Delta Controls DSC-1280 Installation Manual
Delta Controls DSC-1280 is a fully programmable BACnet Building Controller with flexible communication options. It supports Twisted Pair Ethernet 10-BaseT using BACnet IP and BACnet over Ethernet, or an RS-485 LAN using the BACnet MS/TP protocol. This controller is ideal for a wide range of applications requiring no more than 12 inputs and 8 outputs, including HVAC systems, boilers, chillers, etc. It features a second RS-485 port that can be configured as an MS/TP SubLAN or a LINKnet network supporting up to 12 Delta BACstats or other LINKnet controllers.
Advertisement
Advertisement
INSTALLATION GUIDE DSC-1280 Rev 2.0a Installation Guide Document Edition 2.8 Product Description The DSC-1280 is a fully programmable, Native BACnet™ Building Controller that communicates on Twisted Pair Ethernet 10-BaseT using BACnet IP and BACnet over Ethernet, or on an RS-485 LAN using the BACnet MS/TP protocol. The controller includes an easy to mount enclosure and is designed for a wide range of applications requiring no more than 12 inputs and 8 outputs, including but not limited to Roof Top Units, Air Handlers, Boilers or Chillers, etc. A second RS485 port may be configured as an MS/TP SubLAN or a LINKnet network that supports up to 12 Delta BACstats or other Delta LINKnet controllers. Important Information ORCAview OWS and controller firmware must all be of the same version number (i.e. 3.33) to be compatible. When upgrading any of these products from older versions (i.e. 3.22 or 3.30), you must upgrade all the remaining products. Package Contents Product: DSC-1280 (Rev. 2.0a) DSC-1280 (Rev.2.0a) Installation Guide Related Documents Delta Controls Wiring Guidelines ORCAview Operator Guide ORCAview Technical Reference Manual Release Notes for related Firmware Document Edition 2.8 Delta Controls Cautions or Warnings This controller is an Electro-statically sensitive device. Proper ESD protection (ground strap) should be used when installing this product so that damage to the product does not occur. Danger of explosion if the battery is incorrectly replaced. Replace only with the same or equivalent type recommended by the manufacturer. Dispose of used batteries according to the manufacturer’s instructions. Replace the battery with type CR2032. Equipment damage or loss of data may occur if these procedures are not followed as specified. Installations requiring CE conformance: All wiring for CE rated products must use an extra low voltage (SELV) or protective extra low voltage (PELV) transformer. Use safety-isolating transformers, (Class II transformer) per EN61558. The transformer must be rated for 100% duty cycle. Mounting The DSC-1280 includes a plastic enclosure that can be quickly mounted with two screws (not provided). This controller should be mounted in an appropriate location within packaged equipment or another enclosure that meets code requirements. Page 2 of 11 Document Edition 2.8 Page 3 of 11 Delta Controls Board Layout Page 4 of 11 Document Edition 2.8 Controller Configuration Controller Type Various products have the capability of being configured as one of several possible controller types, which represents the network level that it will reside on in the network architecture (Area, System, Subnet). Other than the one controller acting as a router, all other controllers on the same network segment must be configured the same. AREA SYSTEM Area - Configures the controller as an Area level controller on a network. This is an option only on the Ethernet model and is the setting when the controller is connected to an Ethernet network (typically between buildings) and is acting as a router from one LAN to either a network of System controllers or Subnet controllers. SUBNET System - Configures the controller as a System level controller on a network of System controllers. This is the setting when the controller is connected to an Ethernet or BACnet MS/TP network with other System controllers or is a single head-end controller for a network of Subnet controllers. Subnet - Configures the controller as a Subnet level controller on a Subnet of similar controllers. This is the setting when the controller is connected to a BACnet MS/TP network with other Subnet controllers. Note: This also determines where the DIP or MAC address is mapped into the controllers BACnet address and which other portions of its BACnet address are inherited when DNA is enabled. Derived Network Addressing DNA The DNA jumper comes ON by default. This allows the controller to automatically configure a BACnet controller address. This should NOT be removed unless you are assigning a BACnet controller number through software. The BACnet controller number should not be confused with the DIP switch setting, and each controller must still have a unique dip switch address even when using software to define the controller number. Controller Addressing The Dip Switch is a binary switch. Each individual DIP switch represents a unique value, which forms the controller address when added together. To set the address, simply move the switches that add up to the controllers desired address to the ON position. Example: If the controller is to be address 5 on the network, set the switch numbered 4 and the switch numbered 1 (equals 5) to the On position. Note: Each controller on the same MS/TP segment must have a unique DIP switch address. Page 5 of 11 Delta Controls Wiring General All wiring must conform to NEC and local codes and regulations. Use earth ground isolating step-down Class 2 transformers. Do not use autotransformers. Determine supply transformer rating by summing total VA of product and output loads. Risk of Electric Shock or Fire More than one disconnect switch may be required to de-energize the equipment before servicing. Input Class 2 Power Supplies are interconnected. Use only Class 2 sources suitable for interconnections. All terminals are acceptable for Class 2 Circuit connections only Use copper conductors only Apply minimum 6.0 lb-in torque for tightening field wires into the terminal blocks Power This product is designed to use a 24VAC Class 2 power supply. A single transformer may be used to power multiple controllers and/or auxiliary field devices (actuators, etc.) provided the following conditions are met: All devices MUST be ½ wave rectified. Mixing power between ½ wave and full wave rectified devices will damage both the transformer and connected equipment. The transformer is properly sized, including line losses for the total VA requirements. Polarity is observed between controllers (with respect to 24~ and Gnd). Each controller is grounded as shown in the diagram below. This is important to protect equipment and ensure a common ground reference for RS-485 communications. The transformer secondary is fused for its maximum rated load (4A max for Class 2 circuits). Make sure to ground the controller using the ground lug that is available on the controller. The controller uses the ground lug to establish a common reference for communications. If the controller is not grounded then communication problems may occur. Page 6 of 11 Document Edition 2.8 Network Communication The controller communicates on Twisted Pair Ethernet 10-BaseT using BACnet IP and BACnet over Ethernet, or on an RS-485 LAN using the BACnet MS/TP protocol. Refer to Delta Controls Wiring Guidelines for further details. MS/TP (RS485) Wiring For detailed information on MS/TP and LINKnet wiring refer to Delta Controls Wiring Guidelines. The proper specified cabling must be used to ensure reliable communications. (22-24 AWG twisted pair, 100-120 ohms impedance, 17 pF/ft or lower capacitance, with a braided or aluminum foil shield.) Controllers should always be wired together in a daisy-chain fashion. Attempting to connect them using a starred or bus configuration will cause problems on the network. Networks with a total length greater than 4000 ft or with more than 50 controllers require a repeater (RPT-768). LINKnet networks that have only 1-2 controllers, and have less then 100 ft of cable length do not require network terminators. Input and Output Wiring Inputs and outputs on the DSC-1280 controller follow the same general wiring connection diagrams as other Delta Controls products. Refer to separate documentation for additional details. Input Configuration The input must be configured to accept the signal used by the input device. Place the jumper for each input in the correct location on the Input Type Selector Block. The diagram to the right shows the factory default selection of 10 KΩ. 4-20mA For sensors that use a 4 to 20 mA signal. 10K For 10 KΩ Thermistor temperature sensors, as well as Dry Contact binary inputs. 5V For sensors that use a 0 - 5 VDC signal. 10V For sensors that use a 0 -10 VDC signal. Page 7 of 11 Delta Controls HAND OFF Each HOA switch is HAND, OFF, AUTO from right to left. The HAND position allows a user to manually force the output on, the OFF position allows a user to manually force an output off, and the AUTO position allows the output to be controlled automatically by the controller. AUTO Output Configuration Indicators LED Function Description Power Controller Power Indicator This yellow LED turns on to indicate that the controller has power applied. Scan CPU Scan Indicator This red LED flashes at a rate relative to the CPU scan rate. Network (Ethernet) Ethernet Communication Status Indicators The green LNK LED is turned on when a link is established between two Ethernet devices. (for example, controller, computer, switch, etc.) The green ACT LED flashes when communications are active. Network (NET1) MS/TP (RS485) Communication Status Indicators The green LED flashes to indicate when the controller is transmitting out the port, and the red LED flashes to indicate when the controller is receiving data through the port. If communication is good, both LEDs will flash at a high rate. Network (NET2) MS/TP (RS485) Communication Status Indicators The green LED flashes to indicate when the controller is transmitting out the port, and the red LED flashes to indicate when the controller is receiving data through the port. If communication is good, both LEDs will flash at a high rate. Inputs (IP1 – IP12) Input Status Indicators A corresponding red LED varies in intensity and is brightly lit when the associated input is receiving a low voltage input signal (i.e. a closed contact, 0 VDC, 4 – 20 mA or a high temperature reading or low resistance). Outputs (OP1 – OP8) Output Status Indicators A tri-color LED is used. Under automatic control, the corresponding output LED is green and is on or off to match the status of an associated binary output. The LED will also vary in intensity relative to the output signal for an analog output. With HOA switches, the output LED is red in the OFF position and yellow in the HAND position. Product Specifications Power Requirements 24 VAC 50/60Hz or 24 VDC Class 2 Power Consumption 25 VA Ambient Ratings 32° to 131°F (0° to 55°C), 10 to 90% RH (non condensing) Page 8 of 11 Document Edition 2.8 Communication Ports Ethernet 10 BaseT @ 10Mbps BACnet IP, BACnet over Ethernet NET1 BACnet MS/TP (RS-485) Communication: 9600, 19200, 38400, 76800 bps (Default) Maximum of 99 controllers LINKnet Communication: 76800 bps Maximum of 12 LINKnet controllers including up to two DFM controllers BACnet MS/TP (RS-485) Communication: 9600, 19200, 38400, 76800 bps (Default) Maximum of 99 controllers LINKnet Communication: 76800 bps Maximum of 12 LINKnet controllers including up to two DFM controllers Serial RS-232 BACnet PTP Communication: 9600 (default), 19200, 38400 Service Port RJ-11 Jack Used with Delta Controls service tool devices (for example, CON-768) OR NET2 OR Inputs 12 Universal Inputs (10 bit), jumper configurable for the following input types: 0-5 VDC 0-10 VDC 10 KΩ Thermistor Dry Contact (using 10 KΩ Thermistor jumper setting) 4-20 mA Outputs 8 Universal Outputs c/w LED status indication (including HOA status) 0-10 VDC @ 20 mA maximum per output Software configurable as binary or analog Hand/Off/Auto Switches (c/w position feedback) Technology 32 bit processor 2 MB (16 megabit) Flash Memory 512 KB SRAM memory Listings UL 916 Listed BTL Listed (with V3.30 Release 3 firmware only) Compliance CE FCC Page 9 of 11 Delta Controls CE - DECLARATION OF CONFORMITY according to ISO/IEC Guide 22 and EN 45014 Manufacturer's Name: Delta Controls Manufacturer's Address: th 17850 56 Avenue Surrey, British Columbia Canada V3S 1C7 declares that the product (s): Product Name: 12 x 8 System Controllers Model Numbers: DSC-1280 Product Options: All conforms to the following Product Specifications: EN 50081-1:1992 Generic Emission Standard Part 1: Residential EN 55022:1998 Radiated and Conducted Emissions EN 61000-3-3:1998 Power Line Fluctuations Class A Pst < 1, Plt < 0.65 EN 50082-1:1997 Generic Immunity Standard Part 1: Residential EN 61000-4-2:1995 ESD Immunity EN 61000-4-3:1996 RF Electromagnetic Field Immunity ENV 50204:1995 RF Electromagnetic Field Immunity (Keyed Carrier) EN 61000-4-4:1995 EFT/Burst Immunity EN 61000-4-5:1995 Surge Immunity EN 61000-4-6:1996 Conducted Immunity EN 61000-4-11:1994 Voltage Dips / Interruptions Level B Level A Level A Level B Level B Level A Level B/C/C Supplementary Information The product(s) herewith comply with the requirements of the EMC Directive 89/336/EEC. The product(s) were tested in a typical configuration. Lee Dickson Quality Assurance Manager Page 10 of 11 Document Edition 2.8 FCC Compliance Information This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. Industry Canada Compliance Statement ICES-003 This Class A digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations Cet appareil numérique de la Classe A Respecte toutes les exigences du Règlement sur le matérial brouiller du Canada. This product conforms to the following UL requirements: UL916: Energy Management Equipment Page 11 of 11 ">
Download
Advertisement
Key features
Fully programmable
BACnet Building Controller
Ethernet & RS-485 communication
12 inputs & 8 outputs
MS/TP SubLAN & LINKnet support
Frequently asked questions
The DSC-1280 supports BACnet IP, BACnet over Ethernet, and BACnet MS/TP protocol.
A maximum of 99 controllers can be connected on a MS/TP network.
The DSC-1280 supports up to 12 LINKnet controllers, including up to two DFM controllers.