Albeo AHH Series Heavy Industrial High Bay Lighting Installation Guide

Add to My manuals
3 Pages

advertisement

Albeo AHH Series Heavy Industrial High Bay Lighting Installation Guide | Manualzz
Albeo® AHH Series
Installation Guide
ALB082
Albeo® AHH2 LED Luminaire
Heavy Industrial Bay Lighting
ALB082
BEFORE YOU BEGIN
Read these instructions completely and carefully.
Save these instructions for future use.
WARNING/ADVERTISSEMENT/ADVERTENCIA
RISK OF ELECTRIC SHOCK
Turn power off before inspection, installation or removal. Properly
ground electrical enclosure.
RISK OF FIRE
Follow all NEC and local codes for the required wiring systems for
the specific Hazardous Locations involved.
RISQUES DE DÉCHARGES ÉLECTRIQUES
Coupez l’alimentation avant d’inspecter, installer ou déplacer le luminaire, installer
ou déplacer le luminaire. Assurez-vous de correctement mettre à la terre le boîtier
d’alimentation électrique.
RISQUES D’INCENDIE
Respectez tous les codes NEC et codes locaux.
This device complies with Part 15 of the FCC Rules, not part of UL Certification. Operation is subject to the following two conditions: (1) This device may not
cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
CAN ICES-005 (A) / NMB-005 (A)
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules, not part of UL
Certification. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in
which case the user will be required to correct the interference at his own expense.
Save These Instructions
Use only in the manner intended by the manufacturer. If
you have any questions, contact the manufacturer.
Prepare Electrical Wiring
Electrical Requirements
The LED luminaire must be supplied with 120-277 VAC or
347/480 VAC, 50/60 Hz per electrical ratings on product
label and connected to an individual properly grounded
branch circuit.
Grounding Instructions
The grounding and bonding of the overall system shall be
done in accordance with the national electric code (NEC)
Article 600 and local codes.
LED.com
Page 1 of 3
(Rev 10/05/23)
© 2023 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
ALB082-Albeo-AHH-Series-Heavy-Industrial-High-Bay-Lighting-Installation-Guide_R02
Albeo® AHH2 LED Luminaire
Installation Guide
ALB082
Section 1: Unit Installation
Provide at least 12” of clearance from the top of the fixture to any ceiling or surface above.
A
B
Carefully unpack unit and properly inspect
for defects before installing. Wear work
gloves to prevent dirt and oil from being
transferred to the luminaire.
C
AHH2 is suitable for pendant mount only.
Max. Weight (lbs.)
AHH2-Series
Configuration
120-277V
347/480V
Single
21
23
Dual
45
49
Luminaire
Input Power
Dimming
Circuit
Black
Live
White
Neutral
Green
Safety Ground
Purple
0-10V (+)
Pink
0-10V (-)
NOTE: For applications requiring the “R” corrosion resistant finish, use mounting hardware appropriate for the environment.
Section 2: Pendant Mounting
Attach pendant mount cover to ¾” NPT
conduit with at least 3 full threads of
engagement. Determine rotation of
luminaire and lock orientation in place
with provided set screw.
Lift luminaire up and hang on pendant
mount cover using hinge piece.
Feed the AC power lead wire through
the conduit and into the junction box.
Pink
Swing luminaire closed ensuring power
lead wires are not pinched and are fully
enclosed in pendant mount cover.
Secure with the slide clip and lock in
place with screw.
LED.com
Connect the green (ground), black (line)
and white (neutral) wires of the AC line
to the similarly colored wires of the
luminaire’s lead wire using UL listed
wire connectors.
Close junction box.
For dimming options, connect purple
and pink leads to dimming control that
is certified and suitable for the
hazardous locations involved, rated
0-10V min. A 10V signal corresponds
to 100% lumen output. A 0V signal
corresponds to ~10% lumen output.
Cap purple and pink leads separately
when not used.
Page 2 of 3
(Rev 10/05/23)
© 2023 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
ALB082-Albeo-AHH-Series-Heavy-Industrial-High-Bay-Lighting-Installation-Guide_R02
Albeo® AHH2 LED Luminaire
Installation Guide
ALB082
Secure pendant mount cover to luminaire by fully tightening the captive screws on the sides of the pendant mount box to the fixture.
NOTE: Safety chains (installer provided) can be used in mounting slots at end of fixture.
Section 3: Trouble Shooting
Symptom
Solution
Luminaire will not
turn on
• Check that the color of the supply side wires match the color of the wires they are connected to.
• Check that all wire connectors are properly connected.
• Verify that your input voltage is within specs.
• If you are using any additional controls (i.e. dimming wires, motion sensors), please also verify that those are
working properly and that the unit is setup to interface with the controllers.
Section 4: Maintenance
• Product should not be disassembled during installation process and/or while installed.
• Lens should be cleaned periodically for maximum lumen output.
• Inspect and clear any build-up on cooling fins periodically for maximum performance.
Questions:
Web: LED.com
Phone: 1-866-855-8629
These instructions do not purport to cover all details or variations in equipment nor to provide every possible contingency to be met in connection with installation,
operation or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the
matter should be referred to Current.
Ces instructions ne prétendent pas couvrir tous les détails ou variantes de l’équipement ni couvrir toutes les conditions possibles à satisfaire en rapport avec l’installation,
l’opération ou l’entretien. Si des informations supplémentaires sont souhaitées sur des aspects qui ne sont pas suffisamment couverts pour satisfaire les besoins du client,
ou sides problèmes particuliers se présentent, veuillez addresser ces questions à Current.
Estas instrucciones no pretenden cubrir todos los detalles o variaciones en el equipo ni para prever cualquier contingencia que debe cumplir en relación con la instalación,
la operación o el mantenimiento. De ser deseada más información o se surgieran problemas particulares que no están cubiertos suficientemente para los propósitos del
comprador, favor de remitirse a Current.
LED.com
Page 3 of 3
(Rev 10/05/23)
© 2023 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
ALB082-Albeo-AHH-Series-Heavy-Industrial-High-Bay-Lighting-Installation-Guide_R02

advertisement

Key Features

  • Heavy-duty construction
  • High lumen output
  • Energy efficient
  • Pendant mount
  • Dimming options
  • Corrosion resistant finish

Related manuals

Frequently Answers and Questions

How do I install the Albeo AHH Series luminaire?
The luminaire is designed for pendant mount only. You will need to attach the pendant mount cover to a ¾” NPT conduit and then hang the luminaire on the cover. You will then need to connect the AC power lead wire to the junction box and secure the luminaire in place with the slide clip and lock.
What are the dimming options for the Albeo AHH Series luminaire?
The luminaire can be dimmed using a 0-10V dimming control. A 10V signal corresponds to 100% lumen output. A 0V signal corresponds to ~10% lumen output.
What are the electrical requirements for the Albeo AHH Series luminaire?
The luminaire must be supplied with 120-277 VAC or 347/480 VAC, 50/60 Hz per electrical ratings on product label and connected to an individual properly grounded branch circuit.