SONBEST SC7200B RS485 Interface User Manual

Add to My manuals
11 Pages

advertisement

SONBEST SC7200B RS485 Interface User Manual | Manualzz

SC7200B Us er Ma nual http://www.sonbus.com/

SC7200B

RS485 interface with communication function temperature controller

User Manual

File Version: V21.12.10

SC7200B using the standard RS485 bus MODBUS-RTU protocol,easy access to PLC , DCS and other instruments or systems for monitoring temperature state quantities.The internal use of high -precision sensing core and related devices to ensure high reliability and excellent long-term stability,can be customized RS232,RS485,CAN,4-20mA,DC0~5V\10V,ZIGBEE,Lora,WIFI,GPRS and other output methods.

Sha nghai Son best Industrial Co., Ltd Page1

SC7200B Us er Ma nual http://www.sonbus.com/

Technical Parameters

Technical parameter

Brand

Temperature measuring range

Temperature measuring accuracy

Communication Interface

Default baud rate

Power

Running temperature

Working humidity

Product Size

Parameter value

SONBEST

-50 ℃ ~120 ℃

± 0.5

℃ @25 ℃

RS485

9600 8 n 1

AC185~265V 1A

-40~80° C

5%RH~90%RH

How to wiring?

Sha nghai Son best Industrial Co., Ltd Page2

SC7200B Us er Ma nual http://www.sonbus.com/

Application solution

Sha nghai Son best Industrial Co., Ltd Page3

SC7200B Us er Ma nual http://www.sonbus.com/

Sha nghai Son best Industrial Co., Ltd Page4

SC7200B Us er Ma nual http://www.sonbus.com/

Sha nghai Son best Industrial Co., Ltd Page5

SC7200B Us er Ma nual http://www.sonbus.com/

Sha nghai Son best Industrial Co., Ltd Page6

SC7200B Us er Ma nual http://www.sonbus.com/

How to use?

Sha nghai Son best Industrial Co., Ltd Page7

SC7200B Us er Ma nual http://www.sonbus.com/

Communication Protocol

The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands are hexadecimal data. The default device address is 1 when the device is shipped, the default baud rate is

9600, 8, n, 1

1. Read Data (Function id 0x03)

Inquiry frame (hexadecimal), sending example: Query 1# device 1 data, the host computer sends the command:01 03 00 00 00 01 84 0A .

Device ID

01

Function id

03

Start Address

00 00

Data Length

00 01

CRC16

84 0A

For the correct query frame, the device will respond with data:01 03 02 00 79 79 A6 , the response format is parsed as follows:

Device ID Function id Data Length Data 1 Check Code

01 03 02 00 79 79 A6

Data Description: The data in the command is hexadecimal. Take data 1 as an example. 00 79 is converted to a decimal value of 121. If the data magnification is 100, the actual value is 121/100=1.21.

Others and so on.

2. Data Address Table

Address Start Address

40001 00 00

Description temperature

Data type

Read Only

Value range

0~65535

40101

40102

40103

40104

00 64

00 65

00 66

00 67 model code total points

Device ID baud rate

40105

40106

00 68

00 69 mode protocol

3 read and modify device address

(1) Read or query device address

read/write read/write read/write read/write read/write read/write

0~65535

1~20

1~249

0~6

1~4

1~10

Sha nghai Son best Industrial Co., Ltd Page8

SC7200B Us er Ma nual http://www.sonbus.com/

If you don't know the current device address and there is only one device on the bus, you can use the command FA 03 00 64 00 02 90 5F Query device address.

Device ID Function id Start Address Data Length CRC16

FA 03 00 64 00 02 90 5F

FA is 250 for the general address. When you don't know the address, you can use 250 to get the real device address, 00 64 is the device model register.

For the correct query command, the device will respond, for example the response data is: 01 03 02

07 12 3A 79, the format of which is as shown in the following table:

Device ID Function id Start Address Model Code CRC16

01 03 02 55 3C 00 01 3A 79

Response should be in the data, the first byte 01 indicates that the real address of the current device is,

55 3C converted to decimal 20182 indicates that the current device main model is 21820, the last two bytes

00 01 Indicates that the device has a status quantity.

(2)Change device address

For example, if the current device address is 1, we want to change to 02, the command is:01 06 00 66

00 02 E8 14 .

Device ID Function id Start Address Destination CRC16

01 06 00 66 00 02 E8 14

After the change is successful, the device will return information: 02 06 00 66 00 02 E8 27 , its format is parsed as shown in the following table:

Device ID

01

Function id

06

Start Address

00 66

Destination

00 02

CRC16

E8 27

Response should be in the data, after the modification is successful, the first byte is the new device address. After the general device address is changed, it will take effect immediately. At this time, the user needs to change the query command of the software at the same time.

4 Read and Modify Baud Rate

(1) Read baud rate

The device default factory baud rate is 9600. If you need to change it, you can change it according to the following table and the corresponding communication protocol. For example, read the current device's baud rate ID, the command is:01 03 00 67 00 01 35 D5 , its format is parsed as follows.

Device ID Function id Start Address Data Length CRC16

01 03 00 67 00 01 35 D5

Read the baud rate encoding of the current device. Baud rate encoding: 1 is 2400; 2 is 4800; 3 is 9600;

4 is 19200; 5 is 38400; 6 is 115200.

For the correct query command, the device will respond, for example the response data is: 01 03 02

00 03 F8 45, the format of which is as shown in the following table:

Device ID Function id Data Length Rate ID CRC16

01 03 02 00 03 F8 45

coded according to baud rate, 03 is 9600, ie the current device has a baud rate of 9600.

(2)Change the baud rate

For example, changing the baud rate from 9600 to 38400, ie changing the code from 3 to 5, the command is: 01 06 00 67 00 05 F8 1601 03 00 66 00 01 64 15 .

Device ID Function id Start Address Target Baud Rate CRC16

01 03 00 66 00 01 64 15

Sha nghai Son best Industrial Co., Ltd Page9

SC7200B Us er Ma nual http://www.sonbus.com/

Change the baud rate from 9600 to 38400, changing the code from 3 to 5. The new baud rate will take effect immediately, at which point the device will lose its response and the baud rate of the device should be queried accordingly. Modified.

5 Read Correction Value

(1) Read Correction Value

When there is an error between the data and the reference standard, we can reduce the display error by adjusting the correction value. The correction difference can be modified to be plus or minus 1000, that is, the value range is 0-1000 or 64535 -65535. For example, when the display value is too small, we can correct it by adding 100. The command is: 01 03 00 6B 00 01 F5 D6 . In the command 100 is hex 0x64 If you need to reduce, you can set a negative value, such as -100, corresponding to the hexadecimal value of

FF 9C, which is calculated as 100-65535=65435, and then converted to hexadecimal to 0x FF 9C. The correction value starts from 00 6B. We take the first parameter as an example. The correction value is read and modified in the same way for multiple parameters.

Device ID Function id Start Address Data Length CRC16

01 03 00 6B 00 01 F5 D6

For the correct query command, the device will respond, for example the response data is: 01 03 02

00 64 B9 AF, the format of which is as shown in the following table:

Device ID

01

Function id

03

Data Length

02

Data value

00 64

CRC16

B9 AF

In the response data, the first byte 01 indicates the real address of the current device, and 00 6B is the first state quantity correction value register. If the device has multiple parameters, other parameters operate in this way. The same, the general temperature, humidity have this parameter, the light generally does not have this item.

(2)Change correction value

For example, the current state quantity is too small, we want to add 1 to its true value, and the current value plus 100 correction operation command is:01 06 00 6B 00 64 F9 FD .

Device ID Function id Start Address Destination CRC16

01 06 00 6B 00 64 F9 FD

After the operation is successful, the device will return information: 01 06 00 6B 00 64 F9 FD, the parameters take effect immediately after successful change.

Disclaimer

This document provides all information about the product, does not grant any license to intellectual property, does not express or imply, and prohibits any other means of granting any intellectual property rights, such as the statement of sales terms and conditions of this product, other issues. No liability is assumed. Furthermore, our company makes no warranties, express or implied, regarding the sale and use of this product, including the suitability for the specific use of the product, the marketabi lity or the infringement liability for any patent, copyright or other intellectual property rights, etc. Product specifications and product descriptions may be modified at any time without notice.

Contact Us

Company: Shanghai Sonbest Industrial Co., Ltd

Address:Building 8,No.215 North east road,Baoshan District,Shanghai,China

Web: http://www.sonbest.com

Web: http://www.sonbus.com

SKYPE: soobuu

Sha nghai Son best Industrial Co., Ltd Page10

SC7200B Us er Ma nual http://www.sonbus.com/

Email: [email protected]

Tel: 86-021-51083595 / 66862055 / 66862075 / 66861077

Sha nghai Son best Industrial Co., Ltd Page11

advertisement

Key Features

  • Precise temperature measurement and control.
  • RS485 interface for easy integration.
  • MODBUS-RTU protocol for seamless communication.
  • Wide temperature range (-50°C to 120°C).
  • Accuracy of ±0.5°C for reliable measurements.
  • Multiple output options for versatility.

Related manuals

Frequently Answers and Questions

What is the temperature measuring range of the SC7200B?
The SC7200B has a temperature measuring range of -50°C to 120°C.
What communication protocol does the SC7200B use?
The SC7200B uses the MODBUS-RTU protocol for communication.
What is the default baud rate of the SC7200B?
The default baud rate of the SC7200B is 9600, 8, n, 1.