E300 Electronic Overload Relay


Add to my manuals
36 Pages

advertisement

E300 Electronic Overload Relay | Manualzz

Selection Guide

E300 Electronic Overload Relay

Bulletin Numbers 193, 592

E300 Electronic Overload Relay

What’s Inside

Topic

Bulletin 193/592-E300 Overview

Bulletin 193/592-E300 Product Selection

Sensing Modules

Control Modules

Accessories

Bulletin 193/592-E300 Specifications

Bulletin 193/592-E300 Approximate Dimensions

15

25

12

13

Page

3

11

11

2

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

Overview

Bulletin 193/592-E300 Overview

The E300 Electronic Overload Relay is the newest technology for overload protection. Its modular design, communication options, diagnostic information, simplified wiring, and integration into Logix make this the ideal overload for motor control applications in an automation system.

E300 Electronic Overload Relays provide the following benefits:

Intelligent motor control (EtherNet/IP enabled)

Scalable solution

Diagnostic Information

Integrated I/O

Adjustable trip class 5…30

Wide current range

Test/Reset button

Programmable trip and warning settings

True RMS current/voltage sensing (50/60 Hz)

Protection for single- and three-phase motors

NOTE: Your order must include 1) the Cat. No. of the sensing module, control module, and communication module selected, and 2)if required, Cat. No. of any accessories.

Standards Compliance and Certifications

Certifications Standards Compliance

UL508

UL1053 (Class I and Class II)

UL 60947-1

UL 60947-4-1

EN 60947-1

EN 60947-4-1

CSA22.2, No. 14

CSA22.2, No. 60947-1

CSA22.2, No. 60947-4-1

GB 14048.4

UL Listed

CE Marked

CSA Certified

CCC

KCC

Product Overview

The E300 consists of three modules: sensing, control and communications. Users have choices in each of the three with additional accessories to tailor the electronic overload for their application’s exact needs.

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

3

Overview

Sensing Module

Sensing Options

Voltage/current/ground fault

Current/ground fault

Current

Current Range [A]

0.5…30

6…60

10…100

Control Module

Control Voltage

110…120V AC, 50/60 Hz

220…240V AC, 50/60 Hz

24V DC

(1) Includes PTC thermistor and external ground fault.

Inputs

4

4

6

I/O

Relay Outputs

3

3

3

Inputs

2

I/O and Protection

(1)

Relay Outputs

2

2

4

2

2

Communication Module

EtherNet/IP

Expansion Digital I/O

Users can add up to four additional expansion digital modules to the E300 expansion bus.

4 inputs/2 relay outputs

24V DC

120V AC

240V AC

Expansion Analog I/O

Users can add up to four additional expansion analog modules to the E300 expansion bus.

3 universal analog inputs/1 analog output

0…10V

0…5V

1…5V

0…20 mA

4…20 mA

RTD (2-wire or 3-wire)

0…150

Ω

0…750

Ω

0…3000

Ω

0…6000

Ω

(PTC/NTC)

4

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

Overview

Expansion Power Supply

When more than one expansion digital module and one operator station are added to the E300 expansion bus, an expansion power supply is needed to supplement power for the additional modules. One expansion power supply will power a fully loaded E300 expansion bus.

120/240V AC

24V DC

Expansion Operator Station

One operator station can be added to the E300 expansion bus to be used as a user interface device. The operator stations provide E300 status LEDs and function keys for motor control. The operator stations also support CopyCat™, which allows user to upload and download E300 configuration parameters.

Control station

Diagnostic station

Thermal Overload

Thermal Utilization

The E300 Electronic Overload Relay provides overload protection through true RMS current measurement of the individual phase currents of the connected motor. Based on this information, a thermal model that simulates the actual heating of the motor is calculated. Percent of thermal capacity utilization (%TCU) reports this calculated value and can be read via a communications network. An overload trip occurs when the value reaches 100%.

Adjustable Settings

Thermal overload protection setup is accomplished simply by programming the motor’s full load current (FLC) rating and the desired trip class (5…30). Programming of the actual values through software programming ensures the accuracy of the protection.

Thermal Memory

The E300 Electronic Overload Relay includes a thermal memory circuit designed to approximate the thermal decay for a trip class 20 setting. This means that the thermal model of the connected motor is maintained at all times, even if the supply power is removed.

Reset Modes

This flexibility allows the end-user in the ability to select between manual and automatic reset for an overload trip, allowing for broad application. The point of reset is user adjustable from 1…100% TCU.

Time to Trip

During an overload condition, the E300 Electronic Overload Relay provides an estimated time to trip that is accessible via a communications network. This allows corrective action to be taken so that production may continue uninterrupted.

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

5

6

Overview

Time to Reset

Following an overload trip, the E300 Electronic Overload Relay will not reset until the calculated percentage of thermal capacity utilization falls below the reset level. As this value decays, the time to reset, which is accessible via a communications network, is reported.

Thermal Warning

The E300 Electronic Overload Relay provides the capability to alert in the event of an impending overload trip. A thermal warning bit is set in the Current Warning Status when the calculated percentage of thermal capacity utilization exceeds the programmed thermal warning level, which has a setting range of 0…100% TCU.

Two-Speed Protection

The E300 Electronic Overload Relay offers a second FLA setting for 2-speed motor protection. What used to require two separate overload relays - one for each set of motor windings - can now be accomplished with one device. Improved protection is delivered as thermal utilization is maintained in one device during operation in both speeds.

Overtemperature Protection (PTC and RTD)

The E300 Electronic Overload Relay provides motor overtemperature protection with the added provision for monitoring embedded positive temperature coefficient (PTC) thermistors with the E300 Control Module and resistance temperature detectors (RTD) with the E300 Analog Expansion Module. When the monitored PTC thermistors or RTD sensors exceed the programmed resistance level, the E300 Electronic Overload Relay can issue a Trip and/or Warning event.

Phase Loss

The E300 Electronic Overload Relay offers configurable phase loss protection, allowing the installer to enable or disable the function plus set a time delay setting, adjustable from 0.1…25.0 seconds. The trip level is factory-set at a current imbalance measurement of 100%.

Ground (Earth) Fault

The E300 Electronic Overload Relay incorporates zero sequence (core balance) sensing into its design for low level (arcing) ground fault detection. Trip and warning settings are adjustable from 20 mA…5.0 A. For devices rated greater than 200 A and for ground fault detection less than 0.5 A, the external core balance current transformer accessory is required. Class I and Class II protection are provided as defined by UL1053. The E300 Electronic Overload Relay provides a max. trip-inhibit setting, offering flexibility to prevent tripping when the ground fault current magnitude exceeds 6.5 A. This can be useful to guard against the opening of the controller when the fault current could potentially exceed the controller's interrupting capacity rating.

Note: The E300 Electronic Overload Relay is not a Ground Fault Circuit Interrupter for personnel protection as defined in article

100 of the U.S. National Electric Code.

Stall

"Stall" is defined as a condition where the motor is not able to reach full-speed operation in the appropriate amount of time required by the application. This can result in motor overheating as current draw is in excess of the motor’s full load current

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

Overview rating. The E300 Electronic Overload Relay provides user-adjustable stall protection. The trip setting has a range of 100…600%

FLA, and the enable time is adjustable up to 250 seconds.

Jam (Overcurrent)

The E300 Electronic Overload Relay can respond quickly to take a motor off-line in the event of a mechanical jam, thereby reducing the potential for damage to the motor and the power transmission components. Trip adjustments include a trip setting adjustable from 50…600% FLA and a trip delay time with a range of 0.1…25.0 seconds. A separate warning setting is adjustable from 50…600% FLA.

Underload (Undercurrent)

A sudden drop in motor current can signal conditions such as:

Pump cavitation

Tool breakage

Belt breakage

For these instances, rapid fault detection can help minimize damage and aid in reducing production downtime.

Additionally, monitoring for an underload event can provide enhanced protection for motors that are coded by the medium handled (e.g., submersible pumps that pump water). Such motors can become overheated despite being underloaded. This can result from an absence or an insufficient amount of the medium (due to clogged filters, closed valves, etc.).

The E300 Electronic Overload Relay offers underload trip and warning settings adjustable from 10…100% FLA. The trip function also includes a trip delay time with a range of 0.1…25.0 seconds.

Current Imbalance (Asymmetry)

The E300 Electronic Overload Relay offers current imbalance trip and warning settings adjustable from 10…100%. The trip function also includes a trip delay time with a range of 0.1…25.0 seconds.

Remote Trip

The remote trip function allows an external device (e.g., a vibration sensor) to induce the E300 Electronic Overload Relay to trip.

External device relay contacts are wired to the E300 Electronic Overload Relay discrete inputs. These discrete inputs are configurable with an option for assigning the remote trip function.

Voltage Protection

The E300 sensing module with voltage, current, and ground fault current will provide the user with enhanced current-based motor protection with the addition of voltage protection. With this option, users can protect against voltage issues (e.g., undervoltage, voltage imbalance, phase loss, frequency, and phase rotation).

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

7

Overview

Power Protection

While the motor is powering a load, the E300 sensing module with voltage, current, and ground fault current, will also protect the motor based on power. This option will monitor and protect for both excessive and low real power (kW), reactive power

(kVAR), apparent power (kVA), and power factor for a specific application (e.g., pump applications).

Analog Protection

The E300 analog expansion module allows you to protect against over-analog readings from analog-based sensors

(overtemperature, overflow, overpressure, etc.)

Current Monitoring Functions

The E300 Electronic Overload Relay allows the user to monitor the following operational data over a communications network:

Individual phase currents — in amperes

Individual phase currents — as a percentage of motor FLC

Average current — in amperes

Average current — as a percentage of motor FLC

Percentage of thermal capacity utilized

Current imbalance percentage

Ground fault current

Voltage, Power, and Energy Monitoring

The E300 sensing module with voltage, current, and ground fault current can be included in a company’s energy management system. This option will provide voltage, current, power (kW, kVAR, and kVA), energy (kWh, kVARh, kVAh, kW Demand, kVAR

Demand, and kVA Demand), and power quality (power factor, frequency, and phase rotation) information down at the motor level.

Diagnostic Functions

The E300 Electronic Overload Relay allows the user to monitor the following diagnostic information over a communications network:

Device status

Trip status

Warning status

Time to an overload trip

Time to reset after an overload

History of past five trips

History of past five warnings

Hours of operation

Number of starts

Trip snapshot trip

8

Status Indicators

The E300 Electronic Overload Relay provides the following LED indicators:

Power — This green/red LED indicates the status of the overload relay.

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

Overview

TRIP/WARN — This LED flashes a yellow code under a warning condition and a red code when tripped.

Inputs/Outputs

Inputs allow the connection of such devices as contactor and disconnect auxiliary contacts, pilot devices, limit switches, and float switches. Input status can be monitored via the network and mapped to a controller’s input image table. Inputs are rated

24V DC, 120V AC, or 240V AC and are current sinking. Power for the inputs is sourced separately with convenient customer sources at terminal A1. Relay contact outputs can be controlled via the network or DeviceLogix function blocks for performing such tasks as contactor operation.

Test/Reset Button

The Test/Reset button, located on the front of the E300 Electronic Overload Relay, allows the user to perform the following:

Test — The trip relay contact will open if the E300 Electronic Overload Relay is in an untripped condition and the Test/

Reset button is pressed for 2 seconds or longer.

Reset — The trip relay contact will close if the E300 Electronic Overload Relay is in a tripped condition, supply voltage is present, and the Test/Reset button is pressed.

Single/Three-Phase Operation

The E300 Electronic Overload Relay can be applied to three-phase as well as single-phase applications. A programming parameter is provided for selection between single- and three-phase operation. Straight-through wiring is afforded in both cases.

EtherNet/IP Communications

The E300 EtherNet/IP communication module has two RJ45 ports that act as an Ethernet switch to support a star, linear, and ring topology and supports the following:

2 concurrent Class 1 connections [1 exclusive owner + (1 input only or 1 listen only)]

6 simultaneous Class 3 connections (explicit messaging)

Embedded web server

SMTP server for trip and warning events (email and text messaging)

Embedded EDS file

RSLogix 5000 add-on profile

For more information on operation and maintenance of this product, please reference the user manual, publication 193-UM015.

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

9

Overview

Notes:

10

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

Product Selection

Bulletin 193/592-E300 Product Selection

Sensing Modules

Description

Current

Current/Ground Fault

Mounting Options

IEC Contactors

DIN Rail / Panel Mount Power

Terminals

DIN Rail / Panel Mount Power

Terminals.

Directly replaces 193-ECPM_

DIN Rail / Panel Mount Pass-thru

NEMA Contactors

IEC Contactors

DIN Rail / Panel Mount Power

Terminals

DIN Rail / Panel Mount Power

Terminals.

Directly replaces 193-ECPM_

DIN Rail / Panel Mount Pass-thru

NEMA Contactors

Current Range [A]

0.5…30

10…100

0.5…30

6…60

10…100

0.5…30

6…60

10…100

6…60

10…100

0.5…30

6…60

10…100

0.5…30

6…60

0.5…30

10…100

0.5…30

6…60

10…100

0.5…30

6…60

10…100

6…60

10…100

0.5…30

6…60

10…100

0.5…30

6…60

For Use With

100-C09…C23

100-C30…C55

100-C30…C55

100-C60…100-C97

All contactors and external current transformers

All contactors

All contactors and external current transformers.

All contactors

All contactors and external current transformers

All contactors

NEMA Size 0…2

NEMA Size 3

100-C09…C23

100-C30…C55

100-C30…C55

100-C60…100-C97

All contactors

NEMA Size 0…2

NEMA Size 3

592-ESM-I-100A-S3

193-ESM-IG-30A-C23

193-ESM-IG-30A-C55

193-ESM-IG-60A-C55

193-ESM-IG-100A-C97

193-ESM-IG-30A-T

193-ESM-IG-60A-T

193-ESM-IG-100A-T

193-ESM-IG-30A-E3T

193-ESM-IG-60A-E3T

193-ESM-IG-100A-E3T

193-ESM-IG-30A-P

193-ESM-IG-60A-P

193-ESM-IG-100A-P

592-ESM-IG-30A-S2

592-ESM-IG-60A-S2

592-ESM-IG-100A-S3

Cat. No.

193-ESM-I-30A-C23

193-ESM-I-30A-C55

193-ESM-I-60A-C55

193-ESM-I-100A-C97

193-ESM-I-30A-T

193-ESM-I-60A-T

193-ESM-I-100A-T

193-ESM-I-30A-E3T

193-ESM-I-60A-E3T

193-ESM-I-100A-E3T

193-ESM-I-30A-P

193-ESM-I-60A-P

193-ESM-I-100A-P

592-ESM-I-30A-S2

592-ESM-I-60A-S2

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

11

Product Selection

Description Mounting Options

IEC Contactors

DIN Rail / Panel Mount Power

Terminals

Voltage/Current/Ground Fault

DIN Rail / Panel Mount Power

Terminals.

Directly replaces 193-ECPM_

DIN Rail / Panel Mount Pass-thru

NEMA Contactors

Current Range [A]

0.5…30

6…60

10…100

0.5…30

6…60

10…100

0.5…30

6…60

10…100

0.5…30

0.5…30

6…60

10…100

For Use With

100-C09…C23

100-C30…C55

100-C30…C55

100-C60…100-C97

All contactors

External current and potential transformers

NEMA Size 0…2

NEMA Size 3

Control Modules

Description

I/O Module

I/O and Protection Module.

Thermistor (PTC) and External

Ground Fault Current

(1)

No. of Inputs/Outputs

6 in/3 out

4 in/3 out

4 in/3 out

4 in/2 out

2 in/2 out

2 in/2 out

(1) Requires Core Balanced Ground Fault Sensor Cat. No. 193-CBCT_.

Rated Control Voltage [V]

24V DC

110…120V AC, 50/60 Hz

220…240V AC, 50/60 Hz

24V DC

110…120V AC, 50/60 Hz

220…240V AC, 50/60 Hz

Cat. No.

193-EIO-63-24D

193-EIO-43-120

193-EIO-43-240

193-EIOGP-42-24D

193-EIOGP-22-120

193-EIOGP-22-240

Communication Modules

Description

EtherNet/IP

Cat. No.

193-ECM-ETR

Expansion Modules

Description

Digital Expansion Module, 24V DC

Digital Expansion Module, 120V AC

Digital Expansion Module, 240V AC

Analog Expansion Module: mA, V, RTD, and Resistance

Expansion Power Supply

Starter Control Station with 3-Meter Cable

Starter Diagnostic Station with 3-Meter Cable

(1) Module requires control module firmware v3.000 or higher.

No. of Inputs/Outputs

4 in/2 out

4 in/2 out

4 in/2 out

3 universal in/1 out

Rated Control Voltage [V]

24V DC

110…120V AC, 50/60 Hz

220…240V AC, 50/60 Hz

24V DC

110…240V AC, 50/60 Hz

Cat. No.

193-ESM-VIG-30A-C23

193-ESM-VIG-30A-C55

193-ESM-VIG-60A-C55

193-ESM-VIG-100A-C97

193-ESM-VIG-30A-T

193-ESM-VIG-60A-T

193-ESM-VIG-100A-T

193-ESM-VIG-30A-E3T

193-ESM-VIG-60A-E3T

193-ESM-VIG-100A-E3T

193-ESM-VIG-30A-CT

592-ESM-VIG-30A-S2

592-ESM-VIG-60A-S2

592-ESM-VIG-100A-S3

Cat. No.

193-EXP-DIO-42-24D

193-EXP-DIO-42-120

193-EXP-DIO-42-240

193-EXP-AIO-31

(1)

193-EXP-PS-DC

193-EXP-PS-AC

193-EOS-SCS

193-EOS-SDS

(1)

12

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

Accessories

Description

Contactor Coil Module

1-Meter Expansion Module Cable

3-Meter Expansion Module Cable

Core Balanced Ground Fault Sensor

Replacement Connectors

Panel Mount Screw Adapters

(1) Sold in multiples of 10. Order quantity of 10 to receive a package of 10 pieces.

(2) Sold in multiples of 10. Order quantity of 1 to receive a package of 10 pieces.

For Use With

100-C09…100-C23 contactors

100-C30…100-C55 contactors

100-C60…100-C97 contactors

193-EIOGP-42-24D

193-EIOGP-22-120

193-EIOGP-22-240

193-EIO-63-24D

193-EIO-43-120

193-EIO-43-240

193-EIOGP-42-24D

193-EIOGP-22-120

193-EIOGP-22-240

193-ESM-VIG-30A-CT

193-EXP-DIO-42-24D

193-EXP-DIO-42-120

193-EXP-DIO-42-240

193-EXP-AIO-31

193-EXP-PS-DC

193-EXP-PS-AC

193-ESM-I-30A-T

193-ESM-I-60A-T

193-ESM-IG-30A-T

193-ESM-IG-60A-T

193-ESM-VIG-30A-T

193-ESM-VIG-60A-T

193-ESM-I-30A-P

193-ESM-I-60A-P

193-ESM-IG-30A-P

193-ESM-IG-60A-P

193-ESM-VIG-30A-CT

193-ESM-I-100A-T

193-ESM-IG-100A-T

193-ESM-VIG-100A-T

193-ESM-I-100A-P

193-ESM-IG-100A-P

Product Selection

Cat. No.

193-EIO-CM-C23

193-EIO-CM-C55

193-EIO-CM-C97

193-EXP-CBL-1M

193-EXP-CBL-3M

193-CBCT1

193-CBCT2,

193-CBCT3

193-CBCT4

193-NCIO-63-CNT

193-NCIO-43-CNT

193-NCIOGP-42-CNT

193-NCIOGP-22-CNT

193-NCSM-VIG-CNT

193-NCXP-DIO-CNT

193-NCXP-AIO-CNT

193-NCXP-PS-CNT

140M-C-N45

(1)

193-ESM-SA-100

(2)

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

13

Product Selection

Notes:

14

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

Specifications

Bulletin 193/592-E300 Specifications

Wiring Diagrams

Figure 1 - Control Module

193-EIO-_ _-_ _ _ 193-EIOGP-_ _-_ _ _

A1 R03 R04 A2 IN0

IN1

RELAY 0

Additional Inputs for 193-EIO-63-_ _ _

A1 R03 R04 A2 IN0

IN1

RELAY 0

Additional Inputs for 193-EIOGP-42-_ _ _

A1 A1 A2

(+) (-)

IN2 IN3 IN4 IN5

RELAY 1 RELAY 2

PE R13 R14 R23 R24 A1 A1 A2

(+) (-)

IN2 IN3 IT1

PTC

IT2 PE

R13

RELAY 1

R14 S1

Ground

Fault

S2

+

t

Figure 2 - Expansion Digital I/O Modules 193-EXP-DIO-__

R04 R14 RC3

IN2 IN3

IN0 IN1 INC

+

Source

-

IN0 IN1 IN2 IN3 INC

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

15

Specifications

Figure 3 - Expansion Analog I/O Module 193-EXP-AIO-31

OUT+OUT-

IN2+ IN2- RS2

+

24V DC

Power

Supply

-

Analog Current Input

Current

Input

Device

INx+

INx-

IN1+ IN1- RS1

2 Wire RTD/Resistance

INx+

IN0+ IN0- RS0

INx-

Analog Voltage Input

+V INx+

-V

INx-

3 Wire RTD

INx+

INx-

RSx

Analog Voltage or Current Output

Out+

Out-

+

Device

-

Figure 4 - Expansion Power Supplies 193-EXP-PS-__

A1 A2

A1 A2

Electrical Specifications

Motor/Load Ratings

Terminals

Rated Insulation Voltage U i

Rated Operating Voltage U e,

IEC

Rated Operating Voltage U e,

UL

Rated Impulse Voltage (U imp

Rated Operating Current

I

Rated Frequency e

)

1/L1, 3/L2, 5/L3, 2/T1, 4/T2, 6/T3

690V AC

690V AC

690V AC

6 kV

See product selection table

45…65 Hz

(1)

(1) Exception: Any E300 Overload Relay that uses an external ground fault sensor is limited to

50/60 Hz detection.

16

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

Control Module Power Supply Ratings

Rated Supply Voltage (U s

)

Operating Range

Maximum Inrush Current

Maximum Power Consumption

E300:

E300 with expansion:

Maximum Power Interruption Time

V min

:

V max

:

24V DC

11…30V DC

3 A for 30 ms

5 ms

5 ms

120V AC

85…132V AC

10 A for 1 ms

6 W

8 W

10 ms

10 ms

240V AC

159…265V AC

8 A for 3 ms

10 ms

10 ms

Output Relay Ratings (Control Module and Expansion Digital Module)

Relay 0:

Relay 1:

Relay 2:

Type of Contacts

Rated Thermal Current (

I

the

)

Rated Insulation Voltage (U i

)

Rated Operating Voltage (U e

)

Rated Operating Current (

I

e

Minimum Operating Current

Rating Designation

Utilization Category

Short Circuit Current Rating

)

Resistive Load Rating (p.f. = 1.0)

Inductive Load Rating (p.f. = 0.4) (L/R = 7 ms)

Recommended Control Circuit Fuse

Rated Number of Operations

Relay 0, Relay 1, and Relay 2:

W/100-C09…100-C55

W/100-C60…100-C97

W/NEMA Size 0…2

W/NEMA Size 3

R03/R04

R13/R14

R23/R24

Form A SPST - NO

5 A

300V AC

250V AC

3 A (@120V AC), 1.5 A (@240V AC)

0.25 A (@110V DC), 0.1 A (@220V DC)

10 mA @ 5V DC

B300

AC-15

5 A, 250V AC

5 A, 30V DC

2 A, 250V AC

2 A, 30V DC

1,000 A

KTK-R-6

(6 A, 600 V)

5,000,000

2,500,000

1,000,000

300,000

Specifications

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

17

Specifications

Input Ratings (Control Module and Expansion Digital Module)

Input 0:

Input 1:

Input 2:

Input 3:

Input 4:

Input 5:

Supply Voltage

Type of Inputs

On-State Voltage

On-State Current (turn-on)

Off-State Voltage

Off-State Current

Transition Voltage

Transition Current

24V DC

11V DC

2 mA

5V DC

1.5 mA

5...11V DC

1.5...2.0 mA

IN0

IN1

IN2

IN3

IN4

IN5

120V AC

Current Sinking

74V AC

5 mA

20V AC

2.5 mA

20…74V AC

2.5…5 mA

240V AC

159V AC

5 mA

40V AC

2.5 mA

40…159V AC

2.5…5 mA

Analog I/O Ratings (Expansion Analog Module)

Bus to In/Out isolation

Group Isolation (In/Out)

Channel to channel isolation

Max. current draw

Max. Surge Current at Power-Up

Input ranges

Input Impedance Tolerances

Input resolution

Output ranges

Output Resolution

Voltage Output Load

Current Output Load

Output Impedance

Output Open Circuit detect

Max Inductive Load (current outputs)

Max Capacitive Load (voltage outputs)

Module

1000V AC = 1415V DC (1 min.)

1000V AC = 1415V DC (1 min.)

None

85 mA at 24V

0.5 A @ 24V DC for 1 ms

Input Channels

Current: 0…20 mA, 4…20 mA

Voltage: 0…10V, 1…5V, 0…5V

RTD: 100

Ω

, 200

Ω

, 500

Ω and 1000

Ω

PT385 and Pt3916, 100

Ω

Ni618 and Ni672, 10

Ω

Cu 426, 604

Ω

NiFe 518

Resistance: 0-150

Ω

, 0-750

Ω

, 0-3000

Ω

, 0-6000

Ω

Current Impedance: 249

Ω

± 1.0%

Voltage Impedance:

10M at 10V in

4M at 5V in

680k at 1V in

12 bits

Output Channels

Current: 0…20 mA, 4…20 mA

Voltage: 0…10V, 0…5V, 1…5V

12 bits

2k

Ω

min. at 10V output (5 mA max.), including wire resistance

50

Ω minimum to 750

Ω

max

Current: >1M

Ω

, Voltage: <1

Ω

Current outputs: O.C. detect supported

Voltage outputs: O.C. detect not supported

0.1 mH

1

μ

F

18

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

Specifications

Thermistor/PTC Input Ratings (PTC only)

Terminals

Type of Control Unit

Maximum Number of Sensors

Maximum Cold Resistance of PTC Sensor Chain

Trip Resistance

Reset Resistance

Short-circuit Trip Resistance

Maximum Voltage @ PTC Terminals (R

PTC

= 4 k

Ω

)

Maximum Voltage @ PTC Terminals (R

PTC

=open)

Response Time

IT1, IT2

Mark A

6

1500

Ω

3400

Ω

± 150

Ω

1600

Ω

± 100

Ω

25

Ω

± 10

Ω

7.5V DC

30V DC

800 ms

Low Voltage Directive

The E300 Electronic Overload Relay expansion digital modules are tested to comply with EN60947-5-1 Low-voltage switchgear and controlgear Part 5-1: Control circuit devices and switching elements.

Expansion Digital I/O Modules

Expansion Digital I/O Modules

Digital Output Rated Operational Voltage (U e

)

Digital Output Rated Insulation Voltage (U i

)

Rated Impulse Withstand Voltage (U imp

)

Conditional Short-Circuit Current

Recommended Control Circuit Fuse

Utilization Category

Pollution Degree

193-EXP-DIO-42- 24D

250V AC

2000V rms

for 1 s

NA

1000 A

KTK-R (6 A, 600V)

AC15, DC13

3

Expansion Power Supply Modules

Expansion Digital I/O Modules

Rated Operational Voltage (U e

)

Rated Insulation Voltage (U i

)

Rated Impulse Withstand Voltage (U imp

)

Conditional Short-Circuit Current

Protection against Short Circuits

Utilization Category

Pollution Degree

193-EXP-PS-AC

100…250V AC

2640V rms

for 1 s

4 kV

NA

NA

NA

3

193-EXP-DIO-42- 120

250V AC

2000V rms

for 1 s

NA

1000 A

KTK-R (6 A, 600V)

AC15, DC13

3

193-EXP-PS-DC

21.6…26.4V DC

500V for 60s

0.5 kV

NA

NA

NA

3

193-EXP-DIO-42- 240

250V AC

2000V rms

for 1 s

NA

1000 A

KTK-R (6 A, 600V)

AC15, DC13

3

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

19

Specifications

Environmental Specifications

Note: The E300 Electronic Overload Relay expansion power supplies (Cat. Nos. 193-EXP-PS-AC and 193-EXP-PS-DC) surrounding air temperature must not exceed 55 °C (131 °F).

Ambient Temperature

Storage

Operating (open)

Operating (enclosed)

–40…+85 °C (–40…+185 °F)

–20…+55 °C (–4…+131 °F)

–20…+40 °C (–4…+104 °F)

Humidity

Operating

Damp Heat – Steady State (per IEC 68-2-3)

Damp Heat – Cyclic (per IEC 68-2-30)

Cooling Method

Vibration (per IEC 68-2-6)

Shock (per IEC 68-2-27)

Maximum Altitude

Pollution Environment

Terminal Marking

Degree of Protection

5…95% Non-condensing

92% r.h., 40 °C (104 °F), 56 days

93% r.h., 25 °C/40 °C (77 °F/104 °F), 21 Cycles

Natural convection

2.5 G operating, 5 G non-operating

30 G

2000 m

(1)

Pollution Degree 3

EN 50012

IP20

(1) Exception: Any E300 Overload Relay that uses an external ground fault sensor is limited to 50/60 Hz detection.

Electromagnetic Compatibility Specifications

Test Level

Performance Criteria

Electrostatic Discharge Immunity

8kV Air Discharge, 6kV Contact Discharge

1

(1)(2)

Test Level

Performance Criteria

Radio Frequency Immunity

10V/m

1

(1)(2)

Electrical Fast Transient/Burst Immunity

Test Level

Performance Criteria

4kV (Power), 2kV (Control & Comm)

1

(1)(2)

Test Level

Performance Criteria

Radiated Emissions

Conducted Emissions

Surge Immunity

2kV (L-E), 1kV (L-L)

1

(1)(2)

Class A

Class A

(1) Performance Criteria 1 requires the DUT to experience no degradation or loss of performance

(2) Environment 2

20

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

Protection

General Protection

Overload

Phase Loss

Ground Fault

Stall

Jam

Underload

Thermistor (PTC)

Current Imbalance

Communication Fault

Communication Idle

Remote Trip

Blocked Start/Start Inhibit

Under Voltage L-L

Over Voltage L-L

Voltage Unbalance

Phase Rotation

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Trip Warning

Yes Yes

Yes

Yes

No

Yes

No

Yes

Yes

Yes

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

Overload Protection

Type of Relay

Nature of Relay

FLA Setting

Trip Rating

Trip Class

Reset Mode

Overload Reset Level

Ambient Compensated Time-Delay Phase Loss Sensitive

Solid-State

See user manual

120% FLA

5…30

Automatic or Manual

1…100% TCU

Ground Fault Protection

Type

Intended Use

Classification (Per UL 1053)

External Protection Range

Internal Protection Range

Trip & Warning Time Delay

Protection Inhibit Time

Core Balanced

Equipment Protection

Class I and Class II

20…100 mA

100…500 mA

200 mA…1.0 A

1.0…5.0 A

0.5…5.0 A

0.1…25.0 s

0…250 s

Under Frequency

Over Frequency

Under Real Power (kW)

Over Real Power (kW)

Under Reactive Power Consumed (+kVAR)

Over Reactive Power Consumed (+kVAR)

Under Reactive Power Generated (-kVAR)

Over Reactive Power Generated (-kVAR)

Under Apparent Power (kVA)

Over Apparent Power (kVA)

Under Power Factor Lagging (-PF)

Over Power Factor Lagging (-PF)

Under Power Factor Leading (+PF)

Over Power Factor Leading (+PF)

Power Value Overflow (kW, kVAR or KVA)

Over Analog

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Trip Warning

Yes Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Specifications

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

21

Specifications

Accuracy

Metering

Current

Voltage

Power

±2% of Sensing Module Current Range

±2% of Sensing Module Voltage Range

±5% of Sensing Module Current and Voltage Range

Protection Timers

All E300 Electronic Overload Relay trip timers have a resolution of ±0.1 s or 0.1 s/25 s (whichever is greater).

22

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

Notes:

Specifications

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

23

Specifications

24

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

Approximate Dimensions

Bulletin 193/592-E300 Approximate Dimensions

Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.

Figure 5 - E300 Overload Relay Mounted on Bulletin 100-C09…-C23 Contactor

45

(1.76)

87

(3.40)

35

(1.37) n 5 (0.18)

67 (2.65)

190 (7.49)

(ADD 5 mm (0.19 in.)

FOR CONTACTOR COIL

ON LINE SIDE)

37 (1.47)

FROM

CONTACTOR

MTG. HOLE

152 (5.98)

122 (4.81)

60 (2.36)

29 (1.14)

FROM

CONTACTOR

MTG. HOLE

122

(4.78)

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

25

Approximate Dimensions

Figure 6 - E300 Overload Relay Mounted on Bulletin 100-C30…-C37 Contactor

45

(1.76)

104

(4.10)

67 (2.65)

190 (7.49)

(ADD 5 mm (0.19 in.)

FOR CONTACTOR COIL

ON LINE SIDE)

122 (4.81)

37 (1.48) FROM

CONTACTOR

MTG. HOLE

152 (5.98) n 5 (0.18)

35

(1.374)

60 (2.36)

29 (1.13)

FROM

CONTACTOR

MTG. HOLE

122

(4.78)

Figure 7 - E300 Overload Relay Mounted on Bulletin 100-C43…-C55 Contactor

54

(2.12)

107

(4.21)

190 (7.49)

(ADD 5 mm (0.19 in.)

FOR CONTACTOR COIL

ON LINE SIDE)

67 (2.65)

37 (1.48) FROM

CONTACTOR

MTG. HOLE

152 (5.98)

34 (1.34)

FROM

CONTACTOR

MTG. HOLE n 5 (0.18)

45 (1.75)

60 (2.36)

45 (1.76)

122

(4.82)

26

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

Figure 8 - E300 Overload Relay Mounted on Bulletin 100-C60…-C97 Contactor

71.6

(2.82)

126.2

(4.97)

129.5

(5.10)

43.5

(1.71)

FROM

CONTACTOR

MTG. HOLE

91.6

(3.60)

235.1

(9.26)

(ADD 0.24 in. FOR

CONTACTOR COIL

ON LINE SIDE)

177.6

(6.99)

38.9

(1.53)

FROM

CONTACTOR

MTG. HOLE

135.2

(5.32)

Figure 9 - E300 Overload Relay Mounted on Bulletin 500 NEMA Size 0 and Size 1 Contactor

90

(3.56) n 6 (0.22)

5.4

(0.21)

Approximate Dimensions

101

(3.98)

157 (6.17)

180 (7.06)

249 (9.78)

35 (1.38)

70

(2.75)

12 (0.46)

125

(4.91)

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

27

Approximate Dimensions

Figure 10 - E300 Overload Relay Mounted on Bulletin 500 NEMA Size 2 Contactor

100.1 (3.94) n 5.58 (0.22)

183.9

(7.24)

219.2

(8.63)

275.59

(10.85)

40.13

(1.58)

80.01

(3.15)

11.68 (0.46)

124.71

(4.91)

28

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

Figure 11 - E300 Overload Relay Mounted on Bulletin 500 NEMA Size 3 Contactor

138.2

(5.44)

11.35

(0.45)

161.6

(6.36)

19.9

(0.78)

7.9

(0.31)

368

(14.49)

219.9

(8.66)

274.1

(10.79)

Approximate Dimensions

121

(4.76)

139.85

(5.51)

155.45

(6.12)

138.4

(5.45)

Figure 12 - E300 Overload Relay, 193-ESM-___-30A-E3T and -60A-E3T, DIN Rail/Panel Mounted

45

(1.764)

126

(4.94)

6 (0.24)

30

(1.18)

9 (0.33)

46 (1.81)

148 (5.83)

4 (0.16) q

4 (0.14)

135 (5.32)

6 (0.217)

101 (3.96)

4 (0.154) n 5 (0.17)

8 (0.30)

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

29

Approximate Dimensions

Figure 13 - E300 Overload Relay, 193-ESM-___-100A-E3T, DIN Rail/Panel Mounted

71.6

(2.82)

41.2

(1.62)

17.7

(0.70)

5.5

(0.22)

139.9

(5.51) q

76.6

(3.02)

60

(2.36)

130

(5.12)

41.4

(1.63)

141.5

(5.57)

4.05

(0.16)

Figure 14 - E300 Overload Relay, 193-ESM-___-30A-T and -60A-T, DIN Rail Mounted

SHOWN WITH PANEL MOUNT FEET ACCESSORY

CAT. NO. 140M-C-N45

11.35

(0.45) n 4.8

(0.189)

39

(1.53)

135

WITH MTG. FEET

30.1

(1.19) q

4.5

(0.18)

116.2

(4.58)

W/O MTG. FEET

125

(4.921)

124

(4.88)

5

(0.197)

45

(1.76)

30

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

Approximate Dimensions

Figure 15 - E300 Overload Relay, 193-ESM-___-100A-T, DIN Rail Mounted

120.7

(4.75)

W/O FEET q

11.4

(0.45)

41.2

(1.62)

WITH FEET

36.6

(1.44)

W/O FEET

SHOWN WITH PANEL MOUNT ACCESSORY

FEET CAT. NO. 193-ESM-SA-100

60

(2.36) q

52.9

(2.08)

139.9

(5.51)

WITH FEET

130

(5.12)

71.6

(2.82)

141

(5.55) n 5.8

(0.23)

Figure 16 - E300 Overload Relay, 193-ESM-___-30A-P, -30A-CT, and -60A-P, DIN Rail Mounted

11.35

(0.45)

FROM MOUNTING FOOT

MOUNTING HOLE TO

RESET BUTTON

21.5

(0.85)

FROM MOUNTING FOOT

MOUNTING HOLE TO

RESET BUTTON

106.3

(4.18)

W/O MTG. FEET

30.2

(1.19) q

102

(4.00)

W/ MTG. FEET n 4.8

(0.19)

91.5

(3.60)

108

(4.25)

W/ MTG. FEET

45

(1.76)

123.5

(4.86)

5

(0.20)

3 PIN CONNECTOR ONLY WITH

CAT. NO. 193-ESM-VIG-30A-CT

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

31

Approximate Dimensions

Figure 17 - E300 Overload Relay, 193-ESM-___-100A-P, DIN Rail Mounted

q

11.6

(0.46)

26.3

(1.04)

WITH FEET

106.3

(4.18)

W/O FEET

21.4

(0.84)

W/O FEET

SHOWN WITH PANEL MOUNT ACCESSORY

FEET CAT. NO. 193-ESM-SA-100 q

38.8

(1.53)

109.9

(4.33)

WITH FEET n 5.8

(0.23)

60

(2.36)

71.6

(2.82)

140.9

(5.55)

Figure 18 - E300 Digital Expansion Module 193-EXP-DIO-___

22.5

(0.89)

2 x 4.5 (0.18) dia.

100

(3.94)

98 (3.86) 87 (3.43)

80.75 (3.18)

120

(4.73)

32

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

Approximate Dimensions

Figure 19 - E300 Analog Expansion Module 193-EXP-AIO-31

22.5

(0.89)

2 x 4.5 (0.18) dia.

98 (3.86) 87 (3.43)

80.75 (3.18)

Figure 20 - E300 Expansion Power Supply 193-EXP-PS-___

45

(1.77)

4x 4.5 (0.18) dia

98

(3.86)

87

(3.43)

80.75 (3.18)

12

(0.47)

Figure 21 - E300 Starter Control Station 193-EOS-SCS

100

(3.94)

18.5

(0.73)

45 (1.77)

13.5

(0.53)

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

120

(4.73)

120

(4.73)

22.5 (0.89) dia.

33

Approximate Dimensions

Figure 22 - E300 Starter Diagnostic Station 193-EOS-SDS

100

(3.94)

18.5

(0.73)

70

(2.76) n 22.1

(0.87)

13.5

(0.53)

34

Rockwell Automation Publication 193-SG010D-EN-P - April 2015

Allen-Bradley, Rockwell Software, Rockwell Automation, and LISTEN. THINK. SOLVE are trademarks of Rockwell Automation, Inc.

Trademarks not belonging to Rockwell Automation are property of their respective companies.

Publication 193-SG010D-EN-P - April 2015

Supersedes Publication 193-SG010C-EN-P - November 2014 Copyright © 2015 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.