Motion Control Engineering, Inc.
11380 White Rock Road
Rancho Cordova, CA 95742
voice 916 463 9200 fax 916 463 9201 www.mceinc.com
Motion 4000 Traction Elevator Controller
V9.xx software
Manual # 42-02-2P25, Rev A6, February 2016
Copyright
© 2016, Motion Control Engineering. All Rights Reserved.
This document may not be reproduced, electronically or mechanically, in whole or in part, without written permission from Motion Control Engineering.
Trademarks
All trademarks or registered product names appearing in this document are the exclusive property of the respective owners.
Warning and Disclaimer
Although every effort has been made to make this document as complete and accurate as possible,
Motion Control Engineering and the document authors, publishers, distributors, and representatives have neither liability nor responsibility for any loss or damage arising from information contained in this document or from informational errors or omissions. Information contained in this document shall not be deemed to constitute a commitment to provide service, equipment, or software by Motion Control Engineering or the document authors, publishers, distributors, or representatives.
Limited Warranty
Motion Control Engineering (manufacturer) warrants its products for a period of 15 months from the date of shipment from its factory to be free from defects in workmanship and materials. Any defect appearing more than 15 months from the date of shipment from the factory shall be deemed to be due to ordinary wear and tear. Manufacturer, however, assumes no risk or liability for results of the use of the products purchased from it, including, but without limiting the generality of the forgoing: (1) The use in combination with any electrical or electronic components, circuits, systems, assemblies or any other material or equipment (2) Unsuitability of this product for use in any circuit, assembly or environment. Purchasers’ rights under this warranty shall consist solely of requiring the manufacturer to repair, or in manufacturer's sole discretion, replace free of charge,
F.O.B. factory, any defective items received at said factory within the said 15 months and determined by manufacturer to be defective. The giving of or failure to give any advice or recommendation by manufacturer shall not constitute any warranty by or impose any liability upon the manufacturer. This warranty constitutes the sole and exclusive remedy of the purchaser and the exclusive liability of the manufacturer, AND IN LIEU OF ANY AND ALL OTHER WARRANTIES,
EXPRESSED, IMPLIED, OR STATUTORY AS TO MERCHANTABILITY, FITNESS, FOR PURPOSE SOLD,
DESCRIPTION, QUALITY PRODUCTIVENESS OR ANY OTHER MATTER. In no event will the manufacturer be liable for special or consequential damages or for delay in performance of this warranty.
Products that are not manufactured by MCE (such as drives, CRTs, modems, printers, etc.) are not covered under the above warranty terms. MCE, however, extends the same warranty terms that the original manufacturer of such equipment provide with their product (refer to the warranty terms for such products in their respective manual).
End User License Agreement
This End User License Agreement (“Agreement”) grants you the right to use the software contained in this product (the “Software”) subject to the following restrictions: You may not: (i) copy the Software, except for archive purposes consistent with your standard archive procedures; (ii) transfer the Software to a third party apart from the entire product; (iii) modify, decompile, disassemble, reverse engineer or otherwise attempt to derive the source code of the Software; (iv) export the Software or underlying technology in contravention of applicable U.S. and foreign export laws and regulations; and (v) use the Software other than in connection with operation of the product.
“LICENSOR'S SUPPLIERS DO NOT MAKE OR PASS ON TO END USER OR ANY OTHER THIRD PARTY,
ANY EXPRESS, IMPLIED OR STATUTORY WARRANTY OR REPRESENTATION ON BEHALF OF SUCH
SUPPLIERS, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF NON-INFRINGE-
MENT, TITLE, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.”
Important Precautions and Useful Information
This preface contains information that will help you understand and safely maintain MCE equipment. We strongly recommend you review this preface and read this manual before installing, adjusting, or maintaining Motion Control Engineering equipment. This preface discusses:
• Safety and Other Symbol Meanings
• Safety Precautions
• Environmental Considerations
• In This Guide
Safety and Other Symbol Meanings
Danger
This manual symbol is used to alert you to procedures, instructions, or situations which, if not done properly, might result in personal injury or substantial equipment damage.
Caution
This manual symbol is used to alert you to procedures, instructions, or situations which, if not done properly, might result in equipment damage.
Note
This manual symbol is used to alert you to instructions or other immediately helpful information.
Safety Precautions
Danger
This equipment is designed to comply with ASME A17.1, National Electrical Code, CE, and CAN/
CSA-B44.1/ASME-A17.5 and must be installed by a qualified contractor. It is the responsibility of the contractor to make sure that the final installation complies with all local codes and is installed in a safe manner.
This equipment is suitable for use on a circuit capable of delivering not more than 10,000 rms symmetrical amperes, 600 volts maximum. The three-phase AC power supply to the Drive Isolation
Transformer used with this equipment must originate from a fused disconnect switch or circuit breaker sized in conformance to all applicable national, state, and local electrical codes in order to provide the necessary motor branch circuit protection for the Drive Unit and motor. Incorrect motor branch circuit protection will void the warranty and may create a hazardous condition.
Proper grounding is vitally important to safe and successful operation. Bring your ground wire to the system subplate. You must choose the proper conductor size and minimize the resistance to ground by using the shortest possible routing. See National Electrical Code Article 250 or the applicable local electrical code.
Before applying power to the controller, physically check all the power resistors and other components located in the resistor cabinet and inside the controller. Components loosened during shipment may cause damage.
For proper operation of the AC Drive Unit in your controller, you must make sure that: 1) A direct solid ground is provided in the machine room to properly ground the controller and motor. Indirect grounds such as the building structure or a water pipe may not provide proper grounding and could act as an antenna to radiate RFI noise, thus disturbing sensitive equipment in the building. Improper grounding may also render any RFI filter ineffective. 2) The incoming power to the controller and the outgoing power wires to the motor are in their respective, separate, grounded conduits.
This equipment may contain voltages as high as 1000 volts. Use extreme caution. Do not touch any components, resistors, circuit boards, power devices, or electrical connections without ensuring that high voltage is not present.
Environmental Considerations
• Keep the machine room clean.
• Controllers are generally in NEMA 1 enclosures.
• Do not install the controller in a dusty area.
• Do not install the controller in a carpeted area.
• Keep room temperature between 32 and 104 degrees F (0 to 40 degrees C).
• Prevent condensation on the equipment.
• Do not install the controller in a hazardous location or where excessive amounts of vapors or chemical fumes may be present.
• Make certain that power line fluctuations are within plus or minus 10% of proper value.
Air Conditioned Equipment Cabinets
If your control or group enclosure is equipped with an air conditioning unit, it is very important to observe the following precautions. (Failure to do so can result in moisture damage to electrical components.)
• Maintain the integrity of the cabinet by using sealed knockouts and sealing any holes made during installation.
• Do not run the air conditioning while the cabinet doors are open.
• If you turn the air conditioner off while it is running, wait at least five minutes before restarting it. Otherwise, the compressor may be damaged.
• Observe the recommended thermostat setting (75 degrees) and follow recommended maintenance schedules.
• Make certain that the air conditioning drain tube remains clear to avoid water accumulation in the unit.
In This Manual:
This manual is the installation, adjustment, and troubleshooting guide for the TSSA compliant
Motion 4000 traction controller. When viewed online as a pdf file, hyperlinks (buttons or blue text) link to related topics and informational websites. The manual includes:
•
Contents
: Table of Contents. When viewed online as a pdf file, hyperlinks in the Contents link to the associated topic in the body of the manual.
•
Section 1 . General Information: System description; operating modes
•
Section 2 . Installation
•
Section 3 . Final Adjustments
•
Section 4
. User Interface
•
Section 5 . Troubleshooting
• Appendix
•
Index : Alphabetical index to help you find information in the manual. When viewed
online as a pdf file, index entry page references are hyperlinks to the associated information in the body of the manual.
Contents
Important Precautions and Useful Information
Safety and Other Symbol Meanings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-iv
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-iv
Environmental Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-v
Air Conditioned Equipment Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-v
In This Manual: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-vi
Section 1. Motion 4000 Traction Elevator Control
In this section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Motion 4000 Traction Elevator Control Overview . . . . . . . . . . . . . . . . . . . . . . . 1-2
System Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
System Component Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Controller Circuit Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Hand-Held User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Car . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Landing and Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Load Weigher . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
Cartop Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
Hoistway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
Motion 4000 Specific Traveler Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
Operating Mode Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
Inspection Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
Cartop Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
In Car Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10
Hoistway Access Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10
Machine Room Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10
Attendant Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11
Mode Entry. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11
Independent Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11
Mode Entry. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11
Sabbath Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-12
Emergency Medical Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-12
Hospital Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-13
Seismic Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-13
Mode Exit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-13
Modifiers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-13
Fire Service Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-14
i
Emergency Power Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-14
Generator Backup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-14
TAPS Backup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-14
Car Recall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-15
Pretest (Capture for Test) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-15
Test/Pretest Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-15
Monitoring and Control Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-16
iMonitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-16 iReport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-16
BMS-Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-17 mView . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-17
Section 2. Installation
In this Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-2
Personal Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Equipment Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-3
Electrical Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
EMI/RFI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Recommended Tools and Test Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
MCE Wiring Prints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-5
Drawing Number Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Power Nomenclature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Controller Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-6
Controller Wiring Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Proper Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Check for Shorts to Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
AC Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-10
Power Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Motor, Brake, and Encoder Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
Motor Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-11
Insulation Breakdown Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
Motor Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
MRL or Extended Motor Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
Brake Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Standard Brake . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Brake Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Brake Mechanics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Velocity Encoder Installation and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Encoder Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Emergency Brake Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Resetting the Rope Gripper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
ii Manual # 42-02-2P25 2/3/16
Initial Power Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Often Used Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
How to check Car Speed: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
How to place the car on Inspection Mode Fault Bypass: . . . . . . . . . . . . . . . . . . . . . . . 2-15
How to place the car on Automatic Mode Fault Bypass:. . . . . . . . . . . . . . . . . . . . . . . . 2-15
How to change TORQMAX F5 Drive parameter settings: . . . . . . . . . . . . . . . . . . . . . . 2-16
How to change Magnetek Drive parameter settings:. . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
How to access/set the F7 parameters:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
How to Reset Excessive Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Auto Tuning and Encoder Data Loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-17
TORQMAX F5 Drive Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-17
Digital Operator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-17
Keypad Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-18
Clear Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-18
TORQMAX Drive Operation Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-20
Drive Motor/Encoder Setup Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-20
Auto-tuning AC Induction Motors to the F5 Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-21
Manual Induction Motor Parameter Entry. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-22
The Drive Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-22
Setting the Drive to Run Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-22
Magnetek AC Drive Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-23
Digital Operator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-23
Keypad Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-23
Clear Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-23
Magnetek Drive Operation Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-24
Drive Motor/Encoder Setup Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-25
Auto-tuning AC Motors to the Magnetek Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-26
The Drive Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-26
Set Up for Construction Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-27
Minimal Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-27
Jumper Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-27
Bypassing Faults on Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-28
Resolving Faults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-28
Speed and Acceleration Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-29
Required Drive Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-30
TORQMAX F5 AC Drive Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-30
Magnetek AC Drive Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-35
Required Controller Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-43
Acceleration and Deceleration Rates. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-43
Curves Used for Operating Speeds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-43
The F7 Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-44
Restore Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-44
Changing Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-44
Controller Motion Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-45
Using Inspection Stations to Run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-46
Encoder Polarity (TORQMAX) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-46
Align Encoder (Magnetek) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-46
Brake Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-47
Verify Motor Speed, TORQMAX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-48
iii
Verify Motor Speed, Magnetek. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-48
Gear Reduction Ratio, TORQMAX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-49
Temporary Run Box Hookup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-50
Prepare for Inspection Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-51
Hoistway Safety String . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-52
Cartop Safety String . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-52
Hoistway Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-52
Virtual/Physical/Unused . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-52
Seismic Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-53
Running on Inspection Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-54
Controller Power Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-54
Bypassing Faults on Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-55
Finishing Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-55
Landing/Positioning System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-56
LS-EDGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-56
Top Hanger Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-57
Bottom Hanger Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-58
Broken Tape Switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-59
Hanging the Tape. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-59
Tape Tension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-59
Sensor Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-59
Door Zone Magnets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-61
Terminal and ETS Magnets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-62
Electrical Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-64
Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-65
Permanently Attach Magnet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-65
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-65
ELGO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-66
Safety String Connection Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-67
Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-67
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-68
Hoistway Learn, Elgo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-76
Periodic Maintenance Required. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-76
Left to Right Rail Side Reversal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-77
Door Operator and Door Peripherals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-80
Door Safety Equipment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-80
Door Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-80
Car Operating Panels, Position Indicators, and Peripherals . . . . . . . . . . . . . . . . . . . . . . . 2-80
Fire Service Peripherals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-80
Duplex Connection Between Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-81
Hall Calls, Position Indicators, and Peripherals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-81
CE Position Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-81
Adjust Brake to 125% of Full Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-82
Traction Auxiliary Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-82
Installation Review . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-82
iv Manual # 42-02-2P25 2/3/16
Section 3. Final Adjustments
In this Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Basic Service Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-2
Learning the Hoistway, Positioning ETS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-2
ELGO Encoded Magnetic Tape . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Learn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Slowdown Learn, ETS Placement, Elgo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
LS-EDGE Steel Tape . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Hoistway Learn, LS-EDGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Slowdown Learn, ETS Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Adjusting Floor Heights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Door Zone Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Car and Counterweight Balance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-8
Setting Up Performance Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-9
How to Register Calls from the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Acceleration and Deceleration Rates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Curves Used for Operating Speeds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Profile Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
Typical Speed Profile Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
Adjust for Drive Response . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
Verify One Floor Run Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
Verifying Contract Speed Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15
If an ETSL switch is required: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15
Short Floors Near a Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
Short Floor from 1 to 12-inches in Height. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
Additional Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
Tuning (Magnetek) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
Relevel Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
Brake Coordination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
Run Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
Adjustment Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
Placing Calls From the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-20
Load Testing AC Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-21
Trouble Slowing with a Full Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-21
Electrical Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-22
Load Weigher . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-23
Analog Voltage or Relay Closure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-23
Installing the Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-24
Installation with 2 to 1 Roping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-25
Installing the Control Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-26
Analog Weigher Output Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-27
Relay Closure Output Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-27
Controls Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-27
Menu Order . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-27
v
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-28
Manual Calibration with Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-28
Controller Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-30
Auto-zero Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-31
Analog Weigher Additional Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-31
Verifying Empty Car Weight for Analog Weighers . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-31
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-32
Final Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-33
Often Used Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-33
How to check Car Speed: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-33
How to place the car on Inspection Mode Fault Bypass: . . . . . . . . . . . . . . . . . . . . . . . 3-34
How to place the car on Automatic Mode Fault Bypass:. . . . . . . . . . . . . . . . . . . . . . . . 3-34
How to access/set the F7 parameters:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-34
How to Reset Excessive Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-35
Safety String Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-36
SAFH Safety String Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-36
SAFC Safety String Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-36
Motor Contactor Proofing Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-36
Car Stopped at Floor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-36
Car in Motion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-36
Brake Contactor Proofing Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-37
Car Stopped at Floor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-37
Car in Motion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-37
Directional Limits Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-37
Down Direction Limit Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-37
Up Direction Limit Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-37
Final Limit Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-38
Lower Final Limit Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-38
Upper Final Limit Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-38
Car/Counterweight Buffer Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-39
(Car) Buffer Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-39
Traction Loss Detection (Slip) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-40
Inspection Overspeed Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-40
Contract Overspeed Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-40
Leveling Overspeed Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-40
Inner Door Zone Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-41
Normal and Emergency Terminal Switch Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-42
Outer NTS Delta High Speed Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-42
Outer NTS Delta Low Speed Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-42
Continued NTS/ETS Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-43
ETS Testing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-43
Electrical Governor Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-43
Ascending Car Overspeed Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-44
Safety Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-44
Car Safety Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-44
Counterweight Safety Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-45
Emergency Brake Test - Unintended Motion, Rope Brake . . . . . . . . . . . . . . . . . . . . . . . . 3-45
Discrete Brakes - No Brake Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-45
System with Brake Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-46
vi Manual # 42-02-2P25 2/3/16
Emergency or Standby Power Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-53
Traction Auxiliary Power Supply Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-53
Backup Generator Power Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-54
Final Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-56
Section 4. User Interface
In this Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
The HC-MPU Main Processor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-3
Access Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-5
Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Setting Parameters To Default Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-5
Diagnostic Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-6
LCD Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Troubleshooting Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
F1: Program Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
General Description of Program Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-11
Changing Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
Saving Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
Viewing Options Within a Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
Restoring Original Values Before Saving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
Step-By-Step Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
Basic Features Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
Fire Service Menu Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-17
Door Operation Menu Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-19
Timer Menu Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-24
Gongs/Lanterns Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-25
Spare Inputs Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-27
Viewing and Assigning Spare Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-27
Spare Outputs Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-36
Viewing and Assigning Spare Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-36
Extra Features Menu Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-44
UIO Board/Security Enforcement/Connection Order . . . . . . . . . . . . . . . . . . . . . . . . . 4-45
Additional Car Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-52
F2: External Memory Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-53
Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-53
F3: System Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-56
Building Security Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-56
Controller System Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-58
Passcode Request Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-59
Load Weigher Thresholds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-60
Adjusting Thresholds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-61
Analog Load Weigher Learn Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-61
F4: Messages and Floor Labels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-63
vii
F5 Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-65
Controller Utilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-66
Car Call Registration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-66
Date/Time, View / Adjust . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-66
View Event Log. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-67
Clear Event Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-68
Default TC-MPI Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-68
MPI Diagnostic Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-69
MPI-A Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-70
MPI-B Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-78
MPI-C Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-87
EDG Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-96
CTL A Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-114
CTL B Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-124
COP Diagnostics Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-133
System CAN Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-134
Monitoring and Reporting Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-135
Diagnostics, Refresh, Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-136
Terminal Limit Utilities Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-138
Terminal Switch Learn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-138
Perform Terminal Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-138
ETS Position Locator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-138
FCL Brake Unit Utilities Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-139
FCL Diagnostic Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-139
FCL Power Data Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-139
Default TC-FCL Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-139
FCL Adjustment Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-139
F6: Hoistway Learn Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-140
ELGO Encoded Magnetic Tape . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-140
LS-EDGE Steel Tape . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-140
Adjusting Floor Heights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-140
F7: Parameters Adjust . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-141
Restore Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-141
Changing Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-141
Controller Parameter/Drive Parameter Interaction . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-142
Using ID Numbers for Direct Parameter Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-143
Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-149
Speed Related Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-152
Normal Terminal Switch Parameter Explanations . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-153
F8: Software Revision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-164
Status Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-164
F1 & F8: Board Software Versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-165
viii Manual # 42-02-2P25 2/3/16
Section 5. Troubleshooting
In This Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Status and Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-2
Duplexing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-42
Dispatching Algorithm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-42
Hardware Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-42
Power Phasing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-42
PC Board Quick References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-43
HC-CHP CAN Hub and Power Supply Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-44
SW1 DIP Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-45
HC-CTL-2 Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-46
HC-CTL-2 Terminal Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-47
HC-CTL-2 Board LED Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-50
HC-CTL-2 Board Jumpers, Fuses, Testpoints, and Switches . . . . . . . . . . . . . . . . . . . . 5-51
HC-MPU Main Processor Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-53
HC-MPU Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-55
HC-UIO-2 Universal Input/Output Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-56
Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-58
Jumpers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-58
Test Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-58
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-58
Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-58
HC-UIO-2 Switches 7, 8 and 9 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-59
HC-UIO-2 Used for Calls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-59
Hospital Emergency Operation I/O. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-59
Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-60
Call Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-61
Spare Inputs and Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-62
ICE-COP-2 Car Panel Interface Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-63
Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-63
Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-64
ICE-COP-2 Board Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-64
MC-CPI Car Panel Interface Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-67
Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-67
MC-CPI Board Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-69
Before Applying Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-71
MC-LSI Landing System Interface Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-72
LSI Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-72
SC-3HN Three Input Serial Hall Call Node Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-73
Call Bus Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-73
General Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-73
Addressing and CAN Bus Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-75
Riser Assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-75
Floor Number and Front or Rear Opening . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-75
Baud Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-75
CAN Bus Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-75
ix
On Board Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-76
ON LED. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-76
(FLT) FAULT LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-76
TC-MPI Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-77
Motion Brake Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-82
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-82
Switches and Jumpers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-83
ON LED. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-84
Module Connectors Per Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-86
Middle Board, TC-LPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-86
Bottom Board, TC-FCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-87
Calibration (CAN Only). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-88
Trim pots and Function (Discrete Control Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-89
Setup for Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-89
Discrete Control Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-89
CAN Control Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-90
Section A. Appendix
In this Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-1
TORQMAX F5 Parameters Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
Magnetek Parameters Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-6
F7 Settings Record . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-14
General Settings Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-21
Floor Settings Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-27
Customer Notations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-28
R6 Regenerative Drive Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-29
Manual Floor Setup, ELGO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-30
F7 Entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-30
Factory I/O Assignment, ICE-COP-2 Boards . . . . . . . . . . . . . . . . . . . . . . . . . . .A-31
COP-2 Board #1 - ID: 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-31
COP-2 Board #2 - ID: 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-31
COP-2 Board #3 - ID: 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-32
COP-2 Board #4 - ID: 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-32
COP-2 Board #5 - ID: 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-33
COP-2 Board #6 - ID: 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-33
x Manual # 42-02-2P25 2/3/16
Motion 4000 Traction Elevator Control
In this section
This section provides a general description of the Motion 4000 Traction Elevator Control with
Release 9 software, including:
• Controller Overview.
Please refer to “Motion 4000 Traction Elevator Control Overview” on page 1-2.
• System Features.
Please refer to “System Features” on page 1-3.
• Component Descriptions.
Please refer to “System Component Descriptions” on page 1-5.
• Operating Mode Descriptions.
Please refer to “Operating Mode Descriptions” on page 1-9.
• Monitoring and Control Options.
Please refer to “Monitoring and Control Options” on page 1-16.
1-1
Motion 4000 Traction Elevator Control
Motion 4000 Traction Elevator Control Overview
A Motion 4000 controller order may include:
• Controller: Configured according to customer job survey, field programmable.
• Cartop station: Interface between car-mounted equipment and the car controller.
• Serial panel option: Converts car panel analog button data to serial data stream.
• Optional CAN node boards and wiring for serial hall call.
• User Interface: Standard, controller mounted keypad/LCD, optional hand-held keypad/
LCD units to set controller parameters, optional mView PC application.
AC Drive
CAN Hub & Power distribution
MPU Board
Control Board
Motion Processor Interface Board
Universal I/O Boards
Panel Mount Terminals
Standard cabinet (NEMA 1) dimensions:
16” x 42” x 72” (406 x 1067 x 1829 mm) including legs (12” (305 mm).
Table 1.1 Specifications
Maximum car speed
Configuration
Landings
Motor control
Landing/Positioning system
Call Registration
Power requirement
Environment
*Standard enclosure (includes legs)
Available NEMA enclosures
* Variations available
450 fpm, 2.25 m/s
Simplex, Duplex, Group up to 6 cars
32 landings, 64 openings maximum
TORQMAX F5, Magnetek HPV AC drives
Perforated steel tape or encoded magnetic tape
Serial or Discrete COP, Serial or discrete Hall Calls
208 – 600 VAC, 50/60 Hz, 3-phase
32 - 104º F, 0 - 40º C; Humidity 95% non-condensing
42” w x 72” h x 16” d (1067 x 1829 x 406 mm) with knock-outs
NEMA 4, 4X, 12
1-2 Manual # 42-02-2P25
Motion 4000
System Features
System Features
Motion 4000 design incorporates:
• Solid state implementation of redundancy and proofing requirements, eliminating relays whenever possible to improve service life and reliability.
• Retention of the simple LCD/keypad programming interface used on earlier MCE programmable controls but with the addition of a hand-held interface (mPAC) that can be plugged in to any system CAN connector.
• Easy software updates — Internet download through a PC to the hand-held user interface,
MCE SD card, or EEPROM replacement.
• CAN Bus: Circuit boards and major components all communicate through light weight, serial CAN Bus connections. Communication between major system components (i.e., controller to car, controller to hall calls, etc.) uses shielded, twisted-pair cables connected to pluggable terminals (CAN).
• ASME A17.1/CSA B44 compliant throughout.
• Field connections: Field connections are handled by Universal I/O boards. The boards are factory set to handle 24V, 48V, 110V, or 120V AC or DC inputs. This allows a single board design to service all common inputs.
• Positioning: Perforated steel tape (LS-EDGE) or encoded magnetic tape (ELGO).
• Minimized hoistway peripherals: Motion 4000 design allows slowdown, emergency terminal, and hoistway access limit switches to be eliminated. These switches may exist as virtual switches in system software.
• Serial hall call: Motion 4000 may use a serial hall call system for easier field wiring. The riser drop provides CAN communication and power to the fixtures. (Discrete hall call wiring is supported through Universal I/O boards.)
• Serial car panel option: Discrete signals from car panel buttons may be serialized for easy connection to the controller via CAN bus through the cartop interface.
• Light weight traveler and hoistway cabling: Serial communication allows low traveler and hoistway cable conductor counts.
• Optional monitoring capabilities using mView, iMonitor, and iReport software.
• Optional integration with Building Management Software using BMS-LINK.
• Optional Jail Services application for detention center operation.
• (MRL) Optional passenger rescue system provides input from a cartop mounted camera and a rescue control panel with LCD display to allow a technician to safely drift the car to a landing in the absence of commercial or emergency power. Once at the landing, doors must be opened manually.
• Optional Traction Auxiliary Power Supply (TAPS) provides automated return of the car to a landing and automated door opening in the absence of commercial power. Power is provided via an integrated UPS/battery system and requires no generator.
Note
If the job uses a TAPS system and a TORQMAX F5 drive, drive parameter LF.61 must be set to
Di1.
1
1-3
Motion 4000 Traction Elevator Control
Figure 1.1 Functional Block
Hoistway
Final Limit
Seismic Sensor
Final Limit
Controller
CAN Hub Board
CAN I/F
Main Processor
Board
Control Board
Counterweight
Movement
Detection
Load Weigher
Encoded Tape
Position Sensors
PS1
PS2
CAN
Cartop I/F
Car
General I/O
Motion
Processor
Interface
Board
Universal I/O
Board
Drive
COP
Encoder
Machine
Rope Gripper
1-4 Manual # 42-02-2P25
Motion 4000
System Component Descriptions
System Component Descriptions
• Controller boards and hand-held user interface
• Car mounted equipment,
page 1-6
• Hoistway equipment,
page 1-8
Controller Circuit Boards
Circuit boards used depend upon job requirements. Typically, the following boards are used:
• HC-CHP, CAN Hub and Power Supply: Provides
~18-volt, 4-amp DC power for circuit boards in the controller and a central connection point for the Controller Area Network (CAN).
• HC-MPU, Main Processing Unit: Fitted with the appropriate software, performs control data processing. The HC-MPU is responsible for:
• Car operation
• Fire Service
• Programming and diagnostics
• Software validation
M4000 HC-CHP Board
M4000 HC-MPU Board
M4000 HC-CTL-2 Board
• Duplexing / Group communication
• HC-UIO, Universal Input/Output Board: HC-
UIO boards are used for field inputs and outputs. The boards are universal in that they can be configured for AC or DC inputs from 24 to
120 Volts.
M4000 TC-MPI
M4000 HC-UIO
• TC-MPI, Motion Processor Interface Board:
Configured to interface to the drive selected for the job. Handles machine and brake contactors, position system I/O, earthquake/seismic and emergency brake/rope gripper requirements.
M4000 HC-UIO
• HC-CTL-2, Control Board: Monitors I/O, performs safety functions, door operation, and machine room inspection. The HC-CTL-2 board is responsible for:
• Inspection
• Test operation
• Diagnostic Flags
• Hall and Car Door Lock Bypass
• Lanterns and Gongs
• Spare I/O
Additional circuit boards may be used, including:
• CE Fixture board: Used with external, serially controlled position indicator and annunciator fixtures.
1
1-5
Motion 4000 Traction Elevator Control
Hand-Held User Interface
The hand-held user interface, mPac, provides a portable interface and a means to upload new firmware to the system.
The hand-held can be plugged in to a CAN connection in the controller, on the cartop, or in the car (if one is wired).
Car
Landing and Positioning
Motion 4000 uses one of two landing systems; encoded magnetic tape or perforated steel tape and magnets.
The ELGO encoded steel tape system uses a 1/2-inch wide,
Gray code, magnetically encoded tape, hall-effect sensors, and two independent sensor heads (in a single housing) for absolute position control under all powered conditions. The tape provides a unique code for every 1mm of travel. In addition to position, simple distance-over-time calculation provides extremely accurate speed feedback. A third, also independent system provides speed feedback directly from the hoist motor.
The LS-EDGE positioning system uses hall-effect sensors and perforated steel tape to report position as the car moves through the hoistway. 5.5-inch magnets are used at each door zone; one row for front openings, a second for rear openings. The system auto-corrects at each door zone to prevent error accumulation.
LS-EDGE uses capacitor-stored power and non-volatile memory to retain position information in the event of a power failure, continuing to capture information for 22 seconds after power loss and storing the final reading for use after power restoration. Mechanical final limit, ETS, and ETSL switches are used but normal terminal switches may be virtual, based on position, or mechanical depending upon specific controller capabilities. The LS-EDGE system may be used with MCE iControl or Motion 4000 elevator controls.
1-6 Manual # 42-02-2P25
Motion 4000
System Component Descriptions
Load Weigher
Motion 4000 typically uses an EMCO rope strain gauge for load weighing. The controller uses the load weigher input to determine overload conditions and also in conjunction with car call registrations and photo-eye information to make anti-nuisance related decisions.
Figure 1.2 EMCO Load Weigher
1
Processing unit
Sensors (1 per rope)
Installation tool
Cartop Box
A typical Motion 4000 cartop box is pictured below.
Figure 1.3 Motion 4000 Cartop Box
24V Power Supply
Landing System Interface board
EMCO load weigher control unit
Universal I/O board
Car top box dimensions depend upon required components. Enclosure shown is
4” x 15” x 18” (102 x 381 x 457 mm).
Minimum enclosure is 4” x 8” x 12”
(102 x 203 x 305 mm).
1-7
Motion 4000 Traction Elevator Control
Hoistway
For serial hall call, Motion 4000 communicates with hall calls and similar buttons or key switches through an independent CAN Bus for reliability and easy installation. The hall bus provides a CAN signal path and 24 V power for the fixtures.
An SC-3HN three-input hall node board allows discrete hall call buttons and indicators to be connected along a CAN bus to provide serial hall call capability for Motion 4000, greatly reducing the number of conductors necessary in hoistway wiring bundles.
Please refer to “SC-3HN
Three Input Serial Hall Call Node Board” on page 5-73
.
Discrete hall calls are supported using HC-UIO Universal I/O boards.
Please refer to “HC-UIO-
2 Universal Input/Output Board” on page 5-56 .
Motion 4000 Specific Traveler Cable
Special traveler cable for Motion 4000 installations is available from MCE. The cable is sized and labeled to make controller to car connections as simple as possible. MCE PN# 44-03-0034.
1-8 Manual # 42-02-2P25
Motion 4000
Operating Mode Descriptions
Operating Mode Descriptions
Available operating modes are configured when the car is installed. Not all modes are available on all cars. This section describes operating modes, including:
• Normal Operation
• Inspection Operation
(cartop, in-car, access, machine room)
• Attendant Operation
• Independent Operation
• Sabbath Operation
• Emergency Medical Operation
• Hospital Operation
• Seismic Operation
• Fire Operation
• Emergency Power Operation
• Car Recall
• Capture for Test
• Test Mode
Normal Operation
Normal operation is the default elevator operating mode. In this mode, cars are accepting hall calls and servicing car calls as determined by Basic Features Menu and other operating menu
selections. Please refer to “Basic Features Menu” on page 4-13 . Cars are running at contract
speed as affected by short or multi-floor run performance curves.
Inspection Operation
In inspection, a car operates at the set inspection speed using continuous pressure up and down buttons or switches. The car will stop as soon as the buttons are released. Inspection operation may be controlled from four locations. For safety purposes, locations have a priority:
• Cartop
• In-Car
• Access
• Machine Room Inspection
Cartop Inspection
In this mode, the car is operated by pushing the cartop UP or DOWN and ENABLE buttons simultaneously. These buttons are generally provided through a third-party inspection station wired to inspection operation inputs in the elevator controller. There will also be a key switch that enables/disables inspection operation.
Mode Entry
• Bring the car to the access floor
• Enable hoistway access operation using the in-car switch
• Move the car down using the hall controls until the access limit is opened
• Set the cartop switch to Inspection and access the cartop.
• Use ENABLE and UP or DOWN buttons to run the car from the cartop.
1
1-9
Motion 4000 Traction Elevator Control
In Car Inspection
In this mode, the car is operated using a locked subpanel in the COP that provides the inspection key switch and direction buttons. (Top and bottom car call buttons may be used as direction buttons as well.)
Mode Entry
• Bring the car to the desired floor.
• Place the car on in-car inspection.
• Use UP or DOWN buttons to run the car.
Hoistway Access Inspection
Hoistway access operation allows workers to access the top and bottom of the car from designated floors. In this mode, the car is brought to an access floor where a key switch is used to move the car up or down.
Mode Entry
• Bring the car to the access floor
• Place the car on hoistway access using the in-car switch.
• Move the car using the hall way switch until the access limit is opened
• Top access must prevent the car from moving down beyond the point where the crosshead is even with the hoistway entrance sill.
• Bottom access must prevent the car from moving up beyond the point where the bottom of the toe guard is even with the hoistway entrance header
Machine Room Inspection
In this mode, the car is operated using switches on the HC-CTL-2 (Control) board in the controller.
Mode Entry
• Place the car on Machine Room Inspection
(Mode Switch to Inspection).
• Ensure that car and hoistway doors are closed and locked.
• Run the car using the ENABLE and UP or
DOWN Directional switch positions.
1-10 Manual # 42-02-2P25
Motion 4000
Operating Mode Descriptions
Attendant Operation
Attendant operation allows an operator riding in the car to run the car, choosing run direction, and which hall calls to answer. In this mode:
• Doors open automatically when the car is stopped in a door zone.
• The attendant closes the door by pressing and holding the door close button, a car call button, or either car direction (UP/DOWN) button (UPI/DNI input:
Please refer to “Spare
Inputs Menu” on page 4-27 .)
• The attendant chooses the direction using run up (UNI) or down (DNI) buttons.
• The car will stop at the next car or hall call in the direction of travel. Holding the bypass button (NSI input) in will cause hall calls to be bypassed until the button is released. An annunciator panel is required if in-car visibility of hall calls is required.
• The elevator will level into the destination floor automatically, then open its doors.
• During Attendant operation, load weigher inputs are ignored.
Mode Entry
• Call the car to a floor.
• Enter the car and activate the Attendant mode key switch (enables the ATS, Attendant Service, controller input).
Independent Service
In this mode:
• The car is removed from hall call dispatching
• Doors open automatically when the car is stopped in a door zone
• The operator presses and holds the door close button to close doors
• The operator chooses direction and initiates the run by placing car calls (first placed determines direction of run).
• The elevator will level into destination floors automatically and open its doors.
• Hall arrival lanterns or jamb mounted arrival lanterns are inoperative.
Mode Entry
• Call the car to a floor.
• Enter the car and activate the Independent mode key switch (IND input HC-CTL-2 board).
1
1-11
Motion 4000 Traction Elevator Control
Sabbath Operation
Sabbath operation is a special mode that sets the car to consecutively service specified landings
(and openings if the car has front and rear doors) during up and down travel with no hall or car call buttons being pressed. The car will begin from the bottom of the hoistway, travelling up and stopping at each designated stop and opening its doors to allow exit or entry. When the doors close, the car will travel to the next designated stop up the hoistway and repeat door operation.
This will continue until the car reaches the top designated stop, at which point it will travel down the hoistway operating in the same manner.
• Initiate: Sabbath operation is initiated when the spare input SAB is activated.
• Operation: In accordance with the description above and servicing stops set through the
Sabbath Operation parameter in the Extra Features menu.
Please refer to “Extra Features
Menu Options” on page 4-44 .
Emergency Medical Operation
This mode complies to Massachusetts code. It allows a car to be recalled to a floor where it can be boarded by medical personnel and placed in restricted service, using an in-car switch, to respond to a medical emergency.
• Recall: Initiated using a key switch (EMSH input) at the floor assigned by the Massachusetts EMS Service/EMS Service Floor parameter in the Extra Features menu (single switch, single floor).
• The car will immediately cancel all registered calls, return to the designated floor, and open its doors.
• In-Car Medical: Medical personnel board the car and place it in hospital service using the in-car switch (EMSC input).
• If the hall switch has been shut off, the car will wait sixty seconds then return to normal service if the in-car switch has not been activated.
• If the hall switch remains on, the car will wait without restriction until the in-car switch is activated.
1-12 Manual # 42-02-2P25
Motion 4000
Operating Mode Descriptions
Hospital Service
Please refer to “HOSPITAL EMERG. OPERATION?” on page 4-48
. Hospital service allows a car to be recalled to any of one or more assigned floors using a call button at the floor. Once at the floor, the car may be boarded by medical personnel and placed in restricted service, using an incar switch, to respond to a medical emergency.
• Recall: Floors and openings (if the car has front and rear doors) are designated as hospital service through Hospital Emerg Operation parameters in the Extra Features Menu.
Please refer to “Extra Features Menu Options” on page 4-44 . When a designated call button is
activated, the car will recall to the floor.
• The car will immediately cancel all registered calls, move to the call floor, and open its doors.
• A Timer Menu function, Hospital Emergency Timer, allows a timer to be set for a range of up to 10 minutes. After a car recalls to the designated floor, it will remain there until the timer expires, after which it will return itself to automatic passenger service if the in-car, hospital service switch has not been activated.
• Operation: Once the in-car switch (HOSP input assigned through the Spare Inputs Menu) is activated, the car is in restricted service and will accept only calls assigned through the car operating panel.
• When the in-car switch is deactivated, the car returns to normal service.
Seismic Operation
Please refer to “EARTHQUAKE OPERATION?” on page 4-51 . Seismic operation is entered into
automatically if counterweight derailment is detected (CWI input) or if the seismic sensor input
(SSI) is activated. If the CWI input is triggered, the car comes to a full stop, moves at reduced speed (150 FPM or less) to the nearest floor in the direction away from the counterweight, levels, opens its doors to allow passengers to exit, then shuts down.
If only the SSI input is activated, the car will continue to the next available floor, open its doors, and shut down. A programmable option is available to allow the car to run on normal, automatic operation or fire service at reduced speed (150FPM or less).
Mode Exit
• After ensuring that the hoistway is clear and all equipment is undamaged and operating properly:
• Press the EQ Reset button on the Motion Processor Interface (MPI) board.
Modifiers
Some fire codes allow the car to be run in fireman service even though the CWI or SSI input has been activated.
1
Note
Earthquake operating profile overrides the Emergency power profile.
1-13
Motion 4000 Traction Elevator Control
Fire Service Operation
There are many different fire codes that restrict or change elevator operation under fire condi-
tions. Please refer to “Fire Service Menu Options” on page 4-17
. In general, fire service proceeds in two stages; Phase I Fire Recall and Phase II Fire In-Car Operation. When a fire sensor or switch is activated:
• The elevator will recall to the designated main or alternate recall floor. (Main if fire detected on any floor other than the main floor; Alternate if fire detected on the main recall floor. Or, as directed by a manually activated Fire switch.)
• The elevator will open its doors to allow any passengers to exit, then remain at the recall floor until the in-car firefighter switch is activated. Once the in-car switch is activated the car will run on Fire Phase II operation as allowed by the selected fire code.
Emergency Power Operation
Please refer to “EMERGENCY POWER OPERATION?/EMERGENCY POWER RETURN
FLOOR” on page 4-44 . Emergency or standby power operation requires a backup power source.
For large buildings, this is typically a diesel or gasoline powered generator. When this is not practical, backup power for a limited, rescue operation may be provided by a battery-powered system like the MCE TAPS (Traction Auxiliary Power Supply).
Generator Backup
When power is lost, the elevator will come to a full stop. When emergency/backup power comes on line, the elevator will be moved at programmed speed to a designated recall floor and the doors will open to allow passengers to exit. The elevator will remain at the recall floor unless it is designated to run under generator power.
TAPS Backup
When power is lost, the elevator will come to a full stop. When battery power becomes available, the elevator will be moved at reduced speed to the nearest floor in the direction determined by
TAPS settings. At the floor, the doors will cycle, allowing passengers to exit, and then close. The car will remain out of service until commercial power is again available and the TAPS unit switches the car from battery power back to normal power. Please refer to the MCE TAPS manual or data sheets for detailed information.
1-14 Manual # 42-02-2P25
Motion 4000
Operating Mode Descriptions
Car Recall
Inputs may be provided to allow the car to be recalled to a specified floor.
• CTF: Car To Floor - This is a “spare” input that may be assigned to the HC-CTL-2 board or to a Universal I/O board as configured for the job. The floor to which the car is returned is set by the Car to Floor Return Floor parameter in the Extra Features menu.
Please refer to
“Extra Features Menu Options” on page 4-44 .
• When activated, causes the car to stop responding to hall calls. Existing car calls will be serviced before or after recall depending on the setting of Retain Calls (see note below). New car calls will not be registered.
• At the return floor, the car will open then close its doors and remove itself from service.
• CTL: Car to Lobby - This is a “spare” input that may be assigned to the HC-CTL-2 board or to a Universal I/O board as configured for the job. The floor to which the car is returned is
set using the Lobby Floor parameter in the Basic Features menu. Please refer to “Basic
Features Menu” on page 4-13 .
• When activated, causes the car to stop responding to hall calls. Existing car calls will be serviced before or after recall depending on the setting of Retain Calls (see note below). New car calls will not be registered
• At the lobby floor, the car will open then close its doors and remove itself from service.
Note
RETAIN CALLS?: There is a function in the Extra Features menu that determines if registered car calls are serviced before or after recall.
Please refer to “RETAIN CALLS ON CTL / CTF?” on page 4-51 .
Pretest (Capture for Test)
Pretest is used to capture the car in preparation to using Test mode.
• When this input is activated, the car will stop responding to hall calls and disable its gongs but continue to service car calls.
• The intent of the input is to allow maintenance personnel to capture the car while causing as little disruption to service as possible.
• Enter Pretest mode by placing the TEST/NORMAL/PRETEST switch on the HC-CTL-2 board in the PRETEST position. (The car will not enter Pretest if Inspection is active.)
Test/Pretest Modes
Test mode allows the car to be run on automatic operation without operating the doors. When
Test mode is active, door opening circuitry is deactivated, active hall calls are cancelled, and new hall calls will not be registered.
• Enter Test mode by placing the TEST/NORMAL/PRETEST switch on the HC-CTL-2 board in the TEST position. (The car will not enter Test mode if Inspection is active.)
• When Test mode is active, the controller LCD will display TEST MODE.
1
1-15
Motion 4000 Traction Elevator Control
Monitoring and Control Options
Motion 4000 is Ethernet capable, allowing it to use iMonitor and iReport applications for local and/or distance monitoring and control or report generation, archival, and automated alert.
Motion 4000 can be linked to Building Management System software through MCE BMS-Link, providing system visibility and limited control. A machine room-only monitoring and control application, mView, is also available.
iMonitor
iMonitor is an elevator monitoring application that allows local or remote viewing and control of MCE elevator groups using a personal computer running the Windows XP or Windows 7 operating system. Because Motion 4000 controls are Ethernet capable, you can connect to them though a local area network or remotely through internet technology.
iMonitor provides a graphical representation of elevator groups, allowing their activity and status to be quickly and easily viewed. The user defines any number of “Connection Sets.” Each
Connection Set consists of up to fifty connections to elevator group dispatchers selected by the user.
When working in iMonitor, the user simply clicks on a Connection Set which automatically establishes communication with all groups in the set and displays their associated hoistways and cars on the computer screen. Practical viewing limits are established by the speed of the connections and the size of the monitor viewing area.
When connected through iMonitor, the user may register car and general, auxiliary, or special hall calls as desired, control many group security functions, and enable or disable certain elevator operating modes.
iReport
iReport is a system logging and report generating tool that allows local or remote analysis of
MCE elevator groups from a personal computer running the Windows XP or Windows 7 operating system and iReport client software. Because Motion 4000 controls are Ethernet capable, you can use iReport to connect to them through a local area network or remotely through internet/modem technology.
iReport consists of the iReport server and iReport clients. Motion 4000 group dispatchers may be connected to iReport directly through a local area network or they may be connected remotely through the internet. The group dispatcher provides iReport with hall call and car operating mode information. The individual car controllers provide iReport with event and fault notifications.
1-16 Manual # 42-02-2P25
Motion 4000
Monitoring and Control Options
BMS-Link
BMS-LINK allows MCE elevators and escalators to be viewed and monitored using Building
Management Software. Control capabilities in keeping with management system software needs are provided.
1
Utility Company
Building Automation
Internet
Intelligence Intelligence
BMS-LINK
Elevator Controllers
Heating/Cooling Plant Lighting
mView
The mView application runs on a standard PC connected to the controller through an Ethernet hub or switch. mView provides local monitoring, status and event log viewing, diagnostics, and call registration for one or more Motion 4000 controllers.
1-17
Motion 4000 Traction Elevator Control
1-18 Manual # 42-02-2P25
Installation
In this Section
This section contains instructions for installing the controller and peripheral equipment. If you are reading this on a computer, click the blue text to jump to the appropriate section.
• Safety: page 2-2.
• Preparation: page 2-3.
• MCE Wiring Prints: page 2-5.
• Controller Installation: page 2-6.
• Connect AC power: page 2-10.
• Connect motor, brake, encoder: page 2-11.
• Emergency Brake/Rope Gripper installation: page 2-14.
• Initial Power Up: page 2-14.
• Auto-Tune Drive: page 2-17.
• Set up for Construction operation: page 2-27.
• Set up for Inspection operation: page 2-51.
• Running on Inspection: page 2-54.
• Finishing Installation: page 2-55.
• Installing the landing system, page 2-56.
• Adjust Brake: page 2-82.
• Traction Auxiliary Power Supply: page 2-82.
• Installation Review: page 2-82.
2-1
Installation
The job prints are the primary document used to install the controller. The job prints and manual together provide information to install, adjust, and troubleshoot the controller. Study the job prints and read the manual before starting work. Call MCE with any questions.
Instructions in this section assume that the hoist ropes are attached to the car sling, all hoistway doors are closed, and that:
• The CAR SAFETY IS ADJUSTED to the manufacturer specification
• The GOVERNOR IS INSTALLED and the GOVERNOR ROPE CONNECTED to the safety
Safety
Certain fundamental warnings must be kept in mind at all times to help avoid accidental death, severe personal injury, or equipment damage.
Personal Safety
• Motion 4000 Controllers may only be installed by qualified, licensed, trained elevator personnel familiar with the operation of microprocessor-based elevator controls.
• Verify safety devices (limits, governors, hoistway locks, car gate, etc.) are fully functional before running the elevator. Never operate controls with any safety device inoperative.
• The user is responsible for complying with the current National Electrical Code with respect to the overall installation of equipment and proper sizing of electrical conductors.
• The user is responsible for understanding and applying all current local, state, provincial, and federal codes that govern practices such as controller placement, applicability, wiring protection, disconnections, over-current protection, and grounding procedures.
• Controller equipment is at line voltage when AC power is connected. Never operate controls with covers removed from drive or brake controls.
• After AC power has been removed, internal capacitors can remain charged for up to 5 minutes. Wait at least 5 minutes after power down before touching any internal components.
• To reduce the risk of shock, all equipment should be securely grounded to earth ground.
Failure to obtain an actual earth ground may result in electrical shock to personnel. Provide equipment grounding in accordance with local code and NEC Article 250.
• When using test equipment (oscilloscopes, etc.) with a power cord that electrically ties probe common to earth ground, an isolation transformer should be used to isolate the instrument common from earth ground.
• Remain clear of all rotating equipment while working on the controls.
2-2 Manual # 42-02-2P25
Motion 4000
Preparation
Equipment Safety
• Provide equipment grounding in accordance with local code and NEC Article 250. Failure to obtain a true earth ground may result in electrical shock. Improper grounding is the most common cause of electrical component failure and noise-induced problems.
• Replace components only with main line power off. Damage to equipment or unexpected operation of the elevator may occur if this precaution is not observed.
• Do not substitute or modify parts. MCE will not be responsible for modifications made in the field unless they are approved in writing by MCE.
• Circuit boards believed to be defective must be sent to MCE for repair and testing. Field repair may leave the board with undetected problems.
• Care should be taken when using test leads and jumpers to avoid shorting high voltage or ground to low voltage microprocessor circuits.
• Do not allow dust, carbon, or metallic particles to accumulate on any part of the control.
• Avoid vibration, shock, high humidity, high ambient temperature, and caustic fumes.
Preparation
When choosing equipment location, consider:
• Logical arrangement, taking into consideration other equipment, electrical power, and seismic zone requirements.
• Do not install equipment in hazardous or vibration prone locations.
• Locate the drive isolation transformer (if used) near the controller to reduce wire runs.
• Ambient temperature should remain within 32
to 104
Fahrenheit (0
to 40
Celsius).
Temperatures outside these guidelines may be tolerated, but will shorten equipment life.
Adequate ventilation is required. Air conditioning may be necessary.
• The air in the machine room should be free of excessive dust, moisture, or corrosive elements. A NEMA 4 or NEMA 12 enclosure can help meet these requirements if machine room conditions are inadequate. If the machine room has open or unglazed windows or other direct outside openings, place equipment cabinets far enough from them that severe weather does not damage the equipment.
• Very high levels of radio frequency (RF) radiation from nearby sources should be avoided.
RFI may interfere with controller components, degrading elevator performance. Using hand-held communication devices close to the controller may also cause interference.
Interference from permanently installed radio transmitting antennas is not common.
• Power line fluctuation should not be greater than ±10%.
2
2-3
Installation
Electrical Noise
Electrical noise readily occurs when two wires run along side one another with one of them a high power conductor and the other a low signal level conductor. The easiest way to avoid noise problems is to keep low-level wiring in separate conduit from high power wiring. If high and low power wiring must be run in the same duct, separate them by a minimum of three to four inches. If one must cross the other, it should be at a ninety degree angle.
Alternately, low level wiring may use shielded cable. The shield drains induced voltage to ground. The shield must be connected to ground at one end only.
EMI/RFI
To avoid EMI/RFI interference:
• Keep motor leads as short as possible. Run them in a separate conduit.
• Run main line supply leads to the controller or isolation transformer in a separate conduit.
• Run leads from the isolation transformer to the drive cabinet in a separate conduit.
• The controller door will protect against interference only when closed.
Recommended Tools and Test Equipment
Recommended tools and test equipment:
• Digital multimeter, Fluke series 75, 76, 77 or equivalent
• Hand-held tachometer
• Clamp-on AC ammeter
• Hand-held radios
• Test weights
2-4 Manual # 42-02-2P25
Motion 4000
MCE Wiring Prints
MCE Wiring Prints
Become familiar with the wiring prints provided with your control system.
Drawing Number Format
Each print has a drawing number. The drawing number is comprised of the job number, car number, and page number (see example).
Job Number
Year Car Number
2
Page Number
Nomenclature
The following table lists board reference and part numbers. Your installation may not use all boards listed.
Table 2.1 Component Nomenclature
Board Name Description
HC-DB-MOD Front G. A. L. MOD Door Interface Board
HC-DB-MOD-R Rear G. A. L. MOD Door Interface Board
HC-CTL-2
TC-MPI
Controller Board
Motion Processor Interface to drive
HC-UIO
HC-CHP
HC-MPU
ICE-COP-2
Universal I/O Board
CAN Hub and Power Board
Main Processor Board
Control panel interface board
MC-CPI
MC-LSI
SC-3HN
Control panel interface board
Landing System Interface Board
Three Input Hall Call Node Board
Power Nomenclature
MCE job prints and power terminals within the controller are numbered to identify different power buses:
• 1: The number 1 (one) bus is system Common.
• 2: The number 2 (two) bus is AC power.
2-5
Installation
Controller Installation
Mount the controller securely to the machine room floor and use provided wiring knock-outs to install raceway or conduit to route wires into the cabinet.
Caution
If you drill or cut the cabinet, do not allow metal chips or shavings to fall into electronics.
Damage caused by this is not covered by warranty.
Figure 2.1 Mounting Template for Standard NEMA 1 Cabinet with Feet
33.50
27.50
3.00
12.00
0.44
2.00
4.25
7.25
0.75
Dimensions for attaching base feet of Standard NEMA 1 enclosure (16” deep x 42” wide) to floor.
2-6 Manual # 42-02-2P25
Motion 4000
Controller Installation
Controller Wiring Guidelines
Detailed instructions for connecting the Motion 4000 controller and accompanying components are contained in the drawings package for the job. During the job survey, site-specific information collected is used to engineer the drawings package. Contact Motion Control Engineering immediately if you have questions about the drawings or need additional assistance.
2
Note
Be aware of the hierarchy of the inspection inputs. (Cartop has highest priority. In-car is next.
Machine Room is last.) In order to maintain safe operation of the lift while on access, car top, or in-car inspection, the inspection circuits must be wired as shown in the prints.
Caution
PC boards can be easily damaged by Electrostatic Discharge (ESD). Use a properly grounded wrist strap when touching PC boards. Do not touch PC Boards unless you are properly grounded.
• Use the wiring ducts in the controller. The terminals are located conveniently near them.
• Connect wires according to hoistway and car wiring diagrams.
• If the car is part of a duplex or group, there are additional steps related to wiring interconnects between individual cars:
• A separate conduit or wiring trough must be provided for the CAN link between each controller cabinet.
• Wiring details are shown in the job prints.
• Ground all cabinets according to applicable guidelines.
Please refer to “Proper
Ground” on page 2-7
.
Proper Ground
Provide equipment grounding in accordance with local code and NEC Article 250. A proper ground is essential to trouble free operation. Ground is defined as a direct connection to
EARTH GROUND. This type of ground is not always available in the electrical supply panel.
Electrical conduit is not a sufficient ground. Electrical ground should be obtained and certified by the electrical contractor. When seeking an adequate EARTH GROUND:
• Consult with the building engineer or electrical contractor to determine the best source for a low impedance ground.
• Sprinkler system water pipe is not adequate because the sprinkler system is, in most cases, isolated from a free flowing earth water source.
Danger
If a poor ground connection is used and a true electrical ground is later introduced into the system, the difference in potential can lead to the possibility of severe electrical shock to personnel and damage to test equipment.
2-7
Installation
• The chosen ground must conform to all applicable codes. Proper grounding is essential for system safety and helps to reduce noise-induced problems.
• Direct, solid grounding must be provided in the machine room to properly ground the controller and the motor.
Figure 2.2 Ground Wiring to Controller Cabinet
1. An uninterrupted ground wire should be run from each car controller cabinet chassis or back plate to earth ground. The connection at the car controller must be free of paint so connection is made to bare metal. There should be less than 1-ohm to ground with the power off.
2. Ground straps, or short loops of ground wire, should be run from the controller ground connection to the primary duct connections.
3. An uninterrupted ground wire should be run from the hoist motor frame to the controller ground. The ground connection to the hoist motor must be free of paint.
4. An uninterrupted ground wire should be run from a termination point on the cab to the controller ground.
5. An uninterrupted ground wire should be run from the cab enclosure to the ground terminal on the cab to protect passengers from electrical shock.
6. An uninterrupted ground wire should be run from each car operating panel to the ground terminal on the cab to protect passengers from electrical shock.
7. An uninterrupted ground wire should be run from the dispatch cabinet chassis or back plate to earth ground. The connection must be to the bare metal of the enclosure.
2-8 Manual # 42-02-2P25
Motion 4000
Controller Installation
Check for Shorts to Ground
Check for shorts to ground before powering up the system. Power must be OFF at the main
disconnect. If any shorts to ground are discovered, they must be corrected before proceeding.
A short to ground is defined as having a resistance of less than 20 ohms between ground and the terminal being tested.
2
Danger
Be certain that power is OFF at the main disconnect before proceeding.
1. Disengage all 2 Bus fuses.
2. Measure the resistance between the 1 Bus (common) and all field connection terminals.
3. Check for shorts to ground on motor power terminals L1, L2, and L3.
4. Check for shorts to ground on brake terminals B1 and B2, EB1, and EB2 (as applicable).
5. If no shorts to ground are discovered, re-engage the fuses.
2-9
Installation
AC Power Connections
• All conductors entering or leaving the controller must be through conduit.
• High voltage, high current conductors must be separated from control wires.
• Velocity encoder or tachometer wires must be routed in a separate conduit from high voltage, high current wires.
• Incoming power to the controller and outgoing power to the motor must be through separate, grounded conduits.
Brake Module If your job uses a brake control module, your job drawings may show auxiliary power connections specific to the brake from an isolation transformer. Follow the drawings carefully.
1. Check the AC input specifications on your job prints. Verify that the AC supply is as specified.
Note
Proper motor branch circuit protection in the form of a fused disconnect switch or circuit breaker must be provided for each elevator according to applicable electrical code. Refer to the drive manufacturer manual for proper drive circuit fuse sizing. Each disconnect or breaker must be clearly labeled with the elevator number. The electrical contractor must determine the wire size for the main AC power supply and for the wiring from the disconnect or breaker to the controller or isolation transformer.
2. Connect AC supply wiring as shown in the job prints.
Power Check
After connecting power, it is a good practice to temporarily power up the control to check functionality before connecting any field wiring.
1. Verify that the Inspection switch on the Control Board is in the Inspection position.
2. Visually check for loose connections or components.
3. Verify that fuses FB1 and FB2 are disengaged to prevent the brake from lifting.
4. Have a helper power up the controller and remain by the disconnect ready to shut down immediately if needed.
5. Check that the Power On LED on the CHP (CAN Hub) board is on.
• Verify all transformer and power supply voltage levels are correct per the job prints.
• Verify all fuses are intact.
• Check phase-to-phase input voltage. If necessary, shut off main power and swap two of the incoming feeds at the controller main terminal.
6. After verification, shut down the controller and engage fuses FB1 and FB2 before continuing with field connections.
2-10 Manual # 42-02-2P25
Motion 4000
Motor, Brake, and Encoder Connection
Motor, Brake, and Encoder Connection
Danger
Verify that power to the controller has been shut off at the main disconnect before proceeding with connections.
Motor Connection
2
Caution
If you are reusing an existing hoist motor, you must check it for insulation breakdown before proceeding. Applying power from a modern drive to a motor with insulation problems can damage the motor and/or the drive.
Insulation Breakdown Test
1. Disconnect all motor and brake wiring.
2. Perform an insulation test between motor and brake connection points and the body of the motor. Use a Megohm meter to subject the insulation to the same high voltage that would be present during elevator operation.
3. A minimum insulation resistance of 100k Ohms is required.
4. Correct any insulation problems before proceeding with installation. Insulation problems may indicate a serious problem in the equipment.
Motor Wiring
Incoming power to the controller and outgoing power wires to the motor must be through separate grounded conduits.
1. Refer to the power section drawing in your job prints.
2. Use a shielded power cable between the motor drive and the AC Motor stator connections to reduce RFI/EMI noise (Siemens Protoflex - EMV or equivalent). The shield must be terminated to earth ground at both ends.
3. Make connections as shown. Be sure to follow any notes regarding wire sizes.
4. Pay particular attention to motor grounding instructions in the job prints and in the motor manufacturer instructions.
MRL or Extended Motor Cables
If cables from the drive to the motor are over forty feet / 12 meters in length, high voltage peaks or high rates of voltage rise can occur on the motor windings, potentially damaging the motor.
In these installations, a special output filter may be recommended by the drive manufacturer.
Both cable length limitations and filter configuration are dependent on the drive. Refer to the drive manufacturer manual for specific information and treatment.
2-11
Installation
Brake Connection
Motion 4000 controllers may be ordered with or without a brake control module. The module allows more precise control of brake lift and drop rates. The brake module must be calibrated before it will pick the brake. Please refer to “Calibration (CAN Only)” on page 5-85.
Standard Brake
1. Refer to the brake circuit drawing in your job prints to verify the configuration of the braking circuit. (Brake control and brake adjustment resistors vary from job to job.)
• Familiarize yourself with the brake pick, hold, and drop time adjustments.
2. Measure the resistance through the brake coil on the lift machine.
3. Initially, adjust resistance across the Brake Drop Time resistor(s) to three times the measured brake coil resistance.
Note
This resistance determines brake drop time. Too little resistance causes the brake to remain picked for a longer time, perhaps allowing rollback before stopping the car. Three times brake coil resistance is usually a good starting point.
4. Connect the wires from the controller to the brake as shown in the job prints. Remember that brake wires must not be routed in the same conduit with motor power or velocity encoder wires.
Brake Module
If the job uses one machine brake as the service brake and the second machine brake as an emergency brake, a brake module will be provided for each.
• Connect the wires from the controller to the brake as shown in the job prints. Remember that brake wires must not be routed in the same conduit with motor power or velocity encoder wires.
Brake modules must be calibrated to the brake that they will be controlling. Please refer to “Calibration (CAN Only)” on page 5-85 . Both calibration and adjustment are described in the referenced area of the manual.
Brake Mechanics
Check basic brake characteristics at this time:
• Ensure that the brake mechanism is clean and in good condition.
• Check that the brake lining makes good contact with the machine braking surface (at least
95% of the pad must be in contact with the braking surface).
• Check that the adjustment of the brake solenoid is not preventing the brake from fully applying when it is not energized.
• Check to see that the spring adjustments are equal and are torqued to the manufacturer recommended brake torque settings.
2-12 Manual # 42-02-2P25
Motion 4000
Motor, Brake, and Encoder Connection
Velocity Encoder Installation and Wiring
The velocity encoder reports hoist motor speed to the controller. The encoder must be mounted and wired according to the drawings. When installed, the encoder must be electrically isolated from the motor or any other ground. (Resistance between the encoder casing and the motor or other ground should be “infinite.”)
Do not place the encoder or its wiring close to a magnetic field (the motor or brake coils). Magnetic fields can induce AC into the encoder signal. This can cause the drive to miscount, producing erratic control at lower speeds.
Note
The encoder wiring must use a separate grounded conduit. Inside the controller cabinet, if control wires must cross power wires, they must cross at right angles to reduce the possibility of interference. We recommend you use oversize conduit (typically 2- inch) so that connectors may be fed through without having to disassemble the cable.
2
Encoder Wiring
Caution
Check job prints and installed encoder type to be certain they match. ONLY
WHEN the drive is switched off and the voltage supply is disconnected may the
feedback (encoder) connections be removed or connected.
A shielded cable with an appropriate connector at the encoder end is connected to the drive if the type of encoder is known before the job is shipped. If the encoder type is unknown, the cable ends expose trimmed and tinned individual conductors and the installer must attach the encoder connector and make the proper connections at the drive end. The encoder cable must be routed into the controller cabinet in a separate conduit from brake or power conductors.
1. Route the cable through a separate conduit to the controller cabinet.
2. If it was not done at the factory, connect the controller end of the cable as shown on the drive interface sheet of the job prints and according to the encoder manufacturer instructions.
3. Connect the encoder end of the cable to the encoder. (If you are providing the connector, follow the encoder manufacturer instructions.)
Caution
Do not coil excess Encoder cable near high voltage components — noise may be induced. If the cable must be shortened, trim it at the drive end. Do not cut and re-splice in the middle of the cable or shorten at the Encoder end.
2-13
Installation
Emergency Brake Installation
Depending upon job configuration, a rope gripper, a sheave brake, or one of the two machine brakes may be used for emergency braking (unintended motion prevention).
1. Refer to your job prints.
2. Connect the rope gripper or sheave brake as shown.
Note
If you do not yet have the rope gripper or sheave brake on site, refer to Construction Mode
Jumper Requirements on page 2-27
.
Resetting the Rope Gripper
During setup, the rope gripper or sheave brake may well be triggered. To reset the unit:
1. Place the car on Machine Room Inspection.
2. Press and hold the Emergency Brake reset button, EB RST, on the TC-MPI board for eight seconds, then release.
3. Return to normal operation. Check the fault display and correct faults as necessary.
Initial Power Up
Danger
Always have a helper standing by the AC disconnect to power up the controller and to immediately shut down if necessary.
1. Verify brake and motor wiring is correct.
2. On the HC-CTL-2 board, verify that the Machine Room Inspection switch is in the INSP position.
3. Physically verify that all car and hoistway doors are closed and locked and that no one is in a dangerous position should the car move unexpectedly.
4. Power up the control. Be prepared to immediately shut it down if the car slides or attempts to move.
5. Check that the drive is displaying no fault conditions.
Caution
Turning the control on and off repeatedly (more than once every two minutes) can damage the inverter drive.
2-14 Manual # 42-02-2P25
Motion 4000
Initial Power Up
Often Used Procedures
Following are some procedures and techniques that are often used while setting up drive and controller parameters:
How to check Car Speed:
1. Place Function Switch F3 on the HC-MPU board in the ON (up) position.
2. Press the N push button until CONTROLLER SYSTEM MENU is displayed.
3. Press the S push button to select the menu.
4. Press the N push button until POSTN and SPEED are displayed.
5. Run the car. Speed is displayed in feet per minute.
How to place the car on Inspection Mode Fault Bypass:
1. On the HC-MPU board, place Function Switch F3 in the ON (up) position.
2. On the HC-CTL-2 board, use a jumper to short the A-position pins of JP2 Fault Bypass.
3. Press the N push button until CONTROLLER SYSTEM MENU is displayed.
4. Press the S push button to select the menu.
5. Press the N push button until INSPECTION MODE FAULT BYPASS is scrolled on the display.
6. Press the S push button to change the setting to BYPASS ON.
Inspection mode fault bypass remains activated, even across power cycles, until switched off.
2
Note
In the F3 menu, Automatic Mode Fault bypass is just before Inspection Mode Fault bypass.
When you want Inspection Mode bypass, be careful you do not mistakenly set Automatic mode.
How to place the car on Automatic Mode Fault Bypass:
1. On the HC-MPU board, place Function Switch F3 in the ON (up) position.
2. On the HC-CTL-2 board, use a jumper to short the A-position pins of JP2 Fault Bypass.
3. Press the N push button until CONTROLLER SYSTEM MENU is displayed.
4. Press the S push button to select the menu.
5. Press the N push button until AUTOMATIC MODE FAULT BYPASS is scrolled on the display.
6. Press the S push button to change the setting to BYPASS ON.
Automatic mode fault bypass times out after two hours.
2-15
Installation
How to change TORQMAX F5 Drive parameter settings:
1. Use ENTER and START/STOP buttons to select the parameter group and parameter number.
2. Press FUNC. to display the parameter value.
3. Press START/STOP to increase/decrease the parameter value.
4. Press ENTER to save the new parameter value.
How to change Magnetek Drive parameter settings:
1. Use left/right arrow keys to navigate through menus.
2. Use up/down keys to navigate through submenus.
3. Use Enter to select a submenu.
4. Use up/down keys to navigate through items in a submenu. Use Enter to select an item.
5. To change a value, use left/right keys to select the character to be modified and up/ down keys to change the value.
6. Use ESCAPE at any time to move to the next higher level.
How to access/set the F7 parameters:
Important F7 parameters are protected by a jumper on the HC-CTL-2 board. Before you can access them, you must be in Inspection mode and set the JP2 jumper appropriately:
F7 SETTABLE
1. Place the car on Inspection operation. Set the F7 function switch to the up position.
2. Press N until the LCD displays PARAMETER ADJUST MENU. Press S to select. The
LCD will display ADJUST FROM N=LAST / S=START.
• Press N to begin adjustment from the last viewed or edited parameter.
• Press S to begin adjustment starting with the first F7 parameter.
3. Once viewing parameters:
• Press N to move through the parameters listings.
• Press + or - to change a displayed parameters value.
• To move back to a previous parameter, press and hold N (Next) then press - (minus) as needed.
4. Press S to save changed parameters.
How to Reset Excessive Faults
Many of the faults generated while performing acceptance tests are self-resetting once the fault condition is corrected. However, this controller has excessive faults logic which will generate an
EXCESSIVE FAULTS SHUTDOWN if more than the established limit of faults occur within the circumscribed period of time. To reset this fault:
• Press the Fault Reset button on the HC-CTL-2 board.
2-16 Manual # 42-02-2P25
Motion 4000
Auto Tuning and Encoder Data Loading
Auto Tuning and Encoder Data Loading
Drives used in Motion 4000 applications provide auto tuning procedures which allow the drive to directly learn motor characteristics. Tuning both improves performance and automatically calculates some motor values you would otherwise have to enter manually.
2
Danger
Motor circuits may have high voltage present any time AC power is applied to the controller, even if the motor is not rotating. Wait 10 minutes after removing AC power to allow capacitors to discharge before you open the drive cover. Use extreme caution. Do not touch any circuit board, power device, or connection without ensuring that high voltage is not present.
TORQMAX F5 Drive Introduction
The TORQMAX F5 drive is a KEB F5 with custom software specific to Motion Control Engineering. Take the time to study the drive manual. It has very important startup and other information that are beyond the scope of this manual.
Digital Operator
The keypad and LED display are mounted on the digital operator. The operator must be plugged into the drive or the drive will not function. If the operator is removed while the drive is operating, the drive will shut down immediately. If you must remove the operator, do so while the elevator is standing still.
Figure 2.3 TORQMAX F5 Drive
Digital Operator
2-17
Installation
Figure 2.4 TORQMAX Display
ON when drive is transmitting
Parameter group
(LF, LP, US, etc.)
Parameter number
Blinking “point” means that segment (group or number) is ready to accept an entry
ON = Normal
BLINKING = Error
Keypad Operation
Please refer to “TORQMAX Keypad Overview” on page 2-19 .
Clear Error
If an error is displayed (E. UP, etc.), the drive will shut down. To clear the error:
• Press ENTER
The E.ENCC error is an exception and must be cleared using parameter LF.26.
2-18 Manual # 42-02-2P25
Motion 4000
Auto Tuning and Encoder Data Loading
Figure 2.5 TORQMAX Keypad Overview
Display Parameter
Group
Display Parameter Number
2
Parameter Display
ENTER
F/R
START
STOP
FUNC.
SPEED
The blinking determines the active (changeable) the parameter part of change between parameter group and parameter number
ENTER
F/R
ENTER
F/R
START
FUNC.
SPEED
STOP
Parameter Selection
With the keys select the parameter group
“
US
”, “
LF
”, “
LP
”, “
Ld
”,
“ ru
”, “ do
”
With the keys select the respective parameter number
1,2,3,4...99
START
Display Parameter Display Parameter
Value
FUNC.
SPEED
Parameter Change
Increase/Decrease
Parameter Value
ENTER
F/R
START
FUNC.
SPEED
STOP
ENTER
F/R
START
STOP
FUNC.
SPEED
STOP
Changes are accepted and saved only after ENTER is pressed.
Some parameters cannot be changed while the elevator is operating.
2-19
Installation
TORQMAX Drive Operation Overview
The LF.3 parameter determines the mode the drive is in. The drive default mode is “run.”
Generally:
• Set LF.3 to
Stop to adjust parameter values
• Press
Enter to save the adjusted value
• Set LF.3 to
run and press Enter to run the elevator using the controller Inspection controls or for normal operation
Drive Motor/Encoder Setup Overview
Figure 2.6 F5 Motor/Encoder Setup Overview
Determine Motor Type
SErSP
Enter motor data -
LF.20 ... LF.25
Go to US.10, press FUNCTION until correct selection displayed then press ENTER
Enter encoder data -
LF.26 ... LF.29
Go to US.4, set the display to LOAD, then press ENTER indicates successful load.
If does not appear, refer to drive manual.
Check Correct Motor/Control The drive is set up at the factory to match your job configuration. However, before anything else, check that read-only parameter LF.4 displays the correct motor type:
• Induction geared/Closed Loop: ICLSd
• Induction gearless/Closed Loop: IgLSS
• PM Synchronous geared/Closed Loop: PCLSd
• PM Synchronous gearless/Closed Loop: PgLSS
Check Control Mode Drive parameter LF.02 determines control mode. Check that control mode is set to SerSP (Serial Speed Control).
2-20 Manual # 42-02-2P25
Motion 4000
Auto Tuning and Encoder Data Loading
Learn or Enter Motor Data In order to enter motor nameplate data into the drive or learn motor information, you must activate parameter LF.3 appropriately:
• conF (configuration): Operation troubleshooting (90 second time-out)
• S Lrn: Auto tuning drive to motor
• run: Sets drive to run mode
• I Lrn (inertia learn): Learns system inertial / activates FFTC.
• P Lrn (pole learn): Learns motor pole positions (see drive manual).
• StoP: Motor cannot run. Parameter changes allowed with serial control.
Note
When StoP is active, the drive will not respond to the direction inputs and therefore, the motor will not run.
Auto-tuning AC Induction Motors to the F5 Drive
Auto-tuning provides better drive to motor matching and performance than manually entering parameters. Before beginning, make sure that the following parameters have been loaded into the drive:
• Rated Motor Power (horsepower) (LF.10)
• Rated Motor Speed (rpm) (LF.11)
• Rated Motor Current (A) (LF.12)
• Rated Motor Frequency (Hz) (LF.13)
• Rated Motor Voltage (LF.14)
• Rated Power Factor (LF.15) (not viewable for PMAC machines)
1. Verify the controller is on Inspection operation. Remove one brake wire from the controller or reduce brake pick voltage level to prevent the brake from picking.
2. Reduce Inspection Speed F7, 155 to zero.
3. Set F7 parameter 141 Profile Scale to 000% (zero percent).
4. Set LF.3 to S Lrn. The display will change to StArt.
5. Hold the controller Enable button down and select the Up direction. The motor contactor should engage but the brake should not pick. Motor current will begin to flow and the drive display will change to LS103.
The drive will measure motor parameters as well as parameters in the drive motor stage. The drive display will change as different values are measured.
6. Continue holding the Enable and Up direction switch until the drive displays “done”
(five minutes is typical).
7. Release the Enable and Up direction switches. The drive will display CALC and complete updating its parameters.
8. Return the drive to Run mode (LF.3). Reconnect the brake wire. Return F7 parameter
141 Profile Scale to 100% and F7, 155 to its former setting.
If the auto-tune was not successful, the drive will report:
• FAIL: Auto-tuning was interrupted. Repeat the procedure.
• FAILd: There is a configuration error, probably an incorrectly set parameter, that is preventing the drive from beginning measurements.
• Check connections and parameters.
2
2-21
Installation
Manual Induction Motor Parameter Entry
The preceding instruction for auto-tuning the drive to the motor provides better performance and should be used instead of manual entry. If auto-tuning is not possible, use manual entry.
Figure 2.7 Entering Induction Motor Data
Enter motor data
INDUCTION Motors
LF.8 ... LF.17
LF.13 =
Motor Rated Frequency
Motor Overload
LF.8 = ON
LF.9 = Set to Motor FLA
LF.14 =
Motor Rated Voltage
LF.10 =
Motor Power (HP)
LF.15 =
Motor Power Factor
Start @ 0.9 (0.95 max)
Lower for stronger field
Higher weakens field
LF.11 =
Motor Rated Speed from motor nameplate
LF.16 =
Field Weakening Speed
Start @ 80% of sync speed. Reduce if motor does not reach contract speed
LF.12 =
Motor FLA
LF.17 =
Motor torque
Calculated (lb ft)
The Drive Manual
The information included above is very basic. If you are not familiar with the TORQMAX F5 drive, you must take a few minutes to look through the drive manual to learn how to proceed, what to expect, and what adjustments are available through the drive.
Setting the Drive to Run Mode
Parameter LF.3 allows the drive to be configured, to learn, or to be placed in run mode. To set the drive to run mode:
1. Set LF.3 to run.
2. Press
ENTER.
2-22 Manual # 42-02-2P25
Motion 4000
Auto Tuning and Encoder Data Loading
Magnetek AC Drive Introduction
Take the time to study the drive manual. It has very important startup and other information that are beyond the scope of this manual.
Digital Operator
The keypad and display are mounted on the digital operator.
Figure 2.8 Magnetek AC Drive
2
Digital Operator
HPV 600 drive shown. Other AC drives similar.
Keypad Operation
Please refer to “Magnetek Keypad Overview” on page 2-24 .
Clear Fault
Most faults clear automatically. If a persistent (serious) fault is displayed, the drive will shut down. To clear the fault after correcting the cause:
• Access the drive Faults F0 menu, submenu Active Faults, F1.
• Go to Reset Active Faults. Press Enter.
2-23
Installation
Figure 2.9 Magnetek Keypad Overview
Select Menu
Enter Submenus
Select Parameter
Select Digit
Change Value
Move Up a Level
Display 1 D0
Elevator
Data D1
Power
DATA D2
Adjust A0
Drive A1
ENTER
S-Curves
A2
Multistep
REF A3
Power
Convert A4
Motor A5
Configure C0
User
Switches C1
Logic
Inputs C2
Logic
Outputs C3
Analog
Outputs C4
Utility U0
ESCAPE
Magnetek AC Drive Menus & Submenus
Faults F0 Display 2 D0
Password
U1
Hidden
Items U2
Units U3
Ovrspeed
Test U4
Restore
Dflts U5
Active
Faults F1
Elevator
Data D1
Fault
History F2
Sorted
History F3
(900II)
Power
DATA D2
Reset Faults F4
(900II)
Drive Info
U6
Hex Monitor
U7
Language
Sel U8
(600CL, 600PM, 900PM, 900II)
Basics U9
(600, 900II)
Rotor
Alignment U10
(600PM, 900PM)
Autotune Sel U11
(900PM)
Autotune Time U11
(900II)
Changes are saved only after ENTER is pressed.
Some parameters cannot be changed while the elevator is operating.
Magnetek Drive Operation Overview
Menus, sub menus, and parameters may be accessed while the drive is running. Some parameters may not be changed while the drive is running. For these parameters, the word “LOCK-
OUT” appears.
Operator (HPV600/600PM/900/900PM) LEDs indicate the status of the drive:
• Run/Fault: The drive is in run mode. Operational status or a Fault code may be displayed.
• Sub Menu: A sub menu has been accessed.
• Data Ent: A parameter value has been accessed.
Operator (HPV 900II) LEDs indicate the status of the drive:
• Ready: Ready but not actually providing current to the motor.
• Run: Providing current to the motor.
• User: Selected via Logic Outputs C3 submenu.
• Fault: Drive has declared a fault.
• Torque Limit: The drive has reached its torque limit. See drive manual.
• Sub Menu: A sub menu has been accessed.
• Data Entry: A parameter value has been accessed.
2-24 Manual # 42-02-2P25
Motion 4000
Auto Tuning and Encoder Data Loading
Cover (HPV 900/900PM) LEDs indicate the status of the drive:
• Ready: Ready but not actually providing current to the motor.
• Run: Providing current to the motor.
• Program Invalid: No valid software on the drive control board.
• Fault: Drive has declared a fault.
• Torque Limit: The drive has reached its torque limit. See drive manual.
Drive Motor/Encoder Setup Overview
Figure 2.10 Magnetek Motor/Encoder Setup Overview
2
A1 Drive menu
Contract Car Speed
Contract Motor Speed
Brake Pick Time
Encoder Pulses
Mtr Torque Limit
Regen Torq Limit
0.0
900/900PM: C2 Logic Inputs menu
Logic Input 1 (TB1-1)
Logic Input 2 (TB1-2)
Logic Input 3 - 9
Drive Enable
Contact Cfirm
No Function
A2 S-Curves menu
Accel Rate 0
Decel Rate 0
Accel Jerk Out 0
Decel Jerk In 0
Decel Jerk Out 0
A4 Power Convert menu
Input L-L Volts
0.00
0.00
0.00
0.00
0.00
900II: C2 Logic Inputs menu
Logic Input 1 (TB1-6) Drive Enable
Logic Input 2 (TB1-7)
Logic Input 3 - 9
Contact Cfirm
No Function
600/600PM: C2 Logic Inputs menu
Logic Input 1 (TB1-16)
Logic Input 2 (TB1- 7)
Logic Input 3 - 9
Drive Enable
Contact Cfirm
No Function
A5 Motor Menu
Motor ID
Rated Mtr Power
Rated Mtr Volts
Rated Excit Freq
Rated Motor Curr
Motor Poles
Rated Mtr Speed
(4 or 6 pole)
900/900PM: C3 Logic Outputs menu
Logic Output 1 (TB1-14) Ready To Run
Logic Output 2 (TB1-15) Run Commanded
Logic Output 3 (TB1-16) Speed Reg Rls
Logic Output 4 (TB1-17) Ramp Down En
Relay Coil 1 (TB2-51/52/53) Ready to Run
Relay Coil 2 (TB2-54/55/56) Speed Reg Rls
C1 User Switches menu
Spd Command Src
Run Command Src
Spd Reg Type
Cont Confirm Src
Pre-Torque Source
Fault Reset Src
Ramped Stop Sel
Ramp Down En Src
Motor Ovrld Sel
Serial Mode
Serial
Serial
Elev Spd Reg
External
Serial
Serial
Ramp On Stop
Run Logic
Fault At Stop
Mode 1
900II: C3 Logic Outputs menu
Logic Output 1 (TB1-13) Ready To Run
Logic Output 2 (TB1-14) Run Commanded
Logic Output 3 (TB1-15) Speed Reg Rls
Logic Output 4 (TB1-16) Ramp Down En
Relay Coil 1 (TB2-27/28/29) Ready to Run
Relay Coil 2 (TB2-30/31/32) Speed Reg Rls
600/600PM: C3 Logic Outputs menu
Logic Output 1 (TB1-9) Ready To Run
Logic Output 2 (TB1-10) Run Commanded
Logic Output 3 (TB1-11) Speed Reg Rls
Logic Output 4 (TB1-12) Ramp Down En
Relay Coil 1 (TB2-51/52/53) Ready to Run
Relay Coil 2 (TB2-54/55/56) Speed Reg Rls
HPV900: C4 Analog Outputs menu
Analog Output 1 (TB1-33) Speed Command
Analog Output 2 (TB1-35) Speed Feedback
HPV900II: C4 Analog Outputs menu
Analog Output 1 (TB2-1) Speed Command
Analog Output 2 (TB2-8) Speed Feedback
HPV600: C4 Analog Outputs menu
Analog Output 1 (A0-A1) Speed Command
Analog Output 2 (A0-A2) Speed Feedback
HPV600PM: C4 Analog Outputs menu
Analog Output 1 (TB6-A01) Speed Command
Analog Output 2 (TB6-A02) Speed Feedback
2-25
Installation
Auto-tuning AC Motors to the Magnetek Drive
Auto-tuning provides better drive to motor matching and performance and must be performed at some point during installation or adjustment. Because the car must be run through the extent of the hoistway, this procedure should be accomplished after hoistway installations are sufficiently complete. Please refer to Adaptive Tuning in the Magnetek manual and follow those instructions.
Tuning Motor No-Load Current (HPV 600/900/900II Only) Please see Tuning No-Load Motor Current in the appendix of the Magnetek HPV AC Drive Technical Manual for specific steps.
Tuning Motor Flux Saturation Curve (HPV 600/900/900II Only) Please see Tuning Motor Flux Saturation Curve in the appendix of the Magnetek HPV AC Drive Technical Manual for specific steps.
Tuning Motor Rated RPM (HPV 600/900/900II Only) Please see Tuning
Rated Motor RPM in the appendix of the Magnetek HPV AC Drive Technical Manual for specific steps.
Determining System Inertia Please see Using the Software to Estimate the System
Inertia in the appendix of the Magnetek HPV AC Drive Technical Manual for specific steps.
The Drive Manual
The information included above is very basic. If you are not familiar with the Magnetek drive, you must take a few minutes to look through the drive manual to learn how to proceed, what to expect, and what adjustments are available through the drive.
2-26 Manual # 42-02-2P25
Motion 4000
Set Up for Construction Operation
Set Up for Construction Operation
If required, it is possible to run the car during construction to help complete work in the hoistway. In this mode, the car runs at inspection speed. If they are in place, cartop controls may be
used or the car may be run from the controller or a temporary run box. (Refer to Temporary
Run Box on page 2-50 .)
Minimal Requirements
Minimal equipment requirements are:
• The governor must be wired into the Safety string (SAFH).
• Car and counterweight must be roughly balanced.
Note
Typically, the counterweight is sized to equal the weight of the car with 40%, 45%, or 50% of its rated full load weight inside. At inspection speed, in the middle of the hoistway, with the car properly loaded, drive current readings (F5, LF.93 or Magnetek D0/D2 MOTOR CURRENT) should be equal in both up and down directions if counterweight/car balance is approximately correct. A balancing procedure is provided in this section but, before you attempt to run the car on Inspection, you must check that counterweighting has been addressed. Please refer to Car and Counterweight Balance on page 3-7 .
• Motor, brake, and drive connected and set up.
• Velocity encoder connected and functioning.
• Jumpers must be temporarily used to bypass absent equipment.
• The controller must be set to bypass faults on Inspection operation
Jumper Requirements
Temporary jumpers, as necessary, may be placed across the following connections if needed to
run the car on construction operation. If you are using a temporary run box, Please refer to
“Temporary Run Box” on page 2-50
.
Table 2.2 Construction Mode Jumper Requirements
From To
Panel Mount Terminal 15 SAFH HC-CTL-2 board (Safety String, Hoistway)
SAFH HC-CTL-2 board (Safety String, Hoistway) SAFC HC-CTL-2 board (Safety String, Car)
SAFC HC-CTL-2 board (Safety String, Car)
2 (120VAC)
ESC HC-CTL-2 board (In-car Emergency Switch)
GS HC-CTL-2 board (Gate Switch, car door locks)
2 (120VAC)
2 (120VAC)
2 (120VAC)
GSR HC-CTL-2 board (rear gate switch, car door locks)
DLAT HC-CTL-2 board (Door Lock Access Top, hall doors)
DLAB HC-CTL-2 board (Door Lock Access Bottom, hall doors)
2 (120VAC)
G0S1 (Governor overspeed switch)
RG7 (rope gripper)
INN HC-CTL-2 board
DLATR/DLABR HC-CTL-2 board (if rear door present)
GOS2 (Governor overspeed switch)
RG5 (rope gripper)
2 (120VAC)
2
2-27
Installation
Bypassing Faults on Inspection
Because the hoistway has not been set up yet, the car does not have direction limit inputs and will be prevented from moving properly in the hoistway unless the faults generated by this lack are bypassed. To bypass faults on Inspection mode:
1. On the MPU board, place switch F3 in the UP position (all others down).
2. On the HC-CTL-2 board, use a jumper to short the A-position pins of JP2 Fault Bypass.
3. Press N until the display shows Controller System Menu.
4. Press S to enter the menu.
5. Press N until the LCD displays Inspection Mode Fault Bypass OFF.
6. Press S to change bypass state to ON.
7. Set F3 back to the DOWN position.
This setting bypasses controller response to faults during Inspection operation.
IMPORTANT
Because the directional limits are not in place, if the car is not set to Bypass Faults on Inspection, it will not move down the hoistway.
Note
Note that there is an Automatic Mode fault bypass accessible through the Controller System
Menu as well. Be careful you are not setting it instead of Inspection Mode bypass.
Inspection mode fault bypass remains active, even across power cycles, until set to OFF. Automatic Mode fault bypass times out after two hours.
On Inspection Mode bypass, only overspeed faults are recognized.
Resolving Faults
If the car does not respond to a run command, check the HC-MPU board and drive displays for error/fault codes. Please refer to “Status and Error Messages” on page 5-2 .
Error codes are displayed individually in the order of detection. It is possible that, after you correct a current error condition, another will be displayed. All errors must be resolved before the car will operate properly.
Support for troubleshooting position and speed related faults is provided in Sections 4 and 5 of this manual. Please refer to “MPI Diagnostic Menu” on page 4-67 and to Section 5.
2-28 Manual # 42-02-2P25
Motion 4000
Set Up for Construction Operation
Speed and Acceleration Control
Motion 4000 generates the performance curve that controls the drive and transfers that information to the drive through a serial connection. Speed, acceleration, deceleration, and jerk parameters are set up through the F7 menu on the controller (HC-MPU board/controller on
Inspection/F7 function switch UP/all other function switches DOWN).
Even though speed and acceleration/deceleration/jerk parameters are determined by Motion
4000 settings, certain drive settings can still have a limiting effect and, if set incorrectly, can prevent the elevator from reaching commanded speed.
Drive gear ratio, rated RPM, contract speed, roping ratio, and sheave diameter settings dictate the fastest speed at which the drive will run the motor and must be accurately set on the drive.
In the illustration below, the dashed line labeled DRIVE CLIPPING illustrates what can happen to the S-curve if drive settings limit commanded speed. Rather than rolling into commanded speed, the car will drop into a steady speed state abruptly, will run at a less than commanded speed, and will drop into deceleration abruptly. So, improper drive settings can cause failure to achieve commanded speed and bumpy transitions at speed/acceleration transition points.
Figure 2.11 Example of Drive Clipping
Standard-F7:166
Manual-F7:171
Danger-F7:176
Alternate-F7:180
Roll Jerk
Roll Jerk
Standard
Standard-F7:168
Manual-F7:173
Alternate-F7:182
Acceleration
DRIVE CLIPPING
Alternate
DRIVE CLIPPING
Standard-F7:169
Manual-F7:174
Danger-F7:178
Deceleration
Manual
Danger
Standard-F7:165
Manual-F7:170
Danger-F7:175
Alternate-F7:179
Start Jerk
Leveling Speed (F7:158)
Zero Speed
F7-157 Correction Speed
Proximity Distance
Standard-F7:167
Manual-F7:172
Danger-F7:177
Alternate-F7:181
Stop Jerk
2
2-29
Installation
Required Drive Parameter Settings
In order to operate safely in construction, particular drive parameters must be verified and set.
These parameters are set at the factory according to your job requirements but MUST BE
CHECKED for correctness BEFORE PROCEEDING.
Caution
Before powering the controller to make these settings, verify that the Inspection/Normal switch is in the Inspection position.
TORQMAX F5 AC Drive Parameters
Set drive parameters using the drive keypad. If drive parameters are not correctly set, attempting to move the elevator can be VERY DANGEROUS. MCE sets these parameters before shipment, but you must check them at the site.
Danger
Drive parameters must be correctly set. If not, elevator control can be erratic and potentially
DANGEROUS. Never change drive parameters while the elevator is running.
1. Read the drive manufacturer manual shipped with this controller. It provides essential information about setting up the drive that cannot be included in the MCE manual. Follow the Initial Start-up procedure described in the drive manufacturer manual.
2. Read and follow the parameter settings in the table shipped with the controller from
MCE.
Table 2.3 Critical F5 Drive Parameters
Parameter
LF.02 Operating mode: SErSP
LF.04 Per Motor
LF.10 Rated motor power (HP)
LF.11 Rated motor speed
LF.12 Rated motor current
LF.13 Rated motor frequency
LF.14 Rated motor voltage
LF.17 Rated motor torque
LF.20 Contract speed
Parameter
LF.21 Traction sheave diameter
LF.22 Gear reduction ratio
LF.23 Roping ratio
LF.24 Load weight
LF.27 Encoder pulses
LF.30 Closed Loop: 2 d.LF.33 Ki speed offset decel
LF.42 High speed
US.35 Reference splitting: 40
The following drive parameter table is included for your convenience and in the event the table shipped with the controller is not available. Note that the table here reflects generic settings, not those specific to your installation. In the table, IM= induction motor; PM= permanent magnet motor.
2-30 Manual # 42-02-2P25
Motion 4000
Set Up for Construction Operation
Table 2.4 TORQMAX F5 Parameters
Display Parameter Description Unit Range Default Factory
WARNING: Do not change drive parameters while the elevator is running. Incorrect drive
parameter values can cause erratic operation.
WARNING: Parameters with an asterisk (*) must be set correctly for your specific motor / machine / job. Refer to the adjustment manual for detailed information.
LF. 2 bnSPd SerSP
LF. 3
LF. 4
LF. 5
LF. 8
LF. 9
LF.10
LF.11
Signal operating mode:
AbSPd - Absolute Analog Speed d SPd - Digital Speed Selection
A tor - Analog Torque Control
A Spd - Analog Speed Control
SerSP - Serial Com. Speed Control bnSPd - Binary Speed Selection
S POS – Serial Position feedback
Drive configuration: run- run mode conF - Configuration (5 minute time limit)
Stop - Drive stopped, Motor cannot run. Drive will not respond. When using serial com, this mode allows parameter changes
S Lrn - activate auto tune
I Lrn - Inertia Learn. Learns the system inertia and activates the FFTC.
P Lrn: Pole Learn. Learn the pole positions of
PM Motor
SPI - Stationary Pole Learn. Learn absolute encoder position for PM machine under brake without sheave movement.
(N/A for software Version 1.61)
OStST - Over speed test function. Allows car to over speed machine to test governor.
(N/A for software Version 1.61)
Motor-selection: Displays mode selected using US.
4 and US.10
ICLSd - Close loop induction
I9LSS = Closed loop induction gearless
PCLSd = Closed loop permanent magnet (PM)
P9LSS = Closed loop PM gearless
Drive fault auto reset
Electronic motor overload protection
IM - Electronic overload current
PM - not visible, auto set same as LF.12
IM - Rated motor power
PM - read only, auto calc.
Rated motor speed
-
-
1
-
A
HP
AbSPd d Spd
A tor
A Spd
SerSP
BnSPd
S POS run conF
Stop
S Lrn
I Lrn
P Lrn
SPI
OStST see US.10
0 - 10 on, off
1.0 - 110%
Drive rated conF
-
5 off
8.0
0.00 - 125.00 5.00
run
***
5 on
*
*
*
LF.12
LF.13
LF.14
Rated motor current
Rated motor frequency
Rated motor voltage
IM - Name plate rated voltage
PM - No-load, phase-to-phase back EMF rms voltage at LF.11
rpm 10.0 - 6000.0 1165 or
150
A 1.0 - 110%
Drive rated
8.0
Hz 4.0 - 100.0
60.0
V IM: 120 - 500V 230/460
PM: 1 -
32000V/krpm
*
*
*
2-31
2
Installation
Table 2.4 TORQMAX F5 Parameters
Display Parameter Description Unit Range Default Factory
LF.15
LF.16
LF.17
LF.18
LF.19
LF.20
LF.21
LF.22
LF.23
IM: Power factor, PM: not visible
IM: Field weakening speed, PM: not visible
Rated motor torque, IM - read only, auto calc.
PM - enter motor name plate torque
PM: Motor stator resistance - from data sheet or learn procedure (see F5 Drive manual) IM: not visible
PM: Motor leakage inductance - from data sheet or learn procedure (see F5 Drive manual)
IM: not visible
Contract speed
Traction sheave diameter (measured value)
Gear reduction ratio
Roping ratio
LF.24
LF.25
Load weight
Estimated gear ratio: Read only, auto calc.
0.LF.26 Encoder Interface: displays feedback type
LF.27
Encoder pulse number
For InclE and SinCo reference to customer data
For HIPEr set to 1024
For EndAt set to 2048
LF.28
Encoder channel swap / direction
0 nothing reversed
1 encoder A<B>B swapped
2 motor rotation reversed
3 motor rotation reversed, A<B>B swapped
LF.29
Encoder sample time
(recommend gearless = 4, geared = 8)
1 lb ft mH
1
0.50 - 1.00
rpm 0.0 - 6000.0
set @ 80% of LF.11
1 - 10000 ohm 0.0 - 49.999
0.01 - 500.00 1.00
fpm 0 - 1600
0 - 3 mSec 0.5 - 32
0.90
IM - calc.
PM - 18
49.999
inch 7.00 - 80.00
24.00
1
1
1.00 - 99.99
1 - 8
0
30.00
1 lbs 0 - 30000 0
0.01 1.00 - 99.99
-
ppr 256 - 16384
-
1024
0
4
0.90
*
IM - ***
PM
*
PM
*
PM
*
*
*
*
*
*
***
***
*
0
*
LF.30
Control mode
0, 1Open loop induction motor operation
2 - Closed loop speed control (LF. 2 = A Spd)
3 - Closed loop speed control with pre-torque
4 - Closed loop torque control (LF. 2 = A tor)
5 - Close loop speed control with synthesized pretorque
A.LF.31 Kp speed accel: Proportional gain, accel & run d.LF.31 Kp speed decel: Proportional gain, decel
P.LF.31
Kp speed torque (Synth. Pre-torque)
A.LF.32 Ki speed accel: Integral gain, accel & run d.LF.32 Ki speed decel: Integral gain, decel
P.LF.32
KI speed torque (Synth. Pre-torque)
A.LF.33 Ki speed offset accel: Gain at low speed, accel d.LF.33 Ki speed offset decel: Gain at low speed, decel
0.LF.36 Maximum torque (Auto calc by the drive).
1
1
1
1
1
1
1
1
0 - 5
1 - 50396
1 - 50396
1 - 50396
1 - 26214
1 - 26214
1 - 26214
0 - 8000
0
3000
3000
2000
350
250
10000
3000
*
** 3000
** 3000
2000
** 350
** 250
10000
** 3000
1 0 - 8000 1000 ** 1000 lb ft 0 - 500%Trtd Calculated ***
1.LF.36 Maximum torque emergency operation (=LF.17) lb ft 0 - 500%Trtd Calculated ***
LF.37
Open loop torque boost: Open loop op. only % 0 - 25.5
5.0
5.0
LF.38
Carrier frequency; 0 = 8 KHz, 1 = 16KHz
(Note: set LF.38 = 0 if E.OL2 error on drive)
1 0, 1 0 *
2-32 Manual # 42-02-2P25
Motion 4000
Set Up for Construction Operation
Table 2.4 TORQMAX F5 Parameters
Display Parameter Description Unit Range Default
LF.41
LF.42
LF.43
LF.44
Leveling speed (Not used, must set to 0)
High speed (Not used, must set to 0)
Inspection speed (Not used, must set to 0)
High leveling speed (Not used, must set to 0) fpm 0 - 25 fpm 0.0 - LF.20
0.0
0.0
fpm 0.0 - 150.00
0.0
fpm 0.0 - LF.20
0.0
LF.45
LF.46
LF.47
LF.49
Earthquake Speed (Not used, must set to 0) fpm 0.0 – 150.0
Emergency Pwr Speed (Not used, must set to 0) fpm 0.0 - LF.20
Intermediate speed (Not used, must set to 0)
Over speed function Test (N/A for SW Version 1.61 and lower)
0.LF.50 Profile 0 - Starting jerk (not used)
0.LF.51 Profile 0 - Acceleration (not used) fpm 0.0 - LF.20
fpm 1- 2400 ft/s
3 ft/s
2
0.LF.52 Profile 0 - Acceleration jerk (not used)
0.LF.53 Profile 0 - Deceleration jerk (not used) ft/s
3 ft/s
3
0.LF.54 Profile 0 - Deceleration (not used)
0.LF.55 Profile 0 - Approach jerk (not used) ft/s
2 ft/s
3
1.LF.50 Profile 1 - Starting Jerk (not used) ft/s
3
0.0
0.0
0.0
100
1.LF.51 Profile 1 - Acceleration (not used) ft/s
2
1.LF.52 Profile 1 - Acceleration jerk (not used) ft/s
3
1.LF.53 Profile 1 - Deceleration jerk (not used)
1.LF.54 Profile 1 - Deceleration (not used)
1.LF.55 Profile 1 - Approach jerk (not used)
2.LF.50 Profile 2 - Starting jerk (not used)
2.LF.51 Profile 2 - Acceleration (not used)
2.LF.52 Profile 2 - Acceleration jerk (not used)
2.LF.53 Profile 2 - Deceleration jerk (not used) ft/s
3 ft/s
2 ft/s
3 ft/s
3 ft/s
2 ft/s
3 ft/s
3
2.LF.54 Profile 2 - Deceleration (not used) ft/s
2
2.LF.55 Profile 2 - Approach jerk (not used) ft/s
3
LF.56
Stop jerk (not used)
LF.57
LF.58
LF.59
ft/s
3
1
% off, on
0 - 30 sec 0.0 -1.0
1
10
1.0
LF.61
LF.67
LF.68
LF.69
LF.70
LF.71
LF.76
LF.77
Speed following error (0 = off, 1 = on,)
Speed difference
Trigger time speed difference: Following error timer
Emergency operation mode. If using an MCE
TAPS, (Traction Auxiliary Power Supply) this must be set to di1.
Pre-torque gain
Pre-torque offset
Pre-torque direction (0, 1 = +V, -1 = -V)
Speed pick delay (Delay to turn on DRO)
Brake pick delay
Encoder resolution multiplier
2 for incremental encoder
8 for Sin/Cos, EnDat or Hiperface encoder
Absolute encoder position (measured)
-
%
1
1
1
Off, SPd1,
SPd2, SPd3, di1
0.25 - 2.00
sec 0.0 - 3.0
sec 0.0 - 3.0
0 - 13
0 - 65535h off
1.00
-100.0 - 100.0 0.00
0, 1, -1 1
0.30
0.05
2
0 *0
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
1
10
1.0
Factory
0.0
0.0
0.0
0.0
0.0
0.0
0.0
100 off
(di1 if TAPS used)
1.00
0.00
1
0.30
0.05
2
2-33
Installation
Table 2.4 TORQMAX F5 Parameters
Display Parameter Description Unit Range Default Factory
LF.78
Brake drop delay. Time motor will hold full current and control after direction inputs drop.
LF.79
Current hold time. Delay in turning off the drive
(Delay to turn OFF the motor current after the direction is dropped and LF.78 has expired)
Diagnostic Parameters (Read only)
LF.25
LF.80
LF.81
LF.82
LF.83
LF.86
LF.87
LF.88
Estimated gear ratio
Software version
Software date
X2A input state
X2A output state
Operation mode
Actual inverter load (100% = rated load)
Motor command speed sec sec
A
A
-
-
1
-
-
-
% rpm rpm ft/m
V
V
Hz
-
0.00 - 3.00
0.00 - 3.00
see tables in F5 Drive
Manual
0.50
0.30
0.50
0.30
LF.89
LF.90
LF.93
LF.94
Actual motor speed
Actual elevator speed
Phase current
Peak phase current
LF.95
LF.96
Actual DC voltage
Peak DC voltage
LF.97
Actual output frequency
O.LF.98 Last error
US Parameters
US. 1 Password: With different passwords different parameter groups can be accessed for advanced programming.
US. 3 Load defaults: Select LoAd and press ENTER to cause all LF parameters to be reset to drive default values.
US. 4 Load configuration: Select LoAd and press ENTER to load the configuration selected in US.10.
US.10
Select configuration: Selects the drive mode.
ICLSd - Close loop induction
I9LSS = Closed loop induction gearless
PCLSd = Closed loop permanent magnet (PM)
P9LSS = Closed loop PM gearless
-
-
-
-
-
LoAd
LoAd
ICLSd
I9LSS
PCLSd
P9LSS
-
-
-
-
-
*
US.34
Analog Pattern Gain
US. 35 Reference Splitting: This function creates a slope between two successive serially transmitted speed values. This parameter should be adjusted for a time double the actual serial update rate of the speed command
Note: Program to 40 msec for M4000 controller with Rev8
0.01-20.0
mSec 0 –200 mSec
1.0
0.0
40
* Parameters are motor / machine / job dependent.
** Recommended but field adjustable.
*** The value is automatically calculated from the motor data or other parameter values.
Parameters for Drive Software Version (LF 80 Drive Software = 1.61 with LF.81 date code = 2801.9 or later) or (LF 80 Drive Software = 1.71 with LF.81 date code = 704.0 or later.
2-34 Manual # 42-02-2P25
Motion 4000
Set Up for Construction Operation
Magnetek AC Drive Parameters
With the exception of those parameters listed earlier (Magnetek Motor/Encoder Setup Overview on page 2-25), all Magnetek parameters should be left at default values.
Note
Before changing any A5 Motor Menu parameters, make sure the A5 Motor ID parameter is set.
Setting Motor ID loads nominal values into select parameters in the A5 menu.
The following drive parameter table is included for your convenience and in the event the table shipped with the controller is not available. In any case, you should use the table to verify all settings on the elevator drive.
Table 2.5 Magnetek AC Drive Table
# Display Parameter Description Unit Range Defaults Factory
Adjust A0
A1 Drive
Contract Car Spd Elevator Contract Speed
Contract Mtr Spd Motor Speed at elevator contract speed
Response Speed regulator sensitivity. If set too high, motor current and speed will be jittery. If too small, the motor will be sluggish.
Inertia System inertia
Inner Loop Xover Inner speed loop crossover frequency (only with Ereg speed regulator)
Brake Pick Time
Brake Hold Time
Time before a brake pick fault is declared
Time before a brake hold fault is declared fpm 0 - 1500 rpm 50 - 3000 rad/ sec
1.0 - 20.0
Gain Reduce Mult Speed regulator response percentage to use in low gain Mode. 100% = no reduction.
%
Gain Chng Level
Tach Rate Gain
Speed level to change to low gain mode
(only with internal gain switch)
Compensates for rope resonance. Use only after A1, Inertia, and A1, Response, have been set correctly.
Spd Phase Margin Phase margin of speed regulator
(only with PI speed regulator)
%
% o
10 - 100
0 - 100.0
0 - 30.0
45 - 90
Ramped Stop Time Time to ramp from rated torque to zero (only with torque ramp down stop function)
Contact Flt Time Time before a contactor fault is declared sec 0 - 2.50
sec 0.10 - 5.00
400
1130
10 sec 0.25 - 50.00
2.0
rad/ sec
0.1 - 20.0
2.0
100 sec sec
0 - 5.00
0 - 5.00
100
0
80
0.20
0.50
1.00
0.20
Overspeed Level Threshold for detection of overspeed fault
Overspeed Time
Overspeed Mult
Time before an overspeed fault is declared
Multiplier for overspeed test (U4)
Encoder Pulses
Spd Dev Time
Encoder counts per revolution
Spd Dev Lo Level Range around the speed reference for speed deviation low logic output
Time before speed deviation low logic output is true
% 100.0 - 150.0 115.0
sec 0 - 9.99
% 100 - 150
1.00
125 ppr 600 - 10000 1024
% 00.1 - 10.0
10 sec 0 - 9.99
0.5
10
2.0
2.0
100
100
0
80
0.20
0.80
0.0
0.20
115.0
1.00
125
10
0.5
2-35
2
Installation
Table 2.5 Magnetek AC Drive Table
# Display Parameter Description
Spd Dev Hi Level Level for declaring speed deviation alarm
Unit
%
Range
0 - 99.9
Defaults Factory
10.0
Spd Command Bias Subtracts an effective voltage to actual speed command voltage volts 0 - 6.00
Spd Command Mult Scales analog speed command
Pre Torque Bias Subtracts an effective voltage to actual pre torque command voltage
0.90 - 5.00
volts 0 - 6.00
Pre Torque Mult Scales pre-torque command
Zero Speed Level Threshold for zero speed logic output
Zero Speed Time Time before zero speed logic output is declared true
-
%
0.00
1.00
0.00
-10.00-10.00 1.00
0 - 99.99
sec 0 - 9.99
1.00
0.10
Up/Dwn Threshold Detection threshold, up or down direction
Mtr Torque Limit Motoring torque limit. Torque Limit LED will light when this limit is reached.
%
%
Regen Torq Limit Regenerating torque limit. Torque Limit LED will light when this limit is reached.
Flux Wkn Factor Defines torque limit at higher speeds
%
%
Ana 1 Out Offset Subtracts an effective voltage to actual analog output 1
%
Ana 2 Out Offset Subtracts an effective voltage to actual analog output 2
%
Ana 1 Out Gain
Ana 2 Out Gain
Flt Reset Delay
Flt Reset / Hour
Scaling factor for analog output 1
Scaling factor for analog output 2
Time Before a fault is automatically reset
Number of faults allowed to reset automatically per hour
0 - 9.99
0 - 275.0
0 - 275.0
60.0 - 100.0
-99.9 - 99.9
-99.9 - 99.9
-
-
0 - 10.0
0 - 10.0
sec 0 - 120 fault 0 - 10
1.00
200.0
200.0
100.0
0.00
0.00
1.0
1.0
5
3
Up to SPD. Level The logic output function is true when the motor speed is above the user specified speed defined here
%
Mains DIP Speed When enabled by the Main DIP Speed (A1) parameter, speed is reduced by this percent when an undervoltage alarm is declared
%
0 - 110.00
5 - 99.9
Run Delay Timer Delays drive recognition of RUN signal.
sec 0.00 - 0.99
AB Zero Spd Lev Auto Brake Function - N/A to MCE products % 0.00 - 2.00
080.00
25.00
0.00
0.00
AB Off Delay N/A to MCE products
Contactor DO Dly N/A to MCE products
TRQ Lim Msg Dly Time duration drive is in torque limit before
Hit Torque Limit message displayed.
SER2 INSP SPD Defines the serial mode 2 Inspection
(only serial mode 2) sec sec 0.00 - 5.00
0.00
sec 0.00 - 10.00
0.50
ft/ min
0.00 - 9.99
0 - 100
SER2 RS CRP SPD Creep speed used in “rescue mode”
SER2 RS CPR Time Maximum time drive will continue to run at rescue creep speed (only serial mode 2)
SER2 FLT TOL Maximum time that may elapse between valid run time messages before a serial fault is declared (only serial mode 2) ft/ min sec
0 - 300
0 - 200 sec 0.0 - 2.0
Rollback Gain Anti-rollback gain 1 - 20
0.00
30
10
180
0.04
1
10.0
0.00
1.43
0.00
1.00
1.00
0.10
1.00
200.0
200.0
100
0.00
0.00
1.0
1.0
5
3
080.00
25.00
0.00
0.00
0.00
0.00
0.50
30
10
180
0.04
1
2-36 Manual # 42-02-2P25
Motion 4000
Set Up for Construction Operation
Table 2.5 Magnetek AC Drive Table
# Display
Notch Filter Frq
Notch Filt Depth
MSPD Delay 1-4
Parameter Description Unit Range
Notch Filter Center Frequency Hz 5 - 60
Notch filter maximum attenuation % 0 - 100
Recognition time delay for a defined multistep speed command sec 0.00 - 10.0
A2 S-Curves
Accel Rate 0
Decel Rate 0
Accel Jerk in 0
Accel Jerk out 0
Decel Jerk in 0
Decel Jerk out 0
Accel Rate 1
Decel Rate 1
Accel Jerk in 1
Accel Jerk out 1
Decel Jerk in 1
Decel Jerk out 1
Accel Rate 2
Decel Rate 2
Accel Jerk in 2
Accel Jerk out 2
Decel Jerk in 2
Decel Jerk out 2
Accel Rate 3
Decel Rate 3
Accel Jerk in 3
Accel Jerk out 3
Decel Jerk in 3
Decel Jerk out 3
Acceleration rate #0 ft/s
2
Deceleration rate #0
Rate of increase of acceleration, up to ACCEL
Rate, when increasing elevator speed ft/s
2 ft/s
3
Rate of decrease of acceleration to zero when approaching contract elevator speed ft/s
3
Rate of increase of deceleration, up to Decel
Rate, when decreasing elevator speed ft/s
3
Rate of decrease of deceleration to zero when slowing the elevator to leveling speed ft/s
3
Acceleration rate #1 ft/s
2
Deceleration rate #1 ft/s
2
Rate of increase of acceleration, up to ACCEL
Rate, when increasing elevator speed ft/s
3
Rate of decrease of acceleration to zero when approaching contract elevator speed ft/s
3
Rate of increase of deceleration, up to Decel
Rate, when decreasing elevator speed
Acceleration rate #2 ft/s
Rate of decrease of deceleration to zero when slowing the elevator to leveling speed ft/s
3 ft/s
3
2
Deceleration rate #2 ft/s
2
Rate of increase of acceleration, up to ACCEL
Rate, when increasing elevator speed ft/s
3
Rate of decrease of acceleration to zero when approaching contract elevator speed ft/s
3
Rate of increase of deceleration, up to Decel
Rate, when decreasing elevator speed
Acceleration rate #3
Deceleration rate #3 ft/s
Rate of decrease of deceleration to zero when slowing the elevator to leveling speed ft/s
3 ft/s
3
2 ft/s
2
Rate of increase of acceleration, up to ACCEL
Rate, when increasing elevator speed ft/s
3
Rate of decrease of acceleration to zero when approaching contract elevator speed ft/s
3
Rate of increase of deceleration, up to Decel
Rate, when decreasing elevator speed ft/s
3
Rate of decrease of deceleration to zero when slowing the elevator to leveling speed ft/s
3
0 - 7.99
0 - 7.99
0 - 29.9
0 - 29.9
0 - 29.9
0 - 29.9
0 - 7.99
0 - 7.99
0 - 29.9
0 - 29.9
0 - 29.9
0 - 29.9
0 - 7.99
0 - 7.99
0 - 29.9
0 - 29.9
0 - 29.9
0 - 29.9
0 - 7.99
0 - 7.99
0 - 29.9
0 - 29.9
0 - 29.9
0 - 29.9
Defaults Factory
20
0
0.00
20
0
0.00
8.0
8.0
8.0
8.0
8.0
3.00
3.00
8.0
3.00
3.00
8.0
8.0
3.00
3.00
8.0
8.0
8.0
8.0
3.00
3.00
8.0
8.0
8.0
8.0
0.0
0.0
0.0
0.0
0.0
0.00
0.00
0.0
0.00
0.00
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.00
0.00
0.0
0.0
0.0
0.0
2
2-37
Installation
Table 2.5 Magnetek AC Drive Table
# Display Parameter Description
A3 Multistep Ref
Speed Command 1 Multi-Step Speed command #1
Speed Command 2 Multi-Step Speed command #2
Speed Command 3 Multi-Step Speed command #3
Speed Command 4 Multi-Step Speed command #4
Speed Command 5 Multi-Step Speed command #5
Speed Command 6 Multi-Step Speed command #6
Speed Command 7 Multi-Step Speed command #7
Speed Command 8 Multi-Step Speed command #8
Speed Command 9 Multi-Step Speed command #9
Speed Command 10 Multi-Step Speed command #10
Speed Command 11 Multi-Step Speed command #11
Speed Command 12 Multi-Step Speed command #12
Speed Command 13 Multi-Step Speed command #13
Speed Command 14 Multi-Step Speed command #14
Speed Command 15 Multi-Step Speed command #15
Unit Range
ft/m -3000.0-3000.0
0 ft/m -3000.0-3000.0
0 ft/m -3000.0-3000.0
0 ft/m -3000.0-3000.0
0 ft/m -3000.0-3000.0
0 ft/m -3000.0-3000.0
0 ft/m -3000.0-3000.0
0 ft/m -3000.0-3000.0
0 ft/m -3000.0-3000.0
0 ft/m -3000.0-3000.0
0 ft/m -3000.0-3000.0
0 ft/m -3000.0-3000.0
0 ft/m -3000.0-3000.0
0 ft/m -3000.0-3000.0
0 ft/m -3000.0-3000.0
0
Defaults Factory
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
A4 Power Convert
Id Reg Diff gain Flux Current regulator differential gain
Id Reg Prop Gain Flux current regulator proportional gain
Iq Reg Diff Gain Torque current regulator differential gain
Iq Reg Prop Gain Torque current regulator proportional gain
PWM Frequency
UV Alarm Level
Carrier frequency
Level for undervoltage alarm
UV Fault Level Level for undervoltage fault
Extern Reactance External choke reactance
Input L-L Volts Nominal line-line AC input Voltage, RMS
A5 Motor
Motor ID Motor Identification
Rated Mtr Power
Rated Mtr Volts
Rated motor output power
Rated motor terminal RMS voltage
Rated Excit Freq Rated excitation frequency
Rated Motor Curr Rated motor current
Motor Poles Motor poles
Rated Mtr Speed Rated motor speed at full load
% No Load Curr Percent no load current
Stator Leakage X Stator leakage reactance
Rotor Leakage X
Stator Resist
Rotor leakage reactance
Stator resistance
Motor Iron Loss Iron loss at rated frequency
Motor Mech Loss Mechanical loss at rated frequency
Ovld Start Level Maximum continuous motor current
-
-
-
-
0.80 - 1.20
0.20 - 0.40
0.80 - 1.20
0.20 - 0.40
kHz 2.5 - 16.0
% 80 - 99
%
%
50 - 88
0 - 10 volts 110 - 480
1.00
0.30
1.00
0.30
10.0
80
80
0
Drive dep.
1.00
0.30
1.00
0.30
10.0
90
80
0
%
%
%
%
%
%
%
4 Pole DFLT, 6
Pole DFLT
HP 1.0 - 500 0.0
volts 190.0 - 575.0 0.0
Hz 5.0 - 400.0
0.0
amps 1.00 - 800.00 0.00
2 - 32 0
RPM 5.0 - 3000.0
0.0
10.0 - 80.0
0 - 20.0
0 - 20.0
0 - 20.0
0 - 15.0
0 - 15.0
100 - 150
Per ID
Per ID
Per ID
1.5
0.5
1.0
110
1.5
0.5
1.0
110
2-38 Manual # 42-02-2P25
Motion 4000
Set Up for Construction Operation
Table 2.5 Magnetek AC Drive Table
# Display
Ovld Time Out
Flux Sat Break
Flux Sat Slope 1
Flux Sat Slope 2
Parameter Description
Time that defines motor overload curve
Flux saturation curve slope change point
Flux saturation curve slope for low fluxes
Flux saturation curve slope for high fluxes
Configure C0
C1 User Switches
Spd Command Src Speed Command Source -
Unit Range
sec 5.0 - 120.0
%
%
%
0 - 100
0 - 200.0
0 - 200.0
Defaults Factory
60.0
75
0
50
60.0
75
0
50
Run Command Src Run Command Source
Hi/Lo Gain Src High / low gain change switch source
Speed Reg Type Chooses speed regulator
-
-
-
Motor Rotation Allows user to reverse direction of motor rotation
-
Spd Ref Release Determines when speed reference release is asserted
-
Cont Confirm Src Enables external logic input for contactor confirmation.
-
Pre Torque Source Enables and determines the source of the pre torque command
-
Pre Torque Latch Determines if analog pre-torque command is latched
-
PT torq Latch Clck Determines source of pre torque latch control
(if used)
-
Fault Reset Src Fault reset source -
Overspd Test Src Determines external logic source to trigger overspeed test
Brake Pick Src If drive controls mechanical brake, determines source of brake pick command
-
-
Brake Pick Cnfrm Enables a logic input to use for brake pick confirmation
-
Brake Hold Src If drive controls mechanical brake, determines source of brake hold command
-
Ramped Stop Sel Selects normal stop or torque ramp down stop -
None
Analog input
Serial
Not latched
Latched
External TB
Serial
External TB
Serial
Automatic
External TB
Serial
Internal
Serial
None
External TB
Internal time
Internal
Serial
None
Ramp on stop
Analog input
Multi-step
Serial multi-step
Serial
External TB
Serial
Serial+extern
External TB
Serial
Internal
Elev spd reg
Pi speed reg
External reg
Forward
Reverse
Multi-step Serial
External
TB
Elev spd reg
Serial
Internal Internal
Elev spd reg
Reg release
Brake picked
None
External TB
Forward Forward or
Reverse
Reg release
Reg release
None External
TB
None Serial
Not latched
External tb
External tb
External tb
Not
Latched
External
TB
Serial
External tb
Internal Internal
None
Internal
None
None
Internal
Ramp on
Stop
2
2-39
Installation
Table 2.5 Magnetek AC Drive Table
# Display Parameter Description
Ramp Down En Src Determines the source that signals the torque ramp down stop (if used)
-
Unit
Brk Pick Flt Ena
Brk Hold Flt Ena
Ext Torq Cmd Src
Dir Confirm
Brake pick fault enable
Brake hold fault enable
When Speed Reg Type = External Reg, sets the source of the torque command
-
-
-
Range
External TB
Run logic
Serial
Enable
Disable
Enable
Disable
None
Serial
Analog input
Enabled
Disabled
S-Curve Abort
Fast Flux
Main DIP Ena
DB Protection
Encoder Fault
Confirms proper analog signal polarity when enabled and a logic input is programmed to
Run Up and Run Down
Addresses how the S-Curve Speed Reference
Generator handles a reduction in the speed command before the S-Curve Generator has reached its target speed.
Reduces starting takeoff time by reducing motor fluxing time
Dynamic braking Protection fault or alarm selection
Temporarily disables the Encoder Fault
-
-
-
Enables the Mains DIP Speed (A1) parameter that reduces speed when an undervoltage alarm is declared
-
-
Enabled
Disabled
Enabled
Disabled
Enabled
Disabled
Stopping Mode
Motor Ovrld Sel
Auto Stop
Serial Mode
SER2 FLT Mode
MLT-SPD to DLY2
Determines stopping mode when Spd Command Src = multi-step
Motor Overload Selection
Auto Stop Function enable
Serial Protocol selection
-
-
-
-
Defines reaction to a serial communication fault while in Serial Mode 2 (Only serial mode
2)
-
DRV Fast Disable Addresses how fast the drive responds to the removal of Drive Enable logic input.
MLT-SPD to DLY1 Assigns multi-step speed command to recognition delay timer 1
Assigns multi-step speed command to recognition delay timer 1
-
-
Fault
Alarm
Enabled
Disabled
Immediate
Ramp to stop
Alarm
Flt Immediate
Fault at Stop
Disable
Enable
None
Mode 1
Mode 2
Mode 2 test
Immediate
Run remove rescue
Disable
Enable
None mspd1mspd15
None mspd1mspd15
Defaults Factory
External tb
Run Logic
Disable
Disable
None
Disabled Disable
Disabled Disable
Disabled Disabled
Disabled Disable
Fault
Enabled Enable
Immediate
Alarm
Disable
None
Immediate
Disable
None
None
Disable
Disable
None
Fault
Immediate
Fault at stop
Disable
Mode 1
Immediate
Disable
None
None
2-40 Manual # 42-02-2P25
Motion 4000
Set Up for Construction Operation
Table 2.5 Magnetek AC Drive Table
# Display Parameter Description
MLT-SPD to DLY3 Assigns multi-step speed command to recognition delay timer 1
MLT-SPD to DLY4 Assigns multi-step speed command to recognition delay timer 1
-
Unit
-
Range
None mspd1mspd15
None mspd1mspd15
C2 Logic Inputs
Log In 1 TB1-1 Terminal 1 Selection -
Log In 2 TB1-2 Terminal 2 Selection -
Log In 3 TB1-3
Log In 4 TB1-4
Log In 5 TB1-5
Log In 6 TB1-6
Log In 7 TB1-7
Log In 8 TB1-8
Log In 9 TB1-9
Terminal 3 Selection
Terminal 4 Selection
Terminal 5 Selection
Terminal 6 Selection
Terminal 7 Selection
Terminal 8 Selection
Terminal 9 Selection
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Defaults Factory
None None
None None
DRIVE
ENABLE
RUN
STEP REF
B1
DRIVE
ENABLE
CON-
TACT
CFIRM
FAULT
RESET
UP/DWN NO
FUNC-
TION
S-CURVE
SEL 0
NO
FUNC-
TION
STEP REF
B0
NO
FUNC-
TION
NO
FUNC-
TION
STEP REF
B2
EXTERN
FAULT 1
NO
FUNC-
TION
NO
FUNC-
TION
C3 Logic Outputs
Log Out 1 tb1-14 Terminal 14 Selection
Log Out 2 tb1-15 Terminal 15 Selection
Log Out 3 tb1-16 Terminal 16 Selection
Log Out 4 tb1-17 Terminal 17 Selection
Relay Coil 1
Relay Coil 2
Relay 1 Function Selection
Relay 2 Function Selection
-
-
-
-
-
-
-
-
-
-
-
-
READY
TO RUN
RUN COM-
MAND
RUN
COM-
MAND
MTR
OVER-
LOAD
SPEED
REG RLS
ENCODER
FAULT
RAMP
DOWN EN
FAULT
SPEED
REG RLS
READY
TO RUN
SPEED
REG RLS
2
2-41
Installation
Table 2.5 Magnetek AC Drive Table
# Display Parameter Description
C4 Analog Outputs
Ana Out 1 tb1-33 Terminal 33 Selection
Ana Out 2 tb1-35 Terminal 35 Selection
Utility U0
U1 Password
U2 Hidden Items
U3 Unit
U4 Overspeed Test
U5 Restore Dflts
U6 Drive Info
U7 HEX Monitor
Password -
Enable or disable hidden parameters
Enable Disable
Unit for parameters
English Metric
Allows overspeed test during inspection
Yes No
Reset all parameters to default values
-
-
-
Drive information:
Drive Version:
Boot Version:
Cube ID:
Drive Type:
Hex Monitor
-
-
Unit
-
-
-
-
-
-
Range Defaults Factory
SPEED
REF
SPEED
FEEDBK
SPEED
CMD
SPEED
FEEDBK
000000 000000
ENABLE ENABLE
ENGLISH ENGLISH
No No
2-42 Manual # 42-02-2P25
Motion 4000
Set Up for Construction Operation
Required Controller Parameter Settings
Before attempting to move the car, you must verify drive parameters as described in
TORQ-
MAX F5 AC Drive Parameters on page 2-30
or
see “Magnetek AC Drive Table” on page 2-35
.
Acceleration and Deceleration Rates
Acceleration and deceleration rates are measured and programmed in ft/s
2
(feet per second per second). Jerk parameters adjust the rate of transition from one speed to another and are measured and programmed in ft/s
3
(feet per second per second per second). F7 control parameters correspond to curve locations as shown in the following figure. Increasing S-Curve values generally results in more aggressive runs and shorter flight times.
Figure 2.12 Motion 4000 Performance Curves
Standard-F7:166
Manual-F7:171
Danger-F7:176
Alternate-F7:180
Roll Jerk
Roll Jerk
Standard
Alternate
Standard-F7:168
Manual-F7:173
Alternate-F7:182
Acceleration
Standard-F7:169
Manual-F7:174
Danger-F7:178
Deceleration
Manual
Danger
Standard-F7:165
Manual-F7:170
Danger-F7:175
Alternate-F7:179
Start Jerk
Leveling Speed (F7:158)
Zero Speed
F7-157 Correction Speed
Proximity Distance
Curves Used for Operating Speeds
The performance curves shown above and the operating speeds that use them are:
• Standard Curve: Contract, correction, earthquake, and leveling speed
• Alternate Curve: Conservation, and emergency power speed
• Manual Curve: Inspection and reduced inspection speed
• Danger “Curve”: Used for emergency deceleration
Standard-F7:167
Manual-F7:172
Danger-F7:177
Alternate-F7:181
Stop Jerk
2
2-43
Installation
The F7 Menu
Through the F7 menu, you can restore and/or adjust settings for terminal, position, and motion parameters. With the car on Inspection and the F7 function switch in the UP position, the N button is used to cycle between the two (Restore or Adjust) menus.
Important Once set at the factory, F7 parameters are protected by positioning a jumper on the HC-CTL-2 board. Before you can access F7 parameters, you must set the jumper appropriately:
F7 SETTABLE
Restore Parameters
Parameters are stored on both the HC-CTL-2 and the TC-MPI boards. The parameters stored on either board may be used to restore (synchronize) those stored on the other:
1. Place the car on Inspection operation.
2. Set the F7 function switch in the UP position.
3. Press N until the LCD displays PARAMETER RESTORE MENU. Press S to select.
The LCD will display RESTORE SETTINGS FROM: followed by the currently selected board
(HC-CTL or TC-MPI).
4. Press + or - to display the desired board. Press S to restore (or N to return to the previous menu).
The LCD will provide read and restore status and direct you to press N to return to the last viewed or edited parameter.
Changing Parameters
1. Place the car on Inspection operation.
2. Set the F7 function switch to the up position.
3. Press N until the LCD displays PARAMETER ADJUST MENU. Press S to select. The
LCD will display ADJUST FROM N=LAST / S=START.
• Press N to begin adjustment from the last viewed or edited parameter.
• Press S to begin adjustment starting with the first F7 parameter.
4. Once viewing parameters:
• Press N to move through the parameters listings.
• Press + or - to change a displayed parameters value.
• To move back to a previous parameter, press and hold N (Next) then press - (minus) as needed
• Press S to save changed parameters.
2-44 Manual # 42-02-2P25
Motion 4000
Set Up for Construction Operation
Controller Motion Parameters
The following F7 parameters must be checked before you attempt to move the car.
Table 2.6 F7 Menu Settings TORQMAX
# Item Default Recommended
148 Hoist-motor speed +1165.0 rpm Per Job
155 Inspection speed (normal) +50 fpm As desired
170 Manual start jerk
171 Manual roll jerk
+1.00 ft/s3
+1.00 ft/s3
+1.00 ft/s3
+1.00 ft/s3
172 Manual stop jerk
173 Manual acceleration
174 Manual deceleration
184
185
194
Drive type option
Brake type option
Normal brake pick voltage
+1.00 ft/s3
+0.50 ft/s2
+0.50 ft/s2
KEB F5-GRD50
DISCRETE
+1.00 ft/s3
+0.50 ft/s2
+0.50 ft/s2
KEB LF.80 = View LF.80
LF.80 = 1.71 or greater: F5-GRD50 (geared) or
F5-GLS50 (gearless)
LF.80 = Other: F5-GRD49 (geared) or
F5-GLS49 (gearless)
If the controller has a brake module(s): One Module or
Two Modules
If the controller has no brake module: Discrete
Brake Module: Enter pick voltage
No Brake Module: No effect
Table 2.7 F7 Menu Settings Magnetek
# Item Default Recommended
133
134
138
140
185
192
193
194
Brake Pick Delay
Speed Pick Delay
Drive Disable Delay
Profile Advance
Brake type option
Speed Drop Delay
Profile Compensation
Normal brake pick voltage
0 ms
+500 ms
+1250 ms
+100 ms
DISCRETE
Dynamic
Job specific. Initially set to 0.0
Job specific, Initially set to 1.0
1250
Drive tuning specific. Initially set to 1 divided by
Response. View response on A1 Magnetek drive menu.
142 Standard Slew Slope
148 Hoist-motor speed
+0.5 ft/s2 Drive tuning specific. Initially set to 2.0
+1165.0 rpm Per Job
155 Inspection speed (normal) +50 fpm
160 Leveling Distance +1.0 in
As desired
Drive tuning specific. Initially set to 2.0
170 Manual start jerk
171 Manual roll jerk
172 Manual stop jerk
173 Manual acceleration
174 Manual deceleration
184 Drive type option
+1.00 ft/s3
+1.00 ft/s3
+1.00 ft/s3
+0.50 ft/s2
+0.50 ft/s2
KEB F5-GRD50
+1.00 ft/s3
+1.00 ft/s3
+1.00 ft/s3
+0.50 ft/s2
+0.50 ft/s2
MAG HPV600 for 600/600PM
MAG HPV900 for 900/900PM/900II
If the controller has a brake module(s): One Module or
Two Modules
If the controller has no brake module: Discrete
Drive tuning specific. Initially set to 900
Fixed
Brake Module: Enter pick voltage
No Brake Module: No effect
2-45
2
Installation
Using Inspection Stations to Run
In inspection, a car operates at slow speed using up and down buttons. The car will stop when the buttons are released.
Encoder Polarity (TORQMAX)
1. Place the car on Inspection mode.
2. Press and hold the ENABLE button while using the Direction toggle to run the car up or down.
The brake and motor contactors should pick; the car should move.
3. Set drive parameter LF.93 to display motor current.
4. If the car oscillates at zero speed, moves at slow speed, or trips the E.ENCC drive fault, change drive parameter LF.28 (0 to/from 1) to internally swap encoder channels. If the motor draws normal current (LF.93 = 30 - 40% of motor
FLA) but the car moves in the opposite of the direction commanded, set LF.28 to “2” to reverse motor rotation.
Note
TORQMAX E.ENCC Fault: If a malfunction occurs, the drive shuts down and the display is overwritten with an error message. After correction, most errors can be cleared by pressing the
Enter key. E.ENCC errors however can only be cleared through Parameter 0LF.26. If the drive displays E.ENCC, refer to the LF.26 explanation in the drive manual.
Align Encoder (Magnetek)
HPV 600/900/900II
1. Move the elevator on Inspection and verify that the motor is under control and rotating in the proper direction.
For proper operation, motor phasing must match encoder feedback phasing. If the phasing is not correct, the motor will not accelerate up to speed. It will typically oscillate back and forth at zero speed and the current will be at the torque limit.
2. If the motor operates as described above, verify that the encoder is wired as shown in the prints. If it is, swap any two motor phases.
3. If the motor operates properly but is turning in the wrong direction, change the Motor
Rotation parameter in the drive C1 User Switches menu.
HPV 600PM
1. Place the controller on Inspection.
2. Set Inspection Speed (normal), controller F7, 155, to 1/8 of Contract Speed.
3. In the controller F3, Controller Utilities menu, set Inspection Mode Fault Bypass to ON.
(Jumper must be in place on HC-CTL-2 board Fault Reset Jumper JP2.)
4. Refer to and follow the Absolute Encoder Alignment Procedure, Auto Alignment Procedure in the Magnetek HPV 600PM AC Drive technical manual.
5. Restore controller to original settings.
2-46 Manual # 42-02-2P25
Motion 4000
Set Up for Construction Operation
HPV 900PM
1. Place the controller on Inspection.
2. Set controller F7, 141, Profile Scale to 0.0%.
3. In the controller F3, Controller Utilities menu, set Inspection Mode Fault Bypass to ON.
(Jumper must be in place on HC-CTL-2 board Fault Reset Jumper JP2.)
4. Disable the machine brake. (Remove brake wire from brake coil if discrete brake circuit is being used or set the Normal Brake Pick/Hold Voltage (F7, 194 and 195) to 0.0 if a brake module is being used.)
5. Refer to and follow the Absolute Encoder Alignment, Alignment Via Car Controller procedure in the Magnetek HPV 900PM AC Drive technical manual.
6. Restore controller to original settings.
Brake Basics
1. Ensure that the brake is picking cleanly. With the car set up so that it will not move:
• Manually activate the PM and BR contactors to lift the brake.
• Measure DC voltage between terminals B1 and B2. It should be very close to the pick voltage shown in your job prints.
• Refer to job prints and adjust pick voltage if necessary.
2. Ensure that, when set, the brake is capable of holding 125% of rated car capacity. Refer to
Adjust Brake to 125% of Full Load on page 2-82 .
3. Check that brake and motor coordination are such that the brake is dropping just when motor rotation stops.
4. Check that the brake pick delay allows the motor to build sufficient flux to prevent roll back when the car is starting.
2
2-47
Installation
Verify Motor Speed, TORQMAX
If the car is not running at inspection speed as verified using a hand-held tachometer:
• Check the inspection speed setting (F7:155, page 4-156 )
• Check F7:141 Profile Scaling at 100%.
• Check motor speed is properly set, LF.11.
• Verify traction sheave diameter and setting, LF.21.
• Verify Closed Loop control setting LF.30 is set to 2 (closed loop)
• Check F7:148 Hoist motor speed is properly set (increase = slower speed; decrease = faster speed). This value reflects the motor RPM at contract speed.
• If necessary, you can set LF.22 to a value between 125% and 150% of LF.25. This should allow F7:149 Contract Speed, F7:155 Inspection Speed Normal, and F7:148 Motor RPM to determine inspection speed without interference.
Note
There are very important things to consider about the interaction between motion parameters set on the drive and motion parameters on the controller.
TORQMAX: Drive parameters LF.20 Contract Speed, LF.21 Sheave diameter, and LF.11 Motor
RPM determine the drive’s Estimated Gear Ratio, LF.25. The drive will not drive the motor any faster than determined by the Gear Ratio set at LF.22.
Verify Motor Speed, Magnetek
If the car is not running at inspection speed as verified using a hand-held tachometer:
1. While running on Inspection, verify that the Speed Command on the drive D1 Elevator
Data menu is equal to the controller requested F7, 155, Inspection Speed (Normal).
2. On the controller F3 menu, select the car speed display.
3. While running on Inspection, verify the actual speed via the controller LCD or a handheld tachometer (controller LCD preferred). Adjust Contract Mtr Spd on the drive A1
Drive Menu if the speed is not correct (higher RPM for increased speed).
4. When the elevator is running at the correct speed, verify that the controller F5, MPI-C
Diagnostic menu, address 17, Raw Speed Feedback, displays the correct value. If not, adjust controller V7, 148, Hoist Motor Speed (lower RPM = increased speed).
2-48 Manual # 42-02-2P25
Motion 4000
Set Up for Construction Operation
Gear Reduction Ratio, TORQMAX
If the gear reduction ratio is not available from the gear data plate or from the manufacturer, you can estimate it and get in the ballpark:
• Mark the motor shaft.
• Mark the traction sheave.
• Reduce the inspection speed setting.
• Run the car and count the number of motor shaft rotations it takes to equal one sheave rotation.
• Enter that number of motor shaft rotations into the gear reduction ratio parameter.
(Example: 27.1 motor rotations = 1 sheave rotation; enter 27.1.) The drive provides an estimated gear reduction ratio at parameter LF.25.
Note
Using a gearless machine, the gear reduction ratio is 1.
You can fine-tune the accuracy of the Gear Reduction Ratio setting once you have the encoded tape positioning system in place. Difference in the speed perceived by the drive and the speed perceived by the positioning system can problems:
• Use a hand-held tach to check accuracy of inspection speed
• Access the controller F3 menu and check that it shows the correct inspection speed
• TORQMAX Only: If F3 does not show the correct inspection speed, verify that the Gear
Reduction Ratio, LF.22 is greater than the Estimated Gear Reduction, LF.25. To eliminate the effect of LF.22, set its value between 125 and 150% of LF.25. Next, adjust F7:148 to set the correct speed on inspection (increase = faster speed; decrease = slower speed). F7:148 is rated motor RPM.
2
2-49
Installation
Temporary Run Box Hookup
The following illustration shows a temporary run box hookup. Disconnect controller power before attempting to wire the run box. The temporary run box must have an enable button, an up button, a down button, and a stop (Insp/Norm) switch.
Caution
For safety, keep the controller Machine Room Inspection switch in the INSP position while the temporary run box is in use.
Figure 2.13 Temporary Run Box
Car
Temporary Run Box
Machine Room
HC-CTL-2 Board
Traveler
INSP
NORM
ENABLE
CTEN
2
PMT Strip
UP DOWN
ICTD
ICTU
INCT
2-50 Manual # 42-02-2P25
Motion 4000
Prepare for Inspection Operation
Prepare for Inspection Operation
Once the car is running safely on construction operation, you should next install all safety string components in accordance with the job drawings package. The actual equipment in the string may vary from job to job but for the Motion 4000 generally includes:
• Hoistway safety string -
• Governor switch
• Final Limit switches
• Buffer switches
• Compensation sheave switch
• Pit stop switch
• Cartop safety string -
• Safety clamp switch
• Emergency exit contact
• Cartop Inspection station and Stop switch
• In-Car Stop switch (in COP)
• Hoistway Switches
At this point, you should also:
• Install seismic equipment
2
2-51
Installation
Hoistway Safety String
1. Install hoistway safety string devices as shown in your job prints.
2. Install final limit switches at each terminal.
3. Test each device individually after the string is complete to see that it does in fact open the safety string as it should.
Note
In Motion 4000 installations, Final Limit switches are part of the hoistway safety string and should not open unless the car overruns the terminal landing.
Cartop Safety String
1. Install the cartop inspection station and stop switch as shown in your job prints.
2. Install cartop safety string devices as shown in the job prints.
3. If the in-car stop switch is in place, wire it into the string as shown.
4. Verify that the cartop inspection controls work correctly.
Hoistway Switches
Virtual/Physical/Unused
With the exception of the final limit switches, which are always physical, other slowdown switches used in Motion 4000 installations may be physical, virtual, or unused:
• Physical: Normal switches installed in hoistway.
• Virtual: Switches placed in “software” by the positioning system. Please refer to “Terminal
Switch Options, 69 - 74” on page 4-147 .
• Unused: Depending upon car contract speed, some hoistway switch positions may be unused.
Table 2.8 Hoistway Switch Requirements
UETS/DETS and UNTSX/DNTSX switches requirement as per Rated speed (FPM)
Car
Speed
(FPM)
Up to 399 √
400-499 √
>700
UETS/DETS UNTS1/DNTS1 UNTS2/DNTS2 UNTS3/DNTS3 UNTS4/DNTS4 UNTS5/DNTS5
Virtual switch
Learn speed
Virtual switch
Learn speed
Virtual switch
Learn speed
Virtual switch
Learn speed
Virtual switch
Learn speed
Virtual switch
Learn speed
500-599 √
600-699 √
√
80% √
80% √
80% √
80% √
80% √
90%
70%
60%
50%
40%
√
√
√
√
90%
70% √
60% √
50% √
90%
70%
60%
√
√
90%
70% √ 90%
LS-EDGE
Hoistway switch requirements for LS-EDGE are like those for ELGO except that ETS, when required, are 5” magnet strips.
2-52 Manual # 42-02-2P25
Motion 4000
Prepare for Inspection Operation
Seismic Equipment
A “ring and string” circuit detects excessive counterweight motion caused by a seismic disturbance. When motion is detected, the car will make a full stop. After stopping, the car will move to and level at the next available floor in the direction away from the counterweight. After leveling, the car will open its doors and allow passengers to exit.
Modes of operation other than Automatic, for example Fire Phase II or Attendant mode, allow different operating options when potential counterweight derailment has been detected.
Your job may also use a lateral and/or vertical acceleration sensor to detect seismic activity. At this point, you should install counterweight movement detection and seismic sensors in accordance with your job prints and seismic monitor manufacturer instructions.
Figure 2.14 Seismic Equipment
Counterweight Displacement
Kit:
Two steel cables run parallel to counterweight guide rails, passing through a pair of eyebolts on the counterweight. If the counterweight moves laterally, the cable touches the ring, completing the circuit and providing an alert to the controller.
Seismic Detector:
Detects and records vertical and horizontal seismic movement. Peak acceleration along each axis is detected and stored for up to 15 seismic events. The easy to read LCD displays real time acceleration and angle of deflection.
2
2-53
Installation
Running on Inspection Mode
At this point, you should be ready to turn the car over to standard Machine Room and/or Cartop Inspection operation. All equipment, with the exception of the landing/positioning system, the door operator, load weigher, hall call stations, and full car operating panel should now be installed and tested for proper function.
Danger
Controller inspection warnings:
• As always when actively installing an elevator, have someone stand by the main line disconnect when power is applied or when initial attempts are made to move the car.
• Check all safety circuits are functional.
• Check all hoistway door interlocks are functional.
• Check car gate circuitry is functional.
Prior to Applying Power:
• Verify all circuits are wired to the controller properly.
• Check the following items:
• Inspection switch to INSP
• Verify, with an ohmmeter, that the governor overspeed switch and any other devices that are wired in at this time will open the safety circuit.
• Physically verify that all hoistway doors are closed and locked.
• Verify that any temporary jumpers placed for equipment that has now been installed are removed.
Controller Power Up
After powering up the controller, check the following:
1. If the LCD is displaying an error message, troubleshoot to resolve the issue. (
Please refer to Section 5
.)
2. Check that the LCD displays INSPECTION.
3. Using the Enable button and the Up/Down toggle, run the car.
4. Release the Enable button and note that machine and brake power are released and that the brake drops and holds the car.
5. Run the car and use the hand-held tach to verify inspection speed.
2-54 Manual # 42-02-2P25
Motion 4000
Finishing Installation
Bypassing Faults on Inspection
Before installation and adjustment are complete, faults that will be adjusted out later may disrupt operation. To bypass faults on Inspection mode:
1. On the MPU board, place switch F3 in the UP position (all others down).
2. On the HC-CTL-2 board, use a jumper to short the A-position pins of JP2 Fault Bypass.
3. Press N until the display shows Controller System Menu.
4. Press S to enter the menu.
5. Press N until the LCD displays Inspection Mode Fault Bypass OFF.
6. Press S to change bypass state to ON.
7. Set F3 back to the DOWN position.
This setting bypasses controller response to faults during Inspection operation. When bypass is no longer necessary, be certain to change this setting to OFF.
Finishing Installation
With the car running safely on Inspection operation, you are ready to finish installation. This section describes installing:
• Landing/positioning system
• Door operator
• Car operating panel
• Fire service peripherals
• Hall Calls
You must also:
• Balance the car and counterweight
• Adjust brake to hold 125% of full load
2
2-55
Installation
Landing/Positioning System
Depending upon job requirements, Motion 4000 may use an encoded magnetic tape landing system (ELGO) or a perforated steel tape system (LS-EDGE). This section describes both systems. LS-EDGE NEMA 4X/12 systems use stainless steel hoistway components and a sealed sensor head but are otherwise installed just as are standard systems.
LS-EDGE
The LS-EDGE positioning system uses hall-effect sensors and perforated steel tape to report position as the car moves through the hoistway. 5.5-inch magnets are used at each door zone; one row for front openings, a second for rear openings.
The system uses capacitor-stored power and non-volatile memory to retain position information in the event of a power failure, continuing to capture information for 10 seconds after power loss and storing the final reading for use after power restoration.
The LS-EDGE kit contains the sensor head assembly, an “L” bracket to mount the sensor assembly to a uni-strut that is in turn attached to the elevator cab (uni-strut to elevator cab not provided), steel tape, top and bottom steel tape hanger assemblies, the required number of door zone magnets, and the CAT-5 electrical cables required to connect the sensor to the car top interface box.
Depending on applicable code, you may have to route electrical connections through conduit. If so, we recommend minimum 3/4-inch flex so that the modular connectors can slide through without binding. Perforations for cable tie wrap connection are provided on the RJ-45 plug-end of the sensor head.
Figure 2.15 LS-EDGE Components
Top hanger assembly
(diagonal brace not shown)
LS-TAPEMNTOP-EDGE
Together, these are assembly
LS-TAPEMNT-EDGE
Bottom hanger assembly
LS-TAPE MNTBOT-EDGE
Sensor assembly
LS-EDGE
Steel tape, magnets & connecting cables not shown
2-56 Manual # 42-02-2P25
Motion 4000
Landing/Positioning System
Figure 2.16 Tape Installation
Before installing perforated tape, ensure adequate clearance from beams, walls, counterweight, cab, and terminal limit devices. Make sure the sensor is not placed so close to the governor lift arm that, when the car safeties are activated, the sensor is damaged or the car safeties cannot apply.
• Hang the tape high enough in the hoistway so that, when the counterweight is on a fully compressed buffer, the sensor assembly will not be damaged by overhead obstructions.
Uni-struts are provided to attach the tape to the rails.
• Attach the tape in the pit low enough so that, when the car is on fully compressed buffer, the sensor assembly does not contact the bottom hanger assembly.
• Adjust tape spring tension so the tape does not make noise as the car travels up.
• During installation, the edges of the tape sometimes become gouged. After the tape is installed, use a fine file on the edges of the tape to remove any burrs or gouges. This will lead to much quieter operation of the encoder system as the car travels at contract speed.
• After smoothing the edges, wipe off all excess oil and dirt from the face of the tape before installing magnets. Do not use rags that will leave lint on the tape.
Top Hanger Assembly
1. Attach the uni-strut for the top tape hanger across the back of the selected guide rail using the forged rail clips and hardware provided.
2. Attach the diagonal brace as shown below. (Used only for tape length exceeding 150 feet.
19 - 25 ft lbs
2
40 - 50 ft lbs
90 degrees see Detail A
Hang tape on tab
30 - 40 ft lbs
LS-TAPESTRUT-EDGE - included only when tape length requires extra support
40 - 50 ft lbs
Hang tape on tab
Detail A
Top tape clamp hardware,
10 - 12 ft lbs
2-57
Installation
3. Adjust extended strut length as required (tape suspended as close to the guide rail as adequate clearances will allow to reduce loading on end of unistrut). Secure rail mounting hardware (40 - 50 ft lbs.). (The tape hanger slides in the strut for fine adjustment later.)
4. Hook the tape on the protruding tab. Secure the top tape clamp in place (10 - 12 ft lbs.).
5. Record the distance from the rail edge to the tape edge. ________ in/mm.Bottom
Hanger.
Bottom Hanger Assembly
The bottom hanger provides tension to minimize vibration while allowing expansion/contraction across seasonal temperature ranges. Ensure that the tape to rail edge measurement matches that recorded for the top hanger so that the car tracks the tape accurately. Do not use a plumb in case the rail stack is not exactly aligned. The scale values are provided as a guideline only. They are not calibrated. Adjust to suit the installation.
Figure 2.17 Bottom Hanger Attachment
Connection torque specifications,
Wire AWG
Tape tension gauge
Switch cam
Detail B
Tension gauge indicator
40 - 50 ft lbs
10 - 12 ft lbs
Broken Tape Switch
Wire per job prints.
19 - 25 ft lbs
Tension gauge indicator
Tape
Gripping
Tab
Bottom tape clamp hardware
10 - 12 ft lbs
Oval indicates location of
“pre-load” pin holes allowing you to put tension on the spring while hanging the tape.
Detail B
2-58 Manual # 42-02-2P25
Motion 4000
Landing/Positioning System
Broken Tape Switch
The normally closed contacts on the Broken Tape Switch are used to detect a broken tape condition. The switch is mounted backwards for protection during shipment. Remove it and mount it as shown in
Figure 2.17 .
Position the switch so that the cam on the tensioner activates (opens) the switch when the tensioner is at the bottom of its travel (no tension). Note that switch position should be adjusted so that the switch is activated by the cam but not so close that the switch is held against its mechanical stops. The switch activates at approximately 50% of travel.
Hanging the Tape
Work from the cartop to hang the tape from the top hanger and allow it to unroll slowly as you move the car down the hoistway. It is best to allow the tape to hang and straighten for at least
24-hours before attaching it to the bottom hanger.
Tape Tension
The tape is tensioned according to compression of the bottom tape mount spring. The tension gauge provides visual indication of low, medium, and high tension positions. Short runs, up to five floors will generally be acceptable at the low tension position. Runs to 15 floors will generally be acceptable at the medium tension position. Longer runs may require the high tension position but you should start out with the medium setting first. The scale values are provided as a guideline only. They are not calibrated. Adjust to suit the installation.
Tape tension is intended to reduce noise caused by tape vibration at contract speed. Generally, you want to use the lowest tension setting that maintains a quiet tape at contract speed.
Sensor Installation
Tape guide side pieces easily detach so the sensor can be slipped onto the steel tape. Attach the sensor to the cartop as shown in
Figure 2.19
Figure 2.18 Sensor with Guide Sides Removed
2
2-59
Installation
Figure 2.19 Sensor Mounting
LED Indicators UP
40 - 50 ft lbs
“L” bracket (provided)
Customer provided uni-strut
CAR TOP
Sensor Alignment After the tape has been installed, check the sensor alignment. The sensor should not ride hard on either side of the uni-strut bracket during any part of travel through the hoistway. In high-rise buildings, if rail alignment varies substantially, it may cause the encoder guides to wear prematurely. If such misalignment is noted, the installation should be inspected more regularly.
2-60 Manual # 42-02-2P25
Motion 4000
Landing/Positioning System
Door Zone Magnets
5.5-inch strip magnets are used at each floor/opening position. Front and rear magnet alignment is shown on the sensor top label. Looking at the perforated tape from the elevator car, the magnets for the front door zone are mounted to the left of the perforated holes; magnets for the rear door zone are mounted to the right of the holes.
Figure 2.20 Door Zone Magnet Alignment
2
Scribe
Line
2 5/8 inches
Top of
Magnet
To mount the door zone magnets:
Caution
The magnets must be installed so that they face the front cover of the sensor assembly as indicated by the diagram on the LED indicator label.
1. Move the elevator level to the highest floor on inspection.
2. Make a mark on the tape even with the top of the sensor assembly. Lower the car one foot.
3. Place the top of the door zone magnet 2 5/8 inches below the scribe mark and to the left
(front door) or right (rear door) of the perforated holes. For now, simply place the magnets. You can secure them permanently after final adjustments.
4. Continue mounting door zone magnets as described above for successive floors.
2-61
Installation
Terminal and ETS Magnets
Top Terminal and ETS Magnets
Magnets marked with a stripe to differentiate them from the door zone magnets are used at the top and bottom terminals for Motion 4000 installations. 5-inch striped magnets are also used for physical ETS when required. If reduced stroke buffers are used, cam operated ETSL
switches may also be required. Please refer to “Slowdown Learn, ETS Placement” on page 3-6.
Figure 2.21 Motion 4000: Bottom Terminal and ETS Magnet Placement
TOP TERMINAL
FRONT
DOORS
REAR
DOORS
2 5/8” TO
TOP OF
DZ MAGNET
SCRIBE
5” STRIPED
MAGNET
FRONT &
REAR
DOORS
SCRIBE
5” STRIPED
MAGNET
5” STRIPED
MAGNET
5 1/2” DZ
MAGNET
5” STRIPED
MAGNET
24” STRIPED
MAGNET
24” STRIPED
MAGNET
24” STRIPED
MAGNET
IF ETS
5” STRIPED 5” STRIPED 5” STRIPED
MAGNETS
ETS MAGNET ETS MAGNET ETS MAGNET
USED
1. Place a 24-inch, striped magnet to the right of the tape perforations, just below the top door zone magnet as shown above. The top of the 24-inch magnet must be even with the bottom of the door zone magnet.
2. For jobs with front doors only stack two 5-inch striped magnets above the 24-inch magnet. Leave NO GAPS between the striped magnets.
3. For jobs with rear or front and rear doors, stack one 5-inch striped magnet directly above the Rear Door Zone magnet. Leave no gaps between the ends of the magnets.
2-62 Manual # 42-02-2P25
Motion 4000
Landing/Positioning System
Bottom Terminal and ETS Magnets
Magnets marked with a stripe to differentiate them from door zone magnets are used at the top and bottom terminals for Motion 4000 installations. 5-inch striped magnets are also used for physical ETS when required. If reduced stroke buffers are used, cam operated ETSL switches may also be required. Please refer to “If an ETSL switch is required:” on page 3-14.
Figure 2.22 Motion 4000: Bottom Terminal and ETS Magnet Placement
IF ETS
MAGNETS
USED
FRONT
DOORS
5” STRIPED
ETS MAGNET
REAR
DOORS
5” STRIPED
ETS MAGNET
FRONT &
REAR
DOORS
5” STRIPED
ETS MAGNET
2
24” STRIPED
MAGNET
24” STRIPED
MAGNET
24” STRIPED
MAGNET
SCRIBE SCRIBE
2 5/8” TO
TOP OF
DZ MAGNET
5 1/2” DZ
MAGNET
5” STRIPED
MAGNET
5” STRIPED
MAGNET
5” STRIPED
MAGNET
5” STRIPED
MAGNET
BOTTOM TERMINAL
1. Place a 24-inch, striped magnet to the left of the tape perforations, just above the bottom door zone magnet as shown above. The bottom of the 24-inch magnet must be even with the top of the door zone magnet.
2. For jobs with rear doors only, stack two 5-inch striped magnets below the 24-inch magnet. Leave NO GAPS between the striped magnets.
3. For jobs with front or front and rear doors, stack one 5-inch striped magnet directly below the Front Door Zone magnet. Leave no gaps between the ends of the magnets.
2-63
Installation
Electrical Connection
Make electrical connections as shown in the job prints. iControl uses separate Front and Rear door zone connections. Motion 4000 uses the M-CAN connection. For TSSA compliant installations, Motion 4000 uses the DISC (discrete) connection in addition to the M-CAN connection.
In addition to the sensor-to-cartop box connections, there are Landing System Interface board to the controller as shown in the prints for the job.
Caution
Secure cables with a nylon tie wrap through the holes provided. VERY IMPORTANT as it provides strain relief and prevents connector fatigue over time.
Figure 2.23 Sensor Connections
M4000 Standard CAN, single orange cable M4000 TSSA CAN & Discrete, 1 orange and 1 blue cable iControl, single, gray cable per opening
(FRONT/REAR)
2-64 Manual # 42-02-2P25
Motion 4000
Landing/Positioning System
Parameter Settings
Please refer to “Hoistway Learn, LS-EDGE” on page 3-5 for hoistway learn, slowdown learn,
and ETS placement instructions.
Permanently Attach Magnet
Once the hoistway has been successfully learned and magnet placement is satisfactory, you may
“lock” the magnets in place by placing a drop of silicone adhesive immediately above the top end and immediately below the bottom end of each magnet.
Indicators
Lighted indicator LEDs on top of the sensor unit provide information about active signals.
Figure 2.24 Indicator LEDs
MAIN: Sensor processor A active.
DLMR: Down Level Marker Rear.
DZR: Door Zone Rear.
ULMR: Up Level Marker Rear.
SDU: Slow Down Up.
DP1:Quadrature pulse.
DP2: Quadrature pulse.
CAN: CAN communication activity.
SDD: Down Slow Down.
DLM: Down Level Marker (Front).
DZ: Door Zone (Front).
ULM: Up Level Marker (Front).
AUX: Sensor processor B active.
2
• DP1, DP2: Quadrature pulses (iControl). DP1 leads when the car is traveling up. DP2 leads when the car is traveling down. Alternately active whenever the car is in motion.
• CAN: Motion 4000 CAN communication with landing system is active.
2-65
Installation
ELGO
The encoded tape used for the landing system is suspended between two mounting brackets that attach to the car rail using forged clips and hardware. If the job uses 8#, 23#, or 30# rail, you will need an additional kit for the proper size hardware: LS-ELGO-RAIL-08#, LS-ELGO-
RAIL-23#, or LS-ELGO-RAIL-30#. The high speed Elgo positioning system sensor and
tape described here are not compatible with earlier versions. Contact MCE if you have questions.
This information is specific to Elgo-240 standard and NEMA 4X landing systems. To be certain you are following the correct instructions:
• Described here:
• Sensor Head about 19 inches (483mm) long
• Head label starts with LIMAX2 followed by additional characters
• Tape labeled AB20-80-10-1-R-B-15 and has arrows and UP label
• NEMA 4X systems are specifically labeled “NEMA TYPE 4X”
• NEMA 4X systems use stainless steel hangers and hardware for corrosion resistance and a NEMA 4X rated tape switch.
Caution
Improper installation could result in failure of the tape, mounting hardware, and reader. Please read instructions before installing!
The Motion high speed positioning system uses a permanently encoded tape running the length of the hoistway. The tape is about 1/2-inch wide and consists of two bands; a metal band for strength and a dark, magnetic material band that carries the actual encoding.
• The encoded side of the tape (dark side) must face the elevator car.
Magnetic band
Steel band
Caution
The arrows on the magnetic side of the tape must point in the up direction and
face the car.
2-66 Manual # 42-02-2P25
Motion 4000
Landing/Positioning System
Safety String Connection Information
The switch on the bottom tape mount must be connected in the hoistway safety string as shown in your job drawings. If the switch is not shown in your drawings, connect it as shown below.
Figure 2.25 Tape Switch Connection
15
HC-CTL
SAFH
STOP SW.
(PIT)
COMP. ROPE
SHEAVE SW.
BUFFER SW'S
CWT CAR
15B
ELGO TAPE SW.
15E 15D 15C
N.O.
FINAL TERMINAL
STOPPING DEVICES
DOWN15A UP
2
TO CAR STRING
Recommendations
If you install the bottom hanger and safety switch before hanging the tape, go ahead and test the switch function. When opened, the switch should shut off power to the machine and the brake causing the elevator to immediately stop.
After testing switch functionality, use a piece of wire or string to temporarily hold the switch in the closed position so that you can run the car on car top inspection to hang the tape.
Caution
Do not temporarily jumper the switch. It is far too easy to forget and leave the jumper in place.
2-67
Installation
Installation
This kit is configured to mount the sensor head on the left side of the rail (as you face the rail blade). If necessary, you can change this to right side mounting.
Please refer to “Left to Right
Rail Side Reversal” on page 2-77 . Tape hangers are steel channels that clamp across the back of
the car rail using forged rail clips. The tape hangs directly from the top hanger and connects through a tensioning spring to a switch pivot on the bottom hanger. With the tape properly hung, spring tension keeps the pivot held against the switch, keeping it closed. If tension is lost due to a tape failure, the switch will open the safety string and bring the car to a stop.
1. Attach top and bottom hangers to the rail lightly using clips and hardware provided.
2. Use a tape measure to adjust the hangers to provide equal offset from rail edge to encoding tape. Tighten the retaining hardware.
Figure 2.26 Tape Hanging Hardware
tape end clamp
Fine tape alignment adjust
Initial tape offset adjust inner plate is tapped
Sensor
Sensor mounting kit
Springs
Tape switch Screw heads this side
Springs assist in keeping the tape aligned. If you see that the springs are twisted, check that the tape and the sensor head are properly aligned.
2-68 Manual # 42-02-2P25
Fine tape alignment adjust Initial tape offset adjust
Motion 4000
Landing/Positioning System
Tape End Pieces Tape end clamps are loosely assembled using 1-inch, 8x32 screws so that you can simply loosen them up, weave the tape through, and tighten the screws down. It may be easiest to attach just the top end piece now and then attach the bottom end piece after hanging the tape.
1. Loosen the screws on a tape end clamp. Slide the tape through between the center piece and the top clamp, magnetic band up, down through the square hole and back through between the center piece and the bottom clamp. See the figure below.
2
2. Gently tighten the screws in the order shown below. Square up the end clamp and the tape.
4
1
90-degrees
2
3
Side View
3. In the same 1, 2, 3, 4 order, make several passes, tightening each screw just a little each time. Finally, torque each screw to 14 in-lb. or 224 in-oz. (depending on the units on your torque driver).
Hanging Tape With the hangers in position on the rails such that the tape will hang approximately vertically, connect the tape to the top hanger using the hex bolt and locking nut provided. Make certain the arrow on the tape is pointing up and that the magnetic surface is facing the car. Begin unreeling tape toward the bottom of the hoistway:
Hex bolt & lock nut
1. Move slowly down the hoistway and unroll the tape from the carrier.
2-69
Installation
2. Attach the bottom end of the tape using the hanger parts kits and the tensioning springs. Fine tune proper vertical alignment (both front-to-back and side-to-side) — the hanger bracket ends are adjustable to provide fine side-to-side alignment (step 3).
At proper tension (about 16 lbf.), the springs will be stretched about 3.0” (75 mm) beyond their relaxed length.
3. The assemblies to which the tape attaches, both top and bottom, allow fine alignment adjustment without having to work with the heavy, rail clamp hardware. After adjustment, torque the 3/8 bolts/nuts to 10 ft lbs.
Note
Check that the elevator car does not rock excessively. If necessary, adjust roller or other guides until excessive rocking is eliminated. The Elgo reader will track with the car. Excessive lateral car movement will translate into reader/tape alignment movement.
2-70 Manual # 42-02-2P25
Motion 4000
Landing/Positioning System
Sensor Mounting Move the car to the middle of the hoistway. Attach the sensor to the car. The head must be positioned such that the CAN cable exits the top of the sensor head.
Exactly how you mount the sensor head will depend on the physical structure of the car and sling and the position of the tape. Because there is so much variation between jobs, sensor head mounting brackets are usually fabricated on site. Three examples follow.
2
Note
Shims. For the hangers described in this instruction, four shims are provided. Once you have completed sensor installation, if you find you are very slightly out of plumb, you may slightly loosen a bolt or nut and insert a shim to correct. If a component is out more than may be corrected by two or three shims, check major components, level, and plumb and correct the basic installation.
Figure 2.27 Sample Mount A (available option from MCE)
Kit includes “T” strap hanger, two
1/4” square-head bolts, and two lock nuts.
ELGO-RDRMNT-HDWE
2-71
Installation
Figure 2.28 Sample Mount B
Slotted mounting holes on bracket allow adjustment.
The heads of the sensor mounting bolts are captive in a slot on the sensor body.
Bolts are 1/4” diameter with square heads. Use a flat washer against the mounting bracket, and a lock washer between the nut and the flat washer. M6, hex head bolts may also be used.
Use spacers to adjust the vertical alignment of the sensor head.
Mounting channel
Alternatively, you can use 8 x 32 channel nuts and screws or 1/4” square head bolts and nuts.
However, if you are inserting the screws toward the body of the sensor, you must be very careful that you position spacers to prevent the screw from damaging the sensor.
Figure 2.29 Sample Mount C
Channel nuts
8 x 32 bolt/screw
8 x 32 Channel nut
Unistrut part #: P7006-0832
Sensor Body
(to) Avoid jamming the bolt end into the sensor body
Bracket body
Add washers or shims here
2-72 Manual # 42-02-2P25
Motion 4000
Landing/Positioning System
Tape Must Be Plumb and Under Tension Before Completing the Following Steps
1. Adjust the sensor to tape centerline alignment using the plumb tape as a reference as shown below.
Polymer guide
Magnet band
Sensor
2
Elevator Car
2. Remove the front polymer guide from the sensor by flexing it slightly out at the center and pulling it from the retaining clips at each end. Leave the sheet-plastic membrane in position on the sensor.
polymer guide
2-73
Installation
3. Adjust the distance between sensor and tape. Up to a travel height of 110 meters, we recommend an offset of 1 inch (25 mm) with the polymer guide removed. (See the illustration below.) Verify that the offset measures 1.0 inches at both the top and the bottom of the sensor. This will ensure steady, even contact between the steel side of the tape and the polymer guide of the sensor.
Tape
1.0 inches (25 mm)
Sheet-plastic membrane
ELEVATOR CAR
4. Re-attach the polymer guide with the tape resting in the guide slot.
Polymer guide
Tape (magnetic band towards sensor)
Sheet-plastic membrane
Sensor body
CAR
2-74 Manual # 42-02-2P25
Motion 4000
Caution
It is critical to ensure that the sensor is installed so that any mechanical contact between tape and sensor head is between the steel band and the polymer sensor guide. Adjust for a horizontal offset of 1 inch (25 mm) between the sensor metal face and the magnetic band so that contact between the steel side and the polymer guide is firmly forced.
When properly installed, looking at the top of the sensor, there will be a slight gap between the magnetic band and the body of the sensor. Refer to the illustration below.
Correct
Tape
Sheet-plastic membrane gap between tape magnetic surface and body of sensor/ plastic membrane
Landing/Positioning System
With the sensor guide re-installed, the tape should arc gently away from the car at the top and bottom, forcing the steel side of the tape firmly against the polymer guide.
2
Be certain that the sensor head is plumb with the tape. Check top and bottom to be certain it is not out at the bottom while appearing correctly offset at the top.
A rocking car with roller guide or isolation mount problems can exhibit sensor head alignment issues at different points in the hoistway.
2-75
Installation
Verify that the tape is longitudinally aligned with the sensor face.
5. Check proper alignment of tape vs. sensor. Correct any angular offset.
Figure 2.30 Positioning Tape Longitudinal Alignment
6. On cartop inspection, move the car to several points in the hoistway. Verify that tape-tosensor alignment remains satisfactory in each position.
7. After completing installation, clean the tape. Beginning at the top of the hoistway, move down the full travel distance pulling the tape through a soft, dry cloth. Repeat this process before putting the elevator into service after completing installation.
Hoistway Learn, Elgo
Please refer to “ELGO Encoded Magnetic Tape” on page 3-3
.
Periodic Maintenance Required
Inspect and clean the sensor and encoded tape as part of your car top routine or at minimum intervals of 6 months for contract speeds below 400 FPM or 4 months for contract speeds above
400 FPM.
1. Check that the sensor is properly aligned and that the tape is running through the reader slot with the polymer guide pressing firmly against the steel backing and with no contact on the magnetic material, as described in this instruction.
2. Check for abnormal wear on both the tape and the guide.
3. Open the sensor head and check for debris in the guide-way.
4. Check that the bottom spring attachment provides adequate tape tension (spring stretched about 2” (50 mm) beyond its relaxed length, about 16 lbf.).
5. Clean the tape as in step 7 above.
2-76 Manual # 42-02-2P25
Motion 4000
Landing/Positioning System
Left to Right Rail Side Reversal
As shipped, the kit is configured to mount the sensor head on the left side of the rail (as you are facing the rail blade). The kit can be reconfigured for right side mounting as described here. The illustration shows the components as if you were looking “through” the bottom of the bracket.
Figure 2.31 Side Reversal, Bottom Mount
3/8 x 2 bolt
LEFT
3/8 steel flat washer
Composite bushing
Pivot bushing
Pivot plate
Composite bushing
Steel shoulder bushing
2
Channel
1-1/4 inches
3/8 steel flat washer
3/8 x 3/4 bolt
3/8 lock nut
Switch plate
3/8 lock nut
3/8 x 2 bolt
3/8 steel flat washer
Composite bushing
Composite bushing
Steel shoulder bushing
Channel
Switch plate
3/8 lock nut
RIGHT
Pivot bushing
Pivot plate
1-1/4 inches
3/8 steel flat washer
3/8 x 3/4 bolt
3/8 lock nut
2-77
Installation
1. Place the mounting arm assembly on a working surface so that the pivot/switch assembly is on your right but upside down. (The pivot/ switch assembly must always be located on the end of the angle bracket with the openended slot so that it has enough adjustment.
2. On the back of the mounting arm, remove the two lock nuts that secure the pivot/ switch assembly in place.
3. Remove the components. Flip the switch plate and switch so that they are now on the top of the mounting arm.
4. Refer to the preceding illustration for reassembly order. Check that the pivot extends about 1—1/4” beyond the end of the mounting arm.
Assembly must
ALWAYS be on the bracket end with the OPEN slot.
5. With the unit reassembled, torque the 3/8” bolts/nuts to 10 ft-lbs.
6. Remove the #8 Phillips screws, star washers, and nuts that hold the switch in position.
7. Move the switch to the outer mounting position. The switch must be properly aligned and the mounting screws torqued to 15 to 17 in-lbs.
The two alignment tabs must rest on the top lip of the switch bracket. In order to do this, the two mounting screws through the front of the switch must be at the very bottom of the oblong screw holes.
8. Once the switch is in position, rotate the pivot until it closes the switch. With your free hand, press the switch and note that it still has about 1 mm (1/25 in) of travel. This ensures that the pin on the pivot is contacting the inside of the mounting arm and protecting the switch from being damaged by excessive force.
9. Verify that the pivot moves smoothly and will drop when released.
10. When making electrical connections to the switch, note the torque settings for the connection screws and the switch cover screw.
• Cover screw: 15 in-lbs
• Normally Open connection screws: 15 in-lbs
2-78 Manual # 42-02-2P25
Motion 4000
Landing/Positioning System
To change the top mounting arm from left to right side:
1. Set the hanger arm assembly on a working surface so that the hanger plate is on your right.
2. Remove the two 1/2” bolts that secure the top hanger plate.
3. Flip the plate top-to-bottom so that the tape attachment hole is on the bottom.
4. Reassemble with the hanger plate extending beyond the end of the bracket by about
1 and 1/4 inches.
5. Torque the 1/2” bolts to 20 ft-lbs.
Figure 2.32 Changing the Top Mounting Arm from Left to Right Side
LEFT
1/2” x 7/8” bolts
Hanger plate
2
1-1/4 inches
Channel
1/2” twirl nuts
1/2” x 7/8” bolts
Channel
1/2” twirl nuts
RIGHT
Hanger plate
1-1/4 inches
2-79
Installation
Door Operator and Door Peripherals
Check the job prints to see that the door operator you are installing is the operator shown in your job prints.
• Install the operator according to manufacturer instructions.
• Make door operator electrical connections as shown in the MCE job prints.
• Verify that all door related switches and locks are properly installed, adjusted, and wired.
Door Safety Equipment
• Install photo eyes and/or safety edges in accordance with manufacturer instructions.
• Make connections to MCE control as shown in the job prints.
Door Switches
1. Install top, middle, and bottom door locks in accordance with drawings package.
2. Install gate switch and all car door position and limit switches.
Car Operating Panels, Position Indicators, and Peripherals
• Install operating panels according to manufacturer instructions.
• If the job uses the Motion 4000 serial control panel option, install Control Panel Interface board(s) from MCE. Please refer to “MC-CPI Car Panel Interface Board” on page 5-64 .
• Make electrical connections as shown in the MCE job prints for all panel buttons and indicators, position indicators, and controller-connected peripherals (fan/light timer, etc.).
Note
Note that the MCE circuit boards, serial or Universal I/O, communicate with the controller through and are powered through their CAN Bus connections.
Fire Service Peripherals
1. Refer to the MCE job prints.
2. Make electrical connections to fire service switches, sensors, indicators, and buzzers as shown.
Note
After the car is adjusted and running on Automatic operation, fire recall, fire operation, and proper fire or smoke sensors and indicators will be exercised for correct operation.
2-80 Manual # 42-02-2P25
Motion 4000
Door Operator and Door Peripherals
Duplex Connection Between Controllers
If you are installing controllers in a duplex configuration, you must connect a communication cable between the two as shown in your job prints. Jumper JP3 (terminates the CAN bus) must be in place on each HC-MPU board. The controls must also be set up in software to operate as a duplex installation (F1, Program Mode).
Figure 2.33 Typical Duplex Communication Connection
Controller A Controller B
Conduit
2
LCD
Keyboard
RS232 (x3)
Main Processor (HC-MPU)
LCD
Keyboard
RS232 (x3)
Main Processor (HC-MPU)
Hall Calls, Position Indicators, and Peripherals
Motion 4000 hall calls may use discrete call connections or optional CAN Bus connections.
Please refer to “Hall Call Node Wiring” on page 5-71 if you have serial hall calls.
1. Install hall calls, position indicators, and peripherals (auxiliary risers, etc.) according to building requirements and pertinent local and national codes.
2. Install access switches in hall ways in accordance with drawings package.
3. Connect hall switches, push buttons, and indicator lamps or LEDs as shown in the MCE job prints.
CE Position Indicators
CE Electronics position indicators are supported using a CE driver board in the controller. The driver board connects to the controller internal CAN bus. A transformer provides 24-volt power to the board. The three-wire CE output (1= common, 2= fixture power, 3= data) is typically brought to panel mount terminals (RD1, RD2, RD3) for easy access. Refer to the MCE drawings package and to the CE documentation provided with your fixtures.
2-81
Installation
Adjust Brake to 125% of Full Load
1. Bring the car to the bottom landing.
2. Place weights in the car to 2/3 of contract load.
3. Add an additional 50 or 100 pounds.
4. Move the car up a short distance on Inspection.
5. Run the car down and trip the stop switch.
6. Adjust the brake if it does not hold.
7. Repeat until the brake is holding 125% of full load capacity.
8. Remove test weights from car.
Caution
Keep the car near the bottom floor as it is likely to slide through the brake onto the buffers if brake spring tension is inadequate.
Traction Auxiliary Power Supply
If you are installing the TAPS (Traction Auxiliary Power Supply) from MCE to provide emergency power for passenger rescue in the event of commercial power loss, follow instructions in the TAPS manual delivered with the unit.
If TAPS is used with the TORQMAX F5 drive, drive parameter LF.61, Emergency Operation
Mode, must be set to di1. If not, the motor is not correctly powered during TAPS operation.
Installation Review
• Carefully review MCE job prints and job requirements.
• Ensure that all equipment has been correctly installed and connected.
• Verify that all jumpers placed during installation have been removed and replaced with permanent connections.
• Verify that all safety equipment is installed and is functioning properly.
• Ensure that Inspection faults are no longer on bypass in the Controller System Menu (F3 function switch on MPU board)
At this point, controller and related installation should be complete. The car should be running safely on Inspection operation from the cartop and/or the machine room. The next section will describe:
• Learning the hoistway
• Setting controller parameters
• Setting drive parameters
• Performance Adjustment
• Final Test
2-82 Manual # 42-02-2P25
Final Adjustments
In this Section
This section contains instructions for preparing the car for normal automatic operation. If you are viewing this on a computer, click the blue text to jump to the appropriate section.
• Setting basic service parameters.
Basic Service Parameters on page 3-2
.
• Learning the Hoistway, Positioning ETS on page 3-2
• Balance Car and Counterweight.
Car and Counterweight Balance on page 3-8
• Setting Up Performance Curves.
Setting Up Performance Curves on page 3-9.
• Coming up to contract speed.
Additional Adjustment on page 3-17.
• How to place car calls from the controller.
Placing Calls From the Controller on page 3-20
.
• Load testing AC drives.
Load Testing AC Drives on page 3-21 .
• Load Weigher Adjustment.
Load Weigher on page 3-23 .
• Acceptance Testing. Final Tests on page 3-33 .
• Final Adjustment.
Final Adjustment on page 3-56
.
3-1
Final Adjustments
Basic Service Parameters
Parameters accessed through the F1 (Program Mode) function on the HC-MPU board define the building, floors and openings to be serviced, and other basic requirements for the elevator.
Before the controller is shipped, these basic service definitions are set according to the survey forms for the job. However, always verify Basic Features Menu settings are correct for the job before proceeding.
Please refer to “Basic Features Menu” on page 4-13 for basic service setup.
Learning the Hoistway, Positioning ETS
The following table is provided so that you can enter floor heights and offsets for your records.
Table 3.1 Floor Height and Offset Notation
13
14
15
16
9
10
11
12
7
8
5
6
3
4
1
2
Floor Height Offset Floor
29
30
31
32
25
26
27
28
21
22
23
24
17
18
19
20
Height Offset
The F6 menu provides a process to learn the floor levels and counterweight position for the building. The process is different depending on the type of landing/positioning system for the job.
3-2 Manual # 42-02-2P25
Motion 4000
Learning the Hoistway, Positioning ETS
ELGO Encoded Magnetic Tape
1. Verify F7 parameter 191 is set to Elgo 160 or Elgo 240. (160 and 240 designations refer to the distance between the individual sensors in the Elgo sensor head. One is 160mm; the other is 240mm.) Verify F7, 149 is set to the correct Contract Speed.
2. Place the car on Inspection mode.
3. Verify the floors and openings through the F1 (Program Mode) menu if you have not already done so. (
F1: Program Mode on page 4-11
.)
4. Plug the hand-held user interface into a CAN connection in the car panel or on the cartop. Otherwise, use the HC-MPU board keypad/LCD in the controller. (If the controller keypad is used, a technician must be stationed in the car to relay information to the technician in the machine room.)
5. Move the car to level at the first floor.
6. Select the F6 menu on the hand-held or HC-MPU board (F6 switch UP, all others down).
• ELGO LEARN. PRESS NEXT TO LEARN OR SELECT TO FILL
HOISTWAY LEARN
N=LEARN / S=FILL
3
Note
Selecting LEARN will start an operation in which you learn accurate floor levels as the car moves up the hoistway. Selecting FILL lets you skip the learn operation and just plug in an average value for floor heights so that you can take the time to perform a learn operation later.
Learn
Selecting LEARN starts a process in which you move the car up the hoistway a floor at a time, leveling and saving at each floor.
1. Press N. The display will prompt: Go to landing 1.
2. Bring the car as close to level at landing 1 as is practical. Press S.
3. The display will ask you to enter an offset to make up for any difference in level between car and floor: xxx.x In. Adj + - Next when done.
4. Measure the offset (if any).
5. If the car is above the floor, use the + (plus) button to enter the offset value.
If the car is below the floor, use the - (minus) button to enter the offset value.
6. Press N. The display will prompt you to move to the next landing. The process will repeat at each landing until all have been learned.
7. When all floors have been learned, the display will prompt you to learn counterweight position.
• MOVE CAR ADJACENT TO COUNTERWEIGHT, THEN PRESS NEXT.
8. Move the car until car and counterweight are level with one another in the hoistway.
3-3
Final Adjustments
9. Press N. The display will prompt you to store values:
• HOISTWAY LEARNED. S=STORE.
10. Press S. The display will prompt:
• HOISTWAY STORED
11. Exit F6 menu on the hand-held or place F6 switch down on the HC-MPU board.
Fill Selecting FILL allows you to enter a common height for all floors which will then be filled in by system software. The position of the counterweight is automatically set to one half the cumulative height of the floors.
HOISTWAY LEARN
N=LEARN / S=FILL
1. With the car level at floor one, Press S.
2. Use the “+”/”-” buttons to enter a common floor height in inches.
HEIGHT: 0.0 IN
N=NEXT
3. Press N. The display will prompt you to store values:
• HOISTWAY LEARNED. S=STORE.
4. Press S. The display will prompt:
• HOISTWAY STORED
Exit F6 menu on the hand-held or place F6 switch down on the HC-MPU board.
Offset Motion 4000 allow the door zone heights to be individually adjusted in 0.10 inch increments to compensate for minor error up to a maximum +/- 0.9 inches.
Slowdown Learn, ETS Placement, Elgo
This operation determines locations for slowdown and emergency switches for the job and, if
ETS are used, automatically assists you in placing them.
1.
Please refer to “Terminal Switch Options, 69 - 74” on page 4-150 . Reference your job
prints and activate the switches uses on your job.
2. Move the car to the bottom terminal on Test mode.
3. Set the F5 function switch in the UP/ON position.
4. Move to the Terminal Limit Utilities menu and press S to select.
5. The LCD will display PERFORM UXTS AND DXTS LEARN. Press S to Select.
6. The LCD will display TERMINAL LEARN/S: START. Press S to begin.
3-4 Manual # 42-02-2P25
Motion 4000
Learning the Hoistway, Positioning ETS
7. The LCD will ask you to enter switch tripping thresholds for the ETS switches (if used), then for the NTS switches used on the job.
• Press S to move the cursor to a digit position.
• Use +/- buttons to increment/decrement values.
• Typical ETS setting is 80% (of contract speed). Press N to move on.
• NTS settings depend on switch position:
• Outermost NTS: 90% (of contract speed). Press N to move to next NTS switch.
• Next NTS in: 70%. Then 60%, 50%, 40% for additional switches moving toward the terminal.
8. After the last NTS switch is set, the LCD will cue you to press S to store the values.
9. After switch thresholds are stored, the LCD will display LEARN READY/S= LEARN
UXTS. Press S to initiate.
The car will move up the hoistway, reporting each switch as its position and speed are learned.
At the top of the terminal, the LCD will display:
10. UXTS LEARNED/S= LEARN DXTS. Press S to initiate.
11. The car will move down the hoistway, repeating the learn for the bottom terminal. It will stop at the bottom floor and report SAVING SWITCHES, PLEASE WAIT followed by
TERMINAL DONE/S=EXIT. Press S to exit the learn.
LS-EDGE Steel Tape
Parameter Settings
Verify F7, parameter 191 is set to LS-EDGE,
page 4-162
. Verify F7, 149 is set to the correct Contract Speed.
Hoistway Learn, LS-EDGE
1. Place the car on Inspection operation.
2. Move the car to the bottom terminal.
3. Set the F6 function switch in the UP/ON position.
4. The LCD will display HOISTWAY LEARN, PRESS S.
5. Press S to initiate learn.
6. Place car on TEST mode. Shut off INSPECTION. Follow instructions on the LCD.
Synopsis As you follow the instructions on the LCD, the car will first travel down to the bottom terminal then move up to locate the center of the door zone magnet. From the bottom terminal, the car will move up the hoistway finding each door zone and indicating the height in inches of each door zone magnet center (Front and/or Rear as appropriate). Upon reaching the top terminal, the LCD will report hoistway information stored and offer the option to press N if you are Done or S if you want to restart the learn operation.
7. Press N when hoistway learn reports complete to exit the operation.
8. Place F6 in the Down position.
Once the door zones have been learned, you are ready to learn terminal and emergency slow-
down positions, Slowdown Learn, ETS Placement on page 3-6 .
3
3-5
Final Adjustments
Offset Motion 4000 allow the door zone heights to be individually adjusted in 0.10 inch increments to compensate for magnet placement irregularity up to a maximum +/- 0.9 inches for LS-EDGE.
Slowdown Learn, ETS Placement
This operation determines locations for slowdown and emergency switches for the job and, if
ETS magnets are used, automatically assists you in placing them.
1.
Please refer to “Terminal Switch Options, 69 - 74” on page 4-150 . Reference your job
prints and activate the switches uses on your job.
2. Move the car to the bottom terminal on Test mode.
3. Set the F5 function switch in the UP/ON position.
4. Move to the Terminal Limit Utilities menu and press S to select.
5. The LCD will display PERFORM UXTS AND DXTS LEARN. Press S to Select.
6. The LCD will display TERMINAL LEARN/S: START. Press S to begin.
7. The LCD will ask you to enter switch tripping thresholds for the ETS switches (if used), then for the NTS switches used on the job.
• Press S to move the cursor to a digit position.
• Use +/- buttons to increment/decrement values.
• Typical ETS setting is 80% (of contract speed). Press N to move on.
• NTS settings depend on switch position:
• Outermost NTS: 90% (of contract speed). Press N to move to next NTS switch.
• Next NTS in: 70%. Then 60%, 50%, 40% for additional switches moving toward the terminal.
8. After the last NTS switch is set, the LCD will cue you to press S to store the values.
9. After switch thresholds are stored, the LCD will display LEARN READY/S= LEARN
UXTS. Press S to initiate.
The car will move up the hoistway, reporting each switch as its position and speed are learned.
At the top of the terminal, the LCD will display:
10. UXTS LEARNED/S= LEARN DXTS. Press S to initiate.
11. The car will move down the hoistway, repeating the learn for the bottom terminal. It will stop at the bottom floor and report SAVING SWITCHES, PLEASE WAIT followed by
TERMINAL DONE/S=EXIT. Press S to exit the learn.
12. If you have ETS on the job, press N until the LCD displays ETS POSITIONS LOCATOR.
Press S to select.
13. The LCD displays ETS POSITIONS LOCATOR/OFF. Press S to turn the LOCATOR ON.
14. Place the car on Cartop Inspection.
15. Run the car up the hoistway. When it reaches the learned location for the DETS, it will stop. Release the inspection switches.
3-6 Manual # 42-02-2P25
Motion 4000
Learning the Hoistway, Positioning ETS
16. Place the 5”, striped DETS magnet on the tape immediately above the sensor head and just to the RIGHT of the tape perforations. See below.
3
DETS UETS
17. Continue to run the car up the hoistway. When it reaches the learned location for the
UETS, it will stop. Release the inspection switches.
18. Place the 5”, striped UETS magnet on the tape immediately above the sensor head and just to the LEFT of the tape perforations. See above.
19. Set the ETS POSITIONS LOCATOR to OFF. Place the F5 switch down.
Position Adjustments The learn operations described above automatically store switch and speed related information in F7 menu parameter range 1 - 132. Through these parameters, you can display stored values and also make adjustments to the values. Normally, no or very little adjustment is necessary.
Adjusting Floor Heights
Stored floor heights may be accessed through the F7 menu (first 64 parameters) and the height of each floor individually adjusted at any time. F7 parameter 67 allows you to adjust the counterweight height.
1. Place the car on Inspection, enter the F7 menu (F7 up, all other switches down).
2. Press N to advance to the desired parameter.
3. Use “+” or “-” buttons to adjust the height of the floor (or counterweight).
4. Place F7 in the down position.
Door Zone Verification
Following the hoistway learn process, starting at the top floor, move the car down on inspection and verify that the door zone indicators (e.g., LEDs, relays, diagnostic status, etc.) activate only at the appropriate locations at the landings (i.e., +/- 75 mm or 3”) and nowhere else. Be sure to check rear door zones as well, where applicable.
3-7
Final Adjustments
Car and Counterweight Balance
Hoistway machine performance is specified to a particular load (car equipment and passengers) and to a specified offset to the load through counterweighting. On modernizations, the weight of the car is often changed but compensating adjustments to the counterweight are sometimes overlooked. This adjustment is important to performance and ride characteristics.
1. Place a balanced load in the car (specified percentage of full load; typically 40% but sometimes 45 or 50%).
2. On Machine Room Inspection, run the car to the middle of the hoistway to the position learned by performing the counterweight learn procedure.
3. Turn controller power OFF.
4. Manually lift the brake.
5. Watch the car to see if it drifts. If not, the car and counterweight are balanced.
• If the car drifts up, remove weight from the counterweight or add weight to the car and repeat the balancing procedure.
• If the car drifts down, add weight to the counterweight or remove weight from the car and repeat the balancing procedure.
• For a drum machine, follow the manufacturer counterweighting recommendations and test the drum machine limit switches.
6. When car and counterweight are balanced, record the actual weight in the car for future reference. Balanced load = _____________lbs.
7. Restore controller power.
3-8 Manual # 42-02-2P25
Motion 4000
Setting Up Performance Curves
Setting Up Performance Curves
Before attempting to bring the car up to contract speed, you must have verified drive parame-
ters as described in Section 2. TORQMAX F5 AC Drive Parameters on page 2-30 or
Magnetek
AC Drive Parameters on page 2-35
, F7 parameters as described in Section 4,
F7: Parameters
Adjust on page 4-141,
and be successfully running on Inspection mode with all equipment installed.
Performance curves are defined by acceleration and deceleration rates. The top speed attained using a curve is defined by speed settings for a particular mode of operation (Contract Speed,
Inspection Speed, etc.). Multiple speed settings can use the same performance curve. Please refer to “Controller F7 Menu” on page 3-11
.
How to Register Calls from the Controller
To place a call from the controller (or the hand-held):
• Place the F5 function switch up (all others down).
• Press S until Front Call Registration is displayed.
• Refer to the illustration below.
* CONTROLLER *
*UTILITIES MENU*
+ and N
S
- FRONT CALL -
- REGISTRATION -
S
+ and N
FRONT CAR CALL:
LANDING 01 [OFF]
+/-
+ and N
FRONT CAR CALL:
LANDING 02 [OFF]
S
+ and N
FRONT CAR CALL:
LANDING 02 [ON]
+ and N
N
- REAR CALL -
- REGISTRATION -
S
REAR CAR CALL:
LANDING 01 [OFF]
+/-
REAR CAR CALL:
LANDING 02 [OFF]
S
REAR CAR CALL:
LANDING 02 [ON]
N
- VIEW -
- DATE AND TIME-
+ and N + and N + and N
3
• +/- to increment or decrement floor numbers
• Press and momentarily hold S to register calls; displays [ON] while held
• Press + and N together to back out of the current display
3-9
Final Adjustments
Acceleration and Deceleration Rates
Acceleration and deceleration rates are measured and programmed in ft/s
2
(feet per second per second). Jerk parameters adjust the rate of transition from one speed to another and are measured and programmed in ft/s
3
(feet per second per second per second). F7 control parameters correspond to curve locations as shown in the following figure. Increasing Jerk values causes faster change. While adjusting S-Curve parameters, stay away from terminal floors.
Figure 3.1 Motion 4000 Performance Curves
Standard-F7:166
Manual-F7:171
Danger-F7:176
Alternate-F7:180
Roll Jerk
Roll Jerk
Standard
Alternate
Standard-F7:168
Manual-F7:173
Alternate-F7:182
Acceleration
Standard-F7:169
Manual-F7:174
Danger-F7:178
Deceleration
Manual
Danger
Standard-F7:165
Manual-F7:170
Danger-F7:175
Alternate-F7:179
Start Jerk
Leveling Speed (F7:158)
Zero Speed
F7-157 Correction Speed
Proximity Distance
Curves Used for Operating Speeds
The performance curves shown above and the operating speeds that use them are:
• Standard Curve: Contract, correction, earthquake, and leveling speed
• Alternate Curve: Conservation, and emergency power speed
• Manual Curve: Inspection and reduced inspection speed
• Danger “Curve”: Used for emergency deceleration
Standard-F7:167
Manual-F7:172
Danger-F7:177
Alternate-F7:181
Stop Jerk
3-10 Manual # 42-02-2P25
Motion 4000
Setting Up Performance Curves
Profile Parameters
Typical initial values to begin adjusting toward contract speed running are listed in the table below. Hoistway speed and position related information may be reviewed using a controller F5
switch-accessed menu. Please refer to “MPI Diagnostic Menu” on page 4-69 .
• Start jerk - defines rate of transition from zero speed to full acceleration. As Start Jerk increases, the profile transitions more quickly from starting to maximum acceleration.
• Acceleration - determines the maximum acceleration for the profile.
• Roll jerk - Roll Jerk determines the rate that the profile transitions from maximum to zero acceleration and zero to maximum deceleration. As Roll Jerk increases, the profile transitions more quickly. Lower values provide greater comfort but are harder to fit into the shortest one-floor-runs.
• High speed - determines the maximum speed for the Standard curve, usually the same as contract speed (ft/min).
• Contract speed - the rated speed for the car.
• Inspection speed - determines the speed at which the elevator will run when the Manual curve is being used.
• Deceleration - determines the maximum deceleration for this profile.
• Stop jerk - defines the transition from deceleration to Leveling Speed. As Stop Jerk increases, the profile transitions more quickly from Deceleration to Leveling Speed.
• Leveling speed - determines the Speed at which the elevator will level into the floor.
Table 3.2 Controller F7 Menu
Curve Aspect
Start Jerk
Acceleration
F7 Parameter
165, 170, 175, and
179 (each per curve)
168, 173, and 182
(each per curve)
Initial Setting
From 4.0 to 8.0 ft/s
3
(1.219 to 4.438 m/s results in a sharper start.
3
. Higher value
Maximum value is typically 4.0 ft/s
2
(1.219 m/s
2
) and the minimum is usually not less than 2.5 ft/s
2
(0.762 m/s
2
).
Values higher than 4.0 ft/s
2
(1.219 m/s
2
) are possible but do not yield significant improvements in performance.
Set by software.
Unit
ft/s ft/s
3
2
Roll jerk
Deceleration
Stop jerk 167, 172, 177, and
181 (each per curve)
High speed 150
Inspection speed 155
Leveling speed
Contract speed
Profile Scale
158
149
141
166, 171, 176, and
180 (each per curve)
169, 174, 178, and
183 (each per curve) ft/s
3
Maximum value is typically 4.0 ft/s
2
and the minimum is usually not less than 2.0 ft/s
2
with more common values ranging from 2.75 ft/s
2
to 3.75 ft/s
2
(0.838 to 1.143 m/s
2
).
The value of Deceleration is usually slightly less than the value of Acceleration (by 0.25 to 0.5) ft/s
2
From 4.0 to 8.0 ft/s
3
(1.219 to 4.438 m/s results in a sharper stop.
3
. Higher value
Set to Contract Speed.
As desired, up to 66% of contract speed or 125 ft/m
2 to 5% of contract speed, 0 - 8 FPM.
Contract speed
Initially set to 50%. After making some adjusting runs, this can be gradually be increased to 100% to attain contract speed.
ft/s
3 ft/m ft/m ft/m ft/m
%
3
3-11
Final Adjustments
Typical Speed Profile Settings
Table 3.3 Speed Profile Settings Per Rated Speed
Params
25 FPM or Less
(26-75)
FPM
(76-100)
FPM
(101-
199) FPM
0.10
0.15
1.5
3.0
(200-
249) FPM
3.0
(250-
349) FPM
4.0
350FPM or greater
4.0
Standard Jerk (165)
Alt Start Jerk (179)
Standard Roll Jerk (166)
Alt Roll Jerk (180)
Standard Stop Jerk (167)
Alt Stop Jerk (181)
Standard Accel. (168)
Alt Accel (182)
Standard Decel. (169)
Alt Decel. (183)
Man Start Jerk (170)
Man Roll Jerk (171)
Man Stop Jerk (172)
Man Accel. (173)
Man Decel. (174)
Danger start Jerk (175)
Danger Roll Jerk (176)
Danger Stop Jerk (177)
Danger Decel. (178) a
Automatic Slew slope (142)
0.10
0.10
0.10
0.10
0.10
0.10
0.10
0.10
0.10
5.0
2.0
1.0
0.25
0.15
0.15
0.15
0.25
0.25
0.15
0.15
0.15
0.25
0.25
10.0
2.0
2.0
0.75
0.15
1.5
1.5
0.5
0.5
0.50
0.50
0.50
0.50
0.25
3.0
2.5
1.75
1.25
1.00
1.00
1.00
0.50
3.0
2.5
2.5
1.5
4.0
2.5
2.75
1.75
4.0
2.5
3.0
2.0
0.50
0.50
0.50
0.50
0.50
Auto Calc Auto Calc Auto Calc Auto Calc Auto Calc
Auto Calc Auto Calc Auto Calc Auto Calc Auto Calc
Auto Calc Auto Calc Auto Calc Auto Calc Auto Calc
Auto Calc Auto Calc Auto Calc Auto Calc Auto Calc
0.5
1.00
1.00
1.00
0.50
0.5
1.00
1.00
1.00
0.50
0.5
1.00
1.00
1.00
0.50
0.5
a. There is also a setting for Inspection Slew Slope, F7, 205, to soften deceleration during Inspection operation.
3-12 Manual # 42-02-2P25
Motion 4000
Setting Up Performance Curves
Adjust for Drive Response
Depending on how the drive is tuned, the amount of lag between the commanded speed and drive response can vary. As a result, as the drive is adjusted, the Profile Advance parameter in the controller F7 menu will need to be changed as well. Use the information below along with
the information in the figure, Velocity and Acceleration on page 3-14, and the tuning instruc-
tions following the figure to make these adjustment.
• If lag delay is insufficient, the elevator will plow into a landing. The acceleration and jerk rate during deceleration to a landing will be greater than profile values indicate.
• If lag delay is excessive, the elevator will drag into a landing. The acceleration and jerk rate during deceleration to a landing will be less than profile values indicate. In addition, a discontinuity in the profile will occur during the transition from acceleration to deceleration for movement between floors where a stabilized speed (contract speed) is not reached
(short runs).
• To adjust lag delay, observe the commanded speed on the TC-MPI board at the AN1 analog output. Perform one-floor-run movement and observe the peak acceleration transitioning to peak deceleration as the elevator reaches its peak speed (below contract speed). This transition should have no vertical discontinuity (too much lag delay).
This transition adjustment is only valid when the elevator is unable to reach contract speed for the profile under normal operation. Adjust lag delay until the vertical discontinuity is eliminated.
• TORQMAX: Generally, the Profile Advance (F7, 140) will be within 50 to 150 milliseconds.
• Magnetek: Generally, the Profile Advance (F7, 140) will be within the following range (in milliseconds):
3
3-13
Final Adjustments
Figure 3.2 Velocity and Acceleration
(a)
(b) (c) (d)
Velocity and Acceleration: (a) profile at contract speed; (b) insufficient lag compensation with profile at less than contract speed; (c) excessive lag compensation with profile at less than contract speed; (d) optimum lag compensation with profile at less than contract speed.
Tuning
1. For initial setup, set the Profile Advance parameter, F7, 140, to 1 divided by response.
2. Depending upon drive tuning, the leveling distance may have to be generous to allow the elevator speed to completely transition to the requested leveling speed. for initial use, set the Leveling Distance parameter, F7, 160, to 2.0 inches. (Once the drive is tuned, this may be set to a more optimum value.)
3. Depending on drive tuning, the transition from leveling speed to zero speed may be sluggish. For initial use, set the Standard Slew Slope parameter, F7, 142, to 2.0 ft/s2 or greater. (Once the drive is tuned, this may be set to a more optimum value.)
Verify One Floor Run Operation
1. Run the elevator on Inspection between landings and verify that it moves properly.
2. After taking the elevator out of inspection mode, verify that the elevator corrects to a landing and stops properly.
3. Make a one floor run and observe the elevator as it moves between landings and stops at landings.
3-14 Manual # 42-02-2P25
Motion 4000
Setting Up Performance Curves
Verifying Contract Speed Operation
1. Run the elevator between landings and verify that it moves properly.
2. Observe the elevator as it starts from landings, moves between landings, and stops at landings.
3. Progressively increase the number of landings traveled until contract speed is achieved.
Initially, start with a Profile Scale of 75%. If the car runs as expected, slowly increase
Profile Scale to 100%.
4. When the elevator achieves contract speed, verify speed through the F5, MPI-A diagnostics menu, address 16.
5. Place car on Normal operation and place a call to the top terminal. The car must land without a fault.
6. Place a call to the bottom terminal. The car must land without a fault.
TORQMAX:
7. If speed is not correct, set LF.22 to a value between 125% and 150% of LF.25 and adjust hoist motor speed, controller F7, 148.
Magnetek
8. If speed is not correct, adjust Contract Mtr Spd on the A1 Drive menu (higher RPM for increased speed) and adjust hoist motor speed, controller F7, 148.
If an ETSL switch is required:
• The ETS switch will be used as the ETSL and its position will be located at 90% of the reduced stroke buffer rated speed. ETSL Delta Speed will be 5% of the reduced stroke buffer rated speed. If ETSL is too far below the speed curve, you can adjust the Delta Speed closer to 10% of the reduced stroke buffer rated speed.
• The second-in NTS switch will be used as the ETS. The Delta Low Speed for the NTS switch will match the Delta High Speed so that the NTS switch will behave like an ETS.
3
3-15
Final Adjustments
Short Floors Near a Terminal
When a short floor is located immediately preceding a terminal, the NTS1 switch must be located before the “landing” height of the short floor. (This is because the NTS1 switch remains the final correction for the positioning system. When it encounters NTS1, it knows that, regardless of any other information, the next stop is the terminal.) For example, the bottom terminal is at 0.0-inches. If the short floor is at 36 inches, the NTS1 switch must be located between 0.0 and 36-inches.
Figure 3.3 NTS1 Position with Short Floor
Normal Run
DNTS2
DNTS1
Short Floor Run
Terminal Floor
Distance
0.0 inches, Terminal Floor Height
18.0 inches, DNTS1 Distance
36.0 inches, Short Floor Height
Short Floor from 1 to 12-inches in Height
For short floors from one to twelve inches in height, the NTS1 switch cannot be used for overspeed detection. To avoid tripping overspeed errors in this situation, set the NTS1 switch speed significantly beyond the contract speed for the job, for example, 900 FPM.
3-16 Manual # 42-02-2P25
Motion 4000
Additional Adjustment
Additional Adjustment
Tuning (Magnetek)
The Magnetek drive may require additional tuning to the motor:
Tuning Motor No-Load Current (HPV 600/900/900II)
1. To perform this procedure you will need to run the car at reduced speed with a balanced load. Motor torque should be below 15%.
• Motor Torque, Flux Reference, and Est No Load Curr can be viewed on the drive D2
Power Data menu.
• No Load Curr can be adjusted on the drive A5 Motor menu.
• The car maximum speed can be changed via High Speed on the controller F7 menu,
150. (F7, 149, Contract Speed is used to set the rated speed for the car.)
2. Refer to Tuning No-Load Motor Current in the appendix of the Magnetek HPV AC Drive
Technical Manual and follow that procedure.
Tuning Motor Flux Saturation Curve (HPV 600/900/900II)
1. To perform this procedure you will need to run the car at full contract speed with a balanced load.
• Est No Load Curr can be viewed on the drive D2 Power Data menu.
• No Load Curr and Flux Sat Slope 2 can be adjusted on the drive A5 Motor menu.
2. Refer to Tuning Rated Motor RPM in the appendix of the Magnetek HPV AC Drive
Technical Manual and follow that procedure.
Tuning Motor Rated RPM (HPV 600/900/900II) Please see Tuning Motor
Rated RPM in the appendix of the Magnetek HPV AC Drive Technical manual and follow that procedure.
Determining System Inertia (All Magnetek)
In order to properly tune the speed regulator of the Magnetek drive, a valid inertia value must be determined.
1. To perform this procedure, you will need to run the car at full contract speed with a balanced load.
• Est Inertia can be viewed on the drive D1 Elevator Data menu.
• Inertia can be adjusted on the drive A1 Drive menu.
2. Refer to Using the Software to Estimate the System’s Inertia in the appendix of the Magnetek HPV AC Drive Technical Manual and follow that procedure.
3. With system inertia properly adjusted, final tuning of the speed regulator can be performed. The Response parameter on the drive A1 Drive Menu is one parameter that can be used to adjust the speed regulator. Please see the Magnetek HPV AC Drive Technical
Manual for tuning/adjustment procedures.
3
3-17
Final Adjustments
Relevel Operation
On Inspection, move the car to the bottom landing onto leveling. Take the car off Inspection and observe that it re-levels into the landing. If the car attempts to re-level but cannot:
1. If the car attempts to relevel but cannot:
• Adjust Leveling speed parameter F7:158 to get the car to move.
• Check that the car is not opening the down final limit.
2. If a fault code is displayed, troubleshoot and correct the fault.
3. Verify that the position indicator matches the car position.
4. Verify that the brake has been set as described in Section 2 to hold 125% of load, Adjust
Brake to 125% of Full Load on page 2-82 .
Brake Coordination
1. Adjust speed pick delay parameter F7:134 so that the brake is fully picked just as the motor first spins. The goal is to avoid spinning the motor before the brake is picked but not to introduce so much delay that rollback occurs.
2. TORQMAX: Refer to the TORQMAX drive manual for information relating to speed pick delay interaction with pre-torque parameters.
3. Magnetek: Refer to Rollback Gain in the Magnetek HPV AC Drive Technical Manual.
Run Tests
Register calls to all the landings in turn and observe that the car stops properly at the requested landing. As drive adjustments are made to tune performance, parameters on the controller F7 menu may need readjustment: Profile Advance, Leveling Distance, Leveling Dead Zone, Standard Slew Slope, Standard Stop Jerk, etc.
Adjustment Problems
Speed Changes Felt Excessively in Car During high speed, if the speed change from accel to high speed or from high speed to decel can be felt excessively in the car:
• TORQMAX: Decrease parameter A.LF.33 Ki speed offset accel and/or d.LF.33 Ki speed offset decel and d.LF.32 in steps of 100 to achieve smoother transitions. This may also be due to inaccurate drive adjustment,
Please refer to “Speed and Acceleration Control” on page 2-29
.
• MAGNETEK: Consider Estimation of System Inertia, A0/A1 Response, A0/A1 Inner Loop
Xover, A0/A1 Gain Reduce Mult, and A1/A0 Gain Chng Level.
Loss of Control During Acceleration Acceleration rate should be at least as great as deceleration rate but should not exceed deceleration rate by too much. Excessive acceleration rates may cause drive circuits to saturate and effectively lose acceleration control.
3-18 Manual # 42-02-2P25
Motion 4000
Additional Adjustment
Car Overshoots, TORQMAX E.OL/E.OP, MAG Mtr Overload/Overvolt Flt
• Refer to drive manual for error definition and troubleshooting instructions
• Check counterweighting is correct.
• Decrease Standard Acceleration, F7:168, Standard Deceleration F7, 169, Standard Roll
Jerk F7/ 166, and Standard Stop Jerk, F7, 167.
• Increase drive gains, TORQMAX LF.31 and LF.32 or MAG A0/A1 RESPONSE.
• Shut off power. Wait 1 minute to drain DC voltage from dynamic braking circuit. Verify no
DC voltage with voltmeter.
• Check value of braking resistance (RB resistors). Check circuit connections and slip rings.
(Approximately 3 times the measured brake coil resistance is a good starting point.)
Car Oscillates at Contract Speed
• Verify all motor parameters are correctly set and encoder is mounted well (no vibration).
• TORQMAX: Verify gain parameters TORQMAX, A.LF.31 and A.LF.32 are not set too high.
• Magnetek: Verify Estimation of System Inertia, A0/A1 Inner Loop Xover, A0/A1 Gain
Reduce Mult, and A0/A1 Gain Chng Level. Verify A0/A1 Response is not set too high.
3
3-19
Final Adjustments
Placing Calls From the Controller
To place a call from the controller (or the hand-held):
• Place the F5 function switch up (all others down).
• Press S until Front Call Registration is displayed.
• Refer to the illustration below.
* CONTROLLER *
*UTILITIES MENU*
+ and N
S
- FRONT CALL -
- REGISTRATION -
S
+ and N
FRONT CAR CALL:
LANDING 01 [OFF]
+/-
+ and N
FRONT CAR CALL:
LANDING 02 [OFF]
S
+ and N
FRONT CAR CALL:
LANDING 02 [ON]
+ and N
N
- REAR CALL -
- REGISTRATION -
S
REAR CAR CALL:
LANDING 01 [OFF]
+/-
REAR CAR CALL:
LANDING 02 [OFF]
S
REAR CAR CALL:
LANDING 02 [ON]
N
- VIEW -
- DATE AND TIME-
+ and N + and N + and N
• +/- to increment or decrement floor numbers
• Press and momentarily hold S to register calls; displays [ON] while held
• Press + and N together to back out of the current display
If the car opens a Final Limit If the car overshoots a terminal and opens the Final
Limit switch, power will immediately be removed from the machine and brake and the car will come to an immediate stop. If this occurs, it means the Final Limit switch is incorrectly positioned (check job prints), that differential gain or other motor settings are incorrect, or that the
“virtual” slowdown switches selected for the performance curve are too aggressive.
1. Check the Final Limit switch position at both terminals against the job prints.
2. Check all motor and encoder related settings.
3. Slightly increase differential gain settings and/or incrementally move virtual terminal slowdown switches away from the terminal landing.
4. Retest.
Note
If a Final Limit Switch has opened, you will need to place the car on Inspection operation and temporarily “jumper out” the limit switch while you move the car to the terminal landing.
3-20 Manual # 42-02-2P25
Motion 4000
Load Testing AC Drives
If the car does not leave a landing
• If the elevator is trying to level, it will not pick high speed and leave the landing until is completes leveling.
• Check status of SAFL. Verify door locks are made.
• Verify Auxiliary Speed (F7, 153) not set to 0.0 FPM.
• Verify Acceleration and Start Jerk settings.
• If any of the inputs that open the door are active (Safety Edge On, Photo Eye On, etc.) or if the UIO board car call terminal for the current floor (floor displayed in PI) is grounded the car will not move.
Load Testing AC Drives
1. Add 100 or 200 pounds of test weights to the car.
2. Observe current draw as the car is accelerating.
3. Repeat until rated load is achieved, looking for:
• Overload drive errors, indicating that the drive is being pushed close to its limits and may require:
• If requested acceleration rate is excessive, reduce acceleration rate. The lower the acceleration rate, the lower the current demand.
• Adjust jerk for a more gradual transition from acceleration to high speed.
• Adjust drive gains.
• The motor may be underrated. Try reducing the motor speed setting slightly.
• Check for proper counterweighting. (With a balanced load, drive/motor current should be the same in both up and down directions.)
• If needed, make a copy of the drive parameter table and write down all settings. Contact MCE for assistance.
Trouble Slowing with a Full Load
If there is an issue with slowing a fully loaded car in the down travel direction, or if the AC drive is tripping off with an over voltage fault displayed, it may mean that there is a problem with regenerative braking or with the brake control module (if supplied).
Refer to the drive manufacturer manual. Generally:
• 230V drive will trip on over voltage if the DC bus Peak voltage reaches about 400 Volts or if standard DC bus voltage reaches about 325 Volts.
• 460V drive will trip on over voltage if the DC bus Peak voltage reaches about 800 Volts or if standard DC bus voltage reaches about 650 Volts.
1. With the drive in operating mode, check DC bus and DC bus Peak voltage displays while the car is slowing with a full load in the down direction.
3
Danger
If you choose to actually measure the voltage across the drive power terminals, exercise extreme care. These voltages are lethal.
3-21
Final Adjustments
2. Measure the voltage across the controller braking resistors. If there is no measured voltage (car slowing/full load/descending or car slowing/no load/ascending), there may be a wiring problem or a defective brake module.
3. Investigate and solve this problem. The regenerative resistors or the brake module regulate car speed during full load down or empty load up conditions and are critical to safety. Contact MCE if necessary.
Electrical Noise
If the motor makes excessive electrical noise or draws higher than normal current:
• Check Encoder Polarity (TORQMAX) on page 2-46 or Align Encoder (Magnetek) on page 2-46.
• Check TORQMAX LF.29. Try changing it from 4 to 8 or from 8 to 16.
• Verify traction sheave diameter and correct entry in drive parameter.
• Verify machine gear reduction ratio and correct entry in drive parameter.
• Verify Rated Motor Speed and correct entry in drive parameter.
• Verify acceleration and deceleration integral and proportional gain drive settings. Refer to drive manufacturer manual for detail.
Note
Imperial motor nameplates list full load RPM. With induction motors, this value is equal to synchronous RPM less slip. If your motor lists only synchronous RPM, you must determine its slip percentage and subtract that amount to arrive at rated motor speed.
For example, a Reuland motor in a flux vector application has slip between 1.8% and 2.0%. If synchronous RPM is 1200, 1.8% of that is about 22 RPM so rated motor speed would be 1200 minus 22 = 1178 RPM. (F5 drive parameter LF.11. If you auto-tuned the drive to the motor, this parameter is learned and should not become a problem.)
3-22 Manual # 42-02-2P25
Motion 4000
Load Weigher
Load Weigher
Information from the load weigher is used for pre-torquing and for dispatching decisions, e.g. light load anti nuisance, heavy load, and overload.
• Installing the Load Cells (Sensors)
• Installing the Control Unit
• Control Unit description
• Load Weigher calibration
• Final calibration
• Installation with 2 to 1 roping
• Verifying zero calibration (empty car weight)
• Troubleshooting
Components include:
- Control Unit, model VK-3V
- Load Cells, model SWK
- Sensor installation tool
- Terminal tool/key (not shown)
- Terminal cover plate (not shown)
- DIN rail mounting bracket (not shown)
3
Analog Voltage or Relay Closure
The weigher provides both an analog output (0 - 10V) for analog weighing and relay closure outputs for discrete weighing inputs. Check the CT (Cartop) drawings in your job prints to see how your load weigher is connected.
3-23
Final Adjustments
Installing the Sensors
Install sensors using the leverage tool supplied. In some instances it may be necessary to use an extender on the handle to gain more leverage.
Typically the sensors are mounted on the wire ropes directly above the cartop hitch. However, with 2 to 1 roping the sensors must be mounted below the dead-end hitch beneath the overhead.
Please refer to “Installation with 2 to 1 Roping” on page 3-25
.
1. Notice that one of the sensor pins moves in and out. Move the pin to the in position as shown.
2. Place the sensor on the wire rope and apply leverage to rotate the sensor until the pin can be moved to the out position as shown.
Pin In
Pin Out
3-24 Manual # 42-02-2P25
Motion 4000
Installation with 2 to 1 Roping
When the EMCO load weigher is used with 2 to 1 roping, the sensors must be installed just below the dead-end hitch, as shown and do not travel with the car.
Therefore, we recommend that in these cases the EMCO control unit be mounted in the controller cabinet. The signal wires from the load cells must be routed through the overhead to the machine room. The sensor wires, which are only 6 feet in length, must be extended. Use a terminal block to join wire lengths and route wires through conduit.
We recommend enabling the Auto-zero
Calibration option for 2 to 1 roping instal-
lations. Please refer to “Auto-zero Calibration” on page 3-31 .
To Controller
Load Weigher
3
3-25
Final Adjustments
Installing the Control Unit
The control unit may be mounted using the DIN mounting bracket supplied or using the holes in the unit itself. For 1:1 roping, the EMCO unit is mounted on the cartop. For 2:1 roping, the
EMCO unit is mounted in the controller cabinet.
1. EMCO control unit to cartop box (1:1 roping) or controller (2:1 roping):
• Connect one of the terminals directly below the 115Vac label to the controller 1 bus
• Connect the second terminal directly below the 115Vac label to the controller 2 bus
2. Sensor wires connect to the control unit as indicated on the wire:
• red wire to terminal EXC+
• black wire to terminal EXC-
• green wire to terminal IN+
• white wire to terminal IN-
• shield wire to terminal MALLA
Use the Terminal tool/key (wire insertion tool), or a narrow flat blade screwdriver to open the detent in the terminal connector to allow insertion of the tinned wires.
Terminal tool/key
For 2:1 roped units, route the sensor wires through the overhead to the machine room. The sensor wires, which are only 6 feet in length, must be extended. Use a terminal block to join wire lengths and route wires through conduit.
3-26 Manual # 42-02-2P25
Motion 4000
Load Weigher
Analog Weigher Output Wiring
For analog weighers:
1. Connect the EMCO terminal labeled “Com” to the controller 1 bus.
2. Connect the 0 - 10V output to the I/O 16 / LW+ input of the UIO board shown in your job prints.
Relay Closure Output Wiring
For relay closure outputs:
1. Refer to your job prints.
Controls Overview
Use control unit buttons to program the weigher:
• Press the menu button until the desired parameter is displayed.
• Press the button to select the digit to be modified (digit blinks when selected).
• Press the button to change the digit.
• Press the menu button twice to save the new value. Once a value is saved, the control will display the next parameter.
• If you do not press the menu button twice, the changes will not be stored and the control display will continue to show the parameter you were previously modifying.
Menu Order
Pressing the menu button will scroll through the Installation Menu in the following order:
Measured weight in car (value displayed varies with load in car)
Relay C set point (also sets the analog output 10Vdc reference value)
Relay S set point
Relay A set point
Learn empty car weight (Zero weight)
Learn full load weight (Calibrate with Weights)
3
Auto zero calibration (used as required)
Confirmation
3-27
Final Adjustments
Calibration
Manual Calibration with Weights
This procedure allows the EMCO control unit to do the following:
• Learn the empty weight of the car and set this weight as the zero reference (the analog voltage output from the control unit will be about zero volts at this weight).
• Learn a known weight. You place a known weight in the car and enter it into the control unit. The load weigher will then learn this weight.
• If you are using the analog output, you will enter the car overload weight value. The control unit uses this information to scale the analog output so that, at the point the sensors detect overload conditions, the analog output is about 10 volts. The analog output from empty to overload weight will be linear from about 0.0 to 10.0 volts.
• If you are using the relays, you will enter the set points for each relay.
1. Before programming or calibrating the sensors and control unit:
• Bring car to the lowest floor of its total travel.
• Bounce in car to verify that it is free on guide rails.
2. Verify that the sensors are properly connected to the control unit.
3. Power up the control unit and verify that the input voltage is within the voltage range of the control unit.
4. Verify that the sensors are installed on the wire ropes per the previous instructions.
5. Learn the empty car weight (Zero the control unit):
• Press the menu button until is displayed.
• Press the button once. The display will flash.
• While the display is flashing, press the menu button once. If the display stops flashing before you press the menu button, you must start over.
• The control unit display begins to count down. Exit the cartop before the countdown finishes.
• When the zero calibration is complete, will be displayed. If shown, the value has not been saved and this step must be repeated.
6. Learn a known weight (full load is recommended):
is not
• Press the menu button until is displayed, if it is not shown already.
• Place a known weight in the car (full load recommended).
• Enter the value of the known weight. Press the button to select a digit (blinks when selected) and press the button to set the value.
Note
If the overload weight (125% of full load) will exceed 9999 lbs, use a percentage of the full load weight instead. For example, if full load weight is 9,000 lbs, scale it to 80% by entering 7200.
That way, overload weight will be under 9999 lbs (9000 lbs with the given example). If value exceeds 9999, the weigher will display err7.
3-28 Manual # 42-02-2P25
Motion 4000
Load Weigher
• Press the menu button twice. The control unit will begin to count down. Exit the cartop before the countdown finishes. When the known weight has been learned,
will be displayed. You can press the menu button until the weight is shown on the control unit display. The weight displayed should be the value of the weights in the car, or the scaled value.
Complete steps 7, 8, and 9 only if the load weigher analog output will be used (references the analog output to 10Vdc at this weight). Go to Relay Setup for relay output weighing.
7. Enter the overload weight:
• Press the menu button until is displayed.
• Enter the value of the overload weight (or the scaled value if you scaled full load weight
- use the same scaling factor). Press the button to select a digit (blinks when selected) and press the button to set the value.
• Press the menu button three times to save your entries.
8. With the full load of weights in the car, using a digital multimeter, measure the voltage at terminals 0-10v and Com on the control unit. It should be approximately 8 volts.
Note the exact value.
Relay Setup
1. For discrete relay closure weighers, the set points for relays AL C, AL S, and AL A must be programmed as shown in the job prints, typically -
• Light Load - 25% or less of full load, relay ON/normally closed
• Dispatch Load - 60% of full load, relay OFF/normally open
• Heavy Load - 80% of full load, relay OFF/normally open
• Overload - 100% of full load, relay OFF/normally open
• Overload 2 - 125% of full load, relay OFF/normally open
2. Enter the trip point for relay AL C - (EMCO terminal #2 on the job prints).
• Press the menu button until is displayed.
• Enter the value of the desired trip point weight (or the value of the weight scaled by the same percentage used in step 6). Press the button to select a digit (blinks when selected) and press the button to set the value.
• Press the menu button once. The display indicates “On” which means normally closed (contacts will open when weight exceeds set point). Press the button if you want to change it to “Off”, normally open (contacts will close when weight exceeds set point).
• Press the menu button twice to save the settings.
3
3-29
Final Adjustments
3. Enter the trip point for relay AL S - EMCO terminal #4 on the job prints).
• Press the menu button until is displayed.
• Enter the value of the desired trip point weight (or the value of the weight scaled by the same percentage used in step 6). Press the button to select a digit (blinks when selected) and press the button to set the value.
• Press the menu button once. The display indicates “On” which equals normally closed. Press the button if you want to change it to “Off”, normally open.
Press the menu button twice to save the settings.
4. Enter the trip point for relay AL A - EMCO terminal #6 on the job prints).
• Press the menu button until is displayed.
• Enter the value of the desired trip point weight (or the value of the weight scaled by the same percentage used in step 6). Press the button to select a digit (blinks when selected) and press the button to set the value.
• Press the menu button once. The display indicates “On” which equals normally closed. Press the button if you want to change it to “Off”, normally open.
Press the menu button twice to save the settings.
Controller Parameters
• If the load weigher is used for dispatching options, e.g., light load anti-nuisance, dispatch load (lobby door dwell cancel), heavy load (hall call bypass) or overload options, the controller needs to learn the empty and full load weights at every landing available to this car.
• If the load weigher will be used to implement dispatching options, the parameters associated with these options must be set. Please refer to the Adjusting the Load Thresholds section of this manual
3-30 Manual # 42-02-2P25
Motion 4000
Load Weigher
Auto-zero Calibration
The EMCO load weigher has an auto-zero calibration option which can be used if needed. Typically this option is recommended for 2 to 1 roping or where guide shoes, rather than guide rollers, are used.
How auto-zero calibration works:
• The control unit must see no power on the Hold terminals. (Some installations use these terminals to indicate when the doors are closed but these terminals are not used with MCE controls.)
• The CAde parameter must be set to 50.
• When the control unit senses no change in weight for two minutes, it automatically performs the CEro zero load calibration (learns the empty car weight).
To enable auto-zero calibration:
1. Press the menu button until is displayed.
2. Enter the value 50. Press the button to select a digit (blinks when selected) and press the button to set the value.
3. Press the menu button twice to save the value.
Analog Weigher Additional Calibration
1. Connect the multimeter across UIO IO16 and Common. Verify that the reading is the same as the measurement at terminals 0-10v and Com on the EMCO control unit.
2. To verify the linearity of the load weigher, place weights in the car that represent the following and observe the voltage values:
• Empty car - about 0.0 volts
• 25% of overload weight - about 2.5 volts
• 50% of overload weight - about 5.0 volts
• 75% of overload - about 7.5 volts
• Full load weight - about 8 volts
• Overload weight - about 10 volts.
Verifying Empty Car Weight for Analog Weighers
We recommend verifying zero calibration:
• If the ropes are new calibration may change slightly as the ropes stretch. After the first 30 days of operation, check the empty car weight, with the car in the middle of the hoistway, using the display on the EMCO Load Weigher. If the empty car weight has changed (no longer zero), the empty car weight must be re-learned.
• If the car experiences violent motion (emergency stop, buffer contact, etc.), verify zero calibration as described above.
3
3-31
Final Adjustments
Troubleshooting
1. Check for error codes on the display.
= Bad load cell connection or damaged load cell. Verify load cells are connected to the control unit per the wiring diagram. Inspect cables for cuts or broken wires.
= Negative load cell flow. Verify load cell connections to the control unit are per the wiring diagram.
= Positive load cell flow. Load cells are too small for the application and must be replaced with proper units.
= Polarity error. Verify load cell connections to the control unit are per the wiring diagram. Reprogram the control.
= MB-D display short. Locate the short. Disconnect MB-D display, turn off the control, then reconnect the MB-D display.
= Loss of data in memory. Reprogram the control.
2. Verify that proper voltage is being supplied to the control unit.
3. Check all connections to the control unit.
4. Check the fuse: Disconnect power to the control unit. Open the unit by removing the five
(5) screws that hold the cover. Remove fuse from black fuse holder next to controller transformer and replace with new fuse if necessary.
3-32 Manual # 42-02-2P25
Motion 4000
Final Tests
Final Tests
The following tests may be performed in the process of elevator acceptance testing.
• Safety String Test,
Safety String Test on page 3-36
• Motor/Brake Contactor Proofing Tests, Motor Contactor Proofing Test on page 3-36
• Directional Limits Test,
Directional Limits Test on page 3-37
• Final Limits Test,
Final Limit Tests on page 3-38
• Car and Counterweight Buffer Tests, Car/Counterweight Buffer Tests on page 3-39
• Rope Slip/Traction Loss Test, Traction Loss Detection (Slip) on page 3-40
• Inspection Overspeed Test,
Inspection Overspeed Test on page 3-40
• Contract Overspeed Test,
Contract Overspeed Test on page 3-40
• Leveling Overspeed Test, Leveling Overspeed Test on page 3-40
• Inner Door Zone Test, Inner Door Zone Test on page 3-41
• Normal and Emergency Terminal Switch Overspeed Tests,
Normal and Emergency Terminal Switch Tests on page 3-42
• Electrical Governor Test, Electrical Governor Test on page 3-43
• Car/Counterweight Safety Test, Safety Tests on page 3-44
• Emergency Brake Test - Unintended Motion,
Emergency Brake Test - Unintended Motion,
Rope Brake on page 3-45
• Emergency Power tests,
Emergency or Standby Power Operation on page 3-53
3
Caution
In this document, overspeed tests ask you to scale a run speed by 110% in order to exceed the respective overspeed for that setting. This is almost always adequate. However, if the speed required for the test exceeds 110% of contract speed, you will need to increase the scaling percentage, F7-141, to compensate. Otherwise, the overspeed will not be detected which, in some tests, may result in a car or counterweight unintentionally hitting a buffer or overhead.
Always have a technician standing by to shut down the elevator if necessary.
Often Used Procedures
Following are some procedures and techniques that are often used while performing acceptance testing:
How to check Car Speed:
1. Place Function Switch F3 on the HC-MPU board in the ON (up) position.
2. Press the N push button until CONTROLLER SYSTEM MENU is displayed.
3. Press the S push button to select the menu.
4. Press the N push button until POSTN and SPEED are displayed.
5. Run the car. Speed is displayed in feet per minute.
3-33
Final Adjustments
How to place the car on Inspection Mode Fault Bypass:
1. On the HC-MPU board, place Function Switch F3 in the ON (up) position.
2. On the HC-CTL-2 board, use a jumper to short the pins of JP2 Fault Bypass.
3. Press the N push button until CONTROLLER SYSTEM MENU is displayed.
4. Press the S push button to select the menu.
5. Press the N push button until INSPECTION MODE FAULT BYPASS is scrolled on the display.
6. Press the S push button to change the setting to BYPASS ON.
How to place the car on Automatic Mode Fault Bypass:
1. On the HC-MPU board, place Function Switch F3 in the ON (up) position.
2. On the HC-CTL-2 board, use a jumper to short the pins of JP2 Fault Bypass.
3. Press the N push button until CONTROLLER SYSTEM MENU is displayed.
4. Press the S push button to select the menu.
5. Press the N push button until AUTOMATIC MODE FAULT BYPASS is scrolled on the display.
6. Press the S push button to change the setting to BYPASS ON.
How to access/set the F7 parameters:
Important F7 parameters are protected by positioning a jumper on the HC-CTL-2 board:
F7 SETTABLE
1. Place the car on Inspection operation. Set the F7 function switch to the up position.
2. Press N until the LCD displays PARAMETER ADJUST MENU. Press S to select. The
LCD will display ADJUST FROM N=LAST / S=START.
• Press N to begin adjustment from the last viewed or edited parameter.
• Press S to begin adjustment starting with the first F7 parameter.
3. Once viewing parameters:
• Press N to move through the parameters listings.
• Press + or - to change a displayed parameters value.
• To move back to a previous parameter, press and hold N (Next) then press - (minus) as needed
4. Press S to save changed parameters.
Note
A table of F7 values is included in this section, F7 Parameters on page 3-47
.
3-34 Manual # 42-02-2P25
Motion 4000
Final Tests
How to Reset Excessive Faults
Many of the faults generated while performing acceptance tests are self-resetting once the fault condition is corrected. However, this controller has excessive faults logic which will generate an
EXCESSIVE FAULTS SHUTDOWN if more than the established limit of faults occur within the circumscribed period of time. To reset this fault:
• Press the Fault Reset button on the HC-CTL-2 board.
Note
You can review speed and position information through an F5-accessed menu for assistance in seeing what is actually happening in the hoistway.
Please refer to “MPI Diagnostic Menu” on page 4-69 .
3
3-35
Final Adjustments
Safety String Test
This test verifies the Safety String is working correctly.
SAFH Safety String Test
1. Remove the wire from PMT terminal 15 or activate any safety device in the string.
2. A safety message will scroll on the MPU display.
3. Verify that the Safety Relay has dropped out and that the car cannot be run.
4. Reinstall the wires.
SAFC Safety String Test
1. On the CTL board, remove all wires from the SAFC input or activate any safety device in the string.
2. The message CAR SAFETY DEVICE OPEN should scroll on the MPU board display.
3. Verify that the Safety Relay has dropped out and that the car cannot be run.
4. Reinstall the wires.
Motor Contactor Proofing Test
This test simulates a stuck motor contactor. The test should be performed with the car stopped and with the car in motion. Once the fault is generated, the car should not be allowed to move until the contactor is unstuck.
Car Stopped at Floor
This test is performed with the car stopped at a floor.
1. Use a non-metallic object to activate the PM contactor.
2. Observe that the car will not run. MPU displays “PMP input failed to activate”.
Car in Motion
The car is in motion when this test is performed.
1. Place a call.
2. Once the car is in motion, use a non-metallic object to activate and hold the PM contactor “on”.
3. After the car stops at the designated floor, verify that it will not continue to run.
3-36 Manual # 42-02-2P25
Motion 4000
Final Tests
Brake Contactor Proofing Test
This test simulates a stuck brake contactor. The test should be performed with the car stopped and with the car in motion. Once the fault is generated the car should not be allowed to move until the contactor is unstuck.
Car Stopped at Floor
This test is performed with the car stopped at a floor.
1. Use a non-metallic object to activate the BR contactor.
2. Verify that the car will not run. MPU displays “BRP input failed to activate.”
Car in Motion
The car is in motion when this test is performed.
1. Place a call.
2. Once the car is in motion, use a non-metallic object to activate and hold the BR contactor “on.”
3. After the car stops at the designated floor, verify that the car will not continue to run. (A
UIM, unintended motion fault, may occur if the car drifts far enough.
Directional Limits Test
These tests verify proper operation of elevator up and down direction limits.
1. On the MPU board, verify that F7 parameter #68 Direction Limit Distance is set to the desired distance.
2. Verify that the F3 > Controller System Menu > Inspection Mode Fault Bypass parameter is set to BYPASS OFF.
Down Direction Limit Test
1. On Inspection, run the car to the floor above the bottom landing.
2. On Inspection, run the car down below the bottom landing until the car stops.
3. Verify that the Final Limit has not opened and that the car has stopped at approximately the distance set in F7 parameter # 68 Direction Limit Distance.
Up Direction Limit Test
1. On Inspection, run the car to the floor below the top landing.
2. On Inspection, run the car up past the top landing until the car stops.
3. Verify that the Final Limit has not opened and that the car has stopped at approximately the distance set in F7 parameter # 68 Direction Limit Distance.
3
3-37
Final Adjustments
Final Limit Tests
1. Place the car on Inspection.
2. On the MPU board, set F3 > Controller System Menu > INSPECTION MODE FAULT
BYPASS = BYPASS ON. The MPU display will scroll FAULT BYPASS IS ACTIVE
(INSPECTION).
Lower Final Limit Test
1. Place the car one floor above the bottom landing.
2. Run the car down on Inspection until it stops. The MPU display will scroll the message
HOISTWAY SAFETY DEVICE OPEN.
3. On the HC-CTL-2 board, place a jumper between 2 bus and the SAFH input terminal.
4. Run the car up on Inspection.
5. Remove the jumper between 2 bus and the SAFH input terminal on the HC-CTL-2 board.
Upper Final Limit Test
1. Place the car one floor below the top landing.
2. Run the car up on Inspection until it stops. The MPU display will scroll the message
HOISTWAY SAFETY DEVICE OPEN.
3. On the HC-CTL-2 board, place a jumper between 2 bus and the SAFH input terminal.
4. Run the car down on Inspection.
5. Remove the jumper between 2 bus and the SAFH input terminal on the HC-CTL-2 board.
6. Set F3 > Controller System Menu > INSPECTION MODE FAULT BYPASS = BYPASS
OFF.
3-38 Manual # 42-02-2P25
Motion 4000
Final Tests
Car/Counterweight Buffer Tests
Buffer tests verify that the car or counterweight striking the buffer will cause the machine to break traction and that the buffer will return to its fully extended state after having been fully compressed. Following the car buffer test, the counterweight buffer test is executed with an empty car running up.
Note
These test instructions are written with the expectation that the car or counterweight will be traveling at contract speed when it strikes the buffer. If any other speed is required, the test method must be modified appropriately.
(Car) Buffer Test
1. Place a full load in the car.
2. Run the car to the top landing
3. Place the car on Machine Room Inspection.
4. On the MPU board, set F3 > Controller System Menu > INSPECTION MODE FAULT
BYPASS, PLD INSPECTION OVERSPEED BYPASS, and PLD ETS OVERSPEED
BYPASS to ON. Return F3 to the down position.
5. Place a jumper between the 2 Bus and SAFH.
6. Set High Speed (F7, 150) to Contract Speed value for full stroke buffers or rated buffer speed for reduced stroke buffers.
7. Place function switch F5 in the UP position and press N until the TERMINAL LIMIT/
UTILITIES menu is displayed. Press S to select.
8. Press N until PERFORM TERMINAL TESTS is displayed. Press S to select. TERMINAL
TEST RUN/QUIT will be displayed. Press S to start the test.
9. With TERMINAL TEST ARM/QUIT displayed, press S. The LCD will display TERMI-
NAL TEST - READY TO MOVE.
10. Display car speed – F3 > Controller System Menu > POSTN/SPEED.
11. Run the car down using the Machine Room Inspection switches. (If you are in the F5 menu, you will see TERMINAL TEST IN PROGRESS.)
• Release the switches when the car contacts the buffer and the ropes lose traction.
• Car must strike buffer, compress it fully, and cause hoist motor to break traction.
• Check hoistway ropes are still in their grooves before attempting to move car again.
• If the motor rotates more than about one meter after breaking traction, the traction loss fault MPI-C LANDING SYS A/B POSITION DEVIATION will appear. Press Fault
Reset button to clear this fault.
12. If you are in the F5 menu, it will display TERMINAL TEST DONE, PRESS S. Press S.
13. Exit the F5 menu (if used). Return F7 parameters to their original settings (if used).
14. Remove 2 Bus/SAFH jumper. Set INSPECTION MODE FAULT BYPASS, PLD INSPEC-
TION OVERSPEED BYPASS, and PLD ETS OVERSPEED BYPASS to OFF.
3
3-39
Final Adjustments
Traction Loss Detection (Slip)
Perform the car or counterweight buffer test per the instructions provided above. Observe that when the hoist motor breaks traction for about one meter, power is removed from the driving machine motor and brake within 10 seconds, and the car will not restart. To restore normal operation, verify you are in Inspection operation then press the Fault Reset button.
Inspection Overspeed Test
This test verifies that moving the elevator on Inspection at a speed greater than the Inspection
Overspeed setting will result in an emergency stop.
1. Change F7 parameters to:
• 141 PROFILE SCALE = 115% of INSPECTION OVERSPEED
• 187 REDUCED INSPECT SPEED = OFF
• 146 INSPECTION OVERSPEED = 125 FPM
2. Run the car up or down on Inspection.
3. An emergency stop will be performed when 146 INSPECTION OVERSPEED value is exceeded.
4. CTL-A, CTL-B, MPI -C INSPECTION OVERSPEED will be displayed.
5. Return F7 parameters to their original settings
Contract Overspeed Test
This test verifies that moving the elevator at a speed greater than the Contract Overspeed setting will result in an emergency stop.
1. Move the car to bottom floor on Normal operation.
2. TORQMAX only. Set drive LF.22 to a value greater than LF.25 x 1.4
3. Set F7 Parameter 141 PROFILE SCALE = 120.0%
4. Place a call to the top floor.
5. When car speed exceeds Contract Overspeed setting, it must:
• Perform an emergency stop.
• Generate message CTL-A, CTL-B, MPI-C CONTRACT OVERSPEED.
6. Return F7 and (TORQMAX only) drive parameters to their original settings.
Leveling Overspeed Test
This test verifies that the car will perform an emergency stop if, while leveling, it is traveling at a speed greater than the Leveling Overspeed setting.
1. Set parameter #158 to 2 or 3 (leveling speed). Set parameter #147 = 1 (leveling overspeed), #160 = 5 inches, F1>Door Operation Menu > Preopening = Yes.
2. Call to floor not near limits. As car is leveling: Emergency stop, display CTL-A, -B Leveling Overspeed.
3. Return parameters to original values.
3-40 Manual # 42-02-2P25
Motion 4000
Final Tests
Inner Door Zone Test
This test verifies that the car will not move if it stops outside the inner landing zone (75 mm/3.0 inches above and below the level position) if its doors are open.
1. With the car level at a landing, note, then modify F7, parameter 160, leveling distance to
5 inches.
2. Locate the GS input on the HC-CTL-2 board. Slightly loosen the wire so that it may be pulled free quickly during testing.
3. Locate HC-CTL-2 board indicator LEDs DZF and DZR (across the top of the board, toward the left, near the Fault Reset button). These are important indicators for the test.
4. With HC-MPU board F7 and all other function switches down, change the address on the HC-MPU diagnostic display to address 29.
• Note data bit numbers 7 and 3 (underlined in the graphic and shown in the ON (1) states for reference only).
• Bit 7 is active (1) only when the Level
Down input is active.
• Bit 3 is active (1) only when the Level Up input is active.
5. On automatic operation, register a call to an adjacent landing.
6. Observe bits 3 and 7. As the elevator approaches the landing and either bit 3 or 7 activates, but before either HC-CTL-2 board LED indicator DZF or DZR activates, pull the wire from HC-CTL-2 input GS.
7. The elevator will perform an immediate stop. With the wire still pulled, verify that the elevator will not move. (Indicator DZF or DZR must remain unlighted.)
8. Replace and secure the wire in terminal GS. The elevator will level into the landing.
Restore F7, parameter 160 to its original setting.
3
3-41
Final Adjustments
Normal and Emergency Terminal Switch Tests
Obtain a list of learned speeds at all ETS and NTS switches used. At contract speeds below 400
FPM, verify F7 parameters:
• #70 NTS1 = VIRTUAL
• #69 U/DETS = VIRTUAL
Contract Speed
• #74 NTS5 = UNUSED
• #73 NTS4 = UNUSED
• #72 NTS3 = UNUSED
• #71 NTS2 = UNUSED
(VIRTUAL if 400 FPM contract speed)
Graph is an example of 400 FPM installation (2 NTS switches) xNTSn Speed + xNTSn Delta High Speed xNTSn Speed + xNTSn Delta LowSpeed xNTSn Speed xETS Speed + xETS Delta Speed xETS Speed xNTSn Speed + xNTSn Delta High Speed xNTSn Speed + xNTSn Delta LowSpeed xNTSn Speed
Terminal Floor
• xNTSn SPEED = Speed value of switch
Distance xNTSn Distance
• xNTSn DISTANCE - Switch to terminal distance
• xNTSn DELTA DISTANCE - Margin of error allowed to not see switch
• xNTSn DELTA LOW SPEED - Positive offset from xNTSn SPEED value for DELTA LOW
SPEED FAULTS
• xNTSn DELTA HIGH SPEED - Positive offset from xNTSn SPEED value for DELTA HIGH
OVERSPEED FAULTS
Outer NTS Delta High Speed Test
1. Set Delta Low Speed of outer UNTS switch to 60 FPM to move it “out of the way”. Move car away from top landing far enough to reach contract speed. Put in TEST MODE.
2. Set HC-MPU switch F5 UP. Press N until Terminal Limit Utilities appears. Press S.
Press N until Perform Terminal Tests appears. Press S.
3. With TERMINAL TEST/CMD: DN [N]-QUIT displayed, press S to display Terminal
Test [S]-Run [N]-Quit. Press S to display Terminal Test/Cmd: DN [N]- displayed, use +/
- buttons to select UP. Press S.
4. GOING TO TOP will be displayed. Set F5 down while traveling. When the car performs an uncontrolled emergency stop, it will display UNT SW HIGH OVERSPEED.
5. Set F5 up. Press + and N buttons to exit terminal tests. Return Delta Low Speed to original setting.
6. Repeat test for down direction outer DNTS switch.
Outer NTS Delta Low Speed Test
1. Set Delta High Speed for outer UNTS switch to 60 FPM to move it “out of the way”.
Move the car away from the top landing far enough to reach contract speed. Put in TEST
MODE.
2. Set HC-MPU switch F5 UP. Press N until Terminal Limit Utilities appears. Press S.
Press N until Perform Terminal Tests appears. Press S.
3. With TERMINAL TEST/CMD: DN [N]-QUIT displayed, press S to display Terminal
Test [S]-Run [N]-Quit. Press S to display Terminal Test/Cmd: DN [N]- displayed, use +/
- buttons to select UP. Press S.
4. GOING TO TOP will be displayed. Set F5 down while traveling. When the car performs a controlled emergency slowdown, it will display UNT SW LOW OVERSPEED.
5. Set F5 up. Press + and N buttons to exit terminal tests. Return Delta High Speed to original setting.
6. Repeat test for down direction outer DNTS switch.
3-42 Manual # 42-02-2P25
Motion 4000
Final Tests
Continued NTS/ETS Testing
If more than one set of virtual terminal switches are used, outer NTS and ETS switches can be prevented from tripping by setting them to unused. Then, for the switch to be tested, perform high and low overspeed tests as previously described. Note that D/UNTS1 switches should never to set to unused.
ETS Testing
If only one set of NTS switches (NTS1) is used, ETS switches will be closest to the terminal landings.
1. NTS1 switches may not be set to unused, so set NTS1 switch speeds to contract speed to
“move them out of the way” for ETS testing.
2. Complete ETS testing just as Delta High Speed for NTS switches. Once an overspeed occurs, the LCD will display UET SW OVERSPEED for top or DET SW OVERSPEED for bottom.
3. When overspeed occurs, the car will level into a floor and the latched fault ETS FAULT
SHUTDOWN will appear. This fault must be reset using the Fault Reset button.
4. Be sure to return NTS1 switch speeds to their correct values when ETS testing is completed.
Electrical Governor Test
Verifies correct calibration of the electrical governor switch (typically about 110% of contract speed); proves the car will execute an emergency stop when the switch is activated. Car must run fast enough to trip the electrical governor switch, but not so fast as to trip the mechanical governor.
1. Verify no jumper between GOS1/GOS2.
2. Run the car to the top landing.
3. Set F3 > Controller System Menu > AUTOMATIC MODE FAULT BYPASS = BYPASS
ON.
4. TORQMAX Only: Set LF.22 Gear Ratio to LF.25 x 2.
5. Set F7 Parameter 141 PROFILE SCALE to a value above electrical governor trip speed but less than mechanical trip speed (mechanical trip speed typically about 115% of Contract Speed).
6. Place a call to the bottom landing.
7. The car should accelerate and then perform an emergency stop
8. Place the car on Inspection.
9. Reset the electrical governor.
10. To reset the emergency brake: TC-MPI board, press/hold EB RST for 8 seconds.
11. Set F3 > Controller System Menu > AUTOMATIC MODE FAULT BYPASS = BYPASS
OFF.
12. Return F7, 141, and (TORQMAX) drive parameters to their original settings.
3
3-43
Final Adjustments
Ascending Car Overspeed Test
The mechanic must determine appropriate weight, if any, to be placed in the car for this test.
1. Bring the empty car to the bottom floor with car and hoistway doors closed and locked.
2. Observe car speed at F3 POSTN SPEED and stand by to engage brake if governor overspeed switch fails to open.
3. Use your preferred method to mechanically release the machine brake. The car will start to move up the hoistway.
4. When the governor overspeed switch opens, the emergency brake will engage, stop, and hold the car.
5. Reset the emergency brake: thereby releasing the emergency brake.
Safety Tests
This is a two part test. Car safety testing verifies proper operation of car safeties. The objective is to set the safeties causing the machine to break traction. The overspeed must be sufficient to cause the governor to trip mechanically and set the car safeties. The electrical governor switch must not prevent the car from reaching the mechanical trip speed and the safety operated switch (plank switch) must not open the safety string.
Car Safety Test
1. Run the car to the top landing.
2. Set F3 > Controller System Menu > AUTOMATIC MODE FAULT BYPASS = BYPASS
ON.
3. TORQMAX Only: Set LF.22 Gear Ratio to LF.25 x 2.
4. Set F7 Parameter 141 PROFILE SCALE to 115% (mechanical tripping speed is typically about 115% of Contract Speed).
5. Bypass the Electrical Governor Switch by placing a jumper from GOS1 to GOS2.
6. Place a call to the bottom landing.
7. As the car over speeds:
• The governor will trip
• Safeties will set
• The machine will break traction
• Car will stop
8. Place on Inspection. Reset the governor.
9. Return F7 controller parameters (and TORQMAX drive) to their original values.
10. If necessary (unintended motion fault occurred), verify that the car is on Inspection operation, then on the TC-MPI board, press and hold the EB RST button for 8 seconds.
11. Set F3 > Controller System Menu > AUTOMATIC MODE FAULT BYPASS = BYPASS
OFF.
12. Remove the jumper between GOS1 and GOS2.
13. On the HC-CTL-2 board, place a jumper between terminals SAFC and SAFH.
14. Run the car up on Inspection to release the safeties.
15. Remove the jumper between the CTL board terminals SAFC and SAFH.
3-44 Manual # 42-02-2P25
Motion 4000
Final Tests
Counterweight Safety Test
The counterweight safety test verifies the operation of the counterweight safeties. The test is comparable to the car safety test but performed in the opposite direction. If the counterweight has a governor, remember to jumper it out.
1. Run the car to the bottom landing.
2. Set F3 > Controller System Menu > AUTOMATIC MODE FAULT BYPASS = BYPASS
ON.
3. TORQMAX only. Set LF.22 Gear Ratio to LF.25 x 2.
4. Set F7 Parameter 141 PROFILE SCALE to 115% (mechanical tripping speed is typically about 115% of Contract Speed).
5. Bypass the Electrical Governor Switch by placing a jumper between GOS1 and GOS2.
6. Place a call to the top landing.
7. As the counterweight over speeds
• The governor will trip
• Safeties will set
• The machine will break traction
• Car will stop
8. Place the car on Inspection. Reset the governor.
9. TORQMAX only. Return drive parameters to their original values.
10. Return F7 controller parameters to their original values.
11. If an unintended motion fault was triggered, on the TC-MPI board, press and hold the
EB RST button for 8 seconds.
12. Set F3 > Controller System Menu > AUTOMATIC MODE FAULT BYPASS = BYPASS
OFF.
13. Remove the jumper between GOS1 and GOS2.
14. On the HC-CTL-2 board, place a jumper between terminals SAFC and SAFH.
15. Run the car down on Inspection to release the counterweight safeties.
16. Remove the jumper between the CTL board terminals SAFC and SAFH.
Emergency Brake Test - Unintended Motion, Rope Brake
This test verifies that moving the car away from a landing with both the car and Hoistway doors open (termed “Unintended motion” will cause the Emergency Brake (Rope Gripper) to be deployed and that such deployment will stop the elevator. This test demonstrates that the emergency brake will stop the car within 48” from floor level if the car drifts from the floor.
Discrete Brakes - No Brake Module
1. For safety, station a mechanic at the landing where the test is to be performed.
2. Bring the car to the landing away from the terminals and place on Independent service.
3. Load the car as required (100% or 125% of load). Place barricades to prevent entry.
4. Use a non-metallic object to press and hold contactors, BR and BRX (to allow the car to drift from the floor).
5. As the car moves away from the floor, observe that the emergency brake stops and holds the car within 48 inches (122 cm) of floor level.
3-45
3
Final Adjustments
6. To restore normal operation, verify doors are closed, place car on Inspection and press the EB RESET button on the TC-MPI board for a minimum of 8 seconds until the emergency brake resets.
When testing is complete, make sure that all appropriate data has been properly documented.
System with Brake Module
1. For safety, station a mechanic at the landing where the test is to be performed.
2. Bring the car to a landing away from the terminals and place on Independent service.
This will open the doors.
3. Load the car as required (100% or 125% of load). Place barricades to prevent entry.
4. Place the M-Brake Module on Manual mode by moving both dip switches 1 and 2 of switch SW1 into the OFF position.
5. Press and hold both “Brake Test 1" and “Brake Test 2" buttons to pick the brake. Manual brake pick voltage can be adjusted through trim pot R67.
6. As the car moves away from the floor, observe that the emergency brake stops and holds the car within 48 inches (122 cm) of floor level.
7. Return one or both of the switches on M-Brake module switch SW1 to the ON position.
8. Verify doors are closed, place car on Inspection and press the EB RESET button on the
TC-MPI board for a minimum of 8 seconds until the emergency brake resets.
Verify all appropriate data has been properly recorded.
Figure 3.4 Component Locations
BRAKE TEST 1 BRAKE TEST 2
BRAKE MODULE
Dip Switch SW1
3-46 Manual # 42-02-2P25
Motion 4000
Table 3.4 F7 Parameters
28
29
30
31
24
25
26
27
20
21
22
23
16
17
18
19
12
13
14
15
8
9
10
11
4
5
6
7
1
2
3
44
45
46
47
40
41
42
43
48
49
36
37
38
39
32
33
34
35
# Item
Floor 16
Floor 17
Floor 18
Floor 19
Floor 20
Floor 21
Floor 22
Floor 23
Floor 24
Floor 25
Floor 26
Floor 27
Floor 28
Floor 29
Floor 30
Floor 31
Floor 1
Floor 2
Floor 3
Floor 4
Floor 5
Floor 6
Floor 7
Floor 8
Floor 9
Floor 10
Floor 11
Floor 12
Floor 13
Floor 14
Floor 15
Floor 32
Floor 33
Floor 34
Floor 35
Floor 36
Floor 37
Floor 38
Floor 39
Floor 40
Floor 41
Floor 42
Floor 43
Floor 44
Floor 45
Floor 46
Floor 47
Floor 48
Floor 49
Min
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
Default Max
0.0 in
+120.0 in
+240.0 in
+360.0 in
+480.0 in
+600.0 in
+720.0 in
+12000.0 in
+12000.0 in
+12000.0 in
+12000.0 in
+12000.0 in
+12000.0 in
+12000.0 in
+840.0 in
+960.0 in
+12000.0 in
+12000.0 in
+1080.0 in +12000.0 in
+1200.0 in +12000.0 in
+1320.0 in +12000.0 in
+1440.0 in +12000.0 in
+1560.0 in +12000.0 in
+1680.0 in +12000.0 in
+1800.0 in +12000.0 in
+1920.0 in +12000.0 in
+2040.0 in +12000.0 in
+2160.0 in +12000.0 in
+2280.0 in +12000.0 in
+2400.0 in +12000.0 in
+2520.0 in +12000.0 in
+2640.0 in +12000.0 in
+2760.0 in +12000.0 in
+2880.0 in +12000.0 in
+3000.0 in +12000.0 in
+3120.0 in +12000.0 in
+3240.0 in +12000.0 in
+3360.0 in +12000.0 in
+3480.0 in +12000.0 in
+3600.0 in +12000.0 in
+3720.0 in +12000.0 in
+3840.0 in +12000.0 in
+3960.0 in +12000.0 in
+4080.0 in +12000.0 in
+4200.0 in +12000.0 in
+4320.0 in +12000.0 in
+4440.0 in +12000.0 in
+4560.0 in +12000.0 in
+4680.0 in +12000.0 in
+4800.0 in +12000.0 in
+4920.0 in +12000.0 in
+5040.0 in +12000.0 in
+5160.0 in +12000.0 in
+5280.0 in +12000.0 in
+5400.0 in +12000.0 in
+5520.0 in +12000.0 in
+5640.0 in +12000.0 in
+5760.0 in +12000.0 in
Final Tests
Notes
3
3-47
Final Adjustments
79
80
81
82
83
75
76
77
78
69
70
71
72
73
74
84
85
86
87
88
89
90
91
65
66
67
68
Table 3.4 F7 Parameters
61
62
63
64
57
58
59
60
50
51
52
53
54
55
56
#
Floor 50
Floor 51
Floor 52
Floor 53
Floor 54
Floor 55
Floor 56
Floor 57
Floor 58
Floor 59
Floor 60
Floor 61
Floor 62
Floor 63
Floor 64
Item Min
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
Bottom access distance 0.0 in
Top access distance 0.0 in
Counterweight position 0.0 in
Directional limit distance
0.0 in
U/DETS
U/DNT1
U/DNT2
U/DNT3
U/DNTS
U/DNT5
UETS speed
UETS distance
UETS delta distance
UETS delta speed
0 fpm
-1200.0 in
-120.0 in
0 fpm
UNTS1 speed
UNTS1 distance
0 fpm
-1200.0 in
UNTS1 delta distance -120.0 in
UNTS1 delta low speed 0 fpm
UNTS1 delta high speed 0 fpm
UNTS2 speed
UNTS2 distance
0 fpm
-1200.0 in
UNTS2 delta distance -120.0 in
UNTS2 delta low speed 0 fpm
UNTS2 delta high speed 0 fpm
UNTS3 speed
UNTS3 distance
0 fpm
-1200.0 in
UNTS3 delta distance -120.0 in
Default Max
+5880.0 in +12000.0 in
+6000.0 in +12000.0 in
+6120.0 in +12000.0 in
+6240.0 in +12000.0 in
+6360.0 in +12000.0 in
+6480.0 in +12000.0 in
+6600.0 in +12000.0 in
+6600.0 in +12000.0 in
+6720.0 in +12000.0 in
+6840.0 in +12000.0 in
+6960.0 in +12000.0 in
+7080.0 in +12000.0 in
+7200.0 in +12000.0 in
+7320.0 in +12000.0 in
+7440.0 in +12000.0 in
+120.0 in
+120.0 in
+540.0 in
+2.0 in
+12000.0 in
+12000.0 in
+12000.0 in
+1200.0 in
VIRTUAL
VIRTUAL
UNUSED
UNUSED
UNUSED
UNUSED
+332 fpm
+48.0 in
+6.0 in
20 fpm
0 fpm
+104.5 in
+6.0 in
10 fpm
20 fpm
0 fpm
0.0 in
+6.0 in
10 fpm
20 fpm
0 fpm
0.0 in
+6.0 in
+900 fpm
+1200.0 in
+120.0 in
+900 fpm
+900 fpm
+1200.0 in
+120.0 in
+900 fpm
+900 fpm
+900 fpm
+1200.0 in
+120.0 in
+900 fpm
+900 fpm
+900 fpm
+1200.0 in
+120.0 in
Notes
UNUSED, VIRTUAL, PHYSICAL
UNUSED, VIRTUAL, PHYSICAL
UNUSED, VIRTUAL, PHYSICAL
UNUSED, VIRTUAL, PHYSICAL
UNUSED, VIRTUAL, PHYSICAL
UNUSED, VIRTUAL, PHYSICAL
3-48 Manual # 42-02-2P25
Motion 4000
94
95
96
97
98
Table 3.4 F7 Parameters
92
93
# Item Min
UNTS3 delta low speed 0 fpm
UNTS3 delta high speed 0 fpm
UNTS4 speed
UNTS4 distance
0 fpm
-1200.0 in
UNTS4 delta distance -120.0 in
UNTS4 delta low speed 0 fpm
UNTS4 delta high speed 0 fpm
99 UNTS5 speed
100 UNTS5 distance
0 fpm
-1200.0 in
101 UNTS5 delta distance -120.0 in
102 UNTS5 delta low speed 0 fpm
103 UNTS5 delta high speed 0 fpm
104 DETS speed
105 DETS distance
106 DETS delta distance
107 DETS delta speed
0 fpm
-1200.0 in
-120.0 in
0 fpm
108 DNTS1 speed 0 fpm
109 DNTS1 distance -1200.0 in
110 DNTS1 delta distance -120.0 in
111 DNTS1 delta low speed 0 fpm
112 DNTS1 delta high speed 0 fpm
113 DNTS2 speed
114 DNTS2 distance
0 fpm
-1200.0 in
115 DNTS2 delta distance -120.0 in
116 DNTS2 delta low speed 0 fpm
117 DNTS2 delta high speed 0 fpm
118 DNTS3 speed 0 fpm
119 DNTS3 distance -1200.0 in
120 DNTS3 delta distance -120.0 in
121 DNTS3 delta low speed 0 fpm
122 DNTS3 delta high speed 0 fpm
123 DNTS4 speed
124 DNTS4 distance
0 fpm
-1200.0 in
125 DNTS4 delta distance -120.0 in
126 DNTS4 delta low speed 0 fpm
127 DNTS4 delta high speed 0 fpm
128 DNTS5 speed 0 fpm
129 DNTS5 distance -1200.0 in
130 DNTS5 delta distance -120.0 in
131 DNTS5 delta low speed 0 fpm
132 DNTS5 delta high speed 0 fpm
Max
+900 fpm
+900 fpm
+900 fpm
+1200.0 in
+120.0 in
+900 fpm
+900 fpm
+900 fpm
+1200.0 in
+120.0 in
+900 fpm
+900 fpm
+900 fpm
+1200.0 in
+120.0 in
+900 fpm
+900 fpm
+1200.0 in
+120.0 in
+900 fpm
+900 fpm
+900 fpm
+1200.0 in
+120.0 in
+900 fpm
+900 fpm
+900 fpm
+1200.0 in
+120.0 in
+900 fpm
+900 fpm
+900 fpm
+1200.0 in
+120.0 in
+900 fpm
+900 fpm
+900 fpm
+1200.0 in
+120.0 in
+900 fpm
+900 fpm
Default
10 fpm
20 fpm
0 fpm
0.0 in
+6.0 in
10 fpm
20 fpm
0 fpm
0.0 in
+6.0 in
10 fpm
20 fpm
+332 fpm
+48.0 in
+6.0 in
20 fpm
0 fpm
+104.5 in
+6.0 in
0 fpm
0 fpm
0 fpm
0.0 in
+6.0 in
10 fpm
20 fpm
0 fpm
0.0 in
+6.0 in
10 fpm
20 fpm
0 fpm
0.0 in
+6.0 in
10 fpm
20 fpm
0 fpm
0.0 in
+6.0 in
10 fpm
20 fpm
Final Tests
Notes
3
3-49
Final Adjustments
Table 3.4 F7 Parameters
# Item Min Default Max Notes
133 Brake pick delay
134 Speed pick delay
135 Brake hold delay
136 Brake drop delay
0 ms
0 ms
0 ms
0 ms
138 Drive disable delay 0 ms
139 Speed hysteresis delay 0 ms
140
141
142
143
144
145 Contract over-speed
146 Inspection over-speed 0 fpm
147
Profile advance
Profile scale
Standard slew slope
Danger slew slope
Slew filter
Leveling over-speed
0 ms
0%
0.00 ft/s2
0.00 ft/s2
+0.1 Hz
0 fpm
0 fpm
148 Hoist-motor speed
149 Contract speed
150 High speed
151 Intermediate speed
152 Earthquake speed
153 Auxiliary speed
154 Backup power speed
155
Inspection speed
(normal)
156
Inspection speed
(reduced)
157 Correction speed
158 Leveling speed
159 Re-leveling speed
160 Leveling distance
161 Re-leveling distance
162 Proximity distance
163
Leveling dead zone distance
0.0 in
0.0 in
0.0 in
0.0 in
+1.0 rpm
+25 fpm
+25 fpm
+25 fpm
+25 fpm
+25 fpm
+25 fpm
0 fpm
0 fpm
0 fpm
0 fpm
0 fpm
0 ms
+500 ms
+2000 ms
+500 ms
+1250 ms
+1000 ms
+10000 ms
+10000 ms
+10000 ms
+2000 ms
+2000 ms
+10000 ms
+100 ms
100%
+1000 ms
+1000%
+0.5 ft/s2 +50.00 ft/s2
+10.00 ft/s2 +50.00 ft/s2
+20.0 Hz +20 Hz
+375 fpm
+125 fpm
+125 fpm
+1000 fpm
+148 fpm
148 fpm
+1165.0 rpm
+350 fpm
+350 fpm
+300 fpm
+150 fpm
+250 fpm
+200 fpm
+50 fpm
+25 fpm
+75 fpm
+4 fpm
+6 fpm
+1.0 in
+1.0 in
+18.0 in
+0.5 in
+9999.9 rpm
+800 fpm
+800 fpm
+800 fpm
+150 fpm
+800 fpm
+800 fpm
+148 fpm
SPI1 terminal (TC-MPI board)
SPI2 terminal (TC-MPI board)
+148 fpm
+250 fpm
+25 fpm
+25 fpm
+9.0 in
+9.0 in
+120.0 in
+3.0 in
165 Standard start jerk
166 Standard roll jerk
+0.10 ft/s3 +4.00 ft/s3 +15.00 ft/s3
+0.10 ft/s3 +4.00 ft/s3 +15.00 ft/s3
167 Standard stop jerk +0.10 ft/s3 +2.00 ft/s3 +15.00 ft/s3
168 Standard acceleration 0.00 ft/s2 +2.00 ft/s2 +10.0 ft/s2
169 Standard deceleration 0.00 ft/s2 +2.00 ft/s2 +10.0 ft/s2
170 Manual start jerk
171 Manual roll jerk
+0.10 ft/s3 +1.00 ft/s3 +15.00 ft/s3
+0.10 ft/s3 +1.00 ft/s3 +15.00 ft/s3
3-50 Manual # 42-02-2P25
Motion 4000
Table 3.4 F7 Parameters
# Item
172 Manual stop jerk
173 Manual acceleration
174 Manual deceleration
Min Default Max
+0.10 ft/s3 +1.00 ft/s3 +15.00 ft/s3
0.00 ft/s2
0.00 ft/s2
+0.50 ft/s2 +10.0 ft/s2
+0.50 ft/s2 +10.0 ft/s2
175 Danger start jerk
176 Danger roll jerk
177 Danger stop jerk
178 Danger deceleration
+0.10 ft/s3 +25.00 ft/s3 +50.00 ft/s3
+0.10 ft/s3 +25.00 ft/s3 +50.00 ft/s3
+0.10 ft/s3 +25.00 ft/s3 +50.00 ft/s3
0.00 ft/s2 6.00 ft/s2 +15.00 ft/s2
179 Alternate start jerk
180 Alternate roll jerk
+0.10 ft/s3 +2.00 ft/s3 +15.00 ft/s3
+0.10 ft/s3 +2.00 ft/s3 +15.00 ft/s3
181 Alternate stop jerk +0.10 ft/s3 +2.00 ft/s3 +15.00 ft/s3
182 Alternate acceleration 0.00 ft/s2 +1.50 ft/s2 +10.0 ft/s2
183 Alternate deceleration 0.00 ft/s2 +1.50 ft/s2 +10.0 ft/s2
184 Drive type
185 Brake type
186 Emergency brake
187 Reduced inspect speed
188 Unintended motion
189 Following error
190
Sheave Brake Idle
Delay
191 Landing System
0%
0S
192 Speed Drop Delay
193 Profile Compensation
KEB F5-
GRD50
DISCRETE
ROPE GRIP-
PER
OFF
LEVEL ZONE
+25%
30S
Elgo 160
+1000%
3600S
Final Tests
Notes
KEB F5-GRD49, KEB F5-GLS49,
KEB F5-GRD50, KEB F5-GLS50,
YASKAWA,
MAG QUATTRO,
MAG HPV, MAG DSD
DISCRETE, ONE MODULE, TWO
MODULES
DISABLED, ROPE GRIPPER,
SHEAVE BRAKE, MACHINE
BRAKE
OFF,
ETS,
NTS1, NTS2, NTS3, NTS4, NTS5
LEVEL ZONE, DOOR ZONE
Elgo-160, Elgo-240, LS-EDGE
Magnetek drives only. Time in milliseconds during which the drive should continue to exert motor control after the car has achieved the floor and before the brake has dropped.
Dynamic: Variable, controller determined compensation for drive lag based on entry in parameter 140, Profile Advance.
Fixed: Fixed compensation for drive lag using the parameter
140, Profile Advance setting.
194
195
196
Normal Brake Pick Voltage
Normal Brake Hold
Voltage
Normal Brake Relevel
Voltage
0V
0V
0V
300V
300V
300V
3-51
3
Final Adjustments
Table 3.4 F7 Parameters
# Item Min Default Max Notes
197 Normal Brake Lift Rate 0%
198
Normal Brake Drop
Rate
199 Emergency Brake Type
0%
200
201
Emergency Brake Pick
Voltage
Emergency Brake Hold
Voltage
202 Directional Limit Type
0V
0V
203
Landing System Floor
Checksum
100%
100%
300V
300V
Module or Discrete
Virtual Virtual or Physical
This is a read only value. When the hoistway is learned with the LS-EDGE landing system, the learned parameters are stored in the landing system sensor and this checksum is both stored in the sensor and sent to the controller.
If the controller should read a different checksum (i.e., if the sensor head is changed), a new hoistway learn must be performed.
204
Landing System ETS
Overspeed
0% 10% 100%
Used to set the LS-EDGE landing system hardware ETS overspeed threshold as a percentage of contract speed. Magnets on the landing system tape (one lane for UETS and another for DETS) are monitored by the LS-EDGE, detecting the speed at which the car passes. The controller still allows a virtual/physical ETS switch in addition to the magnets.
205 Inspection Slew filter +0.1 Hz
206 Battery Backup Speed 9 FPM
+20.0 Hz
250 FPM
+20 Hz
250 FPM
3-52 Manual # 42-02-2P25
Motion 4000
Final Tests
Emergency or Standby Power Operation
Two emergency power tests are described here. The first is for a car equipped with the TAPS
(Traction Auxiliary Power Supply) from MCE. The second is for a car equipped with backup generator power.
Note
When performing emergency power related testing, ensure that the mPAC hand-held programming unit, if used, is not connected.
Traction Auxiliary Power Supply Test
The MCE Traction Auxiliary Power Supply, TAPS, monitors the commercial electrical power provided to an AC traction elevator controller. If commercial power fails, the auxiliary power supply provides single phase backup power, directs the controller to move the car safely to a landing, and provides power to open the elevator doors. If the elevator controller chooses a direction that draws power beyond a customer-preset level, the system will direct the controller to pause the car, then reverse direction to the nearest landing, again providing power to open the doors and allow passengers to exit. The TAPS unit will then disconnect power to the elevator controller after a customer defined time period or when an output from the controller tells it that the cycle is complete. When commercial power is restored, TAPS will direct commercial power to the elevator controller and automatically recharge the backup batteries for future use.
Check the MCE drawings to verify that the car is properly connected to a TAPS unit. Additionally verify that the TAPS unit is properly charged and is displaying no fault conditions.
Mainline Disconnect Verification This verifies that the fourth pole of the main line disconnect or micro switch is functional when power is intentionally shut off at the main line disconnect.
1. Verify that TAPS BS1 and BS2 are connected to the fourth pole of the main line disconnect.
2. Set the AC/TAPS DISCONNECT switch to the ON position.
3. Shut off power at the main line disconnect.
4. Verify that the car is not energized and remains stopped.
TAPS and Controller Operation Verification
1. Ensure the main line disconnect is in the ON position.
2. Ensure the AC/TAPS DISCONNECT switch is in the ON position.
3. Ensure the TAPS BYPASS switch is in the NORMAL position.
4. Verify the NORMAL POWER indicator is on.
5. With empty car, move the elevator on inspection slightly above the leveling zone of the floor with the longest floor distance moving in the up direction.
6. Push and hold the test button until TAPS is in backup power mode. Verify the BACKUP
POWER indicator is on.
7. Quickly put the elevator back to normal operation.
8. The elevator should begin to move in the up direction until it reaches the floor above.
Once the elevator reaches the floor, it shall cycle the door.
3-53
3
Final Adjustments
9. If TAPS shuts down before the elevator completes the rescue operation due to the timer set in parameter F1-1 “Backup Power Run Time,” extend the timer accordingly and perform the test again.
10. If TAPS shuts down before the elevator completes the rescue operation due to battery voltage drop below F1-5 (error code E-04), let the TAPS charge for 8 hours before performing this test again.
11. If input P3 “Rescue Operation Complete” is used, TAPS shall shut down once the rescue operation is complete and input P3 is energized. This will immediately cancel the parameter F1-1 “Backup Power Run Time.” If the command is not issued to the TAPS unit, please check wiring and controller output.
12. If input P2 “Restart Backup Power Operation” is used, verify by pushing the DOB button in the COP to validate proper wiring and operation. This can be done once TAPS has been shut down by either P3 input or parameter F1-1 “Backup Run Time” having elapsed. TAPS shall then restart when the DOB is pressed and will operate until either
P3 is activated or parameter F1-1 has expired.
13. If input P1 “Remote Backup Power Operation” is used, verify correct operation by triggering this input from the appropriate controller output or the source it is wired to. To do this, TAPS shall be on commercial power operation and “Normal Power” indicator shall be lighted. When the P1 input is triggered and held for the duration defined by F1-
9 “Commercial Power Loss Detection” (factory default is 2 seconds), TAPS shall proceed to “BACK UP” power operation and indicator BACKUP POWER shall light. TAPS shall then operate until cancelled by either input P3 “Rescue operation Complete” or by parameter F1-1 “Backup Power Run Time” having elapsed. Note that shut down may also be caused by drained/discharged batteries, dead batteries, or an inoperative UPS unit.
Backup Generator Power Test
The controller will put the elevator into Emergency Power Operation when the controller receives the Emergency Power Input (EPI) signal. During Phase 1 of Emergency Power Operation, the car will be moved to the emergency power return floor. For groups or duplex installations, each car will be moved to the emergency power return floor one at a time.
During Phase 2 of Emergency Power Operation, if the car Emergency Power Run (EPRUN) input is activated, the car will run normally. Otherwise, the car will remain at the emergency power return floor and will not respond to calls.
For a simplex controller, the car EPRUN input is sometimes connected to a switch so that the input can be turned ON and OFF. For a duplex or groups, each car EPRUN input may be connected to a Run Selection switch. The position of this switch determines which car will run during Phase 2 of Emergency Power Operation.
Often, there is an AUTO position on the Run Selection switch connected to the AUTO inputs on controllers in a group or duplex installation. If the AUTO input is activated, one car will be automatically selected to run during Phase 2 of Emergency Power Operation. For example: If one car happens to be out of service when the operation begins, another car will be automatically selected to run.
3-54 Manual # 42-02-2P25
Motion 4000
Final Tests
Check the MCE drawings to verify that the car is properly connected to the emergency generator and that emergency power (F1, Extra Features Menu) is set up appropriately. A typical generator connection is shown below.
Figure 3.5 Typical Emergency Generator Connection
3
1. Disconnect power from the controller.
2. When the emergency generator comes on line, the EPI input to the controller should be activated.
3. The car will recall to the assigned floor.
4. If the EPRUN input (not shown) is activated, the designated car will respond to hall and car calls. Otherwise, the car will remain at the recall floor.
5. Restore normal power to the controller. If running, the designated car will stop, wait until normal power is fully established, then resume normal operation.
3-55
Final Adjustments
Final Adjustment
Once you are satisfied that the car is operating accurately and safely, you will want to ride the car to verify the comfort of the ride and proper operation from a passenger perspective.
1. Place the car on Independent Service so that it will not respond to hall calls.
2. Verify IND indicator on HC-CTL-2 Control board is lighted.
3. Verify the TEST switch is in the NORMAL position.
4. Verify the LCD displays INDEPENDENT.
While riding the car:
• Verify proper door operation including re-opening, nudging, safe edge, photo eye, and door open and close button operation.
• Verify proper floor leveling at all landings.
Place the car on Normal operation. Verify:
• Hall call operation
• PIs and gongs
• Fire return and in-car operation for main and alternate landings
• Alternate riser operation
• Other options as required per job
• Normal and Inspection Mode Fault Bypasses to OFF
• F3 function switch UP
• System Mode/Controller System Menu
• Automatic mode fault bypass: Bypass OFF
• Inspection mode fault bypass: Bypass OFF
• Make adjustments as required.
3-56 Manual # 42-02-2P25
User Interface
In this Section
The default user interface to the Motion 4000 Traction Control is the LCD and keypad on the
HC-MPU board. A hand-held user interface that functions like the LCD and keypad may also be provided. The hand-held user interface provides access when plugged into any CAN Bus connector in the system. This section describes user interface functionality:
• HC-MPU Main Processor: Board indicators, switches, buttons, connectors and display
• Access Security: Optional password protection system (see
page 4-5
)
Adjustments to system settings are made using switches and buttons on the MPU board or on the hand-held control. There are eight different “functions,” each of which accesses different groups of settings. On the MPU board, you access a functional area by moving one of eight
“function” switches to the UP position. On the hand-held, you press a “function” button.
• With no function selected: Diagnostic messages are displayed. See
page 4-6
.
• F1 — Program Mode:
• Basic Features Menu (see page 4-13
)
• Fire Service Menu (see
page 4-17
)
• Door Operation Menu (see page 4-19
)
• Timer Menu (see
page 4-24
)
• Gongs/Lanterns Menu (see
page 4-25
)
• Spare Inputs Menu (see page 4-27
)
• Spare Outputs Menu (see
page 4-36
)
• Extra Features Menu (see
page 4-44 )
• Additional Car Options (see
page 4-52
)
4-1
User Interface
• F2 — External Memory Mode:
• View data stored in external memory. See page 4-56
.
• F3 — System Mode:
• Building security. See
Building Security Menu on page 4-56 .
• Controller system (fault bypass, data trap). See Controller System Menu on page 4-58 .
• Passcode request (See Passcode Request Menu on page 4-59 .)
• Load weigher thresholds (See
Load Weigher Thresholds on page 4-60 .)
• Analog load weigher learn
• Controller System Menu (real time speed/position
Additional Car Options on page 4-
52)
• F4 — Messages and Floor Labels (
F4: Messages and Floor Labels on page 4-63 )
• F5 — Controller Utilities Menu: Front and rear car call entry, date/time settings, motion diagnostics. (See
F5 Menus on page 4-65
.)
• Monitoring and Reporting ( Please refer to “Monitoring and Reporting Menu” on page 4-135 ).
• Learning Terminal switches ( Please refer to “Terminal Limit Utilities Menu” on page 4-138 ).
• F6 — Hoistway learn operation (
Please refer to “F6: Hoistway Learn Operations” on page 4-140
).
• Floors
• Counterweight position
• F7 — Parameters adjust (download).
Please refer to “F7: Parameters Adjust” on page 4-
141 .
• F8 — Software version (
Please refer to “F8: Software Revision” on page 4-164 .)
• F1 and F8 — Board software versions ( Please refer to “F1 & F8: Board Software Versions” on page 4-165
.)
4-2 Manual # 42-02-2P25
Motion 4000
The HC-MPU Main Processor Unit
The HC-MPU Main Processor Unit
Figure 4.1 HC-MPU Main Processor Unit Board
M1: Ethernet Port A
J10: Ethernet Port B
SW1
JP5
J6: CPU B Debug
J7: RS232 Port B
J3: RS232 Port A
S1: RSTA
LCD Display
JP7
J2: Keyboard Port
J8: CPU-B JTAG
J9: 16VAC input
TP +25V
4
TP +5V
JP1
TP GND
JP4 TP GND
J1 S6
JP2
J5: Internal CAN connection
S4 SW2 SW3 S5 S3
CPU A ON LED
S2: RSTB
JP6
CPU B ON LED
Indicators
JP3
TP +3.3V
J4:External CAN Port
The kind of information displayed by the LCD depends on the settings of function switches F1 -
F8:
• All switches down: Diagnostics mode - scrolling status message, car position, CPU internal memory content.
• Program mode - F1 switch up, others down. Parameter entry. Must be on Inspection.
• External Memory (RAM) - F2 switch up, others down. Review of RAM contents.
• System mode - F3 switch up, others down. Parameter entry for security, load weigher, and other system level functions. System does not have to be in Inspection mode.
• Serial Fixtures - F4 switch up, others down.
• Date/Time, event log, motion diagnostics, monitoring - F5 switch up, others down.
• Positioning system learn operation - F6 switch up, others down.
• Motion parameter Adjust - F7 up, others down. Traction parameters.
• Status - F8 switch up, others down. Display software version, floor eligibility, load as a percentage of full load.
• Board software versions - F1 and F8 up, others down. Press N to cycle through software version for each board in the system.
4-3
User Interface
Table 4.1 HC-MPU Board Switches
Switches
S1
S2
S3
S4
S5
S6
SW1
SW2
SW3
Description
RSTA: Reset CPU A
RSTB: Reset CPU B
“-” minus push button - decrement setting
“S” push button - select
“+” plus push button - increment setting
“N” push button - next
Port Selection: RS232 Port A / Ethernet Port A
DIP Function switches F5 through F8
DIP Function switches F1 though F4
Table 4.2 HC-MPU Board Indicators
Indicators Description
CPU A ON CPU A is executing its program.
CPU B ON CPU B is executing its program.
LED2
LED1
Reserved.
Reserved.
FAULT
CPU ON
MLT
TOS
A fault has been detected.
All processors are fully functional.
Motor/Valve Limit Timer: The motor/valve limit timer has elapsed.
Timed Out of Service: The TOS timer has elapsed and the car is out of service.
FIRE
INSP
IND
HS
DLK
SAF ON
Fire Service: The car is on fire service operation.
Inspection: The car is on inspection operation.
Independent Service: The car is on independent service.
High Speed: The car is running at high speed.
Doors Locked: The door lock contacts are made.
Safety On: The safety circuit is made.
• RSTA - RSTB: Reset. If the elevator is running when reset, the controller will drop the safety relay and bring the elevator to an immediate stop. The elevator will then go to the next landing, self-check, and resume service if warranted. Existing calls are lost if the computer is reset.
• N, S, +, - Push Buttons: Parameter review and entry. Access and function depend on the positions of the Function switches. Generally:
• N = Next. Moves the cursor.
• S = Select or Save.
• +/-: Increment/Decrement.
4-4 Manual # 42-02-2P25
Motion 4000
Access Security
Access Security
Access security is an option. When access security is active, you are required to enter a password before parameters can be adjusted.
Password
Program mode and System mode may be secured by an 8digit, alpha-numeric code. If this is the case, when either mode is selected using the Function switches, the LCD will show:
To enter a password:
• N: to select a digit
• +: to increment value
• -: to decrement value
• S: Enter (check against valid password)
Once a valid code is entered, access is granted. The password will not have to be re-entered until the password timer expires.
4
Note
If Passcode Request appears on the LCD, a passcode is required in order to run the elevator on any mode of opera-
tion other than Inspection. See Passcode Request Menu
for
more information. Please refer to “Passcode Request Menu” on page 4-59 .
Setting Parameters To Default Values
There are occasions when it is necessary to reset system parameters to default values:
• MC-MPU software is changed
• RAM memory is corrupted (lightning strikes can sometimes cause this)
To reset to default values:
1. Place the car on Machine Room Inspection.
2. Place function switches F1, 3, 5, and 7 in the Up position.
3. Press all four push buttons (N, S, +, -) at the same time.
After resetting parameters to their defaults, you will need to set up system parameters again.
4-5
User Interface
Diagnostic Mode
With all Function switches down, Diagnostic Mode is active. The
LCD displays status, position, an internal memory register address and its contents (flags). This mode allows you to select a memory register and view its contents. Memory contents can tell you the exact state of controller inputs and outputs, which is very valuable in troubleshooting.
1. Select the address to view. (See following two tables.)
• Press N to select an address digit (selected digits blink)
• Press + or - to change the blinking digit
2. Press S to select the entered address when ready to view contents (or wait about 20 seconds and the selection will take effect by itself).
Position indicator
(landing 8)
Status
Memory Contents
Register Address
LCD Format
• Control Configuration: D, S, or blank.
• S (slave): Hall call assignments made by group or other controller.
• D (dispatcher): This controller is acting as a dispatcher. It is responsible for assigning hall calls to itself and to a second controller if this is a Duplex installation.
Duplex Configuration:
D = Dispatcher
S = Slave
Blank = Simplex Operation
• Blank: Simplex operation or, if part of a group or duplex, communication has not been established with controller or group.
• Status / Error Message: The top line is elevator status or an error message. Messages are scrolled if longer than the space available. There is a status message for each special operation (e.g., Fire Service). There are also messages for error conditions (e.g., open safety string). Please refer to “Status and Error Messages” on page 5-2 for a list of messages including a description and troubleshooting suggestions.
• PI “nn”: Current elevator position relative to the bottom floor. 1 denotes the lowest landing served.
• Computer Internal Memory: Register address and contents. Each of the 8 data digits
(flags) corresponds to a particular elevator signal or condition. Each digit is either 1 or 0. A
1 indicates the signal or condition is ON and 0 indicates it is OFF.
4-6 Manual # 42-02-2P25
Motion 4000
Diagnostic Mode
The Computer Internal Memory Chart (
Table 4.3 on page 4-7 ) shows the meaning of data at dif-
ferent addresses. For example, the internal memory display might look like this:
4
At address 29; the data is 11110000. To figure out what this means, match up the data digits with row 29 of the Computer Internal Memory Chart table:
Display Data: 1 1 1 1 0 0 0 0
Row 29: DNDO LD DPD DDP UPDO LU UPD UDP
DNDO, LD, DPD and DDP signals are ON; UPDO, LU, UPD and UDP signals are OFF.
Table 4.3 Computer Internal Memory Chart
ADD
24:
25:
26:
27:
28:
29:
2A:
2B:
10:
11:
12:
13:
20:
21:
22:
23:
2C:
2D:
2E:
2F:
30:
31:
33:
38:
42:
43:
FLAGS AND VARIABLES
8 7 6 5 4
INT
SCE
LFP
HD
LLW
DNDO
DMD
TOS
DOLMR
TFAR
DCFR
DOCR
DOLM
TFA
DCF
DOC
PHER
DCR
DCPR
SER
PHE
DC
DCP
SE
FRA
FCCC
UFP
FCOFF
DLK
LD
DCB
MLT
DZR
UCR
DOFR
DCLCR
DZ
UC
DOF
DCLC
FCS
FCHLD
NYDS
DHLD
DDF
DPD
UCB
DOLR
CCR
LOTR
CSBR
DOL
CC
LOT
CSB
FRS
HLI
CCH
IND
REL
DDP
CCB
MGR
DZP
TEMPB
SD
FRBYP
R4
CTLDOT
API
HML
STC
UFQ
SDA
FRON
ISTD/R2 ISTU/R3
CTLF
SAB
SLV
SAF
DZORDZ
DSD
HCR
FCSM
BFD
HYD1_TRC0 ECC
CTL
TEST
CCC
FREE
ALV
HCDX
FRM
SU
CD
DEADZ
EPSTP
DHENDR DHEND
CNFG DLI
COMMUNICATION TIME-OUT ERROR COUNT
COMMUNICATION CHECKSUM ERROR COUNT
DNS
LEF
DIN
IN
ISR
UPDO
DMU
H
DBCR
NDSR
GHTR
DCCR
DBC
NDS
GHT
DCC
3
CCD
FRSS
SUA
ECRN
DHLDI
AUTO
CTST
DLW
UPS
HDLYE
DPR
DLKS
INCF
LU
DCA
HSEL
DOBR
FDCR
HCTR
NUDGR
DOB
FDC
HCT
NUDG
2 1
GEUR
DHOR
GEDR
DOIR
CCTR SDTR
NDGBPSR DSHTR
GEU
DHO
CCT
NDGBPS
GED
DOI
SDT
DSHT
STD/R0
FWI
GTDE
DELSIM
REAR
UPD
UCA
DSH
STU/R1
PIC
GTUE
YSIM
LLI
UDP
CCA
RUN
ISV
FRAS
USD
EPR
PH1
EPRUN
HOSPH2
LWCE
ISRT
FRC
TFD
PFG
NDGF
EPI
HOSP
HLW
4-7
User Interface
Troubleshooting Example
Examining the computer memory (as in the example above) is a useful step in troubleshooting.
It is possible to find out if the controller is receiving input signals correctly and if it is sending proper output signals. It is also possible to look up each of the computer output and input signals shown in the Job Prints.
The following example explains how to use
Table 4.3 on page 4-7
and Table 4.4 on page 4-9 to
check a signal in internal memory.
• Problem: the photo eye will not cause the doors to reopen.
1. Look at
Table 4.4 on page 4-9 . Find the abbreviation or mnemonic for Photo Eye input.
• The table shows that the mnemonic for Photo Eye input is PHE and provides an
Address (Add) and Position (1 - 8).
• This information shows where to look for the signal in Table 4.3 on page 4-7 and on
the computer display.
Table 4.3 on page 4-7
shows that the address of PHE is 20 and the position is 7.
2. Notice in the table that PHE is indeed in position 7 on row 20.
3. Now that the address and position have been determined, look up the PHE signal on the computer.
• First, change the address on the display to address 20.
• Then, look at data bit number 7 (from the right), which is underlined in the graphic:
This digit represents the computer interpretation of the PHE signal. If the digit is 1, the computer thinks that the PHE signal is ON. If the digit is 0 (as shown), the computer thinks that the PHE signal is OFF.
This information can be used to find the source of the problem. The diagnostic display will show that the PHE input is ON when an obstruction is present which should interrupt the photo eye beam. If this is the case, checking the voltage present on the PHE terminal will show if the problem is inside or outside the controller.
4-8 Manual # 42-02-2P25
Motion 4000
Diagnostic Mode
Table 4.4 Alphabetized Flags, Definitions, and Locations
FLAG Definition Add Pos FLAG Definition Add Pos
CCD
CCH
CCR
CCT
CCTR
CD
CNFG
CSB
ALV
API
AUTO
BFD
CC
CCA
CCB
CCC
Other car alive output
Alternate Parking Input
31 5 FRS
33 8 FRSS
Emergency power auto output 31 3 FWI
Bottom floor demand flag 2E 5 GED
Car call flag
Car call above flag
Car call below flag
Car call cancel input
21 5
2A 1
2A 5
38 6
GEDR
GEU
GEUR
GHT
Car call disconnect flag
Car call hold
Car call flag rear
Car call time flag
Car call time flag rear
Car done flag
Configuration error flag
Car stop switch bypass
2C 3
26 5
11 5
22 2
12 2
2F 4
38 5
23 5
GHTR
GTDE
GTUE
H
HCDX
HCR
HCT
HCTR
Fire phase 1 input
Fire phase 1 flag
Fire warning indicator output
Gong enable down output
Gong enable down output rear
Gong enable up output
Gong enable up output rear
Gong hold timer flag
Gong hold timer flag rear
Gong timer down enable
Gong timer up enable
High speed output
Hall call disconnect flag
Hall call reject flag
Hall call door time flag
Hall call door time flag rear
CSBR
CTL
Car stop switch bypass rear
Car to lobby input
CTLDOT Car to lobby door open timer
CTLF Car to lobby function
CTST
DBC
DBCR
DC
Capture for test input
Door close button input
Door close button rear
Down call flag
13 5 HD
31 6 HDLYE
31 8 HLI
31 7 HLW
33 3 HML
20 4 HOSP
10 4 HOSPH2
21 7 HSEL
High speed delay flag
High speed delay elapsed flag
Heavy load input
Heavy load weigher flag
27 8
25 3
25 5
38 1
Home landing input 38 8
In car hospital emergency input flag 33 1
Hospital emergency phase 2 flag
Hospital service select flag
33 2
2B 3
DCA
DCB
Down call above flag
Down call below flag
2A 3 HYD1-TR0 Hydro/Traction flag
2A 7 IN Inspection or access input
DCC Door close complete flag 23 4 INCF
DCCR Door close complete flag rear 13 4 IND
Ind. service car call cancel flag
Independent service input
DCF
DCFR
Door close function output 22 8 INT
Door close function output rear 12 8 ISR
DCLC Door close contact input
DCLCR Door close contact input rear
23 6
13 6
ISRT
ISV
Intermediate speed input
In service and ready
In service truly flag
In service flag
2F 6
27 4
28 3
27 5
24 8
28 4
2C 1
2C 2
12 4
26 2
26 1
2B 4
2C 4
2C 5
22 3
12 3
24 5
2D 3
25 2
20 1
10 1
20 2
10 2
22 4
DCP
DCPR
DCR
DDF
Door close power output
Door close power output rear
Down call flag rear
Double ding function flag
22 7 LD
12 7 LEF
11 7 LFP
28 6 LLI
DDP Down direction preference flag 29 5 LLW
DEADZ Dead zone flag 30 4 LOT
DELSIM Delta simulation bit
DHEND Door hold end
27 2
33 4
LOTR
LU
Level down input
Leveling encounter flag
Lower parking floor flag
Light load input
29 7
25 4
26 8
28 1
Light load weighing funct. input flag 28 8
Lobby door time 22 5
Lobby door time rear
Level up input
12 5
29 3
DHENDR Door hold end rear
DHLD Door hold input flag
DHLDI Normal door hold input flag
DHO Door hold open flag
DHOR Door hold open flag rear
DIN Door open inactive
DLI
DLK
Dispatch Load Input
Door lock input
DLKS
DLW
33 5
27 6
30 3
21 2
11 2
26 4
38 4
28 7
LWCE
MGR
MLT
NDGBPS
NDGBPSR
NDGF
NDS
NDSR
Door lock store bit 27 3 NUDG
Dispatch load weighing function 38 3 NUDGR
Load weighing change enable flag
Motor generator run flag
Motor limit timer flag
Nudging bypass flag
Nudging bypass flag rear
Nudging function flag
Hall door timer non-shorten
Hall door timer non-shorten rear
Nudging output
Nudging output rear
38 2
2B 5
2B 7
23 2
13 2
30 1
21 4
11 4
23 3
13 3
4-9
4
User Interface
Table 4.4 Alphabetized Flags, Definitions, and Locations
FLAG Definition Add Pos FLAG
DMD
DMU
Demand down flag
Demand up flag
DNDO Down direction output
DNS Down direction sense input
DOB Door open button input
DOBR Door open button input rear
DOC Door open command
DOCR Door open command rear
DOF
DOFR
DOI
2A 8
2A 4
29 8
24 4
20 3
10 3
23 8
13 8
NYDS
PFG
PH1
PHE
PHER
PIC
R2
R3
Door open function output 22 6 R4
Door open function output rear 12 6 REAR
Door open intent flag 21 1 RUN
DOIR
DOL
Door open intent flag (rear)
Door open limit input
DOLM Door open limit flag
DOLMR Door open limit flag rear
DOLR
DPD
DPR
DSD
Door open limit rear
Down previous direction
Door protection timer flag
Down slow down input
11 1
20 5
20 8
10 8
10 5
29 6
26 3
2E 6
SAB
SAF
SCE
SD
SDA
SDT
SDTR
SE
DSH
DSHT
Door shortening flag
Door shortening flag
DSHTR Door shortening flag rear
DZ Door zone input
DZORDZ Front or rear door zone input
DZP Door zone previous
DZR
ECC
Door zone input rear
Excess car calls flag
ECRN
EPI
Emergency car run flag
Emergency power input flag
EPR Emergency power return
EPRUN Emergency power run input
EPSTP Emergency power stop input
FCCC Fire phase 2 car call cancel
FCHLD Fire phase 2 hold
FCOFF Fire phase 2 off
2B 2
23 1
13 1
20 6
2D 6
2C 8
10 6
2F 5
2F 3
31 1
2F 2
31 2
31 4
25 7
25 6
27 7
SER
SLV
STC
STD/R0
STU/R1
SU
SUA
TEMPB
TEST
TFA
TFAR
TFD
TOS
UC
UCA
UCB
FCS
FCSM
FDC
FDCR
Fire phase 2 input 24 6 UCR
Fire service PH 2 input memory 2D 5 UDP
Door fully closed phase 2 21 3 UFP
Door fully closed phase 2 rear 11 3 UFQ
FRA
FRAS
Alt. Fire service phase 1 input 24 7 UPD
Alternate fire flag 2D 2 UPDO
FRBYP Fire phase 1 bypass input flag 2F 8 UPS
FRC Fire phase 2 flag 2D 1 USD
FREE
FRM
FRON
No demand and in service
Fire service phase 1 flag
Fire phase 1 on input flag
30 5 YSIM
2D 4
2F 7
Definition Add Pos
New York door shortening flag
Passing floor gong output
Phase 1 return complete flag
Photo eye input
Photo eye input rear
PI correction flag
Absolute floor encoding #2
Absolute floor encoding #3
Absolute floor encoding #4
Rear door flag
Run flag
Sabbath input
Safety string input
Stepping correction enable
Supervisory down flag
Down direction arrow
Short door time flag
Short door time flag rear
Safety edge input
Safety edge input rear
Stable slave flag
13 7
38 7
Stepping complete flag 2C 7
Step down input/absolute encoding #0 24 2
Step up input/absolute encoding #1 24 1
Supervisory up flag 2E 4
Up direction arrow
Temporary bit
2E 3
2D 8
Test switch input
Timing function active
Timing function active rear
Top floor demand flag
Timed out of service flag
Up call flag
Up call above flag
Up call below flag
33 6
21 8
11 8
2E 1
2B 8
21 6
2A 2
2A 6
Up call flag (rear)
Up direction preference
Upper parking floor flag
Up first qualifier flag
Up previous direction
Up direction output
Up direction sense input
Up slow down input
Wye simulation bit
11 6
29 1
26 7
2D 7
29 2
29 4
24 3
2E 2
27 1
33 7
2C 6
25 8
2E 8
2E 7
22 1
12 1
23 7
26 6
2F 1
30 2
20 7
10 7
25 1
30 7
30 6
30 8
28 2
2B 1
4-10 Manual # 42-02-2P25
Motion 4000
F1: Program Mode
F1: Program Mode
These parameters define the building, floors and openings to be served, and other basic requirements for the elevator.
Put the car on Inspection and set Function switch F1 up (all others down) to enter Program mode.
Refer to the Programming Record in the Job Prints for a list of the options and values programmed into the controller at MCE.
Note
If you make programming changes, record them in the reference table, Appendix A, page A-21 .
General Description of Program Mode
Programmable options and features are divided among several menus:
Basic Features Menu
Fire Service Menu
Door Operation Menu
Timer Menu
Gongs/Lanterns Menu
Spare Inputs Menu
Spare Outputs Menu
Extra Features Menu
Additional Car Options Menu
Changing Parameters
Enter Program mode. The Start Message will appear:
• Press N to cycle through the menus.
• Press S when the menu you want appears.
• Press N to view the first option in the menu. (Press repeatedly or hold down to cycle through options.)
• Press S to change the value (i.e., from YES to NO).
Saving Changes
After selecting the new value:
• Press N until the save message appears:
• Press S to save changes (or N if you want to cancel the change).
Unsaved changes will be LOST when the F1 switch is placed in the down position (exiting
Program mode).
Be sure to enter changed parameter values in the table provided in Appendix A.
4
4-11
User Interface
Viewing Options Within a Menu
• To return to the top menu level, press the N and '+' buttons at the same time.
• To scroll backwards, press the S and '-' push buttons at the same time.
• To set an option to NOT USED, press the S and '+' buttons at the same time.
Restoring Original Values Before Saving
If you have made changes but have not saved them yet, you can restore the original values:
• Move the F1 switch back to the down position and the original values will be restored.
Step-By-Step Example
The table provides a step-by-step example of using Program mode. In this example, the Fire
Phase I Alternate floor will be changed.
Table 4.5 Parameter Programming Example
Steps to take Display menus and sub-menus
Put the car on Inspection
Flip F1 switch Up
Press N button for Next
Press N button for Next
D INSPECTION OPE
PI 8 20:1O11OOOO
PROGRAM MODE
PRESS N TO BEGIN
*BASIC FEATURES*
* MENU *
*FIRE SERVICE*
* MENU *
Press S button to Select
Press N button for Next
Press N button for Next
Press S button to select next available value. If you pass desired value, press S until desired value appears again.
Press N button for Next
Press N button for Next
FIRE SERVICE
OPERATION? YES
FIRE PHASE 1
MAIN FLOOR = 1
FIRE PHASE 1
ALT. FLOOR = 1
FIRE SVCE. CODE
ALT.FLOOR = 3
FIRE SVCE. CODE
xxxx
BYPASS STOP SW.
ON PHASE 1? YES
Press N button to scroll through any remaining Fire Service sub-menus.
Press N button for Next
*FIRE SERVICE*
Press N button for Next
* MENU *
*DOOR OPERATION*
Press N button for Next
* MENU *
* TIMER *
* MENU *
Press N button for Next
Press N button for Next
Press N button for Next
Press N button for Next
*GONGS/LANTERNS*
* MENU *
*SPARE INPUTS*
* MENU *
*SPARE OUTPUTS*
*EXTRA FEATURES*
Press N button for Next
Press N button for Next
Press S button to Save
Press N button for Next
Set F1 switch Down. Take car off Inspection
* ASME A17.1 *
*2000 FEATURES*
*SAVE CHANGES?*
* N=NO S=YES *
SAVE COMPLETE:
N = CONTINUE
PROGRAM MODE
PRESS N TO BEGIN
The new options are stored and in effect.
4-12 Manual # 42-02-2P25
Motion 4000
F1: Program Mode
Basic Features Menu
• CONTROLLER TYPE: TRACTION (M4000)
• Identifies controller type to the HC-CPU board.
• Set to TRACTION (M4000). This is the factory default.
Note
When learning to set parameters, it is very easy to unintentionally set the Controller Type to
Motion 2000. If this occurs, you will see the error “MUSE INPUT IS LOW.” To correct, set the
Controller Type to M4000, press N repeatedly until the Save Changes menu appears, then press
S to save changes.
• SIMPLEX/LOCAL OR DUPLEX?
• Each controller is programmed at the factory for either simplex/local, or duplex operation. If the controller is a simplex, it assigns calls only for itself. The Duplex option will not appear.
• If the controller is a duplex, it can operate a single car as a simplex or it can be connected to a second Motion 4000 controller and the two can operate as a duplex.
• Both controllers must have duplex capability for duplexing to work. The option on each controller must be set to duplex. Jumper JP3 on each HC-MPU (lower right corner) must be in place for successful Duplex operation.
• If the controller is controlled by a group dispatcher, it should be set to Simplex/Local.
In Duplex configuration, one of the controllers will assert itself as the dispatcher and will remain the dispatcher unless it is taken offline. The dispatching controller will show a “D” on its
LCD; the other, an “S.” Hall calls are physically connected to both controllers.
• OPERATION:
• Dispatching operation - For simplex operation, you may choose: Selective Collective,
Single Button Collective, or Single Automatic Push button:
• Selective Collective - Use if there is an UP and DOWN button at each landing except for the top floor (DOWN button only) and bottom floor (UP button only) and any number of hall calls can be registered at one time.
• Single Button Collective - Use if there is only one call button at each landing and any number of calls can be registered at one time.
• Single Automatic Push button - Use if there is only one call button at each landing and only one call can be registered and/or serviced at a time.
Note
If Single Button Collective or Single Automatic Push button operation is selected, one of the spare outputs should be used for an INDFRC output. This is used to disconnect hall calls during
Fire Service and Independent Service (
see “Spare Outputs Menu” on page 4-36 , INDFRC out-
put and your job prints for more detail). For duplex operation, the dispatching scheme is always
Selective Collective so the Operation option message will not appear if duplex is selected.
4
4-13
User Interface
Caution
Settings that affect the number of floors in the building, openings served per floor, discrete or serial (CE) position indicators, or the presence or absence of a serial car call board determine the sequence of connections on Universal I/O boards used as “call boards” in the controller (UIO boards with addresses from 0 to 31). These settings are made at the factory and should never need to be changed. If you do need to change these settings, disconnect the orange I/O terminal blocks from the UIO boards first, change the settings, then re-wire and re-connect the terminal blocks.
• TOP LANDING SERVED? (simplex)/TOP LANDING FOR THIS CAR? (duplex)
• Set to the highest floor served by this car. See caution above.
• WALK-THRU DOORS THIS CAR?
• Set to Yes if this car has a second set of doors that can be controlled independently of the front doors.
• CAR SERVES FRNT/FLR 1? (simplex)/THIS CAR SERVES FRNT/FLR 1?
(duplex)
• Set to YES if this car is eligible to serve a front opening at this floor. (This prompt will reappear for each floor.) See caution above.
• Press the '+' button to scroll through available landings. Press N for the next option.
• CAR SERVES REAR/FLR 1? (simplex) / THIS CAR SERVES REAR/FLR 1?
(duplex)
• Set to YES if this car is eligible to serve a rear opening at this floor. (This option will not be displayed if option WALK-THRU DOORS THIS CAR? is set to NO.) (This prompt will reappear for each floor.) See caution above.
• Press the '+' button to scroll through available landings. Press N for the next option.
• TOP LANDING FOR OTHER CAR? (duplex)
• Set to the highest floor served by the other car of the duplex pair.
• WALK-THRU DOORS OTHER CAR? (duplex)
• Set to Yes if the other car of the duplex pair has a second set of doors that can be controlled independently of the front doors.
• OTHER CAR SERVES FRNT/FLR1? (duplex)
• Set to YES if the other car of a duplex pair is eligible to serve a front opening at this floor. (This prompt will reappear for each floor.) See caution above.
• Press the '+' button to scroll through available landings. Press N for the next option.
• OTHER CAR SERVES REAR/FLR1? (duplex
• Set to YES if the other car of a duplex pair is eligible to serve a rear opening at this floor. (This prompt will reappear for each floor.) See caution above.
• Press the '+' button to scroll through available landings. Press N for the next option.
Note: Both controllers in a duplex pair must have the parameters on this page programmed.
4-14 Manual # 42-02-2P25
Motion 4000
F1: Program Mode
• PARKING FLOOR
• Any landing may be the parking floor. The car will go to the parking floor when it is free of call demand. There is a Parking Delay Timer that will cause a free car to wait for a short time before parking. The timer is adjustable, with a value between 0.0 minutes
(no delay) and 6.0 minutes ( see “PARKING DELAY TIMER (Range: 0.0-6.0 Minutes)” on page 4-25 ).
• If the parking feature is not needed, choose NONE. The car will then stay at the last call answered.
• ALT. PARKING FLOOR
• Available only when an API input is programmed and a parking floor is set. Any landing can be chosen as the alternate parking floor. The car will go to the alternate parking floor when it is free of call demand and the API input is active.
• SECONDARY PARKING FLOOR
• Does not apply to Simplex. Any landing may be the secondary parking floor. A car will go to this floor when it is free of call demand and the other car is already parked at the first parking floor. It is acceptable to make the secondary parking floor the same as the first parking floor if both cars are to park at the same floor. If a second parking floor is not needed, choose NONE for the Secondary Park Floor option. The first free car will go to the first parking floor and the second car will stay at the last call answered.
• LOBBY FLOOR
• Any landing may be the Lobby Floor. When the car answers a hall or car call at this floor, the doors will stay open until the Lobby Door Timer elapses. The Lobby Door
Timer is adjustable ( see “LOBBY DOOR TIMER (Range: 0.5-120.0 Seconds)” on page 4-24 ). NOTE: The Lobby Floor is also used for the CTL (Car To Lobby) input.
• CAR IDENTIFIER
• Does not apply to Simplex. Specifies which controller is assigned to car A and which to car B, primarily for controllers using a peripheral device such as a monitoring system.
4
Caution
Settings that affect the number of floors in the building, openings served per floor, discrete or serial (CE) position indicators, or the presence or absence of a serial car call board determine the sequence of connections on Universal I/O boards used as “call boards” in the controller (UIO boards with addresses from 0 to 31). These settings are made at the factory and should never need to be changed. If you do need to change these settings, disconnect the orange I/O terminal blocks from the UIO boards first, change the settings, then re-wire and re-connect the terminal blocks.
• SERIAL COP BOARD TYPE?
• Set to type of installed serial COP board (MC-CPI, ICE-COP-2, or NONE. See caution above.
• DISCRETE PI’s on UIO?
• Set to No if the car uses serial (CE) position indicator fixtures. See caution above.
• Set to Yes if PI’s are connected to HC-UIO boards.
4-15
User Interface
• DEDICATED PI BOARD?
(Appears if “Discrete PI’s on UIO?” is set to Yes. Dedicates first one or two HC-UIO boards to PI’s alone [no call connections]).
• If Yes: Position Indicators will be located on UIO Board 0 (zero) for 2 - 16 stops or boards 0 (zero) and 1 (one) for 2 - 32 stops (board 1 handles 17 - 32 [assuming that PI is one wire per floor]). Calls will begin on a new UIO Board immediately following
Board 0 or 1.
• If No: PI’s are located on UIO boards but calls can begin immediately following the last
PI rather than on the next UIO board.
• SERIAL CARTOP DOOR CONTROL?
• Set to Yes if the door operator is connected to an HC-UIO board in the cartop box rather than using multiple connections through the traveler to the HC-CTL-2 board in the controller cabinet.
• DISABLE LOCAL HALL CALLS?
• Set to Yes if the car is dispatched by a group controller and should not respond to a local (connected to car) riser. If this car has swing operation, do not set this to Yes as it will prevent the car from responding to local riser calls.
4-16 Manual # 42-02-2P25
Motion 4000
F1: Program Mode
Fire Service Menu Options
• FIRE SERVICE OPERATION?
• If Fire Service operation is not required, set to NO. If set to YES, the options below will appear.
• FIRE PHASE 1 MAIN FLOOR
• Any landing may be the Main Fire Return Floor for Fire Service.
• FIRE PHASE 1 ALT. FLOOR
• Any landing may be the Alternate Fire Return Floor for Fire Service.
• FIRE SVCE. CODE
• Fire Service Operation will conform to the selected fire service code. Available codes are:
1. CHICAGO (OLD)
2. VET ADMIN (Veterans' Administration)
9.
CITY OF HOUSTON
10. AUSTRALIA
3. NYC RS-18
4. ANSI A17.1 -89>
5. CALIF. TITLE 8
6. HAWAII
7. CSA B44-M90
8. 34 PA CODE, CH. 7
11. CITY OF DETROIT
12. MASSACHUSETTS
13. ANSI A17.1 85 - 88
14. CITY OF DENVER
15. CHICAGO 2001
16. ANSI A17.1-2000
• FIRE PHASE I 2ND ALT. FLOOR
• Detroit Fire Code only. Any landing may be the 2 nd
alternate fire return floor.
• Select None if there is no second alternate return floor.
• WILL THIS CAR RUN ON PH2?
• If set to yes, this car is allowed to run on Fire Phase II.
• BYPASS STOP SW. ON PHASE 1?
• Prevents the stop switch from being bypassed on Fire Phase I. When set to NO, the
CSB output will not come ON as the car is returning on Fire Phase I.
• HONEYWELL FIRE OPERATION?
• Only if FIRE SVCE. CODE option set to AUSTRALIA ( See “FIRE SVCE. CODE” on page 4-17 ). If set to YES, Australia fire code will conform to Honeywell requirements.
If set to NO, controller will conform to standard Australia code.
• NYC FIRE PHASE 2 AND ANSI 89?
• Available only if FIRE SVCE. CODE is set to ANSI A17.1 89 ( See “FIRE SVCE. CODE” on page 4-17 ). If set to YES, ANSI A17.1 89 Fire Code will conform to New York City
Fire Code requirements when on Fire Phase 2. If set to NO, controller will conform to standard ANSI A17.1 89 Fire Code.
4
4-17
User Interface
• WHITE PLAINS, NY FIRE CODE?
• Available only if FIRE SVCE. CODE set to ANSI17.1 89 ( See “FIRE SVCE. CODE” on page 4-17 ). The city of White Plains requires that, if fire phase one is still in effect, the car can exit fire phase two regardless of the position of the doors. Set to YES to comply with this requirement.
• MASS 524 CMR FIRE CODE?
• Available only if “FIRE SVCE. CODE” set to “A17.1 - 2000". If set to YES, ASME A17.1-
2000 fire code will conform to Massachusetts 524 CMR requirements. If set to NO, controller will conform to standard ASME A17.1-2000 code.
• ASME A17.1A 2000 ADDENDA
• Set to the appropriate addenda for your jurisdiction. (2005, 2007, 2013, NONE)
• DISABLE DPM ON FIRE PH.2?
• If Yes, Door Position Monitoring is disabled when the car is on In Car Firefighter operation (Fire Phase 2). If No, DPM is not disabled on Fire Phase 2.
• LOW VOLTAGE FIRE SENSORS?
• If the fire sensors on this job use 24V signal levels, set this option to Yes.
• If set to No, the signal level is assumed to be 120 VAC.
• FIRE HAT STATUS?
1
Dynamic/Latch Flashing/Latch Initial.
• Dynamic: Regardless of which fire alarm initiating device (FAID) initiated Fire Phase I operation, whenever the FAID in the elevator machine room or hoistway is activated, the fire hat in the associated car will flash. Otherwise, the fire hat will illuminate solidly unless required by code to flash in response to some other, non-FAID device actuation (for example, battery rescue device, low oil, etc.).
• Latch Flashing: Regardless of which fire alarm initiating device (FAID) initiated Fire
Phase I operation, once the FAID in the elevator machine room or hoistway is activated, the fire hat in the associated car will flash and remain flashing throughout fire service.
• Latch Initial: If the fire alarm initiating device (FAID) that initiated Fire Phase I is located in the elevator machine room or hoistway, the fire hat in the associated car will flash and remain flashing throughout fire service. Otherwise, the fire hat will illuminate solidly and remain so throughout fire service unless required by code to flash in response to some other, non-FAID device actuation (for example, battery rescue device, low oil, etc.). This option should be selected for ASME A17.1-2004/CSA B44-04 and later.
1. A17.1/B44 code edition/addenda or jurisdiction dependent: (A) for ASME A17.1-2004/CSA B44-04 and later, the machine room or hoistway sensor must be the sensor that initiated Fire Phase I for the hat to flash; or (B) for earlier editions of A17.1/B44, the fire hat will flash any time the machine room or hoistway sensor is active, regardless of which device initiated Fire Phase I. Also, some jurisdictions occasionally modify the A17.1/B44 requirements, so please consult with the jurisdictional authorities for additional requirements.
4-18 Manual # 42-02-2P25
Motion 4000
F1: Program Mode
Door Operation Menu Options
• NUDGING?
• Enables Nudging Operation when doors are prevented from closing. During Nudging
Operation, controller will turn ON the NUDG output to signal the door operator to close the doors at reduced speed. The NUDG output will stay ON for the amount of time the Nudging Timer specifies and then cycle off for the same amount of time. This cycle will continue until the doors have fully closed.
The NUDG output can also be used to activate a buzzer. The PHE (Photo Eye) input will be ignored during nudging if the Stuck Photo Eye Protection option has been selected ( See “STUCK PHOTO EYE PROTECTION?” on page 4-19 ). A Safety Edge or
Door Open Button input will stop the doors from closing, but will not reopen the doors fully. Nudging Operation will begin when the Nudging Timer elapses. The Nudging
Timer starts when the regular door timer elapses. ( See “NUDGING TIMER (Range:
10-240 Seconds)” on page 4-24.
)
• STUCK PHOTO EYE PROTECTION?
• When enabled, causes controller to ignore PHE (Photo Eye) input and close the doors after the Nudging Timer elapses if the Nudging option is selected or when the Time
Out of Service Timer elapses, whichever comes first. If the Nudging option is not selected, the PHE input will be ignored when the Time Out of Service Timer elapses.
( See “TIME OUT OF SERVICE TIMER (Range: 15-240 Seconds, or None)” on page 4-
24 for more details.)
If the Stuck Photo Eye Protection option is not selected, a PHE input that is stuck ON will keep the doors open indefinitely.
• SEQUENTIAL DOOR OPER. (F/R)?
• Available only if independent rear doors are present. If set to YES, the front and rear doors of the car will not open at the same time. If the controller receives a front and rear call to the same landing, the car will first open and close the front doors, then open and close the rear doors. The default is to open the front doors first unless the rear doors have already started to open.
• CAR CALL CANCELS DOOR TIME?
• If selected, pressing a car call button when the doors are fully open will cause the doors to start closing. There is one exception. If the car is stopped at a floor, pressing the car call button for that same floor will not cause the doors to close, but will cause the doors to reopen if they are in the process of closing.
• NUDGING DURING FIRE PH. 1?
• If selected, the controller will turn ON the NUDG output while the doors are closing during Fire Phase 1. The NUDG output signals the door operator to close the doors at reduced speed. This is useful for elevators that do not have mechanical safety edges.
During Fire Phase 1, all smoke sensitive reopening devices must be disabled. This includes photo eyes and other devices that use infrared beams. If there are no other reopening devices active, the doors should close at reduced speed.
4
4-19
User Interface
• RETIRING CAM OPTION?
• Select for elevators with retiring cams. Affects the car only when it is sitting at a floor.
Without this option, the controller will wait until the doors are closed and locked before it turns OFF the door close signal. However, if the elevator has a retiring cam, the doors will not be locked until the retiring cam is activated.
If selected, the controller will turn OFF the door close signal when the doors are closed instead of waiting for the doors to be locked. More precisely, the controller will turn
OFF the door close output signal (DCF) when the DCLC (Doors Closed Contact) input is ON or when the DCL (Door Close Limit) input is OFF, instead of waiting for the DLK
(Door Lock) input to turn ON.
• PRE-OPENING?
• If selected, the controller will begin to open the doors just before the car stops at a floor. More precisely, the controller will turn ON the DOF (Door Open Function) output signal when the DZ (Door Zone) input turns ON. Typically, the DZ input first turns
ON when the car is about 3 inches away from the final stopping point. Not recommended for elevators that spend an extended period of time leveling.
• MECHANICAL SAFETY EDGE?
• If selected, Nudging Operation will cycle until the doors are fully closed. Otherwise, the nudging function will operate continuously to comply with code requirements where a door reopening device is not used ( See “NUDGING?” on page 4-19 for more details).
• NUDGING OUTPUT/BUZZER ONLY?
• If selected with the Nudging option, NUDG output will be activated when Nudging
Timer elapses. However, if either the Mechanical Safety Edge or the Door Open button is activated, the doors will stop and reopen fully. If this option is not selected, the doors will simply stop under these circumstances, but will not reopen fully. This option may be useful when only a nudging buzzer is required but actual Nudging Operation is not needed ( See “NUDGING?” on page 4-19 for more details). With this option and the
NUDGING option both set to YES, DOOR CLOSE PROTECTION TIMER ELAPSED faults are not generated.
• D.C.B. CANCELS DOOR TIME?
• When doors are fully open, this option will cancel any pre-existing door time and cause the doors to start closing when the Door Close button is pressed.
• LEAVE DOORS OPEN ON MGS?
• With this option set to yes and the MG Shutdown input active, once the car has stopped at a floor, the doors will remain open instead of cycling closed.
• LEAVE DOORS OPEN ON PTI/ESS?
• With this option set to yes and either the Power Transfer (PTI) input or the Elevator
Shutdown Switch (ESS) input selected and active, once the car has stopped at a floor, the doors will remain open instead of cycling closed.
• NUDGING DURING FIRE PHASE 2?
• If selected, the controller will turn ON the NUDG output while the doors are closing during Fire Service Phase II. The NUDG output signals the door operator to close the doors at reduced speed.
4-20 Manual # 42-02-2P25
Motion 4000
F1: Program Mode
• DIRECTIONAL PREFERENCE UNTIL DLK?
• Causes car to maintain its present direction preference until the doors are fully closed.
Otherwise, direction preference is maintained only until door dwell time expires.
• FULLY MANUAL DOORS?
• Set to YES if doors must be opened and closed manually.
• CONT. D.C.B. TO CLOSE DOORS?
• When set to YES, doors will remain open at a landing until the Door Close button is pressed and held. While the Door Close button is pressed, the doors will continue to close. If the Door Close button is released before the doors have closed fully, the doors will re-open.
• CONT. D.C.B. FOR FIRE PH 1?
• When set to YES, doors will remain open when the car goes on Fire Service Phase I until constant DCB forces them closed.
• MOMENT. D.O.B. DOOR OPENING?
• Used to require momentary pressure on the Door Open Button (DOB) to open the doors. If set to NO, momentary pressure on the DOB is not required to open the doors when the car reaches a landing. The doors open automatically in response to a call.
• MOMENT D.O.B. FOR: (FRONT CALLS/ REAR CALLS/ BOTH CALLS)
• Choose whether front calls, rear calls or both calls need momentary D.O.B.
• FRONT CALLS - Requires that DOB be pressed when the car responds to front door calls.
Rear door calls are not affected.
• REAR CALLS - Requires that DOB be pressed when the car responds to rear door calls.
Front door calls are not affected.
• BOTH CALLS - Requires that DOB be pressed when the car responds to both front and rear door calls.
• MOMENT D.O.B. FOR: (HALL CALLS/ CAR CALLS/ ALL CALLS)
• Choose whether hall calls, car calls, or all calls need momentary D.O.B.
• HALL CALLS - Requires that DOB be pressed when the car responds to hall calls. Car calls are not affected.
• CAR CALLS - Requires that DOB be pressed when the car responds to car calls. Hall calls are not affected.
• ALL CALLS - Requires that DOB be pressed when the car responds to both hall calls and car calls.
• DOORS TO OPEN IF PARKED: (NONE/FRONT/REAR/BOTH)
• If set to NONE, doors remain closed while the car is parked. If set to FRONT, REAR, or
BOTH, the corresponding doors automatically open and remain open while the car is parked. This option is available only if a parking floor is programmed in the Basic Features menu. The BOTH option is not available if the car is programmed for sequential door operation. ( See “SEQUENTIAL DOOR OPER. (F/R)?” on page 4-19.
)
• DOORS TO OPEN ON MAIN FIRE?
• Choices are FRONT, REAR, and BOTH. Determines which door(s) should open once the car has completed a Main Fire return.
4
4-21
User Interface
• DOORS TO OPEN ON ALT FIRE?
• Choices are FRONT, REAR, or BOTH. Determines which door(s) should open once the car has completed an Alternate Fire return.
• LEAVE DOORS OPEN ON CTL?
• When set to YES, and the CTL (car to lobby) input is active, once the car has returned to the lobby the doors will remain open instead of cycling closed.
• LIMITED DOOR RE-OPEN OPTION
• Once the doors begin to close after a door dwell time has expired, if a re-opening device input (PHE or SE) is activated, this option allows the doors to re-open as long as the re-opening device is active. Once the re-opening device is inactive, the doors will immediately begin to close again. Without this option set, in this same case, the doors will re-open fully for a (short door) time and then close.
• REDUCE HCT WITH PHOTO EYE
• Causes a normal hall call time to be shortened to a short door time if a photo eye input is seen.
• LEAVE DOORS OPEN ON EPI
• When set to YES, and EPI (Emergency Power) input is active, once the car returns to the emergency power return floor the doors are left open instead of cycling closed.
• DOORS TO OPEN IF NO DEMAND: (NONE/FRONT/REAR/BOTH)
• When set to NONE, the doors remain closed when the car is at a landing with no demand. When set to FRONT, REAR, or BOTH, the corresponding doors automatically open and remain open when the car is at a landing with no demand. The BOTH option is not available if the car is programmed for sequential door operation. ( See
“SEQUENTIAL DOOR OPER. (F/R)?” on page 4-19 .)
• CONST. PRESS OP. BYPASS PHE?
• Used to indicate if Constant Pressure Operations, such as Independent Service, Attendant Service, or if the Constant Pressure Door Close option is set to YES, should bypass the Photo Eye when the Photo Eye is active and there is a demand to close the doors and move the car. When set to YES, the car will bypass the Photo Eye and nudge the doors closed. When set to NO, the car will not bypass the Photo Eye. The doors will remain open until the Photo Eye is cleared.
• DOOR TYPE IS HORIZONTAL / VERTICAL
• Used to indicate if the doors open horizontally or vertically. When set to vertical, requires constant pressure on the door close button (DCB) to shut the doors when exiting Fire Phase 2 away from the recall floor with Fire Phase 1 active.
• FRONT DOOR MECH. COUPLED? YES/NO
• Set to YES if the front car gate is mechanically coupled to the hallway doors. To satisfy
A17.1-2000 code requirements, this option is used to qualify the HD Redundancy fault when the Retiring Cam Option is set to YES and this option is set to YES. ( See “RETIR-
ING CAM OPTION?” on page 4-20.
)
4-22 Manual # 42-02-2P25
Motion 4000
F1: Program Mode
• REAR DOOR MECH. COUPLED? YES/NO
• Set to YES if the rear car gate is mechanically coupled to the hallway doors. To satisfy
A17.1-2000 code requirements, this option is used to qualify the HDR Redundancy fault when the Retiring Cam Option is set to YES and this option is set to YES. ( See
“RETIRING CAM OPTION?” on page 4-20.
)
• PREVENT DCP TIL DOORS CLOSE?
• When set to YES, the DCP (door close power) output will not be generated until the doors close and a demand is present. For example, if DCP is used to power the retiring cam RC relay, DCP should be asserted only after the doors have fully closed as indicated by the DCL input.
• MOMENT. D.C.B TO CLOSE DOORS? YES/NO
• When set to YES, a momentary push on the door close button is required to close the doors on normal operation.
• Set to NO for normal door operation.
• DOORS TO LATCH DOF? FRONT/REAR/BOTH/NONE
• Maintains the Door Open Function on the selected doors continuously as long as a door closing command is absent.
• DOORS TO LATCH DCF? FRONT/REAR/BOTH/NONE
• Maintains the Door Close Function on the selected doors continuously as long as a door opening command is absent.
• INV. DOOR CLOSE LIMIT? NONE/ FRONT/ REAR/ BOTH
• Set for doors that require inverted door close limit input logic (DCL and/or DCLR).
When set, the DCL and/or DCLR inputs must be active when the doors are closed and inactive when the doors are open.
• FIRE PH2. WITH DOORS CLOSED? Yes/No
• FULLY MANUAL DOORS ONLY: If set to Yes, a car recalled on Fire Phase 1 is allowed to enter Fire Phase 2 with doors closed.
4
4-23
User Interface
Timer Menu Options
• SHORT DOOR TIMER (Range: 0.5-120.0 Seconds)
• Determines length of time doors will stay open after being reopened by Photo Eye,
Safety Edge, or Door Open button.
• CAR CALL DOOR TIMER (Range: 0.5-120.0 Seconds)
• Determines length of time doors will stay open when car stops to service a car call.
• HALL CALL DOOR TIMER (Range: 0.5-120.0 Seconds)
• Determines length of time doors will stay open when car stops to answer a hall call.
• LOBBY DOOR TIMER (Range: 0.5-120.0 Seconds)
• Length of time doors will stay open when car stops to answer either a hall call or a car call at Lobby Floor. Location of Lobby Floor is programmable. ( See “CAR SERVES
REAR/FLR 1? (simplex) / THIS CAR SERVES REAR/FLR 1? (duplex)” on page 4-14.
)
• NUDGING TIMER (Range: 10-240 Seconds)
• Used only if the Nudging option is selected. Door Nudging Operation will begin when
Nudging Timer elapses. Nudging Timer will start when regular door timer elapses.
This timer also determines the ON and OFF cycle time for the NUDG output. ( See
“NUDGING?” on page 4-19.
)
• TIME OUT OF SERVICE TIMER (Range: 15-240 Seconds, or None)
• Used to take a car out of service when it is held at a floor excessively and calls are registered at other floors. Timer starts when a call is registered at another floor. If timer expires before the car closes its doors and begins to move, the car will be placed out of service. Typically, this occurs when doors are held open by continuous activation of photo eye, a call button, or another reopening device. When NONE is selected, no
Time Out of Service timing is performed.
When the timer expires, the Timed Out of Service Indicator on the HC-MPU board will turn ON. The controller will ignore the PHE (Photo Eye) input if the Stuck Photo Eye
Protection option is selected. In duplex or group installations, hall calls assigned to the car will be assigned to another car. When the car closes its doors and begins to move again, it will return to Normal service.
• MOTOR LIMIT TIMER (Range: 1.0 - 6.0 Minutes)
• Timer starts when the controller attempts to move the car and is reset when the car reaches its destination floor. If the timer expires before the car reaches its destination, the controller stops trying to move the car to protect the motor. The car is then shut down. The Motor Limit Timer Indicator (MLT) on the HC-MPU board will turn ON.
• MGR OUTPUT TIMER (Range: 1.0 - 27.0 Minutes)
• Timer starts when car is idle at floor. When timer elapses, the motor/generator is shut down. Upon demand, the motor/generator will be restarted and brought up to readiness before the car can move.
4-24 Manual # 42-02-2P25
Motion 4000
F1: Program Mode
• DOOR HOLD INPUT TIMER (Range: 0-240 Seconds)
• Timer used only if there is a DHLD (Door Hold) input to the controller ( See “Spare
Inputs Menu” on page 4-27 ). A Door Hold Open button is usually connected to this
input. Timer determines how long the doors will stay open when the door hold open button is pressed. The timer is canceled and the doors will begin to close if either the
Door Close button or a Car Call button is pressed. If a Door Hold Key switch (instead of a button) is connected to the DHLD input, timer value should be set to zero so that the doors will close immediately when the switch is turned OFF.
• PARKING DELAY TIMER (Range: 0.0-6.0 Minutes)
• Used only if a parking floor is selected. Timer starts when car is free of call demand.
The car will park after the timer expires.
• FAN/LIGHT OUTPUT TIMER (Range: 5.0-20.0 Minutes)
• Used with the FLO output, this timer sets the amount of time that will pass before the
FLO output is activated to shut off the car light and fan. Time will start when the car becomes inactive. The FLO output is typically connected to a relay that turns OFF the fan and light in the car. This is also used for PI Turned Off if No Demand.
• HOSPITAL EMERG. TIMER UNIT? (Range: MIN - SEC)
• Sets the units for the HOSPITAL EMERG. TIMER to minutes or seconds.
• HOSPITAL EMERGENCY TIMER (Range: 1.0-10.0 Minutes or 1-240 Seconds)
• Sets the amount of time the car will remain at the hospital emergency floor with the doors open before automatically returning to normal service. ( See “HOSPITAL
EMERG. OPERATION?” on page 4-48 .)
• DOOR OPEN PROTECTION TIMER (Range 8 - 30 Seconds)
• Determines how long the door operator will attempt to open the doors. If DOL does not go low within this time, the doors will begin to close.
• CTL DOOR OPEN TIMER (Range: 2.0 - 60.0 seconds)
• Used to specify how long the doors should remain open after car returns to lobby when the CTL (Car to Lobby) input is activated.
• DOOR BUZZER TIMER (Range: 0 - 30 Seconds)
• Determines length of time door buzzer sounds before doors are automatically closed.
• OPN/CLS INTRLOCK TIMER (Range: 050ms - 950ms, 50ms increments)
• Introduces a delay when closing or opening doors are abruptly reversed (i.e., photo eye activation, door button press, etc.). This may be required if the door operator is sensitive to such reversal due to de-bounce capability.
• Set to NONE if unnecessary.
• FIRE PH1 RECLOSE TIMER (Range: Disabled or 1 - 120 seconds)
• If set to a value other than NONE, the doors will close after the set number of seconds following a Fire Service Phase 1 recall. Doors may be opened using in-car or hall door open buttons.
Gongs/Lanterns Menu
• MOUNTED IN HALL OR CAR?
4-25
4
User Interface
• Determines when lanterns and gongs are activated - as the car slows into the floor for hall mounted fixtures or after the door lock opens for car mounted fixtures. If both types of lanterns are used, the Hall option is recommended.
• DOUBLE STRIKE ON DOWN?
• Causes lanterns and gongs to double-strike if car direction preference is down.
• PFG ENABLE BUTTON? (Passing Floor Gong Enable Button)
• If selected, the Passing Floor Gong will operate only when initiated by a momentary pressure button. Once initiated, the Passing Floor Gong will operate for the current direction of travel but will be rendered inoperative when the car reverses direction.
The PFGE spare input should also be selected if this option is turned ON. ( See “Spare
Inputs Menu” on page 4-27 .)
• EGRESS FLOOR ARRIVAL GONG? / MAIN EGRESS FLOOR #
• To program this option (Michigan Code), set one of the spare outputs to EFG. Then set
EGRESS FLOOR ARRIVAL GONG? to NO (no gong) or press S to select the floor number where the gong should activate (after the door lock opens). If S is pressed, the display will read MAIN EGRESS FLOOR #1. Press S until the desired floor number is displayed.
• CAR LANTERN DOOR FULLY OPEN?
• If no, the car lantern will come on when the doors begin to open and go off when they are fully closed. If yes, the car lantern will come when the doors are fully open and go off when they begin to close.
4-26 Manual # 42-02-2P25
Motion 4000
F1: Program Mode
Spare Inputs Menu
The first 10 spare input terminals are located on the HC-CTL-2 board. Additional spare inputs are available on each HC-UIO Universal Input/Output board. Please refer to “HC-UIO Universal Input/Output Board” on page 5-56 . If your installation uses ICE-COP-2 or MC-CPI serial control panel boards in the car, spare inputs are also available on these boards and will show up in the Spare Inputs menu as inputs to COP-Fx or CPI-F/CPI-Fx, COP-Rx or CPI-R depending upon the car control panel and rear door board configuration. If the job has ICE-COP-2 or MC-
CPI boards, unused spare inputs to these boards must be set to NOT USED. If controller software is upgraded in the field, it is very important to check programmable car panel interface board inputs and verify unused inputs are set to NOT USED.
“Spare” inputs are inputs that can be assigned to a physical board connection through software, allowing great flexibility in configuring a controller to meet specific requirements.
Viewing and Assigning Spare Inputs
Virtually every elevator installation requires some inputs or outputs that are not “standard.”
Perhaps because one site has elevator security requirements while another does not or uses a switch to detect when the machine brake is picked, etc. To accommodate these features without requiring custom software, MCE defines many spare inputs and outputs in standard software that can be assigned to a physical connector and used at need. Jobs are well defined and tested before shipment, allowing MCE to assign, label, and show in the job prints these non-standard inputs or outputs in most cases.
To view assigned spare inputs:
1. Put the car on Inspection and set Function switch F1 up (all others down).
2. Press the N button to cycle through menus until you see “Spare Inputs Menu,” then press the S button to select that menu.
3. The display will show the first “spare” (assignable) connector on the HC-CTL-2 board and the input assigned there.
4. Press the N button to cycle through available assignable connectors in your system and the input, if any assigned.
5. If you want to assign an input to an unused connector, cycle to the desired connector then begin pressing the S button to cycle through available input signals in the order they are shown in the table below. (You can press and hold S to continuously move through the inputs in their numeric/alphabetic order.)
6. When the desired input is shown, press N (it also may be held to cycle) until the Spare
Inputs menu is completed and the display again shows the top level menus. Press N until the Save screen is displayed. Save your changes by pressing S when prompted.
Note
After selecting an input, you can also press N and + buttons together to go immediately back to the top level menus, then continue to press N until the Save menu is displayed.
4
4-27
User Interface
Table 4.6 Spare Inputs Menu Options
2AB
ABI
ACI
ALI
ALV
API
ARST
ATS
AUTO
AXR
BAB
BPCR
BPS
BSI
CBF
Spare Inputs Menu Options
2AB relay coil monitoring input - If the 2AB relay is ON, the R2AB input will be OFF. R2AB must always be the opposite of 2AB. If not, the 2AB redundancy fault is logged and the elevator shuts down.
Alarm Bell Input - There are three conditions that will initiate a warning. First, if the Alarm
Button is pressed when the car is stopped outside of a door zone. Next, if the Alarm Button is pressed four times in 60 seconds without the car moving. Lastly, if the car fails to complete an LSA movement check after being idle for 10 minutes at a landing. All of these failures will alert the monitoring station.
Reserved for future use.
Alternate Lobby Input - The ALI input is used to substitute the Main Lobby floor value with an Alternate Lobby floor value. When the ALI input is activated, the lobby value is taken not from the LOBBY parameter, but from the ALTLBY parameter. The ALTLBY floor must be specified before using the ALI input.
Alive Input - Used in a duplex configuration; received from the other car. If the input is on, it indicates the other car is powered. Used in emergency power applications.
Alternate Parking Input - Used to determine whether to park at the primary or alternate parking floor. When API is low, the car will park at the primary floor. When API is high, the car will park at the alternate floor.
Alarm Reset Acknowledge input. Reset an alarm initiated by the ABI input or by an open safety string. When active, will not allow the DISL, TDISL, and DISB outputs to operate.
Attendant Service Input - When active, the car is controlled by an attendant (starting, stopping, direction of travel). Doors open automatically when car is stopped at a landing. Doors close only with constant pressure on the door close button, car call button, or a car direction button (UPI or DNI). Attendant may cause the car to bypass all hall calls by activating the
“non-stop button” (NSI). The ATSOPT option must also be enabled. While the car is on
Attendant Service, all Load Weigher Functions (LLW, HLW, OLW) are cleared.
Emergency Power Auto Selection Input - Duplex operation. When activated, one of the cars is automatically chosen to run on emergency power. The dispatcher makes this decision, and will choose itself if able to run. The other car will be chosen if the dispatcher is unavailable to run. See also the ALV input.
Auxiliary Reset Input - Used to reset redundancy error conditions. Typically connected to a push button.
Monitoring input for BAB relay coil. If BAB relay is ON, RBAB input will be OFF. RBAB must always be the opposite of BAB. If not, a BAB redundancy fault is logged and the elevator shuts down.
Backup Power alerting input from the MCE TAPS Traction Auxiliary Power Supply. Lets the elevator know that it is receiving backup power so that correct operating parameters for this situation may be employed. (From the TAPS UPS-1 output)
Brake Pick Switch input. The brake pick switch/sensor monitors the position of the machine brake. Three seconds after a run is initiated, the controller checks the status of this input to see that the BPS is deactivated (low), indicating the brake is fully picked. If the brake is picked, the controller stops monitoring the input for that run. If the brake is not picked, the controller continues to monitor throughout the run and, if the brake does not pick, a fault is reported and the car will be shut down at the end of that run. If the controller detects that the brake is not fully picked initially but picks during the run and this behavior continues for three consecutive runs, a fault is reported and the car shut down after the third run.
Building Security Input - Used to activate MCE Security when the BSI SECURITY KEY, in the
Extra Features Menu (
Please refer to “Building Security Menu” on page 4-56 ), is set to
ENABLED.
Car call Bus Fuse Blown - Input used to monitor the car call bus power. If power is lost, typically caused by a wiring problem or an open fuse, the input goes low and is thereby activated. The error message CAR CALL BUS IS DISCONNECTED is displayed.
4-28 Manual # 42-02-2P25
Motion 4000
F1: Program Mode
Table 4.6 Spare Inputs Menu Options
CCC
CEPFG
CEVA
CNP
CR1-CR8
CR1R-CR8R
CRO
CTF
CTL
CTST
CWI
DCBR
DCL
DCLC
DCLR
DFI
Spare Inputs Menu Options
Car Calls Cancel Input - Activation will unconditionally cancel car calls. Because this input has no logical software qualification, necessary qualification must be done in external circuitry (e.g., disable the signal feeding this input when on Fire Service Phase II).
When active, enables passing floor gong on CE fixture. Non-latching as opposed to PFGE which latches until direction reversal.
When active, enables floor announcements on CE fixture. Always active if CEVA is not programmed. When CEVA is not active, floor announcement on CE fixture is disabled.
Contactor Proof Input - Monitors the normal condition of motor/start contactors and will shut the car down if the contactor fails to make or break contact properly. Generates a Contactor Proofing Redundancy Failure message.
Car call card reader. Used to enable car call registration to secured front landings. Bypassed during fire service Phase II operation.
Car call card reader, rear. Used to enable car call registration to secured rear landings.
Bypassed during fire service Phase II operation.
Car call card reader override. When active, car calls may be registered without restriction.
Car to floor Input - Used to return the car to a previously selected floor. The return floor is selected using CAR TO FLOOR RETURN FLOOR in the EXTRA FEATURES MENU. When activated, this input will cause the car to immediately become non-responsive to hall calls, and will prevent registration of new car calls. Depending upon the setting of Retain Calls, car calls registered prior to activation of the CTF input will be serviced before, or retained for
service after, recall. Please refer to “RETAIN CALLS ON CTL / CTF?” on page 4-51.
Car-to-Lobby Input - Used to return the car to the lobby floor. When activated, this input will cause the car to immediately become non-responsive to hall calls, and will prevent the registration of new call calls. Depending upon the setting of Retain Calls, car calls registered prior to activation of the CTL input will be serviced before, or retained for service after,
recall. Please refer to “RETAIN CALLS ON CTL / CTF?” on page 4-51.
Capture for Test Input - Causes the car to bypass Hall Calls and disable gongs. Car Calls will still be answered and allowed to be entered.
Counterweight Input. Used in conjunction with EDS and EQI inputs for ANSI and modified
California Earthquake Operation. This input tells the computer that the counterweight has moved horizontally beyond normal limits. Activation of this input while a car is in flight will cause an emergency stop. When the car moves to a landing after stopping, it will move in a direction away from the counterweight (historical activity of EDS input determines which direction). For ANSI, continuous activation of CWI is monitored (this information is used to determine if the car will be allowed to run “normally” at reduced speed). For California, CWI is monitored to determine if the car will be allowed to run on fire service or hospital emergency service.
Please refer to “ASME EARTHQUAKE/CALIF EARTHQUAKE” on page 4-51 .
Door Close Button Rear. Used to initiate closing or re-closing of the rear door.
Door Close Limit Input - Associated switch opens when the car door is approximately 1 inch from being closed, causing input to go low. Opening the door approximately 1 inch will reapply power to the DCL input as the switch makes up.
Doors Closed Contact Input - When active (high), indicates doors are closed on Retiring
Cam (RETCAM) jobs. Since the doors do not lock until the car is ready to move, the computer needs to see this input to know when the doors are closed.
Doors Closed Contact Input Rear - When active (high) indicates rear doors are closed on
Retiring Cam (RETCAM) jobs. Since the doors do not lock until the car is ready to move, the computer needs to see this input to know when the doors are closed.
Drive Fault Input - The fault output of the drive may be connected to this input for drive fault detection and recording.
4
4-29
User Interface
Table 4.6 Spare Inputs Menu Options
DHLD
DHLDR
DLI
DLS
DLSR
DNI
DOBR
DOL
DOLR
DPM
DPMR
DRON
DSTI
DSTIC
DSTICR
DSTIR
DZRX
DZX
ECRN
EDS
EDTLS
Spare Inputs Menu Options
Door Hold Input - Activates DHO output to open and hold doors for the period the input is active plus the DLHD timer value. Please refer to “DOOR HOLD INPUT TIMER (Range: 0-240
Seconds)” on page 4-25 . Pressing the door close or a car call button will cancel DHLD time.
Fire Service disables the input.
DHLD for Rear Doors - See description of DHLD.
Dispatch Load Input - A load weigher is typically connected to this input. When the input is activated, door dwell time will be curtailed when the elevator has an up direction at the
Lobby Floor.
Door Lock Sensor Input - Monitors the state of the contacts in the landing door lock string.
Power will be present on the DLS input when all the landing doors are closed and locked.
Used for CSA code with Door lock bypass requirement. NOTE: It is mandatory to have the
DCL input programmed when DLS is used.
Door Lock Sensor Input (Rear) - See DLS.
Down Input (Attendant Service) - Used by attendant during Attendant Service operation to establish a direction preference. Pushing the “DOWN” button in the car activates the input, causing the computer to generate SDA (down direction preference) and DSHT (door shortening) to close the doors.
Door Open Button Rear. Used to initiate opening or re-opening of the rear door.
Door Open Limit input - Active high input from door open limit switch.
Door Open Limit Rear input - Active high input from rear door open limit switch.
Front Door Position Monitoring - Switch makes when car door is approximately 1 inch from being closed, activating (high) DPM input. Opening the door approximately 1 inch removes power from DPM as the switch opens.
Rear Door Position Monitoring - See DPM.
Drive On Input. This input is used to indicate to the microprocessor that the drive is ON and
Ready.
Door Stop Input - If doors are opening or closing when this input is detected, door operation will stop. DOF and DCF/DCP flags are cleared. If the DSTI input is momentary, the doors may be opened or closed using DOB or DBC inputs. If the DSTI input is constant, DOB or
DBC will not override it. This operation will not function in Fire Service, Inspection, or Independent service.
Door Stop Input Complement. Active low. (See DSTI.)
Door Stop Input Complement Rear. Active low. (See DSTI.)
DSTI for rear doors - See DSTI.
Programmable auxiliary rear door zone input. Can be assigned to SPIN-1 through SPIN-6 on
HC-CTL-2 board.
Programmable, auxiliary front door zone input. Can be assigned to SPIN-1 through SPIN-6 on HC-CTL-2 board or to an HC-UIO board and used in place of DZF input on HC-CTL-2 board.
Emergency Car Freeze Input - Used during emergency power to immobilize a car while other cars are returned to the assigned landing. The EPR input must also be programmed to select the car to run.
Earthquake Direction Switch. This input is activated when the car is in line with the counterweight. When the controller receives the momentary EDS input, it will note in what direction the car was traveling to determine the position of the counterweight relative to the car
(counterweight above car, or counterweight below car). This position status is used to safely move the elevator in the event of an earthquake.
Earthquake Direction Terminal Limit Switch - When active, indicates that the car is above the counterweight. When inactive, indicates the car is below the counterweight.
4-30 Manual # 42-02-2P25
Motion 4000
F1: Program Mode
Table 4.6 Spare Inputs Menu Options
ELFI
EMSC
EMSH
EPI
EPR
EPRUN
EPSTP
EQI
ESS
FCCC
FCHLD
FCOFF
FLTM
FRAA
FRAON
FRBYP
FRHTW
FRMR
FRON
FRON2
Spare Inputs Menu Options
External Latching Fault. Multi-purpose input used to assert a fault that must be manually reset to clear. Once latched, input will cause the car to stop at the next possible floor and shut down. Input will persist over a power cycle. Must be manually reset using the fault reset button. Event log will display “External Latching Fault Input.”
Emergency Medical Service (EMS) in-car switch input - When activated, places the car on
EMS phase two operation (car calls may be registered).
Emergency Medical Service (EMS) hallway switch input - When activated, recalls car to the designated EMS floor.
Emergency Power Input - Indicates loss of commercial power when input goes low.
Please refer to “EMERGENCY POWER OPERATION?/EMERGENCY POWER RETURN FLOOR” on page 4-44 .
Emergency Power Return Input - Used during emergency power. When activated, car is lowered to the recall floor. The ECRN input must also be programmed.
Emergency Power Run Input - Wired to the “Run” switch for emergency power car selection.
The “dispatcher” in a duplex system will reference this input when deciding which car should be allowed to run on emergency power. Each car must have its own EPRUN input. Whichever is selected will be chosen to run on Emergency Power Phase II.
Emergency Power Stop Input - When activated before the lowering sequence, holds the car immobilized, preventing the emergency power transition timer from running. Used to coordinate emergency power operation with other systems.
Earthquake Input. When this input is activated, the car will proceed to the next floor at reduced speed and shut down with doors open. The car will remain shut down until EQI is deactivated again for California jobs. For ANSI jobs, the car will go into reduced speed mode after 30 seconds (EQN timer) if the CWI input is not activated.
Elevator Shutdown Input - When activated, the car stops at the next landing in the direction of travel, cycles the doors, and shuts down. Bypassed by Fire, Inspection, Independent,
Attendant, and Hospital service.
Fire Phase II Call Cancel Button Input - When activated during Fire Phase II operation, cancels all registered car calls.
Fire Phase II Door Hold Input - When activated during Fire Phase II operation, fully open doors will not be allowed to close. The “HOLD” position of the In-car Fireman Service switch is wired to this input.
Fire Phase II OFF Input - Used to take the elevator out of Fire Phase II service. The “OFF” position of the In-car Fireman Service switch is wired to this input.
TAPS Fault input. Alerts the controller if the Traction Auxiliary Power Supply unit has faulted.
Fire Phase I Second Alternate Input - Required by Detroit fire code. When activated, initiates emergency return to the second designated alternate floor (FRA must also be active).
The alternate fire return floor sensor should activate this input.
Fire Phase I Alternate Switch ON Position Input - This fire service switch input is second in priority to the main switch input (FRON) but will override the sensor inputs. When the input is ON, the car will return to the alternate fire floor.
Fire Phase I Switch BYPASS Position Input - When activated, causes the system to ignore the fire sensors (restoring normal fire service status if the fire service switch is not active) and unlatches the current fire sensor status.
Hoistway Fire Sensor - (Normally high) Deactivating this input initiates recall to the main fire floor and causes the FWL output to flash.
Machine room fire sensor - (Normally high) Deactivating this input initiates recall to the main fire floor and causes the FWL output to flash.
Fire Phase 1 Switch ON Position Input - When activated, places the system in Fire Service
Phase I operation. The “ON” position of the fire recall switch is typically wired to this input.
Fire Phase 1 Switch ON Position Input (additional input - same as FRON).
4
4-31
User Interface
Table 4.6 Spare Inputs Menu Options
FRSA
FRSM
GOV
GS
GSR
HBF
HCC
HCR1 - 8
HCR1R-8
HCRO
HDCB
HDCBR
HDOB
HDOBR
HDSTI
HDSTIR
HEATD
HIND
HLI
HML
HOSP
Spare Inputs Menu Options
Alternate Fire Service - Normally active input. When this input goes low, Alternate Fire Service operation is initiated and the FWL output (Fire Warning Light) will flash.
Main Fire Service - Normally active input. When this input goes low, Main Fire Service operation is initiated and the FWL output (Fire Warning Light) will flash.
Governor switch input.
Gate Switch Input - Makes up when the car door is approximately 1 inch from fully closed.
With the car door closed, there should be power on the GS input. This input is used for CSA door lock bypass and redundancy logic. NOTE: It is mandatory to have the DCL spare input programmed whenever GS is used.
Gate Switch Rear Input - Indicates the rear car gate is closed. Used for CSA door lock bypass and redundancy logic.
Hall Call Bus Fuse Blown - Input used to monitor the hall call bus power. If power is lost, typically caused by a wiring problem or an open fuse, the input goes low and is thereby activated. The error message HALL CALL BUS IS DISCONNECTED is displayed and if the WLD input is programmed but not activated, the car goes into Wild (emergency dispatch) operation.
Hall Call Cancel. When activated, all hall calls are canceled.
Hall Card Reader Inputs for front landings. Used to enable registration of front hall calls on secured floors.
Hall Card Reader Inputs for rear landings. Used to enable registration of rear hall calls on secured floors.
Hall Card Reader Override input. When active, causes the car to bypass Per Floor Hall Card
Reader security inputs. Hall Calls are permitted without enabling Hall Card Reader inputs.
Hall Door Close Button. When activated, initiates door closing for front door. Disabled during fireman operation, Fire Phase II.
Hall Door Close Button. When activated, initiates door closing for rear door. Disabled during fireman operation, Fire Phase II.
Hall Door Open Button. When activated, initiates door opening for front door. Disabled during fireman operation, Fire Phase II.
Hall Door Open Button. When activated, initiates door opening for rear door. Disabled during fireman operation, Fire Phase II.
Hall Door Stop Input. When activated, stops front door movement until door open or door close button is pressed. Disabled during fireman operation, Fire Phase II.
Hall Door Stop Input Rear. When activated, stops rear door movement until door open or door close button is pressed. Disabled during fireman operation, Fire Phase II.
Heat Detector Input - Detroit Fire Code. Connected to a heat detector in the machine room and used to stop the car at the next floor and open the doors (same as PTI). Once the doors are fully open, the HDSC spare output is turned off indicating it is okay to remove power from the controller and activate machine room sprinklers.
When active, the car will bypass all hall calls, answer existing car calls but not allow additional car calls to be registered. When calls are satisfied, the car will return to the lobby floor and enter Independent service automatically.
Heavy Load Input - Indicates car is loaded to a point at which it should no longer accept hall call assignments (heavy load bypass). A “discrete” load weigher contact is typically wired to this input, usually indicating that the load is 75%-80% of full load.
Home Landing Input - Used with the primary parking feature to determine whether the car will park or not. The HLSOPT option must also be enabled.
In-car Hospital Service Switch Input - Initiates Hospital Service Phase 2 operation. Typically wired to a keyed hospital service switch located inside the car. Upon activation, the car will accept a call for any floor and proceed nonstop to that floor after the doors close. Deactivation restores normal operation of the car. Please refer to “HOSPITAL EMERG. OPERATION?” on page 4-48 .
4-32 Manual # 42-02-2P25
Motion 4000
F1: Program Mode
Table 4.6 Spare Inputs Menu Options
ICPD
ICPU
INA
INSDN
INSUP
INT
IRCOF
IRCOR
LD
LLI
LSR
LU
LWB
MGS
MNO
NSI
OVL
OVL2
PFGE
PHE2F
Spare Inputs Menu Options
In Car Inspection Down Direction. Intended for a car panel inspection direction button input.
In Car Inspection Up Direction. Intended for a car panel inspection direction button input.
Monitoring input for the INAX relay coil.
Inspection Down Input - Indicates intent to move down while on Inspection operation.
Inspection Up Input - Indicates intent to move up while on Inspection operation.
Intermediate speed input.
Front Infrared Cutout - Normally active. When this input goes low, the infrared detector signal is ignored for the front door only and the door will always close at reduced torque and speed, i.e., nudge closed unless the door requires a constant door close button signal to close. In this case the door will close at full speed.
Rear Infrared Cutout - Normally active. When this input goes low, the infrared detector signal is ignored for the rear door only and the door will always close at reduced torque and speed, i.e., nudge closed unless the door requires a constant door close button signal to close. In this case the door will close at full speed.
Level Down.
Light Load Input - When activated the elevator will only allow the number of car calls specified by the Light Load Car Call Limit parameter to be registered. If more are registered, all car calls are canceled. A discrete load weigher contact is typically wired to this input, indicating that a very minimal passenger load exists in the car. Please refer to “LIGHT LOAD
WEIGHING? / LIGHT LOAD CAR CALL LIMIT” on page 4-44 .
Landing System Redundancy Input - Redundancy checking. Monitors the door zone (DZ) level down (LD) circuits. On any run between floors, the LSR input should go low at least once. If, however, the DZ sensor has failed closed, power will be present continuously on the LSR input and the car will not be permitted to restart. “LANDING SYSTEM REDUNDANCY
FAILURE” will be displayed on the LCD. If either the LU or LD sensors fail closed, the controller will not permit the car to restart.
Level Up.
Load Weigher Bypass - Used to bypass load weigher inputs (LLI, HLI, OVL and DLI).
When the MGS input is activated, all car calls are immediately canceled (hall calls will be reassigned, if possible) and the elevator will return to the specified floor, cycle the doors, and be removed from service. This operation is overridden by fire service and other special operations.
Manual Override. When activated, automatic lowering is overridden. The car will recall to the next available landing and complete the recall process.
Non-Stop Input (Attendant Service) - Activation causes the car to bypass all hall calls. The input is enabled only when the car is on Attendant operation.
Overload Input - While the car is stopped at a landing with the doors open, activation of this input indicates there is too much weight in the car. Doors will be held open until the overload condition is cleared and the input goes low. Fire Service will bypass OVL.
Overload 2 Input - While on Fire Phase II, when the car is stopped at a landing with the doors open, activation of this input indicates there is too much weight in the car. Doors will be held open until the overload condition is cleared and the input deactivated (ANSI A17.1-
2000 fire code only).
Passing Floor Gong Enable Input - Used mostly on New York City jobs. Normally there is not an output from the PFG. When this input is momentarily activated, there will be a PFG output as the car passes a floor until the elevator reverses direction (also referred to as “S” button). Please refer to “PFG ENABLE BUTTON? (Passing Floor Gong Enable Button)” on page 4-26 .
Second photo eye input for front doors. Same function as PHE. Required when two PHE inputs are required for cycle testing. PHE and PHE2F must activate simultaneously to pass the cycle test.
4-33
4
User Interface
Table 4.6 Spare Inputs Menu Options
Spare Inputs Menu Options
PHE2R
PHER
PHERX
PHEX
PITFLD
PTI
PTIC
Power Transfer Input - When activated, causes the car to stop at the next landing in the direction of travel, open the doors (in accordance with the “LEAVE DOORS OPEN ON PTI/
ESS?” parameter) and shut down. Used when transferring from normal to emergency power
(testing), emergency to normal power, as the battery or charger fault input from the video rescue system, and/or the overspeed governor slow down switch.
Note: The PTI input may be used as a general elevator shut down input in a variety of circuits. Please refer to the job prints for details when this input is found to be active.
Complementary PTI Input - Provides reverse logic for the PTI function. PTI operation is initiated when this input goes low.
Redundancy monitoring input from the 2AB relay contact. (See description of 2AB input.)
R2AB
R5, R4, R3, R2 Floor Encoding Inputs - Required for absolute floor encoding. NOT USED.
R2L
Redundancy 2L bus. Used to monitor the normally closed contact of an additional 2L relay.
RBAB
RDLSR
Second photo eye input for rear doors. Same function as PHE. Required when two PHE inputs are required for cycle testing. PHER and PHE2R must activate simultaneously to pass the cycle test.
Programmable, auxiliary photo eye input, rear. May be assigned to any spare input on HC-
CTL-2 or HC-UIO boards.
Programmable, auxiliary photo eye input, rear. May be assigned to SPIN1 - SPIN6 on HC-
CTL board or to an HC-UIO board and used instead of the PHER input on HC-RDR board.
Programmable, auxiliary photo eye input, front. May be assigned to any spare input on HC-
CTL-2 or HC-UIO boards and used instead of the PHE input on the HC-CTL-2 board.
Pit Flood. Activated by pit flood sensor. When activated, the car recalls to the lowest landing above flood level, after which it returns to normal service without serving the inaccessible floors. Renders the floors set in the Extra Features menu “# of flrs below floor level” inaccessible. Fire, Parking, and Emergency floors, if below flood level, will be automatically set to the first available landing above floor level.
REO
REOA
REVD
RGS
Redundancy monitoring input for the BAB relay contact. (See description of BAB input.)
Rear Door Lock Relay Redundancy input (CSA Redundancy) - Monitors the state of the two
DLSR relays. Activated if either relay is “picked” (a normally open contact from one relay is wired in parallel with a normally open contact from the other relay to feed this input). Logic compares the state of the RDLSR input with the state of the DLSR input (the DLSR input monitors the string of actual door lock contacts) to see if one of the two DLSR relays has failed in the “picked” mode (if DLSR=0 and RDLSR=1, a failure is declared).
Re-Open Input - Houston fire code requires that doors close after completing a Fire Phase I return. A key switch in the hallway connected to this input is used by the fire person to reopen the doors.
Re-Open Input Alternate - Houston fire code requires that doors close after completing a
Fire Phase I return. A key switch in the hallway connected to this input is used by the fire person to reopen the doors at the Alternate recall floor.
Reverse Direction input from the MCE TAPS Traction Auxiliary Power Supply unit. (From
TAPS Rev output)
Redundancy Gate Switch (front) - Monitors the state of the two GS relays. Activated if either relay is “picked” (a normally open contact from one relay is wired in parallel with a normally open contact from the other relay to feed this input). The logic compares the state of the
RGS input with the state of the GS input (the GS input monitors the actual car gate contact) to check if one of the two GS relays has failed in the “picked” mode (if GS=0 and RGS=1, a failure is declared).
4-34 Manual # 42-02-2P25
Motion 4000
F1: Program Mode
Table 4.6 Spare Inputs Menu Options
Spare Inputs Menu Options
RGSR
RINAX
RUN/A/B
SAB
SAFC
SAFH
SE
SER
SIMP
STARTIN
STDX
STUX
STOP
SWG
UDF
UFL
Redundancy Gate Switch (rear) - Monitors the state of the two GSR relays. Activated if either relay is “picked” (a normally open contact from one relay is wired in parallel with a normally open contact from the other relay to feed this input). The logic compares the state of the RGSR input with the state of the GSR input (the GSR input monitors the actual rear car gate contact) to check if one of the two GSR relays has failed in the “picked” mode (if
GSR=0 and RGSR=1, a failure is declared).
Redundancy monitoring input for the INAX relay contact.
Active when car is selected to run on emergency power. A and B are used for duplex.
Sabbath Operation Input - Selects Sabbath Operation in which the car will move through the hoistway, stopping at landings that are programmed in the Extra Features Menu.
Car safety string input.
Hoistway safety string input.
Safe Edge Input. When active, doors may not close.
Safe Edge Input, Rear. When active, rear doors may not close.
Simplex Input - Activation causes a duplex car to behave as a simplex. The car will respond to hall calls registered on its own call circuitry, will not accept hall calls assigned to it by another controller, and will perform its own parking function independently.
Start Input - Used for the START position of the three position Fire Phase II switch for Australian jobs. Causes the front and rear doors to close. The car will not proceed to answer car calls during Fire Phase II until the STARTIN input has been activated.
Programmable, auxiliary step down input. May be assigned to SPIN1 - SPIN6 on HC-CTL-2 board or to an HC-UIO board and used instead of STD input on HC-CTL-2 board.
Programmable, auxiliary step up input. May be assigned to SPIN1 - SPIN6 on HC-CTL-2 board or to an HC-UIO board and used instead of STU input on HC-CTL-2 board.
When active, the car will immediately stop as long as the input is active or until the input is bypassed and the car is commanded to move.
Swing Input. When active will disconnect from the group and act as a simplex, responding
to calls from its independent riser. Disable Local Hall Calls, page 4-16 , must be set to NO.
Up and Down direction relay fault input.
Up Final Limit Input - This is a latching input that monitors the up final limit. Deactivation of this input will shut the elevator down and require a manual reset by toggling the Inspection switch.
UPI
WLD
Up Input (Attendant Service) - Used by an attendant during attendant service operation to establish a direction preference. Pushing the “UP” button in the car will activate this input, causing the computer to generate SUA (up direction preference) and DSHT (door shortening) to close the doors.
Emergency Dispatch Input - Causes Wild operation (emergency dispatching) to be disabled.
Created to allow building personnel or elevator maintenance personnel to disable emergency dispatching on one or more cars in a multi-car system. For example, if the dispatcher of an 8-car group were to fail, the building may only want 3 cars to run on “wild operation”.
The remaining 5 cars would be inhibited from running on “wild operation” by activating the
WLD input for each.
WPIA - WPIH Bracelet Security (Wandering Patient Security) inputs. These inputs work in conjunction with the WPIA Landing/Side (opening) option in the Extra Features menu. Landing and side options must be set for each WPIx input programmed. When a WPIx input is activated, hall calls to the programmed landing and side associated with the input will be disabled. If the elevator is already located at that landing with the doors open, it will be prevented from leaving that landing and will shut down. (AKA Infant Abduction Security)
4
4-35
User Interface
Spare Outputs Menu
The first four spare output terminals are located on the HC-CTL-2 board. Additional spare outputs are available on each HC-UIO Universal Input/Output board. Please refer to “HC-UIO
Universal Input/Output Board” on page 5-56 . If your installation uses ICE-COP-2 or MC-CPI serial control panel boards in the car, spare outputs are also available on these boards and will show up in the Spare Outputs menu as outputs from COP-Fx or CPI-F/CPI-Fx, COP-Rx or CPI-
R depending upon the car control panel and rear door board configuration. If the job has can panel interface boards, unused spare outputs from these boards must be set to NOT USED. If controller software is upgraded in the field, it is very important to check programmable CPI board outputs and verify unused outputs are set to NOT USED.
“Spare” outputs are outputs that can be assigned to a physical board connection through software, allowing great flexibility in configuring a controller to meet specific requirements.
Viewing and Assigning Spare Outputs
Virtually every elevator installation requires some inputs or outputs that are not “standard.”
Perhaps because one site has elevator security requirements while another does not or uses a switch to detect when the machine brake is picked, etc. To accommodate these features without requiring custom software, MCE defines many spare inputs and outputs in standard software that can be assigned to a physical connector and used at need. Jobs are well defined and tested before shipment, allowing MCE to assign, label, and show in the job prints these non-standard inputs or outputs in most cases.
To view assigned spare outputs:
1. Put the car on Inspection and set Function switch F1 up (all others down).
2. Press the N button to cycle through menus until you see “Spare Outputs Menu,” then press the S button to select that menu.
3. The display will show the first “spare” (assignable) connector and the output assigned there.
4. Press the N button to cycle through available assignable connectors in your system and the output, if any assigned.
5. If you want to assign an output to an unused connector, cycle to the desired connector then begin pressing the S button to cycle through available output signals in the order they are shown in the table below. (You can press and hold S to continuously move through the outputs in their numeric/alphabetic order.)
6. When the desired output is shown, press N (it also may be held to cycle) until the Spare
Outputs menu is completed and the display again shows the top level menus. Press N until the Save screen is displayed. Save your changes by pressing S when prompted.
Note
After selecting an output, you can also press N and + buttons together to go immediately back to the top level menus, then continue to press N until the Save menu is displayed.
4-36 Manual # 42-02-2P25
Motion 4000
F1: Program Mode
Table 4.7 Spare Outputs Menu Options
702-709
702R-709R
801-808
801R-808R
900
ABZ
AFFS
ATSFO
BOTTOM
CARCOM
CCDE
CCT
CD
CEPR
CFLT
CGED
CGEDR
CGEU
Spare Outputs Menu Options
Front Down Hall Call indicators. Typically used for hall gongs or chimes and activated as the elevator levels into the associated landing. See drawings package. Do not use if a dedicated HC-UIO board is used for Hall Call Indicators.
Rear Down Hall Call indicators. Typically used for hall gongs or chimes and activated as the elevator levels into the associated landing. See drawings package. Do not use if a dedicated HC-UIO board is used for Hall Call Indicators.
Front Up Hall Call indicators. Typically used for hall gongs or chimes and activated as the elevator levels into the associated landing. See drawings package. Do not use if a dedicated HC-UIO board is used for Hall Call Indicators.
Rear Up Hall Call indicators. Typically used for hall gongs or chimes and activated as the elevator levels into the associated landing. See drawings package. Do not use if a dedicated HC-UIO board is used for Hall Call Indicators.
Audible Car Call Registered Output - Generated by registration of a car call. Used to comply with specific handicap (barrier-free) codes that require an audible acknowledgment of car call registration.
Attendant Service Buzzer Output - Generated momentarily when a hall call button is pushed while the elevator is on attendant operation. Used for an in-car buzzer to alert the attendant.
Available For Fire Service output. Normally high, will go low if one of the below is true:
Car out of service.
Car is on Inspection.
Car is on Test mode.
Car on hospital service and fire does not bypass hospital.
Car on EMS service and fire does not bypass EMS.
Active when car is on Attendant Service.
Bottom landing output. Activates when the car reaches the bottom landing. Used to facilitate load weigher calibration.
Active when car to car communications are good.
Car Call Disconnect Enable Output - Comes on when car calls are canceled during photoeye anti-nuisance operation.
Car Call Time Flag Output - Represents the state of the CCT flag. Activated when a car call is canceled and deactivated when the door dwell time elapses (or is canceled by pressing a car call or door close button).
Car Done Returning on Emergency Power Output - Active when the car has finished returning on emergency power or when it is determined that the car cannot return.
Complete Emergency Power Return. Generated when the car has completed emergency power return to the recall landing and is parked with doors open.
CSA FAULT OUTPUT - On when there is a CSA Redundancy fault condition (CNP, ILO and
UDF only). Used for Canadian Standards Association (CSA) code. If applicable, refer to the job compliance report.
Car Gong Enable Down Output - Generated to activate the in-car gong/lantern (front doors). Activated (usually a double ding: on-off-on) to announce intention to move down after the doors start to open. This will happen when a down hall call front has been entered and the car has reached the floor the call originated from or if the doors are open and a car call front is entered for a floor below.
CGED for rear doors Output - Same as CGED but for the rear gong/lantern.
Car Gong Enable Up Output - Generated to activate the in-car gong/lantern (front doors).
Activated (usually a single-ding) to announce intention to move up after the doors start to open. This will happen when an up hall call front has been entered and the car has reached the floor the call originated from, or if the doors are open and a car call front is entered for a floor above.
4
4-37
User Interface
Table 4.7 Spare Outputs Menu Options
Spare Outputs Menu Options
CGEUR
CGF
CHBPO
CR01-CR8
Car Card Reader Outputs, front landings. Indicates the associated card reader input has been activated (allowing car call registration to this front landing). Once the call is registered, output will remain active until call completed.
CR01R-CR8R
Car Card Reader Outputs, rear landings. Indicates the associated card reader input has been activated (allowing car call registration to this rear landing). Once the call is registered, output will remain active until call completed.
CSB
CSEO
CSR
CTLDOT
Car Stop Switch Bypass Output - Used to provide redundancy for the in-car stop switch function. Activated during Fire Service Phase I to bypass the in-car stop switch (a similar output is one of the standard outputs). With this second output, failure of one of these devices (stuck in the active mode) will not cause the Stop switch to be bypassed improperly. Redundancy is required by CSA.
Code Sequence Enable Output - Active when car is on security and ready to accept the security code. Goes off once the code is accepted or the code entry timer elapses.
Car Selected to Run Output - Generated when the car is selected to run on Emergency
Power phase 2 via the AUTO or EPRUN input.
Car-to-Lobby Door Open Timer Output - Generated upon completion of the car to lobby function (the car has returned to the lobby landing, the doors have opened, and the CTL door timer has expired).
DBZF
CGEU for rear doors Output - Same as CGEU but for the rear gong/lantern.
Computer Generated Fault Output - Comes on for any computer generated fault.
Car and Hoistway Bypass Output - Active when a door is being bypassed (car gate or hoistway door for both the front and rear sides).
DBZR
DCFR
DCFX
Front Door Buzzer - Active prior to automatic closing of the front doors for the length of time determined by the Door Buzzer Timer.
Rear Door Buzzer - Active prior to automatic closing of the rear doors for the length of time determined by the Door Buzzer Timer.
Like DCFX but for rear doors.
Door Close Function Auxiliary. Signals the controller to attempt to close the doors. Unlike the standard DCF output on the HC-CTL-2 board, this one is disabled on inspection, Fire phase I, or Fire phase II operation.
DCPR
DCPX
DHEND
DHENDR
DHO
DHOF
DHOR
DISB
DISL
Like DCPX but for rear doors.
Door Close Power Auxiliary. Unlike the standard DCP output on the HC-CTL-2 board, this one is disabled on inspection, Fire phase I, or Fire phase II operation.
Door Hold End Output - Activates five seconds prior to Door Hold Timer expiration.
Door Hold End Output Rear - Activates five seconds prior to Rear Door Hold Timer expiration.
Door Hold Output - Indicates doors are being held open by the door hold input function.
(The DHLD input is active or the timer associated with the door hold function has not yet elapsed.) DHO will be active if DHLD or DHLDR is active.
Door Hold Output Front - Indicates front doors are being held open by the door hold input function. (The DHLD input is active or the timer associated with the door hold function has not yet elapsed.) DHOF will be active if DHLD is active.
Door Hold Output Rear - Indicates rear doors are being held open by the door hold input function. (The DHLDR input is active or the timer associated with the door hold function has not yet elapsed.) DHOR will be active if DHLDR is active.
Distress Buzzer. Activated when the emergency stop switch is pulled or the alarm bell input
(ABI) is activated. Pulsates if the SAFH, SAFC, or GOV inputs are low or if the TDISL output is used.
Distress Light. Activated when the car establishes an extended safety string fault or if the emergency stop switch is pulled or the alarm bell input (ABI) activated.
4-38 Manual # 42-02-2P25
Motion 4000
F1: Program Mode
Table 4.7 Spare Outputs Menu Options
DISLX
DLOB
DNO
DNS
DO1
DOFR
DOFX
DEIS
DEISR
DOORENAB
DSH
DSHT
DSHTR
ECRN
EFG
EMSB
EMSIC
EMSIH
EP1
EP2
Spare Outputs Menu Options
Distress Light Auxiliary. Activated when the car is shut down due to a fault or the MGS or
PTI inputs are activated while a car call is latched.
Door Left Open Bell Output - Comes on when a call button is pressed and the door has been left open. Used on single button collective and single automatic push button when the hall and car call buttons are connected.
Down output (Attendant Service) - Used on Attendant Service to indicate that a hall call has been registered below the car and the car has been assigned to answer it. Normally used to light an indicator to alert the attendant that such hall calls exist.
Down Sense. Active while the car travels in the down direction.
DO2, DO4, DO8, DO16, D032 - Binary coded P.I. outputs for digital P.I. devices.
Like DOFX but for rear doors.
Door Open Function Auxiliary. Signals the door operator to attempt to open the doors.
Unlike the standard DOF output on the HC-CTL-2 board, this one is disabled on inspection,
Fire phase I, or Fire phase II operation.
Door Enable Inspection Stop Switch - Activated when front door operation is allowed.
Deactivated if the elevator is on inspection or Test mode or if the door stop input has been activated. See Spare Input, DSTI.
Door Enable Inspection Stop Switch Rear - Activated when rear door operation is allowed.
Deactivated if the elevator is on inspection or Test mode or if the door stop input has been activated. See Spare Input, DSTI.
Door Enable Output. Activated when door operation is permitted. For example, if the car is not on Inspection and not on Test mode.
Door Time Shortening Output (intermediate) - Generated when a destination car call button is pressed. (Causes door dwell time to shorten if the doors are fully open).
Door Time Shortening Front Output (final) - Reflects the status of the DSHT flag. Generated if a destination car call button or the front door close button is pressed.
Door Time Shortening Rear Output (final) - Reflects the status of the DSHTR flag. Generated if a destination car call button or the rear door close button is pressed.
Emergency Power Car Run Output - Reflects status of the emergency car run flag associated with emergency power logic. When activated, indicates the car is being prevented from running by emergency power operation logic.
Egress Floor Gong Output - Activates for 300 milliseconds when the car arrives at the
“egress” floor and opens the doors in response to a hall or car call (requires that the egress floor be programmed, See “EGRESS FLOOR ARRIVAL GONG? / MAIN EGRESS FLOOR #” on page 4-26 ). Used to activate an audible indicator to inform visually impaired passengers that the elevator has arrived at the main egress floor.
Emergency Medical Service Buzzer Output - Comes on as soon as the EMS hall switch is activated (EMSIH) and goes off when the car reaches the EMS floor (Phase 1 return). Used to sound an audible signal in the car to alert passengers that the car is being commandeered on EMS service.
Emergency Medical Service Indicator Car Output - Comes on as soon as the EMS hall switch is activated (EMSH). Stays on until the car returns to normal service. Used to activate a visual indicator in the car to alert passengers that the car is on EMS service.
Emergency Medical Service Indicator Hall Output - Comes on when the EMS hall switch is activated (EMSH). Goes off when the in-car switch is activated (EMSC). Enables an indicator informing EMS personnel that the EMS signal was recognized by the control system.
Emergency Power Phase 1 Output - Activated when Emergency Power is initiated via the
EPI input. Stays on until all cars have been recalled to the emergency power landing
(sequential lowering, the first phase of emergency power).
Emergency Power Phase 2 Output - Activated when the system is in the second phase of emergency power (after recall, the normal running of a car on emergency power generators) and remains activated until commercial power is restored.
4-39
4
User Interface
Table 4.7 Spare Outputs Menu Options
EQIND
EQL
FCHLDO
FCOFFO
FIR1
FLASH
FLO
FRC
FRCT
FRM
FSA
FSLCX
FSLLX
FSM
FSO
FSVC
FWIX
FWL
GEDX
GEDRX
GEUX
Spare Outputs Menu Options
Earthquake indicator output. Generated when the CWI input is activated and the car is out of a door zone on Independent Service
Earthquake Light. Active during earthquake operation.
Monitors the status of the Fire Phase II Door Hold Input.
Monitors the status of the Fire Phase II OFF Input.
Fire Service Phase I output - Activated during Fire Service Phase I Main and Alternate operation.
Flash output - Turns ON and OFF at 0.5 second intervals.
Fan/Light Operation Output - Used to turn OFF the car fan and light. Usually OFF. Turned
ON after the Fan/Light Timer elapses. Timer starts when the car becomes inactive.
Fire Service Phase II Output - Activated when the car is placed on Fire Service Phase II.
Active until the elevator has completely transitioned out of fire service phase II operation.
Depending on the fire code programmed, may not be until the elevator has completed its return to the recall floor and the doors have fully opened after turning the in-car firefighter switch to the off position.
Fire Service Phase II True Output - Like FRC, active when car is placed on Fire Service
Phase II. Remains active after the car is taken off in-car firefighter status and until the car has recalled to the recall landing and the doors are preparing to open.
Fire Service Phase I Output - Activated when the car is on Main or Alternate Fire Service
Phase I. Deactivated when Fire Service Phase II begins.
Fire Service Alternate Output - Activated when the FRA input is activated by the main fire sensor. Remains active while the car is on Fire Service Phase I.
Fire Service Light COP Auxiliary output. When active, indicates in-car fire service light is active.
Fire Service Light Lobby Auxiliary output. When active, indicates the lobby fire service light is active.
Fire Service Main Output - Activated by the fire sensor or switch input for Fire Service Main
Phase I or II.
Fire Service On Output - Activated when the car is on Fire Service Phase I or II. Used to activate the visual fire service indicator in the car.
True Fire Service Output - Activated when the car is on Fire Service Phase I or II. Used to extinguish the hall position indicators as required by ANSI89 Fire Code.
Fire Service Buzzer Auxiliary output.
Fire Warning Light Output - Used to indicate if the car is on Fire Phase I or II. It will be ON solidly unless machine room or hoistway fire sensors have tripped (FRMR, FRHTW, FRSA,
FRSM) in which case it will flash.
Gong Enable Down Auxiliary. Unlike the standard GED output on the HC-CTL-2 board, this one is not active on inspection, Fire phase I, or Fire phase II operation.
Same as GEDX, but for rear doors.
Gong Enable Up Auxiliary. Unlike the standard GEU output on the HC-CTL-2 board, this one is not active on inspection, Fire phase I, or Fire phase II operation.
Same as GEUX, but for rear doors.
Gray Code digital outputs for Gray Code Digital PI devices.
GEURX
GDO1/2/4/8/
16/32
H
HCP
HCR
High Speed Output. Active when the elevator is running at high speed. Informational output.
Hall Call Pushed Output - Active when a hall call button is pressed for the amount of time the button is down.
Hall Call Reject Output - Reflects the status of the HCR flag which indicates that a car is unable to respond to a hall call (car may be out of service or overloaded).
4-40 Manual # 42-02-2P25
Motion 4000
F1: Program Mode
Table 4.7 Spare Outputs Menu Options
Spare Outputs Menu Options
HCR01-HCR8
Hall Card Reader outputs. Indicates that the associated card reader input has been activated, allowing registration of the hall call. Remains active until the call is extinguished.
HCR01R-
HCR8R
HDNL
HDSC
Hall Card Reader outputs Rear. Used to indicate that the associated card reader input has been activated, allowing registration of the hall call. Remains active until the call is extinguished.
High speed down and not leveling. Informational output.
Heat Detector Shutdown Complete Output - Detroit Fire Code. Normally active. When activated, the car stops at the next landing and opens the doors. Once the doors are fully open
(DOL=0), the output is turned off, indicating it is okay to shut down the controller and activate machine room sprinklers.
HEO
HLW
Hospital Emergency Operation. Flashes when the car is responding to a hospital emergency operation call. Remains flashing until the in-car hospital switch is returned to normal or the time interval that the car must wait for the in-car switch to be turned On expires. Please refer to “HOSPITAL EMERG. OPERATION?” on page 4-48.
Heavy Load Weigher Output - Activated when car load exceeds the heavy load threshold
(
see “Load Weigher Thresholds” on page 4-60
) or when the HLI input is activated.
HOSPH2
HSEL
HUNL
HWI
INDFRC
INDO
INSP
ISRT
ISVF
Hospital Phase 2. Activated when the car is at the hospital emergency recall floor. Remains active until the hospital in-car switch is turned off or the time interval that the car must wait for the in-car switch to be turned On expires. Please refer to “HOSPITAL EMERG.
OPERATION?” on page 4-48 .
Hospital Emergency Car Select. Reflects the hospital selection status of an elevator. HSEL is the flag generated when a car is selected to respond to a hospital emergency call. HSEL is generated when the call is assigned to the car (HSEL actually initiates the return to the hospital call floor) and remains on until the in-car hospital switch is activated or the hospital wait timer expires. Please refer to “HOSPITAL EMERG. OPERATION?” on page 4-48.
High speed up and not leveling. Informational output.
Hospital Warning Indicator. This output will remain on when a hospital emergency call is registered in a car on Independent Service. Please refer to “HOSPITAL EMERG. OPERA-
TION?” on page 4-48.
Independent Service/Fire Service Phase 2 Output - Used to disconnect hall calls during Fire
Independent Service for elevators with either single button collective or single automatic push button operation. Please refer to “OPERATION:” on page 4-13 .
Independent Service Output. Active when the elevator is running on Independent mode.
Typically used to drive an indicator light. Please refer to “Independent Service” on page 1-
11 .
Inspection. Active when the car is on Inspection operation (any inspection or access mode).
In Service and Running Output - Reflects the cars ability to respond to hall calls (the ISRT status). ISRT is active when the car status is such that it can answer hall calls.
Flashing In Service Output - Reflects status of the in-service flag (ISV) which indicates that the car is in normal passenger mode operation. This output will flash if the car times out of service.
ISV
IUL
LCTF
In Service Output - Reflects status of the in-service flag (ISV) which indicates that the car is in normal passenger mode operation.
In Use Light output - Activates when the car is in use, e.g., the car is in motion or the doors are open.
Front photo eye cycle test output. When this output and the 2PHEF input are programmed, the front doors will not close until the front photo eye cycle test passes. Prior to closing the front doors, the controller will generate the LCTF output so the door operator will cycle the front PHE inputs (Off to On, then On to Off). During this time, the front PHE is disabled for normal operation. Only fire service bypasses this operation.
4
4-41
User Interface
Table 4.7 Spare Outputs Menu Options
LCTR
LLW
MISV
MLT
NBZX
NCD
NDGR
NDGX
OFR
OFRP
OLW
PFGX
PH1
PI1 - PI8
PRIFLG
RCOMP
RSTDRV
SAFO
SEC
SIMPO
TESTSWO
Spare Outputs Menu Options
Rear photo eye cycle test output. When this output and the 2PHER input are programmed, the rear doors will not close until the rear photo eye cycle test passes. Prior to closing the rear doors, the controller will generate the LCTR output so the door operator will cycle the rear PHE inputs (Off to On, then On to Off). During this time, the rear PHE is disabled for normal operation. Only fire service bypasses this operation.
Light Load Weigher Output - Activated when load in the car is less than the threshold set for light load anti-nuisance (
see “Load Weigher Thresholds” on page 4-60
) or when the LLI input is activated ( see “LIGHT LOAD WEIGHING? / LIGHT LOAD CAR CALL LIMIT” on page 4-44 ).
Mechanically In Service Output - Normally active when the car is running but turned off when the car is mechanically out of service as indicated by the Safety String (SAF) and
Motor Limit Timer (MLT).
Motor Limit Timer Elapsed Output - Activated if the Motor Limit Timer Elapses or when the
EXMLT input is active.
Nudging Buzzer Auxiliary output. Unlike the standard NBZ output on the HC-CTL-2 board, this one is not active on inspection, Fire phase I, or Fire phase II operation.
Emergency Power Return Incomplete Output - Deactivated when car has finished returning on emergency power or when it has been determined that the car cannot lower ( see
“EMERGENCY POWER OPERATION?/EMERGENCY POWER RETURN FLOOR” on page 4-44 ).
Like NDGX, but for rear doors.
Door Nudging Auxiliary output. Signals the controller to attempt to close the doors at reduced torque. Unlike the standard N1 output on the HC-CTL-2 board, this one is not active on inspection, Fire phase I, or Fire phase II operation.
One Floor Run Output - Generated when the car initiates a run. Remains active until the car encounters the first door zone in its movement (active while traversing the first floor height in the direction of travel).
One Floor Run Programmable - Active while making one-floor runs between adjacent floors designated in the Extra Features Menu ( see “OFRP BETWEEN FLRS” on page 4-50 ).
Overloaded Car Threshold Output - Activated when the overload threshold is reached ( see
“Load Weigher Thresholds” on page 4-60
) or OVL input. The car will remain at the floor with doors open. Typically, when used, a visual or audible indicator alerts passengers that the car is overloaded. Overridden by Fire Service Phase II.
Passing Floor Gong Auxiliary output. Unlike the standard PFG output on the HC-CTL-2 board, this one is not active on inspection, Fire phase I, or Fire phase II operation.
Fire Service Phase 1 Return Complete Output - Indicates the car has successfully completed Fire Service Phase I recall (the car is at the fire recall floor with doors open). Most often used as a signal that it is okay to activate machine room sprinklers.
Position Indicator outputs (discrete). One wire per floor.
Priority Service Output - Informs the emergency power overlay that the car is on emergency/priority service and should be selected to run. Priority operation includes Hospital
Service, EMT Service, Fire Service Phase II, Earthquake Service, and Test Mode.
Rescue Complete. Used with a TAPS unit. When the controller is under TAPS operation,
RCOMP will activate (ground) once the car has landed at a floor and cycled doors to let passengers out.
Reset Drive. Allows the controller to activate the drive reset function.
Safety Output. If the car safety string opens, this output activates.
Security Code Incorrect - When elevator security is on, this output is active for five seconds if an incorrect security code is entered.
Simplex Output - Comes on when the SIMP input is activated or when Simplex Operation is chosen. Used to activate a relay(s) to separate the two hoistway risers.
Test switch output. Activates when the car is put in Test mode.
4-42 Manual # 42-02-2P25
Motion 4000
F1: Program Mode
Table 4.7 Spare Outputs Menu Options
TOS
UPO
UPS
WLDI
XPI1 - XPI7
XSDA
XSUA
ZADJ
Spare Outputs Menu Options
Timed Out of Service Output - Reflects the Timed Out of Service flag. The TOS flag is set if the car does not move within a certain amount of time with either SUA or SDA active.
Up Output (Attendant Service) - Indicates that a hall call has been registered above the car and the car has been assigned to answer it. Normally used for an indicator light to alert the attendant that such hall calls exist.
Up Sense. Active while the car travels in the up direction.
Wild Operation Indication Output - Generated when the car is in emergency dispatch mode, e.g., if the hall call bus fuse is blown and emergency dispatching is active.
Auxiliary Position Indicators 1 through 7. Like the standard PI1 - PI7 outputs except that these are disabled on Inspection or Fire Service Phase I or II.
Auxiliary Supervisory Down Arrow - Behaves identically to the standard SDA output except that it is disabled on Inspection and Fire Service Phase I or II.
Auxiliary Supervisory Up Arrow - Behaves identically to the standard SUA output except that it is disabled on Inspection or Fire Service Phase I or II.
Zero Adjust - Causes the analog load weigher to perform a zero adjust procedure. Generated once every 31 hours or when the car is idle at the bottom floor for 30 seconds.
4
4-43
User Interface
Extra Features Menu Options
• PI OUTPUT TYPE
• Choose 1 WIRE PER FLOOR, BINARY BASE 1, BINARY BASE 0, GRAY CODE 1, or
GRAY CODE 0 depending on the inputs required by the position indicator and whether the floor count begins with a zero value or a one value.
• INTERMEDIATE SPEED
• If yes, Intermediate Speed may be applied to the standard curve through the Intermediate (INT) input if programmed. See
Intermediate Speed, 151 on page 4-158
.
• EMERGENCY POWER OPERATION?/EMERGENCY POWER RETURN FLOOR
• If selected, the controller will put the elevator into Emergency Power Operation when it receives an Emergency Power Input (EPI) signal. During Phase 1 of Emergency
Power Operation, the car will be moved to the emergency power return floor. In a duplex configuration, each car will be moved to the return floor individually.
During Phase 2 of Emergency Power Operation, if the car Emergency Power Run
(EPRUN) input is activated, the car will run normally. Otherwise, the car will remain at the emergency power return floor and will not respond to calls.
For a simplex controller, the car EPRUN input is sometimes connected to a switch so that the input can be turned ON or OFF. For a duplex controller, both car EPRUN inputs are usually connected to a Run Selection switch. The position of this switch determines which car will run during Phase 2 of Emergency Power Operation.
Often, there is an AUTO position on the Run Selection switch connected to the AUTO input on both controllers in a duplex. If the AUTO input is activated, one car will be automatically selected to run during Phase 2 of Emergency Power Operation. For example: If one car happens to be out of service when the operation begins, the other car will be automatically selected to run.
If the Emergency Power option is selected, appropriate spare inputs should be config-
ured also. See “Spare Inputs Menu” on page 4-27.
• LIGHT LOAD WEIGHING? / LIGHT LOAD CAR CALL LIMIT
• Used only when the Light Load Weigher Input is activated. (
See “Spare Inputs Menu” on page 4-27.
) To program this option:
• Activate the LLI input.
• Set LIGHT LOAD WEIGHING? to NO or press S to select the maximum number of car calls registered before all car calls are canceled.
• If S is pressed, the display will read LIGHT LOAD CAR CALL LIMIT.
• Press S until the desired number is displayed.
Note
Light Load Weighing/Light Load Car Call Limit is an anti-nuisance feature. It is designed to prevent a single person in the car from placing multiple car calls to delay the car.
4-44 Manual # 42-02-2P25
Motion 4000
F1: Program Mode
• PHOTO EYE ANTI-NUISANCE? / CONSEC STOPS W/O PHE LIMIT
• When ON, car calls will be canceled if the Photo Eye input has not been activated after a programmed number of consecutive stops. The number of consecutive stops must be programmed before the car calls will cancel. To program this option:
• Set PHOTO EYE ANTI-NUISANCE? to NO or press S to select the number of consecutive stops.
• If S is pressed, the display will read CONSEC STOPS W/O PHE LIMIT.
• Press S until the desired number is displayed.
Note
Photo Eye Anti-Nuisance/Consec Stops w/o PHE Limit is an anti-nuisance feature designed to prevent a single person from remaining in the car and “joy-riding” for multiple calls.
• MG SHUTDOWN OPERATION?
• If set to Yes, if a car is idle for a period of time in excess of the MGR timer, it will recall to its parking floor and shut down.
• DEDICATED CARD READER SECURITY?
• Enables card reader security through HC-UIO boards set aside (dedicated) for security
I/O only. No non-security I/O may be connected to these boards.
CARD REDR INPUTS- STACKED C/H? YES/NO - (Applies only if Dedicated Card
Reader Security = Yes)
• No = each UIO board’s connections will be of only one type (hall reader or car panel reader).
• Yes = car and hall security may be serviced by different connections on the same UIO board. It will then need clarification as to which calls must be accommodated, see explanation below:
UIO Board/Security Enforcement/Connection Order
The maximum number of security signal connections for a single floor is four: One each for front and rear control panels and one each for front and rear hall stations. In reality, each floor may not require all four inputs; for example, some floors may not have rear doors while others do. In order to use UIO board connections most efficiently, the system uses the floor service “map” set up through Basic Features, and information from the following four prompts, to set aside the actual number of security connections required for each floor. Note: If the information is available, before the system is shipped, these options are factory-set and you may simply follow the job prints to make connections.
• After setting CARD REDR INPUTS - STACKED C/H to YES, use the + key to move to the next “clarification” prompt.
• CARD REDR INPUTS - F CAR CALS? Y/N. Use the S key to respond. Yes if you have front car call readers; No if you do not. Use the + key to move to the next prompt.
• CARD REDR INPUTS - F HAL CALS? Y/N. Use the S key to respond. Yes if you have front hall call readers; No if you do not. Use the + key to move to the next prompt.
• CARD REDR INPUTS - R CAR CALS? Y/N. Use the S key to respond. Yes if you have rear car call readers; No if you do not. Use the + key to move to the next prompt.
• CARD REDR INPUTS - R HAL CALS? Y/N. Use the S key to respond. Yes if you have rear hall call readers; No if you do not.
• Press N to exit the prompt set.
4
4-45
User Interface
• IND. CNCL. CALLS ON STOP?
• If yes, on Independent service and if more than one car call is registered, when the first car call is answered all other registered car calls will be canceled.
• WPIx LANDING? (x = A through H)
• Wandering Patient Security (Bracelet Security/Infant Abduction Security). When a
WPI input is activated, hall calls to the landing and side associated with that input are disabled. If the elevator is already at that landing with doors open, it will be shut down and prevented from leaving that landing. Set the landing number and the side (Front,
Rear, or Both) to be disabled when the corresponding spare input (WPIA through
WPIH) is activated.
• ALLOW CAR CALLS ON WP SEC.?
• Wandering Patient Security (Bracelet Security). If set to Yes, car calls to landings with active WPIx inputs are allowed, otherwise, car calls to those landings are disabled.
• CANCEL BOTH HALL (U/D) CALLS
• If set to NO, when the car is servicing a hall call, only the call in the direction of travel is canceled.
• If set to YES, when the car is servicing a hall call, calls in both up and down directions are canceled.
• RETAIN CALLS ON CTL / CTF?
• No: If Car To Lobby or Car To Floor are activated, the car will first service registered car calls then move to the recall floor. Hall calls will be canceled.
• Yes: If Car To Lobby or Car To Floor are activated, the car will first service registered car calls then move to the recall floor. Hall calls will be retained and served after the
CTL input is deactivated.
• AUTOMATIC FLOOR STOP OPTION? / AUTOMATIC STOP FLOOR #?
• If you want to use this option, set to a specific floor number. The car will automatically stop at that floor on any run that would normally pass the floor.
• AUTO STOP DOORS OPERATION?
• Causes the selected doors (front, rear or both) to open automatically when an automatic floor stop occurs.
• CC CANCEL W/DIR REVERSAL?
• Causes all previously registered car calls to be canceled when the car reverses travel direction.
• CANCEL CAR CALLS BEHIND CAR?
• If set to YES and the car has a direction arrow (SUA/SDA), no car calls can be registered behind the current car position. For example: If a car is at the fifth floor moving down, no car calls can be registered for the sixth floor and above.
• CE ELECTRONICS BOARD?
• Informs the controller of the revision level, 1 or 2, of the CE interface board in use.
• MASSACHUSETTS EMS SERVICE? / EMS SERVICE FLOOR #
• Provided in the state of Massachusetts only, this option is key-operated and provides immediate car service for Massachusetts Emergency Medical Service personnel.
4-46 Manual # 42-02-2P25
Motion 4000
F1: Program Mode
• BSI SECURITY KEY
• Standard Security is initiated by the BSI Security Key. There are three possible settings: ACTIVATED, ENABLED, or DEACTIVATED.
• If set to ACTIVATED, Security is initiated.
• If set to ENABLED, Security is initiated only if the Building Security Input (BSI) is turned On.
• If set to DEACTIVATED, Security is deactivated regardless of the status of the BSI input.
• PI TURNED OFF IF NO DEMAND?
• When set to YES, allows PI outputs to turn OFF if the car has been inactive for a selected time (from 1 to 10 minutes) as determined by the fan/light timer. Please refer to “FAN/LIGHT OUTPUT TIMER (Range: 5.0-20.0 Minutes)” on page 4-25 .
4
4-47
User Interface
• HOSPITAL EMERG. OPERATION?
• When selected, enables Hospital Emergency Operation. Typically, a hospital emergency call switch is installed at each floor where this service is desired.
• If you do not have Hospital Emergency Service Operation, set the option to NO by pressing the S button. Then, press the N push button to exit.
• If you have Hospital Emergency Service Operation, set the option to YES by pressing the S button, then the N button to continue. A landing number display will appear.
• If you want Hospital Emergency Service to this landing, press S to set to Yes. (If you change your mind, press S a second time to go back to No.)
• Press the '+' push button to scroll through available landings. Press N to continue after making settings for a floor.
• If this car has rear doors, the sequence will repeat.
• Press the '+' button to scroll through available landings. The display will continue to present options for each floor. Press N to exit the Hospital Emergency Service option.
• When a hospital emergency call switch is activated, the hospital emergency call registered light will light at that floor only and the nearest available elevator will respond to the call. All car calls in the selected car will be canceled and any landing calls which had previously been assigned to the car will be transferred to another car if available.
• If the selected car is traveling away from the hospital emergency call, it will slow down and stop at the nearest floor without opening the doors, reverse direction, and proceed nonstop to the hospital emergency floor.
• If the selected car is traveling toward the hospital emergency floor, it shall proceed nonstop to that floor.
• If, at the time of selection, the car is slowing into a floor, it will stop without opening the doors, then travel immediately to the hospital emergency floor.
• When the car reaches the hospital emergency floor, it will remain with doors open for a timer-determined time. After this interval has expired, if the car has not been placed on incar Hospital Emergency Service Operation, the car will return to normal service.
• A hospital emergency key switch in each car operating panel is used to select in-car Hospital
Emergency Service Operation. Upon activation of the key switch, the car will be ready to accept a call to any floor and, after the doors are closed, will proceed nonstop to that floor.
Returning the key switch to the normal position will restore the car to normal service.
• The car selected to respond to a hospital emergency call is removed from automatic service and will accept no additional calls, emergency or otherwise, until it completes the hospital emergency function. In duplex installations, if both cars are out of service and unable to answer an emergency call, the hospital emergency call registered light will not illuminate.
• Four outputs on the first HC-UIO board are used for hospital emergency service calls.
Hospital Emergency Operation (HEO) will flash once the car has been selected to respond to a hospital emergency call and will remain flashing until the in-car hospital switch is returned to normal or the time interval that the car must wait for the in-car switch to be turned ON expires.
Hospital Emergency Warning Indicator (HWI) will remain steadily ON for a car on Independent Service when the hospital call is registered.
Hospital Emergency Select (HSEL) will remain steadily ON, indicating that the car has been selected to answer a hospital call, until the in-car hospital switch is turned ON or the time interval expires.
Hospital Emergency Phase 2 (HOSPH2) will remain ON, indicating that the car has arrived at the hospital call floor until the in-car hospital switch is returned to normal or the time interval that the car must wait for the in-car switch to be turned ON expires.
4-48 Manual # 42-02-2P25
Motion 4000
F1: Program Mode
• FIRE BYPASSES HOSPITAL?
• Set to YES if Hospital Service is used for VIP, Priority or Commandeering Service. Set this option to NO if Hospital Service is truly used for Hospital Service.
• HIGH SPEED DELAY AFTER RUN?
• Setting this option inserts a fixed delay (3 seconds) between the completion of a run and the initiation of the next run. Use in applications in which an immediate “stop/ start” is undesirable. Under most circumstances, the initiation of a run is delayed by the time required for door operation. In some cases, however, the car may stop and start immediately in the absence of a door operation. For example, a direction reversal upon being assigned a hall call while the car was parking.
• SINGLE SPEED AC OPTION
• Setting this option allows the direction output to clear once the car “steps” into the floor. Typically the direction output is not cleared until the car enters the door zone.
However, for applications only requiring one speed, the direction must be cleared prior to door zone to allow the car to arrive at the landing properly.
• SABBATH OPERATION
• If you do not have Sabbath Operation, set this option to NO by pressing the S push button, then press the N push button to exit.
• If you have Sabbath Operation, set this option to YES by pressing the S push button.
Press the N push button to continue. The following will appear:
“FRONT UP STOP AT FLOOR 1?”
• If you want the car to service this floor while traveling or initiating travel in the UP direction, press S to select YES. (Pressing S again will set back to NO.)
• Press + to increment floor value to the next landing. Continue until all desired front UP stops are set to YES.
• Press N to proceed to the next eligibility map. If there are no walk through doors on this controller, rear eligibility maps will not display. In order, the next eligibility maps are:
“REAR UP STOP AT FLOOR 1?”
“FRONT DOWN STOP AT FLOOR 2?”
“REAR DOWN STOP AT FLOOR 2?”
• Remember that the + push button increments the floor value to the next landing and that the N push button displays the next eligibility map.
• LEVELING SENSOR ENABLED/DISABLED
• Factory set to Enabled. Cannot be adjusted.
• KCE DISABLED?
• If set to Yes, keyboard command entry is disabled.
• ANALOG LOAD WEIGHER?
• Enables analog load weigher logic and selects the type of learn operation to be performed depending on the type of load weigher installed.
• IND. BYPASSES SECURITY? YES / NO
• Determines if Elevator Security is bypassed when the car is on Independent Service or
Test operation (available only when Security is enabled).
4
4-49
User Interface
• ATS. BYPASS SECURITY? YES / NO
• Determines if Elevator Security is bypassed when the car is on Attendant Service
(available only when Security and Attendant Service are enabled).
• CAR TO FLOOR RETURN FLOOR
• Determines the floor to which the car will be returned when the CAR TO FLOOR input is activated (see CTF in Spare Inputs Menu Options).
• SCROLLING SPEED (NORMAL/FAST/SLOW)
• Messages too long to be fully displayed on the LCD are scrolled. This setting determines scrolling speed.
• OFRP BETWEEN FLRS
• Sets the floors between which the OFRP output will be triggered. The One Floor Run
Programmable output will then be on while making one-floor runs between designated floors.
• ENABLE FRONT DOB ON SECURITY?
• When enabled, front door open button will be enabled for all landings including secured landings. When disabled, door open button is disabled at secured landings once doors have closed.
• ENABLE REAR DOB ON SECURITY?
• When enabled, rear door open button will be enabled for all landings including secured landings. When disabled, door open button is disabled at secured landings once doors have closed.
• FLR COUNT BELOW FLOOD LEVEL?
• PITFLD spare input required. Indicates the number of floors below flood level and thereby sets the flood level. The set number of floors from the bottom of the hoistway will not be serviced when the PITFLD input is active.
• DISABLE TOP FLRS ON PITFLD
• YES/NO - PITFLD spare input required. Prevents the elevator from servicing floors at the top of the hoistway (determined by FLR COUNT BELOW FLOOD LEVEL) when the PITFLD input is active, thereby preventing the counterweight from going into the water.
• CANCEL BOTH HALL (U/D) CALLS
• If set to NO, when the car is servicing a hall call, only the call in the direction of travel is canceled.
• If set to YES, when the car is servicing a hall call, calls in both up and down directions are canceled.
4-50 Manual # 42-02-2P25
Motion 4000
F1: Program Mode
• RETAIN CALLS ON CTL / CTF?
• No: If Car To Lobby or Car To Floor are activated, the car will first service registered car calls then move to the recall floor. Hall calls will be canceled.
• Yes: If Car To Lobby or Car To Floor are activated, the car will first service registered car calls then move to the recall floor. Hall calls will be retained and served after the
CTL input is deactivated.
• EARTHQUAKE OPERATION?
• Set to Yes if this job has earthquake operation.
• ASME EARTHQUAKE/CALIF EARTHQUAKE
• Use the S button to select the controlling earthquake code in your location.
• If CALIF code is selected, you will be asked to indicate whether or not the hoist machine is a “Counterweighted drum machine.” Only jobs that are termed “Counterweighted Drum Machines” should set this option to Yes.
California jobs without a drum machine should select ASME EQ and set the remaining
EQ option parameters as needed.
Note
ASME Earthquake: Upon activation of a Seismic switch (SSI input), the elevator in motion continue to the nearest available floor, open the doors and shut down. If the Counterweight Displacement switch is not activated (CWI), the elevator will be allowed to run at reduced speed on
Automatic Operation.
If the elevator is in motion when the Counterweight Displacement switch is activated (CWI input) an emergency stop is initiated and then the car will proceed away from the counterweight at reduced speed to the nearest available floor, open the doors and shut down. For this operation the Earthquake Direction Switch input (EDS) must be selected. An elevator may be returned to Normal service by means of the Earthquake Reset button, provided that the Displacement switch (CWI) is no longer activated.
4
Note
California Earthquake: When CALIF Earthquake Operation is selected upon activation of a
Seismic switch (SSI input), the elevator, if in motion, will pause, then proceed to the nearest available floor at a speed of not more than 150 ft/min (0.76 m/s) open the doors and shut down.
When a Counterweight Displacement switch is required and the Counterweight Displacement switch (CWI input) has been activated, the elevator, if in motion, will initiate an emergency stop and proceed away from the counterweight at reduced speed to the nearest available floor, open the doors and shut down. For this operation, the Earthquake Direction Switch (EDS) input must be selected. An elevator may be returned to Normal service using the Earthquake Reset button, provided that the Displacement switch (CWI) is not activated. When Earthquake Operation is needed, the appropriate spare inputs should be selected.
4-51
User Interface
• EQ SHUTDOWN AT LANDING?
• If yes, when the EQI input is activated, the elevator will proceed to the nearest landing, stop, open its doors, and shut down.
• If no, the elevator will react as above but will return to service rather than shutting down.
• CORRECTION AWAY FROM CW?
• If yes, when the SSI input is activated, the elevator will pause (freeze) momentarily, correct to the nearest landing in the direction away from the counterweight, then continue as determined by the EQ SHUTDOWN AT LANDING selection.
• If no, when the SSI input is activated, the elevator will not consider counterweight location when proceeding as determined by the EQ SHUTDOWN AT LANDING selection. Default should be No for A17.1 code. If the CWI input is never activated, the car will proceed to the next available landing, open the doors, and shut down
• EQ SHUTDOWN PH1 FIRE SERV?
• If yes, earthquake shutdown will occur even if the car is on Phase 1, fire return. Default should be Yes for all codes.
• EQ SHUTDOWN PH2 FIRE SERV?
• If yes, earthquake shutdown will occur even if the car is on Phase 2, in-car firefighter service. Default should be Yes for all codes.
• FIRST LOWER/RUN ON EP PWR
• Allows selection of the Duplex car (A or B) that will be first to lower and run on emergency power.
Additional Car Options
• ETS SWITCHES REQUIRED
• Unused parameter. Set to No.
• HOISTWAY ACCESS? (YES/NO)
• Set to YES if job has Hoistway Access operation.
• TOP ACCESS? (F/R)
• Set to the riser in which the hall access switch is located.
• BOTTOM ACCESS? (F/R)
• Set to the riser in which the hall access switch is located.
• DOOR POSITION MONITORS: (NONE/FRONT/REAR/BOTH)
• If job uses door position monitor switches, set accordingly.
• FRONT DOOR CLOSE LIMIT?
• Set to the door close limit signals used by this car. (DCL for door close limit switch. GS and DCAB for gate switch and door closed bottom access. None.)
• REAR DOOR CLOSE LIMIT?
• Set to the door close limit signals used by this car. (DCLR for door close limit switch. GSR and DCABR for gate switch and door closed bottom access. None.)
4-52 Manual # 42-02-2P25
Motion 4000
F2: External Memory Mode
F2: External Memory Mode
Access External Memory by placing Function Switch F2 in the Up position (all others down).
External Memory mode is used to view memory addresses in HC-
MPU board RAM. The external memory address is denoted by the letters DA (Data Address). Viewing external memory is helpful in troubleshooting. The Computer External Memory Chart Table lists address data digits and meanings.
1. Select the address to view. (See following table.)
• Press N to select an address digit (selected digits blink)
• Press + or - to change the blinking digit
2. Press S to select the entered address when ready to view contents (or wait about 20 seconds and the selection will appear by itself).
Example
• The DHLD (Door Hold Open Switch) input is not holding the doors open.
• From your job prints, you see that DHLD is programmed for the Spare 5 input.
1. Find SP5 in the Computer External Memory Chart (
page 4-54 ). Note that the Address of
SP5 is 02AF and the Position is 5.
2. Change the address on the display to Address 02AF. Look at the data bit at position 5 (from the right, underlined in illustration) to see the state of the input. If the digit is 1, the controller sees the SP5 signal as ON. If the digit is 0, the controller sees the SP5 signal as OFF.
3. Check the voltage on the SP5 terminal to see whether the problem is in the controller or with outside components.
4
4-53
User Interface
Table 4.8 Computer External Memory Chart
ADD
0158:
0159:
015A:
015B:
015C:
015D:
015E:
015F:
0150:
0151:
0152:
0153:
0154:
0155:
0156:
0157:
0148:
0149:
014A:
014B:
014C:
014D:
014E:
014F:
0140:
0141:
0142:
0143:
0144:
0145:
0146:
0147:
HALL CALLS
8 7 6 5
601R/UC1R 601/UC1
602R/UC2R 602/UC2 502R/DC2R
603R/UC3R 603/UC3 503R/DC3R
604R/UC4R 604/UC4 504R/DC4R
605R/UC5R 605/UC5 505R/DC5R
606R/UC6R 606/UC6 506R/DC6R
607R/UC7R 607/UC7 507R/DC7R
608R/UC8R 608/UC8 508R/DC8R
502/DC2
503/DC3
504/DC4
505/DC5
506/DC6
507/DC7
508/DC8
609R/UC9R 609/UC9 509R/DC9R 509/DC9
610R/UC10R 610/UC10 510R/DC10R 510/DC10
611R/UC11R 611/UC11 511R/DC11R 511/DC11
612R/UC12R 612/UC12 512R/DC12R 512/DC12
613R/UC13R 613/UC13 513R/DC13R 513/DC13
614R/UC14R 614/UC14 514R/DC14R 514/DC14
615R/UC15R 615/UC15 515R/DC15R 515/DC15
616R/UC16R 616/UC16 516R/DC16R 516/DC16
617R/UC17R 617/UC17 517R/DC17R 517/DC17
618R/UC18R 618/UC18 518R/DC18R 518/DC18
619R/UC19R 619/UC19 519R/DC19R 519/DC19
620R/UC20R 620/UC20 520R/DC20R 520/DC20
621R/UC21R 621/UC21 521R/DC21R 521/DC21
622R/UC22R 622/UC22 522R/DC22R 522/DC22
623R/UC23R 623/UC23 523R/DC23R 523/DC23
624R/UC24R 624/UC24 524R/DC24R 524/DC24
625R/UC25R 625/UC25 525R/DC25R 525/DC25
626R/UC26R 626/UC26 526R/DC26R 526/DC26
627R/UC27R 627/UC27 527R/DC27R 527/DC27
628R/UC28R 628/UC28 528R/DC28R 528DC28
629R/UC29R 629/UC29 529R/DC29R 529/DC29
630R/UC30R 630/UC30 530R/DC30R 530/DC30
631R/UC31R 631/UC31 531R/DC31R 531/DC31
532R/DC32R 532/DC32
SPARE INPUTS*
4 3
ADD 8 7 6 5 4 3 2 1
02AF:
02B0:
02B1
02B2
02B3
02B4
SP8
SP16
SP24
SP32
SP40
SP48
SP7
SP15
SP23
SP31
SP39
SP47
SP6
SP14
SP22
SP30
SP38
SP46
SP5
SP13
SP21
SP29
SP37
SP45
SP4
SP12
SP20
SP28
SP36
SP44
SP3
SP11
SP19
SP27
SP35
SP43
SP2
SP10
SP18
SP26
SP34
SP42
SP1
SP9
SP17
SP25
SP33
SP41
02B5 SP50 SP49
* The first 10 spare inputs are located on the HC-CTL-2 board. The remaining spare inputs are located on
HC-UIO boards numbered 32 through 36 (8 per board).
SPARE OUTPUTS **
ADD 8 7 6 5 4 3 2 1
02EF:
02F0:
02F1:
02F2:
02F3:
02F4:
OUT4
OUT12
OUT20
OUT28
OUT36
OUT44
OUT3
OUT1
OUT19
OUT27
OUT35
OUT43
OUT2
OUT10
OUT18
OUT26
OUT34
OUT44
OUT1
OUT9
OUT17
OUT25
OUT33
OUT45
OUT8
OUT16
OUT24
OUT32
OUT46
OUT7
OUT15
OUT23
OUT31
OUT47
OUT6
OUT14
OUT22
OUT30
OUT48
** The first four spare outputs are located on the HC-CTL-2 board. The remaining spare outputs are located on HC-UIO boards numbered 32 through 35 (8 per board).
OUT5
OUT13
OUT21
OUT29
OUT49
CAR CALLS
2 1
101R/CC1R
102R/CC2R
103R/CC3R
104R/CC4R
105R/CC5R
106R/CC6R
107R/CC7R
108R/CC8R
101/CC1
102/CC2
103/CC3
104/CC4
105/CC5
106/CC6
107/CC7
108/CC8
109R/CC9R 109/CC9
110R/CC10R 110/CC10
111R/CC11R 111/CC11
112R/CC12R 112/CC12
113R/CC13R 113/CC13
114R/CC14R 114/CC14
115R/CC15R 115/CC15
116R/CC16R 116/CC16
117R/CC17R 117/CC17
118R/CC18R 118/CC18
119R/CC19R 119/CC19
120R/CC20R 120//CC20
121R/CC21R 121/CC21
122R/CC22R 122/CC22
123R/CC23R 123/CC23
124R/CC24R 124/CC24
125R/CC25R 125/CC25
126R/CC26R 126/CC26
127R/CC27R 127/CC27
128R/CC28R 128/CC28
129R/CC29R 129/CC29
130R/CC30R 130/CC30
131R/CC31R 131/CC31
132R/CC32R 132/CC32
4-54 Manual # 42-02-2P25
Motion 4000
F2: External Memory Mode
Table 4.9 Hospital Call and Eligibility Memory Chart
HOSPITAL CALL ELIGIBILITY
OTHER CAR THIS CAR
HOSPITAL CALLS
ASSIGNED
HOSPITAL CALLS
REAR FRONT REAR FRONT REAR FRONT
REGISTERED
HOSPITAL CALLS
REAR FRONT
ADD
0258:
0259:
025A:
025B:
025C:
025D:
025E:
025F:
0250:
0251:
0252:
0253:
0254:
0255:
0256:
0257:
0248:
0249:
024A:
024B:
024C:
024D:
024E:
024F:
0240:
0241:
0242:
0243:
0244:
0245:
0246:
0247:
8 7 6 5 4 3 2
ECR25
ECR26
ECR27
ECR28
ECR29
ECR30
ECR31
ECR32
ECR17
ECR18
ECR19
ECR20
ECR21
ECR22
ECR23
ECR24
ECR9
ECR10
ECR11
ECR12
ECR13
ECR14
ECR15
ECR16
ECR1
ECR2
ECR3
ECR4
ECR5
ECR6
ECR7
ECR8
1
EC25
EC26
EC27
EC28
EC29
EC30
EC31
EC32
EC17
EC18
EC19
EC20
EC21
EC22
EC23
EC24
EC9
EC10
EC11
EC12
EC13
EC14
EC15
EC16
EC1
EC2
EC3
EC4
EC5
EC6
EC7
EC8
Legend for Table 4.8
Registered hospital calls for the floor opening.
1 = call is registered 0 = call is not registered
Assigned hospital calls for the floor opening
1 = Call is assigned 0 = Call is not assigned
The car is eligible for hospital Emergency Service Operation for the floor opening.
1 = Hospital emergency call can be entered for the floor opening
0 = Hospital emergency call cannot be entered for the floor opening
Floor # 17
Floor # 18
Floor # 19
Floor # 20
Floor # 21
Floor # 22
Floor # 23
Floor # 24
Floor # 25
Floor # 26
Floor # 27
Floor # 28
Floor # 29
Floor # 30
Floor # 31
Floor # 32
Floor # 1
Floor # 2
Floor # 3
Floor # 4
Floor # 5
Floor # 6
Floor # 7
Floor # 8
Floor # 9
Floor # 10
Floor # 11
Floor # 12
Floor # 13
Floor # 14
Floor # 15
Floor # 16
4
4-55
User Interface
F3: System Mode
System mode allows the user to change certain system-wide options that do not require the car to be on Inspection. To enter System mode:
• Move the F3 switch to the up position (all others down).
• Press N to select the desired System Mode item.
• Building Security Menu (see
page 4-56
)
• Passcode Request Menu (see page 4-59 )
• Load Weigher Thresholds (see
page 4-60 )
• Analog Load Weigher Learn Function (see
page 4-60 )
• Controller System Menu - real time speed and position indication (see page 4-52 )
Building Security Menu
Elevator Security is used to limit access to specified floors to passengers with a valid security code. The Security code for each floor is a sequence of button presses on the car operating panel and may consist of from one to eight “characters”. Any floor with a programmed security code is a secured floor when Security is ON. Security is turned ON or OFF by the controller Building
Security Input (BSI) in combination with the BSI Security Key parameter in the Extra Features
Menu (Program mode). There are three possible settings for the BSI Security Key: ACTIVATED,
ENABLED, and DEACTIVATED:
• If set to ACTIVATED, Security is ON.
• If set to ENABLED, Security is ON when the BSI input is turned ON.
• If set to DEACTIVATED, Security is OFF regardless of the status of BSI.
To find the BSI input, refer to the job prints. When Security is ON, car calls are registered only if the call is not to a secured floor or the call is to a secured floor and the security code is correctly entered within 10 seconds.
4-56 Manual # 42-02-2P25
Motion 4000
Viewing The Building Security Menu
1. Place the F3 switch in the up position (all other switches down). The following display appears:
2. Press the N push button. The following display appears:
F3: System Mode
Programming And Viewing The Security Codes
1. Press S to start changing or viewing Security codes.
If no code has been programmed, the computer displays NO CODE PROGRAMMED for that particular floor.
Press S again to start programming the Security code.
If a code has already been programmed, the computer displays the security code with the floor number blinking.
2. Press + to increment or ber.
–
to decrement floor num-
3. Press S to move to the first character (COP button to be pressed) of the security code. Use + or
–
to change value.
4. Repeat until the desired number of characters are programmed (maximum 8). If any character is left blank, or after all eight characters have been programmed, the S button will return the cursor to the floor number.
5. Continue to program Security codes for all floors.
You may exit the Building Security Menu at any time by pressing the N button. When N is pressed, the
LCD will display:
6. Press S to exit or N to return to the previous display.
If S is pressed, the following will appear (if changes have been made).:
7. Press S to save or N to exit without saving (previous codes will remain in effect if changes are not saved).
4-57
4
User Interface
Controller System Menu
This menu provides real time position and speed information and allows you to bypass faults in both Automatic and Inspection operating modes when required for system tests. It also provides access to a data trap required by ASME A17.2000 code.
• AUTOMATIC MODE FAULT BYPASS. JUMPER MUST BE INSTALLED TO ACTIVATE.
• In order to activate, a jumper must also be installed on Fault
Bypass jumper JP2 on the CTL-2 board. When faults are bypassed, certain faults will not be generated.
• INSPECTION MODE FAULT BYPASS. JUMPER MUST BE
INSTALLED TO ACTIVATE.
• In order to activate, a jumper must also be installed on Fault Bypass jumper JP2 on the CTL-2 board. When faults are bypassed, certain faults will not be generated.
• CHNL A: 0mm
CHNL B: 0mm
• Displays the raw position reported by the two (A and B) sensors in the landing system sensor head. Useful to check functionality and travel direction.
• POSTN: 0.0 IN
SPEED: 0 FPM
• Displays current car position in inches above the bottom floor level position and the car speed in feet per minute.
• PLD ETS OVERSPEED BYPASS
JP2 JUMPER MUST BE INSTALLED TO ACTIVATE
• In order to activate, a jumper must also be installed on Fault Reset jumper JP2 on the
CTL-2 board. When active, this option bypasses the Contract and ETS over-speed functionality on the CTL PLD. The bypass will time-out after 15 minutes.
• PLD ACCESS 75FPM OVERSPEED BYPASS
JP2 JUMPER MUST BE INSTALLED TO ACTIVATE
• In order to activate, a jumper must also be installed on Fault Reset jumper JP2 on the
CTL-2 board. When active, this option bypasses the hoistway access over-speed functionality on the CTL PLD. The bypass will time-out after 15 minutes.
• PLD INSPECTION OVERSPEED BYPASS
JP2 JUMPER MUST BE INSTALLED TO ACTIVATE
• In order to activate, a jumper must also be installed on Fault Reset jumper JP2 on the
CTL-2 board. When active, this option bypasses the inspection operation over-speed functionality on the CTL PLD. The bypass will time-out after 15 minutes.
4-58 Manual # 42-02-2P25
Motion 4000
F3: System Mode
Passcode Request Menu
The Passcode Request Operation can be used to require password entry to run the car on any mode of operation other than Inspection.
Note
If a passcode has not been programmed, the Passcode Request Menu will not appear.
If a passcode has been programmed, the LCD screen will flash the “PASSCODE REQUEST” message when Passcode
Request Operation is activated.
In order to clear or set the Passcode Request Operation, the controller must first be placed in System Mode (F3 up, all others down).
• Press N when the display reads “BUILDING SECURITY
MENU.” The Passcode Request Menu will appear:
4
Entering the Passcode
Press S. If Passcode Request Operation is activated, the following screen appears:
The first character of the passcode will blink. Use + - to scroll through numbers 0-9 and letters A-Z for each character. Press N to advance to the next character position.
Press S to verify the entry is correct. If it is not, the following screen will appear:
Press S to try again. Press N to exit.
If the correct passcode was entered, the following screen appears:
Press N to exit. The car may now be run on Normal operation mode.
4-59
User Interface
Activating the Passcode With the Passcode
Request menu displayed, press S. If Passcode Request Operation is not activated, the following display appears:
• Press S to toggle from “NO” to “YES.”
• Press N with “YES” displayed to activate Passcode
Request Operation and exit this screen. With Passcode
Request Operation activated, the passcode must be entered in order to run the car on any mode of operation other than Inspection.
• Press N with “NO” displayed to exit with Passcode Request inactive.
Load Weigher Thresholds
Note
This section is not applicable to discrete input load weighers. Please refer to “Load Weigher” on page 3-22 or to manufacturer instructions for the installed load weigher.
Analog load weighers provide a signal that corresponds to the load in the car. This value is used to make dispatching decisions. Load thresholds are user-programmable.
• LIGHT LOAD WEIGHER (LLW)
• Used to define the load at which the number of car calls will be limited (anti-nuisance).
If the programmed number of car calls is exceeded, all car calls are canceled.
Example: LLW=20%. If the load in the car is less than 20%, the computer will only allow a certain number of car calls to be registered as defined by the parameter LIGHT
LOAD WEIGHING? / LIGHT LOAD CAR CALL LIMIT in the EXTRA FEATURES
MENU OPTIONS. If the limit is set to a value of three, the computer will only allow three calls to be registered if the load is less than 20%. If a fourth call is registered, all car calls will be canceled.
• DISPATCH LOAD WEIGHER (DLW)
• Used to define the load at which the lobby landing door timer will be reduced so that the doors may begin closing sooner, limiting the number of boarders. This threshold should be set to a value (defined in many specifications as 60%) at which it is appropriate to initiate the process of moving the car out of the lobby.
• HEAVY LOAD WEIGHER (HLW)
• Used to define the load value at which additional hall calls should be bypassed to avoid overloading the elevator.
• OVERLOAD WEIGHER (OLW)
• Used to define the load at which it is considered unsafe to move the elevator. When this threshold is exceeded, the car will remain at the floor with doors open and typically sound a buzzer or otherwise indicate that the car is overloaded.
4-60 Manual # 42-02-2P25
Motion 4000
F3: System Mode
Adjusting Thresholds
Typical values for load thresholds are shown below. Thresholds are user-adjustable.
To adjust thresholds
1. Enter SYSTEM mode (F3 up, all others down).
2. Press N until LOAD WEIGHER THRESHOLDS appears on the LCD.
3. Press S to display the load threshold you wish to set.
4. The value shown is the current threshold value is expressed as a percentage of the full load value (see the explanations above). Press + or - to adjust a value. If a value is set to
0%, that load weigher function is disabled.
5. Press S to select the next threshold to adjust or press N to exit.
6. Place the F3 switch in the down position to exit SYSTEM mode when finished.
If an analog load weigher is used, the Analog Load Weigher Learn Function must be performed before the load weigher system will perform properly.
Analog Load Weigher Learn Function
With the isolated platform load weigher from MCE, the system simply learns the reference values of the empty and fully loaded car weight at any floor. With the crosshead deflection load weigher from K-Tech or the rope stress load weigher from EMCO (using the 0 - 10V analog output), the system must learn the values at each floor because the load varies with car position due to the changing proportion of traveling cable hanging beneath the car and the position of the compensation cables.
The Analog Load Weigher Learn Function is performed as follows:
1. Move the empty car to the floor where the test weights are located. It is best to have one person in the machine room and another person at the floor to load the weights.
2. Place the car on Independent Service operation.
3. Place the F3 switch in the up position and press N to select the Analog Load Weigher
Learn Function (scrolling message is displayed)
• ANALOG LOAD WEIGHER LEARN FUNCTION. PRESS S TO START
4. Press S to start. The computer responds with one of two scrolling messages:
• CAR NOT READY TO LEARN, MUST BE ON INDEPENDENT SERVICE
5. Verify that the car has been placed on Independent Service.
• READY TO LEARN EMPTY CAR VALUES? PRESS S TO START
6. If the empty car values have already been learned and you want to learn full car values, press N and go to step 9. To begin learning empty car values, press S. The computer displays the message:
• LEARNING EMPTY CAR VALUES. PRESS N TO ABORT
7. If the Extra Features Menu Option “Analog Load Weigher?” is set to K-TECH or EMCO, the car will move to the bottom floor, record the empty car value and then move up, stopping at each floor to record the empty car value. When the top floor has been reached, the car will move back to the floor at which the Analog Load Weigher Learn
Function was begun and the computer will display the scrolling message:
• EMPTY CAR LEARN PROCESS COMPLETED. PRESS S TO CONT.
4
4-61
User Interface
8. If the Extra Features Menu Option “Analog Load Weigher?” is set to MCE, the car will learn the empty car value once and display:
• EMPTY CAR LEARN PROCESS COMPLETED. PRESS S TO CONT.
9. Press S. The computer displays the scrolling message:
• READY TO LEARN FULL CAR VALUES? PRESS S TO START.
10. Place the full load test weights in the car and press S to begin learning full car values.
The computer displays the message:
• LEARNING FULL CAR VALUES. PRESS N TO ABORT.
11. If the Extra Features Menu Option “Analog Load Weigher?” is set to K-TECH or EMCO, the car will move to the bottom floor, record the full car value and then move up, stopping at each floor to record the full car value. When the top floor has been reached, the car will move back to the floor at which the Analog Load Weigher Learn Function was begun and the computer will display the scrolling message:
• FULL CAR LEARN PROCESS COMPLETED. PRESS S TO CONT.
12. If the Extra Features Menu Option “Analog Load Weigher?” is set to MCE, the car will learn the full car value once and then display the message:
• FULL CAR LEARN PROCESS COMPLETED. PRESS S TO CONT.
13. Press S. Place the F3 in the down position and take the car off Independent service.
14. To verify that the Load Weigher Learn Function has been performed successfully, place the F8 switch in the up position. With the test weights in the car, the following should be displayed:
• CURRENT LOAD = 1OO%
15. If the Load Weigher Learn Function has not been performed successfully, the following will be displayed:
• CURRENT LOAD = NOT LEARNED
The Load Weigher Learn Function (empty or full values) may be aborted at any time by pressing the N button. The computer will display the message:
• LEARN PROCESS ABORTED... PRESS S TO CONT.
1. When the S button is pressed the computer displays the scrolling message:
• ANALOG LOAD WEIGHER LEARN FUNCTION. PRESS S TO START
2. At this point, you may exit System Mode by placing the F3 switch in the down position, or you may re-start the learn function by moving the car back to the floor where the test weights are located and pressing S to start (go to step 4).
3. If the empty car values have been learned but the full load learn function was aborted, you need not re-learn the empty car values. Instead, when the message
READY TO
LEARN EMPTY CAR VALUES
is displayed, press N. The computer will display:
• READY TO LEARN FULL CAR VALUES? PRESS S TO START.
4. Press S to begin learning full car values (go to step 10).
4-62 Manual # 42-02-2P25
Motion 4000
F4: Messages and Floor Labels
F4: Messages and Floor Labels
The Messages and Floor Labels menu is used to program the CE fixture displays. To access, move the F4 switch to the up position.
FUNCTION SWITCHES
F8 F7 F6 F5 F4 F3 F2 F1
Messages and Floor Labels
This display changes to:
* MESSAGES AND *
* FLOOR LABELS *
Modify Floor Labels Press the S push button. The display changes to:
- MODIFY FLOOR -
- LABELS -
Press the S push button again. The display changes to:
• Press + or - push buttons to change landing
• Press S push button to move to first label field
• Press + or - push buttons to change field value
• Press S push button to move to next field
FLOOR LABEL FOR
LANDING 01: 001
Landing
Floor label 100’s place
Floor label 10’s place
Floor label 1’s place
• Repeat until entries completed
• Press N push button to exit.
• Note: Spaces for three characters (three character display) are provided. If the display has only two characters, use the two right most spaces (ones and tens place) and leave the left most space (hundreds place) blank.
Modify Message Labels There are ten standard messages that will appear based on the operating status of the elevator. For example, if the car doors are in nudging mode, the “03” message will be displayed. The factory default for the 03 message is _ND but you may choose to set it to any three spaces or characters, for example, NUD. Factory defaults are listed below. The
10 “custom” labels are used by MCE when a customer requests a non-standard feature.
Table 4.10 Default Message Labels
Message #
09
10
11
12
13
14
15-24
05
06
07
08
01
02
03
04
Operation
Fire Main
Fire Alternate
Nudging
Independent Service
Overload
Emergency Power
Inspection Service
Seismic Sensor
Door Hold
Hospital Phase I
Hospital Phase II
Out of Service
Stop Switch Active
Heavy Load
Custom Messages 01 - 10
_DH
_H1
_H2
_OS
_SA
_HL
_ _ _
_FM
_FA
_ND
_IN
_OL
_EP
_IS
_SS
Label
4
4-63
User Interface
Initialize all Labels DEFAULT LABELS [S] - Yes [N] - No. Use this function to initialize all labels to factory defaults.If you do not wish to complete the command, press and hold -, then press N to exit.
Figure 4.2 PI Entry Procedure
N
* MESSAGES AND *
* FLOOR LABELS *
S
- MODIFY FLOOR -
- LABELS -
S
N
N
-MODIFY MESSAGE-
- LABELS -
S
N
N
-INITIALIZE ALL-
- LABELS -
S
N
N
FLOOR LABEL FOR
LANDING 01: 001
FIRE MAIN
NUMBER 01: FM
DEFAULT LABELS
[S]-YES [N]-NO
+/-
+/-
N
FLOOR LABEL FOR
LANDING 02: 002
+/-
FIRE ALTERNATE
NUMBER 02 FA
N
+/-
N
FLOOR LABEL FOR
LANDING 02: B
FIRE ALTERNATE
NUMBER 02 AF
N
Custom Messages Message numbers 15 through 24 may be used for custom messages.
Message labels can include numbers, letters and the following characters:
Table 4.11 Characters available for Custom Messages
Character
Programmed
>
?
@
<
=
:
;
Character
Displayed
* space
<
-
>
?
*
4-64 Manual # 42-02-2P25
Motion 4000
F5 Menus
F5 Menus
The F5 switch provides access to several menus:
• Controller Utilities Menu
• Register front and rear car calls, page 4-66
• View and set date and time for controller time stamping,
page 4-66
• View and/or clear the event log, page 4-67
• Default TC-MPI parameters,
page 4-68
• Displays diagnostic registers
• MPI, page 4-69
• LS-EDGE, page 4-96
• CTL A/B,
page 4-114
• COP Diagnostics, page 4-133
• System CAN Bus Data Viewing, page 4-134
• Monitoring & Reporting
• Set up and view Ethernet communications for monitoring applications, page 4-135
• Terminal Limit Utilities Menu,
page 4-138
• Perform UxTS and DxTS Learn
• Perform Terminal Tests
• ETS Position Locator
• FCL Brake Unit Utilities Menu,
page 4-139
• FCL Diagnostic Menu
• FCL Power Data Menu
• Default TC-FCL Parameters
• FCL Adjustment Menu
To view:
F5 up (all others down). Press N to advance through menus. Press S to select a menu.
4
4-65
User Interface
Controller Utilities
Car Call Registration
* CONTROLLER *
*UTILITIES MENU*
+ and N
S
- FRONT CALL -
- REGISTRATION -
S
+ and N
FRONT CAR CALL:
LANDING 01 [OFF]
+/-
+ and N
FRONT CAR CALL:
LANDING 02 [OFF]
S
+ and N
FRONT CAR CALL:
LANDING 02 [ON]
+ and N
N
- REAR CALL -
- REGISTRATION -
S
REAR CAR CALL:
LANDING 01 [OFF]
+/-
REAR CAR CALL:
LANDING 02 [OFF]
S
REAR CAR CALL:
LANDING 02 [ON]
N
- VIEW -
- DATE AND TIME-
+ and N + and N + and N
• +/- to increment or decrement floor numbers
• Press and momentarily hold S to register calls; displays [ON] while held
• Press + and N together to back out of the current display
Date/Time, View / Adjust
1. Press S until Controller Date and Time is displayed.
2. N to select day/month/year/hours/minutes/seconds.
3. + or - to set.
4-66 Manual # 42-02-2P25
Motion 4000
F5 Menus
View Event Log
The event log tracks the most recent system events; each with date and time stamp. Event “01” is the most recent event, with older events numbered “02” through “99” respectively.
1. Press S to view the event log.
An event number and the associated event (usually scrolling due to message length) are displayed on the top line of the display. The time and date (alternating) are displayed on the bottom line.
#01 MPI-B RGOK FAI
C01 08:02:11
#02 MPI-A RGOK FAI
C01 08:02:11
4
2. Press + to increment to the next event. (Press - to decrement events.)
3. Press N to exit event viewing.
Additional Information Certain input and output conditions are important to almost all events. While displaying any event, the status of these inputs/outputs is viewable:
• With an event displayed, press S for additional information:
Column PI: Floor at which event occurred.
Rows D1 and D2 Input/Output State Indicators: 0 = OFF, 1 = ON
Actual Display
PI D1: 00000000
31 D2: 00000011
Interpreted Display
D1: 0 0 0 0 0 0 0 0
SAF SAFH SAFC DOLR DOL DLK UPDO DNDO
D2: 0 0 0 0 0 0 1 1
DZR DZ LU LD UPS DNS USD DSD
D1 Indicator to Corresponding Input
D2 Indicator to Corresponding Input
Table 4.12 Event Message Additional Information
D1 Definition
SAF Safety String, combined
SAFH Safety String, hoistway
SAFC Safety String, car
DOLR Door Open Limit, Rear
DOL Door Open Limit, Front
DLK Door Lock Input
UPDO Up Direction Output
DNDO Down Direction Output
D2 Definition
DZR Door Zone, Rear
DZ Door Zone, Front
LU
LD
Level Up
Level Down
UPS Up Direction Sense Input
DNS Down Direction Sense Input
USD Up Slowdown Input
DSD Down Slowdown Input
• Press S again to return to event log standard display.
4-67
User Interface
Clear Event Log
This allows you to clear the events from the event log.
1. Press S to select the clear function.
A prompt will appear allowing you to back out without clearing events (Yes/No).
2. To clear the log press the S button when prompted.
A message will appear notifying you that all events have been cleared.
Default TC-MPI Parameters
This selection allows you to default the TC-MPI board to factory defaults.
1. Press S to select.
2. Press S to confirm or N to back out.
3. Message MPI Parameters are defaulted will be displayed.
Use the F7 function to upload the defaulted parameters from the TC-MPI (
F7: Parameters
Adjust on page 4-141 ).
4-68 Manual # 42-02-2P25
Motion 4000
F5 Menus
MPI Diagnostic Menu
These diagnostics allow you to view car motion parameters (speed/distance) as the car moves through the hoistway. This information in turn will help you make ride adjustments or troubleshoot ride issues.
The initial screen will show either METRIC or ENGLISH units.
1. To switch between Metric or English units, press N once. (Pressing N a second time will back you out of the menu.)
4
Metric or English units may be displayed
2. With the desired measuring units displayed, press S to begin diagnostics display.
The initial display is for MPI-A (Processor A on the MPI board), address zero. This address displays the number of floors served — two in this example.
3. To select the parameter to display, use the S button to move between digits (processor A,
B, or C or address positions 0000 - 9999) — the selected digit will flash — and the Plus
(+) or Minus (-) buttons to change the value of the selected digit.
For example, to display to speed recorded by MPI Processor B the last time the car passed the
Down Normal Terminal switch S2, select MPI-B, address 0019.
1.01 meters per second (Metric) or
200 feet per minute (English)
• To find the address of the data you want to display, check the following tables.
• MPI-A and MPI-B independently collect information from the Elgo positioning sensors. The information they display per address should usually match. However, if you are displaying position information, you need to factor in that the sensors they monitor in the Elgo sensor head are 160 mm (6.3 inches) or 230 mm (9.05 inches) apart.
• MPI-C collects information from the drive/motor/encoder.
As soon as you select an address, the information stored there is displayed.
4-69
User Interface
MPI-A Diagnostics
The following diagnostic information can be viewed for Safety Processor A on the TC-MPI
Motion Processor Interface board.
Table 4.13 MPI-A Diagnostics
Address
26
27
28
23
24
25
20
21
22
17
18
19
36
37
38
39
32
33
34
35
29
30
31
14
15
16
11
12
13
6
7
4
5
8
9
10
2
3
0
1
Item
Front openings
Rear openings
Floors
Bottom floor
Top floor
Bottom landing
Top landing
Bottom position
Top position
Raw position
Absolute position
Relative position
Delta Distance
Offset distance
Delta position errors
Delta speed errors
Processed speed feedback
Raw speed feedback
Speed @ leveling over-speed fault
Speed @ inspection over-speed fault
Speed @ contract over-speed fault
Runtime speed @ DETS
Runtime speed @ DNTS1
Runtime speed @ DNTS2
Runtime speed @ DNTS3
Runtime speed @ DNTS4
Runtime speed @ DNTS5
Runtime speed @ UETS
Runtime speed @ UNTS1
Runtime speed @ UNTS2
Runtime speed @ UNTS3
Runtime speed @ UNTS4
Runtime speed @ UNTS5
Speed @ DETS over-speed fault
Speed @ DNTS1 over-speed fault
Speed @ DNTS2 over-speed fault
Speed @ DNTS3 over-speed fault
Speed @ DNTS4 over-speed fault
Speed @ DNTS5 over-speed fault
Speed @ UETS over-speed fault
Notes
4-70 Manual # 42-02-2P25
Motion 4000
Table 4.13 MPI-A Diagnostics
Address
61
62
63
58
59
60
55
56
57
52
53
54
40
45
46
47
48
94
50
51
41
42
43
44
73
74
75
70
71
72
76
77
78
79
80
67
68
69
64
65
66
Item
Speed @ UNTS1 over-speed fault
Speed @ UNTS2 over-speed fault
Speed @ UNTS3 over-speed fault
Speed @ UNTS4 over-speed fault
Speed @ UNTS5 over-speed fault
Runtime distance @ DETS
Runtime distance @ DNTS1
Runtime distance @ DNTS2
Runtime distance @ DNTS3
Runtime distance @ DNTS4
Runtime distance @ DNTS5
Runtime distance @ UETS
Runtime distance @ UNTS1
Runtime distance @ UNTS2
Runtime distance @ UNTS3
Runtime distance @ UNTS4
Runtime distance @ UNTS5
Distance @ DETS position fault
Distance @ DNTS1 position fault
Distance @ DNTS2 position fault
Distance @ DNTS3 position fault
Distance @ DNTS4 position fault
Distance @ DNTS5 position fault
Distance @ UETS position fault
Distance @ UNTS1 position fault
Distance @ UNTS2 position fault
Distance @ UNTS3 position fault
Distance @ UNTS4 position fault
Distance @ UNTS5 position fault
DETS type
DTS1 type
DNTS2 type
DNTS3 type
DNTS4 type
DNTS5 type
UETS type
UNTS1 type
UNTS2 type
UNTS3 type
UNTS4 type
UNTS5 type
81 Successful runs
Notes
F5 Menus
4
4-71
User Interface
Table 4.13 MPI-A Diagnostics
Address
82
87
88
89
90
83
84
85
86
91
92
93
95
Fault runs
Floor zone
Position bypass count
Position pass count
System position count
Absolute position count
Position lower sequence
Position upper sequence
Position lower value
Position upper value
Landing code
At landing
Near floor
Item
100
101
102
103
Port A inputs: (n/a)
Port B inputs:
01 = TPM
02 = TBR
03 = PMP
04 = BRP
05 = UETS
06 = DETS
07 = SPI1
08 = SPI2
09 = EGOK
10 = RGR1
11 = RGR2
12 = RGOK
13 = EBPS
14 = EB RST
15 = SPI3
16 = SPI4
Port C inputs:
01 = PMDD
02 = (n/a)
03 = (n/a)
04 = (n/a)
05 = (n/a)
06 = (n/a)
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = (n/a)
Port D inputs: (n/a)
4-72 Manual # 42-02-2P25
Notes
Motion 4000
Table 4.13 MPI-A Diagnostics
Address
104
105
106
Port E inputs:
01 = SW2-1
02 = SW2-2
03 = SW2-3
04 = SW2-4
05 = (n/a)
06 = (n/a)
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = (n/a)
Port F inputs: (n/a)
Port G inputs: (n/a)
Item
110
111
Port A outputs:
01 = DIA6A
02 = DIA5A
03 = DIA4A
04 = DIA3A
05 = DIA2A
06 = DIA1A
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = SPA ON LED
11 = UNINTENDED MOTION LED
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = (n/a)
Port B outputs: (n/a)
Notes
F5 Menus
4
4-73
User Interface
Table 4.13 MPI-A Diagnostics
Address
112
113
114
115
116
Port C outputs:
01 = (n/a)
02 = (n/a)
03 = (n/a)
04 = (n/a)
05 = (n/a)
06 = (n/a)
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = OVERSPEED LED
Port D outputs:
01 = DZF
02 = DZR
03 = PME
04 = BRE
05 = DRE
06 = EB1
07 = EB4
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = (n/a)
Port E outputs: (n/a)
Port F outputs: (n/a)
Port G outputs:
01 = (n/a)
02 = (n/a)
03 = DIA7A
04 = DIA8A
05 = (n/a)
06 = (n/a)
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = (n/a)
Item
4-74 Manual # 42-02-2P25
Notes
Motion 4000
Table 4.13 MPI-A Diagnostics
Address
200
201
202
203
Item
Faults (01 - 16):
01 = Maximum position offset fault
02 = Minimum position offset fault
03 = Landing system fault (emergency brake dropped)
04 = Landing system communication loss fault
05 = Unintended motion
06 = SPC is offline
07 = SPB is offline
08 = (n/a)
09 = Inspection over-speed
10 = Contract over-speed
11 = Leveling over-speed
12 = EEPROM CRC error
13 = EEPROM device error
14 = ETS shutdown
15 = UETS over-speed
16 = UETS position error
Faults (17 - 32):
01 = DETS over-speed
02 = DETS position error
03 = Emergency brake cycle test fault
04 = PMDD contactor pick monitor fault
05 = PMDD contactor drop monitor fault
06 = 2L bus monitor fault
07 = RGOK fault (emergency brake dropped)
08 = Actual and requested direction mismatch
09 = Excessive faults shutdown
10 = 2MV bus monitor fault
11 = EBPS monitor fault
12 = UNTS-L over-speed
13 = UNTS-H over-speed
14 = UNTS position error
15 = DNTS-L over-speed
16 = DNTS-H over-speed
Faults (33 - 48):
01 = DNTS position error
02 = RGOK monitor fault
03 = (n/a)
04 = (n/a)
05 = (n/a)
06 = (n/a)
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = (n/a)
Faults (49 - 64): (n/a)
Notes
F5 Menus
4
4-75
User Interface
Table 4.13 MPI-A Diagnostics
Address
300
301
302
16 = BRE (MPI-A)
15 = DRE (MPI-A)
14 = PME (MPI-A)
13 = DRE (MPI-C)
12 = BRE (MPI-C)
11 = PME (MPI-C)
10 = (n/a)
09 = (n/a)
08 = (n/a)
07 = (n/a)
06 = (n/a)
05 = (n/a)
04 = (n/a)
03 = Danger
02 = Fault
01 = Ready
16 = (n/a)
15 = (n/a)
14 = (n/a)
13 = Up slowdown
12 = Down slowdown
11 = Up direction limit
10 = Down direction limit
09 = Front level up
08 = Front door zone
07 = Front level down
06 = Rear level up
05 = Rear door zone
04 = Rear level down
03 = High speed
02 = Up
01 = Down
16 = (n/a)
15 = (n/a)
14 = (n/a)
13 = (n/a)
12 = (n/a)
11 = (n/a)
10 = Up slowdown
09 = Down slowdown
08 = Near top
07 = Near bottom
06 = Up direction limit
05 = Down direction limit
04 = Front door zone
03 = Rear door zone
02 = Up
01 = Down
Item
4-76 Manual # 42-02-2P25
Notes
Motion 4000
408
409
410
411
412
413
414
415
416
400
401
402
403
404
405
406
407
Table 4.13 MPI-A Diagnostics
Address
303
304
Item
16 = UETS status
15 = UTS1 status
14 = UNTS2 status
13 = UNTS3 status
12 = UNTS4 status
11 = UNTS5 status
10 = DETS status
09 = DTS1 status
08 = DNTS2 status
07 = DNTS3 status
06 = DNTS4 status
05 = DNTS5 status
04 = Front door zone
03 = Rear door zone
02 = Up
01 = Down
16 = In rear floor zone
15 = In front floor zone
14 = Emergency brake: check relay fault
13 = Emergency brake: floor unintended motion
12 = Emergency brake: door unintended motion
11 = Emergency brake: governor over-speed
10 = Zone failure
09 = Rear gate failure
08 = Rear lock failure
07 = Front gate failure
06 = Front lock failure
05 = Emergency brake armed
04 = Rear door open
03 = Front door open
02 = In rear door zone
01 = In front door zone
Down distance @ 100% of contract speed
Down distance @ 90% of contract speed
Down distance @ 80% of contract speed
Down distance @ 70% of contract speed
Down distance @ 60% of contract speed
Down distance @ 50% of contract speed
Down distance @ 40% of contract speed
Down distance @ 30% of contract speed
Down distance @ 20% of contract speed
Down distance @ 10% of contract speed
Up distance @ 100% of contract speed
Up distance @ 90% of contract speed
Up distance @ 80% of contract speed
Up distance @ 70% of contract speed
Up distance @ 60% of contract speed
Up distance @ 50% of contract speed
Up distance @ 40% of contract speed
Notes
F5 Menus
4
4-77
User Interface
Table 4.13 MPI-A Diagnostics
Address
417
418
419
Item
Up distance @ 30% of contract speed
Up distance @ 20% of contract speed
Up distance @ 10% of contract speed
Notes
420
421
422
423
Upper Elgo sensor position in m/in
Lower Elgo sensor position in m/in
Median Elgo sensor position in m/in
Elgo sensor offset in m/in
Example: 1.019M. Processed raw position for MPI-B and MPI-C. Median for
MPI-A.
Example: 0.859M. Processed raw position for MPI-A and MPI-C. Median for
MPI-B.
Upper sensor position for MPI-A, lower for MPI-B
Distance between upper and lower sensors. About +160mm for short Elgo sensor head and +240mm for long sensor head.
900
901
902
903
Software ID
Software Revision
Firmware Revision
Hardware Revision
MPI-B Diagnostics
The following diagnostic information can be viewed for Safety Processor B on the TC-MPI
Motion Processor Interface board.
Table 4.14 MPI-B Diagnostics
Address
6
7
8
4
5
2
3
0
1
13
14
15
16
9
10
11
12
Item
Front openings
Rear openings
Floors
Bottom floor
Top floor
Bottom landing
Top landing
Bottom position
Top position
Raw position
Absolute position
Relative position
Delta Distance
Offset distance
Delta position errors
Delta speed errors
Processed speed feedback
Notes
4-78 Manual # 42-02-2P25
Motion 4000
Table 4.14 MPI-B Diagnostics
Address
38
39
40
35
36
37
32
33
34
29
30
31
17
22
23
24
25
26
27
28
18
19
20
21
50
51
52
47
48
94
57
58
59
53
54
55
56
44
45
46
41
42
43
Item
Raw speed feedback
Speed @ leveling over-speed fault
Speed @ inspection over-speed fault
Speed @ contract over-speed fault
Runtime speed @ DETS
Runtime speed @ DNTS1
Runtime speed @ DNTS2
Runtime speed @ DNTS3
Runtime speed @ DNTS4
Runtime speed @ DNTS5
Runtime speed @ UETS
Runtime speed @ UNTS1
Runtime speed @ UNTS2
Runtime speed @ UNTS3
Runtime speed @ UNTS4
Runtime speed @ UNTS5
Speed @ DETS over-speed fault
Speed @ DNTS1 over-speed fault
Speed @ DNTS2 over-speed fault
Speed @ DNTS3 over-speed fault
Speed @ DNTS4 over-speed fault
Speed @ DNTS5 over-speed fault
Speed @ UETS over-speed fault
Speed @ UNTS1 over-speed fault
Speed @ UNTS2 over-speed fault
Speed @ UNTS3 over-speed fault
Speed @ UNTS4 over-speed fault
Speed @ UNTS5 over-speed fault
Runtime distance @ DETS
Runtime distance @ DNTS1
Runtime distance @ DNTS2
Runtime distance @ DNTS3
Runtime distance @ DNTS4
Runtime distance @ DNTS5
Runtime distance @ UETS
Runtime distance @ UNTS1
Runtime distance @ UNTS2
Runtime distance @ UNTS3
Runtime distance @ UNTS4
Runtime distance @ UNTS5
Distance @ DETS position fault
Distance @ DNTS1 position fault
Distance @ DNTS2 position fault
Notes
F5 Menus
4
4-79
User Interface
89
90
91
86
87
88
92
93
95
81
82
83
84
85
100
Table 4.14 MPI-B Diagnostics
Address
78
79
80
75
76
77
72
73
74
69
70
71
60
65
66
67
68
61
62
63
64
Item
Distance @ DNTS3 position fault
Distance @ DNTS4 position fault
Distance @ DNTS5 position fault
Distance @ UETS position fault
Distance @ UNTS1 position fault
Distance @ UNTS2 position fault
Distance @ UNTS3 position fault
Distance @ UNTS4 position fault
Distance @ UNTS5 position fault
DETS type
DTS1 type
DNTS2 type
DNTS3 type
DNTS4 type
DNTS5 type
UETS type
UNTS1 type
UNTS2 type
UNTS3 type
UNTS4 type
UNTS5 type
Successful runs
Fault runs
Floor zone
Position bypass count
Position pass count
System position count
Absolute position count
Position lower sequence
Position upper sequence
Position lower value
Position upper value
Landing code
At landing
Near floor
Port A inputs: (n/a)
4-80 Manual # 42-02-2P25
Notes
Motion 4000
Table 4.14 MPI-B Diagnostics
Address
101
102
103
104
105
106
Port B inputs:
01 = (n/a)
02 = (n/a)
03 = (n/a)
04 = (n/a)
05 = UETS
06 = DETS
07 = (n/a)
08 = (n/a)
09 = EGOK
10 = RGR1
11 = RGR2
12 = RGOK
13 = (n/a)
14 = EB RST
15 = EBPS
16 = (n/a)
Port C inputs: (n/a)
Port D inputs: (n/a)
Port E inputs:
01 = SW1-1
02 = SW1-2
03 = SW1-3
04 = SW1-4
05 = (n/a)
06 = (n/a)
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = (n/a)
Port F inputs: (n/a)
Port G inputs: (n/a)
Item Notes
F5 Menus
4
4-81
User Interface
Table 4.14 MPI-B Diagnostics
Address
110
111
112
113
114
115
Port A outputs:
01 = (n/a)
02 = (n/a)
03 = DIA2B
04 = DIA1B
05 = DIA7B
06 = DIA7B
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = DIA6B
11 = DIA5B
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = DIA8B
16 = DIA8B
Port B outputs: (n/a)
Port C outputs:
01 = (n/a)
02 = (n/a)
03 = (n/a)
04 = (n/a)
05 = (n/a)
06 = (n/a)
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = SPB ON LED
Port D outputs:
01 = (n/a)
02 = (n/a)
03 = PME
04 = BRE
05 = DRE
06 = EB2
07 = EB3
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = (n/a)
Port E outputs: (n/a)
Port F outputs: (n/a)
Item
4-82 Manual # 42-02-2P25
Notes
Motion 4000
Table 4.14 MPI-B Diagnostics
Address
116
Port G outputs:
01 = (n/a)
02 = (n/a)
03 = DIA4B
04 = DIA3B
05 = (n/a)
06 = (n/a)
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = (n/a)
Item
200
201
Faults (01 - 16):
01 = Maximum position offset fault
02 = Minimum position offset fault
03 = Landing system fault (emergency brake dropped)
04 = Landing system communication loss fault
05 = Unintended motion
06 = SPC is offline
07 = SPA is offline
08 = (n/a)
09 = Inspection over-speed
10 = Contract over-speed
11 = Leveling over-speed
12 = EEPROM CRC error
13 = EEPROM device error
14 = ETS shutdown
15 = UETS over-speed
16 = UETS position error
Faults (17 - 32):
01 = DETS over-speed
02 = DETS position error
03 = Emergency brake cycle test fault
04 = PMDD contactor pick monitor fault
05 = PMDD contactor drop monitor fault
06 = 2L bus monitor fault
07 = RGOK fault (emergency brake dropped)
08 = Actual and requested direction mismatch
09 = Excessive faults shutdown
10 = 2MV bus monitor fault
11 = EBPS monitor fault
12 = UNTS-L over-speed
13 = UNTS-H over-speed
14 = UNTS position error
15 = DNTS-L over-speed
16 = DNTS-H over-speed
Notes
F5 Menus
4
4-83
User Interface
Table 4.14 MPI-B Diagnostics
Address
202
203
Item
Faults (33 - 48):
01 = DNTS position error
02 = RGOK monitor fault
03 = (n/a)
04 = (n/a)
05 = (n/a)
06 = (n/a)
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = (n/a)
Faults (49 - 64): (n/a)
300
301
16 = BRE (MPI-B)
15 = DRE (MPI-B)
14 = PME (MPI-B)
13 = DRE (MPI-C)
12 = BRE (MPI-C)
11 = PME (MPI-C)
10 = (n/a)
09 = (n/a)
08 = (n/a)
07 = (n/a)
06 = (n/a)
05 = (n/a)
04 = (n/a)
03 = Danger
02 = Fault
01 = Ready
16 = (n/a)
15 = (n/a)
14 = (n/a)
13 = Up slowdown
12 = Down slowdown
11 = Up direction limit
10 = Down direction limit
09 = Front level up
08 = Front door zone
07 = Front level down
06 = Rear level up
05 = Rear door zone
04 = Rear level down
03 = High speed
02 = Up
01 = Down
4-84 Manual # 42-02-2P25
Notes
Motion 4000
408
409
410
411
412
413
414
415
416
400
401
402
403
404
405
406
407
Table 4.14 MPI-B Diagnostics
Address
302
303
Item
16 = (n/a)
15 = (n/a)
14 = (n/a)
13 = (n/a)
12 = (n/a)
11 = (n/a)
10 = Up slowdown
09 = Down slowdown
08 = Near top
07 = Near bottom
06 = Up direction limit
05 = Down direction limit
04 = Front door zone
03 = Rear door zone
02 = Up
01 = Down
16 = UETS status
15 = UTS1 status
14 = UNTS2 status
13 = UNTS3 status
12 = UNTS4 status
11 = UNTS5 status
10 = DETS status
09 = DNTS1 status
08 = DNTS2 status
07 = DNTS3 status
06 = DNTS4 status
05 = DNTS5 status
04 = Front door zone
03 = Rear door zone
02 = Up
01 = Down
Down distance @ 100% of contract speed
Down distance @ 90% of contract speed
Down distance @ 80% of contract speed
Down distance @ 70% of contract speed
Down distance @ 60% of contract speed
Down distance @ 50% of contract speed
Down distance @ 40% of contract speed
Down distance @ 30% of contract speed
Down distance @ 20% of contract speed
Down distance @ 10% of contract speed
Up distance @ 100% of contract speed
Up distance @ 90% of contract speed
Up distance @ 80% of contract speed
Up distance @ 70% of contract speed
Up distance @ 60% of contract speed
Up distance @ 50% of contract speed
Up distance @ 40% of contract speed
Notes
F5 Menus
4
4-85
User Interface
420
421
422
423
Table 4.14 MPI-B Diagnostics
Address
417
418
419
Item
Up distance @ 30% of contract speed
Up distance @ 20% of contract speed
Up distance @ 10% of contract speed
Upper Elgo sensor position in m/in
Lower Elgo sensor position in m/in
Median Elgo sensor position in m/in
Elgo sensor offset in m/in
900
901
902
903
Software ID
Software Revision
Firmware Revision
Hardware Revision
Notes
Example: 1.019M. Processed raw position for MPI-B and MPI-C. Median for MPI-A.
Example: 0.859M. Processed raw position for MPI-A and MPI-C. Median for MPI-B.
Upper sensor position for MPI-A, lower for
MPI-B
Distance between upper and lower sensors. About +160mm for short Elgo sensor head and +240mm for long sensor head.
4-86 Manual # 42-02-2P25
Motion 4000
F5 Menus
MPI-C Diagnostics
The following diagnostic information can be viewed for Main Processor on the TC-MPI Motion
Processor Interface board.
Table 4.15 MPI-C Diagnostics
Address
26
27
28
23
24
25
20
21
22
17
18
19
36
37
38
39
32
33
34
35
29
30
31
14
15
16
11
12
13
6
7
4
5
8
9
10
2
3
0
1
Item
Front openings
Rear openings
Floors
Bottom floor
Top floor
Bottom landing
Top landing
Bottom position
Top position
Raw position
Absolute position
Relative position
Upper synchronization position errors
Lower synchronization position errors
Delta position errors
Delta Speed errors
Processed speed feedback
Raw speed feedback
Speed command
Speed @ inspection over-speed fault
Speed @ contract over-speed fault
Down distance @ 100% of contract speed
Down distance @ 90% of contract speed
Down distance @ 80% of contract speed
Down distance @ 70% of contract speed
Down distance @ 60% of contract speed
Down distance @ 50% of contract speed
Down distance @ 40% of contract speed
Down distance @ 30% of contract speed
Down distance @ 20% of contract speed
Down distance @ 10% of contract speed
Up distance @ 100% of contract speed
Up distance @ 90% of contract speed
Up distance @ 80% of contract speed
Up distance @ 70% of contract speed
Up distance @ 60% of contract speed
Up distance @ 50% of contract speed
Up distance @ 40% of contract speed
Up distance @ 30% of contract speed
Up distance @ 20% of contract speed
Notes
4-87
4
User Interface
Table 4.15 MPI-C Diagnostics
90
91
92
93
Address
40
82
83
84
85
41
42
43
81
86
94
95
100
101
102
103
Item
Up distance @ 10% of contract speed
Actual landing
Target landing
Logical landing
Successful runs
Fault runs
Control RPM
Position Bypass
Position Pass
Drive:
17-32 = Control command
01-16 = Control input
Lower position
Upper position
Lower speed
Upper speed
Location:
25-32 = Target floor
17-24 = Start floor
09-16 = Below floor
01-08 = Above floor
Near floor
Port A signal: (n/a)
Port B signal:
01 = (n/a)
02 = (n/a)
03 = QEFLT
04 = ZCHAN
05 = ACHAN
06 = BCHAN
07 = (n/a)
08 = (n/a)
09 = DFLT
10 = DRDY
11 = DRO
12 = CWI
13 = EQR
14 = SSI
15 = BUS 2MV
16 = BUS 2L
Port C signal: (n/a)
Port D signal: (n/a)
4-88 Manual # 42-02-2P25
Notes
Motion 4000
Table 4.15 MPI-C Diagnostics
Address
104
105
106
110
111
112
113
Port E signal:
01 = MDRE
02 = (n/a)
03 = (n/a)
04 = (n/a)
05 = (n/a)
06 = (n/a)
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = (n/a)
Port F signal: (n/a)
Port G signal: (n/a)
Port A input: (n/a)
Port B input:
01 = (n/a)
02 = (n/a)
03 = QEFLT
04 = ZCHAN
05 = ACHAN
06 = BCHAN
07 = (n/a)
08 = (n/a)
09 = DFLT
10 = DRDY
11 = DRO
12 = CWI
13 = EQR
14 = SSI
15 = BUS 2MV
16 = BUS 2L
Port C input: (n/a)
Port D input: (n/a)
Item Notes
F5 Menus
4
4-89
User Interface
Table 4.15 MPI-C Diagnostics
Address
114
115
116
120
121
122
Port E input:
01 = MDRE
02 = (n/a)
03 = (n/a)
04 = (n/a)
05 = (n/a)
06 = (n/a)
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = (n/a)
Port F input: (n/a)
Port G input: (n/a)
Port A output:
01 = (n/a)
02 = (n/a)
03 = DIA2C
04 = DIA1C
05 = (n/a)
06 = (n/a)
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = PWR LED
11 = EQ LED
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = (n/a)
Port B output:
01 = DIA5C
02 = DIA6C
03 = (n/a)
04 = (n/a)
05 = (n/a)
06 = (n/a)
07 = DIA4C
08 = DIA3C
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = (n/a)
Port C output: (n/a)
Item
4-90 Manual # 42-02-2P25
Notes
Motion 4000
Table 4.15 MPI-C Diagnostics
Address
123
124
125
126
127
128
129
Port D output:
01 = FBS
02 = EQIND
03 = PME
04 = BRE
05 = DRE
06 = BRC
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = (n/a)
Port E output: (n/a)
Port F output: (n/a)
Port G output:
01 = (n/a)
02 = (n/a)
03 = DIA7C
04 = DIA8C
05 = (n/a)
06 = (n/a)
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = (n/a)
Machine command
Motor command
Brake command
Item Notes
F5 Menus
4
4-91
User Interface
Table 4.15 MPI-C Diagnostics
Address
130
131
132
Item
01 \
02 |
03 |
04 \ Diagnostic switches
05 /
06 |
07 |
08 /
09 = Encoder fault
10 = Encoder channel Z
11 = Encoder channel A
12 = Encoder channel B
13 = Drive fault
14 = Drive ready
15 = Drive on monitor
16 = Counterweight signal
01 = Earthquake reset
02 = Seismic switch
03 = Bus 2
04 = Bus 2L
05 = Bus 2S
06 = Run
07 = Reset
08 = Test
09 = Inspection
10 = Battery
11 = Generator
12 = Earthquake
13 = Conservation
14 = Terminal
15 = Ready
16 = Fault
01 = Safety string
02 = Safety string monitor
03 = Door locks
04 = Door locks monitor
05 = Motor contactor
06 = Motor contactor monitor
07 = Motor contactor proofing
08 = Brake contactor
09 = Brake contactor monitor
10 = Brake contactor proofing
11 = Front level up
12 = Front door zone
13 = Front level down
14 = Rear level up
15 = Rear door zone
16 = Rear level down
4-92 Manual # 42-02-2P25
Notes
Motion 4000
Table 4.15 MPI-C Diagnostics
Address
133
200
201
202
203
Item
01 = Near top
02 = Near bottom
03 = High speed
04 = Up direction limit
05 = Down direction limit
06 = Wind
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = (n/a)
Faults (01-16):
01 = Motor contactor pick fault
02 = Motor contactor drop fault
03 = Brake contactor pick fault
04 = Brake contactor drop fault
05 = Motor contactor pick proofing fault
06 = Motor contactor drop proofing fault
07 = Brake contactor pick proofing fault
08 = Brake contactor drop proofing fault
09 = Drive not ready
10 = Drive fault
11 = Drive on fault
12 = Drive off fault
13 = Receive communication fault
14 = Transmit communication fault
15 = EEPROM CRC fault
16 = EEPROM device fault
Faults (17 - 32):
01 = Drive position mode fault
02 = Inspection over-speed fault
03 = Contract over-speed fault
04 = Excessive faults shutdown
05 = Landing system A position deviation fault
06 = Landing system B position deviation fault
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = (n/a)
Faults (33 - 48): (n/a)
Faults (49 - 64): (n/a)
Notes
F5 Menus
4
4-93
User Interface
Table 4.15 MPI-C Diagnostics
Address
300
301
302
303
Item
16 = Up
15 = Down
14 = High speed
13 = (n/a)
12 = (n/a)
11 = (n/a)
10 = (n/a)
09 = Normal run
08 = Correction run
07 = Inspection run
06 = Terminal
05 = Danger
04 = System Ready
03 = Ready
02 = System fault
01 = Fault
16 = Up
15 = Down
14 = High speed
13 = Front level up
12 = Front door zone
11 = Front level down
10 = Rear level up
09 = Rear door zone
08 = Rear level down
07 = (n/a)
06 = Terminal
05 = Danger
04 = System ready
03 = Ready
02 = System fault
01 = Fault
16 = Up
15 = Down
14 = High speed
13 = Motor contactor monitor
12 = Motor contactor proofing
11 = Motor contactor
10 = Drive active
09 = Drive on monitor
08 = Drive enable
07 = Drive on
06 = Brake contactor monitor
05 = Brake contactor proofing
04 = Brake contactor
03 = Brake enable
02 = Brake pick
01 = Brake on
Machine:
25-32 = Brake State
17-24 = Motor State
09-16 = Machine State
01-08 = Machine Command
4-94 Manual # 42-02-2P25
Notes
Motion 4000
422
423
424
425
426
427
428
429
430
431
432
900
901
902
903
990
991
992
993
994
Table 4.15 MPI-C Diagnostics
Address Item
420 Upper Elgo sensor position in m/in
421 Lower Elgo sensor position in m/in
Elgo sensor offset in m/in
Median sensor position in m/in
Brake command signal
Brake command voltage
Brake command lift rate
Brake command drop rate
Brake pick voltage
Brake hold voltage
Brake relevel voltage
Brake lift rate
Brake drop rate
Software ID
Software Revision
Firmware Revision
Hardware Revision
Maximum Speed
Movements Initiated on Inspection
Corrections Initiated
Relevels Initiated
Movements Initiated on Automatic
F5 Menus
Notes
Example: 1.019M. Processed raw position for MPI-
B and MPI-C. Median for MPI-A.
Example: 0.859M. Processed raw position for MPI-
A and MPI-C. Median for MPI-B.
Distance between upper and lower sensors. About
+160mm for short Elgo sensor head and +240mm for long sensor head.
Upper sensor position for MPI-C.
4
Highest speed attained. Reset MPI-C to clear.
Reset MPI-C to clear.
Reset MPI-C to clear.
Reset MPI-C to clear.
Reset MPI-C to clear.
4-95
User Interface
50
51
52
53
54
40
41
42
43
44
60
30
31
32
33
34
20
21
22
23
24
EDG Diagnostics
See “MPI Diagnostic Menu” on page 4-69 for use instructions.
Table 4.16 LS-EDGE Diagnostics
Address
12
13
14
8
9
10
11
6
7
4
5
2
3
0
1
Floor number
Front Floor 1
Diagnostic
Sensor Flags
Encoder Pair 1
Encoder Pair 1
Encoder Pair 1
Encoder Pair 1
Main Encoder
Measured Correction in Counts
ETS Velocity
ETS Length
Loaded ETS counter
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Front Floor 2
Front Floor 3
Front Floor 4
Front Floor 5
Front Floor 6
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM edge in counts
Floor height (inch or mm)
4-96 Manual # 42-02-2P25
Motion 4000
100
101
102
103
104
90
91
92
93
94
110
111
112
113
114
80
81
82
83
84
70
71
72
73
74
120
121
122
123
124
130
131
Table 4.16 LS-EDGE Diagnostics
Address
61
62
63
64
Floor number Diagnostic
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Front Floor 7
Front Floor 8
Front Floor 9
Front Floor 10
Front Floor 11
Front Floor 12
Front Floor 13
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
F5 Menus
4
4-97
User Interface
180
181
182
183
184
170
171
172
173
174
190
191
192
193
194
200
201
202
160
161
162
163
164
150
151
152
153
154
Table 4.16 LS-EDGE Diagnostics
Address
132
133
134
Floor number
Floor height in counts
DLM edge in counts
ULM_edge in counts
140
141
142
143
144
Front Floor 14
Diagnostic
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Front Floor 15
Front Floor 16
Front Floor 17
Front Floor 18
Front Floor 19
Front Floor 20
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
4-98 Manual # 42-02-2P25
Motion 4000
240
241
242
243
244
230
231
232
233
234
220
221
222
223
224
210
211
212
213
214
260
261
262
263
264
250
251
252
253
254
270
271
272
273
Table 4.16 LS-EDGE Diagnostics
Address
203
204
Floor number
DLM edge in counts
ULM_edge in counts
Front Floor 21
Front Floor 22
Front Floor 23
Front Floor 24
Front Floor 25
Front Floor 26
Front Floor 27
Diagnostic
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
F5 Menus
4
4-99
User Interface
330
331
332
333
334
320
321
322
323
324
310
311
312
313
314
340
341
342
343
344
300
301
302
303
304
290
291
292
293
294
280
281
282
283
284
Table 4.16 LS-EDGE Diagnostics
Address
274
Floor number
ULM_edge in counts
Front Floor 28
Front Floor 29
Front Floor 30
Front Floor 31
Front Floor 32
Front Floor 33
Front Floor 34
Diagnostic
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
4-100 Manual # 42-02-2P25
Motion 4000
380
381
382
383
384
370
371
372
373
374
360
361
362
363
364
350
351
352
353
354
400
401
402
403
404
410
411
412
413
414
390
391
392
393
394
Table 4.16 LS-EDGE Diagnostics
Address Floor number
Front Floor 35
Front Floor 36
Front Floor 37
Front Floor 38
Front Floor 39
Front Floor 40
Front Floor 41
Diagnostic
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
F5 Menus
4
4-101
User Interface
460
461
462
463
464
450
451
452
453
454
440
441
442
443
444
430
431
432
433
434
480
481
482
483
484
490
470
471
472
473
474
Table 4.16 LS-EDGE Diagnostics
Address
420
421
422
423
424
Floor number
Front Floor 42
Diagnostic
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Front Floor 43
Front Floor 44
Front Floor 45
Front Floor 46
Front Floor 47
Front Floor 48
Front Floor 49
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
4-102 Manual # 42-02-2P25
Motion 4000
530
531
532
533
534
520
521
522
523
524
540
541
542
543
544
510
511
512
513
514
500
501
502
503
504
550
551
552
553
554
560
561
Table 4.16 LS-EDGE Diagnostics
Address
491
492
493
494
Floor number Diagnostic
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Front Floor 50
Front Floor 51
Front Floor 52
Front Floor 53
Front Floor 54
Front Floor 55
Front Floor 56
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
F5 Menus
4
4-103
User Interface
610
611
612
613
614
600
601
602
603
604
620
621
622
623
624
630
631
632
590
591
592
593
594
580
581
582
583
584
Table 4.16 LS-EDGE Diagnostics
Address
562
563
564
Floor number
Floor height in counts
DLM edge in counts
ULM_edge in counts
570
571
572
573
574
Front Floor 57
Diagnostic
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Front Floor 58
Front Floor 59
Front Floor 60
Front Floor 61
Front Floor 62
Front Floor 63
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
4-104 Manual # 42-02-2P25
Motion 4000
670
671
672
673
674
660
661
662
663
664
650
651
652
653
654
640
641
642
643
644
690
691
692
693
694
680
681
682
683
684
700
701
702
703
Table 4.16 LS-EDGE Diagnostics
Address
633
634
Floor number
DLM edge in counts
ULM_edge in counts
Front Floor 64
Rear Floor 1
Rear Floor 2
Rear Floor 3
Rear Floor 4
Rear Floor 5
Rear Floor 6
Diagnostic
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
F5 Menus
4
4-105
User Interface
760
761
762
763
764
750
751
752
753
754
740
741
742
743
744
770
771
772
773
774
730
731
732
733
734
720
721
722
723
724
710
711
712
713
714
Table 4.16 LS-EDGE Diagnostics
Address
704
Floor number
ULM_edge in counts
Rear Floor 7
Rear Floor 8
Rear Floor 9
Rear Floor 10
Rear Floor 11
Rear Floor 12
Rear Floor 13
Diagnostic
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
4-106 Manual # 42-02-2P25
Motion 4000
810
811
812
813
814
800
801
802
803
804
790
791
792
793
794
780
781
782
783
784
830
831
832
833
834
840
841
842
843
844
820
821
822
823
824
Table 4.16 LS-EDGE Diagnostics
Address Floor number
Rear Floor 14
Rear Floor 15
Rear Floor 16
Rear Floor 17
Rear Floor 18
Rear Floor 19
Rear Floor 20
Diagnostic
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
F5 Menus
4
4-107
User Interface
890
891
892
893
894
880
881
882
883
884
870
871
872
873
874
860
861
862
863
864
910
911
912
913
914
920
900
901
902
903
904
Table 4.16 LS-EDGE Diagnostics
Address
850
851
852
853
854
Floor number
Rear Floor 21
Diagnostic
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Rear Floor 22
Rear Floor 23
Rear Floor 24
Rear Floor 25
Rear Floor 26
Rear Floor 27
Rear Floor 28
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
4-108 Manual # 42-02-2P25
Motion 4000
960
961
962
963
964
950
951
952
953
954
970
971
972
973
974
940
941
942
943
944
930
931
932
933
934
980
981
982
983
984
990
991
Table 4.16 LS-EDGE Diagnostics
Address
921
922
923
924
Floor number Diagnostic
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Rear Floor 29
Rear Floor 30
Rear Floor 31
Rear Floor 32
Rear Floor 33
Rear Floor 34
Rear Floor 35
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
F5 Menus
4
4-109
User Interface
1030
1031
1032
1033
1034
1040
1041
1042
1043
1044
1050
1051
1052
1053
1054
1060
1061
1062
1010
1011
1012
1013
1014
1020
1021
1022
1023
1024
Table 4.16 LS-EDGE Diagnostics
Address
992
993
994
Floor number
Floor height in counts
DLM edge in counts
ULM_edge in counts
1000
1001
1002
1003
1004
Rear Floor 36
Diagnostic
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Rear Floor 37
Rear Floor 38
Rear Floor 39
Rear Floor 40
Rear Floor 41
Rear Floor 42
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
4-110 Manual # 42-02-2P25
Motion 4000
1090
1091
1092
1093
1094
1100
1101
1102
1103
1104
1070
1071
1072
1073
1074
1080
1081
1082
1083
1084
1110
1111
1112
1113
1114
1120
1121
1122
1123
1124
1130
1131
1132
1133
Table 4.16 LS-EDGE Diagnostics
Address
1063
1064
Floor number
DLM edge in counts
ULM_edge in counts
Rear Floor 43
Rear Floor 44
Rear Floor 45
Rear Floor 46
Rear Floor 47
Rear Floor 48
Rear Floor 49
Diagnostic
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
F5 Menus
4
4-111
User Interface
Table 4.16 LS-EDGE Diagnostics
Address
1134
Floor number
ULM_edge in counts
Rear Floor 50
1160
1161
1162
1163
1164
1170
1171
1172
1173
1174
1180
1181
1182
1183
1184
1190
1191
1192
1193
1194
1200
1201
1202
1203
1204
1140
1141
1142
1143
1144
1150
1151
1152
1153
1154
Rear Floor 51
Rear Floor 52
Rear Floor 53
Rear Floor 54
Rear Floor 55
Rear Floor 56
Diagnostic
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
4-112 Manual # 42-02-2P25
Motion 4000
1230
1231
1232
1233
1234
1240
1241
1242
1243
1244
1210
1211
1212
1213
1214
1220
1221
1222
1223
1224
1250
1251
1252
1253
1254
1260
1261
1262
1263
1264
1270
1271
1272
1273
1274
Table 4.16 LS-EDGE Diagnostics
Address Floor number
Rear Floor 57
Rear Floor 58
Rear Floor 59
Rear Floor 60
Rear Floor 61
Rear Floor 62
Rear Floor 63
Diagnostic
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
Floor height (inch or mm)
Measured magnet length in counts
Floor height in counts
DLM edge in counts
ULM_edge in counts
F5 Menus
4
4-113
User Interface
CTL A Diagnostics
See “MPI Diagnostic Menu” on page 4-69 for use instructions.
Table 4.17 Controller Board CTL A Processor Diagnostics
Address
28
29
30
31
24
25
26
27
20
21
22
23
16
17
18
19
36
37
38
39
40
32
33
34
35
12
13
14
15
8
9
10
11
6
7
4
5
2
3
0
1
Item
Front openings
Rear openings
Floors
Bottom floor
Top floor
Bottom landing
Top landing
Bottom position
Top position
Raw position
Absolute position
Relative position
Delta Distance
Offset distance
Delta position errors
Delta speed errors
Processed speed feedback
Raw speed feedback
Speed @ leveling over-speed fault
Speed @ inspection over-speed fault
Speed @ contract over-speed fault
Runtime speed @ DETS
Runtime speed @ DNTS1
Runtime speed @ DNTS2
Runtime speed @ DNTS3
Runtime speed @ DNTS4
Runtime speed @ DNTS5
Runtime speed @ UETS
Runtime speed @ UNTS1
Runtime speed @ UNTS2
Runtime speed @ UNTS3
Runtime speed @ UNTS4
Runtime speed @ UNTS5
Speed @ DETS over-speed fault
Speed @ DNTS1 over-speed fault
Speed @ DNTS2 over-speed fault
Speed @ DNTS3 over-speed fault
Speed @ DNTS4 over-speed fault
Speed @ DNTS5 over-speed fault
Speed @ UETS over-speed fault
Speed @ UNTS1 over-speed fault
4-114 Manual # 42-02-2P25
Notes
Motion 4000
Table 4.17 Controller Board CTL A Processor Diagnostics
Address
62
63
64
59
60
61
56
57
58
53
54
55
41
46
47
48
94
50
51
52
42
43
44
45
74
75
76
71
72
73
77
78
79
80
68
69
70
65
66
67
Item
Speed @ UNTS2 over-speed fault
Speed @ UNTS3 over-speed fault
Speed @ UNTS4 over-speed fault
Speed @ UNTS5 over-speed fault
Runtime distance @ DETS
Runtime distance @ DNTS1
Runtime distance @ DNTS2
Runtime distance @ DNTS3
Runtime distance @ DNTS4
Runtime distance @ DNTS5
Runtime distance @ UETS
Runtime distance @ UNTS1
Runtime distance @ UNTS2
Runtime distance @ UNTS3
Runtime distance @ UNTS4
Runtime distance @ UNTS5
Distance @ DETS position fault
Distance @ DNTS1 position fault
Distance @ DNTS2 position fault
Distance @ DNTS3 position fault
Distance @ DNTS4 position fault
Distance @ DNTS5 position fault
Distance @ UETS position fault
Distance @ UNTS1 position fault
Distance @ UNTS2 position fault
Distance @ UNTS3 position fault
Distance @ UNTS4 position fault
Distance @ UNTS5 position fault
DETS type
DTS1 type
DNTS2 type
DNTS3 type
DNTS4 type
DNTS5 type
UETS type
UNTS1 type
UNTS2 type
UNTS3 type
UNTS4 type
UNTS5 type
81
82
Successful runs
Fault runs
Notes
F5 Menus
4
4-115
User Interface
Table 4.17 Controller Board CTL A Processor Diagnostics
Address
83
88
89
90
91
84
85
86
87
92
93
95
Item
Floor zone
Position bypass count
Position pass count
System position count
Absolute position count
Position lower sequence
Position upper sequence
Position lower value
Position upper value
Landing code
At landing
Near floor
100
101
Port A inputs:
01 = (n/a)
02 = (n/a)
03 = (n/a)
04 = MHDBR
05 = (n/a)
06 = (n/a)
07 = FRA
08 = FRON
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = FRSM
14 = FRS
15 = (n/a)
16 = (n/a)
Port B inputs:
01 = HDBO
02 = M2MV
03 = FRES
04 = CDBO
05 = MGB
06 = INA
07 = INN
08 = INCP
09 = MGS
10 = ICTD
11 = ICTU
12 = INCT
13 = MREN
14 = MRIN
15 = MRUP
16 = MSAFS1
Notes
4-116 Manual # 42-02-2P25
Motion 4000
Table 4.17 Controller Board CTL A Processor Diagnostics
Address Item
102
103
104
Port C inputs:
01 = (n/a)
02 = PHE
03 = MCSB
04 = MGBR
05 = FRSA
06 = (n/a)
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = (n/a)
Port D inputs:
01 = SAFSD
02 = CSBA
03 = SAFLD
04 = DZLV
05 = ABGA
06 = GBR
07 = MREN
08 = INCT
09 = INCTU
10 = INN
11 = HDB
12 = HDBR
13 = ABTA
14 = TAB
15 = BAB
16 = ABGRA
Port E inputs:
01 = MABB
02 = DCAB
03 = MDLR
04 = MGSR
05 = FCCC
06 = FCS
07 = FCOFF
08 = HLD
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = (n/a)
Notes
F5 Menus
4
4-117
User Interface
Table 4.17 Controller Board CTL A Processor Diagnostics
Address Item
105
106
Port F inputs:
01 = (n/a)
02 = (n/a)
03 = SPD0A
04 = SPD1A
05 = SPD2A
06 = (n/a)
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = FLT RESET
14 = (n/a)
15 = (n/a)
16 = (n/a)
Port G inputs:
01 = (n/a)
02 = (n/a)
03 = (n/a)
04 = (n/a)
05 = (n/a)
06 = (n/a)
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = DSLA
14 = USLA
15 = UETSA
16 = DETSA
110
111
Port A outputs:
01 = (n/a)
02 = (n/a)
03 = ICTD
04 = (n/a)
05 = (n/a)
06 = (n/a)
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = SPOUT1
11 = SPOUT2
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = SPOUT3
16 = SPOUT4
Port B outputs: (n/a)
4-118 Manual # 42-02-2P25
Notes
Motion 4000
Table 4.17 Controller Board CTL A Processor Diagnostics
Address
112
113
114
115
116
Port C outputs:
01 = (n/a)
02 = (n/a)
03 = (n/a)
04 = (n/a)
05 = (n/a)
06 = (n/a)
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = CTL-A ON LED
Port D outputs: (n/a)
Port E outputs: (n/a)
Port F outputs:
01 = (n/a)
02 = (n/a)
03 = (n/a)
04 = (n/a)
05 = (n/a)
06 = DIA1
07 = DIA2
08 = DIA3
09 = DIA4
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = (n/a)
Port G outputs: (n/a)
Item Notes
F5 Menus
4
4-119
User Interface
Table 4.17 Controller Board CTL A Processor Diagnostics
Address
200
201
202
203
Item
Faults (01 - 16):
01 = Maximum position offset fault
02 = Minimum position offset fault
03 = Landing system communication loss fault
04 = Excessive faults shutdown
05 = FCL-1 is offline
06 = FCL-2 is offline
07 = Landing system ETS fault
08 = MPU-A is offline
09 = Inspection over-speed
10 = Contract over-speed
11 = Leveling over-speed
12 = Up normal limit open
13 = Down normal limit open
14 = ETS shutdown
15 = UETS over-speed
16 = UETS position error
Faults (17 - 32):
01 = DETS over-speed
02 = DETS position error
03 = Drive not ready
04 = Drive fault
05 = Drive on fault
06 = EEPROM error (CRC / device)
07 = Incorrect landing system channel detected
08 = Actual and requested direction mismatch
09 = UNTS-L over-speed
10 = UNTS-H over-speed
11 = UNTS position error
12 = DNTS-L over-speed
13 = DNTS-H over-speed
14 = DNTS position error
15 = Landing system floor checksum error
16 = landing system ETS checksum error
Faults (33 - 48):
01 = (n/a)
02 = (n/a)
03 = (n/a)
04 = (n/a)
05 = (n/a)
06 = (n/a)
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = (n/a)
Faults (49 - 64): (n/a)
Notes
4-120 Manual # 42-02-2P25
Motion 4000
Table 4.17 Controller Board CTL A Processor Diagnostics
Address
300
301
302
Item
16 = BRE (MPI-A)
15 = DRE (MPI-A)
14 = PME (MPI-A)
13 = DRE (MPI-C)
12 = BRE (MPI-C)
11 = PME (MPI-C)
10 = (n/a)
09 = (n/a)
08 = (n/a)
07 = (n/a)
06 = (n/a)
05 = (n/a)
04 = (n/a)
03 = Danger
02 = Fault
01 = Ready
16 = (n/a)
15 = (n/a)
14 = (n/a)
13 = Up slowdown
12 = Down slowdown
11 = Up direction limit
10 = Down direction limit
09 = Front level up
08 = Front door zone
07 = Front level down
06 = Rear level up
05 = Rear door zone
04 = Rear level down
03 = High speed
02 = Up
01 = Down
16 = (n/a)
15 = (n/a)
14 = (n/a)
13 = (n/a)
12 = (n/a)
11 = (n/a)
10 = Up slowdown
09 = Down slowdown
08 = Near top
07 = Near bottom
06 = Up direction limit
05 = Down direction limit
04 = Front door zone
03 = Rear door zone
02 = Up
01 = Down
Notes
F5 Menus
4
4-121
User Interface
408
409
410
411
412
413
414
415
416
400
401
402
403
404
405
406
407
Table 4.17 Controller Board CTL A Processor Diagnostics
Address
303
304
Item
16 = UETS status
15 = UTS1 status
14 = UNTS2 status
13 = UNTS3 status
12 = UNTS4 status
11 = UNTS5 status
10 = DETS status
09 = DTS1 status
08 = DNTS2 status
07 = DNTS3 status
06 = DNTS4 status
05 = DNTS5 status
04 = Front door zone
03 = Rear door zone
02 = Up
01 = Down
16 = In rear floor zone
15 = In front floor zone
14 = Emergency brake: check relay fault
13 = Emergency brake: floor unintended motion
12 = Emergency brake: door unintended motion
11 = Emergency brake: governor over-speed
10 = Zone failure
09 = Rear gate failure
08 = Rear lock failure
07 = Front gate failure
06 = Front lock failure
05 = Emergency brake armed
04 = Rear door open
03 = Front door open
02 = In rear door zone
01 = In front door zone
Down distance @ 100% of contract speed
Down distance @ 90% of contract speed
Down distance @ 80% of contract speed
Down distance @ 70% of contract speed
Down distance @ 60% of contract speed
Down distance @ 50% of contract speed
Down distance @ 40% of contract speed
Down distance @ 30% of contract speed
Down distance @ 20% of contract speed
Down distance @ 10% of contract speed
Up distance @ 100% of contract speed
Up distance @ 90% of contract speed
Up distance @ 80% of contract speed
Up distance @ 70% of contract speed
Up distance @ 60% of contract speed
Up distance @ 50% of contract speed
Up distance @ 40% of contract speed
4-122 Manual # 42-02-2P25
Notes
Motion 4000
Table 4.17 Controller Board CTL A Processor Diagnostics
Address
417
418
419
Item
Up distance @ 30% of contract speed
Up distance @ 20% of contract speed
Up distance @ 10% of contract speed
420
421
422
423
900
901
902
903
904
905
906
907
908
909
910
911
912
913
914
915
916
917
1000
1001
1002
1003
Upper position
Lower position
Median position
Offset distance
Software ID
Software Revision
Firmware Revision
Hardware Revision
CAN1 receiver - overflow counter
CAN1 receiver - invalid message counter
CAN1 transmitter - bus off counter
CAN1 receiver - bus passive counter
CAN1 transmitter - bus passive counter
CAN1 receiver - bus warning counter
CAN1 transmitter - bus warning counter
CAN2 receiver - overflow counter
CAN2 receiver - invalid message counter
CAN2 transmitter - bus off counter
CAN2 receiver - bus passive counter
CAN2 transmitter - bus passive counter
CAN2 receiver - bus warning counter
CAN2 transmitter - bus warning counter
CTL-PLD port A
CTL-PLD port B
CTL-PLD port C
CTL-PLD port D
1010 CTL-PLD mode
Notes
F5 Menus
4
4-123
User Interface
CTL B Diagnostics
See “MPI Diagnostic Menu” on page 4-69 for use instructions.
Table 4.18 Controller Board CTL B Processor Diagnostics
Address
28
29
30
31
24
25
26
27
20
21
22
23
16
17
18
19
36
37
38
39
40
32
33
34
35
12
13
14
15
8
9
10
11
6
7
4
5
2
3
0
1
Item
Front openings
Rear openings
Floors
Bottom floor
Top floor
Bottom landing
Top landing
Bottom position
Top position
Raw position
Absolute position
Relative position
Delta Distance
Offset distance
Delta position errors
Delta speed errors
Processed speed feedback
Raw speed feedback
Speed @ leveling over-speed fault
Speed @ inspection over-speed fault
Speed @ contract over-speed fault
Runtime speed @ DETS
Runtime speed @ DNTS1
Runtime speed @ DNTS2
Runtime speed @ DNTS3
Runtime speed @ DNTS4
Runtime speed @ DNTS5
Runtime speed @ UETS
Runtime speed @ UNTS1
Runtime speed @ UNTS2
Runtime speed @ UNTS3
Runtime speed @ UNTS4
Runtime speed @ UNTS5
Speed @ DETS over-speed fault
Speed @ DNTS1 over-speed fault
Speed @ DNTS2 over-speed fault
Speed @ DNTS3 over-speed fault
Speed @ DNTS4 over-speed fault
Speed @ DNTS5 over-speed fault
Speed @ UETS over-speed fault
Speed @ UNTS1 over-speed fault
4-124 Manual # 42-02-2P25
Notes
Motion 4000
Table 4.18 Controller Board CTL B Processor Diagnostics
Address
62
63
64
59
60
61
56
57
58
53
54
55
41
46
47
48
94
50
51
52
42
43
44
45
74
75
76
71
72
73
77
78
79
80
68
69
70
65
66
67
Item
Speed @ UNTS2 over-speed fault
Speed @ UNTS3 over-speed fault
Speed @ UNTS4 over-speed fault
Speed @ UNTS5 over-speed fault
Runtime distance @ DETS
Runtime distance @ DNTS1
Runtime distance @ DNTS2
Runtime distance @ DNTS3
Runtime distance @ DNTS4
Runtime distance @ DNTS5
Runtime distance @ UETS
Runtime distance @ UNTS1
Runtime distance @ UNTS2
Runtime distance @ UNTS3
Runtime distance @ UNTS4
Runtime distance @ UNTS5
Distance @ DETS position fault
Distance @ DNTS1 position fault
Distance @ DNTS2 position fault
Distance @ DNTS3 position fault
Distance @ DNTS4 position fault
Distance @ DNTS5 position fault
Distance @ UETS position fault
Distance @ UNTS1 position fault
Distance @ UNTS2 position fault
Distance @ UNTS3 position fault
Distance @ UNTS4 position fault
Distance @ UNTS5 position fault
DETS type
DTS1 type
DNTS2 type
DNTS3 type
DNTS4 type
DNTS5 type
UETS type
UNTS1 type
UNTS2 type
UNTS3 type
UNTS4 type
UNTS5 type
81
82
Successful runs
Fault runs
Notes
F5 Menus
4
4-125
User Interface
Table 4.18 Controller Board CTL B Processor Diagnostics
Address
83
88
89
90
91
84
85
86
87
92
93
95
Item
Floor zone
Position bypass count
Position pass count
System position count
Absolute position count
Position lower sequence
Position upper sequence
Position lower value
Position upper value
Landing code
At landing
Near floor
100
101
Port A inputs:
01 = SPD0
02 = SPD1
03 = SPD2
04 = UETS
05 = DETS
06 = SPIN7
07 = DZ
08 = DCL
09 = (n/a)
10 = SPIN8
11 = IND
12 = (n/a)
13 = MRDN
14 = DCABR
15 = DOB
16 = DCB
Port B inputs:
01 = DZR
02 = MABGR
03 = GSR
04 = MBAB
05 = MTAB
06 = MABT
07 = DLR
08 = DL
09 = ABD
10 = ABU
11 = ATD
12 = ATU
13 = SPIN10
14 = SPIN9
15 = ICEN
16 = CTEN
Notes
4-126 Manual # 42-02-2P25
Motion 4000
Table 4.18 Controller Board CTL B Processor Diagnostics
Address Item
102
103
104
105
106
Port C inputs:
01 = (n/a)
02 = MSAFL1
03 = MDZLV
04 = MABGF
05 = GS
06 = (n/a)
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = (n/a)
Port D inputs: (n/a)
Port E inputs:
01 = DOL
02 = DPM
03 = SPIN1
04 = SPIN2
05 = SPIN3
06 = SPIN4
07 = SPIN5
08 = SPIN6
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = (n/a)
Port F inputs:
01 = (n/a)
02 = (n/a)
03 = MHDB
04 = FLTBYPS
05 = (n/a)
06 = (n/a)
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = (n/a)
Port G inputs: (n/a)
Notes
F5 Menus
4
4-127
User Interface
Table 4.18 Controller Board CTL B Processor Diagnostics
Address
110
111
112
113
114
115
Port A outputs: (n/a)
Port B outputs: (n/a)
Port C outputs:
01 = (n/a)
02 = (n/a)
03 = (n/a)
04 = (n/a)
05 = (n/a)
06 = (n/a)
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = CTL-B ON LED
Port D outputs:
01 = SAFSD
02 = CSBB
03 = GB
04 = FWL
05 = FWI
06 = NBZ
07 = FBYP
08 = CTC
09 = FSLL
10 = ABBB
11 = ICPD
12 = ICPU
13 = DOF
14 = DCP/RCO
15 = DCF
16 = NUDG
Port E outputs: (n/a)
Port F outputs:
01 = (n/a)
02 = (n/a)
03 = (n/a)
04 = RST1 PLD
05 = (n/a)
06 = (n/a)
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = (n/a)
Item
4-128 Manual # 42-02-2P25
Notes
Motion 4000
Table 4.18 Controller Board CTL B Processor Diagnostics
Address Item
116
Port G outputs:
01 = (n/a)
02 = (n/a)
03 = (n/a)
04 = (n/a)
05 = (n/a)
06 = (n/a)
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = DIA1
14 = DIA2
15 = DIA3
16 = DIA4
200
201
Faults (01 - 16):
01 = Maximum position offset fault
02 = Minimum position offset fault
03 = Landing system communication loss fault
04 = Excessive faults shutdown
05 = FCL-3 is offline
06 = FCL-4 is offline
07 = Landing system ETS fault
08 =LS-EDGE CPU-B is offline
09 = Inspection over-speed
10 = Contract over-speed
11 = Leveling over-speed
12 = Up normal limit open
13 = Down normal limit open
14 = ETS shutdown
15 = UETS over-speed
16 = UETS position error
Faults (17 - 32):
01 = DETS over-speed
02 = DETS position error
03 = Drive not ready
04 = Drive fault
05 = Drive on fault
06 = EEPROM error (CRC / device)
07 = Incorrect landing system channel detected
08 = Actual and requested direction mismatch
09 = UNTS-L over-speed
10 = UNTS-H over-speed
11 = UNTS position error
12 = DNTS-L over-speed
13 = DNTS-H over-speed
14 = DNTS position error
15 = Landing system floor checksum error
16 = Landing system ETS checksum error
Notes
F5 Menus
4
4-129
User Interface
Table 4.18 Controller Board CTL B Processor Diagnostics
Address
202
203
Faults (33 - 48):
01 = (n/a)
02 = (n/a)
03 = (n/a)
04 = (n/a)
05 = (n/a)
06 = (n/a)
07 = (n/a)
08 = (n/a)
09 = (n/a)
10 = (n/a)
11 = (n/a)
12 = (n/a)
13 = (n/a)
14 = (n/a)
15 = (n/a)
16 = (n/a)
Faults (49 - 64): (n/a)
Item
300
301
16 = BRE (MPI-B)
15 = DRE (MPI-B)
14 = PME (MPI-B)
13 = DRE (MPI-C)
12 = BRE (MPI-C)
11 = PME (MPI-C)
10 = (n/a)
09 = (n/a)
08 = (n/a)
07 = (n/a)
06 = (n/a)
05 = (n/a)
04 = (n/a)
03 = Danger
02 = Fault
01 = Ready
16 = (n/a)
15 = (n/a)
14 = (n/a)
13 = Up slowdown
12 = Down slowdown
11 = Up direction limit
10 = Down direction limit
09 = Front level up
08 = Front door zone
07 = Front level down
06 = Rear level up
05 = Rear door zone
04 = Rear level down
03 = High speed
02 = Up
01 = Down
Notes
4-130 Manual # 42-02-2P25
Motion 4000
408
409
410
411
412
413
414
415
416
400
401
402
403
404
405
406
407
Table 4.18 Controller Board CTL B Processor Diagnostics
Address
302
303
Item
16 = (n/a)
15 = (n/a)
14 = (n/a)
13 = (n/a)
12 = (n/a)
11 = (n/a)
10 = Up slowdown
09 = Down slowdown
08 = Near top
07 = Near bottom
06 = Up direction limit
05 = Down direction limit
04 = Front door zone
03 = Rear door zone
02 = Up
01 = Down
16 = UETS status
15 = UTS1 status
14 = UNTS2 status
13 = UNTS3 status
12 = UNTS4 status
11 = UNTS5 status
10 = DETS status
09 = DNTS1 status
08 = DNTS2 status
07 = DNTS3 status
06 = DNTS4 status
05 = DNTS5 status
04 = Front door zone
03 = Rear door zone
02 = Up
01 = Down
Down distance @ 100% of contract speed
Down distance @ 90% of contract speed
Down distance @ 80% of contract speed
Down distance @ 70% of contract speed
Down distance @ 60% of contract speed
Down distance @ 50% of contract speed
Down distance @ 40% of contract speed
Down distance @ 30% of contract speed
Down distance @ 20% of contract speed
Down distance @ 10% of contract speed
Up distance @ 100% of contract speed
Up distance @ 90% of contract speed
Up distance @ 80% of contract speed
Up distance @ 70% of contract speed
Up distance @ 60% of contract speed
Up distance @ 50% of contract speed
Up distance @ 40% of contract speed
Notes
F5 Menus
4-131
4
User Interface
Table 4.18 Controller Board CTL B Processor Diagnostics
Address
417
418
419
Item
Up distance @ 30% of contract speed
Up distance @ 20% of contract speed
Up distance @ 10% of contract speed
420
421
422
423
900
901
902
903
904
905
906
907
908
909
910
911
912
913
914
915
916
917
1000
1001
1002
1003
Upper position
Lower position
Median position
Offset distance
Software ID
Software Revision
Firmware Revision
Hardware Revision
CAN1 receiver - overflow counter
CAN1 receiver - invalid message counter
CAN1 transmitter - bus off counter
CAN1 receiver - bus passive counter
CAN1 transmitter - bus passive counter
CAN1 receiver - bus warning counter
CAN1 transmitter - bus warning counter
CAN2 receiver - overflow counter
CAN2 receiver - invalid message counter
CAN2 transmitter - bus off counter
CAN2 receiver - bus passive counter
CAN2 transmitter - bus passive counter
CAN2 receiver - bus warning counter
CAN2 transmitter - bus warning counter
CTL-PLD port A
CTL-PLD port B
CTL-PLD port C
CTL-PLD port D
1010 CTL-PLD mode
Notes
4-132 Manual # 42-02-2P25
Motion 4000
F5 Menus
COP Diagnostics Menu
This menu allows you to view diagnostics on the ICE-COP-2 Car Operating Panel (COP) inter-
face board(s). For more information about using the diagnostics see “MPI Diagnostic Menu” on page 4-69.
Table 4.19 COP Diagnostics
Address
40
42
43
48
24
26
29
30
49
50
20
21
22
23
16
17
18
19
12
13
14
15
8
9
10
11
6
7
4
5
2
3
0
1
Description Comments
Voltage on terminal IO1
Voltage on terminal IO2
Voltage on terminal IO3
Voltage on terminal IO4
Voltage on terminal IO5
Voltage on terminal IO6
Voltage on terminal IO7
Voltage on terminal IO8
Voltage on terminal IO9
Voltage on terminal IO10
Voltage on terminal IO11
Voltage on terminal IO12
Voltage on terminal IO13
Voltage on terminal IO14
Voltage on terminal IO15
Voltage on terminal IO16
Voltage on terminal IO17
Voltage on terminal IO18
Voltage on terminal IO19
Voltage on terminal IO20
Voltage on terminal IO21
Voltage on terminal IO22
Voltage on terminal IO23
Voltage on terminal IO24
Power supply voltage
CAN board ID number
CAN message received
Used when communicating
Increments with each message received
CAN message transmitted Increments with each message transmitted
Voltage sum
S2 DIP Switch settings
Averaged power supply voltage measurement
0 = off, 1 = on
Flag from controller will shut of relays when set Force relays off
Power supply voltage max
Power supply voltage min
Good voltage count
Variance between max & min indicates ripple
If count is less than 100, inputs are disabled
4
4-133
User Interface
System CAN Bus
The System CAN Bus/Data Viewing screen allows you to check the working status of the inputs and outputs of any Car Panel Interface board in the system.
SYSTEM CAN BUS
*DATA VIEWING*
• Press S to enter the menu
CID| 00 00 00 00
1C1| 0A 10 00 01
Byte 0
CAN Data Bytes in Hex
Byte 7
Three digit MC-CPI address (see table below)
• Use the + or - buttons to increment/decrement address digit value
• Use the S button to move from digit to digit
• As soon as a valid ID is on the screen, the CAN data from that ID will be visible as the hex data for each CAN byte changes.
• With the desired ID selected, you can place a call from the affected control panel, or press a Door Open button, etc. and view the data transfer on the CAN bus.
1C8
1C9
1CA
1CB
1CC
1CD
1CE
1CF
1C0
1C1
1C2
1C3
1C4
1C5
1C6
1C7
Table 4.20 MC-CPI Board Addresses
ID DATA
Output activity CPI board “0”
Input activity CPI board “0”
Output activity CPI board “1”
Input activity CPI board “1”
Output activity CPI board “2”
Input activity CPI board “2”
Output activity CPI board “3”
Input activity CPI board “3”
Output activity CPI board “4”
Input activity CPI board “4”
Output activity CPI board “5”
Input activity CPI board “5”
Output activity CPI board “6”
Input activity CPI board “6”
Output activity CPI board “7”
Input activity CPI board “7”
If CAN data is not appearing: Please refer to “Status and Error Messages” on page 5-2, entry
“
MPI A or B LANDING SYSTEM COMM LOSS
” for relevant CAN connection car-to-controller troubleshooting information.
4-134 Manual # 42-02-2P25
Motion 4000
F5 Menus
Monitoring and Reporting Menu
If the controller is configured for monitoring or reporting connections through Ethernet, this menu is used to set up the port and to view communication statistics for diagnostic purposes.
• With “Monitoring and Reporting Menu” displayed, press S to enter the menu. The first screen provides a way to exit the menu without making changes. Press N to continue.
4
• The next screen provides the version number of the monitoring software in the controller.
Press N to continue.
• The monitored type screen displays the controller type being monitored.
• Press N to move on. The IP address screen allows the IP address to be set:
See note on following page.
• Press S to move from digit to digit.
• Press + or - to change value.
• Press N to exit.
• The subnet mask screen allows the mask address to be set:
See note on following page.
4-135
User Interface
• The gateway screen allows the gateway address to be set:
See note below.
Note
Any time you make a change to IP address, Subnet Mask, or Gateway Address, you must reset the HC-CHP board (Device) or the XPort. Refer to the information following.
Diagnostics, Refresh, Reset
The following screens provide diagnostic information, and allow Device and XPort refresh (poll for current data) or reset.
• The connections screen indicates which client connections are active. The XPort has the ability to connect to up to six iMonitors. This screen tells you how many connections are currently active.
• The floors screen provides, left-to-right, the number of cars configured, if the car is a duplex dispatcher (D) or a local (L), and the number of floors configured.
Number of cars configured
Car is dispatcher (D) or local (L)
Number of floors configured
• The XPort Comm Resets screen indicates the number of times the port has been reset since the last HC-CHP reset. If it exceeds three, you may have a network problem.
4-136 Manual # 42-02-2P25
Motion 4000
F5 Menus
• The Receive/Transmit screen monitors the current number of receive and transmit messages in the XPort queue, the peak number of messages in that queue, and the maximum acceptable number of messages in each queue.
4
• The error diagnostic displays those data points being checked for change.
E = Events
P = Parameters
M = Monitors
• The Device Data screen displays the data byte in a particular register.
Data present
Register address
• The iReport screen shows the current status of iReport connections (None, Conn, Wait), and the last iReport Port and IP address that was connected.
Port
Status: None, Conn, Wait
IP address
• The Reset XPort screen allows you to reset the XPort and related counters. Resetting is required after changing IP address, Subnet mask, or Gateway address.
• Refresh Device allows you to trigger an immediate data gathering cycle to ensure you are seeing the latest processor information.
4-137
User Interface
• Refresh XPort allows you to trigger an immediate data gathering cycle to ensure you are seeing the latest XPort information (IP address, Gateway address, Subnet Mask, and Type of controller).
• The TFTP Status screen allows you to provide permission for an FTP updater to update the monitoring software on this controller.
• The Default XPort screen allows you to default the XPort to original factory programming.
Terminal Limit Utilities Menu
This menu allows you to:
• Perform UxTS and DxTS Learn Operation
• Perform Terminal Tests
• Use the ETS POSITION LOCATOR
Terminal Switch Learn
- PERFORM UXTS -
- AND DXTS LEARN -
Please refer to Slowdown Learn, ETS Placement, Elgo on page 3-4 or Slowdown Learn, ETS
Placement on page 3-5 (LS-EDGE).
Perform Terminal Tests
Please refer to “Normal and Emergency Terminal Switch Tests” on page 3-41 .
ETS Position Locator
Please refer to “Slowdown Learn, ETS Placement, Elgo” on page 3-4 Slowdown Learn, ETS
Placement on page 3-5 (LS-EDGE).
4-138 Manual # 42-02-2P25
Motion 4000
F5 Menus
FCL Brake Unit Utilities Menu
This menu allows you to check CAN controlled brake module function, check commanded and actual pick voltage/amperage, default module TC-FCL parameters or calibrate a selected module TC-FCL for use on the Motion 4000 controller. Navigate to this menu using the N button, then select it using the S button to access sub-menus. Navigate between sub-menus using the N button. Review Brake Module on page 2-12 for information about module addressing and functionality.
FCL Diagnostic Menu
The FCL diagnostic menu allows data in particular module registries to be examined to diagnose board-level activity. If you are having a problem with a module and you suspect it is a problem with one of the module circuit boards, contact MCE Technical Support so that a technician can work with you to determine whether or not the module is faulty. Generically:
• Use S to move to the module number digit, then +/- to set.
• Use S to move to the register address fields, then +/- to set.
• The LCD will display data present in the selected module register
FCL Power Data Menu
The FCL power data menu allows you to see commanded and actual pick voltage and amperage for a selected brake module.
• Use +/- to select the module.
• CMD: Commanded voltage
• V: Actual applied voltage
• A: Actual applied amperage
Default TC-FCL Parameters
This menu allows you to select a specific module, then default its values to factory settings.
• Place car on Machine Room Inspection
• Use +/- to select the module. Press S to default
• The module values will be defaulted to factory values
FCL Adjustment Menu
This menu is used to calibrate a selected module to Motion 4000 requirements.
• Place car on Machine Room Inspection
• Use +/- to select the module. Press S to calibrate
• The selected module will be calibrated and progress reported on the display
4
4-139
User Interface
F6: Hoistway Learn Operations
The F6 menu provides a process to learn the floor levels and counterweight position for the building. The process is different depending on the type of landing/positioning system for the job.
ELGO Encoded Magnetic Tape
Please refer to “ELGO Encoded Magnetic Tape” on page 3-3 .
LS-EDGE Steel Tape
Please refer to “Hoistway Learn, LS-EDGE” on page 3-5 .
Adjusting Floor Heights
Stored floor heights may be accessed through the F7 menu (first 64 parameters) and the height of each floor individually adjusted at any time. F7 parameter 67 allows you to adjust the counterweight height.
1. Enter the F7 menu (F7 up, all other switches down).
2. Press N to advance to the desired parameter.
3. Use “+” or “-” buttons to adjust the height of the floor (or counterweight).
4. Place F7 in the down position.
4-140 Manual # 42-02-2P25
Motion 4000
F7: Parameters Adjust
F7: Parameters Adjust
Through the F7 menu, you can restore and/or adjust settings for terminal, position, and motion parameters. With the car on Inspection and the F7 function switch in the UP position, the N button is used to cycle between the two (Restore or Adjust) menus.
Important Once set at the factory, F7 parameters are protected by positioning a jumper on the HC-CTL-2 board. Before you can access F7 parameters, you must set the jumper appropriately:
4
F7 SETTABLE
Restore Parameters
Parameters are stored on both the HC-CTL-2 and the TC-MPI boards. The parameters stored on either board may be used to restore (synchronize) those stored on the other:
1. Place the car on Inspection operation.
2. Set the F7 function switch in the UP position.
3. Press N until the LCD displays PARAMETER RESTORE MENU. Press S to select.
The LCD will display RESTORE SETTINGS FROM: followed by the currently selected board
(HC-CTL or TC-MPI).
4. Press + or - to display the desired board. Press S to restore (or N to return to the previous menu).
The LCD will provide read and restore status and direct you to press N to return to the last viewed or edited parameter.
Changing Parameters
1. Place the car on Inspection operation.
2. Set the F7 function switch to the up position.
3. Press N until the LCD displays PARAMETER ADJUST MENU. Press S to select. The
LCD will display ADJUST FROM N=LAST / S=START.
• Press N to begin adjustment from the last viewed or edited parameter.
• Press S to begin adjustment starting with the first F7 parameter.
4. Once viewing parameters:
• Press N to move through the parameters listings.
• Press + or - to change a displayed parameters value.
• To move back to a previous parameter, press and hold N (Next) then press - (minus) as needed
• Press S to save changed parameters.
4-141
User Interface
Controller Parameter/Drive Parameter Interaction
There are very important things to consider about the interaction between motion parameters set on the drive and the setting or collection of motion parameters on the controller.
• Drive parameters LF.20 Contract Speed and LF.11 Motor RPM determine the drive’s Estimated Gear Ratio, LF.25. The drive will not drive the motor any faster than determined by the Gear Ratio set at LF.22. Please refer to “Speed and Acceleration Control” on page 2-30 .
Note
MOTION / DISTANCE DIAGNOSTIC displays are provided through the F5 menu. They can be very helpful in seeing what is actually happening in the hoistway and using that information
to fine tune settings or diagnose fault conditions. Please refer to “MPI Diagnostic Menu” on page 4-69 .
4-142 Manual # 42-02-2P25
Motion 4000
F7: Parameters Adjust
Using ID Numbers for Direct Parameter Access
All F7 parameters have a fixed ID number. When you are in the F7 menu, you can scroll to a particular ID by:
• Press and hold N (Next) to increment to the desired ID.
• Press and hold N, then press and hold - (minus) to decrement to the desired ID.
The table below lists the ID numbers and corresponding parameters. (There is a table that you can record your settings in on page A-14 of the appendix.)
Table 4.21 F7 Parameters
29
30
31
32
25
26
27
28
21
22
23
24
17
18
19
20
33
34
35
36
37
38
13
14
15
16
9
10
11
12
7
8
5
6
3
4
1
2
# Item
Floor 17
Floor 18
Floor 19
Floor 20
Floor 21
Floor 22
Floor 23
Floor 24
Floor 25
Floor 26
Floor 27
Floor 28
Floor 29
Floor 30
Floor 31
Floor 32
Floor 1
Floor 2
Floor 3
Floor 4
Floor 5
Floor 6
Floor 7
Floor 8
Floor 9
Floor 10
Floor 11
Floor 12
Floor 13
Floor 14
Floor 15
Floor 16
Floor 33
Floor 34
Floor 35
Floor 36
Floor 37
Floor 38
Min
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
Default Max
0.0 in
+120.0 in
+240.0 in
+360.0 in
+480.0 in
+600.0 in
+720.0 in
+840.0 in
+12000.0 in
+12000.0 in
+12000.0 in
+12000.0 in
+12000.0 in
+12000.0 in
+12000.0 in
+12000.0 in
+960.0 in +12000.0 in
+1080.0 in +12000.0 in
+1200.0 in +12000.0 in
+1320.0 in +12000.0 in
+1440.0 in +12000.0 in
+1560.0 in +12000.0 in
+1680.0 in +12000.0 in
+1800.0 in +12000.0 in
+1920.0 in +12000.0 in
+2040.0 in +12000.0 in
+2160.0 in +12000.0 in
+2280.0 in +12000.0 in
+2400.0 in +12000.0 in
+2520.0 in +12000.0 in
+2640.0 in +12000.0 in
+2760.0 in +12000.0 in
+2880.0 in +12000.0 in
+3000.0 in +12000.0 in
+3120.0 in +12000.0 in
+3240.0 in +12000.0 in
+3360.0 in +12000.0 in
+3480.0 in +12000.0 in
+3600.0 in +12000.0 in
+3720.0 in +12000.0 in
+3840.0 in +12000.0 in
+3960.0 in +12000.0 in
+4080.0 in +12000.0 in
+4200.0 in +12000.0 in
+4320.0 in +12000.0 in
+4440.0 in +12000.0 in
Notes
4-143
4
User Interface
75
76
77
78
79
80
69
70
71
72
73
74
65
66
67
68
Floor 39
Floor 40
Floor 41
Floor 42
Floor 43
Floor 44
Floor 45
Floor 46
Floor 47
Floor 48
Floor 49
Floor 50
Floor 51
Floor 52
Floor 53
Floor 54
Floor 55
Floor 56
Floor 57
Floor 58
Floor 59
Floor 60
Floor 61
Floor 62
Floor 63
Floor 64
Table 4.21 F7 Parameters
51
52
53
54
47
48
49
50
43
44
45
46
39
40
41
42
59
60
61
62
55
56
57
58
63
64
# Item Min
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
-12.0 in
Bottom access distance 0.0 in
Top access distance 0.0 in
Counterweight position 0.0 in
Directional limit distance
0.0 in
U/DETS
U/DNT1
U/DNT2
U/DNT3
U/DNT4
U/DNT5
UETS speed
UETS distance
UETS delta distance
UETS delta speed
UNTS1 speed
UNTS1 distance
0 fpm
-1200.0 in
-120.0 in
0 fpm
0 fpm
-1200.0 in
Default Max
+4560.0 in +12000.0 in
+4680.0 in +12000.0 in
+4800.0 in +12000.0 in
+4920.0 in +12000.0 in
+5040.0 in +12000.0 in
+5160.0 in +12000.0 in
+5280.0 in +12000.0 in
+5400.0 in +12000.0 in
+5520.0 in +12000.0 in
+5640.0 in +12000.0 in
+5760.0 in +12000.0 in
+5880.0 in +12000.0 in
+6000.0 in +12000.0 in
+6120.0 in +12000.0 in
+6240.0 in +12000.0 in
+6360.0 in +12000.0 in
+6480.0 in +12000.0 in
+6600.0 in +12000.0 in
+6600.0 in +12000.0 in
+6720.0 in +12000.0 in
+6840.0 in +12000.0 in
+6960.0 in +12000.0 in
+7080.0 in +12000.0 in
+7200.0 in +12000.0 in
+7320.0 in +12000.0 in
+7440.0 in +12000.0 in
+120.0 in
+120.0 in
+540.0 in
+2.0 in
+12000.0 in
+12000.0 in
+12000.0 in
+1200.0 in
VIRTUAL
VIRTUAL
UNUSED
UNUSED
UNUSED
UNUSED
+332 fpm
+48.0 in
+6.0 in
20 fpm
0 fpm
+95.9 in
+900 fpm
+1200.0 in
+120.0 in
+900 fpm
+900 fpm
+1200.0 in
Notes
UNUSED, VIRTUAL, PHYSICAL
UNUSED, VIRTUAL, PHYSICAL
UNUSED, VIRTUAL, PHYSICAL
UNUSED, VIRTUAL, PHYSICAL
UNUSED, VIRTUAL, PHYSICAL
UNUSED, VIRTUAL, PHYSICAL
4-144 Manual # 42-02-2P25
Motion 4000
Table 4.21 F7 Parameters
81
82
83
# Item Min
UNTS1 delta distance -120.0 in
UNTS1 delta low speed 0 fpm
UNTS1 delta high speed 0 fpm
89
90
91
92
93
84
85
86
87
88
UNTS2 speed
UNTS2 distance
0 fpm
-1200.0 in
UNTS2 delta distance -120.0 in
UNTS2 delta low speed 0 fpm
UNTS2 delta high speed 0 fpm
UNTS3 speed
UNTS3 distance
0 fpm
-1200.0 in
UNTS3 delta distance -120.0 in
UNTS3 delta low speed 0 fpm
UNTS3 delta high speed 0 fpm
94
95
96
97
98
UNTS4 speed
UNTS4 distance
0 fpm
-1200.0 in
UNTS4 delta distance -120.0 in
UNTS4 delta low speed 0 fpm
UNTS4 delta high speed 0 fpm
99 UNTS5 speed
100 UNTS5 distance
0 fpm
-1200.0 in
101 UNTS5 delta distance -120.0 in
102 UNTS5 delta low speed 0 fpm
103 UNTS5 delta high speed 0 fpm
104 DETS speed
105 DETS distance
106 DETS delta distance
107 DETS delta speed
0 fpm
-1200.0 in
-120.0 in
0 fpm
108 DNTS1 speed 0 fpm
109 DNTS1 distance -1200.0 in
110 DNTS1 delta distance -120.0 in
111 DNTS1 delta low speed 0 fpm
112 DNTS1 delta high speed 0 fpm
113 DNTS2 speed 0 fpm
114 DNTS2 distance -1200.0 in
115 DNTS2 delta distance -120.0 in
116 DNTS2 delta low speed 0 fpm
117 DNTS2 delta high speed 0 fpm
118 DNTS3 speed
119 DNTS3 distance
0 fpm
-1200.0 in
+332 fpm
+48.0 in
+6.0 in
0 fpm
0 fpm
+95.9 in
+6.0 in
0 fpm
0 fpm
0 fpm
0.0 in
+6.0 in
0 fpm
0 fpm
0 fpm
0.0 in
Default
+6.0 in
0 fpm
0 fpm
Max
+120.0 in
+900 fpm
+900 fpm
0 fpm
0.0 in
+6.0 in
0 fpm
0 fpm
0 fpm
0.0 in
+6.0 in
0 fpm
0 fpm
0 fpm
0.0 in
+6.0 in
0 fpm
0 fpm
0 fpm
0.0 in
+6.0 in
0 fpm
0 fpm
+900 fpm
+1200.0 in
+120.0 in
+900 fpm
+900 fpm
+900 fpm
+1200.0 in
+120.0 in
+900 fpm
+900 fpm
+900 fpm
+1200.0 in
+120.0 in
+900 fpm
+900 fpm
+900 fpm
+1200.0 in
+120.0 in
+900 fpm
+900 fpm
+900 fpm
+1200.0 in
+120.0 in
+900 fpm
+900 fpm
+1200.0 in
+120.0 in
+900 fpm
+900 fpm
+900 fpm
+1200.0 in
+120.0 in
+900 fpm
+900 fpm
+900 fpm
+1200.0 in
F7: Parameters Adjust
Notes
4-145
4
User Interface
Table 4.21 F7 Parameters
# Item Min
120 DNTS3 delta distance -120.0 in
121 DNTS3 delta low speed 0 fpm
122 DNTS3 delta high speed 0 fpm
123 DNTS4 speed
124 DNTS4 distance
0 fpm
-1200.0 in
125 DNTS4 delta distance -120.0 in
126 DNTS4 delta low speed 0 fpm
127 DNTS4 delta high speed 0 fpm
128 DNTS5 speed
129 DNTS5 distance
0 fpm
-1200.0 in
130 DNTS5 delta distance -120.0 in
131 DNTS5 delta low speed 0 fpm
132 DNTS5 delta high speed 0 fpm
133 Brake pick delay
134 Speed pick delay
135 Brake hold delay
136 Brake drop delay
0 ms
0 ms
0 ms
0 ms
138 Drive disable delay 0 ms
139 Speed hysteresis delay 0 ms
140 Profile advance
141 Profile scale
142 Standard slew slope
143 Danger slew slope
144 Automatic Slew filter
0 ms
0%
0.00 ft/s2
0.00 ft/s2
+0.1 Hz
145 Contract over-speed 0 fpm
146 Inspection over-speed 0 fpm
147 Leveling over-speed 0 fpm
148 Hoist-motor speed
149 Contract speed
150 High speed
151 Intermediate speed
152 Earthquake speed
153 Auxiliary speed
154 Backup power speed
155
156
Inspection speed
(normal)
Inspection speed
(reduced)
157 Correction speed
158 Leveling speed
+1.0 rpm
+25 fpm
+25 fpm
+25 fpm
+25 fpm
+25 fpm
+9 fpm
0 fpm
0 fpm
0 fpm
0 fpm
Default
+6.0 in
0 fpm
0 fpm
0 fpm
0.0 in
+6.0 in
0 fpm
0 fpm
0 fpm
0.0 in
+6.0 in
0 fpm
0 fpm
0 ms
+500 ms
+2000 ms
+500 ms
Max
+120.0 in
+900 fpm
+900 fpm
+900 fpm
+1200.0 in
+120.0 in
+900 fpm
+900 fpm
+900 fpm
+1200.0 in
+120.0 in
+900 fpm
+900 fpm
+10000 ms
+10000 ms
+10000 ms
+2000 ms
Notes
+375 fpm
+125 fpm
+125 fpm
+1165.0 rpm
+350 fpm
+350 fpm
+300 fpm
+150 fpm
+250 fpm
+200 fpm
+50 fpm
+50 fpm
+75 fpm
+4 fpm
+1250 ms
+1000 ms
+2000 ms
+10000 ms
+100 ms
100%
+1000 ms
+1000%
+0.49 ft/s2 +50.00 ft/s2
+10.00 ft/s2 +50.00 ft/s2
+20.0 Hz +20 Hz
+1000 fpm
+148 fpm
148 fpm
+9999.9 rpm
+800 fpm
+800 fpm
+800 fpm
+150 fpm
+800 fpm
+800 fpm
+148 fpm
+148 fpm
+250 fpm
+25 fpm
SPI1 terminal (TC-MPI board)
SPI2 terminal (TC-MPI board)
4-146 Manual # 42-02-2P25
Motion 4000
Table 4.21 F7 Parameters
# Item
159 Re-leveling speed
Min
0 fpm
Default
+6 fpm
Max
+25 fpm
160 Leveling distance
161 Re-leveling distance
162 Proximity distance
163
Leveling dead zone distance
0.0 in
0.0 in
0.0 in
0.0 in
+0.9 in
+0.9 in
+18.0 in
+0.5 in
+9.0 in
+9.0 in
+120.0 in
+3.0 in
165 Standard start jerk
166 Standard roll jerk
+0.10 ft/s3 +4.00 ft/s3 +15.00 ft/s3
+0.10 ft/s3 +4.00 ft/s3 +15.00 ft/s3
167 Standard stop jerk +0.10 ft/s3 +2.00 ft/s3 +15.00 ft/s3
168 Standard acceleration 0.00 ft/s2 +2.00 ft/s2 +10.0 ft/s2
169 Standard deceleration 0.00 ft/s2 +2.00 ft/s2 +10.0 ft/s2
170 Manual start jerk
171 Manual roll jerk
172 Manual stop jerk
173 Manual acceleration
174 Manual deceleration
+0.10 ft/s3
+0.10 ft/s3
+0.10 ft/s3
0.00 ft/s2
0.00 ft/s2
+1.00 ft/s3 +15.00 ft/s3
+1.00 ft/s3 +15.00 ft/s3
+1.00 ft/s3 +15.00 ft/s3
+0.50 ft/s2 +10.0 ft/s2
+0.50 ft/s2 +10.0 ft/s2
175 Danger start jerk
176 Danger roll jerk
177 Danger stop jerk
178 Danger deceleration
+0.10 ft/s3 +25.00 ft/s3 +50.00 ft/s3
+0.10 ft/s3 +25.00 ft/s3 +50.00 ft/s3
+0.10 ft/s3 +4.00 ft/s3 +50.00 ft/s3
0.00 ft/s2 6.00 ft/s2 +15.00 ft/s2
179 Alternate start jerk
180 Alternate roll jerk
181 Alternate stop jerk
+0.10 ft/s3
182 Alternate acceleration 0.00 ft/s2
183 Alternate deceleration 0.00 ft/s2
+2.00 ft/s3 +15.00 ft/s3
+0.10 ft/s3 +2.00 ft/s3 +15.00 ft/s3
+0.10 ft/s3 +2.00 ft/s3 +15.00 ft/s3
+1.50 ft/s2 +10.0 ft/s2
+1.50 ft/s2 +10.0 ft/s2
F7: Parameters Adjust
Notes
184 Drive type
185 Brake type
186 Emergency brake
187 Reduced inspect speed
188 Unintended Motion
189 Following error
190
Sheave Brake Idle
Delay
191 Landing System
0%
30S
KEB F5-
GRD50
DISCRETE
ROPE GRIP-
PER
OFF
LEVEL ZONE
+50%
30S
+1000%
3600S
Elgo 160
KEB F5-GRD49, KEB F5-GLS49,
KEB F5-GRD50, KEB F5-GLS50,
YASKAWA,
MAG QUATTRO,
MAG HPV, MAG DSD
DISCRETE, ONE MODULE, TWO
MODULES
DISABLED, ROPE GRIPPER,
SHEAVE BRK, MACHINE BRK
OFF,
ETS,
NTS1, NTS2, NTS3, NTS4, NTS5
LEVEL ZONE, DOOR ZONE
Elgo-160, Elgo-240, LS-EDGE
4
4-147
User Interface
Table 4.21 F7 Parameters
# Item Min Default Max Notes
192
193
Speed Drop Delay
Profile Compensation
800 ms
Fixed
Magnetek drives only. Time in milliseconds during which the drive should continue to exert motor control after the car has achieved the floor and before the brake has dropped.
Dynamic: Variable, controller determined compensation for drive lag based on entry in parameter 140, Profile Advance.
Fixed: Fixed compensation for drive lag using the parameter
140, Profile Advance setting.
194
195
Normal Brake Pick Voltage
Normal Brake Hold Voltage
0V
0V
196
Normal Brake Relevel
Voltage
0V
197 Normal Brake Lift Rate 0%
198
Normal Brake Drop
Rate
0%
199 Emergency Brake Type
200
Emergency Brake Pick
Voltage
201
Emergency Brake Hold
Voltage
202 Directional Limit Type
0V
0V
203
204
205
Landing System Floor
Checksum
Landing System ETS
Overspeed
Inspection Slew filter
206 Battery Backup Speed
300V
300V
300V
100%
100%
300V
300V
Module or Discrete
VIRTUAL VIRTUAL, PHYSICAL
This is a read only value. When the hoistway is learned with the LS-EDGE landing system, the learned parameters are stored in the landing system sensor and this checksum is both stored in the sensor and sent to the controller.
If the controller should read a different checksum (i.e., if the sensor head is changed), a new hoistway learn must be performed.
0% 10% 100%
Used to set the LS-EDGE landing system hardware ETS overspeed threshold as a percentage of contract speed. Magnets on the landing system tape (one lane for UETS and another for DETS) are monitored by the LS-EDGE, detecting the speed at which the car passes. The controller still allows a virtual/physical ETS switch in addition to the magnets.
+0.1 Hz +20.0 Hz +20 Hz
4-148 Manual # 42-02-2P25
Motion 4000
F7: Parameters Adjust
Parameters
Floor Heights Parameters 1 through 64 represent floor heights within the building.
Floor heights are stored as absolute values referenced to the first floor, which is always initially displayed as 0.0 inches. You have already learned all floor heights in the building (F6), so they will be displayed as you progress. For all floors and openings, you should need only to view data and press Next to continue. They are here so that, should it be necessary later, you can adjust a floor height here without having to relearn all floors.
Figure 4.3 Adjust Floor Height, LCD Layout
Parameter name
Parameter value. Adjust using the + or - buttons.
Parameter ID
4
1. Press Next. The display will update to show the next opening/floor.
2. Continue using Next to move through the floors and openings.
Bottom Access Distance, 65 This sets the distance above the bottom floor level at which the bottom access “switch” is placed. The value is entered in inches (1/10 inch increments). The Bottom Access Distance must be set such that it prevents the car from moving up beyond the point where the bottom of the toe guard is even with the hoistway entrance header.
Top Access Distance, 66 This sets the distance below the top floor level at which the top access “switch” is placed. The value is entered in inches (1/10 inch increments). The Top
Access Distance must be set such that it prevents the car from moving down beyond the point where the crosshead is even with the hoistway entrance sill.
Note
Hoistway Access: Hoistway access allows the car to be moved to gain access to the car top or to the car bottom through hall and car doors. An enable switch in the car operating panel must be set to enable access, at which point switches at designated landings allow the car to be moved down to access the cartop or up to access the car bottom. Safety considerations will normally not allow the car to move with doors open, so Car Door Bypass and Hoistway Door Bypass switches on the HC-CTL-2 board in the controller must also be set to Bypass positions before access is possible.
4-149
User Interface
Counterweight Position, 67 This is the position of the counterweight (in inches above the bottom floor) at which the car and counterweight are adjacent to one another in the hoistway. The value uploaded was learned in the floor level learn procedure. Check the value to see that it equates to approximately 1/2 the total travel of the car. Press Next to move to the next parameter.
Note
Counterweight Position: Leave at the learned value. This parameter is provided here so that, should it be necessary, this position can be adjusted without having to re-learn floor heights.
Directional Limit Distance, 68 This is the distance in inches at which the Directional
Limit “switches” are placed beyond the terminal floor level positions. The value is entered in inches and is computed from the position of terminal floor levels. For example, a value of 2.0 would place the switches 2” past the level at floor position for each terminal.
If the car fails to stop level at the terminal, this “switch” will prevent the car from traveling further past the terminal landing. These “switches” must be positioned between the terminal floor level and the mechanical Final Limit Switches. If a car reaches the Final Limit Switch, the hoistway safety string will open and it will be necessary to jumper out the safeties to move the car off the limit.
Terminal Switch Options, 69 - 74 On Motion 4000, hoistway switches, with the exception of the Final Limit Switches which are always physical switches, may be virtual (exist only in software) or physical. Depending upon job speed, not all switch positions may be used so there is also the option to set a switch position to “Unused.” The illustration below shows the switches that may be used on Motion 4000 (ETS, NTS-1, NTS-2, NTS-3, NTS-4, and NTS-5).
Table 4.22 Hoistway Switch Requirements
UETS/DETS and UNTSX/DNTSX switches requirement as per Rated speed (FPM)
Car
Speed
(FPM)
Up to 399 √
400-499 √
500-599 √
600-699 √
>700 √
UETS/DETS UNTS1/DNTS1 UNTS2/DNTS2 UNTS3/DNTS3 UNTS4/DNTS4 UNTS5/DNTS5
Virtual switch
Learn speed
Virtual switch
Learn speed
Virtual switch
Learn speed
Virtual switch
Learn speed
Virtual switch
Learn speed
Virtual switch
Learn speed
80% √
80% √
80% √
80% √
80% √
90%
70% √
60% √
50%
40%
√
√
90%
70% √
60% √
50% √
90%
70% √
60% √
90%
70% √ 90%
4-150 Manual # 42-02-2P25
Motion 4000
F7: Parameters Adjust
• Use the + or - buttons to select the kind of switch used on your job (Virtual/Physical/
Unused). For jobs below 400 FPM, NTS-1 is used as the Slowdown Limit switch.
Final Limit (mechanical switch)
Directional Limit
Level at floor
Slowdown Limit (*NTS-1)
NTS-2
NTS-3
NTS-4
ETS**
NTS-5
* NTS-1 switch must be always be within the terminal floor.
** ETS switch position will be different depending on car speed.
4
NTS-5
ETS**
NTS-4
NTS-3
NTS-2
Slowdown Limit (*NTS-1)
Level at floor
Directional Limit
Final Limit (mechanical switch)
4-151
User Interface
Speed Related Parameters
Follow the learn operations described in Section 2 of this manual to set up hoistway switches.
The A processor diagnostics table,
MPI-A Diagnostics on page 4-70 , is very helpful in allowing
you to view actual running conditions in the hoistway (speed at switches, etc.), and test your settings as you make adjustments.
UETS Speed, 75 This is the speed, in feet per minute, which the car must be below when opening the Up Emergency Terminal Switch. This value, plus the value of the UETS Delta Speed settings, must not exceed 95% of Contract Speed.
Note
UETS Switch: Depending upon the speed of the job, the Emergency Terminal Switch may be positioned differently. Refer to your job drawings package.
UETS Distance, 76 This is the distance in inches from the top terminal floor level position at which the Up Emergency Terminal Switch is placed. This value is learned: Please refer to
“Learning the Hoistway, Positioning ETS” on page 3-2 .
UETS Delta Distance, 77 This is the distance in inches on either side of the Up Emergency Terminal Switch position inside which the car must detect the Up Emergency Terminal
Switch. If the switch is not detected within this span, the car will perform an emergency stop.
Generally set to 6.0 inches.
UETS Delta Speed, 78 Delta Speed provides an “adder” to UETS speed. UETS speed and Delta speed together may not exceed 95% of contract speed. The switch speed is learned:
Please refer to “Learning the Hoistway, Positioning ETS” on page 3-2 . Initially, calculate the
Delta as 95% of Contract Speed - Learned Speed @ switch = Delta value.
Note
The UETS Speed setting plus the Delta Speed setting determines the speed which the car must be below in order to avoid an emergency stop. If you are tripping an ETS fault during car setup, you can choose to increase the ETS speed above contract speed or disable the ETS switches by setting them to Unused until you have sufficient control of the car.
Reduced Stroke Buffers Where reduced stroke buffers are used, the ETS inputs on the TC-MPI are used as ETSL (Emergency Terminal Slowdown) switches. ETSL position will be located at 90% of the reduced stroke buffer rated speed. ETSL Delta Speed will be 5% of the reduced stroke buffer rated speed. If ETSL is too far below the speed curve, you can adjust the
Delta Speed closer to 10% of the reduced stroke buffer rated speed.
4-152 Manual # 42-02-2P25
Motion 4000
F7: Parameters Adjust
Normal Terminal Switch Parameter Explanations
At contract speeds below 400 FPM, up and down normal terminal switches are not used as traditional limit switches. Instead, Normal Terminal Limit switches 2 - 5 are set to “unused” through controller F7 parameters and Normal Terminal Limit switches 1 Up and 1 Down are used as Terminal Slowdown Switches. The UNTS-1 and DNTS-1 switches also act as final position arbiters for the elevator positioning system.
At contract speeds above 400 FPM, Normal Terminal switches are used as required per contract speed. Each normal terminal switch has distance and speed parameters associated with it:
• xNTSn Speed: Learned value (percentage of normal run contract speed) at or below which the car must be traveling when the switch is encountered to avoid triggering an overspeed fault. If a fault is triggered, car reaction is determined by the Delta Low and Delta High speed settings.
• xNTSn Delta Low Speed: (3% of Learned Speed) If the car is traveling in excess of xNTSn
Speed + xNTSn Delta Low Speed but not in excess of xNTSn Speed + xNTSn Delta High
Speed, the controller will initiate a controlled slowdown to Correction Speed and continue toward the destination floor until reaching Proximity Distance from the landing. From this point, the controller will move the car at leveling speed and level into the landing.
• xNTSn Delta High Speed: (10% of Contract Speed) If the car is traveling in excess of xNTSn Speed + xNTSn Delta High Speed, the controller will initiate an emergency stop by cutting off power to the motor and dropping the machine brake. After coming to a complete stop, the car will travel to the destination floor at Correction Speed until reaching
Proximity Distance from the landing. From this point, the controller will move the car at leveling speed and level into the landing.
• xNTSn Distance: Distance from the terminal at which the switch is located.
• xNTSn Delta Distance: Defines a distance on each side of the switch to establish a range within which the switch must be encountered to avoid triggering a switch position error. If a switch is not encountered within the range, the controller will initiate an emergency stop by cutting off power to the motor and dropping the machine brake. After coming to a complete stop, the car will travel to the terminal floor at reduced speed, open its doors to allow passenger exit, and remove itself from service until the fault is cleared.
Note
Delta speeds are always added to the base speed at the switch. For example, if contract speed is
250 FPM, and learned switch Speed is 200 FPM, the Delta Low Speed is 6 FPM, and the Delta
High Speed is 25 FPM, the low and high overspeed limits will be 206 FPM and 225 FPM respectively.
4
4-153
User Interface
UNTS1 Speed, 79 Learned value (percentage of Contract Speed) at which the car should be traveling when encountering this switch during a normal run to the terminal in order for normal stopping means to properly slow and stop the car. Please refer to “Learning the
Hoistway, Positioning ETS” on page 3-2 .
UNTS1 Distance, 80 This is the distance in inches from the associated terminal floor level position at which this Normal Terminal Switch is placed. This value is learned: Please refer to “Learning the Hoistway, Positioning ETS” on page 3-2 . NTS1 switches also provide a definitive position check for the PI system.
UNTS1 Delta Distance, 81 This is the distance in inches on either side of the Up Normal Terminal Switch 1 position inside which the car must detect the Up Normal Terminal
Switch. If the switch is not detected within this span, the car will drop high speed. Generally set to 6.0 inches.
UNTS1 Delta Low Speed, 82 Nominal value is 3% of Learned Speed.
Please refer to
“Normal Terminal Switch Parameter Explanations” on page 4-153 .
UNTS1 Delta High Speed, 83 Nominal value is 10% of Contract Speed or 20 FPM,
whichever is higher. Please refer to “Normal Terminal Switch Parameter Explanations” on page 4-153 .
UNTS2, 3, 4, 5 Speed, Distance, and Delta just as with UNTS-1 but with distances and speeds per your Contract Speed. For any switch that has been set to “unused”, parameters can all be set to 0.0.
• Below 400 FPM: NTS2/3/4/5 switches normally set to unused unless the job has reduced stroke buffers.
4-154 Manual # 42-02-2P25
Motion 4000
F7: Parameters Adjust
DETS Speed, 104 This is the speed, in feet per minute, which the car must be below when opening the Down Emergency Terminal Switch. This value, plus the value of the DETS
Delta Speed settings, must not exceed 95% of Contract Speed.
Note
DETS Switch: Depending upon the speed of the job, the Emergency Terminal Switch may be positioned differently. Refer to your job drawings package.
DETS Distance, 105 This is the distance in inches from the bottom terminal floor level position at which the Down Emergency Terminal Switch is placed. During a normal run, the car should be at 80% of Contract Speed at this point. This value is learned: Please refer to “Learning the Hoistway, Positioning ETS” on page 3-2 .
DETS Delta Distance, 106 This is the distance in inches on either side of the Down
Emergency Terminal Switch position inside which the car must detect the Down Emergency
Terminal Switch. If the switch is not detected within this span, the car will perform an emergency stop. Generally set to 6.0 inches.
DETS Delta Speed, 107 Delta Speed provides an “adder” to DETS speed. DETS speed and Delta speed together may not exceed 95% of contract speed. The switch speed is learned:
Please refer to “Learning the Hoistway, Positioning ETS” on page 3-2 . Initially, calculate the
Delta as 95% of Contract Speed - Learned Speed @ switch = Delta value.
Note
The DETS Speed setting plus the Delta Speed setting determines the speed which the car must be below in order to avoid an emergency stop. If you are tripping an ETS fault during car setup, you can choose to increase the ETS speed above contract speed or disable the ETS switches by setting them to Unused until you have sufficient control of the car.
DNTS1 Speed, 108 Learned value (percentage of Contract Speed) at which the car should be traveling when encountering this switch during a normal run to the terminal in order for normal stopping means to properly slow and stop the car. Please refer to “Learning the
Hoistway, Positioning ETS” on page 3-2 .
DNTS1 Distance This is the distance in inches from the associated terminal floor level position at which this Normal Terminal Switch is placed. This value is learned: Please refer to
“Learning the Hoistway, Positioning ETS” on page 3-2 . NTS1 switches also provide a definitive position check for the PI system.
DNTS1 Delta Distance, 110 This is the distance in inches on either side of the Down
Normal Terminal Switch 1 position inside which the car must detect the Down Normal Terminal Switch. If the switch is not detected within this span, the car will drop high speed. Generally set to 6.0 inches.
DNTS1 Delta Low Speed, 111 Nominal value is 3% of Learned Speed.
Please refer to
“Normal Terminal Switch Parameter Explanations” on page 4-153 .
DNTS1 Delta High Speed, 112 Nominal value is 10% of Contract Speed or 20 FPM,
whichever is higher. Please refer to “Normal Terminal Switch Parameter Explanations” on page 4-153 .
4
4-155
User Interface
DNTS2, 3, 4, 5 Speed, Distance, and Delta just as with DNTS-1 but with distances and speeds per your Contract Speed. For any switch that has been set to “unused”, parameters can all be set to 0.0.
• For reduced stroke buffers, refer to UNTS2, 3, 4, 5 on page 4-154 .
Brake Pick Delay, 133 The time in milliseconds after the drive enable command is issued and acknowledged before the brake should pick. The default time of 0 (zero) milliseconds should be appropriate for virtually all scenarios.
Speed Pick Delay, 134 The time in milliseconds after the brake is picked before the speed command is issued. This setting is used to prevent beginning movement under a slowpicking brake. The default of 500 milliseconds is a good starting point.
Figure 4.4 Effect of Speed Pick Delay on Start of Motion
Volts
Speed Pick Delay just right
Not enough
Speed Pick Delay
Too much Speed Pick Delay
Time
Brake Lifts
4-156 Manual # 42-02-2P25
Motion 4000
F7: Parameters Adjust
Brake Hold Delay, 135 After take off, the brake is held fully picked until this timer expires, at which point it settles to hold position/voltage. Default time for a geared machine is
2000 ms. Default time for a gearless machine is 800 ms.
Brake Drop Delay, 136 The delay, in milliseconds, that the brake should be delayed from dropping after the speed command is dropped. The goal is to avoid dropping the brake until the motor has just stopped moving. The default time of 250 milliseconds is a good starting point.
Figure 4.5 Effect of Brake Drop Delay on Stopping
Speed
4
Drop Delay just right
Level at Floor
Not enough Drop Delay Too much Drop Delay
Drive Disable Delay, 138 The time in milliseconds after stopping at a floor which the drive should maintain electrical control of the motor. May be used to compensate for a slow dropping brake. The default time of 1250 milliseconds should be appropriate for virtually all scenarios.
Speed Hysteresis Delay, 139 Provides a delay between when the speed command is issued and when it begins to accelerate the load.
Profile Advance, 140 Compensates for lag in the control loop. Values from 50 mS to
130 mS are common.
Profile Scale, 141 Scales the curve to affect all associated speed settings. Typically used to slow all speeds associated with a curve without having to change individual speed settings.
Useful for overspeed tests with the understanding that drive LF.22 will absolutely limit car speed.
Standard Slew Slope, 142 Determines how aggressively or gradually the current speed transitions to zero speed. Sets the maximum deceleration rate that the S curve is allowed to command when the car is stopping from a speed near releveling speed or lower. If the stop is harsh, reducing this value may provide a softer stop.
Danger Slew Slope, 143 Determines how aggressively or gradually the current speed can transition to a lower or higher speed. Sets the maximum rate of acceleration/deceleration the S curve is allowed to command when the car is running and when the car is stopping from a speed greater than releveling speed. Reducing this value forces a more gradual transition.
4-157
User Interface
Slew Filter, 144 Smooths any harsh transitions in the commanded speed for all operating modes except Inspection. Reducing this value causes a smoother transition.
Contract Overspeed, 145 The setting in feet per minute above contract speed at which a contract overspeed is detected and an emergency stop initiated. Generally set to about
8% above contract speed with variance due to the tracking accuracy of the drive/motor.
• 8% x contract speed + contract speed = overspeed
• Example for 350 FPM: 8% of 350 = 28 + 350 = 378 FPM
Inspection Overspeed, 146 The setting in feet per minute above inspection speed at which an inspection overspeed is detected and an emergency stop initiated. Generally set to about 8% above inspection speed with variance due to the tracking accuracy of the drive/motor.
• 8% x inspection speed + inspection speed = overspeed
• Example for 50 FPM: 8% of 50 = 4 + 50 = 54 FPM
Leveling Overspeed, 147 The setting in feet per minute above leveling speed at which a leveling overspeed is detected and an emergency stop initiated. Generally set to about
8% above leveling speed with variance due to the tracking accuracy of the drive/motor.
• 8% x leveling speed + leveling speed = overspeed
• Example for 20 FPM: 8% of 20 = 1.6 + 20 = 21.6 FPM
Hoist Motor Speed, 148 Enter the motor RPM at which the car achieves contract speed (TORQMAX LF.11). This information is available from the motor nameplate and is visible on TORQMAX RU.7 when the car is running at contract speed. This rated motor RPM is the synchronous motor RPM minus slip RPM.
• Example for 6-pole geared machine: 1200 RPM (synchronous), 1165 RPM (rated).
Contract Speed, 149 Enter the contract speed of the car in feet per minute.
High Speed, 150 Enter the high speed limit for the Standard curve. Normally set to the same as Contract Speed. (Can be used to change car speed without changing profile.)
Intermediate Speed, 151 Enter the reduced speed at which the car is to run when the SPI1 (Spare 1) input to the TC-MPI board is active. Intermediate speed uses the standard curve.
Earthquake Speed, 152 If the elevator is allowed to run after a seismic event, this is the speed that will be used. Default is 150 FPM.
Auxiliary Speed, 153 If the group control commands the car to run at economy speed, this is the speed that will be used. The group may command cars to run at normal contract speed during busy traffic or in response to a timer setting, or at reduced economy speed during light traffic or in response to a timer setting. Selected when the SPI2 (Spare 2) input to the TC-
MPI board is active.
Backup Power Speed, 154 If commercial power is lost and the elevator has backup power available, this is the speed that will be used.
4-158 Manual # 42-02-2P25
Motion 4000
F7: Parameters Adjust
Inspection Speed (Normal), 155 Enter the normal Inspection Speed for the car.
Inspection Speed (Reduced), 156 If the car reduces inspection speed upon encountering normal or emergency terminal speed switches, enter that reduced speed here.
Correction Speed, 157 If the car should lose position, this is the speed at which it will proceed to a known point to re-establish position. Default is 75 FPM.
Leveling Speed, 158 Leveling speed is the speed the car uses when initially leveling into the door zone. Default is 4 FPM.
Re-Leveling Speed, 159 Should the car not level properly initially and require re-leveling, this is the speed that will be used. Default is 6 FPM.
Leveling Distance, 160 This is the distance in inches (above and below) floor level at which the car should slow to leveling speed. Initially, set to 4.0 inches. After initial tuning, 2.0 inches is generally sufficient.
Re-Leveling Distance, 161 If the car initially levels into the floor above or below this distance from accurate level, a re-leveling operation will proceed.
Proximity Distance, 162 Determines the distance at which the speed is transitioned to leveling speed under abnormal conditions like an emergency slowdown.
Leveling Dead Zone Distance, 163 This is the distance from floor level position at which the stop command is issued during initial leveling and the car “coasts” to a stop. Start with 0.7 inches.
Standard Start Jerk, 165 Defines the transition from zero speed to full acceleration.
As Start Jerk increases, the profile transitions more quickly from starting to maximum acceleration. Values typically range from 4.0 to 8.0 ft/s
3 resulting in a sharper start.
(1.219 to 2.438 m/s
3
) with higher values
Standard Roll Jerk, 166 Roll Jerk determines how quickly the profile transitions from maximum to zero acceleration and zero to maximum deceleration. As Roll Jerk increases, the profile transitions more quickly. Lower values provide greater comfort but are harder to fit into the shortest one-floor-runs. We recommend that you identify the shortest full height floor and use it when testing parameter values. Typical values range from a minimum of 4.0 ft.
Standard Stop Jerk, 167 Defines the transition from deceleration to Leveling Speed.
As Stop Jerk increases, the profile transitions more quickly from Deceleration to Leveling
Speed.
Standard Acceleration, 168 Determines the maximum acceleration for the profile.
Determines the maximum current delivered by the AC Drive during acceleration. The maximum value is typically 4.0 ft/s
2
(1.219 m/s
2
) and the minimum is usually not less than 2.5 ft/s
2
(0.762 m/s
2
). Values higher than 4.0 ft/s improvements in performance.
2
(1.219 m/s
2
) are possible but do not yield significant
4
4-159
User Interface
Standard Deceleration, 169 Determines the maximum deceleration for this profile.
The maximum value is typically 4.0 ft/s
2
and the minimum is usually not less than 2.0 ft/s
2 with more common values ranging from 2.75 ft/s
2
to 3.75 ft/s
2
(0.838 to 1.143 m/s
2
). The value of Deceleration is usually slightly less than the value of Acceleration (by 0.25 to 0.5).
Manual Start Jerk, 170 Defines the transition from zero speed to full acceleration. As
Start Jerk increases, the profile transitions more quickly from starting to maximum acceleration. Values typically range from 4.0 to 8.0 ft/s
3 ing in a sharper start.
(1.219 to 2.438 m/s
3
) with higher values result-
Manual Roll Jerk, 171 Roll Jerk determines how quickly the profile transitions from maximum to zero acceleration and zero to maximum deceleration. As Roll Jerk increases, the profile transitions more quickly. Typical values range from a minimum of 4.0 ft.
Manual Stop Jerk, 172 Defines the transition from deceleration to stop. As Stop Jerk increases, the profile transitions more quickly.
Manual Acceleration, 173 Determines the maximum acceleration for the profile.
Determines the maximum current delivered by the AC Drive during acceleration. The maximum value is typically 4.0 ft/s
2
(1.219 m/s
2
) and the minimum is usually not less than 2.5 ft/s
2
(0.762 m/s
2
).
Manual Deceleration, 174 Determines the maximum deceleration for this profile.
The maximum value is typically 4.0 ft/s
2
and the minimum is usually not less than 2.0 ft/s
2 with more common values ranging from 2.75 ft/s
2
to 3.75 ft/s
2
(0.838 to 1.143 m/s
2
). The value of Deceleration is usually slightly less than the value of Acceleration (by 0.25 to 0.5).
Danger Start Jerk, 175 The Danger profile is used for emergency slowdown. If, after stopping, the car restarts while remaining on the Danger curve, this setting defines the transition from zero speed to full acceleration. As Start Jerk increases, the profile transitions more quickly from starting to maximum acceleration.
Danger Roll Jerk, 176 Roll Jerk determines how quickly the profile transitions from maximum to zero acceleration and zero to maximum deceleration. As Roll Jerk increases, the profile transitions more quickly.
Danger Stop Jerk, 177 Defines the transition from deceleration to stop. As Stop Jerk increases, the profile transitions more quickly.
Danger Deceleration, 178 Determines the maximum deceleration for this profile.
Alternate Start Jerk, 179 Defines the transition from zero speed to full acceleration.
As Start Jerk increases, the profile transitions more quickly from starting to maximum acceleration. Values typically range from 4.0 to 8.0 ft/s
3 resulting in a sharper start.
(1.219 to 2.438 m/s
3
) with higher values
4-160 Manual # 42-02-2P25
Motion 4000
F7: Parameters Adjust
Alternate Roll Jerk, 180 Roll Jerk determines how quickly the profile transitions from maximum to zero acceleration and zero to maximum deceleration. As Roll Jerk increases, the profile transitions more quickly. Lower values provide greater comfort but are harder to fit into the shortest one-floor-runs. We recommend that you identify the shortest full height floor and use it when testing parameter values. Typical values range from a minimum of 4.0 ft.
Alternate Stop Jerk, 181 Defines the transition from deceleration to Leveling Speed.
As Stop Jerk increases, the profile transitions more quickly from Deceleration to Leveling
Speed.
Alternate Acceleration, 182 Determines the maximum acceleration for the profile.
Determines the maximum current delivered by the AC Drive during acceleration. The maximum value is typically 4.0 ft/s
2
(1.219 m/s
2
) and the minimum is usually not less than 2.5 ft/s
2
(0.762 m/s
2
). Values higher than 4.0 ft/s
2
(1.219 m/s
2
) are possible but do not yield significant improvements in performance.
Alternate Deceleration, 183 Determines the maximum deceleration for this profile.
The maximum value is typically 4.0 ft/s
2
and the minimum is usually not less than 2.0 ft/s
2 with more common values ranging from 2.75 ft/s
2
to 3.75 ft/s
2
(0.838 to 1.143 m/s
2
). The value of Deceleration is usually slightly less than the value of Acceleration (by 0.25 to 0.5).
Drive Type, 184 Check the TORQMAX drive software version at parameter LF.80. If it is 1.71 or greater, select KEB F5-GRD50 (geared machines) or KEB F5-GLS50 (gearless machine). Otherwise, select KEB F5-GRD49 (geared) or KEB F5GLS49 (gearless).
Brake Type, 185 Motion 4000 may be configured with one or two brake modules or a straight brake drop / brake pick brake (Discrete). Select the controller brake configuration.
Emergency Brake, 186 This setting selects or disables the emergency brake option.
Emergency Brake reset button requires constant pressure for 5 to 8 seconds to clear.
• Disabled: Set to Disabled if the job does not use an emergency brake or rope gripper.
• Rope Gripper: Select if job uses a rope gripper.
• Sheave Brake: Select if job uses a sheave brake.
• Machine Brake: Select if second machine brake used as the emergency brake.
Reduced Inspection Speed, 187 This setting directs the controller to automatically reduce inspection speed to Inspection Speed Reduced (156) value when an Emergency Terminal or Normal Terminal Slowdown switch is encountered.
• Off: Inspection speed remains as set throughout the hoistway.
• ETS: Inspection speed is automatically reduced when the car is running on inspection and encounters an Emergency Terminal Switch.
• NTS-1/-2/-3/-4/-5: Inspection speed is automatically reduced when the car is running on inspection and encounters the selected Normal Terminal Slowdown switch.
Unintended Motion, 188 Determines where unintended motion is detected.
• Level Zone: Detected when car moves out of the leveling zone.
• Door Zone: Detected when car moves out of the door zone.
4-161
4
User Interface
Following Error, 189 Following error sets the allowed margin of deviation from commanded speed as a percentage of that speed. An encoder error will be generated if the actual speed differs from the commanded speed by more than specified here. For example, if commanded speed is 250 FPM and Following Error is set to 5% (5% of 250 is 12.5), then the actual speed will be allowed to differ from 250 FPM by +/- 12.5 FPM without generating the error.
Sheave Brake Idle Delay, 190 Appears if Sheave Brake is the selected emergency brake (186). When a car is idle, the sheave brake will drop after the time set here expires. Allows the brake to be exercised. Range is from 0 to 3600 seconds.
Landing System, 191 Select the landing system used on this job.
• Elgo-160: Elgo system with sensors in the sensor head separated by 160mm.
• Elgo-240: Elgo system with sensors in the sensor head separated by 240mm.
• LS-EDGE: Magnet/Vane landing system.
Note
The sensor heads for the Elgo-160 and -240 systems are visibly different. The -160 sensor head is about 13.25 inches (336 mm) long while the -240 sensor head is about 19.00 inches (482 mm) long.
Speed Drop Delay, 192 Parameter appears only when a Magnetek HPV600,
HPV900, or QUATTRO drive is selected in parameter 184, Drive Type. The time in milliseconds during which the drive should continue to exert motor control after the direction command is removed (car has achieved the floor but brake has not yet dropped). Used for drives that do not independently provide a parameter to extend this period of control. Delay should be equal to or greater than the sum of brake drop delay and time required for the brake shoes to seat fully.
Profile Compensation, 193 Selects the method used to implement Profile Advance, parameter 140 (used to advance application of the speed profile to compensate for internal control lag within the elevator drive). Helpful during runs in which the elevator does not achieve stable contract speed (i.e., short runs) and pattern transition command/drive reaction lag may cause a “bump” in the ride.
• Fixed: Compensates for drive control lag using the fixed value entered in parameter 140,
Profile Advance through all stages of control. Recommended for new installations.
Too much compensation can cause an abrupt transition between acceleration and deceleration at peak speed. Using fixed compensation will probably require a little experimentation to achieve good starts and a smooth ride but will provide better results once dialed in.
Required when a Magnetek HPV600, HPV900, or QUATTRO drive is used.
• Dynamic: Compensates for drive control lag during the deceleration stage only using a variable percentage of the value entered in parameter 140, Profile Advance. Recom-
mended to provide backwards compatibility when upgrading Motion 4000
software in existing installations. (Previous versions always used Dynamic compensation; fixed compensation was not an option.)
Normal Brake Pick Voltage, 194 When a CAN controlled brake module is used, this setting determines pick voltage applied to the normal machine brake. See “Calibration (CAN
Only)” on page 5-85 .
4-162 Manual # 42-02-2P25
Motion 4000
F7: Parameters Adjust
Normal Brake Hold Voltage, 195 When a CAN controlled brake module is used, this setting determines hold voltage applied to the normal machine brake. See “Calibration
(CAN Only)” on page 5-85.
Normal Brake Relevel Voltage, 196 When a CAN controlled brake module is used, this setting determines relevel voltage applied to the normal machine brake. See “Calibration
(CAN Only)” on page 5-85.
Normal Brake Lift Rate, 197 When a CAN controlled brake module is used, this setting determines the lift rate of the normal machine brake. 100% = fastest lift rate.
Normal Brake Drop Rate, 198 When a CAN controlled brake module is used, this setting determines the drop rate of the normal machine brake. 100% = fastest drop rate.
Emergency Brake Type, 199 This setting selects the method of control for the emergency brake. (CAN) Module or Discrete. Appears only if parameter 186 has been used to select an emergency brake type.
Emergency Brake Pick Voltage, 200 Only if Module is selected in 199. Determines the pick voltage applied to the emergency machine brake. See “Calibration (CAN Only)” on page 5-85.
Emergency Brake Hold Voltage, 201 Only is Module is selected in 199. Determines the hold voltage applied to the emergency machine brake. See “Calibration (CAN Only)” on page 5-85.
Directional Limit Type, 202 Virtual/Physical
• Virtual: Directional limits remain software based and operate normally based upon the programmed distance above/below the top/bottom terminal landings.
• Physical: The U/DETS terminals on the TC-MPI board are used for connection to mechanical direction limit switches. For these jobs, customer connections for the directional limit switches will be made to appropriately labeled terminals on the panel mount terminal strip in the bottom of the controller cabinet.
Landing System Floor Checksum, 203 This is a read only value. When the hoistway is learned with the LS-EDGE landing system, the learned parameters are stored in the landing system sensor and this checksum is both stored in the sensor and sent to the controller.
If the controller should read a different checksum (i.e., if the sensor head is changed), a new hoistway learn must be performed.
Landing System ETS Overspeed, 204 Used to set the LS-EDGE landing system hardware ETS overspeed threshold as a percentage of contract speed. Magnets on the landing system tape (one lane for UETS and another for DETS) are monitored by the LS-EDGE, detecting the speed at which the car passes. The controller still allows a virtual/physical ETS switch in addition to the magnets.
Inspection Slew Filter, 205 Smooths any harsh transitions in the commanded speed for inspection modes of operation. Reducing this value causes a smoother transition.
Battery Backup Speed, 206 If commercial power is lost and the elevator has battery backup power available, this is the speed that will be used.
4
4-163
User Interface
F8: Software Revision
Displays current software level for each of the controllers processors.
• R009 R.C. 10
VER # T00.09.0003
Note
The “boot loader” IC polls each processor as the controller is powering up, ensuring that each has the right software. The software version for the boot loader itself is displayed in a scrolling message as the controller is powering up.
Status Displays
To access Status Displays:
• Place function switch F8 in the up position (all others down).
• Press N to cycle through available status displays.
The following status displays are available:
• Software Version - Main processor software version number.
• Eligibility Map - Door access for each floor (F = front, R = rear, B = both). Read left to right:
• Floors 1 through 16 in the top row
• Floors 17 through 32 in the bottom row
Please refer to “CAR SERVES FRNT/FLR 1? (simplex)/THIS CAR SERVES FRNT/FLR 1?
(duplex)” on page 4-14 for programming instructions.
• Current Load - The current load in the car as a percentage of full load (analog load weigher required).
4-164 Manual # 42-02-2P25
Motion 4000
F1 & F8: Board Software Versions
F1 & F8: Board Software Versions
When both F1 and F8 switches are up, board software version numbers are visible. This can be helpful when troubleshooting with an MCE technician.
• Press N button for versions:
• MPUA: MPU board software
• CTLA: Control board A processor software
• CTLB: Control board B processor software
• CTLPLD: Control board C processor software
• MPIA: Motion Processor board A processor software
• MPIB: Motion Processor board B processor software
• MPIC: Motion Processor board C processor software
• UIO(0 - n): UIO board software
• CPI(0 - n): Car Panel Interface board software
• CHP: CHP board software
• FCL-(n): Brake field module software
• EDGE-A/B/C: LS-EDGE landing system sensor processor software
4
4-165
User Interface
4-166 Manual # 42-02-2P25
Troubleshooting
In This Section
This section contains troubleshooting information to help you correct problems. If you are reading this on a computer, you can click on blue text to jump to more information about the topic.
• Status and Error Messages: Table includes a description and troubleshooting tips for each message.
Please refer to “Status and Error Messages” on page 5-2 .
• Status Indicators: HC-MPU status LEDs indicate the state of the safety circuit, door locks, and mode of operation.
Please refer to “HC-MPU Main Processor Board” on page 5-53 .
• Diagnostic and External Memory Modes: Useful tools to isolate and diagnose problems.
Please refer to “Diagnostic Mode” on page 4-6
and to F5 diagnostic information 4-65 .
• PC Board Quick References: Circuit board information and photographs. Please refer to
“PC Board Quick References” on page 5-43
.
• Position and Speed Information:
Please refer to “MPI Diagnostic Menu” on page 4-69
.
• Brake Module Information: If the job uses the mBrake module for machine or emergency brake control,
see “Motion Brake Module” on page 5-82
.
• Wiring Prints: MCE job prints are technical drawings specifically generated for each installation. Use these drawings while tracing problems.
5-1
Troubleshooting
Status and Error Messages
In Diagnostic Mode, the top line of the LCD displays elevator status. The message scrolls if it is too long to be displayed all at once. There are status messages for operating modes
(e.g., FIRE SERVICE PHASE 1 - MAIN) and for error conditions (e.g., SAFETY CIRCUIT IS OPEN).
The following table contains some terms that are unique to
MCE or to electronics manufacturing:
• 2 or 2xx Bus: These are 120VAC buses originating in the controller.
• IDC: Insulated Displacement Connectors. These are connectors that allow an insulated wire to be pressed into place where narrow “jaws” cut the insulation to provide positive connection. When an instruction says to “check IDC,” it means to check signal presence at that connector/number, the integrity of the wire, the source connection, and the source signal.
• NYCHA: New York City Housing Authority.
• Data Trap: An electronic “capture” of the present status, off or on (0 or 1) of eight signals.
Used when troubleshooting to see that signals are in the expected state during a particular point of controller operation.
• Jumper: A board-mounted connector with exposed, vertical pins that can be shorted together using a small “jumper” designed to slide on to two pins.
Jumper
Header connector on circuit board
• PMT: Panel Mount Terminal. Gray screw-terminals arranged on a length of DIN rail.
PMTs provide a convenient point of connection for field wiring.
5-2 Manual # 42-02-2P25
Motion 4000
Status and Error Messages
Note
When troubleshooting inputs, use built-in diagnostics to view memory registers so that you can
see the actual state of the input. Please refer to “Troubleshooting Example” on page 4-8
.
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
2 BUS IS LOW
Description: 2 bus (120VAC) monitoring input is low.
Troubleshooting:
1. Check 2 bus fuses.
2FS BUS IS LOW
Description: 2FS bus (120VAC) monitoring input is low.
Troubleshooting:
1. Check 2 bus fuses.
2HA BUS IS LOW
Description: 2HA (120VAC) bus monitoring input is low.
Troubleshooting:
1. Check 2 bus fuses.
2MV BUS IS LOW
Description: 2MV (120VAC) bus monitoring input is low.
Troubleshooting:
1. Check 2 bus fuses.
ABD INPUT FAILURE
Description: The Bottom Down Access (ABD) switch is at 120VAC when the 120VAC 2 bus that provides its input is low.
Troubleshooting:
1. Check for incorrect wiring or short on the HC-CTL-2 board ABD input and associated 2 bus
2. Check the bottom access switch and associated wiring per the job prints.
ABU INPUT FAILURE
Description: The Hoistway Access Bottom Up (ABU) switch is at 120VAC when the 120VAC 2 bus that provides its input is low.
Troubleshooting:
1. Check for incorrect wiring or short on the HC-CTL-2 board ABU input and associated 2 bus.
2. Check the bottom access switch and associated wiring per the job prints.
ACCESS ENABLED
Description: The controller is on Inspection Access mode, activated by either 120VAC at the Access
Enable Switch input (screw terminal INA on the HC-CTL-2 board) or by placing the front or rear hoistway or car door bypass switches in the bypass position.
ATD INPUT FAILURE
Description: The Top Down Access (ATD) switch is at 120VAC when the 120VAC 2 bus that provides its input is low.
Troubleshooting:
1. Check for incorrect wiring or short on the HC-CTL-2 board ATD input and associated 2 bus connection.
2. Check the top access switch and associated wiring per the job prints.
ATTENDANT SERVICE OPERATION
Description: The car is on attendant operation. The attendant service input (ATS) is activated.
Troubleshooting: In Program Mode (F1), check to see if any spare inputs are programmed as ATS, then check to see if that input is activated.
5-3
5
Troubleshooting
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
ATU INPUT FAILURE
Description: The Top Up Access (ATU) switch is at 120VAC when the 120VAC 2 bus that provides its input is low.
Troubleshooting:
1. Check for incorrect wiring or short on the HC-CTL-2 board ATU input and associated 2 bus.
2. Check the top access switch and associated wiring per the job prints.
BATTERY BACKUP POWER SYSTEM FAULT
Description: The battery powered rescue system has reported a fault.
Troubleshooting:
1. Check the display or fault indicators on the battery backup system.
2. Correct the cause of the fault.
3. If in error, review job prints. Check status of relevant inputs and outputs.
BATTERY POWER CAR RECALL ACTIVATED
Description: Commercial power is not available at the elevator and a battery powered rescue device is recalling/moving the car to an appropriate floor for passenger egress. This may also be displayed during a test operation of the battery powered rescue device.
Troubleshooting: If in error:
1. Check status of commercial power to elevator.
2. Check proper operation of the battery powered rescue device.
3. Review job prints. Check status of relevant inputs and outputs.
BOTTOM ACCESS SW. FAILURE
Description: The Up and Down Bottom Access switch inputs are active at the same time.
Troubleshooting: Check the wiring and the switch associated with the ABU and ABD inputs.
BOTTOM FLOOR OR TOP FLOOR DEMAND
Description: The controller is trying to establish car position by sending it to either the top or the bottom.
Usually associated with bottom floor demand. Bottom Floor Demand has four possible causes:
1. A change from Inspection to Automatic operation.
2. Pressing the COMPUTER RESET button.
3. Initial Power-up.
4. If the car is at the top floor and the controller gets an up slowdown signal (USD), the controller will create a Bottom Floor Demand.
Troubleshooting: Bottom Floor Demand should be cleared when all of the following conditions are met:
1. The car is at the bottom and the down slowdown (DSD) input to the controller is OFF (because the switch should be open).
2. The Door Zone (DZ) input to the controller is ON.
3. The Door Lock (DLK) input to the controller is ON.
If the car is at the bottom and the message still flashes, check the Down slowdown switch and associated wiring and the bottom floor door zone landing system vane/magnet and door lock circuit.
Top Floor Demand should be cleared when all of the following conditions are met:
1. Car is at the top and up slowdown (USD) input is OFF (because the switch should be open).
2. The Door Zone (DZ) input to the controller is ON.
3. The Door Lock (DLK) input to the controller is ON.
If the car is at the top and the message still flashes, inspect the Up slowdown switch and associated wiring.
Also inspect the door zone landing system vane/magnet at the top floor and the door lock circuit.
BRAKE MODULE FAULT LIMIT REACHED
Description: The maximum number of consecutive FCL related faults has been reached. See FCL fault descriptions.
Troubleshooting: Requires fault reset on HC-CTL-2 board.
5-4 Manual # 42-02-2P25
Motion 4000
Status and Error Messages
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
BRAKE PICK FAILURE
Description: The car is shut down because the brake pick switch, BPS, input was activated during three consecutive runs, indicating the brake was not fully picked (BPS is high).
Troubleshooting: In Program Mode (F1), check to see if any spare input is programmed as BPS, then check to see if that input is activated. Check the physical mounting and correct wiring of the switch.
BRP INPUT FAILED TO ACTIVATE
Description: The normally closed auxiliary contact for BR contactor failed to close. When idle, this input should be activated.
Troubleshooting:
1. Check BRP screw terminal on TC-MPI board for 120V. When BR contactor is picked, BRP should go low.
BRP INPUT FAILED TO DEACTIVATE
Description: The normally closed auxiliary contact for BR contactor failed to open. When running, this input should be at zero volts.
Troubleshooting:
1. Check BRP screw terminal on TC-MPI board for 120V. When BR contactor is dropped, BRP should go high.
CALIBRATION RUNNING
Description: CALIBRATION RUNNING. Brake module calibration is in process.
CALIBRATION SUCCESS
Description: CALIBRATION SUCCESS. The brake module calibration process completed successfully.
CAPTURE FOR TEST
Description: CTST input has been activated.
Troubleshooting: In Program Mode (F1), check the spare inputs to see if one is programmed as CTST, then ensure that input is NOT activated.
CAR CALL BUS IS DISCONNECTED
Description: Indicates a problem in wiring or fuses. No power to the Car Call circuits.
Troubleshooting: Check the Car Call Bus fuse. Check the wires that go to the Car Call Power inputs in the controller.
CAR DOOR BYPASS SW. FAILURE
Description: Indicates that the car door bypass switch on the HC-CTL-2 board has failed.
Troubleshooting:
1. Cycle the HC-CTL-2 board car door bypass switch a few times to exercise it. Verify that it is fully in the
ON or OFF position.
2. Verify 2 bus and GS connections and wiring.
CAR IN TEST MODE
Description: The TEST input has been activated.
Troubleshooting: Check the PRETEST/NORM/TEST switch position on the HC-CTL-2 Board.
CAR SAFETY DEVICE OPEN
Description: One of the car safety devices has activated, opening the safety circuit (e.g., emergency exit contact, safety clamp switch, car-top emergency stop switch).
Troubleshooting: Refer to wiring prints and check all car safety devices. Verify that the SAFC terminal on the HC-CTL-2 board is powered.
CAR TO FLOOR FUNCTION
Description: The CTF input has been activated.
Troubleshooting: In Program Mode (F1), see if a spare input is programmed as CTF, then check to see if that input is activated.
5
5-5
Troubleshooting
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
CAR TO LOBBY OPERATION
Description: The CTL input has been activated.
Troubleshooting: In Program Mode (F1), see if a spare input is programmed as CTL, then check to see if that input is activated.
CAR TOP INSPECTION
Description: The controller is currently in cartop inspection (120VAC detected at screw terminal INCT on the HC-CTL-2 board).
CAR TOP INSPECTION BUTTON STUCK
Description: The car top inspection button is stuck closed.
CONFIGURATION ERROR-CHANGE SETTINGS BEFORE INSTALLATION
Description: Incorrectly programmed value(s), e.g., a floor selected for the fire floor is not one at which the elevator stops or conflict with Duplex car. Check Duplex programming.
Troubleshooting: In Program Mode (F1), check all of the values associated with stops and special floors.
Save the values.
If this message reoccurs after cycling power to the controller, the memory backup battery on the HC-MPU board may be low. CR2032 battery voltage should about 3Vdc. If you replace the battery, be sure to default the parameters before reprogramming controller parameters. We recommend you replace the MPU battery every four years. Replace the battery with POWER ON.
CTL-A BRAKE MODULE 1 IS OFFLINE
Description: Brake module 1 is not responding.
Troubleshooting:
1. Check the CAN connection to the module.
2. Check power connections to the module.
3. Replace the module.
CTL-A BRAKE MODULE 2 IS OFFLINE
Description: Brake module 2 is not responding.
Troubleshooting:
1. Check the CAN connection to the module.
2. Check power connections to the module.
3. Replace the module.
CTL-A LANDING SYSTEM ACCESS OVERSPEED
Description: When the car is moving faster than 75 FPM, speed bit values will be SPD0=1, SPD1=1. If the car is moving faster than 150 FPM, speed bit values will be SPD0=0, SPD1=1.
Troubleshooting:
1. If these values appear to be in error, verify connections at the HC-CTL and MC-LSI boards. Voltage should be 24VDC for logic high and near 0VDC for logic low.
CTL A LANDING SYSTEM INSPECTION OVERSPEED
Description: When the car is moving faster than 75 FPM, speed bit values will be SPD0=1, SPD1=1. If the car is moving faster than 150 FPM, speed bit values will be SPD0=0, SPD1=1.
Troubleshooting:
1. If these values appear to be in error, verify connections at the HC-CTL and MC-LSI boards. Voltage should be 24VDC for logic high and near 0VDC for logic low.
CTL A SPD0 and SPD1 ARE LOW
Description: Indicates landing system is not installed. If SPD0=0 and SPD1=0 this error will be generated unless the car is on Inspection Bypass.
Troubleshooting:
1. Verify connections at HC-CTL and MC-LSI boards. Verify M-DISC RJ45 cable from LS-EDGE sensor.
2. Voltage should be 24VDC for logic high and near 0VDC for logic low. If the landing system is not installed, the car must be run on Inspection Bypass.
5-6 Manual # 42-02-2P25
Motion 4000
Status and Error Messages
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
CTL-A or B ACTUAL AND REQUESTED DIRECTION MISMATCH
Description: The processor has detected that the commanded run direction does not match the data reported by the positioning system. Power will be removed from brake and motor to bring the car to an immediate halt.
Troubleshooting:
1. Check CAN bus connections from landing positioning sensor to cartop box MC-LSI board.
2. Check CAN bus connections from MC-LSI board to TC-MPI board in controller.
3. Check 24V power to MC-LSI board in cartop box.
4. Check condition and proper installation of encoded tape for positioning system.
5. Check position sensor for excessive dirt or clogging.
CTL-A or B CONTRACT OVERSPEED
Description: The processor has detected a contract overspeed (F7 menu, parameter 145). Power will be removed from brake and motor to bring the car to an immediate halt. If changes have been made to LF.22, you must reset all three microprocessors on the TC-MPI board.
Troubleshooting:
1. Check the integrity of the landing/positioning system encoded tape.
2. Use a hand tach to check the speed at which the overspeed is triggered.
If this is occurring on a job that is just being set up or adjusted or has had this problem sporadically:
3. Check F7 menu Contract Speed setting (parameter 149).
4. Check F7 menu Contract Overspeed setting (parameter 145 should be set to about 108% of Contract
Speed).
5. Check F7 menu Hoist Motor Speed setting (parameter 148). Check correct gear ratio, TORQMAX drive parameter LF.22.
6. Check drive Contract Speed, High Speed, Sheave Diameter, Gear and Roping Ratio, Integral Gain, and
Encoder settings.
CTL-A or B DET SW OVERSPEED
Description: The processor has detected a Down Emergency Terminal overspeed. Power will be removed from brake and motor to bring the car to an immediate halt.
Troubleshooting:
1. Check the integrity of the landing/positioning system.
2. If the job has a physical DET switch, check the switch and connections.
If this is occurring on a job that is just being set up or adjusted or has had this problem sporadically:
3. Check F7 menu U/DET Option setting (parameter 69).
4. Check F7 menu DET Speed, Distance, and Delta Speed settings (F7 parameters 104 through 107 respectively).
5. Check F7 menu settings for the terminal slowdown switch immediately preceding the DET switch.
CTL A or B DET SW POSITION FAULT
Description: The DET switch was not detected at the expected location. Power will be removed from brake and motor to bring the car to an immediate halt.
Troubleshooting:
1. Check the integrity of the landing/positioning system encoded tape.
2. If a physical DET switch is used on this job, check switch wiring, integrity, and position.
If this is occurring on a job that is just being set up or adjusted or has had this problem sporadically:
3. Check F7 menu U/DET Option setting (parameter 69).
4. Check F7 menu DET Distance and DET Delta Distance (parameters 105, 107 respectively).
5
5-7
Troubleshooting
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
CTL-A or B DNT SW HIGH OVERSPEED
Description: The processor has detected a Down Normal Terminal Switch High overspeed (exceeding switch Speed setting plus Delta High Speed setting). Power will be removed from brake and motor to bring the car to an immediate halt. The car will then move at reduced speed to the next landing in the direction of travel. If the fault clears, the car will resume normal service. If not, the car will open its doors and remove itself from service.
Troubleshooting:
1. Check the integrity of the landing/positioning system encoded tape.
2. If the job has a physical DNT switch, check the switch and connections.
3. Check appropriate F5 menu overspeed parameters (17 - 40), to determine what car speed was at that switch for the last normal run and at the time of the overspeed.
4. Check F7 menu DNTx Speed and Delta High Speed settings. Otherwise, move DNTx closer to terminal landing.
CTL-A or B DNT SW LOW OVERSPEED
Description: The processor has detected a Down Normal Terminal Switch Low overspeed (exceeding switch Speed setting plus Delta Low speed setting). The car will perform an emergency slowdown, then move at reduced speed to the next landing in the direction of travel. If the fault clears, the car will resume normal service. If not, the car will open its doors and remove itself from service.
Troubleshooting:
1. Check the integrity of the landing/positioning system encoded tape.
2. If the job has a physical DNT switch, check the switch and connections.
3. Check appropriate F5 menu overspeed parameters (17 - 40), to determine what car speed was at that switch for the last normal run and at the time of the overspeed.
4. Check F7 menu DNTx Speed and Delta Low Speed settings. Otherwise, move DNTx closer to terminal landing.
CTL A or B DNT SW POSITION ERROR
Description: The DNT switch was not detected at the expected location. The car will perform an emergency slowdown and then move at reduced speed to the next landing in the direction of travel. If the fault clears, the car will resume normal service. If not, the car will open its doors and remove itself from service.
Troubleshooting:
1. Check the integrity of the landing/positioning system encoded tape.
2. If a physical DNT switch is used on this job, check switch wiring, integrity, and position.
If this is occurring on a job that is just being set up or adjusted or has had this problem sporadically:
3. Check F7 menu U/DNT Option setting.
4. Check F7 menu DNT Distance and DNT Delta Distance.
CTL A or B DOWN NORMAL LIMIT OPEN
Description: The indicated processor has detected that the down directional limit switch is open. The car will run no further in the down direction.
Troubleshooting:
1. Review car adjustment and landing settings.
2. Adjust as required to prevent the car from overshooting the terminal and activating the directional limit.
3. If switch is physical, check voltage at terminal SPI3 on TC-MPI board and limit switch connections.
4. If switch is virtual, check F7 programming.
CTL A or B DRIVE FAULT
Description: The drive has faulted.
Troubleshooting:
1. Check the drive display to identify the fault. Proceed as described in the drive manual.
2. After the problem has been corrected, reset the fault on the drive.
5-8 Manual # 42-02-2P25
Motion 4000
Status and Error Messages
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
CTL A or B DRIVE NOT READY
Description: The drive has not reported ready status, DRDY, to the controller.
Troubleshooting:
1. Check the drive display to identify any fault. Proceed as described in the drive manual.
2. Check all connections from the controller to the drive and the drive to the motor.
3. After the problem has been corrected, reset the fault on the drive.
CTL A or B DRIVE ON FAULT
Description: The drive on input was lost while the car was in motion. This fault is reported immediately as opposed to the normal pre-run check Drive On fault which is rechecked after 15 seconds.
Troubleshooting:
1. The drive enable status is not identical on all the processors. Check the event log for discrepancies between the faults logged by each MPI processor.
2. Verify physical cable (DRE signal) connection between controller and drive.
CTL A or B EEPROM FAULT
Description: A device error has been detected during a cyclic redundancy check (code=1) or while reading from or writing to the device (code=2).
Troubleshooting:
1. Reset the microprocessor.
2. Check for recently installed equipment that might be generating electrical noise.
3. If the error occurred while updating firmware, re-attempt the update procedure.
CTL A or B ETS SHUTDOWN FAULT
Description: The named processor has detected that there is a difference in emergency terminal switch data (position or open/closed status) between itself and the other processor. If moving, the car will be stopped at the next landing, the doors opened for passenger exit, and the car taken out of service. If in a door zone, the car will remain at the landing, open doors for passenger exit, and be taken out of service.
Troubleshooting:
1. Check that emergency terminal switch F7 menu designations (virtual, physical, unused) and positions are correct.
2. If switches are physical, check their actual positions and proper operation.
3. Test elevator for proper operation.
CTL A or B EXCESSIVE FAULTS SHUTDOWN
Description: The named processor has detected faults beyond an established limit in a circumscribed period of time.
Troubleshooting:
1. Check the connections to and from the TC-MPI board.
2. Reset the microprocessor.
3. Test elevator for proper operation.
CTL A or B INCORRECT LANDING SYSTEM CHANNEL DETECTED
Description: The named processor has detected that its associated CAN connection from the landing system is not reporting the correct channel identification. Usually, this means that the CAN 1 and CAN 2 connections from the hoistway position sensor to the TC-MPI board have been “swapped” at the TC-MPI board connector.
Troubleshooting:
1. Exchange the CAN 1 and CAN 2 connections on the TC-MPI board J17 connector.
CTL A or B INSPECTION OVERSPEED
Description: The car has exceeded the Parameter 146 speed setting (F7 menu).
Troubleshooting:
1. Check physical motor related settings on drive.
2. Verify inspection speed through the LCD screen (F3 Controller Utilities menu).
5
5-9
Troubleshooting
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
CTL A or B LANDING SYSTEM COMM LOSS
Description: The HC-CTL2 board is not communicating with the landing system properly (A or B channel lost). Before beginning troubleshooting, check all related CAN connections and connectors carefully.
Troubleshooting:
1. On the controller HC-MPU board, place F3 in the UP position. Press “N” to access the system menu.
Press “N” to advance to the Controller System Menu. Press “S” to select. Press “N” until ELGO A and
ELGO B is displayed.If a channel has failed, the position information for that channel will be missing.
ELGO A uses CAN 2, along with the cartop HC-UIO, MC-CPI, and ICE-COP-2 boards. For example:
Connections Through Traveler
1. Check that the CAN connections at J17 on the TC-MPI board are clean and tight.
2. On the cartop, temporarily disconnect the MACHINE ROOM / CANL2 and CANH2 wires from the MC-LSI board. Measure the resistance between them. (All resistance measurements must be performed with power off.) It should read about 120-ohms. Repeat for the CANL1 and CANH1 wires. They should also read about 120-ohms.
3. With power off and all CAN connections to the cartop terminated, resistance should be close to 60ohms.
If a measured resistance is other than shown, you may have a damaged, broken, or shorted wire in the traveler. Resolve this issue before proceeding with additional troubleshooting.
CHANNEL A
1. If the lost channel is the A (CAN 2) channel, verify cartop mounted UIO board baud rate selection is
correct, 5-59. Next, unplug all HC-CPI (control panel interface) and HC-UIO (universal I/O) board CAN
connections from the MC-LSI (landing system interface board) on the cartop (CAN 2 is a shared bus).Recheck the display to see if both channels are now back on line.
2. If the ELGO channels are now OK, reconnect the UIO boards one at a time. If the channel is lost, check the CAN terminations on the UIO board. If the board is terminated, open the termination by moving the jumper so the header pins are not shorted. Repeat for additional UIO boards, checking ELGO information as you go.
3. Check the car panel interface boards to see that only the last board in the string is terminated (CAN).
Reconnect the CPI boards. Check ELGO information. If the A channel is lost again as you reconnect boards, contact MCE support for help in isolating the bad board or termination.
4. If, after disconnecting the CPI and UIO boards, the A channel remained off line, temporarily connect
CAN 1 connections to CAN 2 on the TC-MPI board. Place the processor F3 switch down and check the error code on the display:
• MPI-A INCORRECT LANDING SYSTEM CONNECTED - replace the ELGO reader head
• MPI-A LANDING SYSTEM COMM LOSS - continue numbered steps.
5. Temporarily connect CAN 2 connections to CAN 1 on the TC-MPI board. If the message changes to MPI-
A INCORRECT LANDING SYSTEM CONNECTED, replace the ELGO reader head. If the message remains
MPI-A LANDING SYSTEM COMM LOSS, replace the TC-MPI board.
CHANNEL B
1. If the lost channel is the B (CAN 1) channel, temporarily connect CAN 2 to CAN 1 on the TC-MPI board.
2. If the display changes to MPI-B INCORRECT LANDING SYSTEM CONNECTED, replace the TC-MPI board.
3. If the message remains MPI-B LANDING SYSTEM COMM LOSS, replace the ELGO reader head.
5-10 Manual # 42-02-2P25
Motion 4000
Status and Error Messages
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
CTL A or B LANDING SYSTEM ETS FAULT
Description: The landing system ETS thresholds were not learned with the current controller and landing system configuration.This fault can occur if the TC-MPI board or landing system is replaced.
Troubleshooting:
1. Relearn floor heights.
CTL A or B LANDING SYSTEM ETS MISMATCH
Description: The landing system ETS thresholds were not learned with the current controller and landing system configuration.This fault can occur if the TC-MPI board or landing system is replaced.
Troubleshooting:
1. Relearn floor heights.
CTL A or B LANDING SYSTEM FLOOR MISMATCH (FLOOR LEARN REQUIRED)
Description: The landing system floor heights were not learned with the current controller and landing system configuration.This fault can occur if the TC-MPI board or landing system is replaced.
Troubleshooting:
1. Relearn floor heights.
CTL A or B LEVELING OVERSPEED
Description: CTL A or B on the HC-CTL2 board is reporting an overspeed during leveling.
Troubleshooting:
1. Use a hand-held tach to determine car speed during leveling.
2. Check that the F7, Leveling Overspeed setting is correctly set.
CTL A or B RELATIVE POSITION HIGH
Description: A or B channel from ELGO landing sensor (as specified in message) not being received.
Troubleshooting:
1. Check connections between sensor and cartop interface.
2. Check F3 screen ELGO A/B position and verify that both increment when the car moves up or decrement when the car moves down on inspection. Verify that ELGO A is larger than ELGO B by 160 for the
ELGO 160 system or by 240 for the ELGO 240 system.
CTL A or B RELATIVE POSITION LOW
Description: A or B channel from ELGO landing sensor (as specified in message) not being received.
Troubleshooting:
1. Check connections between sensor and cartop interface.
2. Check F3 screen ELGO A/B position and verify that both increment when the car moves up or decrement when the car moves down on inspection. Verify that ELGO A is larger than ELGO B by 160 for the
ELGO 160 system or by 240 for the ELGO 240 system.
CTL A or B UET SW OVERSPEED
Description: The processor has detected an Up Emergency Terminal overspeed. Power will be removed from brake and motor to bring the car to an immediate halt.
Troubleshooting:
1. Check the integrity of the landing/positioning system encoded tape.
2. If the job has a physical UET switch, check the switch and connections.
If this is occurring on a job that is just being set up or adjusted or has had this problem sporadically:
3. Check F7 menu U/DET Option setting (parameter 65).
4. Check F7 menu UET Speed, Distance, and Delta Speed settings.
5
5-11
Troubleshooting
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
CTL A or B UET SW POSITION FAULT
Description: The UET switch was not detected at the expected location. Power will be removed from brake and motor to bring the car to an immediate halt.
Troubleshooting:
1. Check the integrity of the landing/positioning system encoded tape.
2. If a physical UET switch is used on this job, check switch wiring, integrity, and position.
If this is occurring on a job that is just being set up or adjusted or has had this problem sporadically:
3. Check F7 menu U/DET Option setting (parameter 69). Check F7 menu UET Distance and UET Delta Distance.
CTL-A or B UNT SW HIGH OVERSPEED
Description: The processor has detected an Up Normal Terminal Switch High overspeed (exceeding switch
Speed setting plus Delta High speed setting). Power will be removed from brake and motor to bring the car to an immediate halt. The car will then move at reduced speed to the next landing in the direction of travel.
If the fault clears, the car will resume normal service. If not, the car will open its doors and remove itself from service.
Troubleshooting:
1. Check the integrity of the landing/positioning system encoded tape.
2. If the job has a physical UNT switch, check the switch and connections.
3. Check appropriate F5 menu overspeed parameters (17 - 40), to determine what car speed was at that switch for the last normal run and at the time of the overspeed.
4. Check F7 menu UNTx Speed and Delta High Speed settings. Otherwise, move UNTx closer to the terminal landing.
CTL-A or B UNT SW LOW OVERSPEED
Description: The processor has detected an Up Normal Terminal Switch Low overspeed (exceeding switch speed setting plus Delta Low speed setting). The car will perform an emergency slowdown, then move at reduced speed to the next landing in the direction of travel. If the fault clears, the car will resume normal service. If not, the car will open its doors and remove itself from service.
Troubleshooting:
1. Check the integrity of the landing/positioning system encoded tape.
2. If the job has a physical UNT switch, check the switch and connections.
3. Check appropriate F5 menu overspeed parameters (17 - 40), to determine what car speed was at that switch for the last normal run and at the time of the overspeed.
4. Check F7 menu UNTx Speed and Delta Low Speed settings. Otherwise, move UNTx closer to the terminal landing.
CTL A or B UNT SW POSITION ERROR
Description: The UNT switch was not detected at the expected location. The car will perform an emergency slowdown and then move at reduced speed to the next landing in the direction of travel. If the fault clears, the car will resume normal service. If not, the car will open its doors and remove itself from service.
Troubleshooting:
1. Check the integrity of the landing/positioning system encoded tape.
2. If a physical UNT switch is used on this job, check switch wiring, integrity, and position.
If this is occurring on a job that is just being set up or adjusted or has had this problem sporadically:
3. Check F7 menu U/DNT Option setting.
4. Check F7 menu DNT Distance and DNT Delta Distance.
5-12 Manual # 42-02-2P25
Motion 4000
Status and Error Messages
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
CTL A or B UP NORMAL LIMIT OPEN
Description: The indicated processor has detected that the up directional limit switch is open. The car will run no further in the up direction.
Troubleshooting:
1. Review car adjustment and landing settings.
2. Adjust as required to prevent the car from overshooting the terminal and activating the directional limit.
3. If switch is physical, check voltage at terminal SPI4 on TC-MPI board and limit switch connections.
4. If switch is virtual, check F7 programming.
CTL-B BRAKE MODULE 3 IS OFFLINE
Description: The identified brake module is not responding.
Troubleshooting:
1. Check the CAN connection to the module.
2. Check power connections to the module.
3. Replace the module.
CTL-B BRAKE MODULE 4 IS OFFLINE
Description: The identified brake module is not responding.
Troubleshooting:
1. Check the CAN connection to the module.
2. Check power connections to the module.
3. Replace the module.
CYCLE TEST
Description: A cycle test (exercise operation) of the brake and motor contactors is conducted before the car is allowed to move from a landing. This message will be momentarily displayed while the cycle test completes.
Troubleshooting:
Informational only.
CYCLE TEST FAILURE
Description: A cycle test (exercise operation) of the brake and motor contactors is conducted before the car is allowed to move from a landing. This message will be displayed if the cycle test fails.
Troubleshooting:
Check brake and motor contactors (refer to job prints for guidance).
DCAB INPUT FAILURE
Description: The Bottom Access Door Contact (DCAB) input monitors the bottom door closed contacts.
DCAB should be 120VAC during bottom access operation when the Bottom Access switch is toggled to the up or down position.
Troubleshooting:
1. Verify 120VAC on the 2 bus.
2. Check that all hoistway doors are closed except for the bottom access hoistway door.
3. Check for 120VAC on the DCAB terminal.
5
5-13
Troubleshooting
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
DCLCR INPUT FAILURE
Description: The Rear Door Close Limit Contact (DCLCR) input monitors the rear door closed contacts.
DCLCR should be 120VAC during bottom rear access operation when the Bottom Access switch is toggled to the up or down position. If your door operator connects to a UIO board on the car top (rather than up the traveler to the controller), check that the “spare” inputs used for door operation are correctly pro-
grammed and that Serial Cartop Door Control ( 4-16 ) is set properly. Also verify communication to UIO (if
you have serial cartop door control) by placing F1 and F8 switches UP to view communication with boards.
Troubleshooting:
1. Verify 120VAC on the 2 bus.
2. Check that all hoistway doors are closed except for the bottom rear access hoistway door.
3. Check for 120VAC on the DCLCR terminal.
DL INPUT FAILURE
Description: The Door Lock (DL) input has detected a failure of the Hoistway Door Bypass (HDBA) or Bottom Access Bypass (BABA) outputs, Gate Switch (GS), Door Position Monitor (DPM), or Door Lock Access.
Troubleshooting:
1. Check voltage on HC-CTL-2 board terminal DLAB. DPM should activate two inches before DLAB.
2. If DL is active, GS must also be active.
DLR INPUT FAILURE
Description: The Rear Door Lock (DLR) input has detected a failure of the Rear Hoistway Door Bypass
(HDBBR) or Rear Bottom Access Bypass (BABBR) outputs, Rear Gate Switch (GSR), Rear Door Position
Monitor (DPMR), or Rear Door Lock Access Bypass (DLABR) inputs.
Troubleshooting:
1. Check voltage on HC-CTL-2 board terminal DLABR. DPMR should activate two inches before DLABR.
2. If DLR is active, GSR must also be active.
DOL INPUT FAILURE
Description: The Door Open Limit (DOL) input is not in the correct state for the position of the door as indicated by the Door Position Monitor (DPM) and Gate Switch (GS) inputs. If your door operator connects to a UIO board on the car top (rather than up the traveler to the controller), check that the “spare” inputs used for door operation are correctly programmed and that Serial Cartop Door Control (
4-16
) is set properly. Also verify communication to UIO (if you have serial cartop door control) by placing F1 and F8 switches UP to view communication with boards.
Troubleshooting:
1. If DPM is high, DOL must also be high. Check wiring to HC-CTL-2 board terminal DOL.
2. If the GS input is high, DOL must also be high. Check wiring to terminal DOL.
DOLR INPUT FAILURE
Description: The Rear Door Open Limit (DOLR) input is not in the correct state for the position of the door as indicated by the Rear Door Position Monitor (DPMR) and Rear Gate Switch (GSR) inputs. If your door operator connects to a UIO board on the car top (rather than up the traveler to the controller), check that the “spare” inputs used for door operation are correctly programmed and that Serial Cartop Door Control
(
4-16
) is set properly. Also verify communication to UIO (if you have serial cartop door control) by placing
F1 and F8 switches UP to view communication with boards.
Troubleshooting:
1. If DPMR is high, DOLR must also be high. Check wiring to terminal DOLR on the HC-CTL-2 board.
2. If the GSR input is high, DOLR must also be high. Check wiring to terminal DOLR.
5-14 Manual # 42-02-2P25
Motion 4000
Status and Error Messages
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
DOOR CLOSE PROTECTION TIMER ELAPSED
Description: Failure to lock the doors detected. This condition exists when the doors have closed (DCLC =
1 or DCL = 0/DPM=1) and demand exists for the car to move (DCP=1), but the doors have not locked (DLK
= 0) within 60 seconds.
Troubleshooting: If the Retiring Cam option is set, verify the Retiring Cam relay is activated (DCP=1,
DCL=0/DPM=1 or DCLC=1) and the doors lock (DLK=1). If no Retiring Cam is used, verify door lock contacts are closed to provide power to the door lock input (DLK=1). When a predetermined number of sequential failures is detected (default is four), the car will shut down. The failure will be reset once the doors are locked (DLK=1), the car is placed on Inspection, or the Computer Reset Button is pressed.
DOOR OPEN PROTECTION TIMER ELAPSED
Description: Indicates that DOF (Door Open Function) or DOFR (Door Open Function Rear) have been active for more than 60 seconds and have been cleared.
Troubleshooting: Check for proper door operation and correct any problems.
DOOR ZONE SENSOR FAILURE - OFF POSITION
Description: Indicates that the car completed a run but did not detect a door zone.
Troubleshooting: Reset by pressing the Fault Reset button or by toggling MACHINE ROOM INSPECTION
INSP/NORM switch. Run the car to the same floor and verify that DZ=1 or DZR=1.
1. Check voltage at door zone input to CTL board and at DZFO output from MPI board as shown in your job prints. Make sure wiring between boards is correct.
DOOR ZONE SENSOR FAILURE - ON POSITION
Description: One of the DZ inputs (front or rear) did not transition to the low state during the last run.
Probable cause may be:
1. A faulty door zone sensor or associated circuitry (within the landing system assembly).
2. Faulty wiring from the landing system to the controller.
3. Faulty computer input circuit (HC-CTL-2 Control board).
Troubleshooting: Check door zone sensor operation and wiring. (Place car on inspection, move car away from the floor, noting the transitions in the door zone signal(s) coming from the landing system.)
Verify that the computer diagnostic display of DZ (or DZ rear) matches the state of the sensor signals at the HC-CTL-2 Control board.
If these zones are virtual, check programming (F7, Parameters Adjust).
1. Check voltage at door zone input to CTL board and at DZFO output from MPI board as shown in your job prints. Make sure wiring between boards is correct.
DOWN NORMAL LIMIT OPEN
Description: The indicated processor has detected that the down directional limit switch is open. The car will run no further in the down direction.
Troubleshooting:
1. Review car adjustment and landing settings.
2. Adjust as required to prevent the car from overshooting the terminal and activating the directional limit.
3. If switch is physical, check voltage at terminal SPI3 on TC-MPI board and limit switch connections.
4. If switch is virtual, check F7 programming.
DPM REDUNDANCY FAULT
Description: Front door input, relay, or associated circuitry failure detected. Valid when SAF is on. DLK and DPM must always be in the same state. If your door operator connects to a UIO board on the car top
(rather than up the traveler to the controller), check that the “spare” inputs used for door operation are correctly programmed and that Serial Cartop Door Control (
4-16 ) is set properly. Also verify communica-
tion to UIO (if you have serial cartop door control) by placing F1 and F8 switches UP to view communication with boards.
Troubleshooting:
1. Check that DPM makes (120VAC) 1 to 2 inches prior to door lock.
2. If so, check associated circuitry.
5-15
5
Troubleshooting
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
DPMR REDUNDANCY FAULT
Description: Rear door input, relay, or associated circuitry failure detected. Valid when SAF is on. DLK and
DPMR must always be in the same state. If your door operator connects to a UIO board on the car top
(rather than up the traveler to the controller), check that the “spare” inputs used for door operation are correctly programmed and that Serial Cartop Door Control (
4-16 ) is set properly. Also verify communica-
tion to UIO (if you have serial cartop door control) by placing F1 and F8 switches UP to view communication with boards.
Troubleshooting:
1. Check that DPMR makes (120VAC) 1 to 2 inches prior to door lock.
2. If so, check associated circuitry.
DRIVE FAULT
Description: This fault indicates that the controller has detected a DFLT input. The car will perform an emergency stop with the motor contactor and brake contactor immediately dropped.
Troubleshooting:
1. Examine the drive for faults.
DRIVE RX COMM FAILURE
Description: Serial data from drive to TC-MPI board connector J27 has failed.
Troubleshooting:
1. Check connection and cable integrity from TC-MPI board J27 to drive.
2. Reset C processor on TC-MPI board.
3. Use a scope to check if data is in fact being transmitted from the drive.
DRIVE TX COMM FAILURE
Description: Serial data from TC-MPI board connector J27 to drive has failed.
Troubleshooting:
1. Check connection and cable integrity from TC-MPI board J27 to drive.
2. Reset C processor on TC-MPI board.
3. Use a scope to check if data is in fact being transmitted from the board.
EARTHQUAKE REDUCED SPEED OPERATION
Description: The EQI and/or CWI input is/are active. The car is on earthquake operation moving at reduced speed.
Troubleshooting: If there has been no seismic activity, check the status of the EQI and CWI inputs. Check the counterweight derailment detection sensor. Check the seismic activity sensor. Press the earthquake reset button to clear.
EARTHQUAKE OPERATION
Description: The EQI and/or CWI input is/are active. The car is on earthquake operation.
Troubleshooting: If there has been no seismic activity, check the status of the EQI and CWI inputs. Check the counterweight derailment detection sensor. Check the seismic activity sensor.
ELEVATOR SHUTDOWN SWITCH ACTIVE
Description: The ESS input has been activated.
Troubleshooting: In Program Mode (F1), see if a spare input is programmed as ESS, then check to see if that input is activated.
EMERGENCY BRAKE ACTIVATED
Description: The emergency brake has applied (rope gripper/sheave brake/machine emergency brake).
Troubleshooting:
Informational only.
5-16 Manual # 42-02-2P25
Motion 4000
Status and Error Messages
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
EMERGENCY MEDICAL SERVICE
Description: The EMSH or EMSC input has been activated.
Troubleshooting: Ensure that the MASSACHUSETTS EMS SERVICE option is set correctly. If not required, set to NO and ensure that the EMSH and EMSC inputs are not programmed as spare inputs. If EMS is required, set this option to the floor the car should return to when the EMSH input is activated.
EMERGENCY POWER OPERATION
Description: The car is on Emergency Power operation (EPI is low).
Troubleshooting: Check that the Emergency Power operation option is set correctly. If emergency power is not required, set to NO and ensure that the EPI input is not programmed. If it is required, set this option to the floor the car should return to on Emergency Power and program the EPI input.
ENTER SECURITY CODE
Description: MCE Security has been initiated.
Troubleshooting: Enter floor passcode on the C.O.P. within 10 seconds. Refer to section 4 for instructions on how to program security passcodes.
EXTERNAL LATCHING FAULT INPUT
Description: The External Latching Fault, ELF, Input is low. This active low input is normally used to detect slipping/damaged suspension means (ropes) on traction installations.
Troubleshooting: If in error, check to see that no input is programmed for this function.
FAULT BYPASS IS ACTIVE (AUTOMATIC)
Description: The Automatic operation fault bypass function is set.
Troubleshooting: The F3 Automatic operation fault bypass is on.
FAULT BYPASS IS ACTIVE (INSPECTION)
Description: The Inspection operation fault bypass function is set.
Troubleshooting: The F3 Inspection operation fault bypass is on.
FCL ERROR 3
Description: CALIBRATION ERROR HIGH CURRENT. Measured current during calibration exceeded 20A.
Troubleshooting:
1. Verify brake is properly connected.
2. Verify transformer, if any, correctly connected.
FCL ERROR 4
Description: CALIBRATION ERROR LOW VOLTAGE. Voltage during calibration did not exceed 20VDC.
Troubleshooting:
1. Verify wiring is correct.
2. Verify BR contactor is picking.
FCL ERROR 5
Description: CALIBRATION ERROR CAN TIMEOUT. CAN communication lost for more than 4 seconds during calibration.
Troubleshooting:
1. Verify module is powered.
2. Verify CAN connections are made; swap cables to verify.
3. Repeat calibration.
FCL ERROR 6
Description: CALIBRATION ERROR USER ABORT. The calibration was cancelled by the MPU.
5
5-17
Troubleshooting
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
FCL ERROR 7
Description: CALIBRATION ERROR NO PRESTART. CAN messages out of sequence.
Troubleshooting:
1. Verify CAN connections.
2. Repeat calibration.
FCL ERROR 8
Description: CALIBRATION ERROR LOW CURRENT. Current did not exceed 0.1A during calibration.
Troubleshooting:
1. Verify module is powered.
2. Verify brake coil is connected.
3. Verify BR contactor is picking during calibration.
FCL 1 - 4 - AUX IGBT STUCK CLOSED
Description: The addressed brake module auxiliary IGBT is stuck in the closed position. This fault is triggered if the voltage across the Aux IGBT is insufficient to activate the monitoring circuit during dissipate mode. The car will stop at the next destination. Three consecutive occurrence faults reset automatically after 8 seconds. If the module consecutively faults again, fault “Brake Module Fault Limit Reached” is issued and must be reset on the HC-CTL-2 board.
Troubleshooting:
1. Slow the brake drop rate slightly using module potentiometer R70 (discrete control) or F7 parameter
198 (CAN control). (The brake may be dropping too rapidly for the voltage sensing to work properly.)
2. Contact MCE to verify the resistor/capacitor values of the external dissipate circuit. Too much capacitance on a small brake may cause this fault.
FCL 1 - 4 - AUX IGBT STUCK OPEN
Description: The addressed brake module auxiliary IGBT is stuck in the open position. This fault is triggered if the brake is in pick, hold, or relevel mode and the monitoring circuit returns a high signal for
100mS or more. The car will stop at the next landing. The first and second consecutive occurrence faults reset automatically after 8 seconds. If the module consecutively faults again, fault “Brake Module Fault
Limit Reached” is issued and must be reset on the HC-CTL-2 board.
Troubleshooting: Replace the brake module.
FCL 1 - 4 - BYPASS BUTTON STUCK CLOSED
Description: The addressed brake module is in manual release mode and the bypass button/switch appears to be stuck in the closed position.
Troubleshooting: Please see “SW1, Manual Bypass” on page 5-83 to see if manual release mode is
enabled. Check the manual brake release switch connections and operation. If the problem persists, replace the brake module.
FCL 1 - 4 - CAN DISCONNECTED
Description: The addressed brake module CAN connection appears to be disconnected.
Troubleshooting:
1. Check the CAN connection and the CAN cable. Temporarily swap out the cable to eliminate the possibility that the cable is faulty.
2. Check that module CAN termination jumper JP1 is open.
3. Replace the brake module.
FCL 1 - 4 - DISCRETE INPUT WHILE IN CAN MODE
Description: The addressed brake module is receiving a discrete command input while in CAN mode.
Troubleshooting:
1. Check that F7, parameter 185 brake configuration is properly set.
2. Check that no discrete control voltages have been incorrectly applied. Please refer to “Configuration” on page 5-82
.
5-18 Manual # 42-02-2P25
Motion 4000
Status and Error Messages
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
FCL 1 - 4 IS ON MANUAL MODE
Description: The addressed brake module has been placed in manual mode (will cause Main IGBT stuck open fault to be indicated until the brake contactor is picked to allow power to the brake module). In this mode, a manual brake release switch connected between BRBP1 and BRBP3 will energize the brake coil connected between BRBP2 and BRBP4 and immediately lift the brake regardless of the status of the elevator controller.
Troubleshooting:
Informational only.
FCL 1 - 4 LOAD EXTREME UNDER CURRENT
Description: The addressed brake module has detected that delivered current is less than 40% of the learned operating current. The car will stop at the next landing. First and second consecutive occurrence faults reset automatically after 8 seconds. If the module consecutively faults again, fault “Brake Module
Fault Limit Reached” is issued and must be reset on the HC-CTL-2 board.
Troubleshooting: Check the brake for proper operation according to manufacturer specifications.
FCL 1 - 4 LOAD EXTREME UNDER VOLTAGE
Description: The addressed brake module has detected delivered voltage is less than 40% of the learned operating voltage. The car will stop at the next landing. First and second consecutive occurrence faults reset automatically after 8 seconds. If the module consecutively faults again, fault “Brake Module Fault
Limit Reached” is issued and must be reset on the HC-CTL-2 board.
Troubleshooting: Check the brake for proper operation according to manufacturer specifications.
FCL 1 - 4 - LOAD OVER CURRENT
Description: The addressed brake module has detected excessive current conditions (>20 A during the first 5 seconds of operation or >15 A after the first 5 seconds of operation). The module is rated at 15 A continuous operation and, after the first five seconds of operation current is automatically restricted to this level. The car will stop at the next landing. Three consecutive occurrence faults reset automatically after 8 seconds. If the module consecutively faults again, fault “Brake Module Fault Limit Reached” is issued and must be reset on the HC-CTL-2 board.
Troubleshooting:
1. Check for a shorted brake control wire.
2. Check that the brake does not require more current than 15A. If so, a second module may be required in tandem with the first to handle current requirements.
FCL 1 - 4 - LOAD OVER VOLTAGE
Description: The addressed brake module has detected excessive voltage conditions (>310 VDC for 5 seconds or more). Voltage will be automatically limited to 310 VDC when this fault is issued. The car will stop at the next landing. Three consecutive occurrence faults reset automatically after 8 seconds. If the module consecutively faults again, fault “Brake Module Fault Limit Reached” is issued and must be reset on the HC-CTL-2 board.
Troubleshooting:
1. Check that the brake is operating properly.
2. Check that the brake springs are correctly torqued.
FCL 1 - 4 - LOAD UNDER VOLTAGE
Description: The addressed brake module has detected that delivered voltage is less than 80% of the learned operating voltage. The car will stop at the next destination. Three consecutive occurrence faults reset automatically after 8 seconds. If the module consecutively faults again, fault “Brake Module Fault
Limit Reached” is issued and must be reset on the HC-CTL-2 board.
Troubleshooting: Check the brake for proper operation according to manufacturer specifications.
5
5-19
Troubleshooting
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
FCL 1 - 4 - MAIN IGBT STUCK CLOSED
Description: If the brake is not in pick, hold, relevel, or dissipate mode and there is more than 40 volts or
200 milliamps across the brake coil for 200 mS or more, the IGBT stuck closed fault will occur. In CAN mode, this fault resets automatically after 8 seconds.
Troubleshooting: Check that manual brake pick is not enabled. Please refer to “SW1, Manual Bypass” on page 5-83 .
FCL 1 - 4 - MAIN IGBT STUCK OPEN
Description: If the brake is in pick, hold, or relevel mode and there is less than 20 volts or 100mA across the coil for 200 mS or more, the IGBT stuck open fault will occur. The car will stop at the next landing. The first and second consecutive occurrence faults reset automatically after 8 seconds. If the module consecutively faults again, fault “Brake Module Fault Limit Reached” is issued and must be reset on the HC-CTL-2 board.
Troubleshooting:
1. Check the brake for proper operation according to manufacturer specifications.
2. Verify that the BR contactor supplies the module with sufficient voltage when the Pick command is sent.
FCL 1 - 4 - MODULE ADDRESS ERROR
Description: A brake module address conflict has been detected. The car will stop at the next destination.
Three consecutive occurrence faults reset automatically after 8 seconds. If the module consecutively faults again, fault “Brake Module Fault Limit Reached” is issued and must be reset on the HC-CTL-2 board.
Troubleshooting: Verify SW3 positions for each module.
Please refer to “SW3 Module ID and Software
Features” on page 5-84 .
FCL 1 - 4 - MODULE OVERHEAT
Description: The IGBT units on the bottom of the TC-FCP board generate heat when operating. A thermal sensor on the heat sink is connected to the module logic board through the TS1 and TS2 inputs. If the temperature becomes excessive, the logic module will generate a fault, pulling the FLT output to the Common connection level and alerting the controller.
Troubleshooting:
1. The fault will reset when the module cools.
2. If this is a recurring event, check the brake for proper operation. Check that brake pick and hold volt-
ages are correct. Please refer to “FCL Power Data Menu” on page 4-139 .
FCL 1 - 4 - NOT CALIBRATED
Description: The addressed module is not calibrated to operate with the Motion 4000 system.
Troubleshooting: Calibrate the module. Please refer to “Calibration (CAN Only)” on page 5-88 .
FCL 1 - 4 - TRYING TO RUN IN MANUAL RELEASE MODE
Description: Module is in manual release mode and the controller is attempting to run the car which involves operating the brake.
Troubleshooting: Disable manual release mode. Please refer to “SW1, Manual Bypass” on page 5-83 .
FIRE SERVICE PHASE 1 - ALTERNATE
Description: The car is returning to an alternate fire return landing. The FRS input is low and the FRA input is high or FRAON is active.
Troubleshooting: Inspect the fire sensors (especially the main floor sensor) and Fire Phase I switch wiring. For some fire codes, including ASME, the Fire Phase I switch must be turned to the BYPASS position and then back to OFF to clear the fire service status once activated.
5-20 Manual # 42-02-2P25
Motion 4000
Status and Error Messages
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
FIRE SERVICE PHASE 1 - MAIN
Description: The car is returning to the main fire return landing. The FRS input is low or the FRON or
FRON2 inputs are high.
Troubleshooting: Inspect fire sensors and Fire Phase I switch wiring. For some fire codes, including
ASME, the Fire Phase I switch must be turned to the BYPASS position and then back to OFF to clear the fire service status once activated.
FIRE SERVICE PHASE 2
Description: The FCS controller input is ON.
Troubleshooting: Inspect the phase 2 switch and wiring. In some cases, to exit Fire Service Phase 2, the car must be at the fire floor at which Fire Phase 2 was activated, the doors must be fully open, and the phase 2 switch must be off (the FCOFF input must be activated) to exit phase 2.
FRONT DOL AND DLK ARE BOTH ACTIVE
Description: A critical failure has caused both the Door Open Limit and Door Lock inputs to be active at the same time.(DOL=0 & DLK=1). There is a problem with DOL and/or DLK circuitry or wiring.
Troubleshooting: Inspect the Door Open Limit and the Door Lock circuitry and wiring. When this error is generated, the car will shut down with the doors open and will not answer any calls. The only way to reset this error condition is to put the car on Inspection operation.
FRONT DOOR FAILED TO CLOSE
Description: Doors Open (DCL = 1). There is a problem with DCL circuitry or wiring.
Troubleshooting: Inspect the Door Closed Limit circuitry and wiring. When this error is generated, the car is not allowed to run.
FRONT DOOR IS LOCKED BUT NOT FULLY CLOSED
Description: Doors Open (DCL = 1) and Locked (DLK = 1). There is a problem with DCL and/or DLK circuitry or wiring.
Troubleshooting: Inspect the Door Closed Limit and the Door Lock circuitry and wiring. When this error is generated, the car is not allowed to run.
FRONT DOOR LOCK SWITCH FAILURE
Description: The front door lock contacts have failed closed.
Troubleshooting: Ensure that, with the front hoistway doors closed and locked, there is power on the DLS input and no power present on the DCL input.
FRONT DOOR OPEN LIMIT FAILURE
Description: The door open limit switch has failed open.
Troubleshooting: Ensure that the car gate is open, there is no power on the DOL input, and no power present on the DL or GS inputs.
FRONT DZ RELAY DISCREPANCY
Description: HC-CTL-2 door zone input and door zone flag from TC-MPI board do not match. The elevator will stop at the next floor in the direction of travel and shut down until the fault is cleared (HC-CTL-2 fault reset or toggle Inspection switch).
Troubleshooting:
1. Verify door zone (virtual if ELGO system, magnet if LS-EDGE) input. Reset A, B, and C processors on
TC-MPI board.
2. Verify connection between MPI board DZFO and CTL-2 board DZF.
FRONT GATE SWITCH FAILURE
Description: The front car gate switch has failed closed.
Troubleshooting: Ensure that, with the front car gate closed, there is power on the GS input and no power present on the DCL input.
5
5-21
Troubleshooting
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
GOVERNOR SWITCH OPEN
Description: The overspeed governor has activated, opening the safety circuit.
Troubleshooting: Check the overspeed governor.
GROUP TO CAR COMMUNICATION LOSS
Description: The car controller has detected a loss of communication with the group controller.
Troubleshooting:
1. Verify that the group controller MCP board is functioning properly. Reset if necessary.
2. Verify that SW1, switch 4 is set to OFF on the group controller HC-CHP board (determines communication baud rate).
3. Check the CAN cable between External Network connector J4 on the car MC-MPU board and External
Network connector J17 on the group HC-CHP board.
4. Check polarity of the CAN connection (CANH/CANH and CANL/CANL).
GS INPUT FAILURE
Description: The Gate Switch (GS) input has detected a failure of the ABGA or GBB outputs, DPM, DLAB, or the gate switch.
Troubleshooting:
1. Check the gate switch. DPM should activate two inches before the gate switch.
2. If GS is active, DLAB must also be active.
GSR INPUT FAILURE
Description: The Rear Gate Switch (GSR) input has detected a failure of the ABGAR or RABA outputs,
DPMR, DLABR, or the rear gate switch.
Troubleshooting:
1. Check the gate switch. DPMR should activate two inches before the gate switch.
2. If GSR is active, DLABR must also be active.
HALL AND CAR CALL BUSES DISCONNECTED
Description: A fuse or wiring problem has stopped power to the call circuits.
Troubleshooting: Refer to troubleshooting instructions for CAR CALL BUSS IS DISCONNECTED and HALL
CALL BUS IS DISCONNECTED messages.
HALL CALL BUS IS DISCONNECTED
Description: A fuse or wiring problem has stopped power to the hall call circuits. Activated by HBF input on the car or HCB FAIL message from the Group via the CAN bus. If the WLD input is programmed but not activated, the Car will go into Wild (Emergency Dispatch) operation.
Troubleshooting: Check Group for HCB FAIL message on Status display. Check the hall call bus fuse and the wires to the hall call power inputs in the Car controller and/or Group controller.
HEAVY LOAD WEIGHER CONDITION
Description: The HLI input has been activated.
Troubleshooting: In Program Mode, see if a spare input is programmed as an HLI input, then check to see if that input is activated.
HOISTWAY ACCESS
Description: Hoistway access is active.
Troubleshooting:
Informational only.
HOISTWAY DOOR BYPASS SW. FAILURE
Description: The expected input logic from the HOISTWAY DOOR BYPASS switch has failed.
Troubleshooting:
1. Cycle the HC-CTL-2 board hoistway door bypass switch a few times to exercise it. Verify that it is fully in the ON or OFF position.
2. Verify 2 and DLAB connections and wiring.
5-22 Manual # 42-02-2P25
Motion 4000
Status and Error Messages
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
HOISTWAY SAFETY DEVICE OPEN
Description: One of the hoistway safety devices has activated, opening the safety circuit (e.g., pit stop switch, car and counterweight buffer switches, up/down final limit switches).
Troubleshooting: Check all hoistway safety devices. Refer to controller wiring prints for applicable devices. Verify that the SAFH terminal on the HC-CTL-2 board is powered.
HOSPITAL PHASE 1 OPERATION
Description: A hospital emergency call switch is activated.
Troubleshooting: Check that the hospital emergency operation option is set correctly. If hospital emergency operation is not required, set to no. If required, set floors eligible to answer a hospital call to yes.
HOSPITAL PHASE 2 OPERATION
Description: The car has answered a hospital emergency call or the in-car hospital emergency key switch has been activated (HOSP is high).
Troubleshooting: Check that the hospital emergency operation option is set correctly, then check to see if any spare inputs are programmed as HOSP and if they are activated.
ICPD INPUT FAILURE
Description: The Car Panel Inspection Down (ICPD) input is high while the 2 bus is low.
Troubleshooting:
1. Check for incorrect wiring or short on the HC-CTL-2 board ICPD input and 2 bus.
ICPU INPUT FAILURE
Description: The Car Panel Inspection Up (ICPU) input is high while the 2 bus is low.
Troubleshooting:
1. Check for incorrect wiring or short on the HC-CTL-2 board ICPU input and 2 bus.
ICTD INPUT FAILURE
Description: The Car Top Inspection Down (ICTD) input is high while the SAFH bus is low.
Troubleshooting:
1. Check for incorrect wiring or short on the HC-CTL-2 board ICTD input.
ICTU INPUT FAILURE
Description: The Car Top Inspection Up (ICTU) input is high while the SAFH bus is low.
Troubleshooting:
1. Check for incorrect wiring or short on the HC-CTL-2 board ICTU input.
INA INPUT FAILURE
Description: The INA (COP access enable switch) input did not receive a signal when expected.
Troubleshooting:
1. Check for incorrect wiring or short on the HC-CTL-2 board INA input and 2 bus.
2. Check access enable switch in COP and connection through traveler.
INAX REDUNDANCY FAULT
Description:
Troubleshooting:
IN-CAR INSPECTION
Description: The controller is currently on IN-CAR inspection, activated by 120VAC at screw terminal INCP on the HC-CTL-2 board.
IN CAR INSPECTION BUTTON STUCK
Description: The in car inspection button is stuck closed.
IN CAR STOP SWITCH ACTIVATED
Description: The in-car stop switch has been pulled, opening the safety circuit.
Troubleshooting: Check the status of the in-car emergency stop switch.
5
5-23
Troubleshooting
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
INCP INPUT FAILURE
Description: The Car Panel Inspection INSP/Auto Switch input (INCP) is high while the 2 bus is low.
Troubleshooting:
1. Check for incorrect wiring or short on the HC-CTL-2 board INCP input and 2 bus.
INCT INPUT FAILURE
Description: The Car Top Inspection INSP/AUTO Switch input (INCT) is high while SAFH is low.
Troubleshooting:
1. Check for incorrect wiring or short on the HC-CTL-2 board INCT input and SAFH or 2 bus.
INDEPENDENT SERVICE OPERATION
Description: The Independent Service switch inside the car has been turned on.
Troubleshooting: If unintended, check the Independent Service switch.
INSPECTION DIRECTION SW. FAILURE
Description: Both UP and DN Machine Room Inspection directions are active at the same time.
Troubleshooting:
1. Exercise the HT-CTL board Inspection direction switch. Verify that it remains in the middle when released.
2. Check status of UP and DOWN indicator LEDs.
INSPECTION OPERATION
Description: The car is on Inspection operation.
Troubleshooting: If unintended, check all inspection switches and associated wiring.
LEVELING DOWN
Description: The Level Down input is ON. This input is normally ON when the car is just above a floor.
Troubleshooting: Check F7 programming. Check LS-EDGE sensor.
LEVELING UP
Description: The Level Up input is ON. This input is normally ON when the car is just below a floor.
Troubleshooting: Check F7 programming. Check LS-EDGE sensor.
LIGHT LOAD WEIGHER CONDITION
Description: The Light Load Weighing input is activated.
Troubleshooting: Ensure that Light Load Weighing is required. If not, set the Light Load Weighing option to NO and ensure that the LLI input is not programmed. If Light Load Weighing is required, ensure that the
Light Load Car Call Limit is set to the correct number of stops.
LOSS OF DOOR LOCK OUT OF DOOR ZONE
Description: Door lock lost with elevator outside of door zone (i.e., outside of door zone and leveling).
May also be generated at speed if the door locks are clipped.
Troubleshooting: Inspect door lock circuitry and wiring. Check for any mechanical contact with gate switch or door clutch (if restrictor used) and hoistway components.
LS-EDGE BOTTOM TERMINAL POSITION DEVIATION
Description: LS-EDGE encountered terminal magnets that do not match the learned positions.
Troubleshooting:
1. Verify magnets for terminals have not been changed.
2. Relearn terminal magnets location by performing a floor learn.
LS-EDGE COULD NOT WRITE TO PLD
Description: The ETS trip value cannot be written to the landing system PLD.
Troubleshooting:
1. PLD hardware has failed or software is not loaded.
2. Verify software versions for LS-EDGE.
5-24 Manual # 42-02-2P25
Motion 4000
Status and Error Messages
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
LS-EDGE CPU-B IS OFFLINE
Description: CPU-B in the LS-EDGE sensor head is not communicating.
Troubleshooting:
1. Verify sensor to cartop connection.
LS-EDGE DZF OUTPUT REDUNDANCY FAULT
Description: Measured DZ and the 24VDC discrete DZ sent to the MC-LSI do not match.
Troubleshooting:
1. Check for back-fed wires at the MC-LSI or HC-CTL-2 board.
2. When the reader is sensing a DZ magnet (DZ LED on the reader is on), there should be 24VDC at the
DZ_M terminal on the MC-LSI board.
3. Conversely, there should be about 0VDC at the DZF-M terminal on the MC-LSI board when the reader is not sensing DZ.
LS-EDGE DZR OUTPUT REDUNDANCY FAULT
Description: Measured DZR and the 24VDC discrete DZR sent to the MC-LSI do not match.
Troubleshooting:
1. Check for back-fed wires at the MC-LSI or HC-CTL-2 board.
2. When the reader is sensing a DZR magnet (DZR LED on the reader is on), there should be 24VDC at the DZR_M terminal on the MC-LSI board.
3. Conversely, there should be about 0VDC at the DZR-M terminal on the MC-LSI board when the reader is not sensing DZR.
LS-EDGE LEARN MODE ACTIVE
Description: The LS-EDGE hoistway learn procedure is active.
Troubleshooting:
Informational only.
LS-EDGE QUADRATURE SENSOR LOSS
Description: One pair of LS-EDGE quadrature signals have been lost.
Troubleshooting:
1. A hall effect sensor may have failed or the bias magnet is broken or defective.
LS-EDGE STUCK SENSOR FAULT
Description: A leveling or terminal sensor is not changing state.
Troubleshooting:
1. Verify the LED indicators show state changes while traversing door zones, ETS, or Terminal magnets.
2. Replace LS-EDGE tape reader.
LS-EDGE TOP TERMINAL POSITION DEVIATION
Description: LS-EDGE encountered terminal magnets that do not match the learned positions.
Troubleshooting:
1. Verify magnets for terminals have not been changed.
2. Relearn terminal magnet locations by performing a floor learn.
M2L INPUT FAILURE
Description: The M2L input monitors the status of the relay contacts of SAFL and SAFS against the circuits that drive these relay coils. Bus 2L should be 120VAC and relay SAFL should be picked only if the doors are locked. 2MV bus must also be active. The M2L input is verified when the PM contactor is energized.
Troubleshooting:
1. Check or replace relays SAFL and/or SAFS on the HC-CTL-2 board.
2. Verify that IDC terminal 2L on the HC-CTL-2 board connects to IDC terminal 2L on the TC-MPI board.
5
5-25
Troubleshooting
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
MABB INPUT FAILURE
Description: The Bottom Access Bypass Monitor (door close contacts) (MBAB) input monitors operation of the solid state devices associated with bypassing bottom hoistway door contacts during access operation.
Troubleshooting: Remove the car from access operation and verify that test point MBAB on the HC-CTL-2 board is low with respect to 1 bus.
MABBR INPUT FAILURE
Description: The Bottom Rear Access Monitor (door close contacts) (MABBR) input monitors operation of the solid state devices associated with bypassing bottom rear hoistway door contacts during access operation.
Troubleshooting: Remove the car from access operation and verify that test point TP43 (MABBR) on the
HC-CTL-2 board is low with respect to 1 bus.
MABGF INPUT FAILURE
Description: The Front Access Gate Bypass Monitor (MABGF) input has detected a failure of the Access
Bypass Gate A (ABGA) or Front Access Bypass Bottom (FABB) outputs.
Troubleshooting:
1. Temporarily disconnect then reconnect the CAN connection to the HC-CTL-2 board to reset the microprocessors.
2. Verify that SPA, SPB, and SPC LEDs are all lighted.
3. If this failure occurred while updating software, refer to the update instructions and repeat the process.
MABGR INPUT FAILURE
Description: The Rear Access Gate Bypass Monitor (MABGR) input has detected a failure of the Rear
Access Bypass Gate A (ABGAR) or Rear Access Bypass (RABA) outputs.
Troubleshooting:
1. Temporarily disconnect then reconnect the CAN connection to the HC-CTL-2 board to reset the microprocessors.
2. Verify that SPA and SPB LEDs are lighted.
3. If this failure occurred while updating software, refer to the update instructions and repeat the process.
MABT INPUT FAILURE
Description: The Top Access Bypass Monitor (door close contacts) (MABT) input monitors operation of the solid state devices associated with bypassing the top hoistway door contacts during access operation.
Troubleshooting: Remove the car from access operation and verify that test point MABT on the HC-CTL-2 board is low with respect to 1 bus.
MABTR INPUT FAILURE
Description: The Top Rear Access Bypass Monitor (MABTR) input monitors proper operation of the solid state devices associated with bypassing the top rear hoistway door contacts during access operation.
Troubleshooting: Remove the car from access operation and verify that test point MABTR on the HC-CTL-
2 board is low with respect to 1 bus.
MACHINE ROOM INSPECTION
Description: The controller is in MACHINE ROOM inspection operation.
MBAB INPUT FAILURE
Description: The Bottom Access Bypass Monitor (door lock contacts) (MBAB) input has detected a failure of the Bottom Access Bypass (BAB) or (BABA) outputs or the BAB input.
Troubleshooting:
1. Check wiring at HC-CTL-2 board terminal BAB.
5-26 Manual # 42-02-2P25
Motion 4000
Status and Error Messages
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
MBABR INPUT FAILURE
Description: The Bottom Rear Access Bypass monitor (door lock contacts) (MBABR) input has detected a failure of the Bottom Rear Access Bypass (BABR) or (BABAR) outputs or the BABR input.
Troubleshooting:
1. Check wiring at HC-CTL-2 board terminal BABR.
2. Check Access switches and proper wiring of access terminals (ABU, ABD).
MCSB INPUT FAILURE
Description: The Car Stop Bypass Monitor (MCSB) input on the HC-CTL-2 board is active while the car stop bypass circuit is not active.
Troubleshooting:
1. Verify wiring and connections at ESC and SAFC.
2. Temporarily disconnect then reconnect the CAN connection to the HC-CTL-2 board to reset the microprocessors.
3. Verify that SPA, SPB, and SPC LEDs are all lighted.
4. If this failure occurred while updating software, refer to the update instructions and repeat the process.
MDLR INPUT FAILURE
Description: The Monitor Rear Door Lock (DLR) input has detected a failure of the Rear Hoistway Door
Bypass (HDBBR) or Rear Bottom Access Bypass (BABBR) outputs, Rear Gate Switch (GSR), Rear Door Position Monitor (DPMR), or Rear Door Lock Access Bypass (DLABR) inputs.
Troubleshooting:
1. Check voltage on HC-CTL-2 board terminal DLABR. DPMR should activate two inches before DLABR.
2. If DLR is active, GSR must also be active.
MDZLV INPUT FAILURE
Description: The Door Zone/Leveling Monitor (MDZLV) input has detected a failure of the Door Zone/Leveling (DZLV) or (DZLVA) outputs or failure of the normally open DZ relay.
Troubleshooting: Replace relay DZ.
MGB INPUT FAILURE
Description: Gate switch bypass circuit failure detected.
Troubleshooting:
1. Toggle the gate bypass switch on the HC-CTL-2 board a few times, then make certain it is fully in the
ON or OFF position.
2. Briefly disconnect then reconnect CAN connection to CTL board to reset processors.
MGBR INPUT FAILURE
Description: Rear gate switch bypass circuit failure detected.
Troubleshooting:
1. Toggle the gate bypass switch on the HC-CTL-2 board a few times, then make certain it is fully in the
ON or OFF position.
2. Briefly disconnect then reconnect CAN connection to CTL-2 board to reset processors.
MGS INPUT FAILURE
Description: The Gate Switch Monitor (MGS) input has detected a failure of the gate switch or Door Zone/
Door Zone Leveling (DZ/DZLVA) circuitry.
Troubleshooting:
1. Check gate switch condition.
2. If rear doors are present, check GSR.
5
5-27
Troubleshooting
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
MGSR INPUT FAILURE
Description: The Rear Gate Switch Monitor (MGSR) input (HC-CTL-2 board) has detected a failure of the rear gate switch or Door Zone/Door Zone Leveling (DZ/DZLVA) circuitry.
Condition 1: MGSR should be low during automatic operation when either the rear gate or rear hoistway doors are open as indicated by the GSR and DLR relays, except during re-leveling.
Troubleshooting:
1. If either relay GSR or DLR is not picked, verify that TP48 is low.
2. Check continuity between terminals GS1 and GSR1 on the HC-CTL-2.
Condition 2: If the car is re-leveling, and the front doors are closed, the MGSR input should have 120VAC.
Troubleshooting: Check GSR2 on the HC-CTL-2 board.
Condition 3: This fault is also generated if relays GSR and DLR are picked, indicating that the rear gate and hoistway doors are closed, but the MGSR input is low.
Troubleshooting:
1. Verify relays DLR and GSR are both picked.
2. Verify 120VAC on terminals GSR1 and GSR2.
3. Verify 120VAC on (MDLR) on the HC-CTL-2 board.
4. Verify 120VAC on GSR2 on the HC-CTL-2 board.
MHDB INPUT FAILURE
Description: The Hoistway Door Bypass Monitor (MHDB) input has detected a failure of the Hoistway Door
Bypass (HDB) or (HDBA) outputs.
Troubleshooting:
1. Toggle the door bypass switch on the HC-CTL-2 board a few times, then make certain it is fully in the
ON or OFF position.
2. Briefly disconnect then reconnect CAN connection to CTL board to reset processors.
MHDBR INPUT FAILURE
Description: The Rear Hoistway Door Bypass Monitor (MHDBR) input has detected a failure of the Rear
Hoistway Door Bypass (HDBR) or (HDBBR) outputs.
Troubleshooting:
1. Toggle the door bypass switch on the HC-CTL-2 board a few times, then make certain it is fully in the
ON or OFF position.
2. Briefly disconnect then reconnect CAN connection to HC-CTL-2 board to reset processors.
MOTOR LIMIT TIMER (ANTI-STALL) ELAPSED
Description: The Starter or Thermal Overload has tripped or there is a mechanical problem that prevents or slows motion of the car.
Troubleshooting: To clear the condition, the car must be put on Inspection, then back into Normal operation, or the RESET button must be pressed. Immediately check the starter and thermal overloads and all circuitry associated with the motor.
MPI SPA IS OFFLINE, MPI SPB IS OFFLINE
Description: The indicated safety processor on the TC-MPI board is off line.
Troubleshooting:
1. Verify CAN connection to TC-MPI board.
2. Reset processors (MPI board RSTA, RSTB, RSTC buttons).Verify ON LED lighted for all processors.
3. If fault occurs while updating software, refer to update instructions and repeat process.
5-28 Manual # 42-02-2P25
Motion 4000
Status and Error Messages
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
MPI A EEPROM FAULT
Description: A device error has been detected during a cyclic redundancy check (code=1) or while reading from or writing to the device (code=2).
Troubleshooting:
1. Reset the microprocessor.
2. Check that serial data links are properly connected and routed using shielded cable (through conduit where appropriate).
3. Check for recently installed equipment that might be generating electrical noise.
4. If the error occurred while updating firmware, re-attempt the update procedure.
MPI A EMERGENCY BRAKE CYCLE TEST FAULT
Description: One of the EBP1/2/3/4 relays has failed the cycle test. If moving, the elevator will be taken out of service at the next landing. If in a landing zone, the elevator doors will open and the elevator will be taken out of service.
Troubleshooting:
MPI-A LANDING SYSTEM ETS MISMATCH
Description: SPA on TC-MPI board and landing system ETS positions do not match.
Troubleshooting:
1. Program the desired ETS Overspeed percentage, F7 204.
MPI-A LANDING SYSTEM FLOOR MISMATCH (FLOOR LEARN REQUIRED)
Description: The MPI or LS-EDGE has been replaced and floor tables do not match.
Troubleshooting:
1. Perform a floor learn.
MPI A UNINTENDED MOTION
Description: TC-MPI board has detected the car moving away from the door zone with both car gate and hoistway doors not fully closed and locked. Power will be removed from brake and motor, emergency rope gripper will engage.
Troubleshooting:
1. Put the car on Inspection.
2. Press Fault Reset on the HC-CTL-2 board.
3. Hold down the EB RESET button on the TC-MPI board for at least 8 seconds to reset the rope brake.
MPI-A or B 2L BUS MONITOR FAULT
Description: The 2L AC bus has fallen below the expected voltage.
Troubleshooting:
1. Check the 2L bus fuse.
2. Check connection at PMT terminal X4.
MPI A or B EBPS MONITOR FAULT
Description: The EBPS, Emergency Brake Power Supply, (A and or B) input to the TC-MPI is in an opposite state from the RGR1_A/B, RGR2_A/B, and RGOK_A/B inputs.
Troubleshooting:
1.
Check for 120 VAC on TC-MPI board terminal EBPS. If not present, check governor overspeed switch or fuse FEB (3 A type MDQ or 313 slow acting fuse).
2. Check terminals RG1 and RG7 for 120VAC (power supply output).
3. If no power at RG1 and RG7, check power supply
5
5-29
Troubleshooting
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
MPI A or B EXCESSIVE FAULTS SHUTDOWN
Description: The named processor has detected faults beyond an established limit in a circumscribed period of time.
Troubleshooting:
1. Check the connections to and from the TC-MPI board.
2. Reset the microprocessor.
3. Test elevator for proper operation.
MPI A or B GOVERNOR OVERSPEED
Description: The named processor has detected the opening of the governor overspeed switch. The car will be brought to an immediate emergency stop.
Troubleshooting:
1. If the governor overspeed switch has not opened, check switch integrity and connections.
2. If the car had in fact exceeded governor overspeed switch opening speed, troubleshoot to determine that cause of the overspeed.
MPI A or B INCORRECT LANDING SYSTEM CHANNEL DETECTED
Description: The named processor has detected that its associated CAN connection from the landing system is not reporting the correct channel identification. Usually, this means that the CAN 1 and CAN 2 connections from the hoistway position sensor to the TC-MPI board have been “swapped” at the TC-MPI board connector.
Troubleshooting:
1. Exchange the CAN 1 and CAN 2 connections on the TC-MPI board J17 connector.
MPI A or B INSPECTION OVERSPEED
Description: The car has exceeded the Parameter 146 speed setting (F7 menu).
Troubleshooting:
1. Check physical motor related settings on drive.
2. Verify inspection speed through the LCD screen (F3 Controller Utilities menu).
5-30 Manual # 42-02-2P25
Motion 4000
Status and Error Messages
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
MPI A or B LANDING SYSTEM COMM LOSS
Description: The TC-MPI board is not communicating with the landing system properly (A or B channel lost). Before beginning troubleshooting, check all related CAN connections and connectors carefully.
Troubleshooting:
1. On the controller processor board, place F3 in the UP position. Press “N” to access the system menu.
Press “N” to advance to the Controller System Menu. Press “S” to select. The ELGO CAN channels will be displayed.If a channel has failed, the position information for that channel will be missing. For example:
5
Connections Through Traveler
1. Check that the CAN connections at J17 on the TC-MPI board are clean and tight.
2. On the cartop, temporarily disconnect the MACHINE ROOM / CANL2 and CANH2 wires from the MC-LSI board. Measure the resistance between them. It should read about 120-ohms (the termination value on the TC-MPI board). Repeat for the CANL1 and CANH1 wires. They should also read about 120-ohms.
If a measured resistance other than about 120-ohms, you may have a damaged, broken, or shorted wire in the traveler. Resolve this issue before proceeding with additional troubleshooting.
CHANNEL A
1. If the lost channel is the A (CAN 2) channel, unplug all HC-CPI (control panel interface) and HC-UIO
(universal I/O) board CAN connections from the TC-LSI (landing system interface board) on the cartop
(CAN 2 is a shared bus).Recheck the display to see if both channels are now back on line.
2. If the ELGO channels are now OK, reconnect the UIO boards one at a time. If the channel is lost, check the CAN terminations on the UIO board. If the board is terminated, open the termination by moving the jumper so the header pins are not shorted. Repeat for additional UIO boards, checking ELGO information as you go.
3. Check the HC-CPI boards to see that only the last board in the string is terminated (CAN). Reconnect the CPI boards. Check ELGO information. If the A channel is lost again as you reconnect boards, contact MCE support for help in isolating the bad board or termination.
4. If, after disconnecting the CPI and UIO boards, the A channel remained off line, temporarily connect
CAN 1 connections to CAN 2 on the TC-MPI board. Place the processor F3 switch down and check the error code on the display:
• MPI-A INCORRECT LANDING SYSTEM CONNECTED - replace the ELGO reader head
• MPI-A LANDING SYSTEM COMM LOSS - continue numbered steps.
5. Temporarily connect CAN 2 connections to CAN 1 on the TC-MPI board. If the message changes to MPI-
A INCORRECT LANDING SYSTEM CONNECTED, replace the ELGO reader head. If the message remains
MPI-A LANDING SYSTEM COMM LOSS, replace the TC-MPI board.
CHANNEL B
1. If the lost channel is the B (CAN 1) channel, temporarily connect CAN 2 to CAN 1 on the TC-MPI board.
2. If the display changes to MPI-B INCORRECT LANDING SYSTEM CONNECTED, replace the TC-MPI board.
3. If the message remains MPI-B LANDING SYSTEM COMM LOSS, replace the ELGO reader head.
MPI A or B LANDING SYSTEM FAULT (EMERGENCY BRAKE DROPPED)
Description: The emergency brake dropped due to a landing system fault while the door gate and door lock were open. The landing system fault is either (MPI-A/B) Relative Position High, Relative Position Low, or Landing System Comm Loss.
Troubleshooting:
1. Check the troubleshooting for the referenced faults.
5-31
Troubleshooting
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
MPI A or B LEVELING OVERSPEED
Description: MPI A or B on the TC-MPI board is reporting an overspeed during leveling.
Troubleshooting:
1. Use a hand-held tach to determine car speed during leveling.
2. Check that the F7, Leveling Overspeed setting is correctly set (generally about 8% above drive LF.41, leveling speed).
3. Check that the drive leveling speed, LF.41 is correctly set (about 16% of contract speed).
4. Check that F7, Leveling Distance is correctly set (generally 4.0 inches).
5. Check that drive LF.53 Decel Jerk, LF.54 Decel, and LF.55 Flare Jerk are properly set per your contract speed.
6. The drive uses LF.50-51, LF.42 High Speed, and LF.20 Contract Speed settings to determine minimum slowdown distance, check that these are properly set.
MPI A or B PMDD CONTACTOR DROP MONITOR FAULT
Description: MPI A or B on the TC-MPI board is reporting that the primary motor drop delay contactor did not drop out at the end of a run.
Troubleshooting:
1. PM delay drop relay K6 is stuck open.
2. Verify that 2MV or 2L is not active.
3. Verify that drive disable delay, F7 parameter 138, is less than 2 seconds.
4. Verify the status of 2MV, 2L, and PMDD through MPI-C, F5 diagnostics.
Please refer to “MPI-C Diagnostics” on page 4-87
.
MPI A or B PMDD CONTACTOR PICK MONITOR FAULT
Description: MPI A or B on the TC-MPI board is reporting that the primary motor drop delay contactor did not pick at the beginning of a run.
Troubleshooting:
1. PM delay drop relay K6 is stuck closed.
2. Verify that 2MV and 2L have power. Doors must be closed and the SAFS relay must be picked for 2L to be active.
3. Verify the status of 2MV, 2L, and PMDD through MPI-C, F5 diagnostics.
Please refer to “MPI-C Diagnostics” on page 4-87.
MPI A or B RGOK DROPPED
Description: No voltage detected at terminal RG5 on the TC-MPI board. The OK indication from the rope gripper, which was previously present, has dropped while the car was in motion.
Troubleshooting:
1. Check emergency brake microswitch wiring.
2. Cars without a rope brake should have a permanent jumper between RG5 and RG7.
3. Make sure there is 120V at EBPS terminal of the TC-MPI board.
4. One of the EBP1, EBP2, EBP3, or EBP4 relays may have failed open.
5. Check that when EBPS is high and 2MV is high that there is 120V at terminal RG1.
6. Reset the rope brake: Press fault reset on the HC-CTL-2 board. Hold down the EB RESET button on the
TC-MPI board for at least 8 seconds.
5-32 Manual # 42-02-2P25
Motion 4000
Status and Error Messages
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
MPI A or B RGOK FAILED TO ACTIVATE
Description: No voltage detected at terminal RG5 on the TC-MPI board.
Troubleshooting:
1. Check emergency brake microswitch wiring.
2. Cars without a rope brake should have a permanent jumper between RG5 and RG7.
3. Make sure there is 120V at EBPS terminal of the TC-MPI board.
4. One of the EBP1, EBP2, EBP3, or EBP4 relays may have failed open.
5. Check that when EBPS is high and 2MV is high that there is 120V at terminal RG1.
6. Reset the rope brake: Press fault reset on the HC-CTL-2 board. Hold down the EB RESET button on the
TC-MPI board for at least 8 seconds.
MPI A or B RGOK FAILED TO DEACTIVATE
Description: The processor is reporting that the RGOK monitor signal is active with the Emergency Brake disabled.
Troubleshooting:
1. Check that no wire is inserted into the RG5 terminal on the TC-MPI board. When the Emergency Brake option is set to DISABLED, the controller expects no voltage at the RG5 terminal.
MPI A or B SPC IS OFFLINE
Description: TC-MPI board safety processor MP is offline.
Troubleshooting:
1. Power to the TC-MPI board may not be connected. Check the CAN bus connection between the TC-MPI board and the CAN hub.
2. Make sure jumper JP6 on the TC-MPI board is not shorted.
3. If the MP indicator is not lighted, reboot the processor by cycling power to the controller or by removing the CAN bus connection to the TC-MPI board for a few seconds.
MPI-A or B UNT SW HIGH OVERSPEED
Description: The processor has detected an Up Normal Terminal Switch High overspeed (exceeding switch
Speed setting plus Delta High speed setting). Power will be removed from brake and motor to bring the car to an immediate halt. The car will then move at reduced speed to the next landing in the direction of travel.
If the fault clears, the car will resume normal service. If not, the car will open its doors and remove itself from service.
Troubleshooting:
1. Check the integrity of the landing/positioning system encoded tape.
2. If the job has a physical UNT switch, check the switch and connections.
3. Check appropriate F5 menu overspeed parameters (17 - 40), to determine what car speed was at that switch for the last normal run and at the time of the overspeed.
4. Check Minimum Slowdown Distance (F5 drive LP.2). Must be less than: Shortest floor height minus
(Level Distance + Maximum Stepping Distance + 6 inches). LP.2 is a displayed value, not directly adjustable but affected by F5 drive LF.20, LF.50, LF.51, LF.52, LF.53, LF.54, LF.55.
MPI-A or B UNT SW LOW OVERSPEED
Description: The processor has detected an Up Normal Terminal Switch Low overspeed (exceeding switch speed setting plus Delta Low speed setting). The car will perform an emergency slowdown, then move at reduced speed to the next landing in the direction of travel. If the fault clears, the car will resume normal service. If not, the car will open its doors and remove itself from service.
Troubleshooting:
1. Check the integrity of the landing/positioning system encoded tape.
2. If the job has a physical UNT switch, check the switch and connections.
3. Check appropriate F5 menu overspeed parameters (17 - 40), to determine what car speed was at that switch for the last normal run and at the time of the overspeed.
4. Check Minimum Slowdown Distance (F5 drive LP.2). Must be less than: Shortest floor height minus
(Level Distance + Maximum Stepping Distance + 6 inches). LP.2 is a displayed value, not directly adjustable but affected by F5 drive LF.20, LF.50, LF.51, LF.52, LF.53, LF.54, LF.55.
5
5-33
Troubleshooting
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
MPI A or B UNT SW POSITION ERROR
Description: The UNT switch was not detected at the expected location. The car will perform an emergency slowdown and then move at reduced speed to the next landing in the direction of travel. If the fault clears, the car will resume normal service. If not, the car will open its doors and remove itself from service.
Troubleshooting:
1. Check the integrity of the landing/positioning system encoded tape.
2. If a physical UNT switch is used on this job, check switch wiring, integrity, and position.
If this is occurring on a job that is just being set up or adjusted or has had this problem sporadically:
3. Check F7 menu U/DNT Option setting.
4. Check F7 menu DNT Distance and DNT Delta Distance.
MPI A or B UP NORMAL LIMIT OPEN
Description: The indicated processor has detected that the up directional limit switch is open. The car will run no further in the up direction.
Troubleshooting:
1. Review car adjustment and landing settings.
2. Adjust as required to prevent the car from overshooting the terminal and activating the directional limit.
3. If switch is physical, check voltage at terminal SPI4 on TC-MPI board and limit switch connections.
4. If switch is virtual, check F7 programming.
MPI-B 2MV BUS MONITOR FAULT
Description: The 2MV AC bus monitoring input on the CTL board is no longer detecting correct voltage.
Troubleshooting:
1. Check the 2MV bus fuse.
2. Check connection at PMT terminal X4.
MPI-B SPA IS OFFLINE, SPC IS OFFLINE
Description: TC-MPI displayed board safety processor is offline.
Troubleshooting:
1. Power to the TC-MPI board may not be connected. Check the CAN bus connection between the TC-MPI board and the CAN hub.
2. Make sure jumper JP4 on the TC-MPI board is not shorted.
3. If the SPx indicator is not lighted, reboot the processor by cycling power to the controller or by removing the CAN bus connection to the TC-MPI board for a few seconds.
MPI-C CONTRACT OVERSPEED
Description: The machine has exceeded contract speed.
Troubleshooting:
1. Check for correct gear ratio, drive parameter LF.22.
MPI-C DRIVE FAULT
Description: This fault indicates that the controller has detected a DFLT input The car will perform an emergency stop with the motor contactor and brake contactor immediately dropped.
Troubleshooting:
1. Check and troubleshoot drive faults.
MPI-C DRIVE NOT READY
Description: The drive ready input failed to activate. Check the drive for a fault - troubleshoot the drive fault.
Troubleshooting:
1. Check the DRDY input to the TC-MPI board.
2. Check the ready output from the drive.
3. Check that the drive is operational.
5-34 Manual # 42-02-2P25
Motion 4000
Status and Error Messages
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
MPI-C DRIVE OFFLINE (STOP MODE)
Description: The processor has detected that the drive is off line while the car is stopped.
Troubleshooting:
1. For TORQMAX drive, verify that Lf.03 is set to “run.”
MPI-C DRIVE ON FAILED TO ACTIVATE
Description: The processor has reported that the drive on signal from the inverter drive was not present when checked.
Troubleshooting:
1. Check the signal connection from the drive to TC-MPI J16, P5.
2. Check for error messages on the drive display.
3. Check that the drive is properly configured and that all connections are as shown in the job prints.
4. Check that the drive on output from the drive is in fact present (high).
MPI-C DRIVE ON FAILED TO DEACTIVATE
Description: The processor has reported that the drive on signal from the inverter drive failed to drop when checked.
Troubleshooting:
1. Check the signal connection from the drive to TC-MPI J16, P5.
2. Check for error messages on the drive display.
3. Check that the drive is properly configured and that all connections are as shown in the job prints.
4. Check that the drive on output from the drive is in fact present (high) when the elevator is stopped with no call demand.
5. Replace the drive if the signal is incorrectly present.
MPI-C DRIVE ON LOST
Description: The drive on input was lost while the car was in motion. This fault is reported immediately as opposed to the normal pre-run check Drive On fault which is rechecked after 15 seconds.
Troubleshooting:
1. Check the drive display to identify any drive faults which may have occurred.
MPI-C EEPROM CRC ERROR
Description: The Cyclical Redundancy Checksum (CRC) stored on the TC-MPI board EEPROM does not match the computed CRC from the EEPROM.
Troubleshooting:
1. Cycle power. Reload and save parameters through the F7 menu.
MPI-C EEPROM DEVICE ERROR
Description: The firmware is unable to communicate with the TC-MPI board EEPROM.
Troubleshooting:
1. Cycle power. Reload and save parameters through the F7 menu.
MPI-C EXCESSIVE FAULTS SHUTDOWN
Description: The named processor has detected faults beyond an established limit in a circumscribed period of time.
Troubleshooting:
1. Check the connections to and from the TC-MPI board.
2. Reset the microprocessor.
3. Test elevator for proper operation.
5
5-35
Troubleshooting
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
MPI-C FOLLOWING ERROR
Description: Commanded speed and speed feedback from the motor encoder have deviated by more than the percentage of Following Error set through F7, parameter 189. The car performs an emergency stop, dropping power to the motor and the brake. After stopping, the car will again attempt to run. If the error persists, the car will be removed from service.
Troubleshooting:
1. Check the encoder cable and connection.
2. Check to see what errors the drive is reporting.
3. Run the car on Inspection. Check commanded speed and speed feedback through the MPI-C diagnos-
tics screen. Please refer to “MPI-C Diagnostics” on page 4-87, addresses 16 and 18. For additional ver-
ification, use a hand tach to measure car speed. Adjust F7, 189 to 100% of contract speed to reduce sensitivity. If commanded speed and actual speed track, the problem is likely to be inadequate F7, 189 percentage or F7 and drive settings related to motor speed, gear reduction, sheave diameter, roping, etc. If commanded and actual speed deviate severely, the problem is likely to be with the encoder, encoder connection, or in the drive (which should be reporting errors as well).
MPI-C INSPECTION OVERSPEED
Description: MPI-C is reporting an inspection overspeed.
Troubleshooting:
1. Adjust drive gear ratio parameter LF.22.
2. Reset MPI board microprocessors.
MPI-C LANDING SYS A POSITION DEVIATION
Description: MPI-C on the TC-MPI board has detected that the position reported by the ELGO, A position sensor is not within limits when compared to the position synthesized feedback from the machine encoder.
The car will perform an emergency stop and remove itself from service.
Troubleshooting:
1. Check appropriate F5 menu parameters (16 for microcontroller A/B and C) to determine if the speed feedback for microcontroller C is significantly different from microcontroller A/B. If it is, modify the hoist motor Speed parameter to change the speed seen by microcontroller C.
2. Check the integrity of the position sensor head and tape. Check that the sensor head is clean.
3. Check the CAN connection from the sensor head to the MC-LSI board.
4. Replace the position system sensor head. Refer to the installation section of this manual and follow all installation steps and recommendations carefully.
MPI-C LANDING SYS B POSITION DEVIATION
Description: MPI-C on the TC-MPI board has detected that the position reported by the ELGO, B position sensor is not within limits when compared to the position synthesized feedback from the machine encoder.
The car will perform an emergency stop and remove itself from service.
Troubleshooting:
1. Check appropriate F5 menu parameters (16 for microcontroller A/B and C) to determine if the speed feedback for microcontroller C is significantly different from microcontroller A/B. If it is, modify the hoist motor Speed parameter to change the speed seen by microcontroller C.
2. Check the integrity of the position sensor head and tape. Check that the sensor head is clean.
3. Check the CAN connection from the sensor head to the MC-LSI board.
4. Replace the position system sensor head. Refer to the installation section of this manual and follow all installation steps and recommendations carefully.
MPI-C LEVELING TIMER EXCEEDED
Description: The car is traveling at leveling speed for an unusually long period of time. Direction will be dropped and a correction run will be performed to the next available landing.
Troubleshooting:
1. Verify eligibility is properly reflected in the F7 menu in regards to floor heights.
5-36 Manual # 42-02-2P25
Motion 4000
Status and Error Messages
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
MPI-C UNEXPECTED DIRECTION DROP
Description: The up or down direction input has dropped while the car is running but is not in leveling operation.
Troubleshooting:
Informational only.
MPU-A IS OFFLINE
Description: Indicates a potential failure of the HC-MPU board.
Troubleshooting:
1. Cycle power to the controller.
MSAFL1 INPUT FAILURE
Description: The MSAFL1 input monitors SAFL and SAFS relay contacts against the circuits that drive the relay coils. Bus 2L should be 120VAC and relay SAFL should be picked only if the doors are locked.
Troubleshooting:
1. Check or replace relays SAFL and/or SAFS on the HC-CTL-2 board.
2. Check that IDC terminal 2L on the HC-CTL-2 board connects to IDC terminal 2L on the TC-MPI board.
MSAFS1 INPUT FAILURE
Description: The MSAFS1 input monitors SAFL and SAFS relay contacts against the circuits that drive the relay coils. Relay SAFS should be picked only if the safety string is made.
Troubleshooting:
1. Check or replace relays SAFL and/or SAFS on the HC-CTL-2 board.
2. Check wiring associated with screw terminals SAFH, SAFC and ESC.
MTAB INPUT FAILURE
Description: The Top Access Bypass Monitor (MTAB) input has detected a failure of the Top Access Bypass
(TAB) or (TABA) outputs.
Troubleshooting:
1. Verify wiring at HC-CTL-2 board terminals TAB and DLAT.
2. Check access switches and proper wiring of access terminals ATU, ATD.
MTABR INPUT FAILURE
Description: The Top Rear Access Monitor (MTABR) input has detected a failure of the Top Rear Access
Bypass (TABR) or (TABAR) outputs or the TABR input.
Troubleshooting:
1. Verify wiring at HC-CTL-2 board terminals TABR and DLATR.
2. Check access switches and proper wiring of access terminals ATU, ATD.
MTBR INPUT FAILED TO ACTIVATE
Description: The voltage monitored at the TC-MPI board BR triac did not go high when the triac was deactivated.
Troubleshooting:
1. Check the BR test point. There should be 120V here when the triac is not attempting to pick contactor
BR.
2. Check BR, PM auxiliary contactors, and 2L screw terminal connections and wiring.
MTBR INPUT FAILED TO DEACTIVATE
Description: The voltage monitored at the TC-MPI board BR triac did not go low when the triac was activated.
Troubleshooting:
1. Check the BR test point. There should be 0V here when the triac is attempting to pick contactor BR.
2. Check BR, PM auxiliary contactors, and 2L screw terminal connections and wiring.
5
5-37
Troubleshooting
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
MTPM INPUT FAILED TO ACTIVATE
Description: The voltage monitored at the TC-MPI board PM triac did not go low when the triac was activated.
Troubleshooting:
1. Check the PM test point. There should be 0V here when the triac is attempting to pick the contactor
PM.
2. Check PM, PM2 and 2MV screw terminal connections and wiring.
MTPM INPUT FAILED TO DEACTIVATE
Description: The voltage monitored at the TC-MPI board PM triac did not go high when the triac was deactivated.
Troubleshooting:
1. Check the PM test point. There should be 120V here when the triac is not attempting to pick the contactor PM.
2. Check PM, PM2 and 2MV screw terminal connections and wiring.
NORMAL OPERATION
Description: The elevator is on “automatic” or Normal passenger operation.
NORMAL (PIT FLOOD) OPERATION
Description: The elevator is on “automatic” or Normal passenger operation with the pit flood input active.
In this mode, the car will not serve floors beneath the flood level set. Please refer to “FLR COUNT BELOW
FLOOD LEVEL?” on page 4-50
.
Troubleshooting:
1. If pit flood operation is in error, refer to the drawings for the job and verify the PTFLD input is correctly configured (connected/disconnected/connected in error).
OVERLOAD CONDITION
Description: The car appears to be overloaded, as indicated by the load weigher input OVL.
Troubleshooting: Check the OVL input. If power is present on the OVL input, the load weigher contact associated with this input is closed. This contact being closed indicates the car is overloaded.
PASSCODE REQUEST
Description: The Passcode Request Option is active (System Mode Menu).
Troubleshooting: System can be run on Inspection only. Passcode must be entered correctly in System
Mode Menu to deactivate this option and allow the controller to run normally. See 4-59
.
PLD IS OFFLINE
Description: HC-CTL-2 board safety processor C is offline.
Troubleshooting:
1. Power to the HC-CTL-2 board may not be connected. Check the CAN bus connection between the HC-
CTL-2 board and the HC-CHP CAN hub and board.
2. If the SPC indicator is not lighted, reboot the processor by cycling power to the controller or by removing the CAN bus connection to the HC-CTL-2 board for a few seconds.
3. If fault occurs while updating software, refer to update instructions and repeat process.
PMP INPUT FAILED TO ACTIVATE
Description: Normally closed Auxiliary contactor for PM contact did not drop out at end of run.
Troubleshooting:
1. Check PMP testpoint for 120V on TC-MPI board. When PM contactor is dropped, PMP should go high.
PMP INPUT FAILED TO DEACTIVATE
Description: Normally open Auxiliary contactor for PM contact did not pick at end of run.
Troubleshooting:
1. Check PMP testpoint for 120V on TC-MPI board. When PM contactor is dropped, PMP should go low.
5-38 Manual # 42-02-2P25
Motion 4000
Status and Error Messages
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
POWER TRANSFER INPUT ACTIVE
Description: The car is stopped while power is transferred from commercial to backup or vise versa.
Troubleshooting: Informational.
POWER UP SHUTDOWN DUE TO EARTHQUAKE
R2L INPUT FAILURE (CTLA)
Description: R2L monitors the state of the 2L relay. The R2L input must be low when the 2L bus is active and high when the 2L bus is low.
Troubleshooting:
Check the circuitry associated with the 2L relay.
REAR CAR DOOR BYPASS SW. FAILURE
Description: Indicates that the REAR CAR DOOR BYPASS switch has failed.
Troubleshooting:
1. Cycle the HC-CTL-2 board car door bypass switch a few times to exercise it. Verify that it is fully in the
ON or OFF position.
2. Verify 2 and GSR connections and wiring.
REAR DOL & DLK ARE BOTH ACTIVE
Description: The Door Open Limit Rear and Door Lock inputs are both active, DOLR=0 and DLK=1. There is a problem with DOLR and/or DLK circuitry or wiring.
Troubleshooting: Inspect the Door Open Limit Rear and the Door Lock circuitry and wiring. When this error is generated, the car will shut down with the doors open and will not answer any calls. To reset this error condition, put the car on Inspection operation.
REAR DOOR FAILED TO CLOSE
Description: Doors Open (DCLR = 1). There is a problem with DCLR circuitry or wiring.
Troubleshooting: Inspect the Door Closed Limit Rear circuitry and wiring. When this error is generated, the car is not allowed to run.
REAR DOOR IS LOCKED BUT NOT FULLY CLOSED
Description: Rear Doors Open (DCLR = 1) and Locked (DLK = 1). Indicates a problem with DCLR and/or
DLK circuitry or wiring.
Troubleshooting: Inspect the Door Closed Limit Rear and the Door Lock circuitry and wiring. When this error is generated, the car is not allowed to run.
REAR DOOR LOCK SWITCH FAILURE
Description: The rear door lock contacts have failed closed.
Troubleshooting: Ensure that, with the rear hoistway doors closed and locked, there is power on the
DLSR input and no power on the DCLR input.
REAR DOOR OPEN LIMIT FAILURE
Description: The rear door open limit switch has failed open.
Troubleshooting: Ensure that the rear car gate is open, there is no power on the DOLR input, and no power is present on the DLR or GSR inputs.
REAR DZ RELAY DISCREPANCY
Description: Traction elevator only. HC-CTL-2 door zone input and door zone flag from TC-MPI board do not match. The elevator will stop at the next floor in the direction of travel and shut down until the fault is cleared (HC-CTL-2 fault reset or toggle Inspection switch).
Troubleshooting:
1. Verify door zone (virtual if ELGO system, magnet if LS-EDGE) input. Reset A, B, and C processors on
TC-MPI board. Verify connection between MPI board DZRO and CTL-2 board DZR.
5
5-39
Troubleshooting
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
REAR GATE SWITCH FAILURE
Description: The rear car gate switch has failed closed.
Troubleshooting: Ensure that, with the rear car gate closed, there is power on the GSR input and no power on the DCLR input.
REAR HOISTWAY DOOR BYPASS SW. FAILURE
Description: Indicates that the REAR HOISTWAY DOOR BYPASS switch has failed.
Troubleshooting:
1. Cycle the HC-CTL-2 board hoistway door bypass switch a few times to exercise it. Verify that it is fully in the ON or OFF position.
2. Verify 2 and DLABR connections and wiring.
REDUNDANCY DOOR LOCK RELAY FAILURE
Description: One or both of the front or rear door lock relays has failed closed.
Troubleshooting:
1. Ensure that, with the hoistway doors open, there is no power present on the RDLS or RDLSR inputs. If power is present, one or more of the door lock relays has failed in the closed or picked position.
REDUNDANCY FRONT GATE SWITCH FAILURE
Description: The car gate switch relay has failed closed.
Troubleshooting:
1. Ensure that, with the car gate open, there is no power present on the RGS input. If power is present, the car gate switch relay has failed closed.
REDUNDANCY REAR GATE SWITCH FAILURE
Description: The car gate switch relay has failed closed.
Troubleshooting:
1. Ensure that, with the rear car gate open, there is no power present on the RGSR input. If power is present, the car gate switch relay has failed closed.
RESTORING SAFETY
Description: This message will be displayed while the system checks the safety integrity of the controller when coming out of car top inspection.
SABBATH OPERATION ACTIVE
Description: The spare input SAB has been activated.
Troubleshooting: Check spare input bit address for SAB. Verify that the spare input address matches the actual input connection. Check voltage level at the SAB input.
SAFC INPUT FAILURE
Description: The controller has detected that the Car Safety String (SAFC) input on the HC-CTL-2 board is in an incorrect state. It should not have 120VAC unless the SAFH input also has 120VAC.
Troubleshooting: Check the wiring or devices connected to the SAFC input. This could also be caused by a component failure on the HC-CTL-2 board.
SAFETY CIRCUIT IS OPEN
Description: The Car Operating Panel emergency stop switch has been pulled or another contact switch in the safety circuit is open.
Troubleshooting: Check the C.O.P. stop switch. Check the other switches and contacts in the safety string. Check safety string wiring against the MCE wiring diagrams.
SAFETY DROPPED BY MPU-B
Description: MPU-B on the HC-MPU board has dropped the safety relay.
Troubleshooting:
1. Cycle power. Check the event log to see what events led up to the occurrence.
5-40 Manual # 42-02-2P25
Motion 4000
Status and Error Messages
Table 5.1 Status and Error Messages
Scrolling Message - Special Event Message
SHUTDOWN OPERATION
Description: The car is on MG Shutdown Operation. MGS is high.
Troubleshooting:
1. Ensure that the MG Shutdown Operation option is set correctly. If MG Shutdown is not required, set this option to NO and ensure that the MGS Input is not programmed. If it is required, set this option to the floor that the car should return to on MG Shutdown and program the MGS Input.
SPA IS OFFLINE
Description: HC-CTL-2 board safety processor A is offline.
Troubleshooting:
1. HC-CTL-2 board power may not be connected. Check the CAN bus connection between the HC-CTL-2 board and the HC-CHP CAN board.
2. If the SPA indicator is not lighted, reboot the processor by cycling power to the controller or by removing the CAN bus connection to the HC-CTL-2 board for a few seconds.
3. If fault occurs while updating software, refer to update instructions and repeat process.
SPB IS OFFLINE
Description: HC-CTL-2 board safety processor B is offline.
Troubleshooting:
1. Power to the HC-CTL-2 board may not be connected. Check the CAN bus connection between the HC-
CTL-2 board and the HC-CHP CAN hub and board.
2. If the SPB indicator is not lighted, reboot the processor by cycling power to the controller or by removing the CAN bus connection to the HC-CTL-2 board for a few seconds.
3. If fault occurs while updating software, refer to update instructions and repeat process.
STARTING UP
Description: Indicates a power on event or exiting an inspection mode.
Troubleshooting: Informational.
TIME OUT OF SERVICE
Description: The T.O.S. timer has expired.
Troubleshooting: The elevator has been delayed, usually by a door being obstructed. The Time Out of
Service timer has expired and the elevator has been taken out of service.
TOP ACCESS SW. FAILURE
Description: The Up and Down Top Access switch inputs are active at the same time.
Troubleshooting: Check the wiring and the switch associated with the ATU and ATD inputs.
UP AND DOWN TERMINAL SPEED REDUCING LIMITS OPEN
Description: Floors have not been learned.
Troubleshooting: Check parameters for UNTS1 and DNTS1. Make sure that D/UNTS1 option is set to VIR-
TUAL. If no Elgo tape has been hung, put the car on Inspection Bypass Mode (F3 menu) to stop this fault.
WP SECURITY ACTIVATED
Description: Indicates that Wandering Patient security has been activated.
Troubleshooting:
1. If this status is in error, check to see if the system has an input assigned to WP security and if that input has 110V present.
5
5-41
Troubleshooting
Duplexing
Duplexing allows one car controller to assign hall calls to itself and one other car. Duplexing requires a connecting cable and selecting the Duplex option (
see “F1: Program Mode” on page 4-11
). Duplexing improves hall call assignment, increases efficiency, and decreases wait times.
Dispatching Algorithm
The dispatching algorithm for assigning hall calls is real-time, based on estimated time of arrival (ETA). In calculating the estimated time of arrival for each elevator, the dispatcher will consider, but not be limited to, the location of each elevator, direction of travel, existing hall and car call demand, door time, flight time, lobby removal time penalty, and coincidence call.
Hardware Connections
There are three critical points in duplexing hardware:
• Proper grounding between the two controller subplates
• Proper installation of the duplexing cable
• Jumper JP3 on each HC-MPU board must be in position
Hall calls will be connected to both cars simultaneously. Once in duplex configuration, either of the two controllers can become the dispatcher of hall calls. The controller that assumes the dispatching duty on power up remains the dispatching processor until it is taken out of service. If, for any reason, the communication link between the two controllers does not function, each car will respond to the registered hall calls independently.
In a duplexing configuration, the controller that assumes dispatching duty is identified by the letter D in the upper left corner of the LCD. The other car is identified by the letter S, in the upper left corner of the LCD. If the upper left-hand corner of the LCD is blank (neither D nor S displayed), the cars are not communicating, and troubleshooting will be required to determine the cause.
Power Phasing
When cars are paired for duplex operation, input power phasing to the two must match.
1. Connect a multimeter, set for AC voltage, between a 2 Bus terminal on one controller and a 2 Bus terminal on the second controller. If the meter reads close to zero (0) volts, the two are in phase. If not:
• Swap two of the L1/L2/L3 inputs on one car and repeat step 1.
5-42 Manual # 42-02-2P25
Motion 4000
PC Board Quick References
PC Board Quick References
This section contains component photographs with call outs, input/outputs, indicators, jumpers, test points and other information.
Table 5.2 Motion 4000 Circuit Boards
Board
HC-CHP
HC-CTL-2
HC-MPU
HC-UIO-2
ICE-COP-2
MC-CPI
MC-LSI
SC-3HN
TC-MPI
Name
CAN Hub and Power Supply Board
Control Board, TSSA
Main Processor Unit Board
Universal Input/Output Board
Car panel interface board
Car Panel Interface Board
Landing System Interface Board
Three Input Serial Hall Call Node Board
Motion Processor Interface
See
5-44
5-46
5-53
5-56
5-63
5-67
5-72
5-73
5-77
Figure 5.1 Motion 4000 PC Boards
CAN
External
CONTROLLER
CAN and 24VDC to other controller boards
Transformer Power Supply
16V 24-28V
HALL
28VDC
3-Input Hall Call Node
14 - 18 VAC in
CAN Hub (HC-CHP)
CAN External
3-Input Hall Call Node
Ethernet B
Ethernet A
Internal Can
LCD
Keyboard
RS232 (x3)
Main Processor (HC-MPU)
CAR
Internal Can
INSPECTION
CONTROLS
Controller (HC-CTL)
Spare Inputs
SP1 - SP10
Spare Inputs are programmed for many key functions. The first ten are on the Controller board. Others are on Universal I/O boards.
Additional MC-CPI or ICE-COP-2
(if used)
COP Signals
CAN External
Internal Can
Car/HW Doors,
Safety strings
Fire, Inspection, Access,
Independent modes;
Door safety inputs
Field Input/Output (HC-UIO)
I/O 1
I/O 16
I/O boards are addressable/configurable using DIP switches. Addresses 0 - 31 are used for discrete call/floor inputs/outputs.
Addresses 32 and above are used as assignable Spare I/O for general field connections.
COP Signals
COP Signals
Car Panel Interface
MC-CPI or ICE-COP-2
24VDC
Power
Supply
COP Signals
24VDC
Landing System I/F
MC-LSI
Internal Can
Rope Gripper
Emergency Terminal Switches
Seismic Devices
CAN 1 / CAN 2
24VDC
Door motion
IN
Door motion
OUT F / R
ELGO
Sensor
Magnetek drive I/F
Torqmax drive I/F
Motion Processor (TC-MPI)
5-43
5
Troubleshooting
HC-CHP CAN Hub and Power Supply Board
This board provides 4-amp power for boards throughout the controller and a central connection point for the Controller Area Network (CAN).
Figure 5.2 HC-CHP CAN Hub and Power Supply Board
J16, J17 External
Network connections
M1:Optional Ethernet connection
J1 - J10: Internal Network connections
J11: AC input
18 Vrms max.
JP2
SW1
J12
PWR ON LED
Test Points
+5V, +3.3V, GND
RST button
CPU ON LED
J15
JP1
J13
TP GND
TP V UNREG
JP3
Connectors
• J1 - J10: Network connections to boards inside the controller cabinet.
• J11: Low voltage AC input - 16V1/16V2, maximum 18Vrms.
• J12: Optional +5Vdc output.
• J13: Serial programming port for microcontroller.
• J15: Interface to external memory.
• J16, J17: External CAN network connections to boards or equipment outside the cabinet.
• M1: Optional Ethernet connection.
Jumpers
• JP1: Internal CAN bus termination resistor.
• JP2: External CAN bus termination resistor.
• JP3: Sets pick-off point for power failure detection. Factory use only.
Default is A= Direct AC monitoring.
Test Points
• +5V: +5Vdc measured between this test point and TP GND.
• +3.5V: +3.3Vdc measured between this test point and TP GND.
• GND: 0V.
• V UNREG: 24V A20% measured between this test point and TP GND.
5-44 Manual # 42-02-2P25
Motion 4000
PC Board Quick References
Indicators
• PWR ON: +5V indicator.
• CPU ON: LED on indicates that the on-board microcontroller is functional.
Switches
• SW1: DIP switch used to set board initialization behavior.
• RST: Microcontroller reset button.
Figure 5.3 Upgrading Motion 4000 Firmware
J16, J17, External Network connections
5
SW1 Switches
Update firmware using SD Card
(see Instruction 42-IS-0176)
Update firmware using EEPROMs
(see Instruction 42-IS-0157)
Insert EEPROM with notch facing this side
SW1 DIP Switch Settings
SW1 DIP Switch Settings
DIP 1 DIP 2 DIP 3
Off Off Off
Description
Normal boot up (bypasses firmware update)
On
On
On
On
On
Off
Updates firmware different from EEPROM or SD card
Forced update (fixes corrupted software)
On = switch left, Off = switch right
DIP 4 Sets the communication baud rate for the External CAN bus
(Off = 125 kbs, On = 250 kbs).
DO NOT change this switch setting.
5-45
Troubleshooting
HC-CTL-2 Control Board
The HC-CTL-2 Control board monitors I/O, performs safety functions and provides front and rear door operation. The HC-CTL-2 board is responsible for Inspection, Fire Service, Landing
System, door lock bypass, lanterns, and gongs.
Figure 5.4 HC-CTL-2 Control Board
5-46 Manual # 42-02-2P25
Motion 4000
PC Board Quick References
HC-CTL-2 Terminal Definitions
Table 5.3 HC-CTL-2 Board Terminals
Connector Terminal
J1
J2
J3
J4
J5
J6
MCE wired at factory.
Not for field connection.
J7
J8
MCE wired at factory.
Not for field connection.
J9
MCE wired at factory.
Not for field connection.
DCB
IND
PHE
DPM
DOL
DCL
DCAB
GS
CAN
FCS
CCB
DOB
CAN
DS
DF
US
UF
BAB1
TAB1
ESC
ABB1
SAFC
SAFH
DCAT
DCMS
DLAB
DCP
DCF
DOF
NUDG
NBZ
FWI
FSLC
FSLL
FRON
OFF
HLD
Description
Board programming, factory only
Board programming, factory only
Board programming, factory only
CAN bus connection from HC-CHP board
Not used for traction control
Not used for traction control
Not used for traction control
Not used for traction control
Bottom access
Top access
In-car stop switch bypass (completes SAFC safety string with switch open)
Safety string, car
Safety string, hoistway
Door contact access top (top access floor door contact “made”)
Door contact middle string (floors between access floors, contacts “made”)
Door lock access bottom (bottom access floor door lock “made”)
Door contact access bottom (bottom access floor door contact “made”)
Gate switch (car gate switch “made”)
CAN bus connection, spare
See description, connector J27
See description, connector J27
See description, connector J27
See description, connector J27
See description, connector J27
See description, connector J27
See description, connector J27
See description, connector J27
See description, connector J27
See description, connector J27
See description, connector J27
See description, connector J27
See description, connector J27
See description, connector J27
See description, connector J27
See description, connector J27
See description, connector J27
See description, connector J27
See description, connector J27
See description, connector J27
5
5-47
Troubleshooting
Table 5.3 HC-CTL-2 Board Terminals
Connector Terminal
J10
MCE wired at factory.
Not for field connection.
J11
MCE wired at factory.
Not for field connection.
J12
J14
ICTD
ICTU
CTEN
INCT
FRS
FRA
ABD
ABU
ATD
ATU
INA
INN
INCP
ICEN
GSR
See description, connector J27
See description, connector J27
See description, connector J27
See description, connector J27
See description, connector J27
See description, connector J27
See description, connector J27
See description, connector J27
See description, connector J27
Description
See description, connector J27
See description, connector J27
See description, connector J27
See description, connector J27
See description, connector J27
Gate switch rear (rear opening car gate switch “made” input)
LIM1
LIM2
LIM3
GS
DCAB
DLAB
DCMS
DCAT
DCABR Door contact access bottom rear (bottom access floor rear door contact “made” input)
DLABR Door lock access bottom rear (bottom access floor rear door lock “made” input)
DLMS Door lock middle string (floors between access floors, contacts “made” input)
DLAT
DZF
DZR
LIM0
Door lock access top (top access floor door lock “made” input)
Front door zone input, discrete landing system connection
Rear door zone input, discrete landing system connection
Used with hydro applications only
Used with hydro applications only
Used with hydro applications only
Used with hydro applications only
Gate switch (car gate switch “made” input)
Door contact access bottom (bottom access floor door contact “made” input)
Door lock access bottom (bottom access floor door lock “made” input)
Door contact middle string (floors between access floors, contacts “made” input)
Door contact access top (top access floor door contact “made” input)
SAFH
SAFC
ESC
SPD0
Safety string, hoistway (input)
Safety string, car (input)
In-car stop switch bypass (completes SAFC safety string with switch open)
Speed bit from LS-EDGE landing system sensor
SPD1
SPD2
Speed bit from LS-EDGE landing system sensor
Speed bit from LS-EDGE landing system sensor
SPOUT1 Programmable spare output #1. Defined on job prints if used.
SPOUT2 Programmable spare output #2. Defined on job prints if used.
SPOUT3 Programmable spare output #3. Defined on job prints if used.
SPOUT4 Programmable spare output #4. Defined on job prints if used.
5-48 Manual # 42-02-2P25
Motion 4000
PC Board Quick References
Table 5.3 HC-CTL-2 Board Terminals
Connector Terminal
J15
MCE wired at factory.
Not for field connection.
J16
MCE wired at factory.
Not for field connection.
J17
1 Ground
Description
DCOM
2
2MV
2L
Digital Common
120 VAC
Provides 120VAC to 2L bus when SAFL and SAFS relays are picked (input).
Provides 120VAC to valves and motor signals when doors are locked and safety string is made up (Output).
DZR
DZF
DLAT
DLMS
See description, connector J12
See description, connector J12
See description, connector J12
See description, connector J12
DLABR See description, connector J12
DCABR See description, connector J12
GSR
SPIN1
See description, connector J12
Programmable spare input #1. Defined on job prints if used.
SPIN2
SPIN3
SPIN4
SPIN5
Programmable spare input #2. Defined on job prints if used.
Programmable spare input #3. Defined on job prints if used.
Programmable spare input #4. Defined on job prints if used.
Programmable spare input #5. Defined on job prints if used.
SPIN6
SPIN7
SPIN8
SPIN9
Programmable spare input #6. Defined on job prints if used.
Programmable spare input #7. Defined on job prints if used.
Programmable spare input #8. Defined on job prints if used.
Programmable spare input #9. Defined on job prints if used.
SPIN10 Programmable spare input #10. Defined on job prints if used.
5
5-49
Troubleshooting
Table 5.3 HC-CTL-2 Board Terminals
CCB
FCS
HLD
OFF
FRON
FSLL
FSLC
FWI
DETS
DCL
DOL
DPM
PHE
IND
DCB
DOB
NBZ
NUDG
DOF
DCF
DCP
INCP
INN
INA
ATU
ATD
ABU
ABD
UETS
FRES
FRA
FRS
INCT
CTEN
ICTU
ICTD
ICEN
Connector Terminal
J27 FRSA
FRSM
Description
Fire Service Alternate Initiating Device, machine room (input)
Fire Service Main Initiating Device, all other hoistway fire service initiating devices (input)
Fire Service Reset (input)
Main Landing Smoke Sensor (input)
Smoke/Fire Sensors for all landing that are not main (input)
Car Top Inspection
Car top enable button input
Car top inspection Up button
Car top inspection Down button
In car inspection enable button input
In car inspection switch input, INSP position
COP Access enable switch, NORM input
COP Access enable switch, ACC input
Top access switch, Up position
Top access switch, Down position
Bottom access switch, Up position
Bottom access switch, Down position
Up emergency terminal switch input
Down emergency terminal switch input
Door close limit input
Door open limit input
Door position monitor switch input
Photo eye, infrared detector input
Independent service switch input
Door close button input
Door open button input
Fire service car call cancel button input
Phase II Fire Service Operation On (On position, 3-position fire service switch)
Phase II Fire Service Operation Hold (Hold position, 3-position fire service switch)
Phase II Fire Service Operation Off (Off position, 3-position fire service switch)
Fire Recall Operation On (input)
Fire Service Indicator for Lobby (output)
C.O.P. Fire Service Light (output)
Fire Service Buzzer (output)
Nudging Buzzer (output)
Nudging enable output
Door open function output, initiates door opening at landing
Door close function output, initiates door closing at landing
Door close power, enables door closing power application while car is running
HC-CTL-2 Board LED Indicators
Indicator LEDs for board connections light when the corresponding input or output is active.
5-50 Manual # 42-02-2P25
Motion 4000
PC Board Quick References
HC-CTL-2 Board Jumpers, Fuses, Testpoints, and Switches
Table 5.4 HC-CTL-2 Board Jumpers
Jumper
JP1
JP2
Description
IC U2 program source, factory use only. Default is No Jumper.
Fault Bypass, 2 position. A = Bypass active; C = Bypass off. C position is default.
Table 5.5 HC-CTL-2 Board Fuses
Fuse
F1
F2
F3
F4
Description
Fused 2 Bus (120VAC) testpoint TPF2
Fused 1 Bus (ground) testpoint TPF1
Fuse, unregulated voltage, connector J7, pin 2
Fuse, ESC terminal (in-car stop switch bypass)
5
Table 5.6 HC-CTL-2 Board Test Points
Test Point Description
TP19
TP20
TP21
TP22
TP23
TP24
TP1
TP2
TP3
TP4
TP5
TP6
TP7
TP8
DIA1A, SPA processor factory diagnostic
DIA2A, SPA processor factory diagnostic
DIA3A, SPA processor factory diagnostic
DIA4A, SPA processor factory diagnostic
DIA4B, SPB processor factory diagnostic
DIA1B, SPB processor factory diagnostic
DIA2B, SPB processor factory diagnostic
DIA3B, SPB processor factory diagnostic
TP9 +5V, on-board 5V regulator output for digital circuits, associated LED DS105, 5V
TP10, 11, 12 Ground
TP13
TP14
Ground
2L bus, 120VAC. 2L terminal voltage. PM, BR, FBS contactor logic.
TP15
TP16
TP17
TP18
MSAFS1, SAFS relay monitor.
SAFSB, output SAFS relay coil
SAFSA, input SAFS relay coil
MCSB, in-car stop switch bypass voltage monitor
TP25
SAFLA, input SAFL relay coil
SAFLB, output SAFL relay coil
MRUP, machine room inspection switch Up direction
MRDN, machine room inspection switch Down direction
MDZLV, monitors output of MDZLV (door zone level) solid state relay U23
MABG, monitors output of ABG (access bypass gate) solid state relay U25. MABG must always be in the opposite state of MABGR.
MGB, monitors status of car door bypass switch, front door, pole 4, high = bypass off
5-51
Troubleshooting
Table 5.6 HC-CTL-2 Board Test Points
Test Point
TP26
TP27
TP28
TP29
TP30
TP31
TP32
TP33
TP34
TP35
TP36
TP39
TP40
Description
MGBR, monitors status of car door bypass switch, rear door, pole 1, high = bypass off
MHDB, monitors status of hoistway door bypass switch, pole 4, high = bypass off
MHDBR, monitors status of hoistway door bypass switch, pole 1, high = bypass off
MABT, monitors status of access bypass top solid state relay ABTP U30
MABB, monitors status of access bypass bottom solid state relay ABB, U32
MTAB, monitoring for Top Access Bypass solid state relay U33. If the TAB relay is ON, the
RTAB (Rear Top Access Bypass) input will be OFF. MTAB should always be the opposite of
RTAB otherwise, the TAB redundancy fault is logged and the elevator shuts down.
MBAB, monitoring for BAB, Bottom Access Bypass, solid state relay U34.If the BAB relay is
ON, the RBAB, Rear Bottom Access Bypass) input will be OFF. RBAB should always be the opposite of BAB otherwise, the BAB redundancy fault is logged and the elevator shuts down.
MABGR, monitoring for ABGR, Access Bypass Gate Rear, solid state relay U35. MABGR must always be in the opposite state from MABG.
MDLR, monitoring for DLR, door locks rear, solid state relay U36. High when rear door locks are made.
MGSR, monitoring for GSR, gate string rear, solid state relay U37. High when rear car gate string is made.
MGS, monitoring for GS, gate string, solid state relay U38. High when car gate string is made.
+3.3V logic voltage
V_unreg, pre-regulation board voltage supply. Nominally about 16 - 18 volts.
Table 5.7 HC-CTL-2 Board Switches
Switch
S1
S2
S3
S4
S5
S6
SW1
SW2
SW3
SW4
Description
SPA U3 reset
SPB processor U7 reset
(Run) Enable button, Inspection operation
Test/Pretest switch. Please refer to “Test/Pretest Modes” on page 1-15
.
Board fault reset
PLD U2 reset
Inspection/Normal operation switch
Up/Down Inspection direction
Car Door Bypass
Hoistway Door Bypass
5-52 Manual # 42-02-2P25
Motion 4000
PC Board Quick References
HC-MPU Main Processor Board
The HC-MPU board performs control data processing and is responsible for:
• Car operation
• Car communication
• Programming and diagnostics
• Redundancy cycle testing
• System software validation
• Duplexing
Figure 5.5 HC-MPU Main Processor Unit Board
M1: Ethernet Port A
J10: Ethernet Port B
SW1
JP5
J6: CPU B Debug
J7: RS232 Port B
J3: RS232 Port A
S1: RSTA
LCD Display
JP7
J2: Keyboard Port
J8: CPU-B JTAG
J9: 16VAC input
TP +25V
5
TP +5V
JP1
TP GND
JP4 TP GND
J1 S6
JP2
J5: Internal CAN connection
S4 SW2 SW3 S5 S3
CPU A ON LED
S2: RSTB
JP6
CPU B ON LED
Indicators
JP3
TP +3.3V
J4:External CAN Port
Information displayed on the LCD depends F1 - F8 settings:
• All switches down: Diagnostics mode - scrolling status message, car position, CPU internal memory content.
• Program mode - F1 switch up, others down. Parameter entry. Must be in Inspection.
• External Memory (RAM) - F2 switch up, others down. Review of RAM contents.
• System mode - F3 switch up, others down. Parameter entry for security, load weigher, and other system level functions. System does not have to be in Inspection mode.
• Serial Fixtures - F4 switch up, others down.
• Date/Time, motion diagnostics - F5 switch up, others down.
• Positioning system - F6 switch up, others down.
• Motion parameter Adjust - F7 up, others down. Traction parameters.
• Status - F8 switch up, others down. Display software version, floor eligibility, load as a percentage of full load.
5-53
Troubleshooting
Table 5.8 HC-MPU Board Jumpers
Jumper
JP1
JP2
JP3
JP4
JP5
JP6
JP7
Setting
A
-
Configuration dependent
Configuration dependent
A
Open
-
Description
LCD voltage select. A = 5V, B = 3.3V
CPU A reset. No jumper provided, only required for testing
External CAN network termination
Internal CAN network termination
Ethernet Port B (optional)
JTAG Debug Jumper. Closed = debug mode.
CPU B reset. No jumper provided, only required for testing.
Table 5.9 HC-MPU Board Switches
Switches
S1
S2
S3
S4
S5
S6
SW1
SW2
SW3
Description
RSTA: Reset CPU A
RSTB: Reset CPU B
“-” minus push button - decrement setting
“S” push button - select
“+” plus push button - increment setting
“N” push button - next
Port Selection: RS232 Port A / Ethernet Port A
DIP Function switches F5 through F8
DIP Function switches F1 though F4
Table 5.10 HC-MPU Board Indicators
Indicators Description
CPU A ON CPU A is executing its program
CPU B ON CPU B is executing its program
LED2 Reserved
LED1
FAULT
CPU ON
MLT
Reserved
A fault has been detected.
All processors are fully functional.
Motor/Valve Limit Timer: The motor/valve limit timer has elapsed.
TOS
FIRE
INSP
IND
HS
DLK
SAF ON
Timed Out of Service: The TOS timer has elapsed and the car is out of service.
Fire Service: The car is on fire service operation.
Inspection: The car is on inspection operation.
Independent Service: The car is on independent service.
High Speed: The car is running at high speed.
Doors Locked: The door lock contacts are made.
Safety On: The safety circuit is made.
5-54 Manual # 42-02-2P25
Motion 4000
PC Board Quick References
Table 5.11 HC-MPU Board Test Points
Test Points
GND
+3.3V
+5V
+25V
Description
0V
+3.3 Vdc measured between this test point and TP GND.
+5 Vdc measured between this test point and TP GND.
Unregulated 25Vdc (+/- 2V) from the HC-CHP board
Table 5.12 HC-MPU Board Terminals
Connector
J1
J2
J3
J4
J5
J6
J7
J8
J9
J10
M1
Description
Used to program CPU A. IDC connector.
Keyboard Port. Six-pin DIN connector.
RS-232 Port A. Nine-pin D-sub connector.
External CAN Port. Three-pin Weidmuller connector (CAN H, CAN L, SHLD). Signal for CAN connections outside the controller cabinet.
Internal CAN Port. RJ12 connector/cable to the HC-CHP CAN Hub / Power Supply board.
CPU B Debug Port. Nine-pin D-sub connector.
RS-232 Port B. Nine-pin D-sub connector.
Used to program CPU B. Fourteen-pin header connector.
Low voltage AC input (16V). Two-pin IDC connector.
Optional Ethernet Port B. RJ45 connector.
Ethernet Port A. Serial to ethernet conversion device.
HC-MPU Battery
The battery sustains volatile information when the power is off. Controller operating parameters are stored in battery backed memory and will not be affected by battery removal as long as power is applied to the controller. The battery provides 3.3 VDC. If battery voltage falls below
2.2 VDC, the battery should be replaced. If battery replacement is part of a regular maintenance schedule, we recommend it be replaced every two years.
Table 5.13 HC-MPU Battery
Sanyo
Type
CR2032, 3V, Mn D2-Li cell
Original Specification
Replacement:
1. Place the car on Inspection by placing the MODE switch on the HC-CTL (2) board in the
INSP position. DO NOT remove power to the controller as this will cause the HC-MPU parameters to be reset to default values.
2. On the HC-MPU board, use a non-conductive flat tool to lift the battery tab and slide the old battery out of the battery holder.
3. Install a new battery on the HC-MPU board.
4. Make a brief check of F1 parameters to verify that they have not become corrupted.
5. Return the car to service by placing the MODE switch on the HC-CTL (2) board in the
NORM position.
5-55
5
Troubleshooting
HC-UIO-2 Universal Input/Output Board
Depending upon the software installed, HC-UIO boards may be used for programmable inputs and outputs (16 per board), car and hall calls, door operator interface, or dispatching. In addition to being backwards compatible with the HC-UIO board, the HC-UIO-2 also contains the following enhancements:
1. On-board pull-up resistors can be used by installing the jumpers JP2 through JP17 in the I/O position. This will eliminate glowing of some LED fixtures when they are off.
The PS1 and PS2 terminals allow different voltages to be used.
2. Different circuitry allows button presses to be detected even when long wires or corroded button contacts are used.
3. Output short circuit protection is improved, reducing the need for board replacement.
Danger
If PS1 or PS2 is connected to 120V, 120V may also be present across the large resistors on the board and on jumpers JP2 through JP17! The resistors may also be physically hot. Use caution.
Figure 5.6 HC-UIO-2 Board
PS1 and PS2 are independent (hot lead only) supply inputs for the large pull-up resistors when the associated jumper (JP2 - JP17) is in the I/O position. PS1 supplies I/O 1 - I/O 8.
PS2 supplies I/O 9 through I/O16.
5-56 Manual # 42-02-2P25
JP1, CAN Termination
JP18, Voltage Reference. A=External, B=24V (Internal)
Motion 4000
PC Board Quick References
Figure 5.7 Typical Input and Output Connection (Board ID 0 to 15)
PS1 and PS2 are used to provide input pull-up
ONLY when I/O Jumpers are set to
I/O
+
-
Power Supply
+Vc
When using a board connection in IO mode, connect the associated PS input to the same voltage used to power the fixture.
JP10 - JP17
I/O 9 - I/O 16
JP2 - JP9
I/O 1 - I/O 8
IN
JP2
I/O
PS2
PS1
IO 9
IO 8
IO 7
IO 6
IO 5
IO 4
IO 3
IO 2
IO 1
IO 16
IO 15
IO 14
IO 13
IO 12
IO 11
IO 10
+Vn
+
-
Power Supply
+Vn
Typical Fixture
Connection
PS1 and PS2 can be connected to separate voltages, depending on the job requirements.
5
Figure 5.8 Typical Input or Output Connection (Board ID 32 to 36)
< 500 mA continuous current
Load
+ Power Supply
+Vc
AC or DC
-
JP10 - JP17
I/O 9 - I/O 16
IN
JP17
No jumper
I/O
JP2 - JP9
I/O 1 - I/O 8
IN
JP2
PS2
PS1
I/O
IO 8
IO 7
IO 6
IO 5
IO 4
IO 3
IO 2
IO 1
IO 16
IO 15
IO 14
IO 13
IO 12
IO 11
IO 10
IO 9
Output
Input
+Vn
+
-
Power Supply
+Vn
AC or DC
Typical switch or other wired input
5-57
Troubleshooting
Switches
Switches are ONLY checked by the board processor on start-up. Press the processor RESET button after any change to switches.
• DIP SW2:
• Switches 1 through 6 = Board ID
• Switches 7 & 8 = Baud rate
• Switch 9 = Input levels
• Sw1: RST - Processor reset
Jumpers
• JP1: Internal CAN Network Termination
• JP2 - JP9: Pull Inputs 1 - 8 up to voltage at PS1 when set to I/O
• JP10 - JP17: Pull Inputs 9 - 16 up to voltage at PS2 when set to I/O
• JP18: Selects voltage reference
• A = External power supplied by J3 (default)
• B = 24Vdc power supplied by CAN bus
Danger
Line voltage can be present on jumpers. Move only with power off.
Test Points
• GND: Digital Ground - 0 V
• +5V: +5 Vdc measured between this test point and TP GND.
• 1: 1 Bus (common)
Indicators
• CPU ON: The micro controller is executing its program.
• IO1 - IO16: Indicates the state of the input or output, active or inactive. Blinking indicates overload condition (resets automatically after 5 seconds/processor reset/ or power cycle).
See “Troubleshooting” on page 4.
Terminals
• J1: Used to program the micro controller (IDC connector).
• J2: Internal CAN signal and power (RJ12 connector).
• J3: 1 bus and 2 bus. Weidmuller connector.
• J4: Pull up voltages
• J5: IO1 - IO16
5-58 Manual # 42-02-2P25
Motion 4000
PC Board Quick References
HC-UIO-2 Switches 7, 8 and 9 Settings
On the HC-UIO-2 Board switches 7 and 8 set the baud rate at which the CAN bus communicates with this board.
Table 5.14 HC-UIO-2 Board Switches 7 and 8
Sw 7
OFF
ON
OFF
Sw 8
OFF
OFF
ON
Baud Rate Description
500 kbps For boards inside the controller, RJ12 cable from J2 on HC-UIO board to
HC-CHP board Internal Network J1 through J10.
250 kbps For boards on the cartop, RJ12 cable from J2 on HC-UIO board to MC-LSI board LAN connectors. Caution: Do not connect to J3 on the MC-LSI
(Landing System) board.
125 kbps Future use
On the HC-UIO-2 Board switch 9 sets the activation threshold for inputs IO1 through IO16..
Table 5.15 HC-UIO-2 Board Switch 9 for I/O Boards
Sw 9
OFF
ON
Description
Sets Input activation threshold to 18 Volts ac or dc
Sets Input activation threshold to 55 to 65 Volts ac or dc
Table 5.16 HC-UIO-2 Board Switch 9 for Call Boards
Sw 9
OFF
ON
Description
Sets Input activation threshold to 0.6 Volts ac or dc
Sets Input activation threshold to 0.2 Volts ac or dc
HC-UIO-2 Used for Calls
When HC-UIO-2 boards are used for hall or car calls, the brightness of the LEDs associated with inputs and outputs has significance.
Level o - LED Off
• The input is not active and the output is not latched on.
Level 1 - LED medium brightness
• The input is not active and the output is latched on.
Level 2 - LED full brightness
• The input is active and the output may or may not be latched on.
LED flashing
• Maximum continuous current draw exceeded (overload or short detected).
Hospital Emergency Operation I/O
I/O 1 through I/O 4 on UIO-2 Board #16 are used for hospital emergency operation connections
HEO, HWI, HSEL, and HOSPH2 respectively.
5
5-59
Troubleshooting
Troubleshooting
• I/O LED is Blinking:
• Low impedance or largely reactive load (in-rush current surge >3A or steady state
>300mA)
• Output connected to line source with no series load
• Input board addressed as output board (switches are only checked on boot up; reset processor after any switch change)
• JP-18 not installed
• 1 bus or 2 bus not connected at J3
• 1 bus floating at J3
• Output transistor damaged
• Car or Hall Call Fixture Glowing in OFF State:
• I/O jumpers set to Input mode (pull down)
• JP-18 set in B mode
• Fixture voltages not connected to PS1 and PS2 (no voltage provided to pull up)
• Duplex Operation: 120VAC on controller 1 out of phase with controller 2.
• CPU ON Light Extinguished:
• CAN/Power cable not connected
• No software on board (repeat boot loading)
• Button press not seen by I/O call board:
• Threshold recognition SW9 set for higher voltage
• Voltage greater than 1VDC at I/O terminal during button press
• I/O LED ON (when it should not be)
• PS1 or PS2 terminal not connected (or floating)
• Output transistor damaged
• Duplex Operation: -2 board connected to Rev 2 or 4 board and DIP switch 9 not set.
(Set switch 9 on -2 board.)
5-60 Manual # 42-02-2P25
Motion 4000
PC Board Quick References
Call Inputs and Outputs
Table 5.17 HC-UIO-2 Board Call Assignments
Board
ID
26
27
28
29
30
31
22
23
24
25
18
19
20
21
14
15
16
17
10
11
12
13
06
07
08
09
00
01
02
03
04
05
Switch Setting
1 2 3 4 5 6
Off Off Off Off Off Off
On Off Off Off Off Off
Off On Off Off Off Off
On On Off Off Off Off
Off Off On Off Off Off
On Off On Off Off Off
Off On On Off Off Off
On On On Off Off Off
Off Off Off On Off Off
On Off Off On Off Off
Off On Off On Off Off
On On Off On Off Off
Off Off On On Off Off
On Off On On Off Off
Off On On On Off Off
On On On On Off Off
Off Off Off Off On Off
On Off Off Off On Off
Off On Off Off On Off
On On Off Off On Off
Off Off On Off On Off
On Off On Off On Off
Off On On Off On Off
On On On Off On Off
Off Off Off On On Off
On Off Off On On Off
Off On Off On On Off
On On Off On On Off
Off Off On On On Off
On Off On On On Off
Off On On On On Off
On On On On On Off
IO 1 to IO 16
HC-UIO-2 boards numbered 00 through 31 are used for call related IO.
The associated switch setting is shown to the left. Terminal assignments, beginning with terminal IO 1 through IO 16 on board 00, followed by terminal IO 1 through IO 16 on board 01, etc., are made in the following order:
nn = TOP LANDING SERVED
• PIs PI1 - PI(nn)
• Front car calls
• Rear car calls
101 - 1(nn)
101R - 1(nn)R
• Front down hall calls 502 - 5(nn)
• Front up hall calls 601 - 6(nn-1)
• Rear down hall calls 502R - 5(nn)R
• Rear up hall calls 601R - 6(nn-1)R
HC-UIO-2board terminal assignments are determined by the settings of the following BASIC FEATURE MENU :
• TOP LANDING SERVED?
• HC-RDR BOARD ON THIS CAR?
• CAR SERVES FRNT/FLR 1 (- 32)?
• CAR SERVES REAR/FLR 1 (- 32)?
And also:
• DISCRETE PI’S ON UIO?
• DEDICATED PI BOARD? (allows first one or two UIO boards to be dedicated to PI’s alone)
• SERIAL COP BOARD HC-CPI?
The status of these terminals (On or Off) can be determined by observing the indicators on the HC-UIO-2 boards.
5
5-61
Troubleshooting
Spare Inputs and Outputs
The first ten Spare Inputs (SP1 through SP10) are assigned to terminals SPIN1 through SPIN10 on the HC-CTL board (connectors J6 and J10). The first four Spare Outputs (OUT1 through
OUT4) are assigned to terminals 1 through 4 (J15) on the HC-CTL board. The remainder of the
Spare Inputs and Outputs are assigned to HC-UIO-2 boards numbered 32 through 36 as shown in the table below.
Table 5.18 HC-UIO-2 Spare Input / Output Assignments
Board
ID
SW1 Setting
1 2 3 4 5 6
IO Terminals
1 2 3 4 5 6 7 8
IO Terminals
9 10 11 12 13 14 15 16
58
59
60
61
54
55
56
57
62
63
50
51
52
53
46
47
48
49
40
41
42
43
44
45
36
37
38
39
32
33
Off Off Off Off Off On SP11 SP12 SP13 SP14 SP15 SP16 SP17 SP18 OUT5 OUT6 OUT7 OUT8 OUT9 OUT10 OUT11 OUT12
On Off Off Off Off On SP19 SP20 SP21 SP22 SP23 SP24 SP25 SP26 OUT13 OUT14 OUT15 OUT16 OUT17 OUT18 OUT19 OUT20
*34 Off On Off Off Off On SP27 SP28 SP29 SP30 SP31 SP32 SP33 SP34 OUT21 OUT22 OUT23 OUT24 OUT25 OUT26 OUT27 OUT28
*35 On On Off Off Off On SP35 SP36 SP37 SP38 SP39 SP40 SP41 SP42 OUT29 OUT30 OUT31 OUT32 OUT33 OUT34 OUT35 OUT36
Off Off On Off Off On SP43 SP44 SP45 SP46 SP47 SP48 SP49 SP50 OUT37 OUT38 OUT39 OUT40 OUT41 OUT42 OUT43 OUT44
On Off On Off Off On
Off On On Off Off On
On On On Off Off On
Dedicated Card Reader Inputs Dedicated Card Reader Inputs
Off Off Off On Off On
On Off Off On Off On
Off On Off On Off On
On On Off On Off On
Off Off On On Off On
On Off On On Off On
Off On On On Off On
On On On On Off On
Off Off Off Off On On
On Off Off Off On On
Off On Off Off On On
On On Off Off On On
Off Off On Off On On
On Off On Off On On
Off On On Off On On
On On On Off On On
Off Off Off On On On
On Off Off On On On
Off On Off On On On
On On Off On On On
Off Off On On On On
On Off On On On On
Off On On On On On
On On On On On On
* Addresses 34 and 35 are used on the car top, where the CAN baud rate must be 250k.
HC-UIO Rev 2 will automatically configure the CAN port to communicate at 250k baud.
HC-UIO Rev 4 - refer to Table 1 to set switches 7 and 8 to communicate at 250k baud.
HC-UIO-2 - refer to Table 1 to set switches 7 and 8 to communicate at 250k baud.
5-62 Manual # 42-02-2P25
Motion 4000
PC Board Quick References
ICE-COP-2 Car Panel Interface Board
The ICE-COP-2 board, mounted in the car operating panel, converts the discrete closures from the panel buttons and switches to data on the CAN serial bus and passes it through the MC-LSI
Landing System Interface board on the cartop, up the traveler to the car controller. Additional
ICE-COP-2 boards are used to accommodate rear doors or installations with many floors, COP buttons, and lamps.
Spare assignable inputs to and outputs from ICE-COP-2 boards are available depending upon system configuration.
• F1 menu, Serial COP Board Type = ICE-COP-2: ICE-COP-2 board assignable inputs show up in the Spare Inputs menu as COP FX (front panel board) I1 - I7; COP Rx (rear panel board) I1 - I7. Spare outputs (Spare Outputs menu) will be prefaced with an ‘O’ for Output.
If the job has ICE-COP-2 boards, unused spare inputs to and outputs from these boards must be set to NOT USED. If controller software is upgraded in the field, it is very important to check programmable ICE-COP-2 board inputs and outputs and verify unused connections are set to
NOT USED.
Please refer to “Spare Inputs Menu” on page 4-27.
5
Caution
Spare inputs and outputs used on the
ICE-COP-2
boards must be 24VDC, not to exceed 6 Watts.
Installation Instructions
1. Turn the power off at the main disconnect.
2. Mount the ICE-COP-2 board(s) inside the COP using the supplied hardware and providing sufficient clearance for the components.
Caution
Do not replace C-RJ11-CAN-15 cables between the
ICE-COP-2
and MC-LSI with RJ11 cables purchased locally. These cables MUST be replaced with C-RJ11-CAN-15 supplied by MCE. For a replacement cable, please contact MCE technical support.
3. Refer to the prints for the job to wire the ICE-COP-2 board.
Caution
This system is designed for 24 VDC circuits only! Do not connect 120 VAC or DC to any
terminal on the ICE-COP-2 board. Connect only the 24V power from connector J34
(24V CUSTOMER LOAD SUPPLY) to the load.
5-63
Troubleshooting
Normal Operation
During normal operation, I/O LEDs will be lighted when the associated I/O is active (dimmer when the output is active; brighter when the input is active). The SPA processor LED will be continuously lighted. If I/O LEDs remain in a static condition or the SPA processor LED is not continuously on:
• Press the RST button on the board. The I/O LEDs will all cycle and the board will resume operation.
ICE-COP-2 Board Details
• 24V Inputs Only: Typical circuit for terminals I1 through I16.
• 24V Outputs Only: Typical circuit for terminals O1 through O16 .
• 24V Inputs/Outputs Only: Typical circuit for terminals
IO1 through IO16.
Call Button / Lamp
S2 Switches Eight-position DIP switch S2 allows a unique address to be set for each
COP board, places the board in CAN or iControl communication mode, sets an input threshold, and determines the CAN baud rate (when CAN is enabled).
• RS485 or CAN Communication
• For Motion controls, the board must be set to use CAN communication.
• CAN Enable: Verify/set switch 8 to the ON position.
• Motion Input Threshold Detection
On COP-2 boards with software version 1.1 or later, the input threshold level may be set to
900 or 700mV using DIP switch rocker 5.
• Board revision X2-1 or greater: Recommended, rocker 5 OFF: 900mV (default)
• Board revision X2-0: Recommended, rocker 5 ON: 700mV
• Motion Board Addressing
For Motion controls, each COP-2 board used must have a unique address.
• Addressing - switches 1, 2, and 3:
S2
Front COP Boards Rear COP Boards
Board SW1
1
Off
2
3
On
Off
SW2
Off
Off
On
SW3
Off
Off
Off
SW1
Off
On
Off
SW2
Off
Off
On
SW3
On
On
On
5-64 Manual # 42-02-2P25
Motion 4000
PC Board Quick References
• Motion CAN Baud Rate
• Switch 7 OFF: 250k (default)
• Switch 7 ON: 500k
• Motion Unused Switches
• Switches 4 and 6 are unused and should be left in the OFF position.
• 24V Power: The 24V power supply from the cartop box must be connected to the 24V IN connector J35 on the first ICE-COP-2 board. If additional boards are used, they are con-
nected to 24V as shown in “ICE-COP-2 Board Interconnect” on page 5-65. Load connec-
tions (power source for buttons and switches in the car panel) can be made to any of the boards at the 24V CUSTOMER LOAD SUPPY connector as long as load current at any one board is not more than 4A.
• CAN Bus termination: Jumper JP1 terminates the CAN bus in the correct impedance for CAN signal transmission.
• If more than one COP board is used, ONLY the last board in the CAN string should have jumper JP1 plugged in. (If there is only one COP board, it must have JP1 plugged in.)
Figure 5.9 ICE-COP-2 Board Interconnect
LSI Board
On Cartop
COP Board #1
Address: 0 (S2)
24V LOAD
J34
24V/Com for load connection
COP Board #2
Address: 1 (S2)
24V LOAD
J34
24V/Com for load connection
COP Board #3
Address: 2 (S2)
24V LOAD
J34
24V/Com for load connection
24V
Power
Supply
J31
C-RJ11-CAN-xx
24V IN
J35
+V
Com
+V
Com
JP1
J32 J31
24V IN
J35
+V
Com
+V
Com
JP1
J32 J31
24V IN
J35
+V
Com
+V
Com
JP1
J32
JP1 on last board only
• Factory I/O Assignment Per ICE-COP-2: For a list of factory I/O assignments, see
Appendix page A-31 .
5
5-65
Troubleshooting
ICE-COP-2 Serial Car Operating Panel Board
4-pin “universal” inputs may be used instead of screw terminals if desired.
Not used for
Motion controllers
I/O connections
24 VDC
6W max.
Test points,+5v
Reset button
8-position DIP switch package
SPA processor OK
Test point,+3.3v
To previous board or LSI on cartop
(RJ11)
Not used for
Motion controllers
Board power input. See prints.
Test point COM, GND
+24V
Caution
This system is designed for 24 VDC circuits only. Connecting 120VAC or DC will open the input fuses.
Connection Example:
Universal 4-pin inputs
COM
+24V SIGNAL
COM
CAN to next
ICE-COP-2
+24VDC power for COP buttons/ indicators
CAR CALL
BUTTON
5-66 Manual # 42-02-2P25
Motion 4000
PC Board Quick References
MC-CPI Car Panel Interface Board
The MC-CPI board, mounted in the car operating panel, converts the discrete closures from the panel buttons and switches to data on the CAN serial bus and passes it through the MC-LSI
Landing System Interface board on the cartop, up the traveler to the car controller. Additional
MC-CPI boards are used to accommodate rear doors or installations with many floors, COP buttons, and lamps.
Spare assignable inputs to and outputs from CPI boards are available depending upon system configuration, front control panel only or front and rear control panels.
• F1 menu, Serial COP Board HC-CPI = YES and F1, HC-RDR Board on this Car = NO: CPI board assignable inputs show up in the Spare Inputs menu as CPI F (front panel board)
I10 - I16; CPI FX (front panel extender board) I1 - I7. Spare outputs (Spare Outputs menu) will be prefaced with an ‘O’ for Output.
• F1 menu, Serial COP Board HC-CPI = YES and F1, HC-RDR Board on this Car = YES: CPI board assignable inputs show up in the Spare Inputs menu as CPI F (front panel board)
I10 - I16 and CPI-R (rear panel board) I10 - I16. Spare outputs (Spare Outputs menu) will be prefaced with an ‘O’ for Output.
If the job has MC-CPI boards, unused spare inputs to and outputs from these boards must be set to NOT USED. If controller software is upgraded in the field, it is very important to check programmable CPI board inputs and outputs and verify unused connections are set to
NOTUSED.
Please refer to “Spare Inputs Menu” on page 4-27.
5
Caution
Spare inputs and outputs used on the CPI boards must be 24VDC, not to exceed 6 Watts.
Installation Instructions
1. Turn the power off at the main disconnect.
2. Mount the MC-CPI board(s) inside the COP using the supplied hardware and providing sufficient clearance for the components.
Caution
Do not replace C-RJ11-CAN-15 cables between the MC-CPI and MC-LSI with RJ11 cables purchased locally. These cables MUST be replaced with C-RJ11-CAN-15 supplied by MCE. For a replacement cable, please contact MCE technical support.
3. Refer to the prints for the job to wire the MC-CPI board. An example of a typical wiring print is included in this instruction (
Please refer to “Example: MC-CPI Wiring” on page 5-70
and Please refer to “MC-CPI Serial Car Operating Panel Board” on page 5-68 ).
Caution
This system is designed for 24 VDC circuits only! Do not connect 120 VAC or DC to any
terminal on the MC-CPI board. Connect only the 24V power from connector J6 (24V
CUSTOMER LOAD SUPPLY) to the load. ( Please refer to “MC-CPI Board Details” on page 5-69
and
Please refer to “Example: MC-CPI Wiring” on page 5-70 ).
5-67
Troubleshooting
Figure 5.10 MC-CPI Serial Car Operating Panel Board
Inputs only
24 VDC max.
6W max.
I/O only
24 VDC max.
6W max.
SW1 Board Address
Reset button
SPA ON indicator
Outputs only
24 VDC max.
6W max.
From Power
Supply - J5
+24VDC in
COM
+24VDC
COM
To next board - J10
To MC-LSI board in
Cartop box or
MC-CPI board - J2
+24VDC
COM
J6 - Customer
Load Supply
J3 - To next MC-
CPI board (RJ11)
JP1 - Bus termination on last board
Caution
This system is designed for 24 VDC circuits maximum. Do not connect 120VAC or DC to any terminal on this board at any time.
5-68 Manual # 42-02-2P25
Motion 4000
PC Board Quick References
MC-CPI Board Details
• 24V Inputs Only: Typical circuit for terminals
I1 through I16.
• 24V Outputs Only: Typical circuit for terminals
O1 through O16
.
5
• 24V Inputs/Outputs Only: Typical circuit for terminals
IO1 through IO16.
Call Button / Lamp
• Board address switches: Four-position DIP switch SW1 provides a unique address for each CPI board (you should never have two CPI boards with the same SW1 setting).
DIP 1
Front COP Boards
Board SW1
1
Off
2
3
4
On
Off
On
SW2
Off
Off
On
On
SW3
Off
Off
Off
Off
SW4
Off
Off
Off
Off
Rear COP Boards
SW1
Off
On
Off
On
SW2
Off
Off
On
On
SW3
On
On
On
On
SW4
Off
Off
Off
Off
LSI Board
On Cartop
• 24V Power: The 24V power supply from the cartop box must be connected to the 24V IN connector on the first MC-CPI board. If additional boards are used, they are connected to
24V as shown below. Load connections (power source for buttons and switches in the car panel) can be made to any of the boards at the 24V CUSTOMER LOAD SUPPY connector as long as load current at any one board is not more than 4A.
• CAN Bus termination: Jumper JP1 terminates the CAN bus in the correct impedance for CAN signal transmission.
• If more than one CPI board is used, ONLY the last board in the CAN string should have jumper JP1 plugged in. (If there is only one CPI board, it must have JP1 plugged in.)
CPI Board #1
Address: 0 (SW1)
24V IN
J5
24V LOAD
J6
J10
NEXT BOARD
J2
J3
24V for load connection
CPI Board #2
Address: 1 (SW1)
24V IN
J5
24V LOAD
J6
J10
NEXT BOARD
J2 J3
24V for load connection
CPI Board #3
Address: 2 (SW1)
24V IN
J5
24V LOAD
J6
J10
NEXT BOARD
J2 J3
C-RJ11-CAN-xx
24V for load connection
JP1 JP1 JP1
24V
Power
Supply
JP1 on last board only
5-69
Troubleshooting
Figure 5.11 Example: MC-CPI Wiring
5-70 Manual # 42-02-2P25
Motion 4000
PC Board Quick References
Before Applying Power
Prior to applying power to the MC-CPI board(s):
1. Disconnect all terminal connectors from the MC-CPI boards (I/O connections, internal network and power connections (24V and COM terminals).
2. Apply power to the system.
3. Using a multimeter, check each of the wires to be connected to the MC-CPI boards as follows:
• Input circuits (switches, buttons, dry contacts): Using the VDC setting referenced to 1 bus (common), probe each input circuit. The reading should be either
24VDC or floating.
• Output circuits (indicators, buzzers, chimes): Using the VDC setting referenced to 1bus (common), probe each output circuit. The voltage reading should be approximately 24VDC.
5
Caution
This system is designed for 24 VDC circuits only! Do not connect 120 VAC or DC to any
terminal on the MC-CPI board. Connect only the 24V power from connector J6 (24V
CUSTOMER LOAD SUPPLY) to the load (
Please refer to “MC-CPI Board Details” on page 5-
69
and
Please refer to “Example: MC-CPI Wiring” on page 5-70
).
4. Power down the system.
5. Install the C-RJ11-CAN cable from J2 (Internal Network) on the MC-CPI board to the
MC-LSI (Landing System Interface board) in the cartop box.
6. Install the MC-CPI board I/O connections (I/O terminals).
7. Install the MC-CPI board power connections (24V and COM terminals).
Caution
To avoid damage to the MC-CPI boards, the system must be powered down before connecting and disconnecting the MC-CPI board power connections (unplugging and plugging in the 24V and COM terminals).
8. Apply power to the system and verify that:
• The MC-CPI board SPA indicator is ON (green).
• The relay closes and supplies 24VDC to the 24V CUSTOMER LOAD SUPPLY terminals.
5-71
Troubleshooting
MC-LSI Landing System Interface Board
The MC-LSI provides a connection point for the landing system and for the Car Panel Interface board (HC-CPI) if one is used. The board receives 24 VDC power from an external power supply operating off the controller 2 Bus (120 VAC). In turn, the LSI board provides power to the landing system and to any Universal I/O boards that might be used on the cartop through the CAN connections to those components. A shielded, external CAN connection runs from the LSI board, through the traveler, to the Motion 4000 controller. There are additional, discrete connections through the traveler if the system is TSSA compliant and uses the LS-EDGE landing system.
Figure 5.12 MC-LSI Landing System Interface Board
Landing system to controller. See specific job prints.
Local CAN connections to other car boards
CAN to
Machine
Room
Landing System
ELGO and
LS-EDGE
Landing System
LS-EDGE TSSA
24 VDC from cartop power supply
Door control signals to operators
Door control signals from HC-UIO board
LSI Connections
• Local CAN: CAN and power to additional cartop box boards (HC-UIO, MC-CPI, etc.)
• CAN to Machine Room: CAN connections to/from machine room
• Landing System: CAN and DISC connections to/from landing system
• Door Signals from cartop HC-UIO:
• NDRI: Nudging, rear
• DORI: Door open, rear
• DCRI: Door close, rear
• Door Signals to operators:
NDFI: Nudging, front
DOFI: Door open, front
DCFI: Door close, front
• NDR: Nudging, rear
• DOR: Door open, rear
• DCR: Door close, rear
NDF: Nudging, front
DOF: Door open, front
DCF: Door close, front
• COMR: Common COMF: Common
• Landing System to Controller, Additional:
• See job prints. Controller/Landing System specific signals. See HC-CTL-2,
5-46
.
5-72 Manual # 42-02-2P25
Motion 4000
PC Board Quick References
SC-3HN Three Input Serial Hall Call Node Board
The SC-3HN board is used to provide serial hall calls for Motion systems. The SC-3HN provides analog inputs and outputs for the hall call buttons and LEDs and a CAN connection to the group or controller. Refer to the drawings package for connection instructions to your fixtures.
Figure 5.13 SC-3HN Three Input Serial Hall Call Node Board
Processor
Reset
JP5, CAN Bus termination. Place across pins
ONLY on last board connected to a wire drop.
Entry / Floor
Address
Riser Identification
ON LED, green
FLT LED, red
5
Call Bus Conditions
Make connections as shown on the drawings for the particular job.
• Group: Eight risers are supported; four Main and four Auxiliary.
• Controller: Four main risers are supported.
• Each hoistway wire drop consists of a twisted pair for signals and one wire each for 24V power and common. A wire drop can support more than one riser.
• Settings on each SC-3HN board determine which riser it belongs to, its floor address, and whether it is associated with the Front or Rear car entry.
• SC-3HN boards with the same floor address and entry association will register the same call and light indicators. Each must have a different riser ID but within the same riser group (Main or Auxiliary).
• Main risers A - D use riser IDs 7 - 4. Auxiliary risers A - D use riser IDs 3 - 0. See “Riser
Assignment” on page 5-75.
General Installation
All SC-3HN connections are at one end of the board. One board is installed in each hall call panel electrical box. The board is shipped in an anti-static bag.
1. Make connections to the hall call buttons and indicators. (See following page.)
2. Make connections to the signal/power drop. (See following page.)
3. Set floor number and door (F/R) location, 5-75
.
4. Set riser assignment, 5-75
.
5. Last board on wire drop only: Place a jumper on JP5. All other boards: Ensure jumper
NOT placed across JP5 pins, 5-75
.
6. Insert board in anti-static sleeves and tape closed using supplied ESD sticker.
7. Tuck bag/board into electrical box and re-install hall call.
5-73
Troubleshooting
Figure 5.14 Hall Call Node Wiring
+24 V COM CAN H CAN L
Table 5.19 Hall Wiring Colors
Color
red black brown yellow orange blue violet green gray white
+24V common
CAN H
CAN L
UL+
UL-
DL+
DL-
SP+
SP-
UL -
UP HALL CALL
(Others similar)
UL +
COM
Signal
5-74 Manual # 42-02-2P25
Motion 4000
PC Board Quick References
Addressing and CAN Bus Termination
Set SC-3HN addresses as shown in the job prints for the installation. Generic examples are provided below.
Riser Assignment
There may be up to four Main risers and four Auxiliary risers. Jumper locations JP3, JP2, and
JP1 are used to assign the appropriate riser to the SC-3HN board. In the following table, a “1” indicates a jumper in place.
Table 5.20 Riser Assignment by Jumper Binary Representation
1
1
1
1
JP3 JP2
1
1
0
0
1
0
1
0
JP1
Main A (Binary value 7)
Main B (Binary value 6)
Main C (Binary value 5)
Main D (Binary value 4)
Riser
0
0
0
0
0
0
1
1
1
0
1
0
Auxiliary A (Binary value 3)
Auxiliary B (Binary value 2)
Auxiliary C (Binary value 1)
Auxiliary D (Binary value 0)
Floor Number and Front or Rear Opening
DIP switch SW1, switches 1 through 7 set the floor address for the board, beginning with Floor 1.
Switch 8 selects Front or Rear opening.
ON
SW
8
7
6
3
2
5
4
1
Floor address example = 11
OFF=FRONT, ON=REAR
64
32
16
8
4
2
1
When setting addresses, use the values silkscreened on the circuit board, not those shown on the DIP switch.
ON switch adds its value to floor address.
Baud Rate
Jumper JP4 is reserved for future use to select a different CAN Bus baud rate should it become necessary. For now, the only option is to leave the JP4 jumper in place, setting baud rate to 125 kbps.
CAN Bus Termination
The CAN Bus must be terminated ONLY ON THE LAST SC-3HN connected to the wire drop
(farthest board from Dispatcher).
JP5 OFF/Unterminated
All but last board
JP5 ON/Terminated
Last board on wire drop ONLY.
5
5-75
Troubleshooting
On Board Diagnostics
Two LEDs provide diagnostic information: The ON LED (green) and the FLT LED (red).
ON LED
The ON LED reflects power/communications status.
• ON: Serial hall call bus to Group/Car OK
• OFF: Board is not receiving power or has no software loaded.
• Blinking: Communications error - more than ten seconds have passed without a message from the dispatcher.
(FLT) FAULT LED
The FLT LED reflects the status of the analog outputs.
• ON steady: Internal fault -
• Replace board if problem persists
• OFF: No Errors detected.
• Blinking: Output overload or disconnection. Pressing the Reset button on the SC-3HN board will clear a blinking Fault LED.
• Overload: Excessive current draw. Resets when current draw is corrected and call button is pressed again.
• Not Connected: The output is on (button pressed) but nothing is connected to the UL- or DL- output. Resets when the lamp is connected and the call button is pressed again.
• Output Shorted: If short is very quick, the LED will flash. Pressing the call button for a few moments will cause the board to reboot. Resets when the short is removed and the call button is pressed again.
Note
Please refer to the Motion Group Manual, 42-02-G006, for configuration information relating to group hall calls.
5-76 Manual # 42-02-2P25
Motion 4000
PC Board Quick References
TC-MPI Board
The Motion Processor Interface board provides serial and discrete interface to selected AC or
DC drives. Redundant safety processors are also on this board as well as the connection points for seismic and earthquake devices and for an emergency brake/rope gripper if one is used.
There are three, independent safety processors. Working in conjunction with position and speed feedback sensors, and continuously monitoring one another, the three prevent the elevator from starting or bring it to an emergency stop if position/speed related errors are detected.
• SPA (Safety Processor A): Working in conjunction with the PS1 positioning sensor (one of two positioning sensors on the cartop), SPA performs Emergency Terminal Switch functions and continuously monitors position and speed data from its sensor as well as continuously comparing this data with data reported to SPB.
• SPB (Safety Processor B): Working in conjunction with the PS2 positioning sensor (one of two sensors on the cartop), SPB performs Normal Terminal Switch functions and monitors PS2 position and speed data, continuously comparing this with data reported to SPA.
• MP (Motion Processor): Primary functions are drive and speed control. Additionally, monitors speed and direction from motor rotation and from PS1 positioning sensor. The
MP checks that both SPA/PS1 and SPB/PS2 systems are functioning properly by comparing their data and ensuring that any discrepancy is within a fixed tolerance. Using PS1 data, the MP is also able to perform redundant checking of the ETS function.
5
5-77
Troubleshooting
Figure 5.15 TC-MPI Motion Processor
CAN Bus CT
Drive I/F
Earthquake
Reset
Emergency
Brake Reset
Encoder from Drive
Contactor
Proofing, Door
Zone, Spares
Emergency
Brake
Power and
Common
Buttons
Diagnostic Indicator LEDs
5-78 Manual # 42-02-2P25
Motion 4000
PC Board Quick References
Table 5.21 TC-MPI Board Customer Connections
Connector Pin
J5
CAN Bus
Drive
Control
J7
Rope Gripper
240VAC Max
1
2
3
4
3
4
1
2
Label
CANH3
CANL3
GND
SHLD
RG7
RG5
RG2
RG1
Function
CT drive CAN interface CANH
CT drive CAN interface CANL
CT drive CAN interface Ground
CT drive CAN interface Shield connection
Control out
Control in
Analog Ground
120VAC Out
5
J11
Buffered encoder signal from drive to MPI board
J12
120VAC Max
J16
Discrete
Drive
Control
J20
3
4
1
2
3
4
1
2
7
8
5
6
3
4
1
2
4
5
2
3
7
1
5
6
UETS
DETS
SPI1
SPI2
DPS
DNS
DRE
DCOM
A+
A-
B+
B-
Z+
Z-
GND
SHLD
DRO
DRDY
DFLT
EQ24
CW2
CW1
SSI
EQIND
A+ buffered encoder from drive
A- buffered encoder from drive
B+ buffered encoder from drive
B- buffered encoder from drive
Z+ buffered encoder from drive
Z- buffered encoder from drive
Ground
Shield
Up Emergency Terminal Switch input (if used)
Down Emergency Terminal Switch input (if used)
Spare Input 1 (assignable per job)
Spare Input 2 (assignable per job)
AC Drive Positive, 16 - 14VDC
AC Drive Negative, Ground
TORQMAX Drive Enable, Magnetek Drive Common
TORQMAX A2.20 (16-18VDC), Magnetek Enable
Drive On input
Drive Ready input
Drive Fault input
24V for counterweight “ring and string” movement detector
Counterweight detector, 24VAC Max
Counterweight detector, 24VAC Max
Seismic Sensor Input, 24VAC Max
Earthquake Indicator, 120VAC Max
5-79
Troubleshooting
Table 5.21 TC-MPI Board Customer Connections
Connector Pin
J17
CAN Bus
Hoistway
Position
System
Sensors
1
2
3
4
5
J24
J27
J2
Label Function
CANH1
CANL1
CANH2
CAN interface to first hoistway position sensor
CAN interface to first hoistway position sensor
CAN interface to second hoistway position sensor
CANL2
SHLD
CAN interface to second hoistway position sensor
CAN interface Shield connection
MAGNETEK 9-Pin, D, serial control for Magnetek AC drive
TORQMAX 9-Pin, D, serial control for TORQMAX drive
INTERNAL
NETWORK
CAN and power connections internal to Controller. Factory connection. Disconnection will reset board.
Table 5.22 TC-MPI Board Jumpers
Jumper Function
JP1 Normal = A position: Terminating resistor for RS422/485 communication ON.
B position: Removes terminating resistor from circuit.
JP2, JP3, JP4 Terminating resistors for buffered encoder information from drive. When jumpers are in place, terminating resistors are ON.
JP6 Terminating resistor for internal CAN Bus. When jumper is in place, terminating resistor is ON.
JP5, JP7 Normal = B position: RG monitoring done on TC-MPI board.
A position: RG monitoring by equipment external to TC-MPI board.
Table 5.23 TC-MPI Board MCE Internal Connections
Connector Pin
J3
J9
6
7
4
5
8
2
3
5
1
3
4
1
2
Label
BR
PM
FBS
BRP
PMP
PM2
2L
BRBP
SPI3
SPI4
DZRO
DZFO
BRC
Function
Primary motor contactor
120VAC
Brake control
Spare Input (DNT1 if physical directional limits are used, F7 202)
Spare Input (UNT1 if physical directional limits are used, F7 202)
Door Zone Rear Output
Door Zone Front Output
Brake Contactor Complimentary
Brake Contactor
Primary motor contactor
Full Brake Strength, bypasses brake hold voltage resistor
Brake Contactor
Primary motor contactor
5-80 Manual # 42-02-2P25
Motion 4000
PC Board Quick References
Table 5.23 TC-MPI Board MCE Internal Connections
Connector Pin
J25
J13
4
5
2
3
8
9
10
1
6
7
4
5
1
2
3
Label
RG1
EBS1
EBS2
24VAC
1
1
2MV
2MV
EBD1
EBD2
EBD3
EBD4
EBP12
EBP34
EBPS
Function
Emergency Brake, 120VAC
Emergency Brake, 120VAC
Emergency Brake, 120VAC
Emergency Brake, 120VAC
Emergency Brake, monitoring
Emergency Brake, monitoring
Emergency Brake, Control
120VAC
Emergency Brake, Control
Emergency Brake, Control
24V input
Common
Common
120VAC input
120VAC input
5
Table 5.24 TC-MPI Board Switches
Switch
SW1
SW2
RSTMP, S4
RSTB, S1
RSTA, S2
EB RST, S3
EQ RST, S5
Function
4-Position DIP switch. Board configuration. If replacing TC-MPI in the field, set exactly as original board.
4-Position DIP switch. Board configuration. If replacing TC-MPI in the field, set exactly as original board.
Reset button for Motion Processor
Reset button for B Processor
Reset button for A Processor
Emergency Brake reset
Earthquake reset
Table 5.25 TC-MPI Board Diagnostic LEDs
Indicator Function
3.3V
UM
OS
Indicates presence of 3.3V power on board
Lights if Unintended Motion fault is active
Lights if Overspeed fault is active
EQ Lights if Earthquake fault is active
DIA1A-DIA8C Factory diagnostics only
5-81
Troubleshooting
Motion Brake Module
A brake control module allows the level of the control voltage to be adjusted. Modulated voltages provide control over the entire range of brake movement. The module provides the ability to control the rate at which the brake descends onto the braking surface. With this ability, brake control can be more subtle resulting in a smoother ride under all motion conditions in which the brake plays a part, saving energy, and reducing brake coil temperatures.
The MCE brake module can be controlled by discrete inputs or through a CAN interface. Discrete control provides compatibility with MCE legacy controls.
Figure 5.16 Motion Brake Module
Logic TC-FCL
Logic power supply TC-LPS
Inverter power supply TC-FCP
Heat sink
Configuration
The top board, TC-FCL, provides the controls to configure the module for job requirements.
Such configuration is completed at the factory when the module is shipped installed in a controller. If the module is a modification to an existing control, check this instruction for proper settings. If you are replacing an existing module, set up the new module to match.
5-82 Manual # 42-02-2P25
Motion 4000
Figure 5.17 Configuration
Motion Brake Module
5
Switches and Jumpers
Table 5.26 SW1, Manual Bypass
2 1 Description
Off Off Manual brake pick enabled (will cause Main IGBT stuck open fault to be indicated until the brake contactor is picked to allow power to the brake module). In this mode, a manual brake pick switch connected between BRBP1 and BRBP3 will energize the brake coil connected between
BRBP2 and BRBP4 and immediately lift the brake regardless of the status of the elevator controller.
Off On Unused
On Off Unused
On On Unused
5-83
Troubleshooting
The four switches of DIP switch SW3 function as two independent pairs. Switches 4 and 3 enable various software features. Switches 2 and 1 set the ID for the module. The ID identifies the module to the controller allowing it to be addressed and controlled independently of any other modules used (up to three).
Table 5.27 SW3 Module ID and Software Features
4 3 2 1
Off Off
Off On
On Off
On On
Description
Off Off Brake module, ID=1 Primary brake module address
Off On Brake module, ID=2 Secondary brake module address where module 1 controls the first brake coil and module 2 controls a second brake coil on the same machine.
On Off Brake module, ID=3 Emergency brake module address
On On Module, ID=4 Future unused unused
Enables software update from EEPROM chip inserted in socket U21 unused
Reset Switch The reset switch, RST, resets the logic board processor.
Jumper JP1 JP1 enables/disables the CAN termination resistor.
• A position: Terminates the CAN connection on the board.
• B position: Leaves the CAN termination open on the board (Normal position for this board).
ON LED
The ON LED next to the Reset switch is on solidly when the module is powered and functioning properly. The ON LED will blink if a fault condition is detected. Under fault conditions, the LED will blink a number of times, go dark for a period of time, and then repeat. The number of blinks indicates the fault detected.
Table 5.28 LED Fault Indication
1
Blinks
2
3
Fault Description Reset
Load over current If load current goes above 20A during the first 5 seconds of operation or above 15A after the first 5 seconds of operation, over current condition will be reported through FLT output and current will be limited to 15A.
Load over voltage If load voltage goes above 310VDC for more than 5 seconds, over voltage condition will be reported through FLT output and voltage will be limited to
310V.
Aux IGBT stuck open If the brake is in pick, hold, or relevel mode and the
Aux IGBT monitoring circuit returns a high signal for
100mS or more, the Aux IGBT stuck closed fault will occur.
Current reduction
Voltage reduction
Discrete: Processor reset.
CAN: Auto reset after 8 seconds.
5-84 Manual # 42-02-2P25
Motion 4000
Motion Brake Module
Table 5.28 LED Fault Indication
4
5
6
7
8
9
Blinks
10
11
12
13
14
15
Continuously
Fault Description Reset
Aux IGBT stuck closed If the voltage across the Aux IGBT does not go high enough to trigger the Aux IGBT monitoring circuit during the dissipate mode, the Aux IGBT Stuck closed fault will occur. This fault is scanned for after the module switches from dissipate to inactive mode.
Main IGBT stuck open If the brake is in pick, hold, or relevel mode and there is less than 5 volts or 100mA across the coil for 200 mS or more, the IGBT stuck open fault will occur.
Main IGBT stuck closed If the brake is not in pick, hold, relevel, or dissipate mode and there is more than 10 volts or 2 Amps across the brake coil for 200 mS or more, the IGBT stuck closed fault will occur.
Module overheat The IGBT units on the bottom of the TC-FCP board generate heat when operating. A thermal sensor on the heat sink is connected to the module logic board through the TS1 and TS2 inputs. If the temperature becomes excessive, the logic module will generate a fault, pulling the FLT output to the Common connection level and alerting the controller.
Trying to run in manual release mode
Manual brake pick is enabled.
Bypass button stuck closed
Not used
Brake bypass button stuck closed in manual pick mode.
Discrete: Processor reset.
CAN: Auto reset after 8 seconds.
Discrete: Processor reset.
CAN: Auto reset after 8 seconds.
Discrete: Processor reset.
CAN: Auto reset after 8 seconds.
Temperature reduction.
Remove from manual brake pick mode.
Check button.
CAN MODE ONLY
Discrete input during
CAN operation
Verify discrete pick, hold, and relevel inputs to J1 are not used when CAN control is active.
Module address error.
Verify SW1 positions for each module. 5-84
.
Not calibrated
Load undercurrent
Load undervoltage
CAN disconnected
Module has not been calibrated
Current <80% of learned
Voltage <80% of intended
CAN to module disconnected
Auto reset after 8 seconds.
Auto reset after 8 seconds.
Calibrate module
Auto reset after 8 seconds.
Auto reset after seconds.
Troubleshoot connection
5
5-85
Troubleshooting
Module Connectors Per Board
Top Board, TC-FCL This section provides information about user-accessible module connections.
Table 5.29 J1 Pin Assignment
PICK
HOLD
RELEV
FLT
COM
1
2
TS2
TS1
Pin Function
Discrete Pick control input from controller (V AC/DC)
Discrete Hold control input from controller (V AC/DC)
Discrete Relevel control input from controller (V AC/DC)
Overload fault output
Common connection for PICK, HOLD, RELEV, FLT
1 Bus (common) from elevator controller
2 Bus (120VAC) from elevator controller
Thermal switch input from sensor on module heat sink
Thermal switch input from sensor on module heat sink
J4, J5 J4 is a modular, CAN connector for serial module control. (See preceding information about termination enabling jumper JP1.) J5 provides auxiliary connections that can be used to directly lift the machine brake, regardless of controller status.
Table 5.30 J5 Auxiliary Brake Connections
Pin
BRBP1
BRBP2
BRBP3
BRBP4
Function
With BRBP3, connects to auxiliary brake pick switch
With BRBP4, energizes brake coil when active
With BRBP1, connects to auxiliary brake pick switch
With BRBP2, energizes brake coil when active
The level of the pick voltage is adjusted using potentiometer R67. The maximum pick voltage range is determined by input voltage to the module and whether the input connection is single phase, FCL1/FCL2, or three phase, FCL1/FCL2/FCL3.
J3 J3 provides control signals to the TC-FCP board and accepts feedback voltages from the
TC-FCP board.
J6 J6 accepts DC power voltages from the logic power supply board (TC-LPS).
Middle Board, TC-LPS
1 and 2 bus power connections from the controller are connected to TC-LPS connector
J1. As viewed from the front of the connector, pinout is:
This board provides DC power to the logic board through connector J2.
2 2 1 1
5-86 Manual # 42-02-2P25
Motion 4000
Motion Brake Module
Bottom Board, TC-FCP
The FCP board transforms AC input power (single or three phase) into the DC output voltage required to control the brake. The in-line connectors on the board are sized to handle higher voltage and current.
Table 5.31 In-Line Connectors Pin Assignment
Pin Function
J2, SN1 With SN2, connection point for external filter provided with unit
J2, SN2 With SN1, connection point for external filter provided with unit
J2, SN3 With J3, SN4, connection point for user-provided external filter
J3, SN4 With J2, SN3, connection point for user-provided external filter
J3, FCO- With FCO+, provides power to energize brake coil under normal logic conditions
J3, FCO+ With FCO-, provides power to energize brake coil under normal logic conditions
J5, DT1 Factory Only. Production testing.
J5, DT2 Factory Only. Production testing.
J5, FCL1 AC input, with J6, FCL2 for single-phase use or J6, FCL2/FCL3 for three-phase use
J6, FCL2 AC input, with J5, FCL1 for single-phase use or J5, FCL1/J6 FCL3 for three-phase use
J6, FCL3 AC input, with J5, FCL1 and J6, FCL2 for three-phase use.
Figure 5.18 External Filtering
Module
5
FCO+
SN4
SN2
Filter
SN1
SN3
FCO-
Optional
Filter
Brake Coil
5-87
Troubleshooting
Figure 5.19 Brake Timing Diagram
Calibration (CAN Only)
If CAN control is used, modules must be calibrated for Motion 4000 use through the F5 controller menu. Each module used,
see “SW3 Module ID and Software Features” on page 5-84
, must be calibrated.
Note
If the controller uses an M-Brake Module for the emergency brake, the emergency brake module must be calibrated before any other brake module in the system is calibrated. An emergency brake module is indicated when the EMERGENCY BRAKE option, parameter 186 on the F7 menu, is not set to DISABLED and the EMERGENCY BRAKE TYPE option, parameter 199 on the F7 menu, is set to MODULE. Please note that the EMERGENCY BRAKE TYPE option will not be displayed if the EMERGENCY BRAKE option is set to DISABLED.
1. On Machine Room Inspection, place the HC-MPU F5 function switch in the UP position.
2. Press N until the FCL BRAKE UNIT, UTILITIES MENU is displayed. Press S to select.
3. Press N to advance to FCL ADJUSTMENT MENU. Press S to select.
4. CALIBRATE FCL:1, [S]-SELECT will appear. Use +/- buttons to select appropriate module number. Press S to begin calibration.
5. PICK A DIRECTION TO CALIBRATE will be displayed. Press and hold either UP or
DOWN direction. The display will show CALIBRATING FCL: STATUS: ...
6. Continue holding UP or DOWN direction until CALIBRATION DONE [N]-NEXT appears. If UP or DOWN is released too soon, the display will report CALIBRATE
ABORT [N]-NEXT and the process must be repeated.
7. Repeat if additional modules must be calibrated.
5-88 Manual # 42-02-2P25
Motion 4000
Motion Brake Module
Trim pots and Function (Discrete Control Only)
Potentiometer settings are ignored when the module is being controlled through the TC-FCL,
J4 CAN connection.
• R67, Brake Pick Voltage (maximum output to lift brake), LED lights
• R68, Brake Hold Voltage (percentage of Pick Voltage), LED lights
• R69, Brake Relevel Voltage (percentage of Pick Voltage), LED lights
• R70, Brake Drop Rate (clockwise = faster)
• R71, Brake Pick Rate (clockwise = faster)
Setup for Adjustment
1. Disconnect power to the controller.
2. Discrete control only. Rotate trim pots R67, 68, and 69 counter-clockwise to locate the begin stop, then clockwise to locate the end stop. Then set to the approximate center position.
3. Connect Brake outputs FCO+/FCO- and BRBP2/BRBP4 (if used) as shown in your job drawings. These connections are probably made from the module to a panel-mount connector and from the panel-mount connector to the brake.
4. Connect the brake filter across SN1/SN2 as shown on the job prints. Connect the input
3- or single-phase power as shown in the job prints.
5. Connect control inputs from elevator controller as shown in your job prints (CAN or
Discrete control).
6. Connect a volt meter across the brake coil.
Discrete Control Adjustment
Check that there is no CAN connection to the brake module. This procedure is for discrete voltages control.
1. Apply power to the controller. Place the elevator on Machine Room Inspection operation and pick a direction.
2. With the brake picked, adjust R67 to attain the brake manufacturer pick voltage. Verify that the brake picks cleanly.
3. After the brake settles to hold position, adjust R68 to attain manufacturer hold voltage.
Verify that the brake is not dragging.
4. Disconnect power from the controller.
5. Disconnect the Relevel output from the module (place a wire nut on the wire end for safety). Move the Hold wire to the Relevel output.
6. Reconnect power to the controller.
7. On Inspection, pick direction and allow the brake to pick. The brake hold position is being controlled through the relevel output.
8. Adjust relevel R69 until the brake is just dragging but remains quiet.
9. Disconnect power from the controller. Return connections to their proper states.
5
5-89
Troubleshooting
133
F7 #
134
135
136
138
139
185
186
190
194
195
196
197
198
199
200
201
CAN Control Adjustment
1. Apply power to the controller. Place the elevator on Machine Room Inspection.
2. Verify and/or set F7 brake parameters:
Parameter
Normal Brake Pick Delay
Speed Pick Delay
Normal Brake Hold Delay
Normal Brake Drop Delay
Drive Disable Delay
Speed Hysteresis Delay
Brake Type
Emergency Brake
Sheave Brake Idle Delay
Normal Brake Pick Voltage
Normal Brake Hold Voltage
Normal Brake Relevel Voltage
Normal Brake Lift Rate
Normal Brake Drop Rate
Emergency Brake Type
Emergency Brake Pick Voltage
Emergency Brake Hold Voltage
Description
Time in milliseconds after drive enable command issued and acknowledged before the brake should pick.
Time in milliseconds after brake is picked before the speed command is issued. Used to prevent beginning movement under a slow-picking brake. Default 500.
After take off, the brake is held fully picked until this timer expires, at which point, it settles to hold position/voltage.
Geared machine default 2000. Gearless machine default
800.
Delay in milliseconds that the brake should be delayed from dropping after the speed command is dropped. Goal is to avoid dropping the brake until the motor has just stopped moving. Default 250.
Time in milliseconds after stopping at a floor which the drive should maintain electrical control of the motor. May be used to compensate for a slow dropping brake. Default
1250.
Provides a delay between when the speed command is issued and when it begins to accelerate the load.
Module 1, Module 2, or Discrete. Select as configured.
Selects or disables the emergency brake option. Disabled
= no emergency brake. Rope gripper = rope gripper.
Sheave brake = sheave brake. Machine brake = independent machine brakes with one being used as the emergency brake.
Appears if sheave brake selected as emergency brake.
When car is idle, sheave brake will drop after the time set here expires. Allows brake to be exercised. Time in seconds.
Set to pick voltage required by brake.
Set to hold voltage required by brake.
Set to relevel voltage required by brake.
Set desired lift rate in percentage. 100% = Fastest lift rate.
Set desired drop rate in percentage. 100% = Fastest drop.
Module or Discrete voltages control.
Only if Module selected in 199. Set required brake pick voltage.
Only if Module selected in 199. Set required brake hold voltage.
5-90 Manual # 42-02-2P25
Motion 4000
Motion Brake Module
3. Pick a run direction. Verify that the brake picks cleanly. If not, readjust pick voltage in
F7 menu, save parameters, and retry.
4. After the brake settles to hold position, verify that the brake is not dragging. If necessary, readjust hold voltage in F7 menu, save parameters, and retry.
5. On Inspection, pick direction and verify brake-related F7 delay/time/rate are as desired.
Upon dropping direction, verify brake-related F7 delay/time/rate are as desired. If necessary, readjust settings and retry.
Only if a Manual Brake Pick Button is Used with CAN Control If a manual
brake pick button is used on this job ( see “SW1, Manual Bypass” on page 5-83 ), pick voltage
applied when the button is active is determined by FCL potentiometer R67. To adjust:
1. On Inspection, move the car to mid-point position in the hoistway to allow the car to safely drift up or down when the brake is picked. (Car must be appropriately counterbalanced to avoid rapid movement.)
2. Set SW3 to enable manual pick.
3. Press the manual pick button, observe brake pick while adjusting R67 to minimum required voltage for clean pick action.
Release the manual pick button. Take SW1 off manual pick mode.
5
5-91
Troubleshooting
5-92 Manual # 42-02-2P25
Appendix
In this Section
This section contains:
• TORQMAX F5 Parameter Table, TORQMAX F5 Parameters Table on page A-2
• Magnetek Parameter Table, Magnetek AC Drive Table on page A-6
• Customer F7 Settings Log,
F7 Settings Record on page A-14
• Customer General Settings Log,
General Settings Log on page A-21
• Floor Heights Log,
Floor Settings Log on page A-27
• Customer Notations, Customer Notations on page A-28
• TORQMAX R6 Regen Drive Reference, R6 Regenerative Drive Reference on page A-29
• Floor setup after tape or TC-MPI replacement, Manual Floor Setup, ELGO on page A-30
• ICE-COP-2 I/O Assignment, Factory I/O Assignment, ICE-COP-2 Boards on page A-31
A-1
Appendix
TORQMAX F5 Parameters Table
Enter the settings you make while adjusting into the Field column of the following table.
Table A.1 TORQMAX F5 Parameters for Motion 4000
Display Parameter Description Unit Range Default
WARNING: Do not change drive parameters while the elevator is running. Incorrect drive
parameter values can cause erratic operation.
Field
WARNING: Parameters with an asterisk (*) must be set correctly for your specific motor / machine / job. Refer to the adjustment manual for detailed information.
LF. 2 bnSPd SerSP
LF. 3
LF. 4
LF. 5
LF. 8
LF. 9
LF.10
LF.11
LF.12
LF.13
Signal operating mode:
AbSPd - Absolute Analog Speed d SPd - Digital Speed Selection
A tor - Analog Torque Control
A Spd - Analog Speed Control
SerSP - Serial Com. Speed Control bnSPd - Binary Speed Selection
S POS – Serial Position feedback
Drive configuration: run- run mode conF - Configuration (5 minute time limit)
Stop - Drive stopped, Motor cannot run. Drive will not respond. When using serial com, this mode allows parameter changes
S Lrn - activate auto tune
I Lrn - Inertia Learn. Learns the system inertia and activates the FFTC.
P Lrn: Pole Learn. Learn the pole positions of
PM Motor
SPI - Stationary Pole Learn. Learn absolute encoder position for PM machine under brake without sheave movement.
(N/A for software Version 1.61)
OStST - Over speed test function. Allows car to over speed machine to test governor.
(N/A for software Version 1.61)
Motor-selection: Displays mode selected using US.
4 and US.10
ICLSd - Close loop induction
I9LSS = Closed loop induction gearless
PCLSd = Closed loop permanent magnet (PM)
P9LSS = Closed loop PM gearless
Drive fault auto reset
Electronic motor overload protection
IM - Electronic overload current
PM - not visible, auto set same as LF.12
IM - Rated motor power
PM - read only, auto calc.
Rated motor speed
Rated motor current
Rated motor frequency
-
-
1
-
A
HP
AbSPd d Spd
A tor
A Spd
SerSP
BnSPd
S POS run conF
Stop
S Lrn
I Lrn
P Lrn
SPI
OStST see US.10
0 - 10 on, off
1.0 - 110%
Drive rated conF
-
5 off
8.0
0.00 - 125.00 5.00
rpm 10.0 - 6000.0 1165 or
150
A 1.0 - 110%
Drive rated
8.0
Hz 4.0 - 100.0
60.0
run
A-2 Manual # 42-02-2P25
Motion 4000
TORQMAX F5 Parameters Table
Table A.1 TORQMAX F5 Parameters for Motion 4000
Display Parameter Description Unit Range Default
LF.14
LF.15
LF.16
Rated motor voltage
IM - Name plate rated voltage
PM - No-load, phase-to-phase back EMF rms voltage at LF.11
IM: Power factor, PM: not visible
IM: Field weakening speed, PM: not visible
LF.17
LF.18
LF.19
PM: Motor leakage inductance - from data sheet or learn procedure (see F5 Drive manual)
IM: not visible
Contract speed LF.20
LF.21
LF.22
LF.23
LF.24
Traction sheave diameter (measured value)
Gear reduction ratio
Roping ratio
Load weight
LF.25
Estimated gear ratio: Read only, auto calc.
0.LF.26 Encoder Interface: displays feedback type
LF.27
Encoder pulse number
For InclE and SinCo reference to customer data
For HIPEr set to 1024
For EndAt set to 2048
LF.28
LF.29
LF.30
Rated motor torque, IM - read only, auto calc.
PM - enter motor name plate torque
PM: Motor stator resistance - from data sheet or learn procedure (see F5 Drive manual) IM: not visible
Encoder channel swap / direction
0 nothing reversed
1 encoder A<B>B swapped
2 motor rotation reversed
3 motor rotation reversed, A<B>B swapped
Encoder sample time
(recommend gearless = 4, geared = 8)
Control mode
0, 1Open loop induction motor operation
2 -Closed loop speed control (LF. 2 = A Spd)
3 -Closed loop speed control with pre-torque
4 -Closed loop torque control (LF. 2 = A tor)
5 - Close loop speed control with synthesized pretorque
V
1 rpm 0.0 - 6000.0
set @ 80% of LF.11
lb ft
1
IM: 120 - 500V
PM: 1 -
32000V/krpm
0.50 - 1.00
1 - 10000 ohm 0.0 - 49.999
mH fpm
1 lbs ppr
1
0.01 - 500.00 1.00
0 - 1600
1 - 8
0 - 30000
256 - 16384
0 - 3 mSec 0.5 - 32
0 - 5
230/460
0.90
IM - calc.
PM - 18
49.999
0 inch 7.00 - 80.00
24.00
1 1.00 - 99.99
30.00
1
0
0.01 1.00 - 99.99
-
-
1024
0
4
0
A.LF.31 Kp speed accel: Proportional gain, accel & run d.LF.31 Kp speed decel: Proportional gain, decel
P.LF.31
Kp speed torque (Synth. Pre-torque)
A.LF.32 Ki speed accel: Integral gain, accel & run d.LF.32 Ki speed decel: Integral gain, decel
P.LF.32
KI speed torque (Synth. Pre-torque)
A.LF.33 Ki speed offset accel: Gain at low speed, accel d.LF.33 Ki speed offset decel: Gain at low speed, decel
1
1
1
1
1
1
1
1
1 - 50396
1 - 50396
1 - 50396
1 - 26214
1 - 26214
1 - 26214
0 - 8000
0 - 8000
3000
3000
2000
350
250
10000
3000
1000
0.LF.36 Maximum torque (Auto calc by the drive). lb ft 0 - 500%Trtd Calculated
1.LF.36 Maximum torque emergency operation (=LF.17) lb ft 0 - 500%Trtd Calculated
Field
A
A-3
Appendix
Table A.1 TORQMAX F5 Parameters for Motion 4000
Display Parameter Description Unit Range Default
LF.37
LF.38
LF.41
LF.42
LF.43
LF.44
LF.45
LF.46
LF.47
LF.49
Open loop torque boost: Open loop op. only
Carrier frequency; 0 = 8 KHz, 1 = 16KHz
(Note: set LF.38 = 0 if E.OL2 error on drive)
Leveling speed (Not used, must set to 0)
High speed (Not used, must set to 0)
Inspection speed (Not used, must set to 0)
High leveling speed (Not used, must set to 0)
Earthquake Speed (Not used, must set to 0)
Over speed function Test (N/A for SW Version
1.61)
0.LF.50 Profile 0 - Starting jerk (not used)
%
1 fpm ft/s
3
0 - 25.5
0, 1
0 - 25
5.0
0
0.0
fpm 0.0 - LF.20
0.0
fpm 0.0 - 150.00
0.0
fpm 0.0 - LF.20
fpm 0.0 – 150.0
Emergency Pwr Speed (Not used, must set to 0) fpm 0.0 - LF.20
Intermediate speed (Not used, must set to 0) fpm 0.0 - LF.20
fpm 1- 2400
0.0
0.0
0.0
0.0
100
0.LF.51 Profile 0 - Acceleration (not used) ft/s
2
0.LF.52 Profile 0 - Acceleration jerk (not used) ft/s
3
0.LF.53 Profile 0 - Deceleration jerk (not used) ft/s
3
0.LF.54 Profile 0 - Deceleration (not used)
0.LF.55 Profile 0 - Approach jerk (not used)
1.LF.50 Profile 1 - Starting Jerk (not used)
1.LF.51 Profile 1 - Acceleration (not used)
1.LF.52 Profile 1 - Acceleration jerk (not used)
1.LF.53 Profile 1 - Deceleration jerk (not used)
1.LF.54 Profile 1 - Deceleration (not used) ft/s
2 ft/s
3 ft/s
3 ft/s
2 ft/s
3 ft/s
3 ft/s
2
1.LF.55 Profile 1 - Approach jerk (not used) ft/s
3
2.LF.50 Profile 2 - Starting jerk (not used) ft/s
3
2.LF.51 Profile 2 - Acceleration (not used) ft/s
2
2.LF.52 Profile 2 - Acceleration jerk (not used)
2.LF.53 Profile 2 - Deceleration jerk (not used)
2.LF.54 Profile 2 - Deceleration (not used)
2.LF.55 Profile 2 - Approach jerk (not used)
LF.56
LF.57
LF.58
LF.59
Stop jerk (not used) ft/s
3 ft/s
3 ft/s
2 ft/s
3 ft/s
3
1 off, on
% 0 - 30 sec 0.0 -1.0
1
10
1.0
LF.61
LF.67
LF.68
LF.69
LF.70
LF.71
Speed following error (0 = off, 1 = on,)
Speed difference
Trigger time speed difference: Following error timer
Emergency operation mode. If using an MCE
TAPS, (Traction Auxiliary Power Supply), this must be set to di1.
Pre-torque gain
Pre-torque offset
Pre-torque direction (0, 1 = +V, -1 = -V)
Speed pick delay (Delay to turn on DRO)
Brake pick delay
-
%
Off, SPd1,
SPd2, SPd3, di1
0.25 - 2.00
-100.0 - 100.0 0.00
1 0, 1, -1 sec 0.0 - 3.0
sec 0.0 - 3.0
off
1.00
1
0.30
0.05
Field
A-4 Manual # 42-02-2P25
Motion 4000
TORQMAX F5 Parameters Table
Table A.1 TORQMAX F5 Parameters for Motion 4000
Display Parameter Description Unit Range Default
LF.76
LF.77
LF.78
Encoder resolution multiplier
2 for incremental encoder
8 for Sin/Cos, EnDat or Hiperface encoder
Absolute encoder position (measured)
Brake drop delay. Time motor will hold full current and control after direction inputs drop.
LF.79
Current hold time. Delay in turning off the drive
(Delay to turn OFF the motor current after the direction is dropped and LF.78 has expired)
Diagnostic Parameters (Read only)
LF.25
LF.80
LF.81
LF.82
Estimated gear ratio
Software version
Software date
X2A input state
LF.83
LF.86
LF.87
LF.88
LF.89
LF.90
LF.93
LF.94
X2A output state
Operation mode
Actual inverter load (100% = rated load)
Motor command speed
Actual motor speed
Actual elevator speed
Phase current
Peak phase current
LF.95
LF.96
Actual DC voltage
Peak DC voltage
LF.97
Actual output frequency
O.LF.98 Last error
US Parameters
US. 1 Password: With different passwords different parameter groups can be accessed for advanced programming.
US. 3 Load defaults: Select LoAd and press ENTER to cause all LF parameters to be reset to drive default values.
US. 4 Load configuration: Select LoAd and press ENTER to load the configuration selected in US.10.
US.10
Select configuration: Selects the drive mode.
ICLSd - Close loop induction
I9LSS = Closed loop induction gearless
PCLSd = Closed loop permanent magnet (PM)
P9LSS = Closed loop PM gearless
US.34
Analog Pattern Gain
US. 35 Reference Splitting: This function creates a slope between two successive serially transmitted speed values. This parameter should be adjusted for a time double the actual serial update rate of the speed command
Note: Program to 40 msec for M4000 controller with Rev8
1 0 - 13
1 0 - 65535h sec 0.00 - 3.00
sec 0.00 - 3.00
V
V
Hz
-
A
A rpm ft/m
-
-
1
-
-
-
% rpm
-
-
-
see tables in F5 Drive
Manual
-
LoAd
LoAd
ICLSd
I9LSS
PCLSd
P9LSS
2
0
0.50
0.30
-
-
-
-
0.01-20.0
1.0
mSec 0 –200 mSec 0.0
Field
A
A-5
Appendix
Magnetek Parameters Table
Enter the settings you make while adjusting into the Field column of the following table.
Table A.2 Magnetek AC Drive Table
# Display Parameter Description Unit Range MCE Def Field Set
Adjust A0
A1 Drive
Contract Car Spd Elevator Contract Speed
Contract Mtr Spd Motor Speed at elevator contract speed
Response Speed regulator sensitivity. If set too high, motor current and speed will be jittery. If too small, the motor will be sluggish.
fpm 0 - 3000 rpm 50 - 3000 rad/ sec
1.0 - 20.0
0.1
1130
10
Inertia System inertia
Inner Loop Xover Inner speed loop crossover frequency (only with Ereg speed regulator)
Gain Reduce Mult Speed regulator response percentage to use in low gain Mode. 100% = no reduction.
%
Gain Chng Level Speed level to change to low gain mode
(only with internal gain switch)
%
% Tach Rate Gain Compensates for rope resonance. Use only after A1, Inertia, and A1, Response, have been set correctly.
Spd Phase Margin Phase margin of speed regulator
(only with PI speed regulator) o sec 0.25 - 50.00
2.0
rad/ sec
0.1 - 20.0
2.0
10 - 100 100
0 - 100.0
0 - 30.0
45 - 90
100
0
80
Ramped Stop Time Time to ramp from rated torque to zero (only with torque ramp down stop function) sec 0 - 2.50
Contact Flt Time
Brake Pick Time
Time before a contactor fault is declared
Time before a brake pick fault is declared
Brake Hold Time Time before a brake hold fault is declared
Overspeed Level Threshold for detection of overspeed fault sec sec
0.10 - 5.00
0 - 5.00
0.20
0.50
0.00
sec 0 - 5.00
%
0.00
100.0 - 150.0 125.0
Overspeed Time
Overspeed Mult
Encoder Pulses
Spd Dev Time
Spd DevHi Level
Encoder counts per revolution
Spd Dev Lo Level Range around the speed reference for speed deviation low logic output
Time before speed deviation low logic output is true
Level for declaring speed deviation alarm ppr
% sec
600 - 10000
00.1 - 10.0
0 - 9.99
% 0 - 99.9
Spd Command Bias Subtracts an effective voltage to actual speed command voltage volts 0 - 6.00
1024
10
1.00
20.0
0.00
Pre Torque Bias
Time before an overspeed fault is declared
Multiplier for overspeed test (U4)
Spd Command Mult Scales analog speed command
Subtracts an effective voltage to actual pre torque command voltage
Pre Torque Mult Scales pre-torque command
Zero Speed Level Threshold for zero speed logic output sec 0 - 9.99
% 100 - 150
0.90 - 3.00
volts 0 - 6.00
-
%
1.00
100
1.00
0.00
-10.00-10.00 1.00
0 - 99.99
sec 0 - 9.99
1.00
0.10
Zero Speed Time Time before zero speed logic output is declared true
Up/Dwn Threshold Detection threshold, up or down direction % 0 - 9.99
1.00
A-6 Manual # 42-02-2P25
Motion 4000
Magnetek Parameters Table
Table A.2 Magnetek AC Drive Table
# Display Parameter Description Unit Range MCE Def Field Set
Mtr Torque Limit Motoring torque limit. Torque Limit LED will light when this limit is reached.
Regen Torq Limit Regenerating torque limit. Torque Limit LED will light when this limit is reached.
Flux Wkn Factor Defines torque limit at higher speeds
%
%
%
Ana 1 Out Offset Subtracts an effective voltage to actual analog output 1
%
Up to SPD. Level The logic output function is true when the motor speed is above the user specified speed defined here
%
Mains DIP Speed When enabled by the Main DIP Speed (A1) parameter, speed is reduced by this percent when an undervoltage alarm is declared
%
0 - 250.0
0 - 250.0
60.0 - 100.0
-99.9 - 99.9
75.0
0.00
Ana 2 Out Offset Subtracts an effective voltage to actual analog output 2
%
Ana 1 Out Gain
Ana 2 Out Gain
Scaling factor for analog output 1
Scaling factor for analog output 2
-
-
Flt Reset Delay
Flt Reset / Hour
Time Before a fault is automatically reset
Number of faults allowed to reset automatically per hour
-99.9 - 99.9
0 - 10.0
0 - 10.0
sec 0 - 120 fault 0 - 10
0.00
1.0
1.0
5
3
0 - 110.00
5 - 99.9
250.0
250.0
080.00
25.00
Run Delay Timer Delays drive recognition of RUN signal.
AB Zero Spd Lev Auto Brake Function - N/A to MCE products %
AB Off Delay N/A to MCE products
Contactor DO Dly N/A to MCE products sec 0.00 - 0.99
sec sec
0.00 - 2.00
0.00 - 9.99
0.00 - 5.00
0.00
0.00
0.00
0.00
sec 0.50 - 10.00
0.50
TRQ Lim Msg Dly Time duration drive is in torque limit before
Hit Torque Limit message displayed.
SER2 INSP SPD Defines the serial mode 2 Inspection
(only serial mode 2)
SER2 RS CRP SPD Creep speed used in “rescue mode” ft/ min ft/ min
0 - 100
0 - 100
30
10
SER2 RS CPR Time Maximum time drive will continue to run at rescue creep speed (only serial mode 2)
SER2 FLT TOL Maximum time that may elapse between valid run time messages before a serial fault is declared (only serial mode 2) sec 0 - 200 sec 0.0 - 2.0
Rollback Gain
Notch Filter Frq
Notch Filt Depth
MSPD Delay 1-4
Anti-rollback gain
Notch Filter Center Frequency
Notch filter maximum attenuation
Recognition time delay for a defined multistep speed command
-
Hz
%
1 - 99
5 - 60
0 - 100 sec 0.00 - 10.0
180
0.04
1
20
0
0.00
A2 S-Curves
Accel Rate 0
Decel Rate 0
Accel Jerk in 0
Accel Jerk out 0
Acceleration rate #0 ft/s
2
Deceleration rate #0 ft/s
2
Rate of increase of acceleration, up to ACCEL
Rate, when increasing elevator speed ft/s
3
Rate of decrease of acceleration to zero when approaching contract elevator speed ft/s
3
0 - 7.99
0 - 3.999
0 - 8.0
0 - 8.0
3.00
3.00
8.0
8.0
A-7
A
Appendix
Table A.2 Magnetek AC Drive Table
# Display
Decel Jerk in 0
Decel Jerk out 0
Accel Rate 1
Decel Rate 1
Accel Jerk in 1
Accel Jerk out 1
Decel Jerk in 1
Decel Jerk out 1
Accel Rate 2
Decel Rate 2
Accel Jerk in 2
Accel Jerk out 2
Decel Jerk in 2
Decel Jerk out 2
Accel Rate 3
Decel Rate 3
Accel Jerk in 3
Accel Jerk out 3
Decel Jerk in 3
Decel Jerk out 3
Parameter Description Unit
Rate of increase of deceleration, up to Decel
Rate, when decreasing elevator speed ft/s
3
Rate of decrease of deceleration to zero when slowing the elevator to leveling speed ft/s
3
Acceleration rate #1 ft/s
2
Deceleration rate #1 ft/s
2
Rate of increase of acceleration, up to ACCEL
Rate, when increasing elevator speed ft/s
3
Rate of decrease of acceleration to zero when approaching contract elevator speed ft/s
3
Rate of increase of deceleration, up to Decel
Rate, when decreasing elevator speed
Acceleration rate #2 ft/s
Rate of decrease of deceleration to zero when slowing the elevator to leveling speed ft/s
3 ft/s
3
2
Deceleration rate #2 ft/s
2
Rate of increase of acceleration, up to ACCEL
Rate, when increasing elevator speed ft/s
3
Rate of decrease of acceleration to zero when approaching contract elevator speed ft/s
3
Rate of increase of deceleration, up to Decel
Rate, when decreasing elevator speed
Acceleration rate #3
Deceleration rate #3 ft/s
Rate of decrease of deceleration to zero when slowing the elevator to leveling speed ft/s
3 ft/s
3
2 ft/s
2
Rate of increase of acceleration, up to ACCEL
Rate, when increasing elevator speed ft/s
3
Rate of decrease of acceleration to zero when approaching contract elevator speed ft/s
3
Rate of increase of deceleration, up to Decel
Rate, when decreasing elevator speed ft/s
3
Rate of decrease of deceleration to zero when slowing the elevator to leveling speed ft/s
3
Range
0 - 8.0
0 - 8.0
0 - 7.99
0 - 7.99
0 - 8.0
0 - 8.0
0 - 8.0
0 - 8.0
0 - 7.99
0 - 7.99
0 - 8.0
0 - 8.0
0 - 8.0
0 - 8.0
0 - 7.99
0 - 7.99
0 - 8.0
0 - 8.0
0 - 8.0
0 - 8.0
A3 Multistep Ref
Speed Command 1 Multi-Step Speed command #1
Speed Command 2 Multi-Step Speed command #2
Speed Command 3 Multi-Step Speed command #3
Speed Command 4 Multi-Step Speed command #4
Speed Command 5 Multi-Step Speed command #5
Speed Command 6 Multi-Step Speed command #6
Speed Command 7 Multi-Step Speed command #7
Speed Command 8 Multi-Step Speed command #8
Speed Command 9 Multi-Step Speed command #9
Speed Command 10 Multi-Step Speed command #10 ft/m ft/m ft/m ft/m ft/m ft/m ft/m ft/m ft/m ft/m
0
0
0
0
0
0
0
0
0
0
8.0
8.0
8.0
8.0
8.0
3.00
3.00
8.0
3.00
3.00
8.0
8.0
MCE Def Field Set
8.0
8.0
3.00
3.00
8.0
8.0
8.0
8.0
A-8 Manual # 42-02-2P25
Motion 4000
Magnetek Parameters Table
Table A.2 Magnetek AC Drive Table
# Display Parameter Description
Speed Command 11 Multi-Step Speed command #11
Speed Command 12 Multi-Step Speed command #12
Speed Command 13 Multi-Step Speed command #13
Speed Command 14 Multi-Step Speed command #14
Speed Command 15 Multi-Step Speed command #15
Unit
ft/m ft/m ft/m ft/m ft/m
Range
0
0
0
0
0
MCE Def Field Set
A4 Power Convert
Id Reg Diff gain Flux Current regulator differential gain
Id Reg Prop Gain Flux current regulator proportional gain
Iq Reg Diff Gain Torque current regulator differential gain
Iq Reg Prop Gain Torque current regulator proportional gain
PWM Frequency
UV Alarm Level
Carrier frequency
Level for undervoltage alarm
UV Fault Level Level for undervoltage fault
Extern Reactance External choke reactance
Input L-L Volts Nominal line-line AC input Voltage, RMS
A5 Motor
Motor ID Motor Identification
Rated Mtr Power
Rated Mtr Volts
Rated motor output power
Rated motor terminal RMS voltage
Rated Excit Freq Rated excitation frequency
Rated Motor Curr Rated motor current
Motor Poles Motor poles
Rated Mtr Speed Rated motor speed at full load
% No Load Curr Percent no load current
Stator Leakage X Stator leakage reactance
Rotor Leakage X
Stator Resist
Rotor leakage reactance
Stator resistance
Motor Iron Loss Iron loss at rated frequency
Motor Mech Loss Mechanical loss at rated frequency
Ovld Start Level
Ovld Time Out
Flux Sat Break
Flux Sat Slope 1
Flux Sat Slope 2
Maximum continuous motor current
Time that defines motor overload curve
Flux saturation curve slope change point
Flux saturation curve slope for low fluxes
Flux saturation curve slope for high fluxes
-
-
-
-
0.80 - 1.20
0.20 - 0.40
0.80 - 1.20
0.20 - 0.40
kHz 2.5 - 16.0
% 80 - 99
%
%
50 - 88
0 - 10 volts 110 - 480
1.00
0.30
1.00
0.30
10.0
80
80
0
Drive dep.
4 Pole DFLT, 6
Pole DFLT,
MCE Test
MCE Test
HP 1.0 - 500 Per Job volts 190.0 - 575.0 Per Job
Hz 5.0 - 400.0
Per Job amps 1.00 - 800.00 Per Job
%
%
%
%
2 - 32 Per Job
RPM 50.0 - 3000.0 Per Job
%
%
10.0 - 60.0
0 - 20.0
Per Job
Per Job
0 - 20.0
0 - 20.0
0 - 15.0
0 - 15.0
Per Job
Per Job
Per Job
Per Job
% 100 - 150 sec 5.0 - 120.0
%
%
%
0 - 100
0 - 200.0
0 - 200.0
Per Job
Per Job
Per Job
Per Job
Per Job
A
A-9
Appendix
Table A.2 Magnetek AC Drive Table
# Display Parameter Description
Configure C0
C1 User Switches
Spd Command Src Speed Command Source
Unit Range MCE Def Field Set
Run Command Src Run Command Source
Hi/Lo Gain Src High / low gain change switch source
Speed Reg Type Chooses speed regulator -
Motor Rotation Allows user to reverse direction of motor rotation
-
Spd Ref Release Determines when speed reference release is asserted
Cont Confirm Src Enables external logic input for contactor confirmation.
-
-
Pre Torque Source Enables and determines the source of the pre torque command
-
Pre Torque Latch Determines if analog pre-torque command is latched
-
PT torq Latch Clck Determines source of pre torque latch control
(if used)
-
Fault Reset Src Fault reset source -
Overspd Test Src Determines external logic source to trigger overspeed test
Brake Pick Src If drive controls mechanical brake, determines source of brake pick command
-
-
Brake Pick Cnfrm Enables a logic input to use for brake pick confirmation
-
Brake Hold Src If drive controls mechanical brake, determines source of brake hold command
-
Ramped Stop Sel Selects normal stop or torque ramp down stop -
Ramp Down En Src Determines the source that signals the torque ramp down stop (if used)
-
Brk Pick Flt Ena
Brk Hold Flt Ena
Brake pick fault enable
Brake hold fault enable
Ext Torq Cmd Src When Speed Reg Type = External Reg, sets the source of the torque command
-
-
-
-
-
-
External TB
Serial
External TB
Serial
Automatic
External TB
Serial
Internal
Serial
None
External TB
Internal
Serial
None
Ramp on stop
External TB
Run logic
Serial
Enable
Disable
Enable
Disable
None
Serial
Analog input
Multi-step
Serial
External TB
Serial
Serial+extern
External TB 1
Serial
Internal
Elev spd reg
Pi speed reg
Forward
Reverse
Reg release
Brake picked
None
External TB
None
Analog input
Serial
Not latched
Latched
Multi-step Serial
External
TB1
Internal
Elev spd reg
Forward
Reg release
None
None
Not latched
External tb
External tb
External tb
Internal
None
Internal
None
External tb
Disable
Disable
None
Serial
A-10 Manual # 42-02-2P25
Motion 4000
Magnetek Parameters Table
Table A.2 Magnetek AC Drive Table
# Display
Dir Confirm
S-Curve Abort
Fast Flux
Main DIP Ena
DB Protection
Encoder Fault
Stopping Mode
Motor Ovrld Sel
Auto Stop
Serial Mode
SER2 FLT Mode
DRV Fast Disable Addresses how fast the drive responds to the
MLT-SPD to DLY1 Assigns multi-step speed command to recog-
MLT-SPD to DLY2
MLT-SPD to DLY3
MLT-SPD to DLY4
Parameter Description
Confirms proper analog signal polarity when enabled and a logic input is programmed to
Run Up and Run Down
Addresses how the S-Curve Speed Reference
Generator handles a reduction in the speed command before the S-Curve Generator has reached its target speed.
Reduces starting takeoff time by reducing motor fluxing time
-
-
-
Enables the Mains DIP Speed (A1) parameter that reduces speed when an undervoltage alarm is declared
-
Dynamic braking Protection fault or alarm selection
Temporarily disables the Encoder Fault -
Unit
Determines stopping mode when Spd Command Src = multi-step
Motor Overload Selection
Auto Stop Function enable
Serial Protocol selection
Defines reaction to a serial communication fault while in Serial Mode 2 (Only serial mode
2)
-
-
-
-
-
Range
Enabled
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
Disabled
Fault
Alarm
Enabled
Disabled
Immediate
Ramp to stop
Alarm
Flt Immediate
Fault at Stop
Disable
Enable
Mode 1
Mode 2
Mode 2 test immediate removal of Drive Enable logic input. nition delay timer 1
Assigns multi-step speed command to recognition delay timer 1
Assigns multi-step speed command to recognition delay timer 1
Assigns multi-step speed command to recognition delay timer 1
-
-
-
-
-
Disable
None
None
None
None
MCE Def Field Set
Disabled
Disabled
Enabled
Disabled
Fault
Enabled
Immediate
Alarm
Disable
Mode 1
Immediate
Run remove rescue
Disable
Enable
None mspd1mspd15
None mspd1mspd15
None mspd1mspd15
None mspd1mspd15
C2 Logic Inputs
Log In 1 TB1-1 Terminal 1 Selection -
Log In 2 TB1-2 Terminal 2 Selection -
DRIVE
ENABLE
RUN UP
A
A-11
Appendix
Table A.2 Magnetek AC Drive Table
# Display
Log In 3 TB1-3
Log In 4 TB1-4
Log In 5 TB1-5
Log In 6 TB1-6
Log In 7 TB1-7
Log In 8 TB1-8
Log In 9 TB1-9
Parameter Description
Terminal 3 Selection
Terminal 4 Selection
C3 Logic Outputs
Log Out 1 tb1-14 Terminal 14 Selection
Log Out 2 tb1-15 Terminal 15 Selection
Log Out 3 tb1-16 Terminal 16 Selection
Log Out 4 tb1-17 Terminal 17 Selection
Relay Coil 1
Relay Coil 2
Terminal 5 Selection
Terminal 6 Selection
Terminal 7 Selection
Terminal 8 Selection
Terminal 9 Selection
Relay 1 Function Selection
Relay 2 Function Selection
C4 Analog Outputs
Ana Out 1 tb1-33 Terminal 33 Selection -
Ana Out 2 tb1-35 Terminal 35 Selection
Utility U0
U1 Password
U2 Hidden Items
U3 Unit
U4 Overspeed Test
-
Password -
Enable or disable hidden parameters
Enable Disable
Unit for parameters
English Metric
Allows overspeed test during inspection
Yes No
-
-
-
-
-
-
Unit
-
Range
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
SPEED
CMD
SPEED
FEEDBK
000000
ENABLE
ENGLISH
No
MCE Def Field Set
RUN
DOWN
FAULT
RESET
STEP REF
B0
STEP REF
B1
STEP REF
B2
STEP REF
B3
S-CURVE
SEL 0
NO
FUNC-
TION
NO
FUNC-
TION
NO
FUNC-
TION
NO
FUNC-
TION
NO
FUNC-
TION
NO
FUNC-
TION
SPEED
DEV LOW
NO
FUNC-
TION
RUN COM-
MAND
NO
FUNC-
TION
MTR
OVER-
LOAD
NO
FUNC-
TION
ENCODER
FAULT
NO
FUNC-
TION
FAULT
SPEED
REG RLS
A-12 Manual # 42-02-2P25
Motion 4000
Table A.2 Magnetek AC Drive Table
# Display
U5 Restore Dflts
U6 Drive Info
U7 HEX Monitor
Parameter Description
Reset all parameters to default values
Drive information:
Drive Version:
Boot Version:
Cube ID:
Drive Type:
Hex Monitor
Magnetek Parameters Table
Unit Range MCE Def Field Set
A
A-13
Appendix
F7 Settings Record
Please use the following table to record your F7 menu settings. If the TC-MPI board is replaced in the future, this will provide you a quick way to re-enter proper settings. Also, if you place a support call to MCE, these values are information you will need to speed problems solving.)
Table A.3 F7 Parameter Log
1
2
3-
64
ID# Description
Floor 1 (bottom floor served)
Floor 2 (next floor ascending)
Floors in ascending order
Setting
65
66
67
68
Bottom Access Distance: Distance in Inches from bottom floor to virtual bottom access uptravel limit switch position.
Top Access Distance: Distance in Inches from top floor to virtual top access down-travel limit switch position.
Counterweight Position: Distance in Inches above the bottom floor at which the counterweight is adjacent to the car. Learned through
F6 menu. May be adjusted here.
Directional Limit Distance: Distance in Inches at which the virtual direction limit switches are positioned beyond the terminal floor level positions.
69
70
71
72
U/DETS Option: If up and down emergency terminal switches are positioned in software by the system, they are Virtual. If mechanical switches are installed, they are Physical. If emergency terminal switches are not used, select Unused.
U/DNT1 Option: If up and down position 1 normal terminal switches are positioned in software by the system, they are Virtual. If mechanical switches are installed, they are
Physical. If position 1 normal terminal switches are not used, select Unused.
U/DNT2 Option: If up and down position 2 normal terminal switches are positioned in software by the system, they are Virtual. If mechanical switches are installed, they are
Physical. If position 2 normal terminal switches are not used, select Unused.
U/DNT3 Option: If up and down position 3 normal terminal switches are positioned in software by the system, they are Virtual. If mechanical switches are installed, they are
Physical. If position 3 normal terminal switches are not used, select Unused.
A-14 Manual # 42-02-2P25
Motion 4000
Table A.3 F7 Parameter Log
ID#
73
74
Description
U/DNT4 Option: If up and down position 4 normal terminal switches are positioned in software by the system, they are Virtual. If mechanical switches are installed, they are
Physical. If position 4 normal terminal switches are not used, select Unused.
U/DNT5 Option: If up and down position 5 normal terminal switches are positioned in software by the system, they are Virtual. If mechanical switches are installed, they are
Physical. If position 5 normal terminal switches are not used, select Unused.
75
76
77
78
UETS Speed: Speed in feet per minute which the car must be below when tripping the up emergency terminal switch. Must never be in excess of 95% of contract speed. Determined by contract speed and position of the switch.
UETS Distance: Distance in Inches from the top terminal floor level position at which the up emergency terminal switch is positioned.
Approximately half the distance needed by the drive to decelerate to zero speed from contract speed.
UETS Delta Distance: Distance in Inches on either side of the up emergency terminal switch position inside which the car must detect the up emergency terminal switch. If not, the car will perform an emergency stop.
UETS Delta Speed: Delta speed is generally unused in applications below 400 FPM. Delta
Speed provides an “adder” to UETS speed.
UETS speed and Delta speed together may not exceed 95% of contract speed. If you are tripping an ETS fault during car setup, you can choose to use this adder or you can choose to temporarily disable the ETS switches by setting them to Unused until you have sufficient control of the car.
79
80
81
UNTS1 Speed: Speed in feet per minute which the car must be below when tripping the
UNTS1 switch.
UNTS1 Distance: Distance in inches from the top terminal floor level position at which a virtual UNTS1 switch is positioned.
UNTS1 Delta Distance: Distance in inches on either side of the UNTS1 switch inside which the car must detect the switch. If not, the car will perform an emergency slow down.
F7 Settings Record
Setting
A
A-15
Appendix
Table A.3 F7 Parameter Log
ID#
82
83
Description
UNTS1 Delta Low Speed: Along with the Delta
High Speed setting, determines a speed range which the car must be within to avoid causing an emergency slow down.
UNTS1 Delta High Speed: Along with the Delta
Low Speed setting, determines a speed range which the car must be within to avoid causing an emergency slow down.
84 UNTS2 Speed (See UNTS1)
85 UNTS2 Distance (See UNTS1)
86 UNTS2 Delta Distance (See UNTS1)
87 UNTS2 Delta Low Speed (See UNTS1)
88 UNTS2 Delta High Speed (See UNTS1)
89 UNTS3 Speed (See UNTS1)
90 UNTS3 Distance (See UNTS1)
91 UNTS3 Delta Distance (See UNTS1)
92 UNTS3 Delta Low Speed (See UNTS1)
93 UNTS3 Delta High Speed (See UNTS1)
94 UNTS4 Speed (See UNTS1)
95 UNTS4 Distance (See UNTS1)
96 UNTS4 Delta Distance (See UNTS1)
97 UNTS4 Delta Low Speed (See UNTS1)
98 UNTS4 Delta High Speed (See UNTS1)
99 UNTS5 Speed (See UNTS1)
100 UNTS5 Distance (See UNTS1)
101 UNTS5 Delta Distance (See UNTS1)
102 UNTS5 Delta Low Speed (See UNTS1)
103 UNTS5 Delta High Speed (See UNTS1)
104
105
DETS Speed: Speed in feet per minute which the car must be below when tripping the down emergency terminal switch. Must never be in excess of 95% of contract speed. Determined by contract speed and position of the switch.
DETS Distance: Distance in Inches from the bottom terminal floor level position at which the down emergency terminal switch is positioned. Approximately half the distance needed by the drive to decelerate to zero speed from contract speed.
A-16 Manual # 42-02-2P25
Setting
Motion 4000
Table A.3 F7 Parameter Log
ID#
106
107
Description
DETS Delta Distance: Distance in Inches on either side of the down emergency terminal switch position inside which the car must detect the down emergency terminal switch. If not, the car will perform an emergency stop.
DETS Delta Speed: Delta speed is generally unused in applications below 400 FPM. Delta
Speed provides an “adder” to DETS speed.
DETS speed and Delta speed together may not exceed 95% of contract speed. If you are tripping an ETS fault during car setup, you can choose to use this adder or you can choose to temporarily disable the ETS switches by setting them to Unused until you have sufficient control of the car.
108
109
110
111
112
DNTS1 Speed: Speed in feet per minute which the car must be below when tripping the
DNTS1 switch.
DNTS1 Distance: Distance in inches from the bottom terminal floor level position at which a virtual DNTS1 switch is positioned.
DNTS1 Delta Distance: Distance in inches on either side of the DNTS1 switch inside which the car must detect the switch. If not, the car will perform an emergency slow down.
DNTS1 Delta Low Speed: Along with the Delta
High Speed setting, determines a speed range which the car must be within to avoid causing an emergency slow down.
DNTS1 Delta High Speed: Along with the Delta
Low Speed setting, determines a speed range which the car must be within to avoid causing an emergency slow down.
113 DNTS2 Speed (See DNTS1)
114 DNTS2 Distance (See DNTS1)
115 DNTS2 Delta Distance (See DNTS1)
116 DNTS2 Delta Low Speed (See DNTS1)
117 DNTS2 Delta High Speed (See DNTS1)
118 DNTS3 Speed (See DNTS1)
119 DNTS3 Distance (See DNTS1)
120 DNTS3 Delta Distance (See DNTS1)
121 DNTS3 Delta Low Speed (See DNTS1)
122 DNTS3 Delta High Speed (See DNTS1)
123 DNTS4 Speed (See DNTS1)
124 DNTS4 Distance (See DNTS1)
125 DNTS4 Delta Distance (See DNTS1)
F7 Settings Record
Setting
A
A-17
Appendix
Table A.3 F7 Parameter Log
ID# Description
126 DNTS4 Delta Low Speed (See DNTS1)
127 DNTS4 Delta High Speed (See DNTS1)
128 DNTS5 Speed (See DNTS1)
129 DNTS5 Distance (See DNTS1)
130 DNTS5 Delta Distance (See DNTS1)
131 DNTS5 Delta Low Speed (See DNTS1)
132 DNTS5 Delta High Speed (See DNTS1)
133
134
135
136
138
139
Brake Pick Delay: Time in milliseconds after the drive enable command is issued before the brake should pick.
Speed pick delay: The time in milliseconds after the brake is picked before the speed command is issued.
Brake Hold Delay: After take off, the brake is held fully picked until this timer expires, at which point it settles to hold position/voltage.
Brake Drop Delay: Delay in milliseconds that the brake should be delayed from dropping after the speed command is dropped.
Drive disable Delay: The time in milliseconds after stopping at a floor which the drive should maintain electrical control of the motor.
Speed hysteresis Delay: Provides a delay between when the speed command is issued and when it begins to accelerate the load.
140
141
142
143
Profile Advance: Advances application of the curve but with no speed command issued.
Profile Scale: Scales the curve to affect all associated speed settings. i.e., 50% of Standard pattern would reduce Contract and other associated speeds to 50% of their value.
Standard Slew Slope: Determines how aggressively or gradually the current speed transitions to zero speed. Sets the maximum deceleration rate that the S curve is allowed to command when the car is stopping from a speed near releveling speed or lower. If the stop is harsh, reducing this value may provide a softer stop.
Danger Slew Slope: Determines how aggressively or gradually the current speed can transition to a lower or higher speed. Sets the maximum rate of acceleration/deceleration the
S curve is allowed to command when the car is running and when the car is stopping from a speed greater than releveling speed. Reducing this value forces a more gradual transition.
A-18 Manual # 42-02-2P25
Setting
Motion 4000
Table A.3 F7 Parameter Log
ID#
144
Description
Slew Filter: Smooths any harsh transitions in the commanded speed. Reducing this value causes a smoother transition.
145
146
147
Contract Overspeed: Setting in feet per minute above contract speed at which a contract overspeed is detected.
Inspection Overspeed: Setting in feet per minute above inspection speed at which an inspection overspeed is detected and an emergency stop initiated.
Leveling Overspeed: Setting in feet per minute above leveling speed at which a leveling overspeed is detected and an emergency stop initiated.
148
149
Hoist-motor Speed: Setting in drive sheave
RPM at which the car achieves contract speed.
Contract Speed: Contract speed of the car in feet per minute.
151 Intermediate Speed
152 Earthquake Speed
153 Auxiliary Speed
154 Backup power speed
155 Inspection Speed (Normal)
156 Inspection Speed (Reduced)
157 Correction Speed
158 Leveling Speed
159 Releveling Speed
160 Leveling Distance
161 Releveling distance
162 Proximity distance
165 Standard Start Jerk
166 Standard Roll Jerk
167 Standard Stop Jerk
168 Standard Acceleration
169 Standard Deceleration
170 Manual Start Jerk
171 Manual Roll Jerk
172 Manual Stop Jerk
173 Manual Acceleration
174 Manual Deceleration
F7 Settings Record
Setting
A
A-19
Appendix
Table A.3 F7 Parameter Log
ID# Description
175 Danger Start Jerk
176 Danger Roll Jerk
177 Danger Stop Jerk
178 Danger Deceleration
179 Alternate Start Jerk
180 Alternate Roll Jerk
181 Alternate Stop Jerk
182 Alternate Acceleration
183 Alternate Deceleration
Setting
185 Brake Type Option
186 Emergency Brake Option
187 Reduced Inspect Speed
188 Unintended Motion
189 Following error
190 Sheave Brake Idle Delay
191 Landing System
192
Speed Drop Delay: Magnetek drives only. Time in milliseconds during which the drive should continue to exert motor control after the car has achieved the floor and before the brake has dropped.
193
Profile Compensation:
Dynamic: Variable, controller determined compensation for drive lag based on entry in parameter 140, Profile Advance.
Fixed: Fixed compensation for drive lag using the parameter 140, Profile Advance setting.
194 Normal Brake Pick Voltage
195 Normal Brake Hold Voltage
196 Normal Brake Relevel Voltage
197 Normal Brake Lift Rate
198 Normal Brake Drop Rate
199 Emergency Brake Type
200 Emergency Brake Pick Voltage
201 Emergency Brake Hold Voltage
202 Directional Limit Type
203 Landing Floor Checksum
204 Landing System ETS Overspeed
205 Inspection Slew Filter
206 Battery Backup Speed
Read Only. Stored when floors are learned.
A-20 Manual # 42-02-2P25
Motion 4000
General Settings Log
General Settings Log
Program Mode (F1) Parameter Settings Record
OPTIONS CURRENT VALUES NEW VALUES
Controller Type:
Simplex / Local or Duplex?
Operation:
Top Landing Served (This car)?
Walk Thru Doors this Car (This car)
Car Serves Frnt/Flr (This car)?
BASIC FEATURES
___ Hydro (M2000) ___ Traction (M4000)
___ Simplex ___ Local ___ Duplex
___ Sel. Coll. ___ Single Button
___ Single Auto PB
_____ Yes ______ No
1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31 32
1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31 32
___ Hydro (M2000) ___ Traction (M4000)
___ Simplex ___ Local ___ Duplex
___ Sel. Coll. ___ Single Button
___ Single Auto PB
_____ Yes ______ No
1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31 32
1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31 32
Car Serves Rear/Flr (This car)?
Top Landing Served (Other car)?
Walk Thru Doors Other Car (Other car)
Other Car Serves Frnt/Flr?
_____ Yes ______ No
1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31 32
1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31 32
_____ Yes ______ No
1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31 32
1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31 32
Other Car Serves Rear/Flr?
Parking Floor
Alt. Parking Floor
Secondary Park Floor
Lobby Floor
Car Identifier
Serial COP Board HC-CPI?
Discrete PIs on UIO?
Dedicated PI Board?
Serial Cartop Door CNTRL?
Disable Local Hall Calls?
Set first car to A, next car to B, etc.
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
FIRE SERVICE
_____ Yes ______ No
Set first car to A, next car to B, etc.
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No Fire Service Operation?
Fire Phase 1 Main Floor
Fire Phase 1 Alt. Floor
Fire Service Code
Fire Phase 1, 2 nd
Alt Landing
Will This Car Run on PH2?
Bypass Stop Sw. on Phase 1?
Honeywell Fire Operation?
NYC Fire Phase 2 w/ ANSI 89?
White Plains, NY Fire Code?
Mass 524 CMR Fire Code?
ASME A17.1A 200x Addenda?
Disable DPM on Fire PH.2?
Low Voltage Fire Sensor?
Fire Hat Status
Nudging?
Stuck Photo Eye Protection?
Sequential Door Oper.(F/R)?
Car Call Cancels Door Time?
Nudging During Fire Phase 1?
Retiring Cam Option?
Pre-Opening?
Mechanical Safety Edge?
Nudging Output/Buzzer Only?
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ None ______ 2005 ______ 2007
_____ Yes ______ No
_____ Yes ______ No
Dynamic/Latch Flashing/Latch Initial
DOOR OPERATION
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ None ______ 2005 ______ 2007
_____ Yes ______ No
_____ Yes ______ No
Dynamic/Latch Flashing/Latch Initial
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
A
A-21
Appendix
Program Mode (F1) Parameter Settings Record
OPTIONS
D.C.B. Cancels Door Time?
Leave Door Open on MGS (Traction only)
Leave Door Open on PTI/ESS?
Nudging During Fire Phase 2?
Dir. Preference Until DLK?
Fully Manual Doors?
Cont. D.C.B. to Close Doors?
Cont. D.C.B. for Fire Phase 1?
Moment. D.O.B. door opening?
Moment D.O.B. for:
Moment D.O.B. for:
Doors to open if parked?
Doors to Open on Main Fire?
Doors to Open on Alt. Fire?
Leave Doors Open on CTL
Limited Door Re-Open Option
Reduce HCT with Photo Eye
Leave Doors Open on EPI
Doors to open if No demand?
Const. Press Op. Bypass PHE?
Door Type is?
Front Door Mech. Coupled?
Rear Door Mech. Coupled?
Prevent DCP Till Doors Close:
Moment D.C.B to Close Doors?
Doors to Latch DOF?
Doors to Latch DCF?
Inv. Door Close Limit?
Fire PH2 with Doors Closed?
Short Door Timer
Car Call Door Timer
Hall Call Door Timer
Lobby Door Timer
Nudging Timer
Time out of Service Timer
Motor Limit Timer
MGR Output Timer (Traction only)
Door Hold Input Timer
Parking Delay Timer
Fan/Light Output Timer
Hospital Emerg. Timer Unit?
Hospital Emerg. Timer
Door Open Protection Timer
CTL Door Open Timer
Door Buzzer Timer
Opn/Cls Intrlock Timer
Fire PH1 Reclose Timer?
Mounted in hall or car?
Double strike on Down?
PFG Enable Button?
Main Egress Floor
Egress Floor Arrival Gong?
Car lantern Door Fully Open?
CURRENT VALUES
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
______ No
____Front ____Rear ____Both Doors
____Hall Calls ____Car Calls ____All Calls
___None ___ Front ___ Rear ___ Both
___ Front ___ Rear ___ Both
___ Front ___ Rear ___ Both
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
___None ___ Front ___ Rear ___ Both
_____ Yes ______ No
_____ Horizontal ______ Vertical
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
___None ___ Front ___ Rear ___ Both
___None ___ Front ___ Rear ___ Both
___None ___ Front ___ Rear ___ Both
_____ Yes ______ No
TIMER
_____ seconds
_____ seconds
_____ seconds
_____ seconds
_____ seconds
___None_____ seconds
___None_____ minutes
_____ minutes
_____ seconds
_____ minutes
_____ minutes
_____minutes _____seconds
_____minutes _____seconds
_____ seconds
_____ seconds
_____ seconds
_____ milliseconds
_____ Yes ______ No
GONGS/LANTERNS
_____ Hall _____ Car
_____ Yes _____ No
_____ Yes _____ No
_____ No Main Egress Floor = _____
_____ Yes _____ No
NEW VALUES
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
______ No
____Front ____Rear ____Both Doors
____Hall Calls ____Car Calls ____All Calls
___None ___ Front ___ Rear ___ Both
___ Front ___ Rear ___ Both
___ Front ___ Rear ___ Both
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
___None ___ Front ___ Rear ___ Both
_____ Yes ______ No
_____ Horizontal ______ Vertical
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
_____ Yes ______ No
___None ___ Front ___ Rear ___ Both
___None ___ Front ___ Rear ___ Both
___None ___ Front ___ Rear ___ Both
_____ Yes ______ No
_____ seconds
_____ seconds
_____ seconds
_____ seconds
_____ seconds
___None_____ seconds
___None_____ minutes
_____ minutes
_____ seconds
_____ minutes
_____ minutes
_____minutes _____seconds
_____minutes _____seconds
_____ seconds
_____ seconds
_____ seconds
_____ milliseconds
_____ Yes ______ No
_____ Hall _____ Car
_____ Yes _____ No
_____ Yes _____ No
_____ No Main Egress Floor = _____
_____ Yes _____ No
A-22 Manual # 42-02-2P25
Motion 4000
General Settings Log
Program Mode (F1) Parameter Settings Record
OPTIONS CURRENT VALUES NEW VALUES
SPARE INPUTS
SPIN1 on HC-CTL-2 used for:
SPIN2 on HC-CTL-2 used for:
SPIN3 on HC-CTL-2 used for:
SPIN4 on HC-CTL-2 used for:
SPIN5 on HC-CTL-2 used for:
SPIN6 on HC-CTL-2 used for:
SPIN7 on HC-CTL-2 used for:
SPIN8 on HC-CTL-2 used for:
SPIN9 on HC-CTL-2 used for:
SPIN10 on HC-CTL-2 used for:
IO 1, UIO 32 used for:
IO 2, UIO 32 used for:
IO 3, UIO 32 used for:
IO 4, UIO 32 used for:
IO 5, UIO 32 used for:
IO 6, UIO 32 used for:
IO 7, UIO 32 used for:
IO 8, UIO 32 used for:
IO 1, UIO 33 used for:
IO 2, UIO 33 used for:
IO 3, UIO 33 used for:
IO 4, UIO 33 used for:
IO 5, UIO 33 used for:
IO 6, UIO 33 used for:
IO 7, UIO 33 used for:
IO 8, UIO 33 used for:
IO 1, UIO 34 used for:
IO 2, UIO 34 used for:
IO 3, UIO 34 used for:
IO 4, UIO 34 used for:
IO 5, UIO 34 used for:
IO 6, UIO 34 used for:
IO 7, UIO 34 used for:
IO 8, UIO 34 used for:
IO 1, UIO 35 used for:
IO 2, UIO 35 used for:
IO 3, UIO 35 used for:
IO 4, UIO 35 used for:
IO 5, UIO 35 used for:
IO 6, UIO 35 used for:
IO 7, UIO 35 used for:
IO 8, UIO 35 used for:
IO 1, UIO 36 used for:
IO 2, UIO 36 used for:
IO 3, UIO 36 used for:
IO 4, UIO 36 used for:
IO 5, UIO 36 used for:
IO 6, UIO 36 used for:
IO 7, UIO 36 used for:
IO 8, UIO 36 used for:
CPI F I10
CPI F I11
CPI F I12
CPI F I13
A-23
A
Appendix
Program Mode (F1) Parameter Settings Record
OPTIONS CURRENT VALUES NEW VALUES
CPI F I14
CPI F I15
CPI F I16
CPI R I10
CPI R I11
CPI R I12
CPI R I13
CPI R I14
CPI R I15
CPI R I16
CPI X I1
CPI X I2
CPI X I3
CPI X I4
CPI X I5
CPI X I6
CPI X I7
SPOUT1 used for:
SPOUT2 used for:
SPOUT3 used for:
SPOUT4 used for:
IO 9, UIO 32 used for:
IO 10, UIO 32 used for:
IO 11, UIO 32 used for:
IO 12, UIO 32 used for:
IO 13, UIO 32 used for:
IO 14, UIO 32 used for:
IO 15, UIO 32 used for:
IO 16, UIO 32 used for:
IO 9, UIO 33 used for:
IO 10, UIO 33 used for:
IO 11, UIO 33 used for:
IO 12, UIO 33 used for:
IO 13, UIO 33 used for:
IO 14, UIO 33 used for:
IO 15, UIO 33 used for:
IO 16, UIO 33 used for:
IO 9, UIO 34 used for:
IO 10, UIO 34 used for:
IO 11, UIO 34 used for:
IO 12, UIO 34 used for:
IO 13, UIO 34 used for:
IO 14, UIO 34 used for:
IO 15, UIO 34 used for:
IO 16, UIO 34 used for:
IO 9, UIO 35 used for:
IO 10, UIO 35 used for:
IO 11, UIO 35 used for:
IO 12, UIO 35 used for:
IO 13, UIO 35 used for:
IO 14, UIO 35 used for:
IO 15, UIO 35 used for:
SPARE OUTPUTS
A-24 Manual # 42-02-2P25
Motion 4000
General Settings Log
Program Mode (F1) Parameter Settings Record
OPTIONS CURRENT VALUES NEW VALUES
SPARE OUTPUTS
CPI R O10
CPI R O11
CPI R O12
CPI R O13
CPI R O14
CPI R O15
CPI R O16
CPI X O1
CPI X O2
CPI X O3
CPI X O4
CPI X O5
CPI X O6
CPI X O7
IO 16, UIO 35 used for:
IO 9, UIO 36 used for:
IO 10, UIO 36 used for:
IO 11, UIO 36 used for:
IO 12, UIO 36 used for:
IO 13, UIO 36 used for:
IO 14, UIO 36 used for:
IO 15, UIO 36 used for:
IO 16, UIO 36 used for:
CPI F O10
CPI F O11
CPI F O12
CPI F O13
CPI F O14
CPI F O15
CPI F O16
EXTRA FEATURES
_____1 wire _____Binary 0 _____Binary 1
_____ Yes _____ No
_____1 wire _____Binary 0 _____Binary 1
_____ Yes _____ No
PI Output Type:
Intermediate Speed
Emergency Power Return Floor
Emergency Power Operation?
Consec Stops w/o PHE Limit?
Light Load Weighing?
Photo Eye Anti-Nuisance?
Dedicated Card Reader Security?
Card Reader Inputs
(Dedicated Card Reader)
MG Shutdown Operation (Traction only)
IND Cancel Calls On Stop?
WPIA Landing?
WPIB Landing?
WPIC Landing?
WPID Landing?
WPIE Landing?
WPIF Landing?
WPIG Landing?
WPIH Landing?
Allow Car Calls on WP Sec?
Cancel Both Hall (U/D) Calls?
Retain Calls On CTL/CTF?
__ No Emergency Power Return Floor = ___
__ No Light Load Car Call Limit = ____
__ No Consec Stops w/o PHE Limit = ___
_____ Yes _____ No
___Stkd ___FHC ___FCC ___RHC ___RCC
_____ MGS Return Landing
_____ Yes _____ No
________ ________
________ ________
________ ________
________ ________
________ ________
________ ________
________ ________
________ ________
_____ Yes _____ No
_____ Yes _____ No
_____ Yes _____ No
__ No Emergency Power Return Floor = __
___ No Light Load Car Call Limit = ____
___ No Consec Stops w/o PHE Limit = ___
_____ Yes _____ No
___Stkd ___FHC ___FCC ___RHC ___RCC
_____ MGS Return Landing
_____ Yes _____ No
________ ________
________ ________
________ ________
________ ________
________ ________
________ ________
________ ________
________ ________
_____ Yes _____ No
_____ Yes _____ No
_____ Yes _____ No
A-25
A
Appendix
Program Mode (F1) Parameter Settings Record
OPTIONS CURRENT VALUES NEW VALUES
Automatic Floor Stop Option?
Auto Stop Doors Operation?
Car Call Cancel w/Dir. Reversal?
Cancel Car Calls Behind Car?
CE Electronics Board?
EMS Service Floor
Massachusetts EMS Service?
BSI Security Key
PI Turned off if No Demand?
Hospital Emerg. Operation (This car)
Hospital Calls Frnt/Flr (This car)?
Hospital Calls Rear/Flr (This car)?
Hospital Emerg. Operation (Other car)
Other Car Hospital Calls Frnt/Flr?
Other Car Hospital Calls Rear/Flr?
Fire Bypasses Hospital?
High Speed Delay After Run?
Single Speed AC Option? (Traction only)
Sabbath Operation?
Sabbath Up Calls Front Floor?
Sabbath Up Calls Rear Floor?
Sabbath Down Calls Front Floor?
Sabbath Down Calls Rear Floor?
Intermediate Speed between Floors?
Leveling Sensors
KCE
Analog Load Weigher?
Ind. Bypass Security?
Ats. Bypass Security?
Car to Floor Return Floor
Scrolling Speed
OFRP Between Flrs
Earthquake Operation?
First Lower/Run on EP Power
Enable Front DOB on Security?
Enable Rear DOB on Security?
Flr Count Below Flood Level?
Disable Top Flrs on PITFLD?
Earthquake Operation?
Earthquake Operation
First Lower/Run on EP Power
___ No Floor # for Car to Stop at:_____
_____Front _____ Rear _____Both
_____ Yes _____ No
_____ Yes _____ No
_____ Rev 1 _____ Rev 2
____No Floor # for Car to Stop at:_____
_____Front _____ Rear _____Both
_____ Yes _____ No
_____ Yes _____ No
_____ Rev 1 _____ Rev 2
_____No EMS Service Floor #:_____
___ Activated ___ Deactivated ___ Enabled
_____ Yes _____ No
_____ Yes _____ No
1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31 32
1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31 32
_____ Yes _____ No
1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31 32
1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31 32
_____ Yes _____ No
_____ Yes _____ No
_____ Yes _____ No
_____ Yes _____ No
1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31
1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31
2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18 19
20 21 22 23 24 25 26 27 28 29 30 31 32
2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18 19
20 21 22 23 24 25 26 27 28 29 30 31 32
2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18 19
20 21 22 23 24 25 26 27 28 29 30 31 32
___Enabled ____ Disabled
___Enabled ____ Disabled
___None ____ MCE____K-Tech
_____ Yes _____ No
_____ Yes _____ No
_____ Floor
___Slow ____ Normal ____Fast
_____ Floor _____ Floor
_____ Yes _____ No
_____ A _____ B
_____ Yes _____ No
_____ Yes _____ No
__________
_____ Yes _____ No
_____ Yes _____ No
___ ANSI Eq Op ___ California Eq Op
_____ A _____ B
ADDITIONAL CAR OPTIONS (Traction only)
_____No EMS Service Floor #:_____
___ Activated ___ Deactivated ___ Enabled
_____ Yes _____ No
_____ Yes _____ No
1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31 32
1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31 32
_____ Yes _____ No
1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31 32
1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31 32
_____ Yes _____ No
_____ Yes _____ No
_____ Yes _____ No
_____ Yes _____ No
1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31
1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31
2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18 19
20 21 22 23 24 25 26 27 28 29 30 31 32
2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18 19
20 21 22 23 24 25 26 27 28 29 30 31 32
2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 18 19
20 21 22 23 24 25 26 27 28 29 30 31 32
___ Enabled ____Disabled
___ Enabled ____Disabled
___None ____ MCE____K-Tech
_____ Yes _____ No
_____ Yes _____ No
_____ Floor
___Slow ____ Normal ____Fast
_____ Floor _____ Floor
_____ Yes _____ No
_____ A _____ B
_____ Yes _____ No
_____ Yes _____ No
__________
_____ Yes _____ No
_____ Yes _____ No
___ ANSI Eq Op ___ California Eq Op
_____ A _____ B
ETS Switches Required?
Hoistway Access?
Door Position Monitor
Front Door Close Limit?
Rear Door Close Limit?
_____ Yes _____ No
_____ Yes _____ No
____ None ____Front ____ Rear ____Both
____ None _____DCL____ GS+DCAB
____ None _____DCL____ GS+DCAB
_____ Yes _____ No
_____ Yes _____ No
____ None ____Front ____ Rear _____Both
____ None _____DCL____ GS+DCAB
____ None _____DCL____ GS+DCAB
A-26 Manual # 42-02-2P25
Motion 4000
Floor Settings Log
Floor Settings Log
This table is provided so that you can record floor heights and offsets if desired. .
Table A.4 Floor Height and Offset Notation
13
14
15
16
9
10
11
12
7
8
5
6
3
4
1
2
Floor Height Offset Floor
29
30
31
32
25
26
27
28
21
22
23
24
17
18
19
20
Height Offset
A
A-27
Appendix
Customer Notations
Table A.5 Customer Notation Area
A-28 Manual # 42-02-2P25
Motion 4000
R6 Regenerative Drive Reference
R6 Regenerative Drive Reference
This section includes quick reference information for the PowerBack R6 Regenerative AC drive.
Please refer to the R6 Regenerative drive manual provided with the product for detailed explanation of the parameters.
Table A.6 Quick Reference for PowerBack R6 Regenerative Drive
Display Parameter Description Setting Range Resolution
Field/MCE Set ting
WARNING: Do not change drive parameters while the elevator is running. Incorrect values can cause erratic elevator operation.
CP. 0
CP. 1
CP. 2
CP. 3
CP. 4
CP. 5
CP. 6
CP. 7
CP. 8
CP. 9
CP.10
CP.11
CP.12
CP.13
CP.14
CP.15
CP.16
CP.17
CP.18
CP.19
CP.20
CP.21
CP.22
CP.23
CP.24
CP.25
CP.26
CP.27
CP.28
CP.29
CP.30
CP.31
CP.32*
CP.33*
CP.34*
Password input
Status display
Main Line Frequency
AC-Phase current L1
AC-Phase current L2
AC-Phase current L3
Actual Load
Actual Load / peak value
DC output current
Actual DC voltage
DC voltage / peak value
Heat sink temperature
Overload counter
Active power
Total regen kWhr counter
Total motor kWhr counter
Total net kWhr counter
Apparent power / Line input
Analog output 1 / amplification factor
DC bus switching level
Auto error reset counter
Last Error
Last Error 1
Last Error 2
Last Error 3
Last Error 4
Last Error 5
Last Error 6
Last Error 7
Software version
Software date code
Power part ID code
Pulse off Level
Operating Mode
Control Angle
0...9999
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
-20.00...20.00
+/- 30000.00
0...10
---
---
---
---
---
---
---
---
---
DDMM.Y
---
-100kW...0.0kW
0...3
0.0...60.0
1
---
0.1 Hz
0.1 A
0.1 A
0.1 A
1%
1%
0.1 A
1 V
1 V
1
0
C
1%
0.1kW
0.1 kWh
0.1 kWh
0.1 kWh
0.1 kVA
0.01
0.01
1
0.1kW
1
0.1
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
1.00
Set to 260 for 208 - 240Vac
Set to 600 for 460 - 480Vac
---
---
---
---
3
---
---
---
---
1.3
250
-0.8kW
0
29.0
A
A-29
Appendix
Manual Floor Setup, ELGO
All data modified through the controller F7 menu is stored on the TC-MPI board. This data includes the floor heights associated with the unique values on the ELGO tape. Each tape has unique value encoding. A value near the bottom of the tape provides the zero height reference setting at the first floor for the controller. For example, a tape value of 253,451 mm may be the zero inches reference for a first floor height. All numbers above or below are referenced to that value. If the TC-MPI board or ELGO tape is replaced the floor data must be re-learned or reentered.
If the working floor heights for the job were recorded, they can be used to manually set up floors instead of running a new learn operation.
1. On Inspection Operation, verify the car is exactly level with floor 1. This will be the zero reference.
2. Note the value displayed on the F3 Controller System menu, Elgo screen. For example:
• ELGO A 0000999 mm
• ELGO B 0000839 mm
3. Through the F5 Controller Utilities menu, Default TC-MPI parameters, default the MPI board.
4. Set the F6 switch up (all others down). The display will prompt ELGO LEARN, PRESS
NEXT TO CONTINUE.
5. Press N. The display will prompt: GO TO LANDING 1. PRESS SELECT.
6. Press S. The display will prompt you to enter an offset. You are exactly level with the floor so press N (DONE) without entering an offset.
7. The display will prompt you to move to the next floor and press SELECT. Instead, remain at the first floor but press S as though you had moved. When prompted for an offset value, simply press N (done).
8. Continue as described in Step 8 until all floors have been addressed. You will be prompted to move the car adjacent to the counterweight. Do so, then press N.
9. You will be prompted to store values. Press S to do so. Upon seeing the VALUES ARE
STORED. LEARN IS NOW COMPLETE message, set the F6 switch to the DOWN position.
F7 Entry
1. Obtain recorded floor heights to use as a reference.
2. Set the F7 switch UP (all others down).
3. Beginning with parameter 2 (Floor 2), re-enter floor height data for all floors.
4. Set the F7 switch DOWN.
5. Run the car to test landing accuracy. Adjust if needed.
A-30 Manual # 42-02-2P25
Motion 4000
Factory I/O Assignment, ICE-COP-2 Boards
Factory I/O Assignment, ICE-COP-2 Boards
COP-2 Board #1 - ID: 0
The first COP-2 board contains standard dedicated inputs as follows:
IO8
CRO
IO7
DOB
IO6
DCB
IO5
IND
IO4
FCCC
IO3
FCS
IO2 IO1
FCHLD FCOFF
The first COP-2 board contains standard dedicated outputs as follows:
IO16
CGEU
IO15 IO14
CGED SUA
IO13
SDA
IO12
FWL
IO11 IO10
FWI NDG
IO9
PFG
The first COP-2 board contains standard dedicated car calls (see note) as follows:
IO24
108
IO23
107
IO22
106
IO21
105
IO20
104
IO19
103
IO18
102
IO17
101
COP-2 Board #2 - ID: 1
The second COP-2 board contains standard dedicated car calls (see note) as follows:
IO8
116
IO7
115
IO6
114
IO5
113
IO4
112
IO3
111
IO2
110
IO1
109
IO16
124
IO15
123
IO14
122
IO13
121
IO12
120
IO11 IO10
119 118
IO9
117
IO24
132
IO23
131
IO22
130
IO21
129
IO20
128
IO19
127
IO18
126
IO17
125
A
Note
Note that the front car calls stack on each other. For example, if a car serves floors 1 through 3, does not serve floor 4, but does serve floors above 4, floors above floor 4 will move down one connection rather than leave an I/O open.
A-31
Appendix
COP-2 Board #3 - ID: 2
The third COP-2 board contains spare inputs as follows:
-
IO8 IO7
SPIN
IO6
SPIN
IO5
SPIN
IO4
SPIN
IO3
SPIN
IO2
SPIN
IO1
SPIN
The third COP-2 board contains spare outputs as follows:
IO16 IO15 IO14 IO13
SPOUT SPOUT SPOUT SPOUT -
IO12
-
IO11 IO10
-
IO9
-
IO24
-
IO23
-
IO22
-
IO21
-
IO20 IO19 IO18 IO17
SPOUT SPOUT SPOUT
COP-2 Board #4 - ID: 4
The fourth COP-2 board contains standard dedicated inputs as follows:
IO8
CRO
IO7 IO6
DOBR DCBR
IO5
IND
IO4
FCCC
IO3
FCS
IO2 IO1
FCHLD FCOFF
The fourth COP-2 board contains standard dedicated outputs as follows:
IO16 IO15 IO14
CGEUR CGEDR SUA
IO13
SDA
IO12
FWL
IO11 IO10
FWI NDGR
IO9
PFG
The fourth COP-2 board contains standard dedicated car calls (see note) as follows:
IO24
108R
IO23
107R
IO22
106R
IO21
105R
IO20
104R
IO19
103R
IO18
102R
IO17
101R
Note
Note that the rear car calls stack on each other. For example, if a car serves floors 1 through 3, does not serve floor 4, but does serve floors above 4, floors above floor 4 will move down one connection rather than leave an I/O open.
A-32 Manual # 42-02-2P25
Motion 4000
Factory I/O Assignment, ICE-COP-2 Boards
COP-2 Board #5 - ID: 5
The fifth COP-2 board contains standard dedicated car calls (see note) as follows:
IO8
116R
IO7
115R
IO6
114R
IO5
113R
IO4
112R
IO3
111R
IO2
110R
IO1
109R
IO16
124R
IO15
123R
IO14
122R
IO13
121R
IO12
120R
IO11 IO10
119R 118R
IO9
117R
IO24
132R
IO23
131R
IO22
130R
IO21
129R
IO20
128R
IO19
127R
IO18
126R
IO17
125R
COP-2 Board #6 - ID: 6
The sixth COP-2 board contains spare inputs as follows:
-
IO8 IO7
SPIN
IO6
SPIN
IO5
SPIN
IO4
SPIN
IO3
SPIN
IO2
SPIN
IO1
SPIN
The sixth COP-2 board contains spare outputs as follows:
IO16 IO15 IO14 IO13
SPOUT SPOUT SPOUT SPOUT -
IO12
-
IO11 IO10
-
IO9
-
IO24
-
IO23
-
IO22
-
IO21
-
IO20 IO19 IO18 IO17
SPOUT SPOUT SPOUT
A
Note
Note that the rear car calls stack on each other. For example, if a car serves floors 1 through 3, does not serve floor 4, but does serve floors above 4, floors above floor 4 will move down one connection rather than leave an I/O open.
A-33
Appendix
A-34 Manual # 42-02-2P25
Index
Symbols
0.LF.36 2-32, A-3
0.LF.50 2-33, A-4
0.LF.53 2-33, A-4
0.LF.54 2-33, A-4
1.LF.36 2-32, A-3
2.LF.50 2-33, A-4
2.LF.51 2-33, A-4
2.LF.55 2-33, A-4
A.LF.32 2-32, A-3
A.LF.33 2-32, A-3
AUTOMATIC FLOOR STOP OPTION 4-46
CC CANCEL W/DIR REVERSA 4-46
d.LF.31 2-32, A-3
d.LF.33 2-32, A-3
DOOR BUZZER TIMER 4-25
DOUBLE STRIKE ON DOWN 4-26
Encoder channel swap / direction 2-32, A-3
INV. DOOR CLOSE LIMIT 4-23
LF. 4 2-31, A-2
LF.10 2-31, A-2
LF.17 2-32, A-3
LF.20 2-32, A-3
LF.24 2-32, A-3
LF.25 2-34, A-5
LF.29 2-32, A-3
LF.37 2-32, A-4
LF.38 2-32, A-4
LF.43 2-33, A-4
LF.49 2-33, A-4
LF.61 2-33, A-4
LF.67 2-33, A-4
LF.69 2-33, A-4
LF.70 2-33, A-4
LF.71 2-33, A-4
LF.76 2-33, A-5
LF.77 2-33, A-5
LF.80 2-34, A-5
LF.81 2-34, A-5
LF.82 2-34, A-5
LF.87 2-34, A-5
LF.93 2-34, A-5
LF.96 2-34, A-5
LF.97 2-34, A-5
MOTOR LIMIT TIMER 4-24
P.LF.31 2-32, A-3
US. 1 2-34, A-5
US. 35 2-34, A-5
Numerics
0. LF.50-55
High speed and Earthquake operation 2-30
0.LF.26 2-32, A-3
0.LF.51 2-33, A-4
0.LF.52 2-33, A-4
0.LF.55 2-33, A-4
1.LF.50 2-33, A-4
1.LF.51 2-33, A-4
1.LF.52 2-33, A-4
1.LF.53 2-33, A-4
1.LF.54 2-33, A-4
1.LF.55 2-33, A-4
2 BUS IS LOW 5-3
2 or 2xx Bus 5-2
2.LF.52 2-33, A-4
2.LF.53 2-33, A-4
2.LF.54 2-33, A-4
2AB Spare input 4-28
2FS BUS IS LOW 5-3
2HA BUS IS LOW 5-3
2MV BUS IS LOW 5-3
702-7xx 4-37
702R-7xxR 4-37
801-8xx 4-37
801R-8xxR 4-37
A
A.LF.31 2-32, A-3
ABD 5-50
ABD INPUT FAILURE 5-3
ABI, Alarm Bell Input option 4-28
ABU 5-50
ABU INPUT FAILURE 5-3
ABZ, Attendant Service Buzzer Output option 4-37
AC Drive parameters
TORQMAX F5 Drive A-2, A-6
Acceleration parameter 3-11
ACCESS ENABLED 5-3
Access Overspeed Bypass 4-58
ACI 4-28
Index-1
Alarm Bell Input 4-28
Alarm Reset Acknowledge input 4-28
ALI 4-28
Align Encoder ( TORQMAX) 2-46
Align Encoder (Magnetek) 2-46
Alive Input 4-28
ALLOW CAR CALLS ON WP SEC.? 4-46
ALT. PARKING FLOOR option 4-15
Alternate Acceleration, 182 4-161
Alternate Curve 3-10
Alternate Deceleration, 183 4-161
Alternate Fire Service 4-32
Alternate Lobby Input 4-28
Alternate Parking Input 4-28
Alternate Roll Jerk, 180 4-161
Alternate Start Jerk, 179 4-160
Alternate Stop Jerk, 181 4-161
ALV 4-9
ALV, Alive Input option 4-28
ALV, Other car alive output flag 4-9
Ambient temperature 2-3
ANALOG LOAD WEIGHER? option 4-49
API 4-9
API, Alternate Parking Input flag 4-9
API, Alternate Parking Input option 4-28
ARST 4-28
Ascending Car Overspeed Test 3-44
ASME A17.1A 2005 ADDENDA 4-18
ATD 5-50
ATD INPUT FAILURE 5-3
ATS, Attendant Service Input option 4-28
ATS. BYPASS SECURITY? option 4-50
Attendant Service Buzzer Output 4-37
Attendant Service Input 4-28
ATTENDANT SERVICE OPERATION 5-3
ATU 5-50
ATU INPUT FAILURE 5-4
Audible Car Call Registered Output 4-37
AUTO 4-9
AUTO, Emergency power auto output flag 4-9
AUTO, Emergency Power Auto Selection Input option 4-28
AUTOMATIC MODE FAULT BYPASS 4-58
Automatic Mode Fault Bypass 2-15, 2-28, 3-34
Auto-tuning AC Induction Motors 2-21, 2-26
Auxiliary Position Indicators 4-43
Auxiliary Reset Input 4-28
Auxiliary Speed, 153 4-158
Auxiliary Supervisory Down Arrow 4-43
Auxiliary Supervisory Up Arrow 4-43
AXR, Auxiliary Reset Input option 4-28
B
BAB Spare input 4-28
BAB1 5-47
Backup Power alerting input 4-28
Backup Power Speed 4-158
Basic Feature Menu options 4-13, 4-15
Basic Security 4-56
programming or changing the Security codes 4-57
BATTERY BACKUP POWER SYSTEM FAULT 5-4
Index-2 Manual # 42-02-2P25
BATTERY POWER CAR RECALL ACTIVATED 5-4
Battery replacement 5-55
BFD 4-9
BFD, Bottom floor demand flag 4-9
BMS-LINK 1-17
Board Software Versions 4-165
Both USD and DSD are Open message 5-41
BOTTOM 4-37
Bottom Access Bypass Monitor 5-26
Bottom Access Distance, 65 4-149
Bottom Access Door Contact 5-13
BOTTOM ACCESS SW. FAILURE 5-4
BOTTOM ACCESS? 4-52
Bottom Down Access (ABD) switch 5-3
Bottom Floor Demand message 5-4
Bottom floor level 4-149
BOTTOM FLOOR OR TOP FLOOR DEMAND 5-4
Bottom landing output 4-37
Bottom Rear Access Monitor 5-26
BPCR 4-28
BPS 4-28
Bracelet Security 4-35, 4-46
Brake
Adjust to hold 125% 2-82
Brake control module 5-82
Brake Coordination 3-18
Brake Drop Delay 4-157
Brake Drop Time 2-12
Brake Hold Delay Time 4-157
Brake lining 2-12
Brake module
DIP switches 5-84
External filtering 5-87
LED fault indication 5-84
Switches and Jumpers 5-83
BRAKE MODULE FAULT LIMIT REACHED 5-4
Brake Pick Delay Time 4-156
BRAKE PICK FAILURE 5-5
Brake Pick Switch input. 4-28
Brake Type Option 4-161
BRP INPUT FAILED TO ACTIVATE 5-5
BRP INPUT FAILED TO DEACTIVATE 5-5
BSI Security Key 4-47, 4-56
BSI, Building Security Input option 4-28
Buffer Test 3-39
Building Security Input 4-28
Bumpy transitions 2-29
Bypass Faults 2-28
BYPASS STOP SW. ON PHASE 1 option 4-17
Bypassing Faults on Inspection 2-28, 2-55
C
Calibrate a brake module 4-139
California Earthquake 4-51
CAN Bus 1-3
CAN Bus termination 5-65, 5-69
CAN connections inside controller 5-44
CANCEL BOTH HALL (U/D) CALLS 4-50
CANCEL CAR CALLS BEHIND CAR 4-46
Cannot reach contract speed 2-29
CAPTURE FOR TEST 5-5
Capture for Test Input 4-29
Car and Hoistway Bypass Output 4-38
CAR CALL BUS IS DISCONNECTED 5-5
Car Call Cancellation Output (900) option 4-37
CAR CALL CANCELS DOOR TIME option 4-19
Car call card reader override 4-29
Car call card reader. 4-29
Car Call Disconnect Enable Output 4-37
CAR CALL DOOR TIMER 4-24
Car Call Time Flag Output 4-37
Car Calls Cancel Input 4-29
Car Card Reader Outputs 4-38
Car Controller
installation of 2-6
wiring prints 2-5
Car Done Returning on Emergency Power Output 4-37
CAR DOOR BYPASS SW. FAILURE 5-5
CAR DOORS ARE WALK-THRU option 4-14
Car Gong Enable Down Output 4-37
Car Gong Enable Up Output 4-37
CAR IDENTIFIER option 4-15
CAR IN TEST MODE 5-5
Car lantern actuation point 4-26
CAR LANTERN DOOR FULLY OPEN? 4-26
Car Oscillates at Contract Speed 3-19
Car Overshoots 3-19
Car position 4-58
Car runs at less than commanded speed 2-29
Car runs too slow 2-29
CAR SAFETY DEVICE OPEN 5-5
Car safety string input 4-35
Car Safety Test 3-44
Car Selected to Run Output 4-38
CAR SERVES FRNT/FLR 1 option 4-14
Car speed 2-15, 3-33
Car Stop Switch Bypass Output 4-38
CAR TO FLOOR FUNCTION 5-5
Car to floor Input 4-29
CAR TO FLOOR RETURN FLOOR option 4-50
CAR TO LOBBY OPERATION 5-6
Car top box dimensions 1-7
CAR TOP INSPECTION 5-6
CAR TOP INSPECTION BUTTON STUCK 5-6
Car will not move down 2-28
card reader security 4-45
CARD REDR INPUTS - F CAR CALS? 4-45
CARD REDR INPUTS - F HAL CALS? 4-45
CARD REDR INPUTS - R CAR CALS? 4-45
CARD REDR INPUTS - R HAL CALS? 4-45
CARD REDR INPUTS- STACKED C/H? 4-45, 4-46
Car-to-Lobby Door Open Timer Output 4-38
Car-to-Lobby Input 4-29
CBF - Car call Bus Fuse Blown input 4-28
CC 4-9
CC CARD READER SECURITY 4-45
CC, Car call flag 4-9
CCA, Car call above flag 4-9
CCB 5-47, 5-50
CCB, Car call below flag 4-9
CCC, Car call cancel input flag 4-9
CCC, Car Calls Cancel Input option 4-29
CCD, Car call disconnect flag 4-9
CCDE, Car Call Disconnect Enable Output option 4-37
CCH, Car call hold flag 4-9
CCR, Car call flag (rear) 4-9
CCT, Car call time flag 4-9
CCT, Car Call Time Flag Output option 4-37
CCTR, Car call time flag (rear) 4-9
CD, Car done flag 4-9
CD, Car Done on Emergency Power Output option 4-37
CE ELECTRONICS BOARD 4-46
CEPR 4-37
CFLT, CFLT Output option 4-37
CGED for rear doors Output 4-37
CGED, Car Gong Enable Down Output option 4-37
CGEDR, CGED for rear doors Output option 4-37
CGEU for rear doors Output 4-38
CGEU, Car Gong Enable Up Output option 4-37
CGEUR, CGEU for rear doors Output option 4-38
CGF, Car Generated Fault Output option 4-38
Changing Parameters 4-11
CHBPO 4-38
Check Car Speed 2-15, 3-33
Check for shorts 2-9
CHNL A 4-58
CHNL B 4-58
Clear drive error 2-18, 2-23
Clear Event Log 4-68
Clear events 4-68
CNFG, Configuration error flag 4-9
CNP, Contactor Proof Input option 4-29
Code Sequence Enable Output 4-38
Commanded and actual pick voltage 4-139
Communication baud rate, External CAN bus 5-45
Complimented PTI Input 4-34
Computer Generated Fault Output 4-38
Computer Internal Memory 4-6
conF 2-21
CONFIGURATION ERROR CHANGE SETTINGS BEFORE
INSTALLATION 5-6
Connection Set 1-16
Connections screen 4-136
CONST. PRESS OP. BYPASS PHE 4-22
Construction operation 2-27
Construction operation jumpers 2-27
CONT. D.C.B. FOR FIRE PH 1 option 4-21
CONT. D.C.B. TO CLOSE DOORS option 4-21
Contactor Proof Input 4-29
CONTRACT OVERSPEED 5-34
Contract Overspeed 4-158
Contract Speed 4-158
Control parameters
TORQMAX, Magnetek 2-45
Controller inspection 2-46, 2-54
Controller reset 4-4
CORRECTION AWAY FROM CW 4-52
Correction Speed 4-159
COS/ETS Overspeed Bypass 4-58
Counterweight balancing, preparing for final adjust 3-8
Index-3
Counterweight Input 4-29
Counterweight Position 4-150
Counterweight Safety Test 3-45
CR01-CR8 4-38
CR01R-CR8R 4-38
CR1-CR8 4-29
CR1R-CR8R 4-29
CR2032 battery voltage 5-6
CRO 4-29
CSA FAULT OUTPUT 4-37
CSB, Car stop switch bypass flag 4-9
CSB, Car Stop Switch Bypass Output option 4-38
CSBR, Car stop switch bypass (rear) flag 4-9
CSEO, Code Sequence Enable Output option 4-38
CSR, Car Selected to Run Output option 4-38
CTEN 5-50
CTF
Car To Floor 1-15
CTL
Car to Lobby 1-15
CTL A LANDING SYSTEM INSPECTION OVERSPEED 5-6
CTL A or B ACTUAL AND REQUESTED DIRECTION MIS-
MATCH 5-7
CTL A or B DET SW OVERSPEED 5-7
CTL A or B DET SW POSITION FAULT 5-7
CTL A or B DNT SW HIGH OVERSPEED 5-8
CTL A or B DNT SW POSITION FAULT 5-8
CTL A or B DNTS LOW OVERSPEED 5-8
CTL A or B DOWN NORMAL LIMIT OPEN 5-8
CTL A or B DRIVE FAULT 5-8
CTL A or B DRIVE NOT READY 5-9
CTL A or B DRIVE ON FAULT 5-9
CTL A or B EEPROM FAULT 5-9
CTL A or B ETS SHUTDOWN FAULT 5-9
CTL A or B EXCESSIVE FAULTS SHUTDOWN 5-9
CTL A or B INCORRECT LANDING SYSTEM CHANNEL DE-
TECTED 5-9
CTL A or B INSPECTION OVERSPEED 5-9
CTL A or B LANDING SYSTEM COMM LOSS 5-10
CTL A or B LANDING SYSTEM ETS FAULT 5-11
CTL A or B LANDING SYSTEM ETS MISMATCH 5-11
CTL A or B LANDING SYSTEM FLOOR MISMATCH 5-11
CTL A or B LEVELING OVERSPEED 5-11
CTL A or B RELATIVE POSITION HIGH 5-11
CTL A or B RELATIVE POSITION LOW 5-11
CTL A or B UET SW OVERSPEED 5-11
CTL A or B UET SW POSITION FAULT 5-12
CTL A or B UNT SW HIGH OVERSPEED 5-12
CTL A or B UNT SW LOW OVERSPEED 5-12
CTL A or B UNT SW POSITION FAULT 5-12
CTL A or B UP NORMAL LIMIT OPEN 5-13
CTL A SPD0 AND SPD1 ARE LOW 5-6
CTL, Car to lobby input flag 4-9
CTL, Car-to-Lobby Input option 4-29
CTL-A BRAKE MODULE 1 IS OFFLINE 5-6
CTL-A BRAKE MODULE 2 IS OFFLINE 5-6
CTL-A LANDING SYSTEM ACCESS OVERSPEED 5-6
CTL-A or B CONTRACT OVERSPEED 5-7
CTL-B Brake Module 3 is offline 5-13
CTL-B Brake Module 4 is offline 5-13
CTLDOT, Car to lobby door open timer flag 4-9
CTLDOT, Car-to-Lobby Door Open Timer Output option
4-38
CTLF, Car to lobby function flag 4-9
CTP, Car to floor Input option 4-29
CTST, Capture for test input flag 4-9
CTST, Capture for Test Input option 4-29
CWI 4-29
CYCLE TEST 5-13
CYCLE TEST FAILURE 5-13
D
D = Dispatcher 4-6
D in upper left corner of the LCD 5-42
D.C.B. CANCELS DOOR TIME option 4-20
d.LF.32 2-32, A-3
Danger “Curve” 3-10
Danger Deceleration 4-160
Danger Roll Jerk 4-160
Danger Slew Slope 4-157
Danger Start Jerk 4-160
Danger Stop Jerk 4-160
Date / Time Stamp 4-66
Date/Time, View / Adjust 4-66
DBC, Door close button input flag 4-9
DBCR, Door close button (rear) flag 4-9
DBZF, Front Door Buzzer output option 4-38
DBZR, Rear Door Buzzer output option 4-38
DC, Down call flag 4-9
DCA, Down call above flag 4-9
DCAB 5-47, 5-48
DCAB INPUT FAILURE 5-13
DCABR 5-48
DCAT 5-47, 5-48
DCB 5-47, 5-50
DCB, Down call below flag 4-9
DCBR 4-29
DCC, Door close complete flag 4-9
DCCR, Door close complete flag (rear) 4-9
DCF 5-47, 5-50
DCF, Door close function output flag 4-9
DCFR 4-38
DCFR, Door close function output (rear) flag 4-9
DCFX 4-38
DCL 5-47, 5-50
DCL, Door Close Limit Input option 4-29
DCLC 4-9
DCLC, Doors Closed Contact Input option 4-29
DCLCR INPUT FAILURE 5-14
DCLCR, Door close contact input (rear) flag 4-9
DCLR 4-29
DCMS 5-47, 5-48
DCOM 5-49
DCP 5-47, 5-50
DCP, Door close power output flag 4-9
DCPR 4-38
DCPR, Door close power output (rear) flag 4-9
DCPX 4-38
DCR, Down call flag (rear) flag 4-9
DDF, Double ding function flag 4-9
Index-4 Manual # 42-02-2P25
DDP, Down direction preference flag 4-9
DEADZ, Dead zone flag 4-9
Deceleration parameter 3-11
DEDICATED PI BOARD? 4-16
Default brake module values 4-139
Default parameter values 4-5
Default TC-FCL Parameters 4-139
Default TC-MPI Parameters 4-68
Default the TC-MPI 4-68
Default XPort screen 4-138
DEIS 4-39
DEISR 4-39
Delta speeds 4-153
DETS 4-155, 5-50
DETS Delta Distance, 106 4-155
DETS Delta High Speed 4-155
DETS Distance 4-155
DETS POSITION FAULT 5-7
DETS Speed 4-155
Device Data screen 4-137
DFI 4-29
DHEND 4-38
DHEND, Door hold end flag 4-9
DHEND, Door Hold End Output option 4-38
DHEND2, Door hold end rear flag 4-9
DHENDR 4-38
DHLD, Door hold input flag 4-9
DHLD, Door Hold Input for Normal Service option 4-30
DHLDI, Normal door hold input flag 4-9
DHLDR, DHLD for Rear Doors option 4-30
DHO 4-38
DHO, Door hold open flag 4-9
DHO, Door Hold Output 4-38
DHOF, Door Hold Output Front 4-38
DHOF/R 4-38
DHOR, Door hold open flag (rear) 4-9
DHOR, Door Hold Output Rear 4-38
Diagnostic Mode 4-6, 4-8
DIN, Door open inactive flag 4-9
DIR. PREFERENCE UNTIL DLK option 4-21
Directional Limit 4-150
Directional Limit Distance 4-150
Directional Limit Type, 202 4-163
DISABLE DPM ON FIRE PH.2 4-18
DISABLE DPM ON FIRE PH.2? 4-18
DISABLE LOCAL HALL CALLS 4-16
DISABLE TOP FLRS ON PITFLD 4-50
DISB 4-38
DISL 4-38
DISLX 4-39
Dispatch Load Input 4-30
Display car speed 2-15, 3-33, 4-58
Display current position 4-58
Display position 4-58
Distress Buzzer 4-38
Distress Light 4-38
Distress Light Auxiliary 4-39
DL INPUT FAILURE 5-14
DLAB 5-47, 5-48
DLABR 5-48
DLAT 5-48
DLI, Dispatch Load Input flag 4-9
DLI, Dispatch Load Input option 4-30
DLK, Door lock input flag 4-9
DLKS, Door lock store bit flag 4-9
DLMS 5-48
DLOB 4-39
DLOB, Door Left Open Bell Output option 4-39
DLR INPUT FAILURE 5-14
DLS 4-30
DLSR 4-30
DLW, Dispatch load weighing function flag 4-9
DMD, Demand down flag 4-10
DMU, Demand up flag 4-10
DNDO, Down direction output flag 4-10
DNENDR, Door Hold End Rear Output option 4-38
DNI, Down Input (Attendant Service) option 4-30
DNO 4-39
DNO, Down output (Attendant Service) option 4-39
DNS 4-39
DNS, Down direction sense input flag 4-10
DNT1 5-80
DNTS POSITION FAULT 5-8
DNTS1 Delta Distance 4-155
DNTS1 Delta High Speed 4-155
DNTS1 Distance 4-155
DNTS1 Speed 4-155
DNTS2, 3, 4, 5 4-156
DO1, DO2, DO4, DO8, DO16, D032
Binary coded P.I. outputs for digital P.I. devices 4-39
DOB 5-47, 5-50
DOB, Door open button input flag 4-10
DOBR 4-30
DOBR, Door open button input (rear) flag 4-10
DOC, Door open command flag 4-10
DOCR, Door open command (rear) flag 4-10
DOF 5-47, 5-50
DOF, Door open function output flag 4-10
DOFR 4-39
DOFR, Door open function output (rear) flag 4-10
DOFX 4-39
DOI, Door open intent flag 4-10
DOIR, Door open intent flag (rear) 4-10
DOL 5-47, 5-50
DOL Door Open Limit 4-30
DOL INPUT FAILURE 5-14
DOL, Door open limit input flag 4-10
DOLM, Door open limit memory flag 4-10
DOLMR, Door open limit memory flag (rear) 4-10
DOLR Door Open Limit Rear 4-30
DOLR INPUT FAILURE 5-14
DOLR, Door open limit (rear) flag 4-10
Door Close Button Rear 4-29
Door Close Function Auxiliary 4-38
Door Close Limit Input 4-29
DOOR CLOSE LIMITS? option 4-52
Door Close Power Auxiliary 4-38
Door Close Protection message 5-15
DOOR CLOSE PROTECTION TIMER ELAPSED 5-15
Door Enable Inspection Stop Switch 4-39
Index-5
Door Enable Inspection Stop Switch Rear 4-39
Door Enable Output 4-39
Door Hold End Output 4-38
Door Hold End Output Rear 4-38
Door Hold Input 4-30
Door Hold Output 4-38
Door Hold Output Front 4-38
Door Hold Output Rear 4-38
Door Left Open Bell Output 4-39
Door lock bypass 5-46
Door Lock Sensor Input 4-30
Door mechanically coupled selection 4-22
Door Nudging Auxiliary output 4-42
Door Open Button Rear 4-30
Door Open Function Auxiliary 4-39
Door Open Limit input 4-30
DOOR OPEN PROTECTION TIMER 4-25
Door Operation Menu options 4-19, 4-21, 4-22
DOOR POSITION MONITOR
4-52
Door Position Monitoring 4-30
Door Stop Input 4-30
Door Stop Input Complement 4-30
Door style selection 4-22
Door Time Shortening Front Output 4-39
Door Time Shortening Output 4-39
Door Time Shortening Rear Output 4-39
DOOR TYPE IS HORIZONTAL / VERTICAL 4-22
DOOR ZONE SENSOR FAILURE - ON POSITION 5-15
DOOR ZONE SENSOR FAILURE OFF POSITION 5-15
Door Zone Verification 3-7
DOORENAB 4-39
Doors Closed Contact Input 4-29
DOORS TO LATCH DCF 4-23
DOORS TO LATCH DOF 4-23
DOORS TO OPEN IF NO DEMAND option 4-22
DOORS TO OPEN IF PARKED option 4-21
DOORS TO OPEN ON ALT FIRE option 4-22
DOORS TO OPEN ON MAIN FIRE option 4-21
Down Emergency Terminal overspeed 5-7
Down Input (Attendant Service) 4-30
DOWN NORMAL LIMIT OPEN 5-15
Down Normal Terminal Switch High overspeed 5-8
Down Normal Terminal Switch Low overspeed 5-8
Down output (Attendant Service) 4-39
Down Sense 4-39
DPD, Down previous direction flag 4-10
DPM 5-47, 5-50
DPM Fault 5-15
DPM REDUNDANCY FAULT 5-15
DPM, Front Door Position Monitoring option 4-30
DPMR fault 5-16
DPMR REDUNDANCY FAULT 5-16
DPMR, Rear Door Position Monitoring option 4-30
DPR, Door protection timer flag 4-10
Drawing numbers, description of 2-5
Drive configuration 2-31, A-2
Drive Disable Delay Time 4-157
Drive error, clearing 2-18, 2-23
DRIVE FAULT 5-16
Index-6 Manual # 42-02-2P25
Drive Fault Input 4-29
Drive Motor/Encoder Setup 2-20, 2-25
Drive On Input 4-30
Drive overvoltage fault 3-21
Drive response adjustment 3-13
DRIVE RX COMM FAILURE 5-16
DRIVE TX COMM FAILURE 5-16
Drive Type 4-161
DRON 4-30
DSD, Down slow down input flag 4-10
DSH, Door shortening flag 4-10
DSH, Door Time Shortening Output (intermediate) 4-39
DSHT, Door shortening flag 4-10
DSHT, Door Time Shortening Front Output (final) 4-39
DSHTR, Door shortening flag (rear) 4-10
DSHTR, Door Time Shortening Front Output (rear) 4-39
DSTI, Door Stop Input option 4-30
DSTIC 4-30
DSTICR 4-30
DSTIR, DSTI for rear doors option 4-30
Duplex connection 2-81
Duplex dispatcher (D) or a local (L) 4-136
Duplex operation JP3 4-13
Duplexing 5-42
DZ, Door zone input flag 4-10
DZF 5-48
DZORDZ, Front or rear door zone input flag 4-10
DZP, Door zone previous flag 4-10
DZR 5-48
DZR, Door zone input (rear) flag 4-10
DZRX 4-30
DZX 4-30
E
E.ENCC Fault 2-46
Earthquake Direction Switch 4-30
Earthquake Direction Terminal Limit Switch 4-30
Earthquake indicator output. 4-40
Earthquake Input 4-31
Earthquake Light 4-40
EARTHQUAKE OPERATION 5-16
EARTHQUAKE REDUCED SPEED OPERATION 5-16
Earthquake Speed 4-158
ECC, Excess car calls flag 4-10
ECRN, Emergency Car Freeze Input option 4-30
ECRN, Emergency car run flag 4-10
ECRN, Emergency Power Car Run Output option 4-39
EDS 4-30
EDTLS 4-30
EFG, Egress Floor Gong Output option 4-39
Egress Floor Gong Output 4-39
Electrical noise 2-4
Electrostatic Discharge 2-7
Elevator Shutdown Input 4-31
ELEVATOR SHUTDOWN SWITCH ACTIVE 5-16
ELFI 4-31
ELGO CAN channel loss 5-10, 5-31
EMERGENCY BRAKE ACTIVATED 5-16
Emergency Brake Hold Voltage, 201 4-163
Emergency Brake Option 4-161
Emergency Brake Pick Voltage, 200 4-163
Emergency Brake Type, 199 4-163
Emergency Car Freeze Input 4-30
Emergency Dispatch Input 4-35
EMERGENCY MEDICAL SERVICE 5-17
Emergency Medical Service (EMS) hallway switch input 4-31
Emergency Medical Service (EMS) in-car switch input 4-31
Emergency Medical Service Buzzer Output 4-39
Emergency Medical Service Indicator Car Output 4-39
Emergency Medical Service Indicator Hall Output 4-39
Emergency Power Auto Selection Input 4-28
Emergency Power Car Run Output 4-39
Emergency Power Input 4-31
Emergency Power message 5-17
EMERGENCY POWER OPERATION 5-17
Emergency Power Phase 1 Output 4-39
Emergency Power Phase 2 Output 4-39
Emergency Power Return 4-37
Emergency Power Return Incomplete Output 4-42
Emergency Power Return Input 4-31
Emergency Power Run Input 4-31
Emergency Power Stop Input 4-31
Emergency Terminal Slowdown 4-152
EMI/RFI interference 2-4
EMSB, Emergency Medical Service Buzzer Output 4-39
EMSC, Emergency Medical Switch Car option 4-31
EMSH, Emergency Medical Switch Hall option 4-31
EMSIC, Emergency Medical Service Indicator Car Out 4-39
EMSIH, Emergency Medical Service Indicator Hall Out 4-39
ENABLE FRONT DOB ON SECURITY 4-51
ENABLE FRONT DOB ON SECURITY? 4-50
ENABLE REAR DOB ON SECURITY 4-50
Encoder installation 2-13
Encoder Mounting 2-13
Encoder Wiring 2-13
English 4-69
ENTER SECURITY CODE 5-17
EP1, Emergency Power Phase 1 Output option 4-39
EP2, Emergency Power Phase 2 Output option 4-39
EPI, Emergency power input flag 4-10
EPI, Emergency Power Input option 4-31
EPR, Emergency power return flag 4-10
EPR, Emergency Power Return Input option 4-31
EPRUN 4-44
EPRUN, Emergency power run input flag 4-10
EPRUN, Emergency Power Run Input option 4-31
EPSTP, Emergency power stop input flag 4-10
EPSTP, Emergency Power Stop Input option 4-31
EQ SHUTDOWN AT LANDING 4-52
EQ SHUTDOWN PH1 FIRE SERV 4-52
EQ SHUTDOWN PH2 FIRE SERV 4-52
EQI 4-31
EQIND 4-40
EQL 4-40
Error diagnostic display 4-137
ESC 5-47, 5-48
ESS, Elevator Shutdown Input option 4-31
ET SW SHUTDOWN FAULT 5-9
Ethernet 1-16
ETS SWITCHES REQUIRED 4-52
ETS Testing 3-43
ETSL 4-152
ETSL switch 3-15
Event Calendar 4-67
Excessive faults 2-16, 3-35
EXCESSIVE FAULTS SHUTDOWN 5-9, 5-30
Extended Motor Cables 2-11
External CAN Bus baud rate 5-45
EXTERNAL LATCHING FAULT INPUT 5-17
External Memory Mode 4-55
External Memory mode 4-53
Extra Features Menu options 4-44, 4-48, 4-49
F
F1 - F8 4-3
F1 (Program Mode) 3-2
Fan/Light Operation Output 4-40
FAN/LIGHT OUTPUT TIMER 4-25
Fault Bypass 2-28
FAULT BYPASS IS ACTIVE (AUTOMATIC) 5-17
FAULT BYPASS IS ACTIVE (INSPECTION) 5-17
FCCC, Fire Phase 2 Call Cancel Button Input option 4-31
FCCC, Fire phase 2 car call cancel flag 4-10
FCHLD, Fire phase 2 hold flag 4-10
FCHLD, Fire Phase 2 Switch HOLD Position Input 4-31
FCL 1 - 4 - AUX IGBT STUCK OPEN 5-18
FCL 1 - 4 - BYPASS BUTTON STUCK CLOSED 5-18
FCL 1 - 4 - CAN DISCONNECTED 5-18
FCL 1 - 4 - DISCRETE INPUT WHILE IN CAN MODE 5-17, 5-
18
FCL 1 - 4 - LOAD OVER CURRENT 5-19
FCL 1 - 4 - LOAD OVER VOLTAGE 5-19
FCL 1 - 4 - LOAD UNDER VOLTAGE 5-19
FCL 1 - 4 - MAIN IGBT STUCK CLOSED 5-20
FCL 1 - 4 - MAIN IGBT STUCK OPEN 5-20
FCL 1 - 4 - MODULE ADDRESS ERROR 5-20
FCL 1 - 4 - MODULE OVERHEAT 5-20
FCL 1 - 4 - NOT CALIBRATED 5-20
FCL 1 - 4 - TRYING TO RUN IN MANUAL RELEASE MODE
5-20
FCL 1 - 4 faults 5-18
FCL 1 - 4 IS ON MANUAL MODE 5-19
FCL 1 - 4 LOAD EXTREME UNDER CURRENT 5-19
FCL 1 - 4 LOAD EXTREME UNDER VOLTAGE 5-19
FCL Adjustment Menu 4-139
FCL Diagnostic Menu 4-139
FCL Power Data Menu 4-139
FCOFF, Fire phase 2 off flag 4-10
FCOFF, Fire Phase 2 Switch OFF Position Input option 4-31
FCS 5-47, 5-50
FCS, Fire phase 2 input flag 4-10
FCSM, Fire service phase 2 input memory flag 4-10
FDC, Door fully closed phase 2 flag 4-10
FDCR, Door fully closed phase 2 (rear) flag 4-10
Final Limit 3-20
Final Limit Switches 4-150
FIR1, Fire Service Phase I output option 4-40
FIRE BYPASSES HOSPITAL option 4-49
FIRE HAT STATUS 4-18
FIRE PH1 RECLOSE TIMER 4-25
Index-7
FIRE PH2. WITH DOORS CLOSED 4-23
FIRE PHASE 1 ALT. FLOOR option 4-17
FIRE PHASE 1 MAIN FLOOR option 4-17
Fire Phase 1 Switch ON Position Input 4-31
FIRE PHASE I 2ND ALT. FLOOR option 4-17
Fire Phase I Alternate Switch ON Position Input 4-31
Fire Phase I Second Alternate Input 4-31
Fire Phase I Switch BYPASS Position Input 4-31
Fire Phase II Call Cancel Button Input 4-31
Fire Phase II Door Hold Input 4-31
Fire Phase II OFF Input 4-31, 4-40
Fire Service Alternate 5-20
Fire Service Alternate Output 4-40
Fire Service Buzzer Auxiliary output. 4-40
Fire Service Light COP Auxiliary output. 4-40
Fire Service Light Lobby Auxiliary output 4-40
Fire Service Main message 5-21
Fire Service Main Output 4-40
FIRE SERVICE MENU OPTIONS 4-17
Fire Service On Output 4-40
FIRE SERVICE OPERATION option 4-17
FIRE SERVICE PHASE 1 ALTERNATE 5-20
FIRE SERVICE PHASE 1 MAIN 5-21
Fire Service Phase 1 Return Complete Output 4-42
FIRE SERVICE PHASE 2 5-21
Fire Service Phase I Output 4-40
Fire Service Phase I output 4-40
Fire Service Phase II Output 4-40
Fire Service Phase II True Output 4-40
FIRE SVCE. CODE option 4-17
Fire Warning Light Output 4-40
Flags/Variables and Their Locations 4-9
Flare jerk parameter 3-11
Flash output 4-40
FLASH, Flash output option 4-40
Flashing In Service Output 4-41
FLO, Fan/Light Operation Output option 4-40
Floor Labels 4-63
Floor Labels, programming 4-63
FLR COUNT BELOW FLOOD LEVEL? 4-50
FLTM 4-31
Following Error 4-162
FRA 5-50
FRA, Alternate Fire service phase 1 input flag 4-10
FRAA, Fire Phase 1 Alternate (2nd alternate) Input 4-31
FRAON, Fire Phase 1 Alternate Switch ON Position 4-31
FRAS, Alternate fire flag 4-10
FRBYP, Fire phase 1 bypass input flag 4-10
FRBYP, Fire Phase 1 Switch BYPASS Position Input 4-31
FRC, Fire phase 2 flag 4-10
FRC, Fire Service Phase 2 Output option 4-40
FRCT 4-40
FREE, No demand and in service flag 4-10
FRES 5-50
FRHTW 4-31
FRM, Fire service phase 1 flag 4-10
FRM, Fire Service Phase 1 Output option 4-40
FRMR 4-31
FRON 5-47, 5-50
FRON, Fire phase 1 on input flag 4-10
Index-8 Manual # 42-02-2P25
FRON, Fire Phase 1 Switch ON Position Input option 4-31
FRON2, Fire Phase 1 Switch ON Position Input option 4-31
Front Access Gate Bypass Monitor 5-26
FRONT DOL AND DLK ARE BOTH ACTIVE 5-21
Front Door Buzzer 4-38
FRONT DOOR FAILED TO CLOSE 5-21
FRONT DOOR IS LOCKED BUT NOT FULLY CLOSED 5-21
FRONT DOOR LOCK SWITCH FAILURE 5-21
FRONT DOOR MECH. COUPLED? 4-22
FRONT DOOR OPEN LIMIT FAILURE 5-21
Front Down Hall Call indicators 4-37
FRONT DZ RELAY DISCREPANCY 5-21
FRONT GATE SWITCH FAILURE 5-21
Front Infrared Cutout 4-33
Front Up Hall Call indicators 4-37
FRS 5-50
FRS, Fire phase 1 input flag 4-9
FRSA 5-50
FRSA, Alternate Fire Service input option 4-32
FRSM 5-50
FRSM, Main Fire Service input option 4-32
FRSS, Fire phase 1 flag 4-9
FSA, Fire Service Alternate Output option 4-40
FSLC 5-47, 5-50
FSLCX 4-40
FSLL 5-47, 5-50
FSLLX 4-40
FSM, Fire Service Main Output option 4-40
FSO, Fire Service On Output option 4-40
FSVC, True Fire Service Output option 4-40
FULLY MANUAL DOORS option 4-21
FWI 5-47, 5-50
FWI, Fire warning indicator output flag 4-9
FWIX 4-40
FWL, Fire Warning Light Output option 4-40
G
Gate Switch Input 4-32
Gate Switch Monitor 5-27
Gate Switch Rear Input 4-32
Gateway screen 4-136
GDO1 4-40
GED, Gong enable down output flag 4-9
GEDR, Gong enable down output (rear) flag 4-9
GEDRX 4-40
GEDX 4-40
Generator Backup 1-14
GEU, Gong enable up output flag 4-9
GEUR, Gong enable up output (rear) flag 4-9
GEURX 4-40
GEUX 4-40
GHT, Gong hold timer flag 4-9
GHTR, Gong hold timer flag (rear) 4-9
Gong Enable Down Auxiliary. 4-40
Gong Enable Up Auxiliary 4-40
Gongs/Lanterns Menu options 4-25
GOV 4-32
GOVERNOR OVERSPEED 5-9, 5-30
Governor switch input 4-32
GOVERNOR SWITCH OPEN 5-22
GRAY CODE 4-44
Gray Code outputs 4-40
Gray Code PI 4-40
Grounding 2-7
GROUP TO CAR COMMUNICATION LOST 5-22
GS 5-47, 5-48
GS INPUT FAILURE 5-22
GS, Gate Switch Input option 4-32
GSR 5-48
GSR INPUT FAILURE 5-22
GSR, Gate Switch Rear Input option 4-32
GTDE, Gong timer down enable flag 4-9
GTUE, Gong timer up enable flag 4-9
H
H 4-40
H, High speed output flag 4-9
HALL AND CAR CALL BUSES DISCONNECTED 5-22
HALL CALL BUS IS DISCONNECTED 5-22
Hall Call Cancel 4-32
HALL CALL DOOR TIMER 4-24
Hall Call Pushed Output 4-40
Hall Call Reject Output 4-40
Hall call, serial 2-81
Hall Card Reader 4-41
Hall Card Reader Inputs 4-32
Hall Card Reader Override input 4-32
Hall Door Close Button 4-32
Hall Door Close Button. 4-32
Hall Door Open Button 4-32
Hall Door Stop Input 4-32
HBF - Hall Call Bus Fuse Blown input 4-32
HCC 4-32
HC-CHP CAN Hub and Power Supply Board 5-44
HC-CHP, CAN Hub/Power Supply 1-5
HC-CTL Control board 5-46
HC-CTL, Control Board 1-5
HCDX, Hall call disconnect flag 4-9
HC-MPU board 5-53
HCP, Hall call pushed output option 4-40
HCR, Hall call reject flag 4-9
HCR, Hall Call Reject Output option 4-40
HCR01-HCRxx 4-41
HCR01R-HCRxxR 4-41
HCR1 - 8 4-32
HCR1R-8 4-32
HC-RDR BOARD ON THE OTHER CAR? 4-14
HC-RDR BOARD ON THIS CAR? 4-14
HCRO 4-32
HCT, Hall call door time flag 4-9
HCTR, Hall call door time flag (rear) 4-9
HC-UIO 1-5
HC-UIO Universal I/O 1-8
HC-UIO, Universal Input/Output Board 1-5
HD, High speed delay flag 4-9
HDCB 4-32
HDCBR 4-32
HDNL 4-41
HDOB 4-32
HDOBR 4-32
HDSC, Heat Detector Shutdown Complete Output 4-41
HDSTI 4-32
HDSTIR 4-32
Heat Detector Input 4-32
Heat Detector Shutdown 4-41
HEATD, Heat Detector Input option 4-32
Heavy Load Input 4-32
HEAVY LOAD WEIGHER CONDITION 5-22
Heavy Load Weigher Output 4-41
HEO 4-41, 4-48
High roll jerk parameter 3-11
High Speed 4-158
HIGH SPEED DELAY AFTER RUN 4-49
High speed parameter 3-11
HLD 5-47, 5-50
HLI, Heavy load input flag 4-9
HLI, Heavy Load Input option 4-32
HLW, Heavy load weigher flag 4-9
HLW, Heavy Load Weigher Output option 4-41
HML, Home landing input flag 4-9
HML, Home Landing Input option 4-32
Hoist Motor Speed 4-158
HOISTWAY ACCESS 5-22
Hoistway access 4-149
Hoistway Access Bottom Up 5-3
HOISTWAY ACCESS? 4-52
Hoistway Door Bypass 5-28
HOISTWAY DOOR BYPASS SW. FAILURE 5-22
Hoistway Fire Sensor 4-31
Hoistway Learn 4-140
HOISTWAY SAFETY DEVICE OPEN 5-23
Hoistway safety string input 4-35
Hoistway switches 4-150
Home Landing Input 4-32
HONEYWELL FIRE OPERATION option 4-17
HOSP, Hospital Emergency Operation Input option 4-32
HOSP, In car hospital emergency input flag 4-9
HOSPH2 4-41, 4-48
HOSPH2, Hospital emergency phase 2 flag 4-9
HOSPITAL EMERG. TIMER 4-25
Hospital Emergency Car Select 4-41
Hospital Emergency Operation 4-41, 4-48, 5-59
Hospital Operation I/O 5-59
HOSPITAL PHASE 1 OPERATION 5-23
Hospital Phase 2 4-41
HOSPITAL PHASE 2 OPERATION 5-23
Hospital Service message 5-23
Hospital Warning Indicator 4-41
HSEL 4-41, 4-48
HSEL, Hospital service select flag 4-9
HUNL 4-41
HWI 4-41, 4-48
HYD1-TR0, Hydro/Traction flag 4-9
I
I9LSS 2-31, A-2
ICEN 5-50
ICLSd 2-31, A-2
ICPD 4-33
ICPD INPUT FAILURE 5-23
Index-9
ICPU 4-33
ICPU INPUT FAILURE 5-23
ICTD 5-50
ICTD INPUT FAILURE 5-23
ICTU 5-50
ICTU INPUT FAILURE 5-23
IDC connector 5-2
iMonitor 1-16
IN CAR INSPECTION BUTTON STUCK 5-23
In Car Inspection Down Direction 4-33
In Car Inspection Up Direction 4-33
IN CAR STOP SWITCH ACTIVATED 5-23
In Service and Running Output 4-41
In Service Output 4-41
In Use Light output 4-41
IN, Inspection or access input flag 4-9
INA 5-50
INA INPUT FAILURE 5-23
INA Spare input 4-33
INAX REDUNDANCY FAULT 5-23
In-car Hospital Service Switch Input 4-32
IN-CAR INSPECTION 5-23
In-car stop switch 5-23
INCF, Independent service car call cancel flag 4-9
INCP 5-50
INCP INPUT FAILURE 5-24
INCT 5-50
INCT INPUT FAILURE 5-24
IND 5-47, 5-50
IND, Independent service input flag 4-9
IND. BYPASS SECURITY? option 4-49
IND. CNCL. CALLS ON STOP? 4-46
Independent Service message 5-24
INDEPENDENT SERVICE OPERATION 5-24
Independent Service Output 4-41
Independent service, call cancellation 4-46
Independent Service/Fire Service Phase 2 Output 4-41
INDFRC, Independent Service/Fire Service Phase 2 4-41
INDO 4-41
Infant Abduction Security 4-35, 4-46
Initial power up 2-10
INN 5-50
INSDN 4-33
INSP 4-41
Inspection 4-41, 5-46
Inspection Access mode 5-3
INSPECTION DIRECTION SW. FAILURE 5-24
Inspection Down Input 4-33
Inspection input hierarchy 2-7
INSPECTION MODE FAULT BYPASS 4-58
Inspection Mode Fault Bypass 2-15, 2-28, 3-34
INSPECTION OPERATION 5-24
INSPECTION OVERSPEED 5-9, 5-30, 5-36
Inspection Overspeed 4-158
Inspection Overspeed Bypass 4-58
Inspection Slew Filter, 205 4-163
Inspection speed 4-159
Inspection Speed (Reduced) 4-159
Inspection Up Input 4-33
INSUP 4-33
Index-10 Manual # 42-02-2P25
Intermediate Speed 4-44
Intermediate speed input 4-33
Intermediate Speed, 151 4-158
IP address screen 4-135
IRCOF, Front Infra Red Cutout input option 4-33
IRCOR, Rear Infra Red Cutout input option 4-33
iReport 1-16
iReport screen 4-137
ISR, In service and ready flag 4-9
ISRT, In Service and Running Output option 4-41
ISRT, In service truly flag 4-9
ISV, In service flag 4-9
ISV, In Service Output option 4-41
IUL, In Use Light output option 4-41
J
Jerk parameters 2-43, 2-45
Job prints 2-2
Jumper 5-2
Jumpers for Construction operation 2-27
K
KCE DISABLED? 4-49
L
LANDING SYS A POSITION DEVIATION 5-36
LANDING SYS B POSITION DEVIATION 5-36
Landing System ETS Overspeed, 204 4-163
Landing System Floor Checksum, 203 4-163
Landing System Interface Board 5-72
Landing System Redundancy Input 4-33
Landing system troubleshooting 5-10, 5-31
Landing System, 191 4-162
LATCH FLASHING FIRE HAT? 4-18
LD, Level down input flag 4-9
Learn or Enter Motor or Encoder Data 2-21
LEAVE DOORS OPEN ON CTL option 4-22
LEAVE DOORS OPEN ON EPI option 4-22
LEAVE DOORS OPEN ON MGS 4-20
LEAVE DOORS OPEN ON PTI/ESS option 4-20
Level Dead Zone 4-159
Level Distance 4-159
Leveling distance parameter 3-11
LEVELING DOWN 5-24
LEVELING OVERSPEED 5-11, 5-32
Leveling Overspeed 4-158
Leveling Speed 4-159
Leveling speed parameter 3-11
LEVELING UP 5-24
LF. 2 2-31, A-2
LF. 3 2-31, A-2
LF. 5 2-31, A-2
LF. 8 2-31, A-2
LF. 9 2-31, A-2
LF.11 2-31, A-2
LF.12 2-31, A-2
LF.13 2-31, A-2
LF.14 2-31, A-3
LF.15 2-32, A-3
LF.16 2-32, A-3
LF.18 2-32, A-3
LF.19 2-32, A-3
LF.21 2-32, A-3
LF.22 2-32, A-3
LF.23 2-32, A-3
LF.25 2-32, A-3
LF.27 2-32, A-3
LF.28 2-32, A-3
LF.30 2-32, A-3
LF.41 2-33, A-4
LF.42 2-33, A-4
LF.44 2-33, A-4
LF.45 2-33, A-4
LF.46 2-33, A-4
LF.47 2-33, A-4
LF.56 2-33, A-4
LF.57 2-33, A-4
LF.58 2-33, A-4
LF.59 2-33, A-4
LF.61 2-82
LF.68 2-33, A-4
LF.78 2-34, A-5
LF.79 2-34, A-5
LF.83 2-34, A-5
LF.86 2-34, A-5
LF.88 2-34, A-5
LF.89 2-34, A-5
LF.90 2-34, A-5
LF.94 2-34, A-5
LF.95 2-34, A-5
LFP, Lower parking floor flag 4-9
Light Load Input 4-33
LIGHT LOAD WEIGHER CONDITION 5-24
Light Load Weigher Output 4-42
Limit switches 2-52
LIMITED DOOR RE-OPEN OPTION option 4-22
LLI, Light load input flag 4-9
LLI, Light Load Input option 4-33
LLW, Light Load Weigher Output option 4-42
LLW, Light load weighing function input flag 4-9
Load weigher
Calibration 3-28, 3-31
Control unit installation 3-26
Errors 3-32
Fuse 3-32
Programming 3-23
Rope stretch 3-31
Sensor installation 3-24
Load Weigher Bypass 4-33
Load weighing system
DLW (Dispatch load weigher threshold) 4-60
HLW (Heavy load weigher threshold) 4-60
LLW (Light load weigher threshold) 4-60
OLW (Overloaded car threshold) 4-60
setting load thresholds 4-61
LOBBY FLOOR option 4-15
LOCKOUT 2-24
Loss of Control During Acceleration 3-18
LOSS OF DOOR LOCK OUT OF DOOR ZONE 5-24
LOT, Lobby door time flag 4-9
LOTR, Lobby door time (rear) flag 4-9
LOW VOLTAGE FIRE SENSORS 4-18
Lower Final Limit Test 3-38
LS-EDGE 3-5, 4-140
LS-EDGE BOTTOM TERMINAL POSITION DEVIATION
5-24
LS-EDGE COULD NOT WRITE TO PLD 5-24
LS-EDGE CPU-B IS OFFLINE 5-25
LS-EDGE DZF OUTPUT REDUNDANCY FAULT 5-25
LS-EDGE DZR OUTPUT REDUNDANCY FAULT 5-25
LS-EDGE LEARN MODE ACTIVE 5-25
LS-EDGE QUADRATURE SENSOR LOSS 5-25
LS-EDGE STUCK SENSOR FAULT 5-25
LS-EDGE TOP TERMINAL POSITION DEVIATION 5-25
LSR 4-33
LU, Level up input flag 4-9
LWB, Load Weigher Bypass input option 4-33
LWCE 4-9
M
M2L INPUT FAILURE 5-25
MABB INPUT FAILURE 5-26
MABBR INPUT FAILURE 5-26
MABGF INPUT FAILURE 5-26
MABGR INPUT FAILURE 5-26
MABT INPUT FAILURE 5-26
MABTR INPUT FAILURE 5-26
Machine room fire sensor 4-31
MACHINE ROOM INSPECTION 5-26
Magnetek
Additional tuning 3-17
Clear faults 2-23
Determining system inertia 3-17
Drive response adjustment 3-13
Encoder Alignment 2-46
Keypad overview 2-23
Motor tuning 2-26
Parameter table 2-35
Setup overview 2-25
Status indicators 2-24
Tuning motor flux saturation curve 3-17
Tuning motor no-load current 3-17
Verify motor speed 2-48
Magnetek drive controls 2-16
Magnetek status LEDs 2-24
Main Fire Service 4-32
Manual Acceleration 4-160
Manual Curve 3-10
Manual Deceleration 4-160
Manual Induction Motor Parameter Entry 2-22
Manual Override 4-33
Manual Roll Jerk 4-160
Manual Start Jerk 4-160
Manual Stop Jerk 4-160
MASS 524 CMR FIRE CODE? option 4-18
MASSACHUSETTS EMS 4-46
MASSACHUSETTS EMS SERVICE 5-17
MBAB INPUT FAILURE 5-26
MBABR INPUT FAILURE 5-27
Index-11
MC-CPI board 5-63, 5-67
MC-CPI CAN data viewing 4-134
MC-LSI 5-72
MC-MPU Main Computer Board
setting parameters to default values 4-5
MC-MPU Main Processing Unit 1-5
MCSB INPUT FAILURE 5-27
MDLR INPUT FAILURE 5-27
MDZLV INPUT FAILURE 5-27
MECHANICAL SAFETY EDGE option 4-20
Mechanically In Service Output 4-42
Messages and Floor Labels, programming 4-63
Metric 4-69
Metric or English units 4-69
MG SHUTDOWN OPERATION 4-45
MGB INPUT FAILURE 5-27
MGBR INPUT FAILURE 5-27
MGR OUTPUT TIMER 4-24
MGS 4-33
MGS INPUT FAILURE 5-27
MGSR INPUT FAILURE 5-28
MHDB INPUT FAILURE 5-28
MHDBR INPUT FAILURE 5-28
MISV, Mechanically In Service Output option 4-42
MLT, Motor Limit Timer Elapsed Output option 4-42
MLT, Motor limit timer flag 4-9
MNO 4-33
MOMENT D.O.B. FOR 4-21
MOMENT. D.C.B TO CLOSE DOORS 4-23
MOMENT. D.O.B. DOOR OPENING 4-21
Monitored type screen 4-135
Monitoring input for BAB 4-28
Motion (speed/distance) viewing 4-69
Motion Processor Interface board 5-77
Motion/Position Diagnostics 4-69
Motor insulation test 2-11
Motor leads 2-4, 2-11
Motor Limit Timer 5-28
MOTOR LIMIT TIMER ANTI STALL ELAPSED 5-28
Motor Limit Timer Elapsed Output 4-42
Motor nameplate data 2-21
MP (Motion Processor) 5-77
mPAC 1-3
mPac 1-6
MPI A EEPROM FAULT 5-29
MPI A EMERGENCY BRAKE CYCLE TEST FAULT 5-29
MPI A or B 2L BUS MONITOR FAULT 5-29
MPI A or B 2MV BUS MONITOR FAULT 5-34
MPI A or B EBPS MONITOR FAULT 5-29
MPI A or B EXCESSIVE FAULTS SHUTDOWN 5-30
MPI A or B GOVERNOR OVERSPEED 5-30
MPI A or B INCORRECT LANDING SYSTEM CHANNEL DE-
TECTED 5-30
MPI A or B INSPECTION OVERSPEED 5-30
MPI A or B LANDING SYSTEM COMM LOSS 4-134, 5-31
MPI A or B LANDING SYSTEM FAULT (EMERGENCY
BRAKE DROPPED) 5-31
MPI A or B LEVELING OVERSPEED 5-32
MPI A or B PMDD CONTACTOR DROP MONITOR 5-32
MPI A or B PMDD CONTACTOR PICK MONITOR 5-32
MPI A or B RGOK DROPPED 5-32
MPI A or B RGOK FAILED TO ACTIVATE 5-33
MPI A or B RGOK FAILED TO DEACTIVATE 5-33
MPI A or B SPC IS OFFLINE 5-33
MPI A or B UNT SW HIGH OVERSPEED 5-33
MPI A or B UNT SW LOW OVERSPEED 5-33
MPI A or B UNT SW POSITION FAULT 5-34
MPI A or B UP NORMAL LIMIT OPEN 5-34
MPI A UNINTENDED MOTION FAULT 5-29
MPI B SPA IS OFFLINE, SPC IS OFFLINE 5-34
MPI C CONTRACT OVERSPEED 5-34
MPI C DRIVE FAULT 5-34
MPI C DRIVE NOT READY 5-34
MPI C DRIVE OFFLINE (STOP MODE) 5-35
MPI C DRIVE ON FAILED TO ACTIVATE 5-35
MPI C DRIVE ON FAILED TO DEACTIVATE 5-35
MPI C DRIVE ON LOST 5-35
MPI C EEPROM CRC ERROR 5-35
MPI C EEPROM DEVICE ERROR 5-35
MPI C EXCESSIVE FAULTS SHUTDOWN 5-35
MPI C FOLLOWING ERROR 5-36
MPI C INSPECTION OVERSPEED 5-36
MPI C LANDING SYS A POSITION DEVIATION 5-36
MPI C LANDING SYS B POSITION DEVIATION 5-36
MPI C LEVELING TIMER EXCEEDED 5-36
MPI C UNEXPECTED DIRECTION DROP 5-37
MPI Diagnostic Menu 4-69
English or Metric 4-69
MPI SPA IS OFF LINE message 5-28
MPI SPB IS OFF LINE message 5-28
MPI-A LANDING SYSTEM ETS MISMATCH 5-29
MPI-A LANDING SYSTEM FLOOR MISMATCH (FLOOR
LEARN REQUIRED) 5-29
MPU-A IS OFFLINE 5-37
MSAFL1 INPUT FAILURE message 5-37
MSAFS1 INPUT FAILURE message 5-37
MTAB INPUT FAILURE 5-37
MTABR INPUT FAILURE 5-37
MTBR INPUT FAILED TO ACTIVATE 5-37
MTBR INPUT FAILED TO DEACTIVATE 5-37
MTPM INPUT FAILED TO ACTIVATE 5-38
MTPM INPUT FAILED TO DEACTIVATE 5-38
mView 1-17
N
N, S, +, - Push Buttons 4-4
NBZ 5-47, 5-50
NBZX 4-42
NCD, Car Not Done with Emergency Power Return 4-42
NDGBPS, Nudging bypass flag 4-9
NDGBPSR, Nudging bypass flag (rear) 4-9
NDGF, Nudging function flag 4-9
NDGR 4-42
NDGX 4-42
NDS, Hall door timer non-shorten flag 4-9
NDSR, Hall door timer non-shorten (rear) flag 4-9
NEMA 12 2-3
NEMA 4 2-3
NEW YORK CITY FIRE PHASE 2 AND ANSI 89 option 4-17
Nomenclature 2-5
Index-12 Manual # 42-02-2P25
Nomenclature, description of 2-5
Non-Stop Input (Attendant Service) 4-33
Normal Brake Drop Rate, 198 4-163
Normal Brake Hold Voltage, 195 4-163
Normal Brake Lift Rate, 197 4-163
Normal Brake Pick Voltage, 194 4-162
Normal Brake Relevel Voltage, 195 4-163
NORMAL OPERATION 5-38
NORMAL PIT FLOOR OPERATION 5-38
NSI, Non-Stop Input (Attendant Service) option 4-33
NTS Delta High Speed Test 3-42
NTS Delta Low Speed Test 3-42
NUDG 5-47, 5-50
NUDG, Nudging output flag 4-9
Nudging Buzzer Auxiliary output. 4-42
NUDGING DURING FIRE PH. 1 option 4-19
NUDGING DURING FIRE PHASE 2 option 4-20
NUDGING OUTPUT/BUZZER ONLY option 4-20
NUDGR, Nudging output (rear) flag 4-9
Number of cars configured 4-136
NYCHA 5-2
NYDS, New York door shortening flag 4-10
O
O.LF.98 2-34, A-5
OFF 5-47, 5-50
OFR, One Floor Run Output option 4-42
OFRP 4-42
OFRP BETWEEN FLRS option 4-50
OLW, Overloaded Car Threshold Output option 4-42
One Floor Run Output 4-42
One Floor Run Programmable 4-42
Operating modes 1-9
OPERATION (DISPATCHING OPERATION) option 4-13
OPN/CLS INTRLOCK TIMER 4-25
Options, setting to default values 4-5
OVERLOAD CONDITION 5-38
Overload Input 4-33
Overloaded Car Threshold Output 4-42
OVL, Overload Input option 4-33
OVL2 4-33
OVL2, Overload 2 Input 4-33
P
P.LF.32 2-32, A-3
P9LSS 2-31, A-2
Parameter ID (F7) 4-143
Parameters, setting to default values 4-5
PASSCODE REQUEST 5-38
Passcode Request 4-5
Passing Floor Gong Auxiliary output. 4-42
Passing Floor Gong Enable Input 4-33
PASSWORD TIMER 4-25
PCLSd 2-31, A-2
PFG ENABLE BUTTON? option 4-26
PFG, Passing floor gong output flag 4-10
PFGE, Passing Floor Gong Enable Input option 4-33
PFGX 4-42
PH1, Fire Service Phase 1 Return Complete Output 4-42
PH1, Phase 1 return complete flag 4-10
PHE 5-47, 5-50
PHE, Photo eye input flag 4-10
PHER 4-34
PHER, Photo eye input (rear) flag 4-10
PHERX 4-34
PHEX 4-34
PHOTO EYE ANTI-NUISANCE 4-45
photo eye input, rear 4-34
PI TURNED OFF IF NO DEMAND 4-47
PI Turned Off if No Demand 4-25
PI1 - PI8 4-42
PIC, PI correction flag 4-10
Pit Flood 4-50
PIT FLOOD OPERATION 5-38
Pit Flood. 4-34
PITFLD 4-34
PLD ETS OVERSPEED BYPASS 4-58
PLD IS OFFLINE 5-38
PMP INPUT FAILED TO ACTIVATE 5-38
PMP INPUT FAILED TO DEACTIVATE 5-38
PMT 5-2
Position display 4-58
Position indicators 2-81
POSTN 0.0 IN 4-58
Power for boards inside controller 5-44
Power line fluctuation 2-3
Power Transfer Input 4-34
POWER TRANSFER INPUT ACTIVE 5-39
Power up 2-10
POWER UP SHUTDOWN DUE TO EARTHQUAKE 5-39
PowerBack R6 Regenerative Drive
Parameters Quick Reference A-29
PRE-OPENING option 4-20
Preparing for Final Adjustments
counterweight balancing 3-8
PREVENT DCP TIL DOORS CLOSE? option 4-23
PRIFLG, Priority Service Output option 4-42
Primary motor drop delay contactor 5-32
Prior to Applying Power 2-54
Priority Service Output 4-42
Profile Advance 3-13, 3-14, 4-157
Profile Compensation, 193 4-162
Profile Scale 4-157
Program Mode 4-12
Programmable auxiliary rear door zone input 4-30
Programmable, auxiliary front door zone input 4-30
Programmable, auxiliary photo eye input 4-34
Programmable, auxiliary step down input 4-35
Programmable, auxiliary step up input. 4-35
Proximity Distance 4-159
PTI, Power Transfer Input option 4-34
PTIC 4-34
R
R2AB Redundancy monitoring input 4-34
R2L 4-34
R2L INPUT FAILURE 5-39
R4, Absolute floor encoding #4 flag 4-10
R4, R3, R2, Floor Encoding Input option 4-34
R6 Regenerative AC drive parameters A-29
Index-13
Rated Motor Speed 3-22
RBAB Redundancy monitoring input 4-34
RCOMP 4-42
RDLSR 4-34
Rear Access Gate Bypass Monitor 5-26
REAR CAR DOOR BYPASS SW. FAILURE 5-39
REAR DOL & DLK ARE BOTH ACTIVE 5-39
Rear Door Buzzer 4-38
REAR DOOR CLOSE LIMIT 4-52
Rear Door Close Limit Contact 5-14
REAR DOOR FAILED TO CLOSE 5-39
REAR DOOR IS LOCKED BUT NOT FULLY CLOSED 5-39
Rear Door Lock Relay Redundancy input 4-34
REAR DOOR LOCK SWITCH FAILURE 5-39
REAR DOOR MECH. COUPLED 4-23
REAR DOOR OPEN LIMIT FAILURE 5-39
Rear Down Hall Call indicators 4-37
REAR DZ RELAY DISCREPANCY 5-39
REAR GATE SWITCH FAILURE 5-40
Rear Gate Switch Monitor 5-28
REAR HOISTWAY DOOR BYPASS SW. FAILURE 5-40
Rear Infrared Cutout 4-33
Rear Up Hall Call indicators 4-37
REAR, Rear door flag 4-10
Receive/Transmit screen 4-137
REDUCE HCT WITH PHOTO EYE option 4-22
Reduced Inspection Speed 4-161
Reduced stroke buffers 4-152, 4-156
REDUNDANCY DOOR LOCK RELAY FAILURE 5-40
REDUNDANCY FRONT GATE SWITCH FAILURE 5-40
Redundancy Gate Switch 4-34
Redundancy monitoring input 4-35
REDUNDANCY REAR GATE SWITCH FAILURE 5-40
Refresh Device 4-137
Refresh XPort 4-138
Relevel Operation 3-18
Re-Leveling Distance 4-159
Re-Leveling Speed 4-159
REO, Re-Open Input option 4-34
Re-Open Input 4-34
Rescue Complete 4-42
Reset Drive 4-42
Reset XPort screen 4-137
Resetting the rope gripper 2-14
Resolving Faults 2-28
RESTORING SAFETY 5-40
Retiring Cam 5-15
RETIRING CAM option 4-20
REVD 4-34
Reverse Direction input 4-34
RFI 2-3
RGOK FAILED TO ACTIVATE 5-33
RGOK FAILED TO DEACTIVATE 5-33
RGS 4-34
RGSR 4-35
RINAX 4-35
Rope gripper reset 2-14
Rope slip (traction loss) fault 3-39
RSTDRV 4-42
Run Tests 3-18
Index-14 Manual # 42-02-2P25
Run the motor 2-20, 2-24
RUN, Run flag 4-10
RUN/A/B 4-35
S
S = Slave 4-6
S in upper left corner of LCD 5-42
SAB, Sabbath input flag 4-10
SAB, Sabbath Operation Input option 4-35
SABBATH OPERATION 4-49
Sabbath Operation 4-49
SABBATH OPERATION ACTIVE 5-40
Sabbath Operation Input 4-35
SAF 4-10
SAFC 4-35, 5-47, 5-48
SAFC INPUT FAILURE 5-40
SAFETY CIRCUIT IS OPEN 5-40
SAFETY DROPPED BY SPB 5-40
Safety Edge Rear 4-35
SAFH 4-35, 5-47, 5-48
SAFO 4-42
Saving Changes 4-11
SC-3HN 1-8
SC-3HN board 5-73
SCE, Stepping correction enable flag 4-10
Schematic symbols, description of 2-5
SCROLLING SPEED 4-50
SCROLLING SPEED option 4-51
SD, Supervisory down flag 4-10
SDA, Down direction arrow flag 4-10
SDT, Short door time flag 4-10
SDTR, Short door time flag (rear) 4-10
SE, Safety edge input flag 4-10
SEC, Security Code Incorrect output option 4-42
SECONDARY PARKING FLOOR option 4-15
Security Code Incorrect 4-42
Seismic equipment install 2-53
Selective Collective 4-13
SEQUENTIAL DOOR OPER. (F/R) option 4-19
SER 4-35
SER, Safety edge input (rear) flag 4-10
Serial car panel option 1-3
Serial hall call 1-3
Serial Hall Call Node Board 5-73
SerSP 2-31, A-2
set parameters to default values 4-5
Sheave Brake Idle Delay, 190 4-162
Shorts 2-9
SHUTDOWN OPERATION 5-41
Signal operating mode 2-31, A-2
SIMP, Simplex Input option 4-35
Simplex Input 4-35
SIMPLEX OR DUPLEX option 4-13
Simplex Output 4-42
SIMPO, Simplex Output option 4-42
Single Automatic Push button 4-13
Single Button Collective 4-13
SINGLE SPEED AC OPTION 4-49
Slew Filter 4-158
SLV, Stable slave flag 4-10
Smoothing tape edges 2-57
Software version
CHP 4-165
CTLA 4-165
CTLB 4-165
CTLC 4-165
MPIA 4-165
MPIB 4-165
MPIC 4-165
MPUA 4-165
UIO 4-165
SPA (Safety Processor A) 5-77
SPA IS OFFLINE 5-34, 5-41
SPARE OUTPUTS MENU OPTIONS 4-36
SPB (Safety Processor B) 5-77
SPB IS OFFLINE 5-41
SPC IS OFFLINE 5-33
SPD0 5-48
SPD1 5-48
SPD2 5-48
Specifications 1-2
SPEED 0 FPM 4-58
Speed and Acceleration Control 2-29
Speed Changes Felt Excessively in Car 3-18
Speed Drop Delay, 192 4-162
Speed Hysteresis Delay 4-157
Speed Hysteresis Delay, 139 4-157
Speed Pick Delay Time 4-156
SST, Soft stop timer flag flag 4-9
Standard Acceleration 4-159
Standard Curve 3-10
Standard Deceleration 4-160
Standard Roll Jerk 4-159
Standard Slew Slope 4-157
Standard Start Jerk 4-159
Standard Stop Jerk 4-159
Start Input 4-35
Start jerk 3-11
STARTIN, Start Input option 4-35
STARTING UP 5-41
STDX 4-35
Steel tape 2-57
Stick alignment 2-60
STOP 4-35
Stop SW 5-23
STUCK PHOTO EYE PROTECTION option 4-19
STUX 4-35
SU, Supervisory up flag 4-10
SUA, Up direction arrow flag 4-10
Subnet mask screen 4-135
SWG 4-35
System CAN Bus 4-134
T
TAB1 5-47
Tape cleaning 2-57
TAPS 2-82
LF61 TORQMAX Setting 2-33
TORQMAX LF61 1-3
TAPS Backup 1-14
TAPS Fault input 4-31
TC-MPI 1-5
TEMPB, Temporary bit flag 4-10
Temporary jumpers 2-27
Temporary run box wiring 2-50
TEST, Test switch input flag 4-10
Testing motor insulation 2-11
TESTSWO 4-42
TFA, Timing function active flag 4-10
TFAR, Timing function active (rear) flag 4-10
TFD, Top floor demand flag 4-10
TFTP Status screen 4-138
TIME OUT OF SERVICE 5-41
Timed Out of Service Output 4-43
Timer Menu options 4-24, 4-25
Top Access Bypass Monitor 5-26
Top Access Distance 4-149
TOP ACCESS SW. FAILURE 5-41
TOP ACCESS? 4-52
TOP LANDING FOR OTHER CAR? 4-14
TOP LANDING SERVED option 4-14
Top Rear Access Bypass Monitor 5-26
TORQMAX Display 2-18
Torqmax Display 2-23
TORQMAX F5 drive 2-17
TOS, Time Out of Service Output option 4-43
TOS, Timed out of service flag 4-10
Traction Auxiliary Power Supply 2-82
Traction Auxiliary Power Supply (TAPS) 1-3
Traveler Cable 1-8
Triac 5-3
Troubleshooting
duplexing 5-42
True Fire Service Output 4-40
U
UC, Up call flag 4-10
UCA, Up call above flag 4-10
UCR, Up call flag (rear) 4-10
UDF 4-35
UDP, Up direction preference flag 4-10
UET SW OVERSPEED 5-11
UET SW POSITION FAULT 5-12
UETS 4-152, 5-50
UETS Delta Distance 4-152
UETS Delta High Speed 4-152
UETS Distance 4-152
UETS Speed 4-152, 4-155
UETS Speed, 75 4-152
UFL 4-35
UFP, Upper parking floor flag 4-10
UFQ, Up first qualifier flag 4-10
Unintended Motion 3-45
UNINTENDED MOTION FAULT 5-29
Unintended Motion, 188 4-161
Universal I/O 1-3
UNT SW HIGH OVERSPEED 5-12, 5-33
UNT SW LOW OVERSPEED 5-12, 5-33
UNT1 5-80
UNTS POSITION FAULT 5-12, 5-34
Index-15
UNTS1 Delta Distance 4-154
UNTS1 Delta High Speed 4-154
UNTS1 Delta High Speed, 83 4-154
UNTS1 Distance 4-154
UNTS1 Speed, 79 4-154
UNTS2, 3, 4, 5 4-154
UP AND DOWN TERMINAL SPEED REDUCING LIMITS
OPEN 5-41
Up Emergency Terminal overspeed 5-11
Up Emergency Terminal Switch 4-152
Up Final Limit Input 4-35
Up Input (Attendant Service) 4-35
Up Normal Terminal Switch High overspeed 5-12, 5-33
Up Normal Terminal Switch Low overspeed 5-12, 5-33
Up Output (Attendant Service) 4-43
Up Sense 4-43
UPD, Up previous direction flag 4-10
Update firmware 5-45
UPDO, Up direction output flag 4-10
Upgrading Motion 4000 Firmware 5-45
UPI, Up Input (Attendant Service) 4-35
UPO, Up Output (Attendant Service) option 4-43
Upper Final Limit Test 3-38
UPS 4-43
UPS, Up direction sense input flag 4-10
US. 3 2-34, A-5
US. 4 2-34, A-5
US.10 2-34, A-5
US.34 2-34, A-5
USD, Up slow down input flag 4-10
V
VCI 4-9
Velocity Encoder
Connections 2-13
Velocity Encoder Installation 2-51
Verify Motor Speed, TORQMAX 2-48
Verify Motor Speed, Magnetek 2-48
Verify One Floor Run Operation 3-14
Verifying Contract Speed Operation 3-15
Version number of the monitoring software 4-135
Video rescue system 4-34
View assigned spare inputs 4-27
View assigned spare outputs 4-36
View car speed and distances 4-69
View Event Log 4-67
View events 4-67
W
Wandering Patient Security 4-35, 4-46
WHITE PLAINS, NY FIRE CODE option 4-18
Wild Operation Indication Output 4-43
WILL THIS CAR RUN ON PH2? 4-17
Wiring prints, description of 2-5
WLD, Emergency Dispatch Input option 4-35
WLDI, Wildop Indication Output option 4-43
WP SECURITY ACTIVATED 5-41
WPIA - H 4-35
WPIx LANDING? 4-46
X
XDSA, Auxiliary Supervisory Down Arrow output option 4-43
xNTSn Delta Distance 4-153 xNTSn Delta High Speed 4-153 xNTSn Delta Low Speed 4-153 xNTSn Distance 4-153 xNTSn Speed 4-153
XPI1-XPI7, Auxiliary Position Indicators 1 thru 7 output 4-43
XPort Comm Resets screen 4-136
XSUA, Auxiliary Supervisory Up Arrow output option 4-43
Z
ZADJ, Zero Adjust output option 4-43
Zero Adjust 4-43
Index-16 Manual # 42-02-2P25