EA530 Series Compact Limit Switches-
Product Instructions
Publication #
EAIS02
IMPORTANT
Instructions for proper applications and uses of
COMPACT LIMIT SWITCHES
EXPERIENCE HAS SHOWN THAT THE MECHANICAL
AND ELECTRICAL OPERATING LIFE OF A LIMIT
SWITCH IS INFLUENCED TO A LARGE DEGREE BY
PROPER INSTALLATION AND APPLICATION
PROCEDURES. THIS PUBLICATION IS INTENDED TO
BE USED AS A GUIDE.
WARNING:
A SWITCH IN A PROTECTIVE INTERLOCKING CIRCUIT SHOULD BE
USED WITH AT LEAST ONE OTHER DEVICE THAT WILL PROVIDE A
REDUNDANT PROTECTIVE FUNCTION, AND THE CIRCUIT SHOULD
BE SO ARRANGED THAT EITHER DEVICE WILL INTERRUPT THE
INTENDED OPERATION OF THE CONTROLLED EQUIPMENT.
(PROPOSED NEMA ICS 2-225.95 St'd.)
Wiring and Mounting:
• Unless specifically designed for such service limit switches
SHOULD NOT BE submerged in or splashed with oils, coolant or other liquids . CONSULT FACTORY.
• Limit switches MUST NOT BE used in locations where temperature or atmospheric conditions are beyond those for which they have been specifically designed.
• Power from different sources MUST NOT BE connected to the contacts of one limit switch unless specifically designed for such service.
• Limit switches MUST BE used within their contact ratings and the appropriate limits switch bulletin for acceptable environmental conditions in which the switch has been designed to function properly.
• Limit switches SHOULD BE mounted rigidly and in readily accessible locations, with suitable clearances to permit easy service and replacement when necessary. Cover
• Limit switches SHOULD BE placed in locations where machining chips do not accumulate under normal operating conditions to avoid chip interference with the lever operation.
• Opposite polarities MUST NOT BE connected to the contacts of one limit switch unless the limit switch is specifically designed for such service.
SERVICING ENERGIZED INDUSTRIAL CONTROL EQUIPMENT CAN
BE HAZARDOUS. SEVERE INJURY OR DEATH CAN RESULT FROM
ELECTRICAL SHOCK, BURN OR UNINTENDED ACTUATION OF
CONTROLLED EQUIPMENT.
RECOMMENDED PRACTICE IS TO DISCONNECT AND LOCK OUT
CONTROL EQUIPMENT FROM POWER SOURCES, AND
DISCHARGE STORED ENERGY IN CAPACITORS, IF PRESENT. IF IT
IS NECESSARY TO WORK IN THE VICINITY OF ENERGIZED
EQUIPMENT, ONLY QUALIFIED PERSONNEL SHOULD BE
PERMITTED TO PERFORM SUCH WORK , USING ALL APPLICABLE
SAFETY PRACTICES AND PROTECTIVE EQUIPMENT.
IMPORTANT: MAINTENANCE NOTE
LOW AND HIGH TEMPERATURE LIMIT SWITCHES ARE
MANUFACTURED USING SPECIAL MATERIALS AND
COMPONENTS NOT AVAILABLE AS MAINTENANCE KITS
FROM THE FACTORY. DISCARD DAMAGED OR WORN
LIMIT SWITCHES AND REPLACE WITH NEW SWITCHES
FROM THE FACTORY.
STEP 1
Head Rotation Procedure
STEP 2 STEP 3 STEP 4
Remove 4 top screws.
(Mechanism is spring-loaded.
Watch out for parts.)
Remove spring and plunger assembly from head.
Note orientation of plunger assembly*
* Rotating it clockwise 90° makes it a clockwise-only switch. Rotating it counter-clockwise makes it a counter-clockwise-only switch.
(Switch operates both directions when shipped).
Re-assemble.
EA530 Series Compact Snap-Lock Limit Switch Product Instructions
Actuator Consideration
Where relatively slow motions operate the limit switch, a snap-acting or snap-lock design SHOULD BE used.
Cam or dog arrangements SHOULD BE such that the actuator is not suddenly released to snap back freely unless specifically designed for such service.
Where relatively fast motions are involved, cam arrangement SHOULD BE such that the actuator does not receive a severe impact.
For limit switches with lever actuators, the actuating force
SHOULD BE applied as nearly perpendicular to the lever as practical and perpendicular to the shaft axis in which the lever rotates.
Where relatively fast motions are involved, cams MUST BE designed such that the limit switch will be held operated long enough to operate relays, valves, etc.
Wrong
Wrong
Fast
Motion
Right
Fast
Motion LIMIT SWITCH
EA
LIMIT SWITCH
EA
LIMIT SWITCH
EA
LIMIT SWITCH
EA
Non-
Overriding
Cam
Right
LIMIT SWITCH
EA
For limit switches with pushrod actuators, the actuating force SHOULD BE applied as nearly as possible in line with the pushrod axis.
Wrong
LIMIT SWITCH
EA
LIMIT SWITCH
EA
Non-
Overriding
Cam
LIMIT SWITCH
EA
A limit switch actuator MUST BE allowed to move far enough for positive operation of the contacts.
Right
Stop
Limit switches MUST BE mounted in locations which will prevent false operation by normal movements of operator or machine components.
Limit switches are designed for proper performance with the actuators with which they are supplied.
Supplementary actuators SHOULD NOT BE used unless the limit switches are specifically designed for them.
Limit switches MUST NOT BE operated beyond the manufacturer's recommended travel. Operating positions and lever travel terminology are illustrated in drawing below. For specifications of a specific switch, refer to the switch bulletin.
Operating mechanisms for limit switches MUST BE so designed that, under any operating or emergency conditions, the limit switch is not operated beyond its overtravel limit position. A limit switch MUST NOT BE used as a mechanical stop.
NOTE: When loosening or tightening the pipe plug or set screw used to clamp the actuating lever in the desired position, care must be exercised to restrain the shaft/lever assembly so as not to transmit the applied torque to the switch itself.
T he user should refer to NFPA 70B,
R E C O M M E N D E D P R A C T I C E F O R
ELECTRICAL MAINTENANCE, published by the National Fire Protection
Association, for additional information.