VENTILATORS VE30100 Installation And Operation Manual

Add to My manuals
20 Pages

advertisement

VENTILATORS VE30100 Installation And Operation Manual | Manualzz
VENTILATORS
MODELS:
VH30100 30-100 CFM HRV
VE30100 30-100 CFM ERV
Features
• Three operating modes
(Intermittent, Continuous and High)
• 100% variable speed
VH30100 COMPACT
HEAT RECOVERY VENTILATOR
VE30100 COMPACT ENERGY
RECOVERY VENTILATOR
Installation and Operation Manual
• Quick-connect duct collar system
• Proportional defrost sequence
• Single-person mounting system
• Dual permanently lubricated PSC motors
• Integral balancing taps in duct collars
• Wall-mounting bracket included
i
IMPORTANT: READ AND SAVE THESE INSTRUCTIONS. THIS GUIDE TO BE LEFT WITH EQUIPMENT OWNER.
IO-VENT-SS
WWW.CLEANCOMFORT.COM
7/17
Supersedes 8/15
TABLE OF CONTENTS
SAFETY CONSIDERATIONS ................................. 3
VENTILATION REQUIREMENTS ......................... 4
Determine Your Ventilation Needs
4
FITTING EQUIVALENT LENGTHS ....................... 5
TYPES OF INSTALLATIONS ................................ 6
Independent System installation
6
Exhaust at the Source and Supply in the Return
6
Exhaust and Supply in the Return
7
Installation Kit
7
Finding a Suitable Installation Area HRV or ERV
7
INSTALLATION ................................................... 8
Installation of the HRV / ERV
8
Insulated Flex from Unit to Outside Wall
8
Condensation Drain Line
9
Supplying Power to the HRV/ERV
9
Installing Ventilation Hoods
10
MATRIX™ Ventilation Hoods
10
CONTROLS WIRING .......................................... 11
Controls Connection
11
Wiring Diagrams for Furnace interlock systems
11
Alternate Forced-air Interlocking Wiring
12
SEQUENCE OF OPERATIONS ............................ 13
Sequence of Operations for Ventilator and
Connected Wall Controls and Timer
i CAUTION!
Do not install in a cooking area or connect directly
to any appliance. Turn off all integral disconnects
before servicing.
Notice: Prior to installing, serious consideration must
be taken to ensure this ventilation system will operate
properly if integrated with any other type of mechanical
system such as a forced air system or an air handling unit.
To ensure proper operation and compatibilities of both
systems, the airflows of the Heat Recovery Ventilator
(HRV) or Energy Recovery Ventilator (ERV) must be
balanced by the installer, by following the procedures
found in this manual.
The way in which your HRV/ERV is installed may make a
significant difference to the electrical energy consumed
when operating. To minimize the electricity use of the
HRV/ERV, a stand-alone fully ducted installation is
recommended. If you choose a simplified installation that
operates your furnace or air handler for room-to-room
ventilation, electrical energy consumption and operating
cost will be greatly reduced if the blower of the system's
furnace or air handler has an electronically commutated
(ECM) motor.
Limitations: The product is for residential applications
only and must be installed in accordance with all national
and local regulations, building and safety codes.
13
VENTILATION CONTROL .................................. 13
*INSTALLATION DATE (MM/DD/YYYY)
BALANCING THE UNIT ..................................... 14
________________________________________________________________
TROUBLESHOOTING ........................................ 16
MODEL#: _____________________________________________________ MAINTENANCE ................................................. 17
SERIAL #: _____________________________________________________
WARRANTY ....................................................... 18
*Ask Dealer to provide this information.
(
/
/
)
Proprietary Notice
This document and the information disclosed herein are
proprietary data of Daikin North America LLC. Neither this
document nor the information contained herein shall be
reproduced, used, or disclosed to others without the
written authorization of Daikin North America LLC except
to the extent required for installation or maintenance
of recipient’s equipment.
Liability Notice
Our continuing commitment to quality products may
mean a change in specifications without notice.
© 2015 DAIKIN NORTH AMERICA LLC
All rights reserved.
Houston, Texas • USA
www.cleancomfort.com
1-888-724-5211
Daikin North America LLC does not accept any liability for
installations of ventilation equipment installed by unqualified
personnel or the use of parts/components/equipment that are
not authorized or approved by Daikin.
2
WWW.CLEANCOMFORT.COM
IO-VENT-SS
SAFETY CONSIDERATIONS
i= WARNING!
• To reduce the risk of injury, disconnect power to the
ventilation system while performing service on the
unit. There are impeller wheels turning at a very high
speed that must fully stop rotating prior to accessing
the inside of the unit.
• To reduce the risk of electric shock or fire, do not
perform any service to the HRV system other than as
stated in the operating manual instructions.
• To reduce the risk of electric shock, this ventilation
system comes equipped with a 3-prong plug. This plug
will fit in a polarized 120VAC outlet in only one orientation. Do not modify the power plug in any way;
if modified, there is risk of electric shock or fire.
• Do not use the ventilation system for removal of
flammable fumes, gases or connect directly to any
appliances.
• Do not modify, repair or disassemble this system.
These tasks are to be performed by authorized serviced
personnel only. Fire, electrical shock and/or bodily injury
may result if these warnings are not followed.
• Always assess the operation of the ventilation system
with regard to how it may interact with vented
combustion equipment (e.g. gas furnace, oil furnace,
combustion appliances)
i CAUTION!
• Do not use this ventilation system for outdoor
applications. The electrical components in this
ventilation system are only certified for indoor use.
• Do not pull or twist the ventilation system's power
cord when disconnecting it from the power receptacle.
Grasp the plug firmly, not the cord.
• Do not obstruct or cover the air intake or air outlet of
the ventilation system.
• Do not use for ventilation of areas with swimming
pools or spas.
IO-VENT-SS
WWW.CLEANCOMFORT.COM
3
VENTILATION REQUIREMENTS
Determine Your
Ventilation Needs
Good indoor air quality is based
in part on the capacity of the
home’s ventilation system.
The two most common
methods for determining the
ventilation needs of a home are
the Room Count Calculation
method and the Air Change
Per Hour method. Both
methods calculate an
approximate ventilation rate
(in CFM or L/s). Their calculation
methods are described on
this page.
A. Room Count Calculation Method
LIVING SPACE
Master Bedroom
NUMBER OF ROOMS
CFM (L/S)
CFM REQUIRED
————
x 20 cfm (10 L/s)
=
————
Basement
————
x 20 cfm (10 L/s)
=
————
Single Bedroom
————
x 10 cfm (5 L/s)
=
————
=
————
Living Room
————
x 10 cfm (5 L/s)
Dining Room
————
x 10 cfm (5 L/s)
=
————
Family Room
————
x 10 cfm (5 L/s)
=
————
Recreation Room
————
x 10 cfm (5 L/s)
=
————
Other
————
x 10 cfm (5 L/s)
=
————
Kitchen
————
x 10 cfm (5 L/s)
=
————
Bathroom
————
x 10 cfm (5 L/s)
=
————
Laundry Room
————
x 10 cfm (5 L/s)
=
————
————
x 10 cfm (5 L/s)
=
————
Utility Room
TOTAL ventilation requirement (add last column)
=
1 CFM = 0.47189 L/s
1 L/s = 3.6 m3/hr
B. Air Change Per Hour Calculation Method
TOTAL volume of the house (in cubic feet) X 0.35 air changes/hour = CUBIC FT/HR
Take total CUBIC FT/HR and divide by 60 to get CFM
Example: A 25'x 40' house with basement:
25' X 40' = 1,000 sq. ft.
1,000 sq. ft. x 8' room height x 2 storeys
(1st floor + basement) = 16,000 cu. ft.
16,000 cu. ft. x 0.35 ACH = 5,600 cu. ft.
5,600 cu. ft. / 60 = 93.3 CFM
93.3 CFM is your ventilation requirement
4
WWW.CLEANCOMFORT.COM
IO-VENT-SS
FITTING EQUIVALENT LENGTHS
• Flex pipe equivalent length
is smooth pipe x2
• Flex fitting equivalent length
is smooth fitting x2
• 90° perimeter pipe elbow
equivalent length = 10 ft.
(3.0 m)
NOTE: Where flex duct is used
• 45° perimeter pipe elbow
equivalent length = 5 ft.
(1.52 m)
NOTE: Where flex duct is
used to make 45º elbow
equivalent length =
10 ft. (3.0 m)
• Round wall cap spring
damper or screen
equivalent lengths =
60 ft. (18.29 m)
to make 90° elbow equivalent
length = 20 ft. (6.1 m)
• Y-equal sides equivalent
length = 10 ft. (3.0 m)
• Y-Side branch
equivalent length =
35 ft. (10.7 m)
• Angle boot equivalent
length = 30 ft. (9.14 m)
• Tee take-off equivalent
length = 50 ft. (15.24 m)
• Wall grille 50% free area
equivalent length = 15 ft.
(4.6 m)
• Increaser/Reducer
equivalent length
= 8 ft. (2.43 m)
• Round plastic diffuser
equivalent length = 100 ft.
(30.5 m)
NOTE: Maximum airflow
assumes diffuser is in full
open position.
IO-VENT-SS
WWW.CLEANCOMFORT.COM
5
TYPES OF INSTALLATIONS
Independent System Installation
From an Indoor Air Quality standpoint, this is the preferred method of installing a ventilation system in a home.
This installation uses a dedicated duct system for both the
supply of fresh air and exhausting of stale air accumulated
in the home.
With an Independent System installation, fresh air is
supplied to all bedrooms and living areas and stale air is
exhausted from the bathroom, kitchen and laundry room.
See Figure 1.
Important: For correct performance of your HRV or ERV,
the installation of a 6" round galvanized backdraft damper is
required on the ductwork supplying fresh air to the home.
Figure 1
Exhaust at the Source and Supply
in the Return
This application uses a dedicated duct
system for exhausting the stale air
from the home. The fresh air is routed
to the return air duct and is distributed
through the home by the existing
supply air ductwork of the forced-air
system. See Figure 2.
From Bathroom
or Kitchen
To living space
A
6'
(1.83 m)
B
18" (457 mm)
HRV / ERV
Make sure when using this installation that
your fresh air duct connection to the forced
air system return air duct is not less than 10ft (3 m)
upstream of the return plenum connection to the
forced-air system. Check with your local building codes
or the manufacturer of the forced-air system. The HRV
and forced-air system must be set to operate in continuous mode to achieve maximum comfort and to avoid
cross-contamination.
Note to Installer: Dwellings with multiple forced-air
systems require one HRV/ERV per system.
Ensure the unit runs in conjunction with the forced-air
system. Refer to wiring diagram for furnace interlock
instructions.
6
Forced-air System
A+B=NOT LESS THAN 10FT (3 M)*
Figure 2
* For minimum distance between return and forced-air system, check with
your local building codes or the manufacturer of the forced-air system.
Important: The duct bringing outdoor air to the
return air plenum must be equipped with a manual
damper to balance the outdoor airflow.
Important: For optimal performance of your HRV or
ERV, the installation of an optional 6" round galvanized
backdraft damper is required on the fresh-air-to-home
duct work. When performing duct connections, always
use approved tools and materials. Also use steel duct
connections for this type of installation.
WWW.CLEANCOMFORT.COM
IO-VENT-SS
TYPES OF INSTALLATIONS
Exhaust and Supply in the Return
When using this installation, make sure that there is
minimum of 3 feet (0.9m) between the fresh air
and exhaust air connections of the HRV/ERV in
the return air duct. See Figure 3. Make sure
when using this installation that the fresh air duct
connection to the forced-air system return air
duct is not less than 10ft (3 m) upstream of the
return plenum connection to the forced air system.
Check with your local code or the forced air system's
manufacturer. The HRV and forced-air system must be
set to operate in continuous mode to achieve maximum
comfort and to avoid cross-contamination.
Note to installer: Dwellings with multiple forced-air
systems require one HRV/ERV per system.
Ensure the unit runs in conjunction with forced-air system.
Refer to wiring diagram for furnace interlock instructions.
Important: Building and combustion appliance installation codes
do not allow return air grilles or
openings such as "breather tee" or
indirect connections in an enclosed
room that is susceptible to spillage of
combustion appliances.
Simplified Connection
A
6'
(1.83 m)
To living space
B
18" (457 mm)
Forced
Air System
HRV / ERV
Figure 3
* For minimum distance between return and forced-air system, check with
your local building codes or the manufacturer of the forced-air system.
Important: The duct bringing outdoor air to the return air
plenum must be equipped with a manual damper to balance the
outdoor airflow.
Indirect Connection
Breather Tee
2"
(51 cm)
Important: For optimal performance of your HRV or ERV,
the installation of an optional 6" round galvanized backdraft
damper is required on the fresh-air-to-home duct work. When
performing duct connections, always use approved tools
and materials. Also use steel duct connections for this
type of installation.
Installation Kit
Installation Kit Includes:
• 4 Collars
Finding a Suitable Installation Location
• 12 screws (#10 x 11/4”)
• 4 Caps, Pressure Taps
• 2 screws (#8 x 3/8”)
• 1 Condensation Drain Line • 120VAC power cord
• 1 Drain Adapter with Nut
• Wall-Mounting Bracket
The HRV/ERV unit should be installed in a mechanical room
or as close to an outside wall as possible. This would ensure
a short run of insulated flexible duct.
The HRV/ERV unit must always be installed in an area where
the air is tempered to avoid freezing of the condensate
line. The contractor should install the unit in an area that
is accessible to allow the homeowner easy access for for
performing maintenance.
It is very important to install an electric receptacle (120VAC)
near the HRV/ERV. A separate circuit breaker is also recommended. Installing the HRV/ERV close to a drain for the
condensate would avoid the need for a condensate pump.
Figure 4
Tip to Installer: Removing the core unit will facilitate
your installation.
IO-VENT-SS
WWW.CLEANCOMFORT.COM
7
INSTALLATION
Installation of the HRV/ERV
IMPORTANT Minimum installation requirements:
a) Minimum two 2"x 4" (50.8 mm x 101.6 mm) wood
wall studs and minimum ⅜" (9.5 mm) thick drywall is
required to secure the HRV/ERV wall bracket.
b) Support for weight of 80 lbs, which includes HRV/
ERV, duct connections and accessories. Proper installation requires that the unit be secured to the wall. If
there are no wall studs available, secure a sheet of ¾"
plywood to wall then fasten wall mounting bracket
to plywood.
Tip to installer: If the unit is not level, improper
drainage will occur and could lead to moisture and
leakage problems.
It is recommended that approximately 16 inches of flexible
duct be installed between the HRV or ERV and your rigid
duct. The flexible duct is connected to the HRV or ERV in
the same way as the insulated flex.
NOTE: Clean Comfort Ventilators (HRV/ERV) that use a
fan shut down defrost sequence for frost protection are
NOT equipped with a motorized outdoor air damper.
Special consideration is required when one of the following types of installations is chosen:
a) Exhaust at the source and supply in the return air duct,
or
b) Exhaust and supply in the return air duct
The HRV/ERV must operate in the continuous ventilation
mode to avoid cold, unconditioned air being introduced
through the unit and directly into the furnace during
heating season. However if the homeowner chooses to
run the unit in Intermittent (“INTER”) mode or turn it
“OFF”, cold supply air will be drawn in through the HRV/
ERV when the system’s blower fan is operating e.g. during
a heating cycle. We recommend installing a motorized
damper between the HRV/ERV supply air connection
and the furnace’s return air duct that will automatically
close when the HRV/ERV is not operating. You may also
consider the installation of a backdraft damper on the
ventilator’s exhaust air connection to prevent cold air
infiltration.
Alternatively, installing a ventilator that employs a
recirculating defrost sequence and is equipped with
an integrated motorized outdoor air damper, such as
the VH30120R or VH30160R, would avoid the problem
described above.
Figure 5 Installation of the wall bracket. Secure with two
#10 x 11 ⁄4" screws.
Figure 6 Hang HRV/ERV on
the wall-mounting bracket.
Insulated Flex from Unit to Outside Wall
Tip to installer: To ensure a better installation and to
avoid an undesired bend in the duct, align the flexible duct
with the collar before securing over the four hooks on the
inner surfaces of the collar.
Figure 7 Before completing
the installation, make sure
that the HRV/ERV is level.
All ducting to and from the HRV/ERV must be adequately
insulated to minimize heat loss and gain. All tapes,
mastics, and nonmetallic clamps used for field installation
of flexible ducts shall be listed and labeled to Standard UL
181B - Closure Systems for Use With Flexible Air Ducts and
Air Connectors.
Once insulated flex is attached to the collar, slide collar into
the keeper section and attach collar to the unit with four,
#10 x 5/8" screws supplied in installation kit to ensure a
proper seal. See Figures 9-13 on following page.
Figure 8 Secure HRV/ERV to
wall-mounting bracket with
the two, #8 x 3⁄8" screws.
8
WWW.CLEANCOMFORT.COM
IO-VENT-SS
INSTALLATION
Figure 9 Insert flexible duct
over the hooks and seal with a
tie wrap.
Figure 10 Insert insulation inside
Figure 11 Finish by taping the
vapor barrier to the collar to
ensure proper seal.
Figure 12 Slide collar into the
keeper section of the unit.
the double collar.
Figure 14 Create a trap by forming a loop in the condensate tubing.
Ensure this trap will not be exposed to temperatures where the
condensate can freeze.
Figure 13 Fix and secure the collars
to the HRV/ERV with the #10 x 11⁄4"
screws, supplied in kit.
CAUTION! Always consult
your national and local
regulations, building and
safety codes.
i WARNING!
Always secure the 5" detachable collars with the screws
provided. If this is not done, condensate may accumulate
inside the ventilator causing damage.
Condensation Drain Line
Insert the threaded drain adapter through the bottom of the
HRV/ERV and hand tighten the plastic nut supplied with the
installation kit. Use a wrench to tighten the nut another half turn
to ensure a complete seal.
Figure 15 Use a condensate pump if you don’t have access to a drain.
Supplying Power to the HRV/ERV
IMPORTANT: Only qualified service technicians should
install, repair, or service this HRV/ERV.
NOTE: If the LED light on the unit's control is lit (green),
but the unit's motors do not energize and the controls do
not operate, this indicates that the polarization in the main
power supply outlet is inverted. Correct polarity of supplied
power before continuing with the installation.
Daikin recommends that the unit be connected to a dedicated 120VAC receptacle; use of an extension cord to power
the unit is not recommended. If no receptacle is available
near the unit, have a licensed electrician install one.
Install the condensate line (included in installation kit) by
pushing the clear plastic tubing over the drain adapter. Make
a condensate trap by looping the clear plastic tubing. The
function of this condensate trap is to prevent unpleasant odors
from entering the HRV/ERV. See Figures 14-15.
Figure 16 Insert the power cord on top of the unit.
Press firmly to make sure the power cord is secure.
IO-VENT-SS
WWW.CLEANCOMFORT.COM
9
INSTALLATION
Installing Ventilation Hoods for
Fresh Air and Exhaust
Install the outside ventilation hoods at least 18 inches
(0.5 m) above ground level or above the anticipated
snow level, and we recommend with at least 6 ft
(1.8 m) between the fresh air intake and the exhaust.
6ft (1.83 m)
Always properly seal the supply and exhaust hoods to
the exterior of the thermal envelope of the building
with caulk or other similar material to inhibit air leakage.
18" (457 mm)
Note: Fresh air intake hoods shall be located to avoid
combustion sources or sources of pollutants such as:
• Exhaust air vents from
this HRV/ERV, a clothes
dryer or combustion
appliances
• Driveways (auto exhaust)
• Garbage containers
• Attics or crawl spaces
• Under deck or other
areas of questionable
air quality
IMPORTANT: Always consult your national
and local regulations, building and safety codes.
Figure 17 Locating
Outside Hoods
• Gas meters, oil fill pipes
Matrix™ High-Performance Ventilation Hood
Exterior wall
Installation
Important: Install ventilation hood a minimum of 18"
(457 mm) above ground level or the anticipated snow
level.
Fresh air to home
“BOTTOM”
Do not install under a deck, enclose porch, patio,
garage, crawl space or attic.
i
Exhaust air from home
“TOP”
Exhaust air
to outside
Unique design with individual insulated
transition duct (UL 94 Rated)
WARNING!
hood is for residential applications of
110 CFM or less ONLY.
It must be installed in accordance with
all current national and local regulation
building and safety codes.
Fresh air from outside
Airflow
Airflow Performance Data
Exhaust Airflow Performance
Supply Airflow Performance
0.25
0.25
External Static Pressure
in wg (Pa = n x 248.36)
Limitations: The Matrix ventilation
External Static Pressure
in wg (Pa = n x 248.36)
Airflow Performance Data
Transition
connector plate
Ventilation
cap
Ensure the ventilation hood is installed with a minimum
clearance of 6 ft (1.83 m) away from the exhaust vents
of a combustion source or a source of pollutants such as
a gas furnace, dryer, gas boiler, range hood, barbecue,
garbage bin, driveway or garage..
0.2
0.15
0.1
0.05
0
30
45
60
75
90
105
CFM (L/s = n x 0.4719)
120
0.2
0.15
0.1
0.05
0
30
45
60
75
90
105
120
CFM (L/s = n x 0.4719)
Limitations: This product is for residential applications only. Must be installed in accordance with all current national and local regulation building and safety codes.
10
WWW.CLEANCOMFORT.COM
IO-VENT-SS
CONTROLS / WIRING
Controls Connection
Wiring connections are shown for the Clean Comfort
VHP Series wall controls and timer. See Sequence of
Operations table for description of operation of these
wall controls and timer with the ventilator.
G
VHP-RD1 (2 wires)
R
Low Voltage Ventilator Controller
This control will operate the ventilator when the relative humidity level measured at the control is higher
than the setting on the control.
G
R
G
R
VHP-RD3P (4 wires)
Low Voltage Ventilator Controller
R
G
B
W
R
G
B
W
This control will operate the ventilator when the
relative humidity level measured at the control is
higher than the setting on the control. It can also
override the control on the ventilator by reducing
maximum fan speed by 30% on CONT setting and
15% on High (Override) speed.
R
G
B
W
Forced-air System
VHP-T3 TIMER (3 wires)
This control will operate the ventilator on high speed
for the length of time (20, 40 or 60 minutes) selected
by the user.
B G R
B G R
i CAUTION!
B G R
Minimum wire requirement is LVT18 CSA/UL 4 strand to
ensure proper connection.
Wiring Diagrams for Furnace
Interlock Systems
Jumper
JP-4*
LVC Version 1
Jumper Low Voltage Ventilator Controller
LVC Version 1
JP-4*
2 Relays
RW B G
Jumper
JP-4*
2 Relays
LVC Version 1
To Casing
RW B G
Screw
Standard Forced-air Interlocking Wiring
for Ground
A relay is normally used when tying a ventilation system into
2 Relays
To Casing
the forced-air distribution system. The low voltage ventilator
Screw
RW B G
control on the ventilator is equipped with an internal relayfor Ground
Jumper
that will activate the forced-air system's ventilator when
JP-4*
LVC Version 2
To Casing
there is a demand from the HRV /ERV.
Screw Low Voltage Ventilator Controller
This ventilator control will activate the INTERLOCK relay for Ground
Legend: -------- FieldJumper
Installed Low Voltage
during the following modes: Continuous, Override,
JP-4*
LVC Version 2
Figure 18 Standard forced-air wiring diagram
Recirculation and Defrost. See wiring diagram at right.
RW B G
1 Relay
Jumper
JP-4*
1 Relay
LVC Version 2
RW B G
1 Relay
IO-VENT-SS
WWW.CLEANCOMFORT.COM
RW B G
11
VENTILATION REQUIREMENTS
Alternate Forced-Air Interlock Wiring
Some thermostats will activate the cooling system
when used with the Standard Forced-Air Interlock
Wiring.
If your thermostat operates this way, you must use the
Alternate Forced-Air Wiring shown at right.
Locating the Wiring Diagram
Note to installer: Wiring diagrams for the Clean
Comfort ventilators are placed on the inside back
cover of the exhaust motor bracket of each unit.
Forced-Air
System
Thermostat
Legend: -------- Field-Installed Low Voltage
i CAUTION!
Thermostats that control A/C system must use the
Alternate Interlock Wiring Diagram.
i WARNING!
Figure 19 Alternate forced-air wiring diagram
*Before wiring the ventilator to a forced-air system, always refer
to system’s manual or manufacturer.
i CAUTION!
Always disconnect power to the unit prior to making
any electrical connections. Failure to disconnect the
power could result in electrical shock or can damage
the electronic boards, wall controls and/or unit.
12
Low-Voltage Ventilator Controller
Minimum wire requirements is LVT18 CSA/UL 4 strand
to ensure proper connection.
WWW.CLEANCOMFORT.COM
IO-VENT-SS
SEQUENCE OF OPERATIONS
Sequence of Operations for Ventilator and
Connected Wall Controls and Timer
There is a low voltage ventilator control mounted on the
HRV/ERV to operate the ventilator in Intermittent (INTER)
or Continuous (CONT) operation. When a VHP-RD3P wall
control is connected to the ventilator, it can override the
setting on the ventilator as described in the table below.
Ventilator Control
Setting
In addition, the VHP-RD3P has the ability to operate
the ventilator at a reduced speed by setting the RANGE
selector on the VHP-RD3P to the REDUCED position. In
this position, the ventilator will run at 15% slower fan
speed in CONT mode and 30% slower in Override (High)
speed when responding to a high humidity signal from
the VHP-RD1 or VHP-RD3P wall control or when the
VHP-T3 timer is activated.
VHP-RD3P Control Setting
Action
INTERM
Ventilator runs intermittently (unit is dormant ) but goes to high
speed when %RH is above set point on the wall control, or if a
VHP-T3 timer is activated.
INTER
CONT
Ventilator runs continuously on set speed at ventilator or set
speed on the range setting from the wall control. It will go to
HIGH speed when %RH is above set point on the wall control or if
a VHP-T3 timer is activated.
CONT
INTERM
Ventilator runs intermittently (unit is dormant ) but goes to high
speed when %RH is above set point on the wall control or if a
VHP-T3 timer is activated.
CONT
CONT
Ventilator runs continuously on set speed at ventilator or set
speed on the range setting on the wall control but goes to HIGH
speed when %RH is above set point on the wall control or if a
VHP-T3 timer is activated.
INTER or CONT
OFF
Ventilator does not run even if the Ventilator is set to INTER or
CONT. Ventilator will not go to high speed even if the %RH is above
set point on the wall control or if a VHP-T3 Timer is activated.
INTERM or CONT
Ventilator does not run, even if the wall control is set to INTER or
CONT mode. The Ventilator will not go to high speed even if the
%RH is above set point on the wall control or if a VHP-T3 timer is
activated.
RH sensor dial set to OFF
Ventilator does not run based on RH measured at the wall control
(sensor is disabled). Otherwise the Ventilator and the wall control
operates as described above and will go to high speed if a VHP-T3
timer is activated.
INTER
OFF
INTER or CONT
RUN Mode
When the LED is green, the control is in RUN mode and
the selector switch is used to set the ventilator’s Operating Mode. The options are:
Ventilation Control
• INTER (Intermittent): With the selector switch in the
INTER position, the unit runs only on a call for ventilation from an external wall control or timer. It will then
run on high speed until the call is satisfied.
The low voltage ventilator control mounted on the HRV/
ERV has a three-position selector switch and buttons
(marked “+” and “–” ) to adjust fan speed. The color of the
LED light located above the selector switch indicates the
operating mode of the control as follows:
• LED is GREEN = Control is in Run mode
(normal operation)
• CONT (Continuous): With the selector switch in the
CONT position, the unit runs continuously (low speed)
until there’s a remote call for ventilation (override)
from an external control.
• OFF: When the selector switch is in the OFF position,
the ventilator will not operate even if there’s a remote
call for ventilation from an external control.
• LED is YELLOW = Control is in Balancing mode
IO-VENT-SS
WWW.CLEANCOMFORT.COM
13
SEQUENCE OF OPERATIONS
(+) and (–) buttons: These buttons are used for adjusting
both the high and CONT fan speed settings when the
control is in RUN mode.
4. When in Balancing mode, the selector switch becomes
the motor selector switch. The switch position selects
which fan motors will be adjusted during balancing.
BALANCING Mode
When the control is set to Balancing mode, the LED
indicator turns yellow and the selector switch is used for
setting the high speed of the fans for balancing purposes
(Supply (fresh) air, Exhaust air, and Both). The options are:
• INTER (Intermittent): With the selector switch in this
position, the speed of the exhaust air fan can be set
• CONT (Continuous): With the selector switch in this
position, the speed of BOTH the exhaust and supply air
fans can be set
5. Adjust the airflow rate in the fresh air duct by setting
the selector switch to the OFF position.
6. Connect the airflow measuring device to the integral
balancing taps on the ventilator's collars.
• OFF: With the selector switch in this position, the speed
of the supply air fan can be set.
HIGH (Exhaust Air to Outside)
(+) and (–) buttons: These buttons are used for adjusting
Magnehelic gauge
LOW (Exhaust Air from Home)
the fan speed of either or both of the supply and exhaust
fan motors, depending on the fan motor selected by the
position of the selector switch. The + button increases the
speed of the fan being adjusted
and the (– ) button decreases the speed.
Balancing Tap Connection*
Magnehelic gauge
NOTES:
HIGH (Fresh Air to home)
LOW (Fresh Air from Outside)
1. Continuous low speed is 50% of the fan speed
selected for HIGH speed.
Figure 12 Location
2. When the LED stops flashing, the ventilator is at
its maximum speed.
of balancing taps on
collars
Procedure for Setting High (Override)
Airflow Rate and Balancing the Ventilator
To balance the ventilator, you will need to independently
adjust the flow rate in both the fresh air (supply) duct as
well as the stale air (exhaust) duct. You will need an airflow
measuring device such as a pitot tube or a Magnehelic gauge.
NOTE: Turn the HVAC equipment fan ON while
performing these balancing steps
1. Once the total CFM needed is determined (see
Ventilation Requirements section), you can start
balancing the HRV/ERV.
2. Set the three-position selector switch on the ventilator
control to either the INTER or CONT position.
3. Press and hold both the (+) and (–) buttons
simultaneously for 5 seconds until the LED light turns
yellow, indicating the unit is now in Balancing mode.
Magnehelic Gauge with Airflow Grid
7. Press the (+) and (–) buttons on the ventilator control
to increase or decrease the fan motor speed to produce the desired airflow in the duct being measured.
Note: When the LED stops flashing, the ventilator is
at its maximum speed.
14
WWW.CLEANCOMFORT.COM
IO-VENT-SS
BALANCING THE UNIT
2. Release both buttons
8. Perform the same operation on the stale air side by
selecting the INTER position on the selector switch.
Adjust the airflow rate in the stale air duct to be the
same as the airflow rate in the fresh air duct, so the
airflow entering and leaving the building is balanced.
Testing the Ventilator to Confirm Operation
9. If necessary, the selector switch can be set to the CONT
position, which will adjust the speed of both fan motors
at the same time.
1. Apply power to the ventilator. Set the selector
switch to the CONT position. Verify that the unit
turns on and operates at continuous speed
10. Once this is done, you have set and locked the high
speed on your ventilator and balanced the fresh and
stale airflow rates.
2. Turn the wall control to minimum humidity setting to
create a call for ventilation. Verify that the ventilator
turns on and operates at high speed. Return wall
control to normal humidity setting.
3. Unit has now been reset and is ready for rebalancing, if necessary
11. To exit Balancing mode, press the (+) and (–) buttons at
the same time until the LED turns green, indicating that
the control has returned to Run mode.
Procedure for Setting Low
(Continuous) Ventilation Rate
When the unit is in Run mode, the continuous airflow rate
can then be set by using the (+) and (–) buttons and reading
the CFM using the airflow measuring device.
1. When the unit is in Run mode, the continuous
airflow rate can then be set by using the (+) and (–)
buttons and reading the CFM using the airflow
measuring device.
2. When the selector switch is set to the CONT position,
the ventilator runs at the low (continuous) speed until
there’s a remote call for ventilation (override) from an
external control such as the VHP Series of controls.
Balancing Reset
Balancing of the ventilator is locked upon exiting Balancing
Mode and can only be changed with a reset of the control.
To Reset Control
1. Press the (+) and (–) buttons simultaneously for 10
seconds. After 5 seconds, the LED will turn yellow and
after 10 seconds, it will turn green
3. Repeat for timer control, if one is installed
4. Return the selector switch to the desired position
(INTER or CONT) and the wall control to the desired
settings
5. Inspect the ductwork to verify there are no bends,
kinks or obstructions to airflow. Correct as needed.
*Important: Once balancing is complete, ensure all four
pressure taps are sealed with the rubber caps. Pressure taps
are supplied in the installation kit.
Balancing chart
This balancing chart is based on a Delta P (DP) reading from the
airflow measuring device. A copy of this chart is also located on
the access panel of the ventilator.
Note: To perform a proper installation, the External Static
Pressure (ESP) needs to be measured at each of the 4 stations.
Proceed to measure the Delta P (DP) to determine the corresponding airflow (e.g. 50 CFM), then repeat until the unit is
balanced for both the ESP and airflows.
Balancing Chart when using collar pressure taps.
Pressure
Pa
50
62
75
87
100
112
125
137
150
162
175
187
199
IO-VENT-SS
Fresh Air
in. wg
0.20
0.25
0.30
0.35
0.40
0.45
0.50
0.55
0.60
0.65
0.70
0.75
0.80
L/s
44
41
39
37
35
33
30
29
26
24
22
19
17
Exhaust Air
CFM
93
87
83
79
74
69
65
61
56
50
46
41
36
WWW.CLEANCOMFORT.COM
L/s
43
40
37
36
36
34
32
28
24
22
19
17
15
CFM
90
85
79
77
76
71
67
60
51
47
41
36
31
15
TROUBLESHOOTING
Question / Item
Diagnosis / Solution
• Ventilator not
running
• Verify breaker in main electrical panel
• Verify the HRV or ERV is in the ON position
• Verify all wall controls connected to the ventilator are activated to supply power to the unit
• Unplug ventilator and verify that the wall control is wired correctly to the connection box on
the side of the unit
• Verify main outlet polarization
• Air is too dry
• Increase the humidity level on the wall control (Turn dial towards 60%)
• Reduce continuous airflow rate
• Switch ventilation mode from continuous to intermittent
• Increase the humidity level in the home by installing a whole-home humidifier
• Air too humid
• Suggest continuous operation of ventilator
• Reduce humidity setting on the wall control (Turn dial towards 30%)
• Increase continuous airflow rate (ventilator fan speed)
• Insufficient ventilation, check that the capacity of the ventilator is sufficient
for the size of the home
• Internal source of moisture, e.g. heating wood stove in basement, possible water leaks in
foundation or poor insulation R-value and or clothes dryer is venting in basement
• Vibration or noise
• Verify that the correct mounting equipment (wall-mounting bracket) was used when hanging the ventilator.
• Verify that a section of flexible duct is installed between the ventilator and the rigid duct.
• Verify that the motors are operating properly and the fans are rotating freely and are not
obstructed by any debris
• Cold air
• Misplaced supply outlets
• Defrost not operating correctly
• The ventilator is not properly balanced
• High airflow on furnace continuous mode
• Ensure ventilator is interlocked when integrated with forced-air system
• Pollutants
• Ensure proper clearance of ventilation hoods from source of pollutants
Refer to section "Installing Ventilation Hoods for Fresh Air and Exhaust"
• Condensation
• Verify that the ventilator is level to ensure proper drainage
• Verify that the duct connections are secured with screws to the ventilator.
• Verify the fresh (supply) side duct connections are fully insulated and that the home has a
properly-installed vapor barrier to ensure the home is sealed tightly.
• Look for any sections of crushed ducting, failing duct straps, punctured vapor barrier, or
missing insulation.
• Look for signs of water accumulation/leakage/dripping
• Ensure proper seal of vapor barrier to outside wall.
• Verify that the drain connection is not kinked; i.e. that the “P” trap is not too close to the
ventilator or is blocked with debris.
16
WWW.CLEANCOMFORT.COM
IO-VENT-SS
MAINTENANCE
Routine Maintenance
4. Clean the condensate drain and pan
Seven-Step Maintenance Schedule
With routine preventative maintenance, you can avoid
unnecessary problems, ensure the effectiveness of
your ventilator, and prolong its life.
i WARNING!
Twice a year, check the condensate drain, pan and
tubing to ensure that they are open and free-flowing.
The tubing can be disconnected for cleaning. The
condensate drain must have a “trap” in the tubing
that traps a quantity of water and helps prevent
unpleasant odors from entering the ventilator via this
tubing.
5. Inspect the fans
BE SURE TO DISCONNECT THE ELECTRICAL
POWER BEFORE SERVICING YOUR SYSTEM
1. Clean or replace air filters
Filters, which are located within the ventilator, should
be cleaned every two to three months. Filters should
be vacuumed first, then washed with a mild soap and
water. Most washable filters will last several years
before needing to be replaced.
2. Clean the exterior intake and exhaust vents
of obstructions
Check the outside vents regularly to ensure that the
screen openings are not obstructed by grass, bushes,
leaves, snow or other debris.
3. Clean and inspect the heat-exchange core
Do this twice a year and clean the core as required.
Consult the Installation and Operation manual for
instructions on inspecting and cleaning the core. A
build-up of dust and dirt can restrict airflow and reduce
the efficiency of the ventilator. After inspection and
cleaning, make sure the core is replaced right-side-up.
The fan motors on the ventilator are designed to
operate continuously without lubrication and should
not require inspection. Inspect the blower fans
periodically for dirt on the blades, and remove it by
gently brushing the blades or using a vacuum cleaner.
6. Clean the grilles and inspect the ductwork
Clean the grilles when they are dusty. At least once
a year, visually inspect the ductwork leading to and
from the ventilator. Damaged ducts can lead to
condensation problems, including wet insulation,
water on the floor and, ice build-up.
7. Arrange for an annual servicing
Your ventilator should undergo annual general
servicing by a certified contractor who is familiar
with its operation. If possible, have your furnace and
ventilator serviced at the same time.
Daikin reserves the rights to modify a product, without
prior notice, whether in price, design, color or codes, in
order to offer at all times quality products that are highly
competitive.
Install and service this equipment in compliance
with applicable national and local building and
safety codes.
1. Slide out the filters.
2. Slide out the energy core.
3. Vacuum the filters.
4. Wash out the walls of the unit.
IO-VENT-SS
WWW.CLEANCOMFORT.COM
Louver Orientation
17
WARRANTY
Limited Warranties
Coverage
Daikin North America LLC (“Daikin”) warrants this product,
to the original consumer, to be free from defects in
materials and workmanship under normal use and service,
for the applicable time periods listed below.
Warranty Period (Years after installation)
Product
Ventilation
motors
Heat
Exchange Core
Controls, sensor
and electronics
VH30100
5
5
VH30120R
5
5
VH70220
10
VH30160
10
VH30160R
10
VH30160NC
2
2
VH70220NC
2
2
VE30100
5
VE30160
10
VE70220
10
As long as
the original
owner owns
the product
(Polypropylene heat
recovery
core)
5
(Enthalpy
energy
recovery
core)
Warranties apply only to products installed in their original
location. Installation, use, care, and maintenance must be
normal and in accordance with instructions contained in the
Owner’s Manual and service information. Defective parts
must be returned to the distributor through a registered
servicing dealer for credit. All work shall be performed by
a state-licensed technician. Replacement parts replaced
after expiration of the previously applicable limited warranty
period (if any) are warranted for a period of one year.
5
5
5
Daikin will not be responsible for normal maintenance,
installation, including filter cleaning and/or replacement,
damage or repairs required as a consequence of faulty
installation, misapplication, abuse, improper servicing,
unauthorized alteration or improper operation, damage as
a result of floods, winds, fires, lightning, accidents, corrosive
environments or other conditions beyond the control of
Daikin, parts not supplied or designated by Daikin, or
damages resulting from their use.
5
5
5
Terms Applicable to All Warranties
THE WARRANTIES SET FORTH HEREIN ARE THE ONLY EXPRESS
WARRANTIES ON THE PRODUCT, AND DAIKIN EXPRESSLY
LIMITS THE DURATION OF ANY IMPLIED OR STATUTORY
WARRANTIES, INCLUDING BUT NOT LIMITED TO ANY
WARRANTIES OF MERCHANTABILITY, WORKMANSHIP, OR
FITNESS FOR A PARTICULAR USE, TO THE DURATION OF THE
APPLICABLE EXPRESS WARRANTY. Some states and provinces
do not allow limitations on how long an implied warranty
lasts, so the above limitation may not apply to you.
Daikin’s exclusive obligation, and the purchaser’s only remedy,
under these warranties shall be for Daikin to supply, without
charge, a new or remanufactured replacement for any
covered component or part of the product which is found to
be defective within the applicable warranty period; provided,
however, that Daikin reserves the option to repair and return
the defective part or component. None of these warranties
18
include labor or other costs incurred for diagnosing, repairing, removing, installing, shipping, servicing or handling
of either defective parts/components or replacement
parts/components. DAIKIN SHALL NOT HAVE ANY OTHER
RESPONSIBILITY, INCLUDING ANY LIABILITY FOR INCIDENTAL
OR CONSEQUENTIAL DAMAGES, RESULTING DIRECTLY OR
INDIRECTLY FROM ANY BREACH OF WARRANTY, EXPRESS
OR IMPLIED, OR OTHER CONTRACT BREACH, NEGLIGENCE
OR OTHER TORT. Some states and provinces do not allow
the exclusion or limitation of incidental or consequential
damages, so the above exclusion may not apply to you.
Any part replaced pursuant to this warranty is warranted
only for the unexpired portion of the warranty term
applying to the original part.
This warranty gives you specific legal rights, and you may
also have other rights which vary from state to state or
province to province.
Upon notice of warranted failure, information should
be gathered specific to the cause and results of the failure.
Warranty claim request must be filed within 30 days
of failure.
Contact Daikin Technical Support Line at 1-888-724-5211
and explain the situation, including model and serial number
of the machine. We will advise as to proper procedures to
either repair or replace as necessary and the warranty
coverage available. Important - the unit model as well as
the serial number must be stated to ensure replacement
parts are accurate.
DAIKIN NORTH AMERICA LLC
480 Ferdinand Blvd.
Dieppe, New Brunswick Canada E1A 6V9
1-888-724-5211
WWW.CLEANCOMFORT.COM
IO-VENT-SS
Notes
IO-VENT-SS
WWW.CLEANCOMFORT.COM
19
VENTILATORS
Our continuing commitment to quality products may mean a change in specifications without notice.
©2015
• Houston, Texas • Printed in the USA.
20
WWW.CLEANCOMFORT.COM
IO-VENT-SS

advertisement

Related manuals

Download PDF

advertisement