BDP A 658A Troubleshooting guide
Add to my manuals
16 Pages
The BDP A 658A is a powerful and versatile device that offers a range of features to enhance your home comfort system. With its integrated control motor (ICM2), the BDP A 658A delivers precise airflow management, ensuring optimal performance in various operating modes, including cooling, heating, and heat pump operation. The ICM2 also allows for customization of airflow settings to meet your specific needs. Additionally, the BDP A 658A includes a selection of delay profiles, enabling you to fine-tune the system's operation for improved efficiency and comfort.
advertisement
troubleshooting guide
INTEGRATED CONTROL MOTOR (ICM2)
Cancels: New TI 557A-48-1
3/15/97
CONTENTS
Page
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
COMPONENT DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . 1-5
ICM2 Selection Modes . . . . . . . . . . . . . . . . . . . . . . . . . .
1
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . .
5
I. Continuous Fan Operation . . . . . . . . . . . . . . . . . .
5
II. Cooling Mode, 557A and 657A Units . . . . . . . . .
5
III. Cooling Mode, 658A and 589A Units . . . . . . . . .
5
IV. Heating Mode, 658A and 589A Units . . . . . . . . . .
5
V. Electric Heat Mode . . . . . . . . . . . . . . . . . . . . . . . .
5
VI. Heat Pump, Heating with Auxiliary
Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
VII. ICM2 Control Power . . . . . . . . . . . . . . . . . . . . . . .
5
VIII. Low-Voltage Circuit Fusing . . . . . . . . . . . . . . . . .
5
IX. Motor Power Connections . . . . . . . . . . . . . . . . . .
5
OPERATING PROBLEMS . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
I. Fan Will Not Turn On from Thermostat . . . . . . .
5
II. Fan Will Turn On, but Electric Heat
Stages Will Not . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
III. Easy Select Board Fuse Keeps Blowing . . . . . .
6
IV. Motor Does Not Run . . . . . . . . . . . . . . . . . . . . . .
7
V. Motor Shaft Does Not Rotate Smoothly . . . . . . .
7
VI. Motor Does Not Run Smoothly . . . . . . . . . . . . . .
7
VII. Motor Does Not Stop Running . . . . . . . . . . . . . .
7
TROUBLESHOOTING SUMMARY . . . . . . . . . . . . . . . . . . 8-16
UNIT
557A
589A
657A
658A
WARNING:
GENERAL
This manual contains information to assist in troubleshooting operating problems and errors associated with the
Integrated Control Motor (ICM2). The ICM2 is used in the units listed in Table 1.
Table 1 — Units With ICM2
UNIT SIZE
048,060
048,060
048,060
048,060
Before performing service or repair operations on unit, turn off main unit power. Electrical shock could cause personal injury.
COMPONENT DESCRIPTION
The ICM2 (Fig. 1) is powered with high voltage at all times.
It is pre-programmed and contains airflows for all modes of operation.
The ICM2 reacts to changes in system static pressures to maintain constant airflow. The blower delivers requested airflow up to about 0.7 in. of static pressure.
The ICM2 will not operate with high voltage alone; low voltage must be applied to the control plug for the motor to run.
The ICM2 is first fed high voltage through the 5-pin connector. As this occurs, the AC power is rectified to DC by a diode module. After rectification, the DC signal is electronically communicated and fed in sequential order to stator windings. The frequency of communication pulses determines motor speed.
The rotor is permanently magnetized.
The ICM2 interfaces with the Easy Select Board (Fig. 2 and
3). Setting up desired system airflow is accomplished through selections made on the Easy Select Board. Power for the system is supplied from a 230-vac, 60 Hz line. A class 2 voltage
(24 vac nominal) transformer is used for thermostat connections. The transformer is located either in, or below, the main unit control box, depending on the unit. The secondary (SEC) side of the transformer is connected to the control box. The
24-vac secondary circuit includes a socket, soldered into the circuit at SEC2, to receive a 5-amp automotive-type fuse.
ICM2 SELECTION MODES
Connections to the thermostat are made at leads connected through P1 of the Easy Select Board. Eighteen 0.187-in.
quick-connect terminals comprise the field select taps, which provide programming selection for ICM2. Wiring for the 5 selection modes is listed in Table 2.
Table 2 — ICM2 Selection Mode Wiring
MODE
AUX Heat Range
AC/HP Size
Type
AC/HP CFM Adjust
AC/HP Time Delay
WIRE COLOR
Violet
Blue
Orange
Black
Gray
LEGEND
AC — Air Conditioning
HP — Heat Pump
The 557A, 589A, 657A and 658A units are factory-set to operate properly with system components. See Fig. 4 for factory default settings. To reconfigure a basic system, refer to information printed on the circuit board next to select pins, and to base unit installation instructions. Move the 5 selection wires to match the components used.
DO NOT REMOVE
1 2 3 4 5
POWER CONNECTOR
9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8
CONTROL CONNECTOR
OPTIONAL
SAFETY
GROUND
Table 3 — Allowable Airflows for AUX HEAT
AUX HEAT
Cfm
Gas Heat Input Size
(Btuh)
80,000
100,000
120,000
140,000
Electric Heater Package
(5-10 kW)
EASY SELECT BOARD TERMINAL
1 2 3 4
1300 1400 1600 1700
X
X
X
X
X
X
X
X
X
X
X
X
X
X
B. AC/HP SIZE
The preset factory default selection for AC/HP Size is 400 cfm per ton. The selection pins are configured for 350 cfm per ton at terminals 1 and 3, and 400 cfm per ton at terminals 2 and 4.
C. TYPE
The type is a preset factory default selection. The factory setting is AC for 589A and 557A units. For 658A units, the factory setting is AC. For 657A units the factory setting is
HP. The HPC provides the same airflow as the AC selection.
OPTIONAL
SAFETY
GROUND
CONTROL
CONNECTOR
POWER
CONNECTOR
DRAIN
HOLE
Fig. 1 — Integrated Control Motor 2
A. AUX HEAT RANGE
Airflow for 658A and 589A units is a preset factory selection. The airflow selection must not be set lower than the default. Refer to Table 3 for the allowable airflows.
Airflow for 657A, 557A units requires the installer to select the auxiliary heat airflow that best suits the installation. Refer to installation instructions for electric heaters. See
Table 3 for available airflow.
Each select pin is configured for a certain airflow. The airflow will be supplied in the emergency heat mode, which is the heating mode on units with electric heat as the primary heating source.
For heat pump units, the ICM2 will run whichever is higher; heat pump airflow or electric heat airflow. The preset factory default selection is the highest airflow. This helps ensure safe heater operation.
LEGEND
IFO — Indoor (Evaporator) Fan On
JW — Jumper Wire
Fig. 2 — Easy Select Board
D. AC/HP CFM ADJUST
The preset factory default selection is MED. Selections HI and LO will adjust the airflow supplied for all operation modes.
Refer to Table 4. The selection options are provided for the installer to meet individual installation needs (static compensation, noise, etc.).
Table 4 — Airflow Percentage Difference From
Nominal (MED Setting)
MODE
LO ADJUST
HI ADJUST
FAN ONLY COOLING HEATING HEAT PUMP
−15%
15%
−12.5%
12.5%
−15%
15%
−10%
10%
—2—
L SEC 2 SEC 1 O Y/Y2 W2 G Y1
1
2
3
4
5
6
7
8
9
10
P1
L
R
C
O
Y/Y2
Y1
G
E/W1
W2
W3
JW1
JW2
D2
D1
D3
D4
D5
AC/HP
TIME DELAY
GRY
1
2
3
4
AC/HP
CFM ADJUST
BLK
LO
MED
HI
TYPE
ORN
AC
HPC
HP
AC/HP
SIZE
BLU
1
2
3
4
AUX HEAT
RANGE
VIO
1
2
3
4
P2
1
2
3
4
5
6
7
E/W1/W2
G
R
Y/Y2
Y1
JW3
IFO
R2
2W
R3
2W
R1
2W
Fig. 3 — Easy Select Board Circuitry
LEGEND
IFO — Indoor Fan On
JW — Jumper Wire
VIO
BLU
ORN
BLK
GRY
1300
1400
30 sec ON/
60 sec OFF
1
1
1
AC
LO
589A, 658A MODELS
AUX. HEAT RANGE
2
1400 1600
AC/HP SIZE
2
1600 1750
TYPE
HPC
AC/HP CFM ADJUST
MED
AC/HP TIME DELAY
2
0 sec ON/
0 sec OFF
0 sec ON/
30 sec OFF
3
3
3
HP
HI
4
1750
2000
4
0 sec ON/
45 sec OFF
4
VIO
BLU
ORN
BLK
GRY
1300
1400
30 sec ON/
60 sec OFF
1
1
1
AC
LO
557A MODELS
AUX. HEAT RANGE
2
1400 1600
AC/HP SIZE
2
1600 1750
TYPE
HPC
AC/HP CFM ADJUST
MED
AC/HP TIME DELAY
2
0 sec ON/
0 sec OFF
0 sec ON/
30 sec OFF
3
3
3
HP
HI
4
1750
2000
4
0 sec ON/
45 sec OFF
4
VIO
BLU
ORN
BLK
GRY
1300
1400
30 sec ON/
60 sec OFF
1
1
1
AC
LO
657A MODELS
AUX. HEAT RANGE
2
1400 1600
AC/HP SIZE
2
1600 1750
TYPE
HPC
AC/HP CFM ADJUST
MED
AC/HP TIME DELAY
2
0 sec ON/
0 sec OFF
0 sec ON/
30 sec OFF
3
3
3
HP
HI
4
1750
2000
4
0 sec ON/
45 sec OFF
4
FACTORY DEFAULT SETTING
NOTE: The AC/HP SIZE setting is Terminal 2 for size 048 and Terminal 4 for size 060.
Fig. 4 — Factory Default Settings
—4—
E. AC/HP TIME DELAY
Four motor operation delay profiles are provided to customize and enhance system operation. These selections include an option for no delays, which may be used during service procedures. When other components, such as Integrated Gas
Control (IGC), are used to perform the delay function the preset factory default setting is terminal 2 for 658A and 589A units.
Also available is a 30-second ON/60-second OFF delay profile at terminal 1. This profile may be used to allow system coils time to heat or cool, and may minimize some cold blow in heat pump operation.
A 30-second OFF delay at terminal 3 and a 45-second OFF delay at terminal 4 are optional.
SEQUENCE OF OPERATION
I. CONTINUOUS FAN OPERATION
The thermostat closes circuit R to G. The G signal is sent directly to ICM2.
II. COOLING MODE, 557A AND 657A UNITS
The thermostat closes circuit R to G, R to Y/Y2, R to O, and
R to Y1 (heat pump only) for single speed. The Y/Y2 signal is sent directly to ICM2. On heat pump units, Y1 signal is also sent directly to ICM2.
III. COOLING MODE, 658A AND 589A UNITS
Thermostat closes, closing circuits from R to G, R to Y1, R to Y2 and O (658A units only). All but the G signal are sent to ICM2 directly. The G signal is not sent directly because the JW3 jumper is cut to prevent feedback in heating mode.
The G signal is sent to the Integrated Gas Control (IGC) board, where the indoor fan contacts closes and energize the IFO
(Indoor Fan On) terminal. It is then sent to the ICM2 directly.
IV. HEATING MODE, 658A AND 589A UNITS
A. 658A Units
For heat pumps, the thermostat closes, closing circuits R to
G, R to Y1 and R to Y/Y2. Y1 and Y/Y2 are sent to ICM2 directly. The IGC board sends the G signal to ICM2 through the IFO terminal.
B. 589A Units
Thermostat closes, closing circuit from R to W1. Signal is sent to both the IGC board and the ICM2. When the indoor fan contacts close on the IGC board, a 24-volt signal is sent to
ICM2 through the IFO terminal.
V. ELECTRIC HEAT MODE
Thermostat closes circuit R to W2, W3, or E. The terminal block positions W2, W3 and E are tied together by jumpers
JW1 and JW2. These jumpers are provided for future flexibility staging of electric heater banks. When staging is a requirement, the installer must cut jumpers and wires in thermostats, following common procedure and practice. The 3 electric heater inputs are also interlocked through diodes D1, D2, and D3 to motor input W.
VI. HEAT PUMP, HEATING WITH AUXILIARY HEAT
Thermostat closes circuits R to Y/Y2 and R to Y1, with R to
W2, W3 or E (and R to O in case of defrost). In the event that electric heating is called for by the thermostat while heat pump is operating in heat or defrost mode, the electric heating signal will appear at motor connector pin 1. If necessary, the motor will modify airflow output to provide an airflow that is safe for operation of electric heater.
VII. ICM2 CONTROL POWER
The ICM2 control power is supplied for R circuit through runs to motor control connector pin 5, then through motor control harness to motor. The C side of low voltage control power circuit is connected by printed circuit runs to motor connector pins 3 and 4, then through motor control harness to motor.
VIII. LOW-VOLTAGE CIRCUIT FUSING
Low-voltage circuit is fused by a board-mounted 5-amp automotive-type fuse placed in series with transformer SEC2 and R circuit. The C circuit of transformer is referenced to chassis ground through a printed-circuit run at SEC1, connected to a metal standoff marked ‘Ground Screw Required.’
A ground screw must be in place or erratic motor operation may result.
IX. MOTOR POWER CONNECTIONS
The high-voltage 230-vac power input to the Easy Select Board is provided through line side of contactor to plug 4 of motor. High voltage terminals are 4 and 5. Terminal 3 is ground connection.
OPERATING PROBLEMS
WARNING: Turn off all power to unit before performing any service procedure to avoid the possibility of electric shock and personal injury.
I. FAN WILL NOT TURN ON FROM THERMOSTAT
This may indicate a problem with high voltage connections.
Perform the following checks:
1. Check power leads L1 and L2. If L1 and L2 are not receiving power the system cannot function.
2. Check 5-pin connector at motor for 230 volts, or check for continuity.
3. Check the low-voltage transformer leads. Be sure they are wired correctly.
4. Check output voltage of transformer secondary side
SEC1 and SEC2. Ensure transformer output is approximately 24 vac. If transformer output is 0 vac and the transformer is receiving correct input voltage (208 v or
240 v), then the transformer must be replaced.
If the transformer output is 24 vac, check the Easy Select
Board voltage as follows:
Check low-voltage fuse (Fig. 2). If fuse is blown, replace it.
The transformer cannot supply power to the Easy Select Board with a loose or blown fuse.
If the fuse blows when the unit has power supplied to it, the system likely has one of the following problems:
• Electrical short or miswiring. Check control circuit.
• Transformer load exceeding maximum of 40 va. If the load is excessive, the low-voltage 5-amp fuse will blow to protect the transformer. Check relays for excessive current draw.
Refer to Tables 5 and 6 for Easy Select Board male/female quick connect terminals and connections.
—5—
II. FAN WILL TURN ON, BUT ELECTRIC HEAT STATES WILL
NOT
Perform the following checks:
1. Check relay wirings, fuses to electric heaters (if applicable), and voltage to relay. All relays numbered one receive a 24-vac signal. If the correct voltage is being received, check if relay is closing. If the relay is not closing, relay must be replaced.
2. Check for blown diodes. If diodes are blown it is likely that a plug is miswired. Easy Select Board must be replaced if diode is bad.
3. Check if traces on back of Easy Select Board are overheated. If traces are overheated, there likely has been a high-voltage short, or high-voltage has been applied to a low-voltage circuit. This can be prevented by ensuring the Easy Select Board has been correctly wired prior to applying power.
III. EAST SELECT BOARD FUSE KEEPS BLOWING
When the low-voltage fuse blows, it is likely that the transformer would have blown had the low-voltage fuse not been in circuit to protect it. The fuse usually blows when there is high current drawn on the transformer, high-voltage applied to the low-voltage circuit, or a direct secondary short.
When there is high current drawn on the transformer, it is most likely because the transformer has been shorted or the system is drawing more va than the transformer rating allows. When fuse blows because of high voltage, the system has mixed high and low voltage signals.Perform the following checks:
1. Check transformer, thermostat and control box wiring.
2. Check to be sure low-voltage and high-voltage wiring are connected to proper terminals.
3. Check va draw on transformer. If va draw is more than va rating of the transformer, fuse will blow. Transformer must be replaced with one that has a higher va rating.
FEMALE CONNECTION SIZE
0.25 x 0.032
0.187 x 0.032
Table 5 — Male/Female Quick Connect Terminals
MALE CONNECTION
Y/Y2
Y1
SEC1
SEC2
IFO
O
AUX1
AUX2
G
RED
L
UNITS 557A, 589A, 657A, 658A
High and single speed
Low speed compressor
Secondary connection from transformer (24 vac). This connection is common to chassis ground through eyelet marked GROUND SCREW
REQUIRED.
Secondary connection from transformer (24 vac)
Indoor Fan ON terminal
4-Way valve
Low voltage ground for auxiliary option (24 vac)
Low voltage output for auxiliary option (24 vac)
Indoor Fan
Common to R screw terminal and SEC2
This connection is a field termination for use in connection leads (L) of thermostat. There is no connection of this terminal with control circuitry.
TYPE
CONNECTION
Thermostat
Connection
Integrated Control
Motor 2
TYPE
CONNECTOR
10-Pin
Header
7-Pin
Header
PIN NO.
Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
Pin 6
Pin 7
Pin 8
Pin 9
Pin 10
Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
Pin 6
Pin 7
Table 6 — Connections and Connector
DESCRIPTION
L — This connection is a field termination for use in connecting leads (L) of thermostat. There is no connection of this terminal with control circuitry.
R — Connection for R signal to thermostat (24 vac)
C — Connection for C terminal to thermostat (24 vac common)
O — Connection for O signal from thermostat
Y/Y2 — Connection for Y signal from thermostat
Y1 — Connection for low-speed compressor operation
G — Connection for G signal from thermostat
E/W1 — Connection for E signal from thermostat/W1 on Gas Heat
W2 — Connection for W2 signal from thermostat
W3 — Connection for W3 signal from outdoor thermostat
Diode OR output of E/W1 or W3 or W2 thermostat signals
Thermostat G signal
Common to C, SEC1, and chassis ground
Common to C, SEC1, and chassis ground
Common to R and SEC2 (via 5-amp fuse)
Thermostat Y/Y2 signal
Thermostat Y1 signal
—6—
IV. MOTOR DOES NOT RUN
Perform the following checks:
1. Check all plugs and receptacles on ICM2 circuit board and motor for bad connections. Be sure all plugs are fully seated.
2. Verify that there are approximately 230 v at terminals of contactor. If not, determine if high-voltage is entering the unit.
3. Verify that there is a low-voltage control signal to the motor. The motor receives control signals through the
7-pin motor plug P2. The voltage output of each pin in the plug will be different, depending on mode or operation. Table 7 lists voltage present in each pin of 7-pin plug for each operating mode. Testing should be done between the points listed in Table 7, and the common
C screw terminal. If all the values of any one of the operating modes check out, and the motor still fails to run, it is likely the motor is defective and will need replacement.
V. MOTOR SHAFT DOES NOT ROTATE SMOOTHLY
The motor shaft normally does not run smoothly. This is due to steps in rotation, called motor cogging. The cogging is caused by permanent magnets passing each pole in the motor.
However, the shaft should not require excessive force to turn.
If shaft is very difficult to turn, motor control or bearings have failed and the motor must be replaced.
VI. MOTOR DOES NOT RUN SMOOTHLY
Perform the following check:
Check blower wheel for damage and determine if blower wheel is out of balance. If it is not defective, the motor will likely need replacement.
VII. MOTOR DOES NOT STOP RUNNING
Perform the following checks:
1. Check for good ground between motor ground lead, transformer common lead, and control board. If this does not stop the motor, continue to Step 2.
2. Remove all thermostat wiring. If this makes the motor stop, it means the circuit board is faulty and must be replaced. If it does not stop, continue to Step 3.
3. Remove the 7-pin plug. If motor still runs, replace motor.
Table 7 — Motor Control Test Values
OPERATING MODE
Electric
1-Speed AC
2-Speed AC, Low Speed
2-Speed AC, High Speed
1-Speed HP
1-Speed HP
2-Speed HP, Low Speed
2-Speed HP, Low Speed
2-Speed HP, High Speed
2-Speed HP, High Speed
Continous Fan
SCREW TERMINALS
HAVING 24 VAC
Heating R W2
Cooling R Y/Y2
Cooling R Y1
Cooling R Y/Y2
Cooling R Y/Y2
Heating R Y/Y2
Cooling R
Heating R
Y1
Y1
Cooling R Y/Y2
Heating R Y/Y2
R G
W3* E*
G
G
G
G
G
G
G
Y1
Y1
O
O
G O
G
W
Pin 1
24 vac
0
0
0
0
0
0
0
0
0
0
LEGEND
AC — Air Conditioning
HP — Heat Pump
*Pin 1 has 24 vac with or without jumpers whenever any individual heater input or any combination of heater inputs are energized.
G
Pin 2
0
24 vac
24 vac
24 vac
24 vac
24 vac
24 vac
24 vac
24 vac
24 vac
24 vac
VOLTAGES — 7-PIN PLUG P2
C
Pin 3
0
0
0
0
0
0
0
0
0
0
0
C
Pin 4
0
0
0
0
0
0
0
0
0
0
0
R
Pin 5
Y/Y2
Pin 6
24 vac 0
24 vac 24 vac
24 vac
24 vac
24 vac
24 vac
0
24 vac
24 vac 24 vac
24 vac 24 vac
0
0
Y
Pin 7
0
0
24 vac
0
0
0
24 vac
24 vac
24 vac 24 vac 24 vac
24 vac 24 vac 24 vac
24 vac 0 0
—7—
TROUBLESHOOTING SUMMARY
Use Table 8 and Fig. 5-12 in troubleshooting.
Table 8 — Troubleshooting Summary
SYMPTOM
Motor runs in some operation modes, but not in others.
Circuit board will not operate.
Motor is hard to turn manually.
Motor does not stop running.
Motor does not operate.
CAUSE
Poor connection between components
Burnt components
Blown fuse
Blown transformer
Motor control or bearing failure
Faulty circuit board, thermostat
Faulty motor
Burnt components
REMEDY
Check wiring harness connectors (see Note 1).
Check for a good ground connection between motor ground lead and circuit board screw.
Check thermostat connections (Note 2).
Check for burn traces or burnt components. If present, replace circuit board.
Check 5-amp fuse.
Check for 24v between SEC1 and SEC2.
If no voltage present, check transformer.
Replace motor.
Test circuit board by removing 7-pin plug from circuit board.
If motor stops, it is a problem with the circuit board or thermostat.
Test thermostat by disconnecting it from circuit board.
If motor fails to stop running once 7-pin plug is removed from circuit board, replace motor.
Replace motor and verify that drip loop is present on connection wires.
LEGEND
SEC — Secondary
NOTES:
1. To check wiring harness, shut off power to unit. Remove 5-pin plug from motor. Never
remove 5-pin plug from motor with power on. Check for 24v between pin-1 and pin-12 on the 16-pin plug. If no voltage is present, replace wiring harness. If voltage is present, jumper terminals R-Y/Y2 on circuit board and check for 24v between pin-12 and pin-14 and pin-16 (see below).
16 15 14 13 12 11 10 9
8 7 6 5 4 3 2 1
16-PIN PLUG
2. To check thermostat, remove thermostat wires from circuit board. Jumper screw terminals one at a time as follows: R-G, R-Y/Y2, R-Y1 and R-W2 to check connections.
—8—
Fig. 5 — Wiring Diagram, Units 658A048,060; 208/230-1-60
—9—
LEGEND
AWG — American Wire Gage
BR
C
CAP
CB
— Blower Relay
— Contactor, Compressor
— Capacitor
— Circuit Breaker
COMP — Compressor Motor
CR
CTD
DB
DFT
DR
— Compressor Relay
— Compressor Time Delay
— Defrost Board
— Defrost Thermostat
— Defrost Relay
EQUIP — Equipment
FL
FS
FU
— Fuse Link
— Flame Sensor
— Fuse
GND
GVR
HLR
HR
HS
HV
TRAN
I
ICM
— Ground
— Gas Valve Relay
— Heater Lockout Relay
— Heater Relay (Strip
Heat)
— Hall Effect Sensor
— High-Voltage
Transformer
— Ignitor
— Integrated Control
IDM
IFM
IFO
IGC
LPS
LR
LS
MGV
OAT
OFM
QT
RS
RVS
Motor
— Induced-Draft Motor
— Indoor-Fan Motor
— Indoor-Fan On
— Integrated Gas Control
— Low-Pressure Switch
— Lockout Relay
— Limit Switch
— Main Gas Valve
— Outdoor-Air Thermostat
— Outdoor-Fan Motor
— Quadruple Terminal
— Rollout Switch
— Reversing Valve
Solenoid
SEC — Secondary
TRAN — Transformer
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional
Wiring
To Indicate Common
Potential Only, Not to Represent Wiring
NOTES:
1. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent.
2. Set heat anticipator at .6.
3. Use copper conductors only.
4. ICM board connections.
UNIT
658A
1
TERMINAL NO.
2 3
CFM
4
(VIO)
Aux,
Heat
Range
(BLU)
AC/HP
Size
1300
1400
1400 1600
1600 1750
1750
2000
(GRY)
AC/HP
Time
Delay
30 sec.
ON
1 min.
OFF
0 sec.
ON
0 sec.
OFF
0 sec.
ON
30 sec.
OFF
0 sec.
ON
45 sec.
OFF
LED INDICATIONS
ERROR MODE LED INDICATION
Normal Operation
Hardware Failure
Fan ON/OFF Delay
Modified
Limit Switch Fault
Flame Sense Fault
5 Consecutive Limit
Switch Faults
Ignition Lockout Fault
Inducer Switch Fault
Rollout Switch Fault
Internal Control Fault
ON
OFF
1 FLASH
2 FLASH
3 FLASH
4 FLASH
5 FLASH
6 FLASH
7 FLASH
8 FLASH
Fig. 6 — Wiring Diagram, Units 658A048,060; 208/230-3-60
—10—
LEGEND
AWG
BR
C
CAP
CB
COMP
CR
CTD
DB
DFT
DR
EQUIP
FL
FS
FU
GND
— American Wire Gage
— Blower Relay
— Contactor, Compressor
— Capacitor
— Circuit Breaker
— Compressor Motor
— Compressor Relay
— Compressor Time Delay
— Defrost Board
— Defrost Thermostat
— Defrost Relay
— Equipment
— Fuse Link
— Flame Sensor
— Fuse
— Ground
IGC
IP
LPS
LR
LS
MGV
NEC
OAT
GVR
HLR
HR
HS
—
—
—
—
Gas Valve Relay
Heater Lockout Relay
Heater Relay (Strip Heat)
Hall Effect Sensor
I
HV TRAN — High-Voltage Transformer
— Ignitor
ICM
IDM
IFM
IFO
—
—
—
—
Integrated Control Motor
Induced-Draft Motor
Indoor-Fan Motor
Indoor-Fan On
—
—
—
—
—
—
—
—
Integrated Gas Control
Internal Protector
Low-Pressure Switch
Lockout Relay
Limit Switch
Main Gas Valve
National Electrical Code
Outdoor-Air Thermostat
OFM
QT
RS
RVS
SEC
TH
TRAN
— Outdoor-Fan Motor
— Quadruple Terminal
— Rollout Switch
— Reversing Valve Solenoid
— Secondary
— Thermostat-Heating
— Transformer
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional
Wiring
To Indicate Common
Potential Only, Not to Represent Wiring
NOTES:
1. If any of the original wire furnished must be replaced, it must be replaced with type
90 C wire or its equivalent.
2. Set heat anticipator at .6.
3. Use copper conductors only.
4. ICM board connections.
UNIT
658A
1
TERMINAL NO.
2 3
CFM
4
(VIO)
Aux,
Heat
Range
(BLU)
AC/HP
Size
1300
1400
1400
1600
1600
1750
1750
2000
(GRY)
AC/HP
Time
Delay
30 sec.
ON
1 min.
OFF
0 sec.
ON
0 sec.
OFF
0 sec.
ON
30 sec.
OFF
0 sec.
ON
45 sec.
OFF
LED INDICATIONS
ERROR MODE LED INDICATION
Normal Operation
Hardware Failure
Fan ON/OFF Delay
Modified
Limit Switch Fault
Flame Sense Fault
5 Consecutive Limit
Switch Faults
Ignition Lockout Fault
Inducer Switch Fault
Rollout Switch Fault
Internal Control Fault
ON
OFF
1 FLASH
2 FLASH
3 FLASH
4 FLASH
5 FLASH
6 FLASH
7 FLASH
8 FLASH
NOTES:
1. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent.
2. Use copper conductors only.
3. ICM board connections.
UNIT
589A
(VIO)
Aux,
Heat
Range
(BLU)
AC/HP
Size
1
TERMINAL NO.
2 3
CFM
1300 1400
1400 1600
1600
1750
4
1750
2000
(GRY)
AC/HP
Time
Delay
30 sec.
ON
1 min.
OFF
0 sec.
ON
0 sec.
OFF
0 sec.
ON
30 sec.
OFF
0 sec.
ON
45 sec.
OFF
LEGEND
ICM
IDM
IFM
IGC
LS
MGV
NEC
OFM
PWR
QT
AWG
BR
C
CAP
— American Wire Gage
— Blower Relay
— Contactor
— Capacitor
COMP — Compressor Motor
CR — Combustion Relay
EQUIP — Equipment
FL — Fuse Link
FS
FU
GND
GVR
HS
HV
I
TRAN
—
—
—
—
—
—
—
Flame Sensor
Fuse
Ground
Gas Valve Relay
Hall Effect Sensor
High-Voltage
Transformer
Ignitor
— Integrated Control Motor
— Induced-Draft Motor
— Indoor-Fan Motor
— Integrated Gas Control
— Limit Switch
— Main Gas Valve
— National Electrical Code
— Outdoor-Fan Motor
— Power
— Quadruple Terminal
RS
SEC
—
—
Rollout Switch
Secondary
TRAN — Transformer
Field Splice
Terminal (Marked)
Terminal (Unmarked)
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or
Optional Wiring
To Indicate Common
Potential Only, Not to
Represent Wiring
Fig. 7 — Wiring Diagram, Units 589A048,060; 208/230-1-60
—11—
NOTES:
1. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent.
2. Use copper conductors only.
3. ICM board connections.
UNIT
589A
(VIO)
Aux,
Heat
Range
(BLU)
AC/HP
Size
1
TERMINAL NO.
2 3
CFM
1300 1400
1400 1600
1600
1750
4
1750
2000
(GRY)
AC/HP
Time
Delay
30 sec.
ON
1 min.
OFF
0 sec.
ON
0 min.
OFF
0 sec.
ON
30 sec.
OFF
0 sec.
ON
45 sec.
OFF
LEGEND
I
ICM
IDM
IFM
IGC
LS
MGV
NEC
OFM
PWR
QT
AWG
BR
C
CAP
—
—
—
—
American Wire Gage
Blower Relay
Contactor
Capacitor
COMP — Compressor Motor
CR — Combustion Relay
EQUIP — Equipment
FL
FS
FU
GND
GVR
HS
HV
TRAN
— Fuse Link
— Flame Sensor
— Fuse
— Ground
— Gas Valve Relay
— Hall Effect Sensor
— High-Voltage Transformer
— Ignitor
— Integrated Control Motor
— Induced-Draft Motor
— Indoor-Fan Motor
— Integrated Gas Control
— Limit Switch
— Main Gas Valve
— National Electrical Code
—
—
—
Outdoor-Fan Motor
Power
Quadruple Terminal
RS
RT
— Rollout Switch
— Red Terminal
SEC — Secondary
TRAN — Transformer
Field Splice
Terminal (Marked)
Terminal (Unmarked)
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or
Optional Wiring
To Indicate Common
Potential Only, Not to
Represent Wiring
Fig. 8 — Wiring Diagram, Units 589A048,060; 208/230-3-60
—12—
UNIT
657A
(VIO) Aux, Heat Range
(BLU) AC/HP Size
1
TERMINAL NO.
2 3
CFM
1300 1400 1600
1400 1600 1750
4
1750
2000
(GRY) AC/HP Time Delay
30 sec.
ON
1 min.
OFF
0 sec.
ON
0 sec.
OFF
0 sec.
ON
30 sec.
OFF
0 sec.
ON
45 sec.
OFF
NOTES:
1. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent.
2. Set heat anticipator at .6.
3. Use copper conductors only.
4. For ICM board connections, see table.
AWG
C
— American Wire Gage
— Contactor, Compressor
CAP — Capacitor
COMP — Compressor Motor
CTD
DB
DFT
DR
—
—
—
—
Defrost Board
Defrost Thermostat
Defrost Relay
LEGEND
SEC — Secondary
TRAN — Transformer
Compressor Time Delay
EQUIP — Equipment
FL — Fuse Link
FU
GND
—
—
Fuse
Ground
HR
ICM
IFM
IFO
—
—
—
—
Heater Relay (Strip Heat)
Integrated Control Motor
Indoor-Fan Motor
Indoor-Fan On
IP
LPS
— Internal Protector
— Low-Pressure Switch
MOCP — Maximum Overcurrent
Protection
NEC
OF
OFM
QT
RVS
—
—
—
—
—
National Electrical Code
Outdoor Fan
Outdoor-Fan Motor
Quadruple Terminal
Reversing Valve Solenoid
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or
Optional Wiring
To Indicate Common
Potential Only, Not to
Represent Wiring
Fig. 9 — Wiring Diagram, Units 657A048,060; 208/230-1-60
—13—
UNIT
657A
(VIO) Aux, Heat Range
(BLU) AC/HP Size
1
TERMINAL NO.
2 3
1300 1400
CFM
1600
1400 1600 1750
4
1750
2000
(GRY) AC/HP Time Delay
30 sec.
ON
1 min.
OFF
0 sec.
ON
0 sec.
OFF
0 sec.
ON
30 sec.
OFF
0 sec.
ON
45 sec.
OFF
LEGEND
NOTES:
1. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent.
2. Set heat anticipator at .6.
3. Use copper conductors only.
4. For ICM board connections, see table.
AWG
C
— American Wire Gage
— Contactor, Compressor
CAP — Capacitor
COMP — Compressor Motor
CTD — Compressor Time Delay
DB
DFT
— Defrost Board
— Defrost Thermostat
DR — Defrost Relay
EQUIP — Equipment
FL
FU
GND
HR
—
—
—
—
Fuse Link
Fuse
Ground
Heater Relay (Strip Heat)
ICM
IFM
IFO
IP
— Integrated Control Motor
— Indoor-Fan Motor
— Indoor-Fan On
— Internal Protector
LPS
LS
— Low-Pressure Switch
— Limit Switch
MOCP — Maximum Overcurrent
Protection
NEC
OFM
QT
RVS
— National Electrical Code
— Outdoor-Fan Motor
— Quadruple Terminal
— Reversing Valve Solenoid
Fig. 10 — Wiring Diagram, Units 657A048,060; 208/230-3-60
SEC — Secondary
TRAN — Transformer
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or
Optional Wiring
To Indicate Common
Potential Only, Not to
Represent Wiring
—14—
UNIT
557A
(VIO) Aux, Heat Range
(BLU) AC/HP Size
1
1300
1400
TERMINAL NO.
2 3
1400
CFM
1600
1600 1750
4
1750
2000
(GRY) AC/HP Time Delay
30 sec.
ON
1 min.
OFF
0 sec.
ON
0 sec.
OFF
0 sec.
ON
30 sec.
OFF
0 sec.
ON
45 sec.
OFF
LEGEND
AWG
C
—
—
American Wire Gage
Contactor, Compressor
CAP — Capacitor
COMP — Compressor Motor
EQUIP — Equipment
FL — Fuse Link
FU
GND
—
—
Fuse
Ground
HR
ICM
IFO
NEC
— Heater Relay (Strip Heat)
— Integrated Control Motor
— Indoor-Fan On
— National Electrical Code
OFM
QT
— Outdoor-Fan Motor
— Quadruple Terminal
SEC — Secondary
TRAN — Transformer NOTES:
1. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent.
2. Number(s) indicates the line location of contacts. A bracket over (2) numbers signifies single pole double throw contacts. An underlined number signifies a normally closed contact. Plain numbers (no lines), signify a normally open contact.
3. Set heat anticipator at .6 amp for first stage and .3 amp for second stage.
4. Use copper conductors only.
5. For ICM board connections, see table.
Field Splice
Marked Wire
Fig. 11 — Wiring Diagram, Units 557A048,060; 208/230-1-60
—15—
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or
Optional Wiring
To Indicate Common
Potential Only, Not to
Represent Wiring
UNIT
557A
(VIO) Aux, Heat Range
(BLU) AC/HP Size
1
1300
1400
TERMINAL NO.
2 3
1400
CFM
1600
1600 1750
4
1750
2000
(GRY) AC/HP Time Delay
30 sec.
ON
1 min.
OFF
0 sec.
ON
0 sec.
OFF
0 sec.
ON
30 sec.
OFF
0 sec.
ON
45 sec.
OFF
LEGEND
AWG
C
— American Wire Gage
— Contactor, Compressor
CAP — Capacitor
COMP — Compressor Motor
EQUIP — Equipment
FL
FU
—
—
Fuse Link
Fuse
GND
HR
ICM
IFM
IFO
NEC
OFM
QT
—
—
—
—
—
—
—
—
Ground
Heater Relay (Strip Heat)
Integrated Control Motor
Indoor-Fan Motor
Indoor-Fan On
National Electrical Code
Outdoor-Fan Motor
Quadruple Terminal
SEC — Secondary
TRAN — Transformer
NOTES:
1. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent.
2. Number(s) indicates the line location of contacts. A bracket over (2) numbers signifies single pole
Field Splice double throw contacts. An underlined number signifies a normally closed contact. Plain numbers
(no lines), signify a normally open contact.
3. Set heat anticipator at .6 amp for first stage and .3 amp for second stage.
4. Use copper conductors only.
5. For ICM board connections, see table.
Fig. 12 — Wiring Diagram, Units 557A048,060; 208/230-3-60
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional
Wiring
To Indicate Common
Potential Only, Not to Represent Wiring
Copyright 1997 Carrier Corporation CATALOG NO. BDP-3355-700
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement