FireNET
®
4127 - DIGITAL ANALOG ADDRESSABLE FIRE ALARM
CONTROL PANEL WITH PLEXIGLASS WINDOW
DESCRIPTION
This alternate build of the FireNET
®
4127 control panel is equipped with a Plexiglass window to meet the requirements of major cities including the City of Denver.
Access level 2 is enabled as soon as the outer door of the enclosure is opened (CAT 30 Key).
The FireNET
®
4127 control panel is an digital analog addressable fire alarm panel containing 2 or 4 SLC loops with each loop supporting 127 devices of any combination (sensors or modules), and 127 digital analog sounder bases, for a possible total of 254 points. Communication between devices is transferred through standard cable (shielded or twisted pair is not required). Each panel includes a 5.25 amp power supply and has 4 on board NAC circuits. An RS-485 bus provides communication to the panel network, while the
RS-232 interface allows the convenience of programming via a PC. The system will support a variety of Hochiki devices: photo, ion and heat sensors, which contain a unique, patented sensor design incorporating automatic drift compensation and day/night sensitivity mode. Additional devices include contact monitors, relay controllers, supervised auxiliary output and short circuit isolator modules. In addition, interfaces to conventional detection systems can be established by using a conventional zonemonitoring module. The Loop Explorer Windows ® Software interface provides the installer with fingertip access to installation programming and diagnostic tools. An Auto-learn feature offers the convenience for quick start applications.
Add to this a reputation for high quality and dedicated service makes this an exceptional product both in performance and value.
S6468
PRODUCT LISTINGS
UL 864, Local Signaling Unit.
Types: Automatic, manual, waterflow, sprinkler supervisory, Auxiliary Service (local energy), and Central Station Service,
Remote Station Service and Proprietary
Service (DACT) Non-coded signaling.
NFPA 70, 72 &13 Compliant
California State
Fire Marshal
7165-0410:159
Specifications subject to change without notice.
STANDARD FEATURES
• UL 864 9th Edition Listed
• Seismic certified
• Digital a nalog design using Hochiki’s advanced DCP protocol for fast and robust communication
• Up to 127 sensors & modules, plus 127 digital analog sounder bases, for a total of 254 points possible per loop
• Uses standard wire, no shielded or twisted pair required on SLC loops
• Supports Class B (style 4) and Class A (style 6 or 7)
SLC loops
• 4 on board Class B (style Y) NAC circuits rated at 2.5
Amps each
• Programmable sensitivity levels per device & au tomatic day/night sensitivity modes
• Automatic daily calibration & drift compensation routine
• Large 8-line x 40-character LCD (320 char.)
• 2 loop (FN-2127 Series) or 4 loop (FN-4127 Series) versions (800 addresses/sub-addr. max.)
• Dual RS-485 bus for panel network
• 2 built-in RS-232 interfaces for programming via a and serial printer interface
PC
• 5 on board programmable Form C relays rated at
1 amp at 30VDC (Fire1, Fire2, trouble, supervisory, aux.)
• 500mA of auxiliary power available rated at 24 VDC
• Loop Explorer Windows
®
configuration utility
• 500 network wide software zones
• Network capability of up to 64 panels
• RS485 slave bus for expansion - up to 32
FN-4127-IO boards or up to 15 FN-LCD-S serial annunciators and up to 17 FN-4127-IO boards
• Auto-learn feature
• Fire Drill test function
• Walk test function
• Alarm verification feature
• FireNET ® is UL listed for Central Station Service,
Remote Station Service and Proprietary Service
• Operates on 120VAC or 240VAC input voltage
• Powerful & versatile Cause & Effect programming
(up to 500 maximum, network wide) including:
*Cause & Effect action
*Disable function configuration
*Test mode configuration
Find latest revision at www.hochiki.com Hochiki America Corporation
7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714-522-2246 Fax: 714-522-2268
Technical Support: 800-845-6692 or [email protected] F0093 Rev.1 07/2017
Primary AC
Output DC
Power Supply
Charger Current
Dimensions
Weight
Color
Material
Display
Network
Zones
SLC loops
Devices per loop
Addresses per panel
NAC Outputs
Relay Outputs
Voltage Outputs
Aux. Power
Aux. Inputs
PC Port / Printer
MODEL
FN-2127-DDW
FN-2127-DDWN
FN-4127-DDW
FN-4127-DDWN
FireNET
®
4127 - DIGITAL ANALOG ADDRESSABLE FIRE ALARM
CONTROL PANEL WITH PLEXIGLASS WINDOW
SPECIFICATIONS
120VAC @ 2.1 Amps 60hz or 220VAC @ 1.1Amps 50hz
24VDC @ 5.25 Amps (4 Amps available for system power)
5.25 Amps integrated
1.5 Amps max.
14.5" W x 24" H x 5" D
31 lbs. (without batteries)
Red (optional gray)
ABS/steel enclosure
8 line x 40 character LCD (320 characters total)
Dual RS485 ports (64 panels max.)
500 network wide software zones per system
2 or 4 (class A, "style 6 or 7" or class B, "style 4")
127 sensors & modules, plus 127 digital analog sounder bases, 254 total
(800 addresses+sub-addresses max. per panel)
(4) 2.5 Amps @ 24VDC (class B)
(5) Form C 1 Amp @ 30VDC
(3) 500mA @ 24VDC
500mA @ 24VDC
(8) digital pull downs
RS232
FIRENET
®
ORDERING MODELS
DESCRIPTION
FACP (2 Loop/5.25 Amps)
FACP (2 Loop/5.25 Amps) (w/Network)
FACP (4 Loop/5.25 Amps)
FACP (4 Loop/5.25 Amps) (w/Network)
SLC COMPATIBLE DEVICES & SYSTEM ACCESSORIES
CONTROL PANEL EXPANDERS
FN-4127-SLC
FN-4127-NIC
FN-4127-IO 16
FN-DAC
FN-CTM
ANNUNCIATOR
FN-LCD-N
FN-LCD-S
SLC LOOP DEVICES
ALG-V, ALK-V, ALN-V
AIE-EA
ATG-EA, ATJ-EA
ACA-V, ACC-V
NSA-4 & NSA-6
SCI-B4 & SCI-B6
ASB
ASBL
DH-98A, DH-98AR, DH-99A, DH-99AR
MS-RA, MS-RA/R, MS-KA/R
DCP-FRCME-M
DCP-FRCME-P
DCP-FRCME-4
DCP-FRCMA, DCP-FRCMA-I
DCP-DIMM
DCP-CZM
DCP-R2M
DCP-R2ML/H Series
DCP-SOM
DCP-SOM-A, DCP-SOM-AI
DCP-SOM-R
DCP-SCI
DCP-AMS Series
ACCESSORIES
TCH-B100
FN-ACC
FNP-ETR
Dual SLC Loop Expansion Card
Network Interface Card
16 Channel Input/Output Board
Digital Alarm Communicator
City-Tie Module (Local Energy Type)
Network LCD Annunciator
Serial LCD Annunciator
Digital Analog Addressable Photoelectric Sensor
Digital Analog Addressable Ionization Sensor
Digital Analog Addressable Heat Sensor
Multi-criteria Sensor
Four Inch Sensor Base and Six Inch Sensor Base
Four Inch Short Circuit Isolator Digital Analog Sensor Base & Six Inch Circuit Isolator Digital Analog Sensor Base
Digital Analog Sounder Base
Digital Analog Low Frequency Sounder Base
Digital Analog Addressable Duct Detector Unit (DH-98AR and DH-99AR have relays built-in)
Remote Test Station for DH-98AR & DH-99AR
Contact Monitoring Module (mini w/terminal blocks)
Contact Monitoring Module (mini w/pigtail leads)
Contact Monitoring Module (with faceplate/indicating LED)
Class A Contact Monitoring Module (FRCMA-I has built-in SCI)
Dual Input Monitor Module (with faceplate/indicating LED)
Conventional Zone Module
Dual Relay Module
Dual Relay Module (R2ML-I & R2MH-I has built-in SCI)
Supervised Output Module
Class A Supervised Output Module (SOM-AI has built-in SCI)
Supervised Output Module for Releasing Pre-action System
Short Circuit Isolator Module
Addressable Manual Pull Station
Hand Held Programmer (portable device addresser)
Battery/Accessory Enclosure (houses up to 33AH size batteries)
Enclosure Trim Ring for panel flush mount
Hochiki America Corporation FireNET DIGITAL ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL Specifications subject to change without notice.