CENTURION SYSTEMS VANTAGE 500 Mechanical Installation Manual

Add to My manuals
44 Pages

advertisement

CENTURION SYSTEMS VANTAGE 500 Mechanical Installation Manual | Manualzz

VANTAGE

Mechanical Installation Manual

Centurion Systems (Pty) Ltd www.CentSys.com

page 1 www.CentSys.com

Company Profile

1986

In-house

R&D development team

1990 1995 1999 Today

Manufacture to international quality standard

ISO 9001:2008

100% testing of products

After-sales multi-language

Technical Support from 07h00 to 18h00

UTC+2

Monday to Friday

Sales and technical support to Africa, Europe, Asia, the Americas, Australia and the Pacific

Centurion Systems (Pty) Ltd reserves the right to make changes to the products described in this manual without notice and without obligation of Centurion Systems (Pty) Ltd to notify any persons of any such revisions or changes. Additionally, Centurion Systems (Pty) Ltd makes no representations or warranties with respect to this manual. No part of this document may be copied, stored in a retrieval system or transmitted in any form or by any means electronic, mechanical, optical or photographic, without the express prior written consent of Centurion Systems (Pty) Ltd.

Contents

IMPORTANT SAFETY INSTRUCTIONS

1.

2.

General Description

Icons Used in this Manual

3. Specifications

3.1. Physical Dimensions

3.2. Technical Specifications

3.3. V-Series Controller

3.4. Lightning Protection

3.6. Allowable Gate Mass

3.7. Allowable Wind Load

4. Product Identification

4.1. V-Series Wall Box

5.

6.

Required Tools and Equipment

Preparation of Site

6.1

General Considerations for the Installation

6.2. Determine Gate Opening Angle

6.3. Key Terms Used in this Section

6.4. Side Wall Limitation - Inward Opening

6.5. Pillar Hinge Depth Limitation - Inward Opening

6.6. Wall Bracket Mounting Methods

6.7. Strength of the Gate and Gate Bracket

7. Cabling Requirements

8.

9.

Critical Installation Checklist

Operator Installation - Inward Opening Gate(s)

10. Operator Installation - Outward Opening Gate(s) page 5 page 8 page 9 page 10 page 10 page 11 page 12 page 12 page 12 page 13 page 14 page 15 page 16 page 17 page 18 page 18 page 19 page 20 page 20 page 21 page 22 page 24 page 25 page 26 page 27 page 36 www.CentSys.com

FAST TRACK Mechanical Setup

These quick steps are for the experienced installer who needs a checklist to get a standard installation up and running in the minimum of time.

Detailed installation features and functions are referred to later in this manual.

STEP

1 Gather Required Tools and Equipment

STEP

2

STEP

3

Heed Necessary Site Considerations

Check Cabling Requirements

STEP

4 Determine Gate Swing Angle

STEP

5

STEP

6

STEP

7

STEP

8

STEP

9

Determine Installation Type

• Inward Opening Installation

• Outward Opening Installation

Confirm that gate leaf meets allowable wind loading specifications

Mount the Gate and Wall Bracket(s)

Install Operator and Link to Gate

Mount Controller Enclosure page 4 www.CentSys.com

IMPORTANT

SAFETY INSTRUCTIONS

ATTENTION

To ensure the safety of people and possessions, it is important that you read all the following instructions.

Incorrect installation or incorrect use of the product could cause serious harm to people.

The installer, being either professional or DIY, is the last person on the site who can ensure that the operator is safely installed, and that the whole system can be operated safely.

Warnings for the Installer

CAREFULLY READ AND FOLLOW ALL INSTRUCTIONS before beginning to install the product.

• All installation, repair, and service work to this product must be carried out by a suitably qualified person

• This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety

• Do not activate your gate unless you can see it and can determine that its area of travel is clear of people, pets, or other obstructions

• NO ONE MAY CROSS THE PATH OF A MOVING GATE; always keep people and objects away from the gate and its area of travel

• NEVER LET CHILDREN OPERATE OR PLAY WITH THE GATE CONTROLS

• Secure all easily-accessed gate opener controls in order to prevent unauthorised use of the gate

• Do not in any way modify the components of the automated system

• Do not install the equipment in an explosive atmosphere: the presence of flammable gasses or fumes is a serious danger to safety

• Before attempting any work on the system, cut electrical power to the operator and disconnect the batteries

• The Mains power supply of the automated system must be fitted with an all-pole switch with contact opening distance of 3mm or greater; use of a 5A hydraulic breaker with all-pole circuit break is recommended

• Make sure that an earth leakage circuit breaker with a threshold of 30mA is fitted upstream of the system www.CentSys.com

page 5

• Never short-circuit the battery and do not try to recharge the batteries with power supply units other than that supplied with the product, or manufactured by

Centurion Systems (Pty) Ltd

• Make sure that the earthing system is correctly constructed, and that all metal parts of the system are suitably earthed

• Safety devices must be fitted to the installation to guard against mechanical movement risks such as crushing, dragging and shearing

• It is recommended that at least one warning indicator light be fitted to every system

• Always fit the warning signs visibly to the inside and outside of the gate

• The installer must explain and demonstrate the manual operation of the gate in case of an emergency, and must hand the User Guide/Warnings over to the user

• The installer must explain these safety instructions to all persons authorised to use this gate, and be sure that they understand the hazards associated with automated gates

• Do not leave packing materials (plastic, polystyrene, etc.) within reach of children as such materials are potential sources of danger

• Dispose of all waste products like packing materials, worn-out batteries etc, according to local regulations

• Always check the obstruction detection system, and safety devices for correct operation

• Neither Centurion Systems (Pty) Ltd, nor its subsidiaries, accept any liability caused by improper use of the product, or for use other than that for which the automated system was intended

• This product was designed and built strictly for the use indicated in this documentation; any other use, not expressly indicated here, could compromise the service life/operation of the product and/or be a source of danger

• Everything not expressly specified in these instructions is not permitted

Never run the operator directly from the battery!

Doing so will cause damage to the operator.

Only run the operator from the V-Series Controller.

page 6 www.CentSys.com

This section has been left blank intentionally.

www.CentSys.com

page 7

1. General Description

The VANTAGE linear swing gate motor, available in two models with actuation strokes of

400mm and 500mm, respectively, has been designed to automate a wide variety of swing gates, from single light-domestic gates to heavy industrial double swing gates.

The fail-safe and fully-redundant Position and Collision Detection System has been designed and tested to set the standard in safety of operation and to provide an unparalleled level of reliability and durability in operation.

The gate Travel Limits are managed by a sealed double-redundant opto-electronic system that has been designed not only to ensure ultra-reliable operation, but also to ensure precise position and trajectory control. This enables very accurate and reliable collision detection to ensure safe operation even under trying conditions.

This guide covers the mechanical installation of your new VANTAGE swing gate operator.

VANTAGE swing gate operators can be installed on both inward- and outward opening swing gates. Please see the relevant sections for each type of installation, paying attention to any site preparation that needs to be made before the operators are installed.

page 8 www.CentSys.com

2. Icons Used in this Manual

This icon indicates tips and other information that could be useful during the installation.

This icon denotes variations and other aspects that should be considered during installation.

This icon indicates warning, caution or attention! Please take special note of critical aspects that MUST be adhered to in order to prevent injury. www.CentSys.com

page 9

3. Specifications

3.1. Physical Dimensions

1370mm extended

970mm retracted

Ø100mm

400mm extended piston stroke

FIGURE 1. VANTAGE 400 OVERALL DIMENSIONS

1570mm extended

1070mm retracted

Ø100mm

500mm extended piston stroke

FIGURE 2. VANTAGE 500 OVERALL DIMENSIONS page 10 www.CentSys.com

3.2. Technical Specifications - VANTAGE Operator

Input voltage

Motor voltage

Motor power supply

Battery charger 2

Current consumption (Mains)

Current consumption (motor at rated load)

Operator push force - maximum

Operator stroke

Piston extension/retraction speed

Typical gate opening time 3

Manual override

Maximum number of operations per day

Duty cycle - Mains present 5 6

Operations in standby with 7Ah battery 7

Half day

Full day

Collision Sensing

Operating temperature range

Mass of unit packed (excluding battery)

Single kit 8

Double kit 9

1. Can increase battery capacity for longer standby times

2. Can operate off a solar supply, consult your reseller for assistance

3. Assumes a full stroke of operator is used

4. Each operator comes with a unique set of keys

5. Based on 25°C ambient temperature and unit not in direct sunlight

6. Based on an operator push force of less than 50% of rated

7. Based on double kit excluding Infrared Safety Beams

8. Single kit contains one operator and Wall Box

9. Double kit contains two operators and one Wall Box

VANTAGE 400 VANTAGE 500

90V - 240V AC ± 10%, 50/60Hz

12V DC

Battery-driven (standard capacity - 7Ah) 1

1.8A @ 13.8V

170mA

15A - maximum

250kgf

400mm 500mm

28mm/sec (variable)

14.3 sec 17.8 sec

Key release 4

250

50%

8.5kg

14kg

70

58

Electronic

-15°C to +50°C

9kg

15kg

TABLE 1 www.CentSys.com

page 11

3.3. V-Series Controller

Maximum motor current per channel

Maximum input voltage

Standby current draw

Maximum solenoid current draw

Maximum auxillary output current

Collision detection

Position and trajectory control

Temperature range

Onboard receiver type

Receiver code storage capacity

Receiver frequency

3.4. Lightning Protection

15A (fused)

14.4V DC

48mA

2A DC

3A (Resettable Electronic Fuse)

Current sense and redundant-optical

Redundant optical

-20°C to +60°C

Code-hopping multichannel

64 transmitter buttons

433MHZ

TABLE 2

The V-Series Controller utilises the same proven surge protection philosophy that is used in all our products. While this does not guarantee that the unit will not be damaged in the event of a lightning strike or power surge, it greatly reduces the likelihood of such damage occurring. The earth return for the surge protection is provided via the mains power supply earth. In order to ensure that the surge protection is effective, it is essential that the unit is properly earthed.

3.5. Power Supply

Nominal input voltage

AC current draw (maximum)

Temperature range

Battery charger output current

(dependant on PSU input voltage)

90V - 240V AC ±10% @ 50/60Hz

170mA

-20°C to +60°C

90V AC input: 1.2A @ 13.8V

240V AC input: 1.8A @ 13.8V

TABLE 3 page 12 www.CentSys.com

3.6. Allowable Gate Mass

Ensure that the gate leaf meets Wind Load Specifications

Maximum allowable gate mass for the VANTAGE 400 operator

Gate swing angle

90°

100°

110°

120°

Up to

1.5m

500kg

500kg

500kg

180kg

Up to

2m

500kg

500kg

306kg

100kg

Up to

2.5m

500kg

388kg

198kg

65kg

1. An electric lock must be fitted to secure gate in closed position

Up to

3m 1

360kg

160kg

130kg

Up to

3.5m

260kg

190kg

1

Up to

4m 1

200kg

150kg

Not recommended

TABLE 4

Maximum allowable gate mass for the VANTAGE 500 operator

Gate swing angle

90°

100°

110°

120°

Up to

1.5m

750kg

750kg

750kg

310kg

Up to

2m

750kg

750kg

500kg

170kg

Up to

2.5m

750kg

600kg

320kg

110kg

Up to

3m 1

550kg

420kg

220kg

1. An electric lock must be fitted to secure gate in closed position

Up to

3.5m

1

410kg

310kg

Up to

4m 1

310kg

230kg

Not recommended

TABLE 5 www.CentSys.com

page 13

3.7. Allowable Wind Load

Wind speeds for which operator will still operate the gate.

( VANTAGE 400 or VANTAGE 500 operators)

For a 25% covered gate: (Palisades, etc.) x 1.8 metre high

Value of

A or B dimension once installed 1

100mm

140mm

180mm

220mm

260mm

300mm

340mm

Up to

1.5m

94km/h

119km/h

66km/h

85km/h

48km/h

65km/h

44km/h

57km/h

138km/h 101km/h 78km/h

156km/h 114km/h 89km/h

67km/h

76km/h

171km/h 126km/h 99km/h 84km/h

186km/h 137km/h 108km/h 91km/h

199km/h 147km/h 116km/h 98km/h

1. See Section 9/10 for installation details

2. An electric lock must be fitted

Individual gate leaf lengths:

Up to

2m

Up to

2.5m

Up to

3m 2

Up to

3.5m

2

41km/h

51km/h

60km/h

67km/h

74km/h

80km/h

86km/h

Up to

4m 2

37km/h

46km/h

53km/h

60km/h

65km/h

71km/h

76km/h

TABLE 6

Wind speeds for which operator will still operate the gate.

( VANTAGE 400 or VANTAGE 500 operators)

For a 100% covered gate: (Fully-clad gates, etc.) x 1.8 metre high

Value of

A or B dimension once installed 1

100mm

140mm

180mm

220mm

260mm

300mm

340mm

Up to

1.5m

47km/h

59km/h

69km/h

78km/h

86km/h

93km/h

100km/h

1. See Section 9/10 for installation details

2. An electric lock must be fitted

Individual gate leaf lengths:

Up to

2m

33km/h

43km/h

50km/h

57km/h

63km/h

63km/h

74km/h

Up to

2.5m

24km/h

32km/h

39km/h

44km/h

49km/h

54km/h

58km/h

Up to

3m 2

22km/h

28km/h

34km/h

38km/h

42km/h

46km/h

49km/h

Up to

3.5m

2

Up to

4m 2

47km/h

59km/h

69km/h

78km/h

86km/h

93km/h

19km/h

23km/h

27km/h

30km/h

33km/h

35km/h

100km/h 38km/h

TABLE 7 page 14 www.CentSys.com

4. Product Identification

1

2

7

3

4

5

6

FIGURE 3. KIT IDENTIFICATION

1. Gate Bracket pin

2. 14mm snap ring

3. VANTAGE gate operator

(complete assembly)

4. Wall Bracket

5. Wall Bracket mounting plate

6. Mechanical Installation Manual

7. Gate operator keys 1

8. Stainless steel cap screw M5 x 25

9. Origin clamp

10. M5 barrel nut

11. Gate Bracket

12. Gate Warning Decal

1. Keys are specific to each operator - key number must be recorded

1

2

8

9

10

11

12 www.CentSys.com

page 15

4.1. V-Series Wall Box

1

2

5

3

6

4

FIGURE 4. V-SERIES WALL BOx INCLUDING CHARGER AND CONTROLLER

1. 12V 7.2Ah Battery 1 receiver

3. V-Series

2. V-Series Controller with built-in

User Guide

4. V-Series Electrical Setup &

Commissioning Guide

5. Charger

6. Code-hopping remote controls

1. Batteries can be of a larger capacity for longer power failure autonomy and are not included in the kit;

Consult your local authorised dealer for assistance page 16 www.CentSys.com

5. Required Tools & Equipment

Spanners

17mm/15mm preferably socket set

Hammer

Crimping tool and Pin lugs

Connector block

Electric drilling machine

Hole saw

20mm

Screwdrivers

6mm Phillips

3.5mm Flat

Pliers

G-clamps x2

Allen key

5mm wall mount bracket

Ø6.5mm steel drill bit for gate bracket

Hacksaw

Spirit level

Angle grinder

Pin punch

6mm

Measuring tape

Welding machine and safety equipment

Marking pen/chalk

Soldering iron

Extension cord www.CentSys.com

page 17

Safety equipment

(goggles, gloves etc.)

FIGURE 5

6. Preparation of Site

6.1. General Consideration for the Installation

Always recommend the fitment of additional safety equipment such as safety edges and Safety Beams (i5 or Photon), for additional protection against entrapment or other mechanical risks.

Check that no pipes or electrical cables are in the way of the intended installation.

Check that enough space is available for the gate operator with the gate in the required open position (see Figure 6).

If the swing gate leaf is longer than 3 metres, ensure that an electric lock can be fitted.

For security reasons, never fit an operator on the outside of the gate, where the public has access to it (refer to the instructions for an Outward-opening swing gate).

Never run an operator directly off the 12V battery.

Install the gate operator only if:

• It will not pose a hazard to the public

• There is sufficient clearance to a roadway and/or public thoroughfares

• The installation will meet all municipal and/or local authority requirements once completed

• The gate mass, leaf width, wind loading and application is within the operator specifications

• The gate is in good working order, meaning:

• that it swings freely;

• does not move on its own if left in any position;

• each gate leaf is strong and rigid;

• Once installed, there is sufficient clearance between moving parts during operation of the gate to reduce the risk of personal injury and/or entrapment

• It is recommended that Pushbuttons and Keyswitches, if fitted, be positioned in such a way that the gate is in line of sight of the user page 18 www.CentSys.com

6.2. Determine Gate Opening Angle

Use this procedure to accurately determine the gate opening angle:

6.2.1. Step 1

Close the gate and measure a distance of one metre from the centreline of the gate hinge.

Make a mark on the ground.

Wall Mark the ground

1 metre

Gate in closed position

Gate hinge point 6.2.2. Step 2

Open the gate and measure along the gate a distance of one metre from the centreline of the gate hinge.

Make a mark on the ground.

Measure the distance on the ground between the two marks (Z).

Using this Z-Value, read off the gate opening angle from the Table below.

6.2.3. Step 3

Gate opening angle based on Z-Value

Distance Z

Mark the ground

Gate in open position

FIGURE 6

From

1414mm

1532mm

To

1521mm

1638mm

Use gate swing angle of

90° - 99°

100° - 110°

TABLE 8 www.CentSys.com

page 19

6.3. Key Terms Used in this Section

6.3.1. Pillar maximum

The maximum allowable distance measured from the centre of the gate hinge to the edge of the pillar.

6.3.2. Wall minimum

This value denotes the minimum amount of space needed to install the operator and is measured from the side wall to the gate when the gate is in the open position.

6.4. Side Wall Limitation - Inward Opening

Figure 7 shows the side wall limitations for an Inward opening gate . The operator must be installed in accordance with these limitations. If the wall minimum cannot be achieved, consider using an outward swing configuration.

Gate hinge point

Wall Gate in closed position

Wall minimum must be greater than 200mm

Gate swing angle

Gate in open position

Side wall

FIGURE 7. SIDE WALL LIMITATION FOR INWARD OPENING GATE page 20 www.CentSys.com

6.5. Pillar Hinge Depth Limitation - Inward Opening

Figure 8 shows the pillar hinge depth limitation for an Inward opening gate .

An operator must be installed in accordance with these limitations to ensure that it does not interfere with the operation of the gate during movement. The hinge depth of the gate on the pillar, needs to be checked against the pillar maximum values in Table 9 to determine if the installation is possible. If the hinge depth of the gate is excessive, the gate may have to be relocated on the pillar to achieve the required pillar maximum values.

Gate hinge point

Wall

Gate in closed position

Pillar maximum

Gate swing angle

Gate in open position

FIGURE 8. PILLAR HINGE DEPTH LIMITATION FOR INWARD OPENING GATE

Operator

VANTAGE 400

VANTAGE 400

VANTAGE 400

VANTAGE 500

VANTAGE 500

VANTAGE 500

Pillar Maximum

175mm

155mm

145mm

245mm

235mm

230mm

Swing Gate Angle

90°

100°

110°

90°

100°

110°

TABLE 9 www.CentSys.com

page 21

6.6. Wall Bracket Mounting Methods

The following recommended methods may be used to install the operator.

6.6.1. Through-wall

Applications:

• Pre-fabricated walling

• For heavy gates operating frequently

Pillar

Wall Bracket

Through-wall bolt

Pillar

6.6.2. Chemical anchors

Applications:

• Masonry pillars

• Frequent use

Wall Bracket

Chemical anchor

FIGURE 9

FIGURE 10

Steel pillar

6.6.3. Welding

Application:

• Steel pillars

Wall Bracket

Welding machine page 22

FIGURE 11 www.CentSys.com

6.6.4. Sleeve anchors

Applications:

• Lighter gates

• Domestic

6.6.5. Rawl bolts

Applications:

Lighter gates

Domestic

Pillar

Wall Bracket

Sleeve anchor

Pillar

Wall Bracket

Rawl bolt

FIGURE 12

FIGURE 13 www.CentSys.com

page 23

6.7. Strength of the Gate and Gate Bracket

Gate

6.7.1. Welding

Applications:

• Domestic

• Medium gates

• Frequent use

Gate

Bracket

Welding machine

6.7.2. Through-bolts

(high-tensile)

Applications:

• Domestic

• Light gates

• Infrequent use

TEK screws and mild steel bolts are not recommended.

Gate

Gate Bracket

FIGURE 14

Through-bolts

FIGURE 15 page 24 www.CentSys.com

7. Cabling Requirements

Control box box

350mm cable loop

FIGURE 16. CABLING REQUIREMENTS

Legend

1. 90V - 240V AC Mains cable via Mains isolator 1 or low-voltage 16V AC battery charger supply 3

switch (3 core LNE 0,5mm 2 ) 2

(2 core 1,5mm²).

2. Intercom cable (n1 + 6 core) to house.

,

3. Master Motor (MTR M) or Slave Motor (MTR S) cable.

(Minimum, 2 core 1.5mm

2 + 4 core 0,22mm 2 multi-stranded) 4 .

4. Optional radio receiver cable (3 core 0,5mm 2 multi-stranded, optional) 5 .

5. Optional Pedestrian Keyswitch (2 core 0,5mm 2 multi-stranded) or optional keypad

(3 core 0,5mm 2 multi-stranded).

6. Optional, but recommended infrared Safety Beams (3 core 0,5mm 2 or 4 core 0.5mm

2 for CE compliance).

multi-stranded

7. Optional intercom cable (n2+2 core 0,5mm 2 multi-stranded) to gate station.

8. Optional electric lock (2 core 0.5mm

2 ).

9. Optional Pillar Light cable (3 core, size according to power regulations).

10. Optional ground loop for free-exit (1 core 0.5mm

2 multi-stranded - silicone-coated) 6 .

1.

Mains isolator supplied with V-Series wall box

2. Increase cable thickness if Pillar Lights are to be installed

3. Screened cable is always recommended to provide better protection against lightning - earth one end of screening

4. Please use V-Series cabling. Order reference: CABLEVEC68

5. For optimum range an external receiver can be mounted on the wall

6. Consult manufacturer of loop detector for specific details

• All cables must be routed in conduit unless underground cable is being used

• Mains isolator must be less than one metre from the operator

• Safety Beams are always recommended, i5 or Photon www.CentSys.com

page 25

8. Critical Installation Checklist

The following is a list of critical requirements that must be adhered to in order to ensure reliable operation of your VANTAGE operator(s):

• Ensure that the Wall Bracket is securely anchored

• Make sure that the operator’s maximum stroke is being utilised

• Only use V-Series cable for the installation

• Leave a 350mm long loop in the cable

• Fit an electric gate lock if the leaf width is greater than 3 metres

• Ensure that the opening and closing angles conform to the installation guidelines

• Ensure that your gate and operator(s) are equipped to deal with Wind Loading

(refer to the Table 6 and 7 on page 14)

Never run the operator directly from the battery! Doing so will cause damage to the operator. Only run the operator from the V-Series

Controller.

page 26 www.CentSys.com

Figure 17 illustrates the values corresponding to the Inward Opening Gate Installation

Tables.

Wall

A

Gate in closed position

E

B

VANTAGE operator

The length of the wall bracket should equal B minus E . When looking at the example above, the wall bracket should measure

240mm (B) - 160mm (E) = 80mm (wall bracket length)

FIGURE 17. BRACKET POSITION - INWARD OPENING GATE

Ensure that the gate mass does not exceed the specifications on page 14.

9.1. Key terms used in this section

9.1.1. E-Value

The distance from the centre of the gate hinge to the edge of the pillar.

9.1.2. A-Value

The horizontal distance from the Wall Bracket/pivot pin to the center of the gate hinge.

9.1.3. B-Value

The vertical distance from the Wall Bracket/pivot pin to the center of the gate hinge.

9.2. Step 1

Measure the E-Value and ensure that it does not exceed values shown in Figure 8 and

Table 10 on page 21.

Depending on the gate opening angle determined in Section 6.2 and the E-Value measured, determine the installation distances for the A- and B-Value using the Tables shown on pages 29 to 31.

www.CentSys.com

page 27

Example: 90° Inward Opening gate (VANTAGE 400):

Assume that the E-Value has been measured as 160mm. By looking at this

Table at E-Values that are smaller than (<) 165mm, the relevant A- and

B-Values are: A=145mm and B=240mm.

E-Value

Depth of gate hinge to pillar

<165mm

<175mm

A-Value

145mm

130mm

B-Value

240mm

250mm page 28 www.CentSys.com

VANTAGE 400 Inward Opening Gate Geometry Tables:

90° Inward Opening Gate

E-Value

Depth of gate hinge to pillar

<145mm 1

<155mm

<165mm

<175mm

1.

Optimum Installation

100° Inward Opening Gate

E-Value

Depth of gate hinge to pillar

<125mm 1

<135mm

<145mm

<155mm

1.

Optimum Installation

110° Inward Opening Gate

E-Value

Depth of gate hinge to pillar

<115mm 1

<125mm

<135mm

<145mm

1.

Optimum Installation

A-Value

170mm 1

160mm

145mm

130mm

A-Value

165mm 1

155mm

145mm

135mm

A-Value

155mm 1

145mm

140mm

130mm

B-Value

220mm 1

230mm

240mm

250mm

TABLE 10

B-Value

200mm 1

210mm

220mm

230mm

TABLE 11

B-Value

190mm 1

200mm

210mm

220mm

TABLE 12 www.CentSys.com

page 29

VANTAGE 500 Inward Opening Gate Geometry Tables:

90° Inward Opening Gate

E -Value

Depth of gate hinge to pillar

<190mm 1

<205mm

<215mm

<225mm

<235mm

<245mm

1.

Optimum Installation

A-Value

205mm 1

195mm

180mm

170mm

155mm

140mm

B-Value

280mm 1

290mm

300mm

310mm

320mm

330mm

TABLE 13

100° Inward Opening Gate

E-Value

Depth of gate hinge to pillar

<175mm 1

<185mm

<195mm

<205mm

<215mm

<225mm

<235mm

1.

Optimum Installation

A-Value

195mm 1

185mm

175mm

165mm

155mm

145mm

135mm

B-Value

260mm 1

270mm

280mm

290mm

300mm

310mm

320mm

TABLE 14 page 30 www.CentSys.com

VANTAGE 500 Inward Opening Gate Geometry Table:

110° Inward Opening Gate

E-Value

Depth of gate hinge to pillar

<150mm 1

<160mm

<170mm

<180mm

<190mm

<205mm

<210mm

<220mm

<230mm

1.

Optimum Installation

A-Value

190mm 1

185mm

175mm

170mm

160mm

150mm

145mm

135mm

125mm

B-Value

240mm 1

250mm

260mm

270mm

280mm

290mm

300mm

310mm

320mm

TABLE 15 www.CentSys.com

page 31

9.2. Step 2

Determine a suitable height for the

Wall Bracket.

Ensure that this mounting height will allow the Gate

Bracket to be securely mounted to the Gate Leaf.

Take care to make sure the operator is mounted level.

Gate

Gate Bracket position

FIGURE 18. WALL BRACKET HEIGHT

Cut off excess length

Mark length on bracket

Weld plates together

9.3. Step 3

Mark the determined length on the

Wall Bracket.

Cut off excess length.

Insert the Wall Bracket into the mounting plate.

Weld the brackets together.

Wall Bracket length

FIGURE 19. CUT AND WELD WALL BRACKET

9.4. Step 4

Mount the Wall Bracket according to the A- and B-Values obtained in

Step 1 on page 27.

It is critical that the

Wall Bracket is securely mounted.

See page 18 for Site

Considerations.

Wall

Mounting bolt

Wall

Bracket page 32

FIGURE 20 www.CentSys.com

Gate

Bracket

Pin

9.5. Step 5

Fit the Gate Bracket to the

VANTAGE .

Origin clamp

Wall

VANTAGE operator

FIGURE 21

9.6. Step 6

Fit the motor end of the operator to the Wall Bracket.

Support the operator to prevent damage

Wall

Bracket

Pin

VANTAGE operator

FIGURE 22

9.7. Step 7

Manually rotate the piston to the fully extended position, and then retract it by half to one full turn.

With the gate in the closed position, use a G-clamp or spot weld the Gate

Bracket in position to temporarily hold the Gate Bracket in place.

The G-clamp should only be used to secure the Gate

Bracket in place, and should never be used as a means of securing the operator piston arm as this could result in damage.

Wall

Wall

Bracket

VANTAGE operator

G-clamp or spot weld

Gate Bracket www.CentSys.com

page 33

Gate in closed position

G-clamp

FIGURE 23

Gate in closed position

9.8. Step 8

Manually release the operator using the key provided with the kit, and swing the gate to the desired open position.

Slide the origin clamp along the piston tube, right up to the end to the operator.

Secure origin clamp in place, and tighten properly with an Allen Key.

Wall

VANTAGE operator

G-clamp

Set the origin clamp to the open limit

Gate in open position

G-clamp

FIGURE 24

9.9. Step 9

If the gate opening angle is sufficient and the operator is utilising the majority of its stroke, then secure the Gate Bracket using the most appropriate means.

Remove the operator before welding, if welding is required.

If this is not the case or the operator does not have enough stroke for the gate to open fully, re-check the A- and B-Values from Table 10 on page 29 to Table 15 on page 31.

Bolt

Gate Bracket

Nuts

OR

Gate Bracket

Gate

Welding machine page 34

FIGURE 25 www.CentSys.com

Attach warning labels to the inside and outside of the gate as shown.

The Mechanical part of the installation is now complete.

FIGURE 26 www.CentSys.com

page 35

10. Operator Installation - Outward Opening

Gates

10.1. Step 1

Depending on the gate opening angle determined in Section 6.2 refer to Figures 27 to 28 for the correct installation geometry.

In most cases it will be necessary to make up a suitable extension bracket on which to mount the operator’s Wall Bracket.

Ensure that the gate mass does not exceed the specifications on page 13.

VANTAGE 400 Outward Opening Gate:

Gate in open position

Gate opening angle

B

Make up bracket to suit

Gate in closed position

VANTAGE operator

A

FIGURE 27. VANTAGE 400 OUTWARD OPENING GATE

VANTAGE 400 Outward Opening Geometry Tables:

Gate Opening Angle

90°

100°

110°

A

220mm

200mm

190mm page 36

B

170mm

165mm

155mm

TABLE 16 www.CentSys.com

VANTAGE 500 Outward Opening Gate:

Gate in open position

Gate opening angle

B

Make up bracket to suit

Gate in closed position

VANTAGE operator

A

FIGURE 28. VANTAGE 500 OUTWARD OPENING GATE

VANTAGE 500 Outward Opening Geometry Tables:

Gate Opening Angle

90°

100°

110°

A

280mm

260mm

240mm

B

205mm

195mm

190mm

TABLE 17 page 37 www.CentSys.com

10.2. Step 2

Determine a suitable height for the

Wall Bracket.

Ensure that this mounting height will allow the Gate

Bracket to be securely mounted to the Gate Leaf.

Take care to make sure the operator is mounted level.

10.3. Step 3

Mark the determined length on the

Wall Bracket.

Cut off the excess length.

Insert the Wall Bracket into the mounting plate.

Weld the brackets together.

Gate

Gate Bracket Position

FIGURE 29. BRACKET HEIGHT

Mark length on bracket

Cut off excess length

Weld plates together

Wall Bracket length

FIGURE 30. CUT AND WELD WALL BRACKET

10.4. Step 4

Mount the Wall Bracket according to the A- and B-Values obtained in

Step 1 on page 36.

It is critical that the Wall Bracket is securely mounted and is adequately rigid.

See page 18 for site considerations.

Wall

Sturdy

Custom bracket

Mounting bolt page 38

Wall

Bracket

FIGURE 31 www.CentSys.com

10.5. Step 5

Fit the Gate Bracket to the

VANTAGE .

Origin clamp

10.6. Step 6

Fit the motor end of the operator to the Wall Bracket.

Support the operator to prevent damage

10.7. Step 7

Manually rotate the piston to the fully retracted position, and then extend it by half to one full turn.

With the gate in the closed position, use a G-clamp or spot weld the Gate

Bracket in position to temporarily hold the Gate Bracket in place.

The G-clamp should only be used to secure the Gate

Bracket in place, and should never be used as a means of securing the operator piston arm as this could result in damage.

www.CentSys.com

Wall

Bracket

Gate in closed position

Set the origin clamp to closed limit

G-clamp or spot weld page 39

FIGURE 34

Pin

VANTAGE operator

FIGURE 32

Wall

Pin

VANTAGE operator

Wall

Bracket

FIGURE 33

VANTAGE operator

G-clamp or spot weld

10.8. Step 8

Manually release the operator using the key provided with the kit, and swing the gate to the desired open position.

Gate in position

FIGURE 35

10.9. Step 9

If the gate opening angle is sufficient and the operator is utilising the majority of its stroke, then secure the Gate Bracket using the most appropriate means.

Remove the operator before welding, if welding is required.

If this is not the case or the operator does not have enough stroke for the gate to open fully, re-check the A- and B-Values from Table 16 on page 36 to Table 17 on Page 37.

Bolt

Gate Bracket

Nuts

OR

Gate Bracket

Gate

Welding machine

FIGURE 36 page 40 www.CentSys.com

Attach warning labels to the inside and outside of the gate as shown.

The Mechanical part of the installation is now complete.

FIGURE 37 www.CentSys.com

page 41

Notes

page 42 www.CentSys.com

Notes

www.CentSys.com

page 43

Connect with us on: facebook.com/CenturionSystems

YouTube.com/CenturionSystems

Twitter@askCenturion

Subscribe to the newsletter: www.CentSys.com/Subscribe

Call Centurion Systems (Pty) Ltd .

South Africa

Head Office: +27 11 699 2400

Call Technical Support: +27 11 699 2481 from 07h00 to 18h00 (UTC+2)

DOC12381V100 - VANTAGE INSTALLATION

MANUAL V1 GENERIC-23032015 www.CentSys.com

page 44

advertisement

Related manuals

advertisement