TEST REPORT
IEC / EN 62040-1
Uninterruptible power systems (UPS) –
Part 1: General and safety requirements for UPS
Report Reference No
...................... : 9012326349
Date of issue .................................... : 28.10.2010
Total number of pages ...................... 68 pages + Appendix 3 (4 pages)
CB Testing Laboratory ..................... : The Standards Institution of Israel
Address ............................................ : 42 Chaim Levanon St., 69977 Tel Aviv, Israel
Applicant’s name
............................ : Gamatronic Electronic Industries Ltd.
Address ............................................ : 14 Hartom Str., Har Hotsvim Science-Based Industrial Park, POB
45029, Jerusalem, 45029 Israel
Test specification:
Standard........................................... : IEC / EN 62040-1 : 2008 (1st Edition)
Test procedure ................................. : N/A
Non-standard test method…………..: N/A
Test Report Form No
...................... : IEC62040_1A
Test Report Form(s) Originator ........ : TÜV Rheinland Japan Ltd.
Master TRF ...................................... : Dated 2009-11
Copyright © 2009 IEC System for Conformity Testing and Certification of Electrical Equipment
(IECEE), Geneva, Switzerland. All rights reserved.
This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from the reader's interpretation of the reproduced material due to its placement and context.
If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the CB
Scheme procedure shall be removed.
This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02.
Test item description
..................... : Uninterruptible Power System
Trade Mark ....................................... :
Manufacturer ..................................... : Gamatronic Electronic Industries Ltd.
Model/Type reference ...................... : MEGA SYSTEM 250KW 400V 3/3, Cat. No. 101SMD60
Ratings ............................................. : Input: 3x400Vac, 50Hz, 3x420A (max.);
Output: 3x400Vac, 50Hz, 3x360A (max.)
Page 2 of 68 Report No. 9012326349
Testing procedure and testing location:
CB Testing Laboratory:
Testing location/ address ........................:
Associated CB Laboratory:
Testing location/ address ........................:
Tested by (name + signature).......: SERGEY VOYTENKO
Approved by (+ signature) ............: MICHAEL TERMAN
Testing procedure: TMP
Tested by (name + signature).......:
Approved by (+ signature) ............:
Testing location/ address ........................:
Tested by (name + signature).......:
Witnessed by (+ signature) ...........:
Approved by (+ signature) ............:
Testing location/ address ........................:
Tested by (name + signature).......:
Approved by (+ signature) ............:
Supervised by (+ signature)..........:
Testing location/ address ........................:
Testing procedure: RMT
Tested by (name + signature).......:
Approved by (+ signature) ............:
Supervised by (+ signature)..........:
Testing location/ address ........................:
TRF No. IEC62040_1A
Summary of testing:
Tests performed (name of test and test clause):
5.1.4. Backfeed protection.
5.3 Protective earthing and bonding.
5.5. Over current and earthing fault protection.
5.7. Clearance, creepage and distance through insulation.
7.3. Mechanical strength.
7.4.2. Openings.
7.7 Temperature rise.
8.2 Electrical strength.
8.3 Abnormal operating and fault conditions.
Testing location:
14 Hartom Str., Har Hotsvim Science-Based
Industrial Park, POB 45029, Jerusalem, 45029
Israel
Page 3 of 68 Report No. 9012326349
Appendices:
Appendix 1 – Photographs
Appendix 2 – Electrical Schematics
Appendix 3 – European Group Differences and National Differences (EN 62040-1: 2008)
TRF No. IEC62040_1A
Copy of marking plate:
Page 4 of 68 Report No. 9012326349
SYSTEM
Power Module Static Switch Controller
TRF No. IEC62040_1A
Page 5 of 68 Report No. 9012326349
Test item particulars
.................................................. :
Equipment mobility .................................................... : [] movable [x] stationary [] for building-in
Connection to the mains............................................ : [] pluggable equipment [x] permanent connection
[] detachable power supply cord
[] non-detachable power supply cord
Operating condition ................................................... : [x] continuous
[] rated operating / resting time:
Access location ........................................................ : [x] operator accessible
[] restricted access location
Over voltage category (OVC) ................................... : [] OVC I [x] OVC II [] OVC III [] OVC IV
[] other:
Mains supply tolerance (%) or absolute mains supply values ....................................................................... :
+/- 10%
Tested for IT power systems .................................... : [] Yes [x] No
IT testing, phase-phase voltage (V) ......................... : --
Class of equipment ................................................... : [x] Class I [] Class II
[] Not classified
Considered current rating (A) ................................... : 420A
Pollution degree (PD) ............................................... : [] PD 1 [x] PD 2 [] PD 3
IP protection class .................................................... : IP2X
Altitude during operation (m) .................................... : 2000
Altitude of test laboratory (m) ................................... : 35
Mass of equipment (kg) ............................................ : 450 kg
Possible test case verdicts:
- test case does not apply to the test object.................: N/A
- test object does meet the requirement.......................: P (Pass)
- test object does not meet the requirement.................: F (Fail)
Testing
......................................................................... :
Date of receipt of test item ............................................: 11.07.2010
Date(s) of performance of tests ....................................: 11.07.2010 – 30.08.2010
General remarks:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing testing laboratory.
"(see Enclosure #)" refers to additional information appended to the report.
"(see appended table)" refers to a table appended to the report.
Throughout this report a comma (point) is used as the decimal separator.
Standard IEC 62040-1:2008 is to be used in conjunction with IEC 60950-1:2005, which is referred to in this
TRF as "RD".
General product information:
1. The equipment is a modular uninterruptible power system (UPS). The following modules are incorporated in the equipment: 25kVA Power Module (up to 10 units), Controller Module, and Static
Switch Module.
2. Battery compartment and batteries are not supplied with the UPS.
3. End-user should provide an external circuit breaker specified in the installation instructions.
TRF No. IEC62040_1A
Page 6 of 68 Report No. 9012326349
IEC 62040-1
Clause
4
Requirement + Test
GENERAL CONDITIONS FOR TESTS
Result - Remark Verdict
P
4.5 Components
1.5.2/RD
Comply with IEC 62040-1 or relevant component standard
Evaluation and testing of components
(see appended table 4.5)
Components which are certified to IEC and/or national standards are used correctly within their ratings.
Components not covered by
IEC standards are tested under the conditions present in the equipment.
1.5.3/RD Thermal controls
1.5.4/RD
1.5.5/RD
Transformers
Interconnecting cables
Thermal switch in Power
Module Card 1012 is certified and used correctly.
Transformers used in the equipment are suitable for their intended application and comply with the relevant requirements of the standard.
All interconnecting cables are located within enclosure and are treated as internal wiring.
1.6.1/RD
1.6.2/RD
4.6
1.6.4/RD
AC power distribution systems
Input current
Neutral conductor
(see appended table 4.6)
Neutral conductor is isolated from earthed parts by basic insulation within the equipment.
P
P
P
P
P
N/A
1.5.6/RD
Capacitors bridging insulation
1.5.7/RD
Resistors bridging insulation
1.5.7.1/RD
Resistors bridging functional, basic or supplementary insulation
Provided in cards of Power
Module. Lines to Ground capacitors comply with IEC
60384-14.
No such components
P
N/A
N/A
1.5.7.2/RD
Resistors bridging double or reinforced insulation between a.c. mains and other circuits
N/A
1.5.7.3/RD
Resistors bridging double or reinforced insulation between a.c. mains and antenna or coaxial cable
N/A
1.5.8/RD
N/A Components in equipment for IT power systems The equipment is not intended for IT power systems
P
P
P
P
TRF No. IEC62040_1A
Page 7 of 68 Report No. 9012326349
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict
4.7 Marking and instructions
4.7.1 General
4.7.2 Power rating
1.7.1/RD
P
P
P
Input rated voltage/range (V) ...........................: 400V P
Input rated current/range (A)............................:
420A P
Input symbol for nature of supply (d.c.) ...........:
-- N/A
Input rated frequency/range (Hz) .....................:
50/60Hz P
Number of Input phases and neutral................:
3~, N P
Output rated voltage/range (V) ........................: 400V P
Output rated current/range (A) ........................: 360A P
1.7.1/RD
Output rated power factor, (if less than unity, or active power and apparent power or active power and rated current) .................................:
Active output power and output current are rated
Number of output phases and neutral..............:
3~, N
Output rated active power (W) ........................:
250 kW
P
P
P
Output rated apparent power (VA) ..................: N/A
Output symbol for nature of supply (d.c.) ........:
N/A
Output rated frequency/range (Hz) ..................:
50Hz P
Ambient operating temperature range (
°C).....:
-10 to +40ºC (provided in User
Manual)
P
P Manufacturer’s name or trademark or identification mark ...........................................: GAMATRONIC
Type/model or type reference ..........................: MEGA SYSTEM 250KW 400V
3/3, Cat. No. 101SMD60
P
Symbol for Class II equipment only ................: Class I equipment
Other symbols .................................................:
Warning symbols “General hazard” and “Electric shock
Hazard”.
N/A
P
Certification marks ..........................................:
No certification marks
Instructions for units with automatic bypass/maintenance bypass, additional input a.c. supply, or external batteries, having text
"See installation instructions before connecting to the supply" ...................................................:
Provided in Installation
Manual.
4.7.3.1 General
N/A
P
P
P
Location in a restricted access location only ... :
-- N/A
TRF No. IEC62040_1A
Page 8 of 68 Report No. 9012326349
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict
Permanent connector UPS .............................. :
Suitable statement is provided in Installation Manual
P
Pluggable type A or Pluggable type B UPS .... : -- N/A
4.7.3.3 Operation.......................................................... : in User /Operational Manual
P
According to the Service
Manual, maintenance of product is done only by service personnel.
P
4.7.3.5
4.7.4
1.7.4/RD
Distribution related backfeed............................ :
Main voltage adjustment ................................. :
P
-- N/A
4.7.5
1.7.5/RD
Methods and means of adjustment; reference to installation instructions .................................... :
--
Power outlets.................................................... :
No standard power outlets.
The equipment is provided with output terminals.
N/A
N/A
4.7.6
1.7.6/RD
Fuse identification (marking, special fusing characteristics, cross-reference) ..................... :
Fuses are not located in operator access area.
Unambiguous reference to service documentation is provided.
P
P
4.7.7
1.7.7/RD
Wiring terminals
1.7.7.1/RD Protective earthing and bonding terminals ...... : Main protective earthing bus bar located in the Mounting
Rack is provided with IEC
60417-2-IEC5019 marking.
Bonding terminals in the
Modules are provided with symbol IEC60417-2-IEC 5017.
P
1.7.7.2/RD
1.7.7.3/RD
Terminals for a.c. mains supply conductors
Terminals for d.c. mains supply conductors
Input and output terminals of the Static Switch (rear panel) are marked.
Not connected to the DC mains
Terminals for battery connections (Static Switch rear panel) are marked with “+” and
“–“
P
N/A
P
4.7.9
1.7.8/RD
Controls and indicators
P
1.7.8.1/RD Identification, location and marking ................. :
All circuit breakers are marked in accordance with circuits in which they are used.
P
TRF No. IEC62040_1A
Page 9 of 68 Report No. 9012326349
IEC 62040-1
Clause Requirement + Test Result - Remark
...........................................................: Only functional non-safety related indicators are used.
1.7.8.3/RD Symbols according to IEC 60417.....................: Symbols according to IEC
60417 are used on approved circuit breakers and contactors.
Verdict
P
P
1.7.8.4/RD Markings using figures ...................................:
N/A
4.7.10
1.7.9/RD
Isolation of multiple power sources .................:
The equipment is connected to
AC mains and external battery.
Warning marking for service personnel is provided in the product User Manual.
P
IT power systems
N/A
4.7.11
1.7.2.4/RD
4.7.12
P
4.7.13
5.1/RD
Protection in building installation
External circuit breakers are specified by manufacturer for all possible configurations and number of the Power Modules used.
High leakage current (mA) ..............................:
Required label is provided: P
4.7.14
1.7.10/RD
4.7.15
1.7.2.1/RD and
1.7.8.1/RD
4.7.16
1.7.11/RD
4.7.17
1.7.12/RD
4.7.18
1.7.13/RD
Thermostats and other regulating devices
Language(s) ....................................................: English was reviewed
Durability of markings
Removable parts
Replaceable batteries
N/A
The marking are not located on the removable parts
Such batteries are not used
⎯
P
P
N/A
4.7.19
1.7.2.5/RD
4.7.20
Operator access with a tool..............................:
Battery
A tool is not required to gain access to the operator access area
Not supplied with the equipment
⎯
N/A
N/A
N/A
N/A
TRF No. IEC62040_1A
Clause
2.1.1.5/RD
4.7.21
1.7.2.4/RD
Installation instructions
Page 10 of 68 Report No. 9012326349
IEC 62040-1
Result - Remark Verdict Requirement + Test
Nominal voltage of total battery (V) ................. :
Nominal capacity of total battery (optional) ..... :
Protection against energy hazards There are no bare live parts in the Operator access area which may be bridged by test finger.
Suitable Instructions are provided in Installation Manual.
The appliance is not intended for connection to IT power systems.
N/A
N/A
N/A
N/A
N/A
P
5.1
5.1.1
2.1.1/RD
Protection against electric shock and energy hazards
Protection for UPS intended to be used in operator access areas
2.1.1.1/RD Access to energized parts Only SELV circuits and earthed parts are accessible
Test by inspection ........................................... : Only SELV circuits and earthed parts are accessible
Test with test finger (Figure 2A) ...................... :
No hazardous voltage accessible with the test finger
Test with test pin (Figure 2B) .......................... :
No hazardous voltage accessible with the test pin
Test with test probe (Figure 2C) ..................... :
No TNV circuits
2.1.1.2/RD Battery compartments
2.1.1.3/RD Access to ELV wiring
Working voltage (Vpeak or Vrms); minimum distance through insulation (mm)
2.1.1.4/RD Access to hazardous voltage circuit wiring
No ELV circuits
(see appended table 5.7)
No hazardous voltages are located in operator access area
2.1.1.5/RD
Energy hazards ............................................... :
No energy hazard in operator access area
2.1.1.6/RD Manual controls Touch screen display is not connected to ELV or hazardous voltage parts.
P
P
P
P
P
P
P
N/A
N/A
N/A
⎯
P
P
P
TRF No. IEC62040_1A
Page 11 of 68 Report No. 9012326349
IEC 62040-1
Clause Requirement + Test
2.1.1.7/RD Discharge of capacitors in equipment
Result - Remark
No operator-accessible external point of disconnection of a mains supply
(permanently connected equipment with external circuit breaker).
Measured voltage (V); time-constant (s).......... : --
Verdict
N/A
⎯
2.1.1.8/RD Energy hazards – d.c. mains supply Not connected to DC mains N/A a) Capacitor connected to the d.c. mains supply .. b) Internal battery connected to the d.c. mains supply .............................................................. :
N/A
N/A
2.1.1.9/RD
Audio amplifiers ............................................... :
N/A
5.1.2
2.1.1.5 c)
/RD
Protection for UPS intended to be used in service access areas
Service is not permitted when the equipment is switched on.
N/A
5.1.3
2.1.1.5 c)
/RD
Hazardous energy level
Protection for UPS intended to be used in restricted access areas
Hazardous energy level
N/A
N/A
N/A
⎯
Shock hazard after de-energization of a.c. input for UPS
P
Measured voltage (V); time-constant (s).......... : 0V, 1.2 sec
⎯
P
5.1.5
5.2
5.2.1
2.2/RD
Description of the construction ........................ : Backfeed protection of the equipment is provided by contactors located in the Static
Switch
Emergency switching device The equipment is provided with terminals for connection of the remote emergency switch device. When external
EMO switch is operated, it disconnects the equipment output from any input source.
Suitable statement in the User
Manual is provided.
Requirements for auxiliary circuits
Safety extra low voltage circuit - SELV
P
P
P
TRF No. IEC62040_1A
Page 12 of 68 Report No. 9012326349
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict
2.2.2/RD
2.2.3/RD
2.2.4/RD
5.2.2
2.3/RD
2.3.1/RD
Separation between hazardous voltage circuits and
SELV circuits is provided by the following:
- Power Module:
Card 1012, transformers
29TJIXDA, 29TJIXF;
Card 1013, provided by optical isolators ISO6, ISO7, Cl/Cr;
- Controller Module: approved power supply with
SELV outputs, including LCD touch control panel supplying circuit;
- Static Switch module:
Card 1776, optical isolators
ISO3, ISO4, Cl/Cr.
Voltages under normal conditions (V) ............. : (See appended table 5.2.1)
Voltages under fault conditions (V) ................. : (See appended table 5.5)
Connection of SELV circuits to other circuits .. :
Telephone network voltage circuits - TNV
No TNV circuits
Frequency (Hz) ................................................ :
Measured current (mA) .................................... :
(See appended table 5.2.3)
P
P
P
P
N/A
2.3.2/RD
Limits
Type of TNV circuits......................................... :
Separation from other circuits and from accessible parts
N/A
⎯
N/A
2.3.2.2/RD Protection by basic insulation
2.3.2.3/RD Protection by earthing
2.3.2.4/RD Protection by other constructions .................... :
2.3.3/RD
2.3.4/RD
2.3.5/RD
5.2.3
2.4/RD
N/A
N/A
N/A
N/A
Separation from hazardous voltages
Insulation employed ......................................... :
N/A
⎯
N/A Connection of TNV circuits to other circuits
Insulation employed ......................................... : ⎯
Test for operating voltages generated externally N/A
Test with test probe (Figure 2C) ..................... :
N/A
Limited current circuits N/A
N/A
⎯
⎯
⎯
TRF No. IEC62040_1A
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict
2.4.3/RD
5.2.4
3.5/RD
3.5.2/RD
3.5.3/RD
3.5.4/RD
5.2.5
2.5/RD
Measured voltage (V)....................................... : ⎯
Measured circuit capacitance (nF or µF) ......... :
Connection of limited current circuits to other circuits
⎯
N/A
External signalling circuits
Types of interconnection circuits ..................... :
N/A
ELV circuits as interconnection circuits N/A
Data ports for additional equipment
Limited power source
The equipment is not intended for connection to other equipment.
N/A
N/A
N/A
N/A a) Inherently limited output b) Impedance limited output c) Regulating network limited output under normal operating and single fault condition d) Overcurrent protective device limited output
Max. output voltage (V), max. output current (A), max. apparent power (VA) ............................... :
Current rating of overcurrent protective device (A)
N/A
N/A
N/A
N/A
⎯
⎯
5.3 Protective earthing and bonding
5.3.1 General
2.6/RD Provisions for earthing and bonding All accessible conductive parts of modules are reliably connected to the protective earthing terminal (bus-bar) located in the side of the
Mounting Rack.
Each module frame is bonded to protective earthing by green/yellow conductor. Each module is bonded to its frame by protective pin (located in the frame rear enclosure) and contact secured to the module enclosure.
P
P
P
P
N/A
P 2.6.3/RD Protective earthing and protective bonding conductors
2.6.3.1/RD General P
TRF No. IEC62040_1A
Page 13 of 68 Report No. 9012326349
Page 14 of 68 Report No. 9012326349
IEC 62040-1
Clause Requirement + Test
2.6.3.2/RD Size of protective earthing conductors
Rated current (A), cross-sectional area (mm2),
AWG................................................................. :
2.6.3.3/RD
Size of protective bonding conductors
Rated current (A), cross-sectional area (mm2),
AWG................................................................. :
Protective current rating (A), cross-sectional area (mm2), AWG ............................................ :
Result - Remark
420A, 45mm² (bus-bar
15x5mm)
42A per Power Module,
10mm²
50A per Power Module,
10mm²
Verdict
P
⎯
P
⎯
⎯
2.6.3.4/RD Resistance of earthing conductors and their terminations; resistance (
Ω), voltage drop (V), test current (A), duration (min) ......................... :
(See appended table 5.3.1)
2.6.3.5/RD
Colour of insulation .......................................... :
Green/Yellow P
2.6.4/RD
Terminals
P
2.6.4.1/RD
General
2.6.4.2/RD Protective earthing and bonding terminals Main protective earthing busbar and bonding screw type terminals.
P
P
P
2.6.4.3/RD
Rated current (A), type, nominal thread diameter
(mm) ................................................................. :
Separation of the protective earthing conductor from protective bonding conductors
Main bus-bar 420A,
15mmx5mm, 42A, bonding screw terminal M5
⎯
P
2.6.5/RD Integrity of protective earthing
2.6.5.1/RD Interconnection of equipment Earthing connection is assured for equipment connected to the equipment under test.
P
P
2.6.5.2/RD Components in protective earthing conductors and protective bonding conductors
2.6.5.3/RD Disconnection of protective earth
2.6.5.4/RD Parts that can be removed by an operator
2.6.5.5/RD
2.6.5.6/RD
2.6.5.7/RD
2.6.5.8/RD
Parts removed during servicing
Corrosion resistance
Screws for protective bonding
Reliance on telecommunication network or cable distribution system
No switches and fuses in the protective conductors.
Permanent connection to PE.
Protective earthing connection makers earlier and breaks later than the phase connection when the Power
Module or Controller Module is removed or inserted.
P
P
No risk of corrosion
(combination Zink on steel/aluminium is used).
P
P
No self-tapping and spaced thread screws are used for bonding connection.
P
N/A
TRF No. IEC62040_1A
Clause
5.3.2
2.6.1/RD
2.10/RD
4.2/RD
5.2/RD
Requirement + Test
Protective earthing P
Clearances, creepage distances and distances through insulation
Mechanical strength
Electric strength
P
P
P
P
5.4
AC and d.c. power isolation
5.4.1 General
3.4/RD Disconnection from the mains supply
P
P
P
3.4.2/RD
3.4.3/RD
3.4.4/RD
3.4.5/RD
3.4.6/RD
3.4.7/RD
Disconnect devices
Parts which remain energized
Switches in flexible cords equipment
Page 15 of 68 Report No. 9012326349
IEC 62040-1
Result - Remark Verdict
Permanently connected equipment
Number of poles - single-phase and d.c.
Number of poles - three-phase equipment
External disconnect device is specified in the installation instructions.
External circuit-breaker is used as disconnect device.
Suitable statement in installation instruction is provided.
No such parts. External disconnect device is used.
Three-phase equipment
P
P
P
N/A
N/A
N/A
P
3.4.8/RD
3.4.9/RD
3.4.11/RD
5.4.2
Switches as disconnect devices
Plugs as disconnect devices
Multiple power sources
Disconnect devices
Disconnect all phase conductors simultaneity
Disconnect device is not incorporated in the equipment.
Separate means are provided for AC mains and external battery.
Disconnect device for AC supply is provided.
N/A
N/A
N/A
P
P
5.5
Overcurrent and earth fault protection
5.5.1 General
2.7.3/RD
Short-circuit backup protection
External circuit breaker and circuit breakers in each phase conductor are provided.
P
P
P
TRF No. IEC62040_1A
Page 16 of 68 Report No. 9012326349
IEC 62040-1
Clause
2.7.4/RD
2.7.5/RD
2.7.6/RD
5.5.3
5.5.3.1
5.5.3.2
5.5.3.3
5.3.1/RD
Requirement + Test Result - Remark Verdict
Number and location of protective devices ..... :
Each Phase conductor of each
Power Module is protected by
50A fuse.
Protection by several devices
Warning to service personnel .......................... : Such warnings for service persons are not required.
Battery circuit protection
Overcurrent and earth fault protection
Location of protective device
Rating of protective device
Protection against overload and abnormal operation
P
P
N/A
Protection provided by an external circuit breaker 420A and by:
- AC input/output circuit breakers located in each
Power Module;
- DC input/output fuses 40A located in each Power Module
P
P
Batteries supply circuits are protected by input/output fuses
40A located in each Power
Module.
Batteries are not installed inside the equipment.
Separate battery supply is used. Suitable rating of the over current protective device is provided in User Manual.
P
N/A
P
(see appended table 8.3) P
5.6
2.8.7.4/RD
Protection of personnel – Safety interlocks
Electric strength test
Safety interlocks are not used.
P
N/A
N/A
N/A
N/A
N/A
N/A
2.8.6/RD Overriding
2.8.7/RD Switches and relays
N/A
N/A
N/A
2.8.7.1/RD Contact gaps (mm) .......................................... : N/A
(see appended table 8.2)
N/A
N/A
N/A
TRF No. IEC62040_1A
Page 17 of 68 Report No. 9012326349
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict
5.6.2
5.6.2.1 Introduction
5.6.2.2 Covers
5.6.2.3
5.6.2.4
Service person protection
Location and guarding of parts
Parts on doors
N/A
P
All hazardous voltage and moving parts are protected against unintentional contact by isolation.
P
P
P
N/A
N/A
No doors
No components which require access for adjacent or maintenance.
No interlocks
Cooling fans are guarded
Residual hazardous voltage remains on the capacitors located in Power Modules.
Warning marking and instructions for service personal are provided.
N/A
P
P
N/A
Clearances, creepage distances and distances through insulation P
5.7
2.10/RD
2.10.1/RD General
2.10.1.1/RD Frequency ....................................................... : 50 Hz
P
P
2.10.1.2/RD Pollution degrees ............................................ : II P
2.10.1.3/RD Reduced values for functional insulation N/A
2.10.1.4/RD Intervening unconnected conductive parts
2.10.1.5/RD Insulation with varying dimensions
N/A
N/A
2.10.1.6/RD Special separation requirements
2.10.1.7/RD Insulation in circuits generating starting pulses
2.10.2/RD Determination of working voltage
2.10.2.1/RD General
(See appended table 5.7)
N/A
N/A
P
P
2.10.2.3/RD Peak working voltage
2.10.3/RD Clearances
2.10.3.1/RD General
P
P
P
P
N/A a) AC mains supply ......................................... : N/A
TRF No. IEC62040_1A
Page 18 of 68 Report No. 9012326349
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict b) Earthed d.c. mains supplies ........................ :
N/A c) Unearthed d.c. mains supplies .................... :
N/A d) Battery operation ......................................... :
N/A
2.10.3.3/RD Clearances in primary circuits (see appended table 5.7) P
2.10.3.4/RD Clearances in secondary circuits
2.10.3.5/RD Clearances in circuits having starting pulses
(see appended table 5.7) P
N/A
2.10.3.6/RD Transients from a.c. mains supply .................. : N/A
2.10.3.7/RD Transients from d.c. mains supply .................. : N/A
2.10.3.8/RD Transients from telecommunication networks and cable distribution systems ........................ :
N/A
2.10.3.9/RD Measurement of transient voltage levels a) Transients from a mains supply
For an a.c. mains supply ................................. :
N/A
N/A
N/A
For a d.c. mains supply ................................... :
N/A b) Transients from a telecommunication network . N/A
2.10.4/RD Creepage distances
2.10.4.1/RD General
2.10.4.2/RD Material group and comparative tracking index IIIb
CTI tests ........................................................... :
2.10.4.3/RD Minimum creepage distances
2.10.5 /RD Solid insulation
(see appended table 5.7)
Solid insulation is used only for basic insulation purposes.
P
P
P
⎯
P
N/A
2.10.5.1/RD General
2.10.5.2/RD Distances through insulation
2.10.5.3/RD Insulating compound as solid insulation
(see appended table 5.7)
N/A
N/A
N/A
2.10.5.6/RD Thin sheet material – General
2.10.5.7/RD Separable thin sheet material
N/A
N/A
N/A
N/A
Number of layers (pcs) .................................... :
2.10.5.8/RD Non-separable thin sheet material
⎯
N/A
2.10.5.9/RD Thin sheet material – standard test procedure
2.10.5.10
/RD
Electric strength test
Thin sheet material – alternative test procedure
N/A
(see appended table 8.2) ⎯
N/A
Electric strength test (see appended table 8.2) ⎯
N/A 2.10.5.11
/RD
Insulation in wound components
TRF No. IEC62040_1A
Page 19 of 68 Report No. 9012326349
IEC 62040-1
Clause
2.10.5.12
/RD
Requirement + Test
Wire in wound components
Result - Remark Verdict
N/A
2.10.5.13
/RD
Working voltage .............................................. : ⎯ a) Basic insulation not under stress ................ : N/A b) Basic, supplementary, reinforced insulation :
N/A c) Compliance with Annex U ........................... :
N/A
Two wires in contact inside wound component; angle between 45
° and 90° ............................. :
N/A
N/A Wire with solvent-based enamel in wound components
Electric strength test (see appended table 8.2)
Additional insulation in wound components
⎯
N/A
N/A 2.10.5.14
/RD
Working voltage .............................................. : ⎯
2.10.6/RD
- Basic insulation not under stress .................. : N/A
- Supplementary, reinforced insulation ........... :
N/A
Construction of printed boards
2.10.6.1/RD Uncoated printed boards
P
P
2.10.6.2/RD Coated printed boards
2.10.6.3/RD Insulation between conductors on the same inner surface of a printed board
2.10.8.1/RD Sample preparation and preliminary inspection
2.10.8.3/RD Electric strength test (see appended table 8.2)
N/A
N/A
2.10.6.4/RD Insulation between conductors on different layers of a printed board
Distance through insulation
2.10.7/RD
2.10.8/RD
Number of insulation layers (pcs) ................... :
Component external terminations
Tests on coated printed boards and coated components
N/A
No coated printed boards or components
N/A
N/A
N/A
N/A
N/A
N/A
2.10.8.4/RD Abrasion resistance test
2.10.10/RD Test for Pollution Degree 1 environment and insulating compound
Pollution degree II
⎯
N/A
N/A
N/A
2.10.11/RD Tests for semiconductor devices and cemented joints
2.10.12/RD Enclosed and sealed parts
N/A
N/A
TRF No. IEC62040_1A
Page 20 of 68 Report No. 9012326349
IEC 62040-1
Clause Requirement + Test
6
Wiring, connections and supply
6.1 General
6.1.1 Introduction
3.1/RD General
3.1.1/RD
3.1.2/RD
3.1.3/RD
3.1.4/RD
3.1.5/RD
3.1.6/RD
3.1.7/RD
3.1.8/RD
3.1.9/RD
6.1.2
6.2
6.2.1
3.2.2/RD
3.2.3/RD
Protection against mechanical damage
Securing of internal wiring
Insulation of conductors
Beads and ceramic insulators
Screws for electrical contact pressure
Insulating materials in electrical connections
Self-tapping and spaced thread screws
Termination of conductors
10 N pull test
Current rating and overcurrent protection
Result - Remark
Internal wires are adequate for the current they are intended to carry, see also appended
Table 7.7. Protection is provided by an external circuit breaker specified in Installation
Instructions and by circuit breakers and fuses incorporated in the equipment.
No sharp edges or corners.
Such insulators are not used
Not used for electrical connections.
All conductors are terminated by appropriate connectors.
See appended Table 4.5 Dimensions and rating of bus-bars and insulated conductors
Connection to power
General provisions for connection to power
Multiple supply connections
Permanently connected equipment
1. Separate means are provided for AC mains and external battery..
2. Plug connections are not used.
3. ELV circuits and
Hazardous voltage circuits are not accessible to an operator.
Set of terminals is provided in the Mains Power Connection
Board and Static Switch.
Verdict
P
P
P
P
P
P
P
P
N/A
P
P
P
P
P
N/A
P
P
P
P
P
TRF No. IEC62040_1A
Page 21 of 68 Report No. 9012326349
IEC 62040-1
Clause
3.2.4/RD
3.2.5/RD
Requirement + Test
Number of conductors, diameter of cable and conduits (mm) ................................................. :
Appliance inlets
Power supply cords
Result - Remark Verdict
5-wire, cable is specified in the
Installation Instructions.
⎯
N/A
Not supplied with the equipment.
N/A
3.2.5.1/RD AC power supply cords
Type ................................................................ :
N/A
⎯
Rated current (A), cross-sectional area (mm²),
AWG ................................................................ :
⎯
3.2.5.2/RD DC power supply cords
3.2.6/RD Cord anchorages and strain relief
Mass of equipment (kg), pull (N) .................... :
Longitudinal displacement (mm) ..................... :
3.2.7/RD
3.2.8/RD
N/A
N/A
⎯
⎯
Protection against mechanical damage
N/A
Cord guards
Diameter or minor dimension D (mm); test mass
(g) .................................................................... :
Radius of curvature of cord (mm) .................... :
N/A
⎯
⎯
P Set of terminals for permanent connection to AC mains.
More than one supply connection ................... :
The means of connection to
AC mains and to external batteries are not interchangeable. Terminal contacts are not hazardous live when disconnected from supply.
P
6.3
3.3/RD
Wiring terminals for external power conductors
Wiring terminals for connection of external conductors
P
P
3.3.2/RD
P
N/A Connection of non-detachable power supply cords
Screw terminals
Conductor sizes to be connected
3.3.3/RD
3.3.4/RD
3.3.5/RD
Rated current (A), cord/cable type, crosssectional area (mm2) ....................................... :
Wiring terminal sizes
Rated current (A), type, nominal thread diameter
(mm) ................................................................ :
Certified terminals are used.
AC Input: 420A, 2x70mm²;
AC Output: 360A, 2x70mm²
P
P
⎯
P
AC Input: 420A, bolt, M10;
AC Output: 360A, bolt, M10
⎯
TRF No. IEC62040_1A
Page 22 of 68 Report No. 9012326349
IEC 62040-1
Clause
3.3.6/RD
3.3.7/RD
Requirement + Test
Wiring terminal design
Grouping of wiring terminals
Result - Remark
Certified terminals are used.
Verdict
P
P
P
7.1 Enclosure The equipment enclosure complies with the requirements for fire, electrical and mechanical enclosures.
P
P
7.2
4.1/RD
7.3
4.2/RD
4.2.1/RD General
4.2.2/RD Steady force test, 10 N
4.2.3/RD
4.2.4/RD
Stability
Angle of 10
°
Test force (N) .................................................. :
Mechanical strength
Steady force test, 30 N
Steady force test, 250 N
P
P
250N P
P
P
⎯
P
P
4.2.6/RD
4.2.7/RD
Drop test; height (mm) .................................... :
Stress relief test Metal enclosure
P
P
P
N/A
⎯
4.2.8/RD
4.2.9/RD
4.2.10/RD
Cathode ray tubes
Picture tube separately certified ...................... :
High pressure lamps
Wall or ceiling mounted equipment; force (N) . :
N/A
⎯
N/A
N/A
7.4.1 Introduction
4.3.1/RD
4.3.2/RD
4.3.3/RD
4.3.4/RD
Edges and corners
Handles and manual controls; force (N) .......... :
Adjustable controls
Securing of parts
No sharp edges or corners
--
All screws are provided with lock washers.
P
P
P
N/A
N/A
P
TRF No. IEC62040_1A
Page 23 of 68 Report No. 9012326349
IEC 62040-1
Clause
4.3.5/RD
4.3.7/RD
4.3.11/RD
4.4/RD
Requirement + Test
Connection by plugs and sockets
Heating elements in earthed equipment
Containers for liquids or gases
Protection against hazardous moving parts
Result - Remark
IEC60320 connections are not used for SELV circuits.
No heating elements
All fans impellers are adequately guarded.
Verdict
P
N/A
N/A
P
4.4.1/RD General
4.4.2/RD
Protection in operator access areas ............... :
4.4.3/RD
4.4.4/RD
Protection in restricted access locations ......... :
Protection in service access areas
4.5.1/RD General
4.5.3/RD
4.5.4/RD
4.5.5/RD
P
P
N/A
N/A
P
P
P
Normal load condition per Annex L ................. : Maximum normal load: continuous operation with resistive load of 245 kW
(according to the manufacturer's specification)
Temperature limits for materials
P
P
Touch temperature limits
P
Resistance to abnormal heat .......................... :
(see appended table 7.4) P
TRF No. IEC62040_1A
Page 24 of 68 Report No. 9012326349
IEC 62040-1
Clause Requirement + Test
7.4.2 Openings
Result - Remark
7.4.3
7.4.4
Gas Concentration
Equipment movement set of 15 horizontal openings
7x120mm;
Rear panel – set of 29x9 openings 10x10mm.
Controller Module:
Top panel – set of 3x18 openings 2.5x30mm; opening Ø60mm for fan guard;
Front panel – set of hexagonal openings 4.0mm over an area
60x60mm (fan guard);
Rear panel – set of 2x37 opening 2.5x30mm.
Static Switch:
Left and right side panels – set of 3x15 openings 2x30mm.
Left and right sides of top cover – 2x4 openings
2x30mm.
Top panel of the Controller
Module is covered by Power
Module bottom without openings with distance approx.
10mm.
There are no openings vertically above parts at hazardous voltage.
There are no batteries within the equipment.
Test of 250N was done. No movement of the equipment was noted.
7.5
4.7/RD
4.7.1/RD
Resistance to fire
Reducing the risk of ignition and spread of flame
Method 1, selection and application of components wiring and materials
(see appended table 7.5)
Method 2, application of all of simulated fault condition tests
(see appended table 7.5)
4.7.2/RD Conditions for a fire enclosure
4.7.2.1/RD Parts requiring a fire enclosure
4.7.2.2/RD Parts not requiring a fire enclosure
4.7.3/RD Materials
4.7.3.1/RD General
Fire enclosure is required
All parts of modules
Verdict
P
N/A
P
P
P
P
N/A
P
P
N/A
P
P
TRF No. IEC62040_1A
Page 25 of 68 Report No. 9012326349
IEC 62040-1
Clause Requirement + Test
4.7.3.2/RD Materials for fire enclosures
4.7.3.3/RD
4.7.3.4/RD
Materials for components and other parts outside fire enclosures
Materials for components and other parts inside fire enclosures
Result - Remark
Metal enclosure for all modules
Side covers of the mounting rack are metal.
All components are frame rated min. V-2 and mounted on PCB rated min. V-1.
4.7.3.5/RD Materials for air filter assemblies
4.7.3.6/RD Materials used in high-voltage components
7.6
7.6.1
7.6.2
Battery location External battery is not supplied with equipment
Battery location and installation
Accessibility and maintainability
7.6.3 Distance
Verdict
P
P
P
N/A
N/A
7.6.5 Wiring
7.6.7 Ventilation
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
4.5.1/RD General
4.5.2/RD Temperature tests (see appended table 7.7)
Normal load condition per Annex L ................. :
Maximum normal load: continuous operation with resistive load of 245 kW
(according to the manufacturer's specification)
4.5.3/RD
4.5.4/RD
4.5.5/RD
Temperature limits for materials
Touch temperature limits
P
P
P
P
P
P
P
Resistance to abnormal heat .......................... : P
8
8.1
Electrical requirements and simulated abnormal conditions
General provisions for earth leakage
5.1.1/RD General
P
P
P
TRF No. IEC62040_1A
Page 26 of 68 Report No. 9012326349
IEC 62040-1
Clause
5.1.7/RD
Requirement + Test Result - Remark Verdict
Equipment with touch current exceeding 3,5 mA Measured protective conductor current was 300mA and does not exceed 5% of input current. Warning label is provided. Cross-section area of protective conductor is
45mm². The equipment is permanently connected.
P
8.2
5.2/RD
5.2.1/RD
5.2.2/RD
8.3 Abnormal operating and fault conditions
8.3.1 General
5.3.1/RD
5.3.4/RD
Protection against overload and abnormal operation
5.3.2/RD Motors
5.3.3/RD Transformers
(see appended table 8.3)
(see appended Annex B)
(see appended Annex C)
Functional insulation ........................................ :
Functional insulation was shorted
5.3.5/RD
5.3.9/RD
8.3.3
Electric strength
General
Test procedure
Electromechanical components
Compliance criteria for abnormal operating and fault conditions
Conditions for tests
(see appended table 8.2)
(see appended table 8.2)
Certified cooling fans
No fire occurred, no molten metal was emitted. No breakdown during electric strength test.
P
P
P
P
P
P
N/A
P
P
P
P
P
The appliance was operated at rated voltage.
P
9
6/RD
6.1/RD
Connection to telecommunication networks N/A
6.1.1/RD
6.1.2/RD
Protection of telecommunication network service persons, and users of other equipment connected to the network, from hazards in the equipment
Protection from hazardous voltages
Separation of the telecommunication network from earth
N/A
N/A
N/A
6.1.2.1/RD Requirements
Supply voltage (V) ........................................... :
N/A
⎯
Current in the test circuit (mA) ...................... :
⎯
6.1.2.2/RD
Exclusions ....................................................... : N/A
TRF No. IEC62040_1A
Page 27 of 68 Report No. 9012326349
IEC 62040-1
Clause
6.2/RD
Requirement + Test
6.2.2/RD Electric strength test procedure
6.2.2.1/RD Impulse test
6.2.2.2/RD Steady-state test
Result - Remark
Protection of equipment users from overvoltages on telecommunication networks
(see appended table 9)
(see appended table 9)
6.3/RD
3.5/RD
3.5.1/RD
3.5.2/RD
3.5.3/RD
Verdict
N/A
N/A
N/A
N/A
Protection of the telecommunication wiring system from overheating
Max. output current (A) ................................... :
N/A
N/A
N/A
⎯
Interconnection of equipment
General requirements
N/A
N/A
Types of interconnection circuits ..................... :
N/A
ELV circuits as interconnection circuits N/A
3.5.4/RD
2.1.3/RD
Data ports for additional equipment
Protection in restricted access locations
2.3.1/RD Limits
Type of TNV circuits......................................... :
N/A
N/A
N/A
⎯
2.3.2/RD Separation from other circuits and from accessible parts
N/A
2.3.2.1/RD
General requirements
2.3.2.2/RD Protection by basic insulation
2.3.2.3/RD
Protection by earthing
N/A
N/A
N/A
2.3.2.4/RD
Protection by other constructions .................... :
N/A
2.3.3/RD Separation from hazardous voltages N/A
2.3.4/RD
Insulation employed ......................................... :
Connection of TNV circuits to other circuits
⎯
N/A
Insulation employed ......................................... :
⎯
2.3.5/RD
2.6.5.8/RD
Test for operating voltages generated externally
Reliance on telecommunication network or cable distribution system
N/A
N/A
2.10.3.3/RD Clearances in primary circuits
2.10.3.4/RD Clearances in secondary circuits
(see appended table 5.7)
(see appended table 5.7)
N/A
N/A
2.10.4.1/RD General
2.10.4.2/RD Material group and comparative tracking index
CTI tests ........................................................... :
2.10.4.3/RD Minimum creepage distances
M/RD ANNEX M, CRITERIA FOR TELEPHONE RINGING SIGNALS (see 2.3.1/RD)
N/A
N/A
N/A
⎯
N/A
N/A
TRF No. IEC62040_1A
Page 28 of 68 Report No. 9012326349
IEC 62040-1
Clause Requirement + Test
M.1/RD Introduction
M.2 /RD Method A
M.3.1.1/RD
Frequency (Hz) ............................................... :
M.3.1.2/RD
Voltage (V) ...................................................... :
M.3.1.3/RD
Cadence; time (s), voltage (V) ........................ :
M.3.1.4/RD
Single fault current (mA) ................................. :
Result - Remark Verdict
N/A
N/A
N/A
N/A
⎯
⎯
⎯
⎯
M.3.2/RD
M.3.2.1/RD
Tripping device and monitoring voltage .......... :
N/A
Conditions for use of a tripping device or a monitoring voltage
⎯
M.3.2.2/RD
Tripping device
N/A
M.3.2.3/RD
Monitoring voltage (V) ..................................... :
N/A
A/RD
A.1/RD
Annex A, Tests for resistance to heat and fire
Flammability test for fire enclosures of movable equipment having a total mass exceeding 18 kg, and of stationary equipment (see 4.7.3.2/RD)
N/A
N/A
A.1.1/RD
Samples ........................................................... :
Wall thickness (mm)......................................... :
⎯
⎯
A.1.2/RD
A.1.3/RD
A.1.4/RD
Conditioning of samples; temperature (
°C) ..... : N/A
Mounting of samples ....................................... :
N/A
Test flame (see IEC 60695-11-3)
Flame A, B, C or D .......................................... :
N/A
⎯
A.1.5/RD
A.1.6/RD
A.2/RD
A.2.1/RD
A.2.2/RD
A.2.3/RD
A.2.4/RD
Test procedure
Compliance criteria
Sample 1 burning time (s) ................................ :
N/A
N/A
⎯
Sample 2 burning time (s) ................................ :
Sample 3 burning time (s) ................................ :
⎯
⎯
Flammability test for fire enclosures of movable equipment having a total mass not exceeding 18 kg, and for material and components located inside fire enclosures (see 4.7.3.2/RD and 4.7.3.4/RD)
Samples, material ............................................ :
Wall thickness (mm)......................................... :
N/A
⎯
⎯
Conditioning of samples; temperature (°C) ..... : N/A
Mounting of samples ....................................... : N/A
Test flame (see IEC 60695-11-4) N/A
TRF No. IEC62040_1A
Page 29 of 68 Report No. 9012326349
IEC 62040-1
Clause
A.2.5/RD
A.2.6/RD
A.2.7/RD
Requirement + Test Result - Remark Verdict
Flame A, B or C ............................................... :
⎯
Test procedure
N/A
Compliance criteria
Sample 1 burning time (s) ................................ :
N/A
⎯
Sample 2 burning time (s) ................................ :
Sample 3 burning time (s) ................................ :
⎯
⎯
Alternative test acc. to IEC 60695-11-5, cl. 5 and
9
Sample 1 burning time (s) ................................ :
N/A
⎯
A.3/RD
A.3.1/RD
A.3.2/RD
B.6.4/RD
B.7/RD
B.7.1/RD
Sample 2 burning time (s) ................................ :
Sample 3 burning time (s) ................................ :
Hot flaming oil test (see 4.6.2/RD)
Mounting of samples
Test procedure
⎯
⎯
N/A
N/A
N/A
N/A
B/RD Annex B, Motor tests under abnormal conditions (see 4.7.2.2/RD and 5.3.2/RD)
Position ............................................................ :
N/A
N/A
⎯
B.2/RD
B.3/RD
B.4/RD
B.5/RD
Manufacturer ................................................... :
Type ................................................................ :
Rated values .................................................. :
⎯
⎯
⎯
Test conditions
N/A
Maximum temperatures
N/A
Running overload test
Electric strength test: test voltage (V) ............. :
N/A
Locked-rotor overload test
Test duration (days) ........................................ :
N/A
⎯
⎯
N/A B.6/RD Running overload test for d.c. motors in secondary circuits
B.6.1/RD General N/A
N/A
N/A
Electric strength test; test voltage (V) ............. : N/A
Locked-rotor overload test for d.c. motors in secondary circuits
General
N/A
N/A
TRF No. IEC62040_1A
Clause
B.7.2/RD
B.7.3/RD
B.7.4/RD
B.8/RD
B.9/RD
B.10/RD
C/RD
Page 30 of 68 Report No. 9012326349
IEC 62040-1
Result - Remark Verdict Requirement + Test
Test procedure
Alternative test procedure
N/A
N/A
Electric strength test; test voltage (V) ............. : N/A
Test for motors with capacitors
N/A
Test for three-phase motors
N/A
Test for series motors
Operating voltage (V) ...................................... :
N/A
⎯
C.1/RD
C.2/RD
Annex C, Transformers (see 1.5.4/RD and 5.3.3/RD)
Position ............................................................ :
T1, T2, T4 (Card 1012, Power
Module)
T1 (Card 1776, Static Switch
Module)
P
⎯
Manufacturer ................................................... : Gamatronic
Type ................................................................ : Power Module: T1, T2 -
29TJIXDA; T4 - 29TJIXF;
Static Switch: 29TJIX.
Rated values .................................................. : 3000Vac between Primary and
Secondary winding
⎯
⎯
⎯
Method of protection ........................................ : 29TJIXDA T1, T2 (Card 1012
Power Module): overcurrent protection is provided by three independent methods: fuses in
Primary, thermal cut-off 85ºC, and consumption current feedback.
29TJIXF T4 (Card 1012 Power
Module): overcurrent protection is provided by two independent methods: fuse in
Primary and thermal cut-off
85ºC.
T1 (Card 1776 Static Switch
Module): overcurrent protection is provided by two independent methods: fuse in
Primary and consumption current feedback.
⎯
Overload test
See table 5.5 and 8.3 P
Insulation
P
Protection from displacement of windings ....... :
Margins are provided P
TRF No. IEC62040_1A
Page 31 of 68 Report No. 9012326349
IEC 62040-1
Clause
D/RD
D.1/RD
Requirement + Test Result - Remark
Annex D, Measuring instruments for touch current tests (see 5.1.4/RD)
Measuring instrument Simpson 228. Measuring scheme in accordance with
Figure D.1 of the Standard.
Verdict
P
P
N/A
E/RD
F/RD
Annex E, Temperature rise of a winding (see 1.4.13/RD) N/A
Annex F, Measurements of clearances and creepage distance (see 2.10/RD and Annex
G/RD)
P
G/RD
G.1/RD Clearances
Annex G, Alternative method for determining minimum clearances N/A
N/A
G.1.1/RD General
G.1.2/RD Summary of the procedure for determining minimum clearances
G.2/RD
G.2.1/RD
G.2.2/RD
G.2.3/RD
G.2.4/RD
G.3/RD
G.4/RD
G.4.1/RD
G.4.2/RD
G.4.3/RD
N/A
N/A
Determination of mains transient voltage (V)
AC mains supply ............................................. :
N/A
N/A
Earthed d.c. mains supplies ............................ :
N/A
Unearthed d.c. mains supplies ........................ :
N/A
Battery operation ............................................. :
N/A
Determination of telecommunication network transient voltage (V) ........................................ :
N/A
Determination of required withstand voltage (V)
N/A
Mains transients and internal repetitive peaks :
N/A
Transients from telecommunication networks . :
N/A
Combination of transients N/A
G.4.4/RD
G.5/RD
G.6/RD
H
Transients from cable distribution systems
Measurement of transient voltages (V) a) Transients from a mains supply
For an a.c. mains supply
For a d.c. mains supply b) Transients from a telecommunication network
Annex H, Guidance on protection against ingress of water and foreign objects
(see IEC 60529)
N/A
N/A
N/A
N/A
N/A
N/A
Determination of minimum clearances ............ :
N/A
N/A
TRF No. IEC62040_1A
Page 32 of 68 Report No. 9012326349
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict
I Annex I, Backfeed protection test
I.1 General
I.2
I.3
I.4
I.5
Test for pluggable UPS
Test for permanently connected UPS
Load-induced change of reference potential
Solid-state backfeed protection
(see clause 7.1-7.5 of IEC 62040-2 and clause
7.1-7.2 of IEC 62040-3)
P
P
N/A
P
N/A
N/A
J/RD Annex J, Table of electrochemical potentials (see 2.6.5.6/RD)
Metal(s) used ................................................... : Aluminium / Zn plated steel
(0.15V)
P
⎯
K/RD
K.1/RD
K.2 /RD
K.3/RD
K.4/RD
K.5/RD
K.6/RD
Annex K, Thermal controls (see 1.5.3/RD and 5.3.8/RD)
Certified thermal switch is used
Making and breaking capacity
N/A
N/A
Thermostat reliability; operating voltage (V) ... : N/A
Thermostat endurance test; operating voltage
(V) .................................................................... :
N/A
N/A Temperature limiter endurance; operating voltage (V) ....................................................... :
Thermal cut-out reliability
Stability of operation
L Annex L, Reference loads
L.1 General
Maximum normal load: continuous operation with resistive load of 245 kW
(according to the manufacturer's specification)
N/A
N/A
P
P
P
L.4
L.5
L.5.2
Reference capacitive-resistive loads
Reference non-linear load
Connection of the non-linear reference load
⎯
N/A
N/A
N/A
⎯
TRF No. IEC62040_1A
Page 33 of 68 Report No. 9012326349
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict
M Annex M, Ventilation of battery compartments
M.1 General
N/A
N/A
N/A
N/A
N/A
N P
U/RD
Annex N, Minimum and maximum cross-sections of copper conductors suitable for connection (see 6.3)
Annex U, Insulated winding wires for use without interleaved insulation
(see 2.10.5.4/RD)
N/A
⎯
V.2/RD
V/RD Annex V, AC POWER DISTRIBUTION SYSTEMS (see 1.6.1/RD)
V.1/RD Introduction
TN power distribution systems
P
P
P
TRF No. IEC62040_1A
Page 34 of 68 Report No. 9012326349
IEC 62040-1
Clause Requirement + Test
4.5 TABLE: List of critical components
Object/part no. Manufacturer/ trademark
Type/model
Result - Remark
Technical data
Verdict
P
Standard Mark(s) of conformity
1.
Mounting Rack
Power wiring
Flat cable
Various
DON Connex
Electronics
Various
L02 series
(UL 2651 Style)
10 mm², 600V, 105ºC
28 AWG, 300V, 105ºC,
VW-1
Aluminium, 15x5x1100 mm
VDE, UL
-- --
Interface board
PCB of the
PC1719,
PC1720
Power connector assembly
Hamehaber
Hamekasher
4610
Contact 5900 series:
6-12AWG, 600V
Housing 1300 series: V-0,
105ºC
Plated metal, 50A
UL tested Single female contact for grounding
LCD touch screen
Power Module
Circuit breaker
S101-S102
Fan
Various Various 5Vdc
MINEBEA 4715KL-07W
480/277Vac, 50A, characteristic C, 70ºC
48Vdc, 0.2A, 118CFM
--
UL, E89936
UL
Card PC1010
Fuse F1, F2
Relay K1-K10
X capacitor C5-
C7
Capacitor C1,
C2, C3
Varistor RV-1 -
RV-3
HINODE
OMRON
660GH-40UL 600Vac/dc, 40A
G8P-1AP Coil: 24Vdc, 36mA
Contact: 30A, 277Vac
2500Vac coil /contact,
105ºC
1000pF or 4700pF,
250Vac, Y2, 85ºC
CBB61 250Vac, 20 µF, 85ºC CHUANG GE
ELECTRONIC
THINKING TVR20621 395V, 6.5kA, 220J, 85ºC
UL
UL
UL, VDE
TRF No. IEC62040_1A
Page 35 of 68 Report No. 9012326349
IEC 62040-1
Clause Requirement + Test
Object/part no. Manufacturer/ trademark
Type/model
Result - Remark
Technical data
Current transformer L2,
L4, L6
GAMATRONIC 29TEMF Wire:
Pr. 2.0mm, INVEX
Sec. 0.16mm INVEX
Bobbin:
M-EI 35/18/2ST,
FORMERS, 2 section,
130ºC, V-0
Insulation tape:
IT7007
,
IDEAL TAPE,
2.5mil (0.063mm), 155ºC,
5000Vac.
Withstand voltage PR/SEC
3000Vac.
Choke L1, L3, L5 GAMATRONIC 29TEMX-TK Wire: 1.8mm, INVEX,
180ºC.
Insulation tape: IT7007
,
IDEAL TAPE, 2.5mil
(0.063mm), 155ºC,
5000Vac.
Verdict
Standard Mark(s) of conformity
1.
UL approved materials, tested in appliance
UL approved materials
GPCWM03 20A, 300Vac, 105ºC, V-0 UL, Connector P2 ANYTEC
Card PC 1011
:
Relay K1-K6 OMRON
SAMWHA
G8P-1AP Coil: 24Vdc, 36mA
Contact: 30A, 277Vac
2500Vac coil /contact,
105ºC
SCE2E type 4700pF, 250Vac, Y2, 85ºC UL, VDE
X capacitor C2-
C5
Varistor RV-1 -
RV-4
Current transformer L2,
L4, L6
HITANO VCR-20D681K 420V, 6.5kA, 230J, 85ºC
GAMATRONIC 29TEMF
UL, VDE
UL approved materials, tested in appliance
Wire:
Pr. 2.0mm, INVEX
Sec. 0.16mm INVEX
Bobbin:
M-EI 35/18/2ST,
FORMERS , 2 section,
130ºC, V-0
Insulation tape:
IT7007
,
IDEAL TAPE,
2.5mil (0.063mm), 155ºC,
5000Vac.
Withstand voltage PR/SEC
3000Vac.
TRF No. IEC62040_1A
Page 36 of 68 Report No. 9012326349
Current transformer
T1-T6
GAMATRONIC G9TEXD
IEC 62040-1
Clause Requirement + Test
Object/part no. Manufacturer/ trademark
Type/model Technical data
Wire:
Result - Remark
Pr. 1.0mm, INVEX
Sec. 0.2mm INVEX
Bobbin:
LODESTON, EFD type, V-
0, 150ºC
Verdict
Standard Mark(s) of conformity
1.
UL approved materials, tested in appliance
Voltage measuring transformer
T7-T9
THAI LIN
TL30D-090-
083
Input: 230Vac, 50Hz, 20 mA;
Output: 9Vac, 83mA
Dielectric strange: Pr/Sec
3750Vac
TUV
UL approved materials
Choke L1, L3, L5 GAMATRONIC 29TEMX-TK Wire: 1.8mm, INVEX,
180ºC.
Insulation tape:
IT7007
,
IDEAL TAPE,
2.5mil (0.063mm), 155ºC,
5000Vac.
Card 1012
:
Connector P1 ANYTEC
Fuse R311-314 Littelfuse
(Alternative) Bussmann
Relay K1
(fan circuits)
NINGBO
MULLER
GPCWM06
372 series
SR-5 series
JRC-19F 2C
3V 02
AM-01
300Vac, 20A, 105ºC, V-0
1A, 250V, Time-lag
1A, 250V, Time-lag
Coil: 24Vdc, 0.2W;
Contact: 30Vdc, 2A
Coil/contact 1000Vac, 70ºC
250Vac, 2.5A, 85ºC Thermal protector SW1,
SW2
Optical isolator
(fans control circuits)
FAIRCHILD H11L1M Double protection,
3500Vac.
UL, VDE
UL, VDE
UL, VDE
UL, VDE
TRF No. IEC62040_1A
Page 37 of 68 Report No. 9012326349
IEC 62040-1
Clause Requirement + Test
Object/part no. Manufacturer/ trademark
Type/model
Result - Remark
Technical data
Transformer T1,
T2
GAMATRONIC 29TJIXDA Input: 400V, 0.17A;
Output:
T1 – 8Vac, 0.09A;
8Vac, 1.0A;
13Vac, 0.3A;
T2 - 8Vac, 0.56A
8Vac, 1.0A,
13Vac, 0.22A
Wire:
Pr. 0.16mm, Pacific
Sec. 0.16mm, Pacific,
0.4mm, Totoku.
Bobbin:
EB30-P1212-F, Tokin, 1 section, 130ºC, V-0
Insulation tape:
1350F
,
IDEAL TAPE,
3.2mil (0.088mm), 130ºC,
7000Vac.
PR/SEC 3000Vac (to
SELV winding A -B).
Transformer T4 GAMATRONIC 29TJIXF Input: 400V, 0.15A
Output: 34V, 60W
Wire:
Pr. 0.32mm, Pacific
Sec. 0.4mm Pacific,
0.4mm, Totoku.
Bobbin:
EB30-P1212-F, Tokin, 1 section, 130ºC, V-0
Insulation tape:
1350F
,
IDEAL TAPE,
3.2mil (0.088mm), 130ºC,
7000Vac.
PR/SEC 1500Vac
Verdict
Standard Mark(s) of conformity
1.
UL approved materials, tested in appliance
UL approved materials, tested in appliance
PC1021
:
COSONIC CNR-20D301K 300V, 6.5kA, 220J, 85ºC UL, VDE Varistor RV1-
RV-6
Capacitor C1,
C3, C7, C8,
C11-C28
IGBT module MICROSEMI
VDE
UL, E145592
Sveeving OMERIN
APTGT100TL6
0
600V, 100A, 80ºC
Siligaine 16F3 600V, 155ºC UL
TRF No. IEC62040_1A
Page 38 of 68 Report No. 9012326349
IEC 62040-1
Clause Requirement + Test
Object/part no. Manufacturer/ trademark
Type/model
Result - Remark
Technical data
Verdict
Standard Mark(s) of conformity
1.
PC1022
Fuse F1, F2 HINODE 660GH-40UL 600Vac/dc, 40A, UL
Capacitor C1-3,
C7, C8, C11-
C24
IGBT module
Various Varios 330µF, 450V, 105ºC
MICROSEMI
APTGT100TL6
0
600V, 100A, 80ºC
VDE
UL, E145592
Controller Module
Power supply FSP Group FSP180-50NIV Input: 115/230V,
60/50Hz;
Outputs:
5V, 16A; 12V, 10A; 3.3V,
16.7A; -5V, 0.2A; -12V,
0.3A; 5V, 2A.
SELV, 50ºC
2408NL-04W 12Vdc, 0.11A, 17.6 CFM
UL60950-
1 IEC/EN
60950-1
UL, E190414
TUV, NEMKO
UL, E89936 Fan MINEBEA
Optical isolator
(Card 2MN070A)
FAIRCHILD H11L1M Double protection,
3500Vac.
Computer board VIA Embeded VB7001 120W, 45ºC CE
UL
Static Switch Module:
Fuse F101-F109 Bussmann
Fuse holder Bussmann
AGC series
HTB-48I
250V, 10A
250V, 20A, V-0
Contactor R101 ABB
Contactor R102 ABB
Contactor R103 ABB
Fan
Socket P101,
P102, P107,
P201, P202,
P303
UNITEDPRO
(XRL)
Connector P118,
P121
ANYTEC
DEGSON
A210-30-11 series
A210-30-11 series
A210-30-11 series
A9225H23B-
TC(X1)
TJ-3.5
8EDGK-5.0
690Vac, 350A (300A – UL),
690Vac, 400A (350A – UL)
690Vac, 500A (400A -UL)
230Vac, 50Hz, 13W, 33
CFM
300V, 10A, V-0
300Vac, 15A, V-0
UL, E19180
UL, E14853,
VDE
UL, E79416,
VDE
UL, E79416,
VDE
UL, E79416,
VDE
UL, VDE
UL, E228872
TRF No. IEC62040_1A
Page 39 of 68 Report No. 9012326349
IEC 62040-1
Clause Requirement + Test
Object/part no. Manufacturer/ trademark
Type/model
Power cable PHINO H05VV-F 250Vac, 10A, 3x0.75mm²,
90ºC, VW-1
Result - Remark
Technical data
Verdict
Standard Mark(s) of conformity
1.
VDE
Current transformer
T101-T103
Various
VW-1
GAMATRONIC 29TEXM Wire: 0.2mm INVEX
Bobbin: 2EBK30
Insulation tape:
IT7007
,
IDEAL TAPE,
2.5mil (0.063mm), 155ºC,
5000Vac.
Withstand voltage coil/case
1500Vac.
Optical isolator FAIRCHILD H11L1M Double protection,
3500Vac.
Card PC 1776
Transformer T1 GAMATRONIC 29TJIX
Connector P1,
P2, P7, P13,
P14, P20
Fuse F3
ANYTEC
HOLLY FUSE
GPCWM series
50F-010H
Input: 230V, 0.15A
Output: 8Vac, 0.5A
8Vac, 0.5A
16Vac, 1.0A
Wire:
Pr. 0.16mm, Pacific
Sec. 0.16mm, Pacific,
0.32mm, Totoku.
Bobbin:
EB30-P1212-F, Tokin, 1 section, 130ºC, V-0
Insulation tape:
1350F
,
IDEAL TAPE,
3.2mil (0.088mm), 130ºC,
7000Vac.
Withstand voltage PR/SEC
1000Vac
300V, 20A, V-0
Quick acting, 250V, 1A
Optical isolator
ISO3, ISO4
FAIRCHILD H11L1M Double protection,
3500Vac.
UL, E82910
UL approved materials, tested in appliance
UL, VDE
UL
CSA,
CA118061
UL
Supplementary information:
TRF No. IEC62040_1A
Page 40 of 68 Report No. 9012326349
IEC 62040-1
Result - Remark Verdict Clause
4.6,
1.6.2/RD
U (V)
207
208
207
228
Requirement + Test
TABLE: Electrical data (in normal conditions)
I (A)
390
400
397
356
Irated (A) P (W)
420 80 100
420
420
420
82 500
81 600
80 200
P
Fuse # Ifuse (A) Condition/status
Ext. CB -- Phase L1/ Maximum normal load
Ext. CB
Ext. CB
Ext. CB
--
--
--
Phase L2/ Maximum normal load
Phase L3/ Maximum normal load
Phase L1/ Maximum normal load
230
229
251
253
363
359
323
329
420
420
420
420
82 700
81 400
80 300
82 600
Ext. CB
Ext. CB
Ext. CB
Ext. CB
--
--
--
--
Phase L2/ Maximum normal load
Phase L3/ Maximum normal load
Phase L1/ Maximum normal load
Phase L2/ Maximum normal load
252 325 420 81 200 Ext. CB -- Phase L3/ Maximum normal load
Supplementary information: external battery charging mode with parameters V=864V, max.I=9A
5.1.1 and
2.1.1.7/RD
Condition
TABLE: discharge of capacitors in the primary circuit
τ
calculated
(s)
τ
measured
(s) t u
→ 0V
(s)
Comments
Note(s): no operator accessible connections
N/A
5.2.1 and
2.2.2/RD
Transformer
TABLE: SELV measurement (under normal conditions)
Location Voltage (max.) (V)
V peak V d.c.
T1
T1, T2
Power Module, PC1012
Static Switch, PC1776
11.0
11.0
17.9
---
---
---
Supplementary information:
5.2.1 and
2.2.3/RD
TABLE: SELV measurement (under fault conditions)
Location Voltage (max.) (V) Comments
Supplementary information: see Table 5.5.
TRF No. IEC62040_1A
Voltage Limitation
Component
TR construction
TR construction
P
P
Page 41 of 68 Report No. 9012326349
IEC 62040-1
Clause
5.2.3 and
2.4.2/RD
Location
Requirement + Test
TABLE: Limited current circuit measurement
Supplementary information:
TABLE: Limited power source measurement 5.2.5 and
2.5/RD
Voltage
(V)
Current
(mA)
Limits
Freq.
(kHz)
Result - Remark
Limit
(mA)
Comments
Measured
According to Table 2B/2C (normal condition) current (in A)
Verdict
N/A
N/A
Verdict apparent power (in VA)
According to Table 2B/2C (single fault condition) current (in A) apparent power (in VA)
Supplementary information:
5.3.1 and
2.6.3.4/RD
Location
TABLE: Resistance of earthing measurement
From main grounding stud to single female grounding contact on Mounting Rack
P
Resistance measured (m
Ω) Comments
6.0 For maximal length of the grounding conductor
(upper Power Module position).
11.0 From main grounding stud to Mounting Rack enclosure
From main grounding stud to Power Module enclosure
From main grounding stud to Controller Module enclosure
From main grounding stud to Static Switch enclosure
From main grounding stud to grounding tab connector P5 on the Static Switch PCB PC1776
Supplementary information:
15.0
For upper Power
Module position
11.0
11.0
22.0
TRF No. IEC62040_1A
Page 42 of 68 Report No. 9012326349
IEC 62040-1
Clause Requirement + Test
5.5 and 8.3 TABLE: Abnormal operating and fault conditions
Result - Remark Verdict
Power source for EUT: Manufacturer, model/type, output rating ......................................
Component No. Fault
Supply voltage (V)
Test time
Fuse
#
Fuse current (A)
Power Module
Phase to
Neutral output
Ambient temperature (°C) .....................................
Observation
P
⎯
⎯
(peak) Output circuit breaker opened in
1.5 sec. No hazard.
Power Module
DC output
(charging voltage)
Static Switch
Contactor
RA102 (bypass)
Closed during inverter operation
Static Switch
Triac CR101,
K5, K6
230Vac -- --
Shorted 230Vac -- --
(peak) Fuse F1 (Card PC1010) opened in
1 sec. No hazard.
-- Contactor RA101 opened immediately. Inverter is disconnected from load. No hazard.
-- Short circuit current 20.8A. Bypass operation mode activated within
2 sec. No hazard.
Power Module Card PC1012
:
Capacitor C2
(12V4 output)
Shorted 230Vac 1h -- -- Protection of IC1 operated.
Iscpeak=8A, Iscrms=3.5A.
Maximal stable temperature:
T1=112.5ºC, PCB near FET=45.0ºC.
No hazard.
Capacitor C22
(12VCCpwr output)
Shorted 230Vac 1h --
Capacitor C11
(12V2 output)
Capacitor C17
(20V2 output)
Shorted 230Vac 1h --
Shorted 230Vac 1h --
-- Protection of IC1 operated.
Iscpeak=11A, Iscrms=10A.
Maximal stable temperature:
T1=78ºC, PCB near CR18=211ºC.
No hazard.
-- Protection of IC1 operated.
Iscpeak=2A, Iscrms=1.0A.
Max. stable temperature:
T1=61.5ºC, PCB near CR16=52.8ºC.
No hazard.
-- Protection of IC1 operated.
Iscpeak=2.5A, Iscrms=1.0A.
Max. stable temperature:
T1=52.8ºC, PCB near CR17=46.1ºC.
No hazard.
TRF No. IEC62040_1A
Page 43 of 68 Report No. 9012326349
Capacitor C10
(5V ISO output)
IEC 62040-1
Clause
Capacitor C4
(20V ISO output)
Requirement + Test
Component No. Fault Supply voltage (V)
Test time
Fuse
#
Shorted 230Vac 1h --
Result - Remark
Fuse current (A)
Observation
-- Protection of IC1 operated.
Iscpeak=2.5A, Iscrms=1.6A.
Max. stable temperature:
Verdict
T1=122ºC, PCB near CR7 = 60ºC.
No hazard.
Shorted 230Vac 1h -- -- Protection of U1 operated.
Iscpeak=0.2A, Iscrms=0.2A.
Max. stable temperature:
T1=91ºC, PCB near CR7 = 67ºC.
No hazard.
R28
(feedback)
Capacitor C85
(24V 3 output)
Capacitor C49
(fan supply output))
Disconne cted
230Vac -- --
Shorted 230Vac 1h --
-- Max. peak voltage in output
20Vdc – 24V. No hazard.
-- Protection of IC1 operated.
Iscpeak=7.0A, Iscrms=4.7A.
Max. stable temperature:
T1=107.5ºC, PCB near CR43=
68.5ºC. No hazard.
Shorted 230Vac 1h -- -- Protection of IC2 operated.
Iscpeak=4.2A, Iscrms=4.0A.
Max. stable temperature:
PCB near Q4 = 95ºC. No hazard.
Power module Card 1013
:
Capacitor C54
(24Vdc to 5Vdc)
Shorted 230Vac 1h -- -- Protection of IC30 operated.
Iscpeak=1.5A, Iscrms=1.5A.
Max. stable temperature:
PCB near IC30=62.7ºC.
L2=194ºC. No hazard.
Diode CR55
(24Vdc to
12Vdc)
Shorted 230Vac 1h -- -- Iscpeak=0.18A, Iscrms=0.125A.
Max. stable temperature:
PCB near IC29=50.3ºC, T1=42.7ºC,
L1=41.5ºC. No hazard.
Static Switch Card PC1776
:
Capacitor C118
(+12V1 output)
Shorted 230Vac 1h --
Capacitor C129
(+12V2 output)
Shorted 230Vac 1h --
-- Protection of IC6 operated.
Iscpeak=4.0A, Iscrms=0.7A.
Max. stable temperature:
T1=55.0ºC,
PCB near CR104=57.8ºC.
No hazard.
-- Protection of IC6 operated.
Iscpeak=4.2A, Iscrms=1.0A.
Max. stable temperature:
T1=60ºC
PCB near CR108=56.8ºC.
No hazard.
TRF No. IEC62040_1A
Page 44 of 68 Report No. 9012326349
Capacitor C139
(24Vdc output)
IEC 62040-1
Clause Requirement + Test
Component No. Fault
Capacitor C135
(-12V2 output)
Supply voltage (V)
Test time
Fuse
#
Shorted 230Vac 1h --
Result - Remark
Fuse current (A)
Observation
-- Protection of IC6 operated.
Iscpeak=4.1A, Iscrms=1.0A.
Max. stable temperature:
T1 = 60.2ºC
PCB near CR113 = 57.2ºC.
No hazard.
Verdict
Shorted 230Vac 1h --
Capacitor C139
(-12V2 output)
R281
(feedback)
Shorted 230Vac 1h --
Discon. 230Vac -- --
Supplementary information:
-- Protection of IC6 operated.
Iscpeak=3.0A, Iscrms=0.78A.
Max/ stable temperature:
T1=59ºC
PCB near CR=58.6ºC.
No hazard.
-- Protection of IC6 operated.
Iscpeak=0.4A, Iscrms=0.4A.
Max.stable temperature:
PCB near R297=155.3ºC.
No hazard.
-- Max. peak voltage in output
24Vdc – 62.3Vdc. No hazard.
5.7 and
2.10.2/RD
Table: Working voltage measurement P
Location RMS voltage (V) Peak voltage (V) Comments
230 432
Power Module, Card 1012, transformer T1, between pins 1
(Pr) and 6 (Sec)
Static Switch, Card 1776, transformer T1, between pin 1 (Pr) and 5 (Sec).
Supplementary information:
230 325
TRF No. IEC62040_1A
Page 45 of 68 Report No. 9012326349
IEC 62040-1
Clause Requirement + Test Result - Remark
5.7 and
2.10.4/RD
TABLE: Clearance and creepage distance measurements
Clearance (cl) and creepage distance (cr) at/of/between:
U peak
(V)
U r.m.s.
(V)
Required cl (mm) cl
(mm)
Functional:
Power module
Line to Line
Power module
Line to Neutral
Required cr (mm)
Verdict
P cr
(mm)
565 400 2.0 8.0 4.0 8.0
325 230 1.5 4.0 2.5 4.0
565 400 2.0 7.8 4.0 7.8
Static switch
Line to Line
Static switch
Line to Neutral
325 230 1.5 4.0 2.5 4.0
325 230 1.5 4.0 2.5 4.0
Controller Module
Line to Neutral
Basic
/ supplementary:
Mounting Rack
L1/L2/L3/N to enclosure
Power Module
L1/L2/L3/N to enclosure (from
PC1010, PC1011, PC1012,
PC1021, and PC1022 cards
PCB mounted component leads to enclosure, minimal values).
325 230 1.5 5.0 2.5 6.0
325 230 1.5 3.0 2.5 5.5
Power module Card PC1012
From T1 pin 2 (Pr) to T1 pin 6
(Sec) tracks on PCB
Power module Card PC1012
From C85 (Pr) to CR8 (Sec,
Safety Zone) tracks on PCB
Static Switch Card 1776
From T1 pin1 to T1 pin 5 track
Reinforced:
432 230 1.5 4.0 2.5 4.0
432 230 1.5 8.0 2.5 8.0
325 230 1.5 3.0 2.5 3.0
Power Module Card 1012
From R96 (Pr) track to R5
(Safety zone) track
Static switch Card 1776
Between ISO3, ISO4 leads
Static switch Card 1776
Between pins 2 and 4 connector P8
Supplementary information:
432 230 3.0 9.5 5.0 9.5
325 230 3.0 7.0 5.0 7.0
325 230 3.0 5.0 5.0 5.0
TRF No. IEC62040_1A
Page 46 of 68 Report No. 9012326349
IEC 62040-1
Clause
5.8,
2.1.1.3/RD and 2.10.5.1
/RD
Requirement + Test
TABLE: Distance through insulation measurements
Distance through insulation (DTI) at/of:
U peak
(V)
Result - Remark
U r.m.s.
(V)
Test voltage
(V)
Required
DTI
(mm)
Verdict
N/A
DTI
(mm)
Supplementary information:
TRF No. IEC62040_1A
Page 47 of 68 Report No. 9012326349
IEC 62040-1
Clause Requirement + Test Result - Remark
6, 8.2 and 9 TABLE: Electric strength tests, impulse tests and voltage surge tests
Test voltage applied between: Voltage shape
(AC, DC, impulse, surge)
Test voltage
(V)
Functional:
Verdict
P
Breakdown
Yes / No
Basic
/ supplementary:
Mounting Rack
L1/L2/L3/N Input/ Output to Ground
Static Switch
L1/L2/L3/N Input/ Output to Ground
Static Switch
"+"/"-" battery output to Ground
Power Module
L1/L2/L3/N Input/ Output to Ground
Power Module
"+"/"-" battery output to Ground
Reinforced:
Mounting Rack
L1/L2/L3/N Input/Output to communication circuit
Power Module
L1/L2/L3/N Input/ Output to Internal communication circuit pins 1-4 terminal P8
Power Module
"+"/"-" battery output to Internal communication circuit pins 1-4 terminal P8
Static Switch
L1/L2/L3/N Input/Output to communication circuit
Static Switch
"+"/"-" battery output to communication circuit
Controller Module
L/N to communication circuit (LAN)
Supplementary information:
Voltage DC
Voltage DC
Voltage DC
Voltage DC
Voltage DC
Voltage DC
Voltage DC
Voltage DC
Voltage DC
Voltage DC
Voltage DC
2120
2120
2120
2120
2120
4240
4240
4240
4240
4240
4240
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
TRF No. IEC62040_1A
Page 48 of 68 Report No. 9012326349
IEC 62040-1
Clause Requirement + Test
7.4, 4.5.5/RD TABLE: Ball pressure test of thermoplastic parts
Result - Remark
Part
Allowed impression diameter (mm) ..................
≤ 2 mm
Test temperature
(°C)
Supplementary information:
Impression diameter
(mm)
Verdict
N/A
⎯
7.4.2,
Location
Table: Enclosure opening measurements
Size (mm) Comments
-- --
Supplementary information: see Cl. 7.4.2.
7.5
Part
Table: Resistance to fire
Manufacturer of material
Type of material Thickness
(mm)
Flammability class
N/A
--
N/A
Evidence
Supplementary information:
TRF No. IEC62040_1A
Page 49 of 68 Report No. 9012326349
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict
7.7 TABLE: Temperature test
P
Supply 207 207 253 253 --
⎯
Ambient T min
(
°C) ...........................
29 40* 28 40* --
⎯
Ambient T max
(
°C) ...........................
Maximum measured temperature T of part/at::
29 40* 28 40* --
T (
°C)
⎯
Allowed
T max
(
°C)
GENERAL
:
Mounting rack plastic cover 38.8 49.8 39.0 51.0 -- 95
Mounting rack metal accessible part 32.7 43.7 32.8 44.8 -- 70
Power module
:
AC input connector
AC input CB
AC input choke L1
DC connector P2
AC input relay K1
PCB near coil L1
Capacitor Electrolyte C1
AC output choke L3
Current transformer G9TEXD
Current transformer 29TEMF
AC output relay K4
AC output CB
Flat cable
AC output connector
Controller module
:
35.3
45.9
46.3
56.9
35.2
49.6
47.2
61.6
--
--
85
70
75.8 86.8 82.1 94.1 -- 165
52.1 63.1 55.3 67.3 -- 105
48.9 59.9 53.1 65.1 -- 85
56.7
36.6
67.7
47.6
59.8
35.3
71.8
47.3
--
--
85
105
33.7 44.7 34.6 46.6 -- 105
38.8 49.8 40.9 52.9 -- 105
35.0
40.8
46.0
51.8
35.8
45.2
47.8
57.2
--
--
105
165
35.8
38.5
45.1
41.8
32.5
38.5
46.8
49.5
56.1
52.8
43.5
49.5
37.9
43.1
49.6
49.0
33.2
40.6
49.9
55.1
61.6
61.0
45.2
52.6
--
--
--
--
--
--
120
120
105
70
105
85
Relay
Flat cable
Connector P5
PS output connector
Lithium battery
35.4 46.5 36.9 48.9 -- 50
44.2 55.2 46.3 58.3 -- 105
42.7 53.7 45.0 57.0 -- 70
42.6
48.1
53.6
59.1
44.9
51.8
56.9
63.8
--
--
105
85
44.8
43.3
55.8
54.3
47.8
45.2
59.8
57.2
--
--
85
70
TRF No. IEC62040_1A
Clause Requirement + Test
Maximum measured temperature T of part/at::
Page 50 of 68 Report No. 9012326349
IEC 62040-1
Result - Remark Verdict
PCB near processor
Static Switch module
Tubing for flat cable
Connector "Inv s"
Relay
59.0 70.0
T (
°C)
61.9 73.9 --
Allowed
T max
(
°C)
105
--
39.4 50.4 53.0 65.0 -- 70
39.2 50.2 43.4 55.4 -- 90
40.2 51.2 42.3 54.3 -- 105
38.6 49.6 39.0 51.0 -- 105
40.8 51.8 41.7 53.7 -- 85
41.2 52.2 43.3 55.3 -- 105
50.5 61.5 54.3 66.3 -- 105
49.3 60.3 51.8 63.8 -- 120
43.5 54.5 45.5 57.5 -- 105 PCB near transformer
Supplementary information:
Temperature T of winding: t
1
(°C)
R
1
(
Ω) t
2
(°C)
R
2
(
Ω)
T (
°C)
Allowed
T max
(
°C)
Insulation class
Supplementary information:
TRF No. IEC62040_1A
Page 51 of 68 Report No. 9012326349
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict
8.3.2. TABLE: Temperature test. Abnormal operation.
A – front ventilation openings blocked.
B - rear ventilation opening blocked.
P
Supply ...........................: 230 230 230 230 --
⎯
Ambient T min
(
°C) .............................:
29 40* 29 40* --
⎯
Ambient T max
(
°C) ............................:
29 40* 29 40* --
⎯
Maximum measured temperature T of part/at::
A A B B
T (
°C) Allowed
T max
(
°C)
GENERAL
:
Mounting rack plastic cover
Mounting rack metal accessible part
42.6
35.2
53.6
46.2
38.9
33.3
49.9
44.3
--
--
--
--
Power module
:
AC input connector
AC input CB
AC input choke L1
DC connector P2
AC input relay K1
PCB near coil L1
Capacitor Electrolyte C1
AC output choke L3
Current transformer G9TEXD
Current transformer 29TEMF
AC output relay K4
AC output CB
Flat cable
AC output connector
Controller module
:
49.0
46.2
60.0
57.2
36.2
52.1
47.2
63.1
--
--
--
--
129.6 140.6 81.1 92.1 -- 265
68.1 79.1 55.8 66.8 -- --
53.0 64.0 48.7 59.7 -- --
42.0
44.4
53.0
55.4
46.0
36.5
57.0
47.5
--
--
--
--
63.0 74.0 35.3 46.3 -- --
75.3 86.3 39.7 50.7 -- --
67.1
75.0
78.1
86.0
39.9
48.9
50.9
59.9
--
--
--
265
71.8
78.3
42.5
82.8
89.3
53.5
40.9
45.1
50.0
51.9
56.1
61.0
--
--
--
215
215
--
42.4
46.8
49.6
53.4
57.8
60.6
47.9
34.9
43.9
58.9
45.9
54.9
--
--
--
--
--
--
Relay
Flat cable
Connector P5
50.4 61.4 48.1 59.1 -- --
50.2 61.2 47.7 58.7 -- --
48.7 59.7 46.2 57.2 -- --
48.6 59.6 46.3 57.3 -- --
56.8 67.8 53.8 64.8 -- --
TRF No. IEC62040_1A
Page 52 of 68 Report No. 9012326349
IEC 62040-1
Clause Requirement + Test
Maximum measured temperature T of part/at::
Result - Remark Verdict
PS output connector
Battery
PCB near processor
Static Switch module
52.1
66.3
63.1
48.9 59.9 46.5 57.5 -- --
77.3
T (
°C)
49.5
63.6
60.5 --
Allowed
T max
(
°C)
--
74.6 -- --
Tubing for flat cable
Connector "Inv s"
Relay
67.0 78.0 63.8 74.8 -- --
46.9 57.9 44.7 55.7 -- --
45.3 56.3 43.6 54.6 -- --
41.3 52.3 40.0 51.0 -- --
44.3 55.3 43.0 54.0 -- --
46.1 57.1 44.6 55.6 -- --
57.5 68.5 55.7 66.7 -- --
54.3 65.3 53.0 64.0 -- 215
PCB near transformer 47.8 58.8 46.7 57.7 -- --
Supplementary information: self-reseting internal thermal protection of the Power module operated.
Maximum maesured temperature values for stady state conditions are specified in Table.
Temperature T of winding: t
1
(°C)
R
1
(
Ω) t
2
(°C)
R
2
(
Ω)
T (
°C)
Allowed
T max
(
°C)
Insulation class
Supplementary information:
8.1 P
Condition
TABLE: earth leakage current
L
→ terminal
A
(mA)
N
→ terminal
A
(mA)
Limit
(mA)
Comments
Phase L1
Phase L2
Phase L3
"+" output
21
23
23
3.8
3.6
3.6
3.6
--
3.5
3.5
3.5
3.5
Equipment is evaluated as equipment with high leakage current. Suitable label is provided. Also see supplementary information.
" – " output 3.7 -- 3.5
Supplementary information:
1) min. input current – 360A. Protective conductor current is 0.3A < 0.05*360A= 18A.
TRF No. IEC62040_1A
Page 53 of 68 Report No. 9012326349
IEC 62040-1
Clause Requirement + Test Result - Remark Verdict
P
Transformer part name:
Manufacturer:
Type:
See appended table 4.3
See appended table 4.3
Recurring peak voltage
Required clearance for reinforced
PC1012 T1/T2
GAMATRINIC
29TJIXDA
432V insulation (from table 2H and 2J)
Effective voltage rms
4.0mm
230V
Required creepage distance for reinforced insulation (from table 2L)
Measured min. creepage distance
Location
Winding A-B (Secondary) to winding 1-2 (Primary)
Measured min. clearances
Location
5.0mm inside (mm)
7.0 inside (mm) outside (mm)
13.5
Pin numbers
Prim. 1 – 2 outside (mm)
Winding A-B (Secondary) to winding 1-2 (Primary) --- >20mm
Construction:
Bobbin
Material PBT manufacturer by NEC TOKIN
Thickness 2.0mm
Electric strength test
With AC 3000V after humidity treatment
Result Pass
TRF No. IEC62040_1A
Page 54 of 68 Report No. 9012326349
IEC 62040-1
Clause
M
Requirement + Test
Ventilation of battery compartments
Result - Remark
The required dimension for the ventilation openings will be calculated with the following formula:
A > K1 * Q with Q = (0.054 m³/Ah) * n * I * C
where:
K1 : constant factor of 28 h * cm²/m³
Q : airflow in m³/h n :
I : batteries)
C : number of battery cells constant factor (0,2A/100Ah for valve regulated lead acid nominal capacity of the battery n
With the specific data for the UPS the following dimension for the ventilation openings is required:
: ?
Verdict
N/A
A > 28 h * cm²/m³ * (0.054 m³/Ah) * n * 0.2 A/100 Ah * C
A > ? cm²
Verdict
The size of ventilation openings in battery cabinet exceeds the required airflow by far (as well as the UPS).
TRF No. IEC62040_1A
Page 55 of 68 Report No. 9012326349
List of test equipment used:
Clause Measurement
/ testing
Testing / measuring equipment / material used Range used
Calibration date
SII Ref.
No.
Instrument Type Manufacturer Model Last Due
4.6
1.6.2.RD
5.5
8.3
5.5
8.3
5.1.1
2.1.1.7RD
5.7
2.10.2RD
8.1
Power measuremets
Current measurements
Voltage measurements
Current and voltage measurements
4875 Power Fluke
564544 DC/AC Clamp Meter
5047 True RMS Multimeter
53930
Industrial
Scopemeter
Prova
Instruments
Fluke
434 auto 11/10
87 III
0-500
Vac
02/10 02/11
4.7.16
1.7.11/RD
7.2
4.1RD
3.1.2RD
Leakage current
Durability of markings
Steady force test
Sharp edge testing
6420
--
52839
Leakage current tester
N-hexane
Test probe 250N
54412 Sharp Edge Tester
BIO-LAB
PTL
Underwriters
Laboratories
CAS # 110-54-3 --
P10.64 --
10/07 10/12
06/10 06/11
5.5
7.7
8.3.2.
Temperature measurements
5005
53934
564521
Data
Acquisition/Switch
Unit with
Thermocouples Type
J
20-Channel Armature
Multiplexer
20-Channel Armature
Multiplexer
Agilent
34970A
S/N
US37030301
34901A
S/N
US37242806
34901A
S/N
US37257353 auto 11/09 11/10
5.5
7.7
8.3.2.
6.
8.2
9
5.3.1
2.6.3.4RD
Temperature measurements
Electric strength tests
Grounding bonding resistance
5.7
2.10.4RD
7.4.2
Mechanical measurements
TRF No. IEC62040_1A
563019 Stopwatch / Timer
5971
AC/DC Withstand
Voltage Tester
5972 Ground Bond Tester
Extech
Instruments
Associated
Research
Associated
Research
52697 Digital CD-6”R 07/11
Page 56 of 68 Report No. 9012326349
APPENDIX 1
PHOTOGRAPHS
TRF No. IEC62040_1A
Page 57 of 68 Report No. 9012326349
Fig. 1
General view of the system
TRF No. IEC62040_1A
Page 58 of 68 Report No. 9012326349
Fig. 2
Power Module – overall external views
TRF No. IEC62040_1A
Page 59 of 68 Report No. 9012326349
Fig. 3
Power Module internal view
TRF No. IEC62040_1A
Page 60 of 68 Report No. 9012326349
Fig. 4
Controller – overall external views
TRF No. IEC62040_1A
Page 61 of 68 Report No. 9012326349
Fig. 5
Controller – internal view
TRF No. IEC62040_1A
Page 62 of 68 Report No. 9012326349
Fig. 6
Static Switch – overall external views
TRF No. IEC62040_1A
Page 63 of 68 Report No. 9012326349
Fig. 7
Static switch – internal view
TRF No. IEC62040_1A
Page 64 of 68 Report No. 9012326349
APPENDIX 2
ELECTRICAL SCHEMATICS
TRF No. IEC62040_1A
Page 65 of 68 Report No. 9012326349
Fig. 1
Controller
TRF No. IEC62040_1A
Page 66 of 68 Report No. 9012326349
Fig. 2
Static switch
TRF No. IEC62040_1A
Page 67 of 68 Report No. 9012326349
Fig. 3
Power Module. PC1012 board
TRF No. IEC62040_1A
Page 68 of 68 Report No. 9012326349
Fig. 4
Static Switch. PC 1776 board
TRF No. IEC62040_1A
Page 1 of 4 Report No. 9012326349
APPENDIX 3
EUROPEAN GROUP DIFFERENCES AND
NATIONAL DIFFERENCES
(EN 62040-1: 2008)
Page 2 of 4
IEC 62040_1A - ATTACHMENT
Result - Remark
Report No.: 9012326349
Verdict Clause Requirement + Test
ATTACHMENT TO TEST REPORT IEC 62040-1
EUROPEAN GROUP DIFFERENCES AND NATIONAL DIFFERENCES
Uninterruptible power systems (UPS) –
Part 1: General and safety requirements for UPS
Differences according to................ : EN 62040-1:2008
Attachment Form No...................... : EU_GD_IEC62040_1A
Attachment Originator ................... : Nemko
Master Attachment ......................... : Date (2010-06)
Copyright © 2010 IEC System for Conformity Testing and Certification of Electrical Equipment
(IECEE), Geneva, Switzerland. All rights reserved.
EN 62040-1:2008 – CENELEC COMMON MODIFICATIONS
Clause
Contents
EN 62040-1, GROUP DIFFERENCES (CENELEC common modifications EN)
Result - Remark Requirement + Test
Add the following annexes:
Annex ZA (normative) Normative references to international
Verdict
P
publications
Annex ZB (normative) Special national conditions
Clause
Clause
ZA
Requirement + Test
Page 3 of 4
IEC 62040_1A - ATTACHMENT
Result - Remark
Report No.: 9012326349
Verdict
EN 62040-1, GROUP DIFFERENCES (CENELEC common modifications EN)
Requirement + Test Result - Remark
NORMATIVE REFERENCES TO INTERNATIONAL PUBLICATIONS WITH
THEIR CORRESPONDING EUROPEAN PUBLICATIONS
The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
Note: When an international publication has been modified by common modifications, indicated by (mod), the relevant EN/HD Applies.
Verdict
⎯
Page 4 of 4
IEC 62040_1A - ATTACHMENT
Report No.: 9012326349
Clause Requirement + Test Result - Remark Verdict
ZB ANNEX (normative)
SPECIAL NATIONAL CONDITIONS (EN)
The FI, NO and SE - SNCs originate from IEC 60950-1 2 nd
Edition, which is the reference document (RD) for IEC 62040-1. The national requirements are included in IEC 62040-1 through the following statement in the scope of the standard:
“National requirements additional to those in IEC 60950-1 apply and are found as notes under relevant
clauses of the RD.”
The national requirements have not been specifically listed in the EN 62040-1:2008.
If demanded, CLC/TC 22X will be requested to take proper measures to complete EN 62040-1 with
Annexes ZB containing the SNCs as presented below.
EN 62040-1:2008 supersedes EN 62040-1-1:2003. As a reference, see also SNCs for Finland, Norway and
Sweden as included in the earlier EN 62040-1-1:2003
Clause
4.7.3
Verdict
N/A
4.7.11
Requirement + Test Result - Remark
In Finland, Norway and Sweden, when safety relies upon connection to the safety earth (see
5.3), a pluggable equipment type A UPS shall have a marking on the equipment, stating that the
UPS must be connected to an earthed mains socket-outlet.
The marking text in the applicable countries shall be as follows:
In Finland: "Laite on liitettävä suojakoskettimilla varustettuun pistorasiaan"
In Norway: “Apparatet må tilkoples jordet stikkontakt”
In Sweden: ”Apparaten skall anslutas till jordat uttag”
Not pluggable equipment
In Norway, because of a widely used IT power system, equipment shall be designed or modified
for connection to such a system and shall be marked by a label with the following wording in
Norwegian:
“Apparatet er egnet for tilkopling til et IT forsyningsnett”
Not tested for IT power system
No TNV circuitry of 6.1.2.1 and 6.1.2.2 in Annex ZB of EN 60950-
1:2001 apply.
N/A
N/A