advertisement
Application manual
KNX room temperature controller
EK-EP2-TP
Application manual
KNX room temperature controller EK-EP2-TP
Index
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 2
Application manual
KNX room temperature controller EK-EP2-TP
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 3
Foreword
Application manual
KNX room temperature controller EK-EP2-TP
The present document describes the ekinex
®
KNX room temperature controller with LC-display (EK-EP2-TP version).
1
General information
The device described in the present document works as an electronic digital temperature controller for a room or a zone (consisting e.g. in a group of rooms or a whole floor) of a building and is part of the secundary regulation for heating and cooling. The room temperature controller was developed according to the KNX standard for use in systems of control of homes and buildings.
Through the integrated sensor, the device can measure directly the room temperature value that can be used for control and regulation tasks of heating, cooling and ventilation. Via the bus the device can furthermore receive temperature values from other bus devices. The integrated display visualizes a series of information concerning the room controller function. The device is provided with two rockers that can be used for controlling the thermostat function. The two physical inputs may be configured independently as analogic or digital and allow to extend the basic functions, optimizing comfort, safety and energy savings depending on the user or building needs.
1.1
Function
The main function of the device is to control the temperature of the air mass of the room by means of the actual temperature (T eff
), measured by the device itself or received by the bus, and of the setpoint temperature (T set
) set by the user; comparing the two values and a series of parameters set before the commissioning, the regulation algorithm of the device calculates the control variable value that is converted to a telegram and transmitted on the bus toward KNX actuators (such as binary outputs, fan-coli controllers, valve drives, etc.) able to control the operation of heating and cooling terminal units.
1.2
Main funcional features
The main functions carried out by the device are:
• temperature and brightness measuring through the integrated sensors with possibility of sending the values on the bus;
• 2-points (on/off) or proportional (PWM or continuous) room temperature regulation;
• ventilation control with continuous or 3-speed regulation;
• seasonal modes: heating and cooling with local or via bus switch-over;
• operating modes: comfort, standby, economy and building protection with separate setpoint values for heating and cooling;
• manual or automatic control of a fan-coil unit with 2-pipes or 4-pipes connection
• automatic switching of the operating mode when presence/absence of people or window opening is detected;
• weighted average of two temperature values;
• temperature displaying (measured, setpoint and outdoor values in °C or °F), alarms and errors (with alphanumeric codification);
• signaling opening windows;
• limitation of the surface temperature for floor heating radiant panels;
• anticondensation protection for floor and ceiling cooling radiant panels;
• antistratification function;
• delayed fan start (“hot-start” function) time-scheduled or depending on the conveying fluid temperature measured at the coil battery.
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 4
1.3
Technical data
Feature
Device
Communication
Use
Environmental conditions
Power supply
Current consumption from bus
Switching elements
Programming elements
Display elements
Sensore di temperatura
Sensore di luminosità
Accessories
Installation
Connection
Protection degree
Dimensions (WxHxD)
Application manual
KNX room temperature controller EK-EP2-TP
Valore
KNX S-mode bus device according KNX TP1 standard dry internal rooms
• Operating temperature: - 5 ... + 45°C
• Storage temperature: - 25 ... + 55°C
• Transport temperature: - 25 ... + 70°C
• Relative hunidity: 95% not condensating
SELV 30 Vdc from bus KNX (auxiliary power supply not necessary)
< 13 mA
2-fold pushbutton
1 pushbutton and 1 LED (red) on the front side
1 backlighted LC-display, 8 LED (4 for each rocker)
1 integrated NTC-type
1 integrated
2 square (40x40 mm) rockers and a square frame of the flank or form series (to be ordered separately) - ‘NF (No Frame versions) do not require any frame
On round or square wall-mounting box with disatnce between fixing holes of 60 mm
• bus: black/red KNX terminal block
• inputs: screw terminal blocks
IP20
82 x 75 x 35 mm
1.4
Design
The device is realised for wall-mounting on round or square wall box with distance between fixing holes of 60 mm. The programming pushbutton and the programming led are on the front side under the rockers. On the rear side of the housing there is the 4-pole terminal block for the connection of the 2 inputs and the terminal block for the connection of the bus.
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Device: front and side sights
Application Manual
Page 5
Application manual
KNX room temperature controller EK-EP2-TP
1.5
Delivery
The delivery includes a device, the terminal block for the connection of the bus, the screws (2 pairs) and the metallic support for mounting on the wall box. The packaging inlcludes also the device instructions.
1.6
Accessories
The device is completed with a set of two square 40x40 mm rockers and a square frame of the form (EK-
FOQ-...) or flank (EK-FLQ-...) series that have to be ordered separately. The ‘NF (No Frame) version does not require any frame (see also the following table). Temperature sensors and other devices to be connected to the inputs must be ordered separately.
Code
EK-EP2-TP
EK-EP2-TP-RW
Version
with frame
Colours of LED
blue / green white / red
Accessories
it requires the rockers’ set EK-TSQ-G...-EP2and a square frame of the form (EK-FOQ-...) or flank (EK-FLQ-...) series
EK-EP2-TP-BG-NF
EK-EP2-TP-RW-NF
‘NF (No Frame) blue / green it requires the rockers
’ set EK-TSQ-G...-EP2
on the
‘NF (No Frame) version no frame is mounted
white / red
Accessories of the device: set of rockers and frames
1.7
Marks and certification
The KNX mark on the ekinex device ensures interoperability with the KNX devices ofSBS and other manufacturers installed on the same system bus system. The compliance with the applicable European directives is indicated by the presence of the CE mark.
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 6
2
Installation
Application manual
KNX room temperature controller EK-EP2-TP
The device has degree of protection IP20, and is therefore suitable for use in dry interior rooms. The installation of the device requires the following steps: a) fix the metallic support with the screws supplied on a wall box with distance between fixing holes of
60 mm. It is recommended to install the device at a height of 150 cm; b) if required, snap a square frame of the form or flank series, inserting it from the rear of the device; c) connect the sensors or the contacts required to the 4-poles screw terminal block on the rear of the device; d) insert the terminal for the bus (red/black), previously connected to the bus cable, in its slot on the rear side. At this point it is recommended to carry out the commissioning of the device or at least the download of the physical address; e) install the device on the metallic support through the spring system, tightening then the two screws f) requires also to tighten the screws included in the delivery. For mounting the device follow also the indication TOP (arrow tip pointing up) on the rear side of the device;. g) snap the two rockers onto the device for the operation of the room temperature controller.
The device can only be mounted on a round or square wall flush mounting box with 60 mm distance between fixing holes. If necessary, the metallic support for mounting on the wall box can also be ordered separately.
2.1
Connection
For the operation the device has to be connected to the bus line and addressed, configured and commissioned with ETS (Engineering Tool Software). The connection of one or two sensors to the inputs is optional and must be defined by the planner of the bus system.
2.1.1
Connection of the bus line
The connection of the KNX bus line is made with the terminal block (red/black) included in delivery and inserted into the slot of the housing.
Characteristics of the KNX terminal block
• spring clamping of conductors
• 4 seats for conductors for each polarity
• terminal suitable for KNX bus cable with single-wire conductors and diameter between 0.6 and 0.8 mm
• recommended wire stripping approx. 5 mm
• color codification: red = + (positive) bus conductor, black = - (negative) bus conductor
2.1.2
Connection of the inputs
The connection of the inputs is made with the screw terminals located at the rear side of the device. The maximum cable length is 10 m. For the connection use a cable of max section 1,5 mm². The connection cable must have sufficient length to allow the extraction of the device from the wall-mounting box.
Characteristics of the terminal blocks for the inputs
• screw clamping of conductors
• maximum cross section of conductor 1 mm² (multiwire)
• recommended wire stripping approx. 5 mm
• torque max 0.2 Nm
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 7
Bus
KNX
+
–
Application manual
KNX room temperature controller EK-EP2-TP
Connection of the device of the bus line
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 8
3
Configuration and commissioning
Application manual
KNX room temperature controller EK-EP2-TP
The configuration and commissioning are carried out with the ETS (Engineering Tool Software) tool and the ekinex
®
application program provided free of charge by SBS; you do not need any additional software or plug-in tool. For further information on ETS see also www.knx.org
.
3.1
Configuration
The device functionality is defined by the settings done via software. The configuration requires necessarily
ETS4 (or later releases) and the ekinex
®
APEKEP2TP##.knxprod
(## = release) application program that can be downloaded from the website www.ekinex.com
. The application program allows the configuration of all working parameters for the device. The device-specific application program has to be loaded into ETS or, as alternative, the whole ekinex
®
product database can be loaded; at this point, all the instances of the selected device type can be added to the project.
Application program for ETS APEKEP2TP##.knxprod (## = version)
3.1.1
Tree structure of the application program
At its opening, the tree structure of the program includes the following main items:
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 9
Application manual
KNX room temperature controller EK-EP2-TP
About EK-EP2-TP
General
Internal sensors
Inputs
External sensors (from bus)
LCD display
Led
Temperature control
Energy saving
Other items may appear depending on the choices done for the parameters of the folders.
3.1.2
Languages of the application program
The application program is available in four languages: English, Italian, German and French. The language displayed can be changed in ETS choosing "Settings / Presentation language".
3.2
Commissioning
For the commissioning the device is provided on the front side (in the area usually occupied by the rockers) of:
• a red LED (1) for indication of the active operating mode (LED on = programming, LED off = normal operation);
• a pushbutton (2) for switching between the normal and programming operating mode.
1
2
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Device programming: led (1) and pushbutton (2)
Application Manual
Page 10
Application manual
KNX room temperature controller EK-EP2-TP
For commissioning the device the following activities are required:
• make the electrical connections;
• turn on the bus power supply;
• switch the device operation to the programming mode by pressing the programming pushbutton located on the front side of the housing. In this mode of operation, the programming LED is turned on;
• download into the device the physical address and the configuration with the
ETS
®
program.
When downloading the application program the display shows "PrOg" and the flashing symbol of the clock. At the end of the download the operation of the device automatically returns to normal mode; in this mode the programming LED is turned off. Now the bus device is programmed and ready for use.
3.2.1
Displaying physical address and firmware release
Once the first addressing is done, you can check anytime the physical address and the firmware release directly on the device display. In order to display it, press for more than 3 seconds the – (minus) symbol on the lower rocker and the
symbol on the upper rocker. All segments of the display are turned off; displaying a physical address only the 3 large digits and the small one are active. The information displayed in sequence are: the area number (A), the line number (L), the device number (d) and the firmware release
(F). To scroll through the three elements of the physical address press + or –.
Example of displaying the physical address 10.5.43 (device nr. 43, installed on the line 5 of the area 10) and the firmware release 001
To exit from the physical address displaying press shortly (< 3 seconds) the
symbol on the lower rocker. If you elapse of time interval set in parameter “Time to exit change without saving” without pressing any rocker, the device returns automatically to the previously displayed information.
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 11
4
User interface
Application manual
KNX room temperature controller EK-EP2-TP
The user interface of the room temperature controller includes a LC-display, a pushbutton with two rockers and a series of freely programmable LEDs (4 for each rocker). The colour of the LEDs depend on the device version.
2
1
3
User interface: LC-display (1), rockers (2), LEDs (3) with lightguide
The symbols on the rockers recall the function carried out:
+
‒
temperature or fan speed increase; temperature or fan speed decrease; information sequence, operating mode change, ventilation control, seasonal change-over.
Through a combined pressure of various symbols other functions can be carried out.
4.1
LC-display
The device is provided with a LC-display (1) with adjustable backlight that occupies a vertical area of approx.
40 x 80 mm (WxH) in the left half of the device. Thanks to the integrated brightness sensor, you can set the automatic adjustment of the backlight intensity according to the room brightness conditions.
4.1.1
Information displaying
Depending on the configuration done with ETS, the connections and the availability of information (local or received from the bus), the series of symbols allow to display:
room actual temperature (it may be the temperature calculated using a weighted average of two values);
outdoor temperature, preceded by a ‒ (minus) sign in case of outdoor temperature below 0°C;
temperature setpoint (for the actual operating mode);
alarm and error condition (A01, A02… E01, E02…);
window opening;
operating mode (comfort / standby / economy / building protection);
seasonal mode (heating / cooling);
device status calling / not calling (or setpoint reached / not reached);
operation in manual mode (M);
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 12
operation as slave device (clock);
fan status (1-2-3-automatic-off), when present;
device physical address assigned by ETS.
Display symbols
Digits (for numeric values display)
Celsius degrees
Application manual
KNX room temperature controller EK-EP2-TP
Heating mode active (device not calling or setpoint reached)
Heating mode active (device calling or setpoint not reached)
Fahrenheit degrees Manual operation (M)
Alarm
Window opening
Slave (operation subordinated to a supervising KNX device)
Cooling mode active (device not calling or setpoint reached)
Cooling mode active (device calling or setpoint not reached)
Indoor temperature
Outdoor temperature
SET
OFF (fan-coil switched off)
Automatic fan-coil operation (example: speed 3)
Manual fan-coil operation (example: speed 2)
Building protection operating mode
(off)
Economy operating mode (night)
Standby operating mode
Comfort operating mode
Symbols that can be activated on the LC-display
4.1.2
Segment test
The segment test allows you to check at any time the proper functionality of the display. In order to do the test, press simultaneously + (plus) on the upper rocker and the symbol
on the lower rocker for more than 3 seconds. All symbols are activated simultaneously; then all the symbols are turned off. In the test phase keep available the instructions or the user guide.
If you elapse the time set in the parameter "Time to exit change without saving" (General folder) without pressing a button, the device will return to the previous situation.
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 13
4.1.3
Backlight
Application manual
KNX room temperature controller EK-EP2-TP
The backlight intensity of the LC-display is adjustable. The first setting is done when configuring the device using ETS, but the intensity can be changed later at any time.
To access the change press simultaneously + (plus) and
(bothon the upper rocker) for more than 3 seconds. All symbols are turned off except the digits and the percentage symbol. The actual value (as a percentage) of backlight intensity is displayed. At each pressing of + or – the intensity is increased or decreased by 5%. To confirm the selected intensity press shortly (< 3 seconds) the
symbol either on the upper rocker. Three rapid flashes of the digits indicate that the new value was saved. If you elapse of time interval set in the "Time to exit change without saving " (General folder) without pressing any rocker, the device returns to the previous situation.
4.2
Rockers
The pushbutton with two rockers integrated in the device controls the functions of the thermostat. The set of two rockers has to be ordered separately; the symbols on the rockers of the set are pre-defined and cannot be changed. The areas marked by the symbols + (plus) and – (minus) allow you to change a setting (e.g. the temperature setpoint), while those marked by the symbol ●●●● allow you to display a sequence of information, to change the operating mode, to control the ventilation, to do the seasonal change-over
(heating to cooling and vice versa) or to confirm a setting change.
The part number of the set EK-TSQ-Gxx-EP2 must be completed with the part (xx) that identifies the material, color and finishing; for the exact code please refer also to the latest edition of the ekinex product catalog or the website www.ekinex.com.
Rockers use Upper rocker Lower rocker
Functions for room temperature controlling
+ and and ‒
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 14
5
Sensors
Application manual
KNX room temperature controller EK-EP2-TP
The room temperature controller is equipped with three sensors:
• temperature (1);
• brightness (2).
2
1
Positioning of the sensors: temperature (1), relative humidity (2) and brightness (3).
The temperature sensor (not to be seen in the drawing) is located under the plastic half-shell for the rockers’ mounting.
5.1
Temperature sensor
The integrated temperature sensor allows the measureming of the room temperature in the range from 0 °C to +40 °C with a resolution of 0.1 °C. To keep into account significant environmental interferences such as the proximity to heatsources, the installation on an outer wall, the chimney effect due to rising warm air through the corrugated tube connected to the wall-mounting box, the measured value can be corrected by means of a offset of ± 2.5 K or, preferably, can be used a weighted average between two values of temperature chosen from the following ones: value measured by the integrated sensor, value measured by a temperature sensor connected to one of the inputs of the device, value received via bus from another KNX device (such as ekinexpushbuttons).
5.2
Brightness sensor
The integrated brightness sensor allows the measuring of the light intensity of the room. The sensor can be used to automatically adjust the backlight of the LC-display, but its value can also be sent on the bus via the
Object Communication 1 Brightness value.
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 15
6
Input variables
Application manual
KNX room temperature controller EK-EP2-TP
The data that the device usesin its control algorithms and /or to be displayed may come from:
• the internal sensors;
• sensors or digital signals connected to the two physical inputs of the device;
• the KNX bus through standard Communication Objects.
The processed data can also be transmitted on the KNX bus as Communication Objects.The classification of the input variables is shown in the following table.
Data
Room temperature
Room brightness
Several (depending on the choosen application)
Window state (open/close)
Card holder state (badge in/out)
Presence of condensation
Conveying fluid temperature at the exchange coil
Room temperature (for weighted average value)
Room temperature (other measurement height)
Floor surface temperature
Outdoor temperature
Further temperature value
Room temperature
Antistratification temperature
Outdoor temperature
Conveying fluid temperature at the exchange coil
Floor surface temperature
Presence of condensation
Window state (open/close)
Presence of people in the room
Card holder state (badge in/out)
Coming from
Internal sensor
Input 1 or 2 (device terminals) configurated
KNX bus (through communication objects)
Description
Analogic value for thermoregulation functions
Analogic value for brightness adjusting of the display and value sending on the bus (for other purposes)
[DI] generic digital input
[DI] window contact sensor
[DI] card holder contact sensor
[DI] anticondensation sensor
[AI] coil battery temperaure sensor
[AI] room temperature sensor
[AI] antistratification temperature sensor
[AI] floor surface temperature sensor
[AI] outdoor temperature sensor
[AI] generic (NTC) temperature sensor
Object 147 (2 bytes)
Object 137 (2 bytes)
Object 138 (2 bytes)
Object 140 (2 bytes)
Object 141 (2 bytes)
Object 146(1 bit)
Objects 143 and 144 (1 bit)
Objects 132 and 133 (1 bit)
Object 145 (1 bit)
Input variables from internal sensors, physical inputs and standard communication objects.
The device does not have outputs for direct switching or control of heating/cooling terminals or for status or values signalling. The output variables include exclusively communication objects that are sent on the bus, received and processed by KNX actuators (general-purpose or dedicated to HVAC applications).
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 16
7
Application program for ETS
Application manual
KNX room temperature controller EK-EP2-TP
In the following chapters there is the list of folder, parameters and communication objects of the application program. Some specific functions of the thermostat are described in more detail in the dedicated paragraphs.
The tree structure of the application program as imported into ETS(or by pressing the "Default Parameters" button of ETS) is the following:
About EK-EQ2-TP
General
Internal sensors
Temperature sensor
Inputs
External sensors (from bus)
LCD display
LED
Temperature control
Settings
Heating
Energy saving
Window contact
Presence sensor
Card holder
Other folders may appear depending on the choices done for the parameters of the folders represented in the main tree structure.
7.1
About EK-EP2-TP
The folder
About EK-EP2-TP
is for information purposes only and does not contain parameters to be set.
The information given is :
© Copyright SBS S.p.A. 2014
Application software for ETS4
Version 1.00 (or later)
KNX room temperature controller with LC-display
SBS S.p.A.
Via Circonvallazione s/n
I-28010 Miasino (NO) Italy www.ekinex.com [email protected]
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 17
7.1.1
General
The
General
folder includes the following parameters:
Device operation as
Temperature displayed unit
Default displayed information
Time to return to default display information
Button function level
Time to exit change without saving
Delay after bus voltage recovery
The folder has no secondary folders.
Application manual
KNX room temperature controller EK-EP2-TP
7.1.2
Parameter table
Parameter name
Device operation as
Temperature displayed unit
Default displayed information
Time to return to default display information
Button function level
Time to exit change without saving
Delay after bus voltage recovery
Conditions Values
stand-alone
slave
If configured as slave, the room temperature controller receives from a KNX device (acting as supervisor) HVAC modes, setpont values, etc.
Celsius
Fahrenheit
actual temperature
temperature setpoint
The actual temperature is the value by which the device performs the temperature regulation. It may be the value measured from a single sensor (internal, from the bus or from an input) or the weighted average of the temperatures measured by a main sensor and an additional sensor.
The displayed setpoint temperature is that of the operating mode currently set on the room temperature controller (deduced from the symbol on).
5 s
[other values in the range 10 s … 1 min]
Time interval after which the display automatically switches between the manually recalled information to the default information.
end user
system integrator
This parameter allows you to partially disable the functions that can be recalled using the rockers. The functions that are not enabled if Button function level = end user are the following:
heating / cooling changeover
backlight intensity change
test of display segments
display of physical address and firmware release
8 s
[other values in the range 2 s … 12 s]
Time interval without further pressing of the rockers at the end of which the device exits the procedure without saving the current changes.
00:00:04.000 hh:mm:ss:fff
[range 00:00:04.
000 … 00:10:55.350]
Time interval after which the transmission of the telegrams on the bus starts after the power supply is restored. The delay affects both the event-driven transmission and the cyclic transmission of a telegram. Regarding the latter, the counting of the pause interval for retransmission starts at the end of the time of initial delay.
The field has format hh:mm:ss:fff (hours : minutes : seconds .milliseconds): the default value
00:00:04.000 corresponds to 4 seconds.
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 18
Application manual
KNX room temperature controller EK-EP2-TP
Information displayed as default
One information between the
actual temperature
and the
temperature setpoint
is displayed preferably by the digits of the display. The device allows you to retrieve and display a series of other information pressing the
●●●● symbol on the upper rocker ; after the time set in the parameter "Time to return to default information" without further pressure of ●●●●, the display automatically returns to the default information.
Functional level of the rockers
The use of the rockers for controlling the room temperature controller can be partially inhibited in the configuration phase through a filter for the access to the several functions. When using the rockers a distinction is made between:
first level functions (= short or long pressing of the rockers) for the end user;
second level functions (= combination of rockers); to the first level are added a few functions for a system integrator or an installer.
The enabled functional level is set through a special parameter.
7.2
Internal sensors
The
Internal sensors
folder includes the following parameters:
Temperature sensor
Brightness sensor
7.2.1
Parameter table
Parameter name
Temperature sensor
Brightness sensor
Conditions Values
enabled
disabled
The temperature sensor is enabled as default.
When the sensor is disabled, the corresponding folder disappears from the main tree structure of the application program; in this case to have available again the functions for Temperature control you have to enable Room temperature in the External sensors (from bus) folder or set Input X = [AI] temperature sensor (X = 1, 2) in the Inputs folder.
disabled
enabled
The brightness sensor is disabled as default. When the sensor is enabled, the corresponding folder appears in the main tree structure of the application program.
7.2.2
Temperature sensor
The
Temperature sensor
secondary folder appears only if the corresponding sensor is enabled in the folder
Internal sensors
and includes the following parameters:
Filter type
Temperature offset
Minimum change of value to send [K]
Cyclic sending interval
Threshold 1
Threshold 2
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 19
7.2.2.1
Parameter and communication object tables
Parameter name
Filter type
Temperature offset
Minimum change of value to send [K]
Cyclic sending interval
Threshold 1
Value [°C]
Threshold 2
Value [°C]
Hysteresis
Cyclic sending interval
Application manual
KNX room temperature controller EK-EP2-TP
Conditions
Temperature sensor = enabled
Values
low
medium
high
Low = average value every 4 measurements
Medium = average value every 16 measurements
High = average value every 64 measurements
Temperature sensor = enabled
0°C
[range -2,5°C … +2,5°C]
Temperature sensor = enabled
0,5
[range 0 …5]
If the parameter is set to 0 (zero),no value is sent after a change.
Temperature sensor = enabled
no sending
[other values in the range 30 s … 120 min]
Temperature sensor = enabled
not active
below above
Temperature sensor = enabled,
Threshold 1 = below or above
[range
7
0 … 50]
Temperature sensor = enabled
not active
below above
45
[range
0 … 50]
Temperature sensor = enabled,
Threshold 2 = below or above
Temperature sensor = enabled,
Threshold 1 and/or Threshold 2
= below or above
Temperature sensor = enabled,
Threshold 1 and/or Threshold 2
= below or above
0,4 K
[other values between 0,2 K and 3 K]
no sending
[other values in the range 30 s … 120 min]
Object name Conditions Dim.
2 Bytes
Flags
CR-T--
DPT
[9.001] temperature (°C)
Comm.
Obj. No.
3
Temperature value
Temperature threshold1 - Switch
Temperature threshold 2- Switch
Temperature sensor = enabled
Temperature sensor = enabled,
Threshold 1 = below or above
Temperature sensor = enabled,
Threshold 2 = below or above
1 Bit
1 Bit
CR-T--
CR-T--
[1.001] switch
[1.001] switch
116
117
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 20
Application manual
KNX room temperature controller EK-EP2-TP
Acquisition filter
The acquisition filter calculates an average with a series of measured values before sending on the bus. The parameter can have the following values:
low = average value every 4 measurements;
medium = average value every 16 measurements;
high = average value every 64 measurements.
Correction of the measured temperature
The sampling of the temperature value occurs every 10 seconds, while the display is updated every minute.
During the configuration with ETS the opportunity is given to correct the measured temperature value within the offset range of - 2.5 °C ... + 2.5 °C (step: 0.1 K).
7.2.3
Brightness sensor
The
Brightness sensor
secondary folder appears only if the corresponding sensor is enabled in the folder
Internal sensors
and includes the following parameters:
Filter type
Sensor value multiplier (1÷255) x 0,1
Minimum change of value to send [%]
Cyclic sending interval
Threshold 1
Threshold 2
Value [Lux]
Hysteresis
Using the brightness value
The value measured by the brightness sensor integrated in the device may be used for:
sending the value on the KNX bus through a communication object;
automatically adjusting the light intensity emitted by the backlight of the display.
7.2.3.1
Parameter and communication object tables
Parameter name
Filter type
Sensor value multiplier (1÷255) x 0,1
Minimum change of value to send [Lux]
Cyclic sending interval
Threshold 1
Conditions
Brightness sensor = enabled
Values
low
medium
high
Low = average value every 4 measurements
Medium = average value every 16 measurements
High = average value every 64 measurements
Brightness sensor = enabled
10
[other values in the range
1… 255]
Brightness sensor = enabled
50
[other values in the range 0
… 670760]
If the parameter is set to 0 (zero), no value is sent after a change.
Brightness sensor = enabled
no sending
[other values in the range 30 s … 120 min]
Brightness sensor = enabled
not active
/ below / above
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 21
Parameter name
Value [Lux]
Threshold 2
Value [Lux]
Hysteresis
Cyclic sending interval
Object name
Brightness value -
Light threshold 1 - Switch
Light threshold 2 - Switch
Conditions
Brightness sensor = enabled,
Threshold 1 = below or above
Values
500
[other values in the range
0 … 670760]
Brightness sensor = enabled
not active
/ below / above
Brightness sensor = enabled,
Threshold 2 = below or above
500
[other values in the range
0 … 670760]
Threshold 1 = below or above,
Threshold 2 = below or above
Brightness sensor = enabled, Soglia
1 e/o Soglia 2 = sotto o sopra
50 lux
[other values in the range
5 … 200 Lux]
The value of the parameter Hysteresis is common for both parameters Threshold 1 and Threshold 2.
no sending
[other values in the range30 s … 120 min]
The value of the parameter Cyclic sending interval is common for both parameters
Threshold 1 and Threshold 2.
Conditions
Brightness sensor = enabled
Brightness sensor = enabled,
Threshold 1 = below or above
Brightness sensor = enabled,
Threshold 2 = below or above
Application manual
KNX room temperature controller EK-EP2-TP
Dim.
2 Byte
Flags
CR-T--
DPT
[9.004] lux (Lux)
Comm.
Obj. No.
1
1 Bit
1 Bit
CR-T--
CR-T--
[1.001] switch
[1.001] switch
20
37
7.3
Inputs
The folder
Inputs
allows you to configurate one or two variables (either digital or analogic) depending on the digital signals or the temperature sensors connected to the terminal blocks of the inputs. The physical values or the detected states can be used locally by the device for temperature control functions and/or transmitted on the bus for other purposes. The folder includes the parameters for configuring independently the inputs 1 and 2. The two inputs are identical; for simplicity in the following only parameters and communication objects of a single input are described.
7.3.1
Input X
The folder
Input X
(X = 1, 2) includes the following parameters:
Input X
Contact type
Filter type
Temperature offset
Cyclic sending interval
Minimum change of value to send (K)
Threshold 1
Value [°C]
Threshold 2
Value [°C]
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 22
Hysteresis
Cyclic sending interval
Application manual
KNX room temperature controller EK-EP2-TP
7.3.2
Parameter and communication object tables
Parameter name
Input X
Contact type
Debounce time
Type
Filter type
Offset temperature
Minimum change of value to send [K]
Cyclic sending interval
Threshold 1
Vaue [°C]
Threshold 2
Conditions Values
disabled
[DI] generic digital input
[DI] window contact sensor
[DI] card holder contact sensor
[DI] anticondensation sensor
[AI] coil battery temperature sensor
[AI] room temperature sensor
[AI] antistratification temperature sensor
[AI] floor surface temperature sensor
[AI] outdoor temperature sensor
[AI] generic (NTC) temperature sensor
The [DI] prefix indicates a digital input, the [AI] prefix an analogic input.
Input X = [DI]
…
NO (normally open)
NC (normally closed)
This parameter is always available when the input is configured as digital.
Input X = [DI
] …
00:00:00.200 hh:mm:ss.fff
[range 00:00:00.000
… 00:10:55.350]
This parameter is always available when the input is configured as digital. The field has format hh:mm:ss:fff (hours : minutes : seconds . milliseconds): the default value
00:00:00.200 corresponds to 200 milliseconds.
Input X = [DI] generic digital input
send values or sequences
dimming shutter or venetian blind scene counter
This parameter is available only when the input is configured as generic digital..
Input X
= [AI] … low
medium
high
This parameter is always available when the input is configured as analogic.
Low = average value every 4 measurements
Medium = average value every 16 measurements
High = average value every 64 measurements
Input
X = [AI] …
0°C
[range -2,5°C … +2,5°C]
This parameter is always available when the input is configured as analogic.
0,5
[range 0
…5]
This parameter is always available when the input is configured as analogic. When set to 0 (zero), no value is sent at a change.
Input X different from disabled
no sending
[other values in the range
30 s … 120 min]
Input X =
[AI] …
not active
/ below / above
This parameter is always available when the input is configured as analogic.
Input
X = [AI] …
Threshold 1 = below or above
7
[range 0
… 50]
Input
X = [AI] …
not active
/ below / above
This parameter is always available when the input is configured as analogic.
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 23
Parameter name
Application manual
KNX room temperature controller EK-EP2-TP
Value [°C]
Conditions
Input X
= [AI] …
Threshold 2 = below or above
Values
45
[range 0
… 50]
Hysteresis
Input
X = [AI] …
Threshold 1 = below or above
Threshold 2 = below or above
0,4 K
[other values in the range
0,2 K … 3 K]
Cyclic sending interval
Input
X = [AI] …
Threshold 1 = below or above
Threshold 2 = below or above
no sending
[other values in the range
30 s … 120 min]
Object name
Input 1 – Lock command
Input 2 - Lock command
Window contact sensor (from input 1)
Window contact sensor (from input 2)
Anticondensation sensor (from input 1)
Anticondensation sensor (from input 2)
Card holder contact sensor
(from input 1)
Card holder contact sensor
(from input 2)
Coil battery temperature sensor (from input 1)
Coil battery temperature sensor (from input 2)
Conditions Dim. Flags DPT
Comm.
Obj. No.
Input 1 = [DI] digital generic input
1 Bit CR-T--
[1.xxx] 1 Bit
80
Input 2 = [DI] digital generic input
1 Bit CR-T--
[1.xxx] 1 Bit
97
Input 1 = [DI] windows contact sensor
1 Bit CR-T--
[1.019] window/door
126
Input 2 = [DI] windows contact sensor
1 Bit CR-T--
[1.019] window/door
127
If both inputs (1 and 2) are configured in the same way, only the first one is used by the device.
Input 1 = [DI] anticondensation sensor
1 Bit CR-T-- [1.005] alarm 128
Input 2 = [DI] anticondensation sensor
1 Bit CR-T-- [1.005] alarm 129
If both inputs (1 and 2) are configured in the same way, only the first one is used by the device.
Input 1 = [DI] card holder contact sensor
1 Bit CR-T-- [1.018] occupancy 130
Input 2 = [DI] card holder contact sensor
1 Bit CR-T-- [1.018] occupancy 131
If both inputs (1 and 2) are configured in the same way, only the first one is used by the device.
Input 1 = [AI] coil battery temperature sensor
2 Byte CR-T--
[9.001] temperature
(°C)
120
Input 2 = [AI] coil battery temperature sensor
2 Byte CR-T--
[9.001] temperature
(°C)
123
If both inputs (1 and 2) are configured in the same way, only the first one is used by the device.
Temperature value sensor
(from input 1)
Input 1 = [AI] room temperature sensor
2 Byte CR-T--
[9.001] temperature
(°C)
120
Temperature value sensor
(from input 2)
Input 2 = [AI] room temperature sensor
2 Byte CR-T--
[9.001] temperature
(°C)
123
If both inputs (1 and 2) are configured in the same way, only the first one is used by the device.
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 24
Object name
Antistratification temperature sensor (from input 1)
Antistratification temperature sensor (from input 2)
Floor surface temperature sensor (from input 1)
Floor surface temperature sensor (from input 2)
Outdoor temperature sensor
(from input 1)
Outdoor temperature sensor
(from input 2)
Temperature value sensor
(from input 1)
Temperature value sensor
(from input 2)
Temperature threshold 1 sensor 1 - Switch
Temperature threshold 2 sensor 1 - Switch
Temperature threshold 1 sensor 2 - Switch
Temperature threshold 2 sensor 2 - Switch
Application manual
KNX room temperature controller EK-EP2-TP
Conditions Dim. Flags DPT
Comm.
Obj. No.
Input 1 = [AI] antistratification temperature sensor
2 Byte CR-T--
[9.001] temperature °C
120
Input 2 = [AI] antistratification temperature sensor
2 Byte CR-T--
[9.001] temperature °C
123
If both inputs (1 and 2) are configured in the same way, only the first one is used by the device.
Input 1 = [AI] floor surface temperature sensor
2 Byte CR-T--
[9.001] temperature °C
120
Input 2 = [AI] floor surface temperature sensor
2 Byte CR-T--
[9.001] temperature °C
123
If both inputs (1 and 2) are configured in the same way, only the first one is used by the device.
Input 1 = [AI] outdoor temperature sensor
2 Byte CR-T--
[9.001] temperature °C
120
Input 2 = [AI] outdoor temperature sensor
2 Byte CR-T--
[9.001] temperature °C
123
If both inputs (1 and 2) are configured in the same way, only the first one is used by the device.
Input 1 = [AI] generic (NTC) temperature sensor
2 Byte CR-T--
[9.001] temperature °C
120
Input 2 = [AI] generic (NTC) temperature sensor
2 Byte CR-T--
[9.001] temperature °C
123
If both inputs (1 and 2) are configured in the same way, only the first one is used by the device.
Input
1 = [AI] …
Threshold 1 = below or above,
Threshold 2 = below or above
1 Bit CR-T-- [1.001] switch 121
Input
1 = [AI] …
Threshold 1 = below or above,
Threshold 2 = below or above
1 Bit CR-T-- [1.001] switch 122
Input 2=
[AI] …
Threshold 1 = below or above,
Threshold 2 = below or above
1 Bit CR-T-- [1.001] switch 124
Input 2
= [AI] …
Threshold 1 = below or above,
Threshold 2 = below or above
1 Bit CR-T-- [1.001] switch 125
7.4
External sensors (from bus)
As “external sensors” are intended KNX-devices (or conventional sensors interfaced to the bus through KNX devices) which send states or values to the room temperature controller via the bus. Enabling an external sensor, without connecting the corresponding communication object, generates a permanent alarm on the display and suspends the thermoregulation function.
The folder
External sensors (from bus)
includes the following parameters:
Room temperature
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 25
Antistratification temperature
Outdoor temperature
Floor surface temperature
Anticondensation
Window contact X (X = 1, 2)
Presence sensor X (X = 1, 2)
Card holder contact
Analog sensor timeout
Digital sensor timeout
The folder does not have any secondary folder.
Application manual
KNX room temperature controller EK-EP2-TP
7.4.1
Parameter and communication object tables
Parameter name
Room temperature
Antistratification temperature
Outdoor temperature
Air quality
Coil temperature
Floor surface temperature
Analogic sensors timeout
Anticondensation
Window contact 1
Window contact 2
Presence sensor 1
Conditions Values
disabled
/ enabled
It enables a bus temperature sensor. The measured value can be used to calculate a weighted average value in combination with the temperature sensor integrated into the device or a temperature sensor connected to a device input.
disabled
/ enabled
I t enables a temperature bus sensor to carry out the antistratification function.
disabled
/ enabled
I t enables an outdoor temperature bus sensor to display the measured value on the display. This is alternative to an outdoor temperature sensor connected to a device input: the parameter appears only if the external temperature sensor is disabled in the Inputs folder.
disabled
/ enabled
I t enables an air quality bus sensor to display the measured value (CO
2 concentration) on the display.
disabled
/ enabled
I t enables a bus sensor for measuring the conveying fluid temperature at the coil for heat exchange. The acquisition of the value allows realizing the hot- start function of a fan.
disabled
/ enabled
I t enables a bus sensor for measuring the surface temperature of a floor heating system. The acquisition of the value allows to realize the function of surface temperature limitation.
00:05:00hh:mm:ss
[range
00:00:00 … 18:12:15]
The field has format hh:mm:ss (hours : minutes : seconds): the default value
00:05:00 corresponds to a timeout of 5 minutes. The value 00:00:00 means that the timeout of the analogic sensors is disabled.
disabled
/ enabled
I t enables a bus sensor for detecting the condensation.
disabled
/ enabled
I t enables a bus sensor for detecting the state of opening / closing of a window or a door.
disabled
/ enabled
I t enables a bus sensor for detecting the state of opening / closing of a window or a door.
disabled
/ enabled
I t enables a bus sensor for detecting the presence / absence of people within a room.
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 26
Parameter name
Presence sensor 2
Card holder contact
Digital sensors timeout
Application manual
KNX room temperature controller EK-EP2-TP
Conditions Values
disabled
/ enabled
I t enables a bus sensor for detecting the presence / absence of people within a room.
disabled
/ enabled
I t enables a bus sensor for detecting the presence / absence of people in a hotel room provided with a card holder.
00:05:00hh:mm:ss
[range
00:00:00 … 18:12:15]
The field has format hh:mm:ss (hours : minutes : seconds): the default value
00:05:00 corresponds to a timeout of 5 minutes. The value 00:00:00 means that the timeout of the digital sensors is disabled.
Object name
Room temperature (from bus)
Antistratification temperature (from bus)
Outdoor temperature (from bus)
Coil temperature (from bus)
Floor temperature (from bus)
Anticondensation (from bus)
Windows contact sensor 1 (from bus)
Windows contact sensor 2 (from bus)
Presence sensor 1 (from bus)
Presence sensor 2 (from bus)
Contact of card holder (from bus)
Conditions
enabled enabled enabled enabled enabled enabled enabled enabled enabled enabled enabled
Dim.
2 Byte
2 Byte
2 Byte
2 Byte
2 Byte
1 Bit
1 Bit
1 Bit
1 Bit
1 Bit
1 Bit
Flags
C-W---
C-W---
C-W---
C-W---
C-W---
C-W---
C-W---
C-W---
C-W---
DPT
[9.001] temperature (°C)
[9.001] temperature (°C)
[9.001] temperature °C
[9.001] temperature (°C)
[9.001] temperature (°C)
[1.001] switch
[1.019] window/door
[1.019] window/door
C-W--- [1.018] occupancy
C-W--- [1.018] occupancy
[1.001] switch
Comm. Obj.
No.
134
137
138
140
141
146
143
144
132
133
145
About the sensor timeout
The system of internal control of the thermostat monitors cyclically the updating status of the values of the external sensors (from bus) and the inputs when the timeout setting expires. In case no updated value has been received, the regulation function is suspended, an alarm is displayed on the display through the symbol and the corresponding alarm code (see also the list of alarms in the paragraph Diagnostics).
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 27
Application manual
KNX room temperature controller EK-EP2-TP
7.5
Weighted temperature value
The
Weighted temperature value
folder appears only if two sensors for measuring the room temperature are enabled and includes the following parameters:
Main source for temperature value
Additional source temperature value
Relative weight
Minimum change of value to send [K]
Cyclic sending interval
7.5.1
Parameter and communication object tables
Parameter name
Main source for temperature value
Additional source temperature value
Relative weight
Minimum change of value to send [K]
Cyclic sending interval
Conditions Values
*
*) The values that can be set depend on enabling the internal sensor, the inputs or the external sensors (from bus).
*
*) The values that can be set depend on enabling the internal sensor, the inputs or the external sensors (from bus).
100% main sensor
90% / 10%
80% / 20%
70% / 30%
60% / 40%
50% / 50%
40% / 60%
30% / 70%
20% / 80%
10% / 90%
100% additional sensor
0,5
[other values in the range
0 … 5 K]
If the parameter is set to 0 (zero), no value is sent at the change.
no sending
[other values in the range 30 s … 120 min]
Object name
Weighted temperature
Conditions
Cyclic sending interval different than no sending
Dim.
2 Byte
Flags
CR-T--
DPT
[9.001] temperature °C
Comm.
Obj. No.
147
About the weighted temperature
The device allows the acquisition of the room temperature in three ways:
1) from the temperature sensor integrated in the device;
2) from an external temperature sensor connected to a device input configured as analogic (Inputs
Input 1 or 2 = [AI] room temperature sensor);
3) via bus from another KNX device, e.g. from an ekinex pushbutton (External sensors (from bus)
Room temperature = enabled);
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 28
Application manual
KNX room temperature controller EK-EP2-TP
To optimize or correct the room temperature regulation in special cases (in large rooms, in presence of strong asymmetry of the temperature distribution, when the installation of the device is in a position not suitable, etc.), the device can then use a weighted average between two temperature values. The weights are assigned by the parameter
Relative weight
that assigns a ratio of the two values.
7.6
LC-display
The folder
LCD display
includes the following parameters:
Backlight intensity
Automatic backlight dimming
Energy saving
Visualisation type
Time before energy saving mode
Backlight when in energy saving mode
Behaviour on button press
Temperature setpoint
Energy saving mode
After a configurable time interval, the room temperature controller switches from normal to energy saving operation. In this display mode:
the backlight intensity may be reduced;
the information content to be displayed may be reduced da visualizzare può essere ridotto (two options: partial and temperature only).
Backlight
The default backlight of the display can be configured according to the installation location and light conditions of the room. The backlight intensity can be set to a fixed value (in %) or automatically adjusted by means of the brightness sensor integrated in; for this function it is necessary to enable the brightness sensor.
Information to be displayed
The actual temperature is always displayed; in addition, and depending on individual preferences, other information can be displayed in sequence.
7.6.1
Parameters
Parameter name
Backlight intensity
Automatic backlight dimming
Energy saving
Conditions Values
10% / 20% / 30% / 40% /
50%
/
60% / 70% / 80% / 90% / 100%
Internal sensors
Brightness sensors = enabled
disabled
/ enabled
It enables the automatic correction of the intensity of the backlight of the display according to the room brightness detected by the corresponding sensor.
disabled
/ enabled
If the parameter Energy saving = enabled, after a certain time interval the device automatically reduces the backlight intensity and possibly the information content displayed.
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 29
Parameter name
Visualisation type
Time before energy saving mode
Backlight when in energy saving mode
Behaviour on button press
Application manual
KNX room temperature controller EK-EP2-TP
Conditions
Energy saving = enabled
Values
full
temperature only
In addition to the digits,
“temperature only” includes the symbol (°C or °F).
Energy saving = enabled
10 s
/ 15 s / 30 s
45 s / 1 min
Energy saving = enabled off / 2% / 5% / 10% /
15% / 20% /
25%
/ 30%
Energy saving = enabled
backlight only
backlight and button function
It defines the reaction at the first press of a rocker when the device is in energy saving mode.
At least one temperature sensor enabled
(internal, external from bus, from an input)
enable
/ disabled
Temperature setpoint
7.7
Leds
Each pushbutton channel has four programmable leds; for example, for status feedback of the controlled loads or for orientation nightlight. The light emitted by the leds is diffused by means of an appropriate lightguide.
The folder
Led
includes the following parameters:
Leds intensity from bus
Leds intensity
Leds intensity correlation
Led first colour XY (X = 1, 2; Y= A, B)
Led second colour XY (X = 1, 2; Y= A, B)
Off delay
Always
Blinking
Blinking period / type
Signal from bus
Technical alarm
7.7.1
Parameter and communication object tables
Parameter name
Leds intensity from bus
Leds intensity
Conditions Values
no
/ yes
It enables receiving from the bus of the light intensity value emitted by the Leds.
Leds intensity from bus = no
50%
[range 0%
… 100%]
It allows setting the light intensity value emitted by the leds (if not received from the bus).
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 30
Parameter name
Leds intensity correlation
Led first colour XY
Off delay
Always
Blinking
Blinking period / type
Signal from bus
Led second colour XY
Off delay
Always
Blinking
Application manual
KNX room temperature controller EK-EP2-TP
Conditions
Brightness sensor = enabled
Values
high inverse medium inverse low inverse
none
low direct medium direct high direct
It allows setting the kind of correlation between the intensity of light emitted by the leds and the brightness measured in the room (by the integrated sensor) or received from the bus.
fixed
when contact close
status from bus
X = 1, 2; Y= A, B
Led first colour XY = when contact close
00:00:02:00 hh:mm:ss:ff
[other values in the range
00:00:00:00 … 01:49:13:50]
Led first colour XY = fixed
off
/ on
Led first colour XY = status from bus
no
/ yes
Led first colour XY = status from bus,
Blinking = yes
0,25 s on / 0,25 s off
0,25 s on / 0,75 s off
0,5 s on / 0,5 s off
0,75 s on / 0,25 s off
0,5 s on / 1,5 s off
1 s on / 1 s off
1,5 s on / 0,5 s off
1 s on / 3 s off
2 s on / 2 s off
3 s on / 1 s off
Led first colour XY = status from bus
not inverted
/ inverted fixed
when contact closed
status from bus
X = 1, 2; Y= A, B
00:00:02:00
[other values in the range
00:00:00:00 … 01.49.13:50]
Value in hh:mm:ss:ff.
Led second colour XY = fixed
Led second colour XY = status from bus
off no
/ on
/ yes
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 31
Parameter name
Blinking period / type
Signal from bus
Technical alarm
Object name
Technical alarm
Leds intensity percentage
Rocker X- Led first colour A
Rocker X- Led second colour
A
Rocker X- Led first colour B
Rocker X- Led second colour
B
Application manual
KNX room temperature controller EK-EP2-TP
Conditions
Led second colour XY = status from bus,
Blinking = yes
Values
0,25 s on / 0,25 s off
0,25 s on / 0,75 s off
0,5 s on / 0,5 s off
0,75 s on / 0,25 s off
0,5 s on / 1,5 s off
1 s on / 1 s off
1,5 s on / 0,5 s off
1 s on / 3 s off
2 s on / 2 s off
3 s on / 1 s off
Led second colour XY = status from bus
not inverted
/ inverted
disabled
/ enabled
It enables the communication object nr. 0 "Technical alarm" that allows to activate an alarm signal via a bus telegram. The flashing led indicates that the alarm condition is active.
Conditions
Leds intensity from bus = yes
Led first colour XA = status from bus
Led second colour XA = status from bus
Led first colour XB = status from bus
Led second colour LED XB = status from bus
Dim.
1 Bit
1 Bit
1 Bit
1 Bit
1 Bit
1 Bit
Flags
C--W-
C--W-
DPT
[1.005] alarm
[5.001] percentage
CRWTU- [1.001] switch
CRWTU- [1.001] switch
CRWTU- [1.001] switch
CRWTU- [1.001] switch
Comm.
Obj. No.
0
2
38 (X = 1)
76 (X = 2)
39 (X = 1)
77 (X = 2)
40 (X = 1)
78 (X = 2)
41 (X = 1)
79 (X = 2)
7.8
Temperature control
The
Temperature control
folder includes the following secondary folders:
Settings
Heating
Cooling
Ventilation
Scenes
The
Cooling
and
Ventilation
secondary folders appear only if in the
Settings
folder the parameter
Thermostat function is set to the value
both heating and cooling
or
cooling
.
The
Scenes
secondary folder appears only if in the
Settings
secondary folder the parameter Scenes is set to the value
enabled
.
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 32
7.8.1
Settings
The
Settings
folder includes the following parameters:
Thermostat function
Command Communication Object
Heating – cooling switchover
Setpoint Cyclic sending interval
Max manual temperature change
Saving timeout (manual change)
End of manual operation
Max setpoint temperature change
Scenes
Valve protection function
Frequency
Time interval
Application manual
KNX room temperature controller EK-EP2-TP
7.8.1.1
Parameter and communication object tables
Parameter name
Thermostat function
Command Communication Object
Heating
– cooling switchover
Setpoint cyclic sending interval
Max manual temperature change
Saving timeout (manual change)
End of manual operation
Max setpoint temperature change
Conditions Values
heating
cooling both heating and cooling
Thermostat function = both heating and cooling
separated
/ unique
Thermostat function = both heating and cooling manual
from bus
automatic
no sending
[other values in the range
30 s … 120 min]
The setpoint value that can be sent cyclically is the actual one, depending on the operating mode set manually by the user or automatically by another KNX supervising device with the possibility of time scheduling. The actual setpoint value takes also into account the actual state of the contacts window and presence detection (if the corresponding functions are enabled).
not allowed, ± 1°C, ± 2°C,
± 3°C
, ± 4°C, ±
5°C, ± 6°C, ± 7°C, ± 8°C, ± 9°C, ± 10°C
It defines the maximum range allowed for the manual change of the temperature value.
6 s
[other values in the range
2s … 12 s]
It defines the time interval to wait for a confirmation of a manual change (see previous parameter). If the time interval elapses without confirmation, the device automatically returns to the previous state without saving the change.
General
Device operation as = stand-alone
till first telegram from bus
[other values in the range
30 min … 48 h] not allowed, ± 1°C, ± 2°C, ± 3°C, ± 4°C, ±
5°C, ± 6°C, ± 7°C, ± 8°C,
± 9°C
, ± 10°C
It defines the maximum time allowed for changing the values of temperature setpoint in the several operating modes.
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 33
Parameter name
Scenes
Valve protection function
Frequency
Time interval
Nome oggetto
Actual setpoint
Heating/cooling status out
Heating/cooling status in
HVAC mode in
HVAC forced mode in
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application manual
KNX room temperature controller EK-EP2-TP
Conditions Values
disabled
/ enabled
Valve protection function = enabled
disabled
/ enabled
It enables the function that activates the drive for the valve control during periods of inactivity of the system.
Valve protection function = enabled once a day
once a week
once a month
10 s
[other values in the range 5 s … 20 min]
Conditions Dim. Flags DPT
Comm.
Obj.
No.
152 2 Byte CR-T-- [9.001] temperature (°C)
Thermostat function = both heating and cooling;
Heating
– cooling switchover = manual or automatic
1 Bit CR-T-- [1.100] heating/cooling 148
L’oggetto di comunicazione è trasmesso sul bus all’evento di commutazione elaborato internamente dal regolatore.
[1.100] DPT Heat/Cool 1 Bit
0 = Cool
1 = Heating
Thermostat function = both heating and cooling;
Heating
– cooling switchover = from bus
1 Bit C-W--- [1.100] heating/cooling 149
The communication object is received by the bus
. All’evento di commutazione i regolatori interni degli stadi primario e ausiliario (se abilitato) commutano il modo di conduzione. Il modo di conduzione attivo è segnalato dal l’apposito simbolo sul display.
1 Byte C-W--- [20.102] HVAC mode
The device receives the operating mode (HVAC mode) from a bus device with function of supervisor. The operating mode received through this communication object can be later modified by the user (in questo caso il termostato ambiente passa in controllo manuale).
150
1 Byte C-W--- [20.102] HVAC mode 151
L’oggetto di comunicazione permette di ricevere il modo operativo analogamente a quanto accade con l’oggetto di comunicazione Modo HVAC in; la differenza è che il modo operativo ricevuto tramite questo oggetto (ad eccezione del comando AUTO) non può essere successivamente modificato dall’utente. L’utente può modificare il modo solamente dopo che il
Modo HVAC forzato in ha inviato il comando AUTO.
Application Manual
Page 34
Application manual
KNX room temperature controller EK-EP2-TP
About the heating/cooling terminals
The application functions of the room temperature controller configurable with ETS are particularly suitable for the control through general-purpose or dedicated KNX actuators of the following heating/cooling terminals:
• radiators;
• elettrical heaters;
• fancoils;
• radiant panels;
• dehumidification units;
• radiant panels + radiators (as auxiliary system);
• radiant panels + fancoils (as auxiliary system);
• radiant panels + dehumidification units.
About the heating/cooling switchover
The switchover between the two seasonal modes (heating / cooling) may happens as follows:
1) manually on the device by the end user;
2) automatically by the device;
3) from the KNX bus through a dedicated communication object.
Manual switch-over (mode 1)
The manual switch-over is suitable for bus systems with one or a limited number of room temperature controllers. If the devices have been configured for this purpose, the user does the switch-over manually on the device (that acts as a "master" for the switch-over function); the device sends on the bus the output communication object [DPT 1.100 heat/cool] that switches possibly other room temperature controllers
("slave" devices) connected through a dedicated group address.
Automatic switch-over (mode 2)
The automatic switch-over is suitable for a 4-pipe hydraulic configuration of the heating/cooling installation
(used e.g. for fan-coil units or ceiling radianti panels). Also in this case the information can be sent on the bus with the output communication object [DPT 1.100 heat/cool]; the difference from the first mode is that switching is performed automatically on the basis of a comparison between the values of the actual temperature and the setpoint temperature. In this mode, the manual switching by the user is disabled.
The automatic switch-over is realised with the introduction of a neutral zone according to the scheme in the picture below.
OFF (protection)
ECONOMY STAND-BY COMFORT
32 °C
28 °C
26 °C
24 °C
Dead zone
20 °C
18 °C
16 °C
8 °C
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Neutral zone and example of setpoint values correctly distributed
Application Manual
Page 35
Application manual
KNX room temperature controller EK-EP2-TP
Until the actual (measured) temperature is located below the setpoint value for the heating, the operation is heating; in the same way, if the actual value (measured) is greater than the setpoint value for the cooling, the mode is cooling. If the actual value (measured) temperature is within the dead zone, the previous mode of operation remains active; the switching point of the operation mode for heating / cooling must take place in correspondence with the current setpoint for the active HVAC, in the same way the switching cooling / heating must take place at the setpoint for heating.
Switch-over via KNX bus (mode 3)
The switch-over from the bus requires that the command is received from another KNX device, e.g. another room temperature controller or a Touch&See unit configured to this purpose. The other device works in this way as a “supervisor” device: the switch-over is triggered by the input communication object [DPT 1.100 heat/cool]. In this mode the manual switch-over by an enduser is disabled. Thanks to this mode, the supervising device is able to control the “slave” devices with time-scheduled programs, extending their functionality to that of a chronothermostat (centrally controlled by the supervising device).
About the valve protection function
The function is suitable for heating and cooling systems that use water as thermal conveying fluid and are provided with motorized valves for the interception of a zone or of a single room. Long periods of inactivity of the system can lead to the blockage of valves: to prevent this, the room temperature controller may periodically send a command to open / close the valve in the period of inactivity of the system. This possibility is made available in the application program by means of the parameter "Valve protection function", further defined by the frequency and duration of the valve control.
7.8.2
Heating
The
Heating
folder includes the following parameters:
Comfort temp. setpoint [°C]
Standby temperature setpoint [°C]
Economy temp. setpoint [°C]
Building protection temp. setpoint [°C]
Heating type
Control type
Hysteresis
Cyclic sending interval
Min. change of value to send [%]
PWM cycle time
Proportional band [0,1 K]
Integral time [min]
Floor temperature limitation
Temperature limit [°C]
Hysteresis [K]
Auxiliary heating
Communication object
Disabled from bus
Offset from setpoint
Hysteresis
Cyclic sending interval
Ventilation for auxiliary heating
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 36
7.8.2.1
Parameter and communication object tables
Application manual
KNX room temperature controller EK-EP2-TP
Conditions:
Settings
Thermostat function = heating or both heating and cooling.
Parameter name Conditions
Comfort temp. setpoint [°C]
Standby temperature setpoint [°C]
Economy temp. setpoint [°C]
Values
21
[range
10 … 50]
18
[range
10 … 50]
For a correct operation of the device the standby temperature setpoint has to be < comfort temperature setpoint.
16
[range
10 … 50]
Building protection temp. setpoint [°C]
Heating type
Control type
Hysteresis
Cyclic sending interval
Min. change of value to send [%]
PWM cycle time
Proportional band [0,1 K]
For a correct operation of the device the economy temperature setpoint has to be < standby temperature setpoint.
7
[range
2 … 10]
radiators
elettric fan-coils floor radiant panels ceiling radiant panels
It defines the terminal used for the thermal exchange in the room. The choice affects the parameters of the PWM control algorithm (Proportional band and Integral time) and the control options.
2 point hysteresis
PWM (pulse width modulation) continuous
Control type = 2 point hysteresis
0,3 K
[other values in the range 0,2 K
… 3 K]
Control type = 2 point hysteresis, continuous
no sending
[other values in the range
30 s … 120 min]
Control type = continuous
10
[range
0 … 100]
Control type = PWM
15 min
[range 5
… 240 min]
Control type = continuous or PWM
*
[range 0
… 255]
The value is in tenths of Kelvin (K) degree.
*) The field contains a preset value that depend on the selected heating type (the value can be modified):
radiators: 50 ( 5 K)
elettric: 40 (4 K)
fan-coils: 40 (4 K)
floor radiant panels: 50 (5 K)
ceiling radiant panels: 50 (5 K)
The value of the parameter Proportional band represents the max difference between the setpoint temperature and the measured temperature that causes the max control output.
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 37
Parameter name
Integral time [min]
Floor temperature limitation
Temperature limit [°C]
Hysteresis [K]
Auxiliary heating
Communication object
Disabled from bus
Offset from setpoint
Hysteresis
Cyclic sending interval
Ventilation for auxiliary heating
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application manual
KNX room temperature controller EK-EP2-TP
Conditions
Control type = continuous or PWM
Values
*
[other values in the range 0
… 255 min]
*) The field contains a preset value that depend on the selected heating type (the value can be modified):
radiators: 150 min
elettric: 100 min
fan-coils: 90 min
floor radiant panels: 240 min
ceiling radiant panels: 180 min
Heating type = floor radiant panels,
Inputs
Input 1 or Input 2 = [AI] floor surface temperature sensor or
External sensors
Floor surface temperature sensor = enabled
disabled
/ enabled
Il parametro abilita la funzione di limitazione della temperatura superficiale di un pavimento riscaldante. Per la funzione è indispensabile misurare la temperatura superficiale del pavimento mediante l’abilitazione del sensore di temperatura corrispondente nella scheda Sensori esterni (dal bus) o nella scheda Ingressi.
Important!
This function does not replace the overtemperature protection usually installed in hydronic floor systems, realized with the proper safety thermostat.
Floor temperature limitation = enabled
29
[range 20
… 40]
According to EN 1264 a maximum allowed temperature is prescribed for the surface of a floor heating system:
•
T(sup) max ≤ 29°C per le zone di normale occupazione;
•
T(sup) max ≤ 35°C per le zone periferiche degli ambienti.
National standard may limit those temperatures to lower values. Per zone periferiche si intendono fasce situate generalmente lungo i muri dell’ambiente rivolti verso l’esterno dell’edificio con larghezza massima di 1 m.
Floor temperature limitation = enabled
0,3 K
[other values in the range
0,2 K … 3 K]
Before quitting from the alarm status, the device waits until the surface temperature decreases under the threshold set offset pari al valore di isteresi.
disabled
/ enabled
Auxiliary heating = enabled
separated
unique
Auxiliary heating = enabled
Auxiliary heating = enabled
no
/ yes
It enables the activation and deactivation of the function through a telegram sent on the bus by a supervising device.
0,6 K
[other values in the range
0 …3 K]
Auxiliary heating = enabled
0,3 K
[other values in the range
0,2 K … 3 K]
Auxiliary heating = enabled
no sending
[other values in the range 30 s
… 120 min]
Heating type = floor radiant panels or ceiling radiant panels
disabled
/ enabled
This option allows matching a system with high inertia as the floor radiant panels
(hydronic version) to a system with low inertia as the fan-coils.
Application Manual
Page 38
Application manual
KNX room temperature controller EK-EP2-TP
Object name
Comfort setpoint (heating)
Standby setpoint (heating)
Economy setpoint (heating)
Building protection setpoint
(heating)
Auxiliary heating output command
Conditions Dim. Flags DPT
Comm.
Obj.
No.
153
Heating out command
Auxiliary heating enable
Control type = 2 points hysteresis or
PWM
Control type = continuous
Auxiliary heating = enabled
Auxiliary heating = enabled,
Disabled from bus = yes
2 Byte
2 Byte
2 Byte
2 Byte
1 Bit
1 Byte
1 Bit
1 Bit
CRWTU-
CRWTU-
CRWTU-
CRWTU-
CR-T--
CR-T--
CR-T--
C-W---
[9.001] temperature (°C)
[9.001] temperature (°C)
[9.001] temperature (°C)
[9.001] temperature (°C)
[1.001] switch
[5.001] percentage (0..100%)
[1.001] switch
[1.003] enable
155
157
159
161
163
165
About the floor temperature limitation function
The floor heating system (warm water version) provides plastic pipes embedded in the concrete layer or placed directly under the final coating of the floor (light or "dry" system) filled by heated water. The water releases heat to the final coating that heats the room by radiation. The standard EN 1264 Floor heating (Part
3: Systems and components - Dimensioning) prescribes a maximum allowed temperature (T
Smax
) for the surface of the floor that is physiologically correct defined as:
T
Smax
≤ 29°C for zones of normal occupancy;
T
Smax
≤ 35°C for peripheral zones of the rooms.
National standards may also limit these temperatures at lower values. Peripheral zones are strips generally located along the external walls with a maximum width of 1 m.
The floor heating system (electrically powered version) involves the laying under the floor coating of an electric cable powered by the mains voltage (230 V) or low voltage (for example 12 or 45 V), possibly already prepared in the form of rolls with constant distance between sections of cable. The powered cable releases heat to the overlying coating that heats the room by radiation. The regulation is based on measurement of the temperature of the air mass, but generally requires the monitoring and limiting of the surface temperature by using a NTC-type sensor which is in contact with the floor surface.
The surface temperature limitation may be realized for several purposes:
physiological compatibility (correct temperature at the height of the legs);
when the system is used as auxiliary stage for heating. In this case, the heat losses to the exterior of the building are handled by the main heating stage, while the auxiliary stage only works to keep the floor temperature at a comfortable level (for example in bathrooms of residential buildings, sports centers , spas and thermal baths, etc.);
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 39
Application manual
KNX room temperature controller EK-EP2-TP
protection against damages of the final coating due to an accidental overheating. Note that the warm water radiant panels are usually already equipped with a safety thermostat (with intervention on the hydraulic mixing group), while in the case of electrical power this device is not usable and it is common practice to realize a temperature limitation with a surface temperature sensor connected to the device.
7.8.3
Cooling
The
Cooling
folder includes the following parameters:
Comfort temp. setpoint [°C]
Standby temperature setpoint [°C]
Economy temp. setpoint [°C]
Building protection temp. setpoint [°C]
Cooling type
Control type
Hysteresis
Cyclic sending interval
Min. change of value to send [%]
PWM cycle time
Proportional band [0,1 K]
Integral time [min]
Anticondensation with probe
Auxiliary cooling
Disabled from bus
Offset from setpoint
Hysteresis
Cyclic sending interval
Ventilation for auxiliary cooling
Conditions: Temperature control
Settings
Thermostat function = cooling or both heating and cooling.
7.8.3.1
Parameter and communication object tables
Parameter name
Comfort temp. setpoint [°C]
Standby temperature setpoint [°C]
Economy temp. setpoint [°C]
Building protection temp. setpoint [°C]
Conditions Values
23
[range
10 … 50]
26
[range
10 … 50]
For a correct operation of the device the standby temperature setpoint has to be > comfort temperature setpoint.
28
[range
10 … 50]
For a correct operation of the device the standby temperature setpoint has to be > economy temperature setpoint.
36
[range
30 … 50]
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 40
Parameter name
Cooling type
Control type
Hysteresis
Cyclic sending interval
Min. change of value to send [%]
PWM cycle time
Proportional band [0,1 K]
Integral time [min]
Anticondensation with probe
Auxiliary cooling
Application manual
KNX room temperature controller EK-EP2-TP
Conditions Values
fan-coils floor radiant panels ceiling radiant panels
If in Settings the parameter Thermostat function = both heating and cooling and
Command communication object = unique, the parameter Cooling type is bound to the choice done for Heating.
Command communication object = separated
2 point hysteresis
PWM (pulse width modulation) continuous
If in Settings the parameter Thermostat function = both heating and cooling and
Command communication object = unique, the parameter Control type is bound to the choice done for Heating.
Control type = 2 point hysteresis
0,3 K
[other values in the range
0,2 K … 3 K]
Control type = 2 point hysteresis or continuous
no sending
[other values in the range
30 s … 120 min]
Control type = continuous
10
[range 0
… 100]
Control type = PWM (pulsa width modulation)
15 min
[range 5
… 240 min]
Control type = continuous or PWM
*
[range 0
… 255]
The value is in tenths of Kelvin (K) degree.
*) The field contains a preset value that depend on the selected cooling type (the value can be modified):
fan-coils: 40 (4 K)
floor radiant panels: 50 (5 K)
ceiling radiant panels: 50 (5 K)
The value of the parameter Proportional band represents the max difference between the setpoint temperature and the measured temperature that causes the max control output.
Control type = continuous or PWM
*
[range 0
… 255 min]
*) The field contains a preset value that depend on the selected cooling type (the value can be modified):
fan-coils: 90 min
floor radiant panels: 240 min
ceiling radiant panels: 180 min
Cooling type = floor radiant panels or ceiling radiant panels,
Inputs
Input 1 or Input 2 = [DI] anticondensation sensor or
External sensors (from bus)
Anticondensation = enabled
disabled
/ enabled
disabled
/ enabled
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 41
Parameter name
Disabled from bus
Offset from setpoint
Hysteresis
Cyclic sending interval
Ventilation for auxiliary cooling
Application manual
KNX room temperature controller EK-EP2-TP
Conditions
Auxiliary cooling = enabled
Values
Auxiliary cooling = enabled
no
/ yes
This parameter enables the activation and deactivation of the function through a telegram from a bus device with supervising function.
0,2 K /
0,3 K
/ 0,4 K / 0,5 / 0,6 K
0,8 K / 1 K / 1,5 K / 2 K / 2,5 K / 3 K
Auxiliary cooling = enabled
0,2 K /
0,3 K
/ 0,4 K / 0,5 / 0,6 K
0,8 K / 1 K / 1,5 K / 2 K / 2,5 K / 3 K
Auxiliary cooling = enabled
00:00:00 means that the cyclic sending is not enabled.
Cooling type = floor radiant panels or ceiling radiant panels hh:mm:ss (
disabled
00:00:00
/ enabled
)
This option allows combining a high-inertial system as the floor radiant panels to a lowinertial one as the fan-coils.
Object name
Comfort setpoint (cooling)
Standby setpoint (cooling)
Economy setpoint (cooling)
Building protection setpoint
(cooling)
Auxiliary cooling output command
Conditions Dim. Flags DPT
Comm.
Obj.
No.
154
Cooling out command
Auxiliary cooling enable
Anticondensation alarm
Control type = 2 point hysteresis or
PWM
Control type = continuous
Auxiliary cooling = enabled
Auxiliary cooling = enabled,
Disabled from bus = yes
At least one anticondensation protection enabled
2 Byte
2 Byte
2 Byte
2 Byte
1 Bit
1 Byte
1 Bit
1 Bit
1 Bit
CRWTU-
CRWTU-
CRWTU-
CRWTU-
CR-T--
CR-T--
CR-T--
C-W---
CR-T--
[9.001] temperature (°C)
[9.001] temperature (°C)
[9.001] temperature (°C)
[9.001] temperature (°C)
[1.001] switch
[5.001] percentage (0..100%)
[1.001] switch
[1.003] enable
[1.005] alarm
156
158
160
162
164
166
188
About the anticondensation protection function
The objective of this function is to prevent the condensation on the thermal exchange surfaces of the installation or building when cooling is working. This function is mainly used in systems with thermal exchange consisting in surface terminals such as for the floor and ceiling cooling radiant systems. In this case the hydraulic circuits contain refrigerated water; usually the latent loads (due to the increase of air
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 42
Application manual
KNX room temperature controller EK-EP2-TP
humidity in the room) are handled by air-conditioning units and the temperature and humidity conditions are far from those that could cause condensation. If this is not done in a satisfactory manner, or in case of stop of the air-conditioning units, it is necessary to provide additional safety measures to prevent or restrict the accidental formation of condensation on cold surfaces.
If an anticondensation sensor is used, it is necessary use a device provided with a potential-free signalling contact. The following options are available:
the connection of the signalling contact to an input of the room temperature controller configured as digital (Inputs
Input 1 or Input 2 = [DI] anticondensation sensor). The signal coming from the sensor is received and processed directly by the room temperature controller (case 1a of the table);
the connection of the signalling contact to an input channel of another KNX device, e.g. a pushbutton interface or a binary input (External sensors (from bus)
Anticondensation sensor = enabled). In this case the signal of the sensor is transmitted to the room temperature controller through the status of a communication object (case 1b of the table).
7.8.4
Main and auxiliary ventilation
The
Ventilation
folder includes the following parameters:
Control type
Threshold first speed [0,1 K]
Threshold second speed [0,1 K]
Threshold third speed [0,1 K]
Speed control hysteresis [K]
Proportional band [0,1 K]
Minimo cambiamento valore da inviare [%]
Manual operation
Hot start
Min. temp.to start ventilation [°C]
Antistratification function
Antistratification temp. differential
Hysteresis
Disable ventilation from bus
Signal from bus
Fan start delay
Fan stop delay
The conditions for the appearance of the
Ventilation
folder are:
Heating
Type of heating = fan-coils or Type of cooling = fan-coils or a combination of the two conditions:
Heating
Type of heating = floor radiant panels or ceiling radiant panels and
Heating
Ventilation
Auxiliary heating = enabled
Cooling
Type of cooling = floor radiant panels or ceiling radiant panels and
Cooling
Ventilation for auxiliary = enabled
This way two types of installations can be controlled: i) fan-coil terminals or ii) radiant panels as main stage and fan-coil terminals as auxiliary stage.
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 43
7.8.4.1
Parameter and communication object tables
Parameter name
Control type
Threshold first speed [0,1 K]
Threshold second speed [0,1 K]
Threshold third speed [0,1 K]
Speed control hysteresis [K]
Proportional band [0,1 K]
Minimo cambiamento valore da inviare [%]
Manual operation
Hot start
Application manual
KNX room temperature controller EK-EP2-TP
Conditions Values
1 speed
2 speeds
3 speeds continuous regulation
10
[range 0
… 255]
The value is represented in tenths of Kelvin degrees. If the parameter Thermostat function = both heating and cooling, the threshold value is valid for both seasonal modes.
Control type = 2 speeds
20
[range
0 … 255]
The value is represented in tenths of Kelvin degrees. If the parameter Thermostat function = both heating and cooling, the threshold value is valid for both seasonal modes. For a correct operation of the ventilation, Threshold second speed > Threshold first speed.
Control type = 3 speeds
30
[range
0 … 255]
The value is represented in tenths of Kelvin degrees. If the parameter Thermostat function = both heating and cooling, the threshold value is valid for both seasonal modes. For a correct operation of the ventilation, Threshold third speed > Threshold second speed.
Control type = 1, 2 or 3 speeds
0,3 K
[other values in the range 0,2 K
…3 K]
Control type = continuous regulation
30
[range
0 … 255]
The value is represented in tenths of Kelvin degrees. If the parameter Thermostat function = both heating and cooling, the threshold value is valid for both seasonal modes.
Control type = continuous regulation
10
[range
2 … 40]
not depending on the temperature
depending on the temperature
If the parameter = not depending on the temperature, the fan speed set by the user is not changed even when the temperature setpoint is reached; if the parameter = depending on the temperature, the fan stops when the temperature setpoint is reached.
Thermostat function = both heating and cooling,
Inputs
Input X
[AI] coil battery temperature sensor or
External sensors (from bus)
coil temperature = enabled
no
/ yes
For carrying out the function must be enabled a sensor for measuring the temperature of the heat exchanger of the fan coil. To this purpose either an input (configured as analog) or an external sensor (from bus) can be used.
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 44
Parameter name
Min. temp.to start ventilation [°C]
Object name
Application manual
KNX room temperature controller EK-EP2-TP
Antistratification function
Antistratification temp. differential
Hysteresis
Disable ventilation from bus
Signal from bus
Fan start delay
Fan stop delay
Fan continuous speed
Fan speed 1
Conditions
Hot start = yes
Values
35
[range
28 …40]
If enabled, the function is active only in heating mode.
Inputs
Input X = [AI] antistratification temperature sensor or
External sensors (from bus)
Antistratification temperature = enabled
disabled
/ enabled
For carrying out the function at least a sensor for measuring a second temperature value must be enabled at a different height than that of the room temperature controller. To this purpose either an input (configured as analog) or an external sensor (from bus) can be used.
Antistratification function = enabled
2 [K/m]
[other values in the range 0,25 …
4,00 K/m]
The DIN 1946 recommends a max temperature gradient of 2 K/m for rooms with standard height (between 2,70 and 3 m).
Antistratification function = enabled
0,5 K
[other values in the range
0,2 … 3
K]
no
/ yes
Disable ventilation from bus = yes
not inverted
inverted
0 s
[other values in the range 10 s
…
12 min]
It appears also if the hot-start function is active (through measuring of the conveying fluid temperature at the battery for the thermal exchange). The function is active in both seasonal modes (heating and cooling).
0 s
[other values in the range
10 s …
12 min]
The function allows prolonging the operation of the ventilator, dissipating in the room the residual heat or cool present in battery for the thermal exchange. The function is active in both seasonal modes
(heating and cooling).
Conditions
Control type = continuous regulation
Control type = 1, 2 o 3 speeds
Dim.
1 Byte CR-T--
1 Bit
Flags
CR-T--
DPT
[5.001] percentage (0..100%)
Comm.
Obj.
No.
167
[1.001] switch 168
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 45
Application manual
KNX room temperature controller EK-EP2-TP
Object name Conditions Dim. Flags DPT
Comm.
Obj.
No.
169 Fan speed 2
Fan speed 3
Fan control disable
Control type = 2 or
3 speeds
Control type = 3 speeds
Disable ventilation from bus = yes
1 Bit
1 Bit
1 Bit
CR-T--
CR-T--
C-W---
[1.001] switch
[1.001] switch
[1.002] boolean
170
172
About the delayed fan start (“hot-start”)
This function is used in case the fan forces in the room air passing through a heat exchange coil (as in the case of the terminals to the fan-coil). In the heating mode of operation, to avoid possible discomfort caused by the dispatch of cold air in the room, the room temperature controller does not start the fan until the fluid has not reached a sufficiently high temperature. This situation normally occurs at the first start or after long periods of inactivity. The function can be carried out by:
1. a temperature control (through a temperature sensor on the coil exchange battery);
2. a delayed start (function approximated);
In the first case the temperature of the heat conveying fluid is acquired at the exchange battery. The function then has an effective temperature control, but for the execution is necessary that:
the heat exchange coil is equipped with a sensor of minimum water temperature that acquires the temperature of the heat conveying fluid;
the sensor is connected to an input of the room temperature controller (configured as analog) or to another KNX device with an analog input .
In the second case just sets a time delay starting from the flow request; there is no temperature control. The effectiveness of the function depends on a field measurement of the time actually required to have sufficiently warm air from the terminal.
About the antistratification function
This function is used in the case of heating systems with thermal exchange of convective type for rooms with height and volume much higher than usual (atriums, fitness facility, commercial buildings, etc.). Because of the natural convection - with warm air rising to the highest altitudes of the room - the phenomenon of air stratification occurs, with energy waste and discomfort for the occupants at the same time. The function opposes to the air stratification, forcing the warm air downwards.
The antistratification function requires:
rooms of great height;
availability of ventilation devices able to force the air movement downwards (opposed to the natural convective movement of warm air);
measuring of the temperature at two heights through the installation of a second temperature sensor at an adequate height in order to measure the actual air stratification (the main room temperature controller is supposed to be installed at 1.5 m).
For rooms with ordinary height (2,70÷3,00 m) the DIN 1946 standard recommends not to exceed 2 K/m in order to have an adequate comfort; this gradient may be bigger in higher rooms.
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 46
Application manual
KNX room temperature controller EK-EP2-TP
About the 2-stage configuration with fan-coils as auxiliary stage
The fan-coil units may be used both as a main stage and secondary stage. As main stage they can be combined only to radiators as auxiliary stage. If, however, the main stage is done with (floor or ceiling) radiant panels, the fan-coils can be used as auxiliary stage. In the latter case they work in automatic mode with a configurable offset with respect to the temperature setpoint for the main stage, and then carry out their compensation function while the main stage is brought in temperature with bigger inertia.
The
Ventilation
folder, that is unique, configures a main or a auxiliary stage depending on the settings choosed in the
Heating
and
Cooling
folders. Similarly, the display interface will act on manual / automatic and manual forcing of the only fan-coil.
A particular case occurs when a fan-coil unit works in a season as auxiliary stage and in the other one as main stage. It is for example the case of:
a radiant panels system that works only for heating and has a fan-coil as auxiliary stage; the same fan-coil works as main stage for cooling;
a radiator system that has a fan-coil as auxiliary stage for heating; the same fan coil unit functions as main stage for cooling.
In these cases with the configuration adopted, the following steps are necessary:
1.
Settings
Thermostat function = both heating and cooling. This configuration enables both folders
(heating and cooling)
2.
Heating
Heating type = floor radiant panels or ceiling radiant panels
3.
Heating
Command communication object = separated (if unique is choosen, the parameter Cooling
Cooling type does not appear)
4.
Heating
Auxiliary heating = enabled
5.
Auxiliary heating
Communication object = separated
6.
Heating
Ventilation for auxiliary heating = enabled
7.
Cooling
Cooling type = fancoils
Important!
If the fan-coil system has a 2-pipe hydraulic configuration, the objects 163 Auxiliary heating output command (1 bit) and 162 Cooling out command (1 byte) have to be set in logical OR in the actuator for controlling the fan-coil which in this case is unique.
An alternative solution that avoids the setting of a logic OR can be realized by configuring a main stage for heating and cooling with radiant panels through separate valves and an auxiliary stage for heating and cooling fan coil through combined valves. The offset of the auxialiary stage for cooling is set to the value 0
(zero); this corresponds to a configuration for main stage. The object 162 Cooling out command (1 byte) is not connected so that the radiant panel system works only for heating.
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 47
7.8.5
Scenes
Application manual
KNX room temperature controller EK-EP2-TP
The folder allows the scenes configuration (up to 8), assigning to each one an identification number and the operating mode to be activated when recalled (e.g. with an ekinex pushbutton or another KNX device with this function). If
Learning mode = enabled
, receiving a telegram of scene storage determines the association of the scene to the operating mode currently set on the device.
Important!
Be careful setting the
Download overwrite
parameter. The download of the application program, particularly after the first commissioning of the system, may cause the loss of the already stored scenes.
The
Scenes
folder includes the following parameters:
Download overwrite
Scene X
Scene number
HVAC mode
Activation delay
Learning mode
Condition:
Temperature control
Settings
Scenes = enabled.
7.8.5.1
Parameter and communication object tables
Parameter name
Download overwrite
Scene X
Scene number
HVAC mode
Activation delay
Learning mode
Conditions Values
disabled
/ enabled
If Overwrite download = disabled: at the download of the application on the device, the operating modes previously stored are not overwritten.
If Overwrite download = enabled: at the download of the application on the device, the operating modes previously stored are reprogrammed with the values selected from the HVAC mode parameter.
disabled
/ enabled
This parameter enables the scene X
(X = 1, 2, … 8).
Scene X = enabled
1
[range
1 … 64]
Scene X = enabled auto /
comfort
/ standby / economy / building protection
This parameter defines the operating mode of the scene X.
Scene X = enabled hh:mm:ss (
00:00:00
)
Receiving a telegram that recalls a scene, once elapsed the time interval set in the Activation delay parameter, the programmed operating mode is activated.
Scene X = enabled
disabled
/ enabled
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 48
Object name
HVAC scene number
Application manual
KNX room temperature controller EK-EP2-TP
Conditions Dim. Flags DPT
Comm. Obj.
No.
1 Byte C-W---
[17.001] scene number
[18.001] scene control
173
It stores or recalls a scenario. The six least significant bits (0 to 5) in the byte of the code represent the number of the scene, while the most significant bit (7) is the operation code (1 = stores, 0 = recalls).
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 49
Application manual
KNX room temperature controller EK-EP2-TP
7.9
Energy saving
In order to realise energy-saving functions, window contacts (to detect the opening of windows or doors), presence and movement sensors and card holders can be used.
The
Energy saving
folder includes the following secondary folders:
Window contacts
Presence sensors
Card holder
7.9.1
Window contacts
The
Window contacts
secondary folder appears if at least a sensor dedicated to this function is enabled i.e. if at least one of the two conditions is verified:
1)
Inputs
Input 1 and/or Input 2 = [DI] windows contact sensor
2)
External sensors (from bus)
Windows contact sensor 1 or 2 (from bus) = enabled
For the function can be acquired up to four signals which are combined as a logic OR.
The
Window contacts
folder includes the following parameters:
Window contacts function
Wait time to building protection mode
7.9.1.1
Parameter and communication object tables
Parameter name
Window contacts function
Wait time to building protection mode
Conditions Values
disabled
/ enabled
This parameter enables the window contact function.
Window contacts function = enabled
00:01:00 hh:mm:ss
[range
00:00:00 … 18:12:15]
Time interval before the automatic switching of the device to the Building protection operating mode.
Object name Conditions Dim. Flags DPT
Comm.
Obj. No.
Window contact sensor (from input 1)
Window contacts function = enabled,
Input 1 = [DI] windows contact sensor
1 Bit CR-T-
[1.019] window/door
126
Window contact sensor (from input 2)
Window contacts function = enabled,
Input 2 = [DI] windows contact sensor
1 Bit CR-T-
[1.019] window/door
127
Windows contact sensor 1
(from bus)
Window contacts function = enabled,
Window contact 1 = enabled
1 Bit C-W--
[1.019] window/door
143
Windows contact sensor 2
(from bus)
Window contacts function = enabled,
Window contact 2 = enabled
1 Bit C-W--
[1.019] window/door
144
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 50
7.9.2
Presence sensors
Application manual
KNX room temperature controller EK-EP2-TP
The
Presence sensors
folder includes the following parameters:
Presence sensor function
Presence sensors use
Thermostat modes
Absence time to switch HVAC mode
For this function only use external sensors (from bus) can be used, such as the ekinex EK-SM2-TP movement sensor or the ekinex EK-DX2-TP (X = B, C, D, E) presence sensor. The following condition has to be true:
External sensors (from bus)
Presence sensor 1 (from bus) or Presence sensor 2 (from bus) = enabled
7.9.2.1
Parameter and communication object tables
Parameter name
Presence sensor function
Presence sensors use
Thermostat modes
Absence time to switch HVAC mode
Conditions
Parameter that enables the presence sensor function.
Values
disabled
/ enabled
Presence sensor function = enabled
comfort extension
comfort limitation comfort extension and comfort limitation
Presence sensor function = enabled,
Presence sensors use = comfort extension and comfort limitation or = comfort limitation
comfort-standby
comfort-economy
Presence sensor function = enabled
00:01:00 hh:mm:ss
[range
00:00:00 … 18:12:15]
Time interval before the automatic switching of the operating mode set in the
Thermostat modes parameter.
Object name Conditions Dim. Flags DPT
Comm.
Obj. No.
Presence sensor 1 (from bus)
Presence sensor function= enabled
1 Bit C-W---
[1.018] occupancy
132
Presence sensor 2 (from bus)
Presence sensor function = enabled
1 Bit C-W---
[1.018] occupancy
133
7.9.3
Card holder
The
Card holder
secondary folder appears only if the corresponding sensor is enabled i.e. if one of the two mutually esclusive conditions is true:
1)
Inputs
Input1 or Input 2 = [DI] card holder contact sensor or
2)
External sensors (from bus)
Card holder contact = enabled
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 51
The
Card holder
folder includes the following parameters:
Card holder function
On card insertion switch HVAC mode to
Activation delay on card insertion
On card removal switch HVAC mode to
Activation delay on card removal
Application manual
KNX room temperature controller EK-EP2-TP
7.9.3.1
Parameter and communication object tables
Parameter name
Card holder function
On card insertion switch HVAC mode to
Activation delay on card insertion
On card removal switch HVAC mode to
Activation delay on card removal
Conditions Values
disabled
/ enabled
Parameter that enables the card holder function.
Card holder function = enabled none
comfort
standby economy
This parameter defines to which operating mode the device should automatically switch inserting the card in the holder.
Card holder function = enabled
00:00:00 hh:mm:ss
[range
00:00:00 … 18:12:15]
Time interval before the automatic switching of the operating mode, inserting the card in the holder.
Card holder function = enabled none
standby
economy building protection
This parameter defines to which operating mode the device should automatically switch removing the card from the holder.
Card holder function = enabled
00:00:00 hh:mm:ss
[range
00:00:00 … 18:12:15]
Time interval before the automatic switching of the operating mode, removing the card from the holder.
Object name
Card holder contact sensor
(from input 1)
Card holder contact sensor
(from input 2)
Conditions
Card holder function = enabled
Card holder function = enabled
Dim.
1 Bit
1 Bit
Flags
CR-T--
CR-T--
DPT
[1.001] switch
[1.001] switch
Comm.
Obj. No.
130
131
About the card holder function
The information of card insertion (removal) in (from) a card holder allows you to directly control the temperature by means of the room thermostat, while sending the object value on the bus allows you to control other room functions with KNX (lighting, electrical loads, feedback status for the hotel reception, etc.) depending on the configuration done with ETS. The value of the setpoint temperature and the switching have to be defined with the hotel responsible in accordance with the target of energy saving and level of service to be offered to the guests.
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 52
Application manual
KNX room temperature controller EK-EP2-TP
Conventional (not KNX) card holder
With a conventional card holder the status (card present or absent) of a signal contact is detected through an input of the device configured as
[DI] card holder contact sensor
. This way you can detect only the insertion and extraction of the card, but it cannot be detected e.g. the access of users with different profiles (guests, service staff, maintenance workforce).
KNX card holder
With a KNX card holder you can differentiate the switching to be carried out; this is not resolved by the parameters of the room temperature controller, but through the definition of scenes that are received by the device. Depending on the available device, advanced functions are possible (e.g. different user profiles).
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 53
8
List of communication objects
Nr. Name
0 Technical alarm
1 Brightness value
2 Leds intensity percentage
3 Temperature value
20 Light threshold 1 - Switch
37 Light threshold 2 - Switch
38 Rocker 1 - Led first color A
39 Rocker 1 - Led second color A
40 Rocker 1 - Led first color B
41 Rocker 1 - Led second color B
76 Rocker 2 - Led first color A
77 Rocker 2 - Led second color A
78 Rocker 2 - Led first color B
79 Rocker 2 - Led second color B
116 Temperature threshold 1 - Switch
117 Temperature threshold 2 - Switch
120 Coil battery temperature sensor (from input 1)
120 Room temperature sensor (from input 1)
120 Antistratification temperature sensor (from input 1)
120 Floor surface temperature sensor (from input 1)
120 Outdoor temperature sensor (from input 1)
120 Temperature value sensor (from input 1)
121 Temperature threshold 1 sensor 1 - Switch
122 Temperature threshold 2 sensor 1 - Switch
123 Coil battery temperature sensor (from input 2)
123 Room temperature sensor (from input 2)
123 Antistratification temperature sensor (from input 2)
123 Floor surface temperature sensor (from input 2)
123 Outdoor temperature sensor (from input 2)
123 Temperature value sensor (from input 2)
124 Temperature threshold 1 sensor 2 - Switch
125 Temperature threshold 2 sensor 2 - Switch
126 Window contact sensor (from input 1)
127 Window contact sensor (from input 2)
128 Anticondensation sensor (from input 1)
129 Anticondensation sensor (from input 2)
130 Card holder contact sensor (from input 1)
131 Card holder contact sensor (from input 2)
132 Presence sensor 1 (from bus)
133 Presence sensor 2 (from bus)
134 Room temperature (from bus)
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application manual
KNX room temperature controller EK-EP2-TP
1 Bit
1 Bit
2 Bytes
2 Bytes
2 Bytes
2 Bytes
2 Bytes
2 Bytes
1 Bit
1 Bit
2 Bytes
2 Bytes
2 Bytes
2 Bytes
2 Bytes
2 Bytes
1 Bit
1 Bit
1 Bit
1 Bit
1 Bit
1 Bit
1 Bit
1 Bit
Size
1 Bit
2 Bytes
1 Byte
2 Bytes
1 Bit
1 Bit
1 Bit
1 Bit
1 Bit
1 Bit
1 Bit
1 Bit
1 Bit
1 Bit
1 Bit
1 Bit
2 Bytes
Flags Datapoint Type
-
WC--- [1.5] DPT_Alarm
R-CT-- [9.4] DPT_Value_Lux
-
WC--- [5.1] DPT_Scaling
R-CT-- [9.1] DPT_Value_Temp
R-CT-- [1.1] DPT_Switch
R-CT-- [1.1] DPT_Switch
RWCTU- [1.1] DPT_Switch
RWCTU- [1.1] DPT_Switch
RWCTU- [1.1] DPT_Switch
RWCTU- [1.1] DPT_Switch
RWCTU- [1.1] DPT_Switch
RWCTU- [1.1] DPT_Switch
RWCTU- [1.1] DPT_Switch
RWCTU- [1.1] DPT_Switch
R-CT-- [1.1] DPT_Switch
R-CT-- [1.1] DPT_Switch
R-CT-- [9.1] DPT_Value_Temp
R-CT-- [9.1] DPT_Value_Temp
R-CT-- [9.1] DPT_Value_Temp
R-CT-- [9.1] DPT_Value_Temp
R-CT-- [9.1] DPT_Value_Temp
R-CT-- [9.1] DPT_Value_Temp
R-CT-- [1.1] DPT_Switch
R-CT-- [1.1] DPT_Switch
R-CT-- [9.1] DPT_Value_Temp
R-CT-- [9.1] DPT_Value_Temp
R-CT-- [9.1] DPT_Value_Temp
R-CT-- [9.1] DPT_Value_Temp
R-CT-- [9.1] DPT_Value_Temp
R-CT-- [9.1] DPT_Value_Temp
R-CT-- [1.1] DPT_Switch
R-CT-- [1.1] DPT_Switch
R-CT-- [1.19] DPT_Window_Door
R-CT-- [1.19] DPT_Window_Door
R-CT-- [1.5] DPT_Alarm
R-CT-- [1.5] DPT_Alarm
R-CT-- [1.18] DPT_Occupancy
R-CT-- [1.18] DPT_Occupancy
-
WC--- [1.18] DPT_Occupancy
-
WC--- [1.18] DPT_Occupancy
-
WC--- [9.1] DPT_Value_Temp
Application Manual
Page 54
Nr. Name
137 Antistratification temperature (from bus)
138 Outdoor temperature (from bus)
140 Coil temperature (from bus)
143 Windows contact sensor 1 (from bus)
144 Windows contact sensor 2 (from bus)
145 Contact of card holder (from bus)
146 Anticondensation (from bus)
147 Weighted temperature
148 Heating/cooling status out
149 Heating/cooling status in
150 HVAC mode in
151 HVAC forced mode in
152 Actual setpoint
153 Comfort setpoint (heating)
154 Comfort setpoint (cooling)
155 Standby setpoint (heating)
156 Standby setpoint (cooling)
157 Economy setpoint (heating)
158 Economy setpoint (cooling)
159 Building protection setpoint (heating)
160 Building protection setpoint (cooling)
161 Heating out command
161 Heating out command
161 Heating and cooling out command
161 Heating and cooling out command
162 Cooling out command
162 Cooling out command
163 Auxiliary heating output command
163 Auxiliary heating and cooling output command
164 Auxiliary cooling output command
165 Auxiliary heating enable
166 Auxiliary cooling enable
167 Fan continuous speed
168 Fan speed 1
169 Fan speed 2
170 Fan speed 3
172 Fan control disable
173 HVAC scene number
173 HVAC scene number
179 HVAC mode out
186 Temperature setpoint change lock
187 Manual mode lock
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application manual
KNX room temperature controller EK-EP2-TP
1 Bit
1 Bit
1 Byte
1 Byte
1 Bit
1 Bit
1 Bit
1 Bit
2 Bytes
2 Bytes
2 Bytes
2 Bytes
2 Bytes
2 Bytes
1 Byte
2 Bytes
1 Bit
1 Bit
1 Byte
1 Byte
2 Bytes
2 Bytes
2 Bytes
Size
2 Bytes
2 Bytes
2 Bytes
1 Bit
1 Bit
1 Bit
1 Bit
1 Bit
1 Bit
1 Byte
1 Bit
1 Bit
1 Bit
1 Bit
1 Byte
1 Byte
1 Byte
1 Bit
1 Bit
Flags Datapoint Type
-
WC--- [9.1] DPT_Value_Temp
-
WC--- [9.1] DPT_Value_Temp
-
WC--- [9.1] DPT_Value_Temp
-
WC--- [1.19] DPT_Window_Door
-
WC--- [1.19] DPT_Window_Door
-
WC--- [1.18] DPT_Occupancy
-
WC--- [1.1] DPT_Switch
R-CT-- [9.1] DPT_Value_Temp
R-CT-- [1.100] DPT_Heat_Cool
-
WC--- [1.100] DPT_Heat_Cool
-
WC--- [20.102] DPT_HVACMode
-
WC--- [20.102] DPT_HVACMode
R-CT-- [9.1] DPT_Value_Temp
RWCTU- [9.1] DPT_Value_Temp
RWCTU- [9.1] DPT_Value_Temp
RWCTU- [9.1] DPT_Value_Temp
RWCTU- [9.1] DPT_Value_Temp
RWCTU- [9.1] DPT_Value_Temp
RWCTU- [9.1] DPT_Value_Temp
RWCTU- [9.1] DPT_Value_Temp
RWCTU- [9.1] DPT_Value_Temp
R-CT-- [5.1] DPT_Scaling
R-CT-- [1.1] DPT_Switch
R-CT-- [1.1] DPT_Switch
R-CT-- [5.1] DPT_Scaling
R-CT-- [5.1] DPT_Scaling
R-CT-- [1.1] DPT_Switch
R-CT-- [1.1] DPT_Switch
R-CT-- [1.1] DPT_Switch
R-CT-- [1.1] DPT_Switch
-
WC--- [1.3] DPT_Enable
-
WC--- [1.3] DPT_Enable
R-CT-- [5.1] DPT_Scaling
R-CT-- [1.1] DPT_Switch
R-CT-- [1.1] DPT_Switch
R-CT-- [1.1] DPT_Switch
-
WC--- [1.2] DPT_Bool
-
WC--- [17.1] DPT_SceneNumber
-
WC--- [18.1] DPT_SceneControl
R-CT-- [20.102] DPT_HVACMode
-
WC--- [1.3] DPT_Enable
-
WC--- [1.3] DPT_Enable
Application Manual
Page 55
Nr. Name
188 Anticondensation alarm
189 Rockers lock
190 Ventilation manual operation
191 Thermal generator lock
Application manual
KNX room temperature controller EK-EP2-TP
Size
1 Bit
1 Bit
1 Bit
1 Bit
Flags Datapoint Type
R-CT-- [1.5] DPT_Alarm
-
WC--- [1.2] DPT_Bool
R-CT-- [1.11] DPT_State
-
WC--- [1.5] DPT_Alarm
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 56
9
Diagnostics
E25
E26
E27
E28
E29
E33
E34
E16
E17
E18
E19
E22
E23
E24
E02
E06
E07
E08
E09
E10
E11
E14
E15
Alarm code
A01
A02
A03
Error code
E00
E01
E43
E44
E45
E46
F01
F02
F03
F04
E35
E36
E37
E38
E39
E40
E41
E42
Application manual
KNX room temperature controller EK-EP2-TP
Cause
Surface temperature limit is exceeded
Formation of condensation
Thermal generator lock
Cause
Integrated temperature sensor fault
Integrated relative humidity sensor fault
Integrated brightness sensor fault
Analogic input 1: NTC sensor fault
Analogic input 1: room temperature sensor fault
Analogic input 1: fan-coil temperature sensor fault
Analogic input 1: surface temperature sensor fault
Analogic input 1: external temperature sensor fault
Analogic input 1: antistratification sensor fault
Analogic input 2: NTC sensor fault
Analogic input 2: room temperature sensor fault
Analogic input 2: fan-coil temperature sensor fault
Analogic input 2: surface temperature sensor fault
Analogic input 2: external temperature sensor fault
Analogic input 2: antistratification sensor fault
CO: quality air sensor fault
CO: external temperature sensor fault
CO: room temperature sensor fault
CO: fan-coil temperature sensor fault
CO: surface temperature sensor fault
CO: flow temperature sensor fault
CO: relative humidity sensor fault
CO: antistratification temperature sensor fault
CO: quality air sensor timeout
CO: external temperature sensor timeout
CO: room temperature sensor timeout
CO: fan-coil temperature sensor timeout
CO: surface temperature sensor timeout
CO: flow temperature sensor timeout
CO: relative humidity sensor timeout
CO: antistratification temperature sensor timeout
CO: anticondensation sensor timeout
CO: window contact 1 timeout
CO: window contact 2 timeout
CO: presence sensor 1 timeout
CO: presence sensor 2 timeout
CO: card holder contact timeout
CO: Alarm 1 from bus
CO: Alarm 2 from bus
CO: Alarm 3 from bus
CO: Alarm 4 from bus
Table of alarm and error displayable codes.
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 57
10
Warnings
Application manual
KNX room temperature controller EK-EP2-TP
• Installation, electrical connection, configuration and commissioning of the device can only be carried outby qualified personnel in compliance with the applicable technical standards and laws of the respective countries
• Opening the housing of the device causes the immediate end of the warranty period
• In case of tampering, the compliance with the essential requirements of the applicable directives, for which the device has been certified, is no longer guaranteed
• ekinex
®
KNX defective devices must be returned to the manufacturer at the following address: SBSS.p.A.
Via Circonvallazione s/n, I-28010 Miasino (NO) Italy
11
Other information
• The instruction sheet must be delivered to the end customer with the project documentation
• For further information on the product, please contactthe ekinex
®
technical support at the e-mail address: [email protected] or visit the website www.ekinex.com
• Each ekinex
®
device has a unique serial number onthe label. The serial number can be used by installersor system integrators for documentation purposes and has to be added in each communication addressed to the SBS technical support in case of malfunctioning of the device
• ekinex
• KNX
®
®
is a registered trademark of SBS S.p.A.
and ETS
®
are registered trademarks of KNX Association cvba, Brussels
© SBS S.p.A. 2015. The company reserves the right to make changes to this documentation without notice.
Release 1.0 - Updating: 30/03/2015
© SBS S.p.A. - All rights reserved
Application Manual
Page 58
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 4 Foreword
- 4 General information
- 4 Function
- 4 Main funcional features
- 5 Technical data
- 5 Design
- 6 Delivery
- 6 Accessories
- 6 Marks and certification
- 7 Installation
- 7 Connection
- 7 Connection of the bus line
- 7 Connection of the inputs
- 9 Configuration and commissioning
- 9 Configuration
- 9 Tree structure of the application program
- 10 Languages of the application program
- 10 Commissioning
- 11 Displaying physical address and firmware release
- 12 User interface
- 12 LC-display
- 12 Information displaying
- 13 Segment test
- 14 Backlight
- 14 Rockers
- 15 Sensors
- 15 Temperature sensor
- 15 Brightness sensor
- 16 Input variables
- 17 Application program for ETS
- 17 About EK-EP2-TP
- 18 General
- 18 Parameter table
- 19 Internal sensors
- 19 Parameter table
- 19 Temperature sensor
- 20 Parameter and communication object tables
- 21 Brightness sensor
- 21 Parameter and communication object tables
- 22 Inputs
- 22 Input X
- 23 Parameter and communication object tables
- 25 External sensors (from bus)
- 26 Parameter and communication object tables
- 28 Weighted temperature value
- 28 Parameter and communication object tables
- 29 LC-display
- 29 Parameters
- 30 Parameter and communication object tables
- 32 Temperature control
- 33 Settings
- 33 Parameter and communication object tables
- 36 Heating
- 37 Parameter and communication object tables
- 40 Cooling
- 40 Parameter and communication object tables
- 43 Main and auxiliary ventilation
- 44 Parameter and communication object tables
- 48 Scenes
- 48 Parameter and communication object tables
- 50 Energy saving
- 50 Window contacts
- 50 Parameter and communication object tables
- 51 Presence sensors
- 51 Parameter and communication object tables
- 51 Card holder
- 52 Parameter and communication object tables
- 54 List of communication objects
- 57 Diagnostics
- 58 Warnings
- 58 Other information