Briskheat MPC2 Multi-Point Digital PID Temperature Controller Instruction manual


Add to my manuals
16 Pages

advertisement

Briskheat MPC2 Multi-Point Digital PID Temperature Controller Instruction manual | Manualzz

MPC Series

Digital Temperature Controllers

Installation Instructions

Read and understand this manual before operating or servicing this Centipede adaptor. Failure to understand how to safely operate this adaptor could result in an accident causing serious injury or death.

Only qualified personnel should operate or service these adaptors.

MPC Series: Digital Temperature Controller

Table of Contents

Shipment and Storage .................................................................................................................................. 2

Safety Alert Symbol ....................................................................................................................................... 2

Important Safety Instructions ...................................................................................................................... 3

Installation ...................................................................................................................................................... 3

Mounting the Controller ........................................................................................................................ 4

Power Input Connections ..................................................................................................................... 6

Alarm Dry Contact Connections ........................................................................................................... 8

RS485 Communication Connections ................................................................................................... 8

Operation ........................................................................................................................................................ 9

Programming and Operation ........................................................................................................................ 10

Warranty .........................................................................................................................................................

Shipment

Each BriskHeat® Temperature Controller is shipped in a box specially designed to protect the unit during shipment.

The box containing the controller should be stored indoors in a dry, protected area. Under no circumstances should condensation, rain, snow or water be allowed to come in contact with the box or the controller while in storage.

Storage

Avoid storing the controller in places where:

 The ambient temperature may reach beyond the range of:

 -40 to +80 °C (-40 to 176°F).

 The humidity conditions may go beyond:

 0 to 90% at 40 °C non-condensing

 10 to 50% at 55 °C non-condensing

SAFETY ALERT SYMBOL

The symbol above is used to call your attention to instructions concerning your personal safety. It points out important safety precautions. It means “ATTENTION! Become Alert! Your Personal

Safety is involved!” Read the message that follows and be alert to the possibility of personal injury or death.

Immediate hazards which WILL result in severe personal injury or death

Hazards or unsafe practices that COULD result in severe personal injury or death

Hazards or unsafe practices that COULD result in minor personal injury or property damage

BriskHeat

®

Corporation. All rights reserved

2

IMPORTANT SAFETY INSTRUCTIONS

A person who has not read and understood all operating instructions is not qualified to operate this product.

 Only qualified personnel are allowed to connect electrical wiring.

 All electrical wiring must follow local electrical codes and highly recommend following NEC Article 427.

 Final installation / wiring is to be inspected by the authority who has jurisdiction in the area that the heating tape is installed.

 The end-user is responsible for providing a suitable disconnecting device.

 The end-user is responsible for providing suitable electrical protection device. It is highly recommended that a ground fault circuit breaker is used.

MPC Series: Digital Temperature Controller

 Inspect all components before use.

 Do not use controller if any component is damaged.

 Do not repair a damaged or faulty controller.

 Do not crush or apply severe physical stress on any component of system, including cord assembly.

 Unplug controller when not in use.

Failure to observe these warnings may result in personal injury or damage to the temperature controller.

 Do not immerse or spray controller with liquid.

 Keep volatile or combustible material away from heater when in use.

 Keep sharp metal objects away from heater.

Failure to observe these warnings may result in electric shock, risk of fire, and personal injury.

Installation

It is recommended that the user read this manual in its entirety before installing or operating the temperature control system.

Unless otherwise specified, the controller’s end user must supply branch-circuit protection and the disconnecting means.

General

BriskHeat

® temperature controllers are designed to operate from a single power input connection. Unless custom ordered, BriskHeat

®

temperature controllers do not provide over current protection nor do they have the means of disconnecting power. The end user is responsible for the disconnecting means and branch circuit protection. It is highly recommended that the end user protect the controller with a GFCI, in case of ground-fault.

All electrical connections must be made by a qualified electrician in accordance to all applicable building regulations, electrical codes, and safety standards.

The controller should be installed indoors in an area that is dry and classified as a non-hazardous location.

BriskHeat

®

Corporation. All rights reserved

3

MPC Series: Digital Temperature Controller

Mounting the MPC Controller:

The following procedure should be used when installing the MPC temperature controller.

1. Choose an appropriate location considering the following: a. Proximity to a suitable power supply. b. Proximity to overcurrent protection. c. Proximity to a means of disconnecting or switching equipment. d. Appropriate clearances

i. Example: clearance to open enclosure door at least 90°, clearance to allow easy connection of power

cords and sensors

e. Operating temperature does not go beyond the range of: i. -10 to +55 °C (+14 to131 °F) f. Humidity conditions do not go beyond: i. 0 to 90% up to 40 °C non-condensing, 10 to 50% at 55 °C non-condensing.

2. Mount the controller securely in the chosen location. All four mounting holes should be used and bolted to a strong stable support. The mounted location must provide easy access for the operator. The following drawings display the three different size enclosures that the MPC controllers will use. The drawings display the maximum exterior dimensions, mounting dimensions and recommended clearances needed for normal operation. Depending on the options that have been selected for the MPC controller, the enclosure size for a particular controller may actually be larger than displayed in this manual. In such cases, the customer should contact the factory for the specific enclosure size. (Actual dimensions may vary slightly in the field. All designs are subject to change without notification.)

BriskHeat

®

Corporation. All rights reserved

4

MPC Series: Digital Temperature Controller

Enclosure Size for two to four zones:

Enclosure Size for five to eight zones:

BriskHeat

®

Corporation. All rights reserved

5

MPC Series: Digital Temperature Controller

Enclosure Size for five to eight zones:

Power Input Connections:

Connect the power supply lines for the controller per the following drawings. The distribution block will be located in the bottom center of the inner panel. The installer should punch the appropriate sized hole to install the conduit for the input power

The hazard of electrical shock exists with any electrical installation. Disconnect all power routed to the controller at its source before making any internal connections. Check the controller’s data label or the electrical schematics for the required power supply necessary for your controller. A qualified electrician must make all electrical connections in accordance to all applicable building regulations, electrical codes, and safety standards.

BriskHeat

®

Corporation. All rights reserved

6

Two to seven zone MPC single phase:

MPC Series: Digital Temperature Controller

Eight to ten zone MPC single phase:

Two to seven zone MPC three phase:

BriskHeat

®

Corporation. All rights reserved

7

Eight to ten zone MPC three phase:

MPC Series: Digital Temperature Controller

Alarm Dry Contact Connection:

The male receptacle pin layout is shown in Diagram A. The alarm contact is rated for 220VAC/30VDC at 1A (resistive load).

Diagram A:

The alarm relay cable O.D. must be between 0.11”-0.315” with two to three

18 AWG conductors. The female connector pieces assemble together as shown in Diagram B.

Diagram B:

RS-485 Communications Connection

The female receptacle for the RS485 communications is connected as shown in

Diagram C.

Diagram C:

The Communication cord must be less than 0.28” in diameter and contain two 20AWG conductors. The plug pieces assemble together as shown in the drawing Diagram D.

Diagram D:

BriskHeat

®

Corporation. All rights reserved

8

MPC Series: Digital Temperature Controller

Operation

1. All MPC controllers use, “J” type thermocouples. The thermocouple jacks accept mini thermocouple plugs.

2. Place the thermocouple sensing tip between the surfaces to be heated and the heater to be controlled. The thermocouple tip must be placed in a location which best reflects the end user’s application. Depending on the object’s size and shape, there may be spots that are warmer or colder due to different thermal transfer parameters.

If all areas of the object must reach a minimum temperature, then place the thermocouple tip on the coldest spot.

If the temperature of any area of the object cannot go above the controller’s set point, then place the thermocouple tip on the hottest spot. If a temperature differential is allowable, then place the thermocouple tip on an area where the temperature is between the hottest and coldest.

3. Plug the power lead of the heater (s) into the appropriate zone receptacle.

4. Plug the thermocouple into the thermocouple jack that corresponds to the zone that it is measuring.

5. Push the green switch located on the front of the controller to the “ON” position. The green switch will latch into a recess position and will illuminate.

6. Program each zone controller with the values needed to properly control the heater. (See Programming and Operation page12)

7. It is highly recommended that the end user select the self-tuning for optimal performance. (See Programming and Operation page12)

BriskHeat

®

Corporation. All rights reserved

9

PROGRAMMING AND OPERATION

MPC Series: Digital Temperature Controller

BriskHeat

®

Corporation. All rights reserved

10

MPC Series: Digital Temperature Controller

BriskHeat

®

Corporation. All rights reserved

11

MPC Series: Digital Temperature Controller

BriskHeat

®

Corporation. All rights reserved

12

MPC Series: Digital Temperature Controller

WARRANTY INFORMATION

The BriskHeat

®

Corporation (hereinafter referred as (“BriskHeat”) warrants to the original purchaser for the period of

eighteen (18) months from date of shipment or twelve (12) months from date of installation, whichever comes first, that the products manufactured by BriskHeat

®

: (A) conform to the description and specifications as set forth in

BriskHeat’s current catalogue or in the quotation and drawings submitted by BriskHeat

®

: and (B) are free from defects in materials and workmanship under prescribed use and service.

Remedy. BriskHeat

®

’s obligation and the exclusive remedy under this warranty shall be limited to the repair or replacement, at BriskHeat

® s option, of any parts of the product which may prove defective under prescribed use and service within eighteen (18) months from date of shipment or twelve (12) months from date of installation, whichever comes first, and which, following BriskHeat

®

’s examination, is determined by BriskHeat

® s to be defective under conditions described herein: provided, BriskHeat

®

has, at its option, a representative of BriskHeat

®

present at start-up.

BriskHeat

®

shall not be liable for any incidental, consequential or special damages arising from any breach of warranty, breach of contract, negligence, or any other legal theory, including but not limited to, loss of use of parts or equipment or any associated equipment, cost of capital, cost of any substitute equipment, facilities or services, overhead, downtime costs, or claims of customer of purchaser for such damages. This remedy does not include labor costs for installation or removal of the equipment or parts covered by this warranty, and BriskHeat

®

shall not be responsible for such labor costs.

Limitation. This warranty shall not apply to any product or part thereof which has been subject to accident, negligence, alteration, damage during shipment, improper service, abuse, or misuse, including but not limited to use beyond rated capacity. BriskHeat

®

makes no warranty whatsoever with respect to accessories or parts not supplied or manufactured by BriskHeat

®

. BriskHeat

®

’s obligation under this warranty shall be conditioned upon BriskHeat

®

’s receiving written notice of any defect within fifteen (15) days after its discovery, and, at BriskHeat

®

’s option, return of such equipment or parts prepaid to its factory at 1055 Gibbard Ave., Columbus, Ohio 43201.

Disclaimer. BRISKHEAT MAKES NO WARRANTY WHATSOEVER, EXPRESS OR IMPLIED, EXCEPT AS IS

EXPRESSLY SET FORTH ABOVE. NO AGENT, EMPLOYEE OR REPRESENTATIVE OF BRISKHEAT HAS ANY

AUTHORITY TO BIND BRISKHEAT TO ANY AFFIRMATION, REPRESENTATION OR WARRANTY COVERING THE

SALE OF ANY PRODUCT, AND UNLESS SUCH AFFIRMATION, REPRESENTATION OR WARRANTY MADE BY

AN AGENT, EMPLOYEE OR RERESENTATIVE IS SPECIFICALLY ENDORSED IN WRITING BY BRISKHEAT, IT

SHALL NOT BE ENFORCEABLE BY ANY BUYER. BRISKHEAT MAKES NO EXPRESS OR IMPLED WARRANTY

OF MERCHANTABILITY AND NO EXPRESS OR IMPLIED WARRANTY OF FITNESS FOR PARTICULAR

PURPOSE, EXCEPT AS IS EXPRESSLY SET FORTH ABOVE. BRISKHEAT SHALL NOT BE LIABLE FOR

CONSEQUENTIAL, INCIDENTIAL OR SPECIAL DAMAGES.

This warranty allocates risk between the purchaser and BriskHeat

®

as authorized by the Uniform Commercial Code and other applicable law.

BriskHeat

®

Corporation. All rights reserved

13

NOTES:

MPC Series: Digital Temperature Controller

BriskHeat

®

Corporation. All rights reserved

14

NOTES:

MPC Series: Digital Temperature Controller

BriskHeat

®

Corporation. All rights reserved

15

MPC Series: Digital Temperature Controller

1055 Gibbard Ave, Columbus, OH 43201

Toll Free: 800-848-7673

Phone: 614-294-3376

Fax: 614-294-3807

Email: [email protected]

BriskHeat

®

Corporation. All rights reserved

16

PN: 40890-08 Rev B