REACTa
Installation – Commissioning – Maintenance
Installation
Air flow measuring of REACT requires a straight section of duct before the unit (in air flow direction), according to installation figures. Modbus tables are available in a separate document (REACTa_Modbus-m).
Installation – circular version
Legend to figures 3-5:
1. Circular Variable-flow damper REACT
2. Clamp, FSR
3. Sound attenuator with baffle
20160307
Figure 1. Permissible ambient temperature.
Min. 500 mm
Min. 100 mm
Figure 3. Straight section requirements, circular ducts.
Figure 2. Space required for installation.
Figure 4. REACT requires a duct of ~2 x ØD between the REACT and a sound attenuator fitted with baffles. NOTE: Ducts must be fixed on both sides of REACT.
1
REACT
Figure 5. Installation in a duct system. The ducts must be firmly fixed to the frame of the building on each side of the REACT unit.
Installation measurements – circular version
Size
100
125
160
200
250
315
400
A (mm)
472
472
472
472
522
552
695
Inst. measurements (A + 10 mm)
482
482
482
482
532
562
705
500 822 832
Installation – rectangular version
Measurement B in the figure and table below can be found on page 11, in the table; "Dimension, air-flow and k-factors
– rectangular version".
Straight sections before REACT for rectangular ducts
Type of obstruction
One 90°-bend
One T-piece
E (m
2
=5%)
E = 3 x B
E = 3 x B
E (m
2
=10%)
E = 2 x B
E = 2 x B
E
Straight sections before/after REACT –
Sound attenuator with baffles
E
1 2 3
470 mm ≥500 mm
Figure 7. Straight section requirements, rectangular REACT and sound attenuator with baffles. Installation with a length of straight duct applies to both the supply air and the extract air.
1 = Rectangular Variable-flow damper REACT.
2 =
≥ 500 mm length of straight duct.
3 = Sound attenuator with baffles.
E
E = Straight section.
B = Width, duct.
H = Height, duct.
Figure 6. Straight section requirements, rectangular ducts. Dimensions B
and H (B = Width, H = Height) can be read off the label on the delivered
product.
2
Swegon reserves the right to alter the specifications. 20160307 www.swegon.com
REACT
250
315
400
500
100
125
160
200
Dimensions and weights
REACT – circular
Dimensions (mm)
Size
ØD Ød A
125
150
185
225
275
340
425
525
249
314
399
499
99
124
159
199
472
472
472
472
522
552
695
822
C
45
45
57
57
45
45
45
45
3.4
4.4
6.0
9.0
1.9
2.0
2.1
2.3
REACT
Weight (kg)
REACT
GUAC
2,9
3,0
3,1
3,3
4,4
6,0
7,6
10,6
FSR
0.7
0.8
1.2
1.4
0.4
0.4
0.6
0.6
100
Ød
A
C
Figure 8. Circular REACT and REACT MB.
C
Figur 11. Circular REACT GUAC with spring return actuator.
92
Ø d
45
210
Figure 9. REACT CU, circular and rectangular versions.
D d
Figur 10. FSR.
Swegon reserves the right to alter the specifications. 20160307 www.swegon.com
3
REACT
REACT insulated – circular version
Size
250
315
400
500
100
125
160
200
A
45
45
57
57
45
45
45
45
E
Dimensions (mm)
Ød F
305
370
462
563
180
180
215
255
99
124
159
199
249
314
399
499
451
481
595
723
401
401
401
401
G
395
465
553
653
245
245
285
335
Weight
(kg)
4,1
4,3
5,1
6,2
8,2
10,7
15,6
22,4
REACT – rectangular version
Dimensions B and H (B = Width, H = Height), can be found in the table; "Air flows and measures – rectangular version", see page 11.
250
25
220
Figure 14. REACT and REACT MB, rectangular version.
Figure 12. REACT and REACT MB insulated, circular.
REACT insulated GUAC - circular version
Size
100
125
160
200
250
315
400
500
I
242
242
282
332
392
462
550
650
Dimensions (mm)
Ød J K
99
124
159
199
249
314
399
499
472
472
472
472
522
572
684
810
177
177
212
252
302
367
459
558
M
399
399
399
399
449
479
593
721
Weight
(kg)
4,7
4,9
5,7
6,8
8,8
11,3
16,2
23
Figure 15. REACT CU, rectangular version.
250
Figure 13. REACT insulated GUAC - circular design.
4
Swegon reserves the right to alter the specifications.
ød
J
Figure 16. REACT insulated GUAC - circular design.
20160307 www.swegon.com
REACT
Technical data
To obtain the correct functionality. it is very important that the following is taken into account:
• REACT may only be installed in spaces with an ambient temperature in the range 0-50°C.
• All interconnected regulating equipment must have the same polarity. i.e. the neutral wire must be correctly connected.
• The product should always be installed with its flow meter facing downstream, see air direction arrows on the product label.
• REACT is not suitable for use in explosive environments.
• All service must be carried out with the power supply disconnected.
Operating data
Ambient air temperature:
Air-flow temperature:
Running time open/close (90 degrees):
0° – +50°C
0° – +50°C
5 Nm - 100 s
Storage and transport
Ambient temperature:
Electrical data
Supply voltage
-20° – +80°C
24 V AC/DC +-20%, 50/60 Hz
Power consumption. for transformer rating:
REACT 5 Nm 2.5 W
REACT 10 Nm 2,5 W
REACT 15 Nm 3 W
4 VA
4,5 VA
4,5 VA
GUAC DM3 controller 0,6 W
Spring return actuator 5 Nm 6,5 W (standby 2 W)
Spring return actuator 10 Nm 5 W (standby 2 W)
1,3 VA
7,5 VA
8 VA
Mechanical opening/closing of the spring return actuator
Mechanical handling of dampers can only be performed if the actuator is de-energized. The supplied key (attached to the motor cable) or a 2.5 mm hex key, is used for mechanical handling.
Spring return actuators on REACT GUAC are supplied as standard from the factory with the spring return of the damper set to deenergized/closed.
Swegon reserves the right to alter the specifications. 20160307 www.swegon.com
5
REACT
Wiring, standard version
BU-BN – Operating voltage
BU-BK – Control signal
BU-GY – Feedback signal
Load for output GY: max 0.5 mA
24 V AC/DC
0..10/(2..10) V
0..10/(2..10) V
Wiring, Modbus version
BU-BN – Operating voltage
BU-BK – Control signal
BU-GY – Feedback signal
Load for output GY: max 0.5 mA
24 V AC/DC
0..10/(2..10) V
0..10/(2..10) V
5 Nm
3 W 5 VA
100s (90°) 95°
250 Pa max. 100 kPa
1 2 3 4
BU BN BK GY
+
Y U
1 2 3 4
BU BN BK GY
-
+
Y U
0..10 V DC
(2..10 V DC) a. b. c. d. e.
BU = Blue (1)
BN = Brown (2)
BK = Black (3)
GY = Grey (4)
N L
24 V AC/DC
0..10 V DC
(2..10 V DC)
Figure 17. Wiring diagram, standard version.
1 2 3 4
BU BN BK GY WH WH
-
+
Y U
5 Nm
3 W 5 VA
1000s (90°) 95°
2550 Pa max. 100 kPa
1 2 3 4 A B
BU BN BK GY WH WH
+
Y U
0..10 V DC
(2..10 V DC) a. b. c. d. e.
BU = Blue (1)
BN = Brown (2)
BK = Black (3)
GY = Grey (4)
WH = White (A, B)
N L
24 V AC/DC
A B
Modbus
0..10 V DC
(2..10 V DC)
Figure 19. Wiring diagram, Modbus version.
Connection GUAC version
Connections are made in accordance with the left-hand circuit diagram GUAC, see label on the inside of the cover.
1-2 – Operating voltage
1-3 – Control signal
1-4 – Feedback signal
Load for output GY: max 0.5 mA
24 V AC/DC
0..10/(2..10) V
0..10/(2..10) V
NOTE! Electrical connection of the spring-return actuator installed at the factory.
Override control and control signal
Various options for control can be preset.
See the relevant wiring diagram in figure 17-19.
a. Damper opens fully, 24 V AC (positive rectified half-wave). b. V max c. V min
, 24 V AC/DC.
, no signal, Mode: 0..10 V. d. Damper closes fully, ground/earth (-): 0..10 V – CLOSED if V min
= 0. e. Regulation with the control signal, default 0..10 V (alt. 2..10 V).
GUAC
1 2 3 4
+
Y U
0..10 V DC
(2..10 V DC) a. b. c. d. e.
N L
24 V AC/DC
0..10 V DC
(2..10 V DC)
6
Figure 18. Wiring diagram, GUAC version.
Swegon reserves the right to alter the specifications. 20160307 www.swegon.com
3
Test
I/s m /h
REACT
I/s
Test m /h
Flow
Vmin
Adr
Mode
Test
Vmax
1
2
Vnom Flow
Adr Vmin
Mode
Test
Vmax
227VM
3
I/s
Test
4
3 m /h
Test
I/s m /h
Flow
Vnom
Vmin
Vmax
Flow
Adr
Mode
Vmin
Vmax
Figure 20. The REACT interface.
1 – Select desired mode by turning the "Mode" wheel.
2 – Set values and select sub-settings by turning the ”Edit" wheel.
Flow
4 – ”Gear release” button
Adr Vmin
Mode
Test
Vmax
Menus
Vnom
Flow
I/s
Test
Flow
Vnom
I/s
Test
• Toggle between l/s and m 3 /h using the edit wheel.
Adr
Mode
Test
Vmin
Adr
Vmax
Mode
Test
Vmax
Vmin the selected mode.
Vnom Flow
Adr Vmin
Mode
Test
Vmax
Vmin
I/s
Test m /h
• Select new value for Vmin with the edit wheel.
Vnom Flow
Adr Vmin
Mode
Test
Vmax
Vnom
Test
Mode
Adr
Vmax
I/s
Test
Vmax
Vmin
Flow
• Select new value for Vmax with the edit wheel.
• Vmax value should be greater than Vmin
Vnom Flow
Test
I/s
Test m /h
Adr Vmin
Mode
Test
Vmax
Test
Adr
Vmax
Vnom
Vmin m /h st
Te
I/s
on – Test mode is on, damper stays in current position.
oP – Opens the damper fully.
cL – Closes the damper fully.
Lo – Low flow, forces the actuator to Vmin.
Hi – High flow, forces the actuator to Vmax.
123 – Displays current software version.
Vnom Flow
Adr Vmin
Mode
Test
Vmax
Vnom
Vmax
Test
Flow
Vmin
Adr Vmin
Mode
Test
Flow
Vmax
Mode
Adr
Vnom
Mode
I/s
Test
• Displays selected input and reference signal.
• Toggle between 0-10 and 2-10 V using the edit wheel.
Adr
I/s
Test
• Used for Modbus. for particulars on how to use
Modbus, see next page.
Test
Adr
Vnom
Mode
Adr
Flow
Vmin
Mode
Test
Vmax
Vnom
I/s
Test
• Used for factory configuration, for particulars on how to use Modbus, see next page.
Maintenance
REACT is maintenance-free. Cleaning should only be done by vacuuming with a brush nozzle or dry wiping with a damp cloth. When cleaning the duct system, REACT must be dismounted, unless cleaning hatches are situated near the unit. Cleaning tools, such as feather dusters or soft brushes and the like must not be drawn through the damper.
Commissioning – Flows
• REACT is factory-calibrated and preset for a nominal airflow.
• The set values can be read off the product, see label on the product.
• It is extremely important that the requirement for the lengths of straight duct upstream or downstream are complied with.
• Providing only half the required length of straight duct, may result in up to 20% lower accuracy in flow calculations.
Control signals
• REACT is preset for a signal range of 0-10 V DC (can be reset to 2-10 V DC).
• The Control of the air-flow, using a direct-wired room thermostat, is regulated by a control voltage of <0.5V for min. airflow and 10 V for max. airflow.
• When controlled from a HVAC central/controller, min/ max air-flow settings are controlled by limiting the control signal, i.e. 2,3 - 7,6 V DC.
• If wired to a controller, the REACT is normally set to
0-100% of its operating range.
• At 2-10 V control the following applies:
– 0 - 0.8 V closes the damper.
– 0.8 - 2 V controlls the the damper to min. air-flow.
Airflows
• REACT has a nominal air-flow, Q nom
for each size.
• Max. air-flow: 30-100% of Q nom
.
• Min. air-flow: 0-100% of Q nom
.
NOTE: Min. value must always be lower than max value.
• At Q min
a measured pressure of 1 Pa is obtained and a measurement accuracy of ±5-20 % of the flow.
Wiring examples
When REACT is used for constant-flow regulation, only 24
AC is connected to the controller. Below and on page 9-10, different wiring examples are given, showing different types of control configuration.
CAV – Constant-flow regulation
REACT
Y U
227VM SWN
1 2 3 4
N
AC/DC
L
Figure 21. The wiring diagram shows the connections for constantflow regulation. Q
min
= required constant-flow and Q
max
= 0 l/s.
7
Swegon reserves the right to alter the specifications. 20160307 www.swegon.com
10
11
12
13
14
15
16
17
18
Display number
1
2
3
4
5
6
7
8
9
REACT
How to use Modbus
Modbus tables are available in a separate document (REACTa_Modbus-m).
Function
Adr (Modbus only)
V nom
Description
V min
V max
Test
Mode
Adr.
Enables you to set the actuator's Modbus address, by turning the "edit wheel". It is possible to set the address from 1 till 247. If you turn the value selector to end stop "+", the display will show a "2". This makes it possible to select the second level. If you select the second level, this is indicated in the display by a small circle.
The following functions are available at the second level:
Flow Return to previous level
Not used
Normally shows "OFF"
In order to start a test run, you have to turn the mode wheel to "ON".
Shows the angle of the rotation (0…255 digital 0....100%).
V nom
Used for selecting communication settings for Modbus. See table below.
Used for setting response delay for the Modbus communication (see separate documents)
Set V nom
according to the preset values for circular dampers and rectangular dampers according to the specification in Section 4.7, Calibration list. If 999 is shown in the display, it is possible to enter a userspecific V nom
. The V nom
value can only be set using the Gruner winVAV
Software (applies to the 15 Nm version only). No password is required when entering the first settings. After entering the first settings, you must set the password to 201 and wait until the display flashes; then enter another password.
9
10
11
12
13
14
15
16
17
EEPROM value
0
1
2
3
4
5
6
7
8
Communcation speed
1200
1200
1200
2400
2400
2400
4800
4800
4800
9600
9600
9600
19200
19200
19200
38400
38400
38400
None
Even
Odd
None
Even
Odd
None
Even
Odd
Parity
None
Even
Odd
None
Even
Odd
None
Even
Odd
1
2
1
2
1
1
2
1
1
Stopbits
2
1
1
2
1
1
2
1
1
8
Swegon reserves the right to alter the specifications. 20160307 www.swegon.com
Function
Adr (Modbus only)
V nom
Description
V min
V max
Test
Mode
Adr.
Enables you to set the actuator's Modbus address, by turning the "edit wheel". It is possible to set the address from 1 till 247. If you turn the value selector to end stop "+", the display will show a "2". This makes it possible to select the second level. If you select the second level, this is indicated in the display by a small circle.
The following functions are available at the second level:
Flow Return to previous level
Not used
Normally shows "OFF"
In order to start a test run, you have to turn the mode wheel to "ON".
Shows the angle of the rotation (0…255 digital 0....100%).
V nom
Used for selecting communication settings for Modbus. See table below.
Used for setting response delay for the Modbus communication (see separate documents)
Set V nom
according to the preset values for circular dampers and rectangular dampers according to the specification in Section 4.7, Calibration list. If 999 is shown in the display, it is possible to enter a userspecific V nom
. The V nom
value can only be set using the Gruner winVAV
Software (applies to the 15 Nm version only). No password is required when entering the first settings. After entering the first settings, you must set the password to 201 and wait until the display flashes; then enter another password.
REACT
Room thermostat
REACT
1 2 3 4
RTC
A B
227VM
SWN
0..10 (2..10) V DC
AC/DC
RTCT
REACT
1 2 3 4
A B
227VM
SWN
N
L
120 Ω
*
1 = REACT supply air
2 = REACT extract air
= Modbus
Figure 22. The diagram shows how to wire a RTC room unit with simultaneous control of the extract air. The figure also shows an alternative with RTCT duct temperature sensor.
CO
2
and temperature control
DETECT Q 1 & 2
REACT
1 2 3 4
A B
227VM
SWN
0..10 (2..10) V DC
REACT
1 2 3 4 A B
227VM
SWN
AC/DC
Figure 23. The diagram shows how to wire the CO
2
sensor with combined DETECT Q temperature control and simultaneous control of the extract air.
Two-flow control with presence detector
REACT
1 2
Y U
3 4
A B
227VM
SWN
DETECT O REACT
1 2
Y
3
U
4
A B
227VM
SWN
N
L
120
Ω
*
1 = REACT supply air
2 = REACT extract air
= Modbus
AC/DC
N
L
120 Ω
*
1 = REACT supply air
2 = REACT extract air
= Modbus
Figure 24. The diagram shows how to wire the DETECT O presence detector with simultaneous control of the extract air. Twoflow control, min. or max. airflow.
Swegon reserves the right to alter the specifications. 20160307
*
Should only be used on the last REACT in the Modbus loop
9 www.swegon.com
REACT
VAV regulation with room thermostat and presence detector
RTC DETECT O
REACT
Y U
227VM SWN
1 2 3 4
REACT
1
Y U
2 3 4
227VM SWN
G0
G
Figure 25. The diagram shows how to wire a RTC room unit and DETECT O with simultaneous control of the extract air. VAV is used for occupancy, otherwise min. airflow. The figure also shows the alternative with RTCT duct temperature sensor.
VAV regulation and heat regulation with thermo-actuators
1 = REACT supply air.
2 = REACT extract air.
REACT
1 2
Y U
3 4
A B
227VM
SWN
RTC
* )
0..10 (2..10) V DC
RTCT
REACT
1 2
Y
3
U
4
A B
227VM
SWN
AC/DC
Figure 26. The diagram shows how to wire and refit jumpers of the RTC room thermostat enabling operation of the on/off 24 V VAC thermo-actuator on output YH (4).
*)
The jumper connection in the RTC must be changed when wiring the thermo-actuator (3) to the system. More information is available in the
Installation/Commissioning documentation for RTC.
NOTE: The unit must be de-energized before reconnecting any jumpers!
N
L
1 = REACT supply air
2 = REACT extract air
3 = Thermo-actuator, heat
= Modbus
120 Ω
*
*
Should only be used on the last REACT in the Modbus loop
Slave control with REACT CU as a master
REACT CU
Y U
1 2 3 5
REACT
Y U
1 2 3 4
227VM
SWN
0..10 (2..10) V DC
AC/DC
N
L
Figure 27. The diagram shows the connections between master – slave unit.
In this wiring configuration, the REACT slave controller should be set to a flow range of 0-100% of the nominal airflow.
10
Swegon reserves the right to alter the specifications. 20160307 www.swegon.com
REACT
Diagram, true value voltage/airflow
The diagram only applies to factory-calibrated products for nominal air-flow, according to the
Air-flow and K-factor table. U always refers to Q nom
. NOTE! Does not indicate damper position.
U Volt
10
Ø100 Ø125
Ø160
Ø200
Ø250 Ø315 Ø400
8
Ø500
6
4
2
0
100 200 300 400 500 600 700
Dimension, air-flow and k-factors
800 900
All REACT variants - Standard, Modbus, spring return
1000
Circular version
400 x 200
500 x 200
600 x 200
700 x 200
800 x 200
1000 x 200
300 x 300
400 x 300
500 x 300
600 x 300
700 x 300
800 x 300
1000 x 300
400 x 400
500 x 400
600 x 400
Size
100
125
160
200
250
315
400
Q
Air-flow (l/s) min
*
5
Q nom
62
9 102
16
25
40
63
102
176
280
456
730
1200 k-factor
5.3
8.7
15.5
24.8
40.0
63.4
102.0
Torque (Nm)
5
10
5
5
10
5
5
500 164 1850 164.0
10
* At Q min
a measurement pressure of 1 Pa is obtained with a measurement accuracy of ± 5-20%
Rectangular version
(B = Width, H = Height)
Size
(B x H mm)
200 x 200
300 x 200
Q min
Air-flow (l/s)
Q nom
75
112
367
548 k-factor
33.5
50.0
Torque
(Nm)
5
5
398
454
568
304
382
458
373
170
228
284
340
149
187
224
262
297
1950
2224
2782
1490
1873
2246
1829
833
1117
1391
1665
728
915
1095
1282
1457
178.0
203.0
254.0
136.0
171.0
205.0
66.5
83.5
100.0
117.0
133.0
167.0
76.0
102.0
127.0
152.0
10
10
10
5
10
10
10
5
5
5
5
5
5
5
5
5
1100 1200 1300 1400 1500 1600
Rectangular version – continued
Size
(B x H mm)
700 x 400
Q min
534
Air-flow (l/s)
Q nom
2618
800 x 400
1000 x 400
1200 x 400
610
762
915
1400 x 400 1069
1600 x 400 1221
500 x 500
600 x 500
700 x 500
479
575
671
800 x 500
1000 x 500
767
959
1200 x 500 1149
1400 x 500 1342
1600 x 500 1534
600 x 600
700 x 600
691
807
800 x 600 921
1000 x 600 1152
1200 x 600 1382
1400 x 600 1614
1600 x 600 1845
700 x 700
800 x 700
944
1078
1000 x 700 1348
1200 x 700 1617
1400 x 700 1887
1600 x 700 2156
3757
4699
5631
6573
7515
3385
3955
4513
5642
2991
3735
4480
5236
5981
2344
2815
3286
6770
7909
9037
4623
5280
6606
7920
9246
10560
1700 1800 k-factor
422.0
482.0
603.0
723.0
844.0
964.0
309.0
361.0
412.0
515.0
618.0
722.0
825.0
214.0
257.0
300.0
343.0
429.0
514.0
600.0
686.0
239.0
273.0
341.0
409.0
478.0
546.0
1900 2000 l/s
Torque
(Nm)
15
15
15
15
15
15
15
15
15
10
10
15
15
10
15
15
15
15
10
10
10
10
10
10
15
15
15
11
Swegon reserves the right to alter the specifications. 20160307 www.swegon.com
REACT
Checking performance – REACT
Checking the min. airflow
The easiest way to do this is by disconnecting the white cable marked 3. The damper will then move to the closed position.
Measure the voltage U (between cables 1 and 4)and calculate the airflow using the formulas on this page.
Checking the max. airflow
Use the room thermostat, or some other control equipment, to override the system so the control voltage will be a 10 V input on the white cable 3. As an alternative, you can short circuit between cables 2 and
3. This will command the controller to go to the preset max. airflow setting. Before short circuiting, you must disconnect the cable from the room controller. If this is not done, you will destroy the output on the control equipment. The damper will move to the open position.
Measure the voltage U (between cables 1 and 4) and calculate the airflow using the formulas on this page.
Gear release
The controller of the 227VM SWN has a gear release button, enabling the damper shaft to be turned manually. Spring return actuators on REACT GUAC are supplied as standard from the factory with the spring return of the damper set to de-energized/closed.
Mechanical opening/closing of the spring return actuator
Mechanical handling of dampers can only be performed if the actuator is de-energized. The supplied key (attached to the motor cable) or a 2.5 mm hex key, is used for mechanical handling.
REACT as a constant-flow controller
When REACT is used as a constant-flow controller, the min. flow setting is used as the set point for the constant airflow. Only 24 V AC, should be connected to cable pair 1 and 2.
Troubleshooting – REACT
Incorrect polarity on control signal zero conductor
It is important that the neutral conductor follows the entire chain of connections from thermostat to controller. Check this, by measuring the control voltage between cables 1 and 3 on the REACT. Correctly wired it should be possible to vary the signal between 0-10 V
DC. Incorrectly wired, the delivered signal is ~ 27.4 - 29.1 V DC.
Airflow does not correspond
Inaccurate air-flow is primarily due to disruptions in the duct system. Above all, the straight duct length requirements should be checked. If the ducting deviates from these requirements, the error can be as large as 20%. In systems with dusty air (mostly extract air systems) the unit's sensors can become soiled.
The sensor can be cleaned by blowing it with clean air in the opposite direction to the air-flow, i.e. in the tube connection. We recommend compressed air in a low-pressure aerosol tube. The duct must also be cleaned, to keep the measurement flange and the pressure tappings from blocking up.
Checking performance – REACT CU
Checking signals
Since the REACT CU only uses the controller’s airflow measurement feature, no settings are needed. It is the true value signal from terminal 5 that must be wired further to the slave unit. This is not affected by the settings on the min./max. potentiometers.
Measure the voltage, U (between cables 1 and 5), and calculate the airflow using the formulas below for the relevant signal system;
0-10 or 2-10 V DC. REACT CU is normally supplied with a 0-10 true value signal. Check the marking, to see if it should be set for 2-10
V. For Q nom
see the tables on page 11.
Y U
1 2 3 4
227VM SWN
4,00 V
V DC
Figure 28. How to connect a voltmeter to check the true value.
Formulas for calculating airflows.
A control signal of 0..10 V DC, gives the following formulas:
• To calculate the current actual flow (Q act know the value of the control signal (Y):
) when you
Q act
= Q min
+
Y
10 V DC
(Q max
– Q min
)
• To calculate the current true value (U) when you know the value of the actual flow (Q act
):
U = 10 V DC
Q act
Q nom
A control signal of 2..10 V DC gives the following formulas:
• To calculate the current actual flow (Q act know the value of the control signal (Y):
) when you
Q act
= Q min
+
Y – 2 V DC
8 V DC
(Q max
– Q min
)
• To calculate the current true value (U) when you know the value of actual flow (Q act
):
U = 2 V DC + 8 V DC
Q
Q act nom
Explanations of the formulas above:
Y = Control signal in [V] DC
U
*
= True value signal in [V] DC
Q act
= Actual flow in [l/s]
Q min
= Required min. airflow in [l/s]
Q max
= Required max. airflow in [l/s]
Q nom
= Nominal flow in [l/s], see tables page 11.
* Always refers to Q nom
. NOTE! Does not indicate damper position.
12
Swegon reserves the right to alter the specifications. 20160307 www.swegon.com