Trane VRF SVN59B Wired Remote Control Installation Instructions
The VRF SVN59B Wired Remote Control allows you to control one or multiple indoor units in a group. You can control cooling and heating, adjust temperature, select modes, and view error codes on the device's LCD display. The wired remote control supports features like tracking of individual units, configuration of settings, and communicating with the indoor units.
Advertisement
Advertisement
SAFETY WARNING TVCTRLTWRWD01T, TVCTRLTWRWD01A UNITS: inch (mm) Example with unconcealed cable 4 (102) Screw holes 3. Firmly secure the back cover of the remote control to the wall using the three provided screws. Example with concealed cable 6 (152) If you need more space, this panel can be removed. • Make all electrical connections in accordance with electrical codes and ordinances. • If you install the wired remote control with thermostat wire, remove 12 in. (30 cm) of the cable sheath and install only two of the conductors. The recommended wire size is AWG 18. • Use either the provided U-terminals or U-terminals that match the specifications of those provided. • Use an appropriate screwdriver for tightening the terminal screws. A screwdriver with a small head will strip the head and make proper tightening impossible. • Over-tightening the terminal screws may break them. • Tightening torque for M4 screws: 0.86–1.06 lbf·ft (12.0–14.7 kgf·cm). Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. Hazardous Voltage! F3 F4 Indoor unit terminals Wired remote control Wire (field supplied) V1 V2 F3 F4 F1 F2 Best Practice: Maintain consistent polarity with wiring connections (F3 to F3, F4 to F4) to minimize troubleshooting time. Observe the following requirements and precautions when making electrical connections. WARNING Connect communication wiring to the wired remote control at terminals F3,F4 and to the indoor unit at terminals F3,F4. Wiring UNITS: inch (mm) 6 Connecting Communication Wiring 0.76 (19.5) 5 4.72 (120.0) Dimensions 4 © 2014 Trane All Rights Reserved VRF-SVN59B-EN All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury. Proper Field Wiring and Grounding Required! WARNING Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards. Before installing/servicing this unit, technicians MUST put on all Personal Protective Equipment (PPE) recommended for the work being undertaken. ALWAYS refer to appropriate MSDS sheets and OSHA guidelines for proper PPE. When working with or around hazardous chemicals, ALWAYS refer to the appropriate MSDS sheets and OSHA guidelines for information on allowable personal exposure levels, proper respiratory protection and handling recommendations. If there is a risk of arc or flash, technicians MUST put on all necessary Personal Protective Equipment (PPE) in accordance with NFPA70E for arc/flash protection PRIOR to servicing the unit. Failure to follow recommendations could result in death or serious injury. Personal Protective Equipment Required! WARNING Figure 1. Cable Cable M4X16 User U ties clamps screws manual Installation terminals (2) (3) (5) (1) (6) manual (1) Wired remote control 2. Arrange the power cable and the communication cable so that they fit in the housing along the edges of the back cover. August 2014 NOTICE: alert against unsafe practices. Indicates a situation that could result in equipment or propertydamage only accidents. CAUTIONs could result in minor or moderate injury. It could also be used to Indicates a potentially hazardous situation which, if not avoided, WARNING could result in death or serious injury. Indicates a potentially hazardous situation which, if not avoided, Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment. Model Number: Wired Remote Control Variable Refrigerant Flow (VRF) System Components Table 1. Pre-installation 4.88 (124.0) Installation Instructions 2 1 Important: Environmental Concerns! Scientific research has shown that certain man-made chemicals can affect the earth's naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs. Important: Responsible Refrigerant Practices! Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them. 2.51 (63.8) 2 in. (50 mm) min. 0.4 in. (10 mm) min. UNITS: inch (mm) Wired remote control F1, F2 F3, F4 Indoor unit Wired remote control F1, F2 F3, F4 Indoor unit Wired remote control F1, F2 Wired remote control: Individual control example Outdoor Outdoor unit unit Figure 3. Individual control refers to the use of one wired remote control for controlling one indoor unit, as shown in Figure 3. Wiring for Individual Control Reassembling cover F3, F4 Indoor unit Reassemble the wired remote control by aligning the front cover with the top of the back cover and then tilting it downward, as show in the figure to the left. After replacing the cover, confirm that no wires are stuck in the gap between the front and back covers. Reassembling the Device 7 1. Insert a flat head screwdriver into the square groove at the center top of the remote control. Pull up the front cover to separate it from the back cover. Mounting the Unit Installation 0.4 in. (10 mm) min. 0.4 in. (10 mm) min. Figure 2. Clearances 3 F1, F2 Indoor unit F3, F4 F3, F4 Wired remote control Away/MDS 56 2. Using the up/down arrow buttons, select the appropriate main menu code by referring to Table 2. Press the right arrow button to display the sub-menu. 3. Using the up/down arrow buttons, select the appropriate sub-menu code by referring to Table 2. Press the right arrow button to display the current setting, which will represent either an option setting or a value, depending on the selected menu and sub-menu. 4. To change the digit 1 option setting, use the up/down arrow buttons. Press the right arrow button to move to digit 2. To change the digit 2 option setting, use the up/down arrow buttons. Repeat this procedure for digits 3–6. 5. To save settings and exit to the sub-menu, press the Set button. Sub-menu Digits: 1 2 3 4 Option settings/values (Refer to Table 2.) Wired remote control LCD display Main menu Figure 8. 1 4 3 2 1 Not used Blade setting/ checking Wireless remote control settings (2) Wireless remote control option settings (1) 0 0 2 3 Blade 2 Blade 3 0 0 1 Blade 1 4 — 5 Not used Blade 4 0 1 0 0 0 4 3 2 1 4 0 1 0 Temperature display Use of Auto mode Use of average temperature Temperature sensor selection Temperature unit 3 2 Master/slave wired remote control 1 Use of wireless remote control Factory default option setting/ value Digit Cooling/Heating selection Option description Option settings/values Main Submenu menu code code Table 2. 0: Unlock, 1: Lock 0: Unlock, 1: Lock 0: Unlock, 1: Lock 0: Unlock, 1: Lock — 0: Set temperature 1: Room temperature 0: Not used, 1: Use 0: Not used, 1: Use 0: Indoor unit 1: Wired remote control 0: Celsius (°C), 1: Fahrenheit (°F) 0: Master, 1: Slave 0: Not used, 1: Use 0: Cooling/Heating 1: Cooling only Option setting Note: To exit to normal mode without saving settings, press the Esc button. F3, F4 Indoor unit F1, F2 F1, F2 13 F3, F4 Indoor unit F1, F2 Outdoor unit Outdoor unit 1. Press the Set and Esc buttons simultaneously for > 3 seconds. The main menu will appear as shown in Figure 8. F3, F4 Indoor unit F1, F2 Outdoor unit Outdoor unit Wired remote control: Group control with multiple indoor units connected to different outdoor units 12 Wired remote control Indoor unit F1, F2 Wired remote control: Group control with multiple indoor units connected to one outdoor unit Indoor unit Outdoor Outdoor unit unit Figure 4. Group control refers to the use of one wired remote control to control multiple indoor units. • A maximum of 16 indoor units can be controlled as a group. • All indoor units in the group must be connected to a wired remote control. Examples of two different scenarios are shown in Figure 4 and Figure 5. 9 Figure 5. 8 Wiring for Group Control 3 2 F3, F4 F1, F2 F3, F4 Wired remote control (slave) Indoor unit EEV step Indoor unit option checking (1) 4 5 Use of central control Indoor unit EVAP OUT temperature Indoor unit EVAP IN temperature Indoor unit room temperature 3 2 1 Software version Software code 1 2 Note: This setting determines what occurs when a system reset is activated. 0 Factory defaults settings Not used 8 Not used Temperature increment/decrement (ºC) Number of connected units Number of indoor units Room temperature compensation Temperature compensation value Temperature control reference Option description 7 6 5 Indoor unit 1 1,2,3 1,2,3 1,2,3 1,2,3 1-6 1-6 1 1 3,4 1,2 4,5,6 1,2,3 — — — — — — — 0 0 — — 0 0 Factory default option setting/ value Digit Option settings/values (continued) Wired remote control (master) Outdoor unit — 0: Not used, 1: Use EEV step EVAP OUT temperature (°C) EVAP IN temperature (°C) Room temperature (°C) Software version Software code 0: Reset has no effect on settings 1: Reset changes settings to factory defaults 0: 1°C, 1: 0.5°C, 2: 0.1°C 0 – 16 -9.9–9.9°C Note: Increments of 0.1°C. -9–40°C (16–104°F) Option setting Two wired remote controls used for individual or group control Main Submenu menu code code Table 2. 14 Outdoor unit Figure 6. Two wired remote controls can control one indoor unit or a group of indoor units. In this application, one wired remote control must be configured as a master and one wired remote control must be configured as a slave. (Refer to the Configuration section in the indoor unit manual.) 10 Using Two Wired Remote Controls for Individual or Group Control Indoor unit tracking in progress Indicates tracking in progress 4 3 1 6 EEV stop step in heating Heating temperature compensation Filter time Indoor unit RMC address setting Indoor unit main address setting Note: Setting this option requires outdoor unit reset. Indoor unit main address checking Indoor unit option checking (2) Use of RPM compensation Use of external control Use of hot water coil Use of electric heater Use of drain pump Option description 5,6 3,4 1,2 5 4 3 2 1 4 3 2 — — — — — — — — — — — Factory default option setting/ value Digit Option settings/values (continued) Main Submenu menu code code Table 2. 15 RMC address (00–FE, hexadecimal) Main address (00–3F, hexadecimal) Main address (00–3F, hexadecimal) 0: 0/80 steps, 1: 80 steps 0-2°C, 1-5°C 0: 2000 hours, 1: 1000 hours 0: Not used, 1: Use 0: Not used, 1: Use 0: Not used, 1: Use 0: Not used, 1: Use 0: Not used, 1: Use Option setting To configure or verify option settings on a wired remote control, use the following procedure. Refer to Table 2 for option descriptions and corresponding menu codes. • If the unit does not support the function, “NONE” will be displayed. • In configuration mode, temperature value appear in Celsius. Configuration Total number of units discovered Figure 7. Note: If a system has master and slave wired remote controls, only the master displays the total quantity of discovered units. • When power is applied to a newly installed wired remote control, the device automatically begins tracking. • To repeat tracking at any time, press the Esc and Delete buttons simultaneously for at least 5 seconds. • If the number of connected indoor units is increased or decreased after installation, repeat the tracking process. The VRF system uses the term “tracking” for the process of indoor unit discovery and addressing. During tracking, the wired remote control display flashes to indicate that tracking is in progress. As units are discovered, the display shows the quantity on the left side (see Figure 7). Indoor Unit Tracking 11 6 5 1,2 3,4 Cooling discharge temperature Heating discharge temperature Fresh duct discharge temperature checking 5,6 1 Use of discharge temperature control Heating discharge temperature 6 Humidity setting/checkin g 3,4 3,4 AHU setting RPM setting/checkin g AHU discharge Cooling temperature discharge setting temperature Not used 3 2 1 4 Indoor unit option (2) setting/checking — — — — — — — — — Indoor unit option (1) setting/checking 3 1–24 (See note.) — Indoor unit option setting/checking Option description 2 Main Submenu menu code code 18–30°C (64–86°F) Note: Increments of 1°C. 15–25°C (59–77°F) Note: Increments of 1°C. 30–43°C (86–109°F) Note: Increments of 1°C. 8–18°C (46–64°F) Note: Increments of 1°C. 0: Not used, 1: Use 0: 30, 1 - 40, 2 - 50 0–31 steps Note: Increments of 1 step. Refer to the “Configuration” section in the indoor unit installation manual for a complete list of option settings and codes. Indoor unit option setting Option setting 3 Addressing reset 1 1 2 Reset 1 1 123 456 Power master reset Setting Checking Factory setting Master setting/ checking (F1F2 line indoor unit master) N/A 123 456 1 4 3 Master setting/checking (F3F4 line indoor unit master) 0 0 0 — — 0: Not used, 1: Reset 0: Not used, 1: Use, 2: Release address address Option setting Digit 20 * Digit 19 3 * * 1 2 Digit 8 Digit 7 Digit 14 * 0 Digit 13 Digit 2 Digit 1 * Digit 21 * Digit 15 * Digit 9 * Digit 3 * Digit 22 * Digit 16 * Digit 10 * Digit 4 * Digit 23 * Digit 17 * Digit 11 * Digit 5 * Digit 24 * Digit 18 * Digit 12 * Digit 6 Note: There are 24 available digits. The wired remote control can display only 6 digits at a time. The digits are displayed in 4 groups. Option setting codes are displayed with the first digit of the group a constant value—either 0, 1, 2, or 3—as shown in the table below. This value indicates the group that the digits currently being displayed belong to. 0 7 2 1 Option description Factory default option setting/ value Digit Option settings/values (continued) Main Submenu menu code code Table 2. Factory default option setting/ value Digit 17 Table 2. Option settings/values (continued) 16 Error code display example: Error 101 at indoor unit 200012 Error code display example: Error at wired remote control Note: For error codes on indoor/outdoor units, refer to the installation manual for each unit. Table 3 contains a list of error codes. Figure 10. If the wired remote control has an error, only the error code is displayed; no address is displayed. See the example in Figure 10. Wired Remote Control Error Figure 9. If an indoor or outdoor unit has an error, the address of the unit that has the error alternates in the display with the error code. See the example in Figure 9, in which E101 has occurred at indoor unit No. 200012. (A = indoor unit.) Indoor/Outdoor Unit Error Error codes for the wired remote control and the units connected to the wired remote control are displayed in the wired remote control LCD display. Errors Codes 18 Description © 2014 Trane All rights reserved VRF-SVN59B-EN 01 Aug 2014 Supersedes VRF-SVN59A-EN (15 Aug 2013) We are committed to using environmentally conscious print practices that reduce waste. The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. The manufacturer optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, the manufacturer offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.IRCO.com. - Memory error - No damper feedback Temperature sensor open/close error. Two or more wired remote controls are set as slaves. More than the maximum number (16) of indoor units installed. No communication between wired remote control and indoor units. No communication between master and slave wired remote controls. Communication error between wired remote control and indoor units after successful communication. Error codes and descriptions Display Table 3. 19 ">
Download
Advertisement
Key features
Group control of multiple indoor units
Individual control of one indoor unit
Temperature adjustment
Cooling and heating modes
Error code display
Indoor unit tracking
Configuration settings
Communication with indoor units
Frequently asked questions
A maximum of 16 indoor units can be controlled as a group, and they must be connected to a wired remote control.
Tracking is the process of discovering and addressing indoor units in the system. During tracking, the wired remote control searches for and identifies the connected indoor units.
You can configure options such as temperature settings, fan speed, mode selection, and other settings through the wired remote control's menus and options.