Cumberland EXPERT-32P Wiring Diagram
Cumberland EXPERT-32P is a versatile relay panel designed to automate and monitor various electrical systems. With its 32 programmable relays, you can easily control lighting, fans, heaters, and other devices based on time, temperature, or other triggers. The EXPERT-32P features a user-friendly control box with a large LCD display, allowing for intuitive programming and monitoring of your automated tasks. Additionally, it comes equipped with a PC link for remote access and configuration, providing you with the convenience of managing your system from your computer.
Reklama
Reklama
LEAVE A CLEARANCE OF AT
LEAST 12” TO THE LEFT OF
THE CONTROLLER BOX TO
ALLOW FOR THE COVER TO
BE REMOVED FOR
MAINTENANCE.
12 inches
EXPERT 32P
CONTROL BOX
1 C 2 3 C 4 5 C 6 7 C 8 9 C 10 11 C - +
RELAY PANELS
1 2 3 4 SH
230V
115/230 VAC
SELECTION SWITCH
-
OUT
+
(DWYER GAUGE)
1
PC LINK
2 3 4
TO CABLE SHIELD
{
CONTROLLER
POWER SUPPLY
230 VAC (115 VAC)
RELAY PANEL RP-32DC
INSIDE TOP COVER
115/230 VAC
SELECTION SWITCH
230V
RELAY PANEL
POWER SUPPLY
230 VAC (115 VAC)
{
GREEN
WHITE
BLACK
L2/N
L1
RELAY PANEL RP-32DC
ON-OFF OUTPUTS
1 2 3 4 5 6
7 8
9 10 11 12 13 14 15 16
WHITE
RED
BLACK
GREEN
TO CABLE SHIELD
17 18 19 20 21 22 23 24
USE A SHIELDED CABLE WITH TWO TWISTED PAIRS.
CONNECT THE SHIELDING TO THE SH TERMINAL. USE
ONE PAIR FOR TERMINALS 1 AND 4 AND THE OTHER
PAIR FOR TERMINALS 2 AND 3.
25 26 27 28 29 30
31 32
FANS AND HEATERS ARE SHOWN
ONLY AS AN EXAMPLE.
ALL LOAD SUPPLIES ARE:
120-240 VAC, 50-60 HZ
12-24 VDC
WARNING
THE BACKUP THERMOSTAS
SHOWN ARE FOR ILLUSTRATION
PURPOSES ONLY. SUFFICIENT
BACKUP THERMOSTATS MUST
BE USED TO ENSURE
VENTILATION IF THE RELAY
PANEL LOSES POWER
POWER SUPPLY
{
WATER PIPE
WATER METER (OPTIONAL)
The water meter output should be a dry contact and should not pulse faster than 60 times a second (60 Hz).
A 22/12 AWG gauge cable no longer than 2000 feet (0.6 km) can be used to connect the water meter. Do not use a cable longer than 2000 feet even if a larger cable is used.
DO NOT RUN THE METER CABLE OUTSIDE THE BUILDING!!
ALARM
SUPPLY
L N G
LOAD 25
POWER SUPPLY
{
LOAD 26
POWER SUPPLY
{
LOAD 27
POWER SUPPLY
{
LOAD 28
POWER SUPPLY
{
LOAD 29
POWER SUPPLY
{
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
THERMOSTAT
BACKUP
(NOT INCLUDED)
MAXIMUM LOAD RATINGS :
MAX VOLTAGE = 270VAC OR 30VDC
MAX MOTOR LOAD = 1HP AT 120 VAC, 2HP AT 240VAC
MAX RESISTIVE LOAD CURRENT = 15A.
THERMOSTAT
BACKUP
(NOT INCLUDED)
ON/OFF
ON/OFF
ON/OFF
{
LOAD 32
POWER SUPPLY
{
LOAD 31
POWER SUPPLY
{
LOAD 30
POWER SUPPLY
WIRING DIAGRAM
EXPERT 32P
#891-00065 Rev.07