Advertisement
Advertisement
LEAVE A CLEARANCE OF AT
LEAST 12” TO THE LEFT OF
THE CONTROLLER BOX TO
ALLOW FOR THE COVER TO
BE REMOVED FOR
MAINTENANCE.
12 inches
RELAY PANELS
1 2 3 4 SH
EXPERT 32T
CONTROL BOX
230V
115/230 VAC
SELECTION SWITCH
J9
CONNECTOR FOR
CONFIGURATION
MODULE
TO CABLE SHIELD
SENSOR INPUTS
OUT
1 C 2 3 C 4 5 C 6 7 C 8 9 C 10 11 12 - +
INPUT
13 C 1
PC LINK
2 3 4
ALARM
SUPPLY
115/230V
-
OUT
+
(DWYER GAUGE)
-
OUT
+
(DWYER GAUGE)
WATER PIPE WATER PIPE
WATER METER ROOM 1 (OPTIONAL)
The water meter output should be a dry contact and should not pulse faster than 60 times a second (60 Hz).
WATER METER ROOM 2 (OPTIONAL)
A 22/12 AWG gauge cable no longer than 2000 feet (0.6 km) can be used to connect the water meter. Do not use a cable longer than 2000 feet even if a larger cable is used.
DO NOT RUN THE METER CABLE OUTSIDE THE BUILDING!!
ALARM
SUPPLY
{
CONTROL
POWER SUPPLY
230 VAC (115 VAC)
RELAY PANEL RP-16DC
INSIDE TOP COVER
115/230 VAC
SELECTION SWITCH
230V
RELAY PANEL
POWER SUPPLY
230 VAC (115 VAC)
{
GREEN
WHITE
BLACK
L2/N
L1
WHITE
RED
BLACK
GREEN
TO CABLE SHIELD
RELAY PANEL
RP-16DC
USE A SHIELDED CABLE WITH TWO TWISTED
PAIRS. CONNECT THE SHIELDING TO THE SH
TERMINAL. USE ONE PAIR FOR TERMINALS 1
AND 4 AND THE OTHER PAIR FOR TERMINALS
2 AND 3.
ON-OFF OUTPUTS
1 2 3 4 5 6
7 8
RELAY PANEL
RP-16DC #2
9 10 11 12 13 14 15 16
FANS AND HEATERS ARE SHOWN
ONLY AS AN EXAMPLE.
ALL LOAD SUPPLIES ARE:
120-240 VAC, 50-60 HZ
12-24 VDC
WARNING
THE BACKUP THERMOSTAS
SHOWN ARE FOR ILLUSTRATION
PURPOSES ONLY. SUFFICIENT
BACKUP THERMOSTATS MUST
BE USED TO ENSURE
VENTILATION IF THE RELAY
PANEL LOSES POWER
L N G
1 2 3 4 SH
LOAD 9
POWER SUPPLY
{
LOAD 10
POWER SUPPLY
{
LOAD 11
POWER SUPPLY
{
LOAD 12
POWER SUPPLY
{
LOAD 13
POWER SUPPLY
{
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
THERMOSTAT
BACKUP
(NOT INCLUDED)
MAXIMUM LOAD RATINGS :
MAX VOLTAGE = 270VAC OR 30VDC
MAX MOTOR LOAD = 1HP AT 120 VAC, 2HP AT 240VAC
MAX RESISTIVE LOAD CURRENT = 15A.
THERMOSTAT
BACKUP
(NOT INCLUDED)
ON/OFF
ON/OFF
ON/OFF
{
LOAD 16
POWER SUPPLY
{
LOAD 15
POWER SUPPLY
{
LOAD 14
POWER SUPPLY
WIRING DIAGRAM
EXPERT 32T
#891-00066 Rev.04
Download
Advertisement