INSTALLATION
INSTRUCTIONS
VOLUME 3
REFERENCE DOCUMENTATION
HARDWIRE WIRELESS
COMMERCIAL / RESIDENTIAL
GEMC-255
GEMC-128
GEMC-96
GEMC-32
CONTROL PANEL / COMMUNICATOR
Installing the GEMINI C-Series Control Panels with the
GEMC-FK1 K eyp ad an d t h e GEMC-BK1 K ey p ad
SYSTEM NORMAL
11/02/18 12:05 AM
SYSTEM READY
11/02/18 12:05 AM
© NAPCO 2014
GEMC-FK1 Keypad GEMC-BK1 Keypad
WI1653D Vol 3 12/14
Page 2 Installation Instructions, Volume 3
THIS MANUAL INCLUDES FEATURES WHICH ARE ONLY AVAILABLE IN CONTROL PANEL
FIRMWARE VERSION 85 OR LATER, AND REFLECTS THE FEATURES FOUND IN
PCD-WINDOWS QUICKLOADER DOWNLOAD SOFTWARE VERSION 6.3.2 OR GREATER.
DISCLAIMER
Napco Security Technologies, Inc. (Napco) makes no representations or warranties with respect to the contents hereof and specifically disclaims any implied warranties of merchantability or fitness for any particular purpose.
Further, Napco reserves the right to revise this publication and to make changes from time to time in the content hereof without obligation of Napco to notify any person of such revision or changes.
Information furnished by Napco is believed to be accurate and reliable. However, no responsibility is assumed by
Napco for its use; nor for any infringements of other rights of third parties which may result from its use. No license is granted by implications or otherwise under any patent or patent rights of Napco.
Microsoft
®
and Windows
®
are registered trademarks of the Microsoft Corporation.
All other trademarks cited in this manual are for reference only and are the property of their respective owners.
Copyright © 2014 by Napco Security Technologies, Inc.
This document contains proprietary information of Napco. Unauthorized reproduction of any portion of this manual without the written authorization of Napco is prohibited. The information in this manual is for informational purposes only. It is subject to change without notice. Companies, names and data used in examples herein are fictitious unless otherwise noted. Napco assumes no responsibility for incorrect information this manual may contain.
For systems that include CO detectors, the system must be monitored by a central station.
Napco Security Technologies, Inc., 333 Bayview Avenue, Amityville, New York 11701
Publicly traded on NASDAQ Symbol: NSSC
Visit our website at http://www.napcosecurity.com/
For Sales and Repairs - (800) 645-9445
Refer to accompanying Gemini C-Series Control Panel Programming Instructions (WI1673 volumes 1 and 2) for programming information.
NAPCO Security Systems, Inc.
333 Bayview Avenue, Amityville, New York 11701
For Sales and Repairs, call toll free: (800) 645-9445
For direct line to Technical Service, call toll free: (800) 645-9440
Internet: http://www.napcosecurity.com
Contact your Local Service
Representative:
_________________________
_________________________
_________________________
_________________________
NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 3
Installation Instructions, Volume 3
TABLE OF CONTENTS
Page 3
Specifications and Ratings .............................................................................................................................................................. 4
Gemini C-Series Motherboards ........................................................................................................................................................ 4
Gemini C-Series Motherboard Modules .......................................................................................................................................... 4
GEMC-BM / PS: Burglary Module with Power Supply............................................................................................................ 4
GEMC-BM: Burglary Module ................................................................................................................................................... 4
GEMC-F8ZCPIM: Conventional 8 Fire Zone Expander .......................................................................................................... 5
GEMC-FW-SLC: Fire Signaling Line Circuit Module .............................................................................................................. 5
GEMC-BSLC: Burglary Signaling Line Circuit Module .......................................................................................................... 5
GEMC-NL-MOD: Network Communication Module ............................................................................................................... 5
GEMC-RS232: Control Panel / Computer Converter .............................................................................................................. 5
GEMC-24VR: 24 Volt "Regulated" Output Module ................................................................................................................. 5
Modules Wired To Fire and/or Burglary Buses .............................................................................................................................. 5
GEMC-FK1: Fire Keypad ........................................................................................................................................................... 5
GEMC-BK1: Burglary Keypad .................................................................................................................................................. 5
GEMC-EZM8: Expansion Zone Module ................................................................................................................................... 6
GEMC-RM3008: Relay Module ................................................................................................................................................. 6
GEMC-OUT8: Programmable Output Module ......................................................................................................................... 6
GEMC-RECV: Wireless RF Receiver ....................................................................................................................................... 6
GEMC-NACXX: Supervised NAC Extender ............................................................................................................................. 6
GEMC-FPRINT: Parallel Printer Interface ................................................................................................................................ 6
GEMC-12V2APS-CF: Power Supply ........................................................................................................................................ 6
GEMC-12V2APS-R: Power Supply ........................................................................................................................................... 7
Fire or Burglary Bus Wire Gauges ........................................................................................................................................... 7
GEMC-BSLC-1PT: Single Point Expander .............................................................................................................................. 7
GEMC-BSLC-4PT: Four Point Expander ................................................................................................................................. 7
GEMC-BSLC-PIR: SLC Passive Infrared Sensor ................................................................................................................... 7
GEMC-BSLC-DT: SLC Dual Technology Sensor .................................................................................................................... 7
GEMC-BSLC-RLY: SLC Single Point Relay Module ............................................................................................................... 7
GEMC-BSLC-GB: SLC Glass-Break Detector with Tamper ................................................................................................... 7
Wireless Devices ............................................................................................................................................................................... 8
GEMC-WL-WD2: Window / Door Transmitter ......................................................................................................................... 8
GEMC-WL-WD: Low Profile Window / Door Transmitter ....................................................................................................... 8
GEMC-WL-HEAT: Heat Detector .............................................................................................................................................. 8
GEMC-WL-GB: Glass Break Detector ..................................................................................................................................... 8
GEM-KEYF: Keyfob ................................................................................................................................................................... 8
GEMC-WL-SMK: Supervised Smoke Detector ........................................................................................................................ 8
GEMC-WL-CO: Supervised CO Detector ................................................................................................................................. 8
GEMC-WL-PIR: PIR Transmitter .............................................................................................................................................. 8
GEMC-WL-DT: Dual Technology Sensor ................................................................................................................................ 8
GEMC-WL-CO: Wireless Carbon Monoxide (CO) Detector .................................................................................................... 8
GEMC-PS24V7A: 7 Amp Power Supply .......................................................................................................................................... 9
GEMC-PS24V4A: 4 Amp Power Supply .......................................................................................................................................... 9
AES to Point ID Translation Codes ........................................................................................................................................... 10-11
Ordering Information ................................................................................................................................................................. 12-15
Output Activation Table .................................................................................................................................................................. 15
Commercial Standby Current Calculation Worksheets ............................................................................................................... 16
GEMC C-Series Control Panel Ground Fault Troubleshooting Instructions......................................................................... 17-18
GEMC C-Series Control Panel Firmware Update instructions .................................................................................................... 19
FCC Statement ................................................................................................................................................................................ 23
Limited Warranty ............................................................................................................................................................................. 24
Important Wiring Methods .............................................................................................................................................................. 24
NOTE: THESE INSTRUCTIONS ARE INTENDED AND WRITTEN FOR PROFESSIONAL INSTALLATION PERSONNEL HAVING
SUITABLE TRAINING, EXPERIENCE AND INSTALLATION EQUIPMENT. IT IS RECOMMENDED THAT AFTER PROGRAMMING,
THE ERROR CHECK UTILITY OF PCD-WINDOWS DOWNLOAD SOFTWARE BE USED TO VERIFY THAT THE CONTROL PANEL
PROGRAM CONTAINS NO ERRORS OR CONFLICTS WHICH MAY INHIBIT ITS INTENDED OPERATION.
NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 3
Page 4
0.6;
GEMC-BM/PS total combined standby + 25mA;
GEMC-FW-SLC total combined 24V standby current;
Installation Instructions, Volume 3
SPECIFICATIONS AND RATINGS
Note: See individual accessory work instructions (WI's) for exceptions and other information.
GEMC-255MB, GEMC-128MB, GEMC-96MB and GEMC-
32MB Gemini C-Series Motherboards
Motherboard Power Supply (GEMC-PS24V7A and GEMC-
PS24V4A) Input Power: 120AC 60Hz, 3A; maximum 15A dedicated branch circuit.
Motherboard (GEMC-255MB, GEMC-128MB, GEMC-96MB and
GEMC-32MB) Input Power: 24VDC, maximum 7A.
Power:
Note:
● Maximum Total combined 24V Standby and Alarm Current:
(Total combined 12V standby plus alarm current times 0.6) + NAC A
-D 24V standby plus alarm current:
25mA) times 0.6;
plus GEMC-BM/PS total 24V standby and alarm current +
25mA;
GEMC-FW-SLC total combined 24V standby and alarm current; rent = 6.8A with 7A supply (GEMC-PS24V7A); 3.8A with 4A supply
(GEMC-PS24V4A).
● Maximum Battery Charging Current: Refer to the GEMC-
PS24V7A or GEMC-PS24V4A power supply specifications. The maximum charging current (trickle charge and fast charge) and the maximum ampere-hour capacity of the battery that the product is intended to charge:
Standby
cuits (one 24V and one 12V or 24V selectable).
● NAC A, NAC B, NAC C: Regulated 24V NAC circuit; 2A maximum. When configured for 24V Auxiliary Power, it is a Special Application output only listed with the GEMC-24VR. The GEMC-24VR output is Regulated 24VDC, 1A maximum.
● NAC D: When configured for 24V: Regulated 24V NAC circuit;
2A maximum. When configured for 24V Auxiliary Power, it is a Special Application output only listed with the GEMC-24VR. The GEMC
-24VR output is Regulated 24VDC, 1A maximum.
● NAC D: When configured for 12V: Regulated 12V NAC circuit,
2A maximum or Regulated 12V Auxiliary Power, 1.4A maximum.
● Fire Aux. Relay Output: Wet: 12V Regulated, 750mA max.; Dry:
Remove shunt for dry contacts; see Wiring Diagram; dry contact
Form C relay rated 30VAC / VDC, 2.5A maximum.
● Two Active low programmable outputs: (2A maximum). Note:
Relies on 2A over-current protection of connected circuit.
● Trouble Sounder Output: 12V Regulated, 30mA.
● E7 and E8 Terminals: Active low open collector outputs; 0.1V,
2A (wire only to power limited circuits 30VDC or less).
● Auxiliary Power Output: Output 12V Regulated @ 750mA maximum current.
● Remote Bus Power Output: 12V Regulated @ 750mA maximum current, supporting up to 7 keypads, zone expansion modules, or wireless receivers, etc.
● Auxiliary Power 24V Regulated: Can only be supplied through
NAC A, NAC B, NAC C or NAC D (configured for 24V) programmed for Reverse Polarity and wired to GEMC-24VR. 1.0A* Maximum
(must reduce total combined standby and alarm current by 1.1 times
24V Regulated current).
● Maximum Combined 12V Regulated standby current: Remote
Power + Auxiliary Power + NAC D 12V Output and programmed for
Reverse Polarity + AUX relay if shunt connector is installed:
plus GEMC-BM total standby current plus 25mA;
plus
1.4A*.
If additional 12V current is required, use the GEMC-12V2APS-
CF (for Fire applications) and/or GEMC-12V2APS-R (for non-
Fire applications) Auxiliary Power supplies.
● Maximum Total Combined 12V Regulated Standby and Alarm
Current: Remote Power + Auxiliary Power + NAC D 12V Output and programmed for Reverse Polarity + AUX relay if shunt connector is installed + NAC D alarm current:
GEMC-BM total combined standby and alarm current +
25mA;
● Maximum Total Combined 24V Standby: (Total combined 12V standby plus alarm current times 0.6) + NAC A-D 24V standby current:
POWER SUPPLY" and "GEMC-PS24V4A 4 AMP POWER SUP-
PLY" (data also located in WI1646 and WI1702).
Voltage:
Loop
Loop Resistance: See zone expansion modules.
Operating Environment: 0-49°C (32-120°F).
Modules that plug into the GEMC-XXXMB
Gemini C-Series Motherboards:
GEMC-BM / PS Burglary Module with Power Supply
plied by the "Total Combined Standby and Alarm Current".
Power:
Burg Bell Power: 10.8 - 12.5VDC, 2A maximum.
Burg Bus Power ("Remote Bus Power"): 11.2 - 12.5VDC, 750mA maximum.
PGM1: Active low, 8.2 - 12.0V @ 150mA.
PGM2: Active low, 8.2 - 12.0V @ 150mA.
AUX Power); may be set to a dry form "c" relay contact upon removing or cutting the jumper "R"; output rated 30VAC/DC, 3A (Resistive Load
Only)
Total Combined Standby Current (Auxiliary Power + Burg Bus power + Aux Relay power): 750mA.
Total Combined Standby and Alarm Current (Auxiliary power +
Burg Bus power + Aux Relay power + Bell power): 2.5A.
Options:
One 12V 4AH battery: Maximum standby 500mA + maximum alarm 1A = total 1.5A.
One 12V 7AH or 8AH battery: Maximum standby 750mA + maximum alarm 1.75A = total 2.5A.
Maximum Battery Charging Current: 1A.
Note: Does not affect GEMC-XXXMB standby battery calculations, as all standby current is from dedicated battery. Maximum GEMC-
XXXMB combined alarm and standby current must be reduced by 0.6 times the combined alarm and standby current of the GEMC-BM/PS plus 25mA.
GEMC-BM BURGLARY MODULE
Power:
standby and alarm current. Must reduce GEMC-XXXMB total 12V standby current by GEMC-MB total standby current plus 25mA.
* Must be reduced if an insufficient number of standby batteries are used. Refer to Battery Standby chart.
NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 3
Installation Instructions, Volume 3 Page 5
Note: GEMC-BM total standby and alarm current plus GEMC-XXXMB total 12V standby and 12V alarm current must not exceed 2.5A.
Power:
Burg Bell Power: 12VDC Regulated, 2A maximum.
Modules Mounted Inside the C-Series Motherboard Enclosure:
GEMC-NL-MOD Network Communication Module
Burg Bus Power ("Remote Bus Power"): 12V Regulated, 750mA maximum.
Active low, 10.6 - 12VDC @ 150mA.
Active low, 10.6 - 12VDC @ 150mA (For UL Commercial installations) from AUX Power); may be set to a dry form "c" relay contact upon removing the jumper "R"; output rated 30VDC, 3A (Resistive Load)
Total Combined Standby Current (Auxiliary power + Burg Bus power + Aux Relay power +25mA standby current): 750mA.
Total Combined Standby and Alarm Current (Auxiliary power +
Burg Bus power + Aux Relay power + Bell power): 2.5A.
GEMC-F8ZCPIM Conventional 8 Fire Zone Expander Module
Input Power: Nominal 12VDC, 85mA.
Note: 12V power must be supplied from GEMC-XXXMB AUX PWR terminals. Available panel 12V combined auxiliary current is reduced by 85mA.
Output Power: PGM-style open collector (negative trigger) with a maximum sink current of 50mA. Wire only to power-limited circuits less than 14VDC.
Dimensions: 1½" x 7" x 4¾" (H x W x D)
Note: The GEMC-NL-MOD Network Communication Module can be used as the primary communicator; see WI1754 for details.
GEMC-RS232 Control Panel / Computer Converter
Ratings
standby and alarm current.
Power:
PWR: 12V Regulated, 700mA maximum.
Note: 12V power must be supplied from GEMC-XXXMB AUX PWR terminals. Available GEMC-XXXMB total combined 12V auxiliary current must be reduced by 60mA.
Output: RS232 format, maximum 50 feet.
Note: For supplementary use only.
Dimensions (HxWxD) : 11/16" x 2 9/16" x 2 9/16" Maximum Total Combined Standby and Alarm Current: 120MA + total combined standby current. Must reduce GEMC-XXXMB total combined 12V standby power by GEMC-F8ZCPIM total combined standby current.
Note: For supplementary use only.
GEMC-24VR 24 Volt "Regulated" Output Module
Voltage: 13.8 - 8.5VDC.
Current: 2mA standby loop current.
Alarm: 42mA maximum alarm current per zone.
Maximum Loop Resistance: 10 ohms. output of the GEMC-XXXMB or GEMC-NACXX programmed for reversed polarity.
Output Power: 24V Regulated, 1.0A maximum (maximum is reduced by battery configuration and required standby time). EOLR will not pull any current in standby or in alarm. All initiating circuits are Class B.
GEMC-FW-SLC Fire Signaling Line Circuit Module
Modules Wired to Fire Bus and/or Burglary Bus:
GEMC-FK1 FIRE KEYPAD
current.
Maximum Total Combined 24V Input Current: 475mA.
Output Power: 36V, 150mA maximum. The additional alarm current (5 LED's @ 8mA for 40mA) is automatically added to determine standby + alarm current.
Note: Refer to PCD-Windows Quickloader download software's calculation tools for 24V standby current calculation. GEMC-XXXMB total combined 24V auxiliary standby current must be reduced by GEMC-
FW-SLC input current.
Temperature:
Dimensions W x D x H: 4.5" x 4" x 1"
GEMC-BSLC Burglary Signaling Line Circuit Module
lighting is disabled (cut jumpers W1, W2 & W3).
Maximum Number of Fire Keypads: 7
Maximum Number of Fire Keypads + Burglary Keypads: 15
POWER RATINGS
GEMC-FK1 is powered by the Fire bus of the GEMC-Series motherboard, GEMC-12V2APS or an appropriately rated UL Listed Security/
Signaling power limited power supply. Deduct these values from the system standby current, as described in the control panel wiring diagram.
GEMC-BK1 BURGLARY KEYPAD
ELECTRICAL
Power: 12.5 - 7.5VDC, 110mA maximum (120mA when using integral EZM). 35mA if backlighting is disabled (cut jumpers W1, W2 &
W3).
Power:
Requirements: 24VDC, 55mA (standby current) + device current (provided by GEMC Series control panel).
Maximum Total Combined 24V Input Current: 590mA.
Output Power: 16.5V, 500mA maximum.
Note: Refer to PCD-Windows Quickloader download software's calculation tools for 24V standby current calculation. GEMC-XXXMB total combined 24V auxiliary standby current must be reduced by GEMC-
BSLC current.
Operating Temperature: 32° to 120°F (0° to 49°C)
Dimensions W x D x H: 4.5" x 4" x 1"
PGM Output (active low): 5mA, 12V. Wiring to power limited circuits less than 14VDC.
Maximum Number of Burglary Keypads: 15.
Maximum Number of Fire Keypads + Burglary Keypads: 15.
Maximum Wiring Length for each run: (#22AWG): 1000' divided by total number of keypads on run.
RATINGS
GEMC-FK1 and GEMC-BK1 are both powered by the keypad bus of the control panel, GEMC-12V2APS or an appropriately rated UL Listed
Security/Signaling power-limited power supply. Deduct these values from the system standby current, as described in the control panel wiring diagram.
NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 3
Page 6 Installation Instructions, Volume 3
GEMC-BK1 supports an integral 4 zone EZM:
Zone Loop Voltage: 12V
Zone Loop Current: 4.7mA nominal, 5.5mA when shorted.
Maximum Zone Loop Resistance: 300 ohms.
2.2K End of line resistor.
GEMC-EZM8 Expansion Zone Module
Electrical
Power: 12.5 - 7.5VDC, 60mA.
Zone Loop current: 4.7mA nominal, 5.5mA when shorted.
Maximum Zone Loop Resistance: 300 ohms.
2.2K End of line resistor (UL Listed part number EOL2.2K required in Fire applications).
PGM Output (Active low): 5mA, 12V. Connect only to powerlimited circuits less than 14VDC. Use only in Burglary applications.
Ground Faults Detected: 1.25KΩ to ground or less.
GEMC-RM3008 Relay Module
Electrical
Input
total 118mA of all relays energized.
Voltage: 30VAC or 30VDC maximum.
Current: 2A maximum (resistive load).
Maximum Wiring Length for each run (on Fire Bus or GEMC-BM
burg bus): 750 feet with #22AWG, 1000 feet with #18AWG.
Maximum Wiring Length for each run (on GEMC-BM/PS burg
bus): 20 feet with #22AWG, 40 feet with #18AWG. Note: Do not use bus power to power devices on relay outputs or wire length must be reduced by half for each 120mA used.
Metal Housing (H x W x D): 10 5/16" x 8 ⅜" x 3"
GEMC-OUT8 Programmable Output Module
Electrical
Power: 12.5 - 7.5VDC, 35mA standby maximum.
Current: Standby 35mA + current required for each active output. ty" (see the "NAC/Output Assignment" screen in PCD-Windows Quickloader software). Auxiliary power is 24V Unregulated. When used with the GEMC-24VR, these auxiliary outputs are 24V Regulated.
Supervision:
● AC fail supervision, approximate 1 minute delay to prevent nuisance swingers
● Battery presence, low battery supervision and battery charger voltage supervision; combined to generate a common battery trouble
● Remote bus supervised for opens, shorts or ground faults
Additional GEMC-NACXX Specifications:
NAC End-of-Line Resistor: 2.2K ohms.
Common Trouble Relay ("Out Relay 5"): 30VDC @ 1A, 30VAC
@ .5A Resistive, connect to power limited circuits only.
Common Trouble Relay ("Out Relay 6"): 30VDC @ 1A, 30VAC
@ .5A Resistive, connect to power limited circuits only.
Common Trouble Relay ("Out Relay 7"): 10A / 120VAC; 2.5A /
30VAC / DC Resistive Load.
Input control circuit: 9–32VDC @ 4mA maximum.
Operating Temperature: 32°F to 122°F (0°C to 50°C).
Operating Humidity Range: 10% to 90% relative humidity, from
32°F to 104°F (0°C to 40°C) non-condensing.
Housing
The GEMC-NACXX comes complete with 7A power supply, enclosure and ample room for standby batteries. Two models are available, as determined by the size of the enclosure:
Enclosure Dimensions (W x H x D, Inches):
The GEMC-NAC7S uses the small housing with sufficient room for a pair of 12V standby batteries (model GEMC-
HSKIT1416, size 14.25" x 16" x 5.25")
The GEMC-NAC7L uses the large housing with room for four pairs of 12V standby batteries (model GEMC-HSKIT1425, size
14.25" x 24" x 5.25")
GEMC-FPRINT Parallel Printer Interface (Fire Bus only)
Maximum Single Output Current: 50mA power-limited circuits
14VDC maximum.
Maximum Combined Output Current: 400mA power-limited circuits
14VDC maximum. rent or alarm current depending on the function of the output unless current is provided by a separate UL Listed power supply at 12 volts.
GEMC-RECV Wireless RF Receiver
Temperature: 0°C to 49°C.
Storage Temperature: 20°C to + 85°C.
Antenna: ¼-Wave (2)
Dimensions: 6¾" x 3⅝" x 1½" (W x H x D)
Operating Frequency: 319.5Mhz
GEMC-NACXX Supervised NAC Extender
The GEMC 7 ampere NAC Extender includes 2 models as determined by the housing used: The GEMC-NAC7L (for large enclosure) and
GEMC-NAC7S (for small enclosure).
Ratings
Input Power:
Primary input power: 120VAC, 50/60Hz, 3A, maximum 15A dedicated branch circuit.
Secondary power: 24V operation, up to eight 12V / 7AH / 7.5AH /
8AH batteries in pairs (7AH-32AH standby).
Fire Bus Input Power Rating: 12.5 - 7.5VDC, 8mA.
Power:
Total Output Power: 24VDC, 7A maximum, power limited outputs.
Each NAC circuit output rated @ 2A maximum.
Optional Auxiliary Output Power: 2A maximum per NAC circuit;
1.1A @ 24V maximum standby current (depending on batteries utilized) for 24 hours. Any of the 4 NACs can be used for auxiliary outputs by programming the output with the feature "Reverse Polari-
Dimensions: 1½" x 7" x 4¾" (3.8 x 17.8 x 12cm) H x W x D
MAXIMUM WIRE LENGTH: The GEMC-FPRINT may be mounted on the control panel fire bus up to 500 feet (with #22AWG wire) or 1000 feet (with #18AWG wire) from the control panel. The Parallel Printer must be mounted with 20 feet (6.1m) of the GEMC-FPRINT module.
NOTE: For UL approved installations, the wire length (GEMC-
FPRINT to printer) must be no more than 20 feet (6.1m) and the printer shall reside in the same room as the GEMC-FPRINT with no intervening walls or barriers.
GEMC-12V2APS-CF SPECIFICATIONS
Ratings
(Use dedicated 15A circuit for input power)
Primary Input Power: 120VAC, 60Hz, 1A.
Secondary Input Power: Minimum two 12V / 4AH batteries; two
12AH batteries maximum (see Standby Current Charts for battery requirements).
Total Output Power: 12VDC, 2A maximum combined alarm and standby current (less 40mA standby current for power supply board).
Two Auxiliary Power Outputs: 12V Regulated, 1.5A maximum each; 0.80A @ 12V combined maximum standby current for 24 hours.
Standby Current: 40mA for main board (subtract from overall rating).
Additional Specifications (for GEMC-12V2APS-CF and GEMC-
12V2APS-R)
AC:
off when no AC or brownout is detected. Connect to power-limited circuits only, 30VDC maximum. off when no battery, low battery and/or battery charging circuit trouble is detected. Connect to power-limited circuits only, 30VDC maximum.
Active Low, switches up to 2A DC. Normally active, turns off when microprocessor stops functioning, no AC, brownout or battery trouble. Connect to power-limited circuits only, 30VDC maximum.
Operating Humidity Range: Maximum 85% relative humidity @
NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 3
Installation Instructions, Volume 3 Page 7
30°C.
Enclosure Dimensions (WxHxD): Inches: 13.875" x 12.375" x
3.80" (enclosure not provided with the GEMC-12V2ABOARD)
GEMC-12V2APS-R SPECIFICATIONS
Primary Input Power: 120VAC, 60Hz, 60W (NAPCO TRF-14).
Secondary Input Power: Two 12AH batteries maximum.
Total Output Power: 2.1A minus selected charging current. (see
JUMPERS section for charging current selections).
Two Auxiliary Power Outputs: 12V Regulated, 1.5A maximum each; 0.80A @ 12V maximum standby current for 24 hours (see
GEMC-12V2APS BATTERY / CURRENT SPECIFICATIONS tables).
Standby Current: 40mA for main board (less 40mA standby current for power supply board).
Housing
The GEMC-12V2APS comes complete with transformer, enclosure and ample room for standby batteries. Each model requires either two 12V
4AH, 4.5AH, 5AH batteries, two 12V 7AH, 7.5AH, 8AH batteries or two
12V / 12AH batteries.
Modules Wired to the Fire SLC Bus:
For the devices listed below, refer to PCD-Windows Quickloader download software's calculation tools.
FWC-FSLC-CZM
FWC-FSLC-DUCT
FWC-FSLC-EZM1
FWC-FSLC-EZM2
FWC-FSLC-HEAT
FWC-FSLC-ISO
FWC-FSLC-PROG2
FWC-FSLC-PULL
FWC-FSLC-RM2
FWC-FSLC-SMK
FWC-FSLC-SOM1
Fire or Burglary Bus Wire Gauges
Gauge (solid) Resistance (Ω) Length (ft) Max. Current (ma)
16.8 1000 120
22
18
16
14
12
8.4
4.2
6.6
3.3
1.65
4.2
2.1
1.1
2.6
1.3
.65
1.7
.85
.51
500
250
1000
500
250
1000
500
250
1000
500
250
1000
500
300
240
450
240
480
850
480
850
1700
600
1000
2000
750
1500
2000
Modules Wired to the Burglary SLC Bus:
GEMC-BSLC-1PT Single Point Expander
unit.
Output Power:
Zone Loop Ratings: 16V, 0.31mA, 0.34mA short.
Maximum Zone Loop Resistance: 300Ω.
Maximum Wiring Length: 3000' (#16 AWG). Refer to GEMC-BSLC documentation (WI1648) for complete wiring information.
Operating Temperature: 32° to 120°F (0° to 49°C)
Refer to PCD-Windows Quickloader download software's calculation tools for 24V standby current calculation.
GEMC-BSLC-4PT Four Point Expander
unit.
Output Power:
Zone Loop Ratings: 16V, 0.31mA, 0.34mA short per zone.
Maximum zone loop Resistance: 300 ohms.
Maximum Wiring Length: 3000' (#16 AWG). Refer to GEMC-BSLC documentation (WI1648) for complete wiring information.
Operating Temperature: 32° to 120°F (0° to 49°C)
Refer to PCD-Windows Quickloader download software's calculation tools for 24V standby current calculation.
GEMC-BSLC-PIR Burglary SLC Passive Infrared Sensor
Coverage (L x W): 50 feet x 50 feet (15.2m x 15.2m) at 68°F (20°C), typical (with High Sensitivity Jumper "SEN" installed) 30 feet x 35 feet
(9.1m x 10.6m) at 68°F (20°C), typical (with Normal Sensitivity)
Mounting: Wall or corner, 6 - 12 feet (3.6m) max.
High Temperature Set Point: 90°F +/- 4°F
Low Temperature Set Point: 40°F +/- 4°
RATINGS
Power: 13.6-16.3VDC (supplied by GEMC-BSLC module),
19mA.
Output Power: (not applicable)
Maximum Wiring Length: 2000 feet (#16 AWG). Refer to GEMC-
BSLC documentation for complete wiring information.
Unit shall be connected to model GEMC-BSLC which is employed in the GEMC C-Series control panel which is provided with a minimum of
4 hours standby on battery power.
PHYSICAL
Dimensions (HxWxD): 3.3in x 2.5in x 1.9in (8.4cm x 6.4cm x
4.8cm)
Weight: 5oz. (142g)
GEMC-BSLC-DT Burglary SLC Dual Technology Sensor
at 68°F (20°C), typical: 50 feet long x 40 feet wide; "Look Down" zone added.
Operating Temperature: 14° to 122°F (-10° to +49°C)
Microwave Frequency: 10.525GHz ±25MHz
Physical Dimensions: (HxWxD) 4.6 x 2.9 x 2.9 in.
Shipping
documentation for complete wiring information.
Unit shall be connected to model GEMC-BSLC which is employed in the GEMC C-Series control panel which is provided with a minimum of
4 hours standby on battery power.
GEMC-BSLC-RLY Burglary SLC Single Point Relay Module
Ratings
Voltage: 13.6-16.5VDC (connected to the GEMC-BSLC).
Current: Standby, 3.0mA + 5.0mA with energized relay.
The GEMC-BSLC-RLY is equivalent to 5 devices (and have a maximum distance of 3000 feet per home run when using 16AWG wire). See WI1648. circuits.
UL Contact Ratings: 30VDC, 2A and 30VAC, 1A (resistive load).
Maximum
documentation for complete wiring information.
(inches):
Width: 1½ (38mm) Height: 3⅛ (79mm)
Depth: 1 (25mm)
Operating Temperature: 32° to 120°F (0° to 49°C)
GEMC-BSLC-GB: SLC Glass-Break Detector with Tamper
Electrical Ratings
Input Power: 13.6-16.3VDC, 8mA supplied by GEMC-BSLC control unit.
Maximum Wiring Length: 3000 feet (#16 AWG). Refer to GEMC-BSLC documentation (WI1648) for complete wiring information.
Operating Temperature: 32° to 120°F (0° to 49°C). Refer to the PCD-
NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 3
Page 8 Installation Instructions, Volume 3
Windows Quickloader download software calculation tools for 24V standby current calculation.
Note: Detector stabilizes within 3 minutes of power up.
Relative humidity: 85% (non-condensing)
Minimum size: 10⅞ x 10⅞ in. (276 x 276mm) plate,
3
/
32
- ⅜ in. (2.4 x 9.5mm) plate;
⅛ in. - ⅜ in. (3mm - 9.5mm) tempered;
⅛ in. -
9
/
16
in. (3mm - 14mm) laminated;
¼ in. (6.4mm) wired;
⅝ in. (16mm) overall sealed insulated
Note: Coated glass with security films, including films for solar protection, up to 12 mil. (12/1000 in.) thick may be used. This product
has been evaluated with a maximum range of 6m (20 feet) with sensitivity set at maximum for protecting 3mm (1.8 in.) sealed
insulating glass and 3mm (⅛ in.) laminated glass. Note: (1) Use 20 feet (6m) radius if unsure of glass type. (2) If not using a FG-700 or FG-
701 glassbreak simulator to verify range, reduce range to 15 feet
(4.5m) for windows with blinds or unlined drapes. (3) Reduce coverage
50% for armor-coated glass.
Dimensions (HxWxD): (122 x 106 x 33mm) 4.8 x 4.16 x 1.25in.
5.5oz (160g) [without batteries or transmitter]
plate;
1/8" - 3/8" tempered;
1/8" - 9/16" laminated;
1/4" wired;
5/8" overall sealed insulated
Note: Coated glass with security films, including films for solar protection, up to 12 mil. thick may be used. The Glass-Gard
GGLL1200 has been evaluated with this product by Underwriters Laboratories Inc. UL Recognizes a maximum range of 6m (20') with
sensitivity set at maximum for protecting 3mm (1.8") sealed insu-
lating glass and 3mm (1/8") laminated glass. Note: (1) Use
20' (6m) radius if unsure of glass type. (2) If not using a FG-700 or FG-
701 glassbreak simulator to verify range, reduce range to 15' (4.5m) for windows with blinds or unlined drapes. (3) Reduce coverage 50% for armor-coated glass.
1.25"
5.5oz (160g) [without batteries or transmitter]
NOTE: The GEMC-WL-GB detects shattering of framed glass by a direct impact. It may not consistently detect breakage by blows that only crack the glass, by high velocity projectiles such as bullets, or glass broken without an impact.
GEM-KEYF Wireless Keyfob
NOTE: The GEMC-BSLC-GB detects shattering of framed glass by a direct impact. It may not consistently detect breakage by blows that only crack the glass, by high velocity projectiles such as bullets, or glass broken without an impact.
Wireless Devices:
GEMC-WL-WD2 Wireless Window / Door Transmitter
Powered by a 3-volt lithium battery.
Two zone inputs.
Use only one device when used with Fire initiating devices.
Maximum Zone Wiring Length: 25' (#18-22 AWG).
GEMC-WL-WD Low Profile Window / Door Transmitter
Input Power: Powered by a 3-volt lithium battery.
Operating
GEMC-WL-SMK Wireless Supervised Smoke Detector
Power:
Powered by a 3-volt lithium battery. Use one 3-volt lithium Duracell
DL123A, Varta CR123A, Panasonic CR123A or Sanyo CR123A.
GEMC-WL-PIR Wireless PIR Transmitter
PIR Coverage (l x w): 50' x 50' (15.2m x 15.2m) at 20°C (68°F), typical.
Mounting: Wall or corner, 10' (3m) max.
Dimensions: 4.5'' x 2.5'' x 1.7'' (11.4cm x 6.4cm x 4.3cm) (HxWxD)
Shipping
GEMC-WL-DT Wireless Dual Technology Sensor
Coverage (l x w): 40' x 40' (12.2m x 12.2m) at 20°C (68°F), typical.
Operating Temperature: 0° to +50°C (32° to 122°F)
Self-Test Interval: 11-16 hours
Microwave Frequency: 10.525GHz ± 25MHz
Recommended Mounting Height: 6--8', wall or corner
Powered by a 3-volt lithium battery (Energizer CR2032 or Duracell
DL2032).
Operating Frequency: 319.5Mhz
Operating Temperature: 0°C - 49°C
Maximum External Loop Resistance: 10Ω
GEMC-WL-HEAT Wireless Heat Detector
Electrical
Power:
Powered by a 3-volt lithium battery.
Fixed Temperature Point: 135°F (57°C).
NOTE: Replace battery with a 3V Duracell DL123A, Varta / Power-
One CR123A or Panasonic CR123A only.
GEMC-WL-GB Wireless Glass Break Detector
Range of Coverage (radius distance from sensor): 7.6m (25') maximum, omnidirectional or 4.6m (15'). No minimum range.
Input Power:
Powered by a 3-volt lithium battery; use Duracell DL123A, Varta / Power-One CR123A or Panasonic CR123A only.
Alarm current (LED's disabled): 40uA maximum (transient)
Frequency:
Operating
o
C to 49 o
C (32 o
F to 120 o
F) (Indoor use environment)
Note: Detector stabilizes within 3 minutes of power up.
Relative humidity: 85% (non-condensing)
types:
minimum size: 10-7/8" x 10-7/8", (280 mm x 280 mm) 3/32" - 3/8"
GEMC-WL-CO Wireless Carbon Monoxide (CO) Detector
Dimensions (W×L×D): 5-3/8 x 5-3/8 x 2-1/8" (13.7 x 13.7 x 5.4cm)
Ratings
Input Power: Powered by a 3-volt lithium battery. Use one 3-volt lithium Duracell DL123A, Varta CR123A, Panasonic CR123A or Sanyo
CR123A.
Environment
Temperature: 32°F to 122°F (0°C to 49°C)
Relative humidity: 15% - 95% RH
Manufacturer: Napco Security Technologies, Inc. 333 Bayview
Avenue, Amityville, NY 11701
UL rating: This detector has been evaluated to the CO detector sensitivity limits of UL 2075 / UL 2034.
Environmental class: Indoor, in accordance with the Operating
Environment specifications.
Note: For systems that include CO detectors, the system must be monitored by a central station.
NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 3
Installation Instructions, Volume 3 Page 9
GEMC-PS24V7A 7 AMP POWER SUPPLY
DESCRIPTION
The GEMC-PS24V7A-R is both a charger and a supervised power supply rated at 24VDC/7A. Input rating is
120VAC, 60Hz, 3A. Fuse rated 5A, 250V. Replace only with UL Listed fuse rated 5A, 250V (see WI1653).
FEATURES
24VDC output.
Maximum charge current 1.96A.
7 ampere continuous supply current at 24VDC.
Built-in charger for sealed lead acid or gel type batteries.
Automatic switch over to stand-by battery when AC fails.
AC input, DC output.
Short circuit and thermal overload protection.
Board Dimensions: 9"(L) x 6"(W) x 1⅝"(H)
Specified at 25°C ambient.
INSTALLATION INSTRUCTIONS
H
Caution: Turn off branch circuit before servicing power supply.
The GEMC-PS24V7A-R should be installed in accordance with The National Electrical Code, ANSI / NFPA 70 and all applicable Local Regulations.
To install, see the Gemini C-Series control panel installation instructions (WI1653) detailing removal and reinstallation instructions for all models of the Gemini C-
Series control panels. Install jumpers on J3 as per the chart below:
BATTERY CHARGE CURRENT JUMPERS
No. of Jumpers Trickle Charge Total Charge No. of Batteries
0
1
2
210 mA
440 mA
680 mA
1.50A
1.72A
1.96A
2 sets
3 sets
4 sets
GEMC-PS24V4A 4 AMP POWER SUPPLY
DESCRIPTION
The GEMC-PS24V4A-R is both a charger and a supervised power supply rated at 24VDC/4A. Input rating is
120VAC, 60Hz, 3A. Fuse rated 5A, 250V. Replace only with UL Listed fuse rated 5A, 250V (see WI1653).
FEATURES
24VDC output.
Maximum charge current 1.96A.
4 ampere continuous supply current at 24VDC.
Built-in charger for sealed lead acid or gel type batteries.
Automatic switch over to stand-by battery when AC fails.
AC input, DC output.
Short circuit and thermal overload protection.
Board Dimensions: 9"(L) x 6"(W) x 1⅝"(H)
Specified at 25° C ambient.
INSTALLATION INSTRUCTIONS
H
Caution: Turn off branch circuit before servicing power supply.
The GEMC-PS24V4A-R should be installed in accordance with The National Electrical Code, ANSI / NFPA 70 and all applicable Local Regulations.
To install, see the Gemini C-Series control panel installation instructions (WI1653) detailing removal and reinstallation instructions for all models of the Gemini C-
Series control panels. Install jumpers on J3 as per the chart below:
BATTERY CHARGE CURRENT JUMPERS
No. of Jumpers Trickle Charge Total Charge No. of Batteries
0
1
2
210 mA
440 mA
680 mA
1.50A
1.72A
1.96A
2 sets
3 sets
4 sets
NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 3
Page 10
AES TO POINT ID TRANSLATION CODES
1st column is the report "Type".
2nd column is the Point ID translation code to be reported.
3rd column is the text for that alarm
Fire
01 R110
03 R373 Fire Trouble Restore
Panic
06 E370
07 R370 Panic Trouble Restore
63 R400
64 E121 Keypad Holdup Alarm (ambush)
65 E123 Keypad Panic Alarm
67
68
69
70
E140
E137
E404
R404
Keypad Emergency Alarm
Keypad Tamper Alarm
Fail to Open
Fail to Close
73 E321
74 E338 Burg Mod Low Bat
Burglary
11 R370
Holdup
16 E200
19 R373 Fire Supervisory Trouble Restore
20 E113 Sprinkler Alarm (waterflow)
21 R113
23 R373 Sprinkler Trouble Restore
Gas
26 E370
27 R370 Gas Trouble Restore
30 E370
31 R370 Heat Trouble Restore
32
33
E200
R200
Sprinkler Supv Alarm
Sprinkler Supv Restore
34 E373 Sprinkler Supv Trouble
35 R373 Sprinkler Supv Trouble Restore
36 E100
78 E145 Tamper Alarm EZM
79 E380
81
82
R321
R338
Bell Supv Restore
Burg Mod Low Bat Restore
83 E140
84 R302 Low Battery Restore
85
86
R301
R145
AC Trouble Restore
Tamper Restore EZM
88
89
E351
E352
Tel 1 Fail
Tel 2 Fail
93 E333
94 E338 ACM Low Bat
95
96
E342
R351
ACM AC Failure
Tel 1 Restore
97
98
99
100
101
R352
R353
R354
R310
R333
Tel 2 Restore
Telemetry Trouble Restore
Telemetry Fail Restore
Ground Fault Restore
Ground Fault Fire EZM Restore
102
103
104
105
106
R338
R342
E601
E607
E300
ACM Low Bat Restore
ACM AC Fail Restore
Manual Communication Test
Guard Tour Fail
Fire 4 Wire Bus Failure
108 E306
109 E333 RF Receiver Supervision
55
56
57
58
59
47
48
49
50
51
52
53
40
41
42
43
E150
R150
E370
R370
24 hour Aux. Alarm
24 hour Aux. Restore
24 hour Aux. Trouble
24 hour Aux. Trouble Restore
44 E131 Burg Perimeter Alarm
45 R131
46 E370 Burg Perimeter Trouble
R370
E132
R132
E370
R370
E134
R134
Burg Perimeter Trouble Restore
Burg Interior Alarm
Burg Interior Restore
Burg Interior Trouble
Burg Interior Trouble Restore
Burg Exit/Entry Alarm
Burg Exit/Entry Restore
62
R370
E137
R137
E370
R370
E400
Burg Exit/Entry Trouble Restore
Burg Zone Tamper Alarm
Burg Zone Tamper Restore
Burg Zone Tamper Trouble
Burg Zone Tamper Trouble Restore
Opening
Closing
Opening Report After Alarm
113 E140
114 R300 Fire 4 Wire Bus Restore
116
117
R607
R333
Test End - Restore
RF Receiver Supervision Restore
Transmitter
119 R381
120 E608 Test Timer (Fire System Faulted)
Test
124 E140
Zone
129 E406
130 E384 RF Low Bat By Zone
NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 3
Installation Instructions, Volume 3
Installation Instructions, Volume 3
131
132
E381
E383
RF Supervision By Zone
RF Tamper By Zone
175
176
177
178
179
180
167
168
169
170
171
172
137
138
139
140
141
142
143
144
E380
E383
E380
E385
E386
E571
R571
E614
Undefined
Cancel
Burg SLC Point Tbl
Burg SLC Point Tamper
Fire SLC Point Tbl
Fire SLC Sensitivity High
Fire SLC Sensitivity Low
Fire Zone Bypass
Fire Zone Bypass Restore
Fire One Man Test
User
146 E627
147 E306 Out of Service
149 E382 NL-Mod Supv Trouble
150 E300
151 R614 Fire One Man Test Exited
152
153
154
155
R627
R627
R305
R604
User Unlock Exited
Dealer Unlock Exited
Out of Service Exited
Fire Drill Exited
156
157
158
159
160
161
R382
E344
E140
E140
E344
R344
NL-Mod Supv Tbl Restore
RF Receiver Jam
RF Receiver Tamper
RF Receiver No Response
RF Receiver High Noise
RF Receiver Jam Restore
162
163
R140
R140
RF Receiver Tamper Restore
RF Receiver No Response Restore
164 R344 RF Receiver High Noise Restore
165 E331
E382
E303
R331
R341
R382
R303
Burg SLC No Response
Burg SLC Memory Failure
Burg SLC Tbl Restore
Burg SLC Tamper Restore
Burg SLC NO Response Restore
Burg SLC Memory Failure Restore
E382
E303
R331
R341
R382
R303
Fire SLC No Response
Fire SLC Memory Failure
Fire SLC Tbl Restore
Fire SLC Tamper Restore
Fire SLC No Response Restore
Fire SLC Memory Failure Restore
NAC
185 E523
186
187
R523
E342
NAC Disable Restore
Fire Monitor AC Fail
188
189
190
R342
E342
R342
Fire Monitor AC Fail Restore
Fire Monitor AC Fail Trouble
Fire Monitor AC Fail Trouble Restore
191
192
193
E338
R338
E338
Fire Monitor Bat Test Fail
Fire Monitor Bat Test Restore
Fire Monitor Bat Test Trouble
Page 11
194
195
196
197
198
199
R338
E341
R341
E341
R331
E310
Fire Monitor Bat Test Trouble Restore
Fire Monitor EZM Tamper Alarm
Fire Monitor EZM Tamper Restore
Fire Monitor EZM Tamper Trouble
Fire Monitor EZM Tamper Trouble Restore
Fire Monitor Ground Fault Alarm
200
201
R310
E310
Fire Monitor Ground Fault Restore
Fire Monitor Ground Fault Trouble
202 R310 Fire Monitor Ground Fault Trouble Restore
203 E111
Combustion
209 E373
210
211
R373
E115
Combustion Trouble Restore
Pull Station Alarm
212
213
214
R115
E373
R373
Pull Station Restore
Pull Station Trouble
Pull Station Trouble Restore
Duct
218 R373
222 R373 CO Trouble Restore
223 E330
224 E330 KP No Response
225
226
R330
R330
Relay Board No Response Restore
KP No Response Restore
Undefined
228 R140
Undefined
233 E140
Egress
239 E424
240 E433 Request to Exit
Door
243 E426
244
245
R130
E577
Door Open Restore
ACM Point Bypass
247 R137
248 E401 Opening Only (no restore)
250 R356 Fail to Check-In Restore
System
253 E341
254
255
E356
E998
Fail to Check-In
Used to Disable Restores
NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 3
Page 12 Installation Instructions, Volume 3
ORDERING INFORMATION
OPTIONAL ACCESSORIES AND
PERIPHERALS
GEMC-255MB-R: 255 Zone C-Series Motherboard
GEMC-128MB-R: 128 Zone C-Series Motherboard
GEMC-96MB-R: 96 Zone C-Series Motherboard
GEMC-32MB-R: 32 Zone C-Series Motherboard
All C-Series Control Panels: Installation Instructions (see
WI1653)
All C-Series Control Panels: Programming Instructions (see
WI1673)
FWC-FSLC-CZM: Conventional Zone Module (see WI1714)
FWC-FSLC-DUCT: Duct Smoke Detector (with relay) (see
WI1711)
FWC-FSLC-EZM1: Single Contact Point Monitor (see
WI1713)
FWC-FSLC-EZM2: Dual Input Monitor Module (see WI1712)
FWC-FSLC-HEAT: Heat Detector (see WI1710)
FWC-FSLC-ISO: Loop Isolator (see WI1716)
FWC-FSLC-PROG2: Hand-Held Programmer (see WI1738)
FWC-FSLC-PULL: Pull Station (see WI1736)
FWC-FSLC-RM2: Dual Relay Module (see WI1715)
FWC-FSLC-SMK: Smoke Detector (see WI1709)
FWC-FSLC-SMK6B: 6" Smoke Base (see WI1737)
FWC-FSLC-SOM1: Supervised Output Module (see WI1717)
GEMC-12V2APS: Power Supply (see WI1828)
GEMC-120VAC-R: Replacement 120V wiring harness
GEMC-24VR: Commercial Fire 24V Regulated Output Module
GEMC-2D: 2nd Door Access Control Accessory (see
WI1750)
GEMC-ACM1D: Integrated Access Control Accessory (see
WI1749)
GEMC-BHBM-R: Battery Harness for GEMC-BM/PS (see
WI1704)
GEMC-BHMB-R: Battery Harness Motherboard (see WI1703)
GEMC-BK1: Burg keypad (see WI1650, OI342)
GEMC-BM/PS: BURG Module with 24/12V Power Supply
Converter for 3A/12 Burg and separate battery circuit (see
WI1700)
GEMC-BM: BURG Module without 24/12V Converter or battery circuit; shares motherboard 12V (see WI1701)
GEMC-BSLC: Burg SLC Module (see WI1648)
GEMC-BSLC-1PT: Single point expander (see WI1718)
GEMC-BSLC-4PT: Four point expander (see WI1720)
GEMC-BSLC-DT: Wireless " Dual-Tech" PIR for SLC (see
WI1721)
GEMC-BSLC-GB: SLC Glass-Break Detector with Tamper (see
WI2080)
GEMC-BSLC-PIR: Wireless PIR for SLC (see WI1719)
GEMC-BSLC-RLY: Wireless Single Point Relay Module (see
WI1723)
GEMC-EZM8: Zone Expansion Module listed for Commercial
Fire and Burg (see WI1683)
GEMC-F8ZCPIM: Conventional 8 Fire Zone Expander Plug in
Module (see WI1651)
GEMC-FK1: Fire keypad (see WI1649, OI341 )
GEMC-FPRINT: Print module for Fire Bus (see WI1708)
GEMC-FW-SLC: Fire SLC Module (see WI1647)
GEMC-HSKIT1416: Small Enclosure only + PCB mounting bar kit
GEMC-HSKIT1425: Large Enclosure only + PCB mounting bar kit
GEMC-HSKIT1416W: For Burglary-only systems. Small Enclosure only + PCB mounting bar kit (white color)
GEMC-HSKIT1425W: For Burglary-only systems. Large Enclosure only + PCB mounting bar kit (white color)
GEMC-KOTAMPERKT: Control panel enclosure anti-tamper kit
GEMC-NAC7S: Commercial Fire NAC Extender (7A, small enclosure)
GEMC-NAC7L: Commercial Fire NAC Extender (7A, large enclosure)
GEMC-NL-MOD: NetLink™ TCP/IP reporting module
(WI1731)
GEMC-OUT8: 8 Output OC module for Fire or Burg - outputs unsupervised (see WI1707)
GEMC-PS24V4A-R: 4 AMP 24V Main Power Supply (see
WI1702)
GEMC-PS24V7A-R: 7 AMP 24V Main Power Supply (see
WI1646)
GEMC-RECV: Modified RF Receiver (see WI1682)
GEMC-RM3008: 8 Output relay module for Fire or Burg - outputs unsupervised (see WI1706)
GEMC-RS232: Control Panel / Computer Converter
GEMC-TAMPERKIT: Two universal enclosure tamper switches and related hardware
GEMC-WL-CO: Wireless Commercial Carbon Monoxide (CO)
Detector Transmitter with back tamper (see WI2108)
GEMC-WL-DT: Wireless Mercantile Burg Dual Tech Transmitter with back tamper (see WI1729)
GEMC-WL-GB: Wireless Commercial Glass-Break sensor
(see WI1827)
GEMC-WL-HEAT: Wireless Commercial Fire Heat Detector
Transmitter with back tamper (see WI1727)
GEMC-WL-PIR: Wireless Mercantile Burg PIR Transmitter with back tamper (see WI1728)
GEMC-WL-SMK: Wireless Commercial Fire Smoke Transmitter with back tamper (see WI1726)
GEMC-WL-WD: Wireless Window / Door contact (see
WI1842)
GEMC-WL-WD2: Wireless Window / Door contact (see
WI1743)
GEM-KEYF: Wireless Keyfob Transmitter (see WI1730)
RB1000: Relay Board (see WI737)
EXAMPLES OF COMPATIBLE UL-LISTED DEVICES
Refer to the following list of recommended devices:
Residential Fire / Burglary:
Tane SCS101 (Self Contained Dual Tone Indoor Siren, Rated
6 - 15VDC 400mA)
GE MPI-36 (Surface Mount 2-Channel Siren/Speaker, rated 6
- 13.8VDC 350mA)
Honeywell Ademco Wave 2 (2-Tone Siren)
* Not investigated by UL.
** Not investigated by UL for Commercial applications.
NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 3
Installation Instructions, Volume 3
ORDERING INFORMATION
Napco Commercial Combo. Burglary/Fire Kits
GEMC-COMBO255KT
255 Point GEM-C Commercial Combo. Fire/Burg System Kit
24V Panel, 255 Points via commercial addressable, wireless or conventional fire or burglary devices, 4 on board
NACs, 8 partitions (No Loop Isolator/Extender required)
7 Amp, 24V Power Supply
Burglary Module, with power supply with built in bus isolator for complete separation of fire and burg power and battery standby operation
Built in horn/strobe synchronization module on each NAC
Built in dual line communicator; dual onboard serial ports
Quickloader up/downloading including remote smoke obscuration reporting
Locking, Large Red Enclosure, 16 x 25” reversible door, with 14.25” x 25” base. Houses up to 32AH battery backup
Menu-driven LCD Fire Keypad mounts anywhere on bus
(also, full keyswitch support)
GEMC-COMBO128KT
128 Point GEM-C Commercial Combo. Fire/Burg System Kit
As above, but with
24V Panel, 128 Points via commercial addressable, wireless or conventional fire or burglary devices, 4 on board
NACs, 8 partitions (No Loop Isolator/Extender required)
4 Amp, 24V Power Supply
GEMC-COMBO32KT
32 Point GEM-C Commercial Combo. Fire/Burg System Kit
Similar to above, but with
24V Panel, 32 Points via commercial addressable, wireless or conventional fire or burglary devices, 2 on board
NACs, 8 partitions (No Loop Isolator/Extender required)
4 Amp, 24V Power Supply
Napco Commercial Fire Kits
GEMC-FW-255KT
255 Point GEM-C Firewolf™ 24V Commercial Fire System Kit
24V Panel, 255 Points via commercial addressable, wireless or conventional fire devices, 4 on board NACs providing up to 6.5A notification power
7 Amp, 24V Power Supply
Built in horn/strobe synchronization module on each NAC
Built in dual line communicator; dual onboard serial ports
Quickloader up/downloading including remote smoke obscuration reporting
Locking, Large Red Enclosure, 16 x 25” reversible door, with 14.25” x 25” base. Houses up to 32AH battery backup
Menu-driven LCD Fire Keypad mounts anywhere on bus
(also, full keyswitch support)
GEMC-FW-128KT
128 Point GEM-C Firewolf™ 24V Commercial Fire System Kit
As above, but with
Page 13
24V Panel, 128 Points via commercial addressable, wireless or conventional fire devices, 4 on board NACs providing up to 6.5A notification power
GEMC-FW-32KT
32 Point GEM-C Firewolf™ 24V Commercial Fire System Kit
Similar to above, but with
24V Panel, 32 Points via commercial addressable, wireless or conventional fire devices, 2 on board NACs
4 Amp, 24V Power Supply
Locking, Medium Red Enclosure, 16 x 17” door, with
14.25” x 16” base. Houses up to 16AH battery backup.
GEMC-FW32CONVKT
32 Point GEMC Conventional Commercial Fire System Kit, ideal for sprinkler/waterflow apps. 24V Panel, 32 Points via commercial addressable, wireless or conventional fire devices,
2 on board NACs.
Locking, Medium Red Enclosure, 16 x 17” door, with
14.25” x 16” base. Houses up to 16AH battery backup.
4 Amp, 24V Power Supply
Conventional 8-zone 2-wire fire input module, for conventional 2-wire smokes or any conventional fire detection device (GEMC-F8ZCPIM)
Built in horn/strobe synchronization module on each NAC
Built in dual line communicator; dual onboard serial ports
Quickloader up/downloading including remote smoke obscuration reporting (for addressable detectors)
Menu-driven LCD Fire Keypad mounts anywhere on bus
(GEMC-FK1)
Napco Commercial Burglary Kit
GEMC-BURG96KT
96 Point GEMC Addressable Commercial Burglary System Kit
24V Panel, 96 Points via commercial addressable, wireless or conventional burglary devices, 7 partitions
Locking, Medium White Enclosure, 16 x 17” door, with
14.25” x 16” base. Houses up to 16AH battery backup.
4 Amp, 24V Power Supply
Addressable SLC Burg Module, supports up to 96 addressable SLC burg devices (GEMC-BSLC)
Built in dual line communicator; dual onboard serial ports
Quickloader up/downloading
Menu-driven LCD Burglary Keypad with built-in 4 zone
EZM, mounts anywhere on bus (GEMC-BK1)
Commercial Fire and Burglary Accessories and Options
GEMC-BM/PS
Burg Module, with Power Supply, provides isolated 4-wire
Burg bus for Burg keypads and devices, plus 12V power output for aux devices. Independent Burg Bell output. Provides complete separation of Fire and Burg power, plus independent
Burg battery connection and charger to allow independent
Burg standby operation in case of power failure.
NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 3
Page 14
ORDERING INFORMATION
Installation Instructions, Volume 3
GEMC-BM
Burg Module, provides isolated 4-wire Burg bus for Burg keypads and devices, plus 12V power output for aux devices.
Independent Burg Bell output.
GEMC-FW-SLC
Addressable SLC Fire Module, supports up to 128 addressable SLC Fire devices. Connects to the GEMC control panel (2 maximum).
GEMC-BSLC
Addressable SLC Burg Module, supports up to 128 addressable SLC Burg devices. Connects to the GEMC control panel
(2 maximum).
GEMC-F8ZCPIM
Conventional (8) zone 2-wire fire input module. Plugs into
GEMC Motherboard to provide support for conventional 2-wire smoke detectors, or any other conventional fire detection device.
Burglary Peripherals
GEMC-BK1
LCD Burg Keypad for GEMC Combo System (requires GEMC-
BM or GEMC-BM/PS module).
GEMC-BSLC-4PT
Addressable SLC Commercial Burg Device - 4 Point Input
Expansion Module.
GEMC-BSLC-1PT
Addressable SLC Commercial Burg Device - 1 Point Input
Module.
GEMC-BSLC-DT
Addressable SLC Commercial Burg Device - Dual Technology
Motion Detector , PIR and Microwave, Range 40'x40'.
GEMC-BSLC-GB
Addressable SLC Glass-Break Detector with Tamper - Maximum range 25 feet (7.6m) to the glass with no minimum range
GEMC-BSLC-PIR
Addressable SLC Commercial Burg Device - PIR Motion Detector, Range 50'x50'.
GEMC-BSLC-RLY
Addressable SLC Commercial Burg Device - 1 Point Output
Module.
GEMC-WL-PIR
Wireless Commercial Burg Device - PIR Motion Detector,
Range 50'x50'.
GEMC-WL-GB
Wireless Commercial Burg Device - Acoustic Glass break
Sensor, Max Range 25'.
GEMC-WL-DT
Wireless Commercial Burg Device - Dual Technology Motion
Detector, PIR and Microwave, Range 40'x40'.
Fire Peripherals
GEMC-FK1
LCD Fire Keypad for GEMC Combo System, Red.
GEMC-WL-SMK
Wireless Commercial Fire Device - Photoelectric Smoke Detector.
GEMC-WL-HEAT
Wireless Commercial Fire Device - Heat Detector, 135 F.
Common Peripherals
GEMC-WL-WD2
Wireless 2 Input Module, suitable for Commercial Fire and/or
Burglary applications.
GEMC-RECV
Commercial Fire and Burg approved Wireless Receiver, supports 255 devices, maximum of (4) receivers supported by
GEMC system.
GEMC-EZM8
8 Point Expansion Module, suitable for Commercial Fire and/ or Burg applications.
GEMC-FPRINT
Printer Module, supports parallel printer, suitable for Commercial Fire and/or Burg applications.
GEMC-RM3008
Relay Output Module, provides (8) Form C outputs, suitable for Commercial Fire and/or Burg applications.
GEMC-NL-MOD
Internet Reporting Module, suitable for Commercial Fire and/or
Burg applications.
GEMC-RS232
RS232 Adaptor, Provides Serial Output from GEMC Control
Panel, suitable for Commercial Fire and/or Burg applications.
GEMC-OUT8
PGM Output Module, provides (8) Open Collector PGM Outputs, suitable for Commercial Fire and/or Burg applications.
FWC-FSLC-SMK
Addressable SLC Photoelectric Smoke Detector.
FWC-FSLC-HEAT
Addressable SLC Heat Detector 135°F.
FWC-FSLC-DUCT
Addressable SLC Photoelectric Duct Smoke Detector.
NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 3
Installation Instructions, Volume 3
ORDERING INFORMATION
FWC-FSLC-EZM2
Addressable SLC 2 zone conventional input module. provides two independent contact monitoring circuits while only utilizing one address on the SLC loop. Designed to be used with pull stations, water flow switches, and other applications requiring the monitoring of dry contact alarm initiating devices.
FWC-FSLC-EZM1
Addressable SLC single input conventional input module.
Designed to be used with pull stations, water flow switches, and other applications requiring the monitoring of dry contact alarm initiating devices.
FWC-FSLC-CZM
Addressable SLC single module allows the monitoring of dry contacts such as pull stations and two-wire conventional smoke detectors.
FWC-FSLC-RM2
Addressable SLC Dual Relay Module, provides 2 outputs while only requiring one SLC address.
FWC-FSLC-ISO
Addressable SLC Fire Isolation Module. Can be used to meet
Class A, Style 7 loop requirements.
FWC-FSLC-SOM1
Addressable SLC Fire Supervised Output Module. Can be used for output functions such as elevator recall and HVAC shutdown, or as additional NAC output if used with an additional power supply.
FWC-FSLC-PULL
Addressable SLC Fire Pull Station.
Page 15
FWC-FSLC-PROG2
Programmer required for programming address into SLC devices.
FWC-FSLC-SMK6B
Base required for FWC-FSLC-SMK and FWC-FSLC-HEAT devices.
Support Products
GEMC-12V2APS-CF
Remote Supervised 12VDC Power Supply. Connects to Fire
Bus, powered by direct 120VAC connection, supports (2) pair of 12V, 7AH standby batteries.
GEMC-12V2APS-R
Remote Supervised 12VDC Power Supply. Connects to Burg
Bus, powered by supplied 16.5V, 50VA plug-in transformer, supports (2) pair of 12V, 7AH standby batteries.
GEMC-NAC7L
GEMC-NAC7S
Remote NAC Extender. Provides four (4) NAC Outputs for a combined output rating of 6.5A, or a maximum of 2A on any one output. Includes red enclosure (14"x16"), must be connected to 120VAC source, supports maximum of 28AH standby batteries ( (4) pair 12V, 7AH batteries). Connects to
GEMC Fire Bus and is fully supervised. Any or all NAC outputs may be configured as remote power supply outputs.
Supports Wheelock and System Sensor NAC synchronization.
Maximum of (5) GEMC-NAC7L's or GEMC-NAC7S's may be added to GEMC control panel, allowing for a maximum of 20 additional NAC circuits.
OUTPUT ACTIVATION TABLE
"Area 1 General Alarm" Output Activation Table
Outputs can be programmed to activate on a particular event or combination of events using the PCD-Windows
Quickloader NAC/Output Assignment screen, NAC/Output Events tab. The table below details which Alarm Types and Conditions will activate ("ON") the selected output (selected in the Relay # column in the NAC/Output Assignment screen) for an Area 1 Gen. Alarm event. For configurations that will not activate the output, an "X" is shown in the table cell.
FIRE ALARM
FIRE TROUBLE
WATERFLOW ALARM
WATERFLOW TROUBLE
SPRINKLER
SUPERVISORY ALARM
SPRINKLER
SUPERVISORY TROUBLE
MONITOR ZONE ALARM
MONITOR ZONE TROUBLE
FIRE ZONE
ALARM
(SHORT)
ON
X
X
X
X
FIRE ZONE
TROUBLE
(OPEN)
WATER-
FLOW ZONE
ALARM
WATER-
FLOW ZONE
TROUBLE
X
ON
X
X
X
ON
X
ON
X
X
X
ON
X
ON
X
FIRE
SUPERVISORY
ALARM (SHORT)
X
X
X
X
ON
X
X
X
OUTPUT EVENT "AREA 1 GENERAL ALARM"
X
X
X
X
X
X
X
X
X
X
X
X
FIRE
SUPERVISORY
TROUBLE (OPEN)
X
ON
X
X
X
MONITOR
ZONE
ALARM
(SHORT)
X
ON
X
X
X
ON
X
X
X
ON
X
MONITOR
ZONE
ALARM
(OPEN)
X
ON
X
X
X
X
X
ON
NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 3
Page 16 Installation Instructions, Volume 3
COMMERCIAL STANDBY CURRENT CALCULATION
WORKSHEETS
Most installations can be configured without using additional power supplies, however larger systems may require them. In large systems, the current charts must be used to determine if the design is possible and how many additional power supplies are required.
As the GEMC-FW-SLC, GEMC-BSLC and the GEMC-F8ZCPIM can only derive their power from the motherboard, additional power supplies cannot be used to increase the capability of these circuits. Therefore, the NAPCO Com-
mercial Standby Current Calculation Worksheet(s) must first be completed to determine if the system design is possible.
These Worksheets have been placed into a single Microsoft
®
Excel file, available online at the Napco website:
http://www.napcosecurity.com/
Once at the Napco website, click the link "Dealer support docs" and follow the links to find and download the Excel file to your local computer.
This Excel file contains all of the calculation worksheets that may be required by the AHJ ("authority having jurisdiction") for each installation NAPCO Commercial (GEMC) C- Series configuration type, namely:
GEMC-COMBO with GEMC-BM-PS
(Use to calculate standby current draw of the Fire section of GEMC-Combo control panel).
GEMC-BM/PS (BURG STANDBY ONLY)
(Use to calculate standby current draw of burglary devices powered through the GEMC-BM/PS Burglary Module).
GEMC-COMBO with GEMC-BM
GEMC Fire Only
GEMC Burg Only
When completed, these Worksheets can easily be printed and presented to the AHJ to conform with all applicable codes.
NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 3
Installation Instructions, Volume 3
GEMC C-SERIES CONTROL PANEL
GROUND FAULT TROUBLESHOOTING INSTRUCTIONS
Page 17
These instructions are designed to help resolve a ground fault System Trouble on the Gemini C-Series (GEMC) control panels, for combination Burg/Fire systems that use the GEMC-BM (Burglary Module), GEMC-BM/PS (Burglary Module with Power Supply) and/or the GEMC-BSLC (Burglary SLC Module). The ground fault occurs when earth ground is shorted to a wire extending from the control panel. Use the Burglary and/or Fire Ground Fault Troubleshooting Chart (see next page) and a volt meter with the procedure that follows.
With GEMC Fire-only or combination Fire and Burglary Alarm systems: A Fire alarm system disabled for servicing is no longer protecting the individuals within the premises; therefore extra measures MUST be taken (as required by the authority having jurisdiction) to protect these individuals before the Fire system is disabled. It is far easier to disable and service the Burglary portion of the system alone, since the Fire portion can remain in operation. Therefore, the most rational first step is to always test the Burglary portion of the system before taking the extra measures required when testing the
Fire portion of the system. All tests start with the following preliminary voltage reading:
1. Measure the DC voltage between system ground and earth ground by placing your DC volt meter negative probe to
AUX Power system ground (terminal 23), and the positive probe to earth ground (terminal 1). Make note of the voltage reading in writing. A "normal" reading without a ground fault is approximately 19V (with a ground fault, the abnormal voltage reading could be higher or lower than 19V).
With the abnormal voltage reading noted, find this voltage in the first column of the Burglary and/or Fire Ground Fault
Troubleshooting Chart
to help find the likely shorted wire. If the abnormal voltage reading appears on both charts, test the Burglary portion first; if the abnormal voltage reading appears on the Fire chart only, it is still worth testing and ruling out the Burglary portion of the system before the Fire portion. With the general information you learned with the charts, the following steps will help you confirm the location of the ground fault wire.
Test the Burglary portion of the system:
2. Without removing power, place the Burg Service Jumper (located on the bottom left of the motherboard) from OFF to
ON; the red LED to the left of the jumper lights indicating the Burglary/Access Control portion of the system is disabled.
3. If the GEMC-BM, GEMC-BM/PS or GEMC-BSLC module(s) are used: The general idea is to unplug each of these Burglary modules from the system, one by one, to see if (by removing the problem module) the meter reading returns to the "normal" 19V. With the volt meter probes in place (negative probe to terminal 23, positive probe to terminal 1), unplug one of these Burglary modules from the motherboard and observe the meter voltage reading. If the voltage does NOT return to the normal 19V, the ground fault is NOT due to the wires extending from that unplugged module (reconnect and try the next module). If the voltage DOES return to the normal 19V, the ground fault IS likely due to the wires extending from the module that was unplugged.
Confirm your results: With the suspect Burglary Module still unplugged, remove the meter probes and set your meter to ohms (Ω resistance). Place one probe to earth ground (terminal 1), and place the other probe on each Burglary
Module terminal one at a time and take a reading for each. When the resistance reads low (close to zero), the shorted wire terminal is likely found. Disconnect the wire(s) from the terminal and test the resistance of each individual wire(s); the resistance will read low for the shorted wire. Trace the wire and correct the fault to clear the trouble.
4. If each Burglary Module has been disconnected from the motherboard and the voltage has not yet returned to
the normal 19V, the problem is a ground fault on a Fire system wire
. Before attempting the following steps, take the appropriate measures to protect individuals in the premises, as required by the AHJ.
With the Burg Service Jumper still in the ON position and the red LED (to the left of the jumper) is still lit to indicate the
Burglary/Access Control portion of the system is disabled, proceed as follows:
5. Use the same general procedure outlined in step 3, but test each Fire module. With the volt meter probes in place
(negative probe to terminal 23, positive probe to terminal 1), unplug each of the Fire modules one at a time, each time checking if the earth ground / system voltage has returned to 19V. Continue with the procedure in step 3 until the shorted wire is identified. Trace the wire run until the ground fault is found and remove it.
6. Confirm the earth ground terminal has returned to 19V.
7. Reconnect all wires to their correct terminals and reconnect all Modules. Place the Burg Service Jumper back to the
OFF position to restore Burglary system operation.
Test the system and resume normal premises operation.
NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 3
Page 18 Installation Instructions, Volume 3
B U R G L A R Y G R O U N D F A U L T T R O U B L E S H O O T I N G C H A R T
VDC between system and earth
ground
(negative probe terminal
23; positive probe terminal 1)
Motherboard
Terminal #
Accessory
Terminal #
Wire most likely shorted to earth ground (terminal 1)
16V
13V
14V-8V (pulsing when active)
3V
3.5V
Zero (0) Volts
24
10
1
1
2
8
1 or 3
1
3
7
9
GEMC-BSLC loop (+)
TAMP
BM BURG BELL (+)
BM AUX PWR (+)
BM REMOTE PWR (+)
BM REMOTE BUS GRN
BM REMOTE BUS YEL
BM BURG BELL (+)
GEMC-BSLC POINT ZONE (+)
BM BURG BELL (-)
BM REMOTE PWR (-)
F I R E G R O U N D F A U L T T R O U B L E S H O O T I N G C H A R T
VDC between system and earth
ground
(negative probe terminal
23; positive probe terminal 1)
31V
Motherboard
Terminal #
Accessory
Terminal #
1 or 3
Wire most likely shorted to earth ground (terminal 1)
GEMC-FW-SLC Loop (+)
26V
18V
16V
13V
14V-8V (pulsing when active)
10V
Zero (0) Volts
9
21
20
2
18
3
5
7
13
14
17
22
2
4
6
8
5
7
9
19
4
6
8
3
23
2 or 4
NAC A +
NAC B +
NAC C +
NAC D +
TBL SND +
TBL SND -
KEYSW (+)
AUX PWR +
REM PWR +
NAC A -
NAC B -
NAC C -
NAC D -
REMOTE BUS YEL
REMOTE BUS GRN
NAC A +
NAC B +
NAC C +
NAC D +
NAC A -
NAC B -
NAC C -
NAC D -
REM PWR -
AUX PWR -
GEMC-FW-SLC Loop (-)
NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 3
Installation Instructions, Volume 3
GEMINI C-SERIES (GEMC) CONTROL PANEL
FIRMWARE UPDATE INSTRUCTIONS
Page 19
Visit the Napco Technical Library
( tech.napcosecurity.com
) to find the latest versions of the Gemini C-Series (GEMC) firmware .hex file(s).
Search the website for "GEMC firmware"; when found, copy the .hex file(s) to a temporary folder in your local PC. Note: The below instructions are also located in the GEMC control panel installation instructions, WI1653 Volume 3.
UPDATING PROCESS
1. Run PCD-Windows Quickloader download software
(version 6.03 or greater) and open the Gemini C-
Series account for the control panel you wish to upgrade.
2. When first opened, Fire Quickloader Accounts are locked; to open, click Tools, Unlock the Fire Pro-
gram.
A warning popup appears, indicating "The Account
is locked, it will not allow changes...do you want
to proceed?" Click Yes to continue.
3. Click Tools, Firmware Download. The Firmware
Download dialog opens.
4. The .hex file name references the Micro number
(either Micro 1 or Micro 2; for example,
"ComboMicro1.hex"). Therefore, for the Micro number referenced in the file name, click the appropriate Browse button (within either the Micro 1 or the Micro 2 area) to locate the .hex file. Upon selecting the .hex file, the checkbox located to the right of the Browse button becomes active; check this checkbox and click Download.
As the firmware update process proceeds, the keypad display indicates a variety of text messages; during the final update loading process the display reads:
"Updating Flash 05P"
"05P" indicates "5% complete". The "05P" increments to "10P" and so on until the update process completes and the display reads "System Nor-
mal".
5. If two .hex files are available, repeat the previous step using the appropriate Browse button. If only one .hex file is available, skip to the next step.
6. When the download completes, verify the control panel was correctly updated by clicking the Ver-
sions button. To ensure the latest version information is retrieved, click Update and click OK to immediately communicate with the control panel.
WI2077
NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 3
Page 20
NOTES
Installation Instructions, Volume 3
NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 3
Installation Instructions, Volume 3
NOTES
Page 21
NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 3
Page 22
NOTES
Installation Instructions, Volume 3
NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 3
Installation Instructions, Volume 3 Page 23
FCC STATEMENT
This equipment generates and uses radio-frequency energy and, if not installed and used properly, that is, in strict accordance with the manufacturer's instructions, may cause interference to radio and television reception. It has been type tested and found to comply with the limits for a Class-B computing device in accordance with the specifications in Subpart J of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference in a residential installation.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: reorient the receiving antenna; relocate the computer with respect to the receiver; move the computer away from the receiver; plug the computer into a different outlet so that computer and receiver are on different branch circuits.
If necessary, the user should consult the dealer or an experienced radio/television technician for additional suggestions. The user may find the following booklet prepared by the Federal Communications Commission helpful: "How to Identify and Resolve Radio-TV Interference Problems". This booklet is available from the U.S. Government Printing Office, Washington, DC 20402; Stock No.
004-000-00345-4.
CAUTION: This equipment generates and uses radio-frequency energy. If not installed using conventional installation practices for RF devices, it may cause interference to radio and television reception. It has been tested and found to comply with the limits for a Class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference. However, there is no guarantee that interference will not occur in a particular installation. If it has been found to cause interference to radio or television reception, which can be determined by removing and reapplying AC and battery power to the equipment, the installer should try to correct the interference by one or more of the following measures: reorient the receiving antenna; connect the power transformer to a different outlet so that the control panel and receiver are on different branch circuits; relocate the control panel with respect to the receiver.
Warning: The use of non-NAPCO wireless devices with this control panel has not been evaluated by UL and voids the UL listing. In addition, the performance of these devices can not be guaranteed as compatible with NAPCO control panels. UL Listed to UL864 9 with GEMC-Series and other UL 864 9 th th
Edition when used in conjunction
edition Control Units as specified in the Control Unit Installation Instructions.
NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 3
Page 24 Installation Instructions, Volume 3
NAPCO LIMITED WARRANTY
NAPCO SECURITY SYSTEMS, INC. (NAPCO) warrants its products to be free from manufacturing defects in materials and workmanship for thirty-six months following the date of manufacture. NAPCO will, within said period, at its option, repair or replace any product failing to operate correctly without charge to the original purchaser or user.
This warranty shall not apply to any equipment, or any part thereof, which has been repaired by others, improperly installed, improperly used, abused, altered, damaged, subjected to acts of God, or on which any serial numbers have been altered, defaced or removed.
Seller will not be responsible for any dismantling or reinstallation charges.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, WHICH
EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF.
THERE IS NO EXPRESS OR IMPLIED WARRANTY OF
MERCHANTABILITY OR A WARRANTY OF FITNESS FOR A
PARTICULAR PURPOSE. ADDITIONALLY, THIS WARRANTY IS IN
LIEU OF ALL OTHER OBLIGATIONS OR LIABILITIES ON THE
PART OF NAPCO.
Any action for breach of warranty, including but not limited to any implied warranty of merchantability, must be brought within the six months following the end of the warranty period. IN NO CASE SHALL
NAPCO BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR
INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER
WARRANTY, EXPRESS OR IMPLIED, EVEN IF THE LOSS OR
DAMAGE IS CAUSED BY THE SELLER'S OWN NEGLIGENCE OR
FAULT.
In case of defect, contact the security professional who installed and maintains your security system. In order to exercise the warranty, the product must be returned by the security professional, shipping costs prepaid and insured to NAPCO. After repair or replacement, NAPCO assumes the cost of returning products under warranty. NAPCO shall have no obligation under this warranty, or otherwise, if the product has been repaired by others, improperly installed, improperly used, abused, altered, damaged, subjected to accident, nuisance, flood, fire or acts of God, or on which any serial numbers have been altered, defaced or removed. NAPCO will not be responsible for any dismantling, reassembly or reinstallation charges.
This warranty contains the entire warranty. It is the sole warranty and any prior agreements or representations, whether oral or written, are either merged herein or are expressly cancelled. NAPCO neither assumes, nor authorizes any other person purporting to act on its behalf to modify, to change, or to assume for it, any other warranty or liability concerning its products.
In no event shall NAPCO be liable for an amount in excess of
NAPCO's original selling price of the product, for any loss or damage, whether direct, indirect, incidental, consequential, or otherwise arising out of any failure of the product. Seller's warranty, as hereinabove set forth, shall not be enlarged, diminished or affected by and no obligation or liability shall arise or grow out of Seller's rendering of technical advice or service in connection with Buyer's order of the goods furnished hereunder.
NAPCO RECOMMENDS THAT THE ENTIRE SYSTEM BE
COMPLETELY TESTED WEEKLY.
Warning: Despite frequent testing, and due to, but not limited to, any or all of the following; criminal tampering, electrical or communications disruption, it is possible for the system to fail to perform as expected.
NAPCO does not represent that the product/system may not be compromised or circumvented; or that the product or system will prevent any personal injury or property loss by burglary, robbery, fire or otherwise; nor that the product or system will in all cases provide adequate warning or protection. A properly installed and maintained alarm may only reduce risk of burglary, robbery, fire or otherwise but it is not insurance or a guarantee that these events will not occur.
CONSEQUENTLY, SELLER SHALL HAVE NO LIABILITY FOR ANY
PERSONAL INJURY, PROPERTY DAMAGE, OR OTHER LOSS
BASED ON A CLAIM THE PRODUCT FAILED TO GIVE WARNING.
Therefore, the installer should in turn advise the consumer to take any and all precautions for his or her safety including, but not limited to, fleeing the premises and calling police or fire department, in order to mitigate the possibilities of harm and/or damage.
NAPCO is not an insurer of either the property or safety of the user's family or employees, and limits its liability for any loss or damage including incidental or consequential damages to NAPCO's original selling price of the product regardless of the cause of such loss or damage.
Some states do not allow limitations on how long an implied warranty lasts or do not allow the exclusion or limitation of incidental or consequential damages, or differentiate in their treatment of limitations of liability for ordinary or gross negligence, so the above limitations or exclusions may not apply to you. This Warranty gives you specific legal rights and you may also have other rights which vary from state to state.
I M P O R TA N T W I R I N G M E T H O D S
For single-conductor terminal
blocks (like the type shown at left), to terminate more than one conductor to a terminal, use the wiring methods shown at right:
In
Incorrect
Out
WIRE NUT OR
CRIMP
CONNECTOR
PIGTAIL
In
Correct -- Single incoming and/or pigtail with wire nut / crimp connectors
For "barrier" type terminal
blocks (like the type shown at left), to terminate two conductors to a terminal, use the wiring methods shown at right:
Incorrect
In Out
Correct -- Separate incoming and outgoing conductors
To terminate more than two conductors or conductors of different wire sizes to a terminal, use the "pigtail" type wiring method as shown at right. Use insulated wire for the pigtail, and firmly
PIGTAIL
secure the conductors to the pigtail using an ap-
NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 3
Incorrect
WIRE NUT OR
CRIMP
CONNECTOR
PIGTAIL
advertisement