Yokogawa XL100 Data Station Communication Function Manual
Reklama
Reklama
User’s
Manual
IM XL100C-E
XL100
Portable Data Station
Communication Function
IM XL100C-E
1st Edition: October 2005 (MC)
Introduction
Thank you for purchasing our XL100 Portable Data Station.
This Communication Function Manual provides information necessary for using communication functions and creating communication programs. To ensure correct use, please read this manual thoroughly before beginning operation.
In addition to this manual, the User’s Manual (contained in the CD-ROM as with this manual) and Quick Setup Manual are available separately.
The User’s Manual provides detailed information regarding all of the functions and operations of the XL100 excluding the communication functions. The Quick Setup
Manual briefly explains the basic operations such as measurement operation and setup.
Use them together with this manual.
After reading this manual, keep it in an easily accessible place for later reference. This manual will come in handy when you are unsure of how to operate the product.
Notes
• The contents of this manual are subject to change without prior notice.
• Figures and illustrations representing display views in this manual may differ from actual views.
• Every effort has been made to ensure accuracy in the preparation of this manual.
However, should any doubts arise or errors come to your attention, please contact the vendor from whom you purchased the product.
• The contents of this manual may not be transcribed or reproduced, in part or in their entirety, without prior permission.
Trademark Acknowledgements
The company and product names referred to in this document are either trademarks or registered trademarks of their respective holders.
Revision Information
First Edition: October, 2005
1st Edition: October 2005 (MC)
All Rights Reserved, Copyright © 2005, Yokogawa M&C Corporation
IM XL100C-E
1
2
Safety Precautions
When operating the instrument, be sure to observe the cautionary notes given below to ensure correct and safe use of the instrument. If you use the instrument in any way other than as instructed in this manual, the instrument’s protective measures may be impaired.
Yokogawa Meters & Instruments Corporation is by no means liable for any damage resulting from use of the instrument in contradiction to these cautionary notes.
The following safety symbols are used on the instrument and in this manual.
Danger! Handle with Care. This symbol indicates that the operator must refer to an explanation in the User’s Manual or this manual in order to avoid risk of injury or death of personnel or damage to the instrument.
This symbol indicates DC voltage/current.
This symbol indicates AC voltage/current.
This symbol indicates ON (power).
This symbol indicates OFF (power).
WARNING
Indicates a hazard that may result in the loss of life or serious injury of the user unless the described instruction is abided by.
CAUTION
Indicates a hazard that may result in an injury to the user and/or physical damage to the product or other equipment unless the described instruction is abided by.
Note
Indicates information that should be noted in order to familiarize yourself with the instrument’s operating procedures and/or functions or gives supplementary information.
IM XL100C-E
Description of Displays and Exemption from
Responsibility
Description of Displays
• Some of the representations of product displays shown in this manual may be exaggerated, simplified, or partially omitted for reasons of convenience when explaining them.
• Figures and illustrations representing the controller’s displays may differ from the actual displays in regard to the positions and/or indicated characters (upper-case or lower-case, for example), to the extent that they do not impair correct understanding of the functions and the proper operation and monitoring of the system.
Exemption from Responsibility
• Yokogawa Meters & Instruments does not make any warranties regarding the product except those mentioned in the WARRANTY that is provided separately.
• Yokogawa Meters & Instruments assumes no liability to any party for any loss or damage, direct or indirect, caused by the use of the product, or any unpredictable defect of the product.
• Be sure to use spare parts approved by Yokogawa Meters & Instruments when replacing parts or consumables.
• Modification of the product is strictly prohibited.
• Reverse engineering such as the disassembly or decompilation of software is strictly prohibited.
• No portion of the product supplied by Yokogawa Meters & Instruments may be transferred, exchanged, leased or sublet for use by any third party without the prior permission of Yokogawa Meters & Instruments.
3
IM XL100C-E
Contents
4
Chapter 1 Overview of the Communication Functions
1.1
Relationship between the Communication Function and the Ethernet and Serial
Chapter 2 Ethernet Interface
2.5
Setting the FTP Client (Setting the Auto Transfer of Measurement and Alarm Data
Setting the Login and Timeout Functions of Ethernet Communications ........................ 2-13
Chapter 3 Serial Interface
Chapter 4 Modbus Protocol
Chapter 5 Standard Protocol
Output Commands (RS-485 and USB Dedicated Commands) ..................................... 5-41
5.11
Maintenance/Test Commands (Available when using the maintenance/test server
IM XL100C-E
Contents
Chapter 6 Status
Chapter 7 Error Messages
Appendix
Index
2
3
4
5
6
7
IM XL100C-E
5
Chapter 1 Overview of the Communication Functions
1.1
Relationship between the Communication
Function and the Ethernet and Serial Interfaces
The XL100 comes standard with an Ethernet interface for connecting a LAN cable and a serial interface (RS-232/RS-485 and USB). To use the communication function of the
XL100, the Ethernet or serial communication settings must be configured in advance.
The following figure shows the relationship between the communication function of the
XL100 and the Ethernet and serial interfaces.
XL100 communication function
Application
MODBUS slave
MODBUS master
Setting/Measurement
Maintenance/
Test server server
Web server
FTP server
Login
(User authentication/ access privileges granting)
FTP client E-mail client
HTTP FTP SMTP
Upper layer protocol
Lower layer protocol
Dedicated protocol
MODBUS protocol
Serial communication control
Upper interface
Lower interface
Serial
(RS-232/RS-485)
USB
TCP
IP
Ethernet
10BASE-T/100BASE-TX
To use the communication function of the XL100 via the Ethernet or serial interface, communications must be performed according to the following protocols* that lie in between two.
• FTP (File Transfer Protocol)
• TCP (Transmission Control Protocol)
• IP (Internet Protocol)
• HTTP (Hyper Text Transfer Protocol)
• SMTP (Simple Mail Transfer Protocol)
To use the serial communication function, select one of the following protocols.
• XL100 standard protocol (dedicated protocol)
• Modbus protocol (slave)
• Modbus protocol (master)
2
3
4
5
6
7
App
Index
1-1
IM XL100C-E
1-2
1.2
Explanation of Functions
This section gives an overview of the communication function that can be used to control the XL100.
Modbus Communication
Modbus Slave
• The Modbus protocol can be used to read the measured/calculated data written to the input register of the XL100 from a PC or write/read communication input data from the hold register of the XL100.
• For details on the Modbus function codes that the XL100 supports, see section 4.1.
• This function can be used only when communicating via the serial interface.
• For a description on the settings required to use this function, see sections 4.2 and
4.3.
Modbus Master
• Loads the measured data and other types of data of other instruments using the
Modbus protocol as communication channel input. The loaded data can be scaled and displayed with a unit that you assign. The data can also be used as a calculation channel.
• Function for writing data to other instruments is not supported.
• For details on the Modbus function codes that the XL100 supports, see section 4.1.
• This function can be used only when communicating via the serial interface.
• For a description on the settings required in using this function, see section 4.4.
Setting/Measurement Server
• This function can be used to set almost all of the settings that can be configured using the front panel keys. This function cannot be used to (1) turn the power switch ON/
OFF, (2) set the user name/password for communications, (3) set the user name/ password for key login, and (4) set the destination of the FTP client function.
• The following types of data can be output.
• Measured/calculated data.
• Data in the internal memory or files in the external storage medium.
• Setup data.
• Log data of operation errors and communications.
• The commands that can be used through this function are setting commands and output commands.
• This function can be used when communicating via the Ethernet or the serial interface.
Maintenance/Test Server
• This function can be used to output connection information, network information, and other information regarding Ethernet communications.
• The commands that can be used through this function are maintenance/test commands.
• This function can be used only when communicating via the Ethernet interface.
IM XL100C-E
FTP Server
FTP Client
1.2 Explanation of Functions
• You can use a PC to access the XL100 via FTP. You can perform operations such as retrieving directory and file lists from the internal memory or the external storage medium of the XL100 and transferring and deleting files.
• This function can be used only when communicating via the Ethernet interface.
Load measured data
Ethernet
Hub
PC
FTP server
Hub
Load measured data
PC
2
3
4
5
6
• Automatic File Transfer
• The display data file and log data file that are created in the internal memory of the
XL100 can be automatically transferred to a remote FTP server. The result of the transfer is recorded in the FTP log. The FTP log can be shown on the XL100’s display or output to a PC using commands.
Automatically save measured data
Ethernet
FTP client
Hub
Primary
FTP server
Hub
7
App
Index
Secondary
FTP server
You can specify two destination FTP servers, primary and secondary. If the primary server is down, the file is transferred to the secondary server.
• This function can be used only when communicating via the Ethernet interface.
• FTP Test
• The file transfer can be checked by transferring a test file from the XL100 to a remote FTP server.
• The result of the FTP test can be confirmed on the FTP log display.
• This function can be used only when communicating via the Ethernet interface.
IM XL100C-E
1-3
1.2 Explanation of Functions
Login
• This function can be used only when communicating via the Ethernet interface and when using the setting/measurement server, maintenance/test server, and the FTP server functions.
• User Authentication
This function allows only registered users to access the XL100 in order to prevent invalid access from the network.
• Up to seven names can be registered. One of the names is fixed to administrator privilege. For the other six names, you specify the access privilege when you register the name.
• There are limitations on the number of simultaneous connections and the number of simultaneous users accessing the XL100 from PCs (see section 2.1).
• Granting Access Privileges
This function grants access privilege (user level) to operate the XL100 for the registered users. For example, this prevents user B (user level) from changing the measurement conditions that were set by user A (administrator level).
• There are two user levels on the XL100, user and administrator.
• Administrator
An administrator has privileges to use all setting/measurement server functions, maintenance/test server functions, and FTP server functions.
• User
A user has limited privileges to use the setting/measurement server functions, maintenance/test server functions, and FTP server functions.
• Limitations on the use of the setting/measurement server
A user cannot change settings that would change the XL100 operation. A user can output measured data and setting data.
• Limitations on the use of the maintenance/test server
A user cannot disconnect a connection between another PC and the XL100.
A user can disconnect the connection between the PC that the user is using and the XL100.
• Limitations on the use of the FTP server
You cannot save files to the external storage medium of the XL100 or delete files on it. You can load files.
• Communication Timeout
This function drops the connection with the PC if there is no data transfer for a given time at the application level. For example, this function prevents a PC from being connected to the XL100 indefinitely which would prohibit other users from making new connections for data transfer.
Web Server
1-4
• This function can be used only when communicating via the Ethernet interface.
• The XL100 display can be shown on a Web browser (for Web browsers that have been tested for compatibility, see section 2.10).
• The following two pages are available.
• Monitor page: Monitoring screen (switching is possible among measurement data displays, alarm summary display, and log displays)
• Operator page: This page allows you to switch the XL100 display. You can also switch to Setting mode or File Operation mode to control the
XL100 in the respective mode.
You can use access control (user name and password) to limit the access to each page.
IM XL100C-E
1.2 Explanation of Functions
• The display section of the XL100 can be updated periodically (select from 2, 5, 10, or
30 s).
• The following information can be displayed.
• Measured data
• Alarm summary
• Logs (error log, communication command log, key login/logout log, FTP client log, e-mail log, and Web operation log)
E-mail Transmission
This function can be used only when communicating via the Ethernet interface.
• Transmitting E-mail Messages
• E-mail can be automatically transmitted at the times indicated below. You can specify two groups of destinations and specify the destination for each item. In addition, you can set a header string for each item.
• When an alarm is activated/released
Notifies alarm information.
• When the XL100 recovers from a power failure
Notifies the time of the power failure and the time of recovery.
• When an error related to the external storage medium and FTP client occurs
Notifies the error code and message when an error is detected on the external storage medium or when the data cannot be stored due to insufficient free space on the external storage medium. In addition, notifies the error code and message when data transfer fails using the FTP client function.
• At the specified time
Transmits an e-mail message when the specified time is reached. This can be used to confirm that the e-mail transmission function including the network is working properly. You can specify the reference time and the e-mail transmission interval for each destination.
• E-mail Transmission Test
• You can send a test message from the XL100 to the destination to check e-mail transmissions.
• You can confirm the result of the e-mail transmission test on the e-mail log screen.
Other Functions
IM XL100C-E
• SNTP (Simple Network Time Protocol) Connection
You can synchronize the standard clock by connecting to an SNTP server when using the Ethernet interface.
• Checking the Connection Status of the Ethernet Interface
You can check the connection status of the Ethernet interface with the LAN port LED on the side panel of the XL100 and on the display of the XL100.
• Keepalive (Extension Function of TCP)
This function drops the connection if there is no response to the test packet that is sent periodically at the TCP level.
• Displaying the Error, Communication, FTP, Web Operation, and E-mail Logs
You can display the following operation logs on the log display.
• Error log display: Log of operation errors.
• Communication command display: Log of communication input/output.
• FTP client log display: Log of file transfers carried out using the FTP client function.
• Web operation log display: Log of operations using the Web server function.
• E-mail log display: Log of e-mail transmissions.
1-5
2
3
4
5
6
7
App
Index
Chapter 2 Ethernet Interface
2.1
Ethernet Interface Specifications
Basic Specifications
Item
Number of ports
Electrical and mechanical specifications
Transmission medium type
Data rate
Protocol
Supported services
Connector type
Specifications
1
Conforms to IEEE 802.3.
Ethernet (100BASE-TX/10BASE-T)
100 Mbps maximum
TCP/IP
FTP server, FTP client, SMTP client (mail transmission), Web server, DHCP, DNS, and SNTP
RJ-45
Maximum Number of Simultaneous Connections/Number of Simultaneous Users
The following table shows the maximum number of simultaneous connections, the number of simultaneous users, and the port number for each function.
Function
Setting/Measurement server
Maintenance/Test server
Maximum Number of Connections
3
1
Number of Simultaneous Users
Administrator User
1
1
2
2
*2
1
*2
2
*2
Port Number
34339
34340
FTP server 2 21
*1 The port numbers are fixed.
*2 There are user limitations. For details, see “Granting Access Privileges” under “Login” in section 1.2.
*1
1
2
3
6
7
4
5
App
Index
2-1
IM XL100C-E
2-2
2.2
Connecting of the Ethernet Interface
When Connecting Only the XL100 and the PC
Connect the LAN ports of the XL100 and the PC using a 10BASE-T or 100BASE-TX
LAN cable.
LAN port
RS232
LOGIC/PULSE
ALARM
LAN cable
If you are connecting the XL100 and the PC directly in a one-to-one configuration without using a hub, use a cross LAN cable.
When Connecting to an Existing Network
When connecting the XL100 or the PC to an existing network, communication parameters such as the data rate and connector type must be matched. For details, consult your system or network administrator.
Note
• Depending on the reliability of the network or the volume of network traffic, all the transferred data may not be retrieved by the PC.
• Communication performance deteriorates if multiple PCs access a XL100 simultaneously.
• If the interface is not set to LAN, do not connect the LAN cable.
IM XL100C-E
2.3
Configuring of the Ethernet Interface
The following configurations must be made to use the Ethernet communication functions of the XL100.
Selecting the Communication Interface
Communication can only be performed on a single interface at any given time. You must select the communication interface by carrying out the steps below. The default setting is
LAN (Ethernet).
Procedure
1.
Press SETTING to enter Setting Mode.
1
2
3
4
5
2.
Use the arrow keys to select COMMUNICATION, and press SELECT.
6
7
→
App
Index
3.
With INTERFACE selected, press SELECT.
An interface selection list is displayed.
4.
Use the arrow keys to select a communication interface, and press SELECT.
5.
Press SET.
Setting the Ethernet Parameters
• Setting the Time Zone
Set the time difference from Greenwich Mean Time.
• Setting the DHCP, IP Address, Subnet Mask, Default Gateway, and DNS
Consult your system or network administrator when setting parameters such as the IP address, subnet mask, default gateway, and DNS (domain name system).
• DHCP (Dynamic Host Configuration Protocol)
• The IP address, subnet mask, default gateway, and DNS can be automatically set by using DHCP.
• To use DHCP, the network must have a DHCP server.
• Consult your network administrator to see if DHCP can be used.
• If you use DHCP, a different IP address may be assigned each time the XL100 is powered up. You must pay attention when using the FTP server function of the XL100.
IM XL100C-E
2-3
2.3 Configuring of the Ethernet Interface
• IP Address
• Set the IP address to assign to the XL100. The default setting is 0.0.0.0.
• The IP address is used to distinguish between the various devices connected to the Internet when communicating using the TCP/IP protocol. The address is a
32-bit value expressed using four octets (each 0 to 255), each separated by a period as in [192.168.111.24].
• Subnet Mask
• Specify the mask that is used to determine the network address from the IP address. The default setting is 0.0.0.0.
• Set the value according to the system or network to which the XL100 belongs. In some cases, this setting may not be necessary.
• Default Gateway
• Set the IP address of the gateway (router, etc.) used to communicate with other networks. The default setting is 0.0.0.0.
• Set the value according to the system or network to which the XL100 belongs. In some cases, this setting may not be necessary.
• DNS (Domain Name System)
You must set the DNS if you are using a host name to specify the destination server of the file transfer on an FTP client or the server of the e-mail recipient.
* DNS is a system used to associate names used on the Internet called host names and domain names to IP addresses. The host name/domain name can be used instead of the IP address when accessing the network. The DNS server manages the database that contains the host name/domain name and IP address correlation.
• DNS Server
• Set the IP address of the DNS server. The default setting is 0.0.0.0.
• You can specify up to two DNS server IP addresses, primary and secondary.
If the primary DNS server is down, the secondary DNS server is automatically looked up for the mapping of the host name/domain name and IP address.
• Host Name
Set the XL100’s host name using up to 64 characters.
• Domain Name
• Set the network domain name that the XL100 belongs to using up to 64 characters.
• When the destination server of the file transfer or the server of the e-mail recipient is looked up using the DNS server, this domain name is appended to the host name as a possible domain name if it is omitted. The recipient name (server name) is set to the name specified by FTP Server Name or
SMTP Server Name.
• Domain Suffix
When the IP address corresponding to the server name with the domain name of the previous section is not found, the system may be set up to search using a different domain name. In such cases, set the domain name to be searched following the “domain name” of the previous section as a domain suffix.
• Set the domain suffix using up to 64 characters.
• You can specify up to two domain suffixes, primary and secondary.
2-4
IM XL100C-E
IM XL100C-E
2.3 Configuring of the Ethernet Interface
• Setting the SNTP (Time Synchronization Function)
You can synchronize the standard clock by connecting to an SNTP server when using the Ethernet interface. The following items are set in addition to the Ethernet interface to use this function.
• SNTP ON/OFF
Select whether to enable (ON) or disable (OFF) SNTP.
• Server Name
Set the host name or IP address using up to 64 alphanumeric characters.
• Confirmation Time
Set the cycle for synchronizing the clock in the range of 1 to 24 hours.
• Enabling/Disabling the Login Function of the XL100
If you enable the login function, only registered users can log in to the XL100.
• Communication Timeout
• Selecting ON or OFF
• ON
If there is no data transmission for a specified time at the application level (see section 1.1), the connection is forcibly disconnected.
• OFF
Communication timeout is disabled.
• Setting the Timeout Value
If communication timeout is enabled, the connection is dropped if no data transfer is detected over a time period specified here.
Selectable range: 1 to 120 minutes
• Enabling/Disabling (On/Off) Keepalive
• ON
If there is no response to the inspection packet that is periodically transmitted
(every 30 s) at the TCP level, the connection is forcibly disconnected.
• OFF
Keepalive is disabled.
• Saving the Settings
To activate the settings that have been changed in the basic setting mode, the settings must be saved. Otherwise, the settings that existed before the change are activated.
Procedure
1.
Press SETTING to enter Setting Mode.
1
2
3
4
5
6
7
App
Index
2-5
2.3 Configuring of the Ethernet Interface
2.
Use the arrow keys to select COMMUNICATION, and press SELECT.
→
3.
Use the arrow keys to select ETHERNET, and press SELECT.
→
4.
Use the arrow keys to select the desired item, and press SELECT.
Press SELECT to show a selection list or display for setting the item.
• IP Address Setting display
• DNS Setting display
• SNTP Setting display
2-6
5.
Select or enter the item on the displayed selection list or window.
6.
Press SET.
IM XL100C-E
2.4
Checking the Connection Status of the
Ethernet Interface
Checking the Connection Status on the XL100
You can check the connection status of the Ethernet interface with the LAN port LED of the XL100.
LED Status
Green LED illuminated
Yellow LED blinking
Off
Connection Status of the Ethernet Interface
The Ethernet interface is electrically connected.
Transmitting data.
The Ethernet interface is not electrically connected.
Yellow LED
Blinks when data transmission is normal.
Green LED
Illuminates when communication is possible with the connected destination.
1
2
3
4
5
LAN
Checking the Connection Status on the XL100 Display
You can check the connection status with the icon that is shown in the status display section of the XL100 display. The icon appears when the interface is set to LAN, the
Ethernet parameters (IP address other than 0.0.0.0) are configured, and the cable is connected. For other cases, the icon is gray.
6
7
App
Index
2-7
IM XL100C-E
2-8
2.5
Setting the FTP Client (Setting the Auto Transfer of Measurement and Alarm Data Files)
By setting this function, the measurement and alarm data files created in the internal memory of the XL100 or an external storage medium can be automatically transferred using FTP at the time the files are created. To use this function, however, the Ethernet interface must be configured as described in section 2.3.
• Selecting the Transferred Files
• You can select whether to automatically transfer the measurement and alarm data files. The default setting is OFF.
• The data files are automatically transferred to the FTP destination explained in the next section at the end of the logging operation.
Note
If a file with the same name is detected at the destination, the file is transferred with the last character of the file name changed.
Example: If the file to be transferred named “050714130440.DLO” exists at the destination, the file name is changed to “050714130441.DLO” before it is transferred.
• Setting the FTP Destination
Consult your system or network administrator when setting parameters such as the primary/secondary FTP servers, port number, login name, password, account, and availability of the PASV mode.
• Specifying Primary and Secondary
You can specify two destination FTP servers, primary and secondary. If the primary server is down, the file is transferred to the secondary server.
• FTP Server Name
Enter the name of the file transfer destination FTP server using up to 64 alphanumeric characters.
• If the DNS is used, you can set the host name as a server name.
For details on setting the DNS, see section 2.3, “Setting the Ethernet Interface.”
• You can also set the IP address. In this case, the DNS is not required.
• Port Number
Enter the port number of the file transfer destination FTP server in the range of 1 to
65535. The initial value is 21.
• Login Name
Enter the login name for accessing the FTP server using up to 32 alphanumeric characters.
• Password
Enter the password for accessing the FTP server using up to 32 alphanumeric characters.
• Account
Enter the account (ID) for accessing the FTP server using up to 32 alphanumeric characters.
• PASV Mode
Turn PASV mode ON when using the XL100 behind a firewall that requires the passive mode. The default setting is OFF. A firewall is furnished on a router (or a similar device) that has security features. It prevents intrusion from the outside into the network system.
IM XL100C-E
IM XL100C-E
2.5 Setting the FTP Client (Setting the Auto Transfer of Measurement and Alarm Data Files)
• Initial Path
Enter the directory of the file transfer destination using up to 64 alphanumeric characters. The delimiter for directories varies depending on the implementation of the destination FTP server.
Example
When transferring files to the “data” directory in the “home” directory of an FTP server on a UNIX file system.
/home/data
Note
If the file transfer to both primary and secondary servers fails, the XL100 aborts the file transfer. When the connection to the destination recovers, the XL100 transfers the data files that failed to be transmitted in addition to the new data file.
Procedure
1.
Press SETTING to enter Setting Mode.
1
2
3
4
5
6
7
2.
Use the arrow keys to select COMMUNICATION, and press SELECT.
App
→
Index
3.
Use the arrow keys to select NETWORK FUNC., and press SELECT.
→
4.
With FTP CLIENT selected, press SELECT.
2-9
2.5 Setting the FTP Client (Setting the Auto Transfer of Measurement and Alarm Data Files)
5.
Use the arrow keys to select the desired item, and press SELECT.
Press SELECT to show a selection list or window for setting the item.
• Primary server setting display
6.
Select or enter the item on the displayed selection list or window.
7.
Press SET.
2-10
IM XL100C-E
2.6
FTP Test
You can test whether files can be transferred via the Ethernet interface by transferring a test file from the XL100 to the FTP server specified in section 2.5.
• Items to Check before Performing This Test
• Connect the Ethernet cable correctly. For the connection procedure, see section
2.2.
• Check that the Ethernet interface settings are correct. For the procedure, see section 2.3 or 2.5.
When setting the Ethernet interface, check the settings with your system or network administrator.
• Checking the Results of the FTP Test
• When an FTP test is executed, a test file named XL_FTPC.TXT is transferred to the directory indicated by the initial path at the FTP destination specified in section
2.5.
• The result of the FTP test can be confirmed by displaying the FTP log (displayed on the XL100 (see section 2.8)) or Web screen (see section 2.10) or by outputting the result using the FL command (see section 4.8).
Procedure
1.
Press SETTING to enter Setting Mode.
3
4
5
1
2
6
7
App
Index
2.
Use the arrow keys to select COMMUNICATION, and press SELECT.
→
3.
Use the arrow keys to select NETWORK FUNCTION SETTINGS, and press
SELECT.
→
2-11
IM XL100C-E
2.6 FTP Test
4.
With FTP CLIENT SETTINGS selected, press SELECT.
5.
Use the arrow keys to select FTP TRANSMISSION TEST, and press SELECT.
Press SELECT to transfer the file.
2-12
IM XL100C-E
2.7
Setting the Login and Timeout Functions of
Ethernet Communications
By setting these functions, you can prohibit invalid access from the network to the
XL100, authorize setup operations of the XL100 via the Ethernet network, and disconnect connections if there is no data transmission for a certain time. To use this function, however, the Ethernet interface must be configured as described in section 2.3.
Registering Users
• Selecting the User Level
Select either user level, administrator or user.
• Administrator
One administrator can be registered. The administrator has the privileges to use all the functions of the setting/measurement server, maintenance/test server, and FTP server.
• User
Certain limitations exist in using the setting/measurement server, maintenance/ test server, and FTP server.
• Limitations on the use of the setting/measurement server
Users are not authorized to change the settings that would change the operation of the XL100. Users can output measured and setting data.
• Limitations on the use of the maintenance/test server
A user cannot disconnect a connection between another PC and the XL100.
A user can disconnect the connection between the PC that the user is using and the XL100.
• Limitations on the use of the FTP server
A user cannot save files to the external storage medium of the XL100 or delete files on it. A user can load files.
• Selecting Whether to Register (ON/OFF) Users
• ON
Registers users. You can set the user name and password for logging in.
• OFF
Not register users.
• Setting the User Name
• Enter the user name using up to 16 alphanumeric characters.
• You cannot register the same user names.
• Since the word “quit” is reserved as a command on the XL100, the user name
“quit” is not allowed.
• Setting the Password
Set the password using up to six alphanumeric characters.
1
2
3
4
5
6
7
App
Index
2-13
IM XL100C-E
2.7 Setting the Login and Timeout Functions of Ethernet Communications
Note
• The relationship between the login function and the user name for accessing the XL100 is as follows:
• When the login function is set to ON
• You can log in to the XL100 using the registered user name and password.
• The user level is the user level specified when the user name was registered.
• When the login function is set to OFF
• You can log in to the XL100 as an administrator by accessing the XL100 using the user name “admin.” No password is necessary.
• You can log in to the XL100 as a user by accessing the XL100 using the user name
“user.” No password is necessary.
• The user name “anonymous” has a special meaning only when the FTP server function of the XL100 is used.
• When the login function is set to ON
• If a user name “anonymous” is registered to the XL100, you can log in to the XL100 using the user name “anonymous”.
• No password is necessary (you can log in regardless of whether a password is entered).
• The user level is set to the level of the user that registers “anonymous.”
• When the login function is set to OFF
• You can login using the user name “anonymous”.
• No password is necessary (you can log in regardless of whether a password is entered).
• The user level is set to user.
• There is a limitation on the number of simultaneous connections and the number of simultaneous users accessing the XL100 (see section 2.1).
• For a description of the login process of the Setting/Measurement server and
Maintenance/Test server, see appendix 2, “Login Process.”
Procedure
1.
Press SETTING to enter Setting Mode.
2-14
2.
Use the arrow keys to select SYSTEM, and press SELECT.
→
3.
With USER REGISTER selected, press SELECT.
4.
Use the arrow keys to select the desired user, and press SELECT.
5.
In the window shown, set the items, and press SELECT.
6.
Press SET.
IM XL100C-E
2.8
Showing the Error, Communication, and FTP
Log Displays
• Showing the Error Log Display
The error log display shows a log of operation errors. Up to 50 operation error logs are retained. Logs that exceed 50 are cleared from the oldest data.
1 2 3
4
1
2
3
4
5
1. Last line log No./total number of logs
Displays the log No. shown at the last line of the display and the total number of logs
(up to 50*).
* If the total number of logs exceeds 50, the log is deleted from the oldest one.
2. Date/Time of error occurrence
Displays the date/time when the error occurred.
3. Error code
4. Error Message
• Showing the Communication Log Display
The communication log display shows a log of communication interface I/O operations. Up to a total of 50 logs is retained. Logs that exceed 50 are cleared from the oldest data.
1
2 3 4
5
6
7
App
Index
IM XL100C-E
1. Last line log No./total number of logs
Displays the log No. shown at the last line of the display and the total number of logs
(up to 50*).
* If the total number of logs exceeds 50, the log is deleted from the oldest one.
2. Date/Time of access
Displays the date/time when the user connected and accessed the XL100.
3. Connection user ID number
Displays the ID number (1 to 7) of the user connected to the XL100.
4. Input or output
>: Input. <: Output.
5. Message
Displays the message (up to 20 characters).
2-15
2.8 Showing the Error, Communication, and FTP Log Displays
• Showing the FTP Log Display
The FTP log display shows a log of file transfers. Up to 50 file transfer operation logs are retained. Logs that exceed 50 are cleared from the oldest data.
1
2 3 4
5
1. Last line log No./total number of logs
Displays the log No. shown at the last line of the display and the total number of logs
(up to 50*).
* If the total number of logs exceeds 50, the log is deleted from the oldest one.
2. Date/Time of the file transfer
Displays the date/time when the file was transferred to the FTP server.
3. Error code
For a description of errors, see chapter 8, “Error Messages.”
4. Destination FTP server
P: Primary. S: Secondary.
5. File name
Displays the name of the transferred file (12 characters).
• Showing the Web Browser Operation Log Display
You can display a log (record) of the operations carried out using the Web screen on the Web operation log display. Up to 50 previous operations are logged. Logs that
1
exceed 50 are cleared from the oldest data.
2
3
4 5
2-16
1. Last line log No./total number of logs
Displays the log No. shown at the last line of the display and the total number of logs
(up to 50*).
* If the total number of logs exceeds 50, the log is deleted from the oldest one.
2. Date/Time of Web screen operation
Displays the date/time when a operation was carried out on the Web screen.
3. Operation
4. Error code
For a description of errors, see chapter 8, “Error Messages.”
5. Operation type
IM XL100C-E
IM XL100C-E
2.8 Showing the Error, Communication, and FTP Log Displays
• Showing the E-mail Log Display
You can show a log (record) of e-mail transmissions on the e-mail log display. Up to
50 previous e-mail transmissions are logged. Logs that exceed 50 are cleared from
1
the oldest data.
2
3 4 5
6
1
2
3
4
1. Last line log No./total number of logs
Displays the log No. shown at the last line of the display and the total number of logs
(up to 50*).
* If the total number of logs exceeds 50, the log is deleted from the oldest one.
2. Date/time of e-mail transmission
Displays the date/time of e-mail transmission.
3. E-mail timing
Displays the e-mail transmission timing (periodic, power failure, alarm, etc.).
4. Error code
For a description of errors, see chapter 8, “Error Messages.”
5. Recipient No.
1: Recipient 1. 2: Recipient 2
6. Error description
Note
• There is also a log display that shows a log of key login operations.
• You can also use commands to output the error, communication, FTP, Web operation, and e-mail log data.
5
6
7
App
Index
Procedure
1.
Press DISPLAY to show a pop-up menu for switching the display.
2.
Use the arrow keys to select the desired log display, and press SELECT.
2-17
2-18
2.9
Setting the Web Server Function
To use the Web server function, set the following parameters in addition to those described in section 2.3, “Setting the Ethernet Interface.”
• Enabling/Disabling the Web Server Function
Select ON (enable) or OFF (disable).
• Page Type (Type of Screen to Be Displayed)
• Monitor
• The screen displayed on the XL100 is displayed.
• The following information can be displayed.
• Alarm summary
• Measured and calculated data of all channels
• Logs (message log, error log, key login log, FTP log, e-mail log, and Web operation log)
• For display examples, see section 2.10.
• Operator
The following operations can be carried out in addition to the functions available on the monitor page.
• Switch the display on the XL100 by specifying the display type (trend, digital, or bar graph) and group.
• All operations except the HOLD key operation can be carried out.
• Monitor Page
• Enabling/Disabling the Monitor Page
• ON
The monitor page can be displayed on a Web browser.
• OFF
Disables the monitor page.
• Enabling/Disabling Access Control
• ON
Enables access control. You must enter the user name and password to display the monitor page.
• OFF
Disables access control.
• Setting the User Name
Enter the user name using up to 16 characters.
• Setting the Password
Enter the password using up to six alphanumeric characters.
• Operator Page
• Enabling/Disabling the Operator Page
• ON
The operator page can be displayed on the browser.
• OFF
Disables the operator page.
• Enabling/Disabling Access Control
• ON
Enables access control. You must enter the user name and password to display the operator page.
• OFF
Disables access control.
IM XL100C-E
IM XL100C-E
2.9 Setting the Web Server Function
• Setting the User Name
Enter the user name using up to 16 characters.
• Setting the Password
Enter the password using up to six alphanumeric characters.
• Saving the Settings
To activate the settings that have been changed in the basic setting mode, the settings must be saved. Otherwise, the settings that existed before the change are activated.
Procedure
1.
Press SETTING to enter Setting Mode.
1
2
3
4
5
2.
Use the arrow keys to select COMMUNICATION, and press SELECT.
6
7
→
App
Index
3.
Use the arrow keys to select NETWORK FUNC., and press SELECT.
→
4.
Use the arrow keys to select WEB SERVER, and press SELECT.
→
5.
Use the arrow keys to select the desired item, and press SELECT.
Press SELECT to show a selection list or window for setting the item.
2-19
2.9 Setting the Web Server Function
6.
Select or enter the item on the displayed selection list or window.
7.
Press SET.
2-20
IM XL100C-E
2.10 Showing and Using the Monitor or Operator
Page
This section describes how to show the monitor page and operator page on the Web browser and the operation on each page.
• Web Browsers That Can Be Used
Operations have been confirmed on the following Web browser.
• Microsoft Internet Explorer 6.0
• Setting the URL
Set the URL (Uniform Resource Locator) appropriately according to the network environment that you are using. You can access the XL100 by setting the URL as follows:
http://host name.domain name/file name
• http: Protocol used to access the server. HTTP stands for HyperText Transfer
Protocol.
• Host name.domain name: Host name and domain name of the XL100. You can also use the IP address in place of the host name and domain name.
• File name: File name of the monitor page and operator page of the XL100.
File name of the monitor page: monitor.htm
File name of the operator page: operator.htm
Omitting the file name is equivalent to specifying the monitor page. However, if the monitor page is disabled, it is equivalent to specifying the operator page.
Example
To display the operator page using Internet Explorer on a PC in the same domain as the XL100 (the domain name, host name, and IP address are assumed to be
good.com, XL, and 123.45.67.89, respectively).
URL: http://XL.good.com/operator.htm or
URL: http://123.45.67.89/operator.htm
• Contents of the Monitor Page
• Display Shown by the XL100
• The display shown on the XL100 (waveform, digital, bar graph, review, alarm summary, or log) is displayed on the monitor page.
• If the XL100 is in the Setting Mode or File Operation Mode, the monitor page cannot be displayed. An error message is displayed.
• Refreshing the Monitor Page
The monitor page can be refreshed automatically or manually.
• Auto refresh ON
The monitor page is refreshed at the specified interval selected from 2, 5, 10, or
30 s.
• Auto refresh OFF
The monitor page is not automatically refreshed. You can refresh the page manually. Within 2 s of the last refreshing, the page is not refreshed even if you attempt to refresh the page manually.
• Zooming in or out of the Display
The display shown on the XL100 can be expanded to 200%.
1
2
3
4
5
6
7
App
Index
2-21
IM XL100C-E
2.10 Showing and Using the Monitor or Operator Page
2-22
• Contents of the Operator Page
On the operator page, the following operations can be carried out in addition to the information available on the monitor page.
Switching to Setting Mode or File Operation Mode
You can switch the XL100 to Setting Mode or File Operation Mode, and carry out operations in the same fashion as when operating the XL100 directly using keys.
IM XL100C-E
2.11 Setting the E-mail Transmission Function
To use the e-mail transmission function, set the following parameters in addition to those described in section 2.3, “Setting the Ethernet Interface.”
• Basic Settings of E-mail Transmission
• SMTP* Server Name
Set the SMTP server name (up to 64 alphanumeric characters) or the IP address of the SMTP server.
* Simple Mail Transfer Protocol
• Port Number
Set the port number to be used. The default setting is 25.
• Recipient 1
Set the recipient of the e-mail message using up to 150 alphanumeric characters.
You can specify multiple addresses. To specify multiple addresses, delimit the addresses using spaces.
• Recipient 2
Set the recipient of the e-mail message using up to 150 alphanumeric characters.
You can specify multiple addresses. To specify multiple addresses, delimit the addresses using spaces.
• Sender
Set the e-mail address that has been provided by the network administrator using up to 64 alphanumeric characters. If omitted, the sender is set to the first address specified as the recipient.
• Settings for Transmitting Alarm Information
• Recipient 1, Recipient 2
You can turn ON/OFF the function for each recipient.
• ON
Transmits e-mail messages to the recipient.
• OFF
Does not transmit e-mail messages to the recipient.
• Contents of the Transmitted Mail
• Add Inst. Data
• ON
The instantaneous values of all channels are included in the e-mail message.
• Off
The instantaneous values are not included in the e-mail message.
• Add Source URL (Uniform Resource Locator)
• ON
If the Web server function is specified on the XL100, the URL of the XL100 is attached to the e-mail.
• OFF
The URL of the XL100 is not attached to the e-mail.
• Subject
Set the subject of the e-mail message using up to 32 alphanumeric characters.
The default setting is “(XL100)Alarm_summary.”
• Header 1
Set the string to be attached to the e-mail message using up to 64 alphanumeric characters.
• Header 2
Set the string to be attached to the e-mail message using up to 64 alphanumeric characters.
2-23
2
3
4
5
6
7
App
Index
IM XL100C-E
1
2.11 Setting the E-mail Transmission Function
• Settings When Transmitting E-mail Messages at the Specified Time
• Recipient 1, Recipient 2
You can turn ON/OFF the function for each recipient.
• ON
Transmits e-mail messages to the recipient.
• OFF
Does not transmit e-mail messages to the recipient.
• Interval
Time interval used to repeat the e-mail transmission starting from the
REFERENCE TIME. Select from the following:
1h, 2h, 3h, 4h, 6h, 8h, 12h, or 24h
• REFERENCE TIME
The time when the e-mail message is to be transmitted. In addition, the e-mail transmission is repeated at the specified interval from this point. Specify the time in the following range for each recipient.
00:00 to 23:59
Example: If Reference time is 17:15 and Interval is 8h, e-mail messages are transmitted at 17:15, 01:15, and 09:15.
• Contents of the Transmitted Mail
• Add Inst. Data
• ON
Attaches to the e-mail message the instantaneous values of all channels existing at the time of e-mail transmission.
• OFF
The instantaneous values are not attached to the e-mail message.
• Add Source URL (Uniform Resource Locator)
• ON
If the Web server function is specified on the XL100, the URL of the XL100 is attached to the e-mail.
• OFF
The URL of the XL100 is not attached to the e-mail.
• Subject
Set the subject of the e-mail message using up to 32 alphanumeric characters.
The default value is “(XL100)Periodic_data.”
• Header 1
Set the string to be attached to the e-mail message using up to 64 alphanumeric characters.
• Header 2
Set the string to be attached to the e-mail message using up to 64 alphanumeric characters.
• Settings When Transmitting E-mail Messages at the Time of Recovery from a
Power Failure (System Error Settings)
For the transmitted contents of the system mail, see section 1.2.
• Recipient 1, Sender
You can turn ON/OFF the function for each recipient.
• ON
Transmits e-mail messages to the recipient.
• OFF
Does not transmit e-mail messages to the recipient.
2-24
IM XL100C-E
IM XL100C-E
2.11 Setting the E-mail Transmission Function
• Contents of the Transmitted Mail
• Include Source URL (Uniform Resource Locator)
• ON
If the Web server function is specified on the XL100, the URL of the XL100 is attached to the e-mail.
• OFF
The URL of the XL100 is not attached to the e-mail.
• Subject
Set the subject of the e-mail message using up to 32 alphanumeric characters.
The default setting is “(XL100)System_warning.”
• Header 1
Set the string to be attached to the e-mail message using up to 64 alphanumeric characters.
• Header 2
Set the string to be attached to the e-mail message using up to 64 alphanumeric characters.
Procedure
1.
Press SETTING to enter Setting Mode.
1
2
3
4
5
6
7
2.
Use the arrow keys to select COMMUNICATION, and press SELECT.
App
Index
→
3.
Use the arrow keys to select NETWORK FUNC., and press SELECT.
→
2-25
2.11 Setting the E-mail Transmission Function
4.
Use the arrow keys to select E-MAIL, and press SELECT.
→
5.
Use the arrow keys to select the desired item, and press SELECT.
Press SELECT to show a window for setting the item.
• Basic setting display
• Alarm information transmission setting display
• Designated time setting page 1/2
• Designated time setting page 2/2
2-26
IM XL100C-E
IM XL100C-E
2.11 Setting the E-mail Transmission Function
• System error transmission setting display
1
6.
Select or enter the item on the displayed selection list or window.
7.
Press SET.
2
3
4
5
6
7
App
Index
2-27
2-28
2.12 E-mail Transmission Test
You can transmit test e-mail messages to recipient 1 or recipient 2 that you specified to confirm whether e-mail messages can be transmitted.
• Items to Check before Performing This Test
• Connect the Ethernet cable correctly. For the connection procedure, see section
2.2.
• Check that the Ethernet interface settings are correct. For the procedure, see section 2.3.
• Check that the e-mail settings are correct. For the procedure, see section 2.11.
When setting the Ethernet interface or e-mail, check the settings with your system or network administrator.
• Checking the Results of the E-mail Transmission Test
• The result of the e-mail transmission test can be confirmed by displaying the e-mail log (displayed on the XL100 (see section 2.8)) or Web screen (see section 2.10) or by outputting the result using the FL command (see section 5.9).
• If an error message is displayed on the XL100, see chapter 8, “Error Messages.”
• Contents of the Test E-mail Message
The figure below shows the contents of the test e-mail message.
Test mail example
From: [email protected]
Date: Mon, 5 Dec 2005 07:15:41 +0900 (JST)
Subject: (XL) Test_mail
Test mail
<Host name>
XL
<Time of transmission>
12/05 07:15:35
Procedure
1.
Press SETTING to enter Setting Mode.
IM XL100C-E
IM XL100C-E
2.12 E-mail Transmission Test
2.
Use the arrow keys to select COMMUNICATION, and press SELECT.
1
→
3.
Use the arrow keys to select NETWORK FUNC., and press SELECT.
2
3
4
5
→
4.
Use the arrow keys to select E-MAIL , and press SELECT.
6
7
→
App
5.
With BASIC selected, press SELECT.
Index
6.
Use the arrow keys to select E-MAIL TRANSMISSION TEST, and press SELECT.
Press SELECT to send the mail.
2-29
2-30
2.13 Starting/Stopping E-mail Transmissions
• Starting/Stopping E-mail Transmissions
• If E-MAIL SETTINGS > BASIC SETTINGS > E-MAIL TRANSMISSION is turned
ON, the e-mail transmission function is enabled.
• If E-MAIL SETTINGS > BASIC SETTINGS > E-MAIL TRANSMISSION is turned
OFF, the e-mail transmission function is disabled. Unsent e-mail messages are cleared.
Note
• If the XL100 enters the basic setting mode while the e-mail transmission is turned ON, the e-mail transmission is stopped. If the XL100 returns to the operation mode from the basic setting mode, the condition that existed before entering the basic setting mode is resumed.
• If e-mail transmission fails, the message is retransmitted up to twice at 30-s intervals. If retransmission fails, the e-mail message is discarded.
• Contents of the E-mail Message
The figure below shows examples of an e-mail messages.
• Alarm mail example
From: [email protected]
Date: Fri, 5 Aug 2005 08:12:48 +0900 (JST)
Subject: (XL) Alarm_summary
To: [email protected], [email protected]
Subject
LOOP1
TEMPERATURE
Header 1
Header 2
Alarm summary
<Host name>
XL
Channel number
Number/Type
Date/Time of alarm occurrence/release
<CH>02
<Type>1L
<On>08/05 08:10:13
<Off>08/05 08:12:07
<Instantaneous value>
08/05 08:12:07
01=0.021V
02=-0.041V
03=-0.011V
•
•
29=-0.541V
30=-0.546V
The XL100 display can be seen at the following URL.
http://XL.good.co.jp/
Instantaneous value
(When Include INST is specified)
• Date/Time
• Channel number
• Instantaneous value
URL
(When Include source URL is specified)
• System mail example
From: [email protected]
Date: Fri, 5 Aug 2005 08:12:48 +0900 (JST)
Subject: (XL) System_warning
To: [email protected], [email protected]
Subject
LOOP1
RAW MATERIAL
Memory full
<Host name>XL
08/05 08:12:48
<Media remaining> 53 KB
<Memory remaining> 1 hour
Header 1
Header 2
The reason for the e-mail transmission
Detailed message
(Media remaining is output when an external storage medium is inserted in the slot when data is saved.)
IM XL100C-E
Chapter 3 Serial Interface
3.1
RS-232 Interface Specifications and Setup
Procedure
The RS-232 serial interface specifications of the XL100 are given below.
Item
Connector type
Electrical and mechanical specifications
Connection type
Transmission mode
Synchronization
Baud rate
Start bit
Data length
Parity
Stop bit
Handshaking
(Flow control)
Received buffer length
Specifications
Mini DIN, 8 pins
Conforms to EIA-232
Point-to-point
Full-duplex
Start-stop synchronization
Select 2400, 4800, 9600, 19200, or 38400 bps.
Fixed to 1 bit
Select 7 or 8 bits
Select Odd, Even, or None (no parity).
Select 1 or 2 bits
Select XON/XOFF control or CS/RS control
2047 bytes
• RS-232 Connector Pin Arrangement and Signal Names
5
4
8
2
7
6
1
3
Pin Number Signal Name
1 CS (Clear to Send)
2
3
4
RD (Received Data)
RS (Request to Send)
SD (Send Data)
8 SG (Signal Ground)
* Pins 5, 6, and 7 are not used.
Meaning
Handshaking signal when transmitting data to the connected device. This is an input signal to the L100.
Received data from the connected device. This is an input signal to the XL100.
Handshaking signal when receiving data from the connected device. This is an output signal from the
XL100.
Transmitted data to the connected device. This is an output signal from the XL100.
Signal ground.
• Connection Procedure
Use the dedicated communication cable for the interface cable.
• For the PC. D-sub 9-pin (91011)
• For the PC. D-sub 25-pin (91009)
• For the printer (91010)
1
2
3
4
5
6
7
App
Index
3-1
IM XL100C-E
3.1 RS-232 Interface Specifications and Setup Procedure
Handshaking Method
When using the RS-232 interface for transferring data, it is necessary for equipment on both sides to agree on a set of rules to ensure the proper transfer of data. The set of rules is called handshaking. Because there are various handshaking methods that can be used between the XL100 and the PC, you must make sure that the same method is chosen by both the XL100 and the PC.
You can choose any of the three methods on the XL100 in the table below.
Handshaking
Table of Handshaking Methods (Yes indicates that it is supported)
Data Sending Control
(Control used when sending data to a PC)
Software
Handshaking
Hardware
Handshaking
Data Receiving Control
(Control used when receiving data from a PC)
Software
Handshaking
Hardware
Handshaking
Stops transmission when X-OFF is received.
Resume when
X-ON is received.
Stops sending when
CS (CTS) is false.
Resumes when it is true.
No handshaking
Sends X-OFF when the receive
Sets RS (RTS) to False when the receive data data buffer is 3/4 full. Sends X-ON when the receive buffer is 3/4 full. Sets
RS (RTS) to True when data buffer is
1/4th full.
the receive data buffer becomes 1/4 full.
No handshaking
O F F
X O N / X O F F
C S / R S
3-2
• OFF
• Data transmission control
There is no handshaking between the XL100 and the PC. The “X-OFF” and “X-ON” signals received from the PC are treated as data, and the CS signal is ignored.
• Data reception control
There is no handshaking between the XL100 and the PC. When the received buffer becomes full, all of the data that overflows are discarded.
RS = True (fixed).
• XON/XOFF
• Data transmission control
Software handshaking is performed between the XL100 and the PC. When an “X-
OFF” code is received while sending data to the PC, the XL100 stops the data transmission. When the XL100 receives the next “X-ON” code, the XL100 resumes the data transmission. The CS signal received from the PC is ignored.
• Data reception control
Software handshaking is performed between the XL100 and the PC. When the free area of the received buffer decreases to 1537 bytes, the XL100 sends an “X-OFF” code. When the free area increases to 511 bytes, the XL100 sends an “X-ON” code.
RS = True (fixed).
• CS/RS
• Data transmission control
Hardware handshaking is performed between the XL100 and the PC. When the CS signal becomes False while sending data to the PC, the XL100 stops the data transmission. When the CS signal becomes True, the XL100 resumes the data transmission. The “X-OFF” and “X-ON” signals received from the PC are treated as data.
• Data reception control
Hardware handshaking is performed between the XL100 and the PC. When the free area of the received buffer decreases to 1537 bytes, the XL100 sets
“RS=False.” When the free area increases to 511 bytes, the XL100 sets
“RS=True.”
IM XL100C-E
3.1 RS-232 Interface Specifications and Setup Procedure
Precautions Regarding Data Reception Control
When handshaking is used to control the reception of data, data may still be sent from the PC even if the free space in the receive buffer drops below 256 bytes. In this case, after the receive buffer becomes full, the excess data will be lost, whether or not handshaking is in effect. Data storage of data resumes when there is free space in the buffer.
Setting the RS-232 Interface
• Selecting the Slave Address
Select the address from the following values.
1 to 32
• Selecting the Baud Rate
Select the baud rate from the following:
1200, 2400, 4800, 9600, 19200, or 38400
• Setting the Data Length
Select the data length from below. To output data in binary format, be sure to set the data length to 8 bits.
7 or 8
• Setting the Stop Bit
Select the stop bit from the following:
1 or 2
• Selecting the Parity Check
Select the parity check from the following:
ODD, EVEN, or NONE
• Selecting the handshaking
Select the handshaking method from the following.
OFF, XON/XOFF, or CS/RS
Procedure
1.
Press SETTING to enter Setting Mode.
1
2
3
4
5
6
7
App
Index
IM XL100C-E
2.
Use the arrow keys to select COMMUNICATION, and press SELECT.
→
3-3
3.1 RS-232 Interface Specifications and Setup Procedure
3.
Use the arrow keys to select SERIAL COMM., and press SELECT.
→
4.
With PARAMETERS selected, press SELECT.
Press SELECT to showPARAMETERS setting window.
5.
Select or enter the item on the displayed selection list or window.
6.
Press SET.
3-4
IM XL100C-E
3.2
RS-485 Interface Specifications and Setup
Procedure
Specifications
Item
Terminal block type
Electrical and mechanical specifications
Connection type
Transmission mode
Synchronization
Baud rate
Start bit
Data length
Parity
Stop bit
Received buffer length
Escape sequence
Electrical characteristics
Communication distance
Terminator
Specifications
Number of terminals: 6, terminal attachment screws:
ISO M4/nominal length of 6 mm
Conforms to the EIA-485 (RS-485)
Multi-drop (1:32)
Half-duplex
Start-stop synchronization
Select 1200, 2400, 4800, 9600, 19200, 38400, 57600, or 115200 bps
Fixed to 1 bit
Select 7 or 8 bits
Select Odd, Even, or None (no parity).
Fixed to 1 bit
2047 bytes
Open and close
Three terminals, SG, +, and –
Up to 1.2 km (when using two shielded twisted-pair cables, AWG 24)
External: 120 Ω recommended, 1/2W (connect externally between the + and – terminals)
• RS-485 Terminal Arrangement and Signal Names
SG
1
2
3
4
5
6
7
App
Signal Name
+
–
SG (Signal Ground)
Meaning
Data (+).
Data (–).
Signal ground.
Connection Procedure
Up to 31 stations can be connected to a host calculater. The following figure shows an example when connecting to a PC.
PC
Index
RS-232
RS-232 / RS-485
Converter
+ – SG
Terminator ON
XL100
SG
SG
XL100
SG
SG
XL100
SG
SG
Connect a 120 Ω
terminator
Communication cable
Communication cable
Up to 31 stations
Pair
3-5
IM XL100C-E
3.2 RS-485 Interface Specifications and Setup Procedure
Setting the RS-485 Interface
• Selecting the Slave Address
Select the address from the following values.
1 to 32
• Selecting the Baud Rate
Select the baud rate from the following:
1200, 2400, 4800, 9600, 19200, 38400, 57600, or 115200
• Setting the Data Length
Select the data length from below. To output data in binary format, be sure to set the data length to 8 bits.
7 or 8
• Selecting the Parity Check
Select the parity check from the following:
ODD, EVEN, or NONE
Procedure
1.
Press SETTING to enter Setting Mode.
3-6
2.
Use the arrow keys to select COMMUNICATION, and press SELECT.
→
3.
Use the arrow keys to select SERIAL COMM., and press SELECT.
→
IM XL100C-E
IM XL100C-E
3.2 RS-485 Interface Specifications and Setup Procedure
4.
Use the arrow keys to select the desired item, and press SELECT.
1
2
5.
Select the item from the displayed list.
6.
Press SET.
3
4
5
6
7
App
Index
3-7
3-8
3.3
USB Communication Specifications and Setup
Procedure
When using the USB for serial communication, the XL100 is connected as a device to a host calculater such as a PC.
The only communication protocol that can be used is normal protocol (Yokogawa Meters
& Instruments proprietary protocol).
Client End
Item
Number of ports
Electrical and mechanical specifications
Connector
Power supply
PC system supported
Specifications
1
Conforms to USB Rev.1.1
5-pin Mini-B receptacle
Self-powered
A PC running Windows 98 SE, Windows Me, Windows 2000, or
Windows XP that is equipped with a USB port as standard (a separate device driver is required for the connection with a PC)
Connection Procedure of the USB Communication Interface
Connect a USB cable to the Mini-B connector on the XL100 and a USB hub or a type A connector of a PC on the host calculater end.
Setting the USB Interface
Set the following item.
Setting the USB ID
Set the USB ID number of the XL100 within the following range.
00 to 31
You can connect multiple devices to a host controller on the USB. If the XL100 is connected to multiple devices in a single USB system, the USB ID number is used by the host controller to identify each device. Therefore, unique ID numbers must be assigned to the XL100s within a single system.
Note
Do not change the USB ID number while using the USB.
Procedure
1.
Press SETTING to enter Setting Mode.
IM XL100C-E
IM XL100C-E
3.3 USB Communication Specifications and Setup Procedure
2.
Use the arrow keys to select COMMUNICATION, and press SELECT.
1
2
→
3
3.
Use the arrow keys to select USB, and press SELECT.
4
5
→
4.
Press SELECT to show the USB ID selection list.
5.
Use the arrow keys to select the USB ID, and press SELECT.
6.
Press SET.
6
7
App
Index
3-9
Chapter 4 Modbus Protocol
4.1
Modbus Protocol Specifications and Function
Codes
The Modbus protocol can be used only on the serial interface (RS-232 or RS-485).
Modbus Specifications
The Modbus specifications of the XL100 are as follows:
Specifications
Transmission media
Baud rate
Start bit
Stop bit
Parity
Transmission mode
Data length
Error detection
Data interval
Slave address
Description
RS-232 or RS-485
Select 1200, 2400, 4800, 9600, 19200, 38400, 57600, or 115200 bps
(57600 and 115200 are selectable only on the RS-485)
Fixed to 1 bit
Select 1 or 2 bits
Select Odd, Even, or None (no parity).
RTU (Remote Terminal Unit) mode or ASCII mode
RTU mode: 8 bits. ASCII mode: Select 7 or 8 bits
RTU mode: Uses error detection CRC-16. ASCII mode: Uses LRC
RTU mode: Determines message termination with a time interval equal to 3.5 characters or more.
ASCII mode: Indicates message termination with CR+LF.
RS-232: 1 to 247
RS-485: 1 to 247
Function Codes of the Modbus Protocol
The function codes of Modbus protocol that the XL100 supports are listed below.
Slave Function
The slave function of the XL100 does not support broadcast commands.
Function Function
Code
3 Read the hold register (4xxxx)
4
6
8
Operation
Read the input register (3xxxx)
The master device can read the communication input data written using function codes 6 and 16.
The master device loads the calculated, measured, and time data of the XL100.
Single write to hold register (4xxxx) The master device writes to the communication input data of the XL100.
Loopback test The master device performs a loopback test of the XL100. The XL100 only supports message return (test code 0x00*).
16 Write to the hold register (4xxxx) The master device writes to the communication input data of the XL100.
* Hexadecimal 00.
Master Function
Function Function
Code
3 Read the hold register
(4xxxx and 4xxxxx)
4 Read the input register
(3xxxx and 3xxxxx)
Operation
Read the hold register data of another device into communication input data (Cxx).
Read the input register data of another device into communication input data (Cxx).
1
2
3
4
5
6
7
App
Index
4-1
IM XL100C-E
4-2
4.2
Register Assignments (for Modbus Slave)
The register assignments when operating as a Modbus slave are shown below. The register data does not contain unit and decimal place information. Set them on the
Modbus master.
Binary values are stored to the register in order from the MSB.
Input Register
:
30001
30024
30201
30301
30302
31001
:
31024
31201
31301
31302
32001
32002
:
32003
32064
:
33001
33032
39001
39002
39003
39004
39005
39006
39007
Data
Measured data of analog input CH01
:
Measured data of analog input CH24
Measured data of pulse input CH
Measured data of logic input CH1
Measured data of logic input CH2
• Input registers 30001 to 30008 and 30001 to 30016 correspond to 8-ch input and 16-ch input, respectively.
• The data is a 16-bit signed integer. The value is the same as the measured data in binary output format.
• The data is set to an integer 1 and 0 when the logic input channel is high and low, respectively.
Alarm status of the measured data of analog input CH01
:
Alarm status of the measured data of analog input CH24
Alarm status of the measured data of pulse input CH
Alarm status of the measured data of logic input CH1
Alarm status of the measured data of logic input CH2
• Input registers 30001 to 30008 and 30001 to 30016 correspond to 8-ch input and 16-ch input, respectively.
• The data is a 16-bit integer. The value is the same as the alarm status in binary output format. The register contains the data in the order “A2A1A4A3.” The
XL100 uses only A1. A2 to A4 are always set to zero.
Calculated data of CA01 (higher 2 bytes)
Calculated data of CA01 (lower 2 bytes)
Calculated data of CA02 (higher 2 bytes)
:
Calculated data of CA32 (lower 2 bytes)
The data is a 32-bit signed integer. Two registers are assigned to each data value. The value is the same as the calculated data in binary output format.
Alarm status of calculated data of CA01
:
Alarm status of calculated data of CA32
Data type and value are the same as those of the alarm status of the measured data.
Year (4 digits)
Month
Day
Hour
Minute
Second
Millisecond
Hold Register Data
:
40001 Communication input data of C001
:
40032 Communication input data of C032
Values in the range of –32768 to 32767 can be written to the hold registers.
IM XL100C-E
4.3
Modbus Error Response (for Modbus Slave)
2
3
When using the Modbus slave function, the XL100 returns the error codes below to the master device. For the error messages related to communications that the XL100 displays, see chapter 8, “Error Messages.”
Code
1
Meaning
Bad function code
Bad register number
Bad number of registers
Cause
Unsupported function request. For a list of supported functions, see section 4.1, “Modbus Protocol Specifications and Function Codes.”
Attempted to read/write to a register that has no corresponding channel.
The specified number of registers is zero.
However, no response is returned in the following cases.
• CRC error
• Errors other than those in the above list.
6
7
4
5
1
2
3
App
Index
4-3
IM XL100C-E
4-4
4.4
Setting the Modbus Master Function
Set the items below to use the Modbus master function.
• Communication Interval
The cycle at which data is read from other devices. Select the read cycle from the following:
100 ms, 200 ms, 500 ms, 1 s, 2 s, 5 s, or 10 s
• Timeout Value
Timeout occurs if a response is not received from the specified slave device within the time specified here (timeout value) after a command is sent from the XL100. The
XL100 repeats the operation of sending a command and waiting for a response for the number of times specified by the retrial value. If no response is received even after waiting the timeout value for all retrials, the XL100 stops sending commands to the slave device for a period equal to 10 times the timeout value. Then, the XL100 tries again. For details, see section 4.5, “Data Dropout Handling of the Modbus
Master.”
Select the timeout time from the following:
100 ms, 200 ms, 500 ms, 1 s, 2 s, 5 s, 10 s, or 1 min
• Retrials
This is the number of times to retransmit the command when there is no response from the specified slave device. If no response is received even after retrying the number of times specified here, the XL100 stops sending commands to the slave device for a period equal to 10 times the timeout value. Then, the XL100 tries again.
For details, see section 4.5, “Data Dropout Handling of the Modbus Master.”
Select the number of retrials from the following:
OFF (0), 1, 2, 3, 4, 5, 10, or 20
• Commands
The commands are used to read the data in the register of slave devices into the communication input data of the XL100 at the read cycle. Consecutive registers of the same data type in a slave device can be registered as a single command and read into consecutive communication input data.
• Enabling/Disabling Commands
Turn ON the command registration line to be used. Up to 32 commands can be registered.
• Read channel (First CH, Last CH)
Set the communication input data (CO01 to CO32) to which the data loaded from the slave device is to be assigned.
• Address
Specify the address of the slave device from the following:
1 to 247
• Register
Specify the register number of the slave device. Since 32-bit data is assigned to two registers, specify the smaller register number (see “Type” below).
Input register: 30001 to 39999, 300001 to 365535
Hold register: 40001 to 49999, 400001 to 465535
• Type
Specify the data type assigned to the Modbus register of the slave device.
• INT16
Specify this type when a “16-bit signed integer” is assigned to the Modbus register.
IM XL100C-E
4.4 Setting the Modbus Master Function
• UINT16
Specify this parameter when a “16-bit unsigned integer” is assigned to the
Modbus register.
• INT32_B
Specify this parameter when a “32-bit signed integer” is assigned to the Modbus register in the order upper 16 bits followed by the lower 16 bits.
Specify the smaller register number (the higher register number in this case) in
[Registers].
• INT32_L
Specify this parameter when a “32-bit signed integer” is assigned to the Modbus register in the order lower 16 bits followed by the upper 16 bits.
Specify the smaller register number (the lower register number in this case) in
[Registers].
• UINT32_B
Specify this parameter when a “32-bit unsigned integer” is assigned to the
Modbus register in the order upper 16 bits followed by the lower 16 bits.
Specify the smaller register number (the higher register number in this case) in
[Registers].
• UINT32_L
Specify this parameter when a “32-bit unsigned integer” is assigned to the
Modbus register in the order lower 16 bits followed by the upper 16 bits.
Specify the smaller register number (the lower register number in this case) in
[Registers].
• FLOAT_B
Specify this parameter when a “32-bit floating-point data” is assigned to the
Modbus register in the order upper 16 bits followed by the lower 16 bits.
Specify the smaller register number (the higher register number in this case) in
[Registers].
• FLOAT_L
Specify this parameter when a “32-bit floating-point data” is assigned to the
Modbus register in the order lower 16 bits followed by the upper 16 bits.
Specify the smaller register number (the lower register number in this case) in
[Registers].
Example (Read multiple points of data using a single command)
If you enter the following settings, the values of register 30001 and register 30002
(both INT16 type) are read into CO01 and CO02, respectively.
1
2
3
4
5
6
7
App
Index
IM XL100C-E
• Displaying the Loaded Data
The loaded data can be specified using CO01 to CO32. The decimal place and the unit of the register data depend on the slave device. Correct the loaded data using the scaling function of the XL100.
4-5
4.4 Setting the Modbus Master Function
Procedure
1.
Press SETTING to enter Setting Mode.
2.
Use the arrow keys to select COMMUNICATION, and press SELECT.
→
3.
Use the arrow keys to select SERIAL COMM., and press SELECT.
→
4.
Use the arrow keys to select MODBUS SETUP, and press SELECT.
• Modbus setup display
4-6
• Modbus settings > communication channel settings display
→
5.
Select or enter the item on the displayed selection list or window, and press SET.
IM XL100C-E
4.5
Data Dropout Handling of the Modbus Master
If the read cycle is exceeded before the response to the previous command is completed when the XL100 is communicating with multiple slave devices, a data dropout occurs from not being able to send the command within the read cycle.
If this happens, change the read cycle, timeout value, and retrials to appropriate settings by referring to the figure below.
1. When the response from the slave device takes a long time
Read cycle
1
2
3
4
Slave device 1
Slave device 2
Slave device 3
Data dropout
(Slave 2 and 3)
Data dropout
(Slave 3)
2. When there is no response from the slave device (retrials = 1)
Read cycle
5
6
7
Slave device 1
Timeout value
Slave device 2
Slave device 3
Data dropout
(Slave 2 and 3)
3. When the XL100 disconnects the relevant slave device for a period equal to 10 times the timeout value and makes a normal recovery at the retrial (disconnects the relevant slave device for a period equal to 110 times the timeout value and makes a normal recovery at the retrial
Read cycle
Time during which slave 2 is disconnected:
10 times the specified timeout
App
Index
Slave device 1
Slave device 2
Slave device 3
Timeout value Timeout value
Data dropout
(Slave 2 and 3)
4-7
IM XL100C-E
4.5 Data Dropout Handling of the Modbus Master
After disconnecting slave 2, retry at the first read cycle after a period equal to
10 times the specified timeout value
Read cycle
Slave device 1
Slave device 2
Slave device 3
Timeout value
Data dropout
(Slave 2 and 3)
Normal recovery
4-8
IM XL100C-E
Chapter 5 Standard Protocol
5.1
Command Syntax
1
The syntax of the setting/basic setting/output commands (see sections 5.3 to 5.10) of the
XL100 is given below. ASCII codes (see appendix 1) are used for the character codes.
For the maintenance/test command syntax, see section 5.11.
?
Command name
Terminator Parameter
Delimiter
Sub delimiter
Command example
SR 02,SKIP;SR 03,VOLT,2V,-1500,1800
Parameter (02 SKIP ... 1800)
Delimiter (,)
Command name (SR)
Sub delimiter (;)
• Command Name
Defined using two alphabet characters.
• Parameters
• Command parameters.
• Set using alphabet characters or numerical values.
• Parameters are separated by delimiters (commas).
• All numerical values are specified using integers.
• When the parameter is a numerical value, the valid range of the value varies depending on the command.
• Spaces around the parameter are discarded. (However, spaces are valid for parameters specified using an ASCII character string.)
• You can omit the parameters that do not need to be changed from their current settings. However, delimiters cannot be omitted.
Example SR 01,,2V<Terminator>
If multiple parameters are omitted and delimiters occur at the end of the command, those delimiters can be omitted.
Example
SR 01,VOLT,,,<Terminator> → SR 01,VOLT<Terminator>
• The number of digits of the following parameters is fixed. If the number is exceeded when entering the command, a syntax error results.
• Date YY/MM/DD (8 characters)
YY: Enter the lower two digits of the year.
MM: Month
DD: Day
• Time HH: MM:SS (8 characters)
HH: Hour
MM: Minute
SS: Second
• Channel number: 2 characters
• Alarm output number: 3 characters
2
3
4
5
6
7
App
Index
5-1
IM XL100C-E
5.1 Command Syntax
• Query
• A question mark is used to specify a query.
• By placing a query after a command or parameter, the setting information of the corresponding command can be queried. Some commands cannot execute queries. For the query syntax of each command, see section 5.2.
• Delimiter
• A comma is used as a delimiter.
• Parameters are separated by delimiters.
• Sub Delimiter
• A semicolon is used as a sub delimiter.
• By separating each command with a sub delimiter, up to 10 commands can be specified one after another. However, the commands and queries cannot be specified one after another. Use them independently.
* If there are consecutive sub delimiters, they are considered to be single. In addition, sub delimiters at the front and at the end are ignored.
Example ; SR01,VOLT;;;SR02,VOLT;<terminator> is taken to be
SR01,VOLT;SR02,VOLT<terminator>.
• Terminator
Use either of the following two characters for the terminator.
• CR+LF ( 0DH 0AH in ASCII code)
• LF ( 0AH in ASCII code)
Note
• Do not specify a channel or alarm output number that is not available on the XL100. If you do, an error will occur.
• The total data length from the first character to the terminator must be less than 2047 bytes.
• Commands are not case sensitive (with the exception of user-specified character strings).
• All the commands that are listed using sub delimiters are executed even if any of the commands in the middle is erroneous.
• Spaces that are inserted before and after a parameter are ignored. However, if spaces are inserted before a command, after a sub delimiter, or after a query, an error occurs.
5-2
IM XL100C-E
5.2
Response Syntax
1
Function
Setting/
Measurement server
The following table shows the types of responses for various commands.
The XL100 returns a response (affirmative/negative response) to a command that is delimited by a single terminator. The controller should follow the one command to one response format. When the command-response rule is not followed, the operation is not guaranteed.
Command Response
Setting command Setting
Control
Affirmative response and
ASCII output response
Basic setting command Negative
Output command Control
Affirmative response response
Setup, measurement, and ASCII output response
BINARY output response
RS-485 and USB RS-485 and USB response No response
The syntax of each response is indicated below.
Affirmative Response Syntax
When the command is processed correctly, an affirmative response is returned.
• Syntax
E0<CRLF>
• Example
E0<CRLF>
Negative Response Syntax
Single Negative Response Syntax
When the command is not processed correctly, a single negative response is returned. For a description of error numbers and error messages, see chapter 8, “Error Messages.”
• Syntax
E1_nnn_mmm...m<CRLF> nnn Error number (001 to 999) mmm...m Message (variable length, one line)
_
• Example
Space
E1 001 “System error”
IM XL100C-E
Multiple Negative Response Syntax
• If there is an error in any one of the multiple commands that are separated by sub delimiters, multiple negative responses are returned.
• The response is generated for each erroneous command.
• If there are multiple commands that have errors, the negative responses are separated by commas.
• The error position number is assigned to the series of commands in order starting with
“1” assigned to the first command.
For a description of error numbers and error messages, see chapter 8, “Error Messages.”
• Syntax
E2_ee:nnn<CRLF>
E2_ee:nnn,ee:nnn,•••,ee:nnn<CRLF> ee
Error position (01 to 10) nnn
_
Error number (001 to 999)
Space
• Example
E2 02:001
(When there is only one error)
(When there are multiple errors)
5-3
2
3
4
5
6
7
App
Index
5.2 Response Syntax
ASCII Output Response Syntax
The basic ASCII output syntax is indicated below.
• Syntax
EA<CRLF>
•••••••••••••••<CRLF>
:
•••••••••••••••<CRLF>
•••••••••••••••<CRLF>
EN<CRLF>
The following types of ASCII data are available.
Query response, decimal place/unit information, measured/calculated data, communication log, FTP log, operation error log, key login log, Web operation log, e-mail log, alarm summary, status information, file list, and user level
Each type of ASCII data is described below.
Query Response
The response syntax of the setting corresponding to a command or parameter with a question mark is indicated below. For the query syntax of each command, see sections
5.4 to 5.11.
• Syntax
EA<CRLF>
...<CRLF>
...
...<CRLF>
EN<CRLF>
• Example
Command
Response
UE?<CRLF>
EA<CRLF>
UE OK<CRLF>
EN<CRLF>
Decimal Place/Unit Information
• The FE command is used to output the data.
• The measured/calculated data that are output using the FD command contains only the mantissa. By combining with the binary display data or the decimal place obtained with the FE command, the correct measured/calculated data can be derived.
• Syntax
The data is output for each channel in the following syntax.
EA<CRLF> s_kccuuuuuu,pp<CRLF>
............
EN<CRLF> s Data status (N, S)
N: Normal
S: Skip (when the input range is set to SKIP for a measurement channel)
5-4
IM XL100C-E
IM XL100C-E
5.2 Response Syntax
k Channel type
0: Measurement channel
P: Pulse channel
A: Calculation channel
C: Communication channel cc Channel number
01 to 32 uuuuuu Unit information (6 characters, left-justified) mV____:mV / V_____:V / ^C____:°C / Mc____:Mc / kc___:kc / rpm__:rpm / xxxxxx: (User-defined character string) pp Decimal place (00 to 04)
No decimal (00000) for 00.
One digit to the right of the decimal (0000.0) for 01.
Two digits to the right of the decimal (000.00) for 02.
Three digits to the right of the decimal (00.000) for 03.
Four digits to the right of the decimal (0.0000) for 04.
_ Space
• Example
EA
N 001mV ,01
N 002mV ,01
EN
Measured/Calculated Data
• The FD command is used to output the data.
• The measured/calculated data that are output using the FD command contains only the mantissa. By combining with the binary display data or the decimal place obtained with the FE command, the correct measured/calculated data can be derived.
• Syntax
The measured/calculated data are output in the following syntax along with the date and time information for each channel.
EA<CRLF>
DATE_yy/mo/dd<CRLF>
TIME_hh:mi:ss.mmmt<CRLF> s_kcca1a2a3a4uuuuuufdddddE-pp<CRLF>
............
EN<CRLF> yy year (00 to 99);mo month (01 to 12);dd day (01 to 31);hh hour (00 to 23);mi minute (00 to 59) ;ss second (00 to 59);mmm millisecond (000 to 999. A period is placed between seconds and milli-seconds)
;t reserved (space) s Data status (N, S, O, E)
N: Normal/ S: Skip/O: Over/E: Error k Channel type
0: Measurement analog channel/P: Pulse channel/D: Logic input channel/A:
Calculation channel/
C: Communication channel cc Channel number
01 to 32
1
2
3
4
5
6
7
App
Index
5-5
5.2 Response Syntax
a1a2a3a4 a1 Alarm status a2 Reserved (space character at all times) a3 Reserved (space character at all times) a4 Reserved (space character at all times)
(H, L, I, O, or space)
( H(High limit alarm)/L(Lower limit alarm)/ I(Window IN alarm)/O(Window OUT alarm))
Reserved ( h, l, T, t, R, and r)
Space (no alarm) uuuuuu Unit information (6 characters, left-justified) mV____:mV/V_____:V/^C____:°C/Mc____:Mc/kc___:kc/rpm__:rpm/xxxxxx: (Userdefined character string) f Sign (+, -) ddddd Mantissa (00000 to 99999, 5 digits)
• Eight digits for calculated data.
• For abnormal data (data status is E) or data of which the mantissa or the exponent exceeds the range (data status is O), the mantissa is set to 99999 (99999999 for calculated data).
pp Exponent (00 to 04)
_ Space
• Example
EA
DATE 05/10/23
TIME 19:56:32.500
N 001h mV +12345E-03
N 002 mV -67890E-01
S 003
EN
Note
• Data for non-existing channels are not output (not even the channel number).
• For channels set to skip, output values from alarm status to exponent are spaces.
Communication Log
• The FL command is used to output the data.
• A log of setting/basic setting/output commands and responses is output. Up to 50 logs are retained. Logs that exceed 50 are cleared from the oldest data.
• Syntax
EA<CRLF> yy/mo/dd_hh:mi:ss_n_uuu...ufd_mmm...m<CRLF>
...............
EN<CRLF> yy Year (00 to 99) mo Month (01 to 12) dd Day (01 to 31) hh Hour (00 to 23) mi Minute (00 to 59) ss Second (00 to 59)
5-6
IM XL100C-E
IM XL100C-E
5.2 Response Syntax
n Connection ID. A number used to identify the user that is connected.
0:
Serial
1 to 3: Ethernet uuu...u User name (up to 16 characters) f Multiple command flag
Space: Single
*: Multiple
(If multiple commands are separated by sub delimiters and output at once, “*” is displayed. The multiple commands are divided at each sub delimiter and stored as individual logs (1 log for 1 command and 1 log for 1 response.) d I/O
>: Input
<: Output mmm...m Message (up to 20 characters)
• The communication log contains only the error number and not the error message section.
• Normally, the transfer data are transmitted as they are, but in some cases, a special message is output. Special messages are indicated below.
Receive
(Over length): Command length exceeded.
(Over number): Command numbers exceeded.
(Serial error): Received an error character through serial communications.
Send
(ddd byte): Data output (where ddd is the number of data values)
(Login): Login
(Logout): Logout
(Disconnected): Forced disconnection (occurs when the connection was disconnected when transmitting data using Ethernet)
(Time out): Timeout, keepalive, TCP retransmission, etc.
E1 nnn: Single negative response (where nnn is the error number)
E2 ee:nnn: Multiple negative response (where ee is the error position and nnn is the error number)
_ Space
• Example
The following example shows the log when multiple commands separated by sub delimiters, “
BO1;???;CS1,” are transmitted. The commands are separated and output in order with the multiple command flag “*.”
EA
99/05/11 12:31:11 1 user *> BO1
99/05/11 12:31:11 1 user *< E0
99/05/11 12:31:11 1 user *> ???
99/05/11 12:31:11 1 user *< E2 01:124
99/05/11 12:31:11 1 user *> CS1
99/05/11 12:31:11 1 user *< E0
EN
1
2
3
4
5
6
7
App
Index
5-7
5.2 Response Syntax
5-8
FTP Log
• The FL command is used to output the data.
• The FTP client log is output. Up to 50 file transfer logs are retained. Logs that exceed
50 are cleared from the oldest data.
• Syntax
EA<CRLF> yy/mo/dd_hh:mi:ss_nnn_xxxxxxxxx_k_ffffffff_eee<CRLF>
•••••••••••••••
EN<CRLF> yy Year (00 to 99) mo Month (01 to 12) dd Day (01 to 31) hh Hour (00 to 23) mi Minute (00 to 59) ss Second (00 to 59) nnn Error code (001 to 999) xxxxxxxxx Detailed code (9 characters) k Server type (FTP destination)
P: Primary
S: Secondary ffffffff File name (8 characters) eee Extension (3 characters)
_ Space
• Example
EA
99/07/26 10:00:00 P 72610000 DDR
99/07/27 10:00:00 P 72710000 DDR
99/07/28 10:00:00 123 HOSTADDR P 72810000 DDR
99/07/29 10:00:00 123 HOSTADDR P 72910000 DDR
EN
Error Message Log
• The FL command is used to output the data.
• The operation error log is output. Up to 50 operation error logs are retained. Logs that exceed 50 are cleared from the oldest data.
• Other communication messages (400 to 999) and status messages (500 to 599) are not output.
• Syntax
EA<CRLF> yy/mo/dd_hh:mi:ss_nnn_uuu•••u<CRLF>
•••••••••••••••
EN<CRLF> yy Year (00 to 99) mo Month (01 to 12) dd Day (01 to 31) hh Hour (00 to 23) mi Minute (00 to 59) ss Second (00 to 59) nnn Error code (001 to 999) uuu...u Error message (up to 80 characters)
IM XL100C-E
IM XL100C-E
5.2 Response Syntax
_ Space
• Example
EA
99/05/11 12:20:00 212 “Format error.”
99/05/11 12:30:00 217 “Unknown file type.”
EN
Key Login Log
• The FL command is used to output the data.
• A log of users that have logged in and logged out is output. Up to 50 login/logout logs are retained. Logs that exceed 50 are cleared from the oldest data.
• If the power goes down while logged in, you will be logged out. In this case, however, it will not be recorded as a logout.
• User number and user name are not output at the time of the logout.
• Syntax
EA<CRLF> yy/mo/dd_hh:mi:ss_xxx_nn_uuu•••u<CRLF>
.........................
EN<CRLF> yy Year (00 to 99) mo Month (01 to 12) dd Day (01 to 31) hh Hour (00 to 23) mi Minute (00 to 59) ss Second (00 to 59) xxx Login or log out (In_ or Out). Output left-justified.
nn User number (01 to 07) uuu...u User name (up to 16 characters)
_ Space
• Example
EA
99/05/11 12:20:00 In 01 administrator
99/05/11 12:30:00 Out
99/05/11 12:20:00 In 03 user
99/05/11 12:30:00 Out
EN
Web Operation Log
• The FL command is used to output the data.
• The log of operations on the Web screen is output. Up to 50 operations are retained.
Logs that exceed 50 are cleared from the oldest data.
• Syntax
EA<CRLF> yy/mo/dd_hh:mm:ss_ffffff_eee_???...?<CRLF>
..........
EN<CRLF>
1
2
3
4
5
6
7
App
Index
5-9
5.2 Response Syntax
yy Year (00 to 99) mo Month (01 to 12) dd Day (01 to 31) hh Hour (00 to 23) mi Minute (00 to 59) ss Second (00 to 59) ffffff Requested operation
SCREEN:
Screen change
KEY: Key operation eee Error code when executing the requested operation
All spaces: Success
001 to 999: Error code
???...? Parameter for each cause (see below)
• When ffffff = SCREEN yy/mo/dd_hh:mm:ss_ffffff_eee_ddddd_nnCRLF ddddd Screen type
TREND:
DIGIT:
Waveform & digital display
Digital display
BAR: Bar graph display nn Group number (01 to 04)
• When ffffff = KEY yy/mo/dd_hh:mm:ss_ffffff_eee_kkkkkCRLF kkkkk Type of key that was operated
ESC:
ESC key
HOME:
REVIEW:
FILE:
SETTING:
HOME key
REVIEW key
FILE key
SETTING key
HOLD: HOLD key
TIMEDIVSHORT:
TIME/DIV left key
TIMEDIVLONG: TIME/DIV right key
RANGE:
RANGE key
SAVE:
DISP:
GROUP:
MARK:
MARKLEFT:
MARKRIGHT:
SET :
STARTSTOP:
HOLD:
UP:
DOWN:
RIGHT:
LEFT:
SELECT:
SAVE key
DISPLAY key
GROUP key
MARK key
MARK left key
MARK right key
SET key
START/STOP key
HOLD key
Up arrow key
Down arrow key
Right arrow key
Left arrow key
SELECT key
- Space
5-10
IM XL100C-E
IM XL100C-E
5.2 Response Syntax
• Example
EA
01/02/11 12:20:00 SCREEN 275 TREND 01
01/02/11 12:21:00 SCREEN BAR 01
01/02/11 12:30:00 KEY UP
01/02/11 12:31:00 KEY RIGHT
01/02/11 12:40:00 MSG 05 Hello-Hello
01/02/11 12:41:00 MSG 05 Hello-Hello
EN
E-mail Log
• The FL command is used to output the data.
• The e-mail transmission log is output. Up to 50 operations are retained. Logs that exceed 50 are cleared from the oldest data.
• Syntax
EA<CRLF> yy/mo/dd_hh:mm:ss_ffffff_eee_n_uuu...u<CRLF>
..........
EN<CRLF> yy Year (00 to 99) mo Month (01 to 12) dd Day (01 to 31) hh Hour (00 to 23) mi Minute (00 to 59) ss Second (00 to 59) ffffff Factor
ALARM: Alarm mail
TIME: Scheduled mail
REPORT:
Reserved
FAIL:
FULL:
TEST:
Power failure recovery mail
Memory full mail
Test mail
ERROR: Error message mail eee Error code
All spaces: Success
001 to 999: Error code n Recipient list
1: List 1
2: List 2
+: List 1 and list 2 uuu...u Array of recipient e-mail addresses (up to 30 characters)
_ Space
• Example
EA
01/05/11 12:20:00 ALARM + notice
01/05/11 12:30:00 REPORT 375 1 user1 user2
EN
1
2
3
4
5
6
7
App
Index
5-11
5.2 Response Syntax
Alarm Summary
• The FL command is used to output the data.
• The alarm summary is output. Up to 120 alarm information sets are retained. Alarm information sets that exceed 120 are cleared from the oldest data.
• Syntax
EA<CRLF> yy/mo/dd_hh:mi:ss_kcc_ls_YY/MO/DD_HH:MM:SS<CRLF>
..........
EN<CRLF> yy Year (00 to 99) mo Month (01 to 12) dd Day
(01 to 31) hh Hour
(00 to 23) mi Minute (00 to 59) ss Second (00 to 59) k Channel type
0: Analog measurement channel
P: Pulse measurement channel
D: Logic input channel
A: Calculation channel
C: Communication channel cc Channel number
01 to 32 l Alarm level (fixed to 1) s Alarm type (H, L, I, or O)
YY/MO/DD HH:MM:SS Alarm release time (alarm release time is not output if the alarm has not been released)
YY Year (00 to 99)
MO Month (01 to 12)
DD Day (01 to 31)
HH Hour
(00 to 23)
MM Minute (00 to 59)
SS Second (00 to 59)
_ Space
• Example
EA
01/05/11 12:20:00 001 1L 01/05/11 12:25:00
01/05/11 12:30:00 A31 3t
EN
Status Information
• The IS command is used to output the data.
• The operation status of the XL100 is output.
• For details on the status information, see section 6.2, “Bit Structure of the Status
Information.”
• Syntax
EA<CRLF> ddd.ccc.bbb.aaa<CRLF>
EN<CRLF>
5-12
IM XL100C-E
IM XL100C-E
5.2 Response Syntax
aaa Status information 1 (000 to 255) bbb Status information 2 (000 to 255) ccc Status information 3 (000 to 255) ddd Status information 4 (000 to 255)
• Example
EA
000.000.032.000
EN
File List
• The ME command is used to output the data.
• The file list and the file data sizes of the specified directory on the XL100’s external storage medium are output.
• Syntax
EACRLF ffffffff_eee_ssssssss_yy/mo/dd_hh:mi:ss_llllllllll<CRLF>
.................
zzzzzzz Kbyte free<CRLF>
EN<CRLF> ffffffff File name (8 characters)
If this is a directory, the characters <DIR> are shown at the position displaying the file data size.
eee Extension (3 characters) ssssssss Data size of the file (_______0 to 99999999) [byte(s)] yy Year (00 to 99) mo Month (01 to 12) dd Day (01 to 31) hh Hour (00 to 23) mi Minute (00 to 59) ss Second (00 to 59) zzzzzzz Free space on the medium (______0 to 9999999) llllllllll ID number (_________0 to 9999999999)
• The ID number is set to a space.
• The output is a “0” if the file was saved using another instrument.
_ Space
• Example
EA
XV1 DEV 124 99/02/24 20:07:12 12310
XV1 PNL 1204 99/01/19 01:52:37
DATA <DIR> 99/01/19 01:23:64
523 Kbyte free
EN
1
2
3
4
5
6
7
App
Index
5-13
5.2 Response Syntax
User Level
• The FU command is used to output the data.
• User name, user level, and other information are output.
• Syntax
EA<CRLF> p_l_uuu•••u<CRLF>
EN<CRLF> p Physical layer
E: Ethernet
S: RS-232, RS-485, or USB lUser level
A: Administrator privileges
U: User privileges uuu...uUser name (up to 16 characters)
_ Space
• Example
EA
E A admin
EN
Binary Output Syntax
• Basic Syntax
1 byte
'E'
LF
Binary header
(12 bytes)
'B'
CR
Data length
ASCII format
Binary format
Binary data
Binary data
Binary footer
(2 bytes)
Data sum
• EB CRLF
Indicates that the data is binary.
• Data Length
The byte value of “flag + identifier + header sum + binary data + data sum.”
• Header Sum
The sum value of “data length + flag + identifier.”
• Binary Data
For the output format of various data types, see section 5.3.
• Data Sum
The sum value of binary data.
5-14
IM XL100C-E
IM XL100C-E
5.2 Response Syntax
• Flag
1
0
3
2
5
4
7
6
Flag
Bit Name (Abbreviation) 0
BO
CS
–
–
–
–
–
END
1
–
–
MSB
No
–
–
LSB
Yes
–
–
–
–
– –
Middle End
Meaning of the Flag
Output byte order
Existence of a checksum
In the middle or at the end of the continuous data
• When the BO flag is “0,” the MSB is output first. When the BO flag is “1,” the LSB is output first.
• If the check sum is enabled (parameter = 1) using the CS command parameter, each sum value is inserted in the header sum and data sum sections in the “Basic
Syntax” on the previous page. If the check sum is disabled (parameter = 0), a zero is inserted in the header sum and data sum sections.
• If the amount of data output in response to a ME command is large, not all the data may be returned in one output request (parameter GET). In this case the END flag becomes “0.” You must send output requests (parameter NEXT) to receive the rest of the data until the END flag becomes “1.”
• The bits that have “–” for the name and flag are not used. The value is undefined.
• Identifier
ID Number
8
9
10
11
12
13
6
7
4
5
2
3
0
1
Binary Data Type
–
–
Undefined file
Measured/calculated data
–
–
Manual sampled data file
–
–
–
–
–
–
Screen image data
Type
–
–
File (*.*)
Data
–
–
File (*.*)
–
–
–
–
–
–
File (*.*)
Format
–
–
–
–
–
–
–
–
X
–
–
–
–
X
X: Disclosed. –: Common format
• Binary data can be classified by the ID number shown in the table above.
• Binary data comes in two types, data and file.
• Data
• Measured/calculated data can be output using the FD command.
• The data format is disclosed. See the next and subsequent pages.
• File
• Display data, event data, TLOG data, and setting data files can be used on the software program that came with the XL100.
• Files that are in common formats can be opened using software programs that are sold commercially.
• Other formats are written in ASCII code. A text editor can be used to open these types of files.
• The identifier section in the “Basic Syntax” on the previous page contains the
ID number that indicates the binary data type.
Note
Binary data that is not indicated in the above table is considered undefined files.
5-15
1
2
3
4
5
6
7
App
Index
5.2 Response Syntax
• Calculating the Sum Value
If you set the parameter of the CS command to “1 (enabled),” the checksum value is output only during serial communications. The check sum is the same as that used in the TCP/IP and is derived according to the following algorithm.
Buffer on Which the Sum Value Is Calculated
• For the header sum, it is calculated from “data length + flag + identifier” (fixed to 6 bytes).
• The data sum is binary data.
1 byte
Padding
0
(1) (2) (3) (4) (5) (6)
If the data length of the buffer is odd, a “0” is padded so that it is even. (1) through (6) are summed as unsigned two-byte integers (unsigned short). If the digit overflows a
“1” is added. Finally, the result is bit-wise inverted.
Measured/Calculated Binary Data Syntax
• The FD command is used to output the measured/calculated data.
• The ID number of the output format is 1.
• The measured data is output using signed 16-bit integer; the calculated data is output using signed 32-bit integer. These integers can be understood as physical values by adding the decimal point and the unit. The decimal point position can be determined using the FE command.
Example of Deriving Physical Values from Binary Data
Binary Data
10000
10000
10000
10000
10000
3
4
1
2
Decimal Position Code
0
Physical Value (Measured Value)
10000
1000.0
100.00
10.000
1.0000
• Binary Data Format
2 bytes 2 bytes
Number of blocks
Number of bytes
Binary data of block 1
•••
Binary data of block n
• Number of Blocks
This is the number of blocks.
• Number of Bytes
This is the size of one block in bytes.
5-16
IM XL100C-E
IM XL100C-E
5.2 Response Syntax
• Block
1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 2 byte 1 byte 1 byte
Year
M/C
•••
•••
M/C
•••
•••
Month
Channel
•••
•••
Channel
•••
•••
Day
A2A1
•••
•••
A2A1
•••
•••
Hour
A4A3
•••
•••
A4A3
•••
•••
Minute Second
Measured data
•••
•••
Millisecond
Calculated data
•••
•••
(Reserved)*
Flag
4 bytes
* The sections indicated as (Reserved) are not used. The value is undefined.
Block Member
Name
Year
Month
Day
Hour
Minute
Second
Millisecond
(Reserved)
Binary Value
0 to 99
1 to 12
1 to 31
0 to 23
0 to 59
0 to 59
0 to 999
Undefined
Measurement/Calculation
Channel
Alarm status A1 (Bits 0 to 3)
Alarm status A2 (Bits 4 to 7)
Alarm status A3 (Bits 0 to 3)
00H: measurement, 80H: calculation
01 to 60
0 to 11*
Undefined
Undefined
Alarm status A4 (Bits 4 to 7) Undefined
* A binary value 0 to 11 is entered in the upper and lower 4 bits of a byte (8 bits) for the alarm status. The binary value 0 to 11 correspond to different alarm types, H (high limit alarm), L
(low limit alarm, I (window In), and O (window Out) as follows:
0: no alarm, 1: H, 2: L, 10: I, and 11: O
• Special Data Values
The measured/calculated data take on the following values under special conditions.
Special Data Value
+Over
–Over
Skip (OFF)
Error
Undefined
Measured Data
7FFFH
8001H
8002H
8004H
8005H
Math Data
7FFF7FFFH
80018001H
80028002H
80048004H
80058005H
Note
The number of blocks, number of bytes, and measured/calculated data are output according to the byte order specified with the BO command.
1
2
3
4
5
6
7
App
Index
5-17
5.2 Response Syntax
Manual Sampled Data
• The ME or MO command is used to output the data.
• The ID number of the output format is 4.
• The data format is shown below.
Setup data
.
.
MODEL,XL100,T004
VERSION,1.00
TEMP_UNIT,degC
Blank line
Data header
Unit header
DATE,TIME,CH01,CH02,
,,V,V,V,V,V,degC,
....
....
Measured data
.
.
2005/03/27,14:30:00,0.000
2005/03/27,14:31:00,0.000
.
....
....
Screen Image Data
The screen image data is output to a bitmap file in BMP format.
RS-485 and USB Communication Dedicated Syntax
The following table shows dedicated commands for the RS-485 interface and their responses when Yokogawa Meters & Instruments proprietary protocol is specified.
Command Syntax
<ESC>O<SPC>xx<CRLF>
<ESC>C<SPC>xx<CRLF>
Meaning
Open the device
Close the device.
Response
• Response from the device with the specified address
<ESC>O<SPC>xx<CRLF>
• Response when the device with the specified address does not exist*
None
• Response from the device with the specified address
<ESC>C<SPC>xx<CRLF>
• Response when the device with the specified address does not exist*
None
* Some of the possible reasons that cause the condition in which the device with the specified address cannot be found are a command error, the address not matching that of the device, the device is not turned ON, and the device not being connected via the serial interface.
Note
• <ESC> denotes ASCII code 1BH.
• <CRLF> denotes ASCII codes 0DH and 0AH.
• <SPC> denotes a space and its ASCII code is 20H.
• xx indicates the device address. An address in the range of 01 to 99 can be specified here.
• Only one device can be opened at any one time.
• When a device is opened with the ESC O command, all commands on the device become active.
• When a device is opened with the ESC O command, any other device that is open is automatically closed.
• Normally, either <CR>+<LF> or <LF> can be used as a terminator for communication commands. However, the terminator for these commands must be set to CR+LF.
5-18
IM XL100C-E
5.3
A List of Commands
1
Setting Commands
BB
BC
BD
BY
SI
SJ
FR
BA
SQ
SY
SU
SK
SB
SV
SF
SC
Type Command Function
Setting
SW
SZ
SP
ST
SR
SO
SA
SD
SX
SL
SG
SH
SE
Sets the input range and span.
Sets the differential calculation.
Sets the alarm.
Sets the date and time.
Sets the sampling interval.
Reserved
Reserved
Sets the tag.
Sets the group.
Sets the alarm line
Reserved
Reserved
Sets the background color, waveform line width, and alarm line width.
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Sets the alarm delay.
Sets automated measurement and beep sound.
Usable State
Logging stopped/Logging*
Logging stopped/Logging*
Logging stopped
Logging stopped
Logging stopped
Logging stopped
Logging stopped
All
All
Sets the base position of the bar graph display. All
Sets the average.
Reserved
Logging stopped
Sets the channel color and waveform line width. All
Sets the backlight auto save of the display.
Reserved
All
Logging stopped
Logging stopped
Administrator
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
User
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Page
5-25
5-26
5-27
5-27
5-27
5-28
5-28
5-28
5-28
5-28
5-28
5-29
5-29
5-29
5-29
* Only a portion of the parameters such as the span settings can be changed while logging. Yes: Command usable No: Command not usable
Note
• The operation of the XL100 can be divided into two states, logging stopped state and logging state. The logging stopped state includes Free Running Mode, File Operation Mode, Setting Mode, and Review Mode. The logging state includes Logging Mode and Logging & Review Mode.
A syntax error will occur if you attempt to execute a command in the wrong operation state. If this happens, stop the logging operation with the PS command to switch to the
Free Running state, and then execute the command. Query commands can be executed regardless of the operation state.
• Logging stopped state
The settings can be changed in this state.
• Logging state
As a general rule, commands other than those used in the logging stopped state are used in this state.
• The administrator and user specifications in the table indicate the user level that is specified using the login function for Ethernet communications.
For details, see section 2.7.
IM XL100C-E
5-19
2
3
4
5
6
7
App
Index
5.3 A List of Commands
Type Command Function
Control
UD
PS
AK
EV
Switches the display.
Starts/Stops logging.
Usable State
All
All
Confirms the alarm status (alarm acknowledge). All
Saves the manual sampled or screen image Logging stopped data to the external storage medium.
Reserved
LI
CM
EM
KE
MS
TL
DS
LO
Reserved
Reserved
Loads the setting data.
Saves the setting data.
Sets the communication input data.
Starts/Stops e-mail messages.
Key operation command
Logging stopped
Logging stopped
Logging stopped
All
All
Yes: Command usable
Administrator User Page
Yes
Yes
Yes
Yes
No
No
No
No
5-30
5-30
5-30
5-30
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No: Command not usable
5-30
5-30
5-30
5-31
5-31
5-20
IM XL100C-E
5.3 A List of Commands
Basic Setting Commands
• In order to activate the settings that are changed using the basic setting commands, the basic settings must be saved using the XE command. Be sure to save the settings with the XE command before starting the logging operation from a logging stopped state. If you do not, the settings before the change are activated.
• The settings that are returned in response to a query while logging is stopped will contain the new settings even if they are not saved with the XE command. However, the new settings will not be activated until they are saved. In order to activate the new settings, the XE command must be issued as described earlier. If you discard the settings with the XE command or start the logging operation from a logging stopped state before saving the settings with the XE command, the settings that are returned in response to a query are those before the change.
Administrator User Page Type Command Function
Setting
XD
XO
XT
XK
XR
XQ
RO
RM
XV
XS
XM
XU
XA
XI
XB
XJ
XP
XY
YA
XL
XH
XE
XG
Sets the alarm.
Reserved
Burnout (query only)
RJC (query only)
Sets the sampling interval.
Reserved
Reserved
Sets the language.
Reserved
Reserved
Reserved
Reserved
Sets the external storage medium.
Selects the communication method.
Selects the trigger.
Selects the start trigger.
Selects the end trigger.
Sets the key login and auto logout functions.
Logging stopped
Sets whether or not to store the basic settings. Logging stopped
Sets the time zone.
Reserved
Sets the statistical calculation.
Sets the IP address, subnet mask, and default gateway.
Usable State
Logging stopped
All
All
Logging stopped
Logging stopped
Logging stopped
Logging stopped
Logging stopped
Logging stopped
Logging stopped
Logging stopped
Logging stopped
Logging stopped
YQ
YS
YO
YI
YC
YB
YK
YN
YE
Shows the IPV6 settings (query only).
Sets the keepalive.
Sets the DNS.
Sets the SNTP (time synchronization function). Logging stopped
Sets the communication timeout.
Sets the serial interface.
Loads the setting data.
Saves the setting data.
Logging stopped
Logging stopped
Logging stopped
Logging stopped
Logging stopped
Logging stopped
Resets the system (clears the measured/calculated Logging stopped
YT
YG
YL
YM data and initializes the setting data) .
Sets the FTP transfer timing.
Logging stopped
Sets whether to use the Web server function.
Logging stopped
Sets the operation of the Modbus master function. Logging stopped
Sets the command of the Modbus master function. Logging stopped
Yes: Command usable
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
No
No
No
No
No
No
No
No
No
Yes
No
No
No
No
No
No
No
No
No
No
No
5-31
5-31
5-32
5-32
5-32
Yes
Yes
Yes
Yes
No
No
No
No
No: Command not usable
5-36
5-36
5-36
5-36
5-34
5-34
5-35
5-35
5-35
5-35
5-36
5-36
5-36
5-32
5-32
5-32
5-32
5-33
5-34
5-34
5-34
5-34
5-34
1
2
3
4
5
6
7
App
Index
IM XL100C-E
5-21
5.3 A List of Commands
Type Command Function
Basic settings
YU
YV
YW
YX
Sets the contents to be sent via e-mail.
Sets the e-mail recipient address.
Sets the e-mail sender address.
Sets the e-mail SMTP server name.
Usable State
Logging stopped
Logging stopped
Logging stopped
Logging stopped
Yes: Command usable
Output Commands
Type Command Function
Control
BO
CS
Sets the byte output order.
Sets the check sum.
IF
CC
ID
(can be used only during serial communication)
Sets the status filter.
All
Disconnects Ethernet connection.
Outputs the system data.
Usable State
All
All
All
All
Setting, measurement, and control data output
FC
Outputs the screen image data.
FE
FD
Outputs the setting data.
Logging stopped
Logging stopped
Outputs the most recent measured/calculated data. All
FF
FL
IS
FU
ME
Reserved
Outputs the log and alarm summary.
Outputs status information.
Outputs the user level
All
All
All
Outputs the data saved to the external storage Logging stopped medium (can be used with Ethernet or serial communication).
MI
MO
Reserved
Reserved
RS-485 and USB dedicated commands
Esc O
Opens the device.
Esc C
Closes the device.
All
All
Yes: Command usable
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Administrator User Page
Yes
Yes
Yes
Yes
No
No
No
No
No: Command not usable
5-37
5-38
5-38
5-38
Administrator User Page
Yes
Yes
Yes
Yes
5-38
5-38
Yes
Yes
Yes
Yes
Yes
Yes
5-38
5-38
5-39
Yes
Yes
Yes
Yes
Yes
Yes
No
5-39
5-39
5-40
5-40
5-40
5-40
5-40
Yes
Yes
Yes
Yes
No: Command not usable
5-41
5-41
Maintenance/Test Commands (Available when using the maintenance/test server function via Ethernet communications)
User Type Command Function
Maintenance/Test close con eth help net quit
Administrator
Disconnects the connection between other devices Yes
Outputs connection information.
Outputs Ethernet statistical information.
Outputs help.
Outputs network statistical information.
Disconnects the connection of the device
Yes
Yes
Yes
Yes
Yes being operated.
Yes: Command usable
No
Yes
Yes
Yes
Yes
Yes
No: Command not usable
Page
5-42
5-42
5-42
5-42
5-42
5-43
5-22
IM XL100C-E
5.4
Input Range Parameters
1
The following tables show which input ranges of the instrument correspond to the channel modes of the SR command (input range setting command), VOLT, TC, RTD, pulse, and logic. The tables also show the ranges for the upper and lower limits of the span.
• DC voltage (VOLT)
Input Range Range Parameter Selectable Range of Span Range of Span Parameter of the SR Command Upper and Lower Limits of the SR Command of the Input Range
100 mV
500 mV
100mV
500mV
-100.00 to 100.00 mV
-500.0 to 500.0 mV
-10000 to 10000
-5000 to 5000
1 V
5 V
10 V
30 V
1-5 V
1V
5V
10V
30V
1-5V
-1.0000 to 1.0000 V
-5.000 to 5.000 V
-10.000 to 10.000 V
-30.00 to 30.00 V
1.000 to 5.000 V
-10000 to 10000
-5000 to 5000
-10000 to 10000
-3000 to 3000
1000 to 5000
• Thermocouple (TC)
Input Range Range Parameter of the SR Command
Selectable Range of Span Range of Span Parameter
Upper and Lower Limits of the Input Range
of the SR Command
R
S
R
S
0.0 to 1768°C
0.0 to 1768°C
0 to 1768
0 to 1768
B B 600 to 1800
K
E
J
T
N
K
E
J
T
N
600 to 1800°C
-200.0 to 1372.0°C
-200.0 to 1000.0°C
-200.0 to 1200.0°C
-200.0 to 400.0°C
0.0 to 1300.0°C
-2000 to 13720
-2000 to 10000
-2000 to 12000
-2000 to 4000
0 to 13000
W
L
U
W
L
U
0 to 2315°C
-200.0 to 900.0°C
-200.0 to 400.0°C
0 to 2315
-2000 to 9000
-2000 to 4000
• RTD
Input Range Range Parameter Selectable Range of Span Range of Span Parameter of the SR Command Upper and Lower Limits of the SR Command of the Input Range
Pt100
JPt100
PT
JPT
-200.0 to 850.0°C
-200.0 to 500.0°C
-2000 to 8500
-2000 to 5000
• Logic
Input Range Range Parameter Selectable Range of Span Range of Span Parameter of the SR Command Upper and Lower Limits of the SR Command of the Input Range
None NONE 0 or 1 0 or 1
2
3
4
5
6
7
App
Index
5-23
IM XL100C-E
5.4 Input Range Parameters
• Pulse
Input Range Range Parameter Selectable Range of Span Range of Span Parameter of the SR Command Upper and Lower Limits of the SR Command of the Input Range
Instantaneous
None NONE 0.000 to 50.000
0 to 50000
Integrated value
50 Kc 50KC
500 Kc
5 Mc
500KC
5MC
50 Mc
500 Mc
50MC
500MC
Number of revolutions
500 rpm 500RPM
5 krpm
50 krpm
5KRPM
50KRPM
500 krpm 500KRPM
0.000 to 50.000
0.00 to 500.00
0.0000 to 5.0000
0.000 to 50.000
0.00 to 500.00
0 to 500
0 to 5.000
0.000 to 50.000
0.00 to 500.00
0 to 50000
0 to 50000
0 to 50000
0 to 50000
0 to 50000
0 to 500
0 to 5000
0 to 50000
0 to 50000
• Calculation Channels and Communication Channels
Input Range Range Parameter Selectable Range of Span Range of Span Parameter of the SR Command Upper and Lower Limits of the SR Command of the Input Range
None NONE -99999 to 99999 -99999 to 99999
5-24
IM XL100C-E
5.5
Setting Commands (Setting)
SR Sets the input range
When setting the channel to skip
Syntax SR p1,p2<terminator> p1 Channel number
Analog CH 8-CH input: 01 to 08
16-CH input: 01 to 16
Pulse CH
Logic CH
PL01
DI01, DI02
Query
Calc. CH CA01 to CA32
Comm. CH CO01 to CO32 p2 Channel mode SKIP
SR[ p1]?
Example Set channel 01 to OFF (SKIP).
SR 01,SKIP
Description • This command cannot be specified while logging is in progress.
• Measurements are not made on channels that are set to OFF.
When setting the channel to voltage, thermocouple, RTD, pulse input, calculation channel, or communication channel without scaling
Syntax SR p1,p2,p3,p4,p5<terminator> p1 Channel number
Analog CH 8-CH input: 01 to 08
16-CH input: 01 to 16
Pulse CH
Logic CH
PL01
DI01, DI02
Calc. CH CA01 to CA32
Comm. CH CO01 to CO32 p2 Input type
DC voltage: VOLT
Thermocouple: TC
RTD: RTD
None: NONE
Query p3 Input Range p4 Span lower limit p5 Span upper limit
SR[ p1]?
Example Set the input type for channel 01 to TC type R, span lower limit to 0°C, and span upper limit to
1760.0°C.
SR 01,TC,R,0,17600
Description • Only span parameters p4 and p5 can be specified while logging is in progress.
• Set parameters p3, p4, and p5 according to the tables in section 5.4, “Input Range
Parameters.”
5.5 Setting Commands (Setting)
• For parameters p4 and p6, enter a value using
5 digits or less excluding the decimal point.
The decimal position is fixed to the position indicated in the tables in section 5.4, “Input
Range Parameters.”
• Select “None” for parameter p2 for pulse CH, logic CH, calculation CH, and communication
CH.
When calculating the difference between channels
(no scaling)
Syntax
SR p1,p2,p3,p4,p5,p6,p7<terminator> p1 Channel number
Analog CH 8-CH input:
01 to 08
16-CH input:
01 to 16
Calc. CH
CA01 to CA32
Comm. CH
CO01 to CO32 p2 Setting type DELTA p3 Input type
DC voltage:
VOLT
Thermocouple:
TC
RTD:
None: p4 Input Range
RTD
NONE p5 Span lower limit p6 Span upper limit p7 Reference channel
Analog CH 8-CH input:
01 to 08
16-CH input:
01 to 16
Calc. CH
CA01 to CA32
Comm. CH
CO01 to CO32
Constant –9.9999E+29 to
1.0000E – 30,0,1.0000E
– 30 to 9.9999E+29
Query
SR[ p1]?
Example Set the channel 10 setting type to differential calculation with respect to channel 01 (reference channel), the input type to TC, the input range to
R, the span lower limit to 10.0°C, and the span lower limit to 100.0°C.
SR 10,DELTA,TC,R,100,1000,01
Description • Only span parameters p5 and p6 can be specified while logging is in progress.
• Set parameters p4, p5, and p6 according to the tables section 5.4, “Input Range
Parameters.”
• For parameters p5 and p6, enter a value using 5 digits or less excluding the decimal point. The decimal position is fixed to the position indicated in the tables in section 5.4,
“Input Range Parameters.”
When setting the channel to voltage, thermocouple, RTD, pulse input, calculation channel, or communication channel with scaling
1
2
3
4
5
6
7
App
Index
IM XL100C-E
5-25
5.5 Setting Commands (Setting)
Syntax SR p1,p2,p3,p4,p5,p6,p7,p8,p9, p10<terminator> p1 Channel number
Analog CH 8-CH input: 01 to 08
16-CH input: 01 to 16
Pulse CH
Logic CH
PL01
DI01, DI02
Calc. CH CA01 to CA32
Comm. CH CO01 to CO32 p2 Setting type SCALE p3 Input type
DC voltage: VOLT
Thermocouple: TC
RTD:
None:
RTD
NONE p4 Input range p5 Span lower limit p6 Span upper limit p7 CH other than communication CH
Scaling lower limit: -30000 to 30000
Comm. CH
Span decimal place x.xxxx: 0 xx.xxx: 1 xxx.xx: 2 xxxx.x: 3 xxxxx: 4 p8 CH other than communication CH
Scaling lower limit: -30000 to 30000
Comm. CH
Scaling factor: -99999 to 99999 p9 Scaling decimal place x.xxxx: 0 xx.xxx: 1 xxx.xx: 2
Query xxxx.x: 3 xxxxx: 4 p10 Unit (up to 6 characters)
SR[ p1]?
Example Convert the DC voltage measured on channel 02 to DC current. Set the input range to 6 V, the span lower limit to 1 V, the span upper limit to 5
V, the scale lower limit to 1.00 A, and the scale upper limit to 5.00 A.
SR 02,SCALE,VOLT,6V,1000,5000,100,
500,2,A
Description • Only span parameters p5 and p6 can be specified while logging is in progress.
• Set parameters p4, p5, and p6 according to the tables in section 5.4, “Input Range
Parameters.”
• For parameters p5 and p6, enter a value using
5 digits or less excluding the decimal point.
The decimal position is fixed to the position indicated in the tables in section 5.4, “Input
Range Parameters.”
• For parameters p7, p8, and p9, either set all three parameters or omit all three parameters when the channel is not set to communication channel.
SO Sets the calculating equation
Syntax
SO p1,p2,p3,p4,p5,p6,p7<terminator> p1 Calculation channel number CA01 to CA32 p2 Calculation ON/OFF
31 to 42(*)
ON, OFF p3 Calculating equation (up to 40 characters,
Query differential calculation only) p4 Span lower limit -9999999 to 99999999 p5 Span upper limit -9999999 to 99999999 p6 Span decimal place x.xxxx:
0 xx.xxx:
1 xxx.xx:
2 xxxx.x:
3 xxxxx:
4 p7 Unit (up to 6 characters)
SO[ p1]?
Example Set the calculation channel to 31, the calculation to ON, the calculating equation to “the sum of channel 01 and 02”, the span lower limit to –
10.0000, the span upper limit to 15.0000, and the unit to V.
SO 31,ON,01+02,-100000,150000,4,V
Description • Only span parameters p4 and p5 can be specified while logging is in progress.
• For parameters p4 and p5, enter a value using 7 digits or less ,excluding the decimal, for negative numbers and 8 digits or less for positive numbers.
• For parameters p4, p5, and p6, either set all three parameters or omit all three parameters.
• Setting parameter p1 to 31 to 42 is equivalent to specifying CA21 to CA32.
• The parameters that can be used in the equation of p3 are as follows.
8-CH input: CH01 to CH08
16- CH input: CH01 to CH16
Calc. CH:
Comm. CH:
Constant:
CA01 to CA32
CO01 to CO32
–9.9999E+29 to – 1.0000E
–30,
0,
1.0000E–30 to 9.9999E+
29
5-26
IM XL100C-E
SA Sets the alarm
When not using the alarm
Syntax
SA p1,p2,p3<terminator> p1 Channel number
Analog CH 8-CH input:
01 to 08
16-CH input:
01 to 16
Pulse CH
Logic CH
PL01
DI01, DI02
Calc. CH
CA01 to CA32
Comm. CH
CO01 to CO32 p2 Alarm number1 p3 Alarm ON/OFF OFF
SA[ p1[,p2]]?
Query
Example Turn OFF alarm number 1 of channel 10.
SA 10,1,OFF
Description This command cannot be issued while logging is in progress.
When using the alarm
Syntax SA p1,p2,p3,p4,p5,p6,p7<terminator> p1 Channel number
Analog CH 8-CH input: 01 to 08
16-CH input: 01 to 16
Pulse CH
Logic CH
PL01
DI01, DI02
Calc. CH CA01 to CA32
Comm. CH CO01 to CO32 p2 Alarm number 1 p3 Alarm ON/OFF ON p4 Alarm type
High limit alarm: H
Low limit alarm: L
Window IN:
Window OUT:
I
O
Reserved h, l, R, r, T, and t
(Characters are case-sensitive.) p5 Alarm value1 p6 Relay setting
Relay ON: ON
Relay OFF: OFF p7 Alarm output number p8 Alarm value 2
101 to 104
Query SA[ p1[,p2]]?
Example Set a high limit alarm (alarm value = 1000) in alarm number 1 of channel 02, and activate relay number 1 when an alarm occurs.
SA 02,1,ON,H,1000,ON,I01
Description • This command cannot be issued while logging is in progress.
• When the input range setting (SR command) is set to OFF, p3 cannot be turned ON.
• All alarm settings are turned OFF for the following cases.
• When the input type is changed (VOLT,
TC, etc).
• When the input range is changed.
IM XL100C-E
5.5 Setting Commands (Setting)
• When the span and scaling values are changed during scaling display (includes changing the decimal position).
• When the calculating equation is changed or the span value is changed for a calculation channel (CA01 to CA32).
• For the range of alarm values of p5, see the tables in section 5.4, “Input Range
Parameters.”
• Set the alarm value of a calculation channel
(CA01 to CA32) within the range of the span.
• For the alarm values of p5 and p6, enter a value using 5 digits or less, excluding the decimal. For calculation channels (CA01 to
CA32), enter a value using 5 digits or less, excluding the decimal.
SD Sets the data and time
Syntax
Query
SD p1,p2<terminator> p1 Date (YY/MM/DD fixed form)
YY (year):
00 to 99
MM (month):
01 to 12
DD (day):
01 to 31 p2 Time (HH/MM/SS fixed form)
HH (hour):
00 to 23
MM (min):
00 to 59
SS (s):
00 to 59
SD?
Example Set the internal clock to 13:00:00, October 1,
2005.
SD 05/10/01,13:00:00
Description • The form of p1 and p2 is fixed to 8 characters.
Use the following form. Do not enter spaces between the digits; otherwise an error will occur.
p1 = YY/MM/DD (Lower two digits of the year/ month/day) p2 = HH:MM:SS (Hour:minute:second)
• This command cannot be issued while logging is in progress.
SW Sets the sampling interval
Syntax
SW p1,p2<terminator> p1 Sampling Interval
For 8 ch input:
100ms, 200ms, 500ms, 1s, 2s, 5s,
10s, 20s, 30s, 1min, 2min, 5min,
10min, 20min, 30min, 60min, or 1h
For 16 ch input:
200ms, 500ms, 1s, 2s, 5s, 10s,
20s, 30s, 1min, 2min, 5min,
10min, 20min, 30min, 60min, or 1h p2 Reserved
SW?
Query
Example Sets the sampling interval to 10 s.
SW 10S
5-27
1
2
3
4
5
6
7
App
Index
5.5 Setting Commands (Setting)
Description • This command cannot be issued while logging is in progress.
• Parameter p2 is undefined.
ST Sets the tag
Syntax
ST p1,p2<terminator> p1 Channel number
Analog CH 8-CH input:
01 to 08
16-CH input:
01 to 16
Pulse CH
Logic CH
PL01
DI01, DI02
Calc. CH
CA01 to CA32
Comm. CH
CO01 to CO32 p2 Tag (up to 16 characters)
ST[ p1]?
Query
Example Set the tag of channel 02 to TAG2.
ST 02,TAG2
Description • This command cannot be issued while logging is in progress.
• For the characters that can be used for the tags, see appendix 1, “ASCII Character
Codes.” Note that semicolons and commas cannot be used.
SX Sets the group
Syntax
SX p1,p2,p3<terminator> p1 Group number 1 to 4 p2 Group name (up to 16 characters) p3 Channel configuration (up to eight channels from below)
Analog CH 8-CH input:
01 to 08
16-CH input:
01 to 16
Pulse CH
Logic CH
SX[ p1]?
PL01
DI01, DI02
Calc. CH
CA01 to CA32
Comm. CH
CO01 to CO32
Query
Example Set channels 01, 03, 04 to 06 to group number 1 using a group name GROUP2.
SX 1,GROUP2,01.03.04-06
Set the channel configuration by using periods to separate each channel or by using a hyphen to specify a range of channels.
Description • This command cannot be issued while logging is in progress.
• Alphanumeric characters can be used for the group name.
SL
Syntax
Sets the alarm line
SL p1,p2,p3,p4,p5<terminator> p1 Reserved p2 Reserved p3 Alarm line display ON/OFF ON, OFF p4 Reserved p5 Display Color
5-28
RED, GREEN, BLUE, B.VIOLET,
BROWN, ORANGE, Y.GREEN,
LIGHTBLUE, VIOLET, GRAY,
LIME, CYAN (blue green),
DARKBLUE, YELLOW,
LIGHTGRAY (olive), PURPLE
Query SL[ p1[,p2]]?
Example Display the alarm line in red for group 1.
SL ,,ON,,RED
Description Parameters p1, p2, and p4 are not used.
SE Sets the background color, waveform line width, and alarm line width
Syntax
Query
SE p1,p2,p3,p4,p5,p6,p7,p8<terminator> p1 Reserved p2 Reserved p3 Background color WHITE, BLACK p4 Waveform line width of all channels [dots] p5 Alarm line width [dots] p6 Reserved
1 to 3
1 to 3 p7 Reserved p8 Reserved
SE?
Example Set the background color to white, waveform line width to 1 dot, and alarm line width to 2 dots.
SE ,,WHITE,1,2
SB Sets the base position of the bar graph display
Syntax
Query
SB p1,p2,p3,p4<terminator> p1 Reserved p2 Reserved p3 Base position of the bar graph display
NORMAL, CENTER, RIGHT p4 Reserved
SB[ p1]?
Example Set the base position of the bar graph display to the left.
SB ,,NORMAL,
Description Parameters p1, p2, and p4 are not used.
SV Sets the average
Syntax SV p1,p2<terminator> p1 Reserved p2 Number of samples for calculating the moving average
Query
OFF, 1, 2, 5, 10, or 20
SV[ p1]?
Example Set the number of samples for calculating the moving average to 10.
SV,10
Description • This command cannot be issued while logging is in progress.
IM XL100C-E
• If parameter p2 is set in the range of 2 to 20, it is actually set to the closest of the values 1, 2,
5, 10, and 20.
• Parameter p1 is not used.
SC Sets the channel display color and waveform line width
Syntax
Query
SC p1,p2,p3<terminator> p1 Channel number
Analog CH 8-CH input:
01 to 08
16-CH input:
01 to 16
Pulse CH
Logic CH
PL01
DI01, DI02
Calc. CH
CA01 to CA32
Comm. CH
CO01 to CO32 p2 Display color
RED, GREEN, BLUE, B.VIOLET,
BROWN, ORANGE, Y.GREEN,
LIGHTBLUE, VIOLET, GRAY,
LIME, CYAN (blue green),
DARKBLUE, YELLOW,
LIGHTGRAY (olive), PURPLE p3 Waveform line width [dots] 1 to 3
SC[ p1]?
Example Set the channel 02 display color to blue and the waveform line width to 3 dots.
SC 02,BLUE,3
SQ Sets the display backlight auto off
When the display backlight auto off function is
OFF
Syntax
Query
SQ p1,p2<terminator> p1 Reserved p2 Display backlight auto off function
ON:
ON
OFF:
OFF p3 Reserved
SQ?
Example Turn the display backlight auto off function OFF.
SQ ,OFF
Description Parameter p1 is not used.
When the display backlight auto off function is ON
Syntax
Query
SQ p1,p2,p3,p4<terminator> p1 Reserved p2 Display backlight auto off function ON/OFF
ON p3 Time until turning OFF the backlight
10S, 1MIN, 2MIN, 5MIN, 10MIN,
30MIN, 60MIN, or 1H p4 Reserved
SQ?
Example Turn the display backlight auto off function ON and set the time until the backlight is turned OFF to 1 minute.
SQ ,ON,1MIN
Description Parameter p1 and p4 are not used.
IM XL100C-E
BD
5.5 Setting Commands (Setting)
Sets the delay sampling count
Syntax
BD p1,p2<terminator> p1 Reserved p2 Delay sampling count [s]
BD[ p1]?
1 to 3600
Query
Example Set the delay sampling count to 120 s.
BD ,120
Description Parameter p1 is not used.
BY Sets the automated measurement and beep sound.
Syntax
Query
BY p1,p2<terminator> p1 Auto measurement OFF: OFF
Auto measurement ON:
ON p2 Beep sound OFF: OFF
Beep sound ON:
ON
BY?
Example Turn the automated measurement and beep sound OFF.
BY ON,OFF
Description This command cannot be issued while logging is in progress.
5-29
1
2
3
4
5
6
7
App
Index
5.6 Setting Commands (Control)
5.6
Setting Commands (Control)
UD Switches the display
When switching the display back to the display that existed before settings were changed using communication commands
Syntax UD p1<terminator> p1 Display switching 0
Example Switch the display back to the display that existed before settings were changed using communication commands.
UD 0
When switching the display using communication commands
Syntax UD p1,p2,p3<terminator> p1 Display switching 1 p2 Display item
Waveform & digital display: TREND
Digital display:
Bar graph display:
DIGITAL
BAR
Alarm summary display:
Review display:
Reserved:
ALARM
REVIEW
OVERVIEW p3 Group number 1 to 4
Example Set the display to waveform & digital, and set the number of the group to be displayed to 4.
UD 1,TREND,4
PS Starts/Stops logging
Syntax PS p1<terminator> p1 Logging start/stop
Start: 0
Stop: 1
Example Start logging.
PS 0
Description If the logging start trigger is set to manual and logging does not start immediately, the GS610 enters logging standby until the trigger condition is met.
AK Acknowledges the alarm status
(alarm acknowledge)
Syntax
AK p1<terminator> p1 Execute alarm acknowledge 0
Example Confirm the current hold condition of the alarm
(execute alarm acknowledge).
AK 0
EV
Syntax
Saves manual sampled data and screen image data to the external storage medium
EV p1<terminator> p1 Operation type
5-30
Saves manual sampled data to the external storage medium:
0
Saves screen image data to the external storage medium:
2
Reserved:
1, 3, 4
Example Save manual sampled data to the external storage medium.
EV 1
Description • Data cannot be saved while logging.
• Parameter p1 cannot be set to 0 while the external storage medium is being formatted or while data is being saved to the external storage medium.
LO Loads the setup data
Syntax LO p1 <terminator> p1 File name (up to 8 characters)
Example Load the setting data of setting commands from the setup file SETFILE1 (.pnl extension).
LO SETFILE1
Description • This command is the same as the YO command. To apply the functions of the basic setting commands, the settings must be saved using the XE command.
• This command can be issued only when the external storage medium is specified and the external storage medium is inserted.
LI Saves the setting data
Syntax LI p1 <terminator> p1 File name (up to 8 characters)
Example Save the setting data of both setting and basic setting commands to the file SETFILE2.
LI SETFILE2
Description • A “.set” extension is attached to the saved file.
This command is equivalent to the YI command.
• The settings are not saved with this command if an external storage media error occurs such as the external storage medium not inserted at the save destination.
CM
Syntax
Query
Sets the communication input data
CM p1,p2<terminator> p1 Communication input data number
C01 to C32 (same as CO01 to CO32)
CO01 to CO32 p2 Communication input data
Selectable range:
-9.9999E+29 to -
1.0000E- 30, 0,
1.0000E-30 to
-9.9999E+29
(The + sign of “E+” can be omitted.)
CM?
IM XL100C-E
Example Set 1.0000E-10 to communication input data number CO01.
CM CO01,1.0000E-10
EM Starts/stops the e-mail transmission function
Syntax
M p1<terminator> p1 Operation type
Start:
0
Stop:
1
Example Start the e-mail transmission function.
EM 0
Description To use the e-mail transmission function, you must set the Ethernet interface, e-mail address, and contents to be transmitted. For the procedure to set each item, see section 2.11
“Setting the E-mail Transmission function”.
KE Key operation command
Syntax
KE p1<terminator> p1 Key type
ESC key:
HOME key:
REVIEW key:
ESC
HOME
REVIEW
FILE
FILE key:
SETTING key:
HOLD key:
SETTING
HOLD
TIME/DIV left key:
TIMEDIVSHORT
TIME/DIV right key:
TIMEDIVLONG
RANGE key:
RANGE
SAVE key:
DISPLAY key:
SAVE
DISP
GROUP key:
MARK key:
MARK left key:
GROUP
MARK
MARKLEFT
MARKRIGHT
MARK right key:
SET key:
SET
START/STOP key:
STARTSTOP
HOLD key:
Up arrow key:
Down arrow key:
Right arrow key:
Left arrow key:
SELECT key:
HOLD
UP
DOWN
RIGHT
LEFT
SELECT
Example Press the DISPLAY key.
KE DISP
Description Operates in the same fashion as the key operation on the XL100. For consecutive key operations, transmit the commands in the same order as the key operation on the XL100.
5.7 Basic Setting Commands
5.7
Basic Setting Commands
1
• In order to activate the settings that are changed using the basic setting commands, the settings must be saved using the XE command.
The settings that are returned in response to a query after issuing a basic setting command are the new settings even if the settings have not been saved with the XE command. However, the new settings only take effect after saving the settings using the XE command.
If you discard the settings with the XE command or start the logging operation before saving the settings with the XE command, the settings that are returned in response to a query are reset to those before the change.
• Basic setting commands cannot be used to change settings while logging is in progress.
XA Sets the alarm
Syntax XA p1,p2,p3,p4,p5,p6,p7,p8,p9<terminator> p1 Reserved p2 Output number to be set to AND
For all ORs: NONE
Independent setting: I01, I02, I03, or
Range setting:
I04
Ixx-Ixy
(Ixx,Ixy: I01 to I04) p3 Reserved p4 Output hold/non-hold
Hold:
Non-hold:
HOLD
NONHOLD p5 Hold/Not hold the alarm status display
Hold: HOLD
Non-hold: NONHOLD p6 Reserved p7 Reserved p8Alarm hysteresis ON/OFF: ON or OFF p9Alarm buzzer ON/OFF: ON, OFF
Query XA?
Example Set output numbers I01 to I04 to AND, hold the output, hold the alarm status display, turn the alarm hysteresis ON, and turn the alarm buzzer
ON.
XA ,I01-I12,HOLD,HOLD,,,ON,ON
Description Parameters p1, p3, p6, and p7 are not used.
XB
Syntax
Burnout setting (query only)
XB p1,p2<terminator> p1 Reserved (NULL) p2 Burnout procedure UP
2
3
4
5
6
7
App
Index
IM XL100C-E
5-31
5.7 Basic Setting Commands
Query XB[ p1]?
Description Only a query is available for this command.
XJ RJC setting (query only)
Syntax
Query
XJ p1,p2<terminator> p1 Channel number
For 8 ch input:
01 to 08
For 16 ch input:
01 to 16 p2 Reference junction compensation selection
INTERNAL
XJ[ p1]?
Example Only a query is available for this command.
XV Sets the sampling interval
Syntax
XV p1<terminator> p1 Sampling Interval
For 8 ch input:
100, 200, 500ms, 1, 2, 5, 10,
20, 30s, 1, 2, 5, 10, 20, 30min,
60min, 1h
For 16 ch input:
200, 500ms, 1, 2, 5, 10, 20,
30s, 1, 2, 5, 10, 20, 30min,
60min, 1h
Query
XV?
Example Set the sampling interval to 1 s.
XV 1S
Description This command is the same as the SW setting command.
XU Sets the language
Syntax XU p1,p2,p3,p4,p5<terminator> p1 Reserved p2 Reserved p3 English: ENGLISH
Japanese: JAPANESE p4 Reserved p5 Reserved
Query XU?
Example Set the language to Japanese.
XU ,,JAPANESE
Description Parameters p1, p2, p4, and p5 are undefined.
XD Sets the external storage medium.
Syntax
XD p1 <terminator> p1 External storage media
Internal memory:
0
CF card:
1
XD 1
SD card:
2
USB memory:
3
Query
Example Set the data save and load destination to the CF card.
XD 1
5-32
XO Selects the communication method
When switching to Ethernet communications
Syntax
Query
XO p1<terminator> p1 ETHERNET
Ethernet communications
XO?
Example Set the communication method to Ethernet.
XO ETHERNET
When switching to serial communications (RS-
232, RS-485, or USB)
Syntax
XO p1,p2<terminator> p1 SERIAL
Serial communications p2 Serial communication type
RS232, RS485, or USB
XO?
Query
Example Set the communication method to RS-232.
XO SERIAL,RS232
XT Selects the trigger
Syntax
XT p1,p2<terminator> p1 Trigger mode
Single:
0
Continuous:
1 p2 Normal trigger, pre-trigger, and delay trigger
XT?
setting
Normal:
0
Pre-trigger:
1
Delay trigger:
2 p3 Pre-trigger or delay trigger count
0 to 600
Query
Example Set the trigger to single and the pre-trigger count to 10.
XT 0,1,10
XK Selects the start trigger
When setting the start trigger to OFF
Syntax XK p1 <terminator> p1 Start trigger type
None: 0
Query XK?
Example Set the start trigger to none.
XK 0
When setting the start trigger to external input
Syntax XK p1<terminator> p1 Start trigger type
External input: 1
Query XK?
Example Set the start trigger to external input.
XK 1
When setting the start trigger to analog input level
Syntax XK p1,p2,p3,p4,p5 <terminator> p1 Start trigger type
Analog input level: 2 p2 Analog channel to be used as the start trigger
IM XL100C-E
For 8 ch input: 01 to 08
For 16 ch input: 01 to 16 p3 Start trigger level type
High limit trigger: H
Low limit trigger: L
Window IN: I
Window OUT: O p4 High limit value -99999 to 99999
Query p5 Low limit value -99999 to 99999
XK?
Example Set the start trigger to Window IN of analog input
CH3, and set the high and low limits to 2000 and
1000, respectively.
XK 2,03,I,2000,1000
Description Set the high and low limits using a five-digit integer without a decimal point. The decimal place is the same as the span and scale settings of the analog input channel.
Be sure to set the high limit greater than or equal to the low limit.
When setting the start trigger to an alarm
Syntax XT p1,p2<terminator> p1 Start trigger type
Alarm: 3 p2 Alarm output number to be used as the start trigger
1 to 4
Query XK?
Example Set the start trigger to alarm output number 4.
XK 3,4
When setting the start trigger to a specific time
Syntax XK p1,p2,p3 p1Start trigger type
Time: 4 p2 Start date (YY/MM/DD fixed form)
YY (year): 00 to 99
MM (month): 01 to 12
DD (day): 01 to 31 p3Start time (HH/MM/SS fixed form)
HH (hour): 00 to 23
MM (min): 00 to 59
SS (s): 00 to 59
Query XK?
Example Set the start trigger to 3:45:6 on January 2, 2006.
XK 4,06/01/02,03:45:06
XL Selects the end trigger
When setting the end trigger to OFF
Syntax
Query
XL p1<terminator> p1 End trigger type
None:
0
XL?
Example Set the end trigger to none.
XL 0
When setting the end trigger to external input
Syntax
XL p1<terminator> p1 End trigger type
IM XL100C-E
5.7 Basic Setting Commands
External input: 1
Query XL?
Example Set the end trigger to external input.
XL 1
When setting the end trigger to analog input level
Syntax XLp1,p2,p3,p4,p5<terminator> p1 End trigger type
Analog input level: 2 p2 Analog channel to be used as the end trigger
For 8 ch input: 01 to 08
For 16 ch input: 01 to 16 p3 End trigger level type
High limit trigger: H
Low limit trigger: L
Window IN: I
Window OUT : O p4 High limit value -99999 to 99999
Query p5 Low limit value -99999 to 99999
XL?
Example Set the end trigger to low limit 500 of analog input CH3.
XL 2,03,L,500
Description Set the high and low limits using a five-digit integer without a decimal point. The decimal place is the same as the span and scale settings of the analog input channel.
Be sure to set the high limit greater than or equal to the low limit.
When setting the end trigger to an alarm
Syntax XL p1,p2 p1 End trigger type
Alarm: 3 p2 Alarm output number to be used as the end trigger
1 to 4
Query XL?
Example Set the end trigger to alarm output number 1.
XL 3,1
When setting the end trigger to a specific time
Syntax XL p1,p2,p3 p1 End trigger type
Time: 4 p2 End date (YY/MM/DD fixed form)
YY (year): 00 to 99
MM (month): 01 to 12
DD (day): 01 to 31 p3 End time (HH/MM/SS fixed form)
HH (hour): 00 to 23
MM (min): 00 to 59
SS (s): 00 to 59
Query XK?
Example Set the end trigger to 4:56:7 on February 3,
2030.
XL 4,30:02:03,04:56:07
When setting the end trigger to a timer
Syntax XL p1,p2
5-33
1
2
3
4
5
6
7
App
Index
5.7 Basic Setting Commands
p1 End trigger type
Timer: 5 p2 End timer (s)
1 to 31622400
Query XL?
Example Set the end trigger to a 600-s timer.
XL 5,600
XH Sets the key login and auto logout functions
Syntax
XH p1,p2,p3<terminator> p1 Key login function
Enable:
USE
Disable:
NOT p2 Timeout function
Enable:
USE
Disable:
NOT p3 Reserved
XH?
Query
Example Enable the key login and auto logout functions.
XH USE,ON,
Description Parameter p3 is not used.
XE Sets whether to save or discard the settings specified by a basic setting command
Syntax
XE p1<terminator> p1 Save or discard settings
Save:
STORE
Discard:
ABORT
Example Save the settings of the basic setting command.
XE STORE
Description In order to activate the settings that are changed using the basic setting commands, the settings must be saved using the XE command. If you do not, the settings before the change are activated if logging is started.
XG Sets the time zone
Syntax XG p1<terminator> p1Offset time from the Greenwich Mean Time
-1200 to 1200
Upper two digits (hour): 00 to 12
Lower two digits (minutes): Fixed to 00
Example Set the offset time from the GMT to 9 hours ahead.
XG 0900
XY
Syntax
Sets the statistical calculation
XY p1,p2,p3,p4,p5<terminator> p1 Calculation of the maximum value
Enable:
ON
Disable:
OFF p2 Calculation of the minimum value
Enable:
ON
Disable:
OFF
5-34
Query
YB
Syntax
Query p3 Calculation of the average value
Enable: ON
Disable: OFF p4 Calculation of the peak (P-P) value
Enable: ON
Disable: OFF p5 Calculation of the rms value
Enable: ON
Disable: OFF
XY?
YA Sets the IP address, subnet mask, and default gateway
Syntax
Query
YA p1,p2,p3<terminator> p1 IP address
0.0.0.0 to 255.255.255.255
p2 Subnet mask
0.0.0.0 to 255.255.255.255
p3 Default gateway
0.0.0.0 to 255.255.255.255
YA?
Example Set the IP address to 192.168.111.24, the subnet mask to 255.255.255.0, and the default gateway to 0.0.0.0.
YA 192.168.111.24,255.255.255.0,
0.0.0.0
Description The settings changed with this command are applied when they are saved using the XE command.
Queries the IPV6 information
YB p1,p2,p3<terminator> p1 Default Gateway
OFF,xxxx::xxxx::xxxx::xxxx%6 p2 Global
OFF,xxxx::xxxx::xxxx::xxxx%6 p3 Site-local
OFF,xxxx::xxxx::xxxx::xxxx%4 p4 Link local
OFF,xxxx::xxxx::xxxx::xxxx%4 p5 6to4
OFF,xxxx::xxxx::xxxx::xxxx%6 p6 Automatic tunnel 1
OFF,xxxx::xxxx::xxxx::xxxx%6 p7 Automatic tunnel 2
OFF,xxxx::xxxx::xxxx::xxxx%6 p8 Automatic tunnel 3
OFF,xxxx::xxxx::xxxx::xxxx%6
YB?
YK
Syntax
Query
Sets the keepalive
YK p1<terminator> p1 Enable/Disable keepalive
Enable: ON
Disable: OFF
YK?
IM XL100C-E
Example Disable keepalive.
YK OFF
Description The setting changed with this command is applied when it is saved using the
XE command.
YN Sets the DNS
When not using the DNS
Syntax
YNp1<terminator> p1 Disable DNS
YN?
OFF
Query
Example Do not use the DNS.
YN OFF
Description The setting changed with this command is applied when it is saved using the XE command.
When using the DNS
Syntax
YN p1,p2,p3,p4,p5,p6,p7<terminator> p1 Enable DNS ON p2 Address of the primary DNS server
0.0.0.0 to 255.255.255.255
p3 Address of the secondary DNS server
0.0.0.0 to 255.255.255.255
p4 Host name (up to 64 characters) p5 Domain name (up to 64 characters) p6 Domain suffix 1 (up to 64 characters) p7 Domain suffix 2 (up to 64 characters)
YN?
Query
Example Use the DNS server at 192.168.0.1.
YN ON,192.168.0.1
Description The settings changed with this command are applied when they are saved using the XE command.
YE Sets the SNTP (time synchronization function)
When not using the SNTP
Syntax
Query
YE p1<terminator> p1 Disable 0
YE?
Example Disable SNTP.
YE 0
When using the SNTP
Syntax
YE p1,p2,p3<terminator> p1 Enable 1 p2 Server name (up to 64 alphanumeric
Query characters) p3 Confirmation time interval (hh) 1 to 24
YE?
Example Use the SNTP server named MCC at six-hour intervals.
YE 1,MCC,6
YQ Sets the Ethernet communication timeout
When not using the timeout
Syntax YQ p1<terminator>
IM XL100C-E
5.7 Basic Setting Commands
p1 Enable/Disable communication timeout
Enable: ON
Disable: OFF
Query YQ?
Example Disable timeout.
YQ OFF
Description The setting changed with this command is applied when it is saved using the XE command.
When using the timeout
Syntax YQ p1,p2<terminator> p1 Enable/Disable communication timeout
Enable: ON
Disable: OFF
Query p2 Timeout value (min)
YQ?
1 to 120
Example Enable the communication timeout and set the timeout period to 3 min.
YQ ON,3
Description The settings changed with this command are applied when they are saved using the XE command.
YS Sets the serial interface
Syntax
YS p1,p2,p3,p4,p5,p6,p7<terminator> p1 Baud rate [bps]
1200, 2400, 4800, 9600,
19200, 38400, 57600, or 115200 p2 Data length (number of bits) 7 or 8 p3 Parity check
None:
Odd:
NONE
ODD
Even:
EVEN p4 Handshaking
OFF:
OFF:OFF
XON/XOFF:
XON:XON
CS/RS: p5 Protocol
CS:RS
Normal:
NORMAL
Modbus RTU (slave):
MODBUS
Modbus RTU (master):
MODBUS-M
Modbus ASCII (slave):
MODBUSASCII
Query
Modbus ASCII (master):
MOSBUSASCII-M p6 Stop bit
1 bit:
1
2 bits:
2
YS?
Example Set the baud rate to 9600, the data length to 8, the parity check to ODD, the handshaking to
OFF, the protocol to NORMAL, and the stop bit to 1.
YS 9600,8,ODD,OFF:OFF,NORMAL,1
1
2
3
4
5
6
7
App
Index
5-35
5.7 Basic Setting Commands
Description • The settings changed with this command are applied when they are saved using the XE command.
• Parameter p2 (data length) when Modbus
RTU is selected is fixed to 8 bits.
YO Loads the setting data
Syntax
YO p1<terminator> p1 File name (up to 8 characters)
Example Load the setting data from the setup file
SETFILE1 (.set extension).
YO SETFILE1
Description This command can be specified only when an external storage medium is inserted.
YI Saves the setting data
Syntax
YO p1<terminator> p1 File name (up to 8 characters)
Example Save the setting data to a file named SETFILE2.
YI SETFILE2
Description • A “.set” extension is attached to the saved file.
This command is equivalent to the LI command.
• This command can be specified only when an external storage medium is inserted.
YC Resets the system (clears the measured/calculated data and initializes the setting data)
Syntax YC p1<terminator> p1 Type of data to be cleared or initialized
Clear the measured/calculated data and initializes setup data 0, 1
Clear the measured/calculated data
2
Example Clear the measured/calculated data.
YC 2
Description • The measured/calculated data indicates the data residing in the internal memory of the
XL100.
• This command cannot be specified while the external storage medium is being formatted.
• The date settings, communication settings, language setting, device address setting, slave device address, and USB ID are not initialized.
YT
Syntax
Query
Sets the FTP transfer timing
YT p1,p2<terminator> p1 Auto transfer at the end of logging
ON or OFF p2 Reserved
YT?
5-36
Example Automatically transfer the data files and log file at the end of logging.
YT ON
Description Parameter p2 is not used.
YG Enables/Disables the Web server function
Syntax
YG p1<terminator> p1 Web server function enable/disable
Enable:
USE
Disable:
NOT
YG?
Query
Example Use the Web server function.
YG USE
Description • For details on the settings of the Ethernet, the types of Web pages that can be displayed, and access control, see “Web Server” in section 1.2, “Explanation of Functions.”
• The settings changed with this command are applied when they are saved using the XE command.
YL Sets the operation of the Modbus master function
Syntax
YL p1,p2,p3<terminator> p1 Read cycle
125MS, 250MS, 500MS, 1S, 2S,
5S, or 10S
Query p2 Communication timeout value
25MS, 250MS, 500MS, 1S, 2S, 5S,
10S, or 1MIN p3 Retrials
OFF, 1 to 5, 10, or 20
YL?
Example Set the read cycle to 500 ms, timeout to 250 ms, and retrials to 2.
YL 500MS,250MS,2
Description • This command is valid when the serial interface protocol is set to “Master.” For serial interface settings, see chapter 3, “Serial
Interface.”
• The settings changed with this command are applied when they are saved using the XE command.
YM Sets the command of the
Modbus master function
When not setting a command
Syntax YM p1,p2<terminator> p1 Registration number 1 to 32 p2 Presence or absence of the command
OFF
Query YM[ p1]?
Example Do not set a command to command registration number 1.
YM 1,OFF
IM XL100C-E
When setting a command
Syntax YM p1,p2,p3,p4,p5,p6,p7<terminator> p1 Registration number
1 to 32 p2 Presence or absence of the command
ON p3 First channel number
C01 to C30 (corresponds to CO01 to
CO30),
CO01 to CO32 p4 Last channel number
C01 to C30 (corresponds to CO01 to
CO30),
CO01 to CO32 p5 Slave device address (1 to 247) p6 First register number
30001 to 39999,
40001 to 49999 p7 Type of data assigned to the register
INT16, UINT16, INT32_B,
INT32_L, UINT32_B, UINT32_L,
Query
FLOAT_B, or FLOAT_L
YM[ p1]?
Example Register the following command in command registration number 2: Read the 32-bit signed integer data that is assigned to registers 30003
(upper 16 bits) and 30004 (lower 16 bits) of the slave device at address 5 into C02 of the
CX2000.
YM 2,ON,C02,C02,5,30003,INT32_B
Description • This command is valid when the serial interface protocol is set to “Master.” For serial interface settings, see chapter 3, “Serial
Interface.”
• The settings changed with this command are applied when they are saved using the XE command.
YU Sets the contents to be transmitted by e-mail.
When sending the changes in the alarm status
Syntax
YU p1,p2,p3,p4,p5,p6,p7,p8,p9,p10, p11,p12<terminator> p1 Content to be sent ALARM p2 Enable/Disable recipient 1 ON or OFF p3 Enable/Disable recipient 2 ON or OFF p4 Alarm transmission ON/OFF ON or OFF p5 Reserved p6 Reserved p7 Reserved p8 Enable/disable attachment of instantaneous data
ON, OFF p9 Enable/disable attachment of source URL
ON or OFF p10 Subject (up to 32 alphanumeric characters) p11 Header 1 (up to 64 alphanumeric characters)
IM XL100C-E
5.7 Basic Setting Commands
p12 Header 2 (up to 64 alphanumeric characters)
Query YU[ p1]?
Example Transmit alarms including instantaneous data but not including the source URL to recipient 1. The subject is “ALM”, and the header 1 is “LP2”.
YU ALARM,ON,OFF,ON,ON,ON,ON,ON,OFF,
ALM,LP2
When sending e-mail at scheduled times
Syntax YU p1,p2,p3,p4,p5,p6,p7,p8,p9,p10, p11,p12<terminator> p1 Content to be sent TIME p2 Enable/Disable recipient 1 ON or OFF p3 Interval for sending e-mail to recipient 1
1H, 2H, 3H, 4H, 6H, 8H, 12H, or 24H p4 Time when sending e-mail to recipient 1
HH:MM p5 Enable/Disable recipient 2 ON or OFF p6 Interval for sending e-mail to recipient 2
1H, 2H, 3H, 4H, 6H, 8H, 12H, or 24H p7 Time when sending e-mail to recipient 2
HH:MM p8 Enable/disable attachment of instantaneous data ON or OFF p9 Enable/disable attachment of source URL
ON or OFF p10 Subject (up to 32 alphanumeric characters) p11 Header 1 (up to 64 alphanumeric characters) p12 Header 2 (up to 64 alphanumeric characters)
Query YU[ p1]?
Example Send e-mail at 17 hours 15 minutes every day to recipient 1. Do not include instantaneous data but include the source URL. The subject is
“GOOD”, and the header 1 is “LP2”.
YU TIME,ON,24H,17:15,OFF,,,OFF,ON,
GOOD,LP2
When sending system notifications
Syntax
Query
YU p1,p2,p3,p4,p5,p6,p7<terminator> p1 Content to be sent
SYSTEM p2 Enable/Disable recipient 1 p3 Enable/Disable recipient 2
ON or OFF
ON or OFF p4 Enable/disable attachment of source URL
ON or OFF p5 Subject (up to 32 alphanumeric characters) p6 Header 1 (up to 64 alphanumeric characters) p7 Header 2 (up to 64 alphanumeric characters)
YU[ p1]?
1
2
3
4
5
6
7
App
Index
5-37
5.8 Output Commands (Control)
Example Send system notification e-mail messages including the source URL to recipient 1. The subject is “SystemAlert”, and header 1 is “LP2”.
YU SYSTEM,ON,OFF,ON,SystemAlert,LP2
YV Sets the e-mail transmission recipient address
Syntax
YV p1,p2<terminator> p1 Recipient selection
Recipient 1:
1
Recipient 2:
2 p2 Recipient address (up to 150 alphanumeric
Query characters)
YV[p1]?
Example Set recipient 1 to “[email protected]” and
YV 1,[email protected] [email protected]
Description • To set multiple recipients, separate each recipient with a space.
• For e-mail settings, see section 2.11, “Setting the E-mail Transmission Function” and 2.13,
“Starting/Stopping E-mail Transmissions.”
YW Sets the e-mail transmission sender address
Syntax
YW p1<terminator> p1 Sender address (up to 64 alphanumeric characters)
YW?
Query
Example Set the sender address to “XL100.”
YW XL100
Description For e-mail settings, see section 2.11, “Setting the
E-mail Transmission Function” and 2.13,
“Starting/Stopping E-mail Transmissions.”
YX Sets the e-mail SMTP server name
Syntax YX p1,p2<terminator> p1 SMTP server name (up to 64 alphanumeric characters)
Query p2 Port number 0 to 65535
YX?
Example Set the SMTP server to “mhs.good.com” and port number to “25”.
YX mhs.good.com,25
Description For e-mail settings, see section 2.11, “Setting the
E-mail Transmission Function” and 2.13,
“Starting/Stopping E-mail Transmissions.”
5-38
5.8
Output Commands
(Control)
BO Sets the byte output order
Syntax BO p1<terminator> p1 Byte order
Output the data MSB first:
Output the data LSB first:
Query BO?
Example Output the data MSB first.
0
1
BO 0
Description This command applies to the byte order of numerical data during binary output.
CS Sets the checksum
Syntax CS p1<terminator> p1 Checksum enable/disable
Disable: 0
Enable: 1
Query CS?
Example Enable the checksum.
CS 1
Description Can be used only during serial communications.
IF Sets the status filter
Syntax
IF p1<terminator> p1 Status filter value
0.0.0.0 to 255.255.255.255
IF?
Query
Example Set the status filter value to 1.0.4.0.
IF 1.0.4.0
Description For details, see chapter 7, “Status.”
CC Disconnects the Ethernet connection
Syntax CC p1<terminator> p1 Connection disconnect 0
Query IF?
Example Disconnect the Ethernet connection.
CC 0
Description Can be used only during Ethernet communications.
Note
Initialization of BO/CS/IF command settings
• For serial communication
Settings entered using the BO/CS/IF commands revert to their initial values when the XL100 is reset, when the
XL100 is power cycled, or when the XE command is executed normally.
• Byte output order, checksum: 0
• Status filter: 000.000.000.000
If the XL100 is reset, you must reconfigure these settings.
• For Ethernet communications
IM XL100C-E
5.9 Output Commands (Setting/Measurement/Data Output)
Settings entered using the BO/IF commands revert to their initial values when the connection to the XL100 is cut.
After reconnecting the XL100, you must reconfigure the settings.
5.9
Output Commands (Setting/
Measurement/Data Output)
ID Outputs the system data (query only)
Syntax
ID p1, p2, p3, p4<terminator> p1 Maker name YOKOKGAWA p2 Model XL100 p3 XL100 serial number
16 alphanumeric characters p4 Terminal block serial number
16 alphanumeric characters p5 Firmware revision
Verx.xx
(where x.xx are alphanumeric characters)
Query
ID?
Description Parameter p4, the terminal block serial number, is undefined if the terminal block unit is not connected.
FC Outputs the screen image data
Syntax FC p1<terminator> p1 Screen image data output GET
Example Output the screen image data from the XL100.
FC GET
Description Captures the current displayed screen on the
XL100 and outputs the data in BMP format.
FE Outputs the setting data
Syntax FE p1,p2,p3,p4,p5,p6,p7,p8,p9,p10, p11<terminator> p1 Output data type
Setting data of setting commands:
Decimal place and unit information:
0
1
Setting data of basic setting commands: 2
Reserved: 3
Setting data file: 4 p2 First channel number
For 8 ch input: 01 to 08,
For 16 ch input: 01 to 16
<Numeric value> 00(OFF) p3 Last channel number
For 8 ch input: 01 to 08,
For 16 ch input: 01 to 16
<Numeric value> 00(OFF) p4 First pulse measurement channel number:
PL01, PL00(OFF) p5 Last pulse measurement channel number:
PL01, PL00(OFF) p6 First logic input channel number
DI01 to DI02, DI00(OFF) p7 Last logic input channel number
DI01 to DI02, DI00(OFF) p8 First calculation channel number
CA01 to CA32, CA00(OFF) p9 Last calculation channel number
CA01 to CA32, CA00(OFF) p10 First communication channel number
CO01 to CO32, CA00(OFF) p11 Last communication channel number
CO01 to CO32, CA00(OFF)
Example Get the decimal place and unit for channels 01 to
12 and pulse channel.
FE 1,01,12,PL01,PL01
Description • Set the first channel number and last channel number parameters so that the last channel number is greater than or equal to the first channel number.
• Parameters p2, p3, p4, p5, p6, p7, p8, p9, p10, and p11 are valid when p1 is set to 0, 1,
2, or 3.
1
2
3
4
5
6
7
App
Index
IM XL100C-E
5-39
5.9 Output Commands (Setting/Measurement/Data Output)
FD Outputs the most recent measured/calculated data
Syntax
FD p1,p2,p3,p4,p5,p6,p7,p8,p9,p10, p11<terminator> p1 Output data type
Output the most recent measured/calculated data in ASCII format:
0
Output the most recent measured/calculated data in BINARY format:
1
Reserved: p2 First channel number
4, 5
For 8 ch input:
01 to 08,
For 16 ch input:
01 to 16
<Numeric value>
00(OFF) p3
Last channel number
For 8 ch input:
01 to 08,
For 16 ch input:
01 to 16
<Numeric value>
00(OFF) p4 First pulse measurement channel number:
PL01, PL00(OFF) p5 Last pulse measurement channel number:
PL01, PL00(OFF) p6 First logic input channel number
DI01 to DI02, DI00(OFF) p7 Last logic input channel number
DI01 to DI02, DI00(OFF) p8 First calculation channel number
CA01 to CA32, CA00(OFF) p9 Last calculation channel number
CA01 to CA32, CA00(OFF) p10 First communication channel number
CO01 to CO32, CA00(OFF) p11 Last communication channel number
CO01 to CO32, CA00(OFF)
Example Output from the XL100 the most recent measurement of channels 1 to 5, pulse measurement data, and logic measurement data
1 and 2 and the calculated data of channels 1 to
5 in ASCII data format.
FD 0,01,05,PL01,PL01,DI01,DI02,CA01,
CA05,CO00,CO00
FD 0,01,05
Description • The most recent measured/calculated data corresponds to the most recent measured/ calculated data in the internal memory when the XL100 receives the FD command.
• Set the first channel number and last channel number parameters so that the last channel number is greater than or equal to the first channel number.
FL
Syntax
Outputs the log and alarm summary
FL p1,p2<terminator> p1 Log type
Communication:
FTP client:
COM
FTPC
Error message:
Key login:
Web operation:
E-mail:
ERR
KEY
WEB
Alarm summary:
Reserved:
ALARM
MSG p2 Maximum read length of the log
When p1 is COM: 1 to 200
When p1 is ALARM: 1 to 120
When p1 is some type other than the above:
1 to 50
Example Output the 10 most recent error message logs.
FL ERR,10
Description • Outputs the log that is stored in the XL100.
• If p2 is omitted, all written logs are output.
IS Outputs status information
Syntax
IS p1<terminator> p1 Status information output
Example Output status information.
IS 0
0
Description The output status can be masked using the status filter (IF command).
FU Outputs the user level
Syntax
FU p1<terminator> p1 User information output
Example Output user information.
FU 0
0
Description Outputs the information of the user currently connected to the XL100.
ME
Syntax
Outputs the data stored on the external storage medium
ME p1,p2,p3<terminator> p1 Operation type
Output the file list:
Output (first time):
DIR
GET
Output (subsequent times). This parameter is used to output the remaining data when the first output operation is not adequate:
NEXT
Retransmit the previous output: RESEND
Delete: DEL
Outputs the subsequent file list after the file list is output using the DIRNEXT DIR command. The number of output lists is the p3 value specified with the DIR command. If this command is executed after all lists have been output, only the free space of the storage medium is output.
p2 File name (26 alphanumeric characters)
Specify using a full path.
p3 Maximum number of output file lists
1 to 100
5-40
IM XL100C-E
5.10 Output Commands (RS-485 and USB Dedicated Commands)
If omitted, all the file lists in the specified directory are output.
Example • Output the list of all files in the root directory.
ME DIR,/
• Output 10 files of the file list of the root directory.
ME DIR,/,10
• Output the list of all files in the DATA0 directory.
ME DIR,/DATA0/*.*
• Output the list of all display data files in the
DATA0 directory.
ME DIR,/DATA0/*.DDS
• Output the data in the file 72615100.DDS in the DATA0 directory.
ME GET,/DATA0/72615100.DDS
Description • This command is valid for the specified save destination and load destination medium.
• Parameter p2 is valid when p1 is set to DIR,
GET, or DEL.
• Parameter p3 is valid when p1 is set to DIR.
• This command can be used to output data over the communication interface (Ethernet or serial) that was selected with the XO command.
• If an error occurs during data transmission,
(p1=) RESEND can be used to retransmit the data.
5.10 Output Commands (RS-485
ESC O
and USB Dedicated
Commands)
Opens the device
The ASCII code of ESC is 1BH.
See appendix 1, “ASCII Character Codes.”
Syntax ESC O p1<terminator> p1 Device address 01 to 99
Example Open the device at address 01, and enable all commands.
ESC O 01
Description • Specifies the address of the device with which to communicate.
• Only one device can be opened at any given time.
• When a device is opened with the ESC O command, another device that is currently open is automatically closed.
• When this command is received correctly, the
XL100 transmits the data “ESC O ”.
• Normally, either CR+LF or LF can be used as a terminator for communication commands.
However, the terminator for this command must be set to CR+LF.
ESC C Closes the device
The ASCII code of ESC is 1BH.
See appendix 1, “ASCII Character Codes.”
Syntax ESC C p1<terminator> p1 Device address 01 to 99
Example Close the device whose address is 01.
ESC C 001
Description • Clears the current connection with the device.
• When this command is received correctly, the
XL100 transmits the data “ESC C ”.
• Normally, either CR+LF or LF can be used as a terminator for communication commands.
However, the terminator for this command must be set to CR+LF.
1
2
3
4
5
6
7
App
Index
IM XL100C-E
5-41
5.11 Maintenance/Test Commands
5.11 Maintenance/Test
Commands (Available when using the maintenance/test server function via Ethernet communications)
close Disconnects the connection between other devices
Syntax close,p1,p2:p3<terminator> p1 Port on the XL100 side
0 to 65535 p2 IP address on the PC side
0.0.0.0 to 255.255.255.255
p3 Port on the PC side
0 to 65535
Example close,349,192.168.111.24:1054
E0
Description This command cannot be used to disconnect a server port. Also, it cannot disconnect the XL100 being operated. Use the quit command for this purpose.
con
Syntax
Example
Outputs connection information
con<terminator> con
EA
00/00/00 12:34:56
Active connections
Proto Local Address Foreign Address
State
TCP 192.168.111. 24:34159
192.168.111. 24:1053 ESTABLISHED
TCP 0. 0. 0. 0:34155 0. 0. 0. 0: 0
LISTEN
TCP 0. 0. 0. 0:34159 0. 0. 0. 0: 0
LISTEN
TCP 0. 0. 0. 0:34150 0. 0. 0. 0: 0
LISTEN
EN
TCP: Protocol used
Local Address: The XL100 socket address.
Displays “IP address:port number”
Foreign Address: The destination socket address. Displays “IP address:port number”
State: Connection status
ESTABLISHED: Connection established
eth
Syntax
Outputs Ethernet statistical information
eth <terminator>
5-42
Example
help
Syntax eth
EA
00/00/00 12:34:56
Ethernet Statistics
Name In Pkt In Err Out Pkt Out Err
16 Coll lo0 0 0 0 0 0 mb0 74 0 64 0 0
EN
Outputs help
help [,p1]<terminator> p1 Command name
(close, con, eth, help, net, quit)
Example help
EA con - echo connection information eth - echo ethernet information help - echo help net - echo network status quit - close this connection
EN
net
Syntax
Example
Outputs network statistical information
net
<terminator> net
EA
00/00/00 12:34:56
Network Status
APP: power on time = 00/00/00
12:34:56
APP: applalive = disable
APP: genedrops = 0
APP: diagdrops = 0
APP: ftpsdrops = 0
TCP: keepalive = 30 s
TCP: connects = 14
TCP: closed = 0
TCP: timeoutdrop = 0
TCP: keepdrops = 0
TCP: sndtotal = 53
TCP: sndbyte = 0
TCP: sndrexmitpack = 0
TCP: sndrexmitbyte = 1
TCP: rcvtotal = 0
TCP: rcvbyte = 0
DLC: 16 collisions = 0
EN
TCP: keepalive:Keepalive check cycle
TCP: connects:Total number of connections established
IM XL100C-E
quit
Syntax
TCP: closed: Total number of dropped connections
TCP: timeoutdrop: Total number of dropped connections due to TCP retransmission timeout. When the transmitted packet (the unit of transmitted data) is not received, the packet is automatically retransmitted at a predetermined time interval. If the packet is not received after 14 retransmissions, timeout occurs and the connection is dropped.
TCP: keepdrops: Total number of dropped connections due to TCP keepalive timeout
TCP: sndtotal: Total number of transmitted packets.
TCP: sndbyte: Total number of transmitted bytes
TCP: sndrexmitpack: Total number of retransmitted packets
TCP: sndrexmitbyte: Total number of retransmitted bytes
TCP: rcvtotal: Total number of received packets
TCP: rcvbyte: Total number of received bytes
DLC: 16 collisions: Number of collision incidents.
A collision occurs when two or more instruments on the network attempt to transmit simultaneously. The tendency for collisions to occur increases when the network is congested. 16 collisions refer to
16 consecutive collision incidents.
Disconnects the connection of the device being operated
quit<terminator>
5.11 Maintenance/Test Commands
5
6
3
4
7
1
2
App
Index
IM XL100C-E
5-43
Chapter 6 Status
6.1
Status Information andFilter
The following figure illustrates the status information and filter on the XL100.
4 3
4 bytes
2 1
Status information
Filter
4 3 2 1 Condition register
• The IF command can be used to set the filter.
• When a status indicated on the following page is entered, the corresponding bit in the condition register is set to “1.” The logical AND of the condition register and the filter becomes the status information.
• The IS command is used to output the status information. Status information 1 and 2 are cleared when they are output. Status information 3 and 4 are not cleared when it is output, and remains at “1” while the event is occurring.
• When multiple connections are up, filters can be specified for the individual connection. Therefore, the status information can be held for each connection.
5
6
7
1
2
3
4
App
Index
6-1
IM XL100C-E
6-2
6.2
Bit Structure of the Status Information
Status Information 1
Bit
0
1
Status Information 2
Bit
0
1
Status Information 3
1
2
Bit
0
5
6
3
4
7
4
5
6
7
2
3
4
5
6
7
2
3
The four groups of status information described below are output in response to a status information output request using the IS command. For the output format, see “ASCII
Output Response Syntax” in section 5.2, “Response Syntax.”
–
–
–
–
–
–
Name
–
Medium access complete
Name
–
–
Memory end
–
–
Execution error
–
–
–
–
–
–
–
–
Description
–
Set to 1 when the display, manual sampled, or screen image data file is finished being saved to the external storage medium.
Set to 1 when setting data is successfully saved or loaded.
Name
Measurement dropout
Description
Set to 1 when the measurement process could not keep up.
Decimal point/unit information Set to 1 when the decimal point/unit information is change change changed.
–
–
–
–
Command error
Execution error
Set to 1 when there is a command syntax error.
Set to 1 when an error occurs during command execution.
–
–
–
–
Description
–
–
Set to 1 while the free space in the internal memory or external storage medium is low.
–
–
Set to 1 when an error occurs during command execution.
–
–
IM XL100C-E
Status Information 4
Bit
0
1
2
3
4
Name
Basic setting
Memory sampling
–
Alarm activated
Accessing medium
5
6
7
E-mail started
–
–
6.2 Bit Structure of the Status Information
Description
Set to 1 while basic setting is in progress.
Set to 1 while data are being acquired to the internal memory.
–
–
–
Set to 1 while the alarm is activated.
Set to 1 when the display, manual sampled, or screen image data file is being saved to the external storage medium.
Set to 1 while the e-mail transmission is started.
1
2
3
4
5
6
7
App
Index
IM XL100C-E
6-3
Chapter 7 Error Messages
7.1
Error Messages Related to Settings
1
This section gives a list of error codes and messages of the XL100 and their corrective action. Error responses to communication commands are output in English.
Setting Errors
94
100
101
102
103
81
83
85
86
87
88
89
90
91
92
93
41
42
43
61
21
22
22
40
62
63
64
70
71
8
9
6
7
2
3
4
5
Code Message
1 System error.
Incorrect date or time setting.
A disabled channel is selected.
Incorrect function parameter.
The input numerical value exceeds the set range.
Incorrect input character string.
Too many characters.
Incorrect input mode.
Incorrect input range code.
Cannot set an alarm for a skipped channel.
The upper and lower span limits are equal.
The upper and lower scale limits are equal.
Incorrect group set character string.
There is no specified input channel.
Exceeded the number of channels which can be set.
A channel number cannot repeat in a group.
–
–
–
–
–
–
–
There is no channel specified by the MATH expression.
–
MATH expression grammar is incorrect.
MATH expression sequence is incorrect.
MATH upper and lower span values are equal.
The range of the MATH constant is exceeded.
Set range of the MATH constant is exceeded.
–
–
–
–
–
–
–
Description/Corrective Action
Contact the vendor from which you purchased the product.
–
Enter a correct value.
–
–
Enter a correct character string.
Enter the correct number of characters.
104
All space or ‘quit’ string cannot be specified.
Duplicate used combination of user ID and password.
The login password is incorrect.
The key-lock release password is incorrect.
This key is locked.
This function is locked.
Press [FUNC] key to login.
–
–
–
–
–
–
–
No permission to enter to the SETUP mode.
Password is incorrect.
Press [ESC] key to change to the operation mode.
String including space or all space cannot be specified.
More than one address cannot be specified.
IP address doesn’t belong to class A, B, or C.
The result of the masked IP address is all 0s or 1s.
SUBNET mask is incorrect.
The net part of default gateway is not equal to that of
IP address.
FTP client failed because the memory mode is ‘manual’.
–
–
–
–
–
–
Press ESC.
Spaces are not allowed in the Web browser user name and password.
Only one sender address is allowed.
–
2
3
4
5
6
7
App
Index
7-1
IM XL100C-E
7.1 Error Messages Related to Settings
Execution Errors
Code Message
150 This action is not possible because sampling is in progress.
151
152
153
This action is not possible during sampling or calculating.
This action is not possible because saving is in progress.
Description/Corrective Action
–
–
Wait for the data save operation to complete.
Wait for the format operation to complete.
155
160
This action is not possible because formatting is in progress.
The message is not written while sampling is stopped.
Cannot load the specified data. Change the memory setting.
–
–
7-2
IM XL100C-E
7.2
Error Messages Related to Operation
This section gives a list of error codes and messages of the XL100 and their corrective action. Error responses to communication commands are output in English.
External Storage Media Operation Errors
216
217
218
219
220
230
231
212
213
214
215
Code Message
200 Operation aborted because an error was found in media.
Description/Corrective Action
Check the external storage medium.
201
202
210
211
Not enough free space on media.
Media is read-only.
Media has not been inserted.
Media is damaged or not formatted.
Replace the external storage medium.
Set the external storage medium to enable writing.
Insert an external storage medium.
Replace the external storage medium or format it.
Format error.
The file is read-only.
There is no file or directory.
Exceeded the allowable number of files.
Format the external storage medium again.
Access another file or make the file write-enable.
–
Replace the external storage medium.
Delete unneeded files.
The file or directory name is incorrect.
Unknown file type.
Directory exists. Delete the directory or change directory name.
Invalid file or directory operation.
The file is already in use. Try again later.
There is no setting file.
Abnormal setting exists in file.
–
Specify another file.
–
Tried to delete multiple directory levels.
Wait until the file is accessible.
Specify another file.
Specify another file.
Review Display Errors
Code
232
233
234
Message
There is no available data.
Description/Corrective Action
Displayed when showing the review display.
Specify another file.
The specified review data do not exist.
Displayed when showing the review display.
The specified channel is not assigned to the display group. –
1
2
3
4
5
6
7
App
Index
7-3
IM XL100C-E
7.2 Error Messages Related to Operation
E-mail and Web Server Errors
Code Message
260 IP address is not set or ethernet function is not available.
Description/Corrective Action
An IP address has not been assigned to the XL100.
Check the IP address.
261 SMTP server is not found.
262 Cannot initiate E-mail transmission.
Occurs when the SMTP server is specified by name.
• Check the DNS setting.
• Check the SMTP server name.
• The host name of the XL100 is not correct. Check the host name.
• The port number setting of the SMTP server is not correct.
Check the port number.
263
264
265
Sender’s address rejected by the server.
Some recipients’ addresses are invalid.
SMTP protocol error.
266
267
268
269
275
276
277
Ethernet cable is not connected.
Could not connect to SMTP server.
to the network.
E-mail transmission request failed.
E-mail transfer error.
The current image cannot be output to the Web.
Image data currently being created. Unable to perform key operation.
Could not output screen to Web.
Check the sender’s address.
Check the recipient’s address.
May occur if a network failure (cable problems, duplicate addresses, network device failure, and so on) occurs in the middle of the e-mail transmission.
Check the cable connection.
• Check to see that the SMTP server is connected
• If the SMTP server name is specified using an IP address, check to see that the IP address is correct.
Contact the vendor from which you purchased the product.
May occur if a network failure (cable problems, duplicate addresses, network device failure, and so on) occurs in the middle of the e-mail transmission.
The setup display cannot be output to the Web browser.
This message is displayed on the Web browser.
Try again a little later.
This message is displayed on the Web browser.
This message is displayed on the Web browser.
7-4
IM XL100C-E
7.2 Error Messages Related to Operation
FTP Client Errors
The detail code does not appear in the error message on the screen. You can view the code on the FTP log display of the XL100 or using the FTP log output via communications.
Code Message
280 IP address is not set or FTP function is not available.
Further details are provided by the character string that appears after error code 280.
281
282
Character String and Details
HOSTADDR
An IP address has not been assigned to the XL100.
Check the IP address.
DORMANT
Internal processing error.
*1
LINK
Data link is disconnected.
Check the cable connection.
FTP mail box operation error.
Further details are provided by the character string that appears after error code 281.
Character String and Details
Internal processing error.
*1
STATUS
Internal processing error.
*1
TIMEOUT
Internal processing error.
*1
PRIORITY
Internal processing error.
*1
NVRAM
Internal processing error.
*1
FTP control connection error.
Further details are provided by the character string that appears after error code 282.
Character String and Details
HOSTNAME
Failed the DNS lookup (search the IP address corresponding to the host name).
Check the DNS setting and the destination host name.
*1
TCPIP
Internal processing error.
*1
UNREACH
Failed to connect to a control connection server.
Check the address setting and that the server is running.
OOBINLINE
Internal processing error.
*1
NAME
Internal processing error.
*1
CTRL
The control connection does not exist.
Check that the server does not drop the connection and that it responds within the proper time period.
IAC
Failed to respond in the TELNET sequence.
Check that the server does not drop the connection and that it responds within the proper time period.
ECHO
Failed to transmit data on the control connection.
Check that the server does not drop the connection and that it responds within the proper time period.
REPLY
Failed to receive data on the control connection.
Check that the server does not drop the connection and that it responds within the proper time period.
SERVER
The server is not in a condition to provide the service.
Check that the server is in a condition in which service can be provided.
IM XL100C-E
7-5
1
2
3
4
5
6
7
App
Index
7.2 Error Messages Related to Operation
Code Message
283 FTP command was not accepted.
Further details are provided by the character string that appears after error code 283.
284
Character String and Details
USER
Failed user name verification.
Check the user name setting.
PASS
Failed password verification.
Check the password setting.
ACCT
Failed account verification.
Check the account setting.
TYPE
Failed to change the transfer type.
Check that the server supports the binary transfer mode.
CWD
Failed to change the directory.
Check the initial path setting.
PORT
Failed to set the transfer connection.
Check that the security function is disabled.
PASV
Failed to set the transfer connection.
Check that the server supports PASV commands.
SCAN
Failed to read the transfer connection settings.
Check that proper response to the PASV command is received from the server.
FTP transfer setting error.
Further details are provided by the character string that appears after error code 284.
285
Character String and Details
MODE
Internal processing error.
*1
LOCAL
Internal processing error.
*1
REMOTE
The destination file name is not correct.
Check that you have the authority to create or overwrite files.
ABORT
File transfer abort was requested by the server.
Check the server for the reason for the abort request.
FTP data connection error.
Further details are provided by the character string that appears after error code 285.
Character String and Details
SOCKET
Failed to create a socket for the transfer connection.
*2
BIND
Failed the transfer connection command.
*2
CONNECT
Failed the transfer connection.
*2
LISTEN
Failed the transfer connection reception.
*2
ACCEPT
Failed to accept the transfer connection.
*2
SOCKNAME
Internal processing error.
*2
RECV
Failed to receive data over the transfer connection.
*2
SEND
Failed to send data over the transfer connection.
*2
7-6
IM XL100C-E
7.2 Error Messages Related to Operation
Code Message
286 FTP file transfer error.
Further details are provided by the character string that appears after error code 286.
Character String and Details
READ
Internal processing error.
*1
WRITE
Internal processing error.
*1
*1 Contact the vendor from whom you purchased the product.
*2 These errors may occur if the network experiences trouble during the data transmission (bad cable connection, duplicate addresses, network equipment failure).
Note
The FTP client function on the XL100 has a timer function that drops the connection if there is no data transfer for two minutes. If the server does not respond within this time period, the transfer fails.
1
2
3
4
5
6
7
App
Index
IM XL100C-E
7-7
7.3
Communication Error Messages
This section gives a list of error codes and messages of the XL100 and their corrective action. Error responses to communication commands are output in English.
Setting/Basic Setting/Output Communication Command and Setting Data Load Errors
351
352
353
354
Code Message
300 Command is too long.
301
302
303
350
Too many number of commands delimited with ‘;’.
This command has not been defined.
Data request command can not be enumerated with sub-delimiter.
Command is not permitted to the current user level.
This command cannot be specified in the current mode.
The option is not installed.
This command cannot be specified in the current setting.
This command is not available during sampling or calculating.
Memory Access Errors Using Setting/Basic Setting/Output Communication
Commands
An English error message is returned via the communication interface. It is not shown on the XL100 display.
Code Message
360 Output interface must be chosen from Ethernet or RS by using ‘XO’ command.
362
363
There are no data to send ‘NEXT’ or ‘RESEND’.
All data have already been transferred.
Maintenance/Test Communication Command Errors
An English error message is returned via the communication interface. It is not shown on the XL100 display.
393
394
395
396
397
Code Message
390 Command error.
391
392
Delimiter error.
Parameter error.
No permission.
No such connection.
Use ‘quit’ to close this connection.
Failed to disconnect.
No TCP control block.
7-8
Other Communication Messages+
An English error message is returned via the communication interface. It is not shown on the XL100 display.
403
404
410
411
Code Message
400 Input username.
401
402
Input password.
Select username from ‘admin’ or ‘user’.
Login incorrect, try again!
No more login at the specified level is acceptable.
Login successful. (The special user level)
Login successful. (The general user level)
IM XL100C-E
7.3 Communication Error Messages
Code Message
420 Connection has been lost.
421
422
The number of simultaneous connection has been exceeded.
Communication has timed-out.
ModBus Master Error Log
An English error message is returned via the communication interface. It is not shown on the XL100 display.
Code Message
700 Data could not be received within communication loop time.
701
702
Connection to some slave is suspended.
Connection to slave(s) has recovered.
1
2
3
4
5
6
7
App
Index
IM XL100C-E
7-9
Appendix
Appendix 1 ASCII Character Codes
1
E
F
0 1 2
SP
2
3
0
1
4
5
&
6
(
7
)
8
*
9
A
B
C
+
LF
–
ESC
.
/
D CR
#
%
5
6
3
4
1
2
3
0
7
8
9
:
M
N
K
L
O
I
J
G
H
E
F
C
D
A
B
4
@
•
_
X
Y
V
W
T
U
R
S
P
Q
5
Upper 4 bits
6 7 8 9 A B
p q a b r s c d t u e f v w g h x y
Z j i z m n k l o
C D E F
2
3
4
5
6
7
Index
App-1
IM XL100C-E
Appendix 2 Login Process
App-2
You log into the XL100 from your PC to use the functionality of the setting/measurement server and the maintenance/test server via the Ethernet interface. If you complete the procedure successfully up to login complete in the following figure, the commands in chapter 5 become functional.
When Using the Ethernet Login Function of the XL100
Connect
No
E1 421
Within the number of connections
*1
Disconnect
E1 400
No
Within 2 minutes?
User name
Entered "quit"?
Yes
1
Increment retry count
E1 401
E1 422
Disconnect
1
E1 420
Within 2 minutes?
E1 403 E1 404
Password
Verification match?
No
Within the number of simultaneous uses?
*3
No
E0
Wait 5 s
Within 3 retries?
*2
No
1
Within 3 retries?
*3
No
1
Disconnect
Login complete
Start
Stop
User entry
Decision
Transition
E1 403 Response from the XL100 (message omitted)
For a description of the response format, see section 6.2.
Code
(For a description of the codes and messages, see chapter 8, "Error Messages.")
*1 Connections cannot exceed the maximum number of connections (see section 2.1).
*2 If you attempt to log in using a wrong password four consecutive times, the communication is dropped (the number of retries for login is three).
*3 If you attempt to log in causing the number of simultaneous uses at the administrator or user level to be exceeded (see section 2.1) four consecutive times, the communication is dropped
(even if the password is correct).
IM XL100C-E
IM XL100C-E
Appendix 2 Login Process
When Not Using the Ethernet Login Function of the XL100
Login as “admin” or “user.”
• You can log into the XL100 as an administrator by accessing the XL100 using the user name “admin.”
• You can log into the XL100 as a user by accessing the XL100 using the user name
“user.”
Connect
No
E1 421
Within the number of connections?
Disconnect
E1 402
No
Within 2 minutes?
User name
Entered "quit"?
Yes
1 Increment retry count
1
2
3
4
5
6
7
E1 422
Disconnect
E1 403 E1 404
1
E1 420
Disconnect
Verification match?
No
Within the number of simultaneous uses?
No
E0
Within 3 retries?
No
1
Within 3 retries?
No
1
Index
Login complete
App-3
Appendix 3 Data Output Flow
Example in Which the List of Files in Directory DATA0 Is Output 10 Files at a Time
START
Send the command
ME DIR,/DATA0/,10
Receive the response
EA
• • • • • •
• • • • • • xxxKbyte free
EN
File list
Command to send
Command description
Received response data
Output command for the first file list.
Specify the number of file lists to be output when issuing this command.
Are there more
* file lists?
YES
Send the command
ME DIR,/DATA0/,10
Receive the response
EA
• • • • • •
• • • • • • xxxKbyte free
EN
NO
Output the subsequent file lists.
* When the number of output file lists
is smaller than the maximum number
of file lists specified by the ME DIR
command (10 in this example), one
can conclude that there are no more
file lists.
File list
END
App-4
IM XL100C-E
Appendix 3 Data Output Flow
Example in Which the File 10101000.DDS in the DATA0 Directory Is Output
START
Command to send
Command description
Received response data
Send the command
ME GET,/DATA0/10101000.DDS
Receive the response
BINARY header
BINARY data
BINARY footer
Specify the file name using full path and output the data.
1
2
3
4
5
Are there more data?
*
YES
Send the command
ME NEXT
Receive the response
BINARY header
BINARY data
BINARY footer
NO
Output the subsequent data.
* Bit 0 of the BINARY header flag
0: There is more data.
1: Data transmission is complete.
6
7
Index
END
IM XL100C-E
App-5
Index
Index
A
access control ................................................................... 2-18
access privilege, granting of ............................................... 1-4
account ............................................................................... 2-8
administrator ............................................................. 1-4, 2-13
affirmative response ............................................................ 5-3
AK command .................................................................... 5-30
alarm delay time, setting of ............................................... 5-29
alarm line, setting of .......................................................... 5-28
alarm, setting of ................................................................ 5-27
alarm settings .................................................................... 5-31
alarm status, acknowledgement of ................................... 5-30
alarm summary ................................................................. 5-12
ASCII character codes ................................................... App-1
ASCII output response syntax ............................................ 5-4
automatic file transfer .......................................................... 1-3
automatic transfer ............................................................... 2-8
average, setting of ............................................................ 5-28
B
basic setting command, setting whether to save or di ...... 5-34
basic setting commands ..... 5-31, 5-32, 5-33, 5-34, 5-35, 5-
basic syntax ...................................................................... 5-14
baud rate ..................................................................... 3-3, 3-6
BD command .................................................................... 5-29
binary output syntax .......................................................... 5-14
BO command .................................................................... 5-38
BO flag .............................................................................. 5-15
burnout setting (query only) .............................................. 5-31
BY command .................................................................... 5-29
byte output order, setting of .............................................. 5-38
bytes, number of ............................................................... 5-16
C
calculating equation, setting of .......................................... 5-26
calculation channels .......................................................... 5-24
CC command .................................................................... 5-38
channel display color and waveform line width, setti ........ 5-29
checksum, setting of ......................................................... 5-38
close command ................................................................. 5-42
CM command .................................................................... 5-30
command name .................................................................. 5-1
command-response ............................................................ 5-3
commands .......................................................................... 4-4
communication channels .................................................. 5-24
communication distance ..................................................... 3-5
communication error messages .................................. 7-8, 7-9
communication function ...................................................... 1-1
communication input data ................................................... 4-2
communication input data, setting of ................................ 5-30
communication interface, selection of ................................. 2-3
communication interval ....................................................... 4-4
communication log .............................................................. 5-6
communication log display ................................................ 2-15
communication method, selection of ................................. 5-32
communication timeout ............................................... 1-4, 2-5
IM XL100C-E
1
connection status, checking ................................................ 2-7
connection with other devices, disconnection of ............... 5-42
CR+LF ................................................................................. 5-2
CS command .................................................................... 5-38
CS-RS ................................................................................. 3-2
D
data length .................................................................. 3-3, 3-6
data length (binary output) ................................................ 5-14
data output flow .................................................. App-4, App-5
data reception control ......................................................... 3-2
data sum ........................................................................... 5-14
data transmission control .................................................... 3-2
date and time setting ......................................................... 5-27
DC voltage ........................................................................ 5-23
decimal place/unit information ............................................ 5-4
Default Gateway ................................................................. 2-4
delimiter .............................................................................. 5-2
DHCP ................................................................................. 2-3
display backlight auto off, setting of .................................. 5-29
display, switching of .......................................................... 5-30
DNS ................................................................................. 2-4
DNS server ......................................................................... 2-4
DNS Setting ........................................................................ 2-6
DNS, setting of .................................................................. 5-35
E
e-mail and Web server errors ............................................. 7-4
e-mail log .......................................................................... 5-11
e-mail log display .............................................................. 2-17
e-mail message, contents of ............................................. 2-30
e-mail, setting the contents to be transmitted ................... 5-37
e-mail SMTP server name, setting of ................................ 5-38
e-mail transmission ........... 1-5, 2-23, 2-24, 2-25, 2-26, 2-27
e-mail transmission test .................................................... 2-28
EM command .................................................................... 5-31
END flag ............................................................................ 5-15
end trigger, selection of ..................................................... 5-33
error log display ................................................................ 2-15
error message log ............................................................... 5-8
ESC C command .............................................................. 5-41
ESC O command .............................................................. 5-41
eth command .................................................................... 5-42
ETHERNET ......................................................................... 2-6
Ethernet communication timeout, setting of ...................... 5-35
Ethernet connection, disconnection of .............................. 5-38
Ethernet interface, checking the connection status o ......... 2-7
Ethernet interface, configuration of ............. 2-3, 2-4, 2-5, 2-6
Ethernet interface, connection of ........................................ 2-2
Ethernet interface, specifications of .................................... 2-1
Ethernet parameters, setting of ........................................... 2-3
Ethernet statistical information, outputting of .................... 5-42
EV command .................................................................... 5-30
execution errors .................................................................. 7-2
explanation of functions .............................. 1-2, 1-3, 1-4, 1-5
Index-1
2
3
4
5
6
7
App
Index
external storage media operation errors ............................. 7-3
external storage medium, saving to .................................. 5-30
F
FC command .................................................................... 5-39
FD command .................................................................... 5-40
FE command ..................................................................... 5-39
files, transferred .................................................................. 2-8
filter ................................................................................. 6-1
FL command ..................................................................... 5-40
flag (output byte order/checksum/END check) ................. 5-15
FTP ................................................................................. 1-1
FTP client errors ................................................................. 7-5
FTP client, setting of ................................................... 2-8, 2-9
FTP destination ................................................................... 2-8
FTP log display ................................................................. 2-16
FTP server .......................................................................... 1-3
FTP server name ................................................................ 2-8
FTP test .......................................................... 1-3, 2-11, 2-12
FTP transfer timing, setting of ........................................... 5-36
FU command .................................................................... 5-40
function codes of the Modbus protocol ............................... 4-1
G
group, setting of ................................................................ 5-28
H
handshaking ........................................................................ 3-3
handshaking method ........................................................... 3-2
header sum ....................................................................... 5-14
hold register ........................................................................ 4-2
host name ........................................................................... 2-4
HTTP ................................................................................. 1-1
I
ID command ...................................................................... 5-39
identifier (binary data) ....................................................... 5-15
IF command ...................................................................... 5-38
initial path ............................................................................ 2-9
input range parameters ........................................... 5-23, 5-24
input range, setting of ....................................................... 5-25
input register ....................................................................... 4-2
integrated value, calculation of ......................................... 5-16
interval .............................................................................. 2-24
IP ................................................................................. 1-1
IP address ........................................................................... 2-4
IP Address Setting .............................................................. 2-6
IP address, subnet mask, and default gateway ................ 5-34
IPV6 information, querying of ............................................ 5-34
IS command ...................................................................... 5-40
K
keep alive ............................................................................ 2-5
keepalive ............................................................................. 1-5
key login log ........................................................................ 5-9
L
LAN port LED ...................................................................... 2-7
language, setting of ........................................................... 5-32
LF ................................................................................. 5-2
LI command ...................................................................... 5-30
LO command .................................................................... 5-30
log and alarm summary, outputting of ............................... 5-40
logging, starting/stopping of .............................................. 5-30
logic ............................................................................... 5-23
......................................................................... 1-4, 2-5
login name .......................................................................... 2-8
login process ...................................................... App-2, App-3
M
maintenance/test commands ........................ 5-22, 5-42, 5-43
maintenance/test communication command errors ............ 7-8
maintenance/test server ...................................................... 1-2
manual sampled data ........................................................ 5-18
master (of Modbus) ............................................................. 4-1
maximum number of simultaneous connections ................. 2-1
ME command .................................................................... 5-40
measured/calculated binary data syntax ........................... 5-16
measured/calculated data ................................................... 5-5
memory access error using setting/basic setting/outp ........ 7-8
Modbus error response ....................................................... 4-3
Modbus Master ................................................................... 1-2
Modbus master, data dropout handling of .................. 4-7, 4-8
ModBus master error log .................................................... 7-9
Modbus master function ...................................................... 4-4
Modbus master function, setting the command of ............ 5-36
Modbus master function, setting the operation of ............. 5-36
Modbus protocol ......................................................... 1-1, 4-1
Modbus Slave ..................................................................... 1-2
Modbus slave ...................................................................... 1-2
most recent measured/calculated data, outputting o ........ 5-40
multiple negative responses ............................................... 5-3
N
negative response ............................................................... 5-3
number of simultaneous users ............................................ 2-1
O
OFF-OFF ............................................................................ 3-2
operation, error messages related to .. 7-3, 7-4, 7-5, 7-6, 7-7
operator page, contents of ................................................ 2-22
other communication messages ......................................... 7-8
output commands ............................................................. 5-22
output commands (control) ............................................... 5-38
Output commands (RS-485 and USB dedicated commands) . 5-41
output commands (setting/measurement/data output) .. 5-39, 5-40
output flow of the file list of the external storage ............ App-4
Index-2
IM XL100C-E
P
parameters .......................................................................... 5-1
parity check ................................................................. 3-3, 3-6
password ............................................... 2-8, 2-13, 2-18, 2-19
PASV mode ........................................................................ 2-8
port number ............................................................... 2-8, 2-23
primary ........................................................................ 2-4, 2-8
privilege ............................................................................... 1-4
PS command .................................................................... 5-30
pulse ............................................................................... 5-24
Q
query ................................................................................. 5-2
query response ................................................................... 5-4
quit command ................................................................... 5-43
R
recipient ............................................................................ 2-23
register assignments ........................................................... 4-2
response syntax .. 5-3, 5-4, 5-5, 5-6, 5-7, 5-8, 5-9, 5-10, 5-
11, 5-12, 5-13, 5-14, 5-15, 5-16, 5-17, 5-18
review display errors ........................................................... 7-3
RJC setting (query only) ................................................... 5-32
RS-232 interface, setting of ................................................ 3-3
RS-485 and USB communication dedicated syntax ......... 5-18
RS-485 interface, setting of ................................................ 3-6
RTD ............................................................................... 5-23
S
SA command .................................................................... 5-27
sampling interval, setting of .................................... 5-27, 5-32
SB command .................................................................... 5-28
SC command .................................................................... 5-29
screen image data ............................................................ 5-18
screen image data, outputting of ....................................... 5-39
SD command .................................................................... 5-27
SE command .................................................................... 5-28
secondary ................................................................... 2-4, 2-8
sender ............................................................................... 2-23
serial interface, setting of .................................................. 5-35
serial interface specifications .............................. 3-1, 3-5, 3-7
setting commands ................................................... 5-19, 5-21
setting commands (control) ............................................... 5-30
setting commands (setting) ....... 5-25, 5-26, 5-27, 5-28, 5-29
setting data, loading of ...................................................... 5-36
setting data, outputting of .................................................. 5-39
setting data, saving of ............................................. 5-30, 5-36
setting errors ....................................................................... 7-1
setting/basic setting/output communication and setti .......... 7-8
setting/measurement server ............................................... 1-2
setup data, loading of ........................................................ 5-30
single negative response .................................................... 5-3
SL command ..................................................................... 5-28
slave (of Modbus) ............................................................... 4-1
slave address .............................................................. 3-3, 3-6
SMTP ................................................................................. 1-1
SMTP server ..................................................................... 2-23
SNTP ......................................................................... 1-5, 2-5
SNTP (time synchronization function), setting of .............. 5-35
SNTP Setting ...................................................................... 2-6
SO command .................................................................... 5-26
source URL ....................................................................... 2-23
IM XL100C-E
Index
special data values ........................................................... 5-17
SQ command .................................................................... 5-29
SR command .................................................................... 5-25
ST command ..................................................................... 5-28
standard protocol ................................................................ 1-1
start trigger, selection of .................................................... 5-32
start/stop (e-mail) .............................................................. 2-30
statistical calculation, setting of ......................................... 5-34
status filter, setting of ........................................................ 5-38
status information ...................................................... 5-12, 6-1
status information, bit structure of ............................... 6-2, 6-3
status information, outputting of ........................................ 5-40
stop bit ................................................................................ 3-3
sub delimiter ........................................................................ 5-2
subnet mask ........................................................................ 2-4
SV command .................................................................... 5-28
SW command ................................................................... 5-27
SX command .................................................................... 5-28
system data output (query only) ........................................ 5-39
T
tag, setting of .................................................................... 5-28
TC ............................................................................... 5-23
TCP ................................................................................. 1-1
terminator .................................................................... 3-5, 5-2
thermocouple .................................................................... 5-23
time zone, setting of .................................................. 2-3, 5-34
timeout ................................................................................ 2-5
timeout value ....................................................................... 4-4
trigger, selection of ............................................................ 5-32
U
UD command .................................................................... 5-30
URL ............................................................................... 2-21
USB ID, setting of ............................................................... 3-8
....................................................................... 1-4, 2-13
user authentication .............................................................. 1-4
user level ................................................................. 2-13, 5-14
user level, outputting of ..................................................... 5-40
user name ..................................................... 2-13, 2-18, 2-19
V
VOLT ............................................................................... 5-23
W
Web browsers ................................................................... 2-21
Web operation log ............................................................... 5-9
Web operation log display ................................................. 2-16
Web server ............................................ 1-4, 2-18, 2-19, 2-20
Web server function, enabling/disabling of ....................... 5-36
X
XA command .................................................................... 5-31
XB command .................................................................... 5-31
XE command .................................................................... 5-34
XG command .................................................................... 5-34
XH command .................................................................... 5-34
XJ command ..................................................................... 5-32
XK command .................................................................... 5-32
XL command ..................................................................... 5-33
XO command .................................................................... 5-32
XON-XOFF ......................................................................... 3-2
Index-3
1
2
3
4
5
6
7
App
Index
XT commmand .................................................................. 5-32
XU command .................................................................... 5-32
XV command .................................................................... 5-32
XY command .................................................................... 5-34
Y
YA command .................................................................... 5-34
YB command .................................................................... 5-34
YE command .................................................................... 5-35
YG command .................................................................... 5-36
YI command ...................................................................... 5-36
YK command .................................................................... 5-34
YL command ..................................................................... 5-36
YM command .................................................................... 5-36
YN command .................................................................... 5-35
YO command .................................................................... 5-36
YQ command .................................................................... 5-35
YS command .................................................................... 5-35
YT command ..................................................................... 5-36
YU command .................................................................... 5-37
YV command .................................................................... 5-38
YW command ................................................................... 5-38
YX command .................................................................... 5-38
Index-4
IM XL100C-E