Installation, Service and Operating Instructions for use by heating contractor Viessmann AirflowPLUS AH2A series Hydronic forced air handler Viessmann AirflowPLUS Product may not be exactly as shown IMPORTANT Read and save these instructions for future reference. 5680 011 - 24 07/2022 Please file in Service Binder Safety Viessmann AirflowPLUS AH2A Installation, Operating and Service Safety, Installation and Warranty Requirements Please ensure that these instructions are read and understood before commencing installation. Failure to comply with the instructions listed below and details printed in this manual can cause product/property damage, severe personal injury, and/or loss of life. Ensure all requirements below are understood and fulfilled (including detailed information found in manual subsections). For a listing of applicable literature, please see section entitled “Important Regulatory and Installation Requirements”. Warranty Information contained in this and related product documentation must be read and followed. Failure to do so renders the warranty null and void. Licensed professional heating contractor The installation, adjustment, service and maintenance of this equipment must be performed by a licensed professional heating contractor. Please see section entitled “Important Regulatory and Installation Requirements”. Advice to owner Once the installation work is complete, the heating contractor must familiarize the system operator/ ultimate owner with all equipment, as well as safety precautions/requirements, shutdown procedure, and the need for professional service annually before the heating season begins. WARNING Follow the Viessmann maintenance schedule of the boiler contained in this manual. Operating and service documentation It is recommended that all product documentation such as parts lists, operating and service instructions be handed over to the system user for storage. Documentation is to be stored near air handler in a readily accessible location for reference by service personnel. 2 Fiberglass wool materials WARNING Inhaling of fiberglass wool materials is a possible cancer hazard. These materials can also cause respiratory, skin and eye irritation. The state of California has listed the airborne fibers of these materials as a possible cancer hazard through inhalation. When handling these materials, special care must be applied. Suppliers of fiberglass wool products recommend the following precautions be taken when handling these materials: - Avoid breathing fiberglass dust and contact with skin and eyes. - Use NIOSH approved dust/mist respirator. - Wear long-sleeved, loose fitting clothing, gloves and eye protection. - Wash work clothes separately from other clothing. Rinse washer thoroughly. - Operations such as sawing, blowing, tear-out and spraying may generate airborne fiber concentration requiring additional protection. First aid measures - If eye contact occurs, flush eyes with water to remove dust. If symptoms persist, seek medical attention. - If skin contact occurs, wash affected areas gently with soap and warm water after handling. WARNING Appliance materials of construction, may contain toxic or harmful substances which can cause serious injury or loss of life and which are known to the State of California to cause cancer, birth defects and other reproductive harm. Always use proper safety clothing, respirators and equipment when servicing or working nearby the appliance. 5680 011 - 24 Product documentation Read all applicable documentation before commencing installation. Store documentation near air handler in a readily accessible location for reference in the future by service personnel. Viessmann AirflowPLUS AH2A Installation, Operating and Service Table of Contents 5680 011 - 24 Page Safety Safety, Installation and Warranty Requirements..............2 Product documentation...........................................2 Warranty...............................................................2 Licensed professional heating contractor...................2 Advice to owner....................................................2 Operating and service documentation.......................2 Fiberglass wool materials........................................2 First aid measures..................................................2 General Information About these Installation Instructions..............................5 Necessary Tools.........................................................5 Important Regulatory and Installation Requirements........6 Codes..................................................................6 Instructing the system user...................................6 Initial start-up........................................................6 Working on the equipment......................................6 Technical literature................................................6 Product Description Introduction...............................................................7 Components................................................................7 Features......................................................................8 Equipment Selection and Sizing.....................................9 Compatibility Charts.....................................................9 Installation Before Set-up..............................................................12 Minimum Clearances...................................................12 Dimensions.............................................................13 Heating Circuit Pumps.............................................14 Installation...............................................................14 Installation Examples.................................................15 Horizontal installation...........................................16 Vertical installation..............................................17 Proper Piping Practice................................................17 Connecting to the Heating System..............................17 Removing the Blower Shipping Bracket.......................18 Opening the Air Handling Unit....................................18 Panels.....................................................................19 Accessing the Connection Board................................22 Vitodens 100 B1HA/B1KA Wiring...............................23 Vitodens 100 B1HE, B1KE.........................................24 HO1B Wiring............................................................25 Vitodens 100 B2HE Wiring........................................26 Control Function.......................................................27 Supply Water Temperature (T1).................................27 Freeze Protection Temperature (T3)............................27 A/C Discharge Air Temperature (T4)...........................27 Remote Return Air Sensor (T5)..................................28 Ambient Sensor (T6).................................................28 Sensor Locations......................................................28 S1 Dip Switch Settings.............................................29 Door Safety Switch..................................................30 Electrical.................................................................31 Thermostat.........................................................31 Power Supply...........................................................32 Control Inputs.........................................................33 Setting Fan Speed....................................................34 3 Table of Contents Viessmann AirflowPLUS AH2A Installation, Operating and Service Page Startup Quick Check.............................................................37 Pre-start Checklist.....................................................37 Startup Procedure....................................................38 Air handlers LED Indications for Temperature...............38 Installing Connection Board........................................39 Installing the Access Panels.......................................39 Operation Indicators................................................................40 Flashing LED............................................................40 Normal Operation......................................................41 Heating mode.....................................................41 Cooling mode......................................................41 Summary............................................................41 External Heat Demand via Switching Contact Boilers equipped with HO1B User Interface..................41 Service Illuminated Alarm Indicator.........................................42 Home freeze protect............................................42 Temperature sensor failure....................................42 Alarm Relay and LED Fault Codes..............................43 Control LED flash codes.......................................43 Alarm.................................................................43 Checking ECM (DC) Fan Motor Connections.................44 Troubleshooting.......................................................45 Service and Maintenance...........................................49 Checking temperature sensor................................49 Installed sensors..................................................49 Failed sensors......................................................49 Air filter..............................................................49 Circulator...........................................................49 Coils..................................................................49 4 System Layout 1......................................................50 System Layout 2......................................................51 System Layout 3......................................................52 System Layout 4......................................................53 System Layout 5......................................................54 System Layout 6......................................................55 System Layout 7......................................................56 System Layout 8......................................................57 System Layout 9......................................................58 System Layout 10....................................................59 Electrical Connectors.................................................60 Technical Data.........................................................62 Parts List.................................................................63 5680 011 - 24 Additional Information Viessmann AirflowPLUS AH2A Installation, Operating and Service General Information About these Installation Instructions Take note of all symbols and notations intended to draw attention to potential hazards or important product information. WARNING Warnings draw your attention to the presence of potential hazards or important product information. CAUTION Cautions draw your attention to the presence of potential hazards or important product information. Indicates an imminently hazardous situation which, if not avoided, could result in death, serious injury or substantial product/property damage. Indicates an imminently hazardous situation which, if not avoided, may result in minor injury or product/ property damage. IMPORTANT Helpful hints for installation, operation or maintenance which pertain to the product. This symbol indicates to note additional information This symbol indicates that other instructions must be referenced. Necessary Tools Testing/analysis equipment (Use only calibrated equipment) H Multimeter to measure 0 - 230V, 0 - 12A AC and 0-100 mA DC H Manometer to measure air pressure 0 to 11 "w.c. (accurately) (or a non-electric Magnehelic® manometer may also be utilized) Cleaning supplies H Plastic hand brush H Rags Special items 5680 011 - 24 H Pipe joint sealant 5 General Information Viessmann AirflowPLUS AH2A Installation, Operating and Service Important Regulatory and Installation Requirements Codes Working on the equipment In Canada all electrical wiring is to be done in accordance with the latest edition of CSA C22.1 Part 1 and/or local codes. In the U.S. use the National Electrical Code ANSI/ NFPA 70. The heating contractor must also comply with both the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1, and the Installation Code for Hydronic Heating Systems, CSA B214-01, where required by the authority having jurisdiction. The installation, adjustment, service, and maintenance of this air handler must be done by a licensed professional heating contractor who is qualified and experienced in the installation, service, and maintenance of hot water heating equipment. There are no user serviceable parts on the air handler. Instructing the system user For information regarding other Viessmann System Technology componentry, please reference documentation of the respective product. The installer of the system is responsible to ensure the system operator/ultimate owner is made familiar with the system functioning, its activation, and its shut-down. The following topics must be covered: - Proper system operation sequence. - Explain the equipment. - Demonstrate an emergency shut-down, what to do and what not. - Explain that there is no substitute for proper maintenance to help ensure safe operation. Initial start-up Initial start-up must be performed by a qualified heating contractor. Proper completion of the Maintenance Record by the heating contractor is also required. Please carefully read this manual prior to attempting start-up, maintenance or service. Any warranty is null and void if these instructions are not followed. We offer frequent installation and service seminars to familiarize our partners with our products. Please inquire. Ensure main power supply to equipment, the heating system, and all external controls have been deactivated. Take precautions in all instances to avoid accidental activation of power during service work. The completeness and functionality of field supplied electrical controls and components must be verified by the heating contractor. These include low water cut-offs, flow switches (if used), staging controls, pumps, motorized valves, air vents, thermostats, etc. Technical literature Literature for the Viessmann AirflowPLUS air handler: - Technical Data Manual - Installation, Service, and Operating Instructions - Instructions of other Viessmann products utilized and installed - Installation codes mentioned in this manual Leave all literature at the installation site and advise the system operator/ultimate owner where the literature can be found. Contact Viessmann for additional copies. 6 5680 011 - 24 This product comes with several safety instruction labels attached. Do not remove! Contact Viessmann immediately if replacement labels are required. Viessmann AirflowPLUS AH2A Installation, Operating and Service Product Description Introduction The Viessmann AirflowPLUS AH2A series air handlers are to be used in conjunction with Viessmann boilers. The automatic adjustments are made in heating as well as cooling. This minimizes selecting an oversized heating appliance just to accommodate the cooling load. The Viessmann AirflowPLUS AH2A series is always the right size. Components Cabinet All cabinets have a tough, durable powder coat finish on satin coat 20 gauge steel. Heating coils All heating coils are copper and assembled using no lead solder. All coils and internal piping conform to ASTM B-68, B-88 and/or B-743 standards. High density aluminum fins provide maximum heat transfer for small coil surface. Fan and motor The ECM fan is a wide body dynamically balanced for extra quiet operation. Multi-directional sleeve bearing motors allow mounting in any direction for maximum installation flexibility. Circulating pump The internal circulating pump is matched for maximum performance. All Airflow PLUS air handlers come with internally mounted pumps for ease of installation. 5680 011 - 24 Legend A Standard adaptors (at the rear) B Heating coil and pump slide out for easy service C Integrate pump with check valve D Fibreglass insulation with reinforced foil face and gasket seals E Fan and controls slide out on rails F Integrated filter rack Check valve A check valve is built into the circulator to protect against backflow of water. 7 Product Description Viessmann AirflowPLUS AH2A Installation, Operating and Service Features Pump exercise function If the internal circulating pump has not run in the previous 24 hours, the control will turn the pump on for 1 minute to flush the lines and heat exchanger. This will help ensure that the water lubricated pump does not seize during long periods of inactivity. Home freeze protection The Viessmann AirflowPLUS AH2A series air handlers have an integrated sensor which will help prevent the home from freezing due to a faulty thermostat. Should the ambient temperature get too low, the control will turn the air handler on automatically and maintain the home at approximately 40°F (4°C). Note: this feature will only work if the boiler is turned on and the air handler has power. While in Home freeze protect mode the alarm relay and red light will be on. Refer to page 42. Status and alarm indicators A bicolor LED indicator is installed in the air handler housing and is used to indicate alarm, test mode, and normal operation. The indicator will display temperature readings of the sensors during normal operation. Alarms Should service problems arise the Viessmann AirflowPLUS AH2A series will notify the user with a housing mounted LED. Dry contacts are provided on the controller which can be connected to an external device such as a warning light or home security system. 8 5680 011 - 24 Customizing The heating and cooling features can be field customized to provide maximum comfort for almost any home or location. Refer to page 28, 33, 34 and 35. Product Description Viessmann AirflowPLUS AH2A Installation, Operating and Service Equipment Selection and Sizing Proper sizing of systems components is crucial for proper operation; 1. Obtain room by room heat loss and/or heat gain 2. Determine heating water temperature 3. Determine duct layout Make sure a proper room-by-room heat loss and heat gain for the dwelling is calculated using Manual J, HRAI, ASHRAE or other approved sizing method. Compatibility Charts Air handler model AH2A-213 Boiler supply water temperature Vitodens 100 B1HA-94 Vitodens 100 B1HA-125 Vitodens 100 B1KA-125 120°F (28 MBH) 140°F (46 MBH) 160°F (62 MBH) 180°F (72 MBH) ---- Vitodens 100 B1HE-85 Vitodens 100 B1HE-120 Vitodens 100 B1HE-150 Vitodens 100 B1HE-199 - Vitodens 100 B1KE-120 Vitodens 100 B1KE-199 - Vitodens 222 B2TB-68 Vitodens 222 B2TB-125 - Vitodens 200 B2HB-68 Vitodens 200 B2HB-94 Vitodens 200 B2HB-125 Vitodens 200 B2HB-160 Vitodens 200 B2HB-199 Vitodens 200 B2HA-285 Vitodens 200 B2HA-311 Vitodens 200 B2HA-352 Vitodens 200 B2HA-399 Vitodens 200 B2HA-530 - - Vitodens 200 B2HE-85 Vitodens 200 B2HE-120 Vitodens 200 B2HE-150 Vitodens 200 B2HE-199 - Vitocrossal 300 CU3A-94 Vitocrossal 300 CU3A-125 Vitocrossal 300 CU3A-160 Vitocrossal 300 CU3A-57, 199 5680 011 - 24 Note: Compatibility charts do not take into consideration systems using additional heat emitters, DHW load etc. Ensure the boiler selected meets all of the system requirements for loads generated by additional components. It is the responsibility of the system designer to ensure proper sizing and equipment selection. 9 Product Description Viessmann AirflowPLUS AH2A Installation, Operating and Service Compatibility Charts (continued) Air handler model AH2A-354 Boiler supply water temperature Vitodens 100 B1HA-94 Vitodens 100 B1HA-125 Vitodens 100 B1KA-125 120°F (44 MBH) 140°F (61 MBH) 160°F (83 MBH) 180°F (98 MBH) ---- Vitodens 100 B1HE-85 Vitodens 100 B1HE-120 Vitodens 100 B1HE-150 Vitodens 100 B1HE-199 Vitodens 100 B1KE-120 Vitodens 100 B1KE-199 - - Vitodens 222 B2TB-68 Vitodens 222 B2TB-125 - Vitodens 200 B2HB-68 Vitodens 200 B2HB-94 Vitodens 200 B2HB-125 Vitodens 200 B2HB-160 Vitodens 200 B2HB-199 Vitodens 200 B2HA-285 Vitodens 200 B2HA-311 Vitodens 200 B2HA-352 Vitodens 200 B2HA-399 Vitodens 200 B2HA-530 - - Vitodens 200 B2HE-85 Vitodens 200 B2HE-120 Vitodens 200 B2HE-150 Vitodens 200 B2HE-199 - - Vitocrossal 300 CU3A-94 Vitocrossal 300 CU3A-125 Vitocrossal 300 CU3A-160 Vitocrossal 300 CU3A-199 -- 10 5680 011 - 24 Note: Compatibility charts do not take into consideration systems using additional heat emitters, DHW load etc. Ensure the boiler selected meets all of the system requirements for loads generated by additional components. It is the responsibility of the system designer to ensure proper sizing and equipment selection. Product Description Viessmann AirflowPLUS AH2A Installation, Operating and Service Compatibility Charts (continued) Air handler model AH2A-385 Boiler supply water temperature Vitodens 100 B1HA-94 Vitodens 100 B1HA-125 Vitodens 100 B1KA-125 120°F (51 MBH) 140°F (74 MBH) 160°F (90 MBH) 180°F (115 MBH) - - - Vitodens 100 B1HE-85 Vitodens 100 B1HE-120 Vitodens 100 B1HE-150 Vitodens 100 B1HE-199 Vitodens 100 B1KE-120 Vitodens 100 B1KE-199 - - -- Vitodens 222 B2TB-68 Vitodens 222 B2TB-125 - - Vitodens 200 B2HB-68 Vitodens 200 B2HB-94 Vitodens 200 B2HB-125 Vitodens 200 B2HB-160 Vitodens 200 B2HB-199 Vitodens 200 B2HA-285 Vitodens 200 B2HA-311 Vitodens 200 B2HA-352 Vitodens 200 B2HA-399 Vitodens 200 B2HA-530 -- Vitodens 200 B2HE-85 Vitodens 200 B2HE-120 Vitodens 200 B2HE-150 Vitodens 200 B2HE-199 - - -- Vitocrossal 300 CU3A-94 Vitocrossal 300 CU3A-125 Vitocrossal 300 CU3A-160 Vitocrossal 300 CU3A-199 - - 5680 011 - 24 Note: Compatibility charts do not take into consideration systems using additional heat emitters, DHW load etc. Ensure the boiler selected meets all of the system requirements for loads generated by additional components. It is the responsibility of the system designer to ensure proper sizing and equipment selection. 11 Installation Viessmann AirflowPLUS AH2A Installation, Operating and Service Before Set-up Before placing Viessmann AirflowPLUS in its installation location, ensure all necessary accessories are installed. CAUTION The air handler must be installed in such a way that electrical components are protected from water (spraying, splashing, etc.) during operation and service. Minimum Clearances Horizontal Installation Recommended minimum service clearances For typical Viessmann AirflowPLUS installation, it is recommended to install the air handler with the clearances shown in the illustration. a - 24 in. (610 mm) b - 12 in. (305 mm) These dimensions reflect the recommended service clearance for the air handler only, ensure adequate clearance is left for the installation of ducting, piping and electrical connections. Only the b clearance may be reduced providing there is enough clearance for ductwork, plumbing and electrical connections, with zero clearance between the air handler unit and ducting being acceptable. 12 5680 011 - 24 Vertical Installation Installation Viessmann AirflowPLUS AH2A Installation, Operating and Service Dimensions IMPORTANT The maximum ambient temperature must not exceed 104ºF (40ºC). AH2A-213 AH2A-354 AH2A-385 a in. (mm) 22c (578 mm) 23 (584 mm) 28 (711 mm) b in. (mm) 18 (457 mm) 22 (559 mm) 22 (559 mm) c* in. (mm) 32b (826 mm) 34b (876 mm) 34b (876 mm) d* in. (mm) 22a (572 mm) 24e (620 mm) 24e (620 mm) e* in. (mm) 23b (597 mm) 25b (650 mm) 25b (650 mm) f in. (mm) 2 (51 mm) 1c (44 mm) 1c (44 mm) g in. (mm) 3 (76 mm) 3f (92 mm) 3f (92 mm) h in. (mm) 24c (629 mm) 25 (635 mm) 30 (762 mm) Top view * Using the adjustable levelling feet can add up to 1b in. (38 mm) to the height of the air handler. Legend A Heating water supply connection B Heating water return connection 5680 011 - 24 Front view Side view 13 Installation Viessmann AirflowPLUS AH2A Installation, Operating and Service Heating Circuit Pumps Pump Model Rated voltage Rated current Capacitor Power consumption Grundfos UPS15-58RU VAC Amp F Watts 115 0.74 10 87 Legend A Speed 1 Pump curve B Speed 2 Pump curve C Speed 3 Pump curve Note: All Viessmann AirflowPLUS air handlers come with pump speed factory set to speed 3. Installation The contractor shall adhere to all local, state and national code requirements pertaining to the installation of this equipment. The Viessmann AirflowPLUS AH2A can be suspended by securing straps to the corners of the enclosure (field supplied). The Viessmann AirflowPLUS AH2A series air handler can be mounted in most directions. Upflow, downflow, horizontal left and horizontal right. You cannot install the air handler on it’s back or suspended with front cover facing down. An adequately sized drain pan and drain connection must be installed under the appliance if installed in or above a finished space. Install the air handler with the door screwed in place to avoid distortion of the cabinet. The installing contractor must ensure that suspension materials are sized and installed to provide sufficient support to the air handler and connected accessory fittings and materials. 14 5680 011 - 24 If installed in an unfinished space, a drain pan is not provided, necessary precautions must taken to ensure proper drainage of water in the event of a water leak (e.g. Floor drain, sump pump, moisture alarm...). This appliance shall not be installed in a non conditioned space where the potential may exist for the appliance and or water lines and drain line to freeze. Note: System layout examples are provided starting on page 50 of these instructions. Installation Viessmann AirflowPLUS AH2A Installation, Operating and Service Installation Examples Horizontal installation Supply air IMPORTANT A field fabricated auxiliary drain pan with drain pipe is recommended in all configurations. Suspension material (field supplied) Secure the suspension material to the corners of the air handler housing. CAUTION Return air openings shall not be installed in back panel. IMPORTANT You cannot install the air handler on it’s back or suspended with front cover facing down. Return air Note: Return air openings are provided in both the bottom and side panels. Note: Field selected suspension materials must be sized by installing contractor so as to be of sufficient strength to support air handler weight of 150 lbs. (68 kg) and connected accessory fittings and materials. Temperature sensor and low voltage lead routing A/C Coil installed upstream of Air Handler in return plenum. Refer to “Remote Return Air Sensor T5” on page 27 for information. 5680 011 - 24 For an installation over a finished space A field fabricated auxiliary drain pan with drain pipe is required to prevent damage by overflow due to blocked condensate drain. 15 Installation Viessmann AirflowPLUS AH2A Installation, Operating and Service Installation Examples (continued) Vertical installation The A/C coil is installed in the downstream air flow of the Viessmann AirflowPLUS air handler. Supply air IMPORTANT A field fabricated auxiliary drain pan with drain pipe is required in all configurations. CAUTION Return air openings shall not be installed in back panel. A/C coil A Supply air temperature sensor lead shall be routed out of air handler casing through knock-out provided in either side of casing and secured to plenum using nylon clips provided. A Return air Drill 3/8 in. dia. hole in return air duct a minimum of 15 in. (381 mm) downstream of plenum. Snap round bushing into hole and insert sensor lead approximately 2 in. (51 mm) and secure to duct using nylon strap included. B Air Filter B Supply air temperature sensor lead and low voltage lead wires shall be isolated from high voltage leads and routed through knockouts provided. Vertical installation The A/C coil is installed in the upstream air flow of the Viessmann AirflowPLUS air handler. This will require the use of the remote return air temperature sensor mounted upstream of the A/C coil. See page 27 for additional information regarding the remote return air temperature sensor. Supply air Supply air sensor lead and low voltage lead wires shall be isolated from high voltage leads and routed through knockouts provided. 16 Air Filter A/C Coil 5680 011 - 24 Return air For remote return air temperature sensor drill 3/8 in. dia. hole in return air duct a minimum of 15 in. upstream of plenum. Snap round bushing into hole and insert sensor lead approximately 2 in. (51 mm) and secure to duct using nylon strap included. Installation Viessmann AirflowPLUS AH2A Installation, Operating and Service Installation Examples (continued) Vertical installation The A/C coil is installed in the downflow position of the Viessmann AirflowPLUS air handler. Return air IMPORTANT A field fabricated auxiliary drain pan with drain pipe is required in all configurations. CAUTION Return air openings shall not be installed in back panel. Air Filter B A Supply air temperature sensor lead shall be routed out of air handler casing through knock-out provided in either side of casing and secured to plenum using nylon clips provided. Drill 3/8 in. dia. hole in return air duct a minimum of 15 in. (381 mm) downstream of plenum. Snap round bushing into hole and insert sensor lead approximately 2 in. (51 mm) and secure to duct using nylon strap included. A/C coil B Supply air temperature sensor lead and low voltage lead wires shall be isolated from high voltage leads and routed through knockouts provided. A Supply air Proper Piping Practice Support piping by proper suspension method. Piping must not rest on or be supported by the air handler. Use moderate amount of dope. 2 imperfect threads This section constitutes an overview only! Refer to subsequent sections for detailed information on individual piping connections. Leave 2 threads bare Use an approved pipe sealant or teflon tape when connecting the following installation fittings. 5680 011 - 24 Connecting to the Heating System Air handler piping Depending on the boiler selected and system design it may be required to use a primary, secondary piping arrangement to de-couple the flow through the boiler from the flow through the air handler. Refer to the system layout examples starting on page 50. Duct work All duct designs must be designed to conform with ARI Manuals “J” and “D” or local codes and requirements. To minimize fan noise in the living space, it is recommended that the first six feet of supply and return air duct be lined with acoustic insulation. Boiler Follow the instructions provided with the boiler for installation and start-up of the boiler. Make sure the heating device is turned off during air handler installation and service. Ensure system has been filled, and all air is purged from the system before turning on the heating boiler. Return and supply air duct work should be the same size as the air handler openings up to the first branch, fitting or transition. 17 Installation Viessmann AirflowPLUS AH2A Installation, Operating and Service Removing the Blower Shipping Bracket 1. Remove the bracket retaining thumb screws and discard. 2. Remove the bracket and discard. Opening the Air Handler Unit 1. Remove the lower front panel retaining screws and set aside. 2. Tilt the lower front panel forward at the top and lift out. 3. Remove the upper front panel retaining screws and set aside. 18 5680 011 - 24 4. Slide the upper front panel down and pull out. Viessmann AirflowPLUS AH2A Installation, Operating and Service Installation Panels There are 2 return air openings on the air handler. One is located on the left side for vertical installations and one is located at the bottom for horizontal installations. For horizontal installations, remove the bottom panel and install it to the left side panel opening. Vertical opening (left side) Horizontal opening (bottom) Horizontal installation 1. Remove the bottom panel retaining screws and set aside. 2. Remove the bottom panel and set aside. Note: The fan tray is preinstalled into the bottom of the air handler. 3. Install the bottom panel to the left side of the air handler opening and secure with the retaining screws. 4. Connect the field supplied ducting to the bottom of the air handler. 5680 011 - 24 5. Connect the field supplied ducting as required. 19 Installation Viessmann AirflowPLUS AH2A Installation, Operating and Service Panels (continued) To change the duct connection side of the air handler for vertical installation, the right and left side panel can be interchanged. To interchange the panels refer to the following instructions. 1. Remove the retaining screws and set aside. 2. Remove the side panel by pulling up on the handle and then out. 3. Remove the retaining screws from the panel on the opposite side and set aside. 20 5680 011 - 24 4. Remove the side panel by pulling up on the handle and then out. Viessmann AirflowPLUS AH2A Installation, Operating and Service Installation Panels (continued) 5. Install the side panel (removed from step 2) by placing the panel into the air handler and pushing down with the handle. 6. Reinstall the retaining screws. Note: To install the filter tray, see page 21. 7. Install the side panel (removed from step 4) by placing the panel into the air handler and pushing down with the handle. 5680 011 - 24 8. Reinstall the retaining screws. 21 Installation Viessmann AirflowPLUS AH2A Installation, Operating and Service Panels (continued) Filter tray for vertical installation Note: If an A/C condenser is installed upstream, a field supplied filter tray maybe placed elsewhere in the ducting, see page 15. 1. Remove the retaining screws from the side panel. 2. Install the filter tray into the side panel opening. 3. Drill into the filter tray and secure the filter tray to the side panel using the retaining screws. 4. Remove the 3 plastic retaining screws, open the tray and remove the supplied filter. 5. Remove the side panel of the filter tray and insert the filter. 6. Connect the field supplied ducting to the filter tray as required. Accessing the Connection Board Accessing the connection board with hinged cover 1. Remove the blower assembly retaining screws and set aside. 2. Slide the blower assembly forward. IMPORTANT Careful not to slide the blower assembly out too far, it could put excessive strain on the cables. 3. Remove the 2 retaining screws from the connection board cover. 4. Swing the cover up to open. OR Accessing the connection board with removable cover 1. Remove the blower assembly retaining screw and set aside. 2. Slide the blower assembly forward. IMPORTANT Careful not to slide the blower assembly out too far, it could put excessive strain on the cables. 3. Remove the retaining screw from the connection board cover. 22 5680 011 - 24 4. Remove cover. Viessmann AirflowPLUS AH2A Installation, Operating and Service Installation Vitodens 100 B1HA/B1KA Wiring Viessmann AirflowPLUS Connection Board Thermostat Vitodens 100 B1HA/B1KA 5680 011 - 24 For more details, refer to the Vitodens 100-W Installation Instructions. Connect call for heat (K2) relay of the air handler to the OT connection (X21 terminals 1 and 2) of the Vitodens 100 B1HA/B1KA control. 23 Installation Viessmann AirflowPLUS AH2A Installation, Operating and Service Vitodens 100 B1HE, B1KE 24 Connect call for heat (K2) relay of the air handler to the 96 connection of the Vitodens on the WP board. 5680 011 - 24 For more details, refer to the Vitodens 100-W Installation Instructions. Viessmann AirflowPLUS AH2A Installation, Operating and Service Installation HO1B Wiring Viessmann AirflowPLUS Connection Board Thermostat HO1B Connections (Vitodens 200-W B2HA and B2HB Vitodens 222-F B2TA and B2TB Vitocrossal 300 CU3A) 5680 011 - 24 Refer to the appropriate boiler Installation Instructions. Connect call for heat (K2) relay of the air handler to terminals DE1 of the integrated EA1 module. For coding and programming requirements refer to page 40. 25 Installation Viessmann AirflowPLUS AH2A Installation, Operating and Service For more details, refer to the Vitodens 200-W Installation Instructions. 26 Connect call for heat relay K2 of the air handler to the 96 connection of the WP board or zone inputs 1, 2 and 3 of the MZ10 board. 5680 011 - 24 Vitodens 200 B2HE Wiring Viessmann AirflowPLUS AH2A Installation, Operating and Service Installation Control Function Temperature sensors The Viessmann AirflowPLUS integrated Control includes five temperature sensors. Temperature sensors are 2-wire devices that are connected to the control board with a two pin connector allowing field replacement of individual sensors. Circulator The circulator connection will support up to 5A 115VAC pump motors, activated by control logic on call for heat. Air conditioning relay (24VAC) The Air Conditioning relay is on when the A/C cooling function should be active. It is a 24VAC signal that will energize the A/C power contactor. Fan relay (24VAC 5A Max dry contact) The fan relay is on at any time the fan is running. The relay presents a contact closure that may be used to activate external air cleaners, humidifiers, etc that should be active while the fan is running. Heat relay (24VAC 5A Max dry contact) The heat relay is on when the thermostat calls for heat. Alarm relay (24VAC 5A Max dry contact) The alarm relay provides a dry contact closure that is used to indicate an alarm condition. The contacts are closed during an alarm condition. The alarm relay contacts may be used to activate an external device to alert the user that an alarm condition exists. Alarm conditions include: • Heat exchanger freeze protection limit exceeded • Return air temperature is too low Supply Water Temperature (T1) The sensor is mounted at the supply side of the water heating coil. Freeze Protection Temperature (T3) The sensor will be mounted above the hydronic heat exchanger to detect freezing temperatures from the A/C heat exchanger that could damage the water heat exchanger. The supply air is also monitored during the cooling mode. A/C Discharge Air Temperature (T4) 5680 011 - 24 The sensor is installed in the supply air path of the Air Handler, downstream of the air handler and/or air conditioning assembly. Refer to pages 14 and 15. 27 Installation Viessmann AirflowPLUS AH2A Installation, Operating and Service Remote Return Air Sensor (T5) Remote return air sensor installation Note: If the A/C coil is installed in the return air plenum. • The remote return air sensor must be installed. This sensor is then inserted into the return air duct at a location approximately 15 in. (380 mm) upstream of the A/C coil. (Pages 14 and 15) • Set dip switches as per the system preference. The remote return air sensor is preinstalled within the Viessmann AirflowPLUS cabinet complete with a 10 ft. (3 m) cable lead for remote sensor locations. Remove the strap from the sensor lead and install in the required location. Ambient Sensor (T6) It should be noted that this is a precautionary measure and is not designed to prevent water line freezing in situations where the ambient temperatures may get too low. The ambient sensor provides air handler operation when ambient temperatures outside of the air handler cabinet are less than 40°F (4°C). When the temperature rises above 41°F (5°C) the system will resume normal operation. The sensor connector is plugged onto the control board and routed through the cabinet fan tray openings up to the top panel. Sensor Locations 28 5680 011 - 24 Legend A Supply water temperature B Ambient temperature C Return air temperature D Supply air temperature E Remote air temperature (not shown) Installation Viessmann AirflowPLUS AH2A Installation, Operating and Service S1 Dip Switch Settings Dip switches S2 (in the image below) are shown in the factory setting. Note: The black squares represent the switch positions. Dip switch settings The dip switch will allow the selection of custom setup options. Refer to Variable Table for system options. Maximum heating override The return air temperature will be monitored for unreasonably high values. When the upper limit is reached the unit will override the thermostat and maintain the temperature at the set value. Minimum cooling override The return air temperature will be monitored for unreasonably low values. When the lower limit is reached the unit will override the thermostat and maintain the temperature at the set value. IMPORTANT Start-up: Do not power the unit until the water supply has been connected and the system purged of air. The circulating pump may come on at anytime. Dry operation of the pump will damage the pump and void warranty. Note: To access the connections board see pages 17 and 21. Dip Switch S1 Maximum heating override Dip Switch S1 Minimum cooling override 90°F (32°C) 12 65°F (18°C) 34 85°F (29.5°C) 12 68°F (20°C) 34 80°F (26.5°C) 12 70°F (21°C) 34 75°F (24°C) 12 Note: Power to the Viessmann AirflowPLUS air handler must be turned off before changing switch settings. Note: Factory settings are shown in the grey areas of both charts. 72°F (22°C) 34 System select dip switch settings Four system settings are available. Two for use when the evaporator is in the supply air stream, two for use when the evaporator is in the discharge air stream. In each configuration, the hot water threshold of 85°F or 110°F (29°C or 43°C) may be selected, this ensures that only warm air is available during heating operations. Dip Switch S1 System Settings Evaporator in Supply Air / 110°F (43°C) 5678 Evaporator in Return Air / 110°F (43°C) 5678 5680 011 - 24 Evaporator in Supply Air / 85°F (29°C) 5678 Evaporator in Return Air / 85°F (29°C) 5678 29 Installation Viessmann AirflowPLUS AH2A Installation, Operating and Service Door Safety Switch 30 5680 011 - 24 The door safety switch is located on the internal center support panel. Once the lower front panel is removed, the switch will disconnect power to the control board and fan motor. Installation Viessmann AirflowPLUS AH2A Installation, Operating and Service Electrical Thermostat Most standard heat/cool, setback, or electronic thermostats are compatible with the Viessmann AirflowPLUS AH2A series air handlers. Thermostat wire from the thermostat is connected to the screw terminals located on the control board inside the air handler. They should be connected as follows: RH, RC – power (24VAC) W – heating Y – cooling (if present) G – continuous run fan (if present on thermostat) Note: During continuous fan operation, the fan speed will operate at 40% of the set cooling speed. IMPORTANT A/C condenser must be connected to position “AC relay -Y-C” only. Improper connections will result in loss of protection functions. 24VAC COM 24VAC Fan Speed Stage 2 Cool Stage 1 Cool Stage 1 Heat Viessmann AirflowPLUS Connection Board 5680 011 - 24 Single stage thermostat field supplied (typical) Dry Contacts A/C Relay Heat Fan Alarm Note: Before making the connection to the thermostat for a two stage cooling function, remove the jumper across terminals Y1 and Y2 on the Viessmann AirflowPLUS connection board. 31 Installation Viessmann AirflowPLUS AH2A Installation, Operating and Service Power Supply WARNING WARNING If system components are not grounded, serious injury from electric current can result if an electrical fault occurs. Connect the appliance and pipework to the equipotential bonding of the building in question. Power connections L and N are not interchangeable. Main power supply 120VAC, 1Ph, 60Hz, 12A Main Disconnect Switch WARNING Incorrectly executed electrical installations can lead to injuries from electrical current and result in appliance damage. External Connections Internal Connections > Power Connection Terminal Door Safety Switch AC Line Viessmann AirflowPLUS Connection Board PMP XFO XFI ECM Power 32 5680 011 - 24 ECM Control Viessmann AirflowPLUS AH2A Installation, Operating and Service Installation Control Inputs Heating control A 24VAC input is provided to control the heating function. When the thermostat calls for heat 24VAC is applied to the W contact and a heating cycle will be initiated. Note: the heating cycle control will be ignored while a cooling cycle is in progress. If the heating control is turned off during the initial heat exchanger warm up or during the fan cycle up to speed the heat mode will be terminated with a short run period for the fan prior to shutting down. When thermostat changes off to on: Initially pump speed is active, Fan is off. Provide time for heating coil to warm up. After 15 sec. the fan will active at normal operating speed as set up by the selected dip switch settings. See setting fan speed pages 33, 34 and 35. Cooling control A 24VAC input is provided to control the cooling function. When the thermostat calls for cooling 24VAC is applied to the Y contact and a cooling cycle will be initiated. Note: the heating cycle control will be ignored while a cooling cycle is in progress. If the cooling control is turned off during the fan cycle up to speed period the cool mode will be terminated without an end of cycle fan period. 5680 011 - 24 Thermostat fan on/auto control The 24VAC Thermostat Fan On/Auto input will select the fan operation. When the thermostat is in the Auto state the fan will be off while not heating/cooling. In the fan ON position, 24V is applied to the G contact and the fan will run at the lowest speed while not heating/cooling. During a heating cycle the fan is always off during the initial heat exchanger warm up period. 33 Installation Viessmann AirflowPLUS AH2A Installation, Operating and Service Setting Fan Speed Dip switches S2 (in the image below) are shown in the factory setting. Note: The black squares represent the switch positions. AH2A-213 Viessmann AirflowPLUS Air Handler 1/3 hp ECM - air flow selectable options Example: 12345678 This example shows the factory setting with a heating fan speed of 1155 CFM (Nominal+10%) a cooling fan speed of 1290 CFM (Nominal+10%) and the cooling fan speed profile see chart below for delay. Both the heating and cooling fan speeds must be selected from dip switch S2 adjustment (Nominal+10%, Nominal or Nominal -10%). Note: To access the connections board see pages 17 and 21. Legend H Heat A Adjustment C Cooling D Delay Dip Switch S2 Heating fan speed Dip Switch S2 Adjustment Dip Switch S2 Cooling fan speed 12 12 12 12 Nominal 3 4 +10% 1155 CFM 910 CFM 740 CFM 605 CFM Nominal 1050 CFM 825 CFM 675 CFM Nominal -10% 924 CFM 726 CFM 594 CFM 34 34 Dip Switch S2 Delay 56 56 56 56 1290 CFM 1010 CFM 825 CFM 660 CFM 550 CFM 1175 CFM 925 CFM 750 CFM 600 CFM 484 CFM 1034 CFM 814 CFM 660 CFM 528 CFM Dip Switch S2 Cooling Fan Speed Profiles Pre-Run Time Motor percent Short Run Time Motor percent Motor OFF Time Motor percent 5 min. 82% 2 min. 88% 2 min. 75% 3 min. 82% 2 min. 88% 2 min. 75% 2 min. 82% -- -- 4 min. 75% -- -- -- -- 4 min. 75% 78 78 78 Note: for two stage cooling the first sage (Y1) is approximately 65% of maximum speed, a fan only call is approximately 40% of cool speed. Note: Power to the Viessmann AirflowPLUS air handler must be turned off before changing switch settings. The above values are approximations only, actual results may vary. Note: Factory settings are shown in the grey areas in the charts above. 34 5680 011 - 24 78 Installation Viessmann AirflowPLUS AH2A Installation, Operating and Service Setting Fan Speed (continued) Dip switches S2 (in the image below) are shown in the factory setting. Note: The black squares represent the switch positions. AH2A-354 Viessmann AirflowPLUS Air Handler 1/2 hp ECM - Air Flow Selectable Options Example: 12345678 This example shows the factory setting with a heating fan speed of 1430 CFM (Nominal+10%) a cooling fan speed of 1804 CFM (Nominal+10%) and the cooling fan speed profile see chart below for delay. Both heating and cooling fan speeds must be selected from dip switch S2 adjustment (Nominal+10%, Nominal or Nominal -10%). Note: To access the connections board see pages 17 and 21. Legend H Heat A Adjustment C Cooling D Delay Dip Switch S2 Heating fan speed Dip Switch S2 Adjustment 12 12 1430 CFM 1050 CFM 830 CFM 830 CFM Nominal 1300 CFM 980 CFM 760 CFM 5760 CFM 1640 CFM 1270 CFM 980 CFM 740 CFM Nominal -10% 1140 CFM 860 CFM 660 CFM 660 CFM 860 CFM 650 CFM Nominal 3 4 +10% 34 34 Dip Switch S2 Delay 12 12 Dip Switch S2 Cooling fan speed 56 56 56 1804 CFM 1400 CFM 1050 CFM 1440 CFM 1100 CFM 56 800 CFM Dip Switch S2 Cooling Fan Speed Profiles Pre-Run Time Motor percent Short Run Time Motor percent Motor OFF Time Motor percent 5 min. 82% 2 min. 88% 2 min. 75% 3 min. 82% 2 min. 88% 2 min. 75% 2 min. 82% -- -- 4 min. 75% -- -- -- -- 4 min. 75% 78 78 78 5680 011 - 24 78 Note: for two stage cooling the first sage (Y1) is approximately 65% of maximum speed, a fan only call is approximately 40% of cool speed. Note: Power to the Viessmann AirflowPLUS air handler must be turned off before changing switch settings. The above values are approximations only, actual results may vary. Note: Factory settings are shown in the grey areas in the charts above. 35 Installation Viessmann AirflowPLUS AH2A Installation, Operating and Service Setting Fan Speed (continued) Dip switches S2 (in the image below) are shown in the factory setting. Note: The black squares represent the switch positions. AH2A-385 Viessmann AirflowPLUS Air Handler 3/4 hp ECM - Air Flow Selectable Options Example: 12345678 This example shows the factory setting with a heating fan speed of 1800 CFM (Nominal+10%) a cooling fan speed of 2060 CFM (Nominal+10%) and the cooling fan speed profile see chart below for delay. Both heating and cooling fan speeds must be selected from dip switch S2 adjustment (Nominal+10%, Nominal or Nominal -10%). Note: To access the connections board see pages 17 and 21. Legend H Heat A Adjustment C Cooling D Delay Dip Switch S2 Heating fan speed Dip Switch S2 Adjustment 12 12 12 Dip Switch S2 Cooling fan speed 12 56 56 56 56 Nominal 3 4 +10% 1800 CFM 1750 CFM 1620 CFM 1450 CFM 2060 CFM 1900 CFM 1780 CFM 1650 CFM Nominal 1650 CFM 1590 CFM 1470 CFM 1320 CFM 1875 CFM 1730 CFM 1620 CFM 1500 CFM Nominal -10% 1480 CFM 1430 CFM 1320 CFM 1180 CFM 1680 CFM 1560 CFM 1450 CFM 1350 CFM 34 34 Dip Switch S2 Delay Dip Switch S2 Cooling Fan Speed Profiles Pre-Run Time Motor percent Short Run Time Motor percent Motor OFF Time Motor percent 5 min. 82% 2 min. 88% 2 min. 75% 3 min. 82% 2 min. 88% 2 min. 75% 2 min. 82% -- -- 4 min. 75% -- -- -- -- 4 min. 75% 78 78 78 Note: for two stage cooling the first sage (Y1) is approximately 65% of maximum speed, a fan only call is approximately 40% of cool speed. Note: Power to the Viessmann AirflowPLUS air handler must be turned off before changing switch settings. The above values are approximations only, actual results may vary. Note: Factory settings are shown in the grey areas in the charts above. 36 5680 011 - 24 78 Viessmann AirflowPLUS AH2A Installation, Operating and Service Startup Quick Check WARNING This appliance is not intended for installation in a non conditioned space where the potential may exist for the water and or drain lines to freeze. 1. Is the purge valve installed on the return line from the air handler upstream from the isolation valve? 2. Is the air handler hung and isolated to avoid transmitting vibration through framing and duct work? 3. Full port isolation valves MUST be provided. Restrictive valves will limit performance. 4. Is outdoor cooling unit contactor wired to screw terminals on controller to provide hard-start protection? 5. Are thermostat connections correct, including cooling and continuous run connections? 6. Have the packing materials been removed from the blower and the pump? 7. Is there an installation manual for the home owner? 8. Is the unit accessible? Are there clearances for service and component replacement? 9. Is the supply air temperature stream sensor mounted downstream of the cooling coil? 10. Is the remote return air sensor installed upstream of the A/C coil if the A/C coil is in the return air duct? Refer to page 16. 11. Are the supply air plenum and return duct/drop acoustically lined? [at least 6 ft. (1.8 m)] of the return duct/drop must be lined in addition to the supply plenum). 12. Is the filter cover in place? Is a clean filter in place? Is the supplied filter rack installed? 13. If this appliance is installed with air conditioning, the A/C refrigerant charge and system operation must be verified by a certified/ licensed mechanic prior to commissioning. Pre-start Checklist 1) REMOVE PACKING MATERIALS FROM LEFT SIDE OF BLOWER 2) ONLY IN HORIZONTAL CONFIGURATIONS REMOVE THE PACKING IN THE WATER LINE. 3) BLEED ALL AIR FROM WATER LINES 4) BLEED AIR FROM END OF CIRCULATOR AT SLOTTED BLEED SCREW GENTLY OPEN BLEED SCREW ABOUT 1/2 TURN UNTIL AIR BLEEDS OUT ENSURE WATER DOES NOT LEAK ONTO CONTROL BOARD IN FAN COMPARTMENT 5) DISCHARGE AIR SENSOR INSTALLED DOWNSTREAM OF A/C COIL WHEN A/C COIL INSTALLED IN SUPPLY DUCT DOWNSTREAM OF AIR HANDLER. REFER TO INSTALLATION INSTRUCTIONS. OR REMOTE RETURN AIR SENSOR INSTALLED UPSTREAM OF A/C COIL IF COIL IS INSTALLED IN RETURN AIR DUCT, UPSTREAM OF AIR HANDLER. OR IF A/C COIL IS INSTALLED IN RETURN AIR DUCT UPSTREAM OF AIR HANDLER, AIR FILTER IS INSTALLED UPSTREAM OF A/C COIL 6) INITIATE CALL FOR HEAT, PUMP TURNS ON FAN TURNS ON 7) DISCONNECT POWER TO OUTDOOR CONDENSER. INITIATE CALL FOR COOLING, ONCE FAN IS RUNNING, CONFIRM 24 VOLT OUTPUT AT Y AND C AT COM RELAY ON MAIN CONTROL. RECONNECT POWER IF TEST SUCCESSFUL 5680 011 - 24 8) CANCEL CALL FOR COOLING APPROXIMATELY 1 MINUTE LATER, FAN TURNS OFF 37 Startup Viessmann AirflowPLUS AH2A Installation, Operating and Service Startup Procedure Do not start the air handler or BOILER until ALL Air has been purged from water lines and air handler pump! 1. Fill the boiler loop with water, but do not start it. 5. Start the boiler according to the instructions provided with the boiler. Set the design water temperature and wait for the system to shut off. 2. Purge all air from the heating boiler. 6. Turn on the power to the air handler and set the room thermostat for heat to energize the fan and pump. If a gurgling sound is present, it should subside within one minute. If noise is still present after one minute, repeat step 3 to purge air as necessary. 3. Purge all air from the space-heating loop by closing the isolation valve on the return leg of the loop and open the drain to purge air. Open the return leg isolation valve and then close the drain valve. 4. When there is no bleed screw, we recommend running on high speed #3 for approximately b to 1 minute. If this does not work and you can still hear a ‘swooshing/swirling’ at the pump, then attempt to pulse the air out of the pump by going back and forth between high speed and low speed, 10 seconds on each speed for about 1 minute and that should eliminate the air within the pump. 7. Check supply and return pipes for temperature differences to make sure there is flow. There should be a noticeable difference in temperature between supply and return lines. Air Handler LED Indications for Temperature Temperature for 5 sensors The Air Handler allows the attachment of up to five sensors. The LED sequence for displaying five sensors uses a bicolor LED to indicate the sensor number followed by the sensor temperature reading. The sequence starts with a one red blink to indicate sensor T1, this is followed by the temperature indication using green blinks as described above. This is followed by a 2-blink red LED indication for system select. This is followed by a 3 blink red LED indication for sensor T3. This is followed by the T3 temperature reading using green blinks. This continues up to 6 red blinks indicating the reading for sensor T6. After a short delay sequence begins again with 1 red blink. For example, if sensor T1 is reading 59°F (15°C) and sensor T3 is reading 75°F (24°C) the sequence will start with 1 red blink (sensor T1), 1 green blink, 5 green blinks, 2 red blinks (sensor T3), 2 green blinks, 4 green blinks. The sequence will continue to indicate the temperature, or status, of sensor T4 through T6. First Series of Red Flash(es) Normal temperature indication The LED will blink to indicate temperatures between 32°F and 176°F (0°C and 80°C). When the temperature is below 32°F (0°C) it will indicate 0°C. When the temperature is above 176°F (80°C) it will indicate 80°C. Refer to page 38 for fahrenheit conversion. The temperature is indicated by blinking the most significant digit followed by the least significant digit. If the temperature is 79°F (26°C) the led will blink 2 times, short delay, then 6 times. When the least significant digit of the temperature is 32°F (0°C), the blink indication will substitute 1. If the temperature is 86°F (30°C) the LED will blink 3-1, if it is 122°F (50°C) it will blink 5-1. If the temperature is between 32°F and 48°F (0°C and 9°C), the LED will blink only the least significant digit, that is, if the temperature is 43°F (6°C) the LED will only blink 6 times. If the temperature is 32°F (0°C), a 1 will be substituted, and the LED will blink 1 time. Sensor Second Series of Red Flash(es) 1 1 sec. pause T1 Heating Coil Inlet Water Temperature 3 T3 Heating Coil Freeze Protection Temperature First digit of temperature reading 4 T4 Supply Air Temperature 5 T5 Return Air Temperature 6 T6 Ambient Air Temperature Green Flash(es) 1 sec. pause Second digit of temperature reading 38 5680 011 - 24 Example: 3 Red followed by 5 green is 35°C Viessmann AirflowPLUS AH2A Installation, Operating and Service Startup Installing Connection Board Installing connection board with hinged cover 1. Close connection board cover. 2. Secure cover with the retaining screws. 3. Slide in blower assembly. 4. Reinstall retaining screw. OR Installing connection board with removable cover 1. Install the connection board cover. 2. Secure cover with retaining screw. 3. Slide in blower assembly. 4. Reinstall retaining screw. Installing the Access Panels 1. Set the top of the upper front cover in place and slide up. 2. Reinstall retaining screws. 3. Set the bottom of the lower front panel in place and slide up. 5680 011 - 24 4. Reinstall retaining screws. 39 Operation Viessmann AirflowPLUS AH2A Installation, Operating and Service Indicators A bicolor LED is used as a system status indicator to indicate alarm, test mode, normal operation, etc. The indicator will display the temperature sensor values during normal operation. When abnormal behavior is noted the LED will display an indication to indicate the condition. Flashing LED °F = °C x 1.8 + 32 e.g. 24 x 1.8 + 32 = 75.2°F During normal operating mode the LED will blink to indicate the temperature reading of the five sensors. The LED will blink RED to indicate the sensor number. It will then blink the temperature in GREEN. All temperature readings are in Celsius. Example, while sensor T3 is reading 75°F (24°C) the LED will blink RED 3X then GREEN 2X then GREEN 4X then RED 4X followed by the reading for the next sensor, see LED chart on page 37. LED flash code will indicate the sensor location in RED and temperature in GREEN. e.g. 3RED then 2GREEN, pause, 4GREEN = Sensor T3 is 75°F (24°C) • An 8RED then 8RED flash indicates a bad reading or defective sensor, this may repeat several cycles. Note: If a defective sensor is present, the audible alarm will sound. For corrective action refer to troubleshooting. Sensor 1 should see GREEN flashes of 4GREEN – 3GREEN 110°F (43°C) to 8GREEN –2GREEN 180°F (82°C) depending on the temperature of the hot water source. With 120°F (49°C) to 180°F (82°C) entering water the reading would be 3GREEN – 6GREEN 97°F (36°C) to 7GREEN – 1GREEN 160°F (71°C), after the correct number of red flashes to indicate the sensor #. Refer to page 26 and 27 for sensor numbers and description. 40 5680 011 - 24 Anytime a fault condition exist, the specific fault condition will be displayed represented by a specific LED flash code (refer to page 43) approximately 2 seconds after the display of temperature reading for temperature sensor T6. Viessmann AirflowPLUS AH2A Installation, Operating and Service Operation Normal Operation Heating mode On a call for heat from the thermostat, the circulating pump will turn on. Giving the pump 15 sec. to heat the coil, the fan will activate heating the home until the thermostat is satisfied. Once the thermostat is satisfied, the circulating pump will shut down and fan will continue to run for 2 min. During the heating cycle the hot water temperature is monitored. If the hot water temperature drops below a threshold the fan will be turned off. The hot water temperature continues to be monitored after the fan is shut off. When the temperature rises to 10°F (6°C) above the selected threshold the fan will be restarted. The threshold may be set according to the system select switch. The threshold may be set at 110°F or 85°F (43°C or 29°C) Cooling mode On a call for cooling from the thermostat, if the fan is on, it will turn off and the A/C relay will be energized. The outdoor condenser will turn on and flood the evaporator coil with refrigerant. The fan will turn on and deliver cool air to the system. After approximately 5 min. (this gives the condenser and coil time to normalize pressures), the microprocessor control will cause multiple fan speed adjustments in order to target the latent load first (humidity) before speeding up to capture the sensible load. Sensor feedback allows this enhanced blower fan feature to protect the outdoor unit from refrigerant slugging caused by lower fan speeds, dirty filters, poor duct design or poor installations. Summary In heating mode, most error codes and/or improper unit operation are caused by too low of supply water temperature or sensors not installed correctly. Cooling mode errors are caused by too low or too high of refrigerant charge or gross over sizing of equipment. External Heat Demand via Switching Contact - Boilers equipped with HO1B User Interface Contact closed: 5680 011 - 24 Set address 3A to 3A:2, for external demand upon closure of DE1. • The burner is switched ON subject to load. The boiler heats to the set boiler water temperature selected in coding “9b” in the “General” group. Limiting the boiler water temperature by means of the set boiler water temperature and the electronic maximum limit of the boiler water temperature (coding “06” in the “Combustion Controller” group) 41 Service Viessmann AirflowPLUS AH2A Installation, Operating and Service Illuminated Alarm Indicator • All Viessmann AirflowPLUS AH2A series air handlers are equipped with a housing mounted Illuminated alarm indicator. This indicator light illuminates any time the control mounted alarm relay is activated. • The control mounted alarm relay is turned on under the following circumstances. 1) Home freeze protect Automatic Home Freeze Protection is initiated when the ambient air temperature reads lower than 40°F (4°C). During this time the alarm relay and heat cycle are turned on until the ambient temperature rises above 54°F (12°C). 2) Temperature sensor failure If a sensor has a bad read, or is malfunctioning, the LED will blink RED 8X-8X rather than the green temperature reading. This 8X blink may repeat. Be sure to cycle through all sensors at least three times to determine is a sensor is faulty. 42 5680 011 - 24 Legend A Ambient air temperature sensor B Indicator light Service Viessmann AirflowPLUS AH2A Installation, Operating and Service Alarm Relay and LED Fault Codes Control LED flash codes A visual display is provided by the housing mounted LED. This display advises of the current status of the air handler behavior and its environment should unusual conditions exist. Refer to the chart below. When multiple flash codes are being displayed, they will be displayed in the following order: Flash Code RRR RRG RGG Explanation Cooling Lockout Freeze protect cycle in process Low ambient temperature Cause Page 42 Page 42 Page 42 R = Red G = Green Alarm Buzzer Sounding RED LED Sensor Indication YES Followed by: Alarm Alarm Relay is on when an unusual condition is detected. The connector is a two terminal connector that provides a contact closure when the Alarm Relay is on. It can be silenced again by turning power to the unit off and on. An alarm condition does not mean the unit is not working, it just means the information the control is receiving does not meet specifications. These conditions could be cool supply water, supply air temperature too cold, room air too cold, etc. The alarm will shut off when the condition is corrected. Note: There must be 1 sensor on all inputs in the proper locations. If A/C coil is in the return air plenum then the return MUST be installed on the board at the RETURN AIR receptacle with the sensor lead end located 15 in. (381 mm) upstream of the A/C coil in the return air duct. The supply air sensor (supplied) shall be installed downstream of the heating coil in the supply air ductwork and attached to the SUPPLY AIR receptacle location on the control. Refer to pages 26 and 27 for detailed sensor information. LED Flash Code Reason 3 flashes (Freeze Sensor) 7 green flashes, then 7 green flashes Water coil Freeze Sensor temperature or Supply Air Sensor limit exceeded – inadequate air flow, A/C locked on. YES 4 flashes (Supply Air Sensor) 7 green flashes, then 7 green flashes Water coil Freeze Sensor temperature or Supply Air Sensor limit exceeded – inadequate air flow, A/C locked on. YES 1, 3, 4, 5 or 6 flashes 8 red flashes, then 8 red flashes Temperature Sensor misread, wait for next indication. YES 1, 3, 4, 5 or 6 flashes 8 red flashes, then 8 red flashes Failed Temperature Sensor. Replace. 5680 011 - 24 Temperature Sensor RED LED Flash Code Identification 1 Flashes Water In Temperature Sensor 3 Flashes Water Coil Freeze Temperature Sensor 4 Flashes Supply Air Temperature Sensor 5 Flashes Return Air Sensor 6 Flashes Ambient Temperature Sensor 43 Service Viessmann AirflowPLUS AH2A Installation, Operating and Service Checking ECM (DC) Fan Motor Connections Note: The fan motor operates independent of the controller temperature control logic. Externally installed temperature sensors operate as system safeties only. ECM Motor Control Connector (female) Control (male) 44 5680 011 - 24 Pin number 1 Common C1 2 W/W1 3 Common C2 4 Delay tap select 5 Cool tap select 6 Y1 7 Adjust tap select 8 Output 9 Return (reversing) valve (heat pump only) 10 Humidistat (BK) 11 Heat tap select 12 24VAC (R) 13 2nd stage heat (EM/W2) 14 2nd stage cool (Y/Y2) 15 Fan (G) 16 Output + Viessmann AirflowPLUS AH2A Installation, Operating and Service Service Troubleshooting Power is on at the air handler. Yes Air handler ambient air sensor is activated by a temperature, less than 40°F (4°C). Yes The red light is illuminated on the housing. Yes The internal pump and circulation fan is running. Yes The air handler is in home freeze protect mode. Once return air exceeds 45°F (7°C), pump, fan and red light will turn off. Pump does not run Often, closing the isolation valve on the return leg and opening the drain port so that water flows through the pump can free the pump. For the integrated Grundfos pumps, remove the screw-on cover from the face of the pump, and rotate the shaft one turn with a slotted screwdriver. If either method fails to free the pump, removal for cleaning or replacement is necessary. The pump exercise function will help prevent pump seizing. Pump is noisy at start-up Air is present in heating loop. If sound has not diminished within 1 minute, purge air in accordance with the Start-Up procedures. Insufficient or no heat - Plugged air filter or coil. Refer to Maintenance section for filter care and coil cleaning. - Air in heating loop; purge system. - Inlet and outlet connections to air handler backwards; reverse connections. - Supply water temperature set too low or not calibrated properly; check water temperature. - Restriction in heating loop; remove restrictions, check valves stick, valves too restrictive, left partially closed after purging or closed valve (no or improper flow). Fan runs for cooling but not for heating Room thermostat may be connected improperly. Heating during standby mode Probable cause is thermal Siphoning. See check valve description for details; repair or replace check valve. 5680 011 - 24 Home freeze protection This sequence is initiated by extreme low air temperatures [less than 40°F (4°C)] and are detected by the ambient air temperature sensor. 45 Service Viessmann AirflowPLUS AH2A Installation, Operating and Service Troubleshooting (continued) Water coil freeze protection This sequence is initiated by extreme low air temperatures crossing over the freeze protection sensor located directly above the air handler water coil. The air handler internal water coil freeze sensor T3 is activated by low air temperature. Yes Housing mounted LED is illuminated. Yes Yes The air handler internal water coil freeze sensor T3 is activated by low air temperature. Continue 46 Yes Refer to cooling lockout chart. 5680 011 - 24 Check for poor air flow, restrictions, plugged filters, low refrigerant charge Viessmann AirflowPLUS AH2A Installation, Operating and Service Service Troubleshooting (continued) Cooling lockout This feature is initiated if three freeze protect cycles occur within a single cooling cycle or, if three freeze cycles occur when a cooling cycle is not in progress. A freeze protect cycle is when the air handler integral A/C coil freeze sensor is triggered by unacceptably low supply air temperatures. Power is on at the air handler. Yes The air handler internal water coil freeze sensor is activated by three extreme low temperature cycles. Yes The red light is illuminated on the housing. Yes Observe each sensor code and record related flash codes as shown on the housing mounted LED. Refer to page 43. Yes Sensor T3 flash code indicates 7 green then 7 green. Yes 5680 011 - 24 Inadequate air flow, plugged filter, extreme ESP, low refrigerant. No Outdoor ambient or thermostat set too low. 47 Service Viessmann AirflowPLUS AH2A Installation, Operating and Service Troubleshooting (continued) Temperature sensor failure identification Temperature sensor failure is identified by viewing the housing mounted LED. Power is on at the air handler for more than 24 hours. Yes No The red housing mounted LED is illuminated after 5 minutes of power on. Yes The housing mounted LED will flash an error code. Record colors and number of flashes (5 cycles/min). Refer to chart on page 43 for identification. Continue 48 5680 011 - 24 If 8 red flashes followed by 8 red flashes repeats after a specific sensor, then replace that sensor. Service Viessmann AirflowPLUS AH2A Installation, Operating and Service Service and Maintenance Resistance in k Ohms Checking temperature sensor 1. Remove cables from temperature sensor. 2. Check the sensor resistance and compare the actual values with the curve in the chart. 3. Replace sensor in case of severe deviation. Temperature sensors Uninstalled sensors Systems may elect to not use one, or more, of the five sensors. In this case, the absent sensor temperature is replaced by one long green blink following the red sensor number blinks. Failed Sensors When a sensor is incorrectly installed or defective, the LED indication will substitute red 8-8 for a normal temperature reading. Air filter The Viessmann AirflowPLUS AH2A series of air handlers are provided with a disposable filter media. This filter should be inspected monthly and removed and replaced as required. Circulator The circulator is water lubricated and should require no regular maintenance. The system control has a pump exercise function during prolonged periods of no heat to avoid seizing from long idle periods. 5680 011 - 24 Coils The heating coil should not require cleaning if the filter maintenance schedule is adhered to. If a filter is damaged or collapses from plugging, dust may foul the coils. If this happens, remove the front covers, replace the filter and carefully vacuum the bottom of the heating coil. During this process, avoid dust from falling into the fan below. 49 Additional Information Viessmann AirflowPLUS AH2A Installation, Operating and Service System Layout 1 Refer to page 25 for the Viessmann AirflowPLUS connection to external heat demand of the boiler. 50 IMPORTANT Please note location of expansion tank. Sizing of field-supplied pumps are critical for proper boiler operation in this system layout. An undersized pump may cause short-cycling and/or improper operation of the boiler. 5680 011 - 24 Legend A Vitocrossal 300 CU3A high mass boiler B System fill with expansion tank C Viessmann AirflowPLUS air handler D Thermostat (field supplied) E Indirect fired DHW storage tank Viessmann AirflowPLUS AH2A Installation, Operating and Service Additional Information System Layout 2 Legend A Vitocrossal 300 CU3A high mass boiler B System fill with expansion tank C High temperature heating loop D Viessmann AirflowPLUS air handler E Thermostat (field supplied) F Low temperature heating loop with mixing valve G Indirect fired DHW storage tank H Low loss header (or closely spaced tees) 5680 011 - 24 Refer to page 25 for the Viessmann AirflowPLUS connection to external heat demand of the boiler. IMPORTANT The use of a low-loss header (or closely spaced tees with a maximum spacing of 4X pipe diameter) is strongly recommended if the maximum water flow rate in the application concerned exceeds the maximum or minimum flow rates of the boiler or if the system flow rates are unknown. The low-loss header is available as accessory part. Please note location of expansion tank. System separation is required of underfloor heating systems employing non-oxygen diffusion barrier tubing. All components on the secondary side of the heat exchanger must be made of corrosion-resistant materials. The 3-way mixing valve, built-in to achieve the low temperature level of the under floor heating circuit, is controlled by an accessory kit for a heating circuit with mixing valve. 51 Additional Information Viessmann AirflowPLUS AH2A Installation, Operating and Service System Layout 3 E Thermostat (field supplied) F Low temperature heating loop with mixing valve G Low loss header (or closely spaced tees) Refer to page 25 for the Viessmann AirflowPLUS connection to external heat demand of the boiler. 52 IMPORTANT The use of a low-loss header (or closely spaced tees with a maximum spacing of 4X pipe diameter) is strongly recommended if the maximum water flow rate in the application concerned exceeds the maximum or minimum flow rates of the boiler, or if the system flow rates are unknown. The low-loss header is available as accessory part. Please note location of expansion tank. System separation is required of underfloor heating systems employing non-oxygen diffusion barrier tubing. All components on the secondary side of the heat exchanger must be made of corrosion-resistant materials. The 3-way mixing valve, built-in to achieve the low temperature level of the under floor heating circuit, is controlled by an accessory kit for a heating circuit with mixing valve. 5680 011 - 24 Legend A Vitodens 222-F B2TA/B boilers B System fill with expansion tank C High temperature heating loop D Viessmann AirflowPLUS air handler Viessmann AirflowPLUS AH2A Installation, Operating and Service Additional Information System Layout 4 Legend A Vitodens 200 B2HA/B boilers B System fill with expansion tank C High temperature heating loop D Viessmann AirflowPLUS air handle E Thermostat (field supplied) F Low temperature heating loop with mixing valve G Indirect fired DHW storage tank H Low loss header (or closely spaced tees) 5680 011 - 24 Refer to page 25 for the Viessmann AirflowPLUS connection to external heat demand of the boiler. IMPORTANT The use of a low-loss header (or closely spaced tees with a maximum spacing of 4X pipe diameter) is strongly recommended if the maximum water flow rate in the application concerned exceeds the maximum or minimum flow rates of the boiler, or if the system flow rates are unknown. The low-loss header is available as accessory part. Please note location of expansion tank. System separation is required of underfloor heating systems employing non-oxygen diffusion barrier tubing. All components on the secondary side of the heat exchanger must be made of corrosion-resistant materials. The 3-way mixing valve, built-in to achieve the low temperature level of the under floor heating circuit, is controlled by an accessory kit for a heating circuit with mixing valve. 53 Additional Information Viessmann AirflowPLUS AH2A Installation, Operating and Service System Layout 5 Note: For installations with multiple air handler units, the call for heat from each air handler must be connected in parallel to the boiler demand. Note: The low loss header is optional with the Vitocrossal 300 CU3A boiler. 54 IMPORTANT The use of a low-loss header (or closely spaced tees with a maximum spacing of 4X pipe diameter is strongly recommended if the maximum water flow rate in the application concerned exceeds the maximum or minimum flow rates of the boiler, or if the system flow rates are unknown. The low-loss header is available as accessory part. Please note location of expansion tank. System separation is required of underfloor heating systems employing non-oxygen diffusion barrier tubing. All components on the secondary side of the heat exchanger must be made of corrosion-resistant materials. The 3-way mixing valve, built-in to achieve the low temperature level of the under floor heating circuit, is controlled by an accessory kit for a heating circuit with mixing valve. 5680 011 - 24 Legend A Vitocrossal 300 CU3A high mass boiler / Vitodens 200 B2HA/B boilers (shown) B System fill with expansion tank C High temperature heating loop D Viessmann AirflowPLUS air handler E Thermostat (field supplied) F Low temperature heating loop with mixing valve G Indirect fired DHW storage tank H Low loss header (or closely spaced tees) Viessmann AirflowPLUS AH2A Installation, Operating and Service Additional Information System Layout 6 Legend A Vitodens 200 B2HA/B boilers B System fill with expansion tank C Thermostat (field supplied) D Viessmann AirflowPLUS air handler E Low loss header (or closely spaced tees) 5680 011 - 24 Refer to page 25 for the Viessmann AirflowPLUS connection to external heat demand of the boiler. IMPORTANT The use of a low-loss header (or closely spaced tees with a maximum spacing of 4X pipe diameter) is strongly recommended if the maximum water flow rate in the application concerned exceeds the maximum or minimum flow rates of the boiler, or if the system flow rates are unknown. The low-loss header is available as accessory part. Please note location of expansion tank. Sizing of field-supplied pumps are critical for proper boiler operation in this system layout. An undersized pump may cause short-cycling and/or improper operation of the boiler. 55 Additional Information Viessmann AirflowPLUS AH2A Installation, Operating and Service System Layout 7 For Vitodens 100 B1HE refer to page 23 for the Viessmann AirflowPLUS connection to OT of the boiler. For Vitodens 100 B1HE refer to page 24. 56 IMPORTANT The use of a low-loss header (or closely spaced tees with a maximum spacing of 4X pipe diameter) is strongly recommended if the maximum water flow rate in the application concerned exceeds the maximum or minimum flow rates of the boiler, or if the system flow rates are unknown. The low-loss header is available as accessory part. Please note location of expansion tank. If the heating system does not include a DHW storage tank connected to the boiler the DHW demand contacts of the boiler may be connected to the Viessmann AirflowPLUS heat demand, use the DHW temperature set point to set the desired supply temperature to the air handler. 5680 011 - 24 Legend A Vitodens 100 B1HA/B1HE boiler B System fill with expansion tank C Viessmann AirflowPLUS air handler D Thermostat (field supplied) F Indirect fired DHW storage tank G Closely spaced tees (optional LLH accessory) Viessmann AirflowPLUS AH2A Installation, Operating and Service Additional Information System Layout 8 Legend A Vitodens 100 B1KA/B1KE boiler B System fill with expansion tank C Viessmann AirflowPLUS air handler D Thermostat (field supplied) E Low loss header (or closely spaced tees) 5680 011 - 24 For Vitodens 100 B1HE refer to page 23 for the Viessmann AirflowPLUS connection to OT of the boiler. For Vitodens 100 B1HE refer to page 24. IMPORTANT The use of a low-loss header (or closely spaced tees with a maximum spacing of 4X pipe diameter) is strongly recommended if the maximum water flow rate in the application concerned exceeds the maximum or minimum flow rates of the boiler, or if the system flow rates are unknown. The low-loss header is available as accessory part. Please note location of expansion tank. 57 Additional Information Viessmann AirflowPLUS AH2A Installation, Operating and Service System Layout 9 Legend A Vitodens 200 B2HE series boiler B System fill with expansion tank C High temperature heating loop D Viessmann AirflowPLUS air handler E Thermostat (field supplied) F Low temperature heating circuit with mixing valve G Low loss header (or closely spaced tees) H DHW tank IMPORTANT The use of a low-loss header (or closely spaced tees with a maximum spacing of 4X pipe diameter) is strongly recommended if the maximum water flow rate in the application concerned exceeds the maximum or minimum flow rates of the boiler, or if the system flow rates are unknown. The low-loss header is available as accessory part. Please note location of expansion tank. 58 5680 011 - 24 Refer to page 26 for the Viessmann AirflowPLUS connections. Viessmann AirflowPLUS AH2A Installation, Operating and Service Additional Information System Layout 10 Legend A Vitodens 200 B2HE series boiler B System fill with expansion tank C High temperature heating loop D Viessmann AirflowPLUS air handler E Thermostat (field supplied) F Low temperature heating circuit with mixing valve G Low loss header (or closely spaced tees) H DHW tank IMPORTANT The use of a low-loss header (or closely spaced tees with a maximum spacing of 4X pipe diameter) is strongly recommended if the maximum water flow rate in the application concerned exceeds the maximum or minimum flow rates of the boiler, or if the system flow rates are unknown. The low-loss header is available as accessory part. Please note location of expansion tank. 5680 011 - 24 Refer to page 26 for the Viessmann AirflowPLUS connections 59 Additional Information Viessmann AirflowPLUS AH2A Installation, Operating and Service Electrical Connections Main power supply 120VAC, 1Ph, 60Hz, 12A WARNING Main Disconnect Switch DISCONNECT POWER BEFORE SERVICING BOILER. External Connections If any of the original wires as supplied with the appliance must be replaced, it must be replaced with the exact equivalent. Internal Connections Power Connection Terminal CAUTION > Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing. Door Safety Switch Viessmann AirflowPLUS Connection Board AC Line PMP XFO XFI ECM Power Thermostat - field supplied (optional two stage cooling shown) 60 Dry Contacts A/C Relay Heat Fan Alarm 5680 011 - 24 24VAC COM 24VAC Fan Speed Stage 2 Cool Stage 1 Cool Stage 1 Heat ECM Control Viessmann AirflowPLUS AH2A Installation, Operating and Service Additional Information Electrical Connections (continued) Legend 1 Diagnostic LED 2 Ambient temperature sensor 3 Return air temperature sensor 4 Supply air temperature sensor 5 Freeze protection temperature sensor 7 Supply water temperature sensor 8 A/C power 9 Pump motor 10 24VAC transformer secondary 11 24VAC transformer primary 12 ECM power 13 ECM control Legend AC Line 1 115VAC line 2 115VAC neutral Pump (PMP) 1 115VAC neutral 2 115VAC line XFO 1 24VAC 2 N/C 3 24VAC-COM (GND) XFI 1 115VAC line 2 115VAC neutral ECM Power 1 N/C 2 N/C 3 N/C ECM Control 1 Common C1 2 W/W1 3 Common C2 4 Delay tap select 5 Cool tap select 6 Y1 7 Adjust tap select 8 Output 9 Return valve (heat pump only) qP Humidistat (BK) qQ Heat tap select qW 24VAC (R) qE 2nd stage heat (EM/W2) qR 2nd stage cool (Y/Y2) qT Fan (G) qZ Output + 5680 011 - 24 4 115VAC neutral 5 115VAC line 61 Additional Information Viessmann AirflowPLUS AH2A Installation, Operating and Service Technical Data Description Motor (ECM) Motor rated amps - loaded (1050 RPM) - locked rotor Electrical Heating BTUH (kW) hp AMPS AMPS VOLTS/PH/HZ 120°F (49°C) 140°F (60°C) 160°F (71°C) 180°F (82°C) Flow Nominal (CFM) Cooling capacity Cabinet Supply air opening Return air opening Weight Circulating pump * Type Volts Motor horsepower Capacitor Motor rated amps - loaded - locked rotor Maximum working pressure Min./max. fluid temperature Hydronic heating coil Construction Rows...fins/in. Total face area Piping connections Supply Return Pressure drop through the coil USG/min (L/H) Heating .5” e.s.p. Cooling .5” e.s.p. Heating .2” e.s.p. Cooling .2” e.s.p. (tons) D x W x H* in. (mm) in. (mm) in. (mm) lb. kg AH2A-213 g 5.0 ** 120/1/60 28,000 (8) 46,000 (13) 62,000 (18) 72,000 (21) 3 (681) 600 700 1,100 1,200 1.5 - 3.0 22c x 18 x 32b (578 x 457 x 825) 16 x 20 (406 x 508) 14 x 18 (356 x 457) 85 (39) AH2A-354 AH2A-385 b c 7.7 9.6 ** ** 120/1/60 120/1/60 44,000 51,000 (13) (15) 61,000 74,000 (18) (22) 83,000 90,000 (24) (26) 98,000 115,000 (29) (33) 5 5 (1135) (1135) 1,200 1,600 1,400 1,800 1,900 1,300 2,100 1,600 2.50 - 4.0 3.5 - 5.0 23 x 22 x 34b 28 x 22 x 34b (584 x 559 x 876) (711 x 559 x 876) 20 x 20 20 x 25 (508 x 508) (508 x 635) 18 x 18 18 x 23 (457 x 457) (457 x 584) 100 110 (45) (50) Grundfos 15/58RU 115 1/25 10/180 0.74 4.44 145 120/200 (49/93) 115 1/25 10/180 0.74 4.44 145 120/200 (49/93) Copper tubing, aluminum fins, galvanized steel support frame 3...12 3...12 sq. ft. (m2) 1.3 (0.12) 2.8 (0.26) 3...12 2.8 (0.26) AC hp MFD/VOLTS AMPS AMPS PSI ºF (ºC) in. in. feet of head [@ 160°F (71°C) supply water temperature] 115 1/25 10/180 0.74 4.44 145 120/200 (49/93) b FIP b FIP c FIP c FIP c FIP c FIP 12 2 2 Permissible ambient temperature Installation in living spaces or boiler rooms (standard ambient conditions; - During operation 32 to 104ºF (0 to +40ºC) - During storage and transport -4 to 149ºF (-20 to +65ºC) 62 5680 011 - 24 * Using the adjustable levelling feet can add up to 1b in. (38 mm) to the height of the air handler. ** If motor speed decreases below the programmed stall speed, the motor will shut down and after a delay period, the control will attempt to restart the motor. Starting current is limited to significantly less than full load current. Viessmann AirflowPLUS AH2A Installation, Operating and Service Additional Information Parts List Model No. AH2A 213 AH2A 354 AH2A 385 Serial No. 7561230 7561231 7561232 Ordering Parts: Please provide Model and Serial Number A when ordering replacement parts. Order replacement components from your Viessmann distributor. Parts 0001 0002 0003 0004 0005 0006 0007 0008 0009 0010 0011 0012 0013 0014 0015 0016 0017 0018 0019 0020 0021 0023 0024 0025 0026 0027 0028 0029 0030 Side panel with return air opening Side panel Front panel, top Front panel, bottom Bracket for air filter Panel, return air Fan motor Circuit board Leveling feet (set of 4) Bracket for fan motor Blower housing Blower wheel Hot water coil Circulation pump head, GF UPS15-58RU Sensor for return air (T5) Sensor for AC discharge air (T4) *1 Sensor for freeze protect (T3) Sensor for supply water (T1) Pump support block Sensor, ambient (T6) Diagnostic LED Door safety switch Terminal block (main power supply) Transformer, 120VAC / 24VAC Filter frame *2 Air filter *3 Power factor correction choke *4 Circuit board enclosure Flow check valve Other Parts (not illustrated) 0022 Sensor clamp 0050 Technical Data Manual 0051 Installation and Operating Instructions 0052 Parts List *1 *2 *3 5680 011 - 24 *4 Sensor installed in downstream plenum. For floor-standing installations only. Please purchase quality replacement air filters from a local hardware store: AH2A 213 16 x 20 in. AH2A 354 20 x 20 in. AH2A 385 20 x 25 in. Only for Model AH2A 385. 63 5680 011 - 24 Technical information subject to change without notice. Printed on environmentally friendly (recycled and recyclable) paper. Viessmann AirflowPLUS AH2A Installation, Operating and Service ">
/
İndir
Sadece dostça bir hatırlatma. Belgeyi buradan görüntüleyebilirsiniz. Ancak en önemlisi, yapay zekamız zaten okudu. Karmaşık şeyleri basit terimlerle açıklayabilir, sorularınızı herhangi bir dilde yanıtlayabilir ve en uzun veya en karmaşık belgelerde bile hızlıca gezinmenize yardımcı olabilir.
Reklam