GE Vernova MM300 Quick Start Guide
Below you will find brief information for MM300. The MM300 is a modular motor protection and control system for low-voltage applications, offering flexible protection, control, and communication options. It features a small footprint for MCC, integrated pushbuttons/LEDs, DIN/panel mounting, and optional control panels. It supports multiple communication protocols and Automation FlexLogic for complex starter control.
Advertisement
Advertisement
MM300 Motor Management System Quick Start Guide MM300 Revision: 1.7x Manual P/N: 1601-9022-AE Manual Order Code: GEK-113336N E83849 LISTED IND.CONT. EQ. 52TL *1601-9022-AE* © 2025 GE Vernova. All rights reserved. The MM300 Motor Management System QuickStart Guide for revision 1.7x. MM300 Motor Management System, EnerVista, EnerVista Launchpad, and EnerVista MM300 Setup are registered trademarks of GE Vernova. The contents of this manual are the property of GE Vernova. This documentation is furnished on license and may not be reproduced in whole or in part without the permission of GE Vernova. The content of this manual is for informational use only and is subject to change without notice. Part number: 1601-9022-AE (May 2018) Storage Store the unit indoors in a cool, dry place. If possible, store in the original packaging. Follow the storage temperature range outlined in the Specifications. To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized state once per year, for one hour continuously. Warranty For products shipped as of 1 October 2013, GE Vernova warrants most of its manufactured products for 10 years. For warranty details including any limitations and disclaimers, see our Terms and Conditions at https://www.gevernova.com/grid-solutions/ multilin/warranty.htm For products shipped before 1 October 2013, the standard 24-month warranty applies. Repairs The firmware and software can be upgraded without return of the device to the factory. For issues not solved by troubleshooting, the process to return the device to the factory for repair is as follows: • Contact a GE Vernova Grid Solutions Technical Support Center. Contact information is found in the first chapter. • Obtain a Return Materials Authorization (RMA) number from the Technical Support Center. • Verify that the RMA and Commercial Invoice received have the correct information. • Tightly pack the unit in a box with bubble wrap, foam material, or styrofoam inserts or packaging peanuts to cushion the item(s). You may also use double boxing whereby you place the box in a larger box that contains at least 5 cm of cushioning material. • Ship the unit by courier or freight forwarder, along with the Commercial Invoice and RMA, to the factory. Customers are responsible for shipping costs to the factory, regardless of whether the unit is under warranty. • Fax a copy of the shipping information to the GE Vernova Grid Solutions service department. Use the detailed return procedure outlined at https://www.gevernova.com/grid-solutions/multilin/support/ret_proc.htm The current warranty and return information are outlined at https://www.gevernova.com/grid-solutions/multilin/warranty.htm This product cannot be disposed of as unsorted municipal waste in the European Union. For proper recycling return this product to your supplier or a designated collection point. For more information go to www.recyclethis.info. TABLE OF CONTENTS Table of Contents OVERVIEW Cautions and Warnings ....................................................................................................................... 3 Safety words and definitions......................................................................................................................3 General Safety Precautions - MM300.....................................................................................................3 For Further Assistance.......................................................................................................................... 4 INSTALLATION Mechanical installation ........................................................................................................................ 5 Dimensions..........................................................................................................................................................6 Product identification .....................................................................................................................................6 Mounting ..............................................................................................................................................................7 Electrical installation ...........................................................................................................................10 Module and terminal identification....................................................................................................... 11 Full-voltage non-reversing starter ........................................................................................................ 12 RS485 connections ....................................................................................................................................... 13 Phase current inputs (IO_A module) ..................................................................................................... 14 Phase voltage inputs (IO_B module)..................................................................................................... 17 Type IO_C module connections.............................................................................................................. 18 Type IO_D module connections ............................................................................................................. 19 Type IO_E module connections.............................................................................................................. 20 RTD sensor connections (IO_G module).............................................................................................. 21 Maintenance ...........................................................................................................................................22 In-service maintenance ............................................................................................................................. 22 Out-of-service maintenance.................................................................................................................... 22 Unscheduled maintenance (system interruption) ......................................................................... 22 Interfacing with the MM300.............................................................................................................23 MM300 graphical display pages............................................................................................................ 23 Introduction to the graphical control panel ..................................................................................... 25 Basic control panel ....................................................................................................................................... 30 EnerVista MM300 Setup Software.................................................................................................31 Software requirements............................................................................................................................... 31 Troubleshooting the USB driver.............................................................................................................. 32 Installing the EnerVista MM300 Setup software............................................................................. 35 Upgrading the software............................................................................................................................. 38 Connecting EnerVista MM300 Setup to the relay .................................................................39 Configuring serial communications ..................................................................................................... 39 Using the Quick Connect feature........................................................................................................... 40 Connecting to the relay.............................................................................................................................. 40 Working with setpoints and setpoint files .................................................................................42 Engaging a device......................................................................................................................................... 42 Entering setpoints ......................................................................................................................................... 42 File support....................................................................................................................................................... 43 Using setpoints files ..................................................................................................................................... 44 Downloading and saving setpoints files............................................................................................. 44 Adding setpoints files to the environment......................................................................................... 45 Loading setpoints from a file ................................................................................................................... 45 Uninstalling files and clearing data ...................................................................................................... 46 Upgrading relay firmware ................................................................................................................47 Loading new relay firmware.................................................................................................................... 47 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE i TABLE OF CONTENTS ACTUAL VALUES Actual values overview ......................................................................................................................51 SETPOINTS Understanding setpoints...................................................................................................................53 Configuration setpoints .....................................................................................................................54 Motor setpoints...............................................................................................................................................54 Current and voltage transformers.........................................................................................................58 PROTECTION ELEMENTS Thermal protection ..............................................................................................................................61 Overload curve................................................................................................................................................62 COMMUNICATIONS Communications interfaces ............................................................................................................65 SPECIFICATIONS Protection specifications...................................................................................................................67 User interface specifications...........................................................................................................69 Metering and monitoring specifications....................................................................................69 Control specifications .........................................................................................................................70 Inputs specifications ...........................................................................................................................70 Outputs specifications........................................................................................................................71 Power supply specifications............................................................................................................72 Communications specifications ....................................................................................................72 Testing and certification....................................................................................................................73 Physical specifications.......................................................................................................................74 Environmental specifications..........................................................................................................74 MM300 ORDER CODES Example of an MM300 order code ...............................................................................................76 ii MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE GE Grid Solutions MM300 Motor Management System Chapter 1: Overview Overview The MM300 is a modular motor protection and control system designed specifically for low-voltage motor applications. The MM300 provides the following key benefits. • Flexible protection, control, and communication options to suit any low-voltage motor application. • Small footprint designed specifically for IEC and NEMA MCC applications. • Modular design reduces the number of spare components for maintenance and testing. • Integrated pushbuttons and LED indicators reduce external components and wiring. • DIN rail and Panel Mounting. • Multiple, simultaneous communication protocols allows simple integration into monitoring and control systems. • Optional basic control panel or graphical control panel interface provides local control and access to system information. • Automation FlexLogic™ for applications requiring more complex starter control, or multi-starter scenarios with interlocking or programmable logic control. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 1 CHAPTER 1: OVERVIEW 52 BUS Control PT Power Fuse Control fuse 27X Six inputs and two outputs (standard) Direct voltage inputs (690 V AC maximum) Optional three-phase voltage card 27 59 47 METERING V, A, W, var, VA, PF, Hz Contactor 51R 49 37 66 46 Phase CT 3 50G 51G Ambient air Ground CT 1 Stator RTDs 49 Bearing RTDs RS485 - Modbus RTU Ethernet - Modbus TCP/IP Profibus/DeviceNet MM300 MOTOR MANAGEMENT SYSTEM ? ? Optional RTD card LOAD MOTOR Options: Four form-C contact outputs (max 4 cards) Three RTDs - 100 ohm Platinum (max 2 cards) 38 Thermistor Options: Three-phase voltage card (max 1 card) Six inputs & two form-A outputs (max 5 cards) Temperature Expansion module, two cards per module, maximum of two modules ? ? RTD 853739A2.CDR Table 1-1: MM300 protection functions 2 ANSI device Description 27X Undervoltage, auxiliary input 27 Undervoltage, three-phase 37 Undercurrent and underpower 38 Bearing temperature RTD 46 Current unbalance 47 Voltage phase reversal 49 Thermal overload 50G Ground instantaneous overcurrent 51G Ground time overcurrent 51R Locked/stalled rotor, mechanical jam 59 Overvoltage, three-phase 66 Starts per hour and time between starts MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 1: OVERVIEW CAUTIONS AND WARNINGS Cautions and Warnings Before attempting to install or use the device, review all safety indicators in this document to help prevent injury, equipment damage, or downtime. Safety words and definitions The following symbols used in this document indicate the following conditions Indicates a hazardous situation which, if not avoided, will result in death or serious injury. DANGER: Indicates a hazardous situation which, if not avoided, could result in death or serious injury. IMPORTANT: Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. CAUTION: Indicates practices not related to personal injury. NOTE: NOTE General Safety Precautions - MM300 CAUTION: Failure to observe and follow the instructions provided in the equipment manual(s) could cause irreversible damage to the equipment and could lead to property damage, personal injury and/or death. Before attempting to use the equipment, it is important that all danger and caution indicators are reviewed. If the equipment is used in a manner not specified by the manufacturer or functions abnormally, proceed with caution. Otherwise, the protection provided by the equipment may be impaired and can result in Impaired operation and injury. Caution: Hazardous voltages can cause shock, burns or death. Installation/service personnel must be familiar with general device test practices, electrical awareness and safety precautions must be followed. Before performing visual inspections, tests, or periodic maintenance on this device or associated circuits, isolate or disconnect all hazardous live circuits and sources of electric power. Failure to shut equipment off prior to removing the power connections could expose you to dangerous voltages causing injury or death. All recommended equipment that should be grounded and must have a reliable and un-compromised grounding path for safety purposes, protection against electromagnetic interference and proper device operation. Equipment grounds should be bonded together and connected to the facility’s main ground system for primary power. Keep all ground leads as short as possible. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 3 FOR FURTHER ASSISTANCE CHAPTER 1: OVERVIEW At all times, equipment ground terminal must be grounded during device operation and service. In addition to the safety precautions mentioned all electrical connections made must respect the applicable local jurisdiction electrical code. Before working on CTs, they must be short-circuited. For Further Assistance For product support, contact the information and call center as follows: GE Grid Solutions 650 Markland Street Markham, Ontario Canada L6C 0M1 Worldwide telephone: +1 905 927 7070 Europe/Middle East/Africa telephone: +34 94 485 88 54 North America toll-free: 1 800 547 8629 Fax: +1 905 927 5098 Worldwide e-mail: [email protected] Europe e-mail: [email protected] Website: http://www.gegridsolutions.com/multilin 4 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE GE Grid Solutions MM300 Motor Management System Chapter 2: Installation Installation Mechanical installation This section describes the mechanical installation of the MM300 system, including dimensions for mounting and information on module withdrawal and insertion. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 5 MECHANICAL INSTALLATION CHAPTER 2: INSTALLATION Dimensions The MM300 is packaged in a modular arrangement. The dimensions of the MM300 are shown below. Additional dimensions for mounting and panel cutouts are shown in the following sections. Figure 2-1: MM300 dimensions PANEL 6.071” (154,15 mm) 3.746” (95,15 mm) 4.059” (103,09 mm) 0.565” (14,35 mm) 5.228” (132,78 mm) 5.550” (140,97 mm) 853724A1.CDR Product identification The product identification label is located on the side panel of the MM300. This label indicates the product model, serial number, firmware revision, and date of manufacture. Figure 2-2: MM300 label 2.425” (61.6 mm) Model: Serial Number: Firmware: 0.525” (13.3 mm) 6 Mfg. Date: 853748A1.CDR MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 2: INSTALLATION MECHANICAL INSTALLATION Mounting The MM300 can be mounted three ways: standard panel mount, DIN rail mount, and screw mount for high vibration environments. The standard panel mount and cutout dimensions are illustrated below. Figure 2-3: Base Unit standard panel mounting and cutout dimensions #4 - 40x3/8in SELF-TAP PAN HD PHILIPS QTY: 6 (SUPPLIED); GE PART NO. 1402-0017 TIGHTENING TORQUE: 8 lb-in INSTALL RELAY FROM FRONT OF THE PANEL REAR OF PANEL CUTOUT AND MOUNTING HOLES 5.580” (141,73 mm) 0.105” (2,67 mm) 0.138” (3,49 mm) 1.750” (44,45 mm) 3.775” (95,89 mm) 3.500” (88,90 mm) 5.790” (147,07 mm) 0.130” (QTY: 6) (3,30 mm) 853725A1.CDR The DIN rail mounting is illustrated below. The DIN rail conforms to EN 50022. CAUTION: To avoid the potential for personal injury due to fire hazards, ensure the unit is mounted in a safe location and/or within an appropriate enclosure. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 7 MECHANICAL INSTALLATION CHAPTER 2: INSTALLATION Figure 2-4: Basic Control Panel mounting and cutout dimensions #4-40X3/8in SELF TAP PAN HD PHILIPS QTY: 8; (SUPPLIED); GE PART# 1402-0017 TIGHTENING TORQUE: 7 lb-in 2.635" [66,93mm] 2.515" [63,88mm] 1.500" [38,10mm] . 2.635" [66,93mm] 2.515" 1.500" [63,88mm] [38,10mm] Ø.130" [3,30mm] TypX8 853825A1.cdr Figure 2-5: DIN rail mounting - Base and Expansion units SNAP-IN THE DIN CLIPS (QTY: 4) FOR DIN RAIL MOUNTING 0.30” (7,6 mm) 1.38” (35,1 mm) DIN 3 RAIL 853726A1.CDR 8 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 2: INSTALLATION MECHANICAL INSTALLATION Screw mounts for high vibration environments are illustrated below. Figure 2-6: Base Unit screw mounting MEETS VIBRATION REQUIREMENT OF IEC 60255 SEC 21.1, 21.2, & 21.3 2.250” (57,15 mm) #6 -32 THREADED HOLE QTY: 2 4.100” (104,14 mm) #6-32X1/2FT FLATHEAD PHIL ZINC QTY:2;TIGHTENING TORQUE:10lb.in.C 853727A2.CDR Figure 2-7: Expansion Unit screw mounting 0.356” [9.03 mm] 2.285” [58.04 mm] 0.672” [17.06 mm] EXPANSION UNIT OUTLINE #6-32 THREADED HOLE QTY: 2 #6-32X1/2 FT FLAT HEAD PHIL ZINC QTY: 2; TIGHTENING TORQUE: 10 lb. in. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 1.500” [38.10 mm] 853755A2.cdr 9 ELECTRICAL INSTALLATION CHAPTER 2: INSTALLATION Electrical installation This section describes the electrical installation of the MM300 system. An overview of the MM300 terminal connections is shown below. MM300 is not to be used in any way other than described in this manual. CAUTION: Figure 2-8: MM300 terminal connection overview Profibus or DeviceNet Optional fieldbus protocols Three-phase and residual ground CT inputs RS485 communications and thermistor input Expansion module to base unit with a single connector Optional three-phase voltage module RTD Module with three RTD inputs Switched power supply allows AC or DC control voltage Optional TCP/IP Ethernet I/O card includes: Core-balance ground CT input Expansion module allows additional digital inputs/outputs, RTDs, or voltage inputs • two contactor outputs (form-A) • six programmable inputs • single-phase VT input (60 to 300 V AC) 853740A2.CDR The MM300 can contain up to eight modules. The first four modules (slots A through D) comprise the base unit, and the next four modules (slots E through H) comprise the optional expanded unit. Table 2-1: Module slot position Base Unit Expansion Modules Slot Module types A Power supply module (High or Low) B CPU module with communications (1 of 3 Comm Types) C IO_C or IO_E module D IO_A module E IO_B or IO_C or IO_E or IO_D or IO_G module F IO_C or IO_E or IO_D or IO_G module G IO_C or IO_E or IO_D or IO_G module H IO_C or IO_E or IO_D or IO_G module The following figure shows a typical module arrangement for an expanded unit. CAUTION: Use gauge size appropriate for the voltage and current draw of the device. Table 2-2: Gauge Sizes CPU Card: Themistor, RS485 and Fieldbus 16 AWG (3.50mm pitch terminals)1 PSU / CBCT /IO_C / IO_E / IO_D / IO_G 12 AWG (5.00mm pitch terminals)2 IO_A / IO_B 12 AWG (7.62mm pitch terminals)2 1. The uncovered communications cable shield connected to the common terminal should not exceed 1” (2.5 cm) for proper EMC shielding of the communications cable. 2. Wire gauge size remains constant; increased pitch distance reflects higher voltage rating. 10 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 2: INSTALLATION ELECTRICAL INSTALLATION It is recommended that you install a circuit disconnection system for control power, near the device, which should be easily accessible after installation of the unit. This is in case an emergency power shut-down of the unit is required. NOTE: NOTE Figure 2-9: Example of module arrangement B L V- L N C H V+ PSU 60-300 VAC 84-250 VDC MS NS g Technical Support: Tel: (905) 294-6222 (North America) 1-800-547-8629 Fax: (905) 201-2098 www.GEMultilin.com D 14 14 13 13 13 12 12 12 8 8 7 6 8 5 5 SG 7 R 4 4 6 I 5 3 3 2 1 11 10 11 11 11 10 10 9 9 9 8 8 8 7 7 7 6 6 6 5 5 5 2 4 4 4 3 3 3 1 2 2 2 1 1 1 3 2 1 Base unit 14 10 9 4 IND.CONT.EQ. 52TL H 13 6 10/100 ETHERNET G 14 7 + – C + – E200434 LISTED F E 12 GROUND CT I/P MULTILIN C THERM RS485 FIELD BUS A Slot position Expansion modules 853749A1.CDR Module and terminal identification The MM300 input/output and protection modules are labeled with the “IO_” prefix followed by a one-character identifier as follows. Table 2-3: Input/output module nomenclature Module Description IO_A CT module IO_B VT module IO_C Two 10 A form-A relays, six 60 to 300 V AC digital inputs, and Aux VT input module. IO_D Four 10 A form-C relays module. IO_E Two 10 A form-A relays, six 20 to 60 V DC digital inputs. IO_G 3 RTD module. The MM300 terminals are labeled with a three-character identifier. The first character identifies the module slot position and the second character identifies the terminals within the module. For example, the first terminal in a module in slot C is identified as “C1”. NOTE: NOTE Do not confuse the slot designation with the module ordering designation. That is, terminal “C1” does not imply an IO_C module. Rather, it indicates the first terminal of whatever module is in slot C. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 11 ELECTRICAL INSTALLATION CHAPTER 2: INSTALLATION Full-voltage non-reversing starter Figure 2-10: Full-voltage non-reversing starter wiring - IO_C L N G A B C C14 Aux VT N L Com IN 6 C10 IN 5 C9 IN 4 C8 IN 3 M C7 IN 2 M C11 C6 C5 GE Multilin Contactor I/O Module- Type C M C13 IN 1 PSU MM300 CT2 CT1 Relay 2 IA CT3 CPU RS485 Thermistor Core Balance Surge Gnd - MOTOR + Com + I Gnd R Core Balance CT Relay 1 IB Low Voltage Motor Manager G/F CT Module IC D8 D7 D6 D5 D4 D3 D2 D1 C12 Reset Field Start Field Stop M C4 C3 C2 C1 M RS485 Serial Link Ground at one point 853704A3.cdr Stator Thermistor Figure 2-11: Full-voltage non-reversing starter control wiring - IO_E L N G AC Control Power C14 Aux VT N L C13 Com C11 IN 6 C10 IN 5 PSU C9 Reset Field Start Relay 1 Relay 2 IN 4 C8 IN 3 C7 IN 2 C12 C6 IN 1 Low Voltage Motor Manager I/O Module- Type C GE Multilin MM300 Low Voltage DC Supply to IO Type E + - C5 Field Stop M C4 C3 C2 C1 M 853704B3.cdr 12 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 2: INSTALLATION NOTE: NOTE ELECTRICAL INSTALLATION The above drawing applies only to a high-voltage power supply. If a low-voltage (DC) power supply is used, an appropriate DC voltage source must be used for this power supply. . The full-voltage non-reversing starter type is a full voltage or across-the-line non-reversing starter. When a start control is received, the pre-contactor relay (if any) is picked up for the set precontactor time. When the pre-contactor timer times out, relay1 picks up and seals-in, picking up contactor M, which starts the motor. When a stop control is received, relay1 drops out, contactor M drops out, and the motor stops. The pre-contactor is omitted on forced starts (for example, UVR Immediate, External Start). Connect AUX VT to the Control Supply for correct operation of the UV Restart feature and correct input readings. NOTE: NOTE RS485 connections Figure 2-12: Typical RS485 connection Z T (*) SHIELD MM300 IED TWISTED PAIR B1 RS485 + B2 RS485 - OPTOCOUPLER OPTOCOUPLER DATA DATA COM SCADA, PLC, OR PERSONAL COMPUTER B3 COMMON GROUND THE SHIELD AT THE SCADA/PLC/COMPUTER ONLY OR THE MM300 ONLY IED RS485 + (*) TERMINATING IMPEDANCE AT EACH END (typically 120 ohms and 1 nF) RS485 - COMMON UP TO 32 MM300 OR OTHER IEDs, MAXIMUM CABLE LENGTH OF 1200 m (4000 ft.) IED Z T (*) RS485 + RS485 - COMMON LAST DEVICE 853745A1.CDR One two-wire RS485 port is provided. Up to 32 MM300 IEDs can be daisy-chained together on a communication channel without exceeding the driver capability. For larger systems, additional serial channels must be added. Commercially available repeaters can also be used to add more than 32 relays on a single channel. Suitable cable should have a characteristic impedance of 120 ohms and total wire length should not exceed 1200 meters (4000 ft). Commercially available repeaters will allow for transmission distances greater than 1200 meters. Voltage differences between remote ends of the communication link are not uncommon. For this reason, surge protection devices are internally installed across all RS485 terminals. Internally, an isolated power supply with an optocoupled data interface is used to prevent noise coupling. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 13 ELECTRICAL INSTALLATION CHAPTER 2: INSTALLATION To ensure that all devices in a daisy-chain are at the same potential, it is imperative that the common terminals of each RS485 port are tied together and grounded only once, at the master or at the MM300. Failure to do so may result in intermittent or failed communications. CAUTION: The source computer/PLC/SCADA system should have similar transient protection devices installed, either internally or externally. Ground the shield at one point only, as shown in the figure above, to avoid ground loops. Correct polarity is also essential. The MM300 IEDs must be wired with all the positive (+) terminals connected together and all the negative (–) terminals connected together. Each relay must be daisy-chained to the next one. Avoid star or stub connected configurations. The last device at each end of the daisy-chain should be terminated with a 120 ohm ¼ watt resistor in series with a 1 nF capacitor across the positive and negative terminals. Observing these guidelines will ensure a reliable communication system immune to system transients. The uncovered communications cable shield connected to the common terminal should not exceed 1” (2.5 cm) for proper EMC shielding of the communications cable. Phase current inputs (IO_A module) Figure 2-13: Typical phase current input connections D1 D2 CT1 D3 D4 CT2 D5 Power flow Power flow Power flow D6 CT3 D7 D8 G/F Phase current inputs Residual Ground Connection D1 D2 CT1 D3 D4 CT2 D5 D6 D7 D8 G/F CT3 D1 D2 CT1 D3 D4 CT2 D5 D6 CT3 D7 D8 G/F Phase current inputs Phase current inputs Direct Connection Two CT Connection 853753A1.cdr 14 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 2: INSTALLATION ELECTRICAL INSTALLATION Core Balance (Zero Sequence) Power flow Contactor A B C To switchgear ground bus – + N L D1 D2 D3 D4 CT2 D5 D6 CT3 Phase current inputs D7 D8 G/F R CT1 CBCT / 50 : 0.025 Control power I MM300 Motor Management System 853744A2.CDR The MM300 has three channels for phase current inputs, each with an isolating transformer. The phase CTs should be chosen so the FLA is not less than 50% of the rated phase CT primary. Ideally, the phase CT primary should be chosen such that the FLA is 100% of the phase CT primary or slightly less, never more. This will ensure maximum accuracy for the current measurements. The maximum phase CT primary current is 1000 A. The ground CT connection can either be a zero sequence (core balance) installation or a residual connection. Note that only 1 A and 5 A secondary CTs may be used for the residual connection. The zero sequence connection is shown in the diagram above, and this is recommended. Unequal saturation of CTs, CT mismatch, size and location of motor, resistance of the power system, motor core saturation density, etc. may cause false readings in the residually connected ground fault circuit. Refer to section 2.2.2.1 for CBCT connection. Note that if residual ground connection is selected, the CT primary setpoint used by the Phase CT's will also be used by the residual ground calculations. CAUTION: Polarity of the phase CTs is critical for negative-sequence unbalance calculation, power measurement, and residual ground current detection (if used). MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 15 ELECTRICAL INSTALLATION Two CT configuration CHAPTER 2: INSTALLATION Each of the two CTs acts as a current source. The current that comes out of the CT on phase A flows into the interposing CT on the relay marked CT1. From there, the current sums with the current that is flowing from the CT on phase C which has just passed through the interposing CT on the relay marked CT3. This summed current flows through the interposing CT marked CT2 and from there, the current splits up to return to its respective source (CT). Polarity is very important since the value of phase B must be the negative equivalent of A + C in order for the sum of all the vectors to equate to zero. Only one ground connection should be made as shown. If two ground connections are made, a parallel path for current has been created. In the two CT configuration, the currents will sum vectorially at the common point of the two CTs. The diagram illustrates the two possible configurations. If one phase is reading high by a factor of 1.73 on a system that is known to be balanced, simply reverse the polarity of the leads at one of the two phase CTs (taking care that the CTs are still tied to ground at some point). Polarity is important. Change CT wiring only if the system is de-energized! NOTE: NOTE Figure 2-14: Two CT connection vector diagram 60° 1.73 1 1 60° 1 60° 1 853715A1.CDR To illustrate the point further, the following diagram shows how the current in phases A and C sum up to create phase "B". Figure 2-15: Two CT connection currents 1.73 1 C Two-phase CT currents 1 B A A B C Two-phase CT currents, 180° out-of-phase 808701A1.CDR Once again, if the polarity of one of the phases is out by 180°, the magnitude of the resulting vector on a balanced system will be out by a factor of 1.73. On a three-wire supply, this configuration will always work and unbalance will be detected properly. In the event of a single phase, there will always be a large unbalance present at the interposing CTs of the relay. If for example phase A was lost, phase A would read zero while phase B and C would both read the magnitude of phase C. If on the other hand, phase B was lost, at the supply, phase A would be 180° out-of-phase with phase C and the vector addition would equal zero at phase B. 16 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 2: INSTALLATION ELECTRICAL INSTALLATION Phase voltage inputs (IO_B module) The MM300 has three channels for AC voltage inputs. There are no internal fuses or ground connections on the voltage inputs. Polarity is critical for correct power measurement and voltage phase reversal operation. Figure 2-16: Wye voltage connection Contactor A B C – + N L FUSES - 100 ma typical To switchgear ground bus E2 E1 Control power E3 VT1 E4 E6 E5 VT2 E7 E8 N/C VT3 Phase voltage inputs MM300 Motor Management System 853735A2.CDR Figure 2-17: Delta voltage connection Contactor A B C FUSES To switchgear ground bus – + N L Control power E1 E2 E3 VT1 E4 VT2 E5 E6 VT3 E7 E8 N/C Phase voltage inputs MM300 Motor Management System 853736A2.CDR MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 17 ELECTRICAL INSTALLATION CHAPTER 2: INSTALLATION Type IO_C module connections Figure 2-18: Typical wiring for type IO_C module MM300 Motor Management System SURGE ~14 L ~12 Six contact (digital) inputs + ~13 VT INPUT – AC Control power N COMMON ~11 CONTACT INPUT 6 + ~10 CONTACT INPUT 5 + ~9 CONTACT INPUT 4 + ~8 CONTACT INPUT 3 + ~7 CONTACT INPUT 2 + ~6 B CONTACT INPUT 1 + ~5 A ~4 CONTACT OUTPUT 2 ~3 Two form-A contact outputs B ~2 CONTACT OUTPUT 1 ~1 A Contactors 853741A3.CDR The IO_C module contains two form-A contact output relays, six digital inputs and control voltage input. Contact inputs can be programmed to any of the input functions, such as field stop or process interlock. The exception is that contactor A status is fixed as the first contact input, and contactor B status (where used) is fixed as the second contact input. An AC auxiliary supply must be connected to terminals 12 and 13. This auxiliary voltage (from slot C only) is also used for actual value indication, for auxiliary undervoltage, and for undervoltage restart. When three-phase voltages are not available, it is also used to calculate power quantities and is used as a phase angle reference. When the IO_C module, located in slot C, senses an interruption to its auxiliary supply, it raises an AC Low Aux Voltage Inhibit, and forces the input state of the contact inputs to OFF, as the interruption prevents sensing the actual states. The two contact outputs can be programmed to follow any one of the digital signals developed by the MM300, such as alarms and status signals. The exception is that the contactor A relay is fixed as the first contact output, and contactor B relay is fixed as the second contact output (where used). Connect AUX VT to the Control Supply for correct operation of the UV Restart feature and readings of inputs. NOTE: NOTE The auxiliary voltage connection is required on all IO_C modules, both in slot C and in expansion slots. NOTE: NOTE Substitute the slot position of the input/output module (C, E, F, G, H) wherever the tilde symbol “~” appears in the diagrams above. NOTE: NOTE 18 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 2: INSTALLATION ELECTRICAL INSTALLATION Type IO_D module connections The IO_D module contains four form-C contact output relays. In general, contact outputs can be programmed to follow any one of the digital signals developed by the MM300, such as alarms and status signals. Figure 2-19: Typical wiring for type IO_D contact output module MM300 Motor Management System NOT USED ~14 NOT USED ~13 ~12 CONTACT OUTPUT 4 ~11 ~10 ~9 CONTACT OUTPUT 3 ~8 ~7 Four form-C contact outputs ~6 CONTACT OUTPUT 2 CLOSE COIL ~5 START ~4 52b ~3 CONTACT OUTPUT 1 ~2 TRIP COIL ~1 STOP 52a N Control power + L 853742A1.CDR – Substitute the slot position of the input/output module (E, F, G, or H) wherever the tilde symbol “~” appears in the diagrams above. NOTE: NOTE MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 19 ELECTRICAL INSTALLATION CHAPTER 2: INSTALLATION Type IO_E module connections Figure 2-20: Typical wiring for type IO_E module MM300 Motor Management System SURGE ~14 ~12 Six contact (digital) inputs N – – ~11 CONTACT INPUT 6 + ~10 CONTACT INPUT 5 + ~9 CONTACT INPUT 4 + ~8 CONTACT INPUT 3 + ~7 CONTACT INPUT 2 + ~6 B ~5 A + COMMON CONTACT INPUT 1 + L + ~13 VT INPUT AC Control power DC supply DC supply Contactor Aux ~4 CONTACT OUTPUT 2 ~3 Two form-A contact outputs B ~2 CONTACT OUTPUT 1 ~1 A Contactors 853754A1.CDR The IO_E module contains two form-A contact output relays, six digital inputs and a voltage input, which is a required connection. Contact inputs can be programmed to any of the input functions, such as field stop or process interlock. The exception is that contactor A status is fixed as the first contact input, and contactor B status (where used) is fixed as the second contact input. An AC auxiliary supply must be connected to terminals 12 and 13 of the IO_E module in slot C. This auxiliary voltage from slot C is used for actual value indication, for auxiliary undervoltage, and for undervoltage restart. When three-phase voltages are not available, it is also used to calculate power quantities and is used as a phase angle reference. When the IO_E module, located in slot C, senses a low auxiliary voltage inhibit and the Undervoltage restart function is enabled, the states of the contact inputs are forced to OFF. The auxiliary voltage connection is required on all IO_E modules, both in slot C and in expansion slots. NOTE: NOTE The two contact outputs can be programmed to follow any one of the digital signals developed by the MM300, such as alarms and status signals. The exception is that the contactor A relay is fixed as the first contact output, and contactor B relay is fixed as the second contact output (where used). Substitute the slot position of the input/output module (C, E, F, G, H) wherever the tilde symbol “~” appears in the diagrams above. NOTE: NOTE 20 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 2: INSTALLATION ELECTRICAL INSTALLATION RTD sensor connections (IO_G module) The type IO_G module contains three PT100 RTDs and associated protection functionality. The MM300 monitors up to six RTD inputs for stator, bearing, ambient, or other temperature monitoring types. The type of each RTD is 100 ohm platinum (DIN 43760). RTDs must be three-wire type. The RTD circuitry compensates for lead resistance, provided that each of the three leads is the same length. Lead resistance should not exceed 25 ohms per lead. Shielded cable should be used to prevent noise pickup in industrial environments. RTD cables should be kept close to grounded metal casings and away from areas of high electromagnetic or radio interference. RTD leads should not be run adjacent to or in the same conduit as high current carrying wires. The uncovered communications cable shield connected to the common terminal should not exceed 1” (2.5 cm) for proper EMC shielding of the communications cable. Figure 2-21: RTD wiring RTD1 RTD2 RTD3 MM300 Motor Protection System N/C ~14 Surge ground ~13 Shield ~12 Compensation ~11 Return ~10 Hot ~9 Shield ~8 Compensation ~7 Return ~6 Hot ~5 Shield ~4 Compensation ~3 Return ~2 Hot ~1 Motor starter Three-wire shielded cable Route cable in separate conduit from current carrying conductors RTD terminals at motor Motor RTD in motor stator or bearing RTD terminals in motor starter Maximum total lead resistance: 25 ohms for Platinum RTDs 853737A3.CDR MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 21 MAINTENANCE CHAPTER 2: INSTALLATION Maintenance The MM300 requires minimal maintenance. As a microprocessor-based relay, its characteristics do not change over time. The expected service life of an MM300 is 20 years when the environment and electrical conditions are within stated specifications. While the MM300 performs continual self-tests, it is recommended that maintenance be scheduled with other system maintenance. This maintenance can involve in-service, outof-service, or unscheduled maintenance. In-service maintenance 1. 2. 3. 4. Visual verification of the analog values integrity, such as voltage and current (in comparison to other devices on the corresponding system). Visual verification of active alarms, relay display messages, and LED indications. Visual inspection for any damage, corrosion, dust, or loose wires. Event recorder file download with further events analysis. Out-of-service maintenance 1. 2. 3. 4. 5. 6. FASTPATH: Check wiring connections for firmness. Analog values (currents, voltages, RTDs, analog inputs) injection test and metering accuracy verification. Calibrated test equipment is required. Protection elements setting verification (analog values injection or visual verification of setting file entries against relay settings schedule). Contact inputs and outputs verification. This test can be conducted by direct change of state forcing or as part of the system functional testing. Visual inspection for any damage, corrosion, or dust. Event recorder file download with further events analysis. To avoid deterioration of electrolytic capacitors, power up units that are stored in a deenergized state once per year, for one hour continuously. Unscheduled maintenance (system interruption) • 22 View the event recorder and oscillography for correct operation of inputs, outputs, and elements. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 2: INSTALLATION INTERFACING WITH THE MM300 Interfacing with the MM300 There are three methods of interfacing with the MM300 Motor Management System. • Interfacing via the graphical control panel. • Interfacing via the basic control panel. • Interfacing via the EnerVista MM300 Setup software. This section provides an overview of the interfacing methods available with the MM300 using the Graphical and Basic control panels. For additional details on interface parameters (for example, settings, actual values, etc.), refer to the individual chapters. MM300 graphical display pages A summary of the MM300 page hierarchy is shown below. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 23 INTERFACING WITH THE MM300 CHAPTER 2: INSTALLATION Figure 2-22: MM300 display page hierarchy Motor Values CT-VT Summary Amps Inputs Trips Outputs Alarms Comms Control System Virtual Volts Power Sensor Events Status Message Reset Inputs Counters Waveform Outputs Datalog System Summary Flex Setpoints V Inputs Config V Outputs Protection Thermal Control Mech Security Diag Events Clear Counters Clear Phasors Info Learned Waveform Elec Sensor Starter Inhibits Interlock UV Restart Datalog Control Auto Manual Main menu Level 1 Level 2 Level 3 853701A5.CDR 24 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 2: INSTALLATION INTERFACING WITH THE MM300 Introduction to the graphical control panel The central feature of the graphical control panel is a 3.5-inch 320 by 240 pixel backlit color LCD screen. The panel also contains keys (pushbuttons) that control the display and perform commands. In addition, the interface contains START A, START B, and STOP direct acting control pushbuttons. The display also contains several LED indicators that provide a summary of the machine status. Details are displayed on the screen when the user navigates to the appropriate page. Figure 2-23: MM300 front panel with example default display Graphical display Each display page consists of the three components shown below. Figure 2-24: Graphical display overview The header bar (white text on a blue background) displays the hierarchical path name, the date and time in 24-hour format, and the current password access level. The hierarchical path is always displayed on the left top side of the graphical display. The present time is displayed on the right top side. If the test switch is on, the time is replaced with the text TEST MODE in red. The soft-key labels are indicated on the bottom line. The soft-keys are used for navigation, performing functions, and for acknowledgement. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 25 INTERFACING WITH THE MM300 CHAPTER 2: INSTALLATION • Navigation: soft-keys can be used to traverse across and down the hierarchy of pages. • Functional: soft-keys can be used to perform page-specific functions. • Acknowledgement: soft keys can be used to acknowledge popup windows. Soft-keys labels change to show relevant selections for the displayed screen. The color of each soft-key label indicates its functionality. Soft-keys are highlighted for the displayed page, unauthorized keys are “greyed-out”, and unused keys are not displayed. The remainder of the screen shows the selected page. Pages are organized in a hierarchical or tree-based menu structure. To improve readability, some pages are labeled with rectangular outlines or colored backgrounds. Some pages contain too many fields to display at once. These pages display arrows bars at the right edge to indicate that the page continues below the screen. When recalled, scrolled pages are re-positioned at the top of the page. Fields display actual value or setting information, and have behaviours that allow help display, editing, and control. Each Actual Value analog field displayed on the home page has an associated alarm limit and changes color to orange when that limit is exceeded. Fields with an associated trip limit change their color to red when that limit has tripped. Fields that are disabled or unavailable are greyed-out. Keypad The function keys perform the labeled functionality. The summary of function key operation is shown below. Table 2-4: Summary of function key operations Key Operation HOME Single press recalls the home page; double press recalls the default display UP Scroll up page, select field, tab to next field, increment value DOWN Scroll down page, select field, tab to previous field, decrement value ESC Single press closes pop-up, cancels editing, deselects field, moves to previous page; sustained press logs out (cancels security passcode entry) ENTER Single press freezes scrolling and selects field, edits selected field, saves edited value; double press sets the selected field/page as default; sustained press logs in (enter security passcode) HELP Displays context sensitive help and Modbus address The HOME key always recalls the root or home page. The home page allows access to all sub-pages and also contains a status and process values summary. Double pressing the HOME key recalls the default display. Like a screen-saver, the default display appears after a period of inactivity and displays user-selected information. A typical default display is shown below, indicating a running motor in the forward direction. Figure 2-25: Typical default display (actual size) 26 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 2: INSTALLATION INTERFACING WITH THE MM300 The UP and DOWN keys function in different ways depending on their context. • Where a scroll bar is displayed, the UP and DOWN keys scroll the page up and down. • Where there is no scroll bar or it is greyed-out, the first press of the UP and DOWN keys selects the first field. Subsequent presses tab up and down through the fields, scrolling as required. • When a field is open for editing, the UP and DOWN keys increment/decrement the value of that field. The ENTER key functions in different ways depending on its context. • If there are no selected fields, the ENTER key will freeze any scroll bars and select the first field on the display. • If a field is selected, pressing ENTER will attempt to open it for editing. • If a field is opened for editing, pressing enter will exit the edit sequence. • Double pressing the ENTER key at any time selects the displayed page as the default display. • A sustained press on ENTER prompts the security passcode and displays a dialog box that allows passcode entry. For example, pressing and holding the ENTER key, or attempting a control where a password is required, displays the following page. Figure 2-26: Passcode entry dialog box The ESC key functions in different ways depending on its context. • If a pop-up dialog box is displayed, the ESC key closes it. • If an edit sequence is in progress, the ESC key cancels the edit. • If a field is selected, the ESC key de-selects it. • In all other instances, the ESC key moves back one page in the menu structure. • A sustained press on the ESC key clears the security passcode and prompts for confirmation. The HELP key functions in different ways depending on its context. • If a field is selected, the HELP key displays a help window for the field. • If a help window is displayed, the HELP key closes it. Help windows are also closed when any other key is pressed. A typical help window is shown below. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 27 INTERFACING WITH THE MM300 CHAPTER 2: INSTALLATION Figure 2-27: Typical MM300 help window Pressing an invalid key displays a message explaining the problem and recommending a solution. Where the keypress is invalid because a security passcode is required, the dialog window will be a passcode entry window. When a lockout occurs that clears when a count-down timer expires or when the thermal capacity recovers for a restart, the Status > Message page is displayed indicating timer value or thermal capacity. Status pages The status pages provide the user with up-to-date information on the current status of the MM300. Status pages are divided into five sections. • Message (displays all locked out conditions plus conditions such as alarms, internal faults, control status, etc.). • Inputs (displays the present state of assigned contact inputs). • Outputs (displays the present state of assigned contact outputs). • System (displays the present state of the communications interface). • Flex (displays the present state of the FlexLogic™ engine and number of lines used.) A typical display is shown below: Figure 2-28: Typical status message page Message types are classified by color and associated icon type, as follows:: • Red Triangle = Trip • Orange Square = Alarm • Blue Circle = Inhibit • Black Text = Information Message Message can have an associated countdown timer. 28 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 2: INSTALLATION INTERFACING WITH THE MM300 When the relay is first powered up, the status page lists why the relay is not available for service. This is not an exhaustive list of setpoints to be configured, but is a list of key items such as FLA, CT Type, starter type and control Source, that must be configured before the unit will be available for use. Protection values must still be configured for the motor to be protected correctly. Inhibits These include Process Interlock Stop, and Field Stop. Trips / Alarms These trigger depending on the protection setpoints. A typical example would be; “Overload Trip”. Information Messages Information pages are split into two groups – With navigation (shown above, as an Enter symbol on the right side of the display) – Without navigation When a line showing a message (with navigation) is highlighted, pressing Enter will take the GCP directly to the page in question, so that the situation can be quickly resolved. A typical example would be “FLA not set”. Selecting this entry on the page will take you to the \setpoints\config\motor page. MM300 programming techniques CAUTION: To streamline the setting entry process, the graphical control panel omits non-functional settings from the display. Settings may be changed while the motor is running. However, appropriate measures must be taken to limit the consequences of entering unintended or misunderstood setting values. Consequences of inappropriate settings to the specific application at hand include loss of protection, loss of control, and undesired starting or stopping. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 29 INTERFACING WITH THE MM300 CHAPTER 2: INSTALLATION Basic control panel The MM300 basic control panel provides the basic start and stop panel functionality, as well as a series of LED indications. The basic control panel is illustrated below. Figure 2-29: Basic control panel 853750A1.CDR The following LEDs are provided: IMPORTANT: 30 • Two USER LEDs (USER 1 and USER 2). the user can select parameters from a list • 50%/80%/100% - showing motor load • RUNNING, STOPPED, TRIPPED, and ALARM • COMMS OK • AUTO and MANUAL The STOP button on the MM300 control panel cannot be used as an E-Stop switch. An external Emergency push button should be installed. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 2: INSTALLATION ENERVISTA MM300 SETUP SOFTWARE EnerVista MM300 Setup Software Although settings can be entered manually using the control panel keys, a PC can be used to download values through the communications port. The EnerVista MM300 Setup software is available from GE Multilin to make this as convenient as possible. With EnerVista MM300 Setup running, it is possible to: • Program and modify settings • Load and save setting files to and from a disk • Read actual values • Monitor status • Read pre-trip data and event records • Get help on any topic • Upgrade the MM300 firmware The EnerVista MM300 Setup software allows immediate access to all MM300 features with easy to use pull down menus in the familiar Windows environment. This section provides the necessary information to install EnerVista MM300 Setup, upgrade the relay firmware, and write and edit setting files. The EnerVista MM300 Setup software can run without a MM300 connected to the computer. In this case, settings may be saved to a file for future use. If an MM300 is connected to a PC and communications are enabled, the MM300 can be programmed from the setting screens. In addition, measured values, status and trip messages can be displayed with the actual value screens. Software requirements The following requirements must be met for the EnerVista MM300 Setup software. • Windows 7, Windows 8.1, or Windows 10 is installed and running properly. The EnerVista MM300 Setup software can be installed from either the GE EnerVista CD or the GE Multilin website at www.gegridsolutions.com/Multilin. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 31 ENERVISTA MM300 SETUP SOFTWARE CHAPTER 2: INSTALLATION Troubleshooting the USB driver When the Setup Software is installed on the Windows 2000 or XP operating system, and the device is power recycled while the native USB port is still connected to the PC, the USB driver in the PC Program may get lost and the setup software may fail to recognize the USB device. If this happens, the ‘MM300 USB Serial Emulation (COM #)’ will be missing in the Setup Software’s Device Setup window. To overcome the problem: 1. Remove the USB cable from the native port of the device. 2. Wait for 20 Seconds and connect the cable back to the native port of the device. 3. Check the Setup Software for the availability of the USB Device on the Device setup Window. It will automatically reappear on the ‘USB Device’ list as ‘MM300 USB Serial Emulation (COM #)’ as shown in the image below. 4. 32 If the USB Device is not recognized automatically in the Setup Software, repeat the same procedure 2 or 3 times until the PC Program recognizes the USB device (and ‘MM300 USB Serial Emulation (COM #)’ reappears in dropdown of ‘USB Device’ list). MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 2: INSTALLATION ENERVISTA MM300 SETUP SOFTWARE 5. If problem still persists, uninstall the USB driver from Computer’s ‘Device Manager’ under tree-branch modems from the Installation folder. To uninstall it, right click on MM300 USB Serial Emulation and select Uninstall. 6. After the uninstall, remove the USB cable from the Device’s native USB port, wait for at least 10 Seconds and reconnect it. Now the ‘Found New Hardware Wizard’ will open, select No, not this time and press the Next button. 7. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 33 ENERVISTA MM300 SETUP SOFTWARE CHAPTER 2: INSTALLATION 8. Select Install the software automatically (Recommended) and press the Next button. 9. Press Continue Anyway. 10. At the end press Finish. 11. Check in the Setup Software for the availability of the USB Device on the Device setup Window. Now the device will reappear on the ‘USB Device’ list. For the current version, the USB driver can not be installed on Windows Vista Operating System and communication to the Device via the Native USB port is not supported. 34 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 2: INSTALLATION ENERVISTA MM300 SETUP SOFTWARE Installing the EnerVista MM300 Setup software After ensuring the minimum requirements indicated earlier, use the following procedure to install the EnerVista MM300 Setup software from the enclosed GE EnerVista CD. 1. Insert the GE EnerVista CD into your CD-ROM drive. 2. Click the Install Now button and follow the installation instructions to install the nocharge EnerVista software on the local PC. 3. When installation is complete, start the EnerVista Launchpad application. 4. Click the IED Setup section of the Launch Pad toolbar. 5. In the EnerVista Launchpad window, click the Add Product button and select the MM300 Motor Management System as shown below. Select the Web option to ensure the most recent software release, or select CD if you do not have a web connection, then click the Add Now button to list software items for the MM300. 6. EnerVista Launchpad will obtain the latest installation software from the Web or CD and automatically start the installation process. A status window with a progress bar will be shown during the downloading process. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 35 ENERVISTA MM300 SETUP SOFTWARE 7. 8. 9. CHAPTER 2: INSTALLATION Select the complete path, including the new directory name, where the EnerVista MM300 Setup software will be installed. Click on Next to begin the installation. The files will be installed in the directory indicated, the USB driver will be loaded into the computer, and the installation program will automatically create icons and add EnerVista MM300 Setup software to the Windows start menu. The following screen will appear: Press the Continue Anyway button, then click Finish to end the installation. The MM300 device will be added to the list of installed IEDs in the EnerVista Launchpad window, as shown below. If you are going to communicate from your computer to the MM300 Relay using the USB port: 36 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 2: INSTALLATION ENERVISTA MM300 SETUP SOFTWARE 10. Plug the USB cable into the USB port on the MM300 Relay then into the USB port on your computer. The following screen will appear: 11. Select Install... Automatically 12. Select No, not this time. The above Hardware Installation warning screen (see #8 above) will reappear. Press the Continue Anyway button. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 37 ENERVISTA MM300 SETUP SOFTWARE CHAPTER 2: INSTALLATION 13. In EnerVista > Device Setup: Select USB as the Interface type. 14. Select the appropriate USB device. Upgrading the software The latest EnerVista software and firmware can be downloaded from: https://www.gegridsolutions.com/app/ViewFiles.aspx?prod=mm300&type=7 After upgrading, check the version number under Help > About. If the new version does not display, try uninstalling the software and reinstalling the new versions. 38 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 2: INSTALLATION CONNECTING ENERVISTA MM300 SETUP TO THE RELAY Connecting EnerVista MM300 Setup to the relay Configuring serial communications Before starting, verify that the cable is properly connected to either the USB port on the front panel of the device (for USB communications) or to the Serial port on the rear of the device. This example demonstrates a Serial connection. 1. Install and start the latest version of the EnerVista MM300/MM200 Setup software (available from the GE Multilin web site). See the previous section for the installation procedure. 2. Click on the Device Setup button to open the Device Setup window and click the Add Site button to define a new site. 3. Enter the desired site name in the "Site Name" field. If desired, a short description of the site can also be entered. In this example, we will use “New Site 1” as the site name. 4. The new site will appear in the upper-left list in the EnerVista MM300/MM200 Setup window. 5. Click the Add Device button to define the new device. 6. Enter the desired name in the "Device Name" field and a description (optional) of the device. 7. Select “Serial Device” from the Interface drop-down list. 8. 9. Click the Read Order Code button to connect to the MM300 device and upload the order code. Click OK when the relay order code has been received. The new device will be added to the Site List window (or Online window) located in the top left corner of the main EnerVista MM300/MM200 Setup window. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 39 CONNECTING ENERVISTA MM300 SETUP TO THE RELAY CHAPTER 2: INSTALLATION The MM300 Site Device has now been configured for Serial communications. Proceed to Connecting to the Relay below, to begin communications. Using the Quick Connect feature The Quick Connect button can be used to establish a fast connection through the front panel USB port of a MM300 relay. The following window will appear when the QuickConnect button is pressed: As indicated by the window, the "Quick Connect" feature can quickly connect the EnerVista MM300/MM200 Setup software to a MM300 front port if the USB is selected in the interface drop-down list. Select "MM300 Relay" and press the Connect button. When connected, a new Site called “Quick Connect” will appear in the Site List window. The MM300 Site Device has now been configured via the Quick Connect feature for either USB or Serial communications. Proceed to Connecting to the Relay below, to begin communications. Connecting to the relay Now that the communications parameters have been properly configured, the user can easily communicate with the relay. 1. Expand the Site list by double clicking on the site name or clicking on the «+» box to list the available devices for the given site. 2. Desired device trees can be expanded by clicking the «+» box. The following list of headers is shown for each device: Device Definition Setpoints Values Diagnostics Device Summary Status Exerciser Maintenance. 3. Expand any list item and double click on any item contained in the expanded list to open that item, as shown below: 40 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 2: INSTALLATION CONNECTING ENERVISTA MM300 SETUP TO THE RELAY 4. The window related to that item will open with a corresponding status indicator tab on the lower left of the EnerVista SR3 Setup window. 5. If the status indicator is red, verify that the seria or USB cable is properly connected to the relay, and that the relay has been properly configured for communications (steps described earlier). The "item" settings can now be edited, printed, or changed. Other windows can be displayed and edited in a similar manner. These windows can be arranged, and resized at will. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 41 WORKING WITH SETPOINTS AND SETPOINT FILES CHAPTER 2: INSTALLATION Working with setpoints and setpoint files Engaging a device The EnerVista MM300/MM200 Setup software may be used in on-line mode (relay connected) to directly communicate with a relay. Communicating relays are organized and grouped by communication interfaces and into sites. Sites may contain any number of relays selected from the product series. Entering setpoints The System Setup page will be used as an example to illustrate the entering of setpoints. In this example, we will be changing the current sensing setpoints. 1. Establish communications with the relay. 2. Select the Setpoint > Configure > CT-VT menu item. 3. Select the CT Primary setpoint by clicking anywhere in the parameter box. This will display three arrows: two to increment/decrement the value and another to launch the numerical keypad. 4. 42 Clicking the arrow at the end of the box displays a numerical keypad interface that allows the user to enter a value within the setpoint range displayed near the top of the keypad: Click = to exit from the keypad and keep the new value. Click on X to exit from the keypad and retain the old value. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 2: INSTALLATION WORKING WITH SETPOINTS AND SETPOINT FILES 5. For setpoints requiring non-numerical pre-set values (e.g. CT Primary below), clicking anywhere within the setpoint value box displays a drop-down selection menu arrow. Select the desired value from this list. 6. For setpoints requiring an alphanumeric text string (e.g. "relay name"), the value may be entered directly within the setpoint value box. In the Setpoint > Config > CT-VT dialog box, click on Save to save the values into the MM300 . Click YES to accept any changes and exit the window. Click Restore to retain previous values. Click Default to restore Default values. 7. File support Opening any EnerVista MM300/MM200 Setup file will automatically launch the application or provide focus to the already opened application. If the file is a Settings file (has a ‘M30’ extension) which had been removed from the Settings List tree menu, it will be added back to the Settings List tree. New files will be automatically added to the tree. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 43 WORKING WITH SETPOINTS AND SETPOINT FILES CHAPTER 2: INSTALLATION Using setpoints files The EnerVista MM300/MM200 Setup software interface supports three ways of handling changes to relay settings: • In off-line mode (relay disconnected) to create or edit relay settings files for later download to communicating relays. • Directly modifying relay settings while connected to a communicating relay, then saving the settings when complete. • Creating/editing settings files while connected to a communicating relay, then saving them to the relay when complete. Settings files are organized on the basis of file names assigned by the user. A Settings file contains data pertaining to the following types of relay settings: • Configure • Protection • Control • Security Settings • Modbus User Map • FlexLogic Factory default values are supplied and can be restored after any changes. The EnerVista MM300/MM200 Setup displays relay setpoints with the same hierarchy as the front panel display. Downloading and saving setpoints files Setpoints must be saved to a file on the local PC before performing any firmware upgrades. Saving Setpoints is also highly recommended before making any Setpoint changes or creating new Setpoint files. The Setpoint files in the EnerVista MM300/MM200 Setup window are accessed in the Files Window. Use the following procedure to download and save Setpoint files to a local PC. 1. Ensure that the site and corresponding device(s) have been properly defined and configured as shown in Connecting EnerVista MM300/MM200 Setup to the Relay, above. 2. Select the desired device from the site list. 3. Select the Online > Read Device Settings from Device menu item (at the top of the page), or right-click on the device and select Read Device Settings to obtain settings information from the device. 4. After a few seconds of data retrieval, the software will request the name and destination path of the setpoint file. The corresponding file extension will be automatically assigned. Press Receive to complete the process. A new entry will be added to the tree, in the File pane, showing path and file name for the setpoint file. 44 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 2: INSTALLATION WORKING WITH SETPOINTS AND SETPOINT FILES Adding setpoints files to the environment The EnerVista MM300/MM200 Setup software provides the capability to review and manage a large group of setpoint files. Use the following procedure to add an existing file to the list. 1. In the files pane, right-click on Files and select the Add Existing Setting File item as shown: 2. The Open dialog box will appear, prompting the user to select a previously saved setpoint file. As for any other MS Windows® application, browse for the file to be added then click Open. The new file and complete path will be added to the file list. Loading setpoints from a file CAUTION: An error message will occur when attempting to download a setpoint file with a revision number that does not match the relay firmware. If the firmware has been upgraded since saving the setpoint file, see Upgrading Setpoint Files to a New Revision, above, for instructions on changing the revision number of a setpoint file. The following procedure illustrates how to load setpoints from a file. Before loading a setpoints file, it must first be added to the EnerVista MM300/MM200 Setup environment as described in the section, Adding Setpoints Files to the Environment. 1. Select the previously saved setpoints file from the File pane of the software main window. 2. Select the Offline > Edit Settings File Properties menu item and verify that the corresponding file is fully compatible with the hardware and firmware version of the target relay. If the versions are not identical, see Upgrading Setpoint Files to a New Revision, above, for details on changing the setpoints file version. 3. Right-click on the selected file and select the Write Settings File to Device item. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 45 WORKING WITH SETPOINTS AND SETPOINT FILES CHAPTER 2: INSTALLATION 4. Select the target relay from the list of devices shown and click Send. If there is an incompatibility, an "Incompatible Device" error message will occur: If there are no incompatibilities between the target device and the settings file, the data will be transferred to the relay. An indication of the percentage completed will be shown at the bottom of the main window. Uninstalling files and clearing data The unit can be decommissioned by turning off the power to the unit and disconnecting the wires to it. Files can be cleared after uninstalling the EnerVista software or MM300 device, for example to comply with data security regulations.On the computer, settings files can be identified by the .m30 extension. To clear the current settings file do the following: 1. Create a default settings file. 2. Write the default settings file to the relay. 3. Delete all other files with the .m30 extension. 4. Delete any other data files , which can be in standard formats, such as COMTRADE or .csv. You cannot directly erase the flash memory, but all records and settings in that memory can be deleted. Do this using these commands: DIAGNOSTICS > COMMANDS 46 • CLEAR LAST TRIP DATA PROMPT • CLEAR TRIP COUNTERS • CLEAR MAINTENANCE TIMER • RESET MOTOR INFORMATION MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 2: INSTALLATION UPGRADING RELAY FIRMWARE Upgrading relay firmware To upgrade the MM300 firmware, follow the procedures listed in this section. Upon successful completion of this procedure, the MM300 will have new firmware installed with the factory default setpoints.The latest firmware files are available from the GE Multilin website at http:// www.GEmultilin.com. EnerVista MM300/MM200 Setup software prevents incompatible firmware from being loaded into a MM300 relay. NOTE: NOTE NOTE: NOTE NOTE: NOTE Before upgrading firmware, it is very important to save the current settings to a file on your PC. After the firmware has been upgraded, it will be necessary to load this file back into the MM300 relay. Refer to Downloading and Saving Setpoints Files for details on saving relay setpoints to a file. All IO_C cards must be connected to aux. voltage during any firmware upgrade procedure. If aux. voltage is not connected, calibration data from IO_C cards will not be restored during the upgrade procedure. Loading new relay firmware Loading new firmware into the MM300 flash memory is accomplished as follows: 1. Connect the RJ45 port on the relay (labelled "RS485 to Control Panel") to the RS232 port (COM1) on the local PC, using an RS232 (female)-to-RJ45 (male) custom cable (p/n 0804-0180). If there is no RS232 port on your PC: 1.1. If you are using the MM300 Graphical Control Panel (GCP) or Hand Held Device (HHD), connect the USB port on the front of the MM300 relay, to the USB port on the local PC, using a USB 2.0 type A to mini B cable. This configuration (1) is shown below. 1.2. If you are using the Basic Control Panel (BCP), and your PC has an RS232 port, disconnect the existing RJ45 cable from the side of the base unit (labelled "RS485 to Control Panel"), and connect an RS232-to-RJ45 cable from the PC to that same RJ45 port on the side of the base unit. This configuration (2) is shown below. 1.3. If you are using no control panel, and your PC has an RS232 port, connect an RS232-to-RJ45 cable from the PC to the RJ45 port on the side of the base unit (labelled "RS485 to Control Panel"). This configuration (2) is shown below. Note 1: If your PC does not have an RS232 port, you will have to use a USB-to-serial converter cable (p/n 0100-0001), available at the GE Online Store (http:// www.gegridsolutions.com). This configuration (3) is shown below. Note 2: If the unit does not have Graphical Control Panel (GCP), you will have to use a RS232 to RJ45 custom cable (p/n 0804-0180), available at the GE Online Store (http:// www.gegridsolutions.com). MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 47 UPGRADING RELAY FIRMWARE CHAPTER 2: INSTALLATION Note 3: If you use a USB-to-serial converter cable (see Note 1 above), the effective COM port for this configuration, will be COM10 as shown below. PC (1) USB Port USB (Mini-B)-to-USB (Type-A) cable PC RS 485 TO CONTROL PANEL (2) USB PSU Port RS232 Port (COM1) RS232-to-RJ45 cable USB PSU Port PC RS 485 TO CONTROL PANEL (3) USB Port RS232-to-RJ45 cable (COM10) 2. 3. 48 USB-to-Serial converter cable Click Windows Start Button > Control Panel > System > Hardware tab. Then click Device Manager. Once your physical connections are complete and you have determined which COM PORT you will be using, start your MM300/MM200 EnerVista Setup Program. Save the setpoints to a file as shown in Downloading and Saving Setpoints Files. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 2: INSTALLATION UPGRADING RELAY FIRMWARE 4. 5. Select the Maintenance > Update Firmware menu item. The EnerVista MM300/MM200 Setup software will request the location of the folder containing the new firmware file. Locate the folder that contains the firmware files to load into the MM300 . The firmware filename has the following format: 6. EnerVista MM300/MM200 Setup software now prepares the MM300 to receive the new firmware file. While the file is being loaded into the MM300 a status box appears showing how much of the new firmware file has been transferred and the upgrade status. The entire transfer process takes approximately 10 minutes. 7. 8. The EnerVista MM300/MM200 Setup software will notify the user when the MM300 has finished loading the file. Carefully read any displayed messages and click OK to return the main screen. Cycling power to the relay is recommended after a firmware upgrade. After successfully updating the MM300 firmware, the relay will not be operational and will require setpoint programming. To communicate with the relay, the communication settings may have to be manually reprogrammed. When communications are established, the saved setpoints must be reloaded back into the relay. See Loading Setpoints from a File for details. Modbus addresses assigned to firmware modules, features, settings, and corresponding data items (i.e. default values, min/max values, data type, and item size) may change slightly from version to version of the firmware. Addresses are rearranged when new features are added or existing features are enhanced or modified. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 49 UPGRADING RELAY FIRMWARE 50 CHAPTER 2: INSTALLATION MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE GE Grid Solutions MM300 Motor Management System Chapter 3: Actual values Actual values Actual values overview Measured values, maintenance and fault analysis information are accessed in the actual values screens. Actual values may be accessed via one of the following methods. • Through the graphical control panel, using the keys and display. • With the EnerVista MM300 Setup software supplied with the relay. • Through the RS485 or Ethernet ports and a PLC/SCADA system running user-written software. Actual value messages are organized into logical groups, or pages, for easy reference. Pressing the Values soft-key displays the actual values summary window. A summary of metered current, voltage, and power values are shown for all three phases. Figure 3-1: Actual values summary window MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 51 ACTUAL VALUES OVERVIEW 52 CHAPTER 3: ACTUAL VALUES MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE GE Grid Solutions MM300 Motor Management System Chapter 4: Setpoints Setpoints Understanding setpoints Any of the motor trip and alarm setpoints may be viewed or altered by pressing the Setpoints soft-key. Setpoints data is divided into four pages. • Configuration page: Information about the motor configuration as well as system setup, inputs, outputs, communications, CTs, and VTs. • Protection page: Information about the protection features. • Control page: Information about the process control features. • Security page: Information about the security and password features. Press the Setpoint soft-key to scroll through the setpoints pages. When pressed for the first time, the following screen is displayed. Figure 4-1: Setpoints home page The soft-keys on the Home > Setpoints page open pages two levels down, since the pages immediately below this page are blank. For example, the Config soft-key opens the Home > Setpoints > Config > Motor page. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 53 CONFIGURATION SETPOINTS CHAPTER 4: SETPOINTS The pages containing setpoint fields, except for the inputs and outputs pages, are in a common format. This is a simple tabular format with two columns: setpoint name and units, and setpoint value. Setpoints for features that are not enabled are omitted from the page. Setpoints may be changed while the motor is running; however it is not recommended to change important protection parameters without first stopping the motor. CAUTION: Setpoints will remain stored indefinitely in the internal non-volatile memory even when control power to the unit is removed. Protection parameters are based on the entered data. This data must be complete and accurate for the given system for reliable protection and operation of the motor. Configuration setpoints The configuration setpoints contains data on motor configuration as well as system setup, inputs, outputs, communications, CTs, and VTs. The following sub-pages are available. • Motor (setpoints related to motor configuration). • CT-VT (setpoints related to CT and VT configuration). • Inputs (setpoints related to digital input configuration) • Outputs (setpoints related to digital output configuration) • Comms (setpoints related to communications configuration) • System (setpoints related to MM300 system configuration, such as the faceplate LEDs) • Events (setpoints related to the event recorder) • Counters (setpoints related to the digital counters) Motor setpoints The MM300 starter function is responsible for executing the motor startup sequence, including the pre-contactor start warning. The MM300 provides eight pre-defined starters. Full-voltage non-reversing • Full-voltage reversing • Two-speed • Wye-delta open transition • Inverter • Soft start • Autotransformer open transition • Autotransformer closed transition By selecting a pre-defined starter, inputs and outputs are automatically assigned. NOTE: NOTE 54 • Select the Home > Setpoints > Config > Motor page to edit the motor data settings. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 4: SETPOINTS CONFIGURATION SETPOINTS Figure 4-2: Motor data settings page Common motor setpoints Several motor setpoints are dependent on the chosen starter type. The setpoints shown below are common to all starter types. Motor Name Range: up to 20 alphanumeric characters Default: Motor Name This setpoint specifies a name for the motor. This name will appear in the actual values, sequence of events record, and other reports. Starter Type (Mandatory Setpoint) Range: None, FV Non-Reversing, FV Reversing, Two Speed, Wye-Delta, Inverter, Soft Starter, Autotr Open Trans, Autotr Closed Trans, Custom Starter Default: FV Non-Reversing This setpoint selects the starter type. The relay is essentially disabled when the value is set to “None”. The following figure illustrates typical starter timing beginning from the stopped state for all starter types. Motor FLA (Mandatory Setpoint) Range: 0.5 to 1000.0 amps in steps of 0.1 Default: OFF This setpoint must be specified for motor protection. The value may be taken from the motor nameplate data sheets. Motor Nameplate Voltage (Mandatory Setpoint) Range: 100 to 690 volts in steps of 1 Default: 690 volts This setpoint specifies the rated motor nameplate voltage. This value represents the base phase-to-phase voltage, and is used by the undervoltage and overvoltage protection elements. Supply Frequency (Mandatory Setpoint) Range: 50 Hz, 60 Hz Default: 60 Hz This setpoint specifies the nominal system frequency. Motor Rating (Mandatory Setpoint) Range: 0.3 to 1100.0 kW in steps of 0.1 or OFF Default: OFF This setpoint specifies the motor rating (or low speed motor rating for two-speed starters) in kWs. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 55 CONFIGURATION SETPOINTS CHAPTER 4: SETPOINTS Full Voltage Non-reversing Stop Start A Start B Start A Figure 4-3: Typical starter timing (1 of 2) Motor Current Contactor A Relay Contactor B Relay Pre-contactor P Starting Full Voltage Reversing Running Motor Current Contactor A Relay T T Contactor B Relay Pre-contactor P Starting Running Two Speed Starter Motor Current Contactor A Relay T Contactor B Relay Pre-contactor P Starting Running P - Pre-contactor Time setting T - Transfer Time setting R - Ramp Down Time setting Wye-Delta Starter Motor Current Contactor A Relay T Contactor B Relay Pre-contactor P Starting Inverter Starter and Soft Starter Running Motor Current Contactor A Relay 1s Contactor B Relay Pre-contactor P Starting Running Stopping R 853710A3.CDR 56 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 4: SETPOINTS CONFIGURATION SETPOINTS Autotransformer Closed Transition 1S-2S Stop Start A Start B Start A Autotransformer Open Transition 2S-1S Autotransformer Open Transition 1S-2S Figure 4-4: Typical starter timing (2 of 2) Motor current ~20 ms Contactor A relay Contactor C relay T Contactor B relay ~20 ms Pre-contactor P Starting Running Motor current ~20 ms Contactor A relay Contactor C relay T Contactor B relay ~20 ms Pre-contactor P Starting Running Motor current ~40 ms Contactor A relay ~40 ms Contactor C relay T Contactor B relay ~20 ms Pre-contactor P P - Pre-contactor Time setting T - Transfer Time setting R - Ramp Down Time setting Starting Running Autotransformer Closed Transition 2S-1S Motor current ~40 ms Contactor A relay ~40 ms Contactor C relay T Contactor B relay ~20 ms Pre-contactor P Starting Running 853856A1.CDR The following sections provide additional information for each starter type. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 57 CONFIGURATION SETPOINTS CHAPTER 4: SETPOINTS Current and voltage transformers Select the Home > Setpoints > Config > CT-VT page to edit the current and voltage transformer setpoints. Figure 4-5: Typical current and voltage transformer setpoints window The following setpoints are available to configure the current and voltage transformers. Phase CT Type (Mandatory Setpoint) Range: None, 1 A Secondary, 5 A Secondary, Direct Connect Default: Direct Connect This setpoint specifies the phase CT connection type. The “Direct Connect” value indicates that no phase CTs are used; instead, motor phase current passes directly through the relay. The “Direct Connect” selection should never be used where full load current is greater than 5.0 amps. If Direct Connect is selected and the FLA is set >5 A, a "FLA too high" message will be displayed on the Status page. NOTE: NOTE CT Primary (Mandatory Setpoint) Range: 5 to 1000 amps in steps of 1 Default: 5 amps This setpoint specifies the phase CT primary current. It should never be less than the full load current, and preferably no greater than twice than the full load current. Standard cut-off default is 20% (0.2pu) of CT primary. At CT primary less then 0.2pu, primary CT turns are required and an appropriate current cut-off setpoint. For example: using a 30:1 CT with 6A FLA gives 0.2A CT secondary @ FLA, the cut-off must be lowered to 0.1A and a minimum of 3 primary turns are required. This setpoint is displayed only if the phase CT type is set to 1 A secondary or 5 A secondary. NOTE: NOTE High Speed CT Primary Range: 5 to 1000 amps in steps of 1 Default: 5 amps This setpoint specifies the phase CT primary current when the motor is running at high speed. It should never be less than the high speed full load current, and preferably no greater than twice than the high speed full load current. This setpoint is displayed only if the phase CT type is set to 1 A secondary or 5 A secondary and the motor starter type is two-speed. NOTE: NOTE 58 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 4: SETPOINTS CONFIGURATION SETPOINTS Ground CT Type Range: None, Residual, CBCT 2000:1 Default: CBCT 2000:1 This setpoint specifies the type of ground CT. Select "Residual" if the fourth CT Input on the IO_A is connected to the residual of the Phase CT. Select 2000:1 if a zero sequence CT (CBCT) is connected to the ground input on the CPU card. CT Primary Turns Range: 1 to 10 Default: 1 For smaller motors where the drawn current is very low, the motor leads may be wrapped through the CT Primary with several turns thereby increasing the current seen by the MM300 and as a result increasing the accuracy of the measurement. The value of this setting should equal the number of turns on the CT Primary to display the correct current value. Internally the current measurement will be divided by this setting. Standard cut-off default is 20% (0.2pu) of CT primary. At CT primary less then 0.2pu, primary CT turns are required and an appropriate current cut-off setpoint. For example: using a 30:1 CT with 6A FLA gives 0.2A CT secondary @ FLA, the cut-off must be lowered to 0.1A and a minimum of 3 primary turns are recommended. Three Phase Voltage Connection Range: Wye, Delta Default: Wye The method in which the IO_B voltage inputs are connected must be entered here. Note that phase reversal is disabled for single VT operation. All voltages are assumed balanced. Auxiliary Voltage Connection (Mandatory Setpoint) Range: VabVT, VbcVT, VcaVT, VanVT, VbnVT, VcnVT, VanDirect, VbnDirect, VcnDirect Default: Vab VT This setpoint specifies the control transformer connection to the motor supply voltage. Auxiliary VT Primary Range: 110 to 690 volts in steps of 1 Default: 415 volts This setpoint specifies the primary voltage rating of the control transformer. Auxiliary VT Secondary Range: 110 to 300 volts in steps of 1 Default: 110 volts This setpoint specifies the secondary voltage rating of the control transformer. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 59 CONFIGURATION SETPOINTS 60 CHAPTER 4: SETPOINTS MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE GE Grid Solutions MM300 Motor Management System Chapter 5: Protection elements Protection elements Thermal protection The primary protective function of the MM300 is the thermal model. The MM300 integrates stator and rotor heating into a single model. The rate of motor heating is gauged by measuring the terminal currents. The present value of the accumulated motor heating is maintained in the Thermal Capacity Used actual value register. When the motor is in overload, the motor temperature and thermal capacity used will rise. A trip occurs when the thermal capacity used reaches 100%. When the motor is stopped and is cooling to ambient, the thermal capacity used decays to zero. If the motor is running normally, the motor temperature will eventually stabilize at some steady state temperature, and the thermal capacity used increases or decreases to some corresponding intermediate value, which accounts for the reduced amount of thermal capacity left to accommodate transient overloads. The thermal model consists of six key elements. • Unbalance current biasing that accounts for negative-sequence heating. • Hot/cold biasing that accounts for normal temperature rise. • RTD biasing that accounts for ambient variation and cooling problems • An overload curve that accounts for the rapid heating that occurs during stall, acceleration, and overload. • Cooling rate that accounts for heat dissipation. • Thermal protection reset that controls recovery from thermal trips and lockouts. Each of these categories are described in the following sub-sections. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 61 THERMAL PROTECTION CHAPTER 5: PROTECTION ELEMENTS Overload curve The overload curve accounts for the rapid motor heating that occurs during stall, acceleration, and overload. Specifically, the overload curve controls the rate of increase of Thermal Capacity Used whenever the equivalent motor heating current is greater than 1.01 times the full load current setpoint. The curve is defined by the following equation and reflects that overload heating largely swamps the cooling, and this heating is primarily due to resistive losses in the stator and the rotor windings (said losses being proportional to the square of the current). Trip time = Curve Multiplier ´ 2.2116623 2 0.02530337 x (Pickup - 1) + 0.05054758 x (Pickup -1) Eq. 1 In the above equation, • The trip time represents the time (in seconds) for the MM300 to trip, given the motor starts cold and the current is constant. • The multiplier represents the value of the Curve Multiplier setpoint. This setpoint can be used to adjust the curve to match the thermal characteristics of the motor. • Ieq represents the equivalent motor heating current in per-unit values on a full load current base. The value of Ieq is limited in this equation to 8.0 to prevent the overload from acting as an instantaneous element and responding to short circuits. Equivalent motor heating current is discussed in the Unbalance biasing section. For example, a motor with a stall current (also known as locked rotor current) of 8 times its FLA, with a curve multiplier of 7, if stalled from a cold state, trips in the following amount of time. Eq. 2 This would respect a safe stall cold time of 10 seconds. The standard overload curves are displayed below. 62 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 5: PROTECTION ELEMENTS THERMAL PROTECTION Figure 5-1: Standard overload curves STANDARD OVERLOAD CURVES TIME IN SECONDS 1000 100 x15 10 x1 1.00 0.10 1.00 10 100 MULTIPLE OF FULL LOAD AMPS 853731A3.CDR The trip times for the standard overload curves are tabulated below. Table 5-1: Standard overload curve trip times (in seconds) PICKUP STANDARD CURVE MULTIPLIERS (× FLA) ×1 ×2 ×3 ×4 ×5 ×6 ×7 ×8 ×9 × 10 × 11 × 12 × 13 × 14 × 15 1.01 4353.6 8707.2 13061 17414 21768 26122 30475 34829 39183 43536 47890 52243 56597 60951 65304 1.05 853.71 1707.4 2561.1 3414.9 4268.6 5122.3 5976.0 6829.7 7683.4 8537.1 9390.8 10245 11098 11952 12806 1.10 416.68 833.36 1250.0 1666.7 2083.4 2500.1 2916.8 3333.5 3750.1 4166.8 4583.5 5000.2 5416.9 5833.6 6250.2 1.20 198.86 397.72 596.58 795.44 994.30 1193.2 1392.0 1590.9 1789.7 1988.6 2187.5 2386.3 2585.2 2784.1 2982.9 1.30 126.80 253.61 380.41 507.22 634.02 760.82 887.63 1014.4 1141.2 1268.0 1394.8 1521.6 1648.5 1775.3 1902.1 1.40 91.14 182.27 273.41 364.55 455.68 546.82 637.96 729.09 820.23 911.37 1002.5 1093.6 1184.8 1275.9 1367.0 1.50 69.99 139.98 209.97 279.96 349.95 419.94 489.93 559.92 629.91 699.90 769.89 839.88 909.87 979.86 1049.9 1.75 42.41 84.83 127.24 169.66 212.07 254.49 296.90 339.32 381.73 424.15 466.56 508.98 551.39 593.81 636.22 2.00 29.16 58.32 87.47 116.63 145.79 174.95 204.11 233.26 262.42 291.58 320.74 349.90 379.05 408.21 437.37 2.25 21.53 43.06 64.59 86.12 107.65 129.18 150.72 172.25 193.78 215.31 236.84 258.37 279.90 301.43 322.96 2.50 16.66 33.32 49.98 66.64 83.30 99.96 116.62 133.28 149.94 166.60 183.26 199.92 216.58 233.24 249.90 2.75 13.33 26.65 39.98 53.31 66.64 79.96 93.29 106.62 119.95 133.27 146.60 159.93 173.25 186.58 199.91 3.00 10.93 21.86 32.80 43.73 54.66 65.59 76.52 87.46 98.39 109.32 120.25 131.19 142.12 153.05 163.98 3.25 9.15 18.29 27.44 36.58 45.73 54.87 64.02 73.16 82.31 91.46 100.60 109.75 118.89 128.04 137.18 3.50 7.77 15.55 23.32 31.09 38.87 46.64 54.41 62.19 69.96 77.73 85.51 93.28 101.05 108.83 116.60 3.75 6.69 13.39 20.08 26.78 33.47 40.17 46.86 53.56 60.25 66.95 73.64 80.34 87.03 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 93.73 100.42 63 THERMAL PROTECTION CHAPTER 5: PROTECTION ELEMENTS PICKUP STANDARD CURVE MULTIPLIERS (× FLA) ×1 ×2 ×3 ×4 ×5 ×6 ×7 ×8 ×9 × 10 × 11 × 12 × 13 × 14 × 15 4.00 5.83 11.66 17.49 23.32 29.15 34.98 40.81 46.64 52.47 58.30 64.13 69.96 75.79 81.62 87.45 4.25 5.12 10.25 15.37 20.50 25.62 30.75 35.87 41.00 46.12 51.25 56.37 61.50 66.62 71.75 76.87 4.50 4.54 9.08 13.63 18.17 22.71 27.25 31.80 36.34 40.88 45.42 49.97 54.51 59.05 63.59 68.14 4.75 4.06 8.11 12.17 16.22 20.28 24.33 28.39 32.44 36.50 40.55 44.61 48.66 52.72 56.77 60.83 5.00 3.64 7.29 10.93 14.57 18.22 21.86 25.50 29.15 32.79 36.43 40.08 43.72 47.36 51.01 54.65 5.50 2.99 5.98 8.97 11.96 14.95 17.94 20.93 23.91 26.90 29.89 32.88 35.87 38.86 41.85 44.84 6.00 2.50 5.00 7.49 9.99 12.49 14.99 17.49 19.99 22.48 24.98 27.48 29.98 32.48 34.97 37.47 6.50 2.12 4.24 6.36 8.48 10.60 12.72 14.84 16.96 19.08 21.20 23.32 25.44 27.55 29.67 31.79 7.00 1.82 3.64 5.46 7.29 9.11 10.93 12.75 14.57 16.39 18.21 20.04 21.86 23.68 25.50 27.32 7.50 1.58 3.16 4.75 6.33 7.91 9.49 11.08 12.66 14.24 15.82 17.41 18.99 20.57 22.15 23.74 8.00 1.39 2.78 4.16 5.55 6.94 8.33 9.71 11.10 12.49 13.88 15.27 16.65 18.04 19.43 20.82 The following tables illustrate the relation between GE Multilin MM2 and MM3 curve numbers, NEMA curves, and the MM300 curve multipliers. Table 5-2: MM2 and MM3 curve numbers and MM300 curve multipliers MM2 and MM3 curve number 1 2 3 4 5 6 7 8 MM300 curve multiplier 1 2 3 4 7 9 12 15 Table 5-3: NEMA curves and MM300 curve multipliers 64 NEMA curve Class 10 Class 15 Class 20 Class 30 MM300 curve multiplier 4 6 8 12 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE GE Grid Solutions MM300 Motor Management System Chapter 6: Communications Communications Communications interfaces The MM300 has three communications interfaces. These can be used simultaneously: • RS485 • 10/100Base-T Ethernet • Fieldbus Setpoint changes related to DeviceNet, Profibus, and Ethernet, require a power cycle to be activated. NOTE: NOTE External power must be present on the Fieldbus port at power-up, in order to correctly initialize and operate. NOTE: NOTE For full details, please refer to the MM300 Communications Guide, to be found on the GE Multilin web site. NOTE: NOTE MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 65 COMMUNICATIONS INTERFACES 66 CHAPTER 6: COMMUNICATIONS MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE GE Grid Solutions MM300 Motor Management System Chapter 7: Specifications Specifications Specifications are subject to change without notice. NOTE: NOTE Protection specifications ACCELERATION TIMER Pickup:......................................................................Iav > Ipu Dropout: ..................................................................Iav < Ipu or timer expired Time delay: ............................................................ 0.5 to 250.0 seconds in steps of 0.1 Timing accuracy: ................................................ ±500 ms or 1.5% of total time Elements: ................................................................ trip and alarm AUXILIARY UNDERVOLTAGE Pickup level: ........................................................... 60 to 90% of NCV Time delay: ............................................................ 1 to 60 seconds in steps of 1 Timing accuracy: ................................................ ± 500 ms Elements: ................................................................ trip and alarm CURRENT UNBALANCE Range: ...................................................................... 4 to 40% in steps of 1 Accuracy:................................................................ ±2% Time delay: ............................................................ 1 to 60 seconds in steps of 1 s Timing accuracy: ................................................ ±500 ms Elements: ................................................................ trip and alarm CALCULATION METHOD If IAV ≥ IFLA: ( [IM - IAV] /IAV ) x 100% If IAV ≤ IFLA: ( [IM - IAV] /IFLA ) x 100% Where: IAV = average phase current IM = current in a phase with maximum deviation from IAV IFLA = MOTOR FULL LOAD CURRENT setpoint MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 67 PROTECTION SPECIFICATIONS CHAPTER 7: SPECIFICATIONS FUSE FAILURE (RUNNING STATE ONLY) Timing:..................................................................... 1 s ± 0.1 s Elements: ................................................................ trip and alarm GROUND FAULT (CBCT OR RESIDUAL) Pickup level:........................................................... 0.5 to 15.0 A in steps of 0.1 (CBCT); 10 to 100% of FLA in steps of 1% (residual) Trip time delay on start: .................................. 0 to 10 s in steps of 0.1 s Trip time delay on run:..................................... 0 to 5 s in steps of 0.1 s Alarm time delay on start/run:..................... 0 to 60 s in steps of 1 s Timing accuracy:................................................ ±50 ms or ±0.5% of total time Elements: ................................................................ trip and alarm LOAD INCREASE Pickup level:........................................................... 50 to 150% of FLA in steps of 1% Timing accuracy:................................................ ±500 ms Elements: ................................................................ Alarm MECHANICAL JAM Pickup level:........................................................... 1.01 to 4.50 × FLA in steps of 0.01 Time delay:............................................................ 0.1 to 30.0 seconds in steps of 0.1 Timing accuracy:................................................ ±500 ms Elements: ................................................................ trip PHASE OVERVOLTAGE Pickup level:........................................................... 101 to 120% of rated in steps of 1% Time delay:............................................................ 1 to 60 seconds in steps of 1 s Timing accuracy:................................................ ±500 ms Elements: ................................................................ trip and alarm PHASE UNDERVOLTAGE Pickup level:........................................................... 60 to 99% of rated in steps of 1 Time delay:............................................................ 1 to 60 seconds in steps of 1 s Timing accuracy:................................................ ±500 ms Elements: ................................................................ trip and alarm RTD PROTECTION RTD types: .............................................................. three-wire (100 ohm Platinum) Range:...................................................................... –50 to 250°C in steps of 1 Hysteresis: ............................................................. 2°C THERMAL MODEL Standard curve time multiplier: ................... 1 to 15 in steps of 1 Thermal overload pickup: ............................... 1.01 to 1.25 in steps of 0.01 Motor full load current (FLA): ......................... 0.5 to 1000 A in steps of 0.1 Motor rated voltage: ......................................... 100 to 690 V AC Curve biasing:....................................................... phase unbalance (±5%) hot/cold ratio stator RTD exponential running and stopped cooling rates Update rate:.......................................................... 3 cycles Hot/cold safe stall ratio: .................................. 1 to 100% in steps of 1% Timing accuracy:................................................ ±200 ms or ±2% of total time (based on measured value) Elements: ................................................................ trip and alarm THERMISTOR Sensor types:........................................................ PTC (RHOT = 100 to 30 kohms); NTC (RHOT = 100 to 30 kohms) Timing accuracy:................................................ ±500 ms Elements: ................................................................ Trip and alarm 68 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 7: SPECIFICATIONS USER INTERFACE SPECIFICATIONS UNDERCURRENT Pickup level: ........................................................... 1 to 100% of FLA in steps of 1 Time delay: ............................................................ 1 to 60 seconds in steps of 1 Timing accuracy: ................................................ ±500 ms Elements: ................................................................ trip and alarm UNDERPOWER Pickup level: ........................................................... 1 to 100% of kW rating in steps of 1 Time delay: ............................................................ 1 to 60 seconds in steps of 1 Timing accuracy: ................................................ ±500 ms Elements: ................................................................ trip and alarm VOLTAGE PHASE REVERSAL Configuration:....................................................... ABC or Rev starter Timing accuracy: ................................................ ±500 ms Elements: ................................................................ trip or alarm User interface specifications GRAPHICAL CONTROL PANEL AND HAND HELD DEVICE Size: ........................................................................... width 153mm, height 102mm, depth 35mm LCD: ........................................................................... 3.5-inch color, 320 by 240 pixels LED indicators: ..................................................... 10 LEDs Pushbuttons: ......................................................... Start A, Start B, Stop, plus 11 LCD screen display control keys Ports:......................................................................... USB 2.0 port for laptop computer connection Cable - GCP to Base Unit:................................ Shielded RJ45; Maximum length 6’ (1.83 m) BASIC CONTROL PANEL Size: ........................................................................... BCP: width 75mm, height 75mm, depth 31mm LCD: ........................................................................... 3.5-inch color, 320 by 240 pixels LED indicators: ..................................................... 12 LEDs Pushbuttons: ......................................................... Start A, Start B, Stop, Reset, Auto, Manual Cable - BCP to Base Unit: ................................ Shielded RJ45; Maximum length 6’ (1.83 m) Metering and monitoring specifications EVENT RECORDER Capacity:................................................................. 256 events Data storage: ........................................................ non-volatile memory FREQUENCY METERING Range: ...................................................................... 40.00 to 70.00 Hz in steps of 0.01 Accuracy:................................................................ ±0.05 Hz POWER METERING Real power range: .............................................. –2000.0 to 2000.0 kW in steps of 0.1 Apparent power range:.................................... 0.0 to 2500.0 kVA in steps of 0.1 Accuracy:................................................................ ±1% of full scale POWER FACTOR METERING Range: ...................................................................... –0.99 to +0.99 in steps of 0.01 Accuracy:................................................................ ±0.05 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 69 CONTROL SPECIFICATIONS CHAPTER 7: SPECIFICATIONS Control specifications UNDERVOLTAGE RESTART Dropout/Pickup Level: ...................................... 60 to 100% NCV in steps of 1% Short Dip Time: .................................................... 100 to 500 ms or OFF in steps of 10 ms Medium Dip Time: .............................................. 0.1 to 10.0 s in steps of 0.1 s Medium Dip Delay: ............................................ 0.2 to 90 s in steps of 0.2 s Long Dip Time:..................................................... 0.5 to 60.0 min or OFF in steps of 0.5 min Long Dip Delay: ................................................... 1.0 to 1200.0 s in steps of 1.0 s Short Dip Time Accuracy:............................... ±5% of total time Medium and Long Dip Time Accuracy:.... ±1 s or ±5% of total time, whichever is greater Inputs specifications AUXILIARY VOLTAGE INPUT (UNDERVOLTAGE RESTART SOURCE) External VT primary: ......................................... 110 to 690 V AC in steps of 1 (if used) Input range:........................................................... 60 to 300 V AC Nominal frequency:........................................... 50 or 60 Hz Accuracy: ............................................................... ±5% of reading DIGITAL INPUTS (IO_C MODULE) Fixed pickup: ......................................................... 65 V AC Recognition time:................................................ 2 cycles Current draw at rated voltage: .................... 75 mA @ 120 V AC for 200 µs every cycle 60 mA @ 240 V AC for 800 µs every cycle Input impedence:................................................ 1.7 kΩ Type: ......................................................................... opto-isolated inputs External switch: ................................................... wet contact Maximum input voltage: ................................. 300 V AC DIGITAL INPUTS (IO_E MODULE) Fixed pickup: ......................................................... 20 V DC Recognition time:................................................ 2 cycles Current draw at rated voltage: .................... 7 mA @ 24 V DC 14 mA @ 48 V DC Input impedence:................................................ 1.23 kΩ Type: ......................................................................... opto-isolated inputs External switch: ................................................... wet contact Maximum input voltage: ................................. 60 V DC GROUND CURRENT INPUT (50:0.025) CT primary: ............................................................ 0.5 to 15.0 A Nominal frequency:........................................... 50 or 60 Hz Accuracy (CBCT):................................................. ±0.1 A (0.5 to 3.99 A) ±0.2 A (4.0 A to 15 A) Burden: .................................................................... <8.6 mVA at 25 A 70 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 7: SPECIFICATIONS OUTPUTS SPECIFICATIONS PHASE CURRENT INPUTS (INCLUDING RESIDUAL GROUND CURRENT) Range: ...................................................................... 0.2 to 40 A (8 × CT), direct connection up to 5 A FLA Input type:.............................................................. Combined 1 A / 5 A Frequency: ............................................................. 50 or 60 Hz Accuracy:................................................................ ExtCT: ±2% of reading or ±1% of 8× CTPrimary, whichever is greater Direct: ±2% of reading or ±0.1 A, whichever is greater Withstand (at 5A nominal): ............................. 0.2 s at 100× 1.0 s at 50× 2.0 s at 40× continuous at 3× rated current Burden: .................................................................... <4 mVA at 1A <0.1 VA at 5 A PHASE VOLTAGE INPUTS (THREE-PHASE VOLTAGE) Input range: ........................................................... 208 to 690 V Nominal frequency: ........................................... 50 or 60 Hz Accuracy:................................................................ ±2% of reading, or ±1 V, whichever is greater RTD INPUTS Sensor type: .......................................................... Three-wire RTD (100 ohm Platinum) Sensing current:................................................... 5 mA Accuracy:................................................................ ±3°C THERMISTOR INPUTS Sensor type: .......................................................... Positive temperature coefficient PTC (RHOT =100 to 30000 ohms), negative temperature coefficient NTC(RHOT = 100 to 30000 ohms) Accuracy:................................................................ ±6% of reading or ±100 ohms, whichever is greater Outputs specifications OUTPUT RELAYS Configuration:....................................................... electromechanical form-A (IO_C) and form-C (IO_D) Contact material: ................................................ silver-alloy Operate time:........................................................ 10 ms Minimum contact load: .................................... 10 mA at 5 V DC Maximum switching rate: ............................... 300 operations per minute (no load), 30 operations per minute (load) Mechanical life:.................................................... 10 000 000 operations Continuous current:........................................... 10 A Make and carry for 0.2s:.................................. 30 A per ANSI C37.90 OUTPUT RELAY BREAK CAPACITY (FORM-A RELAY) AC resistive, 120 V AC:....................................... 10 A AC resistive, 240 V AC:....................................... 10 A AC inductive, PF = 0.4 pilot duty:.................. 2 A DC resistive, 30 V DC: ........................................ 10 A OUTPUT RELAY BREAK CAPACITY (FORM-C RELAY) AC resistive, 120 V AC:....................................... 10 A normally-open, 5 A normally-closed AC resistive, 240 V AC:....................................... 10 A normally-open, 8 A normally-closed AC inductive, PF = 0.4 pilot duty:.................. 2.5 A DC resistive, 30 V DC: ........................................ 10 A MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 71 POWER SUPPLY SPECIFICATIONS CHAPTER 7: SPECIFICATIONS Power supply specifications POWER SUPPLY (HIGH PSU) Nominal:.................................................................. 120 to 240 V AC 125 to 250 V DC Range:...................................................................... 60 to 300 V AC (50 and 60 Hz) 84 to 250 V DC Ride-Through:....................................................... 35 ms POWER SUPPLY (LOW PSU) Nominal:.................................................................. 24 to 48 V DC Range:...................................................................... 20 to 60 V DC Ride-Through:....................................................... 35 ms ALL RANGES Voltage withstand: ............................................. 2 × highest nominal voltage for 10 ms Power consumption: ......................................... 16 W typical, 25 W maximum Communications specifications DEVICENET (COPPER) Modes: ..................................................................... slave (125, 250, and 500 kbps) Connector: ............................................................. 5-pin terminal Current Draw:....................................................... 80 mA @ 24 VDC ETHERNET (COPPER) Modes: ..................................................................... 10/100 MB (auto-detect) Connector: ............................................................. RJ-45 SNTP clock synchronization error:.............. <200 ms (typical) Protocol:.................................................................. Modbus TCP PROFIBUS (COPPER) Modes: ..................................................................... DPV0 slave, up to 1.5 Mbps DPV1 slave, up to 1.5 Mbps Connector: ............................................................. 5-pin terminal RS485 PORT Port:........................................................................... opto-isolated Baud rates: ............................................................ up to 115 kbps Protocol:.................................................................. Modbus RTU, half-duplex Maximum distance: ........................................... 1200 m Isolation: ................................................................. 2 kV USB PORT (GRAPHIC CONTROL PANEL ONLY) Standard specification:.................................... Compliant with both USB 2.0 and USB 1.1 Data transfer rate: ............................................. USB device emulating serial communications port at 115 kbps 72 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE CHAPTER 7: SPECIFICATIONS TESTING AND CERTIFICATION Testing and certification TESTING AND CERTIFICATION Test Reference Standard Test Level Dielectric Voltage Withstand: EN60255-5 2.3KV (1 minute) Impulse Voltage Withstand: EN60255-5 5KV Damped Oscillatory: IEC61000-4-18IEC60255-22-1 2.5KV CM, 1KV DM Electrostatic Discharge: EN61000-4-2/IEC60255-22-2 Level 4 RF Immunity: EN61000-4-3/IEC60255-22-3 Level 3 Fast Transient Disturbance: EN61000-4-4/IEC60255-22-4 Class A Surge Immunity: EN61000-4-5/IEC60255-22-5 Level 3 Conducted RF Immunity: EN61000-4-6/IEC60255-22-6 Level 3 Voltage Interruption and Ripple DC: IEC60255-11 15% ripple , 200ms interupts Radiated & Conducted Emissions: CISPR11 /CISPR22/ IEC60255-25 Class A Sinusoidal Vibration: IEC60255-21-1 Class 1 Shock & Bump: IEC60255-21-2 Class 1 Power magnetic Immunity: IEC61000-4-8 Level 5 Pulse Magnetic Immunity: IEC61000-4-9 Level 4 Voltage Dip & Interruption: IEC61000-4-11 0,40,70% dips,250/300cycle interrupts Damped Oscillatory: IEC61000-4-12 2.5KV CM, 1KV DM Harmonics & Interharmonics: IEC61000-4-13 Class 3 Voltage Ripple: IEC61000-4-17 15% ripple Ingress Protection: IEC60529 IP20 (base unit) , IP54 (Control Panel) Environmental (Cold): IEC60068-2-1 -25oC 16 hrs Environmental (Dry heat): IEC60068-2-2 70oC 16hrs Relative Humidity Cyclic: IEC60068-2-30 6-day variant 2 APPROVALS Applicable Council Directive CE compliance: North America: According to Low voltage directive EN60255-5, EN61010-1 EMC Directive EN50263 / EN61000-6-2/ EN61000-6-4 cULus UL1053 [e83849 NKCR] UL508 [e83849 NKCR] C22.2-14 [e83849 NKCR7] EAC Machines and Equipment TR CU 010/2011 ISO: Manufactured under a registered quality program ISO9001 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 73 PHYSICAL SPECIFICATIONS CHAPTER 7: SPECIFICATIONS EAC The EAC Technical Regulations (TR) for Machines and Equipment apply to the Customs Union (CU) of the Russian Federation, Belarus, and Kazakhstan Item Description Country of origin Spain or Canada; see label on the unit Date of manufacture See label on the MM300 unit Declaration of Conformity and/or Certificate of Conformity Available on request Physical specifications DIMENSIONS Size: ........................................................................... Base: 120 mm (W) × 90 mm (H) × 113 mm (D) [+ terminals 10mm] Expansion: 62 mm (W) × 90 mm (H) × 113 mm (D) GCP: 153 mm (W) × 102 mm (H) × 35 mm (D) BCP: 75 mm (W) × 75 mm (H) × 31 mm (D) Weight (Base):....................................................... 0.75 kg Environmental specifications ENVIRONMENTAL SPECIFICATIONS Ambient temperatures: Storage/shipping: - 40oC to 90oC * Operating: -20oC to 60oC * * 1" around Base Unit Humidity: Operating up to 95% (non condensing) @ 55oC (As per IEC60068-2-30 Variant 2, 6days) Altitude: 2000m (max) Overvoltage Category: II Ingress Protection: IP20 (Base Unit) IP54 (Control Panel) Environmental rating: 60oC surrounding air Pollution Degree: II Noise: 0 dB Type 1 (panel mount versions only) 74 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE GE Grid Solutions MM300 Motor Management System Chapter 8: MM300 order codes MM300 order codes The information to specify an MM300 relay is provided in the following order code figure. Figure 8-1: MM300 order codes MM300 * Interface MM300 | Control X panel B G Power supply Communications Options Protection Input/output modules Base E * | | | | H L * | | | | | | S D P * | | | | | | | | | S 1 2 3 * | | | | | | | | | | | | | | | | | C E A Expanded * * * | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | X X X | | | B | | | G G G G C C C C E E E E D D D D * | | | | | | | | | | | | | X MM300 Motor Management System No control panel Basic control panel, no USB Graphical control panel with USB High: 80 to 250 V DC (Standard); 60 to 300 V AC Low*: 24 V DC (24 to 48 V DC Nominal) Standard communications: RS485 Modbus RTU Standard plus DeviceNet Slave and 10/100 Modbus TCP Standard plus Profibus DP Slave and 10/100 Modbus TCP Standard: Starter control and event recorder Option 1: Standard plus undervoltage autorestart Option 2: Option 1 plus waveform capture and data logger Option 3: Option 2 plus FlexLogic No Additional Protection Three-phase voltage metering and three-phase underpower, undervoltage, overvoltage, phase reversal Bank of three (3) RTDs: 100PT (maximum of 2 banks) Two (2) 10 A form-A relays and six (6) 60 to 300 V AC digital Inputs Two (2) 10 A form-A relays and six (6) 20 to 60 V DC digital Inputs Four (4) 10 A form-C relays 853702A4.PDF NOTES: * The UV Restart feature is not supported with the Low-Voltage power supply option. Harsh Environment Coating is a standard feature on all MM300 units. MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE 75 EXAMPLE OF AN MM300 ORDER CODE CHAPTER 8: MM300 ORDER CODES Example of an MM300 order code MM300-GEHS1CAXXXX: MM300 with graphical control panel and USB port, English language display, high voltage 84 to 250 V DC and 60 to 300 V AC power supply, RS485 Modbus RTU communications, starter control, event recorder, undervoltage autorestart, three-phase current, thermal overload, undercurrent, single phase underpower, two 10 A form-A contact output relays, and six digital inputs. 76 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE ">
Download
Advertisement
Key features
Modular design for flexible protection and control
Small footprint suitable for IEC/NEMA MCC
Integrated pushbuttons and LED indicators
Multiple communication protocols (RS485, Ethernet, Profibus, DeviceNet)
Optional control panels for local access
Automation FlexLogic for complex logic control
Frequently asked questions
The MM300 is a modular motor management system designed for low-voltage motor protection and control, providing flexible options for protection, control, and communication.
The MM300 can contain up to eight modules (four in the base unit, four in the expansion unit).
The MM300 supports RS485 (Modbus RTU), Ethernet (Modbus TCP/IP), Profibus, and DeviceNet.
Yes, the MM300 supports DIN rail mounting, conforming to EN 50022.