- Industrial & lab equipment
- Electrical equipment & supplies
- Electrical connection
- Power extensions
- User manual
advertisement
TM
Series ACT Pneumatic and Electric Actuators
Specifications - Installation and Operating Instructions
Bulletin V-ACT
ACT-SR03
ACT-TD01-110VAC
ACT-MI02-110VAC
The W.E. Anderson Series ACT
Actuators are available in either pneumatic or electric models. The wide range of torques and voltages means there is an actuator for almost any application. The standard ISO 5211 mounting configuration makes installation to any valve or damper quick and simple.
W.E. Anderson pneumatic ACT models are a compact rack-and-pinion design with a symmetrical structure that ensures fast and steady action, high precision and high output power. The corrosion resistant anodized aluminum body is designed to withstand the harsh and abusive industrial environments and provide reliable service. We offer double acting and spring return models in a variety of sizes to fit any application.
W.E. Anderson electric ACT models are available in two-position or modulating configurations and NEMA 4X or NEMA
7 rated enclosures. All electric actuators utilize a high grade powder coated aluminum enclosure with visual indicators. The two-position models come standard with two auxiliary switches, and modulating models offer an output for position monitoring.
Certain models are equipped with manual overrides allowing the operator to cycle the valve manually for installation or maintenance checks.
SPECIFICATIONS
Pneumatic “DA” and “SR” Series
Type: DA series is double acting and
SR series is spring return (rack and pinion).
Normal Supply Pressure: DA: 40 to
115 psi (2.7 to 7.9 bar); SR: 80 psi
(5.5 bar).
Maximum Supply Pressure: 120 psi
(8.6 bar).
Air Connections: DA01: 1/8˝ female
NPT; DA02 to DA14: 1/4˝ female NPT;
SR02 to SR14: 1/4˝ female NPT.
Housing Material: Anodized aluminum body and epoxy coated aluminum end caps.
Temperature Limits: -40 to 176°F
(-40 to 80°C).
Accessory Mounting: NAMUR standard.
Electric “TD” and “MD” Series
Power Requirements: 110 VAC,
220 VAC, 24 VAC or 24 VDC (MD models not available in 24 VDC).
Power Consumption: See page 9.
Cycle Time (per 90°): See page 9.
Duty Rating: 85%.
Enclosure Rating: NEMA 4X (IP67).
Housing Material: Powder coated aluminum.
Temperature Limits: -22 to 140°F
(-30 to 60°C).
Electrical Connection: 1/2˝ female
NPT.
Modulating Input: 4 to 20 mA.
Standard Features: Manual override, position indicator, and TD models come with two limit switches.
Electric “TI” and “MI” Series
Power Requirements: 110 VAC,
220 VAC, 24 VAC or 24 VDC.
Power Consumption: See page 9.
Cycle Time (per 90°): See page 9.
Duty Rating: See page 9.
Enclosure Rating: NEMA 7.
Housing Material: Powder coated aluminum.
Temperature Limits: -40 to 140°F
(-40 to 60°C).
Electrical Connection: 1/2˝ female
NPT.
Modulating Input: 4 to 20 mA.
Standard Features: Position indicator and two limit switches.
W.E. ANDERSON,
A DIV. OF DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Phone: 219/879-8000
Fax: 219/872-9057 www.dwyer-inst.com
e-mail: [email protected]
Popular Models
ACT-TD03-110VAC
ACT-TD04-110VAC
ACT-TD05-110VAC
ACT-TD06-110VAC
ACT-MD01-110VAC
ACT-MD02-110VAC
ACT-MD03-110VAC
ACT-MD04-110VAC
ACT-MD05-110VAC
ACT-MD06-110VAC
ACT-TI01-110VAC
ACT-TI02-110VAC
ACT-TI03-110VAC
ACT-TI04-110VAC
ACT-TI05-110VAC
ACT-TI06-110VAC
ACT-TI07-110VAC
ACT-TI08-110VAC
ACT-TI09-110VAC
ACT-TI10-110VAC
ACT-TI11-110VAC
ACT-MI01-110VAC
ACT-MI02-110VAC
ACT-MI03-110VAC
ACT-MI04-110VAC
ACT-MI05-110VAC
ACT-MI06-110VAC
ACT-MI07-110VAC
ACT-MI08-110VAC
ACT-MI09-110VAC
ACT-MI10-110VAC
ACT-MI11-110VAC
Pneumatic Models
ACT-DA01
ACT-DA02
ACT-DA03
ACT-DA04
ACT-DA05
ACT-DA06
ACT-DA07
ACT-DA08
ACT-DA09
ACT-DA10
ACT-DA11
ACT-DA12
ACT-DA13
ACT-DA14
ACT-SR02
ACT-SR03
ACT-SR04
ACT-SR05
ACT-SR06
ACT-SR07
ACT-SR08
ACT-SR09
ACT-SR10
ACT-SR11
ACT-SR12
ACT-SR13
ACT-SR14
Electric Models
ACT-TD01-110VAC
ACT-TD02-110VAC
Description
Double Acting Pneumatic Actuator, 98 in-lb
Double Acting Pneumatic Actuator, 207 in-lb
Double Acting Pneumatic Actuator, 365 in-lb
Double Acting Pneumatic Actuator, 603 in-lb
Double Acting Pneumatic Actuator, 792 in-lb
Double Acting Pneumatic Actuator, 1135 in-lb
Double Acting Pneumatic Actuator, 1690 in-lb
Double Acting Pneumatic Actuator, 2993 in-lb
Double Acting Pneumatic Actuator, 4506 in-lb
Double Acting Pneumatic Actuator, 6866 in-lb
Double Acting Pneumatic Actuator, 11065 in-lb
Double Acting Pneumatic Actuator, 15207 in-lb
Double Acting Pneumatic Actuator, 23834 in-lb
Double Acting Pneumatic Actuator, 33516 in-lb
Spring Return Pneumatic Actuator, 95 in-lb
Spring Return Pneumatic Actuator, 176 in-lb
Spring Return Pneumatic Actuator, 274 in-lb
Spring Return Pneumatic Actuator, 381 in-lb
Spring Return Pneumatic Actuator, 536 in-lb
Spring Return Pneumatic Actuator, 815 in-lb
Spring Return Pneumatic Actuator, 1411 in-lb
Spring Return Pneumatic Actuator, 2460 in-lb
Spring Return Pneumatic Actuator, 3733 in-lb
Spring Return Pneumatic Actuator, 6166 in-lb
Spring Return Pneumatic Actuator, 5253 in-lb
Spring Return Pneumatic Actuator, 7923 in-lb
Spring Return Pneumatic Actuator, 9546 in-lb
Description
Electric Two-Position, 177 in-lb, 110 VAC
Electric Two-Position, 442 in-lb, 110 VAC
Electric Two-Position, 885 in-lb, 110 VAC
Electric Two-Position, 1770 in-lb, 110 VAC
Electric Two-Position, 3540 in-lb, 110 VAC
Electric Two-Position, 5210 in-lb, 110 VAC
Electric Modulating, 265 in-lb, 110 VAC
Electric Modulating, 442 in-lb, 110 VAC
Electric Modulating, 885 in-lb, 110 VAC
Electric Modulating, 1770 in-lb, 110 VAC
Electric Modulating, 3540 in-lb, 110 VAC
Electric Modulating, 5210 in-lb, 110 VAC
EXP Electric Two-Position, 100 in-lb, 110 VAC
EXP Electric Two-Position, 200 in-lb, 110 VAC
EXP Electric Two-Position, 300 in-lb, 110 VAC
EXP Electric Two-Position, 400 in-lb, 110 VAC
EXP Electric Two-Position, 675 in-lb, 110 VAC
EXP Electric Two-Position, 1000 in-lb, 110 VA
EXP Electric Two-Position, 1500 in-lb, 110 VA
EXP Electric Two-Position, 2000 in-lb, 110 VAC
EXP Electric Two-Position, 3840 in-lb, 110 VAC
EXP Electric Two-Position, 5000 in-lb, 110 VAC
EXP Electric Two-Position, 7020 in-lb, 110 VAC
EXP Electric Modulating, 100 in-lb, 110 VAC
EXP Electric Modulating, 200 in-lb, 110 VAC
EXP Electric Modulating, 300 in-lb, 110 VAC
EXP Electric Modulating, 400 in-lb, 110 VAC
EXP Electric Modulating, 675 in-lb, 110 VAC
EXP Electric Modulating, 1000 in-lb, 110 VAC
EXP Electric Modulating, 1500 in-lb, 110 VAC
EXP Electric Modulating, 2000 in-lb, 110 VAC
EXP Electric Modulating, 3840 in-lb, 110 VAC
EXP Electric Modulating, 5000 in-lb, 110 VAC
EXP Electric Modulating, 7020 in-lb, 110 VAC
Note: Optional voltages available for the electric actuators. Change the -110 VAC to -220
VAC, 24 VDC or 24 VAC. The ACT-TD and ACT-MD are not available with 24 VAC.
Page 2
AUTOMATED VALVE DRAWINGS
Pneumatic Actuator
B
A
D
C
ACT
A
B
C
D
DA01
2-3/8˝
60.5 mm
4-9/16˝
116 mm
3-5/32˝
80 mm
1-7/16˝
36.5 mm
DA02/
SR02
2-13/16˝
71 mm
5-23/32˝
145 mm
3-5/8˝
92 mm
1-5/8˝
41 mm
DA03/
SR03
3-15/64˝
82 mm
6-21/32˝
169 mm
4-1/4˝
108 mm
1-13/16˝
46 mm
DA04/
SR04
3-45/64˝
94 mm
7-15/16˝
201 mm
4-23/32˝
120 mm
2-3/64˝
52 mm
DA05/
SR05
3-63/64˝
101 mm
8-15/64˝
209 mm
5-1/32˝
128 mm
2-11/64˝
55 mm
DA06/
SR06
4-17/64˝
108.5
9-17/32˝
242 mm
5-33/64˝
140 mm
2-17/64˝
57.5 mm
DA07/
SR07
4-25/32˝
122 mm
10-53/64˝
275 mm
6-1/32˝
153 mm
2-1/2˝
64 mm
DA08/
SR08
5-13/32˝
137.5 mm
13-5/64˝
332 mm
6-57/64˝
175 mm
2-3/4˝
70 mm
DA09/
SR09
6-1/32˝
153 mm
15-5/32˝
385 mm
7-17/32˝
191.5 mm
3-1/32˝
77 mm
DA10/
SR10
6-55/64˝
174 mm
17-23/32˝
450 mm
8-17/32˝
217 mm
3-29/64˝
87.5 mm
DA11/
SR11
8-1/8˝
206 mm
19-31/32˝
507 mm
10-1/4˝
260 mm
4-1/16˝
103 mm
DA12/
SR12
8-29/32˝
226 mm
22-1/8˝
562 mm
11-3/16˝
285 mm
4-29/64˝
113 mm
DA13/
SR13
10-5/32˝
258 mm
25-7/16˝
646 mm
12-39/64˝
320 mm
5-5/64˝
129 mm
DA14/
SR14
11-1/2˝
292 mm
28-7/16˝
722 mm
13-25/32˝
350 mm
5-3/4˝
146 mm
Electric Actuator
B
D
A
6
2
C
ACT
A
B
C
D
TD01/
MD01
4-7/16˝
113 mm
6-9/32˝
160 mm
4-1/32˝
102.5 mm
3-1/32˝
77 mm
TD02/
MD02
4-7/16˝
113 mm
6-9/32˝
160 mm
4-1/32˝
102.5 mm
3-1/32˝
77 mm
TD03/
MD03
4-3/4˝
121 mm
7-11/16˝
196 mm
4-31/32˝
126 mm
3-7/8˝
98 mm
TD04/
MD04
6-7/32˝
158 mm
10-1/32˝
255 mm
5-13/16˝
148 mm
5-1/4˝
134 mm
TD05/
MD05
6-7/32˝
158 mm
10-1/32˝
255 mm
5-13/16˝
148 mm
5-1/4˝
134 mm
TD06/
MD06
6-7/32˝
158 mm
10-1/32˝
255 mm
5-13/16˝
148 mm
5-1/4˝
134 mm
TD07/
MD07
8-17/32˝
217 mm
12-7/32˝
310 mm
6-1/2˝
165 mm
6-3/8˝
162 mm
TD08/
MD08
8-17/32˝
217 mm
12-7/32˝
310 mm
6-1/2˝
165 mm
6-3/8˝
162 mm
TD09/
MD09
8-17/32˝
217 mm
12-7/32˝
310 mm
6-1/2˝
165 mm
6-3/8˝
162 mm
Explosion-Proof Actuator
A
B D
C
ACT
A
B
C
D
TI01/
MI01
5-1/4˝
133.4 mm
6-1/8˝
154 mm
5˝
125.7 mm
2-5/8˝
66.7 mm
TI02/
MI02
8-1/2˝
216.7 mm
9-3/8˝
238.9 mm
6-3/8˝
162.3 mm
3-1/8˝
79.4 mm
TI03/
MI03
8-1/2˝
216.7 mm
9-3/8˝
238.9 mm
6-3/8˝
162.3 mm
3-1/8˝
79.4 mm
TI04/
MI04
8-1/2˝
215.9 mm
8-1/2˝
215.9 mm
7-1/8˝
180 mm
3-3/8˝
85.7 mm
TI05/
MI05
8-1/2˝
215.9 mm
8-1/2˝
215.9 mm
7-1/8˝
180 mm
3-3/8˝
85.7 mm
TI06/
MI06
8-1/2˝
215.9 mm
8-1/2˝
215.9 mm
7-1/8˝
180 mm
3-3/8˝
85.7 mm
TI07/
MI07
8-1/2˝
215.9 mm
8-1/2˝
215.9 mm
7-1/8˝
180 mm
3-3/8˝
85.7 mm
TI08/
MI08
10˝
254 mm
10˝
254 mm
10˝
253.1 mm
3-3/4˝
174.6 mm
TI09/
MI09
10˝
254 mm
10˝
254 mm
10˝
253.1 mm
3-3/4˝
174.6 mm
TI10/
MI10
12-7/8˝
327mm
14˝
355.6 mm
13-1/2˝
343.4 mm
5-1/2˝
138.1 mm
TI11/
MI11
12-7/8˝
327mm
14˝
355.6 mm
16-1/2˝
418 mm
5-1/2˝
138.1
Page 3
PNEUMATIC ACTUATOR
Note: For optimal operation, pneumatic actuators should be run with a supply of clean, lubricated air.
Spring Return Actuator Operation
Air to PORT 2 (the right hand port) causes the actuator to turn counter clockwise
(CCW). Loss of air to PORT 2 causes air to exhaust and the actuator turns cockwise (CW). This is the FAIL CLOSE operation.
Double Acting Actuators Operation
Air to PORT 2 (the right hand port) causes the actuator to turn counter clockwise
(CCW). Air to PORT 1 (the left hand port) causes the actuator to turn clockwise
(CW).
Pneumatic Actuator Maintenance
Routine maintenance of pneumatic actuator:
• Keep the air supply dry and clean
• Keep the actuator surface clean and free from dust
• Periodic checks should be done to make sure all fittings are tight
• Pneumatic actuators are supplied with lubrication to last the entire life span of the actuator under normal operating conditions.
The outer surface of the pneumatic actuator should be clean to avoid friction or corrosion. All fittings and connections should be tight to prevent leaks during operation. Check the bolts mounting the valve to the actuator to make sure they have not come loose during shipping or installation. Make sure the valve and actuator are not rubbing or jamming against other components during operation.
The actuator should be inspected annually to make sure all fittings and bolts are tight and nothing has come loose during operation.
Disassembling Pneumatic Actuators
WARNING
Before beginning disassembly, ensure the air supply to the actuator has been disconnected, all accessories have been removed, and the actuator has been disassembled from the valve.
1. Loosen the end cap fasteners (22) with a wrench (size varies depending on actuator model). On the spring return actuator, alternate 3 to 5 turns on each fastener until the springs are completely decompressed. Use caution when removing the cap since the springs are under load until the fasteners are fully extended.
2. Remove the pinion snap ring (10) with a lock ring tool. The indicator (7) may now be removed.
3. Turn the pinion shaft (2) counter clockwise until the pistons are at the full end of travel. Disengage the pistons (11) from the pinion. (NOTE: Low pressure air--3 to 5 psi MAXIMUM--might be required to force the pistons completely from the body.)
Note the position of the pistons before removing them from the actuator body.
4. Remove the pinion through the bottom of the actuator. The actuator is now completely disassembled.
Pneumatic Actuators Bill of Materials
Failures
Pneumatic actuator won’t operate
Pneumatic actuator runs slowly
Inspection Items
1. Check the solenoid valve. Is the coil burnt out or is the solenoid spool?
2. The actuator will not move because of debris in the gears.
Corrective Action
1. Replace the solenoid valve coil or remove debris.
2. Disassemble the actuator, clean the debris and reassemble the actuator.
3. Replace pneumatic line to the actuator.
3. The pneumatic line to the actuator is distorted or smashed.
4. The pneumatic line is frozen because of low temperatures and moisture.
1. The air supply pressure is insufficient.
2. Are other pneumatic devices consuming the air required for the actuator to operate?
3. The pneumatic actuator is undersized for the application.
4. Warm the pneumatic lines and remove moisture from supply lines.
1. Increase the air supply pressure and look for leaks in the supply pressure pipeline.
2. Increase the air supply or reduce the number of devices operating at the same time.
3. Replace the actuator with a larger actuator.
Reassembling Pneumatic Actuators
WARNING
Be sure the actuator surfaces are free of debris and scratches before reassembling.
1. Apply a light film of grease to all O-rings and the pinion before replacing.
2. Put the pinion (2) back through the actuator with the flats of the pinion shaft running parallel with the body.
3. When reassembling the actuator, make sure that the piston racks are square to the actuator body and returned to their original orientation. (NOTE: The normal operation of all spring return pneumatic actuators is FAIL CLOSED. To change the orientation to FAIL OPEN, rotate the racks 180º to create a reverse operation.
4. When replacing springs in a spring return actuator, ensure that the springs are replaced in their identical position in the end cap from which they were removed.
(NOTE: In some circumstances, you might want to change the standard 80 pound spring set to fit your application and available air pressure.
5. Seal the end caps with a petroleum lubricant and bolt to actuator body.
6. Check the seal of the actuator by covering seal areas (pinion, end caps) with soapy water and using low pressure air to the actuator to ensure that no bubbles are produced.
22
23
24
25
26
27
15
16
17
18
19
20
21
11
12
13
14
7
8
9
10
5
6
3
4
Part Number
1
2
2
2
1
8
2
2
2
2
2
2
1
2
5 to 12
1
4
1
1
1
1
1
1
1
1
1
1
Quantity
1
1
Part Name
Cylinder
Output Shaft
O-ring
Bearing
Adjusting Cam
Thrust Bearing
Bearing
O-ring
Bearing
Gasket
Damping Ring
Position Indicator
Screw
Position Indicating
Inserts
Piston
Guide Ring
O-ring
Guide Ring
Spring Assembly
O-ring
Left End Cap
Right End Cap
End Cap Bolt
O-ring
Gasket
Nut
Adjusting Bolt
Material
Extruded Aluminum Alloy
Stainless Steel
Fluorine Silicon Rubber
Nylon46
Stainless Steel
Nylon46
Nylon46
Fluorine Silicon Rubber
Nylon46
Stainless Steel
Stainless Steel
PPPP+30%GF
PPPP+30%GF
PPPP+30%GF
Casting Aluminum Alloy
Nylon46
Fluorine Silicon Rubber
Fluorine-Carbon Composite Material
Alloy Spring Steel
Fluorine Silicon Rubber
Casting Aluminum Alloy
Casting Aluminum Alloy
Stainless Steel
Fluorine Silicon Rubber
Stainless Steel
Stainless Steel
Stainless Steel
Page 4
Double Acting Actuator Torque
Model
ACT-DA01
ACT-DA02
ACT-DA03
ACT-DA04
ACT-DA05
ACT-DA06
ACT-DA07
ACT-DA08
ACT-DA09
ACT-DA10
ACT-DA11
ACT-DA12
ACT-DA13
ACT-DA14
Double Acting Pneumatic Actuator Output Torque (in-lb)
Air Pressure
40 psi
49
104
182
302
396
567
845
1497
2253
3433
5532
7603
11917
16758
50 psi
61
130
228
377
495
709
1056
1871
2816
4291
6916
9504
14896
20948
60 psi
74
155
274
453
594
851
1267
2245
3379
5149
8299
11405
17875
25137
70 psi
86
181
319
528
693
993
1478
2619
3942
6008
9682
13306
20855
29327
80 psi
98
207
365
603
792
1135
1690
2993
4506
6866
11065
15207
23834
33516
90 psi
110
233
411
679
891
1277
1901
3367
5069
7724
12448
17107
26813
37706
100 psi
123
259
456
754
990
1419
2112
3742
5632
8582
13831
19008
29792
41896
110 psi
135
285
502
830
1089
1561
2323
4116
6195
9440
15214
20909
32772
46085
115 psi
142
300
529
875
1148
1646
2450
4340
6533
9955
16044
22050
34559
48599
Spring Return Actuator Torque
Model
ACT-SR02
ACT-SR03
ACT-SR04
ACT-SR05
ACT-SR06
ACT-SR07
ACT-SR08
ACT-SR09
ACT-SR10
ACT-SR11
ACT-SR12
ACT-SR13
ACT-SR14
Spring
Sets
10
10
10
10
10
10
10
10
10
10
10
10
10
Torque List of Single Acting Pneumatic Actuator (in-lb)
180
263
385
695
937
1640
2529
4104
Air Pressure
Spring Torque
0°
69.9
120
90°
95.5
176
5253
7923
9546
274
381
536
815
1411
2460
3733
6166
8258
14103
18350
70 psi
0°
111.4
199
348
430
608
783
1682
2303
3479
5578
8052
12932
19781
90°
85.8
143
254
312
458
663
1208
1483
2274
3516
5048
6752
10977
80 psi
0°
137.3
245
424
529
750
994
2056
2866
4337
6961
9953
15911
23970
90°
111.7
189
330
411
599
874
1583
2046
3133
4899
6948
9731
15167
90 psi
0°
163.2
291
499
628
891
1206
2430
3429
5195
8344
11854
18890
28160
90°
137.6
235
405
510
741
1085
1957
2609
3991
6282
8849
12710
19357
100 psi
0° 90°
189.1
336
575
727
163.5
280
481
609
1033
1417
2804
3992
6053
9727
13755
21869
32349
883
1297
2331
3173
4849
7665
10750
15690
23546
110 psi
0° 90°
215
382
650
826
189.4
326
556
708
1175
1628
3178
4556
6911
11111
15656
24849
36539
1025
1508
2705
3736
5707
9048
12651
18669
27736
115 psi
0° 90°
230.6
409
695
885
204.9
353
601
767
1260
1755
3403
4894
7426
11940
16796
26636
39053
1110
1635
2930
4074
6222
9878
13791
20456
30249
ELECTRIC ACTUATORS
Electric Installation
1. Operate valve manually and place in the open position.
2. Remove any mechanical stops the valve might have. (DO NOT REMOVE ANY
PARTS NECESSARY FOR THE PROPER OPERATION OF THE VALVE, SUCH AS
THE PACKING GLAND, PACKING NUT, ETC.)
3. Ensure the actuator output shaft and valve stem are aligned properly. If they are not, operate the valve manually until they are correct.
4. Remove actuator cover.
5. Bring power to the actuator. CAUTION: Make sure power is OFF at the main box.
6. Wire the actuator per the diagram attached to the inside of the cover. Special actuators (those with positioner boards, etc.) will have diagrams enclosed inside the cover.
7. Securely tighten bolts used to mount the actuator to a mounting bracket or directly to the valve mounting pad if it is ISO5211 compliant.
8. Cycle the unit several times and check the open and closed positions of the valve.
Cams are pre-adjusted at the factory; due to the variety of valve designs and types however, slight adjustments might be required.
9. Replace cover and tighten screws.
To Set The Open Position
1. Cycle the valve to the open position by applying power to terminals. The top cam and switch control this position. In the open position, the set screw in the top cam will be accessible.
2. If the valve is not open completely:
A. Slightly loosen the set screw on the top cam.
B. Rotate the cam clockwise (CW) by hand until the switch makes contact.
Contact is made when a slight click can be heard. By making incremental CW movements of the top cam, the valve can be positioned precisely in the desired position.
C. When the top cam is set, tighten the set screw securely.
3. If the valve opens too far:
A. Apply power to terminals. This will begin to rotate the valve CW. When valve is fully open and in the exact position desired, remove power from actuator.
B. Loosen the set screw in the top cam.
C. Rotate the top cam counterclockwise (CCW) until the switch arm drops off the round portion of the cam onto the flat section. A slight click can be heard as the switch changes state.
D. Continue applying power to terminals until valve is in the desired position.
Page 5
To Set The Closed Position
1. Apply power to terminals to move the valve toward the closed position. The bottom cam and switch control the closed position. In the closed position, the set screw in the bottom cam will be accessible.
2. If the valve is not closed completely:
A. Slightly loosen the set screw on the bottom cam.
B. Rotate the cam counter-clockwise (CCW) by hand until the switch makes contact. Contact is made when a slight click can be heard. By making incremental
CCW movements of the bottom cam, the valve can be positioned precisely in the desired position.
C. When the top cam is set, tighten the set screw securely.
3. If the valve closes too far:
A. Apply power to terminals. This will begin to rotate the valve CCW. When valve is fully closed and in the exact position desired, remove power from actuator.
B. Loosen the set screw in the top cam.
C. Rotate the top cam clockwise (CW) until the switch arm drops off the round portion of the cam onto the flat section. A slight click can be heard as the switch is no longer making contact with the round part of the cam.
D. Continue applying power to terminals until valve is in the desired position.
Electric Actuators Wiring Diagram: ACT-TI & ACT-MI
Wiring Diagrams for
TI01-TI10: 120 VAC, TI01-TI10: 220VAC, TI01-TI10: 24 VAC
OPTIONAL
BRAKE
C
NO
SW. #1
NC
C
OPTIONAL HEATER
& THERMOSTAT
GROUND
SCREW
NOTES:
POWER TO TERMINALS ONE & TWO OPENS THE VALVE
(CCW ROTATION)
POWER TO TERMINALS ONE & THREE CLOSES THE VALVE
(CW ROTATION)
TERMINALS 4 & 5 ARE FOR LIGHT INDICATION
WIRING DIAGRAM ILLUSTRATES THE ACTUATOR IN THE
OPEN POSITION
A.C.
SUPPLY
POWER
FIELD WIRING
LIGHTS FOR REMOTE
POSITION INDICATION
DPDT CONTROL SWITCH
SHOWN FOR ILLUSTRATION
ONLY
OPTIONAL EQUIPMENT
FIELD WIRING
+
DC
MOTOR
-
NO NC
1
SW.
#1
C
2
CA
M
3
NO
SW.
#2
NC
C
4
CA
M
5
6
Wiring Diagrams for
TI01-TI10: 12VDC, TI01-TI10: 24 VDC
ACTUATOR SHOWN IN OPEN
POSITION
SW.#1
SW.#2
SWITCH #1 OPEN SWITCH
SWITCH #2 CLOSE SWITCH
OPERATION:
POWER TO 1 & 2 FOR CCW ROTATION
POWER TO 3 & 4 FOR CW ROTATION
TERMINALS 5 & 6 FOR FIELD LIGHT
INDICATION CONNECTION
FIELD WIRING
N
O
C
O
M
N
C
N
O
CO
M
COIL
N
C
SPDT SWITCH SHOWN FOR
ILLUSTRATION ONLY
REVERSING RELAY SUPPLIED BY CUSTOMER
-
DC VOLTAGE
+
Page 6
Wiring Diagrams for
MI01-MI10: 120 VAC, MI01-MI10: 220 VAC, MI01-MI10: 24 VAC
WHT
GREEN
JP4
JP2
JP3
RED
JUMPER SET FOR
FAIL CLOSE UPON
LOSS OF CONTROL
SIGNAL
GREEN
JP4
JP2
JP3
RED
JUMPER SET FOR
FAIL OPEN UPON
LOSS OF CONTROL
SIGNAL
JUMPER AS SHOWN BELOW IS FAIL IN
LAST POSITION UPON LOSS OF SIGNAL
4-20mA POSITIONER
1K OHM FEEDBACK
POTENTIOMETER
RED
PSC MOTOR
NC
C
NO
SW.1
B
L
K
BLU
NO
SW.2
B
L
K
C
NC
CAPACITOR
BRAKE
OPTIONAL
J2
SPAN
ZERO
JP1
DEAD
BAND
R
E
D
S
E
F
U
GREEN
JP4
JP2
JP3
RED
G
R
N
8 7 6 5 4 3 2 1 6 5 4 3 2 1 J1
BLK
WHT
AUXILIARY SWITCHES
OPTIONAL
NC
NO
SW.3
C
SW.4
NO
C
NC
9 10 11 12 13 14
SW. 4, OPEN
SW. 3, CLOSE
SW. 2, OPEN
SW. 1, CLOSE
NOTE:
ACTUATOR SHIPPED IN OPEN
POSITION, 20mA REPRESENTS OPEN
POSITION. DO NOT ADJUST FEEDBACK
POTENTIOMETER OR LIMIT SWITCHES
THEY ARE FACTORY SET AND DO NOT
REQUIRE CALIBRATION. TO
CALIBRATE THE OPEN AND CLOSE
POSITION USE THE ZERO (4mA) AND
SPAN (20mA) TRIM POTENTIOMETERS.
+
+
-
4-20mA CONTROL
SIGNAL
0-10VDC or 0-5VDC
CONTROL SIGNAL
REMOVE JP2, JP3 & JP4
HEATER &
THERMOSTAT
OPTIONAL
TO CALIBRATE OPERATE ACTUATOR
TO CLOSE POSITION AND ADJUST WITH
ZERO TRIM POT THEN OPERAT TO
OPEN POSITION AND SET USING SPAN
TRIM POT. NO FUTHER CALIBRATION IS
NECESSARY.
OPTIONAL EQUIPMENT
FIELD WIRING
1PH-60HZ
POWER SUPPLY
HOT
N
FIELD
WIRING
WI
RING DIAGRAM FOR 1Ph/60Hz ELECTRIC
ACTUATOR WITH 4-20mA, 0-5Vdc OR 0-10Vdc CONTROL.
GREEN
JP4
JP2
JP3
RED
JUMPER SET FOR
FAIL CLOSE UPON
LOSS OF CONTROL
SIGNAL
GREEN
JP4
JP2
JP3
RED
JUMPER SET FOR
FAIL OPEN UPON
LOSS OF CONTROL
SIGNAL
JUMPER AS SHOWN BELOW IS FAIL IN
LAST POSITION UPON LOSS OF SIGNAL
4-20mA POSITIONER
1K OHM FEEDBACK
POTENTIOMETER
J2
SPAN
ZERO
JP1
DEAD
BAND
R
E
D
S
E
F
U
GREEN
JP4
JP2
RED
JP3
G
R
N
Wiring Diagrams for
MI01-MI10: 12 VDC, MI01-MI10: 24 VDC
WHT
RED
PSC MOTOR
NC
C
NO
SW.1
B
L
K
BLU
NO
SW.2
B
L
K
C
NC
AUXILIARY SWITCHES
OPTIONAL
NC
NO
SW.3
C
SW.4
NO
C
NC
8 7 6 5 4 3 2 1 6 5 4 3 2 1 J1
BLK
WHT
9 10 11 12 13 14
+
+
-
1PH-60HZ
POWER SUPPLY
HOT
N
4-20mA CONTROL
SIGNAL
0-10VDC or 0-5VDC
CONTROL SIGNAL
REMOVE JP2, JP3 & JP4
FIELD
WIRING
HEATER &
THERMOSTAT
OPTIONAL
CAPACITOR
BRAKE
OPTIONAL
SW. 4, OPEN
SW. 3, CLOSE
SW. 2, OPEN
SW. 1, CLOSE
NOTE:
ACTUATOR SHIPPED IN OPEN
POSITION, 20mA REPRESENTS OPEN
POSITION. DO NOT ADJUST FEEDBACK
POTENTIOMETER OR LIMIT SWITCHES
THEY ARE FACTORY SET AND DO NOT
REQUIRE CALIBRATION. TO
CALIBRATE THE OPEN AND CLOSE
POSITION USE THE ZERO (4mA) AND
SPAN (20mA) TRIM POTENTIOMETERS.
TO CALIBRATE OPERATE ACTUATOR
TO CLOSE POSITION AND ADJUST WITH
ZERO TRIM POT THEN OPERAT TO
OPEN POSITION AND SET USING SPAN
TRIM POT. NO FUTHER CALIBRATION IS
NECESSARY.
OPTIONAL EQUIPMENT
FIELD WIRING
WI
RING DIAGRAM FOR 1Ph/60Hz ELECTRIC
ACTUATOR WITH 4-20mA, 0-5Vdc OR 0-10Vdc CONTROL.
Page 7
Electric Actuators Wiring Diagram: ACT-TD & ACT-MD
Wiring Diagrams for
TD01-TD09: 120 VAC, TD01-TD09: 220 VAC, TD01-TD09: 24 VAC
Wiring Diagrams for
TD01-TD06: 24 VDC
Wiring Diagrams for
MD01-MD09: 120 VAC, MD01-MD09: 220 VAC, MD01-MD09: 24 VAC
Note: To speed up installation of the control wires to the ACT-MDXX modulating actuator, it is recommended to remove the control module from the actuator. The control module can be removed by removing the two mounting screws on the left and right of the control module. Install the control wires to the correct terminal points and then reinstall the control module.
Electric Actuator Maintenance
Once the actuator has been properly installed, it requires no maintenance. The gear train has been lubricated and in most cases will never be opened.
Duty Cycle Definition
“Duty Cycle” means the starting frequency.
• •
Fomula: Running Time (Running Time Rest Time) x 100% = duty cycle
Rest Time = Running Time x (1 - duty cycle) duty cycle
For example: The running time is 15 seconds
30% duty cycle 15 x [(1 - 30%) / 30%] = 35 The rest time will be 35 seconds
75% duty cycle 15 x [(1 - 75%) / 75%] = 5 The rest time will be 5 seconds
If the duty cycle is higher, the rest time will be shortened. It means the starting frequency will be higher.
Thermal Overload
All actuators are equipped with thermal overload protection to guard the motor against damage due to overheating.
Mechanical Overload
All actuators are designed to withstand stall conditions. It is not recommended to subject the unit to repeated stall conditions.
Explosion-Proof Electric Actuators
WARNING
1. DO NOT under any circumstances remove the cover of the actuator while in a hazardous location. Removal of the cover while in a hazardous location could cause ignition of hazardous atmospheres.
2. DO NOT under any circumstances use an explosion-proof electric actuator in a hazardous location that does not meet the specifications for which the actuator was designed.
3. Always verify that all electrical circuits are de-energized before opening the actuator.
4. Always mount and cycle test the actuator on the valve in a non-hazardous location.
5. When removing the cover, care must be taken not to scratch, scar of deform the flame path of the cover and base of the actuator, since this will negate the NEMA rating of the enclosure.
6. When replacing the cover, take care that the gasket is in place to assure proper clearance after the cover is secured.
7. All electrical connections must be in accordance with the specifications for which the unit is being used.
8. Should the unit ever require maintenance, remove from the hazardous location before attempting to work on the unit.
If the actuator is in a critical application, it is advisable to have a standby unit in stock.
Page 8
Electric Actuators Performance Rating
TD01
Voltage
Cycle Time
Duty Cycle (Two-Position)
AMP Draw
Torque
110 VAC
4 s
85%
0.24 A
177 in-lb
220 VAC
4 s
85%
0.16 A
177 in-lb
24 VAC
4 s
85%
0.28 A
177 in-lb
MD01
Voltage
Cycle Time
MD01 Duty Cycle (Modulating)
AMP Draw
Torque
110 VAC
10 s
85%
0.24 A
265 in-lb
220 VAC
10 s
85%
0.16 A
265 in-lb
24 VDC
4 s
85%
1.28 A
177 in-lb
24 VAC
10 s
85%
1.28 A
265 in-lb
TD02 and MD02
Voltage
(MD Not Available in 24 VDC)
Cycle Time
Duty Cycle (Two-Position)
110 VAC
20 s
85%
220 VAC
20 s
85%
24 VAC
20 s
85%
Duty Cycle (Modulating)
AMP Draw
Torque
85%
0.24 A
442 in-lb
85%
0.16 A
442 in-lb
85%
1.28 A
442 in-lb
24 VDC
20 s
85%
1.28 A
442 in-lb
TD03 and MD03
Voltage
(MD Not Available in 24 VDC)
Cycle Time
Duty Cycle (Two-Position)
110 VAC
30 s
85%
220 VAC
30 s
85%
24 VAC
30 s
85%
Duty Cycle (Modulating)
AMP Draw
Torque
85%
0.57 A
885 in-lb
85%
0.35 A
885 in-lb
85%
2.03 A
885 in-lb
24 VDC
30 s
85%
2.03 A
885 in-lb
TD04 and MD04
Voltage
(MD Not Available in 24 VDC)
110 VAC 220 VAC
Cycle Time
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
AMP Draw
Torque
30 s
85%
85%
0.65 A
1770 in-lb
30 s
85%
85%
0.37 A
1770 in-lb
24 VAC
30 s
85%
85%
3.57 A
1770 in-lb
24 VDC
30 s
85%
3.57 A
1770 in-lb
TD05 and MD05
Voltage
(MD Not Available in 24 VDC)
Cycle Time
Duty Cycle (Two-Position)
110 VAC
30 s
85%
220 VAC
30 s
85%
Duty Cycle (Modulating)
AMP Draw
Torque
85%
1.12 A
3540 in-lb
85%
0.57 A
3540 in-lb
24 VAC
30 s
85%
85%
5.13 A
3540 in-lb
24 VDC
30 s
85%
5.13 A
3540 in-lb
TD06 and MD06
Voltage
(MD Not Available in 24 VDC)
Cycle Time
Duty Cycle (Two-Position)
110 VAC
45 s
85%
220 VAC
45 s
85%
Duty Cycle (Modulating)
AMP Draw
Torque
85%
1.18 A
5210 in-lb
85%
0.60 A
5210 in-lb
24 VAC
45 s
85%
85%
6.04 A
5210 in-lb
24 VDC
45 s
85%
6.04 A
5210 in-lb
TI01
Voltage
Cycle Time
Duty Cycle (Two-Position)
Full Load AMP Draw
Torque (in-lb)
TI02 and MI01, MI02
Voltage
Cycle Time (Two-Position)
Cycle Time (Modulating)
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
Full Load AMP Draw
Torque (in-lb)
110 VAC
2.5 s
25%
0.64
100
5 s
10 s
25%
75%
0.38
200
220 VAC
2.5 s
25%
0.32
100
110 VAC
5 s
10 s
25%
75%
0.18
200
24 VAC
2.5 s
25%
0.4
100
220 VAC 24 VAC
5 s
5 s
25%
75%
0.7
200
24 VDC
2.5 s
25%
0.4
100
24 VDC
5 s
5 s
25%
75%
0.7
200
TI03 and MI03
Voltage
Cycle Time (Two-Position)
Cycle Time (Modulating)
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
Full Load AMP Draw
Torque (in-lb)
110 VAC
5 s
10 s
25%
75%
0.38
300
220 VAC
5 s
10 s
25%
75%
0.18
300
24 VAC
5 s
5 s
25%
75%
0.7
300
24 VDC
5 s
5 s
25%
75%
0.7
300
Page 9
TI04 and MI04
Voltage
Cycle Time (Two-Position)
Cycle Time (Modulating)
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
Full Load AMP Draw
Torque (in-lb)
TI05 and MI05
Voltage
Cycle Time (Two-Position)
Cycle Time (Modulating)
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
Full Load AMP Draw
Torque (in-lb)
TI06 and MI06
Voltage
Cycle Time (Two-Position)
Cycle Time (Modulating)
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
Full Load AMP Draw
Torque (in-lb)
TI07 and MI07
Voltage
Cycle Time (Two-Position)
Cycle Time (Modulating)
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
Full Load AMP Draw
Torque (in-lb)
TI08 and MI08
Voltage
Cycle Time (Two-Position)
Cycle Time (Modulating)
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
Full Load AMP Draw
Torque (in-lb)
TI09 and MI09
Voltage
Cycle Time (Two-Position)
Cycle Time (Modulating)
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
Full Load AMP Draw
Torque (in-lb)
TI10 and MI10
Voltage
Cycle Time (Two-Position)
Cycle Time (Modulating)
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
Full Load AMP Draw
Torque (in-lb)
TI11 and MI11
Voltage
Cycle Time (Two-Position)
Cycle Time (Modulating)
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
Full Load AMP Draw
Torque (in-lb)
110 VAC
10 s
20 s
25%
75%
0.38
400
220 VAC
10 s
20 s
25%
75%
0.18
400
24 VAC
10 s
10 s
25%
75%
0.9
400
24 VDC
10 s
10 s
25%
75%
0.9
400
110 VAC
15 s
30 s
25%
75%
0.38
675
220 VAC
15 s
30 s
25%
75%
0.18
675
24 VAC
15 s
15 s
25%
75%
0.7
675
24 VDC
15 s
15 s
25%
75%
0.7
675
110 VAC
15 s
30 s
25%
75%
0.38
1000
220 VAC
15 s
30 s
25%
75%
0.18
1000
24 VAC
15 s
15 s
25%
75%
1.1
1000
24 VDC
15 s
15 s
25%
75%
1.1
1000
110 VAC
30 s
60 s
25%
75%
0.38
1500
220 VAC
30 s
60 s
25%
75%
0.18
1500
24 VAC
30 s
30 s
25%
75%
1.1
1500
24 VDC
30 s
30 s
25%
75%
1.1
1500
110 VAC
12 s
24 s
100%
100%
1.6
2000
220 VAC
12 s
24 s
100%
100%
1.03
2000
24 VAC
12 s
12 s
100%
100%
3.7
2000
24 VDC
12 s
12 s
100%
100%
3.7
2000
110 VAC
14 s
28 s
100%
100%
1.6
3840
220 VAC
14 s
28 s
100%
100%
1.03
3840
24 VAC
14 s
14 s
100%
100%
5
3840
24 VDC
14 s
14 s
100%
100%
5
3840
110 VAC
38 s
76 s
50%
50%
1.6
5000
220 VAC
38 s
76 s
50%
50%
1.03
5000
24 VAC
38 s
38 s
50%
50%
5
5000
24 VDC
38 s
38 s
50%
50%
5
5000
110 VAC
43 s
86 s
50%
50%
1.6
7020
220 VAC
43 s
86 s
50%
50%
1.03
7020
24 VAC
43 s
43 s
50%
50%
5
7020
24 VDC
43 s
43 s
50%
50%
5
7020
MAINTENANCE/REPAIR
Upon final installation of the Series ACT, only routine maintenance is required. The
Series ACT is not field serviceable and should be returned if repair is needed. Field repair should not be attempted and may void warranty.
WARRANTY/RETURN
Refer to “Terms and Conditions of Sale” in our catalog and on our website. Contact customer service to receive a Return Goods Authorization number before shipping the product back for repair. Be sure to include a brief description of the problem plus any additional application notes
©Copyright 2015 Dwyer Instruments, Inc.
W.E. ANDERSON,
A DIV. OF DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Printed in U.S.A. 3/15
Phone: 219/879-8000
Fax: 219/872-9057
FR# 444215-00 Rev. 5
www.dwyer-inst.com
e-mail: [email protected]
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement