advertisement
Important: Read and save these instructions. This guide to be left with equipment owner.
RH2+
Installation and
Operation Manual
Includes installation, operation maintenance and troubleshooting information for your RH2+ Electric
Steam humidifier
2568051-G| 13 JUL 2015
Thank you for choosing Nortec.
INSTALLATION DATE (MM/DD/YYYY)
MODEL #
SERIAL #
CYLINDER #
Proprietary Notice
This document and the information disclosed herein are proprietary data of Nortec Humidity Ltd. Neither this document nor the information contained herein shall be reproduced, used, or disclosed to others without the written authorization of Nortec Humidity Ltd., except to the extent required for installation or maintenance of recipient’s equipment.
Liability Notice
Nortec does not accept any liability for installations of humidity equipment installed by unqualified personnel or the use of parts/components/equipment that are not authorized or approved by Nortec.
Copyright Notice
Copyright 2015, Nortec Humidity Ltd. All rights reserved.
Contents
1 Introduction
2 Receiving and Unpacking
3 RH2 Models
4 Options and Accessories
5 Installation
6 Typical RH2 Installation
7 Location
8 Mounting with Keyholes
9 Plumbing
10 Steam Distributor
12 Steam Lines and Condensate
Return Instructions
16 Electrical
17 External Controls
22 Options and Accessories
23 Start Up
24 Installation Check
25 On/Off or Modulating Operation
26 Start Up Procedure
27 Nortec Digital Controls
28 RH2 Pre-Start Up Checklist
31 Operation
32 LED Status Lights
32 Selecting a Relative Humidity
Setpoint
33 Humidifier Components
34 Description of Components
35 Humidifier Schematic
36 How the Humidifier Works
38 Humidifier Configuration
40 Maintenance and
Servicing
41 Required Maintenance
45 Extended Shutdown
46 RH2 Maintenance Checklist
47 Troubleshooting
49 General Troubleshooting
51 RH2 Faults
53 RH2 Wiring Diagrams
54 Spare Parts
58 Warranty
Introduction
CAUTION: Servicing
Disconnect main power before any servicing.
The plumbing and electrical compartments contain high voltage components and wiring. Access should be limited to authorized personnel only.
During and following operation of the humidifier, the steam and components in contact with the steam such as the blower pack, steam lines, steam distributors, and condensate lines can become hot and can burn if touched.
Nortec does not accept any liability for installations of humidity equipment installed by unqualified personnel or the use of parts/components/equipment that are not authorized or approved by Nortec.
CAUTION: Electrical
All electrical work should be done according to local and national electrical code.
Electrical connection to be performed by a licensed electrician.
CAUTION: Plumbing
Plumbing to be performed by a licensed plumber.
Drain water from humidifier can be very hot. Do not drain to public sink.
All plumbing work should be done according to local plumbing code.
CAUTION: Installation
Do not mount on hot surfaces.
Do not mount in area where freezing can occur.
Do not mount on vibrating surface.
Do not mount on floor.
The RH2 produces steam at atmospheric pressure. No devices which could block steam output should be connected to the steam outlet.
Steam lines must be installed so that no restriction can produce backpressure in the humidifier.
Regardless of selecting on/off or modulating control method, Nortec humidifiers must have a closed circuit across its on/off security loop control terminal to operate. Nortec highly recommends the use of a high limit humidistat.
1 | Introduction
Receiving and Unpacking
1 Check packing slip to ensure ALL material has been delivered.
2 All material shortages are to be reported to Nortec within 48 hours from receipt of goods.
Nortec assumes no responsibility for any material shortages beyond this period.
3 Inspect shipping boxes for damage and note damages on shipping waybill accordingly.
4 After unpacking, inspect equipment for damage and if damage is found, notify the shipper promptly.
5 All Nortec products are shipped on a Free-On-Board (FOB) factory basis. Any and all damage, breakage or loss claims are to be made directly to the shipping company.
Before Installation
1 Ensure that available voltage and phase corresponds with humidifier voltage and phase as indicated on humidifier’s specification label.
2 Ensure that the dedicated external fuse disconnect is of sufficient size to handle the rated amps as indicated on the specification label. Refer to local codes.
3 Report any discrepancy immediately to the site engineer, if applicable.
4 Ensure sufficient clearances will be available as described in the Location section on pg 7.
5 Ensure steam lines can be routed to duct distributor or blower pack as described in Steam
Lines and Condensate Return Instructions on page 12.
MODEL:
XXXXXXXXXXXXXXXXXXXXXXXX
PHASE:
XXXX
HZ:
VOLTS 2:
VOLTS 3:
F.L.A:
XXXXX
F.L.A:
XXXXX
F.L.A:
XXXXX
DATE:
XXXXXXXXX
S/N:
KW:
KW:
KW:
XXXXXXX
XXXXXX
XXXXXX
XXXXXX
MADE IN CANADA
Figure 1: Specification Label Location
Introduction | 2
RH2 Models
The RH2 is the most advanced residential steam humidifier available and provides steady and reliable humidification for a home using the same proven cylinder technology as Nortec’s industrial electrode platform. The RH2 is available in 2 models: Duct, and Space. The duct model is designed for connection to a steam distributor installed in a supply air duct, or for connection to a remote blower pack. The space model is designed for applications where humidity is to be introduced directly into the conditioned environment. The two models can be differentiated by the grille in the humidifiers front cover, see Figure 2: RH2 Models.
.
Figure 2: RH2 Models
Table 1: RH2 Specifications
Model - Part No. Volts Capacity lb (kg)
KW Amps Phase Max Ext
Fuse
Standard
Cylinder
Net/Full
Weight lb (kg)
RH2 Space - 2560952
RH2 Duct - 2560953
110-120 4 (1.8)
208 6.9 (3.1)
220-240 8 (3.6)
110-120 5 (2.3)
208 8.7 (4.0)
220-240 10 (4.6)
1.5
2.6
3.0
1.9
3.3
3.8
12.7
15.9
1
1
20
20
202
202
16 / 22
(7.5 / 10.0)
15 / 21
(7.0 / 9.5)
3 | Introduction
Options and Accessories
Nortec provides a complete line of options and accessories for every humidification application.
The following options and accessories are available and may have been delivered with your RH2 humidifier. Refer to the installation instructions that came with the accessories for proper installation and operation.
Table 2: Options and Accessories
Option / Accessory
Steam Distributors
Application
Introducing steam into ventilation ducts.
Remote Blower Pack Introducing steam into conditioned environments.
Digital or Modulating Control Humidistats Controlling the output of the humidifier based on sensed RH.
Digital or Modulating High Limit
Humidistats
Preventing over-humidification in a duct by shutting down or throttling down the humidifier when RH approaches saturation.
Air Proving Switches Ensuring humidification only occurs when air is moving in a duct.
Introduction | 4
5 | Installation
Installation
6 Typical RH2 Installation
7 Location
8 Mounting with Keyholes
9 Plumbing
10 Steam Distributor
12 Steam and Condensate Returns
16 Electrical
17 External Controls
17 Control Wiring
17 Duct Humidification Control Location
18 Space Humidification Control Location
19 On/Off Control Wiring
20 Modulating Control Wiring
21 Fan Enable Wiring
21 RH2 Fan Control
21 Nortec On/Off Humidistat Fan Control
22 Options and Accessories
22 Remote Blower Pack
Typical RH2 Installation
2
Figure 3: Typical Humidifier Installation
Installation | 6
Location
Mount on a suitable wall or vertical surface. Do not sit the unit on the floor. Allow clearances required for plumbing and electrical connections. Clearance dimensions shown are for reference only and are the minimum required for maintenance of the humidifier. Consult local and national codes before final location and installation. Nortec does not accept responsibility for installation code violations.
Install only in areas with ambient temperature 41-104°F (5 – 40°C) relative humidity
5 - 95%.
When possible install below the steam distributor. Take care to provide proper steam line routing and proper condensate traps.
DO NOT locate the humidifier any further then absolutely necessary from the steam distributor location as net output will be reduced as a result of heat loss through the steam line.
When possible, mount the RH2 humidifier at a height convenient for servicing.
Note: Do not mount on hot surfaces, where freezing can occur, vibrating surface, or floor.
Overhead clearance for space models only, see table
5-95%
As Close as
Possible to Steam
Distributor
7 ft (2.1 m) min. Height for space models only.
Side clearance for space models only, see table
36 in. (92 cm) duct model m c
Additional front clearance for space models, see table
Mount Humidifier
Level
Humidifier Output lb (kg)
<4 (1.8)
6 (2.7)
8 (3.6)
24 in.(61 cm)
Min Height
Additional Clearance for Space Models Only
Side in. (cm) Overhead in. (cm) Front in. (cm)
12 (30)
16 (40)
18 (46)
12 (30)
18 (46)
18 (46)
36 (92)
42 (107)
48 (120)
Figure 4: Mounting Location / Clearance
7 | Installation
Mounting with Keyholes
1 The RH2 humidifier is wall mounted using a keyhole located on the back of the unit cabinetry.
2 Use #8 x 2 in. (5 cm) screws mounted into 2x4 studs or better. 2 screws are needed, one for hanging the unit and one for securing so it will not lift off the keyhole.
3 Install the top screw so that 1/4 in. (6 mm) is exposed. Raise the unit and place the screw head through the keyhole.
4 Make sure the unit is level and then insert and tighten the second screw through the bottom hole. Tighten the top screw. See Figure 5: Mounting With Keyholes.
Note: Use screws longer than 2” (5 cm) if drywall or other spacer is present.
Keyhole
Insert screw so that
1/4 in. (6 mm) exposed, hang unit, tighten screw.
2x4 or Other
Structural
Member
Hole
Install Second Screw after hanging humidifier
#8 x 2 in. (5 cm)
Wood Screws
Figure 5: Mounting With Keyholes
Installation | 8
Plumbing
1/8 in. NPT
Use 1/4 in. compression fitting to connect supply line to unit.
1.2 in. (30 mm). OD un-threaded outlet with factory supplied bent hose and clamp.
Always install a water shut-off valve.
Note:
1 Fill and drain lines
can also be routed
through opening in
back of cabinet.
2 Optional cover
2548313 Is available
to conceal plumbing
connections.
Air gap required. 2 1/2 in. to 7/8 in.
Copper reducer is ideal. (NORTEC option
P/N 2522172) Hose must not touch the bottom of the funnel.
Min. 7/8 in. OD drain line.
Keep as short as possible.
Slope down to floor drain or main drain.
Use 1/2 in. OD copper to within 4 ft (1.2 m) of humidifier
*Pipe and water shut-off valve not supplied by Nortec.
Figure 6: Water Supply and Drain Connection
All water supply and drain line connections should be installed in accordance with local plumbing codes.
Drain water is automatically cooled to 140°F (60°C). Drain material must be rated for this temperature.
Supply water should at 30 to 80 PSIG and be between 150-1200 Microsiemens
(330-670
S optimal range). Consult factory for water conditions outside of this range. Do not use reverse osmosis or de-ionized water. Supply water should be cold (34-68ºF/1-20ºC).
Install water shut off valve before humidifier to facilitate servicing.
The drain line should not end in a sink used frequently by personnel, or where plumbing codes prohibit it. Route to a floor drain or equivalent for safety reasons.
Ensure drain line is adequately sized to provide free and easy draining and that an air gap is installed as shown. A restricted drain can cause cylinder water to over concentrate and result in poor operation.
If a drain is not located near the humidifier use a condensate pump rated for hot drain water such as Nortec’s Part Number 1429527.
For humidifiers installed in some cities including the City of Los Angeles:
A city-approved spring-loaded double ball CHECK VALVE must be installed by contractor on the potable water inlet to the humidifier. Recommended valve manufacturer: Watts Regulator, phone number 508-688-1811, Size depending on supply line 1/4”, 3/8”, or 1/2” NPT inlet and outlet, Model #7.
9 | Installation
Steam Distributor
Steam generated by the RH2 Space is blown directly into the space by the integrated blower pack. The RH2 Duct requires a steam distributor, installed in the ventilation duct. The RH2
Duct can distribute steam into a ventilation duct using the following distributor options in
Table 3.
Table 3: RH2 Duct Steam Distributor Options
Nortec Part
Number
Option Description Notes
1581820 Nozzle Distributor Kit
Includes a steam distribution nozzle, steam hose, condensate hose, and installation hardware. See Figure 7.
2553708
Select to duct dimensions
RSD 10 Distributor Kit
ASD Duct Distributor
Includes a steam distributor, steam hose, condensate hose, and installation hardware. See Figure 8.
Used when duct width exceeds 12”. Refer to Distributor manual or
HELP software for selection.
Select to duct dimensions
Mini SAM-e
Used when short absorption is necessary. Refer to SAM-e manual or HELP software for selection.
2564776 RMBP for RH2 Duct
Remote Mounted Blower Pack, used with the RH2 Duct, adds steam directly into the space. The blower pack is installed remote to the humidifier.
Whichever method is used, the steam distributor should be installed as close as possible to the humidifier. Short steam distribution lines minimize condensate losses and the possibility of generating backpressure in the steam distribution line.
Installation | 10
Figure 7: RH2 Duct Nozzle Distributor Installation
11 | Installation
Figure 8: RH2 Duct RSD10 Distributor Installation
Steam Lines and Condensate Return Instructions
The following instructions must be followed for installation of steam lines for the RH2 Duct.
Failure to use recommended material and exceeding maximum recommended length in Table
4, or failure to follow any other steam line installation instructions will result in improper operation and could void the warranty.
Table 4: Recommended Steam Line Material for RH2 Duct
Steam Output Material*
Maximum
Steam Line
Length
Possible Losses
Voltage lbs/hr (kg/hr)
Nortec Steam
Hose
MED-L
Copper
Tube
Stainless
Steel
Tube ft (m) lbs/hr (kg/hr)
110-
120V
208V
220-
240V
5
8.7
10
(2.3)
(3.3)
(4.6)
Part Number
1328810
(7/8”)
3/4”
0.875 X
0.049W
7
10
12
(2)
(3)
(3.5)
0.5
1
1.5
(0.2)
(0.5)
(0.7)
110-
120V
208V
220-
240V
Not
Recommended
8.7
10
(3.3)
(4.6)
Oversized Steam Line (used for longer steam runs)**
Not
Recommended
1”
1.125 X
0.049W
12
24
Not Recommended
(3.5)
(7)
2
3
(0.9)
(1.4)
Note: * The use of steam line other than copper, stainless steel tube or Nortec supplied steam line will void the warranty and may adversely affect the operation of the humidifier.
** These diameters require a reducer at humidifier and steam distributor connection. Use Nortec part number 1115444 at humidifier to prevent backpressure caused by condensation collecting at the reduction.
To return condensate for RH2+, insert copper tube (supplied with equipment) half way into the condensate opening of the fill cup along with the spring clamp (supplied with equipment).
Insert the condensate hose into the condensate return hole at the top of the RH unit, and over the copper tube. Fasten in place with the spring clamp.
Figure 9: Condensate Return
Installation | 12
MAIN RULES FOR ATMOSPHERIC STEAM LINES
Steam lines must not have any restrictions which could result in back pressure.
Follow recommended materials, size and length, see tables.
Slope the steam lines.
Insulate with 1.0 in. (2.5 cm) pipe insulation
Trap condensate (Use full size ‘T’ for Traps)
Do not over tighten hose clamp at cylinder steam outlet. The maximum torque is 12 in-lbs.
Support steam line so weight is not on cylinder.
Condensate traps must be a minimum of 6 in. (15 cm) in height or duct static pressure + 2 in. (5 cm), whichever is greater.
Trapping by P-trap or pigtail. Support line as necessary to ensure it remains free of kinks.
Use Appropriate Slope Insulate Pipe
10 Degrees
Steam
Direc tion
1 ft (30 cm)
2 in.
(5 cm)
2 Degrees
0.5 in.
(12 mm)
1ft (30 cm)
Figure 10: Main Steam Line Requirements
1 in. (2.5 cm) pipe insulation
13 | Installation
12 in.(30 cm) min. Radius
2 in. (5 cm) min.
1 ft (30 cm)
1 ft (30 cm) min. before any bend
Connect Condensate
Hose to Fill Cup
Condensate
line
Support
Brackets
Condensate
Trap
Connect Steam
Hose to Cylinder
Min 12 in.
(30 cm) radius
Figure 11: Steam Distributor Above Humidifier (Hose)
Support Brackets
Hose will soften over time proper support
Is necessary
1 ft (30 cm) min. Before any bend
1 ft (30 cm) min.
Condensate
Trap
To Drain
Figure 12: Steam Distributor Below Humidifier (Hose)
Installation | 14
15 | Installation
12 in.
(30 cm) min.
radius
1ft (30 cm) min. before any bend
Support brackets
Hose will soften over time proper support
Is necessary
Obstruction
1 ft (30 cm)
2 in.
(5 cm) min.
1 ft (30 cm) min.
Use full size condensate tee at low point. Slope lines up to “T” and immediately after it.
To drain
To drain
Figure 13: Steam Distributor Below Humidifier With Obstruction (Hose)
Condensate trap not 12 in (30 cm) below distributor
No condensate trap at vertical transition
Steam line not sloped
Figure 14: Common Steam Line Errors
Electrical
Caution: Wiring to be performed by a licensed Electrician.
Figure 15: Primary Power Connection
Installation | 16
External Controls
Control Wiring
Controls are available from Nortec as accessories. If controls were not ordered with humidifier, they must be purchased or supplied by others. The following information is relevant to all controls, factory supplied or otherwise. For wiring use minimum 18 AWG and keep as short as possible.
The RH2 humidifier can be operated with either On/Off controls only or with On/Off controls and one modulating input. The modulating input can be from a duct high limit or humidity control humidistat. See Humidifier Configuration on page 38 to configure the RH2 for modulation.
Caution: Failure to wire the humidifier in accordance with the wiring instructions could cause permanent damage. Such errors will void the warranty.
Duct Humidification Control Location
Figure 16: Control Location (Duct Humidification)
Duct Humidification Control Location
1 Air Proving Switch o Locate upstream so that it can sense air flow or lack of it.
2 Duct High Limit – Can be modulating or On/Off humidistat. o Locate at least 10 feet downstream from steam distributor or far enough that under normal conditions steam is fully absorbed.
3 Humidity Control - Can be Modulating or On/Off humidistat o Can be located either in return air duct (preferred) or in room being humidified. o Avoid placing near discharge diffuser of humidified air. o Mount in area representative of room humidity (draft, doorways, sunlight, or overhang such as a shelf can affect reading).
4 Outdoor Temperature Sensor (not shown) o Mount outside in area representing air temperature.
17 | Installation
Space Humidification Control Location
These instructions apply to the RH2 Space and the RH2 Duct with Remote Blower Pack.
Figure 17: Control Location (In-Space Humidification)
Space Humidification
1 Humidity Control – Can be Modulating or On/Off humidistat o Locate in room being humidified but not in discharge zone of blower pack. o Mount in area representative of room humidity (draft, doorways, sunlight, or overhang such as a shelf can affect reading).
2 High Limit Humidistat (not shown) o Install an On/Off High Limit Humidistat in an area representative of room humidity.
3 Outdoor Temperature Sensor (not shown) o Mount outside in area representing air temperature.
Note: Regardless of selecting on/off or modulating control method,
Nortec humidifiers must have a closed circuit across its on/off security loop control terminal to operate. Nortec highly recommends the use of a high limit humidistat and an air proving switch in series for this function.
Installation | 18
On/Off Control Wiring
Figure 18: On/Off Controls
19 | Installation
Figure 19: Digital On/Off Humidistat
Modulating Control Wiring
Figure 20: Modulating Controls
Figure 21: Modulating Control Wiring
Installation | 20
Fan Enable Wiring
When distributing steam into a duct, there can be a call for humidity when there is no air flow.
Either the RH2 or the Nortec On/Off digital humidistat can be used to enable a fan on a call for humidity. Wiring below is for a typical furnace installation. Consult the air handler’s installation manual for exact wiring instructions on how to enable the fan.
RH2 Fan Control
The RH2 can be used to turn on a furnace fan where there is a demand for humidity without a call for heat.
Fan Enable
Figure 22: RH2 Fan Enable Wiring
*Humidifier will not start producing steam until fan security loop is closed.
Nortec On/Off Humidistat Fan Control
Nortec digital On/Off humdistats include a second dry set of points to enable a fan where there is a call for humidity without a call for heat.
21 | Installation
Figure 23: Nortec Digital On/Off Humidistat Fan Enable
Options and Accessories
Remote Blower Pack
A remote blower pack is available for the RH2 Duct for applications where steam for humidification must be introduced directly into the conditioned environment but the humidifier must be installed in a different location.
For instructions on installing the remote blower pack, refer to the installation instructions supplied with it.
The steam line instructions in this manual are also applicable to remote mounted blower packs except the slope must be larger because the blower pack does not have a separate condensate line and the maximum allowable steam line length is 4 ft (1.2 m)
Figure 24: Remote Mounted Blower Pack
Note:
The blower pack requires additional clearance see the instructions that came with it.
The steam line slope for the blower pack is 4 in. / 1 ft (10 cm / 30 cm).
Installation | 22
23 | Start Up
Start Up
24 Installation Check
25 On/Off or Modulating Operation
26 Start Up Procedure
27 Nortec Digital Controls
27 Modulating Control
27 On/Off Control
28 RH2 Pre-Start Up Checklist
Installation Check
Before turning on power to the RH2 inspect the installation to ensure that it was carried out correctly. Refer to RH2 Pre-Start Up Checklist on page 28, and to the Installation chapter.
Figure 25: Installation Check
Start Up | 24
Caution: Do not leave the On/Off/Drain switch in the drain position for extended periods of time. The drain valve solenoid may heat up and result in damage to the valve and its wiring.
On/Off or Modulating Operation
From the factory the RH2 is configured to operate as an On/Off humidifier. It will run when 24
VAC from terminal 1 is fed back into terminal 2 through an On/Off humidistat and other security devices in series. See On/Off or Modulating Control (J10) on page 39 for instructions on configuring the RH2 to operate as a modulating humidifier.
25 | Start Up
Start Up Procedure
1 Examine the humidifier and installation for damage and/or improper installation.
2 Ensure the cylinder is properly seated in the drain valve and that the electrode plugs are pushed all the way down on the cylinder pins.
3 Ensure that the front cover is in place and secured with its retaining screws.
4 Open the supply water shut off valve.
5 Turn on the main power using the installed disconnect.
Warning: Damaged Units or improperly installed units must not be operated. Damaged or improperly installed units may present a danger to persons and property.
6 Turn the On/Off switch on the front of the humidifier to On.
The humidifier will perform a self-diagnostic sequence during which the LED’s and internal components will be momentarily activated. See Figure 27 on page 32 for an explanation of
LED colors and sequences.
If an error is detected during the self-diagnostic sequence the humidifier will not start. The yellow status LED will flash in sequence to indicate the detected fault. See section RH2
Faults on page 51 for information on diagnosing and correcting faults.
After the system test the humidifier is in normal operation mode.
7 Check and adjust the control setpoint on the control and high limit humidistat.
8 When the external humidistat generates a demand for humidity and the security loop is closed the green humidifying LED on the front of the humidifier will light up, the power relay on the control board will engage, the fill valve will activate (after a delay) and the cylinder will slowly fill with water.
Note: While the cylinder is filling with water there should be no water flowing down the drain. If water is flowing down the drain it can indicate excessive backpressure or a leaking drain valve. See chapter on Troubleshooting.
9 If the fan enable relay is used, the green LED will continue to flash until the air proving closes. Once the air closes, the flashing green LED will become solid and the humidifier will start steam production as described in step 8.
10 It can take 5 – 10 minutes for the water to be heated up by the submerged electrodes and for steam to be produced.
Note: If operated on low conductivity water it may take several hours for the RH2 to reach full output capacity. This is normal. During this time the humidifier will not perform any drains and the conductivity of the water in the cylinder will increase.
Start Up | 26
Nortec Digital Controls
Nortec provides optional On/Off and Modulating digital controls. Figure 26 show the function and meaning of the Digital Control’s display and buttons. All controls are available either wall mounted or with a remote sensor for duct mounting.
Humidity (RH %)
Output signal is shown on modulating controller proportional to the demand.
Indicates the humidistat is on.
A half moon indicates it is off.
State of On/Off humidistat
Snowflake indicates the setpoint is being overridden by outdoor temperature.
Setpoint (RH%)
Power button turns
off the humidiistat if
pressed for 2 seconds
Option button accesses sensor calibration.
See troubleshooting
Increase / Decrease Setpoint
Figure 26: Modulating and On/Off Digital Control Operation
Modulating Control
The modulating controls use a PI control algorithm to transmit a 0-10V control signal to the humidifier. Adjust the setpoint to the desired setting by using the up/down arrow buttons on the controller.
On/Off Control
The On/Off controls use a PI control algorithm to open and close a relay that opens and closes the humidifier’s On/Off loop. Adjust the setpoint to the desired setting by using the up/down arrow buttons on the controller.
Note: It is possible to field calibrate Nortec digital controls if the displayed humidity is found to be different than a known trusted source. See chapter on Troubleshooting.
27 | Start Up
RH2 Pre-Start Up Checklist
Unit Serial #: _________________ No. of humidifiers: _______ Tag: _______________
Unit type: _______ __________ Voltage: ________V/_____ph
Cylinder type: Customer/Job:
WATER QUALITY:
Well water City water Softened water
Address:
HUMIDIFIER MOUNTING:
Level
STEAM LINE(S):
Material
Slope up (min 2 in/ft)
Low point condensate traps
Minimum 1 inch insulation
CONDENSATE LINE(S):
P Trap min 6 in or duct press + 2in
• Front Clearance 36 in.
• Diameter / Size
• Slope down (min 0.500 in/ft)
• No hose kinks / Restrictions
• P Trap min 12 in drop
WATER LINE:
1/2 in to within 4ft of unit
Cold water source (34-68ºF/1-20ºC)
DRAIN LINE:
Air gap within 3 ft of the unit
• Water pressure: 30-80 psig
• Diameter / Size
CYLINDER:
Seated in drain valve yes no
Torque for gear clamp of cylinder steam exit to steam line (max 12 in•lbs): ______________
WIRING:
Wiring connections and connectors secured yes no
CONTROLS:
On / Off / Security loop devices working correctly yes no
Jumper J10 set to
Modulating (removed)
Or
On/Off (installed)
Control Location
High Limit Location
POWER:
Voltage, amp, fuse per Spec Label:
Disconnect switch located close to humidifier
Panel Number
Inspected by: yes no yes no
Date of inspection: ______/_______/______
Company:
Start Up | 28
RH2 Start Up Checklist
Unit Serial #: _________________ No. of humidifiers: _______ Tag: _______________
Unit type: _______ __________ Voltage: ________V/______ph
Cylinder Type: Customer/Job:
PRELIMINARY:
Pre-start-up checklist completed?
Address:
yes no
If no, perform Pre-Start-up Checklist before starting humidifier.
START-UP PROCEDURE:
The prerequisites for the humidifier filling and contactor pulling in to make steam are as follows:
Front cover in place and secured with screws
yes
no
Water supply valve opened
Mains disconnect switched on
Turn On/Off switch on
On/Off security loop (Terminal 1 and 2) closed.
Fan security (Terminal 1 and 8) closed
yes
yes
yes
yes
yes
no
no
no
no
no
CONTROLS:
Installed controls match configuration
Control Setpoint: or
> 3 VDC on terminal 4 (Modulating Humidistat)
Terminal 1 and 2 closed (On/Off Humidistat) yes yes yes
no
High Limit Setpoint:
no
no
The Humidifier will undergo a selftest when the power is turned on activating the LED’s and other internal components.
If the above listed prerequisites are fulfilled the humidifier will start filling the cylinder and begin normal operation.
Note: Most water does not contain enough conductivity for full boil on initial start-up. Units will need to concentrate the water over a time period (hours to days).
REMARKS:
Started by:
Company:
Date of Start Up: _______/_______/______
29 | Start Up
Start Up | 30
31 | Operation
Operation
32 LED Status Lights
32 Selecting a Relative Humidity Setpoint
33 Humidifier Components
34 Description of Components
35 Humidifier Schematic
36 How the Humidifier Works
36 Steam Generation
36 Drains
36 Steam Distribution
37 Steam Line
37 Condensate Return
38 Humidifier Configuration
LED Status Lights
The RH2 user interface includes 2 LED’s which provide information about the humidifier status.
Figure 27: LED Status Indicator Lights
Yellow LED Steady On
When the yellow LED is steady on (not flashing) it indicates that the high water sensor has interrupted filling of the cylinder. The LED is on for information only and unless it persists for an extended period of time, it does not require any action.
Selecting a Relative Humidity Setpoint
The optimum humidity setpoint depends on the reasons that a space is being humidified. The
“ASHRAE Handbook HVAC Applications” recommends specific design relative humidity for specific applications. See also Nortec publication “When You Need Humidity” (Form 124A) for more information on humidity settings.
Health and Comfort - The benefit of humidity is most pronounced for health and comfort in the
40-60% range. A humidity setting of 45-50% is recommended for this purpose to prevent over humidifying.
Temperature Setback - In cold climates it is often necessary to reduce the humidity level in a conditioned environment to prevent build-up of condensation on the inside of exterior walls, windows, and trim. It is highly recommended that the temperature setback function of the
Nortec Digital controls be used under these conditions to prevent damage from condensation.
The digital control with an outdoor temperature sensor installed will automatically setback the humidity setpoint to correspond with outdoor temperature.
Duct High Limit – The duct high limit is intended to prevent saturation and wetting in duct work at high load conditions. Nortec recommends a setting of 85% for the duct high limit. It may be necessary to reduce this setting if the duct work is very cold or in contact with exterior cold surfaces.
Operation| 32
Humidifier Components
Condensate Return
Fill Cup
High Water Sensor
Plug
Steam Outlet
Blowerpack
Cylinder Plug
Cylinder
Fill Valve
High Voltage
Terminal Block
Transformer
Power Relay
Control Board
Control Terminal
Strip
On/Off/Drain Switch
33 | Operation
Drain Canal Drain Valve
Figure 28: RH2 Humidifier Components
Description of Components
Table 5: Humidifier Components
Component
Blowerpack
Function of Component
Disperses steam generated by the humidifier directly into a space being humidified. Consists of a steam distributor, fan, power supply, and mounting bracket.
Condensate Return Provides a connection to return condensate to humidifier.
Control Terminal
Strip
Terminal strip for connecting external controls to humidifier and interfacing with other equipment.
Cylinder Plug
Power connectors to electrodes in cylinder.
Cylinder
Drain Canal
Drain Valve
Holds electrodes in water. Current between electrodes generates heat used to generate steam.
Combines cylinder drain water and fill cup overflow into a single drain outlet.
Drains water from humidifier.
Control Board
Fill Cup
Controls all functions of the humidifier operation and provides input and output connections to humidifier components.
Provides an air gap for backflow prevention.
Fill Valve
Controls flow of water into humidifier.
High Voltage
Terminal Block
Primary power connection from remote disconnect to humidifier.
High Water sensor
Plug
Used to detect max water level in cylinder.
On/Off/Drain Switch Turns power on/off to humidifier controller and drains the cylinder for servicing. Note: Turn off humidifier disconnect to shut off primary power to the humidifier.
Power Relay
Steam Outlet
Transformer
Turns on/off power to cylinder electrodes based on a signal from the humidifier’s controller (mounted on control board).
Connect to steam line with steam hose (shown with steam hose to blower pack).
Steps primary voltage down to 24 VAC for the controller and internal components such as the fill valve and drain valve.
Operation| 34
Humidifier Schematic
35 | Operation
Figure 29: Humidifier Schematic
How the Humidifier Works
The RH2 is an atmospheric steam generator that uses heat generated by electrical current flowing between submerged electrodes to generate steam. The RH2 is designed for air humidification via steam distributor or blower pack.
Steam Generation
Once the unit receives a demand signal and the safety loop between terminal 1 and 2 is closed, the humidifier closes the contactor and measures the electrical current.
If the demand is lower than the actual output the inlet valve is kept closed and output is reduced by letting the water level in the cylinder decrease by evaporation.
If demand is higher than the actual output, after a brief delay the fill valve is activated and water flows into the fill cup. Water from the fill cup flows into the bottom of the cylinder through a hose connected to the drain valve housing.
Note: The cylinder is gravity fed from the fill cup. If backpressure from the steam line is too high it will cause water to back up in the fill cup and flow down the overflow line to the drain.
As soon as the water in the cylinder comes in contact with the energized electrodes, current flows through the water. The resistance of the water to the electrical charge generates heat and in turn steam. The electrical current (and steam output) increases as the level of water increases, as more of the electrode becomes submerged. The unit continues to fill until the current matches demand or the high water sensor detects a high water level.
The RH2 repeats the fill and boil down cycle repeatedly to match output to demand.
Over time minerals in the water will adhere to the cylinder electrodes. The humidifier will automatically fill to a higher water level to maintain full capacity during the life of the cylinder. Eventually because of scale formation it will no longer be possible for the humidifier to reach its full capacity. The RH2 software monitors this condition and, when detected, will stop operating and flash the yellow LED in a repeating sequence of 4 flashes.
Drains
As steam is produced minerals are left behind, increasing the conductivity of the water. The
RH2 patented auto adaptive cycle will monitor the water conductivity and perform drains to maintain the water at optimal conductivity for peak performance.
The auto adaptive cycle ensures cylinder life is maximized. It does this by keeping the tightest control and most efficient use of water during the entire cylinder life.
Steam Distribution
Steam generated by the humidifier may be introduced into the air in several different ways. The most common method for adding the steam into the air is to mount a steam distributor tube in a supply air duct as shown in Figure 29: Humidifier Schematic. For introducing steam directly into a room humidifier, built-in or remote mounted blower packs may be used see Figure 30:
Remote Blower Pack on page 37.
Operation| 36
Steam Line
The steam line between the cylinder steam outlet and the distributor serves two purposes: it is used as a conduit to transfer the atmospheric steam from the humidifier to the distributor, as well as providing a means to remove condensate. See steam distributor on page 10 for information on selecting steam lines.
Condensate Return
Whenever steam is distributed condensate is formed in the distribution system. Insulating steam lines is one important way to reduce the amount of condensate formed. Steam lines are sloped so that condensate does not collect in the lines and create a restriction to steam flow.
The condensate must be collected and removed from the system so that it does not build up and leak into the duct (or room if blower pack is used). Condensate can be returned to the RH2 fill cup to reduce water waste or can be fed to drain.
37 | Operation
Figure 30: Remote Blower Pack
Humidifier Configuration
The RH2 is factory configured to operate under most conditions without the need for any changes to its configuration. If required, several settings can be made using jumpers on the
RH2’s control board. The output of the RH2 can also be reduced by using a potentiometer on the RH2’s control board. See Figure 31: RH2 Control Board Jumpers for location of jumpers and the capacity adjustment potentiometer.
Note: Nortec recommends not making any configuration changes unless they are required and that any changes to the RH2 settings be performed by a qualified technician.
Figure 31: RH2 Control Board Jumpers
Caution: Never adjust jumpers other than those listed in this section. Other jumpers are factory set and must not be changed.
Capacity Adjustment
The capacity adjustment potentiometer can adjust the capacity of the humidifier between 100% and 30% of its rated output. (Factory setting = 100% output).
30% 100%
Figure 32: Capacity Potentiometer Adjustment
Operation| 38
On/Off or Modulating Control (J10)
The RH2 output can be controlled by either an On/Off or a modulating humidistat. To set the
RH2 to operate with a modulating humidistat, remove Jumper J10. (Factory setting = jumper
Installed , On/Off operation)
J10 Removed– Modulating operation, the controller monitors the demand signal on terminal point 4 of the control terminal strip and adjusts humidifier output to match it.
J10 Installed - The RH2 is configured for On/Off operation. The controller will ignore any modulating signals even if they are connected.
Modulation Offset (J13)
The RH2 controller can be configured to work with a modulating humidistat with 4-20 mA or 2-
10 VDC output. Modulation offset can be configured with jumper 13. (Factory setting = Jumper
Removed, 0-10 VDC or 0-20 mA control signal)
J13 Removed – Controller is configured for a 0-10 VDC or 0-20 mA control signal.
J13 Installed – Controller is configured for a 2-10 VDC or 4-20 mA control signal.
For mA control a 500
register is required between terminals 3 and 4 on the low voltage control terminal.
Table 6: Control Jumper Configuration
Resulting Control
On/Off
Modulating 0-10 VDC or 0-20 mA
Modulating 2-10 VDC or 4-20 mA
J10
Installed
Removed
Removed
J13
No Affect
Removed
Installed
Ground Fault Interrupt (GFI) (J15)
Ground current leakage can occur when the humidifier performs drains. With jumper J15 the
RH2 can be configured to turn off the power to the electrodes whenever a drain takes place.
J15 Removed – The power relay is on during drains to control cylinder water concentration.
J15 Installed – The power relay is turned off during drains to control cylinder water concentration.
39 | Operation
Maintenance and Servicing
41 Required Maintenance
41 Cylinder Spent Fault
41 Replacement Cylinder
42 Removing the Cylinder
43 Drain Valve Cleaning
44 Installing the New Cylinder
45 Extended Shutdown
45 Starting After Extended Shutdown
46 RH2 Maintenance Checklist
Operation| 40
Required Maintenance
The RH2 humidifier has been designed to require very little maintenance. Regular maintenance consists of checking the humidifier to ensure it is in good condition, replacing the cylinder when the software advises that the cylinder is spent and cleaning out the drain valve whenever the cylinder is replaced.
Cylinder Spent Fault
When the cylinder is spent the RH2 will stop operating and the yellow LED will flash in a repeating pattern of 4 flashes. See Table 8: Troubleshooting RH2 Faults on page 51 for more information on other flash sequences. At this time the cylinder must be replaced.
The steam cylinder is disposable and must be replaced at end of cylinder life. Cylinder life is dependent on water supply conditions and humidifier usage.
Caution: Failure to replace the cylinder at the end of cylinder life will result in improper operation and may result in damage to the humidifier. Nortec is not responsible for any damages resulting from, or attributed to, the failure to replace a spent cylinder
(see Manufacturer’s Warranty).
Note: Nortec recommends keeping a replacement cylinder in stock throughout the humidification season. This will prevent possible downtime when the humidifier reports cylinder end of life.
Replacement Cylinder
The label on the existing cylinder identifies the cylinder type in its top left corner. When ordering a cylinder always quote the three or five digit model number on the label, the humidifier’s serial number and the humidifiers voltage. Serial number and voltage are located on the specification label on the left side of the humidifier.
41 | Maintenance and Servicing
Figure 33: RH2 Cylinder
Removing the Cylinder
Warning
Disconnect main power at the external disconnect before any servicing.
The inside of the humidifier cabinet contains high voltage components and wiring.
Access should be limited to authorized personnel.
1 Drain the existing cylinder by switching the On/Off/Drain switch to the Drain position. Let the humidifier drain until no more water is flowing out to drain (usually not more than 10 minutes).
2 Turn the humidifier On/Off/Drain switch to off.
3 Close supply water shut off valve.
4 Turn off power to the humidifier with the external disconnect.
5 Remove the two screws securing the front cover.
6 Remove the cylinder plugs from the cylinder pins by pulling vertically.
7 Using a flat screwdriver loosen the hose clamp where the hose is connected to the cylinder.
8 Tip the top of the cylinder forward to pivot it out of the steam hose. When free of steam hose lift the cylinder out.
Cylinder Plug lift vertically
Cylinder
Hose Clamp
Cover Screws
Tilt cylinder forward to clear hose and then lift from drain valve.
On/Off/Drain Switch
Tilt cover forward to .
remove.
Figure 34: Cylinder Removal
Maintenance and Servicing | 42
Drain Valve Cleaning
Always clean the drain valve before installing a new cylinder. Scale from the spent cylinder may have fallen into the drain valve and could prevent its proper operation. To properly clean the drain valve it must be removed and disassembled.
Note: Be sure to reattach the green ground wire to reduce the risk of electrical shock.
1 Disconnect spade terminals from the drain valve.
2 Remove the screw holding the green ground wire and the two screws holding the valve to the drain pan.
3 Squeeze the tabs of the spring clamp holding the hose to the drain valve and slide it up the hose. Pull hose from drain valve. Lift the drain valve from the drain pan.
4 Unsnap red coil cap on solenoid and remove the solenoid from the valve.
5 Loosen brass nut holding actuator to plastic housing with a wrench and disassemble actuator.
6 Clean actuator components and valve housing (inlet port, outlet port, and cylinder port). Put new o-ring that was supplied with new cylinder into valve.
7 Reassemble actuator making sure tapered end of spring is oriented as shown in Figure 36.
Tighten brass nut 1/4 turn past hand tight.
8 Clean out end of hose and reattach to valve. Slide hose clamp back in place and place valve into drain pan.
9 Secure valve with 2 screws and attach green ground wire to solenoid.
43 | Maintenance and Servicing
Figure 35: Drain Valve
Plunger
Spring
(Note Orientation)
Sleeve and
Solenoid
Figure 36: Drain Valve Actuator Assembly
Installing the New Cylinder
CAUTION: Make sure the new cylinder is the same model as the one that was removed.
Model number is on top left corner of cylinder label.
1 Insert cylinder into drain valve. Tilt cylinder forward and fit end of steam hose to steam outlet. Tip cylinder back into place.
2 Tighten hose clamp being careful not to over tighten and crush the plastic cylinder steam outlet.
3 Attach color-coded cylinder plugs to the corresponding color-coded cylinder pin. Push down completely. Connect high water sensor plug. Spring-loaded plugs should fit snuggly onto the cylinder pin. Replace if they are loose or damaged.
4 Replace the humidifier cover and secure with two screws.
5 Turn on power to humidifier with the external disconnect.
6 Open supply water shut off valve.
7 Turn the humidifier On/Off /Drain switch to On.
Maintenance and Servicing | 44
Extended Shutdown
Should it be required to disconnect power to the humidifier for a period of extended shut-down, always drain the cylinder first.
1 Switch the On/Off/Drain Switch to the Drain position.
2 Wait until the humidifier is completely drained (usually takes less than 10 minutes).
3 Turn the On/Off /Drain switch to the off position.
4 Shut off power to the humidifier with the external disconnect.
5 Close the supply water shut-off valve.
Note: As long as the RH2 is powered, it will automatically drain the cylinder when there has not been a call for humidity for an extended period of time. This feature will reduce or prevent the possibility of corrosion of the electrodes and the accumulation of algae and bacteria growing in the cylinder. The cylinder will remain empty until there is a call for humidity at which time the fill valve will open and refill the cylinder.
The unit will go through its normal process for optimum operation.
Starting After Extended Shutdown
1 Check to see the humidifier has not been damaged and the installation has not been altered. Refer to the Chapter on Start Up.
2 Turn on the power to the humidifier with the external disconnect.
3 Turn the On/Off/ Drain switch to the Drain position.
4 Wait until there is no water flowing to drain. It usually takes less than 10 minutes.
5 Follow the start up procedure in the chapter on Start Up.
45 | Maintenance and Servicing
RH2 Maintenance Checklist
Model #: _________________
Serial #: _________________ Tag: ________
Cylinder #:
CHECK CYLINDER
Cylinder spent), yellow LED flashing 4 times in sequence.
(If Yellow LED is On and cylinder is not new then cylinder will have to be replaced soon.)
REPLACE CYLINDER
Cylinder drained.
Disconnect open, On/Off/Drain switch off, water shut off valve closed, cover removed.
Cylinder removed
Drain valve removed / cleaned / new O-Ring
Drain valve installed / ground wire attached.
New Cylinder Installed
New cylinder model #
(Should be same as removed cylinder)
Cylinder plug colors match cylinder dots.
Cylinder plugs snug and in good condition.
High Water Sensor plug snug and in good condition.
Cover replaced, water shut off valve open, On/Off /Drain switch On, Disconnect Closed
SYSTEM CHECK
Yellow Led flashing? No
Yes
Flash Sequence?
(See Troubleshooting Chapter for actions if yellow LED is flashing
)
Cylinder plugs snug and in good condition.
Electrical wiring not loose and in good condition,
Steam hoses and steam lines in good condition / No kinks in hose,
No Signs of water leaking around humidifier, steam line, condensate returns,
Inspected by:
Date of inspection: _______/_______/______
Company:
Maintenance and Servicing | 46
47 | Troubleshooting
Troubleshooting
48 Organization of Troubleshooting Chapter
48 Troubleshooting Requirements
49 General Troubleshooting
49 Humidifier
50 Steam Distributors
50 Blower Pack
50 Digital Humidistat
51 RH2 Faults
51 LED Flash Sequence
51 Clearing a Fault
53 RH2 Wiring Diagram
54 Exploded View and Spare Parts List
58 Warranty
Organization of Troubleshooting Chapter
The troubleshooting chapter is broken down into 2 sections.
General Troubleshooting Deals with troubleshooting incorrect humidifier operation, steam line and plumbing issues without any control software faults.
Humidifier Warnings and Faults Deals with faults that are generated by the humidifier control software.
CAUTION: Be aware, when troubleshooting, that the humidifier is powered by high voltage and familiarity with both good practices and wiring of the humidifier is recommended.
Any troubleshooting that requires opening the cabinet should be done by qualified personnel.
NOTE: Most humidifier faults are not caused by faulty equipment but rather by improper installation. A complete fault diagnosis always involves a thorough examination of the entire system. Often, the steam hose connection has not been properly executed, or the fault lies with the humidity control system.
Troubleshooting Requirements
Ensure the installation meets the installation requirements outlined in the Installation
Chapter of this manual.
Familiarize yourself with the operation of the humidifier by reading the Operation Chapter of this manual.
Wiring diagram for specific for your humidifier is installed on the inside of the humidifier door. A generic copy of the RH2 wiring diagram is also included at the end of this chapter for reference purposes.
When contacting your local representative or Nortec for troubleshooting assistance, please ensure the serial number has been obtained for reference purposes.
Troubleshooting| 48
General Troubleshooting
The following section provides general guidelines for troubleshooting the RH2 humidifier and auxiliary components. For detailed troubleshooting information refer to the manuals that were provided with the auxiliary equipment and to Table 8: Troubleshooting RH2 Faults after in this chapter.
Table 7: General Troubleshooting
Symptom
Nothing happens when On/Off switch is turned on.
1 Fuse blown
Cause Corrective Action(s)
1 Check inline fuse between transformer and control board.
Humidifier will not humidify or not reaching RH2 setpoint
Humidifier has faulted and yellow LED is flashing
2 Incorrect Voltage
2 Check voltage against spec label and correct.
3 Replace the transformer 3 Step Down Transformer not outputting 24VAC
4 Incorrect primary power jumper 4 Check that jumper on high voltage terminal block is connected between P and terminal corresponding to supply voltage.
1 Safety loop open
2 No demand signal
3 Not configured correctly for
On/Off or modulating control
1a Check if there is 24 VAC at terminal 2.
1b Check wiring and operation of On/Off devices connected to terminal 1 and 2.
1c Check jumper is installed in air proving safety loop, terminal 1 and 8.
2 Check voltage between terminal 3 and
4. For demand configuration 35% of full-scale signal must be present for humidifier to start.
3 Check that J10 on control board is removed for modulating control and installed for On/Off control.
4 Capacity has been manually limited
5 Low conductivity water
6 Incorrect configuration
(Modulating or On/OFF)
4 Check Manual Capacity adjustment potentiometer. Clockwise increases capacity.
5 Check if yellow LED is on. If operated on low conductivity water it may take several hours for the RH2 to reach full output capacity. This is normal. During this time the humidifier will not perform any drains and the conductivity of the water in the cylinder will increase.
6 Check J10 on control board, remove if a modulating humidistat is being used.
7 No airflow in duct
1 Software has detected an abnormal condition
7 Check that humidifier fan enable
(terminals 19-20) are properly wired to furnace. Check air proving wired to terminal 8.
1 Refer to Table 8: Troubleshooting RH2
Faults.
49 | Troubleshooting
Steam Distributors
Symptom
Distributor spitting out water
Condensation in duct
3 Condensate line not sloped sufficiently
4 Trap blocked
Cause
1 Distributor not level
2 “P” Trap too close to distributor
5 Steam line not insulated
6 Incorrect steam line installation
1 Installation clearances not observed
2 Design conditions changed
3 High limit not functioning
Corrective Action(s)
1 Use support at end of distributor to ensure it is level.
2 “P” Trap must be a minimum of 12 in
(30 cm) below the distributor to ensure flow. Relocate if required.
3 Sufficient slope to ensure flow is required. Reinstall if required.
4 Check that water flows through trap.
Clear out if blocked.
5 If steam line is long, condensate build up could overload distributor condensate port. Insulate line to improve efficiency and install additional condensate traps as required.
6 Check that steam line has been installed with condensate traps and slope per installation instructions on page 12.
1 Refer to distributor installation manual for required clearances. Relocate distributor if required.
2 Check supply air temperature and humidity to determine if conditions have changed.
3 Check setting and operation of high limit. Replace if defective.
Blower Pack
Symptom
Blower not operating
Cause
1 No power to blower pack
Corrective Action(s)
1a Check power connection to blower pack.
1b Ensure unit is humidifying. The blower will not operate if the humidifier is not generating steam.
Digital Humidistat
Symptom Cause
Humidistat Reading incorrectly 1 Sensor out of calibration
Corrective Action(s)
1 Check reading against known reliable instrument. If out of calibration it can be field calibrated ±10%. Refer to humidistat documentation for calibration instructions.
Troubleshooting| 50
RH2 Faults
The self-diagnostic system built into the RH2 is continually monitoring the operation of the humidifier. When an abnormal condition occurs that cannot be self-corrected by the software the RH2 will turn off power to the cylinder, drain the cylinder, and annunciate the fault using the yellow status LED.
LED Flash Sequence
To differentiate between different fault conditions the yellow LED is flashed in different sequences. Table 8 lists the fault sequences that can be displayed, their meaning, possible cause and suggested corrective actions.
Clearing a Fault
Check the flash sequence against the list of fault messages and take any necessary actions to correct the cause(s) as outlined in Table 8: Troubleshooting RH2 Faults.
Power cycle the humidifier with the On/Off switch waiting 10 seconds between turning it off and on. If an externally powered 0-10V controller is used, it must be turned off prior to clearing the fault.
Table 8: Troubleshooting RH2 Faults
Yellow LED System Detected
1 flash
Excess Current
Current has exceeded
130% of max
Cause Corrective Action(s)
1 Drain blocked water over concentrated
2 Drain solenoid not energized, water over concentrated
1 Clean the drain line
2 Check and correct wiring to drain valve.
3 Replace the fill valve 3 Filling too fast, fill valve damaged and leaking
4 Filling too fast, wrong fill valve 4 Check for correct fill valve in parts list, replace if incorrect
5 Water supply too conductive 5a Contact Nortec representative for recommendation on alternate cylinder
5b Change the water supply
6 Humidifier short cycling 6a Check if high limit or other
On/Off control is cycling
On/Off in less than 5 minutes. Check location and setting of high limit.
6b Reduce the output by turning down the capacity potentiometer.
7 Wrong cylinder installed
8 Cylinder Spent but not detected by software
9 Condensate from other source
10 Back pressure
7 Install correct cylinder model
8 Replace the cylinder (see maintenance chapter)
9 Remove condensate returns other than from steam line.
10 Eliminate back pressure
51 | Troubleshooting
Table 8: Troubleshooting RH2 Faults (Continued)
Yellow LED
2 flashes
System Detected
No Current
Fill valve activated for long time but high water level not reached.
Fill should be faster than
1” per minute.
Cause
1 Drain valve leaking or stuck open
2 Water shut off valve closed
3 Fill Valve strainer blocked
4 High system back pressure
5 High water sensor not connected
6 Low water conductivity
1 Primary wire not looped through current transformer.
Corrective Action(s)
1 Clean drain valve or replace
(see maintenance chapter)
2 Open shut off valve
3 Clean out strainer on fill valve inlet.
4a Check for kinked hose
4b Check for proper condensate removal (see installation chapter)
4c Install fill cup extension
5 Check that cylinder plug with white marker is connected to short electrode with a plastic well around it and to control board.
6a Check if potable water supplied to unit, not treated water (RO or DI) .
6b Check conductivity of water.
If less than 150 µS/cm.
6c Add 1/4 teaspoon of salt to fill cup and restart unit.
1 Open disconnect, rewire primary wire through current transformer.
3 flashes
4 flashes
No Current, High Water
Water level at top of cylinder with no current
2 High water sensor plug is on an electrode pin.
3 Cylinder plugs installed incorrectly
Cylinder Spent
Electrodes covered with scale.
1 Cylinder electrodes are covered with scale and humidifier cannot meet demand
2 Install high water senor plug on cylinder pin with shroud around it.
3 Check that cylinder plugs colors match markers next to electrodes on cylinder and that white marked cylinder plug is connected to short electrode located in plastic well.
1 Replace cylinder with same model number (see maintenance chapter).
In order to clear “spent cylinder” fault codes, externally powered modulating controllers will have to be turned off before power cycling the unit.
Troubleshooting| 52
RH2 Wiring Diagram
53 | Troubleshooting
Exploded View and Spare Parts List
RH2+ Spare Parts
The Nortec residential humidifier model should be confirmed.
The following spares parts are for RH2+ models only:
Nortec Part No.
2560953
2560952
Description
RH2+ Duct, 10lbs/hr, 120/208/240V 1P
RH2+ Space, 8lbs/hr, 120/208/240V 1P
Spare parts RH and RH2 models can be found in RH2 manual 2549509.
Go to www.humidity.com
to download RH2 manual 2549509. t Nortec Part No.
2548759
2548758
2548005
2548004
Description
RH Duct, 10lbs/hr, 120/208/240V 1P
RH Space, 8lbs/hr, 120/208/240V 1P
RH2 Duct, 10lbs/hr, 120/208/240V 1P
RH2 Space, 8lbs/hr, 120/208/240V 1P
Spare Parts| 54
RH2+ Spare Parts
The following spares parts are for RH2+ models only: t Nortec Part No.
2560953
2560952
Description
RH2+ Duct, 10lbs/hr, 120/208/240V 1P
RH2+ Space, 8lbs/hr, 120/208/240V 1P
55 | Spare Parts
Figure 37: RH2 Spare parts
RH2+ Spare Parts
The following spares parts are for RH2 models only:
8
9
10
11
12
13
3
4
5
6
7
14 t Nortec Part No.
2560953
2560952
Item
1
2
Description
RH2+ Duct, 10lbs/hr, 120/208/240V 1P
RH2+ Space, 8lbs/hr, 120/208/240V 1P
2560780 or
2547403
2549654
1323020
2548008
2548314
2548683
2573515
2568368
1456000
2548313
2562415
2547964
1639011
Nortec Part No.
Table 9: RH2 Spare Parts List
Reference
Description
RH2 DUCT Back Cover or
RH2 SPACE Back Cover
RH2 DUCT Front Cover or
RH2 SPACE Front Cover
RH2 Space Preformed Hose
Ground Clamp
RH2 SPACE Power Supply
RH2 SPACE Fan
RH2 SPACE Distributor
Fill Valve
RH2 SPACE Condensate Hose
Drain Valve Assembly
Optional Bottom Cover
Transformer Multi-tap 120/208/240V
Cylinder Plug Kit
Elbow/Compression Fitting Assembly
15
16
17
18
19
20
21
2568048 or
2568047
Reference
Reference
2547998
1583008
1323097
1519002
22 2569903
Not Shown 1583126
PCB RH2+ DUCT10 lbs/hr or
PCB RH2+ SPACE 8 lbs/hr
Electrical Backplate
Drain Pan
Preformed Drain Hose
LED Lens
Rocker Switch
Cylinder 202
Fill Cup Assembly
1.50A Fuse
Spare Parts| 56
57 | Spare Parts
Warranty
Nortec Humidity Inc. and/or Nortec Humidity Ltd. (hereinafter collectively referred to as THE
COMPANY), warrant for a period of two years after installation or 30 months from manufacturer’s ship date, whichever date is earlier, that THE COMPANY’s manufactured and assembled products, not otherwise expressly warranted (with the exception of the cylinder), are free from defects in material and workmanship. No warranty is made against corrosion, deterioration, or suitability of substituted materials used as a result of compliance with government regulations.
THE COMPANY’s obligations and liabilities under this warranty are limited to furnishing replacement parts to the customer, F.O.B. THE COMPANY’s factory, providing the defective part(s) is returned freight prepaid by the customer. Parts used for repairs are warranted for the balance of the term of the warranty on the original humidifier or 90 days, whichever is longer.
The warranties set forth herein are in lieu of all other warranties expressed or implied by law. No liability whatsoever shall be attached to THE COMPANY until said products have been paid for in full and then said liability shall be limited to the original purchase price for the product. Any further warranty must be in writing, signed by an officer of THE COMPANY.
THE COMPANY’s limited warranty on accessories, not of the companies manufacture, such as controls, humidistats, pumps, etc. is limited to the warranty of the original equipment manufacturer from date of original shipment of humidifier.
THE COMPANY makes no warranty and assumes no liability unless the equipment is installed in strict accordance with a copy of the catalog and installation manual in effect at the date of purchase and by a contractor approved by THE COMPANY to install such equipment.
THE COMPANY makes no warranty and assumes no liability whatsoever for consequential damage or damage resulting directly from misapplication, incorrect sizing or lack of proper maintenance of the equipment.
THE COMPANY makes no warranty and assumes no liability whatsoever for damage resulting from freezing of the humidifier, supply lines, drain lines, or steam distribution systems.
THE COMPANY retains the right to change the design, specification and performance criteria of its products without notice or obligation.
Warranty | 58
U.S.A.
2700 90 th
St.
Sturtevant, WI 53177
835 Commerce Park Dr.
Ogdensburg, NY 13669-2209
CANADA
2740 Fenton Road
Ottawa, Ontario K1T 3T7
TEL: 1.866.NORTEC1
EMAIL: [email protected]
WEBSITE: www.humidity.com
advertisement
Related manuals
advertisement