HAT72 ATS CONTROLLER

USER MANUAL

ZHENGZHOU SMARTGEN TECHNOLOGY CO.,LTD

Chinese trademark

English trademark

SmartGen

— make your generator smart

SmartGen Technology Co., Ltd.

No. 28 Jinsuo Road

Zhengzhou City

Henan Province

P. R. China

Tel: +86-371-67988888

+86-371-67981888

+86-371-67991553

+86-371-67992951

+86-371-67981000(overseas)

Fax: 0086-371-67992952

Web: http://www.smartgen.com.cn/

http://www.smartgen.cn/

Email: [email protected]

All rights reserved. No part of this publication may be reproduced in any material form

(including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder.

Smartgen Technology reserves the right to change the contents of this document without prior notice.

If colors of actual products are different from those mentioned within this manual, please take the actual product as the standard.

Software Version

Version

1.0

Date Note

2007-12-01 Original release.

1.1

1.2

2015-03-11 Modify some details.

2015-04-21 Modify some details.

Clarification of notation used within this publication.

SIGN INSTRUCTION

Highlights an essential element of a procedure to ensure correctness.

NOTE

Caution!

Indicates a procedure or practice, which, if not strictly observed, could result in damage or destruction of equipment.

Warning!

Indicates error operation may cause death, serious injury and significant property damage.

HAT72 ATS CONTROLLER USER MANUAL

CONTENT

1 OVERVIEW ....................................................................................................... 5

2 PERFORMANCE AND CHARACTERISTICS ................................................... 5

3 TECHNICAL PARAMETERS ............................................................................ 6

4 DISPLAY PANEL AND OPERATING INSTRUCTIONS .................................... 7

5 TERMINAL ........................................................................................................ 9

6 CASE DIMENSIONS(cutout:67*67mm) .......................................................... 10

7 TYPICAL CONNECTIONS .............................................................................. 10

HAT72 ATS CONTROLLER 2015-04-21 Version 1.2 Page 4 of 11

HAT72 ATS CONTROLLER USER MANUAL

1 OVERVIEW

HAT72 is an Automatic Transfer Switch Control Module for 1 way mains/generator , which features 8-Bit microprocessor control. The module is used to monitor two ways of single-phase supply. Once mains supply failure (under voltage, over voltage, under frequency, over frequency) is detected, the module will control ATS to switch after delay. The controller can send out signal of starting the generator after mains failure delay.

2 PERFORMANCE AND CHARACTERISTICS

Suitable for 1 way mains and 1 way generator ATS control;

Widely power supply range: DC (8-35)V; fit with different voltage environments of start battery;

Mains or generate normal delay can be set; genset start delay can be set;

Mains abnormal delay can be set; genset stop delay can be set;

7 LEDs display the status of operation and alarm;

Transfer relay (CLOSE MAINS, CLOSE GENS) output contact rating: 16A AC250V, passive contact, directly drive the switch to transfer;

Start relay (GENS START) output contact rating: 5A AC250V, passive contact;

Close output can be set to continuous close or pulse close; when pulse close is initiated, close delay can be set.

Providing PC programming port which all delays, power thresholds needed by ATS can be set via PC;

Built-in never halted watch dog to ensure smooth program execution;

Modular design, self extinguishing ABS plastic shell, pluggable terminal, built-in mounting

,compact structure with easy installation.

HAT72 ATS CONTROLLER 2015-04-21 Version 1.2 Page 5 of 11

HAT72 ATS CONTROLLER USER MANUAL

3 TECHNICAL PARAMETERS

 DC power: (8-35)V

AC sampling input: single-phase AC(30-277)V (+20%) 50/60Hz

ATS switch output: 16A AC250V, relay passive contact;

Genset start output: 5A AC250V, relay passive contact;

2 close input ports: active when connected to B-;

Consumption: standby(12V:0.12W, 24V:0.24W), working(12V:1.5W, 24V:1.6W)

Working conditions:

Temperature: -30~+70℃ Humidity: 20~95%

Case dimensions: 72*72*52mm Cut out: 67*67mm

Weight: 0.2kg

HAT72 ATS CONTROLLER 2015-04-21 Version 1.2 Page 6 of 11

HAT72 ATS CONTROLLER USER MANUAL

4 DISPLAY PANEL AND OPERATING INSTRUCTIONS

PUSH BUTTON

Symbol Define Description

Close Mains

MAN/AUTO

Mains close button

MAN/AUTO switch button

At MAN state,push this button,ATS will turn to the mains state

Switch the state to MAN or AUTO

Close Gens

Generator button close At MAN state,push this button,ATS will turn to the Generator

LED

Symbol

Power

Auto

Manual

Mains

Normal

Define

Power led

Auto state led

Man state led

Mains normal led

Description

Lighten when DC supply

Lighten when Module at auto state

Lighten when Module at man state

Lighten when mains is normal; Flicker when mains is abnormal; Die when mains is lost.

Lighten when mains load Mains Closed Mains closed led

Gens Normal Generator normal led

Lighten when Generator is normal;

Flicker when Generator is abnormal;

Die when mains is lost.

Gens Closed Generator closed led Lighten when Generator load

Operating

Module has two states: MAN state and AUTO state: the state can be switch by MAN/AUTO button, the state can be display by Auto state led and Man state led.

MAN state

When Man state led is lighten, the module is at man state. Here, push(CLOSE Mains) button, the relay of close mains will output, push(CLOSE Gens)button, the relay of close

Generator will output.

At this state, the relay of start generator is unable.

AUTO state

When Auto state led is lighten, the module is at auto state. When mains is normal,

HAT72 ATS CONTROLLER 2015-04-21 Version 1.2 Page 7 of 11

HAT72 ATS CONTROLLER USER MANUAL

ATS will turn to the mains after the Mains Normal delay time. When mains is abnormal(under voltage, over voltage, lost voltage), after the Mains Abnormal delay time and Start generator time the relay of start generator will output and the generator will start. If the Generator is normal, ATS will turn to the Generator after

 the Gens Normal delay time.

When mains is normal, ATS will turn to the mains after the Mains Normal delay

 time.

When mains is normal, the relay of start generator will be unable and the generator will stop after the Stop generator time.

Parameters table (only adjust via PC)

Parameter Description Range(Default)

Mains delay

Gens delay normal It is the delay of Mains power from

0-3600s (10) abnormal to normal. normal It is the delay of Mains power from

0-3600s (10) abnormal to normal.

Mains abnormal delay

It is the delay of Mains power from normal

0-3600s (5) to abnormal.

Start GENS Delay

It is the delay from Mains power is abnormal to send out start generator signal.

0-3600s (1)

Stop GENS Delay

ATS close time

Transfer rest time

It is the delay from Mains power is normal

0-3600s (5) to send out stop generator signal.

Breaker close pulse. If it is set to zero, the

0-20.0s (5.0) output will held.

0-3600s (1)

Exceed Convert

After the module has received a close state input, the breaker close output continue to 0-5.0s (0)

Time held until the delay is expended.

Mains voltage

Mains voltage over The setting are used to configure the Mains

0-360V (276) power over voltage point under The setting are used to configure the Mains

0-360V (184) power under voltage point

Gens over voltage

Gens

The setting are used to configure the Gens

0-360V (264) power over voltage point under The setting are used to configure the Gens 0-360V (192)

HAT72 ATS CONTROLLER 2015-04-21 Version 1.2 Page 8 of 11

voltage

HAT72 ATS CONTROLLER USER MANUAL power under voltage point

Frequency upper limit

When the frequency of Gens power is over

40-75Hz(55.0) than the point, over frequency is active.

Frequency lower limit

When the frequency of Gens power is low

0-60Hz(45) than the point, low frequency is active.

Yes or No close input is connect

(Yes)

5 TERMINAL

 Terminal 1(B-):connect to the cathode of battery

 Terminal 2(B+):connect to the anode of battery

Terminal 3(Close Generator Input):Generator supply closed auxiliary input, connect to (B-) is active

(volts free ,5A250V)

 Terminal 6、7(Generator AC Input):Generator AC Input

 Terminal 8、9(Mains AC Input):Mains AC Input

(volts free ,16A250V)

(volts free ,16A250V)

Terminal 14(Close Mains Input):Mains supply closed auxiliary input, connect to (B-) is active

 Terminal (LINK):connect to PC by SG72

HAT72 ATS CONTROLLER 2015-04-21 Version 1.2 Page 9 of 11

HAT72 ATS CONTROLLER USER MANUAL

6 CASE DIMENSIONS(cutout:67*67mm)

7 TYPICAL CONNECTIONS

SGQ-N, T TYPE SWITCH

HAT72 ATS CONTROLLER 2015-04-21 Version 1.2 Page 10 of 11

HAT72 ATS CONTROLLER USER MANUAL

SGQ-M TYPE SWITCH

HAT72 ATS CONTROLLER 2015-04-21 Version 1.2 Page 11 of 11

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Key Features

  • Suitable for 1 way mains and 1 way generator ATS control
  • Widely power supply range: DC (8-35)V
  • Mains or generate normal delay can be set
  • Mains abnormal delay can be set
  • Genset start delay can be set
  • Providing PC programming port which all delays, power thresholds needed by ATS can be set via PC
  • Built-in never halted watch dog to ensure smooth program execution

Related manuals

Frequently Answers and Questions

What is the DC power range of the Smartgen HAT72?
The DC power range is (8-35)V.
What is the AC sampling input range of the Smartgen HAT72?
The AC sampling input range is single-phase AC(30-277)V (+20%) 50/60Hz.
What is the ATS switch output rating of the Smartgen HAT72?
The ATS switch output rating is 16A AC250V, relay passive contact.
What is the genset start output rating of the Smartgen HAT72?
The genset start output rating is 5A AC250V, relay passive contact.
What is the consumption of the Smartgen HAT72 in standby mode at 12V?
The consumption in standby mode at 12V is 0.12W.