Application manual KNX room temperature controller EK

Add to my manuals
58 Pages

advertisement

Application manual KNX room temperature controller EK | Manualzz

Application manual

KNX room temperature controller

EK-EP2-TP

Application manual

KNX room temperature controller EK-EP2-TP

Index

Foreword ............................................................................................................................................................. 4

1 General information ....................................................................................................................................... 4

1.1

Function ................................................................................................................................................. 4

1.2

Main funcional features .......................................................................................................................... 4

1.3

Technical data ........................................................................................................................................ 5

1.4

Design .................................................................................................................................................... 5

1.5

Delivery .................................................................................................................................................. 6

1.6

Accessories ............................................................................................................................................ 6

1.7

Marks and certification ........................................................................................................................... 6

2 Installation ...................................................................................................................................................... 7

2.1

Connection ............................................................................................................................................. 7

2.1.1

Connection of the bus line .............................................................................................................. 7

2.1.2

Connection of the inputs ................................................................................................................ 7

3 Configuration and commissioning ................................................................................................................. 9

3.1

Configuration .......................................................................................................................................... 9

3.1.1

Tree structure of the application program ...................................................................................... 9

3.1.2

Languages of the application program ......................................................................................... 10

3.2

Commissioning .................................................................................................................................... 10

3.2.1

Displaying physical address and firmware release ...................................................................... 11

4 User interface .............................................................................................................................................. 12

4.1

LC-display ............................................................................................................................................ 12

4.1.1

Information displaying .................................................................................................................. 12

4.1.2

Segment test ................................................................................................................................ 13

4.1.3

Backlight ....................................................................................................................................... 14

4.2

Rockers ................................................................................................................................................ 14

5 Sensors ........................................................................................................................................................ 15

5.1

Temperature sensor ............................................................................................................................. 15

5.2

Brightness sensor ................................................................................................................................ 15

6 Input variables ............................................................................................................................................. 16

7 Application program for ETS ....................................................................................................................... 17

7.1

About EK-EP2-TP ................................................................................................................................ 17

7.1.1

General ......................................................................................................................................... 18

7.1.2

Parameter table ............................................................................................................................ 18

7.2

Internal sensors ................................................................................................................................... 19

7.2.1

Parameter table ............................................................................................................................ 19

7.2.2

Temperature sensor ..................................................................................................................... 19

7.2.2.1

Parameter and communication object tables ............................................................ 20

7.2.3

Brightness sensor ........................................................................................................................ 21

7.2.3.1

Parameter and communication object tables ............................................................ 21

7.3

Inputs ................................................................................................................................................... 22

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 2

Application manual

KNX room temperature controller EK-EP2-TP

7.3.1

Input X .......................................................................................................................................... 22

7.3.2

Parameter and communication object tables ............................................................................... 23

7.4

External sensors (from bus) ................................................................................................................. 25

7.4.1

Parameter and communication object tables ............................................................................... 26

7.5

Weighted temperature value ................................................................................................................ 28

7.5.1

Parameter and communication object tables ............................................................................... 28

7.6

LC-display ............................................................................................................................................ 29

7.6.1

Parameters ................................................................................................................................... 29

7.7

Leds ..................................................................................................................................................... 30

7.7.1

Parameter and communication object tables ............................................................................... 30

7.8

Temperature control ............................................................................................................................. 32

7.8.1

Settings ........................................................................................................................................ 33

7.8.1.1

Parameter and communication object tables ............................................................ 33

7.8.2

Heating ......................................................................................................................................... 36

7.8.2.1

Parameter and communication object tables ............................................................ 37

7.8.3

Cooling ......................................................................................................................................... 40

7.8.3.1

Parameter and communication object tables ............................................................ 40

7.8.4

Main and auxiliary ventilation ....................................................................................................... 43

7.8.4.1

Parameter and communication object tables ............................................................ 44

7.8.5

Scenes ......................................................................................................................................... 48

7.8.5.1

Parameter and communication object tables ............................................................ 48

7.9

Energy saving ...................................................................................................................................... 50

7.9.1

Window contacts .......................................................................................................................... 50

7.9.1.1

Parameter and communication object tables ............................................................ 50

7.9.2

Presence sensors ........................................................................................................................ 51

7.9.2.1

Parameter and communication object tables ............................................................ 51

7.9.3

Card holder ................................................................................................................................... 51

7.9.3.1

Parameter and communication object tables ............................................................ 52

8 List of communication objects ..................................................................................................................... 54

9 Diagnostics .................................................................................................................................................. 57

10 Warnings ...................................................................................................................................................... 58

11 Other information ......................................................................................................................................... 58

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 3

Foreword

Application manual

KNX room temperature controller EK-EP2-TP

The present document describes the ekinex

®

KNX room temperature controller with LC-display (EK-EP2-TP version).

1

General information

The device described in the present document works as an electronic digital temperature controller for a room or a zone (consisting e.g. in a group of rooms or a whole floor) of a building and is part of the secundary regulation for heating and cooling. The room temperature controller was developed according to the KNX standard for use in systems of control of homes and buildings.

Through the integrated sensor, the device can measure directly the room temperature value that can be used for control and regulation tasks of heating, cooling and ventilation. Via the bus the device can furthermore receive temperature values from other bus devices. The integrated display visualizes a series of information concerning the room controller function. The device is provided with two rockers that can be used for controlling the thermostat function. The two physical inputs may be configured independently as analogic or digital and allow to extend the basic functions, optimizing comfort, safety and energy savings depending on the user or building needs.

1.1

Function

The main function of the device is to control the temperature of the air mass of the room by means of the actual temperature (T eff

), measured by the device itself or received by the bus, and of the setpoint temperature (T set

) set by the user; comparing the two values and a series of parameters set before the commissioning, the regulation algorithm of the device calculates the control variable value that is converted to a telegram and transmitted on the bus toward KNX actuators (such as binary outputs, fan-coli controllers, valve drives, etc.) able to control the operation of heating and cooling terminal units.

1.2

Main funcional features

The main functions carried out by the device are:

• temperature and brightness measuring through the integrated sensors with possibility of sending the values on the bus;

• 2-points (on/off) or proportional (PWM or continuous) room temperature regulation;

• ventilation control with continuous or 3-speed regulation;

• seasonal modes: heating and cooling with local or via bus switch-over;

• operating modes: comfort, standby, economy and building protection with separate setpoint values for heating and cooling;

• manual or automatic control of a fan-coil unit with 2-pipes or 4-pipes connection

• automatic switching of the operating mode when presence/absence of people or window opening is detected;

• weighted average of two temperature values;

• temperature displaying (measured, setpoint and outdoor values in °C or °F), alarms and errors (with alphanumeric codification);

• signaling opening windows;

• limitation of the surface temperature for floor heating radiant panels;

• anticondensation protection for floor and ceiling cooling radiant panels;

• antistratification function;

• delayed fan start (“hot-start” function) time-scheduled or depending on the conveying fluid temperature measured at the coil battery.

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 4

1.3

Technical data

Feature

Device

Communication

Use

Environmental conditions

Power supply

Current consumption from bus

Switching elements

Programming elements

Display elements

Sensore di temperatura

Sensore di luminosità

Accessories

Installation

Connection

Protection degree

Dimensions (WxHxD)

Application manual

KNX room temperature controller EK-EP2-TP

Valore

KNX S-mode bus device according KNX TP1 standard dry internal rooms

• Operating temperature: - 5 ... + 45°C

• Storage temperature: - 25 ... + 55°C

• Transport temperature: - 25 ... + 70°C

• Relative hunidity: 95% not condensating

SELV 30 Vdc from bus KNX (auxiliary power supply not necessary)

< 13 mA

2-fold pushbutton

1 pushbutton and 1 LED (red) on the front side

1 backlighted LC-display, 8 LED (4 for each rocker)

1 integrated NTC-type

1 integrated

2 square (40x40 mm) rockers and a square frame of the flank or form series (to be ordered separately) - ‘NF (No Frame versions) do not require any frame

On round or square wall-mounting box with disatnce between fixing holes of 60 mm

• bus: black/red KNX terminal block

• inputs: screw terminal blocks

IP20

82 x 75 x 35 mm

1.4

Design

The device is realised for wall-mounting on round or square wall box with distance between fixing holes of 60 mm. The programming pushbutton and the programming led are on the front side under the rockers. On the rear side of the housing there is the 4-pole terminal block for the connection of the 2 inputs and the terminal block for the connection of the bus.

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Device: front and side sights

Application Manual

Page 5

Application manual

KNX room temperature controller EK-EP2-TP

1.5

Delivery

The delivery includes a device, the terminal block for the connection of the bus, the screws (2 pairs) and the metallic support for mounting on the wall box. The packaging inlcludes also the device instructions.

1.6

Accessories

The device is completed with a set of two square 40x40 mm rockers and a square frame of the form (EK-

FOQ-...) or flank (EK-FLQ-...) series that have to be ordered separately. The ‘NF (No Frame) version does not require any frame (see also the following table). Temperature sensors and other devices to be connected to the inputs must be ordered separately.

Code

EK-EP2-TP

EK-EP2-TP-RW

Version

with frame

Colours of LED

blue / green white / red

Accessories

it requires the rockers’ set EK-TSQ-G...-EP2and a square frame of the form (EK-FOQ-...) or flank (EK-FLQ-...) series

EK-EP2-TP-BG-NF

EK-EP2-TP-RW-NF

‘NF (No Frame) blue / green it requires the rockers

’ set EK-TSQ-G...-EP2

on the

‘NF (No Frame) version no frame is mounted

white / red

Accessories of the device: set of rockers and frames

1.7

Marks and certification

The KNX mark on the ekinex device ensures interoperability with the KNX devices ofSBS and other manufacturers installed on the same system bus system. The compliance with the applicable European directives is indicated by the presence of the CE mark.

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 6

2

Installation

Application manual

KNX room temperature controller EK-EP2-TP

The device has degree of protection IP20, and is therefore suitable for use in dry interior rooms. The installation of the device requires the following steps: a) fix the metallic support with the screws supplied on a wall box with distance between fixing holes of

60 mm. It is recommended to install the device at a height of 150 cm; b) if required, snap a square frame of the form or flank series, inserting it from the rear of the device; c) connect the sensors or the contacts required to the 4-poles screw terminal block on the rear of the device; d) insert the terminal for the bus (red/black), previously connected to the bus cable, in its slot on the rear side. At this point it is recommended to carry out the commissioning of the device or at least the download of the physical address; e) install the device on the metallic support through the spring system, tightening then the two screws f) requires also to tighten the screws included in the delivery. For mounting the device follow also the indication TOP (arrow tip pointing up) on the rear side of the device;. g) snap the two rockers onto the device for the operation of the room temperature controller.

The device can only be mounted on a round or square wall flush mounting box with 60 mm distance between fixing holes. If necessary, the metallic support for mounting on the wall box can also be ordered separately.

2.1

Connection

For the operation the device has to be connected to the bus line and addressed, configured and commissioned with ETS (Engineering Tool Software). The connection of one or two sensors to the inputs is optional and must be defined by the planner of the bus system.

2.1.1

Connection of the bus line

The connection of the KNX bus line is made with the terminal block (red/black) included in delivery and inserted into the slot of the housing.

Characteristics of the KNX terminal block

• spring clamping of conductors

• 4 seats for conductors for each polarity

• terminal suitable for KNX bus cable with single-wire conductors and diameter between 0.6 and 0.8 mm

• recommended wire stripping approx. 5 mm

• color codification: red = + (positive) bus conductor, black = - (negative) bus conductor

2.1.2

Connection of the inputs

The connection of the inputs is made with the screw terminals located at the rear side of the device. The maximum cable length is 10 m. For the connection use a cable of max section 1,5 mm². The connection cable must have sufficient length to allow the extraction of the device from the wall-mounting box.

Characteristics of the terminal blocks for the inputs

• screw clamping of conductors

• maximum cross section of conductor 1 mm² (multiwire)

• recommended wire stripping approx. 5 mm

• torque max 0.2 Nm

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 7

Bus

KNX

+

Application manual

KNX room temperature controller EK-EP2-TP

Connection of the device of the bus line

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 8

3

Configuration and commissioning

Application manual

KNX room temperature controller EK-EP2-TP

The configuration and commissioning are carried out with the ETS (Engineering Tool Software) tool and the ekinex

®

application program provided free of charge by SBS; you do not need any additional software or plug-in tool. For further information on ETS see also www.knx.org

.

3.1

Configuration

The device functionality is defined by the settings done via software. The configuration requires necessarily

ETS4 (or later releases) and the ekinex

®

APEKEP2TP##.knxprod

(## = release) application program that can be downloaded from the website www.ekinex.com

. The application program allows the configuration of all working parameters for the device. The device-specific application program has to be loaded into ETS or, as alternative, the whole ekinex

®

product database can be loaded; at this point, all the instances of the selected device type can be added to the project.

Application program for ETS APEKEP2TP##.knxprod (## = version)

3.1.1

Tree structure of the application program

At its opening, the tree structure of the program includes the following main items:

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 9

Application manual

KNX room temperature controller EK-EP2-TP

About EK-EP2-TP

General

Internal sensors

Inputs

External sensors (from bus)

LCD display

Led

Temperature control

Energy saving

Other items may appear depending on the choices done for the parameters of the folders.

3.1.2

Languages of the application program

The application program is available in four languages: English, Italian, German and French. The language displayed can be changed in ETS choosing "Settings / Presentation language".

3.2

Commissioning

For the commissioning the device is provided on the front side (in the area usually occupied by the rockers) of:

• a red LED (1) for indication of the active operating mode (LED on = programming, LED off = normal operation);

• a pushbutton (2) for switching between the normal and programming operating mode.

1

2

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Device programming: led (1) and pushbutton (2)

Application Manual

Page 10

Application manual

KNX room temperature controller EK-EP2-TP

For commissioning the device the following activities are required:

• make the electrical connections;

• turn on the bus power supply;

• switch the device operation to the programming mode by pressing the programming pushbutton located on the front side of the housing. In this mode of operation, the programming LED is turned on;

• download into the device the physical address and the configuration with the

ETS

®

program.

When downloading the application program the display shows "PrOg" and the flashing symbol of the clock. At the end of the download the operation of the device automatically returns to normal mode; in this mode the programming LED is turned off. Now the bus device is programmed and ready for use.

3.2.1

Displaying physical address and firmware release

Once the first addressing is done, you can check anytime the physical address and the firmware release directly on the device display. In order to display it, press for more than 3 seconds the – (minus) symbol on the lower rocker and the



symbol on the upper rocker. All segments of the display are turned off; displaying a physical address only the 3 large digits and the small one are active. The information displayed in sequence are: the area number (A), the line number (L), the device number (d) and the firmware release

(F). To scroll through the three elements of the physical address press + or –.

Example of displaying the physical address 10.5.43 (device nr. 43, installed on the line 5 of the area 10) and the firmware release 001

To exit from the physical address displaying press shortly (< 3 seconds) the



symbol on the lower rocker. If you elapse of time interval set in parameter “Time to exit change without saving” without pressing any rocker, the device returns automatically to the previously displayed information.

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 11

4

User interface

Application manual

KNX room temperature controller EK-EP2-TP

The user interface of the room temperature controller includes a LC-display, a pushbutton with two rockers and a series of freely programmable LEDs (4 for each rocker). The colour of the LEDs depend on the device version.

2

1

3

User interface: LC-display (1), rockers (2), LEDs (3) with lightguide

The symbols on the rockers recall the function carried out:

+

 temperature or fan speed increase; temperature or fan speed decrease; information sequence, operating mode change, ventilation control, seasonal change-over.

Through a combined pressure of various symbols other functions can be carried out.

4.1

LC-display

The device is provided with a LC-display (1) with adjustable backlight that occupies a vertical area of approx.

40 x 80 mm (WxH) in the left half of the device. Thanks to the integrated brightness sensor, you can set the automatic adjustment of the backlight intensity according to the room brightness conditions.

4.1.1

Information displaying

Depending on the configuration done with ETS, the connections and the availability of information (local or received from the bus), the series of symbols allow to display:

 room actual temperature (it may be the temperature calculated using a weighted average of two values);

 outdoor temperature, preceded by a ‒ (minus) sign in case of outdoor temperature below 0°C;

 temperature setpoint (for the actual operating mode);

 alarm and error condition (A01, A02… E01, E02…);

 window opening;

 operating mode (comfort / standby / economy / building protection);

 seasonal mode (heating / cooling);

 device status calling / not calling (or setpoint reached / not reached);

 operation in manual mode (M);

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 12

 operation as slave device (clock);

 fan status (1-2-3-automatic-off), when present;

 device physical address assigned by ETS.

Display symbols

Digits (for numeric values display)

Celsius degrees

Application manual

KNX room temperature controller EK-EP2-TP

Heating mode active (device not calling or setpoint reached)

Heating mode active (device calling or setpoint not reached)

Fahrenheit degrees Manual operation (M)

Alarm

Window opening

Slave (operation subordinated to a supervising KNX device)

Cooling mode active (device not calling or setpoint reached)

Cooling mode active (device calling or setpoint not reached)

Indoor temperature

Outdoor temperature

SET

OFF (fan-coil switched off)

Automatic fan-coil operation (example: speed 3)

Manual fan-coil operation (example: speed 2)

Building protection operating mode

(off)

Economy operating mode (night)

Standby operating mode

Comfort operating mode

Symbols that can be activated on the LC-display

4.1.2

Segment test

The segment test allows you to check at any time the proper functionality of the display. In order to do the test, press simultaneously + (plus) on the upper rocker and the symbol



on the lower rocker for more than 3 seconds. All symbols are activated simultaneously; then all the symbols are turned off. In the test phase keep available the instructions or the user guide.

If you elapse the time set in the parameter "Time to exit change without saving" (General folder) without pressing a button, the device will return to the previous situation.

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 13

4.1.3

Backlight

Application manual

KNX room temperature controller EK-EP2-TP

The backlight intensity of the LC-display is adjustable. The first setting is done when configuring the device using ETS, but the intensity can be changed later at any time.

To access the change press simultaneously + (plus) and



(bothon the upper rocker) for more than 3 seconds. All symbols are turned off except the digits and the percentage symbol. The actual value (as a percentage) of backlight intensity is displayed. At each pressing of + or – the intensity is increased or decreased by 5%. To confirm the selected intensity press shortly (< 3 seconds) the



symbol either on the upper rocker. Three rapid flashes of the digits indicate that the new value was saved. If you elapse of time interval set in the "Time to exit change without saving " (General folder) without pressing any rocker, the device returns to the previous situation.

4.2

Rockers

The pushbutton with two rockers integrated in the device controls the functions of the thermostat. The set of two rockers has to be ordered separately; the symbols on the rockers of the set are pre-defined and cannot be changed. The areas marked by the symbols + (plus) and – (minus) allow you to change a setting (e.g. the temperature setpoint), while those marked by the symbol ●●●● allow you to display a sequence of information, to change the operating mode, to control the ventilation, to do the seasonal change-over

(heating to cooling and vice versa) or to confirm a setting change.

The part number of the set EK-TSQ-Gxx-EP2 must be completed with the part (xx) that identifies the material, color and finishing; for the exact code please refer also to the latest edition of the ekinex product catalog or the website www.ekinex.com.

Rockers use Upper rocker Lower rocker

Functions for room temperature controlling

+ and   and ‒

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 14

5

Sensors

Application manual

KNX room temperature controller EK-EP2-TP

The room temperature controller is equipped with three sensors:

• temperature (1);

• brightness (2).

2

1

Positioning of the sensors: temperature (1), relative humidity (2) and brightness (3).

The temperature sensor (not to be seen in the drawing) is located under the plastic half-shell for the rockers’ mounting.

5.1

Temperature sensor

The integrated temperature sensor allows the measureming of the room temperature in the range from 0 °C to +40 °C with a resolution of 0.1 °C. To keep into account significant environmental interferences such as the proximity to heatsources, the installation on an outer wall, the chimney effect due to rising warm air through the corrugated tube connected to the wall-mounting box, the measured value can be corrected by means of a offset of ± 2.5 K or, preferably, can be used a weighted average between two values of temperature chosen from the following ones: value measured by the integrated sensor, value measured by a temperature sensor connected to one of the inputs of the device, value received via bus from another KNX device (such as ekinexpushbuttons).

5.2

Brightness sensor

The integrated brightness sensor allows the measuring of the light intensity of the room. The sensor can be used to automatically adjust the backlight of the LC-display, but its value can also be sent on the bus via the

Object Communication 1 Brightness value.

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 15

6

Input variables

Application manual

KNX room temperature controller EK-EP2-TP

The data that the device usesin its control algorithms and /or to be displayed may come from:

• the internal sensors;

• sensors or digital signals connected to the two physical inputs of the device;

• the KNX bus through standard Communication Objects.

The processed data can also be transmitted on the KNX bus as Communication Objects.The classification of the input variables is shown in the following table.

Data

Room temperature

Room brightness

Several (depending on the choosen application)

Window state (open/close)

Card holder state (badge in/out)

Presence of condensation

Conveying fluid temperature at the exchange coil

Room temperature (for weighted average value)

Room temperature (other measurement height)

Floor surface temperature

Outdoor temperature

Further temperature value

Room temperature

Antistratification temperature

Outdoor temperature

Conveying fluid temperature at the exchange coil

Floor surface temperature

Presence of condensation

Window state (open/close)

Presence of people in the room

Card holder state (badge in/out)

Coming from

Internal sensor

Input 1 or 2 (device terminals) configurated

KNX bus (through communication objects)

Description

Analogic value for thermoregulation functions

Analogic value for brightness adjusting of the display and value sending on the bus (for other purposes)

[DI] generic digital input

[DI] window contact sensor

[DI] card holder contact sensor

[DI] anticondensation sensor

[AI] coil battery temperaure sensor

[AI] room temperature sensor

[AI] antistratification temperature sensor

[AI] floor surface temperature sensor

[AI] outdoor temperature sensor

[AI] generic (NTC) temperature sensor

Object 147 (2 bytes)

Object 137 (2 bytes)

Object 138 (2 bytes)

Object 140 (2 bytes)

Object 141 (2 bytes)

Object 146(1 bit)

Objects 143 and 144 (1 bit)

Objects 132 and 133 (1 bit)

Object 145 (1 bit)

Input variables from internal sensors, physical inputs and standard communication objects.

The device does not have outputs for direct switching or control of heating/cooling terminals or for status or values signalling. The output variables include exclusively communication objects that are sent on the bus, received and processed by KNX actuators (general-purpose or dedicated to HVAC applications).

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 16

7

Application program for ETS

Application manual

KNX room temperature controller EK-EP2-TP

In the following chapters there is the list of folder, parameters and communication objects of the application program. Some specific functions of the thermostat are described in more detail in the dedicated paragraphs.

The tree structure of the application program as imported into ETS(or by pressing the "Default Parameters" button of ETS) is the following:

About EK-EQ2-TP

General

Internal sensors

Temperature sensor

Inputs

External sensors (from bus)

LCD display

LED

Temperature control

Settings

Heating

Energy saving

Window contact

Presence sensor

Card holder

Other folders may appear depending on the choices done for the parameters of the folders represented in the main tree structure.

7.1

About EK-EP2-TP

The folder

About EK-EP2-TP

is for information purposes only and does not contain parameters to be set.

The information given is :

© Copyright SBS S.p.A. 2014

Application software for ETS4

Version 1.00 (or later)

KNX room temperature controller with LC-display

SBS S.p.A.

Via Circonvallazione s/n

I-28010 Miasino (NO) Italy www.ekinex.com [email protected]

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 17

7.1.1

General

The

General

folder includes the following parameters:

Device operation as

Temperature displayed unit

Default displayed information

Time to return to default display information

Button function level

Time to exit change without saving

Delay after bus voltage recovery

The folder has no secondary folders.

Application manual

KNX room temperature controller EK-EP2-TP

7.1.2

Parameter table

Parameter name

Device operation as

Temperature displayed unit

Default displayed information

Time to return to default display information

Button function level

Time to exit change without saving

Delay after bus voltage recovery

Conditions Values

stand-alone

slave

If configured as slave, the room temperature controller receives from a KNX device (acting as supervisor) HVAC modes, setpont values, etc.

Celsius

Fahrenheit

actual temperature

temperature setpoint

The actual temperature is the value by which the device performs the temperature regulation. It may be the value measured from a single sensor (internal, from the bus or from an input) or the weighted average of the temperatures measured by a main sensor and an additional sensor.

The displayed setpoint temperature is that of the operating mode currently set on the room temperature controller (deduced from the symbol on).

5 s

[other values in the range 10 s … 1 min]

Time interval after which the display automatically switches between the manually recalled information to the default information.

end user

system integrator

This parameter allows you to partially disable the functions that can be recalled using the rockers. The functions that are not enabled if Button function level = end user are the following:

heating / cooling changeover

backlight intensity change

test of display segments

display of physical address and firmware release

8 s

[other values in the range 2 s … 12 s]

Time interval without further pressing of the rockers at the end of which the device exits the procedure without saving the current changes.

00:00:04.000 hh:mm:ss:fff

[range 00:00:04.

000 … 00:10:55.350]

Time interval after which the transmission of the telegrams on the bus starts after the power supply is restored. The delay affects both the event-driven transmission and the cyclic transmission of a telegram. Regarding the latter, the counting of the pause interval for retransmission starts at the end of the time of initial delay.

The field has format hh:mm:ss:fff (hours : minutes : seconds .milliseconds): the default value

00:00:04.000 corresponds to 4 seconds.

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 18

Application manual

KNX room temperature controller EK-EP2-TP

Information displayed as default

One information between the

actual temperature

and the

temperature setpoint

is displayed preferably by the digits of the display. The device allows you to retrieve and display a series of other information pressing the

●●●● symbol on the upper rocker ; after the time set in the parameter "Time to return to default information" without further pressure of ●●●●, the display automatically returns to the default information.

Functional level of the rockers

The use of the rockers for controlling the room temperature controller can be partially inhibited in the configuration phase through a filter for the access to the several functions. When using the rockers a distinction is made between:

 first level functions (= short or long pressing of the rockers) for the end user;

 second level functions (= combination of rockers); to the first level are added a few functions for a system integrator or an installer.

The enabled functional level is set through a special parameter.

7.2

Internal sensors

The

Internal sensors

folder includes the following parameters:

Temperature sensor

Brightness sensor

7.2.1

Parameter table

Parameter name

Temperature sensor

Brightness sensor

Conditions Values

enabled

disabled

The temperature sensor is enabled as default.

When the sensor is disabled, the corresponding folder disappears from the main tree structure of the application program; in this case to have available again the functions for Temperature control you have to enable Room temperature in the External sensors (from bus) folder or set Input X = [AI] temperature sensor (X = 1, 2) in the Inputs folder.

disabled

enabled

The brightness sensor is disabled as default. When the sensor is enabled, the corresponding folder appears in the main tree structure of the application program.

7.2.2

Temperature sensor

The

Temperature sensor

secondary folder appears only if the corresponding sensor is enabled in the folder

Internal sensors

and includes the following parameters:

Filter type

Temperature offset

Minimum change of value to send [K]

Cyclic sending interval

Threshold 1

Threshold 2

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 19

7.2.2.1

Parameter and communication object tables

Parameter name

Filter type

Temperature offset

Minimum change of value to send [K]

Cyclic sending interval

Threshold 1

Value [°C]

Threshold 2

Value [°C]

Hysteresis

Cyclic sending interval

Application manual

KNX room temperature controller EK-EP2-TP

Conditions

Temperature sensor = enabled

Values

low

medium

high

Low = average value every 4 measurements

Medium = average value every 16 measurements

High = average value every 64 measurements

Temperature sensor = enabled

0°C

[range -2,5°C … +2,5°C]

Temperature sensor = enabled

0,5

[range 0 …5]

If the parameter is set to 0 (zero),no value is sent after a change.

Temperature sensor = enabled

no sending

[other values in the range 30 s … 120 min]

Temperature sensor = enabled

not active

below above

Temperature sensor = enabled,

Threshold 1 = below or above

[range

7

0 … 50]

Temperature sensor = enabled

not active

below above

45

[range

0 … 50]

Temperature sensor = enabled,

Threshold 2 = below or above

Temperature sensor = enabled,

Threshold 1 and/or Threshold 2

= below or above

Temperature sensor = enabled,

Threshold 1 and/or Threshold 2

= below or above

0,4 K

[other values between 0,2 K and 3 K]

no sending

[other values in the range 30 s … 120 min]

Object name Conditions Dim.

2 Bytes

Flags

CR-T--

DPT

[9.001] temperature (°C)

Comm.

Obj. No.

3

Temperature value

Temperature threshold1 - Switch

Temperature threshold 2- Switch

Temperature sensor = enabled

Temperature sensor = enabled,

Threshold 1 = below or above

Temperature sensor = enabled,

Threshold 2 = below or above

1 Bit

1 Bit

CR-T--

CR-T--

[1.001] switch

[1.001] switch

116

117

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 20

Application manual

KNX room temperature controller EK-EP2-TP

Acquisition filter

The acquisition filter calculates an average with a series of measured values before sending on the bus. The parameter can have the following values:

 low = average value every 4 measurements;

 medium = average value every 16 measurements;

 high = average value every 64 measurements.

Correction of the measured temperature

The sampling of the temperature value occurs every 10 seconds, while the display is updated every minute.

During the configuration with ETS the opportunity is given to correct the measured temperature value within the offset range of - 2.5 °C ... + 2.5 °C (step: 0.1 K).

7.2.3

Brightness sensor

The

Brightness sensor

secondary folder appears only if the corresponding sensor is enabled in the folder

Internal sensors

and includes the following parameters:

Filter type

Sensor value multiplier (1÷255) x 0,1

Minimum change of value to send [%]

Cyclic sending interval

Threshold 1

Threshold 2

Value [Lux]

Hysteresis

Using the brightness value

The value measured by the brightness sensor integrated in the device may be used for:

 sending the value on the KNX bus through a communication object;

 automatically adjusting the light intensity emitted by the backlight of the display.

7.2.3.1

Parameter and communication object tables

Parameter name

Filter type

Sensor value multiplier (1÷255) x 0,1

Minimum change of value to send [Lux]

Cyclic sending interval

Threshold 1

Conditions

Brightness sensor = enabled

Values

low

medium

high

Low = average value every 4 measurements

Medium = average value every 16 measurements

High = average value every 64 measurements

Brightness sensor = enabled

10

[other values in the range

1… 255]

Brightness sensor = enabled

50

[other values in the range 0

… 670760]

If the parameter is set to 0 (zero), no value is sent after a change.

Brightness sensor = enabled

no sending

[other values in the range 30 s … 120 min]

Brightness sensor = enabled

not active

/ below / above

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 21

Parameter name

Value [Lux]

Threshold 2

Value [Lux]

Hysteresis

Cyclic sending interval

Object name

Brightness value -

Light threshold 1 - Switch

Light threshold 2 - Switch

Conditions

Brightness sensor = enabled,

Threshold 1 = below or above

Values

500

[other values in the range

0 … 670760]

Brightness sensor = enabled

not active

/ below / above

Brightness sensor = enabled,

Threshold 2 = below or above

500

[other values in the range

0 … 670760]

Threshold 1 = below or above,

Threshold 2 = below or above

Brightness sensor = enabled, Soglia

1 e/o Soglia 2 = sotto o sopra

50 lux

[other values in the range

5 … 200 Lux]

The value of the parameter Hysteresis is common for both parameters Threshold 1 and Threshold 2.

no sending

[other values in the range30 s … 120 min]

The value of the parameter Cyclic sending interval is common for both parameters

Threshold 1 and Threshold 2.

Conditions

Brightness sensor = enabled

Brightness sensor = enabled,

Threshold 1 = below or above

Brightness sensor = enabled,

Threshold 2 = below or above

Application manual

KNX room temperature controller EK-EP2-TP

Dim.

2 Byte

Flags

CR-T--

DPT

[9.004] lux (Lux)

Comm.

Obj. No.

1

1 Bit

1 Bit

CR-T--

CR-T--

[1.001] switch

[1.001] switch

20

37

7.3

Inputs

The folder

Inputs

allows you to configurate one or two variables (either digital or analogic) depending on the digital signals or the temperature sensors connected to the terminal blocks of the inputs. The physical values or the detected states can be used locally by the device for temperature control functions and/or transmitted on the bus for other purposes. The folder includes the parameters for configuring independently the inputs 1 and 2. The two inputs are identical; for simplicity in the following only parameters and communication objects of a single input are described.

7.3.1

Input X

The folder

Input X

(X = 1, 2) includes the following parameters:

Input X

Contact type

Filter type

Temperature offset

Cyclic sending interval

Minimum change of value to send (K)

Threshold 1

Value [°C]

Threshold 2

Value [°C]

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 22

Hysteresis

Cyclic sending interval

Application manual

KNX room temperature controller EK-EP2-TP

7.3.2

Parameter and communication object tables

Parameter name

Input X

Contact type

Debounce time

Type

Filter type

Offset temperature

Minimum change of value to send [K]

Cyclic sending interval

Threshold 1

Vaue [°C]

Threshold 2

Conditions Values

disabled

[DI] generic digital input

[DI] window contact sensor

[DI] card holder contact sensor

[DI] anticondensation sensor

[AI] coil battery temperature sensor

[AI] room temperature sensor

[AI] antistratification temperature sensor

[AI] floor surface temperature sensor

[AI] outdoor temperature sensor

[AI] generic (NTC) temperature sensor

The [DI] prefix indicates a digital input, the [AI] prefix an analogic input.

Input X = [DI]

NO (normally open)

NC (normally closed)

This parameter is always available when the input is configured as digital.

Input X = [DI

] …

00:00:00.200 hh:mm:ss.fff

[range 00:00:00.000

… 00:10:55.350]

This parameter is always available when the input is configured as digital. The field has format hh:mm:ss:fff (hours : minutes : seconds . milliseconds): the default value

00:00:00.200 corresponds to 200 milliseconds.

Input X = [DI] generic digital input

send values or sequences

dimming shutter or venetian blind scene counter

This parameter is available only when the input is configured as generic digital..

Input X

= [AI] … low

medium

high

This parameter is always available when the input is configured as analogic.

Low = average value every 4 measurements

Medium = average value every 16 measurements

High = average value every 64 measurements

Input

X = [AI] …

0°C

[range -2,5°C … +2,5°C]

This parameter is always available when the input is configured as analogic.

0,5

[range 0

…5]

This parameter is always available when the input is configured as analogic. When set to 0 (zero), no value is sent at a change.

Input X different from disabled

no sending

[other values in the range

30 s … 120 min]

Input X =

[AI] …

not active

/ below / above

This parameter is always available when the input is configured as analogic.

Input

X = [AI] …

Threshold 1 = below or above

7

[range 0

… 50]

Input

X = [AI] …

not active

/ below / above

This parameter is always available when the input is configured as analogic.

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 23

Parameter name

Application manual

KNX room temperature controller EK-EP2-TP

Value [°C]

Conditions

Input X

= [AI] …

Threshold 2 = below or above

Values

45

[range 0

… 50]

Hysteresis

Input

X = [AI] …

Threshold 1 = below or above

Threshold 2 = below or above

0,4 K

[other values in the range

0,2 K … 3 K]

Cyclic sending interval

Input

X = [AI] …

Threshold 1 = below or above

Threshold 2 = below or above

no sending

[other values in the range

30 s … 120 min]

Object name

Input 1 – Lock command

Input 2 - Lock command

Window contact sensor (from input 1)

Window contact sensor (from input 2)

Anticondensation sensor (from input 1)

Anticondensation sensor (from input 2)

Card holder contact sensor

(from input 1)

Card holder contact sensor

(from input 2)

Coil battery temperature sensor (from input 1)

Coil battery temperature sensor (from input 2)

Conditions Dim. Flags DPT

Comm.

Obj. No.

Input 1 = [DI] digital generic input

1 Bit CR-T--

[1.xxx] 1 Bit

80

Input 2 = [DI] digital generic input

1 Bit CR-T--

[1.xxx] 1 Bit

97

Input 1 = [DI] windows contact sensor

1 Bit CR-T--

[1.019] window/door

126

Input 2 = [DI] windows contact sensor

1 Bit CR-T--

[1.019] window/door

127

If both inputs (1 and 2) are configured in the same way, only the first one is used by the device.

Input 1 = [DI] anticondensation sensor

1 Bit CR-T-- [1.005] alarm 128

Input 2 = [DI] anticondensation sensor

1 Bit CR-T-- [1.005] alarm 129

If both inputs (1 and 2) are configured in the same way, only the first one is used by the device.

Input 1 = [DI] card holder contact sensor

1 Bit CR-T-- [1.018] occupancy 130

Input 2 = [DI] card holder contact sensor

1 Bit CR-T-- [1.018] occupancy 131

If both inputs (1 and 2) are configured in the same way, only the first one is used by the device.

Input 1 = [AI] coil battery temperature sensor

2 Byte CR-T--

[9.001] temperature

(°C)

120

Input 2 = [AI] coil battery temperature sensor

2 Byte CR-T--

[9.001] temperature

(°C)

123

If both inputs (1 and 2) are configured in the same way, only the first one is used by the device.

Temperature value sensor

(from input 1)

Input 1 = [AI] room temperature sensor

2 Byte CR-T--

[9.001] temperature

(°C)

120

Temperature value sensor

(from input 2)

Input 2 = [AI] room temperature sensor

2 Byte CR-T--

[9.001] temperature

(°C)

123

If both inputs (1 and 2) are configured in the same way, only the first one is used by the device.

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 24

Object name

Antistratification temperature sensor (from input 1)

Antistratification temperature sensor (from input 2)

Floor surface temperature sensor (from input 1)

Floor surface temperature sensor (from input 2)

Outdoor temperature sensor

(from input 1)

Outdoor temperature sensor

(from input 2)

Temperature value sensor

(from input 1)

Temperature value sensor

(from input 2)

Temperature threshold 1 sensor 1 - Switch

Temperature threshold 2 sensor 1 - Switch

Temperature threshold 1 sensor 2 - Switch

Temperature threshold 2 sensor 2 - Switch

Application manual

KNX room temperature controller EK-EP2-TP

Conditions Dim. Flags DPT

Comm.

Obj. No.

Input 1 = [AI] antistratification temperature sensor

2 Byte CR-T--

[9.001] temperature °C

120

Input 2 = [AI] antistratification temperature sensor

2 Byte CR-T--

[9.001] temperature °C

123

If both inputs (1 and 2) are configured in the same way, only the first one is used by the device.

Input 1 = [AI] floor surface temperature sensor

2 Byte CR-T--

[9.001] temperature °C

120

Input 2 = [AI] floor surface temperature sensor

2 Byte CR-T--

[9.001] temperature °C

123

If both inputs (1 and 2) are configured in the same way, only the first one is used by the device.

Input 1 = [AI] outdoor temperature sensor

2 Byte CR-T--

[9.001] temperature °C

120

Input 2 = [AI] outdoor temperature sensor

2 Byte CR-T--

[9.001] temperature °C

123

If both inputs (1 and 2) are configured in the same way, only the first one is used by the device.

Input 1 = [AI] generic (NTC) temperature sensor

2 Byte CR-T--

[9.001] temperature °C

120

Input 2 = [AI] generic (NTC) temperature sensor

2 Byte CR-T--

[9.001] temperature °C

123

If both inputs (1 and 2) are configured in the same way, only the first one is used by the device.

Input

1 = [AI] …

Threshold 1 = below or above,

Threshold 2 = below or above

1 Bit CR-T-- [1.001] switch 121

Input

1 = [AI] …

Threshold 1 = below or above,

Threshold 2 = below or above

1 Bit CR-T-- [1.001] switch 122

Input 2=

[AI] …

Threshold 1 = below or above,

Threshold 2 = below or above

1 Bit CR-T-- [1.001] switch 124

Input 2

= [AI] …

Threshold 1 = below or above,

Threshold 2 = below or above

1 Bit CR-T-- [1.001] switch 125

7.4

External sensors (from bus)

As “external sensors” are intended KNX-devices (or conventional sensors interfaced to the bus through KNX devices) which send states or values to the room temperature controller via the bus. Enabling an external sensor, without connecting the corresponding communication object, generates a permanent alarm on the display and suspends the thermoregulation function.

The folder

External sensors (from bus)

includes the following parameters:

Room temperature

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 25

Antistratification temperature

Outdoor temperature

Floor surface temperature

Anticondensation

Window contact X (X = 1, 2)

Presence sensor X (X = 1, 2)

Card holder contact

Analog sensor timeout

Digital sensor timeout

The folder does not have any secondary folder.

Application manual

KNX room temperature controller EK-EP2-TP

7.4.1

Parameter and communication object tables

Parameter name

Room temperature

Antistratification temperature

Outdoor temperature

Air quality

Coil temperature

Floor surface temperature

Analogic sensors timeout

Anticondensation

Window contact 1

Window contact 2

Presence sensor 1

Conditions Values

disabled

/ enabled

It enables a bus temperature sensor. The measured value can be used to calculate a weighted average value in combination with the temperature sensor integrated into the device or a temperature sensor connected to a device input.

disabled

/ enabled

I t enables a temperature bus sensor to carry out the antistratification function.

disabled

/ enabled

I t enables an outdoor temperature bus sensor to display the measured value on the display. This is alternative to an outdoor temperature sensor connected to a device input: the parameter appears only if the external temperature sensor is disabled in the Inputs folder.

disabled

/ enabled

I t enables an air quality bus sensor to display the measured value (CO

2 concentration) on the display.

disabled

/ enabled

I t enables a bus sensor for measuring the conveying fluid temperature at the coil for heat exchange. The acquisition of the value allows realizing the hot- start function of a fan.

disabled

/ enabled

I t enables a bus sensor for measuring the surface temperature of a floor heating system. The acquisition of the value allows to realize the function of surface temperature limitation.

00:05:00hh:mm:ss

[range

00:00:00 … 18:12:15]

The field has format hh:mm:ss (hours : minutes : seconds): the default value

00:05:00 corresponds to a timeout of 5 minutes. The value 00:00:00 means that the timeout of the analogic sensors is disabled.

disabled

/ enabled

I t enables a bus sensor for detecting the condensation.

disabled

/ enabled

I t enables a bus sensor for detecting the state of opening / closing of a window or a door.

disabled

/ enabled

I t enables a bus sensor for detecting the state of opening / closing of a window or a door.

disabled

/ enabled

I t enables a bus sensor for detecting the presence / absence of people within a room.

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 26

Parameter name

Presence sensor 2

Card holder contact

Digital sensors timeout

Application manual

KNX room temperature controller EK-EP2-TP

Conditions Values

disabled

/ enabled

I t enables a bus sensor for detecting the presence / absence of people within a room.

disabled

/ enabled

I t enables a bus sensor for detecting the presence / absence of people in a hotel room provided with a card holder.

00:05:00hh:mm:ss

[range

00:00:00 … 18:12:15]

The field has format hh:mm:ss (hours : minutes : seconds): the default value

00:05:00 corresponds to a timeout of 5 minutes. The value 00:00:00 means that the timeout of the digital sensors is disabled.

Object name

Room temperature (from bus)

Antistratification temperature (from bus)

Outdoor temperature (from bus)

Coil temperature (from bus)

Floor temperature (from bus)

Anticondensation (from bus)

Windows contact sensor 1 (from bus)

Windows contact sensor 2 (from bus)

Presence sensor 1 (from bus)

Presence sensor 2 (from bus)

Contact of card holder (from bus)

Conditions

enabled enabled enabled enabled enabled enabled enabled enabled enabled enabled enabled

Dim.

2 Byte

2 Byte

2 Byte

2 Byte

2 Byte

1 Bit

1 Bit

1 Bit

1 Bit

1 Bit

1 Bit

Flags

C-W---

C-W---

C-W---

C-W---

C-W---

C-W---

C-W---

C-W---

C-W---

DPT

[9.001] temperature (°C)

[9.001] temperature (°C)

[9.001] temperature °C

[9.001] temperature (°C)

[9.001] temperature (°C)

[1.001] switch

[1.019] window/door

[1.019] window/door

C-W--- [1.018] occupancy

C-W--- [1.018] occupancy

[1.001] switch

Comm. Obj.

No.

134

137

138

140

141

146

143

144

132

133

145

About the sensor timeout

The system of internal control of the thermostat monitors cyclically the updating status of the values of the external sensors (from bus) and the inputs when the timeout setting expires. In case no updated value has been received, the regulation function is suspended, an alarm is displayed on the display through the symbol and the corresponding alarm code (see also the list of alarms in the paragraph Diagnostics).

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 27

Application manual

KNX room temperature controller EK-EP2-TP

7.5

Weighted temperature value

The

Weighted temperature value

folder appears only if two sensors for measuring the room temperature are enabled and includes the following parameters:

Main source for temperature value

Additional source temperature value

Relative weight

Minimum change of value to send [K]

Cyclic sending interval

7.5.1

Parameter and communication object tables

Parameter name

Main source for temperature value

Additional source temperature value

Relative weight

Minimum change of value to send [K]

Cyclic sending interval

Conditions Values

*

*) The values that can be set depend on enabling the internal sensor, the inputs or the external sensors (from bus).

*

*) The values that can be set depend on enabling the internal sensor, the inputs or the external sensors (from bus).

100% main sensor

90% / 10%

80% / 20%

70% / 30%

60% / 40%

50% / 50%

40% / 60%

30% / 70%

20% / 80%

10% / 90%

100% additional sensor

0,5

[other values in the range

0 … 5 K]

If the parameter is set to 0 (zero), no value is sent at the change.

no sending

[other values in the range 30 s … 120 min]

Object name

Weighted temperature

Conditions

Cyclic sending interval different than no sending

Dim.

2 Byte

Flags

CR-T--

DPT

[9.001] temperature °C

Comm.

Obj. No.

147

About the weighted temperature

The device allows the acquisition of the room temperature in three ways:

1) from the temperature sensor integrated in the device;

2) from an external temperature sensor connected to a device input configured as analogic (Inputs

Input 1 or 2 = [AI] room temperature sensor);

3) via bus from another KNX device, e.g. from an ekinex pushbutton (External sensors (from bus)

Room temperature = enabled);

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 28

Application manual

KNX room temperature controller EK-EP2-TP

To optimize or correct the room temperature regulation in special cases (in large rooms, in presence of strong asymmetry of the temperature distribution, when the installation of the device is in a position not suitable, etc.), the device can then use a weighted average between two temperature values. The weights are assigned by the parameter

Relative weight

that assigns a ratio of the two values.

7.6

LC-display

The folder

LCD display

includes the following parameters:

Backlight intensity

Automatic backlight dimming

Energy saving

Visualisation type

Time before energy saving mode

Backlight when in energy saving mode

Behaviour on button press

Temperature setpoint

Energy saving mode

After a configurable time interval, the room temperature controller switches from normal to energy saving operation. In this display mode:

 the backlight intensity may be reduced;

 the information content to be displayed may be reduced da visualizzare può essere ridotto (two options: partial and temperature only).

Backlight

The default backlight of the display can be configured according to the installation location and light conditions of the room. The backlight intensity can be set to a fixed value (in %) or automatically adjusted by means of the brightness sensor integrated in; for this function it is necessary to enable the brightness sensor.

Information to be displayed

The actual temperature is always displayed; in addition, and depending on individual preferences, other information can be displayed in sequence.

7.6.1

Parameters

Parameter name

Backlight intensity

Automatic backlight dimming

Energy saving

Conditions Values

10% / 20% / 30% / 40% /

50%

/

60% / 70% / 80% / 90% / 100%

Internal sensors

Brightness sensors = enabled

disabled

/ enabled

It enables the automatic correction of the intensity of the backlight of the display according to the room brightness detected by the corresponding sensor.

disabled

/ enabled

If the parameter Energy saving = enabled, after a certain time interval the device automatically reduces the backlight intensity and possibly the information content displayed.

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 29

Parameter name

Visualisation type

Time before energy saving mode

Backlight when in energy saving mode

Behaviour on button press

Application manual

KNX room temperature controller EK-EP2-TP

Conditions

Energy saving = enabled

Values

full

temperature only

In addition to the digits,

“temperature only” includes the symbol (°C or °F).

Energy saving = enabled

10 s

/ 15 s / 30 s

45 s / 1 min

Energy saving = enabled off / 2% / 5% / 10% /

15% / 20% /

25%

/ 30%

Energy saving = enabled

backlight only

backlight and button function

It defines the reaction at the first press of a rocker when the device is in energy saving mode.

At least one temperature sensor enabled

(internal, external from bus, from an input)

enable

/ disabled

Temperature setpoint

7.7

Leds

Each pushbutton channel has four programmable leds; for example, for status feedback of the controlled loads or for orientation nightlight. The light emitted by the leds is diffused by means of an appropriate lightguide.

The folder

Led

includes the following parameters:

Leds intensity from bus

Leds intensity

Leds intensity correlation

Led first colour XY (X = 1, 2; Y= A, B)

Led second colour XY (X = 1, 2; Y= A, B)

Off delay

Always

Blinking

Blinking period / type

Signal from bus

Technical alarm

7.7.1

Parameter and communication object tables

Parameter name

Leds intensity from bus

Leds intensity

Conditions Values

no

/ yes

It enables receiving from the bus of the light intensity value emitted by the Leds.

Leds intensity from bus = no

50%

[range 0%

… 100%]

It allows setting the light intensity value emitted by the leds (if not received from the bus).

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 30

Parameter name

Leds intensity correlation

Led first colour XY

Off delay

Always

Blinking

Blinking period / type

Signal from bus

Led second colour XY

Off delay

Always

Blinking

Application manual

KNX room temperature controller EK-EP2-TP

Conditions

Brightness sensor = enabled

Values

high inverse medium inverse low inverse

none

low direct medium direct high direct

It allows setting the kind of correlation between the intensity of light emitted by the leds and the brightness measured in the room (by the integrated sensor) or received from the bus.

fixed

when contact close

status from bus

X = 1, 2; Y= A, B

Led first colour XY = when contact close

00:00:02:00 hh:mm:ss:ff

[other values in the range

00:00:00:00 … 01:49:13:50]

Led first colour XY = fixed

off

/ on

Led first colour XY = status from bus

no

/ yes

Led first colour XY = status from bus,

Blinking = yes

0,25 s on / 0,25 s off

0,25 s on / 0,75 s off

0,5 s on / 0,5 s off

0,75 s on / 0,25 s off

0,5 s on / 1,5 s off

1 s on / 1 s off

1,5 s on / 0,5 s off

1 s on / 3 s off

2 s on / 2 s off

3 s on / 1 s off

Led first colour XY = status from bus

not inverted

/ inverted fixed

when contact closed

status from bus

X = 1, 2; Y= A, B

00:00:02:00

[other values in the range

00:00:00:00 … 01.49.13:50]

Value in hh:mm:ss:ff.

Led second colour XY = fixed

Led second colour XY = status from bus

off no

/ on

/ yes

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 31

Parameter name

Blinking period / type

Signal from bus

Technical alarm

Object name

Technical alarm

Leds intensity percentage

Rocker X- Led first colour A

Rocker X- Led second colour

A

Rocker X- Led first colour B

Rocker X- Led second colour

B

Application manual

KNX room temperature controller EK-EP2-TP

Conditions

Led second colour XY = status from bus,

Blinking = yes

Values

0,25 s on / 0,25 s off

0,25 s on / 0,75 s off

0,5 s on / 0,5 s off

0,75 s on / 0,25 s off

0,5 s on / 1,5 s off

1 s on / 1 s off

1,5 s on / 0,5 s off

1 s on / 3 s off

2 s on / 2 s off

3 s on / 1 s off

Led second colour XY = status from bus

not inverted

/ inverted

disabled

/ enabled

It enables the communication object nr. 0 "Technical alarm" that allows to activate an alarm signal via a bus telegram. The flashing led indicates that the alarm condition is active.

Conditions

Leds intensity from bus = yes

Led first colour XA = status from bus

Led second colour XA = status from bus

Led first colour XB = status from bus

Led second colour LED XB = status from bus

Dim.

1 Bit

1 Bit

1 Bit

1 Bit

1 Bit

1 Bit

Flags

C--W-

C--W-

DPT

[1.005] alarm

[5.001] percentage

CRWTU- [1.001] switch

CRWTU- [1.001] switch

CRWTU- [1.001] switch

CRWTU- [1.001] switch

Comm.

Obj. No.

0

2

38 (X = 1)

76 (X = 2)

39 (X = 1)

77 (X = 2)

40 (X = 1)

78 (X = 2)

41 (X = 1)

79 (X = 2)

7.8

Temperature control

The

Temperature control

folder includes the following secondary folders:

Settings

Heating

Cooling

Ventilation

Scenes

The

Cooling

and

Ventilation

secondary folders appear only if in the

Settings

folder the parameter

Thermostat function is set to the value

both heating and cooling

or

cooling

.

The

Scenes

secondary folder appears only if in the

Settings

secondary folder the parameter Scenes is set to the value

enabled

.

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 32

7.8.1

Settings

The

Settings

folder includes the following parameters:

Thermostat function

Command Communication Object

Heating – cooling switchover

Setpoint Cyclic sending interval

Max manual temperature change

Saving timeout (manual change)

End of manual operation

Max setpoint temperature change

Scenes

Valve protection function

Frequency

Time interval

Application manual

KNX room temperature controller EK-EP2-TP

7.8.1.1

Parameter and communication object tables

Parameter name

Thermostat function

Command Communication Object

Heating

– cooling switchover

Setpoint cyclic sending interval

Max manual temperature change

Saving timeout (manual change)

End of manual operation

Max setpoint temperature change

Conditions Values

heating

cooling both heating and cooling

Thermostat function = both heating and cooling

separated

/ unique

Thermostat function = both heating and cooling manual

from bus

automatic

no sending

[other values in the range

30 s … 120 min]

The setpoint value that can be sent cyclically is the actual one, depending on the operating mode set manually by the user or automatically by another KNX supervising device with the possibility of time scheduling. The actual setpoint value takes also into account the actual state of the contacts window and presence detection (if the corresponding functions are enabled).

not allowed, ± 1°C, ± 2°C,

± 3°C

, ± 4°C, ±

5°C, ± 6°C, ± 7°C, ± 8°C, ± 9°C, ± 10°C

It defines the maximum range allowed for the manual change of the temperature value.

6 s

[other values in the range

2s … 12 s]

It defines the time interval to wait for a confirmation of a manual change (see previous parameter). If the time interval elapses without confirmation, the device automatically returns to the previous state without saving the change.

General

Device operation as = stand-alone

till first telegram from bus

[other values in the range

30 min … 48 h] not allowed, ± 1°C, ± 2°C, ± 3°C, ± 4°C, ±

5°C, ± 6°C, ± 7°C, ± 8°C,

± 9°C

, ± 10°C

It defines the maximum time allowed for changing the values of temperature setpoint in the several operating modes.

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 33

Parameter name

Scenes

Valve protection function

Frequency

Time interval

Nome oggetto

Actual setpoint

Heating/cooling status out

Heating/cooling status in

HVAC mode in

HVAC forced mode in

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application manual

KNX room temperature controller EK-EP2-TP

Conditions Values

disabled

/ enabled

Valve protection function = enabled

disabled

/ enabled

It enables the function that activates the drive for the valve control during periods of inactivity of the system.

Valve protection function = enabled once a day

once a week

once a month

10 s

[other values in the range 5 s … 20 min]

Conditions Dim. Flags DPT

Comm.

Obj.

No.

152 2 Byte CR-T-- [9.001] temperature (°C)

Thermostat function = both heating and cooling;

Heating

– cooling switchover = manual or automatic

1 Bit CR-T-- [1.100] heating/cooling 148

L’oggetto di comunicazione è trasmesso sul bus all’evento di commutazione elaborato internamente dal regolatore.

[1.100] DPT Heat/Cool 1 Bit

0 = Cool

1 = Heating

Thermostat function = both heating and cooling;

Heating

– cooling switchover = from bus

1 Bit C-W--- [1.100] heating/cooling 149

The communication object is received by the bus

. All’evento di commutazione i regolatori interni degli stadi primario e ausiliario (se abilitato) commutano il modo di conduzione. Il modo di conduzione attivo è segnalato dal l’apposito simbolo sul display.

1 Byte C-W--- [20.102] HVAC mode

The device receives the operating mode (HVAC mode) from a bus device with function of supervisor. The operating mode received through this communication object can be later modified by the user (in questo caso il termostato ambiente passa in controllo manuale).

150

1 Byte C-W--- [20.102] HVAC mode 151

L’oggetto di comunicazione permette di ricevere il modo operativo analogamente a quanto accade con l’oggetto di comunicazione Modo HVAC in; la differenza è che il modo operativo ricevuto tramite questo oggetto (ad eccezione del comando AUTO) non può essere successivamente modificato dall’utente. L’utente può modificare il modo solamente dopo che il

Modo HVAC forzato in ha inviato il comando AUTO.

Application Manual

Page 34

Application manual

KNX room temperature controller EK-EP2-TP

About the heating/cooling terminals

The application functions of the room temperature controller configurable with ETS are particularly suitable for the control through general-purpose or dedicated KNX actuators of the following heating/cooling terminals:

• radiators;

• elettrical heaters;

• fancoils;

• radiant panels;

• dehumidification units;

• radiant panels + radiators (as auxiliary system);

• radiant panels + fancoils (as auxiliary system);

• radiant panels + dehumidification units.

About the heating/cooling switchover

The switchover between the two seasonal modes (heating / cooling) may happens as follows:

1) manually on the device by the end user;

2) automatically by the device;

3) from the KNX bus through a dedicated communication object.

Manual switch-over (mode 1)

The manual switch-over is suitable for bus systems with one or a limited number of room temperature controllers. If the devices have been configured for this purpose, the user does the switch-over manually on the device (that acts as a "master" for the switch-over function); the device sends on the bus the output communication object [DPT 1.100 heat/cool] that switches possibly other room temperature controllers

("slave" devices) connected through a dedicated group address.

Automatic switch-over (mode 2)

The automatic switch-over is suitable for a 4-pipe hydraulic configuration of the heating/cooling installation

(used e.g. for fan-coil units or ceiling radianti panels). Also in this case the information can be sent on the bus with the output communication object [DPT 1.100 heat/cool]; the difference from the first mode is that switching is performed automatically on the basis of a comparison between the values of the actual temperature and the setpoint temperature. In this mode, the manual switching by the user is disabled.

The automatic switch-over is realised with the introduction of a neutral zone according to the scheme in the picture below.

OFF (protection)

ECONOMY STAND-BY COMFORT

32 °C

28 °C

26 °C

24 °C

Dead zone

20 °C

18 °C

16 °C

8 °C

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Neutral zone and example of setpoint values correctly distributed

Application Manual

Page 35

Application manual

KNX room temperature controller EK-EP2-TP

Until the actual (measured) temperature is located below the setpoint value for the heating, the operation is heating; in the same way, if the actual value (measured) is greater than the setpoint value for the cooling, the mode is cooling. If the actual value (measured) temperature is within the dead zone, the previous mode of operation remains active; the switching point of the operation mode for heating / cooling must take place in correspondence with the current setpoint for the active HVAC, in the same way the switching cooling / heating must take place at the setpoint for heating.

Switch-over via KNX bus (mode 3)

The switch-over from the bus requires that the command is received from another KNX device, e.g. another room temperature controller or a Touch&See unit configured to this purpose. The other device works in this way as a “supervisor” device: the switch-over is triggered by the input communication object [DPT 1.100 heat/cool]. In this mode the manual switch-over by an enduser is disabled. Thanks to this mode, the supervising device is able to control the “slave” devices with time-scheduled programs, extending their functionality to that of a chronothermostat (centrally controlled by the supervising device).

About the valve protection function

The function is suitable for heating and cooling systems that use water as thermal conveying fluid and are provided with motorized valves for the interception of a zone or of a single room. Long periods of inactivity of the system can lead to the blockage of valves: to prevent this, the room temperature controller may periodically send a command to open / close the valve in the period of inactivity of the system. This possibility is made available in the application program by means of the parameter "Valve protection function", further defined by the frequency and duration of the valve control.

7.8.2

Heating

The

Heating

folder includes the following parameters:

Comfort temp. setpoint [°C]

Standby temperature setpoint [°C]

Economy temp. setpoint [°C]

Building protection temp. setpoint [°C]

Heating type

Control type

Hysteresis

Cyclic sending interval

Min. change of value to send [%]

PWM cycle time

Proportional band [0,1 K]

Integral time [min]

Floor temperature limitation

Temperature limit [°C]

Hysteresis [K]

Auxiliary heating

Communication object

Disabled from bus

Offset from setpoint

Hysteresis

Cyclic sending interval

Ventilation for auxiliary heating

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 36

7.8.2.1

Parameter and communication object tables

Application manual

KNX room temperature controller EK-EP2-TP

Conditions:

Settings

Thermostat function = heating or both heating and cooling.

Parameter name Conditions

Comfort temp. setpoint [°C]

Standby temperature setpoint [°C]

Economy temp. setpoint [°C]

Values

21

[range

10 … 50]

18

[range

10 … 50]

For a correct operation of the device the standby temperature setpoint has to be < comfort temperature setpoint.

16

[range

10 … 50]

Building protection temp. setpoint [°C]

Heating type

Control type

Hysteresis

Cyclic sending interval

Min. change of value to send [%]

PWM cycle time

Proportional band [0,1 K]

For a correct operation of the device the economy temperature setpoint has to be < standby temperature setpoint.

7

[range

2 … 10]

radiators

elettric fan-coils floor radiant panels ceiling radiant panels

It defines the terminal used for the thermal exchange in the room. The choice affects the parameters of the PWM control algorithm (Proportional band and Integral time) and the control options.

2 point hysteresis

PWM (pulse width modulation) continuous

Control type = 2 point hysteresis

0,3 K

[other values in the range 0,2 K

… 3 K]

Control type = 2 point hysteresis, continuous

no sending

[other values in the range

30 s … 120 min]

Control type = continuous

10

[range

0 … 100]

Control type = PWM

15 min

[range 5

… 240 min]

Control type = continuous or PWM

*

[range 0

… 255]

The value is in tenths of Kelvin (K) degree.

*) The field contains a preset value that depend on the selected heating type (the value can be modified):

radiators: 50 ( 5 K)

elettric: 40 (4 K)

fan-coils: 40 (4 K)

floor radiant panels: 50 (5 K)

ceiling radiant panels: 50 (5 K)

The value of the parameter Proportional band represents the max difference between the setpoint temperature and the measured temperature that causes the max control output.

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 37

Parameter name

Integral time [min]

Floor temperature limitation

Temperature limit [°C]

Hysteresis [K]

Auxiliary heating

Communication object

Disabled from bus

Offset from setpoint

Hysteresis

Cyclic sending interval

Ventilation for auxiliary heating

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application manual

KNX room temperature controller EK-EP2-TP

Conditions

Control type = continuous or PWM

Values

*

[other values in the range 0

… 255 min]

*) The field contains a preset value that depend on the selected heating type (the value can be modified):

radiators: 150 min

elettric: 100 min

fan-coils: 90 min

floor radiant panels: 240 min

ceiling radiant panels: 180 min

Heating type = floor radiant panels,

Inputs

Input 1 or Input 2 = [AI] floor surface temperature sensor or

External sensors

Floor surface temperature sensor = enabled

disabled

/ enabled

Il parametro abilita la funzione di limitazione della temperatura superficiale di un pavimento riscaldante. Per la funzione è indispensabile misurare la temperatura superficiale del pavimento mediante l’abilitazione del sensore di temperatura corrispondente nella scheda Sensori esterni (dal bus) o nella scheda Ingressi.

Important!

This function does not replace the overtemperature protection usually installed in hydronic floor systems, realized with the proper safety thermostat.

Floor temperature limitation = enabled

29

[range 20

… 40]

According to EN 1264 a maximum allowed temperature is prescribed for the surface of a floor heating system:

T(sup) max ≤ 29°C per le zone di normale occupazione;

T(sup) max ≤ 35°C per le zone periferiche degli ambienti.

National standard may limit those temperatures to lower values. Per zone periferiche si intendono fasce situate generalmente lungo i muri dell’ambiente rivolti verso l’esterno dell’edificio con larghezza massima di 1 m.

Floor temperature limitation = enabled

0,3 K

[other values in the range

0,2 K … 3 K]

Before quitting from the alarm status, the device waits until the surface temperature decreases under the threshold set offset pari al valore di isteresi.

disabled

/ enabled

Auxiliary heating = enabled

separated

unique

Auxiliary heating = enabled

Auxiliary heating = enabled

no

/ yes

It enables the activation and deactivation of the function through a telegram sent on the bus by a supervising device.

0,6 K

[other values in the range

0 …3 K]

Auxiliary heating = enabled

0,3 K

[other values in the range

0,2 K … 3 K]

Auxiliary heating = enabled

no sending

[other values in the range 30 s

… 120 min]

Heating type = floor radiant panels or ceiling radiant panels

disabled

/ enabled

This option allows matching a system with high inertia as the floor radiant panels

(hydronic version) to a system with low inertia as the fan-coils.

Application Manual

Page 38

Application manual

KNX room temperature controller EK-EP2-TP

Object name

Comfort setpoint (heating)

Standby setpoint (heating)

Economy setpoint (heating)

Building protection setpoint

(heating)

Auxiliary heating output command

Conditions Dim. Flags DPT

Comm.

Obj.

No.

153

Heating out command

Auxiliary heating enable

Control type = 2 points hysteresis or

PWM

Control type = continuous

Auxiliary heating = enabled

Auxiliary heating = enabled,

Disabled from bus = yes

2 Byte

2 Byte

2 Byte

2 Byte

1 Bit

1 Byte

1 Bit

1 Bit

CRWTU-

CRWTU-

CRWTU-

CRWTU-

CR-T--

CR-T--

CR-T--

C-W---

[9.001] temperature (°C)

[9.001] temperature (°C)

[9.001] temperature (°C)

[9.001] temperature (°C)

[1.001] switch

[5.001] percentage (0..100%)

[1.001] switch

[1.003] enable

155

157

159

161

163

165

About the floor temperature limitation function

The floor heating system (warm water version) provides plastic pipes embedded in the concrete layer or placed directly under the final coating of the floor (light or "dry" system) filled by heated water. The water releases heat to the final coating that heats the room by radiation. The standard EN 1264 Floor heating (Part

3: Systems and components - Dimensioning) prescribes a maximum allowed temperature (T

Smax

) for the surface of the floor that is physiologically correct defined as:

T

Smax

≤ 29°C for zones of normal occupancy;

T

Smax

≤ 35°C for peripheral zones of the rooms.

National standards may also limit these temperatures at lower values. Peripheral zones are strips generally located along the external walls with a maximum width of 1 m.

The floor heating system (electrically powered version) involves the laying under the floor coating of an electric cable powered by the mains voltage (230 V) or low voltage (for example 12 or 45 V), possibly already prepared in the form of rolls with constant distance between sections of cable. The powered cable releases heat to the overlying coating that heats the room by radiation. The regulation is based on measurement of the temperature of the air mass, but generally requires the monitoring and limiting of the surface temperature by using a NTC-type sensor which is in contact with the floor surface.

The surface temperature limitation may be realized for several purposes:

 physiological compatibility (correct temperature at the height of the legs);

 when the system is used as auxiliary stage for heating. In this case, the heat losses to the exterior of the building are handled by the main heating stage, while the auxiliary stage only works to keep the floor temperature at a comfortable level (for example in bathrooms of residential buildings, sports centers , spas and thermal baths, etc.);

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 39

Application manual

KNX room temperature controller EK-EP2-TP

 protection against damages of the final coating due to an accidental overheating. Note that the warm water radiant panels are usually already equipped with a safety thermostat (with intervention on the hydraulic mixing group), while in the case of electrical power this device is not usable and it is common practice to realize a temperature limitation with a surface temperature sensor connected to the device.

7.8.3

Cooling

The

Cooling

folder includes the following parameters:

Comfort temp. setpoint [°C]

Standby temperature setpoint [°C]

Economy temp. setpoint [°C]

Building protection temp. setpoint [°C]

Cooling type

Control type

Hysteresis

Cyclic sending interval

Min. change of value to send [%]

PWM cycle time

Proportional band [0,1 K]

Integral time [min]

Anticondensation with probe

Auxiliary cooling

Disabled from bus

Offset from setpoint

Hysteresis

Cyclic sending interval

Ventilation for auxiliary cooling

Conditions: Temperature control

Settings

Thermostat function = cooling or both heating and cooling.

7.8.3.1

Parameter and communication object tables

Parameter name

Comfort temp. setpoint [°C]

Standby temperature setpoint [°C]

Economy temp. setpoint [°C]

Building protection temp. setpoint [°C]

Conditions Values

23

[range

10 … 50]

26

[range

10 … 50]

For a correct operation of the device the standby temperature setpoint has to be > comfort temperature setpoint.

28

[range

10 … 50]

For a correct operation of the device the standby temperature setpoint has to be > economy temperature setpoint.

36

[range

30 … 50]

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 40

Parameter name

Cooling type

Control type

Hysteresis

Cyclic sending interval

Min. change of value to send [%]

PWM cycle time

Proportional band [0,1 K]

Integral time [min]

Anticondensation with probe

Auxiliary cooling

Application manual

KNX room temperature controller EK-EP2-TP

Conditions Values

fan-coils floor radiant panels ceiling radiant panels

If in Settings the parameter Thermostat function = both heating and cooling and

Command communication object = unique, the parameter Cooling type is bound to the choice done for Heating.

Command communication object = separated

2 point hysteresis

PWM (pulse width modulation) continuous

If in Settings the parameter Thermostat function = both heating and cooling and

Command communication object = unique, the parameter Control type is bound to the choice done for Heating.

Control type = 2 point hysteresis

0,3 K

[other values in the range

0,2 K … 3 K]

Control type = 2 point hysteresis or continuous

no sending

[other values in the range

30 s … 120 min]

Control type = continuous

10

[range 0

… 100]

Control type = PWM (pulsa width modulation)

15 min

[range 5

… 240 min]

Control type = continuous or PWM

*

[range 0

… 255]

The value is in tenths of Kelvin (K) degree.

*) The field contains a preset value that depend on the selected cooling type (the value can be modified):

fan-coils: 40 (4 K)

floor radiant panels: 50 (5 K)

ceiling radiant panels: 50 (5 K)

The value of the parameter Proportional band represents the max difference between the setpoint temperature and the measured temperature that causes the max control output.

Control type = continuous or PWM

*

[range 0

… 255 min]

*) The field contains a preset value that depend on the selected cooling type (the value can be modified):

fan-coils: 90 min

floor radiant panels: 240 min

ceiling radiant panels: 180 min

Cooling type = floor radiant panels or ceiling radiant panels,

Inputs

Input 1 or Input 2 = [DI] anticondensation sensor or

External sensors (from bus)

Anticondensation = enabled

disabled

/ enabled

disabled

/ enabled

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 41

Parameter name

Disabled from bus

Offset from setpoint

Hysteresis

Cyclic sending interval

Ventilation for auxiliary cooling

Application manual

KNX room temperature controller EK-EP2-TP

Conditions

Auxiliary cooling = enabled

Values

Auxiliary cooling = enabled

no

/ yes

This parameter enables the activation and deactivation of the function through a telegram from a bus device with supervising function.

0,2 K /

0,3 K

/ 0,4 K / 0,5 / 0,6 K

0,8 K / 1 K / 1,5 K / 2 K / 2,5 K / 3 K

Auxiliary cooling = enabled

0,2 K /

0,3 K

/ 0,4 K / 0,5 / 0,6 K

0,8 K / 1 K / 1,5 K / 2 K / 2,5 K / 3 K

Auxiliary cooling = enabled

00:00:00 means that the cyclic sending is not enabled.

Cooling type = floor radiant panels or ceiling radiant panels hh:mm:ss (

disabled

00:00:00

/ enabled

)

This option allows combining a high-inertial system as the floor radiant panels to a lowinertial one as the fan-coils.

Object name

Comfort setpoint (cooling)

Standby setpoint (cooling)

Economy setpoint (cooling)

Building protection setpoint

(cooling)

Auxiliary cooling output command

Conditions Dim. Flags DPT

Comm.

Obj.

No.

154

Cooling out command

Auxiliary cooling enable

Anticondensation alarm

Control type = 2 point hysteresis or

PWM

Control type = continuous

Auxiliary cooling = enabled

Auxiliary cooling = enabled,

Disabled from bus = yes

At least one anticondensation protection enabled

2 Byte

2 Byte

2 Byte

2 Byte

1 Bit

1 Byte

1 Bit

1 Bit

1 Bit

CRWTU-

CRWTU-

CRWTU-

CRWTU-

CR-T--

CR-T--

CR-T--

C-W---

CR-T--

[9.001] temperature (°C)

[9.001] temperature (°C)

[9.001] temperature (°C)

[9.001] temperature (°C)

[1.001] switch

[5.001] percentage (0..100%)

[1.001] switch

[1.003] enable

[1.005] alarm

156

158

160

162

164

166

188

About the anticondensation protection function

The objective of this function is to prevent the condensation on the thermal exchange surfaces of the installation or building when cooling is working. This function is mainly used in systems with thermal exchange consisting in surface terminals such as for the floor and ceiling cooling radiant systems. In this case the hydraulic circuits contain refrigerated water; usually the latent loads (due to the increase of air

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 42

Application manual

KNX room temperature controller EK-EP2-TP

humidity in the room) are handled by air-conditioning units and the temperature and humidity conditions are far from those that could cause condensation. If this is not done in a satisfactory manner, or in case of stop of the air-conditioning units, it is necessary to provide additional safety measures to prevent or restrict the accidental formation of condensation on cold surfaces.

If an anticondensation sensor is used, it is necessary use a device provided with a potential-free signalling contact. The following options are available:

 the connection of the signalling contact to an input of the room temperature controller configured as digital (Inputs

Input 1 or Input 2 = [DI] anticondensation sensor). The signal coming from the sensor is received and processed directly by the room temperature controller (case 1a of the table);

 the connection of the signalling contact to an input channel of another KNX device, e.g. a pushbutton interface or a binary input (External sensors (from bus)

Anticondensation sensor = enabled). In this case the signal of the sensor is transmitted to the room temperature controller through the status of a communication object (case 1b of the table).

7.8.4

Main and auxiliary ventilation

The

Ventilation

folder includes the following parameters:

Control type

Threshold first speed [0,1 K]

Threshold second speed [0,1 K]

Threshold third speed [0,1 K]

Speed control hysteresis [K]

Proportional band [0,1 K]

Minimo cambiamento valore da inviare [%]

Manual operation

Hot start

Min. temp.to start ventilation [°C]

Antistratification function

Antistratification temp. differential

Hysteresis

Disable ventilation from bus

Signal from bus

Fan start delay

Fan stop delay

The conditions for the appearance of the

Ventilation

folder are:

Heating

Type of heating = fan-coils or Type of cooling = fan-coils or a combination of the two conditions:

Heating

Type of heating = floor radiant panels or ceiling radiant panels and

Heating

Ventilation

Auxiliary heating = enabled

Cooling

Type of cooling = floor radiant panels or ceiling radiant panels and

Cooling

Ventilation for auxiliary = enabled

This way two types of installations can be controlled: i) fan-coil terminals or ii) radiant panels as main stage and fan-coil terminals as auxiliary stage.

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 43

7.8.4.1

Parameter and communication object tables

Parameter name

Control type

Threshold first speed [0,1 K]

Threshold second speed [0,1 K]

Threshold third speed [0,1 K]

Speed control hysteresis [K]

Proportional band [0,1 K]

Minimo cambiamento valore da inviare [%]

Manual operation

Hot start

Application manual

KNX room temperature controller EK-EP2-TP

Conditions Values

1 speed

2 speeds

3 speeds continuous regulation

10

[range 0

… 255]

The value is represented in tenths of Kelvin degrees. If the parameter Thermostat function = both heating and cooling, the threshold value is valid for both seasonal modes.

Control type = 2 speeds

20

[range

0 … 255]

The value is represented in tenths of Kelvin degrees. If the parameter Thermostat function = both heating and cooling, the threshold value is valid for both seasonal modes. For a correct operation of the ventilation, Threshold second speed > Threshold first speed.

Control type = 3 speeds

30

[range

0 … 255]

The value is represented in tenths of Kelvin degrees. If the parameter Thermostat function = both heating and cooling, the threshold value is valid for both seasonal modes. For a correct operation of the ventilation, Threshold third speed > Threshold second speed.

Control type = 1, 2 or 3 speeds

0,3 K

[other values in the range 0,2 K

…3 K]

Control type = continuous regulation

30

[range

0 … 255]

The value is represented in tenths of Kelvin degrees. If the parameter Thermostat function = both heating and cooling, the threshold value is valid for both seasonal modes.

Control type = continuous regulation

10

[range

2 … 40]

not depending on the temperature

depending on the temperature

If the parameter = not depending on the temperature, the fan speed set by the user is not changed even when the temperature setpoint is reached; if the parameter = depending on the temperature, the fan stops when the temperature setpoint is reached.

Thermostat function = both heating and cooling,

Inputs

Input X

[AI] coil battery temperature sensor or

External sensors (from bus)

 coil temperature = enabled

no

/ yes

For carrying out the function must be enabled a sensor for measuring the temperature of the heat exchanger of the fan coil. To this purpose either an input (configured as analog) or an external sensor (from bus) can be used.

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 44

Parameter name

Min. temp.to start ventilation [°C]

Object name

Application manual

KNX room temperature controller EK-EP2-TP

Antistratification function

Antistratification temp. differential

Hysteresis

Disable ventilation from bus

Signal from bus

Fan start delay

Fan stop delay

Fan continuous speed

Fan speed 1

Conditions

Hot start = yes

Values

35

[range

28 …40]

If enabled, the function is active only in heating mode.

Inputs

Input X = [AI] antistratification temperature sensor or

External sensors (from bus)

Antistratification temperature = enabled

disabled

/ enabled

For carrying out the function at least a sensor for measuring a second temperature value must be enabled at a different height than that of the room temperature controller. To this purpose either an input (configured as analog) or an external sensor (from bus) can be used.

Antistratification function = enabled

2 [K/m]

[other values in the range 0,25 …

4,00 K/m]

The DIN 1946 recommends a max temperature gradient of 2 K/m for rooms with standard height (between 2,70 and 3 m).

Antistratification function = enabled

0,5 K

[other values in the range

0,2 … 3

K]

no

/ yes

Disable ventilation from bus = yes

not inverted

inverted

0 s

[other values in the range 10 s

12 min]

It appears also if the hot-start function is active (through measuring of the conveying fluid temperature at the battery for the thermal exchange). The function is active in both seasonal modes (heating and cooling).

0 s

[other values in the range

10 s …

12 min]

The function allows prolonging the operation of the ventilator, dissipating in the room the residual heat or cool present in battery for the thermal exchange. The function is active in both seasonal modes

(heating and cooling).

Conditions

Control type = continuous regulation

Control type = 1, 2 o 3 speeds

Dim.

1 Byte CR-T--

1 Bit

Flags

CR-T--

DPT

[5.001] percentage (0..100%)

Comm.

Obj.

No.

167

[1.001] switch 168

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 45

Application manual

KNX room temperature controller EK-EP2-TP

Object name Conditions Dim. Flags DPT

Comm.

Obj.

No.

169 Fan speed 2

Fan speed 3

Fan control disable

Control type = 2 or

3 speeds

Control type = 3 speeds

Disable ventilation from bus = yes

1 Bit

1 Bit

1 Bit

CR-T--

CR-T--

C-W---

[1.001] switch

[1.001] switch

[1.002] boolean

170

172

About the delayed fan start (“hot-start”)

This function is used in case the fan forces in the room air passing through a heat exchange coil (as in the case of the terminals to the fan-coil). In the heating mode of operation, to avoid possible discomfort caused by the dispatch of cold air in the room, the room temperature controller does not start the fan until the fluid has not reached a sufficiently high temperature. This situation normally occurs at the first start or after long periods of inactivity. The function can be carried out by:

1. a temperature control (through a temperature sensor on the coil exchange battery);

2. a delayed start (function approximated);

In the first case the temperature of the heat conveying fluid is acquired at the exchange battery. The function then has an effective temperature control, but for the execution is necessary that:

 the heat exchange coil is equipped with a sensor of minimum water temperature that acquires the temperature of the heat conveying fluid;

 the sensor is connected to an input of the room temperature controller (configured as analog) or to another KNX device with an analog input .

In the second case just sets a time delay starting from the flow request; there is no temperature control. The effectiveness of the function depends on a field measurement of the time actually required to have sufficiently warm air from the terminal.

About the antistratification function

This function is used in the case of heating systems with thermal exchange of convective type for rooms with height and volume much higher than usual (atriums, fitness facility, commercial buildings, etc.). Because of the natural convection - with warm air rising to the highest altitudes of the room - the phenomenon of air stratification occurs, with energy waste and discomfort for the occupants at the same time. The function opposes to the air stratification, forcing the warm air downwards.

The antistratification function requires:

 rooms of great height;

 availability of ventilation devices able to force the air movement downwards (opposed to the natural convective movement of warm air);

 measuring of the temperature at two heights through the installation of a second temperature sensor at an adequate height in order to measure the actual air stratification (the main room temperature controller is supposed to be installed at 1.5 m).

For rooms with ordinary height (2,70÷3,00 m) the DIN 1946 standard recommends not to exceed 2 K/m in order to have an adequate comfort; this gradient may be bigger in higher rooms.

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 46

Application manual

KNX room temperature controller EK-EP2-TP

About the 2-stage configuration with fan-coils as auxiliary stage

The fan-coil units may be used both as a main stage and secondary stage. As main stage they can be combined only to radiators as auxiliary stage. If, however, the main stage is done with (floor or ceiling) radiant panels, the fan-coils can be used as auxiliary stage. In the latter case they work in automatic mode with a configurable offset with respect to the temperature setpoint for the main stage, and then carry out their compensation function while the main stage is brought in temperature with bigger inertia.

The

Ventilation

folder, that is unique, configures a main or a auxiliary stage depending on the settings choosed in the

Heating

and

Cooling

folders. Similarly, the display interface will act on manual / automatic and manual forcing of the only fan-coil.

A particular case occurs when a fan-coil unit works in a season as auxiliary stage and in the other one as main stage. It is for example the case of:

 a radiant panels system that works only for heating and has a fan-coil as auxiliary stage; the same fan-coil works as main stage for cooling;

 a radiator system that has a fan-coil as auxiliary stage for heating; the same fan coil unit functions as main stage for cooling.

In these cases with the configuration adopted, the following steps are necessary:

1.

Settings

Thermostat function = both heating and cooling. This configuration enables both folders

(heating and cooling)

2.

Heating

Heating type = floor radiant panels or ceiling radiant panels

3.

Heating

Command communication object = separated (if unique is choosen, the parameter Cooling

Cooling type does not appear)

4.

Heating

Auxiliary heating = enabled

5.

Auxiliary heating

Communication object = separated

6.

Heating

Ventilation for auxiliary heating = enabled

7.

Cooling

Cooling type = fancoils

Important!

If the fan-coil system has a 2-pipe hydraulic configuration, the objects 163 Auxiliary heating output command (1 bit) and 162 Cooling out command (1 byte) have to be set in logical OR in the actuator for controlling the fan-coil which in this case is unique.

An alternative solution that avoids the setting of a logic OR can be realized by configuring a main stage for heating and cooling with radiant panels through separate valves and an auxiliary stage for heating and cooling fan coil through combined valves. The offset of the auxialiary stage for cooling is set to the value 0

(zero); this corresponds to a configuration for main stage. The object 162 Cooling out command (1 byte) is not connected so that the radiant panel system works only for heating.

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 47

7.8.5

Scenes

Application manual

KNX room temperature controller EK-EP2-TP

The folder allows the scenes configuration (up to 8), assigning to each one an identification number and the operating mode to be activated when recalled (e.g. with an ekinex pushbutton or another KNX device with this function). If

Learning mode = enabled

, receiving a telegram of scene storage determines the association of the scene to the operating mode currently set on the device.

Important!

Be careful setting the

Download overwrite

parameter. The download of the application program, particularly after the first commissioning of the system, may cause the loss of the already stored scenes.

The

Scenes

folder includes the following parameters:

Download overwrite

Scene X

Scene number

HVAC mode

Activation delay

Learning mode

Condition:

Temperature control

Settings

Scenes = enabled.

7.8.5.1

Parameter and communication object tables

Parameter name

Download overwrite

Scene X

Scene number

HVAC mode

Activation delay

Learning mode

Conditions Values

disabled

/ enabled

If Overwrite download = disabled: at the download of the application on the device, the operating modes previously stored are not overwritten.

If Overwrite download = enabled: at the download of the application on the device, the operating modes previously stored are reprogrammed with the values selected from the HVAC mode parameter.

disabled

/ enabled

This parameter enables the scene X

(X = 1, 2, … 8).

Scene X = enabled

1

[range

1 … 64]

Scene X = enabled auto /

comfort

/ standby / economy / building protection

This parameter defines the operating mode of the scene X.

Scene X = enabled hh:mm:ss (

00:00:00

)

Receiving a telegram that recalls a scene, once elapsed the time interval set in the Activation delay parameter, the programmed operating mode is activated.

Scene X = enabled

disabled

/ enabled

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 48

Object name

HVAC scene number

Application manual

KNX room temperature controller EK-EP2-TP

Conditions Dim. Flags DPT

Comm. Obj.

No.

1 Byte C-W---

[17.001] scene number

[18.001] scene control

173

It stores or recalls a scenario. The six least significant bits (0 to 5) in the byte of the code represent the number of the scene, while the most significant bit (7) is the operation code (1 = stores, 0 = recalls).

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 49

Application manual

KNX room temperature controller EK-EP2-TP

7.9

Energy saving

In order to realise energy-saving functions, window contacts (to detect the opening of windows or doors), presence and movement sensors and card holders can be used.

The

Energy saving

folder includes the following secondary folders:

Window contacts

Presence sensors

Card holder

7.9.1

Window contacts

The

Window contacts

secondary folder appears if at least a sensor dedicated to this function is enabled i.e. if at least one of the two conditions is verified:

1)

Inputs

Input 1 and/or Input 2 = [DI] windows contact sensor

2)

External sensors (from bus)

Windows contact sensor 1 or 2 (from bus) = enabled

For the function can be acquired up to four signals which are combined as a logic OR.

The

Window contacts

folder includes the following parameters:

Window contacts function

Wait time to building protection mode

7.9.1.1

Parameter and communication object tables

Parameter name

Window contacts function

Wait time to building protection mode

Conditions Values

disabled

/ enabled

This parameter enables the window contact function.

Window contacts function = enabled

00:01:00 hh:mm:ss

[range

00:00:00 … 18:12:15]

Time interval before the automatic switching of the device to the Building protection operating mode.

Object name Conditions Dim. Flags DPT

Comm.

Obj. No.

Window contact sensor (from input 1)

Window contacts function = enabled,

Input 1 = [DI] windows contact sensor

1 Bit CR-T-

[1.019] window/door

126

Window contact sensor (from input 2)

Window contacts function = enabled,

Input 2 = [DI] windows contact sensor

1 Bit CR-T-

[1.019] window/door

127

Windows contact sensor 1

(from bus)

Window contacts function = enabled,

Window contact 1 = enabled

1 Bit C-W--

[1.019] window/door

143

Windows contact sensor 2

(from bus)

Window contacts function = enabled,

Window contact 2 = enabled

1 Bit C-W--

[1.019] window/door

144

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 50

7.9.2

Presence sensors

Application manual

KNX room temperature controller EK-EP2-TP

The

Presence sensors

folder includes the following parameters:

Presence sensor function

Presence sensors use

Thermostat modes

Absence time to switch HVAC mode

For this function only use external sensors (from bus) can be used, such as the ekinex EK-SM2-TP movement sensor or the ekinex EK-DX2-TP (X = B, C, D, E) presence sensor. The following condition has to be true:

External sensors (from bus)

Presence sensor 1 (from bus) or Presence sensor 2 (from bus) = enabled

7.9.2.1

Parameter and communication object tables

Parameter name

Presence sensor function

Presence sensors use

Thermostat modes

Absence time to switch HVAC mode

Conditions

Parameter that enables the presence sensor function.

Values

disabled

/ enabled

Presence sensor function = enabled

comfort extension

comfort limitation comfort extension and comfort limitation

Presence sensor function = enabled,

Presence sensors use = comfort extension and comfort limitation or = comfort limitation

comfort-standby

comfort-economy

Presence sensor function = enabled

00:01:00 hh:mm:ss

[range

00:00:00 … 18:12:15]

Time interval before the automatic switching of the operating mode set in the

Thermostat modes parameter.

Object name Conditions Dim. Flags DPT

Comm.

Obj. No.

Presence sensor 1 (from bus)

Presence sensor function= enabled

1 Bit C-W---

[1.018] occupancy

132

Presence sensor 2 (from bus)

Presence sensor function = enabled

1 Bit C-W---

[1.018] occupancy

133

7.9.3

Card holder

The

Card holder

secondary folder appears only if the corresponding sensor is enabled i.e. if one of the two mutually esclusive conditions is true:

1)

Inputs

Input1 or Input 2 = [DI] card holder contact sensor or

2)

External sensors (from bus)

Card holder contact = enabled

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 51

The

Card holder

folder includes the following parameters:

Card holder function

On card insertion switch HVAC mode to

Activation delay on card insertion

On card removal switch HVAC mode to

Activation delay on card removal

Application manual

KNX room temperature controller EK-EP2-TP

7.9.3.1

Parameter and communication object tables

Parameter name

Card holder function

On card insertion switch HVAC mode to

Activation delay on card insertion

On card removal switch HVAC mode to

Activation delay on card removal

Conditions Values

disabled

/ enabled

Parameter that enables the card holder function.

Card holder function = enabled none

comfort

standby economy

This parameter defines to which operating mode the device should automatically switch inserting the card in the holder.

Card holder function = enabled

00:00:00 hh:mm:ss

[range

00:00:00 … 18:12:15]

Time interval before the automatic switching of the operating mode, inserting the card in the holder.

Card holder function = enabled none

standby

economy building protection

This parameter defines to which operating mode the device should automatically switch removing the card from the holder.

Card holder function = enabled

00:00:00 hh:mm:ss

[range

00:00:00 … 18:12:15]

Time interval before the automatic switching of the operating mode, removing the card from the holder.

Object name

Card holder contact sensor

(from input 1)

Card holder contact sensor

(from input 2)

Conditions

Card holder function = enabled

Card holder function = enabled

Dim.

1 Bit

1 Bit

Flags

CR-T--

CR-T--

DPT

[1.001] switch

[1.001] switch

Comm.

Obj. No.

130

131

About the card holder function

The information of card insertion (removal) in (from) a card holder allows you to directly control the temperature by means of the room thermostat, while sending the object value on the bus allows you to control other room functions with KNX (lighting, electrical loads, feedback status for the hotel reception, etc.) depending on the configuration done with ETS. The value of the setpoint temperature and the switching have to be defined with the hotel responsible in accordance with the target of energy saving and level of service to be offered to the guests.

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 52

Application manual

KNX room temperature controller EK-EP2-TP

Conventional (not KNX) card holder

With a conventional card holder the status (card present or absent) of a signal contact is detected through an input of the device configured as

[DI] card holder contact sensor

. This way you can detect only the insertion and extraction of the card, but it cannot be detected e.g. the access of users with different profiles (guests, service staff, maintenance workforce).

KNX card holder

With a KNX card holder you can differentiate the switching to be carried out; this is not resolved by the parameters of the room temperature controller, but through the definition of scenes that are received by the device. Depending on the available device, advanced functions are possible (e.g. different user profiles).

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 53

8

List of communication objects

Nr. Name

0 Technical alarm

1 Brightness value

2 Leds intensity percentage

3 Temperature value

20 Light threshold 1 - Switch

37 Light threshold 2 - Switch

38 Rocker 1 - Led first color A

39 Rocker 1 - Led second color A

40 Rocker 1 - Led first color B

41 Rocker 1 - Led second color B

76 Rocker 2 - Led first color A

77 Rocker 2 - Led second color A

78 Rocker 2 - Led first color B

79 Rocker 2 - Led second color B

116 Temperature threshold 1 - Switch

117 Temperature threshold 2 - Switch

120 Coil battery temperature sensor (from input 1)

120 Room temperature sensor (from input 1)

120 Antistratification temperature sensor (from input 1)

120 Floor surface temperature sensor (from input 1)

120 Outdoor temperature sensor (from input 1)

120 Temperature value sensor (from input 1)

121 Temperature threshold 1 sensor 1 - Switch

122 Temperature threshold 2 sensor 1 - Switch

123 Coil battery temperature sensor (from input 2)

123 Room temperature sensor (from input 2)

123 Antistratification temperature sensor (from input 2)

123 Floor surface temperature sensor (from input 2)

123 Outdoor temperature sensor (from input 2)

123 Temperature value sensor (from input 2)

124 Temperature threshold 1 sensor 2 - Switch

125 Temperature threshold 2 sensor 2 - Switch

126 Window contact sensor (from input 1)

127 Window contact sensor (from input 2)

128 Anticondensation sensor (from input 1)

129 Anticondensation sensor (from input 2)

130 Card holder contact sensor (from input 1)

131 Card holder contact sensor (from input 2)

132 Presence sensor 1 (from bus)

133 Presence sensor 2 (from bus)

134 Room temperature (from bus)

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application manual

KNX room temperature controller EK-EP2-TP

1 Bit

1 Bit

2 Bytes

2 Bytes

2 Bytes

2 Bytes

2 Bytes

2 Bytes

1 Bit

1 Bit

2 Bytes

2 Bytes

2 Bytes

2 Bytes

2 Bytes

2 Bytes

1 Bit

1 Bit

1 Bit

1 Bit

1 Bit

1 Bit

1 Bit

1 Bit

Size

1 Bit

2 Bytes

1 Byte

2 Bytes

1 Bit

1 Bit

1 Bit

1 Bit

1 Bit

1 Bit

1 Bit

1 Bit

1 Bit

1 Bit

1 Bit

1 Bit

2 Bytes

Flags Datapoint Type

-

WC--- [1.5] DPT_Alarm

R-CT-- [9.4] DPT_Value_Lux

-

WC--- [5.1] DPT_Scaling

R-CT-- [9.1] DPT_Value_Temp

R-CT-- [1.1] DPT_Switch

R-CT-- [1.1] DPT_Switch

RWCTU- [1.1] DPT_Switch

RWCTU- [1.1] DPT_Switch

RWCTU- [1.1] DPT_Switch

RWCTU- [1.1] DPT_Switch

RWCTU- [1.1] DPT_Switch

RWCTU- [1.1] DPT_Switch

RWCTU- [1.1] DPT_Switch

RWCTU- [1.1] DPT_Switch

R-CT-- [1.1] DPT_Switch

R-CT-- [1.1] DPT_Switch

R-CT-- [9.1] DPT_Value_Temp

R-CT-- [9.1] DPT_Value_Temp

R-CT-- [9.1] DPT_Value_Temp

R-CT-- [9.1] DPT_Value_Temp

R-CT-- [9.1] DPT_Value_Temp

R-CT-- [9.1] DPT_Value_Temp

R-CT-- [1.1] DPT_Switch

R-CT-- [1.1] DPT_Switch

R-CT-- [9.1] DPT_Value_Temp

R-CT-- [9.1] DPT_Value_Temp

R-CT-- [9.1] DPT_Value_Temp

R-CT-- [9.1] DPT_Value_Temp

R-CT-- [9.1] DPT_Value_Temp

R-CT-- [9.1] DPT_Value_Temp

R-CT-- [1.1] DPT_Switch

R-CT-- [1.1] DPT_Switch

R-CT-- [1.19] DPT_Window_Door

R-CT-- [1.19] DPT_Window_Door

R-CT-- [1.5] DPT_Alarm

R-CT-- [1.5] DPT_Alarm

R-CT-- [1.18] DPT_Occupancy

R-CT-- [1.18] DPT_Occupancy

-

WC--- [1.18] DPT_Occupancy

-

WC--- [1.18] DPT_Occupancy

-

WC--- [9.1] DPT_Value_Temp

Application Manual

Page 54

Nr. Name

137 Antistratification temperature (from bus)

138 Outdoor temperature (from bus)

140 Coil temperature (from bus)

143 Windows contact sensor 1 (from bus)

144 Windows contact sensor 2 (from bus)

145 Contact of card holder (from bus)

146 Anticondensation (from bus)

147 Weighted temperature

148 Heating/cooling status out

149 Heating/cooling status in

150 HVAC mode in

151 HVAC forced mode in

152 Actual setpoint

153 Comfort setpoint (heating)

154 Comfort setpoint (cooling)

155 Standby setpoint (heating)

156 Standby setpoint (cooling)

157 Economy setpoint (heating)

158 Economy setpoint (cooling)

159 Building protection setpoint (heating)

160 Building protection setpoint (cooling)

161 Heating out command

161 Heating out command

161 Heating and cooling out command

161 Heating and cooling out command

162 Cooling out command

162 Cooling out command

163 Auxiliary heating output command

163 Auxiliary heating and cooling output command

164 Auxiliary cooling output command

165 Auxiliary heating enable

166 Auxiliary cooling enable

167 Fan continuous speed

168 Fan speed 1

169 Fan speed 2

170 Fan speed 3

172 Fan control disable

173 HVAC scene number

173 HVAC scene number

179 HVAC mode out

186 Temperature setpoint change lock

187 Manual mode lock

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application manual

KNX room temperature controller EK-EP2-TP

1 Bit

1 Bit

1 Byte

1 Byte

1 Bit

1 Bit

1 Bit

1 Bit

2 Bytes

2 Bytes

2 Bytes

2 Bytes

2 Bytes

2 Bytes

1 Byte

2 Bytes

1 Bit

1 Bit

1 Byte

1 Byte

2 Bytes

2 Bytes

2 Bytes

Size

2 Bytes

2 Bytes

2 Bytes

1 Bit

1 Bit

1 Bit

1 Bit

1 Bit

1 Bit

1 Byte

1 Bit

1 Bit

1 Bit

1 Bit

1 Byte

1 Byte

1 Byte

1 Bit

1 Bit

Flags Datapoint Type

-

WC--- [9.1] DPT_Value_Temp

-

WC--- [9.1] DPT_Value_Temp

-

WC--- [9.1] DPT_Value_Temp

-

WC--- [1.19] DPT_Window_Door

-

WC--- [1.19] DPT_Window_Door

-

WC--- [1.18] DPT_Occupancy

-

WC--- [1.1] DPT_Switch

R-CT-- [9.1] DPT_Value_Temp

R-CT-- [1.100] DPT_Heat_Cool

-

WC--- [1.100] DPT_Heat_Cool

-

WC--- [20.102] DPT_HVACMode

-

WC--- [20.102] DPT_HVACMode

R-CT-- [9.1] DPT_Value_Temp

RWCTU- [9.1] DPT_Value_Temp

RWCTU- [9.1] DPT_Value_Temp

RWCTU- [9.1] DPT_Value_Temp

RWCTU- [9.1] DPT_Value_Temp

RWCTU- [9.1] DPT_Value_Temp

RWCTU- [9.1] DPT_Value_Temp

RWCTU- [9.1] DPT_Value_Temp

RWCTU- [9.1] DPT_Value_Temp

R-CT-- [5.1] DPT_Scaling

R-CT-- [1.1] DPT_Switch

R-CT-- [1.1] DPT_Switch

R-CT-- [5.1] DPT_Scaling

R-CT-- [5.1] DPT_Scaling

R-CT-- [1.1] DPT_Switch

R-CT-- [1.1] DPT_Switch

R-CT-- [1.1] DPT_Switch

R-CT-- [1.1] DPT_Switch

-

WC--- [1.3] DPT_Enable

-

WC--- [1.3] DPT_Enable

R-CT-- [5.1] DPT_Scaling

R-CT-- [1.1] DPT_Switch

R-CT-- [1.1] DPT_Switch

R-CT-- [1.1] DPT_Switch

-

WC--- [1.2] DPT_Bool

-

WC--- [17.1] DPT_SceneNumber

-

WC--- [18.1] DPT_SceneControl

R-CT-- [20.102] DPT_HVACMode

-

WC--- [1.3] DPT_Enable

-

WC--- [1.3] DPT_Enable

Application Manual

Page 55

Nr. Name

188 Anticondensation alarm

189 Rockers lock

190 Ventilation manual operation

191 Thermal generator lock

Application manual

KNX room temperature controller EK-EP2-TP

Size

1 Bit

1 Bit

1 Bit

1 Bit

Flags Datapoint Type

R-CT-- [1.5] DPT_Alarm

-

WC--- [1.2] DPT_Bool

R-CT-- [1.11] DPT_State

-

WC--- [1.5] DPT_Alarm

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 56

9

Diagnostics

E25

E26

E27

E28

E29

E33

E34

E16

E17

E18

E19

E22

E23

E24

E02

E06

E07

E08

E09

E10

E11

E14

E15

Alarm code

A01

A02

A03

Error code

E00

E01

E43

E44

E45

E46

F01

F02

F03

F04

E35

E36

E37

E38

E39

E40

E41

E42

Application manual

KNX room temperature controller EK-EP2-TP

Cause

Surface temperature limit is exceeded

Formation of condensation

Thermal generator lock

Cause

Integrated temperature sensor fault

Integrated relative humidity sensor fault

Integrated brightness sensor fault

Analogic input 1: NTC sensor fault

Analogic input 1: room temperature sensor fault

Analogic input 1: fan-coil temperature sensor fault

Analogic input 1: surface temperature sensor fault

Analogic input 1: external temperature sensor fault

Analogic input 1: antistratification sensor fault

Analogic input 2: NTC sensor fault

Analogic input 2: room temperature sensor fault

Analogic input 2: fan-coil temperature sensor fault

Analogic input 2: surface temperature sensor fault

Analogic input 2: external temperature sensor fault

Analogic input 2: antistratification sensor fault

CO: quality air sensor fault

CO: external temperature sensor fault

CO: room temperature sensor fault

CO: fan-coil temperature sensor fault

CO: surface temperature sensor fault

CO: flow temperature sensor fault

CO: relative humidity sensor fault

CO: antistratification temperature sensor fault

CO: quality air sensor timeout

CO: external temperature sensor timeout

CO: room temperature sensor timeout

CO: fan-coil temperature sensor timeout

CO: surface temperature sensor timeout

CO: flow temperature sensor timeout

CO: relative humidity sensor timeout

CO: antistratification temperature sensor timeout

CO: anticondensation sensor timeout

CO: window contact 1 timeout

CO: window contact 2 timeout

CO: presence sensor 1 timeout

CO: presence sensor 2 timeout

CO: card holder contact timeout

CO: Alarm 1 from bus

CO: Alarm 2 from bus

CO: Alarm 3 from bus

CO: Alarm 4 from bus

Table of alarm and error displayable codes.

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 57

10

Warnings

Application manual

KNX room temperature controller EK-EP2-TP

• Installation, electrical connection, configuration and commissioning of the device can only be carried outby qualified personnel in compliance with the applicable technical standards and laws of the respective countries

• Opening the housing of the device causes the immediate end of the warranty period

• In case of tampering, the compliance with the essential requirements of the applicable directives, for which the device has been certified, is no longer guaranteed

• ekinex

®

KNX defective devices must be returned to the manufacturer at the following address: SBSS.p.A.

Via Circonvallazione s/n, I-28010 Miasino (NO) Italy

11

Other information

• The instruction sheet must be delivered to the end customer with the project documentation

• For further information on the product, please contactthe ekinex

®

technical support at the e-mail address: [email protected] or visit the website www.ekinex.com

• Each ekinex

®

device has a unique serial number onthe label. The serial number can be used by installersor system integrators for documentation purposes and has to be added in each communication addressed to the SBS technical support in case of malfunctioning of the device

• ekinex

• KNX

®

®

is a registered trademark of SBS S.p.A.

and ETS

®

are registered trademarks of KNX Association cvba, Brussels

© SBS S.p.A. 2015. The company reserves the right to make changes to this documentation without notice.

Release 1.0 - Updating: 30/03/2015

© SBS S.p.A. - All rights reserved

Application Manual

Page 58

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement

Table of contents