Signet 9950 Relay Module Instruction Sheet

*3-9900.093*

3-9950.091 Rev. 2 12/18 English

Instruction Sheet

Description

The 9950 off ers three types of relay module options. 3-9950.393-1 contains four mechanical relays. 3-9950.393-2 contains two mechanical relays and two solid state relays. 3-9950.393-3 contains two mechanical relays and four binary inputs.

The plug-in Relay Module may be installed either before or after the base unit is installed in the customer’s application. Always disconnect power from the 9950

Before adding or Removing any modules.

Relay Module Installation

The Relay Module plugs in and attaches with one screw.

1. It may be helpful to use a standard screwdriver to gently pry removable terminals away from the receptacle on the module.

2. Remove terminals from the module receptacle prior to installation.

Relay Module Removal

Note: Ensure power is disconnected from the 9950 and the Relay Module.

1. Remove the retaining screw from the relay module and set aside.

2. Insert the pluggable terminal blocks into the relay modules.

3. Grasp the pluggable terminal blocks and pull straight back from the 9950 until the module clears the 9950 base unit.

CAUTION:

Exercise care when installing or removing module. Do not bend connecting pins. Align pins and connectors then push module firmly into place, then attach with screw.

Avoid Electrostatic Discharge (ESD):

● Minimize handling of module to reduce the possibility of damage due to ESD.

● Handle module by the edges. Never touch any exposed circuitry or contacts.

● Wear an anti-static wristband or stand on an anti-static mat, or keep one hand touching a properly grounded pipe or other properly grounded piece of metal when handling module.

CAUTION: Switching active loads (most commonly inductive) can cause contact arcing sufficient to damage the relays. The RC Filter Kit or “snubber” (part number 3-8050.396) is available as an accessory to reduce or eliminate these damaging eff ects.

Relay Module Wiring

• Terminals accept 12 to 24 AWG wire.

• Strip 10 to 12 mm (0.4 to 0.5 in.) of insulation from wire tips and tin bare ends to eliminate fraying.

• Insert wire tip or ferrule completely into the terminal and secure with the screw.

• Do not allow any AC leads that may be connected to the internal relays to come in contact with low voltage wiring.

3-9950.393-1 and 3-9950.393-2

3-9950.393-1

Relay 1: The alarm is OFF during normal operation, and will go ON when relay energizes according to 9950

Relay settings.

RELAY 1

RELAY 2

NO 1

N/C 1

COM 1

NO 2

N/C 2

COM 2

ALARM!

AC or DC power Relay 4: The valve is ON during normal operation, and will go

OFF when relay energizes according to 9950 Relay settings.

NO = normally open (closes when energized)

NC = normally closed (opens when energized)

RELAY 3

RELAY 4

NO 3

N/C 3

COM 3

NO 4

N/C 4

COM 4

AC or DC power

Mechanical Relays Rating: 5A 250 VAC, 5A 30 VDC

Solid State Relays Rating: 50 mA 30V AC/DC

(for 309950.393-2 relay 1 &2)

Flow

Valve

3-9950.393-3

The alarm is OFF during normal operation, and will go ON when the relay energizes according to 9950 Relay settings.

Binary input 4 will be ON when the tank level is above the level switch, Binary Input 4 will be OFF when the tank level is below the level switch.

Binary Input Ratings

Maximum input voltage (without damage) 30 VDC

Minimum input voltage (without damage) -5 VDC (no operation below 0 VDC)

Maximum input voltage for signal

“Off” (low or "0")

Minimum input voltage for signal

“On” (high or "1")

1.5 VDC

3.0 VDC

Maximum current draw for signal “0” (low) <500 µADC

Minimum current draw for signal “1” (high) 500 µA

Typical current draw for signal “1” (high)

6.0 mA at 30 VDC, 4.8 mA at 24 VDC,

2.4 mA at 12 VDC, 1.0 mA at 5 VDC

Power

Switch

EXT

INT

If an externally powered sensor is connected with the

3-9950.393-3 module, set the power switch to the EXT position. The module can power external sensors by switching the power switch to the INT position.

Maximum power that can be drawn from the module is

6mA at 30 VDC.

Ordering Information

Mfr. Part No. Code

3-9950.393-1 159 310 268

3-9950.393-2 159 310 269

3-9950.393-3 159 310 270

RELAY 1

RELAY 2

No Connection

BINARY INPUT 1

BINARY INPUT 2

BINARY INPUT 3

BINARY INPUT 4

RELAY 1

RELAY 2

No Connection

BINARY INPUT 1

BINARY INPUT 2

BINARY INPUT 3

BINARY INPUT 4

Description

Relay Module with 4 Mechanical Relays

Relay Module with 2 Mechanical Relays and 2 Solid State Relays

Relay Module with 2 Mechanical Relays and 4 Binary Inputs

DC power

+

-

N/O 1

N/C 1

COM 1

N/O 2

N/C 2

COM 2

X

SW1

SW2

SW3

SW4

SW COM

N/O 1

N/C 1

COM 1

N/O 2

N/C 2

COM 2

X

SW1

SW2

SW3

SW4

SW COM

Level Switch

Level Switch

ALARM!

AC or DC power

Level

ALARM!

AC or DC power

Level

Georg Fischer Signet LLC, 3401 Aero Jet Avenue, El Monte, CA 91731-2882 U.S.A. • Tel. (626) 571-2770 • Fax (626) 573-2057

For Worldwide Sales and Service, visit our website: www.gfsignet.com • Or call (in the U.S.): (800) 854-4090

For the most up-to-date information, please refer to our website at www.gfsignet.com

3-9950.091 Rev. 2 12/18 English © Georg Fischer Signet LLC 2018

advertisement

Related manuals

Frequently Answers and Questions

What is the purpose of the GF Signet Type 9950 Relay Module?
The relay module offers three types of options: mechanical relays, solid-state relays, and binary inputs.
Can the relay module be installed before or after the base unit?
Yes, the relay module can be installed either before or after the base unit.
What is the procedure for installing the relay module?
To install the relay module, insert the pluggable terminal blocks, grasp and pull them back until the module clears the base unit.
What is the procedure for removing the relay module?
To remove the relay module, first ensure power is disconnected, remove the retaining screw, insert the pluggable terminal blocks, and pull back until the module clears the base unit.
What type of relay does the 3-9950.393-1 relay module contain?
The 3-9950.393-1 relay module contains four mechanical relays.
What is the rating for the mechanical relays?
The mechanical relays are rated for 5A 250 VAC and 5A 30 VDC.
What is the rating for the solid state relays in the 3-9950.393-2 relay module?
The solid state relays in the 3-9950.393-2 relay module are rated for 50 mA 30V AC/DC.
What are the input voltage requirements for the binary inputs in the 3-9950.393-3 relay module?
The binary inputs in the 3-9950.393-3 relay module require a minimum input voltage of 0 VDC and a maximum input voltage of 30 VDC.
How do I know when the tank level is above or below the level switch with the 3-9950.393-3 relay module?
When the tank level is above the level switch, Binary Input 4 will be ON, and when the tank level is below the level switch, Binary Input 4 will be OFF.