Installation Instructions Regarding the Gate Operator

A) Install the gate operator only when:

1) The operator is appropriate for the construction and the usage Class of the gate.

2) All openings of a horizontal slide gate are guarded or screened from the bottom of the gate to a minimum of 4 feet (1.2 m) above the ground to prevent a 2 1/4inch (57.15 mm) diameter sphere from passing through the openings anywhere in the gate, and in that portion of the adjacent fence that the gate covers in the open position.

3) All exposed pinch points are eliminated or guarded, and

4) Guarding is supplied for exposed rollers.

B) The operator is intended for installation only on gates used for vehicles. Pedestrians must be supplied with a separate access opening.

C) The gate must be installed in a location so that enough clearance is supplied between the gate and adjacent structures when opening and closing to reduce the risk of entrapment. Swinging gates shall not open into public access areas.

D) The gate must be properly installed and work freely in both directions prior to the installation of the gate operator.

E) -

F) Controls must be far enough from the gate so that the user is prevented from coming in contact with the gate while operating the controls. Controls intended to be used to reset an operator after 2 sequential activations of the entrapment protection device or devices must be located in the line of sight of the gate outdoor or easily accessible controls shall have a security feature to prevent unauthorized use.

G) All warning signs and placards must be installed where visible in the area of the gate.

H) For a gate operator utilizing a non-contact sensor such as a photo beam:

1) See instructions on the placement of non-contact sensor for each Type of application,

2) Care shall be exercised to reduce the risk of nuisance tripping, such as when a vehicle trips the sensor while the gate still moving, and

3) One or more non-contact sensors shall be located where the risk of entrapment or obstruction exists, such as the perimeter reachable by a moving gate or barrier.

I) For a gate operator utilizing a contact sensor such as an edge sensor:

1) One or more contact sensors shall be located at the leading edge, trailing edge and postmounted both inside and outside of a vehicular horizontal slide gate.

2) One or more contact sensors shall be located at the bottom edge of a vehicular vertical lift gate.

3) One or more contact sensors shall be located at the pinch point of a vehicular vertical pivot gate.

4) A hardwired contact sensor shall be located and its wiring arranged so that the communication between the sensor and the gate operator is not subjected to mechanical damage.

5) A wireless contact sensor such as the one that transmits radio frequency (RF) signals to the gate operator for entrapment protection functions shall be located where the transmission of the signals are not obstructed or impeded by building structures, natural landscaping or similar obstruction. A wireless contact sensor shall function under the intended end-use conditions.

Important Safety Instructions

WARNING - To Reduce the Risk of Injury or Death:

1. READ AND FOLLOW ALL INSTRUCTIONS!

2. Never let children operate or play with gate controls. Keep the remote control away from children.

4. Test the gate operator monthly. The gate MUST reverse on contact with a rigid object or stop when an object activates the non-contact sensors. After adjusting the force or the limit of travel, retest the gate operator, Failure to adjust and retest the gate operator properly can increase the risk of injury or death.

5. Use the emergency release only when the gate is not moving. Make sure the power for the gate operator is off.

6. KEEP GATES PROPERLY MAINTAINED. Read the manual. Have a qualified service person make repairs to the gate or gate hardware.

7. The entrance is for vehicles only. Pedestrians must use separate entrance.

8. SAVE THESE INSTRUCTIONS.

Gate –

A moving barrier such as a swinging, sliding, raising lowering, rolling, or like, barrier, that is a stand-alone passage barrier or is that portion of a wall or fence system that controls entrance and/or egress by persons or vehicles and completes the perimeter of a defined area.

Vehicular horizontal slide-gate operator (or system) – A vehicular gate operator (or system) that controls a gate which slides in a horizontal direction that is intended for use for vehicular entrance or exit to a drive, parking lot, or the like.

Residential vehicular gate operator –

Class I – A vehicular gate operator (or system) intended for use in a home of one-to four single family dwelling, or a garage or parking area associated therewith.

Class I

Commercial/General access vehicular gate operator – Class II

A vehicular gate operator (or system) intended for use in a commercial location or building such as a multi-family housing unit (five or more single family units) hotel, garages, retail store or other building servicing the general public.

Class II

Commercial/General access vehicular gate operator –

Class III –

A vehicular gate operator (or system) intended for use in a industrial location or building such as a factory or loading dock area or other locations not intended to service the general public.

Class III

Restricted access vehicular gate operator –

Class IV – A vehicular gate operator (or system) intended for use in a guarded industrial location or building such as an airport security area or other restricted access locations not servicing the general public, in which unauthorized access is prevented via supervision by security personnel.

Class IV

IMPORTANT!

Because gate coasting distance varies with temperature, Elite

DOES NOT

recommend the installation of a catch post. This could cause the gate to collide with the post.

Correct Installation with Catch Rollers

Incorrect Installation using a Catch Post!

Guide Rollers

(Elite Part #

A UHM

)

Gate in Fully Opened Position Gate Clearances

1/4" Clearance from Top of Gate

Catch Rollers

1/2" Clearance

Between Gate and Rollers

Wall

Minimum Clearance of 5" Between Back of Gate and Wall or Other Objects in Gate's Path

Gate

CAUTION

For safety reasons, a physical stop MUST be installed on the gate prior to installation of the gate operator. This will assure that the gate does not exceed movement limits and derail while in motion.

IMPORTANT NOTICE!

Installers are required to adhere to this procedure: The UL required Warning

Signs must be installed in plain view and on both sides of each gate installed. Each sign is made with fastening holes in each corner and should be permanently secured in a suitable manner. Also the warning sticker should be placed on the operator so it is clearly visible.

Warning Signs on Both Sides of Gate

Warning Sign Clearly Visible on Gate Operator

CAUTION

Owners Must Never Let Pedestrians Cross the Path of a Moving Gate!

CAUTION

Owners Must Never Mount Any Gate Operating Devices Accessible In Between the Gate and the Wall!

CAUTION

Owners Must Never Mount Any Gate Operating Devices Accessible Through the Gate!

Guide Rollers

Warning Signs on Both Sides of Gate

2"x 2" Mesh Wire

Across Entire Gate

3" Maximum Picket Width

Guide Rollers

115 VAC for Each

Gate Operator

Over-Travel Stops on Both Ends of

Gate Rail

Steel V-Groove, High Speed Ball Bearing Wheels

Warning Sign Clearly Visible on Gate Operator

Reinforced Concrete to Bolt Operator on

U.L. Listed Underground Conduit for Wires

Pedestrians MUST have a Separate Walkway!

SL-3000-UL-DM

Two-1/2 hp Motors, 120 VAC, 4.7 amp.

Maximum Gate Length – 37 feet

Maximum Gate Weight – 800 lbs.

SL-3000-UL-1HP

Two-1/2 hp Motors, 120 VAC, 8.4 amps.

Maximum Gate Length – 37 feet

Maximum Gate Weight – 2000 lbs.

SL-3000-UL

1/2 hp Motor, 120 VAC, 4 amp.

Maximum Gate Length – 37 feet

Maximum Gate Weight – 1000 lbs.

Be sure to read and follow all Elite and UL instructions before installing and operating any Elite products. Elite Access Systems, Inc. is not responsible for improper installations or failure to comply with local building codes.

It is highly recommended installing over-travel stops at both ends of the gate rail in any type of installation, to prevent derailing.

FRONT INSTALLATION

Reason: Cost effecient

Over-Travel Stop

Over-Travel Stop

REAR INSTALLATION

Reason: Chain is not visible

Over-Travel Stop

Idler Wheel must have Safety Cover

CEILING MOUNT UNDERGROUND

Reason: Space effecient/chain is not visible

Over-Travel Stop

FRONT INSTALLATION

Weld front bracket with gate in open position.

Weld rear bracket with gate in closed position.

REAR INSTALLATION

Cut the cover 17 1/2 inches high.

Make sure the idler wheel has a safety cover.

REAR INSTALLATION COVER MODIFICATION

Cut the chain access slot on the one side of the cover to the exact specifications.

2"

Important:

For safe operation of the gate opener do not cut the slots any wider or longer than shown.

DO NOT modify the housing in any way other than specified.

17.5"

C O N C R E T E P A D A N D G A T E A T T A C H M E N T

Follow gate manufacturers specifications and local building codes for setting post.

Above

Ground

6"

Below

Ground

24"

24"

Concrete (Reinforced Recommended)

Suggested installation for dirt ground.

The measurements depend on the type of ground (ie., asphalt, cement, dirt)

12"

12"

10"

8"

24"

Red Head Fastener

1/2" x 3 1/2"

Cover over

Wheel

Rear Installation

Over-Travel

Stops on Both

Ends of Rail

Front Installation

Over-Travel

Stops on

Both Ends of Rail

G A T E A N D O P E R A T O R D I S T A N C E

4"

Minimum

Distance

Between Gate and Sprocket

Correct Installation Incorrect Installation

C H O O S I N G M O V E M E N T D I R E C T I O N

Open to the Left

MER

Omni Control Board

60

CENTER SAFETY EXIT

W4

GB A

MS LINK

DC-BACKUP

SYSTEM ON

SENSORS

13 13

TIMER

60

ON

3

13

OFF

OPEN LEFT OPEN RIGHT

POWER

OVERLOAD

FIRE

DEPT.

STRIKE

OPEN

RADIO

RECEIVER

GATE

LOCKED

EXIT

LOOP

SAFETY

LOOP

CENTER

LOOP

RESET

MOTOR

3

OFF

OPEN LEFT

ON

1

OPEN RIGHT

RADIO

Open to the Right

MER

60

OFF

OPEN LEFT

3

ON

1

OPEN RIGHT

Omni Control Board

CENTER SAFETY EXIT

W4

GB A

MS LINK

DC-BACKUP

TIMER

13 13

OFF

60

ON

3

13

OPEN LEFT OPEN RIGHT

POWER

OVERLOAD

FIRE

DEPT.

STRIKE

OPEN

RADIO

RECEIVER

GATE

LOCKED

EXIT

LOOP

SAFETY

LOOP

CENTER

LOOP

RESET

MOTOR

RADIO

H O W T O C O N N E C T P O W E R

Do Not Use This Outlet Unless You Are

An Authorized Service Technician

Suggestion:

Seal all open holes of electronic box with sealant when finished wiring.

Minimum:

15-Amp

Breaker Switch

Per Operator

Required

White Wires

(Neutral)

Black Wires

(120 VAC)

Use U.L. Listed Conduit for Supplying Power to the Unit

Green Wires (Ground)

WIRE GUAGE REQUIREMENT FOR 120 VAC POWER SUPPLY: 1/2 HP AND DUAL MOTOR ONLY

16 Gauge 14 Gauge 12 Gauge 10 Gauge 8 Gauge 4 Gauge

150 Feet 250 Feet 400 Feet 650 Feet 1000 Feet 2200 Feet

Caution: ELITE ACCESS SYSTEMS, INC. is not responsible for conflicts between the information listed in the above chart and the requirements of your local building codes. The information is for suggested use only. Check your local codes before installation.

Gate Operator MUST be properly grounded.

A D J U S T I N G G A T E T R A V E L I N G D I S T A N C E

Nut

Push Plate

Plate

Before Adjusting, Do the Following:

1.Turn the Power OFF!

2. Push the plate inward. Roll the

nut to the direction desired.

Each notch indicates an estimated 1 inch of gate travel

3. Place the plate back in the notch.

4. Turn the machine off.

5. If you need more adjusting,

repeat the process.

Adjusted by Qualified Service Personnel

CENTER SAFETY EXIT

Maximum

Sensitivity

1 3

W4

G B

MS LINK

A

DC-BACKUP

SYSTEM ON

SENSORS

1 3 1 3

TIMER

OFF

OPEN LEFT

60 3

ON

1

OPEN RIGHT

3

FIRE

DEPT.

STRIKE

OPEN

RADIO

RECEIVER

GATE

LOCKED

EXIT

LOOP

SAFETY

LOOP

CENTER

LOOP

RESET

MOTOR

POWER

OVERLOAD

Minimum

Sensitivity

DO NOT

Touch Alarm Sensor

The level of sensitivity has to do with the weight of the gate and the condition of installation.

Too sensitive = if the gate stops or reverses by itself.

Not sensitive enough = if the gate hits an object and does not stop or reverse.

CAUTION:

If the power supply to the gate operator is less than 99 volts, adjust the alarm by turning the alarm adjustment counter-clockwise enough to actuate the alarm when obstructed but not sensitive enough for false triggering to occur.

A D J U S T A B L E T I M E R

Timer ON

TIMER

60 3

Set Timer

1 to 60 seconds

CENTER SAFETY EXIT

OFF

OPEN LEFT

3

ON

1

OPEN RIGHT

DC-BACKUP

W4

G B

MS LINK

A

SYSTEM ON

SENSORS

TIMER

1 3 1 3

OFF

OPEN LEFT

60

ON

1 3

OPEN RIGHT

3

FIRE

DEPT.

STRIKE

OPEN

RADIO

RECEIVER

EXIT

LOOP

SAFETY

LOOP

CENTER

LOOP

GATE

LOCKED

RESET

MOTOR

POWER

OVERLOAD TIMER

OFF

Timer can be set from 1 to 60 seconds ( Timer ON ), or for push open/push close type operation ( Timer OFF ).

OPEN LEFT

60

ON

1 3

3

OPEN RIGHT

Timer OFF

M A S T E R A N D S L A V E W I T H T I M E R O N

Master and Slave Boards are Interchangeable Master Omni Board Primary Control for System

Use Low Voltage Wires to Connect Gate Operators Together

Caution:

115 volts per operator required

Master Omni Board

TIMER

60 3

CENTER SAFETY EXIT

OFF

OPEN LEFT

ON

1

OPEN RIGHT

3

Adjust Time Desired

0 to 60 seconds

Slave Omni Board

W4

G B

MS LINK

A

W4

G B

MS LINK

A

DC-BACKUP

SYSTEM ON

SENSORS

TIMER

1 3 1 3

OFF

OPEN LEFT

60 3

ON

1

OPEN RIGHT

3

FIRE

DEPT.

STRIKE

OPEN

RADIO

RECEIVER

GATE

LOCKED

EXIT

LOOP

SAFETY

LOOP

CENTER

LOOP

RESET

MOTOR

POWER

OVERLOAD

Master Timer “ON”

CENTER SAFETY EXIT

W4

G B A

MS LINK

DC-BACKUP

SYSTEM ON

SENSORS

1 3 1 3

TIMER

OFF

OPEN LEFT

60 3

ON

1 3

OPEN RIGHT

FIRE

DEPT.

STRIKE

OPEN

RADIO

RECEIVER

GATE

LOCKED

EXIT

LOOP

SAFETY

LOOP

CENTER

LOOP

RESET

MOTOR

POWER

OVERLOAD

Use Shielded

Twisted Wires to Connect Gate

Operators Together

W4

G B

MS LINK

A

MAXIMUM

Counterclockwise

Setting

TIMER

60 3

1. Connect

G

from master to

G

of slave.

(G is the shield or a ground wire)

2. Connect

B

from master to

B

of slave.

3. Connect

A

from master to

A

of slave.

OFF

OPEN LEFT

ON

1 3

OPEN RIGHT

4. Turn timers on BOTH Omni boards to the “

ON

” position

5. Turn the SLAVE Timer adjustment all the way Counterclockwise

Slave Timer “ON”

6. Use MASTER timer ONLY to select the desired time

M A S T E R A N D S L A V E W I T H T I M E R O F F

Use Low Voltage Wires to Connect Gate Operators Together

Master Omni Board

Caution:

115 volts per operator required

CENTER SAFETY EXIT

TIMER

60

OFF

OPEN LEFT

ON

1

OPEN RIGHT

3

3

Slave Omni Board

W4

G B

MS LINK

A

DC-BACKUP

SYSTEM ON

SENSORS

1 3 1 3

TIMER

60 3

OFF

OPEN LEFT

ON

1

OPEN RIGHT

3

FIRE

DEPT.

STRIKE

OPEN

RADIO

RECEIVER

EXIT

LOOP

SAFETY

LOOP

CENTER

LOOP

GATE

LOCKED

RESET

MOTOR

POWER

OVERLOAD

CENTER SAFETY EXIT

W4

G B A

MS LINK

DC-BACKUP

SYSTEM ON

SENSORS

1 3 1 3

TIMER

OFF

OPEN LEFT

60 3

ON

1 3

OPEN RIGHT

FIRE

DEPT.

STRIKE

OPEN

RADIO

RECEIVER

GATE

LOCKED

EXIT

LOOP

SAFETY

LOOP

CENTER

LOOP

RESET

MOTOR

POWER

OVERLOAD

W4

G B

MS LINK

A

Use Shielded

Twisted Wires to Connect Gate

Operators Together

W4

G B

MS LINK

A

1. Connect

G

from master to

G

of slave.

(G is the shield or a ground wire)

2. Connect

B

from master to

B

of slave.

3. Connect

A

from master to

A

of slave.

4. Turn timers on BOTH Omni boards to the “

OFF

” position

TIMER

60

OFF

OPEN LEFT

ON

1

OPEN RIGHT

3

3

P A R T I A L M A S T E R / I N D I V I D U A L C O N T R O L

IN ORDER FOR THE FOLLOWING OPERATION TO OCCUR, FOLLOW THE INSTRUCTIONS.

EXAMPLE: There is a double gate, the entry gate is to be opened with a radio transmitter and the exit gate with a free exit loop. Only one safety loop system is to open both gates, and a fire department switch should open both gates at the same time.

1. Connect the radio receiver to entry gate only.

2. Connect the exit loop to exit gate only.

3. Connect the safety loop to both entry and exit gates.

4. Connect the fire department switch to both entry and exit gates.

S O L E N O I D / M A G L O C K J 3 C O N N E C T I O N

Wire Harness

J3

2 1

3 Normally Closed

CENTER SAFETY EXIT

W4

G B A

MS LINK

DC-BACKUP

SYSTEM ON

SENSORS

1 3 1 3

TIMER

60 3

OFF

OPEN LEFT

ON

1 3

OPEN RIGHT

POWER

OVERLOAD

FIRE

DEPT.

STRIKE

OPEN

RADIO

RECEIVER

GATE

LOCKED

EXIT

LOOP

SAFETY

LOOP

CENTER

LOOP

RESET

MOTOR

8

10

7

9

Common

Normally Open

Connection of a Solenoid or Magnetic Lock can be made using the J3 plug and three wires supplied with the unit.

Solenoid Lock

Solenoid Lock

8

10

2

J3

1

3

7

9

#3 Normally Closed

#7 Common

Insert 2 supplied wires into J3 plug (#3 and #7)

(Motor Harness)

Ground

Wire Nut

Power

Ground

Plug-In

Transformer

Magnetic Lock

8

10

2

J3

1

3

7

9

Insert 2 supplied wires into J3 plug (#7 and #8)

(Motor Harness)

#7 Common

Ground

Wire Nut

Magnetic

Lock

Plug-In

Transformer

#8 Normally Open

Power

Ground

QCC socket with QCC access ID inserted

QCC “Mode of Operation” switch

DC-BACKUP

OPEN

QCC

A B

STOP CLOSE MAGLOCK A L A R M ARMED M / S L I N K

W4

OPEN

G B A

A

QCC

B

M A G L O C K A L A R M A R M E D M/S LINK

SYSTEM ON

SENSORS

1 3 1 3

TIMER

OFF

OPEN LEFT

60

ON

1 3

OPEN RIGHT

3

POWER

OVERLOAD

FIRE

DEPT.

EXIT

LOOP

STRIKE

OPEN

RADIO

RECEIVER

SAFETY

LOOP

CENTER

LOOP

GATE

LOCKED

1

RESET

MOTOR

2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

QCC is designed for slide gate operators only!

1

&

2 – Open Command

Omni Option Board

Elite Part #

O-OMNI EXB

10

&

11 – Burglar Alarm Output

3

&

4 – Stop Command 12

&

13 – Burglar Alarm Input

5

&

6 – Close Command

7 – Common

8 – Normally Closed

9 – Normally Open

Maglock or

Solenoid

14 – Ground

15 – B

16 – A

Master/Slave

RS485

Q C C ( Q U I C K C L O S E C U R C U I T )

QCC Access ID (Top Positive)

QCC Access Socket

Mode of Operation Switch

QCC Access ID

Elite Part #

O-QCC OMNI

Omni Option Board

Elite Part #

O-OMNI EXB

the QCC can operate in two different modes. The mode of operation will depend on the switch on the Omni option board.

Mode A

(switch off) If the gate is closing while a car is driving over the safety loop detector, the QCC will stop the gate for a second then open the gate while the car is over the safety loop detector. As soon as the car leaves the safety loop, the QCC will resume closing the gate.

Mode B

(switch on) If the gate is closing, and a vehicle drives over the safety loop, the QCC will stop the gate. It will not open the gate. After the vehicle leaves the safety loop, the QCC will close the gate.

CENTER SAFETY EXIT

DC-BACKUP

W4

QCC

G B A

A B

MAGLOCKALARMARMED M/S LINK

Omni Option Board

Elite Part #

O-OMNI EXB

1 3 1 3

TIMER

60 3

OFF

OPEN LEFT

ON

1 3

OPEN RIGHT

FIRE

DEPT.

STRIKE

OPEN

RADIO

RECEIVER

GATE

LOCKED

EXIT

LOOP

SAFETY

LOOP

CENTER

LOOP

RESET

MOTOR

POWER

OVERLOAD

SE MAGLOCK AL

7 – Common

8 – Normally Closed

9 – Normally Open

Solenoid Lock

7 8 9

Ground

Plug-In

Transformer

Wire Nut

Power

Ground

SE MAGLOCK AL

7 – Common

8 – Normally Closed

9 – Normally Open

CENTER SAFETY EXIT

W4

QCC

G B A

A B

MAGLOCKALARMARMED M/S LINK

Omni Option Board

Elite Part #

O-OMNI EXB

DC-BACKUP

1 3 1 3

TIMER

60 3

OFF

OPEN LEFT

ON

1 3

OPEN RIGHT

FIRE

DEPT.

STRIKE

OPEN

RADIO

RECEIVER

GATE

LOCKED

EXIT

LOOP

SAFETY

LOOP

CENTER

LOOP

RESET

MOTOR

POWER

OVERLOAD

Magnetic

Lock

7 8 9

Wire Nut

Ground

Plug-In

Transformer

Power

Ground

M A S T E R / S L A V E W I T H O P T I O N A L B O A R D

CENTER SAFETY EXIT

ED

M/S LINK

G B A

W4

QCC

G B A

A B

MAGLOCKALARM ARMED M/S LINK

DC-BACKUP

SYSTEM ON

SENSORS

1 3 1 3

TIMER

60 3

OFF

OPEN LEFT

ON

1 3

OPEN RIGHT

FIRE

DEPT.

STRIKE

OPEN

RADIO

RECEIVER

GATE

LOCKED

EXIT

LOOP

SAFETY

LOOP

CENTER

LOOP

RESET

MOTOR

POWER

OVERLOAD

Use this socket (M/S LINK) if the Omni option board is being used, and

Master/Slave option is needed.

H O U S E A L A R M / P R O X I M I T Y S W I T C H

QCC

A B

OPEN STOP CLOSE MAGLOCKALARM ARMED M / S L I N K

Omni Option Board

Elite Part #

O-OMNI EXB

10 11 12 13

CENTER SAFETY EXIT

DC-BACKUP

W4

A

MS LINK

QCC

AB

SYSTEM ON

SENSORS

1 3 1 3

TIMER

OFF

OPEN LEFT

60 3

ON

1 3

OPEN RIGHT

FIRE

DEPT.

STRIKE

OPEN

RADIO

RECEIVER

GATE

LOCKED

EXIT

LOOP

SAFETY

LOOP

CENTER

LOOP

RESET

MOTOR

POWER

OVERLOAD

OmniControl Board

Use Low Voltage

Wire 20 AWG

12VDC

House Alarm System

Dry Contact

House Alarm

2"

Max.

Proximity Switch

Elite Part #

A PRS

CENTER SAFETY EXIT

W4

G B

MS LINK

A

DC-BACKUP

SYSTEM ON

SENSORS

TIMER

1 3 1 3

OFF

OPEN LEFT

60 3

ON

1 3

OPEN RIGHT

FIRE

DEPT.

STRIKE

OPEN

RADIO

RECEIVER

EXIT

LOOP

SAFETY

LOOP

CENTER

LOOP

GATE

LOCKED

RESET

MOTOR

POWER

OVERLOAD

CAUTION:

Use different frequencies for every single loop detector. Turn off gate operator

(from switch on electrical box) during installation.

Wire-Loop “Safety Loop”

Wire-Loop “Exit Loop”

Elite Loop detectors needed to do this function. Elite Part #

A ELD

Omni Option Board Needed

OPEN STOP CLOSE

CENTER SAFETY EXIT

1 2 3 4 5 6

W4

Three Push Button System

(OPEN-STOP-CLOSE)

Step 1 - Cut off jumper wire #W4.

Step 2 - Install Omni option board.

Step 3 - Connect OPEN push button to #

1

&

2

.

Step 4 - Connect STOP push button to #

3

&

4

.

Step 5 - Connect CLOSE push button to #

5

&

6

.

DC-BACKUP

QCC

W4

OPEN

G B A

CLOSE

A B

MAGLOCK A L A R M A R M E D M / S L I N K

SYSTEM ON

SENSORS

TIMER

1 3 1 3

OFF

OPEN LEFT

60 3

ON

1

OPEN RIGHT

3

FIRE

DEPT.

STRIKE

OPEN

RADIO

RECEIVER

EXIT

LOOP

SAFETY

LOOP

CENTER

LOOP

GATE

LOCKED

RESET

MOTOR

POWER

OVERLOAD

Note:

If using the Master/Slave board configuration, unplug the Master/Slave link plug on main board and connect it into the

Omni option board M/S link socket.

CAUTION:

Make sure each push button is dry contact and there are no jumper wires between them.

T E R M I N A L I N P U T C O N N E C T I O N S

Output Power

Terminal 8 = Ground (-)

Terminal 10 = 24 DC (+)

1 3 1 3

OFF

OPEN LEFT

ON

1 3

OPEN RIGHT

MADE IN USA

FIRE

DEPT.

STRIKE

OPEN

RADIO

RECEIVER

GATE

LOCKED

EXIT

LOOP

SAFETY

LOOP

CENTER

LOOP

RESET

MOTOR

1 2 3 4 5 6 7 8 9 10

Fire or

Any Key

Switch

Card

Reader

Radio Receiver

Output Power

Terminal 8 = 24 Volt

Terminal 9 = Relay

Terminal 10 = Radio Power

External “Exit” Loop Detector

Push

Button

HELP

1

4

7

2

5

8

0

3

6

9

Phone

Entry

Photo Cell

External “Safety” Loop Detector

S A F E T Y L O O P S Y S T E M

The safety loop prevents the gate from closing while a car or any other object remains in the gates pathway.

4'

4'

4'

Twisted

Wires

From Loop

Cut

4'

4'

1/4"

4'

Typical

Fill Loop Cuts with Proper

Sealer

Three Wire Layers in Loop Cut

1 1/2"

E X I T L O O P S Y S T E M

The exit loop automatically allows the gate to open when a car is exiting.

Twisted

Wires

From Loop

Cut

4'

4'

4'

4'

4'

1/4"

4'

Typical

Fill Loop Cuts with Proper

Sealer

Three Wire Layers in Loop Cut

1 1/2"

E M E R G E N C Y R E L E A S E

Standard

Manual

Crank

Cover

1. Turn the power OFF!

2. Make sure the crank tool fits the crank input, as shown above: Turn the crank to open the gate. To speed up the process you may use a wireless power drill (6 ”/sec).

Option 1:

Elite Part #

CP-17

Pull firmly on the “T”

Handle to release the chain.

Turn the power OFF

to the gate operator and unlock the fire box.

The chain is held in place by a spring loaded pin.

Option 2:

Elite Part #

DC-1000U-SL

Condition A:

In case of power failure the gate opens automatically one time and stays open. when power is restored the operator returns to normal condition.

Power Back-Up

Condition B:

In case of power failure the gate will not open automatically until activated by a key switch or push button.

for More Details contact your Local Dealer

R E P L A C I N G T H E C O N T R O L B O A R D

Disconnect 2 wire harnesses from OmniControl board. Unscrew nuts to remove board.

A U D I O A L A R M

When one of the following events happens

Twice Consecutively, an Alarm will Sound!

To turn alarm off, cut the power or use the optional stop button.

Refer to “Stop Button Alarm”

1

The gate is too heavy.

2 Objects are on the gate's track such as mud, rocks dirt, etc.

3 The gate is hitting a wall or any other object.

4

The gate has one or more broken wheels.

5 A moving object has hit the gate and the gate is off the track.

Refer to the Troubleshooting Table

S T O P B U T T O N A L A R M S H U T - O F F

Omni Option Board Needed

OPEN

STOP

CLOSE

#3

Stop

Button

1 2 3 4 5 6

#4

Install the stop button in a secure accessible place.

CENTER SAFETY EXIT

W4

QCC

G B A

A B

DC-BACKUP

SYSTEM ON

SENSORS

1 3 1 3

TIMER

60 3

OFF

OPEN LEFT

ON

1 3

OPEN RIGHT

FIRE

DEPT.

STRIKE

OPEN

RADIO

RECEIVER

GATE

LOCKED

EXIT

LOOP

SAFETY

LOOP

CENTER

LOOP

RESET

MOTOR

POWER

OVERLOAD

W4

Cut off jumper wire #W4.

This is an important command required to stop the audio alarm in case it has been triggered. Otherwise the alarm will sound for 5 minutes and reset itself.

Use STOP Button:

•To stop the movement of the gate in case of potential entrapment.

•To reset the audio alarm, (check for obstructions).

•To stop the gate operator while traveling.

When using the Omni option board, use the

STOP

input to connect the stop button.

S E C O N D A R Y E N T R A P M E N T P R O T E C T I O N

Wiring Installation

OmniControl Board

P

CENTER SAFETY EXIT

W4

G B

MS LINK

A

DC-BACKUP

SYSTEM ON

SENSORS

TIMER

1 3 1 3

OFF

OPEN LEFT

60 3

ON

1

OPEN RIGHT

3

FIRE

DEPT.

EXIT

LOOP

STRIKE

OPEN

RADIO

RECEIVER

SAFETY

LOOP

CENTER

LOOP

GATE

LOCKED

RESET

MOTOR

POWER

OVERLOAD

Edge Sensor

Mounting Installation

Drill 1/2" Hole if necessary to Feed Wire Through

2 Wires to

Gate Operator

Omni Control

Board

Use #10 Screws as Necessary to Mount Edge

Black Mounting Tab

All of the installed edge sensors are connected in parallel at the sensor input terminals on the Omni control board.

Top View of Gate Operation Recommended Installation Locations

Recommended Edge Sensor Locations

Wall

Wall

Gate

Edge Sensor

Recommended

Location

Install edge sensors appropriately at recommended locations to insure sufficient entrapment protection for your installation to prevent injury.

SL

Operator

Edge Sensor

Recommended

Location

If you are going to use a contact sensor as a secondary entrapment protection you should use a recognized component to comply with the revised UL 325 for use in class I or class II gate operator.

Electric Sensing Edge, Miller Edge Models: or MGS20

T R O U B L E S H O O T I N G L E D I N F O R M A T I O N

Resetting Motor

Reset Motor LED Light is “ ON ”

Motor Reset Button

Press firmly to reset thermal breaker on the motor.

Gate Will Not Close!

Gate Will Not Open!

Symptom:

The radio receiver LED on the control board remains “

ON

” when using the remote control.

Possible Solutions:

Stuck remote control button. The radio receiver has malfunctioned in the

ON

” position.

Symptom:

The radio receiver LED on the control board remains “OFF” when using the remote control.

Possible Solutions:

Dead battery in the remote control. Remote control code switches are different from radio receiver code switches. The radio receiver has malfunctioned in the “OFF” position.

T R O U B L E S H O O T I N G T A B L E

CONDITION POSSIBLE CAUSES SOLUTIONS

OVERLOAD LED ON

And

POWER LED OFF

OVERLOAD LED ON

And

POWER LED ON

1.Short circuit at terminals 8 and 10

2.Short circuit at any of the loop detectors in the board

3.Short circuit in the control board

1.Excessive current draw at terminal 10

2.Over-voltage at the 120 VAC line input

1.Remove the short circuit condition at

the terminals

2.Remove the defective loop detector

3.Send the board to repair

1.Reduce the accessories load from

terminal 10

2.Verify your electrical power

SYSTEM ON LED

FLASHING

1.One limit switch is faulty

2.Motor thermal fuse has poped-out

1.Test the limit switches and wire

connections, fix the fault

2.Reset the motor

REVERSE SENSOR LED

ON

1.Gate has encountered and obstruction 1.Remove the obstruction during traveling

2.Reverse sensor is extra sensitive

2.Turn the reverse sensor switch counter clockwise a little more and try again

ALARM SENSOR

LED ON

1.Gate encountered an obstruction during traveling

2.Alarm sensor is extra sensitive

1.Remove the obstruction

2.Turn the alarm sensor switch counter clockwise a little more and try again

ALARM SENSOR

LED ON

1.Gate encountered and obstruction during traveling

2.Alarm sensor is extra sensitive

1.Remove the obstruction

2.Turn the alarm sensor switch counter clockwise a little more and try again

COMMAND PROCESSED

LED ON

1.There is a command hold active 1.This is a normal response of the gate

operator. It does not represent necessarily

that there is a problem.

TIMER LED BLINKING

And COMMAND

PROCESSED

LED BLINKING

1.There is a command holding the gate open

TIMER LED BLINKING,

COMMAND PROCESSED

LED BLINKING And

REVERSE SENSOR

LED ON

1.Gate has reopened because it encountered an obstruction while closing.

1. This is a normal response of the gate operator.

It does not represent necessarily that there is a

problem. Check inputs for command.

1.Any re-new command will resume normal

operation. Check for obstructions.

AUDIO ALARM ON

ANY “ LOOP LED ” ON

And

NO VEHICLE ON THE

SENSING AREA

1.Gate has encountered two consecutive obstructions while trying to close or open

1.Any re-new command will resume normal

operation but not a radio command. Check for obstructions.

2.You can stop the alarm by using the stop button.

1.The loop detector needs to be reset.

2.The wire loop has been disrupted

3.The loop detector needs to work in a different frequency

4.The loop detector is too sensitive

1.Reset the loop detector (If you use Elite

Plug-in Loop detectors, change the setting

for sensitivity and come back to your original

setting).

2.Verify and correct connections

3.Set a different working frequency

4.Decrease the sensitivity of the loop detector

S L - 3 0 0 0 P A R T S

*Q029

Q031

Limit Switch

Assembly

Q010

*Q032

Q051

*Q101

Q033

Power Back-Up

SL

Q164

SL DM

Q065

O-DC

Q123

Q209

Q143

O-DC-SL

O-DC-SL DM

Q177

Q024

Q023

Q030

Q254

Electronic Box

Assembly

Q421

Q028

Q237

Q039

Q025

Q027

Q021

Q020

Q420

Q112

Q402 1/2 HP

Q403 1 HP

Q014

Q016

Q015

A H-110

#41

*Q013

A H-113

Q018

Q400

Q404

Q401

Q408

A H-111

#40

A H-125

*Q003

*Q004

Q005

A ELD

Q006

O-OMNI EXB

Q009

O-QCC OMNI

Note: *Sold Individually, 2 Shown.

For part names, refer to parts list

S L - 3 0 0 0 P A R T S L I S T

Idler Sprocket Assembly

Q013

Limit Switch Assembly

Q024

Q010 - Limited Switch Box Cover

Q023 - Limit Switch Box

Q031 - Limit Switch / Shaft

Q032 - Limit Switch Adjustment Nuts

Q051 - Limit Switch / Shaft Bearing

Q101 - Limit Switch Bearing Holder

Power Back-Up Unit

O-DC-SL

O-DC-SL DM

Q065 - Drive Belt (DM)

Q123 - Back-Up Motor DC 12V

Q143 - Chassis DC Back-Up

Q164 - Drive Belt

Q177 - Wire Harness DC-1000

Q209 - Pulley DC-1000 1/2 ID

Electronic Box Assembly

Q402 1/2 HP Q403 1 HP

Flexible Assembly for 1/2 Horse Motor

Q420

Wire Harness and Conduit

Flexible Assembly for Dual Motor

Q421

Wire Harness and Conduit

Muliple Parts “Q” Numbers

#OmniControl Board Accessories

AH-110 - Gate Chain No.41 (10 ft)

A H-111 - Gate Chain No.40 (10 ft)

A H-113 - Master Link, Nickel Plated

A H-125 - Master Link

Q003 - Chain Bolt

Q004 - Chain Bracket

Q005 - SL-3000 Chassis

Q006 - PC Board Nuts (1 Set)

Q009 - Electronic Access Panel

Q014 - Drive Sprocket

Q015 - Gear Reducer

Q016 - Limited Switch Drive Sprocket

Q018 - 1/2 HP Electric Motor

Q020 - Drive Belt

Q021 - Gear Pulley

Q025 - Motor Pulley

Q027 - Motor Capacitor

Q028 - Manual Crank

Q029 - Limit Switch

Q030 - Limit Switch / Chain

Q033 - Limit Switch Sprocket

Q039 - Drive Belt, DM and 1 HP

Q112 - Wire Harness-B Terminal Block

Q237 - Crank Input

Q254 - Cover HD Polyethylene

Q400 - OMNI Main PCB

Q401 - OMNI 1 Horsepower Board #

Q404 - OMNI Alarm

Q408 - Electronic Power Strip

A ELD - Loop Detector #

O-OMNI EXB - OMNI Option Board #

O-QCC OMNI - QCC Access ID #

M A I N T E N A N C E

2. Make sure the gate track is clear of dirt, rocks or other substances.

3. Make sure the wheels are operating smoothly on the track.

4. If you hear an Alarm,

Refer to “Audio Alarm”.

5. Clean the cover on a regular basis.

6. For part illustrations,

Refer to “SL-3000 Parts”.

If you need further assistance, please contact your local service company.

Three Push

Button

External “Safety” Loop Detectors

Remote

Control

System

Key Switch

Card Reader

Photo Electric Eye

Outdoor Digital Lock Key Station

Outdoor Digital Lock with Intercom

Indoor Intercom

Speaker

Outdoor Intercom

Speaker

advertisement

Key Features

  • Suitable for Class II and III gate applications
  • Advanced safety features such as non-contact and contact sensors
  • Powerful motor and durable construction

Related manuals

Frequently Answers and Questions

What is the intended use of the Elite SL-3000-UL SERIES?
The Elite SL-3000-UL SERIES is intended for use in commercial applications, such as multi-family housing units, hotels, and retail stores.
What safety features does the SL-3000-UL SERIES have?
The SL-3000-UL SERIES has advanced safety features such as non-contact and contact sensors, which help to prevent accidents and injuries.
What type of gate can the SL-3000-UL SERIES be used with?
The SL-3000-UL SERIES is designed for use with vehicular horizontal slide gates.