INSTRUCTIONS: Class II Electronic Transformer

CAUTION – TO REDUCE RISK OF FIRE AND ELECTRICAL SHOCK

Always turn off power at main switch prior to installation.

MAX LOAD

MIN LOAD

INPUT VOLTAGE

INPUT CURRENT

OUTPUT VOLTAGE

CASE TEMP

AMBIENT TEMP

60W

20W

120V

0.5A

11.6V

60ºC ( 140

°

F)

-20ºC TO 50ºC (-4

°

F TO 122

°

F)

INSTALLATION:

• Plugs in to standard 120 volt 3 prong grounded outlets.

• Transformers must be installed away from heat sources.

• Regular incandescent dimmer switches may be wired to the primary input wires.

Electronic low voltage dimmers are also suitable.

WIRE SIZE

18 GAUGE

16 GAUGE

14 GAUGE

12 GAUGE

MAXIMUM LENGTH / VOLTAGE DROP GUIDELINE

35 WATT 50 WATT

10 FT

14 FT

9 FT

13 FT

21 FT

28 FT

19 FT

25 FT

60 WATT

8 FT

11 FT

15 FT

21 FT

8/01/02 REV 1