SH 1/2 REV A WINDCHILL VERSION A.1
MOUNTING TO CONCRETE PAD
HOLE LOCATIONS FOR
OPTIONAL MOUNTING TO
A CONCRETE PAD
16 [5/8] DIA. CLEARANCE
HOLE (3) PLACES,
10 [3/8] DIA. MASONRY ANCHOR
BOLTS RECOMMENDED
521
[20.5]
FRONT OF UNIT
457
[18.0]
19.7
[7.7]
393
[15.5]
68
[2.7]
MAIN AC/CONTROL WIRING HOLE FOR 1 1/4" CONDUIT
MAIN AC/CONTROL WIRING HOLE FOR 3/4" CONDUIT
(
-REMOVE FACTORY PLUGS AND DISCARD
-CLOSE ANY UNUSED HOLE WITH A NEMA
3R RATED PLUG (FIELD SUPPLIED)
)
AUXILIARY SHUTDOWN SWITCH
WIRELESS MODULE
FUEL INLET : 1/2" NPT
REQUIRED FUEL PRESSURE : NATURAL GAS : 3.5-7" WATER COLUMN
LIQUID PROPANE (VAPOR) : 10-12" WATER COLUMN 635
[25.0]
345
[13.6]
733
[28.8]
218
[8.6]
REAR VIEW
648
[25.5]
LEFT SIDE VIEW
TITLE
ALL DIMENSIONS IN:
MILLIMETERS [INCHES]
SIZE
A
SCALE
INSTALL HSB GENERATOR ECOGEN WM
CAGE NO
N/A
NTS
DWG NO 10000037315
WT-KG N/A SHEET
REV
A
1 of 2
AIR INTAKE
SH 2/2 REV A WINDCHILL VERSION A.1
457 [18.0]
MINIMUM OPEN AREA
914 [36.0]
MINIMUM OPEN AREA
AIR OUTLET
"DO NOT LIFT BY ROOF"
TOP VIEW
914 [36.0]
MINIMUM OPEN AREA
AIR INTAKE
914 [36.0]
MINIMUM OPEN AREA
LIFTING HOLES 4 CORNERS: 30 [ 1.2]
- MUST BE LIFTED WITH STEEL RODS
- RECOMMENDED LIFTING ROD SIZE: 25 [ 1.0]
1218
[48.0]
RIGHT VIEW
INTAKE PANEL REMOVED
127 [5.0]
GRAVEL PAD/
COMPACTED SOIL
1232
[48.5]
FRONT VIEW
RIGHT SIDE VIEW
TITLE
ALL DIMENSIONS IN:
MILLIMETERS [INCHES]
SIZE
A
SCALE
INSTALL HSB GENERATOR ECOGEN WM
CAGE NO
N/A
NTS
DWG NO 10000037315
WT-KG N/A SHEET
REV
A
2 of 2