EPH Controls CRT2 Operation guide
Below you will find brief information for CRT2. This battery-operated room thermostat offers Normal, Delay Start, and TPI operating modes, adjustable hysteresis (0-1°C), temperature calibration, and keypad lock. It controls heating via a volt-free SPDT output, with a temperature range of 5-35°C and battery life for easy installation.
Advertisement
Advertisement
CRT2 Room Thermostat Installation and Operation Guide Table of contents Installation Instructions Factory Default Settings Specifications LCD Display Buttons Wiring Mounting & installation Replacing the batteries 2 3 4 5 6 7 10 Operating Instructions On / Off Function & Adjusting the Target Temperature Locking the Keypad / Backlight Menu HYS Hysteresis HOn and HOFF Calibrate Setting High and Low limits Operating Mode Normal Mode (Nor) Delay Start Control (On/Off ) Time Proportional Integral Mode (TPI) Resetting the Thermostat 12 13 14 16 17 18 19 20 22 25 Battery operated non-programmable Room Thermostat Installation Instructions Factory Default Settings High and Low Temp. limitation: Keypad lock: Operating mode: Temperature indicator: HYS On: HYS OFF: 2 CRT2 Off Off Normal ˚C 0.4˚C 0.0˚C Specifications Contacts: Power supply / Input: Power consumption: Volt Free 2 x AA Alkaline Batteries Operating 30mW Standby <0.5mW Temperature range: 5 … 35˚C Ambient temperature: 0 … 45˚C Ambient admissible humidity: 5-95%RH Contact rating: 8(3)A, 230Vac Switch output: SPDT Volt Free Dimensions: 91 x 91 x 26mm Internal temperature sensor: NTC 100K Backlight: White IP rating: IP20 Pollution degree: 2 Hysteresis (Switching differential): Adjustable from 0 to 1°C Automatic action: 0.1°C increments 1C EPH Controls Ltd. 3 LCD Display [1] [2] [3] [4] [5] [6] [7] [8] [9] [10] [11] [12] Displays when setting target temperature. Displays current room temperature. Displays current / target temperature. Displays when changing mode setting. Displays when setting in TPI mode. Displays when the batteries need to be replaced. Displays when the thermostat is calling for heat. Displays when keypad is locked. Displays when thermostat is in the OFF mode. Displays when setting HIGH and LOW temperature limit. Displays during [2] [5] [6] [3] [4] calibration mode. Displays when [1] set room temp mode cyc p band setting hysteresis. [7] HYS calibrate high low limit off [12] 4 CRT2 [11] [10] [9] [8] Buttons Reset Button OK Button Standby Button Down Button Up Button EPH Controls Ltd. 5 Wiring 3 2 1 ON COM OFF Terminal Connections 6 Terminal 1 OFF - N/C Normally closed connection Terminal 2 COM - Common connection Terminal 3 ON - N/O Normally open connection CRT2 Mounting & Installation Caution! Installation and connection should only be carried out by a qualified person. Only qualified electricians or authorised service staff are permitted to open the thermostat. If the thermostat is used in a way not specified by the manufacturer, its safety may be impaired. Prior to setting the thermostat, it is necessary to complete all required settings described in this section. Before commencing installation, the thermostat must be first disconnected from the mains. This thermostat can be mounted in the following ways: 1) Directly mounted on wall 2) To a recessed conduit box 3) To a surface mounting box EPH Controls Ltd. 7 Mounting & Installation Continued 8 1) Remove the thermostat from its packaging. 2) Choose a mounting location so that the thermostat can measure the room temperature as accurately as possible. - Mount the thermostat 1.5 metres above the floor level. - Prevent direct exposure to sunlight or other heating / cooling sources. 3) Use a philips screwdriver to loosen the screw on the bottom of the thermostat to open the front housing. 4) Wire the thermostat according to the wiring diagram on page 6. 5) Screw the backplate onto a back box or directly to the surface. 6) Close the front housing and tighten the screw on the bottom of the thermostat. CRT2 90 90 26 45 113 9 Replacing the batteries 1) 10 is displayed when the batteries need to be replaced. 2) Push in the battery compartment to release it. 3) Replace the batteries with 2 x AA Alkaline batteries. 4) Re-insert the battery compartment. Push it until it clicks into place. CRT2 Battery operated non-programmable Room Thermostat Operating Instructions On / Off Function Press to turn the thermostat On or Off. When in the ON mode the thermostat will display the current room temperature. When in the OFF mode the thermostat will display the current room temperature and the word ‘OFF’. Adjusting the Target Temperature 12 Press to increase the target temperature from 5-35˚C. Press or wait 5 seconds. The target temperature is now saved. Press to decrease the target temperature from 5-35˚C. Press or wait 5 seconds. The target temperature is now saved. CRT2 Locking the Keypad To lock the thermostat, press and hold and for 10 seconds. will appear on the screen. The buttons are now disabled. To unlock the thermostat, press and hold and for 10 seconds. will disappear from the screen. The buttons are now enabled. Backlight AUTO There are two settings for selection. ‘AUt’ The backlight is on for 5 seconds when any button is pressed. ‘OFF’ The backlight is permanently off. To adjust the backlight setting, press and hold for 10 seconds. ‘AUt’ appears on the screen. Use Press and to change the mode between AUTO and OFF. to confirm selection and to return to normal operation. EPH Controls Ltd. 13 Menu This menu allows the user to adjust additional functions. To access the menu, press and hold and together for 5 seconds. HYS – Hysteresis HOn and HOf HOn 0.4°C HOff 0°C This menu allows the installer to change the switching differential of the thermostat when the temperature is rising and falling. If ‘HYS ON’ is set at 0.4˚C and the setpoint is 20˚C, then the thermostat will switch on when the temperature drops below 19.6˚C. If ‘HYS OFF’ is set at 0.2˚C and the setpoint is 20˚C, then the thermostat will switch off when the temperature reaches 20.2˚C. To access this setting press and hold and together for 5 seconds. ‘HYS’ will appear on the screen. Press to select. ‘HOn’ will appear on the screen. 14 Press and temperature will begin to flash. Use and to select the ‘HOn’ temperature, press CRT2 to confirm. ‘HOF’ appears on the screen. Press and the temperature will begin to flash. Use and Press to return to normal operation. to select the ‘HOF’ temperature, press EPH Controls Ltd. to confirm. 15 Calibrate This menu allows the installer to calibrate the temperature of the thermostat. To access this setting press and hold and seconds. ‘HYS’ will appear on the screen. Press until ‘CALIBRATE’ flashes on the screen. Press to select. The actual temperature will flash on the screen. 16 Press and Press to confirm the temperature. Press to return to normal operation. to calibrate the temperature. CRT2 together for 5 Setting High and Low limits Hi 35°C Lo 5°C This menu allows the installer to change the minimum and maximum temperatures that the thermostat can be set at. To access this setting press and hold seconds. and together for 5 ‘HYS’ will appear on the screen. Press until ‘LIMIT’ flashes on the screen. Press to select. ‘HIGH LIMIT’ will appear on the screen, the temperature will begin to flash. Use and Press to confirm. to select the high limit for the thermostat. ‘LOW LIMIT’ will appear on the screen, the temperature will begin to flash. Use and Press to confirm. Press to return to normal operation. to select the low limit for the thermostat. ‘LIMIT’ will appear on the screen. EPH Controls Ltd. 17 Operating Mode (Normal / Delay Start / TPI) There are three settings for selection, Normal, Delay Start or TPI mode. The default setting is Normal. Press and hold and together for 5 seconds. ‘HYS’ will appear on the screen. Press until ‘MODE’ appears on the screen. Press to select. Use and to select between: nOr (Normal mode) dS (delay start mode) tPi (Time proportional integral mode) Press 18 to confirm the mode. CRT2 Nor (Normal Mode) When the temperature falls below the target temperature, will appear and the thermostat will activate the demand for heat. When the temperature rises above the target temperature, will disappear, and the thermostat will cancel the demand for heat. Graph (19.1): On / Off Control Temp 22˚C Target Temperature 21˚C 20˚C 19˚C 18˚C 17˚C 0 20 40 60 80 EPH Controls Ltd. 100 Time Minutes 19 Operating Mode (Normal / Delay Start / TPI) continued Delay Start Control (On/Off) When in this mode the thermostat is delayed by a variable time depending on the current temperature, target temperature and also the fall in temperature from when the delay start has activated. The will flash until the thermostat activates. When activated the thermostat will allow the heating system time to reach the target and delay start will remain inactive until it reaches this target. Time delay after Delay Start activated in minutes Graph (20.1): Delay Start Control 20 48 E.g: If the temperature is 6˚C below the thermostat target, the thermostat will call for heat immediately. 42 36 30 24 18 12 6 0 0 4 2 5 1 3 6 Temperature below thermostat setting °C CRT2 If the temperature is 2˚C below the target, the thermostat will not call for heat for 32 minutes. Delay Start Control (On/Off) Continued Delay start can be reactivated by: 1. Press to lower the target below the current temperature. 2. Press to confirm. 3. Press to increase the target temperature above the zone temperature within 6°C . 4. Press to confirm. The heating will be delayed as per the graph on page 20. If the difference between the actual temperature and the target is 1°C the thermostat will delay starting for circa 40 minutes. If the difference between the actual temperature and the target is 3°C the thermostat will delay starting for circa 24 minutes. If the difference is 6°C or more then the thermostat will be switched on immediately. The time delay will change if the temperature drops from the original calculation. EPH Controls Ltd. 21 Operating Mode (Normal / Delay Start / TPI) continued Time Proportional Integral Mode (TPI) When the thermostat is in TPI mode and the temperature is rising in the zone and falls into the Proportional Bandwidth section, TPI will start to affect the thermostats operation. The thermostat will turn on and off as it gains heat so that it doesn’t overshoot the target by too much. It will also turn on if the temperature is falling so it doesn’t undershoot the target which will leave the user with a more comfortable level of heat. There are 2 settings that will affect the thermostats operation 1. The number of heating cycles per hour 2. The Proportional Bandwidth CyC – Number of Heating Cycles per hour 6 Cycles This value will decide how often the thermostat will cycle the heating on and off when trying to achieve the target temperature. You can select 2/3/6 or 12. 22 CRT2 Time Proportional Integral Mode (TPI) Continued Pb -Proportional Bandwidth 2°C This value refers to the temperature below the target at which the thermostat will start to operate in TPI control. You can set this temperature from 1.5°C to 3.0°C in 0.1°C increments. Graph (23.1): TPI Control Temp 22˚C 21˚C Target Temperature 20˚C Proportional Bandwidth 19˚C 18˚C 17˚C 0 Heating On 20 40 60 80 100 Time Minutes Heating Off EPH Controls Ltd. 23 Operating Mode (Normal / Delay Start / TPI) continued Time Proportional Integral Mode (TPI) Continued Once TPI mode is selected, ‘CYC’ and ‘06’ will appear on the screen. Use and Press to confirm. to select from 2,3,6 or 12. ‘P Band’ and ‘2.0’ will appear on the screen. 24 Use and Press to confirm. Press to return to normal operation. to select from 1.5 to 3.0. CRT2 Resetting the Thermostat To reset the thermostat to factory settings, locate the button on the left hand side of the thermostat. Press the reset reset button and release it. ‘nO’ will flash on the screen. Press . ‘YES’ will flash on the screen. Press to confirm. The thermostat will restart and revert to its factory settings. EPH Controls Ltd. 25 EPH Controls IE [email protected] www.ephcontrols.com/contact-us +353 21 471 8440 Cork, T12 F753 EPH Controls UK 2026-01-29_CRT2_DS_PK © 2026 EPH Controls Ltd. [email protected] www.ephcontrols.co.uk/contact-us +44 1933 322 072 Harrow, HA1 1BD ">
Download
Advertisement
Key features
Battery operated
Non-programmable
LCD display
Temperature control
Normal, Delay Start, TPI mode
Keypad lock
Frequently asked questions
When the batteries need to be replaced, the icon will appear on the display. Push in the battery compartment to release it, replace the batteries with 2 x AA Alkaline batteries, and re-insert the compartment until it clicks into place.
The CRT2 thermostat has a temperature range of 5°C to 35°C.
Press the button to increase the target temperature and the button to decrease it. The target temperature will be saved after 5 seconds or by pressing the button.
To lock the keypad, press and hold the and buttons for 10 seconds. The icon will appear on the screen. To unlock the keypad, press and hold the same buttons for 10 seconds.