- Home
- Domestic appliances
- Large home appliances
- Water heaters & boilers
- Morco
- GB24 Series II
- Owner's manual
advertisement
![Morco GB24 Series II Owner Manual | Manualzz Morco GB24 Series II Owner Manual | Manualzz](http://s1.manualzz.com/store/data/007105791_1-80cbaf3dd75d51bb143872dca58201d4-360x466.png)
GB24 & GB30
Series II
User & Installation Instructions
off mode reset min max preheat min e max status burner preheat
GB24
Series II
BOILER OUTPUT
To Domestic Hot Water:
GB24/30 Minimum 8.0 kW (27,296 Btu/h)
GB24 Maximum 24.2 kW (82,570 Btu/h)
GB30 Maximum 30.3 kW (103,384 Btu/h)
To Central Heating:
GB24/30 Minimum 8.0 kW (27,296 Btu/h)
GB24/30 Maximum 24.2 kW (82,570 Btu/h)
Morco House, Riverview Road, Beverley, East Yorkshire, HU17 0LD
Morco Products Ltd
Tel: 01482 325456 Fax: 01482 212869
Website: www.morcoproducts.co.uk
UIN 211292 A01
October 2014
Morco GB24 & GB30 Series II
Combination Boiler
Destination Country:
BE = Belgium
CH = Switzerland
CZ = Czech Republic
ES = Spain
FR = France
GB = UK
GR = Greece
IE = Ireland
IT = Italy
NL = Netherlands
PL = Poland
PT = Portugal
SI = Slovenia
2
CoNTENTS
5
6
7
SECTIoN
1
2
3
4
PAGE
Users Instructions ..........................................................................................................................................4
General Specifications ...................................................................................................................................8
Technical Data ...............................................................................................................................................10
General Installation Requirements.................................................................................................................12
Installation Instructions ..................................................................................................................................14
Commissioning Instructions ...........................................................................................................................23
Routine Servicing Instructions .......................................................................................................................25
8
9
10
Fact Sheets ....................................................................................................................................................31
Fault Codes....................................................................................................................................................32
Combustion Ratio Check ...............................................................................................................................34
11 Warranty ........................................................................................................................................................36
3
SECTION 1 - USERS INSTRUCTIONS
FoR ANy qUERIES PLEASE RING THE
MoRCo CoNSUMER HELPLINE : 01482 325456
NoTE. BoILER RESET PRoCEDURE -
To reset boiler, turn mode control knob to reset position and immediately turn knob back to required setting.
Introduction
The Morco GB Series II is a wall mounted, room sealed, condensing combination boiler, featuring full sequence automatic spark ignition and fan assisted combustion.
Due to the high efficiency of the boiler, condensate is produced from the flue gases and this is drained to a suitable disposal point through a plastic waste pipe at the base of the boiler. A condensate ‘plume’ will also be visible at the flue terminal.
The Morco GB Series II is a combination boiler providing both central heating and instantaneous domestic hot water.
Minimum Clearances
Clearances of 165mm (6 1/2 ”) above, 100mm (4”) below,
2.5mm (1/8”) at the sides and 450mm (17 3/4”) at the front of the boiler casing must be allowed for servicing.
Bottom clearance
Bottom clearance after installation can be reduced to 5mm.
This must be obtained with an easily removable panel, to enable the consumer to view the system pressure gauge, and to provide the 100mm clearance required for servicing.
Safety
Current Gas Safety (Installation & Use)
Regulations or rules in force.
In your own interest, and that of safety, it is the law that this boiler must be installed by a Gas Safe Registered engineer, in accordance with the above regulations.
In other countries the installation must be carried out by a qualified and competent Gas Installer. In the approved country the boiler is installed, this must be in accordance with their current rules in force.
It is essential that the instructions in this booklet are strictly followed, for safe and economical operation of the boiler.
Electricity Supply
This appliance must be earthed.
Supply: 230 V ~ 50 Hz. The fusing should be 3A.
To light the boiler. Refer to Boiler Controls
1. CheCK ThAT The eleCTRICITy SUPPly TO BOIleR IS
OFF.
2. Set the mode knob control (A) to ‘Off’.
3. Set the Domestic hot Water temperature control (B) and
Central heating temperature control (C) to ‘max’.
4. ensure that all hot water taps are turned off.
5. Switch ON electricity to the boiler and check that all controls, e.g. timer and room thermostat, are ON (refer to mechanical timer instructions - Page 6).
6. Set the mode knob control to winter ( ).
If there is a central heating demand the boiler will commence the ignition sequence.
Note. In normal operation the boiler status display (D) will
show codes:
Important Notes
This appliance must not be operated without the casing correctly fitted and forming an adequate seal.
If the boiler is installed in a compartment then the compartment mUST NOT be used for storage purposes.
If it is known or suspected that a fault exists on the boiler then it mUST NOT Be USeD until the fault has been corrected by a Gas
Safe Registered Engineer or in other countries a qualified and competent Gas Installer.
Under NO circumstances should any of the sealed components on this appliance be used incorrectly or tampered with.
This appliance can be used by children from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
Children should be supervised to ensure that they do not play with the appliance.
In cases of repeated or continuous shutdown a Gas Safe Registered
Engineer, or in other countries a qualified and competent Gas Installer, should be called to investigate and rectify the condition causing this and carry out an operational test. Only the manufacturers parts are to be used for replacement.
Standby - no demand for heat.
Ch being supplied.
DhW being supplied.
DhW preheat.
During normal operation the burner on indicator (e) will remain illuminated when the burner is lit.
Note : If the boiler fails to light after five attempts the fault code will be displayed.
RESET PRoCEDURE
To reset boiler, turn the mode control knob (A) to reset position and immediately turn knob back to required setting. The boiler will repeat the ignition sequence if a heat demand is present.
If the boiler still fails to light consult a Gas Safe Registered
Engineer, or in other countries a qualified and competent Gas
Installer.
4
Operation
SECTION 1 - USERS INSTRUCTIONS
Winter conditions - i.e. CH and DHW required.
ensure the mode knob control (A) is set to winter ( )
The boiler will fire and supply heat to the radiators but will give priority to DhW on demand.
Summer conditions - i.e. DHW only required.
Set the mode knob control to Summer ( ).
Set the Ch external controls to OFF.
Note
. The pump will operate briefly as a self-check once every 24 hours, regardless of system demand.
Pre-heat is enabled if the pre-heat indicator (F) is lit. To switch pre-heat on or off move the DhW/Pre-heat control knob (B) fully clockwise and then return it to the required DhW temperature setting.
To shut down the boiler
Set the mode knob control to OFF
To relight the boiler
Repeat the procedure detailed in ‘To light the boiler’.
Frost protection
If the holiday home or park home is to be left unoccupied during cold periods when there is a threat of freezing, the domestic hot and cold water circuits must be drained as follows:
- Turn off the cold water supply
- Open all hot and cold water taps
- Open all drain plugs in the hot and cold water system (do not drain the central heating circuit, which should have been filled with antifreeze if installed in a caravan holiday home or park home).
Refer to the holiday home or Park home owner’s handbook for the drain plug positions and further instructions on draining down.
Control of water temperature
Domestic Hot Water
The DhW temperature is limited by the boiler controls to
64 o C maximum at low draw-off rate, adjustable via the DhW temperature control (B).
Due to system variations and seasonal temperature fluctuations
DHW flow rates/temperature rise will vary, requiring adjustment at the draw off tap : the lower the rate the higher the temperature, and vice versa.
Approx. flow temperatures for the boiler thermostat settings are:
Knob Setting Flow Temperature
Minimum 40 o
C (104 o
F)
Maximum 64 o
C (147 o
F)
Please note there are no drain plugs on the boiler. leave all taps and drain plugs open until next use to allow any residual water to continue to drain.
When installed in a Caravan holiday home or Park home the heating circuit and radiators should be filled with an approved antifreeze (see section 4.8). The level of antifreeze should be checked annually by a competent person. If the home is occupied during very cold and freezing weather, the central heating should be run continuously and the room stat or thermostatic radiator valves set at a minimum of 15ºC.
If the home is unoccupied for even a short period, the hot and cold water system must be drained down. This is the only way to guarantee against frost damage.
ALL FRoST DAMAGE IS oUTSIDE oF THE WARRANTy.
Central Heating
The boiler controls the central heating radiator temperature to a maximum of 80 o
C and a minimum of 45ºC, adjustable via the Ch temperature control (C).
The boiler is a high efficiency combination boiler which is most efficient when operating in condensing mode.
The boiler will operate in this mode if the Ch temperature control
(C) is set to the ‘e’ position (economy mode). This control should be set to maximum for very cold periods
Boiler Overheat Protection
The boiler controls will shut down the boiler in the event of overheating. Should this occur, a fault code will be displayed.
Refer to fault chart.
Flame Failure
Should this occur a fault code will be displayed. Refer to fault chart.
continued . . . . . .
BOILER CONTROLS
Legend
A. Mode Control Knob
B. DHW/Preheat Control Knob
C. CH Control Knob
D. Boiler Status
E. Burner ‘on’ Indication
F. Pre Heat on/off Indication
G. Mechanical Timer
H. Pressure Gauge
J.
K.
Condensate Drain
Gas Isolation Valve
(on position shown)
H off
A mode reset
B min status burner e max preheat min
24
23
22
21
20
19 18
00
17
16
15
14
10 max
C preheat
D
F
E
G
GB24
Series II
J
K
5
PRESSURE GAUGE
SECTION 1 - USERS INSTRUCTIONS
Loss of system water pressure
The pressure gauge indicates the central heating system pressure. If the pressure is seen to fall below the original installation pressure of 1-2 bar over a period of time then a water leak may be indicated. In this event re-pressurise the boiler.
If unable to do so or if the pressure continues to drop a Gas
Safe Registered Engineer, or in other countries a qualified and off status burner e competent Gas Installer should be consulted. reset min min max mode wILL NOT OPERaTE IF THE PRESSURE HaS REDUCED TO
24
23
22
18
17
16
15
14
10
To unblock a frozen condensate pipe;
1. Follow the routing of the plastic pipe from its exit point on the appliance, through its route to its termination point.
locate the frozen blockage. It is likely that the pipe is frozen at the most exposed point external to the building or where there is some obstruction to flow. This could be at the open end of the pipe, at a bend or elbow, or where there is a dip in the pipe in which condensate can collect. The location of the blockage should be identified as closely as possible before taking further action.
2. Apply a hot water bottle, microwaveable heat pack or a warm damp cloth to the frozen blockage area. Several applications may have to be made before it fully defrosts. Warm water can also be poured onto the pipe from a watering can or similar. DO NOT use boiling water.
3. Caution when using warm water as this may freeze and cause other localised hazards.
4.
Once the blockage is removed and the condensate can flow freely, reset the appliance. (Refer to “To light the boiler”)
5. If the appliance fails to ignite, call your Gas Safe Registered engineer, or in other countries a qualified and competent Gas Installer.
Preventative solutions
During cold weather, set the boiler stat to maximum, (must return to original setting once cold spell is over)
Place the heating on continuous and turn the room stat down to 15ºC overnight. (Return to normal after cold spell).
Condensate Drain
This appliance is fitted with a siphonic condensate trap system that reduces the risk of the appliance condensate from freezing. however should the condensate pipe to this appliance freeze, please follow these instructions: a. If you do not feel competent to carry out the defrosting instructions below please call your local Gas Safe Registered
Engineer, or in other countries a qualified and competent Gas
Installer for assistance.
b. If you do feel competent to carry out the following instructions please do so with care when handling hot utensils. Do not attempt to thaw pipework above ground level.
If this appliance develops a blockage in its condensate pipe, its condensate will build up to a point where it will make a gurgling noise prior to locking out an “l2” fault code. If the appliance is reset it will make a gurgling noise prior to it locking out on a failed ignition “l2” code.
Escape of gas
Should a gas leak or fault be suspected contact the Gas Supplier without Delay. TURN oFF ALL GAS SUPPLIES.
Do NOT search for gas leaks with a naked flame.
Cleaning
For normal cleaning simply dust with a dry cloth.
To remove stubborn marks and stains, wipe with a damp cloth and finish off with a dry cloth.
DO NOT use abrasive cleaning materials.
Maintenance
The appliance should be serviced at least once a year by a Gas
Safe Registered Engineer, or in other countries a qualified and competent Gas Installer.
MECHANICAL 24 HoUR TIMER
PRoGRAMMING THE TIMER
1. Decide what times you would like the timeswitch to switch ON and OFF.
2. Push segments towards the programme ring for an OFF period and push away from ring for an ON period. The minimum switching interval is 15 minutes and this can be increased in 15 minute steps.
3. Bring the timeswitch into the correct condition by manually turning the programme ring clockwise through a 24 hour cycle.
4. Turn the programme ring clockwise until the correct time of day on the ring lines up with the time indicator.
Note. The segment dial can be turned when the time controller is operating. In case of power failure, re-adjust the time controller to the correct time of day, turning the dial in a clockwise direction.
Permanently OFF
OFF segment
ON segment
Permanent override
By rotating the central switch so that the symbol ( 1 ) lines up with the time indicator ( ) the unit will be permanently ON.
With the symbol ( ) lining up with the time indicator ( ) the unit acts as a timeswitch.
With the symbol ( ) lining up with the time indicator ( ) the unit will be permanently OFF.
24hr Programme Ring
Timer Control Permanently ON
24
23
22
21
20
19 18
17
16
15
14
3
4
5
6 7
8
9
10
11
Time & Control
Indicator
Timer control segments
1 Segment = 15 mins
Push towards programme ring = OFF
Push away from programme ring = ON
6
SECTION 1 - USERS INSTRUCTIONS
PoINTS FoR THE BoILER USER
Note.
In line with our current warranty policy we would ask that you check through the Troubleshooting guide to identify any problems external to the boiler prior to requesting a service engineers visit. Should the problem be found to be other than with the appliance we reserve the right to levy a charge for the visit, or for any pre-arranged visit where access is not gained by the engineer.
TRoUBLESHooTING
No HoT WATER No CENTRAL HEATING No HoT WATER oR
CENTRAL HEATING
Check the mains switch (fused spur) is turned on and ensure switch mode control knob (A) is in the summer or winter position
Check the mains switch (fused spur) is turned on and ensure switch mode control knob (A) is in the winter position
Is water coming out of the hot water tap when turned on?
NO yeS
See boiler “Fault Codes” section. If ‘0’ is displayed then contact morco if your appliance is under warranty or a Gas
Safe Registered engineer, or in other countries a qualified and competent Gas Installer, if out of warranty.
Check the timer is in an “ON” position and the room thermostat is turned up
Does the boiler operate and provide central heating?
yeS
Check the time settings on the programmer are as you require and adjust if necessary
NO
Check the fused spur is turned on and ensure switch mode control knob (A) is in the winter position
Does the boiler have a display showing on the front control panel?
NO yeS
See boiler “Operation modes” and “Fault Codes” section
Contact a Gas Safe Registered engineer, or in other countries a qualified and competent Gas
Installer.
Contact a Gas Safe Registered engineer, or in other countries a qualified and competent Gas
Installer.
See boiler “Operation modes” and
“Fault Codes” section. If “0” is displayed then contact a Gas Safe
Registered engineer, or in other countries a qualified and competent
Gas Installer.
oPERATIoN MoDES
Note.
These letters are permanently displayed while in that mode.
DISPLAy CoDE oN BoILER DESCRIPTIoN
The boiler is in standby mode awaiting either a central heating call or hot water demand.
The boiler has a call for central heating but the appliance has reached the desired temperature set on the boiler.
The boiler has a call for hot water but the appliance has reached the desired temperature set on the boiler.
The boiler is operating in central heating mode.
The boiler is operating in hot water mode.
The boiler is operating in pre heat mode.
The water in the cental heating circuit is less than 5ºC. If heating is switched on, this display code will change to “c”.
7
SECTION 2 - gENERAL SPECIFICATIONS
2.1 GENERAL SPECIFICATIoNS
The Morco GB Series II range of boilers are wall mounted, full sequence, automatic spark ignition low water content, fanned flue, high efficiency condensing combination boilers.
Note. Due to the high efficiency of the boiler a plume of water vapour will format the terminal during operation. The boiler is supplied for use with Propane only at 37mbar supply pressure. It is particularly suitable for caravan holiday home and park home use.
maximum heat output in either heating or hot water for the GB24 is 24.2kW (82,570 Btu/hr) maximum heat output in heating mode for the GB30 is 24.2 kW
(82,570 Btu/hr) with 30.3 kW (103,384 Btu/hr) available for hot water production.
The boiler can be supplied with a standard concentric flue with additional extensions, flue deflector and vertical flue kits available as optional extras. The only flueS that can be fitted are those detailed in this instruction manual.
The boiler is suitable for connection to fully pumped, sealed heating systems ONly. Adequate arrangements for completely draining the system by provision of drain cocks must be provided in the installation pipework.
The boiler contains the following components:
Cast Aluminium heat exchanger
Domestic hot Water Plate heat exchanger
Diverter Valve
Circulating Pump
Pressure Gauge
Safety Valve and Central heating expansion Vessel
Automatic Bypass
Daily Pump and Diverter Valve exercise mechanical 24hr Timer
The boiler temperature controls are visible, located in the control panel. These enable the user to control both Ch and DhW temperatures independently. There is the additional feature of a
DhW preheat facility. Operating and fault codes are displayed on the status panel.
8 Schematic Diagram
1 Expansion Vessel
2 Pump
3 Auto Air Vent
4 Water Pressure Switch
5 Flow Thermistor
6 Return Thermistor
7 Divertor Valve
8 Fan
9 Venturi
10 DHW Plate Heat Exchanger
11 Ignition Electrode
12 Flame Detection Electrode
13 Gas Valve
14 Siphon / Trap
15 DHW Flow Turbine
16 System Pressure Gauge
17 Sump Cover
12
9
13
11
5
1
17
3
6
2
4
16
14
7
15 10
8
SECTION 2 - gENERAL SPECIFICATIONS
2.2 WIRING DIAGRAM
Fused at 4A
Main Supply
Room Stat
Spark Generator
Flame Sensor Electrode
Divertor V
Gas Valve
Service Connector
- blue - black - brown - red - pink - yellow - white - yellow/green - grey - orange - violet b bk br r p y w y/g g or v ater Flow pressure Switch
9
section 3 - tecHnicAL DAtA
Table 1 - General Data
Morco GB Series II
Gas supply
Gas Supply Connection
Inlet Connection
Outlet Connection
Flow Connection
Return Connection
Domestic hot Water
Domestic hot Water
Central heating
Central heating
24 30
I
3p
- G31 - 37mbar
15mm copper compression
(mm) 3.75 3.75
G 1 /
2
G 1 /
2
G 3 /
4
G 3 /
4
Flue Terminal Diameter electrical Supply mm (in)
Average Flue Temp-mass Flow Rate maximum Working Pressure (Sealed Systems)
(DhW) bar (lb/in 2 ) maximum Domestic hot Water Inlet Pressure bar (lb/in 2 ) (kPa) minimum Domestic hot Water Inlet Pressure* bar (lb/in 2 ) (kPa)
63 o C - 11g/s
100 (4)
2.5 (36.3)
68 o C - 13g/s
10.0 (145) (1000)
0.8 (11.6) (80) 1.3 (18.9) (130)
230 V ~ 50 hz.
W 146 152
Fuse Rating
Water content
Domestic hot Water
Packaged Weight
Central heating
external : 3A Internal : T4h hRC l250 V litre (gal) 1.2 (0.26) litre (gal) kg (lb)
0.5
33.8 (74.4)
(0.11)
34.1 (75.2) maximum Installation Weight
Boiler Casing Size height kg (lb) mm (in)
Width mm (in)
Depth mm (in)
*Required for maximum flow rate. Boiler operates down to 2 l/min DHW delivery
31 (68.3)
700 (27.5)
31.2 (68.8)
395 (15.5)
285 (11.2)
Table 2 - Performance Data - Central Heating
Table 3 - Performance Data - Domestic Hot Water
Boiler Input :
Boiler Input ‘Q’ Nett CV
Max. Min.
24 30 24 30 kW 24.3 24.3 8.0 8.0
Gross CV
Gas Consumption
Btu/h 82,912 82,912 27,296 27,296 kW 26.4 26.4 8.7 8.7
Btu/h 90,077 90,077 29,684 29,684 m 3 /h 1.00 1.25 0.329 0.329
ft 3 /h 35.33 44.20 11.62 11.62
kg/hr 1.83 2.26 0.58 0.58
Boiler Output :
Non Condensing kW 24.2 24.2 8.00 8.00
70 o C mean Water temp. Btu/h 82,570 82,570 27,296 27,296
Condensing kW 25.6 25.6 8.5 8.5
40 o C mean Water temp. Btu/h 87,347 87,347 29,002 29,002
Seasonal efficiency* SEDBUK 2005
Seasonal efficiency* SEDBUK 2009
NOx Classification CLASS 5
91% 91.1%
89% 89% maximum DhW Input :
Btu/h 90,077 112,596
Gas Consumption m 3 /h 1.00 1.25
ft 3 /h 35.33 44.20
kg/hr 1.83 2.26
maximum
DhW Output
Nett CV kW 24.3 30.4
Btu/h 82,912 103,725
Gross CV
DhW Flow Rate at 35°C temp. rise. kW kW
24 30
26.4
24.2
Btu/h 82,570 l/min gpm
9.9
2.2
DHW Specific Rate l/min 11.5
gpm 2.5
33
30.3
103,384
12.4
2.8
14.5
3.2
* The value is used in the UK Government’s Standard Assessment Procedure (SAP) for energy rating of dwellings. The test data from which it has been calculated have been certified by a notified body.
10
Note.
Gas consumption is calculated using a calorific value of 95.65 MJ/m 3 (2569 Btu/ft 3 gross or 88.0 MJ/m 3 (2,360 Btu/ft 3 ) nett
)
To obtain the gas consumption at a different calorific value: a.
For l/s - divide the gross heat input (kW) by the gross C.V. of the gas (MJ/m 3 ) b.
For ft
3 /h
- divide the gross heat input (Btu/h) by the gross C.V. of the gas (Btu/ft 3 ) c. For m 3 /h - multiply l/s by 3.6.
Key to symbols
PMS = maximum operating pressure of water
C
13
C
33
= A room sealed appliance designed for connection via ducts to a horizontal or vertical terminal, which admits fresh air to the burner and discharges the products of combustion to the outside through orifices which, in this case, are concentric. The fan is up stream of the combustion chamber.
I
3P
= An appliance designed for use on 3rd Family gas, Group P only.
*Required for maximum flow rate. Boiler operates down to 2 l/min DHW delivery
Table 3 - Performance Data - Domestic Hot Water
section 3 - tecHnicAL DAtA
BoILER DIMENSIoNS, SERVICES & CLEARANCES
The boiler connections are made on the boiler bulkhead fittings.
The following minimum clearances must be maintained for operation and servicing.
Additional space will be required for installation, depending upon site conditions.
Side and Rear Flue a. Provided that the flue hole is cut accurately, e.g. with a core boring tool or hole cutter the flue can be installed from inside the dwelling where wall thicknesses do not exceed 600mm
(24”). Where the space into which the boiler is going to be installed is less than the length of flue required the flue must be fitted from the outside.
Installation from inside oNLy b. If a core boring tool or hole cutter is to be used inside the dwelling the space in which the boiler is to be installed must be at least wide enough to accommodate the tool.
In either of the above cases safe external access is required to allow the addition of sealant to seal the flue to the aluminium flue collar (RSF 060).
2.5
2.5
from case
395 285
155
17
Side flue dim. A 86.5
700
Underside View - Dimensions to Wall
43.5
65 28.5 28.5 60.6
75 56.4
37.5
103 99 99
W A L L
99 103
Front clearance
The minimum front clearance when built in to a cupboard is 5mm from the cupboard door but 450mm overall clearance is still required, with the cupboard door open, to allow for servicing.
*
Bottom clearance
Bottom clearance after installation can be reduced to 5mm.
This must be obtained with an easily removable panel, to enable the consumer to view the system pressure gauge, and to provide the 100mm clearance required for servicing.
Max 30kW
Max 24kW
2. For flue lengths requiring “D” pack extensions (RSF 341), the flue must incline by 26mm per 1 Metre of flue length.
11
SECTION 4 - gENEral INSTallaTION rEquIrEmENTS
4.1 RECoMMENDATIoNS
Current Gas Safety (Installation and Use) Regulation or Rules in
Force.
The boiler is suitable only for installation in the specified countries and should be installed in accordance with the rules in force.
In GB, the installation must be carried out by a Gas Safe
Registered Engineer, or in other countries a qualified and competent Gas Installer. It must be carried out in accordance with the relevant requirement of the:
•
•
•
•
•
•
•
Gas Safety (Installation and Use) Regulations
Appropriate National Standards
The Water Fittings Regulations
Current IEE Wiring Regulations
Health & Safety Document Nol.635
The Electricity at work Regulations 1989.
BS5482 Part 1 Code of Practice for Domestic butane and propane gas burning installation in permanent dwellings,
• residential park homes and commercial premises.
BSEN1949:2011 Specification for the installation of LPG
Systems for habitation purposes in leisure accommodation vehicles and other road vehicles.
IMPoRTANT
The manufacturer’s notes mUST NOT be taken, in any way as overriding statutory obligations.
4.2 BoILER LoCATIoN
The boiler must be installed on a flat and vertical wall, capable of adequately supporting the weight of the boiler and any ancillary equipment.
The boiler may be fitted on a combustible wall and insulation between the wall and the boiler is not necessary unless required by National Standards.
For electrical Safety reasons there must be no access available from the rear of the boiler.
The boiler must not be fitted outside.
BATHRooM INSTALLATIoNS
This appliance is rated IP20.
The boiler may be installed in any room or internal space, although particular attention is drawn to the requirements of the current
Iee (BS.7671) Wiring Regulations and the electrical provisions of the building regulations applicable in Scotland, with respect to the installation of the boiler in a room or internal space containing a bath or shower. For Ie reference should be made to the current eTCI rules for electrical installations and I.S. 813:2002.
If the appliance is to be installed in a room containing a bath or shower then, providing water jets are not going to be used for cleaning purposes (as in communal baths/showers), the appliance must be installed beyond Zone 2, as detailed in BS.7671.
2.25m
Zone 1
0.6m
Recessed window
Zone 2
Ceiling
CoMPARTMENT INSTALLATIoNS
A compartment used to enclose the boiler should be designed and constructed specially for this purpose.
An existing cupboard or compartment may be used, provided that it is modified for the purpose.
• The position selected for installation MUST allow adequate space for servicing in front of the boiler.
4.3 FLUE TERMINAL PoSITIoN
Pluming will occur at the terminal so avoid locations where this will cause a nuisance.
The boiler mUST be installed so that the terminal is exposed to external air.
It is important that the positions of the terminal allows the free passage of air accross it at all times.
minimum acceptable spacing from the terminal to obstructions and ventilation pump are specified in the table below.
For Caravan Holiday Homes; if the height of the flue terminal from any ground, decking or steps is under 1.5m then a suitable terminal guard should be fitted.
For Residential Park homes, please refer to BS 5440 Part 1.
Terminal Guards are available from boiler suppliers.
TFC Flue Guard - model K6 Round Plastic Coated. www.tfc-group.co.uk
Table 4 - Balanced Flue Terminal Position
Flue Terminal Positions Min. Spacing*
1. Directly below, above or alongside an opening window, air vent or other ventilation opening. 300mm (12”)
2. Below guttering, drain pipes or soil pipes. 25mm ( 1”)*
BS5440-1 2008 75mm (3”)
3. Below eaves. 25mm (1”)*
BS5440-1 2008 200mm (8”)
4. Below balconies or a car port roof. 25mm (1”)*
BS5440-1 2008 200mm (8”)
5. From vertical drain pipes or soil pipes. 25mm (1”)*
BS5440-1 2008 150mm (6”)
6. From an internal or external corner or to a 25mm (1”)* boundary along side the terminal.
BS5440-1 2008 300mm (12”)
7.
Above adjacent ground, roof or balcony level. 300mm (12”)
8. From a surface or a boundary facing the terminal. 600mm (24”)
1,200mm (48”) 9. From a terminal facing a terminal.
10. From an opening in a car port
(e.g. door or window) into dwelling.
11. Vertically from a terminal on the same wall.
1,200mm (48”)
1,500mm (60”)
12. horizontally from a terminal on the wall. 300mm (12”)
Vertical Terminals
13. Above the roof pitch with roof slope of all angles. 300mm (12”)
Above flat roof. 300mm (12”)
14. From a single wall face.
From corner walls.
300mm (12”)
300mm (12”)
15. Below velux window 2000mm (79”)
16. Above or side of velux window 600mm (24”)
Zone 0
3G8913a
* Only one reduction down to 25mm is allowable per installation
otherwise BS5440-1 2008 dimensions must be followed.
12
SECTION 4 - gENEral INSTallaTION rEquIrEmENTS
4.4 AIR SUPPLy
It is NOT necessary to have a purpose provided air vent in the room or internal space in which the boiler is installed. Neither is it necessary to ventilate a cupboard or compartment in which the boiler is installed, due to the low surface temperature of the boiler casing during operation.
4.5 ELECTRICAL SUPPLy
WARNING
This appliance mUST be earthed.
Wiring external to the boiler mUST be in accordance with the correct Iee Regulations and any local regulations.
The boiler has been pre-fitted with a 3 amp fused approved moulded 3 pin plug and flying lead, for use with 230V 50Hz.
The plug should be used with an unswitched/shuttered socket outlet complying with BS1363.
4.6 GAS SUPPLy
A propane gas supply at 37mbar is required.
Ensure that regulator is of sufficient capacity to carry the maximum boiler input plus the full demand for any other installed appliances.
ensure the connection between supply/cylinder to caravan holiday home or park home is designed so that no pressure drop occurs.
Ensure the pipework is of sufficient size to prevent a pressure drop greater than 2.5mbar between the final pressure regulator to the caravan holiday home or park home and all appliances when the installation is subjected to the anticipated maximum load.
IMPoRTANT
The complete installation mUST be tested for gas soundness.
4.7 CoNDENSATE DRAIN
A condensate drain is provided on this boiler.
The drain mUST be connected to an approved drainage point.
All pipework and fittings MUST be made of plastic. No other materials may be used.
Suitable protection against freezing should be undertaken.
4.9 REqUIREMENTS FoR SEALED WATER
SySTEMS
At maximum CH output 24.24kW at a 20ºC differential and flow rate 17.3 l/min a 3.4m wg head is available for the system
Set all radiators to give around 20ºC temperature differential.
The boiler does not normally need a bypass but at least some radiators of load at least 10% of the minimum boiler output.
These radiators should be fitted with lockshield valves only.
A sealed system MUST only be filled by a competent person using an approved filling loop (or other approved method) between the mains water supply pipe and the central heating return pipe.
Once used, the filling loop should be disconnected and capped off.
4.10 ExPANSIoN VESSEL
The boiler is fitted with an 8 litre expansion vessel which is sufficient for a cold fill capacity of up to 143 litres.
For other system volumes refer to table below.
Safety valve setting bar 3.0
Vessel charge pressure bar 0.5 to 0.75
System pre-charge pressure bar
System volume
(litres)
25
50
75
100
125
150
175
190
200
250
300
For other system volumes multiply by the factor across
None 1.0
Expansion vessel volume (litres)
1.6 1.8
3.1 3.7
4.7 5.5
6.3 7.4
7.8 9.2
9.4 11.0
10.9 12.9
11.9 14.0
12.5 14.7
15.6 18.4
18.8 22.1
0.063 0.074
4.8 WATER SySTEMS - GENERAL
This boiler is designed for connections to fully pumped sealed system only.
IMPoRTANT - A minimum length of 1 metre of copper pipe
MUST be fitted to both central heating and DHW flow and return connections from the boiler before connection to any plastic piping.
Central Heating System
IMPoRTANT
- The sealed central heating system must be filled at all times with an antifreeze / inhibitor and water mix that is compatible with aluminium heat exchangers. The concentration levels of the antifreeze / inhibitor should be at least 25% in order to provide adequate corrosion protection. This level also provides protection against frost from -7.5ºC to -11ºC (depending on the product used). The maximum allowable level of antifreeze / inhibitor is around 40%.
The only products approved are as follows:
-
-
Fernox Alphi 11
Sentinel X500
Failure to use these products may result in damage to the boiler and / or the radiators in the heating system.
4.11 PRESSURE RELIEF VALVE
A pressure relief valve set at 3 bar is fitted to the boiler. The connection is shown in the dimensions and connection details.
The discharge pipework must be suitable for use with 3bar water at 110ºC without damage to property and persons.
The run and exit point of the pipework should not leave a hazard or be prone to freezing up.
4.12 DHW SySTEMS
Check that the mains supply pressure is within the units stated in the technical data section in this manual
A pressure reducing valve should be fitted if above 10 bar.
In areas of low mains water pressures the domestic hot water regulator may be removed (by a suitably qualified person). The boiler will require the flow rate to be set to give a temperature of
35ºC at the tap furthest from the boiler.
In hard water areas where mains water exceeds 200ppm total hardness, the fitting of a scale reducing device is recommended
(with the requirements of the local water company).
The use of artificially softened water, however, is not permitted.
The boilers are suitable for connection to most types of washing machine and dishwasher appliances.
13
section 5 - installation instructions
5.1 BoILER PACKAGING
The boilers are supplied in different packagings:
•
•
•
Boiler
Flue System (separate)
Hardware Pack (separate)
5.2 FITTING/MoUNTING THE BoILER
Decide where the boiler is to be fixed on the wall, taking into account installation requirements detailed in previous section.
1. Screw the wall mounting plate to the wall choosing one of the two sets of slots in left and right bank. ensuring that at least one of the screws is fitted into a top slot.
Example of fixing
5.4 INTERNAL WIRING
The boiler has been pre-fitted with a 3 amp fused approved moulded 3 pin and flying lead for use with 230V 50Hz.
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
4
The plug should be used with an unswitched/shuttered socket outlet complying with BS1363.
The boiler comes pre-fitted with a link wire between the room thermostat/Timer connections on the terminal strip. This creates a permanent call for heat and must be removed when adding a room thermostat.
Cable
Clamp
2. lift the boiler onto the wall mounting plate, locating it over the two tabs.
RooM THERMoSTAT - WIRING
To fit a room thermostat proceed as follows:
1. ensure that the electrical supply to the boiler is isolated before proceeding.
2.
Remove the two screws beneath the flap on the front of the boiler and lower the front panel.
3.
Remove the pre-fitted link wire between the Room stat/timer terminals.
4. Pass the cable through a grommet, secure with the cable clamp and connect the room stat as shown in the diagram below.
5. If room stat has a neutral connection, connect this to terminal
N (load) in the fused spur.
6. Carry out all necessary electrical checks.
7. Raise the front panel and relocate the two screws under the small flap.
8. Check operation of room stat if possible.
Note. If present, remove the bottom end support packaging and ensure all plastic plugs are removed from CH & DHW connections.
5.3 WIRING INSTRUCTIoNS
WARNING: ThIS APPlIANCe mUST Be eARTheD
Connections must be made in such a way that allows complete isolation of the electrical supply, e.g. double pole switch with
3mm contact separating in both poles.
L
N
ROOM
STAT/
TIMER
230VAC Feed
230VAC Return
N
Room
Stat
14
section 5 - installation instructions
5.5 WATER AND GAS CoNNECTIoNS
ensure all boss blanking plugs are removed before making any connections.
Each valve must be fitted to the correct boss as shown in diagram below
Do not subject any of the isolating valves to heat as the seals may be damaged.
Ensure that the green fibre washer is used on the CH flow connection.
IMPoRTANT - The gas service cock is sealed with a top hat washer - DO NOT subject to heat.
Pressure Relief Valve (PRV) - located at the bottom right hand side of the boiler connection via a 15mm diameter stub pipe.
Use a replaceable connection to ease the replacement of the valve if required.
ensure a safe discharge point using temperature and pressure resistant materials.
5.6 AIR / FLUE SySTEMS
The flue system is part of the appliance and is approved as such. Only use the flue systems supplied by Morco.
The standard flue kit (RSF303) for the Morco GB range is a 600mm as shown below. There is also a 900mm kit available (RSF305).
600
Turret
60 Part No. RSF303
The minimum cut length is 138mm (includes 30mm into elbow)
The maximum allowable length using extensions (RSF341) is:
GB24 Series II - 8m (minus any flue kit options)
GB30 Series II - 7m (minus any flue kit options)
15
section 5 - installation instructions
5.7 DETERMINING THE FLUE LENGTH
ImPORTANT. The boiler must be installed in a vertical position in accordance to the installation instructions.
STANDARD FLUE KITS
Horizontal Flue Terminal RSF303 (600mm long) - contains: Flue turret, non telescopic single piece flue incorporating a terminal and inner rubber wall seal.
Extension Kit RSF341
- contains: 1 metre length of flue pipe (Functional length 950mm), 1 support bracket.
When extension kits are used the flue duct must incline 1.5 degrees away from the appliance, to allow the condensate to drain back to the boiler and out of the condensate drain. It is recommended that a support bracket is fitted on every 1 metre of pipe work used and the bracket is located as close to the collar as possible. The bracketing must ensure a 1.5 degree fall back to the appliance.
Only use water as a lubricant during assembly.
The horizontal flue kit terminal is classed as part of the maximum flue length.
Once the flue is installed it is IMPORTANT that the white air duct protrudes from the aluminum flue collar (RSF 060) by at least 17mm. The gap between the aluminium flue collar (RSF 060) and the white air duct MUST be sealed with sealant to create an adequate seal.
Internal Sealing
Flubber
WALL
17mm min
Fill with sealant
Fill with sealant
Aluminium Flue
Collar (RSF 060)
It is IMPORTANT that all attachments are fitted in accordance with the installation instructions provided in this manual.
The TURRET supplied in the Horizontal Flue Kits (RSF303 & RSF305) has an upper combustion sample point with a screw cap seal and a lower air sample point with an air stopper seal. Ensure all caps & seals are in place.
Additional Termination Kits
available for use with these Horizontal Flue Kits (RSF303 & RSF305)
Flue Deflector Kit (RSF300) The resistance is the equivalent of 1 metre of flue pipe and therefore must be deducted from any maximum flue length
Total Maximum Permissible Horizontal Concentric Flue Length combining both horizontal Flue Kits and extension Kits
(Measured from centreline of the turret to the outside face of the aluminium flue collar (RSF060))
24 kW appliances
30 kW Appliances
Total Maximum: 8 metres - minus any flue kit options
Total Maximum: 7 metres - minus any flue kit options
Total Maximum Permissible Vertical Flue Length
24 & 30kW Appliances
Total maximum: 7.5 metres - minus any 90º bends
Minimum Horizontal Flue Lengths
(Centre line of turret to outside face of the aluminium flue collar (RSF060))
Rear Flue - 191mm
Side Flue - 236mm (with minimum 2.5mm clearance)
16
section 5 - installation instructions
5.8 DETERMINING THE FLUE LENGTH
FIGURE 1
REAR FLUE
Cut flue length = distance from edge of turret to outside of wall dimension A + 47mm.
Note
. Minimum dimension A which can be accommodated is
91mm.
A
SIDE FLUE
Cut flue length = distance from edge of turret to outside of wall dimension B + 47mm.
Note
. Minimum dimension B which can be accommodated is
136mm (with minimum clearance of 2.5mm).
B
REAR
Fit to wall
SIDE
Fit to wall
Minimum clearance 2.5mm
NOTES
Centre of turret to edge of turret = 100mm
Turret has a flue insertion of 30mm
The white outer flue tube must protrude the wall by 17mm.
From centreline of turret to wall. Rear mount 155mm, side (including clearance) 200mm
Flue length measured from outer terminal lip to end of outer flue
A or B + 47mm
5.9 CUTTINg HORIZONTAL FLUE TERMINAL RSF303 (600MM LONg)
1.
Measure from the outer terminal lip to end of outer flue. Mark the required cut length (A or B + 47mm) around the circumference of the outer flue and cut following the mark to ensure its cut square.
2. Dress the cut end to make sure all burr’s are removed and the cut edge is in its original shape.
3. mark the inner tube 10mm longer than the outer tube around its circumference and cut following the mark to ensure its cut square.
4. Remove all burrs and place a light chamfer on the outer edge to aid assembly.
10mm
Mark cut length =
A or B + 47mm from terminal lip
17
section 5 - installation instructions
5.10 INSTALLING THE FLUE
FITTING FLUE THRoUGH THE WALL
1. ensure the seam and the outlet terminal are at the top and fitted as shown.
2.
Once the flue is installed it is IMPORTANT that the white air duct protrudes from the aluminium flue collar (RSF 060) at least
17mm.
Note. If less than 50% of the length of the flue is internal the flue should be fitted from outside.
3.
Fit the internal sealing flubber to the flue
(leave loose) and check protrusion externally of the white air duct is 17mm.
4. Fit the turret as below
Internal Sealing
Flubber
WALL
17mm min
Fill with sealant
5” hole
Fill with sealant
Aluminium Flue
Collar (RSF 060)
FITTING THE TURRET -
Ensure the condensate trap / siphon is filled with water
1.
Ensure the rubber seal is fitted correctly on the appliance manifold and that all flue seals are undamaged.
2.
Hold the flue firmly and push the turret on until it has travelled 30mm on to the flue pipe and is fully engaged. Make sure the flue has not rotated or moved forward during fitting and the flue seam is upper most.
3.
Push the turret into the manifold ensuring the upper plastic lip is flush with the top of the manifold.
4.
Fully engage the clamp location section into the manifold location holes. Rotate down on to turret flange.
5. Secure clamp to appliance using securing screw.
6.
Ensure all sample points are accessible and all sample plugs and caps are fitted.
7.
Fully engage the flue into the turret and slide internal flubber to wall.
8.
The gap between the aluminium flue collar (RSF 060) and the white air duct MUST be sealed with sealant to create a seal.
Retaining screw
Sample points
Clamp Lugs
D
Flue Outlet
A - Duct Assembly
B - Flue Turret
C - Turret Clamp
D - Seal
Flue Outlet
B
A
C
18
section 5 - installation instructions
5.11 FLUE EXTENSIONS (RSF341) - OPTIONAL
INNER PIPE ASSEMBLy INSTRUCTIoNS
1.
Make sure that ‘top hat’ on the collar (A) fits over the rectangular form on the inner plastic pipe (B).
For side outlet refer to section 1.2 before connecting.
3. Slide the pipe and collar assembly back into the outer housing (e), note that this can only be done at the female end of the outer housing.
A B
Top hat
Rectangular
2.
Ensure that the flat base of the collar (C) is positioned on the bottom lip of the pipe (D).
E
4.
When fitting support brackets (F) make sure they are positioned on the female side of the neck as shown.
C
D
F
5.12 FLUE DEFLECTOR KIT (RSF300) - OPTIONAL
The flue deflector elbow can be fitted to the flue outlet of the standard terminal kits RSF303 or RSF305 to deflect the flue products horizontally to the left or the right only.
1.
Refer to the boiler Installation and Servicing Instructions for fitting of the boiler and its flue system.
Note.
The resistance of the deflector is equivalent to 1 metre of flue length. Ensure this is used when calculating the maximum allowable flue length.
2.
Choose the direction required to deflect the flue products
(horizontally left or right only).
3.
Push the deflector elbow onto the angled flue outlet of the terminal in the desired position and ensure the deflector is pushed up to the shoulder to fully engage the rubber seal. Drill the terminal through the hole in the deflector with a 3.2mm (1/8") drill and secure the deflector with the self tapping screw provided.
Note.
Only use water as a lubricant during assembly. Do not use mineral based oils.
5.13 90º KIT RSF315 (OPTIONAL)
This optional kit can be used on both horizontal and vertical flue kits
1. Use dimensions below for calculating total length
2.
When cutting extensions or flue kits always allow sufficient (+ 30mm air duct + 14mm flue duct) to allow for correct engagement in the fitting
3. 1 elbow reduces the maximum available length by
1m
Note.
Only use water as a lubricant during assembly .
Do not use mineral based oils.
WALL
115
Flue
Deflector
19
section 5 - installation instructions
5.14
FITTINg THE OPTIONAL ROOF FLUE KIT (RSF345) (Pitched)
Note.
A 5º or 14º pitched roof plate (not supplied) is required before proceeding with the installation of this kit.
This kit is suitable for both 5º and 14º pitched roof terminations, using a concentric flue to run vertically from the top of the boiler and terminating above roof level.
Connection to the top of the boiler is made using a vertical connector
(supplied in the kit - RSF346).
WEATHER PRooFING
Where the flue passes through the roof line an adequate seal must be made. This is achieved by using a suitable sealant.
ACCESSoRIES
Flue Duct Extension Kits are available for flue lengths extending beyond 1m. These packs contain 1m extension ducts and may be cut to the desired length. If 90º elbows are used (RSF315) they will reduce the overall height by 1m per elbow.
Terminal Position
Directly below an opening, air brick, windows, etc.
Below plastic / painted gutters
Painted surface
Below eaves or balcony
Below velux windows
Above or side of velux windows
5.15 ASSEMBLING THE RooF FLUE KIT
1.
Position the roof plate (supplied separately) over the hole cut in the roof and insert flue terminal from the roof end.
1
Minimum Dimension
300 mm
300 mm
300 mm
500 mm
2000mm
600mm
Flue Terminal
ASSEMBLy A
MAX LENGTH:
7.5m**
MIN LENGTH:
0.950m
5º & 14º
**minus any
90º bends
BOILER
5º
RSF050
14º
RSF050
2. ensure that if the length needs to be adjusted to allow an additional 30mm added to the outer air tube length 14mm added to the inner flue length. This allows correct engagement into the vertical connector.
Note. ensure a square cut. remove all burrs and sharp edges.
3. Fit the vertical connector (supplied in the kit) and secure the vertical connector by applying downward pressure on the connector.
4.
Position the clamp on the top face of the flue manifold and push it horizontally backwards. Locate both clamp lugs into the flue manifold and secure to the flue manifold clamp with the m5 retaining screw.
5. “Push” assembly A into vertical connector.
Notes.
Ensure turret sample points are servicable and all caps and plugs are fitted.
Ensure condensate siphon/trap is filled with water.
6. Finally ensure the roof plate is correctly sealed to the roof.
20
4
5
Assembly A
Vertical connector
3
section 5 - installation instructions
5.16 CoNDENSATE DRAIN
47
137
Condensate
Drain
156
T his appliance is fitted with a siphonic 75mm sealed condensate trap system that requires filling before operating the appliance for the 1st time or after maintenance.
All condensate pipework should conform to the following: a. Where a new or replacement boiler is being installed, access to an internal ‘gravity discharge’ termination should be one of the main factors considered in determining boiler location.
b. Plastic with push fit or solvent connections.
c. Internal plastic pipe work a minimum of 19mm ID (typically
22mm OD) d. external plastic pipe must be a minimum of 30mm ID (typically
32 OD) before it passes through the sleeved wall.
e. All horizontal pipe runs, must fall a minimum of 45mm per metre away from the Boiler.
f. External & unheated pipe work should be kept to a minimum and insulated with Class “O” waterproof pipe insulation.
g. All installations must be carried out in accordance to the relevant connection methods as shown in the “Condensate installation diagrams” & BS6798:2009 h. Pipe work must be installed so that it does not allow spillage into the dwelling in the event of a blockage (through freezing) i. All internal burrs should be removed from the pipe work and any fittings.
NB. Clip runs to prevent pipework disconnecting due to vibration etc.
In order to minimise the risk of freezing during prolonged very cold spells, one of the following methods of terminating condensate drainage pipe should be adopted.
Internal Drain Connections
Wherever possible, the condensate drainage pipe should be routed to drain by gravity to a suitable internal foul water discharge point such as an internal soil and vent stack or kitchen or bathroom waste pipe etc. See Figs 1 and 2.
Condensate Pump
Where gravity discharge to an internal termination is not physically possible or where very long internal pipe runs would be required to reach a suitable discharge point, a condensate pump of a specification recommended by the boiler or pump manufacturer should be used terminating into a suitable internal foul water discharge point such as an internal soil and vent stack or internal kitchen or bathroom waste pipe etc. (fig 3).
External Drain Connections
The use of an externally run condensate drainage pipe should only be considered after exhausting all internal termination options as described previously. An external system must terminate at a suitable foul water discharge point or purpose designed soak away.
If an external system is chosen then the following measures must be adopted:
The external pipe run should be kept to a minimum using the most direct and “most vertical” route possible to the discharge point, with no horizontal sections in which condensate might collect.
- For connections to an external soil/vent stack see Fig 4.
Insulation measures as described should be used.
- When a rainwater downpipe is used, an air break must be installed between the condensate drainage pipe and the downpipe to avoid reverse flow of rainwater into the boiler should the downpipe become flooded or frozen, see Fig 5.
- Where the condensate drain pipe terminates over an open foul drain or gully, the pipe should terminate below the grating level, but above water level, to minimise “wind chill” at the open end. The use of a drain cover (as used to prevent blockage by leaves) may offer further prevention from wind chill. See Fig 6.
- Where the condensate drain pipe terminates in a purpose designed soak away (see BS 6798) any above ground condensate drain pipe sections should be run and insulated as described above. See Fig 7
Unheated Internal Areas
Internal condensate drain pipes run in unheated areas should be treated as external pipe.
ensure the customer is aware of the effects created by a frozen condensate and is shown where this information can be found in the user manual.
Figure 1 - Connection of Condensate Drainage Pipe to
Internal Soil & Vent Stack
Boiler with 75mm sealed condensate trap
Min Ø 19mm
Internal pipe
Figure 2 - Connection of a Condensate Drainage Pipe
Downstream of a Sink, Basin, Bath or Shower Water Trap to
Internal Soil Vent Stack
Boiler with 75mm sealed condensate trap
Min Ø 19mm
Internal pipe
Minimum connection height up to 3 storeys
Sink/basin/ bath or shower
Boilers without 75mm sealed condensate trap must be fitted with a 75mm trap and visible air break
Boilers without 75mm sealed condensate trap must be fitted with a 75mm trap and visible air break continued . . . . .
21
section 5 - installation instructions
CoNDENSATE DRAIN - CoNT’D.......
Figure 3 - Connection of a Condensate Pump Typical method (see manufacturers detailed instructions)
Figure 4 - Connection of Condensate Drainage Pipe to
External Soil & Vent Stack
Boiler with 75mm sealed condensate trap
Min Ø 19mm
Internal pipe
Visible air break
Condensate pump
(Install in accordance with manufacturers instructions)
Boiler with 75mm sealed condensate trap
Min Ø 19mm
Internal pipe
Boilers without 75mm sealed condensate trap must be fitted with a 75mm trap and visible air break
Min Ø 30mm
Internal pipe
Water/weather proof insulation
Minimum connection height up to 3 storeys
Figure 5 - Connection of a Condensate Drainage Pipe to an external Rainwater Downpipe (only combined foul/rainwater drain)
Boiler with 75mm sealed condensate trap
Min Ø 19mm
Internal pipe
Min Ø 30mm
Internal pipe
Terminated and cut at 45º
43mm 90º male/ female bend
Water/ weather proof insulation combined foul/ rain water drain
External air break
Air gap
68mm Ø PVCU
Strap on fitting
Figure 6 - Connection of Condensate Drainage Pipe
Upstream of a Sink, Basin, Bath or Shower Waste Trap to external Drain, Gulley or Ranwater hopper
Boiler with 75mm sealed condensate trap
Min Ø 19mm
Internal pipe
Sink, basin, bath or shower with integral overflow and 75mm trap
Visible air break at plug hole
Minimum 30mm internal pipe
Water/ weather proof insulation
45º pipe termination
22
Figure 7 - Connection of a Condensate Drainage Pipe to an external Purpose made Soak Away.
Boiler with 75mm sealed condensate trap
Min Ø 19mm
Internal pipe
Min Ø 30mm
Internal pipe
Water/Weather proof insulation
Max 3m external pipework
Boilers without 75mm sealed condensate trap must be fitted with a 75mm trap and visible air break
2 rows of three Ø12mm holes
25mm centres, 50mm from the bottom of the tube, facing away from the house
≥ 500
Limestone chippings
SECTION 6 - COMMISSIONING INSTRUCTIONS
Before commissioning the boiler, the whole gas installation including the meter (if fitted) MUST be purged and tested for gas soundness.
Purge air from the gas installation by the approved methods only.
WARNING. Whilst effecting the required gas soundness test and purging air from the gas installation, open all windows and doors, extinguish naked lights and Do NoT smoke.
Ensure that the flue has been installed correctly and no vents are blocked. Before commencing commissioning, ensure that the Ch system and DHW and cold water system have been flushed. The
Ch system needs to be treated with water treatments that are approved for use with aluminium alloy heat exchangers.
GENERAL
Please Note: The combustion for this appliance has been checked, adjusted and preset at the factory for operation on the gas type defined on the appliance data plate. As part of the commissioning process, the combustion of this appliance must be checked. A flowchart to assist is provided on page 35.
Do NoT adjust the air/gas ratio valve.
having checked:
- That the boiler has been installed in accordance with these instructions.
- The integrity of the flue system and the flue seals, as described in the Flue Installation section.
Proceed to put the boiler into operation as follows:
CHECK THE OPERATIONAL (wORKINg) gAS INLET
PRESSURE
Set up the boiler to operate at maximum rate by opening hot tap to maximum flow.
Gas
Supply
With the boiler operating in the maximum rate condition check that the operational (working) gas pressure at the inlet gas pressure test point complies with the requirements - refer to
“Gas Supply” on page 13.
Gas
Pressure
Test
Point ensure that this inlet pressure can be obtained with all other gas appliances in the property working at maximum.
6.2 CENTRAL HEATING CIRCUIT
Fill the siphon in the condense pipework prior to operating.
In order for the boiler to function correctly, the pressure in the central heating circuit must be between 1 and 1.5 bar on the pressure gauge.
Both the boiler and central heating installation must be purged of any air. The boiler has an auto air vent integral to the pump which must be loose prior to commissioning.
Add an approved flushing solution to one of the radiators.
Fill the central heating circuit using one of the approved methods to 1 bar.
Open radiator vent screws and turn off when water appears.
Turn off the filling method and disconnect.
With the system hot, examine all water connections. The system pressure should not exceed 2.5 bar.
Turn off gas, water and electricity when draining down.
Refill and vent the system, add inhibitor and anti-freeze in the required concentration and check for water leaks.
Check that the condensate operates and the pipework for any leaks.
6.3 INITIAL oPERATIoN
ensure central heating circuit is full and vented, and pressure gauge is reading 1.0 bar.
6.4 DoMESTIC HoT WATER MoDE
Turn the “mode” control knob to tap/radiator icon . ensure all external controls are calling for heat. Set the integral timer to ON.
Display reads “C” then “C” when burner is lit.
ensure all radiators warm up evenly. The Ch temperature can be controlled in between max 80ºC and min 45ºC (flow temp).
Check the DhW functions by turning on a hot water tap.
Close the DhW tap and set the integral timer and external controls to off.
Display will read “0”.
6.1 DoMESTIC HoT WATER
Turn on the main cold water supply.
Fill and vent the installation by turning on and off the various hot water taps in the installation.
Check hot water taps in the installation.
Check for and repair leaks as necessary.
Legend
A. mode Control Knob
B. DhW/Preheat Control
C. Ch Control
D. Boiler Status e. Burner ‘on’ Indication
F. Pre heat on/off Indication status burner e off e max
A mode reset min
B preheat min
C
24
23
22
21
20
19 18
17
16
15
14
5
6
7 8
9
10 max
D preheat
F
23
SECTION 6 - COMMISSIONING INSTRUCTIONS
THE DISPLAy
The user control has one neon and one display to inform the user about the status. The display will show the status of the boiler. The neon will show the status of the flame. If no flame is detected the neon is off. When the flame is detected the neon will be lit permanently.
Below is a list with display function in normal operation.
0
Standby, no demand for heat present.
Boiler is active for central heating.
Boiler is active for domestic hot water.
Boiler is heating up the plate heat exchanger.
Ch circuit water less than 5ºC.
Below is a list with display in fault condition. If the display is flashing with “L” or “F” with alternate numbers / letters refer to page 32.
Boiler is in lockout for a specific error. Display will be blinking, alternating with a number or letter to show which error is detected.
Boiler has a fault for a specific error. Display will be blinking, alternating with a number or letter to show which error is detected.
Service mode
6.5 FINAL CHECKS
Re-light and test for gas soundness.
Set the Ch and DhW temperature knobs to the desired settings.
ensure that the integral timer and/or room thermostat are set to the required settings.
6.6 HANDING oVER
After completing the installation and commissioning of the system the installer should:
• hand the Users Instruction to the owner and emphasise their responsibilities under the relevant national regulations.
• explain and demonstrate the lighting and shut down procedures.
• explain the operation of the boiler and the use and adjustment of the system controls to ensure the greatest possible fuel economy, consistent with the owners heating and hot water requirements.
•
Advise the user of the precautions necessary to prevent damage to the system and to the building in the event of the system remaining in operation during frosty condition.
• explain the function of the boiler fault mode. emphasise that if a fault is indicated, refer to Fault Codes in the User Guide.
• explain and demonstrate system controls, integral timer functions and boiler reset procedure.
IMPoRTANT - Stress the importance of an annual service by a competent gas registered engineer.
24
SECTION 7 - ROuTINE SERvICINg INSTRuCTIONS
7.1 SERVICING SCHEDULE
F or the very latest copy of literature for specification, maintenance practices and parts replacement, visit our website www.morcoproducts.co.uk where you will be able to download the relevant information.
waRNING. Always turn oFF the gas supply at the gas service cock, and switch oFF and disconnect the electricity supply to the appliance before servicing.
Combustion testing must be carried out by a competent person using a combustion analyser conforming to BS7927.
To ensure the continued safe and efficient operation of the appliance it is recommended that it is checked at regular intervals and serviced as necessary. The frequency of servicing will depend upon the installation condition and usage but should be carried out at least annually.
It is the law that any service work must be carried out by a Gas Safe Registered Engineer, or in other countries a qualified and competent Gas Installer.
INSPECTIoN
1. light the boiler and carry out a pre-service check, noting any operational faults.
2.
Check the flue terminal (and terminal guard if fitted) is undamaged and clear of any obstruction.
3. Check all water and gas joints for signs of leakage. Remake any suspect joints ensuring a gas tightness check is carried out if applicable and the water system is correctly refilled, vented and re-pressurised.
CLEANING PRoCEDURE
Note. In order to carry out either servicing or replacement of components the boiler upper and lower front panels must be removed. Refer to Frame 7.2.
1. Clean the main burner. Refer to Frame 7.4.
2.
Clean the heat exchanger & condensate trap/siphon. Refer to
Frames 7.5 & 7.6.
3. Check the main injector for blockage or damage. Refer to
Frame 7.3.
4.
Check that the flue terminal is unobstructed and that the flue system is sealed correctly.
The cleaning procedures are covered more fully in Frames 7.3-7.7 and mUST be carried out in sequence.
IMPoRTANT.
5. After completing the servicing or exchange of components always test for gas tightness.
6. When work is complete the front panels mUST be correctly refitted, ensuring that a good seal is made.
Do NOT OPERaTE the boiler if the upper front panel is not fitted.
7. If, for any reason, the condensate trap/siphon has been removed ensure the trap is refilled with water before reassembling.
8. Check the gas consumption if on metered installations.
9.
Check combustion by connecting the flue gas analyser to the flue gas sampling point as shown in the diagram and measure
CO & CO
2
. (Refer to Section 10, page 35).
If the CO/CO
2 ratio is greater than 0.004 AND the integrity of the complete flue system and combustion circuit seals have been verified and the inlet gas pressure have been verified, then contact morco.
GENERAL
Please Note: During routine servicing, and after any maintenance or change of part of the combustion circuit, the following must be checked:
- The integrity of the flue system and the flue seals,
- The integrity of the boiler combustion circuit and the relevant seals
- The operational (working) gas inlet pressure at maximum rate.
Turn on one or more DhW taps.
- The combustion performance.
CoMPETENCE To CARRy oUT THE CHECK oF
CoMBUSTIoN PERFoRMANCE
Please Note
: BS 6798:2009 Specification for installation and maintenance of gas-fired boilers of rated input not exceeding 70kW net advises that:
- The person carrying out a combustion measurement should have been assessed as competent in the use of a flue gas analyser and the interpretation of the results.
- The flue gas analyser used should be one meeting the requirements of BS7927 or BS-eN50379-3 and be calibrated in accordance with the analyser manufacturers requirements, and
- Competence can be demonstrated, for example, by satisfactory completion of the CPA1 ACS assessment (UK Only), which covers the use of electronic portable combustion gas analysers in accordance with BS7967, Parts 1 to 4.
SERVICE MoDE
To access the service mode:
Using the central heating potentiometer, starting from the 11 o’clock position, move the thumb piece to the maximum position, back to the
11 o’clock position and then finally finish at the maximum position.
The letter “S” will now be displayed.
To toggle to maximum DhW output move the thumb piece up to the 11 o’clock position and then back to maximum. A minimum of 3 seconds will reset the boiler back to normal mode.
Flue Sampling Point
Air Sample
Point
Ensure all caps and seals are re-fitted after use
25
SECTION 7 - ROuTINE SERvICINg INSTRuCTIONS
7.2 BoILER UPPER & LoWER FRoNT PANEL REMoVAL / REPLACEMENT
REMoVAL
1. lift the lower front panel access panel.
2.
Unscrew the two fixing screws, close the access panel to retain the two screws and hinge the lower front panel down into the service position.
3.
Remove the two upper front panel fixing screws, lift the panel and remove.
REPLACEMENT
4. hook the upper panel onto the top retaining clips.
5.
Retain the upper panel with the two fixing screws previously removed ensuring a good seal is made.
6. Swing the lower front panel up and retain with the two screws.
7. Close the lower front panel access panel.
2&6
1&7
3&5
26
7.3 FAN AND VENTURI ASSEMBLy REMoVAL AND CLEANING
1. Disconnect the electrical leads from the fan.
2. Remove the clip from the gas control valve outlet and ease the pipe upwards rotate and then ease down to remove.
3. Remove the extended nut on the fan mounting bracket.
4. lift off fan and venturi assembly.
5. Inspect the injector for blockage or damage.
6. Inspect fan outlet sealing gasket and replace if necessary.
3
5
Injector
2
1
SECTION 7 - ROuTINE SERvICINg INSTRuCTIONS
7.4 BURNER REMoVAL AND CLEANING
1. ensure the sump is fully drained
2. Undo the two screws and remove the sump cover retaining the lower flue manifold.
3. lift the manifold to clear the bottom sealing gasket and remove manifold.
4.
Remove the 2 burner front fixing screws and loosen the 2 rear extended nuts by at least ten turns.
5. lift off the burner from the combustion chamber. To facilitate the removal angle the burner as shown.
IMPoRTANT
The burner head is a ceramic plaque construction. Care must be taken to ensure that the burner is not placed down upon its face as this may cause damage to the ceramic.
6. Brush off any deposits that may be on the ceramic with a SOFT brush.
7. Inspect the sealing gasket around the burner for any signs of damage.
Replace as necessary.
2
3
4
5
2
4
7.5 CLEANING THE CoNDENSATE TRAP/SIPHoN
Note:
Ensure condensate trap is fully drained before removal.
1. Pull off the rubber pipe at the siphon.
2. Turn the siphon clockwise to disengage and lift to remove.
3. Flush out all deposits with clean water.
4. Reassemble in reverse order
Note.
When reassembling ensure the trap is full of water
1
27
28
SECTION 7 - ROuTINE SERvICINg INSTRuCTIONS
7.6 CLEANING THE HEAT ExCHANGER
Note: Ensure the condensate trap/siphon
is fully drained before cleaning. Refer to
Frames 7.5.
1
1.
Remove ignition and flame detection electrodes. Refer to Frames 7.9 & 7.10.
Ignition electrode
2. It is advisable to replace the sump cover prior to the water flush process.
3. Thoroughly flush the heat exchanger by pouring water into the top of the combustion chamber ensuring the full top area is covered.
4. Remove the sump cover and clean loose deposits from the sump.
5. Inspect the ignition and detection electrodes. ensure that they are clean and in good condition - replace if necessary.
6.
Re-fit the ignition and flame detection electrodes. ensure that earth wire is connected to the electrode
7. Check that the ignition and detection gaps are correct. Refer to Frames 7.9 & 7.10.
earth Wire
3
Flame Detection
7.7 REASSEMBLy
Reassemble the boiler in the following order:
1. ensure that the condensate trap/siphon is full of water.
2.
Refit the burner ensuring the sealing gasket is correctly positioned and free from damage (tighten the 4 fixing screws in the sequence A,B,C,D, shown below).
3.
Refit the fan / venturi assembly ensuring the retaining tabs are correctly positioned and the sealing gasket is correctly positioned and free from damage.
4. Reconnect the fan electrical leads.
5.
Remove the sump cover and refit the lower flue manifold as shown.
6.
Refit the sump cover.
7.
Refit the boiler upper and lower front panels.
IMPoRTANT. ensure that the boiler upper front panel is correctly fitted and that a good seal is made. Replace seals as necessary.
8. Turn on the gas supply at the gas service cock.
9. Reconnect the electrical supply.
D
B
5
A
C
SECTION 7 - ROuTINE SERvICINg INSTRuCTIONS
7.8 BURNER REMoVAL
1. Refer to Frame 7.3.
2. Undo the two screws and remove the sump cover.
3. lift the manifold to clear the bottom sealing gasket and remove manifold.
4.
Remove the 2 front fixing screws and loosen the 2 rear extended nuts.
4. lift off the burner from the combustion chamber. To facilitate the removal angle the burner as shown.
5. Fit the new burner, replacing any damaged or deteriorating sealing gasket.
6. Reassemble in reverse order.
7. Check the operation of the boiler.
2
5
3
4
2
7.9 IGNITIoN ELECTRoDE
1. Remove the burner. Refer to Frame 7.8.
2. Check dimensions are correct as in diagram below..
3. Reassemble in reverse order.
FoR REMoVAL:
1. Unplug the ignition lead and remove the earth lead.
2. Remove the 2 retaining screws and remove the electrode.
3. Reassemble in reverse order replacing the gasket if necessary.
Spark Gap
3.5mm
Ignition electrode
Str aig ht ed ge
3mm
4
29
30
SECTION 7 - ROuTINE SERvICINg INSTRuCTIONS
7.10 FLAME DETECTIoN ELECTRoDE
1. Remove the burner. Refer to Frame 7.8.
2. Check dimensions are correct as in diagram below.
3. Reassemble in reverse order.
FoR REMoVAL:
1. Unplug the ignition lead and remove the earth lead.
2. Remove the 2 retaining screws and remove the electrode.
3. Reassemble in reverse order replacing the gasket if necessary.
Str aig ht ed ge
12.5mm
Flame Detection electrode
7.11 FINAL CHECKS
Turn all controls to “oN” position and check their correct functions in both DHW & CH modes.
Additional replacement of parts information can be found on our website. www.morcoproducts.co.uk
SECTION 8 - fACT SHEETS
8 FACT SHEETS
There are a number of detailed fact sheets available for users to download from morco’s website.
Please visit www.morcoproducts.co.uk
The fact sheets can be located in the troubleshooting section and include:
- Winterisation of holiday homes
- Poor hot Water Delivery - Causes and Solutions
- low Central heating Pressure - Fault 1
- Thermostats, Programmers and Thermostatic Radiator Valves
- Combi boiler “cycling”
- Noisy boilers
31
SECTION 9 - faulT COdES
9 FAULT CoDES
DISPLAy CoDE oN BoILER DESCRIPTIoN
BCC Activation Fault
ACTIoN
Restart the appliance - if the boiler fails to operate then please contact morco (if under warranty) or alternatively a Gas Safe Registered engineer if outside of the warranty period. In all other countries contact a Registered Gas Installer.
BCC Fault low Water Pressure
Flame loss
Check system water pressure is between 1 & 1.5bar on the system pressure gauge (G).
To re-pressurise the system see Section 3. If the boiler still fails to operate then please contact morco (if under warranty) or alternatively a Gas Safe Registered engineer if outside of the warranty period. In all other countries contact a Registered Gas Installer.
1. Check other gas appliances in the house are working to confirm a supply is present in the property.
2. If other appliances do not work or there are no other appliances, check the gas supply is on at the meter and/or pre payment meter has credit. If the boiler fails to operate then please contact morco (if under warranty) or alternatively a Gas Safe Registered engineer if outside of the warranty period. In all other countries contact a Registered Gas Installer.
Return temperature greater than flow temperature. Please contact Morco.
Return Thermistor
Fan Fault
Flow Thermistor
Return Thermistor
Outside Sensor Failure low mains Voltage
Restart the appliance - if the boiler fails to operate then please contact morco (if under warranty) or alternatively a Gas Safe Registered engineer if outside of the warranty period. In all other countries contact a Registered Gas Installer.
Restart the appliance - if the boiler fails to operate then please contact morco (if under warranty) or alternatively a Gas Safe Registered engineer if outside of the warranty period. In all other countries contact a Registered Gas Installer.
Restart the appliance - if the boiler fails to operate then please contact morco (if under warranty) or alternatively a Gas Safe Registered engineer if outside of the warranty period. In all other countries contact a Registered Gas Installer.
Restart the appliance - if the boiler fails to operate then please contact morco (if under warranty) or alternatively a Gas Safe Registered engineer if outside of the warranty period. In all other countries contact a Registered Gas Installer.
Contact a qualified electrician or your electricity provider.
Unconfigured PCB Unconfigured PCB. Please contact morco (if under warranty) or alternatively a Gas Safe
Registered engineer if outside of the warranty period. In all other countries contact a
Registered Gas Installer.
Flow Temperature Overheat or No Water Flow
Flame loss
Check system water pressure is between 1 & 1.5bar on the system pressure gauge (G).
To re-pressurise the system see Section 3. If the boiler fails to operate then please contact morco (if under warranty) or alternatively a Gas Safe Registered engineer if outside of the warranty period. In all other countries contact a Registered Gas Installer.
1. Check other gas appliances in the house are working to confirm a supply is present in the property.
2. If other appliances do not work or there are no other appliances, check the gas supply is on at the meter and/or pre payment meter has credit. If the boiler fails to operate then please contact morco (if under warranty) or alternatively a Gas Safe Registered engineer if outside of the warranty period. In all other countries contact a Registered Gas Installer.
5 Boiler Resets in 15 minutes 1. Turn electrical supply to boiler off and on.
2. If the boiler fails to operate please contact morco (if under warranty) or alternatively a
Gas Safe Registered engineer if outside of the warranty period. In all other countries contact a Registered Gas Installer.
False Flame lockout Restart the appliance - if the boiler fails to operate then please contact morco (if under warranty) or alternatively a Gas Safe Registered engineer if outside of the warranty period. In all other countries contact a Registered Gas Installer.
32
33
SECTION 10 - COMBUSTION CHECK
FLOWCHART FOR CO LEVEL AND COMBUSTION RATIO
CHECK ON COMMISSIONING A CONDENSING BOILER
Important Preliminary Information on Checks
The air gas ratio valve is factory-set and must not be adjusted DURING COMMISSIONING.
PRIOR TO CO LEVEL AND COMBUSTION RATIO CHECK
The installation instructions must have been followed, gas type verified and gas supply pressure / gas rate checked as required prior to commissioning.
As part of the installation process, ESPECIALLY WHERE A FLUE HAS BEEN FITTED BY PERSONS OTHER THAN
THE BOILER INSTALLER, visually check the integrity of the whole flue system to confirm that all components are correctly assembled, fixed and supported. Check that maximum flue lengths have not been exceeded and all guidance has been followed (e.g. Gas Safe Register Technical Bulletin (TB) 008 where chimney/flues are in voids).
The ECGA should be of the correct type, as specified by BS 7967.
Prior to its use, the ECGA should have been maintained and calibrated as specified by the manufacturer. The installer must have the relevant competence for use of the analyser.
Check and zero the analyser IN FRESH AIR in accordance with the analyser manufacturer’s instructions.
KEY:
CO = carbon monoxide
CO
2
= carbon dioxide
O2 = oxygen
Combustion Ratio = The CO reading measured in ppm divided by the CO
2
reading first converted to ppm
ppm = parts per million
GS(I&U)R = Gas Safety (Installation and Use) Regulations
34
*Setting to Minimum Rate:
1. Turn the Ch temperature control knob to the 11 O’clock position.
2. Create a Ch demand by ensuring that the system controls are requesting heat and the boiler mode
Knob is in the Winter Position.
3. Within an overall time of 3 seconds, turn the Ch temperature control knob fully clockwise, back to
11 O’clock and then fully clockwise again.
4. “S” will be shown on the display and the boiler output will be reduced to minimum
5. The boiler will remain at minimum rate for 5 minutes before reverting to normal operation
SECTION 10 - COMBUSTION CHECK
Start
Set Boiler to Maximum Gas Rate
In accordance with boiler instructions,
(by fully turning on hot tap) set boiler to operate at maximum rate (full load condition). Allow sufficient time for combustion to stabilise.
Note. Do not insert analyser probe during this period to avoid possible flooding of sensor.
Carry Out Flue Integrity Check Using Analyser
Insert analyser probe into air inlet test point (where available) and allow readings to stabilise.
Note. Where no air inlet test point is provided then a flue integrity check with the analyser is not possible. The installer should verify that flue integrity has been visually checked in accordance with the “Prior to CO level and
combustion ratio check” (see opposite page) before proceeding to the
“check CO level and combustion ratio at maximum rate” stage below.
Verify Flue Integrity
Analyser readings indicate that combustion products and inlet air must be mixing. Further investigation of the flue is therefore required.
Check that flue components are assembled, fixed and supported as per instructions. Check that flue and flue terminal are not obstructed.
No
Is
O2 more than or equal to 20.6% OR CO
2 less than or equal to
0.2%?
Yes
Is
O
2
more than or equal to 20.6% OR CO
2 less than or equal to
0.2%?
No
Yes
Turn off appliance and call Morco Technical Helpline for advice
The appliance must not be commissioned until problems are identified and resolved. If commissioning cannot be fully completed, the appliance must be disconnected from the gas supply in accordance with GSIUR.
Check that no seals, e.g. Those on flue extensions, have been displaced during installation. Rectify if necessary.
Is
CO level less than 350ppm AND CO/CO
2 ratio less than
0.0040?
Yes
Check CO level and Combustion Ratio at Maximum Gas Rate
With boiler still set at maximum gas rate, insert analyser probe into flue gas sampling point. Allow readings to stabilise before recording.
No
Is
CO level less than 350ppm AND CO/CO
2 ratio less than
0.0040?
Yes
Set Boiler to Minimum Gas Rate
(*see opposite page)
In accordance with boiler instructions, set boiler to operate at minimum rate (to minimum load condition).
Allow sufficient time for combustion to stabilise.
No
Check CO and Combustion Ratio at Minimum Gas Rate
With boiler set at minimum rate, insert analyser probe into flue gas sampling point. Allow readings to stabilise before recording.
Turn off Appliance and Call Morco Technical Helpline
The appliance must not be commissioned until problems are identified and resolved. If commissioning cannot be fully completed, the appliance must be disconnected from the gas supply in accordance with GS(I&U)R. NOTE:
Check and record CO level and combustion ratio at both maximum AND minimum rate before contacting Ideal.
No
Is
CO level less than 350ppm AND CO/CO
2 ratio less than
0.0040?
Yes
Boiler is Operating Satisfactorily
No further actions required.
Ensure test points are capped, boiler case is correctly replaced and all other commissioning procedures are completed. Complete Benchmark
Checklist, recording CO and combustion ratio readings as required.
35
SECTION 11 - WARRANTY
WARRANTy CoNDITIoNS
The boiler is guaranteed against manufacturing defects for a period of two years from the date of first commissioning. However the guarantee is subject to proof of commissioning in accordance with the Gas Safety (Installation and Use) act 1998.
The guarantee does NoT cover the following issues:
1. Frost damage to any part of the boiler containing water during freezing conditions.
2. The removal of sludge or hard water scale due to lack of antifreeze/inhibitor
3. Damage to electronics caused by a defective electrical supply.
4. Damage or failure caused by insect contamination or blocked water filters.
5. loss of pressure within the heating system not caused directly by the boiler.
6. Incorrect operation of the boiler caused by defective outlets such as thermostatic mixers or mono block mixer taps.
7. Damage caused by unauthorised modifications to the boiler from original specifications.
36
For more detailed servicing information, workshop manuals, technical advice, spare parts, product training, please phone us on 01482 325456 or contact us at the address below:
MoRCo PRoDUCTS LTD morco house, Riverview Road, Beverley, east yorkshire hU17 0lD
Tel: 01482 325456 FAX: 01482 212869 emAIl: [email protected]
WeBSITe: www.morcoproducts.co.uk
advertisement
Related manuals
advertisement