adjust Mode
. displays all bits, words and function blocks,
. forces I/O bits and internal bits,
. blocks PL7-3 Grafcet steps.
Diagnostic Mode
. displays the processor module front panel indicator data,
. displays the status of the I/O racks and whether or not any faults are present.
Control Mode
. RUN, STOP, INIT,
. displays the list of active steps.
Transfer Mode
. stores (or restores) programs (via Uni-Telway with TSX 17-20 and TSX 47-20) and Adjust mode parameters (for any TSX Series 7 PLC). Storage can be made to the TSX T407 terminal or a tape recorder connected to it.
For further details on the characteristics and the operation of this cartridge, refer to the TSX T407 Adjustment Cartridge Manual.
17
3 UNI-TE Services
3.1
General
Presentation
The Uni-Telway application layer provides a single communication interface for all devices supplied by Telemecanique or other vendors that support the UNI-TE protocol.
The application layer provides standard services can be completed by additional services specific to PLCs, Numerical Controls, Machine Tools, Robots etc.
Most of the implementation steps for these services are implemented by a question and answer dialog called REQUEST/CONFIRM.
Dialog Sequencing
A device that supports the UNI-TE protocol can be a:
CLIENT:
SERVER:
This device initiates communications. It asks a question (reads), sends an answer (writes) or an order (Run, Stop, etc.).
This device executes the order sent by the client and sends a confirm after execution.
1 Request
CLIENT SERVER 2 Action
3 Confirm
Some devices can be both Client and Server. A PLC, for example is a server for its system tasks (program, adjust, diagnostics). It is also a Client of other PLCs
(and machine tool numerical controls, sensors, actuators) via the user program text blocks (when sending commands, reading status data).
TSX 7
Request Request
TX T
XBT 8 SYSTEM
ATV 5
SLAVE
CLIENT
Confirm
SERVER
MASTER
CLIENT
Confirm
SLAVE
SERVER
Important: Being a Client or Server is completely separate from the master/slave relationship on the bus.
18
3 UNI-TE Services
3.2
List of Requests
The standard requests that are listed in detail in the Appendix (Sub-section 5.4) with their coding, provide the following services:
Variable Management
These requests enable access to bits, words or other standard data objects (bit string, word string, etc.) or specific data objects in both read and write modes.
The requests most often used are:
. read bit (R),
. read word (W),
. write bit (B),
. write word (W),
. read data objects,
. write data objects.
Unsolicited Data
This is the only service that does not generate a confirm as it is already a response to an implicit question.
This service will transfer a byte string from the application program without it having been requested first.
The actual use of this data is up to the destination device, that is implicitly awaiting this data.
CLIENT SERVER
APPLICATION
Unsolicited data
APPLICATION Event
Data Link and Device Management
These requests are supported by all Uni-Telway devices. They are especially useful for diagnostics and on power-up (device and application protocol identification, system and communication path tests, etc.).
. identification,
. protocol version,
. read status,
. mirror,
. communication control.
19
3 UNI-TE Services
List of Requests (Cont'd)
Operating Mode Management
These requests are used to run or stop a device connected to the bus. They can also perform initialization and run a self-test sequence.
. Run,
. Stop,
. Self-test,
. Init.
Semaphore Management
These requests are used for device reservation, dereservation or hold reservation functions. Some requests (identification, read variables, etc.) can be used simultaneously by two clients. Other requests (e.g. up/download) require mutual exclusion mechanisms that are controlled by the semaphore management requests.
. reservation,
. dereservation,
. hold reservation.
File Transfer
These requests allow a client device to upload or download blocks (segments) of data, program or other information to or from a server. There are 3 steps in the implementation of this service, once the server has been reserved:
1 Establish a sequence that defines the type of service (up or download) and identify the data to be transferred,
2 Start the sequence on command from the client,
3 End the up/download sequence.
. initialize upload,
. upload a segment,
. end upload,
. initialize download,
. download a segment,
. end download.
Request File
These requests enable a list of requests to be stored and executed. Once execution is complete, the client can read the data received in a confirm file. This gives a coherent picture of the data that cannot normally be accessed with a single request. This service requires that the server be reserved first.
. write the request file,
. read the request file,
. execute the request file,
. clear the request file.
Note: All devices do not necessarily support all requests. Refer to the appropriate product documentation to know which standard requests are supported, what their specific parameters are and how they affect the device.
20
4 Operating Principles
4.1
Addressing System
General
In the Telemecanique communication architecture, all message exchanges are made in peer to peer mode between two logical entities (client and server). The logical entities must be identified by a unique address that is only used once in the entire architecture. The sender and the destination addresses are sent with each message.
Sender
Address
Destination
Address
MESSAGE
In the Telemecanique addressing system that is based on TSX Series 7 PLCs, the sender and destination addresses are encoded in 5 bytes:
. network number,
. station number,
. gate number,
. module number,
. channel number.
The network and station number bytes are used to identify the devices connected to the Telway 7 network.
Network Number
The network number provided for multiple network extensions. If a single
Telway 7 network is used, the network number is set to 0.
Station Number
This corresponds to the station number of the device connected to the Telway 7 network (H'00' to H'0F').
FOR STANDALONE STATIONS THAT ARE NOT CONNECTED TO A TELWAY 7
NETWORK, THE BYTES CORRESPONDING TO THE NETWORK AND
STATION NUMBERS MUST TAKE VALUES OF H'00' AND H'FE'
RESPECTIVELY.
Gate Number
The gate number identifies the following logical devices:
System :
Terminal :
For communication with preprogrammed functions allowing access to PL7 data objects in TSX Series 7 PLCs.
Gate number = H'00'.
For communication with PLC programming terminals.
21
4 Operating Principles
Addressing System (Cont'd)
Text block : To communicate with application programming terminals. The corresponding gate number is H'10' + text block number (in Hex).
Examples: TXT3 corresponds to gate H'13',
TXT12 corresponds to gate H'1C'.
Modules : To communicate with all of the intelligent modules in a PLC and especially with TSX SCM 21.6 Uni-Telway modules.
Gate number is H'05'.
Module Number
Once the module gate number (H'05') has been selected, the module number (in
Hex.) gives the location of the module in the rack.
Examples: H'03' corresponds to rack 0, slot 3,
H'27' corresponds to rack 2, slot 7.
The module number can also take the value H'FE' by default (e.g. Uni-Telway slave to Uni-Telway slave).
FOR PROGRAMMING PORT, TEXT BLOCK AND SYSTEM GATE, THE
MODULE NUMBER IS NON-SIGNIFICANT AND MUST BE SET TO H'00'.
Channel Number
The channel number identifies the various module logical devices. This is used in TSX SCM 21.6 modules in particular. The channel number corresponds to the link address of Uni-Telway slaves, incremented by H'64':
THE CHANNEL NUMBER IS NON-SIGNIFICANT FOR SYSTEM GATES,
PROGRAMMING PORTS AND TEXT BLOCKS. ITS VALUE MUST BE H'00'.
Examples: link address 1 --> channel nbr. = H'65', link address 7 --> channel nbr. = H'6B'.
Addressing Examples
In the case of a standalone PLC:
Address of slave CNC nbr. 2 on the Uni-Telway bus. The TSX SCM 21.6 master module is located in Rack 0, slot 3.
Network nbr.
= H'00'
Station nbr.
= H'FE'
Gate nbr.
Module nbr.
=
=
H'05'
H'03'
Channel nbr.
= H'66'
ATV 45
Variable speed drive
1
MASTER
UNI-TELWAY
ALTIVAR 45
2
NUM 760
NUM 760
22
4 Operating Principles
Addressing System (Cont'd)
Addressing Examples
For a Telway 7 Network:
Network
Station 4
Station 4
TELWAY 7 (network 0)
Station 7 Station 12
Gate System
0
Terminal
Intelligent
Module
5
TXT 0 TXT 4 TXT i
10 + i
Module
Channel
1
Dev.
A
UNI-TELWAY
2
Dev.
B
3
Dev.
C
Device B on Uni-Telway
(data link address 2)
Network nbr.
= H'00'
Station nbr.
= H'07'
Gate nbr.
Module nbr.
=
=
H'05'
H'04'
Channel nbr.
= H'66'
TXT4 in PLC nbr. 7 on
Telway 7
Network nbr.
= H'00'
Station nbr.
= H'07'
Gate nbr.
Module nbr.
=
=
H'14'
H'00'
Channel nbr.
= H'00'
Master
0-4
(Rack, Slot)
2-7
PLC system gate 12 on
Telway 7
Network nbr.
= H'00'
Station nbr.
Gate nbr.
= H'0C'
= H'00'
Module nbr.
= H'00'
Channel nbr.
= H'00'
23
4 Operating Principles
Addressing System (Cont'd)
Application to Uni-Telway
A Uni-Telway slave can access the complete architecture controlled by the master:
. another slave on the Uni-Telway bus,
. a logic gate (system, text block) on the master,
. a PLC connected to the master via Telway 7.
Addressing Examples
1) Slave to Slave on Uni-Telway
MONITOR 77
Address:
Network nbr.
Station nbr.
Gate nbr.
Module nbr.
Channel nbr.
sender
H'00'
H'FE'
H'05'
H'FE'
H'65' destination
H'00'
H'FE'
H'05'
H'FE'
H'66'
The network, station, gate and module numbers take the default values. The channel numbers correspond to the sender and destination data link addresses.
2) Slave to PLC via Telway
TSX 47
Master
CONTRAST DEGAUSS ON.OFF
Reset
Keyboard
ON
OFF
1
UNI-TELWAY
NUM 760
Numerical control
MONITOR 77
NUM 760
2
Address:
Network nbr.
Station nbr.
Gate nbr.
Module nbr.
Channel nbr.
sender
H'00'
H'02'
H'05'
H'02'
H'65' destination
H'00'
H'03'
H'00'
H'00'
H'00'
S2
CONTRAST DEGAUSS ON.OFF
Reset
Keyboard
OFF
ON
1
UNI-TELWAY
S1
TELWAY 7
S3
The channel numbers correspond to the sender and destination data link addresses.
Note: A Uni-Telway slave identified by its link address represents a single logical entity. This explains that when a slave has a number of logical entities, it requires multiple link addresses : one for each addressable logical device. For example a PLC requires three link addresses (system gate, client text block, server text block).
No other slave PLC logical entities can be addressed.
24
4 Operating Principles
4.2
Controlling the Uni-Telway Link
Accessing the Bus
The master polls each slave address. The number of link addresses to poll is defined in the configuration (n).
The master polls each link address in rising order.
The polling message comprises 3 characters:
2 header characters (DLE - ENQ) followed by a character giving the slave link address.
The response from the slave can be either:
. information that there is no message to send (EOT),
. a message (request or confirm) that is sent to another address.
When there is no response to a message before the time-out (TO), then the entity is declared absent. It will then be temporarily deleted from the polling list. The time-out value TO is configurable in the master.
The polling cycle is illustrated below:
MASTER
Polling 1
EOT
Link
Address 1
Polling link address i
EOT
Link
Address i
Polling link address n
EOT
Polling 1
EOT
Link
Address n
Etc...
25
4 Operating Principles
Controlling the Uni-Telway Link (Cont'd)
Sending a Message
1) Master to Slave
The bus master can send a message at any time during the "polling" cycle.
This message can be a request, a confirm or unsolicited data.
A message comprises:
. 2 header characters (DLE-STX),
. 1 character for the message destination link address,
. 1 character for the message length,
. the message itself, comprising:
. the remote address (6 bytes),
. the request code followed by data (1 to 128 characters),
. a check character (BCC).
The answer from the slave can be either:
. an acknowledgment that the message was received (ACK),
. an acknowledgment that the message was received but cannot be processed for lack of system resources (NACK).
No response after a set period of time (time-out) means that the message was incorrect or that the station was absent.
Example: Sending a message from the master to slave 1.
MASTER
Polling 1
EOT
Link
Address 1
Polling link address i
EOT
Link
Address i
Message 1
ACK
Polling n
EOT
Polling n
EOT
Etc...
Link
Address n
26
4 Operating Principles
Controlling the Uni-Telway Link (Cont'd)
Addressing
In the case of communication from the master to a slave device, the various addresses are:
Sender Address
This address is coded in 5 bytes (refer to Sub-section 4.1) and is called a remote address:
. Network number,
. Station number,
. Gate number,
. Module number,
. Channel number.
N S G
Remote address
M CHANNEL
Destination Address
This address is coded in a single byte and is the link address of the destination of the exchange.
The four Network/Station/Gate/Module bytes identify the Uni-Telway master module (TSX SCM 21.6). They are not sent on the line. The destination slave is identified by its link address only.
N S G
Implicit
Remote address
M CHANNEL
Link address + H'64'
2) Slave to Master
The slave can only send a message when it is polled by the master. This message can be a request, a confirm or unsolicited data.
A message comprises:
. 2 header characters (DLE-STX),
. 1 character for the message sender link address,
. 1 character for the message length,
. the message itself, comprising:
- the remote address (1 address type byte, 5 address bytes),
- the request code followed by data (1 to 128 characters),
- a check character (BCC).
An answer from the master that can be either:
. an acknowledgment that the message was received (ACK),
. an acknowledgment that the message was received but cannot be processed for lack of system resources (NACK).
No response after a set period of time (time-out) means that the message was incorrect.
27
4 Operating Principles
Controlling the Uni-Telway Link (Cont'd)
Example: Sending a message from slave i to the master.
MASTER
Link
Address 1
Link
Address i
Link
Address n
Polling 1
EOT
Polling i
Message 1
ACK
Polling n
EOT
Etc...
Addressing
Polling 1
EOT
In the case of communication from the master to a slave device, the various addresses are:
Sender Address
This address is coded in one byte and is the link address of the origin of the exchange.
The four Network/Station/Gate/Module bytes identify the Uni-Telway master module (TSX SCM 21.6). They are not sent on the line. These bytes are added by the master module for possible transmission to a logical entity that is not connected to the Uni-Telway bus (a station on a Telway 7 network for example).
N S G M CHANNEL
Implicit
Link address + H'64'
Destination Address
This address is encoded in 5 bytes (refer to Sub-section 4.1) and is called the remote address:
. Network number,
. Station number,
. Gate number,
. Module number,
. Channel number.
N S G
Remote address
M CHANNEL
28
4 Operating Principles
Controlling the Uni-Telway Link (Cont'd)
3) Slave to Slave
Communication between slaves is performed in two stages that are linked together automatically by the bus master (TSX SCM 21.6 module).
a) slave sending to master, b) master sending to destination slave.
These steps have already been described.
Example: sending a message from i to n.
MASTER
Link
Address 1
Link
Address i
Link
Address i + 1
Link
Address n
Polling 1
EOT
Polling i
Message for device n
ACK
Message from device i
ACK
Polling i + 1
EOT
Etc...
Connecting and Disconnecting a Device
Reminder: The master polls the link addresses from 1 to n, where n is number of link addresses declared when the master is configured.
Disconnecting a Slave
When a link address does not respond to polling from the master (caused by power break, physical disconnection, etc.), it is declared absent. Periodically, every 10 cycles, the master polls an link address again, enabling it to reconnect.
If the disconnected device is the master, then the bus can no longer operate.
Connecting a Slave
If the link address was planned in the configuration of the master, connection is automatic using the procedure described above.
If the new address was not planned, a new master configuration is required.
29
4 Operating Principles
Controlling the Uni-Telway Link (Cont'd)
Multiflow Operation
Uni-Telway allows multiflow operation. This means that a device can start an exchange on the bus even when other devices on the bus are still awaiting answers from previous exchanges.
Example:
Sending a message (request) from the bus master to:
. slave i,
. slave j.
Data is returned after the responses (confirms) have been prepared.
Polling i Polling j
Rqi Rqj Rpi Rpj
Link
Master
Prepare request i
Prepare request j
Process
Rpi
Process
Rpj
Slave i
Slave j
Generate confirm await polling i
Generate confirm await polling j
30
4 Operating Principles
4.3
Bus Performance
The application to application response time on the Uni-Telway bus is a function of:
. the Bus Cycle Time (BCT),
. the software response time of the client and server devices. This cycle time is specific to each type of device and cannot be quantified here,
. the asynchronism in client, bus and server cycle times.
The bus cycle time is the time interval between two successive polling cycles.
The cycle time depends on:
. the number of devices (link addresses) polled,
. the binary data rate,
. the device turnaround time (the time that elapses between polling and its acknowledgement),
. the number type and the length of the messages involved (master to slave, slave to master or slave to slave dialog).
The diagram below illustrates the Bus Cycle Time (BCT) without messages, for a binary data flow of 9600 and 19200 bits per second.
BCT (no message)
(mS)
400
300
A: 9600 bps
B: 19200 bps
200
100
1 4 8
Turnaround time = 5 ms.
12 16 20 24 27
Slave
Addresses
When there are messages, the bus cycle time is determined by adding the following values (expressed in milliseconds) to the times shown in the graph:
M S
S M
S S
9600 bps
24 + 1.2 N
19 + 1.2N
44 + 2.3N
19200 bps
17 + 0.6N
12 + 0.6N
29 + 1.15N
(N = Number of usable characters sent on the line).
31
5 Appendix
5.1
Connection Block and Subscriber Socket Coding
Master
ON
1 2 3 4 5 6
OFF
P 16 8 4 2 1
Device 4
ON
1 2 3 4 5 6
OFF
P 16 8 4 2 1
Device 8
ON
1 2 3 4 5 6
OFF
P 16 8 4 2 1
Device 12
ON
1 2 3 4 5 6
OFF
P 16 8 4 2 1
Device 16
ON
1 2 3 4 5 6
OFF
P 16 8 4 2 1
Device 20
ON
1 2 3 4 5 6
OFF
P 16 8 4 2 1
Device 24
ON
1 2 3 4 5 6
P 16 8 4 2 1
Device 28
1 2 3 4 5 6
ON
OFF
P 16 8 4 2 1
OFF
Device 1
1 2 3 4 5 6
P 16 8 4 2 1
Device 5
1 2 3 4 5 6
P 16 8 4 2 1
Device 9
1 2 3 4 5 6
P 16 8 4 2 1
Device 13
1 2 3 4 5 6
P 16 8 4 2 1
Device 17
1 2 3 4 5 6
P 16 8 4 2 1
Device 21
1 2 3 4 5 6
P 16 8 4 2 1
Device 25
1 2 3 4 5 6
P 16 8 4 2 1
Device 29
1 2 3 4 5 6
P 16 8 4 2 1
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Device 2
ON
1 2 3 4 5 6
OFF
P 16 8 4 2 1
Device 6
ON
1 2 3 4 5 6
OFF
P 16 8 4 2 1
Device 10
ON
1 2 3 4 5 6
OFF
P 16 8 4 2 1
Device 14
ON
1 2 3 4 5 6
OFF
P 16 8 4 2 1
Device 18
ON
1 2 3 4 5 6
OFF
P 16 8 4 2 1
Device 22
ON
1 2 3 4 5 6
OFF
P 16 8 4 2 1
Device 26
ON
1 2 3 4 5 6
OFF
P 16 8 4 2 1
Device 30
ON
1 2 3 4 5 6
OFF
P 16 8 4 2 1
Device 3
ON
1 2 3 4 5 6
OFF
P 16 8 4 2 1
Device 7
ON
1 2 3 4 5 6
OFF
P 16 8 4 2 1
Device 11
ON
1 2 3 4 5 6
OFF
P 16 8 4 2 1
Device 15
ON
1 2 3 4 5 6
OFF
P 16 8 4 2 1
Device 19
ON
1 2 3 4 5 6
OFF
P 16 8 4 2 1
Device 23
ON
1 2 3 4 5 6
OFF
P 16 8 4 2 1
Device 27
ON
1 2 3 4 5 6
P 16 8 4 2 1
Device 31
1 2 3 4 5 6
ON
OFF
P 16 8 4 2 1
OFF
32
5 Appendix
5.2
ASCII Code Table b7 → b6 → b5 → b4 →
0
0
0
0
0
1
0
0
1
0
0
0
1
1
0
0
0
0
0
1
0
1
0
1
1
0
0
1
1
1
0
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0 b3 b2
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1 b1 b0
D
E
B
C
F
9
A
7
8
Line
Column →
0
0 1 2
NUL DLE SP
1
2
SOH
STX
DC1
DC2 "
!
3
4
5
6
ETX DC3 #
EOT DC4 $
ENQ NAK %
ACK SYN &
.
-
/
,
+
*
)
(
' BEL ETB
BS CAN
HT EM
LF SUB
VT ESC
FF FS
CR GS
SO RS
SI US
3 4 5 6 7
^
_
]
\
Z
[
X
Y
V
W
T
U
R
S
P
Q
N
O
L
M
J
K
H
I
F
G
D
E
B
C
@
A
>
?
<
=
;
:
8
9
6
7
4
5
2
3
0
1 k j i h n o l m
~
DEL
}
: z
{ x y f g d e b c
\ a v w t u s r p q
33
5 Appendix
5.3
Request Coding
Family
Operating Mode
Management
Reset counters
RUN
STOP
Self-Test
INIT
Service
Variable
Management
Read a bit
Read a word
Read objects
Read structured objects
Write a bit
Write a word
Write objects
Write structured objects
Unsolicited Data Unsolicited data
Data Link and
Device Management
Device identification
Protocol version
Status
Mirror
Read error counters
Read slave status
34
10
14
37
Request Confirm
Hex.
Dec.
Hex.
Dec.
00
04
00
04
30
34
48
52
Description
Reads a bit (B).
Reads a word (W).
36 54
52
16
20
55
66
64
102 Reads objects (bits, words, bit or word strings ...).
100 Reads homogeneous or heterogeneous objects.
FE 254 Writes a bit (B).
FE 254 Writes a word (W).
35
FC
0F
30
31
53
252
15
48
49
FE 254 Writes objects (bits, words, bit or word strings ...).
FE 254 Writes homogeneous or heterogeneous objects.
_ _ Sends data without first receiving a request.
3F 63
60
61
96
97
Returns the type of device, its version and ref. nbr.
Returns version and communication protocol parameters.
Gives detailed information on the status of a device.
25
32
A4
24
33
FA
A2
250
162
FB 251 Tests the communication system and path.
D2 210 Gives a record of device data link faults.
A3 163 D3 211 Gives the number of slaves controlled by the master and their status (connected or not).
164
36
37
50
51
FE
62
FE 254 Resets a device's error counters.
FE 254 Sets a device to RUN.
63
254
98
99
Sets a device to STOP.
Device self-test.
Device initialization.
34
5 Appendix
Request Coding (Cont'd)
Family
Semaphore
Management
File Transfer
Request Files
Service
Reservation
Dereservation
Hold reservation
Initiate upload sequence
Segment upload
Terminate upload sequence
Initiate download sequence
Segment download
Terminate download sequence.
Write a request file
3D
3E
3F
2D
3A
3B
3C
Request Confirm
Hex.
Dec.
Hex.
Dec.
1D 29
1E 30
Description
FE 254 Authorizes device reservation (with time-out).
FE 254 Authorizes release of a reserved device.
45
58
59
60
FE
6A
254
106
Holds the reservation of a device.
Sets-up an upload sequence.
6B 107 Transfers a segment.
6C 108 Ends an upload sequence.
61
62
63
6D 109 Sets-up a download sequence.
6E 110 Transfers a segment.
6F 111 Ends a download sequence.
20 32
Read a confirm file
Execute a request file.
Clear a request file
21
22
23
33
34
35
FE 254 Writes a file comprising a list of requests.
51 81 Reads the content of the confirm file after executing a request file.
FE 254 Starts the execution of a request file.
FE 254 Clears a request file.
35
5 Appendix
Request Coding (Cont'd)
Syntax
Requests are defined as byte and word sets.
A byte is an 8-bit string. The least significant bit is always sent first.
A word comprises two bytes. The least significant byte is always sent first.
Standard request format
A request comprises:
. a request code (coded in hex. over 1 byte),
. a category code (sender category that defines access rights coded in hex. over
1 byte),
. the parameters and/or data (126 bytes max.).
Request
Code
Category
Code
Parameters/Data
Standard confirm format
A confirm comprises:
. a confirm code (coded in hex. over 1 byte),
. the parameters and/or data (127 bytes max.).
If the confirm is positive, the confirm code depends on the request. If the confirm is negative, the confirm code is H'FD'.
Confirm
Code
Parameters/Data
Note: Some devices will not accept messages of more than 32-bytes. In addition the path used to send the data can also be limited to 32-bytes when, for example, a Telway 7 network is used.
36
5 Appendix
Request Coding (Cont'd)
Read a Bit
This request is used to read the state of a bit (0 or 1) and whether or not it is forced.
Request format
Request
Code
Hex.
Category
Code
Bit Number
00/00
Confirm format
Positive confirm
Confirm
Code
Hex.
Value Forcing
30/48
Value
Forcing
: Comprises an 8-bit string where the address of the first bit is the highest multiple of 8 found in the number of the bit to be read.
: Comprises an 8-bit string that gives the forcing indicator of the 8 "value" bits:
. 1 if the bit is forced, where the forcing value is in the
"value" information,
. 0 if the bit is not forced.
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights,
. Bit number out of range.
37
5 Appendix
Request Coding (Cont'd)
Read a Word
This request will read a word (W).
Request format
Request
Code
Hex.
Category
Code
Word Number
04/04
Confirm format
Positive confirm
Confirm
Code
Hex.
Value
34/52
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights,
. Bit number out of range.
38
5 Appendix
Request Coding (Cont'd)
Read Objects
This request reads simple objects (words or word strings).
Request format
Request
Code
Hex.
Category
Code
Segment
Specific
Byte
Object
Address
Number of Objects to Read
36/54 (*)
(*) Device dependent
Segment
Object address
: specifies the addressing mode of the objects to be read and their location (in Hexadecimal notation):
0 : physical byte addressing,
1 : physical word addressing,
2 : physical bit addressing,
64 : internal bit location,
68 : internal word location,
99 : time location:
. object 0: universal time,
. object 1: local time.
: Physical or logical address in the segment.
Confirm format
Positive confirm
Confirm
Code
Hex.
Specific
Byte
Data
66/102 (*)
(*) Device dependent
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights,
. Unknown segment or object,
. Address out of range,
. Too many objects for the reception buffer.
39
5 Appendix
Request Coding (Cont'd)
Read Structured Objects
This request reads the state of homogeneous and heterogeneous objects.
Request format
Request
Code
Hex.
Category
Code
Segment
Object
Address
Element
Address
Quantity
34/52
Segment
Object address
Element Address
Quantity
: specifies the logical field number of objects with the same structure.
: object address in the segment.
: element address in the object.
: number of consecutive elements to read.
Confirm format
Positive confirm
Confirm
Code
Hex.
64/100
Data
Succession of Bytes
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights,
. Unknown segment or object,
. Address out of range.
40
5 Appendix
Request Coding (Cont'd)
Write a Bit
This request sets a bit to 0 or 1.
Request format
Request
Code
Hex.
Category
Code
Bit Number
Bit
State
10/16
Bit State : 0 → state 0,
1 → state 1.
Confirm format
Positive confirm
Confirm
Code
Hex.
FE/254
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights,
. Bit number out of range.
41
5 Appendix
Request Coding (Cont'd)
Write a Word
This request writes the contents of a word.
Request format
Request
Code
Hex.
Category
Code
Word Number Word Value
14/20
Confirm format
Positive confirm
Confirm
Code
Hex.
FE/254
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights,
. Word number out of range.
42
5 Appendix
Request Coding (Cont'd)
Write Objects
This request writes objects (words or word strings).
Request format
Request
Code
Hex.
Category
Code
Segment
Specific
Byte
Object
Address
Number of Objects to Write
37/55 (*)
Data
Succession of Bytes
(*) Device dependent
Segment
Object Address
: specifies the addressing mode of the objects to be read and their location (in Hexadecimal notation):
0 : physical byte addressing,
1 : physical word addressing,
2 : physical bit field,
64 : internal bit field,
68 : internal word field,
99 : time field:
. object 0 : universal time,
. object 1 : local time.
: Physical or logical address in the segment.
Confirm format
Positive confirm
Confirm
Code
Hex.
FE/254
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights,
. Unknown object,
. Address of the last object out of range.
43
5 Appendix
Request Coding (Cont'd)
Write Structured Objects
This request writes simple homogeneous and heterogeneous objects.
Request format
Request
Code
Hex.
Category
Code
Segment
Object
Address
Element
Address
Quantity Data
35/53
Succession of Bytes
Segment
Object Address
Element Address
Quantity
Confirm format
Positive confirm
Confirm
Code
Hex.
FE/254
: specifies the logical field number of objects with the same structure.
: object address in the segment.
: element address in the object.
: number of consecutive elements to write.
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights,
. Unknown segment or object,
. Address out of range.
44
5 Appendix
Request Coding (Cont'd)
Unsolicited Data
A device on the Uni-Telway bus may have to take the initiative of sending data without having first received a request and therefore having to support a client function.
This type of message does not require a confirm from the destination. Using this service reduces the data flow between clients and servers by avoiding the need for the client to systematically send requests.
As there is no answer from the destination, this service is reserved for certain types of information:
. Random data providing information, that if lost does not affect correct operation.
. Data that triggers a predictable response from the client (triggering a request/ confirm dialog between the client and the server caused by an event).
. Short, cyclically transmitted data, where recurrence is enough to ensure data coherence.
A TSX SCM 21.6 module, configured as a Uni-Telway master also provides an event triggered data service. For further information refer to the TSX SCM 21.6
Uni-Telway User's Manual.
Request format
Request
Code
Hex.
Category
Code
FE/252
File Name
Succession of Bytes
Confirm format
There is no confirm from the destination of the exchange.
45
5 Appendix
Request Coding (Cont'd)
Device Identification
This request allows the server to include device type, software version and reference number in its confirm.
Request format
Request
Code
Hex.
Category
Code
0F/15
Confirm format
Positive confirm
Confirm
Code
Hex.
Dev.
Type
Dev.
Sub-type
Dev.
Version
3F/63 (*) (*) (*)
Reference Number
ASCII Character String (**)
(*)
(**)
Device dependent,
1 byte for length, n ASCII bytes for the device reference number.
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights.
46
5 Appendix
Request Coding (Cont'd)
Protocol Version
This service identifies the version and any application protocol parameters that apply to data communication. In this request the client sends the application protocol versions that it supports, the maximum message size, the size of the request file, etc. The server then sends its own characteristics. This allows the client to send requests using a format and size that is acceptable to both parties.
Request format
Request
Code
Hex.
Category
Code
Max.
Message
Size
30/48
Length
Length
Version
Version
Succession of Bytes
: supported version number.
: list of supported versions.
Confirm format
Positive confirm
Confirm
Code
Hex.
Max.
Message
Size
60/96
Length Version
Succession of Bytes
Request
File Size
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights.
47
5 Appendix
Request Coding (Cont'd)
Status
In its confirm, the server sends a standard status message, with (if required) a device dependent status message in the data field. This provides detailed information on device status (cause of stoppage, active program, etc.).
Request format
Request
Code
Hex.
Category
Code
Required
Detail
31/49 (*)
(*) Device dependent
Confirm format
Positive confirm
Request
Code
Hex.
Current
Status
Status
Mask
61/97
Data
(*)
(*) Device dependent
Current Status : Bit 0 : System idle,
Bit 1 : Correctable error detected,
Bit 2 : Uncorrectable error detected,
Bit 3 : Check the auxiliary power source,
Bit 4 : System reset,
Bit 5 : Critical operation in progress,
Bit 6 : Stopped,
Bit 7 : Local mode.
Status Mask : Bit string. Only current status bits that have a bit of the same weight at "1" in the "Status Mask" are significant.
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights.
48
5 Appendix
Mirror
Request Coding (Cont'd)
This service tests the system and the communication path. The client sends a sequence that the server then returns to the client.
Request format
Request
Code
Hex.
Category
Code
FA/250
Data
Succession of Bytes
Confirm format
Positive confirm
Confirm
Code
Hex.
FB/251
Data
Succession of Bytes Sent by the Request
Negative confirm
There is never a negative confirm.
49
5 Appendix
Request Coding (Cont'd)
Read Error Counters
Each device keeps a log of data link faults (character, frame and protocol errors) by counting 4 types of error in counters (16-bit words):
. number of messages sent not acknowledged,
. number of messages sent and refused,
. number of messages received not acknowledged,
. number of messages received and refused.
Request format
Request
Code
Hex.
Category
Code
A2/162
Confirm format
Positive confirm
Confirm
Code
Hex.
Number of
Messages Sent not Acknowledged
Number of
Messages Sent and Refused
Nbr. of Messages
Received not
Acknowledged
Nbr. of Messages
Received and
Refused
D2/210
Caution:
Negative confirm
Confirm
Code
Hex.
FD/253
There is no counter overflow. They remain stuck at 7FFF (32767) until they are reset by a counter reset request (A4).
Reasons for rejection : . Unknown request.
50
5 Appendix
Request Coding (Cont'd)
Read Uni-Telway Slave Status
The Uni-Telway bus master controls a number of slaves (link addresses) that can be parametered. It also controls their status (connected or not). The number of slaves connected and their status can be determined using this request.
Request format
Request
Code
Hex.
Category
Code
A3/163
Confirm format
Positive confirm
Confirm
Code
Hex.
Number of
Slaves
D3/211
Slave Status
Succession of Bits
Number of Slaves
Slave Status
: Number of slaves that can be controlled, e.g.: 152 for TSX SCM 21.6 Master 152 bits = 19 bytes.
: Succession of bytes with a weight corresponding to the slave address and value to slave status:
Bit 0 : Status Slave 1,
Bit 1 : Status Slave 2,
.
.
:
:
.
.
Bit n : Status Slave n + 1.
Values:
0 : Slave Disconnected,
1 : Slave Connected.
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Controller not configured,
. Unknown request.
51
5 Appendix
Request Coding (Cont'd)
Reset Uni-Telway Diagnostics Counters
This request resets the error counters of a device.
Request format
Request
Code
Hex.
Category
Code
A4/164 0 7
Confirm format
Positive confirm
Confirm
Code
Hex.
FE/254
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights.
52
5 Appendix
RUN
Request Coding (Cont'd)
This request sets a device to Run.
Request format
Request
Code
Hex.
Category
Code
24/36
Caution: Depending on the device used, prior reservation may be required.
Confirm format
Positive confirm
Confirm
Code
Hex.
FE/254
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights,
. No reservation.
53
5 Appendix
STOP
Request Coding (Cont'd)
This request sets a device to Stop.
Request format
Request
Code
Hex.
Category
Code
25/37
Caution: Depending on the device used, prior reservation may be required.
Confirm format
Positive confirm
Confirm
Code
Hex.
FE/254
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights,
. No reservation.
54
5 Appendix
Request Coding (Cont'd)
Self-Test
This request starts a device's self-test procedure.
Request format
Request
Code
Hex.
Category
Code
Test
Type
32/50 (*)
Specific
Code
(* *)
(*)
(**)
Device dependent coding,
Field and coding are optional, depending on the type of test.
Confirm format
Positive confirm
Confirm
Code
Hex.
Result
Specific
Code
62/98 (*) (* *)
(*)
(**)
Test OK : 0
Test NOK : specific code
Specific field and coding are optional.
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights,
. No reservation.
55
5 Appendix
INIT
Request Coding (Cont'd)
This request initializes a device.
Request format
Request
Code
Hex.
Category
Code
33/51
Caution: Depending on the device used, prior reservation may be required.
Confirm format
Positive confirm
Confirm
Code
Hex.
Result
63/99 (*)
(*) INIT OK : 0,
INIT NOK : specific code.
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights,
. No reservation.
56
5 Appendix
Request Coding (Cont'd)
Reservation
This service allows a client to reserve the server device with which it wishes to dialog during critical requests (up/download, manual operation, etc.).
Caution: The station that requests the reservation must send a hold reservation request at least once every 60 seconds, otherwise the server will be automatically dereserved.
Request format
Request
Code
Hex.
Category
Code
1D/29
Confirm format
Positive confirm
Confirm
Code
Hex.
FE/254
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights,
. Reservation by another address.
57
5 Appendix
Request Coding (Cont'd)
Dereservation
As soon as the client sends this request to the server, it ceases to be reserved.
Request format
Request
Code
Hex.
Category
Code
1E/30
Confirm format
Positive confirm
Confirm
Code
Hex.
FE/254
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights,
. Reservation by another address.
58
5 Appendix
Request Coding (Cont'd)
Hold Reservation
This request must be sent at least once every 60 seconds by the entity that requested the reservation, In order to hold the reservation made. This request requires that the entity have been reserved first.
Request format
Request
Code
Hex.
Category
Code
Reserved
2D/45 FF FF
Confirm format
Positive confirm
Confirm
Code
Hex.
FE/254
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights,
. No reservation,
. Reservation by another address.
Note : A reservation will also be held automatically on receipt of any request from the sender that initially reserved it.
The hold reservation request is therefore optional.
59
5 Appendix
Request Coding (Cont'd)
Initiate Upload Sequence
This request authorizes identification of the data to upload. It requires prior reservation.
Request format
Request
Code
Hex.
Category
Code
File Name
3A/58 Succession of 8 Bytes
Confirm format
Positive confirm
Confirm
Code
Hex.
Status
6A/106 (*)
(*) Coding is device dependent.
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights,
. No reservation.
60
5 Appendix
Request Coding (Cont'd)
Segment Upload
This request uploads data from client to server. It requires prior reservation.
Request format
Request
Code
Hex.
Category
Code
Segment Number Segment Length Data
3B/59 Succession of Bytes
Confirm format
Positive confirm
Confirm
Code
Hex.
Status
Received
Segment Nbr.
6B/107 (*)
(*) Coding is device dependent.
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights,
. No reservation.
61
5 Appendix
Request Coding (Cont'd)
Terminate Upload Sequence
This request terminates the upload sequence. It requires prior reservation.
Request format
Request
Code
Hex.
Category
Code
3C/60
Confirm format
Positive confirm
Confirm
Code
Hex.
Status
6C/108 (*)
(*) Coding is device dependent.
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights,
. No reservation.
62
5 Appendix
Request Coding (Cont'd)
Initiate Download Sequence
This request authorizes identification of the data to download. It requires prior reservation.
Request format
Request
Code
Hex.
Category
Code
File Name
3D/61 Succession of 8 Bytes
Confirm format
Positive confirm
Confirm
Code
Hex.
Status
6D/109 (*)
(*) Coding is device dependent.
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights,
. No reservation.
63
5 Appendix
Request Coding (Cont'd)
Segment Download
This request downloads data from server to client. It requires prior reservation.
Request format
Request
Code
Hex.
Category
Code
Segment
Number
3E/62
Confirm format
Positive confirm
Confirm
Code
Hex.
Status Segment Number Segment Length
6E/110 (*)
(*) Coding is device dependent.
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights,
. No reservation.
Data
Succession of Bytes
64
5 Appendix
Request Coding (Cont'd)
Terminate Download Sequence
This request terminates the download sequence. It requires prior reservation.
Request format
Request
Code
Hex.
Category
Code
3F/63
Confirm format
Positive confirm
Confirm
Code
Hex.
Status
6F/111 (*)
(*) Coding is device dependent.
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights,
. No reservation.
65
5 Appendix
Request Coding (Cont'd)
Write a Request File
Once the server is reserved, this request enables writing a list of requests for execution to a buffer of up to 256 bytes max. (called TLIST). These requests are written in their usual format. The device making the request must also tell the server which buffer field is to be used for storing confirms. (The format of the TLIST buffer will be described later).
Caution: The device making the request must ensure that the list of requests and their associated answers do not overflow the space assigned to TLIST. This buffer can store up to 256 bytes max. in servers that can support this size, however a different size can be specified in the answer to the "Protocol Version" request.
Request format
Request
Code
Hex.
Category
Code
20/32
Index in the File
Data
Length
Index in the File
Data Length
Data
Data
Succession of Bytes
: This is the location in the (TLIST) buffer after which the requests to be executed are stored (refer to the buffer format),
: From one byte to the maximum (some devices can only accept lengths of less than 32 bytes),
: Shown using the following format.
Header Reserved
Reception
Buffer Index
Reserved Reserved
(*) 00 00 00
List of Requests
(Request Code ...)
End of
List
FF
Header : 00: Request File.
Reception Buffer Index : Location in the (TLIST) buffer where the confirms are stored once the requests are executed.
Important: Index value must be an even number.
66
5 Appendix
Request Coding (Cont'd)
Write a Request File (Cont'd)
Confirm format
Positive confirm
Confirm
Code
Hex.
FE/254
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights,
. No reservation,
. Request file overflow.
67
5 Appendix
Request Coding (Cont'd)
Read a Confirm File
Once the server is reserved, this request enables reading the confirm file from the
TLIST buffer.
Request format
Request
Code
Hex.
Category
Code
Confirm File
Index
21/33
Data
Length
Index in the File
Data Length
: This is the location in the (TLIST) buffer after which the requests are read,
: From one byte to the maximum (some devices can only accept lengths of less than 32 bytes).
Confirm format
Positive confirm
Confirm
Code
Hex.
Start
Confirm
Field
3A/58
Data
Start Confirm Field
Data
: 00: Confirm field full,
FF: Confirm field empty or being filled.
: Confirms sent to acknowledge requests are in standard format (code, confirm, data...).
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights,
. No reservation,
. TLIST overflow.
68
5 Appendix
Request Coding (Cont'd)
TLIST Buffer Structure
The structure of the TLIST buffer comprizing the request file to execute and its related confirms is detailed below.
Bytes 0
1
2
3
4
5
6
HEADER
RESERVED
RECEPTION
BUFFER INDEX
RESERVED
RESERVED
LIST OF REQUESTS m END OF LIST
N n + 1
255
START CONFIRM FIELD with status indicator
LIST OF
CONFIRMS
69
5 Appendix
Request Coding (Cont'd)
Execute a Request File
Once the server has been reserved, this request can be used to execute a previously written request file.
Request format
Request
Code
Hex.
Category
Code
22/34
Confirm format
Positive confirm
Confirm
Code
Hex.
FE/254
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights,
. No reservation,
. Incorrect request file.
70
5 Appendix
Request Coding (Cont'd)
Clear a Request File
After server reservation, this request can be used to clear a previously written request file.
Request format
Request
Code
Hex.
Category
Code
23/35
Confirm format
Positive confirm
Confirm
Code
Hex.
FE/254
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection : . Unknown request,
. Inadequate access rights,
. No reservation.
71
5 Appendix
5.4
Decimal/Hexadecimal Conversion
This table gives direct conversions for decimal numbers from 0 to 255 and hexadecimal numbers from H'00' to H'FF'.
C0
D0
E0
F0
90
A0
B0
40
50
60
70
80
00
10
20
30
0 1 2 3 4 5 6 7 8 9 A B C D E F
000 001 002 003 004 005 006 007 008 009 010 011 012 013 014 015
016 017 018 019 020 021 022 023 024 025 026 027 028 029 030 031
032 033 034 035 036 037 038 039 040 041 042 043 044 045 046 047
048 049 050 051 052 053 054 055 056 057 058 059 060 061 062 063
064 065 066 067 068 069 070 071 072 073 074 075 076 077 078 079
080 081 082 083 084 085 086 087 088 089 090 091 092 093 094 095
096 097 098 099 100 101 102 103 104 105 106 107 108 109 110 111
112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127
128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143
144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159
160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175
176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191
192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207
208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223
224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239
240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255
72
5 Appendix
5.5
Connecters
Pin Arrangement
The Uni-Telway interface uses a 15-pin Sub-D connecter with a metal case. A female connecter is fitted on the connected component end and a male connecter is fitted on the transmission line end.
The pin arrangement for this connecter is illustrated below:
15-pin Female Sub-D Connecter
Outside view
LINE voltage level
(insulation)
DEVICE voltage level
OVL
D(B)
Illegal
/UTW
N4
N2
N0
6
5
8
7
4
3
2
1
15
14
13
12
11
10
9
OVL
D(A)
Illegal
Address common
Parity
N3
N1
Illegal
Note: The connecter body is connected to the local protective ground (device level).
15-pin Male Sub-D Connecter
Outside view
LINE voltage level
(insulation)
DEVICE voltage level
OVL
D(A)
Illegal
Address common
Parity
N3
N1
Illegal
4
3
6
5
2
1
8
7
15
14
13
12
11
10
9
OVL
D(B)
Illegal
/UTW
N4
N2
N0
Note: The connecter body is connected to the cable shield.
Signals Exchanged
Four types of signals are exchanged via the Uni-Telway interface:
. Addressing signals N0 to N4, the parity and common line. These signals are used for coding the address of the connected device,
. The control signal (/UTW) that is connected as an input to the device and detects if the connected device is using the Uni-Telway protocol or not,
. The data signals on line D(A), D(B) and OVL,
. The shield (SHIELD).
73
5 Appendix
5.6
Frame Code Information
Reminder
A message has the following structure:
Header Link Address
Message
Length
Type of
Address.
Remote Address Data Trailer
The start of message identifier is:
. <DLE> <STX> in a selecting message,
. <DLE> <ENQ> in a polling message.
The type of addressing value is:
. H’00'
. H’20'
. H’22' for simplified addressing, for standard addressing, for service messages (requests not processed by the server).
The end of message identifier is:
. <BCC> The modulo 256 sum of bytes between <DLE> and the last data byte inclusive.
Note: Any <DLE> character included in the data field is duplicated to ensure character transparency.
In this case the second <DLE> character is taken into account when calculating the BCC value.
The other parameters are described in Section 4.
Selection Message
The data link frame is:
Master:
<DLE> <STX> <LINK ADDR.> <LENGTH> <NPDU> <BCC>
<TYPE> <REMOTE ADDR.> <TPDU>
<REQUEST CODE> <CATEGORY CODE> <DATA>
. <NPDU> : Network Protocol Data Unit,
. <TPDU> : Transport Protocol Data Unit.
Slave:
. <ACK> : Message received correctly,
. <NACK> : Message not processed,
. <EOT> : No message available (for polling),
. Silence : Incorrect message.
74
5 Appendix
Frame Code Information (Cont'd)
Interrogation Message
The data link frame is:
Master:
<DLE> <ENQ> <LINK ADDR.>
Slave:
. <EOT> : No message available,
. Silence : Incorrect message received.
<DLE> <STX> <LINK ADDR.> <LENGTH> <NPDU> <BCC>
<TYPE> <REMOTE ADDR.> <TPDU>
Examples
<REQUEST CODE> <CATEGORY CODE> <DATA>
. <NPDU> : Network Protocol Data Unit,
. <TPDU> : Transport Protocol Data Unit.
Slave:
. <ACK> : Message received correctly,
. <NACK> : Message not processed,
. Silence : Incorrect message.
Master
A
Slave
M
1
Slave
B
Master
2 3
Slave
C
Slave
31
75
5 Appendix
Frame Code Information (Cont'd)
A Master
➪
Slave
Example: TXT 8 from the master PLC to device 3.
DLE STX 03 L 20 00 FE 18 00 00 TPDU
≤
128 char.
BCC
Link Address
Message Length
Type of Addressing
: Destination
: TPDU + 6
: Standard
Remote Address
- Network
- Station
- Gate
. Text block offset
. Text block number
: Sender
: 00 by default
: FE by default
: 18 = 10 + 8
- Module
- Channel
: 00 not significant
: 00 not significant
B Slave
➪
Master
Example: Device 2 to TXT 4 of the master PLC.
DLE STX 02 L 20 00 FE 14 00 00 TPDU
≤
128 char.
BCC
Link Address
Message Length
Type of Addressing
: Sender
: TPDU + 6
: Standard
Remote Address
- Network
- Station
- Gate
. Text block offset
. Text block number
: Destination
: 00 by default
: FE by default
: 14 = 10 + 4
- Module
- Channel
: 00 not significant
: 00 not significant
76
5 Appendix
Frame Code Information (Cont'd)
C Slave
➪
Slave
Example: Device 2 to device 3.
Communication takes place in two steps that are automatically synchronized by the system tasks of the master (TSX SCM 21.6
module).
- Device 2 -> Master
- Master -> Device 3
Step 1: Device 2 to master
DLE STX 02 L 20 00 FE 05 FE 67 TPDU
≤
128 char.
BCC
Link Address
Message Length
Type of Addressing
: Sender
: TPDU + 6
: Standard
Remote Address
- Network
- Station
- Gate
- Module
- Channel
. Uni-Telway offset
. Device link address
: Destination
: 00 by default
: FE by default
: 05 = I/O module
: FE by default
: 67 = 64 + 3
Step 2: Master to device 3
DLE STX 03 L 20 00 FE 05 FE 66 TPDU
≤
128 char.
BCC
Link Address
Message Length
Type of Addressing : Standard
: Destination
: TPDU + 6
Remote Address
- Network
- Station
- Gate
- Module
- Channel
: Sender
: 00 by default
: FE by default
: 05 = I/O module
: FE by default
: 66 = 64 + 2
. Uni-Telway offset
. Device link address
77
5 Appendix
Frame Code Information
Step 1
- Device 2 to master
DLE STX 02 L 20 00 FE 05 FE 67 TPDU
≤
128 char.
BCC
Step 2
- Master to device 3
67 - 64 02 + 64
DLE STX 03 L 20 00 FE 05 FE 66 TPDU
≤
128 char.
BCC
78