PORTABLE FIRE EQUIPMENT | FIRE PROTECTION SYSTEMS | FIRE SYSTEM INSTALLATIONS | FIRE SYSTEM SERVICING | COMPLIANCE | FIRE SAFETY TRAINING | MAJOR PROJECTS VIGILANT F3200

VIGILANT F3200

Fire Indicator Panel

Features

Certified to AS 4428.1

LCD and optional zone LEDs

Compatible with a wide range of detectors

Expands up to 64 zones

Versatile input monitoring

Easy to operate

Fully field programmable

Networking option

Low profile remote LCD repeater/mimic

AS ISO 14520.1:2009 Gaseous Fire-Extinguishing

System options

Economical, Flexible and Reliable

The VIGILANT F3200 is an advanced Fire Indicator Panel (FIP) that uses modular internal construction to achieve economical and reliable monitoring and control for up to 64 fire detection zones. In its minimum configuration, F3200 contains all of the facilities required for a comprehensive 8 zone fire alarm and control system. The ease with which it can be expanded, its flexible input monitoring, its networking capability and its extensive field programming facilities make it suitable for a wide range of fire protection applications.

The VIGILANT F3200 is specifically designed to provide reliable operation. It employs modern electronic technology put together with specialist fire detection equipment design expertise. Detector circuits, power supply, warning system, external bells and ancillary outputs are supervised as required by fire alarm standards. In addition, the F3200 employs automatic test techniques to verify that it is functioning correctly. Fuses on all battery-backed power supply outputs are supervised for continuity. A supervisory “Watchdog” monitors system processor operation.

EMAIL COPY ONLY

VIGILANT F3200

ELR

Up to 64

Conventional

Detector Circuits

(8 per Zone Module)

Emergency Warning and Intercommunication

System (EWIS)

Repeater Panels

(up to 8)

Building

Management and/or

AS1668 Control

Systems with

Vigilant IO-NET

Individual Zone

Alarms

F3200 Fire Indicator Panel

Up to 528 Zone

Indications

Logging Printer

Programmable

Open Collector

Outputs (8 per

Zone Module)

Optional

Programmable

Supervised Relay

Outputs (8 per

Relay Module)

Supervised Ancillary

Relay Output

Warning System

External Bell/Strobe

Monitoring Service

Network Connection to other systems

Colour Graphics

Display(s)

Modem Modem

Remote Operation

F3200 System Design

Easily Expanded

A minimum F3200 has one 8-Zone Module fitted, allowing it to monitor up to 8 alarm zone circuits. Further Zone Modules can be added to expand it to 64 zone circuits. External mimic displays are easily implemented using the programmable open collector outputs on each Zone Module.

Standard monitoring service signalling relay outputs are available, and further relay outputs may be added by installing Relay Modules. Each Relay Module provides eight programmable relay outputs with individually selectable supervision. A combined total of eight Zone and Relay Modules is allowable in a system.

Remote repeater LCD displays or mimics, colour graphic displays and a logging printer may also be added. Interfaces to EWIS and BMS are also available, and an optional networking facility adds further flexibility, particularly for larger wide-area systems.

Features and Options

• Compact and attractive cabinet range - 19” rack compatible

• Clear alarm messages on LCD alphanumeric display

• Control panel with “Firefighter Facility” complies with AS 4428.1

• Optional zone LED display

• Outputs for local mimic panel

• Remote repeater panels and mimic panels may have LCD and/or LEDs

• Multiple panel networking option

• Colour Graphics display option

• “Tandem” mode provides dial-in control panel access for remote operation and diagnostics

• Low power consumption

• Integral power supply/battery charger

(3A or 6A)

• Easy to install and service

• Demountable terminals for efficient servicing and accurate cable identification

• Comprehensive test facilities

• Automatic panel self tests

• Automatic battery connection and capacity tests

• Automatic daylight saving time adjustment

• Field programmable

• Supervised front panel MCP

• Wide range of compatible detectors including

IS types

• AS 1668 air-handling, smoke detection and control

• Valve tamper monitoring (type A security)

• Wide Fire Brigade system compatibility

• Supervised outputs for ancillary services, door holders, etc

• Interface for EWIS, BMS, etc

• Built in clock/calendar

• Event logging to internal history file and optional printer

• Two fuse-protected battery backed supply outputs (fuses supervised)

EMAIL COPY ONLY

VIGILANT F3200

Easy to Operate

Operation is straightforward with the F3200’s keypad and alphanumeric LCD. The 40 character, 2 line LCD zone control panel meets the AS 4428.1 “Firefighter Facility” (FF) requirements. Next and Prev keys allow easy scrolling through the 99 event alarm buffer, while all current alarms, faults and isolated zones can be separately recalled.

An internal history log stores the previous 400 events (800 with printer buffer disabled), and these can be recalled to the LCD display at any time. “Tandem” mode enables the panel to be operated from a remote computer for diagnostic or remote monitoring purposes.

The optional easy-to-read English language printer output with system name heading each page, 30 character zone name, and date/time stamp, allows rapid tracing of events.

Fully Field-Programmable

Configuration for a basic fire alarm system is automatic with minimal programming necessary. Systems utilising a variety of input device types and more sophisticated control and timing functions, may be programmed either via the F3200’s front panel or through an external personal computer. Timers, Boolean logic expressions and variables provide powerful programmability allowing a wide range of monitoring and control functions to be configured.

The configuration can be printed and also uploaded to disk for later downloading.

Site-specific configuration parameters are stored in non-volatile flash memory, which remains protected even if the system’s power supply is removed. Programmed information is access code protected, with ten programmable codes available to allow access by different users to be individually logged.

Control Panel Layout

Network Option

A Panel-Link Network upgrade enables the F3200 to network with other compatible fire alarm systems.

• A local F3200 panel may display and control alarms from remote systems

• A “master” networked panel may perform fire brigade signalling for selected “slave” panels using networked master alarm status

• LED indication can be expanded to display up to 528 zones (additional cabinets required) from across the network

• Remote Warning Systems may be activated and/or isolated

• Network Variables enable network-wide output logic

• Operation possible over a variety of media: 2-wire or 4-wire RS485, modem and fibre optic options

• Network-compatible product family includes: F3200 panels, mimic panels (NLDU),

Network Display panels (NDU), computer colour graphics, Panel-Link Modbus Bridge

(PMB), QE90 EWIS panel, event printers and I-Hubs for network expansion

• ”Tandem” mode allows operator access to all panels on the network

• Remote access options allow diagnostics and operation of the system from off-site

Detector Compatibility

The F3200 is compatible with hard contact devices and a wide range of “20 volt” industrystandard detectors including the Minerva and Tyco 614 ranges and Simplex 4098 range.

It is also compatible with many Cerberus, Apollo, Hochiki, Flameguard and Nittan detectors and can be used with 3-wire or 4-wire infrared/UV flame and Optical Beam detectors. A full list of currently approved detectors is available on request.

EMAIL COPY ONLY

VIGILANT F3200

Specifications

System Capacity

FIP Capacity: Up to 8 modules, each module being either an 8-Zone Input

Module or an 8-Relay Output Module

Firefighter Facility: 2 Line 40 Character LCD display provides 30 character text

message for each alarm. Complies with AS 4428.1

Zone Indications: Optional, up to 64 Alarm, Fault, Isolate LEDs in 15U cabinet, up to 528 zones

maximum with additional cabinets

Programmable Outputs: 8 on each Zone Module, transistor pulldown (1.1V)

8 on each Relay Module. Monitoring Service Relays, Warning

System, Ext.Bell/Strobe and Ancillary relays are also programmable

Repeater Panels: Up to 8. More if mimic only (i.e. no controls)

Fire Indicator Panel

Physical

Cabinet Size (mm): 750H x 550W x 230D (small cabinet option 440H)

Cabinet Material: 1.2 mm mild steel. Baked epoxy powdercoat finish:

Cream Wrinkle BFF998CW. Polycarbonate membrane keyboard facia

Style: Wall mounting. Outer door hinges left (003 key lock) to access

controls. Inner door hinges right. Ingress Protection IP30

Shipping Weight: 22 kg (without batteries)

Temperature: -5°C to 45°C operating

Humidity: Up to 95% RH (non-condensing)

Power Supply

Mains Supply: 240Vac +6% -10%, 50 Hz, 150VA

Internal Battery: 2 x 12V, sealed lead-acid, capacity up to 40Ah

Internal Charger: 27.3V (nominal), 3A (6A option), regulated, temperature compensated

Battery Monitoring: Charger high/low, battery low/fail, timed capacity tests

Inputs

Alarm Zone Circuits: 20V nominal, conventional detector circuits. Four modes:

Standard, High Current, Low Current, Tamper

FIP MCP: Supervised with programmable zone mapping

AZC Input Terminations: De-mountable screw terminals, 1.5 sq mm cable capacity

Outputs

Monitoring Service Relays: Alarm, Fault, Standby, Isolated; 5A, 30Vdc resistive

Ancillary & Ext. Bell/Strobe: 2A, 30Vdc resistive. Supervised switched 24V or voltage free

Warning System: 2A, 30Vdc resistive. Supervised (polarity reversal) switched 24V;

battery backed

Zone Module Outputs: 8 programmable 100mA transistor pull-down (1.1V)

Relay Module Relays: Single pole 2A, 30Vdc (2 pole option available). Link selectable supervision

RZDU Comms: Communications port for connection to repeater panels

Printer: Pseudo RS232, Xon/Xoff, Selectable 300 to 9600 baud,

8 data bits, no parity, 1 stop bit

Ancillary Supplies: 2 x 24V, battery-backed, 2A load

1 x 28V, 2A; non battery-backed, fused

Remote LCD Module

Cabinet Size (mm): Wall Mounting: 177H x 450W x 50D (75D option)

Flush Mounting: 220H x 500W x 75D

Cabinet Material: 1.2 mm mild steel. Baked epoxy powdercoat finish:

Grey Gloss PR12/816C. Polycarbonate membrane keyboard facia

Style: Low profile wall mounting or flush mounting options; door hinges

left (003 key lock)

Shipping Weight: 3 kg

Power Supply: 24Vdc, supplied from FIP

Programming Options

The following functions can be programmed:

• Zone/Ancil/Circuit facilities:

- Zone enable/disable

- Zone Identification Text

- Alarm Type Text including MCP override

- Zone to LED mapping

- Normal zone operation

- Flow Switch (variable delays)

- Air Conditioning (variable time delays)

- Sprinkler Valve Tamper

- Alarm Verification

- Ancillary Control

- Latching/Non-latching

- Monitoring Service/Indication only/Status

(no indication)

- Output Supervision enable/disable

- Output Supervision Fault latching/nonlatching

- Mapping to Monitoring Service, Ancillary,

Ext. Bells/Strobe,

Warning System outputs

• Output Logic Programming:

- Variables and Timers

- Boolean AND, OR, XOR, NOT

- Daylight Saving

• System commands:

- Time/date

- Diagnostics

- Database Upload/Download

- Text download to LCD Repeater Panels

- Adjust global settings:

Access code, System name, FF mode,

Printer Setup, Automatic test times/dates

• Repeater Panel Programming

- Zones displayed on LCD/LED

- Zone to LED mapping

- Global or local key functions

- Internal/external power supply

- Local Monitoring Service Relay operation

Approved

F3200 is certified to AS 4428.1 - 1998:

“Fire detection, warning, control and intercom systems - Control and indicating equipment, Part 1: Fire”.

CSIRO ActivFire Listed afp-789 (Tyco)

Copyright © 2012 Tyco Australia Pty Limited. All rights reserved. Tyco reserves the right to make changes to any aspect of this publication at any time without notice.

VIGILANT is a trademark of Tyco New Zealand Limited or its affiliates. F3200broW1204

Australia Phone 133 166 | Email [email protected] | Web Site www.wormald.com.au

EMAIL COPY ONLY

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement