CAL EI2041 PROGRAMMABLE INDICATOR
Thank you for choosing CAL EI2041 INDICATOR.
* 35x77mm sized.
* 4 digits display.
* Display scale can be adjusted between -1999 and 4000.
* Decimal point can be adjusted between 1st. and 3rd. digits.
* Measurement unit can be displayed.
* Selectable four different standard input types (0-20mA, 4-20mA, 0-1V, 0-10V)
* User can calibrate the device according to specified input type.
* Sampling time can be adjusted in four steps.
* Stores maximum and minimum measurement values.
* Maximum or the minimum values can be hold on the display.
* Two relay output for control and alarm. (Optional).
* Above and below setpoint value can be set.
* Selectable independent, deviation and band alarm.
* Sensor supply output. (Optional).
* RS485 Modbus RTU communication protocol feature. (Optional)
* CE marked according to European standards.
mA V ALR OUT
CAL EI2041
Order Code : EI2041 - - - -
Product Basic Code
Programmable Indicator
Supply Voltage Selection
230 230VAC
024 24V AC
012 12V AC
SM 9...30V DC/7...24V AC
TECHNICAL SPECIFICATIONS
Relay Output Selection
- n/a
2R
OUT and ALARM Relay Output
Modbus Selection
- n/a
RS Modbus Communication
Sensor Supply Output
- n/a
12 12V DC 50mA
08 8V DC 50mA
05 5V DC 50mA
ENVIRONMENTAL CONDITIONS
Ambient/storage temperature
Max. relative humidity
0 ... +50 °C/-25 ... +70°C (with no icing).
80% Relative humidity for temperatures up to 31°C, decreasing linearly to 50% at 40°C.
Rated pollution degree
Height
According to EN 60529 Front panel : IP65 Rear panel : IP20
Max. 2000m.
Do not use the device in locations subject to corrosive and flammable gases.
ELECTRICAL CHARACTERISTICS
Supply
Power consumption
Wiring
Date retention
EMC
Safety requirements
230V AC +%10 -%20 or 12/24V AC ±%10 50/60Hz or 9-30V DC /7-24V AC ±%10 SMPS Optional.
Max. 7VA.
2.5mm² screw-terminal connections.
EEPROM (Min. 10 years).
EN 61326-1: 2012.
EN 61010-1: 2010 (Pollution degree 2, overvoltage category II, measurement category I).
EI2041 cannot be used if measurement category II, III or IV is required.
Input type
0-1V DC voltage
0-10V DC voltage
0-20mA DC current
4-20mA DC current
Measurement range Measurement accuracy
Min.
Max.
0V
0V
0mA
0mA
1.1V
12V
25mA
25mA
±0,5% (of full scale)
±0,5% (of full scale)
±0,5% (of full scale)
±0,5% (of full scale)
Input empedance
Approx. 100kW
Approx. 100kW
Approx. 10W
Approx. 10W
While the current measuring mode, input impedance becomes 5Ω . Therefore, in current mode, the device must not be connected any voltage input.
Otherwise, the device is broken. While the device is running in the voltage measurement mode and if required to change to current measurement mode, then firstly the voltage inputs must be removed and after that, input type must be changed to one of the current measurement modes.
OUTPUTS
Sensor power supply
Out
Alarm
Life expectancy for relay
CONTROL
Control type
Control algorithm
Hysteresis
All sensor supply outputs maximum 50 mA. (Regulated and isolated).
Relay: 250V AC, 8A (for resistive load), NO; 1/2 HP 240V AC CosF = 0.4 (for inductive load).
Relay: 250V AC, 8A (for resistive load), NO; 1/2 HP 240V AC CosF = 0.4 (for inductive load).
Mechanical 30.000.000 operation; 100.000 operation at 250V AC, 8A resistive load.
Double set-point and alarm control.
On-Off control.
Adjustable between 1 ... 200.
HOUSING
Housing type
Dimentions
Weight
Enclosure material
Suitable for flush-panel mounting according to DIN 43 700.
W77xH35xD71mm.
Approx. 350g (after packaging)
Self extinguishing plastics.
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
www.west-cs.com
| WEST Control Solutions
The Hyde Business Park
Brighton East Sussex
BN2 4JU United Kingdom
Tel : +44 (0) 1273 606271
Fax : +44 (0) 1273 609990
1/5 EI2041-E-01-CAL-150520
FRONT PANEL
mA V ALR OUT
CAL
EI2041
mA LED : If input type is selected as 0-20mA or 4-20mA, mA LED lights up.
V LED : If input type is selected as 0-1V or 0-10V, V LED lights up.
ALR LED : If alarm output is active, ALR LED lights up. During delay time, LED flashes.
OUT LED : If “OUT” is active, OUT LED lights up. During delay time, LED flashes.
SET
In "Running Mode", indicates output set value.
In “Programming Mode”, indicates the selected parameter value.
In "Running Mode", indicates the maximum measured value.
Used for incrementing values in "Programming Mode".
In "Running Mode", indicates the minimum measured value.
Used for decrementing values in "Programming Mode".
DIMENSIONS
Flush mounting clamp
2
1
77mm
mA V ALR OUT
CAL EI2041
For removing mounting clamps:
- Push the flush-mounting clamp in direction 1 as shown in the figure left.
- Then, pull out the clamp in direction 2.
Flush mounting clamp
Panel cut-out
71,5mm
12 11 10 9 8 7 6 5 4 3 2 1
603 721 07
XX XX XX XX
804
SN
86 ey urk T In de
OR
Ma
AT
S NIC
DIC IN LE
RO CT LE L E
AB
RIA
30
ST
MM
DU
RA
1-2
OG
04
L
PR
EI2
CA
2 Flush mounting clamp
1
Note :
1) While panel mounting, additional distance required for connection cables should be considered.
2) Panel thickness should be maximum 7mm.
3) If there is no 60mm free space at back side of the device, it would be difficult to remove it from the panel.
Depth
71mm 5mm
2
Panel
Rubber packing
CONNECTION DIAGRAM
CAL EI2041 is intended for installation in control panels. Make sure that the device is used only for intended purpose. The shielding must be grounded on the instrument side. During an installation, all of the cables that are connected to the device must be free of energy. The device must be protected against inadmissible humidity, vibrations, severe soiling. Make sure that the operation temperature is not exceeded. All input and output lines that are not connected to the supply network must be laid out as shielded and twisted cables. These cables should not be close to the power cables or components. The installation and electrical connections must be carried on by a qualified staff and must be according to the relevant locally applicable regulations.
CAL Controls | www.west-cs.com
EI2041-230
PROGRAMMABLE INDICATOR
SN: XXXXXXXXX
Made in Turkey
8 680407 721603
230V AC
50/60Hz
+
INPUT
GND
1 2 3 4 5 6 7 8 9 10 11 12
CAL Controls | www.west-cs.com
EI2041-230-2R-05-RS
PROGRAMMABLE INDICATOR
SN: XXXXXXXXX
Made in Turkey
8 680407 722204
230V AC
50/60Hz AUX SUPPLY
+ GND
ALARM
250V 8A~
OUT
250V 8A~
+
INPUT
GND
1 2 3 4 5 6 7 8 9 10 11 12 13
NOTE :
SUPPLY :
184-253V AC
50/60Hz 7VA
1
2
Line
Neutral
Fuse
F 100 mA
250V AC
Switch
230V AC
Supply
Fuse should be connected Cable size: 1,5mm²
Holding screw
0.4-0.5Nm.
Equipment is protected throughout by
DOUBLE INSULATION
Note : 1) Mains supply cords shall meet the requirements of IEC 60227 or IEC 60245.
2) In accordance with the safety regulations, the power supply switch shall bring the identification of the relevant instrument and it
should be easily accessible by the operator.
www.west-cs.com
| WEST Control Solutions
The Hyde Business Park
Brighton East Sussex
BN2 4JU United Kingdom
Tel : +44 (0) 1273 606271
Fax : +44 (0) 1273 609990
2/5 EI2041-E-01-CAL-150520
PROGRAMMING DEVICE
Displaying the Measurement Unit
Measurement
Value
SET
& bAr
SET
In “Running Mode”, if keys are pressed together for 3 seconds, measurement unit appears. See Unit parameter for programming.
Displaying the Minimum Measurement Unit
Measurement
Value
240
Displaying the Maximum Measurement Unit
Measurement
Value
1453
In “Running Mode”, if key is pressed for 3 seconds, minimum measurement value appears.
Resetting Maximum and Minimum Measurement Values
Measurement
Value
SET rE5
In “Running Mode”, if key is pressed for 3 seconds, maximum measurement value appears.
SET
In "Running Mode", if key pressed for 2 seconds, maximum and minimum measurement values become
Locking and Unlocking
Measurement
Value
SET
&
Loc unl
Keys are locked.
Keys are unlocked.
SET
If keys are pressed together for 2 seconds, Loc message appears and keys are
SET locked. For unlocking, keys are pressed together for 2 seconds, unL message appears and keys are unlocked. If one of the keys is pressed while the device locked, Loc message appears on display.
Setting Up User Calibration Values if the standard input values (0-20mA, 4-20mA, 0-1V, 0-10V) will be used, calibration will not be necessary. Except these input values, if different input values to be used Cal.t parameter must be selected as U.Inp .
SET display and proceeding to the next step.
SET
ERROR MESSAGES & DESCRIPTIONS
Error conditions and descriptions are listed below.
* If voltage or current is difference and lower than half of full scale between H.inP and L.inP voltage or current.
* If excessive high-low input current or voltage is applied.
* If an error occurs during L.inP calibration, Err1 message appears on display.
* If an error occurs during H.inP calibration, Err2 and C.Err message appears on display.
* If user calibration is not applied before and an error occurs during calibration process, device runs according to standard calibration values.
* If user calibration is applied before and an error occurs during calibration process, device runs according to previous user calibration values.
Changing Parameters
If keys are pressed together for 2 seconds, Pi message appears and user menu entered. Then in user menu, first parameter's is displayed.
&
SET
When a parameter selected, if key is pressed selected parameter value appears and displayed parameter can be changed by keys. If no
SET operation is performed for 3 seconds after the parameter value is being displayed or key is pressed, parameter name will be shown again. While parameter name displayed, keys are pressed together, returned to "Running Mode" without waiting period.
I.typ
Programming Mode
Hidden Menu
If key is pressed for 7 seconds P2 message appears on the display and hidden menu is entered. Selected
SET parameter values can be displayed with key and canged with keys. Accessing to the parameters and storing functions are as in the user menu. All parameters can be accessed from this menu.
Parameter Transfer Between Menus
SET
If keys are pressed together for 2 seconds, parameter transferred to user menu. In this way up to 12 parameters can be transferred to the user menu.
SET
In user menu, if keys are pressed together for 2 seconds, parameter is removed from user menu. When a parameter is displayed in the user menu, mA LED lights up in the hidden menu.
baUd
I.typ
Setting Up Measurement Unit (Unit) Parameters
SET
If pressed key in Unit parameter, related digit blinks on display. For desired number, letter or symbol is adjusted by pressing the key for related digit. For
SET setting up other digits key is pressed. When parameter setting process is completed, by pressing key or no key is pressed for 3 seconds without pressing any key, parameters can be saved.
Factory Defaults Viewing the Revision
SET
& message will see and restore the factory parameters
Running Mode Error Messages
L.inp.
Input voltage or input current below zero.
H.inp.
Input voltage higher then 15V or input current higher than 25mA.
Err.1
L.INP calibration error
Err.2
H.INP calibration error
C.Err
Calibration failed www.west-cs.com
| WEST Control Solutions
The Hyde Business Park
Brighton East Sussex
BN2 4JU United Kingdom
Tel : +44 (0) 1273 606271
Fax : +44 (0) 1273 609990
3/5 EI2041-E-01-CAL-150520
Independent alarm
A.tyP.=indE
ON
OFF A.5tA.= Hi
ALARM CONDITIONS
Deviation alarm
A.tyP.= dE.
O.5Et
ON
OFF A.5tA.= Hi
Band alarm
A.tyP.= bAnd
O.5Et
ON
O.5Et: Out set value
A.5Et: Alarm set value
OFF A.5tA.= Bo.Hi.
ON
OFF
A.5tA.= Lo
ON
OFF
A.5tA.= Lo
ON
OFF A.5tA.= Bi.Hi.
A.Hy5
A.5Et
A.Hy5
A.Hy5
A.Hy5
O.5Et - A.5Et
O.5Et + A.5Et
O.5Et + A.5Et
PARAMETER LIST
CONFIGURATION PARAMETERS
I.typ
Input type selection. (0-20mA, 4-20 mA, V, d5p.C
ratE
Hold
V
Indicator configuration. (prc5 : Process value, Pr.Un : 4 Seconds process value, 2 Seconds Unit value.)
Measurement ranges.
Fa5t : Average of 1 measurement value is gathered in 200msec.
5lo.1 : Average of 4 measurement value is gathered in 200msec.
5lo2 : Average of 8 measurement value is gathered in 200msec.
5lo3 : Average of 16 measurement value is gathered in 200msec.
Indicator holding parameter. ( nonE : instant measurement value, lo. : minimum value, HI : maximum value is displayed.)
Unit Measurement value. (Desired measurement value for unit selection).
Cal.t
Calibration type. ( 5.Inp : Standard input type, U.Inp : User defined input type selection ).
d.Pnt
Decimal point selection. ( Adjustable between the 1th. and 3rd digits ).
L.5CL
Lower scale value. ( Adjustable between -1999 and H.5CL value ).
Initial Value
0-10
Prc5
5lo.1
nonE
nonE
5.Inp
0
0
H.5CL
Upper scale value. ( Adjustable between L.5CL and 4000 value ).
OUTPUT CONTROL PARAMETERS
O.5Et
Output set value. ( Adjustable between L.5CL and H.5CL).
2000
Initial Value
2000
O.HY5
O.5ta
Output hysteresis value. ( Adjustable between 1 and 200 ).
2
Output status. (Off: Output not active, Lo: Becomes active below the setpoint output value, H1:Becomes active above the setpoint output value).
oFF
O.Pon
Required relay-on delay time in order to set output to active state after power-up. ( Adjustable between 0 and 99 minutes ).
O.ton
Output relay-on delay time. ( Adjustable between 0 and 99 minutes ).
01:00
01:00
O.toF
Output relay-off delay time. Adjustable between 0 and 99 minutes ).
ALARM CONTROL PARAMETERS a.5Et
Alarm set value. ( Adjustable between L.5CL and H.5CL).
01:00
Initial Value
2000 a.HY5
Alarm hysteresis value. ( Adjustable between 1 and 200 ).
a.typ
Alarm type. (IndE : Independent alarm, dE: Deviation alarm, band: Band alarm) a.5ta
Alarm condition. (OFF:Alarm not active. For independent or deviation alarm, Lo: Alarm is active below the set value, H1: Alarm is active above the set value. For band alarm, BI.HI : Activated in "in-band", Bo.HI : Activated in "out-band".)
A.Pon
Required relay-on delay time in order to set alarm output to active state after power-up. ( Adjustable between 0 and 99 minutes ).
A.ton
Alarm output relay-on delay time. ( Adjustable between 0 and 99 minutes ).
A.toF
RS485 MODBUS COMMUNICATION PARAMETERS
2 indE
oFF
01:00
01:00
01:00
Initial Value adr5
Slave device address. ( Adjustable between 1 and 247 ) baUd Baudrate. ( Off, 1200, 2400, 4800, 9600,19200 kbps ayarlanabilir )
1
9600 www.west-cs.com
| WEST Control Solutions
The Hyde Business Park
Brighton East Sussex
BN2 4JU United Kingdom
Tel : +44 (0) 1273 606271
Fax : +44 (0) 1273 609990
4/5 EI2041-E-01-CAL-150520
MODBUS ADDRESS MAP
HOLDING REGISTERS
Holding Register
Addresses
Decimal Hex
0000d
Data
Type
0x0000 word
Data Content
Input type selection. 0=0-20;1=4-20;2=0-1;3=0-10
0008d
0009d
0010d
0011d
0012d
0013d
0014d
0015d
0001d
0002d
0003d
0004d
0005d
0006d
0007d
0016d
0017d
0018d
0x0001 word
0x0002 word
0x0003 word
0x0004 word
0x0005 word
0x0006 word
0x0007 word
0x0008 word
0x0009 word
0x000A word
0x000B word
0x000C word
0x000D word
0x000E word
0x000F word
0x0010 word
0x0011 word
0x0012 word
Measurement ranges. 0=Fa5t;1=5.lo1;2=5.lo2;3=5.lo3
Indicator locking parameter. 0=nonE;1=lo;2=HI
Decimal point. 0=x;1=x.x;2=x.xx;3=x.xxx
Scale lower value.
Scale upper value.
Output set value.
Output hysteresis value.
Output condition. (0=OFF,1=Lo, 2=H1)
Required relay-on delay time in order to set output to active state after power-up.
Output relay-on delay time.
Output relay-off delay time.
Alarm set value.
Alarm hysteresis value.
Alarm type. 0=IndE;1=dE;2=band
Alarm condition. 0=OFF, 1=Lo;1=H1;2=b1.H1;3=bo.H1
Required relay-on delay time in order to set alarm output to active state after power-up.
Alarm output relay-on delay time.
Alarm output relay-off delay time.
Parameter
Name o.5ta
o.pon
o.ton
o.tof
a.5Et
a.HY5
A.typ
A.5ta
i.tyP
RAtE hold d.pnt
l.5Cl
H.5Cl
o.5Et
o.Hy5
a.pon
a.ton
a.tof
Read / Write
Permission
INPUT REGISTERS
Holding Register
Addresses
Decimal Hex
Data
Type
Data Content Parameter
Name
Read / Write
Permission
0000d
0001d
0x0000 word
0x0001 word
Measured value
Minimum measured value
–
–
Read Only
Read Only
0002d 0x0002 word Maximum measured value – Read Only
* Holding and Input Register parameters, which in integer type is defined as signed integer. Timing parameters are defined as seconds.
(For example, 01:15 is defined as 75 seconds).
DISCRATE INPUTS
Holding Register
Addresses Data
Type
Decimal Hex
0000d 0x0000 bit
0001d 0x0001 bit
Data Content
OUT Control output condition. (0=OFF; 1=ON).
Alarm control output condition. (0=OFF; 1=ON).
Parameter
Name
–
–
Read / Write
Permission
Read Only
Read Only
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
COILS
Coil
Addresses
Decimal Hex
0000d 0x0000
0001d 0x0001
Data
Type bit bit
Data Content
Indicator configuration oFF=pr.C5, ON=Pr.Un
Calibration type oFF=5.Inp, ON=U.Inp
Parameter
Name d5p.C
Cal.t
Read / Write
Permission
R W
R W www.west-cs.com
| WEST Control Solutions
The Hyde Business Park
Brighton East Sussex
BN2 4JU United Kingdom
Tel : +44 (0) 1273 606271
Fax : +44 (0) 1273 609990
5/5 EI2041-E-01-CAL-150520
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement