- Industrial & lab equipment
- Measuring, testing & control
- Omega
- DPi8A/CNi16A CNi8A-AL/CNi16A-AL
- User manual
advertisement
User’s Guide
Shop on line at
®
®
omega.com
e-mail: [email protected]
iSeries info: omega.com/specs/iseries
For latest porduct manuals omegamanual.info
Temperature & Process Monitor
DPi8A/CNi16A
Temperature & Process Limit Alarm
CNi8A-AL/
CNi16A-AL
with Isolated Analog Output Board
TABLE OF CONTENTS
Part 1: Introduction ..............................................................................................2
1.1 Description ...................................................................................2
1.2 Safety Considerations..................................................................3
1.3 Before You Begin .........................................................................4
Part 2: Setup........................................................................................................5
2.1
Front Panel View..........................................................................5
2.2
2.3
1
1
8
⁄
⁄
16
DIN Rear Panel Connections .................................................6
DIN Rear Panel Connections................................................7
2.4
Electrical Installation .................................................................8
2.4.1
Fuse Requirement (see Specifications) .......................8
2.4.2
Thermocouple - Input Connection................................9
2.4.3
Two / Three / Four Wire RTD-Hookup .........................10
2.4.4
Process Current - Wiring Hookup...............................11
2.4.5
Process Voltage - Wiring Hookup ...............................11
2.4.6
Wiring Outputs - Wiring Hookup.................................12
Part 3: Operation: Configuration Mode ..............................................................13
3.1 Introduction ................................................................................13
Turning your Instrument On for the First Time
Buttons Functions in Configuration Mode
3.2 Menu Configuration ...................................................................14
3.2.1
ID Number......................................................................15
3.2.2
Set Points.......................................................................16
3.2.3
Configuration Menu .......................................................17
3.2.4
Input Type Menu.............................................................17
Input Type (Thermocouple) ...........................................18
Input Type (RTD) ............................................................19
Input Type (Process) .....................................................20
3.2.5
Reading Configuration Menu/Field Calibration ..............21
3.2.6
Analog Output (Retransmission) ...................................25
3.2.7
Alarm 1 Menu.................................................................27
3.2.8
Alarm 2 Menu.................................................................27
3.2.9
Reading Adjust Menu .....................................................31
3.2.10 ID Code Menu ................................................................32
3.2.11 Communication Options Menu.......................................34
3.2.12 Display Color Selection Menu ........................................41
Part 4: Specifications.........................................................................................44
4.1
4.2
1
1
8
⁄
⁄
16
DIN Mounting ........................................................................46
DIN Mounting .......................................................................46
Part 5: Factory Preset Values............................................................................48
Part 6: CE Approval Information ........................................................................49 i
LIST OF FIGURES:
Figure 2.1
Figure 2.2
Figure 2.3
Figure 2.4
1 ⁄
8 and
1 ⁄
16
DIN Front Panel Display.............................................5
1 ⁄
8 and
1 ⁄
16
DIN Rear View .............................................................5
1 ⁄
8
DIN Rear Panel Input Connections .......................................6
1 ⁄
16
DIN Rear Panel Input Connections ......................................7
Figure 2.5
Main Power Connections ..........................................................8
Figure 2.6
Thermocouple Wiring Hookup..................................................9
Figure 2.7
Two/Three/Four-wire RTD
a) RTD-1000 ohm and 500 ohm Wiring Hookup ......................10
Figure 2.8
b) RTD-100 ohm Wiring Hookup ..............................................10
Process Current Wiring Hookup
Figure 2.9
(Internal and External Excitation) ...............................................11
Process Voltage Wiring Hookup
a) With Sensor Excitation .........................................................11
b) Without Sensor Excitation ....................................................11
Figure 2.10
a) Mechanical Relay & SSR Output – Wiring Hookup..............12
b) Pulse Output – Wiring Hookup.............................................12
Figure 2.11
Analog Output Wiring Hookup....................................................12
Figure 2.12
Communication Outputs:
a) RS232 Output – Wiring Hookup...........................................12
b) RS485 Output – Wiring Hookup...........................................12
Figure 2.13
Excitation Output........................................................................12
Figure 3.1
Flow Chart for ID and Set Points Menu......................................14
Figure 3.2
Figure 3.3
Figure 3.4
Figure 3.5
Flow Chart for Configuration Menu ............................................17
Flow Chart for Input Type Menu.................................................17
Flow Chart for Reading Configuration Menu..............................21
Flow Chart for Analog Output Menu...........................................25
Figure 3.6
Figure 3.7
Figure 3.8
Figure 3.9
Flow Chart for Alarm 2 Menu .....................................................27
Flow Chart for Reading Adjust Menu/Field Calibration ..............31
Flow Chart for ID Code Menu ....................................................32
Flow Chart for Communication Option Menu.............................34
Figure 3.10
Flow Chart for Display Color Selection Menu ............................41
Table 2.1
Table 2.2
Table 2.3
Table 2.4
Table 2.5
Table 3.1
Table 3.2
Table 4.1
Table 5.1
LIST OF TABLES:
1
1
Front Panel Annunciators .........................................................5
8
⁄ DIN Rear Panel Connector.....................................................6
⁄
16
DIN Rear Panel Connector....................................................7
Fuse Requirement......................................................................8
TC Wire Color Chart...................................................................9
Button Function in Configuration Mode......................................13
Conversion Table .......................................................................24
Input Properties..........................................................................47
Factory Preset Values................................................................48 ii
NOTES, WARNINGS and CAUTIONS
Information that is especially important to note is identified by following labels:
• NOTE
• WARNING or CAUTION
• IMPORTANT
• TIP
NOTE: Provides you with information that is important to successfully setup and use the Programmable Digital Meter.
CAUTION or WARNING: Tells you about the risk of electrical shock.
CAUTION, WARNING or IMPORTANT: Tells you of circumstances or practices that can effect the instrument’s functionality and must refer to accompanying documents.
TIP: Provides you helpful hints.
1
PART 1
INTRODUCTION
1.1 Description
This device can be purchased as monitor (read process value only), limit alarm with alarm menu but no PID control (specify -AL option), or as a controller.
• The iSeries Temperature/Process monitors offer unparalleled flexibility in process measurement. Each unit allows the user to select the input type, from 10 thermocouple types (J, K, T, E, R, S, B, C, N and J DIN), Pt RTDs
(100, 500 or 1000 Ω, with either 385 or 392 curve), analog voltage or current input. The voltage/current inputs are fully scalable to virtually all engineering units, with selectable decimal point, perfect for use with pressure, flow or other process input.
• The iSeries device features a large, three color programmable display with capability to change a color every time the Alarm is triggered. The standard features include isolated analog voltage or current output. Options include programmable RS232 or RS485 serial communication and excitation. Analog
Output is fully scaleable and configured as retransmission to follow your display. Universal power supply accepts 90 to 240 Vac. Low voltage power option accepts 24 Vac or 20 to 36 Vdc.
2
1.2 Safety Considerations
This device is marked with the International Caution Symbol. It is
important to read this manual before installing or commissioning this device as it contains important information relating to Safety and EMC
(Electromagnetic Compatibility).
This instrument is a panel mount device protected in accordance with
EN 61010-1:2001, electrical safety requirements for electrical equipment for measurement, control and laboratory. Installation of this instrument should be done by qualified personnel. In order to ensure safe operation, the following instructions should be followed.
This instrument has no power-on switch. An external switch or circuit-
breaker shall be included in the building installation as a disconnecting device. It shall be marked to indicate this function, and it shall be in close proximity to the equipment within easy reach of the operator. The switch or circuit-breaker shall meet the relevant requirements of IEC 947–1 and
IEC 947-3 (International Electrotechnical Commission). The switch shall not be incorporated in the main supply cord.
Furthermore, to provide protection against excessive energy being drawn from the main supply in case of a fault in the equipment, an overcurrent protection device shall be installed.
• Do not exceed voltage rating on the label located on the top of the instrument housing.
• Always disconnect power before changing signal and power connections.
• Do not use this instrument on a work bench without its case for safety reasons.
• Do not operate this instrument in flammable or explosive atmospheres.
• Do not expose this instrument to rain or moisture.
• Unit mounting should allow for adequate ventilation to ensure instrument does not exceed operating temperature rating.
• Use electrical wires with adequate size to handle mechanical strain and power requirements. Install without exposing bare wire outside the connector to minimize electrical shock hazards.
EMC Considerations
• Whenever EMC is an issue, always use shielded cables.
• Never run signal and power wires in the same conduit.
• Use signal wire connections with twisted-pair cables.
• Install Ferrite Bead(s) on signal wires close to the instrument if EMC problems persist.
Failure to follow all instructions and warnings may result in injury!
3
1.3 Before You Begin
Inspecting Your Shipment:
Remove the packing slip and verify that you have received everything listed. Inspect the container and equipment for signs of damage as soon as you receive the shipment. Note any evidence of rough handling in transit. Immediately report any damage to the shipping agent. The carrier will not honor damage claims unless all shipping material is saved for inspection. After examining and removing the contents, save the packing material and carton in the event reshipment is necessary.
Customer Service:
If you need assistance, please call the nearest Customer Service
Department, listed in this manual.
Manuals, Software:
The latest Operation and Communication Manual as well as free configuration software are available at the website listed on the cover
page of this manual.
For first-time users: Refer to the QuickStart Manual for basic operation and set-up instructions.
If you have the Serial Communications Option you can easily configure the controller on your computer.
To Reset the Meter:
When the monitor is in the "MENU" Mode, push c once to direct monitor one step backward of the top menu item.
Push c twice to reset monitor, prior to resuming "Run" Mode except after
"Set Points" and "Alarms", that will go to the "Run" Mode without resetting the monitor.
4
PART 2
SETUP
2.1 Front Panel
Figure 2.1
1 ⁄
8
and
1 ⁄
16
DIN Front Panel Display
Table 2.1 Front Panel Annunciators
1
2
°C
°F a b c d
Setpoint 1/ Alarm 1 indicator (inactive)
Setpoint 2/ Alarm 2 indicator
°C unit indicator
°F unit indicator
Changes display to Configuration Mode and advances through menu items*
Used in Program Mode and Peak Recall*
Used in Program Mode and Valley Recall*
Accesses submenus in Configuration Mode and stores selected values*
* See Part 3 Operation: Configuration Mode
Figure 2.2
1 ⁄
8
and
1 ⁄
16
DIN Rear View
5
2.2
1 ⁄
8
DIN Rear Panel Connections
The rear panel connections are shown in Figure 2.3.
3 2 1 3 2 1
Output 2 is for
-AL Limit Alarm
Option only.
8 7 6 5 4 3 2 1
Figure 2.3
1 ⁄
8
DIN Rear Panel Input Connections
Table 2.2
1 ⁄
8
DIN Rear Panel Connector
POWER AC/DC Power Connector: All models
INPUT Input Connector: All models TC, PR (Process), RTD
OUTPUT 1 Not available
OUTPUT 2 Based on one of the following models: Relay SPDT, Solid State
Relay, Pulse. For -AL Limit Alarm Option only
OUTPUT 3 Isolated Analog (Output Voltage and Current)
OPTION Based on one of the following models:
• RS232C or RS485 programmable
• Excitation
6
2.3
1 ⁄
16
DIN Rear Panel Connections
The rear panel connections are shown in Figure 2.4.
Output 2 is for
-AL Limit Alarm
Option only.
Figure 2.4
1 ⁄
16
DIN Rear Panel Input Connections
Table 2.3
1 ⁄
16
DIN Rear Panel Connector
POWER AC/DC Power Connector: All models
INPUT Input Connector: All models TC, PR (Process), RTD
OUTPUT 1 Not available
OUTPUT 2 Based on one of the following models:
For -AL limit option only
• Relay SPDT
• Solid State Relay
• Pulse
OUTPUT 3 Isolated Analog (Output Voltage and Current)
OPTION
Based on one of the following models:
• RS232C or RS485 programmable
• Excitation
7
2.4 Electrical Installation
2.4.1 Power Connections
Caution: Do not connect power to your device until you have completed all input and output connections. Failure to do so may result in injury!
Connect the main power connections as shown in Figure 2.5.
Figure 2.5 Main Power Connections
Table 2.4 Fuse Requirements (see Specifications)
FUSE
FUSE 1
FUSE 2
Connector
Power
Power
Output Type
N/A
N/A
For 115 Vac 90 - 240 Vac DC
100 mA(T) 100 mA(T) 100 mA(T)
N/A N/A 400 mA(T)
For the low voltage power option, in order to maintain the same degree of protection as the standard high voltage input power units (90 - 240 Vac), always use a Safety Agency Approved DC or AC source with the same
Overvoltage Category and pollution degree as the standard AC unit
(90 - 240 Vac).
The Safety European Standard EN61010-1 for measurement, control, and laboratory equipment requires that fuses must be specified based on
IEC127. This standard specifies for a Time-lag fuse, the letter code “T”.
The above recommended fuses are of the type IEC127-2-sheet III. Be aware that there are significant differences between the requirements listed in the UL 248-14/CSA 248.14 and the IEC 127 fuse standards. As a result, no single fuse can carry all approval listings. A 1.0 Amp IEC fuse is approximately equivalent to a 1.4 Amp UL/CSA fuse. It is advised to consult the manufacturer’s data sheets for a cross-reference.
8
2.4.2 Thermocouple
The figure below shows the wiring hookup for any thermocouple type. For example, for Type K hookup, connect the yellow wire to the "2" terminal and the red wire to the "1(-)" terminal.
When configuring your monitor, select Thermocouple and Thermocouple Type in the Input Type menu (see Part 3).
Figure 2.6 Thermocouple Wiring Hookup
Table 2.4 TC Wire Color Chart
TYPE
J
K
Input Connector
Terminal 1 (-) Terminal 2 (+) Extension
Red White dark-Brown
Red Yellow
Jacket (external insulation) dark-Brown
Grade
Black
Yellow
T
E
N
Red
Red
Red
Blue
Purple
Orange dark-Brown dark-Brown dark-Brown
Blue
Purple
Brown
If the input wires of the meter get disconnected or broken, it will display
+OPN “Input (+) Open” message. For safety purpose you may want to set up your alarm to be triggered when input is open. Be sure to set your
Alarm correctly (see Alarm 2 chapter for details).
9
2.4.3 Two/Three/Four-Wire RTD
The figures below show the input connections and input connector jumpers
(shown in bold lines) required to hookup a 2-, 3- or 4-wire RTD.
RTD (1000/500Ω) 4-Wire
RTD (1000/500Ω) 3-Wire
RTD (1000/500Ω) 2-Wire
RTD (100Ω) 4-Wire
RTD (100Ω) 3-Wire
RTD (100Ω) 2-Wire
Figure 2.7 a) RTD-1000 ohm and
500 ohm Wiring Hookup b) RTD-100 ohm Wiring Hookup
The two-wire connection is simplest method, but does not compensate for lead-wire temperature change and often requires calibration to cancel lead-wire resistance offset.
The three-wire connection works best with RTD leads closely equal in resistance. The device measures the RTD, plus upper and lower lead drop voltage and the subtracts twice the measured drop in the lower supply current lead producing excellent lead-resistance cancellation for balanced measurements.
The four-wire RTD hookup is applicable to unbalanced lead resistance and enables the device to measure and subtract the lead voltage, which produces the best lead-resistance cancellation.
When configuring your instrument, select RTD type and RTD value in the Input
Type menu (see Part 3).
If the input wires of the meter get disconnected or broken, it will display
+OPN “Input (+) Open” message except in case of 500/1000 Ω 2-wire
RTD. In this case the display shows -OPN “Input (-) Open” message. For safety purpose you may want to set up your alarm to be triggered when input is open. Be sure to set your Alarm correctly (see Alarm 2 chapter for details).
10
2.4.4 Process Current
The figure below shows the wiring hookup for Process Current 0 – 20 mA.
Figure 2.8 Process Current Wiring Hookup
(Internal and External Excitation)
When configuring your instrument, select Process Type in the Input Type Menu
(see Part 3).
2.4.5 Process Voltage
The figure below shows the wiring hookup for Process Voltage 0 – 100 mV,
0 – 1 V, 0 – 10 V.
Figure 2.9
a) Process Voltage Wiring Hookup b) Process Voltage Wiring Hookup with Sensor Excitation without Sensor Excitation
R
L
- Voltage limited resistor, which allows to convert 24 Vdc internal excitation voltage to the appropriate process input value. For instance: if the potentiometer value is equal to 10 kΩ, the minimum R
L is 14 kΩ for 10 V process input.
When configuring your instrument, select Process Type in the Input Type Menu
(see Part 3).
11
2.4.6 Wiring Outputs
This meter, if ordered with -AL Limit Alarm Option, has one factory installed output, located at “Output 2”. The SPDT Mechanical Relay, SPST Solid State Relay and
Pulse Output Connection are shown below.
Figure 2.10
a) Relay & SSR Output Wiring Hookup b) Pulse Output Wiring
This device has analog output. The Analog Output Connections are shown below.
Figure 2.11
Analog Output
Wiring Hookup
Use copper conductors only for power connections
This device may also have a programmable communication output. The RS232 and RS485 Output Connection are shown below.
Figure 2.12
a) RS232 Output Wiring Hookup b) RS485 Output Wiring Hookup
This meter is capable of supplying 24 Vdc sensor excitation. The excitation output connection is shown below. This option is not available for low voltage power supply.
12
Figure 2.13
Excitation Output
If your meter has an excitation option, then communication is not available.
PART 3
OPERATION: Configuration Mode
3.1 Introduction
The instrument has two different modes of operation. The first, Run Mode, is used to display values for the Process Variable, and to display or clear Peak and Valley values. The other mode, Menu Configuration Mode, is used to navigate through the menu options and configure the instrument. Part 3 of this manual will explain the Menu Configuration Mode. For your instrument to operate properly, the user must first "program" or configure the menu options.
Turning your Instrument On for the First Time a
MENU b
(UP) c
(DOWN) d
ENTER
The device becomes active as soon as it is connected to a power source. It has no On or Off switch. The device at first momentarily shows the software version number, followed by reset RST, and then proceeds to the Run Mode.
For first-time users: Refer to the QuickStart Manual for basic operation and set-up instructions.
If you have the Serial Communications Option you can easily configure the controller on your computer.
Table 3.1 Button Function in Configuration Mode
• To enter the Menu, the user must first press a button.
• Use this button to advance/navigate to the next menu item. The user can navigate through all the top level menus by pressing a.
• While a parameter is being modified, press a to escape without saving the parameter.
• Press the up b button to scroll through “flashing” selections. When a numerical value is displayed press this key to increase value of a parameter that is currently being modified.
• Holding the b button down for approximately 3 seconds will speed up the rate at which the set point value increments.
• In the Run Mode press b causes the display to flash the PEAK value – press again to return to the Run Mode.
• Press the down c button to go back to a previous Top Level Menu item.
• Press this button twice to reset the monitor to the Run Mode.
• When a numerical value is flashing (except set point value) press c to scroll digits from left to right allowing the user to select the desired digit to modify.
• When a setpoint value is displayed press c to decrease value of a setpoint that is currently being modified. Holding the c button down for approximately 3 seconds will speed up the rate at which the setpoint value is decremented.
• In the Run Mode press c causes the display to flash the VALLEY value – press again to return to the Run Mode.
• Press the enter d button to access the submenus from a Top Level Menu item.
• Press d to store a submenu selection or after entering a value — the display will flash a STRD message to confirm your selection.
• To reset flashing Peak or Valley press d.
Reset: Except for Alarms, modifying any settings of the menu configuration will reset the instrument prior to resuming Run Mode.
13
3.2 Menu Configuration
Figure 3.1 Flow Chart for ID and Set Points
14
3.2.1 ID Number
SEE ID MENU SELECTION IN CONFIGURATION SECTION FOR
ENABLE/DISABLE OR CHANGE ID CODE.
If ID Code is Disabled or set as Default
0000 the menu will skip ID step to Set Point Menu.
If ID Code is set to Full Security Level and user attempts to enter the
Main Menu, they will be prompted for an ID Code.
If ID Code is set to Setpoint/ID Security Level and user attempts to enter the Configuration Menu, they will be prompted for an ID Code.
ENTERING YOUR NON-DEFAULT FULL SECURITY ID NUMBER.
Press a
Press d
1) Display shows ID.
2) Display advances to ____.
Press b & c 3) Press b to increase digit 0-9. Press c to activate next digit
(flashing). Continue to use b and c to enter your 4-digit ID code.
Press d 4) If the correct ID code is entered, the menu will advance to the
Setpoint 1 Menu, otherwise an error message ERRo will be displayed and the instrument will return to the Run Mode.
To change ID Code, see ID Menu in the Configuration section.
ENTERING YOUR NON-DEFAULT SETPOINT/ID SECURITY ID NUMBER.
Press a
Press a
5) Display shows SP2 Setpoint 2 Menu.
6) Display shows ID ID Code Menu.
Press d 7) Display advances to ____.
Press b & c 8) Use b and c to change your ID Code.
Press d 9) If correct ID Code is entered, the display will advance to the
INPT Input Menu, otherwise the error message ERRo will be displayed and the instrument will return to the Run Mode.
To prevent unauthorized tampering with the setup parameters, the instrument provides protection by requiring the user to enter the ID Code before allowing access to subsequent menus. If the ID Code entered does not match the ID Code stored, the instrument responds with an error message and access to subsequent menus will be denied.
Use numbers that are easy for you to remember. If the ID Code is forgotten or lost, call customer service with your serial number to access and reset the default to 0000.
15
3.2.2 Set Points
SETPOINT 2:
For this model with isolated Analog Output the Setpoint 1 is inactive.
Press a
Press d
1) Press a, if necessary until respectively.
SP2 prompt appears.
2) Display shows previous value of “Setpoint 2” with 1 flashing.
Press b & c 3) Press b and c to increase or decrease Setpoint 2 st digit
Holding b & c buttons down for approximately 3 seconds will speed up the rate at which the setpoint value increments or decrements.
Press d 4) Display shows STRD stored message momentarily and then advances to CNFG only, if a change was made, otherwise press a to advance to CNFG Configuration Menu.
16
3.2.3 Configuration Menu
Figure 3.2 Flow Chart for Configuration Menu
Enter Configuration Menu:
Press
Press
Press a d a
1) Press a, if necessary, until CNFG prompt appear.
2) Display advance to INPT Input Menu.
3) Pressing and releasing a to scroll through all available menus of Configuration section.
3.2.4 Input Type Menu
Figure 3.3 Flow Chart for Input Type Menu
17
Input Type (Thermocouple)
ENTER INPUT TYPE MENU:
Press
Press
Press a d d
1) Press a, if necessary, until CNFG prompt appears.
2) Display advance to INPT Input Menu.
3) Display flashes T.ç, RTD or PROC (Thermocouple, RTD or
Process). If the displayed input type is T.ç, press a to skip to step 6 ( T.ç stops flashing).
THERMOCOUPLE SUBMENU:
Press b
Press d
Press d
Press b
Press d
4) Scroll through the available selection to T.ç (flashing).
5) Display shows STRD stored message momentarily and then
T.ç (not flashing).
6) Display flashes previous thermocouple type selection. i.e. J
(see below for types).
7) Scroll through the available thermocouple types to the selection of your choice.
8) Display shows STRD stored message momentarily and then advances to the RDG Reading Configuration Menu.
Use the Input Type (Thermocouple) (RTD) or (Process) and verify your
Electrical Installation (see Section 2.3).
See the following pages for (TC), (RTD), (Process) menus.
Thermocouple Types: J, K, T, E, N, DIN J, R, S, B, C
Display: J K T E N DNJ R S B C
18
Input Type (RTD)
ENTER INPUT TYPE MENU:
Press
Press
Press a d d
RTD SUBMENU:
1) Press a, if necessary, until CNFG prompt appears.
2) Display advances to INPT Input Menu.
3) Display flashes T.ç, RTD or PROC (Thermocouple, RTD or
Process). If the displayed input type is RTD, press a to skip to step 6 ( RTD stops flashing).
Press
Press
Press
Press
Press b d d b d
4) Scroll through the available selection to RTD (flashing).
5) Display shows STRD stored message momentarily and then
RTD (not flashing).
6) Display flashes previous RTD type selection i.e. 392.2
(see below for RTD types selection).
7) Scroll through the available RTD types to the selection of your choice.
8) Display shows STRD stored message momentarily and then advances to RTD RTD value.
RTD Types: 392 385 Two, Three or Four-wire
Display: 392.2, 392.3, 392.4, 385.2, 385.3, 385.4
Last digit indicates: 2-, 3- or 4-wire input.
RTD VALUE SUBMENU:
Press
Press
Press d b d
9) Display flashes previous RTD value selection i.e. 100_
(see below for RTD value selection).
10) Scroll through the available RTD values to the selection of your choice.
11) Display shows STRD stored message momentarily and then advances to RDG Reading Configuration Menu.
RTD Values: 100 ohm
Display: 100_
500 ohm 1000 ohm
500_ 1000
19
Input Type (Process)
ENTER INPUT TYPE MENU:
Press
Press
Press a d d
1) Press a, if necessary, until CNFG prompt appears.
2) Display advance to INPT Input Menu.
3) Display flashes T.ç, RTD or PROC (Thermocouple, RTD or
Process). If the displayed input type is PROC, press a to skip to step 6 ( PROC stops flashing).
PROCESS SUBMENU:
Press
Press
Press
Press
Press b d d b d
4) Scroll through the available selection to PROC (flashing).
5) Display shows STRD stored message momentarily and then
PROC (not flashing).
6) Display flashes previous Process type selection. i.e.
0-10
(see below for Process types selection).
7) Scroll through the available Process types to the selection of your choice.
8) Display shows STRD stored message and then advances to
RDG Reading Configuration Menu.
Process Types: 100 mV 1 V
Display:
10 V 0 – 20 mA
0-0.1 0-1.0 0-10 0-20
For 4-20 mA Input select 0-20 mA and adjust the Input/Reading accordingly.
To adjust 4-20 mA input, see example under Input/Reading Submenu.
20
3.2.5 Reading Configuration Menu
Figure 3.4 Flow Chart for Reading Configuration Menu
ENTER READING CONFIGURATION MENU:
Press a
Press d
Press a
Press d
1) Press a, if necessary, until CNFG prompt appears.
2) Display advances to
3) Display advances to
4) Display advances to
DECIMAL POINT SUBMENU:
INPT Input Menu.
RDG Reading Configuration Menu.
DEC Decimal Point.
Press d
Press b
Press d
5) Display flashes previous selection for Decimal location.
6) Scroll though the available selections and choose Decimal location: FFFF or FFF.F (also FF.FF and F.FFF — if PROC
Process type was selected in the Input Type Menu).
7) Display shows STRD stored message momentarily and then advances to TEMP Temperature Unit.
Decimal Point for Process Input Type is passive.
21
TEMPERATURE UNIT SUBMENU:
Press
Press
Press d b d
8) Display flashes previous Temperature Unit selection.
9) Scroll though the available selections to the Temperature Unit of your choice: °F or °C.
10) Display shows STRD stored message momentarily and then advances to FLTR Filter Constant.
FILTER CONSTANT SUBMENU:
Press d
Press b
Press d
11) Display flashes previous selection for Filter Constant.
12) Scroll though the available selections:
13) Display shows
0001, 0002, 0004,
0008, 0016, 0032, 0064, 0128. - Default is 0004
STRD stored message momentarily only, if a change was made, otherwise press a to advance to the next menu.
If Process was selected in the Input Type Menu the display will advance to IN.RD Input/Reading Submenu, otherwise the display advances to the ALR1 Alarm Menu.
The Filter Constant Submenu allows the user to specify the number of readings stored in the Digital Averaging Filter.
For PID control select filter value 0001-0004. A filter value of 2 is approximately equal to 1 second RC low pass time constant.
22
Reading Configuration (If Process was selected)
INPUT/READING (SCALE AND OFFSET) SUBMENU:
Input Voltage or Current can be converted or scaled into values appropriate for the process or signal being measured. So, a reading may be displayed, for example, in units of weight or velocity instead of in amperes or volts.
The instrument determines Scale and Offset values based on two user-provided input values entered with the corresponding readings. Note that
IN1 Input 1 and
IN!2 Input 2 are represented and entered as a product of the input voltage/current and the conversion number from the Table 3.2.
The following instructions include details for a specific scenario in which a
4-20 mA input (in the 20 mA Process Mode) is to be represented as a measurement of 0-100 percent.
Press d
Press d
14) Press d at the IN.RD prompt. Display shows IN1 Input 1
Submenu.
15) Display shows Input 1 value with 1 st digit flashing.
Press b & c 16) Use b and c buttons to enter IN1 value.
The IN1 value = min. input value * conversion number.
Disregard the position of the decimal point (2000 counts may actually appear as
2000, 200.0, 20.00, or 2.000 ).
Example: 4 mA as 4(mA) x 500 = 2000.
Press d 17) Display advances to RD1 Reading 1 Submenu.
Press b & c 18) Use b and c buttons to enter RD1 value.
This value represents IN1 in terms of some meaningful engineering units. To show the 4 mA as zero percent enter RD1 value = 0000.
Example: RD1 value = 0000.
Press
Press d d
19) Display
IN!2 Input 2 Submenu.
20) Display shows Input 2 value with 1 st digit flashing.
The
IN!2 value = max. input value * conversion number.
Example: 20(mA) x 500 = 10000 (9999).
Press
Press
Press b & c 21) Use b and c buttons to enter IN!2 value.
d 22) Display advances to b & c 23) Use b and c buttons to enter RD!2 value.
Example:
RD!2 value = 0100.
Press d 24) Display flashes STRD stored message momentarily and then advances to ALR1 only, if change was made, otherwise press d to advance to ALR1 Alarm Menu.
23
Conversion number is a coefficient of conversion between input values and real full display range (10000 counts, shown as 9999). See Table 3.2 below for proper conversion number.
Table 3.2 Conversion Table
RANGE
100 mV
1 V
10 V
0 -20 mA
CONVERSION NUMBER
10000 / (100 x 1) = 100
10000 / (1000 x 1) = 10
10000 / (1000 x 10) = 1
10000 / (20 x 1) = 500
Example =
0 - 1 V = 0 - 100.0
In 1 = 0
Rd 1 = 0
Inp 2 = 9999
Rd 2 = 100.0
24
3.2.6 Analog Output (Retransmission)
Figure 3.5 Flow Chart for Analog Output (Retransmission)
ENTER ANALOG OUTPUT MENU:
Press a
Press d
Press
Press a d
1) Press a, if necessary, until CNFG prompt appears.
2) Display advances to INPT Input Menu.
3) Press a, if necessary, until Display advances to ANLG
Analog Output Menu.
4) Display advances to Analog Output CURR or VoLT
Current/Voltage Submenu and flashes the previous selection.
CURRENT/VOLTAGE SUBMENU:
Press
Press
Press d b d
5) Display flashes CURR Current or VoLT Voltage.
6) Scroll through the available selection: Current or Voltage.
(Example VoLT).
7) Display shows STRD stored message momentarily and then advances to RD1 Submenu only if it was changed, otherwise press a to advance to RD1 Reading 1 Submenu.
READING 1:
Press d
Press b & c 9) Enter “Reading 1” value. (Example 0000).
Press d
8) Display flashes 1 st digit of previous “Reading 1” value.
10) Display advances to OUT.1 Out 1 Submenu.
OUT 1:
Press d 11) Display flashes 1 st digit of previous “Out 1” value.
Press b & c 12) Enter “Out 1” value. (Example 00.00).
Press d 13) Display advances to
RD!2 Reading 2 Submenu.
25
READING 2:
Press d 14) Display flashes 1 st digit of previous “Reading 2” value.
Press b & c 15) Enter “Reading 2” value. (Example 9999).
Press d 16) Display advances to OUT.2 Out 2 Submenu.
OUT 2:
Press d
Press b & c 18) Enter “Out 2” value. (Example 10.00)
Press d
17) Display flashes 1 st digit of previous “Out 2” value.
19) Display advances to the ALR2 Alarm 2 Menu.
The above example is for 0-10 V output of the entire range of the
Process Input and Analog Output. For 0-20 mA output you need to set
“Analog Type” to Current and OUT 2 to 20.00.
26
3.2.7 Alarm 1
For this model with Isolated Analog Output, Alarm 1 is inactive.
3.2.8 Alarm 2
Figure 3.6 Flow Chart for Alarm 2
ENTER ALARM MENU:
Press a
Press d
Press a
Press d
1) Press a, if necessary, until CNFG prompt appears.
2) Display advances to INPT Input Menu.
3) Press a, if necessary, until Display advances to ALR2 Alarm
Menu.
4) Display advances to the ABSo Absolute/Deviation Submenu.
27
ALARM ABSOLUTE/DEVIATION SUBMENU:
Press
Press d d
5) Display flashes previous selection. Press b to ABSo Absolute or _DEV Deviation.
6) Display shows STRD stored message momentarily and then advances to LTçH only, if it was changed, otherwise press a to advance to LTçH Alarm Latch/Unlatch Submenu.
Absolute Mode allows Alarm to function independently from Setpoint 1. If the process being monitored does not change often, then "Absolute" Mode is recommended.
Deviation Mode allows changes to Setpoint 1 to be made automatically to
Alarm. Deviation Mode is typically the ideal mode if the process temperature changes often. In Deviation Mode, set Alarm a certain number of degrees or counts away from Setpoint 1 — this relation remains fixed even if Setpoint 1 is changed.
ALARM 2 LATCH/UNLATCH SUBMENU:
Press
Press d d
7) Display flashes previous selection. Press b to LTçH Latched or UNLT Unlatched.
8) Display shows STRD stored message momentarily and then advances to CT.CL only, if it was changed, otherwise press a to advance to CT.CL Contact Closure Submenu.
Latched Mode: Relay remains "latched" until reset. To reset already latched alarm, select Alarm Latch and press Max twice (i.e. Unlatch and then back to
Latch) or from a Run Mode, push d twice to put the instrument in Standby Mode and then push done more time to return to the Run Mode.
Unlatched Mode: Relay remains latched only as long as the alarm condition is true.
28
ACTIVE SUBMENU:
Press
Press d d
9) Display flashes previous selection. Press b to scroll through the available selections: ABoV Above, BELo Below, HI.Lo
HI/Low and BAND Band. (Band is active if _DEV Deviation was selected).
10) Display shows STRD stored message momentarily and then advances to ALR.L only, if it was changed, otherwise press a to advance to ALR.L Alarm Low Value Submenu.
Above: Alarm 2 condition triggered when the process variable is greater than the
Alarm Hi Value (Low value ignored).
Below: Alarm 2 condition triggered when the process variable is less than the
Alarm Low Value (Hi value ignored).
Hi/Low: Alarm 2 condition triggered when the process variable is less than the
Alarm Low Value or above the Hi Value.
Band: Alarm 2 condition triggered when the process variable is above or below the "band" set around Setpoint 2. Band equals Hi Value (Low Value ignored). A
"band" is set around the Setpoint by the instrument only in the "Deviation" Mode.
The Band for the AL 2 would be following the Setpoint 2 value.
The Band or the Deviation Value should be entered under:
AL2 High (if they want Alarm 2)
AL Low value is ignored in the Band mode.
Example: if customer requires a Deviation Value of ±10 degrees around a setpoint (using Output 2 as alarm)
Output 2: disabled (this enables the Alarm 2)
Alarm 2: - Deviation
Contact Closure type: Deviation---Band
AL2 High: 10 (Band they want around Setpoint 2) then the band value is to be entered under AL2 HI: 10 not 80 +10 = 90
29
ALARM LOW VALUE SUBMENU:
Press d 11) Display flashes 1 st enter new value.
digit of previous value. Use b and c to
Press b & c 12) Use b and c to enter Alarm Low Value.
Press d 13) Display shows STRD storage message momentarily and then advances to ALR.H only, if it was changed, otherwise press a to advance to ALR.H Alarm Hi Value Submenu.
ALARM HI VALUE SUBMENU:
Press d 14) Display flashes 1 st digit of previous value. Use b and c to enter new value.
Press b & c 15) Use b and c to enter Alarm Hi Value.
Press d 16) Display shows STRD stored message momentarily and then advances to the next menu only, if it was changed, otherwise press a to advance to the next menu.
30
3.2.9 Reading Adjust Menu / Field Calibration
ENTER READING ADJUST MENU:
Press a
Press d
Press a
1) Press
3) Press a, if necessary, until CNFG prompt appears.
2) Display advances to
Reading Adjust Menu.
INPT Input Menu.
a, if necessary, until Display advances to R.ADJ
READING ADJUST VALUE SUBMENU:
Press d 4) Display flashes 1 st digit of previous Reading Adjust value.
Press b & c 5) Press b and c buttons to enter a new Reading Adjust value
Press d
(-1999 to 9999).
6) Display shows STRD stored message momentarily and then advances to the CAL1 Menu.
For Temperature Reading only, not Process
Reading Offset Adjust allows the user to fine tune a minor error of the transducer, however some applications may require a large offset adjust.
(Displayed Process Value = Measured Process
Value ±R.ADJ).
Reading Adjust value is adjustable between
-1999 to 9999.
Figure 3.7 Flow Chart for
Reading Adjust Menu / Field
Calibration
THERMOCOUPLE FIELD CALIBRATION SUBMENU:
CAUTION: Do not perform the following steps until you fully understand this entire section.
RTD and Process are perfectly calibrated. This section is applicable to
Thermocouple (TC) calibration only.
Be sure that the TC being used to calibrate the meter is of the type selected in the TC submenu. Place the TC in an ice-bath (or other
0°C / 32°F environment). In ambient temperature conditions: connect the
TC to the meter, apply power to the meter.
CAUTION: Do not proceed with TC calibration unless the above conditions have been in effect for at least one hour.
Press a
Press d
Press a
Press d
7) Display shows CAL1.
8) Display shows flashing 0000.
9) Display will still show flashing 0000.
10) Display shows OUT1 (meaning Calibration is complete)
* If you accidently engage the flashing 0000 (CAL° alert) simply re-press the last button you pressed, to avoid unintentionally mis-calibrating your meter.
31
3.2.10 ID CODE
Figure 3.8 Flow Chart for ID Code Menu
ENTER ID CODE MENU:
Press
Press
Press a d a
1) Press a, if necessary, until CNFG prompt appears.
2) Display advances to INPT Input Menu.
3) Press a, if necessary, until Display advances to ID ID Code
Menu.
ENTERING OR CHANGING YOUR (NON-DEFAULT) ID CODE:
Press d 4) Display advances to ____ with 1 st under score flashing.
Press b & c 5) Press b and c to enter your 4-digit “ID Code” number.
Press d 6) Display advances to CH.ID Change ID Code Submenu.
If entered “ID Code” is incorrect display shows ERRo Error message momentarily and then skips to the Run Mode.
Press d 7) Display flashes the first digit of previous entered “ID Code” number.
Press b & c 8) Press b and c buttons to enter your new “ID Code” number.
Press d 9) Display shows STRD stored message momentarily and then advances to the FULL Full Security Submenu.
32
ENTERING OR CHANGING YOUR (DEFAULT) ID CODE:
Press
Press d d
Enter ID menu (Repeat steps from 1 to 3).
10) Display advances to CH.ID Change ID Code Submenu.
11) Display shows 0000 message with flashing 1 st digit.
If you want to change your default “ID Code” you can do it now, otherwise press a and menu will skip to FULL Full Security
Submenu.
Press b & c 12) Press b and c buttons to enter your new “ID Code” number.
Press d 13) Display shows STRD stored message momentarily and then advances to the FULL Full Security Submenu.
FULL SECURITY LEVEL SUBMENU:
Press
Press
Press d b d
14) Display flashes ENBL Enable or DNBL Disable.
15) Scroll through the available selections: “Enable” or “Disable”.
16) Display shows STRD stored message momentarily and then advances to SP.ID Setpoint/ID Submenu.
If "Full" Security Level is "Enabled" and the user attempts to enter the Main Menu, they will be prompted for an ID Code. The
ID Code should be correct to enter the instrument Menu item.
SETPOINT/ID SECURITY LEVEL SUBMENU:
This Security Level can be functional only if FULL Security
Level is Disabled.
Press
Press
Press d b d
17) Display flashes ENBL Enable or DNBL Disable.
18) Scroll through the available selections: “Enable” or “Disable”.
19) Display shows STRD stored message momentarily and then advances to COMM Communication Submenu.
If "Setpoint/ID" Security Level is "Enabled" and the user attempts to advance into the CNFG Configuration Menu, he will be prompted for ID Code number. The ID Code should be correct to proceed into the Configuration Menu, otherwise display will show an Error and skip to the Run Mode.
If “Full” and “Setpoint/ID” Security Levels are "Disabled", the ID code will be “Disabled” and user will not be asked for ID Code to enter the Menu items (“ID” Submenu will not show up in
“ID/Setpoint” Menu).
33
3.2.11 COMMUNICATION OPTION
Purchasing the device with Serial Communications permits an instrument to be configured or monitored from an IBM PC compatible computer using software available at the website listed on the cover of this manual. For complete instructions on the use of the Communications Option, refer to the Serial Communications
Reference Manual.
Figure 3.9 Flow Chart for Communication Option
34
ENTER COMMUNICATION OPTION MENU:
Press a
Press d
Press a
Press d
1) Press
3) Press a, if necessary, until CNFG prompt appears.
2) Display advances to a, if necessary, until Display advances to COMM
Communication Options Menu.
4) Display advances to
Submenu.
INPT Input Menu.
C.PAR Communication Parameters
If Communication Option is not installed, the display shows
NONE and skips to the Color Display Menu.
COMMUNICATION PARAMETERS SUBMENU:
Allows the user to adjust Serial Communications Settings of the instrument.
When connecting an instrument to a computer or other device, the
Communications Parameters must match. Generally the default settings
(as shown in Section 5) should be utilized.
Press d 5) Display advances to BAUD Baud Submenu.
BAUD SUBMENU:
Press
Press
Press d b d
6) Display flashes previous selection for BAUD value.
7) Scroll through the available selections: 300_, 600_, 1200,
2400, 4800, 9600, 19.2K.
8) Display shows STRD stored message momentarily and then advances to PRTY only, if it was changed, otherwise press a to advance to DATA Parity Submenu.
PARITY SUBMENU:
Press
Press
Press d b d
9) Display flashes previous selection for “Parity”.
10) Scroll through the available selections: NO, ODD, EVEN.
11) Display shows STRD stored message momentarily and then advances to DATA only, if it was changed, otherwise press a to advance to DATA Data Bit Submenu.
DATA BIT SUBMENU:
Press d
Press b
Press d
12) Display flashes previous selection for “Data Bit”.
13) Scroll through the available selections: 7-BIT, 8-BIT.
14) Display shows STRD stored message and then advances to
STOP only, if it was changed, otherwise press a to advance to
STOP Stop Bit Submenu.
35
STOP BIT SUBMENU:
Press d
Press b
Press d
15) Display flashes previous selection for “Stop Bit”.
16) Scroll through the available selections: 1-BIT, 2-BIT.
17) Display shows STRD stored message momentarily and then advances to BUS.F only, if it was changed, otherwise press a to advance to BUS.F Bus Format Submenu.
BUS FORMAT SUBMENU:
Determines Communications Standards and Command/Data Formats for transferring information into and out of the instrument via the Serial
Communications Bus. Bus Format submenus essentially determine how and when data can be accessed via the Serial Communications of the device.
Press d 18) Display advances to M.BUS Modbus Submenu.
MODBUS PROTOCOL SUBMENU:
Press
Press
Press d b d
19) Display flashes previous selection for M.BUS.
20) Scroll through the available selections: NO, YES.
21) Display shows STRD stored message momentarily and then advances to _LF_ only, if it was changed, otherwise press a to advance to _LF_ Line Feed submenu.
To select iSeries Protocol, set Modbus submenu to “No”.
To select Modbus Protocol, set Modbus submenu to “Yes”.
If Modbus Protocol was selected, the following Communications
Parameters must be set as: No Parity, 8-bit Data Bit, 1-Stop Bit. Do not attempt to change these parameters.
LINE FEED SUBMENU:
Determines if data sent from the instrument will have a Line Feed appended to the end - useful for viewing or logging results on separate lines when displayed on communications software at a computer.
Press d
Press b
Press d
22) Display flashes previous selection for “Line Feed”.
23) Scroll through the available selections: NO, YES.
24) Display shows STRD stored message momentarily and then advances to ECHO only, if it was changed, otherwise press a to advance to ECHO Echo Submenu.
36
ECHO SUBMENU:
When valid commands are sent to the instrument, this determines whether the command will be echoed to the Serial Bus. Use of echo is recommended in most situations, especially to help verify that data was received and recognized by the instrument.
Press
Press
Press d b d
25) Display flashes previous selection for “Echo”.
26) Scroll through the available selections: NO, YES.
27) Display flashes STRD stored message momentarily and then advances to STND only if it was changed, otherwise press a to advance to STND Communication Standard Submenu.
COMMUNICATION INTERFACE STANDARD SUBMENU:
Determines whether device should be connected to an RS232C serial port
(as is commonly used on IBM PC-compatible computers) or via an RS485 bus connected through appropriate RS232/485 converter. When used in RS485
Mode, the device must be accessed with an appropriate Address Value as selected in the Address Submenu described later.
Press
Press
Press d b d
28) Display flashes previous selection for “Standard”.
29) Scroll through the available selections: 232C, 485.
30) Display shows STRD stored message momentarily and then advances to MoDE only, if it was changed, otherwise press a to advance to MoDE Data Flow Mode Submenu.
DATA FLOW MODE SUBMENU:
Determines whether the instrument will wait for commands and data requests from the Serial Bus or whether the instrument will send data automatically and continuously to the Serial Bus. Devices configured for the RS485
Communications Standard operate properly only under Command Mode.
Press d
Press b
Press d
31) Display flashes previous selection for “Mode”.
32) Scroll through the available selections:
CoNT “Continuous”.
33) Display shows
CMD_ “Command”,
STRD stored message momentarily and then advances to SEPR only, if it was changed, otherwise press a to advance to SEPR Data Separation Submenu.
37
DATA SEPARATION CHARACTER SUBMENU:
Determines whether data sent from the device in Continuous Data Flow Mode will be separated by spaces or by Carriage Returns.
Press
Press
Press d b d
34) Display flashes previous selection for “Separation” Submenu.
35) Scroll through the available selections: SPCE “Space” or
_çR_ “Carriage Return”.
36) Display shows STRD stored message momentarily and then advances to DAT.F only, if it was changed, otherwise press a to advance to DAT.F Data Format Submenu.
DATA FORMAT SUBMENU:
Preformatted data can be sent automatically or upon request from the instrument.
Use the Data Format Submenus to determine what data will be sent in this preformatted data string. Refer to the iSeries Communications Manual for more information about the data format. At least one of the following suboptions must be enabled and hence output data to the Serial Bus.
This menu is applicable for Continuous Mode of RS232 communication.
Press d 37) Display advances to
ALARM STATUS SUBMENU:
STAT Alarm Status Submenu.
Includes Alarm Status bytes in the data string.
Press
Press
Press d b d
38) Display flashes previous selection for “Status” (alarm status).
39) Scroll through the available selections: NO, YES.
40) Display shows STRD stored message momentarily and then advances to RDNG only, if it was changed, otherwise press a to advance to RDNG Reading Submenu.
MAIN READING SUBMENU:
Includes Main Reading in the data string.
Press d
Press b
Press d
41) Display flashes previous selection for “Reading”.
42) Scroll through the available selections: NO, YES.
43) Display shows STRD stored message momentarily and then advances to PEAK only, if it was changed, otherwise press a to advance to PEAK Peak Submenu.
38
PEAK VALUE SUBMENU:
Includes Peak Value in the data string.
Press
Press
Press d b d
44) Display flashes previous selection for PEAK Submenu.
45) Scroll through the available selections: NO, YES.
46) Display shows STRD stored message momentarily and then advances to VALY only, it was changed, otherwise press a to advance to VALY Valley Submenu.
VALLEY VALUE SUBMENU:
Includes Valley Value in the data string.
Press d
Press b
Press d
47) Display flashes previous selection for “Valley”.
48) Scroll through the available selections: NO, YES.
49) Display shows STRD stored message momentarily and then advances to UNIT only, if it was changed, otherwise press a to advance to UNIT Temperature Unit Submenu.
TEMPERATURE UNIT SUBMENU:
Includes a byte in the data string to indicate whether reading is in Celsius or
Fahrenheit.
Press
Press
Press d b d
50) Display flashes previous selection for UNIT.
51) Scroll through the available selections: NO, YES.
52) Display shows STRD stored message momentarily and then advances to ADDR only, if it was changed, otherwise press a to advance to ADDR Address Setup Submenu.
ADDRESS SETUP SUBMENU:
This menu is applicable to the RS485 Option only.
Press d 53) Display advances to “Address Value” (0000 to 0199) Submenu.
ADDRESS VALUE SUBMENU:
Press d
Press b & c 55) Press b and c to enter new “Address Value”.
Press d
54) Display flashes 1
56) Display shows st digit of previously stored Address Value.
STRD stored message momentarily and then advances to TR.TM only, if it was changed, otherwise press a to advance to TR.TM Transmit Time Interval Submenu.
39
TRANSMIT TIME INTERVAL SUBMENU:
This menu is applicable if “Continuous” Mode was selected in the “Data
Flow Mode” Submenu and the device is configured as an RS232C
Standard device. Also, one or more options under the Data Format
Submenu must be enabled.
Press d 57) Display advances to “Transmit Time Value” Submenu.
TRANSMIT TIME INTERVAL VALUE SUBMENU:
Determines the interval at which data will be emitted to the RS232 Serial Bus when the instrument is in Continuous Data Flow Mode.
Press d 58) Display flashes 1 st digit of previous “Transmit Time Value” in seconds.
Press b & c 59) Press b and c to enter new “Transmit Time Value”, e.g.
0030 will send the data every 30 seconds in Continuous Mode.
Press d 60) Display shows STRD stored message momentarily and then advances to COLR only, if it was changed, otherwise press a to advance to COLR Color Display Selection Menu.
For more details, refer to the Communication Manual available at the website listed on the cover page of this manual.
40
3.2.12 DISPLAY COLOR SELECTION
This submenu allows the user to select the color of the display.
Figure 3.10 Flow Chart for Display Color Selection
ENTER DISPLAY COLOR SELECTION MENU:
Press
Press
Press a d a
Press d
1) Press a, if necessary, until CNFG prompt appears.
2) Display advances to INPT Input Menu.
3) Press a, if necessary, until Display advances to COLR
Display Color Selection Menu.
4) Display advances to N.CLR Normal Color Submenu.
NORMAL COLOR DISPLAY SUBMENU:
Press d
Press b
Press d
5) Display flashes the previous selection for “Normal Color”.
6) Scroll through the available selections:
7) Display shows
GRN, RED or AMBR.
STRD stored message momentarily and then advances to 2.CLR only, if it was changed, otherwise press a to advance to 2.CLR Alarm 2 Display Color Submenu.
The menu below allows the user to change the color of display when alarm is triggered.
41
ALARM 2 DISPLAY COLOR SUBMENU:
Press
Press
Press d b d
8) Display flashes previous selection for “Alarm Color Display”.
9) Scroll through the available selections: GRN, RED or AMBR.
10) Display shows STRD stored message momentarily and then momentarily shows the software version number, followed by
RST Reset, and then proceeds to the Run Mode.
IN ORDER TO DISPLAY ONE COLOR, SET THE SAME DISPLAY
COLOR ON BOTH SUBMENUS ABOVE.
Example 1:
Alarm 2 Setup: Absolute, Above, Alarm 2 HI Value “ALR.H” = 200,
Color Display Setup: Normal Color “N.CLR” = Green, Alarm 2 Color
“2.CLR” = Red
Display Colors change sequences:
GREEN RED
•--
‰------------------------------•-----------------------------------------------------------‰
0 AL2.H = 200
Example 2:
Alarm 2 Setup: Absolute, Below, Alarm 2 Low Value “ALR.L” = 300,
Color Display Setup: "N.CLR" = Green, "2.CLR" = Red
Display Colors change sequences:
‰ RED GREEN ‰
• ------------------------------------------------•------------------------------------------- --•
0 AL2.L = 300
42
Example 3:
Setpoint 2: 200
Alarm 2 Setup: Deviation, Band, “ALR.H” = 10
Color Display Setup: “N.CLR” = Green, “2.CLR” = Amber
Display Colors change sequences:
AMBER GREEN AMBER
•
‰---------------•------•------•---------------------------------------------------------------------‰
0 190 200 210
Example 4:
Setpoint 2: 200
Alarm 2 Setup: Deviation, Hi/Low, “ALR.H” = 10, “ALR.L” = 5
Color Display Setup: “N.CLR” = Green, “2.CLR” = Red
Display colors change sequences:
RED GREEN RED
•
‰---------------•------•------•---------------------------------------------------------------------‰
0 195 200 210
Reset: The instrument automatically resets after the last menu of the
Configuration Mode has been entered. After the instrument resets, it advances to the Run Mode.
43
PART 4
SPECIFICATIONS
Accuracy
±0.5°C temp; 0.03% reading process
Thermocouple Lead Resistance
100 ohm max
Resolution
1°/0.1°; 10 μV process
RTD Input (ITS 68)
100/500/1000 Ω Pt sensor, 2-, 3- or
4-wire; 0.00385 or 0.00392 curve
Temperature Stability
1) RTD: 0.04°C/°C
2) TC @ 25°C (77°F): 0.05°C/°C
- Cold Junction Compensation
3) Process: 50 ppm/°C
Voltage Input
0 to 100 mV, 0 to 1 V, 0 to 10 Vdc
NMRR
60 dB
Input Impedance
10 MΩ for 100 mV
1 MΩ for 1 or 10 Vdc
Current Input
0 to 20 mA (5 ohm load) CMRR
120 dB
A/D Conversion
Dual slope
Configuration
Single-ended
Reading Rate
3 samples per second
Polarity
Unipolar
Digital Filter
Programmable
Step Response
0.7 sec for 99.9%
Display
4-digit, 9-segment LED,
21 mm (0.83”)
1
10.2 mm (0.40")
⁄
8
1 ⁄
DIN
16
DIN red, green and amber programmable colors for process variable, set point and temperature units
Decimal Selection
None, 0.1 for temperature
None, 0.1, 0.01 or 0.001 for process
Setpoint Adjustment
-1999 to 9999 counts
Span Adjustment
0.001 to 9999 counts
Warm up to Rated Accuracy
30 min.
Thermocouple Type (ITS90)
J, K, T, E, R, S, B, C, N, L
Offset Adjustment
-1999 to +9999
INPUT
Input Types
Thermocouple, RTD, Analog Voltage,
Analog Current
44
ANALOG OUTPUT (programmable)
Isolated, Retransmission 0 to 10 Vdc or
0 to 20 mA, 500 Ω max.
Accuracy is 1% of FS, for Scaling Gain from 0.03 to 100 mV per count
Isolation is 1000 Vdc
Linearity is 0.2%
COMMUNICATIONS
(Optional in place of excitation)
RS232/RS422/RS485/MODBUS:
Selectable from menu; both ASCII and modbus protocol selectable from menu. Programmable 300 to 19.2 K baud; complete programmable setup capability; program to transmit current display, alarm status, min/max, actual measured input value and status.
RS485
Addressable from 0 to 199
ALARM 2 (programmable):
Type
Programmable to display color change
Relay*
250 Vac or 30 Vdc @ 3 A
(Resistive Load)
Output 1: not available
Output 2*: SPDT type, can be configured as Alarm 2 output
SSR*
20-265 Vac @ 0.05-0.5 A
(Resistive Load); continuous
DC Pulse*
Non-Isolated; 10 Vdc @ 20 mA
* Only with -AL Limit Alarm Option
Operation
High/low, above/below, latch/unlatch, normally open/normally closed and process/deviation; front panel configurations
EXCITATION
(optional in place of Communication)
24 Vdc @ 25 mA
Not available for Low Power Option
APPROVALS
FM, UL, C-UL, and see CE Approval Section
INSULATION
Power to Input/Output,
2300 Vac per 1 min. test,
1500 Vac per 1 min. test,
(Low Power Option)
Power to Relays/SSR Outputs,
2300 Vac per 1 min. test
Relays/SSR to Relay/SSR Outputs,
2300 Vac per 1 min. test
RS232/485 to Inputs/Outputs,
500 Vac per 1 min. test
GENERAL
Line Voltage/Power
90-240 Vac +/-10%, 50-400 Hz*
110-375 Vdc, equivalent voltage
5 W, power consumption
* No CE compliance above 60 Hz
Low Voltage/Power Option
20-36 Vdc, 4 W**, power consumption
External power source must meet
Safety Agency Approvals.
** Units can be powered safely with 24 Vac but, no Certification for CE/UL are claimed.
External Fuse Required
Time-Delay, UL 248-14 listed:
100 mA/250 V
400 mA/250 V
(Low Voltage/Power Option)
Time-Lag, IEC 127-3 recognized:
100 mA/250 V
400 mA/250 V
(Low Voltage/Power Option)
Environmental Conditions
0 to 55°C (32 to 131°F),
90% RH non-condensing
0 to 50°C (32 to 122°F) for UL only.
90% RH non-condensing
Protection
NEMA 1 (Type 1) front bezel
1
NEMA 4 (IP65) front bezel 1
⁄
8
DIN
⁄
16
DIN
45
4.1 Mounting
46
Dimensions
48 H x 96 W x 127 mm D
(1.89 x 3.78 x 5")
Panel Cutout
45 H x 92 W mm
(1.772" x 3.622 ")
Weight
295 g (0.65 lb)
4.2
1 ⁄
16
DIN Mounting
47
Dimensions
48 H x 48 W x 127 mm D
(1.89 x 1.89 x 5")
Panel Cutout
45 mm (1.772") square
Weight
159 g (0.35 lb)
Table 4.1 Input Properties
TC
J
K
T
E
R
S
B
Input Type
Iron-Constantan
CHROMEGA ® -
ALOMEGA ®
Copper-Constantan
CHROMEGA-
Constantan
Pt/13%Rh-Pt
Pt/10%Rh-Pt
30%Rh-Pt/
6%Rh-Pt
C
N
5%Re-W/
26%Re-W
Nicrosil-Nisil
L
RTD
RTD
PROCESS
J
DIN
Pt, 0.00385, 100 Ω,
500 Ω, 1000 Ω
Pt, 0.00392, 100 Ω,
500 Ω, 1000 Ω
Voltage
PROCESS Current
Range
-210 to 760°C
-346 to 1400°F
-270 to -160°C
-160 to 1372°C
-454 to -256°F
-256 to 2502°F
-270 to -190°C
-190 to 400°C
-454 to -310°F
-310 to 752°F
-270 to -220°C
-220 to 1000°C
-454 to -364°F
-364 to 1832°F
-50 to 40°C
40 to 1788°C
-58 to 104°F
104 to 3250°F
-50 to 100°C
100 to 1768°C
-58 to 212°F
212 to 3214°F
200 to 640°C
640 to 1820°C
212 to 1184°F
1184 to 3308°F
0 to 2354°C
32 to 4253°F
-250 to -100°C
-100 to 1300°C
-418 to -148°F
-148 to 2372°F
-200 to 900°C
-328 to 1652°F
200 to 900°C
-328 to 1652°F
-200 to 850°C
-328 to 1562°F
0 to 100 mV, 0 to 1 V,
0.7°F
0.4°C
0.7°F
0.4°C
0.7°F
0.4°C
0.7°F
0.03% rdg
0 to 10 Vdc 0.03% rdg
0 to 20 mA, 4 to 20 mA 0.03% rdg
Accuracy
0.4°C
0.7°F
1.0°C
0.4°C
1.8°F
0.7°F
1.0°C
0.4°C
1.8°F
0.7°F
1.0°C
0.4°C
1.8°F
0.7°F
1.0°C
0.5°C
1.8°F
0.9°F
0.4°C
0.7°F
1.0°C
0.4°C
1.8°F
0.5°C
1.8°F
0.9°F
1.0°C
0.5°C
1.8°F
0.9°F
1.0°C
48
PART 5
FACTORY PRESET VALUES
Table 5.1 Factory preset value
MENU ITEMS
Set Point 2 (SP2)
Input:
Input Type (INPT)
Reading Configuration (RDG):
Decimal Point (DEC.P)
Temperature unit (TEMP)
Filter value (FLTR)
ANALOG OUTPUT (Retransmission):
Current/Voltage (CURR/VOLT)
Scale and Offset
Alarm:
Alarm 2 (ALR2)
Absolute/Deviation (ABSO/DEV)
Latch/Unlatch (LTCH/UNLT)
Active (ACTV)
FACTORY PRESET VALUES
000.0
TC, type K
FFF.F
°F
0004
Voltage (VOLT)
Reading: 0 - 999.9 cts, Output: 0 - 10 V
Alarm Low (ALR.L)
Alarm High (ALR.H)
Reading Adjust Value (R.ADJ):
Field Calibration (CAL°)
ID:
ID Value
Full ID (FULL)
Set Point ID (ID.SP)
Communication Parameters:
Baud Rate (BAUD)
Parity (PRTY)
Data bit (DATA)
Stop Bit
Modbus Protocol (M.BUS)
Line Feed (LF)
Echo (ECHO)
Enable (ENBL)
Absolute (ABSO)
Unlatch (UNLT)
Above (ABOV)
-100.0
400.0
000.0
0000
0000
Disable (DSBL)
Disable (DSBL)
9600
Odd
7 bit
1 bit
No
No
Yes
Standard Interface (STND)
Command Mode (MODE)
Separation (SEPR)
Alarm Status (STAT)
Reading (RDNG) Yes
Peak No
Valley (VALY)
Units (UNIT)
No
No
Multipoint Address (ADDR)
Transmit Time (TR.TM)
Display Color (COLR):
Normal Color (N.CLR)
Alarm 2 Color (2.CLR)
RS232 (232C)
Command (CMD)
Space (SPCE)
No
0001
0016
Green (GRN)
Amber (AMBR)
49
NOTES
PART 6
CE APPROVALS INFORMATION
This product conforms to the EMC directive 89/336/EEC amended by
93/68/EEC, and with the European Low Voltage Directive 72/23/EEC.
Electrical Safety EN61010-1:2001
Safety requirements for electrical equipment for measurement, control and laboratory.
Double Insulation
Pollution Degree 2
Dielectric withstand Test per 1 min
• Power to Input/Output:
• Power to Input/Output:
(Low Voltage dc Power Option*)
2300Vac (3250Vdc)
1500Vac (2120Vdc)
• Power to Relays/SSR Output:
• Ethernet to Inputs:
• Isolated RS232 to Inputs:
• Isolated Analog to Inputs:
2300Vac (3250Vdc)
1500Vac (2120Vdc)
500Vac (720Vdc)
500Vac (720Vdc)
No Isolation • Analog/Pulse to Inputs:
Measurement Category I
Category I are measurements performed on circuits not directly connected to the
Mains Supply (power). Maximum Line-to-Neutral working voltage is 50Vac/dc.
This unit should not be used in Measurement Categories II, III, IV.
Transients Overvoltage Surge (1.2 / 50uS pulse)
• Input Power: 2500V
• Input Power:
(Low Voltage dc Power Option*)
• Ethernet:
1500V
1500V
• Input/Output Signals: 500V
Note: *Units configured for external low power dc voltage, 20-36Vdc
EMC EN61326:1997 + and A1:1998 + A2:2001
Immunity and Emissions requirements for electrical equipment for measurement, control and laboratory.
• EMC Emissions Table 4, Class B of EN61326
• EMC Immunity** Table 1 of EN61326
Note: **I/O signal and control lines require shielded cables and these cables must be located on conductive cable trays or in conduits.
Furthermore, the length of these cables should not exceed 30 meters
Refer to the EMC and Safety installation considerations (Guidelines) of this manual for additional information.
50
NOTES
NOTES
NOTES
NOTES
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of one (1) year from the date of purchase. In addition to OMEGA’s standard warranty period, OMEGA Engineering will extend the warranty period for four (4) additional years if the warranty card enclosed with each instrument is returned to OMEGA.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an
Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s control. Components which wear are not warranted, including but not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by it will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND
WHATSOEVER, EXPRESS OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY
WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED.
LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.
RETURN REQUESTS/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING
ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM
OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit.
FOR WARRANTY RETURNS, please have the following information available BEFORE contacting OMEGA:
1. Purchase Order number under which the product was
PURCHASED,
2. Model and serial number of the product under warranty, and
3. Repair instructions and/or specific problems relative to the product.
FOR NON-WARRANTY REPAIRS, consult OMEGA for current repair charges. Have the following information available
BEFORE contacting OMEGA:
1. Purchase Order number to cover the COST of the repair,
2. Model and serial number of product, and
3. Repair instructions and/or specific problems relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the latest in technology and engineering.
© Copyright 2013 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior written consent of OMEGA ENGINEERING, INC.
TRADEMARK NOTICE:
®
, omega.com
® ,
®
, and ™ are Trademarks of OMEGA ENGINEERING, INC.
PATENT NOTICE: This product is covered by one or more of the following patents: U.S. Pat. No. Des. 336,895; 5,274,577;
6,243,021 / CANADA 2052599; 2052600 / ITALY 1249456; 1250938 / FRANCE BREVET No. 91 12756 / SPAIN 2039150;
2048066 / UK PATENT No. GB2 249 837; GB2 248 954 / GERMANY DE 41 34398 C2. The “Meter Bezel Design” is a Trademark of NEWPORT Electronics, Inc. Used under License. Other US and International Patents pending or applied for.
Where Do I Find Everything I Need for
Process Measurement and Control?
OMEGA…Of Course!
Shop on line at omega.com
TEMPERATURE
R Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies
R Wire: Thermocouple, RTD & Thermistor
R Calibrators & Ice Point References
R Recorders, Controllers & Process Monitors
R Infrared Pyrometers
PRESSURE, STRAIN AND FORCE
R Transducers & Strain Gauges
R Load Cells & Pressure Gauges
R Displacement Transducers
R Instrumentation & Accessories
FLOW/LEVEL
R Rotameters, Gas Mass Flowmeters & Flow Computers
R Air Velocity Indicators
R Turbine/Paddlewheel Systems
R Totalizers & Batch Controllers
pH/CONDUCTIVITY
R pH Electrodes, Testers & Accessories
R Benchtop/Laboratory Meters
R Controllers, Calibrators, Simulators & Pumps
R Industrial pH & Conductivity Equipment
DATA ACQUISITION
R Data Acquisition & Engineering Software
R Communications-Based Acquisition Systems
R Plug-in Cards for Apple, IBM & Compatibles
R Datalogging Systems
R Recorders, Printers & Plotters
HEATERS
R Heating Cable
R Cartridge & Strip Heaters
R Immersion & Band Heaters
R Flexible Heaters
R Laboratory Heaters
ENVIRONMENTAL
MONITORING AND CONTROL
R Metering & Control Instrumentation
R Refractometers
R Pumps & Tubing
R Air, Soil & Water Monitors
R Industrial Water & Wastewater Treatment
R pH, Conductivity & Dissolved Oxygen Instruments
M3610/0213
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project