DVPEN01-SL

Ethernet Communication Module

Operation Manual

DVP-0204320-02

Ethernet Communication Module DVPEN01-SL

Warning

3

Please read this instruction carefully before use and follow this instruction to operate the device in order to prevent damages on the device or injuries to staff.

3

Switch off the power before wiring.

3

RTU-DNET is an OPEN TYPE device and therefore should be installed in an enclosure free of airborne dust, humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key or specific tools are required for operating the enclosure) in case danger and damage on the device may occur.

3

RTU-DNET is to be used for controlling the operating machine and equipment. In order not to damage it, only qualified professional staff familiar with the structure and operation of RTU-DNET can install, operate, wire and maintain it.

3

DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all the wirings again before switching on the power and DO NOT touch any terminal when the power is switched on. Make sure the ground terminal is correctly grounded in order to prevent electromagnetic interference.

Table of Contents

1 INTRODUCTION...................................................................................................................................3

1.1

Functions.....................................................................................................................................3

1.2

Specifications ..............................................................................................................................3

2 PRODUCT PROFILE & OUTLINE .......................................................................................................4

2.1

Dimension ...................................................................................................................................4

2.2

Product Profiles...........................................................................................................................4

2.3

LED Indicators.............................................................................................................................5

2.4

RJ-45 PIN Definition....................................................................................................................5

3 INSTALLATION & WIRING ..................................................................................................................5

3.1

Installation ...................................................................................................................................5

4 CONTROL REGISTER (CR) ................................................................................................................6

4.1

Control Registers in DVPEN01-SL..............................................................................................6

4.2

Explanations on CR ....................................................................................................................8

4.3

Numbering of Left-Side Modules...............................................................................................13

5 SETTING UP SOFTWARE .................................................................................................................14

5.1

Setting up Communication & Searching for Modules................................................................14

5.2

Basic Settings ...........................................................................................................................20

5.3

Network Settings .......................................................................................................................21

5.4

Setting up E-Mails .....................................................................................................................24

5.5

Data Exchange..........................................................................................................................25

5.6

RTU ...........................................................................................................................................26

5.7

IP Filter ......................................................................................................................................27

5.8

Static ARP Table........................................................................................................................27

5.9

Setting up Password .................................................................................................................28

DVP-PLC Operation Manual

1

Ethernet Communication Module DVPEN01-SL

5.10

Returning to Default Setting ..................................................................................................... 29

6 APPLICATION EXAMPLES............................................................................................................... 30

6.1

Setting up IP and Communicating through WPLSoft................................................................ 30

6.2

Connecting the PC with DVPEN01-SL through LAN ................................................................ 33

6.3

Setting up Password and Clearing Password .......................................................................... 37

6.4

When the Password is Lost (Returning to Default Setting by RS-232)..................................... 39

6.5

IP Filter Protection .................................................................................................................... 40

6.6

Setting up Static ARP Table ...................................................................................................... 42

6.7

Application of E-Mail................................................................................................................. 44

6.8

Application of Data Exchange (1) ............................................................................................. 45

6.9

Application of Data Exchange (2) ............................................................................................. 48

6.10

Application of Data Exchange (3) ............................................................................................. 49

6.11

Application of Data Exchange (4) ............................................................................................. 50

6.12

Application of Data Exchange (5) ............................................................................................. 52

6.13

Application of Modbus TCP Master .......................................................................................... 53

6.14

RTU Mapping............................................................................................................................ 54

2

DVP-PLC Operation Manual

Ethernet Communication Module DVPEN01-SL

1 Introduction

Thank you for choosing DVPEN01-SL module. To correctly install and operate DVPEN01-SL, please read the manual carefully before using the module.

DVPEN01-SL is an Ethernet communication module for remote setting and communication through

WPLSoft. DVPEN01-SL is able to send E-mails, automatically correct the RTC in DVP28SV11R/T and exchange data. It supports Modbus TCP communication protocol and can conduct remote monitoring by using

SCADA (Supervisor Control and Data Acquisition) software or HMI (Human Machine Interfaces). DVPEN01-SL can be the master of Modbus TCP, sending out Modbus TCP instructions and controlling the peripheral equipment. In addition, under MDI/MDI-X auto-detection, it does not need to use a crossing cable. See the contents below for more detailed instructions on DVPEN01-SL module.

1.1 Functions

z Auto-detects 10/100Mbps transmission speed z MDI/MDI-X z Supports Modbus TCP protocol (at the same time supports Master and Slave mode) z Able to send out E-mails z Auto-corrects the RTC in PLC through the Internet time correction function z Supports point-to-point data exchange (Max. data exchange length: 200 bytes)

1.2 Specifications

ƒ Internet interface

Item Specification

Number of ports

Transmission method

Transmission cable

Transmission speed

Network protocol

ƒ

Serial communication interface

1 Port

IEEE802.3, IEEE802.3u

Category 5e

10/100 Mbps Auto-Detect

ICMP, IP, TCP, UDP, DHCP, SMTP, NTP, Modbus TCP

Item Specification

Interface RS-232

Number of ports 1 Port

Transmission cable DVPACAB230, DVPACAB215, DVPACAB2A30, DVPACAB2B10

ƒ Environment

Item

Noise immunity

Environment

Specification

ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge

EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV

Analog & Communication I/O: 1KV

Damped-Oscillatory Wave: Power Line: 1KV

RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m

Operation: 0

°

C ~ 55

°

C (temperature), 50 ~ 95% (humidity), Pollution degree 2;

DVP-PLC Operation Manual

3

Ethernet Communication Module DVPEN01-SL

Item Specification

Storage: -25

°

C ~ 70

°

C (temperature), 5 ~ 95% (humidity)

Vibration/ Shock Resistance Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)

ƒ

Electrical specifications

Item

Power supply voltage

Power consumption

Insulation voltage

Weight (g)

Specification

24VDC (-15% ~ 20%) (Power is supplied by the internal bus of MPU.)

1.5W

500V

92 (g)

2 Product Profile & Outline

2.1 Dimension

3 [0.118]

DVPEN01

POWER

RS-232

100M

LINK

RS-232

LAN

Unit: mm [inches]

60 [2.362]

4

1

3

DVPEN01

POWER

RS-232

100M

LINK

RS-232

2

8

4

7

1.

Model name

2.

Extension port to connect device

3.

Extension port to connect I/O module

4.

POWER, LINK, RS-232, 100M indicators

5.

DIN rail clip

5

LAN

9

6

6.

Fixing tenon for I/O module

7.

Fixing clip for I/O module

8.

RS-232 connection port

9.

Ethernet RJ-485 connection port

DVP-PLC Operation Manual

Ethernet Communication Module DVPEN01-SL

Indicator Color

POWER Green

RS-232 Red

100M Orange

LINK Green

Indication

Communication status of the series port

Network status

Network communication speed

2.4 RJ-45 PIN Definition

RJ-45 sketch Terminal No.

1

2

3

6

4, 5, 7, 8

Definition

Tx+

Tx-

Rx+

Rx-

-

Explanation

Positive pole for data transmission

Negative pole for data transmission

Positive pole for data receiving

Negative pole for data receiving

N/C

3 Installation & Wiring

This section gives instructions on how to connect DVPEN01-SL with PLC MPU and how to connect

DVPEN01-SL to the network.

3.1 Installation

Connect PLC MPU to DVPEN01-SL z Adjust the I/O module clip on the left side of the MPU. z Meet the I/O module port of the MPU with DVPEN01-SL as shown in the figure below. z Fasten the I/O module clip on the left side of the MPU.

DVP28SV

DVPEN01

POWER

RS-232

100M

LINK

RS-232

LAN

Connect DVPEN01-SL to other I/O modules z To connect DVPEN01-SL with the other I/O module, lift the extension clip of the I/O module by a screwdriver and open the side cover.

DVP-PLC Operation Manual

5

Ethernet Communication Module DVPEN01-SL

Connect DVPEN01-SL to the Network:

Connect DVPEN01-SL to the Ethernet Hub by twisted pair cable CAT-5e. DVPEN01-SL has Auto MDI/MDIX function; therefore, DVPEN01-SL does not need to use a crossing cable between the PC and DVPEN01-SL.

Network connections between the PC and DVPEN01-SL:

DVPEN01 DVP28SV

DVPEN01

POWER

RS-232

100M

LINK

RS-232

DVP28SV

LAN

PC Master

Ethernet

DVPEN01

POWER

RS-232

100M

LINK

DVPEN01 DVP28SV

DVP28SV

RS-232

LAN

6

4.1 Control Registers in DVPEN01-SL

CR#

HW LW

Attribute

#1

#2

Content Explanation

R Firmware version

Set up by the system; read only. Model code of DVPEN01-SL

= H’4050

Displaying the current firmware version in hex.

R Communication mode b0: Modbus TCP mode; b1: data exchange mode

#3

#4

#5

#6

W

W

W

W

E-Mail Event 1 trigger

E-Mail Event 2 trigger

E-Mail Event 3 trigger

E-Mail Event 4 trigger

Set up whether to send E-Mail 1

Set up whether to send E-Mail 2

Set up whether to send E-Mail 3

Set up whether to send E-Mail 4

DVP-PLC Operation Manual

Ethernet Communication Module DVPEN01-SL

CR#

HW LW

#7

#8

Attribute Content

R Status of E-Mail 1, 2

R Status of E-Mail 3, 4

Explanation b0 ~ b7: Current status of E-Mail 2 b8 ~ b15: Current status of E-Mail 1 b0 ~ b7: Current status of E-Mail 4 b8 ~ b15: Current status of E-Mail 3

Filled in by the user, and it will be send by E-mail.

Filled in by the user, and it will be send by E-mail.

Filled in by the user, and it will be send by E-mail.

Filled in by the user, and it will be send by E-mail.

#13 R/W Data exchange trigger Set up whether to send out data in data exchange mode

#14 R Status of data exchange Displaying current status of data exchange.

#15 RW 1: Enable; 0: Disable. Default = 0

#16 RW b0: Status of RTU slave 1 b1: Status of RTU slave 2 b2: Status of RTU slave 3 b3: Status of RTU slave 4

#24 ~ #17

#68 ~ #49

#80 ~ #69

- Reserved

Destination IP address for data exchange

#27 - Reserved

#28 R/W Destination Slave ID Destination Slave ID for data exchange

#48 ~ #29 R/W Data transmission buffer Buffer for transmitted data in data exchange

R Data receiving buffer

- Reserved

Buffer for received data in data exchange

Slave transmission buffer address for data exchange

Number of registers for read data

Buffer address for the receiving Master in data exchange

Buffer address for the receiving Slave in data exchange

Number of registers for data transmission

Master transmission buffer address for data exchange

#110 ~ #87 - Reserved

#111 R/W 8-bit processing mode Setting up Modbus TCP Master control as 8-bit mode

Modbus TCP Keep-Alive Time-out (s)

#114 R/W Modbus TCP time-out Setting up Modbus TCP time-out (in ms)

DVP-PLC Operation Manual

7

Ethernet Communication Module DVPEN01-SL

8

CR#

HW LW

Attribute Content

#115 R/W Modbus TCP trigger

Explanation

Setting up whether to send out data in Modbus TCP mode

#118 #117 R/W

Modbus TCP destination IP

Setting up destination IP address for Modbus TCP transaction

#119 R/W Modbus TCP data length Setting up the data length for Modbus TCP transaction

#219 ~ #120 R/W Modbus TCP data buffer Data buffer of Modbus TCP for storing sending/receiving data

#248 ~ #220 - Reserved

Displaying the errors. See table of error codes in the following section for more information.

#255 ~ #252 - Reserved

Symbols “R” refers to “able to read data by FROM instrcution”; “W” refers to “able to write data by TO instrcution”.

4.2 Explanations on CR

C R # 0 :

Model Name

Explanations:

1. Model code of DVPEN01-SL = H’4050.

2. You can read the model code in the program to see if the I/O module exists.

C R # 1 :

Firmware Version

Explanations:

The firmware version of DVPEN01-SL is displayed in hex, e.g. H’0100 indicates version V1.00.

C R # 2 :

Communication Mode

Explanations:

Bit No. Mode “0”

Disable

Disable

“1”

Enable

Enable

„

E-mail Functions

CR#3 ~ 6:

E-Mail Event 1 ~ 4 Trigger

Explanations:

When the CR is set as “1”, E-mail sending will be enabled. After the sending is completed, the

CR will automatically be reset as “0”. Note: Please trigger by differential instructions.

DVP-PLC Operation Manual

Ethernet Communication Module DVPEN01-SL

C R # 7 ~ 8 :

Status of E-Mail 1 ~ 4

Explanations:

1. CR#7_b0 ~ b7: current status of E-Mail 2; CR#7_b8 ~ b15: current status of E-Mail 1.

2. CR#8_b0 ~ b7: current status of E-Mail 4; CR#8_b8 ~ b15: current status of E-Mail 3.

3. Table of E-Mail status

CR value

0

E-Mail status

Not been sent

2

10

11

12

13

E-Mail sending is successful

Fail to connect to SMTP-Server

Incorrect recipient E-Mail address

SMTP-Server communication error

Exceeding the max. number of TCP connection

3 ~ 9, 14 ~ 255 Reserved

C R # 9 ~ 1 2 :

E-Mail 1 ~ 4 Additional Message

Explanations:

The user fills in the code, and the code will be stored in the title of the E-Mail and sent out with the

E-Mail.

„

Data Exchange

C R # 1 3 :

Data Exchange Trigger

Explanations:

When the CR is set as “0”, the data in data exchange area will not be transmitted. When the CR is set as “1”, the data in data exchange area will be transmitted. f When the Execute Mode in the software is set to “Program Control” (See 5.5), set CR#13 to 2, and the data exchange will continue to execute. Set CR#13 to 0 to stop the data exchange. f When the Execute Mode in the software is set to “Always Enable”, the data exchange will continue to execute whatever the setting in CR#13 is.

(Firmware V2.0 and later versions support continuous execution of data exchange.)

C R # 1 4 :

Data Exchange Status

Explanations:

When the CR is set as “0”, the data have not yet been received. When the CR is set as “1”, the data exchange is in progress. When the CR is set as “2”, the data exchange is successful. When the CR is set as “3”, the data exchange fails.

DVP-PLC Operation Manual

9

Ethernet Communication Module DVPEN01-SL

10

CR value

2

3

0

1

Status

Data have not yet been received.

Data exchange is in progress.

Data exchange is successful.

Data exchange fails.

C R # 2 5 , 2 6 :

Destination IP

Explanations:

To set up the Slave IP address for data exchange manually, write “0” into CR#28 first before setting up the destination IP. For example, if the user wants to set the destination IP address to

192.168.0.2, write H’0002 to CR#25 and H’C0A8 to CR#26. (K192 = H’C0, K168 = H’A8, K0 =

H’00, K2 = H’02).

C R # 2 8 :

Destination Slave ID

Explanations:

When you set up the Salve ID (i.e. K1 ~ K255) for data exchange, DVPEN01-SL will automatically search for the corresponding IP address from the Slave IP list. For example, if the

ID is set as “0”, the value in CR#25 and #26 will be regarded as the destination IP.

C R # 2 9 ~ 4 8 :

Data Transmission Buffer

Explanations:

Storing the data to be transmitted to the remote MPU.

C R # 4 9 ~ 6 8 :

Data Receiving Buffer

Explanations:

Storing the data received from the remote MPU.

C R # 8 1 :

Read Address for Data Exchange

Explanations:

Setting up manually the Modbus address of the register for Slave data exchange. Only register address is allowed (e.g. D0 = H’1000).

C R # 8 2 :

Read Length for Data Exchange

Explanations:

The number of receiving registers (K1 ~ K100) in data exchange.

DVP-PLC Operation Manual

Ethernet Communication Module DVPEN01-SL

C R # 8 3 :

Read Length for Data Exchange

Explanations:

Setting up the Modbus address of the register for Master data exchange.

C R # 8 4 :

Written-in Address for Data Exchange

Explanations:

Setting up manually the Modbus address of the register for Slave data exchange.

C R # 8 5 :

Written-in Address for Data Exchange

Explanations:

The number of transmission registers (K1 ~ K100) in data exchange.

C R # 8 6 :

Transmission Address for Data Exchange

Explanations:

1. Setting up the Modbus address of the register for Master data exchange.

2. Example: Write H’1000 (D0) into CR#81, K1 into CR#82, and H’1064 (D100) into CR#83. If the data exchange is successful, the value in D0 of the Slave will be written into D100 of the

MPU. Or write H’1002 (D2) into CR#84, K4 into CR#85, and H’1008 (D8) into CR#86. If the data exchange is successful, the value in D8 ~ D11 of the Master will be written into D2 ~ D5 of the Slave. Both sending and receiving can be executed at the same time. When the values in CR#82 and #85 are both “0”, DVPEN01-SL will use the default registers (CR#29 ~ CR#68) and number of registers (K20).

„

Sending Modbus TCP Instruction

C R # 111 :

8-bit Processing Mode

Explanations:

Setting up the Modbus TCP transmission mode. When the CR value is set as “0” Æ 16-bit mode; when the CR value is set as “1” Æ 8-bit mode.

C R # 11 2 :

Modbus Client Keep-Alive Time-out

Explanations:

CR#112 is the TCP Keep-Alive time-out for Modbus TCP connection (s). Default: 30s. If the connection idle time becomes longer than the keep-alive time-out, DVPEN01-SL will cut off the idle connection.

DVP-PLC Operation Manual

11

Ethernet Communication Module DVPEN01-SL

12

C R # 11 4 :

Modbus TCP Time-Out

Explanations:

Setting up the communication time-out (in ms) for Modbus TCP mode.

C R # 11 5 :

Modbus TCP Trigger

Explanations:

When the CR value is set as “1”, Modbus TCP will be triggered. After the data transmission is completed in Modbus TCP mode, the CR value will automatically be reset to “0”. Please trigger by differential instructions.

C R # 11 6 :

Modbus TCP Status

Explanations:

Displaying the current communication status of Modbus TCP mode. When the CR value is set as”0” Æ the data have not yet been received; when the CR value is set as “1” Æ the data exchange is in progress; when the CR value is set as “2”

Æ

the data exchange is successful; when the CR value is set as “3” Æ the data exchange fails.

CR value

0

1

2

3

Data exchange status

The data have not been received.

The data exchange is in progress.

The data exchange is successful.

The data exchange fails.

C R # 11 7 , 11 8 :

Modbus TCP Destination IP

Explanations:

Setting up the destination IP address in Modbus TCP mode. See explanations on CR#70 and

#71 for how to set.

C R # 11 9 :

Modbus TCP Data Length

Explanations:

Setting up the length of communication data in Modbus TCP mode. Length for 8-bit mode: K1

~K100; length for 16-bit mode: K1 ~ K200.

C R # 1 2 0 ~ 2 1 9 :

Modbus TCP Data Buffer

Explanations:

Buffer for transmitted/received data in Modbus TCP mode.

DVP-PLC Operation Manual

Ethernet Communication Module DVPEN01-SL

C R # 2 5 1 :

Error Code

Explanations:

Table of error code:

Bit No. b0 b1 b2 b3

Error

The network is not yet connected.

Incorrect IP setting

CR#13 is set as “transmitting data”, but the data exchange is forbidden.

CR#13 is set as “transmitting data”, but the data exchange mode has not yet been enabled.

„

RTU Mapping

b7 b8

SMTP-Server connection fails.

DHCP has not obtained the correct network parameter.

C R # 1 5 :

Enabling Flag for RTU Mapping

Explanations:

1: Enable; 0: Disable. Default = 0

Firmware V2.0 and later versions support RTU mapping.

C R # 1 6 :

Connection Status of RTU Mapping Slave

Explanations

: b3 ~ b0 display the connection status of RTU slave. The connection may encounter some problems when any of the bits becomes 0. Firmware V2.0 and later versions support RTU mapping. b0: Status of RTU slave 1 b1: Status of RTU slave 2 b2: Status of RTU slave 3 b3: Status of RTU slave 4

4.3 Numbering of Left-Side Modules

After DVPEN01-SL is installed properly, you need to compile the PLC program to control the special I/O module. PLC offers FROM instruction (for reading) and TO instruction (for writing) to control the control registers

(CR) in the special I/O module.

Numbering of the modules: Every special I/O module connected to PLC MPU has a No. to allow you to know which module is which when compiling the PLC program. The first special I/O module attached at the left hand side of the PLC MPU is numbered as K100, the second as K101, the third K102, and so on.

DVP-PLC Operation Manual

13

Ethernet Communication Module DVPEN01-SL

5 Setting up Software

This section gives instructions on how to set up DVPEN01-SL by DCISoft and explanations on each setup page. Before you start a setup page, you have to select “Ethernet” in the communication setting. Next, you can search by IP address or use Auto-Search. You also can open the setup page for DVPEN01-SL by RS-232.

DVPEN01-SL is set up by UDP port 20006; therefore, you have to be aware of the relevant settings of the firewall.

5.1 Setting up Communication & Searching for Modules

„

Communication settings

1. Open DCISoft in your PC and click on “Communication Setting”.

14

2. Select “Ethernet” as the transmission type.

DVP-PLC Operation Manual

Ethernet Communication Module DVPEN01-SL

„

Broadcast search

1. Click broadcast icon in DCISoft to search for all Delta Ethernet products on the network. The window on the left hand side shows the models found, and the window on the right hand side displays the device list of all models.

2. Click a model on the left hand side, and you will see the device list of the model selected on the right hand side. Click the device to be set up to enter the setup page.

DVP-PLC Operation Manual

15

Ethernet Communication Module DVPEN01-SL

3. You will see the basic setup page as follow.

16

„

Designating model to search

1. Right click “Ethernet” on the left hand side window and select “Configure” to designate a model to search for.

DVP-PLC Operation Manual

DVP-PLC Operation Manual

Ethernet Communication Module DVPEN01-SL

2. After configure a model, select “DVPEN01-SL” and click “OK” to auto-search for DVPEN01-SL modules on the network.

3. List of the current DVPEN01-SL modules

17

Ethernet Communication Module DVPEN01-SL

„

Searching by IP address

1. Set the communication type to “Ethernet” and enter the IP address. Click “OK”.

2. Click “IP Search” icon to start searching for the designated IP.

18

3. The DVPEN01-SL module found will be displayed in the right hand side window. Double click it to enter the setup page.

DVP-PLC Operation Manual

Ethernet Communication Module DVPEN01-SL

„

Opening DVPEN01-SL setup page by RS-232

1. Select “RS232" as the transmission type in communication setting. You will have to designate a communication port. When DVPEN01-SL is searched by RS-232, you do not need to set up the parameters (i.e. data length, parity, stop bits and baud rate).

2. After setting up the communication port, press “broadcast search” icon. If the searching is successful, the setup page for DVPEN01-SL will open automatically.

DVP-PLC Operation Manual

19

Ethernet Communication Module DVPEN01-SL

The basic settings include parameters as module name, language, enabling Modbus TCP and time correction.

„

Setting up DVPEN01-SL basics

20

There can be many DVPEN01-SL modules in the network. Thus, you can set up a module name for each module to identify the module when you need to use them.

2. Module Language:

You can select a language for each module name, and the windows will be displayed in the selected language.

3. Enable Modbus TCP:

To enable or disable Modbus TCP. When Modbus TCP is disabled, WPLSoft will not be able to upload or download.

4. Enable time correction:

DVPEN01-SL adopts NTP (Network Time protocol), which means it can acquire correct time automatically from the time server in the network and correct the RTC in the MPU every fixed period of time to ensure correct time in the MPU. The default setting of this function is “disable”.

5. Start Daylight Saving Time:

Daylight Saving Time; also known as summer time is a conventional local time adopted by many countries in the world on a seasonal basis. Most commonly DST is obtained by adjusting the official local time forward, by one hour, for the spring, summer, and early autumn periods.

Daylight Saving Time is not implemented in Taiwan; therefore, you do not need to check this item.

6. Time Server:

IP address of the time server. You can acquire correct time from the time server to correct the time in the MPU.

DVP-PLC Operation Manual

Ethernet Communication Module DVPEN01-SL

7. Time Zone:

A time zone is a region of the Earth that has adopted the same standard time, usually referred to as the local time. Most adjacent time zones are exactly one hour apart, and by convention compute their local time as an offset from Greenwich Mean Time (see also UTC). Standard time zones can be defined by geometrically subdividing the Earth's spheroid into 24 lunes

(wedge-shaped sections), bordered by meridians each 15° of longitude apart. The local time in neighboring zones is then exactly one hour different. However, political and geographical practicalities can result in irregularly shaped zones that follow political boundaries or that change their time seasonally (as with daylight saving time), as well as being subject to occasional redefinition as political conditions change. You should choice the Time zone that you are.

The first step for all the network equipment to connect to the network is to have its own IP address (Internet

Protocol). The IP address is like a number for every network equipment to be identified in the network.

„

Setting up static IP of the PC

1. Enter Control Panel → Network Connection → click on “Local Area Connection”

2. You will see the “Local Area Connection Status” window. Click on “Properties”.

DVP-PLC Operation Manual

21

Ethernet Communication Module DVPEN01-SL

22

3. Click on “Internet Protocol (TCP/IP).

4. Enter 192.168.0.1 into IP address. Click on “OK” to complete the IP address setting of the PC.

DVP-PLC Operation Manual

Ethernet Communication Module DVPEN01-SL

„

Setting up DVPEN01-SL Network

1. IP configuration:

There are two types of IP, static IP and DHCP.

Static IP: Preset or manually modified by the user.

DHCP: Automatically updated by the server. There has to be a server in the LAN.

IP Explanation

Static The user enters the IP address, subnet mask and gateway.

DHCP DHCP server offers the IP address, subnet mask and gateway.

2. IP address:

IP address is the location of the equipment in the network. Every equipment connected to the network has to have an IP address. Incorrect IP address will result in connection failure on the equipment or even other equipment. Ask your ISP for questions about IP address setup. The default

IP for DVPEN01-SL is 192.168.1.5.

3. Subnet mask:

Subnet mask is an important parameter for setting up the subnet, used for seeing if the destination

IP and the local equipment are in the same subnet. If not, the equipment will send the packet to the gateway, and the gateway will send the packet to another subnet. Incorrect setting may cause the destination equipment unable to communicate with DVPEN01-SL. To see if your setting is correct, conduct bitwise AND operations between your IP and subnet mask and destination IP and subnet mask. If the two values obtained are the same, the two IPs are in the same subnet. The default subnet mask of DVPEN01-SL is 255.255.255.0.

4. Gateway:

Gateway is the gate for two different subnets, allowing the two ends in different subnets to communicate. For example, if the LAN has to be connected to WAN, it will need a gateway to bridge the communication. The IP of the gateway has to be in the same subnet as DVPEN01-SL. The default gateway IP address of DVPEN01-SL is 192.168.1.1.

DVP-PLC Operation Manual

23

Ethernet Communication Module DVPEN01-SL

5.4 Setting up E-Mails

E-mail is the abbreviation of electronic mail, which transmits mails through the network. DVPEN01-SL has

E-Mail functions for the user to pre-save a segment of text messages, which can be a descriptive message or error message, into the subject of the E-Mail. When the E-Mail is triggered, DVPEN01-SL will send the messages to the user by E-Mail.

DVPEN01-SL offers 4 sets of E-Mail information, and you can self-define the register or bit information to be read. When the trigger occurs, DVPEN01-SL will add the set register or bit present value read to the E-Mail.

Every set of E-Mail information is able to contain maximum 100 continuous register data.

„

Setting up DVPEN01-SL mail

24

1. SMTP Server:

The E-Mail will first be sent to SMTP server, and SMTP server will send it to the designated address. For example, assume there is an E-Mail to be sent to [email protected], and the

SMTP server is 172.16.144.121. The E-Mail will be sent to SMTP server first, and the server will further send it to the recipient [email protected].

2. Subject of E-Mail:

You can enter text message in the column, and the message will be placed in the subject of the

E-Mail and sent to the recipient. DVPEN01-SL is able to contain 1 ~ 4 E-Mail subjects (max. 63

English characters are allowed).

You can select additional information for the E-Mail. Every set of E-Mail is able to contain 100 continuous addresses of registers.

3. E-Mail of Sender:

Maximum 63 English characters are allowed.

4. E-mail of Recipient:

You can enter 4 E-Mail addresses. One mail can be sent to 4 addresses (max. 63 English characters are allowed).

After you have set up all the parameters for the E-Mail, you will need to select recipients. The

DVP-PLC Operation Manual

Ethernet Communication Module DVPEN01-SL

E-Mail will be sent to the designated recipients when the E-Mail is triggered. To trigger E-Mail, set the value is CR#3 ~ CR#6 as “1”.

6. See “Application Examples Section 6.8” for more details.

Notes:

To correctly send out E-Mails, there has to be a SMTP server in the network. When we send out an E-Mail, the mail will be sent to SMTP server first, and the server will further send the mail to the designated address.

DVPEN01-SL is able to designate a data exchange area for PLC MPUs to exchange and synchronize their data.

„

Setting up DVPEN01-SL data exchange

Check the box to enable or disable data exchange. Start data exchange after enable it.

2. Execute Mode:

You can set it to ”Always Enable” or ”Program Control”. When set to “Always Enable”,

DVPEN01-SL will execute data exchange continuously until the setting in DCISoft is changed.

When set to “Program Control”, DVPEN01-SL will execute data exchange according to the program setting (CR#13 = 2: Execute; CR#13 = 0: Stop).

3. Communication Address & Data exchange host IP:

You have to enter the IP address of DVPEN01-SL at the other end. For example, if you would like DVPEN01-SL to exchange data with 192.168.0.1, set No. 1 as 192.168.0.1. When the data are being exchanged, if the value in CR#28 is H’0001, the data will be exchanged with

192.168.0.1.

4. Master Address & Slave address & Quantity.

Read ( Å ): Start address of the master’s receiving register Å Start address of the slave’s sending register

Write ( Æ ): Start address of the master’s sending register Æ Start address of the slave’s

DVP-PLC Operation Manual

25

Ethernet Communication Module DVPEN01-SL

receiving register

In data exchange, DVPEN01-SL will execute Write (

Æ

) first before Read (

Å

).

Quantity: A slave is able to send and receive at the same time maximum 100 consecutive data.

f For data exchange, D register is parted into 2 sections, D0000 ~ D4095 and D4096 ~ D9999.

Please DO NOT use different sections for the consecutive sent and received data (start address + number of data).

5. See “Application Examples Section 6.11” for more details.

5.6 RTU

Use the “RTU” function to conduct mapping between Delta’s network modules DVPEN01-SL and

RTU-EN01.Set up the mapping information first, and you will be able to use WPLSoft in DVPEN01-SL to save and retrieve the mapped bit (M) and register (D) in order to operate the remote RTU-EN01.

„

The settings

26

1. Enable Remote I/O Mapping:

Check the box to enable the remote I/O mapping. The mapping with remote RTU-EN01 will be enabled according to the settings.

2. Communication Parameters:

Set up “Communication Timeout” (ms) and “Update Cycle” (ms) here.

3. PLC I/O Mapping:

Set up the start address of the mapped bit and analog register (RCR) of digital input (X) and digital output (Y) on remoter RTU-EN01. The bit starts from M2000, and read/write register starts from D2000/D3000. The software will automatically calculate the end address according to the settings below.

4. Remote Device Mapping:

Check “Enable” and enter the remote RTU-EN01 ID (Slave ID), IP Address, number of digital input points (RX), number of digital output points (RY), number of mapped read registers (Read) and write register (Write).

DVPEN01-SL offers 4 slaves for mapping. Max. number of digital and analog points for mapping

DVP-PLC Operation Manual

Ethernet Communication Module DVPEN01-SL

of every slave:

Digital I/O points (RX+RY): 256

Analog (Read) register: 64

Analog (Write) register: 64

IP filter is used for restricting the connection of the network in case some uncertain IP will cause errors. Only the IP set within a certain range can establish a connection. Other IPs will be rejected.

„

Setting up IP filter

1. Enable IP Filter Function:

Check the box to enable IP filter.

2. IP:

IP addresses that are allowed to establish connections. Maximum 8 IPs are allowed.

3. Netmask:

The subnet of the IP is allowed to establish a connection. To see whether the destination IP is allowed, conduct bitwise AND operations between the allowed IP and subnet mask and destination

IP and subnet mask. If the two values obtained are the same, the destination IP is allowed by the IP filter. For example, assume the IP is 192.168.0.1 and subnet mask 255.255.255.255, the only one IP allowed to establish a connection is 192.168.0.1. If the subnet mask is 255.255.255.0, the IPs allowed to establish connections will become 192.168.0.0 ~ 192.168.0.255.

ARP (Address Resolution Protocol) is used for obtaining the MAC address corresponding to the IP address in data transmission. For example, there is a datum to be sent to 172.16.155.250, but you do not know the corresponding MAC address. You can use ARP to look up the MAC address by IP address, and the corresponding MAC address will be saved, so you do not need to look it up again when sending the next datum.

DVP-PLC Operation Manual

27

Ethernet Communication Module DVPEN01-SL

Therefore, if you do not know the MAC address, you will have to spend some time looking up the MAC address.

If you want to enhance the transmission efficiency, use static ARP table to save time. For example, assume IP:

192.168.0.1 and MAC: 00:14:22:56:0F:7F. As long as there are data sent to 192.168.0.1, you will get the MAC address from the table.

„

Setting up static ARP table

Destination IP address in data transmission.

2. MAC:

The MAC addresses corresponding to the IP address.

Note:

Incorrect settings may result in connection failure. Therefore, DO NOT set the MAC address of the equipment without the network into the table.

5.9 Setting up Password

To prevent the set values in DVPEN01-SL from being modified, you can set up password to lock the settings in DVPEN01-SL.

„

Setting up DVPEN01-SL password

28

DVP-PLC Operation Manual

Ethernet Communication Module DVPEN01-SL

Check the box to modify the password.

2. New Password:

Maximum 4 characters are allowed. Leave the column “blank” to disable the password protection function.

3. Confirm Password:

Enter the new password again.

4. See “Application Examples Section 6.4” for more details.

Note:

After the password is locked, all the pages cannot be set up unless you unlock the password.

However, if you set up DVPEN01-SL by RS-232, you can return the setting to default setting whether the password is locked or not. For example, if you have locked DVPEN01-SL but forget the password, you have to return DVPEN01-SL to factory default setting by RS-232, and all the settings will return to default ones.

5.10 Returning to Default Setting

If you need to clear all the settings after many modifications on the settings and return the settings to default ones, check the “default setting” box.

„

DVPEN01-SL returning to default setting

DVP-PLC Operation Manual

29

Ethernet Communication Module DVPEN01-SL

Check “Default Setting” box and click on “Yes”.

Note:

If you set up DVPEN01-SL by RS-232, you can return the setting to default setting whether the password is locked or not. It takes approximately 10 seconds to return to default setting, so DO NOT switch off the power within the 10 seconds.

6.1 Setting up IP and Communicating through WPLSoft

Application Setting up network parameters of DVPEN01-SL directly on the PC.

Network requirement

(1) IP of PC executing WPLSoft: 192.168.0.3

(2) Subnet mask: 255.255.255.0; Gateway: 192.168.0.1

(3) IP of DVPEN01-SL: 192.168.0.4

(4) Connect the PC and DVPEN01-SL by RJ-45 cable.

Note:

Both PC and DVPEN01-SL have to adopt static IP.

1. The connection

DVPEN01 DVP-PLC

PC

2. Open "Communication Setting” in WPLSoft.

30

DVP-PLC Operation Manual

Ethernet Communication Module DVPEN01-SL

3. Select “Ethernet” and press "OK”.

4. Click on “Auto-Search” icon to search for all DVPEN01-SL modules in the network.

5. Designate a DVPEN01-SL and double click it to open the setup page.

DVP-PLC Operation Manual

31

Ethernet Communication Module DVPEN01-SL

6. Open “Basic” setup page.

32

7. Switch to “Network” setup page

DVP-PLC Operation Manual

Ethernet Communication Module DVPEN01-SL

8. Enter IP address: 192.168.0.4; Netmask: 255.255.255.0; Gateway: 192.168.0.1. Press “OK” to complete the setup, and WPLSoft will automatically search for DVPEN01-SL.

9. The IP of DVPEN01-SL has been modified into the new setting (DELTA DVPEN01-SL:

192.168.0.4).

10. Click on DELTA DVPEN01-SL, and WPLSoft will be able to communicate with the MPU.

6.2 Connecting the PC with DVPEN01-SL through LAN

Application Setting up network parameters of DVPEN01-SL by WPLSoft through LAN.

Network requirement

(1) Connect the PC and DVPEN01-SL by using DHCP server through LAN.

(2) IP of DVPEN01-SL: 172.16.157.148

Note:

DVPEN01-SL can use RJ-45 cable with/without jump wire.

1. The connection

DVP-PLC Operation Manual

33

Ethernet Communication Module DVPEN01-SL

PC

DHCP Server

DVPEN01 DVP-PLC

PC

Hub

2. Open “Communication Setting” in WPLSoft.

3. Select “Ethernet” and press “OK”.

34

DVP-PLC Operation Manual

Ethernet Communication Module DVPEN01-SL

4. Click on “Auto-Search” icon to search for all DVPEN01-SL modules in the network. Follow “View Æ

Workspace

Æ

Communication” or “View

Æ

Workspace

Æ

Project” to find the detected

DVPEN01-SL module (default module name: DELTA DVPEN01-SL, IP: 192.168.1.5) in the window.

5. Designate a DVPEN01-SL and double click it to open the setup page.

DVP-PLC Operation Manual

35

Ethernet Communication Module DVPEN01-SL

6. Open the setup page. You can modify the module name for easier identification.

7. Next, set up the new IP of DVPEN01-SL. First switch to “Network” setup page. If there is a DHCP server in the LAN, select DHCP in “IP Configuration”. If there is no DHCP server in the LAN, you can set a static IP. Please be noted that the settings of subnet mask and gateway have to be the same as the settings in the same LAN. Press “OK” to complete the setting, and WPLSoft will automatically search for DVPEN01-SL.

8. The module name and IP of DVPEN01-SL have been modified into new settings (TEST:

172.16.157.148).

36

9. Click on DVPEN01-SL, and WPLSoft will be able to communicate with the MPU (e.g. uploading/downloading program or monitoring devices).

DVP-PLC Operation Manual

Ethernet Communication Module DVPEN01-SL

6.3 Setting up Password and Clearing Password

Application Setting up and clearing password by WPLSoft

Network requirement

(1) Set password in DVPEN01-SL

(2) Unlock DVPEN01-SL

(3) Clear the password in DVPEN01-SL

1. See 6.1 for the connection and how to set up the communication.

2. Open the setup page and switch to “Password” page.

3. Check “Modify” box and enter “aabb” in “New Password” and “Confirm Password" columns. Click on

“OK” to save the password.

4. Open the setup page again, and DVPEN01-SL is now locked by the password. You cannot open any of the settings now. Click on “Unlock” to leave the entering password window.

DVP-PLC Operation Manual

37

Ethernet Communication Module DVPEN01-SL

5. Enter the password to temporarily unlock the protection and modify the parameters. If you close the setup page, the locking will automatically be recovered.

38

6. To clear the password, simply leave the password columns blank. Click on “OK” to clear the password.

DVP-PLC Operation Manual

Ethernet Communication Module DVPEN01-SL

7. After the password is cleared, you can modify the parameters.

6.4 When the Password is Lost (Returning to Default Setting by RS-232)

Application Returning to default setting by RS-232

Network requirement

(1) DVPEN01-SL is set with a password.

(2) The password is forgotten.

1. Use DVPACAB2A30 cable to connect the PC and DVPEN01-SL and open the setup page. Open the “reset to default setting”” pages. Click on “Unlock”.

DVP-PLC Operation Manual

39

Ethernet Communication Module DVPEN01-SL

2. Check the “Default Setting” box and the “Warning” dialog box will appear. Click on “Yes” to return to default setting (in approx. 5 ~ 10 seconds), and the password will be cleared as well.

3. After the searching, all the parameters have already returned to their default settings.

6.5 IP Filter Protection

Application

Network requirement

Setting up IP filter protection

(1) IP of DVPEN01-SL: 192.168.0.4

(2) Only connections to 192.168.0.7 and 172.16.0.1~172.16.0.255 are allowed.

1. See 6.1 for the connection and how to set up the communication.

2. Open the setup page and switch to “IP Filter” page.

40

DVP-PLC Operation Manual

Ethernet Communication Module DVPEN01-SL

3. Check “Enable IP Filter Function” box. Enter “192.168.0.4” in No. 1 IP and “255.255.255.255” in all

“Netmask” columns.

4. Enter “192.168.0.1” in No. 2 IP and “255.255.255.0” in No.2 “Netmask” column. Click on "OK” to complete the setting. Only the equipment within the IP range can be connected.

DVP-PLC Operation Manual

41

Ethernet Communication Module DVPEN01-SL

6.6 Setting up Static ARP Table

Application

Network requirement

Setting up static ARP table

(1) MAC address of equipment 192.168.1.6 is 00:18:23:10:00:35

(2) MAC address of equipment 192.168.1.1 is 00:18:23:10:00:04

1. See 6.1 for the connection and how to set up the communication.

2. Open the setup page and switch to “Static ARP Table” page.

42

3. Check “Enable ARP Table” box. Enter “192.168.1.6” in No. 1 IP, and its corresponding MAC address is “00:18:23:10:00:35”.

DVP-PLC Operation Manual

Ethernet Communication Module DVPEN01-SL

4. Enter “192.168.1.1” in No.2 IP, and its MAC address is “00:18:23:10:00:04”. Click on “OK” to complete the setting. Only the equipment within the IP range can be connected.

Note:

The MAC address of DVPEN01-SL can be obtained from WPLSoft or the MAC address sticker on the equipment. The MAC address of PC can be found in the “Network Connection Details” (see below).

DVP-PLC Operation Manual

43

Ethernet Communication Module DVPEN01-SL

6.7 Application of E-Mail

Application

Network application

Sending an E-Mail to notify the administrator when the current status of X0 and Y0 is changed.

(1) SMTP Server IP: 172.16.144.121

(2) E-mail address of administrator: [email protected]

(3) An E-mail message will be generated when the status of X0 and Y0 is changed.

1. See 6.1 for the connection and how to set up the communication.

2. Open the setup page and switch to "Mail” page.

44

3. In “Subject and Mail” page, enter the address of SMTP server, subject of E-Mail, and E-mail address of the recipient. E-mail address of the recipient, and the present value and the number of data for D,

T, C registers.

DVP-PLC Operation Manual

Ethernet Communication Module DVPEN01-SL

4. Switch to “Select Recipients” page. Check all the boxes of “Recipient 1”. Click on “OK” to complete the setting.

5. After all the settings in DVPEN01-SL are completed, compile the ladder diagram in the MPU and download it to the MPU. See below for the program design:

X0

T0 K100 K3 K1 K1

X0

T0 K100

K4

K1 K1

Y0

T0 K100 K5 K1 K1

Y0

T0 K100 K6 K1 K1

END

Explanations:

If the rising-edge of X0 is triggered, X0 will go from Off to On. Write “1” into CR#3 of

DVPEN01-SL, and the first E-Mail will be sent out.

If the falling-edge of X0 is triggered, X0 will go from On to Off. Write “1” into CR#4 of

DVPEN01-SL, and the second E-Mail will be sent out.

If the rising-edge of Y0 is triggered, Y0 will go from Off to On. Write “1” into CR#5 of

DVPEN01-SL, and the third E-Mail will be sent out.

If the falling-edge of Y0 is triggered, Y0 will go from On to Off. Write “1” into CR#6 of

DVPEN01-SL, and the fourth E-Mail will be sent out.

6.8 Application of Data Exchange (1)

Application

Network requirement

Writing the time in RTC in PLC_B into D0 ~ D6 of PLC_A

(1) Adopting static IP.

(2) IP of PLC_A: 192.168.0.4

(3) IP of PLC_B: 192.168.0.5”

(4) Update from PLC_B to PLC_A

DVP-PLC Operation Manual

45

Ethernet Communication Module DVPEN01-SL

1. See 6.1 for how to set up the communication.

2. Open the setup page of PLC_B and switch to “Data Exchange” page.

3. Check “Enable Data Exchange” box. Select “Program Control” for Execute Mode. Enter IP address of

PLC_A “192.168.0.4” in No. 1 Data Exchange Host IP column. Click on “OK” to complete the setting.

46

4. After all the settings in PLC_B are completed, compile the ladder diagram in the MPU and download it to PLC_B. See below for the program design:

DVP-PLC Operation Manual

Ethernet Communication Module DVPEN01-SL

M1000

D100

M1013

M2 M1

M1

SET M1

TOP

K100

TOP K100

TOP K100

TOP K100

K28

K29

K14

K13

K1

D100

K0

K1

K1

K7

K1

K1

M2

SET

RST

M2

M1

FROM K100 K14 D14 K1

= D14 K2

RST

RST

M2

M2 = D14 K3

END

Explanations:

The data exchange will be executed every one second.

Write the communication address of the destination PLC in CR#28, and DVPEN01-SL will automatically detect by the previous setting that No. 1 IP is “192.168.0.4".

Write the data in RTC into CR#29 ~ CR#35.

Write “1” into CR#13 to start the data exchange.

CR#14 = 2 refers to successful exchange. CR#14 = 3 refers to failed exchange.

5. Compile the ladder diagram for PLC_A and download it to PLC_A.

M1013

FROM K100 K49 D0 K7

END

Explanations:

The received data are stored in CR#49 ~ CR#55.

The data received every one second are written into D0 ~ D6.

DVP-PLC Operation Manual

47

Ethernet Communication Module DVPEN01-SL

6.9 Application of Data Exchange (2)

Available in firmware V2.0 and later versions

Application

Network requirement

“Always Enable” Data Exchange. Enable a timer and write the timer values into D0 ~ D99.

Continue to write the present values in D0 ~ D99 of PLC_A into D0 ~ D99 of PLC_B, and write the values in D0 ~ D99 of PLC-B into D200 ~ D299 of PLC_A.

(1) Adopting static IP.

(2) IP of PLC_A: 192.168.1.99

(3) IP of PLC_B: 192.168.1.97”

(4) Update from PLC_A to PLC_B and PLC_B to PLC_A.

1. See 6.1 for how to set up the communication.

2. Open the setup page of PLC_A and switch to “Data Exchange” page.

4. Check “Enable Data Exchange” box. Select “Always Enable” for Execute Mode. Enter IP address of

PLC_B “192.168.1.97”, D200 Å D0 Quantity: 100 and D0 Æ D0 Quantity: 100 in No. 1 Data Exchange

Host IP column. Click “OK” to complete the setting.

48

5. After all the settings in PLC_A are completed, compile the ladder diagram in the MPU and download it to PLC_A. See below for the program design:

DVP-PLC Operation Manual

Ethernet Communication Module DVPEN01-SL

6.10 Application of Data Exchange (3)

Available in firmware V2.0 and later versions

Application

Network requirement

Enable a timer (X20) and write the timer values into D0 ~ D99. Control the program (X21) and write the present values in D0 ~ D99 of PLC_A into D0 ~ D99 of PLC_B, and write the values in D0 ~ D99 of PLC-B into D200 ~ D299 of PLC_A. Control the program (X21) to stop the execution.

(1) Adopting static IP.

(2) IP of PLC_A: 192.168.1.99

(3) IP of PLC_B: 192.168.1.97”

(4) Update from PLC_A to PLC_B and PLC_B to PLC_A.

1. See 6.1 for how to set up the communication.

2. Open the setup page of PLC_A and switch to “Data Exchange” page.

3. Check “Enable Data Exchange” box. Select “Program Control” for Execute Mode. Enter IP address of

PLC_B “192.168.1.97”, D200

Å

D0 Quantity: 100 and D0

Æ

D0 Quantity: 100 in No. 1 Data Exchange

Host IP column. Click “OK” to complete the setting.

DVP-PLC Operation Manual

49

Ethernet Communication Module DVPEN01-SL

After all the settings in PLC_A are completed, compile the ladder diagram in the MPU and download it to PLC_A. See below for the program design:

6.11 Application of Data Exchange (4)

Application

Network requirement

Writing the time in RTC in PLC_B into D0 ~ D6 of PLC_A by designating IP by ladder diagram.

(1) Adopting static IP.

(2) IP of PLC_A: 192.168.0.4

(3) IP of PLC_B: 192.168.0.5

(4) Update from PLC_B to PLC_A

1. See 6.1 for how to set up the communication. Compile the ladder diagram in the MPU and download it to PLC_B. See below for the program design:

50

DVP-PLC Operation Manual

Ethernet Communication Module DVPEN01-SL

M1000

M1013

M2

M1

M1

D100

M1 SET

TOP K100 K28

TOP

TOP

K100

K100

TOP K100

TOP K100

TOP K100

K0 K1

K26 HC0A8

K25

K29

H4

D100

K14

K13

K0

K1

K1

K1

K7

K1

K1

M2

= D14 K2

= D14 K3

SET

RST

M2

M1

FROM K100

RST

RST

M2

M2

K14 D14 K1

END

Explanations:

The data exchange will be executed every one second.

Write “0” into CR#28, and PLC_B will use CR#25 ~ CR#26 as the IP address of the destination

PLC.

Write the IP address of PLC_A into CR#25 and CR#26. The first two IP codes (192.168 =

H’C0A8) should be written into CR#26, and the last two IP codes (0.4 = H’0004) into CR#25.

Write the data in RTC into CR#29 ~ CR#35.

Write “1” into CR#13 to start the data exchange.

CR#14 = 2 refers to successful execution. CR#14 = 3 refers to failed execution.

2. Compile the ladder diagram for PLC_A and download it to PLC_A.

M1013

FROM K100 K49 D0 K7

END

Explanations:

The received data are stored in CR#49 ~ CR#55.

The data received every one second are written into D0 ~ D6.

DVP-PLC Operation Manual

51

Ethernet Communication Module DVPEN01-SL

52

6.12 Application of Data Exchange (5)

Application

Network requirement

Writing the time in RTC in PLC_B directly into D0 ~ D6 of PLC_A without writing in ladder diagram into PLC_A.

(1) Adopting static IP.

(2) IP of PLC_A: 192.168.0.4

(3) IP of PLC_B: 192.168.0.5

(4) Update from PLC_B to PLC_A.

1. See 6.1 for how to set up communication.

2. Compile the ladder diagram in the MPU and download it to PLC_B. We do not need to write any corresponding ladder diagram into PLC_A.

M1000

D100

M1013 M2 M1

SET M1

M1

TOP K100 K28 K0 K1

TOP K100 K26 HC0A8 K1

TOP K100

TOP K100

TOP K100

TOP K100

K25 H4

K81 H1000

K84 H1000

K85 K7

K1

K1

K1

K1

TOP K100 K86 H1064 K1

TOP K100

TOP K100

K14

K13

K0

K1

SET M2

RST M1

M2

FROM

K100

K14 D14

= D14 K2

= D14 K3

RST

RST

END

M2

M2

Explanations:

The data exchange will be executed every one second.

K1

K1

K1

DVP-PLC Operation Manual

Ethernet Communication Module DVPEN01-SL

Write “0” into CR#28, and PLC_B will use CR#25 ~ CR#26 as the IP address of the destination

PLC.

Write the IP address of PLC_A into CR#25 and CR#26. The first two IP codes (192.168 =

H’C0A8) should be written into CR#26, and the last two IP codes (0.4 = H’0004) into CR#25.

Write the Modbus address of D0 (H’1000) in PLC_A into CR#81 and CR#84.

Write the Modbus address of D100 (register of RTC) (H’1064) into CR#86.

Write the number of registers K7 into CR#85.

Write “1” into CR#13 to start the data exchange.

CR#14 = 2 refers to successful execution. CR#14 = 3 refers to failed execution.

Once the data exchange is successful, the values in D1313 ~ D1318 in PLC_B will be written into

D0 ~ D6 of PLC_A.

6.13 Application of Modbus TCP Master

Application Compiling Modbus instruction by PLC_B, making Y0 of PLC_A flashing

Network requirement

(1) Adopt static IP.

(2) IP of PLC_A: 192.168.0.4

(3) IP of PLC_B: 192.168.0.5

(4) Update from PLC_B to PLC_A

(5) Use Modbus instruction 050500FF00 to set “On” Y0.

(6) Use Modbus instruction 0505000000 to set “Off” Y0.

(7) Y0 goes between On/Off once every one second.

1. See 6.1 for how to set up the communication.

2. Compile the ladder diagram in the MPU and download it to PLC_B. See below for the program design.

We do not need to write any corresponding ladder diagram into PLC_A.

M1013 M2 M1

SET M1

M1

TOP K100 K118 HC0A8 K1

TOP K100 K117 H4 K1

= D0 K0

= D0 K1

TOP

TOP

TOP

TOP

TOP

TOP

TOP

K100 K111

K100 K120

K100 K121

K100 K122

K100 K123

K100 K124

K100

K124

K1

H0

H5

H5

H0

HFF

H0

K1

K1

K1

K1

K1

K1

K1

DVP-PLC Operation Manual

53

Ethernet Communication Module DVPEN01-SL

= D0 K2

TOP

TOP

K100 K125

K100 K119

TOP

TOP

INC

K100 K116

K100

D0

K115

MOV

SET

K0

M2

D0

H0

K6

K0

K1

K1

K1

K1

K1

M2

RST M1

FROM K100 K116 D14 K1

= D14 K2

RST M2

= D14 K3

RST M2

END

Explanations:

The data exchange will be executed every one second.

Write the IP address of PLC_A into CR#117 and CR#118. The first two IP codes (192.168 =

H’C0A8) should be written into CR#118, and the last two IP codes (0.4 = H’0004) into CR#117.

Set CR#111 as “1” to enable the 8-bit mode. The Modbus instruction is stored in the low byte of

CR#120 ~ CR#247.

Write Modbus instruction into CR#120 ~ CR#125. CR#120 is the Modbus address.

Write the length of the instruction into CR#119.

Write “1” into CR#115 to start the execution of Modbus TCP instruction.

CR#116 = 2 refers to successful execution. CR#116 = 3 refers to failed execution.

If the execution is successful, Y0 on PLC_A will go between On and Off every one second.

6.14 RTU Mapping

Application

Network requirement

Using RTU mapping to read/write the remote digital I/O and analog I/O registers.

DVP28SV+DVPEN01-SL Æ RTU-EN01+DVP06XA+DVP16SP

(1) Adopt static IP.

(2) IP of DVPEN01-SL: 192.168.1.90

(3) IP of RTU-EN01: 92.168.1.91

(4) Use DCISoft for RTU-EN01and check 10 mapping data for read and 10 mapping data for write.

(5) Set up the mapping start address and number of data for RX, RY, RCR (read) and RCR

(write) at DVPEN01-SL.

(6) Enable the mapping function in DVP-SV PLC at DVPEN01-SL. Use M2000 and D2000 in DVP-SV to read and M3000 and D3000 to write the value in the remote RTU-EN01.

54

DVP-PLC Operation Manual

Ethernet Communication Module DVPEN01-SL

1. See 6.1 for how to set up the communication.

2. Use DCISoft for RTU-EN01 to set up the mapping CR for read/write.

3. Use DCISoft for DVPEN01-SL to set up the mapping start address and number of data. RX: M2000 ~

M2009, RY: M3000 ~ M3009, RCR Read: D2000 ~ D20009, RCR Write: D3000 ~ D3009

4. Edit the ladder diagram in the MPU and download it to DVPEN01-SL. See the program design as shown below:

DVP-PLC Operation Manual

55

Ethernet Communication Module DVPEN01-SL

Explanations:

1. Enable mapping: CR15 = 1

2. Disable mapping: CR15 = 0

3. Once CR#15 is enabled, M2000 ~M2009 and D2000 ~ D2009 will read the data, and M3000 ~ M3009 and D3000 ~ D3009 will read the present value before starting to write.

4. During the execution of mapping, other devices are not allowed to modify the value in the mapped register.

56

DVP-PLC Operation Manual