BJ194E-9S4 Multifunction Power Meter User Manual


Add to my manuals
27 Pages

advertisement

BJ194E-9S4 Multifunction Power Meter User Manual | Manualzz

Chongqing Blue Jay Electronic Co.,Ltd Product Manual

BJ194E-9S4 Multifunction Power Meter

User Manual

`

Tel: +0086-023-86850812 Email:[email protected]

Fax:+0086-023-67636974

Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District, Chongqing

Chongqing Blue Jay Electronic Co.,Ltd Product Manual

Read me

When you use BJ194E-9S4 series Multifunction Power Meter, be sure to carefully read this user manual, and be able to fully understand the implications, the correct guidance of operations in accordance with user manual, which will help you make better use BJ194E-

9S4 series Multifunction Power Meter, and help to solve the various problems at the scene.

1. Before the meter turning on the power supply, be sure that the power supply within the provisions of the instrument;

2. When installation, the current input terminal must non-open, voltage input terminals must

Non-short circuit;

3. Communication terminal (RS232 or RS485) is strictly prohibited to impose high pressure;

4. Be sure the instrument wiring consistent with the internal system settings;

5. When communicating with the PC, instrument communication parameters must be consistent with the PC

Please read carefully before using this user manual

Please save this document

Tel: +0086-023-86850812 Email:[email protected]

Fax:+0086-023-67636974

Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District, Chongqing

- 1 -

Chongqing Blue Jay Electronic Co.,Ltd Product Manual

Directory

CONTENTS Page

1. SUMMARIZE------------------------------------------------------------------------------------------------------- 3

2. APPLICATIONS --------------------------------------------------------------------------------------------------- 3

3. FEATURES --------------------------------------------------------------------------------------------------------- 4

3.1. - Electricity metering ---------------------------------------------------------------------------------------- 4

3.2. - Specifications ----------------------------------------------------------------------------------------------- 5

4.- INSTALLATION AND START-UP ------------------------------------------------------------------------- 7

4.1. – Installation ------------------------------------------------------------------------------------------------ 7

4.2. - Connection Terminal (see label on the rear part) -------------------------------------------------- 8

4.3. - Connection Drawing for the BJ194E-9S4 ----------------------------------------------------------- 10

5. SCREEN DISPLAY ------------------------------------------------------------------------------------------- 12

5.1. - Panel Diagram --------------------------------------------------------------------------------------------- 12

5.2. - Display Summary ----------------------------------------------------------------------------------------- 12

6. OPERATING INSTRUCTIONS ------------------------------------------------------------------------------- 13

7. SETUP PROCEDURE ------------------------------------------------------------------------------------------ 14

7.1. - Password Enter -------------------------------------------------------------------------------------------- 14

7.2. - System Display Settings --------------------------------------------------------------------------------- 14

7.3. - Input Signal Selection ------------------------------------------------------------------------------------ 16

7.4. - Communication Preferences --------------------------------------------------------------------------- 20

7.5. - Menu Structure -------------------------------------------------------------------------------------------- 22

7.6. - Display Character instructions ------------------------------------------------------------------------- 23

8.

SAFETY CONSIDERATIONS -------------------------------------------------------------------------------- 24

9. MAINTENANCE -------------------------------------------------------------------------------------------------- 24

10. TECHNICAL SERVICE --------------------------------------------------------------------------------------- 25

Tel: +0086-023-86850812 Email:[email protected]

Fax:+0086-023-67636974

Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District, Chongqing

- 2 -

Chongqing Blue Jay Electronic Co.,Ltd Product Manual

1. - SUMMARIZE

BJ194E-9S4 Series Multifunction Power Meter is used for power quality monitoring, factory automation and building automation.

It can measure all of the power parameters in power grid:

Current, Reactive power,

Voltage,

Frequency,

Apparent power,

Energy,

Active power, Power factor,

Also can transmit the parameter into 1 route analog output or 1 route pulse output. For transformers, generators, capacitor banks and motors of the distributed detection, automatic control system, on-line monitoring display.

It can replace the traditional analog or many digital measurement instruments (such as ammeter, voltmeter, power meter, power factor meter, frequency meter, etc.), greatly reduce system cost, convenient on-site wiring, improve system reliability. BJ194E-9S4 Multifunction

Power Meter has serial port, can connection to PC; Uses Modbus to set programming and read the data.

Based on this power meters, can simply set up a monitoring system, that only use the IPC and central software.

2. - APPLICATIONS

◆ All power parameter measurement;

◆ Power factor measurement and control;

◆ Energy Measurement;

◆ Replace the three-phase power meter, three phase electricity transmitter;

◆ Transformers, generators, capacitors and electric motors distributed detection;

◆ Medium and low pressure systems;

◆ SCADA, EMS, DCS integrators.

Tel: +0086-023-86850812 Email:[email protected]

Fax:+0086-023-67636974

Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District, Chongqing

- 3 -

Chongqing Blue Jay Electronic Co.,Ltd Product Manual

3. - FEATURES

3.1. - Electricity metering

By means of an internal microprocessor it simultaneously measures:

Parameter

Single phase voltage

*Phase-phase voltage

Current

Frequency

Power factor

Active power

Reactive power

Active energy

Reactive energy

Symbol A-phase B-phase C-phase Average

V

V

A

x

x

x

x

x

x

x

x

x

Hz

Cos Φ

W

Var

x x

x x

x x

x x

x x

x x

x x

x x

x x

x

x

x

x

Wh

Varh

x x x x x x x

x

Notes: Phase-phase voltage is Uab, Ubc, Uca, voltage data determined by the different wiring

Available: x: Display and communications xx: Communications.

The 194E-9S4 delivers the visualization of above listed parameters by means of three line 4-digit, led type displays. Up to 3 parameters can be simultaneously read in the screen.

“▽”Indicator LED shows currently displayed the parameters, “

K” means in thousands, “

M” means in million.

OTHER FEATURES

- Low-size (96 x 96 mm), panel-mounting meter.

- True R.M.S. measuring system.

- Instantaneous, maximum and minimum values of each measured parameter.

- Energy measurement (indication through a lighting led)

- RS-485 or RS-232 type communication to a PC (optional)

Tel: +0086-023-86850812 Email:[email protected]

Fax:+0086-023-67636974

Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District, Chongqing

- 4 -

Chongqing Blue Jay Electronic Co.,Ltd Product Manual

3.2. - Specifications

1. - Reference standard:

Basic electricity: GB/T13850-1998 (IEC688-1992)

Active power: GB/T17215-2002 (IEC61036:2000)

Reactive power: GB/T17882-1999 (IEC61268:1995)

2- Accuracy standards

Parameter

Voltage

Current

Active Power

Reactive Power

Apparent power

Power Factor

Active Energy

Reactive Energy

Frequency

Accuracy A phase B phase C phase

0.5%fs

0.5%fs

0.5%fs

0.5%fs

0.5%fs

0.5%fs

1%rd

2%rd

0.05%rd

V1

A1

W1 var1

VA1

PF1

V2

A2

W2 var2

VA2

PF2

V3

A3

W3 var3

VA3

PF3

All

W var

VA

PF

Wh varh

Hz

Averag e

VE

AE

3. - Input

Voltage: Rated 400V (optional 100V)

Current: Rated 5A (optional 1A)

Frequency: 45-65Hz

4. - Load

Voltage: <0.5VA / phase (rated 220V)

Current: <0.5VA / phase (rated 5A)

5. - Overload

Current: 1.2 times rated continuous; 10 seconds for 10 times the rated

Voltage: 1.2 times the rated continuous; 10 seconds for 800V

6. - Dielectric strength

IEC 688 / IEC 255-3 (1989)

2kV AC RMS 1 minute, between input / output / case / power supply

Tel: +0086-023-86850812 Email:[email protected]

Fax:+0086-023-67636974

Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District, Chongqing

- 5 -

Chongqing Blue Jay Electronic Co.,Ltd Product Manual

7. - EMC Test

Electrostatic discharge immunity test:

Electrical fast transient burst immunity test standard

IEC-61000-4-2 level 4

IEC61000-4-4 level 3

Surge (Shock) immunity test

IEC61000-4-5 level 4

8. - Work environment

Temperature: -20℃~ +60℃

Humidity: RH 20%~95%(No condensation)

9. - Protection

Panel: IP40

10. - Storage Conditions

Temperature:-25℃~+70℃

Humidity: RH 20%~95%

11. - Working Power

AC 80-265V, 45-65Hz, DC 80-380V

DC 20-60V (Optional)

Maximum power consumption 6W

12. - Dimensions

L × W × H =96mm×96mm×128mm

13. - Installation hole size

L × W = (91+0.8mm) × (91+0.8mm)

Test voltage

8Kv

Input 1kV; Power supply 2kV common mode test voltage

4kV

Tel: +0086-023-86850812 Email:[email protected]

Fax:+0086-023-67636974

Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District, Chongqing

- 6 -

Chongqing Blue Jay Electronic Co.,Ltd Product Manual

4.- INSTALLATION AND START-UP

The manual you hold in your hand contains information and warnings that the user should respect in order to guarantee a proper operation of all the instrument functions and keep its safety conditions. The instrument must not be powered on and used until its definitive assembly on the cabinet’s door.

If the instrument is not used as manufacturer’s specifications, the protection of the instrument will be damaged.

When any protection failure is suspected to exist (for example, it presents external visible damages),the instrument must be immediately powered off. In this case contact a qualified service representative.

4.1.- Installation

Mounting

Instrument is to be mounted on panel (cut-out 91+0.8 x 91+0.8 mm). All connections keep inside the cabinet.

Note that with the instrument powered on, the terminals could be dangerous to touching and cover opening actions or elements removal may allow accessing dangerous parts.

Therefore, the instrument must not be used until this is completely installed.

Notes:

Input signal: BJ194E using a separate acquisition calculate for each measurement channel, to ensure consistent in use, for different load forms, its a variety of connection mode.

A. Voltage input:

Input voltage should not exceed the rated input voltage products (100V or 400V),

Otherwise, should use external CT, the input voltage to be installed in the 1A fuse.

B. Current Input:

Standard input current is 5A, if greater than 5A should use external CT.

Even if you are using on the CT are connecting with other instruments, wiring methods should be used in series. Before remove the current input connection, must be sure to disconnect the primary circuit or shorted secondary circuit of CT. Suggest using the terminal block, please not directly connect to CT, in order to facilitate disassembly.

C. Please make sure that the input voltage and current corresponding to the same phase

Tel: +0086-023-86850812 Email:[email protected]

Fax:+0086-023-67636974

Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District, Chongqing

- 7 -

Chongqing Blue Jay Electronic Co.,Ltd Product Manual

sequence, and the same direction; Otherwise, the Values and symbols will wrong!!

(Power and Energy)

The input network configuration of instrument depends on the CT number of the system: in the condition of 2 CT, select the three-phase, three-lines two components; in the condition of 3 CT, select the three-phase, four-lines three component mode.

Instrument connection mode, set of the instrument (programming input network NET) should be the same load wiring as measured wiring. Otherwise, the measurement instrument will lead to incorrect voltage or power.

In three-phase three-wire mode, the measurement and shows the line voltage;

In three-phase four-wire mode, the measurement and shows the phase voltage.

Auxiliary power:

BJ194E Series Multifunction Power Meter with universal (AC / DC) power input, if not for a special statement, we provide the 220VAC/DC or 110VAC/DC power interface for standard products. Instruments limit work power supply : AC / DC :80-270V, please ensure that the auxiliary power can match for BJ194E series meter to prevent damage to the product.

A. Suggest install 1A fuse in the fire line side.

B. For the areas with poor power quality, suggest install lightning surge suppressor and rapid burst suppressor to prevent lightning strikes.

4.2. - Connection terminal (see label on the rear part)

Terminal description

Upper connection terminal

1 2 58 59 60 46 47 48 49

Power supply

RS485A RS485B GUD AP+ AP- RP+ RP-

1. *Supply voltage input: 0 V

2. *Supply voltage input: 220 Va.c.

58. RS-485 ( + )

59. RS-485 ( - )

60. RS-485 ( GND )

46. Pulse output +

47. Pulse output -

48. Analog output +

49. Analog output -

Tel: +0086-023-86850812 Email:[email protected]

Fax:+0086-023-67636974

Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District, Chongqing

- 8 -

Chongqing Blue Jay Electronic Co.,Ltd Product Manual

Lower connection terminal

Three-phase network.- 4 wires

4 5 6 7 8 9 11 12 13 14

A-phase Current B-phase Current C-phase Current Ua Ub Uc Un

4. Current A-phase - S1 input

5. Current A-phase - S2 input

6. Current B-phase - S1 input

7. Current B-phase - S2 input

8. Current C-phase - S1 input

9. Current C-phase - S2 input

11. Voltage A-phase input

12. Voltage B-phase input

13. Voltage C-phase input

14. Neutral Voltage input

Three-phase network.- 3 wires

4 5 6 7 8 9 11 12 13 14

A-phase Current B-phase Current C-phase Current Ua Ub Uc Un

4. Current A-phase - S1 input

5. Current A-phase - S2 input

6. Current B-phase - S1 input

7. Current B-phase - S2 input

8. Current C-phase - S1 input

9. Current C-phase - S2 input

11. Voltage A-phase input

12. Voltage B-phase input

13. Voltage C-phase input

14. Neutral Voltage input

Tel: +0086-023-86850812 Email:[email protected]

Fax:+0086-023-67636974

Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District, Chongqing

- 9 -

Chongqing Blue Jay Electronic Co.,Ltd Product Manual

4.3. - Connection Drawing for the BJ194E-9S4

a. - Three-phase network.- 4 wires (low voltage) :

Tel: +0086-023-86850812 Email:[email protected]

Fax:+0086-023-67636974

Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District, Chongqing

- 10 -

Chongqing Blue Jay Electronic Co.,Ltd Product Manual

b. - Three-phase network.- 3 wires (low voltage) :

IMPORTANT REMARK!

If power = -0.01 is shown for any of the phases and voltage and current are not zero for this phase, check out following points:

-

Assure that A, B and C phases coincide in voltage and current.

-

Correct polarity? Reverse the current transformer placed at this phase.

Tel: +0086-023-86850812 Email:[email protected]

Fax:+0086-023-67636974

Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District, Chongqing

- 11 -

Chongqing Blue Jay Electronic Co.,Ltd Product Manual

5. SCREEN DISPLAY

5.1. - Panel diagram

5.2. - Display Summary

No. Display

1 Negative symbol

Explanation

Show the direction of the current measure data, red LED on mean "-", otherwise means"+"

2 Digital display module

3 Indicator of the data Unit

4

Indicator of the current display data

5* Enter key

6*

7*

Menu key

Up and Down key

Three lines 4 digital LED show power data, include voltage, current, power, power factor, frequency, etc.; And the contents of the programming menu

"K" means thousand; "M" means million

4 LED show the display module reading data

For menu selection and confirmation

Used to open the menu and return to previous menu

Set the programming value

Note: Please see detail instructions of “*” items at “OPERATION MODE”.

Tel: +0086-023-86850812 Email:[email protected]

Fax:+0086-023-67636974

Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District, Chongqing

- 12 -

Chongqing Blue Jay Electronic Co.,Ltd Product Manual

6. - OPERATION MODE

The instrument has three line displays. Each one has also a LED type indicator (red colour).

Every led will be on according to the parameter presently shown in screen.

When the 194E-9S4 is powered up, all the LED indicator will on, and meter start self- test, after some seconds, the meter is ready for operation and shows one of the available screens.

Parameters on display can be switch by pressing the key or . LED on the right indicates the parameters shown on screen at any moment.

When the first led (red) is on, it means that VOLTAGE values are shown on screen, that is, the user can read the voltage of the A-phase (Va), voltage of the B-phase (Vb) and voltage of the

C-phase (Vc).

Whether the key is press, the next led will be on, so indicating that for this screen

CURRENT values of each phase are now shown.

Pressing again the key , the next led will be on, and the screen will shown following parameters, and so successively.

At programming display mode, press and to increase or decrease the value, pressing the key and or and the instantaneous at the same time, value can increase or decrease number “x10”.

Pressing the "Manu" key can open the programming menu and return to previous menu.

Pressing the “Enter” key, you exit it with saving any modification that you might have done, in menu operation press “Enter” key ,user can go to the next menu.

Tel: +0086-023-86850812 Email:[email protected]

Fax:+0086-023-67636974

Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District, Chongqing

- 13 -

Chongqing Blue Jay Electronic Co.,Ltd Product Manual

7. - SETUP PROCEDURE

The SETUP procedure of the BJ194E-9S4 is performed by means of several SETUP options.

Once into the SETUP, use the keyboard to select different options and enter required variables:

1. Password enter;

2. Choice of default initial screen;

3. Input signal selection;

4. Communication preferences.

7.1. - Password enter

A 4-figure password is required to be entered (in case that this password is not correct, will not be set on the meter).

At normal display mode, press to enter the programming mode, meter display, then press ;

Meter display “ ”,

Ask for the password. Press and to increase or decrease the number, to switch password. After password switch press to confirm the input.

If password is correct, meter can enter next setting.

7.2. - System display settings

7.2.1. - Choice of default initial screen

This option allows choice among fixed or rotary screen:

After password, you will see the meter show “Set” like this:

Tel: +0086-023-86850812 Email:[email protected]

Fax:+0086-023-67636974

Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District, Chongqing

- 14 -

Chongqing Blue Jay Electronic Co.,Ltd Product Manual

Press to go to the level 2 menu, use and to choose item “DISP”,

You will see the meter show “Display” like this:

Press , then enter the level 3 menu, user can use and to choose number

0-6, meaning as the following:

0. Rotary screen display:

Meter can show data as this cycle: Current; Voltage; Active power, Reactive Power, Power factor; Frequency; Active Energy; Reactive Energy.

All 5 screens are successively shown at intervals of 5 s.

1-5 Fixed screen:

1. Three-phase current display:

Meter display always three-phase current data in 3 line LED display, shows each phase current data.

2. Three-phase voltage display

Meter display always three-phase voltage data in 3 line LED display, shows each phase voltage data.

3. Active/reactive power and power factor display:

On line 1 LED, meter shows total active power data;

On line 2 LED, meter shows total reactive power data;

On line 3 LED, meter shows total power factor.

4. Frequency display:

Meter display frequency data on line 1 LED.

5. Active energy display:

Meter display active energy on 2 line LED, show 8 digital data, 2 decimal.

6. Reactive energy display:

Meter display reactive energy on 2 line LED, show 8 digital data, 2 decimal.

Tel: +0086-023-86850812 Email:[email protected]

Fax:+0086-023-67636974

Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District, Chongqing

- 15 -

Chongqing Blue Jay Electronic Co.,Ltd Product Manual

7.2.2. - Clear energy counters

In “Set” menu, user can deleting energy counters.

Enter “Set” menu, in level 2 menu, use and to choose item “CLr.E”, meter show like this:

Press to confirm clear all the energy data, meter display:

And then press again, to save the operation and exit.

7.3. - Input signal selection

Press , return to level 1 menu.

In this section, user will set:.

1. Input net mode;

2. Voltage measure range select;

3. Current measure range select;

4. Voltage transformation ratio;

5. Current transformation ratio.

7.3.1.- Choice the input net mode

In level 1 menu, use and to choose item “INPT”, meter show like this:

Tel: +0086-023-86850812 Email:[email protected]

Fax:+0086-023-67636974

Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District, Chongqing

- 16 -

Chongqing Blue Jay Electronic Co.,Ltd Product Manual then press , enter the level 2 menu, choose “NET”, meter show: then press again, enter the level 3 menu.

Use and to select the right wiring mode, meter show like this:

Or

N.3.4: Three-phase four-wire, wiring reference section 4.3 a.

N.3.3: Three-phase three-wire, wiring reference section 4.3 b.

Note: Select the wiring mode must match actual wiring, or the reading data will go wrong.

7.3.2.- Choice voltage measure range

In level 1 menu of “INPT”.

Choose item “U.SCL”, meter show like this: then press , enter the level 3 menu, user can change the voltage range:

Or

400V: Maximum measured value is 400V

Tel: +0086-023-86850812 Email:[email protected]

Fax:+0086-023-67636974

Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District, Chongqing

- 17 -

Chongqing Blue Jay Electronic Co.,Ltd Product Manual

100V: Maximum measured value is 100V

Note: Select a different range will affect the accuracy of measurements, if the accuracy is 0.5.

Select 100V range, means the minimum scale value is 0.5V (100 x 0.5%);

Select 400V range, means the minimum scale value is 2V (400 x 0.5%).

7.3.3.- Current measure range select

In level 1 menu of “INPT”.

Choose “I.SCL”, meter show like this: then press , enter the level 3 menu, user can change the current range:

Or

5A: Maximum measured value is 5A.

1A: Maximum measured value is 1A.

Note: Select a different range will affect the accuracy of measurements, if the accuracy is 0.5.

Select 1A range, means the minimum scale value is 0.005A (1 x 0.5%);

Select 5A range, means the minimum scale value is 0.025A (5 x 0.5%).

7.3.4- Voltage transformation ratio

In level 1 menu of “INPT”.

Choose item “T.U” , meter show like this:

Tel: +0086-023-86850812 Email:[email protected]

Fax:+0086-023-67636974

Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District, Chongqing

- 18 -

Chongqing Blue Jay Electronic Co.,Ltd Product Manual then press , enter the level 3 menu, allowing us to set the current transformer.

To write or modify the value just repeatedly press or , pressing the key and or and the instantaneous at the same time, value can increase or decrease the number “x10”, Input value is 1~9999.

Note: The input values represent the voltage transformer (primary side voltage) / (secondary side voltage) .

Secondary side voltage is 100V or 400V; user set it at section

7.3.2

7.3.5. - Current transformation ratio

In level 1 menu of “INPT”.

Choose the item “T.I”, meter show like this: then press , enter the level 3 menu, allowing us to set the current transformer.

To write or modify the value just repeatedly press or , pressing the key and or and the instantaneous at the same time, value can increase or decrease the number “x10”, Input value is 1~9999.

Note: The input values represent the current transformer (primary side voltage) / (secondary side current) .

Secondary side current is 1A or 5A, user set it at section 7.3.3.

Tel: +0086-023-86850812 Email:[email protected]

Fax:+0086-023-67636974

Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District, Chongqing

- 19 -

Chongqing Blue Jay Electronic Co.,Ltd Product Manual

7.4. - Communication Preferences

Press , return to level 1 menu.

In this section, user will set:

1. Meter communication address;

2. Baud rate;

3. Communication format.

4. Data format

Note: Not all the meter have communication function, please make sure your purchase meter first, if no communication mode, you can skip this section.

7.4.1. - Meter communication address setting

One or some BJ194Umeter can be connected to a P.C. With this system we can get all the parameters in one central point of reading. The BJ194..., has a serial RS-485 or RS-232 type output (according to the model). If we connect more than one device to the same communication line (RS-485), we have to assign to each of them a different code or direction (from 1 to 247), since the P.C. needs the identification of every measuring point.

In level 1 menu, choose the item “CONN”, the meter show like this:

Then press , enter the level 2 menu, choose the item “SN”, meter show like this:

Then press to level 3 menu, to write or modify the value just repeatedly press

or ,pressing the key and or and the instantaneous at the same time, value can increase or decrease the number “x10”, Input value is 1~247.

Tel: +0086-023-86850812 Email:[email protected]

Fax:+0086-023-67636974

Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District, Chongqing

- 20 -

Chongqing Blue Jay Electronic Co.,Ltd Product Manual

7.4.2.- Communication Baud rate setting

In level 1 menu of “CONN”.

Choose item “BAUD”, meter show like this: then press , enter the level 3 menu, allowing us to set the Baud rate 4800 or 9600.

Or

7.4.3.- Choose communication format

In level 1 menu of “CONN”.

Choose item “Protocol”, meter show like this: then press , enter the level 3 menu, allowing us to set the Word communication or Byte communication. (Factory setting word communication)

Tel: +0086-023-86850812 Email:[email protected]

Fax:+0086-023-67636974

Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District, Chongqing

- 21 -

Chongqing Blue Jay Electronic Co.,Ltd Product Manual

7.5. – Menu Structure

level 1 Level 2

(Password) CODE

(System set)

SET

——

DISP

CLR.E

Level 3

Description

Password data

9999

Only when the correct password to enter programming)

0-6

(The default password is 0001)

Select the display mode, automatic or individual

—— Energy will clear after confirmed

(Signal input)

INPT

(Communication

Parameters)

CONN

(Net) NET N.3.4 and N.3.3

Select the input signal network measurement

(Voltage Range)

U.SCL

(Current Range)

I.SCL

(Voltage transformation ratio)

T.U

(Current transformation ratio)

T.I

400V and 100V

5A and 1A

1-9999

1-9999

Select the range of measured voltage signal

Select the range of measured current signal

Setting voltage signal

transformation

ratio = 1 / 2 scale

Setting current signal

transformation

ratio = 1 / 2 scale

(Address)

SN

1-247 Instrument address range 1-247

(Communication speed)

BAUD

Protocol PROT

4800~9600

Word or Byte communication

Baud Rate 4800、9600

Factory default communication mode for the word

Tel: +0086-023-86850812 Email:[email protected]

Fax:+0086-023-67636974

Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District, Chongqing

- 22 -

Chongqing Blue Jay Electronic Co.,Ltd Product Manual

7.6. - Display Character instructions

Tel: +0086-023-86850812 Email:[email protected]

Fax:+0086-023-67636974

Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District, Chongqing

- 23 -

Chongqing Blue Jay Electronic Co.,Ltd Product Manual

8. - SAFETY CONSIDERATIONS

All installation specification described at the previous chapters named:

INSTALLATION AND STARTUP, INSTALLATION MODES and

SPECIFICATIONS.

Note that with the instrument powered on, the terminals could be dangerous to touching and cover opening actions or elements removal may allow accessing dangerous parts. This instrument is factory-shipped at proper operation condition.

9. - MAINTENANCE

The 194E does not require any special maintenance. No adjustment, maintenance or repairing action should be done when the instrument open and powered on, should those actions are essential, high-qualified operators must perform them.

Before any adjustment, replacement, maintenance or repairing operation is carried out, the instrument must be disconnected from any power supply source.

When any protection failure is suspected to exist, the instrument must be immediately put out of service. The instrument’s design allows a quick replacement in case of any failure.

Tel: +0086-023-86850812 Email:[email protected]

Fax:+0086-023-67636974

Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District, Chongqing

- 24 -

Chongqing Blue Jay Electronic Co.,Ltd Product Manual

10. - TECHNICAL SERVICE

FAQ’s

1. The BJ-194E Multifunction Power Meter, once cabled and connected is seen to give a correct voltage and current reading, but shows negative values for active power (generation).

This is an error with the cabling for the current transformer secondary; the direction of the transformer current has to be respected as shown in the connection diagram. The current transformers have a two face primary; the current must pass from P1 to P2 giving the result in secondary (S1 and S2) of 5 amps.

The error stems from:

a). The current transformers have been incorrectly installed. As a result it gives the direction of the current as passing from P2 to P1; to resolve this problem, the current transformer does not have to be dismantled and installed again, but the transformer secondary (S1 and S2) just has to be inverted.

b). The connection of the current secondary in the current transformers have been incorrectly connected; to resolve this problem just connect the S1 transformer secondary to the S1 on the meter and the S2 on the current transformer to the S2 on the meter

2. The BJ-194E, once cabled and connected, is seen to give an incoherent Power factor and

CosΦ reading (-0.01 or similar).

This is again a current transformer and voltage phase connection error phase A, must correspond to the current transformer installed in phase A; phase B, must correspond to the current transformer installed in phase B; and phase C, must correspond to the current transformer installed in phase C.

This connection is clearly shown on the back of the analyzer.

3. The BJ-194E is measuring in average voltage and is displaying the secondary voltage (for example 110 volts).

Ensure that the voltage Transformer ratio has been correctly set (see section on 7.3.4).

Tel: +0086-023-86850812 Email:[email protected]

Fax:+0086-023-67636974

Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District, Chongqing

- 25 -

Chongqing Blue Jay Electronic Co.,Ltd Product Manual

4. The BJ-194E does not correctly display the current reading. It shows values varying between

0 to 5 amps of current.

Ensure that the Transformer ratio has been correctly set; once correctly set the current measurement shall be shown correctly (see section on 7.3.5).

For any inquiry about the instrument performance or whether any failure happens, contact to Blue Jay’s technical service.

Blue Jay - After-sales service

Redstone Road 2# 17-3

Jiangbei District , 400020 Chongqing

Tel - + 0086 023 67636974

Fax - + 0086 023 67636974

E-mail: [email protected]

Tel: +0086-023-86850812 Email:[email protected]

Fax:+0086-023-67636974

Add: Building 13, 2-8, Jialing third village Pioneer Park, Jiangbei District, Chongqing

- 26 -

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement