Condair CP3 Owner Manual
Annons
Annons
Condair CP3
Electrode Humidifiers
INSTALLATION AND OPERATING INSTRUCTIONS
Contents
1.2 Notes on the installation and operating instructions
3.2 Identification of the unit
3.3 Steam humidifier construction
3.5 Humidification system overview
3.6 Overview unit interconnection
3.10 Storing/Transportation/Packaging
4 Notes for the planning engineer
4.1 Selecting the unit version
4.1.1 Calculating the maximum required steam capacity 19
4.2 Selecting the options an accessories
4.3 Selecting the control system 21
5 Mounting and installation work 24
5.1 Important notes for mounting and installation work 24
5.2.1 Notes on locating the unit
5.2.3 Inspecting the installed unit
5.3.1 Overview steam installation
5.3.2 Positioning and mounting of the steam distribution pipes
5.3.3 Installing the steam distributors
5.3.4 Positioning and mounting of the fan unit
5.3.5 Installing the steam hose
5.3.6 Installing the condensate hose
5.3.7 Inspecting the steam installation
5.4.1 Overview water installation
5.4.2 Notes on water installation
5.4.3 Inspecting the water installation
5.5.1 Wiring diagram Condair CP3 Basic/Pro
5.5.2 Wiring diagram CP3 Pro Link Up systems
5.5.3 Wiring diagram Option CVI and Option Trafo
5.5.4 Fuses F5 for heating voltage supply
5.5.6 Notes on electric installation
5.5.7 Inspecting the electrical installation
6.1 Function of the display and operating elements
6.3.1 Remote operating and fault indication
6.3.2 Notes on the operation at ambient temperatures ≤ 0°C
6.3.3 Inspections during operation
6.3.4 Carrying out manual draining
6.4 Taking the unit out of operation
6.5 Overview and operating of the menu
6.6.1 Interrogation of the operating information in the indication level
6.6.2 Interrogation of unit information
6.6.3 Interrogation of the malfunction list
6.7.1 Launching the unit settings menu
6.7.2 Selecting the dialogue language
6.7.5 Setting the capacity limitation
6.7.6 Configuring the On/Off timer 55
6.7.7 Activating/Deactivating fault current relay operation 56
6.7.8 Setting the operation mode for multiple units
6.7.9 Water management settings
6.7.10 Performing remote relay tests
6.7.13 Setting the display contrast
7.1 Important notes on maintenance
7.3 Removing and installing parts for maintenance
7.3.1 Removal and installation of the steam cylinder
7.3.2 Disassembly and assembly of the cleanable steam cylinder type D...
7.3.3 Removal and installation of the water cup and the water hoses
7.3.4 Removal and installation of the drain pump
7.3.5 Removal and installation of the inlet valve
7.4 Notes on cleaning the unit components
7.6 Resetting the maintenance indication
8.2 Resetting the error indication (red LED lights)
8.3 Notes on fault elimination
8.4 Replacing the backup battery on the control board of the Condair CP3 Pro
9 Taking out of service/Disposal
3
4
1 Introduction
1.1 To the very beginning
We thank you for having purchased the steam humidifier Condair CP3.
The steam humidifier Condair CP3 incorporates the latest technical ad van ces and meets all recognized safety standards. Nevertheless, improper use of the Condair CP3 may result in danger to the user or third parties and/or impairment of material assets.
To ensure a safe, proper, and economical operation of the steam humidifier Condair CP3, please observe and comply with all information and safety instructions contained in the present installation and operating instructions as well as the instructions given in the manuals for the components used in the humidification system.
If you have questions, which are not or insufficiently answered in this documentation, please contact your Condair supplier. They will be glad to assist you.
1.2 Notes on the installation and operating instructions
Limitation
The subject of these installation and operating instructions are the steam humidifier Condair
CP3 in its versions “Basic” and “Pro”. The various accessories (e.g. steam distributor, steam distribution system, etc.) are only described insofar as this is necessary for proper operation of the equipment. Further information on accessories can be obtained in the respective instructions.
These installation and operating instructions are restricted to the
installation, commissioning,
operation, servicing and trouble shooting of the steam humidifier Condair CP3 and is meant for
well trained personnel being sufficiently qualified for their respective work.
These installation and operating instructions are supplemented by various separate items of documentation (spare parts list, manuals for accessories, etc.). Where necessary, appropriate cross-references are made to these publications in these installation and operating instructions.
Symbols used in this manual
CAUTION!
The catchword “CAUTION” designates notes in this documentation that, if neglected, may cause
damage and/or malfunction of the unit or other material assets.
WARNING!
The catchword “WARNING” used in conjunction with the general caution symbol designates safety and danger notes in this documentation that, if neglected, may cause to injury to persons.
DANGER!
The catchword “DANGER” used in conjunction with the general caution symbol designates safety and danger notes in this documentation that, if neglected, may lead to
severe injury or even
death of persons.
Safekeeping
Please safeguard these installation and operating instructions in a safe place, where it can be immediately accessed. If the equipment changes hands, the documentation should be passed on to the new operator.
If the documentation gets mislaid, please contact your Condair supplier.
Language versions
The present installation and operating instructions are available in various languages. Please contact your Condair supplier for information.
Copyright protection
The present installation and operating instructions are protected under the Copyright Act. Passing-on and reproduction of the manual (or part thereof) as well as exploitation and communication of the contents are prohibited without written permission by the manufacturer. Violation of copyright terms is subject to legal prosecution and arises liability for indemnification.
The manufacturer reserves the right to fully exploit commercial patent rights.
5
6
2 For your safety
General
Every person working with the Condair CP3 must have read and understood the present installation and operating instructions before carrying out any work.
Knowing and understanding the contents of the present installation and operating instructions is a basic requirement for protecting the personnel against any kind of danger, to prevent faulty operation, and to operate the unit safely and correctly.
All ideograms, signs and markings applied to the unit must be observed and kept in readable state.
Qualification of personnel
All actions described in the present installation and operating instructions (installation, operation, maintenance, etc.) must be carried out only by
well trained and sufficiently qualified personnel
authorised by the owner.
For safety and warranty reasons any action beyond the scope of this manuals must be carried out only by qualified personnel authorised by the manufacturer.
It is assumed that all persons working with the Condair CP3 are familiar and comply with the appropriate regulations on work safety and the prevention of accidents.
This unit may not be used by persons (including children) with reduced physical, sensory or mental abilities or persons with lacking experience and/or knowledge, unless they are supervised by a person responsible for their safety or they received instructions on how to operate the unit.
Children must be supervised to make sure that they do not play with unit.
Intended use
The steam humidifier Condair CP3 is intended exclusively for
air humidification via a steam distributor or a ventilation unit approved by the manufacturer within the specified operating con-
ditions (see chapter 10 “Product specifications”). Any other type of application without the express written consent of the manufacturer is considered as not conforming with the intended purpose and may lead to the Condair CP3 becoming dangerous.
Operation of the equipment in the intended manner requires
that all the information in these instal-
lation and operating instructions is observed (in particular the safety instructions).
Danger that may arise from the unit
DANGER!
Danger of electrical shock!
The Condair CP3 is mains powered. One may get in touch with live parts when the unit is open. Touching live parts may cause severe injury or danger to life.
Prevention: Before carrying out any work set the Condair CP3 out of operation as described in chapter 6.4 (switch off the unit, disconnect it from the mains and stop the water supply) and secure the unit against inadvertent power-up.
WARNING!
Hot water vapour - Danger of scalding!
The Condair CP3 produces hot water vapour. There is danger of scalding when getting in
touch with hot water vapour.
Prevention: Do not carry out any work on the steam system during operation (steam lines, steam distributor, fan unit, etc.). If the steam system is leaky set the Condair CP3 immediately out of operation as described in chapter 6.4. Correctly seal the steam system before putting the unit into operation again.
WARNING!
Danger of burning!
During operation the components of the steam system get very hot (up to 100 °C). There is danger of burning when touching the hot components.
Prevention: Before carrying out any work on the steam system set the Condair CP3 out of operation as described in chapter 6.4, then wait until the components have cooled down sufficiently thus preventing danger of burning.
Behaviour in case of danger
If it is suspected that safe operation is no longer possible, then the Condair CP3 should immediately
be shut down and secured against accidental power-up according to chapter 6.4. This can be the case under the following circumstances:
– if the Condair CP3 or its mains cable is damaged
– if the Condair CP3 is no longer operating correctly
– if connections and/or piping are not sealed
All persons working with the Condair CP3 must report any alterations to the unit that may affect safety to the owner without delay.
Prohibited modifications to the unit
No modifications must be undertaken on the Condair CP3 without the express written consent of the manufacturer.
For the replacement of defective components use exclusively original accessories and spare parts available from your Condair supplier.
7
8
3 Product Overview
3.1 Models overview
Steam air humidifiers Condair CP3 are available in the versions “ Basic" and “Pro” with different
heating voltages and steam capacities ranging from 5 kg/h up to a max. of 180 kg/h.
Heating voltage * Max. steam capacity in kg/h
400V3
(400V/3~/50...60Hz)
230V3
(230V/3~/50...60Hz)
230V1
(230V/1~/50...60Hz)
50
60
75 **
90 **
100 **
120 **
152 **
160 **
180 **
5...15
16...30
44
5...15
16...45
52
60
70
80
90
105 **
120 **
135 **
5...8
* Other heating voltages on request
** Link Up systems
Graduation in kg/h
90
100
120
50
60
75
152
160
180
5...15
16...30
44
5...15
16...45
52
60
105
120
135
70
80
90
5...8
--
--
--
50
60
--
--
--
--
5...15
16...30
44
5...15
16...45
52
60
--
--
--
70
80
90
5...8
--
--
--
--
--
--
1
1
--
--
--
--
--
--
--
--
--
--
1
1
--
--
1
Model Condair CP3
Basic...
Pro...
Single unit small
1
Unit size / Number of units
Single unit large
Double unit large
1
1
1
1
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
Key model designation
Example:
Condair CP3 Pro 45 400V3
Unit Version:
Pro
Basic
Maximum steam capacity in kg/h:
Heating voltage:
400V/3~/50...60Hz:
400V3
230V/3~/50...60Hz:
230V3
230V/1~/50...60Hz:
230V1
3.2 Identification of the unit
The identification of the unit is found on the type plate (for the location of the type plate see unit overview):
Heating voltage
Maximum steam capacity per unit
Admissible water supply pressure
Field with certification symbols
Type designation Serial number (7 digits) Month/Year
Type: CP3 Pro 45
Condair AG, CH-8808 Pfäffikon
Ser.Nr.: XXXXXXX
Heating Voltage: 400V / 3~ / 50...60Hz Power: 33.8 kW
Steam Capacity: 45.0 kg/h
Water Pressure: 1...10 bar
Ctrl.Voltage: 230V / 1~ / 50...60Hz
Model: Main Unit / Modul A
11.06
Made in Switzerland
Power consumption
Control voltage
Model
9
10
3.3 Steam humidifier construction
12
13
14
15
16
17
18
19
24
23
20
The illustration above shows the large unit
26
25
1 Housing (small, large)
2 Cable openings, top side
3 Main contactor
4 Power board
5 Control board with CP3 Card
6 Display and control unit
7 Remote operating and fault indication board
8 Operation status indicators
9 Cable openings, bottom side
10 Drain key
11 Unit switch
12 Steam outlet
13 Water cup
14 Filling hose
15 Water supply hose
16 Inlet valve
17 Overflow hose
18 Drain connection (not visible)
19 Water supply pipe
20 Drain pump
21 Type plate
22 Data plate CP3 Card
23 Steam cylinder
24 Level sensor
25 Auxiliary drain hose
26 Electrode plug
3
4
5
6
22
21
10
11
7
8
9
1
2
3.4 Functional description
The steam humidifier Condair CP3 is a pressureless steam generator that utilizes an electrode heating. The steam humidifier Condair CP3 is designed for air humidification via a steam distributor
(steam distribution pipe, ventilation unit or steam distribution system OptiSorp).
Steam generation
Any time steam is requested, the electrodes are supplied with voltage via main contactor. Simultaneously, the inlet valve opens and water enters the steam cylinder from the bottom via water cup and supply line. As soon as the electrodes come in contact with the water, current begins to flow between the electrodes, eventually heating and evaporating the water. The more the electrode surface is exposed to water, the higher is the current consumption and thus the steam capacity.
Upon reaching the requested steam capacity, the inlet valve closes. If the steam generation decreases below a certain percentage of the required capacity, due to lowering of the water level (e.g. because of the evaporation process or drainage), the inlet valve opens until the required capacity is available again.
If the required steam capacity is lower than the actual output, the inlet valve is closed until the desired capacity is achieved by lowering of the water level (evaporation process).
Level monitoring
A sensor provided in the steam cylinder cover detects when the water level gets too high. The moment the sensor comes in contact with water, the inlet valve closes.
Drainage
As a result of the evaporation process, the conductivity of the water increases due to an escalating mineral concentration. Eventually, an inadmissibly high current consumption would take place if this concentration process were permitted to continue. To prevent this concentration from reaching a value, unsuitably high for the operation, a certain amount of water is perio dically drained from the cylinder and replaced by fresh water.
Control
The steam production can be controlled steplessly via the internal or an external continuous controller or with an On/Off control via an external humidistat.
11
12
3.5 Humidification system overview
41-..
61-..
81-..
14
KS10
13
1
2
6
Z261
5
3
4
125...1250 µS/cm
1...10 bar
1...40 °C
DS22
DS60
DS80
DS60
DS80
12
15
Basic
FAN3S CP Basic M
FAN3S CP Basic L
Pro
FAN3S CP Pro M FC
FAN3S CP Pro M
FAN3S CP Pro L
11
8
DS80
7
10
9
1 Steam humidifier
2 Steam connection
3 Water drain connection
4 Water supply connection
5 Filter valve (accessory “Z261”)
6 Manometer (installation recommended)
7 Funnel with siphon (building side)
8 Water drain hose (accessory “DS80”
9 Control voltage supply
10 Heating voltage supply
11 Cable openings
12 Steam hose (accessory “DS..”)
13 Condensate hose (accessory “KS10”)
14 Steam distribution pipe
(accessory “41-..”/“61-..”/“81-..”)
15 Ventilation unit (accessory “FAN3S...”)
3.6 Overview unit interconnection
Single unit (CP3 5...45)
Main unit, Module A
(CP3 5 ... 45)
Control board
I/O
Heating voltage
Control voltage
Control signal
Remote indication RFI
Double unit (CP3 5...90)
Main unit, Module B
(CP3 46 ... 90)
Heating voltage
Main unit, Module A
(CP3 5 ... 45)
Control board
I/O
Ribbon cable
Heating voltage
Heating voltage
Control voltage
Control signal
Remote indication RFI
Double unit + single unit (CP3 Pro 5...135) or two double units (CP3 Pro 5...180)
---> Link Up systems, Pro versions only
Main unit, Module B
(CP3 46 ... 90)
Main unit, Module A
(CP3 5 ... 45)
Extension unit, Module A
(CP3 91... 135)
Control board
I/O
Ribbon cable
Heating voltage
Control voltage
Control signal
Remote indication RFI
Bus cable max. 50 m
Heating voltage
Control voltage
Control board
I/O
13
14
3.7 Options
3.7.1 Options overview
Condair CP3 Basic... / Condair CP3 Pro...
D...
RFI
OPS Overpressure set
Kit for mounting the water cup to the unit cover when operating the steam humidi fiers in systems with a duct air pressure of up to 10 kPa.
P/B
THV Terminals heating voltage
Separate terminals for systems where direct connection of heating voltage to main contactor (standard version) is not permitted by local regulations.
e-LINKS e-LINKS CP3
Gateway to connect the Condair CP3 to a building management system. Two versions are available: BACnet/IP or LonWorks.
P
1x OPS
B * 1x M-THV
PG
SC..
SCCT.. Steam hose connector with condensate trap
CT
MP
230V1
400V3
Cleanable steam cylinder
Cleanable steam cylinder as an alternative to the disposable steam cylinder built in as standard (see also chapter 3.7.2).
230V3
P/B
Remote operating and fault indication
PCB with relay contacts for the connection of remote displays for “Operation”, “Steam”,
“Fault” and “Service”.
B *
Cable gland
Steam hose connector
Condensate trap
Mounting profile
CVI Internal control voltage
TRAFO Transformer (400V/230V)
P/B
B *
1x PG
1x SC22
B 1x SCCT22
P/B
P/B
P/B
P/B
5...8
5...8
5...8
1x D3..
1x RFI
1x CT22
1x MP
1x M-CVI
1x M-Trafo
9...15
9...15
1x D4..
1x RFI
1x OPS
1x M-THV
52/60/70/80/90 105/120/135
44/50/60
2x D6..
1x RFI
2x OPS
2x L-THV
75/90
3x D6..
1x RFI
3x OPS
3x L-THV
Configuration according to separate documentation
1x PG
1x SC60
1x SCCT60
1x CT60
1x MP
1x M-CVI
1x M-Trafo
B Unit version Basic
P Unit version Pro
* Standard for unit version Pro
** Unit version Basic requires additionally option THV for unit module B
16...45
16...30
1x D6..
1x RFI
1x OPS
1x L-THV
1x PG
1x SC80
1x SCCT80
1x CT80
1x MP
1x L-CVI
1x L-Trafo
2x PG
2x SC80
2x SCCT80
2x CT80
2x MP
1x L-CVI **
1x L-Trafo **
3x PG
3x SC80
3x SCCT80
3x CT80
3x MP
2x L-CVI
2x L-Trafo
152/160/180
100/120
4x D6..
1x RFI
4x OPS
4x L-THV
4x PG
4x SC80
4x SCCT80
4x CT80
4x MP
2x L-CVI
2x L-Trafo
3.7.2 Option details
Steam cylinder
The steam humidifier is available with two different types of steam cylin ders:
–
Exchangeable steam cylinder type A... (standard version)
–
Cleanable steam cylinder type D... (option)
The following tables present an overview of the steam cylinders used in the different models.
9...15
16...25
26...45
52/60/70/80/90 105/120/135 152/160/180 Condair CP3...400V3
5...8
For water conductivity from 125 to 1250 µS/cm
Exchangeable steam cylinder
Cleanable steam cylinder
1xA363
1xD363
For low water conductivity <125 µS/cm
Exchangeable steam cylinder
Cleanable steam cylinder
1xA343
1xD343
Condair CP3...230V3
5...8
For water conductivity from 125 to 1250 µS/cm
Exchangeable steam cylinder 1xA343
Cleanable steam cylinder 1xD343
Condair CP3...230V1
5...8
For water conductivity from 125 to 1250 µS/cm
Exchangeable steam cylinder
Cleanable steam cylinder
1xA342
1xD342
1xA464
1xD464
1xA444
1xD444
9...15
1xA444
1xD444
1xA674
1xD674
1xA654
1xD654
16...21
1xA654
1xD654
1xA664
1xD664
1xA644
1xD644
22...30
1xA644
1xD644
2xA664
2xD664
2xA644
2xD644
44/50/60
2xA644
2xD644
3xA664
3xD664
3xA644
3xD644
75/90
3xA644
3xD644
4xA664
4xD664
4xA644
4xD644
100/120
4xA644
4xD644
If you have questions regarding the steam cylinders please contact your Condair representative.
15
16
3.8 Accessories
3.8.1 Accessories overview
Accessories for water installation
230V1
400V3
230V3
5...8
5...8
5...8
9...15
9...15
Condair CP3 Basic... / Condair CP3 Pro...
16...45
16...30
52/60/70/80/90
44/50/60
Z261 (1 pcs. per system)
105/120/135
75/90
152/160/180
100/120
Filter valve
Accessories for steam installation
Steam distribution pipe
(Details see chapter 3.8.2)
Steam distribution system OptiSorp
(Details see chapter 3.8.2)
Fan unit
(Details see chapter 3.8.2)
Steam hose / meter
Condensate hose / meter
230V1
400V3
230V3
Basic
Pro
Condair CP3 Basic... / Condair CP3 Pro...
5...8
5...8
5...8
1x 41-...
9...15
9...15
1x 61-...
16...45
16...30
1x 81-...
52/60/70/80/90
44/50/60
2x 81-...
105/120/135
75/90
3x 81-...
152/160/180
100/120
4x 81-...
–––
1x
FAN3S CP Basic M or
1x
FAN3S CP Basic M FC
1x
FAN3S CP Pro M or
1x
FAN3S CP Pro M FC
1x DS22 1x DS60
1x KS10
System 1
1x
FAN3S CP Basic L
1x
FAN3S CP Pro L
1x DS80
System 2
2x
FAN3S CP Basic L
3x
FAN3S CP Basic L
2x
FAN3S CP Pro L
2x DS80
2x KS10
System 3
3x
FAN3S CP Pro L
3x DS80
3x KS10
System 4
4x
FAN3S CP Basic L
4x
FAN3S CP Pro L
4x DS80
4x KS10
Accessories for humidity control
Humidity sensor for duct installation
Humidity sensor for room installation
Duct humidistat
Room humidistat
230V1
400V3
230V3
General accessories
5...8
5...8
5...8
230V1
400V3
230V3
5...8
5...8
5...8
All-weather protective housing
9...15
9...15
Condair CP3 Basic... / Condair CP3 Pro...
16...45
16...30
52/60/70/80/90
44/50/60
CDC (1 pcs. per system)
CRC (1 pcs. per system)
HBC (1 pcs. per system)
HSC (1 pcs. per system)
105/120/135
75/90
152/160/180
100/120
9...15
9...15
Condair CP3 Basic... / Condair CP3 Pro...
16...45
16...30
52/60/70/80/90
44/50/60
Layout according to the separate data sheet
105/120/135
75/90
152/160/180
100/120
3.8.2 Accessory details
3.8.2.1 Steam distribution pipe 41-.../61-.../81-...
The steam distribution pipes are selected on the basis of the
duct width (for horizontal installation) or the duct height (for vertical installation) and the capacity of the steam humidifier.
Important! Always select the longest possible steam distribution pipe (opti mum humidification distance).
1)
2)
Steam distribution pipes for
Condair CP3
1)
Type 41-.. Type 61-.. Type 81-..
41-200
41-350
41-500
41-650
41-800
41-1000
41-1200
61-2000
61-350
61-500
61-650
61-800
61-1000
61-1200
61-1500
61-1800
81-350
3)
81-500
3)
81-650
81-800
81-1000
81-1200
81-1500
81-1800
81-2000
81-2300
81-2500
Material: CrNi steel
special length on request
Length (L) steam distribution pipe in mm
2)
Duct width (B) in mm
200
350
500
650
800
1000
1200
1500
1800
2000
2300
2500
210...400
400...600
550...750
700...900
900...1100
1100...1300
1300...1600
1600...2000
2000.2400
2200...2600
2500...2900
2700...3100
3)
up to max. 30 kg/h steam capacity
Note: If the humidification distance (see chapter 5.4.2) has to be reduced for technical reasons, the amount of steam per basic unit must be divided between two steam distribution pipes or the steam
distribution system OptiSorp must be used. If this is the case, contact your Condair supplier.
3.8.2.2 OptiSorp steam distribution system
The OptiSorp steam distribution system is used in ventilation ducts with a short humidification distance
(for the calculation of the humidification distance refer to chapter 5.4.2). When ordering an OptiSorp system the duct dimension must be specified. Please consult the data in the following table.
17
OptiSorp
System 1
System 2
System 3
System 4
Number of steam connectors
1
2
3
4
Max. steam
capacity in kg/h
1)
45 (30)
90 (60)
135 (90)
180 (120)
Duct dimensions
Width in mm Height in mm
450-2700 450-1650
450-2700
450-2700
450-2700
450-2200
800-3200
800-3200
1)
For duct widths <600 mm the values in brackets apply
18
3.8.2.3 Fan unit
The fan units – in combination with the steam humidifiers Condair
CP3 – are used for the direct room humidification. They are mounted
separately above the unit to the wall.
The type of fan unit and the amount required is dependent on the steam capacity and on the type of the basic unit(s) and can be gathered from the table in chapter 3.8.1.
Note: Further information on the fan units can be found in the separate installation and operating instructions supplied with the fan unit.
3.9 Standard delivery
The standard delivery includes:
– Steam humidifier Condair CP3 equipped with the options ordered according to chapter 3.7, fixing set and installation and operating instructions (this document), packaged in cardboard box
– Unit small (WxHxD): 456 mm x 620 mm x 280 mm, shipping weight: 26 kg
– Unit large (WxHxD): 559 mm x 667 mm x 350 mm, shipping weight: 31 kg
– Ordered accessories with operating instructions according chapter 3.8, packed separately
– Spare parts list
3.10 Storing/Transportation/Packaging
Storing
Store the unit in a protected area meeting the following requirements:
– Room temperature: 1 ... 40 °C
– Room humidity: 10 ... 75 %rh
Transportation
For optimum protection always transport the unit in the original packaging.
The weight of the small and the large unit is more than 20 kg (weight without packaging: small unit
23 kg, large unit 28 kg). Therefore, always transport the unit with the help of another person or use a forklift or a crane. Always place the unit on its back side.
Packaging
Keep the original packaging of the Condair CP3 for later use.
In case you wish to dispose of the packaging, observe the local regulations on waste disposal. Never dispose of the packaging to the environment.
4 Notes for the planning engineer
4.1 Selecting the unit version
To select the unit version the following planning steps are required:
1. Calculating the required maximum steam capacity according chapter 4.1.1
2. Selecting the unit version from the table in chapter 4.1.2
4.1.1 Calculating the maximum required steam capacity
The maximum required steam capacity must be calculated based on one of the following formulas:
m
D
=
V • ρ
• (x
2
- x
1
)
1000
or
V
m
D
=
1000 • ε
• (x
2
- x
1
) m
D
: maximum steam demand in
kg/h
V: volume of supply air portion per hour in m to be humidified per hour in
m
ρ: specific gravity of air in kg/m
3
ε: specific volume of air in m
x x
1
3
/kg
2
: desired absolute room air humidity in
g/kg
3
/h (for indirect room humidification) or room volume
3
/h (for direct room humidification)
: minimum absolute supply air humidity in
g/kg
The values for ρ, ε, x moist air respectively.
2
and x
1
can be gathered from the h,x-diagram or the Carrier-Diagram for
Important notes:
– The required maximum steam capacity depends on the specific application and the installation.
The calculated steam capacity based on the above formulas, the h,x diagram and the condition of the air to be humidified does not consider any steam loss (e.g. due to condensation in the steam hoses and the steam distributors), any heat loss of the unit as well as any absorption or release of humidity of materials located in the room being humidi fied.
In addition, the calculated steam capacity does not consider any losses caused by the draining rate depending on the water quality as well as any losses occur if the steam humidifier is operated on a mains circuit with a ground fault circuit interrupter.
The total amount of losses depends on the entire system and must be taken into consideration when calculating the required steam capacity. If you have any questions regarding the calculation of the steam capacity please contact your Condair supplier.
– For systems where the max. required steam capacity varies extensively (e.g. for test facilities or for systems with variable air volume flow, etc.), please contact your Condair supplier.
19
20
4.1.2 Selecting the unit
Condair CP3 Pro 45 400V3
Heating voltage * Max. steam capacity in kg/h
Graduation in kg/h
400V3
(400V/3~/50...60Hz)
230V3
(230V/3~/50...60Hz)
230V1
(230V/1~/50...60Hz)
50
60
75 **
90 **
100 **
120 **
152 **
160 **
180 **
5...15
16...30
44
5...15
16...45
52
60
70
80
90
105 **
120 **
135 **
5...8
* Other heating voltages on request
** Link Up systems
--
--
--
--
--
--
1
1
--
--
--
--
--
--
--
--
--
--
1
1
--
--
1
Model Condair CP3
Basic...
Pro...
--
--
--
50
60
--
--
--
--
5...15
16...30
44
5...15
16...45
52
60
--
--
--
70
80
90
5...8
90
100
120
50
60
75
152
160
180
5...15
16...30
44
5...15
16...45
52
60
105
120
135
70
80
90
5...8
Single unit small
1
Unit size / Number of units
Single unit large
Double unit large
1
1
1
1
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
4.2 Selecting the options an accessories
For selecting the options and accessories see chapter 3.7 and 3.8.
4.3 Selecting the control system
The various control systems
–
System 1: Room humidity control
System 1 is suited for direct room humidification and air conditioning systems with mainly
recirculated air. The humidity sensor or humidistat respectively is preferably located in the room itself or in the exhaust air duct.
21
A1 humidity sensor
B1 ventilation interlock
B2 airflow monitor
B3 safety humidistat
B4 humidistat
PI
I
Internal P/PI controller
PI
E
External continuous controller
(e.g. PI controller)
Y input signal from A1
–
System 2: Room humidity control with continuous limitation of the supply air humidity
System 2 is suited for air conditioning systems with a large portion of supply air, low supply
air temperature, post-humidification, or variable airflow volume. If the supply air hum idity exceeds the preset value, the continuous limitation is effected prior to the room hum idity control.
The humidity sensor (A1) is preferably located in the exhaust air duct or in the room itself. The humidity sensor (A2) for the limitation of the supply air humidity is located in the supply air duct after the steam distribution pipe. This control system requires a continuous controller with the option to connect a second humidity sensor.
Attention! The continuous limitation of the supply air humidity is no substitute for the safety humidistat.
A1/2 humidity sensor
B1 ventilation interlock
B2 airflow monitor
B3 safety humidistat
PI
I
PI
E
Internal P/PI controller
External continuous controller
(e.g. PI controller)
Y input signal from A1
Z input signal from A2
22
–
System 3: Supply air humidity control with continuous output limitation
Supply air humidity control (humidity sensor installed in supply air duct) should be used
only where room humidity control is impracticable for technical reasons. Such systems always require a PI-controller.
The humidity sensor (A1) is located in the supply air duct after the steam distribution pipe. The humidity sensor (A2) for the continuous output limitation is located in the supply air duct before the steam distribution pipe. Such a system requires a PI-controller with the option to connect a second humidity sensor.
A1/2 humidity sensor
B1 ventilation interlock
B2 airflow monitor
B3 safety humidistat
PI
I
PI
E
Internal PI controller
External PI controller
Y input signal from A1
Z input signal from A2
Which humidity control system for which application?
Application Location of the humidity sensor room or exhaust air duct supply air duct
Air conditioning systems with:
– supply air portion up to 33%
– supply air portion up to 66%
– supply air portion up to 100%
– supply air humidity control
Direct room humidification
System 1
System 1 or 2
System 2
—
System 1
System 1
System 2 or 3
System 3
System 3
—
Please contact your Condair supplier, if your application meets the following conditions:
– Humidification of small rooms up to 200 m
3
– Air conditioning systems with a high number of air exchanges
– Systems with variable air volume flow
– Test facilities with extreme control accuracy requirements
– Rooms with a high variation in max. steam capacity
– Systems with temperature fluctuations
– Cold rooms and systems with dehumidification
Input signals
Control with external controller
Control signals
0...5 VDC (Potentiometer 135 Ω ... 10 kΩ)
1...5 VDC
0...10 VDC
2...10 VDC
0...16 VDC
3.2...16 VDC
0 ... 20 mA
4 ... 20 mA
Humidistat (24 V On/Off)
Control with internal PI controller
Humidity sensor signals
0...5 VDC (Potentiometer 135 Ω ... 10 kΩ)
1...5 VDC
0...10 VDC
2...10 VDC
0...16 VDC
3.2...16 VDC
0 ... 20 mA
4 ... 20 mA
23
24
5 Mounting and installation work
5.1 Important notes for mounting and installation work
Qualification of personnel
All mounting and installation work must be carried out only by
well qualified personnel authorised
by the owner. It is the owner’s responsibility to verify proper qualification of the personnel.
General note
Strictly observe and comply with all information given in the present installation and operating instructions regarding the location of the unit and the installation of water, steam and electricity.
Observe and comply with all local regulations dealing with water, steam and electrical installations.
Safety
Some installation work requires removal of the unit cover. Please note the following:
DANGER!
Danger of electrical shock!
You may get in touch with live parts when the unit is open. The steam humidifier must be connected to the mains only after all mounting and installation work has been completed and the cover has been relocated properly.
CAUTION!
The electronic components inside the humidifier are very sensitive to electrostatic discharge.
When the unit is open for installation work, appropriate measures must be taken to protect these components against damage caused by electrostatic discharge (ESD protection).
5.2 Mounting the unit
5.2.1 Notes on locating the unit
min. 250 mm
60...70 °C
min. 400 mm
50 mm
T
B
Module
A
min. 600 mm
Module B
1 ... 40 °C max. 75 %rh
IP20
25
Condair CP3 ... 230V1
Condair CP3 ... 230V3
Condair CP3 ... 400V3
Dimensions
Housing (BxHxT) in mm
Weights
Net weight in kg
Operating weight in kg
456x620x280
559x667x350
Basic Pro
5...8
Basic Pro Basic Pro Basic Pro Basic Pro Basic Pro
5...8
9...15
16...21
22...30
44/50/60
Pro
75/90
Pro
100/120
Basic Pro Basic Pro Basic Pro Basic Pro Basic Pro
5...8
9...15
16...25
26...45
Pro Pro
52/60/70/80/90 105/120/135 152/160/180
1 1
21
26
21
32
1
28
65
1
28
65
2
2x 28
2x 65
3
3x 28
3x 65
4
4x 28
4x 65
26
The installation site of the steam humidifier depends largely on the location of the steam distributor
(see chapter 5.3). To ensure proper functioning of the steam humidifier and to obtain an optimal
efficiency, the following points must be considered and observed when choosing the location for the steam humidifier:
– Install the steam humidifier so that the
length of the steam hose is kept as short as possible
( max. 4 m) and that the minimum bend radius (R= 300 mm) and up-slope (20 %) or down-
slope (5 %) of the steam hose is observed (see chapter 5.3.5).
– The steam humidifiers Condair CP3 are designed for wall-mounting. Make sure that the construction (wall, pillar, floor-mounted console, etc.) to which the humidifiers are to be mounted, offers a sufficiently high load-bearing capacity (take notice of the weight information found in the dimension sand weights table above), and is suitable for the installation.
CAUTION!
Do not mount the steam humidifier directly to the ventilation duct (insufficient stability).
– The back panel of the Condair CP3 is retaining heat during operation (max. surface temperature of the metal housing approx. 60 - 70 °C). Make sure, therefore, that the construction (wall, pillar, etc.) to which the units are to be mounted, does not consist of heat-sensitive material.
– Install the steam humidifier in such a manner that it is freely accessible with sufficient space available for maintenance purposes (refer to the above illustration for minimum distances).
– The Condair CP3 is protected according to IP20. Make sure the units are installed in a drip-proof location and the admissible ambient conditions are complied with.
– The steam humidifier Condair CP3 may only be installed in rooms with a floor drain.
CAUTION!
If for some reason the Condair CP3 must be installed in a location without floor drain, it is mandatory to provide a leakage monitoring device to safely interrupt the water supply in case of leakage.
– When fixing the Condair CP3 use only the fixing materials supplied with the unit. If fixing with the materials supplied is not possible in your particular case, select a method of fixing that is of similar stability.
– The Condair CP3 is designed for installation and operation within buildings (admissible temperature range see chapter 10.1). For outdoor operation the Condair CP3 must be placed in a weather protective housing. If ambient temperatures near or below the freezing point have to be expected, the protective housing must equipped with a thermostat controlled heating of sufficient capacity. The water supply pipe must be equipped with a trace-heating and must be insulated up to the protective housing. Furthermore the special notes regarding the operation at ambient temperatures ≤ 0°C must be observed (see chapter 6.3.2).
5.2.2 Mounting the humidifier
a
A
B d e
B
Dimension c d a b e
Housing size small
228 mm
51 mm
500 mm
90 mm
180 mm
large
284 mm
51 mm
545 mm
144 mm
216 mm
27
Procedure
1. Mark the attachment point “A” on the wall.
2. Drill hole for attachment point “A” (diameter: 8 mm, depth: 40 mm).
3. Insert the supplied plastic plug, and tighten the screw until the distance between the wall and the screw head is 4 mm.
4. Unlock the two screws fixing the front panel to the unit, then remove the front panel.
5. Hang up the unit onto the screw and adjust it horizontally and vertically using a spirit level. Then, mark the fixing points “B”.
6. Drill the holes for the fixing points “B” (diameter: 8 mm, depth: 40 mm).
7. Insert the supplied plastic plugs, and tighten the screws until the distance between the wall and the screw head is 4 mm.
8. Hang the unit up onto the screws. Before tightening the screws, readjust the unit with the spirit level.
9. Reattach the front panel and secure it with the two screws.
28
5.2.3 Inspecting the installed unit
Check the following points:
Is the unit installed in the correct place (see chapter 5.2.1)?
Is the supporting surface stable enough?
Is the unit correctly aligned, vertically and horizontally?
Is the unit properly secured (see chapter 5.2.2)?
Has the front panel of the unit been relocated and correctly fixed with the two screws?
5.3 Steam installation
5.3.1 Overview steam installation
Basic
FAN3S CP Basic M
FAN3S CP Basic L
Pro
FAN3S CP Pro M FC
FAN3S CP Pro M
FAN3S CP Pro L
41-...
61-...
81-...
Pmax
Pmin
1500 Pa
-800 Pa
41-...
61-...
81-...
Pmax
Pmin
1500 Pa
-800 Pa min. 20 %
–
KS10
Ømin. 200 mm
– min. 20 %
Ømin. 200 mm min. 5 %
– max. 4 m
KS10
Rmin. 300 mm
Rmin. 300 mm max. 4 m min. 5 %
–
+ min. 20 %
DS22
DS60
DS80
DS60
DS80
29
30
5.3.2 Positioning and mounting of the steam distribution pipes
The location for the steam distribution pipes should be determined at the time of dimensioning the air conditioning system. Please note the following instructions to ensure proper humidification of the duct air.
Calculating the humidification distance
The water vapour, emitting from the steam distribution pipes, requires a certain distance to be absorbed by the ambient air so that it is no longer visible as steam. This distance is referred to as
humidification distance “B
N
” and serves as a basis for the determination of the minimum distances from the upstream components in the system.
Humidification distance B
N
Expansion and mixing zone
φ1: Supply air humidity before humidification
φ2: Supply air humidity after humidification
The calculation of the humidification distance “B estimation of the humidification distance “B
N
” is dependent on several factors. For a rough
N
”, the following table is useful. Recommended standard values listed in this table are based on a supply-air temperature range of 15 °C to 30 °C. The values given in bold type only apply to steam distribution pipes 41-..., 61-... and 81-..., the values in
brackets apply to the OptiSorp steam distribution system.
Humidity at inlet
φ1 in %rh
5
10
20
30
40
50
60
70
Length of humidification distance B
N
in m
Humidity at outlet φ2 in %rh
40 50 60 70 80 90
0,9 (0,22) 1,1 (0,28) 1,4 (0,36) 1,8 (0,48) 2,3 (0,66) 3,5 (1,08)
0,8 (0,20) 1,0 (0,26) 1,3 (0,34) 1,7 (0,45) 2,2 (0,64) 3,4 (1,04)
0,7 (0,16) 0,9 (0,22) 1,2 (0,30) 1,5 (0,41) 2,1 (0,58) 3,2 (0,96)
0,5 (0,10) 0,8 (0,17) 1,0 (0,25) 1,4 (0,36) 1,9 (0,52) 2,9 (0,88)
–
–
–
–
0,5 (0,11) 0,8 (0,20) 1,2 (0,30) 1,7 (0,45) 2,7 (0,79)
–
–
–
0,5 (0,13)
–
–
1,0 (0,24)
–
1,5 (0,38)
0,7 (0,16) 1,2 (0,30) 2,1 (0,58)
0,8 (0,20)
2,4 (0,69)
1,7 (0,45)
For duct widths <600 mm the humidification distance for the OptiSorp system increases by approx. 50%
φ1 in %rh: Relative supply air humidity prior to humidification at the lowest supply air temperature
φ2 in %rh: Relative supply air humidity after the steam distribution pipe at maximum capacity
Example given: humidification distance B
N
:
φ1= 30 %rh, φ2= 70 %rh
1,4 m (0.36 m for steam distribution system OptiSorp)
Note: If the humidification distance has to be reduced for technical reasons, the amount of steam per basic unit must be divided between
two steam distribution pipes or the steam distribution
system OptiSorp must be used. If this is the case, contact your Condair supplier.
Minimum distances to be observed
To prevent the water vapour, that is emitting from the steam distribution pipe, from condensing on downstream system components, a minimum distance to the steam distribution pipe must be observed
(depends on the humidification distance “B
N
”).
before/after constriction after expansion before bend
31
before branch before diffuser before control sensor before/after filter/register before/after fan, zone exit
1.5 x B
N *
5 cm
2,5 x B
N
before aerosol filter
B
N
B
N
Installation notes and dimensions
The steam distribution pipes are designed for either horizontal installation (on the duct wall) or, with accessories, for vertical installation (in the duct floor). The outlet orifices should always point
upwards and at right angles to the airflow.
If possible, the steam distribution pipes should be installed on the pressure side of the duct (max.
duct pressure 1500 Pa). If the steam distribution pipes are installed on the suction side of the duct, the maximum vacuum must not exceed 800 Pa.
Select a location for the installation, tailored to suit your duct (see the following illustrations) and position the steam distribution pipes in the duct so that a uniform distribution of steam is achieved.
32
In positioning the steam distribution pipes, the following dimensions should be observed:
1/2
1/2
1/2
1/2
2/3
1/3 h min
H
H
H
H min.= 250 mm H ≥400 mm H min.= 200 mm
1/3
1/3
1/3
H
3/7
2/7
2/7 h min
H min.= 400 mm
H
3/7
2/7
2/7 h min g min
H min.= 350 mm
H
H min.= 300 mm
1/4
1/4
1/4
1/4
H
2/5
1/5
1/5
1/5 h min
H min.= 600 mm
H
2/5
1/5
1/5
1/5 h min g min g min
H min.= 500 mm
H
H min.= 400 mm
2/6
1/6
1/6
1/6
1/6 h min
H min.= 720 mm g min.= 100 mm h min.= 85 mm
H
2/6
1/6
1/6
1/6
1/6 h min g min g min g min
H min.= 600 mm
H
1/5
1/5
1/5
1/5
1/5
H
H min.= 500 mm
Note: When locating the OptiSorp steam distribution system please note the instructions in the separate documentation for this product.
Guidelines for dimensioning the ventilation ducts
– To facilitate the installation of the steam distribution pipes and for control purposes, a sufficiently sized control opening should be planned.
– Within the range of the humidification distance, the ventilation duct should be waterproofed.
– Air ducts passing through cold rooms should be insulated to prevent the humidified air from condensing along the duct wall.
– Poor airflow conditions within the air duct (e.g. caused by obstacles, tight bends, etc.) can lead to condensation of the humidified air.
– Steam distribution pipes must not be mounted to round ducts.
If you have questions relating to the dimensioning of ventilation ducts in combination with steam humidifiers Condair CP3, contact your Condair supplier.
5.3.3 Installing the steam distributors
Detailed information on the installation of steam distribution pipes 41-.., 61-.../81-... and OptiSorp steam distribution system can be found in the separate “Mounting Instructions” for this products.
33
34
5.3.4 Positioning and mounting of the fan unit
The fan unit is mounted on the wall separately above the unit. To allow the steam coming from the fan unit to spread out evenly, without condensing on obstacles (ceilings, joists, pillars, etc.), the following minimum dimensions must be observed when selecting the location for the fan unit.
D
D
D
D
B
B
E
C
C
A A m
D
max.
A min.
B min.
C min.
D min.
E min.
E max. (max. steam hose length)
FAN3S CP ... M
FAN3S CP ... M FC
8 kg/h
4.0 m
1.0 m
2.2 m
1.0 m
FAN3S CP ... L
15 kg/h
6.0 m
1.0 m
2.2 m
30 kg/h
8.0 m
1.0 m
2.2 m
1.0 m 1.0 m
0.15 m
4.0 m (recommended: 2.0 m)
45 kg/h
10.0 m
1.5 m
2.2 m
1.5 m
Note: The minimum spaces in the table apply for a room atmosphere of 15 °C and max. 60 %rh. For lower temperatures and/or higher humidity the values should be adjusted accordingly
Note: In order to achieve a uniform distribution of the humidity within the room, additional factors such as the room size, the room height, etc., must be taken into consideration besides observing the minimum distances. If you have questions concerning the direct room humidification, please contact your Condair supplier.
Further information is provided in the separate installation and operating instructions for the fan unit.
5.3.5 Installing the steam hose
Important! Use original Condair steam hose exclusively. Other types of steam hoses can cause undesired operational malfunctions.
Instructions for the hose layout
The hose layout depends on the position of the steam distribution pipe:
– Steam distribution pipe is mounted more than 300 mm above the top edge of the humidifier:
35 min. 5 %
Rmin.300 mm min. 20 % min. 20 %
Rmin.
300 mm
Initially, lead the steam hose with an
upslope of at least 20% over a minimum height of 300
mm, then lead the hose with a minimum upslope of 20% and/or a minimum downslope of
5% to the steam distribution pipe.
– Steam distribution pipe is mounted less than 300 mm above the top edge of the humidifier: min. 5 % min. 20 % min. 5 % min. 20 %
Rmin. 300 mm min. 20%
300 mm
Rmin.
Initially, the steam hose is led with an
upslope of at least 20 % over a minimum height of 300
mm above the top edge of the humidifier and then down to the steam distribution pipe with a
minimum slope of 5 %.
– The steam hose should be kept as short as possible ( max. 4 m) while observing the minimum
bend radius of 300 mm. Important! Allowance must be made for a pressure loss of 10 mm
water column (approx. 100 Pa) per meter steam hose.
Note: If your particular installation exceeds the maximum steam hose length of 4 m contact your
Condair representative. In any case, steam hoses longer than 4 m must be insulated in their entire length.
– Reductions in the cross section such as kinks should be avoided throughout the entire length of the hose. The installation of a stop cock in the steam hose is not permissible.
36
– Steam hoses must be prevented from sagging (condensate pockets); if necessary, support with pipe clamps, trough, or wall brackets, or install a condensate drain in the steam hose.
– Important! When deciding on the length and layout of the hose, it should be noted that the steam hose may become somewhat shorter with progressive ageing.
Securing the hose
The steam hose must be secured to the steam distribution pipe and humidi fier steam outlet by means of hose clamps.
Caution! Do not overtighten the hose clamp on the steam connector of the steam humidifier.
Steam line with fixed piping
For steam lines with fixed piping, the same instructions apply to the laying of the piping as already described. The following additional notes should be observed:
minimum internal diameter of 22 mm, 30 mm or 45 mm respectively should be applied over the whole length of the piping.
– Use exclusively Cu pipe or stainless steel (min. DIN 1.4301).
– To minimize the condensate formation (=loss), the steam pipes must be insulated.
– Connection of the steam pipe to the steam distribution pipe and to the steam humidifier is effected by means of short lengths of steam hose secured with hose clamps.
– Important! Allowance must be made for a pressure loss of 10 mm water column (approx.
100 Pa) per meter length or per 90° bend.
5.3.6 Installing the condensate hose
Important! Use original Condair condensate hose exclusively. Other types of hoses can cause operational malfunctions.
The hose layout depends on the position of the steam distribution pipe:
– Steam distribution pipe is mounted more than 300 mm above the top edge of the humidifier:
Condensate hose is led down to the humidifier with a minimum slope of 20 %, in the form of a
siphon (min. hose bend diameter Ø200 mm ), and inserted about 2 cm into the specified opening.
min. 20 %
Ømin. 200 mm min. 20 %
Ømin. 200 mm
– Steam distribution pipe is mounted less than 300 mm above the top edge of the humidifier:
Condensate hose is led down with a minimum slope of 20 %, in the form of a siphon (min.
hose bend diameter Ø200 mm), directly into a discharge funnel.
37 min. 20 % min. 20 %
Ømin. 200 mm
Ømin. 200 mm
Note: If your unit feeds a number of steam distribution pipes, the individual condensate hoses are to be led into the discharge funnel.
Important! Before putting the unit into operation, the siphon of the condensate hose must be filled with water.
5.3.7 Inspecting the steam installation
Use the following check list to ascertain that the steam installation was performed correctly:
– Steam distribution pipe
Steam distributors (steam distribution pipe or OptiSorp steam distribution system) correctly positioned and secured (screws tightened)?
Are the outlet orifices at right angles to the air flow direction?
– Steam hose
Maximum length of 4 m?
Minimum bend radius of 300 mm (4-5 x internal diameter with fixed piping)?
Have the instructions for hose positioning been followed?
Steam hose: no sagging (condensate pocket) or condensate drain with siphon (hose bend with a minimum diameter of 200 mm) installed at the lowest point?
Rigid steam lines: properly insulated? Correct installation material used? Minimum internal diameter maintained?
Steam hose(s) securely attached with clamps?
Heat expansion during operation and shortening of the hose with ageing taken into consideration?
– Condensate hose
Downslope of at least 20 %?
Siphon (min. ø 200 mm) existing and filled with water?
Condensate hose correctly fixed and not kinked?
38
5.4 Water installation
5.4.1 Overview water installation
ø40 mm
125...1250 µS/cm
1...10 bar
1...40 °C
G 1/2"
G 1/2"
ø10/8 mm
DS80
Z261
≥ 40 mm min. 10 %
– min. 10 %
–
5.4.2 Notes on water installation
Water supply
The water supply is to be carried out according to the figure found in chapter 5.4.1 and the applicable local regulations for water installations. The indicated connection specifications must be observed.
– The installation of the filter valve (accessory “Z261”, alternatively a shut-off valve and a 5 µm water filter can be used) should be made as close as possible to the steam humidifier.
– Admissible mains pressure
1.0 to 10.0 bar (hammer-free system)
For mains pressures >10 bar, the connection must be made via a pressure reducing valve (adjusted to 1.0 bar). For mains pressures <1.0 bar please contact your Condair supplier.
– Notes on water quality:
– For the water supply of the Condair CP3, use exclusively untreated drinking water.
– The use of additives such as corrosion inhibitors, disinfectants, etc. is not allowed, since these additives may endanger health and affect proper operation.
– If the Condair CP3 shall be operated with softened or partly softened water, please contact your Condair supplier.
– The connection material must be pressure-proof and certified for use in drinking water systems.
– Important! Before connecting the water line, the line should be well flushed out.
CAUTION!
The thread at the humidifier connection is made of plastic. To avoid overtightening, the union nut of the water pipe must be tightened by hand only.
39
Water drain
The water drain is to be carried out according to the figure found in chapter 5.4.1 and the applicable local regulations for water installations. The indicated connection specifications must be observed.
– Make sure that the drain pipe is correctly fixed and easily accessible for inspections and cleaning purposes.
– The draining temperature is: 80…90 °C (approx. 70...80 °C with activated drain water cooling).
Use temperature-resistant installation materials only!
40
5.4.3 Inspecting the water installation
Check the following topics:
– Water supply
Has filter valve (accessory “Z261”) or shut-off valve and 5 µm water filter respectively been installed in supply line?
Have admissible water pressure (1 – 10 bar) and admissible temperature (1 – 40 °C) been observed?
Does the supply capacity match the humidifier and is the minimum inside diameter of the supply pipe maintained throughout the entire length?
Are all components and pipes properly secured and are all threaded connections securely tightened?
Is the water system properly sealed?
Does the water supply installation meet the requirements of the local regulations for water installations?
– Water drain
Is the minimum inside diameter of the drain pipe of 40 mm maintained throughout the entire length?
Has drain pipe been installed with a downslope of at least 10 %?
Has the heat resistance of the material used been verified to be at least 100 °C?
Is the drain hose properly secured (hose clamps at unit connection tightened)?
Does the water drain installation meet the requirements of the local regulations for water installations?
5.5 Electric installation
5.5.1 Wiring diagram Condair CP3 Basic/Pro
X15
X5
S2 LEVEL
L'
CONTA.
N L'
DRAIN
N L' N
INLET
L'
SC
N L1FU N
SWITCH
L1SW NSW
JP4
JP1
JP5
LINK UP
OR CONTACT DRAIN INLET SC SYSTEM
315mAT
EXTERNAL CON.
F3
CPU BOARD
. SIGN. GNDIN
X10
X11
X14
X6
X1
V+
IN
GND
Analog Out
4 3 2 1 2 1
Max. 60mA
Sensor Supply
V+
IN
CP3 Card Main unit
J3 DRIVER B J2 FAUL
X15
X5
S2 LEVEL
L'
CONTA.
N L' N
DRAIN
N
INLET
L' L'
SC
N L1FU N
SWITCH
L1SW NSW
OR CONTACT DRAIN INLET SC SYSTEM
JP4
JP1
JP5
LINK UP
EXTERNAL CON.
315mAT
F3
CPU BOARD
. SIGN. GNDIN
X10
X11
X14
X6
X1
400 V/3~/50..60 Hz 230 V/3~/50..60 Hz
400 V/3~/50..60 Hz 230 V/3~/50..60 Hz
41
42
5.5.2 Wiring diagram CP3 Pro Link Up systems
X15
X5
S2 LEVEL
L'
CONTA.
N L'
DRAIN
N L' N
INLET
L'
SC
N L1FU N
SWITCH
L1SW NSW
JP4
JP1
JP5
LINK UP
OR CONTACT DRAIN INLET
EXTERNAL CON.
315mAT
F3
SC SYSTEM
CPU BOARD
. SIGN. GNDIN
X10
X11
X6
X1
230 V/1~/ 50..60 Hz
Extension Module B (if existing)
CP3 Card Extens. unit
J3 DRIVER B J2 FAUL
X15
X5
S2 LEVEL
L'
CONTA.
N L'
DRAIN
N L' N
INLET
L'
SC
N L1FU N
SWITCH
L1SW NSW
JP4
JP1
JP5
LINK UP
OR CONTACT DRAIN INLET
EXTERNAL CON.
315mAT
F3
SC SYSTEM
CPU BOARD
. SIGN. GNDIN
X10
X11
X6
X1
V+
IN
GND
Analog Out
4 3 2 1 2 1
Max. 60mA
Sensor Supply
V+
IN
CP3 Card Main unit
J3 DRIVER B J2 FAUL
X15
X5
S2 LEVEL
L'
CONTA.
N L'
DRAIN
N L' N
INLET
L'
SC
N L1FU N
SWITCH
L1SW NSW
JP4
JP1
JP5
LINK UP
OR CONTACT DRAIN INLET
EXTERNAL CON.
315mAT
F3
SC SYSTEM
CPU BOARD
. SIGN. GNDIN
X10
X11
X6
X1
Safety Chain
400 V/3~/50..60 Hz 230 V/3~/50..60 Hz
400 V/3~/50..60 Hz 230 V/3~/50..60 Hz
400 V/3~/50..60 Hz 230 V/3~/50..60 Hz
5.5.3 Wiring diagram Option CVI and Option Trafo
Option CVI
L1 N SC1 SC2 PE
L1 L2 L3
K1
L1 N SC1 SC2 PE
Option Trafo
L1 L2 L3
K1
F7
L1 L1 L2 L3 N PE
XE1
Trafo
0 500 480 460 440 400 0 Si
220
F7/F8 = 6.3 AT
F7 F8
L1 L1 L2 L3 L3 PE
XE1
max.
K
B3
∆p
B2
B1
L1 N
M
Q5
F5
L1 L2 L3 N PE
400 V/3~/50..60 Hz
230 V/3~/50..60 Hz max.
K
B3
∆p
B2
B1
L1 N
M
Q5
F5
L1 L2 L3 PE
400 V/3~/50..60 Hz
5.5.4 Fuses F5 for heating voltage supply
Heating voltage
400V3
(400V/3~/50...60Hz)
230V3
(230V/3~/50...60Hz)
230V1
(230V/1~/50...60Hz)
Max. steam capacity
[kg/h]
90
100
120
5
6...8
44
50
60
75
152
160
180
5...8
9...15
16...21
22...26
27...30
90
105
120
135
52
60
70
80
5...8
9...12
13...15
16...20
21...25
26...30
31...42
43...45
Model Condair CP3
Basic...
--
5
--
--
6...8
44
50
60
--
--
--
--
5...8
9...15
16...21
22...26
27...30
90
--
--
--
52
60
70
80
5...8
9...12
13...15
16...20
21...25
26...30
31...42
43...45
Unit design
**
2x DG
2x DG
2x DG
EK
EK
EG
EG
EG
DG
DG
DG
DG + EG
DG + EG
2x DG
2x DG
EK
EK
DG
DG
DG
DG
DG
DG + EG
DG + EG
DG + EG
EG
EG
EG
EG
EK
EK
EK
EG
Pro...
90
100
120
5
6...8
44
50
60
75
152
160
180
5...8
9...15
16...21
22...26
27...30
90
105
120
135
52
60
70
80
5...8
9...12
13...15
16...20
21...25
26...30
31...42
43...45
** EK= Single unit small / EG= Single unit large / DG= Double unit large
Note: The minimum cross section of the supply cable must comply with the local regulations.
Nominal power
[kW]
4x 28.5
4x 30.0
4x 33.8
6.0
11.3
15.8
19.5
22.5
2x 16.5
2x 18.8
2x 22.5
3x 18.8
3x 22.5
4x 22.5
4x 22.5
3.8
6.0
2x 19.5
2x 22.5
2x 26.3
2x 30.0
2x 33.8
3x 26.3
3x 30.0
3x 33.8
6.0
9.0
11.3
15.0
18.8
22.5
31.5
33.8
Nominal
current
[A]
4x 41.1
4x 43.3
4x 48.8
15.8
29.6
41.4
51.2
59.1
2x 43.4
2x 49.3
2x 59.1
3x 49.3
3x 59.1
4x 59.1
4x 59.1
16.3
26.1
2x 28.1
2x 32.5
2x 37.9
2x 43.3
2x 48.8
3x 37.9
3x 43.3
3x 48.8
8.7
13.0
16.3
21.7
27.1
32.5
45.5
48.8
Main fuses F5
[A]
4x (3x 50)
4x (3x 50)
4x (3x 63)
3x 20
3x 40
3x 50
3x 63
3x 80
2x (3x 63)
2x (3x 63)
2x (3x 80)
3x (3x 63)
3x (3x 80)
4x (3x 63)
4x (3x 80)
20
35
3x 10
3x 16
3x 20
3x 25
3x 35
3x 40
3x 50
3x 63
2x (3x 40)
2x (3x 40)
2x (3x 50)
2x (3x 50)
2x (3x 63)
3x (3x 50)
3x (3x 50)
3x (3x 63)
43
44
5.5.5 Inserting the CP3 Card
All important operating parameters such as the maximum steam capacity, the heating voltage, the number of base units as well as the differentiation between main and extension unit are permanently stored on the CP3 Card.
Before you start the electrical installation, check whether the CP3 Card is installed. If it is not,
check whether the type designation on the CP3 Card supplied corresponds with the type designation on the data plate of the unit (the data plate is located above the type plate of the
unit). If the designations match, place the CP3 Card in the card holder on control print . Then cover the data plate above the type plate with the data plate supplied (self-adhesive).
If the type designation on the CP3 Card and the data plate do not match, the CP3 Card must not be installed. If this is the case, contact your Condair supplier.
5.5.6 Notes on electric installation
– The electric installation must be carried out according to the wiring diagram in chapter 5.5.1 or
5.5.2 and the applicable local regulations. All information given in the corresponding wiring diagram must be followed and observed.
– All cables must be lead into the unit via the cable openings equipped with cable glands (e.g. option “PG-cable gland”). The cable for the heating voltage supply must be lead into the unit from the bottom via the cable opening equipped with the clamp strap. Fix the cable with the clamp strap.
– Make sure the cables do not scrub on any components.
– Maximum cable length and required cross section per wire must be observed.
– The supply voltages for heating and control must match the respective voltages stated in the wiring diagram.
5.5.7 Inspecting the electrical installation
Check the following points:
Do the supply voltages for heating and control comply with the relevant voltages given in the wiring diagram?
Is the correct CP3 Card inserted?
Are the voltage supplies (heating and control voltage) correctly fused?
Is the service switch “Q..” installed in the supply line for to the heating and control voltage?
Are all components correctly connected according to the wiring diagram?
Are all connecting cables fastened?
Are the connecting cables free of tension (passed through cable glands?)
Does the electric installation meet the applicable local regulations for electric installations?
Is the front panel mounted and correctly fixed with the two screws?
6 Operation
6.1 Function of the display and operating elements
Display and control unit
Function: Configuration of the Condair CP3.
Indication of operating parameters.
Reset of maintenance counter and error indication.
red LED “Error”
Function: The LED lights in case of a malfunction of the unit. The type of malfunction is shown in the display, see chapter 8).
The LED flashes alternately with the green LED if the external safety chain (ventilation interlock, safety humidistat, etc.) is open.
yellow LED “Warning”
Function: The LED lights if the cylinder maintenance is due.
green LED “Steam”
Function: The LED lights if the unit produces steam.
The LED flashes alternately with the red LED if the external safety chain (ventilation interlock, safety humidistat, etc.) is open.
Drain key
Function: Manual draining of the steam cylinder. After having pressed the drain key, the draining is controlled via the display and control unit.
Unit switch
Function: Switches the unit on and off. The switch is illuminated when the unit is running.
6.2 Commissioning
Proceed as follows when putting the unit into operation:
1. Examine the steam humidifier and installation for possible damage.
DANGER!
Damaged devices or devices with damaged installation may present danger to human life or cause severe damage to material assets.
Damaged units and/or units with damaged or faulty installation must not be operated.
2. Check whether the front panel is mounted and fixed with the two screws.
3. Open the filter valve (or the shut-off valve, respectively) in the water supply line.
4. Verify the set humidity value at the humidity controller or at the humidistat, and readjust as required.
5. Switch on the service switches for mains supplies (heating and control voltage).
45
46
6. Actuate the unit switch of the steam humidifier. Switch lights up.
CP3 PRO
Menu Set
The steam humidifier carries out a system test, during which all the
LEDs light up and the opposite display is shown.
If a failure occurs on the system test, a corresponding error message is shown in the display.
CP3 P45 400V3
Menu
CP3 P45 400V3
Menu
Set
Set
After the system test the unit is in normal operation mode. The display shows the standard operating display (first page of the indication level).
Note: The contents of the standard operating display depends on the actual operating status and on the configuration of the Condair CP3 and can differ from the opposite display.
As soon as the humidity controller or the humidistat requires humidity, power is switched on for heating. The inlet valve opens (slight delay) and the steam cylinder fills with water. As soon as the submerged electrodes heat the water up the green LED lights up and after a few minutes (approx. 5–10 minutes, depending on the conductivity of the water) steam is produced.
Note: If the Condair CP3 is operated with water of low conductivity it may happen that the maximum steam capacity is not reached in the first few hours of operation. This is normal. As soon as the conductivity has reached a sufficient level (due to the vaporisation process) the humidifier will reach the maximum steam capacity.
6.3 Notes on operation
6.3.1 Remote operating and fault indication
Via the operating and fault indication the following operating status are shown remotely:
Activated remote indication relay
H1 “Error”
When?
Display on unit
H2 “Service”
H3 “Steam demand”
H4 “Unit on”
A malfunction is present, further operation is not possible, the heating voltage is interrupted
Steam cylinder maintenance is due. The unit remains operational for a certain time
Steam demand/
Steam production
Unit ready for operation
Red LED lights
An error message is shown in the display
Yellow LED lights
The service warning message is shown in the display
Green LED lights
The standard operating display is shown.
Unit switch lights
The standard operating display is shown.
6.3.2 Notes on the operation at ambient temperatures ≤ 0°C
If during operation ambient temperatures ≤ 0°C must be expected (operation of the Condair CP3 in a protective housing outside the building), the standby draining function must be set to “Full” and the period of time in standby operation after which an automatic cylinder draining takes place must be set to 1 hour (see chapter 6.7.9).
6.3.3 Inspections during operation
During operation the Condair CP3 and the humidification system have to be inspected weekly. On this occasion check the following:
• the water and steam installation for any leakage.
• the steam humidifier and the other system components for correct fixing and any damage.
• the electric installation for any damage.
If the inspection reveals any irregularities (e.g. leakage, error indication) or any damaged components take the Condair CP3 out of operation as described in chapter 6.4. Then, contact your Condair representative.
47
6.3.4 Carrying out manual draining
Proceed as follows to drain the unit manually:
Manual Drain
Press START or STOP
Modul A
Esc Start Set
1. Briefly press the drain key. The drain dialogue appears in the display.
2. Press the <Start> key. The heating voltage is interrupted and the drain pump starts. The yellow LED flashes.
To stop the drain cycle press the <Stop> key.
Note: By pressing the
<Esc> key the unit returns to the indication level. A drain cycle in progress will be stopped automatically.
6.4 Taking the unit out of operation
In order to take the steam humidifier out of operation, perform the following steps:
1. If the unit has to be switched off because of a malfunction, please note the error code of the actual error message shown in the display.
2. Close the shut-off valve in the water supply line
3. Start manual draining (see chapter 6.3.4) and wait until the steam cylinder is empty.
4.
Actuate the unit switch
5. Disconnect steam humidifier from the mains: Switch off all service switches to mains supplies (heating and control voltage) and secure switches in “off” position against accidentally being switched on, or clearly mark the switches.
6. If ambient temperatures ≤ 0°C must be expected when the unit is out of operation (operation of the Condair CP3 in a protective housing outside the building): drain the water supply pipe and the water filter (filter valve).
WARNING!
Danger of burning!
If steam was produced just before the unit is taken out of operation, wait before opening the unit and let the steam cylinder cool down to prevent danger of burning.
48
6.5 Overview and operating of the menu
Operating
CP3 P45 400V3
Menu Set
The operating and display unit is operated via the four keys located just below the display. The 4 status fields at the bottom of the display show the active keys the functions assigned to them.
actual key setting keys
Menu overview
CP3 P90 400V3
XXXXXXXXXXXXXXXXXXXX
2014-01-21 12:00:00
Menu Set
CP3 P90 400V3
Limitsignal :0-10V
Modbus Addr.:1
Menu Set
CP3 P90 400V3
Request B :50%
∑ Steam :45kg/h
Menu Set
Indication level
CP3 P90 400V3
Cylinder A :22h
Cylinder B :21h
Menu Mdl B
CP3 P90 400V3
StandbyDrain:Partial
Force Drain :On
Menu Mdl B
CP3 P90 400V3
Power Limit :Off
Hum.Setpoint:Off
Menu Set
Menu level
Main Menu
Info :Set
Engineering :Set
Hum.Setpoint:45%rH
Esc Set
Info
ErrorHistory:Set
Esc Set
Menu
Info
– Interrogation of unit information
– Interrogation of the malfunction list
Main Menu
User :Set
Esc Set
Main Menu
Info :Set
Hum.Setpoint:
Esc
45%rH
Set
Enter Number
Confirm with Set
Esc Set
Modbus :Set
Set
Menu
User
– Resetting the maintenance counter
– Unit settings
– Modbus settings
Menu
Engineering
The engineering level requires special knowledge and may only be served by a Condair service technician.
Main Menu
Info :Set
Esc Set
Modifying humidity setpoint
Note: this menu item appears only, if the internal P/PI controller is activated and the humidity setpoint timer is deactivated!
6.6 Interrogation functions
6.6.1 Interrogation of the operating information in the indication level
In the normal operating mode the operating and display unit is in the indication level. The indication level forms a loop that includes several pages holding operating information which can be accessed with the arrow keys. The various displays of the indication level are shown below.
Standard operating display
The appearance of the standard operating display depends on the actual operating status and the configuration of the Condair CP3. The following display are possible.
CP3 P90 400V3
2014-01-21 12:00:00
Menu Set
Standard operating display with control via the external controller
– Standby (no humidity demand) or Demand % (humidity demand present)
– Set supply air limitation in % *
* this parameter appears only if external supply air limitation is activated
CP3 P90 400V3
Lim.Range : 70-90%
Menu Set
Standard operating display with control via the internal controller
– Actual humidity in %rh
– Set nominal humidity %rh
– Set supply air limitation in % **
– Set range for supply air limitation in % **
** these parameters appear only if internal supply air limitation is activated
Info page: Settings
CP3 P90 400V3
Menu Set
– Software version (1.14)/language version (LA02)
– Set control signal range (signal Y)
– Set control signal range for the supply air limitation (signal Z). Appears only if supply air limitation is activated.
– Set Modbus address of the unit
Info page: Performance data
CP3 P90 400V3
Menu Set
– Set power limitation in %
– Actual humidity demand unit A in %rh
– Actual humidity demand unit B in %rh (if present)
– Actual steam capacity of the unit in kg/h
Info page: Steam cylinder type and operating hours
CP3 P90 400V3
– Steam cylinder type
– Operating hours of the steam cylinder A since the last reset.
– Operating hours of the steam cylinder B since the last reset.
Menu Set
Info page: Drain settings
CP3 P90 400V3
Menu Set
– Set drain factor
– Conductivity of the water
– Set draining type in standby operation
– Set time interval for forced draining
49
50
Info Page: Timer settings
CP3 P90 400V3
Hum.Setpoint:Off
Menu Set
– Actual status of On/Off timer
– Actual status of power limit timer
– Actual status of humidity setpoint timer (appears only if internal P/PI controller is activated)
6.6.2 Interrogation of unit information
Unit Status
0h
1
2
2014-01-21 12:00:00
Esc Set
11
12
13
14
15
5
6
7
3
4
8
9
10
Select the list with the unit information:
Path:
Main menu > Info > Unit Status
Press < > and < > keys, in order to select the unit information available in the list:
1 Total operating hours since the initial commissioning.
2 Actual current unit A (and B)
3 Actual status of the remote indication relay “Steam”
4 Actual status of the remote indication relay “Service”
5 Actual status of the remote indication relay “Error”
6 Actual status of the remote indication relay “Unit on”
7 Actual signal value at analog output 1 (corresponds to the actual steam capacity converted to the signal range of 0...10 V)
8 Actual signal value at analog output 2 (0...10V)
9 Calculated mean drain time in seconds of unit A (and B)
10 Current average request of unit A (and B)
11 Actual status of the maximum level sensor in the steam cylinder A
(and B)
12 Counter showing the number of times the maximum level in the steam cylinder A (and B) has been exceeded
13 Actual status of the inlet valve of unit A (and B)
14 Actual status of the drain pump of unit A (and B)
15 Actual status of the main contactor of unit A (and B)
Press the <Esc> key several times to quit the unit information list and to return to the standard operating display.
6.6.3 Interrogation of the malfunction list
The error messages generated by the last 20 malfunctions that occurred are saved in the malfunction list of the Condair CP3 and can be interrogated.
ErrorHistory
E32A HumSensor broken
2014-01-21 12:00:00
Esc Set
Select the error history list:
Path: Main menu > Info > ErrorHistory
The last error that occurred is shown with:
– running number of the error
– date and time of occurrence (version Pro only)
– error code (Warning: W..., Error: E...)
– error message
– additional info text regarding the error
Press < > and < > keys, in order to select further error messages in the list.
Press the <Esc> key several times to quit the error history list and to return to the standard operating display.
51
52
6.7 Unit settings
6.7.1 Launching the unit settings menu
Settings
Controls :Set
Select the unit settings menu:
Path: Main menu > User > Password entry: 8808 > Settings
On/Off Timer :Set
Esc Set
Press the < > and < > keys in order to select the individual settings in the settings menu.
Detailed information on the different settings are found in the following chapters.
6.7.2 Selecting the dialogue language
Settings
Controls :Set
On/Off Timer :Set
Esc Set
Select “ Language” in the settings menu, then press the <Set> key.
In the upcoming modification dialogue select the desired dialogue language. After confirmation, the unit automatically switches to the selected dialogue language.
Factory setting:
Options:
country specific divers languages
6.7.3 Control settings
Settings
Controls :Set
On/Off Timer :Set
Esc Set
Controls
Timeout :5s
Hum.Setpoint:Set
Esc Set
Select “ Controls” in the settings menu, then press the <Set> key.
The control settings appear. The settings available depend on the selected signal source and the control type. The opposite display shows the maximum number of settings available.
Description of the control settings
–
SignalSource:
Selecting the signal source.
Factory setting:
Options:
Analog
Analog, Modbus
– Timeout: Setting the timeout for control signal transmission via Modus.
Note: this setting is available only if the parameter “SignalSource” is set to “Modbus”.
Factory setting:
Setting range:
5 seconds
1 .... 600 seconds
–
Hum.Control:
Selecting the control type.
Factory setting:
Options:
Extern
Extern (external continuous controller),
24VOn/Off (external On/Off humidistat),
Int. (P) (Internal P controller)
Int. (PI) (Internal PI controller)
–
Controlsign.:
Selecting the control signal.
Note: This setting is available only if the internal or external P or PI controller is activated.
Factory setting:
Options:
0–10V
0–5V, 1–5V, 0–10V, 2–10V, 0–16V, 3.2–16V,
0–20mA, 4–20mA
–
Hum.Setpoint:
This menu item is available only if the internal P or PI controller is activated.
With the parameters in the “Hum.Setpoint” submenu you determine whether the Condair CP3 is to be controlled with a fix humidity setpoint (factory setting) or whether it is to be operated timer controlled with different humidity setpoints.
– Control with fix humidity setpoint:
Hum.Setpoint
Hum.Setpoint:50%rH
Timer deactivated, humidity setpoint adjustable (factory setting: 50 %rH, Setting range:
15...95 %rH)
Esc Set
– Timer controlled with different humidity setpoints:
Hum.Setpoint
Event 1 :06:00
If the timer is activated, up to eight switching points (events 1 - 8) with different humidity setpoints can be defined.
Event 4 :--:--
Esc Set
Event 2
Time :18:00
Each switching point is defined by a weekday or weekday range, the switching point and the humidity setpoint.
Esc Set
Configuration notes:
– the settings of an event remain active up to the next event.
– the software does not check the plausibility of the timer settings.
Therefore, make sure your settings make sense.
– the On/Off timer (see chapter 6.7.6) overrides the humidity setpoint timer.
–
P-Band:
Setting the proportional range in % for the internal P/PI controller.
Note: This setting is available only if the internal P or PI controller is activated.
Factory setting:
Setting range:
18 %
6...65 %
–
Integr.-Time:
Setting the integral time in minutes for the internal PI controller.
Note: This setting is available only if the internal PI controller is activated.
Factory setting:
Setting range:
8 minutes
1...60 minutes
53
54
–
Lim. Control:
Activating/Deactivating the supply air limitation (signal Z).
Note: This setting is available only if the external or internal P or PI controller is activated.
Factory setting:
Options:
Off
On, Off
–
Limitsignal:
Selecting the supply air limitation signal.
Note: This setting is available only if the external or internal P or PI controller and the supply air limitation are activated.
Factory setting:
Options:
0–10V
0–5V, 1–5V, 0–10V, 2–10V, 0–16V, 3.2–16V,
0–20mA, 4–20mA
–
Limit Min:
Setting the lower limit value in %rh for the supply air limitation.
Note: This setting is available only if the internal P or PI controller and the and the supply air limitation are activated.
Factory setting:
Setting range:
70 %rh
15 ... 95 %rh
–
Limit Max:
Setting the upper limit value in %rh for the supply air limitation.
Note: This setting is available only if the internal P or PI controller and the and the supply air limitation are activated.
Factory setting:
Setting range:
90 %rh
15 ... 95 %rh
6.7.4 Cylinder settings
Settings
Controls :Set
On/Off Timer :Set
Esc Set
Cylinder
Cyl. Number :644
Select “ Cylinder” in the settings menu, then press the <Set> key.
The cylinder settings appear. Press the
< > and < > keys in order to select the individual settings and press the <Set> key to call up the modification dialogue for the selected setting.
Esc Set
Description of the cylinder settings
– Cyl. Line: Selecting the cylinder type.
Factory setting:
Options:
Dispos
Dispos (Disposable cylinder A..)
Clean (Cleanable cylinder D..)
–
Cyl. Number:
Selecting the cylinder number
Factory setting:
Options:
according the installed cylinder
342, 343, 363, 444, 464, 654, 644, 664, 674
6.7.5 Setting the capacity limitation
Settings
Cylinder :Set
GFCI-Mode :On
Esc Set
Select “ Power Limit” in the settings menu, then press the <Set> key.
With the parameters in the “Power Limit” submenu you determine whether the Condair CP3 is to be operated with a fix capacity limit (factory setting) or whether it is to be operated with a timer controlled capacity limitation.
Note: set the desired capacity limitation in % of the maximum capacity of the humidifier.
– Operation with fix capacity limit:
Power Limit
Power Limit :100%
Timer deactivated, capacity limit adjustable (factory setting: 100 %, Setting range:
30...100 %).
Esc Set
– Timer controlled capacity limitation:
Power Limit
Event 1 :06:00
If the timer is activated, up to eight switching points (events 1 - 8) with different capacity limits can be defined.
Event 4 :--:--
Esc Set
Event 2
Time :18:00
Each switching point is defined by a weekday or weekday range, the switching point and the capacity limit.
Esc Set
Configuration notes:
– the settings of an event remain active up to the next event.
– the software does not check the plausibility of the timer settings.
Therefore, make sure your settings make sense.
– the On/Off timer (see chapter 6.7.6) overrides the capacity limit timer.
55
6.7.6 Configuring the On/Off timer
Settings
Power Limit :Set
Multi-Mode :Sequence
Esc Set
Select “ On/Off Timer” in the settings menu, then press the <Set> key.
With the parameters in the “On/Off Timer” submenu you determine whether or not the Condair CP3 is to be switched on and off timer controlled.
– On/Off timer deactivated:
On/Off Timer
Timer :Off
Esc Set
56
– On/Off timer activated:
On/Off Timer
Event 1 :06:00
Event 4 :--:--
Esc Set
Event 2
Time :22:00
Esc Set
If the timer is activated, up to eight switching points (events 1 - 8) with different On/
Off events can be defined.
Each switching point is defined by a weekday or weekday range, the switching point and the operating mode.
Configuration notes:
– the settings of an event remain active up to the next event.
– the software does not check the plausibility of the timer settings.
Therefore, make sure your settings make sense.
– the On/Off timer overrides all other timers.
6.7.7 Activating/Deactivating fault current relay operation
Settings
On/Off Timer :Set
Water Manag.:Set
Esc Set
Select “ GFCI-Mode” in the settings menu, then press the <Set> key.
In the upcoming modification dialogue select whether or not the Condair
CP3 is connected to a fault current relay protected mains supply.
Factory setting:
Options:
On
On (mains supply with fault current relay protection)
Off (mains supply without fault current relay protection)
6.7.8 Setting the operation mode for multiple units
Note: This setting is available only on main module A of multiple units.
Settings
GFCI-Mode :On
Remote Test :Set
Esc Set
Select “ Multi-Mode” in the settings menu, then press the <Set> key.
In the upcoming modification dialogue you determine how the demanded steam capacity is shared among the units.
Factory setting:
Options:
Sequence
Sequence (sequential load sharing)
Parallel (even load sharing)
Notes on Multi-Mode settings
– Sequence: the demand is distributed as follows: the first cylinder (Module A) takes 0 – 50% of the demand and the second cylinder (Module B) 51 – 100%. In order to ensure balanced cylinder operating hours the parameters “Seq. Rotation” and “Seq. Interval” must be set accordingly in the engineering level.
– Parallel: The demand is distributed evenly on both cylinders, i.e. with a demand of 50 % both cylinders working with 50% demand.
6.7.9 Water management settings
Select “ Water Manag.” in the settings menu, then press the <Set> key.
Settings
Multi-Mode :Sequence
Date :19.10.07
Esc Set
Water Manag.
Drain Factor:1.0
Force Drain :On
Esc Set
The water management settings menu appears.
Press the < > and < > keys in order to select the individual settings and press the <Set> key to call up the modification dialogue for the selected setting.
Force Delay :72h
Description of the water management settings
–
Conductivity:
Selecting the conductivity range of the supply water.
Factory setting:
Options:
>125 μS/cm
>125 μS/cm, <125 μS/cm
–
Drain Factor:
Setting the drain factor
Factory setting:
Setting range:
1.0
0.5...2.0
–
StandbyDrain:
Selecting the type of draining which takes place after a certain time (see following setting) of standby operation.
Factory setting:
Options:
Full
Full (complete draining) *
Partial (partial draining) **
Off (draining deactivated)
* with outdoor operation it is mandatory to use this setting.
** The cylinder is drained so far that the water does not touch the electrodes any longer.
–
StandbyDelay:
Setting the period of time in standby operation after which an automatic cylinder draining takes place.
Factory setting:
Setting range:
72 hours
1...720 hours ***
*** with outdoor operation it is mandatory to set the period of time in standby operation after which an automatic cylinder draining takes place to
1 hour.
–
Force Drain:
Activating/Deactivating the forced draining which takes place after a certain time of operation. The forced draining takes place also during steam production.
Factory setting:
Options:
Off
On (Forced draining activated)
Off (Forced draining deactivated)
–
Force Delay:
Setting the time of operation after which a forced draining takes place.
Factory setting:
Setting range:
72 hours
1...720 hours
57
58
6.7.10 Performing remote relay tests
Select “ Remote Test” in the settings menu, then press the <Set> key.
Settings
Water Manag.:Set
Time :12:00
Esc Set
Remote Test
The list with the remote relay tests appears, the first relay test is shown.
Press the < > and < > keys in order to select the further relay tests available and press the <Set> key to activate/deactivate the corresponding relay for testing.
Esc Set
6.7.11 Setting the date
Settings
Remote Test :Set
Contrast :15
Esc Set
Select “ Date” in the settings menu, then press the <Set> key. In the upcoming modification dialogue set the actual date (format:“dd.mm.yy”).
6.7.12 Setting the time
Settings
Remote Test :Set
Contrast :15
Esc Set
Select “ Time” in the settings menu, then press the <Set> key. In the upcoming modification dialogue set the actual time (format:“hh.mm”).
6.7.13 Setting the display contrast
Settings
Remote Test :Set
Contrast :15
Esc Set
Select “ Contrast” in the settings menu, then press the <Set> key.
In the upcoming modification dialogue set the desired value for the display contrast.
Factory setting:
Setting range:
15
0 (no display) ...100 (display turns black)
6.8 Modbus settings
Modbus
Remote :Set
2014-01-21 12:00:00
Esc Set
Select the Modbus menu:
Path: Main menu > User > Password entry: 8808 > Modbus
The Modbus menu appears. In the Modbus menu you can set the communication parameters for the Modbus interface on the control board
(Network) and for the Modbus interface on the power board (Remote).
Description of the Modbus settings
– Networking:
Networking
Parity :none1
2014-01-21 12:00:00
Esc Set
With the parameters in the “Networking” sub menu you can adjust the settings for the Modbus interface on the control board. The Modbus interface on the control board works with a fixed baud rate of 9600 baud and a fixed timeout of 5 seconds.
– Modbus Addr.: Modbus address of the Condair CP3.
Factory setting:
1
Setting range:
1...247
–
Parity:
Parity bit for the data transmission
Factory setting:
None1
Options:
None1, None2, Odd, Even
– Remote:
Remote
Modbus Addr.:1
With the parameters in the “Remote” sub menu you can adjust the settings for the Modbus interface on the power board. The Modbus interface on the power board works with a fixed timeout of 5 seconds.
Esc Set
–
Settings:
Operation mode of the interface.
Factory setting:
Remote
Options:
Remote, Upload
Note: the “Upload” function is intended only for the service technician of your Condair representative. In this operation mode the Modbus interface works with fixed settings.
–
Modbus Addr.:
Modbus address of the Condair CP3.
Factory setting:
1
Setting range:
1...247
– Baudrate: Baud rate for thr data transmission.
Factory setting:
9600
Options:
9600, 19200, 38400, 57600
–
Parity:
Parity bit for the data transmission
Factory setting:
None1
Options:
None1, None2, Odd, Even
59
60
7 Maintenance
7.1 Important notes on maintenance
Qualification of personnel
All maintenance work must be carried out only by
well qualified and trained personnel authorised
by the owner. It is the owner’s responsibility to verify proper qualification of the personnel.
General note
The instructions and details for maintenance work must be followed and upheld.
Only the maintenance work described in this documentation may be carried out.
Only use original Condair spare parts to replace faulty parts.
Safety
Some maintenance work requires removal of the unit cover. Please note the following:
DANGER!
Danger of electrical shock!
You may get in touch with live parts when the unit is open. Touching live parts may cause severe injury or even lethal violation.
Prevention: Before carrying out any maintenance work set the Condair CP3 out of operation as described in chapter 6.4 (switch off the unit, disconnect it from the mains and stop the water supply) and secure the unit against inadvertent power-up.
CAUTION!
The electronic components inside the humidifier are very sensitive to electrostatic dis-
charge.
Prevention: Before carrying out any maintenance work to the electrical or electronic equipment of the humidifier, appropriate
measures must be taken to protect the respective components
against damage caused by electrostatic discharge (ESD protection).
7.2 Maintenance list
To maintain operational safety the Condair CP3 steam humidifier must be maintained at regular intervals. This is differentiated between the f
irst maintenance after approx. 500 operating hours
(I), steam cylinder maintenance after the yellow LED lights (II) and annual maintenance (III).
Below you will find a summary of the work to be carried out for each of the three maintenance stages.
Components
I
Cleanable steam cylinder Type D..
X
Electrode plug
Replacement steam cyl. type A..
Drain pump
Steam cylinder receptacle
Inlet valve
Drain pipe and siphon
Steam installation
Water installation
Electrical installation
X
X
X
X
Interval
II
X
X
X
Work to be done
III
X Clean steam cylinder and electrodes and check for damage, replace if necessary. Note: The steam cylinder must be replaced after a maximum operating time of 5,000 h.
X Check to see firmly positioned (remove cover and tighten fixing screw with hexagonal head socket wrench).
Warning! This work should only be carried out by an electrician.
Remove and replace.
X Remove, disassemble and clean, replace if necessary.
X Inspect, clean if necessary.
X Remove and clean filter insert, replace if necessary.
X Inspect, clean if necessary (decalcify and rinse out).
X Inspect steam and condensate hoses for cracks and to see that they are correctly attached, replace faulty hoses.
X Inspect water hoses in the unit for cracks and to see that they are correctly attached, replace faulty hoses
Check supply pipe is tight, make tight if necessary.
Clean water filter, if available.
X Check all cables in the unit are firmly positioned and examine status of insulation.
61
62
7.3 Removing and installing parts for maintenance
7.3.1 Removal and installation of the steam cylinder
1 2
1. Use a screwdriver to undo the two screws fixing the front panel to the unit, then remove the front panel.
2. Units with steam hose connector in housing top: release the two hose clamps on the rubber sleeve using a screwdriver, then detach the rubber sleeve from the connection in the unit cover and from the steam outlet connection of the steam cylinder.
Units without steam hose connector in housing top (not shown): release the hose clamp on the steam hose using a screwdriver, then detach the steam hose from the steam outlet connection of the steam cylinder.
3 4
3. Remove all plugs from the electrodes and from the level sensor.
4. Loosen the two screws of the steam cylinder fixing device by a few turns, then push the fixing device upwards until it comes loose and remove it.
5
5. Carefully lift steam cylinder away from the cylinder receptacle, then remove it to the front.
CAUTION!
Put steam cylinder down carefully to avoid damage to the lower connection piece!
Installation of the steam cylinder follows the reverse sequence. Observe the following:
– Before installing the steam cylinder in the unit, check the O-ring of the cylinder receptacle for damage and replace if necessary.
– Moisten the O-ring of the cylinder receptacle with water (do not use grease or oil), then insert steam cylinder into the receptacle and push it down to the stop.
– Attach the electrode plugs and the level sensor plug to the respective electrode and sensor connections according to the following table.
Cable configuration red
Steam cylinder type
A363 / D363
A464 / D464
A664 / D664
A674 / D674
black brown brown red black
Sensor white black red brown
Sensor white
– Fasten steam hose on the connector in the unit cover and on steam connector of the cylinder with hose clamps.
CAUTION!
A leaky steam hose can cause damage due to moisture inside the unit.
CAUTION!
The outlet connector of the steam cylinder is made of plastic. Do not overtighten the hose clamp on the steam connector of the steam cylinder.
63
64
7.3.2 Disassembly and assembly of the cleanable steam cylinder type D...
1 3 4
2
1. Fasten electrode snap fastenings and push electrodes approx. 2 cm downwards into the steam cylinder.
2. Release clamp clips of the cylinder cover and raise cover.
3. Remove carefully electrodes by lifting upwards.
4. Remove O-rings from the electrodes.
Note: Intact O-rings can be reused.
The assembly of the cleanable steam cylinder follows the reverse sequence. Observe the follow ing:
– Before assembling the steam cylinder, check the O-ring in the steam cylinder cover and the O-rings on the electrodes for damage, and replace if necessary. Make sure to relocate O-rings correctly.
– Insert electrodes into steam cylinder cover and push them upwards until the snap fasteners engage.
– Place the cylinder cover (with mounted O-ring) in the correct position (align the two cams on the steam cylinder body with the corresponding grooves in the cylinder cover) on the cylinder body and secure cover with the fastening clips.
7.3.3 Removal and installation of the water cup and the water hoses
65
To improve accessibility for removing the water cup and the water hoses we recommend to remove the steam cylinder first (see chapter 7.3.1).
1. Release hose clamps using pliers, then disconnect all hoses from the corresponding connectors and remove the hoses.
Note: The hoses connected to the water cup may also be removed together with the water cup
(see illustration) and then disconnected from the connectors of the water cup outside the unit.
2. Carefully pull fixing clip of the water cup to the front, then push water cup down from the holding device and remove it to the front.
The installation of the water cup and the water hoses follows the reverse sequence. Before fixing the water hoses to the connector using the hose clamps, align the hoses in a way that they are not twisted.
66
7.3.4 Removal and installation of the drain pump
2
4
2
1
3
The steam cylinder does not need to be removed when removing the drain pump.
1. Detach electric cables (polarity of the cables must not be observed).
2. Release hose clamps and remove the hoses from the connectors.
3. Pull the drain pump off the holding device.
4. Separate the electric motor from the pump body: release the lock on the bayonet catch, then counter-rotate the electric motor and the pump body.
The assembly and the installation of the drain pump follows the reverse sequence. Before assembling the pump, check O-ring for damage and replace if necessary. Then, place the O-ring on the centering collar and moisten the O-ring with water.
7.3.5 Removal and installation of the inlet valve
1
3
2
3
The steam cylinder does not need to be removed when removing the inlet valve.
1. Detach electric cables (polarity of the cables must not be observed).
2. Release hose clamp and remove the hose from the connector.
3. Unlock union nut of the water pipe and remove water pipe.
4. Pull the inlet valve off the holding device.
The installation of the inlet valve follows the reverse sequence. The union nut of the water pipe must be tightened by hand only.
7.4 Notes on cleaning the unit components
Unit component
Steam cylinder cover
Steam cylinder body
Cylinder strainer
What to clean and how to clean
• Knock off or brush away any limescale as much as possible (do not use a wire brush).
If the parts are heavily calcified, place them in an 8% formic acid solution (
observe safety notes in chap-
ter 7.5), until the limescale comes off.
• Finally wash parts in a lukewarm soap solution and rinse well with tap water.
67
Heating electrodes
Water hoses
• Immerse the heating electrodes (up to 2 cm below the snap fastening) in a container with 8-percent formic acid
( observe safety notes in chapter 7.5). Allow the acid to take effect until the limescale has dissolved.
Note: The heating elements do not have to be entirely free from scale.
• Finally rinse the heating electrodes well with tap water and let them dry.
CAUTION: On no account remove limescale from the heating electrodes using tools (screw driver, scraper, etc.) or by striking. This could damage the heating elements.
• Remove any limescale by slightly knocking on the tubes using a rubber hammer. Then, rinse the tubes well with hot tap water.
Inlet valve
Strainer insert
• Remove strainer insert with pointed pliers. Use a brush
(do not use a wire brush) to remove any limescale.
• Wash strainer insert with a lukewarm soap solution, then rinse well with tap water.
Let the inlet valve dry before reinstallation!
68
Unit component
Drain pump
O-ring
What to clean and how to clean
• Use a brush to remove any limscale from the pump housing and the pump wheel (do not use a wire brush).
• Then, wipe pump wheel with a damp cloth. Wash the pump housing with a lukewarm soap solution and rinse well with tap water. pump wheel
Cylinder receptacle in the unit
• Remove any limscale from the cylinder receptacle and its connectors using a brush (do not use a wire brush).
• Wash the cylinder receptacle with a lukewarm soap solution and rinse well with tap water.
Water cup
• Remove any limscale from the water cup and its connectors using a brush (do not use a wire brush).
• Wash the water cup with a lukewarm soap solution and rinse well with tap water.
Interior of the unit
(water side only)
Wipe the interior of the unit with a damp cloth without using any cleaning agent.
CAUTION! Take care that the electrical connections and the electronic components remain dry.
7.5 Notes on cleaning agents
Only use cleaning agents stated in the table above. The use of disinfectants is only permitted if they do not leave any toxic residues. In any case the parts must be thoroughly rinsed with water after cleaning.
WARNING!
Formic acid is indeed harmless to the skin, but it attacks the mucous membranes. Therefore prevent your eyes and respiratory tracts from getting in touch with the acid and its vapours (wear goggles and work in a well ventilated room or outside).
CAUTION!
Do not use any solvents, aromatized or halogenized hydrocarbons or other aggressive
substances as they may cause damage to the components of the unit.
It is mandatory to observe and comply with the information and instructions regarding cleaning agents.
Observe in particular: all information relating to the protection of personnel, environmental protection and restrictions regarding usage.
69
7.6 Resetting the maintenance indication
After completing maintenance work, the maintenance indication (yellow LED lights) must be reset as follows:
Maintenance
Cyl. A Reset:Set
Select the maintenance menu:
Path: Main menu > User > Password entry: 8808 >
2014-01-21 12:00:00
Esc Set
Select “ Cyl. A Reset” (or “Cyl. B Reset”) in the maintenance menu, then press the <Set> key.
Cyl. A Reset
Are you sure?
The reset dialogue shows up in the display. Press the <Yes> key to reset the maintenance counter.
Note: Press the <No> key if you wish to abort the reset procedure. is very dangerous!
Esc No Yes Set
To return to the standard operating display press the <Esc> key several times.
70
8 Troubleshooting
Important! Most operational malfunctions are not caused by faulty equipment but rather by improper installation or disregarding of planning guidelines. Therefore, a complete fault diagnosis always involves a thorough examination of the entire system. Often, the steam hose connection has not been properly executed, or the fault lies with the humidity control system.
8.1 Malfunction list
8.1.1 System faults
LED
Warning
Display
CP3 Card missing
(Test run possible)
–––
–––
–––
–––
–––
Warning
W1: CP3-Card Missing
–––
–––
–––
–––
–––
Extension unit missing
Warning
W6: Extended Missing
–––
–––
–––
–––
–––
–––
LED
Error
Display
CP3 Card missing
Cause Remedy
red lights
Error
E1: CP-Card Missing
CP3 Card is empty
red lights
Error
E2: CP-Card Empty red lights
CP3 Card is defective
Error
E3: CP-Card Invalid
CP3 Card is incompatible
red lights
Error
E4: CP-Card incompat red lights
Module B missing
red lights
Error
E5: Modul B Missing
Main unit missing
Error
E6: Main Missing
No CP3 Card installed on the control board.
No data stored on the CP3 Card.
Invalid data stored on the CP3 Card.
The installed CP3 Card is not compatible with the hardware of the unit or with the basic settings of the control electronics.
Module B not correctly connected or defective.
Install CP3 Card or start test run.
Install new CP3 Card.
Install new CP3 Card.
Install correct CP3 Card. Let your Condair service technician adjust the basic settings.
Check module B and both connecting cables.
No communication between main unit and extension unit.
Check/connect bus cable.
Main or extension unit not switched on.
Switch on main unit and/or extension unit.
Extension unit is in error status
red lights
Error
E7: Extended Error
The display of the main unit indicates that the extension unit is in error status.
The type of error is shown on the display of the extension unit.
Take corresponding measures according to the indicated error type.
Extension unit is not compatible
red lights
Error
E8: Extend.Incompat.
Wrong hardware settings
red lights
Error
E9: Illegal Settings
The CP3 Card of the main unit is not compatible with the one of the extension unit.
Install correct CP3 Cards into the units.
False test run parameters.
Let your Condair service technician adjust the test run parameters (heating voltage,
Cylinder-No.).
LED
–––
–––
Warning
Display
–––
–––
–––
On/Off timer active
Warning
W12: Timer Disable
LED
red lights
Error
Display
Hardware fault
Error
E10: Flash R/W Fault
Error
E11: Clock R/W Fault
Cause
Control board defective.
Backup battery on control board
discharged.
––– –––
Remedy
Replace control board.
Let have the backup battery be replaced
(see chapter 8.4).
The system is deactivated via the On/Off-
Timer.
None. If necessary adjust On/Off timer settings.
71
8.1.2 Unit faults
LED
External safety chain is open
red and green flash
–––
Warning
Display
Warning
W20A: Safety loop open
Max. filling level of steam cylinder reached
Warning
W21A: Cyl.Max.Level
Permissible filling time exceeded
(20 minutes)
–––
Warning
W22A: Max. Filltime
LED
Error
Display
Cause Remedy
––– ––– Ventilation interlock open.
Air flow monitor triggered.
Safety humidistat triggered.
If applicable, check/turn on ventilation system.
Check ventilator/filter of the ventilation system.
Wait. If applicable, check safety humidistat
Max. filling level of steam cylinder reached but no heating current
red lights
Error
E21A: Cyl.Max.&NoCurr
Water conductivity too low (after initial operation).
Wait until the mineral content of the cylinder has increased
Water conductivity too low for type of steam cylinder.
Phase failure heating voltage.
Select correct steam cylinder type.
Check service switch in the mains supply line and switch on if applicable. Check mains fuse(s) and replace if applicable.
Permissible filling time exceeded
(more than 4 hours)
red lights
Error
E22A: Max. Filltime
Water supply obstructed/shut-off valve closed/water pressure too low.
Inspect water supply (filter, water piping, etc.), check/open shut-off valve, check water pressure.
Inlet valve blocked or defective.
Inspect strainer insert in the inlet valve, if applicable clean strainer insert or replace inlet valve.
Excessive back pressure in the steam line (duct pressure too high, steam line too long or kinked), causing water loss via filling cup.
Check duct pressure, inspect steam installation. If applicable install pressure compensation kit (see options).
Leakage in the water system.
Inspect water system and seal if necessary.
72
LED
Warning
Display
No electrode current for more than 20 minutes
–––
Warning
W23A: No Current
Electrode current in relation to the steam demand too high
–––
Warning
W24A: Over Current
Max. admissible electrode
–––
–––
current exceeded
Warning
W25A: Excess Current
–––
LED
Error
Display
No electrode current for more than 4 hours
red lights
Error
E23A: No Current
Cause
Phase failure heating voltage.
Remedy
Inspect/turn on service switch of the mains supply line. Inspect the fuses of the mains supply, replace if necessary.
Water supply obstructed/shut-off valve closed/water pressure too low.
Inspect water supply (filter, water piping, etc.), check/open shut-off valve, check water pressure.
Inlet valve blocked or defective.
Inspect strainer insert of the inlet valve, if applicable clean strainer insert or replace inlet valve.
Excessive back pressure in the steam line (duct pressure too high, steam line too long or kinked), causing water loss via filling cup.
Check duct pressure, inspect steam installation. If applicable install pressure compensation kit (see options).
Leakage in the water system.
Inspect water system and seal if necessary.
Electrode current in relation to the steam demand too high
red lights
Error
E24A: Over Current
Humidity demand has decreased too fast. Automatic adaptation of the operating point.
Drain pump defective.
Inspect drain pump, replace if necessary.
Drain in steam cylinder blocked.
Water conductivity too high for this type of steam cylinder.
Clean/replace steam cylinder.
Select correct steam cylinder type.
red lights
Max. admissible electrode current exceeded
Error
E25A: Excess Current
Drain pump defective.
Drain in steam cylinder blocked.
Water conductivity too high for this type of steam cylinder.
Inspect drain pump, replace if necessary.
Clean/replace steam cylinder.
Select correct steam cylinder type.
red lights
Main contactor jammed
Error
E26A: Req.Off Current
Main contactor jammed in activated position.
Inspect main contactor, replace if necessary.
–––
Foam detection
Warning
W27A: Foam
Foam detection (4 automatic drainings within 24 hours)
red lights
Error
E27A: Foam
Foaming in steam cylinder.
Drain steam cylinder via drain key (several times, if necessary). Check quality of the supply water.
Steam cylinder needs service
yellow lights
Warning
W28A: Cyl. Maintenance
Service interval for steam cylinder exceeded
red and yellow flash
Error
E28A: Cyl. Maintenance
Mineral deposits and/or electrodes spent. Steam cylinder Type A: replace
Steam cylinder Type D: clean
Important: After replacement or cleaning of the steam cylinder, reset the maintenance counter (see chapter 7.6).
Steam cylinder needs service Max. operating hours of the steam cylinder reached
yellow lights
Warning
W29A: Cyl. Maintenance red and yellow flash
Error
E29A: Cyl. Maintenance
Maximum operating hours of the steam cylinder reached.
Steam cylinder Type A: replace
Steam cylinder Type D: clean
Important: After replacement or cleaning of the steam cylinder, reset the maintenance counter (see chapter 7.6).
LED
Warning
Display
Humidity sensor signal (signal Y) missing
–––
Warning
W32A: Ctrl.Sens.Broken
Signal of humidity limitation sensor (signal Z) missing
–––
Warning
W33A: Lim.-Sens.def.
LED
Error
Display
Humidity sensor signal (signal Y) missing for more than 1 minute
red lights
Error
E32A: Ctrl.Sens.Broken
Cause
No sensor signal present at signal input
(Signal Y).
Signal of humidity limitation sensor (signal Z) missing for more than 1 minute
red lights
Error
E33A: Lim.Sens.Broken
No sensor signal present at signal input
(signal Y).
Module A (B) locked via Modbus
–––
Warning
W34A: Modbus disable
––– Module A (B) locked because the corresponding Modbus register is deactivated.
Remedy
Check humidity sensor (signal Y) , replace if necessary. Inspect wiring.
Check humidity sensor (signal Y) , replace if necessary. Inspect wiring.
Activate the corresponding Modbus register.
––– ––– red lights
Modbus Timeout (5 s)
Error
E35A: Modbus Timeout
No actual demand or humidity signal received via Modbus.
Send actual demand or humidity signal.
–––
Standby draining of steam cylinder active
Warning
W36A: Standby Drain
–––
Forced draining of steam cylinder active
Warning
E37A: Forced Drain
–––
–––
–––
–––
Automatic standby draining of steam cylinder active.
No measures must be taken.
Forced draining of steam cylinder active. No measures must be taken.
8.2 Resetting the error indication (red LED lights)
To reset the error indication:
Disconnect the steam air humidifier from the mains. Wait approx. 5 seconds, then reconnect the unit to the mains.
Note: If the fault has not been eliminated, the error indication reappears after a short while.
73
8.3 Notes on fault elimination
DANGER!
For the elimination of faults set the steam humidifier out of operation as described in chapter 6.4,
separate the unit from the mains and secure it against inadvertent power-up.
The elimination of faults must be carried out by qualified and well trained professionals only.
Malfunctions relating to the electrical installation (e.g. replacement of the backup batterie, replacement of fuses, etc.) must be repaired by authorized personnel or by your Condair representative’s service technician only.
Repair work and the replacement of faulty components must be carried out by your Condair representative’s service technician only!
74
8.4 Replacing the backup battery on the control board of the
Condair CP3 Pro
1.
Set the Condair CP3 out of operation as described in chapter 6.4, disconnect it from the
mains and secure the unit against inadvertent power-up.
2. Undo the two screws of the front cover, then remove the front cover.
CAUTION!
The electronic components inside the humidifier are very sensitive to electrostatic discharge.
Before carrying out the next step, appropriate
measures must be taken to protect the electronic
components against damage caused by electrostatic discharge (ESD protection).
3. Carefully lift-off the display and control unit from the housing frame, swivel it 90° to the left, then fix it to the unit frame again.
4. Undo the fastening screw of the control board, then carefully pull-off the control board from the control unit assembly.
5. Replace the backup battery (CR2032, Lithium 3V).
6. Reassemble the unit in reverse order.
7. If necessary set date and time (see chapter 6.7.11 and 6.7.12).
WARNING!
Environmental hazard!
The old battery must be returned to an authorised collecting point for correct disposal/ recycling in accordance with local regulations. In no case the old battery must be disposed of in the domestic waste or into the environment.
9 Taking out of service/Disposal
9.1 Taking out of service
If the Condair CP3 must be replaced or if the humidification system is not needed any more, proceed as follows:
1. Take the unit out of operation as described in chapter 6.4.
2. Have the unit (and all other system components, if necessary) unmounted by a qualified service technician.
75
9.2 Disposal/Recycling
Components not used any more must not be disposed of in the domestic waste. Please dispose of the unit or the individual components in accordance with local regulations at the authorised collecting point.
If you have any questions, please contact the responsible authority or your local
Condair representative.
Thank you for your contribution to environmental protection.
76
10 Product specifications
10.1 Technical data
Heating voltage 230V/1~/50..60Hz
Unit model:
Steam capacity in kg/h:
Max. power consumption in kW
Heating voltage 230V/3~/50..60Hz
Unit model:
Steam capacity in kg/h:
Max. power consumption in kW
Heating voltage 400V/3~/50..60Hz
Unit model:
Steam capacity in kg/h:
Max. power consumption in kW
Control voltage
Operating conditions
Admissible water pressure
Water quality
Admissible water temperature
Admissible ambient temperature
Admissible ambient humidity
Admissible duct air pressure
Type of protection
Conformity
Dimensions/Weights
Housing (WxHxD) in mm
Net weight in kg
Operating weight in kg
Equipment/options
Steam cylinder type
(Type A.. standard equipment)
Steam hose connector
Steam hose connector
with condensate trap
Condensate trap
Cable gland
Overpressure set
Remote operating and fault indication
Terminals heating voltage
Mounting profile
Internal control voltage with terminals
Transformer 400V/230V
Housing front cover, stainless steel
Accessories
Steam distribution pipe
Steam distribution system OptiSorp
Fan unit
Steam hose / meter
Condensate hose / meter
456x620x280 1
559x667x350
21
26
A3.../D3...
1
A4.../D4...
A6.../D6...
SC22 1
SC60
SC80
SCCT22 1
SCCT60
SCCT80
CT22
CT60
CT80
PG 1
OPS 1
RFI 1
M-THV 1
L-THV
MP 1
M-CVI 1
L-CVI
M-Trafo 1
L-Trafo
M-INOX 1
L-INOX
41-...
1
61-...
81-...
System 1 1
System 2
System 3
System 4
FAN3S CP ... M 1
FAN3S CP ... L
DS22 1
DS60
DS80
KS10 1
Basic Pro
5...8
5...8
3.8...6.0
Basic Pro Basic Pro Basic Pro Basic Pro Basic Pro
5...8
5...8
3.8...6.0
9...15
9...15
6.8...11.3
16...21
16...21
12.0...15.8
22...30
22...30
44/50/60
44/50/60
Pro
75/90
75/90
16.5...22.5
33.0/37.6/45.0
56.5/76.5
Pro
100/120
100/120
75.0/90.0
Basic Pro Basic Pro Basic Pro Basic Pro Basic Pro
5...8
5...8
3.8...6.0
9...15
9...15
6.8...11.3
16...25
16...25
12.0...18.8
1 x 230V / 50-60 Hz
26...45
26...45
19.5...33.8
Pro Pro
52/60/70/80/90 105/120/135 152/160/180
52/60/70/80/90 105/120/135 152/160/180
39.0...67.5
78.8...101.3
2 x 230V / 50-60 Hz
114.0...135.0
1...10 bar
Untreated drinking water with a conductivity of 125...1250 uS/cm
1...40 °C
1...40 °C max. 75% rh (non-condensing)
-0.8 kPa...1.5 kPa; overpressure kit (option) up to 10.0 kPa
IP 20
CE, VDE, GOST
1
21
26
1
S
1
S
1
S
S
1
1
1
1
1
1
1
1
1
1
21
32
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
21
32
1
S
1
S
S
S
1
1
1
1
1
1
1
1
1
1
1
28
65
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
28
65
1
S
S
1
1
S
1
S
1
1
1
1
1
1
1
1
1
28
65
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1 2 2
28 2x 28 2x 28
65 2X 65 2X 65
1
S
S
1
1
S
1
S
1
1
1
1
1
1
1
1
2
2
2
1
2
1
2
1
1
1
2
2
1
2
2
2
2
S
S
1
2
S
2
S
1
1
2
2
1
2
2
2
3
3x 28
3X 65
3
S
S
3
3
S
3
S
2
2
3
3
1
3
3
3
4
4x 28
4x 65
4
S
2
4
S
4
2
4
S
4
S
4
1
4
4
4
10.2 Unit dimensions
Condair CP3 5...15 (dimensions in mm)
150
178
456
ø22.5 (5...8 kg/h)
ø30.0 (9...15 kg/h)
228
77
280
34
93
28
105
40
71
180 90
78
Condair CP3 16...45 (Dimensions in mm)
175 228
559
ø45
284
350
34
93 28
105
40
71
216 144
© Condair Ltd., Printed in Switzerland
Technical modifications reserved
CONSULTING, SALES AND SERVICE:
Reg.No. 40002-2
Manufacturer:
Condair Ltd.
Member of the Walter Meier Group
Talstrasse 35-37, 8808 Pfäffikon, Switzerland
Ph. +41 55 416 61 11, Fax +41 55 416 62 62 [email protected], www.condair.com