Can System User Manual

Add to My manuals
43 Pages

advertisement

Can System User Manual | Manualzz

Coachair

BMS38BX1

OPERATION, MAINTENANCE &

OVERVIEW MANUAL

Heat-Cool Model with Drivers Unit

Document Number: SM424-3381

Revision No.: 00

Issue Date: Oct 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

BMS38BX1 A/C System – Operation & Overview Manual

Rev

00

Date

Oct 30, 2006

Description

First Release, CR 12098

Released

31 October, 2006

Winfried Wirfler

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 2

BMS38BX1 A/C System – Operation & Overview Manual

NOTICE

The information in this manual is subject to change without notice.

Coachair shall not be liable for technical or editorial errors or omissions contained herein.

No part of this manual may be photocopied or reproduced in any form without prior consent from Coachair.

Coachair

Telephone:

Facsimile:

Address:

CUSTOMER SUPPORT INQUIRIES

Australia

+61 2 9830 7132

+61 2 9672 1082

3 Distillers Place

Huntingwood 2148

Australia

Malaysia

+60 3 61208760

+60 3 61208712

Lot No. 9, Jalan Empat,

Kawasan Perindustrian

Selayang, Off Jalan Besar,

Bandar Selayang,

68100 Selangor D.E. Malaysia

China

+86 519 5125568

+86 519 5113086

No. 268 West Hehai Road

Xinbei District,

Changzhou City

Jiangsu Province - P.

R.

China 213000

WEB www.aitransit.com

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 3

BMS38BX1 A/C System – Operation & Overview Manual

IMPORTANT INFORMATION

Use R134a Refrigerant Only!

The A/C system is designed for use with R134a refrigerant. Do not use any other refrigerant.

The use of any other refrigerant may result in damage to the A/C unit and/or compressor.

WARNING

WARNING

Use Ester Oil Only!

The A/C system is designed for use with ester compressor oil. Do not use any other lubricating oil. The use of incorrect oil may result in damage to the A/C unit and/or compressor.

WARNING

*

NOTE

Handle Electronics With Care!

Do not attempt to remove, repair, or handle the climate control panel or any components in any way without referring to the correct procedures. The electrical control panel houses sensitive equipment that may be damaged if handled incorrectly.

Refer to the CCC007* Climate Control System Manual for electronics service details.

,

CAUTION

Temperature Probes

Each temperature probe in the unit is factory calibrated. Use Probes as they have been allocated.

DO NOT swap or mix the probes, as this may lead to unit damage and faulting.

,

CAUTION

24V DC ONLY

This unit is designed for a 24V DC electrical circuit ONLY. Do not under any circumstances use another voltage, as this may cause unit damage and faulting.

There is power to the motors all the time. Never attempt to do repairs on motors or motor wiring without manually breaking the correct circuit breaker first.

WARNING

,

CAUTION

Black Heat Sink

The black heat sink built onto the ESP109 PCB is at earth potential. DO NOT, under any circumstances, place an earth or a bridge circuit on the heat sink, as this will cause serious unit damage.

,

CAUTION

DO NOT use a test light. Use a suitable multimeter only!

,

CAUTION

DO NOT push the red reset button for more than 2 seconds, as this could provide unintentional access to the CCC007* memory settings.

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 4

BMS38BX1 A/C System – Operation & Overview Manual

CONTENTS

SECTION 1: - System Details ............................................................... 6

1.1 Introduction ..................................................................................................... 6

1.2 Specifications ................................................................................................... 7

1.3 System Layout ................................................................................................. 8

1.4 System Parameters .......................................................................................... 9

1.5 Air Flow ......................................................................................................... 11

1.6 Refrigeration System....................................................................................... 13

1.7 Heating System .............................................................................................. 17

1.8 Electrical System ............................................................................................ 17

SECTION 2: - Installation ................................................................. 19

2.1 Installation Checklist....................................................................................... 19

2.2 Unit Inspection............................................................................................... 19

2.3 Ducting & Vent Distribution System.................................................................. 20

2.4 Unit Mounting ................................................................................................ 21

2.5 Condensate Drains.......................................................................................... 21

2.6 Refrigeration Piping ........................................................................................ 22

2.7 Heating System Components ........................................................................... 22

2.8 Electrical Installation ...................................................................................... 23

SECTION 3: - Testing and Commissioning........................................... 26

SECTION 4: - Operating the A/C Unit ................................................. 27

SECTION 5: - Trouble Shooting.......................................................... 28

SECTION 6: - Maintenance Schedule .................................................. 33

SECTION 7: - Maintenance Procedures ............................................... 33

7.1 Pumping Down the System.............................................................................. 33

7.2 Reclaiming Refrigerant .................................................................................... 33

7.3 Pressure Testing ............................................................................................ 33

7.4 System Evacuation ......................................................................................... 33

7.5 Refrigerant Charging ...................................................................................... 33

7.6 Safety Device Checks...................................................................................... 34

SECTION 8: - Spare Parts .................................................................. 35

8.1 Compressor Area (BMS38BX1) ......................................................................... 35

8.2 Drivers Unit Dash Panel................................................................................... 35

8.3 Evaporator Unit Assembly (BFW5BX5) .............................................................. 36

8.4 Driver’s Unit Assembly (BMV5BX5) ................................................................... 37

8.5 Other Components (BMV5BX5) ........................................................................ 38

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 5

BMS38BX1 A/C System – Operation & Overview Manual

S E C T I O N 1 : - S y s t e m D e t a i l s

1.1 Introduction

This manual is a guide to the operation, maintenance and spare parts for the BMS38BX1 bus air conditioning system manufactured by Coachair as specifically developed for Bus & Coach International.

The BMS38BX1 air conditioning system consists of a high performance XT175 roof top A/C system for passenger comfort combined with a BMV5BX5 driver’s A/C system for driver comfort and demisting the windscreen.

The BMS38BX1 air conditioning system is a ‘split system’ comprising of components that are designed to be integrated into the bus during its manufacture.

The BMS38BX1 system includes the following primary components (units):

 A roof mounted evaporator/condenser unit (XT175) providing A/C (cooling and heating) for the passenger area.

 One under dash type evaporator unit (BFW5BX5) and associated piping and harnesses (collectively referred to as BMV5BX5) providing A/C (cooling and heating) and demisting airflow;

 An off-engine mounted compressor.

 Two driver's dash panels each controlling either the roof unit or the Driver’s system.

 Generic installation fittings.

The BMS38BX1 system has the following key features:

 Light-weight construction.

 Standard operating voltage of 24 V DC.

 Use of environmental friendly R134a refrigerant.

 Efficient use of engine heat for heating requirements.

1.1.1 Hierarchy of Manuals

The BMS38BX1 A/C system units are drawn from the Coachair product family. Manuals already exist for the XT roof top unit and these have been retained as discrete documents to allow timely updates of information as products are refined and improved.

There are significant differences between the driver’s unit described in the existing manual (SM348 -

2793 Dash A/C Unit – Installation, Operation & Maintenance Manual) and the BCI unit. As such the relevant information from that manual plus any additional information has been incorporated into this manual.

Manual Description

BMS38BX1 Complete Bus A/C System

SM424 3381

BMS38BX1 Operation & Maintenance &

Overview Manual

Purpose

Overview of A/C System and Special items

XT175 Roof Top Unit

SM417 3283

XT Bus & Coach A/C – Installation, Operation

& Maintenance Manual

SM425 3283 XT A/C Unit – Spare Parts Manual

SM423-3283 CCC007* Climate Control System Manual

BMV5BX5 Drivers Unit

SM424 3381

BMS38BX1 Operation & Maintenance &

Overview Manual

Other

09704

KK73.1

FKX50/775K Bock Compressor Manual

Lang Clutch Operating Instructions

Installation, Operation & Maintenance

Information

Spare Parts

Operation & Control

Installation, Operation, Maintenance & Spare

Parts Information

Maintenance of Bock Compressor

Maintenance of Lang Clutch

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 6

BMS38BX1 A/C System – Operation & Overview Manual

1.2 Specifications

The following specifications are correct for the A/C system at the time of printing.

Cooling Capacity

(nominal)

Heating Capacity

(nominal)

Dimensions

Weight

Combined:

XT175:

BMV5BX5:

Combined:

XT175:

BMV5BX5:

- 40 kW @ 35°C ambient, 27/19°C DB/WB Mixed Air

- 35 kW

- 5 kW

- 42 kW

- 38 kW

- 4 kW

XT175 Unit:

BFW5BX5 Unit:

- 3810mm long x 1940mm wide x 235mm high

- 350mm high x 500mm wide x 350mm deep

XT175 Unit: - 265 kg

BFW5BX5 Unit: - 14 kg

Compressor with Clutch: 54 kg

R134a

Refrigerant

Compressor

Bock FKX50/775K reciprocating 6 cylinder design ~ 775 cc, engine driven.

Maximum speed 3,500 rpm

Lang KK73.1.23 2xSPB Ø 160mm OD electro-magnetic

Compressor Clutch

Airflow

XT175:

BFW5BX5:

- 1,444 l/s (5,200 m

3

/hr) at high speed (free blow)

- 200 l/s (720m

3

/hr) at high speed (free blow)

24 V DC nom. Max. 30 V DC cont., 45 V DC momentary, 20 V DC Min.

Operating Voltage

Current Draw

Combined:

XT175:

- 77A (max.)

- 62A (max.)

BFW5BX5: - 12A (max.)

Clutch: - 2.6A (max.)

See SM417 manual.

Condenser Unit

Evaporator Unit

Expansion Valve

Drier Receiver

Safety Features

For XT see SM417 Manual. For Drivers Unit:

Coil: 1-off rifle copper tube with high efficiency aluminium fins

Motor: 1-off medium duty, long life, permanent magnet type, double shaft, steel ball bearings.

Fans: 2-off double inlet rotor.

For XT see SM417 Manual. For Drivers Unit: Internally equalized block valve.

See SM417 manual.

Climate Controller

High and low pressure cut-out safety switches

Electrical de-ice thermostat

Electrical protection fuses

For XT see SM417 Manual. For Drivers Unit: Driver controlled modulating water valve.

See SM417 manual.

Fresh air

Casing

Corrosion Protection

Lubricant

For XT see SM417 Manual. For Drivers Unit:

Primarily constructed of 2.0 mm aluminium ensuring resistance to corrosion and physical damage due to its robust design.

For XT see SM417 Manual. For Drivers Unit:

The casing is chemically prepared for paint application to all internal and external surfaces.

Ester Oil Type – Fuchs Reniso Triton SE 55 (Or Equivalent).

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 7

BMS38BX1 A/C System – Operation & Overview Manual

1.3 System Layout

The typical configuration of the installed BMS38BX1 A/C system and it various components are shown in the following diagram:

Drawing No. T3381007 Issue A

1.3.1 XT175 Roof Top Unit

Drawing No. T3381002 Issue 00

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 8

BMS38BX1 A/C System – Operation & Overview Manual

1.4 System Parameters

1.4.1 XT175 Roof Top Unit

Drawing No. T3381001 Issue 00

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 9

BMS38BX1 A/C System – Operation & Overview Manual

1.4.2 BFW5BX5 Evaporator Unit

Drawing No. T3381501 Issue 00

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 10

BMS38BX1 A/C System – Operation & Overview Manual

1.5 Air Flow

The XT175 roof top and Driver’s unit are not connected on the air side. Refer to the SM417 manual for the XT Unit.

The Driver’s unit utilises cooling and heating functions to deliver conditioned air to the driver and/or windscreen as determined by the control settings.

The unit is designed to be mounted under the dash in front of the bus driver. This positioning is shown in Section 1.3 - System Layout.

Drawing No. T3381502 Issue 00

 When operational the unit produces the following airflow:

 Return air from the bus cabin is drawn by the supply fan through the return air filter (Supplied by the Bus Body Builder) into the unit.

 The air is conditioned as it passes through the evaporator and heater coils inside the unit.

The evaporator coil cools and dehumidifies the air.

The heater coil heats the air.

The type and amount of air conditioning provided is controlled by the driver according to the water valve setting.

 The conditioned supply air is discharged from the unit through the A/C or DEMIST outlets by an electrically operated damper. This switches the main airflow between the driver outlets and the windscreen outlet.

 Five air outlets on the top of the unit are provided for supplying air to the windscreen during

DEMIST mode.

The airflow from these outlets is to be ducted by the bus body builder towards the windscreen.

 Four air openings are provided on the return air side of the unit for supplying air to the driver during A/C mode.

The airflow from this outlet is to be ducted by the bus body builder towards the driver face / body area.

 One foot outlet on the side of the unit supply air during A/C and DEMIST modes.

In A/C and DEMIST modes air exits from the two side outlets. The airflow from the two side outlets is not affected by the position of the shutter.

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 11

The airflow from these outlets is to be ducted by the bus body builder towards the driver’s feet area (or may be blocked off as required).

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 12

BMS38BX1 A/C System – Operation & Overview Manual

1.6 Refrigeration System

The refrigeration system for the BCI system is based on the XT system described in the SM417 manual. There is a 1/2 liquid line take-off in the XT unit which supplies cooled refrigerant to the BFW5BX5 driver’s evaporator Unit. The suction line from the driver’s unit then returns, under the passenger floor, to the engine mounted compressor.

A solenoid valve is used to stop flow to the Driver’s unit when cooling is not required. This solenoid valve is operated as a de facto compressor clutch for the driver’s unit.

1.6.1 Refrigeration Piping and Connections

Drawing No. T3381005 Issue A

Component List

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 13

BMS38BX1 A/C System – Operation & Overview Manual

Piping Layout

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 14

BMS38BX1 A/C System – Operation & Overview Manual

1.6.2 Major Components

COMPONENT

Compressor

Condenser Coils

Condenser Fans

Pressure Relief

Valve

Receiver Tank

Ball Valve

DETAILS AND FUNCTION

Compresses low pressure, low temperature refrigerant vapour to a high pressure, high temperature gas.

Transfer heat from the refrigerant into the ambient air, causing the high pressure, high temperature gas to condense into a high-pressure liquid.

Draw air in the side grilles through the condenser coils and force it out through the other side grilles.

In case of high pressure the valve opens at 2,900 kPa to vent excess pressure to atmosphere.

The valve reseats at when the system pressure then reduces to 2,700 kPa.

Stores and separates high pressure liquid from the gas/liquid mixture incoming from the condenser coils, to ensure that only liquid refrigerant passes on to the TX valve.

Together with the solenoid valve, enables the Filter/Drier to be isolated from the system for removal & replacement without loss of refrigerant from the system.

Solenoid Valve

Filter/Drier

Sight Glass

Eliminates liquid refrigerant migration from the low-pressure side of the system to compressor sump during off cycle, protecting the compressor against damaging liquid slugging.

The solenoid valve is in a closed position when the A/C system is off.

Filters and removes moisture and foreign particles from the refrigerant.

The valves either side of the Filter/Drier enable easy replacement with reduced gas loss.

Indicates the refrigerant level and moisture content in the system.

The positioning of the sight glass allows for easy viewing from inside the bus saloon area through the Return Air Plenum.

Regulates the refrigerant flow into the evaporator coil by expanding the liquid from a high pressure, high temperature liquid to a low temperature, low pressure liquid.

Thermal

Expansion (TX)

Valve

Evaporator Coils

Evaporator

Blowers

Check Valve

Transfers heat from the air to the refrigerant, causing the low pressure, low temperature liquid to evaporate in the evaporator into a low-pressure vapour.

As air passes through the coil it is cooled and dehumidified.

Draws air into the unit through the return air & fresh air openings; through the evaporator coils – and directing it into the supply air openings.

Prevents return of liquid refrigerant from the condenser to the compressor when the

A/C system is inoperative.

Ensures not to much refrigerant cycles through the Driver’s units.

Pressure

Regulator

Unit Connections

Compressor

Connections

Suction and discharge refrigeration pipelines are connected to the unit by leak-proof flanges. The connections are made at the unit base inside the vehicle on the nearside or off-side air supply roof opening, or at the back of the unit outside the vehicle.

Piping is connected to the compressor via hoses with flange connections.

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 15

BMS38BX1 A/C System – Operation & Overview Manual

1.6.3 Safety Devices

High and Low Pressure Switches

The compressor high and low-pressure switches on the compressor feed signals to the Coachair

Climate Controller. If the refrigeration system pressures become abnormally high or low the climate controller will cut out the clutch.

LP Switch

Cut-out:

Cut-in:

HP Switch

Cut-out:

Cut-in:

40 kPa

175 kPa

2,070 kPa

1,380 kPa

1.6.4 Compressor

The Bock FKX50/775K compressor is recommended to be used with the A/C system. Further details can be found in the compressor manual and at www.bock.de.

Compressor

Displacement per rev (cc)

Speed Range (rpm)

Cylinders

Weight (kg)

Oil Charge (litres)

Capacity Control

Bock FKX50K/775K

775

500 – 3,500

6

42

2.6

100% / 67% / 33%

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 16

BMS38BX1 A/C System – Operation & Overview Manual

1.6.5 Clutch

The Lang KK73.1.23 160mm diameter electromagnetic clutch is recommended to be used with the

A/C system. Further details can be found in the compressor manual and at wwwealang.com

.

The cross section of a typical clutch is illustrated below.

1.7 Heating System

The XT175 roof top and Driver’s units heating systems can operate independently. Refer to the SM417 manual for how a typical heating system works.

The booster pump is controlled by the XT75 climate control system but is typically not required for the

Driver’s unit when it is operating alone.

1.8 Electrical System

Refer to the SM417 manual for the XT Unit.

The XT175 roof top and Drivers Unit are not connected electrically. The Driver’s Unit requires the

XT175 Unit to be in cooling mode (with the compressor clutch engaged) for then to provide cooling.

All system operations are controlled by the dash panel and the relays on the evaporator unit (Refer to diagram in the Section 2.8 – Electrical Installation).

The evaporator coil thermostat allows the system to disengage the electro-magnetic compressor clutch should the temperature drop too low. This is intended to prevent ice from forming on the coil.

Once the coil temperature rises clutch operation is re-enabled.

1.8.1 Power Supply

UNIT VOLTAGE IS 24 V DC.

The power supply line is the red cable in the 6 pin plug from the evaporator unit to the bus battery.

Coachair recommends that a 25A slow blow fuse is installed on the power supply line as close as possible to the battery pack. (See Section 2.8.4 – Connect A/C System to the Bus).

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 17

BMS38BX1 A/C System – Operation & Overview Manual

1.8.2 Ground Connection

The ground line is a black cable in the 6 pin plug from the evaporator unit to the bus frame/chassis.

(See Section 2.8.4 – Connect A/C System to the Bus).

Use a Multi-Meter Only!

DO NOT make a bridge connection between any terminals or use a test light. This may cause serious electrical damage to the unit and/or injury. Use a multi-meter only!

1.8.3 Temperature Probes

Evaporator (De-Ice) Probe

The evaporator thermostat has a probe which is inserted into the fins of evaporator coils to measure the actual coil temperature. The de-ice probe are housed in stainless steel shafts to provide adequate strength & protection – as well as optimum contact with the coil fins.

1.8.4 De-Ice Control

Should the evaporator coil temperature drop too low ice may begin to form on the coils blocking airflow and compromising A/C unit operation. To prevent this situation, the thermostat reduces cooling by cutting power to the clutch (and unloaders if available) when the coil temperature drops too low.

1.8.5 Driver's Dash Control Panel

The driver manually controls the A/C system with the driver dash panel. The Dash Panel is connected to the relay harness on the evaporator unit and features controls for:

 Selecting the operating mode of the A/C system between OFF, DEMIST, and A/C

 Adjusting the blower fan speed

 Setting the desired amount of reheating of the conditioned air

1.8.6 (Refer to 3.1.1De-Ice Operation (Driver’s Unit)

A thermostat probe is located in the fins of the evaporator coil. The coil temperature is monitored by the thermostat to detect low temperatures and prevent icing of the coils.

To check the de-ice operation run the A/C system. Open the evaporator access cover or stop the evaporator blowers by removing their relays from the circuit. This will cause the evaporator coil temperature to drop quickly and activate the safety cut out.

 As the coil/de-ice probe temperature drops the solenoid valve should close at -3°C.

 As the coil/de-ice probe temperature rises the solenoid valve should open at +1°C.

 If necessary adjust the thermostat so that the valve operates at the required temperature.

Operating the A/C Unit)

1.8.7 Harness Arrangement

Refer to Section 2.8.2 - BMV5BX5 Harness Arrangement Detail.

1.8.8 Wiring Diagram

Refer to Section 2.8.3 - BMV5BX5 Wiring Diagram.

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 18

BMS38BX1 A/C System – Operation & Overview Manual

S E C T I O N 2 : - I n s t a l l a t i o n

Refer to the SM417 manual for the XT Unit.

2.1 Installation Checklist

 Check off all items.

 Inspect the evaporator units and loose items.

 Check for correct preparation of mounting locations.

 Check the ducting and distribution vent system.

 Install the evaporator and loose items.

 Install the return air grille.

 Install the condensate drains.

 Install refrigeration piping.

 Connect the piping to the evaporator and piping panels.

 Connect the piping to the XT system.

 Install heating system components.

 Install driver dash panel.

 Install electrical harnesses.

 Pressure test of the system.

 Evacuate the system.

 Charge the system with refrigerant.

 Finalise heating system installation.

 Check safety devices.

 Complete post-installation checklist.

2.2 Unit Inspection

Before beginning the installation, perform a visual inspection of the units. Check to make sure no damage has occurred during shipping:

 No external damage to the casing.

 No damage to coil fins or other external components.

 5 - 10 mm clearance between the condenser fan blade and top grille.

REPORT ANY VISIBLE DAMAGE!

Do Not Remove Sealing Caps!

Do not remove the refrigeration sealing caps before installing the unit. The sealing flange is to be removed

immediately before

connecting the body piping.

As supplied, the unit is sealed and pressurised to 350-400 kPa.

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 19

BMS38BX1 A/C System – Operation & Overview Manual

2.3 Ducting & Vent Distribution System

An appropriately designed bus air ducting and distribution system is essential for efficient and trouble-free operation of the A/C system. Use the guidelines given in SM417.

2.3.1 Return Air Interface

Six bolts are used to secure the return air duct to the Unit. The interface is shown below.

Drawing No. T2793004 Issue 00

2.3.2 Vent Arrangement

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 20

BMS38BX1 A/C System – Operation & Overview Manual

2.3.3 Sufficient non-closing type relief vents should be provided for constant air distribution to the windscreen, head and feet regions (Refer to Section 1.4.2 - BFW5BX5 Evaporator

Unit

Drawing No. T3381501 Issue 00

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 21

BMS38BX1 A/C System – Operation & Overview Manual

).

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 22

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 23

BMS38BX1 A/C System – Operation & Overview Manual

2.3.4 Seal the Air Openings

Seal the return air and supply air openings against water and air leakages, using a good quality non-drying type sealant. This seal ensures there is no air leakage or foreign matter (water, dust) can enter into the bus from this area.

2.3.5 Return Air Grille

Install the return air grille in the return air opening.

If the return air grille (and filter) assembly is to be provided by the body builder or installer, the following recommendations should be followed:

 The grille should be of a hinged or removable type so as to provide easy access into the unit evaporator section.

 The return air filter restriction should be less than 30 Pa @ 1.5 m/s air velocity.

BMS38BX1 A/C System – Operation & Overview Manual

2.4 Unit Mounting

Refer to the SM417 manual for the XT Unit.

The driver’s unit is secured to the bus via 4 brackets (2 at the front and 2 at the rear).

Sufficient clearance is required at the back of the unit to allow the access cover to be removed for access to the de-ice thermostat and evaporator motor.

Typically the unit must be removed from the return air side so the bulkhead it is attached to must also be removable or an alternate method of removal, say by taking the bonnet off the bus, must be identified.

Drawing No. T3381507 Issue 00

2.5 Condensate Drains

Refer to the SM417 manual for the XT Unit.

Included with the driver’s unit are:

 16mm PVC pipe

 2x aluminium tubes

 2x Drain nozzles

 4 hose clips

The standard configuration of drain hoses is shown below.

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 25

BMS38BX1 A/C System – Operation & Overview Manual

Drawing No. T3381508 Issue 00

When installing drain hoses; the following notes must be adhered to:

 Route drain hoses to the bottom of the bus but to an area protected from road dirt and mechanical damage.

 Do not route the flow line uphill.

 Use correct size hose clamps and tighten securely.

 Make sure that there are no kinks or restrictions in the hoses at any point.

 Install drain nozzles to prevent air drawing up the drain hoses.

2.6 Refrigeration Piping

The diagram in Section 1.6.1 – Refrigeration Piping and Connections shows the refrigeration piping circuit. Refer to SM417 manual for typical detail on installing and connecting refrigeration piping.

2.6.1 Refrigeration Piping Considerations

For installation of the refrigeration piping Coachair recommends the following:

Only use the recommended pipe sizes:

SUCTION PIPING: 1 3/8” OD copper (XT175 unit)

7/8” OD copper [5/8” in vertical rise] (BFW5BX5)

DISCHARGE PIPING:

LIQUID LINE:

1 1/8" OD copper

1/2” OD copper (BMV5BX5 unit)

2.6.2 Suction & Discharge Piping Panels

The driver’s unit has two piping panels supplied loose. These contain the components required for the suction and discharge lines for the driver’s unit. The water modulating valve is also included on the suction panel. These panels should be installed and connected as per the refrigeration diagram.

Drawing No. T3381501 Issue 00 Drawing No. T3381502 Issue 00

2.7 Heating System Components

Refer to SM417 manual for typical water piping details. The XT175 and BMV5BX5 unit should use 3/4” water pipe. The booster pump should be installed between the motor and the take off to both units.

See the diagram in Section 1.6.1 – Refrigeration Piping and Connections

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 26

BMS38BX1 A/C System – Operation & Overview Manual

2.8 Electrical Installation

Refer to the SM417 manual for the XT Unit.

2.8.1 Typical Wiring Harness Layout BMS38BX1

Drawing No. T3381008 Issue A

2.8.2 BMV5BX5 Harness Arrangement Detail

The harness arrangement for the driver’s unit is shown below.

Drawing No. AS338150 Issue A

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 27

BMS38BX1 A/C System – Operation & Overview Manual

2.8.3 BMV5BX5 Wiring Diagram

The wiring for the driver’s unit is shown below.

Document Number: SM424-3381

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 28

BMS38BX1 A/C System – Operation & Overview Manual

2.8.4 Connect A/C System to the Bus

The driver’s unit is powered through a six pin plug on the main harness. The wiring on the bus required for this plug is shown below. The plug on the bus is a Carroll male QK6BLT connecting to the equivalent female plug on the relay harness.

2.8.5 Install Dash Panel and Harness

The dash panel is to be installed on the vehicle dashboard with the cut out shown below.

 Fix the dash panel using the four mounting holes.

The dash harness connects from the dash panel to the relay harness on the evaporator unit control.

 Run the cable along the shortest path.

 Secure the cable against vibration and shock.

 Keep the cable away from heat and electrical emissions. Do not run the dash harness with the battery cable or any other electrical wiring unless it is unavoidable.

2.8.6 Install Solenoid Valve Wiring

The solenoid valve acts as surrogate compressor (clutch) for the driver’s unit. A 2 pin Carroll male

QK2BSL connector is required on the cable connecting to the driver’s unit.

Wiring should be as shown in Section 2.8.3 - BMV5BX5 Wiring Diagram

2.8.7 Install Water Modulation Valve wiring

The Coachair supplied cabling is used to connect the water modulation valve.

Harnesses should be as shown in Section 2.8.2 - BMV5BX5 Harness Arrangement Detail

2.8.8 Check Operation of All Fans

Check the operation and rotating direction of the evaporator blower immediately after installing the electrical harnesses, before refrigerant charging.

BMS38BX1 A/C System – Operation & Overview Manual

S E C T I O N 3 : - T e s t i n g a n d

C o m m i s s i o n i n g

The commissioning of the A/C system must be carried out by Coachair Service personnel or authorised agents.

 Refer to the SM417 manual for Testing and Commissioning details.

 The XT175 unit must be in cool mode for the Driver’s A/C system cooling to be tested.

 To balance the systems the pressure regulator on the Driver’s Units suction line should be adjusted. On initial start up this should be in the fully open position to provide maximum flow to the Driver’s Units

3.1.1 De-Ice Operation (Driver’s Unit)

A thermostat probe is located in the fins of the evaporator coil. The coil temperature is monitored by the thermostat to detect low temperatures and prevent icing of the coils.

To check the de-ice operation run the A/C system. Open the evaporator access cover or stop the evaporator blowers by removing their relays from the circuit. This will cause the evaporator coil temperature to drop quickly and activate the safety cut out.

 As the coil/de-ice probe temperature drops the solenoid valve should close at -3°C.

 As the coil/de-ice probe temperature rises the solenoid valve should open at +1°C.

 If necessary adjust the thermostat so that the valve operates at the required temperature.

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 30

BMS38BX1 A/C System – Operation & Overview Manual

S E C T I O N 4 : - O p e r a t i n g t h e A / C U n i t

Refer to SM417 & SM423 manuals for operating the XT175 Unit.

 Where there is a conflict between instructions the XT175 instruction should take priority.

 For the Driver’s A/C system to provide cooling the XT175 must be put into A/C mode and be operating.

4.1.1 Using the Dash Panel

Coachair supplies a dash panel for driver control of the driver’s unit. The dash panel features three switches and a rotary control.

Mode Switch

Mode Lights

Fan Speed Switch

Temperature

Control

Selects the A/C system operating mode between OFF, DEMIST, and A/C.

Set switch to upper position.

Set switch to middle position.

Set switch to lower position.

In DRIVER mode the unit provides ventilation / cooling / heating operation depending on the temperature control setting and the return air temperature. Fans operate at the selected speed.

In DEMIST mode the unit operates at the heating level selected, with or without cooling, depending on the temperature control setting and the return air temperature. Fans operate at the selected speed. An output signal for an external damper motor is also provided.

Illuminate when the switch is set to DEMIST or A/C to indicate operation.

Selects the operating speed of the fan blowers during DEMIST and A/C modes.

Set switch to upper position.

Set switch to middle position.

Provides for adjustment of the set point temperature.

Set switch to lower position.

A/C On/ Off

Switch

Illuminates when the A/C system is providing cooling operation. When switched on, the compressor clutch engages, regardless of ambient conditions.

4.1.2 Damper Motor Controller

There are three lights (green, orange & red) on the damper motor controller which operate as follows:

 Green Blinking – Damper moving to top position

 Green Solid – Damper in top position

 Orange Blinking – Damper moving to bottom position

 Orange Solid – Damper in bottom position

 Red – fault present

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 30

BMS38BX1 A/C System – Operation & Overview Manual

S E C T I O N 5 : - T r o u b l e S h o o t i n g

Refer to SM417 & SM423 manuals for operating the XT175 Unit.

 Where there is a conflict between instructions the XT175 instruction should take priority.

 For the Driver’s A/C system to provide cooling the XT175 must be put into A/C mode and be operating.

5.1.1 System will not start:

5.1.2 System produces no Heating:

5.1.3 System only Partially Heats:

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 32

BMS38BX1 A/C System – Operation & Overview Manual

5.1.4 System produces No Cooling (compressor operative):

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 33

BMS38BX1 A/C System – Operation & Overview Manual

5.1.5 System provides only Partial Cooling:

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 34

BMS38BX1 A/C System – Operation & Overview Manual

5.1.6 System is excessively noisy:

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 35

BMS38BX1 A/C System – Operation & Overview Manual

5.1.7 System Cools Intermittently:

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 36

BMS38BX1 A/C System – Operation & Overview Manual

S E C T I O N

6 : - M a i n t e n a n c e S c h e d u l e

Refer to SM417 manual for maintenance scheduling details.

S E C T I O N

7 : - M a i n t e n a n c e P r o c e d u r e s

Turn Isolating Switch to OFF and disconnect power!

Before performing any service procedures, ensure that the XT175 ignition-isolating switch on the unit control panel is set to the off position. Also ensure that the Driver’s Units 6 pin power plug has been disconnected. See Section 2.8.4 - Connect A/C System to the Bus.

WARNING

Refer to the SM417 manual for maintenance procedures for the system.

Particular notes pertaining to the combined system are given below.

7.1 Pumping Down the System

Pumping down the system involves pumping the refrigerant into the condenser and receiver.

1. Connect a manifold gauge to the suction service valve.

2. Run both A/C units.

3. Close the unit ball valve (near the receiver).

4. Disable the low-pressure switch by bridging the contacts.

5. Check the operating pressures. When the suction pressure reaches 7 kPa vacuum shut down the

A/C unit. If the pressure rises rapidly this indicates that there is still some residual refrigerant in the compressor crankcase. If this is the case run the A/C system again and check that the reaches

7 kPa vacuum. Do not reduce the pressure on the low side of the system any further, as a slight positive pressure will reduce the chance of contaminants rushing into the system when it is opened.

6. When the pressure remains at 7 kPa vacuum on system shutdown or raise very slowly close the compressor discharge valve.

7.2 Reclaiming Refrigerant

Correct evacuation and containment of the refrigerant enables the refrigerant to be re-used and reduces pollution.

In order to remove and store the refrigerant from the A/C system a commercial refrigerant recovery unit is required. Refer to the manufacturers instructions for the operation of the recovery unit.

With the check valve installed in the unit, the reclaim hoses need to be connected to either the service port at the receiver, the solenoid valves in the reclaim process.

both

systems have to be energised to open during

7.3 Pressure Testing

Note: The solenoid valves in both systems have to be energised to open.

7.4 System Evacuation

Note: The solenoid valves in both systems have to be energised to open.

7.5 Refrigerant Charging

Note: Ensure both systems are run when charging the system.

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 37

BMS38BX1 A/C System – Operation & Overview Manual

7.6 Safety Device Checks

WARNING

Be Ready to Shut Down the System!

Take care while checking the pressure switch operation. You must be ready to shut down the system immediately if the pressure switches do not operate correctly. Personal injury and damage to the A/C equipment could result from a large build up of pressure.

 Pressure switch test can be done with just the XT175 system operating

 Check both the XT175 and Driver’s Unit de-ice sensors.

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 38

BMS38BX1 A/C System – Operation & Overview Manual

S E C T I O N 8 : - S p a r e P a r t s

Refer to SM425 manual for typical XT175 spares.

8.1 Compressor Area (BMS38BX1)

Part Number Description

295200

Bock FKX50/775K Compressor

8.2 Drivers Unit Dash Panel

Part Number Description

SLC004

Lang KK73.1.23 Clutch

3

-

-

2

4

-

Ref Part Number Description

AS279354 Complete Dash Panel

1 662968 Rocker Switch - Mode

662969

667173

681395

854269

S2793055

Rocker Switch - Fans

On/Off Switch (Push Button)

Temperature Control Pot.

Label

Dash Panel metalwork

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 38

BMS38BX1 A/C System – Operation & Overview Manual

8.3 Evaporator Unit Assembly (BFW5BX5)

Drawing No. AS3381507 Issue 00

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 40

BMS38BX1 A/C System – Operation & Overview Manual

BMS38BX1 A/C System – Operation & Overview Manual

8.4 Driver’s Unit Assembly (BMV5BX5)

Drawing No. AS3381506 Issue A

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 41

8.5 Other Components (BMV5BX5)

Part Number Description

525010 7/8” Pressure Regulator

Part Number Description

531354 '/2” Filter Drier

Part Number Description

552042 '/2” Solenoid Valve

Part Number Description

668140 Coil for solenoid Valve

Part Number Description

517714 Ball Valve 5/8” Solder

517713 Ball Valve 1/2” Solder

Part Number Description

744991 BALL VALVE 1/2 FTOF BSP

Part Number Description

518006 FLARE NUT PLAIN 1/2 F10010

Part Number Description

RRV117

Schrader Valve Assembly

Part Number Description

320959 Water Valve Controller

Part Number Description

320958 Actuator Motor Controller

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 42

BMS38BX1 A/C System – Operation & Overview Manual

Part Number Description

522259 Valve - 4 way

Part Number Description

AS279368

WATER VALVE LOOM

Document Number: SM424-3381

Issue Date: October 2006

Uncontrolled Copy: Please refer to the Network for the current issue of this manual

Page 43

advertisement