Carrier 38APD 025-130 Air Cooled Condensing Unit Instruction manual
Carrier 38APD 025-130 Vibration Isolation Accessory is designed to reduce noise and vibration transmitted from your air conditioning unit to the supporting structure. It consists of 4 oil-resistant, ribbed neoprene pads that can be installed during initial unit installation or retrofitted to existing units. The pads are placed under the mounting feet of the unit and help to isolate it from the surrounding environment. This can be particularly useful in reducing noise and vibration in sensitive areas such as bedrooms or offices.
Anúncio
Anúncio
38APD 025-130, 38APS 025-065,
09DPM 035-130, 09DPS 018-030
30MPA 020-071, 30MPE, 30MPW 016-071
30RAP 010-130
Vibration Isolation Accessory
Installation Instructions
Part No. 30RA-900---005, 30MP-900---003
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.
It is important to recognize safety information. This is the safetyalert symbol . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
Table 1 — Product Usage
UNIT
38APD 025-100
38APD 115-130
38APS 025-065
09DPM 035-95
09DPM 115-130
09DPS 018-030
30MPA 020-071
30MPA 020-071 with
Height Adjustment Accessory
30MPE
30MPE with
Height Adjustment Accessory
30MPW 016-071
30MPW016-071 with
Height Adjustment Accessory
30RAP 010-090
30RAP 115-130
ACCESSORY PART NO.
QTY
1
30RA-900---005
2
1
1
2
1
1
2
1
30MP-900---003
2
1
30RA-900---005
2
1
2
GENERAL
Multiple accessory packages may be required depending on prod -
uct, see Table 1 for accessory package selection. Each vibration
isolation accessory package consists of 4 resilient neoprene pads
Refer to Table 2. The pads are oil-resistant and have a ribbed de
-
PRE-INSTALLATION
Remove accessory from packaging and inspect shipment for dam age. File claim with shipping company if accessory is damaged or incomplete.
INSTALLATION
The accessory kit is usually installed at the initial unit installation.
If the kit is to be installed after the unit is already in place, discon nect all power, chilled fluid piping, and refrigerant piping to the unit first.
WARNING
Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed.
Install the accessory kit as follows:
1. Rig unit per base unit installation instructions and raise unit
above its final installation location (see Fig. 3-5).
2. Locate pads at mounting points as shown in Fig. 6.
3. Lower unit in place. Note that unit must be leveled according to base unit installation instructions.
4. Restore unit power and piping connections or continue with initial unit installation.
Table 2 — Package Contents
PART NO.
DESCRIPTION
30MP-900---003
30RA-900---005
VIRBATION
PAD
PART NO.
2004386152
30GX501130
PAD DIMENSIONS in. (mm)
3.5x3.5x1/4
(89x89x6)
24x3x1/4
(610x76x6)
QTY
4
4
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53090037-01 Printed in U.S.A.
Form 09-30-38-16SI Pg 1 9-22 Replaces: 09-30-38-13SI
.25 in. ref
24.00 in.
A
3.00 in.
3.00 in.
A
Fig. 1 — Vibration Isolation Pad Dimensions (30RA-900- - -005)
.25 in. ref
Section A:A
3.50 in.
A
3.50 in.
3.50 in.
A
Section A:A
Fig. 2 — Vibration Isolation Pad Dimensions
(30MP-900- - -003)
Vibration
Isolation
Fig. 4 — 38AP, 09DP, and 30RAP
Typical Installation
Fig. 3 — 30MP Typical Installation
Vibration
Isolation
Vibration
Isolation
2
Fig. 5 — 30MP with Height Adjustment Typical
Installation
09DPS018, 30RAP010, 011, 015, and 016 Units 09DPS020-030, 30RAP018-030, 38APD025-030,
and 38APS025-030 Units
09DPM035-060, 30RAP035-060, 38APD040-070,
and 38APS040-065 Units
09DPM075-095, 38APD080-100, and 30RAP070-090 Units
09DPM115/130, 38APD115/130, and 30RAP100-150 Units
30MPA020-071, 30MPW016-071, and 30MPE Units
30MPA020-071, 30MPW016-071, and 30MPE Units with Height Adjustment Accessory
NOTE: Place pads under mounting feet.
Fig. 6 — Vibration Isolation Pad Locations
3
© 2022 Carrier
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53090037-01 Printed in U.S.A.
Form 09-30-38-16SI Pg 4 9-22 Replaces: 09-30-38-13SI
Download